Houseplan 1
Houseplan 1
Door Schedule
Comme
Type Mark Width Height nts
Single-Panel 2 1 3'-0" 7'-0"
Single-Decorative 2 2 3'-0" 6'-8"
Single-Panel 2 3 3'-0" 6'-8"
Single-Panel 2 4 3'-0" 6'-8"
Single-Flush 5 2'-8" 6'-8"
Single-Panel 2 6 2'-6" 6'-8"
Single-Flush 7 2'-8" 6'-8"
Type Window size Type Single-Flush 8 2'-6" 6'-8"
Type Mark Width Height Count Comments Sliding-Closet 9 4'-0" 6'-8"
Single-Panel 2 10 3'-0" 6'-8"
Slider with Trim 1 4'-0" 4'-0" 2
Single-Panel 2 11 3'-0" 6'-8"
Olympia, WA 98512-6292
2011 Mottman Road SW
(360) 754-7711
9'-3" 10'-2 1/2"
10"X10" VENT
ICE MKR EGRESS
MAKEUP AIR
3'-3"
DW REF
2X6
4'-6 1/2"
2X6
4'-3"
7'-3 3/4"
8'-4 3/4"
10'-0"
11'-8 3/4"
11'-6 3/4"
11'-1" 2'-0 1/2" 2'-0 1/2" 3'-4 1/2"
2'-6"
13'-3 3/4"
3'-11 1/2" 3'-2 3/4"
2X6
BATHROOM 2
13'-5"
STORAGE
BEDROOM 2
16'-3 3/8"
50
F CFM BATHROOM LAUNDRY
2'-10 1/2" 14
PANTRY
3'-7"
STOR
4
KITCHEN
7
3'-4"
15
3
13
ALL SMOKE/CO DETECTORS LINKED W/ BATTERY BACKUP MAX. RISE 7 3/4" MIN. RUN 10"
WD 16
S /P
2x6
2x6
6
VENT LIN
3'-6 1/2"
6'-9"
6'-9"
3'-4"
3 S/P
8" 1 1
HAND RAIL A302 A302
1112
STATUS: Preliminary
S/P HAND RAIL 5
2'-4 1/2"
2'-4 1/2"
2'-4 1/2"
914 SQUARE FEET S/P 17 S/P
1ST FLOOR 10
W/PAN
10'-2 3/4"
9 8 18
LIVING ROOM
3'-11 1/2" 4'-11 1/2" 3'-11"
15'-1"
BEDROOM 3
3 BEDROOM 1 BEDROOM 4
HOUSE
EGRESS EGRESS
EGRESS
PROJECT:
1
8 8
1 1
HB
REVIISIIONS
# DESCRIIPTIION DATE
28'-0"
SHEET SCALE:
4
A302 1/4" = 1'-0"
6/18/2013 11:18:47 AM
1ST FLOOR - DIMENSION
1 2 2ND FLOOR - DIMENSION SHEET TIITLE:
A101 1/4" = 1'-0" A101
1/4" = 1'-0" FLOOR PLANS
2'-0"
2'-0"
PORCH ROOF 2'-0" GABLE AND EVE OVERHANG TYP.
OPEN SOFFIT
4'-0"
MANUFACTURED TRUSSES @ 24" O.C. TYP.
2'-0"
32'-0"
32'-0"
36'-0"
36'-0"
36'-0"
CONTINUOUS RIDGE VENT TYP.
42'-0"
STATUS: Preliminary
2'-0"
HOUSE
PROJECT:
2'-0"
2'-0"
4'-3 3/4" 13'-8 1/2" 9'-11 3/4" 13'-8 1/2"
32'-0" 32'-0"
REVIISIIONS
# DESCRIIPTIION DATE
2 1
ROOF FRAMING PLAN A106 ROOF PLAN
A106
1/4" = 1'-0" 1/4" = 1'-0"
SHEET SCALE:
1/4" = 1'-0"
6/18/2013 11:18:48 AM
A106
CONTINUOUS RIDGE VENT
12
6
GUTTERS AT ALL HORIZONTAL FASCIAS.
