UTL800 Winterizing and Heat Tracing
UTL800 Winterizing and Heat Tracing
Abstract
This section covers design and installation considerations for winterizing in general
and heat tracing in particular. Winterizing is the application of a general design
philosophy aimed at preventing the disabling of equipment due to the solidification
or viscosity increase of liquids, and the mechanical distortion that occurs at low
ambient temperatures.
Heat tracing is the most common method of accomplishing winterizing. This
section deals with electric, steam, glycol, and hot oil heat tracing systems.
Contents Page
810 General
This section discusses the need for, and methods of, heat tracing and winterizing
piping and equipment frequently requiring cold weather protection or process
temperature maintenance. Not included in this manual is the heat tracing of instru-
mentation, which is included in Section 1500 of the Instrumentation and Control
Manual. Insulation of equipment is covered in the Insulation and Refractory
Manual. For steam heat tracing only, the size and thickness of insulation is
discussed in Sub-section 834 of this manual.
The term winterizing is frequently substituted for the term heat tracing. They are
not equivalent. In this section, winterizing is defined to encompass all the design
considerations necessary to prevent freezing and includes consideration of liquid
pour point, burial, insulation, heat tracing, line routing, equipment layout and
design, process design, and operational methods. Heat tracing is a subset of winter-
izing, and this section deals extensively with its use as the main winterizing tool.
The following design and plant layout comments should not be construed as
applying to all fluids but only to those fluids for which temperature maintenance
would be required.
plant is shut down. If this is not practical or if a line has intermittent flow, it
should be winterized.
2. Avoid putting process valves in vertical lines: this creates a nondrainable
pocket above the valve gate.
3. In horizontal lines mount block valves with stems vertical so bonnets will not
collect water.
4. Provide large untraced valves in water service with body drains for protection
during shutdowns.
5. Branches should come off the tops or sides of lines so water will remain in the
main line.
6. Bypass lines should be self-draining, i.e., with their valves located in the
highest horizontal section of the bypass.
Pumps
1. In addition to other winterizing criteria, consider the need to prevent thermal
shock on standby pumps. Use heat tracing and/or recirculation warm-up lines
to keep pumps warm when not in use.
2. Pump vents routed to flare should be heat traced if condensation could occur or
water vapor is present.
3. Heavy oil pumps without mechanical seals may be steam purged to keep drains
open.
4. A glycol (or other low pour point fluid) cooling system for pumps is recom-
mended to avoid the freezing problems encountered with cooling water
systems.
Safety Showers
Refer to Sub-section 280 of this manual, Tempered Water Systems for Safety
Shower and Eyewash, for alternates to winterizing or for limits on installation of
winterizing.
Utility Stations
1. Water and steam lines from supply headers to utility stations should be run
together and enclosed in the same insulation, logistics permitting.
2. Use a branch from the steam line to trace the valves at the station.
3. Locate a drain hub at each station so water dripping to grade will not form ice
patches.
When the selection of steam or electric tracing is truly optional there is seldom a
clear cut choice based on economics. This is due to the variety of parameters that
must be analyzed involving costs of design, material, installation, operation and
maintenance, in addition to energy costs. Each situation should be individually
analyzed. The normal practices of the facility may govern.
Thermon Manufacturing Company, Chemelex (Raychem), Dekoron (Samuel
Moore Group) and other heat tracing manufacturers have developed computer
programs that can quickly make economical comparisons and recommendations,
and thus, provide an optimal heat tracing design to meet individual specifications.
Any Vendor’s design must be checked to ensure compliance with design specifica-
tions and that adequate design factors were used.
In addition to firms that provide economic analyses and detailed designs, there are
also firms that provide heat tracing installation and performance checks on a
turnkey basis. This approach should be considered where limited heat tracing expe-
rience is available or for large, complex projects.
The following discussion provides some general guidelines comparing capital,
energy, and maintenance costs for steam and electric tracing.
Capital costs
Electric tracing is generally cheaper than steam for short tracer lengths (less than
about 100 feet) providing the current is low enough for the thermostat to be used as
a contactor. On short runs most of the cost is in the branch circuits for electric
tracers, and for steam tracing, in the steam and condensate piping for steam tracing.
Branch circuits for electric tracers, however, are usually less expensive than steam
and condensate piping.
Most instrument tracing falls into the electric heat tracing category. This is
discussed in the Instrumentation and Control Manual.
