CONTENTS PAGES
1. Description - use................................. 1
2. Range................................................. 1
3. Overall dimensions ............................. 1
4. Preparation - Connection .................... 1
5. General characteristics ....................... 2
6. Conformities and approvals .............. 20
7. Characteristic curves ........................ 21
8. Auxiliaries and accessories............... 38
Symbol:
Technology:
. Current limiting device.
. 1,5 module (26,7 mm) per pole.
. Trip free mechanism.
2. RANGE
Number of Poles:
. 1P / 2P / 3P / 4P.
Breaking capacity:
. 25 kA according to IEC/EN/NF 60947-2
1 / 38
DX3 MCB 25kA up to 63A Cat N°(s): 4 097 20 to 4 098 95
Supply: Labelling:
. Either from the top or from the bottom. . Circuit identification by way of a label inserted in the label holder
situated on the product.
Terminal depth:
. 19 mm.
. It is possible to separate the terminals by retractable insulation
shields.
Connectable section:
Copper cable
Sealing:
Sealing: 110 V~
. Possible in ʺOpenʺ position (OFF) or ʺCloseʺ position (ON).
230 V~ Ics 75% of Icu 75% of Icu 75% of Icu
Lockout:: 400 V~
. By 5 mm padlock (cat. n° 4 063 13) or 6 mm padlock (cat. n° 0 227
97) with padlock support (cat. n° 4 063 03) in “Open” position Short-
Short-circuit breaking capacity of only one pole:
Consignment: . Three-phase network 220 / 380 V~ to 240 / 415 V~
- In TN neutral system, Icn1 = 25 kA (under 220 to 240 V~)
. On site padlocking system, possible only open circuit - 0 / OFF
- In IT neutral system, Iit = 6,25 kA (under 380 to 415 V~)
handle position - with 1,5mm² stripped wire for example or 2,4mm
. Three-phase network 110 / 220 V~ to 120 / 240 V~
wide colring.
- In TN neutral system, Icn1 = 50 kA (under 110 to 127 V~)
- In IT neutral system, Iit = 12,5 kA (under 220 to 240 V~)
2 / 38
DX3 MCB 25kA up to 63A Cat N°(s): 4 097 20 to 4 098 95
Short-
Short-circuit breaking
breaking capacity: (continued) Average weight per pole:
. Direct current according to standard IEC 60947-2 . 0,220 kg.
Enclosure material:
. Polyester. . Impedance per pole (Ω) = Power dissipated
. Characteristics of this material: self extinguishing, heat and fire In2
resistant according to EN 60898-1, glow-wire test at 960°C for
external parts made of insulating material necessary to retain in
position current-carrying parts and parts of protective circuit (650°C
for all other external parts made of insulating material).
3 / 38
DX3 MCB 25kA up to 63A Cat N°(s): 4 097 20 to 4 098 95
Derating of circuit-
circuit-breakers according to ambient temperature
temperature :
. The nominal characteristics of a circuit breaker are modified according to the ambient temperature inside the cabinet or the enclosure where
the circuit breaker is located.
In (A) - 25°C - 10°C 0°C 10°C 20°C 30°C 40°C 50°C 60°C 70°C
16 21.9 20.0 18.7 18.0 17.3 16.6 16.0 15.4 14.7 14.1
20 27.7 25.0 23.2 22.4 21.6 20.8 20.0 19.2 18.4 17.6
25 34.5 31.5 29.5 28.3 27.2 26.0 25.0 24.0 22.7 21.7
30 41.7 38.3 36.0 34.5 33.0 31.5 30.0 28.8 27.3 26.1
32 45.8 41.0 37.8 36.5 34.9 33.3 32.0 30.7 29.1 27.8
40 55.5 51.0 48.0 46.0 44.0 42.0 40.0 38.0 36.0 34.0
50 70.0 64.0 60.0 57.5 55.0 52.5 50.0 47.5 45.0 42.5
63 88.1 80.6 75.6 72.5 69.9 66.1 63.0 59.8 56.1 52.9
Derating
Derating of MCB for use with fluorescent lights:
Ferromagnetic and electronic ballasts have a high inrush current for a short time. These currents can cause the tripping of circuit breakers.
