REB - Configuration Procedure

The document provides step-by-step instructions for configuring a REB protection system using REBCON software. It details how to create a new project, add bay units, assign CTs and PTs, build the single line diagram, assign zones and feeders, and configure inputs.

Uploaded by

eprprakash9502
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
12 views

REB - Configuration Procedure

The document provides step-by-step instructions for configuring a REB protection system using REBCON software. It details how to create a new project, add bay units, assign CTs and PTs, build the single line diagram, assign zones and feeders, and configure inputs.

Uploaded by

eprprakash9502
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 85

REB CONFIGURATION PROCEDURE 1

REBCON SOFTWARE V 7.31

1. Click REBCON.exe file from start menu.

1
REB CONFIGURATION PROCEDURE 2
REBCON SOFTWARE V 7.31

1. Goto file and create a new project.

2
REB CONFIGURATION PROCEDURE 3
REBCON SOFTWARE V 7.31

1. Give the name of the project.

3
REB CONFIGURATION PROCEDURE 4
REBCON SOFTWARE V 7.31

1. The following screen appears.


2. Click ok.

4
REB CONFIGURATION PROCEDURE 5
REBCON SOFTWARE V 7.31

1. Enter the station name and customer name as per the project.
2. Select the licensed components details as shown.
3. Select central in type of installation and press apply and ok

5
REB CONFIGURATION PROCEDURE 6
REBCON SOFTWARE V 7.31

1. Enter the voltage rating of the project.


2. Select the frequency and type of scheme.
3. Click solidly grounded and apply.

6
REB CONFIGURATION PROCEDURE 7
REBCON SOFTWARE V 7.31

1. Enter the opto-coupler group voltage level and then click change value of all.
2. Click apply and ok.

7
REB CONFIGURATION PROCEDURE 8
REBCON SOFTWARE V 7.31

1. From the pull down menu click Device structure.


2. The following screen appears.

8
REB CONFIGURATION PROCEDURE 9
REBCON SOFTWARE V 7.31

Click next

9
REB CONFIGURATION PROCEDURE 10
REBCON SOFTWARE V 7.31

No of bay units

1. For 1 Diameter we need 5 Bay units.


2. Enter the number of bay units in Add text box.

10
REB CONFIGURATION PROCEDURE 11
REBCON SOFTWARE V 7.31

Select the CT and PT and number of IOs

Enter CU01 here

1. After entering the label and BU type click on Add dialogue box for Next to
appear.
2. Click Next

11
REB CONFIGURATION PROCEDURE 12
REBCON SOFTWARE V 7.31

1. Select IEC 61850 dialogue box and press next.

12
REB CONFIGURATION PROCEDURE 13
REBCON SOFTWARE V 7.31

Click Finish to build process

13
REB CONFIGURATION PROCEDURE 14
REBCON SOFTWARE V 7.31

14
REB CONFIGURATION PROCEDURE 15
REBCON SOFTWARE V 7.31

Click on Single-line diagram.

