Design Siemens
Design Siemens
SPEEDFAXTM 2017
Contents
Types of Power Distribution Systems
Ground Fault Protection
T Section
T-2 – T-4
T-5 – T-10
Overcurrent Protection and Coordination T-11
System Analysis T-12
Current Limiting Circuit Breaker Technology T-13
Series-Connected Combination Ratings T-14
Harmonics / K-factor Ratings T-15 – T-16
Table 1:
Ampacities of Insulated Conductors T-17
Table 2:
Correction Factors for Ambient Temperatures T-17
Table 4A:
Motor Full-Load Currents of
Three Phase AC Induction Type Motors T-18
Table 4B:
Motor Full-Load Currents in Amperes,
Single Phase AC T-18
Table 4C:
Motor Full-Load Currents in Amperes, DC T-18
Table 4D:
Conversion Table of Polyphase Design T-18
Table 5:
Normal-Load and Fault Currents of
Three Phase Transformers T-18
Table 6:
Electrical Formulas for Finding Amperes,
Horsepower Kilowatts, and kVA T-19
Table 7:
Grounding Electrode Conductor for
AC Systems T-19
Table 8:
Minimum Size Grounding Conductors for
Grounding Raceways and Equipment T-19
Capacitor Circuit Conductors T-20
Conversion Table T-21
T
TECHNICAL
Scan to connect
online to the
most up-to-
date version of
this Section of
SPEEDFAX.
There are several basic considerations The low voltage service entrance circuit
which must be included by the system comes into the building through service
design engineer to select and design the entrance equipment and terminates at a
best power distribution system which will main switchgear assembly, switchboard or
supply power to both present and future panelboard. Feeder circuits are provided to
loads most economically. Among these the loads or to other subswitchboards,
are: distribution cabinets, or panelboards.
Figure 1 shows the two forms of radial
b Safety
circuit arrangements most frequently
b Reliability used. Under normal operating conditions,
b Maintenance the entire load is served through the
b Flexibility single incoming supply circuit, and in the
case of high voltage service, through the
b Voltage Regulation transformer. A fault in the supply circuit,
b Initial Investment the transformer, or the main bus will
b Simplicity of Operation cause an interruption of service to all
The characteristics of electrical service loads. A fault on one of the feeder or
available at the building site, the types of branch circuits should be isolated from the Figure 3. Expanded Radial Systems
loads, the quality of service required, and rest of the system by the circuit protective individual Primary Feeder Protection
the size and configuration of building are device on that circuit. Under this
also important factors that will influence condition, continuity of service is making it possible to limit outages due to
system design and circuit arrangement. maintained for all loads except those a feeder or transformer fault to the loads
served from the faulted circuit. associated with the faulted equipment. If
Four basic circuit arrangements are used
for the distribution of electric power. They The need for continuity of service often circuit breakers are used for primary
are the radial, primary selective, secondary requires multiple paths of power supply as feeder protection, the cost of this system
selective, and secondary network circuit opposed to the single path of power will be high. Even if fused switches are
arrangements. The following discussion of supply in the radial system. used, the cost of the arrangement of
these circuit arrangements covers both Figure 3 will exceed the cost of the
the high-voltage and low-voltage circuits. arrangement of Figure 2.
The reader should recognize that the high- Primary Selective System
voltage circuits and substations may be
The circuit arrangement of Figure 4
owned by either the utility company or the
provides means of reducing both the
building owner, depending upon the
extent and duration of an outage caused
electric rates, the practice, and
by a primary feeder fault. This operating
requirements of the particular electric
feature is provided through the use of
utility serving the specific building site.
duplicate primary feeder circuits and load
Radial System interrupter switches that permit
If power is brought into a building at connection of each secondary substation
utilization voltage, the simplest and the transformer to either of the two primary
lowest cost means of distributing the feeder circuits. Each primary feeder circuit
power is to use a radial circuit must have sufficient capacity to carry the
arrangement. The radial system is the Figure 2. Expanded Radial System—Single total load in the building.
