Manual - Desicool - en (Munters)
Manual - Desicool - en (Munters)
Operating manual
DesiCool™
1 Introduction
1.1 Definition
The Air Treatment System described in this manual is hereafter referred to as the “unit”.
1.3 Warnings
Information about dangers are in this manual indicated by the common hazard symbol:
WARNING!
Indicates a possible danger that can lead to personal injury.
CAUTION!
CAUTION!
Indicates a possible danger that can lead to damage to the unit or other property, or cause environmental damage.
1.4 Warranty
The warranty is based on the terms of sale and delivery of Munters. The warranty is not valid if repairs or
modifications are carried out without the written agreement of Munters, or if the unit does not operate under
the conditions agreed with Munters. Damages resulting from negligence, poor maintenance or failure to
comply with the recommendations will not be covered by the warranty.
TEN-DSC-D1401 Introduction 1
DesiCool
It is a condition of the warranty that the unit for the full warranty period is serviced and maintained by a
qualified Munters engineer or Munters approved engineer. Access to specific and calibrated test equipment
is necessary. The service and maintenance must be documented for the warranty to be valid.
The warranty is limited to a free exchange of parts or components which have failed as a result of defects
in materials or workmanship.
Commissioning/Start-up inspection "S" by Munters is mandatory to validate the full warranty.
Always contact Munters for service or repair. Operating faults can occur if the unit is maintained
insufficiently or incorrectly.
2 Introduction TEN-DSC-D1401
DesiCool
2 Safety
2.1 Intended use
The unit delivered by Munters must only be used for the treatment of air. This includes filtering, heating,
cooling, humidifying, dehumidifying and transporting air. Munters explicitly rules out any other use.
The unit is designed to meet the safety requirements, directives and standards listed in the EC Declaration of
Conformity.
No modification of the unit is allowed without prior approval by Munters. Attachment or installation of
additional devices is only allowed after written agreement by Munters.
The conditions of operation specified in the separate Data sheet must be observed absolutely. Any other use
of the equipment can cause personal injury and damage to the unit and other property.
TEN-DSC-D1401 Safety 3
DesiCool
1
0
WARNING!
Installation, adjustments, maintenance and repairs must only be carried out by qualified personnel who are
aware of the risks involved when working with equipment operating with high electrical voltage and high machine
temperatures.
WARNING!
Do not open distribution boxes or other electrical connection boxes. The unit is connected to high voltage which
can cause serious injury or death.
WARNING!
Before doing any service or maintenance work on the unit make sure that all electrical equipment is disconnected
from the power supply, and secured against reconnection.
WARNING!
The unit must never be connected to a voltage or frequency other than that for which it was designed. Refer to the
unit identification plate.
WARNING!
Any external electrical equipment, for example a portable lamp, must be connected to an earth fault breaker.
WARNING!
Commissioning and initial start-up of the unit must be carried out by authorized personnel only.
4 Safety TEN-DSC-D1401
DesiCool
WARNING!
Rotating hazard. The unit contains rotating fans and other moving parts.
To prevent personal injury, the unit must be run with all panel doors closed and all removable panels and protective
grids properly in place. Never open the doors or panels before all fans and other moving parts have come to a
complete stop, and the main power is switched off.
Fans and other moving parts can start automatically and without warning.
WARNING!
The unit sections are heavy. Use only approved lifting equipment adapted to the weight of the sections to avoid
accidents.
WARNING!
Make sure that all pipe couplings are properly tightened before the medium supply for cooling or heating coils
is turned on.
WARNING!
Cleaning agents, cooling media, oil and grease are substances that are dangerous to personal health and to the
environment. They must not be allowed to drain away into the soil or the public sewer system. The disposal of such
substances must be effected in accordance with local and national law and regulations.
TEN-DSC-D1401 Safety 5
DesiCool
CAUTION!
CAUTION!
The unit is not intended for use in classified areas, nor for treating air polluted with solvents, dust or other
aggressive, corrosive or abrasive particles.
CAUTION!
CAUTION!
Failure to correctly adjust the air flows can cause malfunction of the unit.
