Fire Pump Data Book
Fire Pump Data Book
ii
A Brief Introduction
History of PUMPSENSE goes back to 1995 when a group of professionals working in large
international pumps companies decided to team together. At PUMPSENSE, we are united
through a common vision to build an excellent pumps company through which we can express
ourselves fully and freely. Each one of us has an abiding interest in one aspect or the other of
the pumps business – right from hydraulic design to applications engineering, product
development to marketing. We also share a common conviction that with our skills, passion
and commitment, we can redefine the existing norms and standards of customer satisfaction.
We wish to work, learn and create value in a nourishing and fulfilling environment for our
customers, business associates and ourselves. PUMPSENSE exists to fulfill this collective
dream, based on a core set of values which are our guiding philosophy in creating this
organization.
The business of PUMPSENSE is to provide centrifugal pumps and related services. We
will constantly strive to increase the delivered value to our customer by careful attention to
details, by continuous improvement of our core capabilities and by our commitment to delight
the customer at every point of contact. The quality of our products and services will reflect the
improvement in the quality of life that we are able to bring to our employees – we will provide
them with an informal and liberal work environment, where they can constantly learn and grow.
We recognize that our suppliers play a key role in the quality of our products and services. We
will work closely with our suppliers so that they share our energy and focus to serve the
customer with excellence. Above all, we will strive to create an organization where there are
no barriers amongst customers, employees and suppliers and all of us work together to create
value, to grow, to learn and to enhance the quality of our lives.
3
1. Fire Pumps (Objectives for Development)
Fire pumps manufactured by Pumpsense are in full compliance with the requirements of
NFPA20. In addition, these pumps meet all the clausal requirements of established fire pumps
approval standards such as FM1311 of Factory Mutual and UL448 of Underwriters
Laboratories.
In particular, fire pumps manufactured by PUMPSENSE has the following objectives.
a) Efficiency is not the hardest criteria.
b) To obtain a steep H-Q characteristic and preferably, a non-overloading power curve
characteristic in a low specific speed.
c) Any fire pump shall be designed for rated capacities equal to or greater than 25USGPM.
Rated pump pressure shall be at least 40 psi.
d) The pump shall develop its rated pressure when delivering at rated capacity. The pump
shall not exceed 140% of its rated pressure at any point along its characteristic curve,
including the shut-off point. The shut-off head shall not be less than 99% of its rated head.
e) The pump shall develop at least 65% of its rated pressure when operating at a suction lift
of at least 15ft (4.6m), referred to sea level, and delivering 150% of rated capacity. If
mechanical seals are used, they shall not allow air to leak into the pump at any point along
the characteristic curve, not including the shut-off. This poses a design challenge, especially
for lower trims.
f) Design an economical unit which meets the high-test pressure requirement of UL
(Maximum pressure + 75 PSI) × 2.
g) Achieve increased mechanical reliability and driver rating optimization.
h) The minimum internal dimensions of the passage at any point shall not be less than (UL
448). 5/16 inch (7.9mm) for a pump rated 500 gallons per minute (1893 L/min) or less; or
½ inch (12.7mm) for a pump rated more than 500 gallons per minute.
i) All water passages shall be designed to minimize the possibility of foreign materials
becoming lodged in them (FM 1311). The minimum width of these passages at the
periphery or at any point within the impeller shall be at least ½ in. (12.7mm) for pumps
rated 500 gallons per minute (1895 L/min) and larger. Passages in pumps having rated
capacities of 100 to less than 500 gallons per minute (380 to less than 1895 L/min) shall be
at least 3/8in. (9.5mm). Passages in pumps having rated capacities less than 100 gallons per
minute (380 L/min) shall be at least ¼ in. (6.3mm).
