This document provides operating instructions for a safety-monitoring module (SRB 301MC). It describes the purpose of the document, intended users, symbols used, appropriate uses, safety instructions, warnings, and exclusions from liability. It also provides a product description, ordering code information, special versions, intended uses, and technical specifications for the module.

Uploaded by

Sudheer Rawat
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
100% found this document useful (1 vote)
585 views

SRB 301MC

This document provides operating instructions for a safety-monitoring module (SRB 301MC). It describes the purpose of the document, intended users, symbols used, appropriate uses, safety instructions, warnings, and exclusions from liability. It also provides a product description, ordering code information, special versions, intended uses, and technical specifications for the module.

Uploaded by

Sudheer Rawat
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 6

Operating instructions

Safety-monitoring module SRB 301MC

1 About this document

1.1 Function
This operating instructions manual provides all the information you need
for the mounting, set-up and commissioning to ensure the safe operation
and disassembly of the safety-monitoring module. The operating instruc-
tions must be available in a legible condition and a complete version in
EN Operating instructions...................... pages 1 to 6 the vicinity of the device.
Translation of the original operating instructions
1.2 Target group: authorised qualified personnel
All operations described in this operating instructions manual must
be carried out by trained specialist personnel, authorised by the plant
operator only.

Please make sure that you have read and understood these operating
FR Vous trouverez la version Encontrará el manual de instructions and that you know all applicable legislations regarding
ES
actuelle du mode d’emploi dans instrucciones actual en su occupational safety and accident prevention prior to installation and
votre langue nationale officielle idioma oficial de la UE en
sur l’Internet, www.schmersal. nuestra página de Internet putting the component into operation.
net. www.schmersal.net.

U vindt de huidige versie van Il manuale d‘istruzioni aggior-


The machine builder must carefully select the harmonised standards
NL IT
de gebruikshandleiding in uw nato nella vostra lingua (lingua to be complied with as well as other technical specifications for the
officiële landstaal op het Inter- ufficiale UE) è scaricabile in selection, mounting and integration of the components.
net, www.schmersal.net. Internet all‘indirizzo www.
schmersal.net.
1.3 Explanation of the symbols used
JP EU公用語で書かれた最新の
取扱説明書は、インターネッ
(www.schmersal.net)からダウ Information, hint, note:
ンロードできます。 This symbol is used for identifying useful additional information.

Caution: Failure to comply with this warning notice could


Content
lead to failures or malfunctions.
Warning: Failure to comply with this warning notice could
1 About this document
lead to physical injury and/or damage to the machine.
1.1 Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
1.2 Target group: authorised qualified personnel . . . . . . . . . . . . . . . . . 1
1.3 Explanation of the symbols used . . . . . . . . . . . . . . . . . . . . . . . . . . 1 1.4 Appropriate use
1.4 Appropriate use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 The products described in these operating instructions are developed to
1.5 General safety instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 execute safety-related functions as part of an entire plant or machine. It
1.6 Warning about misuse . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 is the responsibility of the manufacturer of a machine or plant to ensure
1.7 Exclusion of liability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 the proper functionality of the entire machinery or plant.

2 Product description The safety-monitoring module must be exclusively used in accordance


2.1 Ordering code . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 with the versions listed below or for the applications authorised by the
2.2 Special versions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 manufacturer. Detailed information regarding the range of applications
2.3 Destination and use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 can be found in the chapter "Product description".
2.4 Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
2.5 Safety classification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 1.5 General safety instructions
The user must observe the safety instructions in this operating instruc-
3 Mounting tions manual, the country-specific installation standards as well as all
3.1 General mounting instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 prevailing safety regulations and accident prevention rules.
3.2 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Further technical information can be found in the Elan
4 Electrical connection catalogues or in the online catalogue on the Internet:
4.1 General information for electrical connection . . . . . . . . . . . . . . . . . 3 www.schmersal.net.

