Polymobil Plus Merged
Polymobil Plus Merged
SP
Service Instructions
From Serial-No. 10100
© Siemens AG 2000
The reproduction, transmission or
use of this document or its contents
is not permitted without express
written authority. Offenders will be
liable for damages. All rights,
including rights created by patent
grant or registration of a utility
model _or_ design,_are_ reserved.
English
Print No.: SPR8-125.061.02.01.02 Release Date: 01.00
Replaces: n.a.
0-2 Revision
Letzte
Seite
Kapitel
des
Page
1 _______Prerequisites ___________________________________________________ 1-1
Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
Position and function of the LEDs, fuses, test points and potentiometers. . . . . . . . 2-4
D915 CPU, control and measurement value acquisition . . . . . . . . . . . . . . 2-4
D925 Rotating anode starter, filament inverter, ON/OFF switching circuit . . . . . 2-5
U1 power supply unit 5 V ± 5% / 15 V ± 10 %. . . . . . . . . . . . . . . . . . . . 2-6
U2 power supply unit 12.5 V ± 10 %. . . . . . . . . . . . . . . . . . . . . . . . . 2-6
D950 capacitor charging circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-7
D970 Capacitor bank . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-7
Status of the LED’s (optimum condition) . . . . . . . . . . . . . . . . . . . . . . 2-8
3 _______Troubleshooting_________________________________________________ 3-1
Page
Measuring the filament nominal value . . . . . . . . . . . . . . . . . . . . . . . 5-13
Setting the tube current for the exposure . . . . . . . . . . . . . . . . . . . . . . 5-13
Testing and setting the mAs counter . . . . . . . . . . . . . . . . . . . . . . . . . . 5-15
Coincidence of light and radiation fields . . . . . . . . . . . . . . . . . . . . . . . . 5-16
Testing and readjusting the counterbalance . . . . . . . . . . . . . . . . . . . . . . 5-19
Readjusting the counterbalance with accessories attached . . . . . . . . . . . . . . 5-19
Letzte
Seite
des
Kapitel
0
Text emphasis 1
Required documents 1
The tools, measurement and auxiliary devices required, with the exception of the standard
service equipment and the current transformer, are listed in part 3 of the ARTD.
R3 R4
R5
C1
VCC
+ -
Fig. 1
• Connect the POLYMOBIL Plus only to a line voltage supply (line voltage receptacle) that
complies with the requirements of VDE 0107, or corresponds to the local national
regulations.
• Disconnect the POLYMOBIL Plus at the line voltage OFF switch on the operating
console and disconnect the line voltage plug prior to any service work.
• Remove or insert boards with the generator switched OFF only; observe
ESD guidelines when handling boards.
• Damaged or missing screws may only be replaced by steel screws as specified in the
installation drawings conforming to DIN267 and must have the specified tensile strength.
CAUTION All Allen screws must have a tensile strength rating of 8.8.
Cleaning 1
Preparation 2
R3 R4
R5
C1
VC C
+ -
Fig. 1
Fig. 2 Fig. 3
To check the assemblies, remove the upper covers, the handles and the lower front cover
of the switchbox.
Proceed as follows:
• Switch POLYMOBIL Plus OFF and disconnect the line voltage plug.
• Remove the 4 Allen screws (1/Fig.2) in the handle and remove the handle
(refer to Fig.2 and Fig.3).
2
4
3
Fig. 4 Fig. 5
• Remove the four Allen screws at the bottom of the switchbox cover (2/Fig.4) and remove
the cover.
• After removing the four panel screws (3/Fig.4), remove the bottom cover at the front with
the cassette tray.
WARNING Always measure the actual voltage present with the DVM at test
points -VCC and + VCC on the D 960 inverter board or (more
accessible) on the D 970 capacitor board at the + connection
point of capacitor C3 and on the right side of fuse F3.
LED:
V22 Preparation ON
V23 Exposure ON
V24 Error occurred
V25 not used
V34 Radiation ON
Test points:
X15 Pin Color
1 black Ground (+ 5 V)
3 black Ground (+ 5 V)
4 red + 5 V ± 5%
5 brown +15 V ± 10 %
6 blue Ground (+/- 15 V)
7 yellow -15 V ± 10 %
Potentiometers:
P1 Setting of the mAs counter
P2 OFFSET mAS - converter
Set at the factory - Do not change!
P3 Max. filament inverter frequency
P4 Max. main inverter frequency
P5 Adjustment/setting of filament heating circuit
P6 Nominal filament current (standby and ZB), nominal tube current
(exposure)
Set at the factory - Do not change!
