EWPlus EO LVD - EN

This document describes an EWPlus 961/971/974 EO LVD controller that offers energy saving algorithms for refrigerated cabinets. It has LED indicators for reduced setpoint/economy mode, fans status, compressor status, defrost status, alarms, auxiliary output, Celsius/Fahrenheit temperature units. It can be mounted in a panel and has terminals to connect probes, power supply, compressor relay, auxiliary relay, fans relay, and digital/TTL inputs.

Uploaded by

norbertscribd
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
627 views12 pages

EWPlus EO LVD - EN

This document describes an EWPlus 961/971/974 EO LVD controller that offers energy saving algorithms for refrigerated cabinets. It has LED indicators for reduced setpoint/economy mode, fans status, compressor status, defrost status, alarms, auxiliary output, Celsius/Fahrenheit temperature units. It can be mounted in a panel and has terminals to connect probes, power supply, compressor relay, auxiliary relay, fans relay, and digital/TTL inputs.

Uploaded by

norbertscribd
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 12

EWPlus 961/971/974 EO LVD

Versatile high-performance controllers thanks to the new


Energy Saving algorithms for plug-in refrigerated cabinets.

USER INTERFACE
Reduced SET / Economy LED Fans LED
Permanently on: Energy Saving active Permanently on: fans active
Flashing: Reduced SET active Off: otherwise
Quick flashing: access to level2 parameters
Off: otherwise
Compressor LED Defrost LED
Permanently on: compressor active Permanently on: defrost active
Flashing: a delay, a protection or a Flashing: manual or D.I. activation
EWPLUS EO LVD locked start-up Off: otherwise
Off: otherwise
Alarm LED Aux LED
Permanently on: alarm active Permanently on: Aux output active
Flashing: alarm acknowledged Flashing: Deep Cooling cycle active
NOTE Off: otherwise Off: Aux output not active
When switched on, the device performs a Lamp Test; the °C LED °F LED
display and LEDs will flash for several seconds to check that
they all function correctly. Permanently on: °C setting (dro = 0) Permanently on: °F setting (dro = 1)
Off: otherwise Off: otherwise

KEYs

set
UP DOWN STAND-BY (ESC) SET (ENTER)
Press and release Press and release Press and release Press and release
• Scroll menu items • Scroll menu items • Returns to the previous menu level • Displays alarms (if active)
• Increases values • Decrease values • Confirms parameter value • Opens Machine Status menu
Press for at least 5 sec Press for at least 5 sec Press for at least 5 sec Press for at least 5 sec
• Activates the Manual Defrost function • Function can be configured by the user • Activates the Standby function (OFF) • Opens Programming menu
(see parameter H32) (when outside the menus) • Confirm commands

MOUNTING - DIMENSIONS
The device is designed for panel mounting. Drill a 29x71 mm hole and insert the instrument; secure it with the special brackets
provided. Do not install the instrument in damp and/or dirty places; in fact, it is suitable for use in places with ordinary or normal levels
of pollution. Keep the area around the instrument cooling slots adequately ventilated.

70mm
29mm

71mm

74mm
67mm

32mm

EN
CONNECTIONs
EWPlus 961 EO LVD TERMINALs
EWPLUS 961 LVD
TTL D.I.2
2-3 Compressor relay ( )
(A)
A 3-4 230Va power supply input
230Va (±10%)
4.5W
N-L 230Va power supply
2 3 4 9 10 11 9-10 Pb1 probe
11-10 Digital Input 1 (H11≠0)
TTL TTL input or Digital Input 2 (H12≠0)

D.I.1
Pb1
N
L

EWPlus 971 EO LVD TERMINALs


EWPLUS 971 LVD 2-3 Compressor relay ( )
TTL D.I.2
3-4 230Va power supply input
(A) (B)
A
230Va (±10%)
4.5W
N-L 230Va power supply
5-6 N.O. AUX relay ( )
2 3 4 5 6 7 8 9 10 11
5-7 N.C. AUX relay ( )
8-10 Pb2 probe
D.I.1
Pb2

Pb1

9-10 Pb1 probe


N
L 11-10 Digital Input 1 (H11≠0)
TTL TTL input or Digital Input 2 (H12≠0)

EWPlus 974 EO LVD TERMINALs


1-3 AUX relay ( )
EWPLUS 974 LVD
TTL D.I.2 2-3 Compressor relay ( )
Max 17A
(C) (A)
230Va (±10%)
(B)
A 3-4 230Va power supply input
4.5W
N-L 230Va power supply
1 2 3 4 5 6 7 8 9 10 11 5-6 N.O. Fans relay ( )
5-7 N.C. Fans relay ( )
8-10 Pb2 probe
D.I.1
Pb2

Pb1

N 9-10 Pb1 probe


L
11-10 Digital Input 1 (H11≠0)
TTL TTL input or Digital Input 2 (H12≠0)

APPLICATIONS TABLE
F = Functions EWPlus 961 EO LVD EWPlus 971 EO LVD EWPlus 974 EO LVD
H = Inputs and Outputs
R = Relay Output APP. 1 APP. 2 APP. 3 APP. 4 APP. 1 APP. 2 APP. 3 APP. 4 APP. 1 APP. 2 APP. 3 APP. 4

F - End defrost by time X X X X X X X X X X X X


F - End defrost by temperature X X X X X X X X
F - Alarm on Pb1 X X X X X X X X X X X X
F - Supply voltage control X (*) X (*) X (*)
H - Pb1 present X X X X X X X X X X X X
H - Pb2 present X X X X X X X X
H - Pb3 / D.I.1 enabled D.I.1 D.I.1 D.I.1 D.I.1 D.I.1 D.I.1 D.I.1 D.I.1 D.I.1 D.I.1 D.I.1 D.I.1
R - Compressor X X X X X X X X X X X X
R - Defrost X X
R - Fans X X X X
R - AUX X X X X X
R - Condenser fans reversion X
(*) The parameters which manage the function are not included in the vectors. Their value will remain unvaried in case the vector changes.

EWPlus EO LVD 2/12


LOADING DEFAULT APPLICATIONs
The procedure used to load one of the default applications is:
• when the instrument switches on, press and hold the set key: the label “AP1” will appear;
• scroll through the various applications (AP1-AP2-AP3-AP4) using the and keys;
• select the desired application using the key set (“AP3” in the example) or cancel the procedure by pressing the key ;
alternatively wait for the timeout;
• if the operation is successful, the display will show “y”, otherwise “n” will appear;
• after a few seconds the instrument will return to the main display.

Power-on + set

set

RESET PROCEDURE
EWPlus EO LVD instruments can be RESET and the default factory settings restored in a simple and user-friendly way. Simply reload
one of the basic applications by following the procedure described in the paragraph "Loading default applications".
You may need to RESET the instrument in special circumstances in which the normal operation of the instrument is compromised or
if you decide to restore the instrument to its default configuration (e.g. Application 1 values).

IMPORTANT!: This operation resets the instrument to its initial state, returning all the parameters to their default
! factory values. This means that all changes made to operating parameters will be lost.

