EHS 00005 R13 Chemical Handling and Storage
EHS 00005 R13 Chemical Handling and Storage
EHS-00005 R13
Hard copy of this document, if not marked “CONTROLLED” in red,
is by definition uncontrolled and may be out of date.
REVISION
Rev DCN No. Change Summary Release DCN Initiator Document
No. (Revised sections are in blue font.) Date Owner
13 DCN2094 Changes made for removing and updating 4-23-21 D. Brookhart T. Diamond
nomenclature, chemical storage, chemical
cabinet usage, inspection, grounding, and
ownership.
Prior revision history, if applicable, is available from the Document Control Office.
1. PURPOSE
To provide minimum requirements for the safe handling and storage of
hazardous chemicals at NY CREATES / SUNY Polytechnic Institute
(SUNY Poly) Albany Facility.
2. SCOPE
2.1 This specification applies to the storage and handling of liquid and solid
chemicals at NY CREATES / SUNY Poly it does not apply to storage and
handling of compressed gases (EHS-00011) or hazardous waste (EHS-
00009).
2.3 Tenant employees, contractors and sub-contractors may comply with their
own organization’s program provided that it meets and/or exceeds the
minimum requirements set forth in this procedure.
3. DEFINITIONS
The following definitions apply to the various hazardous chemicals stored
and handled at the NY CREATES /SUNY Poly Albany facilities:
3.2 Physical Hazard means a chemical for which there is scientifically valid
evidence that it is a combustible liquid, a compressed gas, explosive,
flammable, an organic peroxide, an oxidizer, pyrophoric, unstable
(reactive) or water-reactive.
3.3 Health Hazard means a chemical for which there is statistically significant
evidence based on at least one study conducted in accordance with
established scientific principles that acute or chronic health effects may
occur in exposed individuals. The term “health hazard” includes chemicals
which are carcinogens, toxic or highly toxic agents, reproductive toxins,
3.4 Control Area: Spaces within a building which are enclosed and bounded
by exterior walls, fire walls, fire barriers and roofs, or a combination
thereof, where quantities of hazardous materials not exceeding the
maximum allowable quantities per control area are stored, dispensed,
used or handled.
3.5 Combustible Liquid. A liquid having a closed cup flash point at or above
100oF (38 oC). Combustible liquids shall be subdivided as follows:
3.5.1 Class II. Liquids having a closed cup flash point at or above 100 oF
(38 oC) and below 140oF (60 oC).
3.5.2 Class IIIA. Liquids having a closed cup flash point at or above 140 oF
(60 oC) and below 200 oF (93 oC).
3.5.3 Class IIIB. Liquids having a closed cup flash point at or above 200 oF
(93 oC).
3.6 Flammable Liquid. A liquid having a closed cup flash point below 100 oF
(38 oC). Flammable liquids are further categorized into a group known as
Class I liquids. The Class I category is subdivided as follows:
3.6.1 Class IA. Liquids having a flash point below 73 oF (23 oC) and having a
boiling point below 100 oF (38 oC).
3.6.2 Class IB. Liquids having a flash point below 73 oF (23 oC) and having a
boiling point at or above 100 oF (38 oC).
3.6.3 Class IC. Liquids having a flash point at or above 73 oF (23 oC) and below
100 oF (38 oC).
3.7.2 Absorption. A chemical that has a median lethal dose (LD50) of 200
milligrams or less per kilogram of body weight when administered by
continuous contact 24 hours (or less if death occurs within 24 hours) with
the bare skin of albino rabbits weighing between 2 and 3 kilograms each.
3.7.3 Inhalation. A chemical that has a median lethal concentration (LC50) in air
of 200 parts per million by volume or less of gas or vapor, or 2 milligrams
per liter or less of mist, fume or dust, when administered by continuous
inhalation for 1 hour (or less if death occurs within 1 hour) to albino rats
weighing between 200 and 300 grams each.
3.7.4 Mixtures of these materials with ordinary materials, such as water, might
not warrant classification as highly toxic. While this system is basically
simple in application, any hazard evaluation that is required for the precise
categorization of this type of material shall be performed by experienced,
technically competent persons.
3.8 Oxidizer. A material that readily yields oxygen or other oxidizing gas, or
that readily reacts to promote or initiate combustion of combustible
materials. Examples of other oxidizing gases include bromine, chlorine
and fluorine.
3.8.2 Class 3. An oxidizer that will cause a severe increase in the burning rate
of combustible materials with which it comes in contact or that will undergo
vigorous self-sustained decomposition due to contamination or exposure
to heat.
