Commercial Electrical

This document provides a schedule of loads for the main distribution panel and commercial space panelboard. It lists 4 load items connected to the main distribution panel including an office distribution panel, admin panel board, commercial space panelboard, and elevator. For each load, it specifies the number of outlets, switches, amperage, circuit breaker size, size of wiring, and conduit size. The commercial space panelboard then lists 5 additional load items with similar specifications.

Uploaded by

Naga Alab
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
100% found this document useful (1 vote)
85 views1 page

Commercial Electrical

This document provides a schedule of loads for the main distribution panel and commercial space panelboard. It lists 4 load items connected to the main distribution panel including an office distribution panel, admin panel board, commercial space panelboard, and elevator. For each load, it specifies the number of outlets, switches, amperage, circuit breaker size, size of wiring, and conduit size. The commercial space panelboard then lists 5 additional load items with similar specifications.

Uploaded by

Naga Alab
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

SCHEDULE OF LOADS

MAIN DISTRIBUTION PANEL (MDP) COMMERCIAL SPACE PANELBOARD (CPB)


N NO OF OUTLET SWITCHES AMPERE CB
NO OF OUTLET SWITCHES AMPERE CB DESCRIPTION VA V POLE CB SIZE OF WIRE CONDUIT SIZE
NO DESCRIPTION VA V POLE CB SIZE OF WIRE CONDUIT SIZE O LO CO SPO S1 S2 S3 3WS 3Ø 1Ø TYPE
LO CO SPO 3Ø 1Ø TYPE AB CA BC
S1 S2 S3 3WS AB CA BC
2 SETS OF 3- 50mm2 THHN CU + 2-22mm2 1 AIR CONDITIONING UNIT 1 4,150 230 18.04 18.04 2P 30A 5.5mm2 THHN CU + 3.5mm2 Grounding Wire 20mm dia., PVC
81 70 34 - - - - 101,610 230 132.48 140.26 169.04 - 3P 2- 40mm dia., PVC MCCB
1 OFFICE DISTRIBUTION PANEL (ODP) 300A MCCB Grounding Wire
2 AIR CONDITIONING UNIT 1 4,150 230 18.04 18.04 2P 30A 5.5mm2 THHN CU + 3.5mm2 Grounding Wire 20mm dia., PVC
89 34 29 - - - - 31,540 230 43.13 44.30 49.70 - 3P 30mm2 THHN CU + 8.0mm2 Grounding Wire 40mm dia., PVC MCCB
2 ADMIN PANEL BOARD (APB) 100A MCCB
3 AIR CURTAIN 1 1,200 230 5.22 5.22 2P 20A 3.5mm2 THHN CU + 2.0mm2 Grounding Wire 20mm dia., PVC
MCCB
22 4 7 - - - - 20,910 230 52.09 23.48 15.35 - 3P 30mm2 THHN CU + 8.0mm2 Grounding Wire 40mm dia., PVC
3 COMMERCIAL SPACE PANELBOARD (CPB) 125A MCCB
4 FLOOR CONVENIENCE OUTLET 1 1,800 230 7.83 7.83 2P 20A 3.5mm2 THHN CU + 2.0mm2 Grounding Wire 20mm dia., PVC
MCCB
14mm2 THHN CU + 8.0mm2 Grounding Wire
4 ELEVATOR 7,500 230 18.85 18.85 18.85 3P 50A MCCB 25mm dia., PVC
5 CONVENIENCE OUTLET 4 1,440 230 6.26 6.26 2P 20A 3.5mm2 THHN CU + 2.0mm2 Grounding Wire 20mm dia., PVC
MCCB
8.0mm2 THHN CU + 8.0mm2 Grounding Wire
5 AUXILLIARY 7,000 230 30.43 2P 40A MCCB 25mm dia., PVC 6 LIGHTING OUTLET 10 500 230 2.17 2.17 2P 20A 3.5mm2 THHN CU + 2.0mm2 Grounding Wire 20mm dia., PVC
MCCB