Any damage to the unit resulting from incorrect adjustment of the air flows can invalidate the warranty of the unit.
The unit must not be run for more than a few minutes before setting up the correct air flows.
CAUTION!
CAUTION!
Service and maintenance work should only be carried out by qualified and trained personnel. Operating faults can
occur if the unit is maintained insufficiently or incorrectly.
CAUTION!
CAUTION!
Never climb on the unit or use it as scaffolding.
6 Safety TEN-DSC-D1401
DesiCool
TEN-DSC-D1401 Safety 7
DesiCool
Figure 2.3 Risk of electrical Figure 2.4 Hot air flow or Figure 2.5 Unit starts Figure 2.6 Pinch hazard.
shock. surface. automatically.
CAUTION!
CAUTION!
Only use the main power switch to stop the unit in the case of an emergency. The normal shutdown sequence will
not be followed. The fans stop and the heater can be very hot, which can result in damage to the heater and other
components close to it.
8 Safety TEN-DSC-D1401
DesiCool
1 2 3 4 5 6 7 8
Figure 3.1 DesiCool system design example*
There are several possible operation modes for the DesiCool system. Depending on the outside
temperature and humidity, and on the supply setpoints, the controller will activate the components as
needed.
In summer time the unit produces cool and dehumidified air by a desiccant cooling process. The ambient air
is dehumidified in the desiccant rotor. This process increases the air temperature. In the thermal recovery
rotor the air is indirectly cooled by the evaporative cooler in the exhaust. Finally, the air is further cooled
directly by the evaporative cooler in the supply.
There is a heater in the exhaust air stream for reactivation of the desiccant rotor. See the more detailed
description in section 4.1, Desiccant rotor.
In winter time the unit produces warm air. The thermal recovery rotor starts to rotate and recovers heat
from the exhaust air stream. If more heat recovery is required the desiccant rotor also starts to rotate and
recovers both heat and moisture. At extreme ambient winter conditions the hot water coil in the supply is
also in operation.
Through the use of bypass dampers it is possible to optimize the way the air is treated.
DH TH
8 7 6
M M
1 2 33 44 55
1. Differential pressure switch on filter PSW1 6. Differential pressure switch on filter PSW2
2. Input temperature and RH sensor THS1 7. Reactivation temperature sensor TS11
3. Flow control differential pressure sensor DP4 8. Antifreeze thermostat TS9
4. Antifreeze thermostat TS10 9. Flow control differential pressure sensor DP3
5. Supply temperature sensor TS2
DH. Dehumidification rotor
TH. Thermal recovery rotor
CAUTION!
CAUTION!
Coils must be frost protected when there is a risk of frost. See section 4.3.3, Frost protection.
4.1.1 Function
2
1
1. Process air
2. Dry air
3. Reactivation air
4 3 4. Wet air
The rotor is the adsorption dehumidifying component in the unit. The rotor structure is comprised of a
large number of small air channels.
The desiccant rotor is made of a composite material that is highly effective in attracting and retaining water
vapour. The rotor is divided in two zones. The airflow to be dehumidified, process air, passes through the
largest zone of the rotor and then leaves the rotor as dry air. Since the rotor rotates slowly, the incoming air
always meets a dry zone on the rotor, thus creating a continuous dehumidification process.
The airflow that is used to dry the rotor, reactivation air, is heated. The reactivation air passes through
the rotor in the opposite direction to the process air and leaves the rotor as wet air (warm, moist air). This
principle enables the dehumidifier to work effectively, even at freezing temperatures.
The rotor is monitored by a rotation sensor to enable an alarm if the rotor stops unintentionally.
4.2.1 Function
The thermal rotor is, depending on the ambient conditions, used either for cooling or for heating of the
supply air. This is done by exchanging heat between the supply air stream passing through the lower half of
the rotor, and the exhaust air stream passing through the top half in the opposite direction while the rotor
rotates.
The thermal rotor is manufactured from aluminium with many small channels through which the air passes,
making a large contact surface to transfer the heat.
The rotor is driven by an electric motor and a drive belt around the circumference of the rotor.
