This document provides information about DX3 MCB 25kA circuit breakers including their description and use, range of options, dimensions, preparation and connection details, general characteristics, conformities and approvals, characteristic curves, and auxiliaries and accessories.

Uploaded by

Fahru Zaini
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
33 views

1

This document provides information about DX3 MCB 25kA circuit breakers including their description and use, range of options, dimensions, preparation and connection details, general characteristics, conformities and approvals, characteristic curves, and auxiliaries and accessories.

Uploaded by

Fahru Zaini
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 38

87045 LIMOGES Cedex

Telephone: +33 5 55 06 87 87 – FAX: +33 5 55 06 88 88

DX3 MCB 25kA up to 63A Cat N°(s): 4 097 20 to 4 098 95

(1,5 modules per po


pole)

CONTENTS PAGES

1. Description - use................................. 1
2. Range................................................. 1
3. Overall dimensions ............................. 1
4. Preparation - Connection .................... 1
5. General characteristics ....................... 2
6. Conformities and approvals .............. 20
7. Characteristic curves ........................ 21
8. Auxiliaries and accessories............... 38

1. DESCRIPTION - USE 3. OVERALL


OVERALL DIMENSIONS
Thermo-magnetic circuit breaker with positive contact indication for
control, protection and isolation of electrical circuits.

Symbol:

Technology:
. Current limiting device.
. 1,5 module (26,7 mm) per pole.
. Trip free mechanism.

2. RANGE

Number of Poles:
. 1P / 2P / 3P / 4P.

Rated current In:


. 32 / 40 / 50 / 63 B and C curves.
. 16 / 20 / 25 / 32 / 40 / 50 / 63 D curve.
. 12,5 / 16 / 25 / 40 / 63 MA curve. N° of poles “X” (mm)

Tripping characteristics and magnetic tripping calibrations: 1P 26,7 mm


mm
calibrations:
. B curve (between 3 and 5 In). 2P 53,4 mm
. C curve (between 5 and 10 In).
. D curve (between 10 and 14 In). 3P 80,1 mm
. MA curve (between 12 and 14 In, with tolerances reduced
4P 106,8 mm
to + / -10% ).

Thermal threshold: 4. PREPARATION - CONNECTION


. Non operating current (Inf): 1,05 In.
. Operating current (If): 1,3 In.
Fixing:
. On symmetric rail EN/IEC 60715 or DIN 35.
Rated Voltage / Frequency:
. 230 / 400 V ~, 50 / 60 Hz with standard tolerances.
Operating position:
. 240 / 415 V ~, 50 / 60 Hz with standard tolerances. . Vertical Horizontal Upside down on the side
. 125 V per pole in direct current.

Maximum operating voltage:


. 500 V ~, 50 / 60 Hz with derating of breaking capacity.

Breaking capacity:
. 25 kA according to IEC/EN/NF 60947-2

Technical data sheet: F01217EN/00 Updated: - Created: 19/12/2011

1 / 38
DX3 MCB 25kA up to 63A Cat N°(s): 4 097 20 to 4 098 95

(1,5 modules per po


pole)
4. PREPARATION – CONNECTION (continued) 4. PREPARATION – CONNECTION (continued)

Supply: Labelling:
. Either from the top or from the bottom. . Circuit identification by way of a label inserted in the label holder
situated on the product.
Terminal depth:
. 19 mm.
. It is possible to separate the terminals by retractable insulation
shields.

Stripping length recommended:


. 17 mm for main terminals.

Screw head: 5. GENERAL CHARACTERISTICS


. Mixed, slotted and Pozidriv n°2.
Front side marking:
Tightening torque: . By permanent ink pad printing showing:
. Recommended: 3 Nm. - Trade name: DX3
. Mini 2,5 Nm. - Breaking curve
. Maxi 3,5 Nm. - Rated current (in A)
- Icu in kA, Breaking capacity according to IEC/ EN 60947-2
Tools required:
standard (25kA)
. For the terminals: Pozidriv n°2 or flat screwdriver 5,5 mm (6 mm
- Catalogue number and logo
maximum).
- Mark: Legrand
. For fixing: flat screwdriver 5,5 mm (6 mm maximum).

Connectable section:
Copper cable

Without ferrule Without ferrule

Rigid 1 x 1,5mm² to 50mm²


50mm²
-
cable 2 x 1,5mm² to 16mm²

Flexible 1 x 1,5mm² to 35mm²


1 x 1,5mm² to 35mm²
cable 2 x 1,5mm² to 10mm² Short-
Short-circuit breaking
breaking capacity:
. Alternate current 50/60Hz, single-phase or three-phase network,
Manual actuation of the MCB:
MCB: according to IEC 60947-2. B, C, D and MA curves
. Ergonomic 2 position handle:
Un 1P 2P 3P / 4P
0 / OFF: Device open.
I / ON: Device closed. 110 V~ 36 kA 72 kA -

Contact status display:


display: 230 V~ 25 kA 50 kA 50 kA
. By marking of the associated m.c.b. handle:
“O-Off“ white on a green background = contacts opened. 400 V~ Icu - 25 kA 25 kA
“I-On” white on a red background = contacts closed.
440 V~ - 20 kA 20 kA
. By mechanical indicator on front face:
Green = contacts opened. 500 V~ - 10 kA 10 kA
Red = contacts closed.

Sealing:
Sealing: 110 V~
. Possible in ʺOpenʺ position (OFF) or ʺCloseʺ position (ON).
230 V~ Ics 75% of Icu 75% of Icu 75% of Icu
Lockout:: 400 V~
. By 5 mm padlock (cat. n° 4 063 13) or 6 mm padlock (cat. n° 0 227
97) with padlock support (cat. n° 4 063 03) in “Open” position Short-
Short-circuit breaking capacity of only one pole:
Consignment: . Three-phase network 220 / 380 V~ to 240 / 415 V~
- In TN neutral system, Icn1 = 25 kA (under 220 to 240 V~)
. On site padlocking system, possible only open circuit - 0 / OFF
- In IT neutral system, Iit = 6,25 kA (under 380 to 415 V~)
handle position - with 1,5mm² stripped wire for example or 2,4mm
. Three-phase network 110 / 220 V~ to 120 / 240 V~
wide colring.
- In TN neutral system, Icn1 = 50 kA (under 110 to 127 V~)
- In IT neutral system, Iit = 12,5 kA (under 220 to 240 V~)

Technical data sheet: F01217EN/00 Updated: - Created: 19/12/2011

2 / 38
DX3 MCB 25kA up to 63A Cat N°(s): 4 097 20 to 4 098 95

(1,5 modules per po


pole)
5. GENERAL CHARACTERISTICS (continued) 5. GENERAL CHARACTERISTICS (continued)

Short-
Short-circuit breaking
breaking capacity: (continued) Average weight per pole:
. Direct current according to standard IEC 60947-2 . 0,220 kg.

