ETEndsem Aut 2022
ETEndsem Aut 2022
Marks Obtained (in words) Signature of the Examiner Signature of the Scrutineer
P a g e 1 | 24
INDIAN INSTITUTE OF TECHNOLOGY KHARAGPUR
End-Autumn Semester Examination 2022-23
Date of Examination: ____14 February 2023_ Session: AN___ Duration: 3 hrs. Full marks: 100__ _
Subject Number: EE11003, EE11001 Subject: Electrical Technology _
Department/Centre/School: Electrical Engineering_________ _
Specific charts, graph papers, log book, etc. required: No___ _Special instructions if any: No _
Please check that this booklet has all 24 pages. Answer all questions.
Write the detailed solutions clearly and neatly using the space provided.
Solution
P a g e 2 | 24
Consider the circuit shown in Fig. Q1b.
Q1b. 𝑗𝑗8 Ω + −𝑗𝑗8 Ω
(i) Find the active power supplied by the voltage source.
10∠0° V [3 marks]
−𝑗𝑗4 Ω − 𝑗𝑗4 Ω
(ii) Find the active power supplied by the current source.
2∠0° 𝐴𝐴
[3 marks]
Fig. Q1b
Solution
P a g e 3 | 24
𝑅𝑅 𝑗𝑗6 Ω
Q1c. In Fig. Q1c, the complex power supplied by the current source is
𝑅𝑅 (40 + 𝑗𝑗0)𝑉𝑉𝑉𝑉. Find X C and R.
Solution
P a g e 4 | 24
P a g e 5 | 24
Q1d. 20∠0° V 20∠0° V In Fig. Q1d, find the currents 𝐼𝐼1 , 𝐼𝐼2 , and 𝐼𝐼3 using nodal
analysis. [6 marks]
𝐼𝐼1 =
20∠90° V
−𝑗𝑗4 Ω 𝑗𝑗4 Ω 𝐼𝐼2 =
𝑗𝑗4 Ω 2Ω −𝑗𝑗4 Ω
Fig. Q1d
Solution
P a g e 6 | 24
Q2a. Consider the circuit shown in Fig. Q2a.
Fig. Q2a
Solution
P a g e 7 | 24
P a g e 8 | 24
Consider the circuit shown in Fig. Q2b.
Q2b
The switches K1 and K 2 are kept close and open re-
spectively for sufficiently long time. The AC supply
voltage is v(t ) = 100 sin (314t ) V . At an instant t=t0,
(t0>0) the switch K1 is opened and the switch K 2 is
closed simultaneously.
What is the minimum value of t0 such that there is
no transient in inductor current?
[12 marks]
Fig. Q2b
Solution
P a g e 9 | 24
P a g e 10 | 24
Q3a. A 3-phase Y-connected load takes 10 kVA at 0.6 power factor lagging from a source of 220 V RMS. It
is in parallel with a balanced delta connected load having 16 Ω resistance and 12 Ω capacitive reactance
in series in each phase. Find the line current and power factor of the combination. [5+5=10 marks]
Solution
P a g e 11 | 24
Q3b.
Fig. Q3b
Two balanced three-phase systems X and Y are interconnected with line having impedance of (1+j2) Ω .
The line voltage (RMS) at the terminal of System X is V ab = 12∠0 0 kV and at the terminal of System Y
is V AB = 12∠5 0 kV . The phase sequences of Systems X and Y are, respectively, a-b-c and A-B-C.
Determine which system is acting as a source and which one is a load, and how much active power is
received by the system acting as load.
Solution
P a g e 12 | 24
P a g e 13 | 24
Consider a 200V/50V, 50Hz, 10kVA single phase two-winding transformer.
Q4a.
(i) If the high voltage (HV) side of the transformer is supplied from a 48 V battery having 1 Ω internal
resistance, find the output voltage across the low voltage (LV) terminals at steady state for the following
cases: (a) the LV side is open circuited, and (b) a resistance of 10 Ω is connected across the LV side.
[2 marks]
(ii) How the coils of this two-winding transformer can be connected to form an autotransformer having
maximum VA rating at the output? Justify your solution with proper circuit diagram including dots.
[6 marks]
Solution
P a g e 14 | 24
P a g e 15 | 24
Q4b. A 10 kVA, 50 V, 50 Hz load is to be supplied from a 200 V, 50 Hz ideal voltage source. This is carried
out by employing a two-winding transformer (case A) or an autotransformer (case B) of suitable rating. Find the
ratio of requirement of copper in case B with respect to case A. [4 marks]
P a g e 16 | 24
Two coils shown in Fig. Q4b are magnetically coupled. The self-
Q4c. inductances of coil having terminals A-B and C-D are 10 mH and 8
mH respectively.
(i)What can be the maximum value of M (in mH) that can be
achieved for this arrangement? [1 mark]
Solution
P a g e 17 | 24
The nameplate of a single-phase transformer reads: 10MVA, 50Hz, 25kV/10kV, leakage impedance
Q5a. (Zeq) = 0.2 p.u.. During short-circuit (SC) test on the high voltage (HV) side of this transformer (with
low voltage (LV) side shorted), the ammeter and wattmeter readings were 200A and 50kW respectively.
(i) What is the value of the voltage in p.u. that was applied during the above-mentioned SC test? [1 mark]
Also find the value of total leakage reactance (xeq) referred to the HV side. [3 marks]
(ii) While supplying a load, the terminal voltages of the HV side and LV side of this transformer are
found to be 25kV∠0° and 10kV∠10° respectively. The load is connected to which terminals (i.e., LV
terminals or HV terminals) of the transformer? [1 mark]
Neglecting winding resistances, find the active power delivered by the transformer. [3 marks]
Also find the regulation of the transformer under this operating condition. [2 marks]
Solution
P a g e 18 | 24
P a g e 19 | 24
P a g e 20 | 24
Q5b.
a k
a k c
a k c
5H 1.25H
b d
b d b
d c
Fig. Q5(b)-(i) Fig. Q5(b)-(ii) Fig. Q5(b)-(iii)
The voltage ratings of the two windings, a-b and c-d of a 4 kVA, 50 Hz transformer (shown in Fig.
Q5(b)-(i)) are 400 V and 200 V respectively. The parameters of the transformer are:
Self-inductance of winding a-b, Lab = 5.0 H; Self-inductance of winding c-d, Lcd = 1.25 H;
Co-efficient of coupling, k = 0.98;
Number of turns of winding a-b, Nab = 360; Number of turns of winding c-d, Ncd = 180;
Now, this transformer has to be used as an inductor such that none of its limits (rated voltage and current
of the windings and rated flux density of the core) is violated. Two probable connections to achieve this
are shown in Fig. Q5(b)-(ii) and Fig. Q5(b)-(iii). For each of these connections, find the net inductance.
Now, for the inductor having larger inductance find the current rating, the VA rating and the peak value
of maximum total flux in the core. Losses of the transformer are neglected and the magnetizing current
is considered sinusoidal. [4 marks]
Solution
P a g e 21 | 24
P a g e 22 | 24
P a g e 23 | 24
P a g e 24 | 24