1 Alpha Terrace - Heat Loss Calculation Report 5.12.2023

This document summarizes the radiator schedule and heat loss calculations for a building. It includes a table showing the required heat output and selected radiator model for each room. The total required output is 3404.1W and the total output provided by the radiators is 3533.4W. It also includes specifications for the building fabric U-values and calculates the hot water cylinder will reheat in 70 minutes.

Uploaded by

Daniel Tackie
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
18 views2 pages

1 Alpha Terrace - Heat Loss Calculation Report 5.12.2023

This document summarizes the radiator schedule and heat loss calculations for a building. It includes a table showing the required heat output and selected radiator model for each room. The total required output is 3404.1W and the total output provided by the radiators is 3533.4W. It also includes specifications for the building fabric U-values and calculates the hot water cylinder will reheat in 70 minutes.

Uploaded by

Daniel Tackie
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

Name of project - Radiator Schedule

Summary Table of Heat Emitters

Heat Pump Specified 5kW Vaillant aroTHERM plus & AI VWL


Outdoor design temperature for Heat Loss Calculation 55/6 A 230V S2
Heat pump output at outdoor design temperature (kW) -1.8 deg C
Internal room temperature 6.6 kW
21.0 deg C
Heating system design flow temperature 45.00 deg C
Radiator Downsizing Correction factor applied 0.30

Room Description Heat Load Heat Emitter Type Radiator Heat Rad Length Total Heat
Required Model No. Output x Height Output Emitter
(W) (W) (mm) (W) Duty %
Lounge 668.5 Stelrad_compact_horizontal_K2 143791 727.5 1400 - 600 727.5 109%
Dining Room 354.6 Stelrad_compact_horizontal_K2 143786 415.8 800 - 600 415.8 117%
Kitchen 341.5 Stelrad_compact_horizontal_K2 143784 311.7 600 - 600 311.7 91%
Store Room 265.3 Unheated
Landing 238.4 Stelrad_compact_horizontal_K2 143784 311.7 600 - 600 311.7 131%
Bedroom1 524.8 Stelrad_compact_horizontal_K2 143788 519.6 1000 - 600 519.6 99%
Bedroom2 425.5 Stelrad_compact_horizontal_K2 143788 519.6 1000 - 600 519.6 122%
Bedroom3 216.3 Stelrad_compact_horizontal_K2 143784 311.7 600 - 600 311.7 144%
Bathroom 369.2 Stelrad_compact_horizontal_K2 143786 415.8 800 - 600 415.8 113%

TOTAL 3404.1 3533.4 1082%

93 Dynevor Rd, London, N16 0DA


Next Step Heating Limited www.nextstepheating.co.uk, [email protected], 02081254864
Name of project - Radiator Schedule

Building Fabric Performance: U Values

Fabric Perfomance: U-Value


Fabric Description U-Value
Wall Solid masonry wall, Kingspan Kooltherrm K118 0.66 W/m2⋅K
Floor Floor + Insulation 0.7 W/m2⋅K
Roof Roof + Insulation 0.3 W/m2⋅K
Glazing Average glazing for whole window and glass doors 1.5 W/m2⋅K

Hot Water Cylinder Reheat Time Calculation


Size of Cylinder (l) 200 l
Heat Pump Size (kW) 6.0 kW
Target Stored Hot Water Tank Temperature (C) 50.00 C
Cold Water Temperature (C) 20 C
Delta T (C) 30.00 C
Reheat Tim (mins) 70 mins

93 Dynevor Rd, London, N16 0DA


Next Step Heating Limited www.nextstepheating.co.uk, [email protected], 02081254864