Volume when packed:


Volume (dm³)

Single pole 0,36


Un 1P 2P 3P 4P
Double pole 0,63
24 ÷ 48 V d.c. 25 kA 25 kA - -
Triple / Four pole 1,14
110 V d.c. Icu - 25 kA 25 kA -
Ambient operating temperature:
temperature:
230 V d.c. - - - 25 kA . Min. = -25°C. Max. = +70°C

Ambient storage temperature:


24 ÷ 48 V d.c. 25 kA 25 kA - - . Min. = -40°C. Max. = +70°C
110 V d.c. Ics - 25 kA 25 kA - Protection class:
. Protection index of terminals against solid and liquid bodies:
230 V d.c. - - - 25 kA
IP 20 (according to IEC 529, EN 60529 et NF C 20-010).
Minimum operating voltage : . Protection index of the box against solid and liquid bodies:
. 12 V a.c. / d.c. per pole. IP 40 (according to IEC 529, EN 60529 et NF C 20-010).
. Protection index against mechanical shocks:
Pulse rated voltage: IK 02 (according to EN 50102 et NF C 20-015).
. Uimp = 6 kV (wave 1.5 / 50 µs).
Resistance to sinusoidal vibrations:
Insulation rated voltage: . According to IEC 60068-2-35.
. Ui = 500 V. . Axis : x, y, z.
. Frequency range: 5÷100 Hz ; duration 90 minutes
Pollution degree:: . Displacement (5÷13,2 Hz) : 1mm.
. 3. . Acceleration (13,2÷100 Hz) : 0,7g (g=9,81 m/s2)
Dielectric strength: Recognition:
ecognition:
. 2500 V. . Recognition of the circuit by insertion of a label in the label holder.

Operation at 400Hz: Power dissipated


dissipated per pole at In (in W) :
. mcbs B, C and D curves
. The magnetic thresholds increase by 45%.
In 16 A 20 A 25 A 32 A 40 A 50 A 63 A
Load to close and to open of a pole trough the handle:
. 0,17 Nm per pole to close. 1P ÷ 4P 2,75 4,72 2,8 4,4 4,6 4,32 6,05
. 0,09 Nm per pole to open.
. mcb MA curve
Mechanical endurance according to IEC 60947-
60947-2 :
. 20 000 operations without load In 12,5 A 16 A 25 A 40 A 63 A
. 10 000 operations with load (under In x Cos ϕ=0.9)
2P ÷ 4P 2,2 2,75 2,8 4,6 6,05
. 2 000 operations with load (under In in DC current)

Enclosure material:
. Polyester. . Impedance per pole (Ω) = Power dissipated
. Characteristics of this material: self extinguishing, heat and fire In2
resistant according to EN 60898-1, glow-wire test at 960°C for
external parts made of insulating material necessary to retain in
position current-carrying parts and parts of protective circuit (650°C
for all other external parts made of insulating material).

Technical data sheet: F01217EN/00 Updated: - Created: 19/12/2011

3 / 38
DX3 MCB 25kA up to 63A Cat N°(s): 4 097 20 to 4 098 95

(1,5 modules per po


pole)
5. GENERAL CHARACTERISTICS (continued)

Derating of circuit-
circuit-breakers according to ambient temperature
temperature :
. The nominal characteristics of a circuit breaker are modified according to the ambient temperature inside the cabinet or the enclosure where
the circuit breaker is located.

. Reference temperature: 40°C according IEC/EN 60947-2.


Ambient temperature / In

In (A) - 25°C - 10°C 0°C 10°C 20°C 30°C 40°C 50°C 60°C 70°C

16 21.9 20.0 18.7 18.0 17.3 16.6 16.0 15.4 14.7 14.1

20 27.7 25.0 23.2 22.4 21.6 20.8 20.0 19.2 18.4 17.6

25 34.5 31.5 29.5 28.3 27.2 26.0 25.0 24.0 22.7 21.7

30 41.7 38.3 36.0 34.5 33.0 31.5 30.0 28.8 27.3 26.1

32 45.8 41.0 37.8 36.5 34.9 33.3 32.0 30.7 29.1 27.8

40 55.5 51.0 48.0 46.0 44.0 42.0 40.0 38.0 36.0 34.0

50 70.0 64.0 60.0 57.5 55.0 52.5 50.0 47.5 45.0 42.5

63 88.1 80.6 75.6 72.5 69.9 66.1 63.0 59.8 56.1 52.9

Derating
Derating of MCB for use with fluorescent lights:
Ferromagnetic and electronic ballasts have a high inrush current for a short time. These currents can cause the tripping of circuit breakers.
At the time of the installation, it should take into account the maximum number of ballasts per circuit breaker that the manufacturers of lamps
and ballasts indicate in their catalogues.

Influence of the altitude:


≤2000 m 3000 m 4000 m 5000 m

Dielectric holding 3000 V 2500 V 2000 V 1500 V

Max operational Voltage 400 V 400 V 400 V 400 V

Derating at 40°C none none none none

Derating of MCBs
MCBs function of the number of devices side by side:
When several MCBs are juxtaposed and operate simultaneously, the thermal evacuation of the poles is limited. This results in an increase in
operating temperature of the circuit breakers which can cause unwanted tripping. It is recommended to apply the following coefficients to the
rated currents.

Number of circuit breakers


Coefficient
side by side

2-3 0.9

4–5 0.8

6-9 0.7

≥ 10 0.6

These values are given by the recommendation of IEC 60439-1, NF C 63421 and EN 60439-1 standards.
To avoid to have to use these coefficients, it is necessary to allow a good ventilation and to separate the devices with 0.5 module spacing
elements (cat. N° 4 063 07).

Technical data sheet: F01217EN/00 Updated: - Created: 19/12/2011

4 / 38
DX3 MCB 25kA up to 63A Cat N°(s):
N°(s): 4 097 20 to 4 098 95

(1,5 modules per po


pole)
5. GENERAL CHARACTERISTICS (continued):

MCB’s back-
back-up protection in three-
three-phase network (+ neutal) 400 / 415 V~ according to IEC/EN 60947-
60947-2:
For TT or TN neutral system in 230/400 V network, to know the breaking capacity of the combination of a double pole breaker (connected
between phase and neutral under 230V) downstream of a triple-pole circuit-breaker, take the values shown in Tables 230/400V.
Fuse upstream

gG type

m.c.b. downstream ≤20A 25A 32A 40A 50A 63A 80A 100A 125A 160A

16A - 100kA 100kA 100kA 100kA 100kA 100kA 100kA 100kA 100kA

20A - - 100kA 100kA 100kA 100kA 100kA 100kA 100kA 100kA

25A - - - 100kA 100kA 100kA 100kA 100kA 100kA 100kA


DX3 25kA
32A - - - - 100kA 100kA 100kA 100kA 100kA 100kA
B, C and D curves
40A - - - - - 100kA 100kA 100kA 100kA 100kA

50A - - - - - - 100kA 100kA 100kA 100kA

63A - - - - - - 100kA 100kA 100kA 100kA

Fuse upstream

aM type

m.c.b. downstream ≤20A 25A 32A 40A 50A 63A 80A 100A 125A 160A

16A - 100kA 100kA 100kA 100kA 100kA 100kA 100kA 100kA 100kA

20A - - 100kA 100kA 100kA 100kA 100kA 100kA 100kA 100kA

25A - - - 100kA 100kA 100kA 100kA 100kA 100kA 100kA


DX3 25kA
32A - - - - 100kA 100kA 100kA 100kA 100kA 100kA
B, C and D curves
40A - - - - - 100kA 100kA 100kA 100kA 100kA

50A - - - - - - 100kA 100kA 100kA 100kA

63A - - - - - - 100kA 100kA 100kA 100kA

All these values are also valid for circuit breakers associated to differential blocks.
According to the curves and ratings of circuit breakers, attention to the magnetic threshold and to the size of upstream circuit breakers which
must necessarily be higher.

