Atmospheric Blowdown Tank Calculation Report
Atmospheric Blowdown Tank Calculation Report
Contractor's Name:
This document is issued by Harris Pye DMCC, Dubai UAE. The information contained in this document is the confidential property of
Harris Pye. It cannot be disclosed, copied or used for any purpose without written approval from Harris Pye. If you are not authorised
to possess this document, please destroy it immediately.
Client: Galliford Try Doc. No. MI-17085-PR-CR-002
Project: Hull Biomass UK LLP 1 Tag No. T-06-17023
Location: Hull, United Kingdom Job No. MI-17085
ATMOSPHERIC BLOWDOWN TANK Rev. Date Sheet
2 of 49_____
PROCESS DESIGN REPORT 4 22/08/17
REVISION HISTORY
692284769.xlsx
3 of 49_____
692284769.xlsx
Client: Galliford Try Doc. No. MI-17085-PR-CR-002
Project: Hull Biomass UK LLP 1 Tag No. T-06-17023
Location: Hull, United Kingdom Job No. MI-17085
ATMOSPHERIC BLOWDOWN TANK Rev. Date Sheet
PROCESS DESIGN REPORT 4 22/08/17 4 of 49_____
TABLE OF CONTENTS
Revision History 2
Contents 3
Design Input Data 4
Assumptions 5
Nozzles Sizing 6
N1 - Inlet 6
N2 - Deaerator Feedwater Tank Drain and Overflow 6
N3 - Boiler Intermittent Blowdown 8
N4 - Sootblower Condensate 11
N5 - Flash Tank Liquor 13
N6 - Service Water 14
N7 - Vent 14
N8 - Water Outlet 17
N9 - Drain 17
Instrumentation 17
N10 - Level Indicator Transmitter 17
N11 - Pressure Indicator Transmitter 18
N12 - Temperature Indicator Transmitter 18
Vessel Sizing 20
Vessel Diameter for Gravity Separation 20
Calculation of Vessel Height 22
References 24
692284769.xlsx
5 of 49_____
692284769.xlsx
Client: Galliford Try Doc. No. MI-17085-PR-CR-002
Project: Hull Biomass UK LLP 1 Tag No. T-06-17081
Location: Hull, United Kingdom Job No. MI-17085
ATMOSPHERIC BLOWDOWN TANK Rev. Date Sheet
PROCESS DESIGN REPORT 6 of 49_ ____
4 22/08/17
After Flashing
692284769.xlsx
Client: Galliford Try Doc. No. MI-17085-PR-CR-002
Project: Hull Biomass UK LLP 1 Tag No. T-06-17081
Location: Hull, United Kingdom Job No. MI-17085
ATMOSPHERIC BLOWDOWN TANK Rev. Date Sheet
PROCESS DESIGN REPORT 7 of 49_ ____
4 22/08/17
Stream Intermittent
Units Blowdown flash tank Sootblower Condensate Deaerator Overflow
Description Blowdown
Liquid Vapour Liquid Vapour Liquid Vapour Liquid Vapour
Flow Rate [kg/h] 738.30 0.00 1354.92 645.08 743.77 256.23 946.12 73.88
[kg/s] 0.21 0.00 0.38 0.18 0.21 0.07 0.26 0.02
Density [kg/m³] 992.16 0.00 1.85 0.60 958.35 0.60 958.35 0.60
Volume flow rate [m³/s] 0.0002 0.00 0.2032 0.30 0.0002 0.12 0.0003 0.03
Pressure [bar(a)] 1.01 0.00 1.01 1.01 1.01 1.01 1.01 1.01
Temperature [°C] 40.07 0.00 100.01 100.01 100.01 100.01 100.01 100.01
Enthalphy [kJ/kg] 167.90 0.00 419.13 2675.58 419.13 2675.58 419.13 2675.58
692284769.xlsx
8 of 49_ ____
692284769.xlsx
Client: Galliford Try Doc. No. MI-17085-PR-CR-002
Project: Hull Biomass UK LLP 1 Tag No. T-06-17081
Location: Hull, United Kingdom Job No. MI-17085
ATMOSPHERIC BLOWDOWN TANK Rev. Date Sheet
PROCESS DESIGN REPORT 4 22/08/17 9 of 49_____
ASSUMPTIONS
The following assumptions were made for the design of the atmospheric blowdown tank:
1. The operating pressure in the flash tank is established by the backpressure in the vent line and associated piping. The vessel
operating pressure shall not exceed 5 psi (0.35 barg). The pressure will be the atmospheric pressure plus the pressure drops
of the flashed steam in the vent line. In the following, a preliminary vent piping routing is assumed for back pressure
calculation, to be verified after pipe routing and vessel sizing. Tipically, the backpressure is limited to 1 Psi (0.069 barg) by
2. design.
The vapor-liquid separation in the vessel is mainly achieved by gravity settling of the liquid droplets and by action of the
inlet device. Tipically, the backpressure is limited to 1 Psi (0.069 barg) by design.
