Design Procedure
Design Procedure
ISBN: 9780070483156
Authors: BHEL (Bharat Heavy Electricals Limited)
9. Design Procedure
R.C. Agarwal
Influence of core diameter, flux density and leg length over various parameters while maintaining the % reactance as constant is
tabulated below:
Parameter Increased core diameter Increased flux density Increased leg length
© McGraw-Hill Education. All rights reserved. Any use is subject to the Terms of Use, Privacy Notice and copyright information.
9.6. Selection of Type of Windings
The windings along with its insulations form the electric circuit of the transformer. Due care must be taken while designing the
windings to ensure its healthiness during normal as well as fault conditions. The windings must be electrically and
mechanically strong to withstand both over-voltage under incidence of surges and mechanical stresses during short-circuit
conditions. The temperature of windings at rated, over-load and short-circuit conditions should be within the limits, ensuring the
proper life of transformer.
The power transformers are manufactured for a very wide range of outputs and voltages and realization of these requirements
is possible only by using different kinds of windings. The following types of windings are used in power transformers.
a. Spiral winding
b. Helical winding
Spiral winding is a medium-current and low-voltage winding. Tertiary winding, of star/star/delta connected power transformer
used for stabilizing purposes and sometimes feeding small loads, could be generally spiral winding.
Helical winding is a high-current and low-voltage winding. Normally, it is used for LV coils of large generator transformers.
When number of turns preclude the use of helical winding, the reversed section winding is used. It is generally used for high-
voltage and low-to medium current rating. Reversed section (disc) winding is usually used up to 132 kV class windings.
Higher voltage windings above 132 kV class are mostly multilayer or interleaved disc winding. Number of layers of layer-type
windings are generally five to nine. Ordinary reversed section disc winding is not suitable for voltage above 132 kV because of
impulse distribution characteristics of winding. However, by doing the interleaving of conductors/turns, impulse distribution
characteristics improves and therefore, interleaved disc windings are used for HV coil above 132 kV class.
a. Tapping range
b. Number of steps
c. Step voltage
d. Current rating
e. Location of tapping
g. Insulation level
h. Type of voltage variation, i.e. constant flux, variable flux and mixed type
Constructional details and various types of tapchangers have been described inChapter 6.
(9.1)
f = frequency in Hz
Therefore, after fixing the core area and flux density, volts per turn is calculated by Eq. (9.1). Then LV (lowest voltage winding)
turns are calculated. LV turns are rounded off to nearest integer and volts per turn is adjusted and new value of flux density is
worked out by back calculation. The number of turns in other windings are determined by the new value of volts per turn.
After deciding the values of current densities, copper area required for each winding is determined. Now suitable number of
parallel conductors or pretransposed cables in both radial and axial direction and their width and thickness are selected, such
as to meet the desired performance values. For large current ratings, pretransposed cables offer the advantage. Conductors of
chosen dimensions must be strong enough to withstand short-circuit forces; also they should not have excessive eddy
currents.
Details of insulation design, method of improvement of voltage stress, etc., have been discussed at length inChapter 5.
© McGraw-Hill Education. All rights reserved. Any use is subject to the Terms of Use, Privacy Notice and copyright information.
(9.2)
where
f = Frequency (Hz)
When HV winding is split as in Fig. 9.2(b), percentage reactance can be calculated by the equation
(9.3)
© McGraw-Hill Education. All rights reserved. Any use is subject to the Terms of Use, Privacy Notice and copyright information.
where b′1 and b″1 stand for lateral dimension of layers of HV windings and a′ is gap between two layers.
(9.4)
The percentage reactance can be calculated, for any coil arrangement, with the help of ampere-turn diagram, as discussed
above. Desired value of reactance can be achieved by suitably altering the various parameters.
The percentage impedance and reactance are practically the same for large transformers, as they have very low winding
resistance. The regulation in the system fixes the highest acceptable impedance and the requirements of transformer
protection, which fixes the lowest acceptable impedance value. It is of interest to note that variation in impedance affects the
cost of transformer. It is difficult to give a specific picture of how transformer economics are affected by variation in
impedance, because this depends upon the relative price of copper and core material, as also the rates at which core-loss and
copper-loss are capitalized. In general, for a given material content, a high impedance value would result in higher copper-loss
and lower iron-loss. In any case, very high impedances are undesirable, as they may give substantially high stray losses,
resulting in hot spots. Low impedance values are desirable where regulation is regarded as most important and on the other
hand, they pose considerable problems for designing the transformer suitable for large mechanical forces developed under
short-circuit conditions. Also, low impedance transformers would require large core diameter, resulting in higher iron-loss, lower
copper-loss and higher transport weight of the largest packet.
