Table of Contents
Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 Energy Responsible Tool . . . . . . . . . . . . . . . . . . . . . . . 4
Valve Stroking Time . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Ordering Information . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2
Product Bulletin
i2P-100 Transducer 62.1:i2P-100
D103197X012 August 2020
Specifications
Input Signal Frequency Response: Gain is attenuated 3 dB at 3 Hz
Available as standard with 4-20 mA. with transducer output signal piped to a typical
User configurable by dip switch for split ranging, see instrument input
table below.
Temperature Effect: $0.14% per degrees Celsius
($0.075 per degrees Fahrenheit) of span
Output Signal
Available as standard 0.2 to 1.0 bar (3 to 15 psig), Supply Pressure Effect: 0.2% of full scale output span
0.4 to 2.0 bar (6 to 30 psig), or 0.14 to 2.3 bar per psi supply pressure change)
(2 to 33 psig). User configurable by dip switch
selection and zero and span potentiometer Vibration Effect: Less than 1% of full scale output span
adjustment, see table below. when tested to ISA S75.13
OUTPUT PRESSURE
INPUT SIGNAL Electromagnetic Compatibility
Bar Psig
Meets EN 61326-1:2013
0.2 to 1.0 3 to 15
Immunity—Industrial locations per Table 2 of
4 to 20 mA DC 0.4 to 2.0 6 to 30 EN 61326-1 Standard. Performance is
0.14 to 2.3 2 to 33 shown in table 1 below.
4 to 12 mA DC 0.2 to 1.0 3 to 15 Emissions—Class A
12 to 20 mA DC 0.2 to 1.0 3 to 15 ISM equipment rating: Group 1, Class A
Equivalent Circuit
The i2P-100 equivalent circuit is a series circuit Operating Ambient Temperature Limits(1)
consisting of a constant voltage drop (battery) of
approximately 4 VDC and a total resistance of 40 -40 to 85_C (-40 to +185_F)
ohms. Input is shunted by two 6.8 V zener diodes (see
figure 4).
Electrical Seal
Supply Pressure(1)
Recommended: 0.34 bar (5 psi) higher than upper Single sealed device per ANSI/ISA 12.27.01
range limit of output signal
Maximum: 3.4 bar (50 psig)
Medium: Air or Non-Corrosive Natural Gas Electrical Classification
3
Product Bulletin
62.1:i2P-100 i2P-100 Transducer
August 2020 D103197X012
Specifications (continued)
Hazardous Area Approvals (continued) Adjustments(5)
INMETRO— National Institute of Metrology, Quality, Zero and Span: Trim potentiometers (20 turn) for
and Technology (Brazil) zero and span adjustments are located under the
housing cap.
KTL—Korea Testing Laboratory (South Korea) Switch: Allows input signal split range and
user-configurable 0.14 to 2.3 bar (2 to 33 psig)
NEPSI— National Supervision and Inspection Centre
output.
for Explosion Protection and Safety of
Instrumentation (China)
Connections
Contact your Emerson sales office for Supply and Output Pressure: 1/4 NPT internal
classification/certification specific information connection
Vent: 1/4 NPT internal
Electrical Housing:
Electrical: J Standard 1/2 NPT
When Remotely Vented No Remote Venting Wire Size: 18 to 22 AWG
CSA—Type 4X Encl. CSA—Type 3 Encl.
FM— NEMA 4X FM— NEMA 3 Mounting Position
ATEX—IP66 ATEX—IP64 J Actuator J pipestand or J surface
IECEx—IP66 IECEx—IP64
Approximate Weight
2.5 kg (5.5 lbs)
Construction Materials
Housing: ASTM: A03600 material composition alloy Options
O-rings: Nitrile J Output pressure gauge J M20 or PG13 conduit
Diaphragms: Nitrile adapter
NOTE: Specialized instrument terms are defined in ANSI/ISA Standard 51.1 - Process Instrument Terminology
1. The pressure and temperature limits in this document and any applicable standard or code limitation should not be exceeded.