3. For gravity settling, the momentum equation reduces to a balance of the gravity and drag forces at steady state. This allows
to calculate a terminal velocity, which is the superficial velocity around the liquid droplets under equilibrium conditions.
The sizing of the vessel diameter will be made here according to [ref 3], so that the steam space velocity is ≤ 11 ft/s (3.35
m/s).
4. The Dearator Overflow has been assumed as the 21% of the total dearator inlet flow.
5. The boiler drains are assumed to be cold (T ≤ 40°C) and at atmospheric pressure (boiler drained after shutdown).
Therefore, the cold drained water has a small residence time in the vessel.
6. The standing liquid in the vessel is assumed to be pseudo-stratified, and cold water from the bottom part of the vessel is
discharged after cooling to ≤ 40°C. The water remaining in the vessel after discharge is cooled down. typically, the quantity
of water to be cooled lies below the NWL. The cooling is achieved through heat losses from the vessel surface.
7. In case the time to cool down the standing water is higher than the time between blodown cycles, service water will be
injected automatically in the lower part of the vessel, to help cool down the water prior to discharge to foul drainage
system.
8.
In the design case, the Sootblower condensate, the Intermittent Blowdown and th Deaerator Overflow are assumed to occur
simultaneously, even if in the probability of occurrence of such event is low in normal operation.
9. The frequency of the blowdown cycles and of the sootblowing considered are:
- 12 intermittent blowdowns and these are open sequentially for a max period of 30 seconds. The daily Intermittent
Blowdown water consumption is 600 kg/day.
- The total sootblowers condensate flow rate is 2,000 kg/h, as per information received from Boiler OEM.
692284769.xlsx
10 of 49_____
692284769.xlsx
Client: Galliford Try Doc. No. MI-17085-PR-CR-002
Project: Hull Biomass UK LLP 1 Tag No. T-06-17081
Location: Hull, United Kingdom Job No. MI-17085
ATMOSPHERIC BLOWDOWN TANK Rev. Date Sheet
PROCESS DESIGN REPORT 11 of 49_____
4 22/08/17
Rev NOZZLES SIZING
In this section, the main vessel inlet and outlet nozzles, as well as instrument nozzles will be sized.
Due to the lack of information the Boiler Drains Header inlet diameter has been considered to be 2".
The Deaerators Overflow and Drain flow in the inlet piping and nozzle to the Atmospheric Blowdown vessel is, in general,
a 2-phase mixture. In fact, flashing of the fluid would occur in the drain line when the Deaerator Overflow valve is open.
The following table summarizes the properties of the inlet fluid to the Deaerator overflow (OF) nozzle.
Two-Phase Inlet to
Description Units Design Condition (3)
Vessel (1)
- Norm Vapor Liquid
Flow Rate min [kg/h] 1,020 74 946
[kg/s] 0.283 0.021 0.263
Pressure p [bar(a)] 1.014 1.014 1.014
Temperature T [°C] 100.0 100.0 100.0
Enthalphy h [kJ/kg] 582.6 2675.6 419.1
Quality x [-] 0.072 1 0
Density ρ [kg/m³] 8.19 0.60 958.3
Viscosity μ [cP] 0.199 (2) 0.012 0.282
Volumetric Flow Q [m³/s] 0.035 0.034 0.0003
Notes:
(1) Two-Phase mixture after Actuated valve AV-06-07028, in the drain line.
(2) Mixture viscosity approximated with saturated liquid viscosity.
(3) Design condition taken as the peak flow condition. The flash pressure in this case was assumed equal
to the vessel operating pressure.
Since the inlet to the vessel is a multiphase fluid, the determination of the flow regime in the inlet line is very important for
the inlet nozzle sizing and for the efficient separation of the two components. Normally, the inlet nozzle of a blowdown
tank is sized for Annular or Spray flow. Other flow regimes, such as Slug, Plug and Froth are not recommended.
692284769.xlsx
12 of 49_____
692284769.xlsx
Client: Galliford Try Doc. No. MI-17085-PR-CR-002
Project: Hull Biomass UK LLP 1 Tag No. T-06-17081
Location: Hull, United Kingdom Job No. MI-17085
ATMOSPHERIC BLOWDOWN TANK Rev. Date Sheet
PROCESS DESIGN REPORT 13 of 49_____
4 22/08/17
Rev NOZZLES SIZING
The velocity obtained is not high, so it is possible to proceed with the maximum velocity allowed in two phase flows.
The maximum velocity in a two-phase line is usually established by the erosional limit, which can be calculated according
to:
Taking this as a base it has been possible to determine the flow regime in the new line, using a flow map from the literature
[Ref.1]. To use this map, some flow parameters must be calculated, and used as input to the chart axes. The insersection
point gives the flow regime in the pipe with sufficient accuracy for practical applications.
