0% found this document useful (0 votes)
158 views

CARE Everything

Uploaded by

Ebuzer
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
158 views

CARE Everything

Uploaded by

Ebuzer
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1552

CARE User Guide

Copyright © 2018 Honeywell GmbH ● All Rights Reserved EN2Z-0937GE51 R0518


CARE USER GUIDE

EN2Z-0937GE51 R0518
CARE USER GUIDE

CARE
V 10.08.01

USER GUIDE

EN2Z-0937GE51 R0518
CARE USER GUIDE

Software License Advisory This document supports software that is proprietary to Honeywell GmbH, Honeywell
Control Systems Ltd, and/or to third party software vendors. Before software
delivery, the end user must execute a software license agreement that governs
software use. Software license agreement provisions include limiting use of the
software to equipment furnished, limiting copying, preserving confidentiality, and
prohibiting transfer to a third party. Disclosure, use, or reproduction beyond that
permitted in the license agreement is prohibited.

Restricted Functionality Please refer to the local announcement document of your CentraLine sales leader
which contains the functions that are not finally released and therefore need
additional approval. Please ask your national CentraLine support person for advice.

Trademark Information CentraLine and ´close to you` are trademarks of Honeywell Inc.

Windows XP Professional, Windows 7 and Word are registered trademarks of


Microsoft Corp.

BACnet is a registered trademark of American Society of Heating, Refrigerating and


Air-Conditioning Engineers (ASHRAE).

Echelon, LON, LONMARK, LONWORKS, LonBuilder, NodeBuilder, LonManager,


LonTalk, LonUsers, LonPoint, Neuron, 3120, 3150, the Echelon logo, the LonMark
logo, and the LonUsers logo are trademarks of Echelon Corporation registered in
the United States and other countries. LonLink, LonResponse, LonSupport, and
LonMaker are trademarks of Echelon Corporation.

EN2Z-0937GE51 R0518
CARE USER GUIDE

TABLE OF CONTENTS

BASICS ............................................................................................................................. 15
CENTRALINE DEVICE LIST ........................................................................................................................... 17

INTRODUCTION .............................................................................................................................................. 19
Applicable Literature ................................................................................ 19
CARE Features ....................................................................................... 20

CARE CONCEPTS .......................................................................................................................................... 21

CARE ENVIRONMENT .................................................................................................................................... 27


Logical Plant Tree .................................................................................... 32
Network Tree ........................................................................................... 35
Interactivity between Logical Plant Tree and Network Tree ..................... 41

CUSTOMIZE WINDOWS DEFAULT REGIONAL AND LANGUAGE SETTINGS ........................................... 43

QUICK TOURS ................................................................................................................................................ 66


Create Project.......................................................................................... 66
Set Global CARE Options........................................................................ 72
Create Controller ..................................................................................... 84
Create Plant............................................................................................. 86
Create Plant Schematic ........................................................................... 89
Modify Datapoints .................................................................................... 94
Manually Assign Datapoints to Controller ................................................ 96
Develop Control Strategy......................................................................... 97
Develop Switching Logic........................................................................ 106
Create Time Program ............................................................................ 113
Create Daily Program ....................................................................... 116
Create Weekly Program.................................................................... 120
Design and Configure C-Bus Network .............................................. 122
Startup Controller .................................................................................. 125
Physically Connect to Controller ....................................................... 125
Translate Controller .......................................................................... 126
Download Controller ......................................................................... 127
Commission LON Controller / LON Device / LonWorks Network ...... 132
Generate Documentation....................................................................... 134

BEYOND THE BASICS .................................................................................................. 137


PROJECTS DEFINITION AND MANAGEMENT ........................................................................................... 139
Create New Project................................................................................ 139
Change Project Password ..................................................................... 148
Open Existing Project ............................................................................ 148
Rename Project ..................................................................................... 152
Delete Project ........................................................................................ 152
Display/Change Project Information ...................................................... 152
Enter Project Offset ............................................................................... 153

PLANTS DEFINITION AND MANAGEMENT ................................................................................................ 157


Create New Plant .................................................................................. 157
Create Plant Schematic ......................................................................... 159
Add Control Strategy to Plant ................................................................ 160
Add Switching Logic to Plant ................................................................. 160
Display/Change Plant Information ......................................................... 160
Change Target I/O Hardware for a Plant .......................................... 162
Display Plant Schematic ........................................................................ 164
Copy / Replicate Plant ........................................................................... 165
General Procedure For Any Controllers ............................................ 167
Background Process of BACnet Controllers ..................................... 170
Additional Procedure For LON Controllers........................................ 171
Additional Procedure For OPS Controllers ....................................... 173
Delete a Plant ........................................................................................ 174

5 EN2Z-0937GE51 R0518
USER GUIDE CARE

CONTROLLERS DEFINITION, ATTACHMENT, AND MANAGEMENT ....................................................... 176


Create New Controller ........................................................................... 176
Attach/Detach Plant............................................................................... 179
Attach Plant to Controller .................................................................. 179
Detach Plant from Controller ............................................................ 182
Detach Plant from one Controller and Attach it to another
Controller .......................................................................................... 183
Copy Controller ..................................................................................... 183
Rename Controller ................................................................................ 186
Delete Controller ................................................................................... 186
Display/Modify Controller Information .................................................... 186
Controller Translation ............................................................................ 190
Controller Download .............................................................................. 191
Rename Datapoints ............................................................................... 192
Delete Unused Datapoints..................................................................... 192

PLANT SCHEMATICS ................................................................................................................................... 193


Schematic Window Description ............................................................. 193
Segment Additions and Insertions ......................................................... 197
Segment Deletion .................................................................................. 200
Macros................................................................................................... 200
Save a Segment as a Macro ............................................................ 200
Load a Macro .................................................................................... 201
Delete a Macro From the Library ...................................................... 201
Physical Point Types ............................................................................. 202
Analog Inputs.................................................................................... 202
Analog Outputs ................................................................................. 205
Digital Inputs ..................................................................................... 206
Digital Outputs .................................................................................. 207
Totalizers .......................................................................................... 209
Feedback Points ............................................................................... 210
Extra User Addresses Display .......................................................... 211
Flex Points............................................................................................. 211
DO_Feedback_DI Points .................................................................. 211
Pulse_2 Points .................................................................................. 212
Multistage Points .............................................................................. 214
User Address Changes ......................................................................... 215
Points Without a Graphic ....................................................................... 217
Plant Information ................................................................................... 218
Point Count ....................................................................................... 219
User Addresses ................................................................................ 219
Segment Information ........................................................................ 220
Extra Text ......................................................................................... 221
Controller Input/Output Information .................................................. 221
Schematic Redraws .............................................................................. 222
Print Plant Schematic ............................................................................ 222
Schematic Function Exit ........................................................................ 222

CONTROL STRATEGY ................................................................................................................................. 223


Control Strategy Window ....................................................................... 224
Control Loop Selection .......................................................................... 227
New Control Loops ........................................................................... 227
Existing Control Loops ...................................................................... 227
Control Loop Functions ......................................................................... 228
Select and Place a Control Icon ....................................................... 228
Connect Control Icons to Plant ......................................................... 229
Connect Two Control Icons .............................................................. 232
Examples .......................................................................................... 233
Delete a Control Icon and its Connections........................................ 235
Delete a Completed Connection ....................................................... 235
Delete an Incomplete Connection ..................................................... 235
Pseudopoints and Flags ........................................................................ 237
General Steps ................................................................................... 240
Create/Assign New Pseudopoints and Flags.................................... 241
Load/Assign Pseudopoints and Flags............................................... 243
Search for Pseudopoints and Flags via Keyboard ............................ 245
Modify Pseudopoint and Flag User Address..................................... 245
Delete Pseudopoints and Flags ........................................................ 247
Connect a Pseudopoint or Flag to a Control Loop ............................ 249
XFMs ..................................................................................................... 249
Map Software Point to XFM Parameter ............................................ 250

EN2Z-0937GE51 R0518 6
CARE USER GUIDE

Map Software Point to an XFM Internal Datapoint ............................ 253


Automatically Create User Addresses of the Same Name and
Map to XFM Internal Datapoint ......................................................... 257
Unmap Mapped Software Point from an XFM Parameter ................. 258
Modify XFM Parameter ..................................................................... 258
Plant Information Displays ..................................................................... 259
Physical Point Information ................................................................ 259
User Addresses ................................................................................ 260
Loop Management................................................................................. 260
Copy a Control Loop ......................................................................... 260
Delete a Control Loop ....................................................................... 261
Check a Control Loop ....................................................................... 262
Print a Control Loop .......................................................................... 262
Control Strategy Exit .............................................................................. 262

SWITCHING LOGIC ....................................................................................................................................... 263


Switching Logic Window ........................................................................ 263
Switching Table Description .................................................................. 267
“AND” Logic ...................................................................................... 268
“OR” Logic ........................................................................................ 269
Time Delays ...................................................................................... 269
Switching Table Creation ....................................................................... 272
Multiple Tables for a Point ................................................................ 273
Row Deletion .................................................................................... 277
Result Row ............................................................................................ 277
Command Changes .......................................................................... 277
Delay Command to a Digital Output Point ........................................ 279
Digital Condition Rows........................................................................... 280
Delay for a Row Condition ................................................................ 280
True or False Changes ..................................................................... 282
Analog Condition Rows ......................................................................... 283
Comparison Type.............................................................................. 283
Comparison Value ............................................................................ 284
Deadband (or Hysteresis) Value ....................................................... 285
True or False Changes ..................................................................... 286
MATH Rows .......................................................................................... 287
Delay for a Logical AND (Column Delay)............................................... 288
OR Columns and Exclusive OR Columns.............................................. 289
Exclusive OR Tables......................................................................... 290
Pseudopoints ......................................................................................... 292
Switching Logic File Management ......................................................... 293
Save a Switching Table .................................................................... 293
Copy a Switching Table to Another Point.......................................... 293
Load a Switching Table..................................................................... 294
Delete a Switching Table .................................................................. 295
Restore a Switching Table ................................................................ 295
Start a New Switching Table ............................................................. 295
Macros ................................................................................................... 295
Save the Switching Table as a Macro ............................................... 295
Load a Macro .................................................................................... 296
Plant Information Displays ..................................................................... 297
Physical Point Information ................................................................ 297
User Addresses ................................................................................ 297
Print Switching Tables ........................................................................... 298
Switching Logic Function Exit ................................................................ 298

EDITORS........................................................................................................................................................ 299
Datapoint Editor ..................................................................................... 300
Edit Datapoints ................................................................................. 301
Basic Working Techniques ............................................................... 301
Point Descriptions ............................................................................. 321
Point Descriptions ............................................................................. 321
BACnet Points .................................................................................. 364
Copy Attribute Values within the Grid ............................................... 463
Simply Copy Values and Texts without Validity Checking ................ 464
Copy Attribute Values per Drag and Drop within the Tree ................ 464
Search and Replace Attribute Settings ............................................. 465
Quick Search in Tree ........................................................................ 471
Use Filters ......................................................................................... 473
Create Report ................................................................................... 477
Configure Drag and Drop .................................................................. 479
Assign Color Map to Datapoint ......................................................... 481

7 EN2Z-0937GE51 R0518
USER GUIDE CARE

Print Datapoint Descriptions ............................................................. 481


Miscellaneous Text Editor (CARE XL-5000).......................................... 482
Analog Engineering Units ................................................................. 486
Digital Engineering Units .................................................................. 487
Point Descriptors .............................................................................. 489
Alarm Texts ...................................................................................... 491
Characteristics .................................................................................. 492
Miscellaneous Text Editor (CARE-BACnet)........................................... 494
Configure BACnet Point.................................................................... 506
Create and Assign Characteristic to BACnet Point ........................... 507
Default Text Editor................................................................................. 516
CARE User Address Search Templates Editor ..................................... 518

TIME PROGRAM EDITOR ............................................................................................................................ 521


Initiate Time Program Function ............................................................. 523
Select a Time Program .......................................................................... 525
User Address Function ..................................................................... 527
Daily Program Function .................................................................... 529
Weekly Program Function ................................................................ 533
Holiday Program Function ................................................................ 535
Yearly Program Function .................................................................. 537
Return Function ................................................................................ 542
Print Time Programs ............................................................................. 542

TERMINAL ASSIGNMENT ............................................................................................................................ 543


Invoke TAF ............................................................................................ 543
Using the Context Menu ........................................................................ 544
Working With Housings ......................................................................... 544
Add Housing ..................................................................................... 545
Remove Housing .............................................................................. 545
Working With Modules........................................................................... 545
Insert Standard Module .................................................................... 545
Insert LON Module............................................................................ 546
Insert XF528 Module ........................................................................ 547
Modify Module Type ......................................................................... 547
Set/Modify Neuron ID for DIO Module .............................................. 548
Modify Module Number..................................................................... 550
Move Module .................................................................................... 550
Remove Module ............................................................................... 554
Working With Points .............................................................................. 554
Assign Point to IP or DIO Module ..................................................... 555
Assign Point/NV to LON device ........................................................ 555
Move Point........................................................................................ 555
Remove Point ................................................................................... 556
Display/Change Point Type .............................................................. 557
Combine Point and Module .............................................................. 559
Working With LON Devices ................................................................... 565
Configure Display ............................................................................. 565
Logical Assignment of LON devices ................................................. 568

FILE MANAGEMENT .................................................................................................................................... 569


Back Up the CARE Database................................................................ 570
Back Up a Project.................................................................................. 571
Restore the CARE Database................................................................. 572
Restore a Project................................................................................... 576
Export the Element Library .................................................................... 579
Import the Element Library .................................................................... 580
Import Controller Files ........................................................................... 583

DOCUMENTATION ....................................................................................................................................... 587


Export Graphic Files .............................................................................. 587
Print Documentation .............................................................................. 590
Select General Pre-Settings ............................................................. 592
Printing Modes .................................................................................. 594
Select Print Options .......................................................................... 595
Technical Information ............................................................................ 632
Default Selections ............................................................................. 632
Printing Order ................................................................................... 635
Print Table of Contents ..................................................................... 637
Suppress "Not Generated" Parameters ............................................ 637
Printer Settings ................................................................................. 638

EN2Z-0937GE51 R0518 8
CARE USER GUIDE

Point Type Abbreviations ....................................................................... 639


Frequently Asked Questions.................................................................. 640

CONTROLLERS ............................................................................................................. 641


EXCEL 800 / 600 / 500 / SMART / 100 / 80 / 50 CONTROLLERS ................................................................ 643

EXCEL 10 CONTROLLERS .......................................................................................................................... 645


Q7752A2 Zone Manager Controller / ELink Controller .......................... 645
Export Zone Manager File to E-Vision .............................................. 649
CARE Time Schedules ..................................................................... 650
EXCEL LINK (XLINK) CONTROLLER ................................................... 652
Steps................................................................................................. 652
Excel VAV2 Controller ........................................................................... 673
Technical Overview: Airflow Sensing ................................................ 673
Engineering Scenarios ...................................................................... 683
Excel 10 Commissioning ....................................................................... 700

OPEN LINK CONTROLLER .......................................................................................................................... 703


OLink Interface/OLink Template) ........................................................... 703
Engineering Process.............................................................................. 705
CARE Environment View ....................................................................... 707
Create OLink Template.......................................................................... 707
Create OLink Controller ......................................................................... 707
Create OLink Plant ................................................................................ 709
Create CARE Datapoints ....................................................................... 709
Create Control Strategy and Switching Logic ........................................ 709
Create OLink Subsystem Controller ...................................................... 710
Create OLink Point(s) ............................................................................ 710
Define OLink Engineering Units ............................................................. 712
Create OLink Conversion Table ............................................................ 712
Map CARE Datapoints to OLink Points ................................................. 714
Automatic Mapping ........................................................................... 714
Manual Mapping ............................................................................... 717
Unmap OLink Points ......................................................................... 719
Move OLink Point.............................................................................. 721
Delete OLink Subsystem Controller/OLink Point .............................. 721
Replicate Plant ...................................................................................... 722
Import/Export OLink Controller .............................................................. 723
Import OLink Controller ..................................................................... 723
Export OLink Controller..................................................................... 724
Migration Strategy ................................................................................. 726

OPS CONTROLLER ...................................................................................................................................... 729


OPS Interface (Template) ...................................................................... 730
Engineering Process.............................................................................. 731
OPS Template Editor ............................................................................. 732
Create OPS Template....................................................................... 732
Save OPS Templates ....................................................................... 735
Rename OPS Template, Subsystem Controller, Subsystem Point ... 735
Delete OPS Template, Subsystem Controller, Subsystem Point ...... 735
Expand and Collapse the Tree ......................................................... 735
Create OPS Controller ........................................................................... 736
Create OPS Plant .................................................................................. 737
Create CARE Datapoints ....................................................................... 737
Create Control Strategy and Switching Logic ........................................ 737
Create OPS Subsystem Controller ........................................................ 738
Create OPS Point(s) .............................................................................. 738
Map CARE Datapoints to OPS Points ................................................... 740
OPS Point Naming Terminology ....................................................... 740
Unmap OPS Points ........................................................................... 742
Move Subsystem Point ..................................................................... 745
Replicate Plant ...................................................................................... 745
Import/Export OPS Controller ................................................................ 746
Import OPS Controller....................................................................... 746
Export OPS Controller ...................................................................... 747
Migration Strategy ................................................................................. 748

FALCON AND EAGLE CONTROLLERS ...................................................................................................... 753


Create BACnet Project .......................................................................... 754
Create BACnet Controller ...................................................................... 754

9 EN2Z-0937GE51 R0518
USER GUIDE CARE

Display/Modify BACNet Controller Properties................................... 757


Upgrade FALCON Controller ............................................................ 761
Create Plant .......................................................................................... 764
Create Datapoints ................................................................................. 766
Add Control Strategy / Switching Logic to Plant .................................... 767
Create Fast Access Lists ....................................................................... 767
Terminal Assignment ............................................................................. 779
Show Datapoints in Grid ........................................................................ 779
BACnet Network Engineering ................................................................ 780
BACnet Topologies ........................................................................... 780
BACnet Network Structure................................................................ 781
Design and Configure BACnet Network............................................ 783
Setup BACnet Controller ....................................................................... 807
Establish Physical Connection to BACnet Controller ........................ 807
Connect to BACnet Controller .......................................................... 811
Connect to Particular BACnet Controller .......................................... 816
Connect to Remote BACnet Controller ............................................. 818
Download Settings into BACnet Controller ....................................... 819
Download Application into BACnet Controller................................... 820
Upload Controller Application from BACnet Controllers.................... 822
Stop/Start Application ....................................................................... 832
Download Firmware into BACnet Controller (Upgrade) .................... 833
Reset BACnet Controller Configuration ............................................ 836
Create Certificate .............................................................................. 837
Modbus Support .................................................................................... 840
Insert Modbus Device from Device Library ....................................... 850
Create Modbus Devices in the Device Library .................................. 852
M-Bus Support ...................................................................................... 854
Commission M-Bus Device in M-Bus Channel ................................. 860
Terminal Assignment of M-Bus Device ............................................. 861
M-Bus Devices Procedures in Device Library................................... 864
Read M-Bus Records from M-Bus Device ........................................ 871
User Access Manager ........................................................................... 877
Start User Access Manager .............................................................. 879
Copy Users ....................................................................................... 890
Notification Class Manager.................................................................... 891
Start Notification Class Manager ...................................................... 892
Application Generator ............................................................................ 900
Event Enrollment Objects / Algorithmic Change Reporting ................... 903
Enable Event Enrollment Alarming for Plant ..................................... 903
Enable Event Enrollment Alarming for Controller System Status ..... 905
Email Alarming ...................................................................................... 906
Enable Event Enrollment Alarming for Controller E-Mail Alarming ... 919
Control Loops ........................................................................................ 921
Mouse and Function Keys ................................................................ 921
Toolbar Buttons ................................................................................ 923
General Functions ............................................................................ 923
Create Control Loop ......................................................................... 924
Edit Control Loop Properties............................................................. 926
Create and Edit control Loop Logic .................................................. 927
Set Execution Order of Control Loop Logic ...................................... 939
Delete Control Loop .......................................................................... 942
Find Element in Control Loop ........................................................... 943
Create Report ................................................................................... 944
Positioning Icons .............................................................................. 946
Connecting Icons .............................................................................. 946
Macros................................................................................................... 956
Create Macro .................................................................................... 957
Edit Macro Properties ....................................................................... 967
Edit the Properties of Inputs/Outputs/Parameters/Registers of a
Macro................................................................................................ 975
Create and Edit Macro Logic ............................................................ 982
Use Pre-configured Macros .............................................................. 993
Convert Protected Macro into Editable Macro .................................. 995
Delete Macro .................................................................................... 997
Flags...................................................................................................... 998
Create and Edit Flags ....................................................................... 998
Global Macro Library ........................................................................... 1002
Macro Conflict................................................................................. 1002
Open Global Macro Library............................................................. 1003
Create Global Macro Library........................................................... 1005
Rename Global Macro Library ........................................................ 1005
EN2Z-0937GE51 R0518 10
CARE USER GUIDE

Delete Global Macro Library ........................................................... 1005


Create Folder .................................................................................. 1005
Rename Folder ............................................................................... 1006
Delete Folder .................................................................................. 1006
Create Global Macro ....................................................................... 1007
Create Global Macro Logic ............................................................. 1017
Add a Macro of a Control Loop to the Global Macro Library ........... 1019
Edit Global Macro Properties .......................................................... 1021
Copy Global Macro ......................................................................... 1022
Update Global Macro in Project ...................................................... 1023
Delete Global Macro ....................................................................... 1024
Dataexchange between Controllers and 3rd Party Devices /
Working with Reference Datapoints..................................................... 1024
Import Datapoint Information from 3rd Party BACnet Device
into Eagle Controller ....................................................................... 1027
Read and Use Status Flags from Remote Devices ......................... 1033
Import Text Macro (XFM) ................................................................ 1037
Loop Objects ....................................................................................... 1043
Create Loop Object ......................................................................... 1043
BACnet Parameter Access via Loop Object ................................... 1053
Graphics Editor .................................................................................... 1068
Background Knowledge .................................................................. 1068
Preparation Notes ........................................................................... 1071
Graphic Components ...................................................................... 1072
The Workspace Environment.......................................................... 1075
Basic Working Techniques for Selection, Adjustment and Editing .. 1079
Basic Steps in Creating a Graphic .................................................. 1083
View / Change Databinding or Links ............................................... 1097
The Graphic Library ........................................................................ 1098
Edit Texts ........................................................................................ 1127
Copy Graphic .................................................................................. 1131
Import / Export Graphic ................................................................... 1133
Project Backup and Restore ........................................................... 1134
Schedules and Calendars.................................................................... 1135
Schedules ....................................................................................... 1137
Calendars ....................................................................................... 1183

LONWORKS ENGINEERING ....................................................................................... 1193


LONWORKS NETWORK ENGINEERING ................................................................................................... 1195
Excel 800/500/50 Controller Network Interface ................................... 1195
Changes on the Controller Network Interface/CARE Application .... 1196
Mapping and Binding ........................................................................... 1197
Design and Configure Network ............................................................ 1201
Set Default LON Properties ............................................................ 1201
Change Service Type for BACnet Datapoints ................................. 1201
The Default Network Structure ........................................................ 1202
Create C-Bus Subsystems.............................................................. 1204
Create Channel ............................................................................... 1205
Connect Channels via Router ......................................................... 1206
Create LON-Bus Subsystems ......................................................... 1209
Create and Place Controller in the Network tree ............................. 1210
Move Controllers in the Network Tree by Drag&Drop ..................... 1211
Configure Channel .......................................................................... 1211
Configure LON-Bus......................................................................... 1211
Configure Lon Interface .................................................................. 1212
Reset Second Domain .................................................................... 1213
Network Topologies for Excel 800, 500 and Smart Controllers ....... 1213
Data Priority of NVs and Datapoints .................................................... 1230
Enter Program ID ................................................................................. 1230
Assign LON devices (Binding) ............................................................. 1232
Add LON Device to the Network ..................................................... 1232
Connect CARE Datapoints/NVs to NVs .......................................... 1239
Display Connected Devices ............................................................ 1251
Permanent and Temporary Display of Devices ............................... 1254
Show Connections of Devices ........................................................ 1254
Configure Connection ..................................................................... 1256
Delete Connection / Remove Binding ............................................. 1257
Remove Datapoint / NV from Terminal ........................................... 1259
Indicate bound Datapoint on LON Device /
Show Bound LON Device of Datapoint ........................................... 1261
View Bound LON Devices on Plant Level ....................................... 1262