SUPPLY VOLTAGE CONTROL


The supply voltage can be monitored by means of a dedicated analog input.
When the voltage is lower than the minimum threshold value (set by parameter SPL) or when it exceeds the maximum threshold
value (set by parameter SPH), the outputs are deactivated (one, two or all outputs, depending on the value set at parameter SoU).
When the voltage exceeds the value SPL+dFL or when it is lower than the value SPH-dFL, the outputs are activated again, taking into
consideration also the delays possibly set. If SPL/SPH=0, the low/high voltage control is deactivated.
Here below you can find the regulation diagrams and an example of the functioning of the compressor:
REGULATOR
OUT OUT

ON ON
OFF OFF
dFL dFL
Volt Volt
SPL SPL+dFL SPH-dFL SPH

Example of COMPRESSOR FUNCTIONING


SUPPLY
VOLTAGE

SPH
SPH-dFL
... ...

SPL+dFL
SPL

ON ... ...
OFF

EWPlus EO LVD 3/12


ENERGY SAVING / SWITCH-ON FOLLOWING A POWER FAILURE
The "Energy Saving" function can be enabled by keystroke (DOWN or ESC), by digital input (DI1 or DI2) or remotely.
The operating algorithms are determined by the ESt and ESA parameters. The Economy LED ( ) will light up in all cases in which the
function is active. The ESt parameter determines the type of application to be controlled (see FIG.1, FIG.2 and FIG.3) while the ESA para-
meter switches the LIGHT on or off (AUX output). Energy Saving can also be enabled by a "virtual" door switch.
The ESP parameter determines the sensitivity of the controller, while the dOt parameter determines how long the "virtual" door switch must
remain open for. When the time dOt expires, the door is deemed closed and normal temperature control resumes.
NOTES: 1) if ESP > 0, dOt MUST be > 0.
2) at the end of an Energy Saving period the controller will implement an optimised algorithm that will gradually restore the
temperature to the SEt value (normal operation).
If ESt = 5, after a power failure the instrument will always work in standard mode (day) until the first closing of the door. In the absence of
a door opening / closing, after a time Cdt, the device will always work in Economy mode (Energy Saving) for a period equal to: dnt.

FIG.1) BOTTLE COOLER OPEN FRONT (ESt = 4) FIG.2) BOTTLE COOLER GLASS DOOR (ESt = 5)
°C °C ENVIRONMENTALLY OPTIMISED
ENVIRONMENTALLY OPTIMISED
8°C 8°C

6°C
6°C

ON

ON OFF

OFF
SPn

SPn SEt

SEt ON
SPF
OFF
QUICK
ON cdt dnt
CHILL
OFF

dnt dFt
FAST
COOLING

FIG.3) VERTICAL DISPLAY CABINET WITH DOOR (ESt = 6)

°C ENVIRONMENTALLY OPTIMISED
ON
7°C OFF
2 12 24 26 36 48 50
0
6°C
(h)

ON

OFF ON
OFF
SPn
cdt dnt
SEt

ON
OFF Fon/FoF Fon/FoF Fon/FoF Fnn/FnF Fon/FoF
Fnn/FnF

cdt

AUTOMATIC DEEP COOLING CYCLE - DCC (dCA = 2)

On activation of DCC (Deep Cooling Cycle), the °C


compressor controller will regulate in relation to the
Sid
setpoint dCS, with a differential equal to the value
diF; the interval between defrosts is reset to zero and SEt
defrosts are disabled.
dCS
If tdC = 0, DCC will end when the setpoint dCS is
reached. SEt

If tdC ≠ 0, DCC will end after a time set in parameter dCS


tdC. ON

OFF

toS

EWPlus EO LVD 4/12


ACCESSING AND USING THE MENUs
Resources are organised into 2 menus which are accessed as explained below:
• “Machine Status” menu: press and release the set key.
• “Programming” menu: press for at least 5 secs the set key.
Either do not press any keys for 15 seconds (time-out) or press the , key once, to confirm the last value displayed and return to
the previous screen.

"MACHINE STATUS" MENU


Access the Machine Status menu by pressing set and releasing the key. If no alarms are active, the “SEt” label appears.
Use the keys and to scroll through all the folders in the menu:

set - AL: alarms folder (only visible if an alarm is active);


- SEt: Setpoint setting folder;
- Pb1: probe 1 - Pb1 folder;
- Pb2: probe 1 - Pb2 folder* (EWPlus 971/974 EO LVD models only);
- Pb3: power supply value folder.
* folder displayed if Pb2 present (H42 = y)
SETPOINT SETTING: To display the Setpoint value press the set key when the “SEt” label is displayed. The Setpoint value
appears on the display. To change the Setpoint value, press the and keys within 15 seconds.
Press set to confirm the modification.

set set

set

LOCK SETPOINT MODIFICATION: The keypad can be locked by programming the ‘LOC’ parameter.
With the keypad locked you can still access the ‘Machine Status’ menu by pressing set to display
the Set point, but you cannot edit them. To disable the keypad lock, repeat the locking procedure.
When labels Pb1 or Pb2* are present, press the set key to view the value measured by the
DISPLAYING THE PROBES:
corresponding probe.
N.B.: 1) Pb2 is only present on EWPlus 971/974 EO LVD models.
2) the value cannot be modified.

PROGRAMMING MENU
To access the “Programming” menu, press the set key for more than 5 seconds. If specified, an access PASSWORD will be requested:
PA1 for “User” parameters and PA2 for “Installer” parameters (see “PASSWORD” paragraph).
“User” parameters: When accessed, the display will show the first parameter (e.g. “diF”). Press and to scroll through all the
parameters on the current level. Select the desired parameter by pressing set . Press and to modify it and set to save the
changes.
“Installer” parameters: When accessed, the display will show the first folder (e.g. “CP”). Press and to scroll through the
folders on the current level. Select the desired folder using set . Press and to scroll through the parameters in the current
folder and select the parameter using set . Press and to modify it and set to save the changes.
N.B.: Make sure you switch the instrument off and on again each time the parameter configuration is changed, in order to
prevent malfunctioning in the configuration and/or timing in progress.

PASSWORD
Password PA1: used to access “User” parameters. The password is not enabled by default (PS1=0).
To enable it (PS1≠0): press and hold set for longer than 5 seconds, scroll through the parameters using and until you see
the label PS1, press set to display the value, modify it using and , then save it by pressing set or .
If enabled, it will be required in order to access the User parameters.
Password PA2: used to access “Installer” parameters. The password is enabled by default (PS2=15).
To modify it (PS2≠15): press and hold set for longer than 5 seconds, scroll through the parameters using and until you
see the label PA2, press set , set the value to “15” using and , then confirm using set . Scroll through the folders until you
find the label diS and press set to enter. Scroll through the parameters using and until you see the label PS2, press set to
display the value, modify it using and , then save it by pressing set or .
The visibility of “PA2” is as follows:
1) PA1 and PA2 ≠ 0: Press and hold set for longer than 5 seconds to display PA1 and PA2. It will then be possible to decide whether
to access the “User“ parameters (PA1) or the “Installer“ parameters (PA2).
2) Otherwise: The password PA2 is amongst the level1 parameters. If enabled, it will be required when accessing the Installer
parameters; to enter it, proceed as instructed for password PA1.
N.B.: If the password entered is incorrect, the label PA1/PA2 will be displayed again and the procedure will need to be repeated.

