Product Bulletin

i2P-100 Transducer 62.1:i2P-100


D103197X012 August 2020

Fisher™ i2P-100 Electro-Pneumatic Transducer


The Fisher i2P-100 electro-pneumatic transducer, uses
a converter module that converts a milliampere input
to a proportional pressure output. Both the current
input and pressure output range are user-configurable
in the field. The converter module uses small parts of
minimum mass, which are balanced symmetrically
around a pivot point at the center of the mass. This
balanced arrangement results in a high performance
instrument that reduces sensitivity to vibration. REPLACEABLE
FILTER WITH
An integral pneumatic relay provides the high capacity REMOVABLE
ORIFICE
necessary to drive pneumatic control valve/actuator INTEGRAL
assemblies without additional boosters or positioners. VENT
PNEUMATIC
The transducer also provides stable, accurate RELAY
operation when its output is transmitted to small
volume chambers, such as a pneumatic positioner or W8710

other pneumatic instrument. Reduced sensitivity to


vibration, combined with high capacity and first order n High Output Capability and Rangeability— The
lag characteristics, make the i2P-100 transducer
integral output relay volume of the transducer is
suitable for direct mounting on control valve/actuator
combinations. adequate to drive valve/actuator combinations
without requiring a positioner or volume booster.
Selectable user field-configurable dip switch setting
for output range of 0.14 to 2.3 bar (2 to 33 psi).

n Split Range—Selectable user field-configurable


Features two-way split range, using either half of the
standard input signal.
n Approved for use with Natural Gas—The i2P-100 is
n Corrosion Resistant—Separate housing
approved for use with natural gas as the pneumatic
compartments isolate the electronics from the
supply.
pneumatic process. The electronics module is
encased in a rugged plastic shell which helps to
n Low Pneumatic Supply Consumption—The prevent damage to the electronics. The printed
transducer has low pneumatic supply consumption wiring board and dip switches are conformal coated
which lowers operating costs. Maximum steady to help prevent corrosion. Converter module coils
state consumption is less than the 6 SCFH have corrosion resistant coating and all flexures are
requirement set for the oil and gas industry by the gold plated to provide protection from hostile
US Environmental Protection Agency (New Source environments.
Performance Standards Subpart OOOO,
EPA­HQ­QAR­2010­0505). n Tolerant of Dirty Supply Medium—Free-flow pilot
stage design and large internal air passages provide
n Single Sealed Device— The i2P-100 has been tested excellent tolerance to dirty pneumatic supply, by
in accordance with ANSI/ISA Standard 12.27.01 reducing the effects of contaminant buildup and
(Requirements for Process Sealing Between erosion. The removable primary orifice and
Electrical Systems and Flammable or Combustible replaceable 5 micrometer filter are easy to remove
Process Fluids) as a single sealed device. for service and maintenance.

www.Fisher.com
Product Bulletin
62.1:i2P-100 i2P-100 Transducer
August 2020 D103197X012

Figure 1. Fisher i2P-100 Electro-Pneumatic Figure 2. Fisher i2P-100 Electro-Pneumatic


Transducer Mounted on a Rotary Actuator Transducer Mounted on a Sliding-Stem Actuator

W8693-1

W8723-1

n Easy Maintenance—Modular electronics and


converter modules contained in separate housing
compartments, isolating the electronics from the
process, allow for easy replacement in the field for
reduced maintenance time and costs.
Valve Stroking Time
Figure 3 shows relative times for loading and
exhausting an actuator. Stroking time depends upon
n Vibration Resistance—The transducer, used in a the size of the actuator, travel, relay characteristics
standard valve/actuator mounted application, and the magnitude and rate of change of the input
exhibits an output shift of less than 1 percent of signal. If stroking time is critical, contact your Emerson
span when tested to ISA S75.13. sales office.

