This document is a letter from KLH Engineers located in Fort Thomas, Kentucky discussing fire protection for a renovation project. It includes a legend describing sprinkler head types, notes on hazard occupancies, and general fire protection notes. The notes specify that renovated areas must be 100% sprinklered, all work must comply with NFPA 13 and building codes, and fire suppression work must be done by a licensed contractor.

Uploaded by

Ashar Shakir
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
134 views17 pages

MEP Drawings

This document is a letter from KLH Engineers located in Fort Thomas, Kentucky discussing fire protection for a renovation project. It includes a legend describing sprinkler head types, notes on hazard occupancies, and general fire protection notes. The notes specify that renovated areas must be 100% sprinklered, all work must comply with NFPA 13 and building codes, and fire suppression work must be done by a licensed contractor.

Uploaded by

Ashar Shakir
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 17

MECHANICAL/ELECTRICAL ENGINEERS

WWW.KLHENGRS.COM
06/25/19
1538 ALEXANDRIA PIKE, SUITE 11
FT. THOMAS, KENTUCKY 41075
800-354-9783
859-442-8050
859-442-8058 FAX

LEXINGTON, KENTUCKY
LOUISVILLE, KENTUCKY
COLUMBUS, OHIO
NEW YORK, NEW YORK

FIRE PROTECTION LEGEND


SYMBOL DESCRIPTION

SPRINKLER HEAD TYPES


N, X, D SPRINKLER TAG (NEW, EXISTING TO REMAIN, DEMOLITION)

CONCEALED WHITE PLATE SPRINKLER - MATCH EXISTING


GYMNASIUM
105 RECESSED PENDANT SPRINKLER - MATCH EXISTING

HAZARD OCCUPANCY

BY
LH LIGHT HAZARD OCCUPANCY

DATE
ACT ACT CEILING

GYP GYPSUM BOARD CEILING


X

X X

GENERAL FIRE PROTECTION NOTES

REVISIONS
LOBBY
101 A. RENOVATED AREAS SHALL BE 100% SPRINKLERED.
B. COORDINATE CLOSELY WITH OTHER TRADES. REFER TO ARCHITECTURAL DRAWINGS FOR
LH T CEILING TYPES.
X X C. ALL SPRINKLER WORK SHALL BE INSTALLED PER NFPA 13, BUILDING CODE, AND OWNER'S
INSURANCE CARRIER REQUIREMENTS.
ELEVATOR D. MAKE PROVISIONS FOR DRAINING AND PROVIDE INSPECTOR TESTS AS REQUIRED. ALL
DRAIN PIPING SHALL BE PIPED TO OUTSIDE OR INDIRECTLY TO SINK OR FLOOR DRAIN.
104 E. COORDINATE EXACT LOCATION OF PIPING AND HEADS WITH REFLECTED CEILING PLANS,
MECHANICAL AND ELECTRICAL DRAWINGS.
F. ALL HOSE VALVES AND FIRE DEPARTMENT CONNECTIONS SHALL MATCH LOCAL FIRE
FRONT DESK DEPARTMENT THREADS.
X X

REV
X 102 G. ALL FIRE SUPPRESSION WORK SHALL BE PERFORMED BY A FIRE PROTECTION
LH N CONTRACTOR LICENSED IN THE STATE OF OHIO.
X H. ALL SPRINKLER HEADS SHALL BE LOCATED IN CENTER OF CEILING TILE. PLUS OR MINUS
ONE HALF INCH

DS
06/26/2019

GRS
T I. SPRINKLER CONTRACTOR SHALL BE RESPONSIBLE FOR ALL CUTTING AND PATCHING FOR
X N N VESTIBULE SPRINKLER WORK IN ALL AREAS OF BUILDING. REFER TO SPECIFICATIONS.
X

PG.
J. ALL ARMOVER PIPING RELATED TO SPRINKLERS TO BE DEMOLISHED, SHALL HAVE ALL
100 PIPING REMOVED BACK TO THE OUTLET ON THE BRANCHLINE.

APPROVED BY:
LH K. WHEN MODIFYING EXISTING SPRINKLER SYSTEMS, SPRINKLER CONTRACTOR SHALL

CHECKED BY:
X

DRAWN BY:
MAINTAIN THE INTEGRITY OF THE EXISTING SPRINKLER ZONES. COORDINATE WITH NEW

T
FIRE RATING PLANS AS NEEDED.
L. FIRE PROTECTION CONTRACTOR IS REQUIRED TO RAISE/REWORK ALL EXISTING PIPING AS

DATE:

F.B.
NO.
NEEDED TO ACCOMMODATE NEW CEILINGS AND HIGHER CEILING HEIGHTS AS APPLICABLE.

X X N N

10990 THORNVIEW DRIVE, CINCINNATI OHIO 45241


SHARONVILLE COMMUNITY CENTER
21T-005 - SPRINKLER NOTES
FITNESS ROOM
SCALE: NONE

FIRE PROTECTION UPPER LEVEL


103

LOBBY AND FITNESS ROOM RENOVATION


LH
X X X X

EXISTING SPRINKLERS IN THIS AREA


TO BE REUSED AND REINSTALLED IN
NEW FITNESS ROOM CEILING.

X X X X

X
X X X

AREA OF WORK

FP UPPER LEVEL - RCP


NTS N
6/24/2019 4:46:12 PM

SCALE: As indicated

HORZ:

VERT:

CONTRACT NO:

180881
KEY PLAN SHEET

NTS
F-101
MECHANICAL/ELECTRICAL ENGINEERS
WWW.KLHENGRS.COM
06/25/19
1538 ALEXANDRIA PIKE, SUITE 11
FT. THOMAS, KENTUCKY 41075
800-354-9783
859-442-8050
859-442-8058 FAX

LEXINGTON, KENTUCKY
LOUISVILLE, KENTUCKY
COLUMBUS, OHIO
NEW YORK, NEW YORK

MECHANICAL LEGEND
SYMBOL DESCRIPTION

PLAN-VIEW LINE TYPES


WORK SHOWN FADED INDICATES EXISTING WORK TO REMAIN OR NEW WORK BY
OTHERS AS APPLICABLE
GYMNASIUM
105 WORK SHOWN BOLD-DASHED INDICATES SELECTIVE DEMOLITION WORK

WORK SHOWN BOLD-CONTINUOUS INDICATES NEW WORK

MECHANICAL MISCELLANOUS
CONNECT TO EXISTING (FIELD VERIFY EXISTING UTILITY SERVICE TYPE, PRIOR TO
MAKING CONNECTION)

X MECHANICAL STATS & SENSORS

BY
TS TEMPERATURE SENSOR

X X

DATE
T LOW VOLTAGE THERMOSTAT

T LOW VOLTAGE THERMOSTAT WITH LOCKABLE GUARD


LOBBY
101 MECHANICAL AIR DEVICES
X X
SR SUPPLY REGISTER

ELEVATOR

REVISIONS
RR RETURN REGISTER
104

ER EXHAUST REGISTER

X X
SG SUPPLY GRILLE

X RETURN GRILLE
D RG

CD CEILING DIFFUSER
X X VESTIBULE
D
100

REV
CD-10"Ø 2'x2' SQUARE CEILING DIFFUSER WITH 10" NECK
X
RCD ROUND CEILING DIFFUSER

DS
06/26/2019

GRS
LINEAR SLOT DIFFUSER

PG.
D D
MECHANICAL DUCTWORK

APPROVED BY:
X X

CHECKED BY:
DRAWN BY:
SCOPE OF WORK
UP SUPPLY DUCT WITH ELBOW TURNED UP

DATE:

F.B.
NO.
DN SUPPLY DUCT WITH ELBOW TURNED DOWN
DEMOLISH ALL ARMOVERS AND

FIRE PROTECTION DEMOLITION UPPER LEVEL


ASSOCIATED PIPING OF HEADS TO BE UP RETURN DUCT WITH ELBOW TURNED UP
D DEMOLISHED BACK TO THE OUTLET
ON THE BRANCHLINE.
DN RETURN DUCT WITH ELBOW TURNED DOWN
X X FITNESS ROOM X X
103

10990 THORNVIEW DRIVE, CINCINNATI OHIO 45241


SHARONVILLE COMMUNITY CENTER
UP EXHAUST DUCT WITH ELBOW TURNED UP

DN EXHAUST DUCT WITH ELBOW TURNED DOWN

LOBBY AND FITNESS ROOM RENOVATION


EXISTING SPRINKLERS IN THIS AREA 24X12 SA SUPPLY DUCT
TO BE REUSED AND REINSTALLED IN
NEW FITNESS ROOM CEILING.
24X12 RA RETURN DUCT

X X X X EXHAUST DUCT
24X12 EA

24X12 OA OUTSIDE AIR DUCT

1" LINED DUCTWORK

FLEXIBLE DUCTWORK CONNECTION

BRANCH TAKEOFF

X 24"/12" RA OVAL DUCT

X X X
REDUCER, CONCENTRIC

REDUCER, NONCONCENTRIC

FD UPPER LEVEL - RCP DUCT FLEX CONNECTOR

NTS
N
AREA OF WORK
6/24/2019 4:46:18 PM

SCALE: As indicated

HORZ:

VERT:

CONTRACT NO:

KEY PLAN 180881


SHEET
NTS
FD101
MECHANICAL/ELECTRICAL ENGINEERS
WWW.KLHENGRS.COM
06/25/19
1538 ALEXANDRIA PIKE, SUITE 11
FT. THOMAS, KENTUCKY 41075
800-354-9783
859-442-8050
859-442-8058 FAX

LEXINGTON, KENTUCKY
LOUISVILLE, KENTUCKY
COLUMBUS, OHIO
NEW YORK, NEW YORK

KEYED NOTES
H3 BID ALTERNATE IS TO CONNECT NEW VAV BOX TO EXISTING DUCTWORK,
ASSOCIATED HOT WATER PIPING AND CONTROL VALVE, AND EXISTING
JOHNSON CONTROLS BUILDING AUTOMATION SYSTEM.
H4 EXISTING VAV BOX TO REMAIN. CLEAN AND VERIFY PROPER OPERATION.
SERVICE VAV BOX (REPLACE EXISTING DAMPER ACTUATOR, FAN, AND
BAS CONTROLLER) BY A QUALIFIED PROFESSIONAL AS REQUIRED.
H5 PROVIDE AIR DEVICE IN FITNESS ROOM TO MATCH EXISTING.

420 CFM 420 CFM 420 CFM 420 CFM GYMNASIUM


105

515 CFM

BY
515 CFM

DATE
515 CFM

A
"S
18
515 CFM

"x
24
VFP-202B
H4

375 CFM 14"x14" SA LOBBY

24"x18" SA
101

REVISIONS
24"x18" SA
375 CFM 330 CFM

16"ø SA
VFP-202C
T
VFP-202A
330 CFM
H4 H3
ELEVATOR 16"ø SA H3 H4 330 CFM
104
FRONT DESK VFP-202C
102

SA

REV
A H3 H4
"S

12"x12" RA


A
"S

16
12

18 VFP-202D RELOCATED
"x
40

VFP-202D
"x
TRANSFER
20

DS
06/26/2019

MVA
T 200 CFM
24"x18" SA VESTIBULE
240 CFM
100

PG.
H4
240 CFM VFP-201 200 CFM

APPROVED BY:
CHECKED BY:
12"x48" RR
155 CFM 155 CFM

DRAWN BY:
36"x12" SA

T
240 CFM VFP-201

DATE:
SA

F.B.
NO.
16"x5" SA


10

155 CFM 155 CFM


H5
DUCTWORK AND AIR BALANCE
36"x12" SA 240 CFM MODIFICATIONS THIS AREA ARE LIMITED TO

MECHANICAL DUCTWORK UPPER LEVEL


ADDITION OF NEW VFP-202D AIR DEVICES
240 CFM
FITNESS ROOM IN FITNESS ROOM EXPANSION.

10990 THORNVIEW DRIVE, CINCINNATI OHIO 45241


SHARONVILLE COMMUNITY CENTER
103

LOBBY AND FITNESS ROOM RENOVATION


24"x10" SA

155 CFM 155 CFM


24"x12" SA

T
26"x10" SA
VFP-207A/B VFP-207A
115 CFM
36"x24" RA

115 CFM

H4
155 CFM
8"x14" SA
8"x8" SA

115 CFM 155 CFM


115 CFM 115 CFM 155 CFM

24"x12" SA 155 CFM


115 CFM 24"x12" SA
115 CFM 115 CFM 155 CFM
12"x10" SA
8"x14" SA
8"x8" SA

155 CFM
115 CFM
H4 VFP-207B
115 CFM 115 CFM

26"x10" SA 155 CFM 155 CFM


115 CFM

AREA OF WORK

HV UPPER LEVEL - FLOORPLAN - DEFAULT


NTS N
6/25/2019 11:52:20 AM

SCALE: As indicated

HORZ:

VERT:

CONTRACT NO:

KEY PLAN 180881


SHEET
NTS
M-101
MECHANICAL/ELECTRICAL ENGINEERS
WWW.KLHENGRS.COM
06/25/19
1538 ALEXANDRIA PIKE, SUITE 11
FT. THOMAS, KENTUCKY 41075
800-354-9783
859-442-8050
859-442-8058 FAX

LEXINGTON, KENTUCKY
LOUISVILLE, KENTUCKY
COLUMBUS, OHIO
NEW YORK, NEW YORK

BY
DATE
5
6 1
4
3
4

REVISIONS
2 12
KEYED NOTES: 7

INSULATION 1. SUSPEND FROM STRUCTURE WITH


1 7 GALVANIZED THREADED HANGER
8 RODS. RODS TO HAVE VIBRATION 8
9 ISOLATORS UNLESS FAN AND MOTOR
MAIN
ARE INTERNALLY ISOLATED
SUPPLY
3 2. INSULATED FLEXIBLE INLET DUCT WITH
DUCT

REV
MAXIMUM LENGTH OF 24" 9
3. ELECTRIC OR HOT WATER COIL
4 2 4. FLEXIBLE DUCT CONNECTION
8 5. ACOUSTICAL DUCT LINER THROUGH

DS
06/26/2019

MVA
2 GENERAL NOTES: FIRST ELBOW OR FIRST TAKE-OFF
10 2
UNLESS SPECIFIED OTHERWISE
5 6 1. OMIT FLEX DUCT ON DISTRIBUTION 6. SPACE SUPPLY DUCT-TRANSITION TO

PG.
SYSTEMS THAT PENETRATE 1-HR FIRE 11
SIZE SHOWN ON PLAN
BARRIERS. REFER TO ARCHITECTURAL

APPROVED BY:
7. ELECTRIC COIL SIDE HINGED TERMINAL
KEYED NOTES:

CHECKED BY:
PLANS FOR LOCATIONS OF FIRE BARRIERS. BOX

DRAWN BY:
8. INTERNAL TURNING VANES OR BAFFLE
1. MAXIMUM LENGTH OF INSUL. FLEX DUCT6. SECURE TO CEILING PER MANUFACTURER'S TO ASSURE EVEN AIRFLOW ACROSS
EQUALS 5 FEET. FLEX NOT PERMITTED IN

DATE:
RECOMMENDATIONS AND PER CEILING FINISH. HEATING COIL

F.B.
NO.
INACCESSIBLE CEILINGS PROVIDE GRID CLIPS PER MFG'R REQUIREMENTS. 9. FILTER FRAME
2. INSULATED DUCT, COLLAR AND
DIFFUSER BY HVAC CONTRACTOR
PROVIDE FRAMING FOR DRYWALL
INSTALLATION.
10. PLENUM AIR INLET
11. CONTROL BOX. PROVIDE 36"
GENERAL NOTES:
3. SCOOP 7. HANGER, SECURE TO STRUCTURE AND CLEARANCE TO SIDE. PROVIDE ACCESS A. OMIT FLEX DUCT ON DISTRIBUTION
4. SPIN IN FITTING WITH MANUAL VOLUME DUCTWORK PANEL IF ABOVE INACCESSIBLE CEILING SYSTEMS THAT PENETRATE 1-HR FIRE
DAMPER 8. PEEL BACK INSULATION AND PROVIDE STRAPPING 12. SHEET METAL DUCT INTO VAV BOX, BARRIERS. REFER TO ARCHITECTURAL
5. INTERNAL BUTTERFLY DAMPER FOR AND SHEET METAL SCREWS AT FLEX CONNECTION MINIMUM LENGTH OF 3 TIMES INLET PLANS FOR LOCATIONS OF FIRE
DRYWALL APPLICATIONS ONLY. TO DUCT. THEN PROVIDE STRAPPING AROUND DUCT DIAMETER BARRIERS.
(PROVIDE KEY FOR ADJUSTMENT)

10990 THORNVIEW DRIVE, CINCINNATI OHIO 45241


INSULATION.

SHARONVILLE COMMUNITY CENTER


9. SUPPORT FLEX TO PREVENT COLLAPSING

LOBBY AND FITNESS ROOM RENOVATION


233713.00-04 - DIFFUSER INSTALLATION TYPICAL 233613.00-03 - SERIES FAN POWERED VAV BOX
SCALE: NONE SCALE: NONE

MECHANICAL - DETAILS
GENERAL NOTES: VAV KEYED NOTES:
TERMINAL DEVICE
1. PROVIDE SPLITTER DAMPER AIR FLOW 1. 20 GAUGE DOUBLE SHEET
(SD) AT ALL MAIN BRANCH METAL AIR FOIL FULL DEPTH OF
TAKEOFFS MAIN DUCT UP TO 12" WIDE
2 4 BRANCHES 18 GAUGE ON WIDER
2. PROVIDE MANUAL VOLUME

BRANCH
DAMPERS AT ALL BRANCH BRANCHES
TAKEOFFS 2. MAIN DUCT
3 3. GALVANIZED 3/16" ROD
3. PROVIDE MINIMUM 3 TIMES MVD 1
STRAIGHT INLET DIAMETER CD (CEILING 4. VENTLOCK NO. 600-3 DAMPER
BRANCH BLADE, BRACKET & LOCKING
TO ALL VAV TERMINAL DIFFUSER)
DEVICES BALL JOINT WITH 1/4"Ø
AIR AIR
4. DAMPER NOT REQUIRED MAIN BRANCH MVD 5 5 GALVANIZED OPERATOR PAD
FLOW FLOW
AT TERMINAL DEVICE 5. BRANCH MAIN DUCT
TAKEOFF 6. DOUBLE THICKNESS TURNING
MVD SD VANES (TYPICAL)
5. ALL MANUAL DAMPERS
SHALL BE LOCATED IN AN RR (RETURN 6 7. 3" RADIUS MINIMUM
BRANCH
ACCESSIBLE CEILING. REGISTER)
PROVIDE ACCESS PANEL AS MVD
DUCT TEE
MVD 2
REQUIRED

MAIN BRANCH
BRANCH
AIR AIR
SR BRANCH ER (EXHAUST FLOW FLOW
(SUPPLY REGISTER) REGISTER)

MVD

3 4

BRANCH
7
MAIN BRANCH
1
SD MVD
SD LD AIR
(LINEAR DIFFUSER) FLOW
5

AIR AIR
6/25/2019 11:46:22 AM

DUCT MAIN DUCT MAIN


FLOW FLOW MAIN BRANCH SCALE: 1/8" = 1'-0"

HORZ:

VERT:
233300.00-01 - MANUAL DAMPER DETAIL CONTRACT NO:

SCALE: NONE
180881
SHEET

M-501
MECHANICAL/ELECTRICAL ENGINEERS
WWW.KLHENGRS.COM
06/25/19
1538 ALEXANDRIA PIKE, SUITE 11
FT. THOMAS, KENTUCKY 41075
800-354-9783
859-442-8050
859-442-8058 FAX

LEXINGTON, KENTUCKY
LOUISVILLE, KENTUCKY
COLUMBUS, OHIO
NEW YORK, NEW YORK

HVAC ACCESSORIES
ACCESSORIES:
1. MOTOR DAMPER 5. INTAKE HOOD 9. ACCESS DOOR 13. FACE/BYPASS DAMPER 17. DUCT FLANGES 21. ECON POWERED EXHAUST
2. ECONOMIZER 6. VIBRATION ISOLATION 10. FLEX CONNECTIONS 14. CONDENSATE PUMP 18. BASE RAIL 22. ECON BAROMETRIC RELIEF
3. ROOF CURB 7. FLAT FILTER 11. MOUNTING COLLAR 15. MOTOR GUARD 19. HUMIDIFIER 23. HOT GAS REHEAT COIL
4. HAIL GUARDS 8. FILTER/MIXING BOX 12. HOT GAS BYPASS 16. GREASE TRAP 20. CO2 SENSORS 24. SHAFT GROUNDING BRUSHES

HVAC VENTILATION SCHEDULE


NATURAL
NUMBER NAME AREA LEVEL CEILING HEIGHT AIR CHGS OA CHGS PEOPLE RED OA PER PERSON OA PER SQ FT. REQ SUP ACT SUP REQ OA ACT OA ACT RET ACT EXH CRIT OA PRESSURE PCT OPERABLE VENTILATION
100 VESTIBULE 134 SF UPPER LEVEL 14' - 0 27/32" 0 0 0 0 0 379 400 53 56 400 0 0 E 0
101 LOBBY 1960 SF UPPER LEVEL 14' - 8 9/32" 0 0 10 7.5 0.06 0 0 0 0 0 0 0 E
102 FRONT DESK 167 SF UPPER LEVEL 15' - 4" 0 0 3 7.5 0.06 186 200 26 28 200 0 0.2 E 0
103 FITNESS ROOM 2848 SF UPPER LEVEL 10' - 0 1/4" 0 0 30 20 0.06 3950 4190 553 587 4190 0 0.23 E 0
TOTAL 5108 SF

BY
DATE
HVAC ELECTRICAL COORDINATION SCHEDULE
ABBREVIATIONS CONTRACTOR TYPE MOTOR CONTROL TYPE CONTROL TYPE
DC LOCAL DISCONNECT EC ELECTRICAL CONTRACTOR CS COMBINATION STARTER TC TIMECLOCK
MC MOTOR CONTROL (POWER) EX EXISTING MCC MOTOR CONTROL STARTER CPT CONTROL POWER TRANSFORMER
SD DUCT SMOKE DETECTOR FC FIRE PROTECTION CONTRACTOR MG MAGNETIC STARTER OR CONTACT BAS BUILDING AUTOMATION SYSTEM
CN CONTROLS GC GENERAL CONTRACTOR MS MANUAL STARTER LOW LOW VOLTAGE CONTROLS
TS TOGGLE SWITCH HC HVAC CONTRACTOR VFD VARIABLE FREQUENCY DRIVE LINE LINE VOLTAGE CONTROLS
C/B H.A.C.R. CIRCUIT BREAKER AT SOURCE PANELBOARD MFR MANUFACTURER MSR MANUAL STARTER W/ CONTROL RELAY RLINE REVERSE ACTING LINE VOLTAGE THERMOSTAT
FUSE FUSE AT LOCAL DISCONNECT (VERIFY FIELD RATING) PC PLUMBING CONTRACTOR OV OVERCURRENT PROTECTION MAN MANUAL
FLA OPERATING FULL LOAD AMPS OR OWNER OR OTHERS FA FIRE ALARM

REVISIONS
MCA MINIMUM CIRCUIT AMPACITY CO CARBON MONOXIDE SENSOR
CP CORD AND PLUG CONNECTION INT INTEGRAL TO EQUIPMENT

AVAILABLE
FAULT CURRENT
EQUIPMENT MARK DESCRIPTION VOLTS (V) PHASE EMERGENCY BHP (HP) HP (HP) HTG (kW) WATTS FLA (A) MCA (A) OCP (A) DC TYPE DC FURN DC INST DC WIRE MC TYPE MC FURN MC INST MC WIRE CN TYPE CN FURN CN INST CN WIRE SD TYPE (A)
VFP-202A FAN POWERED VAV BOX 277 1 .75 0 4.6 EC EC EC MG MFR MFR MFR BAS HC HC HC 1680
VFP-202C FAN POWERED VAV BOX 277 1 .33 0 2.6 EC EC EC MG MFR MFR MFR BAS HC HC HC 1170
VFP-202D FAN POWERED VAV BOX 277 1 .33 0 2.6 EC EC EC MG MFR MFR MFR BAS HC HC HC 1498

REV
HVAC AIR TERMINAL UNIT SCHEDULE

DS
06/26/2019

MVA
Equipment shall be braced and labeled by the equipment manufacturer to withstand the minimum scheduled available fault current value for listed equipment.

