HA033172 - 3 - EPackLITE - 2PH - Power Controller - User - Guide
HA033172 - 3 - EPackLITE - 2PH - Power Controller - User - Guide
2
EPack
Legal Information
The information provided in this documentation contains general descriptions and/or
technical characteristics of the performance of the products contained herein. This
documentation is not intended as a substitute for and is not to be used for
determining suitability or reliability of these products for specific user applications. It
is the duty of any such user or integrator to perform the appropriate and complete risk
analysis, evaluation and testing of the products with respect to the relevant specific
application or use thereof. Eurotherm Limited, Schneider Electric or any of its
affiliates or subsidiaries shall not be responsible or liable for misuse of the
information contained herein.
If you have any suggestions for improvements or amendments or have found errors
in this publication, please notify us.
You agree not to reproduce, other than for your own personal, non-commercial use,
all or part of this document on any medium whatsoever without permission of
Eurotherm Limited, given in writing. You also agree not to establish any hypertext
links to this document or its content. Eurotherm Limited does not grant any right or
license for the personal and non-commercial use of the document or its content,
except for a non-exclusive license to consult it on an "as-is" basis, at your own risk.
All other rights are reserved.
All pertinent state, regional, and local safety regulations must be observed when
installing and using this product. For reasons of safety and to help ensure compliance
with documented system data, only the manufacturer should perform repairs to
components.
When devices are used for applications with technical safety requirements, the
relevant instructions must be followed.
Failure to use Eurotherm Limited software or approved software with our hardware
products may result in injury, harm, or improper operating results.
HA033172 Issue 3 3
Table of Contents EPack
Table of Contents
Table of Contents ...............................................................................4
Safety Information ..............................................................................8
Important Information................................................................................... 8
Safety Notes ......................................................................................9
Reasonable use and responsibility .............................................................11
SELV ................................................................................................................ 12
Symbols Used in the Instrument Labeling........................................................ 13
Hazardous Substances .................................................................................... 13
Cybersecurity ................................................................................................... 14
Introduction ................................................................................................ 14
Cybersecurity Good Practices ................................................................... 14
Introduction ......................................................................................15
Unpacking the Units ......................................................................................... 15
Order Code ...................................................................................................... 16
Software Upgrade Options......................................................................... 18
Installation ........................................................................................20
Mechanical Installation..................................................................................... 20
Mounting details......................................................................................... 20
Mechanical installation requirements......................................................... 22
Mounted clearance dimensions ................................................................. 23
Bulkhead Mounting .............................................................................. 23
DIN Rail Mounting................................................................................ 26
Dimensions ................................................................................................ 27
16A to 32A unit dimensions ................................................................. 27
40A to 63A unit dimensions ................................................................. 28
80A to 100A unit dimensions ............................................................... 29
125A unit dimensions........................................................................... 30
Summary - all units (16A - 125A) ......................................................... 31
Electrical Installation ........................................................................................ 32
Connection Details..................................................................................... 33
Auxiliary supply .......................................................................................... 37
24V ac/dc auxiliary supply ................................................................... 37
85 to 550Vac auxiliary supply .............................................................. 37
Connections (Supply Power and Load) ..................................................... 39
16A to 32A and 40A to 63A Units ......................................................... 41
......................................................................................................................... 41
Load Configurations................................................................................... 43
Delta .................................................................................................... 43
Star ...................................................................................................... 44
Signal wiring............................................................................................... 45
Firing Enable........................................................................................ 45
Alarm Acknowledge ............................................................................. 45
Main Setpoint ....................................................................................... 45
Relay Output ........................................................................................ 45
I/O Input & Output Details .................................................................... 47
Fuse Holders Contact Data (Fuse Ordering Code HSM)..................... 48
Operator Interface ............................................................................51
Display ............................................................................................................. 51
Status area................................................................................................. 51
Softkey icons.............................................................................................. 52
Pushbuttons ..................................................................................................... 53
Pushbutton functions ................................................................................. 53
Menu item value selection ......................................................................... 53
4 HA033172 Issue 3
EPack Table of Contents
HA033172 Issue 3 5
Table of Contents EPack
6 HA033172 Issue 3
EPack Table of Contents
HA033172 Issue 3 7
Safety Information EPack
Safety Information
Important Information
Read these instructions carefully and look at the equipment to become familiar with
the device before trying to install, operate, service, or maintain it. The following
special messages may appear throughout this manual or on the equipment to warn of
potential hazards or to call attention to information that clarifies or simplifies a
procedure.
W DANGER
DANGER indicates a hazardous situation which, if not avoided, will result in
death or serious injury.
W WARNING
WARNING indicates a hazardous situation which, if not avoided, could result in
death or serious injury.
W CAUTION
CAUTION indicates a hazardous situation which, if not avoided, could result in
minor or moderate injury.
NOTICE
NOTICE is used to address practices not related to physical injury.
8 HA033172 Issue 3
EPack Safety Notes
Safety Notes
W DANGER
HAZARD OF ELECTRICAL SHOCK, EXPLOSION OR ARC FLASH
• Apply appropriate personal protective equipment (PPE) and follow safe electrical work practices. See
applicable national standards e.g. NFPA70E, CSA Z462, BS 7671, NFC 18-510.
• This equipment must only be installed and serviced by qualified electrical personnel.
• The product is not suitable for isolation applications, within the meaning of EN60947-1. Turn off all power
supplying this equipment before working on the loads of the equipment.
• Turn off all power supplying this equipment before working on equipment.
• Always use a properly rated voltage sensing device to confirm power is off.
• If on receipt, the unit or any part within is damaged, do not install but contact your supplier.
• Do not disassemble, repair or modify the equipment. Contact your supplier for repair.
• This product must be installed, connected and used in compliance with prevailing standards and/or
installation regulations.
• The unit must be installed in an enclosure or cabinet connected to the protective earth ground.
• Electrically conductive pollution must be excluded from the cabinet in which the product is mounted.
• Do not allow anything to fall through the case apertures and ingress the product.
• Before any other connection is made, the protective earth ground terminal must be connected to a protective
conductor.
• Protective conductor must be sized in compliance with local and national regulatory requirements.
• Tighten all connections in conformance with the torque specifications. Periodic inspections are required.
• High speed fuses (supplemental fuses in addition to branch circuit protective device), as listed in fusing
sections, are mandatory to protect EPack Lite against load short circuit.
• If opening of either the branch circuit protective device or the high-speed fuses (supplemental fuses) occurs,
the product must be examined by suitably qualified personnel and replaced if damaged.
• A High-speed fuse (supplemental fuses in addition to branch circuit protective device) or a double protection
fuse as listed in fusing sections is mandatory for 85Vac to 550Vac auxiliary supply.
• If opening of any fuses or branch circuit protection device that supply the 85Vac to 550Vac auxiliary supply
occurs, first check the wiring. If the wiring is not damaged, do not replace the fuse and contact the
manufacturer's local service center.
• The maximum voltage between any pole of the 85Vac to 550Vac auxiliary supply and all other terminals must
be lower than 550Vac.
• The “24V auxiliary supply” is an SELV circuit. The supply Voltage must be derived from a SELV or PELV
circuit.
• The I/O Input & Output, the Communications ports are SELV circuit. They must be connected to SELV or
PELV circuit.
Failure to follow these instructions will result in death or serious injury.
HA033172 Issue 3 9
Safety Notes EPack
W DANGER
HAZARD OF ELECTRICAL SHOCK, EXPLOSION OR ARC FLASH
• The relay output and the fuse holders contacts are compliant to the SELV requirements; they can be
connected to SELV, PELV circuit or to voltage up to 230V (maximum value of rated operational voltage to
earth:230V)
• Ensure all cables and wiring harness are secured using a relevant strain relief mechanism.
• Replace doors and plug-in terminals before turning on power to this equipment.
• Use appropriate safety interlocks where personnel and/or equipment hazards exist.
Failure to follow these instructions will result in death or serious injury.
W DANGER
HAZARD OF FIRE
• Product current rating must be greater than or equal to the maximum current of the load.
• This product does not contain any branch-circuit protection, the installer must add branch-circuit protection
upstream of the unit.
• Branch circuit protection must be selected according to maximum current in each phase and must be rated in
compliance with local and national regulatory requirements.
• Power connections: The cables must be rated 90°C stranded copper only, the cross section must be selected
according to the branch circuit protection rating.
• The cables used to connect the EPack Lite’s auxiliary supply and voltage reference must be protected by
branch-circuit protection. Such branch-circuit protection must comply with local and national regulatory
requirements.
• Connection of two conductors in the same terminal is not permitted, partial or total loss of connection may
create an overheat of the terminals.
• At commissioning ensure that under maximum load condition, the ambient temperature of the product will not
exceed the limit stated in that manual.
• Heat-sink must be cleaned regularly. Periodicity depends on the local environment, but should not exceed 1
year.
Failure to follow these instructions will result in death or serious injury.
10 HA033172 Issue 3
EPack Safety Notes
W WARNING
UNINTENDED EQUIPMENT OPERATION
• Do not use the product for critical control or protection applications where
human or equipment safety relies on the operation of the control circuit.
• Signal and power voltage wiring must be kept separate from one another.
Where this is impractical, all wires must be rated to the power voltage &
shielded cables are recommended for signal wiring.