4.2.2 Rotor
The rotor surface must be inspected regularly.
If the rotor is dirty it can be cleaned with a vacuum cleaner, or with low pressure compressed air if necessary.
CAUTION!
CAUTION!
Hot and cold water supply lines must only be designed and executed by qualified personnel taking into account
the respective relevant local regulations.
When there is a risk of frost, the water coils must be frost protected. See section 4.3.3, Frost protection.
CAUTION!
CAUTION!
Hot and cold water supply lines must only be designed and executed by qualified personnel taking into account
the respective relevant local regulations.
When there is a risk of frost, the water coils must be frost protected. See section 4.3.3, Frost protection.
A B
A cooling section can be equipped with a droplet separator to remove droplet carry-over from the cooling
coil.
The droplet separator is built from a patented three-plane-fluted pad that is set at an angle to the flow of air.
The separator absorbs the water droplets and transports them down through the material to the drainage
section.
4.3.5 Cleaning
WARNING!
Coil fins have sharp edges. Always wear protective gloves when working with coils.
1. The coils should be checked at least once a year, and cleaned if required.
2. Some of the dust which passes through the filters comes to rest on the coil cells. This layer of dust
affects the air flow and reduces the rate of exchange leading to decreased unit efficiency.
3. The coils should therefore be kept clean. Cleaning can be done by using a vacuum cleaner, low pressure
compressed air or low pressure water and a soft brush. Do not forget to clean the unit internally after the
coil cleaning. Never use HP cleaners, this will damage the coil fins.
4. Furthermore, in the case of cooling coils, clean the drip tray and siphon for the condensation water once
per year. Note that siphons need to be refilled with water after the winter season.
Evaporative coolers/humidifiers are placed both in the supply and exhaust air streams.
They can have either a direct water supply, or a recirculated system.
The heart of the FA6 cooler/humidifier is a cassette made from inorganic evaporative media – GLASdek®.
Water is supplied to the top of the evaporative media via a distribution header. The water flows down
the corrugated surface of the media. As the warm and dry air passes through the media it evaporates a
proportion of the water and thus produces cool, humidified air. The rest of the water assists in washing the
media, and is drained back to the tank. In the case of a recirculated system, there must be a bleed-off and an
automatic drainage in order to avoid contamination of the water.
The energy that is needed for the evaporation is taken from the air itself. The air that leaves the humidifier is
therefore humidified and cooled simultaneously without any external energy supply for the evaporation.
This is in essence the adiabatic cooling process. It is very efficient and the consumption of energy is very low.
Periodic maintenance of the coolers is recommended once a year, following the operating season.
Figure 4.4 Open the safety catch on the distribution header by turning a quarter turn
6. Check that the humidifier cassette is evenly wetted and that no calcium streaks can be found on the
inlet side.
7. Check that the hoses and couplings do not leak.
8. Check the discharge pipe and water trap. Clean if necessary.
NOTE! For more information on servicing of evaporative coolers/humidifiers, see the separate Munters FA6
manual.
4.5 Fans
The unit can be equipped with plug fans or scroll fans. The fans are driven by electric motors that can be
controlled by frequency converters, which enable adjustment of the air pressure and air flow from the
operator panel.
4.5.2 Maintenance
1. Before starting up the unit, ensure that there are no loose objects inside the unit.
2. Clean the inside of the unit using a vacuum cleaner.
3. If the fan impellers come into contact with contaminated air or dust, it is imperative that they are cleaned
regularly to avoid vibrations caused by unbalance.
4. Do not use any aggressive cleaning agents, clean fan housing with warm water if required.
5. Never use a high pressure cleaner or water spray for cleaning.
4.6 Filters
WARNING!
There is a fire hazard, or risk of unit malfunction, if filters are maintained insufficiently or incorrectly.
WARNING!
When replacing the filters or working in a dusty area: To protect the user from dust, wear a suitable CE marked face
mask selected and fitted in accordance with the applicable safety standards.
The filters require regular replacement. The frequency depends on the amount of dust in the air and the
operating conditions. A filter guard will indicate when replacement is required (option).
