USER INTERFACE
Reduced SET / Economy LED Fans LED
Permanently on: Energy Saving active Permanently on: fans active
Flashing: Reduced SET active Off: otherwise
Quick flashing: access to level2 parameters
Off: otherwise
Compressor LED Defrost LED
Permanently on: compressor active Permanently on: defrost active
Flashing: a delay, a protection or a Flashing: manual or D.I. activation
EWPLUS EO LVD locked start-up Off: otherwise
Off: otherwise
Alarm LED Aux LED
Permanently on: alarm active Permanently on: Aux output active
Flashing: alarm acknowledged Flashing: Deep Cooling cycle active
NOTE Off: otherwise Off: Aux output not active
When switched on, the device performs a Lamp Test; the °C LED °F LED
display and LEDs will flash for several seconds to check that
they all function correctly. Permanently on: °C setting (dro = 0) Permanently on: °F setting (dro = 1)
Off: otherwise Off: otherwise
KEYs
set
UP DOWN STAND-BY (ESC) SET (ENTER)
Press and release Press and release Press and release Press and release
• Scroll menu items • Scroll menu items • Returns to the previous menu level • Displays alarms (if active)
• Increases values • Decrease values • Confirms parameter value • Opens Machine Status menu
Press for at least 5 sec Press for at least 5 sec Press for at least 5 sec Press for at least 5 sec
• Activates the Manual Defrost function • Function can be configured by the user • Activates the Standby function (OFF) • Opens Programming menu
(see parameter H32) (when outside the menus) • Confirm commands
MOUNTING - DIMENSIONS
The device is designed for panel mounting. Drill a 29x71 mm hole and insert the instrument; secure it with the special brackets
provided. Do not install the instrument in damp and/or dirty places; in fact, it is suitable for use in places with ordinary or normal levels
of pollution. Keep the area around the instrument cooling slots adequately ventilated.
70mm
29mm
71mm
74mm
67mm
32mm
EN
CONNECTIONs
EWPlus 961 EO LVD TERMINALs
EWPLUS 961 LVD
TTL D.I.2
2-3 Compressor relay ( )
(A)
A 3-4 230Va power supply input
230Va (±10%)
4.5W
N-L 230Va power supply
2 3 4 9 10 11 9-10 Pb1 probe
11-10 Digital Input 1 (H11≠0)
TTL TTL input or Digital Input 2 (H12≠0)
D.I.1
Pb1
N
L
Pb1
Pb1
APPLICATIONS TABLE
F = Functions EWPlus 961 EO LVD EWPlus 971 EO LVD EWPlus 974 EO LVD
H = Inputs and Outputs
R = Relay Output APP. 1 APP. 2 APP. 3 APP. 4 APP. 1 APP. 2 APP. 3 APP. 4 APP. 1 APP. 2 APP. 3 APP. 4
Power-on + set
set
RESET PROCEDURE
EWPlus EO LVD instruments can be RESET and the default factory settings restored in a simple and user-friendly way. Simply reload
one of the basic applications by following the procedure described in the paragraph "Loading default applications".
You may need to RESET the instrument in special circumstances in which the normal operation of the instrument is compromised or
if you decide to restore the instrument to its default configuration (e.g. Application 1 values).
IMPORTANT!: This operation resets the instrument to its initial state, returning all the parameters to their default
! factory values. This means that all changes made to operating parameters will be lost.
ON ON
OFF OFF
dFL dFL
Volt Volt
SPL SPL+dFL SPH-dFL SPH
SPH
SPH-dFL
... ...
SPL+dFL
SPL
ON ... ...
OFF
FIG.1) BOTTLE COOLER OPEN FRONT (ESt = 4) FIG.2) BOTTLE COOLER GLASS DOOR (ESt = 5)
°C °C ENVIRONMENTALLY OPTIMISED
ENVIRONMENTALLY OPTIMISED
8°C 8°C
6°C
6°C
ON
ON OFF
OFF
SPn
SPn SEt
SEt ON
SPF
OFF
QUICK
ON cdt dnt
CHILL
OFF
dnt dFt
FAST
COOLING
°C ENVIRONMENTALLY OPTIMISED
ON
7°C OFF
2 12 24 26 36 48 50
0
6°C
(h)
ON
OFF ON
OFF
SPn
cdt dnt
SEt
ON
OFF Fon/FoF Fon/FoF Fon/FoF Fnn/FnF Fon/FoF
Fnn/FnF
cdt
OFF
toS
set set
set
LOCK SETPOINT MODIFICATION: The keypad can be locked by programming the ‘LOC’ parameter.