Primary Feeder
simplest that can be used, and has the
lowest system investment. It is suitable for
smaller installations where continuity of A fault in a primary feeder in the
service is not critical. arrangement shown in Figure 2 will cause
the main protective device to operate and
interrupt service to all loads. If the fault
were in a transformer, service could be
restored to all loads except those served
from that transformer. If the fault were in
a primary feeder, service could not be
restored to any loads until the source of
trouble had been eliminated. Since it is to
T
when a fault occurs in either a primary Secondary Network System Figure 7. Simple Spot Network System
feeder or a transformer. Many buildings with radial distribution
The cost of the secondary selective systems are served at utilization voltage A simple spot network, such as shown in
system will depend upon the spare from utility secondary network systems. Figure 7, consists of two or more identical
capacity in the transformers and primary The network supply system assures a transformers supplied over separate
feeders. The minimum transformer and relatively high degree of service reliability. primary feeder circuits. The transformers
primary feeder capacity will be determined The utility network may take the form of a are connected to a common low voltage
bus through network protectors and are selective switching arrangement with
operated in parallel. A network protector each transformer, or by using three or
is an electrically operated power circuit more transformers. If the primary
breaker controlled by network relays in selective switching arrangement is used,
such a way that the circuit breaker the total load can be about 160 percent
automatically opens when power flows of the nameplate rating of one of the
from the low voltage bus toward the transformers. This produces an overload
transformer. When voltages in the on one transformer until such time as
system are such that power would flow the remaining transformer can be
toward the low voltage bus from the switched to the other feeder in the case
transformer, it will close automatically. of a primary feeder fault.
Network protectors are normally The interrupting duty imposed on the
equipped with relays which operate for low voltage protective devices in a spot
faults in the network transformer or high network substation is higher than in
voltage feeder only. The network is often radial, primary selective, or secondary
operated on the assumption that selective substations having the same
network failure will “burn” open. load capability because of the spare
Network protectors without transformer capacity required in the spot
supplementary protection do not meet network substation and because the
transformers are operated in parallel. Figure 9. Primary Selective Secondary
the requirements of the NEC for Network System
overcurrent, ground fault, or short circuit
protection. Protection of the network or various load buses. In normal operation,
collector bus may be added by providing the substations are about equally loaded
sensing devices, including ground fault and the current flowing in the tie circuits
detection, with tripping of the network is relatively small. However, if a network
protectors. The most common use of the protector opens to isolate a transformer
network protector, however, has been by on a primary feeder fault, the load on the
utilities in vaults where failure of the associated bus is then carried by the
network devices could cause damage adjacent network units and is supplied
limited to the vault. High integrity design over the tie circuits. This arrangement
involving wide phase separation and the provides for continuous power supply to
use of “catastrophe” fusing minimize the all low voltage load buses, even though a
danger and extent of a network failure. A primary feeder circuit or a transformer is
conventional circuit breaker with time taken out of service.
overcurrent and instantaneous trip In the network arrangement in Figure 9,
devices plus network relays can meet if there were three incoming primary
the NEC requirements. However, the full feeder circuits and three transformers,
reliability of the network may be the combined capacity of two of the
compromised since selectivity between transformers should be sufficient to carry
these devices is difficult to obtain. the entire load on the three substations
Under normal operating conditions, the Figure 8. Secondary Network System on the basis that only one feeder is out
total load connected to the bus is shared of service at one time. Generally, these
equally by the transformers. Should a The spare transformer capacity, the transformers would all have the same
fault occur in a transformer or on a pri network protectors, and the higher ratings. With this arrangement, as with
mary feeder, the network protector interrupting duty will make the secondary the spot network arrangement, a
associated with the faulted transformer network arrangement much more reduction in spare transformer capacity
or feeder will open on reverse power expensive than the other arrangements. can be achieved, if a primary selective
flow to isolate the fault from the low At the same time, these elements make switching arrangement is used at each
voltage bus. The remaining transformer the reliability of the network system substation transformer. However, if three
or transformers in the substation will greater than for the other system or more primary feeder circuits are
continue to carry the load and there will configurations. available, the reduction in transformer
be no interruption of service to the loads, The secondary network may also capacity achieved through the use of a
except for a voltage dip during the time take the form shown in Figure 8. primary selective arrangement may be
that it takes for the protective equipment In this arrangement there is only small.