3.8.3 Class 2. An oxidizer that will cause a moderate increase in the burning
rate or that causes spontaneous ignition of combustible materials with
which it comes in contact.
3.8.4 Class 1. An oxidizer whose primary hazard is that it slightly increases the
burning rate but which does not cause spontaneous ignition when it
comes in contact with combustible materials.
3.9.1 Ingestion. A chemical that has a median lethal dose (LD50) of more than
50 milligrams per kilogram, but no more than 500 milligrams per kilogram
of body weight when administered orally to albino rats weighing between
200 and 300 grams each.
3.9.2 Absorption. A chemical that has a median lethal dose (LD50) of more than
200 milligrams per kilogram but not more than 1,000 milligrams per
kilogram of body weight when administered by continuous contact for 24
hours (or less if death occurs within 24 hours) with the bare skin of albino
rabbits weighing between 2 and 3 kilograms each.
3.9.3 Inhalation. A chemical that has a median lethal concentration (LC50) in air
of more than 200 parts per million but not more than 2,000 parts per
million by volume of gas or vapor, or more than 2 milligrams per liter but
not more than 20 milligrams per liter of mist, fume or dust, when
administered by continuous inhalation for 1 hour (or less if death occurs
within 1 hour) to albino rats weighing between 200 and 300 grams each.
3.10.1 Class 3. Materials that react explosively with water without requiring heat
or confinement.
3.10.2 Class 2. Materials that may form potentially explosive mixtures with water.
3.10.3 Class 1. Materials that may react with water with some release of energy,
but not violently.
4. RESPONSIBILITIES
4.1 It is the responsibility of each NY CREATES / SUNY Poly project manager,
tenant (Tool Owner/operator) or individual who utilizes and/or stores
chemicals at the NY CREATES / SUNY Poly Albany facilities to ensure
that the proper procedures, as detailed below, are followed for handling
and storage of such chemicals. The individual using chemicals is also
considered a hazardous waste generator and is responsible for properly
characterizing, packaging and labeling the waste with the appropriate
hazard information, as described in EHS-00009 Hazardous Waste
Management.
chemicals to arrange for the safe and proper storage of those hazardous
gases and chemicals when received onsite. Hazardous gases and
chemicals should not be delivered to and shall not be stored in office
areas. They should be delivered to the Shipping and Receiving dock
(NFN), where they can be stored temporarily until placed in bulk storage
or delivered to the ultimate user. When delivered to a laboratory or
cleanroom area, the chemicals should be placed into appropriate storage
cabinets prior to use. Hazardous chemicals should only be stored in areas
designed with adequate ventilation, spill control and fire protection
systems.
5. ASSOCIATED DOCUMENTS
5.1 Building and Fire Codes of New York State.
6.2.1 When the area is less than 300 square feet of storage the area must
consist of minimum one-hour fire resistive construction.
6.2.2 When greater than 300 square feet of storage the area must consist of
minimum two-hour fire resistive construction.
6.2.4 Spill containment shall be provided through the use of sills, sumps and/or
drains.
6.2.5 Exhaust ventilation at the rate of one cubic foot per minute per square foot
of floor area, or six air changes per hour, whichever is greater, and
arranged such that exhaust is taken within 12” of the floor.
6.2.6 Exhaust ventilation shall not be re-circulated within the room or building.
6.2.7 Electrical wiring and equipment shall be installed in accordance with the
National Electric Code (NEC). In areas where flammables are stored,
electrical equipment and wiring shall be approved for Class I, Division 1,
hazardous locations.
6.2.14 Any chemical or gas that has been identified as expired or “out of
specification” that cannot be used in the laboratory or on cleanroom tools
must be "RED TAGGED" by the shipping and receiving department or the
gas and chemical handling firm’s personnel upon delivery, or the
responsible chemical user if discovered during storage or use. The
material container must be tagged on all sides (cylinders require only 1
tag). If the “out of specification” material is in a laboratory or in a
cleanroom, it should be either stored in an appropriate cabinet for return to
the supplier or moved to the chemical storage rooms by the gas and
chemical handling firm. Expired material if determined to be unusable
should be sent for disposal as a waste chemical through the NY
CREATES / SUNY Poly’s gas and chemical handlers.
7. IN-USE STORAGE
7.1 For the purpose of this specification, in-use storage refers to those
chemicals which have been removed from the bulk storage areas and/or
are being stored in or near the laboratory, cleanroom or maintenance
areas where they will be used.