15
REB CONFIGURATION PROCEDURE 16
REBCON SOFTWARE V 7.31

Click here

16
REB CONFIGURATION PROCEDURE 17
REBCON SOFTWARE V 7.31

De-select

17
REB CONFIGURATION PROCEDURE 18
REBCON SOFTWARE V 7.31

1. Select F10A1B from the pull down and click Apply.

18
REB CONFIGURATION PROCEDURE 19
REBCON SOFTWARE V 7.31

19
REB CONFIGURATION PROCEDURE 20
REBCON SOFTWARE V 7.31

1. Similarly select the model number as shown for 1 ½ Breaker scheme.


2. The model number can be obtained by referring the REB technical manual.

20
REB CONFIGURATION PROCEDURE 21
REBCON SOFTWARE V 7.31

21
REB CONFIGURATION PROCEDURE 22
REBCON SOFTWARE V 7.31

22
REB CONFIGURATION PROCEDURE 23
REBCON SOFTWARE V 7.31

Click cancel when everything is inserted

23
REB CONFIGURATION PROCEDURE 24
REBCON SOFTWARE V 7.31

24
REB CONFIGURATION PROCEDURE 25
REBCON SOFTWARE V 7.31

Select Process bus


zones

25
REB CONFIGURATION PROCEDURE 26
REBCON SOFTWARE V 7.31

Select the bus as shown

26
REB CONFIGURATION PROCEDURE 27
REBCON SOFTWARE V 7.31

Click on New bus zone

27
REB CONFIGURATION PROCEDURE 28
REBCON SOFTWARE V 7.31

Click here and nodes will be assigned

28
REB CONFIGURATION PROCEDURE 29
REBCON SOFTWARE V 7.31

Similarly select all bus and un connected nodes and create new bus zone as shown

29
REB CONFIGURATION PROCEDURE 30
REBCON SOFTWARE V 7.31

30
REB CONFIGURATION PROCEDURE 31
REBCON SOFTWARE V 7.31

31
REB CONFIGURATION PROCEDURE 32
REBCON SOFTWARE V 7.31

32
REB CONFIGURATION PROCEDURE 33
REBCON SOFTWARE V 7.31

33
REB CONFIGURATION PROCEDURE 34
REBCON SOFTWARE V 7.31

34
REB CONFIGURATION PROCEDURE 35
REBCON SOFTWARE V 7.31

Click here after completing all node


alloccation

35
REB CONFIGURATION PROCEDURE 36
REBCON SOFTWARE V 7.31

Click Ok

36
REB CONFIGURATION PROCEDURE 37
REBCON SOFTWARE V 7.31

37
REB CONFIGURATION PROCEDURE 38
REBCON SOFTWARE V 7.31

Edit label as per SLD and type the name

38
REB CONFIGURATION PROCEDURE 39
REBCON SOFTWARE V 7.31

39
REB CONFIGURATION PROCEDURE 40
REBCON SOFTWARE V 7.31

Click Close

40
REB CONFIGURATION PROCEDURE 41
REBCON SOFTWARE V 7.31

41
REB CONFIGURATION PROCEDURE 42
REBCON SOFTWARE V 7.31

42
REB CONFIGURATION PROCEDURE 43
REBCON SOFTWARE V 7.31

43
REB CONFIGURATION PROCEDURE 44
REBCON SOFTWARE V 7.31

Click the pull down menu

44
REB CONFIGURATION PROCEDURE 45
REBCON SOFTWARE V 7.31

Select the bay that you want to assign to the first feeder in the pull down
menu shown by arrow mark

45
REB CONFIGURATION PROCEDURE 46
REBCON SOFTWARE V 7.31

Click here

46
REB CONFIGURATION PROCEDURE 47
REBCON SOFTWARE V 7.31

Repeat the same process

47
REB CONFIGURATION PROCEDURE 48
REBCON SOFTWARE V 7.31

48
REB CONFIGURATION PROCEDURE 49
REBCON SOFTWARE V 7.31

49
REB CONFIGURATION PROCEDURE 50
REBCON SOFTWARE V 7.31

50
REB CONFIGURATION PROCEDURE 51
REBCON SOFTWARE V 7.31

51
REB CONFIGURATION PROCEDURE 52
REBCON SOFTWARE V 7.31

52
REB CONFIGURATION PROCEDURE 53
REBCON SOFTWARE V 7.31

53
REB CONFIGURATION PROCEDURE 54
REBCON SOFTWARE V 7.31

54
REB CONFIGURATION PROCEDURE 55
REBCON SOFTWARE V 7.31

55
REB CONFIGURATION PROCEDURE 56
REBCON SOFTWARE V 7.31

56
REB CONFIGURATION PROCEDURE 57
REBCON SOFTWARE V 7.31

57
REB CONFIGURATION PROCEDURE 58
REBCON SOFTWARE V 7.31

58
REB CONFIGURATION PROCEDURE 59
REBCON SOFTWARE V 7.31

59
REB CONFIGURATION PROCEDURE 60
REBCON SOFTWARE V 7.31

Click on Inputs

60
REB CONFIGURATION PROCEDURE 61
REBCON SOFTWARE V 7.31

Click here

61
REB CONFIGURATION PROCEDURE 62
REBCON SOFTWARE V 7.31

Click on New signal

62
REB CONFIGURATION PROCEDURE 63
REBCON SOFTWARE V 7.31

Select Isolator position

63
REB CONFIGURATION PROCEDURE 64
REBCON SOFTWARE V 7.31

Click Ok

64
REB CONFIGURATION PROCEDURE 65
REBCON SOFTWARE V 7.31

Click the required opto as per the schematic

65
REB CONFIGURATION PROCEDURE 66
REBCON SOFTWARE V 7.31

Proceed in the same way for all other assignments

66
REB CONFIGURATION PROCEDURE 67
REBCON SOFTWARE V 7.31

67
REB CONFIGURATION PROCEDURE 68
REBCON SOFTWARE V 7.31

68
REB CONFIGURATION PROCEDURE 69
REBCON SOFTWARE V 7.31

69
REB CONFIGURATION PROCEDURE 70
REBCON SOFTWARE V 7.31

70
REB CONFIGURATION PROCEDURE 71
REBCON SOFTWARE V 7.31

71
REB CONFIGURATION PROCEDURE 72
REBCON SOFTWARE V 7.31

72
REB CONFIGURATION PROCEDURE 73
REBCON SOFTWARE V 7.31

Click on Outputs

73
REB CONFIGURATION PROCEDURE 74
REBCON SOFTWARE V 7.31

Click here

74
REB CONFIGURATION PROCEDURE 75
REBCON SOFTWARE V 7.31

Click here

75
REB CONFIGURATION PROCEDURE 76
REBCON SOFTWARE V 7.31

Select Trip in the pull down menu

76
REB CONFIGURATION PROCEDURE 77
REBCON SOFTWARE V 7.31

1. Select the output relays which you want to configure as per schematic
2. Then click apply and OK.

77
REB CONFIGURATION PROCEDURE 78
REBCON SOFTWARE V 7.31

78
REB CONFIGURATION PROCEDURE 79
REBCON SOFTWARE V 7.31

Here we can see all the Inputs that we assigned in the previous step. We can directly edit
as per our requirement.

79
REB CONFIGURATION PROCEDURE 80
REBCON SOFTWARE V 7.31

80
REB CONFIGURATION PROCEDURE 81
REBCON SOFTWARE V 7.31

Similarly we can see all the Outputs in this page. We can also edit in the same way.

81
REB CONFIGURATION PROCEDURE 82
REBCON SOFTWARE V 7.31

82
REB CONFIGURATION PROCEDURE 83
REBCON SOFTWARE V 7.31

Enter the values as shown, except the IP-address which is to be entered as per the
scheme. This IP-address is only for rear port communication. For front port no
communication is required.

83
REB CONFIGURATION PROCEDURE 84
REBCON SOFTWARE V 7.31

84
REB CONFIGURATION PROCEDURE 85
REBCON SOFTWARE V 7.31

Enter the password as System. It is case sensitive.


Once the port is connected we can directly down load the configurations.