11 EN2Z-0937GE51 R0518
USER GUIDE CARE

View Bound LON Devices on LON Object Level ............................ 1263


Copy LON Devices ......................................................................... 1266
Show associated NV of Bound Datapoint ....................................... 1268
The Device Library .............................................................................. 1270
Structure Device Library Tree ......................................................... 1272
Create LON Device......................................................................... 1275
Create OLink Template................................................................... 1277
Create OPS Device ........................................................................ 1279
Configure NV List Display ............................................................... 1280
Assign Value Conversion Table ...................................................... 1282
Rename LON Device ...................................................................... 1284
Copy LON Device ........................................................................... 1284
Delete LON Device ......................................................................... 1286
Export Device Library ..................................................................... 1286
Import Device Library...................................................................... 1288
Copy LON Device Settings .................................................................. 1291
Copy NV Settings ........................................................................... 1291
Copy CPs and NCIs........................................................................ 1294
Edit Excel 500/800 Controller Network Interface Manually .................. 1297
Create and Manually Map NV to Datapoint .................................... 1297
Create LON Object ......................................................................... 1301
Create/Edit Input - / Output NV ....................................................... 1302
Select Input - / Output NV of structured type .................................. 1308
Many-to-One Mapping/NV-Booster® ............................................... 1311
Arrange NVs ................................................................................... 1312
Delete NV/LON Object.................................................................... 1312
Build Conversion Table................................................................... 1313
Copy Conversion Table .................................................................. 1318
Onnet Tuning....................................................................................... 1321
Go Onnet ........................................................................................ 1321
Status of Devices ............................................................................ 1322
Go Offnet ........................................................................................ 1323
Address Device .............................................................................. 1324
Set Device(s) Offline/Online ........................................................... 1329
Reset Device(s) .............................................................................. 1330
Wink Device(s) ............................................................................... 1330
Test Device(s) ................................................................................ 1331
Replace Device .............................................................................. 1332
Upload Parameters ......................................................................... 1333
Get Online Value of NV .................................................................. 1334
Set NV Offline ................................................................................. 1336
Integrate Third Party Devices .............................................................. 1338
CARE and LNS ................................................................................... 1340
Synchronize with LNS..................................................................... 1340
Create LNS Device Template ......................................................... 1351
Consistency Check ......................................................................... 1352
Apply “Sandbox” Channel ............................................................... 1354
Upload Parameters from LNS Database ........................................ 1357
LON Device Monitoring................................................................... 1357
EBI Settings .................................................................................... 1357
LNS Plug-Ins .................................................................................. 1360
Replace Device in LNS Controlled Mode........................................ 1369
Restore CARE Projects .................................................................. 1370
Delete LNS Project(s) ..................................................................... 1370
LNS Credits Handling ..................................................................... 1372
Incremental LonWorks Engineering ................................................ 1372
Download Firmware ........................................................................ 1377
Download Application Remotely (Excel Online Remote) ..................... 1379
Excel Web Remote LON Commissioning ............................................ 1383

ONLINE SERVICE AND COMMISSIONING ................................................................. 1385


ONLINE SERVICE AND COMMISSIONING ............................................................................................... 1387
Overview ............................................................................................. 1387
Getting started ..................................................................................... 1387
Physically Connect to Controller ..................................................... 1387
Start XL Online ............................................................................... 1388
Exit XL Online ................................................................................. 1394
Procedures .......................................................................................... 1395
Define Default Settings ................................................................... 1395
Download Controller ....................................................................... 1401

EN2Z-0937GE51 R0518 12
CARE USER GUIDE

View/Change Application Parameters............................................. 1409


Monitor Z-Registers ........................................................................ 1412
Monitor X/Y-Registers ..................................................................... 1413
Set RACL Cycle time ...................................................................... 1415
Start / Stop Application ................................................................... 1417
View/Modify Time Programs ........................................................... 1418
Set System Clock............................................................................ 1429
Save Application in Flash ROM ...................................................... 1431
Erase Flash ROM ........................................................................... 1431
Work with MMI ................................................................................ 1432
Monitor Points ................................................................................. 1435
Trend Points ................................................................................... 1442
View Alarms .................................................................................... 1455
View Controller Status .................................................................... 1458
Refresh Controller Status................................................................ 1460
Set Controller Number/View Bus Interface Configuration ............... 1460
Download Firmware ........................................................................ 1460
Download Application Remotely ..................................................... 1462

APPENDIX .................................................................................................................... 1463


APPENDIX A: CONTROL ICONS ............................................................................................................... 1465

APPENDIX B: ENGINEERING UNITS ......................................................................................................... 1466


Analog ................................................................................................. 1466
Digital................................................................................................... 1473

APPENDIX C: POINT ATTRIBUTES TABLES............................................................................................ 1475


Analog Input Point Type ...................................................................... 1476
Analog Output Point Type.................................................................... 1477
Pseudo Analog Point Type .................................................................. 1478
Digital Input Point Type........................................................................ 1479
Digital Output Point Type ..................................................................... 1480
Pseudo Digital Point Type ................................................................... 1481
Totalizer Point Type ............................................................................. 1482
Pseudo Totalizer Point Type ................................................................ 1483
Global Analog and Digital Point Types ................................................ 1484
DO Feedback DI Point Type ................................................................ 1485
Pulse 2 Point Type .............................................................................. 1486
Multistage Point Type .......................................................................... 1487

APPENDIX D: PLANT AND CONTROLLER UPGRADES AND DOWNGRADES ..................................... 1488


Multiple Operating System Handling.................................................... 1488
Upgrade Excel 500 Controller to Excel 800 Controller ........................ 1491
Upgrade Controller to OS 2.04 and higher .......................................... 1492
NO/NC Processing.......................................................................... 1492
Upgrade Controller to OS 2.06 when using Multistage or
DO_Feedback_DI Points on DIO .................................................... 1498
Controller OS 2.06 usage and functionality in CARE 4 and
CARE- XL500 10.08.01 ....................................................................... 1499
Sensor Offset Handling ................................................................... 1499
NO/ NC Attribute Handling .............................................................. 1500
Characteristics Handling ................................................................. 1501
Actuator Run Time Handling ........................................................... 1503
OS XLIRC Support .............................................................................. 1504
Default Text Editor .......................................................................... 1504
IRC Register Class Names (DEFT) ................................................ 1506
IRC Engineering Units (DEFT) ........................................................ 1507
IRC Register Class Names (MISC) ................................................. 1507
IRC Engineering Units (MISC) ........................................................ 1508
S 1.1/1.1.30 Support ....................................................................... 1509

APPENDIX E: CHECK UTILITY .................................................................................................................. 1511

APPENDIX F: ERROR MESSAGES ............................................................................................................ 1515


General Errors ..................................................................................... 1515
RACL Generation Errors...................................................................... 1519

INDEX .......................................................................................................................... 1523

13 EN2Z-0937GE51 R0518
USER GUIDE CARE

EN2Z-0937GE51 R0518 14
CARE

BASICS
CENTRALINE DEVICE LIST
INTRODUCTION
CARE CONCEPTS
GETTING STARTED
CARE ENVIRONMENT
QUICK TOURS

15 EN2Z-0937GE51 R0518
CARE

EN2Z-0937GE51 R0518 16
CARE

CENTRALINE DEVICE LIST


This user guide originally refers to different target audiences, CentraLine and Honeywell. In most of the functional descriptions
and screenshots, the Honeywell product names are shown and used, whereas in the CARE software, the Honeywell product
names are replaced with the selectable CentraLine product names. If a product name is not explicitly mentioned as CentraLine
product name, please refer to the following cross-reference table when using CentraLine products and applying CARE
functions that are described in this user guide using Honeywell product names.

Device Name in Honeywell CARE Name in CentraLine System Name in CentraLine Partner
(or in Demo Mode for this Integrator CARE or in Demo CARE or in Demo Mode for
CARE) Mode for this CARE) this CARE)
XL800 CPU XL800 LION LION
XL50 CPU XL50 XL50/PANTHER PANTHER
XL80 CPU XL80 XL80 Not visible
XL100 CPU XL100 XL100 Not visible
XL500 CPU XL500 XL500/TIGER TIGER
XL600 CPU XL600 XL600 Not visible
XL500 Smart CPU XL Smart XL Smart Not visible
Excel Web Excel Web Falcon Not visible
Eagle Excel Web2 EAGLE EAGLE
Analog Input (LON) XFL821A CLIOL821A CLIOL821A
Analog Output (LON) XFL822A CLIOL822A CLIOL822A
Analog Output (LON, XFLR822A CLIOLR822A CLIOLR822A
with manual override)
Binary Input (LON) XFL823A CLIOL823A CLIOL823A
Relay output (LON) XFL824A CLIOL824A CLIOL824A
Relay output (LON, XFLR824A CLIOLR824A CLIOLR824A
with manual overrides)
Analog Input (Panel Bus) XF821A CLIOP821A CLIOP821A
Analog Output XF822A CLIOP822A CLIOP822A
(Panel Bus)
Analog Output XFR822A CLIOPR822A CLIOPR822A
(Panel Bus, with manual
override)
Binary Input (Panel Bus) XF823A CLIOP823A CLIOP823A
Relay Output (Panel Bus) XF824A CLIOP824A CLIOP824A
Relay Output XFR824A CLIOPR824A CLIOPR824A
(Panel Bus, with manual
override)
Floating Actuator XFR825A CLIOPR825A CLIOPR825A
(Panel Bus, with manual
override)
Analog inputs, analog XF830A CLIOPR830A CLIOPR830A
outputs, binary inputs,
and relay outputs (Panel
Bus)
ELink, XLink, OLink, ELink, XLink, OLink, OPS ELink, XLink, OLink, OPS Not visible
OPS

When the “TIGER” controller is selected, special provisions like manual point assignment have to be taken for the engineering
of his controller. Please, refer to the TIGER user guide.

17 EN2Z-0937GE51 R0518
CENTRALINE DEVICE LIST CARE

EN2Z-0937GE51 R0518 18
CARE INTRODUCTION

INTRODUCTION
Applicable Literature
Form No. Title

EN1Z-0964GE51 CARE Installation Guide

74-3556 (US) Excel Live CARE User Guide


EN2B-0183GE51 (Europe) Instructions for using Live CARE software to access controller files on-line and
simulate operation

EN2Z-0940GE51 Excel CARE Control Icons User Guide


Descriptions and application examples of control icons used in the CARE control
strategy

EN2B-162GE51 RACL Editor User Guide


Graphical Editor for creation oft strategy logic programs for Excel 800/500
controllers.

74-3594 (US) ASPECD Editor User Guide


EN2B-185GE51 (Europe) Provides functions to modify the user interface for Excel Operator Terminals

EN2Z-0962GE51 Falcon User Guide


Comprehensive description of the BACnet functions and operation of the Falcon
controller via Web interface

EN2Z-0970GE51 Eagle Web Interface User Guide


Comprehensive description of the BACnet functions and operation of the EAGLE
controller via Web interface

EN2Z-0971GE51 Eagle User Guide


Comprehensive description of the Onboard HMI Eagle controller operation

EN2Z-0929GE51 CL-Touch User Guide


Detailed instructions for using the CL-Touch panel unit

EN2B-0092GE51 Excel 50/100/500/600/800 Software Description


Fundamentals of the Excel 5000 system

EN2B-1031GE02 Excel OpenLink Point Server User & Installation Guide

EN3B-1007 Excel OpenLink Point Server Flyer


Server Flyer

19 EN2Z-0937GE51 R0518
INTRODUCTION CARE

CARE Features
CARE (Excel Computer Aided Regulation Engineering) software provides graphic
tools to create downloadable control programs for EXCEL 5000® Controllers. The
CARE process includes the development of:

• C-bus, LON-bus, and BACnet networks


• Schematics (does not apply to Excel Web controller and ELink controller)
• Control strategies
• Switching logics
• Point attributes
• Point mapping files (optional)
• Time programs
• Job documentation

Supported Controllers and Devices


• Excel 10 / 50 / 80 / 100 / 500 / 600 / 800
• Excel Smart Controller
• Falcon/Eagle Controller
• Excel Link (XLink) Controller
• Excel OLink/OPS Controller
• Excel IRC
• Excel ELink
• Standard I/O Modules
• Distributed I/O Modules
• Smart I/O Modules
• Panel I/O Modules (pluggable)
• Mixed I/O Modules (with panel bus communication)
• M7410G Linear Valve Actuator with LON capabilities and other Honeywell LON
devices
• 3rd party LON devices
• 3rd party BACnet devices

Excel 10 Controllers Excel 10 applications use an Excel 10 Zone Manager Controller (ELink Controller)
as the interface between the EXCEL 5000 C-bus and an E-bus with Excel 10
Controllers. In addition to providing point mapping between the C-bus and the E-
bus, the Excel 10 Zone Manager Controller has the functionality of an Excel 100,
except that it has no physical points.
Excel 10 applications cover the Q7750A1xxx (1000-series) devices used with VAV 1
(Standard VAV) applications and the 2000-series including the Q7752A2xxx Zone
Manager and its corresponding controllers such as VAV 2 and FCU.
CARE 10.08.01 can only be applied to the engineering of 2000-series applications.
For these the process is partly done in CARE and completed within the E-Vision
software tool.

The complete process is described in the Excel E-Vision User Guide 74-2588. The
CARE steps are described in the Excel 10 Applications section in this User Guide.

Excel Link (XLink) Controller Excel Link applications enable the connection of C-NAP bus controllers to an
EXCEL 5000 C-bus. C-NAP bus controllers include Excel MicroCel, Excel
MacroCel, Excel W7620, and Excel W7600.

The CARE process for Excel Link applications is similar to that for the Excel
800/500 controller. There are special considerations as well as additional software
requirements for Excel Link applications.

Excel OLink/OPS Controller The Excel OLink controller and its successor the Excel OPS (Open Point Server)
controller can be engineered in CARE in the same way as a standard Excel
800/500 controller. External bus system information such as from M-bus will be
integrated by simple point mapping between subsystem points and CARE
datapoints.

EN2Z-0937GE51 R0518 20
CARE INTRODUCTION

CARE CONCEPTS
An HVAC control system is typically composed of controller(s) and plant(s). A
controller can be any EXCEL 5000 controller. Plants are specified by their type such
as Air conditioning, Chilled water and Hot water.

Physical Control System A plant is a controlled mechanical system. For example, a plant can be an air
handler, boiler, chiller, or MicroCel Variable Air Volume (VAV) system which is
composed for example, of boilers, heaters, pumps, sensors, and other devices.
Depending on the technical function, each device has its inputs, respectively its
outputs.

The controller and the device are connected via their inputs/outputs. Depending on
the used bus system, the devices are connected physically (C-Bus) or logically
(LON-Bus, or BACnet-bus) to the controller. The plant is controlled by the
application program (control strategy, switching logic, time program) running in the
controller. For example, if the sensor gives a changed temperature value, the
actuator drives the valve to the appropriate position to compensate the temperature
deviation.

CARE Control System Model The physical HVAC control system is realized in CARE by a "Controller - Datapoint
- Plant schematic" model.

CONTROLLER
(Application Program)

Input Output Input Output


Data Exchange
Control

Datapoint: Datapoint: Datapoint: Datapoint: Application


OaTemp AcPos SmkDet ElecHeat Download

Sensor Actuator Detector Heater

PLANT SCHEMATIC

Control Strategy Switching Logic Time Program

Controller The controller is provided by CARE with its controller specific features such as
controller memory and datapoint capacity.

Plant Schematic The physical plant is represented by a schematic (not applicable to Excel Web
controller and ELink controller), that shows the equipment in the plant and how it is
arranged.

21 EN2Z-0937GE51 R0518
INTRODUCTION CARE

Datapoints At the bottom of the schematic (CARE XL-5000 only), arrowheads represent the
inputs/outputs of the equipment as datapoints. They are color-coded, directional
(down is input; up is output), and marked with special symbols for additional
information:

Color Direction Datapoint Type


within
triangle

Green downward Digital input or totalizer


Red downward Analog input
Blue upward Digital output
Violet upward Analog output
Light blue upward Flex point

Alternatively a plant schematic can be drawn without the component symbols and
just displaying the datapoints as arrows.

CARE distinguishes between physical or hardware points which are related to


physical inputs or outputs and software or pseudopoints. Software points can be
created for processing calculation results of software programs.

Datapoints are specified by certain properties, such as point type (analog input,
digital output etc.), user address (OaTemp=outside air temperature) etc. Datapoints
can be identified within the EXCEL 5000 system by their unique user address.

To control the equipment, a control strategy, a switching logic and/or a time


program is added to the plant (see also CARE Main Applications section). For the
control process through the application program in the controller, the datapoints
represent links to provide data exchange between the controller and the plant. Data
exchange through datapoints will be performed according to the attached logic
functions.

Project All relevant information of controllers and their attached plants are saved in a
project.

Example of a project with four plants and three controllers:

EN2Z-0937GE51 R0518 22
CARE INTRODUCTION

Project - Honey well Towers

Heating Plant Controller 1

Chiller Plant Controller 2

Air Handler 1 Controller 3

Air Handler 2

In addition, general information such as reference number, client name, and order
number are part of the project.

Bus Types The controller and plant devices are attached to certain communications media
(bus) and communicate with one another using a common communication protocol.
CARE supports the proprietary Honeywell C-bus (local LON-bus), the open LON-
bus (LonWorks), BACnet-bus and 3rd party bus systems such as Meter bus.

Network Architecture In addition to the specified bus type, the physical arrangement of the devices
attached to the bus can be represented as network architecture in CARE.

A project can cover multiple of different buses building up a network, for example, a
network can include the C-Bus and the LON-Bus.

PROJECT

C-Bus LON-Bus

Subsystem 1
Main System
(Block A)
Subsystem 1
1 (Cooling)
Excel Smart
Excel 500

2 Excel Smart
Excel Smart
Excel 500
Subsystem
3 Excel Smart

Excel 500

..30 Excel 50

Subsystem 2
Subsystem 2 (Heating)
(Block B)

1
Excel 500
Excel 100

2
Excel Smart
Excel 50

3 XFC3A04001

Excel 500

..30 XFC2D06001

CHANNEL 1

23 EN2Z-0937GE51 R0518
INTRODUCTION CARE

CARE Main Applications CARE provides four main applications to create downloadable control programs:

• Plant Schematics (CARE XL-5000 only)


• Control Strategy
• Switching Logic
• Time Programs

Plant Schematic The physical plant is represented by a schematic, that show the equipment in the
plant and how it is arranged (CARE XL-5000 only).

Control Strategy After the plant schematic has been created, a control strategy may be created that
provides the controller with the intelligence to handle the system. Control strategy
defines loops for decisions based on conditions, mathematical calculations, and/or
time-of-day schedules. Control can depend on analog values, digital values, or
both. CARE provides standard control algorithms such as Proportional-Integral-
Derivative (PID), minimum value, maximum value, averaging, and sequencing.

Switching Logic In addition to adding a control strategy, a switching logic can be added to a
schematic for digital control such as switch status.

Switching logic is based on logic tables that set up logical ORs, logical ANDs, and
exclusive ORs. For example, switching logic can be defined to have the return fan
start after a programmed delay from the time that the supply fan was started.

Time Programs Time programs can be set up that control equipment on/off times to coincide with
occupancy. Daily schedules (for example, weekdays, weekends, holidays) will be
defined and assigned to weekly schedules.

Connecting Inputs/Outputs Depending on the used hardware and bus type, CARE provides 2 methods to
connect inputs/outputs between plant and controller.

Terminal Assignment (Panel Bus)


In case of physical connections between controller, for example the Excel 800 and
devices on the panel bus, the controller has panel I/O modules and/or distributed
I/O modules. Then, the device inputs/outputs, respectively the corresponding
datapoints will be automatically assigned to the controller terminals. The
connections can graphically be viewed and re-arranged on the terminal assignment
pane.

Datapoints assigned
to Terminals

Panel I/O module

Binding (Open LON-bus)


In case of a logical connection between a LON controller and other (3rd party) LON
devices on an Open LON-bus, the controller uses neither IP nor distributed I/O
modules. Instead, the device inputs/outputs, respectively the corresponding
datapoints are boardless. Then, connections wíll be made by dragging&dropping

EN2Z-0937GE51 R0518 24
CARE INTRODUCTION

boardless controller points to LON device datapoints which are called network
variables (NVs). The process of connecting LON devices to each other is called
Binding.

Network variable

Connected datapoint

LON device

Application Download into Controller After a plant has been completed by editing the main applications such as control
strategy, switching logic, etc., the application files will be translated into a suitable
controller format. Then the file will be downloaded and the controller test operation
can be started.

25 EN2Z-0937GE51 R0518
INTRODUCTION CARE

EN2Z-0937GE51 R0518 26
CARE CARE ENVIRONMENT

CARE ENVIRONMENT
When you start CARE, you can see three distinct panes of the CARE environment.

This pane contains the


Logical Plant Tree.

This pane displays the


properties and information of
the item selected in the logical
plant tree, respectively in the
network tree.

This pane contains the


Network Tree and the
Control Functions tree

In the CARE-BACnet environment, the left bottom pane further can be split. So a
fourth pane will be displayed.

The left bottom pane includes two trees, the network tree and the control functions
tree. When starting CARE-BACnet, the control functions tree is not visible. To view
the control functions tree, point the cursor on the bottom border till the pointer´s
image changes to a split pointer.

27 EN2Z-0937GE51 R0518
CARE ENVIRONMENT CARE

Move the split bar upwards. The control functions tree will be visible in the fourth
pane.

Logical Plant Tree


The logical plant tree allows to maintain an overall view regarding the logic structure
of the project. This helps you to manage and organize the logical components
(controllers, plants, datapoints, schedules and control loops) of your project.

EN2Z-0937GE51 R0518 28
CARE CARE ENVIRONMENT

Network Tree
The network tree allows to maintain an overall view regarding the bus systems and
the network architecture of the project. This helps you to manage and arrange the
network components (Controllers, BACnet devices, LON devices, LON-objects,
etc.) of your project(s).

Control Functions Tree (CARE-BACnet only)


The control functions tree provides control functions and control macros which will
be used in the control editor for creating control loops.

29 EN2Z-0937GE51 R0518
CARE ENVIRONMENT CARE

Sizing the Tree Displays


The size of the tree display can be varied by moving the split pointer/split bar up or
downwards.

Information and Editing Pane


The right pane can look very different depending on the item selected in the logical
plant tree, respectively in the network tree. It shows the properties for the selected
item. For example, it can show the properties of the project such as name, client,
units of measurement etc. or it can show the terminal assignment of a selected
controller.

EN2Z-0937GE51 R0518 30
CARE CARE ENVIRONMENT

All information available


for the selected item is
grouped on tabs.

Example 1: Project Properties

Example 2: Terminal Assignment

31 EN2Z-0937GE51 R0518
CARE ENVIRONMENT CARE

Logical Plant Tree


The logical structure of the project is shown in a hierarchical tree, the logical plant
tree. It shows the controllers with their plants (attached or unattached) and the
datapoints grouped in types such as Analog Input, Analog Output etc.

The icons in the logical plant tree have the following meaning:

= Project (max. one)

= Controller

= Plant

= Point Type

= Single Point (color depends on point status such as mapped or bound)

The following information can be displayed and edited on the right pane by clicking
on the corresponding tree item:

• Properties of the project, controller, plant and datapoint


• Terminal assignment
• Plant schematic

Display and Edit Properties Clicking on the desired item (project, controller, plant, datapoint) in the logical plant
tree displays the corresponding properties on the right pane for editing:

EN2Z-0937GE51 R0518 32
CARE CARE ENVIRONMENT

Example 3: Project Properties

Display Plant Schematic Clicking on the plant in the logical plant tree and then selecting the Schematic
(CARE XL-5000 only) tab on the right pane displays the plant schematic (display only). To create and edit
a plant schematic, please refer to the ”Create Plant Schematic” section.

33 EN2Z-0937GE51 R0518
CARE ENVIRONMENT CARE

Display Terminal Assignments Clicking on the controller in the logical plant tree and then selecting the Terminal
Assignment tab on the right pane, displays the terminal assignments of the
controller. If LON devices have been added, they will also be displayed.

To assign datapoints to terminals, please refer to the “Manually assign Datapoints


to Controller” section.

Display Datapoints in Grid Clicking either on the project, controller or plant in the logical plant tree and then
selecting the Grid tab on the right pane, displays all datapoints with their attributes
in a grid. To edit datapoints, please refer to the “Modify Datapoints” section.

EN2Z-0937GE51 R0518 34
CARE CARE ENVIRONMENT

Network Tree
The Bus types and A project can cover multiple of different buses (C-Bus, LON-Bus, BACnet-Bus or
Network Architecture other) building up the network. The skeletal structure of the network represents the
physical and logical conditions in the building.

PROJECT

C-Bus LON-Bus

Subsystem 1
Main System
(Block A)
Subsystem 1
1 (Cooling)
Excel Smart
Excel 500

2 Excel Smart
Excel Smart
Excel 500
Subsystem
3 Excel Smart

Excel 500

..30 Excel 50

Subsystem 2
Subsystem 2 (Heating)
(Block B)

1
Excel 500
Excel 100

2
Excel Smart
Excel 50

3 XFC3A04001

Excel 500

..30 XFC2D06001

CHANNEL 1

Example 4: Project with multiple different buses, in this case (C-Bus and LON-
Bus)

The network is displayed below the logical plant tree in a hierarchical network tree.