P7 Nominal kV value
SW2
P6 P7 X12
D 915 V22 V23 V24 V25
P5 X15
P4 ST
P3
P2 V34 Service
P1 X11 X10 X20
1 1 1
GND JR REG CAL KVP KV KVN IH JRS KVS F1 I I1 I2 TRG JIM SCH GND VC BAT KVM SCM VR
Fig. 6
LED:
Fuses:
X4 Pin Color
1 red +12.5 V ± 10 %
2 red +12.5 V ± 10 %
3 red +12.5 V ± 10 %
4 black Ground (+12.5 V)
5 black Ground (+12.5 V)
6 black Ground (+12.5 V)
Fuse: 2 A T
Fuse: 5 A T
LED:
Fuse:
F1 10 AT Charging circuit
Test points:
LED:
Fuse:
Test points:
D950: LED 450 Vcc (V30) glows for 10 minutes following shutdown
D925: LED VP ON
LED +12 V ON
LED I/O ON
LED AR ON
LED +DC ON
LED -DC ON
c) Preparation
All LED’s as described under b) and also V22 on D915.
d) Exposure
All LED’s as described under b) and also V22 and V23 as well as radiation indicator V34
on D915.
In case of an error, V24 on D915 glow (red).
Error messages 3
NOTICE Error messages Err 1, and initialization errors Err 90, Err 96 and
Err 97 block the generator so that the system must be switched
off and switched back on again.
"StandBy" error messages disappear when the error is cleared.
Error messages which occur during an exposure will continue
flashing until another key is activated.
a) During initialization
b)During stand by
c)During exposure
Err 5 KVact ≠ 0
- No connection to the single tank generator (D915 X8)?
- Plug-in connection on D900 in the single tank generator ok?
Err 6 mAact ≠ 0
- Error in the measurement acquisition on D915? => Replace D915 .
- No connection to the single tank generator (D915 X8)?
- Plug-in connection on D900 in the single tank generator ok?
Err 7 Rot ≠ 0 (rotating anode speed ≠ 0)
- Error on D915 or D925.
Err 8 Braking failure (error when braking the rotating anode - a current was
measured in the auxiliary capacitor C2 during the braking.)
- D915TP ’I1’. No current must be measured here when braking.
- D915 TP ’I2’. Braking current must be measured here.
- TRIAC ’V7’ or ’V8’ defective? => Replace D925.
Err 9 Pressure switch (oil pressure switch in the single tank generator is
active)
- Tube is overheated?
- Measure D915 plug X8 at pin 8. In case of malfunction, 0V are measured.
Err 10 Rot = 0 (rotating anode speed is 0 on exposure)
The error is only displayed as long preparation is depressed.
- LED ’AR’ on D925 flashes ; is fuse F5 ok?
- Measure at TP ’I1’ and ’I2’. Current has to be present during acceleration.
- Check D925.
- Is the power factor correction capacitor C2 defective?
- Connection to/in the single tank generator ok?
Err 11 Short circuit in main inverter
- Check D960 .
- Check D915 .
- Main inverter frequency too high?
Err 12 KVmax
- Interruption of KVact measurement. Measure TP ’KVN’ and ’KVP’ on D915.
Both signals must have the same amplitude.
- ’KVN’ or ’KVP’ > 70 kV.
- Error in kV measurement circuit?
- Error in kV control circuit?
Err 13 Imax
The tube or filament current is recorded.
- Check the filament circuit.
- Exposure filament basic value incorrectly set (P5 on D915)?
- Tube arcing?
If kVact < kVnom, Err 14 or Err 13 is detected and displayed. Refer also to the
troubleshooting information under Err 14.
Err 14 KVact < KVnom
- Voltage in the capacitor bank too low (D950 TP ’VC’)?
- Defective capacitors /fuses on the capacitor bank (D970)?
- No KVact?
- Error in the measurement circuit on D915?
- Main inverter frequency too low?
- Defect in the main inverter D960?
Err 15 mAACT < mANOM
- Check the filament circuit.
2
SW2
P6 P7 X12
D 915 V22 V23 V24 V25
X15
P5
P4 ST
"OPEN"
P3
P2 Service
GND JR REG CAL KVP KV KVN IH JRS KVS F1 I I1 I2 TRG JIM SCH GND VC BAT KVM SCM VR
Fig. 1
To bypass the service mode, the ST slot (1/Fig.1, below the display on D915) has to be
jumpered before switching on the POLYMOBIL Plus.
