KP Thermostats Danfoss
KP Thermostats Danfoss
FEATURES
P636
• Wide regulating range.
• Can be used for deep freeze, refrigeration and air conditioning systems.
• Welded bellows elements mean increased reliability.
• Small dimensions — Easy to install in refrigerated counters or cold
rooms.
• Ultra-short bounce times. Long operating life. Unnecessary cut-in and
cut-out of control equipment is avoided.
• Standard versions with changeover switch. Possible to obtain opposite
switch function or to connect a signal.
• Electrical connection at the front of the unit facilitates rack mounting.
Saves space.
• Suitable for alternating and direct current.
• No spade or lug terminals required.
• Integral 1/2 NPSM swivel cable connector. Allows direct attachment of
1/2 in. male pipe thread connector.
• Extensive and wide range. P636C
APPROVALS
UL listed, file E31024.
CSA certified, LR 27339.
463
REFRIGERATION THERMOSTATS
DANFOSS REFRIGERATION THERMOSTATS
ORDERING
CAPILLARY TUBE
DIFFERENTIAL t
LENGTH
BULB REGULATION
CHARGE TYPE At Lowest At Highest RESET P/N
TYPE RANGE
Temperature Temperature in. ft
Setting °F Setting °F
KP 61 B -20 → 55 8 → 40 2.2 → 13 Auto. 80 6.5 60L2002
KP 62 C -20 → 60 10 → 40 2.7 → 13 Auto. 60L2015
Vapour*
KP 63 A -60 → 15 18 → 125 4.9 → 15 Auto. 80 6.5 60L2007
KP 69 B 25 → 95 8 → 45 3.2 → 13 Auto. 80 6.5 60L2009
KP 71 E2 25 → 70 4.5 → 18 4 → 18 Auto. 80 6.5 60L2010
KP 71 E2 25 → 70 Fixed 5.4 Fixed 5.4 Man., Min.** 80 6.5 60L2011
KP 73 D -15 → 60 8 → 36 6.3 → 36 Auto. 80 6.5 60L2017
Adsorption†
KP 73 E1 0 → 80 10 → 35 10 → 35 Auto. 80 6.5 60L2029††
Oil: 30 to 90 Oil: fixed 22 Oil: fixed 22 40 3.2
KP 98 E2 Man., Max. 60L2025
HT: 210 to 350 HT: fixed 45 HT: fixed 45 80 6.5
*Bulb must be installed in colder position than thermostat housing and capillary tube.
†Bulb can be placed warmer or colder than thermostat housing.
**On manual minimum reset units the set value is equal to the cut-out value (lowest activating temperature).
Reset is possible after a temperature rise of 5.4° F.
††Factory setting:
Cut-In: 60° F
Cut-Out: 25° F
B
Dia. 3/8 in. x 2-3/4 in. remote air coil
D
Dia. 3/8 in. x 2-3/4 in. double contact remote bulb
NOTE: Cannot be used in sensor (bulb) pocket.
E
E1: Dia. 1/4 in. x 3-3/8 in. remote bulb
E2: Dia. 3/8 in. x 4 in. remote bulb
464
TEMPERATURE & PRESSURE CONTROLS
ALCO TF115 TEMPERATURE CONTROLS
The TF115 Temperature Controls are designed to sense space or
surface temperatures in cooling or heating applications for cycling
and alarm applications. Maximum application flexibility is pro-
vided by using a heavy-duty 24 amp single pole double throw
SPDT switch and temperature ranges and power elements
designed for specific applications. P1024
P1026
Procedure
1. Adjust the Range Screw/Pointer to the desired “High Event” P1026A
setting.
2. Adjust the Differential Screw to the desired differential. Procedure
Low Event = High Event – Differential 1. Adjust the Range Screw to the desired “High Event” setting.
• Adjustment of the Range Screw changes both high and low Low Event = High Event – Fixed Differential
events
• Adjustment of the Range Screw changes both the high and low
• Adjustment of the Differential Screw changes the “Low Event”
events.
only.
465
TEMPERATURE & PRESSURE CONTROLS
RANCO LUBE OIL PROTECTION CONTROLS
These lube oil protection controls guard pressure-lubricated
refrigeration compressors against major damage due to loss of oil
pressure. If adequate oil pressure is lost, the built-in S30 Time
Delays Switch starts timing. If the oil pressure does not recover
within the set period, the control circuit is opened, stopping the
compressor.
P1123
P1127
1290132
P/N OVERALL HOSE LENGTH FITTINGS (1/4″″ SAE)
RAN-1290132-B18 18″
RAN-1290132-B24 24″
Straight 7/16 - 20 Female Flare Connection
RAN-1290132-B36 36″
RAN-1290132-B48 48″
RAN-1290132-A18 18″
One Straight And One 90° Elbow
RAN-1290132-A24 24″
Both Ends Have 7/16 - 20 Female Flare Connection
RAN-1290132-A36 36″
RAN-1290132-A48 48″
466
TEMPERATURE & PRESSURE CONTROLS
RANCO MINI PRESSURE CONTROLS
LOW, HIGH PRESSURE AND FAN CYCLING
CONTROLS
Ranco Mini Pressure, fixed setting controls are used on refrigera-
tion or air conditioning systems.
P1125
P1126
467
TEMPERATURE & PRESSURE CONTROLS
JOHNSON CONTROLS A19 REMOTE BULB CONTROL
DESCRIPTION
The A19 Series are single stage temperature controls that
incorporate liquid filled sensing elements.
P4411
SELECTION CHART
BULB WELL NO.
