Control-Unit Keypad
Control-Unit Keypad
DESCRIPTION ! WARNING
The Control-Unit Keypad/Display is a replacement part used Use caution when connecting power: high-
to replace a faulty component. voltage and AC-powered circuits are present in
the control unit. Be sure to adequately ground
SUPPLIED PARTS the control unit to reduce the risk of electrical
• Kidde Fire Systems, Control-Unit Keypad/Display, shock.
P/N 76-600000-011 a) Disconnect the standby batteries and de-energize
the commercial AC line voltage.
REQUIRED TOOLS b) Slip on a wrist ground strap and clip the ground
• No. 2 Phillips Head Screwdriver. strap to an earth-ground in the enclosure. Do not
• Wrist Ground Strap with Clip work on the printed-circuit board (PCB) unless you
have established a common earth-ground potential
PROCEDURE among yourself, the enclosure, and the PCB.
1. How to Remove the Faulty Keypad/Display. c) Refer to Figure 1. Unscrew the four screws that
attach the keypad / display to its four nylon standoffs.
! WARNING Set the four screws aside.
Two different sources of power can be
connected to the control unit. Disconnect both d) Carefully separate the two headers on the rear, right-
sources of power and critical components such hand side of the keypad / display from the two sets
as control-heads for special extinguishing of mating pins attached to the printed-circuit board.
systems and addressable pilot relays e) Discard the old keypad / display.
controlling facility-power shutoff before
servicing the control unit. The control unit and
associated equipment may be damaged by
removing and/or inserting powered boards and
components, or by connecting cables, while the
control unit is energized.
Nylon Standoffs
Typ (4)
Ke
yp
ad
/D
isp
la Headers
y Mating Pins
Fastening Screws
Typ (4)