0% found this document useful (0 votes)
67 views56 pages

Brochure - BS88 - Low Voltage Fuses and Fuse Holders

The document provides extensive information about Mersen's BS88 LV fuse links and fuse holders for industrial and residential applications. It includes specifications, characteristics and application information for different fuse link and fuse holder types for various voltages.

Uploaded by

pifehic372
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
67 views56 pages

Brochure - BS88 - Low Voltage Fuses and Fuse Holders

The document provides extensive information about Mersen's BS88 LV fuse links and fuse holders for industrial and residential applications. It includes specifications, characteristics and application information for different fuse link and fuse holder types for various voltages.

Uploaded by

pifehic372
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 56

TITRE

IEC FUSES & FUSEGEAR

B S 8 8 LV
FUSE LINKS
& FUSE HOLDERS
#3

1 Mersen • BS88 LV Fuse Links & Fuse Holders


M E R S E N P R OT E C T I O N
I N I N D U S T R I A L A P P L I C AT I O N S

B
D C A

A B C D E

Main Incomer Main Fuse Distribution Switch Fuse Street Lighting


BTLM 750 Combination Switch Fuse Board BTIS 63 BLST 32
BTKF 315 BTC 100

2 Mersen • BS88 LV Fuse Links & Fuse Holders


M E R S E N P R OT E C T I O N
I N R E S I D E N T I A L A P P L I C AT I O N S

F G H

Feeder Pillar House Service Consumer Unit


BJU BMF 100 BLD 30

3 Mersen • BS88 LV Fuse Links & Fuse Holders


MERSEN

Expertise in Power Protection


Mersen is a global expert in electrical power and advanced materials for high-tech industries. With more
than 135 years of experience, the company is represented in over 50 industrial locations and 16 R&D
centres in 35 countries.

Mersen Electrical Power offers a broad product portfolio in the area of electrical protection and control.
Mersen offers solutions for power management applications, for the development and delivery of custom
tailored solutions and key products for various key markets such as trade, industry, renewable energies,
power electronics and eMobility. The teams at Mersen Electrical Power work together with customers
around the world with Mersen’s mission to make customer applications safer and more reliable.

Mersen is a world leader in fuse technology with a powerful presence in the circuit protection market,
Mersen Electrical Protection Activity offers innovative solutions to enhance the safety of low voltage
installations and equipment.

Above and beyond the supply of products, the company also provides added value in the form of
technical support for OEMs, electrical contractors, panel builders, plant maintenance departments and
utilities.

As a global player, Mersen has established production facilities on every continent to optimise the
availability of products (France, Tunisia, United States, Canada, Mexico, India, Japan and China). All these
locations are united around a global quality, safety and environment policy.

The world-class organisation of Mersen offers tried, tested and approved solutions ensuring the safety and
integrity of our customers equipment protected devices and the safety of people working around them.
Additionally guarding our customer’s electrical equipment and installations over the long term, Mersen can
offer the widest range of safe, reliable electrical and thermal protection solutions.

Mersen solutions are sold all over the world at over 4500 points of sale through professional distributors of
electrical common equipment.

4 Mersen • BS88 LV Fuse Links & Fuse Holders


INDEX

HIGH QUALITY PROTECTION FOR INDUSTRIAL & RESIDENTIAL APPLICATIONS


BS88 LV fuses and fuse holders. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Range Mapping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Comparison Chart. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Offset Bolted Tag Fuse Links (A-type). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Reference Data (415V) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Dimensions & Electrical characteristics (415V) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Reference Data (550V) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Dimensions & Electrical characteristics (550V) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Reference Data (690V) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Dimensions & Electrical characteristics (690V) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Offset Blade Fuse Links (F-type). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Reference Data (550V) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Dimensions & Electrical characteristics (550V) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Central Bolted Tag Fuse Links (B & C-type) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Reference Data (415V) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Dimensions & Electrical characteristics (415V) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Reference Data (690V) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Dimensions & Electrical characteristics (690V) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Time Vs Current Characteristics (415V) - A, B & C type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Time Vs Current Characteristics (415/550V) - A & F type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Time Vs Current Characteristics (690V) - A, B & C type. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Cut-Off Current Characteristics for A, B & C types (415V). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Cut-Off Current Characteristics for A, B, C & F Types (550/690V). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
I2 t characteristics & Power Dissipation chart. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Application Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
BS88 Fuse Holders. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Mersen Fuse Holder Chart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Mersen profile & range mapping. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34

CYLINDRICAL FUSES FOR STREET LIGHTING PROTECTION


BLD/BMD/BLST Fuse Links. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Cylindrical Type BLD Fuse Links. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
BLD time current / cut-off curve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
BS Cylindrical Type BMD Fuse Links. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
BMD time current / cut-off curve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Offset Bolted Tag BLST Fuse Links. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
BLST time current / cut-off curve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43

LOW VOLTAGE DISTRIBUTION WIRING SYSTEMS


Feeder Pillar Fuse Links. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Feeder Pillar Fuse Links 415VAC 80kA. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Feeder Pillar Fuse Links 415VAC 80kA time current / cut-off curve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Feeder Pillar Fuse Links 415VAC 33kA. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Feeder Pillar Fuse Links 415VAC 33kA time current / cut-off curve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Comparison chart. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Application information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Approvals. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55

5 Mersen • BS88 LV Fuse Links & Fuse Holders


H IG H Q UALIT Y
PROTEC TIO N
FO R IN DUSTRIAL
& R ESI DENTIAL
APPLIC ATIO NS

6 Mersen • BS88 LV Fuse Links & Fuse Holders


B S 8 8 LV F U S E S A N D F U S E H O L D E R S

Mersen BS88 fuses UKCA and CE approved


Mersen’s comprehensive range of BS88 low voltage fuses and fuse holders have been
developed to answer today’s demands in various industrial applications, including areas
such as motor protection, utility, cable and device protection which with our high level
performance fuses protect installations and keep people safe in residential and industrial
buildings.

With proven experience in electrical protection, Mersen supports you in defining your
needs according to your application. Furthermore, overcurrent protection for any low
voltage electrical circuit is guaranteed by our design and manufacture.

Mersen provides you with high quality products in compliance with ISO 9001 standard.

All the circuit protection solutions shown in this catalogue are compliant with the RoHS
European Directive. Mersen BS88 fuses are UKCA and CE approved.

For your own safety do NOT open BS88 fuse holders onload.

All items except those marked with * are ASTA 20 certified.

Range Mapping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Comparison Chart. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Offset Bolted Tag Fuse Links (A-type). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Reference Data (415V) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Dimensions & Electrical characteristics (415V) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Reference Data (550V) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Dimensions & Electrical characteristics (550V) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Reference Data (690V) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Dimensions & Electrical characteristics (690V) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Offset Blade Fuse Links (F-type). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Reference Data (550V) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Dimensions & Electrical characteristics (550V) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Central Bolted Tag Fuse Links (B & C-type) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Reference Data (415V) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Dimensions & Electrical characteristics (415V) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Reference Data (690V) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Dimensions & Electrical characteristics (690V) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Time Vs Current Characteristics (415V) - A, B & C type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Time Vs Current Characteristics (415/550V) - A & F type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Time Vs Current Characteristics (690V) - A, B & C type. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Cut-Off Current Characteristics for A, B & C types (415V). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Cut-Off Current Characteristics for A, B, C & F Types (550/690V). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
I2 t characteristics & Power Dissipation chart. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Application Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
BS88 Fuse Holders. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Mersen Fuse Holder Chart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Mersen profile & range mapping. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34

7 Mersen • BS88 LV Fuse Links & Fuse Holders Mersen • BS88 LV Fuse Links & Fuse Holders 7
RANGE MAPPING

BS TYPE DESIGNATION AC / DC CATEGORY CURRENT RATINGS

gG 2, 4, 6, 10, 16, 20, 25, 32


550/250
F1 BNS gM 10M16, 16M20, 20M25, 20M32, 25M32
415 gM 20M36, 32M36, 32M40, 32M50, 32M63
550 gG 2, 4, 6, 10, 16, 20, 25, 32
F2 BES
415 gG 36, 40, 50, 63
BEIT 415/250 gG 36, 40, 50, 63
A1 gG 2, 4, 6, 10, 16, 20, 25, 32
BNIT 550/250
gM 10M16, 16M20, 20M25, 20M32, 25M32
gG 2, 4, 6, 10, 16, 20, 25, 32
550/250
gM 10M16, 16M20, 20M25, 20M32, 25M32
A2 BTIA
gG 2, 4, 6, 10, 16, 20, 25, 32, 36, 40, 50, 63
690/460
gM 10M16, 16M20, 20M25, 20M32, 25M32, 32M36, 32M40, 32M50, 32M63
BTSS 415/240 gG 36, 40, 50, 63
gG 80, 100, 125
BTSDS 415/240
gM 63M80, 63M100, 80M100, 100M125
A3 gG 36, 40, 50, 63, 80, 100, 125, 160
415/240
gM 100M125, 100M160
BTIS
gG 36, 40, 50, 63
690/460
gM 32M36, 32M40, 32M50, 32M63
gG 80, 100, 125
BTSD 415/240
gM 63M80, 63M100, 80M100, 100M125
gG 125, 160
415/240
gM 100M125, 100M160, 100M200
A4 BTCP
gG 36, 40, 50, 63, 80, 100
690/460
gM 32M36, 32M40, 32M50, 32M63, 63M80, 63M100, 80M100
gG 125, 160, 200
BTFP 415/240
gM 200M250, 200M315
BTBC 415/240 gG 32, 40, 50, 63
gG 80, 100, 125
BTSDC 415/240
gM 63M80, 63M100, 80M100, 100M125
B1 gG 125, 160
415/240
gM 100M125, 100M160, 100M200
BTC
gG 80, 100
690/460
gM 63M80, 63M100, 80M100
gG 125, 160, 200
415/240
gM 200M250, 200M315
B2 BTF
gG 125, 160, 200
690/460
gM 125M160, 125M200
gG 250, 315
BTKF 415/240
B3 gM 315M400
BTKF 690/460 gG 250, 315
B3x BTKM 415/240 gG 250, 315
415/240 gG 355, 400
B4 BTMF gG 250, 315, 355, 400
690/460
gM 315M400
415/240 gG 355, 400
C1 BTM
690/460 gG 250, 315, 355, 400
415/240 gG 450, 500, 560, 630
C2 BTTM
690 gG 450, 500, 560, 630
415/240 gG 670, 710, 750, 800
C3 BTLM
690 gG 670, 710, 750, 800

8 Mersen • BS88 LV Fuse Links & Fuse Holders


CO M PA R I S O N C H A R T FO R B S 8 8 LV F U S E L I N K S

COMPETITORS MERSEN BS TYPE REF. RATINGS

NS-415V NSD-550V BNS55Vxx F1 2-32A

ES-415V - BES42Vxx F2 10-36A

- ESD-550V BES55Vxx F2 40-63A

EIT-415V - BEIT42Vxx A1 36-63A

NIT-415V NITD-550V BNIT55Vxx A1 2-32A

TSA-415V AAO-550V BTIA55Vxx A2C 2--32A

TIA-660V H07-690V BTIA69Vxx A2 2-32A

TIS-660V BAO-550V BTIS69Vxx A3 36-63A

TSS-415V - BTSS42Vxx A3C 36-63A

TSDS-415V - BTSDS42Vxx A3 80-125A

TSD-415V - BTSD42Vxx A4C 80-125A

TCP-660V L14-690V BTCP69Vxxx A4/A4C 36-100A

TSDC-415V CD-415V BTSDC42Vxxx B1C 80-125A

TC-660V L09-690V BTC69Vxxx B1 80-100A

TSFP-415V DEO-415V BTFP42Vxxx A4xC 125-200A

TSF-415V DD-415V BTF42Vxxx B2/B2C 125-200A

TFP-660V M09-690V BTF69Vxxx B2 125-200A

TF-660V M09-690V BTF69Vxxx B2 125-200A

TSK-415V N09/P09-690V BTMF69Vxxx B4 250-400A

TKF-660V N09/P09-690V BTMF69Vxxx B4 250-400A

TSMS-415V P11-690V BTM69Vxxx C1 250-400A

TSM-415V P11-690V BTM69Vxxx C1 250-400A

TM-660V P11-690V BTM69Vxxx C1 250-400A

TSTS-415V FF-550V BTTM42Vxxx C2 450-630A

TST-415V FF-550V BTTM42Vxxx C2 450-630A

TTM-660V FF-550V BTTM69Vxxx C2 450-630A

TSLS-415V GF-550V BTLM42Vxxx C3 670-800A

TSL-415V GF-550V BTLM42Vxxx C3 670-800A

TLM-660V GF-550V BTLM69Vxxx C3 670-800A

9 Mersen • BS88 LV Fuse Links & Fuse Holders


O F F S E T B O LT E D TAG F U S E L I N K S (A-T Y P E )

Reference Data
Rated Voltage: 4
 15 V ac Breaking Capacity: 80 kA
240/250 V dc Breaking Capacity: 40 kA
VOLTAGE (V) RATING REFERENCE CATALOGUE BS TYPE STD.
BS TYPE REF (A) NUMBER NUMBER REF PACK

