Factors Affecting Power Cable Current Ratings
Factors Affecting Power Cable Current Ratings
Technical Publication1
1 Electrotechnik Pty Ltd - www.elek.com.au
Abstract
As well as the construction of the cables themselves, there are various installation conditions which affect the current rating of cables installed in both air
and soil. For cables in air; ambient air temperature and exposure to direct solar radiation. For buried cables; soil dry-out, soil thermal resistivity, phase
spacing, ambient soil temperature and backfill construction. For cables both in air and in soil; conductor size, conductor material, circuit grouping, duct size
and duct material affect current rating. It’s important to consider these factors during the modelling for an accurate calculation of current rating and to match
them with the specific installation conditions of your cable project.
Keywords: High voltage power cables; Current rating; Finite element method
www.elek.com.au
2 Factors Affecting Power Cable Current Ratings
Figure 1 Current rating versus conductor size – Copper and Figure 3 Current rating versus duct size – cables in air
aluminium cables in air
Figure 4 Current rating of 120 mm2 , 400 mm2 and 800 mm2 cables
Figure 2 Current rating versus ambient air temperature exposed to varying solar radiation intensity
www.elek.com.au
Patrick and Dayan 3
Figure 6 Current rating versus separation between trefoil groups Figure 8 Current rating versus native soil thermal resistivity
www.elek.com.au
4 Factors Affecting Power Cable Current Ratings
Figure 9 Current rating versus spacing (separation) between Figure 11 Sheath loss factor versus spacing (separation) between
phases phases
in the order of 2.5 °C.m/W. Ground which is composed of building the current rating reduces with phase spacing as the increase in
rubble and as such has air gaps may have resistivity higher than 3 sheath loss factor has a greater impact on current rating than the
°C.m/W. reduction in mutual heating effects. For smaller cables with lower
sheath loss factors an increase in phase spacing causes a slight
4.3. Spacing between phases and sheath losses increase in current rating. The increase in sheath loss factor can be
Figure 9 shows that as the spacing between phases is increased seen in Figure 11.
the current rating also increases, except for large cables with solid For certain solidly bonded cases there is a point where the effect
bonding (explained in the next sections). This is due to a reduction of increased circulating currents becomes less than the reduction
in the mutual heating effects between phases. of mutual heating effects and the current rating slightly increases.
Increasing the phase spacing has the following positive and In comparison, the sheath loss factor in a solidly bonded mul-
negative effects: ticore cable is much lower than for single core cables and this
Single-point bonded cables – current rating increases often sig- difference is observed in Figure 12. Note that the modelled ar-
nificantly; and sheath standing voltage (which is a safety concern) rangement for the single core circuit is trefoil and touching.
is increased due to increased mutual inductances between sheath
and conductor. This increase in standing voltage can be seen in 4.4. Touching and non-touching cables
Figure 10. When cables are touching or laid in close proximity to each other,
Solid bonded cables – losses in the sheath (or screen) increases the heat flux of a cable will be distorted by that of other cables
with conductor spacing as the reactance of the sheath Xs increases that are nearby. In general, this distortion becomes significant with
according to cables which are spaced by less than two cable diameters. For this
s reason the empirical equations given by the IEC Standard (2) for
Xs ∝ ln( )
d touching cables are different to those for spaced cables, the latter
where s is phase spacing and d is screen diameter. For large cables of which were originally derived using the finite element method
Figure 10 Standing voltage versus spacing (separation) between Figure 12 Sheath loss factor versus conductor size in single core
phases and multicore cables
www.elek.com.au
Patrick and Dayan 5
to account for the heat flux distortion. tical buried single core trefoil circuits spaced by 0.2 m from each
Heat emanates radially from the conductor, which is the hottest other.