Table of Contents
Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 Energy Responsible Tool . . . . . . . . . . . . . . . . . . . . . . . 4
Valve Stroking Time . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Ordering Information . . . . . . . . . . . . . . . . . . . . . . . . . . 6

2
Product Bulletin
i2P-100 Transducer 62.1:i2P-100
D103197X012 August 2020

Specifications
Input Signal Frequency Response: Gain is attenuated 3 dB at 3 Hz
Available as standard with 4-20 mA. with transducer output signal piped to a typical
User configurable by dip switch for split ranging, see instrument input
table below.
Temperature Effect: $0.14% per degrees Celsius
($0.075 per degrees Fahrenheit) of span
Output Signal
Available as standard 0.2 to 1.0 bar (3 to 15 psig), Supply Pressure Effect: 0.2% of full scale output span
0.4 to 2.0 bar (6 to 30 psig), or 0.14 to 2.3 bar per psi supply pressure change)
(2 to 33 psig). User configurable by dip switch
selection and zero and span potentiometer Vibration Effect: Less than 1% of full scale output span
adjustment, see table below. when tested to ISA S75.13
OUTPUT PRESSURE
INPUT SIGNAL Electromagnetic Compatibility
Bar Psig
Meets EN 61326-1:2013
0.2 to 1.0 3 to 15
Immunity—Industrial locations per Table 2 of
4 to 20 mA DC 0.4 to 2.0 6 to 30 EN 61326-1 Standard. Performance is
0.14 to 2.3 2 to 33 shown in table 1 below.
4 to 12 mA DC 0.2 to 1.0 3 to 15 Emissions—Class A
12 to 20 mA DC 0.2 to 1.0 3 to 15 ISM equipment rating: Group 1, Class A

Equivalent Circuit
The i2P-100 equivalent circuit is a series circuit Operating Ambient Temperature Limits(1)
consisting of a constant voltage drop (battery) of
approximately 4 VDC and a total resistance of 40 -40 to 85_C (-40 to +185_F)
ohms. Input is shunted by two 6.8 V zener diodes (see
figure 4).
Electrical Seal
Supply Pressure(1)
Recommended: 0.34 bar (5 psi) higher than upper Single sealed device per ANSI/ISA 12.27.01
range limit of output signal
Maximum: 3.4 bar (50 psig)
Medium: Air or Non-Corrosive Natural Gas Electrical Classification

Maximum Steady-State Flow Rate(2)(3) Hazardous Area Approvals

Refer to tables 2 and 3 CSA — Intrinsically Safe, Explosion proof,


Type n, Dust‐Ignition proof
Maximum Output Air Capacity(3)
FM— Intrinsically Safe, Explosion proof,
8.04 m3/hr (300 scfh) at 1.4 bar (20 psig) supply
Type n, Non‐incendive, Dust‐Ignition proof
pressure
ATEX— Intrinsically Safe, Flameproof , Type n
Performance(4)
Reference Accuracy: ±1.0% of full scale output span; IECEx— Intrinsically Safe, Flameproof, Type n
includes combined effects of hysteresis, linearity, and
deadband CUTR—Customs Union Technical Regulations
(Russia, Kazakhstan, Belarus, and Armenia)
Independent Linearity: ±0.5% of full scale output span
Hysteresis: 0.4% of full scale output span (continued on next page)
-continued-

3
Product Bulletin
62.1:i2P-100 i2P-100 Transducer
August 2020 D103197X012

Specifications (continued)
Hazardous Area Approvals (continued) Adjustments(5)
INMETRO— National Institute of Metrology, Quality, Zero and Span: Trim potentiometers (20 turn) for
and Technology (Brazil) zero and span adjustments are located under the
housing cap.
KTL—Korea Testing Laboratory (South Korea) Switch: Allows input signal split range and
user-configurable 0.14 to 2.3 bar (2 to 33 psig)
NEPSI— National Supervision and Inspection Centre
output.
for Explosion Protection and Safety of
Instrumentation (China)
Connections
Contact your Emerson sales office for Supply and Output Pressure: 1/4 NPT internal
classification/certification specific information connection
Vent: 1/4 NPT internal
Electrical Housing:
Electrical: J Standard 1/2 NPT
When Remotely Vented No Remote Venting Wire Size: 18 to 22 AWG
CSA—Type 4X Encl. CSA—Type 3 Encl.
FM— NEMA 4X FM— NEMA 3 Mounting Position
ATEX—IP66 ATEX—IP64 J Actuator J pipestand or J surface
IECEx—IP66 IECEx—IP64
Approximate Weight
2.5 kg (5.5 lbs)
Construction Materials
Housing: ASTM: A03600 material composition alloy Options
O-rings: Nitrile J Output pressure gauge J M20 or PG13 conduit
Diaphragms: Nitrile adapter

