0% found this document useful (0 votes)
35 views

Manual Ethernet Ip Module en 80004

MANUAL MODULO 80004

Uploaded by

salgueraj
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
35 views

Manual Ethernet Ip Module en 80004

MANUAL MODULO 80004

Uploaded by

salgueraj
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 70

Reference Manual

00809-0100-4765, Rev. AB
April 2016

Rosemount™ 8732EM EtherNet/IP™ Module


Reference Manual Table of Contents
00809-0100-4765, Rev. AB April 2016

Contents
1Section 1: Introduction
1.1 About the Rosemount™ 8732EM EtherNet/IP™ Module . . . . . . . . . . . . . . . . . . . . . 1
1.1.1 Functional overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
1.1.2 Communications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
1.1.3 External view of device. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
1.1.4 Default web pages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

2Section 2: Installation
2.1 Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
2.2 Device installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
2.3 Final steps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

3Section 3: Basic Network Configuration


3.1 TCP/IP settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
3.1.1 IP access control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
3.2 Modbus® serial network settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10

4Section 4: Rosemount™ Web Server


4.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
4.2 General access information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
4.2.1 Ports . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
4.2.2 Users . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
4.3 Rosemount web pages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
4.3.1 Home page . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

5Section 5: Troubleshooting
5.1 LED display indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
5.2 Common problems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
5.3 Customer Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
5.4 Return policy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
5.4.1 Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
5.4.2 New and unused equipment. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
5.4.3 Used equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

Table of Contents i
Table of Contents Reference Manual
April 2016 00809-0100-4765, Rev. AB

AAppendix A: Connector Pin Assignments


A.1 Ethernet connector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
A.2 Power connector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
A.3 Ethernet Config Tool connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18
A.3.1 Configuration cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
A.3.2 RJ-11 (EtherNet/IP™ Module) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
A.3.3 DBF9 (PC) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
A.4 Modbus® serial network interface. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
A.4.1 Bias resistors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
A.4.2 Termination . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
A.4.3 Pin assignments (EtherNet/IP Module). . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
A.5 Typical connection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20

BAppendix B: Device Profile


B.1 Object classes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21
B.2 Object details . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21
B.2.1 Identity Object, Class 01h . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
B.2.2 Message Router, Class 02h . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
B.2.3 Assembly Object, Class 04h . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
B.2.4 Port Object, Class F4h . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
B.2.5 TCP/IP Interface Object, Class F5h. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
B.2.6 Ethernet Link Object, Class F6h . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
B.2.7 Diagnostic Object, Class AAh . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
B.2.8 Parameter Data Input Mapping Object, Class B0h . . . . . . . . . . . . . . . . . . . 28
B.2.9 Parameter Data Output Mapping Object, Class B1h . . . . . . . . . . . . . . . . . 29
B.3 I/O data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31
B.3.1 Input assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
B.3.2 Output assembly. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
B.3.3 Input parameters—explicit data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
B.3.4 Output parameters—explicit data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
B.4 Get and Set services. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .46
B.4.1 Get Attribute Single service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
B.4.2 Set Attribute Single service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
B.5 Data types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .47
B.6 Codes and integer values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .47

ii Table of Contents
Reference Manual Table of Contents
00809-0100-4765, Rev. AB April 2016

CAppendix C: Specifications
C.1 Physical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .61
C.1.1 Housing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
C.1.2 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
C.2 Electrical. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .61
C.2.1 Power supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
C.2.2 Power consumption . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
C.3 Environmental . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .61
C.3.1 Relative humidity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
C.3.2 Temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
C.4 Regulatory compliance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .62
C.4.1 EMC compliance (CE) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
C.4.2 UL/c-UL compliance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
C.4.3 Galvanic isolation on Modbus serial interface . . . . . . . . . . . . . . . . . . . . . . . 62

Table of Contents iii


Table of Contents Reference Manual
April 2016 00809-0100-4765, Rev. AB

iv Table of Contents
Reference Manual Introduction
00809-0100-4765, Rev. AB April 2016

Section 1 Introduction

1.1 About the Rosemount™ 8732EM EtherNet/IP™


Module
The Rosemount 8732EM EtherNet/IP™ Module is a customization of the Anybus®
Communicator™ from HMS Industrial Networks. The Ethernet module enables integration
of industrial devices into the Ethernet network with no loss of functionality, control, or
reliability. The Ethernet module can be used for new or retrofit installations.

This manual contains only the information required to install, configure, and use the
Ethernet module. Other OEM features are still enabled on the device, but are not
documented here. For information on other features of the device, see the Anybus
Communicator User Manual manual, available on the HMS web site.

1.1.1 Functional overview


The Rosemount 8732EM EtherNet/IP Module acts as a gateway between the serial output of
a Rosemount 8732EM Modbus® Magnetic Flowmeter Transmitter and an Ethernet network.

The Ethernet module is a Modbus master and an Ethernet slave. On the Modbus side, it polls
the transmitter for a standard set of process variables and stores the data locally. See
Section B.3 for a list of available data. On the Ethernet side, it receives requests for data and
responds with the current values. Figure 1-1 illustrates the Ethernet module in operation.
 The Ethernet module is installed with a Rosemount 8732EM Modbus Transmitter.
 The web browser is used for transmitter configuration and administration, via a
connection to the Rosemount web pages on the Ethernet module.

Figure 1-1 EtherNet/IP Module with Rosemount 8732EM Modbus Transmitter

A. PLC F. Configuration loop (with configuration cable)


B. Web browser G. Modbus/RS-485
C. Ethernet H. PC with Ethernet config tool
D. Other devices (SCADA, PC, Inverter) I. Rosemount 8732EM Transmitter
E. EtherNet/IP Module J. To sensor

Introduction 1
Introduction Reference Manual
April 2016 00809-0100-4765, Rev. AB

1.1.2 Communications
The following communications methods and protocols are supported:
 Ethernet module to Rosemount transmitter: Modbus RTU on RS-485
 Ethernet module to Ethernet network:
- EtherNet/IP group 2 and 3 servers
- Web server
- 10/100 Mbit/sec, twisted pair

1.1.3 External view of device


Figure 1-2. External View of Device

E G

A. Ethernet connector E. Modbus serial connector (transmitter)


B. Configuration switches F. Power connector
C. Status LEDs G. DIN rail connector
D. PC connector (configuration)

1.1.4 Default web pages


The Ethernet module is preloaded with the Rosemount 8732EM web pages. These pages
allow the user to view process data and alerts, configure the most commonly used
parameters on the transmitter, perform maintenance procedures, and download support
files from the device.

2 Introduction
Reference Manual Installation
00809-0100-4765, Rev. AB April 2016

Section 2 Installation

Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3
Device installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3
Final steps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page 6

2.1 Components
Ensure all required components are present:
 Rosemount™ 8732EM EtherNet/IP™ Module
 Power connector
 Rosemount 8732EM EtherNet/IP Resource CD
- Rosemount 8732EM EtherNet/IP Module User Manual
- EDS file
 Modbus® serial cable and connector (included)
 Ethernet cable and connector (not included)

2.2 Device installation


1. Mount the transmitter.

2. Wire the transmitter to the sensor and to a power source.

3. After the transmitter has been powered up:


a. Set the Modbus address on the transmitter to 1.
b. Configure its RS-485 terminals as follows:
 Modbus RTU
 38400 baud
 0-1-2-3 Float byte sequence order
 2 stop bits
 No parity

Installation 3
Installation Reference Manual
April 2016 00809-0100-4765, Rev. AB

4. Mount the Ethernet module on the DIN rail.


Snap on Snap off

1
1

2 2

5. Wire the Ethernet module to power (24 VDC) as shown in Figure 2-1.

Figure 2-1. Ethernet Module Power Connection

A. +24 VDC
B. Ground

6. Install the Modbus serial cable between the Ethernet module and the RS-485
terminals on the transmitter.

EtherNet/IP Module
Modbus terminals
1 Modbus serial connector Transmitter
4
1) Not used RS-485/A RS-485/B
2) Not used
8732EM 2 1
9
5 3) Not used
4) Not used
6
1
5) Not used
6) Not used
1
7) Not used
2
8) RS-485/A
9) RS-485/B

7. Set the configuration dip switches on the Ethernet module as follows:


 Switches 1–7: Off
 Switch 8: On

This sets the IP addess to 192.168.0.1.

4 Installation
Reference Manual Installation
00809-0100-4765, Rev. AB April 2016

8. Power up the Ethernet module. At this point, the module will attempt to make a
Modbus connection to the transmitter. If the Subnet Status LED (LED 5) is green,
continue. If it is not green, see Section 5.1.

9. Set the network settings for the Ethernet module.


a. Change Ethernet address setting for your PC so that it is on the same
subnet as the device. When prompted, enter the following:
 IP address: 192.168.0.x, where x is something other than 1
 Subnet mask: 255.255.255.0
b. Disable the popup blocker on your web browser.
c. Use a crossover cable (or a standard cable with a switch) and your web
browser to connect to the device, using the IP address assigned in Step 7:
192.168.0.1.
d. At the login screen, enter admin. Ignore the auto-configuration popup
window.
e. On the Network Settings page, change the settings as required, and close
the web browser.
f. At the Ethernet module, set all dip switches to Off.
g. Cycle power to the Ethernet module.

10. Connect the Ethernet module to the Ethernet network as shown in Figure 2-2.

Figure 2-2. Ethernet Connector

A. Ethernet connector pins:


Pin 1—TD+
Pin 2—TD–
Pin 3—RD+
Pin 4—NC
Pin 5—NC
Pin 6—RD–
Pin 7—NC
Pin 8—NC

11. Wait for the auto-configuration process to complete.

Installation 5
Installation Reference Manual
April 2016 00809-0100-4765, Rev. AB

Important
For initial startup, the auto-configuration process is required to ensure device memory is
completely set up.

