PQ Unit 2 Notes
PQ Unit 2 Notes
Single phase linear and non-linear loads – single phase sinusoidal, non-sinusoidal source –
Supplying linear and nonlinear loads – three phase balanced system – three phase unbalanced
System – three phase unbalanced and distorted source supplying non-linear loads – concept of
Power factor – three phase- three wire – three phase - four wire system.
1.1 Introduction
The definitions of power and its various components are very important to understand quantitative
and qualitative power quality aspects in power system [1]–[5]. This is not only necessary from the
point of view of conceptual clarity but also very much required for practical applications such as
metering, quantification of active, reactive power, power factor and other power quality parameters
in power system. These aspects become more important when power system is not ideal i.e., it
deals with unbalance, harmonics, faults and fluctuations in frequency. We therefore, in this chapter
explore the concept and fundamentals of single phase system with some practical applications and
illustrations.
Let us consider a single-phase system with sinusoidal system voltage supplying a linear load as
shown in Fig. 1.1. A linear load is one which consists of ideal resistive, inductive and capacitive
elements. The voltage and current are expressed as below.
√
v(t) = 2 V sin ωt
√
i(t) = 2 I sin(ωt − φ) (1.1)
1
v i
∆
Q = max {preactive (t)} (1.3)
It should be noted that the way Q is defined is different from P . The Q is defined as maximum
value of the second term of (1.2) and not an average value of the second term. This difference
should always kept in mind.
Equation (1.2) shows that instantaneous power can be decomposed into two parts. The first term
has an average value of V I cos φ and an alternating component of V I cos 2ωt, oscillating at twice
the line frequency. This part is never negative and therefore is called unidirectional or dc power.
The second term has an alternating component V I sin φ sin 2ωt oscillating at twice frequency with
a peak vale of V I sin φ. The second term has zero average value. The equation (1.2) can further
be written in the following form.
With the above definitions of P and Q, the instantaneous power p(t) can be re-written as following.
2
√
Example 1.1 Consider a sinusoidal supply voltage v(t) = 230 2 sin ωt supplying a linear load of
impedance ZL = 12 + j13 Ω at ω = 2πf radian per second, f = 50 Hz. Express current i(t) as a
function of time. Based on v(t) and i(t) determine the following.
(a) Instantaneous power p(t), instantaneous active power pactive (t) and instantaneous reactive
power preactive (t)
(b) Compute average real power P , reactive power Q, apparent power S, and power factor pf .
3
The above implies that,
1 T
Z
P = p(t) dt
T 0
P = V I cos φ = 230 × 13 × cos 47.29o = 2028.23 W
Reactive power (Q) is given as maximum value of preactive , and equals to V I sin φ as given below.
For Case 2, the voltage, current and various components of the power are shown in Fig. 1.3. The
explanation given earlier also holds true for this case.
4
400 6000
Voltge (V)
4000
200
VA, W, VAr
2000
0
0
-200
-2000
p(t)
-400 -4000
0 0.01 0.02 0.03 0 0.01 0.02 pact(t) 0.03
sec sec preact(t)
20 2400
Current (A)
10 2300 Average Power (W)
Reactive Power (VAr)
W, VAr
0 2200
-10 2100
-20 2000
0 0.01 0.02 0.03 0 0.01 0.02 0.03
sec sec
Therefore, we have
√
v(t) = 230 2 sin ωt
√
i(t) = 19.167 2 sin ωt
p(t) = 230 × 19.167 cos 0o {1 − cos(2 × 314t)} − 230 × 19.167 sin 0o sin(2 × 314t)
= 4408.33(1 − cos(2 × 314t))
Voltage (V)
4000
200
VA, W, VAr
2000
0
0
-200
-2000
p(t)
-400 -4000 p (t) 0.03
0 0.01 0.02 0.03 0 0.01 0.02 act
sec sec preact(t)
20 3000
Current (A)
2000
10
1000
Average Power (W)
W, VAr
0 0 Reactive Power (VAr)
-1000
-10
-2000
-20 -3000
0 0.01 0.02 0.03 0 0.01 0.02 0.03 0.04
sec sec
For Case 3, the voltage, current and various components of the power are shown in Fig. 1.4. Since
the load is resistive, as seen from the graph preactive is zero and p(t) is equal to pactive . The average
value of p(t) is real power (P ), which is equal to 4408.33 W.
Case 4: When the load is purely reactive, ZL = j13 Ω , |ZL | = 13 Ω, I = 230 13
= 17.692 A, and
φ = 90o . Therefore, we have
√
v(t) = 230 2 sin ωt
√
i(t) = 17.692 2 sin(ωt − 90o )
p(t) = 230 × 17.692 cos 90o (1 − cos(2 × 314t)) − 230 × 17.692 sin 90o sin(2 × 314t)
= 0 − 4069 sin(2 × 314t)
pactive (t) = 0
preactive (t) = 4069 sin(2 × 314t)
Voltage (V)
8000
200
VA, W, VAr
6000
0
4000
-200 2000
0
-400 p(t)
0 0.01 0.02 0.03 0 0.01 0.02 pact(t) 0.03
sec sec
preact(t)
30 5000
Current (A)
20 4000
W, VAr
0 2000
-10 1000
-20 0
-30 -1000
0 0.01 0.02 0.03 0 0.01 0.02 0.03
sec sec
For Case 4, the voltage, current and various components of the power are shown in Fig. 1.5. The
load in this case is purely reactive, hence their is no average component of p(t). The maximum
value of p(t) is same as preactive (t) or Q, which is equal to 4069 VArs.
The load current is now considered as nonlinear load. A non-linear load is one which consists
of switched elements such as diode, transistors, MOSFET, etc., in the circuit. In power circuit,
non-linear load current exists, when source supplies to power electronics based loads such as rec-
tifier, inverter, cyclo-converters etc.. These loads cause presence of harmonics in the load current.
Assuming that all harmonics are present in the load current, the voltage and current are expressed
as following.
√
v(t) = 2 V sin ωt
∞
√ X
i(t) = 2 In sin(nωt − φn ) (1.6)
n=1
7
400 5000
Voltage (V)
200
VA, W, VAr
0 0
-200
p(t)
-400 -5000
0 0.01 0.02 0.03 0 0.01 0.02 pact(t) 0.03
sec preact(t)
30 5000
Current (A)
20 4000
10
3000
W, VAr
0 Active Power (W)
2000 Reactive Power (VAr)
-10
-20 1000
-30 0
0 0.01 0.02 0.03 0 0.01 0.02 0.03
∞
√ √ X
p(t) = v(t) i(t) = 2 V sin ωt 2 In sin(nωt − φn )
n=1
∞
X
= V [In 2 sin ωt sin(nωt − φn )]
n=1
= V [I1 2 sin ωt sin(ωt − φ1 )]
X∞
+ V [In 2 sin ωt sin(nωt − φn )] (1.7)
n=2
Note that 2 sin A sin B = cos(A − B) − cos(A + B), using this, Eqn. (1.7) can be re-written as
the following.
8
p(t) = V I1 [cos φ1 − cos(2ωt − φ1 )] − V I1 sin φ1 sin 2ωt
X∞
+V In [ (cos φn − cos(2nωt − φn )) − sin φn sin 2nωt]
n=2
= V I1 cos φ1 (1 − cos 2ωt) − V I1 sin φ1 sin 2ωt (1.8)
∞
X
+ V In [ cos φn (1 − cos 2nωt) − sin φn sin 2nωt]
n=2
= A + B
In above equation, average active power P and reactive power Q are given by,
S = V Iq
S = V [I12 + I22 + I32 + .....] (1.10)
q
H=V [I22 + I32 + I42 + .....] (1.12)
9
This is represented by power tetrahedron instead of power triangle (in case of voltage and current
of sinusidal nature of fundamental frequency). In this context, some important terms are defined
here.
Displacement Power Factor (DPF) or Fundamental Power Factor (pf1 ) is denoted by cos φ1
and is cosine angle between the fundamental voltage and current. This is equal to,
P1
DPF = pf1 = cos φ1 = . (1.13)
S1
The Power Factor (pf ) is defined as ratio of average active power to the total apparent power
(V I) and is expressed as,
P
Power Factor (pf ) =
S
V I1 cos φ1 I1
= = cos φ1
VI I
= cos γ cos φ1 (1.14)
The equation (1.14) shows that power factor becomes less by a factor of cos γ, which is ratio of
fundamental to the total current. This is due to the presence of the harmonics in the load current.
The nonlinear load current increases the ampere rating of the conductor for same amount of active
power transfer with increased VA rating. Such kind of load is not desired in power system.
10
i (t ) Id
v (t )
∞
√ X 4Idc
p(t) = v(t) i(t) = 2 V sin ωt sin(nωt). (1.15)
n=2h+1
nπ
By expansion of the above equation, the average active power (P ) and reactive power (Q) are given
as below.
11
300
Supply current (A)
200 Supply voltage (V)
100
0
-100
-200
-300
4
x 10
2.5
1.5
instantaneous power
1 Average power (W)
Reactive power (Var)
0.5
-0.5
12
and
∞
X √
i(t) = Idc + 2In sin(nωt − φin ) (1.17)
n=1
∞ ∞
X √ X √
p(t) = [Vdc + 2Vn sin(nωt − φvn )].[Idc + 2In sin(nωt − φin )] (1.18)
n=1 n=1
∞ ∞
X √ X √
p(t) = Vdc Idc + Vdc 2In sin(nωt − φin ) + Idc 2Vn sin(nωt − φvn )
| {z }
I | n=1 {z } | n=1
{z }
II III
∞ ∞
X √ X √
+ 2Vn sin(nωt − φvn ) 2In sin(nωt − φin ) (1.19)
|n=1 {zn=1 }
IV
The term I (pdc−dc ) contributes to power from dc components of voltage and current. Terms II
(pdc−ac ) and III (pac−dc ) result from the interaction of dc and ac components of voltage and current.
In case, there are no dc components all these power components are zero. In practical cases, dc
components are very less and the first three terms have negligible value compared to IV term.
Thus, we shall focus on IV (pac−ac ) term which corresponds to ac components present in power
system. The term IV can be written as,
∞ ∞
th
X √ X √
IV term = pac−ac = 2Vn sin(nωt − φvn ) 2Ih sin(hωt − φih ) (1.21)
n=1 h=1
13
frequency terms will interact. This is expressed below.
