Study Summary
CYMCAP Version 8.1 Revision 2
Study: Current Calculations
Execution: Duct Bank 1200 mm2 132 kV single Circuit
Date: 11/16/2023 11:45:06 AM
General Simulation Data
Steady State Option Equally Loaded
Consider Electrical interaction between circuits No
Induced currents in metallic layers as a fraction of conductor current (applied to all single phase circuits) : 0.0
Conductor Resistances Computation Option: IEC-228
Standard Settings Options
General guidance Custom
Factor on RAC due to magnetic armour CIGREGuidance
Factor on RAC due to magnetic duct CIGREGuidance
Factor on ƛ₁ due to magnetic armour CYMCAPGuidance
Factor on ƛ₁ due to magnetic duct CIGREGuidance
Factor on ƛ₂ due to ƛ'₁ CYMCAPGuidance
ƛ''₁ computation CIGREGuidance
ƛ₂pipe computation CYMCAPGuidance
Wd computation CIGREGuidance
T₂ computation CIGREGuidance
T₄ computation CYMCAPGuidance
Installation Type:Multiple Ductbanks/Backfills
Ambient Soil Temperature at Installation Depth [°C] 40.0
Native Soil Thermal Resistivity [K.m/W] 1.5
Consider Non-Isothermal Earth Surface No
Thermal
Layer Name X [m] Y [m] Width [m] Height [m] Resistivity
[K.m/W]
NSTD DB1 0.0 1.3 1.2 0.8 1.0
Backfill 0.0 0.45 1.2 0.9 1.5
Results Summary
Daily Load X coordinate Y coordinate Conductor
Cable No. Cable ID Circuit No. Feeder ID Cable Phase Cable Frequency Ampacity [A]
Factor [m] [m] temperature [°C]
1 1200-132KV-YEMEN 1 A 60.0 1.0 -0.4 1.5 87.5 939.3
2 1200-132KV-YEMEN 1 B 60.0 1.0 0.0 1.5 90.0 939.3
3 1200-132KV-YEMEN 1 C 60.0 1.0 0.4 1.5 87.5 939.3
Steady State Summary
CYMCAP Version 8.1 Revision 2
Study: Current Calculations
Execution: Duct Bank 1200 mm2 132 kV single Circuit
Date: 11/16/2023 11:45:06 AM
Simulation Data
Installation type: Multiple Ductbanks
Steady State Option Equally Loaded
Ambient temperature [°C] 40
Native Soil Thermal Resistivity [K.m/W] 1.5
Consider Non-Isothermal Earth Surface No
Consider effect of soil dry out No
Consider Electrical interaction between circuits No
Induced current in metallic layers as a fraction of conductor current (applied to all
0
single phase circuits)
Variable Description Unit Cables
Cable No. Cable Index Number 1 2 3
General Input Data
Cable ID Cable Equipment ID 1200-132KV-YEMEN 1200-132KV-YEMEN 1200-132KV-YEMEN
Circuit No. Circuit No. 1 1 1
Phase Cable Phase A B C
Fq Operating Frequency [Hz] 60.0 60.0 60.0
x X coordinate [m] -0.4 0.0 0.4
y Y coordinate [m] 1.5 1.5 1.5
DLF Daily Load Factor [p.u.] 1.0 1.0 1.0
1 Conductor Crossbonded 1 Conductor Crossbonded 1 Conductor Crossbonded
Bonding Type
Flat Flat Flat
Ampacity
I Steady State Ampacity [A] 939.3 939.3 939.3
Temperatures
θc Conductor temperature [°C] 87.5 90.0 87.5
θs Sheath/Shield temperature [°C] 80.2 82.6 80.1
θa Armour temperature [°C] n/a n/a n/a
θsurf Cable surface temperature [°C] 79.1 81.5 79.0