Olympia, WA 98501
5''-0""""
5/4X4 PRIMED SPRUCE
CORNER BATTS AND WINDOW WRAP F.F.L. 2nd FLR F.F.L. 2nd FLR
TYP. 9'-1 3/4" 9'-1 3/4"
LIGHT T.O.W. 1st FLR
8'-1 1/8" T.O.W. 1st FLR
8'-1 1/8"
"HARDIE PLANK" SIDING W/ 6" REVEAL
COMMUNITY COLLEGE
Olympia, WA 98512-6292
2011 Mottman Road SW
1 FRONT 2 RIGHT
A201 A201
STATUS: Preliminary
37th Ave SE Lacey Wa 98503
T.O.W. 2nd FLR
14'-1 3/4" T.O.W. 2nd FLR
14'-1 3/4"
HOUSE
8'-1 1/8"
8'-1 1/8"
PROJECT:
H.B.
GFCI
F.F.L. 1st FLR F.F.L. 1st FLR REVIISIIONS
0" 0" # DESCRIIPTIION DATE
SHEET TIITLE:
ELEVATIONS
A201
ELEVATIONS
4X8 BEAM
TYPICAL EXTERIOR
WALLS: "HARDIE PLANK" SIDING W/6"
REVEAL R-6 1" RIGID FOAM
INSULATION APPROVED BUILDING
WRAP
7/16" O.S.B. SHEATHING O.A.E.
30 YEAR ARCHITECTURAL GRADE ROOFING 2X6 STUDS @ 16" O.C.
Olympia, WA 98501
APPROVED BUILDING
O.A.E.
SCREENED
VENTING 1" CLEARANCE
GALVANIZED METAL "Z" FLASHING
F.F.L. 1st FLR
5/4 PRIMED 0"
SPRUCE
FASCIA
R-38 BATT INSULATION 5/4X4 RADIUS CEDAR DECKING
CONTINUOUS 11-7/8 RIM JOIST
GUTTER
(2) 5/8" GALVANIZED THRU BOLT 3' O.C.
COMMUNITY COLLEGE
EACH TRUSS MAX RISE 7 3/4"
Olympia, WA 98512-6292
2011 Mottman Road SW
MIN RUN 10" (SEE FOUNDATION DETAILS)
1/2" G.W.B TYP.
www.spscc.ctc.edu
(360) 754-7711
TYPICAL EXTERIOR WALLS:
"HARDIE PLANK" SIDING W/6" REVEAL
R-6 1" RIGID FOAM INSULATION
APPROVED BUILDING WRAP
7/16" O.S.B. SHEATHING O.A.E. R-21 BATT INSULATION 2X8 P.T. JOISTS @16"
O.C.
2X6 STUDS @ 16" O.C.
R-21 WALL INSULATION
1/2" GYPSUM WALL BOARD
R-38 BATT INSULATION
LEDGER W/ FLASHING AND
ATTACHMENT
4X8 P.T. BEAM
7/8 T&G OSB SUBFLOOR 3
GLUED AND NAILED A302
F.F.L. 2nd FLR
9'-1 3/4"
12
6
PREFAB SCISSOR TRUSSES @
24" O.C.
LOW "E" INSULATED GLAZING (SEE ROOF FRAMING)
STATUS: Preliminary
37th Ave SE Lacey Wa 98503
T.O.W. 2nd FLR
2X6 SILL PLATE 14'-1 3/4"
5/4 PRIMED SPRUCE
R-5 RIDGID
TYP. EXT. TRIM
FOAM
5'-0"
1'-0 5/8"
MAX. RISE 7 3/4"
HOUSE
0" 9'-1 3/4"
MIN. RUN 10"
11-7/8" ENGINEERED I-JOIST @ 16" O.C. NOSING 3/4 TO 1-1/4
T.O.W. 1st FLR
PROJECT:
8'-1 1/8"
JOIST HANGER
2X6 P.T. SILL PLATE
DOUBLE RIM
3-1/8" X 8" PARALAM JOISTS
FILTER FABRIC PER CODE
4" PVC DRAIN PIPE SLOPED
TO DRYWELL
8'-1 1/8"
.006 BLACK POLY VAPOR BARRIER A302 REVIISIIONS
# DESCRIIPTIION DATE
2 WALL SECTION
A302 F.F.L. 1st FLR
3/4" = 1'-0" 0"
SHEET SCALE:
CRAWL SPACE
.006 BLACK POLY VAPOR BARRIER
As indicated
6/18/2013 11:18:51 AM
SHEET TIITLE:
BUILDING
1 BUILDING SECTION SECTIONS
A302
3/8" = 1'-0"
A302
BUILDING SECTIONS
ABBREVIATIONS
A E P
GENERAL NOTES
A/C Air conditioning EQUIV Equivalent PERIM Perimeter 1. All construction to comply with the current release of the International Residential Code (IRC)
A/E Architect/engineer ESMT Easement PK LOT Parking lot and all other appropriate codes and standards. The IRC takes precedence over drawings.