At the time of the installation, it should take into account the maximum number of ballasts per circuit breaker that the manufacturers of lamps
and ballasts indicate in their catalogues.
Derating of MCBs
MCBs function of the number of devices side by side:
When several MCBs are juxtaposed and operate simultaneously, the thermal evacuation of the poles is limited. This results in an increase in
operating temperature of the circuit breakers which can cause unwanted tripping. It is recommended to apply the following coefficients to the
rated currents.
2-3 0.9
4–5 0.8
6-9 0.7
≥ 10 0.6
These values are given by the recommendation of IEC 60439-1, NF C 63421 and EN 60439-1 standards.
To avoid to have to use these coefficients, it is necessary to allow a good ventilation and to separate the devices with 0.5 module spacing
elements (cat. N° 4 063 07).
4 / 38
DX3 MCB 25kA up to 63A Cat N°(s):
N°(s): 4 097 20 to 4 098 95
MCB’s back-
back-up protection in three-
three-phase network (+ neutal) 400 / 415 V~ according to IEC/EN 60947-
60947-2:
For TT or TN neutral system in 230/400 V network, to know the breaking capacity of the combination of a double pole breaker (connected
between phase and neutral under 230V) downstream of a triple-pole circuit-breaker, take the values shown in Tables 230/400V.
Fuse upstream
gG type
m.c.b. downstream ≤20A 25A 32A 40A 50A 63A 80A 100A 125A 160A
16A - 100kA 100kA 100kA 100kA 100kA 100kA 100kA 100kA 100kA
Fuse upstream
aM type
m.c.b. downstream ≤20A 25A 32A 40A 50A 63A 80A 100A 125A 160A
16A - 100kA 100kA 100kA 100kA 100kA 100kA 100kA 100kA 100kA
All these values are also valid for circuit breakers associated to differential blocks.
According to the curves and ratings of circuit breakers, attention to the magnetic threshold and to the size of upstream circuit breakers which
must necessarily be higher.
5 / 38
DX3 MCB 25kA up to 63A Cat N°(s): 4 097 20 to 4 098 95
MCB’s back-
back-up protection in three-
three-phase network (+ neutal) 400 / 415 V~ according to IEC/EN 60947-
60947-2:
For TT or TN neutral system in 230/400 V network, to know the breaking capacity of the combination of a double pole breaker (connected
between phase and neutral under 230V) downstream of a triple-pole circuit-breaker, take the values shown in Tables 230/400V.
m.c.b. upstream
m.c.b. downstream ≤25A 32A 40A 50A 63A 80A ≤25A 32A 40A 50A 63A
63A - - - - - 36kA - - - - -
m.c.b. upstream
m.c.b. downstream ≤25A 32A 40A 50A 63A 80A ≤25A 32A 40A 50A 63A
16A - 36kA 36kA 36kA 36kA 36kA - 50kA 50kA 50kA 50kA
50A - - - - - - - - - - -
63A - - - - - - - - - - -
m.c.b. upstream
DX3 50kA
D curve
50A - - - - 50kA
63A - - - - -
All these values are also valid for circuit breakers associated to differential blocks.
According to the curves and ratings of circuit breakers, attention to the magnetic threshold and to the size of upstream circuit breakers which
must necessarily be higher.
6 / 38
DX3 MCB 25kA up to 63A Cat N°(s): 4 097 20 to 4 098 95
MCB’s back-
back-up protection in three-
three-phase network (+ neutal) 400 / 415 V~ according to IEC/EN 60947-
60947-2:
For TT or TN neutral system in 230/400 V network, to know the breaking capacity of the combination of a double pole breaker (connected
between phase and neutral under 230V) downstream of a triple-pole circuit-breaker, take the values shown in Tables 230/400V.