• This product has been designed for environment A (Industrial). Use of this
product in environment B (domestic, commercial and light industrial) may
cause unwanted electromagnetic disturbances in which cases the installer
may be required to take adequate mitigation measures.
• Nominal current of product must be set between 25% & 100% of maximum
current.
W CAUTION
HOT SURFACE RISK OF BURNS
• Allow heatsink to cool before servicing.
The safety and EMC of any system incorporating this product is the responsibility of
the assembler/installer of the system.
Failure to use approved software/hardware with our hardware products may result in
injury, harm, or improper operating results
HA033172 Issue 3 11
Safety Notes EPack
Eurotherm shall not be held responsible for any damage, injury, losses or expenses
caused by inappropriate use of the product (EPack Lite), or failure to comply with
these instructions.
SELV
SELV is defined (in IEC60947-1) as an electrical circuit in which the voltage cannot
exceed 'ELV' under normal conditions or under single fault conditions, including earth
ground faults in other circuits. The definition of ELV is complex as it depends on
environment, signal frequency, etc. See IEC 61140 for further details.
The I/O connector (5-way) & auxiliary supply (24V ac/dc, 2-way) are compliant to the
SELV requirements.
The alarm relay output and the fuse holder contacts are compliant with the SELV
requirements; they can be connected to SELV or to voltage up to 230V (Rated
insulation voltage Ui: 230V).
12 HA033172 Issue 3
EPack Safety Notes
Hazardous Substances
This product conforms to European Restriction of Hazardous Substances (RoHS)
(using exemptions) and Registration, Evaluation, Authorisation and Restriction of
Chemicals (REACH) Legislation.
RoHS Exemptions used in this product involve the use of lead. China RoHS legislation
does not include exemptions and so lead is declared as present in the China RoHS
Declaration.
HA033172 Issue 3 13
Safety Notes EPack
Cybersecurity
Introduction
When utilizing EPack Lite controllers’ range in an industrial environment, it is
important to take ‘cybersecurity’ into consideration: in other words, the installation’s
design should aim to prevent unauthorized and malicious access. This includes
physical access (for instance via the front fascia).
WARNING
UNINTENDED EQUIPMENT OPERATION
• At commissioning, ensure cybersecurity robustness of the installation.
Failure to follow these instructions can result in death, serious injury or
equipment damage.
To minimize any potential loss of control when communicating across a network via a
third-party device (i.e. controller, PLC or configuration tool), ensure all system
hardware, software and network design are correctly configured and commissioned
for maximum cybersecurity robustness.
14 HA033172 Issue 3
EPack Introduction
Introduction
This document describes the installation, operation and configuration of a 2 phase
EPack Lite Power Controller.The unit includes the following analog and digital inputs
and outputs, fitted as standard:
• Two digital inputs (contact closure or voltage level), of which one of the digital
inputs can be configured as 10V user output.
The operator interface consists of a 1.44 inch square TFT display and four
pushbuttons for navigation and data selection.
The 2 phase EPack Lite comes in four versions with maximum load currents of: 32A,
63A, 100A and 125A.
The supply voltage for the units can be specified as either low voltage (24V ac/dc) or
line voltage (85 to 550V ac). The choice is made at time of order and cannot be
changed in the field.
W DANGER
HAZARD OF ELECTRICAL SHOCK, EXPLOSION OR ARC FLASH
• If on receipt, the unit or any part within is damaged, do not install but contact
your supplier.
Failure to follow these instructions will result in death or serious injury.
The units are despatched in a special pack, designed to give adequate protection
during transit. If any of the outer boxes show signs of damage, open them
immediately and examine the instrument. If there is evidence of damage, do not
operate the instrument and contact your local representative for instructions.
After the instrument has been removed from its packing, examine the packing to
ensure that all accessories and documentation have been removed. Then store the
packing for future transport requirements.
HA033172 Issue 3 15
Introduction EPack
Order Code
EPack Lite power controller is ordered using a short code for hardware and
chargeable software options code.
W DANGER
HAZARD OF FIRE
• Product current rating must be greater than or equal to the maximum current
of the load.
Failure to follow these instructions can result in death, serious injury or
equipment damage.
Calculate the maximum current of the load by taking account of load resistive
tolerance (tolerance and variation due to temperature) and voltage tolerance.
16 HA033172 Issue 3
EPack Introduction
HA033172 Issue 3 17
Introduction EPack
18 HA033172 Issue 3
EPack Introduction
HA033172 Issue 3 19
Installation EPack
Installation
Mechanical Installation
Mounting details
W DANGER
HAZARD OF ELECTRICAL SHOCK, EXPLOSION OR ARC FLASH
• Apply appropriate personal protective equipment (PPE) and follow safe
electrical work practices. See applicable national standards e.g. NFPA70E,
CSA Z462, BS 7671, NFC 18-510.
• Turn off all power supplying this equipment before working on equipment.
• Always use a properly rated voltage sensing device to confirm power is off.
• If on receipt, the unit or any part within is damaged, do not install but contact
your supplier.
• Do not disassemble, repair or modify the equipment. Contact your supplier for
repair.
W DANGER
HAZARD OF ELECTRICAL SHOCK, EXPLOSION OR ARC FLASH
• The unit must be installed in an enclosure or cabinet connected to the
protective earth ground.
Failure to follow these instructions will result in death or serious injury.
Notes:
1. CE: protective earth ground minimum size must be selected according to IEC
60364-5-54 table 54.2 or IEC61439-1 table 5 or applicable national standards.
2. U.L.: protective earth ground minimum size must be selected according to NEC
table 250.122 or NFPA79 table 8.2.2.3 or applicable national standards.
20 HA033172 Issue 3
EPack Installation
W DANGER
HAZARD OF ELECTRICAL SHOCK, EXPLOSION OR ARC FLASH
• Electrically conductive pollution must be excluded from the cabinet in which
the product is mounted.
Failure to follow these instructions will result in death or serious injury.
Notes:
1. The product has been designed for pollution degree 2 according to IEC60947-1
definition: Normally, only non-conductive pollution occurs. Occasionally, however,
a temporary conductivity caused by condensation may be expected.
2. Electrically conductive pollution must be excluded from the cabinet in which the
product is mounted. To ensure a suitable atmosphere in conditions of conductive
pollution, fit adequate air conditioning/filtering/cooling equipment to the air intake
of the cabinet, e.g. fitting fan-cooled cabinets with a fan failure detection device
or a thermal safety cut-out.
W DANGER
HAZARD OF ELECTRICAL SHOCK, EXPLOSION OR ARC FLASH
• Do not allow anything to fall through the case apertures and ingress the
product.
Failure to follow these instructions will result in death or serious injury.
Note: Conductive or non-conductive parts which ingress the product may reduce or
short circuit the insulation barriers inside the product.
W WARNING
UNINTENDED EQUIPMENT OPERATION
• Observe all electrostatic discharge precautions before handling the unit.
Failure to follow these instructions can result in death, serious injury or
equipment damage.
HA033172 Issue 3 21
Installation EPack
Notes:
1. The product is designed to be mounted vertically.
2. There must be no obstructions (above or below) which could reduce or hamper
airflow.
3. If more than one instance of the product is in the same cabinet, they must be
mounted in such a way that air from one unit is not drawn into another.
4. The gap between two EPack Lite devices must be at minimum 10mm.
5. The gap between EPack Lite and cable tray must be at least those defined in the
table in Mounted clearance dimensions.
W DANGER
HAZARD OF FIRE
• At commissioning ensure that under maximum load condition, the ambient
temperature of the product will not exceed the limit stated in that manual.
Failure to follow these instructions can result in death or serious injury.
Notes:
1. EPack Lite has been designed for a maximum temperature of 45°C (113°F) at
1000m (3281ft) altitude at nominal current & 40°C (104°F) at 2000m (6562ft)
altitude at nominal current.
2. At commissioning ensure that the ambient temperature inside the cabinet does
not exceed the limit under maximum load condition.
W DANGER
HAZARD OF FIRE
• Heat-sink must be cleaned regularly. Periodicity depends on the local
environment, but should not exceed 1 year.
Failure to follow these instructions can result in death or serious injury.
W CAUTION
HOT SURFACE RISK OF BURNS
• Do not allow flammable or heat-sensitive parts in the immediate vicinity of
heatsink.
Failure to follow these instructions can result in injury or equipment
damage.
22 HA033172 Issue 3
EPack Installation
Phase: 2 phase
between cable tray and 70 (2.76) 100 (3.94) 150 (5.91) 150 (5.91)
EPack Lite
between two cable trays 306 (12.05) 366 (14.41) 530 (20.87) 530 (20.87)
The units are designed for DIN Rail or bulkhead mounting using the mounting fixings
supplied.