12. Add the Ethernet module to the Ethernet network control system. The EDS file is
available on the Resource CD, the Ethernet module (download from Administration
page), and the Rosemount web site.

For more information on transmitter installation and wiring, see the transmitter installation
manual. For information on configuring the RS-485 terminals and making an RS-485
connection, see the transmitter configuration manual.

2.3 Final steps


1. From a browser, access the login screen and enter admin. Ignore the
auto-configuration popup window.

2. Use the Device Configuration page to configure the Ethernet module.

6 Installation
Reference Manual Basic Network Configuration
00809-0100-4765, Rev. AB April 2016

Section 3 Basic Network Configuration

TCP/IP settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 7


Modbus® serial network settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 10

3.1 TCP/IP settings


To participate on the Ethernet network, the Rosemount™ 8732EM EtherNet/IP™ Module
needs a valid TCP/IP configuration.

The Ethernet module can retrieve the TCP/IP settings from a DHCP or BootP server. If no
such server is found, the Ethernet module uses the settings from the system file \ethcfg.cfg.
If this file is not found, or the settings are invalid, the Ethernet module will halt and report an
error on the status LED. However, the network configuration may still be accessed via the
Ethenet Config Tool.

You can define the TCP/IP settings for the Ethernet module in four ways:
 Rosemount Network Configuration web page (recommended)
 Configuration switches on the device
 Ethernet Config Tool
 System file \ethcfg.cfg on the device

Rosemount web page

The Network Configuration page, in the Rosemount web pages, allows setting of the IP
address, gateway address, and subnet address. Connecting to the Ethernet module using a
crossover cable and the default IP address allows setting all three parameters. The changes
take effect at the next connection.

Configuration switches

If the configuration switches on the Ethernet module are set to any non-zero value, the
device is locked to the following network settings:

Table 3-1 Network settings, locked

Parameter Value
IP address 192.168.0.x
where x is determined by the switches

Basic Network Configuration 7


Basic Network Configuration Reference Manual
April 2016 00809-0100-4765, Rev. AB

Table 3-1 Network settings, locked

Parameter Value
Gateway 192.168.0.255
Subnet 255.255.255.0
DHCP OFF

To set the IP address, see the following table.

Table 3-2 Network settings using switches

Switch
IP address
1 2 3 4 5 6 7 8
OFF OFF OFF OFF OFF OFF OFF ON 192.168.0.1
OFF OFF OFF OFF OFF OFF ON OFF 192.168.0.2
OFF OFF OFF OFF OFF OFF ON ON 192.168.0.3
ON ON ON ON ON ON ON OFF 192.168.0.254
ON ON ON ON ON ON ON ON Invalid

Ethernet Config Tool

See the Anybus® Communicator™ manual for instructions.

Important
If you change the network settings using the Ethernet Config Tool, you will not be able to
use the Rosemount web pages to change network settings in the future. All future changes
to network settings must be performed using the Ethernet Config Tool.

ethcfg.cfg file

To set the network settings using the \ethcfg.cfg file:

1. Set all configuration switches on the device to OFF.

2. Make a connection to the device from the Ethernet Config Tool and disable TCP/IP
Settings (Fieldbus parameter section). Alternatively, you can access the TCP/IP
parameters using the TCP/IP Interface Object.

3. From the FTP server, access and edit \ethcfg.cfg as desired.

In this scenario, if no \ethcfg.cfg file is found, the Ethernet module will attempt to retrieve
the settings via DHCP for 30 seconds. If the attempt fails, the Ethernet module will halt and
indicate an error via the LEDs.

See the Anybus Communicator manual for more information.

8 Basic Network Configuration


Reference Manual Basic Network Configuration
00809-0100-4765, Rev. AB April 2016

3.1.1 IP access control


You can limit the set of IP addresses that are allowed to connect to the Ethernet module.
This information is stored in the system file \ip_accs.cfg.

Sample file:

[Web]
xxx.xxx.xxx.xxx (All nodes listed can access the EtherNet/IP Module
web server)
...
[FTP]
xxx.xxx.xxx.xxx (All nodes listed can access the EtherNet/IP Module
FTP server)
...
[EtherNet/IP]
xxx.xxx.xxx.xxx (All nodes listed can access the EtherNet/IP Module
via EtherNet/IP)
...
[All]
xxx.xxx.xxx.xxx (Fallback setting; used when one or more of the
above keys is omitted)
...

Basic Network Configuration 9


Basic Network Configuration Reference Manual
April 2016 00809-0100-4765, Rev. AB

3.2 Modbus® serial network settings


The required parameters for the Modbus serial network for use with the Ethernet module
are listed in the following table.

Note
The Rosemount 8732EM Modbus® Transmitter default parameters for Modbus serial
network communication are different than those listed below. Transmitter configuration
may be required to match the parameters in Table 3-3.

Table 3-3 Required parameters for Modbus serial network

Parameter Required setting


Baud 38400
Float byte sequence order 0-1-2-3
Data bits 8 (Modbus RTU)
Parity None
Physical layer RS485
Start bits 1
Stop bits(1) 2

1. For baud rates of 38400 and above, 2 stop bits are required.

These must match the RS-485 parameters configured in the transmitter. To change them in
the Ethernet module, you must use the Ethernet Config Tool. See the Anybus
Communicator manual for more information.

10 Basic Network Configuration


Reference Manual Rosemount™ Web Server
00809-0100-4765, Rev. AB April 2016

Section 4 Rosemount™ Web Server


41

Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 11
General access information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 11
Rosemount web pages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 11

4.1 Overview
The configuration and administration functions of the Rosemount 8732EM EtherNet/IP™
Module are implemented as web pages on the device. Users use their web browsers to
connect to the web server. They are automatically directed to the Rosemount web pages.

4.2 General access information


4.2.1 Ports
The web server communicates through port 80.

4.2.2 Users
Two users are predefined for the Rosemount web pages. You can change the passwords, but
you cannot add or delete users.

Default
Username Description
password
admin admin Complete access to all functions on the Rosemount web pages
operator operator Read-only access to the Rosemount web pages

4.3 Rosemount web pages


When the user connects to the Ethernet module, he is prompted for a user name and
password, then taken to the Ethernet module home page.

Rosemount™ Web Server 11


Rosemount™ Web Server Reference Manual
April 2016 00809-0100-4765, Rev. AB

4.3.1 Home page


Figure 4-2. EtherNet/IP Module Home Page

On this page, current data for the most commonly used process variables is displayed. Tabs
provide access to other web pages:
 Administration page: Allows the admin user to change passwords and perform
downloads from the Ethernet module (the EDS file).
 Network Configuration page: Allows the user to view or configure Ethernet module
network settings
 All other pages: Various transmitter tasks, including viewing process data,
configuration, calibration, stopping and starting totalizers, and Smart Meter
Verification. For more information about any of these tasks, see your transmitter’s
configuration manual.

Note
If the Ethernet module loses communication with the Rosemount device, all process variables
are shown as 0.0f. Also, an explicit read to 0xB0-0x01-0x1D returns a value of 0.

12 Rosemount™ Web Server


Reference Manual Troubleshooting
00809-0100-4765, Rev. AB April 2016

Section 5 Troubleshooting

LED display indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 13


Common problems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 14
Customer Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 15
Return policy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 15

5.1 LED display indicators

LED display
Status Meaning
number/name
1 Module Off No power applied to the module.
Status
Solid green The module is operating correctly.
Flashing green Standby; the module has not been initialized.
Flashing red Minor fault. The module may or may not be able to recover.
Solid red Major fault. No recovery is possible. The module must be returned to
Rosemount™ for repair. See the manual for the return policy.
Ethernet

Flashing green/red Self-test


2 Network Off The module has no power or no IP address has been assigned.
Status
Solid green The module has at least one established Ethernet connection.
Flashing green There are no Ethernet connections established to the module.
Flashing red One or more of the connections to this module has timed out.
Solid red The module has detected that its IP address is already in use.
Flashing green/red Self-test
N/A 3 Link Off The module does not sense a link.
Solid Green The module is connected to an Ethernet network.
N/A 4 Activity Flashing green Packet is received or transmitted.

Troubleshooting 13
Troubleshooting Reference Manual
April 2016 00809-0100-4765, Rev. AB

LED display
Status Meaning
number/name
5 Subnet Off Power off.
Status
Flashing green Running correctly, but one or more transaction errors has occurred.
Solid Green Running.
Solid Red Transaction error/timeout or network stopped. Check the Modbus
Modbus Serial

serial network wiring and configuration, especially the baud.


Flashing red Missed transactions.
6 Device Status Off Power off.
Flashing red/green Configuration missing or invalid.
Solid Red Contact Rosemount customer service.
Flashing red Contact Rosemount customer service.
Solid Green Initializing
Flashing green Configuration OK.