7.2.1 No chemicals or gases shall be stored in office areas, with the exception
of small quantities of chemical containing office products such as printer/
copier toner, white board cleaners, or other cleaning products, which are
exempt from these requirements.
7.2.2 Chemical containers should have the date received and first opened for
use noted on them to aid in determining shelf life and product quality.
Many chemicals degrade after exposure to moisture in the air and some,
such as ethyl ether and tetrahydrofuran, form peroxides as a result, which
are unstable and may cause a fire or explosion upon opening the
container.
7.2.3 The storage of hazardous chemicals shall be within fully enclosed storage
cabinets and/or in cabinets under lab hoods and wet benches.
7.2.6.1 Corrosives cabinets (especially those used for storing nitric and/or sulfuric
acids) are exempted from this provision. HDPE or similar engineered
plastic materials provide better resistance to corrosion in the event of a
spill of those materials.
7.2.7 All wiring within flammable cabinets or explosion proof refrigerators must
be in accordance with the NEC.
7.2.8 Specific Chemical hazard labels for each chemical must be attached to
the exterior of the cabinet. If a number of different chemicals are stored in
a cabinet, a listing of the current inventory on a removable sheet that can
be updated regularly is acceptable. The list shall be updated when each
new chemical is added or the use of a listed chemical is discontinued.
Separation of incompatible materials must be maintained.
7.2.9 The bottoms of cabinets utilized for the storage of liquids shall be liquid-
tight to a minimum height of 2 inches.
7.2.12 All chemical storage cabinets on site shall be inspected, cleaned out and
wiped down with a suitable cleaning agent at a minimum annually.
The cabinet owner must maintain a record of the date that the
annual inspection and wipe down was completed.
This shall be coordinated by the individuals responsible for the
storage cabinet.
The maximum weight capacity per cabinet shelf must not be
exceeded.
All chemicals in storage for over a year should be carefully
reviewed by the cabinet owner for chemical purity and continued
need.
o If chemical is determined to be of no use, then dispose of as
hazardous waste.
7.3.1.1 Chemicals may be stored on chemical carts in the NFSX chemical transfer
areas provided that they are either in the process of being used, or
properly stored within the same shift.
8. SEPARATION CLASSIFICATION
8.1 The following are the five general classes of chemicals that must not be
intermingled in the same storage cabinet:
8.2.2 When approved by EHS, some Oxidizers may be stored with Bases.
8.2.3 Strong mineral acids, which are also oxidizers (e.g., fuming Nitric acid),
must never be stored with organic acids or bases, unless segregated
8.3 Flammables/Combustibles
8.3.2 A maximum total of 120 gallons of Class I, Class II, and Class III liquids
may be stored. Of this total, no more than 60 gallons total may be Class I
and Class II liquids (See definitions Sec 3.1, 3.2) may be stored in each
cabinet.
8.3.3 No more than three (3) 60 gallon flammable storage cabinets are allowed
within any area, unless they are separated from the next nearest group of
three cabinets by at least 100 feet. Multiple combinations of storage
cabinet types are allowed provided that no more than 180 gallons of
flammable liquids are stored within the flammable storage cabinets in a
given room.
8.3.5.1 The integrity of the ground shall be tested in accordance with the following
schedule:
8.3.5.2 The EHS Department may keep an inventory list of chemical storage
cabinets at the NY CREATES / SUNY Poly Albany facility.
8.4 Acids
8.4.1 May be stored only within blue acid storage cabinets or acid wet station
cabinets.
8.4.3 The cabinet shelves and its bottom must be constructed or covered with
polyethylene, polypropylene, or similar acid resistant material, with molded
"traps" to catch acid spills.
8.4.5 Inorganic mineral acids (nitric, sulfuric, hydrochloric) and organic acids
(acetic, lactic) shall not be stored in the same cabinet unless segregated
within the cabinet in separate spill containment trays capable of holding
110% of the largest container of each material stored.
8.5 Bases
8.5.1 May be stored only within blue base storage cabinets or base wet station
cabinets.
8.6 Oxidizers
8.6.1 May be stored in blue oxidizer storage cabinets or oxidizer wet station
cabinets.
8.6.2 When approved by EHS, oxidizers may be stored with some bases but
shall never be stored in same cabinet or spill containment area as organic
acids or flammable organics.
8.7 Miscellaneous
8.7.2 The cabinets must be blue and labeled with their contents, and hazards.
8.9.3 The average density of hazardous chemicals within a single control area
or laboratory shall not exceed that listed in Table III. The design and
number of control areas in any given building shall comply with the
requirements set forth in New York State Fire Code Table 2703.8.3.2 -
Appendix G.