35 EN2Z-0937GE51 R0518
CARE ENVIRONMENT CARE

The icons in the network tree have the following meaning:

= Project

= Bus type

EN2Z-0937GE51 R0518 36
CARE CARE ENVIRONMENT

= LON-channel

= User defined Default System or Subsystem, or Uploaded Devices

= LON device (dependent on status different colors)

= LON object (dependent on status different colors)

= Input NV (dependent on status different colors)

= Output NV (dependent on status different colors)

= Structured Input NV

= Structured Output NV

= Standard configuration property type (SCPT) / User-defined configuration


property type (UCPT)

= Connection between datapoint/NV and NV

= Router

The network tree shows two basic bus types. In CARE XL-5000, it contains the C-
Bus, simply named Bus and LON-Works.

In CARE-BACnet, it contains the BACnet-Bus and LON-Works.

Each bus is sub-divided by default to allow an arrangement of the network


components according to the physical conditions in the building.

37 EN2Z-0937GE51 R0518
CARE ENVIRONMENT CARE

The C-Bus (Bus) folder contains the Bus 1 subfolder by default. Further created
subfolders will be numbered continuously. The Bus subfolders represent the
physical C-Bus network structure of the project and contain the C-bus controllers
which control that segment of the building.

NOTE: The subfolder names are examples and freely editable. For example, the
default Bus 1 subfolder can be named into Area1 or Block A.

The LON-Works folder represents the network interface of the LON-Bus and is
subdivided by default into a physical part, called Channels and a logical part, called
Default System.

EN2Z-0937GE51 R0518 38
CARE CARE ENVIRONMENT

The Channels folder contains the Channel_1 subfolder by default. Additional


channels can be created and their names are freely editable.

A channel arranged in the Channels folder, represents the physical medium, for
example, twisted-pair cable, and lists all LON devices attached to this cable.
Controllers can be shifted between channels to model the physical conditions in the
building.

The Default System represents the logical LON-Bus part and provides all software
functions necessary to work on LON devices, LON objects, NVs etc. It might
contain the following components:

• Subsystems (to be created below the Default System)


• LON devices
• LON objects
• NVs (network variables)
• SCPTs (standard configuration property types)

39 EN2Z-0937GE51 R0518
CARE ENVIRONMENT CARE

NOTE: The Default System and subsystems can have further subsystems.
Names as "Default System" and "Subsystem" are examples and freely
editable.

Display and Edit Properties Clicking on the desired item (project, subsystem, LON device, LON object, NV) in
the network tree, displays the corresponding properties on the right pane for editing:

Example 5: Channel Properties

EN2Z-0937GE51 R0518 40
CARE CARE ENVIRONMENT

Example 6: NV Properties

Interactivity between Logical Plant Tree and Network Tree


For fast navigation and working during the Engineering process, both the logical
plant tree and the network tree are available in parallel, that is, important functions
are concurrently activated in both trees.

When creating a controller in the logical plant tree, it will be automatically created in
the network tree and available four times in all:

• Once in the logical plant tree


• Once in the C-Bus (Bus) folder
• Once in the Channels folder
• Once in the Default System folder

Hence, the terminal assignment of a particular controller is automatically available


in both trees by simply double-clicking on the controller, either in the logical plant
tree or in the network tree. A selected controller is then highlighted in yellow at
every location in the tree.

41 EN2Z-0937GE51 R0518
CARE ENVIRONMENT CARE

At this time, the Terminal Assignment


tab is selected on the Information and
Editing pane.

The yellow-highlighted controller C01


is selected in the logical plant tree
and 4 times available in the trees.

EN2Z-0937GE51 R0518 42
CARE CUSTOMIZE WINDOWS DEFAULT REGIONAL AND LANGUAGE SETTINGS

CUSTOMIZE WINDOWS DEFAULT REGIONAL AND LANGUAGE SETTINGS


In order to setup an Excel 5000 system that uses any language other than the
respective Windows default language, you must customize the Regional and
Language Options Settings in Windows as a prerequisite before working with
CARE / COACH and Excel Online / COACH Online. In addition, for a successful
application engineering, the controller must be equipped with the appropriate
firmware and XI582 with the appropriate EPROM.

For all settings to be done, please refer to the country and language settings table
that lists the settings for:

• Windows
• CARE / COACH
• Excel Online / COACH Online
• XI852 EPROM
• Controller firmware

For information on coding special characters in Western, Eastern and Turkish


languages, please refer to the character settings tables following the country and
language settings table.

To customize Windows, refer to the procedure following the character settings


tables.

Table 1. HBS Country and Language Settings

Country Windows Version / CARE Country Controllers with Internal Text MMI Controllers with Controllers with XL Online
Regional and Language Code / Location Internal External
Options Settings Selection Graphic MMI XI581/2

XL 40 XL 50 XL 50 XL100/500/800

XL40A2MMI XL50CH XI581/2


XI40AI XL50- MMI-xxxx XL50CY XI581B/2B
(required XL50D XL50TW (required
firmware) XL50A-MMI-xxxx XL50ACH hardware)
XL50A-UMMI-xxxx XL50ACY
(required XL50ATW
firmware) (required
firmware)

Several Arabic Arabic not supported not supported not supported not supported not supported
(not supported)

Australia English (Australia) Australia XL50I207.02C EU50L207.02C or EU50L207.02C XI581B/2B-EU Western


or higher higher or higher

Albania Albanian not supported XL50I207.02C EU50L207.02C or EU50L207.02C XI581B/2B-EU Western


or higher higher or higher

Austria German (Austria) Austria XL50I207.02C EU50L207.02C or EU50L207.02C XI581B/2B-EU Western


or higher higher or higher

Belgium Dutch (Belgium), Belgium XL50I207.02C or EU50L207.02C or EU50L207.02C XI581B/2B-EU Western


French (Belgium) or higher higher or higher

Bulgaria Bulgarian Russia not supported not supported EU50L207.02C XI581B/2B-EU Cyrillic
or higher

Brazil Portuguese (Brazil) Brazil XL50I207.02C EU50L207.02C or EU50L207.02C XI581B/2B-EU Western


or higher higher or higher

Canada English (Canada) Canada XL50I207.02C EU50L207.02C or EU50L207.02C XI581B/2B-EU Western


or higher higher or higher

China Chinese (Simplified) PR China not supported not supported EU50L207.02C XI581B/2B-EU CHINESE_
or higher XI581B/2B-CH BIG5

Croatia Croatian Slovakia XL50I207.02C EU50L207.02C or EU50L207.02C XI581B/2B-EU Central

43 EN2Z-0937GE51 R0518
CARE ENVIRONMENT CARE

Country Windows Version / CARE Country Controllers with Internal Text MMI Controllers with Controllers with XL Online
Regional and Language Code / Location Internal External
Options Settings Selection Graphic MMI XI581/2

XL 40 XL 50 XL 50 XL100/500/800

XL40A2MMI XL50CH XI581/2


XI40AI XL50- MMI-xxxx XL50CY XI581B/2B
(required XL50D XL50TW (required
firmware) XL50A-MMI-xxxx XL50ACH hardware)
XL50A-UMMI-xxxx XL50ACY
(required XL50ATW
firmware) (required
firmware)
or higher higher or higher European

Czech Czech Slovakia XL50I207.02C EU50L207.02C or EU50L207.02C XI581B/2B-EU Central


Republic or higher higher or higher European

Denmark Danish Denmark XL50I207.02C EU50L207.02C or EU50L207.02C XI581B/2B-EU Western


or higher higher or higher

Finland Finnish Finland XL50I207.02C EU50L207.02C or EU50L207.02C XI581B/2B-EU Western


or higher higher or higher

France French France XL50I207.02C EU50L207.02C or EU50L207.02C XI581B/2B-EU Western


or higher higher or higher

Germany German Germany XL50I207.02C EU50L207.02C or EU50L207.02C XI581B/2B-EU Western


or higher higher or higher

Several Hebrew Hebrew XL50I207.02C EU50L207.02C or EU50L207.02C XI581B/2B-EU Western


or higher higher or higher

Hungary Hungarian Slovakia XL50I207.02C EU50L207.02C or EU50L207.02C XI581B/2B-EU Central


or higher higher or higher European

Iceland Icelandic Iceland XL50I207.02C EU50L207.02C or EU50L207.02C XI581B/2B-EU Western


or higher higher or higher

Ireland English (Ireland) Ireland XL50I207.02C EU50L207.02C or EU50L207.02C XI581B/2B-EU Western


or higher higher or higher

Italy Italian Italy XL50I207.02C EU50L207.02C or EU50L207.02C XI581B/2B-EU Western


or higher higher or higher

Japan Japanese Japan not supported not supported not supported XI581B/2B-JP Japanese

Korea Korean Korea not supported not supported not supported not supported Western

Several Several Latin America XL50I207.02C EU50L207.02C or EU50L207.02C XI581B/2B-EU Western


or higher higher or higher

Lithuania Lithuanian not supported not supported not supported EU50L207.02C XI581B/2B-EU Cyrillic
or higher

Macedonia Macedonian Russia not supported not supported EU50L207.02C XI581B/2B-EU Cyrillic
or higher

Mexico Spanish (Mexico) Mexico XL50I207.02C EU50L207.02C or EU50L207.02C XI581B/2B-EU Western


or higher higher or higher

Morocco French France XL50I207.02C EU50L207.02C or EU50L207.02C XI581B/2B-EU Western


or higher higher or higher

Nether- Dutch Netherlands XL50I207.02C or EU50L207.02C or EU50L207.02C XI581B/2B-EU Western


lands higher higher or higher

New English (New Zealand) New Zealand XL50I207.02C EU50L207.02C or EU50L207.02C XI581B/2B-EU Western
Zealand or higher higher or higher

Norway Norwegian Norway XL50I207.02C EU50L207.02C or EU50L207.02C XI581B/2B-EU Western


or higher higher or higher

Poland Polish Slovakia XL50I207.02C EU50L207.02C or EU50L207.02C XI581B/2B-EU Central


or higher higher or higher European

Portugal Portuguese Portugal XL50I207.02C EU50L207.02C or EU50L207.02C XI581B/2B-EU Western


or higher higher or higher

Romania Romanian Slovakia XL50I207.02C EU50L207.02C or EU50L207.02C XI581B/2B-EU Central

EN2Z-0937GE51 R0518 44
CARE CUSTOMIZE WINDOWS DEFAULT REGIONAL AND LANGUAGE SETTINGS

Country Windows Version / CARE Country Controllers with Internal Text MMI Controllers with Controllers with XL Online
Regional and Language Code / Location Internal External
Options Settings Selection Graphic MMI XI581/2

XL 40 XL 50 XL 50 XL100/500/800

XL40A2MMI XL50CH XI581/2


XI40AI XL50- MMI-xxxx XL50CY XI581B/2B
(required XL50D XL50TW (required
firmware) XL50A-MMI-xxxx XL50ACH hardware)
XL50A-UMMI-xxxx XL50ACY
(required XL50ATW
firmware) (required
firmware)
or higher higher or higher European

Russia Russian Russia not supported not supported EU50L207.02C XI581B/2B-EU Cyrillic
or higher

Serbia Serbian (Latin, Bosnia not supported not supported not supported EU50L207.02C XI581B/2B-EU Cyrillic
and Herzegovina) or higher

Slovakia Slovak Slovakia XL50I207.02C or EU50L207.02C or EU50L207.02C XI581B/2B-EU Central


higher higher or higher European

Slovenia Slovenian Slovakia XL50I207.02C EU50L207.02C or EU50L207.02C XI581B/2B-EU Central


or higher higher or higher European

Spain Spanish Spain XL50I207.02C EU50L207.02C or EU50L207.02C XI581B/2B-EU Western


or higher higher or higher

Sweden Swedish Sweden XL50I207.02C EU50L207.02C or EU50L207.02C XI581B/2B-EU Western


or higher higher or higher

Switzerland German (Switzerland), Switzerland XL50I207.02C EU50L207.02C or EU50L207.02C XI581B/2B-EU Western


French (Switzerland), or higher higher or higher
Italian (Switzerland)

Taiwan Chinese (Taiwan) Taiwan not supported not supported TW50L207.02C XI581B/2B-TW Thai
or higher

Tunisia French France XL50I207.02C EU50L207.02C or EU50L207.02C XI581B/2B-EU Western


or higher higher or higher

Turkey Turkish Turkey XL50I207.02C EU50L207.02C or EU50L207.02C XI581B/2B-EU Turkish


or higher higher or higher

U.A.E. Arabic (U.A.E.) Arabic not supported not supported not supported not supported not supported
(not supported)

Ukraine Ukrainian Russia not supported not supported EU50L207.02C XI581B/2B-EU Cyrillic
or higher

United English (United Kingdom) United Kingdom XL50I207.02C EU50L207.02C or EU50L207.02C XI581B/2B-EU Western
Kingdom or higher higher or higher

United English United States XL50I207.02C or EU50L207.02C or EU50L207.02C XI581B/2B-EU Western


States higher higher or higher XI581B/2B-TW
TW50L207.02C or TW50L207.02C XI581B/2B-CH
higher or higher XI581B/2B-JP
XL50L207.02C or XL50L207.02C XI581B/2B-CY
higher or higher

Table 2. CentraLine Country and Language Settings

Country Windows Version / COACH Controllers with Internal Text MMI Controllers with Controllers with COACH
Regional and Language Country Internal External Online
Options Settings Selection Graphic MMI CLMMI00N2x

Tiger Panther Panther Lion

45 EN2Z-0937GE51 R0518
CARE ENVIRONMENT CARE

CLTG38L11 CLPA13LC1x CLPA13LC2x CLMMI00N2x


CLTG00MMI CLPA13LM1x CLPA13LM2x (required
(required CLPA21CM1x CLPA21LC2x hardware)
firmware) CLPA21LC1x CLPA21LM2x
CLPA21LM1x (required
(required firmware)
firmware)

Several Arabic not supported not supported not supported not supported not supported not supported

Australia English (Australia) Australia XL50I207.02C EU50L207.02C or EU50L207.02C XI581B/2B-EU Western


or higher higher or higher

Albania Albanian Albanian XL50I207.02C EU50L207.02C or EU50L207.02C XI581B/2B-EU Western


or higher higher or higher

Austria German (Austria) Austria XL50I207.02C EU50L207.02C or EU50L207.02C XI581B/2B-EU Western


or higher higher or higher

Belgium Dutch (Belgium), Belgium XL50I207.02C or EU50L207.02C or EU50L207.02C XI581B/2B-EU Western


French (Belgium) or higher higher or higher

Bulgaria Bulgarian Bulgaria not supported not supported EU50L207.02C XI581B/2B-EU Cyrillic
or higher

Brazil Portuguese (Brazil) not supported not supported not supported not supported not supported not supported

Canada English (Canada) not supported not supported not supported not supported not supported not supported

China Chinese (Simplified) not supported not supported not supported not supported not supported not supported

Croatia Croatian Croatia XL50I207.02C EU50L207.02C or EU50L207.02C XI581B/2B-EU Central


or higher higher or higher European

Czech Czech Czech Republic XL50I207.02C EU50L207.02C or EU50L207.02C XI581B/2B-EU Central


Republic or higher higher or higher European

Denmark Danish Denmark XL50I207.02C EU50L207.02C or EU50L207.02C XI581B/2B-EU Western


or higher higher or higher

Finland Finnish Finland XL50I207.02C EU50L207.02C or EU50L207.02C XI581B/2B-EU Western


or higher higher or higher

France French France XL50I207.02C EU50L207.02C or EU50L207.02C XI581B/2B-EU Western


or higher higher or higher

Germany German Germany XL50I207.02C EU50L207.02C or EU50L207.02C XI581B/2B-EU Western


or higher higher or higher

Several Hebrew as desired XL50I207.02C EU50L207.02C or EU50L207.02C XI581B/2B-EU Western


or higher higher or higher

Hungary Hungarian Hungary XL50I207.02C EU50L207.02C or EU50L207.02C XI581B/2B-EU Central


or higher higher or higher European

Iceland Icelandic Iceland XL50I207.02C EU50L207.02C or EU50L207.02C XI581B/2B-EU Western


or higher higher or higher

Ireland English (Ireland) United Kingdom XL50I207.02C EU50L207.02C or EU50L207.02C XI581B/2B-EU Western
or higher higher or higher

Italy Italian Italy XL50I207.02C EU50L207.02C or EU50L207.02C XI581B/2B-EU Western


or higher higher or higher

Japan Japanese not supported not supported not supported not supported not supported not supported

Korea Korean not supported not supported not supported not supported not supported not supported

Lithuania Lithuanian Lithuania not supported not supported EU50L207.02C XI581B/2B-EU Cyrillic
or higher

Macedonia Macedonian Macedonia not supported not supported EU50L207.02C XI581B/2B-EU Cyrillic
or higher

Mexico Spanish (Mexico) not supported not supported not supported not supported not supported not supported

Morocco French Morocco XL50I207.02C EU50L207.02C or EU50L207.02C XI581B/2B-EU Western


or higher higher or higher

Nether- Dutch Netherlands XL50I207.02C or EU50L207.02C or EU50L207.02C XI581B/2B-EU Western


lands higher higher or higher

EN2Z-0937GE51 R0518 46
CARE CUSTOMIZE WINDOWS DEFAULT REGIONAL AND LANGUAGE SETTINGS

Country Windows Version / COACH Controllers with Internal Text MMI Controllers with Controllers with COACH
Regional and Language Country Internal External Online
Options Settings Selection Graphic MMI CLMMI00N2x

Tiger Panther Panther Lion

CLTG38L11 CLPA13LC1x CLPA13LC2x CLMMI00N2x


CLTG00MMI CLPA13LM1x CLPA13LM2x (required
(required CLPA21CM1x CLPA21LC2x hardware)
firmware) CLPA21LC1x CLPA21LM2x
CLPA21LM1x (required
(required firmware)
firmware)

New English (New Zealand) not supported not supported not supported not supported not supported not supported
Zealand

Norway Norwegian Norway XL50I207.02C EU50L207.02C or EU50L207.02C XI581B/2B-EU Western


or higher higher or higher

Poland Polish Poland XL50I207.02C EU50L207.02C or EU50L207.02C XI581B/2B-EU Central


or higher higher or higher European

Portugal Portuguese Portugal XL50I207.02C EU50L207.02C or EU50L207.02C XI581B/2B-EU Western


or higher higher or higher

Romania Romanian Romania XL50I207.02C EU50L207.02C or EU50L207.02C XI581B/2B-EU Central


or higher higher or higher European

Russia Russian Russia not supported not supported EU50L207.02C XI581B/2B-EU Cyrillic
or higher

Serbia Serbian (Latin, Bosnia Serbia not supported not supported EU50L207.02C XI581B/2B-EU Cyrillic
and Herzegovina) or higher

Slovakia Slovak Slovakia EU50L207.02C EU50L207.02C or EU50L207.02C XI581B/2B-EU Central


or higher higher or higher European

Slovenia Slovenian Slovenia XL50I207.02C EU50L207.02C or EU50L207.02C XI581B/2B-EU Central


or higher higher or higher European

Spain Spanish Spain XL50I207.02C EU50L207.02C or EU50L207.02C XI581B/2B-EU Western


or higher higher or higher

Sweden Swedish Sweden XL50I207.02C EU50L207.02C or EU50L207.02C XI581B/2B-EU Western


or higher higher or higher

Switzerland German (Switzerland), Switzerland XL50I207.02C EU50L207.02C or EU50L207.02C XI581B/2B-EU Western


French (Switzerland), France or higher higher or higher
Italian (Switzerland) not supported

Taiwan Chinese (Taiwan) not supported not supported not supported not supported not supported not supported

Tunisia French Tunisia XL50I207.02C EU50L207.02C or EU50L207.02C XI581B/2B-EU Western


or higher higher or higher

Turkey Turkish Turkey XL50I207.02C EU50L207.02C or EU50L207.02C XI581B/2B-EU Turkish


or higher higher or higher

U.A.E. Arabic (U.A.E.) U.A.E. not supported not supported not supported not supported not supported
(not supported)

Ukraine Ukrainian Ukraine not supported not supported EU50L207.02C XI581B/2B-EU Cyrillic
or higher

United English (United Kingdom) United Kingdom XL50I207.02C EU50L207.02C or EU50L207.02C XI581B/2B-EU Western
Kingdom or higher higher or higher

United English not supported not supported not supported not supported not supported not supported
States

Table 3. Character Settings (Western Europe)