As soon as "Pr. 1" appears in the display, bring the jumper back to the "OPEN" position.
mAs +/- Setting of the mAs values in "Pr. 5" and "Pr. 6".
To quit the service mode, switch the POLYMOBIL Plus off/on or press the Reset button
SW 2 (2/Fig.1).
Line voltage 5
The line voltage must be set between 110 V ( + 10%) or 230 V ( + 10%).
The line voltage is adjusted automatically.
Fig. 1
Charging frequency 5
Fig. 2
Fig. 3
The charging current is dependent on the line voltage present and the charge sta-
tus(capacitor voltage Uc) of the capacitor bank.
Fig. 3 shows the charging current in standby, i. e. when the C-bank is charged.
The charging time depends upon the residual charge of the capacitor bank and on the
available line voltage, e.g. with 230 V the max. charging time is about 15 s.
In the worst case, ( line voltage <100 V and residual charge = 0V), charging time
can take 40 seconds.
For the following measurement, the line voltage was 230 V and the residual charge 30 V.
Fig. 4
Acceleration 5
Fig. 5 shows the stator currents during rotating anode acceleration (230 V).
Fig. 5
Fig. 6
kV Control 5
5 V/Div.
20 µs/Div.
0→
FMAX = 18 kHz
TMIN = 55.5 µs Tolerance: -1.5 µs /+1.5 µs
Fig. 7
• Switch OFF POLYMOBIL Plus and wait until the capacitor voltage has dropped to a
value < 10 V.
• Disconnect the cable from the inverter to capacitor C1 and push the cable through the
current transformer 50 A : 50 mA (with a parallel resistor of 10 ohms) and connect the
cable again.
• Connect the oscilloscope to the current transformer.
• Switch ON POLYMOBIL Plus .
• Set 60 KV, 10 mAs on POLYMOBIL Plus and release exposure.
The diagram must correspond to Fig 8.
Fig. 8
Fig. 9
Fig. 10 shows that one kVact cable from the single tank generator to the D915 is damaged
or disconnected.
The monitor (KVM) responds (curve 3) because KVN and KVP have different amplitudes;
the exposure is terminated with ERR 12.
Refer to function description "KV monitoring".
Fig. 10
Fig. 11
The maximum filament inverter freqency is 25 kHz and can be set with P3 on D915.
Proceed as follows:
• Switch POLYMOBIL Plus OFF.
• Remove fuse F6 on D925.
• Connect the oscilloscope to D915 at TP "CAL" and "GND".
• Switch POLYMOBIL Plus ON (Err 03 is blinking).
The oscillogram must appear like the one in Fig. 12.
Fig. 12
The filament nominal value is set at the factory and should not be changed.
The filament nominal value can be measured on D915 at TP "JRS" and "GND" with the
DVM and is 1.5 V ± 4% in standby.
NOTICE If this value is changed, the nominal values for preparation and
exposure are also affected.
Fig. 13
If this is not the case, adjust P5 on D915 until there is minimal current overshoot at the
beginning of the exposure.
The standby heating of the exposure is set via P5 ( IH , IH ).
Fig. 13 shows the correct setting.
In Fig. 14 the standby heating is set too high.
In Fig. 15 the standby heating is set too low.
3
Ch1 1.00V M20.0ms Ch1 1.56V
Ch3 500mV
Standby heating too high
Fig. 14
Length
Marker
Side marker
Fig. 16
Procedure:
• Insert film into the 24 cm x 30 cm or 10” x 12” cassette and place it on a table or similar
surface.
• Adjust the vertical SID of 100 cm or 40” to the top edge of the cassette using a measuring
tape.
• Use the knobs to set a format of 18 cm x 24 cm or 8” x 10”.
• Switch on the light localizer and align the cassette.
• Apply radiopaque markers (e.g. washers, coins) as shown in Fig. 16 .
Use one washer as a side marker.
• Release an exposure (60 kV, 10 mAs) and develop the film.
• Log the following data on the developed film using a water-resistant felt-tip pen.
- SID setting
- Film size
- Radiation field size
Y1
Film
Light field
X2 X1
Radiation field
Y2
Fig. 17
• The deviations in length (total Y) as well as the deviations in width (total X) must be
smaller than 1.6 cm respectively.
Fig. 18 Fig. 19
• If the deviation is larger, loosen the 4 Allen screws a little ( arrow /Fig.18/19) and shift the
collimator accordingly.
