Powermust 400 Offline

This user manual provides important safety instructions for PowerMust 400/600/1000 Offline uninterruptible power supply (UPS) systems. It describes the front panel features and connections on the back panel. It also provides instructions for inspecting the UPS for damage, charging the battery, and placing the UPS in its operating environment. The manual warns of electrical shock hazards and precautions for handling the battery safely.

Uploaded by

viorel lazaroiu
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
84 views

Powermust 400 Offline

This user manual provides important safety instructions for PowerMust 400/600/1000 Offline uninterruptible power supply (UPS) systems. It describes the front panel features and connections on the back panel. It also provides instructions for inspecting the UPS for damage, charging the battery, and placing the UPS in its operating environment. The manual warns of electrical shock hazards and precautions for handling the battery safely.

Uploaded by

viorel lazaroiu
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 10

GB

USER’S MANUAL
PowerMust 400/600/1000 Offline

Uninterruptible Power System

28-2MAXPO00201

Downloaded from www.Manualslib.com manuals search engine


IMPORTANT SAFETY INSTRUCTIONS

SAVE THESE INSTRUCTIONS – This manual


contains important instructions for models
PowerMust 400 Offline, PowerMust 600 Offline,
and PowerMust 1000 Offline that should be
followed during installation and maintenance of
the UPS and batteries.

Downloaded from www.Manualslib.com manuals search engine


Safety – CAUTION!

 This product is specially designed for PCs and it is not recommended


for use in any life-supporting system and other specific important
equipment.
 CAUTION: Risk of electric shock, do not remove cover. No user
serviceable parts inside. Refer servicing to qualified service
personnel.
 Connection to any other type of receptacle other than a two-pole,
three-wire grounded receptacle may result in shock hazard as well as
violate local electrical codes.
 In the event of an emergency, press the OFF button and disconnect
the power cord from the AC power supply to properly disable the
UPS.
 Do not allow liquids or any foreign object to enter the UPS. Do not
place beverages or any other liquid-containing vessels on or near the
unit.
 This unit intended for installation in a controlled environment
(temperature controlled, indoor area free of conductive contaminants).
Avoid installing the UPS in locations where there is standing or
running water, or excessive humidity.
 Do not plug the UPS input into its own output.
 Do not attach a power strip or surge suppressor to the UPS.
 Do not attach non-computer-related items, such as medical
equipment, life-support equipment, microwave ovens, or vacuum
cleaners to UPS
 To reduce the risk of overheating the UPS, do not cover the UPS’
cooling vents and avoid exposing the unit to direct sunlight or
installing the unit near heat emitting appliances such as heaters or
furnaces.
 Unplug the UPS prior to cleaning and do not use liquid or spray
detergent.
 Do not dispose of batteries in a fire as they may explode.
 Do not open or mutilate the battery or batteries. Released electrolyte
is harmful to the skin and eyes. It may be toxic.
 A battery can present a risk of electrical shock and high short circuit
current. The following precautions should be observed when working
on batteries:
1) Remove watches, rings, or other metal objects from the hands.
2) Use tools with insulated handles.
3) Wear rubber gloves and boots.
4) Do not lay tools or metal parts on top of batteries.
5) Disconnect charging source prior to connecting or disconnecting

Downloaded from www.Manualslib.com manuals search engine


battery terminals.
 Servicing of batteries should be performed or supervised by
personnel knowledgeable of batteries and the required precautions.
Keep unauthorized personnel away from batteries.
 When replacing batteries, replace with the same number and type of
sealed lead-acid battery.
 This pluggable type A equipment with battery already installed by the
supplier is operator installable and may be operated by laymen.
 During the installation of this equipment it should be assured that the
sum of the leakage currents of the UPS and the connected loads
does not exceed 3.5mA
 Attention, hazardous through electric shock. Also with disconnection
of this unit from the mains, hazardous voltage still may be accessible
through supply from battery. The battery supply should be therefore
disconnected in the plus and minus pole at the connectors of the
battery when maintenance or service work inside the UPS is
necessary.
 The mains socket outlet that supplies the UPS shall be installed near
the UPS and shall be easily accessible.
 Φ on the rating label stands for phase symbol.

WARNING: This is a UPS Class C2. In residential subdivision the


product may cause harmful interference, then the users have to take
additional measures.”

Downloaded from www.Manualslib.com manuals search engine


1. System Description

Front panel:
1. Power Switch 3. Fault LED: Red flashing
2. UPS status Indicator –
AC Mode: Green lighting
Battery Mode: Green flashing

400/600 1000
Back Panel
1. Output receptacles 3. Modem/Phone Line Surge
2. Fuse (Protection Function)
4. AC Input

400/600 1000

Downloaded from www.Manualslib.com manuals search engine


2. Installation and operation

1. Inspection
Remove the UPS from its packaging and inspect it for damage that
may have occurred during shipping. If any damage is discovered,
repack the unit and return it to the place of purchase.