4
2. Mechanical Design (Criterions to be fulfilled)
Pumpsense always fulfill the following mechanical design criteria for its fire pump models.
a) A casting shall be smooth and free from scale, lumps, cracks, blisters, sand holes, and
defects of any nature that may affect the use for which it is intended. A casting shall not be
plugged or filled but may be impregnated to remove porosity.
b) A bolt, stud, cap screw, or gland swing bolt to assemble parts subject to stress due to water
pressure shall not be less than 3/8 inch (9.5mm) in diameter.
c) An interior bolt or screw that is exposed to pumped water shall be constructed of the
corrosion resistant material or series 400 stainless steel.
d) The maximum combined shear stress for a pump shaft, based upon the minimum diameter
at the root of threads or an undercut (not including the undercutting for keys), shall not
exceed 30 percent of the elastic limit in tension or be more than 18 percent of the ultimate
tensile strength of the shafting steel used. For shafts with keyways, the allowable stress
limits shall be 75 percent of the stresses calculated using the minimum shaft diameter at
the key location (not including the undercut). Compliance with this requirement is to be
verified by a review of manufacturers’ stress calculation.
e) The impellers shall be dynamically balanced to G6.3 balance quality grade in accordance
with the requirements for pump impellers in the Standard for Mechanical Vibration -
Balance Quality Requirements of Rigid Rotors, Part 1: Specification and Verification
of Balance Tolerances, ISO 1940-1.
f) Flange dimensions and bolt layouts used in pipe connections shall comply with the
requirements of one of the following standards.
1) Standard for cast iron pipe flanges and flanged fittings, ANSI/ASME B16.1;
2) Standard for ductile iron pipe flanges and flanged fittings: Classes 150 and 300,
ANSI/ASME B16.42; or
3) Standard for pipe flanges and flanged fittings: NPS ½ through 24, ANSI/ASME B16.5,
when steel is used.
g) A pump casing shall be constructed to permit examination of impellers and other interior
parts without disturbing suction or discharge piping. The casing shall include means to
facilitate disassembly of the casing, and the stuffing box cover (if provided), without
requiring the use of wedges or prying elements, such as by provision of tapped holes for
jackscrews.
5
h) The pump shall be provided with feet or with provisions for accommodating feet or a
fabricated base support such as bolt holes and a bearing surface for attaching the base to
the pump.
i) A drain opening shall be provided so that all parts of the pump casing can be drained. The
opening shall be threaded to receive a plug, i.e.,
1) Not smaller than ½ inch (12.7mm) nominal pipe size for pumps having rated capacities
equal to or greater than 100 gallons per minute and ¼ inch (6.4mm) nominal pipe size
for pumps having rated capacities less than 100 gallons per minute;
2) Formed of corrosion – resistant material.
j) A pump shall be provided with casing wear rings that are made of material that will not
gall. The rings shall be secured to the casing in a manner that does not permit rotational or
axial movement. Impeller wearing rings need not be provided.
k) The radial clearance between a stationary and moving part of a pump shall not be less than
0.191mm.
l) The impellers shall be secured in an axial direction, permitting no contact with the casing
under operating conditions.
m) The impellers shall be of the closed type; that is, they shall incorporate shrouds or sidewalls
that completely enclose the impeller waterways from the suction eye to the periphery.
n) Ball and roller bearings shall have an L-10 rating of not less than 5000 hours at maximum
load in accordance with the Standard for Load Ratings and Fatigue Life for Ball Bearings,
ANSI / ABMA 9, and load ratings and Fatigue Life for Roller Bearings, ANSI / ABMA 9,
and Load Ratings and Fatigue Life for Roller Bearings, ANSI / ABMA 11, respectively.
6
7
3. Fire Pump Packages
3.1 FM Approved Fire pump packages
The fire pump packages consist of the following components which are furnished by the
pump manufacturer, alternate manufacturer, or a fire pump packager.
1) Fire pump (FM Approved);
2) Driver – diesel engine (FM Approved) or electric motor;
3) Pump controller (electric motor or diesel engine) (FM Approved);
4) Flexible coupling (not all elastomeric) or drive shaft;
5) Suction and discharge pressure gauges (FM Approved);
6) Pressure relief valve (FM Approved) and waste cone, when required;
7) Automatic air release valve (FM Approved);
8) Circulation relief valve (FM Approved);
9) Substantial bed plate for pump and driver;
10) Diesel engine accessories:
i) Starting batteries,
ii) Rigid cooling water and fuel lines (May have short flexible elements in close
proximity to engine to minimize vibration),
iii) Exhaust piping and muffler,
iv) Fuel tank.
11) Instruction, operation and maintenance manual in local language,
12) Spare mechanical seals (optional, for pumps FM Approved with mechanical seal).
