Sensor Installation Manual
Sensor Installation Manual
E-T / TRHM-E7
Temperature/Humidity sensors E- LDSx-y
Liquid Detection Sensor
E-SRN-M
E-BCN-R Siren
Beacon
E-TDS
Tamper Switch
E-M-DCS3
Door Contact Switch
TABLE OF CONTENTS
Introduction...................................................................................................................................................................... 2
Connect Sensors to E-MINI-LXO /-MICRO-T(rhp).......................................................................................................... 2
E-T or TRHM-E7.......................................................................................................................................................... 2
Sensor Cable ............................................................................................................................................................... 3
E-LD............................................................................................................................................................................. 4
Contact Sensors .......................................................................................................................................................... 5
Connect Sensors to The E-xD Models............................................................................................................................ 6
RJ45 Sensors .............................................................................................................................................................. 6
Temperature, Humidity Sensors ............................................................................................................................... 6
Contact Sensors ....................................................................................................................................................... 7
Digital In Terminals................................................................................................................................................ 7
Liquid Detection Sensors.......................................................................................................................................... 9
BEACON and SIREN Connections ........................................................................................................................... 10
RJ45 Sensor Cable.................................................................................................................................................... 11
Liquid Detection False Alert Fix................................................................................................................................. 11
TABLE OF FIGURES
1
NTI ENVIROMUX SENSOR INSTALLATION
INTRODUCTION
Many different sensors can be connected to the ENVIROMUX Series Enterprise Environment Monitoring Systems. Series models
include E-16D/5D/2D, E-MINI-LXO and E-MICRO-T(RHP). A complete listing of available sensors and accessories can be found
at
http://www.networktechinc.com/environment-monitor-16d.html for the E-16D,
http://www.networktechinc.com/environment-monitor-5d.html for the E-5D,
http://www.networktechinc.com/environment-monitor-2d.html for the E-2D, and http://www.networktechinc.com/environment-
monitoring.html for the E-MINI-LXO.
http://www.networktechinc.com/environment-monitor-micro.html for the E-MICRO-T(RHP)
Manuals for each Environment Monitoring System covering installation and configuration for all features can also be found at
these websites. This manual is only provided to instruct how to connect the various sensors to these systems.
E-T or TRHM-E7
For measuring temperature and humidity, the E-MINI-LXO and E-MICRO-T(RHP) uses the E-T-E7 (temperature only), E-TRHM-
E7 (combination temperature and humidity sensor). For high-temperature environments, E-MINI-IND uses the E-T-IND-E7 High
Temperature Sensor.
1. Connect either of the temperature / humidity sensors to an available port on the E-MINI-LXO. Plug the RJ45 connector
to either of the two ports marked "TEMPERATURE/HUMIDITY". The E-T/TRHM-E7 sensors can be secured anywhere
that the temperature and/or relative humidity need to be sensed.
Note: The E-TRHM-E7 sensor will work with the E-MINI-LXO provided firmware version 2.3 or later is installed, and with
the E-MICRO provided firmware version 1.3 or later is installed.
Note: Mounting the sensor in the path of a fan or on a heated surface may affect the accuracy of the sensor’s readings.
Note: For best results, use the E-T-IND-E7 with model E-MINI-IND.
2
NTI ENVIROMUX SENSOR INSTALLATION
Sensor Cable
The CAT5 connection cable between the E-MINI-LXO / E-MICRO-T(RHP) and the RJ45 Sensors is terminated with RJ45
connectors and must be wired according to the EIA/TIA 568 B industry standard. Wiring is as per the table and drawing below.