MANUAL DEFROST CYCLE ACTIVATION


Hold down the . key for longer than 5 seconds. It is only activates if the temperature conditions are fulfilled.
Otherwise, the display will flash three times to indicate that the operation will not be performed.

EWPlus EO LVD 5/12


INSTRUMENT ON/OFF
The instrument can be switched off by pressing the key for longer than 5 seconds.
In this condition, the adjustment algorithms and defrost cycles are disabled and the text “OFF” will appear on the display.

USING THE UNICARD/COPYCARD


The Unicard/Copycard is connected to the serial port (TTL) and allows rapid programming of the instrument parameters.
Access “Installer” parameters by entering PA2, scroll through the folders using and until folder FPr appears.
Select it using set , scroll through the parameters using and , then select the function using set (e.g. UL).
• Upload (UL): Select UL and press set . This function uploads the programming parameters from the instrument to the card.
If the procedure is a success, “y”, will appear on the display, otherwise “n” will appear.
• Format (Fr): This command is used to format the Unicard/Copycard, (recommended when using the card for the first time).
IMPORTANT: the Fr parameter deletes all data present. This operation cannot be cancelled.
• Download: Connect the Unicard/Copycard when the instrument is switched off. At power-on, data is downloaded from the
Unicard/Copycard to the instrument automatically. At the end of the lamp test, the display will show “dLy” if the
operation was successful and “dLn” if not.
N.B.: After downloading, the instrument works with the settings of the new map just downloaded.