36 M1045269 BTIS42V36 A3 10
40 N1045270 BTIS42V40 A3 10
415 V AC 50 P1045271 BTIS42V50 A3 10
240 V DC 63 Q1045272 BTIS42V63 A3 10
80 R1045273 BTIS42V80 A3 10
100 S1045274 BTIS42V100 A3 10
125 L1019186 BTIS42V125 A3 10
415 V AC 160 M1019187 BTIS42V160 A3 10
240 V DC 100M125 N1019188 BTIS42V100M125 A3 10
100M160 Q1019190 BTIS42V100M160 A3 10
80 Y1019197 BTSD42V80 A4C 10
100 Z1019198 BTSD42V100 A4C 10
125 A1019199 BTSD42V125 A4C 10
415 V AC
63M80 B1019200 BTSD42V63M80 A4C 10
240 V DC
63M100 C1019201 BTSD42V63M100 A4C 10
80M100 X1054363 BTSD42V80M100* A4C 10
100M125 D1019202 BTSD42V100M125 A4C 10
36 T1045275 BTCP42V36 A4C 10
40 Z1045280 BTCP42V40 A4C 10
415 V AC 50 S1045297 BTCP42V50 A4C 10
240 V DC 63 T1045298 BTCP42V63 A4C 10
80 V1045299 BTCP42V80 A4C 10
100 X1045301 BTCP42V100 A4C 10
125 W1019195 BTCP42V125 A4 10
160 X1019196 BTCP42V160 A4 10
415 V AC
100M125 A226297 BTCP42V100M125 A4C 10
240 V DC
100M160 B226298 BTCP42V100M160 A4C 10
100M200 C226299 BTCP42V100M200 A4C 5
125 D226300 BTFP42V125 A4XC 5
160 E226301 BTFP42V160 A4XC 5
415 V AC
200 F226302 BTFP42V200 A4XC 5
240 V DC
200M250 G226303 BTFP42V200M250 A4X 5
200M315 H226304 BTFP42V200M315 A4X 5
INDIAN MARKET ONLY
36 A1019176 BEIT42V36 A1 10
40 B1019177 BEIT42V40 A1 10
Note:
415 V AC
250 V DC 50 C1019178 BEIT42V50 A1 10 1. A3C, A4C represents compact
63 D1019179 BEIT42V63 A1 10 dimensions with respect to BS88/
36 R1019191 BTSS42V36 A3C 10 IEC60269 standards specified
415 V AC 40 S1019192 BTSS42V40 A3C 10 dimensions
240 V DC 50 T1019193 BTSS42V50 A3C 10
63 V1019194 BTSS42V63 A3C 10
80 E1019180J BTSDS42V80 A3 10
2. A4X represents extended rating
100 F1019181J BTSDS42V100 A3 10 with respect to BS88 / IEC 60269
125 G1019182J BTSDS42V125 A3 10 specified ratings
415 V AC
63M80 H1019183J BTSDS42V63M80 A3 10
240 V DC
63M100 J1019184J BTSDS42V63M100 A3 10 2. Note that items marked with an *
80M100 W1054362J BTSDS42V80M100* A3 10 are not ASTA certified
100M125 K1019185J BTSDS42V100M125 A3 10

10 Mersen • BS88 LV Fuse Links & Fuse Holders


O F F S E T B O LT E D TAG F U S E L I N K S (A-T Y P E )

Dimensions
D D
G F G
A A F

E B E B
H

H
Figure 1 Figure 2 J
K
K

DIMENSIONS (MM)
FUSE TYPE
BS REF CURRENT RATING (A)
(FIG. 1) A B D E F G H K
MAX MAX MAX MAX NOM NOM NOM MAX

A1 BEIT 36, 40, 50, 63 39.5 17.1 65.5 11 1.2 55 5.5 18.2
A3C BTSS/BTIS 36, 40, 50, 63 38.8 17.1 84 9.2 1.2 73 5.2 18.5
A3 BTIS 125, 160, 100M125, 100M160 57 26.9 88.5 13 1.2 73 5.5 28

DIMENSIONS (MM)
FUSE TYPE
BS REF CURRENT RATING (A)
(FIG. 2) A B D E F G H J K
MAX MAX MAX MAX NOM NOM NOM NOM MAX

A3 BTSDS/BTIS 80, 100, 125, 63M80, 63M100, 80M100, 100M125 54.5 21 87 12.7 1.2 73 5.5 8 22.5
A4C BTSD/BTCP 36, 40, 50, 63, 80,100,125,63M80, 63M100, 80M100, 100M125 58.5 21 110 14.3 3.2 94 8.7 11 24.5
A4/ A4C BTCP 125, 160, 100M125, 100M160 59.5 26.9 111 19.5 2.4 94 8.7 11 28.5
A4XC /A4C BTFP/BTCP 125, 160, 200, 100M200 47 31 110 19 3.2 94 9 10 32
A4X BTFP 200M250, 200M315 76 41.9 111 19.5 3.2 94 8.7 11 44

Electrical characteristics
I 2 T (AMPERE 2 SECONDS)
FUSE TYPE CURVE TYPE CURRENT RATING (A) WATT LOSS
PRE ARCING TOTAL

BEIT/BTSS/BTCP gG 36 1000 4000 2.8


BEIT/BTSS/BTIS/BTCP gG 40 1300 4200 3.0
BEIT/BTSS/BTIS/BTCP gG 50 2600 8750 3.6
BEIT/BTSS/BTIS/BTCP gG 63 4000 13900 4.7
BTSDS/BTSD/BTIS/BTCP gG 80 8500 38250 6.5
BTSDS/BTSD gM 63M80 8500 38250 5.1
BTSDS/BTSD/BTIS/BTCP gG 100 14000 65000 7.5
BTSDS/BTSD gM 63M100 14000 65000 4.7
BTSDS/BTSD gM 80M100 14000 65000 6
BTSDS/BTSD gG 125 16000 70000 11.5
BTIS/BTCP gG 125 28000 78400 11.3
BTFP gG 125 17000 70000 9.2
BTSDS/BTSD gM 100M125 16000 70000 9.2
BTIS/BTCP gM 100M125 28000 78400 9
BTIS/BTCP gG 160 60000 168000 14.0
BTFP gG 160 57000 150000 10.7
BTIS/BTCP gM 100M160 60000 168000 8.8
BTFP gG 200 105000 293000 16.2
BTCP gM 100M200 105000 293000 8.1
BTFP gM 200M250 190000 532000 19.2
BTFP gM 200M315 270000 756000 19.7

11 Mersen • BS88 LV Fuse Links & Fuse Holders


C E N T R A L B O LT E D TAG F U S E L I N K S (B & C-T Y P E )

Reference Data
Rated Voltage: 415 V ac Breaking Capacity: 80 kA
240 V dc Breaking Capacity: 40 kA

VOLTAGE RATING REFERENCE BS TYPE STD.


CATALOGUE NUMBER
(V) (A) NUMBER REF PACK

32 J226305 BTBC42V32 B1C 10


415 V AC 40 K226306 BTBC42V40 B1C 10
240 V DC 50 L226307 BTBC42V50 B1C 10
63 M226308 BTBC42V63 B1C 10
415 V AC 80 Y1045302 BTC42V80 B1C 10
240 V DC 100 Z1045303 BTC42V100 B1C 10
125 E1019203 BTC42V125 B1 10
160 F1019204 BTC42V160 B1 10
415 V AC 100M125 Q226311 BTC42V100M125 B1C 10
240 V DC
100M160 R226312 BTC42V100M160 B1C 10
100M200 S226313 BTC42V100M200 B1C 5
125 T226314 BTF42V125 B2C 5
160 V226315 BTF42V160 B2C 5
415 V AC 200 W226316 BTF42V200 B2C 5
240 V DC
200M250 X226317 BTF42V200M250 B2 1
200M315 Y226318 BTF42V200M315 B2 1
250 Z226319 BTKF42V250 B3 1
415 V AC 315 A226320 BTKF42V315 B3 1
240 V DC
315M400 B226321 BTKF42V315M400 B3 1
415 V AC 250 C226322 BTKM42V250 B3X 1
240 V DC 315 D226323 BTKM42V315 B3X 1
415 V AC 355 E226324 BTMF42V355 B4 1
240 V DC 400 F226325 BTMF42V400 B4 1
415 V AC 355 G226326 BTM42V355 C1 1
240 V DC 400 H226327 BTM42V400 C1 1
450 J226328 BTTM42V450 C2 1
415 V AC 500 K226329 BTTM42V500 C2 1
240 V DC 560 L226330 BTTM42V560 C2 1
630 M226331 BTTM42V630 C2 1
670 N226332 BTLM42V670 C3 1
415 V AC 710 P226333 BTLM42V710 C3 1
240 V DC 750 Q226334 BTLM42V750 C3 1
800 R226335 BTLM42V800 C3 1
INDIAN MARKET ONLY
80 G1019205 BTSDC42V80 B1C 10
100 H1019206 BTSDC42V100 B1C 10
125 J1019207 BTSDC42V125 B1C 10
415 V AC
63M80 K1019208 BTSDC42V63M80 B1C 10
240 V DC
63M100 L1019209 BTSDC42V63M100 B1C 10 Note:
80M100 Y1054364 BTSDC42V80M100* B1C 10 1. B1C, B2C represents compact
100M125 M1019210 BTSDC42V100M125 B1C 10 dimensions with respect to BS88/
IEC60269 standards specified
dimensions

2. B3X represents extended rating


with respect to BS88 / IEC 60269
specified ratings

2. Note that items marked with an *


are not ASTA Certified
12 Mersen • BS88 LV Fuse Links & Fuse Holders
C E N T R A L B O LT E D TAG F U S E L I N K S (B & C-T Y P E )

Dimensions
D
G D
B
A F L G L
A

H
E

H
J
B F
Figure 1 Figure 2 J

DIMENSIONS (MM)
BS REF FUSE TYPE CURRENT RATING (A)
A MAX B MAX D MAX E MAX F NOM G NOM H NOM J NOM LNOM

FIG. 1

B1C BTBC 32, 40, 50, 63 57 26.9 137 19.5 3.2 111 8.7 14 -
B1C BTSDC/BTC 80, 100, 125, 63M80, 63M100, 80M100, 100M125 58.5 21 127 14.3 3.2 111 8.7 11.1 -
B1/B1C BTC 125, 160, 100M125, 100M160 57 26.9 137 19.5 3.2 111 8.7 14 -
B1C/B2C BTC/BTF 125, 160, 200, 100M200 47 31 136 19 3.2 111 9 12.5 -
B2/B3 BTF/ BTKF 250, 315, 200M250, 200M315 73 41.9 138 19.5 3.2 111 8.7 14 -
B3X BTKM 250, 315 73 41.9 159 26 3.2 133 10.3 14 -
B3 BTKF 250, 315, 315M400 75 59.1 138 26 4.8 111 8.7 14 -
B4 BTMF 355, 400 75 59.1 138 26 4.8 111 8.1 14 -
FIG. 2

C1 BTM 355, 400 75 59.1 212 26 4.8 133 10.3 16 25.4


C2 BTTM 450, 500, 560, 630 83 74.4 212 26 6.3 133 10.3 16 25.4
C3 BTLM 670, 710, 750, 800 86 82.4 212 26 9.5 133 10.3 16 25.4

Electrical characteristics
I 2 T (AMPERE 2 SECONDS)
FUSE TYPE CURVE TYPE CURRENT RATING (A) WATT LOSS
PRE ARCING TOTAL

BTBC gG 32 700 3000 3.6


BTBC gG 40 1300 5850 4.0
BTBC gG 50 2600 11700 4.8
BTBC gG 63 4000 17500 5.9
BTSDC/BTIS gG 80 8500 38250 6.5
BTSDC gM 63M80 8500 38250 5.1
BTSDC/BTIS gG 100 14000 65000 7.5
BTSDC gM 63M100 14000 65000 4.7
BTSDC gM 80M100 14000 65000 6
BTSDC gG 125 16000 70000 11.5
BTC gG 125 28000 78400 11.3
BTF gG 125 17000 70000 9.2
BTSDC gM 100M125 16000 70000 9.2
BTC gM 100M125 28000 78400 9
BTC gG 160 60000 168000 14.0
BTF gG 160 57000 150000 10.7
BTC gM 100M160 60000 168000 8.8
BTF gG 200 105000 293000 16.2
BTC gM 100M200 105000 293000 8.1
BTKF/BTKM gG 250 190000 532000 24
BTF gM 200M250 190000 532000 19.2
BTKF/BTKM gG 315 270000 756000 31
BTF gM 200M315 270000 756000 19.7
BTKF gM 315M400 505000 1414000 30
BTMF/BTM gG 355 395000 1106000 32
BTMF/BTM gG 400 505000 1414000 38
BTTM gG 450 650000 1820000 42
BTTM gG 500 850000 2380000 48
BTTM gG 560 1200000 3360000 50
BTTM gG 630 1546000 4437000 54
BTLM gG 670 1950000 5460000 60
BTLM gG 710 2400000 6720000 62
BTLM gG 750 3000000 8400000 65
BTLM gG 800 3769000 10900000 68

13 Mersen • BS88 LV Fuse Links & Fuse Holders


T I M E VS . C U R R E N T C H A R AC T E R I S T I C S

gG Curves - 32 to 800A - 415 V ac

250A 250A
200A 200A
160A 160A
125A 125A
100A 100A
80A 80A
63A 63A
50A 50A
40A 40A
36A 36A
32A 32A

315A 315A
355A 355A
400A 400A
450A 450A
500A 500A
560A 560A
630A 630A
670A 670A
710A 710A
750A 750A
800A 800A

gM Curves - 63M80 to 315M400A - 415V ac

14 Mersen • BS88 LV Fuse Links & Fuse Holders


C U T- O F F C U R R E N T C H A R AC T E R I S T I C S

A, B & C Type - 415 V ac

Prospective current (SYM. R.M.S. kA)

15 Mersen • BS88 LV Fuse Links & Fuse Holders


O F F S E T B L A D E /O F F S E T TAG F U S E L I N K S
(F& A-T Y P E )

Reference Data
Rated Voltage: 415/550 V ac Breaking Capacity: 80 kA
250 V dc Breaking Capacity: 40 kA
VOLTAGE (V) RATING (A) REFERENCE NO. CATALOGUE NO. BS TYPE REF STD. PACK