AB Anchor Bolt EST PL Property line 2. Plans and dimensions to be checked and verified by contractor prior to construction.
Estimate
ABS Acrylonitrile butadiene styrene PLYWD Plywood Avoid scaling distances off of the prints as plans may expand during reproduction.
EW Each way
ACOUS Acoustical insulation PREFAB Prefabrication 3. Building codes are subject to change and varying interpretation. Every effort has been made
EWH Electric water heater
INSUL ACS Access door PRELIM Preliminary to insure these plans comply with local and state regulations and codes.
EXIST Existing
DR Acoustic PREV Previous 4. The permit process includes plan review by the building department with jurisdiction
EXST GR Existing grade
ACST Americans with Disabilities Act PRKG Parking
EXT Exterior over the building site.
ADA Automatic door closer PROP Property
F 5. Contractor shall verify all existing dimensions, member sizes, and conditions prior to
ADC Adhesive PT Pressure treated
FA
commencing any work.
ADH Adjacent Fire alarm PT CONC Post-tensioned concrete
FACP 6. All wood exposed to the weather, including decks, railings, joists, beams, and posts shall be
ADJ Administration Fire alarm control panel PTD Paper towel dispenser
ADMIN FAS PVC
pressure treated or cedar. All fasteners and hardware in contact with pressure treated lumber
Above finished floor Fascia Polyvinyl chloride (plastic)
AFF FD shall be hot-dipped galvanized, G185 galvanized, z-max or equivalent.
Aggregate Floor drain Q 7. Unless otherwise indicated, all new interior walls are standard 2x4 wood frame construction with
Olympia, WA 98501
COMMUNITY COLLEGE
BD South
Bevel G SC
Olympia, WA 98512-6292
Galvanized steel Solid core 12. EGRESS WIINDOWS:
www.spscc.ctc.edu
Smoke detector
(360) 754-7711
Built GL BLK SF
BLDG Glazing Square feet with
Built-in GLU LAM SGD
BLT Gymnasium Sliding glass door finished sill height below adjacent ground elevation shall have a window well which shall comply
Boulevard GLZ SH
BLT Gypsum wall board Single hung (window) with the following: Net operable area of 9 square feet, a minimum dimension of 36” and when
Below GYM SHR
IN GWB SHTHG Shower vertical depth is greater than 44” an approved affixed ladder or stairs shall be provided.
BLVD Beam
Hose bib SHV Sheathing LIVING
BLW H Hollow core SLD Shelving AREA SQ. DECK SQUARE FOOTAGE
Bottom HB Horizontal sliding window
BM
Building Paper HC
Handicapped
Heavy duty
WDW
SND Sanitary napkin dispenser
13. SMOKE DETECTORS AND CARBON MONOXIIDE ALARMS:
A Smoke Detector shall be installed in each sleeping area and in the corridor leading to them.
FOOTAGE FRONT PORCH: 84 SQUARE FEET
Bedroom HCP Specification
BOT
BP Bracing HD
Header
Hardwood
SPEC
SQ Square
Detectors shall be hard wired, installed on each floor level, and shall have a battery back-up
feature. The Carbon Monoxide alarm shall be installed on each floor and in the corridor serving the
LEVEL AREA REAR PORCH: 32 SQUARE FEET
BR Bridging HDR
SQ IN Square inch F.F.L. 1st FLR 846 SF
Hemlock fir sleeping areas.
BRCG Bearing HDWD
SQ YD Square yard
Hanger 14. STAIIR DESIIGN CRIITERIIA:
BRDG Basement HF ST Street
Holdown 7-3/4” maximum rise / 10” minimum run. Minimum head room shall be 6’-8”. Place handrails 34” –
BRG Bathtub HGR Standard
Handrail STD
38” above tread nosing. Guard rails minimum 36” high with intermediate members installed not
BSMT
BT
Better
British thermal unit
HLDN
HNDRL
Horizontal STOR
STRUCT
Storage
Structural
more than 4” apart. Minimum size of stair nosing shall be ¾” with a maximum of 1-3/4”. SYMBOL LEGEND
HORIZ
Height 15. SAFETY GLAZIING:
BTR Between SUB FL Subfloor
HT
Heavy All glazing in I.R.C. deemed hazardous Ares must be safety glazing including: All ingress and egress
Btu Hot water SURF Surface
BTWN HVY SUSP Suspended door glazing, any sliding door assemblies and panels (exclude wardrobe doors). Tub/shower
Center to center Highway 101 1t
HW SWR enclosures and any glazing in walls within 60” of standing area, Glazing in any opening adjacent to a
C Cabinet Sewer
C TO C Cantilever
HWY Identification SYM Symbol door within 12” where the bottom is less than 60” above the walking surface, All glazing less than 18” Sheet List
above the floor, All glazing in stairwell landings and railings.
