Relay Test Report: Overcurrent Settings
Relay Test Report: Overcurrent Settings
17/09/2023
PAGE 1
Nameplate Data
MANUFACTURER: MODEL: TEST STATUS: Pass
Asset ID: SERIAL NUMBER: DATASHEET:
SUBSTATION PT RATIO: kV : V Counter Clockwise Rotation 0-360 Lag
LZOP: CT RATIO: :5 A Earthing L->N JOB #:
PROTECTION: RELAY FIRMWARE:
Overcurrent Settings
Phase Time Overcurrent
Manufacturer: IEC Model: All
Curve: I>: 3.10 A I>>: 37.50 A I>>>: 0.00 A Reset: 1.00 (s)
IEC Curve B Very Inverse Mult: 0.050 tI>>: 0.04 (s) tI>>>: 0.00 (s)
ABC
Multiple
1.364
2 1.50 4.650 1.283 1.350 1.418 1.03% P
0.686
3 2.00 6.200 0.642 0.676 0.726 1.53% P
0.345
4 3.00 9.300 0.321 0.338 0.388 2.33% P