PG.
EQUIPMENT AVAILABLE
MARK DESCRIPTION DUCT CONN (in) LOCATION STATUS FED FROM HEIGHT (ft) MANUFACTURER MODEL EMERGENCY VOLTS PHASE HP (hp) MAX CFM (cfm) MIN CFM (cfm) HMIN CFM (cfm) MBH (mbh) EAT (Deg F) HW GPM (gpm) EWT (Deg F) FLA (amps) FAULT CURRENT SHEET NUMBER

APPROVED BY:
CHECKED BY:
VFP-202A FAN POWERED VAV BOX 16 TITUS DQTS 277 1 .75 2810 2565 2565 67 70 5 180 4.6 1680

DRAWN BY:
VFP-202C FAN POWERED VAV BOX 16 TITUS DQTS 277 1 .33 990 990 990 38 70 2 180 2.6 1170
VFP-202D FAN POWERED VAV BOX 16 TITUS DQTS 277 1 .33 1300 1300 1300 42 70 2 180 2.6 1498

DATE:

F.B.
NO.
Control Sequences

1. Fan-Powered VAV – Parallel/Variable Flow (Fitness Room VAV Boxes)


a. Provide a three-way, failsafe open, modulating control valve for hot water reheat coils.
b. On a call for cooling, control valve shall shut and fan shall de-energize. On a further call for cooling, modulate the primary air damper open to satisfy room temperature.
c. On a call for heat, VAV primary air damper shall modulate down to minimum setpoint position. On a further call for heating, energize the fan. On a further call for heating, hot water
control valve shall open and modulate to maintain space temperature.

10990 THORNVIEW DRIVE, CINCINNATI OHIO 45241


SHARONVILLE COMMUNITY CENTER
d. Provide supply air temperature sensor tied to unit controller.

2. Fan-Powered VAV – Series/Constant Flow (Lobby VAV Boxes)

LOBBY AND FITNESS ROOM RENOVATION


a. Provide a three-way, failsafe open, modulating control valve for hot water reheat coils.
b. On a call for cooling, control valve shall shut and ECM controller shall modulate the fan off. On a further call for cooling, modulate the primary air damper open to satisfy room

MECHANICAL - SCHEDULES
temperature.
c. On a call for heat, VAV primary air damper shall modulate down to minimum setpoint position. On a further call for heating, ECM controller shall modulate the fan on. On a further
call for heating, hot water control valve shall open and modulate to maintain space temperature.
d. Provide supply air temperature sensor tied to unit controller.
6/25/2019 11:46:27 AM

SCALE:

HORZ:

VERT:

CONTRACT NO:

180881
SHEET

M-601
MECHANICAL/ELECTRICAL ENGINEERS
WWW.KLHENGRS.COM
06/25/19
1538 ALEXANDRIA PIKE, SUITE 11
FT. THOMAS, KENTUCKY 41075
800-354-9783
859-442-8050
859-442-8058 FAX

LEXINGTON, KENTUCKY
LOUISVILLE, KENTUCKY
COLUMBUS, OHIO
NEW YORK, NEW YORK

KEYED NOTES
H1 EXISTING FITNESS ROOM AIR DEVICES TO BE REUSED AND INSTALLED IN
NEW FITNESS ROOM CEILING.
H2 BID ALTERNATE IS TO DEMOLISH EXISTING VAV BOX. EXISTING INLET
DUCTWORK, DOWNSTREAM DUCTWORK, ASSOCIATED HOT WATER
PIPING, AND CONTROL VALVES TO REMAIN FOR RECONNECTION TO NEW
VAV BOX.

GYMNASIUM
105

BY
DATE
REVISIONS
LOBBY
101
T

H2
ELEVATOR H2
104

FRONT DESK
102

REV
H2

DS
06/26/2019

MVA
VESTIBULE

PG.
100
RELOCATE

APPROVED BY:
CHECKED BY:
12"x12"

DRAWN BY:
TRANSFER

DATE:

F.B.
NO.
MECHANICAL DEMOLITION UPPER LEVEL
FITNESS ROOM

10990 THORNVIEW DRIVE, CINCINNATI OHIO 45241


SHARONVILLE COMMUNITY CENTER
103

LOBBY AND FITNESS ROOM RENOVATION


T

H1
H1

AREA OF WORK

HD UPPER LEVEL - FLOORPLAN - DEFAULT


NTS N
6/25/2019 11:46:33 AM

SCALE: As indicated

HORZ:

VERT:

CONTRACT NO:

KEY PLAN 180881


SHEET
NTS
MD101
MECHANICAL/ELECTRICAL ENGINEERS
WWW.KLHENGRS.COM 06/25/19
1538 ALEXANDRIA PIKE, SUITE 11
FT. THOMAS, KENTUCKY 41075
800-354-9783
859-442-8050
859-442-8058 FAX

LEXINGTON, KENTUCKY
LOUISVILLE, KENTUCKY
COLUMBUS, OHIO
NEW YORK, NEW YORK

ELECTRIC LEGEND ELECTRIC LEGEND


SYMBOL DESCRIPTION SYMBOL DESCRIPTION

GENERAL ELECTRICAL INSTALLATION NOTES LIGHTING AND LIGHTING CONTROLS SINGLE LINE DIAGRAM
A. CODE COMPLIANCE: PROVIDE ALL ELECTRICAL WORK COMPLIANT WITH ALL PREVAILING CODES. LUMINAIRE (REFER TO THE LUMINAIRE SCHEDULE) ELECTRIC UTILITY COMPANY METER
M
B. LISTINGS: PROVIDE MATERIALS, COMPONENTS AND ASSEMBLED COMPONENTS WITH LISTINGS AND NOTE THAT OTHER SHAPES MAY ALSO BE USED TO REPRESENT LUMINAIRES
LABELS FROM A NATIONALLY RECOGNIZED TESTING LABORATORY (NRTL), MANUFACTURED, LISTED PANEL

AND LABELED FOR THEIR INTENDED USE. SHADED LUMINAIRES DENOTE THOSE CONNECTED TO EMERGENCY OR STANDBY POWER AS APPLICABLE NAME ELECTRICAL PANELBOARD OR DISTRIBUTION BOARD
C. RATED BUILDING SURFACES: PROVIDE LISTED FIRE-RATED WRAPS AROUND ALL RECESSED OUTLET, (UNSWITCHED LUMINAIRES ARE EGRESS LIGHTS AND/OR NIGHT-LIGHTS THAT OPERATE 24/7)
DEVICE AND EQUIPMENT BOXES IN FIRE/SMOKE RATED WALLS, CEILINGS AND FLOORS TO MEET OR
EXCEED THE RESPECTIVE FIRE/SMOKE RATING OF THE SURFACE. WALL SINGLE / DOUBLE SIDED EXIT SIGN ELECTRICAL SWITCHBOARD OR SWITCHGEAR
D. RATED PENETRATIONS: SEAL ALL PENETRATIONS THROUGH FIRE-RATED AND/OR SMOKE-RATED MOUNT CONNECT AHEAD OF SWITCHING & CONFIGURE ARROWS TO INDICATE DIRECTION OF EGRESS TRAVEL
MEMBRANES (FLOORS, WALLS, CEILINGS, ETC.) USING SEALANT PRODUCTS THAT MEET OR EXCEED A NL A = LUMINAIRE TYPE, NL = NIGHT-LIGHT (UNSWITCHED), a = SWITCHING DESIGNATION,
E.
THE RATING OF THE RESPECTIVE MEMBRANE.
GANGED DEVICES: INSTALL WIRING DEVICES GANGED WHEREVER POSSIBLE FOR INSTANCES WHERE a EL EL = EGRESS LUMINAIRE (ILLUMINATES PATH OF EGRESS, ON ALL TIMES SPACE IS OCCUPIED) WIRE / CABLE / RACEWAY
THEY ARE SHOWN TOGETHER. THIS INCLUDES LOCATIONS ABOVE COUNTERS AND WORK SURFACES BRANCH CIRCUIT HOME RUN WITH PANEL NAME AND CIRCUIT NUMBER(S)
LIGHTING SWITCH (KEYS: 2 = 2-POLE, 3 = 3-WAY, 4 = 4-WAY, D=DIMMER, K=KEYED, LV = LOW VOLTAGE LPA-1,3
WHERE APPLICABLE.
M = MOMENTARY-CONTACT 1PDT W/CENTER-REST, P = SWITCH W/PILOT LIGHT, T = TIMER SWITCH)
F. OUTLET BOXES NEAR CORNERS: INSTALL WALL-MOUNTED SWITCHES, CONTROLS, RECEPTACLES,
OUTLETS, ETC. AT LEAST 6 INCHES FROM WALL CORNERS. CABLING / RACEWAY INSTALLED CONCEALED IN WALLS OR ABOVE CEILING
RECEPTACLES AND MISCELLANEOUS OUTLETS

BY
G. CONCEALMENTS: CONCEAL ALL CONDUIT DROPS AND RISES WITHIN WALLS, AND PROVIDE FLUSH-
MOUNTED WALL OUTLET BOXES UNLESS OTHERWISE INDICATED.
H. DOCUMENTS OF OTHER TRADES: REVIEW DOCUMENTS OF OTHER TRADES, INCLUDING SINGLE ("SIMPLEX"), DUPLEX, AND DOUBLE DUPLEX ("QUAD") RECEPTACLE RESPECTIVELY FEEDER BUSWAY
ARCHITECTURAL, PRIOR TO SUBMITTING A BID. PROVIDE ELECTRICAL WORK FOR EQUIPMENT,

DATE
DEVICES, ETC. OF OTHER TRADES AS REQUIRED TO RENDER THEM FULLY OPERATIONAL. REFER TO
ARCHITECTURAL ELEVATIONS FOR INTENDED LOCATIONS AND MOUNTING HEIGHTS FOR EQUIPMENT TYPE FLOOR OUTLET - POWER AND / OR TECHNOLOGY J FLUSH MOUNTED JUNCTION BOX OR PULL BOX AS APPLICABLE FOR APPLICATION
AND OUTLETS, ETC. PRIOR TO COMMENCING WITH ANY RELATED ROUGH-IN WORK.
I. SCHEMATIC REPRESENTATIONS: CIRCUITING WORK SHOWN ON DRAWINGS IS FOR SCHEMATIC
GENERAL GRAPHIC REPRESENTATION ONLY. DETERMINE SPECIFICS IN FIELD (POINT-TO-POINT H C RECEPTACLE ATTRIBUTES SURFACE RACEWAY WITH INTEGRAL RECEPTACLES ("PLUGSTRIP")
ROUTING, HOME-RUN LOCATIONS, METHODS OF CONCEALMENT, ETC.). LOCATIONS AND ROUTING 42" = MOUNT RECEPTACLE AT THIS HEIGHT ABOVE GRADE / FINISHED FLOOR
INDICATED ON PLANS ARE SCHEMATIC AND DIAGRAMMATIC IN NATURE. LAYOUT AND INSTALL ALL C = INSTALL ABOVE COUNTER AND BACKSPLASH
T 42" W
ELECTRICAL WORK IN STRICT COMPLIANCE WITH CHAPTER 1, PART II, ARTICLE 110.26 OF THE LATEST
ADOPTED EDITION OF THE NATIONAL ELECTRICAL CODE (NFPA 70).
H = INSTALL RECEPTACLE HORIZONTALLY
L = LIT (PROVIDE ILLUMINATED FACE OR INDICATOR LIGHT TO INDICATE THERE IS POWER TO RECEPTACLE)
ABBREVIATIONS
J. HOME-RUN DESIGNATIONS: HOME-RUN DESIGNATIONS INDICATED ON PLANS ARE SCHEMATIC SW L SW = SPLIT WIRED
DESIGNATIONS ONLY. DETERMINE EXACT CIRCUIT ASSIGNMENTS IN FIELD BASED ON FIELD T = TAMPER-RESISTANT (R) RELOCATE FIXTURE, EQUIPMENT OR DEVICE IG ISOLATED GROUND
CONDITIONS. PROVIDE COLOR-CODED CONDUCTOR INSULATION ACCORDINGLY, CODED PROPERLY W = WEATHER PROOF WHILE IN USE COVER AND WEATHER RESISTANT RECEPTACLE 42" DISTANCE ABOVE FINISHED FLOOR / GRADE /

REVISIONS
DEPENDING ON SYSTEM, PHASE, NEUTRAL, ETC. PROVIDE EQUIPMENT AND PANELBOARD SCHEDULES PAVEMENT LR LEGALLY REQUIRED STANDBY
K.
THAT ACCURATELY INDICATE INSTALLED CONDITIONS.
LOCAL DISCONNECTS AND CONTROLS AT EQUIPMENT: LOCAL DISCONNECTS AND LOCAL CONTROLS
DOOR OPERATORS/DEVICES AF AMP FRAME OF FUSED SWITCH OR CIRCUIT LI
LSI
LONG - INSTANTANEOUS
LONG - SHORT - INSTANTANEOUS
BREAKER
SHOWN AT OR ON EQUIPMENT IN PLAN-VIEW ARE SHOWN FOR SCHEMATIC ASSOCIATIONS ONLY. AFCI ARC-FAULT CIRCUIT INTERRUPTER LSIG LONG - SHORT - INSTANTANEOUS - GROUND
AVOID INSTALLING DISCONNECTS OR CONTROLS ON EQUIPMENT ENCLOSURES. INSTALL ON ELECTRIC DOOR OPERATOR
MANUAL (LEFT) AUTOMATIC (RIGHT) AIC AMPS INTERRUPTING CURRENT FAULT
ADJACENT WALLS OR BUILDING STRUCTURE, OR PROVIDE FIELD-FABRICATED UNISTRUT OR AT AMP TRIP OF FUSED SWITCH OR CIRCUIT
EQUIVALENT ASSEMBLIES AS NEEDED. PROVIDE FIELD COORDINATION WITH SITE CONDITIONS AND PUSH PLATE FOR MANUAL CONTROL OF ELECTRIC DOOR OPERATOR BREAKER MCB MAIN CIRCUIT BREAKER
OTHER TRADES, AND PROVIDE ALL RELATED WORK IN STRICT COMPLIANCE WITH NFPA 70, INCLUDING ATS AUTOMATIC TRANSFER SWITCH MFR MANUFACTURER
ARTICLE 110.26. MLO MAIN LUGS ONLY
L. EQUIPMENT & LOAD COORDINATION: REFER TO AND COORDINATE WITH POWER FLOOR PLANS, MTS MANUAL TRANSFER SWITCH
EQUIPMENT SCHEDULES (INCLUDING EQUIPMENT COORDINATION SCHEDULES), DRAWINGS OF ALL FIRE ALARM DEVICES BAS BUILDING AUTOMATION SYSTEM
MW MICROWAVE OVEN
TRADES, ALL DIVISIONS AND SECTIONS OF SPECIFICATIONS AND INSTALLERS OF ALL TRADES. BASED C.T.C. WORK UNDER DIVISION 27 OR 28 AS
ON ACTUAL EQUIPMENT BEING PROVIDED, DETERMINE AND PROVIDE APPROPRIATE BREAKERS, PUSHBUTTON FOR SILENT ALARM APPLICABLE NIC NOT IN CONTRACT (SHOWN FOR REFERENCE
FUSES, CONDUCTORS, CONTROLS, POWER DISTRIBUTION EQUIPMENT, ETC. PERFORM THESE C/B CIRCUIT BREAKER ONLY)

REV
SERVICES PRIOR TO FURNISHING POWER DISTRIBUTION EQUIPMENT SUBMITTALS. CH COUNTER HEIGHT OR SPECIAL HEIGHT DEVICE NTS NOT TO SCALE
M. EXTERIOR ELECTRICAL WORK AND WORK SUBJECT TO MOISTURE: EXTERIOR ELECTRICAL WORK FIRE ALARM SYSTEM MANUAL PULL STATION DW DISHWASHER
SHALL BE WEATHERPROOF AND WATER-TIGHT, AND SHALL BE RUST-RESISTANT. PROVIDE XHHW-2 OFE OWNER-FURNISHED EQUIPMENT - INSTALLED
CONDUCTORS FOR ALL APPLICATIONS THAT ARE BELOW GRADE OR SUBJECT TO MOISTURE. PROVIDE E EMERGENCY AND WIRED BY E.C.

PJM
KAH
06/26/2019
MINIMUM NEMA 3R ENCLOSURES FOR ALL OUTDOOR EQUIPMENT AND ALL INDOOR EQUIPMENT THAT IS cd FIRE ALARM SYSTEM HORN / STROBE DEVICE
E.C. WORK UNDER DIVISION 26 OS OPTIONAL STANDBY
SUBJECT TO MOISTURE. PROVIDE NEMA 1 ENCLOSURES FOR ALL OTHER INDOOR EQUIPMENT. (PROVIDE CANDELA (cd) RATING FOR STROBE AS INDICATED ON DRAWINGS)
EMS ENERGY MANAGEMENT SYSTEM
N. EQUIPMENT GROUNDING CONDUCTORS: PROVIDE EQUIPMENT GROUNDING CONDUCTORS IN STRICT EPO EMERGENCY POWER OFF P.C. WORK UNDER DIVISION 22
FARP

PG.
COMPLIANCE WITH THE LATEST ADOPTED EDITION OF THE NATIONAL ELECTRICAL CODE (NFPA 70), FACP FIRE ALARM PANELS - (DIMENSIONS MAY VARY / FLUSH OR SURFACE MOUNTED AS INDICATED) ER EQUIPMENT ROOM
INCLUDING ARTICLE 250 AND TABLE 250.122. THESE CONDUCTORS MAY OR MAY NOT BE INDICATED ON ERM ENERGY REDUCTION MAINTENANCE SWITCH S.C. WORK UNDER DIVISION 21

APPROVED BY:
SINGLE-LINE DIAGRAMS OR ELSEWHERE, BUT SHALL BE PROVIDED UNDER BASE BID NEVERTHELESS. FACP - FIRE ALARM CONTROL PANEL

CHECKED BY:
FSCP ESP EMERGENCY STANDBY RATING SCCR SHORT CIRCUIT CURRENT RATING
O. OVERHEAD WORK: HOLD ALL NEW OVERHEAD ELECTRICAL WORK AS TIGHTLY AS POSSIBLE TO THE FAVE FARP - FIRE ALARM REMOTE BATTERY PANEL / CABINET

DRAWN BY:
ETR EXISTING TO REMAIN SPD SURGE PROTECTIVE DEVICE
BOTTOM OF THE OVERHEAD STRUCTURE. DO NOT INSTALL ANY ELECTRICAL WORK WITHIN SIX INCHES FAVE - FIRE ALARM VOICE EVACUATION PANEL EWC ELECTRIC WATER COOLER ST SHUNT TRIP
OF ROOF DECKING. FASP FARA FSCP - FIREFIGHTER'S SMOKE CONTROL PANEL EX. EXISTING

DATE:
P. COORDINATION DRAWINGS: LAYOUT ALL PROPOSED RACEWAY ROUTING, ELEVATIONS, INSTALLATION FASP - FIRE ALARM SPRINKLER MONITOR PANEL TAAC TO ABOVE ACCESSIBLE CEILING

