CCCC - in Duct 1200 mm2 132 KV Double Circuits (Filling 1.5 K.M-W)

This document summarizes the results of a steady state thermal rating calculation for a 1200 mm^2, 132 kV double circuit installation using the CYMCAP software. The installation has 6 cables in two circuits, with ambient temperature of 40°C, native soil resistivity of 1.5 K.m/W, and backfill properties specified. The simulation found conductor temperatures from 82.7°C to 90°C and ampacities of 805.6A for all cables.

Uploaded by

Manaf
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
92 views10 pages

CCCC - in Duct 1200 mm2 132 KV Double Circuits (Filling 1.5 K.M-W)

This document summarizes the results of a steady state thermal rating calculation for a 1200 mm^2, 132 kV double circuit installation using the CYMCAP software. The installation has 6 cables in two circuits, with ambient temperature of 40°C, native soil resistivity of 1.5 K.m/W, and backfill properties specified. The simulation found conductor temperatures from 82.7°C to 90°C and ampacities of 805.6A for all cables.

Uploaded by

Manaf
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 10

Study Summary

CYMCAP Version 8.1 Revision 2


Study: Current Calculations
Execution: In Duct 1200 mm2 132 kV Double Circuits
Date: 11/16/2023 11:39:34 AM

General Simulation Data


Steady State Option Equally Loaded
Consider Electrical interaction between circuits No

Induced currents in metallic layers as a fraction of conductor current (applied to all single phase circuits) : 0.0

Conductor Resistances Computation Option: IEC-228

Standard Settings Options


General guidance Custom
Factor on RAC due to magnetic armour CIGREGuidance
Factor on RAC due to magnetic duct CIGREGuidance
Factor on ƛ₁ due to magnetic armour CYMCAPGuidance
Factor on ƛ₁ due to magnetic duct CIGREGuidance
Factor on ƛ₂ due to ƛ'₁ CYMCAPGuidance
ƛ''₁ computation CIGREGuidance
ƛ₂pipe computation CYMCAPGuidance
Wd computation CIGREGuidance
T₂ computation CIGREGuidance
T₄ computation CYMCAPGuidance

Installation Type:Backfill
Ambient Soil Temperature at Installation Depth [°C] 40.0
Native Soil Thermal Resistivity [K.m/W] 1.5
Thermal Resistivity of Backfill [K.m/W] 1.5
Depth of Center of Backfill [m] 0.86
Backfill Width [m] 2.4
Backfill Height [m] 1.7
Results Summary
Daily Load X coordinate Y coordinate Conductor
Cable No. Cable ID Circuit No. Feeder ID Cable Phase Cable Frequency Ampacity [A]
Factor [m] [m] temperature [°C]
1 1200-132KV-YEMEN 1 A 50.0 1.0 -1.0 1.5 82.7 805.6
2 1200-132KV-YEMEN 1 B 50.0 1.0 -0.6 1.5 87.8 805.6
3 1200-132KV-YEMEN 1 C 50.0 1.0 -0.2 1.5 90.0 805.6
4 1200-132KV-YEMEN 2 A 50.0 1.0 0.2 1.5 90.0 805.6
5 1200-132KV-YEMEN 2 B 50.0 1.0 0.6 1.5 87.8 805.6
6 1200-132KV-YEMEN 2 C 50.0 1.0 1.0 1.5 82.7 805.6
Steady State Summary
CYMCAP Version 8.1 Revision 2
Study: Current Calculations
Execution: In Duct 1200 mm2 132 kV Double Circuits
Date: 11/16/2023 11:39:34 AM

Simulation Data
Installation type: Backfill
Steady State Option Equally Loaded
Ambient temperature [°C] 40
Native Soil Thermal Resistivity [K.m/W] 1.5
Consider Non-Isothermal Earth Surface No
Consider effect of soil dry out No
Consider Electrical interaction between circuits No
Induced current in metallic layers as a fraction of conductor current (applied to all single
0
phase circuits)

