MP-V - SmartX IP Controller Specification Sheet
MP-V - SmartX IP Controller Specification Sheet
com/buildings | 1
MP-V
SmartX IP Controller
MP-V
SmartX IP Controller
Universal inputs For all analog inputs, maximum and minimum levels
The universal inputs are ideal for any mix of can be defined to automatically detect over-range and
temperature, pressure, flow, status points, and similar under-range values.
point types in a building control system.
Triac outputs
As counter inputs, they are commonly used in energy The triac outputs can be used in many applications to
metering applications. As RTD inputs, they are ideal for switch 24 VAC on or off for external loads such as
temperature points in a building control system. As actuators, relays, or indicators. The triac outputs are
supervised inputs, they are used for security isolated from the controller. Triacs are silent and are not
applications where it is critical to know whether or not a adversely affected by relay contact wear.
wire has been cut or shorted. These events provide a
separate indication of alarms and events in the system.
MP-V
SmartX IP Controller
MP-V
SmartX IP Controller
• WorkStation/WebStation interface
eCommission SmartX Controllers mobile app • Script and Function Block programming options
Using the eCommission SmartX Controllers mobile • Device discovery
application, you can connect to one or many MP Series
controllers. You can connect to a single MP Series • Engineering efficiency
controller using the eCommission Bluetooth Adapter
connected to a SmartX Sensor. Using a wireless WorkStation/WebStation interface
access point or a network switch, you can connect to a WorkStation and WebStation provide a consistent user
network of MP Series controllers on the local IP experience regardless of which EcoStruxure BMS
network. server the user is logged on to. The user can log on to
the parent EcoStruxure BMS server to engineer,
Device configuration commission, supervise, and monitor the SmartX IP
With the eCommission SmartX Controllers mobile controller and its I/O as well as its attached SmartX
application, you can easily discover SmartX IP Sensors. For more information, see the WorkStation and
controllers on the IP network. You can change the WebStation specification sheets.
configuration of each controller, including the BACnet
and IP network settings, location, and parent server. To Script and Function Block programming options
save engineering time, you can save common device Unique to the industry, the MP Series controllers have
settings and then reuse them for controllers of the same both Script and Function Block programming options.
model. This flexibility assures that the best programming
method can be selected for the application. Existing
programs can easily be reused between the
EcoStruxure BMS server and the controller.
MP-V
SmartX IP Controller
MP-V
SmartX IP Controller
Part Numbers
Specifications
AC input
Nominal voltage .....................................................................................................................................................24 VAC
Operating voltage range .......................................................................................................................................+/-20 %
Frequency ...........................................................................................................................................................50/60 Hz
Maximum power consumption (MP-V-7A) ................................................................................................................21 VA
Maximum power consumption (MP-V-9A) ................................................................................................................22 VA
Power input protection ...............................................................................................MOV suppression and internal fuse
Environment
Ambient temperature, operating ..................................................................................................0 to 50 °C (32 to 122 °F)
Ambient temperature, storage ............................................................................................-40 to +70 °C (-40 to +158 °F)
Maximum humidity.....................................................................................................................95 % RH non-condensing
Material
Plastic flame rating ..............................................................................................................................................UL94 V-0
Ingress protection rating ............................................................................................................................................IP 20
MP-V
SmartX IP Controller
Mechanical
Dimensions ......................................................................................161 W x 198 H x 63 D mm (6.3 W x 7.8 H x 2.5 D in.)
MP-V
SmartX IP Controller
Communications
BACnet .........................................................................................................BACnet/IP, port configurable, default 47808
...................................................................................................BTL B-AAC (BACnet Advanced Application Controller)a
a) See the BTL Product Catalog for up-to-date details on BTL listed firmware revisions on BACnet International's home
page.
CPU
Frequency .......................................................................................................................................................... 500 MHz
Type ..........................................................................................................................................ARM Cortex-A7 dual-core
DDR3 SDRAM .......................................................................................................................................................128 MB
NOR flash memory ..................................................................................................................................................32 MB
Memory backup ......................................................................................................................128 kB, FRAM, non-volatile
Damper actuator
Torque rating .............................................................................................................................................6 Nm (53 lbf.in)
Stroke .........................................................................................................................................0° to 90°, fully adjustable
Timing .............Approximately 2 seconds/degree at 60 Hz and 2.4 seconds/degree at 50 Hz for 90° rotation at 24 VAC
Position indication ....................................................................................................................................Visual indication
Damper position feedback ..........................................................................................................................................Yes
Manual override ..................................................................................................................... Push-button clutch release
Damper shaft diameter ...................................................................................12.7 mm (0.5 inch) or 9.5 mm (0.375 inch)
..........................................................................Adapter kit AM-135 is required for 9.5 mm (0.375 inch) diameter shafts.