σ = Fluid surface tension = 0.051 N/m
𝑋 = (𝐺_𝑙 𝜆 𝜓)/𝐺_𝑣
= 85.4
𝑌 = 𝐺_𝑣/𝜆
= 0.19 lbm/ft² s
Nozzle sizing
To size the nozzle, a maximum (conservative) value for the kinetic energy per unit volume (ρv²) is usually specified, and
the nozzle diameter calculated iteratively based on this value.
692284769.xlsx
14 of 49_____
692284769.xlsx
Client: Galliford Try Doc. No. MI-17085-PR-CR-002
Project: Hull Biomass UK LLP 1 Tag No. T-06-17081
Location: Hull, United Kingdom Job No. MI-17085
ATMOSPHERIC BLOWDOWN TANK Rev. Date Sheet
PROCESS DESIGN REPORT 4 22/08/17 15 of 49_____
The feed nozzle size and the type of feed inlet device (if any) have an impact on the vapor / liquid separation that can be
achieved. The feed nozzle is normally sized to limit the momentum of the feed. The limitation depends on whether or not a
feed inlet device is installed.
The entrance loss, with the assumption of incompressible flow (Δp≤10% Pin), and A1/A2 → 0 is given by:
(𝑉_1^2)/2 (1−𝐴_1/𝐴_2 )^2=(𝑉_1^2)/2
Δpentr = = 0.5736 Pa
Finally, the pressure drop due to the change in direction of the fluid inside the vessel due to the tangential inlet would
need to be estimated.
However, since the calculation of the pressure drop of a 2-phase fluid changing direction is very involved, this loss will
be conservatevely estimated as 1.5 times the entrance loss, to be conservative.
Thus:
Δpbp = 1.5*Δpentr = 0.8604 Pa
The Intermittent Blowdown flow in the inlet piping and nozzle to the Atmospheric Blowdown vessel is, in general, a 2-
phase mixture. In fact, flashing of the fluid would occur in the blowdown line, when the IBD valve is open.
The following table summarizes the properties of the inlet fluid to the IBD nozzle.
Two-Phase Inlet to
Description Units Design Condition (3)
Vessel (1)
- Norm Vapor Liquid
Flow Rate min [kg/h] 2,000 645 1,355
[kg/s] 0.556 0.179 0.376
Pressure p [bar(a)] 1.014 1.014 1.014
Temperature T [°C] 100.0 100.0 100.0
Enthalphy h [kJ/kg] 1,146.9 2675.6 419.1
Quality x [-] 0.323 1 0
692284769.xlsx
Client: Galliford Try Doc. No. MI-17085-PR-CR-002
Project: Hull Biomass UK LLP 1 Tag No. T-06-17081
Location: Hull, United Kingdom Job No. MI-17085
ATMOSPHERIC BLOWDOWN TANK Rev. Date Sheet
PROCESS DESIGN REPORT 17 of 49_____
4 22/08/17
Rev NOZZLES SIZING
Determination of the flow regime in the inlet line
Since the inlet to the vessel is a multiphase fluid, the determination of the flow regime in the inlet line is very important for
the inlet nozzle sizing and for the efficient separation of the two components. Normally, the inlet nozzle of ablowdown tank
is sized for Annular or Spray flow. Other flow regimes, such as Slug, Plug and Froth are not recommended.
A preliminary calculation of the velocity in the existing line shows that for the two-phase mixture, the velocity is
unrealistic. Therefore, the line has to be resized to avoid such high velocities.
The maximum velocity in a two-phase line is usually established by the erosional limit, which can be calculated according
to:
Taking this as a base, the new line size has been calculated iteratively, and the flow regime in the new line was determined,
using a flow map from the literature [Ref.1]. To use this map, some flow parameters must be calculated, and used as input
to the chart axes. The insersection point gives the flow regime in the pipe with sufficient accuracy for practical applications.
𝑋 = (𝐺_𝑙 𝜆 𝜓)/𝐺_𝑣
= 12.1
692284769.xlsx
18 of 49_____
692284769.xlsx
Client: Galliford Try Doc. No. MI-17085-PR-CR-002
Project: Hull Biomass UK LLP 1 Tag No. T-06-17081
Location: Hull, United Kingdom Job No. MI-17085
ATMOSPHERIC BLOWDOWN TANK Rev. Date Sheet
PROCESS DESIGN REPORT 4 22/08/17 19 of 49_____
Nozzle sizing
To size the nozzle, a maximum (conservative) value for the kinetic energy per unit volume (ρv²) is usually specified, and
the nozzle diameter calculated iteratively based on this value.
The feed nozzle size and the type of feed inlet device (if any) have an impact on the vapor / liquid separation that can be
achieved. The feed nozzle is normally sized to limit the momentum of the feed. The limitation depends on whether or not a
feed inlet device is installed.
The entrance loss, with the assumption of incompressible flow (Δp≤10% Pin), and A1/A2 → 0 is given by:
(𝑉_1^2)/2 (1−𝐴_1/𝐴_2 )^2=(𝑉_1^2)/2
Δpentr = = 129 Pa
Finally, the pressure drop due to the change in direction of the fluid inside the vessel due to the tangential inlet would need
to be estimated.
