0% found this document useful (0 votes)
455 views2 pages

Liebert Ita2 Data Sheet English

The document describes the Liebert ITA2 10-30 kVA UPS system. It provides power protection for IT equipment through true online double conversion and has a compact rack/tower design. It offers high efficiency, flexibility, and can be installed in parallel configurations for increased capacity.

Uploaded by

Jamshed Ahmed
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
455 views2 pages

Liebert Ita2 Data Sheet English

The document describes the Liebert ITA2 10-30 kVA UPS system. It provides power protection for IT equipment through true online double conversion and has a compact rack/tower design. It offers high efficiency, flexibility, and can be installed in parallel configurations for increased capacity.

Uploaded by

Jamshed Ahmed
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

Liebert® ITA2 10 - 30 kVA

Flexible power protection for Rack or Tower installation

Remarkable Efficiency and Flexibility characterize the


HIGHLIGHTS Liebert® ITA2 UPS
The Liebert ITA2 series is ideally Featuring true online double conversion technology, unity
suited for:
y Small computer rooms
power factor and an extremely compact rack-tower design,
y Integrated solutions Liebert ITA2 is the perfect power protection solution for
y Branch offices your computer rooms, storage and network equipment.
y Servers
y Network computers and
peripherals
y Storage device Description Liebert ITA2 offers enhanced flexibility
y VoIP. With a unity output power factor, Liebert with a wide range of accessories for
ITA2 perfectly matches the needs of both stand-alone and rack-mount
Product Features:
modern IT loads, and with its wide input installations. When rack mounted, it
y Rack-tower design for installation allows to install up to 30 kVA UPS in just
flexibility voltage and frequency range it effectively
reduces the need for battery intervention, 3 U of space, achieving a remarkable
y Able to deliver both three-phase space saving. Parallelability and
and single-phase output (10-20 thus prolonging battery life.
maintenance are facilitated through the
kVA) It is also endowed with intelligent fans use of dedicated maintenance bypass
y Ultra high power density, thanks with automatic speed control, which option while extended backup time can
to 30% reduced dimensions effectively save energy and reduce
compared to the previous be provided with matching battery
noise. modules for a neat rack-mounted
generation
Liebert ITA2 supports common battery installation.
y 0.99 input power factor for better
grid or generator compatibility configurations between paralleled UPS Liebert ITA2 features a multi-lingual LCD
y Unity output power factor for and the number of batteries per string, user interface allowing close control and
additional power availability which can be arranged flexibly, monitoring of system status and
y Efficiency in double conversion up facilitating the utilization of different performance.
to 96.2% battery systems and saving on battery
y ECO mode operation with investment.
efficiency up to 99% and An extra powerful battery charger
remarkable energy-saving across all models capable of recharging
performance high capacity battery strings ensures a
y Powerful charging capability for fast charge-restoration even after a
minimum battery recharging prolonged power outages.
time.
The UPS is compatible with any
Building Management System
(BMS) by offering the following
communication features:
y Voltage-free contact ports
y USB interface
y Vertiv™ IntelliSlot™ for SNMP,
Modbus or Relay communication
y Programmable output terminals
(10-20 kVA).

Liebert ITA2 10 - 30 kVA


Liebert® ITA2 10 - 30 kVA

Liebert® ITA2 10 - 30 kVA

Technical Specifications
Ratings (kVA) 10 15 20 30

Input
Nominal input voltage (V) 380/400/415 (three-phase + neutral)
Input voltage range without battery discharge (V) 173 to 498*
Nominal input frequency (Hz) 50/60
Input frequency range (Hz) 40-70
Bypass voltage tolerance (%) selectable from +20 to -40
Bypass frequency tolerance (%) ±20 (±10 selectable)
Input power factor at full load (kW/kVA) 0.99
Current THD at full linear load (THDI%) ≤3*

Battery Management
Battery blocks per string 24-40*
Voltage temperature compensation (mV/°C/Cell) -3
Battery charger max. current (A) 13

Output
Nominal output voltage (V) 380/400/415 (three-phase) or 220/230/240 (single-phase) 380/400/415 (three-phase)
Nominal output frequency (Hz) 50/60
Maximum active power (kW) 10 15 20 30
THDv at full linear load (%) ≤2
105% for 60 min; 125% 10 min;
Inverter overload capacity at 25°C 105% for 60 min; 125% 5 min; 150% for 1 min, > 150%, 200 ms
150% for 1 min, > 150%, 200 ms

Efficiency
Double conversion efficiency Up to 96.2%
ECO Mode Efficiency Up to 99%

Dimensions and Weight


Dimensions (W x D x H) (mm) 430 x 500 x 130 (UPS)
430 x 500 x 130 (Battery module 3U, 16 x 9 Ah)
430 x 650 x 85 (Battery module 2U, 16 x 9 Ah)
430 x 500 x 175 (single POD)
430 x 500 x 260 (1+1 parallel POD)
Net Weight (kg) 23 (UPS)
51 (Battery module 3U, 16 x 9 Ah)
51 (Battery module 2U, 16 x 9 Ah)
18 (single POD)
30 (1+1 parallel POD)

General
Noise at 1 m (dBA) ≤58 <60
Ventilation Front to back
Maximum altitude 1500 m without derating (max. 3000 m)
Protection level IEC (60529) IP20
General and safety requirements for UPS EN/IEC/AS 62040-1
EMC requirements for UPS EN/IEC/AS 62040-2
UPS classification according to CEI EN 62040-3 VFI-SS-111
* Conditions apply

Vertiv.com | Vertiv Infrastructure Limited, George Curl Way, Southampton, SO18 2RY, VAT Number: GB188146827