SWITCH RANGE DIFF F° BULB AND RANGE MAX. BULB
P/N (Order
ACTION °F (°C) (C°) CAPILLARY ADJUSTER TEMP °F (°C)
Separately)
Wide Range — Adjustable Differential
SPST
A19ABA-40C* –30 to 100 (–34 to 38) 3 to 12 (1.7 to 6.7) 3/8 in. x 4 in., 6 ft Cap. WEL14A-602R Screwdriver Slot 140 (60)
Open Low
A19ABC-4C SPDT 50 to 130 (10 to 55) 3-1/2 to 14 (1.9 to 8) 3/8 in. x 5 in., 8 ft Cap. WEL14A-603R Knob 170 (77)
▲ A19ABC-24C† SPDT –30 to 100 (–34 to 38) 3 to 12 (1.7 to 6.7) 3/8 in. x 4 in., 8 ft Cap. WEL14A-602R Convertible 140 (60)
▲ A19ABC-36C SPDT –30 to 100 (–34 to 38) 3 to 12 (1.7 to 6.7) 3/8 in. x 4 in., 20 ft Cap. WEL14A-602R Convertible 140 (60)
A19ABC-37C SPDT –30 to 100 (–34 to 38) 3 to 12 (1.7 to 6.7) 3/8 in. x 4 in., 10 ft Cap. WEL14A-602R Screwdriver Slot 140 (60)
A19ABC-74C SPDT –30 to 100 (–34 to 38) 3 to 12 (1.7 to 6.7) 3/8 in. x 4 in., 6 ft Cap. WEL14A-602R Screwdriver Slot 140 (60)
Fixed Differential
A19AAF-12C SPDT 25 to 225 (–4 to 107) 3-1/2 (1.9) 3/8 in. x 3 in., 10 ft Cap. WEL14A-602R Screwdriver Slot 275 (135)
CASE COMPENSATED — FIXED DIFFERENTIAL
A19AAC-4C SPDT 0 to 80 (–18 to 27) 5 (2.8) 3/8 in. x 4 in., 6 ft Cap. WEL14A-602R Screwdriver Slot 140 (60)
SPST
A19AAD-12C –30 to 50 (–34 to 10) 2-1/2 (1.4) 3/8 in. x 4 in., 7 ft Cap. WEL14A-602R Screwdriver Slot 140 (60)
Open Low
Close Differential
SPST 30 to 50 (–1 to 10)
A19AAD-5C** 2-1/2 (1.4) 3/8 in. x 2-5/8 in., 6 ft Cap. WEL16A-601R Screwdriver Slot 190 (88)
Open Low (Bulk Milk Cooler)
A19AAF-20C SPDT –30 to 100 (–34 to 38) 2-1/2 (1.4) 3/8 in. x 4 in., 6 ft Cap. WEL14A-602R Screwdriver Slot 140 (60)
A19AAF-21C SPDT 40 to 90 (4 to 32) 1-1/2 (0.8) 3/8 in. x 5-3/4 in., 6 ft Cap. WEL14A-603R Screwdriver Slot 140 (60)
Manual Reset
SPST
A19ACA-14C –30 to 100 (–34 to 38) Manual Reset 3/8 in. x 4 in., 6 ft Cap. WEL14A-602R Screwdriver Slot 140 (60)
Open Low
SPST
A19ACA-15C –30 to 100 (–34 to 38) Manual Reset 3/8 in. x 4 in., 10 ft Cap. WEL14A-602R Screwdriver Slot 140 (60)
Open Low
SPST
A19ADB-1C 100 to 240 (38 to 116) Manual Reset 3/8 in. x 3-1/2 in., 6 ft Cap. WEL14A-602R Knob 290 (143)
Open High
SPST
A19ADN-1C 100 to 240 (38 to 116) Manual Reset 3/8 in. x 4 in., 6 ft Cap. WEL14A-602R Screwdriver Slot 290 (143)
Open HIgh
468
TEMPERATURE & PRESSURE CONTROLS
JOHNSON CONTROLS A419 ELECTRONIC TEMPERATURE CONTROL
DESCRIPTION
The A419 Series control is a line voltage, single-stage, elec-
tronic temperature control with a Single-Pole, Double-Throw
(SPDT) output relay. It has heating or cooling modes of
operation with an adjustable set point and differential, a
lockable keypad, an adjustable anti-short cycle delay, and
binary input for temperature offset. The A419 combines
remote sensing capability and interchangeable sensors with
electronic accuracy, all in a NEMA 1 high-impact plastic
enclosure that is suitable for surface-mounting or DIN-rail P4412
mounting.
APPLICATIONS
The A419 can be used to control a wide variety of sin- SELECTION CHART
gle-stage refrigeration or HVAC equipment. Typical applica-
tions include: P/N DESCRIPTION
• freezer control in convenience stores A419 Electronic Temperature Control with Display and
A419ABC-1C
• reach-in coolers Sensor (120/240 VAC model)
• supermarket display cases for produce or meats A419 Electronic Temperature Control with Display and
A419GBF-1C
• restaurant or convenience store walk-in coolers Sensor (24 VAC model)
• boiler control A99BB-200C PTC Sensor with 6.5 ft (1.98 m) Leads
• compressor lockout (disables the compressor when tem- BKT287-1R 35 x 7.5 mm, 0.305 m (12 in.) long DIN Rail
perature exceeds limits) BKT287-2R 35 x 7.5 mm, 0.914 m (36 in.) long DIN Rail
• condenser fan cycling PLT344-1R Two End Clamps, for DIN Rail Mounting
• pump control for cooling towers CLK350-2 7-Day Programmable Digital Clock; Electronic Switch Output
• space and return-air temperature WEL11A-601R Immersion Well (Use with Thermal Compound)
P4415
SELECTION CHART
ITEM P/N DESCRIPTION
A319 Temperature Control with Sensor A319ABC-12-01 Cut-in Range: 100 to 220° F (38 to 105° C)
Differential: 1 to 30° F (0.5 to 17° C)
Sensor Lead Length: 8 ft (2.4 m)
A319 Temperature Control With Sensor A319ABC-24-01 Cut-in Range: –20 to 100° F (–30 to 38° C)
Differential: 1 to 30° F (0.5 to 17° C)
Sensor Lead Length: 8 ft (2.4 m)
A319 Temperature Control With Sensor A319ABC-07-01 Cut-in Range: –25 to 50° F (–32.5 to 10° C)
Differential: 1 to 15° F (0.5 to 8° C)
Sensor Lead Length: 8 ft (2.4 m)
A319 Temperature Control Without Sensor A319ABC-12-02 Cut-in Range: 100 to 220° F (38 to 105° C)
Differential: 1 to 30° F (0.5 to 17° C)
A319 Temperature Control Without Sensor A319ABC-24-02 Cut-in Range: –20 to 100° F (–30 to 38° C)
Differential: 1 to 30° F (0.5 to 17° C)
A319 Temperature Control Without Sensor A319ABC-07-02 Cut-in Range: –25 to 50° F (–32.5 to 10° C)
Differential: 1 to 15° F (0.5 to 8° C)
469
TEMPERATURE & PRESSURE CONTROLS
JOHNSON CONTROLS A28 SERIES TWO-STAGE FLANGE MOUNTED DUCT
THERMOSTAT
DESCRIPTION
The A28AK is a two-stage temperature control with special air coil
sensing element and adjustable mounting flange.