Bulkhead Mounting
HA033172 Issue 3 23
Installation EPack
Figure 1 Fitting upper bulkhead mounting bracket (32A unit shown; 63A units similar)
24 HA033172 Issue 3
EPack Installation
HA033172 Issue 3 25
Installation EPack
A
A
160mm ±3
(6.29 inches)
125mm ±3
(4.92 inches)
D Slide up
D
Figure 3 DIN rail mounting (32A unit shown; 63A units similar)
26 HA033172 Issue 3
EPack Installation
Dimensions
View on
upper face
Voltage reference
connected to Line3
Front view
View on
right-hand side
Relay output
HA033172 Issue 3 27
Installation EPack
90.5 mm
(3.56 in)
(3.15 in)
(3.15 in)
80 mm
80 mm
View on upper
AC/DC
24V
face C
L
N/L2
202.1 mm (7.96 in)
Power mains line (2 phases)
46.7mm (1.84 in)
Voltage reference
connected to Line3
1/L1
Front view
321.23 mm (12.65 in)
View on
right-hand side
2/T1
Relay output
80 mm
04 01 02
28 HA033172 Issue 3
EPack Installation
View on
upper face
Voltage reference
Connected to Line3 Power mains line (2 Phases)
Wire guide
Power mains line
(2 places)
terminals screw head
Door
catch
Front View
Right-hand side
View
Door catch
Wire guide
Load power output
(2 places)
terminals screw head
View on lower
face
Wall Bracket
I/O connector
Relay output
HA033172 Issue 3 29
Installation EPack
View on
upper face
Voltage reference
connected Line3
Door catch
Front View
Right-hand side
View
Wall bracket
I/O connector
Relay output
30 HA033172 Issue 3
EPack Installation
Phase 2 phase
Dimensions mm (inches)
with Double DIN Rail 213.5 (8.405) 213.5 (8.405) N/A1 N/A1
with Wall back plate 229.5 (9.035) 229.5 (9.035) 291 (11.456) 291 (11.456)
Doors open 290 (11.417) 290 (11.417) 310 (12.204) 310 (12.204)
with Wall back plate 192 (7.559) 227 (8.937) 242 (9.527) 242 (9.527)
HA033172 Issue 3 31
Installation EPack
Electrical Installation
W DANGER
HAZARD OF ELECTRICAL SHOCK, EXPLOSION OR ARC FLASH
• Apply appropriate personal protective equipment (PPE) and follow safe
electrical work practices. See applicable national standards e.g. NFPA70E,
CSA Z462, BS 7671, NFC 18-510.
• Turn off all power supplying this equipment before working on equipment.
• Always use a properly rated voltage sensing device to confirm power is off.
• If on receipt, the unit or any part within is damaged, do not install but contact
your supplier.
• Do not disassemble, repair or modify the equipment. Contact your supplier for
repair.
W DANGER
HAZARD OF ELECTRICAL SHOCK, EXPLOSION OR ARC FLASH
• Do not allow anything to fall through the case apertures and ingress the
product.
Failure to follow these instructions will result in death or serious injury.
W DANGER
HAZARD OF ELECTRICAL SHOCK, EXPLOSION OR ARC FLASH
• Ensure all cables and wiring harness are secured using a relevant strain relief
mechanism.
Failure to follow these instructions will result in death or serious injury.
32 HA033172 Issue 3
EPack Installation
W WARNING
UNINTENDED EQUIPMENT OPERATION
• Observe all electrostatic discharge precautions before handling the unit.
• Signal and power voltage wiring must be kept separate from one another.
Where this is impractical, all wires must be rated to the power voltage &
shielded cables are recommended for signal wiring.
Connection Details
W DANGER
HAZARD OF ELECTRICAL SHOCK, EXPLOSION OR ARC FLASH
• Before any other connection is made, the protective earth ground terminal
must be connected to a protective conductor.
The earth connection must be made by using a lug terminal of size as given in
Table 1, “Connection Details”. The cables must be rated 90°C stranded copper only.
• CE: The protective earth ground cable minimum size must be selected according
to IEC 60364-5-54 table 54.2 or IEC61439-1 table 5 or applicable national
standards. The protective earth ground connection must be made to the unit with
a ring type crimp terminal, using the nut and shakeproof washer supplied (M6 for
16A to 125A units).
• U.L.: The protective earth ground cable cross sectional area should be selected
according to NEC table 250.122 or NFPA79 table 8.2.2.3 or applicable national
standards. The protective earth ground connection must be made to the unit with
a U.L. listed ring type crimp terminal, using the nut and shakeproof washer
supplied (M6 for 16A to 125A units).
HA033172 Issue 3 33
Installation EPack
W DANGER
HAZARD OF FIRE
• Power connections: The cables must be rated 90°C stranded copper only, the
cross section must be selected according to the branch circuit protection
rating.
Failure to follow these instructions will result in death or serious injury.
CE: Wire conductor cross sections must comply with IEC 60364-5-52 or applicable
national standards
U.L.: Wire conductor cross sections must comply with NEC Table 310.15(B)(16)
(formerly Table 310.16) taking account of table 310.15(B)(2) for the ampacity
correction factors or NFPA79 Table 12.5.1 taking account of Table 12.5.5(a) for the
ampacity correction factors or applicable national standards.
Table 1, “Connection Details” gives details of tightening torques for the various supply
power and signal wiring connections.
34 HA033172 Issue 3
EPack Installation
1. AWG (American Wire Gauge) for USA and Canada (according to cUL standard); section in mm² for IEC countries (according to IEC/EN
standard).
HA033172 Issue 3 35
Installation EPack
W DANGER
HAZARD OF ELECTRICAL SHOCK, EXPLOSION OR ARC FLASH
• Tighten all connections in conformance with the torque specifications. Periodic
inspections are required.
Failure to follow these instructions will result in death or serious injury.
• The protective earth ground connection may be too resistive. In case of short
circuit between live parts and heatsink, the heatsink may reach a dangerous
voltage.
W DANGER
HAZARD OF FIRE
• Connection of two conductors in the same terminal is not permitted.
Failure to follow these instructions will result in death or serious injury.
36 HA033172 Issue 3
EPack Installation
Auxiliary supply
The auxiliary supply connections (to operate the EPack unit) are terminated using a
2-way (24V ac/dc version) or 3-way (85 to 550Vac version) connector, located on the
upper side of the unit, as shown in Figure 8 and Figure 9.
W DANGER
HAZARD OF ELECTRICAL SHOCK, EXPLOSION OR ARC FLASH
• The “24V auxiliary supply” is an SELV circuit. The supply Voltage must be
derived from a SELV or PELV circuit.
Failure to follow these instructions will result in death or serious injury.
SELV is defined (in IEC60947-1) as an electrical circuit in which the voltage cannot
exceed 'ELV' under normal conditions or under single fault conditions, including earth
ground faults in other circuits.
Branch circuit protection is mandatory to protect the cable used to connect the
auxiliary supply.
HA033172 Issue 3 37
Installation EPack
W DANGER
HAZARD OF ELECTRICAL SHOCK, EXPLOSION OR ARC FLASH
• A High-speed fuse (supplemental fuses in addition to branch circuit protective
device) or a double protection fuse as listed in "Fusing" on page 85 is
mandatory for 85Vac to 550Vac auxiliary supply.
Failure to follow these instructions will result in death or serious injury.
This fuse is necessary to avoid the 85Vac to 550Vac auxiliary supply to emit flame or
molten element in case of breakdown of a component.
High-speed fuse (supplemental fuse) does not protect the wiring, they must be fitted
(in addition to branch circuit protective device).
Double protection fuse comprises a branch circuit fuse and a high-speed fuse.
Branch circuit protection fuses standards in USA/Canada differ from IEC standards
(e.g; Europe (CE)). Therefore:
• A fuse approved as branch circuit protection fuses in all countries where IEC
standards apply (e.g; Europe (CE)) is not a branch circuit in USA/Canada.
W DANGER
HAZARD OF ELECTRICAL SHOCK, EXPLOSION OR ARC FLASH
• If opening of any fuses or branch circuit protection device that supply the
85Vac to 550Vac auxiliary supply occurs, first check the wiring. If the wiring is
not damaged, do not replace the fuse and contact the manufacturer’s local
service center.
Failure to follow these instructions will result in death or serious injury.
If the wiring is not damaged a component inside the 85Vac to 550Vac auxiliary supply
is broken and product must go back to service center.
W DANGER
HAZARD OF ELECTRICAL SHOCK, EXPLOSION OR ARC FLASH
• The maximum voltage between any pole of the 85Vac to 550Vac auxiliary
supply and all other terminals must be lower than 550Vac.
Failure to follow these instructions will result in death or serious injury.
38 HA033172 Issue 3
EPack Installation
W DANGER
HAZARD OF FIRE
• Power connections: The cables must be rated 90°C stranded copper only, the
cross section must be selected according to the branch circuit protection
rating.
Failure to follow these instructions will result in death or serious injury.
CE: Wire conductor cross sections must comply with IEC 60364-5-52 or applicable
national standards
U.L.: Wire conductor cross sections must comply with NEC Table 310.15(B)(16)
(formerly Table 310.16) taking account of table 310.15(B)(2) for the ampacity
correction factors or NFPA79 Table 12.5.1 taking account of Table 12.5.5(a) for the
ampacity correction factors or applicable national standards.
W DANGER
HAZARD OF ELECTRICAL SHOCK, EXPLOSION OR ARC FLASH
• High speed fuses (supplemental fuses in addition to branch circuit protective
device), as listed in fusing sections, are mandatory to protect EPack Lite
against load short circuit.
• If opening of either the branch circuit protective device or the high-speed fuses
(supplemental fuses) occurs, the product must be examined by suitably
qualified personnel and replaced if damaged.
Failure to follow these instructions will result in death or serious injury.
