Copyrighted material licensed to University of Toronto by Techstreet LLC, subscriptions.techstreet.com, downloaded on 2022-09-02 10:33:34 +0000 by University of Toronto User.
No further reproduction or distribution is permitted.
Table 6-1 Minimum Ventilation Rates in Breathing Zone
Default Values
People Outdoor Area Outdoor
Air Rate Rp Air Rate Ra Occupant Density
cfm/ L/s· #/1000 ft2 Air OS
Occupancy Category person person cfm/ft2 L/s·m2 or #/100 m2 Class (6.2.6.1.4)
Animal Facilities
Animal exam room (veterinary office) 10 5 0.12 0.6 20 2
Animal imaging (MRI/CT/PET) 10 5 0.18 0.9 20 3
Animal operating rooms 10 5 0.18 0.9 20 3
Animal postoperative recovery room 10 5 0.18 0.9 20 3
Animal preparation rooms 10 5 0.18 0.9 20 3
Animal procedure room 10 5 0.18 0.9 20 3
Animal surgery scrub 10 5 0.18 0.9 20 3
Large-animal holding room 10 5 0.18 0.9 20 3
Necropsy 10 5 0.18 0.9 20 3
Small-animal-cage room (static cages) 10 5 0.18 0.9 20 3
Small-animal-cage room (ventilated cages) 10 5 0.18 0.9 20 3
Correctional Facilities
Booking/waiting 7.5 3.8 0.06 0.3 50 2
Cell 5 2.5 0.12 0.6 25 2
Dayroom 5 2.5 0.06 0.3 30 1
Guard stations 5 2.5 0.06 0.3 15 1
Educational Facilities
Art classroom 10 5 0.18 0.9 20 2
Classrooms (ages 5 to 8) 10 5 0.12 0.6 25 1
Classrooms (age 9 plus) 10 5 0.12 0.6 35 1
Computer lab 10 5 0.12 0.6 25 1
Daycare sickroom 10 5 0.18 0.9 25 3
Daycare (through age 4) 10 5 0.18 0.9 25 2
Lecture classroom 7.5 3.8 0.06 0.3 65 1
Lecture hall (fixed seats) 7.5 3.8 0.06 0.3 150 1
Libraries 5 2.5 0.12 0.6 10
Media center 10 5 0.12 0.6 25 1
Multiuse assembly 7.5 3.8 0.06 0.3 100 1
Music/theater/dance 10 5 0.06 0.3 35 1
Science laboratories 10 5 0.18 0.9 25 2
University/college laboratories 10 5 0.18 0.9 25 2
Wood/metal shop 10 5 0.18 0.9 20 2
Food and Beverage Service
Bars, cocktail lounges 7.5 3.8 0.18 0.9 100 2
ANSI/ASHRAE Standard 62.1-2022 17
Copyrighted material licensed to University of Toronto by Techstreet LLC, subscriptions.techstreet.com, downloaded on 2022-09-02 10:33:34 +0000 by University of Toronto User.
No further reproduction or distribution is permitted.
