Modbus RTU - ASCII Slave Manual 2 - Simply Modbus Software
Modbus RTU - ASCII Slave Manual 2 - Simply Modbus Software
Home
Operation Manual
About
MODBUS
Simply Modbus Slave 2.1
Modbus RTU Slave and Modbus ASCII Slave Software
About
Enron System Requirements:
MODBUS
Windows NT, 95, 2000, XP. (not recommended for Windows 7 or Vista )
PC with serial port (built in, serial card or USB serial port)
RTU Slave
manual2
manual7 Installation - Simply Modbus Slave 2.1 (1.75 MB) :
manual8
Click to download SimplyModbusSlave2.1.zip
TCP Client Unzip the compressed files into a common folder on your hard drive.
Contact Known Issues with version 2.1: Two instances normally appears in the taskbar while the program is running, the runtime
engine and the program iself, Sometimes the runtime engine does not quit when the program is closed, although it is not
consistent and behaves differently on different PCs. It is more likely to happen when the program is opened and closed
within a few seconds. Waiting longer or sending a request before closing may help it quit properly. It may quit by itself after
a few minutes on some Windows 7 and Vista systems. Although it's okay on others.
Work Arounds: It can be forced to quit by right clicking on the taskbar item and selecting close. Using Alt-F4 to quit the
program also works better in some cases.
Simply Modbus Slave 7.1 looks and runs exactly like Simply Modbus Slave 2.1 but was created using a newer compiler. It
is a significantly larger download and has an install program. It appears to be more stable with the newer Windows versions.
see.....manual7
Simply Modbus Slave 7.1 will automatically use a license for Simply Modbus Slave if already installed on the PC.
https://www.simplymodbus.ca/RTUslavemanual2.htm 1/10
17/11/2020 Modbus RTU/ASCII Slave Manual 2 | Simply Modbus Software
The progress bar will take approximately 15 seconds to load the demonstration version.
During this time, you can press the ENTER KEY and see
After purchasing and receiving a license key by email, enter the key and press OK.
https://www.simplymodbus.ca/RTUslavemanual2.htm 2/10
17/11/2020 Modbus RTU/ASCII Slave Manual 2 | Simply Modbus Software
Program Summary:
When the program is opened, the circular clock indicator spins to show that the program is running. The program monitors
the chosen serial port looking for incoming bytes from a modbus master. All bytes received (and sent) are displayed in the
'Log'.
The most recent request received is displayed in the indicator labelled "Latest Request received". A lookup is done to
determine if the request has a valid SlaveID, function code, data addresses, valid data if writing and valid error detection
bytes (CRC or LRC.
The request must meet the following 2 conditions before a response is generated and sent:
1) The ID in the request (the first byte received) must match the entered Slave ID,
or 'Respond to all Slave IDs' must be checked.
If the ID does not match, the Slave program will ignore the request since it is intended for a different slave.
2) The CRC (if RTU mode) or LRC (if ASCII mode) at the end of the request must be correct.
The request must meet the following additional conditions before a response with data is generated and sent:
3) the request must have a function code that matches enabled data in the tables.
Function code 03 or 04 to read registers with a block of register data set with the same code.
Function code 06 or 16 to write registers with a block of register data set as read/write.
Function code 01 or 02 to read coils with a block of coil data set with the same code.
Function code 05 or 15 to write coils with a block of coil data set as read/write.
If not, an exception code 01 is generated and sent.
4) The requested registers or coils must exist in an enabled block. More specifically, the request must be for register
or coil addresses with a hex values that match the register number minus offset for one of the enabled tables.
If not, an exception code 02 is generated and sent.
For example, A request for 0003 addresses starting from 0002 will match a block setup with Registers 40001 to
40008 and offset 40001. It will reply with data from 40003, 40004 & 40005. A request for 0007 addresses
starting from 0002 will not match the same block, since it needs registers 40003 through 40009.
Since 40009 does not exist in the block, an exception code 02 would be generated and sent.
5) When receiving function codes that request writing data, the data size and format must be correct.
If not, an exception code 03 is generated and sent.