HA033172 Issue 3 39
Installation EPack
W DANGER
HAZARD OF ELECTRICAL SHOCK, EXPLOSION OR ARC FLASH
• Respect electrical installation requirements to ensure optimum IP rating.
Failure to follow these instructions will result in death or serious injury.
If the conductor stripping lengths of the power cables are longer than the
requirements, then IP20 is compromised.
If the conductor stripping lengths of the power cables are shorter than the
requirements there is a potential risk of total loss of connection. Wires may slip out of
the terminals.
If the breakaway features are removed for cables with diameter lower than 9mm then
IP20 rating is compromised and the product is rated at IP10.
W DANGER
HAZARD OF FIRE
• The conductor stripping length must be as stated in Electrical Installation.
Failure to follow these instructions will result in death or serious injury.
If the conductor stripping lengths of the power cables are shorter than the
requirements there is a potential risk of partial loss of connection which may create
an overheat of the terminals
W DANGER
HAZARD OF ELECTRICAL SHOCK, EXPLOSION OR ARC FLASH
• Replace doors and plug-in terminals before turning on power to this equipment
Failure to follow these instructions will result in death or serious injury.
If the upper and/or lower access door are open, then IP20 rating is compromised and
the products are rated at IP10.
40 HA033172 Issue 3
EPack Installation
Figure 8 Supply power and Load connection details (16A to 63A units)
Power mains lines (2 phases) 63A units shown; 32A units similar
View on
Lift-up flaps upper face
Pull-down flap
Access to load power output
terminals screw heads
Voltage reference
connected to Line3
HA033172 Issue 3 41
Installation EPack
Pull-down flap
Access to power mains 125A unit shown; 100A & 80A units
line terminals screw head similar
View on
upper face
Lift-up flap
Figure 9 Supply power and Load connection details (80A to 125A units)
.
See Figure 9 for basic wiring details.
EPack rating Exposed conductor length Remove terminal housing breakaway part? Cable diameter maximum
(Amps) mm (inch) mm (inch) cable diameter mm (inch)
16A to 63A 20 - 23 (0.79 - 0.91) Yes, for cables greater than 9 (0.35) 10.5 (0.41)
80A to 125A 20 - 23 (0.79 - 0.91) Yes, for cables greater than 9 (0.35) 17.5 (0.69)
42 HA033172 Issue 3
EPack Installation
Load Configurations
Delta
Closed Delta
High speed thyristor Phase 1
protection fuses
Phase 2
Phase 3
1/L1 2/T1
Phase 1 Isolating
devices
EPack auxiliary
Fuse
supply (low voltage Fuse
V 1/L1 3/L2
V3 option shown)
Vline Vline 3
3
Lo
ad
ad
Lo
Voltage reference
1
connected
to Line3
Load 2
3/L2 4/T2 2/T1 4/T2
Phase 2
Vline 2 V2
Phase 3
HA033172 Issue 3 43
Installation EPack
Star
Isolating
Phase 1 1/L1 2/T1 devices
Fuse
EPack auxiliary
supply
Load 1
(low voltage Fuse
option shown) 1/L1 3/L2
Vline V
V3
Vline 3
Lo Voltage
ad
2
reference
ad
3
Lo
connected to
Phase 2 3/L2 4/T2
Line3 2/T1 4/T2
V2
Vline 2
Phase 3
44 HA033172 Issue 3
EPack Installation
Signal wiring
Figure 12 shows the connector location, on the underside of the unit, for the digital
and analog inputs, and for the internal relay output.
Firing Enable
For the power module thyristors to operate, the Firing Enable must be enabled.
In the default configuration Digital input 1 is used to enable the firing and is
configured in contact closure type. Therefore, Firing Enable is achieved by shorting
pins 0V and DI1 of the I/O connector located on the underside of the unit (Digital
input 1).
QuickCode menu allows the user to select Digital input 2 to Enable Firing. Digital
input 2 is configured in contact closure type, therefore, Firing Enable is achieved by
shorting pins 0V and DI2 of the I/O connector located on the underside of the unit
(Digital input 2).
Alarm Acknowledge
In the default configuration, shorting pins 0V and DI2 of the I/O connector located on
the underside of the unit (Digital input 2) acknowledges alarms. This can be done
also using DI1.
DI can be configured as a voltage input (if required), and in this case it requires a high
signal to be applied to DI with the relevant zero voltage connected to 0V.
Main Setpoint
In the default configuration, the analog input sets the main setpoint.
Relay Output
The relay is normally energized (Common and Normally Open pins shorted), and is
de-energized (Common and Normally Closed pins shorted) when active. In the
default configuration, the relay output is operated by the Fault detect ‘Custom Alarm’
becoming active.
In configuration mode, it is also possible to configure the relay using the Alarm Relay
menu in the Operator Interface ().
HA033172 Issue 3 45
Installation EPack
a. It is not possible to detect a thyristor short circuit when the unit is delivering
100% output power.
46 HA033172 Issue 3
EPack Installation
1 (0 V)
Digital inputs
(Pins 3, 4, and 5) Relay output
2 (+) View on
lower face 02
Contact input
3 (0 V)
800Ω to ∞ = open
0Ω to 450Ω = closed
01
4 (DI1)
451Ω to 799Ω = undefined
04
5 (DI2)
Voltage level inputs Pins:
11V to 30V, with >6mA to <30mA = high 02 = Normally connected
-3V to 5V, with >2mA to <30mA= low 01 = Common
or 04 = Normally open
5V to 11V with <2mA Switching characteristics
(resistive loads):
Digital Output (DI2) • Vmax: 264V RMS
User configurable output • Vmin: 5V dc
10.2v, with max. 10mA • Imax: 2A RMS
• Imax: 10mA
1. Diagram shows DI1 as a contact input and DI2 as a voltage level input.
2. DI1 can be configured as contact inputs or voltage inputs.
3. DI2 can be configured as contact inputs or voltage inputs or 10.2V output
(with max. 10mA).
4. Analog input type (Volts or mA) is selected in I/O Analog IP configuration.
When a mA range is selected, a suitable shunt resistor is automatically
connected into circuit. It is thus unnecessary for the user to fit external
components.
W DANGER
HAZARD OF ELECTRICAL SHOCK, EXPLOSION OR ARC FLASH
• Do not exceed the device's ratings
• The I/O Input & Output, the Communications ports are SELV circuit. They
must be connected to SELV or PELV circuit.
• The relay output and the fuse holders contacts are compliant to the SELV
requirements; they can be connected to SELV, PELV circuit or to voltage up to
230V (maximum value of rated operational voltage to earth:230V).
Failure to follow these instructions will result in death or serious injury.
SELV is defined (in IEC60947-1) as an electrical circuit in which the voltage cannot
exceed 'ELV' under normal conditions or under single fault conditions, including earth
ground faults in other circuits.
HA033172 Issue 3 47
Installation EPack
• The relay output and the fuse holders contacts are compliant to the SELV
requirements; they can be connected to SELV, PELV circuit or to voltage up to
230V (maximum value of rated operational voltage to earth:230V).
Failure to follow these instructions will result in death or serious injury.
SELV is defined (in IEC60947-1) as an electrical circuit in which the voltage cannot
exceed 'ELV' under normal conditions or under single fault conditions, including earth
ground faults in other circuits.
If fuse ordering code HSM has been selected, the fuses holder is delivered with a
contact kit which provides indication if the fuse is blown or missing. This is shown
locally on the fuseholder by a red handle which also activates microcontacts. These
contacts may be wired to a digital input on the EPack as shown in the following
diagrams.
48 HA033172 Issue 3
EPack Installation
For contact kit reference according to product rating see Table 3 or Table 4.
Contact kit Mersen Y227928A, for fuse size 14x51 or Contact kit Mersen G227959A
for fuse size 22x58.
• These contacts are compatible with Digital inputs configured in contact closure
mode.
Recommended wiring:
NC
Fuse holder
contact
• These contacts are not compatible with Digital inputs configured in contact
closure mode.
• These contacts are compatible with Digital inputs configured in Voltage inputs
with external dc power supply and load 100 mA dc minimum.
NC
Fuse holder
contact
HA033172 Issue 3 49
Installation EPack
50 HA033172 Issue 3
EPack Operator Interface
Operator Interface
Located at the front of the Driver Module, the operator interface consists of a square
display, and four pushbutton switches.
Display
The display is divided vertically into three areas, which for the purposes of this
manual are called the status area at the top, the data display, in the center, and the
soft keys at the bottom. This display, together with the four pushbuttons allows full
operation and configuration of the unit.
Status area
Display area
Softkey icons
Status area
This area at the top of the screen contains text descriptive of the current operation,
and a number of icons as follows
Configuration key. Displayed when the unit is in configuration mode.
Alarm symbol. Indicates that one or more alarms is active.
HA033172 Issue 3 51
Operator Interface EPack
Softkey icons
A number of icons can appear at the bottom of the display, and each icon represents
the action of the pushbutton immediately below it.
Menu. This appears in the bottom left corner, and operation of the
Return pushbutton causes the top level menu to appear.
Return. This red cross icon appears in the bottom left corner, and
operation of the Return pushbutton causes any configuration changes
on the current page to be ‘undone’ or, if none, causes the display to ‘go
up’ one level.