T
to operate. one transformer in each secondary Cable ties or busway ties, as shown in
If only two transformers are used in a substation, and the substations are Figures 8 and 9, will require careful
interconnected by normally closed
TECHNICAL
would vaporize about 1.0 cubic in. of The ground sensor is located
which encircles all phase conductors (and downstream from the point at which the
copper or 2.5 cubic in. of aluminum. neutral on four wire system) to detect
Obviously a fault of the magnitude system is grounded and can be mounted
ground faults. either on the line side or load side of the
shown in Figure 10 could cause a
considerable amount of damage. The operation of this system is such that main disconnect device. This method can
under normal operating conditions (eg., be used on incoming main disconnect or
The nature of low-level arcing ground no ground fault on the system) there is on feeders.
faults makes impractical their detection
4-Wire System
To avoid false tripping, a fourth current
sensor is connected in the neutral
conductor to sense normal neutral
current. This fourth sensor is connected
so that it cancels the normal neutral
current which is developed in the residual
circuit as shown in Figure 15.
Under normal conditions, the vector sum
of the current in all phases equals the
neutral current. Disregarding the effects
of the neutral sensor connection, the
neutral current would flow through the
GND element. Since this is normal
neutral current, pickup of the GND
element is not desired. Therefore, the
neutral sensor is added to sense the
same neutral current as the GND sensor
— but opposite in polarity. The result is a
circulating current between the phase
sensing current sensors and the neutral
sensor, with no current flowing through
the GND sensor. This is similar to a Figure 15. Schematic for Ground Protection on 4-Wire Systems, Residual Sensing
differential relay circuit. When a phase-to-
ground fault occurs, the vector sum of fault current returns via the ground bus current exceeds the pickup setting of the
the phase currents will no longer equal and bypasses the neutral. If the GND element for the required time, the
the neutral current because the ground magnitude of the phase-to-ground trip unit will operate to open the breaker.
current bands of disconnects in series two modes of operation. If a ground fault system should be made before using this
must not overlap and must be separated occurs between it and the nearest type of interlocking.
TECHNICAL
from each other sufficiently to allow for downstream disconnect, it should operate For a zone selective system, the time-
the clearing time of each disconnecting in its fast tripping mode. current bands of disconnects in series,
means used. The time / current selective When a ground fault occurs beyond the although used only for backup protection,
system is recommended for applications downstream disconnect, the downstream should not overlap and should be
where damage levels associated with the GFP device should open in its fast separate from each other sufficiently to
time / current settings used are tolerable. tripping mode and simultaneously allow for the opening time of each
This type of system does not require disconnecting means used.
Typical Application Diagrams means can be utilized, providing it is and ground return sensors provide
Figures 18 through 23 on this and the suitable for use with a ground fault protection only on the load side of associ
facing page show the basic methods of protection system as indicated in the ated disconnects. If a vector summation
applying ground fault protection (GFP). scope of this application guide. The method is used and its sensors are
Other types of distribution systems will examples do not show protection against located on load side of a disconnect, the
require variations of these methods to a ground fault on the supply side of the zone between a source and actual sensor
satisfy other system conditions. main disconnect. location becomes the responsibility of
Sensing device and disconnect locations the next upstream protective device.