m.c.c.b. upstream
36kA 50kA
m.c.b. downstream 16A 25A 40A 63A 100A 125A 16A 25A 40A 63A 80A 100A 125A 160A
16A - 30kA 30kA 30kA 30kA 30kA - 36kA 36kA 36kA 36kA 36kA 36kA 36kA
25A - - 30kA 30kA 30kA 30kA - - 36kA 36kA 36kA 36kA 36kA 36kA
DX3 25kA
32A - - 30kA 30kA 30kA 30kA - - 36kA 36kA 36kA 36kA 36kA 36kA
B, C and D curves
40A - - - 30kA 30kA 30kA - - - 36kA 36kA 36kA 36kA 36kA
m.c.c.b. upstream
m.c.b. downstream 25A 40A 63A 100A 125A 100A 160A 250A 90A 130A 170A 240A
16A 30kA 30kA 30kA 30kA 30kA 30kA 30kA 30kA 30kA 30kA 30kA 30kA
20A 30kA 30kA 30kA 30kA 30kA 30kA 30kA 30kA 30kA 30kA 30kA 30kA
25A - 30kA 30kA 30kA 30kA 30kA 30kA 30kA 30kA 30kA 30kA 30kA
DX3 25kA
32A - - 30kA 30kA 30kA 30kA 30kA 30kA 30kA 30kA 30kA 30kA
B, C and D curves
40A - - 30kA 30kA 30kA 30kA 30kA 30kA 30kA 30kA 30kA 30kA
50A - - - 30kA 30kA 30kA 30kA 30kA 30kA 30kA 30kA 30kA
63A - - 30kA 30kA 30kA 30kA 30kA 30kA 30kA 30kA 30kA
All these values are also valid for circuit breakers associated to differential blocks.
According to the curves and ratings of circuit breakers, attention to the magnetic threshold and to the size of upstream circuit breakers which
must necessarily be higher.
7 / 38
DX3 MCB 25kA up to 63A Cat N°(s): 4 097 20 to 4 098 95
MCB’s back-
back-up protection in three-
three-phase network (+ neutal) 400 / 415 V~ according to IEC/EN 60947-
60947-2:
For TT or TN neutral system in 230/400 V network, to know the breaking capacity of the combination of a double pole breaker (connected
between phase and neutral under 230V) downstream of a triple-pole circuit-breaker, take the values shown in Tables 230/400V.
m.c.c.b. upstream
upstream
36 - 70kA 36kA
All these values are also valid for circuit breakers associated to differential blocks.
According to the curves and ratings of circuit breakers, attention to the magnetic threshold and to the size of upstream circuit breakers which
must necessarily be higher.
8 / 38
DX3 MCB 25kA up to 63A Cat N°(s): 4 097 20 to 4 098 95
MCB’s back-
back-up protection in three-
three-phase network (+ neutal) 400 / 415 V~ according to IEC/EN 60947-
60947-2:
For TT or TN neutral system in 230/400 V network, to know the breaking capacity of the combination of a double pole breaker (connected
between phase and neutral under 230V) downstream of a triple-pole circuit-breaker, take the values shown in Tables 230/400V.
m.c.c.b. upstream
36 – 70 – 100kA 36 – 70 – 100kA
m.c.b. downstream 25A 40A 63A 100A 160A 250A 250A 320A 400A 500A 630A
32A - 36kA 36kA 36kA 36kA 36kA 36kA 36kA 36kA 36kA 36kA
DX3 25kA 40A - - 36kA 36kA 36kA 36kA 36kA 36kA 36kA 36kA 36kA
m.c.c.b. upstream
36 – 70 – 100kA 36 – 70 – 100kA
m.c.b. downstream 25A 40A 63A 100A 160A 250A 250A 320A 400A 500A 630A
16A 36kA 36kA 36kA 36kA 36kA 36kA 36kA 36kA 36kA 36kA 36kA
20A 36kA 36kA 36kA 36kA 36kA 36kA 36kA 36kA 36kA 36kA 36kA
25A - 36kA 36kA 36kA 36kA 36kA 36kA 36kA 36kA 36kA 36kA
DX3 25kA
32A - 36kA 36kA 36kA 36kA 36kA 36kA 36kA 36kA 36kA 36kA
D curve
40A - - 36kA 36kA 36kA 36kA 36kA 36kA 36kA 36kA 36kA
50A - - 36kA 36kA 36kA 36kA 36kA 36kA 36kA 36kA 36kA
m.c.c.b. upstream
36kA 50kA
m.c.b. downstream 16A 25A 40A 63A 100A 125A 16A 25A 40A 63A 80A 100A 125A 160A
12,5A 30kA 30kA 30kA 30kA 30kA 30kA 36kA 36kA 36kA 36kA 36kA 36kA 36kA 36kA
16A - 30kA 30kA 30kA 30kA 30kA - 36kA 36kA 36kA 36kA 36kA 36kA 36kA
DX3 25kA
25A - - 30kA 30kA 30kA 30kA - - 36kA 36kA 36kA 36kA 36kA 36kA
MA curve
40A - - - 30kA 30kA 30kA - - - 36kA 36kA 36kA 36kA 36kA
All these values are also valid for circuit breakers associated to differential blocks.
