HANUR SOLAR POWERPLANT
66/11KV SUBSTATION Page 1 of 2
O/C & E/F RELAY TEST REPORT
DATE:25/07/23
TEST REPORT FOR OVER CURRENT AND EARTH FAULT RELAY
Customer : M/S ECOREN ENERGY Date : 24/07/2023
Model No : P141811N2M0520J Aux. Voltage :110 VDC
Serial No : 34386318/03/18 Frequency : 50 Hz
MAKE : ALSTOM MICOM Settings Recommended by:
Panel Ref : 66/11KV TRANSFORMER CUM
FEEDER RELAY PANAL-(6KLA)
All setting values are reference to secondary side.
MEASURNMENT CHECK
CT RATIO 400/1A
PHASE INJECTED VALUE MEASURD VALUE
R PH 1A 400.1
Y PH 1A 399.1
B PH 1A 399.5
OVER CURRENT PROTECTION (50/51):
Setting :
I>Char IEC-S INVERSE
I> 0.62 A
tms> 0.1 S
I>> 5.45 A
tms>> 0S
TIMING TEST:
Expected Relay operated Time(Sec)
FUNCTION Injected Current (A) Operation
R Y B
Time(Sec)
I> 0.80 (1.3times) 2.73 2.78 2.79 2.79
I> 1.24 (2 times) 1.00 1.03 1.03 1.03
I> 3.1 (5 times) 0.42 0.44 0.44 0.45
Non- Directional Over current and Earth Fault Relay Page 1 of 3
HANUR SOLAR POWERPLANT
66/11KV SUBSTATION Page 2 of 2
O/C & E/F RELAY TEST REPORT
DATE:25/07/23
Overcurrent Fault Protection (51):
I>>: 5.45 Time: 0
Phase Ref Injected current (A) Operating Time(Sec)
R 5.45 0.042
Y 5.45 0.040
B 5.45 0.042
Earth fault Protection (50N):
I0> Char IEC-S INVERSE
I0 > 0.11 A
TMS0> 0.1 S
I0>> 0.56 A
T0>> 0.2 S
TIMING TEST:
Expected Time Relay operated Time(S)
FUNCTION Injected Current (A) (Sec)
Ie ( Injected on R/Y/B)
I0 > 0.143 (1.3 times) 2.66 2.72
I0 > 0.22 (2 times) 1.00 1.04
I0 > 0.55 (5 times) 0.42 0.44
Earth Fault Protection (51N):
I0>>:0.57 Time: 0.2
Phase Ref Injected current (A) Operating Time(Sec)
R 0.57 0.225
Y 0.57 0.228
B 0.57 0.227
Non- Directional Over current and Earth Fault Relay Page 2 of 3
HANUR SOLAR POWERPLANT
66/11KV SUBSTATION Page 3 of 2
O/C & E/F RELAY TEST REPORT
DATE:25/07/23
LBB:
Setting:
I</IN< Current Set 0.2A
CB Fail-1 Timer 100mS
CB Fail-2 Timer 200mS
Volt Protection Reset I<Only
Current Protection Reset I<Only
Protection operates with start signal of remaining protection. The overcurrent protection 2nd stage is
turned on to get the start signal for breaker failure protection.
Phase Ref Injected current (A) Operating Time(Sec)
R 5.45
Y 5.45 0.126
B 5.45
MODEL NO P141811N2M0520J
SL NO 34386318/03/18
: 66/11KV TRANSFORMER CUM FEEDER RELAY
PANEL
PANAL-(6KLA)
RESULT PASS
REMARKS
Tested By Witnessed By Witnessed By
For M/s.ISSPL For M/s. For M/s.
Name: Kamal P Name: Suresh Kumar Name:
Testing Engineer
Date: 25.07.2023
Non- Directional Over current and Earth Fault Relay Page 3 of 3