Vdocuments - MX - Pec Ac Resistance Reactance Table

The document provides a table listing the resistance and reactance values for different sized copper and aluminum cables operating at 600 volts and 60 Hz at 75°C. The table includes values for alternating current resistance, reactance, and effective impedance for cables in various conduit types. Notes provide additional context about the parameters and definitions used to calculate the values in the table.

Uploaded by

Jhoanna Callo
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
235 views2 pages

Vdocuments - MX - Pec Ac Resistance Reactance Table

The document provides a table listing the resistance and reactance values for different sized copper and aluminum cables operating at 600 volts and 60 Hz at 75°C. The table includes values for alternating current resistance, reactance, and effective impedance for cables in various conduit types. Notes provide additional context about the parameters and definitions used to calculate the values in the table.

Uploaded by

Jhoanna Callo
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

*

9
.1
Table 9.1.1.9 Alternating-Current Resistance and Reactance for 600-Volt Cables, .1
.9
-Phase, 60 Hz, 7S°C -Three Single Conductors in Conduit m

Conductor Size
Ohms to Neutral per 305 m

Alternating-Current Alternating-Current
X|, (Reactance) for All Effective Z at 0.85 PF for Effective Z at 0.85 PF for
Resistance for Uncoated Resistance for Aluminum
Wires Uncoated Copper Wires Aluminum Wires
Copper Wires Wires
PVC, Aluminum Steel PVC Aluminum Steel PVC Aluminum Steel PVC Aluminum Steel PVC Aluminum Steel
Conduits Conduit Conduit Conduit Conduit Conduit Conduit Conduit Conduit Conduit Conduit Conduit Conduit Conduit
2.0 (1.6) 0,058 0.073 3.1 3.1 3.1 2.7 2.7 2.7 ----- ------ -----------

3.5 (2.0) 0.054 0.068 2.0 2.0 2.0 3.2 3.2 3.2 1.7 1,7 1.7 2.8 2.8 2.8
5.5(26) 0.050 0.063 1.2 1.2 1.2 2.0 2.0 2.0 1.1 1.1 1.1 1.8 1,8 1.8
8.0 (3.2) 0.052 0.065 0.78 0.78 0.78 1.3 1.3 1.3 0 .69 0.69 0.70 1,1 1.1 1.1
C
14 0.051 0.064 0.49 0.49 0.49 0.81 0.81 0.81 0.44 0.45 0.45 0,71 0.72 0.72 H
22 0.048 p. 060 0.31 0.31 0.31 0.51 0,51 0.51 0.29 0.29 0.30 0.46 0.46 0.46 A
0.20 0.32 0.20 0.30 P
30 0.045 0.057 0.19 0.20 0.32 0.32 0.19 0.19 0,30 0.30 T
38 0.046 0.057 0 .15 0.16 0.16 0.25 0.26 0.25 0.16 0.16 0.16 0.24 0.24 0.25 E
R
50 0.044 0.055 0.12 0.13 0.12 0.20 0,21 0.20 0.13 0 13 0.13 0.19 0.20 0.20
60 0.043 0,054 0.10 0.10 0,10 0.16 0.16 0,16 0.11 0.11 0.11 0,16 0.16 0.16 9
80 0.042 0.052 0 .0 77 0 .0 82 0.079 0.13 0.13 0.13 0,088 0.092 0.094 0.13 0.13 0.14 -
T
100 0.041 0.051 0 .0 62 0 .0 67 0.063 0, 10 0.11 0.10 0 .0 74 0. 078 0.080 0.1 1 0,11 0.1 1 A
125 0.041 0.052 0 .0 52 0 .05 7 0 .0 54 0 .0 85 0, 09 0 0 .0 86 0.066 0.070 0.073 0.094 0.098 0.10 B
L
150 0.041 0.051 0 .0 44 0 .0 49 0. 04 5 0. 071 0.076 0.072 0. 05 9 0. 063 0.065 0 ,0 82 0. 086 0.088 E
175 0.040 0.050 0.038 0.043 0 .0 39 0. 061 0.066 0.063 0.053 0.058 0.060 0 .0 73 0. 07 7 0.080 S
200 0.040 0.049 0,033 0.038 0.035 0.054 0.059 0.055 0. 04 9 0. 053 0.056 0. 06 6 0. 071 0.073
250 0.039 0.048 0.027 0.032 0.029 0,043 0.048 0.045 0.043 0,048 0.050 0.057 0.061 0,064
325 0.039 0.048 0.023 0.028 0.025 0.036 0.041 0.038 0.040 0.044 0,047 0.051 0.055 0.058
375 0.038 0.048 0.019 0,024 0.021 0.029 0.034 0,031 0.036 0.040 0.043 0.045 0.049 0.052
400 0,038 0.048 0.019 0.024 0.021 0.029 0.034 0.031 0.036 0.040 0.043 0.045 0.049 0.052
500 0.037 0.046 0.015 0.019 0.018 0.023 0.027 0.025 0.032 0.036 0.040 0.039 0.042 0.046
Notes:
1.These valuesarebased on thefollowingconstants:UL-typeRHHwireswithClassBstranding,incradled configuration.Wireconductivitiesare 100percent IACS
copperand61 percentIACS aluminum,and aluminumc onduitis45 percent IACS.Capacitivereactance isignored,since itisnegligibleatthese voltages.
Theseresistancevalues arevalidonly at75°Cand forthe parametersas given,butarerepresenta tivefor 600-voltwiretypes operatingat60 Hz.
2. EffectiveZisdefinedasRcos(0) +X sin(0),where 0isthe powerfactor angleofthe circuit.Multiplying current byeffective impedance givesagood approximation
forline-to-neutralvoltage drop.Effective impedance valuesshown inthis tablearevalid onlyat0.85 powerfactor. 1
5
Foranothercircuitpowerfactor (PF),effectiveimpedance(Ze)canbecalculatedfromRandXLvaluesgiven in thistable asfollows: 0
6
Z e -  R x P F  +  X t sin[arccos(PF)J.