NOTE: Specialized instrument terms are defined in ANSI/ISA Standard 51.1 - Process Instrument Terminology
1. The pressure and temperature limits in this document and any applicable standard or code limitation should not be exceeded.
2. Average flow rate determined at 12 mA and 0.6 bar (9 psig) output.
3. Normal m3/hour--Normal cubic meters per hour (0_C and 1.01325 bar, absolute). Scfh--Standard cubic feet per hour (60_F and 14.7 psig).
4. Performance values are obtained using a transducer with a 4 to 20 mA DC input signal and a 0.2 to 1.0 bar (3 to 15 psig) output signal at an ambient temperature of 24_C (75_F).
5. For other ranges, zero and span adjustments needed.

Energy Responsible Tool


The web based Energy Responsible Tool
provides calculations for estimating operating costs
and emissions for instrument air and natural gas in
tonnes of Equivalent Carbon Dioxide (Co2e).
Scan or click the QR code to calculate pneumatic
energy savings.

4
Product Bulletin
i2P-100 Transducer 62.1:i2P-100
D103197X012 August 2020

Table 1. EMC Summary Results—Immunity


Performance
Port Phenomenon Basic Standard Test Level
Criteria(1)
4kV Contact
Electrostatic discharge (ESD) IEC 61000-4-2 A
8kV Air
Enclosure 80 to 1000 MHz @ 10V/m with 1 kHz AM at 80%
Radiated EM field IEC 61000-4-3 1400 to 2000 MHz @ 3V/m with 1 kHz AM at 80% A
2000 to 2700 MHz @ 1V/m with 1 kHz AM at 80%
Burst (fast transients) IEC 61000-4-4 1 kV A
I/O signal/control Surge IEC 61000-4-5 1 kV (line to ground only, each) A
Conducted RF IEC 61000-4-6 150 kHz to 80 MHz at 3 Vrms A
Specification limit = ±1% of span
1. A=No degradation during testing. B = Temporary degradation during testing, but is self-recovering.

Figure 3. Output-Time Relationships Table 2. Maximum Steady-State Flow Rate (Air)


STEADY STATE
SUPPLY PRESSURE OUTPUT PRESSURE
FLOW RATE(1)
Bar Psi Bar Psi m3/hr Scfh
100
0.2 - 1.0 3 - 15
(% OF i2P-100 OUTPUT SPAN)

90
0.2 3 0.04 1.5
80 1.4 20
0.62 9 0.06 2.0
70 LOADING 1.0 15 0.07 2.6
OUTPUT

60 0.4 - 2.0 6 - 30
50 0.4 6 0.05 1.7
2.4 35
40 1.2 18 0.08 2.9
EXHAUSTING
30 2 30 0.12 4.1
20 0.1 - 2.3 2 - 33
10 0.1 2 0.04 1.5
2.6 38
0
1.2 17.5 0.08 2.9
0 10 20 30 40 50 60 70 80 90 100 2.3 33 0.12 4.3
1. Normal m3/hour - Normal cubic meters per hour (0C and 1.0135 bar, absolute).
A6815 TIME (%) Scfh - Standard cubic feet per hour (60F and 14.7psig).

Table 3. Maximum Steady-State Flow Rate


(Natural Gas)
Figure 4. Equivalent Circuit STEADY STATE
SUPPLY PRESSURE OUTPUT PRESSURE
FLOW RATE(1,2)
4 - 20 mA Bar Psi Bar Psi m3/hr Scfh
0.2 - 1.0 3 - 15
0.2 3 0.06 1.95
1.4 20
0.62 9 0.07 2.6
1.0 15 0.1 3.38
0.4 - 2.0 6 - 30
6.8V 6.8V 4V
0.4 6 0.6 2.21
2.4 35
1.2 18 0.11 3.77
2 30 0.15 5.33
40 Ohm 0.1 - 2.3 2 - 33
0.1 2 0.06 1.94
2.6 38
1.2 17.5 0.11 3.74
2.3 33 0.18 5.55
1. Normal m3/hour - Normal cubic meters per hour (0C and 1.0135 bar, absolute).
Scfh - Standard cubic feet per hour (60F and 14.7psig).
2. Natural gas steady state flow based on natural gas specific gravity of 0.6.
Flow decreases as specific gravity increases.