Following accessories must be provided by the pump manufacturer along with the UL listed
pumps.
a) Automatic air-release valve (self-venting pumps excluded);
b) Circulation relief valve (except for engine driven pumps for which engine cooling
water is taken from the pump discharge) and;
c) Pressure gauges.
8
4. Fire Pumps Technical Datasheet
9
5. UL Listed Fire Pumps, Split Case
PUMPSENSE UL Listed Centrifugal Fire Pumps, Split Case
Sr. Rated Size, in. Model Rated Approx. Max Impeller Diameter, mm. Pump BKW, min Remarks
No. Capacity, Net Speed, Working to max
usgpm Pressure RPM Pressure,
Range, psi
psi
Minimum Maximum kW hP
1 300 6" x 4" 4HF12L 88-139 2600 300 260 310 30.97 41.53 Single
to to Stage
50.85 68.19 Pump
2 300 6" x 4" 4HF12L 104-161 2800 300 260 310 38.68 51.87 Single
to to Stage
63.51 85.17 Pump
3 300 6" x 4" 4HF12L 116-180 2950 300 260 310 45.24 60.67 Single
to to Stage
74.27 99.59 Pump
4 300 6" x 4" 4HF12L 120-186 3000 300 260 310 47.58 63.81 Single
to to Stage
78.11 104.75 Pump
5 400 6" x 4" 4HF12L 84-134 2600 300 260 310 30.97 41.53 Single
to to Stage
50.85 68.19 Pump
6 400 6" x 4" 4HF12L 99-157 2800 300 260 310 38.68 51.87 Single
to to Stage
63.51 85.17 Pump
7 400 6" x 4" 4HF12L 111-175 2950 300 260 310 45.24 60.67 Single
to to Stage
74.27 99.59 Pump
8 400 6" x 4" 4HF12L 115-182 3000 300 260 310 47.58 63.81 Single
to to Stage
78.11 104.75 Pump
9 400 4" x 3" 3HFT11 194-327 2930 410 230 295 91 to 122.03 Two
137 to Stage
183.72 Pump
10 450 6" x 4" 4HF12L 81-132 2600 300 260 310 30.97 41.53 Single
to to Stage
50.85 68.19 Pump
11 450 6" x 4" 4HF12L 96-155 2800 300 260 310 38.68 51.87 Single
to to Stage
63.51 85.17 Pump
12 450 6" x 4" 4HF12L 108-173 2950 300 260 310 45.24 60.67 Single
to to Stage
74.27 99.59 Pump
13 450 6" x 4" 4HF12L 113-179 3000 300 260 310 47.58 63.81 Single
to to Stage
78.11 104.75 Pump
14 500 6" x 4" 4HF12L 78-129 2600 300 260 310 30.97 41.53 Single
to to Stage
50.85 68.19 Pump
15 500 6" x 4" 4HF12L 93-152 2800 300 260 310 38.68 51.87 Single
to to Stage
63.51 85.17 Pump
10
16 500 6" x 4" 4HF12L 105-171 2950 300 260 310 45.24 60.67 Single
to to Stage
74.27 99.59 Pump
17 500 6" x 4" 4HF12L 109-177 3000 300 260 310 47.58 63.81 Single
to to Stage
78.11 104.75 Pump
18 500 6" x 4" 4HF13 130-176 2600 300 305 350 60.85 81.6 to Single
to 116.44 Stage
86.83 Pump
19 500 6" x 4" 4HF13 153-206 2800 300 305 350 76.01 101.93 Single
to to Stage
108.45 145.43 Pump
20 500 6" x 4" 4HF13 171-230 2950 300 305 350 88.89 119.2 Single
to to Stage
126.83 170.08 Pump
21 500 6" x 4" 4HF13 177-238 3000 300 305 350 93.48 125.36 Single
to to Stage
133.38 178.87 Pump
22 500 4" x 3" 3HFT11 187-320 2930 410 230 295 91 to 122.03 Two
137 to Stage
183.72 Pump
23 750 6" x 4" 4HF12 79-124 2600 300 264 310 41.12 55.14 Single
to to Stage
59.31 79.54 Pump