Hex
Dec Char Unicode ISO/IEC 10646-1:2000 Character Name

20 32 32 SPACE

47 EN2Z-0937GE51 R0518
CARE ENVIRONMENT CARE

Hex
Dec Char Unicode ISO/IEC 10646-1:2000 Character Name

23 35 # 35 NUMBER SIGN

24 36 $ 36 DOLLAR SIGN

25 37 % 37 PERCENT SIGN

26 38 & 38 AMPERSAND

27 39 ' 39 APOSTROPHE

28 40 ( 40 LEFT PARENTHESIS

29 41 ) 41 RIGHT PARENTHESIS

2E 46 . 46 FULL STOP

30 48 0 48 DIGIT ZERO

31 49 1 49 DIGIT ONE

32 50 2 50 DIGIT TWO

33 51 3 51 DIGIT THREE

34 52 4 52 DIGIT FOUR

35 53 5 53 DIGIT FIVE

36 54 6 54 DIGIT SIX

37 55 7 55 DIGIT SEVEN

38 56 8 56 DIGIT EIGHT

39 57 9 57 DIGIT NINE

3A 58 : 58 COLON

40 64 @ 64 COMMERCIAL AT

41 65 A 65 LATIN CAPITAL LETTER A

42 66 B 66 LATIN CAPITAL LETTER B

43 67 C 67 LATIN CAPITAL LETTER C

44 68 D 68 LATIN CAPITAL LETTER D

45 69 E 69 LATIN CAPITAL LETTER E

46 70 F 70 LATIN CAPITAL LETTER F

47 71 G 71 LATIN CAPITAL LETTER G

48 72 H 72 LATIN CAPITAL LETTER H

49 73 I 73 LATIN CAPITAL LETTER I

4A 74 J 74 LATIN CAPITAL LETTER J

4B 75 K 75 LATIN CAPITAL LETTER K

4C 76 L 76 LATIN CAPITAL LETTER L

4D 77 M 77 LATIN CAPITAL LETTER M

4E 78 N 78 LATIN CAPITAL LETTER N

4F 79 O 79 LATIN CAPITAL LETTER O

50 80 P 80 LATIN CAPITAL LETTER P

EN2Z-0937GE51 R0518 48
CARE CUSTOMIZE WINDOWS DEFAULT REGIONAL AND LANGUAGE SETTINGS

Hex
Dec Char Unicode ISO/IEC 10646-1:2000 Character Name

51 81 Q 81 LATIN CAPITAL LETTER Q

52 82 R 82 LATIN CAPITAL LETTER R

53 83 S 83 LATIN CAPITAL LETTER S

54 84 T 84 LATIN CAPITAL LETTER T

55 85 U 85 LATIN CAPITAL LETTER U

56 86 V 86 LATIN CAPITAL LETTER V

57 87 W 87 LATIN CAPITAL LETTER W

58 88 X 88 LATIN CAPITAL LETTER X

59 89 Y 89 LATIN CAPITAL LETTER Y

5A 90 Z 90 LATIN CAPITAL LETTER Z

5F 95 _ 95 LOW LINE

61 97 a 97 LATIN SMALL LETTER A

62 98 b 98 LATIN SMALL LETTER B

63 99 c 99 LATIN SMALL LETTER C

64 100 d 100 LATIN SMALL LETTER D

65 101 e 101 LATIN SMALL LETTER E

66 102 f 102 LATIN SMALL LETTER F

67 103 g 103 LATIN SMALL LETTER G

68 104 h 104 LATIN SMALL LETTER H

69 105 i 105 LATIN SMALL LETTER I

6A 106 j 106 LATIN SMALL LETTER J

6B 107 k 107 LATIN SMALL LETTER K

6C 108 l 108 LATIN SMALL LETTER L

6D 109 m 109 LATIN SMALL LETTER M

6E 110 n 110 LATIN SMALL LETTER N

6F 111 o 111 LATIN SMALL LETTER O

70 112 p 112 LATIN SMALL LETTER P

71 113 q 113 LATIN SMALL LETTER Q

72 114 r 114 LATIN SMALL LETTER R

73 115 s 115 LATIN SMALL LETTER S

74 116 t 116 LATIN SMALL LETTER T

75 117 u 117 LATIN SMALL LETTER U

76 118 v 118 LATIN SMALL LETTER V

77 119 w 119 LATIN SMALL LETTER W

78 120 x 120 LATIN SMALL LETTER X

79 121 y 121 LATIN SMALL LETTER Y

49 EN2Z-0937GE51 R0518
CARE ENVIRONMENT CARE

Hex
Dec Char Unicode ISO/IEC 10646-1:2000 Character Name

7A 122 z 122 LATIN SMALL LETTER Z

7E 126 ~ 126 TILDE

80 128 Ç 199 LATIN CAPITAL LETTER C WITH CEDILLA

81 129 ü 252 LATIN SMALL LETTER U WITH DIAERESIS

82 130 é 233 LATIN SMALL LETTER E WITH ACUTE

83 131 â 226 LATIN SMALL LETTER A WITH CIRCUMFLEX

84 132 ä 228 LATIN SMALL LETTER A WITH DIAERESIS

85 133 à 224 LATIN SMALL LETTER A WITH GRAVE

86 134 å 229 LATIN SMALL LETTER A WITH RING ABOVE

87 135 ç 231 LATIN SMALL LETTER C WITH CEDILLA

88 136 ê 234 LATIN SMALL LETTER E WITH CIRCUMFLEX

89 137 ë 235 LATIN SMALL LETTER E WITH DIAERESIS

8A 138 è 232 LATIN SMALL LETTER E WITH GRAVE

8B 139 ï 239 LATIN SMALL LETTER I WITH DIAERESIS

8C 140 î 238 LATIN SMALL LETTER I WITH CIRCUMFLEX

8D 141 ì 236 LATIN SMALL LETTER I WITH GRAVE

8E 142 Ä 196 LATIN CAPITAL LETTER A WITH DIAERESIS

8F 143 Å 197 LATIN CAPITAL LETTER A WITH RING ABOVE

90 144 É 201 LATIN CAPITAL LETTER E WITH ACUTE

91 145 æ 230 LATIN SMALL LETTER AE

92 146 Æ 198 LATIN CAPITAL LETTER AE

93 147 ô 244 LATIN SMALL LETTER O WITH CIRCUMFLEX

94 148 ö 246 LATIN SMALL LETTER O WITH DIAERESIS

95 149 ò 242 LATIN SMALL LETTER O WITH GRAVE

96 150 û 251 LATIN SMALL LETTER U WITH CIRCUMFLEX

97 151 ù 249 LATIN SMALL LETTER U WITH GRAVE

98 152 ÿ 255 LATIN SMALL LETTER Y WITH DIAERESIS

99 153 Ö 214 LATIN CAPITAL LETTER O WITH DIAERESIS

9A 154 Ü 220 LATIN CAPITAL LETTER U WITH DIAERESIS

9B 155 ø 248 LATIN SMALL LETTER O WITH STROKE

9D 157 Ø 216 LATIN CAPITAL LETTER O WITH STROKE

9F 159 ƒ 402 LATIN SMALL LETTER F WITH HOOK

A0 160 á 225 LATIN SMALL LETTER A WITH ACUTE

A1 161 í 237 LATIN SMALL LETTER I WITH ACUTE

A2 162 ó 243 LATIN SMALL LETTER O WITH ACUTE

A3 163 ú 250 LATIN SMALL LETTER U WITH ACUTE

EN2Z-0937GE51 R0518 50
CARE CUSTOMIZE WINDOWS DEFAULT REGIONAL AND LANGUAGE SETTINGS

Hex
Dec Char Unicode ISO/IEC 10646-1:2000 Character Name

A4 164 ñ 241 LATIN SMALL LETTER N WITH TILDE

A5 165 Ñ 209 LATIN CAPITAL LETTER N WITH TILDE

A8 168 ¿ 191 INVERTED QUESTION MARK

B5 181 Á 193 LATIN CAPITAL LETTER A WITH ACUTE

B6 182 Â 194 LATIN CAPITAL LETTER A WITH CIRCUMFLEX

B7 183 À 192 LATIN CAPITAL LETTER A WITH GRAVE

C6 198 ã 227 LATIN SMALL LETTER A WITH TILDE

C7 199 Ã 195 LATIN CAPITAL LETTER A WITH TILDE

D0 208 ð 240 LATIN SMALL LETTER ETH

D1 209 Ð 208 LATIN CAPITAL LETTER ETH

D2 210 Ê 202 LATIN CAPITAL LETTER E WITH CIRCUMFLEX

D3 211 Ë 203 LATIN CAPITAL LETTER E WITH DIAERESIS

D4 212 È 200 LATIN CAPITAL LETTER E WITH GRAVE

D5 213 ı 305 LATIN SMALL LETTER DOTLESS I

D6 214 Í 205 LATIN CAPITAL LETTER I WITH ACUTE

D7 215 Î 206 LATIN CAPITAL LETTER I WITH CIRCUMFLEX

D8 216 Ï 207 LATIN CAPITAL LETTER I WITH DIAERESIS

DE 222 Ì 204 LATIN CAPITAL LETTER I WITH GRAVE

E0 224 Ó 211 LATIN CAPITAL LETTER O WITH ACUTE

E1 225 ß 223 LATIN SMALL LETTER SHARP S

E2 226 Ô 212 LATIN CAPITAL LETTER O WITH CIRCUMFLEX

E3 227 Ò 210 LATIN CAPITAL LETTER O WITH GRAVE

E4 228 õ 245 LATIN SMALL LETTER O WITH TILDE

E5 229 Õ 213 LATIN CAPITAL LETTER O WITH TILDE

E6 230 µ 181 MICRO SIGN

E7 231 þ 254 LATIN SMALL LETTER THORN

E8 232 Þ 222 LATIN CAPITAL LETTER THORN

E9 233 Ú 218 LATIN CAPITAL LETTER U WITH ACUTE

EA 234 Û 219 LATIN CAPITAL LETTER U WITH CIRCUMFLEX

EB 235 Ù 217 LATIN CAPITAL LETTER U WITH GRAVE

EC 236 ý 253 LATIN SMALL LETTER Y WITH ACUTE

ED 237 Ý 221 LATIN CAPITAL LETTER Y WITH ACUTE

EF 239 ´ 180 ACUTE ACCENT

F8 248 ° 176 DEGREE SIGN

Table 4. Character Settings (Eastern Europe)

51 EN2Z-0937GE51 R0518
CARE ENVIRONMENT CARE

Hex
Dec Char Unicode ISO/IEC 10646-1:2000 Character Name

20 32 32 SPACE

23 35 # 35 NUMBER SIGN

24 36 $ 36 DOLLAR SIGN

25 37 % 37 PERCENT SIGN

26 38 & 38 AMPERSAND

27 39 ' 39 APOSTROPHE

28 40 ( 40 LEFT PARENTHESIS

29 41 ) 41 RIGHT PARENTHESIS

2E 46 . 46 FULL STOP

30 48 0 48 DIGIT ZERO

31 49 1 49 DIGIT ONE

32 50 2 50 DIGIT TWO

33 51 3 51 DIGIT THREE

34 52 4 52 DIGIT FOUR

35 53 5 53 DIGIT FIVE

36 54 6 54 DIGIT SIX

37 55 7 55 DIGIT SEVEN

38 56 8 56 DIGIT EIGHT

39 57 9 57 DIGIT NINE

3A 58 : 58 COLON

40 64 @ 64 COMMERCIAL AT

41 65 A 65 LATIN CAPITAL LETTER A

42 66 B 66 LATIN CAPITAL LETTER B

43 67 C 67 LATIN CAPITAL LETTER C

44 68 D 68 LATIN CAPITAL LETTER D

45 69 E 69 LATIN CAPITAL LETTER E

46 70 F 70 LATIN CAPITAL LETTER F

47 71 G 71 LATIN CAPITAL LETTER G

48 72 H 72 LATIN CAPITAL LETTER H

49 73 I 73 LATIN CAPITAL LETTER I

4A 74 J 74 LATIN CAPITAL LETTER J

4B 75 K 75 LATIN CAPITAL LETTER K

4C 76 L 76 LATIN CAPITAL LETTER L

4D 77 M 77 LATIN CAPITAL LETTER M

4E 78 N 78 LATIN CAPITAL LETTER N

EN2Z-0937GE51 R0518 52
CARE CUSTOMIZE WINDOWS DEFAULT REGIONAL AND LANGUAGE SETTINGS

Hex
Dec Char Unicode ISO/IEC 10646-1:2000 Character Name

4F 79 O 79 LATIN CAPITAL LETTER O

50 80 P 80 LATIN CAPITAL LETTER P

51 81 Q 81 LATIN CAPITAL LETTER Q

52 82 R 82 LATIN CAPITAL LETTER R

53 83 S 83 LATIN CAPITAL LETTER S

54 84 T 84 LATIN CAPITAL LETTER T

55 85 U 85 LATIN CAPITAL LETTER U

56 86 V 86 LATIN CAPITAL LETTER V

57 87 W 87 LATIN CAPITAL LETTER W

58 88 X 88 LATIN CAPITAL LETTER X

59 89 Y 89 LATIN CAPITAL LETTER Y

5A 90 Z 90 LATIN CAPITAL LETTER Z

5F 95 _ 95 LOW LINE

61 97 a 97 LATIN SMALL LETTER A

62 98 b 98 LATIN SMALL LETTER B

63 99 c 99 LATIN SMALL LETTER C

64 100 d 100 LATIN SMALL LETTER D

65 101 e 101 LATIN SMALL LETTER E

66 102 f 102 LATIN SMALL LETTER F

67 103 g 103 LATIN SMALL LETTER G

68 104 h 104 LATIN SMALL LETTER H

69 105 i 105 LATIN SMALL LETTER I

6A 106 j 106 LATIN SMALL LETTER J

6B 107 k 107 LATIN SMALL LETTER K

6C 108 l 108 LATIN SMALL LETTER L

6D 109 m 109 LATIN SMALL LETTER M

6E 110 n 110 LATIN SMALL LETTER N

6F 111 o 111 LATIN SMALL LETTER O

70 112 p 112 LATIN SMALL LETTER P

71 113 q 113 LATIN SMALL LETTER Q

72 114 r 114 LATIN SMALL LETTER R

73 115 s 115 LATIN SMALL LETTER S

74 116 t 116 LATIN SMALL LETTER T

75 117 u 117 LATIN SMALL LETTER U

76 118 v 118 LATIN SMALL LETTER V

77 119 w 119 LATIN SMALL LETTER W

53 EN2Z-0937GE51 R0518
CARE ENVIRONMENT CARE

Hex
Dec Char Unicode ISO/IEC 10646-1:2000 Character Name

78 120 x 120 LATIN SMALL LETTER X

79 121 y 121 LATIN SMALL LETTER Y

7A 122 z 122 LATIN SMALL LETTER Z

7E 126 ~ 126 TILDE

80 128 Ç 199 LATIN CAPITAL LETTER C WITH CEDILLA

81 129 ü 252 LATIN SMALL LETTER U WITH DIAERESIS

82 130 é 233 LATIN SMALL LETTER E WITH ACUTE

83 131 â 226 LATIN SMALL LETTER A WITH CIRCUMFLEX

84 132 ä 228 LATIN SMALL LETTER A WITH DIAERESIS

85 133 ů 367 LATIN SMALL LETTER U WITH RING ABOVE

86 134 ć 263 LATIN SMALL LETTER C WITH ACUTE

87 135 ç 231 LATIN SMALL LETTER C WITH CEDILLA

88 136 ł 322 LATIN SMALL LETTER L WITH STROKE

89 137 ë 235 LATIN SMALL LETTER E WITH DIAERESIS


LATIN CAPITAL LETTER O WITH DOUBLE
8A 138 Ő 336
ACUTE
8B 139 ő 337 LATIN SMALL LETTER O WITH DOUBLE ACUTE

8C 140 î 238 LATIN SMALL LETTER I WITH CIRCUMFLEX

8D 141 Ź 377 LATIN CAPITAL LETTER Z WITH ACUTE

8E 142 Ä 196 LATIN CAPITAL LETTER A WITH DIAERESIS

8F 143 Ć 262 LATIN CAPITAL LETTER C WITH ACUTE

90 144 É 201 LATIN CAPITAL LETTER E WITH ACUTE

91 145 Ĺ 313 LATIN CAPITAL LETTER L WITH ACUTE

92 146 ĺ 314 LATIN SMALL LETTER L WITH ACUTE

93 147 ô 244 LATIN SMALL LETTER O WITH CIRCUMFLEX

94 148 ö 246 LATIN SMALL LETTER O WITH DIAERESIS

95 149 Ľ 317 LATIN CAPITAL LETTER L WITH CARON

96 150 ľ 318 LATIN SMALL LETTER L WITH CARON

97 151 Ś 346 LATIN CAPITAL LETTER S WITH ACUTE

98 152 ś 347 LATIN SMALL LETTER S WITH ACUTE

99 153 Ö 214 LATIN CAPITAL LETTER O WITH DIAERESIS

9A 154 Ü 220 LATIN CAPITAL LETTER U WITH DIAERESIS

9B 155 Ť 356 LATIN CAPITAL LETTER T WITH CARON

9C 156 ť 357 LATIN SMALL LETTER T WITH CARON

9D 157 Ł 321 LATIN CAPITAL LETTER L WITH STROKE

9F 159 č 269 LATIN SMALL LETTER C WITH CARON

EN2Z-0937GE51 R0518 54
CARE CUSTOMIZE WINDOWS DEFAULT REGIONAL AND LANGUAGE SETTINGS

Hex
Dec Char Unicode ISO/IEC 10646-1:2000 Character Name

A0 160 á 225 LATIN SMALL LETTER A WITH ACUTE

A1 161 í 237 LATIN SMALL LETTER I WITH ACUTE

A2 162 ó 243 LATIN SMALL LETTER O WITH ACUTE

A3 163 ú 250 LATIN SMALL LETTER U WITH ACUTE

A4 164 Ą 260 LATIN CAPITAL LETTER A WITH OGONEK

A5 165 ą 261 LATIN SMALL LETTER A WITH OGONEK

A6 166 Ž 381 LATIN CAPITAL LETTER Z WITH CARON

A7 167 ž 382 LATIN SMALL LETTER Z WITH CARON

A8 168 Ę 280 LATIN CAPITAL LETTER E WITH OGONEK

A9 169 ę 281 LATIN SMALL LETTER E WITH OGONEK

AB 171 ź 378 LATIN SMALL LETTER Z WITH ACUTE

AC 172 Č 268 LATIN CAPITAL LETTER C WITH CARON

AD 173 ş 351 LATIN SMALL LETTER S WITH CEDILLA

B5 181 Á 193 LATIN CAPITAL LETTER A WITH ACUTE

B6 182 Â 194 LATIN CAPITAL LETTER A WITH CIRCUMFLEX

B7 183 Ě 282 LATIN CAPITAL LETTER E WITH CARON

B8 184 Ş 350 LATIN CAPITAL LETTER S WITH CEDILLA

BD 189 Ż 379 LATIN CAPITAL LETTER Z WITH DOT ABOVE

BE 190 ż 380 LATIN SMALL LETTER Z WITH DOT ABOVE

C6 198 Ă 258 LATIN CAPITAL LETTER A WITH BREVE

C7 199 ă 259 LATIN SMALL LETTER A WITH BREVE

D0 208 đ 273 LATIN SMALL LETTER D WITH STROKE

D1 209 Đ 272 LATIN CAPITAL LETTER D WITH STROKE

D2 210 Ď 270 LATIN CAPITAL LETTER D WITH CARON

D3 211 Ë 203 LATIN CAPITAL LETTER E WITH DIAERESIS

D4 212 ď 271 LATIN SMALL LETTER D WITH CARON

D5 213 Ň 327 LATIN CAPITAL LETTER N WITH CARON

D6 214 Í 205 LATIN CAPITAL LETTER I WITH ACUTE

D7 215 Î 206 LATIN CAPITAL LETTER I WITH CIRCUMFLEX

D8 216 ě 283 LATIN SMALL LETTER E WITH CARON

DD 221 Ţ 354 LATIN CAPITAL LETTER T WITH CEDILLA

DE 222 Ů 366 LATIN CAPITAL LETTER U WITH RING ABOVE

E0 224 Ó 211 LATIN CAPITAL LETTER O WITH ACUTE

E1 225 ß 223 LATIN SMALL LETTER SHARP S

E2 226 Ô 212 LATIN CAPITAL LETTER O WITH CIRCUMFLEX

E3 227 Ń 323 LATIN CAPITAL LETTER N WITH ACUTE

55 EN2Z-0937GE51 R0518
CARE ENVIRONMENT CARE

Hex
Dec Char Unicode ISO/IEC 10646-1:2000 Character Name

E4 228 ń 324 LATIN SMALL LETTER N WITH ACUTE

E5 229 ň 328 LATIN SMALL LETTER N WITH CARON

E6 230 Š 352 LATIN CAPITAL LETTER S WITH CARON

E7 231 š 353 LATIN SMALL LETTER S WITH CARON

E8 232 Ŕ 340 LATIN CAPITAL LETTER R WITH ACUTE

E9 233 Ú 218 LATIN CAPITAL LETTER U WITH ACUTE

EA 234 ŕ 341 LATIN SMALL LETTER R WITH ACUTE


LATIN CAPITAL LETTER U WITH DOUBLE
EB 235 Ű 368
ACUTE
EC 236 ý 253 LATIN SMALL LETTER Y WITH ACUTE

ED 237 Ý 221 LATIN CAPITAL LETTER Y WITH ACUTE

EE 238 ţ 355 LATIN SMALL LETTER T WITH CEDILLA

F8 248 ° 176 DEGREE SIGN

FB 251 ű 369 LATIN SMALL LETTER U WITH DOUBLE ACUTE

FC 252 Ř 344 LATIN CAPITAL LETTER R WITH CARON

FD 253 ř 345 LATIN SMALL LETTER R WITH CARON

Table 5. Character Settings (Turkey)

Hex
Dec Char Unicode ISO/IEC 10646-1:2000 Character Name

20 32 32 SPACE

23 35 # 35 NUMBER SIGN

24 36 $ 36 DOLLAR SIGN

25 37 % 37 PERCENT SIGN

26 38 & 38 AMPERSAND

27 39 ' 39 APOSTROPHE

28 40 ( 40 LEFT PARENTHESIS

29 41 ) 41 RIGHT PARENTHESIS

2E 46 . 46 FULL STOP

30 48 0 48 DIGIT ZERO

31 49 1 49 DIGIT ONE

32 50 2 50 DIGIT TWO

33 51 3 51 DIGIT THREE

34 52 4 52 DIGIT FOUR

35 53 5 53 DIGIT FIVE

36 54 6 54 DIGIT SIX

37 55 7 55 DIGIT SEVEN

EN2Z-0937GE51 R0518 56
CARE CUSTOMIZE WINDOWS DEFAULT REGIONAL AND LANGUAGE SETTINGS

Hex
Dec Char Unicode ISO/IEC 10646-1:2000 Character Name

38 56 8 56 DIGIT EIGHT

39 57 9 57 DIGIT NINE

3A 58 : 58 COLON

40 64 @ 64 COMMERCIAL AT

41 65 A 65 LATIN CAPITAL LETTER A

42 66 B 66 LATIN CAPITAL LETTER B

43 67 C 67 LATIN CAPITAL LETTER C

44 68 D 68 LATIN CAPITAL LETTER D

45 69 E 69 LATIN CAPITAL LETTER E

46 70 F 70 LATIN CAPITAL LETTER F

47 71 G 71 LATIN CAPITAL LETTER G

48 72 H 72 LATIN CAPITAL LETTER H

49 73 I 73 LATIN CAPITAL LETTER I

4A 74 J 74 LATIN CAPITAL LETTER J

4B 75 K 75 LATIN CAPITAL LETTER K

4C 76 L 76 LATIN CAPITAL LETTER L

4D 77 M 77 LATIN CAPITAL LETTER M

4E 78 N 78 LATIN CAPITAL LETTER N

4F 79 O 79 LATIN CAPITAL LETTER O

50 80 P 80 LATIN CAPITAL LETTER P

51 81 Q 81 LATIN CAPITAL LETTER Q

52 82 R 82 LATIN CAPITAL LETTER R

53 83 S 83 LATIN CAPITAL LETTER S

54 84 T 84 LATIN CAPITAL LETTER T

55 85 U 85 LATIN CAPITAL LETTER U

56 86 V 86 LATIN CAPITAL LETTER V

57 87 W 87 LATIN CAPITAL LETTER W

58 88 X 88 LATIN CAPITAL LETTER X

59 89 Y 89 LATIN CAPITAL LETTER Y

5A 90 Z 90 LATIN CAPITAL LETTER Z

5F 95 _ 95 LOW LINE

61 97 a 97 LATIN SMALL LETTER A

62 98 b 98 LATIN SMALL LETTER B

63 99 c 99 LATIN SMALL LETTER C

64 100 d 100 LATIN SMALL LETTER D

65 101 e 101 LATIN SMALL LETTER E

57 EN2Z-0937GE51 R0518
CARE ENVIRONMENT CARE

Hex
Dec Char Unicode ISO/IEC 10646-1:2000 Character Name

66 102 f 102 LATIN SMALL LETTER F

67 103 g 103 LATIN SMALL LETTER G

68 104 h 104 LATIN SMALL LETTER H

69 105 i 105 LATIN SMALL LETTER I

6A 106 j 106 LATIN SMALL LETTER J

6B 107 k 107 LATIN SMALL LETTER K

6C 108 l 108 LATIN SMALL LETTER L

6D 109 m 109 LATIN SMALL LETTER M

6E 110 n 110 LATIN SMALL LETTER N

6F 111 o 111 LATIN SMALL LETTER O

70 112 p 112 LATIN SMALL LETTER P

71 113 q 113 LATIN SMALL LETTER Q

72 114 r 114 LATIN SMALL LETTER R

73 115 s 115 LATIN SMALL LETTER S

74 116 t 116 LATIN SMALL LETTER T

75 117 u 117 LATIN SMALL LETTER U

76 118 v 118 LATIN SMALL LETTER V

77 119 w 119 LATIN SMALL LETTER W

78 120 x 120 LATIN SMALL LETTER X

79 121 y 121 LATIN SMALL LETTER Y

7A 122 z 122 LATIN SMALL LETTER Z

7E 126 ~ 126 TILDE

80 128 Ç 199 LATIN CAPITAL LETTER C WITH CEDILLA

81 129 ü 252 LATIN SMALL LETTER U WITH DIAERESIS

82 130 é 233 LATIN SMALL LETTER E WITH ACUTE

83 131 âyyy 226 LATIN SMALL LETTER A WITH CIRCUMFLEX

84 132 ä 228 LATIN SMALL LETTER A WITH DIAERESIS

85 133 à 224 LATIN SMALL LETTER A WITH GRAVE

86 134 å 229 LATIN SMALL LETTER A WITH RING ABOVE

87 135 ç 231 LATIN SMALL LETTER C WITH CEDILLA

88 136 ê 234 LATIN SMALL LETTER E WITH CIRCUMFLEX

89 137 ë 235 LATIN SMALL LETTER E WITH DIAERESIS

8A 138 è 232 LATIN SMALL LETTER E WITH GRAVE

8B 139 ï 239 LATIN SMALL LETTER I WITH DIAERESIS

8C 140 î 238 LATIN SMALL LETTER I WITH CIRCUMFLEX

8D 141 ı 305 LATIN SMALL LETTER DOTLESS I

EN2Z-0937GE51 R0518 58
CARE CUSTOMIZE WINDOWS DEFAULT REGIONAL AND LANGUAGE SETTINGS

Hex
Dec Char Unicode ISO/IEC 10646-1:2000 Character Name

8E 142 Ä 196 LATIN CAPITAL LETTER A WITH DIAERESIS

8F 143 Å 197 LATIN CAPITAL LETTER A WITH RING ABOVE

90 144 É 201 LATIN CAPITAL LETTER E WITH ACUTE

91 145 æ 230 LATIN SMALL LETTER AE

92 146 Æ 198 LATIN CAPITAL LETTER AE

93 147 ô 244 LATIN SMALL LETTER O WITH CIRCUMFLEX

94 148 ö 246 LATIN SMALL LETTER O WITH DIAERESIS

95 149 ò 242 LATIN SMALL LETTER O WITH GRAVE

96 150 û 251 LATIN SMALL LETTER U WITH CIRCUMFLEX

97 151 ù 249 LATIN SMALL LETTER U WITH GRAVE

98 152 İ 304 LATIN CAPITAL LETTER I WITH DOT ABOVE

99 153 Ö 214 LATIN CAPITAL LETTER O WITH DIAERESIS

9A 154 Ü 220 LATIN CAPITAL LETTER U WITH DIAERESIS

9B 155 ø 248 LATIN SMALL LETTER O WITH STROKE

9D 157 Ø 216 LATIN CAPITAL LETTER O WITH STROKE

9E 158 Ş 350 LATIN CAPITAL LETTER S WITH CEDILLA

9F 159 ş 351 LATIN SMALL LETTER S WITH CEDILLA

A0 160 á 225 LATIN SMALL LETTER A WITH ACUTE

A1 161 í 237 LATIN SMALL LETTER I WITH ACUTE

A2 162 ó 243 LATIN SMALL LETTER O WITH ACUTE

A3 163 ú 250 LATIN SMALL LETTER U WITH ACUTE

A4 164 ñ 241 LATIN SMALL LETTER N WITH TILDE

A5 165 Ñ 209 LATIN CAPITAL LETTER N WITH TILDE

A6 166 Ğ 286 LATIN CAPITAL LETTER G WITH BREVE

A7 167 ğ 287 LATIN SMALL LETTER G WITH BREVE

A8 168 ¿ 191 INVERTED QUESTION MARK

B5 181 Á 193 LATIN CAPITAL LETTER A WITH ACUTE

B6 182 Â 194 LATIN CAPITAL LETTER A WITH CIRCUMFLEX

B7 183 À 192 LATIN CAPITAL LETTER A WITH GRAVE

C6 198 ã 227 LATIN SMALL LETTER A WITH TILDE

C7 199 Ã 195 LATIN CAPITAL LETTER A WITH TILDE

D2 210 Ê 202 LATIN CAPITAL LETTER E WITH CIRCUMFLEX

D3 211 Ë 203 LATIN CAPITAL LETTER E WITH DIAERESIS

D4 212 È 200 LATIN CAPITAL LETTER E WITH GRAVE

D6 214 Í 205 LATIN CAPITAL LETTER I WITH ACUTE

D7 215 Î 206 LATIN CAPITAL LETTER I WITH CIRCUMFLEX

59 EN2Z-0937GE51 R0518
CARE ENVIRONMENT CARE

Hex
Dec Char Unicode ISO/IEC 10646-1:2000 Character Name

D8 216 Ï 207 LATIN CAPITAL LETTER I WITH DIAERESIS

DE 222 Ì 204 LATIN CAPITAL LETTER I WITH GRAVE

E0 224 Ó 211 LATIN CAPITAL LETTER O WITH ACUTE

E1 225 ß 223 LATIN SMALL LETTER SHARP S

E2 226 Ô 212 LATIN CAPITAL LETTER O WITH CIRCUMFLEX

E3 227 Ò 210 LATIN CAPITAL LETTER O WITH GRAVE

E4 228 õ 245 LATIN SMALL LETTER O WITH TILDE

E5 229 Õ 213 LATIN CAPITAL LETTER O WITH TILDE

E6 230 µ 181 MICRO SIGN

E9 233 Ú 218 LATIN CAPITAL LETTER U WITH ACUTE

EA 234 Û 219 LATIN CAPITAL LETTER U WITH CIRCUMFLEX

EB 235 Ù 217 LATIN CAPITAL LETTER U WITH GRAVE

EC 236 ì 236 LATIN SMALL LETTER I WITH GRAVE

ED 237 ÿ 255 LATIN SMALL LETTER Y WITH DIAERESIS

F8 248 ° 176 DEGREE SIGN

Procedure 1. In Windows, click Start>Settings>Control panel.