DOWNLOAD
OR
UPLOAD

TABLE OF "USER" MENU PARAMETERs


EWPlus 961 EO LVD EWPlus 971 EO LVD EWPlus 974 EO LVD
PAR. DESCRIPTION RANGE M.U.
AP1 AP2 AP3 AP4 AP1 AP2 AP3 AP4 AP1 AP2 AP3 AP4
SEt Temperature control SEtpoint LSE ... HSE °C/°F 3,5 3,5 3,5 3,5 3,5 1,5 1,0 3,5 3,5 1,5 1,0 2,0
diF Compressor relay activation differential (diF must be ≠ 0). 0,1 ... 30,0 °C/°F 2,0 2,0 2,0 2,0 2,0 4,0 2,0 2,0 2,0 4,0 2,0 8,0
HSE Maximum value that can be assigned to the Setpoint LSE ... 320 °C/°F 99,0 99,0 99,0 99,0 99,0 99,0 99,0 99,0 99,0 99,0 99,0 99,0
LSE Minimum value that can be assigned to the Setpoint -67,0 ... HSE °C/°F -50,0 -50,0 -50,0 -50,0 -50,0 -50,0 -50,0 -50,0 -50,0 -50,0 -50,0 -50,0
dty Type of defrost (0 = electrical, 1 = reverse cycle, 2 = "Free"). 0/1/2 num 0 0 1 0 0 0 1 0
dit Interval between the start of two consecutive defrost cycles 0 ... 250 hours 24 24 24 24 24 2 6 24 24 2 6 10
dEt Defrost timeout; determines the maximum defrost duration 1 ... 250 min 30 30 30 30 30 30 30 30 30 30 30 45
dSt Defrost end temperature (determined by evaporator probe) -67,0 ... 320 °C/°F 8,0 3,0 8,0 8,0 8,0 3,0 8,0 7,0
Fans stop temperature; if Pb2 > FSt, the fans are stopped. The value is
FSt either positive or negative and, depending on parameter FPt, can be either -67,0 ... 320 °C/°F 50,0 50,0 50,0 -20,0 50,0
the absolute temperature or the temperature relative to the Setpoint.
Fdt Fan activation delay after a defrost cycle 0 ... 250 min 0 0 0 0 0
dt Coil drainage time 0 ... 250 min 0 0 0 0 0 0 0
Allows to select the evaporator probes exclusion during defrost.
dFd n/y flag y y y y y
y = yes; n = no.
Maximum temperature alarm. Temperature value which, if exceeded in an
HAL LAL ... 320 °C/°F 50,0 50,0 50,0 50,0 50,0 50,0 50,0 50,0 50,0 50,0 50,0 9,5
upward direction, triggers the activation of the alarm signal.
Minimum temperature alarm. Temperature value which, when exceeded
LAL -67,0 ... HAL °C/°F -50,0 -50,0 -50,0 -50,0 -50,0 -50,0 -50,0 -50,0 -50,0 -50,0 -50,0 -2,0
downwards, triggers the activation of the alarm signal.
tAO Tempo ritardo segnalazione allarme temperatura. 0 ... 250 min 0 0 0 0 0 0 0 0 0 0 0 30
dCS Deep cooling cycle setpoint -67,0 ... 320 °C/°F -2,0 -2,0 -2,0 -2,0 -2,0 -2,0 -2,0 -2,0 -2,0 -2,0 -2,0 -2,0
tdC Deep cooling cycle duration 0 ... 255 min 0 0 0 0 0 0 0 0 0 0 0 0
OSP Offset on setpoint -30,0 ... 30,0 °C/°F 0,5 0,5 1,0 1,0 0,5 1,0 0,5 0,5 0,5 1,0 0,5 1,0
OdF Intervention differential correction 0,0 ... 30,0 °C/°F 4,0 4,0 2,0 2,0 4,0 2,0 4,0 4,0 4,0 2,0 4,0 2,0
dnt Duration of night mode 0 ... 24 hours 11 11 10 9 11 10 10 11 11 10 10 9
dFt Duration of fast cooling mode 0 ... 24 hours 0 0 1 1 0 1 1 0 0 1 1 1
SPn Night mode setpoint LSE ... HSE °C/°F 0,7 0,7 3,0 6,5 0,7 3,0 1,0 0,7 0,7 3,0 1,0 6,5
dFn Night mode offset 0,1 ... 30,0 °C/°F 4,0 4,0 2,0 0,1 4,0 2,0 4,0 4,0 4,0 2,0 4,0 0,1
SPF Fast cooling setpoint LSE ... HSE °C/°F 0,0 0,0 -0,5 -6,8 0,0 -0,5 -2,0 0,0 0,0 -0,5 -2,0 -6,8
dFF Fast cooling offset 0,1 ... 30,0 °C/°F 0,1 0,1 0,1 0,1 0,1 0,1 0,1 0,1 0,1 0,1 0,1 0,1
LOC LOCk. Basic commands modification lock. n = no; y = yes. n/y flag n n n n n n n n n n n n
PAssword 1. When enabled (PS1 ≠ 0) it constitutes the access key for
PS1 0 ... 250 num 0 0 0 0 0 0 0 0 0 0 0 0
level1 parameters (User).
CA1 Calibration 1. Value to be added to the value read by probe Pb1. -12,0 ... 12,0 °C/°F 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0
CA2 Calibration 2. Value to be added to the value read by probe Pb2. -12,0 ... 12,0 °C/°F 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0
Display mode during defrost.
0 = display the temperature read by probe Pb1;
1 = locks the reading at the temperature value read by Pb1 when
ddL 0/1/2 num 1 1 1 1 1 1 1 1 1 1 1 1
defrosting starts and until the next time the SEt value is reached;
2 = displays the label deF during defrosting and until the next time the
SEt value is reached (or until Ldd has elapsed).
Ldd Timeout value for display unlock - dEF label 0 ... 255 min 30 30 30 30 30 30 30 30 30 30 30 30
H42 Evaporator probe present (Pb2). n= not present; y= present. n/y flag y y y y y y y y
rEL firmware rELease. Reserved: read-only parameter / / / / / / / / / / / / / /
tAb tAble of parameters. Reserved: read-only parameter / / / / / / / / / / / / / /
Note: ** The USER menu parameters also include 'PA2', which can be used to access the Installer menu.
EWPlus EO LVD 6/12
TABLE OF "INSTALLER" MENU PARAMETERS
EWPlus 961 EO LVD EWPlus 971 EO LVD EWPlus 974 EO LVD
PAR. DESCRIPTION RANGE M.U.
AP1 AP2 AP3 AP4 AP1 AP2 AP3 AP4 AP1 AP2 AP3 AP4
Temperature control SEtpoint.
SEt LSE ... HSE °C/°F 3,5 3,5 3,5 3,5 3,5 1,5 1,0 3,5 3,5 1,5 1,0 2,0
The SEtpoint is visible from the "machine status" menu only.
COMPRESSOR ("CP" folder)
diFferential. Compressor relay activation differential.
diF 0,1 ... 30,0 °C/°F 2,0 2,0 2,0 2,0 2,0 4,0 2,0 2,0 2,0 4,0 2,0 8,0
N.B.: diF cannot be equal to 0.
Maximum value that can be assigned to the Setpoint. N.B.: The two Setpoints
HSE LSE ... 320 °C/°F 99,0 99,0 99,0 99,0 99,0 99,0 99,0 99,0 99,0 99,0 99,0 99,0
are interdependent: HSE cannot be less than LSE and vice-versa.
Minimum value that can be assigned to the Setpoint. N.B.: The two Setpoints
LSE -67,0 ... HSE °C/°F -50,0 -50,0 -50,0 -50,0 -50,0 -50,0 -50,0 -50,0 -50,0 -50,0 -50,0 -50,0
are interdependent: LSE cannot be higher than HSE and vice-versa.
Controller on time for faulty probe.
Ont - if Ont = 1 and OFt = 0, the compressor remains ON, 0 ... 250 min 0 0 0 0 0 1 0 0 0 1 0 0
- if Ont > 0 and OFt > 0, it runs in duty cycle mode.
Controller off time for faulty probe.
OFt - if OFt = 1 and Ont = 0, the compressor remains OFF, 0 ... 250 min 1 1 1 1 1 1 1 1 1 1 1 1
- if Ont > 0 and OFt > 0, it runs in duty cycle mode.
dOn Compressor relay activation delay after request. 0 ... 250 secs 0 0 0 0 0 15 0 0 0 15 0 10
dOF Delay after switching off and subsequent activation. 0 ... 250 min 0 0 0 0 0 3 0 0 0 3 0 2
dbi Delay between two consecutive compressor activations. 0 ... 250 min 0 0 0 0 0 0 0 0 0 0 0 2
OdO Delay in activating outputs after the instrument is switched on or after a
0 ... 250 min 0 0 0 0 0 0 0 0 0 0 0 0
(!) power failure. 0 = not active
dFA Delay time in activating compressor and condenser fans after request 0 ... 255 secs 0 0 0 0 0 0 0 0 0 0 0 10
DEFROST ("dEF" folder)
Type of defrost.
0= electric defrost - compressor OFF during defrost cycle
dty 0/1/2 num 0 0 1 0 0 0 1 0
1= cycle inversion defrost (hot gas) - compressor ON during defrost cycle
2= ‘Free’: defrosting independently of compressor
Interval between the start of two consecutive defrost cycles.
dit 0 ... 250 hours 24 24 24 24 24 2 6 24 24 2 6 10
0 = function disabled (defrosting NEVER performed)
Selects the count mode for the defrost interval:
0 = compressor hours of operation (DIGIFROST® method);
Defrost active ONLY when the compressor is on.
N.B.: compressor operation time is counted separately from
the evaporator probe (count active also when evaporator probe
dCt missing or faulty). 0/1/2/3 num 1 1 1 1 1 0 1 1 1 0 1 1
1 = appliance running hours = the defrost count is always active when the
machine is on and starts at each power-on;
2 = compressor stop Every time the compressor stops, a defrost cycle is
performed according to parameter dtY;
3 = temperature
dOH Defrost start delay time after request. 0 ... 59 min 0 0 0 0 0 0 0 0 0 0 0 0
dEt Defrost time-out; determines the maximum defrost duration. 1 ... 250 min 30 30 30 30 30 30 30 30 30 30 30 45
dSt Defrost end temperature (determined by the evaporator probe). -67,0 ... 320 °C/°F 8,0 3,0 8,0 8,0 8,0 3,0 8,0 7,0
Determines whether the instrument must enter defrost mode (if the
dPO temperature measured by the evaporator allows this operation). n/y flag n n n n n n n n n n n y
n = no, does not start defrosting at start-up; y = yes, starts defrost at start-up.
dSE Temperature threshold for start of defrost. -67,0 ...320 °C/°F 0,0 0,0 0,0 0,0 0,0 -6,0 0,0 0,0 0,0 -6,0 0,0 -6,0
dtt Time for which the temperature of the evaporator must remain below dSE. 0 ... 255 min 0 0 0 0 0 0 0 0 0 0 0 0
FAN REGULATOR ("FAn" folder)
Characterizes the "FSt" parameter that can be expressed or as an absolute
FPt 0/1 flag 0 0 0 0 0 0 0 0
temperature value or as a value related to Setpoint. 0 = absolute; 1 = relative.
Fan lock temperature; if Pb2 > FSt, the fans are stopped.
FSt The value is either positive or negative and, depending on parameter FPt, can -67,0 ... 320 °C/°F 50,0 -20,0 50,0 50,0 50,0 -20,0 50,0 50,0
be either the absolute temperature or the temperature relative to the Setpoint.
FAd Fan starting differential (see parameters FSt and Fot). 1,0 ... 50,0 °C/°F 2,0 1,0 2,0 2,0 2,0 1,0 2,0 1,0
Fdt Delay time in activating fans after a defrost operation. 0 ... 250 min 0 0 0 0 0 0 0 0
dt drainage time. Dripping time. 0 ... 250 min 0 0 0 0 0 0 0 0
Allows to select the evaporator fans exclusion during defrost.
dFd n/y flag y y y y y y y y
y = yes; n = no.
Evaporator fans operating mode. The state of the fans will be:
DAY NIGHT
COMPRESSOR COMPRESSOR COMPRESSOR COMPRESSOR
H42 FCO
ON OFF ON OFF
0 Regulated by Pb2 OFF Regulated by Pb2 OFF
H42 = y

