2016 EPCOT Code Supplement To 2015 Edition
2016 EPCOT Code Supplement To 2015 Edition
Page 1 of 10
a 2-inch-diameter sphere. Construction of guardrails BS16-0008
shall be adequate in strength, durability and attachment
for their purpose as described in Subsection 902.2(h). Proponent: Jonathan Cantwell, Fire Protection Engineer
5. 6. For areas not accessible to the public, including (de) Installation of boiler rooms and heating equipment
catwalks and mechanical areas, the clear distance shall be in accordance with the requirements of
between rails, measured at right angles to the rails, Subsection 503.17, Table 5.2 and the EPCOT
shall not exceed 18 inches. Mechanical Code.
87. The triangular openings formed by the riser, tread Proponent: Jonathan Cantwell, Fire Protection Engineer
and bottom rail at the open side of a stairway, shall be
a maximum size such that a sphere of 6 inches in 715.1 Criteria.
diameter cannot pass through the opening.
(i) Sprinkler systems exposed to freezing temperatures
9. Docks where access is restricted or where space is that do not meet the requirements of Paragraph (f) shall
dedicated for mooring of boats. be insulated.
BS16-0007 BS16-0010
Proponent: Jonathan Cantwell, Fire Protection Engineer Proponent: Jonathan Cantwell, Fire Protection Engineer
Page 2 of 10
A readily visible, durable sign in letters not less than 1 (c) Duct penetrations of corridor walls shall be protected
inch high on a contrasting background that reads as with listed smoke dampers in accordance with the
follows shall be located on the egress side of each door EPCOT Mechanical Code.
opening:
Page 3 of 10
withstand a horizontally applied normal load of 50
pounds on an area equal to 1 square foot, including
openings and space between rails.
BS16-0016
New Section
SECTION 5-12.301
DESIGN AND CONSTRUCTION
5-12.301.2 Interior Finish. The interior finish within (b) The smoke-control equipment for the mall shall be
amusement attractions and special amusement separate from that serving tenant spaces.
buildings shall be Class 1 throughout the show space
and queue area in accordance with Section 711. (c) The covered mall building shall be compartmented
into smoke-control zones. Smoke-control zones shall be
(Note: Added changes to Section 5-12.401 for separated from each other by construction having a fire-
consistency.) resistive time period of not less than 1 hour. Walls
between tenant spaces used to separate smoke-control
SECTION 5-12.401 zones shall extend from the floor to the underside of the
AMUSEMENT BUILDINGS AND floor or roof above.
AMUSEMENT ATTRACTIONS
(d) A smoke barrier shall be provided separating the
5-12.401.1 Exits. tenant ceiling space from the mall ceiling space.
(a) Means of egress from amusement buildings and
attractions, including stairways and platforms, ramps, (e) A smoke-control zone shall coincide with the area of
fences and barricades, seats for spectators and safe coverage of a single sprinkler supply. Within that
dispersal areas, shall comply with the applicable sprinkler zone, there may be one or more air-moving
requirements of Chapter 8 as specified by the Building systems, but no single smoke-control zone shall be
Official. larger than the sprinkler area.
(b) Catwalks shall comply with the specific catwalk (f) When a fire occurs within a tenant sprinkler zone,
requirements found in Appendix M. that zone is to go to 100 percent exhaust and the
supply air to that zone is to be shut down. All adjoining
(cb) Exit Illumination and Signs. ExitH tenant smoke-control zones shall go into normal
operation.
The mall shall go to 100 percent fresh air supply without
BS16-0018 exhaust or recirculation.
(g)When a fire occurs within the mall, the mall smoke
Proponent: Jonathan Cantwell, Fire Protection Engineer control equipment shall go to 100 percent exhaust and
the adjoining tenant spaces shall go into normal
SECTION I-401 operation.