P4408
SELECTION CHART
DIFFERENTIAL F° (C°) MAXIMUM ALLOWABLE
NUMBER OF SWITCH RANGE FIXED
P/N TEMPERATURE AT BULB
STAGES ACTION °F (°C)
Each Stage Between Stage °F (°C)
A28AK-1C 2 2-SPDT Switches 30 to 110 (–1 to 43) 2 (1.1) 3 (1.7) 140 (60)
A28AK-2C 2 2-SPDT Switches 60 to 130 (16 to 54) 2 (1.1) 3 (1.7) 200 (93)
P4410
SELECTION CHART
LOW PRESSURE HIGH PRESSURE MAXIMUM
SWITCH psig (kPa) psig (kPa) PRESSURE LMITED
P/N OVERPRESSURE
ACTION CONNECTOR KNOB ADJ.
Range Diff Range Diff (Non-Adj) psig (kPa)
MICRO-SET™ FOR R-12, R-22, R-134a, R-500, R-502 (R)
65 psi at < 300 psig
36 in. Cap. with 325 Low
P70LB-6C 75 psi at 300-400 psig Cut-out
12 in. to 80 Min 5 (34) 100 to 500 1/4 in. Flare Nut 525 High
SPST 95 psi at > 400 psig
(–41 to 552) Max 35 (241) (690 to 3447) (2241 Low)
Lockout 36 in. Cap. with
P70MA-18C None (3620 High)
(Requires Manual Reset) 1/4 in. Flare Nut
“ALL RANGE” FOR R-12, R-22, R-134a, R-500, R-502 (R)
65 psi < 300 psig
36 in. Cap. with
▲ P70LB-1C 75 psi 300-400 psig Cut-out
Min 7 (48) 1/4 in. Flare Nut 325 Low
95 psi > 400 psig
20 in. to 100 Max 50 (345) 100 to 500 525 High
SPST Lockout 36 in. Cap. with
▲ P70MA-1C (–68 to 690) (690 to 3447) (2241 Low)
(Requires Manual Reset) 1/4 in. Flare Nut
None (3620 High)
Lockout Lockout 36 in. Cap. with
▲ P70NA-1C
(Manual Reset) (Requires Manual Reset) 1/4 in. Flare Nut
Switchable Between
Two Independent 12 in. to 80 Min 5 (34) 100 to 500 36 in. Cap. with 525 Low
P70SA-1C Manual and Automatic None
SPDT Switches (–41 to 552) Max 35 (241) (690 to 3445) 1/4 in. Flare Nut 525 High
Reset
FOR AMMONIA
65 psi < 300 psig
1/4 in. Female 325 Low
P70LA-2C 75 psi 300-400 psig
20 in. to 100 Min 7 (48) 100 to 500 NPT Conn. 525 High
SPST 95 psi > 400 psig None
(–68 to 690) Max 50 (345) (690 to 3445) (2241 Low)
Lockout 1/4 in. Female
P70MA-2C (3620 High)
(Requires Manual Reset) NPT Conn.
▲ Universal Replacement.
470
TEMPERATURE & PRESSURE CONTROLS
JOHNSON CONTROLS P72 SERIES TWO-POLE LOW-PRESSURE CONTROL
DESCRIPTION
The P72 Series of controls employs a set of DPST contacts that are opened and closed by the pres-
sure actuated bellows. The heavy duty load-carrying contacts provide direct control of motors having
integral line-interrupting overload protectors up to three horsepower, 240 volt, single phase. Starter is
unnecessary. Primarily used on air-conditioning and refrigeration applications but also used to con-
trol air, water, and lube oil pressure.
SELECTION CHART
MAX BELLOWS
SWITCH RANGE DIFFERENTIAL PRESSURE KNOB
P/N OVERPRESSURE
ACTION psig (kPa) (psi) CONNECTOR ADJUSTMENT psig (kPa)
DPST: Close High, 20 in. to 100 psi Min 7 (41) 36 in. Cap. with P1019
P72AA-1C None 325 (2241)
Open Low (–68 to 690) Max 50 (345) 1/4 in. flare Nut
SELECTION CHART
MAX BELLOWS
P/N SWITCH RANGE DIFFERENTIAL PRESSURE LIMITED KNOB OVERRUN
ACTION psig (kPa) psi (kPa) CONNECTOR ADJUSTMENT PRESSURE
psig (kPa)
P1019
MICRO-SET™ FOR R-12, R-22, R-134a, R-500, R-502 (R)
Close High 12 in. to 80 Min 5 (34) 36 in. Cap. with
▲ P70AB-12C Cut-out* 525 (3620)
Open Low (–40 to 551) Max 35 (241) 1/4 in. Flare Nut
“ALL RANGE” FOR R-12, R-22, R-134a, R-500, R-502 (R)
▲ P70AA-1C
36 in. Cap with None
1/4 in. Flare Nut
Close High 1/4 in. Male
▲ P70AB-1C Cut-out*
Open Low Min 7 (48) Flared Conn.