1 Regulated by Pb2 Regulated by Pb2 Regulated by Pb2 Regulated by Pb2


2 Regulated by Pb2 Dutycycle Day Regulated by Pb2 Dutycycle Night
FCO 0/1/2/3 num 3 0 3 3 3 0 3 1
3 Dutycycle Day Dutycycle Day Dutycycle Night Dutycycle Night
0 ON OFF ON OFF
H42 = n

1 ON Dutycycle Day ON Dutycycle Night


2 ON Dutycycle Day ON Dutycycle Night
3 Dutycycle Day Dutycycle Day Dutycycle Night Dutycycle Night
Dutycycle Day: controlled by means of parameters “Fon” and “FoF”.
Dutycycle Night: controlled by means of parameters “Fnn” and “FnF”.
FdC Evaporator fans switch-off delay after compressor disabled. 0 ... 99 min 1 0 1 1 1 0 1 0
Fans ON time in duty cycle. Fans used in duty cycle mode; valid when
Fon 0 ... 250 secs*10 12 2 12 12 12 2 12 2
FCO = dc and H42=1 (Pb2 probe present)
Fans OFF time in duty cycle. Fans used in duty cycle mode; valid when
FoF 0 ... 250 secs*10 6 1 6 6 6 1 6 1
FCO = dc and H42=1 (Pb2 probe present)
EWPlus EO LVD 7/12
EWPlus 961 EO LVD EWPlus 971 EO LVD EWPlus 974 EO LVD
PAR. DESCRIPTION RANGE M.U.
AP1 AP2 AP3 AP4 AP1 AP2 AP3 AP4 AP1 AP2 AP3 AP4
Fans ON time in night duty cycle. Fans used in duty cycle mode; valid when
Fnn 0 ... 250 secs*10 1 1 1 1 1 1 1 1
FCO = dc and H42=1 (Pb2 probe present)
Fans OFF time in night duty cycle. Fans used in duty cycle mode; valid when
FnF 0 ... 250 secs*10 12 10 12 12 12 10 12 10
FCO = dc and H42=1 (Pb2 probe present)
ALARMS ("AL" folder)
Parameters HAL and LAL intended as the absolute temperature value or
differential in relation to the setpoint. 0 = absolute value; 1 = relative value.
Att N.B.: In case of relative values (para. Att=1) parameter HAL should 0/1 num 1 1 1 1 1 0 1 1 1 0 1 1
be set to positive values, whilst parameter LAL should have
only negative values (-LAL).
AFd Alarm differential. 1,0 ... 50,0 °C/°F 2,0 2,0 2,0 2,0 2,0 2,0 2,0 2,0 2,0 2,0 2,0 1,0
Maximum temperature alarm. Temperature value (intended either as
distance from Setpoint or as an absolute value based on Att) which, if
HAL (!) LAL to 320 °C/°F 50,0 50,0 50,0 50,0 50,0 50,0 50,0 50,0 50,0 50,0 50,0 9,5
exceeded in an upward direction, triggers the activation of the alarm signal.
See "Max/Min Temperature Alarms".
Minimum temperature alarm. Temperature value (intended as distance from
the set point or as an absolute value based on Att) which, when exceeded
LAL (!) -67,0 to HAL °C/°F -50,0 -50,0 -50,0 -50,0 -50,0 -50,0 -50,0 -50,0 -50,0 -50,0 -50,0 -2,0
downwards, triggers the activation of the alarm signal.
See "Max/Min Temperature Alarms".
Alarm exclusion time after instrument switch on, after a power failure.
PAO (!) 0 ... 10 hours 0 0 0 0 0 0 0 0 0 0 0 2
This parameter refers to high/low temperature alarms only.
dAO Temperature alarm exclusion time after defrost. 0 ... 999 min 0 0 0 0 0 0 0 0 0 0 0 60
Alarm signaling delay (low and high temperature) after digital input
OAO 0 ... 10 hours 0 0 0 0 0 0 0 0 0 0 0 0
disabling (door close).
tdO Alarm activation delay time open door. 0 ... 250 min 0 0 0 0 0 0 0 0 0 0 0 0
Temperature alarm signal delay time.
tAO 0 ... 250 min 0 0 0 0 0 0 0 0 0 0 0 30
This parameter refers to high/low temperature alarms only.
Alarm for defrosting ended due to time out.
dAt n/y flag n n n n n n n n
n = alarm deactivated; y = alarm activated.
rLO External alarm locks controllers. n = does not lock; y=locks n/y flag n n n n n n n n n n n n
Alarm output polarity.
AOP 0/1 num 1 1 1 1 1 1 1 1
0 = alarm active and output disabled; 1 = alarm active and output enabled.
COOL PROTECTION ("CPr" folder)
CPS Cool protection setpoint -67,0 ... 320 °C/°F -10,0 -10,0 -10,0 -10,0 -10,0 -10,0 -10,0 -10,0 -10,0 -10,0 -10,0 -10,0
CPd Cool protection differential 0,1 ... 30,0 °C/°F 1,0 1,0 1,0 1,0 1,0 1,0 1,0 1,0 1,0 1,0 1,0 1,0
CPt Time that the temperature remains below the cool protection Setpoint (CPS) 0 ... 255 min 0 0 0 0 0 0 0 0 0 0 0 0
LIGHTS & DIGITAL INPUTS ("Lit" folder)
Enable utility switch-off on activation of door switch.
dOd 0 = disabled 1 = disables fans 0/1/2/3 num 1 1 1 1 1 0 1 1 1 0 1 0
2 = disables the compressor 3 = disables fans and compressor
dAd Activation delay for digital input 0 ... 255 min 0 0 0 0 0 0 0 0 0 0 0 0
dCO Compressor deactivation delay after door opened 0 ... 255 min 0 0 0 0 0 0 0 0 0 0 0 0
dCd Fans activation delay after door closed 0 ... 250 secs 10 10 10 10 10 10 10 10 10 10 10 0
PRESSURE SWITCH ("PrE" folder)
PEn Number of errors allowed for general pressure switch input. 0 = disabled. 0 ... 15 num 5 5 5 5 5 5 5 5 5 5 5 5
PEI Minimum/maximum pressure switch error count interval 1 ... 99 min 1 1 1 1 1 1 1 1 1 1 1 1
PEt Delay in activating compressor after pressure switch deactivation 0 ... 255 min 0 0 0 0 0 0 0 0 0 0 0 0
POWER SUPPLY CONTROL ("SuC" folder) NOTE: all parameters available in the folder are not available in the vectors.
SPH Maximum supply voltage threshold. 0 = deactivated. 0 ... 300 Volt 250 250 250
SPL Minimum supply voltage threshold. 0 = deactivated. 0 ... 250 Volt 190 190 190
dFL Intervention differential. 0 = deactivated. 0,1 ... 25,0 Volt 5,0 5,0 5,0
Selection of the output to be deactivated. 0= no output; 1= out1 (A);
SoU 2= out2 (B); 3= out1 (A) + out2 (B); 4= out3 (C); 5= out1 (A) + out3 (C); 0 ... 7 num 1 1 1
6= out2 (B) + out3 (C); 7= out1 (A) + out2 (B) + out3 (C)
DEEP COOLING ("dEC" folder)
dCA Enable deep cooling (0 = disabled; 1 = manual; 2 = automatic). 0/1/2 num 2 2 2 2 2 2 2 2 2 2 2 2
dCS Deep cooling setpoint. -67,0 ... 320 °C/°F -2,0 -2,0 -2,0 -2,0 -2,0 -2,0 -2,0 -2,0 -2,0 -2,0 -2,0 -2,0
tdC Deep cooling duration. 0 ... 255 min 0 0 0 0 0 0 0 0 0 0 0 0
dcc Defrost delay after deep cooling. 0 ... 255 min 0 0 0 0 0 0 0 0 0 0 0 0
Sid Deep cooling start threshold. -67,0 ... 320 °C/°F 12,0 12,0 12,0 12,0 12,0 12,0 12,0 12,0 12,0 12,0 12,0 12,0
toS Over-threshold time for deep cooling start. 0 ... 255 min 5 5 5 5 5 5 5 5 5 5 5 5
ENERGY SAVING ("EnS" folder)
Energy Saving mode:
0= disabled; 1= Offset on setpoint; 2= Offset on differential;
ESt 0 ... 6 num 5 5 4 4 5 4 6 5 5 4 6 4
3= Offset on setpoint and differential; 4= 'Bottle cooler open front' algorithm;
5= 'Bottle cooler glass door' algorithm; 6= 'Vertical display cabinet' algorithm
AUX output status in energy saving mode:
ESA 0/1/2 num 0 0 0 0 1 1 0 0 1 1 1 1
0 = disabled (no effect on AUX); 1 = AUX off; 2 = AUX on
Night mode activation (Energy saving) for fans.
ESF n/y flag y y y y y y y y y y y y
n = disabled; y=enabled if energy saving mode is active (ESt ≠ 0)
Cdt Door close time 0 ... 255 min*10 6 6 6 6 6 6 6 6 6 6 6 6
ESo Cumulative door open time for disabling Energy Saving mode 0 ... 10 num 0 0 0 0 0 0 5 0 0 0 5 0