Damper shaft minimum length (from VAV box) ................................................................................22.2 mm (0.875 inch)
Air flow sensor
Range ........................................................................................................................................0 to 249 Pa (0 to 1 inH2O)
Resolution ................................................................................................................0.33 Pa (0.001 inH2O) at 25°C (77°F)
Accuracy ...............................................................................................±5% of 249 Pa (1.00 inH2O) span at 25°C (77°F)
Universal inputs, UI
Channels, MP-V-7A ....................................................................................................................................... 3, UI1 to UI3
Channels, MP-V-9A ....................................................................................................................................... 4, UI1 to UI4
Absolute maximum ratings .......................................................................................................................-0.5 to +24 VDC
A/D converter resolution ..........................................................................................................................................16 bits
Universal input protection .............................................................................Transient voltage suppressor on each input
Digital inputs
Range .........................Dry contact switch closure or open collector/open drain, 24 VDC, typical wetting current 2.4 mA
Minimum pulse width ..............................................................................................................................................150 ms
Counter inputs
Range .........................Dry contact switch closure or open collector/open drain, 24 VDC, typical wetting current 2.4 mA
Minimum pulse width ................................................................................................................................................20 ms
Maximum frequency..................................................................................................................................................25 Hz
MP-V
SmartX IP Controller
Supervised inputs
5 V circuit, 1 or 2 resistors
Monitored switch combinations.............................................................Series only, parallel only, and series and parallel
Resistor range ................................................................................................................................................1 to 10 kohm
For a 2-resistor configuration, each resistor must have the same value +/- 5 %
Voltage inputs
Range ..............................................................................................................................................................0 to 10 VDC
Accuracy...............................................................................................................................+/-(7 mV + 0.2 % of reading)
Resolution................................................................................................................................................................1.0 mV
Impedance..........................................................................................................................................................100 kohm
Current inputs
Range ................................................................................................................................................................0 to 20 mA
Accuracy..........................................................................................................................+/-(0.01 mA + 0.4 % of reading)
Resolution....................................................................................................................................................................1 μA
Impedance .............................................................................................................................................................47 ohm
Resistive inputs
10 ohm to 10 kohm accuracy .......................................................................................................+/-(7 + 4 x 10-3 x R) ohm
R = Resistance in ohm
10 kohm to 60 kohm accuracy .....................................................................................+/-(4 x 10-3 x R + 7 x 10-8 x R2) ohm
R = Resistance in ohm
Temperature inputs (thermistors)
Range................................................................................................................................-50 to +150 °C (-58 to +302 °F)
Supported thermistors
Honeywell .............................................................................................................................................................20 kohm
Type I (Continuum) ...............................................................................................................................................10 kohm
Type II (I/NET) .......................................................................................................................................................10 kohm
Type III (Satchwell) ...............................................................................................................................................10 kohm
Type IV (FD) ......................................................................................................................................................... 10 kohm
Type V (FD w/ 11k shunt) ....................................................................................................................Linearized 10 kohm
Satchwell D?T......................................................................................................................................Linearized 10 kohm
Johnson Controls .................................................................................................................................................2.2 kohm
Xenta....................................................................................................................................................................1.8 kohm
Balco.......................................................................................................................................................................1 kohm
Measurement accuracy
20 kohm...................................................................................................-50 to -30 °C: +/-1.5 °C (-58 to -22 °F: +/-2.7 °F)
...................................................................................................................-30 to 0 °C: +/-0.5 °C (-22 to +32 °F: +/-0.9 °F)
.................................................................................................................. 0 to 100 °C: +/-0.2 °C (32 to 212 °F: +/-0.4 °F)