√ √
pac−ac (t) = 2V1 sin(ωt − φv1 ) 2I1 sin(ωt − φi1 )
| {z }
A
∞
√ X √
+ 2V1 sin(ωt − φv1 ) 2Ih sin(hωt − φih )
h=2,h6=1
| {z }
B
√ √
+ 2V2 sin(2ωt − φv2 ) 2I2 sin(2ωt − φi2 )
| {z }
A
∞
√ X √
+ 2V2 sin(2ωt − φv2 ) 2Ih sin(hωt − φih ) + . . . + . . .
h=1,h6=2
| {z }
B
√ √
+ 2Vn sin(nωt − φvn ) 2In sin(nωt − φin )
| {z }
A
∞
√ X √
+ 2Vn sin(nωt − φvn ) 2Ih sin(hωt − φih ) (1.22)
h=1,h6=n
| {z }
B
The terms in A of above equation form similar frequency terms and terms in B form dissimilar
frequency terms, we shall denote them by pac−ac−nn and pac−ac−nh . Thus,
∞
X
pac−ac−nn (t) = Vn In 2 sin(nωt − φvn ) sin(nωt − φin ) (1.23)
n=1
and
∞ ∞
X √ X √
pac−ac−nh (t) = 2Vn sin(nωt − φvn ) 2In sin(hωt − φih ) (1.24)
n=1 h=1,h6=n
14
where φn = (φin − φvn ) = is phase angle between nth harmonic current and voltage. Therefore,
∞
X
pac−ac−nn (t) = [Vn In cos φn {1 − cos(2nωt − 2φvn )}]
n=1
X∞
− [Vn In sin φn sin(2nωt − 2φvn )]. (1.26)
n=1
It has non-negative value with some average component, giving average active power. Therefore,
1 T
Z
P = p(t) dt
T 0
X∞
= Vdc Idc + Vn In cos φn . (1.29)
n=1
The reactive component of the instantaneous power is denoted by preactive (t) and is given as fol-
lowing.
∞
X
preactive (t) = − [Vn In sin φn sin(2nωt − 2φvn )] (1.30)
n=1
resulting in
15
Q , max of (1.30) magnitude
∞
X
= Vn In sin φn . (1.31)
n=1
From (1.29)
∞
X
P = Pdc + Vn In cos φn
n=1
= Pdc + V1 I1 cos φ1 + V2 I2 cos φ2 + V3 I3 cos φ3 + . . .
= Pdc + P1 + P2 + P3 + . . .
= Pdc + P1 + PH (1.32)
In above equation,
Pdc = Average active power corresponding to the dc components
P1 = Average fundamental active power
PH = Average harmonic active power
Average fundamental active power (P1 ) can also be found from fundamentals of voltage and cur-
rent i.e.,
Z T
1
P1 = v1 (t) i1 (t)dt (1.33)
T 0
∞
X
PH = Vn In cos φn = P − P1 . (1.34)
n=1
∞
X
Q = Vn In sin φn
n=1
= V1 I1 sin φ1 + V2 I2 sin φ2 + V3 I3 sin φ3 + . . .
= Q1 + Q2 + Q3 + . . .
= Q1 + QH (1.35)
16
Usually this reactive power is referred as Budeanu’s reactive power, and sometimes we use sub-
script B’ to indicate that i.e.,
The remaining dissimilar terms of (1.27) are accounted using prest (t). Therefore, we can write,
where,
S = V
qI q
2 2 2 2
= Vdc + V1 + V2 + · · · Idc + I12 + I22 + · · · (1.39)
q q
= Vdc2 + V12 + VH2 Idc
2
+ I12 + IH
2
Where,
∞
X
VH2 = V22 + V32 + · · · = Vn2
n=2
∞
X
2
IH = I22 + I32 + · · · = In2 (1.40)
n=2
VH and IH are denoted as harmonic voltage and harmonic current respectively. Expanding (1.39)
we can write
17
S2 = V 2I 2
= (Vdc2 + V12 + VH2 )(Idc2
+ I12 + IH2
)
= Vdc Idc + Vdc I1 + Vdc IH + V1 I1 + V12 Idc
2 2 2 2 2 2 2 2 2
+ V12 IH
2
+ VH2 Idc
2
+ VH2 I12 + VH2 IH
2
= Vdc2 Idc
2
+ V12 I12 + VH2 IH
2
+ Vdc2 (I12 + IH
2 2
) + Idc (V12 + VH2 ) + V12 IH
2
+ VH2 I12
2
= Sdc + S12 + SH 2
+ SD 2
= S12 + Sdc 2
+ SH 2
+ SD 2
| {z }
= S12 + SN
2
(1.41)
In above equation, the term SN is as following.
2
SN = Vdc2 I12 + Vdc2 IH
2
+ V12 Idc
2
+ V12 IH
2
+ VH2 Idc
2
+ VH2 I12 + VH2 IH
2 2 2
+ Idc 2
IH + Idc Vdc2 (1.42)
Practically in power systems dc components are negligible. Therefore neglecting the contribution
of Vdc and Idc associated terms in (1.42), the following is obtained.
2
SN = I12 VH2 + V12 IH
2
+ VH2 IH
2
= DV2 + DI2 + SH 2
(1.43)
The terms DI and DV in (1.43) are known as apparent powers due to distortion in current and
voltage respectively. These are given below.
DV = I1 VH
DI = V1 IH (1.44)
These are further expressed in terms of THD components of voltage and current, as given below.
VH
T HDV =
V1
IH
T HDI = (1.45)
I1
From (1.45), the harmonic components of current and voltage are expressed below.
VH = T HDV V1
IH = T HDI I1 (1.46)
Using (1.44) and (1.46),
DV = V1 I1 T HDV = S1 T HDV
DI = V1 I1 T HDI = S1 T HDI
SH = VH IH = S1 T HDI T HDV (1.47)
Therefore using (1.43) and (1.47), SN could be expressed as following.
18
2
SN = S12 (T HDI2 + T HDV2 + T HDI2 T HDV2 ) (1.48)
SN ≈ S1 DI (1.49)
The above relationship shows that as the THD content in voltage and current increases, the non fun-
damental apparent power SN increases for a given useful transmitted power. This means there are
more losses and hence less efficient power network.
S2 = P 2 + N 2 (1.50)
This power includes both fundamental as well as non fundamental components, and is usually
computed by knowing active power (P ) and apparent power (S) as given below.
√
N = S2 − P 2 (1.51)
S 2 = P 2 + Q2 + D2 . (1.52)
Therefore,
p
D= S 2 − P 2 − Q2 . (1.53)
P1
pf1 = cos φ1 = (1.54)
S1
The fundamental power factor as defined above is also known as displacement power factor.
19
1.4.7 Power Factor
Power factor for the single phase system considered above is the ratio of the total real power (P )
to the total apparent power (S) as given by the following equation.
P
pf =
S
P 1 + PH
= p 2 2
S1 + SN
(1 + PH /P1 ) P1
= p (1.55)
1 + (SN /S1 )2 S1
Substituting SN from (1.48), the power factor can further be simplified to the following equation.
(1 + PH /P1 )
pf = p pf1 (1.56)
1 + T HDI2 + T HDV2 + T HDI2 T HDV2
Thus, we observe that the power factor of a single phase system depends upon fundamental (P1 )
and harmonic active power (PH ), displacement factor (DP F = pf1 ) and THDs in voltage and
current. Further, we note following points.
1. P/S is also called as utilization factor indicator as it indicates the usage of real power.
2. The term SN /S1 is used to decide the overall degree of harmonic content in the system.
3. The flow of fundamental power can be characterized by measurement of S1 , P1 , pf1 , and Q1 .
For a practical power system P1 >> PH and T HDV << T HDI , the above expression of power
factor is further simplified as given below.
pf1
pf = p (1.57)
1 + T HDI2
Example 1.3 Consider the following voltage and current in single phase system.
√ √
vs (t) = 230 2 sin(ωt) + 50 2 sin(3ωt − 30◦ )
√ √
i(t) = 2 + 10 2 sin(ωt − 30◦ ) + 5 2 sin(3ωt − 60◦ )
20
Solution: Here the source is non-sinusoidal and is feeding a non-linear load. The instantaneous
power is given by,
p(t) = v(t) i(t)
∞
X√ ∞
X √
p(t) = {Vdc + 2 Vn sin(nωt − φvn )} {Idc + 2 In sin(nωt − φin )}
n=1 n=1
(a) The active power ’P’ is given by,
1 T
Z
P = p(t) dt
T 0
= Pdc + V1 I1 cos φ1 + V2 I2 cos φ2 + ...... + Vn In cos φn (1.58)
= Pdc + P1 + PH
where,
φn = φin − φvn
Pdc = Vdc Idc
P1 = V1 I1 cos φ1
X∞
PH = Vn In cos φn
n=2
Here, Vdc = 0, V1 = 230 V, φv1 = 0, V3 = 50 V, φv3 = 30◦ , Idc = 2 A, I1 = 10 A, φi1 = 30◦ ,
I3 = 5 A, φi3 = 60◦ . Therefore, φ1 = φi1 − φv1 = 30◦ and φ3 = φi3 − φv3 = 30◦ .
Substituting these values in (1.58), the above equation gives,
where,
q
VH = V22 + V32 + ....Vn2
q
IH = I22 + I32 + .....In2
21
Substituting the values of voltage and current components, the apparent power S is computed as
following.
√ √
S = 0 + 2302 + 502 22 + 102 + 52
= 235.37 × 11.357 = 2673.31 VA
P 2208.36
pf = = = 0.8261 lag
S 2673.31
∞ √
X 2Vn
v(t) = Vdc + sin(nωt − φvn )
n=1
n2
√
with Vdc = 10 V, Vn /n2 = 230 2/n2 and φvn = 0 f or n = 1, 3, 5, 7, . . .
∞ √
X 2In
i(t) = Idc + sin(nωt − φin ).
n=1
n
(a) Plot instantaneous power p(t), pactive (t), preactive (t), Pdc , and prest (t).
(d) Compute S, S1 , SH , N, D.
22
∞ √ ! ∞ √ !
X 230 2 X 20 2
p(t) = v(t) i(t) = 10 + 2
sin(nωt) 2+ sin n(ωt − 300 )
n=1,3,5
n n=1,3,5
n
∞ √ ∞ √
X 20 2 0
X 230 2
= |{z}
20 + 10 sin n(ωt − 30 ) + 2 sin(nωt)
n=1,3,5
n n=1,3,5
n2
I
| {z } | {z }
II III
∞ √ ! ∞ √ !
X 230 2 X 20 2
+ 2
sin(nωt) sin n(ωt − 300 )
n=1,3,5
n n=1,3,5
n
| {z }
IV
∞ √ ∞ √
X 200 2 X 460 2
= |{z}
20 + sin n(ωt − 300 ) + 2
sin(nωt)
n=1,3,5
n n=1,3,5
n
I
| {z } | {z }
II III
∞
X 4600
+ 3
(cos(30o n)(1 − cos 2nωt) − sin (2nωt) sin(30o n))
n=1,3,5
n
| {z }
IV A
∞ √ ! ∞ √ !