Blocked filters can reduce the air flow in the unit. Replacing the filters is therefore of prime importance for
the correct operation of the installation. Incorrect air flow will reduce the capacity and the energy efficiency
of the unit. Replace the filters when:
■ Final pressure drop is reached.
■ There is a filter alarm.
■ The filter is damaged and air is passing without filtration.
■ Paper frame filters have become wet.
4.7 Dampers
Dampers are used to open and close the inlet and the outlet of the unit, as well as optionally for controlling
bypass and recirculation.
WARNING!
Keep hands clear of the dampers when they are moving. Risk of personal injury.
Any unducted air dampers should be fitted with a protective grille (not included in Munters delivery) to prevent
injury from the damper blade movement.
Damper maintenance
Clean and check the operation of the dampers, the gearing and bearings.
The blades can be cleaned with water or compressed air.
Check the position in respect of the indications “OPEN” and “CLOSED”.
If the dampers do not move freely, lubricate the gearing and bearings with silicone oil.
Flexible duct connections are used in order to avoid any transmission of structure borne noise and
vibrations.
The length in operation is normally 120 mm (fully extended 200 mm).
The flexible connections are relatively fragile and cuts must be avoided.
The flexible connections are fixed during transport.
WARNING!
As the pressure inside can be high, the flexible connections must not be dismounted during operation.
CAUTION!
CAUTION!
The flexible connections can never be used as duct support.
5 Commissioning
CAUTION!
CAUTION!
Commissioning and initial start-up of the unit should be carried out by Munters personnel only.
CAUTION!
CAUTION!
Rotation direction is checked in the factory meaning that if one motor is rotating in the wrong direction, all motors
are actually rotating in the wrong direction. Phases must then be inverted on the main terminal block. It is still
important to check all motors.
- The cooling coil sections are supplied with drains. Check that they are correctly connected to allow
efficient drainage.
- Fit the air filters. Ensure that the filters are firmly attached to the frame.
NOTE! Before putting the unit into operation, the bag filters must be protected to avoid the excessive
accumulation of dirt caused by the first use (dust and construction residue in the unit).
24 Commissioning TEN-DSC-D1401
DesiCool
5.3 Starting up
After carrying out all the checks listed above, the unit can be put into operation and the following points
checked:
a) Measure the tension of the network and the intensity absorbed by each motor and compare them to the
figures on the motor identification plate.
NOTE! The power of the motors in our units is calculated with a predetermined safety coefficient. Compare the
theoretical intensity with the intensity absorbed by the motor of the unit while it is operating.
b) The system’s external static pressure must comply with the order specifications. Non-conformance will
lead to variations in the air flow.
The flow rate varies according to the rotation speed of the fan, the pressure according to the square of the
rotation speed and the absorbed power according to the cube of this speed. If the system pressure is lower
than the values estimated, the flow rate will increase together with the absorbed power, which creates a risk
of overloading the motor. This is especially important for forward curved fans. For backward curved fans
the absorbed power curve follows almost exactly the rotation speed curve.
NOTE! Compliance with all these points is a condition of the guarantee.
TEN-DSC-D1401 Commissioning 25
DesiCool
1
0
Electrical hazard
WARNING!
Installation, adjustments, maintenance and repairs must only be carried out by qualified personnel who are
aware of the risks involved when working with equipment operating with high electrical voltage and high machine
temperatures.
WARNING!
Do not open distribution boxes or other electrical connection boxes. The unit is connected to high voltage which
can cause serious injury or death.
WARNING!
Before doing any service or maintenance work on the unit make sure that all electrical equipment is disconnected
from the power supply, and secured against reconnection.
WARNING!
Any external electrical equipment, for example a portable lamp, must be connected to an earth fault breaker.
Physical hazard
WARNING!
Remove hand wheels from water and steam supply valves, or otherwise lock off reopening on a component that
is isolated to prevent inadvertent reopening. Alternatively, place a notice on the valve indicating that it is closed
for a reason.
WARNING!
Rotating hazard. The unit contains rotating fans and other moving parts.
