HRFW-75 T5 RENTAL RANGE
Powered by FPT_IVECO
SERVICE PRP ESP
POWER kVA 73 80
POWER kW 58 64
RATED SPEED r.p.m. 1.500
MAIN VOLTAGE V 400/230
AVAILABLE VOLTAGES V 200/115 · 230 V (t)
RATED AT POWER Cos Phi 0,8
FACTOR
RENTAL RANGE SOUNDPROOFED RENTAL
HIMOINSA Company with quality certification ISO 9001
HIMOINSA gensets are compliant with EC mark which includes the following
directives: D10R
• 2006/42/CE Machinery safety.
• 2014/30/UE Electromagnetic compatibility.
• 2014/35/UE electrical equipment designed for use within certain voltage limits
• 2000/14/EC Sound Power level. Noise emissions outdoor equipment. (amended by
2005/88/EC) WATER-COOLED
• EN 12100, EN 13857, EN 60204
Ambient conditions of reference according to ISO 8528-1:2018 normative: 1000 mbar,
25ºC, 30% relative humidity.
Prime Power (PRP):
THREE PHASE
According to ISO 8528-1:2018, Prime power is the maximum power which a
generating set is capable of delivering continuously whilst supplying a variable
electrical load when operated for an unlimited number of hours per year under the
agreed operating conditions with the maintenance intervals and procedures being
carried out as prescribed by the manufacturer. The permissible average power output 50 HZ
(Ppp) over 24 h of operation shall not exceed 70 % of the PRP.
Emergency Standby Power (ESP):
According to ISO 8528-1:2018, Emergency standby power is the maximum power
available during a variable electrical power sequence, under the stated operating DIESEL
conditions, for which a generating set is capable of delivering in the event of a utility
power outage or under test conditions for up to 200 h of operation per year with the
maintenance intervals and procedures being carried out as prescribed by the
manufacturers. The permissible average power output over 24 h of operation shall not
exceed 70 % of the ESP
Continuous Power (COP): According to Standard ISO 8528-1:2018, this is the Himoinsa has the right to modify any feature without prior notice.
maximum power available for continuous loads for unlimited running hours a year
between the maintenance times recommended by the manufacturer under the Weights and dimensions based on standard products. Illustrations may
environmental conditions established by the same. include optional equipment.
G2 class load acceptance in accordance with ISO 8528-5:2018 Technical data described in this catalogue correspond to the available
information at the moment of printing.
HIMOINSA HEADQUARTERS: The illustrations and images are indicative and may not coincide in their
Fábrica: Ctra. Murcia - San Javier, Km. 23,6 | 30730 SAN JAVIER (Murcia) Spain entirety with the product.
Tel.+34 968 19 11 28 Fax +34 968 19 12 17 Fax +34 968 19 04 20 |
[email protected] | www.himoinsa.com Industrial design under patent.
Manufacture facilities:
SPAIN • FRANCE • INDIA • CHINA • USA • BRAZIL • ARGENTINA
Subsidiaries:
PORTUGAL | POLAND | GERMANY | UK | SINGAPORE | UAE | PANAMA |
DOMINICAN REPUBLIC | ARGENTINA | ANGOLA | SOUTH AFRICA
2023-MAY.-25 16:02
Ctra. Murcia - San Javier, km. 23,6 | 30730 San Javier (Murcia) SPAIN | Tel.: +34 902 19 11 28 / +34 968 19 11 28
Fax: +34 968 19 12 17 | Export Fax +34 968 19 04 20 | E-mail:[email protected] | www.himoinsa.com
HRFW-75 T5
Engine Specifications | 1.500 r.p.m.