However, since the calculation of the pressure drop of a 2-phase fluid changing direction is very involved, this loss will be
conservatevely estimated as 1.5 times the entrance loss, to be conservative.
Thus:
692284769.xlsx
20 of 49_____
692284769.xlsx
Client: Galliford Try Doc. No. MI-17085-PR-CR-002
Project: Hull Biomass UK LLP 1 Tag No. T-06-17081
Location: Hull, United Kingdom Job No. MI-17085
ATMOSPHERIC BLOWDOWN TANK Rev. Date Sheet
PROCESS DESIGN REPORT 4 22/08/17 21 of 49_____
The Sootblowers Drain flow in the inlet piping and nozzle to the Atmospheric Blowdown vessel is, in general, a 2-phase
mixture. In fact, flashing of the fluid would occur in the condensate line, when the SBC valve is open.
The following table summarizes the properties of the inlet fluid to the SBC nozzle.
In the first column, the calculated velocity assuming same line size upstream and downstream of the steam trap set
is shown. The velocity in this case is exceeding the erosional limit velocity. For this reason, the line size was recalculated
to achive safe results and the optimal size is shown in the second column.
Two-Phase Inlet to
Description Units Design Condition (3)
Vessel (1)
- Norm Vapor Liquid
Flow Rate min [kg/h] 1,000 256 744
[kg/s] 0.278 0.071 0.207
Pressure p [bar(a)] 1.014 1.014 1.014
Temperature T [°C] 100.0 100.0 100.0
Enthalphy h [kJ/kg] 997.3 2675.6 419.1
Quality x [-] 0.256 1 0
Density ρ [kg/m³] 2.33 0.60 958.3
Viscosity μ [cP] 0.282 (2) 0.012 0.282
Volumetric Flow Q [m³/s] 0.119 0.119 0.0002
Notes:
(1) Two-Phase mixture after blowdown valve, in the blowdown line. Assumption of SBC valve as close
as possible to the tank.
(2) Mixture viscosity approximated with saturated liquid viscosity.
(3) Design condition taken as the peak flow condition. The flash pressure in this case was assumed equal
to the vessel operating pressure.
Since the inlet to the vessel is a multiphase fluid, the determination of the flow regime in the inlet line is very important for
the inlet nozzle sizing and for the efficient separation of the two components. Normally, the inlet nozzle of a blowdown
tank is sized for Annular or Spray flow. Other flow regimes, such as Slug, Plug or Froth are not recommended.
692284769.xlsx
22 of 49_____
692284769.xlsx
Client: Galliford Try Doc. No. MI-17085-PR-CR-002
Project: Hull Biomass UK LLP 1 Tag No. T-06-17081
Location: Hull, United Kingdom Job No. MI-17085
ATMOSPHERIC BLOWDOWN TANK Rev. Date Sheet
PROCESS DESIGN REPORT 4 22/08/17 23 of 49_____
Taking this as a base, the new line size has been calculated iteratively, and the flow regime in the new line was determined,
using a flow map from the literature [Ref.1]. To use this map, some flow parameters must be calculated, and used as input
to the chart axes. The insersection point gives the flow regime in the pipe with sufficient accuracy for practical applications.
𝑋 = (𝐺_𝑙 𝜆 𝜓)/𝐺_𝑣
= 16.8
𝑌 = 𝐺_𝑣/𝜆
= 2.57 lbm/ft² s
Nozzle sizing
To size the nozzle, a maximum (conservative) value for the kinetic energy per unit volume (ρv²) is usually specified, and
the nozzle diameter calculated iteratively based on this value.
The feed nozzle size and the type of feed inlet device (if any) have an impact on the vapor / liquid separation that can be
achieved. The feed nozzle is normally sized to limit the momentum of the feed. The limitation depends on whether or not a
feed inlet device is installed.
692284769.xlsx
24 of 49_____
692284769.xlsx
Client: Galliford Try Doc. No. MI-17085-PR-CR-002
Project: Hull Biomass UK LLP 1 Tag No. T-06-17081
Location: Hull, United Kingdom Job No. MI-17085
ATMOSPHERIC BLOWDOWN TANK Rev. Date Sheet
PROCESS DESIGN REPORT 25 of 49_____
4 22/08/17
Rev NOZZLES SIZING
Check of (ρv²) value with chosen nozzle diameter.
The entrance loss, with the assumption of incompressible flow (Δp≤10% Pin), and A1/A2 → 0 is given by:
Finally, the pressure drop due to the change in direction of the fluid inside the vessel due to the tangential inlet would need
to be estimated.
However, since the calculation of the pressure drop of a 2-phase fluid changing direction is very involved, this loss will be
conservatevely estimated as 1.5 times the entrance loss, to be conservative.