20 in. to 100 Max 50 (345) 36 in. Cap. with
▲ P70AB-2C Cut-out* 325 (2241)
(–68 to 690) 1/4 in. Flare Nut
Open High 36 in. Cap. with
▲ P70CA-1C None
Close Low 1/4 in. Flare Nut
P70EA-10C SPDT 5 (34) Fixed 1/4 in. Male None
Flared Conn.
FOR AMMONIA
Close High
P70AA-5C
Open Low 20 in. to 100 Min 7 (48) 1/4 in. Female None 325 (2241)
Open High (–68 to 690) Max 50 (345) NPT
P70CA-4C Close Low
*Adjusting knob supplied on differential (cut-out setting) to limit adjustments to 5 psi (34 kPa) above or below normal setting.
▲ Universal Replacement.
SPST ELECTRICAL RATINGS (P70A and P70C Models) SPDT ELECTRICAL RATINGS (P70E Models)
HERMETIC STANDARD
STANDARD COMPRESSOR SINGLE-PHASE RATINGS
SINGLE-PHASE RATINGS SINGLE-PHASE
120 VAC 208 VAC 240 VAC
RATINGS
Motor Full-Load Amp 16.0 9.2 8.0
120 VAC 208 VAC 240 VAC 208/240 VAC
Motor Locked Rotor Amp 96.0 55.2 48.0
Motor Horsepower 1.5 3 3 —
Non-Inductive Amp 16.0 9.2 8.0
Motor Full-Load Amp 20 18.7 17 20
Pilot Duty 125 VA at 120 to 600 VAC
Motor Locked Rotor Amp 120 112.2 102 120
Non-Inductive Amp 22 22 22 —
Pilot Duty 125 VA at 120 to 600 VAC; 57.5 VA at 120 to 300 VDC
471
TEMPERATURE & PRESSURE CONTROLS
JOHNSON CONTROLS V46 SERIES PRESSURE ACTUATED WATER REGULATING
VALVE
DESCRIPTION
The V46 is a pressure actuated, modulating valve that is suitable for use
either on closed or open systems. Direct acting valves open on pressure
increase. This type of valve is primarily used to regulate the flow of water
or glycol to a water cooled condenser on a refrigeration system. Reverse
acting valves open on pressure decrease and are generally used in paral-
lel with a direct-acting valve or for bypass operation.
P4409
SELECTION CHART
OPENING POINT
PIPE SIZE INLET AND PRESSURE ELEMENT SEAT REPAIR REPLACEMENT
P/N RANGE
(in.) OUTLET STYLE KIT POWER ELEMENTS
psig (kPa)
COMMERCIAL TYPE, STANDARD FLOW — NON-CORROSIVE REFRIGERANTS (R)
V46AA-1C 3/8 NPT STT14A-600R SEP91A-600R and SEC37A-601R
V46AB-1C 1/2 NPT STT15A-602R SEP91A-602R and SEC37A-602R
V46AC-1C 3/4 NPT Threaded 30 in. Capillary STT16A-601R SEP91A-601R and SEC37A-602R
70 to 260
1/4 in. Flare Nut
V46AD-1C 1 NPT (483 to 1793) STT17A-609R
(Style 45)
V46AE-1C 1-1/4 NPT SEP91A-603R and SEC37A-600R
STT17A-610R
V46AR-1C 1-1/2
70 to 170
V46AS-1C 2 SEP81A-602R
(483 to 1172)
STT18A-600R
160 to 260
V46AS-2C 2 4 Hole SEP81A-601R
(1103 to 1793) 1/4 in. Male Flare Fitting
ASME Flange
70 to 170 (Style 5)
V46AT-1C 2-1/2 SEP81A-602R
(483 to 1172)
STT18A-601R
160 to 260
V46AT-2C 2-1/2 SEP81A-601R
(1103 to 1793)
472
PRESSURE CONTROLS
ALCO FF115 SINGLE LOW PRESSURE CONTROLS
The FF115 Low Pressure Controls are designed to sense the FF115 ELECTRICAL RATINGS
suction pressure in refrigeration systems for cycling, limit and
MAXIMUM LOAD 120 VAC 240 VAC
alarm applications. Maximum application flexibility and accuracy
Full Load Amps 24 FLA 24 FLA
are assured by using a heavy-duty 24 amp single pole double
Locked Rotor Amps 144 LRA 144 LRA
throw (SPDT) switch and customized pressure ranges for precise
Horsepower 2 HP 3 HP
sensing.
Pilot Duty 720 VA 720 VA
P1019 Noninductive 24 amps 24 amps
PRESSURE REPLACES
DIFFERENTIAL SWITCH PRESSURE
PART NUMBER RANGE IN
RANGE IN PSI ACTION CONNECTION Penn Copeland Ranco
PSIG
O10-1402
FF-115-S1-BAK 24 to 42 3 to 30 P70AB-12* 085-0098-21
36″ Capillary O16-557
with P70AB-2 O10-1483
FF-115-S3-BAK SPDT 1/4″ Flare Nut P70AB-12 085-0098-00 O11-3099
Auto Reset P70CA-1 O16-527
15 to 100 7 to 70
P70AB-1 O10-1831
1/4″ SAE†
FF-115-S3-BAA P170AB-2,-12* — O11-1799
Male Flare
P170CA-1 O16-107
*Controls have an extended range.