θduct Duct surface temperature [°C] 71.9 74.3 71.8
Resistances
R₀ DC Resistance of the conductor at 20°C [Ω/km] 0.0151 0.0151 0.0151
R AC Resistance of the Conductor at Operating Temperature [Ω/km] 0.02255 0.02267 0.02254
ys Skin Effect Factor 0.17803 0.17571 0.17809
yp Proximity Effect Factor 0.00191 0.00188 0.00191
Losses
Wc Conductor Losses [W/m] 19.89201 20.00474 19.88948
Wd Dielectric Losses [W/m] 0.52954 0.52954 0.52954
Ws Metallic Screen Losses [W/m] 0.28286 0.2274 0.22118
Wa Armor/Pipe Losses [W/m] 0.0 0.0 0.0
Wt Total Losses [W/m] 20.70441 20.76168 20.6402
ƛ₁ Screen Loss Factor 0.01422 0.01137 0.01112
ƛ₂ Armour Loss Factor + Pipe Loss Factor 0.0 0.0 0.0
Thermal resistances
T1 Thermal resistance of insulation [K.m/W] 0.36642 0.36642 0.36642
T2 Thermal resistance of bedding/medium inside pipe-type [K.m/W] 0.0 0.0 0.0
T3 Thermal resistance of outer covering [K.m/W] 0.0533 0.0533 0.0533
T4 External thermal resistance [K.m/W] 1.88576 1.99751 1.88953
Others
Δθint Temperature rise due to surrounding heat sources [°C] 17.0 19.6 17.0
Induced Voltage (standing) on Concentric Wires [V/km] 0.0 0.0 0.0
Induced current on Metallic Screen [A] 57.7 51.6 51.0
Electrical Parameters
CYMCAP Version 8.1 Revision 2
Study: Current Calculations
Execution: Duct Bank 1200 mm2 132 kV single Circuit
Date: 11/16/2023 11:45:06 AM
No. Description Unit Cable No.1 Cable No.2 Cable No.3
1200-132KV- 1200-132KV- 1200-132KV-
1 Cable Equipment ID
YEMEN YEMEN YEMEN
Resistances
DC Resistance of the conductor at 20°C
2 [Ω/km] 0.0151 0.0151 0.0151
DC Resistance of Conductor at Operating Temperature
3 [Ω/km] 0.01911 0.01925 0.0191
4 AC Resistance of Conductor at 20°C [Ω/km] 0.01912 0.01912 0.01912
AC Resistance of Conductor at Operating Temperature
5 [Ω/km] 0.02255 0.02267 0.02254
6 DC Resistance of Concentric Wires at 20°C [Ω/km] 0.06868 0.06868 0.06868
DC Resistance of Concentric Wires at Operating Temperature
7 [Ω/km] 0.08492 0.08557 0.0849
Losses
Conductor Losses
8 [W/m] 19.89201 20.00474 19.88948
Dielectric Losses
9 [W/m] 0.52954 0.52954 0.52954
Metallic Screen Losses
10 [W/m] 0.28286 0.2274 0.22118
Armor/Pipe Losses
11 [W/m] 0.0 0.0 0.0
Total Losses
12 [W/m] 20.70441 20.76168 20.6402
Capacitance, Inductance, Impedance
Capacitance
13 [µF/km] 0.242 0.242 0.242
Inductance of Conductor
14 [mH/km] 0.63283 0.63283 0.63283
Reactance of Conductor
15 [Ω/km] 0.23857 0.23857 0.23857
Inductance of Metallic Sheath
16 [mH/km] 0.44255 0.44255 0.44255
Reactance of Metallic Sheath
17 [Ω/km] 0.16684 0.16684 0.16684
Positive Sequence Impedance
0.022546 + 0.022674 + 0.022543 +
18 [Ω/km]
j0.238571 j0.238571 j0.238571
Negative Sequence Impedance
0.022546 + 0.022674 + 0.022543 +
19 [Ω/km]
j0.238571 j0.238571 j0.238571
Zero Sequence Impedance
0.086468 + 0.086433 + 0.086469 +