Pair 3
RJ45 Sensor Socket Wiring for E-MINI-LXO
and E-MICRO-T(RHP): Pair 2 Pair 1 Pair 4
Signal Pin Wire Color Pair
+5 VDC 1 White/Orange 2
TRIG 2 Orange 2 T R T R T R T R
SCL 3 White/Green 3
1 2 3 4 5 6 7 8
GND 4 Blue 1
+ - + - + - + -
SDA 5 White/Blue 1
GND 6 Green 3
FREQ 7 White/Brown 4
ID 8 Brown 4
3
NTI ENVIROMUX SENSOR INSTALLATION
E-LD
Connect the liquid detection sensor E-LD (E-LDx-y, E-LD-LCx-y, E-CDx-y) to a set of terminals (1-5) marked “DIGITAL IN”.
The twisted orange sensing cable should be placed flat on the surface (usually the floor) where liquid detection is desired. If tape
is required to hold the sensor in place, be sure to only apply tape to the ends, exposing as much of the sensor as possible. At
least 5/8" of the sensor must be exposed for it to function. (See Figure 2)
Do not
expose
connector
to liquids.
Do not
submerge.
Note: The connection between the two-wire cable and the sensor cable is not designed for exposure to liquids and
cannot be submerged.
After installation of rope style leak detection sensor in its desired location, it is very important to test the sensor to verify correct
installation. This applies to all rope-style leak detection sensors.
4
NTI ENVIROMUX SENSOR INSTALLATION
If the rope is still giving you problems after you have cleaned it with isopropyl alcohol or if you think the rope needs a good
scrubbing, you can clean it with warm soapy water. You will have to remove the rope from its installed location. It may be helpful
to label the sections of the rope or note their locations before you start for an easier re-installation.
1. Gather Dawn dish soap, a large bucket or plastic bin, warm water, soft-bristled scrub brushes, and clean rags.
2. Add dish soap to the bucket of water, approximately 1 cup of detergent to 1 gallon of warm water. To determine if the
solution is concentrated enough, place your finger and thumb in the water and rub them together. You should feel a
slick/slimy residue. If you do not feel a residue, add more detergent to the water and gently mix to distribute the soap.
3. Submerge a section of the rope in the water. Using a scrub brush or rag, scrub along all sides of the rope with firm
pressure.
4. Remove the section of the rope from the soapy solution and rinse it in a bucket of clean, fresh water.
5. Ensure that there are no oily deposits along the length of the rope. If the rope does not appear clean, submerge it in
water and scrub again, repeating steps (3) to (5).
6. Hang the clean rope up to dry. Try to point the connectors down, so water cannot pool inside the connectors. The drying
process may take 6-8 hours, depending on the room conditions.
7. When the rope is completely dry, reinstall it in its original location.
Contact Sensors
Up to five dry-contact sensors or liquid detection sensors can be connected to the terminals marked “DIGITAL IN”. Sensors with
16-26 AWG connection wires that operate on 5V at 10mA maximum current may be used. A contact resistance of 10k or less
will be interpreted by the E-MINI-LXO as a closed contact.
Note: The terminal block is removable for easy sensor wire attachment if needed.
Shielded cable must be used to connect to the DIGITAL IN terminals in order to meet CE emission requirements.
Connect the drain wire of the shield to the ground ( ) terminal of the dry contact in addition to the contact return wire.
5
NTI ENVIROMUX SENSOR INSTALLATION
RJ45 Sensors
Several sensors for the E-16D/5D/2D Enterprise Environment Monitoring Systems have RJ45 connection ports. Some of these
sensors include E-STS (temperature only), E-STHSB (temperature and humidity), E-STHS-99 (wide range temperature and
humidity) and E-LDS (liquid detection). In all cases, the CAT5 cable between the sensor and the ENVIROMUX can be up to 1000
feet in length.
6
NTI ENVIROMUX SENSOR INSTALLATION
Contact Sensors
Some sensors do not have RJ45 connectors on them and instead have terminal blocks. These can either be connected to the
"DIGITAL IN" connectors or they can be terminated and plugged into the remaining RJ45 connectors (see Figure 6). (The
illustration uses CAT5 patch cable to make cable connection easy.) Examples of these sensors include E-IMD (motion detector),
E-IMD-CM (ceiling mount motion detector), E-SDS
(smoke detection), and E-GBS (glass break sensor).