CAB ID I SIM
CANTIL
CAP Capacity 16. EXHAUST FAN DESIIGN CRIITERA:
1
A101 1 Ref
Sheet Number Sheet Name
INSTL Install T The point of discharge of exhaust air shall be at least 3’-0” from any building opening. Exhaust fans
DOOR TAGS WIINDOW TAG
G001 COVER SHEET
CD Construction Documents T&G Tongue and groove
Ref
Ref
INT Interior are required in each kitchen bathroom, water closets, laundry facility and any other areas where A101 FLOOR PLANS
CEM Cement T/S Tub/shower BUIILDIING SECTIION
IRC International Residential Code excess water vapor or cooking odor is produced. Each dwelling shall be equipped with a whole 1 1 A106 ROOF PLANS
CHK Check TB Towel bar
CJ Control J TD Towel dispenser house fan NAME A201 ELEVATIONS
CL JAL Jalousie that provides a continuous exhaust of 1 sone or less, 45 cfm for 2-3 bedrooms or 60 cfm for a 4 SIM ELEVATION A302 BUILDING SECTIONS
joint Center TEL Telephone 1 Ref
J-BOX Junction box bedroom house. A label is to best installed at the location of the whole house fan switch that A101 S101 FOUNDATION PLAN
CLG line Ceiling TEMP Temporary
states: “Whole House Fan”. 1 IINTERIIOR ELEVATIION S102 FLOOR FRAMING PLAN
CLO Closet K TFF Top of finished
CLR THK 17. WATER CLOSET DESIIGN CRIITERA: A101 S105 LATERAL PLAN
Color K Thousand floor Thickness
CMPTR Computer KD Kiln dried TO FND Top of foundation Water closets shall be installed in a clear space of no less than 30” in width and the clear space in WALL SECTIION LEVEL WIITH ELEVATIION
CMU Concrete masonry KIT Kitchen TOC Top of concrete front of the toilet shall not be less than 24”.
CNR unit Corner KO Knockout TOPO Topography 18. WATER HEATERS:
CNTR Counter TOS Top of slab Water heaters shall be anchored or strapped to resist horizontal displacement due to earth quake
L TOW Top of wall motion. Temperature and pressure relief valves shall be drained to the exterior of the building.
COL Column L CL Linen closet TPD
CONC Concrete Toilet paper dispenser All electric water heaters shall be placed in a metal pan when installed over wood framing and if
LAM Laminate TRANS
CONC FLR Concrete floor Transom installed in an unheated space or on a concrete floor on an R-10 insulated pad.
LATL Lateral TV
CONSTR Construction Television 19. ATTIIC ACCESS:
LAV Lavatory TYP
CONT Continue Typical Attics with a minimum vertical height of 30” must be provided with an access of not less than 22” X
STATUS: Preliminary
LBR Lumber
CR Closet rod LC Laundry chute U 30”. If an access is provided it must be installed with a curb of not less than 12”.