F.B.
NO.
METHODS, ETC. ON COORDINATION DRAWINGS AND COORDINATE ALL PROPOSED RACEWAY ROUTING FARA - FIRE ALARM REMOTE ANNUNCIATOR FBO FURNISHED BY OTHERS - INSTALLED AND TR TAMPER RESISTANT
WITH ALL AFFECTED TRADES PRIOR TO COMMENCING WITH WORK. IN ADDITION, REVIEW THE WIRED BY E.C. TTB TELEPHONE TERMINAL BOARD
INFORMATION WITH ARCHITECT, ENGINEER AND OWNER FOR ALL AREAS WHERE THE RACEWAYS WILL
BE VISIBLE AFTER COMPLETION OF CONSTRUCTION.
MISCELLANEOUS FIBO FURNISHED AND INSTALLED BY OTHERS - TYP TYPICAL
WIRED BY E.C.
Q. JUNCTION AND PULL BOXES: LOCATE JUNCTION AND PULL BOXES SO THAT THEY REMAIN LOW VOLTAGE THERMOSTAT (LEFT) AND TEMPERATURE SENSOR (RIGHT) FP RECEPTACLE TO BE USED FOR A FLAT PANEL UCR UNDER COUNTER REFRIGERATOR
T TS
ACCESSIBLE AFTER ALL CONSTRUCTION WORK IS COMPLETE. COORDINATE ALL WORK WITH ALL DISPLAY. UL UNDERWRITER'S LABORATORY
OTHER TRADES PRIOR TO COMMENCEMENT OF THE WORK. LOCATE BOXES IN A MANNER THAT FWE FURNISHED WITH EQUIPMENT BY OTHERS - U.L.S.E. LISTED FOR SERVICE ENTRANCE
AVOIDS HAVING TO USE ACCESS PANELS. IF ACCESS PANELS ARE INEVITABLE, PROVIDE THEM RATED LINE VOLTAGE THERMOSTAT (LEFT) AND REVERSE ACTING THERMOSTAT (RIGHT) INSTALLED AND WIRED BY E.C. UNO UNLESS NOTED OR INDICATED OTHERWISE ON
L R
TO MEET OR EXCEED THE FIRE AND/OR SMOKE RATINGS OF THE RESPECTIVE CEILING OR WALL, AND DRAWINGS OR IN SPECIFICATIONS

10990 THORNVIEW DRIVE, CINCINNATI OHIO 45241


SHARONVILLE COMMUNITY CENTER
OBTAIN APPROVAL OF DESIGN PROFESSIONALS FOR EACH LOCATION.. GD GARBAGE DISPOSAL
R. CONDUCTOR TERMINATIONS: IN CASES WHERE CONDUCTOR SIZES ARE TOO LARGE TO FIT INTO INDICATES DIRECT CONNECTION TO EQUIPMENT GFEP GROUND FAULT EQUIPMENT PROTECTION VFD / VSD VARIABLE FREQUENCY / SPEED DRIVE
LUGS/TERMINALS, PROVIDE APPROPRIATE FACTORY LUG KITS FOR AFFECTED EQUIPMENT IF GFI / GFCI GROUND FAULT CIRCUIT INTERRUPTER DEVICE VIF VERIFY IN FIELD
AVAILABLE. ELSEWHERE, PROVIDE INSULATED BUTT-SPLICES OR EQUIVALENT METHOD, WITH TAILS GND GROUND VM VENDING MACHINE
MS MSR

LOBBY AND FITNESS ROOM RENOVATION


SIZED TO FIT LUGS/TERMINALS. PROVIDE SPLICES IN SEPARATE BOXES IF REQUIRED BASED ON FIELD MOTOR RATED TOGGLE SWITCH, MANUAL STARTER WITH PILOT LIGHT, AND MANUAL STARTER WITH PILOT VP VANDAL PROOF
CONDITIONS, BOX SIZE LIMITATIONS, ETC. CONCEAL BOXES IN ACCESSIBLE OVERHEAD JOIST SPACES LIGHT WITH EXTERNAL RELAY FOR CONTROL OR MONITORING RESPECTIVELY - ALL MAY BE KEYED "K" H.C. WORK UNDER DIVISION 23
IN FINISHED REGULARLY OCCUPIED AREAS. H.O.A. "HAND - OFF - AUTO" SWITCH W / WP WEATHERPROOF
ENCLOSED CIRCUIT BREAKER
WG WIRE GUARD

ELECTRIC COVER SHEET


WR WEATHER RESISTANT
TIME CLOCK FOR PROGRAMMABLE TIME-OF-DAY AND EXTENDED CONTROL
TC

FRONT ELECTRICAL SWITCHBOARD OR SWITCHGEAR


PLAN-VIEW AND GRAPHIC LINE TYPES
(DIMENSIONS MAY VARY)
WORK SHOWN BOLD-CONTINUOUS INDICATES NEW WORK
ELECTRICAL PANELBOARD OR DISTRIBUTION BOARD (UNLESS OTHERWISE INDICATED)
(DIMENSIONS MAY VARY / FLUSH OR SURFACE MOUNTED AS INDICATED)
WORK SHOWN FADED INDICATES EXISTING WORK TO REMAIN OR NEW WORK BY OTHERS AS APPLICABLE
FRONT DRY TYPE TRANSFORMER (UNLESS OTHERWISE INDICATED)

WORK SHOWN BOLD-DASHED INDICATES SELECTIVE DEMOLITION WORK


OIL FILLED TRANSFORMER (UNLESS OTHERWISE INDICATED)
PAD POLE

ELECTRIC DESIGN CRITERIA

APPLICABLE BUILDING CODES


2017 OHIO BUILDING CODE (BASED ON THE INTERNATIONAL BUILDING CODE)
2017 NFPA 70 - NATIONAL ELECTRICAL CODE
2017 OHIO FIRE CODE (BASED ON 2016 NFPA 72 - NATIONAL FIRE ALARM AND SIGNALING CODE)
2012 INTERNATIONAL ENERGY CONSERVATION CODE (IECC)
6/25/2019 11:51:55 AM

SCALE: 1/8" = 1'-0"

HORZ:

VERT:

CONTRACT NO:

180881
SHEET

E-001
EXISTING CONDITIONS - DEMOLITION NOTES EXISTING CONDITIONS - POWER CONTINUITY NOTES EXISTING CONDITIONS - GENERAL NOTES
KEYED NOTES
A. DEFINITION OF DEMOLITION: WHERE THE TERM “DEMOLITION” IS USED IN ELECTRICAL DOCUMENTS, INTERPRET IT TO THE FOLLOWING NOTES BROADLY DEFINE SOME OF THE SPECIALTY BASE BID SCOPE OF WORK REQUIRED TO PROVIDE A. INTENT OF DOCUMENTS: IT IS NOT THE INTENT OF ELECTRICAL DOCUMENTS THAT EXISTING CONDITIONS BE
MEAN “DEMOLITION” OR “SELECTIVE DEMOLITION” AS APPLICABLE FOR THE RESPECTIVE SCOPE OF WORK. WHERE SPECIAL TEMPORARY POWER FOR NEW AND EXISTING FACILITIES TO ACCOMMODATE UTILITY POWER INTERRUPTIONS. ACCURATELY SHOWN. EXISTING ELECTRICAL WORK IS SHOWN TO A VERY LIMITED EXTENT ON DRAWINGS AND IS
E3 REMOVE EXISTING MONUMENT-STYLE FLOOR BOX AND ALL ASSOCIATED THE TERM “DEMOLISH”, “REMOVE” OR SIMILAR TERMS ARE USED IN ELECTRICAL DOCUMENTS, INTERPRET TO MEAN FIELD VERIFY ALL SPECIFICS AND PROVIDE MATERIALS, NORMAL TIME LABOR, PREMIUM TIME LABOR, SERVICES, ETC. FOR SHOWN FOR GENERAL PLANNING REFERENCE ONLY. LOCATIONS AND INFORMATION WERE DERIVED FROM CURSORY
WIRING. PROVIDE COVER PLATE FOR NEW FLOOR OPENING. “DISCONNECT, REMOVE, DISPOSE OF, AND REMOVE ALL RELATED ELECTRICAL CONDUIT, RACEWAYS, WIRING, ALL WORK UNDER BASE BID, INCLUDING BUT NOT LIMITED TO THE FOLLOWING. VISUAL OBSERVATIONS OR FROM PORTIONS OF DOCUMENTS THAT WERE PREPARED FOR PREVIOUSLY INSTALLED
CABLES, BOXES, SUPPORTS, ETC.”. WORK (NOT FROM RECORD DRAWINGS OR "AS-BUILTS"). MECHANICAL/ELECTRICAL ENGINEERS
T6 REMOVE SPEAKER AND SAVE FOR REINSTALLATION. TYPICAL OF ALL B. GENERAL ACCOMMODATIONS: PROVIDE ELECTRICAL DEMOLITION WORK AS REQUIRED TO ACCOMMODATE PROJECT A. INVESTIGATION OF EXISTING CONDITIONS: LOCATE, IDENTIFY, AND PROTECT ELECTRICAL SERVICES PASSING B. PRE-BID SURVEY: PERFORM A DETAILED PRE-BID WALK-THROUGH FIELD INSPECTION AND SURVEY TO REVIEW THE WWW.KLHENGRS.COM 06/25/19
SPEAKERS. DEMOLITION AND AS REQUIRED TO ACCOMMODATE NEW CONSTRUCTION. DISCONNECT AND REMOVE WORK TO BE THROUGH DEMOLITION AREAS AND SERVING OTHER AREAS OUTSIDE THE DEMOLITION LIMITS. MAINTAIN SERVICES TO EXISTING STRUCTURES AND PREMISES, TO ACCURATELY DETERMINE EXISTING CONDITIONS, AND TO DETERMINE
ABANDONED, AND AS REQUIRED TO ACCOMMODATE WORK OF OTHER TRADES, IN AREAS AFFECTED BY THIS AREAS OUTSIDE DEMOLITION LIMITS. WHEN SERVICES MUST BE INTERRUPTED, PROVIDE TEMPORARY SERVICES FOR SCOPE OF REQUIRED ELECTRICALLY RELATED WORK. INCLUDE APPLICABLE ACCESSIBLE CEILING CAVITY AREAS IN 1538 ALEXANDRIA PIKE, SUITE 11
PROJECT UNLESS SPECIFICALLY NOTED OTHERWISE ON PLANS OR DETERMINED OTHERWISE DURING PRE- AFFECTED AREAS. IT IS RECOGNIZED THAT THERE MAY BE SOME CONDUIT SYSTEMS RENDERED INACTIVE BY THIS INSPECTION. FT. THOMAS, KENTUCKY 41075
DEMOLITION SURVEY. COORDINATE WORK CAREFULLY WITH OWNER PRIOR TO BEGINNING ELECTRICAL DEMOLITION DEMOLITION, CAUSING DISCONNECTION OF "DOWNSTREAM" OUTLETS, ETC. INVESTIGATE THESE TYPES OF C. RISK MITIGATION: MINIMIZE RISKS TO INDIVIDUALS AND PROPERTY THROUGHOUT THE DURATION OF THE PROJECT.
WORK. CONDITIONS (FOR ALL SYSTEMS) PRIOR TO DEMOLITION. PROVIDE NECESSARY CORRECTIVE ELECTRICAL WORK PRIOR COORDINATE WITH, AND OBTAIN APPROVAL FROM, THE OWNER AND DESIGN PROFESSIONAL FOR ALL MATERIALS, 800-354-9783
C. REMOVAL OF ABANDONED WORK: REMOVE ACCESSIBLE ABANDONED, INACTIVE AND OBSOLETE RACEWAY SYSTEMS. TO DEMOLITION TO ENSURE THAT SUCH "DOWNSTREAM" DEVICES REMAIN PERMANENTLY ACTIVE THROUGHOUT METHODS, STEPS, LOCATIONS, INSTALLATIONS, ETC. PRIOR TO COMMENCEMENT OF WORK. DETERMINE AND EMPLOY 859-442-8050
REMOVE ABANDONED, INACTIVE AND OBSOLETE EQUIPMENT, LUMINAIRES, DEVICES, CONDUIT, RACEWAYS, WIRING, DEMOLITION, DURING NEW CONSTRUCTION, AND AFTER PROJECT COMPLETION. PROTECT EXISTING ELECTRICAL MEANS AND METHODS AS REQUIRED TO SAFELY AND SECURELY IMPLEMENT ALL RELATED WORK. 859-442-8058 FAX
CABLES, BOXES, SUPPORTS, CONTROLS, ETC. ABANDONED RACEWAYS EMBEDDED IN FLOORS, WALLS, AND CEILINGS WORK SERVING EXISTING SPACES AND EQUIPMENT THAT MUST REMAIN OPERATIONAL DURING PART OR ALL OF THE D. REUSE OF REMOVED MATERIALS: DO NOT REUSE REMOVED ELECTRICAL MATERIALS UNLESS SPECIFICALLY
MAY REMAIN IF SUCH MATERIALS DO NOT INTERFERE WITH NEW INSTALLATIONS. THIS APPLIES FOR ALL ELECTRICAL CONSTRUCTION PERIOD, AND ENSURE POWER CONTINUITY IS MAINTAINED FOR SAME THROUGHOUT DURATION OF INDICATED IN PROJECT DOCUMENTS. EXISTING WIRING SYSTEMS MAY BE UTILIZED ONLY TO THE EXTENT INDICATED LEXINGTON, KENTUCKY
WORK, AND ALL COMMUNICATIONS AND INFORMATION TECHNOLOGY TYPE WORK, INCLUDING ALL SUCH WORK CONSTRUCTION ACTIVITIES. IN PROJECT DOCUMENTS, OR AS DIRECTED BY OWNER'S REPRESENTATIVE IN FIELD.
LOUISVILLE, KENTUCKY
ABOVE CEILINGS, ETC. REMOVE RELATED ABANDONED UNUSED RACEWAY BACK TO THE NEAREST RESPECTIVE B. COORDINATION WITH OWNER: CAREFULLY COORDINATE WORK AND SYSTEM SHUTDOWNS IN ADVANCE WITH E. POWER DISTRIBUTION AND BRANCH CIRCUIT WORK: DETERMINE WHICH EXISTING BRANCH CIRCUITS MUST REMAIN
"UPSTREAM" JUNCTION BOX THAT REMAINS ACTIVE EVEN IF OUTSIDE OF THE CONFINES OF THE PROJECT AREA. OWNER'S REPRESENTATIVE, AND WITH AFFECTED TRADES SO THAT NORMAL BUILDING ACTIVITIES AND OTHER ACTIVE. RECONNECT (OR MAINTAIN IN OPERATION WHERE APPLICABLE) AND SCHEDULE THEM. COMPLETELY RE-TYPE COLUMBUS, OHIO
REMOVE ABANDONED UNUSED WIRING AND CABLES BACK TO RESPECTIVE SOURCES SOURCE EVEN IF SOURCES ARE CONSTRUCTION TRADES ARE MINIMALLY AFFECTED. PERFORM ELECTRICALLY RELATED CONSTRUCTION WORK, WHICH PANELBOARD DIRECTORIES FOR PANELBOARDS AFFECTED BY THIS PROJECT USING ACCURATE “AS-BUILT” NEW YORK, NEW YORK
OUTSIDE THE CONFINES OF THE PROJECT AREA. WILL AFFECT AN OCCUPIED AREA (INCLUDING THOSE WHICH ARE LOCATED OUTSIDE THE IMMEDIATE AREA OF INFORMATION. WHERE APPLICABLE ENSURE THAT RECONNECTED SHARED NEUTRALS ARE PROPERLY BALANCED
D. RE-USE OF EXISTING CONDUIT: EXISTING BRANCH CIRCUIT AND SYSTEMS CONDUIT, NOT CONFLICTING WITH NEW PROJECT WORK) AT SPECIAL TIMES AS DIRECTED BY OWNER'S REPRESENTATIVE IN FIELD. DO NOT INTERRUPT WITH THE CORRECT PHASE CONDUCTORS. WHERE APPLICABLE, PROVIDE CORRECT COLOR-CODING FOR INSULATION
CONSTRUCTION AND NOT CONFLICTING WITH OVERHEAD OR CEILING CAVITY REQUIREMENTS, MAY BE RE-USED AT ELECTRICAL UTILITY SERVICE(S) TO THE FACILITY, OR ANY PART THEREOF, UNLESS PERMITTED UNDER THE OF RECONNECTED CONDUCTORS IN A MANNER COMPLIANT WITH NFPA 70 AND CONSISTENT WITH EXISTING
THE DISCRETION OF THE ELECTRICAL INSTALLER AFTER ALL ABANDONED CONDUCTORS AND CABLES HAVE BEEN FOLLOWING CONDITIONS, AND THEN ONLY AFTER PROVIDING TEMPORARY ELECTRICAL SERVICE(S)/FEEDS: NOTIFY CONDITIONS. WHEN ADDING COMPONENTS TO EXISTING POWER DISTRIBUTION EQUIPMENT, PROVIDE FULL SIZE (NO
REMOVED FROM THEM. DO NOT EXCEED NFPA 70 REQUIRED CONDUIT FILL AND DO NOT INSTALL WIRING FED FROM OWNER AND DESIGN PROFESSIONALS NO FEWER THAN FOURTEEN DAYS IN ADVANCE OF EACH PROPOSED SPLIT OR TANDEM DEVICES) OVERCURRENT PROTECTION DEVICES (OCPs) TO MATCH THOSE ALREADY IN PLACE,
DIFFERENT SOURCES IN COMMON CONDUIT. INTERRUPTION OF AN ELECTRICAL SERVICE; DO NOT PROCEED WITH INTERRUPTION OF AN ELECTRICAL SERVICE INCLUDING MANUFACTURER, MODEL/SERIES, SHORT CIRCUIT CURRENT (SCCR/AIC) RATINGS. PROVIDE OCPs AS
E. MODIFICATIONS TO ACCOMMODATE NEW WORK: REMOVE AND RELOCATE EQUIPMENT, LUMINAIRES, DEVICES, WITHOUT OWNER'S WRITTEN PERMISSION; DO NOT ENERGIZE ANY NEW WORK WITHOUT NOTIFICATION TO, AND REQUIRED TO RENDER ALL NEW AND MODIFIED ELECTRICAL WORK FULLY OPERATIONAL. PROVIDE COMMON TRIPS
CONDUIT, RACEWAYS, WIRING, CABLES, BOXES, SUPPORTS, ETC. THAT CONFLICT WITH CONSTRUCTION RELATED SUBSEQUENT PERMISSION FROM, THE OWNER AND ALL AFFECTED PARTIES. (NO FIELD-INSTALLED HANDLE TIES) IN THE SAME GUTTER FOR MULTI-POLE DEVICES. PROVIDE SWITCHING DUTY
WORK OF ALL TRADES AS NECESSARY TO ACCOMMODATE NEW WORK OF RESPECTIVE TRADES. REWORK AND C. COORDINATION WITH BUILDING OPERATIONS: PROVIDE WORK IN A MANNER THAT ENSURES EXISTING SYSTEMS AND (SWD), HACR AND HID RATINGS WHERE APPLICABLE FOR LOADS. PROVIDE HANDLE LOCK-ON DEVICES FOR
EXTEND RACEWAY AND WIRING AS REQUIRED TO ACCOMMODATE NEW OR RELOCATED ELECTRICAL WORK. COMPONENTS REMAIN FULLY OPERATIONAL IN OCCUPIED SPACES DURING OCCUPIED PERIODS. MAINTAIN EXISTING EMERGENCY AND CRITICAL LOADS. ALL CIRCUIT ASSIGNMENTS SHOWN ON DRAWINGS ARE SHOWN TO INDICATE NEW
MAINTAIN (OR RECONNECT IF APPLICABLE) REMAINING WIRING. PROVIDE ELECTRICAL DISCONNECTIONS, AND ELECTRICAL SERVICE AND FEEDERS TO OCCUPIED AREAS AND OPERATIONAL FACILITIES, UNLESS OTHERWISE CIRCUIT REQUIREMENTS. DETERMINE EXACT NUMBERING AND SEQUENCING OF CIRCUITS IN FIELD BASED ON
RECONNECTIONS WHERE APPLICABLE, FOR EQUIPMENT TO BE REMOVED (OR RELOCATED) BY OTHER TRADES. INDICATED, OR WHEN AUTHORIZED OTHERWISE IN WRITING BY OWNER’S REPRESENTATIVE. PROVIDE TEMPORARY LOADING, LOAD BALANCING AND EXISTING CONDITIONS.
F. CUTTING AND PATCHING: PERFORM CUTTING AND PATCHING REQUIRED FOR DEMOLITION, RESTORED TO MATCH SERVICE DURING INTERRUPTIONS TO EXISTING FACILITIES. SCHEDULE MOMENTARY OUTAGES WHEN NECESSARY FOR F. ADDED LOADS TO EXISTING CIRCUITS: IN CASES WHERE NEW LOADS ARE INDICATED TO BE CONNECTED TO EXISTING
SURROUNDING REMAINING SURFACES, INCLUDING FIRE/SMOKE RATINGS. REPLACING EXISTING WIRING SYSTEMS WITH NEW WIRING SYSTEMS. WHEN THAT "CUTTING-OVER" HAS BEEN CIRCUITS WITH EXISTING LOADS, CHECK RESULTANT LOAD IN ADVANCE TO ENSURE COLLECTIVE LOAD DOES NOT
G. LUMINAIRES: FOR ALL EXISTING LUMINAIRES WHICH ARE SCHEDULED FOR REUSE, REMOVE FROM EXISTING CEILINGS SUCCESSFULLY ACCOMPLISHED, REMOVE RELATED WIRING THAT HAS BEEN ABANDONED. EXCEED 80 PERCENT OF THE SOURCE CIRCUIT BREAKER AMPERE RATING. IF THAT LOAD IS EXCEEDED, PROVIDE
DURING DEMOLITION; PROTECT DURING CONSTRUCTION; CLEAN, SERVICE (IF REQUIRED), RE-LAMP (WITH LAMPS TO D. TEMPORARY ARRANGEMENTS: COMPLY WITH NFPA 70 (INCLUDING ARTICLE 590), NFPA 70E AND ALL OTHER ADDITIONAL CIRCUIT HOME-RUN WORK TO SOURCE PANELBOARD(S) AS REQUIRED TO ACCOMMODATE THE ENTIRE
MATCH BUILDING STANDARD) AND REINSTALL AT LOCATIONS INDICATED. FOR ALL EXISTING LUMINAIRES WHICH ARE PREVAILING CODES. DURING CONSTRUCTION RELATED ELECTRICAL OUTAGES, SWITCHOVERS, DISCONNECTIONS, RESULTANT LOAD. DETERMINE ALL APPLICABLE CONDITIONS IN FIELD PRIOR TO COMMENCEMENT OF WORK.
SCHEDULED TO BE REMOVED AND TURNED OVER TO OWNER, THE LUMINAIRES SHALL BE DISCONNECTED, RECONNECTIONS, ETC. PROVIDE ALL TEMPORARY INSULATED CONDUCTORS, TAPS, JUMPERS, ETC. TO AND FROM G. REASSIGNMENT OF EXISTING CIRCUITS: IN CASES WHERE EXISTING CIRCUITS ARE REUSED (BASED ON INFORMATION
CAREFULLY REMOVED AND TURNED OVER TO OWNER. TRANSFER SUCH LUMINAIRES TO STORAGE AREA AS EXISTING AND NEW OR TEMPORARY ELECTRICAL EQUIPMENT, INCLUDING BUT NOT LIMITED TO, CONDUCTORS, SHOWN ON DRAWINGS OR BASED ON FIELD CONDITIONS) BUT MUST BE CONNECTED TO BREAKERS OTHER THAN
DIRECTED IN FIELD. SPLICES, LUG FITTINGS, REWORK, PREMIUM TIME, SECURITY AND SAFETY MEASURES, ETC. COORDINATE WITH, AND THEIR ORIGINAL BREAKER, MODIFY COLOR-CODING AS REQUIRED IF THE NEW BREAKER ASSIGNMENT IS CONNECTED
H. DISPOSAL OF MATERIALS: REFER TO OWNER’S REPRESENTATIVE FOR DISPOSAL INSTRUCTIONS FOR ABANDONED OBTAIN APPROVAL FROM, OWNER AND DESIGN PROFESSIONALS FOR ALL MATERIALS, METHODS, STEPS, LOCATIONS, TO A DIFFERENT LINE/PHASE THAN THE ORIGINAL ONE. USE MEANS AND METHODS COMPLIANT WITH NFPA 70 AND
ELECTRICAL MATERIALS REMOVED DURING DEMOLITION AND THEREAFTER. NEATLY STORE ELECTRICAL MATERIALS INSTALLATIONS, SEQUENCING, ETC. PRIOR TO COMMENCEMENT OF WORK. DETERMINE AND EMPLOY MEANS AND WITH AUTHORITIES HAVING JURISDICTION.
THAT THE OWNER ELECTS TO RETAIN AT THE SITE AS DESIGNATED BY THE OWNER'S REPRESENTATIVE. LEGALLY METHODS AS REQUIRED TO SAFELY AND SECURELY IMPLEMENT ALL RELATED WORK. COMPLY WITH NFPA 70E. H. ELECTRICAL WORK TO REMAIN OR BE RELOCATED: IF REQUIRED TO ACCOMMODATE CONSTRUCTION RELATED
DISPOSE OF MATERIALS THAT THE OWNER ELECTS NOT TO RETAIN. DISCONNECT AND REMOVE ELECTRICAL SCHEDULE ALL OUTAGES IN ADVANCE WITH OWNER, AT DAYS OF WEEK AND TIMES OF DAY OR NIGHT AS DIRECTED BY ACTIVITIES, TEMPORARILY REMOVE, STORE IN PROTECTED LOCATION ON SITE, AND REINSTALL CONFLICTING
MATERIALS DESIGNATED FOR SALVAGE (REMOVAL AND REUSE, OR FOR TURNING OVER TO OWNER) UNDAMAGED. OWNER, AS NECESSARY TO ACCOMMODATE ALL CONSTRUCTION RELATED ELECTRICAL OUTAGES, SWITCHOVERS AND ELECTRICAL EQUIPMENT, LUMINAIRES, OR DEVICES THAT ARE TO REMAIN OR TO BE RELOCATED. THE FOLLOWING
DISCONNECT AND REMOVE WIRING AND "WHIPS" FROM EQUIPMENT TERMINAL POINTS. CAREFULLY TRANSPORT RELATED CONNECTIONS AND DISCONNECTIONS. APPLIES TO ELECTRICAL MATERIALS THAT WILL REMAIN OR BE REUSED UNDER THIS PROJECT: PROTECT DURING
SALVAGED ELECTRICAL MATERIALS TO A PROTECTED ON-SITE STORAGE LOCATION AS DIRECTED IN FIELD AND CONSTRUCTION ACTIVITIES; CLEAN LUMINAIRES IMMEDIATELY PRIOR TO OCCUPANCY OF THE FINISHED
NEATLY STORE THEM GROUPED BY SYSTEM TYPE. CONSTRUCTION AREA; CLEAN AND SERVICE (IF SERVICE IS REQUIRED) EQUIPMENT IN THE CONSTRUCTION AREA
I. CLEANING OF REUSED COMPONENTS: CLEAN COMPONENTS TO BE REUSED INSIDE AND OUT, AND REINSTALL WHERE IMMEDIATELY PRIOR TO OCCUPANCY OF THE AREA.
INDICATED ON DRAWINGS. MODIFY AND EXTEND RELATED EXISTING WIRING IN CONDUIT ACCORDINGLY. I. PROTECTIVE BARRIERS: PROVIDE AND MAINTAIN TEMPORARY PARTITIONS AND DUST BARRIERS ADEQUATE TO
PREVENT THE SPREAD OF DUST AND DIRT TO ADJACENT FINISHED AREAS AND OTHER SYSTEM COMPONENTS.