9. PERCHLORIC ACID
9.1 Perchloric acid ≥73% forms highly explosive and unstable compounds
with many combustible materials and with metals. Unstable perchlorate
compounds may collect in the duct work of improperly installed fume
hoods and cause fire or violent explosions.
9.2 Perchloric acid should be used with extreme caution and only in a fume
hood designed for its use.
9.5 Only minimum quantities should be kept, with no more than a one pound
bottle in the laboratory at any time. No flammables or organic solvents
should be used in a perchloric acid hood.
9.6 Perchloric acid should not be kept for more than a year since explosive
crystals may form. To verify adherence to this rule the requestor must
place a date on the bottle of perchloric acid as soon as it is received.
Aldehydes
Ethers, especially cyclic ethers and those containing primary and
secondary alcohol groups
Compounds containing benzylic hydrogen atoms (particularly if the
hydrogens are on tertiary carbon atoms)
Compounds containing the allylic structure, including most alkenes.
Vinyl and vinylidene compounds.
10.2 Among the more widely-used compounds which may form peroxides in
storage are:
sodium amide
tetrahydrofuran (THF)
tetrahydronaphthalene
tetralin
vinyl acetate
vinylidene chloride
10.3 Peroxide compounds are very reactive and often highly unstable.
10.5.1.2 Labeled with the date (MM/DD/YY) on which the material was received
and the identity of a responsible employee, group or department.
10.7.1 Ensure that the material is within its approved storage / disposal limits.
10.7.3 Once a container is opened the chemical should be tested for peroxides
not less frequently than once every month and dispose of after six months.
11.1.1 Pyrophoric liquids in quantities greater than 0.4 gallons shall be stored in
an approved flammable storage cabinet or exhausted enclosure that is
constructed of at least 18-gauge steel and is equipped with a highly
sensitive smoke detection device (e.g., VESDA).
11.1.2 If used, the highly sensitive smoke detector shall be tied into the fire alarm
control panel which will page the ERT directly.
11.1.3 Accept delivery from the shipping department and transfer immediately to
the storage location. Unpack vessel from the shipping packaging.
11.1.1 Upon receipt of a pyrophoric liquid the ampoule and inner metal container
should be checked that it is labeled with the name and hazard
classification. If such a label is not present then a GHS or NFPA label must
be attached to identify the name and hazards associated with the
chemical.
11.1.2 Also upon receipt the receiver must attach a ‘status tag’ to the outside of
the ampoule and inner metal container to identify its current state of ‘full,
in-use or empty’.
11.1.5 Emergency response PPE and spill equipment shall be located near the
storage cabinet to allow for immediate emergency response.
11.2 Delivery
11.2.1 Pyrophoric liquids shall be transported on a cart with the ampoule inside a
metal container/housing.
11.2.2 Pyrophoric liquids can only be delivered to the NFN chemical pass-
through between the hours of 9:00am-3:00pm, Monday-Friday and
handed off directly to the person using them. Once received, this material
shall be transported directly to the cabinet and loaded immediately.
11.3 Loading/Unloading/Handling
11.3.2 Wearing the PPE specified in EHS-00010 and only if qualified to do so,
the person loading or unloading the material shall ensure that the area
around them is barricaded.
11.3.4 Once loaded the status tag on the ampoule shall be marked as ‘in use’
and when removed shall be marked as ‘empty’.
11.3.5 Please note that the quantity of pyrophoric liquids at any one workstation
shall be limited to 0.5 gallons.
11.4.2 Emergency response PPE and spill equipment shall be located near the
storage cabinet to allow for immediate emergency response.
11.5.2 Remove the in use / empty labels from the vessel before packing.
11.5.3 Place the vessel in the packing. Seal and label, as required. Bring the
complete package to the shipping location.
The source of the material (i.e., tool, system the material is from),
A contact name and number and,
The date on which the bag was created
12.1.2 The bags may not contain any free liquid or produce any odor.
12.1.3 Hazardous material bags once properly labeled can be stored either in the
fab/subfab or in a designated storage area.
12.1.4 Bags left in the fab/subfab and not in a designated storage area should
not be more than 6 months old. After 6 months the contact on the bag will
be contacted and either asked to remove the bag and place it in a storage
area or deem the bag waste and have it removed as hazardous waste.
13.2 If the material is on the approved chemical list, S&R will contact the
Chemical and Gas handling firm telling them that the chemical has arrived
and ask that they place it into storage. In the event that the material needs
to be placed into storage before it is approved by the EHS department,
S&R must place a ‘jailed/quarantined’ note on the container and/or outer
packaging.