5 Operating principle and settings The information contained in this operating instructions manual is
5.1 LED functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 provided without liability. Subject to technical modifications.
5.2 Terminal description (see Fig. 1) . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
5.3 Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 The entire concept of the control system, in which the
safety component is integrated, must be validated to
6 Set-up and maintenance EN ISO 13849-2.
6.1 Functional testing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
26.07.2010 / Index: 420/10 / Teile-Nr. 1190702-EN

6.2 Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 There are no residual risks, provided that the safety instructions as well
as the instructions regarding mounting, commissioning, operation and
7 Disassembly and disposal maintenance are observed.
7.1 Disassembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
7.2 Disposal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 1.6 Warning about misuse

8 Appendix In case of inadequate or improper use or manipulations of


8.1 Wiring examples . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 the safety-monitoring module, personal hazards or damage
8.2 Start configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 to machinery or plant components cannot be excluded.
8.3 Sensor configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 The relevant requirements of the standards EN 1088 and
8.4 Actuator configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 EN ISO 13850 must be observed.
8.5 EC Declaration of conformity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

EN 1

Downloaded from www.Manualslib.com manuals search engine


Operating instructions
Safety-monitoring module SRB 301MC

1.7 Exclusion of liability Pull-in delay for typ. 100 ms


We shall accept no liability for damages and malfunctions resulting from automatic start:
defective mounting or failure to comply with this operating instructions Pull-in delay with reset button: typ. 20 ms
manual. The manufacturer shall accept no liability for damages resulting Drop-out delay in case typ. 20 ms
from the use of unauthorised spare parts or accessories. of emergency stop:
Drop-out delay on typ. 80 ms
For safety reasons, invasive work on the device as well as arbitrary re- "supply failure":
pairs, conversions and modifications to the device are strictly forbidden; Bridging in case of typ. 80 ms
the manufacturer shall accept no liability for damages resulting from voltage drops:
such invasive work, arbitrary repairs, conversions and/or modifications Mechanical data
to the device. Connection type: Screw terminals
Cable section: min. 2 mm² / max. 2 mm²
The safety-monitoring module must only be used when the enclosure is Connecting cable: rigid or flexible
closed, i.e. with the front cover fitted. Tightening torque for 0.6 Nm
the terminals:
With removable terminals (Y/N): No
2 Product description Mechanical life: 10 million operations
Electrical life: Derating curve available on request
2.1 Ordering code Resistance to shock: 10 g / 11 ms
This operating instructions manual applies to the following types: Resistance to vibrations 10 ... 55 Hz, amplitude 0.35 mm
to EN 60068-2-6:
SRB 301MC Ambient conditions
Ambient temperature: –25°C … +60°C
Storage and transport –40°C … +85°C
Only if the information described in this operating instructions temperature:
manual are realised correctly, the safety function and therefore Protection class: Enclosure: IP 40,
the compliance with the Machinery Directive is maintained. Terminals: IP 20,
Wiring compartment: IP 54
Air clearances and creepage 4 kV/2 (basic insulation)
2.2 Special versions distances to IEC/EN 60664-1:
For special versions, which are not listed in the order code below 2.1, EMC rating: to EMC Directive
these specifications apply accordingly, provided that they correspond to Electrical data
the standard version. Contact resistance in new state: max. 100 mΩ
Power consumption: max. 2.0 W / 4.9 VA
2.3 Destination and use Rated operating voltage Ue1: 24 VDC –15%/+20%,
The safety-monitoring modules for integration in safety circuits are residual ripple max. 10%
designed for fitting in control cabinets. They are used for the safe 24 VAC –15% / +10%
evaluation of the signals of positive break position switches or magnetic Frequency range: 50 Hz / 60 Hz
safety sensors for safety functions on sliding, hinged and removable Max. fuse rating of the internal electronic fuse,
safety guards as well as emergency stop control devices and AOPD's. operating voltage: tripping current > 500 mA,
reset after approx. 1 sec.
The safety function is defined as the opening of the enabling circuits Monitored inputs
13-14, 23-24 and 33-34 when the inputs S11-S12 and/or S21-S22 are Cross-wire detection (Y/N): Yes
opened. Wire breakage detection (Y/N): Yes
The safety-relevant current paths with the outputs contacts 13-14, 23-24 Earth leakage detection (Y/N): Yes
and 33-34 meet the following requirements under observation of a PFH Number of NO contacts: 0
value assessment (also refer to chapter 2.5 "Safety classification"): Number of NC contacts: 2
– Control category 4 - PL e to DIN EN ISO 13849-1 Cable lengths: 1.500 m with 1,5 mm²
– SIL 3 to DIN EN 61508-2 2.500 m with 2,5 mm²
– SILCL 3 to DIN EN 62061 Conduction resistance: max. 40 Ω
(meets the requirements of control category 4 to DIN EN 954-1) Outputs
Number of safety contacts: 3
To determine the Performance Level (PL) of the entire safety function Number of auxiliary contacts: 1
(e.g. sensor, logic, actuator) to DIN EN ISO 13849-1, an analysis of all Number of signalling outputs: 0
relevant components is required. Switching capacity of the 13-14; 23-24;33-34:
safety contacts: max. 250 V, 8 A ohmic (inductive in
2.4 Technical data case of suitable protective wiring);
min. 10 V / 10 mA, residual current
General data at ambient temperature up to 45°C:
Standards: IEC/EN 60204-1, EN 60947-5-1; 24 A / 55°C: 18 A / 60°C: 12 A
EN ISO 13849-1, IEC 61508 Switching capacity of 41-42:
Climate resistance: EN 60068-2-78 the auxiliary contacts: 24 VDC / 2 A
Fixing: Snaps onto standard DIN rails to Fuse rating of the external (Ik = 1000 A) to EN 60947-5-1
DIN EN 60715 safety contacts: Safety fuse 10 A quick blow, 8 A slow
Terminal designations: EN 60947-1 blow
Material of the enclosure: glass-fibre reinforced thermoplastic, Recommended fuse for external (Ik = 1000 A) to EN 60947-5-1
ventilated the auxiliary contacts: Safety fuse 2,5 A quick blow, 2 A slow
Material of the contacts: AgSnO, self-cleaning, positive drive blow
Weight: 230 g Utilisation category AC-15 / DC-13: EN 60947-5-1
Start conditions Automatic or start button to EN 60947-5-1:
Feedback circuit (Y/N): Yes Dimensions (H/W/D): 100 mm x 22.5 mm x 121 mm
The data specified in this manual are applicable when the component
is operated with rated operating voltage Ue ±0%.