5
Product Bulletin
62.1:i2P-100 i2P-100 Transducer
August 2020 D103197X012

Installation Ordering Information


Refer to figure 5 for location of standard mounting To determine what ordering information is required,
holes in the housing. See figures 1 and 2 for typical refer to the Specifications table. Carefully review the
mounting configurations. Standard mounting description of each specification. Specify the desired
hardware is provided for mounting on the actuator, a choice whenever there is a selection available. Also,
pipestand, or surface mount. Field wiring connections specify options that are applicable to the application.
are made to the terminal block accessible under the
housing cap, via the 1/2 NPT conduit connection.
Dimensions are shown in figures 5, 6, 7, and 8.

Figure 5. Dimensions

1/2 14 NPT 22.3


58.7 CONDUIT CONNECTION (0.88)
(2.31)

74.2
(2.92)
36.3
(1.43)
103.9 103.9
(4.09) (4.09)
34.7
(1.37)
81.6
(3.21)
98.7
(3.89) 1/4 18 NPT VENT
OR PIPE-A-WAY
CONNECTION
1/4 18 NPT 1/4 18 NPT
OUTPUT CONNECTION OUTPUT CONNECTION
1/4 18 NPT 22.9
67.8 33.3 SUPPLY CONNECTION (0.90)
(2.67) (1.31) 33.3
55.7 33.3 (1.31)
(2.19) (1.31)
GE06439 67 (2.62) CAP 67 (2.62) CAP
(sheet 1 of 4)
REMOVAL 75.2 75.7 REMOVAL
CLEARANCE (2.96) (2.98) CLEARANCE

mm
(INCH)

6
Product Bulletin
i2P-100 Transducer 62.1:i2P-100
D103197X012 August 2020

Figure 6. Dimensions with Optional Fisher 67 Filter-Regulator (Yoke/Bracket Mounted)

67 (2.62) 238.1 126.3


(9.37) (4.97)
COVER REMOVAL
CLEARANCE 69.9
(BOTH COVERS) (2.75) 74.2
(2.92)
8.6 6.4
(0.34) (0.2
5)

57.2
(2.25)
50.8 170.8
(2.00) (6.72)

101.1
(3.98)

GE06439 240 204.8


(sheet 2 of 4)
(9.45) (8.06) mm
(INCH)

Figure 7. Dimensions with Optional Fisher 67 Filter-Regulator (Surface/Wall Mounted)

146.1
(5.75)
67 (2.62)
COVER REMOVAL
CLEARANCE
(BOTH COVERS)

146.1
(5.75)

91.1
(3.59)

GE06439
mm
(sheet 3 of 4) 209.6 (INCH)
(8.25)

7
Product Bulletin
62.1:i2P-100 i2P-100 Transducer
August 2020 D103197X012

Figure 8. Dimensions with Optional Fisher 67 Filter-Regulator (Pipestand Mounted)


238.1
67 (2.62)
(9.37)
COVER REMOVAL 50.8
CLEARANCE (2.00)
(BOTH COVERS) 60.5
(2.38)

74.2
(2.92)

170.8
(6.72)

240
(9.55) 243.2
GE06439
(sheet 4 of 4) (9.58) mm
(INCH)

Scan or click the


QR code to find out
more about the
i2P-100 transducer

Neither Emerson, Emerson Automation Solutions, nor any of their affiliated entities assumes responsibility for the selection, use or maintenance
of any product. Responsibility for proper selection, use, and maintenance of any product remains solely with the purchaser and end user.
Fisher is a mark owned by one of the companies in the Emerson Automation Solutions business unit of Emerson Electric Co. Emerson Automation Solutions,
Emerson, and the Emerson logo are trademarks and service marks of Emerson Electric Co. All other marks are the property of their respective owners.

The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy, they are not
to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. All sales are
governed by our terms and conditions, which are available upon request. We reserve the right to modify or improve the designs or specifications of such
products at any time without notice.
Emerson Automation Solutions
Marshalltown, Iowa 50158 USA
Sorocaba, 18087 Brazil
Cernay 68700 France
Dubai, United Arab Emirates
Singapore 128461 Singapore

www.Fisher.com

E