X 230 2 X 20 2
+ 2
sin nωt sin h(ωt − 300 )
n=1,3,5
n h=1,3,5;h6=n
h
| {z }
IV B
a. Computation of p(t), pactive (t), preactive (t), Pdc ., and prest (t)
pdc−dc (t) = 20 W
∞
X 4600
pactive (t) = 3
cos n300 (1 − cos 2nωt)
n=1,3,5
n
∞
X 4600
preactive (t) = − 3
sin(n300 ) sin(2nωt)
n=1,3,5
n
∞ √ ∞ √
X 200 2 0
X 460 2
prest (t) = sin n(ωt − 30 ) + sin(nωt)
n=1,3,5
n n=1,3,5
n2
∞ √ ! ∞ √ !
X 230 2 X 20 2
+ 2
sin nωt sin h(ωt − 300 )
n=1,3,5
n h=1,3,5;h6=n
h
23
b. Computation of P, P1 , PH
Z T
1
P = p(t)dt
T 0
∞
X 4600
= 20 + 3
cos(30o n)
n=1,3,5
n
∞
X 4600
= 20 + 4600 cos 300 + 3
cos(30o n)
n=3,5,7...
n
= 20 + 3983.71 + (−43.4841)
= Pdc + P1 + PH
Thus,
Active power contributed by dc components of voltage and current, Pdc = 20 W.
Active power contributed by harmonic frequency components of voltage and current, PH = −43.4841
W.
c. Computation of Q, Q1 , QH
∞
X 4600
Q = 3
sin(30o n)
n=1,3,5
n
∞
0
X 4600
= 4600 sin 30 + 3
sin(30o n)
n=3,5,7...
n
= 2300 + 175.7548 VArs
= Q1 + QH
P∞ 3 o
The above implies that, Q1 = 4600 VArs and QH = n=3,5,7... (4600/n ) sin(30 n) = 175.7548
VArs.
24
The apparent power S is expressed as following.
q
Vrms = Vdc2 + V12 + V32 + V52 + V72 + V92 + ....
p
= 102 + 2302 + (230/32 )2 + (230/52 )2 + (230/72 )2 + (230/92 )2 + ....
= 231.87 V (up to n = 9)
q
2
Irms = Idc + I12 + I32 + I52 + I72 + I92 + ....
p
= 22 + 202 + (20/3)2 + (20/5)2 + (20/7)2 + (20/9)2 + ....
= 21.85 A (up to n = 9)
q
VH = V32 + V52 + V72 + V92 + ....
p
= (230/32 )2 + (230/52 )2 + (230/72 )2 + (230/92 )2 + ....
= 27.7 V (up to n = 9)
q
IH = I32 + I52 + I72 + I92 + ....
p
= (20/3)2 + (20/5)2 + (20/7)2 + (20/9)2 + ....
= 8.57 A (up to n = 9).
25
200
20
Voltage (v)
Current (A)
100
10
0
0
-100
-10
-200
-20
0 0.005 0.01 0.015 0.02 0.025 0.03 0.035 0.04
0 0.005 0.01 0.015 0.02 0.025 0.03 0.035 0.04
time (sec) time (sec)
2000 3000
2000
0
1000
-2000
0
0 0.005 0.01 0.015 0.02 0.025 0.03 0.035 0.04 0 0.005 0.01 0.015 0.02 0.025 0.03 0.035 0.04
time (sec) time (sec)
1000
2000
500
0
0
-500
-1000
-2000
0 0.005 0.01 0.015 0.02 0.025 0.03 0.035 0.04 0 0.005 0.01 0.015 0.02 0.025 0.03 0.035 0.04
time (sec) time (sec)
3000
Non active power (VA)
1168
Total apparent power (VA)
2500
Avg. active power (W) 1167
2000
1000 1165
0 0.005 0.01 0.015 0.02 0.025 0.03 0.035 0.04 0 0.005 0.01 0.015 0.02 0.025 0.03 0.035 0.04
time (sec) time (sec)
References
[1] IEEE Group, “IEEE trial-use standard definitions for the measurement of electric power quan-
tities under sinusoidal, nonsinusoidal, balanced, or unbalanced conditions,” 2000.
[2] E. Watanabe, R. Stephan, and M. Aredes, “New concepts of instantaneous active and reactive
powers in electrical systems with generic loads,” IEEE Transactions on Power Delivery, vol. 8,
no. 2, pp. 697–703, 1993.
[3] T. Furuhashi, S. Okuma, and Y. Uchikawa, “A study on the theory of instantaneous reactive
power,” IEEE Transactions on Industrial Electronics, vol. 37, no. 1, pp. 86–90, 1990.
[4] A. Ferrero and G. Superti-Furga, “A new approach to the definition of power components in
three-phase systems under nonsinusoidal conditions,” IEEE Transactions on Instrumentation
and Measurement, vol. 40, no. 3, pp. 568–577, 1991.
[5] J. Willems, “A new interpretation of the akagi-nabae power components for nonsinusoidal
three-phase situations,” IEEE Transactions on Instrumentation and Measurement, vol. 41,
no. 4, pp. 523–527, 1992.
26
THREE PHASE CIRCUITS: POWER
DEFINITIONS AND VARIOUS
COMPONENTS
In the following section, we shall study the various three-phase circuits such as balanced, un-
balanced, balanced and unbalanced harmonics and discuss their properties in details [1]–[5].
27
a a
b b
c c
and
√
ia (t) = 2I sin(ωt − φ)
√
ib (t) = 2I sin(ωt − 120◦ − φ) (2.2)
√
ic (t) = 2I sin(ωt + 120◦ − φ)
In (2.1) and (2.2) subscripts a, b and c are used to denote three phases which are balanced. Balanced
three-phase means that the voltage or current magnitude (V or I) are same for all three phases and
they have a phase shift of −120o and 120o . The currents are assumed to have φ degree lag with
their respective phase voltages. The balanced three phase system has certain interesting properties.
These will be discussed in the following section.
In above equation, pa (t), pb (t) and pc (t) are expressed similar to single phase system done previ-
ously. These are given below.
Adding three phase instantaneous powers given in (2.4), we get the three-phase instantaneous
power as below.
p(t) = 3 V I cos φ − V I cos φ{cos 2ωt + cos 2(ωt − 120o ) + cos 2(ωt + 120o )}
− V I sin φ{sin 2ωt + sin 2(ωt − 120o ) + sin 2(ωt + 120o )} (2.5)
28
p3φ (t) = p(t) = 3V I cos φ. (2.6)
This is quite interesting result. It indicates for balanced three-phase system, the total instantaeous
power is equal to the real power or average active power (P ), which is constant. This is the reason
we use 3-phase system. It does not involve the pulsating or oscillating components of power as in
case of single phase systems. Thus it ensures less VA rating for same amount of power transfer.
Here, total three-phase reactive power can be defined as sum of maximum value of preactive (t)
terms in (2.4). Thus,
Q = Qa + Qb + Qc = 3V I sin φ. (2.7)
Is there any attempt to define instantaneous reactive power q(t) similar to p(t) such that Q is
average value of that term q(t)?. H. Akagi et al. published paper [6], in which authors defined term
instantaneous reactive power. The definition was facilitated through αβ0 transformation. Briefly
it is described in the next subsection.
The abc coordinates and their equivalent αβ0 coordinates are shown in the Fig. 2.2 below.
vc
-j c
- c /2
- b /2 60
o O va
vb j b
j
v0 (t)
r √1 √1 √1
va (t)
2 2 −1
2
−1
2
vα (t) = 1 √2 2
√
vb (t) (2.11)
vβ (t) 3 3 − 3 vc (t)
0 2 2
v0 va
vα = [Aoαβ ] vb
vβ vc
The above is known as Clarke-Concordia transformation. Thus, va , vb and vc can also be expressed
in terms of v0 , vα and vβ by pre-multiplying (2.11) by matrix [A0αβ ]−1 , we have
va v0
vb = [A0αβ ]−1 vα
vc vβ
r 1 −1
√ √1 √1
2 2 2 2
[A0αβ ]−1 = [Aabc ] = 1 √ −1
2
−1
2
√
3 3 − 3
0 2
1 2
r √
2
1 0
2 √1 −1 √3
[A0αβ ]−1 = 2 2 2
√
T
= [A0αβ ] = [Aabc ] (2.12)
3 1 −1 − 3
√
2 2 2
Similarly, we can write down instantaneous symmetrical transformation for currents, which is
given below.
r 1
√1 √1
i0 √ i
2 2 2 a
iα = 2 1 −1 −1 ib (2.13)
√2 √2
iβ 3 3 − 3 ic
0 2 2
Now based on ’0αβ’ transformation, the instantaneous active and reactive powers are defined as
follows. The three-phase instantaneous power p(t) is expressed as the dot product of 0αβ compo-
nents of voltage and currents such as given below.
30
p(t) = vα iα + vβ iβ + v0 i0
" √ √
2 vb vc ib ic 3 3
= va − − ia − − + (vb − vc ) (ib − ic )
3 2 2 2 2 2 2
1 1
+ √ (va + vb + vc ) √ (ia + ib + ic )
3 3
= va ia + vb ib + vc ic (2.14)
Now what about instantaneous reactive power? Is there any concept defining instantaneous reactive
power? In 1983-84,authors H.akagi have attempted to define instantaneous reactive power using
stationary αβ0 frame, as illustrated below. In [6], the instantaneous reactive power q(t) is defines
as the cross product of two mutual perpendicular quantities, such as given below.
q(t) = vα × iβ + vβ × iα
q(t) = vα iβ − vβ iα
" √ √ #
2 vb vc 3 3 ib ic
= va − − (ib − ic ) − (vb − vc ) ia − −
3 2 2 2 2 2 2
√ h
2 3 vb vc vb vc vb vc vb vc i
= (−vb + vc ) ia + va − − + − ib + −va + + + − ic
3 2 2 2 2 2 2 2 2 2
1
= − √ [(vb − vc ) ia + (vc − va ) ib + (va − vb ) ic ]
3 √
= − [vbc ia + vca ib + vab ic ] / 3 (2.15)
As a check for power invariance, we shall compute the energy content of voltage signals in two
transformations. The energy associated with the abc0 system is given by (va2 + vb2 + vc2 ) and the
energy associated with the αβ0 components is given by v02 + vα2 + vβ2 . The two energies must
be equal to ensure power invariance in two transformations. It is proved below. Using, (2.11) and
31
squares of the respective components, we have the following.