2 EN

Downloaded from www.Manualslib.com manuals search engine


Operating instructions
Safety-monitoring module SRB 301MC

2.5 Safety classification 5.2 Terminal description (see Fig. 1)

Standards: EN ISO 13849-1, IEC 61508, Voltages: A1 +24 VDC/24 VAC


EN 60947-5-1, DIN EN 574 A2 0 VDC/24 VAC
PL: up to e Inputs: S11-S12 Input channel 1 (+)
Control category: up to 4 S12-S22 Input channel 2 (+)
PFH-value: ≤ 2,00 x 10-8/h S21-S22 Input channel 2 (–) (with cross-wire
SIL: up to 3 short detection)
Service life: 20 years Outputs: 13-14 First safety enabling circuit
23-24 Second safety enabling circuit
The PFH value of 2.00 x 10-8/h applies to the combinations of contact 33-34 Third safety enabling circuit
load (current through enabling contacts) and number of switching Start: X1-X2 Feedback circuit and external reset
cycles (n-op/y) mentioned in the table below. 41-42 Auxiliary NC contact
At 365 operating days per year and a 24-hours operation, this results
in the below-mentioned switching cycle times (t-cycle) for the relay 5.3 Notes
contacts. Diverging applications upon request.
Signalling outputs must not be used in safety circuits.
Contact n-op/y t-cycle (s / min)
load:
20% 525,600 60 s / 1,0 min Due to the operating principle of the electronic fuse, the
40% 210,240 150 s / 2,5 min customer must check that no hazard is caused by an
60% 75,087 420 s / 7,0 min unexpected restart in circuits without reset button
80% 30,918 1020 s / 17 min (automatic reset).
100% 12,223 2580 s / 43 min

Opening the front cover (see Fig. 2)


• To open the front cover, insert a slot screwdriver in the top and bottom
3 Mounting cover notch and gently lift it.
• When the front cover is open, the electrostatic discharge requirements
3.1 General mounting instructions must be respected and observed.
Mounting: snaps onto standard DIN rails to EN 60715. • After the setting, the front cover must be fitted back in position.