5.2 Common problems

Symptom Resolution
Problem during configuration Serial communication failed. Try again.
upload/download.
The Config Line LED turns red in Serial communication failed. Try again.
the Ethernet Config Tool.
The serial port seems to be avail- • The serial port may be in use by another application. Exit the Ethernet module
able, but it is not possible to Configuration Tool and close all other applications, including the ones in the system
connect to the Ethernet tray. Try again.
module. • Select another serial port. Try again.
Poor performance • In the Ethernet Config Tool, right-click Sub-Network in the Navigation window and
select Sub-Network Status to see status / diagnostic information about the Moldbus
serial network. If the Ethernet module reports a large number of re-transmissions,
check your cabling and/or try a lower baud rate setting for the Modbus serial
network (if possible).
• Is the Sub-Net Monitor in the Ethernet Config Tool active? The sub-network
monitor has a negative influence on the overall performance of the gateway, and
should be used only when necessary.
• Is the Node Monitor in the Ethernet Config Tool active? The node monitor has a
negative influence on the overall performance of the gateway, and should be used
only when necessary.
No Modbus serial network func- • Use the Data logger functionality of the Ethernet Config Tool to record the serial
tionality data communication on the sub-network.
• If no data is being transmitted, use the Ethernet Config Tool to check the configura-
tion.
• If no data is being received, check the cables and connections. Also verify that the
transmitted data is correct.
Process variables displayed or • Verify the Modbus connection between the Ethernet module and the device.
reported as 0

14 Troubleshooting
Reference Manual Troubleshooting
00809-0100-4765, Rev. AB April 2016

5.3 Customer Service


Location Telephone number
U.S.A. 800-522-6277 (toll free)
Canada and Latin America +1 303-527-5200 (U.S.A.)
Asia Japan 3 5769-6803
All other locations +65 6777-8211 (Singapore)
Europe U.K. 0870 240 1978 (toll-free)
All other locations +31 (0) 318 495 555 (The Netherlands)
Email: [email protected]

5.4 Return policy


5.4.1 Requirements
Emerson Process Management procedures must be followed when returning equipment.
These procedures ensure legal compliance with government transportation agencies and
help provide a safe working environment for Emerson employees. Failure to follow Emerson
Process Management procedures will result in your equipment being refused delivery.

Information on return procedures and forms is available from the Rosemount Customer
Service department.

5.4.2 New and unused equipment


Only equipment that has not been removed from the original shipping package will be
considered new and unused. New and unused equipment requires a completed Return
Materials Authorization form.

5.4.3 Used equipment


To expedite the return process outside the United States, contact the nearest Rosemount
representative. Within the United States and Canada, call the North American Response
Center using the 800-654-RSMT (7768) toll-free number. The Response Center, available 24
hours a day, will assist you with any needed information or materials.

The center will ask for product, model, and serial numbers and will provide a Return Material
Authorization (RMA) number. The center will also ask for the name of the process material
to which the product was last exposed.

Mishandling products exposed to a hazardous substance may result in death or serious


injury. If the product being returned was exposed to a hazardous substance as defined by
OSHA, a copy of the required Material Safety Data Sheet (MSDS) for each hazardous
substance identified must be included with the returned goods. The North American
Response Center will detail the additional information and procedures necessary to return
goods exposed to hazardous substances.

Troubleshooting 15
Troubleshooting Reference Manual
April 2016 00809-0100-4765, Rev. AB

16 Troubleshooting
Connector Pin Assignments Reference Manual
April 2016 00809-0100-4765, Rev. AB

Appendix A Connector Pin Assignments

Ethernet connector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 17


Power connector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 17
Ethernet Config Tool connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 18
Modbus® serial network interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 19
Typical connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 20

A.1 Ethernet connector

Pin Signal
Housing Cable shield
1 TD+
2 TD–
1 8
3 RD+
4 NC
5 NC
6 RD–
7 NC
8 NC

A.2 Power connector

Pin Description 1 2

1 +24 VDC
2 Ground

 Use 60/75 or 75 x C copper (CU) wire only.


 The terminal tightening torque must be between 5 and 7 lbs-in (0.5 to 0.8 Nm).

Connector Pin Assignments 17


Reference Manual Connector Pin Assignments
00809-0100-4765, Rev. AB April 2016

A.3 Ethernet Config Tool connection


A.3.1 Configuration cable
DP9F (PC) RJ-11 (EIP)

1 1 Ground

RS232 Rx 2 2 Ground

RS232 Tx 3 3 Rx

4 4 Tx

Ground 5

A.3.2 RJ-11 (EtherNet/IP™ Module)

Pin Description
1 Ground 4
2 Ground 3
3 RS-232 Rx (Input) 2
1
4 RS-232 Tx (Output)

A.3.3 DBF9 (PC)


Pin Description
5 (female) 1

1 Unused
2 RS-232 Rx (Input)
9 6
3 RS-232 Tx (Output)
4 Unused
5 Signal ground
6–9 Unused

18 Connector Pin Assignments


Connector Pin Assignments Reference Manual
April 2016 00809-0100-4765, Rev. AB

A.4 Modbus® serial network interface


The Modbus serial network is based on an RS-485 physical layer.

A.4.1 Bias resistors


When idle, RS-485 enters an indeterminate state, which may cause the serial receivers to
pick up noise from the serial lines and interpret this as data. To prevent this, the serial lines
should be forced into a known state using pull-up and pull-down resistors, commonly
known as bias resistors.

The bias resistors forms a voltage divider, forcing the voltage between the differential pair
to be higher than the threshold for the serial receivers, typically >200 mV. Note that bias
resistors shall only be installed on one node. Installing bias resistors on several nodes may
compromise the signal quality on the network and cause transmission problems.

A.4.2 Termination
To avoid reflections on the serial lines, it is important to properly terminate the sub-network
by placing termination resistors between the serial receivers near the end nodes.

Additionally, if the distance from the Ethernet module to the transmitter is greater than
100 feet, Rosemount™ recommends adding the termination resistors.

The resistor value should ideally match the characteristic impedance of the cable, typically
100 to 120 ohms.

A.4.3 Pin assignments (EtherNet/IP Module)


Pin Description
1 Unused
2 Unused 5 (female) 1
3 Unused
4 Unused
9 6
5 Ground
6 Unused
7 Unused
8 RS-485/A (Tx+)
9 RS-485/B (Tx–)
(housing) Cable shield

Connector Pin Assignments 19


Reference Manual Connector Pin Assignments
00809-0100-4765, Rev. AB April 2016

A.5 Typical connection


5V

470 
RS-485/A

120  120 
RS-485/B

470 
Signal ground

Signal ground RS-485/B RS-485/A

Cable shield Node


EtherNet/IP Module

20 Connector Pin Assignments


Device Profile Reference Manual
April 2016 00809-0100-4765, Rev. AB

Appendix B Device Profile

Object classes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 21


Object details . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 21
I/O data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 31
Get and Set services . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 46
Data types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 47
Codes and integer values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 47

B.1 Object classes


Table B-1 lists and describes all object classes supported by the Ethernet module.

Table B-1. Object Classes and Descriptions

Optional/
Object Class ID Description
required
Identity 0x01 Required Contains information that uniquely describes the device
Message Router 0x02 Required Tracks the accessibility of the object classes and instances
Assembly 0x04 Required Contains a list of attributes that data can be written to (sink) or read
from (source)
Port 0xF4 Required
TCP/IP Interface 0xF5 Required Groups settings related to TCP/IP.
Ethernet Link 0xF6 Required Groups diagnostic information for the Ethernet interface
Diagnostic 0xAA Optional Groups diagnostic information for the fieldbus interface
Parameter Data 0xBO Optional Used for acyclic access to input data
Input Mapping
Parameter Data 0xB1 Optional Used for acyclic acces to output data
Output Mapping

B.2 Object details


B.2.1 Identity Object, Class 01h
This object provides identification of and general information about the device. It contains
informational attributes that uniquely describe the device.

Example: The use of attributes Vendor ID, Device Type, Product Code, and Serial Number
together uniquely identify this device.

Device Profile 21
Reference Manual Device Profile
00809-0100-4765, Rev. AB April 2016

Supported services
Class services:
 Get Attribute All
 Get Attribute Single

Instance services:
 Get Attribute All
 Get Attribute Single
 Reset

Class attributes

# Access Name Type Value Description


1 Get Revision UINT 0001h Revision 1

Instance attributes

# Access Name Type Value Description


1 Get Vendor ID UINT Default: 0392h Rosemount Inc
2 Get Device Type UINT Default: 000Ch Communication Adapter
3 Get Product UINT Default: 0002h 2 = 8732EM EtherNet/IP™
Code Module
4 Get Revision Struct of:
USINT Major fieldbus version
USINT Minor fieldbus version
5 Get Status WORD Device status; see
following table
6 Get Serial UDINT Serial number (set at production)
Number
7 Get Product SHORT_STRING “8732EM EtherNet/IP Name of product
Name Module”

22 Device Profile
Device Profile Reference Manual
April 2016 00809-0100-4765, Rev. AB

Device status

Bit(s) Name
0 Module Owned
1 (reserved)
2 Configured
3 (reserved)
4... 7 Extended Device Status:
Value: Meaning:
0000b Unknown
0010b Faulted I/O Connection
0011b No I/O connection established
0100b Non-volatile configuration bad
0110b Connection in Run mode
0111b Connection in Idle mode
(other) (reserved)
8 Set for minor recoverable faults
9 Set for minor unrecoverable faults
10 Set for major recoverable faults
11 Set for major unrecoverable faults
12... 15 (reserved)

Reset service
When the Identity Object receives a Reset request, it:
 Determines if it can provide the type of reset requested
 Responds to the request
 Attempts to perform the type of reset requested

B.2.2 Message Router, Class 02h


The Message Router Object provides a messaging connection point through which a Client
may address a service to any object class or instance residing in the physical device.

B.2.3 Assembly Object, Class 04h


The Assembly Object binds attributes of multiple objects, which allows data to or from each
object to be sent or received over a single connection. Assembly objects can be used to bind
input data or output data. The terms “input” and “output” are defined from the network's
point of view. An input produces data on the network and an output consumes data from
the network.

This object provides access to the I/O Data in the Input and Output Data areas in the
Ethernet module.