Name of requestor:
Name of the material:
Location to be stored or delivered to:
Hex ID of the tool that will use the chemical:
Approved by EHS: (Y / N)
Date requested:
Date delivered:
Delivered by:
14.2 The requestor should allow at least 12-24 hours for the material to be
delivered. In the event that the material needs to be approved by the EHS
department, the requestor should allow 5-10 business days before the
material can be approved and thereafter delivered.
15. HANDLING
15.1 General
15.1.1 The required Personal Protective Equipment (PPE) must be worn when
using, handling, transferring or transporting chemicals (See EHS-00010).
15.1.2 Ensure all containers, baths, holding tanks, storage cabinets, etc., are
properly labeled. If a chemical is transferred into smaller container or
secondary container, the chemical identification and its associated
hazards must be clearly labeled. Labels can be obtained from label
centers located throughout the facility. Chemical label centers are located
in: each of the clean room gowning rooms; are generally available in the
CESTM labs; and can also be obtained from the EHS office.
15.2.1 When powered industrial lift trucks are necessary, only trained and
authorized operators are allowed to drive a powered industrial truck to
transport chemicals.
15.2.2 When bulk chemicals are transported, only compatible chemicals may be
transported on the same pallet (See Appendix A - Figure 1 for
Compatibility / Separation Matrix).
15.2.3 All boxes on a pallet must be secured before being transported via
motorized or manual pallet movers (e.g., shrink wrap, tie downs, utilization
of tension belts, strapping, or similar means).
15.2.4 When new chemicals are received, every effort must be made to place
them within their proper storage area immediately. In no instance shall
chemicals remain outside of the storage area beyond one shift.
15.2.5 When chemicals are pulled for clean room or laboratory use, they shall be
brought directly to the research area. Those which are not immediately
transferred to the clean room or laboratory area must be stored within the
appropriate chemical cabinets or returned back to the appropriate storage
room.
15.2.7 Once emptied, boxes shall be broken down and removed to the
designated trash dumpster. In no instance shall empty boxes remain
beyond one shift nor shall chemicals be stored inside in a box and inside
the storage cabinet.
15.2.8 Special shipping containers, such as those used for shipping highly toxic
or flammable precursor materials, should be labeled “Hold for return
shipment”. A request should be made to Shipping and Receiving or the
Clean room or Laboratory manager for temporary storage of the container
in the chemical storage area.
15.3.1.2 Dumbwaiters and freight elevators can be used for transport of chemicals,
but shall NEVER be used as a chemical storage location, not even on a
temporary basis.
15.3.1.3 When carrying a one gallon size bottle, it shall be supported by one hand
at the neck of the bottle and one under the bottom. The use of chemical
carriers to move individual bottles is strongly recommended.
15.3.1.4 Multiple small containers (e.g., 20-100 ml or cc, 0.7-3.4 oz.) can be carried
in a chemical carrier or an over pack container of suitable size as long as
chemically compatible.
15.3.1.5 At no time shall either full or empty chemical bottles be transported without
its cover firmly fastened.
15.3.1.6 Empty bottles shall be handled and disposed of in accordance with the
hazardous waste procedures.
15.3.1.7 When two or more gallon size bottles are transported, it shall be by means
of a cart which is constructed of a chemical resistant material.
15.3.1.9 The length or width of the cart shall not exceed 48 inches.
15.3.1.11 Non-compatible chemicals shall not be transported within the same cart,
dumbwaiter, or freight elevator at the same time.
15.3.2.2 Five-gallon drums may be stacked up to three drums high, provided that
the drums are designed for stacking, while they are in bulk storage. No
stacking of drums is allowed for In-Use storage.
15.3.3.1 Larger drums shall be transported by means of a hand truck of tripod style
and designed for the load.
15.3.3.2 Drums shall be transported in the upright position with their bungs/tops
secured. This section, applies to all drums to include full, in-service, and
empty drums.
15.3.3.3 Once emptied, drums shall have an "EMPTY" label affixed, and be treated
as still having the chemical hazard associated with the original chemical
until they have been triple rinsed.
15.3.3.5 Empty drums may be stacked on their sides with both ends secured. They
should only be stored in designated storage areas, and if outside, not
subject to storm water runoff. The stacking of empty drums is limited to
three rows high.
Spill clean-up kits must be prepared and available in the work area.