24 750 6" x 4" 4HF12 96-149 2800 300 264 310 51.36 68.87 Single
to to Stage
74.08 99.34 Pump
25 750 6" x 4" 4HF12 106-169 2950 300 264 310 60.07 80.56 Single
to to Stage
86.63 116.2 Pump
26 750 6" x 4" 4HF12 109-176 3000 300 264 310 63.17 84.71 Single
to to Stage
91.11 122.18 Pump
27 750 6" x 4" 4HF13 114-162 2600 300 305 350 81.6 to 81.6 to Single
116.44 116.44 Stage
Pump
28 750 6" x 4" 4HF13 137-192 2800 300 305 350 101.93 101.93 Single
to to Stage
145.43 145.43 Pump
29 750 6" x 4" 4HF13 155-215 2950 300 305 350 119.2 119.2 Single
to to Stage
170.08 170.08 Pump
30 750 6" x 4" 4HF13 162-224 3000 300 305 350 125.36 125.36 Single
to to Stage
178.87 178.87 Pump
31 1000 6" x 5" 5HF11 82-124 2600 300 252 310 54.3 to 72.82 Single
84.58 to Stage
113.42 Pump
32 1000 6" x 5" 5HF11 97-147 2800 300 252 310 67.82 90.95 Single
to to Stage
105.64 141.67 Pump
33 1000 6" x 5" 5HF11 109-165 2950 300 252 310 79.31 106.36 Single
to to Stage
123.55 165.68 Pump
11
34 1000 6" x 5" 5HF11 113-171 3000 300 252 310 83.41 111.85 Single
to to Stage
129.94 174.25 Pump
35 1000 8" x 6" 6HF14K 127-175 2600 335 320 360 99 to 132.76 Single
131 to Stage
175.67 Pump
36 1000 8" x 6" 6HF14K 151-206 2800 335 320 360 124 to 166.29 Single
164 to Stage
219.93 Pump
37 1000 8" x 6" 6HF14K 169-230 2950 335 320 360 145 to 194.45 Single
192 to Stage
257.48 Pump
38 1000 8" x 6" 6HF14K 175-239 3000 335 320 360 153 to 205.18 Single
202 to Stage
270.89 Pump
39 1000 8" x 6" 6HFTD12L 179-262 2600 443 260 314 134 to 179.69 Two
224 to Stage
300.39 Pump
40 1000 8" x 6" 6HFTD12L 210-306 2800 443 260 314 168 to 225.29 Two
279 to Stage
374.15 Pump
41 1000 8" x 6" 6HFTD12L 240-347 2975 443 260 314 201 to 269.55 Two
335 to Stage
449.24 Pump
42 1250 8" x 6" 6HF20 80-122 1500 271 428 520 95 to 127.39 Single
137 to Stage
183.72 Pump
43 1250 8" x 6" 6HF20 113-173 1760 271 428 520 153 to 205.18 Single
221 to Stage
296.37 Pump
44 1250 8" x 6" 6HF20 119-182 1800 271 428 520 164 to 219.93 Single
236 to Stage
316.48 Pump
45 1250 8" x 6" 6HF12 113-180 3000 275 245 305 106 to 142.15 Single
170 to Stage
227.97 Pump
46 1250 8" x 6" 6HFTD12L 229-342 2975 443 260 314 201 to 269.55 Two
335 to Stage
449.24 Pump
47 1500 8" x 6" 6HF20 76-117 1500 271 428 520 95 to 127.39 Single
137 to Stage
183.72 Pump
48 1500 8" x 6" 6HF20 109-167 1760 271 428 520 153 to 205.18 Single
221 to Stage
296.37 Pump
49 1500 8" x 6" 6HF20 115-175 1800 271 428 520 164 to 219.93 Single
236 to Stage
316.48 Pump
50 1500 8" x 6" 6HF12 106-172 3000 275 245 305 106 to 142.15 Single
170 to Stage
227.97 Pump
51 2000 10" x 8" 8HF20 80-122 1500 272 425 515 124 to 166.29 Single
186 to Stage
249.43 Pump
12
52 2000 10" x 8" 8HF20 115-172 1760 272 425 515 200 to 403.65 Single
301 Stage
Pump
53 2000 10" x 8" 8HF20 121-181 1800 272 425 515 214 to 286.98 Single
322 to Stage
431.81 Pump