Technical data sheet: F01217EN/00 Updated: - Created: 19/12/2011

5 / 38
DX3 MCB 25kA up to 63A Cat N°(s): 4 097 20 to 4 098 95

(1,5 modules per po


pole)
5. GENERAL CHARACTERISTICS (continued):

MCB’s back-
back-up protection in three-
three-phase network (+ neutal) 400 / 415 V~ according to IEC/EN 60947-
60947-2:
For TT or TN neutral system in 230/400 V network, to know the breaking capacity of the combination of a double pole breaker (connected
between phase and neutral under 230V) downstream of a triple-pole circuit-breaker, take the values shown in Tables 230/400V.
m.c.b. upstream

DX3 36kA DX3 50kA

C curve B, C and D curves

m.c.b. downstream ≤25A 32A 40A 50A 63A 80A ≤25A 32A 40A 50A 63A

32A - - 36kA 36kA 36kA 36kA - - 50kA 50kA 50kA

DX3 25kA 40A - - - 36kA 36kA 36kA - - - 50kA 50kA

B and C curves 50A - - - - 36kA 36kA - - - - 50kA

63A - - - - - 36kA - - - - -

m.c.b. upstream

DX3 36kA DX3 50kA

C curve B and C curves

m.c.b. downstream ≤25A 32A 40A 50A 63A 80A ≤25A 32A 40A 50A 63A

16A - 36kA 36kA 36kA 36kA 36kA - 50kA 50kA 50kA 50kA

20A - - 36kA 36kA 36kA 36kA - - 50kA 50kA 50kA

25A - - - 36kA 36kA 36kA - - - 50kA 50kA


DX3 25kA
32A - - - - 36kA 36kA - - - - 50kA
D curve
40A - - - - - 36kA - - - - -

50A - - - - - - - - - - -

63A - - - - - - - - - - -

m.c.b. upstream

DX3 50kA

D curve

m.c.b. downstream ≤25A 32A 40A 50A 63A

16A 50kA 50kA 50kA 50kA 50kA

20A 50kA 50kA 50kA 50kA 50kA

25A - 50kA 50kA 50kA 50kA


DX3 25kA
32A - - 50kA 50kA 50kA
D curve
40A - - - 50kA 50kA

50A - - - - 50kA

63A - - - - -

All these values are also valid for circuit breakers associated to differential blocks.
According to the curves and ratings of circuit breakers, attention to the magnetic threshold and to the size of upstream circuit breakers which
must necessarily be higher.

Technical data sheet: F01217EN/00 Updated: - Created: 19/12/2011

6 / 38
DX3 MCB 25kA up to 63A Cat N°(s): 4 097 20 to 4 098 95

(1,5 modules per po


pole)
5. GENERAL CHARACTERISTICS (continued):

MCB’s back-
back-up protection in three-
three-phase network (+ neutal) 400 / 415 V~ according to IEC/EN 60947-
60947-2:
For TT or TN neutral system in 230/400 V network, to know the breaking capacity of the combination of a double pole breaker (connected
between phase and neutral under 230V) downstream of a triple-pole circuit-breaker, take the values shown in Tables 230/400V.
m.c.c.b. upstream

DPX 125 DPX3 160 / DPX3 160 + diff.

36kA 50kA

m.c.b. downstream 16A 25A 40A 63A 100A 125A 16A 25A 40A 63A 80A 100A 125A 160A

16A - 30kA 30kA 30kA 30kA 30kA - 36kA 36kA 36kA 36kA 36kA 36kA 36kA

20A - 30kA 30kA 30kA


30kA 30kA 30kA - 36kA 36kA 36kA 36kA 36kA 36kA 36kA

25A - - 30kA 30kA 30kA 30kA - - 36kA 36kA 36kA 36kA 36kA 36kA
DX3 25kA
32A - - 30kA 30kA 30kA 30kA - - 36kA 36kA 36kA 36kA 36kA 36kA
B, C and D curves
40A - - - 30kA 30kA 30kA - - - 36kA 36kA 36kA 36kA 36kA

50A - - - 30kA 30kA


30kA 30kA - - - 36kA 36kA 36kA 36kA 36kA

63A - - - - 30kA 30kA - - - - 36kA 36kA 36kA 36kA

m.c.c.b. upstream

DPX 160 DPX 250ER DPX 250ER AB

36 - 50kA 36 - 50kA 36kA

m.c.b. downstream 25A 40A 63A 100A 125A 100A 160A 250A 90A 130A 170A 240A

16A 30kA 30kA 30kA 30kA 30kA 30kA 30kA 30kA 30kA 30kA 30kA 30kA

20A 30kA 30kA 30kA 30kA 30kA 30kA 30kA 30kA 30kA 30kA 30kA 30kA

25A - 30kA 30kA 30kA 30kA 30kA 30kA 30kA 30kA 30kA 30kA 30kA
DX3 25kA
32A - - 30kA 30kA 30kA 30kA 30kA 30kA 30kA 30kA 30kA 30kA
B, C and D curves
40A - - 30kA 30kA 30kA 30kA 30kA 30kA 30kA 30kA 30kA 30kA

50A - - - 30kA 30kA 30kA 30kA 30kA 30kA 30kA 30kA 30kA

63A - - 30kA 30kA 30kA 30kA 30kA 30kA 30kA 30kA 30kA

All these values are also valid for circuit breakers associated to differential blocks.
According to the curves and ratings of circuit breakers, attention to the magnetic threshold and to the size of upstream circuit breakers which
must necessarily be higher.

Technical data sheet: F01217EN/00 Updated: - Created: 19/12/2011

7 / 38
DX3 MCB 25kA up to 63A Cat N°(s): 4 097 20 to 4 098 95

(1,5 modules per po


pole)
5. GENERAL CHARACTERISTICS (continued):

MCB’s back-
back-up protection in three-
three-phase network (+ neutal) 400 / 415 V~ according to IEC/EN 60947-
60947-2:
For TT or TN neutral system in 230/400 V network, to know the breaking capacity of the combination of a double pole breaker (connected
between phase and neutral under 230V) downstream of a triple-pole circuit-breaker, take the values shown in Tables 230/400V.
m.c.c.b. upstream
upstream

DPX3250 / DPX3250+diff. DPX 400AB

36 - 70kA 36kA

m.c.b. downstream 100A 160A 200A 250A 320A 400A

16A 36kA 36kA 36kA 36kA 36kA 36kA

20A 36kA 36kA 36kA 36kA 36kA 36kA

25A 36kA 36kA 36kA 36kA 36kA 36kA


DX3 25kA
32A 36kA 36kA 36kA 36kA 36kA 36kA
B, C and D curves
40A 36kA 36kA 36kA 36kA 36kA 36kA

50A 36kA 36kA 36kA 36kA 36kA 36kA

63A 36kA 36kA 36kA 36kA 36kA 36kA

All these values are also valid for circuit breakers associated to differential blocks.
According to the curves and ratings of circuit breakers, attention to the magnetic threshold and to the size of upstream circuit breakers which
must necessarily be higher.