2 C1006643 BNS55V2 F1 10
4 D1006644 BNS55V4 F1 10
6 E1006645 BNS55V6 F1 10
10 N1019211 BNS55V10 F1 10
16 P1019212 BNS55V16 F1 10
20 Q1019213 BNS55V20 F1 10
550 V AC
25 R1019214 BNS55V25 F1 10
250 V DC
32 S1019215 BNS55V32 F1 10
10M16 T1019216 BS55V10M16 F1 10
16M20 V1019217 BNS55V16M20 F1 10
20M25 W1019218 BNS55V20M25 F1 10
20M32 X1019219 BNS55V20M32 F1 10
25M32 Z1019221 BNS55V25M32 F1 10
20M36 D1036981 BNS42V20M36* F1 10
32M36 E1036982 BNS42V32M36* F1 10
415 V AC 32M40 F1036983 BNS42V32M40* F1 10
32M50 G1036984 BNS42V32M50* F1 10
32M63 H1036985 BNS42V32M63* F1 10
2 Y1050799 BES55V2* F2 10
4 Z1050800 BES55V4* F2 10
6 A1050801 BES55V6* F2 10
10 F1006646 BES55V10 F2 10
550 V AC 16 G1006647 BES55V16 F2 10
20 H1006648 BES55V20 F2 10
25 J1006649 BES55V25 F2 10
32 K1006650 BES55V32 F2 10
36 L1006651 BES55V36 F2 10
40 J226351 BES42V40 F2 10
415 V AC 50 K226352 BES42V50 F2 10
63 L226353 BES42V63 F2 10
2 E1006576 BNIT55V2 A1 10
4 F1006577 BNIT55V4 A1 10
6 G1006578 BNIT55V6 A1 10
10 B1019223 BNIT55V10 A1 10
16 C1019224 BNIT55V16 A1 10
20 D1019225 BNIT55V20 A1 10
550 V AC
25 E1019226 BNIT55V25 A1 10
250 V DC
32 F1019227 BNIT55V32 A1 10
10M16 G1019228 BNIT55V10M16 A1 10
16M20 H1019229 BNIT55V16M20 A1 10
20M25 J1019230 BNIT55V20M25 A1 10
20M32 K1019231 BNIT55V20M32 A1 10
25M32 R1019237 BNIT55V25M32 A1 10
2 S1019238 BTIA55V2 A2C 10
4 T1019239 BTIA55V4 A2C 10
6 V1019240 BTIA55V6 A2C 10
10 W1019241 BTIA55V10 A2C 10
16 X1019242 BTIA55V16 A2C 10
20 Y1019243 BTIA55V20 A2C 10
550 V AC
25 Z1019244 BTIA55V25 A2C 10
250 V DC
32 A1019245 BTIA55V32 A2C 10 Note:
10M16 B1019246 BTIA55V10M16 A2C 10
16M20 C1019247 BTIA55V16M20 A2C 10 1. A2C, represents compact dimensions
20M25 D1019248 BTIA55V20M25 A2C 10 with respect to BS88/ IEC60269
20M32 E1019249 BTIA55V20M32 A2C 10 standards specified dimensions
25M32 F1019250 BTIA55V25M32 A2C 10
32M40 G226280 BTIA42V32M40 A2 10
415 V AC
250 V DC
32M50 H226251 BTIA42V32M50 A2 10 2. Note that items marked with an *
32M63 K226283 BTIA42V32M63 A2 10
are not ASTA Certified

16 Mersen • BS88 LV Fuse Links & Fuse Holders


O F F S E T B L A D E /O F F S E T TAG F U S E L I N K S
(F& A-T Y P E )

Dimensions
Rated Voltage: 415/550 V ac Breaking Capacity: 80 kA
D F A
D F
D A
F A
E

NN N
E
E B
B
B

DIMENSIONS (MM)
FUSE
BS REF CURRENT RATING (A)
TYPE
A MAX B MAX D MAX E MAX F NOM N NOM

F1 BNS 2, 4, 6, 10, 16, 20, 25, 32, 10M16, 16M20, 20M25, 20M32, 25M32 35.5 13.5 61 12.7 0.8 3.5
F1 BNS 20M36, 32M36, 32M40, 32M50, 32M63 35.5 17.1 61 12.7 0.8 3.5
F2 BES 2, 4, 6, 10, 16, 20, 25, 32, 36, 40, 50, 63 39.5 17.1 69 15.2 1.2 3.5

DIMENSIONS (MM)
BS FUSE
CURRENT RATING (A)
REF TYPE A MAX B MAX D MAX E MAX F NOM G NOM H NOM K MAX

A1 BNIT 2, 4, 6, 10, 16, 20, 25, 32, 10M16, 16M20, 20M25, 20M32, 25M32 35.5 13.5 56 11.2 0.8 44.5 4.8 14.5

DIMENSIONS (MM)
BS FUSE
CURRENT RATING (A)
REF TYPE A B D E F G H J K
MAX MAX MAX MAX NOM NOM NOM MAX NOM

A2C BTIA 2, 4, 6, 10, 16, 20, 25, 32, 10M16, 16M20, 20M25, 20M32, 25M32 35.5 13.5 86 9.2 0.8 73 8 5.5 14.5
A2 BTIA 32M40, 32M50, 32M63 56.5 21.9 86 9.2 1.2 73 8 5.5 23.5

17 Mersen • BS88 LV Fuse Links & Fuse Holders


O F F S E T B L A D E /O F F S E T TAG F U S E L I N K S
(F& A-T Y P E )

Electrical characteristics
I 2 T (AMPERE 2 SECONDS)
FUSE TYPE CURVE TYPE CURRENT RATING (A) WATT LOSS
PRE ARCING TOTAL

BNS/BNIT/BTIA gG 2 1 5 0.9

BNS/BNIT/BTIA gG 4 7.6 38 1.5

BNS/BNIT/BTIA gG 6 28 40 1.8

BNS/BNIT/BTIA/BES gG 10 70 350 1.2

BNS/BNIT/BTIA/BES gG 16 120 550 1.6

BNS/BNIT/BTIA gM 10M16 120 550 1

BNS/BNIT/BTIA/BES gG 20 250 1250 1.7

BNS/BNIT/BTIA gM 16M20 250 1250 1.36

BNS/BNIT/BTIA/BES gG 25 420 2100 2

BNS/BNIT/BTIA gM 20M25 420 2100 1.6

BNS/BNIT/BTIA/BES gG 32 670 3350 2.9

BNS/BNIT/BTIA gM 20M32 670 3350 1.8

BNS/BNIT/BTIA gM 25M32 670 3350 2.3

BNS/BES gG 36 700 4000 2.8

BNS gM 20M36 700 4000 1.6

BNS/BES gG 40 1300 4200 3

BNS gM 32M40 1300 4200 2.4

BNS/BES gG 50 2600 8750 3.6

BNS gM 32M50 2600 8750 2.3

BNS/BES gG 63 4000 13900 4.7

BNS gM 32M63 4000 13900 2.4

18 Mersen • BS88 LV Fuse Links & Fuse Holders


T I M E VS . C U R R E N T C H A R AC T E R I S T I C S

gG Curve-2 to 63A - 415/550 V ac

gM Curve-10M16 to 32M63-415/550 V ac

19 Mersen • BS88 LV Fuse Links & Fuse Holders


O F F S E T B O LT E D TAG F U S E L I N K S (A-T Y P E )

Reference Data
Rated Voltage: 690 V ac Breaking Capacity: 80 kA
460 V dc Breaking Capacity: 40 kA
VOLTAGE REFERENCE BS TYPE STD.
RATING (A) CATALOGUE NUMBER
(V) NUMBER REF PACK

2 G1019251 BTIA69V2 A2 10
4 H1019252 BTIA69V4 A2 10
6 J1019253 BTIA69V6 A2 10
10 K1019254 BTIA69V10 A2 10
16 L1019255 BTIA69V16 A2 10
20 M1019256 BTIA69V20 A2 10
25 N1019257 BTIA69V25 A2 10
32 P1019258 BTIA69V32 A2 10
10M16 A1019751 BTIA69V10M16 A2 10
16M20 B1019752 BTIA69V16M20 A2 10
690 V AC
20M25 Q1019259 BTIA69V20M25 A2 10
460 V DC
20M32 R1019260 BTIA69V20M32 A2 10
25M32 C1019753 BTIA69V25M32 A2 10
36 S1019261 BTIA69V36 A2 10
40 T1019262 BTIA69V40 A2 10
50 V1019263 BTIA69V50 A2 10
63 W1019264 BTIA69V63 A2 10
32M36 A1019268 BTIA69V32M36 A2 10
32M40 X1019265 BTIA69V32M40 A2 10
32M50 Y1019266 BTIA69V32M50 A2 10
32M63 Z1019267 BTIA69V32M63 A2 10
36 N1006584 BTIS69V36 A3 10
40 P1006585 BTIS69V40 A3 10
50 Q1006586 BTIS69V50 A3 10

690 V AC 63 R1006587 BTIS69V63 A3 10


460 V DC 32M36 C1019270 BTIS69V32M36 A3 10
32M40 D1006598 BTIS69V32M40 A3 10
32M50 E1006599 BTIS69V32M50 A3 10
32M63 F1006600 BTIS69V32M63 A3 10
36 H1019275 BTCP69V36 A4C 10
40 M1006606 BTCP69V40 A4C 10
50 N1006607 BTCP69V50 A4C 10
63 J1019276 BTCP69V63 A4C 10
32M36 K1019277 BTCP69V32M36 A4C 10
32M40 L1019278 BTCP69V32M40 A4C 10
690 V AC
32M50 M1019279 BTCP69V32M50 A4C 10
460 V DC Note:
32M63 N1019280 BTCP69V32M63 A4C 10
1. A4C represents compact dimensions
80 S1006611 BTCP69V80 A4 10
with respect to BS88/ IEC60269
100 T1006612 BTCP69V100 A4 10
standards specified dimensions
63M80 V1006613 BTCP69V63M80 A4 10
63M100 W1006614 BTCP69V63M100 A4 10
2. Note that items marked with an *
80M100 Z1054365 BTCP69V80M100* A4 10
are not ASTA Certified

20 Mersen • BS88 LV Fuse Links & Fuse Holders


O F F S E T B O LT E D TAG F U S E L I N K S (A-T Y P E )

Dimensions

D
G F
A

E B

H
J K

DIMENSIONS (MM)
BS FUSE
CURRENT RATING (A)
REF TYPE A B D E F G H J K
MAX MAX MAX MAX NOM NOM NOM NOM MAX

A2 BTIA 2, 4, 6, 10, 16, 20, 25, 32, 10M16, 16M20, 20M25, 20M32, 25M32 56.5 21.9 86 9.2 1.2 73 8 5.5 23.5
A2 BTIA 36, 40, 50, 63, 32M36, 32M40, 32M50, 32M63 54.5 21 86 8.7 1.2 73 8 5.5 22.3
A3 BTIS 36, 40, 50, 63, 32M36, 32M40, 32M50, 32M63 54.5 21 87 12.7 1.2 73 8 5.5 22.5
A4C BTCP 36, 40, 50, 63, 32M36, 32M40, 32M50, 32M63 57.5 21 109 14.3 3.2 94 11 8.7 22.3
A4 BTCP 80, 100, 63M80, 63M100, 80M100 59.5 26.9 111 19.5 2.4 94 11 8.7 28.5

Electrical characteristics
I 2 T (AMPERE 2 SECONDS)
FUSE TYPE CURVE TYPE CURRENT RATING (A) WATT LOSS
PRE ARCING TOTAL

BTIA gG 2 1 6.5 0.8


BTIA gG 4 7.6 50 1.4
BTIA gG 6 28 180 1.7
BTIA gG 10 70 380 1.2
BTIA gG 16 120 580 1.6
BTIA gM 10M16 120 580 1
BTIA gG 20 250 1450 1.7
BTIA gM 16M20 250 1450 1.4
BTIA gG 25 420 2500 2.0
BTIA gM 20M25 420 2500 1.6
BTIA gG 32 670 3900 2.9
BTIA gM 20M32 670 3900 1.8
BTIA gM 25M32 670 3900 2.3
BTIA/BTIS/BTCP gG 36 700 4500 3.8
BTIA/BTIS/BTCP gM 32M36 700 4500 3.4
BTIA/BTIS/BTCP gG 40 1300 7400 4.0
BTIA/BTIS/BTCP gM 32M40 1300 7400 3.2
BTIA/BTIS/BTCP gG 50 2600 15000 4.8
BTIA/BTIS/BTCP gM 32M50 2600 15000 3
BTIA/BTIS/BTCP gG 63 4000 23000 5.9
BTIA/BTIS/BTCP gM 32M63 4000 23000 3
BTCP gG 80 8500 48500 6.5
BTCP gM 63M80 8500 48500 5.1
BTCP gG 100 14000 80000 7.5
BTCP gM 63M100 14000 80000 4.7
BTCP gM 80M100 14000 80000 6

21 Mersen • BS88 LV Fuse Links & Fuse Holders


C E N T R A L B O LT E D TAG F U S E L I N K S (B & C-T Y P E )

Reference Data
Rated Voltage: 690 V ac Breaking Capacity: 80 kA
460 V dc Breaking Capacity: 40 kA
VOLTAGE REFERENCE BS TYPE STD.
RATING (A) CATALOGUE NUMBER
(V) NUMBER REF PACK

80 B1019775J BTC69V80 B1 10

100 A1006618J BTC69V100 B1 10


690 V AC
63M80 B1006619J BTC69V63M80 B1 10
460 V DC
63M100 C1006620J BTC69V63M100 B1 10

80M100 A1054366J BTC69V80M100* B1 10

125 D1006621E BTF69V125 B2 5

160 E1006622E BTF69V160 B2 5


690 V AC
200 F1006623E BTF69V200 B2 5
460 V DC
125M160 G1006624E BTF69V125M160 B2 5

125M200 H1006625E BTF69V125M200 B2 5

250 P1036991A BTKF69V250 B3 1


690 V AC
460 V DC
315 Q1036992A BTKF69V315 B3 1

250 J1006626A BTMF69V250 B4 1

315 K1006627A BTMF69V315 B4 1


690 V AC
355 L1006628A BTMF69V355 B4 1
460 V DC
400 M1006629A BTMF69V400 B4 1

315M400 N1006630A BTMF69V315M400 B4 1

250 P1006631A BTM69V250 C1 1

315 R1006633A BTM69V315 C1 1


690 V AC
460 V DC
355 S1006634A BTM69V355 C1 1

400 W1006637A BTM69V400 C1 1

450 Y1006639A BTTM69V450 C2 1

500 Z1006640A BTTM69V500 C2 1


690 V AC
560 A1006641A BTTM69V560 C2 1

630 B1006642A BTTM69V630 C2 1

670 D1019271A BTLM69V670 C3 1

710 E1019272A BTLM69V710 C3 1


690 V AC
750 F1019273A BTLM69V750 C3 1 Note:
1. Note that items marked with an *
800 G1019274A BTLM69V800 C3 1
are not ASTA Certified.

