0% found this document useful (0 votes)
18 views

Piping Size Calculation Sheet

1. The document provides a summary of major utilities for a process plant project with 11 items listed including cooling towers, water chiller, brine chiller, air compressor, and steam boiler. 2. Pipe sizing calculations are provided for liquid, compressed air and nitrogen, and steam based on flow rate, velocity, and inner diameter. 3. Pump head calculations include suction head components of vertical height, horizontal piping length, and bends, as well as delivery head components of vertical height, horizontal piping length, and bends to determine total dynamic head.

Uploaded by

e43n56gg
Copyright
© © All Rights Reserved
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
18 views

Piping Size Calculation Sheet

1. The document provides a summary of major utilities for a process plant project with 11 items listed including cooling towers, water chiller, brine chiller, air compressor, and steam boiler. 2. Pipe sizing calculations are provided for liquid, compressed air and nitrogen, and steam based on flow rate, velocity, and inner diameter. 3. Pump head calculations include suction head components of vertical height, horizontal piping length, and bends, as well as delivery head components of vertical height, horizontal piping length, and bends to determine total dynamic head.

Uploaded by

e43n56gg
Copyright
© © All Rights Reserved
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 5

SEA

Projects Pvt Ltd

Client : DISCOVERY INTERMEDIATES PVT. LTD Rev No : 00

Project No : 036 Date : 09.10.2017

Doc No : SEA-036-DIPL-UTILITY EQUIP-SUMMARY-001


SUMMARY OF MAJOR UTILITIES
BRIEF DESCRIPTION/
S.NO TAG NO EQUIPMENT NAME UOM CAPACITY QTY
MOC

1 CT-001 Cooling Tower for Process Induced Draft TR 550 1

Cooling Tower for Water chiller


2 CT-002 Induced Draft TR 220 1
Cooling Tower for Brine chiller

3 WC-001 Water Chiller (+5 deg C) Reciprocating Type TR 125 1

4 WCT-001 Hot & Cold well tank MS tank M3/Hr 20 1

5 BC-001 Brine Chiller (-20 deg C) Reciprocating Type TR 55 1

6 BCT-001 Hot & Cold well tank MS tank M3/Hr 10 1

Air Compressor with Air Drying


7 AC-001 Screw Compressor CFM 120 1
Unit

8 AHT-001 Air Receiver MS tank M3/Hr 5 1

9 HW-001 Hot water MS Jacketed Tank M3/Hr 20 1

10 SB-001 Steam Boiler Coal Fired Boiler TPH 2.5 1

11 N2-001 Nitrogen Plant - NM3/Hr 20 1


TR to Cum:
1 TR= 0.65 Cum TR Cum
100 0.6 130

Pipe size for Liquid:


Q=AV
Q= ((π/4) d2)V
d2= (4Q)/(πV)
d= √(4Q)/(πV) Q π V T
d= 4 130 3.14 2 3600 0.023

Q= Flow rate in Cum/Hr


V= Flow Velocity in M/Sec
d= Inner diameter of pipe in mm

Pipe size for CA & N2: CFM to CMH


Q=AV
Q= ((π/4) d2)V
d2= (4Q)/(πV)
d= √(4Q)/(πV) Q π V T
d= 4 300 3.14 40 3600 0.003

Q= Flow rate in Cum/Hr


V= Flow Velocity in M/Sec
d= Inner diameter of pipe in mm

Pipe size for Steam


Q=AV
Q= ((π/4) d2)V
d2= (4Q)/(π∫V)
d= √(4Q)/(π∫V) Q π V T
d= 4 250 3.14 25 3600 0.001

Q= Flow rate in Cum/Hr


V= Flow Velocity in M/Sec
d= Inner diameter of pipe in mm
∫ = 3.11 Kg/Cum
0.152 152

109.14 109

0.034 34
Pump Head Calculation
Suction head Qty (M) Qty (Feet)
Vertical height Total qty 0 0
Horizontal pipe line used 2% of used qty 3 9.6
No. of bends 01 feet per each bend 1 1

Delivery head Qty (M) Qty (Feet)


Vertical height Total qty 15 48
Horizontal pipe line used 2% of used qty 160 512
No. of bends 01 feet per each bend 20 20
Total head
Total Head (Feet) Total Head (Mts)
0
0.192
1

48
10.24
20
79.24 24.7625