With the keypad locked you can still access the ‘Machine Status’ menu by pressing set to display
the Set point, but you cannot edit them. To disable the keypad lock, repeat the locking procedure.
When labels Pb1 or Pb2* are present, press the set key to view the value measured by the
DISPLAYING THE PROBES:
corresponding probe.
N.B.: 1) Pb2 is only present on EWPlus 971/974 EO LVD models.
2) the value cannot be modified.
PROGRAMMING MENU
To access the “Programming” menu, press the set key for more than 5 seconds. If specified, an access PASSWORD will be requested:
PA1 for “User” parameters and PA2 for “Installer” parameters (see “PASSWORD” paragraph).
“User” parameters: When accessed, the display will show the first parameter (e.g. “diF”). Press and to scroll through all the
parameters on the current level. Select the desired parameter by pressing set . Press and to modify it and set to save the
changes.
“Installer” parameters: When accessed, the display will show the first folder (e.g. “CP”). Press and to scroll through the
folders on the current level. Select the desired folder using set . Press and to scroll through the parameters in the current
folder and select the parameter using set . Press and to modify it and set to save the changes.
N.B.: Make sure you switch the instrument off and on again each time the parameter configuration is changed, in order to
prevent malfunctioning in the configuration and/or timing in progress.
PASSWORD
Password PA1: used to access “User” parameters. The password is not enabled by default (PS1=0).
To enable it (PS1≠0): press and hold set for longer than 5 seconds, scroll through the parameters using and until you see
the label PS1, press set to display the value, modify it using and , then save it by pressing set or .
If enabled, it will be required in order to access the User parameters.
Password PA2: used to access “Installer” parameters. The password is enabled by default (PS2=15).
To modify it (PS2≠15): press and hold set for longer than 5 seconds, scroll through the parameters using and until you
see the label PA2, press set , set the value to “15” using and , then confirm using set . Scroll through the folders until you
find the label diS and press set to enter. Scroll through the parameters using and until you see the label PS2, press set to
display the value, modify it using and , then save it by pressing set or .
The visibility of “PA2” is as follows:
1) PA1 and PA2 ≠ 0: Press and hold set for longer than 5 seconds to display PA1 and PA2. It will then be possible to decide whether
to access the “User“ parameters (PA1) or the “Installer“ parameters (PA2).
2) Otherwise: The password PA2 is amongst the level1 parameters. If enabled, it will be required when accessing the Installer
parameters; to enter it, proceed as instructed for password PA1.
N.B.: If the password entered is incorrect, the label PA1/PA2 will be displayed again and the procedure will need to be repeated.
DOWNLOAD
OR
UPLOAD
ALARMS
Label Fault Cause Effects Remedy
• Display label E1
• Alarm icon permanently on
• measured values are outside operating
Probe1 faulty • check probe wiring
E1 range • Disable max/min alarm controller
(cold room) • replace probe
• Probe faulty/short-circuited/open • Compressor operation based on parameters
'Ont' and 'OFt'.
Probe2 faulty • Display label E2
(defrost) • measured values are outside operating • Alarm icon permanently on
• check probe wiring
E2 range • The Defrost cycle will end due to Timeout (dEt)
• replace probe
only on • Probe faulty/short-circuited/open • The evaporator fans will work in Duty Cycle
EWPlus971/974 EO LVD mode.
Alarm for HIGH value read by Pb1 > HAL after time of tAO. • Recording of label AH1 in folder AL • Wait until value read by Pb1 returns below
AH1
Pb1 temperature (see “MAX/MIN TEMPERATURE ALARMs") • No effect on regulation HAL-AFd.