To prevent personal injury, the unit must be run with all panel doors closed and all removable panels and protective
grids properly in place. Never open the doors or panels before all fans and other moving parts have come to a
complete stop, and the main power is switched off.
Fans and other moving parts can start automatically and without warning.
WARNING!
Cleaning agents, cooling media, oil and grease are substances that are dangerous to personal health and to the
environment. They must not be allowed to drain away into the soil or the public sewer system. The disposal of such
substances must be effected in accordance with local and national law and regulations.
NOTE! A portable lamp is required when carrying out service work inside the unit.
Property hazard
CAUTION!
CAUTION!
Service and maintenance work should only be carried out by qualified and trained personnel. Operating faults can
occur if the unit is maintained insufficiently or incorrectly.
CAUTION!
CAUTION!
Protect the bottom panels if work must be carried out inside the unit.
6.2 General
Most air treatment units require the same type of maintenance. The following paragraphs explain the
necessary basic rules.
Service and maintenance interval lengths are primarily determined by operating conditions and the
environment in which the unit is installed. For example, if the process air contains a lot of dust, preventative
maintenance should be carried out at shorter intervals. The same also applies if the unit works intensively.
The service levels for a standard service and maintenance programme are described in section
6.3, Service options.
The control system is equipped with a service indicator. It is programmed at commissioning to give a service
alarm after an estimated number of operating hours, or on the preset date for the next service.
NOTE! Commissioning/Start-up inspection "S" by Munters is mandatory to validate the full warranty.
Munters service engineers have special equipment and rapid spare parts access to handle service on all
Munters products. All test equipment used by our personnel to ensure proper system balancing is certified
for accuracy.
Munters Service can offer a service plan adapted to suit the conditions of a specific installation. See contact
addresses on the back page of this manual.
Service work Operating time in hours 0 4000 8000 12000 16000 20000 24000
Inspection and leakage check of system boxes and doors, adjust hinges if
X X
necessary
NOTE! Service work should be performed at indicated operating hours or calendar time, whichever is reached
first.
NOTE! The desiccant rotor will not be replaced preventively, capacity monitoring will indicate rotor replacement.
Service level A B A B A D
Service work Operating time in hours 28000 32000 36000 40000 44000 48000
Inspection and leakage check of system boxes and doors, adjust hinges
X
if necessary
7 Scrapping
The unit must be scrapped in accordance with applicable legal requirements and regulations. Contact your
local authorities.
The rotor material is not combustible, and should be deposited like glass fibre materials.
If the rotor has been exposed to chemicals that are dangerous to the environment the risk must be assessed.
The chemicals can accumulate in the rotor material. Take the necessary precautions to comply with
applicable legal requirements and regulations.
WARNING!
If the rotor is to be cut in pieces, wear a suitable CE marked face mask selected and fitted in accordance with the
applicable safety standards to protect from the dust.
TEN-DSC-D1401 Scrapping 31
DesiCool
8 Supplements
Additional information is available in supplements as applicable:
■ Product specification data sheet
■ Control system
■ Installation
■ Humidification
32 Supplements TEN-DSC-D1401
DesiCool
9 Contact Munters
AUSTRIA Munters GmbH Eduard-Kittenberger-Gasse 56, Tel: +43 1 616 4298–92 51
Air Treatment Obj. 6 [email protected]
Zweigniederlassung Wien A-1235 Wien www.munters.at
ITALY Munters Italy S.p.A Strada Piani 2 Tel: +39 0183 521377
Air Treatment I-18027Chiusavecchia [email protected]
IM www.munters.it
SPAIN Munters Spain SA Europa Epresarial. Edificio Londres. Tel: +34 91 640 09 02
Air Treatment C/Playa de Liencres 2. [email protected]
28230 Las Matas. Madrid www.munters.es
UNITED KINGDOM Munters Ltd Pathfinder Place 10 Ramsay Court Tel: +44 1480 432 243
Air Treatment Hinchingbrooke Business Park [email protected]
Huntingdon PE29 6FY Cambs www.munters.co.uk