"r #2
2 vb vc
vα2 = va − −
3 2 2
vb2 vc2 2va vb 2vb vc 2va vc
2
vα2 = 2
v + + − + −
3 a 4 4 2 4 2
2 2
2 2 vb v 2va vb vb vc 2va vc
= va + + c − + − (2.17)
3 6 6 3 3 3
"√ r #2
3 2
vβ2 = (vb − vc )
2 3
1 2
vb + vc2 − 2vb vc
=
2
v2 v2
= b + c − vb vc (2.18)
2 2
2 2
vα2 + vβ2 = va + vb2 + vc2 − vc vb − vb vc − vc va
3 2
va vb2 vc2 2va vb 2vb vc 2va vc
2 2 2
= va + vb + vc − + + + + +
3 3 3 3 3 3
1
= va2 + vb2 + vc2 − (va + vb + vc )2
3
2
2 2 2
1
= va + vb + vc − √ (va + vb + vc ) (2.19)
3
From the above it is implies that the energy associated with the two systems remain same instant to
instant basis. In general the instantaneous power p(t) remain same in both transformations. This
is proved below.
32
Using (2.14), following can be written.
p(t) = vα iα + vβ iβ + vo io
T
v0 i0
p(t) = vα iα
vβ iβ
T
va ia
= [Aabc ] vb [Aabc ] ib
vc ic
T
va ia
= vb [Aabc ]T [Aabc ] ib
vc ic
T
va ia
= vb [Aabc ]−1 [Aabc ] ib
vc ic
ia
= va vb vc ib
ic
= va ia + vb ib + vc ic (2.21)
33
Vc Vb
o
30
3 V
V ab
Va V0o
Vb
The above relationship between phase and line to line voltages is also illustrated in Fig. 2.3. For
the above three-phase system, the instantaneous power p(t) can be expressed using (2.21) and it is
equal to,
p(t) = va ia + vb ib + vc ic
= vα iα + vβ iβ + v0 i0
= 3 V I cosφ (2.24)
1 √ √ √
q(t) = − √ [ 3 2V sin (ωt − 90o ) 2I sin (ωt − φ)
3
√ √ √
+ 3 2V sin (ωt + 150o ) 2I sin (ωt − 120o − φ)
√ √ √
+ 3 2V sin (ωt + 30o ) 2I sin (ωt + 120◦ − φ)]
= −V I [cos (90◦ − φ) − cos (2ωt − 90o − φ)
+ cos (90o − φ) − cos (2ωt − 30o − φ)
+ cos (90o − φ) − cos (2ωt + 150o − φ)]
= −V I [3 sin φ − cos (2ωt − φ + 30o ) − cos (2ωt − φ + 30o + 120o )
− cos (2ωt − φ + 30o − 120o )]
= −V I [3 sin φ − 0]
q(t) = −3V I sin φ (2.25)
The above value of instantaneous reactive power is same as defined by Budeanu’s [1] and is given
in equation (2.7). Thus, instantaneous reactive power given in (2.15) matches with the conven-
tional definition of reactive power defined in (2.7). However the time varying part of second terms
of each phase in (2.4) has no relevance with the definition given in (2.15).
Another interpretation of line to line voltages in (2.15) is that the voltages vab , vbc and vca have
34
90o phase shift with respect to voltages vc , va and vb respectively. These are expressed as below.
√
vab = 3vc ∠ − 90o
√
vbc = 3va ∠ − 90o (2.26)
√ o
vca = 3vb ∠ − 90
In above equation, vc ∠ − 90o implies that vc ∠ − 90o lags vc by 90o . Analyzing each term in
(2.15) contributes to,
√
vbc ia = 3va ∠ − 90◦ . ia
√ √ √
= 3 2V sin (ωt − 90◦ ) . 2I sin (ωt − φ)
√
= 3V I 2 sin (ωt − 90◦ ) . sin (ωt − φ)
√
= 3V I [cos (90◦ − φ) − cos (2ωt − 90◦ − φ)]
√
= 3V I [sin φ − cos {90◦ + (2ωt − φ)}]
√
= 3V I [sin φ + sin (2ωt − φ)]
√
= 3V I [sin φ + sin 2ωt cos φ − cos 2ωt sin φ]
√
vbc ia / 3 = V I [sin φ (1 − cos 2ωt) + cos φ sin 2ωt]
Similarly,
√
2π
vca ib / 3 = V I sin φ 1 − cos 2 ωt −
3
2π
+V I cos φ. sin 2 ωt −
3
√
2π
vab ic / 3 = V I sin φ 1 − cos 2 ωt +
3
2π
+V I cos φ. sin 2 ωt + (2.27)
3
Thus, we see that the role of the coefficients of sin φ and cos φ have reversed. Now if we take
average value of (2.27), it is not equal to zero but V I sin φ in each phase. Thus three-phase reactive
power will be 3V I sin φ. The maximum value of second term in (2.27) represents active average
power i.e., V I cos φ. However, this is not normally convention about the notation of the powers.
But, important contribution of this definition is that average reactive power could be defined as the
average value of terms in (2.27).
√
va = 2Va sin (ωt − φva )
√
vb = 2Vb sin (ωt − 120o − φvb ) (2.28)
√
vc = 2Vc sin (ωt + 120o − φvc )
35
and,
√
ia = 2Ia sin (ωt − φia )
√
ib = 2Ib sin (ωt − 120o − φib ) (2.29)
√
ic = 2Ic sin (ωt + 120o − φic )
For the above system, the three-phase instantaneous power is given by,
p3φ (t) = p(t) = va ia + vb ib + vc ic
√
= 2Va sin (ωt − φva ) sin (ωt − φia )
√ √
+ 2Vb sin (ωt − 120o − φvb ) 2Ib sin (ωt − 120o − φib ) (2.30)
√ √
+ 2Vc sin (ωt + 120o − φvc ) 2Ic sin (ωt + 120o − φic )
Simplifying above expression we get,
p3φ (t) = Va Ia cos φa {1 − cos (2ωt − 2φva )}
| {z }
pa,active
−V I sin φa sin (2ωt − 2φva )
| a a {z }
pa,reactive
+Vb Ib cos φb [1 − cos {2 (ωt − 120◦ ) − 2φvb }]
−Vb Ib sin φb sin {2 (ωt − 120◦ ) − 2φvb }
+Vc Ic cos φc [1 − cos {2 (ωt + 120◦ ) − 2φvc }]
−Vc Ic sin φc sin {2 (ωt + 120◦ ) − 2φvc } (2.31)
where φa = (φia − φva )
Therefore,
p3φ (t) = pa,active + pb,active + pc,active + pa,reactive + pb,reactive + pc,reactive
= pa + pb + pc + pea + peb + pec (2.32)
where,
pa = Pa = Va Ia cos φa
pb = Pb = Vb Ib cos φb (2.33)
pc = Pc = Vc Ic cos φc
and
pea = −Va Ia cos (2 ωt − φa − 2 φva )
peb = −Vb Ib cos (2 ωt − 240o − φb − 2 φvb ) (2.34)
pec = −Vc Ic cos (2ωt + 240 − φc − 2 φvc )
Also it is noted that,
pa + pb + p c = va ia + vb ib + vc ic = P (2.35)
36
and,
pea + peb + pec = −Va Ia cos(2ωt − φva − φib )
−Vb Ib cos {2(ωt − 120) − φvb − φib }
−Vc Ic cos {2(ωt + 120) − φvc − φic }
6= 0
This implies that, we no longer get advantage of getting constant power, 3V I cos φ from interaction
of three-phase voltages and currents. Now, let us analyze three phase instantaneous reactive power
q(t) as per definition given in (2.15).
1
q(t) = − √ (vb − vc )ia + (vc − va )ib + (va − vb )ic
3
2 h
= − √ {Vb sin(ωt − 120o − φvb ) − Vc sin(ωt + 120o − φvc )} Ia sin(ωt − φia )
3
√
+ {Vc sin(ωt + 120o − φvc ) − Va sin(ωt − φva )} 2Ib sin(ωt − 120o − φib ) (2.36)
o o
√ o
i
+{Va sin(ωt − 120 − φva ) − Vb sin(ωt − 120 − φvb )} 2Ic sin(ωt + 120 − φic )
Z T
1 1 h
q(t)dt = − √ Vb Ia cos(φia − φvb − 120o )
T 0 3
−Vc Ia cos(φia − φvc + 120o )
+Vc Ib cos(φib + 240o − φvc )
−Va Ib cos(φib − 120o − φva )
+Va Ic cos(φic − 120o − φva )
i
o
−Vb Ic cos(φic − 240 − φvb )
= q a (t) + q b (t) + q c (t)
6 = Va Ia sin φa + Vb Ib sin φb + Vc Ic sin φc (2.38)
Hence the definition of instantaneous reactive power does not match to that defined by Budeanue’s
reactive power [1] for three-phase unbalanced circuit. If only voltages or currents are distorted, the
37
above holds true as given below. Let us consider that only currents are unbalanced, then
√
va (t) = 2V sin(ωt)
√
vb (t) = 2V sin(ωt − 120◦ ) (2.39)
√ ◦
vc (t) = 2V sin(ωt + 120 )
and
√
ia (t) = 2Ia sin(ωt − φa )
√
ib (t) = 2Ib sin(ωt − 120o − φb ) (2.40)
√ o
ic (t) = 2Ic sin(ωt + 120 − φc )
And the instantaneous reactive power is given by,
q(t) = − √13 [vbc ia + vca ib + vab ic ]
√ √ √
= − √13 [ 3 va ∠−π/2 ia + 3 vb ∠ − π/2 ib + 3 vc ∠ − π/2 ic ]
√ √
= −[√ 2V sin(ωt − π/2) 2Ia sin(ωt √ − φia )
+√2V sin(ωt − 120 − π/2)√ 2Ib sin(ωt − 120o − φib )
o
Z T
1
Q= q(t)dt = −(V Ia sin φia + V Ib sin φib + V Ic sin φic ) (2.41)
T 0
qe(t) = V Ia sin(2ωt − φia ) + V Ib sin(2ωt − 240o − φib ) + V Ic sin(2ωt + 240o − φic ) (2.42)
which is not similar to what is being defined as reactive component of power in (2.4).
38
a concept of symmetrical components introduced by C. L. Fortescue, will be discussed. In 1918,
C. L Fortescue, wrote a paper [7] presenting that an unbalanced system of n-related phasors can
be resolved into n system of balanced phasors, called the symmetrical components of the original
phasors. The n phasors of each set of components are equal in length and the angles. Although,
the method is applicable to any unbalanced polyphase system, we shall discuss about three phase
systems.
For the discussion of symmetrical components, a complex operator denoted as a is defined as,
a + a2 + a3 = 0. (2.43)
a 1120
o
o a 1o
3 o
a 2 1 120o
Fig. 2.4 Phasor representation of a, a2 and a3
These quantities i.e., a, a2 and a3 = 1 also represent three phasors which are shifted by 120o
from each other. This is shown in Fig. 2.4.