Technical data sheet: F01217EN/00 Updated: - Created: 19/12/2011

8 / 38
DX3 MCB 25kA up to 63A Cat N°(s): 4 097 20 to 4 098 95

(1,5 modules per po


pole)
5. GENERAL CHARACTERISTICS (continued):

MCB’s back-
back-up protection in three-
three-phase network (+ neutal) 400 / 415 V~ according to IEC/EN 60947-
60947-2:
For TT or TN neutral system in 230/400 V network, to know the breaking capacity of the combination of a double pole breaker (connected
between phase and neutral under 230V) downstream of a triple-pole circuit-breaker, take the values shown in Tables 230/400V.
m.c.c.b. upstream

DPX / H / L 250 DPX / DPXH / DPXL 630MT

36 – 70 – 100kA 36 – 70 – 100kA

m.c.b. downstream 25A 40A 63A 100A 160A 250A 250A 320A 400A 500A 630A

32A - 36kA 36kA 36kA 36kA 36kA 36kA 36kA 36kA 36kA 36kA

DX3 25kA 40A - - 36kA 36kA 36kA 36kA 36kA 36kA 36kA 36kA 36kA

B and C curves 50A - - 36kA 36kA 36kA 36kA 36kA


36kA 36kA 36kA 36kA 36kA

63A - - - 36kA 36kA 36kA 36kA 36kA 36kA 36kA 36kA

m.c.c.b. upstream

DPX / H / L 250 DPX / DPXH / DPXL 630MT

36 – 70 – 100kA 36 – 70 – 100kA

m.c.b. downstream 25A 40A 63A 100A 160A 250A 250A 320A 400A 500A 630A

16A 36kA 36kA 36kA 36kA 36kA 36kA 36kA 36kA 36kA 36kA 36kA

20A 36kA 36kA 36kA 36kA 36kA 36kA 36kA 36kA 36kA 36kA 36kA

25A - 36kA 36kA 36kA 36kA 36kA 36kA 36kA 36kA 36kA 36kA
DX3 25kA
32A - 36kA 36kA 36kA 36kA 36kA 36kA 36kA 36kA 36kA 36kA
D curve
40A - - 36kA 36kA 36kA 36kA 36kA 36kA 36kA 36kA 36kA

50A - - 36kA 36kA 36kA 36kA 36kA 36kA 36kA 36kA 36kA

63A - - - 36kA 36kA 36kA 36kA 36kA 36kA 36kA 36kA

m.c.c.b. upstream

DPX 125 DPX3 160 / DPX3 160 + diff.

36kA 50kA

m.c.b. downstream 16A 25A 40A 63A 100A 125A 16A 25A 40A 63A 80A 100A 125A 160A

12,5A 30kA 30kA 30kA 30kA 30kA 30kA 36kA 36kA 36kA 36kA 36kA 36kA 36kA 36kA

16A - 30kA 30kA 30kA 30kA 30kA - 36kA 36kA 36kA 36kA 36kA 36kA 36kA
DX3 25kA
25A - - 30kA 30kA 30kA 30kA - - 36kA 36kA 36kA 36kA 36kA 36kA
MA curve
40A - - - 30kA 30kA 30kA - - - 36kA 36kA 36kA 36kA 36kA

63A - - - - 30kA 30kA - - - - 36kA 36kA 36kA 36kA

All these values are also valid for circuit breakers associated to differential blocks.
According to the curves and ratings of circuit breakers, attention to the magnetic threshold and to the size of upstream circuit breakers which
must necessarily be higher.

Technical data sheet: F01217EN/00 Updated: - Created: 19/12/2011

9 / 38
DX3 MCB 25kA up to 63A Cat N°(s): 4 097 20 to 4 098 95

(1,5 modules per po


pole)
5. GENERAL CHARACTERISTICS (continued):

MCB’s back-
back-up protection in three-
three-phase network (+ neutal) 400 / 415 V~ according to IEC/EN 60947-
60947-2:
For TT or TN neutral system in 230/400 V network, to know the breaking capacity of the combination of a double pole breaker (connected
between phase and neutral under 230V) downstream of a triple-pole circuit-breaker, take the values shown in Tables 230/400V.
m.c.c.b. upstream

DPX 160 DPX 250ER DPX 250ER AB

36 - 50kA 36 - 50kA 36kA

m.c.b. downstream 25A 40A 63A 100A 125A 100A 160A 250A 90A 130A 170A 240A

12,5A 30kA 30kA 30kA 30kA 30kA 30kA 30kA 30kA 30kA 30kA 30kA 30kA

16A 30kA 30kA 30kA 30kA 30kA 30kA 30kA 30kA 30kA 30kA 30kA 30kA
DX3 25kA
25A - 30kA 30kA 30kA 30kA 30kA
30kA 30kA 30kA 30kA 30kA 30kA 30kA
MA curve
40A - - 30kA 30kA 30kA 30kA 30kA 30kA 30kA 30kA 30kA 30kA

63A - - - 30kA 30kA 30kA 30kA 30kA 30kA 30kA 30kA 30kA

m.c.c.b. upstream

DPX3250 / DPX3250+diff. DPX / H / L 250 DPX 400AB

36 - 70kA 36 – 70 – 100kA 36kA

m.c.b. downstream 100A 160A 200A 250A 25A 40A 63A 100A 160A 250A 320A 400A

12,5A 36kA 36kA 36kA 36kA 36kA 36kA 36kA 36kA 36kA 36kA 36kA 36kA

16A 36kA 36kA 36kA 36kA 36kA 36kA 36kA 36kA 36kA 36kA 36kA 36kA
DX3 25kA
25A 36kA 36kA 36kA 36kA 36kA
36kA 36kA 36kA 36kA 36kA 36kA 36kA 36kA
MA curve
40A 36kA 36kA 36kA 36kA 36kA 36kA 36kA 36kA 36kA 36kA 36kA 36kA

63A 36kA 36kA 36kA 36kA 36kA 36kA 36kA 36kA 36kA 36kA 36kA 36kA

m.c.c.b. upstream

DPX / DPXH / DPXL 630MT

36 – 70 – 100kA

m.c.b. downstream 250A 320A 400A 500A 630A

12,5A 36kA 36kA 36kA 36kA 36kA

16A 36kA 36kA 36kA 36kA 36kA


DX3 25kA
25A 36kA 36kA 36kA 36kA 36kA
MA curve
40A 36kA 36kA 36kA 36kA 36kA

63A 36kA 36kA 36kA 36kA 36kA

All these values are also valid for circuit breakers associated to differential blocks.
According to the curves and ratings of circuit breakers, attention to the magnetic threshold and to the size of upstream circuit breakers which
must necessarily be higher.