These diagrams show circuit breakers as
the disconnects. Any disconnecting define zones of protection. Source side
Figure 18 Figure 19
TECHNICAL
Figure 20 Figure 21
Ground Fault Protection on Main, Feeder and Selected Double-Ended System with Ground Fault Protection on
Branch Disconnects with Zone Selective Interlocking Main and on Tie and Feeder Disconnects
Note: Interlocking
Supplementary interlocking is
required but will vary depending
on equipment used.
Figure 22 Figure 23
T
TECHNICAL
Coordination of a power distribution plotted on standard log-log coordination where possible. Selective coordination is
system requires that circuit protective paper to facilitate the coordination study. usually obtained in low voltage systems
devices be selected and set so that when the log-log plot of time / current
electrical disturbances, such as over-loads Mechanics Of Achieving Coordination: characteristics displays a clear space
or short circuits, will be cleared promptly The process of achieving coordination between the characteristics of the
by isolating the faulted equipment with among protective devices in series is protective devices operating in series,
minimum service disruption of the essentially one of selecting individual units that is, no overlap should exist between
distribution system. Time / Current to match particular circuit or equipment any two time/current characteristics if
Characteristic Curves are available for protection requirements, and of plotting full selective coordination is to be
circuit protective devices, such as circuit the time/current characteristic curves of obtained. Allowance must be made for
breakers and fuses, which show how these devices on a single overlay sheet of relay overtravel and for relay and fuse
quickly they will operate at various values log-log coordination paper. curve accuracy. Quite often the
of overload and short circuit current. The achievement of coordination is a trial- coordination study will stop at a point
Coordination can be obtained by and-error routine in which the various short of complete selective coordination
comparing these curves for each device in time / current characteristic curves of the because a compromise must be made
series in the system. series array of devices are matched one between the competing objectives of
In developing the system, it will be noted against another on the graph plot. maximum protection and maximum
that many compromises must be made service continuity.
When selecting protective devices one
between the various objectives: must recognize ANSI and NEC Computer Aided Coordination:
1. System reliability. requirements and adhere to the limiting The philosophy discussed above applies
2. Continuity of service. factors of coordination such as load to the “classical” practice of performing
3. Equipment and system protection. current, short-circuit current, and motor coordination studies manually. Today,
4. Coordination of protective devices. starting. The protective devices selected however, there are numerous personal
5. System cost. must operate within these boundaries computer software programs available
Preliminary steps in Coordination study: while providing selective coordination for performing coordination studies.
A) One-line diagram: used as a base on
which to record pertinent data and
information regarding relays, circuit
breakers, fuses, current transformers, and
operating equipment while at the same
time, providing a convenient
representation of the relationship of circuit
protective devices with one another.
B) Short-circuit study: record all applicable
impedances and ratings; using these
values, a short-circuit study is made to
determine currents available at any
particular point in the system.
C) Determine maximum load currents
which will exist under normal operating
conditions in each of the power-system
circuits, the transformer magnetizing
inrush currents, and times, and the
starting currents, and accelerating times of
large motors. These values will determine
the maximum currents which circuit
protective devices must carry without
operating. The upper boundary of current
sensitivity will be determined by the
smallest values resulting from the
following considerations:
1) Maximum available short-circuit
current obtained by calculation.
T
and transformers.
3) Thermal and mechanical limitations
of equipment.
D) Time / current characteristic curves of
all the protective devices to be coordi
nated must be obtained. These should be Figure 24. Coordination of Example System
General 4. Load Flow Studies: calculate volt- component. Hence, the total fault current
Proper system design requires that the ages, phase angles, real and reactive is asymmetric with respect to the current
system be coordinated so the interrupting power, line and transformer loadings axis. The value of the DC component
capacity and / or short circuit withstand under simulated conditions to aid in depends on the point of the voltage wave
capabilities of the various components in determining the performance of a at which the fault was initiated. For
the system are not exceeded for any new or revamped system during the system studies, it is assumed that the
operating situation. Good practice also planning stage. fault is initiated at the worst point, to
requires that the system be selective, that 5. Motor Starting Studies: determine produce a “fully offset” fault current. This
is, that the minimum portion of the severity of voltage dips and adequacy is illustrated in Figure 25.