Enter. This green tick appears in the bottom right corner, and operation
of the Enter pushbutton causes any configuration change(s) on the
display page to be confirmed.
52 HA033172 Issue 3
EPack Operator Interface
Pushbuttons
The functions of the four pushbuttons below the display depend on what is displayed
in the softkey area. The leftmost pushbutton (Return) is associated with the leftmost
soft key, the down arrow pushbutton is associated with the next soft key and so on. In
the example above, the ‘Return’ key is used both to enter the Menu, and to return
from it to the initial display.
Pushbutton functions
Return Returns to previous menu (while menus are displayed), cancels
editing (during parameter editing), and performs screen cycling
(during operator mode).
Scroll down/up Allows the user to scroll through the available menu items or
values.
Enter Goes to next menu item. In parameter edit mode, this button
confirms the changes.
Where multiple changes have to be made (as in editing an IP address for example),
the Enter pushbutton acts as a right cursor key, moving from the field just edited to
the next field. (The Return pushbutton moves the cursor left). Once all fields have
been edited, the Enter pushbutton is used a final time to confirm the choice.
HA033172 Issue 3 53
Operator Interface EPack
Instrument events
Conf Entry The instrument has been placed in configuration mode
(cogwheel symbol).
Conf Exit The instrument has been taken out of configuration mode (no
icon).
GlobalAck A global acknowledgement of all latched alarms has been
performed.
Quick Code Entry The Quick Code menu is active (cogwheel icon + ‘QCode’ in
display area).
The following alarms all cause a red bell icon to appear in the top right hand corner of
the screen.
Indication alarms
LoadOverI An over current alarm has become active in one or more Network
blocks.
System alarms
ChopOff The ‘Chop-off’ alarm has been detected.
FuseBlown There is no internal fuse, but it is possible to use DI2 as a
‘fuse-blown’ input wired to the alarm block in iTools.
MainsFreq Mains Frequency is outside the acceptable range.
Missmains Supply power is missing.
NetwDip The ‘network dip’ alarm has been detected.
Thyr SC Thyristor short circuit. It is not possible to detect a thyristor short
circuit when the unit is delivering 100% output power.
Process alarms
ClosedLp The Control block ‘Closed Loop’ alarm has been detected.
Ana_In Over C Over current in shunt. If this alarm is detected, firing is stopped
by default and Analog Input type is automatically switched to
0-10V mode to avoid damage.
Under Volt Line under voltage
Over Volt Line over voltage (configurable between 2 and 10% of nominal
voltage)
PLF The ‘Partial Load Failure’ alarm has been detected.
TLF The ‘Total Load failure’ alarm has been detected.
54 HA033172 Issue 3
EPack Quickcode
Quickcode
At first switch-on, the EPack unit enters the ‘QuickCode’ menu which allows the user
to configure the major parameters without having to enter the full configuration menu
structure of the unit. Figure 14 shows an overview of a typical QuickCode menu. The
actual displayed menu items will vary according to the number of software features
purchased. When ‘Finish’ is selected to ‘Yes’, the instrument cold starts after
confirmation (Enter key); when set to ‘Cancel’ the instrument discards any changes
and restarts with the previous configuration.
HA033172 Issue 3 55
Quickcode EPack
56 HA033172 Issue 3
EPack Quickcode
Logic
Power switches on, two or three zero crossings of the supply voltage after the logic
input switches on. Power switches off, two or three zero crossings of current after the
logic input switches off. For resistive loads, voltage and current cross zero
simultaneously. With inductive loads, a phase difference exists between the voltage
and current, meaning that they cross zero at different times. The size of the phase
difference increases with increasing inductance.
Tcyc
HA033172 Issue 3 57
Quickcode EPack
Power Power
applied applied
Power applied Power applied
Min off Min on Min off Min on
Ton Toff Ton Ton Toff Ton
Toff = 1/2 Min on = 66.7% duty cycle Toff = Min on = 50% duty cycle
Power applied Power applied
Min On = Min Off = 2 Min on
for these examples Ton Toff Ton
58 HA033172 Issue 3
EPack Quickcode
Feedback type
All feedback types (except ‘Open Loop’) are based on real-time measurement of
electrical parameters that are normalized to their equivalent Nominal values.
V2 Feedback is directly proportional to the square of the RMS
voltage measured across the load.
I2 Feedback is directly proportional to the square of the RMS
current through the load. For two- or three-phase systems,
feedback is proportional to the average of the squares of
the individual RMS load currents.
Open loop No measurement feedback. The thyristor firing angle in
Phase angle mode, or the duty cycle in burst-firing mode,
are proportional to the setpoint.
HA033172 Issue 3 59
Quickcode EPack
60 HA033172 Issue 3
EPack Configuration from the Front Panel
EPackLite2PH
EPackLite2PH
VN.NN = software
75.4 revision level
HA033172 Issue 3 61
Configuration from the Front Panel EPack
Menu Pages
Operating the return key opens the first page of the menu, the content of which
depends on the current access level and on the number of options enabled.
62 HA033172 Issue 3
EPack Configuration from the Front Panel
Meas menu
This menu allows the user to view a number of measured values in real time.
Meas Meas
Meas
Meas
Supply voltage
Frequency
Vline frequency
Frequency
0.00
V
I
Meas Meas
V VN
Displays an RMS
measurement of the
V2 selected load voltage
V3 (load 1, 2, 3, or the
V Average 0.0 average of all three)
Meas
Meas Displays an RMS
I IN measurement of the
selected load current
I2 (load 1, 2, 3, or the
I3 0.0 average of all three)
I Average
0.0
Meas
Energy
0
1 Wh
Meas Meas
Energy Z
Z Z2
Load impedance
Z3
0
HA033172 Issue 3 63
Configuration from the Front Panel EPack
Adjust menu
This menu allows a number of network and firing output parameters to be set up, as
well as Analog input type.
Enter nominal
Adjust values Adjust
Vline Load
Nominal Adjust Adjust
Coupling Select the rele-
vant Load
I NominalPV configuration
230 Nominal 3S
16.0 52900
Adjust
Adjust
Adjust
Firing Mode
Lgc Max Cyc Lgc Max
SP Op Access. Cycle Time Set the
Cycle
Backlight Di. 750 Time
Adjust
Adjust
Ana_in type SP
Safety Ramp
Op Access
Soft Start Select
Soft Stop No Yes or No
Menu
Adjust Adjust
Backlight
PLF Adjust R
Dimming
PLF Adjuste
PLF Sensitiv. Select
Yes Yes or No
Adjust
Ana_In
Adjust
type
PLF 0–10V
Select
analogue
Sensitivity input type
2
Adjust
Safety
Select Adjust Ramp Select
Sensitivity val- Ramp Rate
ue PLF Adjust Adjust Adjust 16
Adjusted Soft
PLF Soft
Adjust Req Stop Start
No
No Off Off
Select Select
Yes or No number of
Select Select number of cycles
Yes or No cycles
64 HA033172 Issue 3
EPack Configuration from the Front Panel
Vline Nominal Line voltage nominal value (Line to line for all listed config-
urations), see Load Configurations (page 43).
I Nominal Nominal current supplied to the load.
NominalPV Nominal Process Variable. Defines the nominal value for
each control type. For example, for Vsq control, you must
set NominalPV to the nominal value you expect for Vsq—
typically this could be VloadNominal * VloadNominal.
Load Coupling Allows you to specify how the load is configured on your in-
stallation. Select one of the following; 3D (closed Delta), or
3S (Star without Neutral). See Load Configurations
(page 43) for more details.
Lgc Max Cyc Max cycle time for Logic mode. This is set in mains
periods.This is the equivalent to the modulation period and
it is used to compute Network electrical quantities when
there is no modulation shift. It is only available in Logic
Mode.
Firing Mode Firing Mode allows the firing mode to be selected as Burst
Var, Burst Fix, or Logic.
SP Op Access Setpoint Operator Access: Allows the user setpoint access
via the front panel, in operator configuration when enabled.
To enable set to Yes. (The default setting is Yes).
Backlight Di. Backlight Dimming: By default, the backlight on the
EPack’s display dims automatically to save power. Set this
parameter to No if you want the backlight to always remain
on. If set to Yes, the backlight dims 30 seconds after you
last operate the buttons on the front panel.
Ana_in type Select the Analog Input type as 0 to 10V, 1 to 5 V, 2 to 10V,
0 to 5V, 0 to 20mA,4 to 20mA.
‘Safety Ramp’ Displays the startup ramp duration, in supply voltage
cycles (0 to 255), to be applied at startup. The ramp is
either a phase angle ramp from zero to the requested
target phase angle or, for Burst Firing, from 0 to 100%.
‘Safety Ramp’ is not applicable to Half cycle Mode.
Soft Start For Burst Firing only, this is the soft start duration, in supply
voltage cycles, applying a phase angle ramp at the
beginning of each ON period.
Soft Stop In Burst Firing, the soft stop duration, in supply voltage
cycles, applying a phase angle ramp at the end of each ON
period.
Delay Triggering Appears only if Mode is Burst, Soft Start is Off, and Load
Type is TxFormer. Delayed Trigger specifies the triggering
delay, in phase angle, when delivering power into a
transformer load. Used to minimize inrush current, the
value is configurable between 0 and 90 degrees, inclusive.