Electric tracing is generally cheaper than steam tracing for water freeze protection
and similar low temperature applications in nonclassified areas.
For other applications, and assuming steam is available, steam tracing within a
process unit is generally cheaper than electric tracing.
For heat requirements greater than 20 to 30 watts/ft, an electric tracing system can
be more expensive than a steam tracing system because a greater number of electric
tracers per pipe will be required.
For off-plot applications, the cost of tracer systems depends on the availability of
steam or electricity. Electric power is usually more readily available.
Energy Costs
Electric energy tends to be cheaper than steam for lower temperatures such as is
required for freeze protection. Steam tracers greatly overheat the line when the
ambient temperature approaches or exceeds the required line temperature, while
electric tracers are thermostatically controlled to shut off when the required temper-
ature is reached. While low-pressure steam often appears to be cheap or free, its use
impacts the overall steam balance and must be evaluated carefully. See
Sub-section 340.
Steam energy tends to be cheaper than electric energy for maintaining a product at
high temperatures.
Tracer systems designed to operate only in plant shutdowns, usually have annual
energy costs low enough to be ignored in economic comparisons.
Maintenance Costs
Meaningful comparative maintenance costs for steam and electric tracing are not
readily available. Studies indicate maintenance costs for steam are about twice as
much as for comparable electric tracing. This higher cost is due mainly to steam
trap wear.
Electric tracing maintenance costs are less than steam, providing the tracing is prop-
erly designed, installed, and operated. (Indeed, many steam tracing systems are so
poorly installed that maintenance costs are quite high.) Electric tracing is sensitive
to overheating from line steamout, loss of insulation, and mechanical damage, most
of which can be avoided. A properly designed and operated electric tracing system
should incur very low maintenance costs.
For comparison purposes, maintenance costs normally are only a small percentage
of total cost.
Total Costs
As previously stated, each installation should be assessed individually as to the
method of heat tracing used. However, several guidelines may be applied.
• Steam tracing is more economical than electric tracing for piping in large
process units.
• Electric tracing is more economical than steam tracing for short, low wattage
applications, e.g., instruments.
– Electric tracers required for short, low wattage applications have a lower
capital cost than steam tracers.
– Energy cost differences are generally negligible because of the short
length of the tracers and relatively low heat losses.
• For off-plot and remote area tracers, electric power is usually more readily
available but the lower capital and energy costs of steam tracers may justify
bringing a steamline into an area where a large amount of tracing is required at
high heat densities and at high temperatures.
Design Considerations
The following are some important points that should be considered whether the
design is done by the Company, or the Company is checking the design work of
others.
General
• A preliminary design in sufficient detail to place orders for long lead time
items, such as transformers, may be necessary.
• The arrangement of circuits should be determined only after a careful study of
the process flow diagrams and the piping and instrument diagrams. This is
essential to a reliable design.
• Waiting until field measurements can be made to fabricate the cables will not
normally delay a job. Cables can be shipped by air and can be received at the
jobsite in less than a week if the order is placed against a prior commitment.
• Electric heat tracing routing and control layouts may be shown on transparen-
cies of piping drawings, but in most cases it is better to show them on isometric
sketches made especially for the tracing system.
• Heat tracing cables must be carefully selected to avoid overheating or under-
heating piping and equipment. Some catalogs also contain charts and tables
from which heating cables of various resistance values can be selected to
match the required heat input.
• In the past, many electric heat tracing cables have been replaced or had their
voltage increased because they failed to maintain required pipe temperatures.
Such failures can result from a number of factors, for example:
a. Inadequate weather protection for insulation or poor insulation mainte-
nance
b. Inadequate allowance for insulation variables and lower than normal volt-
ages
c. Design wind conditions that are too low
d. Use of a design minimum ambient temperature that is too high
e. Inadequate allowance for heat sinks such as valves, flanges, pipe supports,
and exposed portions of equipment
• Metal jacketing, see Area Classification, this section.
Temperature
• For all operating conditions, the maximum surface temperature of the electric
heat tracing cable must be lower than the ignition temperature of the fluid in
the pipe being heat traced. The applicable temperature limits can be found in
Article 500 of NFPA 70, the National Electric Code.
• The cable temperature should always be checked at the worst energized or de-
energized conditions (such as for high temperature upsets or steamouts) so that
it does not exceed manufacturer’s rating.