2 SETS OF 3-100mm2 THHN CU + 2 SETS 30mm2 7 REFFRIGERATOR 1 1,840 230 8.00 8.00 2P 20A 3.5mm2 THHN CU + 2.0mm2 Grounding Wire 20mm dia., PVC
TOTAL 192 108 70 - - - - 168,560 230 246.54 257.33 252.94 3P 500A 2- 65 mm dia., RMC MCCB
MCCB Grounding Wire
8 REFFRIGERATOR 1 1,840 230 8.00 8.00 2P 20A 3.5mm2 THHN CU + 2.0mm2 Grounding Wire 20mm dia., PVC
MCCB
TOTAL LOAD FEEDER CONDUCTOR: MAIN PANEL PROTECTION DEVICE: TRANSFORMER SIZE
COMPUTATION: USE = 2 SETS OF 3-100mm² THHN WIRE USE = 500AT, 700AF THREE PHASE, 3 POLE, 230 VOLTS IL = (417.78 A ) x 230 V x 1.73 x 0.8 d.f. ) 9 LIGHTING OUTLET 12 600 230 2.61 2.61 2P 15A 2.0mm2 THHN CU + 2.0mm2 Grounding Wire 15mm dia., PVC
IL = 164,360 KVA + (25% x 7500 KVA)
IN 2 SETS OF 65mmØ RMC BOLT ON TYPE, MCCB, with GROUNDING TERMINAL IL = 132.99 kVA MCCB
230 x 1.73
IL = 417.78 AMPERES 2-30mm² GROUNDING WIRE
10 FLOOR CONVENIENCE OUTLET 1 1,800 230 7.83 7.83 2P 20A 3.5mm2 THHN CU + 2.0mm2 Grounding Wire 20mm dia., PVC
USE 3-167kVA OISC TRANSFORMER MCCB
APPLY SAFETY FACTOR 13,200/240 V, 60HZ
I = 417.78 A x 1.25 11 CONVENIENCE OUTLET 4 1,440 230 6.26 6.26 2P 20A 3.5mm2 THHN CU + 2.0mm2 Grounding Wire 20mm dia., PVC
IL = 522.23 AMPERES MCCB

12 EMERGENCY LIGHTS 3 150 230 0.65 0.65 2P 20A 3.5mm2 THHN CU + 2.0mm2 Grounding Wire 20mm dia., PVC
MCCB
OFFICE DISTRIBUTION PANEL (ODP) TOTAL 22 4 7 - - - - 20,910 230 52.09 23.48 15.35 - 3P 30mm2 THHN CU + 8.0mm2 Grounding Wire 40mm dia., PVC
125A MCCB
NO OF OUTLET SWITCHES AMPERE CB
NO DESCRIPTION VA V POLE CB SIZE OF WIRE CONDUIT SIZE TOTAL LOAD FEEDER CONDUCTOR: MAIN PANEL PROTECTION DEVICE:
LO CO SPO S1 S2 S3 3WS 3Ø 1Ø TYPE COMPUTATION: APPLY SAFETY FACTOR
AB CA BC USE = 3-30mm² THHN WIRE USE = 125AT, 225AF, 3 POLE, 230 VOLTS
IL = 31,860 KVA + (25% x 2760 KVA) I = 81.80 A x 1.25
IN 40mmØ PVC BOLT ON TYPE, MCCB, with GROUNDING TERMINAL
1 TYPICAL OFFICE PANELBOARD (O1-PB, O2-PB) 10 8 4 - - - - 11,420 230 15.74 9.91 24.00 - 3P 40A 8.0mm2 THHN CU + 8.0mm2 Grounding Wire 20mm dia., PVC 230 x 1.73 IL = 102.26 AMPERES
MCCB IL = 81.80 AMPERES 8.0mm² GROUNDING WIRE