PLF Adjust R Partial Load Failure Adjustment Request: When the
process has achieved a steady state condition the
operator must set the PLFAdjustReq. This makes a load
impedance measurement to be used as a reference for
detecting a partial load failure. If the load impedance
measurement is successful ‘PLFAdjusted’ is set. The
measurement cannot be made if the load voltage (V) is
below 30% of VNominal or if the current (I) is below 30%
of INominal. The input is edge sensitive, so if the request
is made from external wiring, and the input remains
permanently at a high level, only the first 0 to 1 edge is
taken into account.
PLF Adjusted Partial Load Failure Adjusted: A successful load imped-
ance measurement has been made (see PLF Adjust R
above).
HA033172 Issue 3 65
Configuration from the Front Panel EPack
Examples
Output
voltage
Output
voltage Line
Line supply
Delayed trigger angle
supply
Resistive load Inductive load
Figure 21 Safety ramp (burst firing) examples
Soft start = 2
Output
voltage
Line
supply
Load voltage
Load current
66 HA033172 Issue 3
EPack Configuration from the Front Panel
PLF menu
The PLF (Partial Load Failure) menu is only available in Engineer mode.
PLF
PLF Adjust R
PLF Adjuste.
PLF Sensitiv. PLF
PLF
Adjusted
No Read-only
PLF
PLF
Read-only
Sensitivity
HA033172 Issue 3 67
Configuration from the Front Panel EPack
Info menu
This display gives read only information about the unit.
Info
Serial
Num
1234567890
Info
SW
Version
Info E N.NN
Serial Num
Serial Num
SW version
SW version
Passcode1
Info
Clone Code
Passcode1 Passcode1
12345
Clone Code
X3XX00
X0101X
68 HA033172 Issue 3
EPack Configuration from the Front Panel
Alarms menu
Allows the user to view Global acknowledgement enable status, and issues with
calibration (if any). Any active alarms appear, and details can be found by highlighting
the relevant alarm and using the Enter pushbutton.
Alarms
Alarm
Yes
ACK?
Alarms
Calib
Error
Alarms
1
Alarm Ack
Calib Error Use Enter button to
Miss Mains acknowledge alarms
Alarms
Thyr SC
Miss Mains
P1Latched
ACK?
HA033172 Issue 3 69
Configuration from the Front Panel EPack
To disable or re-enable an alarm, simply scroll through the list and select the alarm
you want, then use the arrow keys to toggle its status between Disable and Enable as
required.
Alm Disab Use the arrow keys to scroll through the list of
Miss Mains alarms, and press the Enter key when the green
cursor is next to the alarm you want.
Thyr SC
Volt Dips
Freq Fault
Alm Disab
Chop Off
Under Volt
Over Volt
Alm Disab
TLF
Alarm
name
Alm Disab Disable
PLF
PLU
Over I Use the arrow keys to toggle
Ana_In Over. between Disable and Enable for the
selected alarm.
You do not need to press the
Enter key for this to take effect.
(Pressing the Enter key here moves
Alm Disab to the next alarm
in the list.)
Closed Loop
Extern In
70 HA033172 Issue 3
EPack Configuration from the Front Panel
To select the latching type, simply scroll through the list and select the alarm you
want, then use the arrow keys to toggle its status between Latch and NoLatch as
required.
Alm Latch
Use the arrow keys to scroll through the list of
Miss Mains alarms, and press the Enter key when the green
cursor is next to the alarm you want.
Thyr SC
Volt Dips
Freq Fault
Alm Latch
Chop Off
Under Volt
Over Volt Alm Latch
TLF
Alarm
name
Alm Latch
Latch
PLF
PLU
Over I Use the arrow keys to toggle
Ana_In Over. between Latch and NoLatch for the
selected alarm.
You do not need to press the
Enter key for this to take effect.
(Pressing the Enter key here moves
Alm Latch to the next alarm
in the list.)
Closed Loop
Extern In
HA033172 Issue 3 71
Configuration from the Front Panel EPack
To change whether an alarm causes the EPack Lite to stop firing, simply scroll
through the list and select the alarm you want, then use the arrow keys to toggle its
status between Stop and NoStop as required.
Alm Stop Use the arrow keys to scroll through the list of
alarms, and press the Enter key when the green
Miss Mains cursor is next to the alarm you want.
Thyr SC
Volt Dips
Freq Fault
Alm Stop
Chop Off
Under Volt
Over Volt
Alm Stop
TLF
Alarm
name
Alm Stop Stop
PLF
PLU
Over I Use the arrow keys to toggle
between Stop and NoStop for the
Ana_In Over. selected alarm.
You do not need to press the
Enter key for this to take effect.
(Pressing the Enter key here moves
to the next alarm
Alm Stop
in the list.)
Closed Loop
Extern In
72 HA033172 Issue 3
EPack Configuration from the Front Panel
Alm Relay
Miss Mains
Thyr SC
Volt Dips
Freq Fault
Alm Relay
Chop Off
Under Volt
Over Volt
Alm Relay
TLF
Alarm
name
Alm Relay Yes
PLF
PLU
Over I
For each alarm selected choose
Ana_In Over. ‘Yes’ if you want the watchdog relay
to operate (de-energise) when the
alarm is raised.
Otherwise, select ‘No’.
Alm Relay
Closed Loop
Extern In
HA033172 Issue 3 73
Configuration from the Front Panel EPack
DI Stat menu
The DI Stat menu displays the status of the EPack Lite’s two digital inputs, DI1 and
DI2.
‘0’ means a low level logic signal is being received at the input, ‘1’ means a high level
logic signal is being received at the input.
DI Stat
DI1 DI2
0 1
74 HA033172 Issue 3
EPack Configuration from the Front Panel
Settings menu
The Settings menu is only available in Engineer mode. This menu is read-only, and
lets you view the values of the parameters described below.
Settings
Vline
Nominal Settings
I
230
Nominal
16.0
Settings
Vline Nomin. Settings
I Nominal
Load
Load Coupling
Coupling
Firing Mode
3S
Settings
Firing
Mode
Settings BurstVar
Ana_in
type
2–10V
HA033172 Issue 3 75
Configuration from the Front Panel EPack
Access menu
Allows access to the Operator, Engineer, Configuration, and Quick Code menus and
allows passwords to be set up.
Edit Edit
Goto Pass
Code
Select access Select correct
Config level required 3 pass code for
selected access
level
Edit
Config
Code
Edit Config
Menu 3 level code
Goto
Config Code
Engineer Co.
Quick Code Edit
Edit Engineer
Quick Code
Code Edit Engineer
Edit
level code
4 Quick code 2
access code
76 HA033172 Issue 3
EPack Configuration from the Front Panel
HA033172 Issue 3 77
Alarms EPack
Alarms
W DANGER
HAZARD OF ELECTRICAL SHOCK, EXPLOSION OR ARC FLASH
• Use appropriate safety interlocks where personnel and/or equipment hazards
exist.
Failure to follow these instructions will result in death or serious injury.
EPack Lite alarms protect thyristors and loads against abnormal operation, and
provide the user with valuable information regarding the type of fault.
• The first one is related to a detected failure on displays microcontroller board and
EPack Lite displays ‘CONFIG ERROR’. For this kind of problem it is
recommended to send the unit back to a repair center. EPack Lite also displays a
code in hexadecimal for a technician. This code is also available in decimal
through iTools in Global Status 0.
• The second one reports issues related to a hardware problem detected by the
microcontroller. Issues can be located on the different boards. In this situation
EPack Lite displays ‘HW Problem’. For this kind of problem it is recommended to
send the unit back to a repair center or contact your local representative. EPack
Lite also displays a code in hexadecimal for a technician. This code is also
available in decimal through iTools in Global Status 1.
• The third one is more related to configuration data set on production line, or
during upgrade. In this case EPack Lite displays ‘INVALID DATA’. For this kind of
problem it is recommended to send the unit back to a repair center. EPack Lite
also displays a code in hexadecimal for a technician. This code is also available
in decimal through iTools in Global Status 2.
78 HA033172 Issue 3
EPack Alarms
System Alarms
System alarms are considered to be ‘Major Events’ which help prevent proper
operation of the system, and the unit is placed in standby mode.
Missing mains
Supply power is missing.
Over temperature
Reserved for future development.
Network dips
This detects a reduction in supply voltage, and if this reduction exceeds a
configurable measured value (VdipsThreshold), firing will be inhibited until the supply
voltage returns to a suitable value. VdipsThreshold represents a percentage change
in supply voltage between successive half cycles and is set to 20% of Vline Nominal.
HA033172 Issue 3 79
Alarms EPack
Process Alarms
Process Alarms are related to the application and can be configured either to stop the
unit firing (Standby Mode) or to allow operation to continue. Process alarms can also
be configured to be latched and if so, they have to be acknowledged before the alarm
is considered to be non-active. Alarms cannot be acknowledged until the trigger
source has returned to a non-active state.
Alarm input
The alarm input associated with the alarm block is active.
80 HA033172 Issue 3
EPack Alarms
Non-inductive loads, for example resistance furnaces, resistive loads with low
temperature coefficient or short wave infrared loads can be monitored using this
function. For other load types, for example AC51 slightly inductive loads or AC56a
primary of transformer, please consult Eurotherm.