22 Mersen • BS88 LV Fuse Links & Fuse Holders


C E N T R A L B O LT E D TAG F U S E L I N K S (B & C-T Y P E )

Dimensions
D
D
G
G
A F
A F

HH
E E

J
J B
B

DIMENSIONS (MM)
BS REF FUSE TYPE CURRENT RATING (A)
A MAX B MAX D MAX E MAX F NOM G NOM H NOM J NOM

B1 BTC 80, 100, 63M80, 63M100, 80M100 57 26.9 137 19.5 3.2 111 8.7 14
B2 BTF 125, 160, 200, 125M160, 125M200 73 41.9 138 19.5 3.2 111 8.7 14
B3 BTKF 250, 315 73 41.9 138 19.5 3.2 111 8.7 14
B4 BTMF 250, 315, 355, 400, 315M400 75 59.1 138 26 4.8 111 8.7 14
D
D B
L G L B
L G
A L
A
E E

HH

J F
J F

DIMENSIONS (MM)
BS REF FUSE TYPE CURRENT RATING (A)
A MAX B MAX D MAX E MAX F NOM G NOM H NOM J NOM L NOM

C1 BTM 250, 315, 355, 400 75 59.1 212 26 4.8 133 10.3 16 25.4
C2 BTTM 450, 500, 560, 630 83 74.4 212 26 6.3 133 10.3 16 25.4
C3 BTLM 670, 710, 750, 800 86 82.4 212 26 9.5 133 10.3 16 25.4

Electrical characteristics
I 2 T (AMPERE 2 SECONDS)
FUSE TYPE CURVE TYPE CURRENT RATING (A) WATT LOSS
PRE ARCING TOTAL

BTC gG 80 8500 48500 6.5


BTC gM 63M80 8500 48500 5.1
BTC gG 100 14000 80000 7.5
BTC gM 63M100 14000 80000 4.7
BTC gM 80M100 14000 80000 6
BTF gG 125 28000 140000 11.3
BTF gG 160 60000 300000 14.5
BTF gM 125M160 60000 300000 11.3
BTF gG 200 105000 350000 16.2
BTF gM 125M200 105000 350000 10.1
BTMF/BTM/BTKF gG 250 190000 700000 24
BTMF/BTM/BTKF gG 315 270000 1350000 31
BTMF/BTM gG 355 395000 1975000 32
BTMF/BTM gG 400 505000 2525000 38
BTMF gM 315M400 505000 2525000 30
BTTM gG 450 650000 3300000 42
BTTM gG 500 850000 4250000 48
BTTM gG 560 1200000 5800000 50
BTTM gG 630 1546000 9800000 54
BTLM gG 670 1950000 10100000 60
BTLM gG 710 2400000 12000000 62
BTLM gG 750 3000000 14200000 65
BTLM gG 800 3769000 15000000 68

23 Mersen • BS88 LV Fuse Links & Fuse Holders


T I M E VS . C U R R E N T C H A R AC T E R I S T I C S

gG Curves - 2 to 800A - 690 V ac


250A
200A
160A
125A
250A
100A
200A
80A
160A
63A
125A
50A
100A
40A
80A
36A
63A
32A
50A
40A
36A
32A

315A
355A
400A
450A
315A
500A
355A
560A
400A
630A
450A
670A
500A
710A
560A
750A
630A
800A
670A
710A
750A
800A

gM Curves - 10M16 to 315M400A - 690 V ac

24 Mersen • BS88 LV Fuse Links & Fuse Holders


C U T- O F F C U R R E N T C H A R AC T E R I S T I C S

A, B, C, & F - Type 550/690 V ac

Prospective current (SYM. R.M.S. kA)

25 Mersen • BS88 LV Fuse Links & Fuse Holders


I 2 T C H A R AC T R I S T I C S

(Ampere
(Ampere
I2 t let-through
I2 t let-through 2 2
seconds)
seconds)

Fuse-link rating (A)

Fuse-link rating (A)

Power dissipation chart


(Watts)(Watts)
Power dissipation
Power dissipation

Current rating (A)

26 Mersen • BS88 LV Fuse Links & Fuse Holders Current rating (A)
A P P L I C AT I O N I N FO R M AT I O N

Voltage rating selection Motor circuit protection


BS88 fuses comply with IEC 60269 standards. They The motor starter manufacturers generally recommend
are tested under a voltage at least 10% higher than the the fuse link rating to be used in conjunction with the
fuse rated voltage. motor starter. Type 2 co-ordination is easily obtained
with Mersen fuses in view of having the pre-arcing I2t
Ambient temperature values closer to the lower limit of the specified limits of
the standard. The gM fuse selection as for an aM fuse
Above an ambient of 40°C a general de-rating of 0.5% requires the melt current at 5 seconds is 7 times the
of the fuse-link rated current per excess degree fuse rating.
centigrade is recommended.
Protection against electrical shock
Cable protection
The rule is to disconnect within a time specified by
gG fuses protect cables against both overload and local standards. Generally wiring regulations require a
short circuit. The cable is protected when the following disconnecting time not exceeding 5 seconds for a
conditions are fulfilled. distribution circuit. It will be less than 1 second in many
other cases. The maximum value of each fault loop

IB ≤ IN ≤ Iz
impedance (Zs) for gG fuse link for BS88: part 2 & 6
are as shown at 240V.

IF ≤ 1.45Iz RATING (A) Z S (OHMS)

IB : Operating current of the cable 2 40.00


Iz : Maximum current carrying capacity of the cable 4 20.00
IN : Rated current of the fuse 6 15.00
IF : Conventional fusing current of the fuse 10 8.00
16 4.90

Capacitor circuit protection 20 3.48


25 2.67
The fuse selection must take into account: 32 2.18

• The inrush current occurring when the capacitor 36 1.85


is switched on. 40 1.60
50 1.26
• The harmonic currents during the normal operation
63 0.93
of the network.
80 0.68
• Capacitor tolerances. 100 0.48

The fuse link should be chosen with a current rating 125 0.43
greater than 1.7 times the rated capacitor current. 160 0.29
Correction for ambient temperature higher than 40°C 200 0.22
must be added. 250 0.171
315 0.137
Transformer protection 355 0.126
Fuses must be fitted both in the primary and the 400 0.114
secondary of the transformer. The fuse selection must 450 0.100
take into account the high transient inrush current
500 0.086
in the primary of the transformer. Consequently the
normal current rating of the fuse links on the primary 560 0.077
side of transformers should be at least twice the 630 0.071
nominal transformer primary current. The normal 670 0.063
In value of the fuse links on the secondary side 710 0.056
of transformers is at least equal to the nominal
750 0.053
transformer secondary current when the temperature
does not exceed 40°C. 800 0.050

27 Mersen • BS88 LV Fuse Links & Fuse Holders


BS88 FUSE HOLDERS & NEUTR AL LINK

For Offset Blade & Bolted Tag Fuse Links


For Offset Blade & Bolted Tag Solid Neutral link
Fuse Links PART E1 PACK NOMINAL E1 CAT
VOLTAGE
NUMBER SIZE CURRENT (A) NUMBER
Fuse holders from Mersen comply with BS88-1
D239134 550 10 32 BNEUTRALF1
and BS88-6: 1988. The fuse holders are designed
E239135 550 10 63 BNEUTRALF2
to prevent direct contact with live parts when being F239136 550 10 32 BNEUTRALA1
inserted or removed, preventing any likelihood G239137 690 10 32 BNEUTRALA2
of inadvertent contact with live metal. Also, cable H239138 690 10 63 BNEUTRALA3
terminals within the fuse base are fully shrouded J239139 690 10 125 BNEUTRALA4
when holder is removed (product is IP2X Classified). Q1065581 690 5 200 BNEUTRALB2
R1065582 690 5 400 BNEUTRALB4
T1065584 690 5 800 BNEUTRALC3
S1065583 690 5 400 BNEUTRALC1

Type Of Connection

BFF Front wire connected BBB Back stud connected BFB Front Back (busbar)
(front-front) 3 connection styles (back-back) Mounting on board stud connected Mounting
possible: Mounting on board with with two cables on the back on board with upstream or
cable upstream and downstream (connection via lug. see table) downstream cable and back cable

Advantages
1. DIN Rail Mounting for ease of assembly

2. Safety Shrouds

3. Options for colour and terminations

4. RoHs compliance

28 Mersen • BS88 LV Fuse Links & Fuse Holders


BS88 FUSE HOLDERS & NEUTR AL LINK

For Offset Blade & Bolted Tag Fuse Links


NOMINAL REFERENCE CATALOGUE STANDARD MERSEN FUSE/NEUTRAL
TYPE VOLTAGE RATING (V) COLOUR CONNECTION
CURRENT (A) NUMBER NUMBER PACK LINK TYPE

F1 550 32 Black Front-Front A230138 BFF32F1 6


F1 550 32 Black Back-Back N239120 BBB32F1 6
F1 550 32 Black Front-Back B230139 BFB32F1 6
BNS55Vxx
F1 550 32 Green Front-Front B1012553 BFF32F1G 6
F1 550 32 Green Back-Back V1012547 BBB32F1G 6
F1 550 32 Green Front-Back Y1012550 BFB32F1G 6
F1 550 32 White Front-Front P239121 BFF32F1W 6
F1 550 32 White Back-Back Q239122 BBB32F1W 6 BNEUTRALF1
F1 550 32 White Front-Back R239123 BFB32F1W 6
F2 550 63 Black Front-Front S239124 BFF63F2 6
F2 550 63 Black Back-Back T239125 BBB63F2 6
F2 550 63 Black Front-Back V239126 BFB63F2 6 BES55Vxx
F2 550 63 Green Front-Front Z239130 BFF63F2G 6 BES42Vxx
F2 550 63 Green Back-Back A239131 BBB63F2G 6
F2 550 63 Green Front-Back B239132 BFB63F2G 6
F2 550 63 White Front-Front W239127 BFF63F2W 6
F2 550 63 White Back-Back X239128 BBB63F2W 6 BNEUTRALF2
F2 550 63 White Front-Back Y239129 BFB63F2W 6
A1 550 32 Black Front-Front D239088 BFF32A1 6
A1 550 32 Black Back-Back E239089 BBB32A1 6
A1 550 32 Black Front-Back F239090 BFB32A1 6
BNIT55Vxx
A1 550 32 Green Front-Front K239094 BFF32A1G 6
A1 550 32 Green Back-Back L239095 BBB32A1G 6
A1 550 32 Green Front-Back M239096 BFB32A1G 6
A1 550 32 White Front-Front G239091 BFF32A1W 6
A1 550 32 White Back-Back H239092 BBB32A1W 6 BNEUTRALA1
A1 550 32 White Front-Back J239093 BFB32A1W 6
A2 690 32 Black Front-Front C230140 BFF32A2 6
A2 690 32 Black Back-Back P1012542 BBB32A2 6
A2 690 32 Black Front-Back D230141 BFB32A2 6 BTIA55Vxx
A2 690 32 Green Front-Front Z1012551 BFF32A2G 6 BTIA69Vxx
A2 690 32 Green Back-Back S1012545 BBB32A2G 6
A2 690 32 Green Front-Back W1012548 BFB32A2G 6
A2 690 32 White Front-Front A1012552 BFF32A2W 6
A2 690 32 White Back-Back T1012546 BBB32A2W 6 BNEUTRALA2
A2 690 32 White Front-Back X1012549 BFB32A2W 6
A3 690 63 Black Front-Front F230143 BFF63A3 6
A3 690 63 Black Back-Back V239103 BBB63A3 6 BTSS42Vxx
A3 690 63 Black Front-Back G230144 BFB63A3 6 BTSDS42Vxx
A3 690 63 Green Front-Front Z239107 BFF63A3G 6 BTSDS42Vxxx
A3 690 63 Green Back-Back A239108 BBB63A3G 6 BTIS69Vxx
A3 690 63 Green Front-Back B239109 BFB63A3G 6
A3 690 63 White Front-Front W239104 BFF63A3W 6
A3 690 63 White Back-Back X239105 BBB63A3W 6 BNEUTRALA3
A3 690 63 White Front-Back Y239106 BFB63A3W 6
A4 690 125 Black Front-Front H230145 BFF125A4 1
A4 690 125 Black Back-Back C239110 BBB125A4 1
A4 690 125 Black Front-Back J230146 BFB125A4 1 BTSD42Vxxx
BTCP42Vxxx
A4 690 125 Green Front-Front K239117 BFF125A4G 1 BTCP69Vxxx
A4 690 125 Green Back-Back L239118 BBB125A4G 1
A4 690 125 Green Front-Back M239119 BFB125A4G 1
A4 690 125 White Front-Front D239111 BFF125A4W 1
A4 690 125 White Back-Back E239112 BBB125A4W 1 BNEUTRALA4
A4 690 125 White Front-Back F239113 BFB125A4W 1

Additional neutral links


REFERENCE NUMBER CATALOGUE NUMBER MERSEN FUSE/NEUTRAL LINK TYPE

Q1065581 BNEUTRALB2 BSGP NEUTRAL LINK B2 200A


R1065582 BNEUTRALB4 BSGP NEUTRAL LINK B4 400A
T1065584 BNEUTRALC3 BSGP NEUTRAL LINK C3 800A
S1065583 BNEUTRALC1 BSGP NEUTRAL LINK C1 400A
29 Mersen • BS88 LV Fuse Links & Fuse Holders
BS88 FUSE HOLDERS & NEUTR AL LINK

Technical characteristics
SPECIFICATIONS F1 F2 A1 A2 A3 A4

3 kinds of electrical connections in Black White & Green

Front connected BFF32F1 BFF63F2 BFF32A1 BFF32A2 BFF63A3 BFF125A4

Back connected BBB32F1 BBB63F2 BBB32A1 BBB32A2 BBB63A3 BBB125A4

Front Back connected BFB32F1 BFB63F2 BFB32A1 BFB32A2 BFB63A3 BFB125A4

Cable cross-section for font connection

Min: 1 or 2 cables 1 mm2 1 mm2 1 mm2 1 mm2 1 mm2 1 mm2

Max: 1 cable 16 mm2 25 mm2 16 mm2 16 mm2 50 mm2 70 mm2

Max: 2 cables 10 mm2 16 mm2 10 mm2 10 mm2 25 mm2 35 mm2

Type of wire to be used: Copper multi strand or single strand


Note: Multistrand cable with maximum 17 strands.
For more than 17 strands a circular sleeve at the end of the cable is compulsary
Lug diameter of the cable for Back & Busbar
M6 M8 M6 M6 M8 M8
connection terminal diameter (refer Note)