According to the curves and ratings of circuit breakers, attention to the magnetic threshold and to the size of upstream circuit breakers which
must necessarily be higher.
9 / 38
DX3 MCB 25kA up to 63A Cat N°(s): 4 097 20 to 4 098 95
MCB’s back-
back-up protection in three-
three-phase network (+ neutal) 400 / 415 V~ according to IEC/EN 60947-
60947-2:
For TT or TN neutral system in 230/400 V network, to know the breaking capacity of the combination of a double pole breaker (connected
between phase and neutral under 230V) downstream of a triple-pole circuit-breaker, take the values shown in Tables 230/400V.
m.c.c.b. upstream
m.c.b. downstream 25A 40A 63A 100A 125A 100A 160A 250A 90A 130A 170A 240A
12,5A 30kA 30kA 30kA 30kA 30kA 30kA 30kA 30kA 30kA 30kA 30kA 30kA
16A 30kA 30kA 30kA 30kA 30kA 30kA 30kA 30kA 30kA 30kA 30kA 30kA
DX3 25kA
25A - 30kA 30kA 30kA 30kA 30kA
30kA 30kA 30kA 30kA 30kA 30kA 30kA
MA curve
40A - - 30kA 30kA 30kA 30kA 30kA 30kA 30kA 30kA 30kA 30kA
63A - - - 30kA 30kA 30kA 30kA 30kA 30kA 30kA 30kA 30kA
m.c.c.b. upstream
m.c.b. downstream 100A 160A 200A 250A 25A 40A 63A 100A 160A 250A 320A 400A
12,5A 36kA 36kA 36kA 36kA 36kA 36kA 36kA 36kA 36kA 36kA 36kA 36kA
16A 36kA 36kA 36kA 36kA 36kA 36kA 36kA 36kA 36kA 36kA 36kA 36kA
DX3 25kA
25A 36kA 36kA 36kA 36kA 36kA
36kA 36kA 36kA 36kA 36kA 36kA 36kA 36kA
MA curve
40A 36kA 36kA 36kA 36kA 36kA 36kA 36kA 36kA 36kA 36kA 36kA 36kA
63A 36kA 36kA 36kA 36kA 36kA 36kA 36kA 36kA 36kA 36kA 36kA 36kA
m.c.c.b. upstream
36 – 70 – 100kA
All these values are also valid for circuit breakers associated to differential blocks.
According to the curves and ratings of circuit breakers, attention to the magnetic threshold and to the size of upstream circuit breakers which
must necessarily be higher.
10 / 38
DX3 MCB 25kA up to 63A Cat N°(s): 4 097 20 to 4 098 95
MCB’s back-
back-up protection in three-
three-phase network (+ neutal) 230 / 240 V~ according to IEC/EN 60947-
60947-2:
Fuse upstream
upstream
gG type
m.c.b. downstream ≤20A 25A 32A 40A 50A 63A 80A 100A 125A 160A
16A - 100kA 100kA 100kA 100kA 100kA 100kA 100kA 100kA 100kA
Fuse upstream
aM type
m.c.b. downstream ≤20A 25A 32A 40A 50A 63A 80A 100A 125A 160A
16A - 100kA 100kA 100kA 100kA 100kA 100kA 100kA 100kA 100kA
m.c.b. downstream ≤25A 32A 40A 50A 63A 80A ≤25A 32A 40A 50A 63A
63A - - - - - 60kA - - - - -
All these values are also valid for circuit breakers associated to differential blocks.