Thus:
To size the flash tank inlet, a nozzle size (and line size) is assumed and the fluid velocity is checked. The criteria for liquid
outlet nozzles is usually based on the fluid velocity, as follows:
Two-Phase Inlet to
Description Units Design Condition (3)
Vessel (1)
- Norm Vapor Liquid
Flow Rate min [kg/h] 738.3 - 738.3
[kg/s] 0.205 - 0.205
Pressure p [bar(a)] 3.40 - 1.014
Temperature T [°C] 40.00 - 40.07
Enthalphy h [kJ/kg] 167.836 - 167.90
Quality x [-] 0.000 - 0.00
Density ρ [kg/m³] 992.16 - 992.16
Viscosity μ [cP] 0.20 - 0.20
Volumetric Flow Q [m³/s] 0.0002 - 0.0002
692284769.xlsx
26 of 49_____
692284769.xlsx
Client: Galliford Try Doc. No. MI-17085-PR-CR-002
Project: Hull Biomass UK LLP 1 Tag No. T-06-17081
Location: Hull, United Kingdom Job No. MI-17085
ATMOSPHERIC BLOWDOWN TANK Rev. Date Sheet
27 of 49_____
PROCESS DESIGN REPORT 4 22/08/17
Rev NOZZLES SIZING
The mass flow rate of the service water has been calculated considering the heat loss of the Atmospheric Blowdown Tank
and the H&M balance of that device. The blowing time ot the process has been given by the Boiler OEM as being 6 min,
and on our side it has been assumed to be composed of 3 sessions per day: one every 8 hours.
To size the service water inlet, a nozzle size (and line size) is assumed and the fluid velocity is checked. The criteria for
liquid inlet nozzles is usually based on the fluid velocity, as follows:
For this application it has been considered that 1" nozzle diameter was acceptable.
The vent nozzle shall be sized to relief all the flash steam developed in the vessel, so that the backpressure in the piping and
vent silencer are less than 0.35 bar, usually. This allows the atmospheric blowdown tank to operate always around
atmospheric pressure. In the following, to size the vent line, the total amount of steam flashed in the tank from the various
inlets will be computed, considering simultaneous IBD, SB warm-up cycles and deaerator overflow and assuming a
configuration of the vent piping, to be confirmed after final pipe routing. Finally, the vent line can be sized, so that the
steam velocity lies within the typical velocities for low pressure steam (15 m/s ≤ vs ≤ 20 m/s), which will minimize water
(and chemical) entrainment with the steam as well as the noise in the vent pipe.
692284769.xlsx
28 of 49_____
692284769.xlsx
Client: Galliford Try Doc. No. MI-17085-PR-CR-002
Project: Hull Biomass UK LLP 1 Tag No. T-06-17081
Location: Hull, United Kingdom Job No. MI-17085
ATMOSPHERIC BLOWDOWN TANK Rev. Date Sheet
29 of 49_____
PROCESS DESIGN REPORT 4 22/08/17
Rev NOZZLES SIZING
Steam Vented to Atmosphere (1) Units Steam Flow in Vent Line from
- IBD SB Drain DeA OF Total
Flow Rate min [kg/h] 645.1 256.2 73.9 330
[kg/s] 0.179 0.071 0.021 0.092
Pressure p [bar(a)] 1.01 1.01 1.01 1.01
Temperature T [°C] 100.0 100.0 100.0 100.0
Enthalphy h [kJ/kg] 2,676 2,676 2,676 2,676
Quality x [-] 1.0 1.0 1.0 1.0
Density ρ [kg/m³] 0.60 0.60 0.60 0.60
Viscosity μ [cP] 0.012 0.012 0.012 0.012
Volumetric Flow Q [m³/s] 0.299 0.119 0.034 0.153
Notes:
(1) Assumption of simultaneous discharge of IBD, SB drain and DeA Overflow in the Design Case.
With the total steam flow in the vent nozzle (and piping), the minimum required diameter of the vent nozzle is:
𝐷/1000≥√(4/𝜋∙𝑄_𝑠/𝑣_𝑚𝑎𝑥 )
(4) (0.153)
= = 0.099 m
(3.14) (20)
where:
D = Minimum Inside Diameter of the flash tank vessel = 98.778 mm
vmax = Maximum velocity of steam in the vent nozzle = 20 m/s
Qs = Flash steam max volumetric flow rate = 0.153 m³/s
The following table summarizes the chosen Vent nozzle data, obtained after iteration.
Description Unit
Line Number - - -
Material - - Carbon Steel
Pipe Size NPS - 10
Nominal Diameter DN - 250
Outside Diameter OD mm 273
Schedule Sch. - STD
Thickness t mm 9.27
Inside Diameter ID mm 254.5
Flow Area A m² 0.0509
Flow Velocity v m/s 3.01
With the chosen vent size, the pressure drop in the vent line is then calculated, and the backpressure added to the
atmospheric pressure to determine a new value of the vessel operating pressure. After a few iterations, the vessel pressure
converges and the final values for the operating pressure, amount of flashed steam and vessel size are found.
Even though the calculation would suggest to chose a smaller diameter in order to increse the velocity through the nozzle,
following Ref. [10] the diameter selected has been 10". This is to account for all the uncertainties in the input design data
received from the client, which might result in an excessive increase of the backpressure in case the flow rates were
understimated.
