Caterpillar China Power System
Troubleshooting
SMCS - 4450-035
View Image
g00555151
Illustration 1
PMPE Generator Wiring Diagram
(CR1 through CR6) Rectifiers
(CR7) Varistor
(L1) Exciter field (stator)
(L2) Exciter armature (rotor)
(L3) Main field (rotor)
(L4) Main armature (stator)
(L5) Pilot exciter armature
(PM) Permanent magnet
(RFA) Rotating field assembly
(CST) Customer supplied transformer
(T1, T2, T3) Generator terminals and/or generator leads
This section provides probable causes to a known problem. There may be several probable causes to each
problem. Specific inspections or tests are recommended in order to help isolate the damaged component.
The generator is a component of the generator set. The generator should be tested with the entire system.
The voltage regulator's service manual provides tests in order to determine if the generator is the cause of
a generator set malfunction.
A problem must be identified and defined before the problem can be corrected. After you identify the
problem, refer to Table 1.
The following procedure should be used to identify the problem:
1. Perform Visual Checks in order to help identify the problem.
2. If previous tests were performed from the voltage regulator service manual, use the test results to
help identify the problem.
3. Perform the Generator Functional Test. The Generator Functional Test will help identify the
problem.
Visual Checks
A visual inspection of the generator set can detect possible causes of a malfunction. Inspect all wiring for
worn insulation or missing insulation. Ensure that all wire terminal connections are tight. Also ensure that
Page 1 of 2
Caterpillar China Power System
all wire terminal connections are not corroded. Discolored electrical components indicate that the item has
been greatly stressed.
A large percentage of electrical problems are caused by mechanical defects. Carefully inspect the total
installation. Keep the mechanical defects separate from the electrical defects.
Problem List
Table 1
PROBLEM PROBABLE CAUSE REFERENCE
All Phase Voltages Are Too Low. Damaged diodes (CR1 through "Rotating Rectifier -
CR6) Test"
Damaged exciter armature "Winding - Test"
(Rotor - L2)
Damaged exciter field (Stator - "Winding - Test"
L1)
Damaged PM armature (L5) "Winding - Test"
Damaged varistor (CR7) "Varister - Test"
The Phase Voltages Are Not Equally Damaged main armature (Stator "Winding - Test"
Balanced. - L4)
The Phase Voltages Do Not Change With Damaged diodes (CR1 through "Rotating Rectifier -
Engine Speed. CR6) Test"
Damaged Exciter armature "Winding - Test"
(Rotor - L2)
Damaged exciter field (Stator - "Winding - Test"
L1)
Damaged PM armature (L5) "Winding - Test"