2 OFFICE 2 PANELBOARD (O2-PB) 10 8 4 - - - - 11,420 230 15.74 9.91 24.00 - 3P 40A 8.0mm2 THHN CU + 8.0mm2 Grounding Wire 25mm dia., PVC
MCCB

3 OFFICE 3 PANELBOARD (O3-PB) 8 8 3 - - - - 11,140 230 16.43 16.87 15.13 - 3P 40A 8.0mm2 THHN CU + 8.0mm2 Grounding Wire 20mm dia., PVC
MCCB RESIDENTIAL UNIT 1 PB (U1-PB)
4 OFFICE 4 PANELBOARD (O4-PB) 10 7 4 - - - - 11,240 230 15.91 15.74 17.22 - 3P 40A 8.0mm2 THHN CU + 8.0mm2 Grounding Wire 20mm dia., PVC NO OF OUTLET SWITCHES AMPERE
MCCB N CB
DESCRIPTION VA V POLE CB SIZE OF WIRE CONDUIT SIZE
O LO CO SPO S1 S2 S3 3WS 3Ø 1Ø TYPE
OFFICE 5 PANELBOARD (O5-PB) 11,240 8.0mm2 THHN CU + 8.0mm2 Grounding Wire 20mm dia., PVC AB CA BC
5 10 7 4 - - - - 230 11.30 22.43 15.13 - 3P 40A
MCCB
1 SPARE 1 1,200 230 5.22 2P 20A 3.5mm2 THHN CU + 2.0mm2 Grounding Wire 20mm dia., PVC
6 OFFICE 6 PANELBOARD (O6-PB) 6 8 3 - - - - 11,040 230 10.43 13.57 24.00 - 3P 40A 8.0mm2 THHN CU + 8.0mm2 Grounding Wire 20mm dia., PVC MCCB
MCCB
TYPICAL OFFICE PANELBOARD, OFFICE 7 & 8 2 CONVENIENCE OUTLET 9 1,620 230 7.04 2P 20A 3.5mm2 THHN CU + 2.0mm2 Grounding Wire 20mm dia., PVC
7 10 8 4 - - - - 11,420 230 16.70 15.74 17.22 - 3P 40A 8.0mm2 THHN CU + 8.0mm2 Grounding Wire 20mm dia., PVC MCCB
(O7-PB, O8-PB) MCCB
3 AIR CONDITIONING UNIT 1 2,760 230 12.00 2P 30A 5.5mm2 THHN CU + 3.5mm2 Grounding Wire 20mm dia., PVC
OFFICE 8 PANELBOARD (O8-PB) 11,420 8.0mm2 THHN CU + 8.0mm2 Grounding Wire 20mm dia., PVC MCCB
8 10 8 4 - - - - 230 16.70 15.74 17.22 - 3P 40A
MCCB
4 SPARE 1 1,200 230 5.22 2P 20A 3.5mm2 THHN CU + 2.0mm2 Grounding Wire 20mm dia., PVC
9 OFFICE 9 PANELBOARD (O9-PB) 7 8 4 - - - - 11,270 230 13.52 20.35 15.13 - 3P 40A 8.0mm2 THHN CU + 8.0mm2 Grounding Wire 20mm dia., PVC MCCB
MCCB
2 SETS OF 3- 50mm2 THHN CU + 2-22mm2 Grounding 5 SPARE 1 1,200 230 5.22 2P 20A 3.5mm2 THHN CU + 2.0mm2 Grounding Wire 20mm dia., PVC
TOTAL 81 70 34 - - - - 101,610 230 132.48 140.26 169.04 - 3P 2- 40mm dia., PVC MCCB
300A MCCB Wire
6 LIGHTING OUTLET 10 500 230 2.17 2P 15A 2.0mm2 THHN CU + 2.0mm2 Grounding Wire 15mm dia., PVC
TOTAL LOAD FEEDER CONDUCTOR: MAIN PANEL PROTECTION DEVICE: MCCB
COMPUTATION: APPLY SAFETY FACTOR USE = 2 SETS OF3-50mm² THHN WIRE USE = 300AT, 400AF THREE PHASE, 3 POLE, 230 VOLTS
IL = 101,050 KVA + (25% x 2760 KVA) I = 255.69 A x 1.25
IN 2 SETS OF 40mmØ PVC BOLT ON TYPE, MCCB, with GROUNDING TERMINAL TOTAL 10 9 4 - - - - 8,480 230 - - - - 36.87 2P 50A 14mm2 THHN CU + 8.0mm2 Grounding Wire 25mm dia., PVC
230 x 1.73 IL = 319.62 AMPERES MCCB
IL = 255.69 AMPERES 2-22mm² GROUNDING WIRE
TOTAL LOAD FEEDER CONDUCTOR: MAIN PANEL PROTECTION DEVICE:
COMPUTATION: APPLY SAFETY FACTOR USE = 8.0mm² THHN WIRE USE = 50AT, 50AF, 3 POLE, 230 VOLTS
IL = 8,480 KVA + (25% x 2760 KVA) I = 39.87 A x 1.25
IN 20mmØ PVC BOLT ON TYPE, MCCB, with GROUNDING TERMINAL
230 IL = 49.84 AMPERES
IL = 39.87 AMPERES 8.0mm² GROUNDING WIRE