2. Double-click Regional and Language Options. The Regional and Language


Options dialog box displays.

3. On the Regional Options tab under Standards and formats, select the
language for displaying standards and formats such as format numbers,
currencies, dates, and time.

4. Under Location, select the matching country for supporting you with local
services such as news and weather.

EN2Z-0937GE51 R0518 60
CARE CUSTOMIZE WINDOWS DEFAULT REGIONAL AND LANGUAGE SETTINGS

5. Select the Languages tab.

6. If you want to support Arabic, Armenian, Georgian, Thai, Hebrew, Indic, Thai
and Vietnamese languages, check Install files for complex script and right-
to-left languages (including Thai).

7. If you want to support Japanese, Chinese and Korean languages, check Install
files for East Asian languages under Supplemental language support.

8. Make sure that you have the necessary harddisk space indicated in the
message boxes displayed. Close the message boxes by clicking OK.

After confirming by clicking OK or Apply, the additional files will be installed on


the PC.

9. After successful installation, repeat steps 1 through 5, and then proceed with
step 10.

10. Click Details button. The Text Services and Input Languages dialog box
displays. The actual input language is selected in Default input language and
the corresponding installed services are highlighted in bold under Installed
services.

11. To add a new input language, click the Add button. The Add Input Language
dialog box displays.

61 EN2Z-0937GE51 R0518
CARE ENVIRONMENT CARE

12. In Input Language, select the language, in this case Italian. Check/select
optional settings for Keyboard layout/IME, Handwriting recognition and Speech
if available and if desired.

13. Click OK. The new language and its services are added to the Installed
Services list and can be selected as default input language.

14. In Default input language, select the language, in this case Italian.

EN2Z-0937GE51 R0518 62
CARE CUSTOMIZE WINDOWS DEFAULT REGIONAL AND LANGUAGE SETTINGS

15. In the Text Services and Input Languages dialog box, click the Language bar
button. The Language Bar Settings dialog box displays. Check Show the
Language bar on the desktop and Show additional Language bar icons in
the task bar. These enabled options allow toggling between several
language(s) on the desktop and in the taskbar after the customization is
finished.

16. Click OK.

17. In the Text Services and Input Languages dialog box, click OK, and then select
the Advanced tab in the Regional and Language Options dialog box.

63 EN2Z-0937GE51 R0518
CARE ENVIRONMENT CARE

18. In Language for non-Unicode programs, select the language, in this case
Italian.

19. Click OK to save all settings. The Advanced message box may display.

20. Follow the instructions described in the message box, and close the message
box. The Change Regional Options message box displays.

21. Restart the PC by clicking Yes. After restart, the new language, in this case
Italian is added to the Language bar.

EN2Z-0937GE51 R0518 64
CARE CUSTOMIZE WINDOWS DEFAULT REGIONAL AND LANGUAGE SETTINGS

22. Check the language in the Language bar.

23. For selecting the language in CARE, COACH, XL-Online respectively in


COACH Online, please refer to the corresponding Online Help and/or PDF
documentation.

65 EN2Z-0937GE51 R0518
QUICK TOURS CARE

QUICK TOURS
The following engineering steps are typical for Excel 800 / 600 / 500 / Smart / 100 /
80 / 50 controllers in CARE XL-5000 and are described in more detail in the
subsequent sections:

• Create Project
• Set Global CARE Options
• Create Controller
• Create Plant
• Create Plant Schematic
• Modify Datapoints
• Assign Datapoints to Controller
• Develop Control Strategy
• Develop Switching Logic
• Create Time Program
• Design and Configure C-Bus Network
• Startup Controller
• Generate Documentation

For special information on basic engineering of LON controllers and BACnet


controllers refer to the LonWorks Engineering and Excel Web Controller chapters.

Create Project
Purpose Define project name, password, and general information such as reference number,
client name, and order number. This information appears in the final documentation
for the project, is used in pricing estimates, and controls access to the projects.

Procedure 1. Click menu item Project, then drop-down item New.

RESULT: The New Project dialog box displays.

EN2Z-0937GE51 R0518 66
CARE QUICK TOURS

CARE-XL-5000: New Project dialog box

67 EN2Z-0937GE51 R0518
QUICK TOURS CARE

CARE-BACnet: New Project dialog box

2. Enter information in all fields. In some fields defaults are displayed. Do not
leave any fields blank. For detailed information on the fields and listbox values,
please refer to the PROJECTS DEFINITION AND MANAGEMENT section.

3. Click OK (or press Enter key) to close dialog box and create project. All fields
must have entries or the OK button is inactive.

RESULT: In CARE-XL 5000, the Edit Project Password dialog box displays.

NOTE: In CARE XL 5000, the input of a password is not necessary. If


applied, a password must have at least 5 characters and can have
maximum 15 characters. For the password, any combination of
numbers, letters, and special characters like commas are possible.

RESULT: In CARE-BACnet, the Edit Project Passwords dialog box displays.

EN2Z-0937GE51 R0518 68
CARE QUICK TOURS

NOTE: In CARE-BACnet you must enter the following three passwords:

SystemAdmin
Allows general access to the project for the CARE user and
unlimited web-browser access with SystemAdmin rights. The
System Admin password must have at least 5 characters, but
should have more characters, including upper & lower case, letters,
numbers and special characters. It can have maximum 33
characters

XwAdmin
Allows restricted access to the Linux operating system of the
controller including access to the tool and application directories.
This allows setting up the controller including translation and
connection, application upload and download, download of
settings, download of graphics (UI Suite), firmware upgrade
and reset of the configuration

Root
Allows unrestricted access to the Linux operating system of the
controller via serial interface using a console

FTP user
Allows uploading/downloading diagnostic files via FTP

For the root, XwAdmin, and FTP passwords, CARE proposes


visible passwords. You can change these passwords as described
in step 5. The XwAdmin, Root, and FTP passwords have 16
characters and can have maximum 33 characters.

For all passwords, any combination of numbers, letters, and


special characters like commas are possible and should be used.

69 EN2Z-0937GE51 R0518
QUICK TOURS CARE

4. For a CARE XL 5000 project, type in the password in New Password and
Verify if desired, and then click the OK button. For a CARE-BACnet project
continue with step 5.

CAUTION
If a password was entered, make a note of the password. No one can
work on the project without knowing this password.

5. For a CARE-BACnet project, enter the project password twice in New


Password and Verify. This password is for the CARE user with SystemAdmin
rights. When entering the passwords they are hidden.

6. In XwAdmin, Root, and FTP user visible passwords are shown. If desired,
change the passwords.
.

EN2Z-0937GE51 R0518 70
CARE QUICK TOURS

7. Then, click the OK button.

CAUTION
Make a note of all the passwords. No one can work on the project
without knowing the SystemAdmin password. No one can setup the
controller in CARE without knowing the XwAdmin password. No one can
access the controller via a console without knowing the Root password.

RESULT: The Project is created and displayed twice, in the logical plant tree
and in the network tree. On the right pane, the project properties
are displayed.

CARE-XL-5000: Project Properties

71 EN2Z-0937GE51 R0518
QUICK TOURS CARE

CARE-BACnet: Project Properties

8. Continue by setting default settings as described under the “Set Global CARE
Options” section.

Set Global CARE Options


Purpose To set global settings for the project and the different buses (C-Bus, LonWorks, and
BACnet).

These settings are project-related and will be applied globally within the project.
Global settings include the following:

• Default project settings such as project description and simultaneous NV


renaming in case of datapoint renaming etc.
• Default LON properties settings such as default connection settings and channel
limit
• XL 500/800 Controller settings for translation, LiveCARE, etc.
• BACnet Controller settings such as timeouts, etc.
• LNS Synchronization options
• Backup/Restore
• Email Alarming

Procedure 1. Click on menu item Options, then submenu item Global Options.

RESULT: The Global Options dialog box displays.

EN2Z-0937GE51 R0518 72
CARE QUICK TOURS

2. On the General tab, enter Project Default Settings. For detailed description of
the settings, please refer to the Create New Project section.

3. Check the Rename mapped NV on Datapoint name change option if you


want a NV name to be changed accordingly when changing the referring
datapoint name.

4. Check the Rename Lon Object name on Plant name change option if you
want a Lon Object name to be changed accordingly when changing the
referring plant name.

5. Check Rename Event Enrollments on Controller/Plant/Datapoint name


change option if you want the names of event enrollments to be changed
accordingly when changing the referring controller, plant, or datapoint name.

6. Check the Prevent automatic rename of Datapoint and NV names option if


you want a NV name not to be changed accordingly when changing the
referring datapoint name.

7. Continue by clicking the Default LON Properties tab.

73 EN2Z-0937GE51 R0518
QUICK TOURS CARE

RESULT: The default LON properties are shown. The Default System
Name and Default Channel Name are displayed in disabled
fields. These defaults have been set in the network tree and can
be changed there at any time. The NV Type list Version displays
the version number, which is useful for the Honeywell Technical
Support Center (TAC) in case of updates.

8. Enter/change the following:

Max. Lon Object Name Length


The max. Lon Object Name Length has to be considered when replicating
plants. The length of NV object names is restricted to 16 characters. Names
longer than 16 characters will abort the translation of the application and must
be reworked. Defaults to 16.

Max. NV Name Length


The max. NV Name Length has to be considered when replicating plants.
The length for NV names is restricted to 21 characters. Names longer than 21
will abort the translation of the application and must be reworked. Defaults to
21.

NOTE: The Max. NV Name Length should only be changed if longer names
are desired for exclusive use of CARE, not in LNS (EBI).

9. Check the Generate LON interface change warning option if you want to
display the following warning in case the LON interface has been changed.

EN2Z-0937GE51 R0518 74
CARE QUICK TOURS

That is, this warning will be displayed whenever you change the LON interface
in the network tree by adding or deleting NVs and/or LON objects.

10. Check the Allow to exceed channel limit option if you want to allow
exceeding the max. number of devices to be added to channels.

IMPORTANT
The physical layer of the LonTalk protocol is designed for max. 64 devices
per channel in order to assure a properly working network. Exceeding that
number of devices may cause electrical problems. When adding more than
64 devices to the channel, increased traffic on the LonWorks network may
also cause problems. It is recommended to avoid exceeding the limits.
Whenever it may become necessary to exceed the limit of 64 devices, it is
recommended to use a repeater.

11. Under Default Connection Settings, check the settings that should be used
for connections when creating bindings. Note that these settings will become
valid only for bindings created from now on. If you are not an advanced user of
LON technology, it is recommended to keep the settings as provided by CARE.

IMPORTANT
Multiple Bindings (Group Binding) and Address Table Entries
Allocation

When creating group binding (multiple bindings) by connecting one


datapoint to multiple terminals of LON devices, CARE has an option to
specify the broadcast type (Use Broadcast field). In order to save
address table entries it is possible to use the binding type ´Yes, if
group`. That will ensure that no address table entry is needed
independent on how many bindings will be created.

But, on LNS synchronization this may cause a problem because LNS


issues one address table entry for each group binding. For controllers
were all address tables are used up, a workaround could be to
change the connection type to broadcast before performing the
bindings (either in the Global Options dialog before performing the
bindings or for each connection individually afterwards).

12. Continue by clicking the XL500/800/MVC Controller tab.

75 EN2Z-0937GE51 R0518
QUICK TOURS CARE

13. Enter/change the following:

Time Program Size for Online Changes


This value defines the enhanced buffer size in KBytes for online changes of the
time program. Defaults to 4096.

Max. RACL Columns


This value defines the max. number of RACL columns. For XL 50 fixed
applications it is recommended to set the value to 255.

Live CARE Settings


Here you select the default settings which will be set in the Live CARE
Communication dialog box after starting Live CARE.

Default Password
The default password to automatically connect to the controller without the
need of entering the password in the Communication dialog box, is 3333. If you
change the password here, you must enter the same password in the
Communication dialog box.

Default COM Port


Selects the Default COM Port that Live CARE uses for connection to the
controller.

Use Simulator as default


If checked, the Use Simulator option is preselected in the Communication
dialog box. Then Live CARE simulates controller function via simulation
software, but communicates not directly with a controller (online).

User Privileges
If checked, it allows to modify Z-Registers

If checked, it allows to modify point roles

14. Continue by clicking the BACnet Controller tab.

EN2Z-0937GE51 R0518 76
CARE QUICK TOURS

15. Enter/change desired values:

IP Addresses

X-Over
USB over adapter
USB direct
The IP Addresses above are defined defaults in the controller and cannot be
changed.

The following local IP addresses are pre-defined default addresses the local
PC can use when connecting to the Excel Web controller. Each address should
match the original IP address issued when creating the corresponding
connection (X-Over= crossover cable, Serial direct or USB). For detailed
instructions on connection types, please refer to the Setup BACnet Controller
chapter and its subsections. If an IP address displayed/entered here is not the
same as in the corresponding network connection, an error message will be
displayed when connecting to the controller via this connection.

CARE PC X-Over
Crossover cable
Allows initial setup of the controller by local access like with USB cable, but
with higher speed and temporary disconnection to the network.

CARE PC Serial (RS-232)


Using a null modem cable, the Excel Web controller can be connected to the
PC via the RS232 interface.

CARE PC USB
For initial access to the controller, you must connect via USB cable.

Make sure that the local IP addresses of the above connection types match the
original IP addresses of the connections. If an IP address of the connection has
been changed, change the address here likewise.

77 EN2Z-0937GE51 R0518
QUICK TOURS CARE

For more information on PC - Excel Web network connections, please refer to


the Excel Web User Guide, EN2B-0289GE51.

Use BACnet MS/TP Device ID scheme (with step size 1000)

If checked, for every controller created from now you can select a controller
number in the range of 1000 through 65000 with steps of 1000. Already
allocated numbers will be considered.

If unchecked, for every device (controller) created from now you can select a
controller number in the range of 1 through 512 with steps of 1.

For both schemas, already allocated numbers will be considered.


You can toggle the schema at any time.

When applying the schema option, it also affects the network number and
device ID.

If a controller is created as first controller in the project and it has one BACnet
MS/TP bus, this single BACnet MS/TP-1 bus will receive the same network
number as the controller, starting with 1000. If a controller is created as first
controller in the project and it has two BACnet MS/TP busses, the second
BACnet MS/TP-2 bus will receive the network number 1500.

EN2Z-0937GE51 R0518 78
CARE QUICK TOURS

A device ID is assigned to any device belonging to the BACnet MS/TP bus


(BACnet MS/TP 1 or BACnet MS/TP 2) according to the following formula:

device ID = network number + MAC address

Check for application size limit (16 MB)


If checked, CARE will check the application size during controller translation.
When the size of 16 MB is extended, a warning will be displayed. If unchecked,
no warning will be displayed if the application size is greater than 16 MB.

79 EN2Z-0937GE51 R0518
QUICK TOURS CARE

Support new BACnet features beyond BACnet version 12.00.04 (with BTL
certificate)

If checked, CARE allows the creation of loop objects.

Timeouts

RPC Timeouts
This time sets the timeout for the communication between CARE and the
BACnet controller.

Start-Stop Timeout
This time sets the timeout for the Start and Stop commands initiated by CARE
for the BACnet controller. If this time is decreased, the corresponding status
message displays earlier. It is recommended to keep the default time for
normal application sizes, for big application sizes it is recommended to
increase the time to the desired value.

MS/TP Device Settings

No. of MS/TP Devices


This number defines the max. number of devices that can be created for a
MS/TP bus. The MS/TP bus can have a pure MS/TP topology for integrating
EAGLE controllers and BACnet 3rd party devices based on an already existing
wired building channel, or it can be part of a BACnet IP network including panel
bus and MS/TP bus.

Online Graphic

Worksheet Width
Shows the default width for online graphics.

Worksheet Height
Shows the default height for online graphics.

Change the width and/or height values if desired.

Terminal Assignment for Panel I/O

Default HW Interface
Defines the default hardware interface when using panel I/O modules. By
default, datapoints will be assigned to the hardware interface selected.

EN2Z-0937GE51 R0518 80
CARE QUICK TOURS

16. Continue by clicking the Backup / Restore tab.

17. Select desired options:

Default Settings
For backups and restores in CARE, the listed items can be purposefully
included/excluded from the backup and restore process.

NOTE: It is recommended to include all items. Items which are not included in
a backup cannot be restored.

Check the items, you want to to be included in a backup / restore.

Include XFMs (applies to CARE-XL 5000 only)


XFMs (Extended Function Modules) are applications (or subprograms) that can
combine with other control icons, subprograms, or points to provide additional
control strategy functionality. For details on XFMs, please refer to the
“CONTROL STRATEGY” section and the Control Icons User Guide, EN2B-
0184GE51.

Include Default Files (applies to CARE-XL 5000 only)


Default files can be customized for use in a specific area or region. Default files
have a file extension of ID and correspond to different versions of controllers.
For example, the default file for Excel 500 Controllers, OS Version 2.06, is

81 EN2Z-0937GE51 R0518
QUICK TOURS CARE

called xl_2_6.id. For OS Version 1.5, the file is called xl_1_5.id. For details on
default files, please refer to the “DEFAULT TEXT EDITOR” section.

Include Pic Files


These are the segment graphics in the plant schematics

Include Element Lib (applies to CARE-XL 5000 only)


The Element library includes ”Elements” (source records) for the segments that
are available for each type of plant. For example, an air conditioning plant can
have fan, sensor, and damper segments. The fan segment can include return
and supply air fans in single and multiple configurations. For details on
Element Library, refer to the “IMPORT THE ELEMENT LIBRARY” and the
“EXPORT THE ELEMENT LIBRARY “ sections.

Include Controller Files


Controller files are multiple files (.IPL, .ADL, .KDX, .PRA, .RAZ, .RAP, and
others) generated during controller translation for latter download into the
controller.

NOTES: It is recommended to include all items. When backing up / restoring a


project or the database you can include/exclude the same items in the
corresponding dialog.

Default Archive Folder


Here you select the folder to/from which the selected items will be by default
backupped/restored. Click Browse button, select the default folder, and then
click OK. The selected folder will be displayed as default folder.

18. Continue by clicking the LNS Synchronization Options tab.

19. Select desired options:

EN2Z-0937GE51 R0518 82
CARE QUICK TOURS

Synychronize Controllers without bindings


If checked, controllers without bindings will be available in LNS after
Synchronization. If unchecked, such controllers will not be available after
Synchronization.

Check LNS Version Compatibility for Client/Remote


If checked, CARE displays a message if the local and remote LNS versions are
not compatible. In case of incompatibility, synchronization will be aborted. To
get a proper synchronization, please make sure you have compatible LNS
versions. If unchecked, CARE does not check for compatibility and displays no
message even if the LNS versions are incompatible. In this case,
inconsistencies and failure results may occur in the remote LNS database.

NOTES: We recommend using the checked default options and using


compatible LNS versions. We asure compatibility when using LNS
3.08 and LNS Turbo SP2 3.22 versions.

20. Continue by clicking the E-Mail tab (applies to CARE-XL Web only).

Here you enter the global email address for Email Alarming that CARE by
default uses for each controller of the project. This email address can be
changed later for each controller individually. See “Email Alarming” and
“Create Excel Web” sections.

Template
Select this radio button, if the global sender email address of the controller
should by default be as: <ControllerName><ProjectName>@.Com

User Defined
Select this radio button, if you want to use another address than the template
address as global sender email address, and then enter the email address.

21. Confirm your settings by clicking OK.

22. Continue by creating a controller as described under the “Create Controller”


section.

83 EN2Z-0937GE51 R0518
QUICK TOURS CARE

Create Controller
Purpose Create a new controller

Procedure 1. If not already highlighted in the logical plant tree, select the project.

2. Click menu item Controller, then drop-down item New.

Or, click right mouse key and with left mouse key, click on Create Controller in
the context menu.

RESULT: The New Controller dialog box displays.

3. Type a controller name (must be unique within the project). In this example,
CONT01.

4. Tab to Bus Name (CARE XL-5000) or Subsystem/Subnet Name (CARE-


BACnet). This field allows to select the subfolders, where the controller should
be arranged. By default, software creates a folder named "Bus 1" (CARE XL-
5000) and “IP-Subnet 1” (CARE-BACnet).

Click down arrow and select a subfolder.

5. Tab to Controller Number. Click down arrow and select a number from 1
through 30 (must be unique within the project). In this example 5.

NOTE: In CARE-BACnet, please note if a controller offset has been issued


during project creation. In this case, only a controller number higher
than the entered offset can be set here.

EN2Z-0937GE51 R0518 84
CARE QUICK TOURS

6. Tab to Controller Type. Tab to the next field to keep current type or click down
arrow to display and select a different type.

7. Tab to Controller OS Version (the version of OS that will be running in the


controller). Tab to the next field to keep the current version or click down arrow
to display and select a different version.

8. Tab to Country Code (CARE XL-5000) or Location (CARE-BACnet). The


operator interface is required to provide the correct language for the selected
country. The default depends on the Windows version installed. Tab to the
next field to keep it or click down arrow to display and select a different country.

9. Tab to Default File Set. Select the appropriate default file for the selected
Controller OS Version. A short description for the selected default file set is
given below the drop down list box.

10. Tab to Units of Measurement. Select whether the controller should use
International (metric) or Imperial units in Control Strategy EMS icons. This
selection controls whether inputs are accepted in Celsius or Fahrenheit.

11. Tab to Hardware Type (CARE-BACnet only). Select the hardware type.

12. Tab to Power Supply. Select desired module type. Power supply applies only to
Excel 800, 500 and 600 controllers.

13. Tab to Installation Type. Normal installation is the default selection. If the
controller has high-density digital inputs, select Cabinet Door Installation.
Installation Type applies only to Excel 800, 500 and 600 controllers.

14. Tab to Wiring type and select desired type (screw terminals or flat strip
cabling). Wiring type applies only to Excel 50 controllers.

15. Tab to LON (applies only to Excel 500 controllers OS version 2.04). Select
desired configuration:

Shared / Open LON I/O


Allows multiple controllers with its distributed I/O modules residing on one
physical LON-bus and/or integration of additional Open LON devices.

NOTE: For this configuration, the controller must contain the 3120E5 LON
chip. In Shared configuration only the following distributed I/O
modules can be used: XFL521B, XFL522B, XFL523B, XFL524B.

Local
Allows just one controller with its distributed I/O modules residing on one
physical LON-bus.

NOTE: For this configuration, controllers containing the 3120E5 LON chip and
earlier controller models containing the 3120B1 LON chip can be
used. In Local configuration the following distributed I/O modules can
be used: XFL521, XFL522A, XFL523, XFL524A. If B-types of
distributed I/Os shall be used, the backwards compatibility must be
enabled by pressing service while turning hex switch.

For detailed information on the configuration, please refer to the Define


LonWorks Network Architecture section.