• If the de-energized temperature is too high, select a cable with a higher temper-
ature rating.
• If the energized temperature is too high, also consider heat transfer cement to
reduce cable temperature or a greater number of cables operating at a lower
wattage per foot of cable.
Length
• If a cable is too short, either a field splice or a separate short section of cable
with its own transformer is required. If the cable is too long, it will have to be
cut off and a termination fitting will have to be field installed or else the cable
will have to be doubled back on the end of the pipe or spiral wrapped around
the pipe. (Spiral wrapping, if feasible, is preferable to doubling back.)
• Changes in length of series cables after the voltage of the power source is fixed
should be limited as the power per foot of cable is inversely proportional to the
square of the length. Doubling back should only be done after it is determined
that it will not result in overheating the line or cable. Spiral wrapping cannot be
done if heat transfer cement is required or if the cable is not flexible enough to
be maneuvered around the pipe in the space available.
• Heat tracing circuits longer than 250 feet should be fabricated in multiple
sections with cold junction splices being made in an accessible junction box.
Underground
• When electric heat tracing is to be used underground, it should be designed to
allow maintenance without excavating the pipe. Use a 1/2- or 3/4-inch conduit
or similar steel raceway banded to the pipe. Have ground level pull points
every 300 feet maximum.
Individual Circuits
• Large and small pipes, pipes located indoors and outdoors, and pipes above
grade and buried, normally require separate tracers.
• Each cable must trace pipe that has uniform conditions (fluid flow and heat
loss) for the entire length of the heater.
• A single cable or cables in series should not be used to trace two or more lines
in different services.
• Use a single cable wherever possible. Use one tracer with heat transfer cement
instead of two or more tracers without heat transfer cement.
Power Supplies
• Power supply points to the cables and temperature sensors should be located so
as to minimize costs of the electrical wiring to the heater.
Control
• Thermostats must be installed in such a way that they sense a temperature that
is representative for the entire heating cable under all operating conditions. For
example, installing too close to hot or cold piping or equipment can result in
false signals.
• Optional fluid flow paths that may result in stagnant fluids and sections of pipe
with no flow, such as normally closed bypasses and dead end legs, normally
require separately controlled tracers.
Pumps
• Pumps should normally be traced with a separate section of heat tracing cable
which can be readily disconnected from any cables heating suction and
discharge lines. Valves can normally be traced with the same cable that is on
the line, with the cable installed in such a way that the valve can be removed
without cutting the cable. Alternately, valves that require frequent removal for
maintenance can be enclosed by a heated box.
Series Cables
• Series type cables should be factory fabricated to exact field dimensions of
erected pipe if at all possible to avoid the more costly and less reliable field
connections. A field check is usually necessary because piping is seldom
installed exactly as shown on the drawings.
• For series type cables, try to select a cable with a resistance such that the
voltage drop for the required length of cable is equal to a standard voltage to
avoid use of a step-down transformer.
Self-Regulating
• Copper resistance wires and self-regulating cables draw considerably more
current when cold than when final design temperature has been reached. This
can result in larger transformers, feeders, and overcurrent protective devices
than would be required for cables with alloy resistance wires such as nichrome.
Insulation
• Using correct insulation factors for the calculations is very important.
Changing insulation type can increase heat loss by a factor of two or more.
• The Insulation and Refractory Manual and various manufacturers’ catalogs
contain tables from which the required heat input can be determined for
various temperature differences between pipe and ambient for various insula-
tion thicknesses and material.
• Heat loss should be based on insulation inside diameter rather than pipe size
when oversize insulation is required to fit over the cable. A safety factor of at
least 35% should be used to allow for insulation variables unless this factor is
included in manufacturer’s selection tables. Some manufacturers’ tables
require the addition of a wind factor for outdoor lines.
• For temperatures below 212°F, insulation should be a water repellent, low
hydroscopic type such as water repellent rigid mineral wool or cellular glass.
• Weather protection for insulation is very important because electric tracing
normally has insufficient heat output to dry wet insulation. Even if drying is
possible, some insulations will never regain their full efficiency after once
being wet.
• Service test tracing before insulation.
Area Classification
• Applications for classified and nonclassified areas should be considered.
Follow the manufacturer’s recommendations.