Rated Engine Output (PRP) kW 72,5 Lube oil consumption with 0,5 % of fuel
full load consumption
Rated Engine Output (ESP) kW 79,9
Total oil capacity including
Manufacturer FPT_IVECO L 12,8
tubes, filters
Model NEF45SM3 Total coolant capacity L 18,5
Engine Type 4-stroke diesel Governor Type Mechanical
Injection Type Direct Air Filter Type Dry
Aspiration Type Turbocharged Inner diameter exhaust pipe mm 70,3
Number of cylinders and 4-L
arrangement
Bore and Stroke mm 104 x 132
Displacement L 4,5
Liquid (water +
Cooling System 50% glycol)
Lube Oil Specifications ACEA E3 - E5
Compression Ratio 17,5:1
• Diesel engine • Water separator filter (no visible • Mechanical governor
level)
• 4-stroke cycle • Hot parts protection
• Dry air filter
• Water-cooled • Moving parts protection
• Radiator with pusher fan
• 12V electrical system
Generator Specifications | STAMFORD
Manufacturer STAMFORD Enclosure (according IP23
IEC-34-5)
Model UCI224F
Self-excited,
Poles No. 4 Exciter system brushless
Connection type (standard) Star-series Voltage regulator A.V.R. (Electronic)
Mounting type S-3 11"1/2 Bracket type Single bearing
Insulation Class H class Coupling system Flexible disc
Standard (Vacuum
Coating type impregnation)
• Self-excited and self-regulated
• IP23 protection
• H class insulation
2023-MAY.-25 16:02
Ctra. Murcia - San Javier, km. 23,6 | 30730 San Javier (Murcia) SPAIN | Tel.: +34 902 19 11 28 / +34 968 19 11 28
Fax: +34 968 19 12 17 | Export Fax +34 968 19 04 20 | E-mail:[email protected] | www.himoinsa.com
HRFW-75 T5
WEIGHT AND DIMENSIONS
High High
Standard Optional Capacity Capacity
Version version version version
Length (L) mm 2.810 2.810 2.810 2.810
Height (H) mm 1.782 1.782 1.928 2.201
Width (W) mm 1.150 1.150 1.150 1.150
Maximum shipping volume m³ 5,76 5,76 6,23 7,11
Weight with liquids in radiator Kg 1650 1670 1800 1930
and sump
Fuel tank capacity L 240 240 390 850
Autonomy (100% PRP) Hours 12 12 20 44
Plastic Steel tank Steel tank Steel tank
tank
SOUND PRESSURE
Sound pressure level dB(A)@7m 69 ± 2,4
APPLICATION DATA
EXHAUST SYSTEM NECESSARY AMOUNT OF AIR
Maximum exhaust temperature ºC 516 Intake air flow m³/h 273
Maximum allowed back pressure kPa 5 Cooling Air Flow m³/s 2,2
Exhaust Flange Size (external Alternator fan air flow m³/s 0,216
mm 90
diameter)
Heat dissipated by exhaust pipe KCal/Kwh 543
FUEL CONSUMPTION FUEL SYSTEM
Fuel Consumption ESP l/h 21,2 Fuel Oil Specifications Diesel
Fuel Consumption 100% PRP l/h 19,4 Fuel Tank L 240
Fuel Consumption 70 % PRP l/h 13,47 Other fuel tank capacities L 240, 390, 850
Fuel Consumption 50 % PRP l/h 9,6
STARTING SYSTEM
Starting power kW 3
Starting power CV 4,08
Recommended battery Ah 100
Auxiliary Voltage Vdc 12
Soundproofed version
2023-MAY.-25 16:02
Ctra. Murcia - San Javier, km. 23,6 | 30730 San Javier (Murcia) SPAIN | Tel.: +34 902 19 11 28 / +34 968 19 11 28
Fax: +34 968 19 12 17 | Export Fax +34 968 19 04 20 | E-mail:[email protected] | www.himoinsa.com
• Steel chassis • Chassis with integrated fuel tank • Oil sump extraction kit
• Manhole to fill the radiator • Fuel level gauge • Versatility to assemble a high capacity
chassis with a metallic fuel tank
• Pre-installation or niche to house the quick • Bodywork made from high quality steel
connection hydraulic fittings for fuel transfer plate • External filling of the fuel tank with safety
key
• Anti-leakage chassis, predisposed to retain • High mechanical strength
liquids (retention tray) • Emergency stop button (double emergency
• Low noise emissions level stop protection: Interior on the panel +
• Manhole for fuel tank cleaning and drainage Exterior on the bodywork)
• Soundproofing provided by high-density
• Manhole for chassis cleaning volcanic rock wool • Mechanized for power cable output
• Oversized chassis to protect the bodywork • Epoxy polyester powder coating • Door with window to visualize control panel,
• Slide carriage and brackets for • Full access for maintenance (water, oil and alarms and measurements
transportation with forklift filters, no need to remove the canopy) • Pressure locks
• Tilting cap in the exhaust • Reinforced lifting hooks for crane hoisting • IP Protection according to ISO
• Anti-vibration shock absorbers • Steel residential silencer -35db(A) 8528-13:2016
attenuation. • 3 way valve for external fuel supply (available in
1/2" and 3/8" fittings) (Opcional).