system be interrupted on occurrence of a of load accelerating torque when start- Short circuit currents are determined by
fault. The need for selectivity must always ing large motors on a weak system. the system impedance, including both
be balanced against the requirements of reactance and resistance. The effect of
Today, most studies are performed using
economics and coordination with the the reactance is to cause the initial fault
computers. Some specialized studies
overall process needs. current to be high, with the fault current
require large computing resources, but
At the conceptual phase of a project, many studies can now be performed on declining as time proceeds. This is
several distribution system alternatives personal computers. A wide variety of represented as the summation of a DC
should be considered, and examined both software packages are available. In component which decays relatively
technically and economically. This study addition, many specialty firms exist which rapidly over time, and an AC component,
should include sufficient detail for a provide engineering service to perform which decays at a slower rate. The rate of
thorough understanding of the system such studies. decay of the components depends on the
alternatives. The conceptual study should system X / R ratio.
determine the optimal distribution system Short Circuit Calculations Since the reactance of rotating machines
configuration for the project, on which The single-line diagram serves as the varies with the time from fault initiation,
definitive design can proceed. starting point for the system study and the short circuit calculations must use the
At all stages of design, the principal selection of equipment ratings. The appropriate machine reactance values.
objectives of personnel safety, equipment single-line must be modified to show all Subtransient reactance (X”d) governs
protection, process continuity, fault power sources and capacities, and current flow for approximately the first 6
clearing, and service continuity should be system impedances. Sources of short cycles of a fault. Then, transient
considered. circuit current include utility connections, reactance (X’d) determines current flow
local generation, and all rotating machines up to around 30-120 cycles, depending on
In designing a new or modified
connected to the system at the instant the machine. After this, synchronous
distribution system, the following types of
the fault occurs. The system study should reactance (Xd) applies, but studies
system studies may be needed:
consider various fault types (line-to-line seldom use this value as faults are not
1. Short Circuit Studies: three phase, and line-to-ground) and fault locations. usually allowed to persist for this length
line-to-line, and line-to-ground faults of time.
The value of normal load current in a
can be calculated for both close-and-
circuit depends on the load connected, For transformers, the actual tested value
latch and interrupting conditions,
and is essentially independent of the of the transformer impedance is used. If
necessary for checking interrupting
capacity of the power system. On the this is not available, use design
device and related equipment ratings,
other hand, the short circuit current impedance adjusted to the minimum
and setting protective devices.
depends almost entirely on the capacity value allowed by manufacturing tolerance
2. Circuit Breaker Application Studies: of the power system, not the size of the of +– 7.5%. For example, a 5.75% design
consider the AC and DC decrements load. unit has a tolerance range of 5.32-6.18%,
in the fault current, and the speed of and 5.32% would be used in a system
The total fault current consists of a
the various medium voltage circuit study prior to manufacture.
symmetrical AC component,
breakers, to determine close-and-latch
superimposed on a DC (offset)
and interrupting duties.
3. Protective Device Coordination
Studies: determine characteristics
and settings of protective devices,
e.g., relays, trip devices, fuses, etc.
The coordination study should provide
a balance between protection of
system equipment and continuity
of service.
T
TECHNICAL
Series-Connected Rating In a series-connected system, however, With the advent of fuseless current
A series-connected rating can be assigned the individual components (or circuit limiting circuit breakers such as Sentron,
to a combination of components — breakers) have already been tested in another important development in series-
typically circuit breakers — which has series and the combination has been connected combinations has emerged.
been tested in combination to a higher given an interrupting rating equal to or Because of the fuseless current limiting
interrupting rating than that of the lowest greater than various prospective fault circuit breaker’s extremely fast interrupting
rated protective device of the currents which are available. The capability, this device provides more
combination. These ratings must be combination, therefore, acts as a single control over high prospective fault
substantiated by extensive UL testing. entity, and performs the same protective currents than traditional series-connected
function as individual circuit breakers in systems.