According to the curves and ratings of circuit breakers, attention to the magnetic threshold and to the size of upstream circuit breakers which
must necessarily be higher.
11 / 38
DX3 MCB 25kA up to 63A Cat N°(s): 4 097 20 to 4 098 95
MCB’s back-
back-up protection in three-
three-phase network (+ neutal) 230 / 240 V~ according to IEC/EN 60947-
60947-2:
m.c.b. upstream
m.c.b. downstream ≤25A 32A 40A 50A 63A 80A ≤25A 32A 40A 50A 63A
16A - 60kA 60kA 60kA 60kA 60kA - 70kA 70kA 70kA 70kA
50A - - - - - - - - - - -
63A - - - - - - - - - - -
m.c.b. upstream
DX3 50kA
D curve
50A - - - - 70kA
63A - - - - -
All these values are also valid for circuit breakers associated to differential blocks.
According to the curves and ratings of circuit breakers, attention to the magnetic threshold and to the size of upstream circuit breakers which
must necessarily be higher.
12 / 38
DX3 MCB 25kA up to 63A Cat N°(s): 4 097 20 to 4 098 95
MCB’s back-
back-up protection in three-
three-phase network (+ neutal) 230 / 240 V~ according to IEC/EN 60947-
60947-2:
m.c.c.b. upstream
50kA
m.c.b. downstream 16A 25A 40A 63A 80A 100A 125A 160A
m.c.c.b. upstream
50kA
m.c.b. downstream 16A 25A 40A 63A 80A 100A 125A 160A
m.c.c.b. upstream
m.c.b. downstream 25A 40A 63A 100A 125A 100A 160A 250A 100A 160A 200A 250A
16A 55kA 55kA 55kA 55kA 55kA 55kA 55kA 55kA 60kA 60kA 60kA 60kA
20A 55kA 55kA 55kA 55kA 55kA 55kA 55kA 55kA 60kA 60kA 60kA 60kA
25A - 55kA 55kA 55kA 55kA 55kA 55kA 55kA 60kA 60kA 60kA 60kA
DX3 25kA
32A - 55kA 55kA 55kA 55kA 55kA 55kA 55kA 60kA 60kA 60kA 60kA
B, C and D curves
40A - - 55kA 55kA 55kA 55kA 55kA 55kA 60kA 60kA 60kA 60kA
50A - - 55kA 55kA 55kA 55kA 55kA 55kA 60kA 60kA 60kA 60kA
All these values are also valid for circuit breakers associated to differential blocks.
According to the curves and ratings of circuit breakers, attention to the threshold and size of upstream fuse which must necessarily be higher
13 / 38
DX3 MCB 25kA up to 63A Cat N°(s): 4 097 20 to 4 098 95
MCB’s back-
back-up protection in three-
three-phase network (+ neutal)
neutal) 230 / 240 V~ according to IEC/EN 60947-
60947-2:
m.c.c.b. upstream
36kA 70 – 100kA
m.c.b. downstream 25A 40A 63A 100A 160A 250A 25A 40A 63A 100A 160A 250A
16A 55kA 55kA 55kA 55kA 55kA 55kA 60kA 60kA 60kA 60kA 60kA 60kA
20A 55kA 55kA 55kA 55kA 55kA 55kA 60kA 60kA 60kA 60kA 60kA 60kA
25A - 55kA 55kA 55kA 55kA 55kA - 60kA 60kA 60kA 60kA 60kA
DX3 25kA
32A - 55kA 55kA 55kA 55kA 55kA - 60kA 60kA 60kA 60kA 60kA
B, C and D curves
40A - - 55kA 55kA 55kA 55kA - - 60kA 60kA 60kA 60kA
m.c.c.b. upstream
36kA 70 – 100kA
m.c.b. downstream 25A 40A 63A 100A 160A 250A 25A 40A 63A 100A 160A 250A
16A 55kA 55kA 55kA 55kA 55kA 55kA 60kA 60kA 60kA 60kA 60kA 60kA
20A 55kA 55kA 55kA 55kA 55kA 55kA 60kA 60kA 60kA 60kA 60kA 60kA
25A - 55kA 55kA 55kA 55kA 55kA - 60kA 60kA 60kA 60kA 60kA
DX3 25kA
32A - 55kA 55kA 55kA 55kA 55kA - 60kA 60kA 60kA 60kA 60kA
B, C and D curves
40A - - 55kA 55kA 55kA 55kA - - 60kA 60kA 60kA 60kA
All these values are also valid for circuit breakers associated to differential blocks.