Technical data sheet: F01217EN/00 Updated: - Created: 19/12/2011

10 / 38
DX3 MCB 25kA up to 63A Cat N°(s): 4 097 20 to 4 098 95

(1,5 modules per po


pole)
5. GENERAL CHARACTERISTICS (continued):

MCB’s back-
back-up protection in three-
three-phase network (+ neutal) 230 / 240 V~ according to IEC/EN 60947-
60947-2:
Fuse upstream
upstream

gG type

m.c.b. downstream ≤20A 25A 32A 40A 50A 63A 80A 100A 125A 160A

16A - 100kA 100kA 100kA 100kA 100kA 100kA 100kA 100kA 100kA

20A - - 100kA 100kA 100kA 100kA 100kA 100kA 100kA 100kA

25A - - - 100kA 100kA 100kA 100kA 100kA 100kA 100kA


DX3 25kA
32A - - - - 100kA 100kA 100kA 100kA 100kA 100kA
B, C and D curves
40A - - - - - 100kA 100kA 100kA 100kA 100kA

50A - - - - - - 100kA 100kA 100kA 100kA

63A - - - - - - 100kA 100kA 100kA 100kA

Fuse upstream

aM type

m.c.b. downstream ≤20A 25A 32A 40A 50A 63A 80A 100A 125A 160A

16A - 100kA 100kA 100kA 100kA 100kA 100kA 100kA 100kA 100kA

20A - - 100kA 100kA 100kA 100kA 100kA 100kA 100kA 100kA

25A - - - 100kA 100kA 100kA 100kA 100kA 100kA 100kA


DX3 25kA
32A - - - - 100kA 100kA 100kA 100kA 100kA 100kA
B, C and D curves
40A - - - - - 100kA 100kA 100kA 100kA 100kA

50A - - - - - - 100kA 100kA 100kA 100kA

63A - - - - - - 100kA 100kA 100kA 100kA

Coordination between modular circuit-


circuit-breakers, three-
three-phase network (+ neutal) 230 / 240 V~ according to IEC/EN 60947-
60947-2:
m.c.b. upstream
upstream

DX3 36kA DX3 50kA

C curve B, C and D curves

m.c.b. downstream ≤25A 32A 40A 50A 63A 80A ≤25A 32A 40A 50A 63A

32A - - 60kA 60kA 60kA 60kA - - 70kA 70kA 70kA

DX3 25kA 40A - - - 60kA 60kA 60kA - - - 70kA 70kA

B and C curves 50A - - - - 60kA 60kA - - - - 70kA

63A - - - - - 60kA - - - - -

All these values are also valid for circuit breakers associated to differential blocks.
According to the curves and ratings of circuit breakers, attention to the magnetic threshold and to the size of upstream circuit breakers which
must necessarily be higher.

Technical data sheet: F01217EN/00 Updated: - Created: 19/12/2011

11 / 38
DX3 MCB 25kA up to 63A Cat N°(s): 4 097 20 to 4 098 95

(1,5 modules per po


pole)
5. GENERAL CHARACTERISTICS (continued)

MCB’s back-
back-up protection in three-
three-phase network (+ neutal) 230 / 240 V~ according to IEC/EN 60947-
60947-2:
m.c.b. upstream

DX3 36kA DX3 50kA

C Curve B and C curves

m.c.b. downstream ≤25A 32A 40A 50A 63A 80A ≤25A 32A 40A 50A 63A

16A - 60kA 60kA 60kA 60kA 60kA - 70kA 70kA 70kA 70kA

20A - - 60kA 60kA 60kA 60kA - - 70kA 70kA 70kA

25A - - - 60kA 60kA 60kA - - - 70kA 70kA


DX3 25kA
32A - - - - 60kA 60kA - - - - 70kA
Curve D
40A - - - - - 60kA - - - - -

50A - - - - - - - - - - -

63A - - - - - - - - - - -

m.c.b. upstream

DX3 50kA

D curve

m.c.b. downstream ≤25A 32A 40A 50A 63A

16A 70kA 70kA 70kA 70kA 70kA

20A 70kA 70kA 70kA 70kA 70kA

25A - 70kA 70kA 70kA 70kA


DX3 25kA
32A - - 70kA 70kA 70kA
D curve
40A - - - 70kA 70kA

50A - - - - 70kA

63A - - - - -

All these values are also valid for circuit breakers associated to differential blocks.
According to the curves and ratings of circuit breakers, attention to the magnetic threshold and to the size of upstream circuit breakers which
must necessarily be higher.

Technical data sheet: F01217EN/00 Updated: - Created: 19/12/2011

12 / 38
DX3 MCB 25kA up to 63A Cat N°(s): 4 097 20 to 4 098 95

(1,5 modules per po


pole)
5. GENERAL CHARACTERISTICS (continued)

MCB’s back-
back-up protection in three-
three-phase network (+ neutal) 230 / 240 V~ according to IEC/EN 60947-
60947-2:
m.c.c.b. upstream

DPX3 160 / DPX3 160 + diff.

50kA

m.c.b. downstream 16A 25A 40A 63A 80A 100A 125A 160A

32A - - 65kA 65kA 65kA 65kA 65kA 65kA

DX3 25kA 40A - - - 65kA 65kA 65kA 65kA 65kA

B and C Curves 50A - - - 65kA 65kA 65kA 65kA 65kA

63A - - - - 65kA 65kA 65kA 65kA

m.c.c.b. upstream

DPX3 160 / DPX3 160 + diff.

50kA

m.c.b. downstream 16A 25A 40A 63A 80A 100A 125A 160A

16A - 65kA 65kA 65kA 65kA 65kA 65kA 65kA

20A - 65kA 65kA 65kA 65kA 65kA 65kA 65kA

25A - - 65kA 65kA 65kA 65kA 65kA 65kA


DX3 25kA
32A - - 65kA 65kA 65kA 65kA 65kA 65kA
D curve
40A - - - 65kA 65kA 65kA 65kA 65kA

50A - - - 65kA 65kA 65kA 65kA 65kA

63A - - - - 65kA 65kA 65kA 65kA

m.c.c.b. upstream

DPX 160 DPX 250ER DPX3 250 / DPX3 250 + diff.

50kA 50kA 70kA

m.c.b. downstream 25A 40A 63A 100A 125A 100A 160A 250A 100A 160A 200A 250A

16A 55kA 55kA 55kA 55kA 55kA 55kA 55kA 55kA 60kA 60kA 60kA 60kA

20A 55kA 55kA 55kA 55kA 55kA 55kA 55kA 55kA 60kA 60kA 60kA 60kA

25A - 55kA 55kA 55kA 55kA 55kA 55kA 55kA 60kA 60kA 60kA 60kA
DX3 25kA
32A - 55kA 55kA 55kA 55kA 55kA 55kA 55kA 60kA 60kA 60kA 60kA
B, C and D curves
40A - - 55kA 55kA 55kA 55kA 55kA 55kA 60kA 60kA 60kA 60kA

50A - - 55kA 55kA 55kA 55kA 55kA 55kA 60kA 60kA 60kA 60kA

63A - - - 55kA 55kA 55kA 55kA


55kA 55kA 60kA 60kA 60kA 60kA

All these values are also valid for circuit breakers associated to differential blocks.
According to the curves and ratings of circuit breakers, attention to the threshold and size of upstream fuse which must necessarily be higher

Technical data sheet: F01217EN/00 Updated: - Created: 19/12/2011

13 / 38
DX3 MCB 25kA up to 63A Cat N°(s): 4 097 20 to 4 098 95

(1,5 modules per po


pole)
5. GENERAL CHARACTERISTICS (continued)

MCB’s back-
back-up protection in three-
three-phase network (+ neutal)
neutal) 230 / 240 V~ according to IEC/EN 60947-
60947-2:
m.c.c.b. upstream