DIN Rail Mounting 35 mm DIN Rail

Whether the plastic material complies with RoHS Thermoplastic Polyamid, RoHS compliant & Fire Retardant

Diameter of the screw to be used for panel mounting


M5 screw (Pan head/Cheese head)
Deep base = 4mm

Max torque for the mounting screw on the panel 3.5 Nm 4 Nm 3.5 Nm 4 Nm 3.5 Nm 4 Nm

Max torque for the grub screw (back & bus bar
3.5 Nm 4 Nm 3.5 Nm 3.5 Nm 3.5 Nm 4 Nm
connections)

Certifcation ASTA

550 V AC 550 V AC 690 V AC 690 V AC 690 V AC


Rated Voltage 550 V AC
250 V DC 250 V DC 460 V DC 460 V DC 460 V DC

Rated Current 32 A 63 A 32 A 32 A 63 A 125 A

Rated peak withstand current @ rated voltage 80 kA

Tool specification for tightening Electric Screw driver /


3.5 Nm 4 Nm 3.5 Nm 4 Nm 4 Nm 4 Nm
Manual crew driver - Max Torque setting

Screwdriver bit Diameter 6 x 100mm

with working edge thickness of 1mm and width


0.8 x 4.8 mm 1 x 6 mm 0.8 x 4.8 mm 1 x 6 mm 1 x 6 mm 1 x 6 mm
of 7mm

U imp according to IEC 60269-1 8 kA

30 Mersen • BS88 LV Fuse Links & Fuse Holders


BS88 FUSE HOLDERS & NEUTR AL LINK

Dimensions for F type

Front Front Connection (BFF) Back Back Connection (BBB) Front Back (Busbar) Connection (BFB)
A B
A B
A B

C
E

D
E

C
D
C
D

G
H

F
I J
K

FUSE HOLDER TYPE A B C D E F G H I J K

BFF32F1 75.5 26.5 54 41.5 7.8 - - - - - -


BBB32F1 75.5 26.5 54 41.5 - 40 17 9.7 58 5.6 -
BFB32F1 75.5 26.5 54 41.5 7.8 40 17 9.7 - - 2.7
BFF63F2 89 28.5 64 48.6 9 - - - - - -
BBB63F2 89 28.5 64 48.6 - 39 18.3 12 67 7 -
BFB63F2 89 28.5 64 48.6 9 39 18.3 12 - - 3.3

Panel Drilling Dimensions


3.3
2

2.5 5.5
58

67

13
13

2
3.3

For F1 For F2

31 Mersen • BS88 LV Fuse Links & Fuse Holders


BS88 FUSE HOLDERS & NEUTR AL LINK

Dimensions for A type

Front Front Connection (BFF) Back Back Connection (BBB) Front Back (Busbar) Connection (BFB)
A B E
A B

E
B

C
A D

C
G
H

F
D H

G
F
C

FUSE HOLDER TYPE A B C D E F G H I

BFF32A1 77.2 27.5 57 9 97.2 - - - -


BBB32A1 77.2 27.5 57 - - 28.6 122 11.9 58
BFB32A1 77.2 27.5 57 9 87.2 28.6 122 11.9 -
BFF32A2 99.8 33 56 9 119.8 - - - -
BBB32A2 99.8 33 56 - - 28.6 122 11.9 76.1
BFB32A2 99.8 33 56 9 109.8 28.6 122 11.9 -
BFF63A3 105.8 38 74.5 17.5 132.8 - - - -
BBB63A3 105.8 38 74.5 - - 28.6 161 11.9 80
BFB63A3 105.8 38 74.5 17.5 119.3 28.6 161 11.9 -
BFF125A4 134 48.9 97.8 17.5 165.7 - - - -
BBB125A4 134 48.9 97.8 - - 28.6 184.4 11.9 94.1
BFB125A4 134 48.9 97.8 17.5 149.9 28.6 184.4 11.9 -

Panel Drilling Dimensions

13 13 13 13

6.5
5.5 12.8
5.5
5.7

12.8
5.5
25
58

6.4
76.1

80

94.1
6.4

0.8

13 13 22.5
13
13

For A1
for A1 For
for A2 For
for A3 For
for A4
A4

32 Mersen • BS88 LV Fuse Links & Fuse Holders


BS88 FUSE HOLDERS & NEUTR AL LINK

For Offset Blade - Phenolic Type


83.00

43.7
32.9

59.6
82.1
38.4

47.6 24.6
66.7
14.3

43.7

43.7

66.7
24.6

NOMINAL CURRENT REFERENCE CATALOGUE STANDARD


TYPE VOLTAGE RATING (V) COLOR CONNECTION MERSEN FUSE TYPE
(A) NUMBER NUMBER PACK

INDIAN MARKET ONLY

F1 550 32 Black Front-Front T1036995F BNSH32F1 6


BNS55Vxx
F1 550 32 Black Back-Back W1036297F BNSP32F1 6

TYPE VOLTAGE RATING (V)

Front connected BFF32F1


Back connected BBB32F1
Cable cross-section for font connection
Min: 1 or 2 cables 1 mm2
Max: 1 cable 16 mm2
Max: 2 cables 10 mm2

Type of wire to be used: Copper multi strand or single strand


Note: Multistrand cable with maximum 17 strands. For more than 17 strands a circular sleeve at the end of the cable is compulsary

Lug diameter of the cable for Back & Busbar connection terminal diameter (refer Note) M6
Diameter of the screw to be used for panel mounting
M5 screw (Pan head/Cheese head)
Deep base = 4mm
Max torque for the mounting screw on the panel 3.5 Nm
Max torque for the grub screw (back & bus bar connections) 3.5 Nm
Rated Voltage 550 V AC
Rated Current 32 A
Rated peak withstand current @ rated voltage 80 kA
Tool specification for tightening
3.5 Nm
Electric Screw driver / Manual crew driver - Max Torque setting
Screwdriver bit Diameter 6 x 100mm
with working edge thickness of 1mm and width of 7mm 0.8 x 4.8 mm
U imp according to IEC 60269-1 8 kV

33 Mersen • BS88 LV Fuse Links & Fuse Holders


MERSEN PROFILE & R ANGE MAPPING

Range Mapping

CATALOGUE BREAKING CAPACITY


VOLTAGE AC AMPS STANDARDS
NUMBER KA

BLD 24 V …. 240 V 6,10,16,20,25 16.5 "IEC 60269 Pt 1 & 2, BS 88 Pt 1 & 2"


BLD 24 V …. 240 V 30 16.5 BSHD 60269-3 (BS1361)
BMD 42 V …. 415 V 2,4,6,8,10,20,25,32 80.0 "IEC 60269 Pt 1 & 2 BS 88 Pt 1 & 2"
BLST 24 V …. 240 V 2,4,6,10,16,20,25,32 33.0 "IEC 60269 Pt 1 & 2 BS 88 Pt 1 & 2"

BLD 24 V 10 BMD 42 V 10 BLST 24 V 10

VOLTAGE AMP RATING FUSE FA- VOLTAGE AMP RATING VOLTAGE AMP RATING
FUSE FAMILY FUSE FAMILY
240 V 10 A MILY 415 V 10 A 240 V 10 A

Comparison Chart for BLD/BMD/BLST Fuse Links



COMPETITORS MERSEN RATINGS

LD 6-25,240 V C 3030-240 V BLD24 V… 6,10,16,20,25


LD 30 C 3030-240 V BLD24 V … 30
LST 2-32,240 V STD 2-32,240 V BLST24 V… 2,4,6,10,16,20,25,32
MD 2-32,415 V SMD 2-32,415 V BMD42 V… 2,4,6,8,10,16,20,25,32

34 Mersen • BS88 LV Fuse Links & Fuse Holders


N OT E S

35 Mersen • BS88 LV Fuse Links & Fuse Holders


CYLIN DRIC AL
FUS ES FO R STR EE T
LIG HTIN G PROTEC TIO N

36 Mersen • BS88 LV Fuse Links & Fuse Holders


B L D/ B M D/ B L S T F U S E L I N K S

Simplicity and high reliability


The majority of existing street lighting networks are normally protected by a common Feeder
Protection Device (FPD). FPD is based on a simple overcurrent unidirectional technique to
protect against faults on the street lighting cables. The Mersen fuse technology ensures safety
in street lighting applications by providing better coordination, immediate isolation and ensures
fire safety through safe and correct fuse selection.

All the circuit protection solutions shown in this catalogue are ASTA 20 certified* and comply
with the RoHS European Directive. Mersen BS88 fuses are UKCA and CE approved.

For your own safety do NOT open BS88 fuse holders onload.

* Note that any items marked with * are not ASTA 20 certified.

Cylindrical Type BLD Fuse Links..........................................................................................................................................................................38

BLD time current / cut-off curve .........................................................................................................................................................................39

BS Cylindrical Type BMD Fuse Links................................................................................................................................................................ 40

BMD time current / cut-off curve .........................................................................................................................................................................41

Offset Bolted Tag BLST Fuse Links...................................................................................................................................................................42

BLST time current / cut-off curve .......................................................................................................................................................................43

37 Mersen • BS88 LV Fuse Links & Fuse Holders Mersen • BS88 LV Fuse Links & Fuse Holders 37
CYLINDRICAL T YPE BLD FUSE LINKS
R E F E R E N C E DATA : B L D

Reference data: BLD


Rated Voltage: 240 V ac Breaking Capacity: 16.5 kA
Reference Data: BLD
Full Range Protection, gG
Cylindrical Type BLD Fuse Links
Rated Voltage: 240 V ac Breaking Capacity: 16.5 kA
Full Range Protection, gG
RATINGS (AMPS)
PART
PART DESCRIPTIONS VOLTAGE (VOLTS) STANDARD PACKING
REFERENCE RATINGS (AMPS) BSHD 602693
IEC 60269-PT 1&2
(BS 1361)
PART PART VOLTAGE STANDARD
REFERENCE DESCRIPTIONS (VOLTS) BSHD
M1065693 BLD24 V6 IEC 60269-Pt 1&2 602693 6 PACKING -- 10
(BS 1361)
N1065694 BLD24 V10 10 -- 10
M1065693 BLD24 V6 6 -- 10
P1065695 BLD24 V16 16 -- 10
N1065694 BLD24 V10 10 240V -- 10
Q1065696 BLD24 V20 20 -- 10
P1065695 BLD24 V16 16 -- 10
R1065697 240V
BLD24 V25 25 -- 10
Q1065696 BLD24 V20 20 -- 10
T1065699 BLD24 V30 -- 30 10
R1065697 BLD24 V25 25 -- 10
T1065699 BLD24 V30 -- 30 10

Dimensions
Dimensions
29 ±0,4 ,1
±0
,7
12
Ø

8 ±0,5

Cylindrical Type BLD Fuse Links


Cylindrical Type BLD Fuse Links
DIMENSIONS IN MM
FUSE CURRENT RATINGS DIMENSIONS IN MM
TYPE AMPS A B C
FUSE CURRENT RATINGS
TYPE AMPS MAX A
MAX MAX
B C
BLD 6,10,16,20,25,32 29.4 MAX
12.8 8.5 MAX MAX

BLD 6,10,16,20,25,32 29.4 12.8 8.5

Electrical Characteristics:
Electrical Characteristics
PRE - ARCING I t CLEARING I t 2 2
FUSE VOLTAGE CURRENT RATINGS
(AMPERE 2 (AMPERE 2 WATT LOSS
TYPE AC AMPS
SECONDS) SECONDS) 2
PRE - ARCING I T CLEARING I 2 T
FUSE TYPE VOLTAGE AC CURRENT RATINGS AMPS WATT LOSS
6 13 (AMPERE
20
2
SECONDS) 1.98 (AMPERE 2 SECONDS)

10 6 25 13 63 1.53 20 1.98
16 10 204 25 510 1.54 63 1.53
BLD 240 V
20 16 459 204 1148 1.54 510 1.54
BLD 240 V
25 20 625 459 1563 2.14 1148 1.54
30 25 816 625 2041 2.85 1563 2.14
30 816 2041 2.85

38 Mersen • BS88 LV Fuse Links & Fuse Holders


BBLLDD TTI IMMEE CCUURRRREENNTT // CCUUT-
T-OOFFFF CCUURV
RVEE
B L D T I M E C U R R E N T / C U T- O F F C U RV E

BLD
BLDTIME CURRENT
time CURVES
current curves
BLD TIME CURRENT CURVES
10,000
6
10,000
4 16A
6
20A
2
4 16A
25A
20A
2
1000 30A
25A
6
1000 30A
4
6
4
2

2
100
6
100
4
6
TIME(SECONDS)

2
4
TIME(SECONDS)

2
10
6
10
4
6
4
2

2
1
6
1
4
6
2
4

2
0.1
6 10A
0.1
4 6A
6 10A
4
2 6A

2
0.01
2 4 6 8 10 2 4 6 8 100 2 4 6 8 1000 2
0.01 CURRENT(AMPERES)
2 4 6 8 10 2 4 6 8 100 2 4 6 8 1000 2
CURRENT(AMPERES)

BLD CUT-OFF CURVE


BLD
BLD cut-off
CUT-OFF curve
CURVE

8
6
8
4
6
4
2

1002
8
1006
8
4
6
(kA PEAK)

4
2
(kA PEAK)

102
8
CURRENT

106
8
4
CURRENT

6
4
2 30A
CUT-OFF

25A
12 20A
30A
CUT-OFF

8 25A
16 16A
20A
8
4 10A
6 16A
6A
4 10A
2
6A

2
0.1
8
6
0.1
8
4
6
4
2

2
0.01
0.01 2 4 6 8 0.1 2 4 6 8 1 2 4 6 8 10 2 4 6 8 100
0.01 17.5
0.01 2 4 6 8 0.1 2 4 6 8 1 2 4 6 8 10 2 4 6 8 100
PROSPECTIVE CURRENT (SYM. R.M.S. kA)
17.5

PROSPECTIVE CURRENT (SYM. R.M.S. kA)

39 Mersen • BS88 LV Fuse Links & Fuse Holders Mersen • Electrical Safety of Street Light 5

Mersen • Electrical Safety of Street Light 5


BS CYLINDRICAL T YPE BMD FUSE LINKS

R E F E R E N C E DATA : B M D

Reference data: BMD


Rated Voltage: 415 V AC, Breaking Capacity: 80 kA
Reference
Full Data:
Range BMD
Protection, gG
BS Cylindrical Type BMD Fuse Links
Rated Voltage: 415 V AC, Breaking Capacity: 80 kA
Full Range Protection, gG
PART
PART DESCRIPTIONS VOLTAGE (VOLTS) RATINGS (AMPS) STANDARD PACKING
REFERENCE