†For applications where the condensing unit/control is exposed to temperatures below 20° F, 1/4″ lines are recommended.
The FF115 High Pressure Controls are designed to sense the FF115 DIMENSIONAL DRAWINGS
high side pressure in refrigeration systems for high pressure limit,
alarm and condenser fan control. Maximum application flexibility
is assured by using a heavy-duty 24 amp single pole double
throw (SPDT) switch and wide range pressure setting capability.
P1020
PRESSURE REPLACES
DIFFERENTIAL SWITCH PRESSURE
PART NUMBER** RANGE IN
RANGE IN PSI ACTION CONNECTION Penn Copeland Ranco
PSIG
O10-2000
FF-115-S4-BAK 15 to 290 15 to 145 P70AA-2 085-0098-33
36″ Capillary O16-593
with O10-2054
P70AA-118
FF-115-S5-BAK 1/4″ Flare Nut 085-0098-08 O11-1711
SPDT P70CA-3
O16-108
Auto Reset
30 to 220 O10-1894
P70CA-2
1/4″ SAE O11-1713
FF-115-S5-BAA P170AA-118 —
Male Flare O16-503
90 to 450 P170CA-3
O16-570
36″ Capillary
SPDT P70DA-1
FF-115-S5-BRK with — O16-200†
Manual Reset P70KA-1*
60 PSI fixed 1/4″ Flare Nut
Trips on
1/4″ SAE
FF-115-S5-BRA pressure rise P170DA-1 — O16-209
Male Flare
*FF115-S5-BRK has common power feed for limit and alarm function.
†48” capillary.
**Limited to stock on hand.
473
PRESSURE CONTROLS
ALCO PS1 SERIES SINGLE PRESSURE CONTROLS
PS1 Single Pressure Controls are designed for use on high SPECIFICATIONS
and low pressure applications in refrigeration and heat • SPDT switch rated for 120 VAC/240 VAC at 24 FLA and
pump systems. By operating a set of electrical contacts, a 144 LRA.
pressure is kept inside a certain limit. • Agency approvals include: UL/CUL file #E85974,
VDE 0631/0660, TUV, CE 73/23/EWG, CE 93/68/EWG.
FEATURES
• Low pressure and high pressure versions available with
• Adjustable pressures and differentials. TUV approval according to EN 12263 (supersedes DIN
• Narrow adjustable differential depending on model. 32733) to meet requirements of DIN 8901 and EN378
• Range and differential pointer in units bar and psig. (supercedes DIN 8975).
• Range and differential individually lockable by wire seal.
• High rated SPDT contacts for all versions.
• Captive terminal and cover screws.
• Manual toggle for system checkout and override.
FF115 REPLACEMENT
• Factory installed wire bridge for reduced installation
effort.
OPTIONS
• Different pressure connections.
• Automatic and manual reset versions.
• Factory set to customer specifications.
• Different types of mounting brackets.
474
PRESSURE CONTROLS
ALCO PS1 SERIES SINGLE PRESSURE CONTROLS
ALCO ADJUSTMENT RANGE FACTORY
ALCO U.S. PRESSURE
P/N EUROPE Upper Setpoint Diff. Setpoint SETTIG
PCN CONNECTION
PCN PSI (BAR) PSI (BAR) PSI (BAR)
LOW PRESSURE CONTROLS
TPC-PS1-X1K 097898 24″ Hg to 42 (-.75 to 3) 4 to 29 (.25 to 2) 7/15 (.5/1) Capillary/nut
PS1-A3A 4370700 7/16″ -20 UNF
TPC-PS1-X3A 097914 7/16″ -20 UNF, 1/4″ SAE male
PS1-A3K 4370600 Capillary/nut
15″ Hg to 100 7 to 73 50/65
TPC-PS1-X3K 097904 Capillary/nut
(-0.5 ... +7) (0.5 ... 5) (3.5/4.5)
PS1-A3L 4714945 Capillary/solder
PS1-A3U 4714945 Solder 6 mm
PS1-A3X 4713430 Solder tube 1/4″
PS1-R3A 4350100 External 7/16″ -20 UNF
PS1-R3K 4713431 Manual Reset Capillary/nut
15″ Hg to 100
PS1-R3L 4715135 Low Pressure 50 (3.5) Capillary/solder
(-0.5 ... +7)
PS1-R3U 4713432 15 psi Solder 6 mm
PS1-R3X 4713433 (1 bar) fixed Solder tube 1/4″
HIGH PRESSURE CONTROLS
TPC-PS1-X4K 097901 15 to 290 (1 to 20) 15 to 100 (1 to 7) 145/115 (10/8) Capillary/nut
PS1-A5A 4350500 230/290 (16/20) 7/16″ -20 UNF
TPC-PS1-X5A 097919 190/280 (10/19) 7/16″ -20 UNF
PS1-A5K 4370400 90 to 450 29 to 217 Capillary/nut
TPC-PS1-X5K 097908 (6 ... 31) (2 ... 15) 230/290 Capillary/nut
PS1-A5L 4715136 (16/20) Capillary/solder
PS1-A5U 4713325 Solder 6 mm
PS1-A5X 4713434 290 (20) Solder tube 1/4″
PS1-R5A 4350700 290 (20) 7/16″-20 UNF
TPC-PS1-Y5A 097923 Ext. Manual Reset 390 (27) 7/16″-20 UNF, 1/4″ SAE male