DPX 250 DPX H / L 250

36kA 70 – 100kA

m.c.b. downstream 25A 40A 63A 100A 160A 250A 25A 40A 63A 100A 160A 250A

16A 55kA 55kA 55kA 55kA 55kA 55kA 60kA 60kA 60kA 60kA 60kA 60kA

20A 55kA 55kA 55kA 55kA 55kA 55kA 60kA 60kA 60kA 60kA 60kA 60kA

25A - 55kA 55kA 55kA 55kA 55kA - 60kA 60kA 60kA 60kA 60kA
DX3 25kA
32A - 55kA 55kA 55kA 55kA 55kA - 60kA 60kA 60kA 60kA 60kA
B, C and D curves
40A - - 55kA 55kA 55kA 55kA - - 60kA 60kA 60kA 60kA

50A - - 55kA 55kA 55kA 55kA - - 60kA 60kA 60kA 60kA

63A - - - 55kA 55kA 55kA - - 60kA 60kA 60kA

m.c.c.b. upstream

DPX 630MT DPX H / L 630

36kA 70 – 100kA

m.c.b. downstream 25A 40A 63A 100A 160A 250A 25A 40A 63A 100A 160A 250A

16A 55kA 55kA 55kA 55kA 55kA 55kA 60kA 60kA 60kA 60kA 60kA 60kA

20A 55kA 55kA 55kA 55kA 55kA 55kA 60kA 60kA 60kA 60kA 60kA 60kA

25A - 55kA 55kA 55kA 55kA 55kA - 60kA 60kA 60kA 60kA 60kA
DX3 25kA
32A - 55kA 55kA 55kA 55kA 55kA - 60kA 60kA 60kA 60kA 60kA
B, C and D curves
40A - - 55kA 55kA 55kA 55kA - - 60kA 60kA 60kA 60kA

50A - - 55kA 55kA 55kA 55kA - - 60kA 60kA 60kA 60kA

63A - - - 55kA 55kA 55kA - - 60kA 60kA 60kA

All these values are also valid for circuit breakers associated to differential blocks.
According to the curves and ratings of circuit breakers, attention to the magnetic threshold and to the size of upstream circuit breakers which
must necessarily be higher.

Technical data sheet: F01217EN/00 Updated: - Created: 19/12/2011

14 / 38
DX3 MCB 25kA up to 63A Cat N°(s): 4 097 20 to 4 098 95

(1,5 modules per po


pole)
5. GENERAL CHARACTERISTICS (continued)

Selectivity between two levels of protection


. The downstream circuit breaker must always have a magnetic threshold and a rated current lower than those of the upstream protection.
. Selectivity is indicated total (T) if there is selectivity up to the value of breaking capacity (according to IEC / EN 60947-2) of the downstream
circuit breaker.

Selectivity between modular circuit breakers and fuses:


. Selectivity limit at 400V~: values in Ampere.
Fuse upstream

gG type

m.c.b. downstream 32A 40A 50A 63A 80A 100A 125A 160A

32A - - 1200 1700 1900 3500 4500 8000

DX3 25kA 40A - - - - 1700 3000 4000 6000

B and C curves 50A - - - - 1600 2600 3500 5000

63A - - - - - 2400 3300 5000

16A - 1400 1800 2600 3000 5600 8000 15000

20A - 1200 1500 2200 2500 4600 6300 10000

25A - - 1200 1800 2100 3700 5000 6000


DX3 25kA
32A - - - 1500 1800 3000 4000 5000
D curve
40A - - - - 1700 2600 3500 4500

50A - - - - 1400 2000 3000 4000

63A - - - - - 2000 3000 4000

Fuse upstream

aM type

m.c.b. downstream 25A 32A 40A 50A 63A 80A 100A 125A 160A

32A - - - 1300 2400 3800 5000 7700 9000

DX3 25kA 40A - - - - 2100 3100 4200 6400 7000

B and C curves 50A - - - - 2000 2900 3700 6000 6000

63A - - - - - 2800 3500 5500 6000

16A - 1000 1400 2100 4000 6000 9000 21000 25000

20A - - 1300 1800 3400 5100 7000 14000 20000

25A - - 1000 1500 2700 4000 5500 9000 12000


DX3 25kA
32A - - - 1100
1100 2100 3500 4700 7500 10000
D curve
40A - - - - 1800 2800 4000 6000 7000

50A - - - - 1800 2500 3500 5500 6000

63A - - - - - 2500 3500 5500 6000

Technical data sheet: F01217EN/00 Updated: - Created: 19/12/2011

15 / 38
DX3 MCB 25kA up to 63A Cat N°(s): 4 097 20 to 4 098 95

(1,5 modules per


per po
pole)
5. GENERAL CHARACTERISTICS (continued)

Selectivity between modular circuit breakers:


. Selectivity limit at 400V~: values in Ampere.
m.c.b. upstream

DX3 50kA

C curve

m.c.b. downstream 10A 16A 20A 25A 32A 40A 50A 63A

32A - - - - - 300 500 600

DX3 25kA 40A - - - - - - 400 600

B and C curves 50A - - - - - - - 500

63A - - - - - - - -

16A - - - - 300 500 700 1300

20A - - - - - 400 500 1000

25A - - - - - - 500 800


DX3 25kA
32A - - - - - - - 600
D curve
40A - - - - - - - -

50A - - - - - - - -

63A - - - - - - - -

m.c.b. upstream

DX3 50kA

D curve

m.c.b. downstream 10A 16A 20A 25A 32A 40A 50A 63A

16A - - 240 300 384 500 700 1300

20A - - - 300 384 480 600 1000

25A - - - - 384 480 600 800


DX3 25kA
B, C and D 32A - - - - - 480 600 756
curves
40A - - - - - - 600 756

50A - - - - - - - 756

63A - - - - - - - -

Technical data sheet: F01217EN/00 Updated: - Created: 19/12/2011

16 / 38
DX3 MCB 25kA up to 63A Cat N°(s): 4 097 20 to 4 098 95

(1,5 modules per po


pole)
5. GENERAL CHARACTERISTICS (continued)

Selectivity between modular circuit breakers and M.C.C.B.s:


. Selectivity limit at 400V~: values in Ampere.
m.c.c.b. upstream

DPX3160E / B / N
DPX 160
DPX3160E / B / N + diff.

16 - 25 - 50kA 25 – 36 – 50kA

m.c.b. downstream 16A 25A 40A 63A 80A 100A 125A 160A 25A 40A 63A 100A 160A

32A - - - T T T T T - - 2000 3500 7000

DX3 25kA 40A - - - T T T T T - - 2000 2500 6000

B and C curves 50A - - - 4000 4000 5000 10000 10000 - - - 2000 5500

63A - - - - 3000 5000 10000 10000 - - - 2000 5000

16A - T T T T T T T 6000 6000 6000 6000 T

20A - - T T T T T T - 5000 5000 5000 18000

25A - - T T T T T T - 3500 4500 4500 8500


DX3 25kA
32A - - - T T T T T - - 4000 4000 7000
D curve
40A - - - T T T T T - - 3000 3000 6000

50A - - - - 4000 5000 10000 10000 - - - 3000 5500

63A - - - - 3000 5000 10000 10000 - - - 3000 5000

12,5A T T T T T T T T 7000 7000 7500 7500 T

16A - T T T T T T T 6000 6000 6000 6000 T


DX3 25kA
25A - - T T T T T T - 3500 4500 4500 8500
MA curve
40A - - - T T T T T - - 3000 3000 6000