According to the curves and ratings of circuit breakers, attention to the magnetic threshold and to the size of upstream circuit breakers which
must necessarily be higher.
14 / 38
DX3 MCB 25kA up to 63A Cat N°(s): 4 097 20 to 4 098 95
gG type
m.c.b. downstream 32A 40A 50A 63A 80A 100A 125A 160A
Fuse upstream
aM type
m.c.b. downstream 25A 32A 40A 50A 63A 80A 100A 125A 160A
15 / 38
DX3 MCB 25kA up to 63A Cat N°(s): 4 097 20 to 4 098 95
DX3 50kA
C curve
m.c.b. downstream 10A 16A 20A 25A 32A 40A 50A 63A
63A - - - - - - - -
50A - - - - - - - -
63A - - - - - - - -
m.c.b. upstream
DX3 50kA
D curve
m.c.b. downstream 10A 16A 20A 25A 32A 40A 50A 63A
50A - - - - - - - 756
63A - - - - - - - -
16 / 38
DX3 MCB 25kA up to 63A Cat N°(s): 4 097 20 to 4 098 95
DPX3160E / B / N
DPX 160
DPX3160E / B / N + diff.
16 - 25 - 50kA 25 – 36 – 50kA
m.c.b. downstream 16A 25A 40A 63A 80A 100A 125A 160A 25A 40A 63A 100A 160A
B and C curves 50A - - - 4000 4000 5000 10000 10000 - - - 2000 5500
17 / 38
DX3 MCB 25kA up to 63A Cat N°(s): 4 097 20 to 4 098 95
m.c.b. downstream 100A 160A 250A 90A 130A 170A 240A 25A 40A 63A 100A 160A 250A
B and C curves 50A 2000 5500 7000 4500 4500 T T - - - 4000 8000 T
18 / 38
DX3 MCB 25kA up to 63A Cat N°(s): 4 097 20 to 4 098 95
DPX3 250
DPX 400AB
DPX3 250 + diff.
25 - 36 - 70kA 36kA
32A T T T T T T
63A 15000 T T T T T
16A T T T T T T
20A T T T T T T
25A T T T T T T
DX3 25kA
32A T T T T T T
D curve
40A T T T T T T
50A 20000 T T T T T
63A 15000 T T T T T
12,5A T T T T T T
16A T T T T T T
DX3 25kA
25A T T T T T T
MA curve
40A T T T T T T
63A - T T T T T
19 / 38
DX3 MCB 25kA up to 63A Cat N°(s): 4 097 20 to 4 098 95
Compliance to standards:
standards:
. Standard reference: IEC/EN 60947-2 with 25 kA breaking capacity
. CEE guidelines : 73/23/CEE + 93/68/CEE
. Legrand circuit-breakers can be used under the conditions of use as defined by IEC / EN 60947.
. The performance of circuit breakers can be influenced by particular climates: hot dry, cold dry, hot humid, salt fog atmosphere
Plastic materials :
. Halogens-free plastic materials.
. Marking of parts according to ISO 11469 and ISO 1043.