• When metal jacketing is used, it should be smooth (rather than corrugated) and
should be of formed-modified “S” longitudinal joints. The circumferential
joints should be sealed with closure bands with nonsetting sealer applied
between the band and the jacket on each outer edge. Jacketing that is over-
lapped or otherwise closed without sealant is worthless as a barrier to moisture.
Series-Type Cables
In series-type cables, the heating elements are insulated resistance wires that are
connected together at the remote end to form a series path or loop for the electric
current. See Figure 800-1.
Advantages Disadvantages
Efficient Must be Factory Cut to Correct Length
Low Installation Cost Field Modifications Very Difficult
Accurate Temperature Control Restriction on Minimum Length Without Stepdown
Transformer
Very High Temperatures Possibility of Hot Spots
Long Circuits Possible
The required voltage for a given heat density (watts per foot of cable) is propor-
tional to the length. (For a fixed voltage, the heat density is inversely proportional
to the square of the length.) Therefore, for a given cable, different voltages are
required for different lengths. Field changes in length cannot be made without
substantially affecting the heat density unless the voltage can also be changed.
Mineral Insulated (MI) series-type cable consists of one or more copper or resis-
tance alloy conductors embedded in magnesium oxide electrical insulation and
enclosed in a copper, stainless steel or Inconel sheath. It is available from Nelson
Electric Company, Thermon, and Emerson-Chromalox. Nelson Cables are UL
approved for use in Class I, Group D, Division 2 areas when the heat density is
reduced to limit sheath temperature to a safe value.
Teflon Insulated series-type cable consists of one or more copper or resistance
alloy conductors insulated with Teflon and protected by braid. Thermon TEK cable
is the most common of this type of cable in refinery service. TEK “Sure-Flow”
cable, TEK cable with a heat transfer jacket extruded over it, can be used where
heat transfer cement is required.
Parallel Cables
Constant Wattage. This type of cable consists of two parallel bus strips or wires
with heating elements connected electrically. See Figure 800-2.
Advantages Disadvantages
Efficient Maximum Length Limitation
Low Installation Cost Possibility of Hot Spots
Can be Field Modified Easily Limited High Temperature Range
Cut to Length in Field
Uses Standard Voltages
Several suppliers make parallel-type heating cables in which the heating elements
are Nichrome wires wrapped around the two insulated bus wires and alternately
connected to them at 1- to 4-foot intervals. The assembly is enclosed in plastic insu-
lation and may be covered with a metallic braid.
The effective heating length of parallel heat tracing cable must be an integral
multiple of the distance between heating element connections to the bus wire. For
while standard voltages can be used for most applications and the cable can be
readily cut to length in the field without affecting heat density, no heat is produced
in the heating element between the last connection to the bus and the cut end.
Consideration of length also impacts in overly long runs where the bus wires set up
a resistance to current flow and, therefore, cause a voltage drop.
Self-regulating. These are also called “self-limiting” and are parallel type cables.
The resistance element is a blend of irradiated plastic and graphite particles. The
bus wires are in continuous contact, via the graphite mix, with the current flowing
between them. The entire assembly is insulated with plastic and may also be metal
jacketed. See Figure 800-3.
The resistance of the heat tracing graphitic material increases rapidly with tempera-
ture increases (and decreases with temperature decreases), making the cables self-
Advantages Disadvantages
Efficient Limited High Temperature Range
Low Installation Cost Maximum Length Limitation
Accurate Temperature Control Maximum Heat Density Less Than Series Type
Cable
Cut to Length in Field
Hot Spots Not a Problem
No Minimum Length
Uses Standard Voltages
Does Not Necessarily Require Thermostat
regulating. This feature minimizes the probability of burnouts, eliminates the need
for high- or low-temperature limit switches in most applications, and allows for the
use of a single cable on complex piping systems where heat loss may vary greatly
at different points or where doubling back and overlapping of the cable on itself is
necessary.
These cables are also flat enough to fit under standard size insulation. They give
good heat transfer without the use of cement, especially when used with aluminum
tape, and they are flexible enough to be easily wrapped (overlapped and doubled
back) around valves and equipment.
A more sophisticated type of self-regulating cable is available; utilizing four-wire,
480-volt power for use with long lines (several thousand feet). Power is supplied at
one end of the line and the heat duty is divided among the three phases and the
ground wire, at 270 volts, along the length of the line. Little Company experience is
currently available with this design.