PS1-R5K 4370300 90 to 450 High Pressure Capillary/nut
TPC-PS1-Y5K 097911 (6 ... 31) 60 psi Capillary/nut
PS1-R5L 4715137 (4 bar) fixed 290 (20) Capillary/solder
PS1-R5U 4713435 Solder 6 mm
PS1-R5X 4713436 Solder tube 1/4″
PRESSURE LIMITER FOR LOW PRESSURE PROTECTION
PS1-W3A 4368300 7/16″-20 UNF
PS1-W3K 4321400 Capillary/nut
15″ Hg to 100 7 to 73 50/65
PS1-W3L 4715138 Capillary/solder
(-0.5 ... +7) (0.5 ... 5) (3.5/4.5)
PS1-W3U 4713437 Solder 6 mm
PS1-W3X 4713438 Solder tube 1/4″
PRESSURE CUT OUT FOR LOW PRESSURE PROTECTION
PS1-B3A 4470400 7/16″-20 UNF
PS1-B3K 4715139 Ext. Manual Reset Capillary/nut
15″ Hg to 100 Low Pressure 65
PS1-B3L 4715140 Capillary/solder
(-0.5 ... +7) 15 psi (4.5)
PS1-B3U 4715141 (1 bar) fixed Solder 6 mm
PS1-B3X 4715142 Solder tube 1/4″
PRESSURE LIMITER FOR HIGH PRESSURE PROTECTION
PS1-W5A 4353200 7/16″-20 UNF
PS1-W5K 4359100 Capillary/nut
90 to 450 29 to 217 230/290
PS1-W5L 4715143 Capillary/solder
(6 ... 31) (2 ... 15) (16/20)
PS1-W5U 4713439 Solder 6 mm
PS1-W5X 4713440 Solder tube 1/4″
475
PRESSURE CONTROLS
ALCO PS1 SERIES SINGLE PRESSURE CONTROLS
ORDERING INFORMATION FOR PS1 SINGLE PRESSURE CONTROLS
ADJUSTMENT RANGE
ALCO U.S. ALCO EUROPE FACTORY SETTING PRESSURE
P/N PCN PCN Upper Setpoint Diff. Setpoint PSI (BAR) CONNECTION
PSI (BAR) PSI (BAR)
PRESSURE CUT OUT FOR HIGH PRESSURE PROTECTION
PS1-B5A 4353300 7/16″-20 UNF
PS1-B5K 4359200 Ext. Manual Reset Capillary/nut
90 to 450 High Pressure
PS1-B5L 4715144 (6 ... 31) 60 psi 290 (20) Capillary/solder
PS1-B5U 4712332 (4 bar) fixed Solder 6 mm
PS1-B5X 4713441 Solder tube 1/4″
SAFETY PRESSURE CUT OUT FOF HIGH PRESSURE PROTECTION
PS1-S5A 4368400 7/16″-20 UNF
PS1-S5K 4359400 Int. Manual Reset Capillary/nut
90 to 450
PS1-S5L 4715145 (6 ... 31) High Pressure 304 (21) Capillary/solder
PS1-S5U 4711591 60 psi (4 bar) fixed Solder 6 mm
PS1-S5X 4713442 Solder tube 1/4″
476
PRESSURE CONTROLS
ALCO PS1 SERIES SINGLE PRESSURE CONTROLS
PS1 PARTS/ACCESSORIES
477
PRESSURE CONTROLS
ALCO FF215 DUAL PRESSURE CONTROLS
FF215 ELECTRICAL RATINGS
MAXIMUM LOAD 120 VAC 240 VAC
Full Load Amps 24 FLA 24 FLA
Locked Rotor Amps 144 LRA 144 LRA
Horsepower 2 HP 3 HP
Pilot Duty 720 VA 720 VA
P1021 Noninductive 24 amps 24 amps
LOW PRESSURE LO PRESS. DIFF. HIGH PRESSURE HI PRESS. DIFF. SWITCH PRESSURE
PART NUMBER**
RANGE IN PSIG RANGE IN PSI RANGE IN PSIG RANGE IN PSI ACTION CONNECTION
FF-215-S9-BAUK 24 to 42 3 to 30 LP SPDT (2) 48″ Capillary
Auto Reset with
FF-215-S7-BAUK
1/4″ Flare Nut
90 to 450 60 fixed
15 to 100 7 to 70 HP SPDT
1/4″ SAE Male
FF-215-S7-BAUA Convertible—User Selects
Flare†
Auto or Manual Reset
P1022
478
PRESSURE CONTROLS
ALCO PS2 SERIES DUAL PRESSURE CONTROLS
PS2 Dual Pressure Controls are designed for use on high and OPTIONS
low pressure applications in refrigeration and heat pump sys- • Different pressure connections.
tems. By operating a set of electrical contacts, a pressure is • Automatic and manual reset versions.
kept inside certain limits. • Factory set to customer specification.
• Different types of mounting brackets.
FEATURES
SPECIFICATIONS
• Adjustable pressures and differentials.
• Narrow adjustable differential depending on model. • SPDT switch rated for 120 VAC/240 VAC at 24 FLA and
144 LRA.
• Range and differential pointer in units bar and psig.
• Agency approvals include: UL/CUL file #E85974, VDE
• Range and differential individually lockable by wire seal.
0631/0660, TÜV, CE 73/23/EWG, CE 93/68/EWG.
• High rated SPDT contacts for all versions.
• Low pressure and high pressure versions available with TÜV
• Captive terminal and cover screws.
approval according to DIN 32733 to meet requirements of
• Manual toggle for system checkout and override. DIN 8901and DIN 8975.
• Factory-installed wire bridge for reduced installation effort.