• Fuel transfer pump (Opcional).
HRFW-75 T5
FEATURES OF THE
CONTROL UNITS
CEM 7
Voltage between phases •
Voltage between neutral and phase •
Current intensities •
Generator Readings
Frequency •
Apparent power (Kva) •
Active power (Kw) •
Reactive power (kVAr) •
Power factor •
Voltage between phases
Voltage between phases and neutral
Current intensities
Frequency
Mains Readings
Apparent power
Active power
Reactive power
Power factor
Coolant temperature •
Oil pressure •
Engine Readings
Fuel level (%) •
Battery voltage •
R.P.M. •
Battery charge alternator voltage •
High water temperature •
High water temperature by sensor •
Low water temperature by sensor •
Low oil pressure •
Low oil pressure by sensor •
Low water level •
Unexpected shutdown •
Fuel storage •
Fuel storage by sensor •
Stop failure •
Battery voltage failure •
Engine Protections
Battery charge alternator failure •
Overspeed •
Underspeed •
Start failure •
Emergency stop •
• Standard Optional
2023-MAY.-25 16:02
Ctra. Murcia - San Javier, km. 23,6 | 30730 San Javier (Murcia) SPAIN | Tel.: +34 902 19 11 28 / +34 968 19 11 28
Fax: +34 968 19 12 17 | Export Fax +34 968 19 04 20 | E-mail:[email protected] | www.himoinsa.com
HRFW-75 T5
CEM 7
High frequency •
Low frequency •
High voltage •
Low voltage •
Alternator Protections
Short-circuit •
Asymmetry between phases •
Incorrect phase sequence •
Inverse power •
Overload •
Genset signal drop •
Total hour counter •
Partial hour counter •
Kilowatt meter •
Starts valid counters •
Counters
Starts failure counters •
Maintenance •
RS232 ⓪
RS485 ⓪
Modbus IP ⓪
Modbus ⓪
CCLAN ⓪
Software for PC ⓪
Analogue modem ⓪
Communications
GSM/GPRS modem ⓪
Remote screen ⓪
Tele signal ⓪ (8 + 4)
J1939 ⓪
(100)
Alarm history •
External start •
Start inhibition •
Mains failure start
Start under normative EJP •
Pre-heating engine control •
Genset contactor activation •
Mains & Genset contactor activation
Fuel transfer control •
Engine temperature control •
Manual override •
Programmable alarms •
Genset start function in test mode •
Features
Programmable outputs •
Multilingual •
GPS Positioning ⓪
Synchronisation
Special Functions
⓪
Mains synchronization ⓪
Second Zero elimination ⓪
RAM7 ⓪
Remote screen ⓪
• Standard Optional
2023-MAY.-25 16:02
Ctra. Murcia - San Javier, km. 23,6 | 30730 San Javier (Murcia) SPAIN | Tel.: +34 902 19 11 28 / +34 968 19 11 28
Fax: +34 968 19 12 17 | Export Fax +34 968 19 04 20 | E-mail:[email protected] | www.himoinsa.com
HRFW-75 T5
CONTROL
PANELS
M5
Digital manual Auto-Start control panel and thermal magnetic protection (depending on current and
voltage) and differential with CEM7.
Digital control unit CEM7
Electrical system
• M5 control panel with electronic • Adjustable earth leakage • Starter battery/ies installed
CEM7 control unit and switched protection (time & sensitivity) (cables and bracket included)
emergency stop standard in M5 and AS5, with
thermal magnetic protection • Ground connection electrical
• Power panel with built-in circuit installation with connection
breaker plates • 4-pole thermal magnetic circuit ready for ground spike (not
breaker supplied)
• Safety relay in output terminal
board (thermal magnetic trip • Battery charger alternator with • Battery Switch (Opcional).
and alarm in control unit) ground connection
2023-MAY.-25 16:02
Ctra. Murcia - San Javier, km. 23,6 | 30730 San Javier (Murcia) SPAIN | Tel.: +34 902 19 11 28 / +34 968 19 11 28
Fax: +34 968 19 12 17 | Export Fax +34 968 19 04 20 | E-mail:[email protected] | www.himoinsa.com