Refer to the Controllers with changeable Hardware Configuration section for a


detailed introduction into system configuration. Refer to the Terminal
Assignment Tool section for assigning the neuron IDs to the modules.

16. Click OK.

RESULT: The new controller is created and displayed four times in all:
• Once in the logical plant tree
• Once in the C-Bus folder
• Once in the Channels folder
• Once in the Default System folder

85 EN2Z-0937GE51 R0518
QUICK TOURS CARE

On the right pane, the controller properties are displayed.

17. Continue by creating plants as described under the Create Plant section.

Create Plant
Purpose Define a plant name, select a plant type and preferred target I/O hardware, and
preassign a controller (if desired).

Attached/Unattached Plants A plant is automatically attached to the selected controller. To create unattached
plants in the beginning, the project instead of the controller must be selected.
Plants can be detached or re-attached by simply dragging&dropping them to the
desired destination (controller, project).

Procedure 1. If not already highlighted in the logical plant tree, select the controller, you want
attach the plant to.

2. Click menu item Plant, then drop-down item New.

Or, click right mouse key and with left mouse key, click on Create Plant in the
context menu.

RESULT: The New Plant dialog box displays.

EN2Z-0937GE51 R0518 86
CARE QUICK TOURS

3. Type a plant name in the Name field (the new name cannot match an existing
plant name in the project). Maximum 30 alphanumeric characters; no spaces;
first character cannot be a number.

4. Type a additional description in the Description field (CARE-BACnet only).

5. From the Plant Type drop down listbox (CARE-XL5000 only), select desired
type:

Air Conditioning Air handler or fan system building blocks.

Chilled Water Cooling tower, condenser water pumps, and chiller building
blocks.

Elink Elements that represent system points for Excel 10


Controllers.

Hot Water Boilers, converters, and hot water system building blocks.

MacroCel Air handling unit of moderate control complexity building


blocks

MicroCel VAV box, small central air handler, converter and exhaust
fan building blocks

W7620 Individual HVAC zone equipment

W7620WSHP Water source heat pump building blocks

XLink Master plant that contains the system points for MicroCel,
MacroCel, W7620 and W7620WSHP subsystem plants.

6. From the Plant OS Version drop down listbox select desired version (CARE-
XL5000 only). This number is the OS version of the controller where the plant
will be downloaded. See Appendix for rules on upgrading/downgrading
controller versions.

7. From the Plant Default File Set drop down listbox (CARE-XL5000 only), select
desired plant default file. Plant default files are customized project defaults for
use in specific areas or regions generated in the Default Text editor (see

87 EN2Z-0937GE51 R0518
QUICK TOURS CARE

Default Text Editor section). A short description for the selected default file set
is given below the drop-down list box.

8. Under Units of Measurement (CARE-XL5000 only), select the desired type for
the plant, International (metric) or Imperial. This selection tells the Control
Strategy EMS icons which type of inputs to accept, Celsius or Fahrenheit. Units
of Measurement applies not to ELink applications.

9. Under Preferred Target I/O Hardware (CARE XL-5000 only), select desired
target I/O hardware:

Standard I/O (XF5..)


(applicable to Excel 500 and 50 with OS 2.0 - 2.06).
Hardware points of this plant will be assigned to XF5.. modules (IP bus).

Panel I/O (XF8..)


(applicable to Excel 800, OS 3.00 only)
Hardware points of this plant will be assigned to XF8.. modules (panel bus).

Distributed I/O (XFL5..)


(applicable to Excel 500 and Smart with OS 2.0 - 2.04).
Hardware points of this plant will be assigned to XFL5.. modules. (LonWorks-
bus).

Distributed I/O (XFL8..)


(applicable to Excel 800, OS 3.00 only).
Hardware points of this plant will be assigned to XFL8.. modules (LonWorks-
bus).

Open LON
Hardware points of this plant will be boardless, that is, unassigned (applicable
to Excel 800, 500, Smart, 50 with OS 2.06 and higher, and Excel 10)

10. Click OK.

RESULT: The new plant is created and automatically attached to the


controller. It is displayed in the logical plant tree. On the right pane,
the plant properties are displayed.

11. Continue by creating the plant schematic as described under the Create Plant
Schematic section.

EN2Z-0937GE51 R0518 88
CARE QUICK TOURS

Create Plant Schematic


Purpose To provide control over the system operation.

To get a good control of the plant a minimum number of datapoints are required.
These datapoints are automatically created by drawing a graphical plant schematic
or by quickly creating datapoints without graphics. Both procedures can be
combined.

NOTE: For the EXCEL WEB and EXCEL WEB II controllers (CARE-BACnet)
schematic creation is not possible.

NOTE: For the ELink controller, schematic and quick datapoint creation is not
possible.

Draw Plant Schematic When drawing a plant schematic you define the equipment of the plant and how it
works together. A plant schematic is a combination of graphical segments such as
boilers, heaters, and pumps. Segments consist of equipment such as sensors,
status points, valves, and pumps. Each segment has an associated minimum
number of datapoints required for good control.

Creation of HW/SW Points In comparison to drawing a plant schematic, datapoints without graphics can
without Graphic quickly be generated. These quick creation can include hardware as well as
software points.

For detailed information on point types, please refer to the PLANT SCHEMATICS
section.

Procedures A) Draw Plant Schematic

1. If not already highlighted in the logical plant tree, select the plant.

2. Click menu item Plant, then drop-down item Schematic.

RESULT: The Schematic Main Window displays.

89 EN2Z-0937GE51 R0518
QUICK TOURS CARE

3. Click menu item Segments, then select the desired component to insert it into
the plant.

EN2Z-0937GE51 R0518 90
CARE QUICK TOURS

4. Add the following components by selecting the corresponding menu


sequences:

– Dampers/Outside, Return and Relief/Mixing Damper/No Minimum


Damper
– Sensor/Temperature/Mixed Air
– Safeties/Freeze Status
– Filter/Outside, Mixed or Supply Air Duct/Differential Pressure Status
– Coil/Hot Water Heating Coil/Supply Duct/3-Way Valve/No Pump
– Chilled Water Cooling Coils/Supply Duct/3-Way Valve/No Pump
– Fan/Single Supply Fan/Single Speed with Vane Control/Fan and Vane
Control with Status
– Sensor/Temperature/Discharge Air Temp
– Sensor/Pressure/Supply Duct Static

91 EN2Z-0937GE51 R0518
QUICK TOURS CARE

5. When finished the drawing, click menu item File, then submenu item End.

RESULT: In the logical plant tree, the datapoints assigned to the plant
components are displayed.

6. If desired, continue with adding HW/SW points without graphic to the


schematic as described in the Quick Creation of HW/SW Points without
Graphic procedure.

B) Quick Creation of HW/SW Points without Graphic

1. If not already highlighted in the logical plant tree, select the plant.

2. Click menu item Plant, then drop-down item Create HW/SW Points.

Or, click right mouse key and with left mouse key, click on
Create HW/SW Point(s) in the context menu.

EN2Z-0937GE51 R0518 92
CARE QUICK TOURS

RESULT: The New Point dialog box displays.

3. From the Type drop-down listbox, select the datapoint type and, if available,
from the Subtype drop-down listbox, select the datapoint subtype.

4. In the Number field, select the number of points to be created and in the User
Address fields enter the name of the datapoint(s) to be created. If you are
adding more than one point, software automatically numbers the corresponding
user addresses sequentially to guarantee unique user addresses. For example,
if you enter pt and request two points, software creates two points named pt1
and pt 2. Only use alphabetic characters. Do not use blanks.

5. Click OK.

RESULT: In the following example, the datapoints are added to the Analog
Input type folder in the logical plant tree.

6. To view the plant schematic, click on the plant in the logical plant tree and
select the Schematic tab on the right pane.

93 EN2Z-0937GE51 R0518
QUICK TOURS CARE

7. Continue by modifying datapoints as described under the Modify Datapoints


section.

Modify Datapoints
Purpose To customize point attributes according to desired system operation.

Points can be modified in two different views, in the itemized display and in the grid
display (for display options, see Basic Working Techniques section). The itemized
display is suited for editing only a few datapoints, the grid display is suited for
editing many datapoints in an overall view.

Procedures A) Modify Datapoints in Itemized Display

1. In the logical plant tree, select the point you want to modify.

RESULT: On the right pane, the point attributes are displayed on the
Properties tab.

EN2Z-0937GE51 R0518 94
CARE QUICK TOURS

2. Modify desired values in the fields and/or select/deselect desired options.

3. Continue with assigning datapoints to the controller as described under the


Manually Assign Datapoints to Controller section.

B) Modify Datapoints in Grid Display

1. In the logical plant tree, select the plant of which datapoints you want to edit
and select the Grid tab on the right pane.

RESULT: All datapoints assigned to that plant are displayed in a grid.

95 EN2Z-0937GE51 R0518
QUICK TOURS CARE

2. Modify desired values in the fields and/or select/deselect desired options.

3. Continue by assigning the datapoints to the controller as described under the


Assign Datapoints to Controller section.

Manually Assign Datapoints to Controller


Purpose To accommodate the terminal assignments in CARE to the physical cabling.

When creating a plant schematic for a XL 50, 80, 100, 500, 600, Smart, or 800
controller, CARE automatically assigns the datapoints of the plant to the
appropriate hardware modules, for example, analog inputs are assigned to the
XF521A module, digital outputs are assigned to the XF524A module of an XL5800
controller. But, the order of the datapoints on their module do not necessarily
correspond to the physical cabling. Therefore in some cases, datapoints need to be
moved on their module in CARE. On the other hand it is also possible to
accommodate the physical cabling according to the CARE terminal layout.

NOTE: For the XL 500/Smart and XL 800 controllers, the target hardware can be
chosen among the following different module types:

• Standard I/O (XF5..)


• Panel IO (XF8..)
• Distributed I/O (XFL5..)
• Distributed I/O (XFL8..)
• Open LON

Procedure 1. In the logical plant tree, select the controller.

2. On the right pane, select the Terminal Assignment tab.

RESULT: The terminal assignments of the controller are displayed.

EN2Z-0937GE51 R0518 96
CARE QUICK TOURS

3. If datapoints need to be relocated, click on the datapoint and with pressed


mouse key, move it to the target terminal.

RESULT: The datapoint gets green as you move it over terminals which it
matches to.

NOTE: You can move datapoints only to terminals which match to the
datapoint type. Over terminals which do not match to the datapoint
type, the datapoint gets black and is indicated via a forbidden
symbol.

4. On the target terminal, release mouse key.

5. Continue by developing control strategy for the plant as described under the
Develop Control Strategy section.

Develop Control Strategy


Purpose The control strategy for a plant consists of control loops that monitor the
environment and adjust equipment operation to maintain comfort levels. For
example, a control loop for an air handling system can turn on a return air fan

97 EN2Z-0937GE51 R0518
QUICK TOURS CARE

when discharge air temperature in the return air duct is greater than or equal to
68 F (20 ºC). Control loops consist of a series of “control icons” that dictate a
sequence of events. Control icons provide preprogrammed functions and
algorithms to implement sequences of control in a plant schematic. For detailed
information on control strategy development, please refer to the Control Strategy
section.

Example (CARE XL-5000):

In the following you will add a PID control element to the plant.

Procedure 1. In the logical plant tree, select the plant.

2. Click menu item Plant, then drop-down item Control Strategy.

RESULT: The Control Strategy Main Window displays.

Title bar
Menu bar

Plant schematic

Physical point bar

Control Icons

Workspace

Software point bar

RESULT: The Control Strategy Main Window is divided in the following


areas:

• Title
• Menu bar
• Plant schematic
• Physical point bar
• Software point bar
• Work space

EN2Z-0937GE51 R0518 98
CARE QUICK TOURS

• Control icons

The functions will be described by creating a new control loop in


the following steps.

3. The sequence of operation requires control of the duct static pressure.

4. To create a new control strategy, click menu file, then drop-down menu New.

RESULT: The Create New Control Loop dialog box displays.

5. Enter a name, e.g. Pressure for the control loop and click OK.

RESULT: You can now select the control icons to place them into the
workspace.

6. Click the PID control icon.

7. Click a free rectangle in the control strategy work space to place the control
icon.

RESULT: Software places the symbol in the rectangle.

Software may then display a dialog box that asks for “internal
parameter” information relevant to the control icon. In this case, the
PID icon asks for proportional band, derivative time, integral action,
minimum output, and maximum output. For this system the default
values are fine.

8. Click OK.

RESULT: Notice the control icon. The red color indicates that not all inputs
and outputs are connected to the schematic.

9. To connect the icon to required inputs and outputs, double-click the icon to
display an input/output dialog box that requests required variables.

For example, the PID icon displays the following dialog box:

99 EN2Z-0937GE51 R0518
QUICK TOURS CARE

The Y, X, and W variables need connection to either physical points,


pseudopoints, and/or other control icons. Variables on the left (Y in this case)
are outputs. Variables on the right (X and W in this case) are inputs.

The two blank rectangles in the dialog box are editing fields where you can
enter values to replace the physical connections. For example, in the PID
dialog box, you can type an engineering unit table reference and value for the
W variable, instead of connecting W to a point or control icon. For engineering
unit, enter the corresponding index number.

10. To connect the icon, click a W, X, or Y check box, click a physical point at the
schematic, then click the control icon in the dialog box.

11. To connect the sensor input, click on the X check box.

12. Select the static pressure sensor physical point by clicking the red arrow head
on the far right.

EN2Z-0937GE51 R0518 100


CARE QUICK TOURS

RESULT: The arrow head turns black indicating that it has been selected.

13. Click the control icon symbol in the dialog box.

RESULT: a. The dialog box closes.


b. The active control icon changes color to dark blue.
c. Software adds a short connecting line leaving the icon from the
X location
d. Two lines appear in the work space. One line is vertical; one is
horizontal. Where they intersect each other is the focus point for
mouse clicks. You can move these lines by moving the mouse:

— When you move the mouse left or right, the vertical line moves
left or right.
— When you move the mouse up or down, the horizontal line
moves up or down.

14. Move and click the intersection point to create connecting lines. Move the
intersection point over the point arrow head until a cross, +, appears. Click the
left mouse key to complete the connection.

RESULT: Software connects the point and icon.

15. Now connect the W input of the PID control icon to the reference variable - a
user definable setpoint. An alternative would be to use the editing fields in the
control icon dialog box which would fix the setpoint to the value entered.

16. To create a software point, click on a free position in the software point bar.
Locate it near the relevant control icon.

RESULT: The Create/Select Software Address dialog box displays.

101 EN2Z-0937GE51 R0518


QUICK TOURS CARE

The selected software bar position is displayed at the bottom line


of the dialog box. The list displays all existing pseudopoints/flags
including unassigned, assigned and connected, assigned and
unconnected pseudopoints/flags. Unassigned and assigned
points/flags can be distinguished by the following symbols:

Assigned points: Pseudopoints/flags that reside on the software


bar.

Unassigned pseudopoints/flags or points in switching tables in


folder color with point abbreviation.

Unassigned software points mapped to internal datapoints of


XFMs.

Unassigned software points mapped to XFM parameters.

Each pseudopoint/flag type has its own colored folder which can be
empty or contain already created pseudopoints/flags.

Each pseudopoint/flag type has its own colored folder which can be
empty or contain already created pseudopoints/flags.

17. Click the Pseudo Analog folder.

18. Click right mouse button, and with left mouse button click New in the context
menu,

or

EN2Z-0937GE51 R0518 102


CARE QUICK TOURS

click menu item Edit, then drop-down item New.

RESULT: The New Software Datapoint dialog box displays.

19. Enter "static_setpoint" in the User Address field.

RESULT: In the software point bar, the created software point is indicated by
VA (virtual analog).

20. To connect the PID control icon to the software point, double-click the control
icon once to open it.

21. Click the W checkbox, then click on the VA software point you have been
created.

22. Click the control icon symbol in the control icon dialog box.

RESULT: Notice that there is a red line leaving the control icon from the W
location.

23. Complete the connection, by clicking on the software point in the software point
bar.

103 EN2Z-0937GE51 R0518


QUICK TOURS CARE

24. To finally connect the PID control icon´s output to the dampers on the fan,
double-click the control icon once to open it.

25. Click the Y checkbox, then click the violet arrow head beneath the fan.

RESULT: The physical point is now black indicating that it has been selected.

26. Click the control icon symbol in the control icon dialog box.

RESULT: Notice that there is a red line leaving the control icon from the Y
location.

27. Complete the connection, by clicking on the physical point previously selected.

RESULT: The PID icon changes color to light blue to let you know that the
PID is correctly connected to your system.

EN2Z-0937GE51 R0518 104


CARE QUICK TOURS

This completes the sequence of operation for the static pressure.


When the fan is on, control strategy modulates the damper to
maintain static pressure at the setpoint. When the fan is off, the
switching logic will place the damper in the minimum position.

28. Click menu item File, then submenu item Exit.

29. To check the control loop connections, click OK in the End Control Strategy
dialog box.

105 EN2Z-0937GE51 R0518


QUICK TOURS CARE

30. CARE verifies that all control connections are complete by the following
Information dialog box.

31. Confirm the Information dialog box by clicking OK.

32. Continue by developing the switching logic for the plant as described in the
Develop Switching Logic section.

Develop Switching Logic


Purpose Switching logic provides a convenient means to implement digital (Boolean) logic
control of a point. An analog or digital point is commanded to a specific value or
state if a certain set of conditions are met. Time delays can also be added. For
example, switching logic can start a return air fan 30 seconds after a supply air fan
starts. For detailed information on switching logic development, please refer to the
Switching Logic section.

Example (CARE XL-5000):

According to the sequence of operation, the dampers of the fan will be placed in
minimum position in case of fan failure.

Procedure 1. In the logical plant tree, select the plant.

2. Click menu item Plant, then drop-down item Switching Logic.

RESULT: The Switching Logic Main Window displays.

EN2Z-0937GE51 R0518 106


CARE QUICK TOURS

Title bar
Menu bar

Control bar

Plant schematic

Control Icons
Tool Box

Workspace

The Switching Logic Main Window is divided into the following areas:

– Title bar
– Menu bar
– Control bar
– Plant schematic
– Switching table (Work space)
– Switching logic icons toolbox

The functions will be described by adding switching logic tables in the following
steps.

3. To begin a switching logic for the dampers, click on the fan address point
(violet arrow head, 1) that controls the dampers.

107 EN2Z-0937GE51 R0518


QUICK TOURS CARE

1
RESULT: The title " SaFanVolCtrl" is the user address for the damper input
point on the fan. The default of "0.000" matches the condition
required by the sequence of operation. No change is required. We
will use the status of the fan to determine when the damper will
return to minimum position.

4. Click the green arrow head representing the fan status physical point (2) to add
it to the current switching table.

EN2Z-0937GE51 R0518 108


CARE QUICK TOURS

RESULT: According to the sequence of operation, the dampers of the fan will
be placed in minimum position in case of fan failure. The field
containing the "-" should indicate the status of the fan when you
want the damper to be closed.

5. Click the "-" field twice to change it to a "0" (a false or off condition).

109 EN2Z-0937GE51 R0518


QUICK TOURS CARE

RESULT: The switching table is now complete. If the fan status is "0" false or
off), the damper will be placed in a minimum position. The system
also needs a table to open the heater valve under freeze
conditions. The new button from the button bar is used to start a
new switching table.

6. Click the button in the control bar.

RESULT: The following dialog box displays.

7. Save the switching table by clicking OK.

RESULT: The violet arrow head for the fan dampers is now cross hatched.
This indicates that a switching table is assigned to the point.

8. To start a switching table for the heating coil, click on the heating coil control
point (second violet arrow head from left, 3).

RESULT: The title "HtgVlv" is the user address for the hot water valve. The
default of "0.000" represents a fully closed valve. We need to
change the condition to fully open.

EN2Z-0937GE51 R0518 110


CARE QUICK TOURS

9. Click the third column once to change 0.000 to 100.

10. Type 100 and press ENTER key to fully open the heater valve if the switching
conditions are met.

RESULT: The heater valve is now set to 100 % open when the switching
table conditions are met. Now we will specify those conditions.

The temperature of the freeze status is one input that should


determine the position of the heater valve.

11. Click the green arrow head (left from the heating coil control point, 4)
representing the freeze status physical point.

RESULT: The title "Frz Stat" is the user address and the "-" is a true/false or
on/off condition. The arrow head representing the physical point
turns black to indicate which point is active. Clicking the "-" toggles
between "-", "1" and "0".

12. Click the "-" field once to turn it to a "1".

13. For this plant, we want to add an "OR" function with the next step. This is
accomplished by adding an additional column.

111 EN2Z-0937GE51 R0518


QUICK TOURS CARE

5 4

14. Click the + COL icon on the switching logic icons tool box once.

RESULT: The column is inserted.

15. The heater valve will open to 100 % if the freeze status is active. We also need
to open the heater valve if the mixed air temperature is less than 34 degrees
Fahrenheit.

16. Click the red arrow head representing the mixed air temperature sensor
physical point (second from left, 5).

RESULT: The title "MaTemp" is the user address for the mixed air
temperature sensor. The "0" below on the left represents the
temperature that activates the condition. The "0" on the right
indicates the deadband before the condition is deactivated. The
first change needed on this table is to toggle the "=>" to a "<="
sign.

17. Click the "=>" to change it to a "<=" sign.

18. The "0" in the left column represents the temperature that activates the
condition. Entering a 34 in the left column indicates you wish to activate the
heater valve when the temperature is less that or equal to 34 degrees
Fahrenheit.

19. To change the temperature to 34, first click the "0" in the left column.

20. Then type "34" and press ENTER key.

21. The "0" in the second column represents how much the temperature will rise
above 34 degrees Fahrenheit before the condition is no longer active. A
deadband of 2 degrees is appropriate for this system.

22. Click the "0" field once to enter the deadband.

23. Type 2 and press ENTER key.

EN2Z-0937GE51 R0518 112


CARE QUICK TOURS

24. The field on the far right is where the "or" condition is entered. Clicking the"-
"field" cycles through three conditions: "-" which is neutral, "1"which is true, and
"0" which is false.

25. Click the "-" field" once to turn it to a "1" (true).

RESULT: The table is now complete. When the freeze status is active or the
mixed air temperature is equal to or below 34 degrees Fahrenheit,
the hot water valve will be opened to 100 %.

26. Click menu File, then drop-down menu Exit.

27. Save the switching table by confirming with OK in the dialog box.

28. Continue by creating a time program as described under the Create Time
Program section.

Create Time Program


Purpose Create time sequences for controller operation of devices. For example, set HVAC
start and stop times. Time Programs implement these command schedules.

A controller can have a maximum of 20 time programs. Every time program created
will be performed by the controller.

Each Time Program specifies a list of datapoints to command. A Weekly Program


defines the normal daily activity of the system by specifying which Daily Programs a
controller should use for each day of the week (Sunday through Saturday). The
Weekly Program applies for each week of the year. There is only one Weekly
Program per Time Program.

Daily Programs list points and point actions and times for the controller to
implement.

Holiday programs define special daily programs for holidays such as Christmas and
Easter.

Yearly Programs define time periods with special daily programs. Yearly programs
are suited to consider specific local conditions, for example, regional vacation and
public /religious festivals. Yearly programs can be defined for more than one year.

The following procedure describes the time program handling in CARE XL-5000.
For the handling in CARE-BACnet, please refer to the Schedules and Calendars
section.

Procedure (CARE XL-5000) 1. In the logical plant tree, select the controller.

2. Click menu item Controller, then drop-down item Edit and Time Program Editor.

RESULT: The Time Program Editor displays.

113 EN2Z-0937GE51 R0518


QUICK TOURS CARE

3. Click menu item Edit,

RESULT: The Time Program dialog box displays.

4. Click Add.

RESULT: The Add Time Program dialog box displays.

EN2Z-0937GE51 R0518 114


CARE QUICK TOURS

5. Enter name for the time program and click OK,

6. The ACTIVE holiday radio button enables the Holiday Program. To disable the
Holiday Program, click the INACTIVE holiday radio button. If holiday is inactive,
this Time Program uses the Daily Programs, as set up by the Weekly Program,
on holidays.

RESULT: The Time Program dialog box redisplays. It shows the name of
the overall time program to which then you can add daily,
weekly, holiday and yearly programs.

7. Click Edit.

RESULT: The Time Program: <name of time program> dialog box


displays.

115 EN2Z-0937GE51 R0518


QUICK TOURS CARE

Create Daily Program


Purpose Define Daily Programs and assign point commands and command times to each
Daily Program. Each Daily Program covers a 24-hour period

Daily Programs specify switching times, setpoints, and switching status for selected
points.

Each time program must have a list of assigned datapoints before you can set up
Daily Programs....

Assign/Unassign User Addresses

1. In the Time Program: <name of time program> dialog box, click menu item
User address.

RESULT: The Select User Address dialog box displays. To set up any
daily program, you first must define user addresses which
should be controlled by the daily time program. You can assign
each user address to only one time program.

EN2Z-0937GE51 R0518 116


CARE QUICK TOURS

2. Click Reference to list already assigned datapoints.

3. Click on datapoint in the list you want to assign and click (De)Select.

RESULT: The assigned datapoint will be marked by an #.