Variable Description Unit Cables


Cable No. Cable Index Number 1 2 3 4 5 6
General Input Data
Cable ID Cable Equipment ID 1200-132KV-YEMEN 1200-132KV-YEMEN 1200-132KV-YEMEN 1200-132KV-YEMEN 1200-132KV-YEMEN 1200-132KV-YEMEN
Circuit No. Circuit No. 1 1 1 2 2 2
Phase Cable Phase A B C A B C
Fq Operating Frequency [Hz] 50.0 50.0 50.0 50.0 50.0 50.0
x X coordinate [m] -1.0 -0.6 -0.2 0.2 0.6 1.0
y Y coordinate [m] 1.5 1.5 1.5 1.5 1.5 1.5
DLF Daily Load Factor [p.u.] 1.0 1.0 1.0 1.0 1.0 1.0
1 Conductor Crossbonded 1 Conductor Crossbonded 1 Conductor Crossbonded 1 Conductor Crossbonded 1 Conductor Crossbonded 1 Conductor Crossbonded
Bonding Type
Flat Flat Flat Flat Flat Flat
Ampacity
I Steady State Ampacity [A] 805.6 805.6 805.6 805.6 805.6 805.6
Temperatures
θc Conductor temperature [°C] 82.7 87.8 90.0 90.0 87.8 82.7
θs Sheath/Shield temperature [°C] 77.6 82.6 84.7 84.8 82.6 77.5
θa Armour temperature [°C] n/a n/a n/a n/a n/a n/a
θsurf Cable surface temperature [°C] 76.8 81.8 83.9 84.0 81.8 76.8
θduct Duct surface temperature [°C] 71.7 76.8 79.0 79.0 76.8 71.7
Resistances
R₀ DC Resistance of the conductor at 20°C [Ω/km] 0.0151 0.0151 0.0151 0.0151 0.0151 0.0151
R AC Resistance of the Conductor at Operating Temperature [Ω/km] 0.02135 0.02162 0.02173 0.02174 0.02162 0.02135
ys Skin Effect Factor 0.13279 0.12906 0.12752 0.1275 0.12907 0.13283
yp Proximity Effect Factor 0.00143 0.00139 0.00138 0.00138 0.00139 0.00143
Losses
Wc Conductor Losses [W/m] 13.85513 14.03017 14.10514 14.10614 14.02975 13.85319
Wd Dielectric Losses [W/m] 0.44128 0.44128 0.44128 0.44128 0.44128 0.44128
Ws Metallic Screen Losses [W/m] 0.19575 0.15088 0.15142 0.19858 0.15087 0.14965
Wa Armor/Pipe Losses [W/m] 0.0 0.0 0.0 0.0 0.0 0.0
Wt Total Losses [W/m] 14.49215 14.62232 14.69784 14.746 14.6219 14.44412
ƛ₁ Screen Loss Factor 0.01413 0.01075 0.01074 0.01408 0.01075 0.0108
ƛ₂ Armour Loss Factor + Pipe Loss Factor 0.0 0.0 0.0 0.0 0.0 0.0
Thermal resistances
T1 Thermal resistance of insulation [K.m/W] 0.36642 0.36642 0.36642 0.36642 0.36642 0.36642
T2 Thermal resistance of bedding/medium inside pipe-type [K.m/W] 0.0 0.0 0.0 0.0 0.0 0.0
T3 Thermal resistance of outer covering [K.m/W] 0.0533 0.0533 0.0533 0.0533 0.0533 0.0533
T4 External thermal resistance [K.m/W] 2.53903 2.85875 2.98966 2.98176 2.85835 2.54443
Others
Δθint Temperature rise due to surrounding heat sources [°C] 20.0 24.9 27.0 27.0 24.9 20.0
Induced Voltage (standing) on Concentric Wires [V/km] 0.0 0.0 0.0 0.0 0.0 0.0
Induced current on Metallic Screen [A] 48.2 42.0 41.9 48.0 42.0 42.2
Electrical Parameters
CYMCAP Version 8.1 Revision 2
Study: Current Calculations
Execution: In Duct 1200 mm2 132 kV Double Circuits
Date: 11/16/2023 11:39:34 AM