CSMT Casement LD BRG UBC Uniform Building Code
Load-bearing
CSWK Casework LF UFC Uniform Fire Code
Linear feet
CTR
CTRL
Center LIN Linear
UMC
UP
Uniform Mechanical Code ENERGY CODE NOTES
HOUSE
DIM
Microwave W/O
Dimension N Without
DIST WC
Distance N Water closet
North WD
PROJECT:
DJ Double joist NO Wood
Number WDW
DL Dead load NTS Window
Not to scale WH
DF Douglas fir Water heater
DR O WL
Water line
Door OC WP
DS Down spout On center Weatherproof
OH WSCT
DW Dishwasher Overhang WT
Wainscot
OPT
DWG Drawing Optional WTR
Weight
OUT
DX OUT Duplex outlet Outlet WWF
Water
E P Wire welded fabric REVIISIIONS
E
PERIM X # DESCRIIPTIION DATE
East Perimeter XL
PL
EA Each Property line Extra large
PLYWD
EH Electric heater PREFAB
Plywood Y
EJ Prefabrication YD
Expansion joint PRELIM Yard
ELEC Preliminary YR
Electric PRKG Year
ENGR PT
Parking Z
Engineer
EOS PTD Pressure treated N/A
Edge of slab
EQ PVC Paper towel dispenser N/A
Equal Polyvinyl chloride (plastic)
SHEET SCALE:
As indicated
6/18/2013 11:18:53 AM
SHEET TIITLE:
COVER SHEET
6'-9"
AND MAY REQUIRE BEARING CAPACITY TO BE DETERMINED BY A SOILS INVESTIGATION.
2. FOR ALL BUILDINGS, PLATE WASHERS A MINIMUM OF 1/4" x 3" x 3" IN SIZE SHALL BE PROVIDED
BLOCKING
BETWEEN THE FOUNDATION SILL PLATE AND THE NUT.
3. ALL FOUNDATION POST COLUMNS REQUIRE A POSITIVE CONNECTION AT THE BOTTOM END TO
PREVENT LATERAL DISPLACEMENT.
2X6 DBL. TOP PLATE
4. EXCEPT FOUNDATION WALLS SUPPORTING LESS THAN 4'-0" OF UNBALANCED BACKFILL, THE
BACKFILL SHALL NOT BE PLACED AGAINST THE FOUNDATION WALL UNTIL IT HAS CURED FOR 14 6'-0" 3'-0" 5'-10 3/4" 6'-0" 5'-4 3/4"
DAYS.
3'-10 1/4"
2X6 PONY WALL CONT.
2'-1 1/2"
5. THE GRADE AWAY FROM THE FOUNDATION WALLS SHALL FALL A MINIMUM OF 6 INCHES WITHIN 10 1/4" 10 1/4"
THE FIRST 10 FEET. W/ NO SHEATHING
4'-0"
7. FOUNDATION WALLS THAT RETAIN EARTH AND ENCLOSE HABITABLE OR USABLE SPACES LOCATED
COMMUNITY COLLEGE
3'-0 1/4"
9. ANY DETAIL SHOWING A "SIMPSON" CONNECTOR MAY HAVE THE CONNECTOR REPLACED WITH
Olympia, WA 98512-6292
CONTINUOUS RIBBON
www.spscc.ctc.edu
(360) 754-7711
VAPOR BARRIER
7"
ONE-STORY: 12" BELOW UNDISTURBED SOIL
4'-6 1/4"
TWO-STORY: 18" BELOW UNDISTURBED SOIL
NOTE:
6X6 POSTS @ POINT LOADS
FOUNDATION VENTS 2/150
1'-3" S.F. PER CODE
900 S.F./150=6(2)=12 VENTS
3'-5"
4 FOOTING W/ PONY WALL
S101
1" = 1'-0"
7'-9 1/4"
32'-0"
32'-0"
.006 BLACK POLY VAPOR BARRIER
13'-3 1/4"
FLOOR SYSTEM
2X6 P. T. CONTINUOUS MIN. 1/2" A.B. @ 6'-0" O.C. 11-7/8" RIM BOARD FLOOR JOISTS
SILL PLATE W/7" EMBEDMENT PER PLAN
- (2) A.B. PER PLATE SECTION 2X6 P.T. SILL PLATE
STATUS: Preliminary
-4-1/2" FROM END OF PLATE
-3"X3"-1/4" PLATE WASHER
ALTERNATE: MAINTAIN 1/2" AIRSPACE
MFR'D MUDSILL ANCHORS BETWEEN PONY WALL AND CONCRETE.
SPACING PER MFR'S SPEC.
GRADE
2X6 DBL. TOP PLATE
5'-10 1/4"
5'-10 1/4"
WITHIN THE TOP NO SHEATHING
6'-0"
1'-1"
12"
#4 @ 48" O.C. 4'-3 3/4" 6'-0 1/4" 6'-0" 1'-8 1/4" 9'-11 3/4"
4" STD. HOOK 2X6 P.T. SOLE PLATE
W/ POSITIVE CONNECTION
HOUSE
6'-6"
1'-3"
PROJECT:
28'-0"
SHEET SCALE:
As indicated
6/18/2013 11:18:54 AM
SHEET TIITLE:
FOUNDATION PLAN
1'-6" 5'-0"1'-6"
4'-0"
NOTE: RIM BOARD REQUIRED @ PORCH CONNECTIONS UNDER SECOND FLOOR WALLS
Olympia, WA 98512-6292
11-7/8" ENGINEERED I-JOIST @ 16" O.C.