OSP Offset on setpoint -30,0 ... 30,0 °C/°F 0,5 0,5 1,0 1,0 0,5 1,0 0,5 0,5 0,5 1,0 0,5 1,0
OdF Intervention differential correction 0,0 ... 30,0 °C/°F 4,0 4,0 2,0 2,0 4,0 2,0 4,0 4,0 4,0 2,0 4,0 2,0
dnt Duration of night mode 0 ... 24 hours 11 11 10 9 11 10 10 11 11 10 10 9
dFt Duration of fast cooling mode 0 ... 24 hours 0 0 1 1 0 1 1 0 0 1 1 1
SPn Night mode setpoint LSE ... HSE °C/°F 0,7 0,7 3,0 6,5 0,7 3,0 1,0 0,7 0,7 3,0 1,0 6,5
EWPlus EO LVD 8/12
EWPlus 961 EO LVD EWPlus 971 EO LVD EWPlus 974 EO LVD
PAR. DESCRIPTION RANGE M.U.
AP1 AP2 AP3 AP4 AP1 AP2 AP3 AP4 AP1 AP2 AP3 AP4
dFn Night mode offset. 0,1 ... 30,0 °C/°F 4,0 4,0 2,0 0,1 4,0 2,0 4,0 4,0 4,0 2,0 4,0 0,1
SPF Fast cooling setpoint. LSE ... HSE °C/°F 0,0 0,0 -0,5 -6,8 0,0 -0,5 -2,0 0,0 0,0 -0,5 -2,0 -6,8
dFF Fast cooling offset. 0,1 ... 30,0 °C/°F 0,1 0,1 0,1 0,1 0,1 0,1 0,1 0,1 0,1 0,1 0,1 0,1
ESP Virtual door regulator's sensitivity. 0 ... 5 num 0 0 0 0 0 0 0 0 0 0 0 0
dOt Maximun Time Door Open with virtual door switch. 0 ... 255 sec 0 0 0 0 0 0 0 0 0 0 0 0
COMMUNICATION ("Add" folder) NOTE: all parameters available in the folder are not available in the vectors.
PtS (!) Communication protocol selection (t = Televis; d = ModBus). t/d flag t t t
dEA (!) Device address: indicates the device address to the management protocol. 0...14 num 0 0 0
FAA (!) Family address: indicates the device family to the management protocol. 0...14 num 0 0 0
Pty (!) Modbus parity bit setting (n = none; E = even; o = odd). n/E/o flag n n n
StP (!) Modbus stop bit setting. 1b/2b flag 1b 1b 1b
DISPLAY ("diS" folder)
LOCk. Setpoint change shutdown. There is still the possibility to enter into
LOC parameters programming and modify these, including the status of this n/y flag n n n n n n n n n n n n
parameter to permit keyboard shutdown. n = no; y = yes.
PAssword 1. When enabled (PS1 ≠ 0), this is the access key to level 1
PS1 0...250 num 0 0 0 0 0 0 0 0 0 0 0 0
parameters (User).
PAssword 2. When enabled (PS2 ≠ 0), this is the access key to level 2
PS2 0...250 num 15 15 15 15 15 15 15 15 15 15 15 15
parameters (Installer).
Display with decimal point.
ndt n/y flag y y y y y y y y y y y y
n = no (integers only); y = yes (displayed with decimal point).
Calibration 1. Positive or negative temperature value added to the value
CA1 read by Pb1. This sum is used both for the temperature displayed and for -12,0...12,0 °C/°F 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0
regulation.
Calibration 2. Positive or negative temperature value added to the value
CA2 read by Pb2. This sum is used both for the temperature displayed and for -12,0...12,0 °C/°F 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0
regulation.
Display mode during defrost.
0 = display the temperature read by Pb1;
1 = locks the reading on the temperature value read by Pb1 when
ddL 0/1/2 num 1 1 1 1 1 1 1 1 1 1 1 1
defrosting starts, and until the next time the SEt value is reached;
2 = displays the label deF during defrosting, and until the next time the
SEt value is reached. (or until Ldd has elapsed).
Ldd Timeout value for display unlock - dEF label 0 ... 255 min 30 30 30 30 30 30 30 30 30 30 30 30
Select °C or °F for displaying the temperature read by probes. 0 = °C, 1 = °F.
dro NOTE: switching between °C and °F or vice-versa DOES NOT modify 0/1 num 0 0 0 0 0 0 0 0 0 0 0 0
the SEt, diF values, etc. (e.g. Setpoint=10°C becomes 10°F).
Selection of type of value to be displayed.
ddd 0/1/2/3 num 1 1 1 1 1 1 1 1 1 1 1 1
0 = Setpoint; 1 = probe Pb1; 2 = probe Pb2; 3 = not used.
CONFIGURATION ("CnF" folder) - NOTE: the instrument must be switched off and then on again each time folder CnF parameter configuration is modified to prevent
any malfunction of the configuration and/or current timer operations.
Stand-by operating mode.
0 = display switch off; the loads are active and the device reactivates the
H08 display to signal any alarms; 0/1/2 num 2 2 2 2 2 2 2 2 2 2 2 2
1 = display switch off, loads and alarms stopped;
2 = display with OFF label, loads and alarms stopped.
Configuration of digital input 1/polarity (D.I.1).
0 = disabled; ± 1 = defrost; ± 2 = reduced SET; ±3 = AUX;
± 4 = door switch; ± 5 = external alarm; ± 6 = stand-by (ON-OFF);
H11 ± 7 = pressure switch; ± 8 = deep cooling; ± 9 = energy saving; -10 ... 10 num 10 0 9 9 10 9 10 10 10 9 10 9
±10 = door switch + energy saving.
N.B.: - the “+” sign indicates that the input is active if the contact is closed
- the “-” sign indicates that the input is active if the contact is open
H12 Configuration of digital input 2/polarity (D.I.2). Same as H11. -10 ... 10 num 0 0 0 0 0 0 0 0 0 0 0 0
Configurability of digital output 1 (A).
0 = disabled; 1 = compressor; 2 = defrost; 3 = Fans;
H21 0 ... 9 num 1 1 1 1 1 1 1 1 1 1 1 1
4 = alarm; 5 = AUX; 6 = Stand-by; 7 = not used;
8 = condenser fan change rotation; 9 = retain valve.
H22 Configurability of digital output 2 (B). Analogo a H21. 0 ... 9 num 5 5 2 3 3 3 2 8
H23 Configurability of digital output 3 (C). Analogo a H21. 0 ... 9 num 5 5 3 5
Enable/Disable buzzer.
H25 0 ... 9 num 0 0 0 0 0 0 0 0 0 0 0 0
0 = disabled; 4 = enabled; 1-2-3-5-6-7-8-9 = not used
Configurability of DOWN key.
H32 0 = disabled; 1 = defrost; 2 = AUX; 3 = reduced SET; 0 ... 6 num 0 0 0 0 2 2 0 0 2 2 0 2
4 = Stand-by; 5 = deep cooling; 6 = energy saving
H33 Configurability of ESC key. Same as H32 0 ... 6 num 4 4 4 4 4 4 4 4 4 4 4 4
H42 Evaporator probe present (Pb2). n= not present; y= present. n/y flag y y y y y y y y
reL reLease firmware. Device version: read-only parameter / / / / / / / / / / / / / /
tAb tAble of parameters. Reserved: read-only parameter / / / / / / / / / / / / / /
COPY CARD ("Fpr" folder)
UL Upload. Programming parameter transfer from instrument to Copy Card. / / / / / / / / / / / / / /
Format Copy Card. Erase all data contained in the Copy Card.
Fr ATTENTION: If parameter “Fr” is used, the data entered will be / / / / / / / / / / / / / /
permanently lost. This operation cannot be cancelled
FUNCTION ("FnC" folder)
The following function is available in the ‘FnC’ folder:
Function Function label ACTIVE Function label INACTIVE alarm signalled
Reset pressure switch alarms rAP rAP Led ON
NOTES: • To modify the status of a specified function press the ‘set’ button
• If the unit is switched off, the function labels go back to their default status.
EWPlus EO LVD 9/12
DIAGNOSTICS
Alarms are always indicated by the buzzer (if present) and the alarm icon .
To switch off the buzzer, press and release any key; the corresponding icon will continue to flash.
N.B.: If alarm exclusion times have been set (see “AL” folder in the parameters table) the alarm will not be signalled.