BY
PROTECT ADJACENT INSTALLATIONS DURING CUTTING AND PATCHING OPERATIONS. REMOVE PROTECTION AND
BARRIERS AFTER DEMOLITION OPERATIONS ARE COMPLETE. PREVENT AIRBORNE DUST AND PARTICULATE MATTER
RESULTING FROM ELECTRICAL WORK FROM ENTERING OCCUPIED SPACES, AND FROM ENTERING AIR INTAKES TO
OPERATING HVAC SYSTEMS. MEET WITH OWNER AND HVAC INSTALLER TO DETERMINE SPECIAL INDOOR AIR QUALITY

DATE
(IAQ) REQUIREMENTS RELATED TO ELECTRICAL THAT MAY APPLY TO THIS PROJECT. COOPERATE FULLY WITH HVAC
IAQ REQUIREMENTS THAT AFFECT ELECTRICAL WORK AND ARE AFFECTED BY ELECTRICAL WORK.
J. PENETRATIONS: MAKE REQUIRED ELECTRICAL OPENINGS THROUGH WALLS, FLOORS, ETC. IMMEDIATELY PRIOR TO
INSTALLATION OF WORK. PROPERLY AND PERMANENTLY SEAL ELECTRICAL OPENINGS IMMEDIATELY AFTER
GYMNASIUM INSTALLATION OF WORK. PROVIDE TEMPORARY SEALS FOR APPLICATIONS WHERE PENETRATIONS ARE MADE BUT
CANNOT BE PERMANENTLY SEALED WITHIN FOUR HOURS.
105 K. PRE-EXISTING CODE VIOLATIONS: INSPECT EXISTING ELECTRICAL WORK IN AREAS ACCESSED UNDER THIS PROJECT
AND BRING INTO COMPLIANCE WITH NFPA 70. THIS APPLIES ONLY TO THE EXTENT THAT SUCH WORK IS UNCOVERED
IN THE IMMEDIATE PROJECT AREAS AFFECTED BY CONSTRUCTION ACTIVITIES, AND ONLY TO THE LIMITED EXTENT
THAT IT APPLIES TO PRE-EXISTING GENERAL INSTALLATION METHODS SUCH AS MISSING JUNCTION BOX PLATE, OPEN
JUNCTION BOX KNOCKOUT, MINOR CONDUIT RE-ANCHORING AND MINOR EXPOSED WIRING/CONNECTIONS. IF MORE
EXTENSIVE CODE OR SAFETY VIOLATIONS ARE DISCOVERED, IMMEDIATELY BRING THEM TO THE ATTENTION OF THE

REVISIONS
OWNER'S REPRESENTATIVE (DETAILED IN WRITING) ALONG WITH PROPOSED COST FOR CORRECTIONS AND IMPACT
(IF ANY) ON THE CONSTRUCTION SCHEDULE.
L. TEMPORARY LIGHTING AND POWER: COMPLY WITH NFPA 70 (INCLUDING ARTICLE 590), NFPA 70E AND ALL OTHER
PREVAILING CODES. PROVIDE SUFFICIENT LIGHTING AND POWER CENTERS THROUGHOUT INTERIOR OF NEW WORK
OR RENOVATION SCOPE. PROVIDE GFCI PROTECTION FOR ALL WORK. COORDINATE WITH GENERAL CONTRACTOR
AND OTHER TRADES, AND PROVIDE ANY ADDITIONAL TEMPORARY ELECTRICAL NEEDS THAT ARE REQUIRED. FULLY
DEMOLISH TEMPORARY ELECTRIC BY END OF PROJECT. TEMPORARY ELECTRICAL SERVICE(S) MAY BE DERIVED FROM
EXISTING BUILDING ENERGIZED SERVICE. PROVIDE OVERCURRENT PROTECTION, DISCONNECTS, CABLES,
CONDUCTORS, RACEWAY, ETC. ACCORDINGLY.
M. INTERIM LIFE-SAFETY PROVISIONS: PROVIDE INTERIM ELECTRICAL FIRE ALARM AND LIFE SAFETY PROTECTION IN
DEMOLITION AND CONSTRUCTION AREAS AS INDICATED BELOW. CONTACT DESIGN PROFESSIONAL IF FURTHER
DEFINITION IS NEEDED. REMOVE ALL TEMPORARY LIFE SAFETY WORK WHEN NO LONGER NEEDED. PROVIDE
TEMPORARY PLASTIC COVERS, OBTAINED FROM SMOKE DETECTOR MANUFACTURER OR OBTAINED FROM A THIRD
PARTY AND SPECIFICALLY APPROVED FOR SUCH USE BY SMOKE DETECTOR MANUFACTURER, OVER EXISTING SMOKE

REV
DETECTORS WITHIN PROJECT AREA, AND IN ADJACENT AREAS THAT ARE EXPOSED TO CONSTRUCTION-RELATED
DUST OR AIRBORNE PARTICULATES, DURING WORKING PERIODS. REMOVE COVERS AFTER EACH SHIFT. PROVIDE
LOBBY TEMPORARY UL 924 COMPLIANT EXIT AND/OR EGRESS LIGHTING ALONG EGRESS ROUTES AFFECTED BY THIS
PROJECT, AS OR IF APPLICABLE. PROVIDE TEMPORARY FIRE ALARM SYSTEM PULL STATIONS AND/OR AUDIO/VISUAL

PJM
KAH
06/26/2019
101
ALARM NOTIFICATION DEVICES ALONG ALL AFFECTED EGRESS ROUTES THAT MUST REMAIN ACTIVE DURING THE
PROJECT, AS OR IF APPLICABLE.
N. CONDUCTOR TRACING: PRIOR TO COMMENCEMENT OF WORK, TRACE ALL FEEDERS AND BRANCH CIRCUITS WITHIN

PG.
THE PROJECT AREA, AND AFFECTED BY THE PROJECT, AND DOCUMENT THE RESULTS. DETERMINE AND DOCUMENT
T EXISTING LOADS FOR ALL CIRCUITS AND FEEDERS WITH LOADS THAT WILL REMAIN. CREATE CURRENT AS-BUILT

APPROVED BY:
CHECKED BY:
DIRECTORIES FOR ALL POWER DISTRIBUTION EQUIPMENT. LIKEWISE, DETERMINE AND DOCUMENT ROUTING AND

DRAWN BY:
SPECIFICS FOR ALL RELEVANT EXISTING CONDUITS AND PATHWAYS FOR ALL SYSTEMS. SUBMIT THIS INFORMATION
FRONT DESK TO OWNER AND DESIGN PROFESSIONALS AS INFORMATIONAL SUBMITTALS.
ELEVATOR

DATE:
102

F.B.
NO.
104
(R)

K
(R)

10990 THORNVIEW DRIVE, CINCINNATI OHIO 45241


SHARONVILLE COMMUNITY CENTER
FP FP
VESTIBULE
100

LOBBY AND FITNESS ROOM RENOVATION


T6 T6

ELECTRIC DEMOLITION PLAN


T
T6
S
S
FP

(R)

FP

FARA
(R)
FP
T

S
FITNESS ROOM
103

PLUG
STRIP

S S
S

E3

FP

(R) AREA OF WORK


S S

S S S

C
6/25/2019 11:52:02 AM

C
SCALE: As indicated
FP HORZ:

VERT:

CONTRACT NO:

1 ELECTRIC DEMOLITION PLAN KEY PLAN 180881


SHEET
ED101 SCALE: 1/8" = 1'-0" N NTS
ED101
ELECTRIC LUMINAIRE SCHEDULE GENERAL LIGHTING PLAN NOTES
LAMP BALLAST / BALLAST /
TYPE DESCRIPTION MANUFACTURER / SERIES SIZE HOUSING / MOUNTING MATERIAL LENS DESCRIPTION QTY LAMP TYPE LAMP BASE DRIVER QTY DRIVER FINISH COMMENTS FIXTURE LOAD VOLTAGE A. EXIT SIGN CONNECTIONS: CONNECT ALL EXIT SIGNAGE AHEAD OF ANY SWITCHING.
A2 LED FLAT PANEL LITHONIA EPANL 2'x4'x2" RECESSED STEEL SATIN WHITE FLAT LUMINOUS ACRYLIC LENS 1 LED, 3500K, 80 4800 1 ELECTRONIC WHITE FLAT STEEL DOOR FRAME 47 VA B. INDOOR EGRESS LIGHTING: CONNECT ALL INDOOR EGRESS LIGHTING, DESIGNATED
DAY-BRITE 2FXP CRI NOMINAL DRIVER, 120-277V, "EL", AHEAD OF ANY SWITCHING. UNLESS CONTROL METHODS ARE INDICATED
MECHANICAL/ELECTRICAL ENGINEERS
COLUMBIA CFP24 LUMENS 0-10V DIMMING OTHERWISE FOR A GIVEN AREA. WWW.KLHENGRS.COM
METALUX 24FP 06/25/19
EXA EXIT SIGN - AC LITHONIA LE 12"x8"x2" UNIVERSAL, REFER TO CAST ALUMINUM STENCIL FACE 1 0W LED, WITH 0 NO BALLAST WHITE EXIT SIGNAGE COLOR TO BE BASED ON OWNER 2 VA 120 V 1538 ALEXANDRIA PIKE, SUITE 11
ONLY - CAST CHLORIDE 55L PLAN SIGN PREFERENCE OR EXISTING CONDITIONS, BRUSHED FT. THOMAS, KENTUCKY 41075
ALUMINUM DUAL-LITE SE ALUMINUM FACE, AC ONLY 800-354-9783
SURELITES CX7
KEYED NOTES 859-442-8050
859-442-8058 FAX

E1 CIRCUIT NEW LUMINAIRE TO NEARBY EMERGENCY LIGHTING CIRCUIT WITH LEXINGTON, KENTUCKY
SPARE CAPACITY. VERIFY ADDED LOAD WILL NOT OVERLOAD CIRCUIT PRIOR LOUISVILLE, KENTUCKY
TO MAKING FINAL CONNECTION. COLUMBUS, OHIO
E4 DURING NORMAL OPERATIONAL HOURS, AS DETERMINED BY OWNER, THE NEW YORK, NEW YORK
FITNESS CENTER LIGHTING SHALL TURN "ON" AND "OFF" BASED ON THE
TIME SCHEDULE PROGRAMMED INTO THE TIME-CLOCK. PROVIDE
MOMENTARY OVERRIDE SWITCH FOR MAXIMUM OVERRIDE OF 2 HOURS TO
LUMINAIRE SCHEDULE ALLOW FOR AFTER HOURS CONTROL OF LIGHTING.

GENERAL NOTES
A. REFER TO DRAWINGS FOR MOUNTING TYPE, NUMBER
OF FACES AND ARROWS OF EXIT SIGNS. VERIFY IN
FIELD PRIOR TO INSTALLATION.
B. VERIFY COMPATIBILITY WITH VOLTAGE, CONTROLS,
ETC. FOR ALL LUMINAIRE COMPONENTS
C. COORDINATE EACH LUMINAIRE LOCATION WITH THE
ARCHITECTURAL REFLECTED CEILING PLANS, CEILING
INSTALLERS, ETC. AND PROVIDE APPROPRIATE
MOUNTING SYSTEM REQUIRED FOR EACH LUMINAIRE.
ALSO, PROVIDE PLASTER FRAMES, WALL BRACKETS,
SUPPORTS, OR OTHER APPURTENANCES AS
REQUIRED FOR PROPER AND COMPLETE
INSTALLATIONS.
D. WEAR CLEAN WHITE COTTON GLOVES WHEN
HANDLING EXPOSED REFLECTIVE LUMINAIRE
SURFACES. REMOVE PLASTIC SHIPPING BAGS ONLY
AFTER INTERIOR WORK IS COMPLETE, AND CLEAN ALL
SURFACES WITH CLEAN DRY CHEESECLOTH.
E. MOUNTING HEIGHTS INDICATED ARE TO THE BOTTOM
OF THE LUMINAIRE, UNLESS OTHERWISE NOTED.

BY
F. PRODUCTS: PROVIDE PRODUCTS INDICATED ON
DRAWINGS AND SCHEDULES. WHERE MULTIPLE
MANUFACTURER SERIES/MODEL NUMBERS ARE
LISTED FOR A SINGLE LUMINAIRE, PROVIDE ONE OF

DATE
THOSE LISTED. WHERE A SPECIFIC MANUFACTURER
SERIES/MODEL NUMBER IS LISTED AS BASIS-OF- GYMNASIUM
DESIGN, AND WHERE IT IS STATED THAT EQUIVALENTS
105
WILL BE CONSIDERED, ANY PROPOSED NON-LISTED
LUMINAIRES ARE SUBJECT TO REVIEW BY DESIGN
PROFESSIONAL(S), SUBMITTALS FOR WHICH SHALL BE
FURNISHED AT LEAST (10) DAYS PRIOR TO BID DUE
DATE OR THEY WILL NOT BE CONSIDERED. THESE
PRE-BID SUBMITTALS SHALL CLEARLY STATE EXACTLY
WHAT IS BEING PROPOSED AND SHALL DEMONSTRATE

REVISIONS
COMPLIANT EQUIVALENCY. SIMILAR REQUESTS FOR
PROPOSED SUBSTITUTIONS MAY BE MADE ONLY
AFTER BIDS ARE RECEIVED, AND ONLY IF OWNER
CHOOSES TO CONSIDER SUBSTITUTION REQUESTS.
DESIGN PROFESSIONAL(S) AND OWNER RESERVE THE
EMERGENCY LIGHTING LOAD CALCULATION
RIGHT TO REJECT ALL PRODUCTS THAT ARE NOT FITNESS CENTER
DEEMED TO BE FULLY EQUIVALENT TO THE BASIS-OF- DEMOLISHED LIGHTING LOAD = 2 FIXTURES X 96 W/FIXTURE = 192 W
DESIGN LISTING(S). SUBMIT ALL REQUESTS AND ADDED LIGHTING LOAD = 4 FIXTURES ("A2") X 47 W/FIXTURE = 188 W
QUESTIONS THROUGH THE FORMALLY-ESTABLISHED 1 FIXTURE ("EXA") X 2 W/FIXTURE = 2 W
BIDDING PROCESS, NOT DIRECTLY TO ENGINEER. 2 W SPARE
EXISTING LIGHTING CIRCUIT WILL NOT BE OVERLOADED.

REV
LOBBY
101

PJM
KAH
06/26/2019

PG.
APPROVED BY:
CHECKED BY:
DRAWN BY:
ELEVATOR
104

DATE:

F.B.
NO.
FRONT DESK
K
102 (R)
E1

EXA

Interior Lighting
TC
E4 M EXA

10990 THORNVIEW DRIVE, CINCINNATI OHIO 45241


SHARONVILLE COMMUNITY CENTER
VESTIBULE
LPH2 - 1 E1
Compliance Certificate A2
100

LOBBY AND FITNESS ROOM RENOVATION


A2 A2 A2 A2 A2
E1
EL

ELECTRIC LIGHTING PLAN


2012 IECC
Section 1: Project Information A2
Project Type: Alterations
A2 A2 A2 A2
Section 2: Interior Lighting and Power Calculation
Floor Area (sq. ft.) Watts per sq. ft. Allowed Watts Proposed Watts Complies
2,848 sq. ft. 1.0 W/sq. ft. (Exercise Center) 2,848 W See Below Yes

Section 3: Interior Lighting Fixture Schedule FITNESS ROOM


103
TYPE LAMP TYPE BALLAST / DRIVER LAMP QTY COUNT LOAD TOTAL LOAD
A2 LED, 3500K, 80 CRI ELECTRONIC DRIVER, 120-277V, 0-10V DIMMING 1 29 47 VA 1363 VA
1363 VA A2 A2 A2 A2 A2 A2
E1 E1
EL EL

A2 A2 A2 A2 A2 A2 AREA OF WORK

A2 A2 A2 A2 A2 A2
E1
EL
6/25/2019 11:52:50 AM

SCALE: As indicated

HORZ:

VERT:

CONTRACT NO:

1 ELECTRIC LIGHTING PLAN KEY PLAN


180881
EL101 SCALE: 1/8" = 1'-0" NTS
N SHEET

EL101
GENERAL POWER PLAN NOTES
A. EQUIPMENT COORDINATION SCHEDULES: REFER TO EQUIPMENT COORDINATION
SCHEDULES FOR REQUIREMENTS ASSOCIATED WITH EQUIPMENT CIRCUITING,
CONNECTIONS, ANCILLARY DEVICES AND EQUIPMENT, ETC. COORDINATE
LOCATIONS AND REQUIREMENTS FOR ALL EQUIPMENT WITH RESPECTIVE MECHANICAL/ELECTRICAL ENGINEERS
EQUIPMENT SUPPLIERS AND INSTALLERS PRIOR TO ORDERING ANY RELATED WWW.KLHENGRS.COM
MATERIALS OR COMMENCING WITH ANY RELATED ROUGH-IN WORK. 06/25/19
1538 ALEXANDRIA PIKE, SUITE 11
FT. THOMAS, KENTUCKY 41075
800-354-9783
859-442-8050
KEYED NOTES 859-442-8058 FAX

LEXINGTON, KENTUCKY
E2 NEW LOCATION OF RELOCATED UNDERCOUNTER PUSH BUTTON FOR
LOUISVILLE, KENTUCKY
SILENT ALARM. MAINTAIN ALL WIRING AND CONTROL WITH EXISTING
COLUMBUS, OHIO
ALARM BELL.
NEW YORK, NEW YORK
E5 NEW LOCATION OF RELOCATED REMOTE ANNUNCIATOR. VERIFY
LOCATION IN FIELD PRIOR TO INSTALLATION.
E6 PROVIDE FLOOR-MOUNTED RACEWAY SYSTEM FOR POWER TO FITNESS
EQUIPMENT, STARLINE "POWER ONLY SERIES" OR APPROVED EQUAL.
PROVIDE POWER FEED URPF060-4H-3-BLK, (1) PLUG-IN MODULE FOR
EACH TREADMILL SHOWN, AND ALL ADDITIONAL PIECES REQUIRED TO
ACCOMMODATE LENGTH OF RACEWAY SHOWN.
E7 CONNECT NEW DOOR OPENER TO EXISTING CIRCUIT. VERIFY ADDED
LOAD WILL NOT OVERLOAD CIRCUIT PRIOR TO MAKING FINAL
CONNECTION.
E8 WIRE DOOR OPERATOR BUTTON TO ACTIVATE BOTH DOORS ON SAME
SIDE PER PEDESTRIAN TRAFFIC PATTERN.
E9 WIRE DOOR OPERATOR BUTTON TO ACTIVATE SINGLE DOOR ONLY.
E10 RELOCATE EXISTING RECEPTACLE FOR FLAT PANEL DISPLAY TO BE
BELOW CEILING AT HEIGHT SHOWN.
E11 ALTERNATE #5: REPLACEMENT OF VAV BOXES. PROVIDE NEW CIRCUIT
AND WIRING AS REQUIRED.
E12 REFER TO ARCHITECTURAL PLANS FOR CEILING FAN SPECIFICATIONS.
E13 PROVIDE PEDESTAL FOR MOUNTING OF DOOR OPERATOR BUTTON.
NEATLY CUT AND PATCH FLOOR AS REQUIRED TO INSTALL WIRING FOR
POWER AND CONTROL. VERIFY LOCATIONS IN FIELD PRIOR TO TO
ROUGH-IN.