No. Description Unit Cable No.1 Cable No.2 Cable No.3 Cable No.4 Cable No.5 Cable No.6
1200-132KV- 1200-132KV- 1200-132KV- 1200-132KV- 1200-132KV- 1200-132KV-
1 Cable Equipment ID
YEMEN YEMEN YEMEN YEMEN YEMEN YEMEN
Resistances
DC Resistance of the conductor at 20°C

2 [Ω/km] 0.0151 0.0151 0.0151 0.0151 0.0151 0.0151

DC Resistance of Conductor at Operating Temperature

3 [Ω/km] 0.01882 0.01912 0.01925 0.01925 0.01912 0.01882

4 AC Resistance of Conductor at 20°C [Ω/km] 0.01807 0.01807 0.01807 0.01807 0.01807 0.01807
AC Resistance of Conductor at Operating Temperature

5 [Ω/km] 0.02135 0.02162 0.02173 0.02174 0.02162 0.02135

6 DC Resistance of Concentric Wires at 20°C [Ω/km] 0.06868 0.06868 0.06868 0.06868 0.06868 0.06868
DC Resistance of Concentric Wires at Operating Temperature

7 [Ω/km] 0.08422 0.08557 0.08615 0.08616 0.08557 0.08421

Losses
Conductor Losses

8 [W/m] 13.85513 14.03017 14.10514 14.10614 14.02975 13.85319

Dielectric Losses

9 [W/m] 0.44128 0.44128 0.44128 0.44128 0.44128 0.44128


Metallic Screen Losses

10 [W/m] 0.19575 0.15088 0.15142 0.19858 0.15087 0.14965

Armor/Pipe Losses

11 [W/m] 0.0 0.0 0.0 0.0 0.0 0.0

Total Losses

12 [W/m] 14.49215 14.62232 14.69784 14.746 14.6219 14.44412

Capacitance, Inductance, Impedance


Capacitance

13 [µF/km] 0.242 0.242 0.242 0.242 0.242 0.242

Inductance of Conductor

14 [mH/km] 0.63283 0.63283 0.63283 0.63283 0.63283 0.63283

Reactance of Conductor

15 [Ω/km] 0.19881 0.19881 0.19881 0.19881 0.19881 0.19881

Inductance of Metallic Sheath

16 [mH/km] 0.44255 0.44255 0.44255 0.44255 0.44255 0.44255

Reactance of Metallic Sheath

17 [Ω/km] 0.13903 0.13903 0.13903 0.13903 0.13903 0.13903


Positive Sequence Impedance

0.021349 + 0.021619 + 0.021734 + 0.021736 + 0.021618 + 0.021346 +


18 [Ω/km]
j0.198810 j0.198810 j0.198810 j0.198810 j0.198810 j0.198810

Negative Sequence Impedance

0.021349 + 0.021619 + 0.021734 + 0.021736 + 0.021618 + 0.021346 +


19 [Ω/km]
j0.198810 j0.198810 j0.198810 j0.198810 j0.198810 j0.198810

Zero Sequence Impedance

0.085785 + 0.085728 + 0.085705 + 0.085705 + 0.085728 + 0.085785 +


20 [Ω/km]
j0.139031 j0.139031 j0.139031 j0.139031 j0.139031 j0.139031

Surge Impedance

21 [Ω] 51.15335 51.15335 51.15335 51.15334 51.15334 51.15334

Others
Dielectric Stress at Insulation Inner Surface

22 [kV/mm] 5.72001 5.72001 5.72001 5.72001 5.72001 5.72001

23 Dielectric Stress at Insulation Outer Surface [kV/mm] 3.22098 3.22098 3.22098 3.22098 3.22098 3.22098
Insulation Resistance at 60°F (15.8°C)