Table 6-1 Minimum Ventilation Rates in Breathing Zone (Continued)
Default Values
People Outdoor Area Outdoor
Air Rate Rp Air Rate Ra Occupant Density
cfm/ L/s· #/1000 ft2 Air OS
Occupancy Category person person cfm/ft2 L/s·m2 or #/100 m2 Class (6.2.6.1.4)
Cafeteria/fast-food dining 7.5 3.8 0.18 0.9 100 2
Kitchen (cooking) 7.5 3.8 0.12 0.6 20 2
Restaurant dining rooms 7.5 3.8 0.18 0.9 70 2
General
Break rooms 5 2.5 0.06 0.3 25 1
Coffee stations 5 2.5 0.06 0.3 20 1
Conference/meeting 5 2.5 0.06 0.3 50 1
Corridors — — 0.06 0.3 — 1
Occupiable storage rooms for liquids or gels 5 2.5 0.12 0.6 2 2
Hotels, Motels, Resorts, Dormitories
Barracks sleeping areas 5 2.5 0.06 0.3 20 1
Bedroom/living room 5 2.5 0.06 0.3 10 1
Laundry rooms, central 5 2.5 0.12 0.6 10 2
Laundry rooms within dwelling units 5 2.5 0.12 0.6 10 1
Lobbies/prefunction 7.5 3.8 0.06 0.3 30 1
Multipurpose assembly 5 2.5 0.06 0.3 120 1
Miscellaneous Spaces
Banks or bank lobbies 7.5 3.8 0.06 0.3 15 1
Bank vaults/safe deposit 5 2.5 0.06 0.3 5 2
Computer (not printing) 5 2.5 0.06 0.3 4 1
Freezer and refrigerated spaces (<50°F [10°C]) 10 5 0 0 0 2
Manufacturing where hazardous materials 10 5.0 0.18 0.9 7 2
are not used
Manufacturing where hazardous materials are 10 5.0 0.18 0.9 7 3
used (excludes heavy industrial and chemical
processes)
Pharmacy (prep. area) 5 2.5 0.18 0.9 10 2
Photo studios 5 2.5 0.12 0.6 10 1
Shipping/receiving 10 5 0.12 0.6 2 2
Sorting, packing, light assembly 7.5 3.8 0.12 0.6 7 2
Telephone closets — — 0.00 0.0 — 1
Transportation waiting 7.5 3.8 0.06 0.3 100 1
Warehouses 10 5 0.06 0.3 — 2
Office Buildings
Breakrooms 5 2.5 0.12 0.6 50 1
Main entry lobbies 5 2.5 0.06 0.3 10 1
18 ANSI/ASHRAE Standard 62.1-2022
Copyrighted material licensed to University of Toronto by Techstreet LLC, subscriptions.techstreet.com, downloaded on 2022-09-02 10:33:34 +0000 by University of Toronto User.
No further reproduction or distribution is permitted.
Table 6-1 Minimum Ventilation Rates in Breathing Zone (Continued)
Default Values
People Outdoor Area Outdoor
Air Rate Rp Air Rate Ra Occupant Density
cfm/ L/s· #/1000 ft2 Air OS
Occupancy Category person person cfm/ft2 L/s·m2 or #/100 m2 Class (6.2.6.1.4)
Occupiable storage rooms for dry materials 5 2.5 0.06 0.3 2 1
Office space 5 2.5 0.06 0.3 5 1
Reception areas 5 2.5 0.06 0.3 30 1
Telephone/data entry 5 2.5 0.06 0.3 60 1
Public Assembly Spaces
Auditorium seating area 5 2.5 0.06 0.3 150 1
Courtrooms 5 2.5 0.06 0.3 70 1
Legislative chambers 5 2.5 0.06 0.3 50 1
Libraries 5 2.5 0.12 0.6 10 1
Lobbies 5 2.5 0.06 0.3 150 1
Museums (children’s) 7.5 3.8 0.12 0.6 40 1
Museums/galleries 7.5 3.8 0.06 0.3 40 1
Places of religious worship 5 2.5 0.06 0.3 120 1
Residential
Common corridors — — 0.06 0.3 1
Retail
Sales (except as below) 7.5 3.8 0.12 0.6 15 2
Barbershop 7.5 3.8 0.06 0.3 25 2
Beauty and nail salons 20 10 0.12 0.6 25 2
Coin-operated laundries 7.5 3.8 0.12 0.6 20 2
Mall common areas 7.5 3.8 0.06 0.3 40 1
Pet shops (animal areas) 7.5 3.8 0.18 0.9 10 2
Supermarket 7.5 3.8 0.06 0.3 8 1
Sports and Entertainment
Bowling alley (seating) 10 5 0.12 0.6 40 1
Disco/dance floors 20 10 0.06 0.3 100 2
Gambling casinos 7.5 3.8 0.18 0.9 120 1
Game arcades 7.5 3.8 0.18 0.9 20 1
Gym, sports arena (play area) 20 10 0.18 0.9 7 2
Health club/aerobics room 20 10 0.06 0.3 40 2
Health club/weight rooms 20 10 0.06 0.3 10 2
Spectator areas 7.5 3.8 0.06 0.3 150 1
Stages, studios 10 5 0.06 0.3 70 1
Swimming (pool and deck) — — 0.48 2.4 — 2
ANSI/ASHRAE Standard 62.1-2022 19