Product data sheet RE7MY13MW
Characteristics time delay relay 8 functions - 0.05..1 s - 240 V
AC DC - 2OC
Main
Range of product Zelio Time
Product or component Industrial timing relay
type
Contacts type and com- 2 C/O
position
Component name RE7
Time delay type A
C
D
Di
H
Qg
Qt
W
It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof.
Time delay range 0.05 s...300 h
[Us] rated supply volt- 24...240 V AC/DC 50/60 Hz
age
Complementary
Discrete output type Relay
Contacts material 90/10 silver nickel contacts
The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications.
Width pitch dimension 22.5 mm
Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein.
Voltage range 0.85...1.1 Us
Connections - terminals Screw terminals, clamping capacity: 2 x 2.5 mm² flexible without cable end
Screw terminals, clamping capacity: 2 x 1.5 mm² flexible with cable end
Tightening torque 0.6...1.1 N.m
Setting accuracy of time delay +/- 10 % of full scale
Repeat accuracy +/- 0.2 %
Temperature drift < 0.07 %/°C
Voltage drift < 0.2 %/V
Minimum pulse duration 20 ms
Reset time 50 ms
Maximum switching voltage 250 V AC/DC
Mechanical durability 20000000 cycles
[Ith] conventional free air thermal current 8A
[Ie] rated operational current <= 0.2 A DC-13 115 V at 70 °C conforming to IEC 60947-5-1/1991/VDE 0660
<= 0.1 A DC-13 250 V at 70 °C conforming to IEC 60947-5-1/1991/VDE 0660
<= 3 A AC-15 at 70 °C conforming to IEC 60947-5-1/1991/VDE 0660
<= 2 A DC-13 24 V at 70 °C conforming to IEC 60947-5-1/1991/VDE 0660
Minimum switching capacity 12 V/10 mA
Input voltage < 60 V Y1Z2 terminal(s)
< 60 V X1Z2 terminal(s)
Maximum switching current 1 mA Y1Z2 terminal(s)
1 mA X1Z2 terminal(s)
Input compatibility 3/4 wires sensors PNP/NPN without internal load, cable length: <= 50 m Y1Z2
terminal(s)
3/4 wires sensors PNP/NPN without internal load, cable length: <= 50 m X1Z2
terminal(s)
Potentiometer characteristic Linear 47 kOhm (+/- 20 %), 0.2 W, cable length: <= 25 m Z1Z2terminal(s)
Marking CE
Overvoltage category III conforming to IEC 60664-1
Mar 9, 2013
1
[Ui] rated insulation voltage 300 V between contact circuit and power supply CSA certified
300 V between contact circuit and control inputs CSA certified
250 V between contact circuit and power supply IEC certified
250 V between contact circuit and control inputs IEC certified
Supply disconnection value > 0.1 Uc
Operating position Any position without derating
Surge withstand 2 kV conforming to IEC 61000-4-5 level 3
Power consumption in VA 3.2 VA 110 V
2.5 VA 48 V
6 VA 240 V
2 VA 24 V
Power consumption in W 3.2 W 110 V
2 W 240 V
2 W 24 V
1 W 48 V
Peak current 0.001 kA for 30 s on energisation
Terminal description (15-16-18)OC_OFF
(25-26-28)OC_OFF
(A1-A2)CO
(X1)UNUSED
(Y1)UNUSED
(Z1)UNUSED
(Z2)UNUSED
Height 78 mm
Width 22.5 mm
Depth 80 mm
Product weight 0.15 kg
Environment
Immunity to microbreaks 3 ms
Standards EN/IEC 61812-1
Product certifications CSA
GL
UL
Ambient air temperature for storage -40...85 °C
Ambient air temperature for operation -20...60 °C
Relative humidity 15...85 % (3K3) conforming to IEC 60721-3-3
Vibration resistance 0.35 mm (f = 10...55 Hz) conforming to IEC 60068-2-6
Shock resistance 15 gn for 11 ms conforming to IEC 60068-2-27
IP degree of protection IP50 (housing)
IP20 (terminals)
Pollution degree 3 conforming to IEC 60664-1
Dielectric strength 2.5 kV
Non-dissipating shock wave 4.8 kV
Resistance to electrostatic discharge 8 kV (in air) conforming to IEC 61000-4-2 level 3
6 kV (in contact) conforming to IEC 61000-4-2 level 3
Resistance to electromagnetic fields 10 V/m conforming to IEC 61000-4-3 level 3
Resistance to fast transients 2 kV conforming to IEC 61000-4-4 level 3
Disturbance radiated/conducted CISPR 11 group 1 - class A
CISPR 22 - class A
Contractual warranty
Period 18 months
2
Product data sheet RE7MY13MW
Technical Description
Function A : Power on Delay Relay
Description
The timing period T begins on energisation. After timing, the output(s) R close(s). The second output can be either timed or instantaneous.