24 [㏁.km] 1520.39871 1520.39871 1520.39871 1520.39871 1520.39871 1520.39871

Reduction Factor (2pt bonded & single metallic screen)

25 n/a n/a n/a n/a n/a n/a

Charging Current for One Cable (Phase)

26 [A/km] 5.79032 5.79032 5.79032 5.79032 5.79032 5.79032


Charging Capacity of three phase system at Uo

27 [kvar/km] 1323.84463 1323.84463 1323.84463 1323.84463 1323.84463 1323.84463

Voltage drop for Three Phase System

28 [V/A/km] 0.03698 0.03745 0.03765 0.03765 0.03744 0.03697

29 Induced Voltage (standing) on Concentric Wires [V/km] 0.0 0.0 0.0 0.0 0.0 0.0
Induced current on Metallic Screen

30 [A] 48.2 42.0 41.9 48.0 42.0 42.2


Cable Parameters under Normal Operation
CYMCAP Version 8.1 Revision 2
Study: Current Calculations
Execution: In Duct 1200 mm2 132 kV Double Circuits
Date: 11/16/2023 11:39:34 AM

No. Symbol Description Unit Cable No.1 Cable No.2 Cable No.3 Cable No.4 Cable No.5 Cable No.6
1 Cable Equipment ID 1200-132KV-YEMEN 1200-132KV-YEMEN 1200-132KV-YEMEN 1200-132KV-YEMEN 1200-132KV-YEMEN 1200-132KV-YEMEN
Normal Operation IEC 60287-1-1
Conductor AC Resistance
DC Resistance of the conductor at 20°C
2 R₀ [Ω/km] 0.0151 0.0151 0.0151 0.0151 0.0151 0.0151

DC Resistance of Conductor at Operating Temperature


3 R' [Ω/km] 0.01882 0.01912 0.01925 0.01925 0.01912 0.01882

4 dc Conductor Diameter [mm] 43.4 43.4 43.4 43.4 43.4 43.4


5 s Distance Between Conductor Axes [mm] 400.0 400.0 400.0 399.99995 399.99995 399.99995
6 ks Factor Used for xs Calculation (Skin Effect) 0.8 0.8 0.8 0.8 0.8 0.8
7 kp Factor Used for xp Calculation (Proximity Effect) 0.37 0.37 0.37 0.37 0.37 0.37
Component of Ys Calculation (Skin Effect)
8 Xs² 5.34089 5.25677 5.22161 5.22114 5.25697 5.34184

Component of Yp Calculation (Proximity Effect)


9 Xp² 2.47016 2.43126 2.41499 2.41478 2.43135 2.4706

Skin Effect Factor


10 ys 0.13279 0.12906 0.12752 0.1275 0.12907 0.13283

Proximity Effect Factor

11 yp 0.00143 0.00139 0.00138 0.00138 0.00139 0.00143

AC Resistance of Conductor at Operating Temperature


12 R [Ω/km] 0.02135 0.02162 0.02173 0.02174 0.02162 0.02135

Dielectric Losses
13 tanδ Dielectric Loss Factor 0.001 0.001 0.001 0.001 0.001 0.001
14 ε Insulation Relative Permitivity 2.5 2.5 2.5 2.5 2.5 2.5
Cable Capacitance
15 C [µF/km] 0.242 0.242 0.242 0.242 0.242 0.242

16 U₀ Voltage [kV] 76.21024 76.21024 76.21024 76.21024 76.21024 76.21024


Cable Dielectric Losses Per Phase
17 Wd [W/m] 0.44128 0.44128 0.44128 0.44128 0.44128 0.44128