Packaging:
. Design and manufacture of packaging in accordance with Decree 98-638 of 07.20.98 and Directive 94/62/EC
20 / 38
DX3 MCB 25kA up to 63A Cat N°(s): 4 097 20 to 4 098 95
21 / 38
DX3 MCB 25kA up to 63A Cat N°(s): 4 097 20 to 4 098 95
22 / 38
DX3 MCB 25kA
25kA up to 63A Cat N°(s): 4 097 20 to 4 098 95
23 / 38
DX3 MCB 25kA up to 63A Cat N°(s): 4 097 20 to 4 098 95
. Thermal
Thermal energy limiting curves
curves of
of circuit breakers B curve,
curve, 2P (400V~ / 50Hz) :
24 / 38
DX3 MCB 25kA
25kA up to 63A Cat N°(s): 4 097 20 to 4 098 95
. Thermal
Thermal energy limiting curves
curves of circuit breakers B curve,
curve, 3P / 4P (400V~ / 50Hz) :
25 / 38
DX3 MCB 25kA up to 63A Cat N°(s): 4 097 20 to 4 098 95
26 / 38
DX3 MCB 25kA up to 63A Cat N°(s): 4 097 20 to 4 098 95
. Thermal
Thermal energy limiting curves
curves of circuit breakers
breakers C curve , 2P (230V~ / 50Hz) :
27 / 38
DX3 MCB 25kA up to 63A Cat N°(s): 4 097 20 to 4 098 95
(1,5
(1,5 modules per po
pole)
7. CURVES (continued)
. Thermal
Thermal energy limiting curves
curves of circuit breakers C curve,
curve, 2P (400V~ / 50Hz) :
28 / 38
DX3 MCB 25kA up to 63A Cat N°(s): 4 097 20 to 4 098 95
. Thermal
Thermal energy limiting curves
curves of circuit breakers
breakers C curve,
curve, 1P / 3P / 4P (400V~ / 50Hz) :
29 / 38
DX3 MCB 25kA up to 63A Cat N°(s): 4 097 20 to 4 098 95
30 / 38
DX3 MCB 25kA up to 63A Cat N°(s): 4 097 20 to 4 098 95
. Thermal
Thermal energy limiting curves
curves of circuit breakers D curve,
curve, 2P (230V~ / 50Hz) :
31 / 38
DX3 MCB 25kA up to 63A Cat N°(s): 4 097 20 to 4 098 95
32 / 38
DX3 MCB 25kA up to 63A Cat N°(s): 4 097 20 to 4 098 95
. Thermal
Thermal energy limiting curves
curves of circuit breakers D curve,
curve, 1P / 3P / 4P (400V~ / 50Hz) :
33 / 38
DX3 MCB 25kA up to 63A Cat N°(s): 4 097 20 to 4 098 95
34 / 38
DX3 MCB 25kA up to 63A Cat N°(s): 4 097 20 to 4 098 95
. Thermal
Thermal energy limiting curves
curves of circuit breakers MA curve,
curve, 2P (230V~ / 50Hz) :
35 / 38
DX3 MCB 25kA up to 63A Cat N°(s): 4 097 20 to 4 098 95
(1,5 modules
modules per po
pole)
7. CURVES (continued)
. Thermal
Thermal energy limiting curves
curves of circuit breakers MA curve,
curve, 2P (400V~ / 50Hz) :
36 / 38
DX3 MCB 25kA up to 63A Cat N°(s): 4 097 20 to 4 098 95
. Thermal
Thermal energy limiting curves
curves of circuit breakers MA curve,
curve, 3P / 4P (400V~ / 50Hz) :
37 / 38
DX3 MCB 25kA up to 63A Cat N°(s): 4 097 20 to 4 098 95
Add-
Add-on modules 63A:
63A:
Add on module
mcb 2P 3P 4P
2P X - -
3P - X -
4P - - X
Wiring accessories:
. Sealable screw cover (cat n° 4 063 06).
. Insulating shields (cat n° 4 063 12)
. Aluminium terminals 50mm² max (cat. N° 4 063 10
Signal auxiliaries:
. Auxiliary contact (½ module – cat n° 4 062 58).
. Fault signalling changeover switch (½ module – cat n° 4 062 60).
. Auxiliary contact modifiable in default signal (½ module – cat n°
4 062 62).
. Auxiliary contact + fault signalling switch - can be modified to 2
auxiliary contacts (1 module - cat n° 4 062 66).
Control auxiliaries:
. Shunt releases (1 module - cat n°.4 062 76 / 78).
. Under voltage release (1 module - cat n° 4 062 80 / 82).
. Autonomous shunt trip for NC push-button (1 module - cat n°.
4 062 87).
Sealing:
. Possible in ʺOpenʺ mode (OFF) or ʺCloseʺ mode (ON).
Locking
Locking options:
options:
. By padlock (Cat.N°. 4 063 13 or 0 227 97), whit padlock support
(Cat.N°. 4 063 03).
Installation software:
. XL PRO3
38 / 38