This calculation assumes a typical vent piping configuration and a vent silencer pressure drop of 6 mbar. The pressure drop
across the vent piping should be limited to 1 psi (0.069 bar), to ensure that the pipe is of sufficient size to vent the steam,
and prevent an increase in the atmospheric blowdown 692284769.xlsx
tank pressure.
30 of 49_____
692284769.xlsx
Client: Galliford Try Doc. No. MI-17085-PR-CR-002
Project: Hull Biomass UK LLP 1 Tag No. T-06-17081
Location: Hull, United Kingdom Job No. MI-17085
ATMOSPHERIC BLOWDOWN TANK Rev. Date Sheet
31 of 49_____
PROCESS DESIGN REPORT 4 22/08/17
Rev NOZZLES SIZING
Taking the chosen pipe size as per the above table, the pressure drop in the vent piping will be the sum of friction (or
distributed) pressure drop and concentrated (or minor) pressure drops, as per the following. The static head losses are
neglected in the calculations.
〖∆𝑝〗 _𝑣= 〖∆𝑝〗 _𝑓+ 〖∆𝑝〗 _𝑐+ 〖∆𝑝〗 _𝑠=𝑓 𝐿/𝐷 𝜌 𝑣^2/2+∑_𝑖▒ 〖𝐾 _(𝑖 ) 𝜌 𝑣^2/2+𝜌𝑔(𝑧_2−𝑧_1 ) 〗
where:
The calculation of the friction factor starts with the computation of the Reynolds Number:
f = 0.02283
10.0 (3)²
Δpf = 0.02283 0.60 = 2.4 Pa = 0.00002 bar
0.2545 2
To calculate the minor pressure drops, a piping configuration with the following fittings, valves, etc. is assumed, to be
confirmed after piping layout.
The total minor losses, including also the pressure drop in the vent silencer, are:
(3)²
Δpc = 3.7 0.60 + 600 = 610.1 Pa = 0.00610 bar
2
Total pressure drop in the vent line, with the chosen vent nozzle and piping diameter, is:
692284769.xlsx
Client: Galliford Try Doc. No. MI-17085-PR-CR-002
Project: Hull Biomass UK LLP 1 Tag No. T-06-17081
Location: Hull, United Kingdom Job No. MI-17085
ATMOSPHERIC BLOWDOWN TANK Rev. Date Sheet
PROCESS DESIGN REPORT 4 22/08/17 32 of 49_____
To size the oultet liquid/liquor line, a nozzle size (and line size) is assumed and the fluid velocity is checked. The criteria
for liquid outlet nozzles is usually based on the fluid velocity, as follows:
9. Drain
The Drain outlet nozzle has been designed following [10]. The chosen diameter is 2".
10. Instrumentation
The following table summarizes the main data for the Level Instrument Nozzles [Ref.7].
Number of Nozzles - 2
Nozzle Size NPS 3/4" NWL
600
DN 20
600
LWL
Nozzle Schedule Sch. 80
Nozzle Outside Diameter mm 26.7 3/4"
100
692284769.xlsx
Client: Galliford Try Doc. No. MI-17085-PR-CR-002
Project: Hull Biomass UK LLP 1 Tag No. T-06-17081
Location: Hull, United Kingdom Job No. MI-17085
ATMOSPHERIC BLOWDOWN TANK Rev. Date Sheet
33 of 49_____
PROCESS DESIGN REPORT 4 22/08/17
N10 A
Rev NOZZLES SIZING
The following table summarizes the main data for the Pressure Instrument Nozzle [Ref.7].
HWL
1200
NWL
LWL
The following table summarizes the main data for the Temperature Instrument Nozzle [Ref.7].
For the Temperature transmitter position see "Vessel Sizing" at page 22.
692284769.xlsx
Client: Galliford Try Doc. No. MI-17085-PR-CR-002
Project: Hull Biomass UK LLP 1 Tag No. T-06-17081
Location: Hull, United Kingdom Job No. MI-17085
ATMOSPHERIC BLOWDOWN TANK Rev. Date Sheet
34 of 49_____
PROCESS DESIGN REPORT 4 22/08/17
Rev NOZZLES SIZING
The nozzles sizes, rate and type are shown in the following table:
REMARKS
[1] Internal deep pipe with syphon breaker (hole)
692284769.xlsx
35 of 49_____
692284769.xlsx
Client: Galliford Try Doc. No. MI-17085-PR-CR-002
Project: Hull Biomass UK LLP 1 Tag No. T-06-17081
Location: Hull, United Kingdom Job No. MI-17085
ATMOSPHERIC BLOWDOWN TANK Rev. Date Sheet
PROCESS DESIGN REPORT 36 of 49___ __
4 22/08/17
Rev VESSEL SIZING
An atmospheric blowdown vessel is typically sized, as a flash tank, to achieve proper separation of the water droplets by
gravity settling and to avoid water entrainment with the flashed steam. This is achieved, in the steam space, by decreasing the
steam velocity to a value below the critical velocity for separation of the water droplets and by locating the inlet nozzles at a
proper distance from the standing liquid High Level (HWL).