Circulating Loss Factor


18 Rs AC Resistance used for Circulating Loss Factor computation [Ω/km] 0.08422 0.08557 0.08615 0.08616 0.08557 0.08421
19 d Mean diameter used for Circulating Loss Factor computation [mm] 87.52 87.52 87.52 87.52 87.52 87.52
Reactance used for Circulating Loss Factor computation
20 X [Ω/km] 0.13903 0.13903 0.13903 0.13903 0.13903 0.13903

Mutual Reactance
21 Xm [Ω/km] 0.04355 0.04355 0.04355 0.04355 0.04355 0.04355

Component for Circulating Loss Factor Formula (Clause 2.3.3)


22 P [Ω/km] 0.18258 0.18258 0.18258 0.18258 0.18258 0.18258

Component for Circulating Loss Factor Formula (Clause 2.3.3)


23 Q [Ω/km] 0.12451 0.12451 0.12451 0.12451 0.12451 0.12451

Spacing Factor (applied when spacing between cable uneven or non-equal minor section length)
24 Fspacing 0.004 0.004 0.004 0.004 0.004 0.004

Screen Loss Factor Caused by Circulating Current

25 ƛ'₁ 0.01413 0.01075 0.01074 0.01408 0.01075 0.0108

Eddy Loss Factor


Screen Loss Factor Caused by Eddy Current
26 ƛ''₁ 0.0 0.0 0.0 0.0 0.0 0.0

Metallic Screen Loss factor


Screen Loss Factor
27 ƛ₁ 0.01413 0.01075 0.01074 0.01408 0.01075 0.0108

Armour and Pipe Loss Factor


Armour Loss Factor
28 ƛ₂a 0.0 0.0 0.0 0.0 0.0 0.0

Pipe Loss Factor


29 ƛ₂pipe 0.0 0.0 0.0 0.0 0.0 0.0

Armour Loss Factor + Pipe Loss Factor


30 ƛ₂ 0.0 0.0 0.0 0.0 0.0 0.0
Normal Operation IEC 60287-2-1
Thermal Resistance Between Conductor and Screen
32 T₁ [K.m/W] 0.36642 0.36642 0.36642 0.36642 0.36642 0.36642

33 t₁ Insulation Thickness Between Conductor and Screen [mm] 21.0 21.0 21.0 21.0 21.0 21.0
34 ρTi Thermal Resistivity of Insulation [K.m/W] 3.5 3.5 3.5 3.5 3.5 3.5
Thermal Resistance of Jacket/Pipe Coating
35 T₃ [K.m/W] 0.0533 0.0533 0.0533 0.0533 0.0533 0.0533

36 t₃ Thickness of Jacket/Pipe Coating [mm] 4.5 4.5 4.5 4.5 4.5 4.5
37 ρTJ Thermal Resistivity of Jacket/Pipe Coating [K.m/W] 3.5 3.5 3.5 3.5 3.5 3.5
38 Thermal resistance [K.m/W] 0.02659 0.02659 0.02659 0.02659 0.02659 0.02659

39 T Thermal resistance equation


Conductor
Shield
40 Thermal resistivity [K.m/W] 2.5 2.5 2.5 2.5 2.5 2.5
41 Layer thickness [mm] 1.5 1.5 1.5 1.5 1.5 1.5
42 Internal diameter [mm] 43.4 43.4 43.4 43.4 43.4 43.4
43 Thermal resistance [K.m/W] 0.3199 0.3199 0.3199 0.3199 0.3199 0.3199

44 Thermal resistance equation


T
Insulation
45 Thermal resistivity [K.m/W] 3.5 3.5 3.5 3.5 3.5 3.5
46 Layer thickness [mm] 18.0 18.0 18.0 18.0 18.0 18.0
47 Internal diameter [mm] 46.4 46.4 46.4 46.4 46.4 46.4
48 Thermal resistance [K.m/W] 0.01992 0.01992 0.01992 0.01992 0.01992 0.01992