SMOKE VENTING (h)The covered mall building smoke-control equipment
shall be sized to provide a minimum of six air changes
I-401.1 Smoke-Control System. A mechanically per hour.
operated air-handling system shall be installed in (i) Mall exhaust inlets shall not be less than 6 feet
covered mall buildings, which will restrict the movement above the walking surface for each pedestrian level.
of smoke to the general area of fire origin and maintain (j) During those hours when the building air-conditioning
the exiting egress system in a condition that is safe for systems are not operating, smoke detector or sprinkler
exiting. systems shall be designed so the activation of either will
transmit an alarm as required in Paragraph (a) and shall
I-401.2 activate the smoke-control system.
(a) The smoke-control system shall be designed in
accordance with Section 720. connected to both the I-401.3 Acceptance Testing. The equipment shall be
sprinkler system and the smoke detector system, and tested in accordance with Section 702.18.before the
shall automatically operate when either the sprinkler smoke-control system is accepted by the Building
system or smoke detector system is actuated. The Official. It shall be tested Final acceptance of the
smoke-control system shall go into operation system shall be in the presence of the Building Official
immediately following actuation of the smoke detector. to confirm that the system is operating in compliance
The smoke-control system shall be as follows: with the requirements of this Subsection.
(a)Operational testing of individual components shall be
Smoke detectors shall be provided as follows: conducted when they are installed and shall be certified
1. A minimum of one area-type smoke detector in each by the installer as being complete and functional.
tenant space having an opening to the mall. Such (b)The mechanical engineer or designer of the smoke-
detector shall be located at each opening to the mall. control system shall coordinate the acceptance testing.
2. Area-type smoke detectors or approved projected It shall be demonstrated to the Building Official that the
beam detectors shall be installed to monitor the mall final system complies with the approved specified
area that can contain combustible loading, such as design and that it is operating properly.
kiosks or displays. Such installations shall be
Page 5 of 10
(c)The system shall consist of an investigation of the (b) When the heights of the show area exceeds three
performance during: stories, an exhaust system shall be provided as
1. Automatic smoke-control mode, after activation of required in Paragraph(a), however, supply air shall be
first alarm. introduced mechanically from the floor of the show
2. Manual override of normal and smoke-control modes. area. The capacity of the supply shall be 75 to 85
3. Return to normal. percent of the exhaust.
BS16-0019
Fuel Gas
Proponent: Jonathan Cantwell, Fire Protection Engineer
FGS16-0001
New Section
Proponent: Kenny Locke, Chief Technical Inspector
N-101.15 Temporary Toilet Fixtures. Additional
permanent or temporary toilet fixtures shall be provided New Section
in accordance with EPCOT Plumbing Code Table 403.1
when the temporary occupant load is in addition to the 309.15 Flanges.
original occupant load.
309.15.1 General Requirements. All flanges shall
comply with ASME B16.1, ASME B16.20 or MSS SP-6.
BS16-0020 The pressure-temperature ratings shall equal or exceed
that required by the application.
Proponent: Mike Rickabaugh, Deputy Building Official
309.15.2 Flange Facings. Standard facings shall be
New Subsection permitted for use under this Code. Where 150-pound
pressure-rated steel flanges are bolted to Class 125
5-1.401.13 Escalator and Moving Walks. Exterior of cast-iron flanges, the raised face on the steel flange
trusses shall be enclosed with a 1-hour fire-rated shall be removed.
material.
309.15.3 Lapped Flanges. Lapped flanges shall be
5-1.401.13.1 Escalators shall be provided with used only above ground or in exposed locations
guardrails that comply with Section 503.11. accessible for inspection.