15.3.5 Exceptions
16.1.1 The stations shall be installed within 25 feet of any hazardous chemical
location or within 10 seconds of travel, must be unobstructed at all times
and have a continuous water supply.
17.1.1 Small chemical spills of known materials (i.e., less than one quart) of low
to moderately hazardous materials can be cleaned up by qualified
laboratory personnel. Larger spills should be cleaned up by ERT, since
larger quantities of spill supplies than typically stored in a laboratory will be
required. In addition, special precautions such as use of PPE may be
needed based on the type and volume of material spilled.
17.2 All chemical leaks must be contained immediately upon discovery, and the
leak source repaired and cleaned up as soon afterward as business
conditions allow. At no time shall a leak be allowed to continue
uncontained.
17.2.1 Only persons who have been deemed qualified shall contain chemical
leaks.
17.2.3 Leaking chemical containers should be clearly labeled to indicate that they
are leaking, and should not be moved without adequate spill containment
Damaged or leaking chemical containers are contained and over-packed if
necessary by the ERT and placed in designated storage areas. If the
leaking container is deemed unfit for use and declared waste, it should be
labeled according to EHS-00009.
18.1.2 Emergency power-off switch (red mushroom “panic” button) controlling all
power to the work station.
18.1.4 Minimum hood face capture velocity shall be 100 fpm and for wet
benches, sinks and hoods which utilize slots in the freeboard area above
the liquid level of the bath shall have minimum slot velocities of 750 fpm
and a minimum capture velocity, 9" above the liquid level at the center of
the chemical bath, of 125 fpm.
18.2.1 Work stations shall be all metal (18-gauge stainless steel minimum)
construction, or Factory Mutual Flame retardant plastic meeting 4910
performance standard.
18.2.2 All stations shall have point of use (in station or directly above)
extinguishing system, either water or Halon/CO2 system. If Halon/CO2
system, both manual and automatic, utilizing UV/IR detectors (not
powered by the emergency off switch).
18.2.3 There must be a means for electrically grounding the hood or work station
to prevent static accumulation.
18.2.4 Electrical equipment & wiring, including lighting inside the hood, shall be
rated for flammable atmospheres, Class I, Division II; or shall be located in
a separate nitrogen-purged area of the work station. The nitrogen purge
must have a flow indicator.
18.3.1 Heaters, or heated work stations must have a primary temperature control,
and an independent over temperature detector tied to the heater power
cut-off. This shall also apply to hotplates used in lab hoods or on lab
bench tops. Power must auto shut off if temperature exceeds 15 degrees
C above the process temperature.
18.3.2 A low liquid level indicator must be interlocked to the heater power. An
optical or nitrogen bubbler type level detector is preferred over floats
because floats may corrode. A bubbler type shall have a nitrogen flow
indicator.
18.3.3 Any heating element which transfers heat by passing fluid through the
heating element must have an appropriate pressure or flow sensor
capable of removing power from the heating element, should flow fall
below a specified limit.
19.2 Placarding
19.2.2 In the event that a package does not have a placard, the S&R department
will place the appropriate placard on the outside of the package before
allowing the HPM to be transported.
19.5 The transport cart must be clearly marked and designated for transporting
compatible materials (e.g., corrosive; flammable).
19.9.1 The transport cart shall be equipped with spill pads for containing and
cleaning up spills of less than a pint.
19.9.2 The transporter shall have knowledge of NY CREATES / SUNY Poly ERT
and the phone number to activate the team should there be a spill of
greater than a pint.
19.9.3 The transporter shall be aware of pull stations and use one in the event
that a situation occurs that is beyond their control, such as a material that
is fuming, smoking or otherwise reacting.
20.2 Chemical carts should be loaded and staged the day prior to expected
delivery. The staging should take place in CUB, HPM Storage building or
NFN receiving area
20.3 While transporting the chemical cart into the building and down hallways
the lead person shall assists with doors and any obstructions while the
second person steers the cart.
20.4 No one is allowed to travel inside ANY elevator while transporting HPM
chemicals.
20.5 Two qualified persons are required for transporting HPM chemicals in
elevators.
20.5.1 A qualified person is one who has been trained in Chemical Handling,
PPE and Emergency Spill Response Procedures.
1. One person stays at the elevator loading floor and the second is in
position at the off-loading floor level.
2. The chemical cart is loaded into the elevator. No one travels inside the
elevator with chemicals. A sign shall be hung on the front of the cart
that reads “Hazardous Materials/Waste in Transport. DO NOT
BOARD’.
3. The person at the off-loading floor calls for the elevator and receives
the cart.