Disadvantages of the self-regulating cables are that the maximum heat density is
less than for series-type cables.
Advantages Disadvantages
Efficient Limited Use for Shorter Circuits
Accurate Temperature Control More Difficult to Install
Very Long Circuits Must be Carefully Engineered
Can Usually be Replaced Without Removing Insulation
Because the voltage drop due to current flow in the tube is approximately equal to
the voltage induced in the tube by current flow in the internal wire (by transformer
action), the net voltage on the tube is very small.
The tube serves two purposes: as a conduit and as a heating element. At one end the
conductor is bonded to the cable and at the other, an alternating current supply is
connected across the heat tube and the cable, closing the electrical circuit. As power
is applied, the resistance of the heat tube and the cable produce heat within the heat
tube itself. This action generates about 90% of the total heat energy.
A phenomenon is then produced by an electromagnetic interaction between the
many small parallel elements of the alternating currents within the power cable,
heat tube, and flux linkage surrounding them. This interaction is called skin effect.
It causes current to concentrate on the inner surface of the heat tube wall, permit-
ting the heat tube to be welded to the carrier pipe, while giving an excellent heat
transfer from the heat tube to the product in the carrier pipe.
In addition to the heat generated by current flow in the wire and tube due to their
resistance, heat is generated in the tube by magnetic hysteresis and eddy currents
induced by the alternating current.
This system is especially applicable to long pipelines because it permits long
distances between feed points. For example, distances between feed points up to
8000 feet are practicable at 480 volts or up to 12 miles at 4000 volts.
It is especially suitable for underground pipelines because in the event of an elec-
trical failure, repairs and replacement can be made without digging up the pipeline.
Similarly, repairs can readily be made on insulated aboveground lines without need
to remove pipe insulation. This system can maintain line temperatures up to about
300°F, using Teflon insulated wire.
It is recommended that the Engineering and Technology Department (ETD)
Mechanical and Electrical Division be contacted for counsel and assistance if IWIS
heat tracing is being considered.
IWIS systems are generally used for pipelines, such as Carter Creek’s 21 mile
molten sulfur line. The system is designed to provide heat to the carrier pipe and
the product evenly along the full length of the pipe. Constant temperature is main-
tained by cycling the system on and off. A temperature sensor attached to the
carrier pipe is constantly monitored by a temperature controller.
Monitoring Devices
Monitoring devices to check heater operation should be provided in critical applica-
tions. High- and low-temperature alarms and ammeters or current relays activating
alarms to check current flow can be used. Ammeters are less costly than a relay-
alarm system, but must be manually read to check on current flow (and thus heater
operation).
With series cables, current is either 100% (heater operating) or zero (heater cable
open). Even if several series cables are connected in parallel to a single circuit,
current will change by relatively large increments as individual cables fail. Hence,
relatively insensitive and inexpensive meters or relays can be used.
With self-regulating parallel cables, the current is a function of heater temperature;
thus, current monitoring cannot be used to determine heater condition.
With resistance parallel cables, current will drop off as individual heater elements
fail. However, because a heater cable consists of many parallel elements, several
elements would have to fail to affect total current significantly. This means that a
segment of a traced line may already be frozen without any indication of failure via
current measurement. Voltage fluctuations also directly affect total current. Thus,
current monitoring is of limited usefulness with parallel-type cables.
The voltage between bus wires of a parallel-type cable can be monitored at the
remote end by a pilot light or voltage relay. This will indicate whether the entire
cable is intact and energized. Voltage at the remote end will not positively ensure
that the cable is heating properly; anywhere from zero to all of the parallel elements
may have failed.
Major heating cable suppliers offer fairly sophisticated monitoring and alarm pack-
ages, and development work in this area is continuing. Suppliers should be
contacted for further details.
Fault Detection
If a fault occurs in a series-type cable, the fault current is limited by the resistance
of the cable up to the point of fault. If this is near the remote end, the fault current
may be only slightly greater than the normal current, and thus will not trip the over-
current protective device. There have been instances in which faults have occurred
and the resulting arcs have burned back along the cable toward the source until the
resistance was reduced sufficiently to permit the overcurrent device to trip.
In classified areas and in other critical installations, fault protection should be
considered. A ground fault circuit interrupter (GFCI) will provide the required
protection.
Field Supervision
Proper installation of the tracer system is essential to prevent cable burnouts and to
obtain the required amount of heating. For this reason, very careful and thorough
field supervision is required.