ADMIN PANEL BOARD (APB)


TYPICAL RESIDENTIAL UNIT PB (U2-PB, U3-PB)
N NO OF OUTLET SWITCHES AMPERE CB
DESCRIPTION VA V POLE CB SIZE OF WIRE CONDUIT SIZE NO OF OUTLET SWITCHES AMPERE
O LO CO SPO S1 S2 S3 3WS 3Ø 1Ø TYPE N CB
AB CA BC DESCRIPTION VA V POLE CB SIZE OF WIRE CONDUIT SIZE
O LO CO SPO S1 S2 S3 3WS 3Ø 1Ø TYPE
AB CA BC
1 LIGHTING OUTLET, GF 8 400 230 1.74 1.74 2P 15A 2.0mm2 THHN CU + 2.0mm2 Grounding Wire 15mm dia., PVC
MCCB
1 LIGHTING OUTLET 10 500 230 2.17 2P 15A 2.0mm2 THHN CU + 2.0mm2 Grounding Wire 15mm dia., PVC
MCCB
2 LIGHTING OUTLET, GF 10 500 230 2.17 2.17 2P 15A 2.0mm2 THHN CU + 2.0mm2 Grounding Wire 15mm dia., PVC
MCCB
2 CONVENIENCE OUTLET 11 1,980 230 8.61 2P 20A 3.5mm2 THHN CU + 2.0mm2 Grounding Wire 20mm dia., PVC
MCCB
3 LIGHTING OUTLET, 2ND 9 450 230 1.96 1.96 2P 15A 2.0mm2 THHN CU + 2.0mm2 Grounding Wire 15mm dia., PVC
MCCB
3 AIR CONDITIONING UNIT 1 2,760 230 12.00 2P 30A 5.5mm2 THHN CU + 3.5mm2 Grounding Wire 20mm dia., PVC
MCCB
4 LIGHTING OUTLET, 3RD 9 450 230 1.96 1.96 2P 15A 2.0mm2 THHN CU + 2.0mm2 Grounding Wire 15mm dia., PVC
MCCB
4 SPARE 1 1,200 230 5.22 2P 20A 3.5mm2 THHN CU + 2.0mm2 Grounding Wire 20mm dia., PVC
MCCB
5 LIGHTING OUTLET, 4TH 9 450 230 1.96 1.96 2P 15A 2.0mm2 THHN CU + 2.0mm2 Grounding Wire 15mm dia., PVC
MCCB
5 SPARE 1 1,200 230 5.22 2P 20A 3.5mm2 THHN CU + 2.0mm2 Grounding Wire 20mm dia., PVC
MCCB
6 LIGHTING OUTLET, 5TH 14 700 230 3.04 3.04 2P 15A 2.0mm2 THHN CU + 2.0mm2 Grounding Wire 15mm dia., PVC
MCCB
6 SPARE 1 1,200 230 5.22 2P 20A 3.5mm2 THHN CU + 2.0mm2 Grounding Wire 20mm dia., PVC
MCCB
7 CONVENIENCE OUTLET 3 540 230 2.35 2.35 2P 20A 3.5mm2 THHN CU + 2.0mm2 Grounding Wire 20mm dia., PVC
MCCB
TOTAL 10 11 4 - - - - 8,840 230 - - - - 38.43 2P 50A 14mm2 THHN CU + 8.0mm2 Grounding Wire 25mm dia., PVC
MCCB
8 RESIDENTIAL UNIT 1 PB (U1-PB) 10 9 4 - - - - 8,480 230 36.87 36.87 2P 50A 14mm2 THHN CU + 8.0mm2 Grounding Wire 25mm dia., PVC
MCCB TOTAL LOAD FEEDER CONDUCTOR: MAIN PANEL PROTECTION DEVICE:
COMPUTATION: APPLY SAFETY FACTOR USE = 14mm² THHN WIRE USE = 50AT, 50AF, 3 POLE, 230 VOLTS
9 TYPICAL RESIDENTIAL UNIT PB (U2-PB, U3-PB) 10 11 4 - - - - 8,840 230 38.43 38.43 2P 50A 14mm2 THHN CU + 8.0mm2 Grounding Wire 25mm dia., PVC IL = 8,840 KVA + (25% x 2760 KVA) I = 41.43 A x 1.25
MCCB IN 20mmØ PVC BOLT ON TYPE, MCCB, with GROUNDING TERMINAL
230 IL = 51.79 AMPERES
IL = 41.43 AMPERES 8.0mm² GROUNDING WIRE *TYPICAL TO U2-PB, U3-PB
10 EMERGENCY LIGHTS 9 450 230 1.96 1.96 2P 20A 3.5mm2 THHN CU + 2.0mm2 Grounding Wire 20mm dia., PVC
MCCB

