0% found this document useful (0 votes)
2K views3 pages

Electrical Cable - GTP

The document provides the guaranteed technical particulars for instrumentation cables to be supplied by Suyog Electricals Ltd. to HPCL for their LPG import facility project in Mangalore. It specifies the details of the cable construction including the number of cores/pairs, insulation material, screening, inner and outer sheath materials, electrical and mechanical properties to be met. The cable sizes range from 1 to 24 pairs with copper conductors, XLPE insulation, PVC inner and outer sheathing, steel wire armouring and will meet various IS standards and testing including flame retardant and smoke density requirements.

Uploaded by

Nawfel Arafath
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
2K views3 pages

Electrical Cable - GTP

The document provides the guaranteed technical particulars for instrumentation cables to be supplied by Suyog Electricals Ltd. to HPCL for their LPG import facility project in Mangalore. It specifies the details of the cable construction including the number of cores/pairs, insulation material, screening, inner and outer sheath materials, electrical and mechanical properties to be met. The cable sizes range from 1 to 24 pairs with copper conductors, XLPE insulation, PVC inner and outer sheathing, steel wire armouring and will meet various IS standards and testing including flame retardant and smoke density requirements.

Uploaded by

Nawfel Arafath
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 3

GUARANTEED TECHNICAL PARTICULAR

Customer : HPCL
Project : HPCL-LPG CAVERN AT MANGLORE LPG IMPORT FACILITY
Ref No. : SEPL/KM/HPCL/GTP/23-24/9092
Manufacturer : Suyog Electricals Ltd. Rev.03.Dt.24.07.2023
SR
Description Unit 1Pair x 1.5mm2 2Pair x 1.5mm2 3Pair x 1.5mm2 4Pair x 1.5mm2
No.
1 MAKE SEPL
2 Type of Cables(size) 1P x 1.5mm2 2P x 1.5mm2 3P x 1.5mm2 4P x 1.5mm2
3 No of Element P 1P 2P 3P 4P
4 Voltage Grade V 650/1100 V
5 Screening Type Overall Screening Individual & Overall Screening
6 Conductor Material Annealed Stranded Bare Copper as per IS :8130
7 Insulation material Extruded XLPE As per IS : 7098 P1
8 Pair Identification Black & Blue Black & Blue with number identification on Tape or Insulation
9 Insulation Thickness (Nominal) mm 0.6
10 No of twist/mtr twst/mtr Min 10
11 a) Al. Myler Thickness - Individual shield mm NA 0.05
b) Al. Myler Thickness - Overall shield mm 0.05 0.075
12 Drain Wire mm2 ATC - 0.5mm2
13 Communication Pair NA Provided (Green & Red)
14 Rip Cord Provided
15 INNER SHEATH
a) Material Extruded FR PVC TYPE ST-2 as per IS:5831
b) Thickness of sheath (min) mm 0.3
c) Colour Black
d) Dia over inner sheath (+/- 2mm) mm 7.1 12 12.8 13.9
16 ARMOUR
a) Material G.S Round Wire G.S Flat Strip
b) Armour Size (Nominal) mm 1.4 4.0 x 0.8
c) Dia over armour (+/- 2mm) mm 9.8 14.7 15.6 15.5
17 OUTER SHEATH
a) Material Extruded FRLS PVC TYPE ST-2 as per IS:5831
b) Thickness (min) mm 1.24 1.4
c) Colour Black
d) Tolerance on Overall Diameter (+/-2mm)
e) Overall dia of cable (+/-2mm) mm 12.6 17.5 18.7 18.6
f) Net weight of cable (Approx) kg/km 282 540 600 570
18 FRLS PROPERTIES
a) Oxygen Index(test as per ASTM-D2863) % 29% (min)
b) Temperature Index Test ( ASTM-D2863) Deg. C. 250 Deg.C (min)
c) Smoke Density(test as per ASTM-D2843) % 60% (max) SDAR
d) Acid gas emission(test as per IEC-754(I)) % 20% (max)
19 ELECTRICAL PARAMETERS
1 High Voltage test
Between Conductor 2 KV - AC / 1 Minute
Bet,Core & Screen 1 KV - AC / 1 Minute
2 Resistance Test at 20 'C
Conductor Ω/km 12.3 Max
Drain wire Ω/km 30 Max
3 Mutual Capacitance core to core at 1kHz pF/mtr 100 (max)
4 Capacitance Pair to Screen pF/mtr 400 (max)
5 L/R Ratio µH/Ω 40 (max)
6 Insulation resistance MΩ/km 1000 (min)
20 Marking on cable (Printing) SEPL 650/1100V Instrumentation Cable FRLS , Cable Size , Year , Seq Mark
21 Standard Drum Length mtr 500/1000 mtr/PO Qty (± 3%)
NOTE :-
1 The Data specified above are based on IS specification and in case of any dispute or typographical error,
interpretation of IS specification shall prevail.
2 The conductor diameter are indicative and shall confirm to meet the IS requirements of conductor resistance
3 The packing drum dimension and weight are approximate and may vary.
4 Non standard length shall be limited to 10% of the ordered quantity.
GUARANTEED TECHNICAL PARTICULAR