General the traditional method. The difference is The concept behind using fuseless current
Article 110.9 of the 2011 National that combinations in series-connected limiting circuit breakers as a component in
Electrical Code states the following: systems contain devices with lower a series-connected system is twofold: (1)
“Equipment intended to interrupt current interrupting ratings. higher interrupting ratings, and (2)
at fault levels shall have an interrupting Siemens circuit breakers used in series increased control over peak current (ip) and
rating not less than the nominal circuit combinations which have passed energy let-through (I2t).
voltage and the current that is available extensive tests required by Underwriters
at the line terminals of the equipment. For example, a current limiting circuit
Laboratories are listed in the UL breaker is placed at the side closest to the
Equipment intended to interrupt current Recognized Component Directory
at other than fault levels shall have an source of power and rated according to
according to manufacturer’s name and the prospective fault current available at
interrupting rating at nominal circuit type. The listing means that such circuit
voltage not less than the current that the line-side terminals. In effect, doing this
breakers are UL Recognized for the series places a “shroud of protection” over the
must be interrupted.” interrupting ratings as noted in the downstream components. Because of the
The difference between the phrases “at Directory, and that they can be used as an inherent high interrupting capability of the
fault levels” and “at other than fault entity to meet Article 110.9 of the NEC. current limiting circuit breaker, the breaker
levels” is the part of the Code which Using the previous example, if the itself meets or exceeds the prospective
makes series-connected systems prospective fault current at the line short circuit current. Because of its current
possible. For example, the traditional terminals of the panelboard is 100,000 limiting action the prospective I2t never
method of satisfying the Code was to amperes RMS symmetrical, the series- reaches downstream components. This is
select each breaker in the series with an connected method would involve illustrated in Figure 29.
interrupting rating equal to or greater than selecting a specific combination from the
the prospective fault current. The It is important to recognize that the
UL Recognized Component Directory with current limiting circuit breaker be an
interrupting rating of a circuit breaker — a rating of 100,000 amperes RMS
stated in RMS symmetrical amperes — is individual component in a UL tested
symmetrical or greater interrupting combination, and that it is the combination
the amount of short circuit current the capacity. That combination might include
device can safely interrupt and continue to itself — current limiting circuit breaker
individual components which have lower plus other circuit breakers — that forms
function as a circuit breaker. individual interrupting ratings than 100,000 entity specified in day-to-day applications.
Thus, if the prospective fault current at the amperes RMS symmetrical.
line terminals of a panelboard is 100,000A For specific series-connected
However, all the components in the combinations that have met UL
RMS symmetrical, this traditional method combination have been tested together
would require that all the circuit breakers requirements and are listed in the UL
and form an entity that will safety interrupt Recognized Component Directory, check
within the panelboard be rated at the prospective fault current of the
100,000A RMS symmetrical or greater with your local Siemens sales office listed
particular situation being examined as long on the back cover. Since the Directory is
interrupting capacity. This is illustrated in as the interrupting rating listed matches
Figure 28. In the traditional system, both updated every six months, please check
the prospective fault current. for additional combinations which may
the main and the feeder breaker are
subjected to several short circuit peaks. have been tested and approved.
T
TECHNICAL
Figure 28 — Without Current Limiting Figure 29 — Series-Connected Protective Scheme With Current
Limiting Main Circuit Breaker
Non-Linear Loads
Voltage of Current Waveform for Linear Loads (Sine Wave)
When a sinusoidal voltage is applied to a
linear load, the resultant current
waveform takes on the shape of a sine
wave as well. Typical linear loads are
resistive heating and induction motors.
