0% found this document useful (0 votes)
86 views3 pages

Occupation Density

Uploaded by

spy boy
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
86 views3 pages

Occupation Density

Uploaded by

spy boy
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 3

Copyrighted material licensed to University of Toronto by Techstreet LLC, subscriptions.techstreet.com, downloaded on 2022-09-02 10:33:34 +0000 by University of Toronto User.

No further reproduction or distribution is permitted.


Table 6-1 Minimum Ventilation Rates in Breathing Zone

Default Values
People Outdoor Area Outdoor
Air Rate Rp Air Rate Ra Occupant Density
cfm/ L/s· #/1000 ft2 Air OS
Occupancy Category person person cfm/ft2 L/s·m2 or #/100 m2 Class (6.2.6.1.4)
Animal Facilities
Animal exam room (veterinary office) 10 5 0.12 0.6 20 2

Animal imaging (MRI/CT/PET) 10 5 0.18 0.9 20 3


Animal operating rooms 10 5 0.18 0.9 20 3
Animal postoperative recovery room 10 5 0.18 0.9 20 3
Animal preparation rooms 10 5 0.18 0.9 20 3
Animal procedure room 10 5 0.18 0.9 20 3

Animal surgery scrub 10 5 0.18 0.9 20 3


Large-animal holding room 10 5 0.18 0.9 20 3
Necropsy 10 5 0.18 0.9 20 3
Small-animal-cage room (static cages) 10 5 0.18 0.9 20 3
Small-animal-cage room (ventilated cages) 10 5 0.18 0.9 20 3
Correctional Facilities
Booking/waiting 7.5 3.8 0.06 0.3 50 2
Cell 5 2.5 0.12 0.6 25 2
Dayroom 5 2.5 0.06 0.3 30 1
Guard stations 5 2.5 0.06 0.3 15 1
Educational Facilities
Art classroom 10 5 0.18 0.9 20 2
Classrooms (ages 5 to 8) 10 5 0.12 0.6 25 1

Classrooms (age 9 plus) 10 5 0.12 0.6 35 1


Computer lab 10 5 0.12 0.6 25 1

Daycare sickroom 10 5 0.18 0.9 25 3

Daycare (through age 4) 10 5 0.18 0.9 25 2


Lecture classroom 7.5 3.8 0.06 0.3 65 1 
Lecture hall (fixed seats) 7.5 3.8 0.06 0.3 150 1 
Libraries 5 2.5 0.12 0.6 10
Media center 10 5 0.12 0.6 25 1

Multiuse assembly 7.5 3.8 0.06 0.3 100 1 


Music/theater/dance 10 5 0.06 0.3 35 1 
Science laboratories 10 5 0.18 0.9 25 2
University/college laboratories 10 5 0.18 0.9 25 2
Wood/metal shop 10 5 0.18 0.9 20 2

Food and Beverage Service


Bars, cocktail lounges 7.5 3.8 0.18 0.9 100 2

ANSI/ASHRAE Standard 62.1-2022 17


Copyrighted material licensed to University of Toronto by Techstreet LLC, subscriptions.techstreet.com, downloaded on 2022-09-02 10:33:34 +0000 by University of Toronto User.
No further reproduction or distribution is permitted.
Table 6-1 Minimum Ventilation Rates in Breathing Zone (Continued)

Default Values
People Outdoor Area Outdoor
Air Rate Rp Air Rate Ra Occupant Density
cfm/ L/s· #/1000 ft2 Air OS
Occupancy Category person person cfm/ft2 L/s·m2 or #/100 m2 Class (6.2.6.1.4)
Cafeteria/fast-food dining 7.5 3.8 0.18 0.9 100 2

Kitchen (cooking) 7.5 3.8 0.12 0.6 20 2


Restaurant dining rooms 7.5 3.8 0.18 0.9 70 2

General

Break rooms 5 2.5 0.06 0.3 25 1 


Coffee stations 5 2.5 0.06 0.3 20 1 
Conference/meeting 5 2.5 0.06 0.3 50 1 
Corridors — — 0.06 0.3 — 1 
Occupiable storage rooms for liquids or gels 5 2.5 0.12 0.6 2 2
Hotels, Motels, Resorts, Dormitories