20 [Ω/km]
j0.166837 j0.166837 j0.166837
Surge Impedance
21 [Ω] 51.15335 51.15335 51.15335
Others
Dielectric Stress at Insulation Inner Surface
22 [kV/mm] 5.72001 5.72001 5.72001
23 Dielectric Stress at Insulation Outer Surface [kV/mm] 3.22098 3.22098 3.22098
Insulation Resistance at 60°F (15.8°C)
24 [㏁.km] 1520.39871 1520.39871 1520.39871
Reduction Factor (2pt bonded & single metallic screen)
25 n/a n/a n/a
Charging Current for One Cable (Phase)
26 [A/km] 6.94838 6.94838 6.94838
Charging Capacity of three phase system at Uo
27 [kvar/km] 1588.61355 1588.61355 1588.61355
Voltage drop for Three Phase System
28 [V/A/km] 0.03905 0.03927 0.03905
29 Induced Voltage (standing) on Concentric Wires [V/km] 0.0 0.0 0.0
Induced current on Metallic Screen
30 [A] 57.7 51.6 51.0
Cable Parameters under Normal Operation
CYMCAP Version 8.1 Revision 2
Study: Current Calculations
Execution: Duct Bank 1200 mm2 132 kV single Circuit
Date: 11/16/2023 11:45:06 AM
No. Symbol Description Unit Cable No.1 Cable No.2 Cable No.3
1 Cable Equipment ID 1200-132KV-YEMEN 1200-132KV-YEMEN 1200-132KV-YEMEN
Normal Operation IEC 60287-1-1
Conductor AC Resistance
DC Resistance of the conductor at 20°C
2 R₀ [Ω/km] 0.0151 0.0151 0.0151
DC Resistance of Conductor at Operating Temperature
3 R' [Ω/km] 0.01911 0.01925 0.0191
4 dc Conductor Diameter [mm] 43.4 43.4 43.4
5 s Distance Between Conductor Axes [mm] 400.0 400.0 400.0
6 ks Factor Used for xs Calculation (Skin Effect) 0.8 0.8 0.8
7 kp Factor Used for xp Calculation (Proximity Effect) 0.37 0.37 0.37
Component of Ys Calculation (Skin Effect)
8 Xs² 6.31342 6.26537 6.3145
Component of Yp Calculation (Proximity Effect)
9 Xp² 2.91996 2.89773 2.92046
Skin Effect Factor
10 ys 0.17803 0.17571 0.17809
Proximity Effect Factor
11 yp 0.00191 0.00188 0.00191
AC Resistance of Conductor at Operating Temperature
12 R [Ω/km] 0.02255 0.02267 0.02254
Dielectric Losses
13 tanδ Dielectric Loss Factor 0.001 0.001 0.001
14 ε Insulation Relative Permitivity 2.5 2.5 2.5
Cable Capacitance
15 C [µF/km] 0.242 0.242 0.242
16 U₀ Voltage [kV] 76.21024 76.21024 76.21024
Cable Dielectric Losses Per Phase
17 Wd [W/m] 0.52954 0.52954 0.52954
Circulating Loss Factor
18 Rs AC Resistance used for Circulating Loss Factor computation [Ω/km] 0.08492 0.08557 0.0849
19 d Mean diameter used for Circulating Loss Factor computation [mm] 87.52 87.52 87.52
Reactance used for Circulating Loss Factor computation
20 X [Ω/km] 0.16684 0.16684 0.16684
Mutual Reactance
21 Xm [Ω/km] 0.05226 0.05226 0.05226
Component for Circulating Loss Factor Formula (Clause 2.3.3)
22 P [Ω/km] 0.2191 0.2191 0.2191
Component for Circulating Loss Factor Formula (Clause 2.3.3)
23 Q [Ω/km] 0.14942 0.14942 0.14942
Spacing Factor (applied when spacing between cable uneven or non-equal minor section length)