After adjusting the collimator, tighten the screws again (arrow / Fig.18/19).
• Repeat the test and readjust the collimator until the light and radiation fields are within
the acceptable tolerance (< 1.6 cm).
1
2
Fig. 20 Fig. 21
• Loosen the rotating knob (2/Fig.20) and unlock the C-arm (1/Fig.20).
It should be possible to move the C-arm without any attached accessories easily across
the whole range and the arm should come to a stop in any desired position.
If the C-arm with accessories attached does not come to a stop in any desired position,
readjust the spring tension for the counterbalance.
• Remove the cover (3/Fig.20) at the stand.
• Release the supplemental brake at the C-arm (2/Fig.20) completely.
• Move the C-arm into a vertical position.
• Tighten the screw using a 17 mm Allen key (4/Fig.21).
Adjust the spring tension in such a way, that there is a balance when the C-arm is in a
vertical position, i.e. that equal force is required to lift and lower the tube assembly.
Fig. 1 Fig. 2
To replace the single tank generator, remove it from the stand as described in the follow-
ing:
• Remove the collimator (refer to “Replacing the collimator”).
• Move the arm into the lowest position and check whether the safety mechanism (bolt 1 /
Fig. 1) is locked into position.
Now the stand cannot be moved upwards.
• Remove the four Allen screws of the single tank generator cover (2/Fig.2), remove the
cover, disconnect the connections and the strain relief of the corrugated tubing (3/Fig.2)
and remove it.
Fig. 3
• Take out one of the four mounting screws and insert it into the threaded hole and tighten
it (arrow/Fig.3).
WARNING This is a safety device to prevent the arm of the unit from flying
upward if the lever for the transport lock is inadvertantly
activated.
Fig. 4 Fig. 5
• Attach the new collimator with the four screws (arrow /Fig.4/5) and center it.
• Reconnect the cables and the back panel.
• Check the coincidence of the light and radiation fields and adjust, if required.
(Refer to “Coincidence of light and radiation field”, page 5-15.)
9 10
7
8 11
Fig. 6 Fig. 7
• The replacement light localizer lamp is located below the cassette module.
• Turn both knobs (8/Fig.6) to the end position and remove them.
• Remove the front panel after removing both screws (7/Fig.6) .
Caution: The front panel is connected to the collimator via a cable (9/Fig.7).
• Remove both screws (10/Fig.7) and take off the metal bracket for the temperature
switch).
• Take out the defective lamp (11/Fig. 7) and replace it with a new lamp.
Fig. 8
Step:
1 Loosen only Allen screws on the left and right (2.5 mm wrench.
2 Pull back hexagonal shaft
3 Remove pedal
4 Remove Allen screws (wrench size 6 mm).
5 Pull out the caster.
6 Align the threaded holes on the new caster.
R3 R4
R5
C1
VCC
+ -
Fig. 9
2
R3 R4
R5
C1
1
VCC
+ -
1
2
Fig. 10 Fig. 11
POLYMOBIL Plus
SP
Maintenance Instructions
System
POLYMOBIL Plus
© Siemens AG 2005
The reproduction, transmission or use
of this document or its contents is not
permitted without express written
authority. Offenders will be liable for
damages. All rights, including rights
created by patent grant or registration
of a utility model or design, are
reserved.
Disclaimer
The installation and service of equipment described herein is to be performed by qualified
personnel who are employed by Siemens or one of its affiliates or who are otherwise
authorized by Siemens or one of its affiliates to provide such services.
Assemblers and other persons who are not employed by or otherwise directly affiliated
with or authorized by Siemens or one of its affiliates are directed to contact one of the
local offices of Siemens or one of its affiliates before attempting installation or service pro-
cedures.
0 Table of Contents
1 _______ General ________________________________________________________ 4
Required documentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Required tools, measurement and auxiliary equipment . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Required lubricant . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Text emphasis . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Safety information and protective measures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Explanation of abbreviations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Information on the protective conductor resistance test . . . . . . . . . . . . . . . . . . . . . . . . . 12
Information on the device leakage current measurement . . . . . . . . . . . . . . . . . . . . . . . 14
Technical Safety Checks (TSC) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Visual inspection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Checking for signs of damage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Labels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Customer documents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Checking the screws . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Checking the handles . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Checking the wheels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Checking the pedal positions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Single tank . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Double-slot diaphragm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Stand . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Radiation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Control console. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Protective conductor test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Device leakage current measurement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
DAP measuring system (optional) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Final Work Steps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Please observe:
¹ the product-specific safety information in these instruc-
tions
¹ the general safety information in the document
TD00-000.860.01... and
¹ the safety information according to ARTD part 2.