component and the main heat source inside the cable. The heat The isolated current rating for a single core trefoil circuit is
fields for both touching and spaced cables are shown in Figure 13, 534 A. For identical trefoil circuits that are equally loaded, where
and were calculated using the finite element method. The meshed mutual heating is considered, the current rating is reduced by 33.7
layouts are given in Figure 14, where the hottest points on the % to 354 A.
outer surfaces of the cables (caused by the mutual heating between The mutual heating effect can be clearly examined when the cir-
cables) are indicated with yellow-coloured crosses. cuits are unequally loaded. For circuits that are unequally loaded,
such as shown in Figure 16, the cable circuits in the middle of the
arrangement have a higher degree of mutual heating and thus a
4.5. Multiple Buried Circuits lower current rating compared with the outer circuits, 334 A and
Often multiple circuits are buried inside the same trench. Due to 391 A respectively.
the mutual heating effects between the cables the current rating of When there are both single-core and multi-core circuits buried
the circuits will be reduced. Since there are an infinite number of near each other, the multi-core cables tend to have a slightly higher
arrangements for this scenario there are no general rules to follow. degree of mutual heating than the single-core cables, due to the
However, in general the higher the number of circuits and the additional cores. Subsequently, the multi-core circuit has a greater
closer they are spaced the more their current ratings are reduced thermal resistivity increase than the single core circuit, which ends
due to the mutual heating. up decreasing the current rating of the multi-core circuit slightly
As an example, Figure 15 shows an arrangement of four iden- more than the single core circuit. This decrease can be seen in
www.elek.com.au
6 Factors Affecting Power Cable Current Ratings
Figure 15 Multiple buried identical trefoil circuits - equally loaded Figure 17 Single core and multicore buried circuits
Figure 17. ing cables at depths greater than 1 metre, to consider and to pro-
Without considering mutual heating, the multi-core circuit in pose to your client to use expected soil ambient temperature and
Figure 17 has a current rating of 531 A and the single-core circuit not a conservative value such as 25 °C from the standards. The
has a current rating of 534 A. However, when mutual heating expected average soil ambient temperature can be calculated based
is considered, the multi-core circuit drops to 469 A, whereas the on the following data:
single-core circuit drops to 474 A. The multi-core circuit has had a
greater current rating loss than the single-core circuit.
1. Annual average temperature.
4.6. Ambient soil temperature 2. Maximum annual temperature variation from average.
3. Soil thermal diffusivity (inertia).
The ambient soil temperature affects the cable rating and is de-
4. Time of year.
pendent on climatic factors as well as installation specific factors.
5. Depth of burial.
The ambient soil temperature can either be measured or taken
from relevant meteorological data sources. Applicable national
standards exist which specify the ambient temperatures at which For example, a particular installation in a moderate climate
cable ratings shall be calculated for your country or a region, how- the average annual temperature is 12 °C and the maximum tem-
ever where these are not available then IEC 60287-3-1 (3) may be perature is 35 °C. Therefore, the maximum annual temperature
referred to. variation is 23 °C. The soil composition resembles wet sand hence
Figure 18 shows that as soil ambient temperature goes up cable the soil thermal diffusivity is 0.01 cm2 /s. The anticipated depth of
current rating goes down linearly. The drop in current rating is burial of cables is 1 metre.
greater for larger cables than it is for smaller cables due to surface Figure 19 shows that during summer at a depth of 1 metre the
area. soil temperature is 21.64 °C. As can be seen, as depth of burial ap-
It is often commercially advantageous, particularly when bury- proaches infinity the soil ambient temperature approaches average
ambient temperature.
www.elek.com.au
Patrick and Dayan 7
Figure 20 Modelled backfill area. Note the circuit remains in the Figure 22 Current rating of cables versus backfill thermal
centre. resistivity
www.elek.com.au
8 Factors Affecting Power Cable Current Ratings
Appendix
Cable dimensions are required for modelling in ELEK™ Cable HV
software. The following cable data was taken from the Olex HV
cable catalogue (5).
www.elek.com.au