PART V1036973
PART BMD42 V2
VOLTAGE RATINGS STANDARD 2 10
REFERENCE DESCRIPTIONS (VOLTS) (AMPS) PACKING
W1036974 BMD42 V4 4 10
V1036973 BMD42 V2 2 10
X1036975 BMD42 V6 6 10
W1036974 BMD42 V4 4 10
P1065074 BMD42 V8 8 10
X1036975 BMD42 V6 6 10
Y1036976 BMD42 V10 415 V 10 10
P1065074 BMD42 V8 8 10
Z1036977 BMD42 V16 16 10
Y1036976 BMD42 V10 415 V 10 10
Z1036977 A1036978
BMD42 V16 BMD42 V20 16 10 20 10

A1036978 B1036979
BMD42 V20 BMD42 V25 20 10 25 10

B1036979 C1036980
BMD42 V25 BMD42 V32 25 10 32 10
C1036980 BMD42 V32 32 10

Dimensions
Dimensions
8 ±0,5 ,1
±0
,7
12
Ø

29 ±0,4

Cylindrical Type
Cylindrical Type BLD
BLD Fuse Fuse Links
Links

DIMENSIONS IN MM
FUSE CURRENT RATINGS DIMENSIONS IN MM
TYPE
FUSE AMPS A
CURRENT RATINGS B C
TYPE AMPS MAX MAX
A MAX B C
MAX MAX MAX
BMD 2,4,6,8,10,16,20,25,30,32 29.4 12.8 8.5
BMD 2,4,6,8,10,16,20,25,30,32 29.4 12.8 8.5

Electrical Characteristics:
Electrical Characteristics
PRE - ARCING I 2 t CLEARING I 2 t
FUSE VOLTAGE CURRENT RATINGS
(AMPERE 2 (AMPERE 2 WATT LOSS
TYPE AC AMPS
SECONDS) PRE SECONDS)
- ARCING I 2 T CLEARING I 2 T (AMPERE 2
FUSE TYPE VOLTAGE AC CURRENT RATINGS AMPS WATT LOSS
(AMPERE 2 SECONDS) SECONDS)
2 1 3.5 1.17
4 2 8 1 27 1.48 3.5 1.17

6 4 22 8 77 1.54 27 1.48

8 6 13 22 55 1.01 77 1.54

BMD 415 V 10 8 27 13 113 1.42 55 1.01


BMD 415 V16 10 107 27 451 1.43 113 1.42
20 16 241 107 1015 1.52 451 1.43
25 20 428 241 1805 2.28 1015 1.52
32 25 668 428 2821 2.64 1805 2.28
32 668 2821 2.64

40 Mersen • BS88 LV Fuse Links & Fuse Holders


BBMMDD TTI IMMEE CCUURRRREENNTT // CCUUT-
T-OOFFFF CCUURV
RVEE
B M D T I M E C U R R E N T / C U T- O F F C U RV E

BMD TIME CURRENT CURVES


BMD time current curves
BMD TIME CURRENT CURVES
10,000
6
10,000
4 16A
6 20A
2
4 16A
25A
1000
2 20A
32A
6 25A
1000
4 32A
6
2
4
100
2
6
100
4
TIME(SECONDS)

6
2
4
TIME(SECONDS)

10
2
6
10
4
6
2
4
1
2
6
41
6
2
4
0.1
2
6 10A
0.1
4 8A
6A
6 10A
2 4A
4 8A
2A
6A
0.01
2 4A
2 4 6 8 10 2 4 6 8 100 2 4 6 8 1000 2
2A
0.01 CURRENT(AMPERES)
2 4 6 8 10 2 4 6 8 100 2 4 6 8 1000 2

CURRENT(AMPERES)

BMD CUT- OFF CURVE


BMD
BMD cut-off
CUT- curve
OFF CURVE

8
6
4
8
6
2
4

1002
8
6
100
4
8
6
(kA PEAK)

2
4
(kA PEAK)

102
8
CURRENT

6
10
4
8
CURRENT

6 32A
2 25A
4 20A
CUT-OFF

16A
32A
21 25A
10A
8 20A
8A
CUT-OFF

6 16A
6A
1 4A
10A
4
8 8A
6 2A
6A
2 4A
4
2A
0.1
2
8
6
0.1
4
8
6
2
4

0.01
2
0.01 2 4 6 8 0.1 2 4 6 8 1 2 4 6 8 10 2 6 8 100

0.01
0.01 2 4 8 0.1
6 PROSPECTIVE
2 4 6 8 1(SYM.
CURRENT 2 R.M.S. 6 8 10
4 kA) 2 6 8 100

PROSPECTIVE CURRENT (SYM. R.M.S. kA)

Mersen • Electrical Safety of Street Light 7


41 Mersen • BS88 LV Fuse Links & Fuse Holders
Mersen • Electrical Safety of Street Light 7
O F F S E T B O LT E D TAG B L S T F U S E L I N K S

R E F E R E N C E DATA : B L S T
Reference data: BLST
Rated Voltage: 240V AC Breaking Capacity: 33 kA
Full Range Protection - gG
eference Data: BLST
Offset Bolted Tag BLST Fuse Links
ated Voltage: 240V AC Breaking Capacity: 33 kA
ull Range Protection PART
- gG PART DESCRIPTIONS VOLTAGE (VOLTS) RATINGS (AMPS) STANDARD PACKING
REFERENCE

D1065685 BLST24 V2 2 10
PART PART E1065686 VOLTAGE
BLST24 V4 RATINGS STANDARD 4 10
REFERENCE DESCRIPTIONS (VOLTS) (AMPS) PACKING
F1065687 BLST24 V6 6 10
D1065685 BLST24 V2 2 10
E1065686 BLST24 G1065688
V4 BLST24 V104 10V
240
10 10

F1065687 BLST24 H1065689


V6 BLST24 V166 10 16 10

G1065688 J1065690
BLST24 V10 BLST24 V2010 10 20 10
240 V
H1065689 BLST24 K1065691
V16 BLST24 V2516 10 25 10
J1065690 BLST24 L1065692
V20 BLST24 V3220 10 32 10
K1065691 BLST24 V25 25 10
L1065692 BLST24 V32 32 10

Dimensions
Dimensions
47 ±0,4
,1
4,5 ±0,3

38 ±0,4 0,8 ±0,03 ±0


,7
12
Ø
9,4 ±0,25

4,5 ±0,3 24 ±0,4 14,6 ±0,4

Off Set Bolted Tag Type BLST Fuse Links


Cylindrical Type BLD Fuse Links
DIMENSIONS IN MM
FUSE CURRENT RATINGS
TYPE AMPS A B DIMENSIONS
D E IN MMF G K
FUSE CURRENTMAX
RATINGSMAX MAX MAX MAX MAX MAX
TYPE AMPS A B D E F G H
BLST 2,4,6,10, 16,20,25,32 24.4 12.8 47.4
MAX 9.65MAX 0.83 38.4
MAX 15 MAX MAX MAX MAX

BLST 2,4,6,10, 16,20,25,32 24.4 12.8 47.4 9.65 0.83 38.4 15

Electrical Characteristics:
Electrical
FUSE VOLTAGE
Characteristics
CURRENT RATINGS PRE - ARCING I t CLEARING I t 2 2
WATT LOSS
TYPE AC AMPS (AMPERE 2 SECONDS) (AMPERE 2 SECONDS)

PRE - ARCING I 2 T CLEARING I 2 T (AMPERE 2


FUSE TYPE VOLTAGE
2 AC CURRENT
0.6 RATINGS AMPS 1 1.02 SECONDS) WATT LOSS
(AMPERE 2
SECONDS)

4 2 5 7
0.6 1.29 1 1.02
6 4 10 516 1.33 7 1.29
10 29 67 1.40
BLST 240 V 6 10 16 1.33
16 152 348 1.79
10 29 67 1.40
20 533 1225 1.04
BLST 240 V 16 152 348 1.79
25 725 1668 1.80
20 533 1225 1.04
32 947 2178 2.64
25 725 1668 1.80
32 947 2178 2.64
32 668 2821 2.64

42 Mersen • BS88 LV Fuse Links & Fuse Holders


BBLLSSTT TTI IMMEE CCUURRRREENNTT // CCUUT-
T-OOFFFF CCUURV
RVEE
B L S T T I M E C U R R E N T / C U T- O F F C U RV E

BLST TIME CURRENT CURVES


BLST time current curves
BLST TIME CURRENT CURVES
10,000
6
4
10,000 16A
6
2 20A
4 25A
16A
1000 32A
20A
2
6 25A
4
1000 32A
6
2
4
100
2
6
4
100
6
2
TIME(SECONDS)

4
10
2
6
TIME(SECONDS)

4
10
6
2
4
1
2
6
4
1
6
2
4
0.1
2
6 10A
4
0.1 6A

6 4A
10A
2 2A
4 6A
0.01 4A
22 42A 6 8 10 2 4 6 8 100 2 4 6 8 1000 2
0.01 CURRENT(AMPERES)
2 4 6 8 10 2 4 6 8 100 2 4 6 8 1000 2
CURRENT(AMPERES)

BLST CUT- OFF CURVE


BLST
BLST cut-off
CUT- curve
OFF CURVE

8
6
4
8
6
2
4

100
2
8
6
1004
8
(kA PEAK)

6
2
4
(kA PEAK)

10
2
8
CURRENT

6
104
8
CURRENT

6
2 32A
4
CUT-OFF

25A
1 20A
2 32A
8
CUT-OFF

6 25A
16A
10A
41 20A
8 6A
6 4A
16A
2 10A
2A
4
6A
4A
0.1
2
8 2A
6
0.1
4
8
6
2
4

0.01
2 0.01 2 4 6 8 0.1 2 4 6 8 1 2 4 6 8 10 2 6 8 100
33.5
0.01
0.01 2 4 6 PROSPECTIVE
8 0.1 2 CURRENT
4 6 8 1 (SYM.
2 R.M.S.
4 6kA)
8 10 2 6 8 100
33.5

PROSPECTIVE CURRENT (SYM. R.M.S. kA)

Mersen • Electrical Safety of Street Light 9


43 Mersen • BS88 LV Fuse Links & Fuse Holders
Mersen • Electrical Safety of Street Light 9
LOW VO LTAG E
DISTRIB UTIO N WI RI N G
SYSTEMS

44 Mersen • BS88 LV Fuse Links & Fuse Holders


FEEDER PILL AR FUSE LINKS

Ensuring continuous service


The Mersen range of Low Voltage Feeder Pillar Fuse Links are designed for the use with wedge
type fuse carriers with fixing centres of 82mm and 92mm. These are primarily for use by
Electricity Supply Industries in distribution pillars, open type substation boards, heavy duty
service cut-outs and underground disconnecting boxes.

The Mersen range of House Service Fuse Links are designed for the use in consumer
distribution boards, electricity control units, houses and office buildings.

All the circuit protection solutions shown in this catalogue are ASTA 20 certified* and comply
with the RoHS European Directive. Mersen BS88 fuses are UKCA and CE approved.

For your own safety do NOT open BS88 fuse holders onload.

* Note that any items marked with * are not ASTA 20 certified.

Feeder Pillar Fuse Links 415VAC 80kA............................................................................................................................................................46

Feeder Pillar Fuse Links 415VAC 80kA time current / cut-off curve ................................................................................................ 48

Feeder Pillar Fuse Links 415VAC 33kA............................................................................................................................................................ 49

Feeder Pillar Fuse Links 415VAC 33kA time current / cut-off curve ................................................................................................. 51

Comparison chart......................................................................................................................................................................................................... 55

Application information........................................................................................................................................................................................... 53

Approvals.......................................................................................................................................................................................................................... 55

45 Mersen • BS88 LV Fuse Links & Fuse Holders


F E E D E R P I L L A R F U S E L I N K S 41 5 VAC 8 0 K A

Reference data
Rated Voltage: 415V AC
Breaking Capacity: 80kA
ASTA 20 Certified

CATALOG FS STANDARD BS STANDARD IEC STANDARD FIXING CENTRE


VOLTAGE (V) RATING (A) PACK.
NUMBER REFERENCE REFERENCE REFERENCE (MM)

20 BJU42V020PA H1003888F BS88-5 IEC60269-2 82 6


25 BJU42V025PA J1003889F BS88-5 IEC60269-2 82 6
32 BJU42V032PA K1003890F BS88-5 IEC60269-2 82 6
40 BJU42V040PA L1003891F BS88-5 IEC60269-2 82 6
50 BJU42V050PA M1003892F BS88-5 IEC60269-2 82 6
415 63 BJU42V063PA N1003893F BS88-5 IEC60269-2 82 6
80 BJU42V080PA P1003894F BS88-5 IEC60269-2 82 6
100 BJU42V100PA Q1003895F BS88-5 IEC60269-2 82 6
125 BJU42V125PA R1003896F BS88-5 IEC60269-2 82 6
160 BJU42V160PA S1003897F BS88-5 IEC60269-2 82 6
200 BJU42V200PA T1003898F BS88-5 IEC60269-2 82 6
20 BJU42V020SA V1003899C BS88-5 IEC60269-2 92 3
25 BJU42V025SA W1003900C BS88-5 IEC60269-2 92 3
32 BJU42V032SA X1003901C BS88-5 IEC60269-2 92 3
40 BJU42V040SA Y1003902C BS88-5 IEC60269-2 92 3
50 BJU42V050SA Z1003903C BS88-5 IEC60269-2 92 3
415 63 BJU42V063SA A1003904C BS88-5 IEC60269-2 92 3
80 BJU42V080SA B1003905C BS88-5 IEC60269-2 92 3
100 BJU42V100SA C1003906C BS88-5 IEC60269-2 92 3
125 BJU42V125SA D1003907C BS88-5 IEC60269-2 92 3
160 BJU42V160SA H1003911C BS88-5 IEC60269-2 92 3
200 BJU42V200SA V1003922C BS88-5 IEC60269-2 92 3
250 BJU42V250PB W1003923C BS88-5 IEC60269-2 82 3
315 BJU42V315PB Y1003925C BS88-5 IEC60269-2 82 3
415
355 BJU42V355PB Z1003926C BS88-5 IEC60269-2 82 3
400 BJU42V400PB D1003930C BS88-5 IEC60269-2 82 3
250 BJU42V250SB E1003931C BS88-5 IEC60269-2 92 3
315 BJU42V315SB F1003932C BS88-5 IEC60269-2 92 3
415
355 BJU42V355SB G1003933C BS88-5 IEC60269-2 92 3
400 BJU42V400SB H1003934C BS88-5 IEC60269-2 92 3
450 BJU42V450SC J1003935A BS88-5 IEC60269-2 92 1
415
500 BJU42V500SC F1003955A BS88-5 IEC60269-2 92 1
560 BJU42V560SD G1003956A BS88-5 IEC60269-2 92 1
415
630 BJU42V630SD H1003957A BS88-5 IEC60269-2 92 1