Device Profile 23
Reference Manual Device Profile
00809-0100-4765, Rev. AB April 2016

Supported services
Class services:
 Get Attribute Single

Instance services:
 Get Attribute Single
 Set Attribute Single

Class attributes

# Access Name Type Value Description


1 Get Revision UINT 0002h Revision 2
2 Get Max Instance UINT - The highest initiated instance
number

Instance attributes - Instance/Connection Point 64h


This instance corresponds to I/O Data (Input) in the Rosemount™ 8732EM EtherNet/IP
Module. The Ethernet module supports two different configurations. Specific input
assembly attributes depend on the configuration in use.

Configuration Input assembly attributes


Basic See Section B.3.1

Note
The default input data size is non-zero. The actual size depends on the configuration in use.
If the I/O input data size is set to 0, this instance will NOT be initialized.

# Access Name Type Value Description


3 Get Data Array of BYTE - Data produced by the Ethernet
module

Instance attributes - Instance/Connection Point 96h


This instance corresponds to I/O Data (Output) in the Ethernet module. The Ethernet
module supports two different configurations. Specific input assembly attributes depend
on the configuration in use.

Configuration Output assembly attributes


Basic See Section B.3.2

24 Device Profile
Device Profile Reference Manual
April 2016 00809-0100-4765, Rev. AB

Note
The default output data size is non-zero. The actual size depends on the configuration in
use. If the I/O output data size is set to 0, this instance will NOT be initialized.

# Access Name Type Value Description


3 Set Data Array of BYTE - Data consumed by the Ethernet
module

Note
Rockwell Automation PLCs have the first four bytes consumed by a device defined as status
information. This behavior is specific to devices from Rockwell Automation and is not
defined in the Ethernet specification. However, since all known PLCs are implemented this
way, the Ethernet module adopts this behavior and strips off the corresponding four bytes
from the consumed data.

B.2.4 Port Object, Class F4h


Supported services
Class services:
 Get Attribute Single
 Get Attribute All

Instance services:
 Get Attribute Single
 Get Attribute All

Class attributes

# Access Name Type Value Description


1 Get Revision UINT 0001h Revision 1
2 Get Max Instance UINT 0002h 2 is the highest instance number
3 Get No. of instances UINT 0001h 1 instance is implemented
8 Get Entry Port UINT 0002h Returns the instance of the Port object
that describes the port.
9 Get All Ports Array of 0000h Array of structure containing attributes
STRUCT 0000h 1 and 2 from each instance. Instance 1 is
at byte offset 4. Instance 2 is at byte
{UINT; UINT;} 0000h
offset 8, etc. The 4 bytes at offset 0 shall
0000h
be 0. (Default)
0004h
0002h

Device Profile 25
Reference Manual Device Profile
00809-0100-4765, Rev. AB April 2016

Instance attributes, Instance 02h

# Access Name Type Value Comments


1 Get Port Type UINT 0000h TCP/IP
2 Get Port Number UINT 0002h Port 2
3 Get Port Object Struct of:
Path Size UINT 0002h -
Path Padded EPATH 20 F5 24 01h TCP class, Instance 1
4 Get Port Name SHORT_STRING “TCP/IP” Name of port
8 Get Node Address Padded EPATH - -

B.2.5 TCP/IP Interface Object, Class F5h


This object groups TCP/IP-related settings.

Supported services
Class services:
 Get Attribute All
 Get Attribute Single

Instance services:
 Get Attribute All
 Get Attribute Single
 Set Attribute Single

Class attributes

# Access Name Type Value Comments


1 Get Revision UINT 0001h Revision 1
2 Get Max Instance UINT 0001h 1 is the highest instance number
3 Get No. of instances UINT 0001h 1 instance is implemented

Instance attributes

# Access Name Type Value Comments


1 Get Status DWORD 00000001h Attribute #5 contains valid infor-
mation.
2 Get Configuration Capability DWORD 00000016h Attribute #5 is settable. Capable
of obtaining network configura-
tion via DHCP.
3 Get/Set Configuration Control DWORD 0: Configuration from
non-volatile memory
2: Configuration from DHCP

26 Device Profile
Device Profile Reference Manual
April 2016 00809-0100-4765, Rev. AB

# Access Name Type Value Comments


4 Get Port Object Struct of:
Path Size UINT 0002h 2 words
Path Padded EPATH 20 F6 24 01h Path to Ethernet Class, Instance 1
5 Get/Set Interface Configuration Struct of:
IP Address UDINT IP address
Subnet Mask UDINT Subnet mask
Gateway Address UDINT Gateway Address
Name Server 1 UDINT Primary DNS
Name Server 2 UDINT Secondary DNS
Domain Name STRING Default domain name
6 Get/Set Host Name STRING Host name

B.2.6 Ethernet Link Object, Class F6h


This object groups diagnostic information for the Ethernet interface.

Supported services
Class services:
 Get Attribute All
 Get Attribute Single

Instance services:
 Get Attribute All
 Get Attribute Single

Class attributes

# Access Name Type Value Description


1 Get Revision UINT 0001h Revision 1
2 Get Max Instance UINT 0001h 1 is the highest instance number
3 Get No. of instances UINT 0001h 1 instance is implemented

Instance attributes

# Access Name Type Value Comments


1 Get Interface Speed UDINT 10 or 100 Actual Ethernet interface
speed
2 Get Interface Flags DWORD
3 Get Physical Address Array of 6 USINTS (MAC ID) Physical network address

Device Profile 27
Reference Manual Device Profile
00809-0100-4765, Rev. AB April 2016

B.2.7 Diagnostic Object, Class AAh


This object groups diagnostic information for the fieldbus interface.

Supported services
Class services:
 Get Attribute All

Instance services:
 Get Attribute Single

Class attributes

# Access Name Type Value Description


1 Get Revision UINT 0001h Revision 1

Instance attributes

# Access Name Type Description


01h Get Module serial number UDINT Serial number
02h Get Vendor ID UINT Manufacturer Vendor ID
03h Get Fieldbus Type UINT Fieldbus Type
04h Get Module Software version UINT Module software version
0Ah Get Module Type UINT Module Type
0Fh Get IN cyclic I/O length UINT Size of I/O Input area (in bytes)
11h Get IN total length UINT Total number of IN bytes supported
12h Get OUT cyclic I/O length UINT Size of I/O Output area (in bytes)
14h Get OUT total length UINT Total number of OUT bytes supported

B.2.8 Parameter Data Input Mapping Object, Class B0h


This object can be used to access Input Data acyclically, and is set up dynamically based on
the Parameter Data Mailbox initialization (see Section B.3.3).

Supported services
Class services:
 Get Attribute All

Instance services:
 Get Attribute Single

28 Device Profile
Device Profile Reference Manual
April 2016 00809-0100-4765, Rev. AB

Class attributes

# Access Name Type Value Description


1 Get Revision UINT 0001h Revision 1

Instance attributes, Instance 01h


Each attribute corresponds to a block of Input Data.

# Access Name Type Description


01h Get Data Array of USINT Mapped block of Input Data
02h Get Data Array of USINT Mapped block of Input Data
...
32h Get Data Array of USINT Mapped block of Input Data

The specific parameters in the block depend on the configuration in use.

Configuration Input parameters (explicit data)


Basic See Section B.3.3

B.2.9 Parameter Data Output Mapping Object, Class B1h


This object can be used to access Output Data acyclically, and is set up dynamically (see
Section B.3.4).

Supported services
Class services:
 Get Attribute All

Instance services:
 Get Attribute Single
 Set Attribute Single

Class attributes

# Access Name Type Value Description


1 Get Revision UINT 0001h Revision 1

Device Profile 29
Reference Manual Device Profile
00809-0100-4765, Rev. AB April 2016

Instance attributes, Instance 01h

# Access Name Type Description


01h Get/Set Data Array of USINT Mapped block of Output Data
02h Get/Set Data Array of USINT Mapped block of Output Data
...
32h Get/Set Data Array of USINT Mapped block of Output Data

The specific parameters in the block depend on the configuration in use.

Configuration Output parameters (explicit data)


Basic See Section B.3.4

30 Device Profile
Device Profile Reference Manual
April 2016 00809-0100-4765, Rev. AB

B.3 I/O data


B.3.1 Input assembly
Bytes Access Name Type Notes
0-3 Get Flow Rate Float
4–7 Get Total A Float 0–235
8–11 Get Total B Float 0–235
12–15 Get Total C Float 0–235
16-19 Get Electronics Temperature Float
20-23 Get Line Noise Float
24-27 Get 5 Hz SNR Float
28-31 Get 37 Hz SNR Float
32-35 Get Signal Power Float
36-39 Get Empty Pipe Value Float
40-43 Get Electrode Coating Value Float
44-47 Get Internal Flow Simulator Test Deviation (Continuous) Float
48-51 Get Electrode Resistance Value (Continuous) Float
52-55 Get Coil Resistance Value (Continuous) Float
56-59 Get Coil Inductance Value (Continuous) Float
60-63 Get Coil Inductance Deviation (Continuous) Float
64-67 Get Pulse Output Float 0-11000
68-71 Get Internal Flow Simulator Value (SMART™ Meter Verifica- Float
tion) (Do not use)
72-75 Get Coil Current Float
76-77 Get Status Register0 U16 Table B-37
78-79 Get Status Register1 U16 Table B-38
80-81 Get Status Register2 U16 Table B-39
82-83 Get Status Register3 U16

B.3.2 Output assembly


Bytes Access Name Type Notes
0 Get/Set Start/Stop All Totals Byte 0: Stop
1: Start
1 Get/Set Reset All Totals Byte 0: No Action
1: Reset
2 Get/Set Reset Total A Byte 0: No Action
1: Reset
3 Get/Set Reset Total B Byte 0: No Action
1: Reset
4 Get/Set Reset Total C Byte 0: No Action
1: Reset

Device Profile 31
Reference Manual Device Profile
00809-0100-4765, Rev. AB April 2016

B.3.3 Input parameters—explicit data


To update any of these attribute values, the associated trigger byte must be toggled before
reading the attribute value (executing the Get service). See Section B.3.4 for more
information on trigger bytes.