The sensitivity of the partial load failure measurement can be set to any value
between 2 to 6 inclusive, where an entry of 2, for example, means that one half of the
elements (or more) must be open circuit in order to trigger the alarm; an entry of 3
means that one third of the elements (or more) must be open circuit in order to trigger
the alarm, and so on down to one sixth. All elements must have identical
characteristics and identical impedance values and must be connected in parallel).
Indication Alarms
Indication Alarms signal events for operator action if required. Indication alarms
cannot be configured to stop power module firing, but they may be latched if required,
and if latched, they must be acknowledged for the Signalling Status to return to the
normal (non-alarm) state.
Load Over-Current
Indicates when a configurable RMS load current threshold (OverIthreshold) is
reached or exceeded. This threshold is set to 120% of he nominal current.
HA033172 Issue 3 81
Alarms EPack
82 HA033172 Issue 3
EPack Maintenance
Maintenance
Precautions
W DANGER
HAZARD OF ELECTRICAL SHOCK, EXPLOSION OR ARC FLASH
• Apply appropriate personal protective equipment (PPE) and follow safe
electrical work practices. See applicable national standards e.g. NFPA70E,
CSA Z462, BS 7671, NFC 18-510.
• The product is not suitable for isolation applications, within the meaning of
EN60947-1 Turn off all power supplying this equipment before working on the
loads of the equipment.
• Turn off all power supplying this equipment before working on equipment.
• Always use a properly rated voltage sensing device to confirm power is off.
• Do not disassemble, repair or modify the equipment. Contact your supplier for
repair.
The safety and EMC of any system incorporating this product is the responsibility of
the assembler/installer of the system.
Failure to use approved software/hardware with our hardware products may result in
injury, harm, or improper operating results.
Eurotherm shall not be held responsible for any damage, injury, losses or expenses
caused by inappropriate use of the product (EPack Lite), or failure to comply with
these instructions.
HA033172 Issue 3 83
Maintenance EPack
Under some circumstances, the EPack Lite heatsink temperature may rise by more
than 50°C and it can take up to 15 minutes to cool after the product is shut down.
W CAUTION
HOT SURFACE RISK OF BURNS
• Allow heatsink to cool before servicing.
Preventive Maintenance
W DANGER
HAZARD OF ELECTRICAL SHOCK, EXPLOSION OR ARC FLASH
• Tighten all connections in conformance with the torque specifications. Periodic
inspections are required.
Failure to follow these instructions will result in death or serious injury.
• The protective earth ground connection may be too resistive. In case of short
circuit between live parts and heatsink, the heatsink may reach a dangerous
voltage.
W DANGER
HAZARD OF ELECTRICAL SHOCK, EXPLOSION OR ARC FLASH
• Do not allow anything to fall through the case apertures and ingress the
product.
Failure to follow these instructions will result in death or serious injury.
Conductive or non-conductive parts which ingress product may reduce or short the
insulations barriers inside the product.
W DANGER
HAZARD OF FIRE
• Heat-sink must be cleaned regularly. Periodicity depends on the local
environment, but should not exceed 1 year.
Failure to follow these instructions will result in death or serious injury.
84 HA033172 Issue 3
EPack Maintenance
Fusing
W DANGER
HAZARD OF FIRE
• This product does not contain any branch-circuit protection, the installer must
add branch-circuit protection upstream of the unit.
W DANGER
HAZARD OF ELECTRICAL SHOCK, EXPLOSION OR ARC FLASH
• High speed fuses (supplemental fuses in addition to branch circuit protective
device), as listed in fusing sections, are mandatory to protect EPack Lite
against load short circuit.
• If opening of either the branch circuit protective device or the high-speed fuses
(supplemental fuses) occurs, the product must be examined by suitably
qualified personnel and replaced if damaged.
Failure to follow these instructions will result in death or serious injury.
The power circuit must be protected by a supplementary fuse, which should be used
in conjunction with suitable fuse holders (and contact kits, if required) as shown in
Table 3 or Table 4.
Note: With a supplementary fuse (high speed fuse), EPack is suitable for use on a
circuit capable of delivering not more than 100kA RMS symmetrical amperes, 500
Volts Maximum (coordination Type 2)
HA033172 Issue 3 85
Maintenance EPack
Table 3: Details of high-speed fuses (WITHOUT microswitch) and fuse holders required for
EPack with order code HSP
Mersen
Mersen
30A US102
FR10GR69V30
≤25A or 10×38 or
Mersen
32A Mersen
FR10GR69V32
CUS102
Mersen
FR14GR69V40
Mersen
32A 40A
FR14GC69V40
Cooper-Bussmann Mersen
FWP-40A14F 14×51
US142
Mersen 2 1 0
FR14UC69V50
40A 50A
Cooper-Bussmann
FWP-50A14F
Mersen
50A 63A
FR22UD69V63
Mersen Mersen
22x58
FR22GC69V80 US222
63A 80A
Cooper Bussmann
FWP-80A22F
86 HA033172 Issue 3
EPack Maintenance
Table 4: Details of high-speed fuses (WITH microswitch) and fuse holders required for
EPack with order code HSM
Mersen
FR14GR69V32T
Mersen
≤25A 32A
FR14GC69V32T
Cooper-Bussmann
FWP-32A14FI
Mersen
FR14GR69V40T Mersen Mersen
14×51
Mersen US142 Y227928A
32A 40A
FR14GC69V40T
Cooper-Bussmann
FWP-40A14FI
Mersen 2 1 2
FR14UD69V50T
40A 50A
Cooper-Bussmann
FWP-50A14FI
Mersen
50A 63A
FR22UD69V63T
W DANGER
HAZARD OF ELECTRICAL SHOCK, EXPLOSION OR ARC FLASH
• Tighten all connections in conformance with the torque specifications. Periodic
inspections are required.
Failure to follow these instructions will result in death or serious injury.
Unless otherwise mentioned on the side of the fuse holders, torque fuse holders
terminals at 2Nm.
Wires are not properly retained in terminals with insufficient torque. Insufficient torque
may increase the contact resistance, causing the power terminals to overheat.
HA033172 Issue 3 87
Maintenance EPack
56.5 mm
2.22 in
35 mm 20 mm
1.378 in 0.78 in
17.5 mm
.689 in
45 mm
1.8 in
76.5 mm
3.01 in
79.3 mm
3.12 in
4.6 mm
43 mm 0.18 in
1.69 in
76.9 mm
3.03 in
88 HA033172 Issue 3
EPack Maintenance
94mm
3.7 in
70 mm
2.8 in
50.5 mm 53 mm
1.99 in 2.1 in
107 mm 4.21 in
45 mm
1.8 in
50.5 mm 3.8 mm
1.99 in 0.15 in
52 mm
26.5 mm
2.0 in
1.04 in
76.5 mm
3.0 in
HA033172 Issue 3 89
Maintenance EPack
96.5 mm 3.80 in
70 mm
2.8 in
50.5 mm
1.99 in 70mm 2.76 in
126.5mm 4.98 in
45 mm
1.77 in
1 mm
50.5 mm
0.03 in
1.99 in
35 mm
1.38 in
76.5 mm 3.01 in
Figure 37 Fuse holder dimensions: US222 (22x58mm)
80mm 3.2 in
40mm 1.6in
5.25mm
117mm 4.61in
0.21in 29.5mm
1.16in 57mm 2.2in
4mm
8mm
0.16in
0.3in
63mm 2.48in
80.5mm
37.5mm 1.48in
3.12 in
46mm 1.81in
32mm
1.23in
45mm 1.77in
17.5mm
0.689in
55 7in
35mm 1.38in
130mm 5.12in
2.1
mm
75mm 2.95in
66mm 2.60in
118mm 4.65in
146mm 5.75in
25.5mm
1.00in
6mm
0.24in
6mm
0.24in
90 HA033172 Issue 3
EPack Maintenance
Branch circuit protection is mandatory to protect the cable used to connect the
auxiliary supply.
W DANGER
HAZARD OF ELECTRICAL SHOCK, EXPLOSION OR ARC FLASH
• A High-speed fuse (supplemental fuses in addition to branch circuit protective
device) or a double protection fuse as listed in fusing sections is mandatory for
85Vac to 550Vac auxiliary supply.
Failure to follow these instructions will result in death or serious injury.
This fuse is necessary to avoid the 85Vac to 550Vac auxiliary supply to emit flame or
molten element in case of breakdown of a component.
High-speed fuse (supplemental fuse) does not protect the wiring they must be fitted
in addition to branch circuit protective device).
Double protection fuse combines a branch circuit fuse and a high-speed fuse. Double
protection fuse must be selected according to applicable national standards. Branch
circuit protection fuses Standard in USA/Canada differ from IEC standards (e.g;
Europe (CE)). Therefore:
• A fuse approved as branch circuit protection fuses in all countries where IEC
standards apply (e.g; Europe (CE)) is not a branch circuit in USA/Canada.
HA033172 Issue 3 91
Maintenance EPack
W DANGER
HAZARD OF ELECTRICAL SHOCK, EXPLOSION OR ARC FLASH
• If opening of any fuses or branch circuit protection device that supply the
85Vac to 550Vac auxiliary supply occurs, first check the wiring. If the wiring is
not damaged, do not replace the fuse and contact the manufacturer's local
service center.
Failure to follow these instructions will result in death or serious injury.