Barracks sleeping areas 5 2.5 0.06 0.3 20 1 


Bedroom/living room 5 2.5 0.06 0.3 10 1 
Laundry rooms, central 5 2.5 0.12 0.6 10 2
Laundry rooms within dwelling units 5 2.5 0.12 0.6 10 1

Lobbies/prefunction 7.5 3.8 0.06 0.3 30 1 


Multipurpose assembly 5 2.5 0.06 0.3 120 1 
Miscellaneous Spaces
Banks or bank lobbies 7.5 3.8 0.06 0.3 15 1 
Bank vaults/safe deposit 5 2.5 0.06 0.3 5 2 
Computer (not printing) 5 2.5 0.06 0.3 4 1 
Freezer and refrigerated spaces (<50°F [10°C]) 10 5 0 0 0 2
Manufacturing where hazardous materials  10 5.0 0.18 0.9 7 2
are not used
Manufacturing where hazardous materials are 10 5.0 0.18 0.9 7 3
used (excludes heavy industrial and chemical
processes)
Pharmacy (prep. area) 5 2.5 0.18 0.9 10 2
Photo studios 5 2.5 0.12 0.6 10 1

Shipping/receiving 10 5 0.12 0.6 2 2


Sorting, packing, light assembly 7.5 3.8 0.12 0.6 7 2
Telephone closets — — 0.00 0.0 — 1

Transportation waiting 7.5 3.8 0.06 0.3 100 1 


Warehouses 10 5 0.06 0.3 — 2

Office Buildings

Breakrooms 5 2.5 0.12 0.6 50 1


Main entry lobbies 5 2.5 0.06 0.3 10 1 

18 ANSI/ASHRAE Standard 62.1-2022


Copyrighted material licensed to University of Toronto by Techstreet LLC, subscriptions.techstreet.com, downloaded on 2022-09-02 10:33:34 +0000 by University of Toronto User.
No further reproduction or distribution is permitted.
Table 6-1 Minimum Ventilation Rates in Breathing Zone (Continued)

Default Values
People Outdoor Area Outdoor
Air Rate Rp Air Rate Ra Occupant Density
cfm/ L/s· #/1000 ft2 Air OS
Occupancy Category person person cfm/ft2 L/s·m2 or #/100 m2 Class (6.2.6.1.4)
Occupiable storage rooms for dry materials 5 2.5 0.06 0.3 2 1
Office space 5 2.5 0.06 0.3 5 1 
Reception areas 5 2.5 0.06 0.3 30 1 
Telephone/data entry 5 2.5 0.06 0.3 60 1 
Public Assembly Spaces
Auditorium seating area 5 2.5 0.06 0.3 150 1 
Courtrooms 5 2.5 0.06 0.3 70 1 
Legislative chambers 5 2.5 0.06 0.3 50 1 
Libraries 5 2.5 0.12 0.6 10 1

Lobbies 5 2.5 0.06 0.3 150 1 


Museums (children’s) 7.5 3.8 0.12 0.6 40 1

Museums/galleries 7.5 3.8 0.06 0.3 40 1 


Places of religious worship 5 2.5 0.06 0.3 120 1 
Residential
Common corridors — — 0.06 0.3 1 
Retail
Sales (except as below) 7.5 3.8 0.12 0.6 15 2
Barbershop 7.5 3.8 0.06 0.3 25 2 
Beauty and nail salons 20 10 0.12 0.6 25 2
Coin-operated laundries 7.5 3.8 0.12 0.6 20 2
Mall common areas 7.5 3.8 0.06 0.3 40 1 
Pet shops (animal areas) 7.5 3.8 0.18 0.9 10 2
Supermarket 7.5 3.8 0.06 0.3 8 1 
Sports and Entertainment
Bowling alley (seating) 10 5 0.12 0.6 40 1
Disco/dance floors 20 10 0.06 0.3 100 2 
Gambling casinos 7.5 3.8 0.18 0.9 120 1
Game arcades 7.5 3.8 0.18 0.9 20 1
Gym, sports arena (play area) 20 10 0.18 0.9 7 2
Health club/aerobics room 20 10 0.06 0.3 40 2
Health club/weight rooms 20 10 0.06 0.3 10 2
Spectator areas 7.5 3.8 0.06 0.3 150 1 
Stages, studios 10 5 0.06 0.3 70 1 
Swimming (pool and deck) — — 0.48 2.4 — 2

ANSI/ASHRAE Standard 62.1-2022 19