4. The person at the off-loading floor shall wait until the second qualified
person is present to proceed with transportation down hallways.
NFS
NFE
CESTM
20.7.3 Passenger elevators should never be used to transport HPMs in buildings
where chemical elevators are available (NFN, NFX, and NFC). If the
freight elevator is unavailable, EHS must review and approve each
alternate transport request on a case-by-case basis.
20.7.4 HPMs shall not be transported in corridors that have a width of less than
44 inches.
20.8.1 Corridors being used cannot have dead ends and must be equipped with
smoke detection devices, pull stations, and fire alarm horns/strobes.
20.9 Chemicals can be transported into NFS labs within an approved cart in the
NFS passenger elevator between 5:00am and 7:00 am only on Tuesdays
and Thursdays.
20.11 Hazardous Waste removal follows the same process as for chemical
transport.
20.11.1 Chemicals delivered to the NFN loading dock shall be transferred from the
NFN loading dock to the NFE loading dock within one day of delivery.
20.11.3 Chemicals and waste delivered to the NFE loading dock that will not
immediately be transferred to their final destination must be secured in a
flammable or corrosive staging cabinet.
20.11.4 Chemicals delivered to the NFN loading dock shall be transferred from the
NFN loading dock to the CESTM labs within one day of delivery.
20.12.1 HPMs shall be transported from Shipping and Receiving dock on the
second floor of NFN to the second floor CESTM labs.
20.12.2 If chemicals need to be transported to the first or third floor CESTM labs,
the transporter shall use the elevators located in CESTM.
20.13 Hazardous Waste removal from labs in NFE/CESTM follows the same
route and process as outlined for chemical transportation.
20.14 Biosafety materials delivered to the NFN loading dock shall be placed in
refrigerated/freezer storage awaiting pick up and transported directly to
the designated lab(s) in NFE/CESTM.
20.14.1 Biosafety waste shall be picked up from each biosafety lab and
transported by a qualified NY CREATES / SUNY Poly employee, in a
labeled cardboard shipping box, directly to the designated biosafety waste
storage area in the CUB.
21. RECORDS
21.1 Chemical and gas inventory records shall be maintained by the cleanroom
maintenance support group or laboratory manager.
21.4 EHS shall maintain records of training for individuals required to handle
and store chemicals, or clean up chemical spills or leaks.
22. APPENDICES
22.1 Appendix A - Figure 1: HPM Separation Matrix
Toxic __
NR S S S S S S S S
Acid __
1 hr. S S Sc S S Sc S S
__
Base
1 hr. S S S S S S S S
Flammable __
1 hr. S SC S S R S S S
Oxidizers __
1 hr. S S S S S Sc S S
Water
__
Reactives 1 hr. S S S R S S S S
Pyrophoric __
1 hr. S SC S S Sc S S S
NOTES:
b. Hazardous production material gas shall be separated from HPM liquids and solids by a 1-hour fire-barrier or
shall be kept in approved gas cabinets.
The following list of chemicals in the left-hand column should be transported, stored, used, and disposed
of in such a manner that they do not accidentally come in contact with the corresponding chemicals in the
right–hand column. These chemicals could react violently if allowed to come in accidental contact with
each other, resulting in an explosion, or may produce highly toxic and/or flammable gases or vapors.
However, it should be remembered that this list is not in any way complete, but is to serve only as a guide
for the commonly used chemicals.
This is Table 1804.2.1 from the Fire Code of New York State, specific to semiconductor fabrication facilities in
Group H-5.
NOTES:
a. Hazardous materials within piping shall not be included in the calculated quantities.
b. Quantity of hazardous materials in a single fabrication area shall not exceed exempt amounts in Table
2703.1(1) and 2703.1.1(2) in the Fire Code of New York State.
c. The aggregate quantity of flammable, pyrophoric, toxic and highly toxic gases shall not exceed 9,000 cubic
feet at normal temperature and pressure (NTP).
d. The aggregate quantity of pyrophoric gases in the building shall not exceed the amounts set forth in Tables
2703.1(1) and 2703.8.2 in the Fire Code of New York State.
Table 1805.2.1 from the Fire Code of New York State, Chapter 18 – Semiconductor Fabrication Facilities.
NOTES:
a. DOT shipping containers with a capacity of greater than 5.3 gallons shall not be located within a workstation.
b. Maximum allowable quantities shall be increased 100 percent for use-closed systems operations. When Note
c also applies, the increase for both notes shall be allowed.
c. Quantities shall be allowed to be increased 100 percent when workstations are internally protected with an
approved automatic fire-extinguishing or suppression system complying with Chapter 9. When note b also
applies, the increase for both notes shall be allowed.
d. Allowed only in workstations that are internally protected with an approved automatic fire-extinguishing or
suppression system complying with Chapter 9.