46 Mersen • BS88 LV Fuse Links & Fuse Holders


F E E D E R P I L L A R F U S E L I N K S 41 5 VAC 8 0 K A

Feeder Pillar
FeederFuse Links
Pillar Fuse Links
DIMENSIONS
Dimensions
Dimensions

Feeder Pillar Fuse Links


Feeder Pillar Fuse Links
Fig. 1 Fig. 2

Fig. 4
Fig. 3

Fig. 5 Fig. 6

Fig. No. Catalog Ref

ELECTRICALcharacteristics
Electrical CHARACTERISTICS 1
2
BJU42V020PA - BJU42V200PA
BJU42V020SA - BJU42V200SA
3 BJU42V250PB
Fig.
- BJU42V400PB
Catalog
Rating I2t (Ampere2 seconds) Watts 4
Fuse Type Curve I 2T (AMPERE 2 SECONDS) BJU42V250SB
No. FIG. - BJU42V400SB
Reference
CATALOG
(A)
RATING Loss LOSS NO. REFERENCE
FUSE TYPE
(A)
CURVE Pre Arcing Total WATTS
5 BJU42V450SC - BJU42V500SC
PRE ARCING TOTAL
1 BJU42V020PA - BJU42V200PA
Electrical characteristics
BJU42V020PA/SA
BJU42V020PA/SA
20 gU 100 1125 2.4 6 BJU42V560SD
2
BJU42V020PA - BJU42V200PA
- BJU42V630SD
1 BJU42V020SA - BJU42V200SA
BJU42V025PA/SA 20 25
gU 100 gU 250 1125
1890 2.4 2.7
3 BJU42V250PB - BJU42V400PB
Fuse Rating 2 BJU42V020SA - BJU42V200SA
gU gU Curve 250670 I t (Ampere seconds)
2.7 3.2 Watts
2 2
BJU42V025PA/SA
BJU42V032PA/SA 25 32 1890
3000 4 BJU42V250SB - BJU42V400SB
Type (A) Pre Arcing Total Loss
BJU42V040PA/SA 32 40 3 BJU42V250PB - BJU42V400PB
BJU42V032PA/SA gU gU 1300
670 5850
3000 3.2 4.5 5 BJU42V450SC - BJU42V500SC
BJU42V020PA/SA 20 gU 100 1125 2.4
BJU42V050PA/SA 50 gU 2600 11700 4.8 6
4BJU42V560SD - BJU42V630SD
BJU42V250SB - BJU42V400SB
BJU42V040PA/SA 40
BJU42V025PA/SA 25 gU gU 1300 250 5850 1890 4.5 2.7
BJU42V063PA/SA 63 gU 4000 18000
BJU42V032PA/SA
BJU42V050PA/SA 50 32 gU gU 2600 670 11700 3000 4.8 6.2 3.2 5 BJU42V450SC - BJU42V500SC
BJU42V080PA/SA
BJU42V040PA/SA80 40 gU gU 4150
1300 21000 5850 8.4 4.5 6 BJU42V560SD - BJU42V630SD
BJU42V063PA/SA
BJU42V100PA/SA
63 100 gU gU 4000
8240
18000
37000
6.2 8.7
BJU42V050PA/SA 50 gU 2600 11700 4.8
BJU42V080PA/SA
BJU42V125PA/SA 80 125
BJU42V063PA/SA 63 gU gU gU 4150 4000
16600 21000
74700 18000 8.4 9.3 6.2
BJU42V080PA/SA
BJU42V100PA/SA 100160
BJU42V160PA/SA 80 gU gU gU 4150
37500
8240 168000
37000 21000 8.7 10.7 8.4
BJU42V100PA/SA
BJU42V200PA/SA 100 gU 8240 37000 8.7
BJU42V125PA/SA 125 200 gU gU 57000
16600 256500
74700 9.3 16.2
BJU42V125PA/SA
BJU42V250PB/SB 250 125 gU gU 16600
60000 270000 74700 20 9.3
BJU42V160PA/SA 160
BJU42V160PA/SA 160 gU gU 3750037500 168000 16800010.7 10.7
BJU42V315PB/SB 315 gU 105000 472500 27
BJU42V200PA/SA
BJU42V200PA/SA 200 200 gU gU 5700057000 256500 25650016.2 16.2
BJU42V355PB/SB 355 gU 134000 603300 29
BJU42V250PB/SB 250 gU 60000 270000 20
BJU42V250PB/SB
BJU42V400PB/SB 250400 gU gU 60000
160000 270000
720000 20 32
BJU42V315PB/SB 315 gU 105000 472500 27
BJU42V315PB/SB
BJU42V450SC 315 450
BJU42V355PB/SB 355 gU gU gU 105000
210000
134000 472500
945000 60330027 36 29
BJU42V500SC
BJU42V355PB/SB 355500
BJU42V400PB/SB 400 gU gU gU 302000
134000
160000 1359000 72000029 37
603300 32
BJU42V560SD
BJU42V450SC 560 450 gU gU 485000
210000 2910000 945000 35 36
BJU42V400PB/SB 400 gU 160000 720000 32
BJU42V500SC 630
BJU42V630SD 500 gU gU 302000
634000 38000001359000 39 37
BJU42V450SC 450 gU 210000 945000 36
BJU42V560SD 560 gU 485000 2910000 35
BJU42V500SC 5500
BJU42V630SD 630 gU gU 302000
634000 1359000 380000037 39
5
BJU42V560SD 560 gU 485000 2910000 35
BJU42V630SD 630 gU 634000 3800000 39

47 Mersen • BS88 LV Fuse Links & Fuse Holders


F E E D E R P I L L A R F U S E L I N K S 41 5 VAC 8 0 K A
T I M E C U R R E N T / C U T- O F F C U RV E
rves
es Set for
rves Set
Set for
Feeder
for Feeder
Pillar Fuse Links
Feeder Pillar
Pillar Fuse
Fuse Links
Links
SetCurves Set for House Service Cut-out
es Set for Feeder Pillar Fuse Links
rves
E VS.
es
urves
ime Set
CURRENT
Curves
for
vs. for
Feeder
Set
Currentfor SetFeeder
CHARACTERISTICS
Curves
Pillar
Curves for
Set
Fuse
Feeder SetLinks
for
characteristics Pillar
House
for House
Pillar
House Fuse
Service
Service
Fuse
Service Links
Cut-out
Cut-out Fuse Links
Links
Cut-out Fuse Links
ves
Time
ME
me
Time
Set
RVES
VS.-
vs.Curves
for
vs.
20 TO Feeder
Current
630A
CURRENT
Curves
Current
vs. - Current
- Set
Pillar
forSet House
Fuse Links
characteristics
415VAC
CHARACTERISTICS
Set
Curves forSet House
characteristics
Curves
Service
Service
for House Service
for House Service
characteristics
Cut-out
Cut-outCut-out
Cut-out
Fuse Links
Fuse Links
me vs.
U curves Current
Time characteristics
vs.630A
20 to current characteristics
- 415VAC

Curves
Curves
Curves
Curves
Time
URVES
gU
me vs.
- 20
curves
vs. TO- Current
630A
20
Current to -630Acharacteristics
415VAC- 415VAC
characteristics
me vs.gU
U curves Current
- curves characteristics
20 to-630A TO -630A
415VAC

Curves
Curves
20 - 415VAC

CurvesCurves
gU curves - 20 to 630A - 415VAC

Set
SetSet
SetSetSet
Set
forfor
forSet
forfor
for
forHouse
for
House
House
HouseHouse
House
House
House Service
Service
Service
Service
Service
Service
Service
ServiceCut-out
Cut-out
Cut-out
Cut-out
Cut-out
Cut-out Fuse
Fuse
Fuse
Fuse
Links
Links
Links
Links

ut
TCut off- -CURRENT
OFF Current characteristics
CHARACTERISTICS
Cut-out

offCut- Current characteristics


off - current characteristics
Cut-out

tTt off
Cut -
off
OFF Current
- Current characteristics
characteristics
Cutoff off- CURRENT
- - Current CHARACTERISTICS
Current characteristics
characteristics
t off - Current characteristics
ut off - Current characteristics

9
48 Mersen • BS88 LV Fuse Links & Fuse Holders
6 9
9
F E E D E R P I L L A R F U S E L I N K S 41 5 VAC 33 K A

Reference data
Rated Voltage: 415V ac
Breaking Capacity: 33kA
ASTA 20 Certified

REFERENCE DATA
CATALOG FS STANDARD BS STANDARD IEC STANDARD FIXING CENTRE
VOLTAGE (V) RATING (A) PACK.
NUMBER REFERENCE REFERENCE REFERENCE (MM)

5 BME42V05 C1003860J BS1361 IEC60269-3 22x57 10


Rated Voltage: 415V ac 10 Voltage BME42V10
Rating D1003861J
Catalog FSBS1361
Standard BSIEC60269-3
Standard IEC22x57
Standard Size 10
Standard Pack.
Breaking Capacity: 33kA 15 (V) (A)
BME42V15 Number
E1003862J Reference
BS1361 Reference
IEC60269-3 Reference
22x57 (mm)
10
5 BME42V05 C1003860J BS1361 IEC60269-3 22x57 10
ASTA 20 Certified 20 BME42V20 F1003863J BS1361 IEC60269-3 22x57 10
10 BME42V10 D1003861J BS1361 IEC60269-3 22x57 10
25 BME42V25 G1003864J BS1361 IEC60269-3 22x57 10
House Service Cut-out Fuse 15Links
House Service Cut-out Fuse Links
30
BME42V30
BME42V15
H1003865J
E1003862J
BS1361
BS1361
IEC60269-3
IEC60269-3
22x57
Curves
22x57
10
Set
10 for
415 20 BME42V20 F1003863J BS1361 IEC60269-3 22x57 10
Reference data 40 BME42V40 L1003868J BS1361 IEC60269-3 22x57 10
Links
Links

25 BME42V25 G1003864J BS1361 IEC60269-3 22x57 10


Rated Voltage: 415V ac 45 BME42V45 N1003870J BS1361 IEC60269-3 22x57 10
30 BME42V30 H1003865J BS1361 IEC60269-3 22x57 10
Breaking Capacity: 33 kA 50 415 BME42V50 Q1003872J BS1361 IEC60269-3 22x57 10
FuseFuse

40BS StandardBME42V40 L1003868J BS1361 IEC60269-3 22x57 10


Voltage Rating 60 Catalog BME42V60 R1003873J
IEC Standard BS1361
Size Std. IEC60269-3 22x57 10
(V) (A) Number Reference Reference (mm) Pack.
45 BME42V45 N1003870J BS1361 IEC60269-3 22x57 10
Service Cut-out

5 70 BME42V70BS1361 S1003874J
BME42V05 IEC60269-3 BS1361
22x57 10 IEC60269-3 22x57 10
10 BME42V10 50 BS1361 BME42V50
IEC60269-3 Q1003872J
22x57 10 BS1361 IEC60269-3 22x57 10
15
80 BME42V80
BME42V15 BS1361
T1003875J
IEC60269-3
BS1361
22x57 10
IEC60269-3 22x57 10
20 BME42V20 60 BME42V60 R1003873J BS1361 IEC60269-3 22x57 10
30 BMF42V30BS1361 V1003876F
IEC60269-3 22x57
BS1361 10 IEC60269-3 30x57 6
Cut-out

25 BME42V25
70 BS1361BME42V70
IEC60269-3 22x57 10
S1003874J BS1361 IEC60269-3 22x57 10
30 40 BMF42V40BS1361 W1003877F
BME42V30 IEC60269-3 BS1361 10
22x57 IEC60269-3 30x57 6
415

40 BME42V40 80 BS1361BME42V80
IEC60269-3 T1003875J
22x57 10 BS1361 IEC60269-3 22x57 10
45
50 BMF42V50BS1361 X1003878F
BME42V45 IEC60269-3
BS1361 10
22x57
IEC60269-3 30x57 6
415 50 60 BME42V50
BMF42V60BS1361 Y1003879F
IEC60269-3 22x57
BS1361 10 IEC60269-3 30x57 6
House ServiceHouse

60 BME42V60 30 BS1361BMF42V30
IEC60269-3 V1003876F
22x57 10 BS1361 IEC60269-3 30x57 6
70 70 BMF42V70BS1361 Z1003880F
BME42V70 IEC60269-3 BS1361 10
22x57 IEC60269-3 30x57 6
80 BME42V80
40 BS1361
BMF42V40
IEC60269-3
W1003877F
22x57 10
BS1361 IEC60269-3 30x57 6
80 BMF42V80 A1003881F BS1361 IEC60269-3 30x57 6
50 BMF42V50 X1003878F BS1361 IEC60269-3 30x57 6
30 100 BMF42V30 BS1361 B1003882F
BMF42V100 IEC60269-3 30x57
BS1361 6 IEC60269-3 30x57 6
40 415
BMF42V40 60 BS1361BMF42V60
IEC60269-3 Y1003879F
30x57 6 BS1361 IEC60269-3 30x57 6
50 BMF42V50 BS1361 IEC60269-3 30x57 6
70 BS1361BMF42V70 Z1003880F BS1361 IEC60269-3 30x57 6
415

60 BMF42V60 IEC60269-3 30x57 6


70 BMF42V70 80 BS1361BMF42V80
IEC60269-3 30x57 6
A1003881F BS1361 IEC60269-3 30x57 6
80 BMF42V80 BS1361 IEC60269-3 30x57 6
100 BMF42V100 100 BS1361BMF42V100
IEC60269-3 B1003882F
30x57 6 BS1361 IEC60269-3 30x57 6