Digital In Terminals
To connect contact sensors without using RJ45 connectors, terminal blocks have been provided labeled "DIGITAL IN". Two wire
switch-only type sensors can be connected to the plus (+) and minus (-) terminals (E-16D) or the plus (+) and ground ( )
terminals (E-2D/5D). If the sensors require a 12V power source to operate, these models include 12V and ground terminals for a
power connection. Connect each two-wire or four-wire contact sensor using 16-26 AWG wire.
FYI: The terminal block is removable for easy sensor wire attachment if needed.
7
NTI ENVIROMUX SENSOR INSTALLATION
Examples of devices the are "switch only" type devices are E-DCSR-V2 (Rugged Door Contact Sensor), E-DCSR-UV2 (Rugged
Door Contact Sensor with Universal Magnet), or E-LLS-SF-xxCM (Liquid Level Float Switch).
8
NTI ENVIROMUX SENSOR INSTALLATION
After installation of rope style leak detection sensor in its desired location, it is very important to test the sensor to verify correct
installation. This applies to all rope-style leak detection sensors (E-LD/ E-LD-LC / E-CD, etc.).
9
NTI ENVIROMUX SENSOR INSTALLATION
Terminals have been provided for connection of a beacon (E-BCN-R(L)), siren (E-SRN-M, E-BEEP1, etc) , or beacon and
siren (E-SRN-BCNL/R-O) to use for visual alerts and audible alerts when configured. Devices such as this can be installed in
locations best suited to get attention. All devices must be installed using 16-26 AWG wire.
10
NTI ENVIROMUX SENSOR INSTALLATION
For a complete listing of available sensors and accessories go to the product page for ENVIROMUX Enterprise Environment
Monitoring Systems at http://www.networktechinc.com/enviro-monitor.html , and at http://www.networktechinc.com/enviro-
mini.html for the E-MINI-LXO. Manuals for each product covering installation and configuration for all features can also be found
at these websites.
The CAT5 connection cable between the ENVIROMUX and connected external sensors is terminated with RJ45 connectors and
must be wired according to the EIA/TIA 568 B industry standard. Wiring is as per the table and drawing below. The sensors
that connect to “RJ45 Sensor” ports (E-xD) or the “Temperature/Humidity” ports (E-MINI-LXO) are all designed to use cables
wired to this standard.
Pair 3
Problem: Receiving false alert messages from installed ENVIROMUX Liquid Detection sensor E-LDx-y or
E-LD-LCx-y.
Cause: Sensor is in environment with significant electrical noise and is picking up this noise and conducting it back
to the ENVIROMUX Environment Monitoring System providing a false signal of closure.
Solution: Install a .1uf capacitor (available from NTI) between the two “Digital In” terminals the Liquid Detection
sensor is connected to as shown below. (E-MINI-LXO used for example, but this applies to any ENVIROMUX
Environment Monitoring System.)
Note: This is to be applied only to installations of Liquid Detection Sensors. Applications with other sensors
may cause the ENVIROMUX to malfunction.
11
NTI ENVIROMUX SENSOR INSTALLATION
TRADEMARK
ENVIROMUX is a registered trademark of Network Technologies Inc in the U.S. and other countries.
COPYRIGHT
Copyright © 2008-2021 by Network Technologies Inc. All rights reserved. No part of this publication may be reproduced, stored
in a retrieval system, or transmitted, in any form or by any means, electronic, mechanical, photocopying, recording, or otherwise,
without the prior written consent of Network Technologies Inc, 1275 Danner Drive, Aurora, Ohio 44202.
CHANGES
The material in this guide is for information only and is subject to change without notice. Network Technologies Inc reserves the
right to make changes in the product design without reservation and without notification to its users.
12