.............................................................................................................100 to 150 °C: +/-0.5 °C (212 to 302 °F: +/-0.9 °F)
10 kohm, 2.2 kohm, and 1.8 kohm.......................................................-50 to -30 °C: +/-0.75 °C (-58 to -22 °F: +/-1.35 °F)
..........................................................................................................-30 to +100 °C: +/-0.2 °C (-22 to +212 °F: +/-0.4 °F)
.............................................................................................................100 to 150 °C: +/-0.5 °C (212 to 302 °F: +/-0.9 °F)
MP-V
SmartX IP Controller
Linearized 10 kohm .................................................................................-50 to -30 °C: +/-2.0 °C (-58 to -22 °F: +/-3.6 °F)
...............................................................................................................-30 to 0 °C: +/-0.75 °C (-22 to +32 °F: +/-1.35 °F)
.................................................................................................................. 0 to 100 °C: +/-0.2 °C (32 to 212 °F: +/-0.4 °F)
.............................................................................................................100 to 150 °C: +/-0.5 °C (212 to 302 °F: +/-0.9 °F)
1 kohm ..............................................................................................-50 to +150 °C: +/-1.0 °C (-58 to +302° F: +/-1.8 °F)
RTD temperature inputs
Supported RTDs ..............................................................................................................Pt1000, Ni1000, and LG-Ni1000
Pt1000
Sensor range .....................................................................................................................-50 to +150 °C (-58 to +302 °F)
Ni1000
Sensor range .....................................................................................................................-50 to +150 °C (-58 to +302 °F)
LG-Ni1000
Sensor range .....................................................................................................................-50 to +150 °C (-58 to +302 °F)
MP-V
SmartX IP Controller
Analog outputs, AO
Channels, MP-V-7A ....................................................................................................................................... 1, VO1/CO1
Channels, MP-V-9A .................................................................................................................2, VO1/CO1 and VO2/CO2
Analog output protection ............................................................................Transient voltage suppressor on each output
Voltage outputs
Range ..............................................................................................................................................................0 to 10 VDC
Accuracy..............................................................................................................................................................+/-60 mV
Resolution.................................................................................................................................................................10 mV
Minimum load resistance........................................................................................................................5 kohm to ground
Load range........................................................................................................................................................0 to +2 mA
Terminals .....................................................................................................................Voltage Output (VO), Return (RET)
Current outputs
Range ................................................................................................................................................................0 to 20 mA
Accuracy ............................................................................................................................................................+/-0.2 mA
Resolution..................................................................................................................................................................21 µA
Load range.....................................................................................................................................................0 to 650 ohm
Terminals .....................................................................................................................Current Output (CO), Return (RET)
MP-V
SmartX IP Controller
MP-V-7A
MP-V-9A
MP-V
SmartX IP Controller
a) For more information, see the Product Selection Guide (SmartX IP Controllers - Accessories). Abbreviations: UTP (Unshielded Twisted Pair), CMP (Plenum-rated
cable)
a) For more information, see the Product Selection Guide (SmartX IP Controllers - Accessories). Abbreviations: UTP (Unshielded Twisted Pair), CMP (Plenum-rated
cable), LSZH (Low Smoke Zero Halogen)
MP-V
SmartX IP Controller
a) For more information, see the Product Selection Guide (SmartX IP Controllers - Accessories). Abbreviations: UTP (Unshielded Twisted Pair), PVC (Polyvinyl
chloride)
Regulatory Notices
Federal Communications Commission CE - Compliance to European Union (EU)
FCC Rules and Regulations CFR 47, Part 15, Class B 2014/30/EU Electromagnetic Compatibility Directive
This device complies with part 15 of the FCC Rules. Operation is subject to the following two 2011/65/EU Restriction of Hazardous Substances (RoHS) Directive
conditions: (1) This device may not cause harmful interference. (2) This device must accept 2015/863/EU amending Annex II to Directive 2011/65/EU
any interference received, including interference that may cause undesired operation. This equipment complies with the rules, of the Official Journal of the European Union, for
governing the Self Declaration of the CE Marking for the European Union as specified in the
Industry Canada above directive(s) per the provisions of the following standards: EN 60730-1, EN 60730-2-
This Class B digital apparatus complies with Canadian ICES-003. 11, and EN 50491-3 Safety Standards.
Cet appareil numérique de la classe B est conforme à la norme NMB-003 du Canada.
Regulatory Compliance Mark (RCM) - Australian Communications and Media WEEE - Directive of the European Union (EU)
Authority (ACMA) This equipment and its packaging carry the waste of electrical and electronic equipment
This equipment complies with the requirements of the relevant ACMA standards made under (WEEE) label, in compliance with European Union (EU) Directive 2012/19/EU, governing the
the Radiocommunications Act 1992 and the Telecommunications Act 1997. These disposal and recycling of electrical and electronic equipment in the European community.
standards are referenced in notices made under section 182 of the Radiocommunications
Act and 407 of the Telecommunications Act.
UL 916 Listed products for the United States and Canada, Enclosed Energy
Management Equipment. UL file E80146.
www.schneider-electric.com