HPS30 HPS50 HPS100 HPS120 HPS150
HPS30/50
AC(on-grid)
Apparent power 33kVA 55kVA 110kVA 132kVA 165kVA
HPS100/120/150 Rated power
Rated voltage
30kW
400V
50kW
400V
100kW
400V
120kW
400V
150kW
400V
Rated current 43A 72A 144A 173A 217A
Voltage range 360V-440V 360V-440V 360V-440V 360V-440V 360V-440V
Large capacity all-in-one hybrid inverter for commercial application,
Rated frequency 50/60Hz 50/60Hz 50/60Hz 50/60Hz 50/60Hz
supporting up to 600kW system capacity. Frequency range 45~55/55~65Hz 45~55/55~65Hz 45~55/55~65Hz 45~55/55~65Hz 45~55/55~65Hz
THDI <3% <3% <3% <3% <3%
PF 0.8 lagging~0.8 leading 0.8 lagging~0.8 leading 0.8 lagging~0.8 leading 0.8 lagging~0.8 leading 0.8 lagging~0.8 leading
AC connection 3/N/PE 3/N/PE 3/N/PE 3/N/PE 3/N/PE
AC input 60kVA 100kVA 200kVA 240kVA 240kVA
AC(off-grid)
Apparent power 33kVA 55kVA 110kVA 132kVA 165kVA
Rated power 30kW 50kW 100kW 120kW 150kW
Rated voltage 400V 400V 400V 400V 400V
Rated current 43A 72A 144A 173A 217A
THDU ≤2% linear ≤2% linear ≤2% linear ≤2% linear ≤2% linear
Rated frequency 50/60Hz 50/60Hz 50/60Hz 50/60Hz 50/60Hz
Features
Overload capability 110%-10 mins 120%-1 min 110%-10 mins 120%-1 min 110%-10 mins 120%-1 min 110%-10 mins 120%-1 min 110%-10 mins 120%-1 min
DC (Battery and PV)
All-in-one hybrid inverter Max. PV open-circuit 1000V DC 1000V DC 1000V DC 1000V DC 1000V DC
voltage
Max. PV power 45kWp 75kWp 150kWp 180kWp 225kWp
Seamless on/off grid transfer within 10 ms PV MPPT voltage range 480V-800V DC 480V-800V DC 480V-800V DC 480V-800V DC 480V-800V DC
Battery voltage range
450V-600V 500V-600V 500V-600V 517V-600V 500V-600V
at Max. charge power
Battery voltage range 352V-600V 352V-600V 352V-600V 352V-600V 352V-600V
Programmable working mode
Max. charge power 45kW 75kW 150kW 180kW 225kW
Max. discharge power 33kW 55kW 110kW 132kW 165kW
Max. charge current 100A 150A 300A 350A 450A
Support remote control of DG Max. discharge current 93A 156A 313A 374A 467A
Touchscreen LCD General Information
Protection degree IP20 IP20 IP20 IP20 IP20
Noise emission <65dB(A)@1m <65dB(A)@1m <65dB(A)@1m <65dB(A)@1m <65dB(A)@1m
Quadruple capacity by paralleling 4 units Operating temperature -25 °C~+55 °C -25 °C~+55 °C -25 °C~+55 °C -25 °C~+55 °C -25 °C~+55 °C
Cooling method Forced-air Forced-air Forced-air Forced-air Forced-air
Relative humidity 0-95% non-condensing 0-95% non-condensing 0-95% non-condensing 0-95% non-condensing 0-95% non-condensing
Maximum altitude 6000m 6000m 6000m 6000m 6000m
(derate over 3000m) (derate over 3000m) (derate over 3000m) (derate over 3000m) (derate over 3000m)
Block Diagram
Dimension (W/H/D) 700/1660/600mm 950/1860/750mm 1200/1900/800mm 1200/1900/800mm 1200/1900/800mm
Weight 355kg 610kg 948kg 1025kg 1230kg
Build-in transformer Yes Yes Yes Yes Yes
Lightning protection Type II Type II Type II Type II Type II
Transfer
Automatic≤10ms Automatic≤10ms Automatic≤10ms Automatic≤10ms Automatic≤10ms
between on/off grid
Standby consumption <30W <30W <30W <30W <30W
Communication
Display Touch screen Touch screen Touch screen Touch screen Touch screen
Communication RS485/CAN RS485/CAN RS485/CAN RS485/CAN RS485/CAN
Certificate
CE , MEA , PEA , UKCA, AS 4777.2, EN 61000-6-4:2007+A1:2011 , EN61000-6-2:2005 , EN62109-1:2010 , EN62109-2:2011 , EN 50549-1:2019 , IEC62109.1 ,
IEC62109.2, NRS 097-2-1:2017, G99, VDE-AR-N 4105:2018,DIN VDE V 0124-100:2020-06, PSE:2018-12
* The MPPT voltage of PV strings should be 50~200V higher than the Max battery voltage.