DIMENSIONS
Dimensions
Dimensions

SIZE Size Fuse


FUSE CURRENT RATING Current Rating
DIMENSIONS (MM) Dimensions (mm)
Size Fuse Current Rating Dimensions (mm)
(mm)
(mm)
(MM)
Type
Type
TYPE (A) (A) A B C
(A) A C B C
A B
22x57 BME22x57 BME
5,10,15,20,25,30,40,45,50,60,70,80 5,10,15,20,25,30,40,45,50,60,70,80
57 16 22.23 57 16 22.23
30x57 22x57
BMF BME 5,10,15,20,25,30,40,45,50,60,70,80
30,40,50,60,70,80,100 57 16 30.16 57 16 22.23
30x57 BMF 30,40,50,60,70,80,100 57 16 30.16
30x57 BMF 30,40,50,60,70,80,100 57 16 30.16

EElectrical
LECTRICAL CHARACTERISTICS
characteristics
Fuse
Type
Rating
(A)
Size
(mm)
I2t (Ampere2 seconds)
Pre Arcing Total
Watts
Loss
BME42V05 5 22x57 12 Rating 100 Size 1.5 I2t (Ampere2 seconds) Watt
Fuse Type
BME42V10 10 22x57 25 (A) 185 (mm) 1.7 Pre Arcing Total Loss
BME42V15 15 22x57 120 540 1.9
BME42V20 20 BME42V05
22x57 250 5 1125 22x572.1 12 100 1.5
BME42V25 25 22x57 300 1890 2.3
BME42V30 30
BME42V10
22x57 400
10 4500
22x572.65 25 185 1.7
BME42V40 40 22x57
BME42V15 520 15 5850 22x574.4 120 540 1.9
BME42V45 45 22x57 1250 11700 4.6
BME42V50 50 BME42V20
22x57 1600 20 16000 22x574.75 250 1125 2.1
BME42V60 60 22x57 2100 19200 4.8
BME42V70 70
BME42V25
22x57 2600
25 26250
22x575.3 300 1890 2.3
BME42V80 80 22x57
BME42V30 4000 30 30000 22x575.6 400 4500 2.65
BMF42V30 30 30x57 400 4500 2.6
BMF42V40 40 BME42V40
30x57 520 40 5850 22x574.3 520 5850 4.4
BMF42V50 50 30x57 1600 16000 4.6
BMF42V60 60 BME42V45
30x57 2100 45 19200 22x574.7 1250 11700 4.6
BMF42V70 70 30x57
BME42V50 2600 50 26250 22x575.2 1600 16000 4.75
BMF42V80 80 30x57 4000 30000 5.5
BMF42V100 100 BME42V60
30x57 8500 60 68000 22x575.8 2100 19200 4.8
8 49 Mersen • BS88 LV Fuse Links & Fuse Holders
BME42V70 70 22x57 2600 26250 5.3
BME42V80 80 22x57 4000 30000 5.6
FEEDER PILL AR FUSE LINKS

Electrical characteristics

I 2T (AMPERE 2 SECONDS)
RATING SIZE
FUSE TYPE WATTS LOSS
(A) (MM)
PRE ARCING TOTAL

BME42V05 5 22x57 12 100 1.5


BME42V10 10 22x57 25 185 1.7
BME42V15 15 22x57 120 540 1.9
BME42V20 20 22x57 250 1125 2.1
BME42V25 25 22x57 300 1890 2.3
BME42V30 30 22x57 400 4500 2.65
BME42V40 40 22x57 520 5850 4.4
BME42V45 45 22x57 1250 11700 4.6
BME42V50 50 22x57 1600 16000 4.75
BME42V60 60 22x57 2100 19200 4.8
BME42V70 70 22x57 2600 26250 5.3
BME42V80 80 22x57 4000 30000 5.6
BMF42V30 30 30x57 400 4500 2.6
BMF42V40 40 30x57 520 5850 4.3
BMF42V50 50 30x57 1600 16000 4.6
BMF42V60 60 30x57 2100 19200 4.7
BMF42V70 70 30x57 2600 26250 5.2
BMF42V80 80 30x57 4000 30000 5.5
BMF42V100 100 30x57 8500 68000 5.8

50 Mersen • BS88 LV Fuse Links & Fuse Holders


F E E D E R P I L L A R F U S E L I N K S 41 5 VAC 33 K A
T I M E C U R R E N T / C U T- O F F C U RV E
Curves Set
Curves
Curves Set
Curves for
CurvesSet
for
CurvesSet
Set House
for
House
for
Setfor
Curves
for
Curves
House
House
Set for
House
Set
Service
HouseService
Service
forHouse
Service
House
Cut-out
Service
Cut-out
Service
Cut-out
Service Fuse Cut-out
Cut-out
Service Cut-out
FuseLinks
Cut-out
Cut-outFuse
FuseLinks
Links Links
vs.
Time
vs.Current
Time vs.
Current characteristics
vs.Current characteristics
characteristics
Current characteristics

Curves
Curves

Curves
Curves
Time vs. current characteristics

CurvesSet
CurvesSet

CurvesSet
CurvesSet
CURRENT
ME CHARACTERISTICS
VS. CURRENT CHARACTERISTICS

Setfor

Setfor
forHouse

forHouse
Setfor
Setfor
HouseService

HouseService
forHouse
forHouse
ServiceCut-out

ServiceCut-out
HouseService
HouseService
Cut-outFuse

Cut-outFuse
ServiceCut-out
ServiceCut-out
FuseLinks

FuseLinks
Links

Links
Cut-out
Cut-out
fff Cut
-CURRENT off - current characteristics
Cut
T-Cut-Current
OFFoff
Current
off characteristics
- -CURRENT
-Current characteristics
CHARACTERISTICS
CHARACTERISTICS
characteristics
Current characteristics

9 9
51 Mersen • BS88 LV Fuse Links & Fuse Holders 9 9
CO M PA R I S O N C H A R T

Comparison chart for feeder pillar fuse links

COMPETITORS MERSEN RATINGS

JPUxx xxxMJ30-8 BJU42VxxxPA 20 - 200 amps


JPUxx xxxMJ30-7 BJU42VxxxPA 20 - 200 amps
JSUxx xxxMJ31-7 BJU42VxxxSA 20 - 200 amps
JPUxx xxxPJ30-7 BJU42VxxxPB 250 - 400 amps
JSUxx xxxPJ31-7 BJU42VxxxSB 250 - 400 amps
JPUxx xxxRJ31-7 BJU42VxxxSC 450 - 500 amps
JSUxx xxxSJ31-6 BJU42VxxxSD 560 - 630 amps

Mersen numbering system

B JU 42V XXX PA

BS88 J type utility fuse Rated Voltage (415V AC) Current Rating P-82mm fixing centre, A-036.1mm

Comparison chart for house service cut out fuse links


COMPETITORS MERSEN RATINGS

MExx xxKR85 BME42Vxxx 5 - 80 amps


MFxx xxxLR85 BMF42Vxxx 30 - 100 amps

Mersen numbering system

B ME 42V XXX

BS88 Part Number Rated Voltage (415V AC) Current Rating

B MF 42V XXX

BS88 Part Number Rated Voltage (415V AC) Current Rating

This list is intended for guidance only. Mersen do not guarantee identical performance for the comparative types.
It is essential that the performance characteristics are checked to ensure compatibility

52 Mersen • BS88 LV Fuse Links & Fuse Holders


A P P L I C AT I O N I N FO R M AT I O N

Selection Procedure for Feeder Pillar Fuse Links for protection


of distribution transformer
Mersen range of feeder pillar fuse-links have wedge tightening contacts of standard dimensions
(82mm & 92mm) and performance
intended for use in a.c. electricity supply networks. These fuses comply as per IEC60269-2, BS: 88
Part 5 requirements.
Selection:
1. The primary fuse side is selected as per table below based on transformer ratings.

RATED VOLTAGE
RANGE OF 3/7.2 6/12 10/24 20/36
FUSE-LINK (KV)

SERVICE VOLTAGE
6 10 20 30
OFTRANSFORMER (KV)

RATED RATED RATED RATED


REL. SHORT TRANSFORMER CURRENT TRANSFORMER CURRENT TRANSFORMER CURRENT TRANSFORMER CURRENT
TRANSFORMER
CIRCUIT RATED OF RATED OF RATED OF RATED OF
OUTPUT (KVA)
VOLTAGE CURRENT (A) FUSE-LINK CURRENT (A) FUSE-LINK CURRENT (A) FUSE-LINK CURRENT (A) FUSE-LINK
(A) (A) (A) (A)

4.8 16-20 2.9 10 1.5 4 0.96 2-6.3


100 9.6 20-31.5 5.8 16-20 2.9 10 1.9 6.3-10
125 12 25-40 7.2 20-25 3.6 10-16 2.4 6.3-10
160 15.4 31.5-50 9.2 20-31.5 4.6 16-20 3.1 10
200 19.2 40-63 11.5 25-40 5.8 16-20 3.8 10-16
Uk = 4%
250 24.1 40-80 14.4 31.5-50 7.2 20-25 4.8 16-20
Application Information
Application Information 315 30.3 50-100 18.2 40-63 9.1 20-31.5 6.3 16-25
r Pillar Fuse Links for
400 protection
38.5 of distribution
63-125 23.1 40-80 11.5 25-40 7.7 20-25
Application Information
Application Information

500 8.1 80-160 28.9 50-100 14.4 31.5-50 9.6 20-31.5


protection of distribution
630 transformer
60.6 100-200 36.4 63-100 18.2 40-63 12.1 25-40
nks have wedge tightening contacts of standard dimensions (82mm &
a.c. electricity supply 800 These fuses77.1
networks. comply 125-200 46.2
as per IEC60269-2, 80-125 23.1 40-63 15.4 31.5-40
ntacts of standard dimensions (82mm & 92mm) and performance
Uk = 5%
mply as per IEC60269-2, 1000
BS: 88 96.3
Part 5 requirements. 125-160 57.7 100-160 28.9 50-80 19.2 40-50
1250 120.3 160-200 72.2 125-200 36.1 63-100 24.1 40-50
Uk = 6% on transformer
table below based 1600 ratings 154 200 92.4 125-200 46.2 80-100 30.8 50-63
on transformer ratings.

10000

20/36
20/36 6
4

2
Curve ‘A’
30
30 1000
6
4
of of

Curve ‘B’
rated

(A)(A)

2
current
(A)(A)

current
fuse-link
rated

100
current
Transformer

fuse-link

6
current

4
Rated
Rated

10
TIME(SECONDS)

.96 2-6.3 6
0.96 2-6.3 4
1.9 6.3-10
1.9 6.3-10 2
2.4 6.3-10 1
2.4 6.3-10
3.1 10 6
3.1 10 4 125A
3.8
3.8
10-16
10-16 2 10A

4.8
4.8
16-20
16-20
0.1
6
6.3
6.3 16-25
16-25 4

7.7
7.7 20-25
20-25
2

0.01
9.6
9.6 20-31.5 1 2 4 6 8 10 2 4 6 8 100 2 4 6 8 1000 2
60A
CURRENT(AMPERES) 31A
2.1
12.1 25-40
Max permissible current
Magnetic inrush current

on primary side

15.4
5.4 31.5-40
31.5-40
Curve ‘A’ : Primary Fuse
19.2
9.2 40-50
40-50 Curve ‘B’ : Secondary Fuse
24.1
4.1 40-50
40-50
30.8
0.8 50-63
50-63

econdary fuse should• be


53 Mersen observed
BS88 (Feeder
LV Fuse Links & FusePillar fuse):
Holders
ld be observed (Feeder Pillar fuse):
A P P L I C AT I O N I N FO R M AT I O N

The following procedure for selecting secondary fuse should be observed (Feeder Pillar fuse):
a) Transformer ratings
• Service voltage (U)
• Rated output (S)
• Relative short-circuit voltage (UK 4%)
• Inrush current (factor 8…12 IN)
b) Time current characteristics of HV/LV fuse links

3. Procedure based on an example:


A 50 kVA transformer has a transformer rated primary full load current of 2.6A with a ratio 11kV/415V.
The short circuit current on secondary terminal short-circuit is given from the relative short-circuit voltage.
The fuse should be selected to operate within 2 seconds as the transformer is designed to withstand
minimum short circuit current (25 IN) for 2 seconds. The primary fuse link is selected to ensure withstand
of primary inrush current of 12 IN for 0.1 seconds.
Selection of secondary fuse is based on the full load current which includes 130% overload withstand
for 3 hours(secondary maximum current is 90.5A) and with temperature correction factor, the fuse-link
rating of 125A is selected (Please refer to Mersen Feeder Pillar fuse range-BJU42V125PA).

To check whether the selected fuse is ok, the following conditions needs to be satisfied.
• Referring to the curve above which consists of primary fuse time-current curve along with the
secondary fuse time-current curve reflected on to primary, it is found that the selected secondary fuse
will be operated within 2 seconds for minimum Short Circuit fault current on secondary side, thus
protecting transformer from secondary faults

54 Mersen • BS88 LV Fuse Links & Fuse Holders


A P P R OVA L S

Comparison chart for feeder pillar fuse links

55 Mersen • BS88 LV Fuse Links & Fuse Holders


G LO BA L E XP ERT
IN ELEC TRICAL POWER
A N D A D VA N C E D M AT E R I A L S .

EUROPE NORTH AMERICA ASIA


- 8995 - BR-BS88GP03-0622

UNITED KINGDOM USA INDIA


Mersen UK Teesside Limited Unit 12, Mersen USA Mersen India Pvt. Ltd.
Tungsten Building, George Street, Newburyport-MA L.L.C. # 19, 4 th Cross,
Portslade, West Sussex, BN41 1RA 374 Merrimac Street Bommasandra Industrial Area,
Tel: +44(0) 1273 425119 Newburyport, MA 01950 Bangalore – 560099
[email protected] Tel: +1 978-462-6662 Tel: +91 80 27834001/5/6
E-mail: [email protected]
FRANCE
Mersen France SB S.A.S.
Rue Jacques de Vaucanson
F-69720 Saint-Bonnet-de-Mure
Tel: + 33 4 72 22 66 11

EP.MERSEN.COM