24 Fspacing 0.004 0.004 0.004
Screen Loss Factor Caused by Circulating Current
25 ƛ'₁ 0.01422 0.01137 0.01112
Eddy Loss Factor
Screen Loss Factor Caused by Eddy Current
26 ƛ''₁ 0.0 0.0 0.0
Metallic Screen Loss factor
Screen Loss Factor
27 ƛ₁ 0.01422 0.01137 0.01112
Armour and Pipe Loss Factor
Armour Loss Factor
28 ƛ₂a 0.0 0.0 0.0
Pipe Loss Factor
29 ƛ₂pipe 0.0 0.0 0.0
Armour Loss Factor + Pipe Loss Factor
30 ƛ₂ 0.0 0.0 0.0
Normal Operation IEC 60287-2-1
Thermal Resistance Between Conductor and Screen
32 T₁ [K.m/W] 0.36642 0.36642 0.36642
33 t₁ Insulation Thickness Between Conductor and Screen [mm] 21.0 21.0 21.0
34 ρTi Thermal Resistivity of Insulation [K.m/W] 3.5 3.5 3.5
Thermal Resistance of Jacket/Pipe Coating
35 T₃ [K.m/W] 0.0533 0.0533 0.0533
36 t₃ Thickness of Jacket/Pipe Coating [mm] 4.5 4.5 4.5
37 ρTJ Thermal Resistivity of Jacket/Pipe Coating [K.m/W] 3.5 3.5 3.5
38 Thermal resistance [K.m/W] 0.02659 0.02659 0.02659
39 T Thermal resistance equation
Conductor
Shield
40 Thermal resistivity [K.m/W] 2.5 2.5 2.5
41 Layer thickness [mm] 1.5 1.5 1.5
42 Internal diameter [mm] 43.4 43.4 43.4
43 Thermal resistance [K.m/W] 0.3199 0.3199 0.3199
44 Thermal resistance equation
T
Insulation
45 Thermal resistivity [K.m/W] 3.5 3.5 3.5
46 Layer thickness [mm] 18.0 18.0 18.0
47 Internal diameter [mm] 46.4 46.4 46.4
48 Thermal resistance [K.m/W] 0.01992 0.01992 0.01992
49 T Thermal resistance equation
Insulation
Screen
50 Thermal resistivity [K.m/W] 3.5 3.5 3.5
51 Layer thickness [mm] 1.5 1.5 1.5
52 Internal diameter [mm] 82.4 82.4 82.4
53 Thermal resistance [K.m/W] 0.0 0.0 0.0
54 T Thermal resistance equation
Concentric
wires
55 Thermal resistivity [K.m/W] 0.0 0.0 0.0
56 Layer thickness [mm] 2.12 2.12 2.12
57 Internal diameter [mm] 85.4 85.4 85.4
58 Thermal resistance [K.m/W] 0.0533 0.0533 0.0533
59 Thermal resistance equation
T
Jacket
60 Thermal resistivity [K.m/W] 3.5 3.5 3.5
61 Layer thickness [mm] 4.5 4.5 4.5
62 Internal diameter [mm] 89.64 89.64 89.64
Thermal resistance inside the duct
63 U Constant from IEC6028721 clause4272 1.87 1.87 1.87
64 V Constant from IEC6028721 clause4272 0.312 0.312 0.312
65 Y Constant from IEC6028721 clause4272 0.0037 0.0037 0.0037
66 θm Mean temperature of the medium in conduit [°C] 76.22931 78.68294 76.18636
67 Deq Equivalent diameter of the cables inside the conduit [mm] 98.64 98.64 98.64
Thermal resistance of the medium in conduit
68 T₄' [K.m/W] 0.27261 0.26909 0.27267
Thermal resistance of the duct
69 Do Outer diameter of the conduit [mm] 200.0 200.0 200.0
70 Di Inner diameter of the conduit [mm] 185.0 185.0 185.0
71 ρT Thermal resistivity of the conduit material [K.m/W] 6.0 6.0 6.0
Thermal resistance of the conduit
72 T₄'' [K.m/W] 0.07445 0.07445 0.07445
Thermal resistance of the external medium