(9.5)
N = number of turns.
By putting the corresponding values for different windings in Eq. (9.5), their conductor material weights can be worked out.
The alternating current flow, in the windings, is associated with load-loss comprising I2 R-loss and eddy current loss in the
windings and stray losses in tank, clamping gear, etc. The resistive loss in the windings, i.e. I2 R-loss depends on resistivity of
conductor material, number of turns, and cross-sectional area and length of mean turn of conductor.
(9.6)
By knowing the resistance of each winding, I2 R-loss in various windings can be worked out. Eddy current loss in conductors
depends upon their configuration and stray loss in tank and clamping structure, etc., depends upon leakage flux, and can be
suitably estimated with reasonable accuracy. The load-loss of transformer is a function of temperature and generally
expressed at a reference temperature of 75°C.
© McGraw-Hill Education. All rights reserved. Any use is subject to the Terms of Use, Privacy Notice and copyright information.
The load losses in the transformer consist of losses due to the ohmic resistance of winding and stray losses. These stray
losses take place in the loaded and unloaded windings, clamping framework and transformer tank and depend upon leakage
flux and magnetic field surrounding the leads. The total stray loss in the transformer is generally made up of the following
components.
a. Stray loss in the transformer tank due to leakage flux from the windings.
c. Stray loss in the clamping framework due to leakage flux from the windings.
The component of flux parallel to the axis of coil is termed as axial flux and that perpendicular to the axis of coil is termed as
radial flux. The axial and radial flux densities at various regions can be calculated by various methods such as image method,
Roth method, Rabins method, etc.
Leakage flux going back to core, does not give significant losses and temperature rise. However, the flux impinging upon flat
surface of core, where the flux cuts perpendicular to the lamination, additional losses will take place and can lead to high local
temperatures.
The losses due to leakage field emerging from winding depend upon the amount and intensity of flux, permeability and
resistivity of metallic materials. Low resistivity materials will give rise to higher eddy currents and higher losses. The losses also
depend upon the distance of metallic parts from the source of leakage flux, as with the increased distance the amount and the
intensity of flux is reduced.
In large transformers, a turn in winding consists of large number of conductors. In such an arrangement, unequal voltages are
induced in different conductors due to varying leakage field in radial direction and variation in length of each conductor. The
unequal voltages in parallel strands (conductors) give rise to circulating currents. The losses due to circulating current within a
few stands of turn may not reflect much in overall losses, but still can cause over-heating of strands.
Eddy current and circulating current losses can also take place in idle windings, not connected in load circuit but lying in
leakage field.
The clamp plates made of thin lamination stacks and placed edgewise are ideal for large transformers. Outer packets of core
are also sometimes subdivided to reduce temperature rise on core plates for large rating transformers.
The use of transposed cables for high-current windings result in considerable reduction in stray losses. In high-voltage winding
with moderate current, requiring two or three conductors in parallel, bunched conductors can be used to improve winding space
factor, and to provide subdivision of conductors.
(9.7)
where
The determination of initial voltage distribution is merely the calculation of the various capacitances of windings. The greater
the value of α the greater is the divergence from uniform voltage distribution from line to ground. It is evident that value of α is
high for a small transformer. For transformers of higher rating and especially for higher line voltage, Cg decreases because it is
determined largely by clearances, while Cs increases because of greater radial depth of the winding. Thus, α is lower and initial
voltage distribution is more close to uniform. Due to stress concentration at the ends of winding, a few end turns are provided
with extra insulation. To reduce stress concentration at the ends, disc coil windings are provided with stress rings that act as
radial shields, although they do not materially improve the axial distribution. Axial improvement can be gained by the addition of
shields or by several other means of controlling the electric field distribution. Also refer to Chapter 5, Clause 5.2 for surge
behaviour of windings.
© McGraw-Hill Education. All rights reserved. Any use is subject to the Terms of Use, Privacy Notice and copyright information.