FF215 REPLACEMENT
NOMENCLATURE — Example PS2-G8A
PS2 G 8 A
Product Name Function Pressure Ranges Pressure Connector Type
PS2 = Adjustable Dual A = Both sides: Pressure controls, automatic reset, 7 = Left side: 15″ Hg to 100 psi A = 7/16″ -20 UNF male for
Pressostat internal range and differential adjustments (-0.5 to 7 bar) 1/4″ SAE flare fitting
PSB = Customer Special B = Both sides: Pressure cut out, external manual
Version reset, DIN/TÜV approved, internal range and Right side: 90 to 450 psi C = R 1/4″ stainless steel with
differential adjustments (6 to 31 bar) steel bellows
C = Left side: Pressure control, automatic reset, 8 = Left side: 90 to 450 psi F = 1/4″ -18 NPTF stainless steel
DIN/TÜV approved, internal range and differential (6 to 31 bar) with steel bellows
adjustments. Right side: Safety cut out, external
manual reset, DIN/TÜV approved, internal range Right side: 90 to 450 psi K* = 7/16″ -20 UNF flare nut with
and differential adjustments. (6 to 31 bar) 1 meter (3 ft) cap tube
G = Left side: Pressure control, automatic reset, 9 = Left side: 24″ Hg to 45 psi L = 1/4″ ODM solder with
DIN/TÜV approved, internal range and differential (-0.75 to 3 bar) 1 meter (3 ft) cap tube
adjustments. Right side: Safety limiter, internal
manual reset, DIN/TÜV approved, internal range Right side: 90 to 450 psi R = R 1/4″
and differential adjustments. (6 to 31 bar) U = 6 mm ODF solder,
L = Left side: Pressure control, automatic reset, 80 mm tube length
internal range and differential adjustments. X = 1/4″ ODF solder, 80 mm tube
Right side: Pressure cut out, external manual
reset, internal range and differential adjustments. length
M = Left side: Pressure control, automatic reset,
internal range and differential adjustments. *Controls with housing variants
Right side: Convertible reset from R to A, internal X/Y/Z have extended copper
range and differential adjustments. ends, without schrader valve
R = Both sides: Pressure cut out, external manual depressor and brass end fitting
reset, internal range and differential adjustments.
S = Both sides: Pressure safety cut out, internal with copper gasket
manual reset, DIN/TÜV approved, internal range
and differential adjustments.
T = Left side: Pressure control, automatic reset,
DIN/TÜV approved, internal range and differential
adjustments. Right side: Safety limiter, internal
manual reset, DIN/TÜV approved, internal range
and differential adjustments.
U = Both sides: Convertible from R to A.
W = Both sides: Pressure control, automatic reset,
TÜV approved, internal range and differential
adjustments.
X = Both sides: Pressure controls, automatic reset,
external range and differential adjustments.
Y = Left side: Pressure control, automatic reset,
external range and differential adjustments.
Right side: Convertible from external manual reset
to automatic reset, external range and differential
adjustments.
Z = Both sides: Convertible from external manual reset
to automatic reset, external range and differential
adjustments.
LOW PRESSURE MANUAL RESET: Cut outs with
manual reset function and in combination with the low
pressure side of Pressure Ranges 7 and 9 have a low
pressure manual reset function (15 psi differential).
HIGH PRESSURE MANUAL RESET: Cut outs with
manual reset function and in combination with the high
pressure side of Pressure Ranges 7 and 9 have a high
pressure manual reset function (60 psi differential).
479
PRESSURE CONTROLS
ALCO PS2 SERIES DUAL PRESSURE CONTROLS
ORDERING INFORMATION FOR PS2 DUAL PRESSURE CONTROLS
ADJUSTMENT RANGE
ALCO FACTORY SETTING
ALCO U.S. Upper Setpoint Differential PRESSURE
P/N EUROPE
PCN Left Right Left Right Left Right CONNECTION
PCN
PSI (BAR) PSI (BAR) PSI (BAR) PSI (BAR) PSI (BAR) PSI (BAR)
COMBINED LOW AND HIGH PRESSURE CONTROLS
TPC-PS2-A7A 097874 4353400 7/16″ -20 UNF
TPC-PS2-A7K 097875 4350900 Capillary/nut
15″ Hg to 100 90 to 450 7 to 72 29 to 217 50/65 230/290
TPC-PS2-A7L 097876 4713565 Capillary/solder
(-0.5...7) (6...31) (0.5...5) (2...5) (3.5/4.5) (16/20)
PS2-A7U 4713415 Solder 6 mm
PS2-A7X 4713416 Solder tube 1/4″
TPC-PS2-L7A 097877 4351100 7/16″ -20 UNF
PS2-L7K 4370500 External Manual Reset Capillary/nut
15″ Hg to 100 90 to 450 7 to 72 50/65 290
TPC-PS2-L7L 097878 4440800 High Press. Capillary/solder
(-0.5...7) (6...31) (0.5...5) (3.5/4.5) (20)
PS2-L7U 4713417 60 (4) fixed Solder 6 mm
PS2-L7X 4713418 Solder tube 1/4″
PS2-R7A 4351300 7/16″ -20 UNF
PS2-R7K 4713421 External Manual Reset External Manual Reset Capillary/nut
15″ Hg to 100 90 to 450 50 290
PS2-R7L 4715134 Low Press. High Press. Capillary/solder
(-0.5...7) (6...31) (3.5) (20)
PS2-R7U 4713419 15 (1) fixed 60 (4) fixed Solder 6 mm
PS2-R7X 4713420 Solder tube 1/4″
