Ele 291 Lab Report Exp7
Ele 291 Lab Report Exp7
OPEN-CIRCUIT TEST
100
Definition:
An open circuit is a circuit that does not allow current to flow. Only a "closed circuit" allows
current to flow in a circuit. An open circuit occurs when there is a break in the circuit
somewhere, and current cannot flow.
The two terminals of an open circuit are disconnected. As a result, the circuit's continuity is
disrupted. While no current can pass across the circuit, there is a voltage drop between the
two sites.
Procedure:
1. Connect the components as shown in the circuit diagram.
2. Turn on the power and adjust the autotransformer to apply the rated voltage of the
secondary winding.
3. For the no-load state, write down the readings on the ammeter, voltmeter, and
wattmeter.
4. Turn on the load and gradually increase the secondary current to the specified value.
5. For each phase of the process, record the ammeter, voltmeter, and wattmeter values.
6. Reduce the load before turning the power off.
7. To discover efficiency and regulation, tabulate the readings and do the relevant
calculations using the formula.
Result:
Table 7.1 Data Collected From Open Circuit Test
𝑽𝒐𝒄 (V) 𝑽𝟐 (V) 𝑰𝟏 (A) 𝑷𝒐𝒄 (W)
100 210 0.4 16
Question/Discussion:
1. What is the value of core/iron loss obtained?
- the core losses depend on the transformer rated voltage, and the copper losses
depend on the currents through the transformer primary and secondary windings
𝑷𝒄𝒐𝒓𝒆 =𝑷𝒐𝒄
= 16w
3. Draw the equivalent circuit for this case and sketch the pasor diagram for
I 1 , I C ∧I M
Conclusion
The value of full rated current is bigger compare to no load .The copper loss occurs only on
the primary winding of the transformer because the secondary winding is open. The reading
of the wattmeter only represents the core and iron losses. The core loss of the transformer is
the same for all types of loads.
SHORT CIRCUIT TEST
-A short-circuit test for determination of transformer impedance and losses is carried out with relatively low
power and applied to the transformer and with winding currents of the same magnitude as in operation. Its also
to determine the value of Req (equivalent resistance) and Xeq (equivalent reactance) and always conducted at
the rated winding current. It also can be determined by short circuiting the output line at the secondary side of
transformer
2. PROCEDURE
SHORT-CIRCUIT TEST
Psc
Note: The maximum range: Vsc (15 V), I2 (5 A), I1 (10 A) and Psc (25 A,50 V).
2. Make sure the connection is inspected by the lecturer/instructor before switching on the power.
3. Raise the supply voltage (VSC) gradually until the current I1 is at 50% of the rated current that is 4.58 A.
4. Then increase I1 in steps until it reaches 100% of its rated value. Record all the reading in Table 7.2.
3. RESULTS
Table 7.2 Data Collected from Short Circuit Test
Psc(W) 23 31 46 54 64 78
4.QUESTION/DISCUSSION
1. Determine the equivalent winding resistance and leakage reactance (reffered to the low-voltage terminal).
Perform the calculation at rated current.
= cos−1
= 62.59˚
𝑍𝑒𝑞 = 𝐼 𝑠𝑐∠𝑉𝑠𝑐−𝜃𝑠𝑐
= (0.97+1.88 j) Ω
1.88 Ω
V 2 240
A= =2.18
V 1 110
A=2.18
i2
A=
i1
i2
2.18=
3
i 2=6.55 A