ALARMS
Label Fault Cause Effects Remedy
• Display label E1
• Alarm icon permanently on
• measured values are outside operating
Probe1 faulty • check probe wiring
E1 range • Disable max/min alarm controller
(cold room) • replace probe
• Probe faulty/short-circuited/open • Compressor operation based on parameters
'Ont' and 'OFt'.
Probe2 faulty • Display label E2
(defrost) • measured values are outside operating • Alarm icon permanently on
• check probe wiring
E2 range • The Defrost cycle will end due to Timeout (dEt)
• replace probe
only on • Probe faulty/short-circuited/open • The evaporator fans will work in Duty Cycle
EWPlus971/974 EO LVD mode.
Alarm for HIGH value read by Pb1 > HAL after time of tAO. • Recording of label AH1 in folder AL • Wait until value read by Pb1 returns below
AH1
Pb1 temperature (see “MAX/MIN TEMPERATURE ALARMs") • No effect on regulation HAL-AFd.
Alarm for LOW value read by Pb1 < LAL after time of tAO. • Recording of label AL1 in folder AL • Wait until value read by Pb1 returns above
AL1
Pb1 temperature (see “MAX/MIN TEMPERATURE ALARMs") • No effect on regulation LAL+AFd.
• Recording of label EA in folder AL
digital input activation • check and remove the external cause which
EA External Alarm • Alarm icon permanently on
(H11 = ±5) triggered the alarm on the D.I.
• Regulation locked if rLO = y
digital input activation • Recording of label Opd in folder AL
• close the door
OPd Door open alarm (H11 = ±4) • Alarm icon permanently on
• delay function defined by OAO
(for longer than tdO) • Controller locked
end of defrost cycle due to timeout rather
end of defrost • Recording of label Ad2 in folder AL • wait for the next defrost cycle for automatic
Ad2 than due to defrost end temperature being
cycle due to timeout • Alarm icon permanently on return
recorded by probe Pb2.
activation of the defrost for temperature
end of defrost • Recording of label Ad3 in folder AL • wait for the next defrost cycle for automatic
Ad3 independently dAt.
cycle due to timeout • Alarm icon permanently on return
(active if dCt = 3)
• Display label HiP
HIGH voltage Voltage value read by the analog input is • wait for the value read by the analog input
HiP • Alarm icon permanently on
alarm higher than the SPH value. returns below SPH-dFL
• Regulation locked depending on SoU value.
• Display label LoP
LOW voltage Voltage value read by the analog input is • Wait for the value read by the analog input
LoP • Alarm icon permanently on
alarm lower than the SPL value. returns above SPL+dFL
• Regulation locked depending on SoU value.
If the number N of pressure switch activations is
Activation of pressure alarm by general N<PEn: • check and remove the cause which
General pressure
nPA pressure switch. • Recording of folder nPA in folder AL, triggered the alarm on the D.I.
switch alarm
(H11 = ±7) with the number of pressure switch activations (Automatic Reset)
• Regulation locked (Compressor and Fans)
If the number N of pressure switch activations is
N=PEn: • Switch the device off and back on again
Activation of pressure alarm by general
General pressure • Display label PAL • Reset alarms by entering the functions folder
PAL pressure switch.
switch alarm • Recording of label PA in folder AL and selecting the rAP function
(H11 = ±7)
• Alarm icon permanently on (Manual Reset)
• Regulation locked (Compressor and Fans)

MAX/MIN TEMPERATURE ALARMs


Relative Temperature Absolute Temperature
Value to setpoint (Att=1) Value (Att=0)