BY
DATE
GYMNASIUM
105

REVISIONS
VFP-202B

REV
LOBBY
101

PJM
KAH
06/26/2019
FP
60"
FRONT DESK

PG.
LP-LB - 29 T
102
E11 CPU

APPROVED BY:
E11

CHECKED BY:
C

DRAWN BY:
VFP-202A VFP-202C
ELEVATOR LPH2- 19 E2 LPH2- 21
CPU

DATE:
104 (R) CPU
C

F.B.
NO.
C
CPU VESTIBULE
LP-LB - 10 LP-LB - 21
C 100
VFP-202D
LPH2- 23 E11
(R) LP-LB - 19
LP-LB - 12 E7 c
FARA E5 E13

ELECTRIC POWER PLAN - UPPER LEVEL


c

10990 THORNVIEW DRIVE, CINCINNATI OHIO 45241


E8 E9

SHARONVILLE COMMUNITY CENTER


T

VFP-201 b,d
d
b

LOBBY AND FITNESS ROOM RENOVATION


LP-LB - 22
a
E9 a,c
E13

T
30 cd E12
E8
FP b
96"
E10
(R)
LPH2 LP-LB LP-LBA

FACP

LP-LB - 20

LP-LB - 33,35,37
FP
E6 96"
T FITNESS ROOM BP1
103
TREADMILL

VFP-207A
TREADMILL

TREADMILL
FP
96"
FP E10
96" TREADMILL
(R)
FP
96"
AREA OF WORK
TREADMILL

VFP-207B
FP
96"
6/25/2019 11:53:01 AM

SCALE: As indicated

HORZ:

VERT:

CONTRACT NO:

1 ELECTRIC POWER PLAN 180881


EP101 SCALE: 1/8" = 1'-0" KEY PLAN SHEET

N NTS EP101
MECHANICAL/ELECTRICAL ENGINEERS
WWW.KLHENGRS.COM 06/25/19
1538 ALEXANDRIA PIKE, SUITE 11
FT. THOMAS, KENTUCKY 41075
800-354-9783
859-442-8050
859-442-8058 FAX

LEXINGTON, KENTUCKY
LOUISVILLE, KENTUCKY
COLUMBUS, OHIO
NEW YORK, NEW YORK

HVAC ELECTRICAL COORDINATION SCHEDULE


ABBREVIATIONS CONTRACTOR TYPE MOTOR CONTROL TYPE CONTROL TYPE
DC LOCAL DISCONNECT EC ELECTRICAL CONTRACTOR CS COMBINATION STARTER TC TIMECLOCK
MC MOTOR CONTROL (POWER) EX EXISTING MCC MOTOR CONTROL STARTER CPT CONTROL POWER TRANSFORMER
SD DUCT SMOKE DETECTOR FC FIRE PROTECTION CONTRACTOR MG MAGNETIC STARTER OR CONTACT BAS BUILDING AUTOMATION SYSTEM
CN CONTROLS GC GENERAL CONTRACTOR MS MANUAL STARTER LOW LOW VOLTAGE CONTROLS
TS TOGGLE SWITCH HC HVAC CONTRACTOR VFD VARIABLE FREQUENCY DRIVE LINE LINE VOLTAGE CONTROLS
C/B H.A.C.R. CIRCUIT BREAKER AT SOURCE PANELBOARD MFR MANUFACTURER MSR MANUAL STARTER W/ CONTROL RELAY RLINE REVERSE ACTING LINE VOLTAGE THERMOSTAT
FUSE FUSE AT LOCAL DISCONNECT (VERIFY FIELD RATING) PC PLUMBING CONTRACTOR OV OVERCURRENT PROTECTION MAN MANUAL
FLA OPERATING FULL LOAD AMPS OR OWNER OR OTHERS FA FIRE ALARM
MCA MINIMUM CIRCUIT AMPACITY CO CARBON MONOXIDE SENSOR
CP CORD AND PLUG CONNECTION INT INTEGRAL TO EQUIPMENT

BY
AVAILABLE
FAULT CURRENT
(A)

DATE
EQUIPMENT MARK DESCRIPTION VOLTS (V) PHASE EMERGENCY BHP (HP) HP (HP) HTG (kW) WATTS FLA (A) MCA (A) OCP (A) DC TYPE DC FURN DC INST DC WIRE MC TYPE MC FURN MC INST MC WIRE CN TYPE CN FURN CN INST CN WIRE SD TYPE
VFP-202A FAN POWERED VAV BOX 277 1 .75 0 4.6 EC EC EC MG MFR MFR MFR BAS HC HC HC 1680
VFP-202C FAN POWERED VAV BOX 277 1 .33 0 2.6 EC EC EC MG MFR MFR MFR BAS HC HC HC 1170
VFP-202D FAN POWERED VAV BOX 277 1 .33 0 2.6 EC EC EC MG MFR MFR MFR BAS HC HC HC 1498

REVISIONS
REV

PJM
KAH
06/26/2019

PG.
APPROVED BY:
CHECKED BY:
TECHNOLOGY ELECTRICAL COORDINATION SCHEDULE

DRAWN BY:
EQUIPMENT MARK DESCRIPTION ROOM NAME ROOM NUMBER VOLTS (V) POLES POWER (W) NEMA CONFIGURATION HEAT GAIN

DATE:
FRONT DESK 102 120 V 1 0 VA 0 Btu/h

F.B.
NO.
FITNESS ROOM 103 120 V 1 360 VA
FITNESS ROOM 103 120 V 1 360 VA
FITNESS ROOM 103 120 V 1 360 VA
FITNESS ROOM 103 120 V 1 360 VA
LOBBY 101 120 V 1 360 VA

10990 THORNVIEW DRIVE, CINCINNATI OHIO 45241


SHARONVILLE COMMUNITY CENTER
LOBBY AND FITNESS ROOM RENOVATION

ELECTRIC POWER - DETAILS


GENERAL NOTES:
A. REVIEW PROPOSED INSTALLATION MATERIALS, METHODS, ROUTING, ETC. CASE-BY-CASE AND AREA-BY-AREA FOR EACH APPLICATION WITH THE
ARCHITECT AND OWNER PRIOR TO INSTALLATION. ACCORDINGLY, PREPARE INSTALLATION DRAWINGS AND SUBMIT TO DESIGN PROFESSIONALS
FOR REVIEW AND COMMENT. REVISE AND RESUBMIT AS REQUIRED BASED ON COMMENTS FROM DESIGN PROFESSIONALS. COORDINATE WITH ALL GENERAL NOTES:
FEED SURFACE MOUNTED TRADES WHILE PREPARING THE INSTALLATION DRAWINGS. SHOW ELEVATIONS AND ROUTES RELATIVE TO ADJACENT WORK OF ALL TRADES.
COMPONENTS THAT ARE A. ALIGN ALL DEVICES SHOWN ON PLANS AT SAME
B. GROUP CONDUITS TOGETHER IN TIGHT BANKS WHEN ROUTED IN THE SAME DIRECTION IN A GIVEN SPACE. COORDINATE WITH MECHANICAL TRADES DIMENSION FROM DOOR FRAME OR WALL.
MOUNTED HIGH ON WALL AND ROUTE THE CONDUIT BANKS ALONG COMMON PATHS WHEREVER POSSIBLE, AND AT COMMON ELEVATIONS UNLESS THE CONDUIT BANKS CAN
FROM ABOVE. B. CONDUIT/CABLES SHALL BE ROUTED
BE INSTALLED DIRECTLY ABOVE OR BELOW THE MECHANICAL WORK. REVIEW PROPOSED ROUTES AND ELEVATIONS WITH DESIGN PROFESSIONALS WHEREVER NECESSARY TO KEEP DEVICES
PRIOR TO INSTALLATION. ALIGNED.
C. INSTALL CONDUITS THAT PEEL OFF FROM BANKS IN A MANNER THAT RESULTS IN THE CONDUITS BEING PROGRESSIVELY TAKEN OFF FROM THE
SIDES OF THE BANKS, ONE AT A TIME WITHOUT CROSSING OVER OR UNDER OTHER CONDUITS IN THE BANK. RISE AND DROP CONDUITS AT THE
℄ C. ALL DEVICES MOUNTED AT SAME HEIGHT TO BE
ALIGNED HORIZONTALLY.
SAME ELEVATION IN AREAS WITH COMMON VISIBILITY. ENSURE ALL DEVICES ARE LEVEL AND PLUMB
D.
E.
PROVIDE CLEAN, TIGHT AND UNIFORM BENDS AND OFFSETS FOR ALL CONDUITS AND CONDUIT BANKS.
ROUTE OVERHEAD WORK PERPENDICULAR AND PARALLEL TO ARCHITECTURAL AND STRUCTURAL BUILDING LINES. DO NOT INSTALL WORK BELOW EXIT
℄ AFTER INSTALLATION.
D. FOR MULTI-GANG DEVICES, ALIGN DEVICES AT
PROVIDE FIRE-STOPPING AT SKYLIGHT ASSEMBLIES OR IN FRONT OF WINDOW ASSEMBLIES. CENTER OF GROUP. PROVIDE SINGLE
RATED PENETRATIONS. F. PROVIDE SURFACE CONDUIT AND RACEWAY FOR WALL-MOUNTED APPLICATIONS ONLY WHERE IT IS IMPOSSIBLE TO FISH OR CUT/PATCH, OR ONLY FACEPLATE FOR GROUPS OF DEVICES WHERE
NEATLY OFFSET RACEWAYS WHERE SPECIFICALLY INDICATED ON DRAWINGS, OR ONLY WHERE SPECIFICALLY DIRECTED BY ARCHITECT. IMPROPER SEQUENCING OF WORK AT APPLICABLE.
AS REQUIRED FOR OUTLET WALLS SHALL NOT BE USED AS A REASON TO SURFACE-MOUNT CONDUIT, BOXES OR RACEWAYS; INSTALL ALL SUCH WORK CONCEALED AS THE E. COORDINATE WITH ALL TRADES CASE-BY-CASE.
BOX ENTRY. WALLS ARE CONSTRUCTED. PROVIDE CONDUIT IN AREAS THAT ARE EXCLUSIVELY UTILITARIAN, SUCH AS DEDICATED MECHANICAL OR ELECTRICAL
ROOMS. PROVIDE FINISHED SURFACE RACEWAY SYSTEMS FOR APPLICATIONS IN ALL OTHER AREAS. CONSULT WITH DESIGN PROFESSIONALS IN
ADVANCE OF ANY INSTALLATION FOR FINAL DIRECTION ON WHERE TO USE CONDUIT VERSUS SURFACE RACEWAY SYSTEMS.
G. INSTALL CONDUITS AND RACEWAYS AS OUT-OF-SITE AS REASONABLY POSSIBLE. FOR INSTANCE IF AN RECEPTACLE OUTLET NEEDS TO BE
INSTALLED AT THE CENTER OF A WALL AND THERE IS NO POSSIBILITY OF FEEDING FROM BELOW THE FLOOR, ROUTE THE DROP IN A CORNER OF
THE ROOM THEN TRANSITION AND RUN HORIZONTALLY TO THE OUTLET LOCATION.
H. INSTALL CONDUIT AND RACEWAY WITH A MINIMUM 2-INCH RADIUS CONTROL AT BEND POINTS.
FEED SURFACE MOUNTED I. SECURE CONDUIT AND RACEWAY WITH SCREWS OR OTHER ANCHOR-TYPE DEVICES AT INTERVALS NOT EXCEEDING 48 INCHES AND WITH NO LESS S S T
SWITCHES AND THAN TWO SUPPORTS PER STRAIGHT SECTION. SUPPORT ACCORDING TO MANUFACTURER'S WRITTEN INSTRUCTIONS.
RECEPTACLES FROM J. UTILIZE SUPPORTS FOR WALL-MOUNTED APPLICATIONS THAT CLEANLY CONFORM TO THE SHAPE OF THE CONDUIT OR RACEWAY AND DO NOT IN ℄
BELOW. ANY WAY PROTRUDE OUT PAST THE OUTER CONTOURS OF THE CONDUIT OR RACEWAY. AS AN EXAMPLE, INSTALL WALL-MOUNTED CONDUIT USING
TWO-HOLE STRAPS INSTEAD OF CONDUIT HANGERS. TAPE, GLUE, TIE-WRAPS, CLIPS, WEDGES, ETC. ARE NOT ACCEPTABLE SUPPORT METHODS.
K. REVIEW ALL PROPOSED MOUNTING MEANS AND METHODS WITH DESIGN PROFESSIONALS FOR LUMINAIRES, DEVICES, OUTLETS, EQUIPMENT, ETC.
THAT WILL BE SUSPENDED OVERHEAD.
L. DO NOT USE "TRAPEZE" MOUNTING METHODS FOR SUSPENSIONS UNLESS CASE-BY-CASE PERMISSION IS GRANTED BY DESIGN PROFESSIONALS
2" MAX. (TYPICAL FOR GROUPINGS)
OR UNLESS NOTED OTHERWISE IN THESE DOCUMENTS.
M. INSTALL CONDUITS AND RACEWAYS IN A MANNER THAT MINIMIZES DETRIMENTAL EFFECTS ON ROOM AESTHETICS. FOR INSTANCE, AS APPLICABLE,
RISE FROM BELOW FOR WALL SWITCHES, GENERAL RECEPTACLE OUTLETS AND COMMUNICATIONS WALL OUTLETS; DROP FROM ABOVE FOR WALL
MOUNTED LIGHTS, AND OTHER SYSTEM OUTLETS THAT ARE INSTALLED HIGH ON WALL; MAKE DROPS NEAR CORNERS, WINDOW CASINGS, DOOR
CASINGS, ETC.

GRAPHIC EXAMPLE OF NOTES "M" & "N" N. FEED RECEPTACLES AND SWITCHES ON EXPOSED-MASONRY AND NON-"FISHABLE" WALLS FROM BELOW. ROUTING THE WIRING DOWN FROM THE
RESPECTIVE AREA SERVED TO THE CAVITY BETWEEN THE FLOOR ABOVE AND THE FINISHED CEILING BELOW.
O. PAINT (TWO COATS)ALL EXPOSED RACEWAY, ANCHORS, FITTINGS, BOXES, ETC. IN ALL FINISHED REGULARLY-OCCUPIED AREAS WITH TYPE AND
COLOR OF PAINT AS DIRECTED BY ARCHITECT.
6/25/2019 11:53:08 AM

SCALE: 1/8" = 1'-0"

HORZ:

VERT:

260533.00-01 - SCHEMATIC SURFACE RACEWAY INSTALLATION DETAIL 260502.00-01 - DEVICE ALIGNMENT DETAIL CONTRACT NO:

SCALE: NONE
SCALE: NONE 180881
SHEET

EP501
MECHANICAL/ELECTRICAL ENGINEERS
WWW.KLHENGRS.COM 06/25/19
1538 ALEXANDRIA PIKE, SUITE 11
FT. THOMAS, KENTUCKY 41075
800-354-9783
859-442-8050
859-442-8058 FAX

LEXINGTON, KENTUCKY
LOUISVILLE, KENTUCKY
COLUMBUS, OHIO
NEW YORK, NEW YORK

BY
DATE
REVISIONS
REV

PJM
KAH
06/26/2019

PG.
APPROVED BY:
CHECKED BY:
LPLA LPLA1

DRAWN BY:
DATE:

F.B.
NO.
LPIN LPLD

ELECTRIC POWER - SINGLE LINE DIAGRAM


LPLC LPLCA LP-LB LP-LBA TRANSFORMER

10990 THORNVIEW DRIVE, CINCINNATI OHIO 45241


SHARONVILLE COMMUNITY CENTER
T1

LOBBY AND FITNESS ROOM RENOVATION


TRANSFORMER CH3

TRANSFORMER TRANSFORMER

T4 MCC2
T3 T2

ELEVATOR CH2
TVSS
LPH3 LPH2 LPH1 MCC1

SPARE SPARE

PAD MOUNTED
UTILITY CO.
MPDP480 #108030762
TRANSFORMER
1200A MCB PEAK DEMAND
480/277V 3PH 4W
M 222.1KW
24837 AIC
EXISTING SCCR T
FED FROM: UTILITY
X1200
DISTRIBUTION MAIN SECTION INCOMING CABLE &
SECTION DISTRIBUTION SECTION(S) METERING SECTION CONC. PAD

480V, 3-PHASE, 4-WIRE SERVICE (SERVICE 1 OF 3)


6/25/2019 11:53:13 AM

SHOWN FOR REFERENCE ONLY SCALE: 1/8" = 1'-0"


TO UTILITY
HORZ:
ELECTRIC SINGLE LINE DIAGRAM VERT:

CONTRACT NO:
SCALE: NONE

180881
SHEET

EP601
MECHANICAL/ELECTRICAL ENGINEERS

SWITCHBOARD: MPDP480 PANEL NAME: LPH2 WWW.KLHENGRS.COM 06/25/19


SUPPLY FROM: UTILITY FAULT CURRENT (A): 24837 SUPPLY FROM: MPDP480 MAINS RATING (A): 150 FAULT CURRENT (A): 5378 SURGE SUPRESSION: 1538 ALEXANDRIA PIKE, SUITE 11
FT. THOMAS, KENTUCKY 41075
LOCATION: SHORT CIRCUIT RATING (A): EXISTING LOCATION: MAINS TYPE: SHORT CIRCUIT RATING (A): EXISTING ULSE: 800-354-9783
DISTRIBUTION SYSTEM: 480/277V 3PH 4W ENCLOSURE TYPE: NEMA 1 DISTRIBUTION SYSTEM: 480/277V 3PH 4W FEEDER ID: X150 LUGS TYPE: 200% NEUTRAL: 859-442-8050
MAINS RATING (A): 1200 SURGE SUPRESSION: FEEDER: EXISTING FEEDER, AT RATING INDICATED, TO REMAIN UNLESS NOTED OTHERWISE ENCLOSURE TYPE: NEMA 1 ISOLATED GROUND: 859-442-8058 FAX
MAINS TYPE: THERMAL MAGNETIC ULSE: CKT CIRCUIT DESCRIPTION VD% AWG GND TRIP FRAME POLE A B C POLE FRAME TRIP GND AWG VD% CIRCUIT DESCRIPTION CKT LEXINGTON, KENTUCKY
200% NEUTRAL: ISOLATED GROUND: 1 (#) LIGHTING FITNESS ROOM 0.526 #12 #12 20 A 20 A 1 1.18 0.00 1 -- 20 A -- -- -- (EX) 2 LOUISVILLE, KENTUCKY
FEEDER ID: X1200 3 (EX) LIGHTS RM 207 -- -- -- 20 A -- 1 0.00 0.00 1 -- 20 A -- -- -- (EX) LOBBY WALLS 4 COLUMBUS, OHIO
FEEDER: EXISTING FEEDER, AT RATING INDICATED, TO REMAIN UNLESS NOTED OTHERWISE NEW YORK, NEW YORK
5 (EX) 2ND FL LIGHTS OFF BATH AND MECH -- -- -- 20 A -- 1 0.00 0.00 1 -- 20 A -- -- -- (EX) ENTRANCE LIGHTS 6
NOTES:
7 (EX) -- -- -- 20 A -- 1 0.00 0.00 1 -- 20 A -- -- -- (EX) 8
9 (EX) -- -- -- 20 A -- 1 0.00 0.00 1 -- 20 A -- -- -- (EX) LIGHTS LOBBY 10
CKT TRIP FRAME POLES VD% AWG GND CIRCUIT DESCRIPTION LOAD
11 (EX)(OFF) LIGHTS ROTUNDA -- -- -- 20 A -- 1 0.00 0.00 1 -- 20 A -- -- -- (EX) LIGHTS LOBBY 12
1 250 A 250 A 3 SL SL SL (EX) MCC2 | NON-CONTINUOUS 0.00 kVA
13 (EX) 1ST FLOOR LIGHTS -- -- -- 20 A -- 1 0.00 0.00 1 -- 20 A -- -- -- (EX) 14
2 150 A 150 A 3 SL SL SL (EX) MCC1 | NON-CONTINUOUS 0.00 kVA
15 (EX) 1ST FLOOR LIGHTS -- -- -- 20 A -- 1 0.00 0.00 1 -- 20 A -- -- -- (EX) 16
3 350 A -- 3 -- -- -- (EX) CHILLER 2 0.00 kVA
4 350 A -- 3 -- -- -- (EX) CHILLER 3 0.00 kVA 17 (EX) 1ST FLOOR LIGHTS -- -- -- 20 A -- 1 0.00 0.00 1 -- 20 A -- -- -- (EX) 18
5 125 A -- 3 -- -- -- (EX) ELEVATOR 0.00 kVA 19 (#)(ALT) VFP-202A | COOLING LOBBY 101 0.571 #12 #12 20 A 20 A 1 1.27 0.00 1 -- 20 A -- -- -- (EX) 20
6 200 A -- 3 -- -- -- (EX) LPH1 0.00 kVA 21 (#)(ALT) VFP-202C | COOLING LOBBY 101 0.425 #12 #12 20 A 20 A 1 0.72 0.00 1 -- 20 A -- -- -- (EX) 22
7 150 A 150 A 3 SL SL SL (EX) LPH2 71.19 kVA 23 (#)(ALT) VFP-202D | COOLING FRONT DESK 102 0.306 #12 #12 20 A 20 A 1 0.72 0.00 1 -- 20 A -- -- -- (EX) 24
8 150 A -- 3 -- -- -- (EX) LPH3 0.00 kVA 25 (EX) SPARE -- -- -- 20 A -- 1 0.00 0.00 1 -- 20 A -- -- -- (EX) 26
9 30 A -- 3 -- -- -- (EX) TVSS 0.00 kVA 27 (EX) SPARE -- -- -- 20 A -- 1 0.00 0.00 1 -- 20 A -- -- -- (EX) 28
10 70 A -- 3 -- -- -- (EX) T4 0.00 kVA
29 (EX) SPARE -- -- -- 20 A -- 1 0.00 0.00 1 -- 20 A -- -- -- (EX) 30
11 100 A -- 3 -- -- -- (EX) SPARE 0.00 kVA
31 (EX) SPACE -- -- -- -- -- -- 0.00 0.00 -- -- -- -- -- -- (EX) SPACE 32
12 30 A -- 3 -- -- -- (EX) SPARE 0.00 kVA
33 (EX) SPACE -- -- -- -- -- -- 0.00 0.00 -- -- -- -- -- -- (EX) SPACE 34
LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND DEMOLITION LOAD SUMMARY BREAKER QUANTITIES (NEW ONLY)
Continuous 0 VA 0.00% 0 VA Lighting: 125% 3.75kVA 35 (EX) SPACE -- -- -- -- -- -- 0.00 0.00 -- -- -- -- -- -- (EX) SPACE 36
Cooling 2714 VA 100.00% 2714 VA Receptacle: 100% 1.08kVA 37 (EX) SPACE -- -- -- -- -- -- 0.00 10.20 38
Heating 0 VA 0.00% 0 VA 39 (EX) SPACE -- -- -- -- -- -- 0.00 8.84 3 70 A 70 A SL SL SL (EX) T-2 | NON-CONTINUOUS 40
Kitchen Equipment 0 VA 0.00% 0 VA 41 (EX) SPACE -- -- -- -- -- -- 0.00 9.06 42
Lighting 1175 VA 125.00% 1469 VA TOTAL CONNECTED LOAD: 26.2 kVA 24.0 kVA 21.0 kVA