For all input parameters in Table B-2, the class is B0h and the instance is 01h.

Table B-2. Input Parameters—Explicit Data

Trigger
Attribute Access Name Type byte write Description
attribute
01h Get Software Revision U16 110h
02h Get Internal Flow Simulator Test Deviation (Contin- U8 111h 57: %
uous) UOM
Get Coil Inductance Deviation (Continuous) UOM U8 57: %
Get Coil Inductance Value (Continuous) UOM U8 245: mH
Get Coil Resistance Value (Continuous) UOM U8 37: Ohms
Get Electrode Resistance Value (Continuous) UOM U8 163: kOhms
Get Electrode Coating Value UOM U8 163: kOhms
Get Empty Pipe Value UOM U8 251: None
Get Electronics Temperature UOM U8 32: Degrees C
33: Degrees F

Get Density Unit U8 92: kgs/m^3


94: lbs/ft^3

Get Meter Verification Result U8 Table B-10


Get Sensor Calibration Test Result U8 Table B-10
Get Coil Circuit Test Result U8 Table B-10
Get Electrode Circuit Test Result U8 Table B-10
Get Calibration Test Result U8 Table B-10
Get Test Limit U8 1-10
0: Equivalent to not run

Get Test Condition U8 Table B-11


Get Pulse Scaling UOM U8 0.0001 - 3,401,574.912

32 Device Profile
Device Profile Reference Manual
April 2016 00809-0100-4765, Rev. AB

Table B-2. Input Parameters—Explicit Data (continued)

Trigger
Attribute Access Name Type byte write Description
attribute
03h Get Flow Rate UOM U8 112h Table B-12
Get/Set Total A UOM U8 Table B-13
Get/Set Total B UOM U8 Table B-13
Get/Set Total C UOM U8 Table B-13
Get/Set Line Size U8 Table B-14
Get Electrode Material U8 Table B-15
Get Electrode Type U8 Table B-16
Get/Set Transmitter Tag A8 8 Packed ASCII
Characters
Get Flange Material U8 Table B-17
Get Flange Type U8 Table B-18
Get Liner Material U8 Table B-19
Get Base Time Unit U8 Table B-20
Get Base Volume Unit U8 Table B-13
Get Coil Drive Frequency U8 0: 5Hz
1: 37.5Hz

Get Digital Signal Processing Control U8 0: Off


1: On

Get Operating Mode U16 0: Normal


1: Filter

Get Samples U8 1 - 125


Get Flow Display U8 0: Flow, TotalizerA
1: Flow, TotalizerB
2: Flow, TotalizerC

Device Profile 33
Reference Manual Device Profile
00809-0100-4765, Rev. AB April 2016

Table B-2. Input Parameters—Explicit Data (continued)

Trigger
Attribute Access Name Type byte write Description
attribute
04h Get Language U8 113h Table B-23
Get Display Lock U8 0: Off
1: On

Get Pulse Mode U8 0: Pulse Output


1: Frequency Output

Get/Set Counts U8 2-50


Get Empty Pipe Limit U8 1-10
Lowpower: 3-10

Get Flowing Limit U8 1-10


Lowpower: 3-10

Get No Flow Limit U8 1-10


Lowpower: 3-10

Get Continuous Limit U8 2-10


Lowpower: 3-10

Get Discreet I/O direction control U8 1: Input


2: Output
251: Not Available

Get DI/DO Input Mode U8 Table B-24


Get DI/DO Output Mode1 U8 Table B-25

34 Device Profile
Device Profile Reference Manual
April 2016 00809-0100-4765, Rev. AB

Table B-2. Input Parameters—Explicit Data (continued)

Trigger
Attribute Access Name Type byte write Description
attribute
05h Get DI/DO Output Mode2 U8 114h Table B-25
Get Status Mode 1 U8 Table B-26
Get Status Mode 2 U8 Table B-26
Get Limit Mode (Totalizer A Limit) U8 Table B-26
Get/Set Reset Option (Totalizer A) U8 0: Not Allowed
1: Allowed

Get/Set Direction (Totalizer A) U8 0: Net


1: Forward
2: Reverse

Get/Set Reset Option (Totalizer B) U8 0: Not Allowed


1: Allowed

Get/Set Direction (Totalizer B) U8 0: Net


1: Forward
2: Reverse

Get/Set Reset Option (Totalizer C) U8 0: Not Allowed


1: Allowed

Get/Set Direction (Totalizer C) U8 0: Net


1: Forward
2: Reverse

Get Select sensor components to baseline U8 Table B-27


Get Select system components to verify U8 Table B-28
Get Select test condition of the process test U8 Table B-11
condition
Get/Set Address U8 1-247
Get/Set Float Point Order U8 Table B-29
Get/Set Minimum Response Delay U8 0-250
06h Get Baud Rate U8 115h Table B-30
Get Parity U8 0: No parity
1: Odd
2: Even

Get Stop Bits U8 1: 1 stop bit


2: 2 stop bits

07h Get Auto Lock U8 116h 0: Off


1: 1 Minute
2: 10 Minute

Get Transmitter Model U8 60: 8732E Modbus


Get Manufacturer U8 38: Rosemount Flow
Get Backlight U8 Table B-31

Device Profile 35
Reference Manual Device Profile
00809-0100-4765, Rev. AB April 2016

Table B-2. Input Parameters—Explicit Data (continued)

Trigger
Attribute Access Name Type byte write Description
attribute
08h Get Device ID U32 117h 0X000000 - 0XFFFFFF
Get Sensor Serial Number U32 0- 9,999,999
1: Demo Mode

Get Final Assembly Number U32 0X000000 - 0XFFFFFF


Get/Set License Key U32
09h Get Lower Sensor Limit F32 118h -39.37 ft/s
Get Upper Sensor Limit F32 39.37 ft/s
Get Primary Variable Minimum Span (Do not use) F32
Get Simulated Velocity F32
Get Actual Velocity F32
Get Transmitter Deviation F32
Get Sensor Deviation F32
Get Measured Coil Inductance F32
Get Measured Coil Resistance F32
Get Measured Electrode Resistance F32
0Ah Get Coil Inductance Baseline F32 119h 0.5 - 20,000
Get Coil Resistance Baseline F32 0.5 - 1000.0
Get Electrode Resistance Baseline F32 0.1 - 5,000,000

36 Device Profile
Device Profile Reference Manual
April 2016 00809-0100-4765, Rev. AB

Table B-2. Input Parameters—Explicit Data (continued)

Trigger
Attribute Access Name Type byte write Description
attribute
0Bh Get/Set Flow Damping; Damping F32 11Ah 0–256.0
Get/Set Conversion Number F32 0–9,999,999
Get/Set Low Flow Cutoff F32 0.01–38.37
Get/Set Pulse Scaling F32 0.0001–
3,401,574.912-ft
Get/Set Pulse Width F32 .1 – 650.0
Get/Set Enter Flow Rate F32 0.0 ft/s
1.0 - 39.37008 ft/s

Get/Set Density Value F32 0.01–900 lbs/ft3


Get/Set Trigger Level F32 3–2000
Get/Set High Limit 1 F32
Get/Set Low Limit 1 F32
Get/Set High Limit 2 F32
Get/Set Low Limit 2 F32
Get/Set Flow Hysteresis F32
Get/Set Hight Limit (Totalizer Limit) F32 -1,999,999,999 –
1,999,999,999 feet

Get/Set Low Limit (Totalizer Limit) F32 -1,999,999,999 –


1,999,999,999 feet

Get/Set Totalizer Hysteresis F32 0–1,999,999,999 feet


Get/Set Coating Level Limit 1 F32 0.0–100,000
Get/Set Coating Level Limit 2 F32 0.0–100,000
0Ch Get/Set Fixed pulse output value F32 11Bh 0: Off
1–11000Hz

Get/Set Signal processing Percent of Rate F32 0–100.0


Get/Set Signal processing Time Limit F32 0.6–256.0
0Dh Get/Set Special Flow Rate Unit A4 11Ch 4 Packed ASCII
Characters
Get/Set Special Volume Unit A4 4 Packed ASCII
Characters
Get/Set Calibration Number A16 Table B-32
0Eh Get Message A32 11Dh 32 Packed ASCII
Characters
Get Sensor Tag; Sensor Tag A8 8 Packed ASCII
Characters
Get Descriptor A16 16 Packed ASCII
Characters

Device Profile 37
Reference Manual Device Profile
00809-0100-4765, Rev. AB April 2016

Table B-2. Input Parameters—Explicit Data (continued)

Trigger
Attribute Access Name Type byte write Description
attribute
0Fh Get Write Protect U8 11Eh Bit0: Write Protect
Get Update In Progress(Do not use) U8
Get Process Noise U8 Table B-33
Get Line Noise U8 Table B-33
Get Discrete I/O U8 Table B-33
Get Meter Verification U8 Table B-33
Get Electrode Coating U8 Table B-33

38 Device Profile
Device Profile Reference Manual
April 2016 00809-0100-4765, Rev. AB

Table B-2. Input Parameters—Explicit Data (continued)

Trigger
Attribute Access Name Type byte write Description
attribute
10h Get/Set Reset All U8 11Fh 0: Cancel
1: Reset