In many cases, particularly where series-type cables are used, every inch of cable is
critical and should be inspected before the thermal insulation is installed. In addi-
tion, after installation each cable should be checked for continuity and meggered
(use of high voltage ohmmeter) to check resistance to ground.
The installation and checkout of an electric heat tracing system should be under the
direct supervision of an experienced construction engineer. If a qualified Company
engineer is not available, the services of a supplier’s factory trained man should be
obtained at least at the start of installation work to assist the installation supervisor
and craftsmen in understanding product operation and installation.
Depending on the size of a job, additional services may be justified for taking accu-
rate field measurements of installed pipe, inspection of cable installation, and
startup of the system. For this, the service to consider is that of a turn-key design,
procure, and install contractor.
easily that tracer tubes are inadequate to prevent solids buildup (for example lines
carrying liquid sulfur). An example of steam jacketed double wall pipe is shown in
Figure 800-6.
Internal Steam Tracing uses a return bend or hairpin tracer inside the product line.
This system provides a high heat transfer rate and eliminates the oversize insulation
needed to fit over tracers that are external.
Internal tracing has application for long runs of large diameter pipe where a high
heat input per foot is required. For example, penetration asphalt handling systems.
In intermittent services such as loading lines, internal tracing can provide fast
startup because normally all that is required is to melt a small area around the tracer
for flow to begin.
Disadvantages are that pigs or scrapers cannot be used, cross contamination is
possible, flow area is reduced, and alloys are required to prevent corrosion by some
products. Contamination through leakage may be of serious concern and should not
be overlooked.
Where low pressure steam will be required to prevent boiling or overheating of the
product in the line, particularly on small lines, electrical tracing should be consid-
ered. Use of insulating strips between a high pressure steam tracer and the pipe is
an alternative to low pressure steam use.
Assumptions
1. The tracer does not touch the traced line and all heat transfer is by convection
and radiation.
2. The inside surface of the insulation is at the product temperature.
3. The outside of the tracer is at the steam temperature.
4. The thermal resistance on the outside of insulation is negligible. This assump-
tion causes an error of less than 0.5% when wind velocities are 15 MPH or
higher or when a cold rain is falling.
5. Thermal equilibrium has been reached.
Equations
Q t = Q Convection + Q Radiation
T s – Tp
0.25
( T s + 460 ) 4 ( T p + 460 ) 4
= 0.131N t d t ------------------ ( T s – T p ) + 0.0453N t d t F ---------------------------
- – -----------------------------
dt 100 100
(Eq. 800-1)
0.524KS
Q i = --------------------------- ( T p – T a )
di
ln -----------------
d i – 2t i
(Eq. 800-2)
Q
W s = -------i
Hv
(Eq. 800-3)
where:
di = Outside diameter of insulation, in.
dt = Outside diameter of tracers, in.
F = Factor for net radiation from the tracer. Use 0.5 for copper tubing
and carbon steel pipe tracers.
Hv = Heat of vaporization of the steam, Btu/lb
K = Conductivity of insulation Btu/hr-ft2 - °F/in. (If not listed, refer
to the Insulation and Refractory Manual for selection)
Nt = Number of tracers
Qt = Heat loss from tracer(s), Btu/hr per foot of pipe
Methods of Solution
1. If the desired holding temperature, Tp, is known, solve by trial and error for the
smallest number and diameter of tracers that will cause Qt to be equal to or
greater than Qi.
2. If the number and diameter of tracers is known, solve by trial and error for the
product temperature that will cause Qt to equal Qi.
3. When a large number of calculations are required, a computer or a program-
mable calculator can easily be programmed to solve these equations.
Fig. 800-7 Maximum Tracer Length Between Traps 3/8-Inch Nominal (1/2-Inch OD) Tube
lb/hr Steam Length of Tracers, ft
per 100 ft 15 psig 40 psig 150 psig
Tracer Tube Steam Steam Steam
5 200 310 500
10 120 200 410
15 100 150 320
20 80 130 260
25 — 110 220
30 — 100 200
35 — — 180
40 — — 160
Note For explanation see Section 836.