49 T Thermal resistance equation


Insulation
Screen
50 Thermal resistivity [K.m/W] 3.5 3.5 3.5 3.5 3.5 3.5
51 Layer thickness [mm] 1.5 1.5 1.5 1.5 1.5 1.5
52 Internal diameter [mm] 82.4 82.4 82.4 82.4 82.4 82.4
53 Thermal resistance [K.m/W] 0.0 0.0 0.0 0.0 0.0 0.0

54 T Thermal resistance equation


Concentric
wires
55 Thermal resistivity [K.m/W] 0.0 0.0 0.0 0.0 0.0 0.0
56 Layer thickness [mm] 2.12 2.12 2.12 2.12 2.12 2.12
57 Internal diameter [mm] 85.4 85.4 85.4 85.4 85.4 85.4
58 Thermal resistance [K.m/W] 0.0533 0.0533 0.0533 0.0533 0.0533 0.0533

59 Thermal resistance equation


T
Jacket
60 Thermal resistivity [K.m/W] 3.5 3.5 3.5 3.5 3.5 3.5
61 Layer thickness [mm] 4.5 4.5 4.5 4.5 4.5 4.5
62 Internal diameter [mm] 89.64 89.64 89.64 89.64 89.64 89.64
Thermal resistance inside the duct
63 U Constant from IEC6028721 clause4272 1.87 1.87 1.87 1.87 1.87 1.87
64 V Constant from IEC6028721 clause4272 0.312 0.312 0.312 0.312 0.312 0.312
65 Y Constant from IEC6028721 clause4272 0.0037 0.0037 0.0037 0.0037 0.0037 0.0037
66 θm Mean temperature of the medium in conduit [°C] 74.81467 79.8543 82.00483 82.02457 79.84231 74.7679
67 Deq Equivalent diameter of the cables inside the conduit [mm] 98.64 98.64 98.64 98.64 98.64 98.64
Thermal resistance of the medium in conduit
68 T₄' [K.m/W] 0.27467 0.26745 0.26448 0.26445 0.26747 0.27474

Thermal resistance of the duct


69 Do Outer diameter of the conduit [mm] 200.0 200.0 200.0 200.0 200.0 200.0
70 Di Inner diameter of the conduit [mm] 185.0 185.0 185.0 185.0 185.0 185.0
71 ρT Thermal resistivity of the conduit material [K.m/W] 6.0 6.0 6.0 6.0 6.0 6.0
Thermal resistance of the conduit
72 T₄'' [K.m/W] 0.07445 0.07445 0.07445 0.07445 0.07445 0.07445

Thermal resistance of the external medium


73 L Depth of cable/conduit axis [m] 1.5 1.5 1.5 1.5 1.5 1.5
74 De External diameter of the cable conduit [m] 0.2 0.2 0.2 0.2 0.2 0.2
Geometric factor as per IEC60287-2-1 clause 4.2.2
75 u 15.0 15.0 15.0 15.0 15.0 15.0

76 ρTs Thermal resistivity of the soil [K.m/W] 1.5 1.5 1.5 1.5 1.5 1.5
Thermal resistance of the cable isolated
77 T₄'''self [K.m/W] 0.81171 0.81171 0.81171 0.81171 0.81171 0.81171

Thermal resistance associated to the temperature rise due to surrounding heat sources
78 T₄'''mutual [K.m/W] 1.3782 1.70515 1.83902 1.83115 1.70473 1.38353