BS16-0021 FGS16-0002
Proponent: Jonathan Cantwell, Fire Protection Engineer Proponent: Kenny Locke, Chief Technical Inspector
Proponent: Kenny Locke, Chief Technical Inspector 405.4 Fire Sprinkler Interlock Required. In buildings
or structures provided with an automatic fire sprinkler
New Sections: 405.1 through 405.6 system, air distribution systems with a capacity greater
than 2,000 ft3/min shall shutdown upon the activation of
405.1 Where Required. Smoke detectors listed for use the automatic fire sprinkler water flow alarm.
in air distribution systems shall be located as follows:
(a) Downstream of the air filters and ahead of any 405.4.1 Means of Egress. All air distribution systems
branch connections in air supply systems having a serving a means of egress in buildings or structures
capacity greater than 2,000 ft3/min. with automatic fire sprinkler systems shall shutdown
(b) At each story prior to the connection to a common upon activation of the automatic fire sprinkler water flow
return and prior to any recirculation or fresh air inlet alarm.
connection in air return systems having a capacity
greater than 15,000 ft3/min and serving more than one 405.5 Controls. All controls shall be listed.
story.
(c) All air distribution systems serving a means of 405.6 Manual Reset. Air distribution systems required
egress shall be provided with a duct smoke detector to shut down by this Section shall not restart until
and automatic shutdown. manually reset.
405.1.1 Area Smoke Detectors. Return system smoke 405.1 Capacity Greater than 15,000 Cubic Feet per
detectors shall not be required where the entire space Minute (CFM). Recirculating air systems shall
served by the air distribution system is protected by a automatically shut down when smoke within the system
system of area smoke detectors installed in accordance becomes excessive and upon the activation of an
with NFPA 72. automatic sprinkler water flow alarm. The automatic
smoke control shall be in the return airstream prior to
405.1.2 Exhaust. Smoke detectors shall not be exhausting from the building or mixing with fresh air
required for fan units whose sole function is to remove makeup.
air from the inside of the building to the outside of the
building. 405.2 Capacity Greater than 2,000 CFM and Less
than 15,000 CFM. Recirculating air systems shall
405.2 Function. automatically shut down upon the activation of an
automatic sprinkler waterflow alarm.
405.2.1 Automatic Stop. Smoke detectors required by
Subsection 405.1 shall automatically stop their 405.3 Capacity 2,000 CFM or Less. Recirculating air
respective fan(s) on detecting the presence of smoke. systems with a fan capacity of 2,000 cfm or less, but
serving an area used for egress, shall have automatic
Exception: Where the return air fan is functioning shut down.
as part of an engineered smoke-control system and
a different mode is required, the smoke detectors 405.4 Controls. All controls shall be listed. Upon
shall not be required to automatically stop their activation, the system shall not restart until manually
respective fans. reset.
Page 7 of 10
MS16-0002 interfere with the operation of the smoke control
system; or
Proponent: Jonathan Cantwell, Fire Protection Engineer 1.4. The penetrations are in parking garage exhaust
or supply shafts that are separated from other
SECTION 407 building shafts by not less than 2-hour fire-resistance-
STAIRWELL ENCLOSURES rated construction.
407.1 Ducts Serving Other Spaces. Ducts serving 2. In Group B and R occupancies equipped
other spaces shall not be located in or pass through exit throughout with an automatic sprinkler system in
enclosures. accordance with the EPCOT Building Code, smoke
dampers are not required at penetrations of shafts
407.2 Smokeproof Enclosures. Where required for where kitchen, clothes dryer, bathroom and toilet
high-rise buildings, stairwells shall be designed as room exhaust openings with steel exhaust subducts,
smokeproof enclosures in accordance with EPCOT having a minimum thickness of 0.0187 inch (No. 26
Building Code Subsection 720.20. gage), extend at least 22 inches vertically and the
exhaust fan at the upper terminus is powered
Minimum Ventilation. When the EPCOT Building continuously in accordance with the provisions of the
Code requires the stair shaft to be ventilated with EPCOT Building Code for emergency power systems,
mechanical supply and exhaust air, there shall be a and maintains airflow upward to the outdoors.
minimum of 2,500 cfm discharged through a dampered
relief opening or an exhaust fan at the top of the stair 3. Smoke dampers are not required at penetrations of
shaft. The supply shall be sufficient to provide a exhaust or supply shafts in parking garages that are
minimum positive pressure of 0.05 inch water column, separated from other building shafts by not less than
in addition to the maximum anticipated stack pressure, 2-hour fire-resistance-rated construction.