BY
Motor 7640 VA 104.91% 8015 VA LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND NOTES: BREAKER QUANTITIES (NEW ONLY)
Non-Continuous 3500 VA 100.00% 3500 VA Continuous 0 VA 0.00% 0 VA
Receptacle 360 VA 100.00% 360 VA Cooling 2714 VA 100.00% 2714 VA

DATE
PANEL TOTALS Heating 0 VA 0.00% 0 VA
METERED PEAK DEMAND (PER NEC 220.87): 222100.0 VA Kitchen Equipment 0 VA 0.00% 0 VA
ADDED CONNECTED LOAD: 15389 VA Lighting 1175 VA 125.00% 1469 VA
DEMOLISHED DEMAND: 4825 VA Motor 7640 VA 104.91% 8015 VA
DEMAND CALCULATION NOTES 125% EXISTING METERED DEMAND, LESS DEMOLISHED DEMAND Non-Continuous 3500 VA 100.00% 3500 VA
Receptacle 360 VA 100.00% 360 VA
TOTAL DEMAND: 288678.2 VA PANEL TOTALS DEMOLITION LOAD SUMMARY:
TOTAL DEMAND AMPS: 347 A EXISTING CONNECTED LOAD: 55800 VA Lighting: 125% 3.75kVA

REVISIONS
EXISTING LOAD DEMAND FACTOR: 100.00% Receptacle: 100% 1.08kVA
ADDED CONNECTED LOAD: 15389 VA
DEMOLISHED DEMAND: 4825 VA
DEMAND CALCULATION NOTES: 100% EXISTING, LESS DEMOLISHED DEMAND
TOTAL DEMAND: 66853 VA
TOTAL DEMAND AMPS: 80 A

PANEL NAME: LP-LB

REV
SUPPLY FROM: T-2 MAINS RATING (A): 150 FAULT CURRENT (A): 4422 SURGE SUPRESSION:
LOCATION: MAINS TYPE: THERMAL MAGNETIC SHORT CIRCUIT RATING (A): EXISTING ULSE:

PJM
KAH
06/26/2019
DISTRIBUTION SYSTEM: 208/120V 3PH 4W FEEDER ID: X150 LUGS TYPE: 200% NEUTRAL:
FEEDER: EXISTING FEEDER, AT RATING INDICATED, TO REMAIN UNLESS NOTED OTHERWISE ENCLOSURE TYPE: NEMA 1 ISOLATED GROUND:

PG.
CKT CIRCUIT DESCRIPTION VD% AWG GND TRIP FRAME POLE A B C POLE FRAME TRIP GND AWG VD% CIRCUIT DESCRIPTION CKT
1 (EX) REC OFFICE 221 -- -- -- 20 A -- 1 0.00 0.00 1 -- 20 A -- -- -- (EX) REC OFFICE 218 2

APPROVED BY:
CHECKED BY:
3 (EX) REC OFFICE 223 -- -- -- 20 A -- 1 0.00 0.00 1 -- 20 A -- -- -- (EX) REC OFFICE 220 4

DRAWN BY:
5 (EX) REC OFFICE 222 -- -- -- 20 A -- 1 0.00 0.00 1 -- 20 A -- -- -- (EX) REC OFFICE 219 6

DATE:
7 (EX) REC OFFICE 217 -- -- -- 20 A -- 1 0.00 0.00 1 -- 20 A -- -- -- (EX) COPIER ROOM 217 8

F.B.
NO.
9 (EX) REC CORRIDOR 215 -- -- -- 20 A -- 1 0.00 0.50 1 20 A 20 A #12 #12 1.194 (#) NON-CONTINUOUS FRONT DESK 102 10
11 (EX) REC OFFICE 214 -- -- -- 20 A -- 1 0.00 0.66 1 20 A 20 A #12 #12 2.482 (#) RECEPTACLE FRONT DESK 102 12
13 (EX) REC ROOM 207 - SOUTH WALL -- -- -- 20 A -- 1 0.00 0.00 1 -- 20 A -- -- -- (EX) EWC 209 14
15 (EX) REC ROOM 207 - WEST WALL -- -- -- 20 A -- 1 0.00 0.00 1 -- 20 A -- -- -- SPARE 16

ELECTRIC POWER - PANEL SCHEDULES


17 (EX) REC ROOM 207 - WEST WALL -- -- -- 20 A -- 1 0.00 0.00 1 -- 20 A -- -- -- (EX) REC. MACHINE ROOM 18

10990 THORNVIEW DRIVE, CINCINNATI OHIO 45241


SHARONVILLE COMMUNITY CENTER
19 (#) NON-CONTINUOUS FRONT DESK 102 1.311 #12 #12 20 A 20 A 1 0.50 1.20 1 20 A 20 A *#10 *#10 2.169 NON-CONTINUOUS FITNESS ROOM 103 20
21 (#) NON-CONTINUOUS FRONT DESK 102 1.311 #12 #12 20 A 20 A 1 0.50 0.14 1 20 A 20 A #12 #12 0.288 (#) FAN | MOTOR FITNESS ROOM 103 22
23 (EX) REC ROOM 207 - EAST WALL & OUTSIDE -- -- -- 20 A -- 1 0.00 0.00 1 -- 20 A -- -- -- (EX) LASER PRINTER 24

LOBBY AND FITNESS ROOM RENOVATION


25 (EX) UH-212 1/20 HP -- -- -- 20 A -- 1 0.00 0.00 1 -- 20 A -- -- -- (EX) FILE SERVER 26
27 (EX) REC CAMERA EQUIPMENT -- -- -- 20 A -- 1 0.00 0.00 -- -- -- -- -- -- SPACE 28
29 (#) NON-CONTINUOUS FRONT DESK 102 1.311 #12 #12 20 A 20 A 1 0.50 0.00 1 -- 20 A -- -- -- (EX) LIGHTS LOBBY BY EXIT IN CEILING 30
31 (EX) REC ROOM 207 -- -- -- 20 A -- 1 0.00 0.00 1 -- 20 A -- -- -- (EX) SPARE 32
33 3.00 0.00 1 -- 20 A -- -- -- (EX) LIGHTS IN COUNTER 34
35 BP1 0.438 #4 #10 60 A 60 A 3 3.00 0.00 1 -- 20 A -- -- -- (EX) SPARE 36
37 1.50 0.00 38
39 (->) TEMP CONTROL PANEL -- -- -- 20 A -- 1 0.00 0.00 3 100 A 100 A SL SL SL (EX) LP-LBA | NON-CONTINUOUS 40
41 (EX) REC ROOM 207 - TV -- -- -- 20 A -- 1 0.00 0.00 42
TOTAL CONNECTED LOAD: 10.2 kVA 8.8 kVA 9.1 kVA
LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND NOTES: BREAKER QUANTITIES (NEW ONLY)
Continuous 0 VA 0.00% 0 VA (3) 20A / 1P, (1) 60A / 3P
Cooling 0 VA 0.00% 0 VA
Heating 0 VA 0.00% 0 VA
Kitchen Equipment 0 VA 0.00% 0 VA
Lighting 0 VA 0.00% 0 VA
Motor 7640 VA 104.91% 8015 VA
Non-Continuous 3500 VA 100.00% 3500 VA
Receptacle 360 VA 100.00% 360 VA
PANEL TOTALS DEMOLITION LOAD SUMMARY:
EXISTING CONNECTED LOAD: 16600 VA Receptacle: 100% 1.08kVA
EXISTING LOAD DEMAND FACTOR: 100.00%
ADDED CONNECTED LOAD: 11500 VA
DEMOLISHED DEMAND: 1080 VA
DEMAND CALCULATION NOTES: 100% EXISTING, LESS DEMOLISHED DEMAND
TOTAL DEMAND: 27215 VA
TOTAL DEMAND AMPS: 76 A

PANEL SCHEDULE LEGEND (LT) = PROVIDE LOCK-OUT/TAG-OUT DEVICE


PANEL SCHEDULE GENERAL NOTES
6/25/2019 11:53:20 AM

(->) = CONNECT BRANCH CIRCUIT, WHICH WAS DISCONNECTED FROM ANOTHER PANEL KEY SCALE:
(EX) = EXISTING CIRCUIT TO REMAIN SOURCE AS PART OF SELECTIVE DEMOLITION, TO POLE SPACE(S) INDICATED, A. PROVIDE HACR RATED BREAKERS ON ALL MOTOR LOADS.
(#) = NEW CIRCUIT TO EXISTING CIRCUIT BREAKER B. PROVIDE LOCKING TYPE BREAKER FOR ALL LIFE SAFETY AND NIGHT LIGHTING BRANCH CIRCUITS. HORZ:
DETERMINE EXACT POLE ASSIGNMENT(S) BASED ON EXISTING COLOR-CODING MPDP480 LPH2
(G) = PROVIDE GROUND-FAULT CIRCUIT INTERRUPTER (GFCI) CIRCUIT BREAKER OF THE BRANCH CIRCUIT CONDUCTOR INSULATION. PROVIDE NEW BREAKER IF C. ALL VOLTAGE DROP CALCULATIONS AND COMPENSATED WIRE SIZES ARE BASED ON RIGHT VERT:
(GE) = PROVIDE GROUND-FAULT EQUIPMENT PROTECTION (GFEP) CIRCUIT BREAKER REQUIRED. ANGLE CIRCUIT LENGTHS TO THE LAST DEVICE. ACTUAL VOLTAGE DROP VARIES BASED ON CONTRACT NO:
(ST) = PROVIDE SHUNT TRIP CIRCUIT BREAKER * = WIRE SIZED TO COMPENSATE FOR VOLTAGE DROP INSTALLED WIRE LENGTH.
(A) = PROVIDE ARC FAULT CIRCUIT INTERRUPTER (AFCI) CIRCUIT BREAKER
(L) = PROVIDE LOCK-ON DEVICE
**
SL
=
=
REFER TO DRAWINGS FOR SPECIFICATIONS
SEE THE SINGLE LINE DIAGRAM / SCHEDULE FOR WIRE SIZE AND VOLTAGE DROP
LP-LB 180881
SHEET

EP602
MECHANICAL/ELECTRICAL ENGINEERS
WWW.KLHENGRS.COM 06/25/19
1538 ALEXANDRIA PIKE, SUITE 11
FT. THOMAS, KENTUCKY 41075
800-354-9783
859-442-8050
859-442-8058 FAX

LEXINGTON, KENTUCKY
LOUISVILLE, KENTUCKY
COLUMBUS, OHIO
NEW YORK, NEW YORK

TECHNOLOGY LEGEND GENERAL NOTES: DRAWING IDENTIFICATION:


A. NOTHING SET FORTH IN THESE DRAWINGS SHALL RELEASE ANY CONTRACTOR FROM HIS
SYMBOL DESCRIPTION RESPONSIBILITY TO PROVIDE APPROPRIATE QUANTITIES, FIELD MEASUREMENTS, DIMENSIONAL
DRAWING IDENTIFICATION
DRAWING PREFIX
STABILITY, INSTALLATION, ANCHORAGE, AND COORDINATION WITH OTHER TRADES; OR RELEASE
DRAWING TYPE
TELECOMMUNICATIONS HIM FROM HIS RESPONSIBILITY TO IDENTIFY AND RESOLVE DEVIATIONS FROM THE
REQUIREMENTS OF THE CONTRACT DOCUMENTS, OR FREE HIM OF HIS RESPONSIBILITY TO
DRAWING PREFIX
T TECHNOLOGY
DISCIPLINE ID
WALL DATA OUTLET ALERT DESIGNER TO ERRORS OR OMISSIONS.
WAP = WIRELESS ACCESS POINT B. CONTRACTOR SHALL UTILIZE THESE DRAWINGS IN CONJUNCTION WITH THE SPECIFICATIONS TO SEQUENCE # DRAWING TYPE
0 LEGEND/INDEX/COMPOSITE
DETERMINE THE FULL SCOPE, INTENT AND REQUIREMENTS OF THE PROJECT. SPECIFICATIONS 1 FLOORPLANS
AUDIO-VISUAL SYSTEMS AND DRAWINGS ARE INTENDED TO BE COMPLEMENTARY, NOT MUTUALLY EXCLUSIVE. WORK 2 ELEVATIONS

WALL FLAT PANEL DISPLAY


SHOWN ON THE DRAWINGS BUT NOT LISTED IN THE SPECIFICATIONS, AND WORK DESCRIBED IN
THE SPECIFICATIONS BUT NOT SHOWN ON THE DRAWINGS SHALL BE INTERPRETED AS THOUGH T-501 3
4
SECTIONALS
ENLARGED FLOORPLANS AND DETAILS

BY
FP
WORK WERE FULLY DESCRIBED IN BOTH PLACES. THE HIGHER QUANTITY, HIGHER QUALITY, 5 DETAILS

CEILING SPEAKER MORE LABOR INTENSIVE AND OVERALL MORE STRINGENT AND MORE COSTLY REQUIREMENT DRAWING IDENTIFICATION IS INTENDED TO 6 DIAGRAMS
S SHALL APPLY UNLESS OTHERWISE CLARIFIED IN WRITING PRIOR TO BID. PROVIDE AN ORDERLY FORMAT TO DELIVER 7 PATHWAY/ROUGH-IN

DATE
C. EACH CONTRACTOR SHALL VERIFY IN THE FIELD ALL EXISTING APPLICABLE CONDITIONS AND PROJECT INFORMATION. A MAJORITY OF
DIMENSIONS SHOWN ON THE DRAWINGS AND AS PERTINENT TO THE INTENT OF THESE DRAWINGS CONTAIN INFORMATION THAT IS DISCIPLINE ID
SECURITY SYSTEMS DRAWINGS. ANY DISCREPANCY DISCOVERED SHALL BE BROUGHT TO THE ATTENTION OF THE REQUIRED OR WILL BE BENEFICIAL TO 0 INFORMATION TECHNOLOGY - ALL DISCIPLINES
DESIGNER PRIOR TO THE COMMENCEMENT OF ANY WORK AFFECTED BY, OR RELATED TO, SUCH MULTIPLE DISCIPLINES AND / OR 1 STRUCTURED CABLING
CEILING SECURITY CAMERA
C DISCREPANCY. EACH CONTRACTOR SHALL BE RESPONSIBLE FOR ALL COSTS ASSOCIATED WITH, CONTRACTORS. LIKEWISE, EACH 2 DATA SYSTEMS
3 TELEPHONE SYSTEM
OR CAUSED BY HIS FAILURE TO COMPLY WITH THIS REQUIREMENT. SPECIFICATION SECTION MAY REQUIRE
4 A/V SYSTEMS
D. EACH CONTRACTOR SHALL BE RESPONSIBLE FOR JOB CLEANLINESS. PROJECT AREAS SHALL BE INFORMATION ON MULTIPLE DRAWINGS TO
CABLE / RACEWAY / SPACE THOROUGHLY CLEANED AND TRASH DISPOSED OF AT THE END OF EACH WORK DAY. OWNER'S COMPLETE THE SYSTEM(S). 5 DISTRIBUTED COMMUNICATIONS
6 RESERVED
CIRCUIT HOME RUN WITH RACK IDENTIFIER AND PORT NUMBER FACILITIES SHALL NOT BE USED FOR WASTE DISPOSAL.
7 SECURITY
ER-02-01,13 E. EACH CONTRACTOR SHALL BE RESPONSIBLE FOR PROTECTION OF ALL SURFACES AND FINISHES 8 SITE/OUTDOOR (OSP)

REVISIONS
IN THE INTERIOR OR EXTERIOR OF THE FACILITY. DAMAGED SURFACES OR FINISHES RESULTING 9 RESERVED
CABLING / RACEWAY INSTALLED CONCEALED IN WALLS OR ABOVE CEILING FROM THE PERFORMANCE OF THE WORK OR NEGLIGENCE SHALL BE REPAIRED AT NO COST TO
THE OWNER AND BE MADE TO MATCH THE EXISTING FINISHES OR SURFACES TO THE SEQUENCE #
CABLING / RACEWAY INSTALLED BELOW FLOOR OR GRADE SATISFACTION OF THE OWNER. 0 RESERVED
F. FOR COORDINATION PURPOSES, OCCASSIONALLY AN ITEM OF WORK WILL BE SHOWN ON THE E 1-9 FIRST-NINTH
SERIES DRAWINGS AND THE T SERIES DRAWINGS. IN ADDITION, THE SAME WORK MAY BE A-Z 10-36
CABLE TRAY INCLUDED ON MULTIPLE T SERIES DETAIL SHEETS FOR SIMILAR REASONS.
G. FOR MULTI-PHASED PROJECTS. THE CONTRACTOR SHALL MAINTAIN ALL EXISTING UTILITY
LADDER RACK SERVICES AND BUILDING SYSTEMS. THE CONTRACTOR SHALL COORDINATE WITH THE OWNERS
IT REPRESENTATIVE AS NECESSARY TO ALLOW FOR OPERATION ACCEPTABLE TO THE OWNER
DURING CONSTRUCTION. THE CONTRACTOR SHALL PROVIDE TEMPORARY WIRING AS
SYSTEM DIAGRAM LEGEND
SERVICE POLE - POWER AND TECHNOLOGY WHERE APPLICABLE. NECESSARY.
MANUFACTURE (BRAND) AND
H. PROVIDE DUST PROTECTION WHEN WORKING IN EXISTING FACILITIES. SEAL OFF ALL WORK

REV
MODEL NUMBER OF THE
UP 4" CONDUIT SLEEVE UP OR DOWN THROUGH FLOOR AREAS FROM REMAINDER OF THE EXISTING FACILITY.
PRODUCT.
DN * INPUT (EXAMPLE: “QSC CMX 500Va”)
GENERAL ROUGH-IN AND PATHWAY NOTES: CONNECTIVITY

SMB
06/26/2019

MSN
CONDUIT SLEEVE THROUGH WALL * OUTPUT
LABELS HERE
A. PROVIDE PATHWAYS FOR COMMUNICATIONS AND SECURITY SYTEMS CABLING. REFER TO MANUFACTURE CONNECTIVITY
SECTIONS “PATHWAYS FOR COMMUNICATIONS”. LABELS HERE
MODEL

PG.
PLAN-VIEW LINE TYPES B. ROUGH-IN/PATHWAYS SHALL BE CLOSELY REVIEWED AND COORDINATED PRIOR TO INSTALLATION. TYPICAL

APPROVED BY:
IT IS THE RESPONSIBILITY OF THE ROUGH-IN PROVIDER TO THROUGHLY REVIEW AND

CHECKED BY:
WORK SHOWN BOLD-CONTINUOUS INDICATES NEW WORK UNDERSTAND THE REQUIREMENTS OF THE SYSTEMS THAT WILL USE THE PATHWAYS. PRODUCT

DRAWN BY:
(UNLESS INDICATED OTHERWISE) GENERIC PRODUCT
C. WHERE CONDUITS ARE SPECIFIED “TAAC” (TO ABOVE ACCESSIBLE CEILING) THIS SHALL MEAN DESCRIPTION
GENERIC
WORK SHOWN FADED INDICATES EXISTING WORK TO REMAIN OR NEW WORK BY OTHERS AS APPLICABLE THAT CONDUITS SHALL BE STUBBED INTO AN ACCESSIBLE CEILING CAVITY WITHIN THE SAME (EXAMPLE: “POWER

DATE:
PRODUCT
ROOM AS THE DEVICE THE CONDUIT SERVES.