Therefore, the combined effect of nozzle size, inlet nozzle configuration and/or devices, and vessel diameter allow for
minimum entrainment and good steam-water separation in the vessel.
In the following, the vapor space will be sized, to achieve a velocity of ≤ 11 ft/s (3.35 m/s), as per recommendations in [Ref.3].
This will be also compared to an empirical calculation of the critical settling velocity for water droplets, by using the Souders
and Brown correlation [Ref.1,2,10]. However, a derating factor to account for the absence of a mist eliminator will have to be
applied to this correlation. Then, the liquid volume will be calculated, based on the chosen diameter, the NWL and the HWL of
the vessel will be established, and the total total vessel height (TL-TL) determined.
The blowdown flash vessel will be able to separate the liquid droplets larger than 150 μm by gravity.
Dp = 150 μm = 1.5E-04 m
where:
Substituting,
(
0.154) (.) (4.37E-05) (130.82)
ut = = 0.669 m/s
(7.322) (0.00773)
An alternative method to calculate the terminal velocity makes use of the following general formula:
𝑢_𝑡=1.15√(( 〖 𝜌〗 _𝑔 𝐷_𝑝 ( 〖𝜌 _𝑙−𝜌 〗_𝑔))/( 〖 𝜌〗
_𝑔 𝐶_𝐷 ))
Since CD is dependent on Re, and thus on the terminal velocity, an iterative approach would be required. However, using a the
following correlation, together with the following Figure 4, the terminal velocity is eliminated and the drag coefficient can be
directly calculated.
692284769.xlsx
37 of 49___ __
692284769.xlsx
Client: Galliford Try Doc. No. MI-17085-PR-CR-002
Project: Hull Biomass UK LLP 1 Tag No. T-06-17081
Location: Hull, United Kingdom Job No. MI-17085
ATMOSPHERIC BLOWDOWN TANK Rev. Date Sheet
PROCESS DESIGN REPORT 4 22/08/17 38 of 49___ __
Taking the lower value of the two terminal velocities calculated above (conservative), the required vessel diameter can be
calculated, with the vapor velocity being less than the terminal velocity, to avoid entrainment:
𝐷/1000≥√(4/𝜋∙𝑄_𝑎/𝑢_𝑡 )
(4) (0.4528)
= = 0.930 m
(3.14) (0.667)
where:
Vessel Diameter
Typically, a blowdown vessel is sized to contain the water quantity (liquid) from two intermittent Blowdown cycles, plus the
vapor space above the water. The latter is sized to achieve proper water droplet separation, and to have a vapor velocity lower
than the critical gravity separation velocity.
Ref.8 recommends a maximum velocity of 11 ft/s (3.35 m/s) in the steam space, as a commonly used value to allow for proper
separation e minimization of water re-entrainment.
Thus, the minimum vesel diameter to satisfy the above condition would be:
𝐷_𝑣/1000≥√(4/𝜋∙𝑄_𝑠/𝑉_𝑚 )
(4) (0.453)
= = 0.41 m say 500 mm
(3.14) (3.35)
where:
Considering the resuls obtained and the uncertainties in the design data provided by the Client and boiler OEM, a high safety
factor it has been considered the following vessel diameter:
692284769.xlsx
39 of 49___ __
692284769.xlsx
Client: Galliford Try Doc. No. MI-17085-PR-CR-002
Project: Hull Biomass UK LLP 1 Tag No. T-06-17081
Location: Hull, United Kingdom Job No. MI-17085
ATMOSPHERIC BLOWDOWN TANK Rev. Date Sheet
PROCESS DESIGN REPORT 40 of 49___ __
4 22/08/17
Rev VESSEL SIZING
2. Calculation of Vessel Height
The starting point for the vessel height determination, following the procedure in [Ref.3], is the determination of the volume of
water after one cycle of intermittent blowdown and of drains, which will be the amount stored in the tank up to the Normal
Water Level (NWL). On the other hand, the volume of water after two cycles would be stored in below the vessel High Water
Level (HWL).
In this case, however, there are additional water inlet at high temperature apart from the IBD, which need to be stored in the
vessel. Therefore, the volume of water stored in the vessel for cooling will be the volume of water after a certain amount of
time, corresponding to the longest cycle duration among the high-temperature streams (IBD, SB Drains and Deaerator
Overflow).
The other streams, such as the CBD Liquor or boiler drains, do not need to be stored, as they are entering the vessel at low
temperature and could be discharged after a small amount of time to allow for settling of any deposit that might be carried over
with the fluid.
The duration of one cycle in design case is the maximum of the cycle duration of IBD, SB condensate and the DOF Deaerator
overflow.