2. Charging

This unit is shipped from the factory with its internal battery fully
charged, however, some charge may be lost during shipping and the
battery should be recharged prior to use. Plug the unit into an
appropriate power supply then switch ON the UPS and allow the UPS
to charge fully by leaving it plugged in for at least 10 hours with no load
(no electrical devices such as computers, monitors, etc.) connected

3. Placement
Install the UPS unit in a protected environment that provides adequate
airflow around the unit, and is free from excessive dust, corrosive
fumes and conductive contaminants. Do not operate your UPS in an
environment where the ambient temperature or humidity is high.

Downloaded from www.Manualslib.com manuals search engine


4. Computer Connection
Plug the UPS into a 2-pole, 3-wire grounded receptacle. Then connect
one computer-related device into each of the power receptacles
supplied on the back of the UPS.

5. Modem/Phone Line Connection


Plug incoming Modem/Phone line into the “In” socket at the back of the
UPS. Use another cable and plug one end to the “Out” socket at the
back of the UPS. Plug the other end to the modem input socket as
shown.
Incoming
Modem/Phone
Line

5. Turn On/Off
Press the switch of the UPS continuously for 1 second and the UPS
turns into its normal state (the green light is on and the beeper is off)
after it performs a self-diagnosis (the beeper and the red and green
indicator lights are on) for several seconds. At this time, user may turn
on the PC and other loads. Press the switch of the UPS continuously
for 1 second to turn off the UPS.

Note: 1. For the convenience of maintenance, please turn on the UPS first
before turning on the PC and the other loads, and turn off the UPS
after the loads are turned off.
2. At ordinary times, we recommend to remain the UPS on with the
battery charging (even if the loads are turned off), which is benefit
to the maintenance of the battery.

Downloaded from www.Manualslib.com manuals search engine


3. Trouble Shooting

Symptom Possible Cause Remedy


No LED display 1. Battery Weak 1. Re-charge battery up to 8
on the front hours.
panel. 2. Battery defect. 2. Replace with the same
type of battery.
3. Power switch is not 3. Press power switch again.
pressed.
4. Battery connector loosed4. Check the internal battery
connection
When power 1. Overload of the UPS. 1. Remove some non-critical
failure, backup load.
time is short. 2. Battery voltage is too low. 2. Charge battery 8 hours or
more.
3. Battery defect due to high 3. Replace with the same
temperature operation type of battery.
environment, or improper
operation to battery.
Mains normal 1. Fuse is blown. 1. Replace the same type of
but LED is fuse.
flashing. 2. Power cord is loose. 2. Reconnect the power cord
properly.
If any abnormal situations occur that are not listed above, please call service
people immediately.

Downloaded from www.Manualslib.com manuals search engine


4. Specification
PowerMust 400 PowerMust 600 PowerMust
MODEL
Offline Offline 1000 Offline
CAPACITY VA/W 400VA/200W 600VA/300W 1000VA/600W
INPUT Voltage 110/120VAC 220/230/240VAC
Voltage Range 90-145VAC / 170-280VAC
OUTPUT Voltage 110/120VAC 220/230/240VAC
Voltage Regulation
±10%
(Batt. Mode)
Frequency 50Hz or 60Hz
Frequency Regulation
+/-1 Hz
(Batt. Mode)
Output Waveform
Modified Sinewave
(Batt. Mode)
BATTERY Battery Type & Number 12V/4.5Ah x 1pc 12V/7AH x 1pc 12V/7AH x 2pc
Back up Time (at a PC
6 minutes 13 minutes 30minutes(typical)
load with 15" monitor)
Recharge Time 10 hours to 90% after complete discharge
TRANSFER
Typical 2-6ms, 12ms max
TIME
AC Mode Green LED lighting
Battery Mode Green LED flashing every 4 seconds
Low Battery at Battery
Green LED flashing every second
Mode
Fault Red LED lighting
INDICATOR Battery Weak at AC
Red LED flashing every 2 seconds for 30 seconds
Mode
Battery Fault at AC
Red LED flashing three times every 2 seconds
Mode
Red LED flashing
Overload N/A
twice every second
Battery Mode Sounding every 4 seconds
Low Battery at Battery
Sounding every second
Mode
Fault Continuously sounding
AUDIBLE Battery Weak at AC
Sounding every 2 seconds for 30 seconds
ALARM Mode
Battery Fault at AC
Sounding three times every 2 seconds
Mode
Sounding twice every
Overload N/A
second

Downloaded from www.Manualslib.com manuals search engine


PROTECTION Full Protection Discharge, overcharge, overload*(only for 1000VA)
Dimension, DXWXH
213x75x185 281.4x84x240.5
PHYSICAL (mm)
Net Weight (kgs) 2.5 3.1 6.5
Operating Environment 0- 40°C, 0-90 % relative humidity (non-condensing)
ENVIRONMENT
Noise Level Less than 45dB

Downloaded from www.Manualslib.com manuals search engine