Appendix E - Table III (A): (TABLE F2703.1.1(1)) Maximum Allowable Quantity per
Control Area of Hazardous Materials Posing a “Physical” Hazard a,j,m
NOTES:
b. The aggregate quantity in use and storage shall not exceed the quantity listed for storage.
c. The quantities of alcoholic beverages in retail and wholesale sales occupancies shall not be limited providing
the liquids are packaged in individual containers not exceeding 1.3 gallons.
d. Maximum allowable quantities shall be increased 100 percent in buildings equipped throughout with an
approved automatic sprinkler system in accordance with §F903.3.1.1. Where Note e also applies, the
increase for both notes shall be applied accumulatively.
e. Maximum allowable quantities shall be increased 100 percent when stored in approved storage cabinets, gas
cabinets, or exhausted enclosures. Where Note d also applies, the increase for both notes shall be applied
accumulatively.
f. Quantities shall not be limited in a building equipped throughout with an approved automatic sprinkler system.
g. Allowed only in buildings equipped throughout with an approved automatic sprinkler system.
h. Containing not more than the maximum allowable quantity per control area of Class IA, Class IB or Class IC
flammable liquids.
i. Inside a building, the maximum capacity of a combustible liquid storage system that is connected to a fuel-oil
piping system shall be 660 gallons provided such system conforms to this code.
j. Quantities in parenthesis indicate quantity units in parenthesis at the head of each column.
k. A maximum quantity of 200 pounds of solid or 20 gallons of liquid Class 3 oxidizers is allowed when such
materials are necessary for maintenance purposes, operation or sanitation of equipment when the storage
containers and the manner of storage are approved.
l. Net weight of pyrotechnic composition of the fireworks. Where the net weight of the pyrotechnic composition
of the fireworks is not known, 25 percent of the gross weight of the fireworks including packaging shall be
used.
m. For gallons of liquids, divide the amount in pounds by 10 in accordance with §F2703.1.2.
Appendix F - Table III (B): (TABLE F2703.1.1 (1)) Maximum Allowable Quantity per
Control Area of Hazardous Materials Posing a “Health” Hazard a,b,c,j
NOTES:
b. In retail and wholesale sales occupancies, the quantities of medicines, foodstuffs consumer or industrial
products, and cosmetics, containing not more than 50 percent by volume of water-miscible liquids and with the
remainder of the solutions not being flammable, shall not be limited, provided that such materials are
packaged in individual containers not exceeding 1.3 gallons.
c. For storage and display quantities in Group M and storage quantities in Group S occupancies complying with
§F2703.11, see Table F2703.11.1.
d. The aggregate quantity in use and storage shall not exceed the quantity listed for storage.
e. Maximum allowable quantities shall be increased 100 percent in buildings equipped throughout with an
approved automatic sprinkler system in accordance with §F903.3.1.1. Where Note f also applies, the increase
for both notes shall be applied accumulatively.
f. Maximum allowable quantities shall be increased 100 percent when stored in approved storage cabinets, gas
cabinets, or exhausted enclosures. Where Note e also applies, the increase for both notes shall be applied
accumulatively.
g. A single cylinder containing 150 pounds or less of anhydrous ammonia in a single control area in a non-
sprinklered building shall be considered a maximum allowable quantity. Two cylinders, each containing 150
pounds or less in a single control area shall be considered a maximum allowable quantity provided the building
is equipped throughout with an automatic sprinkler system in accordance with §F903.3.1.1.
h. Allowed only when stored in approved exhausted gas cabinets or exhausted enclosures.
i. Quantities in parenthesis indicate quantity units in parenthesis at the head of each column.
j. For gallons of liquids, divide the amount in pounds by 10 in accordance with §F2703.1.2.
Below 1 75 3 1
grade 2 50 2 1
Lower Not Applicable Not Applicable Not Applicable
than 2
NOTES:
a. Percentages shall be of the maximum allowable quantity per control area shown in Table F2703.1.1(1) and
Table F2703.1.1(2), with all increases allowed in the footnotes of those tables.
b. There shall be a maximum of two control areas per floor in Group M occupancies and in buildings or portions
of buildings having Group S occupancies with storage conditions and quantities in accordance with §F2703.11.
c. Fire barriers shall include walls and floors as necessary to provide separation from other portions of the
building.