Knowing the above and using Fortescue theorem, three unbalanced phasor of a three phase un-
balanced system can be resolved into three balanced system phasors.
1. Positive sequence components are composed of three phasors, equal in magnitude, phase shift
39
of −120o and 120o between phases with phase sequence same to that of the original phasors.
2. Negative sequence components consist of three phasors equal in magnitude, phase shift of
120o and −120o between phases with phase sequence opposite to that of the original phasors.
3. Zero sequence components consist of three phasors equal in magnitude with zero phase shift
from each other.
V a = V a+ + V a− + V a0
V b = V b+ + V b− + V b0 (2.44)
V c = V c+ + V c− + V c0
Graphically, these are represented in Fig. 2.5. Thus if we add the sequence components of each
phase vectorially, we shall get V a , V b and V s as per (2.44). This is illustrated in Fig. 2.6.
V c
V b
Va0
Vb 0
V a Vc0
Va
V c
(a) (b) (c)
V b
Fig. 2.5 Sequence components (a) positive sequence (b) negative sequence (c) zero sequence
Now knowing all these preliminaries, we can proceed as following. Let V a+ be a reference phasor,
therefore V b+ and V c+ can be written as,
V b+ = a2 V a+ = V a+ ∠ − 120◦
V c+ = aV a+ = V a+ ∠120◦ (2.45)
40
V c
Vc0
V c
Vc V a V a
Va0
o Va
Vb
Vb Vb
Vb 0
Fig. 2.6 Unbalanced phasors as vector sum of positive, negative and zero sequence phasors
V b− = aV a− = V a− ∠120◦
V c− = a2 V a− = V a− ∠ − 120◦ (2.46)
The zero sequence components have same magnitude and phase angle and therefore these are
expressed as,
V b0 = V c0 = V a0 (2.47)
V a = V a0 + V a+ + V a− (2.48)
V b = V b0 + V b+ + V b−
= V a0 + a2 V a+ + a V a− (2.49)
V c = V c0 + V c+ + V c−
= V a0 + a V a+ + a2 V a− (2.50)
41
1 1 1
Premultipling by inverse of matrix [Asabc ] = 1 a2 a , the symmetrical components are
1 a a2
expressed as given below.
V a0 1 1 1 Va
V a+ = 1 1 a a2 V b (2.52)
3 1 a2 a
V a− Vc
Va
= [A012 ] V b
Vc
The symmetrical transformation matrices A012 and Asabc are related by the following expression.
From (2.52), the symmetrical components can therefore be expressed as the following.
1
V a0 = (V a + V b + V c )
3
1
V a+ = (V a + aV b + a2 V c ) (2.54)
3
1
V a− = (V a + a2 V b + aV c )
3
The other component i.e., V b0 , V c0 , V b+ , V c+ , V b− , V c− can be found from V a0 , V a+ , V a+ . It
should be noted that quantity V a0 does not exist if sum of unbalanced phasors is zero. Since sum
of line to line voltage phasors i.e., V ab +V bc +V ca = (V a −V b )+(V b −V c )+(V c −V a ) is always
zero, hence zero sequence voltage components are never present in the line voltage, regardless of
amount of unbalance. The sum of the three phase voltages, i.e., V a + V b + V c is not necessarily
zero and hence zero sequence voltage exists.
Similarly sequence components can be written for currents. Denoting three phase currents by
I a , I b , and I c respectively, the sequence components in matrix form are given below.
I a0 1 1 1 Ia
I a+ = 1 1 a a2 I b (2.55)
3 1 a2 a
I a− Ic
Thus,
1
I a0 = (I a + I b + I c )
3
1
I a+ = (I a + aI b + a2 I c )
3
42
1
I a− = (I a + a2 I b + aI c )
3
In three-phase, 4-wire system, the sum of line currents is equal to the neutral current (I n ). thus,
In = Ia + Ib + Ic
= 3I a0 (2.56)
This current flows in the fourth wire called neutral wire. Again if neutral wire is absent, then zero
sequence current is always equal to zero irrespective of unbalance in phase currents. This is illus-
trated below.
a a
a a
b b
b b
c c
c c
(a) (b)
Fig. 2.7 Various three phase systems (a) Three-phase three-wire system (b) Three-phase four-wire system
In 2.7(b), in may or may not be zero. However neutral voltage (VN n ) between the system and
load neutral is always equal to zero. In 2.7(a), there is no neutral current due to the absence of the
neutral wire. But in this configuration the neutral voltage, VN n , may or may not be equal to zero
depending upon the unbalance in the system.
43
Solution Using (2.54), sequence components are computed. These are:
1
V a0 = (V a + V b + V c )
3
= 31.91∠ − 50.48o V
1
V a+ = (V a + aV b + a2 V c )
3
= 104.16∠4.7o V
1
V a− = (V a + a2 V b + aV c )
3
= 28.96∠146.33o V
If you find energy content of two frames that is abc and 012 system, it is found to be constant.
The term S v is referred as vector or geometric apparent power. The difference between will be
given in the following. The transformation matrix [Asabc ] has following properties.
44
The matrix, [I], is identity matrix. Using (2.58), (2.57) can be written as the following.
T ∗
V a0 I a0
S v = P + jQ = V a+ 3[I]I a+
V a− I a−
T ∗
V a0 I a0
= 3 V a+
I a+
V a− I a−
∗ ∗ ∗
S v = P + jQ = V a I a + V b I b + V c I c
∗ ∗ ∗
= 3 [V a0 I a0 + V a+ I a+ + V a− I a− ] (2.59)
Equation (2.59) indicates that power invariance holds true in both abc and 012 components. But,
this is true on phasor basis. Would it be true on the time basis? In this context, concept of instanta-
neous symmetrical components will be discussed in the latter section. The equation (2.59) further
implies that,
S v = P + jQ = 3 [ (Va0 Ia0 cos φa0 + Va+ Ia+ cos φa+ + Va− Ia− cos φa− )
+j(Va0 Ia0 sin φa0 + Va+ Ia+ sin φa+ + Va− Ia− sin φa− ) ] (2.60)
The power terms in (2.60) accordingly form positive sequence, negative sequence and zero se-
quence powers denoted as following. The positive sequence power is given as,
P + = Va+ Ia+ cos φa+ + Vb+ Ib+ cos φb+ + Vc+ Ic+ cos φc+
= 3Va+ Ia+ cos φa+ . (2.61)
Negative sequence power is expressed as,
P − = 3Va− Ia− cos φa− . (2.62)
The zero sequence power is
P 0 = 3Va0 Ia0 cos φa0 . (2.63)
45
Here, positive sequence, negative sequence and zero sequence apparent powers are denoted as the
following.
+
p
S + = |S | = P +2 + Q+2 = 3Va+ Ia+
+
p
S − = |S | = P −2 + Q−2 = 3Va− Ia−
+
p
S 0 = |S | = P 02 + Q02 = 3Va0 Ia0 (2.66)
SA = |S a | + |S b | + |S c |
= |Pa + jQa | + |Pb + jQb | + |Pc + jQc | (2.68)
p q p
= Pa2 + Q2a + Pb2 + Q2b + Pc2 + Q2c
Based on these two definitions of the apparent powers, the power factors are defined as the follow-
ing.
P
Vector apparent power = pfv = (2.70)
Sv
P
Arithematic apparent power = pfA = (2.71)
SA
46
Example 2.2 Consider a 3-phase 4 wire system supplying resistive load, shown in Fig. 2.8
below. Determine power consumed by the load and feeder losses.
r jx a
a'
Ia R
r jx Va
' b
Ib
r jx Vb c
c'
Ic
r jx Vc
'
n
n
In
√
( 3V )2 3V 2
Power dissipated by the load = =
√ R R
3V Va−Vb
The current flowing in the line = =| |
R R
and I b = −I a
√ !2 √ !2
3V 3V
Therefore losses in the feeder = ×r+ ×r
R R
r 3 V 2
=2
R R
Now, consider another example of a 3 phase system supplying 3-phase load, consisting of three
resistors (R) in star as shown in the Fig. 2.9. Let us find out above parameters.
2
V 3V 2
Power supplied to load = 3 ×R=
R R
2
r 3V 2
V
Losses in the feeder = 3 ×r =
R R R
Thus, it is interesting to see that power dissipated in the unbalanced system is twice the power loss
in balanced circuit. This leads to conclusion that power factor in phases would become less than
unity, while for balanced circuit, the power factor is unity. Power analysis of unbalanced circuit
shown in Fig. 2.8 is given below.
47
r jx a R
a'
Ia
r jx Va b R
b' n
Ib
r jx Vb c R
c'
Ic
r jx Vc
n'
In
√
Va−Vb V ab 3 Va
The current in phase-a, I a = = = ∠30◦
R √ R R
3V
The current in phase-b, I b = −I a = ∠(30 − 180)o
√ R
3V
= ∠ − 150o
R
The current in phase-c and neutral are zero, I c = I n = 0
The phase active and reactive and apparent powers are as following.
√
◦ 3
Pa = Va Ia cos φa = V I cos 30 = VI
2
1
Qa = Va Ia sin φa = V I sin 30◦ = VI
2
Sa = Va Ia = V I
√
◦ 3
Pb = Vb Ib cos φb = V I cos(−30) = VI
2
1
Qb = Vb Ib sin φb = V I sin(−30)◦ = − V I
2
Sb = Vb Ib = V I
Pc = Qc = Sc = 0
√
3 √
Thus total active power P = Pa + Pb + Pc = 2 × V I = 3V I
√ 2
√ 3V
= 3V
R
3V 2
P =
R
Total reactive power Q = Qa + Qb + Qc = 0
48
p
The vector apparent power, Sv = P 2 + Q2 = 3 V 2 /R = P √
The arithmetic apparent power, SA = Sa + Sb + Sc = 2 V I = (2/ 3) P
For balance load SA = SV , therefore, pfA = pfV = 1.0. Thus for three-phase electrical cir-
cuits, the following holds true.
pfA ≤ pfV (2.72)
The equivalent three-phase unbalanced and balanced circuits with same power output and losses
are shown in Fig. 2.10. From these figures, to maintain same losses,
r jx Va Ra r jx Re
a' a'
Ia Iea
r jx Vb Rb r jx Vea Re
'
b n b' n
Ib Ieb
r jx Vc Rc r jx Veb Re
c' c'
Ic Iec
r jx Vn r jx Vec
'
n n'
(a) In (b) In 0
Fig. 2.10 (a) Three-phase with unbalanced voltage and currents (b) Effective equivalent three-phase system
50
2.3.2 Positive Sequence Powers and Unbalance Power
The unbalance power Su can be expressed in terms of fundamental positive sequence powers P + ,
Q+ and S + as given below.
q
Su = Se2 − S + 2 (2.77)
2 2 2
where S + = 3 V + I + and S + = P + + Q+ .
