05 Power Swing
05 Power Swing
© Siemens AG 2008
Energy Sector
Basics
XG XL XM
VG VM VG VM
P sin( )
XG XL XM
VA VB
VG VM
ϑ
0° 90° 180° ϑ
© Siemens AG 2008
Page 2 21.08.23 Jörg Blumschein Energy Sector
Influence of voltage angle
Pmax
ϑ=120° VG VB V M
PM=PG I*XG I V I*XL I*XM
ϑ=60° A
I
I*XG
V VA I*XL VB I*XVM
G M
I
VG VB VM
ϑ=60°
ϑ=120°
ϑ=180°
ϑ=180° VA=0
0° 90° 180° ϑ
© Siemens AG 2008
Page 3 21.08.23 Jörg Blumschein Energy Sector
Typical impedance trajectory
Z(ϑ = 0°)
ϑ = 60°
X
normal load condition
ϑ = 120°
dangerous for
distance protection
ϑ = 180°
unstable power swing
out of step tripping
Z(ϑ = 60°)
φ
Z(ϑ = 180°) Z(ϑ = 120°) R
© Siemens AG 2008
Page 4 21.08.23 Jörg Blumschein Energy Sector
Required characteristics for power swing detection
© Siemens AG 2008
Page 5 21.08.23 Jörg Blumschein Energy Sector
Principle of power swing detection
X
Continuous
calculation and
monitoring of
Impedances
First impedance in
power swing area:
R algorithm starts to
analyze the
Zone impedance trajectory
automatically sized
power swing area
© Siemens AG 2008
Page 6 21.08.23 Jörg Blumschein Energy Sector
Main criteria for power swing detection
monotony
power swing
AND
detected
continuity
smoothness
© Siemens AG 2008
Page 7 21.08.23 Jörg Blumschein Energy Sector
monotony criterion
power swing if
X ΔR1 and
and ΔR
ΔR22 and
or
ΔX1 ΔX1 and
and ΔX
ΔX22
ΔX2 have
have same
same directions
direction
ΔX2 ΔX11 ΔX2 no power swing if
ΔR1 and ΔR2 and
ΔR2
ΔR2 ΔR1 ΔX1 and ΔX2 have
ΔR2 different directions
ΔR1
© Siemens AG 2008
Page 8 21.08.23 Jörg Blumschein Energy Sector
continuity criterion
power swing
X if ΔR or ΔX
exceed a threshold
ΔX
no power swing
if ΔR and ΔX are
below the threshold
ΔR
© Siemens AG 2008
Page 9 21.08.23 Jörg Blumschein Energy Sector
smoothness criterion
power swing if
X ΔR1 nearly ΔR2
ΔX1 and ΔX1 nearly ΔX2
ΔX1 ΔX2 no power swing if
ΔR1 strong vary from ΔR2
ΔR2 ΔR1ΔX2 or
ΔX1 strong vary from ΔX2
ΔR2 ΔR1
© Siemens AG 2008
Page 10 21.08.23 Jörg Blumschein Energy Sector
If three machines oscillating against each other
X Impedance trajectory
will not follow a
perfect elliptical path
difficult to manage
with blinders
© Siemens AG 2008
Page 11 21.08.23 Jörg Blumschein Energy Sector
Quick redetection of power swing after fault inception
© Siemens AG 2008
Page 12 21.08.23 Jörg Blumschein Energy Sector
Secure power swing detection during open pole condition
© Siemens AG 2008
Page 13 21.08.23 Jörg Blumschein Energy Sector
Necessity of power swing detection, example
D1 Trip Trip D2
3-phase-fault initiates
a power swing in the
transmission network
Busbar Busbar
G 1 2
Transmission network
D3 Trip Trip D4
Power swing blocking
function prevents the
distance relays D1 ..
Relay 5
3-phase D4 from unselective
fault tripping
Distribution network
© Siemens AG 2008
Page 14 21.08.23 Jörg Blumschein Energy Sector
Impedance Vector for Distance Relay D4
X
3-phase reverse fault:
Zone Z2
Impedance vector
Zone Z1 jumps to ZFault
ZLoad power swing is initiated by
the reverse fault:
The impedance moves
R on a circular trajectory
ZFault
The power swing blocking
Zone
function prevents an
Zone Z3 unselective trip, before
the impedance vector
enters the tripping zone
Power Swing Detection Z1
© Siemens AG 2008
Page 15 21.08.23 Jörg Blumschein Energy Sector
© Siemens AG 2008
Page 16 21.08.23 Jörg Blumschein Energy Sector
Rotor angle and impedance trajectories for stable
and unstable power swing
Impedance trajectory
X
for stable power swing distinguish between
Rotor angle for stable power swing
stable and unstable
power swing
R
Trip only for
unstable out of step
condition
© Siemens AG 2008
Page 17 21.08.23 Jörg Blumschein Energy Sector
Basic signals for out of step detection
X
1. power swing detected
2. impedance in out of
step area detected
3. impedance crosses
1 the line angle from
3 2
4 the right side
5 4. impedance leaves
power swing area
α
at opposite side after
R
complete crossing
5. impedance crosses
the line angle from
the left side
© Siemens AG 2008
Page 18 21.08.23 Jörg Blumschein Energy Sector
special out of step tripping logic
COUNTER
impedance in out of step area Out of Step Trip
Trip, if the impedance crosses the line angle 3 times inside the
predefined area
© Siemens AG 2008
Page 19 21.08.23 Jörg Blumschein Energy Sector
special out of step tripping scheme
© Siemens AG 2008
Page 20 21.08.23 Jörg Blumschein Energy Sector
conclusion
© Siemens AG 2008
Page 21 21.08.23 Jörg Blumschein Energy Sector