Fig. 2:
DANGER When working on the open unit there is a risk of electrical shock!
Non-compliance can lead to injuries or death.
• Connect the Polymobil Plus only to a line voltage supply (line voltage receptacle) that
complies with the requirements of VDE 0107 or corresponds to the local national regu-
lations.
• Disconnect the Polymobil Plus at the line voltage OFF switch on the operating console
and disconnect the line voltage plug prior to performing any service work.
• Remove or insert boards with the generator switched OFF only; observe ESD guide-
lines when handling boards.
Abbrev. Explanation
SI Safety Inspection
SIE Electrical Safety Inspection
SIM Mechanical Safety Inspection
PM Preventive Maintenance
PMP Preventive Maintenance Preventive Parts Replacement, External Inspec-
tion, etc.
PMA Preventive Maintenance Adjustments
PMF Preventive Maintenance, Function Check, Operating Value Check
Q Quality Check
QIQ Image Quality Check
QSQ System Quality Check
SW Software Maintenance
The items identified by these abbreviations are contained in the Maintenance Protocol
and should be checked off upon completion.
NOTE For evaluation, the value first measured and values documented
during previous maintenance or safety checks are to be compared
to the measured values. A sudden increase of the measured val-
ues, even if the limit value of 0.2 Ohm is not exceeded, indicates
errors in the protective conductor connection (protective conduc-
tor or contacts).
Measurement is to be carried out according to DIN VDE 0751, part 1 (see ARTD part 2).
In doing so, the protective conductor resistance to all conductive and accessible parts is
to be measured in the normal operating status of the unit.
Make sure that control or data cables between components of the unit do not simulate a
protective conductor connection.
During measurement, the power supply cable and additional connection cables with inte-
grated protective conductor are to be moved section by section in order to detect breaks
in the cables.
The protective conductor resistance must not exceed 0.2 Ohm.
Fig. 3: Measuring circuit for measuring the protective conductor resistance for units that are
disconnected from power, in compliance with DIN VDE 0751-1/2001-10, Fig. C2.
Pos. 1 = System
Pos. 2 = Application part type B (if available)
Pos. 3 = Measurement setup (integrated into measuring device)
The values that were determined are to be logged and evaluated in the report “Protective
conductor resistance / report” by indicating the measuring points.
In addition, the measuring procedure and the measuring device used (designation and
serial number) are to be documented.
Observe the instructions in the “Safety rules for installation and maintenance”
(ARTD-002.731.17...).
Measurement
Measurement is to be carried out according to DIN VDE 0751, part 1 (see
ARTD-002.731.17...) and the determined value is to be logged.
The measuring method indicated in the report is to be used for this.
If the value first measured needs to be determined again (see instructions above), either
direct measurement or differential measurement can be selected.
Measuring the device leakage current according to the differential current method (mea-
suring setup according to (Fig. 4 / p. 15)) is the preferred method, as the person carrying
out the measurement or other persons are not endangered during the measurement.
However, observe the minimum resolution of the leakage current measuring device and
additional manufacturer specifications which limit usage of the measuring device.
Fig. 4: Measuring circuit for measuring the leakage current according to the differential current
method in compliance with DIN VDE 0751-1/2001-10, Fig. C6 for protection class I.
Pos. 1 = System
Pos. 2 = Application part type B (if available)
Pos. 3 = Measurement setup (integrated into measuring device)
If direct measurement of the device leakage current is used (measuring setup according
to (Fig. 5 / p. 16)), the system must be installed in an insulated way and must not be
touched during measurement.
Fig. 5: Measuring circuit for direct measurement of the leakage current in compliance with DIN
VDE 0751-1/2001-10, Fig. C5 for protection class I.
Pos. 1 = System
Pos. 2 = Application part type B (if available)
Pos. 3 = Measurement setup (integrated into measuring device)
The unit must be switched on during measurement. Therefore, measuring devices with
automated measuring procedure must be set to manual measuring.
The highest value must be entered into the report “Device leakage current / report”.
This value must not exceed the permissible leakage current values according to DIN VDE
0751-1/2001-10, Table F.1, line “Device leakage current for units according to remarks 1
and 3”, of 2.5 mA.
The actual mains voltage is to be measured and logged. If the measured mains voltage
deviates from the nominal voltage, the measuring value is to be corrected to the value
which corresponds to a measurement with the nominal value of the mains voltage. This is
to be additionally documented.