Get/Set Reset Total A U8 0: Cancel


1: Reset

Get/Set Reset Total B U8 0: Cancel


1: Reset

Get/Set Reset Total C U8 0: Cancel


1: Reset

Get/Set Status Alert (Totalizer A Limit) U8 0: Off


1: On

Get/Set Self Test U8 0: Uninitialized/No test


1: Self test activate

Get/Set Start Digital Trim U8 0: Inactive


1: Start/active

Get/Set Perform Auto Zero U8 0: Inactive


1: Start/active

Get/Set Start Universal Trim U8 0: Inactive


1: Start/active

Get/Set Start Meter Verification U8 0: Inactive


1: Start/active

Get/Set Re-Baseline Sensor U8 0: Inactive


1: Start/active

Get/Set Recall Last Baseline U8 0: Inactive


1: Recall/active

Get/Set Reset Maximum Coating Resistance Value U8 0: Inactive


1: Start/active

Get/Set Perform Master Reset U8 0: Inactive


1: Recall/active

Get/Set Empty Pipe Detection U8 Table B-34


Get/Set High Process Noise Detection U8 Table B-34
Get/Set Grounding / Wiring Fault Detection U8 Table B-34
Get/Set Electronics Temperature Range Detection U8 Table B-34
Get/Set Electrode Coating Detection U8 Table B-34
Get/Set Coils (Continuous Meter Verification) U8 Table B-33

Get/Set Electrodes (Continuous Meter Verification) U8 Table B-33

Get/Set Transmitter (Continuous Meter Verification) U8 Table B-33

Device Profile 39
Reference Manual Device Profile
00809-0100-4765, Rev. AB April 2016

Table B-2. Input Parameters—Explicit Data (continued)

Trigger
Attribute Access Name Type byte write Description
attribute
11h Get Electronics Failure U8 120h Table B-36
Get Coil Open Circuit U8 Table B-36
Get Empty Pipe U8 Table B-36
Get Reverse Flow U8 Table B-36
Get Grounding / Wiring Fault U8 Table B-36
Get High Process Noise U8 Table B-36
Get Electronics Temperature Out of Range U8 Table B-36
Get Electrode Coating Limit 1 U8 Table B-36
Get Electrode Coating Limit 2 U8 Table B-36
Get Continuous Meter Verification U8 Table B-36
Get Coil Overcurrent Detected U8 Table B-36
Get Sensor Electrode Saturated U8 Table B-36
Get Coil Power Limit Exceeded U8 Table B-36
Get Write Protect Start/Stop U8 0: Disable
1: Enable

Get Write Protect Reset U8 0: Disable


1: Enable

Get Start/Stop from the LOI U8 0: Not Allowed


1: Allowed

Get Reset from the LOI U8 0: Not Allowed


1: Allowed

12h Get/Set Status Alert 1 U8 121h 0: Off


1: On

Get/Set Status Alert 2 U8 0: Off


1: On

Get/Set Reverse Flow Mode U8 0: Disable


1: Enable

40 Device Profile
Device Profile Reference Manual
April 2016 00809-0100-4765, Rev. AB

B.3.4 Output parameters—explicit data


For all output parameters in the following table, the class is B1h and the instance is 01h.

Table B-3. Output Parameters—Explicit Data

Attribute Access Name Type Description


01h Get/Set Language U8 Table B-23
Get/Set Display Lock U8 0: Off
1: On

Get/Set Pulse Mode U8 0: Pulse Output


1: Frequency Output

Get/Set Counts U8 2-50


Get/Set Empty Pipe Limit U8 1-10
Lowpower: 3-10

Get/Set Flowing Limit U8 1-10


Lowpower: 3-10

Get/Set No Flow Limit U8 1-10


Lowpower: 3-10

Get/Set Continuous Limit U8 2-10


Lowpower: 3-10

Device Profile 41
Reference Manual Device Profile
00809-0100-4765, Rev. AB April 2016

Table B-3. Output Parameters—Explicit Data (continued)

Attribute Access Name Type Description


02h Get/Set Status Mode 1 U8 Table B-26
Get/Set Status Mode 2 U8 Table B-26
Get/Set Limit Mode (Totalizer A Limit) U8 Table B-26
Get/Set Reset Option (Totalizer A) U8 0: Not Allowed
1: Allowed

Get/Set Direction (Totalizer A) U8 0: Net


1: Forward
2: Reverse

Get/Set Reset Option (Totalizer B) U8 0: Not Allowed


1: Allowed

Get/Set Direction (Totalizer B) U8 0: Net


1: Forward
2: Reverse

Get/Set Reset Option (Totalizer C) U8 0: Not Allowed


1: Allowed

Get/Set Direction (Totalizer C) U8 0: Net


1: Forward
2: Reverse

Get/Set Select sensor components to baseline U8 Table B-27


Get/Set Select system components to verify U8 Table B-28
Get/Set Select test condition of the process test U8 Table B-11
condition

Get/Set Address U8 1-247


Get/Set Float Point Order U8 Table B-29
Get/Set Minimum Response Delay U8 0-250
03h Get/Set License Key U32

42 Device Profile
Device Profile Reference Manual
April 2016 00809-0100-4765, Rev. AB

Table B-3. Output Parameters—Explicit Data (continued)

Attribute Access Name Type Description


04h Get/Set Flow Damping; Damping F32 0 - 256.0
Get/Set Conversion Number F32 0-9,999,999
Get/Set Low Flow Cutoff F32 0.01–38.37
Get/Set Pulse Scaling F32 0.0001–3,401,574.912-ft
Get/Set Pulse Width F32 .1–650.0
Get/Set Enter Flow Rate F32 0.0 ft/s
1.0–39.37008 ft/s

Get/Set Density Value F32 0.01–900 lbs/ft3


Get/Set Trigger Level F32 3–2000
Get/Set High Limit 1 F32
Get/Set Low Limit 1 F32
Get/Set High Limit 2 F32
Get/Set Low Limit 2 F32
Get/Set Flow Hysteresis F32
Get/Set Hight Limit (Totalizer Limit) F32 -1,999,999,999–
1,999,999,999 feet
Get/Set Low Limit (Totalizer Limit) F32 -1,999,999,999–
1,999,999,999 feet
Get/Set Totalizer Hysteresis F32 0–1,999,999,999 feet
Get/Set Coating Level Limit 1 F32 0.0–100,000
Get/Set Coating Level Limit 2 F32 0.0–100,000
05h Get/Set Fixed pulse output value F32 0: Off
1–11000Hz

Get/Set Signal processing Percent of Rate F32 0–100.0


Get/Set Signal processing Time Limit F32 0.6–256.0
06h Get/Set Special Flow Rate Unit A4 4 Packed ASCII Characters
Get/Set Special Volume Unit A4 4 Packed ASCII Characters
Get/Set Calibration Number A16 Table B-32
07h Get/Set Reverse Flow Mode U8 0: Disable
1: Enable

08h Set Start All (1), Stop All (0) U8


09h Get/Set Reset All U8 0: Cancel
1: Reset

0Ah Get/Set Reset Total A U8 0: Cancel


1: Reset

0Bh Get/Set Reset Total B U8 0: Cancel


1: Reset

0Ch Get/Set Reset Total C U8 0: Cancel


1: Reset

Device Profile 43
Reference Manual Device Profile
00809-0100-4765, Rev. AB April 2016

Table B-3. Output Parameters—Explicit Data (continued)

Attribute Access Name Type Description


0Dh Get/Set Self Test U8 0: Uninitialized/No test
1: Self test activate

0Eh Get/Set Perform Auto Zero U8 0: Inactive


1: Start/active

0Fh Get/Set Start Meter Verification U8 0: Inactive


1: Start/active

10h Get/Set Re-Baseline Sensor U8 0: Inactive


1: Start/active

11h Get/Set Recall Last Baseline U8 0: Inactive


1: Recall/active

12h Get/Set Perform Master Reset U8 0: Inactive


1: Recall/active

13h Get/Set Empty Pipe Detection U8 Table B-34


14h Get/Set High Process Noise Detection U8 Table B-34
15h Get/Set Grounding / Wiring Fault Detection U8 Table B-34
16h Get/Set Electronics Temperature Range Detection U8 Table B-34
17h Get/Set Electrode Coating Detection U8 Table B-34
18h Get/Set Coils (Continuous Meter Verification) U8 Table B-35
19h Get/Set Electrodes (Continuous Meter Verification) U8 Table B-35
1Ah Get/Set Transmitter (Continuous Meter Verification) U8 Table B-35
1Bh Get/Set Status Alert 1 U8 0: Off
1: On

1Ch Get/Set Status Alert 2 U8 0: Off


1: On

1Dh Get/Set Status Alert (Totalizer A Limit) U8 0: Off


1: On

1Eh Set Trriger Byte -1 U8


1Fh Set Trriger Byte -2 U8
20h Set Trriger Byte -3 U8
21h Set Trriger Byte -4 U8
22h Set Trriger Byte -5 U8
23h Set Trriger Byte -6 U8
24h Set Trriger Byte -7 U8
25h Set Trriger Byte -8 U8
26h Set Trriger Byte -9 U8
27h Set Trriger Byte -10 U8
28h Set Trriger Byte -11 U8
29h Set Trriger Byte -12 U8
2Ah Set Trriger Byte -13 U8

44 Device Profile
Device Profile Reference Manual
April 2016 00809-0100-4765, Rev. AB

Table B-3. Output Parameters—Explicit Data (continued)

Attribute Access Name Type Description


2Bh Set Trriger Byte -14 U8
2Ch Set Trriger Byte -15 U8
2Dh Set Trriger Byte -16 U8
2Eh Set Trriger Byte -17 U8
2Fh Set Trriger Byte -18 U8
30h Get Flow Rate UOM U8 Table B-12
31h Get/Set Total A UOM U8 Table B-13
Get/Set Total B UOM U8 Table B-13
Get/Set Total C UOM U8 Table B-13
Get/Set Line Size U8 Table B-14
Get Electrode Material U8 Table B-15
Get Electrode Type U8 Table B-16
Get/Set Transmitter Tag A8 8 Packed ASCII Characters
Get Flange Material U8 Table B-17
Get Flange Type U8 Table B-18
Get Liner Material U8 Table B-19
Get Base Time Unit U8 Table B-20
Get Base Volume Unit U8 Table B-13
Get Coil Drive Frequency U8 0: 5Hz
1: 37.5Hz

Get Digital Signal Processing Control U8 0: Off


1: On

Get Operating Mode U16 0: Normal


1: Filter

Get Samples U8 1 - 125


Get Flow Display U8 0: Flow, TotalizerA
1: Flow, TotalizerB
2: Flow, TotalizerC

Device Profile 45
Reference Manual Device Profile
00809-0100-4765, Rev. AB April 2016

B.4 Get and Set services


The Get Attribute Single and Set Attribute Single services are used with many objects and
attributes. Details of these two services are provided here.

