Distance Protection Study
Distance Protection Study
Commissioning of Substations
Distance Protection: 1. Fault Types: 4. Measuring loop for single- phase faults
Distance protection is a non-unit system of protection, which measures the ◼ Transmission lines 85% The distance protection relays are always set based on the phase
impedance between the relay location and the point where the fault is ◼ Busbar 12% impedance to the fault. The measured Impedance is a function of
incident and compares it with the set value. If the measured impedance is ◼ Transformer/ Generator 3% positive and zero sequence impedance
less than the set value, the relay operates and isolates the faulty section.
Since, the line impedance is directly proportional to line length, we get the ◼ Transient faults
exact location of the fault in kms. Since it protects a certain length of ◼ are common on transmission lines, approximately 80-85%
transmission line, it is called a distance relay. If the measured impedance < ◼ lightnings are the most common reason
setting impedance, the relay operates. ◼ can also be caused by birds, falling trees, swinging lines etc.
◼ will disappear after a short dead interval
So, the input quantities to the distance relay are voltage and current and the
output it gives is V/I which is impedance (Z). Since it uses two input ◼ Persistent faults
quantities, its reliability is more than that of overcurrent relay, which uses ◼ can be caused by a broken conductor fallen down 5. Distance Protection Zones
only one input quantity (i.e., current) ◼ can be a tree falling on a line
◼ must be located and repaired before normal service There could be usually 03 to 05 impedance zone depending upon the
Power lines have impedances of size 0,3- 0,4 ohm/km and normal angles of application.
80-85 degrees. 2. Measuring loop for three- phase faults
The principle of distance protection The distance protection relays are always set based on the phase
ZL =R+jX impedance to the fault. The measured impedance is equal to the
positive sequence impedance up to the fault location
The line impedance must be converted to secondary values with the formula:
𝑽𝑻𝒔𝒆𝒄 𝑪𝑻𝒑𝒓𝒊𝒎
𝒁𝒔𝒆𝒄 = 𝒁𝒑𝒓𝒊𝒎 𝒙 𝒙
𝑽𝑻𝒑𝒓𝒊𝒎 𝑪𝑻𝒔𝒆𝒄
3. Measuring loop for two- phase faults
The distance protection relays are always set based on the phase
impedance to the fault. The measured impedance is equal to the
positive sequence impedance up to the fault location
____________________________________________________________________________________________________________________________________________________________________________________________________________________________________________
Prepared By: Babar Shahzad Date: 18-03-2023 Rev:00 Page 1 of 2
Installation, Maintenance, Testing &
Commissioning of Substations
To provide fast fault clearance for all faults, both transient and
End of Training;
permanent, along the length of the protected circuit, it is necessary to
use a signal aided tripping scheme. The simplest of these is the
Hope after going through all above, each participant has a greater level of
Permissive Under Reach (PUR) protection scheme. The channel for a
understanding regarding distance protection.
PUTT scheme is by operation of the underreaching zone 1 elements of
the relay. If the remote relay has detected a forward fault upon receipt
of this signal, the relay will operate with no additional delay. Faults in
the last 20% (If Zone-1 set to cover 80%) of the protected line are
____________________________________________________________________________________________________________________________________________________________________________________________________________________________________________
Prepared By: Babar Shahzad Date: 18-03-2023 Rev:00 Page 2 of 2