9.19. Mechanical Forces in Windings
When transformer is loaded, the flow of currents in its primary and secondary windings gives rise to leakage flux and mutual
forces between windings. The mechanical repulsive force with normal load currents is low compared to the strength of coils.
Under fault conditions, the forces produced may be increased many times. The design of transformer windings, insulating
cylinders, coil clamping rings, clamping plates, etc., should be such that they are able to withstand these forces. The forces
produced are radial as well as axial. Radial component of force tends to burst outer winding and crush inner windings and axial
component gives bending and compressive stresses. Various forces and their effect have been discussed at length in Chapter
7.
Gradient of the windings can be reduced by providing the directed oil flow, in the case of forced oil cooled transformer. The
gradient in various windings of a transformer are adjusted by suitably altering the winding design to result in economical
cooling equipment and thus overall economy. The design of cooling equipment is to be such that it shall be capable of
delivering the rated MVA, under specified conditions, without exceeding the guaranteed values of top oil temperature rise and
mean winding temperature rise. Top oil temperature rise depends upon mean oil temperature rise and half of the difference in
oil temperatures at the inlet and the outlet of the cooling equipment. Mean winding temperature rise depends upon mean oil
temperature rise and winding gradient. Various types of cooling have been discussed in Chapter 8.
© McGraw-Hill Education. All rights reserved. Any use is subject to the Terms of Use, Privacy Notice and copyright information.
H.V. winding design
© McGraw-Hill Education. All rights reserved. Any use is subject to the Terms of Use, Privacy Notice and copyright information.
Radial dimension of coil
Calculating in the same manner as for HV coil, axial dimension/coil for 32 sections = 252.00
For 9 turns per section, calculating in the same manner as for HV, radial dimension of coil = 29 mm (inclusive of building
tolerance)
LV winding design
© McGraw-Hill Education. All rights reserved. Any use is subject to the Terms of Use, Privacy Notice and copyright information.
Reactance calculation at normal tap (Fig. 9.8)
(9.8)
© McGraw-Hill Education. All rights reserved. Any use is subject to the Terms of Use, Privacy Notice and copyright information.
Figure 9.8 Ampere turns diagram at normal tap position.
© McGraw-Hill Education. All rights reserved. Any use is subject to the Terms of Use, Privacy Notice and copyright information.
Resistance calculations
Eddy current loss and stray losses based on similar past design as 5 kW and 10 kW respectively
Impulse distribution across different sections of coils, temperature gradients of windings and mechanical forces are further
done to ascertain the design adequacy vis-a-vis test requirements.
Example 9.2 Typical design calculations for 20 MVA, 132/66/11 kV, Star/Star/Delta, 3 phase, 50 Hz auto transformer with
onload tappings on HV winding for voltage variation of HV from – 10% to + 10% in 16 steps. Percentage impedance 12.5% on
20 MVA, base.
© McGraw-Hill Education. All rights reserved. Any use is subject to the Terms of Use, Privacy Notice and copyright information.
Current calculations
Series and common windings can be reversed section coils. Tapping winding can be inter-wound spiral coil placed between
common and series windings or elsewhere depending upon the impedance variation required. LV winding can be spiral coil.
Design of these coils can be done in a similar manner. While calculating impedance and other performance, auto factor is to be
used suitably as applicable.
9.22. REFERENCES
© McGraw-Hill Education. All rights reserved. Any use is subject to the Terms of Use, Privacy Notice and copyright information.
9.22. REFERENCES
1. Say, M.G., "Electrical Engineers Reference Book".
3. Blume, L.F., A. Boyajian, G. Camilli, T.C. Lennox, S. Minneci, and V.M. Montsinger, "Transformer Engineering" a Treatise on
the Theory, Operation and Application of Transformers", Book, Chapman and Hald Ltd., London, 1951.
4. Say, M.G., "Performance and Design of AC Machines", Book, Sir Isaac Pitman & Sons, 1962.
5. Narke, D.V., and R.K. Talwar "Paper on Stray Losses in Power Transformer" BHEL, Bhopal.
6. Khosla, A.K., Paper on "Recent Trends in the Design of Large Size Transformers" BHEL, Bhopal.
© McGraw-Hill Education. All rights reserved. Any use is subject to the Terms of Use, Privacy Notice and copyright information.