CCCC - in Duct 1200 mm2 132 KV Double Circuits (Filling 1.5 K.M-W)
CCCC - in Duct 1200 mm2 132 KV Double Circuits (Filling 1.5 K.M-W)
Induced currents in metallic layers as a fraction of conductor current (applied to all single phase circuits) : 0.0
Installation Type:Backfill
Ambient Soil Temperature at Installation Depth [°C] 40.0
Native Soil Thermal Resistivity [K.m/W] 1.5
Thermal Resistivity of Backfill [K.m/W] 1.5
Depth of Center of Backfill [m] 0.86
Backfill Width [m] 2.4
Backfill Height [m] 1.7
Results Summary
Daily Load X coordinate Y coordinate Conductor
Cable No. Cable ID Circuit No. Feeder ID Cable Phase Cable Frequency Ampacity [A]
Factor [m] [m] temperature [°C]
1 1200-132KV-YEMEN 1 A 50.0 1.0 -1.0 1.5 82.7 805.6
2 1200-132KV-YEMEN 1 B 50.0 1.0 -0.6 1.5 87.8 805.6
3 1200-132KV-YEMEN 1 C 50.0 1.0 -0.2 1.5 90.0 805.6
4 1200-132KV-YEMEN 2 A 50.0 1.0 0.2 1.5 90.0 805.6
5 1200-132KV-YEMEN 2 B 50.0 1.0 0.6 1.5 87.8 805.6
6 1200-132KV-YEMEN 2 C 50.0 1.0 1.0 1.5 82.7 805.6
Steady State Summary
CYMCAP Version 8.1 Revision 2
Study: Current Calculations
Execution: In Duct 1200 mm2 132 kV Double Circuits
Date: 11/16/2023 11:39:34 AM
Simulation Data
Installation type: Backfill
Steady State Option Equally Loaded
Ambient temperature [°C] 40
Native Soil Thermal Resistivity [K.m/W] 1.5
Consider Non-Isothermal Earth Surface No
Consider effect of soil dry out No
Consider Electrical interaction between circuits No
Induced current in metallic layers as a fraction of conductor current (applied to all single
0
phase circuits)
No. Description Unit Cable No.1 Cable No.2 Cable No.3 Cable No.4 Cable No.5 Cable No.6
1200-132KV- 1200-132KV- 1200-132KV- 1200-132KV- 1200-132KV- 1200-132KV-
1 Cable Equipment ID
YEMEN YEMEN YEMEN YEMEN YEMEN YEMEN
Resistances
DC Resistance of the conductor at 20°C
4 AC Resistance of Conductor at 20°C [Ω/km] 0.01807 0.01807 0.01807 0.01807 0.01807 0.01807
AC Resistance of Conductor at Operating Temperature
6 DC Resistance of Concentric Wires at 20°C [Ω/km] 0.06868 0.06868 0.06868 0.06868 0.06868 0.06868
DC Resistance of Concentric Wires at Operating Temperature
Losses
Conductor Losses
Dielectric Losses
Armor/Pipe Losses
Total Losses
Inductance of Conductor
Reactance of Conductor
Surge Impedance
Others
Dielectric Stress at Insulation Inner Surface
23 Dielectric Stress at Insulation Outer Surface [kV/mm] 3.22098 3.22098 3.22098 3.22098 3.22098 3.22098
Insulation Resistance at 60°F (15.8°C)
29 Induced Voltage (standing) on Concentric Wires [V/km] 0.0 0.0 0.0 0.0 0.0 0.0
Induced current on Metallic Screen
No. Symbol Description Unit Cable No.1 Cable No.2 Cable No.3 Cable No.4 Cable No.5 Cable No.6
1 Cable Equipment ID 1200-132KV-YEMEN 1200-132KV-YEMEN 1200-132KV-YEMEN 1200-132KV-YEMEN 1200-132KV-YEMEN 1200-132KV-YEMEN
Normal Operation IEC 60287-1-1
Conductor AC Resistance
DC Resistance of the conductor at 20°C
2 R₀ [Ω/km] 0.0151 0.0151 0.0151 0.0151 0.0151 0.0151
Dielectric Losses
13 tanδ Dielectric Loss Factor 0.001 0.001 0.001 0.001 0.001 0.001
14 ε Insulation Relative Permitivity 2.5 2.5 2.5 2.5 2.5 2.5
Cable Capacitance
15 C [µF/km] 0.242 0.242 0.242 0.242 0.242 0.242
Mutual Reactance
21 Xm [Ω/km] 0.04355 0.04355 0.04355 0.04355 0.04355 0.04355
Spacing Factor (applied when spacing between cable uneven or non-equal minor section length)
24 Fspacing 0.004 0.004 0.004 0.004 0.004 0.004
33 t₁ Insulation Thickness Between Conductor and Screen [mm] 21.0 21.0 21.0 21.0 21.0 21.0
34 ρTi Thermal Resistivity of Insulation [K.m/W] 3.5 3.5 3.5 3.5 3.5 3.5
Thermal Resistance of Jacket/Pipe Coating
35 T₃ [K.m/W] 0.0533 0.0533 0.0533 0.0533 0.0533 0.0533
36 t₃ Thickness of Jacket/Pipe Coating [mm] 4.5 4.5 4.5 4.5 4.5 4.5
37 ρTJ Thermal Resistivity of Jacket/Pipe Coating [K.m/W] 3.5 3.5 3.5 3.5 3.5 3.5
38 Thermal resistance [K.m/W] 0.02659 0.02659 0.02659 0.02659 0.02659 0.02659
76 ρTs Thermal resistivity of the soil [K.m/W] 1.5 1.5 1.5 1.5 1.5 1.5
Thermal resistance of the cable isolated
77 T₄'''self [K.m/W] 0.81171 0.81171 0.81171 0.81171 0.81171 0.81171
Thermal resistance associated to the temperature rise due to surrounding heat sources
78 T₄'''mutual [K.m/W] 1.3782 1.70515 1.83902 1.83115 1.70473 1.38353
107 Q Number of armour wires 74.0 74.0 74.0 74.0 74.0 74.0
Concentric
108 Mean diameter of armour wire [mm] 2.12 2.12 2.12 2.12 2.12 2.12
wires
109 Length of lay [mm] 956.0 956.0 956.0 956.0 956.0 956.0
110 Mean diameter of armour [mm] 87.52 87.52 87.52 87.52 87.52 87.52
111 Wire Shape is half-circle 0.0 0.0 0.0 0.0 0.0 0.0
112 Thermal capacitance [J/m.K] 3194.0953 3194.0953 3194.0953 3194.0953 3194.0953 3194.0953