9
.1
Table 9.1.1.9 Alternating-Current Resistance and Reactance for 600-Volt Cables, .1
.9
-Phase, 60 Hz, 7S°C -Three Single Conductors in Conduit m
Conductor Size
Ohms to Neutral per 305 m
Alternating-Current Alternating-Current
X|, (Reactance) for All Effective Z at 0.85 PF for Effective Z at 0.85 PF for
Resistance for Uncoated Resistance for Aluminum
Wires Uncoated Copper Wires Aluminum Wires
Copper Wires Wires
PVC, Aluminum Steel PVC Aluminum Steel PVC Aluminum Steel PVC Aluminum Steel PVC Aluminum Steel
Conduits Conduit Conduit Conduit Conduit Conduit Conduit Conduit Conduit Conduit Conduit Conduit Conduit Conduit
2.0 (1.6) 0,058 0.073 3.1 3.1 3.1 2.7 2.7 2.7 ----- ------ -----------
3.5 (2.0) 0.054 0.068 2.0 2.0 2.0 3.2 3.2 3.2 1.7 1,7 1.7 2.8 2.8 2.8
5.5(26) 0.050 0.063 1.2 1.2 1.2 2.0 2.0 2.0 1.1 1.1 1.1 1.8 1,8 1.8
8.0 (3.2) 0.052 0.065 0.78 0.78 0.78 1.3 1.3 1.3 0 .69 0.69 0.70 1,1 1.1 1.1
C
14 0.051 0.064 0.49 0.49 0.49 0.81 0.81 0.81 0.44 0.45 0.45 0,71 0.72 0.72 H
22 0.048 p. 060 0.31 0.31 0.31 0.51 0,51 0.51 0.29 0.29 0.30 0.46 0.46 0.46 A
0.20 0.32 0.20 0.30 P
30 0.045 0.057 0.19 0.20 0.32 0.32 0.19 0.19 0,30 0.30 T
38 0.046 0.057 0 .15 0.16 0.16 0.25 0.26 0.25 0.16 0.16 0.16 0.24 0.24 0.25 E
R
50 0.044 0.055 0.12 0.13 0.12 0.20 0,21 0.20 0.13 0 13 0.13 0.19 0.20 0.20
60 0.043 0,054 0.10 0.10 0,10 0.16 0.16 0,16 0.11 0.11 0.11 0,16 0.16 0.16 9
80 0.042 0.052 0 .0 77 0 .0 82 0.079 0.13 0.13 0.13 0,088 0.092 0.094 0.13 0.13 0.14 -
T
100 0.041 0.051 0 .0 62 0 .0 67 0.063 0, 10 0.11 0.10 0 .0 74 0. 078 0.080 0.1 1 0,11 0.1 1 A
125 0.041 0.052 0 .0 52 0 .05 7 0 .0 54 0 .0 85 0, 09 0 0 .0 86 0.066 0.070 0.073 0.094 0.098 0.10 B
L
150 0.041 0.051 0 .0 44 0 .0 49 0. 04 5 0. 071 0.076 0.072 0. 05 9 0. 063 0.065 0 ,0 82 0. 086 0.088 E
175 0.040 0.050 0.038 0.043 0 .0 39 0. 061 0.066 0.063 0.053 0.058 0.060 0 .0 73 0. 07 7 0.080 S
200 0.040 0.049 0,033 0.038 0.035 0.054 0.059 0.055 0. 04 9 0. 053 0.056 0. 06 6 0. 071 0.073
250 0.039 0.048 0.027 0.032 0.029 0,043 0.048 0.045 0.043 0,048 0.050 0.057 0.061 0,064
325 0.039 0.048 0.023 0.028 0.025 0.036 0.041 0.038 0.040 0.044 0,047 0.051 0.055 0.058
375 0.038 0.048 0.019 0,024 0.021 0.029 0.034 0,031 0.036 0.040 0.043 0.045 0.049 0.052
400 0,038 0.048 0.019 0.024 0.021 0.029 0.034 0.031 0.036 0.040 0.043 0.045 0.049 0.052
500 0.037 0.046 0.015 0.019 0.018 0.023 0.027 0.025 0.032 0.036 0.040 0.039 0.042 0.046
Notes:
1.These valuesarebased on thefollowingconstants:UL-typeRHHwireswithClassBstranding,incradled configuration.Wireconductivitiesare 100percent IACS
copperand61 percentIACS aluminum,and aluminumc onduitis45 percent IACS.Capacitivereactance isignored,since itisnegligibleatthese voltages.
Theseresistancevalues arevalidonly at75°Cand forthe parametersas given,butarerepresenta tivefor 600-voltwiretypes operatingat60 Hz.
2. EffectiveZisdefinedasRcos(0) +X sin(0),where 0isthe powerfactor angleofthe circuit.Multiplying current byeffective impedance givesagood approximation
forline-to-neutralvoltage drop.Effective impedance valuesshown inthis tablearevalid onlyat0.85 powerfactor. 1
5
Foranothercircuitpowerfactor (PF),effectiveimpedance(Ze)canbecalculatedfromRandXLvaluesgiven in thistable asfollows: 0
6
Z e - R x P F + X t sin[arccos(PF)J.