For example, A FC16 request to write 0005 16bit addresses must contain 10 data bytes (two per address),
otherwise an exception code 03 would be generated and sent.
https://www.simplymodbus.ca/RTUslavemanual2.htm 3/10
17/11/2020 Modbus RTU/ASCII Slave Manual 2 | Simply Modbus Software
When a response is generated, it is written to the serial port and the Log.
On a multi-dropped network (eg. RS485) with multiple slaves, this application will also receive responses from other slaves.
All messages received will be monitored and processed to determine if they are valid requests from a modbus master.
Setup Details:
Controls (inputs) that can be changed by the user are shown in yellow.
Indicators (outputs) that cannot be changed are shown in blue.
Enter the input information in the controls to match the Slave you wish to emulate.
serial settings: Set these settings to match the setting of the modbus slave device connected.
baud: The baud rate (bits per second) of the serial connection.
data bits: The number of data bits in each byte, RTU mode requires 8, ASCII mode is usually 7 but may be 8.
stop bits: The number of stop bits for each byte sent. allowable values are 1, 1.5 or 2 .
parity: The value of the parity bit for each byte sent. allowable values are none, odd, even, mark or space.
When this box is checked, the program will respond to requests directed to any Slave ID.
Other Settings:
When checked, the program will send the data high byte first
When checked, the program will send the data high word first for 32 bit data types.
When checked, the program will apply a random multiplier to the values found in the tables
to a maximum of the '%reading' value entered.
The program will then give slightly different responses when the same request is repeated.
All bytes sent and received are added to the byte history log with date/time stamps.
Displays a 'Save As..' dialog box to allow the log contents to be saved to a text file.
https://www.simplymodbus.ca/RTUslavemanual2.htm 4/10
17/11/2020 Modbus RTU/ASCII Slave Manual 2 | Simply Modbus Software
Uncheck this box to keep the log from scrolling when new data is added.
Press the Close box 'X' in the top corner to Exit the program.
Press the button to display and change the register and coil tables.
Six data tables can be setup that contain the blocks of data for the slave to respond with.
https://www.simplymodbus.ca/RTUslavemanual2.htm 5/10
17/11/2020 Modbus RTU/ASCII Slave Manual 2 | Simply Modbus Software
Each register block is set to respond to either FC03 or FC04 read register requests.
Each coil block is set to respond to either FC01 or FC02 read coil requests.
Each block can be set as read only to accept the only the function code above,
or read/write to allow the host to change the data with FC06&16 (for registers) and FC05&15 (for coils)
Each register block can be set as 16bit registers (typical for standard modbus),
or 32bit registers (used for Enron modbus 32bit Int (5000) block or 32bit float (7000) block)
This control selects the data type for the table. more info...
All values in one table have the same data type.
Selectable as 32bit IEEE Floating Point
32bit Unsigned Integer (0 to 4.3 billion)
32bit Signed Integer (-2.1 to 2.1 billion)
16bit Unsigned Integer (0 to 65535)
16bit Signed Integer (-32768 to 32767)
Selecting a 32bit Data type with 16 bit register size will use 2 registers for each value.
Sets the difference between the register number and the hex number used in the commands for each block.
For example register#40005 minus offset 40001 = hex address 0004)
A read-only indicator displaying the hexadecimal equivalent of register or coil numbers minus the offset.
Displays a 'Save As..' dialog box to allow saving the current settings to a text file.
The data file is saved in csv format (comma separated values).
The file can be edited with a spreadsheet application and reloaded into the program using RESTORE CFG
Displays a 'Open File' dialog box to allow selecting a previously saved settings file to load.
https://www.simplymodbus.ca/RTUslavemanual2.htm 6/10
17/11/2020 Modbus RTU/ASCII Slave Manual 2 | Simply Modbus Software
The configuration file is saved in tabbed text format (tab separated values) and appears like this in notepad...
The preset tabs in Notepad cause the cells with long labels to push the other columns over.
Sending it to, or opening it from, a spreadsheet program like Excel will use the tabs as column delimiters as shown here...
The data can be saved and edited within a spreadsheet and then loaded into the program with the RESTORE CFG button.
https://www.simplymodbus.ca/RTUslavemanual2.htm 7/10
17/11/2020 Modbus RTU/ASCII Slave Manual 2 | Simply Modbus Software
Physical Connection:
To receive requests from a modbus master before sending a message, the serial port needs to be physically connected to a
modbus master device. The simplest connection is RS232C on a single serial cable.