The measuring method (differential measurement or direct measurement) and the mea-
suring device used (designation and serial number) are to be documented.
NOTE For evaluation, the value first measured and the values document-
ed during previous maintenance or safety tests are to be com-
pared with the measured values. A sudden increase of the
measured values, even if the limit value of 2.5 mA is not exceeded,
indicates errors in the primary circuit of the mains voltage supply
(insulation damages, damages due to dampness, faulty suppres-
sor element or similar).
The report “Device leakage current / report” is to be filed in the “Certificates” register in the
system folder.
NOTE The report “Device leakage current / report” is filed in the “Certifi-
cates” register in the system folder.
NOTE Within the scope of DIN VDE 0751-1, the operator of medical-tech-
nical products is required to carry out technical safety checks at
regular intervals.
The tests listed in these maintenance instructions include all tech-
nical safety checks required according to DIN VDE 0751-1.
For the technical safety checks, a separate report is available with
the print number SP00-000.834.01....
Within the scope of DIN VDE 0751-1, we recommend documenting
the results of maintenance in the maintenance protocol as well as
the TSC protocol, completing it and handing it over to the custom-
er.
The following table allocates the corresponding maintenance pro-
cedures to each technical safety check which is documented in the
document SP00-000.834.01....
2.1.2 Labels
SIM Labels
• Check all labels on the device with model and serial number, as well as warnings. Posi-
tioning of the labels is described in the operator manual (chapter “Location of labels”).
• Make sure all labels are available and readable.
Fig. 2: Fig. 3:
SIM Suspension
• The single tank support (1//Fig. 2 / p. 27) with the single tank must be seated securely
on the flange of the support arm. Check the torque of the 4 screws (2//Fig. 2 / p. 27);
T • NOM: 25 Nm, Tolerance: ± 10%.
Fig. 4:
• Connect the line voltage cable and turn the Polymobil Plus ON .
PMF Light localizer lamp
• Check the function of the light localizer lamp and replace, if necessary. Refer to the Ser-
vice Instructions "Replacing the light localizer lamp".
SIM Rotating
• Check whether the double-slot diaphragm can easily be rotated ± 45 (Fig. 4 / p. 28).
PMF Format setting
• Check the format setting (pairs of collimator leaves) for ease of movement and unifor-
mity (by sliding the diaphragm adjusting levers (1//Fig. 4 / p. 28).
• Switch the Polymobil Plus OFF and disconnect the line voltage plug.
PMF 0° degree position
• Move the support arm into its uppermost position.
• Place a water level against the double-slot collimator and check the 0° setting.
If necessary, readjust the scale on both sides.
2.8 Stand
Fig. 5: Fig. 6:
Fig. 7: Fig. 8:
• Release the support arm from the (transport) park position (1//Fig. 7 / p. 30)
• Slowly move the support arm into the uppermost position. When doing so, the support
arm must stop in any desired position without accessories attached and without the
supplementary brake applied (2//Fig. 7 / p. 30).
• Check the additional locking of the support arm with the knob (2//Fig. 7 / p. 30)
Readjusting the spring tension:
- Remove the cover (3//Fig. 7 / p. 30) from the stand.
- Fully release the supplementary brake on the support arm (2//Fig. 7 / p. 30).
- Move the support arm into the horizontal position.
- Firmly tighten the nut (4//Fig. 8 / p. 30) using a 17-mm open-ended wrench. Adjust
the spring tension so that the support arm is balanced in the horizontal position, i.e.,
so that equal force is required when lifting and lowering the tube.
SIM Chains of the spring counterbalance
• Remove the cover (3//Fig. 7 / p. 30) from the stand.
• The condition of the chains (5//Fig. 8 / p. 30) for the spring counterbalance must be
checked carefully. If the chain is defective, the stand column must be replaced.
2.9 Radiation
Fig. 9:
• Insert line voltage plug, Polymobil Plus ON
• Close the double-slot diaphragm. Set 60 kV, 10 mAs.
SIE Radiation indicator
SIE Acoustic signal
• The longitudinal deviation ( ΣY) and the width deviation ( ΣX) must be less than 1.6 cm
respectively.
NOTE If the deviation exceeds 1.6 cm, please refer to the Service Instruc-
tions, chapter "Coincidence of light field and radiation field".
NOTE The report “Device leakage current / report” is filed in the “Certifi-
cates” register in the system folder.