63A - - - - 3000 5000 10000 10000 - - - 3000 6000

Technical data sheet: F01217EN/00 Updated: - Created: 19/12/2011

17 / 38
DX3 MCB 25kA up to 63A Cat N°(s): 4 097 20 to 4 098 95

(1,5 modules per po


pole)
5. GENERAL CHARACTERISTICS (continued)

Selectivity between modular circuit breakers and M.C.C.B.s:


. Selectivity limit at 400V~: values in Ampere.
m.c.c.b. upstream

DPX 250ER DPX 250ER AB DPX 250 / H / L

25 – 36 – 50kA 36kA 25 - 70 - 100kA

m.c.b. downstream 100A 160A 250A 90A 130A 170A 240A 25A 40A 63A 100A 160A 250A

32A 4000 7000 T T T T T - - 2000 5000 T T

DX3 25kA 40A 3500 6000 T 8 T T T - - 2000 5000 10000 T

B and C curves 50A 2000 5500 7000 4500 4500 T T - - - 4000 8000 T

63A 2000 5000 5000 4500 4500 T T - - - 4000 8000 T

16A 6000 T T T T T T - 4000 4000 10000 T T

20A 6000 T T T T T T - 4000 4000 8000 T T

25A 5500 8500 T T T T T - - 3000 6000 T T


DX3 25kA
32A 4500 7000 T T T T T - - 2000 5000 T T
D curve
40A 4500 6000 T 8000 T T T - - - 5000 10000 T

50A 3500 5500 T 4000 4000 T T - - - 4000 8000 T

63A 3500 5000 6000 4000 4000 T T - - - 4000 8000 T

12,5A T T T T T T T 5000 5000 5000 T T T

16A 6000 T T T T T T - 4000 4000 10000 T T


DX3 25kA
25A 5500 8500 T T T T T - - 3000 6000 T T
MA curve
40A 4500 6000 T 4500 T T T - - - 5000 10000 T

63A 3500 5000 6000 3500 3500 T T - - - 4000 8000 T

Technical data sheet: F01217EN/00 Updated: - Created: 19/12/2011

18 / 38
DX3 MCB 25kA up to 63A Cat N°(s): 4 097 20 to 4 098 95

(1,5 modules per po


pole)
5. GENERAL CHARACTERISTICS (continued)

Selectivity between modular circuit breakers and M.C.C.B.s:


. Selectivity limit at 400V~: values in Ampere.
m.c.c.b. upstream

DPX3 250
DPX 400AB
DPX3 250 + diff.

25 - 36 - 70kA 36kA

m.c.b. downstream 100A 160A 200A 250A 320A 400A

32A T T T T T T

DX3 25kA 40A T T T T T T

B and C curves 50A 20000 T T T T T

63A 15000 T T T T T

16A T T T T T T

20A T T T T T T

25A T T T T T T
DX3 25kA
32A T T T T T T
D curve
40A T T T T T T

50A 20000 T T T T T

63A 15000 T T T T T

12,5A T T T T T T

16A T T T T T T
DX3 25kA
25A T T T T T T
MA curve
40A T T T T T T

63A - T T T T T

Technical data sheet: F01217EN/00 Updated: - Created: 19/12/2011

19 / 38
DX3 MCB 25kA up to 63A Cat N°(s): 4 097 20 to 4 098 95

(1,5 modules per po


pole)
6. CONFORMITIES AND APPROVALS

Compliance to standards:
standards:
. Standard reference: IEC/EN 60947-2 with 25 kA breaking capacity
. CEE guidelines : 73/23/CEE + 93/68/CEE
. Legrand circuit-breakers can be used under the conditions of use as defined by IEC / EN 60947.
. The performance of circuit breakers can be influenced by particular climates: hot dry, cold dry, hot humid, salt fog atmosphere

Classification according to Annex Q (standard IEC/EN 60947-


60947-1) :
. Category C with a range test temperature -25 °C / +70 °C
. salt fog atmosphere according IEC 60068-2-52

Respect of the environment – Compliance with CEE directives:


. Compliance with Directive 2002/95/EC of 27/01/03 called "RoHS" which provides for the banning of hazardous substances such as lead,
mercury, cadmium, hexavalent chromium, brominated flame retardants polybrominated biphenyls (PBBs) and polybrominated diphenyl ethers
(PBDEs) from 1st July 2006
. Compliance with Directive 91/338/CEE of 18/06/91 and Decree 94-647 of 27/07/04

Plastic materials :
. Halogens-free plastic materials.
. Marking of parts according to ISO 11469 and ISO 1043.

Packaging:
. Design and manufacture of packaging in accordance with Decree 98-638 of 07.20.98 and Directive 94/62/EC

Technical data sheet: F01217EN/00 Updated: - Created: 19/12/2011

20 / 38
DX3 MCB 25kA up to 63A Cat N°(s): 4 097 20 to 4 098 95

(1,5 modules per po


pole)
7. CURVES

Current limiting curves


curves:

.B, C, D, and MA curves

. Icc = Square value of symmetric component of the short circuit current ( kA ).


. IP = Max peak value ( kA )

Technical data sheet: F01217EN/00 Updated: - Created: 19/12/2011

21 / 38
DX3 MCB 25kA up to 63A Cat N°(s): 4 097 20 to 4 098 95

(1,5 modules per po


pole)
7. CURVES (continued)

Operating characteristic of circuit breakers B curve :

Technical data sheet: F01217EN/00 Updated: - Created: 19/12/2011

22 / 38
DX3 MCB 25kA
25kA up to 63A Cat N°(s): 4 097 20 to 4 098 95

(1,5 modules per po


pole)
7. CURVES (continued)

. Thermal energy limiting curves


curves of circuit breakers B curve,
curve, 2P (230V~ / 50Hz) :

. Icc = Square value of symmetric component of the short circuit current ( kA ).


. I2t = Thermal energy limited (A²s).

Technical data sheet: F01217EN/00 Updated: - Created: 19/12/2011

23 / 38
DX3 MCB 25kA up to 63A Cat N°(s): 4 097 20 to 4 098 95

(1,5 modules per po


pole)
7. CURVES (continued)

. Thermal
Thermal energy limiting curves
curves of
of circuit breakers B curve,
curve, 2P (400V~ / 50Hz) :

. Icc = Square value of symmetric component of the short circuit current ( kA ).


. I2t = Thermal energy limited (A²s).

Technical data sheet: F01217EN/00 Updated: - Created: 19/12/2011

24 / 38
DX3 MCB 25kA
25kA up to 63A Cat N°(s): 4 097 20 to 4 098 95

(1,5 modules per po


pole)
7. CURVES (continued)

. Thermal
Thermal energy limiting curves
curves of circuit breakers B curve,
curve, 3P / 4P (400V~ / 50Hz) :

. Icc = Square value of symmetric component of the short circuit current ( kA ).


. I2t = Thermal energy limited (A²s).

Technical data sheet: F01217EN/00 Updated: - Created: 19/12/2011

25 / 38
DX3 MCB 25kA up to 63A Cat N°(s): 4 097 20 to 4 098 95

(1,5 modules per po


pole)
7. CURVES (continued)

Operating characteristic of circuit


circuit breakers C curve:
curve:

Technical data sheet: F01217EN/00 Updated: - Created: 19/12/2011

26 / 38
DX3 MCB 25kA up to 63A Cat N°(s): 4 097 20 to 4 098 95

(1,5 modules per po


pole)
7. CURVES (continued)

. Thermal
Thermal energy limiting curves
curves of circuit breakers
breakers C curve , 2P (230V~ / 50Hz) :

. Icc = Square value of symmetric component of the short circuit current ( kA ).