73 L Depth of cable/conduit axis [m] 1.4988 1.4988 1.4988
74 De External diameter of the cable conduit [m] 0.2 0.2 0.2
Geometric factor as per IEC60287-2-1 clause 4.2.2
75 u 14.988 14.988 14.988
76 ρTs Thermal resistivity of the soil [K.m/W] 1.33077 1.30991 1.33089
Thermal resistance of the cable isolated
77 T₄'''self [K.m/W] 0.71996 0.70868 0.72003
Thermal resistance associated to the temperature rise due to surrounding heat sources
78 T₄'''mutual [K.m/W] 0.81874 0.94529 0.82239
Temperature rise due to surrounding heat sources
79 Δθint [°C] 16.95156 19.62588 16.97426
Thermal resistance of the external medium
80 T₄''' [K.m/W] 1.5387 1.65397 1.54242
Thermal Capacitance IEC 853-2
81 Thermal capacitance [J/m.K] 4140.0 4140.0 4140.0
82 Q Thermal capacitance equation
Conductor
83 Material surface [mm²] 1200.0 1200.0 1200.0
84 Volumetric specific heat of the material [J/(K*m³)] 3450000.0 3450000.0 3450000.0
85 Thermal capacitance [J/m.K] 507.80693 507.80693 507.80693
86 Q Thermal capacitance equation
Conductor
Shield
87 External diameter [mm] 46.4 46.4 46.4
88 Internal diameter [mm] 43.4 43.4 43.4
89 Volumetric specific heat of the material [J/(K*m³)] 2400000.0 2400000.0 2400000.0
90 Thermal capacitance [J/m.K] 3148.62983 3148.62983 3148.62983
91 Thermal capacitance equation
Q1
Insulation
92 External diameter [mm] 82.4 82.4 82.4
93 Internal diameter [mm] 46.4 46.4 46.4
94 Volumetric specific heat of the material [J/(K*m³)] 2400000.0 2400000.0 2400000.0
95 Thermal capacitance [J/m.K] 5591.53236 5591.53236 5591.53236
96 Thermal capacitance equation
Q2
Insulation
97 External diameter [mm] 82.4 82.4 82.4
98 Internal diameter [mm] 46.4 46.4 46.4
99 Volumetric specific heat of the material [J/(K*m³)] 2400000.0 2400000.0 2400000.0
100 Thermal capacitance [J/m.K] 948.88665 948.88665 948.88665
101 Q Thermal capacitance equation
Insulation
Screen
102 External diameter [mm] 85.4 85.4 85.4
103 Internal diameter [mm] 82.4 82.4 82.4
104 Volumetric specific heat of the material [J/(K*m³)] 2400000.0 2400000.0 2400000.0
105 Thermal capacitance [J/m.K] 260.67223 260.67223 260.67223
106 Thermal capacitance equation
107 Q Number of armour wires 74.0 74.0 74.0
Concentric
108 Mean diameter of armour wire [mm] 2.12 2.12 2.12
wires
109 Length of lay [mm] 956.0 956.0 956.0
110 Mean diameter of armour [mm] 87.52 87.52 87.52
111 Wire Shape is half-circle 0.0 0.0 0.0
112 Thermal capacitance [J/m.K] 3194.0953 3194.0953 3194.0953
113 Thermal capacitance equation
Q
Jacket
114 External diameter [mm] 98.64 98.64 98.64
115 Internal diameter [mm] 89.64 89.64 89.64
116 Volumetric specific heat of the material [J/(K*m³)] 2400000.0 2400000.0 2400000.0
Ampacity
Total external thermal resistance
117 T₄ [K.m/W] 1.88576 1.99751 1.88953
Cable core ampacity
118 I [A] 939.29361 939.29361 939.29361