Total water volume after each cycle with its duration τi, is then:
𝑉_𝑤=∑_𝑖▒ 〖𝑄 _𝑖 𝜏_𝑖 〗
= τIBD∙QIBD + τSB∙QSB + τDOF∙QDOF + τBFT∙QBFT = 360∙(0.21)+360∙(0.38)+60∙(946.12) = 0.17 m³
The Normal Water Level (NWL) height from the bottom of the vessel, assuming a 2:1 semi-ellipsoidal bottom head, is:
The total cylindrical length of the vessel, from tangent line to tangent line (TL-TL), is then calculated with the following
formula, modified from [Ref.3] to incorporate HP experience:
HT-T = HHWL + 1.75 Dves = 600 + 1.75 ∙ 1200 = 2698 mm say 2700 mm
Total vessel height, including bottom and top heads, will be:
Finally, the distance of the inlet nozzles from the bottom tangent line can be estimated as
692284769.xlsx
41 of 49___ __
692284769.xlsx
Client: Galliford Try Doc. No. MI-17085-PR-CR-002
Project: Hull Biomass UK LLP 1 Tag No. T-06-17081
Location: Hull, United Kingdom Job No. MI-17085
ATMOSPHERIC BLOWDOWN TANK Rev. Date Sheet
PROCESS DESIGN REPORT 4 22/08/17 42 of 49___ __
The following figure shows a sketch of the vessel, with highlighted the main dimensions of nozzles and vessel parts.
Vent
N7
N5 H head = 300 mm
N6
600 mm Hhwl
100 mm Hnwl
H1 N7 Water Outlet
N8
Deaerator
Sootblower Condensate Overflow N2
N4
692284769.xlsx
43 of 49___ __
692284769.xlsx
]
Client: Galliford Try Doc. No. MI-17085-PR-CR-002
Project: Hull Biomass UK LLP 1 Tag No. T-06-17081
Location: Hull, United Kingdom Job No. MI-17085
ATMOSPHERIC BLOWDOWN TANK Rev. Date Sheet
44 of 49_____
PROCESS DESIGN REPORT 4 22/08/17
INSULATION THICKNESS
Calculate the insulation thickness for PP (?), using the EN 12241 standard.
692284769.xlsx 09/19/2023
45 of 49_____
]
Client: Galliford Try Doc. No. MI-17085-PR-CR-002
Project: Hull Biomass UK LLP 1 Tag No. T-06-17081
Location: Hull, United Kingdom Job No. MI-17085
ATMOSPHERIC BLOWDOWN TANK Rev. Date Sheet
PROCESS DESIGN REPORT 4 22/08/17
692284769.xlsx 09/19/2023
Client: Galliford Try Doc. No. MI-17085-PR-CR-002
Project: Hull Biomass UK LLP 1 Tag No. T-06-17081
Location: Hull, United Kingdom Job No. MI-17085
ATMOSPHERIC BLOWDOWN TANK Rev. Date Sheet
46 of 49_____
PROCESS DESIGN REPORT 4 22/08/17
REFERENCES
[1] Green, D.W.; Perry, R.H. - Perry's Chemical Engineering Handbook, 8th Ed. (2008).
[2] Ludwig, E.E. - Applied Process Design Vol. 1, 3rd Ed. (1999).
[3] GPSA Engineering Data Book, Vol. I & II, 12th Ed. (2004).
[4] Towler, G.; Sinnott, R. - Chemical Engineering Design (2008).
[5] API 14E - Recommended Practice for Design and Installation of Offshore Production Platforms and Piping Systems,
5th Ed. (1991)
[6] Drawing No. HULL_01_DWG_19_70017_D - Blowdown System P&ID
[7] NB-27, Sizing a blow off vessel
692284769.xlsx
47 of 49_____
692284769.xlsx
Client: Galliford Try Doc. No. -
Project: Hull Biomass Plant UK Line No. 06-250-STM-CS1-H18
Location: Hull, UK Job No. MI-17085
Rev. Date 48 of 49
Sheet
CALCULATION SHEET
0 09/05/17
Atmospheric Blowdown Tank Air Vent Pressure Drop
Sootblower Condensate 8
Flash
Tank
Continuous Blowdown 1 T-06-
17026
6
Atmospheric
Blowdown Tank
T-06-17081
3 4
Make-up Water KEY
LCV
Preheater 12 Water
HE-06-17083 Saturated Steam
Make-up Water from Condensate
5
Treatment Plant To Drain System Intermittent Cond.
TCV
Foul Water
STREAM 1 2 3 4 5 6 7 8 9 10 11 12
Continuous Flash Tank Cold Hot Intermittent Sootblower Deaerator Blowdown
Description Flash Steam Cold Liquor Boiler Drains Vent Steam
Blowdown Liquor Make-up Make-up Blowdown Condensate Overflow Tank Outlet
Flow [kg/h] #NAME? #NAME? #NAME? #NAME?
Temperature [°C] #NAME? #NAME? #NAME? 20
Pressure [bar(a)] 48.8 #NAME? #NAME? 4
Density [kg/m³] #NAME? #NAME? #NAME? 998.3
Volume Flow [ m³/h] #NAME? #NAME? #NAME?