DTE masters (PC serial ports) have DB9 male connectors which transmits on pin3, receives pin2 and grounds on pin5. A
DCE slave will have a DB9 Female connector which will allow the use of a straight through cable. A DTE slave will have a
DB9 Male connector and will require the use of a null modem cable.
The RS232 specification states a maximum distance of 50 feet at 20kbaud. Slightly longer connections are possible at
slower baud rates depending on cable quality and noise in the area.
Modems and radios are used to transmit longer distances. These are typically DCE devices so straight through cables can be
used. Some MDS non-spread spectrum radios require RTS Delay to be used so a 4th conductor is needed on pin 4.
RS485 converters can be used to extend the distance up to 4000 feet at 100kbaud. This can be a 4 wire or 2 wire system,
depending on the converter. This also allows multi-dropping up to 32 devices on one pair of wires.
Program Operation:
Once the correct input data is entered, the program operates by itself.
When bytes are read on the serial port, they are displayed here.
The bytes are then processed to see if a response should be generated.
The first byte of the request is shown in 'ID'. This is the Slave Address that the Master is requesting a response from.
This hex value is converted to decimal and compared to the 'Slave ID' entered.
If they match or if "Respond to all Slave IDs" is selected, the 'ID match' indicator will turn green as shown.
The second byte of the request is shown in 'fc'. This is the Function code indicating which table to read from.
This program support function codes 01,02,03,04,05,06,15 (0F hex) and 16 (10 hex).
If one of these function codes is found in the request, the 'fc okay' indicator will turn green as shown.
https://www.simplymodbus.ca/RTUslavemanual2.htm 8/10
17/11/2020 Modbus RTU/ASCII Slave Manual 2 | Simply Modbus Software
The 3rd and 4th bytes of the request are shown in '1st register req'. This is the register address
of first register to read.
This number is converted from hex to decimal and shown in 'First Register req'.
The program then looks for this register in the data tables showing the function code above.
If found, the matching table is displayed in 'found in block', and the 'data found' indicator will turn green as shown.
The 5th and 6th bytes of the request are shown in 'number of regs'. This is the number of registers
to read.
This hex value is converted to decimal and displayed in '# of Registers'.
The 7th and 8th bytes of the request are shown in 'CRC' (or 'LRC' if in ASCII mode).
The expected CRC (or LRC) is calculated from the first 6 bytes and displayed in 'Expected CRC' (or 'Expected LRC').
If the two match, the 'crc ok' indicator will turn green as shown.
crc The last 2 bytes of a modbus RTU message are the cyclic redundancy check. These are error detection bytes more
info...
lrc ASCII Mode messages are preceded with a colon and the crc is replaced with an lrc (longitudinal redundancy check),
carriage return and line feed characters. more info...
If the 'ID match', 'fc okay', 'data found' and ' crc ok' indicators all turn green, a response with data will be generated.
The data is read from the matching table and a response is generated and returned.
A breakdown of the response is shown in this table. A scrollbar will appear for
responses with more than 5 values as shown here.
The columns show the register number (including the offset), its value in hex,
If the 'ID match' and ' crc ok' indicators both turn green, but the function code found is not supported, a response is
generated with exception code '01'.
If the 'ID match' and ' crc ok' indicators both turn green, but the data is not found in the table, a response is generated with
exception code '02'.
https://www.simplymodbus.ca/RTUslavemanual2.htm 9/10
17/11/2020 Modbus RTU/ASCII Slave Manual 2 | Simply Modbus Software
If the 'ID match' and ' crc ok' indicators both turn green, and a 'write data' function code 05, 06, 15, or 16 is found followed
by valid data, the data is written to the tables and an appropriate response is generated.
If the 'ID match' and ' crc ok' indicators both turn green, and a 'write data' function code 05, 06, 15, or 16 is found followed
by invalid or missing data, a response is generated with exception code '03'.
Troubleshooting
Check the physical connection to make sure the correct conductors are on the correct pins and the correct serial port.
Check the serial settings in the master device to make sure they match the settings in the slave.
Make sure the serial port driver file (serpdrv) is in the same folder as Simply Modbus Slave 2.1.exe