Fig. 800-8 Maximum Tracer Length Between Traps 5/8-Inch Nominal (3/4-Inch OD) Tube
lb/hr Steam Length of Tracers, ft
per 100 ft 15 psig 40 psig 150 psig
Tracer Tube Steam Steam Steam
5 450 500 500
10 320 490 500
15 240 380 500
20 200 310 500
25 180 280 500
30 160 250 500
35 140 220 450
40 130 200 410
45 120 180 380
Note For explanation see Section 836.
Fig. 800-9 Maximum Tracer Length Between Traps 1-Inch Nominal (1 1/8-Inch OD) Tube
lb/hr Steam Length of Tracers, ft
per 100 ft 15 psig 40 psig 150 psig
Tracer Tube Steam Steam Steam
5 500 500 500
10 500 500 500
15 500 500 500
20 500 500 500
25 500 500 500
30 450 500 500
35 410 500 500
40 360 500 500
45 300 500 500
Note For explanation see Section 836.
Fig. 800-10 Maximum Tracer Length Between Traps 1/2-Inch Schedule 80 Pipe
lb/hr Steam Length of Tracers, ft
per 100 ft 15 psig 40 psig 150 psig
Tracer Pipe Steam Steam Steam
5 270 420 500
10 170 270 500
15 130 200 440
20 110 180 350
25 — 150 300
30 — 130 270
Note For explanation see Section 836.
Fig. 800-11 Maximum Tracer Length Between Traps 3/4-Inch Schedule 80 Pipe
lb/hr Steam Length of Tracers, ft
per 100 ft 15 psig 40 psig 150 psig
Tracer Pipe Steam Steam Steam
5 460 500 500
10 320 490 500
15 240 380 500
20 200 310 500
25 — 280 500
30 — 250 500
Note For explanation see Section 836.
Fig. 800-12 Maximum Tracer Length Between Traps 1-Inch Schedule 80 Pipe
lb/hr Steam Length of Tracers, ft
per 100 ft 15 psig 40 psig 150 psig
Tracer Pipe Steam Steam Steam
5 500 500 500
10 500 500 500
15 480 500 500
20 420 500 500
25 370 500 500
30 330 500 500
35 310 500 500
Note For explanation see Section 836.
Two-Phase Flashing—Caution
Some condensate flashes to steam as it discharges through the traps to a lower pres-
sure. More condensate flashes to steam as the pressure is reduced in flowing
through the condensate piping. This produces a propensity for 2-phase flow (liquid
and vapor) in the condensate return lines. Therefore, pressure drop calculations
should be based on two-phase flashing flow (discussed in Section 350 of this
manual).
When traps are grouped in a common manifold, all of the traps will occasionally
discharge simultaneously. Typically, lines from grouped traps to the branch collec-
tion header are sized for the sum of the instantaneous rates of all traps on the mani-
fold. Lines serving steam tracers only, however, should be sized for half this load.
An allowance should be made for future additions to the system, for fouling of the
pipe with rust and scale, and for blowing of live steam through worn traps or traps
that have failed open.
Oversizing of the condensate return system may also promote excessive flashing
and subsequent restriction in condensate return. This will lead to inadequate tracer
functioning.
850 References
Engineering Data Book, Gas Processors Suppliers Association (GPSA).
Fig. 800-26 Insulation Size and Minimum Thickness for Traced Lines in Figures 800-14 through 800-25
Traced Insulation Insulation Insulation
Line Size, Thickness(1) Thickness(1)
Size Inside Diameter K = 0.3 to 0.4 K < 0.3
1 1 ½(2) 1 1
1½ 2(2) 1½ 1
2 3 1½ 1
3 4 1½ 1
4 6 2 1½
6 8 2 1½
8 10 2 1½
10 12 2 1½
12 14 2 1½
14 16 2 1½
16 18 2 1½
18 20 2 1½
20 22 2 1½
24 26 2 1½
Note Guidelines for selection of economic insulation thickness, are discussed in the Insulation and Refractory Manual, Section 300.
(1) Insulation thickness for K = 0.3 to 0.4 Btu/hr-ft2-×F/in. were based on economics for the United States in 1974. They may not be the most
economical thicknesses today. Fuel cost assumed was $5.00/EFO bbl. The insulation thicknesses for K less than 0.3 were selected to
give approximately the same heat loss at K = 0.3 as the thicker insulation at K = 0.4.
(2) Use 2-inch insulation size on 1-inch line and 3-inch insulation size on 1 ½-inch line when Schedule 80 pipe tracers are used.