In contrast, a non-linear load either:
b Draws current during only part of the
cycle and acts as an open circuit for
the balance of the cycle,
or
b Changes the impedance during the
cycle, hence the resultant waveform is
distorted and no longer conforms to a Typical Current Waveform of Switching Power Supply
pure sine wave shape
In recent years, the use of electronic
equipment has mushroomed in both
offices and industrial plants. These
electronic devices are powered by
switching power supplies or some type
of rectifier circuit. Examples of these
devices used in offices are: computers,
fax machines, copiers, printers, cash
registers, UPS systems, and solid-state
ballasts. In industrial plants, one will find
other electronic devices such as variable
speed drives, HID lighting, solid-state A Non-Linear Current and Its Fundamental, Plus 3rd and 5th Harmonic Components
starters and solid-state instruments. They
all contribute to the distortion of the
current waveform and the generation of
harmonics. As the use of electronic
equipment increases and it makes up a
larger portion of the electrical load, many
concerns are raised about its impact on
the electrical power supply system.
Harmonics
As defined by ANSI / IEEE Std. 519-1992,
harmonic components are represented
by a periodic wave or quantity having a
frequency that is an integral multiple of
the fundamental frequency. Harmonics
are voltages or currents at frequencies
that are integer multiples of the
fundamental (60 Hz) frequency: 120 Hz,
180 Hz, 240 Hz, 300 Hz, etc. Harmonics
are designated by their harmonic number, Figure 30 — Effect of Harmonics on Current Waveform
or multiple of the fundamental frequency.
Thus, a harmonic with a frequency of 180 generated by the non-linear load. Total Therefore, it is the percentage amount of
Hz (three times the 60 Hz fundamental Harmonic Distortion (THD) is calculated odd harmonics (3rd, 5th, 7th ,..., 25th,...)
frequency) is called the 3rd harmonic. as the square root of the sum of the present in the load which can affect the
Harmonics superimpose themselves on squares of all harmonics divided by the transformer, and this condition is called a
the fundamental waveform, distorting it normal 60 Hz value. “Non-Linear Load” or “Non-Sinusoidal
and changing its magnitude. For instance, Load”. To determine what amount of
T
Table 1
NEC Table 310.15(B)(16) (formerly Table 310.16) Allowable Ampacities of Insulated Conductors Rated Up to and Including
2000 Volts, 60°C Through 90°C (140°F Through 194°F), Not More Than Three Current-Carrying Conductors in Raceway,
Cable, or Earth (Directly Buried), Based on Ambient Temperature of 30°C (86°F)a
Aluminum Conductors
Copper Conductors Copper-Clad Aluminum Conductors
60°C 75°C 90°C 60°C 75°C 90°C
Size (140°F) (167°F) (194°F) (140°F) (167°F) (194°F) Size
Types Types Types Types Types Types
TBS TBS,
SA SA, SIS,
SIS THHN
AWG RHW FEP RHW THHW AWG
Kcmil THW FEPB THHW THW-2, THWN-2, Kcmil
THWN RHH THW RHH, RHW-2
XHHW THHN THWN USE-2
TW USE THHW TW XHHW XHH, XHHW
UF ZW XHHW UF USE XHHW-2, ZW-2
0018 — — 014 — — — —
0016 — — 018 — — — —
0014 b
015 020 025 — — — —
0012 b
020 025 030 015 020 a
025 12
a
Table 2
Correction Factors for Ambient Temperature Over 30°C (86°F) Based on NEC Table 310.15(B)(2)(A)
Ambient For ambient temperature over 30°C, (86°F) multiply the ampacities shown above by the appropriate factor Ambient
Temperature°C shown below. Temperature°F
10 or less 1.29 1.20 1.15 1.29 1.20 1.15 50 or less
11-15 1.22 1.15 1.12 1.22 1.15 1.12 51-59
16-20 1.15 1.11 1.08 1.15 1.11 1.08 60-68
21–25 1.08 1.05 1.04 1.08 1.05 1.04 69–77
26–30 1.00 1.00 1.00 1.00 1.00 1.00 78–86
31–35 .91 .94 .96 .91 .94 .96 87–95
36–40 .82 .88 .91 .82 .88 .91 96–104
41–45 .71 .82 .87 .71 .82 .87 105–113
46–50 .58 .75 .82 .58 .75 .82 114–122
T
aRefer
to 310.15(B)(2) for the ampacity correction factors bReferto 240.4(D) for conductor overcurrent protection
where the ambient temperature is other than 30°C (86°F) limitations.