B.4.1 Get Attribute Single service


Table B-4. Get Service Arguments

Parameter name Data type Required Parameter value Notes


Attribute ID USINT Y The attribute ID of the No default
attribute to be read

B.4.2 Set Attribute Single service


Table B-5. Get Service Response

Return value Data type


Attribute value The data type of the returned attribute

Table B-6. Set Service Arguments

Parameter name Data type Required Parameter value Notes


Attribute ID USINT Y The attribute ID of the No default
attribute to be set
Attribute Value The data type of the Y The value to which the No default
attribute being set attribute will be set

Table B-7. Set Service Response

Return value Data type


No success response data

46 Device Profile
Device Profile Reference Manual
April 2016 00809-0100-4765, Rev. AB

B.5 Data types


Table B-8. Data Types

Data type Size (bytes) Description Range


BOOL 1 True/false represented as 0 = false and 1 = 0, 1
true
SINT 1 8-bit signed integer –128 to +127
USINT 1 8-bit unsigned integer 0 to 255
INT 2 16-bit signed integer –32768 to +32767
UINT 2 16-bit unsigned integer 0 to 65535
DINT 4 32-bit signed integer –2147483648 to +2147483647
UDINT 4 32-bit unsigned integer 0 to 4294967296
REAL 4 IEEE single-precision floating-point –3.8E38 to +3.8E38
DREAL 8 IEEE double-precision floating-point
ENGUNITS 1 Enumerated value representing an engi- 4096 to 65535
neering unit of measure
BYTE 1 8-bit bitfield N/A
SHORT_STRING Up to 128 bytes Character array where the first byte is the N/A
number of characters in the array, and the
subsequent bytes contain the ASCII charac-
ters. This is not a NULL terminated string.

B.6 Codes and integer values


Table B-9. Slot 0 Transmitter Variable Index

Code Description
0 Flow Rate
1 Pulse Output Frequency
2 Totalizer A
3 Totalizer B
4 Totalizer C
5 Electronics Temperature
6 Line Noise
7 5Hz SNR
8 37Hz SNR
9 Signal Power
10 Empty Pipe Value
11 Internal Flow Simulator Test Deviation (Continuous)
12 Electrode Coating Value
13 Electrode Resistance Value (Continuous)

Device Profile 47
Reference Manual Device Profile
00809-0100-4765, Rev. AB April 2016

Table B-9. Slot 0 Transmitter Variable Index (continued)

Code Description
14 Coil Resistance Value (Continuous)
15 Coil Inductance Value (Continuous)
16 Coil Inductance Deviation (Continuous)

Table B-10. Meter verification results

Code Description
0 Not Run
1 Pass
2 Fail
3 Not Licensed

Table B-11. Test condition

Code Description
0 Not Run
1 No Flow, Full Pipe
2 Flow, Full Pipe
3 Empty Pipe
255 Not Initialized

Table B-12. Flow Rate Units

Code Description
15 cubic feet/min
16 gal/min
17 liter/min
18 imp gal/min
19 cubic meter/hour
20 ft/s
21 meter/sec
22 gal/sec
24 liter/sec
26 cubic feet/sec
27 cubic feet/day
28 cubic meter/sec
29 cubic meter/day
30 imp gal/hour
31 imp gal/day
73 kg/sec

48 Device Profile
Device Profile Reference Manual
April 2016 00809-0100-4765, Rev. AB

Table B-12. Flow Rate Units (continued)

Code Description
74 kg/min
75 kg/hr
76 kg/day
77 metric ton/min
78 metic ton/hr
79 metric ton/day
80 lbs/sec
81 lbs/min
82 lbs/hr
83 lbs/day
84 short tons/min
85 short tons/hour
86 short tons/day
130 cubic feet/hr
131 cubic meter/min
132 barrel(42 gals)/sec
133 barrel(42 gals)/min
134 barrel(42 gals)/hr
135 barrel(42 gals)/day
136 gals/hr
137 imp gals/sec
138 liters/hr
235 gals/day
240 liters/day
241 barrels(31.gals)/sec
242 barrels(31.gals)/min
243 barrels(31.gals)/hr
244 barrels(31.gals)/day
248 cubic cm/min
253 Special

Table B-13. Totalizer Units

Code Description
40 gals
41 liters
42 imp gals
43 cubic meters

Device Profile 49
Reference Manual Device Profile
00809-0100-4765, Rev. AB April 2016

Table B-13. Totalizer Units (continued)

Code Description
44 feet
45 meters
46 barrels(42 gals)
61 kilograms
62 metric tons
63 pounds
64 short tons
112 cubic feet
246 cubic cm
247 barrels(31 gals)
253 special

Table B-14. Line/Tube Size

Code Description
0 0.1-in
1 0.15-in
2 0.25-in
3 0.3-in
4 0.5-in
5 0.75-in
6 1.0-in
7 1.5-in
8 2.0-in
9 2.5-in
10 3.0-in
11 4.0-in
12 5.0-in
13 6.0-in
14 8.0-in
15 10.0-in
16 12.0-in
17 14.0-in
18 16.0-in
19 18.0-in
20 20.0-in
21 24.0-in
22 28.0-in

50 Device Profile
Device Profile Reference Manual
April 2016 00809-0100-4765, Rev. AB

Table B-14. Line/Tube Size (continued)

Code Description
23 30.0-in
24 32.0-in
25 36.0-in
26 40.0-in
27 42.0-in
28 44.0-in
29 48.0-in
30 54.0-in
31 56.0-in
32 60.0-in
33 64.0-in
34 66.0-in
35 72.0-in
36 78.0-in
37 80.0-in

Table B-15. Electrode Material

Code Description
2 316L SST
3 Nickel Alloy 276
5 Tantalum
6 Titanium
7 Platinum-Iridium
8 Alloy 20 (8732E only)
17 Ryton (8732E only)
252 Other
253 Unknown

Table B-16. Electrode Type

Code Description
0 Standard
1 Ultrasonic (8732E only)
2 Bullet
3 Standard and Ground
4 Replaceable
5 High Pressure
252 Other

Device Profile 51
Reference Manual Device Profile
00809-0100-4765, Rev. AB April 2016

Table B-16. Electrode Type

Code Description
253 Unknown

Table B-17. Flange Material

Code Description
0 Carbon Steel
1 304 SST
2 Wafer
3 316L SST
252 Other
253 Unknown

Table B-18. Flange Type

Code Description
0 ANSI 150
1 ANSI 300
2 ANSI 600
3 PN 10
4 PN 16
5 PN 40
6 Wafer
7 ANSI 900
8 PN 25
9 PN 64
10 ANSI 1500
11 ANSI 2500
252 Other
253 Unknown

Table B-19. Liner Material

Code Description
10 PTFE
14 Polyurethane
16 ETFE
17 RYTON
19 Neoprene
20 Natural Rubber
252 Other

52 Device Profile
Device Profile Reference Manual
April 2016 00809-0100-4765, Rev. AB

Table B-19. Liner Material

Code Description
253 Unknown

Table B-20. Base Time Unit

Code Description
50 min
51 sec
52 hour
53 day

Table B-21. Fixed Output Codes for SMART Meter Verification

Value Description
0 Last measured value
1 Fault value

Table B-22. Enable SMART Meter Verification

Code Description
1 Enable with fixed output (see Table B-21)
5 Abort
6 Enable with continuous measurement

Table B-23. Language

Code Description
0 English
1 Spanish
2 German
3 French
4 Portuguese

Table B-24. DI/DO Input Mode

Code Description
0 PZR
1 Totalizer A Reset
2 Totalizer B Reset
3 Totalizer C Reset
4 Reset All Totalizers
251 Not Available

Device Profile 53
Reference Manual Device Profile
00809-0100-4765, Rev. AB April 2016

Table B-25. DI/DO Output Mode1&2

Code Description
0 Reverse Flow
1 Zero Flow
2 Transmitter Fault(Alarm)
3 Empty pipe
4 Flow limit1
5 Flow limit2
6 Diagnostic Status Alert
7 Totalizer Limit 1
251 Not Available

Table B-26. Status/Flow Limit Mode

Code Description
0 > High limit
1 < Low limit
2 In Range
3 Out of Range

Table B-27. Select Sensor Components to Baseline

Code Description
0 All
1 Coils
2 Electrodes
255 Not Initialized

Table B-28. Select System Components to Verify

Code Description
0 All
1 Flow tube
2 Transmitter
255 Not Initialized

Table B-29. Float Point Order

Code Description
0 0-1-2-3
1 2-3-0-1
2 1-0-3-2
3 3-2-1-0

54 Device Profile
Device Profile Reference Manual
April 2016 00809-0100-4765, Rev. AB

Table B-30. Baud Rate

Code Description
0 1200
1 2400
2 4800
3 9600
4 19200
5 38400
6 57600
7 115200

Table B-31. Backlight

Code Description
0 Off
1 10 Seconds
2 20 Seconds
3 30 Seconds
4 On

Table B-32. Calibration Number-"AAAAABCCDDDDDEFG"