F.B.
(UNLESS INDICATED OTHERWISE)

NO.
DESCRIPTION AMPLIFIER”)
D. WHERE DEVICE CONDUITS ARE SPECIFIED “TAHC” (TO ABOVE ACCESSIBLE HALLWAY/CORRIDOR
WORK SHOWN BOLD-DASHED INDICATES SELECTIVE DEMOLITION WORK CEILING) THIS SHALL MEAN THAT CONDUITS SHALL BE RUN CONTINUOUS AND STUBBED OUT INTO
(UNLESS INDICATED OTHERWISE) AN ACCESSIBLE CEILING CAVITY WITHIN THE NEAREST CORRIDOR FEATURING AN ACCESSIBLE
CEILING CAVITY. DEVICE ID
ABBREVIATIONS E. CONDUIT INSTALLER SHALL INSTALL PULL STRINGS IN ALL CONDUITS IMMEDIATELY AFTER
“DEVICE ID” UNIQUELY
INSTALLATION.
F. WHERE CONDUIT IS SHOWN AND/OR SPECIFIED, PROVIDE PULL BOXES SHOWN ON THE DRAWINGS IDENTIFIES
AN INSTANCE OF A DEVICE IN

10990 THORNVIEW DRIVE, CINCINNATI OHIO 45241


(R) RELOCATE FIXTURE, EQUIPMENT OR DEVICE HDMI HIGH DEFINITION MULTIMEDIA INTERFACE PLUS ADDITIONAL PULL BOXES FOR EVERY 180 DEGREES OF CONDUIT BEND AND 100 FEET OF

SHARONVILLE COMMUNITY CENTER


CONDUIT. A SYSTEM
42" DISTANCE ABOVE FINISHED FLOOR / GRADE / IP INTERNET PROTOCOL (EXAMPLE “PAMP.01”)
PAVEMENT LI LOCAL INPUT G. PROVIDE COVER PLATES FOR JUNCTION AND PULL BOXES. COORDINATE MATERIAL AND FINISH OF
LO LOCAL OUTPUT BLANK PLATES TO MATCH SURROUNDING PLATES.

LOBBY AND FITNESS ROOM RENOVATION


H. WHERE A MOUNTING HEIGHT MEASUREMENT IS APPLIED TO A ROUGH-IN, THE MEASUREMENT

TECHNOLOGY COVER SHEET


ACC ADMINISTRATIVE CONTROL CONSOLE
ACD ACCESS CONTROLLED DOOR OFE OWNER FURNISHED EQUIPMENT SHALL BE REFERENCED TO THE CENTER OF THE ROUGH-IN DEVICE.
AFF ABOVE FINISHED FLOOR OFCI OWNER FURNISHED CONTRACTOR INSTALLED INPUT PLATE/PANEL
I. PATHWAYS SHALL BE INSTALLED IN A CONCEALED MANNER. EXPOSED CONDUIT SHALL NOT BE
AFG ABOVE FINISHED GRADE PERMITTED IN FINISHED AREAS.
AVR AUDIO VISUAL SYSTEM EQUIPMENT RACK PBB PRIMARY GROUNDING BUSBAR
PM PATIENT MONITOR
J. PROVIDE CODE-COMPLIANT FIRE-STOPPING FOR PATHWAYS THROUGH FIRE-RATED WALLS,
BAS BUILDING AUTOMATION SYSTEM PS PATIENT STATUS FLOORS AND CEILINGS.
BFC BELOW FINISHED CEILING K. PROVIDE CONDUITS WITH NYLON END-BUSHINGS. INSTALL BUSHINGS AT THE END OF EACH PLATES OUTPUT PLATE/PANEL

R ROUGH-IN ONLY CONDUIT AND EACH ADDITIONAL LOCATION WHERE CABLES COULD BE DAMAGED WHEN PULLING AND
C CONDUIT THEM THROUGH THE CONDUIT.
CH COUNTER HEIGHT OR SPECIAL HEIGHT DEVICE SBB SECONDARY GROUNDING BUSBAR PANELS
L. DEVICES TO BE INSTALLED AT COUNTER HEIGHT, CASEWORK OR FURNITURE SHALL BE CLOSELY
SER SECURITY SYSTEM EQUIPMENT RACK
SSR SOUND SYSTEM EQUIPMENT RACK
COORDINATED IN THE FIELD WITH ARCHITECT, CASEWORK AND FURNITURE VENDORS PRIOR TO
DP DISPLAY PORT
DS DIGITAL SIGNAGE ROUGH-IN.
DVI DIGITAL VIDEO INTERFACE TAAC TO ABOVE ACCESSIBLE CEILING M. WHERE FLOORBOXES, POWER POLES AND OTHER DUAL SERVICE PATHWAYS ARE INDICATED ON COMPLETE PLATE/PANEL BLOCKS PARTIAL PLATE/PANEL BLOCKS
DVR DIGITAL VIDEO RECORDER TAHC TO ABOVE ACCESSIBLE HALLWAY CEILING THE DRAWINGS. PATHWAY DEVICES SHALL BE PROVIDED BY THE EC. SEE ELECTRIC DRAWINGS
TR TELECOMMUNICATIONS ROOM FOR REQUIREMENTS AND ADITIONAL INFORMATION.
EC ELECTRICAL CONTRACTOR TBB TELECOMMUNICATIONS BACKBOARD N. MANY COMMUNICATIONS DEVICES ARE INTENDED TO HAVE ADJACENT POWER OR INTEGRAL
EF ENTRANCE FACILITY RECEPTACLES (MULTI-SERVICE) TO SERVE THE SAME EQUIPMENT. COORDINATE THE LOCATION GENERAL CABLING NOTES:
EMR ELECTRONIC MEDICAL RECORDS WP WEATHERPROOF
EQR EQUIPMENT RACK WG WIRE GUARD OF SEPARATE DEVICES SO THAT THEY ARE LOCATED ADJACENT AND AT THE SAME ELEVATION.
A. PLENUM CABLE REQUIRED. ALL CABLE THAT WILL NOT BE INSTALLED IN A FULLY ENCLOSED
ER EQUIPMENT ROOM FACEPLATES SHALL BE COORDINATED TO THE SAME TYPE AND COLOR.
CONDUIT SYSTEM SHALL BE RATED FOR INSTALLATION WITHIN A RETURN AIR PLENUM.
ETR EXISTING TO REMAIN O. CONDUITS STUBBED INTO THE CEILING CAVITY SHALL BE MARKED WITH AN INDELIBLE MARKER
B. ALL INSTALLED CABLING SHALL BE CONTINUOUS AND WITHOUT SPLICES, EXCEPT WHERE
EX EXISTING INDICATING THE CONDUIT’S INTENDED USE. MARK CONDUIT WITHIN SIX INCHES OF THE CONDUIT
OTHERWISE NOTED.
BUSHING SO AS TO BE READABLE FROM BELOW.
C. COLORS OF CABLING USED FOR ALL TECHNOLOGY WORK SHALL BE REVIEWED AND
P. LADDER RACK AND OTHER COMMUNICATION TECHNOLOGY CABLING PATHWAYS DEPICTED ON THE
APPROVED PRIOR TO PROCUREMENT AND INSTALLATION.
ENLARGED FLOOR PLANS SHALL BE PROVIDED AS INDICATED. ADDITIONAL PRODUCTS
NECESSARY FOR PROFESSIONAL WIRE MANAGEMENT WITHIN THE MAIN EQUIPMENT ROOM <ER>
AND ALL TELECOMMUNICATION ROOMS <TR> SHALL BE ALSO BE PROVIDED AS NECESSARY.
Q. PROVIDE A MINIMUM OF ONE (1) 2-INCH DIAMETER THROUGH-THE-WALL CONDUIT SLEEVES FOR
USE AS COMMUNICATION AND SECURITY CABLE PATHWAYS INTO EACH SPACE CONTAINING
COMMUNICATION AND SECURITY DEVICES. ROUTE CONDUITS FROM ABOVE ACCESSIBLE CEILING
TO THE NEAREST HALLWAY/CORRIDOR FEATURING AN ACCESSIBLE CEILING CAVITY.
6/25/2019 10:57:30 AM

SCALE: As indicated

HORZ:

VERT:

CONTRACT NO:

180881
SHEET

T-001
KEYED NOTES
MECHANICAL/ELECTRICAL ENGINEERS
T1 RELOCATE EXISTING SOUND SYSTEM EQUIPMENT RACK. SEE ED WWW.KLHENGRS.COM 06/25/19
DRAWINGS FOR ORIGINAL LOCATION. VERIFY CONDITION OF EQUIPMENT
PRIOR TO REMOVAL. BRING ANY FAULTS TO OWNER/DESIGNER 1538 ALEXANDRIA PIKE, SUITE 11
ATTENTION. FT. THOMAS, KENTUCKY 41075
800-354-9783
T2 EXISTING SPEAKER. CLEANED AND REINSTALL. TYPICAL OF ALL
SPEAKERS. 859-442-8050
859-442-8058 FAX
T3 EXISTING DEVICE. REMOVE DURING DEMOLITION STAGE AND REINSTALL
DURING CONSTRUCTION STAGE IN THE SAME LOCATION. IMMEDIATELY
LEXINGTON, KENTUCKY
BRING ANY FAULTS TO OWNER/DESIGNER ATTENTION.
LOUISVILLE, KENTUCKY
T4 EXISTING DISPLAY; RELOCATED FROM OTHER LOCATION. SEE ED PLANS. COLUMBUS, OHIO
T5 PROVIDE SAMSUNG LH49DCJPLGA/G0 WITH CHIEF TS318TU DISPLAY NEW YORK, NEW YORK
MOUNT

GYMNASIUM
105

BY
DATE
REVISIONS
LOBBY
101

FP

REV
ELEVATOR
104

SMB
06/26/2019

MSN
FRONT DESK
T1 102

PG.
APPROVED BY:
CHECKED BY:
DRAWN BY:
VESTIBULE

DATE:

F.B.
NO.
100

S S

TECHNOLOGY UPPER LEVEL PLAN DEFAULT


T2

T3
S

10990 THORNVIEW DRIVE, CINCINNATI OHIO 45241


FP

SHARONVILLE COMMUNITY CENTER


T3

LOBBY AND FITNESS ROOM RENOVATION


FP

T4 FP

FITNESS ROOM
103

S S
S

96"
? T5
FP

T3
FP

T5
S
96"
? FP
S

S S S
T3 T4
FP
T3
C C

CT UPPER LEVEL - FLOORPLAN - DEFAULT


NTS
6/25/2019 10:57:35 AM

SCALE: 1/8" = 1'-0"

HORZ:

VERT:

CONTRACT NO:

180881
SHEET

T-101
MECHANICAL/ELECTRICAL ENGINEERS
WWW.KLHENGRS.COM 06/25/19
1538 ALEXANDRIA PIKE, SUITE 11
FT. THOMAS, KENTUCKY 41075
800-354-9783
859-442-8050
859-442-8058 FAX

LEXINGTON, KENTUCKY
LOUISVILLE, KENTUCKY
COLUMBUS, OHIO
NEW YORK, NEW YORK

LABELING NOTES: PROJECT COORDINATION SCHEDULE EACH CABLE SHALL BE LABELED


ON EACH END WITHIN 4-6"

BY
A. ALL CABLES SHALL HAVE A LABEL AFFIXED TO THE JACKET AT EACH END 3" PANEL OR 12" AT WORKSTATION FINISH/COLOR STYLE JACK FRAME OF THE TERMINATION (TYPICAL)
ER/TR
FACEPLATE. THIS LABEL SHALL IDENTIFY THE SOURCE, DESTINATION, AND PORT IDENTIFIER. FACEPLATE STAINLESS STEEL DECORA GRAY BACKBOAR TRx-153-C1
EXAMPLE: C-XX-YYYY-1A01-YYYY YYYY-SVID. D

DATE
B. THESE DETAILS ARE NOT INTENDED TO SHOW EXACT PROJECT REQUIREMENTS FOR
RACK/CABINET LAYOUTS, FACEPLATE CONFIGURATION, EXACT CABLE TYPES, CABLE CABLES RATING
DESTINATIONS OR CABLE QUANTITIES. THESE DETAILS DO DIAGRAMMATICALLY INDICATE CABLES IN AIR HANDELING CEILING OR FLOOR SPACE PLENUM
PROJECT REQUIREMENTS FOR LABELING, COLOR-CODING, AND TERMINATIONS FOR THIS
PROJECT. USE THESE DETAILS AS A GUIDE; SUBMIT ANY QUESTIONS IN WRITING WITH THE CABLES IN FULLY DUCTED CEILING OR FLOOR SPACE RISER
PROCEDURE FOUND IN THE SPECIFICATIONS. 4" SLOTTED ROUTE CABLE
C. IN CAMPUS ENVIRONMENTS WITH MULTIPLE BUILDINGS, EACH TELECOMMUNICATIONS ROOM CABLES IN CONTINIOUS METAL CONDUIT RISER FINGER DUCT THROU DUCT
SHALL HAVE A UNIQUE IDENTIFIER CONSISTING OF 1] CAMPUS, 2] UNIQUE 2 LETTER BUILDING OSP WATER BLOCKED [NOTE 1] WITH COVER AND COIL
CABLES OUTDOORS OR WET LOCATIONS
CODE, AND 3] ROOM NUMBER.
D. COORDINATE “FINAL” ROOM NUMBERS OR IDENTIFIERS WITH OWNER PRIOR TO PERFORMING

REVISIONS
WORK; ALL LABELING SHALL CONFORM TO OPERATIONAL ROOM IDENTIFIERS FOR BUILDING USE. CABLE TYPE CABLE COLOR TERMINATION 1 TERMINATION 2 GRADE
IF ACTUAL ROOM NUMBER AND ARCHITECTURAL ROOM NUMBERS ARE DIFFERENT, BOTH SHALL
HORIZONTAL VOICE 4 PAIR UTP BLUE HORIZONTAL PANEL SAME AS JACK FRAME CAT 6
BE INCLUDED ON AS-BUILT FLOORPLANS.
E. IN EACH ER/TR, "HORIZONTAL" PATCH PANELS SHALL BE LABELED WITH AN ALPHA DESIGNATOR HORIZONTAL DATA 4 PAIR UTP BLUE HORIZONTAL PANEL SAME AS JACK FRAME CAT 6
RF
PURSUANT TO THE TOP AREA OF IT'S MOUNTING POSITION. THIS, IN CONJUNCTION WITH THE HORIZONTAL WAP 4 PAIR UTP GREEN S. U. PANEL [NOTE 3] GREEN JACK CAT 6A BROADBAND
PORT NUMBER OF EACH PORT, WILL BE THE UNIQUE LINK IDENTIFIER. TRx-153
HORIZONTAL CAMERA 4 PAIR UTP YELLOW S. U. PANEL [NOTE 3] YELLOW JACK CAT 6 VIDEO
F. EACH CABLE (LINK) SHALL HAVE A LABEL CONSISTING OF THE ORIGINATING POINT (ER/TR), THE
B4 B5

DISTRIBUTION
UNIQUE IDENTIFIER, AND THE DESTINATION POINT (ROOM). HORIZONTAL VIDEO 4 PAIR UTP GRAY S. U. PANEL [NOTE 3] GRAY JACK CAT 6 B6

G. FIBER OPTIC PANELS SHALL BE IDENTIFIED WITH SOURCE, DESTINATION, STRAND IDENTIFIER AS S. U. PANEL [NOTE 3] PURPLE JACK
HORIZONTAL "OTHER" 4 PAIR UTP VIOLET CAT 6
WELL AS WITH THE CORE DIAMETERS.
S. U. PANEL [NOTE 3] ORANGE JACK COORDINATE ALL
H. LABEL CROSS-CONNECT FIELDS, RACK/CABINET PANELS, FACEPLATES, CABLES ETC. UTILIZING HORIZONTAL MEDICAL 4 PAIR UTP ORANGE CAT 6
WALL-MOUNTED
THE EXAMPLES IN THE DIAGRAM AS A GUIDE. LOCAL CONTROL [NOTE 2] 4 PAIR UTP WHITE WHITE JACK WHITE JACK CAT 6 EQUIPMENT WITH 3D

REV
COPPER BACKBONE MULTI-PAIR UTP GRAY 110 STYLE BLOCKS BACKBONE PANEL CAT 3 THE OWNER.
FIBER OPTIC BACKBONE SINGLEMODE YELLOW SC CONN IN PANEL SC CONN IN PANEL OS2

SMB
06/26/2019

MSN
FIBER OPTIC BACKBONE MULTIMODE 50/125 AQUA SC CONN IN PANEL SC CONN IN PANEL OM4
HORIZONTAL RF RG-6 VIDEO COAX BLACK F STYLE ON DEVICE F STYLE ON FP CPLR N/A TERMINATION NOTES (THIS DETAIL)

PG.
RF BACKBONE RG-11 VIDEO COAX BLACK F STYLE ON DEVICE F STYLE ON DEVICE N/A A. TERMINATE ALL HORIZONTAL COAXIAL CABLES WITH COMPRESSION TYPE F-STYLE

APPROVED BY:
CONNECTORS ON BOTH ENDS.

CHECKED BY:
B. PROVIDE A F-STYLE BULKHEAD FITTING TO LAND CABLE TERMINATION AT OUTLET LOCATIONS.

DRAWN BY:
NOTE 1: SPLICING MAY BE REQUIRED UNLESS AN INDOOR/OUTDOOR CONSTRUCTION IS UTILIZED WITH THE
CORRECT NEC RATING. C. HORIZONTAL COAXIAL CABLES WILL LAND ON BULKHEAD FITTINGS AT THE OUTLET END AND
COILED ON THE ER/TR BACKBOARD FOR DEVICE ATTACHMENT.

DATE:
NOTE 2: LOCAL CONTROL CABLES ARE POINT TO POINT AND DO NOT HAVE AN ER/TR DESTINATION

F.B.
NO.
NOTE 3: SPECIAL USE PANEL REFERENCE IS APPLICABLE IN PROJECTS SO EQUIPPED; SEE ENLARGED
RACK LAYOUT FOR PANEL REQUIREMENTS
NOTE 4: WHERE CABLE GRADE IS SPECIFIED IT SHALL BE INTERPRETED THAT THE GRADE OF BOTH CABLE
AND TERMINIATIONS SHALL MATCH. 271533.00-06 - HORIZONTAL COAX CABLING
SCALE: NONE
EACH CABLE SHALL BE LABELED

10990 THORNVIEW DRIVE, CINCINNATI OHIO 45241


SHARONVILLE COMMUNITY CENTER
ON EACH END WITHIN 4-6" LABELING ORDER HORIZONTAL CABLES
OF THE TERMINATION (TYPICAL) TEL A TELEPHONE BACKBONE
ROOM TYPE
+78" 1 6 7 12 13 18 19 24 ROOM IDENTIFIER

LOBBY AND FITNESS ROOM RENOVATION


WAP
SPECIAL USE - WAP / CTL / CAM DESTINATION ROOM #
PANEL IDENTIFIER LABEL SHALL BE
SU

TRxx-101-SU1 TRxx-101-A3,A4
TRx-168-SU6 PANEL IDENTIFIER
153

48PT FONT WITH NORMAL WIDTH ON


1 67 1213 1819 24
.7" MIN WHITE TAPE WITH BLACK PANEL PORT NUMBER

TECHNOLOGY DETAILS
EACH CABLE SHALL BE C
LABELED ON EACH END WITHIN LETTERS
4-6" OF THE TERMINATION
(TYPICAL)
TRxx-101-CAM1
SU 153-6
SPECIAL USE - WAP / CTL / CAM

1 6 7 12 13 18 19 24

153 153 153 168

WAP
ROOM IDENTIFIER LABEL SHALL BE
TRXX-1234-A01
1 48p HORIZONTAL PATCH PANEL 24
B

9PT FONT WITH NORMAL WIDTH ON BACKBONE CABLES


.35" WHITE TAPE WITH BLACK
ORIGINATION IDENTIFIER
TRxx-101-SU2,SU3
LETTERS DESTINATION IDENTIFIER
TRx-168-C7 TRxx-101-A5,A6 153-4
CABLE TYPE
1 6 STRAND/FIBER COUNT
TRx-153
B4 B5 2D B 48p HORIZONTAL PATCH PANEL

IDENTIFIER IF MULTIPLES
TRxx-101-A1,A2
B6
LABELING NOTES (THIS DETAIL)
W CABLE TYPES
A. PANEL IDENTIFIERS SHALL BE USED TO IDENTIFY THE USE OF PANELS AND TO CREATE A FS – SINGLEMODE FIBER
2D
UNIQUE CABLE ID. TRXX-ERXX-FS72[A] FM – MULTIMODE FIBER
B. HORIZONTAL CABLE TERMINATION PANELS SHALL BEGIN WITH PANEL “A” AND CONTINUE CT – TWISTED PAIR COPPER
TERMINATION NOTES (THIS DETAIL) ALPHABETICALLY TOP TO BOTTEM.
ENTRANCE CX - COAXIAL
A. TERMINATE ALL HORIZONTAL 4 PAIR UTP CABLES TO EIA/TIA T568b WIRING SPECIFICATION ON C. A RACK WILL BE LIMITED ON THE QUANTITY OF PANELS; CONTINUE THE LETTERING LABELING NOTES (THIS DETAIL)
BOTH ENDS. SEQUENCE IN THE NEXT RACK.
B. ALL HORIZONTAL 4 PAIR CABLES SHALL TERMINATE AT THE WORKSTATION ON JACKS AND AT D. WHERE SO NOTED, SPECIAL USE PANELS MAY BE USED TO SEGREGATE CERTAIN CABLE A. LABELING PATTERN EXAMPLES REPRESENT MINIMUM REQUIREMENTS. (CAMPUS
LABELING NOTES (THIS DETAIL) USES.
THE ER/TR/REMOTE CABINET ON PANELS. PROJECTS SHALL ALSO INCLUDE A BUILDING IDENTIFIER).
C. CABLES AND JACKS MAY BE COLOR CODED; SEE DRAWINGS FOR DETAILS. A. WHERE CABLE HAVE THE SAME SOURCE AND DESTINATION (ROOM) THE LABELING ORDER E. SPECIAL USE DESIGNATORS MAY BE CAM, WAP, TEL OR SU (WHEN THE PANEL IS USED FOR B. EVERY CABLE SHALL BE LABELED AT EACH END WITHIN 4 TO 6" OF THE TERMINATION.
D. HORIZONTAL 4 PAIR CABLES MAY BE SEGREGATED ON SEPARATE PATCH PANELS SUCH AS WILL BE CLOCKWISE FROM THE ROOM ENTRANCE. WALL OUTLETS WILL PRECEDE CEILING MORE THAN ONE TYPE). POSITION AND ORIENT LABEL TO BE READABLE WITHOUT DISASSEMBLY.
“SPECIAL USE”, “WAP” “CAM”. SEE ENLARGED RACK LAYOUT FOR PROJECT REQUIREMENTS. DEVICES. F. ALL LABELS SHALL BE APPLIED STRAIGHT. C. EXISTING FACILITIES SHALL FOLLOW PRE-EXISTING LABELING PATTERNS; COORDINATE
E. CABLES SHALL BE LANDED IN ALPHANUMERIC ORDER ON PANELS BY CABLE ID. G. UNLESS OTHERWISE NOTED LABELS SHALL BE BLACK TEXT ON WHITE BACKGROUND. WITH OWNER.