4. Click Close.

5. In the Time Program: <name of time program> dialog box , click menu item
Daily program.

RESULT: The Daily Program dialog box displays.

117 EN2Z-0937GE51 R0518


QUICK TOURS CARE

6. Click Add.

RESULT: The Add Daily Program dialog box displays.

7. Enter the name for the daily program and click OK.

RESULT: The Daily Program dialog box redisplays with the new name
highlighted.

8. Click Edit.

EN2Z-0937GE51 R0518 118


CARE QUICK TOURS

RESULT: The Edit Daily Program <name of daily program> dialog box
displays in which you assign the datapoints to command the
daily program.

9. Click Add.

RESULT: The Add Point to Daily Program dialog box displays.

10. From the User Address drop-down listbox, select the user address.

NOTE: The following values and options to be set depend on the type of
datapoint selected.

11. In the time fields, enter the time.

12. From the Value drop-down listbox, respectively in the value field, select option,
respectively enter the value.

13. For switching points select optimization or not by clicking the corresponding
option in the Optimize dropdown list box.

14. Click OK.

RESULT: The Edit Daily Program <name of daily program> dialog box
redisplays for adding further datapoints. Each line in the list
represents one command. Each command specifies time, user
address, and value or status command.

119 EN2Z-0937GE51 R0518


QUICK TOURS CARE

15. Click Add to add further datapoints, etc.

16. Click Close.

17. Continue by creating weekly programs as described under the Create Weekly
Program section.

For detailed information on creating time programs, please refer to the Time
Program Editor section. In the following you will open an existing switching
logic.

Create Weekly Program


Purpose Assign Daily Programs to days of the week.

Every Time Program has one Weekly Program that specifies a Daily Program for
each day of the week.

Software uses the Weekly Program to generate the annual program. The Annual
Program is a repeat of the Weekly Programs for each week of the year.

Default Daily Program If you do not assign a Daily Program to a weekday, the Time Program uses the
Daily Program for the previous weekday. The default assignments display after you
exit the Weekly program function and then reselect it.

Procedure 1. In the Time Program: <name of time program> dialog box , click menu item
Weekly programs.

RESULT: The Assign daily program(s) to week days dialog box displays.

EN2Z-0937GE51 R0518 120


CARE QUICK TOURS

2. To assign a Daily Program to a weekday, click Daily Program name, then click
Assign.

RESULT: The Select Daily Program dialog box displays. The existing daily
programs for the Time Program display in the list box.

Click desired program name, then click OK.

RESULT: The dialog box closes and the Assign daily program(s) to week
days dialog box redisplays. The new Daily Program assignment is
in the list box.

3. When through assigning Daily Programs, click OK.

RESULT: The dialog box closes and software assigns the last-assigned Daily
Program to the weekdays that were not specified, in this case the
daily program "Standard".

121 EN2Z-0937GE51 R0518


QUICK TOURS CARE

Example:

Monday Weekday
Tuesday Holiday
Wednesday
Thursday
Friday
Saturday
Sunday

Software assigns “Holiday” to Wednesday through Sunday


because Holiday was the last Daily Program assigned.
The Time Program window redisplays.

Holiday Program and Yearly Programs To create Holiday and Yearly Programs, please refer to the Holiday Program
Function and Yearly Program Function sections.

Design and Configure C-Bus Network


NOTE: For information on the BACnet-Bus network structure in CARE-BACnet,
please refer to the "BACnet Network Structure" section.

NOTE: For detailed instructions on LON network engineering, please refer to the
LonWorks Network Engineering chapter.

Purpose To structure the C-bus according to conditions in the building.

Default Network Structure By default, the network tree shows the two basic bus types, Bus (=C-Bus) and LON-
Works.

Each bus is sub-divided by default to allow an arrangement of the network


components according to the physical conditions in the building.

EN2Z-0937GE51 R0518 122


CARE QUICK TOURS

Bus

The C-Bus (Bus) folder contains the Bus 1 subfolder by default. Further created
subfolders will be numbered continuously. The Bus subfolders represent the
physical C-Bus network structure of the project and contain the C-bus controllers
which control that segment of the building.

NOTE: The subfolder names are examples and freely editable. For example, the
default Bus 1 subfolder can be named into Area1 or Block A.

Create C-Bus Subsystems

Procedure 1. With left mouse key, select the physical Bus folder in the network tree.

123 EN2Z-0937GE51 R0518


QUICK TOURS CARE

2. Click right mouse key and with left mouse key, click Create Bus in the context
menu.

RESULT: The new subsystem folder will be added below the Bus folder.

3. On the Properties tab on the right pane, edit the name in the (Sub)System
Name field, if desired, and click on the created subsystem folder below the Bus
folder.

RESULT: The new named subsystem folder displays.

4. For further information on the Subsystem Properties, please refer to the Create
C-Bus Subsystems section under LONWORKS NETWORK ENGINEERING.

5. To position controllers in Bus subsystems, please refer to the Create and Place
Controller in the Network tree section.

Create and Place Controller in the Network tree

When creating a controller via the New Controller dialog, the Bus subsystem where
the controller should be placed in, can be selected in the Bus Name drop-down
listbox.

Controllers can also be moved between different subsystems by Drag&Drop as


described in the Move Controllers in the Network Tree by Drag&Drop section.

EN2Z-0937GE51 R0518 124


CARE QUICK TOURS

Move Controllers in the Network Tree by Drag&Drop

In the C-C-Bus part of the network tree, controllers can be moved between different
subsystem folders.

IMPORTANT
Do not move controllers which are already bound to other devices. First,
move the controller and then do the binding.

Procedure 1. In the source folder, select controller (controller device), drag it to the desired
target folder and drop it.

Move CONT2
to the Bus 2
folder

Example 7: Move C-Bus Controller between Bus Subsystems

For detailed instructions on LON network engineering, please refer to the LonWorks
Network Engineering chapter.

Startup Controller
NOTE: This section applies to CARE XL-5000 only. Some steps are more or
less the same in CARE-BACnet. For specific details on starting up an
Excel Web Controller, please refer to the Setup Excel Web Controller
section.

Starting up a controller includes the following steps:

1. Physical connection
2. Translation
3. Download
4. Commissioning (LON controllers only)

Physically Connect to Controller


Purpose Physically connect controller to Excel CARE PC so that CARE can upload or
download to the controller database.

Requirements The PC must be within 49 ft. (15m) of the controller. At greater distances (up to
3281 ft. [1000m]), you must add a line driver.

Use a XW585 Connection Cable.

Procedure 1. Insert plug on the XW585 connection cable into the socket on the front of the
controller computer module.

2. Insert the other plug on the XW585 connection cable to the serial interface
socket on the back of the PC (COM 1 or COM 2).

3. Power on the PC.

4. Start XL Online as described in the Start XL Online section.

125 EN2Z-0937GE51 R0518


QUICK TOURS CARE

Translate Controller
Purpose Convert the files for an attached plant to a form suitable for download into the
controller.

Procedure 1. In the logical plant tree, select the controller, you want to translate.

2. Click menu item Controller, then drop-down item Translate or, click the
Translate button in the button bar.

RESULT: If there are errors in the application, the Check controller


application window displays. To solve a problem, read the cause of
the issue in the Text column. For datapoint issues you can jump to
the datapoint by double-clicking on the corresponding line.

3. After you have solved the problems and closed the Check controller application
window, repeat step 2.

RESULT: CARE finishes the translation. The execution messages are shown
in the Honeywell CARE DDC-Translator window.

EN2Z-0937GE51 R0518 126


CARE QUICK TOURS

4. Click End button to exit the translate function.

5. Click Print button to print the translation result.

Download Controller
Purpose Copy translated files to the CARE XL-5000 controller.

NOTE: For copying files into a BACnet controller, please refer to the "Download
Application into Excel Web Controller" section.

Prerequisites The controller must be connected to the CARE PC and translated.

Procedure 1. Click menu item Controller, then submenu item Tools and XL Online.

RESULT: The XL Online main window displays. Software tries to connect


to the port according to the settings defined in the XL Online
dialog box (see Define Port Settings section).

If no controller is connected to the port or software cannot


connect to the controller due to wrong port settings, the XI
581/2 MMI is gray and the status message No connection is
displayed.

If the connection is completed and no application is running, the


MMI is blue and blank. If an application is running, the MMI is
blue and the initial text is shown.

2. If the MMI is gray, connect the controller to the port as follows:

3. Click menu item File, then submenu item Connection.


Or, click on the Change serial port settings icon on the button bar.

RESULT: The Connect dialog box displays.

127 EN2Z-0937GE51 R0518


QUICK TOURS CARE

4. Select the serial port and the baudrate by clicking the corresponding radio
buttons. Select Auto detect, if you do not know the baudrate (default setting).

5. Click the Connect button.

RESULT: If the connection could not be completed, a status report is


displayed with the message that CARE is unable to establish
the connection. If the connection could be completed, the MMI
is invoked in blue and the initial text is shown, if an application
is running. If no application is running the MMI is blank.

6. If no application is running, reset the controller by pressing the Reset button at


the controller.

7. Make sure that the controller number in CARE and in the MMI is the same. If
they are different, set them equal either in CARE or in the MMI. For operating
instructions of the MMI refer to the XI581/2 Operator Terminal Manual.

8. Click the Controller tab.

RESULT: Controller status information is listed.

EN2Z-0937GE51 R0518 128


CARE QUICK TOURS

9. Check the information.

10. Click menu item controller, then submenu item Download


or,
click on Download to Controller icon on the toolbar.

RESULT: The Application download dialog box displays.

129 EN2Z-0937GE51 R0518


QUICK TOURS CARE

RESULT: On the top, the path of the previously downloaded application is


displayed.

11. If you want to download a new application, click Application button and select
the desired application (.pra file).

12. Click Start download button if you want to download the previously downloaded
application or the new application.

RESULT: Depending on the kind of application you want to download,


different messages can appear (see What kind of Application to
Download section).

The download starts. Action and status messages will be listed


while the download proceeds.

EN2Z-0937GE51 R0518 130


CARE QUICK TOURS

13. Click the Close button when the download is finished.

131 EN2Z-0937GE51 R0518


QUICK TOURS CARE

RESULT: Eventually alarms are generated as indicated by the flashing


alarm icon on the Alarms tab.

14. Click the Alarms tab, check the messages and perform appropriate trouble-
shooting procedures if necessary.

Commission LON Controller / LON Device / LonWorks Network


NOTE: Commissioning applies to LON controllers and LON devices only.
Commissioning is the final necessary step in order to complete the
startup a LON controller. For more information on LON engineering,
please refer to the LonWorks Network Engineering section.

Purpose The commissioning process is the software supported startup of a LON node and
executes the following steps:

• Addressing (network address)


• Binding (binding information of NVs)
• Configuration (parameters)

In CARE, it is possible to commission single devices, all devices of a system (top-


level system such as the Default System) or subsystem), or the complete LonWorks
network.

When commissioning all devices of a system or the network, only those devices will
be commissioned which network interface had been changed in CARE since the
latest commissioning, that is, the current state of the device is different to the
current state in CARE.

Prerequisites The controller must be connected to the CARE PC, translated and downloaded.

Procedure 1. In the network tree, click on the desired item (LonWorks folder = complete
network, system folder = all devices of the system, or the device) you want to
commission.

2. Click right mouse key and with left mouse key, click Commission.

EN2Z-0937GE51 R0518 132


CARE QUICK TOURS

RESULT: For any device which is not addressed yet, the Get Service Pin
dialog box displays asking you to press the service pin. Press the
service pin and Click OK. After all devices have been addressed,
they will be commissioned. Commissioned devices are indicated by
the fully colored green display of the devices in the network tree as
well as on the device status icon on the devices.

133 EN2Z-0937GE51 R0518


QUICK TOURS CARE

Generate Documentation
Purpose Print reports showing system operation and parameters. Also, you can output a
variety of file types to supplement job documentation. For example, you can create
graphic metafiles (.WMF extension) that are a plant’s schematics, control loops,
and switching tables. You can also create spreadsheet files that contain information
useful for pricing (Data Export function).

CARE provides printing of:

• Complete projects
• Controller(s) with attached plants
• Unattached plants

IMPORTANT
Printing complete projects is not recommended because this results in
Word documents that exceed 1000 pages and file in excess of 40
Megabytes. These large documents cause Word for Windows to become
very slow.

Procedure 1. Click menu item Database, then submenu item Print.


Or, in the logical plant tree, right-click on the controller, plant or project and with
left mouse key, click on Print in the context menu.Use Database/Select to
select the controller, plant or project you wish to print.

2. Select Database/Print....

RESULT: The printout main dialog box is displayed showing the options for
printout. Depending on the application (controller, plant, project)
selected, not all options are available and grayed therefore. For
example, for plants you can only print table of contents, project
data sheet, plant schematic, control strategy loops, switching logic
tables and parameter list sorted by usage.

3. Check the options that you wish to print.

EN2Z-0937GE51 R0518 134


CARE QUICK TOURS

4. Press the Print button in order to print directly or alternatively press the File
Output... button to store the printout in a file that can be edited by Word.

NOTES: You may want to have different page breaks or change the layout of
tables, etc. To optimize the page breaks and document layout,
Microsoft Word for Windows can be used to edit the document.

RTF (Rich Text Format) is a text format that can be accessed by


Word. This format has been selected for the printout, because it is
much more reliable than the DOC format. After loading a file into
Word, it might be saved also as DOC or any other Word supported file
format (refer to the Word user’s manual).

135 EN2Z-0937GE51 R0518


QUICK TOURS CARE

EN2Z-0937GE51 R0518 136


CARE

BEYOND THE BASICS


PROJECTS DEFINITION AND MANAGEMENT
CONTROLLERS DEFINITION, ATTACHMENT AND MANAGEMENT
PLANTS DEFINITION AND MANAGEMENT
PLANT SCHEMATICS
CONTROL STRATEGY
SWITCHING LOGIC
EDITORS
TIME PROGRAMS
TERMINAL ASSIGNMENT FUNCTION
FILE MANAGEMENT
DOCUMENTATION

137 EN2Z-0937GE51 R0518


CARE

EN2Z-0937GE51 R0518 138


CARE PROJECTS DEFINITION AND MANAGEMENT

PROJECTS DEFINITION AND MANAGEMENT


Purpose This chapter describes how to define and select a project as well as other project
management functions in CARE, for example, how to change existing project
information.

Project Definition A project is a set of controllers with attached plants communicating via bus. A
project can cover multiple of different buses (C-Bus, LON-Bus etc.) building up a
network.

Example of a project with four plants and three controllers:

Project - Honey well Towers

Heating Plant Controller 1

Chiller Plant Controller 2

Air Handler 1 Controller 3

Air Handler 2

You can assign more than one plant to a controller. You cannot assign the same
plant to more than one controller.

In addition, general information such as reference number, client name, and order
number are part of the project.

CARE organizes plants by project. The first step when you start CARE is to select a
project. If none exists, or if you need a new one, you can define a new project.

Chapter Contents Create New Projects


Open Existing Projects
Change Project Password
Display and/or Modify Project Information
Rename Projects
Rename User Addresses
Delete Projects
Rename Datapoints
Delete Unused Datapoints

See Also ⇒ File Management chapter for procedures to delete, back up, and restore projects

Create New Project


Purpose Define project name, password, and general information such as reference number,
client name, and order number. This information appears in the final documentation
for the project, is used in pricing estimates, and controls access to the projects.

Procedure 1. Click menu item Project, then drop-down item New.

RESULT: The New Project dialog box displays.

139 EN2Z-0937GE51 R0518


PROJECTS DEFINITION AND MANAGEMENT CARE

CARE-XL-5000: New Project dialog box

EN2Z-0937GE51 R0518 140


CARE PROJECTS DEFINITION AND MANAGEMENT

CARE-BACnet: New Project dialog box

2. Enter information in all fields of the box. Do not leave any fields blank. In some
fields defaults are displayed, which are defined in the ProjectsDefaults section
of the CARE.INI file:

Project Name
Name of project, for example, site location. First character must be a letter.
There cannot be any spaces; use an underscore, _, to separate words, if
desired. Maximum 32 alphanumeric characters.

NOTE: For LON projects where a synchronization is highly probable to be


done, the number of alphanumeric characters of 16 must not be
exceeded.

Description
Default Text about the project that may help to identify it. Approximate
maximum 30 alphanumeric characters. Default display is defined in the
CARE.INI file.

Reference number
A number that further describes the project. For example, enter branch
number. Numeric characters only (0-9). Approximate maximum 9 numeric
characters. Default display is defined in the CARE.INI file.

Customer
Customer name. Approximate maximum 30 alphanumeric characters; Default
display is defined in the CARE.INI file .

141 EN2Z-0937GE51 R0518


PROJECTS DEFINITION AND MANAGEMENT CARE

Order number
Number assigned to project order. Approximate maximum 10 numeric
characters (0-9). Default display is defined in the CARE.INI file.

Discount
Percent of discount from list price. Maximum two numbers (0-99). This value is
available to the data export file that can be used in an Excel spreadsheet.
Default display (1) is defined in the CARE.INI file.

Job Factor
Difficulty factor (0 through 99.99). If you enter a number with more than two
decimal places, software truncates the entry to two decimal places after you
click OK. For example, if you enter 15.045, software saves 15.04. If you enter a
number with more than two integer digits, software displays an error message
and lets you enter another value. Default display (1) is defined in the CARE.INI
file.

When calculating project costs, software multiplies additional services in the


estimate with this factor. Job factor can result in an increase or decrease in
total costs. This value is available to the data export file that can be used in an
Excel spreadsheet.

Controller Number Offset (BACnet Project only)


The number of the first controller in the project will be equal to the controller
number offset plus 1.

Project Engineer
Name of responsible project engineer. Approximate maximum 20 alphanumeric
characters. Default display is defined in the CARE.INI file.

Date
Date of most recent project modification. Approximate maximum 20
alphanumeric characters.

User Addresses
Whether you want non-unique or unique user addresses in this project. Unique
is the default. You cannot change this assignment after you create a project.
The following text explains the implications of the two choices.

It is recommended that you select “unique” addresses. Enabling this feature


tells software to check for duplicate nonglobal, uncommon points within the
controller and project (a project is a bus) as you create points in the other
CARE functions (schematics, control strategy, etc). If software detects
duplicate points, software issues a warning message. You cannot attach a
controller that has duplicate nonglobal or uncommon points. If a controller is to
be used with a central (for example, Excel Building Supervisor [XBS] or Excel
Building Supervisor-Integrated [XBS-i]), the addresses must be unique.

Global points are points that send their information to receiver pseudopoints in
other controllers. The points have the same user addresses. Global points are
meant to be duplicated and used by multiple controllers.

Common points are used multiple times in the same controller but in different
plants. For example, the ahu1 and ahu2 plants in controller 1 can use the same
outdoor air temperature sensor in their schematics. The sensor is considered a
common point to two plants.

Selecting “unique” also allows you to modify user addresses in the Schematic
function when you select an element that is already in a previous plant. When
software encounters a repeat element, it displays the following message:

User address already exists, create nevertheless?

There are two buttons in the message box, OK and Cancel.

If you click OK, software creates the element with the same user address as
before. This action is desirable in the case of common points.

EN2Z-0937GE51 R0518 142


CARE PROJECTS DEFINITION AND MANAGEMENT

If you click Cancel and the element is a segment (not a Point Without a
Graphic), software creates the element and appends a number to a user
address. For example, a user address of OaTemp becomes OaTemp1. If the
element is selected again in another plant and you click Cancel again,
software appends a 2 (that is, OaTemp2). You can also change user
addresses later when you use the Editors.

If you click Cancel and the element is a Point Without a Graphic, software
does not create a point.

Units of Measurement
Set default for project: International or English. This selection affects the
operation of the icons in Control Strategy that perform EMS operations. The
values for the inputs and outputs are different depending on the selection of
International or English units. See Excel CARE Control Icons User Guide 74-
5577 (US) / EN2B-0184 (Europe) for more information.

Character Set (BACnet Project only)


The appropriate character set is necessary for unobstructed communication
between devices on the BACnet bus. For proper communication between Excel
Web controllers and the EBI central, the ANSI character set must be selected.

IMPORTANT
CARE does not check for entering any illegal characters. If ANSI X3.4 has
been choosen, you can enter characters like é, è, ä, ö, or ü without any
warning. If ISO-Latin-1 has been chosen, you can enter the Euro sign,
which is no Latin-1 character, without any warning.

ProjectSubdirectory
According to the description entered in the Project field, a subdirectory where
the project and the controller files are saved is concurrently set under the
CARE\projects directory. The entry can have max. 8 digits. By default the first 5
digits are taken from the Project Name, which can have a maximum of 18
digits. The last 3 digits are numbers starting with 000 and counting forward
when defining new projects, which start their project names with the same first
5 digits than the first project created.

The entry can be changed during creation of a new project to any desired
name or on the Project´s Properties tab.
With this function you can structure related projects by their names and save
them under different subdirectories.

Example:
Project Name Project Subdirectory
AirportTerminalA Airpo000
AirportTerminalB Airpo001
AirportTerminalC Airpo002

Email Alarming (BACnet Project only)


Shows the default email address used for the Email Alarming of the controller
in the Global Sender EMail Address field. The default is defined in the Global
Options dialog as described in the Set Global CARE Options section. You can
change the email address here if the email address displayed does not match
the email address you want to use for email alarming or if you use different
email addresses for email alarming in multiple projects.

3. Click OK (or press Enter key) to close dialog box and create project. All fields
must have entries or the OK button is inactive.

RESULT: In CARE-XL 5000, the Edit Project Password dialog box displays.

143 EN2Z-0937GE51 R0518


PROJECTS DEFINITION AND MANAGEMENT CARE

NOTE: In CARE XL 5000, the input of a password is not necessary. If


applied, a password must have at least 5 characters and can have
maximum 15 characters. For the password, any combination of
numbers, letters, and special characters like commas are possible.

RESULT: In CARE-BACnet, the Edit project passwords dialog box displays.

NOTE: In CARE-BACnet you must enter the following three passwords:

SystemAdmin
Allows general access to the project for the CARE user and
unlimited web-browser access with SystemAdmin rights. The
System Admin password must have at least 5 characters, but
should have more characters, including upper & lower case, letters,
numbers and special characters. It can have maximum 33
characters

XwAdmin
Allows restricted access to the Linux operating system of the
controller including access to the tool and application directories.
This allows setting up the controller including translation and
connection, application upload and download, download of
settings, download of graphics (UI Suite), firmware upgrade
and reset of the configuration

Root
Allows unrestricted access to the Linux operating system of the
controller via serial interface using a console

FTP user
Allows uploading/downloading diagnostic files via FTP

EN2Z-0937GE51 R0518 144


CARE PROJECTS DEFINITION AND MANAGEMENT

For the root, XwAdmin, and FTP access, CARE proposes visible
passwords. You can change these passwords as described in step
5. The XwAdmin, Root, and FTP passwords have 16 characters
and can have maximum 33 characters.

For all passwords, any combination of numbers, letters, and


special characters like commas are possible and should be used.

4. For a CARE XL 5000 project, type in the password in New Password and
Verify if desired, and then click the OK button. For a CARE-BACnet project
continue with step 5.

CAUTION
If a password was entered, make a note of the password. No one can
work on the project without knowing this password.

5. For a CARE-BACnet project, enter the project password twice in New


Password and Verify. This password is for the CARE user with SystemAdmin
rights. When entering the passwords they are hidden.
In XwAdmin, Root, and FTP user change the visible passwords if desired.

145 EN2Z-0937GE51 R0518


PROJECTS DEFINITION AND MANAGEMENT CARE

6. Then, click the OK button.

CAUTION
Make a note of all the passwords. No one can work on the project
without knowing the SystemAdmin password. No one can setup the
controller in CARE without knowing the XwAdmin password. No one can
access the controller via a console without knowing the Root password.
No one can upload/download diagnostic files without knowing the FTP
user password.

RESULT: The Project is created and displayed twice, in the logical plant tree
and in the network tree. On the right pane, the project properties
are displayed.

CARE-XL-5000: Project Properties

EN2Z-0937GE51 R0518 146


CARE PROJECTS DEFINITION AND MANAGEMENT

CARE-BACnet: Project Properties


9. The following properties are available only after a BACnet project has been
created:

Program ID Offset
The project offset is used for calculating unique program IDs for the network
interfaces if more than one CARE project is used for the same construction
project (see also Enter Project Offset section)

Enable Web Server


If checked, this option provides access to a BACnet controller via Web
Interface.

Enable Comfortable Login


If checked, this option provides the login to the web interface without the
necessity to enter user name and password each time you are logging in.

CAUTION
If checked, make sure that the controller is operated in a closed network or
VPN to avoid misuse through cyber attacks or easy login by other persons
not knowing your password and user name.

Enable QVGA Pages


If checked, the web pages will be displayed in QVGA (quarter VGA = 320 pixels
by 240 pixels) resolution. This is necessary for the proper display of the web
pages in the CL Touch panel.