54 2000 10" x 8" 8HF13 120-148 2800 300 305 330 146.07 195.88 Single
to to Stage
190.76 255.81 Pump
55 2000 10" x 8" 8HF13 136-167 2950 300 305 330 170.82 229.07 Single
to to Stage
223.09 299.17 Pump
56 2000 10" x 8" 8HF13 141-173 3000 300 305 330 179.65 240.91 Single
to to Stage
234.62 314.63 Pump
57 2500 10" x 8" 8HF20 74-115 1500 272 425 515 124 to 166.29 Single
186 to Stage
249.43 Pump
58 2500 10" x 8" 8HF20 110-166 1760 272 425 515 200 to 403.65 Single
301 Stage
Pump
59 2500 10" x 8" 8HF20 115-175 1800 272 425 515 214 to 286.98 Single
322 to Stage
431.81 Pump
13
6. FM Approved Fire Pumps, Split Case
PUMPSENSE FM Approved Centrifugal Fire Pumps, Split Case
Sr. Rated Size, Model Rated Net Approx. Max Impeller Diameter, Pump BKW, Remarks
No. Capacity in. Pressure Speed, Working mm. min to max
, usgpm Range, psi RPM Pressure,
psi
Minimum Maximum kW hP
1 300 6" x 4" 4HF12L 88-139 2600 261.8 260 310 28-48 38-64 Single
Stage Pump
2 300 6" x 4" 4HF12L 104-162 2800 261.8 260 310 38-63 51-84 Single
Stage Pump
3 300 6" x 4" 4HF12L 116-180 2950 261.8 260 310 44-73 59-98 Single
Stage Pump
4 300 6" x 4" 4HF12L 120-187 3000 261.8 260 310 46-77 62- Single
103 Stage Pump
5 400 6" x 4" 4HF12L 85-135 2600 261.8 260 310 28-48 38-64 Single
Stage Pump
6 400 6" x 4" 4HF12L 99-158 2800 261.8 260 310 38-63 51-84 Single
Stage Pump
7 400 6" x 4" 4HF12L 111-177 2950 261.8 260 310 44-73 59-98 Single
Stage Pump
8 400 6" x 4" 4HF12L 115-183 3000 261.8 260 310 46-77 62- Single
103 Stage Pump
9 450 6" x 4" 4HF12L 82-133 2600 261.8 260 310 28-48 38-64 Single
Stage Pump
10 450 6" x 4" 4HF12L 97-155 2800 261.8 260 310 38-63 51-84 Single
Stage Pump
11 450 6" x 4" 4HF12L 109-174 2950 261.8 260 310 44-73 59-98 Single
Stage Pump
12 450 6" x 4" 4HF12L 113-181 3000 261.8 260 310 46-77 62- Single
103 Stage Pump
13 500 6" x 4" 4HF12L 78-129 2600 261.8 260 310 28-48 38-64 Single
Stage Pump
14 500 6" x 4" 4HF12L 94-152 2800 261.8 260 310 38-63 51-84 Single
Stage Pump
15 500 6" x 4" 4HF12L 106-171 2950 261.8 260 310 44-73 59-98 Single
Stage Pump
16 500 6" x 4" 4HF12L 110-177 3000 261.8 260 310 46-77 62- Single
103 Stage Pump
14
17 750 6" x 4" 4HF12 79-122 2600 265.2 264 310 41-55 55-74 Single
Stage Pump
18 750 6" x 4" 4HF12 94-147 2800 265.2 264 310 48-74 64-99 Single
Stage Pump
19 750 6" x 4" 4HF12 107-166 2950 265.2 264 310 55-87 74- Single
117 Stage Pump
20 750 6" x 4" 4HF12 112-172 3000 265.2 264 310 58-90 78- Single
121 Stage Pump
21 1000 6" x 5" 5HF11 80-126 2600 262.9 252 310 50-83 67- Single
111 Stage Pump
22 1000 6" x 5" 5HF11 95-148 2800 262.9 252 310 67-108 90- Single
145 Stage Pump
23 1000 6" x 5" 5HF11 107-167 2950 262.9 252 310 78-126 105- Single
169 Stage Pump
24 1000 6" x 5" 5HF11 111-173 3000 262.9 252 310 82-132 110- Single
177 Stage Pump
25 1250 8" x 6" 6HF12 83-132 2600 263.8 252 305 68-109 91- Single