Alarm for LOW value read by Pb1 < LAL after time of tAO. • Recording of label AL1 in folder AL • Wait until value read by Pb1 returns above
AL1
Pb1 temperature (see “MAX/MIN TEMPERATURE ALARMs") • No effect on regulation LAL+AFd.
• Recording of label EA in folder AL
digital input activation • check and remove the external cause which
EA External Alarm • Alarm icon permanently on
(H11 = ±5) triggered the alarm on the D.I.
• Regulation locked if rLO = y
digital input activation • Recording of label Opd in folder AL
• close the door
OPd Door open alarm (H11 = ±4) • Alarm icon permanently on
• delay function defined by OAO
(for longer than tdO) • Controller locked
end of defrost cycle due to timeout rather
end of defrost • Recording of label Ad2 in folder AL • wait for the next defrost cycle for automatic
Ad2 than due to defrost end temperature being
cycle due to timeout • Alarm icon permanently on return
recorded by probe Pb2.
activation of the defrost for temperature
end of defrost • Recording of label Ad3 in folder AL • wait for the next defrost cycle for automatic
Ad3 independently dAt.
cycle due to timeout • Alarm icon permanently on return
(active if dCt = 3)
• Display label HiP
HIGH voltage Voltage value read by the analog input is • wait for the value read by the analog input
HiP • Alarm icon permanently on
alarm higher than the SPH value. returns below SPH-dFL
• Regulation locked depending on SoU value.
• Display label LoP
LOW voltage Voltage value read by the analog input is • Wait for the value read by the analog input
LoP • Alarm icon permanently on
alarm lower than the SPL value. returns above SPL+dFL
• Regulation locked depending on SoU value.
If the number N of pressure switch activations is
Activation of pressure alarm by general N<PEn: • check and remove the cause which
General pressure
nPA pressure switch. • Recording of folder nPA in folder AL, triggered the alarm on the D.I.
switch alarm
(H11 = ±7) with the number of pressure switch activations (Automatic Reset)
• Regulation locked (Compressor and Fans)
If the number N of pressure switch activations is
N=PEn: • Switch the device off and back on again
Activation of pressure alarm by general
General pressure • Display label PAL • Reset alarms by entering the functions folder
PAL pressure switch.
switch alarm • Recording of label PA in folder AL and selecting the rAP function
(H11 = ±7)
• Alarm icon permanently on (Manual Reset)
• Regulation locked (Compressor and Fans)
Minimum temperature alarm Temp. ≤ Set + LAL * Temp. ≤ LAL (LAL with sign)
Maximum temperature alarm Temp. ≥ Set + HAL ** Temp. ≥ HAL (HAL with sign)
Temp. ≥ Set + LAL + AFd or
Returning from minimum temperature alarm Temp. ≥ LAL + AFd
≥ Set - ILALI + AFd (LAL < 0)
Returning from maximum temperature alarm Temp. ≤ Set + HAL - AFd (HAL > 0) Temp. ≤ HAL - AFd
* if LAL is negative, Set + LAL < Set
** if HAL is negative, Set + HAL < Set
EWPlus EO LVD 10/12
TECHNICAL DATA (EN 60730-2-9)
Classification: control device (not safety) to integrate
Mounting: panel mounting with 71x29 mm (+0.2/-0.1 mm) drilling template
Control type: 1.B
Pollution rating: 2
Material class: IIIa
Overvoltage category class: II
Nominal impulsive voltage: 2500V
Temperature: Operating: –5 … +55 °C - Storage: –30 … +85 °C
Power Supply: 230Va (±20%) 50/60 Hz
Consumption: 4,5W max
Digital Output (relays): please refer to the device label
Fire resistance class: D
Software class: A
NOTE: check the power supply specified on the instrument label; for relay, power supply capacities and PTC probes, contact
the Sales Office.