2. Average flow rate determined at 12 mA and 0.6 bar (9 psig) output.
3. Normal m3/hour--Normal cubic meters per hour (0_C and 1.01325 bar, absolute). Scfh--Standard cubic feet per hour (60_F and 14.7 psig).
4. Performance values are obtained using a transducer with a 4 to 20 mA DC input signal and a 0.2 to 1.0 bar (3 to 15 psig) output signal at an ambient temperature of 24_C (75_F).
5. For other ranges, zero and span adjustments needed.
4
Product Bulletin
i2P-100 Transducer 62.1:i2P-100
D103197X012 August 2020
90
0.2 3 0.04 1.5
80 1.4 20
0.62 9 0.06 2.0
70 LOADING 1.0 15 0.07 2.6
OUTPUT
60 0.4 - 2.0 6 - 30
50 0.4 6 0.05 1.7
2.4 35
40 1.2 18 0.08 2.9
EXHAUSTING
30 2 30 0.12 4.1
20 0.1 - 2.3 2 - 33
10 0.1 2 0.04 1.5
2.6 38
0
1.2 17.5 0.08 2.9
0 10 20 30 40 50 60 70 80 90 100 2.3 33 0.12 4.3
1. Normal m3/hour - Normal cubic meters per hour (0C and 1.0135 bar, absolute).
A6815 TIME (%) Scfh - Standard cubic feet per hour (60F and 14.7psig).
5
Product Bulletin
62.1:i2P-100 i2P-100 Transducer
August 2020 D103197X012
Figure 5. Dimensions
74.2
(2.92)
36.3
(1.43)
103.9 103.9
(4.09) (4.09)
34.7
(1.37)
81.6
(3.21)
98.7
(3.89) 1/4 18 NPT VENT
OR PIPE-A-WAY
CONNECTION
1/4 18 NPT 1/4 18 NPT
OUTPUT CONNECTION OUTPUT CONNECTION
1/4 18 NPT 22.9
67.8 33.3 SUPPLY CONNECTION (0.90)
(2.67) (1.31) 33.3
55.7 33.3 (1.31)
(2.19) (1.31)
GE06439 67 (2.62) CAP 67 (2.62) CAP
(sheet 1 of 4)
REMOVAL 75.2 75.7 REMOVAL
CLEARANCE (2.96) (2.98) CLEARANCE
mm
(INCH)
6
Product Bulletin
i2P-100 Transducer 62.1:i2P-100
D103197X012 August 2020
57.2
(2.25)
50.8 170.8
(2.00) (6.72)
101.1
(3.98)
146.1
(5.75)
67 (2.62)
COVER REMOVAL
CLEARANCE
(BOTH COVERS)
146.1
(5.75)
91.1
(3.59)
GE06439
mm
(sheet 3 of 4) 209.6 (INCH)
(8.25)
7
Product Bulletin
62.1:i2P-100 i2P-100 Transducer
August 2020 D103197X012
74.2
(2.92)
170.8
(6.72)
240
(9.55) 243.2
GE06439
(sheet 4 of 4) (9.58) mm
(INCH)
Neither Emerson, Emerson Automation Solutions, nor any of their affiliated entities assumes responsibility for the selection, use or maintenance
of any product. Responsibility for proper selection, use, and maintenance of any product remains solely with the purchaser and end user.
Fisher is a mark owned by one of the companies in the Emerson Automation Solutions business unit of Emerson Electric Co. Emerson Automation Solutions,
Emerson, and the Emerson logo are trademarks and service marks of Emerson Electric Co. All other marks are the property of their respective owners.
The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy, they are not
to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. All sales are
governed by our terms and conditions, which are available upon request. We reserve the right to modify or improve the designs or specifications of such
products at any time without notice.
Emerson Automation Solutions
Marshalltown, Iowa 50158 USA
Sorocaba, 18087 Brazil
Cernay 68700 France
Dubai, United Arab Emirates
Singapore 128461 Singapore
www.Fisher.com
E
8 2004, 2020 Fisher Controls International LLC. All rights reserved.