Table 5
Normal-Load and Fault Currents of Three Phase Transformers
Transformer
Characteristics AC Voltage 3-Phase
3-Phase 208V 240V 480V
a Valuesmay vary depending on manufacturer, Normal Load Short Normal Load Short Normal Load Short
type of motor and NEMA design. kVA % Continuous Circuit Continuous Circuit Continuous Circuit
For full load currents of 200 volt motors, increase the Rating Impedance Amperes Current Amperes Current Amperes Current
T
corresponding 230 volt motor full-load current by 112.5 3.90 312 8,007 271 6,940 135 3,470
15 percent. 150 3.70 416 11,253 361 9,753 180 4,876
Table 5 Notes: 225 4.70 625 13,288 541 11,517 271 5,758
TECHNICAL
1. Primary source available is assumed as 500 MVA at the 300 4.50 834 18,505 722 16,038 361 8,019
primary of the transformer with a source circuit X/R
ratio of 12.
500 4.50 1388 30,842 1203 26,730 601 13,365
2. Motor contribution is included in the table at twice the 750 5.75 2080 36,206 1804 31,379 902 15,689
full-load current for 208 volt transformers and at 4 1000 5.75 2780 48,275 2406 41,838 1203 20,919
times the full-load current for 240 volt and 480 volt 1500 5.75 4162 72,412 3610 62,575 1805 31,379
transformers. These values are derived from the 2000 5.75 —00 —0 0 0 4812 83,676 2406 41,838
assumption that 208 volt systems are 50% motor load 2500 5.75 —00 —0 0 0 6010 104,596 3008 52,298
and 240 and 480 volt systems are 100% motor load.
3. All short circuit current values are in symmetrical
RMS amperes.
Table 6
Electrical Formulas for Finding Amperes, Horsepower, Kilowatts and kVA
Alternating Current
To Find Single Phase Two Phase a, Four Wire Three Phase Direct Current
I x E x pf I x E x 2 x pf I x E x 1.73 x pf IxE
Kilowatts
1000 1000 1000 1000
IxE IxEx2 I x E x 1.73
kVA
1000 1000 1000
Horsepower I x E x % EFF x pf I x E x 2 x % EFF x pf I x E x 1.73 x % EFF x pf I x E x % EFF
(Output) 746 746 746 746
Amperes when
HP x 746 HP x 746 HP x 746 HP x 746
Horsepower
E x % EFF x pf 2 x E x % EFF x pf 1.73 x E x % EFF x pf E x % EFF
is Known
Amperes when
KW x 1000 KW x 1000 KW x 1000 KW x 1000
Kilowatts
E x pf 2 x E x pf 1.73 x E x pf E
is Known
Amperes when kVA x 1000 kVA x 1000 kVA x 1000
kVA is Known E 2xE 1.73 x E
Over 350 kcmil to 600 kcmil Over 500 kcmil to 900 kcmil 1/0 3/0
Over 600 kcmil to 1100 kcmil Over 900 kcmil to 1750 kcmil 2/0 4/0
Over 1100 kcmil Over 1750 kcmil 3/0 250 kcmil
a In
three wire, two phase circuits the current in b Additionalinformation and exceptions are stated in
the common conductor is 1.41 times that in either Article 250 — Grounding, National Electrical Code.
other conductor.
E = Volts I = Amperes
% EFF = Per Cent Efficiency pf = Power Factor
a 0.001"
= 0.0254 mm
1 mm = 0.03937"