146 Stage Pump
26 1250 8" x 6" 6HF12 134-154 2800 263.8 252 305 86-136 115- Single
182 Stage Pump
27 1250 8" x 6" 6HF12 115-170 2950 263.8 252 305 100- 134- Single
160 215 Stage Pump
28 1250 8" x 6" 6HF12 121-179 3000 263.8 252 305 105- 141- Single
167 224 Stage Pump
29 1500 8" x 6" 6HF12 108-165 2950 263.8 252 305 100- 134- Single
160 215 Stage Pump
30 1500 8" x 6" 6HF12 114-174 3000 263.8 252 305 105- 141- Single
167 224 Stage Pump
31 1500 8" x 6" 6HF18 101-124 1800 214.5 395 436 122- 164- Single
165 220 Stage Pump
32 1500 8" x 6" 6HF21 100-140 1480 217.3 438 520 123- 165- Single
185 250 Stage Pump
33 2000 10" x 8HF13 120-146 2800 287.5 305 330 156- 209- Single
8" 192 257 Stage Pump
34 2000 10" x 8HF13 135-166 2950 287.5 305 330 182- 244- Single
8" 225 302 Stage Pump
15
35 2000 10" x 8HF13 138-173 3000 287.5 305 330 192- 257- Single
8" 236 316 Stage Pump
36 2000 10" x 8HF21 98-126 1480 210.2 455 520 141- 189- Single
8" 191 255 Stage Pump
37 2000 10" x 8HF17 110-140 1770 220.8 375 450 198- 266- Single
8" 260 350 Stage Pump
38 2500 10" x 8HF17 106-136 1770 220.8 375 450 198- 266- Single
8" 260 350 Stage Pump
16
7. UL Listed // FM Approved Curves
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
8. UL Listed // FM Approved GA Drawings
59
60
61
62
63
64
65
66
67
68
69
70
71
72
9. NFPA20 Fire Pumps Stack Chart
73
10. NFPA20 Selection Chart
PUMPSENSE Centrifugal Fire Pumps, Split Case, NFPA20 SELECTION CHART
Rated Net Max Impeller
Rated Pressure Range, Approx. Diameter, mm.
Sr. Size, Working Pump
Capacity, Model Speed,
No. in. Pressure, Type
gpm RPM
Meter psi psi Minimum Maximum
Two
1 150 3”X2.5” 2.5HFT9 80-140 115-200 2950 300 150 220 Stage
Pump
Two
2 2.5HFT12 55-232 78-330 2950 400 171 305 Stage
Pump
Single
3 90-143 130-203 2950 320 256 320 Stage
Pump
250
Single
4 4”X3” 3HF12 95-148 135-210 3000 320 256 320 Stage
Pump
Single
120-
5 170-212 3600 320 256 280 Stage
149
Pump
Single
6 92-143 130-203 2950 320 256 320 Stage
Pump
Single
7 4”X3” 3HF12 95-148 135-210 3000 320 256 320 Stage
Pump
Single
120-
8 170-212 3600 320 256 320 Stage
149
Pump
Single
9 62-98 88-139 2600 300 260 310 Stage
Pump
300
Single
10 73-114 104-162 2800 300 260 310 Stage
Pump
6”X4” 4HF12L
Single
11 82-127 116-180 2950 300 260 310 Stage
Pump
Single
12 84-131 120-187 3000 300 260 310 Stage
Pump
Two
120-
13 3”X2.5” 2.5HFT12 170-313 2950 400 230 305 Stage
220
Pump
Single
14 80-140 115-200 2950 320 256 320 Stage
Pump
Single
15 3HF12 84-144 120-205 3000 320 256 320 Stage
Pump
4”X3”
Single
112-
16 160-205 3600 320 256 278 Stage
144
Pump
Two
136-
17 3HFT11 194-327 2930 410 230 295 Stage
230
Pump
400
Single
18 59-94 84-134 2600 300 260 310 Stage
Pump
Single
19 70-110 99-157 2800 300 260 310 Stage
Pump
6”X4” 4HF12L
Single
20 78-123 111-175 2950 300 260 310 Stage
Pump