relative to other parts of the building measured with all
doors closed. The combined positive pressure shall not 4. Smoke dampers are not required at penetrations of
exceed 0.35-inch water column. The air supply shall be shafts where ducts are used as part of an approved
taken directly from outside of the building. The stair mechanical smoke control system designed in
pressure shall be static pressures measured at the level accordance with the EPCOT Building Code and
of discharge from the stair. where the smoke damper will interfere with the
Exception: The minimum positive pressure shall be operation of the smoke control system.
increased to 0.15-inch water column in an unsprinklered
building. 5. Fire dampers and combination fire/smoke dampers
are not required in kitchen and clothes dryer exhaust
systems installed in accordance with this Code.
MS16-0003
607.9.1 Enclosure at the Bottom. Shaft enclosures
Proponent: Kenny Locke, Chief Technical Inspector that do not extend to the bottom of the building or
structure shall be protected in accordance with the
New Section EPCOT Building Code.
609.8 Reserved.
Page 9 of 10
TABLE 403.1
MINIMUM NUMBER OF PLUMBING FACILITIESa
(see Subsections 403.2 and 403.3)
Theaters, halls, museums, etc. 1 per 125 1 per 65 1 per 200 — 1 per 1,000 1 service sink
Coliseums, arenas (less than 3,000 1 per 75 1 per 40 1 per 150 — 1 per 1,000 1 service sink
seats)
Coliseums, arenas (3,000 seats or 1 per 120 1 per 60 1 per 150 — 1 per 1,000 1 service sink
greater)
Churchesb 1 per 150 1 per 75 1 per 200 — 1 per 1,000 1 service sink
Stadiums (less than 3,000 seats), 1 per 100 1 per 50 1 per 150 — 1 per 1,000 1 service sink
pools, etc.
Stadiums (3,000 seats or greater) 1 per 150 1 per 75 1 per 150 — 1 per 1,000 1 service sink
Business (see Subsections 403.2, 1 per 50 1 per 80 — 1 per 100 1 service sink
403.4 and 403.5)
Educational 1 per 50 1 per 50 — 1 per 100 1 service sink
Factory and industrial 1 per 100 1 per 100 (see Section 411) 1 per 400 1 service sink
Passenger terminals and 1 per 500 1 per 750 — 1 per 1,000 1 service sink
transportation facilities
Residential care 1 per 10 1 per 10 1 per 8 1 per 100 1 service sink
Hospitals, ambulatory nursing
1 per room d 1 per roomd 1 per 15 1 per 100 1 service sink floor
home patientsc
INSTITUTIONAL
1 automatic clothes
washer connection
per 20 dwelling unitsf
Dormitories 1 per 10 1 per 10 1 per 8 1 per 100 1 service sink
1 kitchen sink per
One- and two-family dwellings 1 per dwelling unit 1 per dwelling unit 1 per dwelling unit — dwelling unit;
1 automatic clothes
washer connection
per dwelling unitsf
Storage (see Subsections 403.2 1 per 100 1 per 100 (see Section 411) 1 per 1,000 1 service sink
and 403.4)
a. The fixtures shown are based on one fixture being the minimum required for the number of persons indicated or any fraction of the number of persons
indicated. The number of occupants shall be determined by the EPCOT Building Code.
b. Fixtures located in adjacent buildings under the ownership or control of the church shall be made available during periods when the church is occupied.
c. Toilet facilities for employees shall be separate from facilities for inmates or patients.
d. A single-occupant toilet room with one water closet and one lavatory serving not more than two adjacent patient rooms shall be permitted where such room is
provided with direct access from each patient room and with provisions for privacy.
e. For day nurseries, a maximum of one bathtub shall be required.
f. For attached one- and two-family dwellings, one automatic clothes washer connection shall be required per 20 dwelling units.
g. See Definition in Chapter 2.
Page 10 of 10