AFd AFd AFd AFd


SEt

SEt + LAL SEt + HAL LAL HAL


LAL + AFd LAL - AFd
SEt + LAL + AFd SEt + HAL – AFd

Minimum temperature alarm Temp. ≤ Set + LAL * Temp. ≤ LAL (LAL with sign)
Maximum temperature alarm Temp. ≥ Set + HAL ** Temp. ≥ HAL (HAL with sign)
Temp. ≥ Set + LAL + AFd or
Returning from minimum temperature alarm Temp. ≥ LAL + AFd
≥ Set - ILALI + AFd (LAL < 0)
Returning from maximum temperature alarm Temp. ≤ Set + HAL - AFd (HAL > 0) Temp. ≤ HAL - AFd
* if LAL is negative, Set + LAL < Set
** if HAL is negative, Set + HAL < Set
EWPlus EO LVD 10/12
TECHNICAL DATA (EN 60730-2-9)
Classification: control device (not safety) to integrate
Mounting: panel mounting with 71x29 mm (+0.2/-0.1 mm) drilling template
Control type: 1.B
Pollution rating: 2
Material class: IIIa
Overvoltage category class: II
Nominal impulsive voltage: 2500V
Temperature: Operating: –5 … +55 °C - Storage: –30 … +85 °C
Power Supply: 230Va (±20%) 50/60 Hz
Consumption: 4,5W max
Digital Output (relays): please refer to the device label
Fire resistance class: D
Software class: A
NOTE: check the power supply specified on the instrument label; for relay, power supply capacities and PTC probes, contact
the Sales Office.
FURTHER INFORMATIONS
Input Characteristics
Display Range: NTC: –50.0°C ... +110°C (on display with 3 digit + sign)
Accuracy: Better than 0,5% of full-scale + 1 digit
Resolution: 0,1 °C
Buzzer: YES (it depends from model)
Analogue Input: 1 NTC (EWPlus 961 EO LVD) or 2 NTC (EWPlus 971/974 EO LVD)
Digital Input: 2 voltage-free digital inputs (D.I.1 and D.I.2)
NOTE: D.I.2, if activated, should be connected to terminals 1-2 of the TTL connector (H12 ≠ 0)
Output Characteristics
Digital Output: EWPlus 961 EO LVD: 1 Compressor relay: UL60730-1 12 (8)A max 250Va
UL60730 2Hp (12FLA - 72LRA) max 240Va
EWPlus 971 EO LVD: 1 Compressor relay: UL60730-1 12 (8)A max 250Va
UL60730 (A) 2Hp (12FLA - 72LRA) max 240Va
1 AUX relay: N.A. 8(4)A - N.C. 6(3)A max 250Va
EWPlus 974 EO LVD: 1 Compressor relay: UL60730-1 12 (8)A max 250Va
UL60730 (A) 2Hp (12FLA - 72LRA) max 240Va
1 Fans relay: N.A. 8(4)A - N.C. 6(3)A max 250Va
1 AUX relay: 5(2)A max 250Va
Mechanical Characteristics
Casing: PC+ABS UL94 V-0 resin casing, polycarbonate window, thermoplastic resin keys
Dimensions: front panel 74x32 mm, depth 59 mm (without terminals)
Terminals: screw/disconnectable terminals for cables with a diameter of 2.5mm2
Connectors: TTL for connection of Copy Card + D.I.2
Humidity: Use / Storage: 10…90% RH (non-condensing)
LVD Characteristics
Power voltage reading accuracy: +3% -2%
Power voltage measuring method: Peak-value voltmeter
BUS ADAPTER: compatible with low-consumptation model only (BUS ADAPTER 350)
Regulations
Electromagnetic compatibility: The device conforms to Directive 2004/108/EC
Safety: The device conforms to Directive 2006/95/EC
Food Safety: The device complies with standard EN 13485 as follows:
- suitable for storage
- application: air
- climate range A
- measurement class 1 in the range from -25°C to 15°C
(exclusively using Eliwell NTC probes)
NOTE: The technical specifications given in this document regarding measurement (range, accuracy, resolution, etc.) refer to the
instrument and not to any accessories provided, such as the probes.
This means, for example, that the error introduced by the probe must be added to the typical error of the instrument.
ELECTRICAL CONNECTIONs
Attention! Make sure the machine is switched off before working on the electrical connections.
The instrument is equipped with screw or disconnectable terminal blocks for connecting electrical cables with a max. diameter of
2.5 mm2 (one wire per terminal for power connections): for the terminal ratings, see the label on the instrument. Do not exceed the
maximum permissible current; in case of higher loads, use a suitably rated contactor.
Make sure the power supply voltage complies with that required by the instrument.
Probes have no connection polarity and can be extended using a normal bipolar cable (note that the extension of the probes influences
the electromagnetic compatibility - EMC - of the instrument: take great care with the wiring).
Probe cables, power supply cables and the TTL serial cable should be routed separately from power cables.

EWPlus EO LVD 11/12


LIABILITY AND RESIDUAL RISKS
ELIWELL CONTROLS SRL declines any liability for damage due to:
- installation/uses different from those specified and, in particular, not complying with the safety regulations and/or instructions
given in this document;
- use on panels that do not provide adequate protection against electric shocks, water or dust when assembled;
- use on panels allowing access to dangerous parts without the use of tools;
- tampering with and/or modifying the product;
- installation/use on panels not complying with current standards and regulations.

DISCLAIMER
This document is the exclusive property of ELIWELL CONTROLS SRL and may not be reproduced or circulated unless expressly
authorised by ELIWELL CONTROLS SRL itself. Every care has been taken in preparing this document; nevertheless ELIWELL
CONTROLS SRL cannot accept liability for any damage resulting from its use.
The same applies to any person or company involved in preparing and editing this document.
ELIWELL CONTROLS SRL reserves the right to make aesthetic or functional changes at any time without notice.

CONDITIONS OF USE
Permitted use
For safety reasons, the instrument must be installed and used according to the instructions supplied and, in particular, parts under
dangerous voltages must not be accessible in normal conditions. The device must be adequately protected from water and dust
with regard to its application, and must only be accessible using tools (except for the front panel). The device is suitable for use
in household refrigeration appliances and/or similar equipment and has been tested for safety aspects in accordance with the
harmonised European reference standards.
Improper use
Any use other than that expressly permitted is prohibited. The relay contacts provided are of a functional type and subject to failure:
any protection devices required by product standards, or suggested by common sense for obvious safety requirements, must be
installed externally to the instrument.

Eliwell Controls s.r.l.


Via dell’Industria, 15 • Z.I. Paludi
32010 Pieve d’Alpago (BL) ITALY
Telephone +39 0437 986 111
Facsimile +39 0437 989 066
www.eliwell.com

Technical Customer Support:


Technical helpline +39 0437 986 300
E-mail: [email protected]

Sales:
Telephone +39 0437 986 100 (Italy)
+39 0437 986 200 (other countries)
E-mail: [email protected]

cod. 9IS24215-1 - EWPlus 961/971/974 EO LVD - EN - rel.06/11 -


© Eliwell Controls s.r.l. 2011 All rights reserved.
EWPlus EO LVD 12/12