271513.00-18 - HORIZONTAL COPPER CABLING 270553.00-08 - OUTLET LABELING SEQUENCE 270553.00-04 - PATCH PANEL LABELING 270553.00-01 - CABLE LABEL PATTERNS
SCALE: NONE SCALE: NONE SCALE: NONE SCALE: NONE
6/25/2019 10:57:41 AM

SCALE: 1/8" = 1'-0"

HORZ:

VERT:

CONTRACT NO:

180881
SHEET

T-501
SEE OUTLET CONDUIT PATHWAY NOTES: WORKSTATION OUTLET NOTES:
DETAIL FOR ADDITONAL A. CONDUIT SHALL BE CONSTRUCTED OF MATERIAL SUITABLE FOR THE ENVIRONMENT. INDOOR
INFORMATION ENVIRONMENTS SHALL UTILIZE EMT. AREAS SUBJECT TO MOISTURE INCLUDING HUMIDITY SHALL A. DETAILS SHOWN ARE DIAGRAMMATIC AND ARE INTENDED TO DEFINE PROJECT REQUIREMENTS.
BE GALVANIZED RIGID CONDUIT. B. UTILIZE THE PROJECT COORDINATION SCHEDULE FOR DEVICE SPECIFICS INCLUDING STYLE, MECHANICAL/ELECTRICAL ENGINEERS
TAHC OR NON-ACCESSIBLE
B. CONDUITS PENETRATING/INTERSECTING BUILDING EXPANSION JOINTS SHALL UTILIZE EXPANSION COLORS, AND RATINGS. PROVIDE ALL FACEPLATES. JACK FRAMES, BLANKS AND TERMINATION
CEILING WOULD REQUIRE WWW.KLHENGRS.COM
CABLE SUPPORT SHALL BE LOCATED IN JOINT FITTINGS. DEVICES. 06/25/19
CONDUIT TO EXTEND TO
CLOSE PROXIMITY TO ROUGH-IN TO C. SLEEVES THROUH FIRE-RATED FLOORS AND WALLS SHALL UTILIZE STI E-Z PATH SELF SEALING C. OUTLET SUBSCRIPT LEGEND WILL DEFINE THE CONNECTIVITY REQUIREMENTS OF THE INSTANCE.
CORRIDOR ACCESSIBLE 1538 ALEXANDRIA PIKE, SUITE 11
PROVIDE SUPPORT FOR SERVICE LOOP SLEEVE ASSEMBLIES. D. OUTLET SUBSCRIPT LEGEND WILL DEFINE THE TYPICAL MOUNTING HEIGHT. CO-LOCATED
CEILING(NOT SHOWN) SEE OUTLET FT. THOMAS, KENTUCKY 41075
D. SLEEVES THROUGH FLOORS SHALL HAVE A 2" CURB ABOVE THE FINISHED FLOOR TO PREVENT OUTLETS SHALL MATCH ELECTRICAL DEVICE HEIGHT.
CONDUIT FOR DETAILS 800-354-9783
ACCIDENTAL FLUID LEAKAGE TO AREAS BELOW. E. MOUNTING HEIGHT IS O.C. (ON CENTER OF DEVICE) EITHER AFF (ABOVE FINISHED FLOOR) OR BCL
BUSHING 859-442-8050
ACCESSIBLE CEILING LINE E. ALL CONDUITS OVER 3' IN LENGTH SHALL BE GROUNDED PURSUANT TO THE CODE AND (BELOW CEILING LINE).
859-442-8058 FAX
APPLICABLE STANDARDS. F. SUBSCRIPTS MAY ALTER MOUNTING HEIGHT WITH AN EXC (EXCEPTION). ANY EXCEPTION TO THE
CONDUIT ELBOW SHALL TURN-OUT F. DIAGRAM ADDRESSES BACKBONE PATHWAYS; ADDITIONAL PATHWAY MAY BE REQUIRED FOR BASE DEVICE HEIGHT IS FOR THE SPECIFIC INSTANCE; ALL OTHER INSTANCES ARE AT BASE
DEVICE HEIGHT. LEXINGTON, KENTUCKY
AT APPROXIMATELY 6" ABOVE HORIZONTAL CABLES TO ENTER TELECOMMUNICATIONS ROOMS, CABINETS OR PATHWAY LOUISVILLE, KENTUCKY
ACCESSIBLE CEILING SYSTEM. G. DEVICES DESIGNATED WITH THE “CH” SUBSCRIPT (COUNTER HEIGHT) SHALL BE CLOSELY
COORDINATED IN THE FIELD WITH ARCHITECTURAL CASEWORK AND FURNITURE VENDORS COLUMBUS, OHIO
G. HORIZONTAL CABLES EXPOSED IN GARAGE AND SERVICE AREAS (NOT CONDITIONED OFFICE NEW YORK, NEW YORK
AREAS) SHALL BE RUN IN GRC CONDUIT. PRIOR TO ROUGH-IN.
CONDUIT SHALL EXTEND TO H. PATHWAYS SHALL NOT BE OVER-FILLED. SEE DETAILS AND STANDARDS FOR SIZING H. MOUNTING HEIGHTS FOR USE IN BLOCK WALLS SHALL BE ADJUSTED TO FIT THE COURSE AND
ACCESSIBLE CEILING CAVITY WITHIN INFORMATION. SHALL BE CONSISTANT WITH THE ELECTRICAL DEVICE MOUNTING HEIGHT.
OR ADJACENT TO SPACE SERVED I. THIS DIAGRAM INDICATES MINIMUM PULL/JUNCTION BOX REQUIREMENTS. ADDITIONAL BOXES I. OUTLET REQUIREMENTS WHERE POWER/COMMUNICATIONS MUST BE CO-LOCATED, SEPARATION
AND MARKED WITH AN INDELABLE WILL BE REQUIRED TO COMPLY WITH GENERAL RULES FOR PULLING DISTANCE AND NUMBER OF OF THE CABLING SHALL BE REQUIRED.
MARK BENDS BETWEEN PULL POINTS. J. WHERE MULTI-COMPARTMENT SURFACE RACEWAY, FLOORBOXES, OR FIRE-RATED
J. ALL JUNCTION/PULL BOXES SHALL BE METALLIC AND RATED FOR USE WITH THE REQUIRED POKETHROUGHS ARE REQUIRED - SUBSTITUTE 4-PORT JACK FRAMES AND INTEGRAL
MINIMUM ONE 1" FACEPLATE(S) IN PLACE OF THE SINGLE/DOUBLE GANG FACEPLATES SHOWN ON THIS DRAWING.
VARIES CONDUITS AND IN THE ENVIRONMENT WHERE BEING UTILIZED.
CONDUIT K. SURFACE RACEWAY OUTLET LOCATIONS REQUIRING FOUR (4) OR FEWER PORTS SHALL UTILIZE A
K. 4" CONDUITS WILL HAVE 3 X 3 CELL MAXCELL TEXTILE INNER-DUCTS IN THE PRIMARY CONDUIT.
PER “GANG” SINGLE 4 PORT JACK FRAME AND FACEPLATE, BLANKING ANY ADDITIONAL GANGS.
SECONDARY CONDUITS SHALL HAVE A PULL ROPE INSTALLED. TIE OFF ALL DUCTS AND PULLING
ROPE TO PREVENT BEING RETRACTED INTO CONDUIT. L. DETERMINE THE FINAL FLOOR DEVICE WITH THE ROUGH-IN INSTALLER. COORDINATE THE
BOX SIZED TO L. CONDUITS IN OPEN CEILING AREAS SHALL BE TRAPEZE MOUNTED. APPROPRIATE FACEPLATE MOUNTING BASED ON MANUFACTURER, SIZE, AND STYLE OF FLOOR
SUPPORT M. STANDARDS REQUIRE COLOR CODING AND IDENTIFICATION OF PATHWAYS. SEE THE STANDARD DEVICE.
FACEPLATE GANG AND DETAILS FOR REQUIREMENTS. M. FILL ALL UNUSED OPENINGS WITH BLANKS WHERE NOT NEEDED.
REQUIREMENT – SEE N. PULL BOXES SHOWN OUTSIDE THE BUILDING WOULD BE OPEN BOTTEM HAND HOLES WITH A N. OUTLET CABLES SHALL CONTINUE TO THE POINT OF ORIGIN AS SHOWN IN THE OUTLET/DEVICE
DETAIL MINIMUM OF 36"X36". SEE DETAILS FOR SIZING REQUIREMENTS. LEGEND; INCLUDE TERMINATION OF BOTH ENDS OF EACH CABLE.
O. EXPOSED CONDUIT SHALL NOT BE PERMITTED IN FINISHED AREAS UNLESS SPECIFICALLY NOTED. O. TR (TELECOMMUNICATIONS ROOM) TBB (TELECOMMUNICATIONS BACKBOARD) ORIGINATIONS
SURFACE MOUNTED BACK BOXES AND MATCHING RACEWAY SHALL BE USED FOR DEVICES THAT REFER TO THE TELECOMMUNICATIONS ROOM SERVING THE AREA. TBB PNL REFERS TO A
VARIES - SEE DETAIL ARE NOT INSTALL WITHIN A WALL OR CEILING. SYSTEMS PANEL MOUNTED ON THE BACKBOARD.
P. CONDUIT INSTALLER SHALL INSTALL BUSHING AND PULL STRING IN CONDUITS IMMEDIATELY P. TR (TELECOMMUNICATIONS ROOM) PANEL ORIGINATION REFERS TO HORIZONTAL CROSS-
AFTER INSTALLATION. CONNECTS SERVING THE AREA. THESE MAY BE MIXED USE HORIZONTAL OR SPECIAL USE
PANELS. SEE ROOM DETAILS FOR PANEL LAYOUTS.
Q. AVR (AUDIO VISUAL RACK) ORIGINATION REFERS TO CONNECTION TO EQUIPMENT MOUNTED IN
THE A/V RACK. INSTANCES WILL BE LOCATED AS SHOWN ON THE FLOORPLANS. SEE A/V DIAGRAM
FOR CONNECTIVITY DETAILS.

270528.00-03 - WALL OUTLET PATHWAY AND MOUNTING

BY
SCALE: NONE
UNLESS NOTED AS “TAHC”, NO MORE THAN 180 DEGREES OF QUANTITY OF JACKS VARY
FACEPLATE WITH

DATE
AREAS WHERE CABLE(S) TO BENDS OR 100 FEET IN LENGTH WITH SUBSCRIPT; SEE
ACCESSIBLE WITHOUT ACCESSIBLE PULL BOX GROMMETED HOLE
DESTINATION PATHWAY FOR LEGEND THIS DETAIL
CEILING WILL CONCEAL
THE SYSTEM MAY SPEAKER ATTACHMENT
CABLE SEE PROJECT COORDINATION SEE PROJECT COORDINATION
BLOCKING FOR SINGLE BLOCKING FOR TWO HORIZONTAL CABLES FOR BUSHING VARY SCHEDULE FOR COLOR- SCHEDULE FOR COLOR-CODING
STUD STYLE DISPLAY STUD / MULTI-POINT THE PATHWAY TO TRAY; ADJUST HEIGHT OF RUN AS SURFACE
MOUNTS. STYLE DISPLAY MOUNTS CODING AND PROJECT SPECIFIC
ROUGH-IN MAY TURN OUT ELBOW; SEAL NECESSARY TO FIT MOUNTED / RECESSED AND PROJECT SPECIFIC INFORMATION
SUSPENDED 4 PORTS OR FEWER
INTO ROOM AND J-HOOK AROUND ENVIRONMENT INFORMATION
PATHWAY MAY BE AND MINIMIZE BENDS ** OUTLET DEVICE LEGEND
PENETRATIONS
WOOD STUD UTILIZED. SLEEVE AND ** OUTLET DEVICE LEGEND
CEILING LINE BASE OUTLET/DEVICE

REVISIONS
FIRESTOP ALL
INSTALL WOOD STUD
PENETRATIONS MINIMUM ONE 1" CONDUIT BASE OUTLET/DEVICE
IN METAL STUD TURN OUT A MINIMUM OF 4" SQUARE BOX, ONE (1) 1" CONDUIT
PER “GANG” CONTINIOUS
CAVITY 6" ABOVE CEILING 4" SQUARE BOX, ONE (1) 3/4" CONDUIT,SINGLE DEVICE TRIM RING
TO OUTLET BOX SINGLE DEVICE TRIM RING, SINGLE GANG FACEPLATE
CEILING LINE GROMMETED FACEPLATE, DIRECT CONNECTION
NOTES (THIS DETAIL): SUBSCRIPT TERMINATION CABLE MTG HT ORIGINATION
1" X 8" WOOD BLOCKING SUBSCRIPT TERMINATION CABLE MTG HT ORIGINATION
A. ALL REFERENCES TO CONDUIT SIZE SHALL BE TO THE RECOGNIZED TRADE SIZE. NONE ONE (1) RJ45 JACK ONE (1) 4 PAIR 18" O.C. AFF TR PANEL
SPACE FOR FACE SECURED TO STUDS
B. UNLESS OTHERWISE SPECIFICALLY NOTED, ALL CONDUIT BENDS SHALL BE ACCOMPLISHED WITH NONE SPEAKER – SEE
SPECIFICATION ONE (1) 1 PAIR AUDIO CLG SEE SYSTEM
DIAGRAM

PLATE(S) OR IN- ADDITIONS TO BASE OUTLET/DEVICE


WALL DISPLAY SPACE FOR FACE FACTORY ELBOWS WITH A BEND RADIUS EQUAL OR GREATER THAN 4 TIMES THE TRADE SIZE. ADDITIONS TO BASE OUTLET/DEVICE
BACKBOX PLATE(S) OR IN-WALL EXAMPLE:1" – BEND RADIUS GREATER THAN 4", 90 DEGREE FITTING LENGTH APPROXIMATELY 15". SUBSCRIPT TERMINATION CABLE MTG HT EXC ORIGINATION
DISPLAY BACKBOX C. CONDUITS SHALL BE ATTACHED TO BOXES WITH A BOX CONNECTOR FITTING AND THREAD-ON [X] SPECIAL SPEAKER TYPE –
SEE SPECIFICATION MFGR INST
BUSHING. CONDUIT ENDS NOT TERMINATING AT A BOX OR ENCLOSURE SHALL HAVE A NYLON 1D NO ADDITIONAL

REV
TWO-STUD / MULTI- WG WIREGUARD
BUSHING. 2D ONE (1) RJ45 JACK ONE (1) 4 PAIR TR PANEL
POINT STYLE DISPLAY
MOUNT. D. PULL STRINGS SHALL BE INSTALLED IN ALL CONDUITS.
PROVIDE (3) E. MINIMUM CONDUIT REQUIREMENTS SHALL BE A 1" TRADE SIZE CONDUIT. PER GANG. TWO 1" WAP ONE (1) RJ45 JACK ONE (1) 4 PAIR [NOTE 1] 6" BCL TR PANEL
WOOD BLOCKED CONDUITS MAY BE REPLACED BY A SINGLE 1 ¼” CONDUIT. INTEGRAL BACK BOX, ONE (3/4) 1" CONDUIT

SMB
06/26/2019

MSN
STUDS IN THE STUD SPACE
F. KNOCK OUT REQUIREMENTS EXCEEDING MANUFACTURER’S STANDARD SIZES SHALL BE 3D TWO (2) RJ45 JACKS TWO (2) 4 PAIR TR PANEL
LOCATION OF SPRAKER GRILL AND TRIM RING, DIRECT CONNECTION
DISPLAY. SEE ACCOMODATED WITH A PUNCH OF THE CORRECT SIZE HOLE; FILE SHARP EDGES AND BURRS. 4D THREE (3) RJ45 JACKS THREE (3) 4 PAIR TR PANEL

PG.
FLOOR PLANS. 60" AFF U.O.N G. CONDUIT SHALL BE EMT UNLESS OTHERWISE NOTED. [X] RECESSED SPEAKER –
SEE SPECIFICATION MFGR INST
H. EXCEPTION: CONDUIT(S) FOR FLOORBOXES SHALL HAVE A TRANSITION BOX ABOVE ACCESSIBLE

APPROVED BY:
CHECKED BY:
CEILING; SEE FLOORBOX DETAILS FOR REQUIREMENTS. WG WIREGUARD

DRAWN BY:
TYPICAL METAL
FRAMING

DATE:
FINISHED FLOOR

F.B.
NO.
[X] INDICATES A SPECIFIC SPEAKER TYPE; SEE SPECIFICATION. **
S **
[X]
274100.00-03 - WALL DISPLAY BLOCKING 270528.00-02 - OUTLET CONDUIT

10990 THORNVIEW DRIVE, CINCINNATI OHIO 45241


271543.00-07 - CEILING SPEAKER OUTLET WALL OUTLET 271513.00-13 - WALL DATA OUTLET

SHARONVILLE COMMUNITY CENTER


WALL OUTLET
SCALE: NONE SCALE: NONE SCALE: NONE SCALE: NONE

LOBBY AND FITNESS ROOM RENOVATION


TYPICAL BUILDING STRUCTURE
ROUGH-IN NOTES (THIS DETAIL): QUANTITY OF JACKS VARY WITH
(ADJUST MOUNTING AS NECESSARY) PROVIDE FACEPLATE SUBSCRIPT; SEE LEGEND THIS
A. SURFACE MOUNTED HOUSING(S) SHALL BE STRAPPED TO BUILDING STRUCTURE AND COMPATIBLE WITH THE DETAIL
MINIMUM 1” SERVICE LOOP SUPPORT SHALL BE CLAMPED TO ALLOW RE-POSITIONING AS REQUIRED WALL ENCLOSURE

TECHNOLOGY DETAILS
CONDUIT BY SYSTEM INSTALLER.
SEE PROJECT COORDINATION
SCHEDULE FOR COLOR-CODING
AND PROJECT SPECIFIC
CONDUIT SHALL INFORMATION
ANCHOR SECURELY
EXTEND TO
WITH ** OUTLET DEVICE LEGEND
VARIES NEAREST
LOCKNUTS TO SECURED
ACCESSIBLE
CONDUIT TO SUPPORT A BASE OUTLET/DEVICE
CEILING
MINIMUM OF 20 POUNDS
OR PATHWAY RECESS WALL BOX BY TYPE [X], MIN. 1 1/4" CONDUIT
CEILING
JACK FRAME(S) AND INTEGRAL FP OR STANDARD FP
OUTLET BOX
SUBSCRIPT TERMINATION CABLE MTG HT ORIGINATION
FIXED UN-ACCESSIBLE CEILING NONE “F” FEEDTHROUGH RF VIDEO COAX 54" O.C. AFF TR TBB
TYPICAL BUILDING STRUCTURE ONE (1) RJ45 JACK ONE (1) 4 PAIR TR PANEL
(ADJUST MOUNTING AS NECESSARY) TYPICAL BUILDING STRUCTURE
(ADJUST MOUNTING AS ADDITIONS TO BASE OUTLET/DEVICE
NECESSARY)
SUBSCRIPT TERMINATION CABLE MTG HT EXC ORIGINATION
1D NO ADDITIONAL
DUAL PORT SURFACE 2D ONE (1) RJ45 JACK ONE (1) 4 PAIR TR PANEL
HOUSING; PLENUM RATED OR CABLE(S) TO ER/TR UTILIZE CADDY SPEED
COMPLETELY WRAPPED WITH LINK CABLE(S) TO ER/TR 3D TWO (2) RJ45 JACKS TWO (2) 4 PAIR TR PANEL
UNIFRAX FYREWRAP 0.5 VARIES
TO SUPPORT DEVICE
VARIES GANG 2 - ADD GANGS AS NEEDED TO ACCOMMODATE CONNECTIVITY
MINIMUM 20' SERVICE
MINIMUM 10' SERVICE LOOP DUAL DEVICE TRIM RING, TWO GANG FACEPLATE
CEILING LINE LOOP
COILED ON SUPPORT
COILED ON SUPPORT PLENUM RATED CABLE CEILING LINE
PLENUM RATED CAT 6 NONE HDMI FEEDTHROUGH M-M HDMI CABLE LOCAL INPUT
UTILIZE CADDY SPEED LINK CLIPPED TO SUPPORT
(6A – WAP) PATCH
TO A
CABLE (RJ45) CLIPPED 4' SQUARE BOX WITH SINGLE BRACKET TO SUPPORT BOX
SUPPORT DEVICE
TO SUPPORT DEVICE TRIM RING (FLUSH) - MOUNTED FACE DOWN IN B
GROMMET KNOCK-OUT FOR TILE; CLIPS TO T-BAR GRID
ACCESSIBLE CEILING ACCESSIBLE CEILING
CABLE ENTRY C
[X] INDICATES THE WALL ENCLOSURE TYPE SEE ROUGH-IN DETAILS FOR ** {Y}
ADDITIONAL INFORMATION FP
{Y} INDICATES THE INSTANCE CORRELATING WITH SYSTEM DIAGRAM IN FORMAT OF x.### [X]
270528.00-04 - ABOVE CEILING OUTLET PATHWAY AND MOUNTING 271543.00-12 - WALL FLAT PANEL OUTLET
6/25/2019 10:57:45 AM

SPECIAL WALL OUTLET


SCALE: 1/8" = 1'-0"
SCALE: NONE SCALE: NONE HORZ:

VERT:

CONTRACT NO:

180881
SHEET

T-511