Snap the bottom of the enclosure slightly tilted forwards in the DIN rail Only touch the components after electrical discharge!
and push up until it latches in position.

3.2 Dimensions
All measurements in mm. Setting the switch (see Fig. 3)
• The cross-wire short monitoring function (factory setting) is pro-
Device dimensions (H/W/D): 100 x 22.5 x 121 mm grammed by means of the switch underneath the front cover of the
safety-monitoring module.
• The switch must only be operated in de-energised condition by means
4 Electrical connection of a finger or an insulated blunt tool.
• Pos. nQS (top), not cross-wire short proof:
4.1 General information for electrical connection suitable for 1-channel applications and applications with outputs
connected to potential in the control circuits.
As far as the electrical safety is concerned, the protection • Pos. QS (bottom), cross-wire short proof:
against unintentional contact of the connected and therefore suitable for 2-channel applications without outputs connected to
electrically interconnected apparatus and the insulation of the potential in the control circuits.
feed cables must be designed for the highest voltage, which
can occur in the device.

The electrical connection may only be carried out by


authorised personnel in de-energised condition.

Wiring examples: see appendix


S11 13 23 33 S11 13 23 33 S12 18 28 38
S12 14 24 34 S12 14 24 34
5 Operating principle and settings
UB UB
Ui SRB Ui SRB
5.1 LED functions K1 301
K1 301 nQS
QS
• K1: Status channel 1 K2 K2
• K2: Status channel 2
• UB: Status operating voltage (LED is on, when the operating S22 41 X1 A1 S22 41 X1 A1 S22 45 X1 A1
voltage on the terminals A1-A2 is ON) S21 42 X2 A2 S21 42 X2 A2
• Ui: Status internal operating voltage (LED is on, when the
operating voltage on the terminals A1-A2 is ON and the fuse
has not been triggered)

Fig. 1 Fig. 2 Fig. 3

EN 3

Downloaded from www.Manualslib.com manuals search engine


Operating instructions
Safety-monitoring module SRB 301MC

6 Set-up and maintenance 8.2 Start configuration

6.1 Functional testing External reset button (non-monitored start) (see Fig. 5)
The safety function of the safety-monitoring module must be tested. • The external reset button is integrated in the feedback circuit in series.
The following conditions must be previously checked and met: • The safety-monitoring module is activated upon actuation of the reset
1. Correct fixing button.
2. Check the integrity of the cable entry and connections
3. Check the safety-monitoring module's enclosure for damage. Automatic start (see Fig. 6)
4. Check the electrical function of the connected sensors and • The automatic start is programmed by connecting the feedback circuit
their influence on the safety-monitoring module and the to the terminals X1/X2. If the feedback circuit is not required, establish
downstream actuators a bridge.
• Caution: Not admitted without additional measure due to the risk
6.2 Maintenance of gaining access by stepping behind!
A regular visual inspection and functional test, including the following • When the SRB 301MC safety-monitoring module is used with the
steps, is recommended: operating mode "Automatic start", an automatic restart after a
1. Check the correct fixing of the safety-monitoring module shutdown in case of emergency must be prevented by the upstream
2. Check the cable for damages control to EN 60204-1 paragraph 9.2.5.4.2.
3. Check electrical function
Due to the operating principle of the electronic fuse, the
The device has to be integrated into the periodic check-ups customer must check that no hazard is caused by an
according to the Ordinance on Industrial Safety and Health, unexpected restart in circuits without reset button
however at least 1x/year. (automatic reset).