. I2t = Thermal energy limited (A²s).

Technical data sheet: F01217EN/00 Updated: - Created: 19/12/2011

27 / 38
DX3 MCB 25kA up to 63A Cat N°(s): 4 097 20 to 4 098 95

(1,5
(1,5 modules per po
pole)
7. CURVES (continued)

. Thermal
Thermal energy limiting curves
curves of circuit breakers C curve,
curve, 2P (400V~ / 50Hz) :

. Icc = Square value of symmetric component of the short circuit current ( kA ).


. I2t = Thermal energy limited (A²s).

Technical data sheet: F01217EN/00 Updated: - Created: 19/12/2011

28 / 38
DX3 MCB 25kA up to 63A Cat N°(s): 4 097 20 to 4 098 95

(1,5 modules per po


pole)
7. CURVES (continued)

. Thermal
Thermal energy limiting curves
curves of circuit breakers
breakers C curve,
curve, 1P / 3P / 4P (400V~ / 50Hz) :

. Icc = Square value of symmetric component of the short circuit current ( kA ).


. I2t = Thermal energy limited (A²s).

Technical data sheet: F01217EN/00 Updated: - Created: 19/12/2011

29 / 38
DX3 MCB 25kA up to 63A Cat N°(s): 4 097 20 to 4 098 95

(1,5 modules per po


pole)
7. CURVES (continued)

Operating characteristic of circuit breakers D curve:


curve:

Technical data sheet: F01217EN/00 Updated: - Created: 19/12/2011

30 / 38
DX3 MCB 25kA up to 63A Cat N°(s): 4 097 20 to 4 098 95

(1,5 modules per po


pole)
7. CURVES (continued)

. Thermal
Thermal energy limiting curves
curves of circuit breakers D curve,
curve, 2P (230V~ / 50Hz) :

. Icc = Square value of symmetric component of the short circuit current ( kA ).


. I2t = Thermal energy limited (A²s).

Technical data sheet: F01217EN/00 Updated: - Created: 19/12/2011

31 / 38
DX3 MCB 25kA up to 63A Cat N°(s): 4 097 20 to 4 098 95

(1,5 modules per po


pole)
7. CURVES (continued)

. Thermal energy limiting curves


curves of circuit breakers
breakers D curve,
curve, 2P (400V~ / 50Hz) :

. Icc = Square value of symmetric component of the short circuit current ( kA ).


. I2t = Thermal energy limited (A²s).

Technical data sheet: F01217EN/00 Updated: - Created: 19/12/2011

32 / 38
DX3 MCB 25kA up to 63A Cat N°(s): 4 097 20 to 4 098 95

(1,5 modules per po


pole)
7. CURVES (continued)

. Thermal
Thermal energy limiting curves
curves of circuit breakers D curve,
curve, 1P / 3P / 4P (400V~ / 50Hz) :

. Icc = Square value of symmetric component of the short circuit current ( kA ).


. I2t = Thermal energy limited (A²s).

Technical data sheet: F01217EN/00 Updated: - Created: 19/12/2011

33 / 38
DX3 MCB 25kA up to 63A Cat N°(s): 4 097 20 to 4 098 95

(1,5 modules per po


pole)
7. CURVES (continued)

Operating characteristic of circuit breakers MA curve:


curve:

Technical data sheet: F01217EN/00 Updated: - Created: 19/12/2011

34 / 38
DX3 MCB 25kA up to 63A Cat N°(s): 4 097 20 to 4 098 95

(1,5 modules per po


pole)
7. CURVES (continued)

. Thermal
Thermal energy limiting curves
curves of circuit breakers MA curve,
curve, 2P (230V~ / 50Hz) :

. Icc = Square value of symmetric component of the short circuit current ( kA ).


. I2t = Thermal energy limited (A²s).

Technical data sheet: F01217EN/00 Updated: - Created: 19/12/2011

35 / 38
DX3 MCB 25kA up to 63A Cat N°(s): 4 097 20 to 4 098 95

(1,5 modules
modules per po
pole)
7. CURVES (continued)

. Thermal
Thermal energy limiting curves
curves of circuit breakers MA curve,
curve, 2P (400V~ / 50Hz) :

. Icc = Square value of symmetric component of the short circuit current ( kA ).


. I2t = Thermal energy limited (A²s).

Technical data sheet: F01217EN/00 Updated: - Created: 19/12/2011

36 / 38
DX3 MCB 25kA up to 63A Cat N°(s): 4 097 20 to 4 098 95

(1,5 modules per po


pole)
7. CURVES (continued)

. Thermal
Thermal energy limiting curves
curves of circuit breakers MA curve,
curve, 3P / 4P (400V~ / 50Hz) :

. Icc = Square value of symmetric component of the short circuit current ( kA ).


. I2t = Thermal energy limited (A²s).

Technical data sheet: F01217EN/00 Updated: - Created: 19/12/2011

37 / 38
DX3 MCB 25kA up to 63A Cat N°(s): 4 097 20 to 4 098 95

(1,5 modules per po


pole)
8. AUXILIARIES AND ACCESSORIES

Add-
Add-on modules 63A:
63A:
Add on module

mcb 2P 3P 4P

2P X - -

3P - X -

4P - - X

Wiring accessories:
. Sealable screw cover (cat n° 4 063 06).
. Insulating shields (cat n° 4 063 12)
. Aluminium terminals 50mm² max (cat. N° 4 063 10

Signal auxiliaries:
. Auxiliary contact (½ module – cat n° 4 062 58).
. Fault signalling changeover switch (½ module – cat n° 4 062 60).
. Auxiliary contact modifiable in default signal (½ module – cat n°
4 062 62).
. Auxiliary contact + fault signalling switch - can be modified to 2
auxiliary contacts (1 module - cat n° 4 062 66).

Control auxiliaries:
. Shunt releases (1 module - cat n°.4 062 76 / 78).
. Under voltage release (1 module - cat n° 4 062 80 / 82).
. Autonomous shunt trip for NC push-button (1 module - cat n°.
4 062 87).

Possible combinations of auxiliaries and MCBs:


MCBs:
. The auxiliaries are installed to the left of the MCBs
. Maximum number of auxiliaries = 3.
. Maximum number of 1 module signalling auxiliaries = 2.
. Maximum number of control auxiliairies (Cat. N°. 4 063 76 to
4 062 87) = 1.
. The control auxiliary (Cat.N°. 4 062 76 to 4 062 87 must
mandatorily be placed to the left of the signalling auxiliaries (Cat.
N°. 4 062 58 to 4 052 66) where the auxiliaries from these 2 families
are connected to the same MCB.

Sealing:
. Possible in ʺOpenʺ mode (OFF) or ʺCloseʺ mode (ON).

Locking
Locking options:
options:
. By padlock (Cat.N°. 4 063 13 or 0 227 97), whit padlock support
(Cat.N°. 4 063 03).

Installation software:
. XL PRO3

Technical data sheet: F01217EN/00 Updated: - Created: 19/12/2011