Customer : HPCL
Project : HPCL-LPG CAVERN AT MANGLORE LPG IMPORT FACILITY
Ref No. : SEPL/KM/HPCL/GTP/2023/9092
Manufacturer : Suyog Electricals Ltd. Rev.03.Dt.24.07.2023
SR
Description Unit 6Pair x 1.5mm2 7Pair x 1.5mm2 10Pair x 1.5mm2 12Pair x 1.5mm2 24Pair x 1.5mm2
No.
1 MAKE SEPL
2 Type of Cables(size) 6P x 1.5mm2 7P x 1.5mm2 10P x 1.5mm2 12P x 1.5mm2 24P x 1.5mm2
3 No of Element P 6P 7P 10P 12P 24P
4 Voltage Grade V 650/1100 V
5 Screening Type Individual & Overall Screening
6 Conductor Material Annealed Stranded Bare Copper as per IS :8130
7 Insulation material Extruded XLPE As per IS : 7098 P1
8 Pair Identification Black & Blue with number identification on Tape or Insulation
9 Insulation Thickness (Nominal) mm 0.6
10 No of twist/mtr twst/mtr Min 10
11 a) Al. Myler Thickness - Individual shield mm 0.05
b) Al. Myler Thickness - Overall shield mm 0.075
12 Drain Wire mm2 ATC - 0.5mm2
13 Communication Pair Provided (Green & Red)
14 Rip Cord Provided
15 INNER SHEATH
a) Material Extruded FR PVC TYPE ST-2 as per IS:5831
b) Thickness of sheath (min) mm 0.3
c) Colour Black
d) Dia over inner sheath (+/- 2mm) mm 17.1 17.6 20.3 21.4 28.9
16 ARMOUR
a) Material G.S Flat Strip
b) Armour Size (Nominal) mm 4.0 x 0.8
c) Dia over armour (+/- 2mm) mm 18.7 19.2 21.9 24 31.4
17 OUTER SHEATH
a) Material Extruded FRLS PVC TYPE ST-2 as per IS:5831
b) Thickness (min) mm 1.4 1.56
c) Colour Black
d) Tolerance on Overall Diameter (+/-2mm)
e) Overall dia of cable (+/-2mm) mm 21.8 22.3 25 27.1 34.9
f) Net weight of cable (Approx) kg/km 780 820 1045 1140 1880
18 FRLS PROPERTIES
a) Oxygen Index(test as per ASTM-D2863) % 29% (min)
b) Temperature Index Test ( ASTM-D2863) Deg. C. 250 Deg.C (min)
c) Smoke Density(test as per ASTM-D2843) % 60% (max) SDAR
d) Acid gas emission(test as per IEC-754(I)) % 20% (max)
19 ELECTRICAL PARAMETERS
1 High Voltage test
Between Conductor 2 KV - AC / 1 Minute
Bet,Core & Screen 1 KV - AC / 1 Minute
2 Resistance Test at 20 'C
Conductor Ω/km 12.3Max
Drain wire Ω/km 30 Max
3 Mutual Capacitance core to core at 1kHz pF/mtr 100 (max)
4 Capacitance Pair to Screen pF/mtr 400 (max)
5 L/R Ratio µH/Ω 40 (max)
6 Insulation resistance MΩ/km 1000 (min)
20 Marking on cable(Printing) SEPL 650/1100V Instrumentation Cable FRLS , Cable Size , Year , Seq Mark
21 Standard Drum Length mtr 500/1000 mtr/PO Qty (± 3%)
NOTE :-
1 The Data specified above are based on IS specification and in case of any dispute or typographical error,
interpretation of IS specification shall prevail.
2 The conductor diameter are indicative and shall confirm to meet the IS requirements of conductor resistance
3 The packing drum dimension and weight are approximate and may vary.
4 Non standard length shall be limited to 10% of the ordered quantity.
GUARANTEED TECHNICAL PARTICULAR