X1 X1
Damaged or defective components must be replaced.
J
KA KA
7 Disassembly and disposal
KB KB
7.1 Disassembly
The safety-monitoring module must be disassembled in a
X2 X2
de-energised condition only. Fig. 5 Fig. 6
Push up the bottom of the enclosure and hang out slightly tilted
forwards.
8.3 Sensor configuration
7.2 Disposal
The safety-monitoring module must be disposed of in an appropriate Single-channel emergency stop circuit with command devices to
manner in accordance with the national prescriptions and legislations. DIN EN ISO 13850 (EN 418) and EN 60947-5-5 (Fig. 7)
• Wire breakage and earth leakage in the control circuits are detected.
• Control category 1 – PL c to DIN EN ISO 13849-1 possible
8 Appendix
Dual-channel emergency stop circuit with command devices to
8.1 Wiring examples DIN EN ISO 13850 (EN 418) and EN 60947-5-5 (Fig. 8)
• Wire breakage and earth leakage in the control circuits are detected.
Dual-channel control, shown for a guard door monitor with two • Cross-wire shorts between the control circuits are not detected.
position switches where one has a positive break contact; with • Control category 4 – PL e to DIN EN 13849-1 possible
external reset button J (Fig. 4) (with protective wiring).
• Relay outputs: Suitable for 2-channel control, for increase in capacity
or number of contacts by means of contactors or relays with positive- Dual-channel emergency stop circuit with command devices to
guided contacts. DIN EN ISO 13850 (EN 418) and EN 60947-5-5 (Fig. 9)
• The control system recognises wire-breakage, earth faults and cross- • Wire breakage and earth leakage in the control circuits are detected.
wire shorts in the monitoring circuit. • Cross-wire shorts between the control circuits are detected.
• S = Feedback circuit • Control category 4 – PL e to DIN EN ISO 13849-1 possible

L1 S11 S12 S11 S21 S11 S21


KB S
J
KA nQS nQS nQS
QS QS QS
A1 S12 S11 S21 S22 X1 X2 13 23 33 41
F1
a) nQS S12 S22 S12 S22 S12 S22
QS
K1 KA Fig. 7 Fig. 8 Fig. 9
UB Ui K2 KA
K1 K2
A2 14 24 34 42
KA KB
N

Fig. 4
a) Logic

4 EN

Downloaded from www.Manualslib.com manuals search engine


Operating instructions
Safety-monitoring module SRB 301MC

Single-channel guard door monitoring circuit with interlocking For example, the following safety sensors meet the
devices to EN 1088 (Fig. 10) requirements:
• At least one contact with positive break required – BNS33-02z-2187, BNS33-02zG-2187
• Wire breakage and earth leakage in the control circuits are detected. – BNS260-02z, BNS260-02zG
• Control category 1 – PL c to DIN EN ISO 13849-1 possible – BNS260-02-01z, BNS260-02-01zG

Dual-channel guard door monitoring circuit with interlocking


When sensors with LED are wired in the control circuit
device to EN 1088 (Fig. 11)
(protective circuit), the following rated operating voltage
• At least one contact with positive break required
must be observed and respected:
• Wire breakage and earth leakage in the control circuits are detected.
–  24 VDC with a max. tolerance of –5 %/+20 %
• Cross-wire shorts between the monitoring circuits are not detected.
–  24 VAC with a max. tolerance of –5 %/+10 %
• Control category 4 – PL e to DIN EN 13849-1 possible
(with protective wiring).
Otherwise availability problems could occur, especially in
series-wired sensors, where a voltage drop in the control
Dual-channel guard door monitoring circuit with interlocking
circuit is triggered by LED's for instance.
device to EN 1088 (Fig. 12)
• At least one contact with positive break required
• Wire breakage and earth leakage in the control circuits are detected. +24V +24V S11 S21 S11 S21
• Cross-wire shorts between the monitoring circuits are detected.
• Control category 4 – PL e to DIN EN ISO 13849-1 possible
nQS nQS nQS
QS QS QS
S11 S12 S11 S21 S11 S21