Code Description
AAAAA 01500-19999
B 0, 1, 2, 3, 4, 5 (XMTR_MODE = 0)
B 1, 5, 6 (XMTR_MODE = 1)
CC 00- 99
DDDDD 01500-19999
E 0 -9
F 0-9 (0-3 if B=5)
G 0-9 (0-3 if B=5)

Table B-33. License Status

Code Description
Byte0:7 Reserved 0
6 Reserved 0
5 Reserved 0
4 Electrode Coating
3 8714i Verification
2 Digital I/O
1 Gnd /Wiring Fault Det

Device Profile 55
Reference Manual Device Profile
00809-0100-4765, Rev. AB April 2016

Table B-33. License Status (continued)

Code Description
0 Hi process noise Det
Byte1:7 Reserved 0
6 Reserved
5 Reserved
4 Reserved
3 Reserved
2 Reserved
1 Reserved
0 Reserved

Table B-34. Diagnostic Handling

Code Description
Bit:0 Empty Pipe
1 High Process Noise
2 Grounding/Wiring
3 Electrode Temp
4 Electrode Coating
5 Reserved, Always 0
6 Reserved, Always 0
7 Reserved, Always 0
8 Reserved, Always 0
9 Reserved, Always 0
10 Reserved, Always 0
11 Reserved, Always 0
12 Reserved, Always 0
13 Reserved, Always 0
14 Reserved, Always 0
15 Reserved, Always 0

Table B-35. Continuous Meter Verification Enabling

Code Description
Bit:0 Coils
1 Electrodes
2 Transmitter
3 Reserved , Always 0
4 Reserved , Always 0
5 Reserved , Always 0

56 Device Profile
Device Profile Reference Manual
April 2016 00809-0100-4765, Rev. AB

Table B-35. Continuous Meter Verification Enabling

Code Description
6 Reserved , Always 0
7 Reserved , Always 0
8 Reserved , Always 0
9 Reserved , Always 0
10 Reserved , Always 0
11 Reserved , Always 0
12 Reserved , Always 0
13 Reserved , Always 0
14 Reserved , Always 0
15 Reserved , Always 0

Table B-36. Diagnostic Status Alert

Code Description
Bit:0 Electronic Failure
1 Coil Open Circuit
2 Empty pipe
3 Reverse Flow
4 Ground/ Wiring Fault
5 High Process Noise
6 Elect Temp Out of Range
7 Electrode Coating Limit 1
8 Electrode Coating Limit 2
9 Reserved, Always 0
10 Reserved, Always 0
11 Reserved, Always 0
12 Continuous Meter verification
13 Coil Over Current
14 Sensor Electode Saturation
15 Coil Power Limit
16 Reserved, Always 0
17 Reserved, Always 0
18 Reserved, Always 0
19 Reserved, Always 0
20 Reserved, Always 0
21 Reserved, Always 0
22 Reserved, Always 0
23 Reserved, Always 0

Device Profile 57
Reference Manual Device Profile
00809-0100-4765, Rev. AB April 2016

Table B-36. Diagnostic Status Alert (continued)

Code Description
24 Reserved, Always 0
25 Reserved, Always 0
26 Reserved, Always 0
27 Reserved, Always 0
28 Reserved, Always 0
29 Reserved, Always 0
30 Reserved, Always 0
31 Reserved, Always 0

Table B-37. Status Register 0

Code Description
Bit:0 Sensor Out of Range
1 Empty pipe condition detected
2 I/O Processor failure
3 Pulse output out of range
4 Update missed
5 Output at alarm level
6 Modbus non-volatile memory error
7 Pulse output fixed
8 EPROM checksum error
9 NOVRAM checksum error
10 RAM checksum error
11 Factory NOVRAM checksum error
12 Continuous meter verification error
13 PZR output is active
14 Coil drive current is zero
15 Reverse Flow detected

Table B-38. Status Register 1

Code Description
Bit:0 Internal Flow Simulation Error
1 Excess Auto Zero Correction, ZR too Low
2 Excess Auto Zero Correction, ZR too High
3 Auto Zero attempt with Nonzero flow
4 Totalizer Limit Alert 1
5 Universal Trim Failure
6 Flow Limit Alert 1

58 Device Profile
Device Profile Reference Manual
April 2016 00809-0100-4765, Rev. AB

Table B-38. Status Register 1 (continued)

Code Description
7 Flow Limit Alert 2
8 Electrode Coated Limit 1
9 Electrode Coated Limit 2
10 Excess Calibration Correction. GN too Low
11 Excess Calibration Correction. GN too High
12 Calibration Attempt Without Calibrator
13 Grounding/Wiring Fault
14 High Process Noise Detected
15 Electronics Temperature Out of Range

Table B-39. Status Register 2

Code Description
Bit:0 Digital I/O 1 Active
1 Digital Output 2 Active
2 Diagnostic Status Alert Active
3 Modbus in Listen Only mode
4 I/O Processor Comm Failure
5 Coil Over Current Detected
6 Sensor Electrode Saturated
7 Coil Power Limit
8 Electronics Failure
9 Coil Resistance Error
10 Coil Inductance Error
11 Digital Trim Failure
12 Reverse Flow Detected
13 Electrode Resistance Error
14 Auto Zero Failure
15 Reserved for Status bit

Device Profile 59
Reference Manual Device Profile
00809-0100-4765, Rev. AB April 2016

60 Device Profile
Specifications Reference Manual
April 2016 00809-0100-4765, Rev. AB

Appendix C Specifications

Physical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 61
Electrical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 61
Environmental . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 61
Regulatory compliance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 62

C.1 Physical
C.1.1 Housing
Plastic housing with snap-on connection to DIN rail

Protection class: IP20

C.1.2 Dimensions
4.72-in. × 2.95-in. × 1.06-in. (120 mm x 75 mm x 27 mm) L×W×H

C.2 Electrical
C.2.1 Power supply
24 V ±20%

C.2.2 Power consumption


Maximum: 300 mA on 24 V

Typical: 100 mA

C.3 Environmental
C.3.1 Relative humidity
5 to 95% non-condensing

C.3.2 Temperature
Operating: 32 °F to 131 °F (0 °C to 55 °C)

Ambient: –13 °F to +185 °F (–25 °C to +85 °C)

Specifications 61
Reference Manual Specifications
00809-0100-4765, Rev. AB April 2016

C.4 Regulatory compliance


C.4.1 EMC compliance (CE)
Complies with EMC directive 2004/108/EC.

EN 61001-6-4 Emission standard for industrial environment EN 55016-2-3 Class A


(2007) (2006)
EN 61000-6-2 Immunity standard for industrial environment EN 61000-4-2 (2009)
(2005) EN 61000-4-3 (2006)
EN 61000-4-4 (2004)
EN 61000-4-5 (2005)
EN 61000-4-6 (2007)

C.4.2 UL/c-UL compliance


The certification has been documented by UL in file E214107.

C.4.3 Galvanic isolation on Modbus serial interface

EN 60950-1 (2001) Pollution Degree 2


Material Group IIIb
250 V RMS or 250 VDC Working voltage
500 V Secondary circuit transient rating

62 Specifications
Reference Manual
00809-0100-4765, Rev. AB
April 2016
Global Headquarters
Emerson Process Management
6021 Innovation Blvd.
Shakopee, MN 55379, USA
+1 800 522 6277 or +1 303 527 5200
+1 303 530 8459
[email protected]

North America Regional Office


Emerson Process Management
7070 Winchester Circle
Boulder, CO 80301, USA
+1 800 522 6277 or +1 303 527 5200
+1 303 530 8459
[email protected]

Latin America Regional Office


Emerson Process Management
Multipark Office Center
Turrubares Building, 3rd & 4th floor
Guachipelin de Escazu, Costa Rica
+1 506 2505 6962
+1 954 846 5121
[email protected]

Europe Regional Office


Emerson Process Management Flow B.V.
Neonstraat 1 Linkedin.com/company/Emerson-Process-Management
6718 WX Ede
The Netherlands
Twitter.com/Rosemount_News
+31 (0) 318 495555
+31 (0) 318 495556
[email protected] Facebook.com/Rosemount

Asia Pacific Regional Office


Youtube.com/user/RosemountMeasurement
Emerson Process Management Asia Pacific Pte Ltd
1 Pandan Crescent
Singapore 128461 Google.com/+RosemountMeasurement
+65 6777 8211
+65 6777 0947
[email protected] Standard Terms and Conditions of Sale can be found at:
www.Emerson.com/en-us/pages/Terms-of-Use.aspx
The Emerson logo is a trademark and service mark of Emerson Process
Middle East and Africa Regional Office Management.
SMART Meter Verification (SMV), Rosemount and Rosemount logotype are
Emerson Process Management trademarks of Emerson Process Management.
Emerson FZE P.O. Box 17033, EtherNet/IP is a trademark of ControlNet International under license by
ODVA, Inc.
Jebel Ali Free Zone - South 2 Modbus is a registered trademark of Modicon, Inc.
Dubai, United Arab Emirates Anybus is a registered trademark of HMS Industrial Networks AB, Sweden,
USA, Germany, and other countries.
+971 4 8118100 Anybus Communicator is a trademark of HMS Industrial Networks AB,
+971 4 8865465 Sweden, USA, Germany, and other countries.
All other marks are the property of their respective owners.
[email protected] © 2016 Emerson Process Management. All rights reserved.

You might also like