Mounting instructions
Working is not affected, in any way, by the mounting position (angle of
elevation).
Before mounting it is necessary to verify that data on the label
correspond tothe ones required (type of input, auxiliary supply. etc.).
Front description
IME
2 H200 A
AL
English
Pg. Up
3
1 " IP50 FRONT FRAME PROTECTION EN6O529 (DG4P/DG4Q)
As option, IP54 front frame protection is available.
2" DISPLAY
Red LED dsplay, highest indication -1999..1999 (DG4P/RM3C) and
0..9999 (DG40).
3 KEYBOARD
3 keys used for the configuration or to select the display (instantaneous
value, peak value and state of the alarns).
4" ALARM DETECTING LED
Its lighting shows that one or both of the alarns have intervened (entering
the menu you can display the state of the alarms, verifying if one or both
of the relays are in anomaly condition).
When this anomaly condition is over, the LED automatically turns off.
5-ENGINEERING UNIT STICKY LABEL
User-customizable. Together with the meters 18 sticky labels with the most
common engineering units are supplied.
10780631 07-2003 3Ed. IME C
Programmable parameters
InP / input channel (range)
The choice of input channel (and therefore of the range) is made on two
levels, connection (input terminals) and by the keyboard programming.
5input channels are available
Ch1 range 200V (Un)
Ch2 range 20V (Un)
Ch3 range 200mV (Un)
Ch4 range 20mA (In)
Ch5 range 2mA (In)
Display
Besides the measured instantaneous value, it is possible to display the
highest reading (highest peak) and the state of the alarms ("On" =alarm
condition or "OFF" = monitoring condition).
PEAK VALUE
English
During normal working. pressing the key Ait is possible to display the
highest measured value.
Keeping this key pressed for about 5seconds, you can reset the peak
value "rS.P".
Reset is automatically made also when the meter is turned off (ack of auxtiliary 5
supply) or upon changing of input signal or display programming.
ALARM DETECTING
By passingone or both of the set thresholds, LED "AL" isturned on.
Repeatedly press PgUp until rL.A is displayed
Simultaneously press AV.
Display shows PAS followed by AL.1
By pressing A state of the alarm 1 is displayed
On = alarm condition actually present
OFF = standard condition
By pressing PgUp AL.2 is displayed
By pressing state of the alarm 2 isdisplayed
On = alarm condition actually present
OFF = standard condition
By pressing PgUpEnd is displayed
Simultaneously press A.
Display shows Sto and the meter automaticaly leaves the programming.
10780631 " 07-2003 3rEd. IME O
RANGE
It allows to select the desired range, 5 ranges (channels) are available
Programming
Pg. Up
Thanks to InP and dSP menus, it is possible to select the value of signal to
be measured as wel as its corresponding display.
Programming is made on three different phases:
Input channel " Measuring range " Display
1" Input channel
Select the channel within whose values the signal tobe measured is included
Menu InP
Ch. input channel
Menu dSP
L.In beginning of measuring range value
H.in end of measuring range value
3" Display
Program the values to be displayed corresponding with the measuring range
Menu dSP
dP. display decimal point
L.dS value to be displayed corresponding with the beginning
of the measuring range (L.In)
H.ds value to be displayed corresponding with the end of
the measuring range (H.in)
H
IIME S 10780631 07-2003 3Ed.
DISPLAY
40 Press PgUp the display shows InP
50 Press once again PgUp the display shows dSP
60 Simultaneously press A
The display shows PAS followed by L.In (beginning of measuring range)
71 Pressing once on the display, the beginning of measuring range
value is shown.
a If the displayed value is the desired one, press PgUp and go
on with the programming (see item 8) English
b If youwant to modify the value, act on or until you get
the desired one, then press PgUp
80 Display shows H.In (end of measuring range)
91 Pressing once on the display, the end of measuring range value
is shown.
a If the displayed value is the desired one, press PgUp and go on
with the programming (see item 10)
b If youwant tO modify the value, act on A or until you get the
desired one, then press PgUp
100 Display shows dP (comma)
111 Pressing once A on the display, the decimal point is shown.
a If the comma position is the desired one, press
PgUpand go no
with the programming (see item 12)
b If you want to modify its position, act on until youget
the
desired one, then press PgUp
120 Display shows L.dS (beginning of scale display)
131 Pressing once onthe display, the beginning of scale
If the displayed value is thedesired one, press value shown.
is
PgUp and go on
with the programming (see item 14)
b If you want to modify the value, act on
desired one, then press PgUp until you get the
140 Display shows H.dS (ful scale display)
151 Pressing once Aon the display, the full-scale value is shown.
If the displayed value is the desired one, press
the
PgUpand go on with
programming (see
item 16)
H
10780631 "07-2003 3rdEd. IME
b Ifyou want to modify the value, act on A or until you get the
desired one, then press PgUp
160 Display shows End, simultaneously press to confirm the programming.
170 Display shows Sto
Themeter stores the setting and automatically leaves the programming.
IME 10780631 07-2003 3Ed
Alarms
S 305/138 (option)
91
INPUT SENSOR OUTPUT
SUPPLY
+
+
Ch3 200mV
(3)
Chi 200V
Ch2 20V
Ch5 2mA
S 305/139 (option)
SENSOR
2 1 OUTPUT 81
SUPPLY INPUT +
(+) 23
20) (21)
Ch3 200mV
110
100
S 260/14
SUPPLY INPUT 1
(+) -) 4 +
75 35
RM3C
Ch3 200mV