Temperature rise due to surrounding heat sources


79 Δθint [°C] 19.97308 24.93318 27.02968 27.00215 24.92639 19.98391

Thermal resistance of the external medium


80 T₄''' [K.m/W] 2.18991 2.51686 2.65073 2.64286 2.51644 2.19524

Thermal Capacitance IEC 853-2


81 Thermal capacitance [J/m.K] 4140.0 4140.0 4140.0 4140.0 4140.0 4140.0

82 Q Thermal capacitance equation


Conductor

83 Material surface [mm²] 1200.0 1200.0 1200.0 1200.0 1200.0 1200.0


84 Volumetric specific heat of the material [J/(K*m³)] 3450000.0 3450000.0 3450000.0 3450000.0 3450000.0 3450000.0
85 Thermal capacitance [J/m.K] 507.80693 507.80693 507.80693 507.80693 507.80693 507.80693

86 Q Thermal capacitance equation


Conductor
Shield
87 External diameter [mm] 46.4 46.4 46.4 46.4 46.4 46.4
88 Internal diameter [mm] 43.4 43.4 43.4 43.4 43.4 43.4
89 Volumetric specific heat of the material [J/(K*m³)] 2400000.0 2400000.0 2400000.0 2400000.0 2400000.0 2400000.0
90 Thermal capacitance [J/m.K] 3148.62983 3148.62983 3148.62983 3148.62983 3148.62983 3148.62983

91 Thermal capacitance equation


Q1
Insulation
92 External diameter [mm] 82.4 82.4 82.4 82.4 82.4 82.4
93 Internal diameter [mm] 46.4 46.4 46.4 46.4 46.4 46.4
94 Volumetric specific heat of the material [J/(K*m³)] 2400000.0 2400000.0 2400000.0 2400000.0 2400000.0 2400000.0
95 Thermal capacitance [J/m.K] 5591.53236 5591.53236 5591.53236 5591.53236 5591.53236 5591.53236

96 Thermal capacitance equation


Q2
Insulation
97 External diameter [mm] 82.4 82.4 82.4 82.4 82.4 82.4
98 Internal diameter [mm] 46.4 46.4 46.4 46.4 46.4 46.4
99 Volumetric specific heat of the material [J/(K*m³)] 2400000.0 2400000.0 2400000.0 2400000.0 2400000.0 2400000.0
100 Thermal capacitance [J/m.K] 948.88665 948.88665 948.88665 948.88665 948.88665 948.88665

101 Q Thermal capacitance equation


Insulation
Screen
102 External diameter [mm] 85.4 85.4 85.4 85.4 85.4 85.4
103 Internal diameter [mm] 82.4 82.4 82.4 82.4 82.4 82.4
104 Volumetric specific heat of the material [J/(K*m³)] 2400000.0 2400000.0 2400000.0 2400000.0 2400000.0 2400000.0
105 Thermal capacitance [J/m.K] 260.67223 260.67223 260.67223 260.67223 260.67223 260.67223

106 Thermal capacitance equation

107 Q Number of armour wires 74.0 74.0 74.0 74.0 74.0 74.0
Concentric
108 Mean diameter of armour wire [mm] 2.12 2.12 2.12 2.12 2.12 2.12
wires
109 Length of lay [mm] 956.0 956.0 956.0 956.0 956.0 956.0
110 Mean diameter of armour [mm] 87.52 87.52 87.52 87.52 87.52 87.52
111 Wire Shape is half-circle 0.0 0.0 0.0 0.0 0.0 0.0
112 Thermal capacitance [J/m.K] 3194.0953 3194.0953 3194.0953 3194.0953 3194.0953 3194.0953

113 Thermal capacitance equation


Q
Jacket
114 External diameter [mm] 98.64 98.64 98.64 98.64 98.64 98.64
115 Internal diameter [mm] 89.64 89.64 89.64 89.64 89.64 89.64
116 Volumetric specific heat of the material [J/(K*m³)] 2400000.0 2400000.0 2400000.0 2400000.0 2400000.0 2400000.0
Ampacity
Total external thermal resistance
117 T₄ [K.m/W] 2.53903 2.85875 2.98966 2.98176 2.85835 2.54443

Cable core ampacity


118 I [A] 805.58983 805.58983 805.58983 805.58983 805.58983 805.58983