Function: 1 Output
Function: 2 Outputs
2 timed outputs (R1/R2) or 1 timed output (R1) and 1 instantaneous output (R2 inst.)
Function C : Off-Delay Relay with Control Signal
Description
After power-up and closing of the control contact C, the output R closes. When control contact C re-opens, timing T starts. At the end of the
timing period, the output(s) R revert(s) to its/their initial state. The second output can be either timed or instantaneous.
Function: 1 Output
Function: 2 Outputs
2 timed outputs (R1/R2) or 1 timed output (R1) and 1 instantaneous output (R2 inst.)
Function D : Symmetrical Flasher Relay (Starting Pulse Off)
Description
Repetitive cycle with two timing periods T of equal duration, with output(s) R changing state at the end of each timing period T.
The second output can be either timed or instantaneous.
Function: 1 Output
3
Function: 2 Outputs
2 timed outputs (R1/R2) or 1 timed output (R1) and 1 instantaneous output (R2 inst.)
Function Di : Symmetrical Flasher Relay (Starting Pulse On)
Description
Repetitive cycle with two timing periods T of equal duration, with output(s) R changing state at the end of each timing period T.
The second output can be either timed or instantaneous.
Function: 1 Output
Function: 2 Outputs
2 timed outputs (R1/R2) or 1 timed output (R1) and 1 instantaneous output (R2 inst.)
Function H : Interval Relay
Description
On energisation of the relay, timing period T starts and the output(s) R close(s). At the end of the timing period T, the output(s) R revert(s) to
its/their initial state. The second output can be either timed or instantaneous.
Function: 1 Output
Function: 2 Outputs
2 timed outputs (R1/R2) or 1 timed output (R1) and 1 instantaneous output (R2 inst.)
Function Qg: Star-Delta Timing
Description
Timing for star-delta starter with contact for switching to star connection.
Function: 1 Output
4
Function Qt: Star-Delta Timing
Description
Timing for star-delta starter with double On-delay period.
Function: 1 Output
Function W : Interval Relay with Control Signal Off
Description
After power-up and opening of the control contact, the output(s) close(s) for a timing period T.
At the end of this timing period the output(s) revert(s) to its/their initial state.
The second output can be either timed or instantaneous.
Function: 1 Output
Function: 2 Outputs
2 timed outputs (R1/R2) or 1 timed output (R1) and 1 instantaneous output (R2 inst.).
Legend
Relay de-energised
Relay energised
Output open
Output closed
C Control contact
G Gate
R Relay or solid state output
R1/ 2 timed outputs
R2
R2 The second output is instantaneous if the right position is selected
inst.
T Timing period
Ta Adjustable On-delay
Tr Adjustable Off-delay
U Supply
5
Product data sheet RE7MY13MW
Dimensions Drawings
Width 22.5 mm
Rail Mounting
Screw Fixing
6
Product data sheet RE7MY13MW
Connections and Schema
Internal Wiring Diagram
Recommended Application Wiring Diagram
Start on Energisation
1 Supply
2 12…48 V
3 24 V
Recommended Application Wiring Diagram
Start by External Control
1 Supply
2 12…48 V
3 24 V
Recommended Application Wiring Diagram
External Control of Partial Stop
1 Supply
2 12…48 V
3 24 V
Control of Several Relays
7
Control of several relays with a single external control contact
Connection of Potentiometer
Connection Precautions
WARNING
UNEXPECTED EQUIPMENT OPERATION
No galvanic isolation between supply terminals and control inputs.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
8
Product data sheet RE7MY13MW
Performance Curves
Performance Curves
A.C. Load Curve 1
Electrical durability of contacts on resistive loading millions of operating cycles
X Current broken in A
Y Millions of operating cycles
A.C. Load Curve 2
Reduction factor k for inductive loads (applies to values taken from durability curve 1).
X Power factor on breaking (cos ϕ)
Y Reduction factor k
Example: An LC1-F185 contactor supplied with 115 V/50 Hz for a consumption of 55 VA or a current consumption equal to 0.1 A and cos
ϕ = 0.3. For 0.1 A, curve 1 indicates a durability of approximately 1.5 million operating cycles. As the load is inductive, it is necessary to
apply a reduction coefficient k to this number of cycles as indicated by curve 2. For cos ϕ = 0.3: k = 0.6 The electrical durability therefore
6
becomes:1.5 10 operating cycles x 0.6 = 900 000 operating cycles.
D. C. Load Limit Curve
X Current in A
Y Voltage in V
1 L/R = 20 ms
2 L/R with load protection diode
3 Resistive load