If the wiring is not damaged a component inside the 85Vac to 550Vac auxiliary supply
is broken and product must go back to service center.
92 HA033172 Issue 3
EPack Maintenance
Instrument upgrade
Contact your local representative.
Software upgrade
Software upgrade can be carried out by following the section below.
HA033172 Issue 3 93
Maintenance EPack
94 HA033172 Issue 3
EPack Maintenance
HA033172 Issue 3 95
Technical Specification EPack
Technical Specification
Standards
The product is designed and produced to comply with:
Standard
Countries Standard details
symbol
EN60947-4-3:2014.
Low-voltage switchgear and controlgear -
Part 4-3:Contactors and motor-starters - AC
European semiconductor controllers and contactors
community for non-motor loads (identical to
IEC60947-4-3:2014).
Declaration of conformity available on
request.
96 HA033172 Issue 3
EPack Technical Specification
Installation Categories
W DANGER
HAZARD OF ELECTRICAL SHOCK, EXPLOSION OR ARC FLASH
• Do not exceed the device's ratings.
Failure to follow these instructions will result in death or serious injury.
The insulation barriers of the equipment have been designed for the rating as defined
in the table below at an altitude of 2000m maximum.
Specification
W DANGER
HAZARD OF ELECTRICAL SHOCK, EXPLOSION OR ARC FLASH
• The maximum voltage between any pole of the 85Vac to 550Vac auxiliary
supply and all other terminals must be lower than 550Vac.
Failure to follow these instructions will result in death or serious injury.
W DANGER
HAZARD OF ELECTRICAL SHOCK, EXPLOSION OR ARC FLASH
• The “24V auxiliary supply” is an SELV circuit. The supply voltage must be
derived from a SELV or PELV circuit.
Failure to follow these instructions will result in death or serious injury.
SELV is defined (in IEC60947-1) as an electrical circuit in which the voltage cannot
exceed 'ELV' under normal conditions or under single fault conditions, including earth
ground faults in other circuits.
HA033172 Issue 3 97
Technical Specification EPack
W DANGER
HAZARD OF ELECTRICAL SHOCK, EXPLOSION OR ARC FLASH
• Electrically conductive pollution must be excluded from the cabinet in which
the product is mounted.
Failure to follow these instructions will result in death or serious injury.
The product has been designed for pollution degree 2 according to IEC60947-1
definition: Normally, only non-conductive pollution occurs. Occasionally, however, a
temporary conductivity caused by condensation may be expected.
Electrically conductive pollution must be excluded from the cabinet in which the
product is mounted. To ensure a suitable atmosphere in conditions of conductive
pollution, fit adequate air conditioning/filtering/cooling equipment to the air intake of
the cabinet, e.g. fitting fan-cooled cabinets with a fan failure detection device or a
thermal safety cut-out.
W DANGER
HAZARD OF ELECTRICAL SHOCK, EXPLOSION OR ARC FLASH
• Do not exceed the device's ratings.
Failure to follow these instructions will result in death or serious injury.
Only SLIGHTLY inductive loads are allowed, contact Eurotherm for advice for Loads
lower than 32A.
98 HA033172 Issue 3
EPack Technical Specification
Physical
Dimensions and mounting See Figure 4, Figure 5, Figure 6 and Figure 7 for
centers details
Weight:
16 to 32A units 2530g + user connectors
40 to 63A units 2970g + user connectors
80A and 100A units 5830g + user connectors
125 A units 7940g + user connectors
Environment
Temperature limits:
Operating: 0°C to 45°C at 1000m
0°C to 40°C at 2000m
Storage: -25°C to +70°C
Altitude: 1000m maximum at 45°C
2000m maximum at 40°C
W DANGER
HAZARD OF ELECTRICAL SHOCK, EXPLOSION OR ARC FLASH
• Do not exceed the device's ratings.
Failure to follow these instructions will result in death or serious injury.
The insulations barriers of the equipment have been designed for an altitude of
2000m maximum.
W DANGER
HAZARD OF FIRE
• At commissioning ensure that under maximum load condition, the ambient
temperature of the product will not exceed the limit stated in that manual.
Failure to follow these instructions will result in death or serious injury.
W DANGER
HAZARD OF ELECTRICAL SHOCK, EXPLOSION OR ARC FLASH
• Respect electrical installation requirements to ensure, improve the IP rating.
Failure to follow these instructions will result in death or serious injury.
If the conductor stripping lengths of the power cables are longer than the
requirements IP20 is compromised.
If the conductor stripping lengths of the power cables are shorter than the
requirements there is a potential risk of total loss of connection. Wires may slip out of
the terminals.
If the breakaway features are removed for cables with diameter lower than 9mm the
IP20 is compromised and the product is IP10.
HA033172 Issue 3 99
Technical Specification EPack
W WARNING
UNINTENDED EQUIPMENT OPERATION
• Do not use the product for critical control or protection applications where
human or equipment safety relies on the operation of the control circuit.
• Signal and power voltage wiring must be kept separate from one another.
Where this is impractical, all wires must be rated to the power voltage &
shielded cables are recommended for signal wiring.
• This product has been designed for environment A (Industrial). Use of this
product in environment B (domestic, commercial and light industrial) may
cause unwanted electromagnetic disturbances in which cases the installer
may be required to take adequate mitigation measures.
• For Electromagnetic Compatibility, the panel or DIN rail to which the product is
attached must be grounded.
• Nominal current of product must be set between 25% & 100% of maximum
current
Failure to follow these instructions can result in death, serious injury or
equipment damage.
W DANGER
HAZARD OF ELECTRICAL SHOCK, EXPLOSION OR ARC FLASH
• The I/O Input & Output, the Communications ports are SELV circuit. They must
be connected to SELV or PELV circuit.
• The relay output and the fuse holders contacts are compliant to the SELV
requirements; they can be connected to SELV, PELV circuit or to voltage up to
230V (maximum value of rated operational voltage to earth:230V)
Failure to follow these instructions will result in death or serious injury.
SELV is defined (in IEC60947-1) as an electrical circuit in which the voltage cannot
exceed 'ELV' under normal conditions or under single fault conditions, including earth
ground faults in other circuits.
Operator Interface
Display 1.44” square TFT colour display allowing
viewing of selected parameter values in real
time, plus configuration of instrument
parameters for users with adequate access
permission.
Push buttons Four push buttons provide page and item entry
and scroll facilities.
Inputs/Outputs
All figures are with respect to 0V, unless otherwise stated.
Note 1: w.r.t. total working span Note 3: After warm up. Ambient = 25 °C
Note 2: % of effective range (0 to 20mA)
Digital Inputs
Voltage inputs
Active level (high): 11V<Vin<30V with 6mA<input current<30mA
Non-active level (low): -3V<Vin<5V with 2mA<input current<30mA
Or
5V<Vin<11V with input current <2mA
Contact closure inputs
Source current: 10mA min - 15mA max
Open contact (non active)
resistance: >800Ω
Closed contact (active)
resistance: <450Ω
Absolute Maxima: ±30V or ±25mA
Relay Specification
The relay has gold plated contacts suitable for ‘dry circuit’ (low current) use. See
"I/O Input & Output Details" on page 47.
Contact life
Resistive loads: 100,000 operations
Inductive loads: Derate as per accompanying graph
(Figure 39)
High power use
Current: 2A (resistive loads)
Voltage: <264V RMS (UL: voltage 250Vac.)
Low power use
Current: >10 mA
Voltage: >5V
Contact configuration: Single pole change-over (one set of Common,
Normally Open and Normally Closed
contacts)
Termination Removable 3-way connector. Located as
shown in Figure 12.
Installation Category Installation category III, assuming that nominal
phase to earth ground voltage is ≤ 300V RMS.
Absolute max. switching <2A at 240V RMS (resistive loads)
capability
Note: ‘Normally Closed’ and ‘Normally Open’ refer to the relay when the coil is not
energized.
Reduction factor
The parameters below are directly derived from measurements for each phase.
Accuracy (20 to 25°C)
Line frequency (F): ±0.02Hz
Line RMS voltage (Vline): ±2% of Nominal Vline.
Load RMS voltage (V): ±2% of Nominal V for voltage readings
>1% of Nominal V. Unspecified for
readings lower than 1%Vnom.
Load current (IRMS): ±2% of Nominal IRMS for current readings
>3.3% of Nominal IRMS. Unspecified for
readings ≤ 3.3% of Nominal. IRMS.
Load RMS voltage squared (Vsq): ±2% of (Nominal V)2
Thyristor RMS current squared (Isq): ±2% of (Nominal I)2
Frequency resolution 0.1 Hz
Measurement resolution 11 bits of Nominal value
Measurement drift with ambient <0.02% of reading / °C
temp.
Further parameters (Z, IsqBurst, and Vsq Burst) are derived from the above, for the
network (if relevant).
W WARNING
UNINTENDED EQUIPMENT OPERATION
• Nominal current of product must be set between 25% & 100% of maximum
current.
Failure to follow these instructions can result in death, serious injury or
equipment damage.
Eurotherm Ltd
Faraday Close
Durrington
Worthing
West Sussex
BN13 3PL
Phone: +44 (0)1903 268500
www.eurotherm.co.uk
As standards, specifications, and designs change from time to time, please ask for confirmation
of the information given in this publication.