In this case,
Sa = Sb = Sc ,
Pa = P b = Pc , (2.80)
Qa = Qb = Qc ,
Da = Db = Dc .
In above the terms Da , Db and Dc are known as distortion powers in phase-a, b, c respectively. The
definition of The distortion power, D, is given in Section 1.4.5. The above equation suggests that
such a system has potential to produce significant additional power loss in neutral wire and ground
path.
51
2.4.1 Neutral Current
The neutral current for three-phase balanced system with harmonics can be given by the following
equation.
in = ia + i b + i c
√
= 2 [ Ia1 sin (wt − β1 ) + Ia2 sin (2wt − β2 ) + Ia3 sin (3wt − β3 )
+Ia1 sin (wt − 120o − β1 ) + Ia2 sin (2wt − 240o − β2 ) + Ia3 sin (3wt − 360o − β3 )
+Ia1 sin (wt + 120o − β1 ) + Ia2 sin (2wt + 240o − β2 ) + Ia3 sin (3wt + 360o − β3 )
The RMS value of the current in neutral wire is therefore given by,
" ∞ #1/2
X
In = 3 In2 . (2.83)
n=3,6,..
Due to dominant triplen harmonics in electrical loads such as UPS, rectifiers and other power
electronic based loads, the current rating of the neutral wire may be comparable to the phase wires.
It is worth to mention here that all harmonics in three-phase balanced systems can be catego-
rized in three groups i.e., (3n + 1), (3n + 2) and 3n (for n = 1, 2, 3, ...) called positive, nega-
tive and zero sequence harmonics respectively. This means that balanced fundamental, 4th, 7th
10th,... form positive sequence only. Balanced 2nd, 5th, 8th, 11th,... form negative sequence only
and the balanced triplen harmonics i.e. 3rd, 6th, 9th,... form zero sequence only. But in case of
unbalanced three-phase systems with harmonics, (3n + 1) harmonics may start forming negative
and zero sequence components. Similarly, (3n + 2) may start forming positive and zero sequence
components and 3n may start forming positive and negative sequence components.
52
vab (t) = va (t) − vb (t)
∞ ∞
X √ X √
= 2Vn sin(n ωt − αn ) − 2Vn sin(n (ωt − 120o ) − αn )
n=1 n=1
∞ ∞
X √ X √
= 2Vn sin(n ωt − αn ) − 2Vn sin((n ωt − αn ) − n × 120o )
n=1 n=1
∞
X √
= 2Vn [sin(n ωt − αn ) − sin(n ωt − αn ) cos(n × 120o )
n=1
+ cos(n ωt − αn ) sin(n × 120o )]
∞
X √
= 2Vn [sin(n ωt − αn ) − sin(n ωt − αn ) (−1/2)
n6=3,6,9...
√ i
+ cos(n ωt − αn ) (± 3/2)
∞
√ X h √ i
= 2 Vn (3/2) sin(n ωt − αn ) + (± 3/2) cos(n ωt − αn )
n6=3,6,9...
∞
√ √ X h√ i
= 3 2 Vn ( 3/2) sin(n ωt − αn ) + (±1/2) cos(n ωt − αn ) (2.84)
n6=3,6,9...
√
Let 3/2 = rn cos φn and ±1/2 = rn sin φn . This impliles rn = 1 and φn = ±30o . Using this,
equation (2.84) can be written as follows.
∞
√ √ X
vab (t) = 3 2 Vn [sin(n ωt − αn ± 30o )] . (2.85)
n6=3,6,9...
In equations (2.84) and (2.85), vab = 0 for n = 3, 6, 9, . . . and for n = 1, 2, 4, 5, 7, . . ., the ± sign
of 1/2 or sign of 300 changes alternatively. Thus it is observed that triplen harmonics are missing
in the line to line voltages, inspite of their presence in phase voltages for balanced three-phase
system with harmonics. Thus the following identity hold true for this system,
√
VLL ≤ 3 VLn (2.86)
√
3 VLL I ≤ 3 VLn I. (2.87)
In above equation, I refers the rms value of the phase current. For above case, Ia = Ib = Ic = I
and In = 3 ∞ 2
P
n=3,6,9... In . Therefore, effective rms current, Ie is given by the following.
53
s P∞ 2
3 I2 + 3 n=3,6,9... In
Ie =
3
v
u ∞
X
In 2
u
= tI 2 + (2.88)
n=3,6,9...
≥I
54
q
Ie = (Ia2 + Ib2 + Ic2 )/3
= I (2.95)
Therefore √
Se = S = 3Vll I (2.96)
For a four-wire system, Ve is same is given (2.94) and Ie is given by (2.88). Therefore, the
effective apparent power is given below.
√
3Vll I ≤ 3 Vln Ie (2.97)
The above implies that,
Se ≥ SA . (2.98)
Therefore, it can be further concluded that,
pfe (= P/Se ) ≤ pfA (= P/SA ). (2.99)
∞
X √
va (t) = 2Van sin(n ωt − αan )
n=1
∞
X √
vb (t) = 2Vbn sin {n (ωt − 120o ) − αbn } (2.100)
n=1
∞
X √
vc (t) = 2Vcn sin {n (ωt + 120o ) − αcn }
n=1
55
For the above voltages and currents in three-phase system, instantaneous power is given as follow-
ing.
In (2.102), each phase power can be found using expressions derived in Section 1.4 of Unit 1. The
direct result is written as following.
∞
X ∞
X
pa (t) = Van Ian cos φan {1 − cos(2nωt − 2αan )} − Van Ian sin φan cos(2nωt − 2αan )
n=1 n=1
∞
! ∞
!
X √ X √
+ 2Van sin(nωt − αan ) 2Iam sin(mωt − βam )
n=1 m=1, m6=n
∞
X X∞
= Pan {1 − cos(2nωt − 2αan )} − Qan cos(2nωt − 2αan )
n=1 n=1
∞
! ∞
!
X √ X √
+ 2Van sin(nωt − αan ) 2Iam sin(mωt − βam ) (2.103)
n=1 m=1, m6=n
In the above equation, φan = (βan − αan ). Similarly, for phases b and c, the instantaneous
power is expressed as below.
∞
X ∞
X
o
pb (t) = Pbn [1 − cos {2n(ωt − 120 ) − 2αbn }] − Qbn cos {2n(ωt − 120o ) − 2αbn }
n=1 n=1
∞
! ∞
!
X √ X √
+ 2Vbn sin {n(ωt − 120o ) − αbn } 2Ibm sin {m(ωt − 120o ) − βbm }
n=1 m=1, m6=n
(2.104)
56
and
∞
X ∞
X
o
pc (t) = Pcn [1 − cos {2n(ωt + 120 ) − 2αcn }] − Qcn cos {2n(ωt + 120o ) − 2αcn }
n=1 n=1
∞
! ∞
!
X √ X √
+ 2Vcn sin {n(ωt + 120o ) − αcn } 2Icm sin {m(ωt + 120o ) − βcm }
n=1 m=1, m6=n
(2.105)
From equations (2.103), (2.104) and (2.105), the real powers in three phases are given as follows.
∞
X
Pa = Van Ian cos φan
n=1
∞
X
Pb = Vbn Ibn cos φbn (2.106)
n=1
X∞
Pc = Vcn Icn cos φcn
n=1
∞
X
Qa = Van Ian sin φan
n=1
∞
X
Qb = Vbn Ibn sin φbn (2.107)
n=1
X∞
Qc = Vcn Icn sin φcn
n=1
Therefore, the total active and reactive powers are computed by summing the phase powers using
equations (2.106) and (2.107), which are given below.
∞
X
P = P a + Pb + Pc = (Van Ian cos φan + Vbn Ibn cos φbn + Vcn Icn cos φcn )
n=1
= Va1 Ia1 cos φa1 + Vb1 Ib1 cos φb1 + Vc1 Ic1 cos φc1
X∞
+ (Van Ian cos φan + Vbn Ibn cos φbn + Vcn Icn cos φcn )
n=2
∞
X
= Pa1 + Pb1 + Pc1 + (Pan + Pbn + Pcn )
n=2
= P1 + PH (2.108)
57
and,
∞
X
Q = Qa + Qb + Qc = (Van Ian sin φan + Vbn Ibn sin φbn + Vcn Icn sin φcn )
n=1
= Va1 Ia1 sin φa1 + Vb1 Ib1 sin φb1 + Vc1 Ic1 sin φc1
X∞
+ (Van Ian sin φan + Vbn Ibn sin φbn + Vcn Icn sin φcn )
n=2
∞
X
= Qa1 + Qb1 + Qc1 + (Qan + Qbn + Qcn )
n=2
= Q1 + QH (2.109)
p
Sa = Pa2 + Q2a + Da2
q
Sb = Pb2 + Q2b + Db2 (2.110)
p
Sc = Pc2 + Q2c + Dc2
The three-phase arithmetic apparent power is arithmetic sum of Sa , Sb and Sc in the above equation.
This is given below.
SA = Sa + Sb + Sc (2.111)
The three-phase vector apparent power is given as following.
p
Sv = P 2 + Q2 + D2 (2.112)
Where P and Q are given in (2.108) and (2.109) respectively. The total distortion power D is given
as following.
D = Da + Db + Dc (2.113)
Based on above definitions of the apparent powers, the arithmetic and vector power factors are
given below.
P
pfA =
SA
P
pfv = (2.114)
Sv
From equations (2.111), (2.112) and (2.114), it can be inferred that
SA ≥ Sv
pfA ≤ pfv (2.115)
58
2.5.2 Effective Apparent Power
Effective apparent power (Se =3Ve Ie ) for the three-phase unbalanced systems with harmonics can
be found by computing Ve and Ie as following. The effective rms current (Ie ) can be resolved into
two parts i.e., effective fundamental and effective harmonic components as given below.
q
2 2
Ie = Ie1 + IeH (2.116)
Similarly,
q
Ve = 2
Ve12 + VeH (2.117)
Where
r
1 2
Ve1 = [3(Va1 + Vb12 + Vc12 ) + (Vab1
2 2
+ Vbc1 2
+ Vca1 )]
18
r
1 2 2 2 2 2 2
VeH = [3(VaH + VbH + VcH ) + (VabH + VbcH + VcaH )] (2.121)
18
For three-phase three-wire system, In = 0 = In1 = InH .
59
r
2 2 2
Ia1 + Ib1 + Ic1
Ie1 =
r 3
2 2 2
IaH + IbH + IcH
IeH = (2.122)
3
Similarly
r
2 2 2
Vab1 + Vbc1 + Vca1
Ve1 =
r 9
2 2 2
VabH + VbcH + VcaH
VeH = (2.123)
9
The expression for effective apparent power Se is given as following.