Single
21 81-128 115-182 3000 300 260 310 Stage
Pump
74
Single
22 80-140 115-200 2950 320 256 320 Stage
Pump
Single
23 4”X3” 3HF12 84-144 120-205 3000 320 256 320 Stage
Pump
Single
112-
24 160-205 3600 320 256 276 Stage
144
Pump
Single
25 450 57-93 81-132 2600 300 260 310 Stage
Pump
Single
26 67-109 96-155 2800 300 260 310 Stage
Pump
6”X4” 4HF12L
Single
27 76-122 108-173 2950 300 260 310 Stage
Pump
Single
28 79-126 113-179 3000 300 260 310 Stage
Pump
Single
29 80-140 115-200 2950 320 256 320 Stage
Pump
Single
30 4”X3” 3HF12 84-144 120-205 3000 320 256 320 Stage
Pump
Single
112-
31 160-205 3600 320 256 274 Stage
144
Pump
Single
32 4HF10 35-60 50-85 2950 185 180 230 Stage
Pump
Single
33 55-91 78-129 2600 300 260 310 Stage
Pump
Single
34 65-107 93-152 2800 300 260 310 Stage
Pump
4HF12L
Single
35 74-120 105-171 2950 300 260 310 Stage
Pump
500
Single
36 6”X4” 77-124 109-177 3000 300 260 310 Stage
Pump
Single
37 91-124 130-176 2600 300 305 350 Stage
Pump
Single
108-
38 153-206 2800 300 305 350 Stage
145
Pump
4HF13
Single
120-
39 171-230 2950 300 305 350 Stage
162
Pump
Single
124-
40 177-238 3000 300 305 350 Stage
167
Pump
Two
131-
41 4”X3” 3HFT11 187-320 2930 410 230 295 Stage
225
Pump
Two
200-
42 5"X3" 3HFTD14 284-469 2970 585 280 350 Stage
330
Pump
Single
43 56-86 79-122 2600 300 260 310 Stage
Pump
Single
44 66-103 94-147 2800 300 260 310 Stage
Pump
750 6”X4” 4HF12
Single
45 75-117 107-166 2950 300 260 310 Stage
Pump
Single
46 79-121 112-172 3000 300 260 310 Stage
Pump
75
Single
47 80-114 114-162 2600 300 305 350 Stage
Pump
Single
48 96-135 137-192 2800 300 305 350 Stage
Pump
4HF13
Single
109-
49 155-215 2950 300 305 350 Stage
151
Pump
Single
114-
50 162-224 3000 300 305 350 Stage
157
Pump
Single
51 5”X4” 4HF16 80-120 113-171 2350 270 316 395 Stage
Pump
Two
150-
52 213-327 1780 600 383 470 Stage
230
Pump
4HFT19
Two
210-
53 6”X4” 299-448 2100 600 383 470 Stage
315
Pump
Two
125-
54 4HFTD13 178-427 2950 550 230 350 Stage
300
Pump
Single
55 56-89 80-126 2600 260 252 310 Stage
Pump
Single
56 67-104 95-148 2800 260 252 310 Stage
Pump
6"X5" 5HF11
Single
57 75-117 107-167 2950 260 252 310 Stage
Pump
Single
58 78-122 111-173 3000 260 252 310 Stage
Pump
Single
135-
59 192-259 2950 355 320 370 Stage
182
Pump
6HF15
Single
127-
60 1000 180-235 2800 360 320 370 Stage
165
Pump
Two
160-
61 8”X6” 6HFTD12 227-348 2950 440 240 300 Stage
245
Pump
Single
120-
62 170-230 2950 325 300 355 Stage
162
Pump
6HF14K
Single
105-
63 150-210 2800 325 300 355 Stage
148
Pump
Two
240-
64 4HFT19 341-533 2300 600 383 470 Stage
375
Pump
6”X4”
Two
180-
65 4HFT14 256-427 2950 550 280 352 Stage
300
Pump
Single
66 6HF12 80-127 113-180 2950 275 245 305 Stage
Pump
Single
67 6HF13 90-150 128-213 2950 285 264 330 Stage
Pump
Single
110-
68 156-220 2950 315 300 355 Stage
155
Pump
1250 8”X6” 6HF14K
Single
113-