(360) 754-7711
2X8 LEDGER W/ TYP. FLASHING HANGER ALL JOIST-LEDGER CONNECTIONS TYP.
(SEE PORCH SECTION VIEW)
15'-10 1/4"
5/4 RADIUS CEDAR DECKING TYP.
STAGGERED BLOCKING @ GIRDER BEAM TYP.
6'-5 1/2"
DOUBLE AND HANGER @ INTERRUPTED HANGING JOISTS
32'-0"
32'-0"
32'-0"
32'-0"
TYP.
16'-1 3/4"
STAGGERED BLOCKING @ BEARING WALL TYP.
STEPS
13'-6 1/4"
4X4 POST
STATUS: Preliminary
NOTE: RIM BOARD REQUIRED @ PORCH CONNECTIONS
28'-0"
HOUSE
PROJECT:
6'-8" 5'-0" 2'-4"
28'-0" REVIISIIONS
# DESCRIIPTIION DATE
3 PORCH FRAMING PLAN - FRONT 1 FLOOR FRAMING PLAN - 1ST FLOOR 2 FLOOR FRAMING PLAN - 2ND FLOOR
S102 S102 S102
1/2" = 1'-0" 1/4" = 1'-0"
1/4" = 1'-0"
SHEET SCALE:
As indicated
6/18/2013 11:18:55 AM
SHEET TIITLE:
FLOOR FRAMING
PLAN
S102
FLOOR FRAMING PLAN
28'-4 1/8"
GENERAL NOTES - LATERAL BRACING
BRACED WALL LINE AND BRACED WALL LOCATIONS
1. BUILDINGS SHALL BE PROVIDED WITH EXTERIOR AND INTERIOR BRACED WALL LINES.
4'-2 1/8" 20'-0" 4'-2 1/8"
BRACED WALL LINE SPACING SHALL NOT EXCEED 25'-0" IN BOTH DIRECTIONS EACH
STORY. NOTE: THURSTON COUNTY EXEMPTS ONE 900 S.F. LIVING SPACE AREA ON EACH
FLOOR FROM INTERIOR LATERAL BRACED WALL LINE COMPLIANCE.
2. BRACED WALL LINES SHALL CONSIST OF BRACED WALL LINES ACCORDING TO DETAILS
WALL STUDS @ 16" O.C.
4'-2 1/8"
4'-2 1/8"
PROVIDED AND IF MORE THAN ONE OFFSET OCCURS IN THE SAME INTERIOR BRACED
WALL LINE, THE CODE LIMITS THE SUM OF THE OFFSETS TO 8 FEET.
3. BRACED WALL PANELS SHALL START AT NO MORE THAN 8" FROM EACH END OF A
BRACED WALL LINE. THE CODE LIMITS THE SUM OF THE OFFSETS TO 8 FEET.
INTERIOR FINISH
4. ONE STORY BUILDINGS MUST HAVE 20% OF THE EXTERIOR WALL AREA CONSIST OF BRACED
PROVIDE CORNER CLIPS
WALL PANELS. THE FIRST STORY OF A TWO-STORY BUILDING MUST HAVE 45% OF THE
OR BLOCKING AS NEEDED
EXTERIOR WALL AREA CONSIST OF BRACED WALL PANELS IN ADDITION TO THE SECOND
FLOOR HAVING A MINIMUM OF 20% WALL PANEL AREA.
4'-0"
4'-0"
CONSTRUCTION OF BRACED WALL PANELS
"CALIFORNIA CORNER" 1. OPTIONAL SHEATHING MATERIALS:
A. WOOD STRUCTURAL PANEL SHEATHING WITH A THICKNESS NOT LESS THAN 5/16"
FOR 16" O.C. SPACING AND NOT LESS THAN 3/8" FOR A 24" O.C. STUD SPACING.