Se = 3 Ve Ie
q q
= 3 Ve12 + VeH 2 2
Ie1 2
+ IeH
q
= 9 Ve12 Ie1
2
+ (9Ve12 IeH
2 2 2
+ 9VeH 2 2
Ie1 + 9VeH IeH )
q
2 2
= Se1 + SeN (2.124)
In the above equation,
Se1 = 3 Ve1 Ie1 (2.125)
q
2
SeN = Se2 − Se1
q
2 2 2
= DeV + DeI + SeH
q
2 2
= 3 Ie1 VeH + Ve12 IeH
2 2 2
+ VeH IeH (2.126)
In equation (2.126), distortion powers DeI , DeV and harmonic apparent power SeH are given as
following.
DeI = 3Ve1 IeH
DeV = 3VeH Ie1 (2.127)
SeH = 3VeH IeH
By defining above effective voltage and current quantities, the effective total harmonic distortion
(T HDe ) are expressed below.
VeH
T HDeV =
Ve1
IeH
T HDeI = (2.128)
Ie1
Substituting VeH and IeH in (2.126),
q
2 2 2 2
SeN = Se1 T HDe1 + T HDeV + T HDeI T HDeV . (2.129)
60
In above equation,
DeI = Se1 T HDI
DeV = Se1 T HDV (2.130)
SeH = Se1 (T HDI )(T HDV ).
Using (2.124) and (2.129), the effective apparent power is given as below.
q q
2 2 2 2 2 2
Se = Se1 + SeN = Se1 1 + T HDeV + T HDeI + T HDeV T HDeI (2.131)
Based on above equation, the effective power factor is therefore given as,
P P1 + P H
pfe = = p
Se Se1 1 + T HDeV2 2
+ T HDeI 2
+ T HDeV 2
T HDeI
(1 + PH /P1 ) P1
= p 2 2 2 2 S
1 + T HDeV + T HDeI + T HDeV T HDeI e1
(1 + PH /P1 )
= p 2 2 2 2
pfe1 (2.132)
1 + T HDeV + T HDeI + T HDeV T HDeI
Practically, the THDs in voltage are far less than those of currents THDs, therefore T HDeV <<
T HDeI . Using this practical constraint and assuming PH << P1 , the above equation can be
simplified to,
pfe1
pfe ≈ p 2
(2.133)
1 + T HDeI
In the above context, their is another useful term to denote unbalance of the system. This is
defined as fundamental unbalanced power and is given below.
q
SU 1 = 2
Se1 − (S1+ )2 (2.134)
Where, S1+ is fundamental positive sequence apparent power, which is given below.
q
+
S1 = (P1+ )2 + (Q+
1)
2 (2.135)
Example 2.3 Consider the following three-phase system. It is given that voltages V a , V b and V c
are balanced sinusoids with rms value of 220 V. The feeder impedance is rf +jxf = 0.02+j0.1 Ω.
The unbalanced load parameters are: RL = 12 Ω and XL = 13 Ω. Compute the following.
a. The currents in each phase, i.e., I a , I b and I c and neutral current, I n .
61
r f jx f
va Va
Ia
XL
vb Vb
LOAD
Ib
vc Vc
Ic RL
vn Vn
In
Solution:
a. Computation of currents
√
va (t) = 220 2 sin (ωt)
√
vb (t) = 220 2 sin (ωt − 120◦ )
√
vc (t) = 220 2 sin (ωt + 120◦ )
√
vab (t) = 220 6 sin (ωt + 30◦ )
Therefore,
√
220 3∠30
Ia = ◦
= 29.31∠−60◦ A
13∠90
Ib = −I a = −29.311∠−60◦ = 29.31∠120◦ A
220∠120◦
Ic = = 18.33∠120◦ A.
12
Thus, the instantaneous expressions of phase currents can be given as following.
b. Computation of losses
62
The losses occur due to resistance of the feeder impedance. These are computed as below.
Similarly,
∗
S b = V b I b = 220∠−120◦ × 29.31∠60◦ = −3224.21 + j5584.49
implies that, Pb = −3224.1 W, Qb = 5584.30 VAr
For phase-c,
∗
S c = V c I c = 220∠120◦ × 18.33∠−120◦ = 4032.6 + j0
implies that, Pc = 4032.6 W, Qc = 0 VAr
The arithmetic, vector and effective apparent powers are computed as below.
Sv = |Sa + Sb + Sc |
= |4032.6 + j11168.6| = |11874.32∠70.14| = 11874.32 VA
r
Ia2 + Ib2 + Ic2 + In2
Se = 3Ve Ie = 3 × 220 ×
r 3
29.31 + 29.31 + 18.332 + 18.332
2 2
= 3 × 220 × = 3 × 220 × 28.22
3
= 18629.19 VA
63
Based on the above apparent powers, the arithmetic, vector and effective apparent power factors
are computed as below.
P3−phase 4032.6
pfA = = = 0.2382
SA 16928.84
P3−phase 4032.6
pfv = = = 0.3396
Sv 11874.32
P3−phase 4032.6
pfe = = = 0.2165
Se 18629.19
In the above computation, the effective voltage and current are found as given in the following.
r
Va2 + Vb2 + Vc2
Ve = = 220 V
3
r
Ia2 + Ib2 + Ic2 + In2
Ie = = 28.226 A
3
Example 2.4 A 3-phase, 3-wire system is shown in Fig. 2.12. The 3-phase voltages are balanced
sinusoids with RMS value of 230 V. The 3-phase loads connected in star are given as following.
Za = 5 + j12 Ω, Zb = 6 + j8 Ω and Zc = 12 − j5 Ω.
b. Load active and reactive powers and power factor of each phase.
Vsa I la
Vsc I lc a
N
Vsb I lb
c Zb
Solution:
a. Computation of currents
64
Given that Za = 5 + j 12 Ω, Zb = 6 + j 8 Ω, Zc = 12 − j 5 Ω.
V sa = 230∠0◦ V
V sb = 230∠−120◦ V
V sc = 230∠120◦ V
1 V sa V sb V sc
V nN = 1 + +
Za
+ Z1b + Z1c Za Zb Zc
230∠0◦ 230∠−120◦ 230∠120◦
1
= 1 1 1 + +
5+j12
+ 6+j8 + 12−j5 5 + j12 6 + 8j 12 − j5
1
= ◦
31.23∠−164.50◦
0.2013∠−37.09
= −94.22 − j123.18 = 155.09∠−127.41◦ V
V sa − V nN 230∠0◦ − 155.09∠−127.41◦
I al = = = 26.67∠−46.56◦ A
Za 5 + j12
V sb − V nN 230∠−120◦ − 155.09∠−127.41◦
I bl = = = 7.88∠−158.43◦ A
Zb 6 + j8
V sc − V nN 230∠120 − 155.09∠−127.41◦
◦
I cl = = = 24.85∠116.3◦ A
Zc 12 − j5
∗
Sa = V a I a = 230∠0◦ × 26.67∠46.56◦ = 4218.03 + j4456.8
∗
Sb = V b I b = 230∠−120◦ × 7.88∠158.43◦ = 1419.82 + j1126.06
∗
Sc = V c I c = 230∠120◦ × 24.85∠−116.3◦ = 5703.43 + j368.11
implies that,
Pa = 4218.03 W, Qa = 4456.8 VAr
Pb = 1419.82 W, Qb = 1126.06 VAr
Pc = 5703.43 W, Qc = 368.11 VAr
65
Total three-phase active and reactive powers are given by,
P3−phase = Pa + Pb + Pc = 4218.03 + 1419.82 + 5703.43 = 11341.29 W
Q3−phase = Qa + Qb + Qc = 4456.8 + 1126.06 + 368.11 = 5950.99 VAr.
The power factors for phases a, b and c are given as follows.
Pa 4218.03 4218.03
pfa = =√ = = 0.6873 (lag)
|Sa | 2
4218.03 + 4456.8 2 6136.3
Pb 1419.82 1419.82
pfb = = 2 2
= = 0.7835 (lag)
|Sb | 1419.82 + 1126.06 1812.16
Pc 5703.43 5703.43
pfc = = 2 2
= = 0.9979 (lag)
|Sc | 5703.43 + 368.11 5715.30
c. Computation of various apparent powers and power factors
The arithmetic, vector and effective apparent powers are computed as below.
SA = |Sa | + |Sb | + |Sc |
= 6136.3 + 1812.16 + 5715.30 = 13663.82 VA
Sv = |Sa + Sb + Sc |
= |11341.29 + j5909.92| = 12807.78 VA
r
2
Ila + Ilb2 + Ilc2 + Iln
2
Se = 3Ve Ie = 3 × 230 ×
r 3
26.67 + 7.88 + 24.852 + 02
2 2
= 3 × 220 × = 3 × 230 × 21.53
3
= 14859.7 VA
The arithmetic, vector and effective apparent power factors are computed as below.
P3−phase 11341.29
pfA = = = 0.8300
SA 13663.82
P3−phase 11341.29
pfv = = = 0.8855
Sv 12807.78
P3−phase 11341.29
pfe = = = 0.7632
Se 14859.7
References
[1] IEEE Group, “IEEE trial-use standard definitions for the measurement of electric power quan-
tities under sinusoidal, nonsinusoidal, balanced, or unbalanced conditions,” 2000.
66
[2] E. Watanabe, R. Stephan, and M. Aredes, “New concepts of instantaneous active and reactive
powers in electrical systems with generic loads,” IEEE Transactions on Power Delivery, vol. 8,
no. 2, pp. 697–703, 1993.
[3] T. Furuhashi, S. Okuma, and Y. Uchikawa, “A study on the theory of instantaneous reactive
power,” IEEE Transactions on Industrial Electronics, vol. 37, no. 1, pp. 86–90, 1990.
[4] A. Ferrero and G. Superti-Furga, “A new approach to the definition of power components in
three-phase systems under nonsinusoidal conditions,” IEEE Transactions on Instrumentation
and Measurement, vol. 40, no. 3, pp. 568–577, 1991.
[5] J. Willems, “A new interpretation of the akagi-nabae power components for nonsinusoidal
three-phase situations,” IEEE Transactions on Instrumentation and Measurement, vol. 41,
no. 4, pp. 523–527, 1992.
[6] H. Akagi, Y. Kanazawa, and A. Nabae, “Instantaneous reactive power compensators compris-
ing switching devices without energy storage components,” IEEE Transactions on Industry
Applications, no. 3, pp. 625–630, 1984.
[7] C. L. Fortesque, “Method of symmetrical co-ordinates applied to the solution of polyphase
networks,” AIEE, 1918.
67
Three-Phase System
ItI
(a)
!I f
Uniform magnetic
field
0-866 E k
M
(b)
- 0 - 8 6 6 E,
rad/s
co
rad/s
8
120°
SJ20 (c) (d)
12C 120°
/120'
'V
Y
FIG. 5.1 (b, c, d).