69 160-200 2800 325 300 355 Stage
141
Pump
Single
128-
70 6HF15 182-249 2950 355 320 370 Stage
175
Pump
Two
140-
71 6HFTD12 199-334 2950 440 240 300 Stage
235
Pump
76
Two
72 82-126 117-179 1480 490 390 465 Stage
Pump
Two
128-
73 6HFTD18 178-267 1800 490 390 465 Stage
188
Pump
Two
182-
74 259-381 2100 490 390 465 Stage
268
Pump
Single
75 6HF12 75-121 106-172 2950 275 245 305 Stage
Pump
Single
76 6HF13 90-145 128-206 2950 285 264 330 Stage
Pump
Single
77 6HF18 70-88 101-124 1800 140 395 436 Stage
Pump
Single
78 8”X6” 6HF20 75-120 107-171 1800 220 440 520 Stage
Pump
Single
79 1500 6HF21 70-102 100-145 1480 150 438 520 Stage
Pump
Two
120-
80 171-256 1800 490 390 465 Stage
180
Pump
6HFTD18
Two
178-
81 253-373 2100 490 390 465 Stage
262
Pump
Single
82 8”X8” 8HF12H 40-72 56-102 2350 200 300 340 Stage
Pump
Two
190-
83 8”X6” 6HFTD13 270-469 2950 550 270 334 Stage
330
Pump
Single
84 84-103 120-146 2800 300 305 330 Stage
Pump
Single
85 8HF13 95-117 135-166 2950 300 305 330 Stage
Pump
Single
86 97-122 138-173 3000 300 305 330 Stage
Pump
10”X8”
Single
87 8HF17 70-98 100-140 1800 155 375 450 Stage
Pump
Single
88 2000 8HF20 80-125 114-178 1800 280 430 515 Stage
Pump
Single
89 8HF21 70-91 100-130 1480 140 455 520 Stage
Pump
Two
120-
90 6HFTD21 170-284 1480 375 430 540 Stage
200
Pump
8”X6”
Two
140-
91 6HFTD12S 199-341 2950 505 264 330 Stage
240
Pump
Single
116-
92 10”X8” 8HF14 165-186 2950 305 320 340 Stage
131
Pump
Single
108-
93 12”X8” 8HF15 154-239 2950 350 305 380 Stage
168
Pump
Single
95 10”X8” 8HF17 75-96 106-136 1800 155 375 450 Stage
2500
Pump
Single
96 10”X8” 8HF20 75-120 107-171 1800 280 430 515 Stage
Pump
77
Single
120-
97 12”X8” 8HF15 171-228 2950 350 330 380 Stage
160
Pump
Single
98 52-83 74-118 1480 270 410 510 Stage
Pump
10HF20
Single
99 3000 14"X10" 80-122 114-174 1800 270 410 510 Stage
Pump
Single
100 10HF22 68-89 97-127 1480 300 490 561 Stage
Pump
Single
105-
101 12”X10” 10HF27 149-235 1480 440 560 690 Stage
165
Pump
Single
102 48-80 68-114 1480 270 410 510 Stage
Pump
10HF20
Single
103 4000 75-120 107-171 1800 270 410 510 Stage
Pump
14”X10”
Single
100-
104 142-186 1800 300 490 561 Stage
131
Pump
10HF22
Single
105 5000 95-125 135-178 1800 300 490 561 Stage
Pump
78
11. NFPA20 Curves
79
80
81
82
83
84
85
86
87
88
89
90
91
92
93
94
95
96
97
98
99
100
101
102
103
104
105
106
107
108
109
110
111
112
113
114
115
116
117
118
119
120
121
122
123
124
125
126
127
128
129
130
131
132
133
12. NFPA20 Fire Pumps GA Drawings
134
135
136
137
138
139
140
141
142
143
144
145
146
147
148
149
150
151
152
153
154
155
156
157
158
159
160
161
162
163
164
165
166
167
168
169
170
13. Sectional Drawings
171
172
173
174
175
176
14. Common GA and Dimensional Sheet
177
178
179
180
181
15. Flange Details
182
183
184
185
16. Material equivalence chart
186
17. Recommended spare parts
187