COMBINED PRESSURE LIMITER FOR LOW PRESSURE/HIGH PRESSURE PROTECTION
PS2-W7A 4360100 7/16″ -20 UNF
PS2-W7K 4450200 Capillary/nut
15″ Hg to 100 90 to 450 7 to 72 29 to 217 50/65 230/290
PS2-W7L 4450300 Capillary/solder
(-0.5...7) (6...31) (0.5...5) (2...5) (3.5/4.5) (16/20)
PS2-W7U 4712436 Solder 6 mm
PS2-W7X 4713429 Solder tube 1/4″
COMBINED PRESSURE LIMITER/PRESSURE CUT OUT FOR LOW PRESSURE/HIGH PRESSURE PROTECTION
PS2-C7A 4353500 7/16″ -20 UNF
PS2-C7K 4348400 External Manual Reset Capillary/nut
PS2-C7L 5715131 High Press. Capillary/solder
15″ Hg to 100 90 to 450 7 to 72 50/65
PS2-C7U 4713422 60 (4) fixed Solder 6 mm
(-0.5...7) (6...31) (0.5...5) (3.5/4.5) 290
PS2-C7X 4713423 Solder tube 1/4"
(20)
TPC-PS2-Y7A 097954 7/16″ -20 UN
TPC-PS2-Y7K 097943 Convertible Auto/Manual Capillary/nut
24″ Hg to 45 90 to 450 4 to 29 Reset
TPC-PS2-Y9K 097950 7/15 Capillary/nut
(-0.8...3) (6...31) (.25...2)
480
PRESSURE CONTROLS
ALCO PS2 SERIES DUAL PRESSURE CONTROLS
ORDERING INFORMATION FOR PS2 DUAL PRESSURE CONTROLS
ADJUSTMENT RANGE
ALCO FACTORY SETTING
ALCO U.S. Upper Setpoint Differential PRESSURE
P/N EUROPE
PCN Left Right Left Right Left Right CONNECTION
PCN
PSIG (BAR) PSIG (BAR) PSIG (BAR) PSIG (BAR) PSIG (BAR) PSIG (BAR)
COMBINED PRESSURE LIMITER/SAFETY PRESSURE CUT OUT — FOR LOW PRESSURE/HIGH PRESSURE PROTECTION
PS2-T7A 4368500 7/16″ -20 UNF
PS2-T7K 4448000 Internal Capillary/nut
15″ Hg to 100 90 to 450 7 to 72 Manual Reset 50/65 290
PS2-T7L 4715132 Capillary/solder
(-0.5...7) (6...31) (0.5...5) High Press. (3.5/4.5) (20)
PS2-T7U 4713424 60 (4) fixed Solder 6 mm
PS2-T7X 4713425 Solder tube 1/4″
COMBINED PRESSURE CUT OUT — FOR LOW PRESSURE/HIGH PRESSURE PROTECTION
PS2-B7A 4360200 7/16″ -20 UNF
External External
PS2-B7K 4446600 Capillary/nut
15″ Hg to 100 90 to 450 Manual Reset Manual Reset 65 290
PS2-B7L 4446700 Capillary/solder
(-0.5...7) (6...31) Low Press. High Press. (4.5) (20)
PS2-B7U 4449400 Solder 6 mm
15 (1) fixed 60 (4) fixed
PS2-B7X 4713426 Solder tube 1/4″
COMBINED PRESSURE CUT OUT — FOR HIGH PRESSURE/HIGH PRESSURE PROTECTION
PS2-G8A 4368600 7/16″ -20 UNF
External Internal
PS2-G8K 4445500 Capillary/nut
15″ Hg to 100 90 to 450 Manual Reset Manual Reset 65 290
PS2-G8L 4715133 Capillary/solder
(-0.5...7) (6...31) Low Press. High Press. (4.5) (20)
PS2-G8U 4713427 Solder 6 mm
15 (1) fixed 60 (4) fixed
PS2-G8X 4713428 Solder tube 1/4″
481
PRESSURE CONTROLS
ALCO PS2 SERIES DUAL PRESSURE CONTROLS
PS1 DIMENSIONAL DIAGRAM
PS2 PARTS/ACCESSORIES
MOUNTING BRACKET Z TYPE
Alco U.S. PCN #097063, KB-00025
Alco Europe PCN #0411759
UNIVERSAL ANGLE BRACKET
Alco U.S. PCN #097064, KB-00026
Alco Europe PCN #0153962
482
PRESSURE CONTROLS
ALCO FD113-ZU(K) OIL PRESSURE SAFETY CONTROLS
The FD113 Oil Pressure Safety Control senses the effective oil pressure on pressure lubricate
compressors. If inadequate oil pressure exists, a time delay is energized. If the oil pressure
does not recover to safe levels within the time delay setting, the compressor is shut down. The
time delay allows the compressor adequate time to establish oil pressure on start up and avoids
nuisance shutdowns on pressure drop of short duration during the run cycle.
Maximum application flexibility is assured by providing an adjustable differential pressure switch
which can be adjusted to the compressor’s minimum required oil pressure needs and an adjust-
able electronic time delay which allows you to select the length of time the compressor runs
below the minimum pressure before shutdown. The minimum pressure setting and time delay
values specified by the compressor manufacturer should be used when installing the FD113
control.
FEATURES P1023
• Pressure range adjustable from 4 to 65 PSID; Timer start
pressure-timer stop pressure is 3 PSID above timer start pressure.
• A SPDT switch is used in the pressure portion of the control which allows the
addition of a “safe light” if desired.
• Electronic timer is Timer-Adjustable from 20 to 150 seconds.
• Supply voltage - 24 to 240 Volt AC/DC. Timing unaffected by voltage or ambi-
ent temperature variations.
• A SPDT Manual Reset Switch is used in the Timer Module. Upon time-out,
the compressor is stopped and an alarm circuit is energized. To restart the
compressor and de-energize the alarm circuit, the reset button is pushed. SPECIFICATIONS
• A factory installed jumper allows the FD113 to be powered from a single • Agency approvals include: UL/CUL file
power source. Should separate circuits be desired for the timer and “Lockout” #E85974, VDE 0631/0660, TUV, CE 73/23/EWG,
switch, the jumper can be removed. CE 93/68/EWG.
P1023B P1023A
*For applications where the condensing unit/control is exposed to temperatures below 20° F, 1/4″ lines are recommended.
483