(b)
B
R
S F Ys RF B
s Yp
FIG. 5.2.
and RF, Ys and YF, and Bs and BF. It should be noted that all coil
sides marked S (Start) are 120° apart and likewise all coil sides
marked F (Finish) are also 120° apart. These coils may be
172 ELECTRICAL ENGINEERING PRINCIPLES FOR TECHNICIANS
FIG. 5.3.
VRY = VRN+VNY-
But VNY = -VYN
VRN-VYN-
= 2xVRN
x^
Thus the line voltage is y/3 times the value of the phase voltage.
The other two line voltages may be found in a similar manner.
174 ELECTRICAL ENGINEERING PRINCIPLES FOR TECHNICIANS
'V
RY
(a)
(b)
^YN
FIG. 5.4.
VYB = V +V
YNNB
= v -v .
YN BN
VBR = V +V
= BNNR
VBN~~ VRN-
THREE-PHASE SYSTEM 175
These phasors are also shown in Fig. 5.4(a). The three line
voltages are seen to have a 120° phase displacement and as they are
all of the same magnitude, the general statement can be made that
in a balanced three-phase system,
h = /P.
line voltage
Phase voltage volts
(3
6600
volts
/3
= 3810 V.
Reference to Fig. 5.5(a) shows that the voltage across any one
phase is equal to the voltage between the corresponding lines.
Thus for a delta-connected circuit,
(a) b
FIG. 5.5.
• • IR IYR~~IRB'
THREE-PHASE SYSTEM 177
The current — IRB is in the opposite direction to IRB and when
—JRB is added to IYR
, the line current IR is obtained.
Thus the line current is the phasor difference between the
associated phase currents. For balanced conditions, it can be
shown by using the construction given in Fig. 5.4(a),
IL = 2xIPcos 30°
IB = IRB — IBY-
Right-hand junction: =
IYR + IY 1BY
. . Iy — IBY~IYR-
windings and cables, etc., are neglected, the line voltage is always
y/3 times the phase voltage for balanced or unbalanced loading
provided that there is a neutral conductor in the system. This
constitutes the three-phase, four-wire system. If there is no
neutral conductor, the system is described as being three-phase,
three-wire. When there is a balanced star-connected load on a
three-phase, three-wire system, the above voltage relationship still
holds but if the load is unbalanced, there is no fixed relationship
between the line and phase voltages. Generally, all the phase
voltages will be different.
V3
VL
and
.*. Power P
v = v
P L
and
14-4 A.
415
(a) Impedance per phase Z = r— ohms
14-4
= 28-8 a
Resistance per phase R = Z cos (j)
= 2 8 - 8 x 0 - 8 ohms
= 2 3 0 Q.
Reactance per phase X — Z sin $
= 2 8 - 8 x 0 - 6 ohms
= 17-3 Q.
V
(b) Resistance per phase R —
IP x cos (j)
415
ohms
14-4x0-8
36 0Q.
V
Reactance per phase X
IP x sin cj)
415
ohm
14-4x0-6
47-9 Q.
415
= ^ volts
= 240 V.
In star, phase current IP = 200 A.
240
Impedance of one phase Z = ohms
= 1-2 Q.
415
In delta, phase current IP = - y ^ amperes
= 346 A.
In delta, line current IL — (^/3) IP
— ( ^ 3 ) x 346 amperes
= 600 A.
30,000
Supply current IL -
G / 3 ) x 4 1 5 x 0 - 8 amperes
5-21 A.
phase current 5-21 A.
4153
Voltage per phase ; volts
V
240 V.
240
Impedance per phase Z = T^TT ohms
5-21
46 Q.
Resistance per phase R Z cos cj)
= 46 x 0-8 ohms
= 36-8 ft.
Reactance per phase XL = Z sin cf)
= 46 x 0-6 ohms
= 27-6 a.
When delta-connected,
415
Phase current IP••
— amperes
9-02 A.
Line current IL
(y/3) x9-02 amperes
= 15-63 A.
Power consumed P
( x/ 3 ) x 4 1 5 x 15-63x0-8 watts
9000 W.
(i.e. three times the power con-
Alternatively, sumed when star-connected).
Power consumed P : (3 x 2 4 0 x9-02 x0-8) watts
9000 W.
THREE-PHASE SYSTEM 183
5.6. Kilowatts, kilovolt-amperes and reactive kilovolt-amperes
In a balanced three-phase system, the power in kilowatts is
given by the expression
3
p = ( ^ 3 ) vL IL cos cb x 1 0 " kilowatts
18,000 W or 18 kW.
kW
(a) Supply kVA
COS (f)
_18
0-8
22 5 kVA.
I N
t-J
R- • R
Y -
" Y
B - - B
N -
-N
Houses
I L N I I L N I
I I I 1 I
I I I I I J
FIG. 5.6.
THREE-PHASE SYSTEM 185
currents in the three lines and this is usually smaller t h a n any of
the three line currents. In an ideal case when the loads were
balanced, the neutral current would be zero.
In a factory, the lighting load and the 13-A socket outlets would
all come from a line and neutral connection. These loads are
distributed between the three phases in a n attempt to balance the
loading. The distribution of a fluorescent lighting load between
the three phases eliminates the s t r o b o s c o p e effects by which
rotating machinery may appear to be stationary.
When a balanced load such as a three-phase motor is connected
across the three lines of a three-phase, four-wire system, there is
no change in the current in the neutral conductor. The addition of
such a machine to an existing system would result in a n increase in
the currents in the three lines but not necessarily by the same
amount.
EXAMPLE 5.7. The following loads are connected between line
and neutral in a 200-V, three-phase, four-wire system:
Red line to neutral: 8 k W at unity power factor.
Yellow line to neutral: 6 k W at 0-8 power factor lagging.
Blue line to neutral: 10 k W at 0-95 power factor lagging.
Find the neutral current.
200
Phase voltage = —rr = 1 1 5 V .
8000
Red phase current IR amperes.
115x1
= 69-4 A.
6000
Yellow phase current IY = amperes
115x0-8
= 65 A .
10,000
Blue phase current IB =
115x0-95 amperes
= 91-4A.
186 ELECTRICAL ENGINEERING PRINCIPLES FOR TECHNICIANS
VRN
V
YN
(a)
I cos 0°
R
(b)
F I G . 5.7. Phasor diagrams for Example 5.7. (Part (c) on facing page.)
THREE-PHASE SYSTEM 187
Problems
1. A three-phase balanced load of 40 kW at 0-8 power factor is supplied
from a three-phase, 415-V system. Determine the line and phase currents if the
load is connected in (a) star, (b) delta.
( (a) 69-6 A, 69-6 A; (b) 69-6 A, 40-2 A . )
2. A three-phase, star-connected induction motor takes a line current of 50A
at the instant of connection to a three-phase, 415-V supply. If the windings
of the motor had been delta-connected, what would be the current under the
same conditions ?
(150 A.)
3. With the aid of a diagram, explain how a three-phase supply is generated
by an alternator (a.c. generator).
Three balanced loads are connected in delta and take a power of 30 kW at
0-8 power factor from a three-phase, 415-V supply. Calculate the line current.
If the above loads are reconnected in star, to the same supply, what power
would be consumed ?
(52-2 A, 10 kW.) (N.C.T.E.C.)
4. Three equal impedances are connected in star to a 400-V (line), three-
phase, 50-Hz supply, and take in all 15 kVA at a power factor of 0-8 lag. If
these impedances were connected in delta to the same supply, what would be
the line current and total power ? Sketch a circuit diagram in each case.
(65 A, 36 kW.) (U.L.C.I.)
5. How many three-phase, 400-V induction motors can be supplied by a
500-kVA transformer if each motor has an output of 50 hp and their power
factor and efficiency are 0-8 and 88% respectively?
(16 motors.)
6. A balanced three-phase, delta-connected load consists of a resistor and a
capacitor in each phase. If the supply is 415-V, 50-Hz and the power con-
sumed is 2 kW at a power factor of 0-8, calculate the size of the resistor and
capacitor if the components are connected in (a) series, (b) parallel.
( (a) 166 ohms, 25-1 /xF; (b) 259 ohms, 9-2 fiF.) (U.L.C.I.)
7. A balanced star-connected load takes 9 kW at a power factor of 0-9 from
a three-phase, three-wire, 415-V supply. Calculate the supply current.
If one line is disconnected from the load, what will be (a) the new line
current, (b) the new power consumed ?
(13-9 A, (a) 12-1 A, (b) 4500 W.)
8. A motor-driven pump raises 1200 gal of water through a vertical distance
of 120 ft every minute. If the efficiency of the pump is 78%, calculate the
output of the motor in kW.
If the motor is supplied from a three-phase, 415-V supply, calculate the line
current if the motor efficiency is 85 % and the power factor is 0-8 lagging.
Assume that 1 gal of water weighs 10 lbf.
(41-7 kW, 85-3 A.)
THREE-PHASE SYSTEM 189
9. A three-phase 2200-V, star-connected alternator feeds a 3000-hp, delta-
connected induction motor which is operating on full load at a power factor of
0-8 and an efficiency of 85%. Calculate (a) the motor line current, (b) the
motor phase current, (c) the alternator phase current.
((a) 864 A, (b) 499 A, (c) 864 A. ) (U.L.C.I.)
10. Three identical impedances, each having a resistance of 20 CI and an
inductance of 0 1 H, are connected in star to a three-phase, three-wire, 415-V,
50-Hz supply. Calculate the total power consumed.
If one line becomes disconnected, what power is now consumed ?
(2490 W, 1245 W.) (U.L.C.I.)
Answers are not given to the following problems.
11. A three-phase, 50-hp delta connected induction motor has an efficiency
of 92% and a power factor of 0-85. It is supplied by a 500-V, star-connected
alternator.
Find the current in each motor and alternator phase and the active and
reactive components of the motor phase current. Draw the circuit diagram and
sketch a phasor diagram showing line and phase voltages and currents for the
induction motor.
(U.E.I.)
12. Describe what is meant by a three-phase, three-wire supply, and mention
TWO advantages of such a system over a single-phase supply. Calculate the
total power taken from a three-phase, 415-V (line) supply by three 50-Cl
resistors when they are connected (a) in star, (b) in delta.
(W.J.E.C.)
13. In a three-phase, 415-V, four-wire system the loads are:
R line to neutral: 15 A at unity power factor;
Yline to neutral: 10 A at a power factor of 0-8 lagging;
B line to neutral: 25 A at a power factor of 0-9 lagging.
The phase sequence is R Y B. By drawing to scale a phasor diagram, find
the current in the neutral wire. What is the total power consumed?