11 CONVENIENCE OUTLET (POP-UP) 8 1,440 230 6.26 6.26 2P 20A 3.5mm2 THHN CU + 2.0mm2 Grounding Wire 20mm dia., PVC
MCCB

12 RESIDENTIAL UNIT 3 PB (U3-PB) 10 11 4 - - - - 8,840 230 38.43 38.43 2P 50A 14mm2 THHN CU + 8.0mm2 Grounding Wire 25mm dia., PVC
MCCB

TOTAL 89 34 29 - - - - 31,540 230 43.13 44.30 49.70 3P 30mm2 THHN CU + 8.0mm2 Grounding Wire 40mm dia., PVC
100A MCCB

TOTAL LOAD FEEDER CONDUCTOR: MAIN PANEL PROTECTION DEVICE:


COMPUTATION: APPLY SAFETY FACTOR USE = 3-30mm² THHN WIRE USE = 100AT, 200AF THREE PHASE, 3 POLE, 230 VOLTS
IL = 31,860 KVA + (25% x 2760 KVA) I = 81.80 A x 1.25
IN 40mmØ PVC BOLT ON TYPE, MCCB, with GROUNDING TERMINAL
230 x 1.73 IL = 102.26 AMPERES
IL = 81.80 AMPERES 8.0mm² GROUNDING WIRE

PROJECT TITLE : REVISION DATE R.A. 545 APPROVED : SHEET CONTENTS : SHEET NO. :

SCHEMES, DRAWINGS, & PLANS ARE


PROPERTIES OF THE DESIGNER.
UNAUTHORIZED COPYING, PUBLIC
PRESENTATION, EXCERPT AND
DOCUMENTATION OF THESE DOCUMENTS
E-4
DATE :
ARE PROHIBITED. VIOLATIONS ARE
PUNISHABLE BY LAW.
OWNER
04 07
PROFESSIONAL ELECTRICAL ENGINEER CHECKED :