FURTHER INFORMATIONS
Input Characteristics
Display Range: NTC: –50.0°C ... +110°C (on display with 3 digit + sign)
Accuracy: Better than 0,5% of full-scale + 1 digit
Resolution: 0,1 °C
Buzzer: YES (it depends from model)
Analogue Input: 1 NTC (EWPlus 961 EO LVD) or 2 NTC (EWPlus 971/974 EO LVD)
Digital Input: 2 voltage-free digital inputs (D.I.1 and D.I.2)
NOTE: D.I.2, if activated, should be connected to terminals 1-2 of the TTL connector (H12 ≠ 0)
Output Characteristics
Digital Output: EWPlus 961 EO LVD: 1 Compressor relay: UL60730-1 12 (8)A max 250Va
UL60730 2Hp (12FLA - 72LRA) max 240Va
EWPlus 971 EO LVD: 1 Compressor relay: UL60730-1 12 (8)A max 250Va
UL60730 (A) 2Hp (12FLA - 72LRA) max 240Va
1 AUX relay: N.A. 8(4)A - N.C. 6(3)A max 250Va
EWPlus 974 EO LVD: 1 Compressor relay: UL60730-1 12 (8)A max 250Va
UL60730 (A) 2Hp (12FLA - 72LRA) max 240Va
1 Fans relay: N.A. 8(4)A - N.C. 6(3)A max 250Va
1 AUX relay: 5(2)A max 250Va
Mechanical Characteristics
Casing: PC+ABS UL94 V-0 resin casing, polycarbonate window, thermoplastic resin keys
Dimensions: front panel 74x32 mm, depth 59 mm (without terminals)
Terminals: screw/disconnectable terminals for cables with a diameter of 2.5mm2
Connectors: TTL for connection of Copy Card + D.I.2
Humidity: Use / Storage: 10…90% RH (non-condensing)
LVD Characteristics
Power voltage reading accuracy: +3% -2%
Power voltage measuring method: Peak-value voltmeter
BUS ADAPTER: compatible with low-consumptation model only (BUS ADAPTER 350)
Regulations
Electromagnetic compatibility: The device conforms to Directive 2004/108/EC
Safety: The device conforms to Directive 2006/95/EC
Food Safety: The device complies with standard EN 13485 as follows:
- suitable for storage
- application: air
- climate range A
- measurement class 1 in the range from -25°C to 15°C
(exclusively using Eliwell NTC probes)
NOTE: The technical specifications given in this document regarding measurement (range, accuracy, resolution, etc.) refer to the
instrument and not to any accessories provided, such as the probes.
This means, for example, that the error introduced by the probe must be added to the typical error of the instrument.
ELECTRICAL CONNECTIONs
Attention! Make sure the machine is switched off before working on the electrical connections.
The instrument is equipped with screw or disconnectable terminal blocks for connecting electrical cables with a max. diameter of
2.5 mm2 (one wire per terminal for power connections): for the terminal ratings, see the label on the instrument. Do not exceed the
maximum permissible current; in case of higher loads, use a suitably rated contactor.
Make sure the power supply voltage complies with that required by the instrument.
Probes have no connection polarity and can be extended using a normal bipolar cable (note that the extension of the probes influences
the electromagnetic compatibility - EMC - of the instrument: take great care with the wiring).
Probe cables, power supply cables and the TTL serial cable should be routed separately from power cables.
DISCLAIMER
This document is the exclusive property of ELIWELL CONTROLS SRL and may not be reproduced or circulated unless expressly
authorised by ELIWELL CONTROLS SRL itself. Every care has been taken in preparing this document; nevertheless ELIWELL
CONTROLS SRL cannot accept liability for any damage resulting from its use.
The same applies to any person or company involved in preparing and editing this document.
ELIWELL CONTROLS SRL reserves the right to make aesthetic or functional changes at any time without notice.
CONDITIONS OF USE
Permitted use
For safety reasons, the instrument must be installed and used according to the instructions supplied and, in particular, parts under
dangerous voltages must not be accessible in normal conditions. The device must be adequately protected from water and dust
with regard to its application, and must only be accessible using tools (except for the front panel). The device is suitable for use
in household refrigeration appliances and/or similar equipment and has been tested for safety aspects in accordance with the
harmonised European reference standards.
Improper use
Any use other than that expressly permitted is prohibited. The relay contacts provided are of a functional type and subject to failure:
any protection devices required by product standards, or suggested by common sense for obvious safety requirements, must be
installed externally to the instrument.