nQS nQS nQS S12 S22 S12 S22 S12 S22


QS QS QS
Fig. 13 Fig. 14 Fig. 15

S12 S22 S12 S22 S12 S22 8.4 Actuator configuration


Fig. 10 Fig. 11 Fig. 12
Single-channel control (see Fig. 16)
• Suitable for increase in capacity or number of contacts by means of
Dual-channel control of a safety-related electronic contactors or relays with positive-guided contacts.
(microprocessor-based) safety guard with p-type transistor • If the feedback circuit
outputs e.g. AOPD's to EN IEC 61496 (see Fig. 13) is not required, establish a bridge.
• Wire breakage and earth leakage in the control circuits are detected. • S = Feedback circuit
• Cross-wire shorts between the control circuits are usually detected
by the safety guards. The safety-monitoring module therefore is not Dual-channel control with feedback circuit (Fig. 17)
equipped with a cross-wire short detection here. • Suitable for increase in capacity or number of contacts by means of
• Control category 3 – PL e to DIN EN ISO 13849-1 possible contactors or relays with positive-guided contacts.
• If cross-wire shorts in the control circuits are detected by the safety • If the feedback circuit is not required, establish a bridge.
guard: control category 4 – PL e to DIN EN ISO 13 849-1 possible. • S = Feedback circuit

2-channel control of magnetic safety switches according to L1 L1


EN 60947-5-3 (see Fig. 14)
• The control system recognises wire breakage and earth faults in the S KA S KA KB
control circuit.
• Cross-wire shorts between the control circuits are not detected.
X1 X2 13 X1 X2 13
• Control category 3 – PL e to DIN EN ISO 13849-1 possible KA
KB
KA
2-channel control of magnetic safety switches according to 14 14
EN 60947-5-3 (see Fig. 15)
• The control system recognises wire breakage and earth faults in the KA KA KB

control circuit. N N
• Cross-wire shorts between the control circuits are detected. Fig. 16 Fig. 17
• Control category 4 – PL e to DIN EN ISO 13849-1 possible

The connection of magnetic safety switches to the SRB 301


MC safety-monitoring module is only admitted when the
requirements of the standard EN 60 947-5-3 are observed.

As the technical data are regarded, the following minimum


requirements must be met:
– switching capacity: min. 240 mW
– switching voltage: min. 24 VDC
– switching current: min. 10 mA

EN 5

Downloaded from www.Manualslib.com manuals search engine


Operating instructions
Safety-monitoring module SRB 301MC

Appendix

8.5 EC Declaration of conformity

EC Declaration of conformity

Translation of the original declaration of conformity Elan Schaltelemente GmbH & Co. KG
valid as of December 29, 2009 Im Ostpark 2 · 35435 Wettenberg
Germany
Internet: www.elan.de

We hereby certify that the hereafter described safety components both in its basic design and
construction conforms to the applicable European Directives.

Name of the safety component: SRB 301MC

Description of the safety component: Safety-monitoring module for emergency


stop circuits, guard door monitoring,
magnetic safety switches and AOPD's

Harmonised EC-Directives: 2006/42/EC EC-Machinery Directive


2004/108/EC EMC-Directive

Person authorized for the compilation Ulrich Loss


of the technical documentation: Möddinghofe 30
42279 Wuppertal

Notified body, which approved the full TÜV Rheinland Industrie Service GmbH
quality assurance system, referred to Alboinstraße 56
in Appendix X, 2006/42/EC: 12103 Berlin
ID n°: 0035

Place and date of issue: Wuppertal, October 6, 2009


SRB301MC-B-EN

Authorised signature
Heinz Schmersal
Managing Director

Note
The currently valid declaration of conformity can be
downloaded from the internet at www.schmersal.net.

Elan Schaltelemente GmbH & Co. KG


Im Ostpark 2, D - 35435 Wettenberg
Postfach 1109, D - 35429 Wettenberg

Telefon: +49 (0)641 9848-0


Telefax: +49 (0)641 9848-420
E-Mail: [email protected]
Internet: www.elan.de