B. G.W.B. 1/2" THICK AND 4'-0" WIDE ON STUDS NO MORE THAN 24" O.C. W/NAILS @ 7" O.C.
C. HARDBOARD PANEL SIDING.
Olympia, WA 98501
12'-0"
CONNECTED TO THE FOUNDATION WITH A TIE-DOWN DEVICE PROVIDING AN UPLIFT
FASTEN W/8d COMMON @ CAPACITY OF AT LEAST 1,800 LBS.
6" O.C. ALL EDGES & 12" O.C. 2. IN THE FIRST STORY OF TWO STORY BUILDINGS, EACH PANEL SHALL BE PROVIDED WITH
IN THE FIELD WOOD STRUCTURAL PANEL SHEATHING ON BOTH SIDES WITH MINIMUM TIE-DOWN
16'-0"
4'-0" IINTERIIOR LATERAL EXEMPTIION 896 S.F.
DEVICE UPLIFT CAPACITY OF 3,000 LBS. ALL REQUIRED BRACED WALL PANELS IN
BUILDINGS
WITH PLAN DIMS. GREATER THAN 50' SHALL BE SUPPORTED BY CONTINUOUS FOOTINGS.
4'-0 1/8"
www.spscc.ctc.edu
*TYPICALLY USED ON INTERIOR WALLS
3/4" = 1'-0" 6
OPTIONAL LATERAL PLAN - 1ST FLOOR
S105
SHEATHINGS 1/4" = 1'-0"
SEE GENERAL NOTES
28'-4 1/8"
FASTEN W/8d
14'-3 5/8" 14'-0 5/8"
COMMON NAILS
@ 6" O.C. ALL EDGES
& 12" O.C. FIELD 4'-2 1/8" 20'-0" 4'-2 1/8"
TOP NAILING
(3) 16d @
4'-2 1/8"
4'-2 1/8"
16" O.C.
TOP PLATE
TO FRAMING NOTE:
ABOVE. BRACING
PANELS ATTACH
TO PARALLEL
STATUS: Preliminary
ROOF FRAMING
ABOVE.
4'-0"
4'-0"
PROVIDE FLAT
LADDER
16'-0 3/8"
BLOCKING
NOTE:
18'-7 7/8"
2x BLOCK @ ANY NEEDED
WALL
PLYWOOD JOINT BETWEEN ROOF
PANELS NEED
NOT FRAMING
INTERSECT EXTERIOR MEMBERS.
WALLS BUT MUST WHEN FRAMING
SOLE PLATE RUNS
BEGIN WITHIN 8'-0"
OF EXTERIOR WALL. PERPENDICULAR
SUB-FLOOR TO BRACING
PANELS
16'-0"
RIM JOIST/ FLOOR FRAMING
1/2" GYPSUM WALL
HOUSE
BOARD MAY BE
P.T. SOLE PLATE BEARING PLATE WASHER INSTALLED VERTICALLY NOTE:
ALL VERTICAL
PROJECT:
OR HORIZONTALLY
W/ SCREWS OR NAILS JOINTS OF
@ 7" O.C. PANEL
(2) 1/2" A.B. W/7" SHEATHING
EMBEDMENT MIN. SHALL OCCUR
OVER STUDS.
4'-0"
1'-0"
HORIZONTAL
JOINTS SHALL
OCCUR OVER
BLOCKING
REVIISIIONS
EQUAL IN SIZE
TO THE # DESCRIIPTIION DATE
STEM WALL
4'-0"
STUDS.
BOTTOM
NAILING
FOOTING
(3) 16d @
16 O.C.
SOLE
PLATE TO NOTE:
FRAMING WHEN JOISTS RUN PARALLEL TO BRACED WALL LINES
BELOW. ABOVE, PROVIDE DOUBLE JOISTS UNDER AND IN LINE WITH
BRACED WALL PANELS.
7 LATERAL PLAN - 2ND FLOOR
S105 4'-2 1/8" 20'-0" 4'-2 1/8"
WHERE JOISTS ARE PERPENDICULAR TO BRACED WALL SHEET SCALE:
1/4" = 1'-0"
LINES ABOVE, FULL DEPTH BLOCKING SHALL BE PROVIDED
UNDER AND IN LINE WITH BRACED WALL PANELS. 14'-3 5/8" 14'-0 5/8" As indicated
STANDARD LATERAL - INTERIOR 6/18/2013 11:18:56 AM
5 DETAIL
28'-4 1/8"
S105 SHEET TIITLE:
1" = 1'-0"
STANDARD LATERAL PANEL - LATERAL PLAN
2 ELEVATION
S105
1" = 1'-0"