Customer : HPCL
Project : HPCL-LPG CAVERN AT MANGLORE LPG IMPORT FACILITY
Ref No. : SEPL/KM/HPCL/GTP/2023/9092
Manufacturer : Suyog Electricals Ltd. Rev.03.Dt.24.07.2023
SR
Description Unit 1Triad x 1.5mm2
No.
1 MAKE SEPL
2 Type of Cables(size) 1T x 1.5mm2
3 No of Element P 1T
4 Voltage Grade V 650/1100 V
5 Screening Type Overall Screening
6 Conductor Material Annealed Stranded Bare Copper as per IS :8130
7 Insulation material Extruded XLPE As per IS : 7098 P1
8 Pair Identification Blue , Black & Brown
9 Insulation Thickness (Nominal) mm 0.6
10 No of twist/mtr twst/mtr Min 10
11 a) Al. Myler Thickness - Individual shield mm NA
b) Al. Myler Thickness - Overall shield mm 0.05
12 Drain Wire mm2 ATC - 0.5mm2
13 Rip Cord Provided
14 INNER SHEATH
a) Material Extruded FR PVC TYPE ST-2 as per IS:5831
b) Thickness of sheath (min) mm 0.3
c) Colour Black
d) Dia over inner sheath (+/- 2mm) mm 8.2
15 ARMOUR
a) Material G.S Round Wire
b) Armour Size (Nominal) mm 1.4
c) Dia over armour (+/- 2mm) mm 10.9
16 OUTER SHEATH
a) Material Extruded FRLS PVC TYPE ST-2 as per IS:5831
b) Thickness (min) mm 1.24
c) Colour Black
d) Tolerance on Overall Diameter (+/-2mm)
e) Overall dia of cable (+/-2mm) mm 13.7
f) Net weight of cable (Approx) kg/km 367
17 FRLS PROPERTIES
a) Oxygen Index(test as per ASTM-D2863) % 29% (min)
b) Temperature Index Test ( ASTM-D2863) Deg. C. 250 Deg.C (min)
c) Smoke Density(test as per ASTM-D2843) % 60% (max) SDAR
d) Acid gas emission(test as per IEC-754(I)) % 20% (max)
18 ELECTRICAL PARAMETERS
1 High Voltage test
Between Conductor 2 KV - AC / 1 Minute
Bet,Core & Screen 1 KV - AC / 1 Minute
2 Resistance Test at 20 'C
Conductor Ω/km 12.3 Max
Drain wire Ω/km 30 Max
3 Mutual Capacitance core to core at 1kHz pF/mtr 100 (max)
4 Capacitance Pair to Screen pF/mtr 400 (max)
5 L/R Ratio µH/Ω 40 (max)
6 Insulation resistance MΩ/km 1000 (min)
19 Marking on cable (Printing) SEPL 650/1100V Instrumentation Cable FRLS , Cable Size , Year , Seq Mark
20 Standard Drum Length mtr 500/1000 mtr/PO Qty (± 3%)
NOTE :-
1 The Data specified above are based on IS specification and in case of any dispute or typographical error,
interpretation of IS specification shall prevail.
2 The conductor diameter are indicative and shall confirm to meet the IS requirements of conductor resistance
3 The packing drum dimension and weight are approximate and may vary.
4 Non standard length shall be limited to 10% of the ordered quantity.