NOTE: The settings (checked or unchecked) of the Enable Web Server


Enable and Comfortable Login properties will be applied to any

147 EN2Z-0937GE51 R0518


PROJECTS DEFINITION AND MANAGEMENT CARE

controller created afterwards in the project. When changing the


settings again, the settings of the controllers created before the
change will not be reverted. The settings of each controller can/must
then be changed individually.

10. Continue by setting default settings as described under the “Set Global CARE
Options” section.

Change Project Password


Purpose Replace the current password for a project.

Procedure 1. Open the project and click on any item in the logical plant tree.

2. Click menu item Project, then drop-down item Change Password.

RESULT: The Edit Project Password dialog box displays.

3. In the Old Password field, type old password. Tab to the New Password field
and type a new password (maximum 20 characters). Tab to the Verify field and
retype the new password.

4. Click OK to confirm.

Open Existing Project


Purpose Specify a project, plant, and/or controller to work on.

Procedure 1. Click menu item Project, then drop-down item Open.

RESULT: The Project Password dialog box displays.

CARE - XL 5000: Project Password dialog

EN2Z-0937GE51 R0518 148


CARE PROJECTS DEFINITION AND MANAGEMENT

CARE - BACnet: Project Password dialog

2. In Please select a Project, select the project.

3. In Please select an User, select the user (CARE-BACnet only).

4. In Please insert the Project Password !, do any of the following:

a. In CARE-XL 5000, the input of a password is optional when creating a


project. If a password had been issued when the project was created,
enter it. If not, continue with step 5.
b. In CARE-BACnet, enter the System Admin password which had been
issued when the project was created.

RESULT: If the project contains old unsecure passwords for XwAdmin,


ftpuser, and/or Root, the following message box displays:

c. It is recommended to change the passwords. Hence, confirm by clicking


Yes.

RESULT: The Edit project passwords dialog box displays.

149 EN2Z-0937GE51 R0518


PROJECTS DEFINITION AND MANAGEMENT CARE

d. In the XwAdmin, Root, and FTP user fields, change the passwords.

CAUTION
Make a note of all the passwords. No one can work on the project
without knowing the SystemAdmin password. No one can setup the
controller in CARE without knowing the XwAdmin password. No one can
access the controller via a console without knowing the Root password.
No one can upload/download diagnostic files without knowing the
FTPuser password.

5. Click OK.

RESULT: The project is displayed in the logical plant tree and the network
tree. Plants and controllers can be listed by clicking the plus
symbols. On the Properties tab on the right, project data can be
entered/edited.

EN2Z-0937GE51 R0518 150


CARE PROJECTS DEFINITION AND MANAGEMENT

CARE-XL-5000: Project Properties

CARE-BACnet: Project Properties

151 EN2Z-0937GE51 R0518


PROJECTS DEFINITION AND MANAGEMENT CARE

6. On the Properties tab, change project information, if desired. For detailed


description of the fields, please refer to the Create New Project section and the
Enter Project Offset section.

Rename Project
Purpose Rename a project.

Procedure 1. In the logical plant tree, click on the project.

2. On the Properties tab on the right, rename the project in the Project Name field.

3. In the logical plant tree on the left, click on the project.

Delete Project
Purpose Delete a project.

Procedure 1. With right mouse key, click on the project in the logical plant tree.

2. With left mouse key, click on Delete in the context menu.

RESULT: A message box displays.

3. Click Yes to delete the project.

Display/Change Project Information


Purpose Display and/or change project information such as reference number, client name,
and order number.

Procedure 1. In the logical plant tree, click on the project.

2. On the Properties tab on the right, change desired project data.

EN2Z-0937GE51 R0518 152


CARE PROJECTS DEFINITION AND MANAGEMENT

For detailed description of the fields, please refer to the Create New Project section
and the Enter Project Offset section.

Enter Project Offset


Purpose The project offset is used for calculating unique program IDs for the network
interfaces if more than one CARE project is used for the same construction project.
The offset is only effective for controllers being newly created.

Procedure 1. In the logical plant tree, double-click on project name.

153 EN2Z-0937GE51 R0518


PROJECTS DEFINITION AND MANAGEMENT CARE

CARE XL-5000 Project Properties

CARE- BACnet Project Properties

2. From the Offset (CARE XL-5000) respectively Program ID Offset (CARE-


BACnet) drop-down listbox, select an offset value.

EN2Z-0937GE51 R0518 154


CARE PROJECTS DEFINITION AND MANAGEMENT

Export Project Data to Niagara


Purpose For CARE-BACnet and CARE-XL5000 projects, the following project data can be
exported to Niagara in XML format via NIDEX file:

Project name and ID


BACnet-Bus, C-Bus, and LON-Bus properties and their network structure (folders,
subsystems, channels)
BACnet, C-Bus, and LON controllers and devices
BACnet notification classes
Datapoints and their properties
C-Bus parameter files
BACnet schedules and C-Bus timeprograms

NOTE: The control logic and switching logic cannot be exported.

Procedure 1. In the logical plant tree, right-click on the project name.

RESULT: The Export to NIDEX file dialog box displays.

155 EN2Z-0937GE51 R0518


PROJECTS DEFINITION AND MANAGEMENT CARE

2. In the File name field, enter a file name.

3. Click the Save button.

4. In the smartcon message box, click the OK button.

EN2Z-0937GE51 R0518 156


CARE PLANTS DEFINITION AND MANAGEMENT

PLANTS DEFINITION AND MANAGEMENT


Purpose This chapter describes how to define and select plants as well as other plant
management functions that CARE provides, for example, plant replication and
deletion.

CARE functions such as Schematics, Control Strategy, and Switching Logic pertain
to specific plants. The first step when you start CARE is to select a project and then
a plant. If no plant exists, or if you need a new one, you can create a new plant.

Shortcuts You can copy existing plants and then modify the copies to create new plants more
quickly. You can also copy plants to other projects to reuse them.

CARE also provides a library of standard plants that you can use in any project.
See Excel 5000™ Control Application Manual 74-3958 for descriptions of the
applications. The Copy Applications from the Control Application Library section
describes how to load a standard application.

Maximum Plants You can define a maximum of 128 plants per controller.

Chapter Contents Create New Plant


Display/Change Plant Information
View Plant Schematic
Replicate a Plant
Rename a Plant
Copy a Plant
Delete a Plant

See Also ⇒ File Management chapter for procedures to back up and restore plants

Appendix Plant and Controller Upgrades and Downgrades for details on changing
the OS version for a plant

Create New Plant


Purpose Define a plant name, select a plant type and preferred target I/O hardware, and
assign a controller (if desired).

You can define a maximum of 128 plants per controller.

When creating a plant, you can instantly attach the plant to a controller or create it
unattached for later attachment.

Procedure 1. In the logical plant tree, click on the controller, to which you want attach the
plant.
Or, if you want to create an unattached plant for later attachment, click on the
project.

2. Click menu item Plant, then drop-down item New.

RESULT: The New Plant dialog box displays.

157 EN2Z-0937GE51 R0518


PLANTS DEFINITION AND MANAGEMENT CARE

3. Type a plant name in the Name field (the new name cannot match an existing
plant name in the project). Maximum 30 alphanumeric characters; no spaces;
first character cannot be a number.

4. Type a additional description in the Description field (CARE- BACnet only).

5. From the Plant Type drop down listbox (CARE-XL5000 only), select desired
type:

Air Conditioning Air handler or fan system building blocks.


Chilled Water Cooling tower, condenser water pumps, and chiller building
blocks.
Elink Elements that represent system points for Excel 10
Controllers.
Hot Water Boilers, converters, and hot water system building blocks.

MacroCel Air handling unit of moderate control complexity building


blocks

MicroCel VAV box, small central air handler, converter and exhaust
fan building blocks

W7620 Individual HVAC zone equipment

W7620WSHP Water source heat pump building blocks

XLink Master plant that contains the system points for MicroCel,
MacroCel, W7620 and W7620WSHP subsystem plants.

6. From the Plant OS Version drop down listbox select desired version (CARE-
XL5000 only). This number is the OS version of the controller where the plant
will be downloaded. See Appendix for rules on upgrading/downgrading
controller versions.

7. From the Plant Default File Set drop down listbox (CARE-XL5000 only), select
desired plant default file. Plant default files are customized project defaults for
use in specific areas or regions generated in the Default Text editor (see
Default Text Editor section). A short description for the selected default file set
is given below the drop-down list box.

EN2Z-0937GE51 R0518 158


CARE PLANTS DEFINITION AND MANAGEMENT

8. Under Units of Measurement (CARE-XL5000 only), select the desired type for
the plant, International (metric) or Imperial. This selection tells the Control
Strategy EMS icons which type of inputs to accept, Celsius or Fahrenheit. Units
of Measurement applies not to ELink applications.

9. Under Preferred Target Hardware (CARE XL-5000 only), select desired target
I/O hardware:

Standard I/O (XF5..)


(applicable to Excel 500 and 50 with OS 2.0 - 2.06).
Hardware Points of this plant will be assigned to XF5.. modules (IP bus).

Panel I/O (XF8..)


(applicable to Excel 800, OS 3.00 only)
Hardware points of this plant will be assigned to XF8.. modules (panel bus).

Distributed I/O (XFL5..)


(applicable to Excel 500 and Smart with OS 2.0 - 2.04).
Hardware Points of this plant will be assigned to XFL5.. modules. (LonWorks-
bus).

Distributed I/O (XFL8..)


(applicable to Excel 800, OS 3.00 only).
Hardware Points of this plant will be assigned to XFL8.. modules (LonWorks-
bus).

Open LON
Hardware points of this plant will be boardless, that is, unassigned (applicable
to Excel 800 OS 3.0, Excel 500, Smart, 50 with OS 2.06 and higher, and Excel
10)

10. Click OK.

RESULT: If the new name is acceptable, software closes the dialog box. In
the logical plant and network tree, the plant is added below the
controller (plant attached) or below the project (plant unattached).

CARE software performs validation checks for an attached plant while you are
creating schematics, control loops, and switching tables for the plant. For
example, if you attach the plant to an Excel 80 controller, CARE issues warning
messages if you add too many points to the plant schematic.

Restrictions Certain point types are not supported by Open LON. When using OS 2.04, non-
supported types will be put on IP (Excel 500, 50) or distributed I/O modules (Excel
500, Smart), even if Open LON was selected. When using OS 2.06 or 3.0, non-
supported types will be indicated in red in the logical plant tree and must be put
manually on IP boards or Panel I/O boards.

Point types not supported by Open LON:

DO Pulsed Digital Output


FF Flex DO_Feedback_DI
FM Flex Multistage
FP Flex Pulse2
GA Global Analog
GD2 Global Digital 2state
GDn Global Digital Nstate
PT Pseudo Totalizer
TO Totalizer

When Distributed I/O was selected for an Excel 500/800 controller and the
application contains a point type, which is not supported by distributed I/O modules,
these points will be put on standard I/O / Panel I/O modules.

Create Plant Schematic


Please refer to the PLANT SCHEMATICS chapter.

159 EN2Z-0937GE51 R0518


PLANTS DEFINITION AND MANAGEMENT CARE

Add Control Strategy to Plant


Please refer to the CONTROL STRATEGY chapter.

Add Switching Logic to Plant


Please refer to the SWITCHING TABLES chapter.

Display/Change Plant Information


Purpose Display/Change the Plant Information such as plant name, plant type, OS version
with corresponding default file set, engineering unit, and target I/O hardware
selection.

Attached or unattached plant You cannot change any item of attached plants except the target I/O hardware, if
the plant OS version is 2.0 or higher. For unattached plants you can change any
item except plant name and plant type.

Procedure 1. In the logical plant tree, click on plant you want to display/change plant
information for.

2. On the Properties tab on the right, change desired plant data as described in
the following.

3. Plant OS Version is the OS version of the controller where the plant will be
downloaded. Select desired version from the list. Note that depending on the
version number and state of the plant, error messages may occur if you change
Plant OS Version. See Appendix Plant and Controller Upgrades and
Downgrades for details on changing the OS version for a plant.

4. Plant default files are customized project defaults for use in specific areas or
regions generated in the Default Text Editor. Plant Default Files Set includes all
plant default files to the corresponding OS version selected under Plant OS
Version. To select a different file, click the drop down arrow, and then click the
desired file from the list. A short description for the selected default file set is
given below the drop-down list box.

EN2Z-0937GE51 R0518 160


CARE PLANTS DEFINITION AND MANAGEMENT

5. Units of Measurement selection affects the operation of the icons in Control


Strategy that perform EMS operations. The values for the inputs and outputs
are different depending on the selection of International (metric) or Imperial
units. To change Units of Measurement, click desired type, International or
Imperial.

6. Preferred Target Hardware displays the module type that the hardware points
of the plant are assigned to (only applies to OS Versions 2.0 and higher):

Standard I/O (XF5..)


(applicable to Excel 500 and 50 with OS 2.0 - 2.06).
Hardware points of this plant will be assigned to XF5.. modules (IP bus).

Panel I/O (XF8..)


(applicable to Excel 800, OS 3.00 only)
Hardware points of this plant will be assigned to XF8.. modules (panel bus).

Distributed I/O (XFL5..)


(applicable to Excel 500 and Smart with OS 2.0 - 2.04).
Hardware points of this plant will be assigned to XFL5.. modules. (LonWorks-
bus).

Distributed I/O (XFL8..)


(applicable to Excel 800, OS 3.00 only).
Hardware points of this plant will be assigned to XFL8.. modules (LonWorks-
bus).

If desired, change the target I/O hardware by clicking the corresponding


radio button.
Preserve technical address refers to modification of the target hardware
via the Standard I/0 and Distributed I/O radio buttons, if point changes
in the TAF have already been made before (only applies to Excel 500
controller OS Versions 2.0 and higher).

Enabling this checkbox when changing the target hardware results in


the following:

Points that are already assigned to that target hardware type, which will
be changed to, preserve their technical address on the corresponding
module.

Disabling this checkbox when changing the target hardware results in


the following:

Points that are already assigned to that target hardware type, which will
be changed to, may lead to a change of the technical address on the
corresponding module. The Attach process optimizes for best use of
modules.

Open LON
Hardware points of this plant will be boardless, that is, unassigned (applicable
to Excel 800, 500, Smart, 50 with OS 2.06 and higher, and Excel 10)

7. Click OK to confirm.

RESULT: An attached plant will be automatically detached, all empty


hardware modules will be removed and the plant automatically
attached to the selected target hardware.

Restrictions Certain point types are not supported by Open LON. When using OS 2.04, non-
supported types will be put on IP (Excel 500, 50) or distributed I/O modules (Excel
500, Smart), even if Open LON was selected. When using OS 2.06 or 3.0, non-
supported types will be indicated in red in the logical plant tree and must be put
manually on IP boards or Panel I/O boards.
Point types not supported by Open LON:

DO Pulsed Digital Output

161 EN2Z-0937GE51 R0518


PLANTS DEFINITION AND MANAGEMENT CARE

FF Flex DO_Feedback_DI
FM Flex Multistage
FP Flex Pulse2
GA Global Analog
GD2 Global Digital 2state
GDn Global Digital Nstate
PT Pseudo Totalizer
TO Totalizer

When Distributed I/O was selected for an Excel 500/800 controller and the
application contains a point type, which is not supported by distributed I/O modules,
these points will be put on standard I/O / panel I/O modules.

IMPORTANT
When an Excel 50/800 controller is full, that is, the maximum number of
modules has been reached, a change in the plant target I/O hardware will
not be able to create any different module type. Therefore the actual
hardware will not change, even if the setting for the plant is changed. In
this case you have to do manual changes via the Terminal Assignment or
set the Controller to the other target I/O hardware which will affect all
plants.

Change Target I/O Hardware for a Plant


NOTE: This function is only applicable to the Excel 800 with OS 3.0 and Excel
500, Smart and 50 controllers with its relevant OS Versions, 2.0 and
higher.

Purpose Modify target I/O hardware from standard I/O (IP bus modules) to distributed I/O
(LON-bus modules) to Open LON with boardless points and vice versa. All changes
are possible. This allows to create a mixed hardware configuration on the same
controller. To create a unique hardware configuration refer to the ModifyTarget I/O
Hardware for a Complete Controller section.

Procedure 1. In the logical plant tree, click on plant you want to change target hardware for,
in this case an unattached plant.

2. On the Properties tab on the right, select desired hardware by clicking


corresponding radio button under Preferred Target Hardware:
Standard I/O (XF5..)

EN2Z-0937GE51 R0518 162


CARE PLANTS DEFINITION AND MANAGEMENT

(applicable to Excel 500 and 50 with OS 2.0 - 2.06).


Hardware points of this plant will be assigned to XF5.. modules (IP bus).

Panel I/O (XF8..)


(applicable to Excel 800, OS 3.00 only)
Hardware points of this plant will be assigned to XF8.. modules (panel bus).

Distributed I/O (XFL5..)


(applicable to Excel 500 and Smart with OS 2.0 - 2.04).
Hardware points of this plant will be assigned to XFL5.. modules. (LonWorks-
bus).

Distributed I/O (XFL8..)


(applicable to Excel 800, OS 3.00 only).
Hardware points of this plant will be assigned to XFL8.. modules (LonWorks-
bus).

If desired, change the target I/O hardware by clicking the corresponding


radio button.
Preserve technical address refers to modification of the target hardware
via the Standard I/0 and Distributed I/O radio buttons, if point changes
in the TAF have already been made before (only applies to Excel 500
controller OS Versions 2.0 and higher).

Enabling this checkbox when changing the target hardware results in


the following:

Points that are already assigned to that target hardware type, which will
be changed to, preserve their technical address on the corresponding
module.

Disabling this checkbox when changing the target hardware results in


the following:

Points that are already assigned to that target hardware type, which will
be changed to, may lead to a change of the technical address on the
corresponding module. The Attach process optimizes for best use of
modules.

Open LON
Hardware points of this plant will be boardless, that is, unassigned (applicable
to Excel 800 OS 3.0 and Excel 500, Smart, 50 with OS 2.06 and higher, and
Excel 10)

3. Click on the plant icon in the logical plant tree.

RESULT: An attached plant will be automatically detached, all empty


hardware modules will be removed and the plant automatically
attached to the selected target hardware.

Restrictions Certain point types are not supported by Open LON. When using OS 2.04, non-
supported types will be put on IP (Excel 500, 50) or distributed I/O modules (Excel
500, Smart), even if Open LON was selected. When using OS 2.06 or 3.0, non-
supported types will be indicated in red in the logical plant tree and must be put
manually on IP boards or Panel I/O boards.

Point types not supported by Open LON:

DO Pulsed Digital Output


FF Flex DO_Feedback_DI
FM Flex Multistage
FP Flex Pulse2
GA Global Analog
GD2 Global Digital 2state
GDn Global Digital Nstate
PT Pseudo Totalizer
TO Totalizer

163 EN2Z-0937GE51 R0518


PLANTS DEFINITION AND MANAGEMENT CARE

When Distributed I/O was selected for an Excel 500/800 controller and the
application contains a point type which is not supported by distributed I/O modules,
these points will be put on standard I/O modules / panel I/O modules.

IMPORTANT
When an Excel 500/800 controller is full, that is, the maximum number of
modules has been reached, a change in the plant target I/O hardware will
not be able to create any different module type. Therefore the actual
hardware will not change, even if the setting for the plant is changed. In
this case you have to do manual changes via the Terminal Assignment or
set the Controller to the other target I/O hardware which will affect all
plants.

Display Plant Schematic


Purpose Quick view of the plant schematic without editing.

Procedure 1. In the logical plant tree on the left, click on the plant.

2. On the right pane, click on the Schematic tab.

RESULT: The schematic is displayed without the possibility for editing.


For detailed information about editing/creating plant schematics
etc., please refer to the PLANT SCHEMATICS chapter.

3. Use the horizontal scroll bar to view the complete schematic.

EN2Z-0937GE51 R0518 164


CARE PLANTS DEFINITION AND MANAGEMENT

Copy / Replicate Plant


Purpose Create one or more copies of an attached or unattached plant and its information.
A plant can be replicated on controller level and on project level. The replicate
process on controller level is called Copy Plant. The replicate process on project
level is called Replicate Plant. In both processes the plants can be replicated
multiple times.

The replicate function is useful in reducing the amount of time necessary to set up
similar plants in a controller or project. When replicating a plant, the following
information will be copied and changed during the replication process:

• Plant name
• Datapoint names
• LON object names and NV names (only if LON controller is applied)
• Panel bus modules
• MS/TP devices with referenced datapoints
• OPS subsystem names and OPS point names (only if OPS controller is applied)
• Mapping information between LON points, respectively OPS points and CARE
datapoints
• Modbus and M-Bus structure and mappings (on controller level only)

NOTE: When replicating plants on project level, Modbus and M-bus mappings
will be lost and must be re-done manually in the replicated plants of the
target project. When replicating plants on controller level, the Modbus
and M-bus mappings will be kept in the replicated plants of the target
controller.

To get the replication well done, you need to set how the particular information
items should be changed. For the new plant(s), each item to be generated, will be
composed of several, partly freely definable, items.

Example: Creation of plant name

The new plant name can be composed of the following items:

• Project name where the plant belongs to


• Controller name where the plant is attached to
• Plant name (current plant name)
• Custom text (freely definable)
• Counter (numerical and/or alphabetical with incremental step)
• Replicate counter (counts the number of replications)

Rules for Composition The new name, in this case the plant name must be composed of at least one
name (project, or controller, or plant) or custom text and one counter:

IMPORTANT
A counter must be used in any case the times to replicate is higher than 1.

Each name or custom text can be used as variable item which means that the full
text of the source item is taken for composing the new name or as fixed item which
means that the source item is taken with a defined length. The length of the item is
defined by Start and Length, e.g.:

Source item Exhibition with Start = 1 and length = 4 results in Exhi,


Source item AirportMunich with Start = 4 and length = 7 results in portMun

Example: Creating new plant name based on source items with variable length

165 EN2Z-0937GE51 R0518


PLANTS DEFINITION AND MANAGEMENT CARE

Project name Controller Current plant Number of New plant names


name name Replications
AirportMunich TerminalA TerminalA 3
Items selected for composition
Plant name x TerminalA01
Counter (numerical, incremental TerminalA02
step = 1, length format = 2) TerminalA03
Project name x AirportMunich01
Counter (numerical, incremental AirportMunich02
step = 1, length format = 2) AirportMunich03
Project name x AirportMunichTerminalA01
Plant x AirportMunichTerminalA02
Counter (numerical, incremental AirportMunichTerminalA03
step = 1, length format = 2)

Example: Creating new plant name based on source items with fixed length

Project name Controller Current Number of New plant names


name plant name Replications
AirportMunich TerminalA TerminalA 3
Items selected for
composition
Plant name (Start=1, x Term01
length=4) Term02
Counter (numerical, Term03
incremental step = 1,
length format = 2)
Project name (Start=1, x AirpA
length=4) AirpB
Counter (alphabetical, AirpC
incremental step = 1,
length format = 1)
Project name (Start=1, x AirportMunichTerm0A
length=10) AirportMunichTerm0B
Plant name (Start=1, x AirportMunichTerm0C
length=4)
Counter=alphabetical,
incremental step = 1,
length format = 2

The same procedures must be applied in a corresponding fashion for the datapoint
names, the LON items and the OPS items.

Restrictions and Inconsistencies Note, that the max. length for datapoint names is 18 characters in CARE-XL 5000
and 64 characters in CARE-BACnet. For plant names, the max. length is 30
characters. If the new datapoint names are longer than 18 characters in CARE-XL
5000, CARE truncates the letters beyond 18. If the plant name used for datapoint
names creation is more than 18 characters, all new datapoint names are truncated
to the same 18-character name.

The length for NV names is restricted to 21 characters, the length of NV object


names is restricted to 16 characters. Names longer than 21, respectively 16
characters will abort the translation of the application and must be reworked.

EN2Z-0937GE51 R0518 166


CARE PLANTS DEFINITION AND MANAGEMENT

The length for OPS subsystem names and OPS point names is restricted to 32
characters.

Besides long names, CARE will also detect double, non-unique names and the use
of invalid characters. They will be displayed in bold in a tree structured dialog for
changing. For the OPS controller multiple identical names are allowed.

General Procedure For Any Controllers


NOTE: The following procedure describes the main steps for the replication of a
plant for any kind of controller. The additional steps for LON and OPS
controllers will be described in the subsequent sections.

1. In the logical plant tree, click on the plant, you want to replicate or copy.

2. To copy a plant on controller level, right-click the plant in the logical plant tree,
then click Copy plant in the context menu.

3. Or, to replicate a plant on project level, click menu item Plant, then drop-down
item Replicate.

RESULT: The Automatic Name Generation dialog box displays.

The new name of the plant will be composed of several items which are
defined in rows. The new name starts with the first row at position one (Pos 1).
Every further row will add a new item to the previous one building up the new
plant name. By default, 2 rows (Pos1 and Pos 2) are provided by CARE. The
Option 1 column in the Pos 1 row shows the item, which the new plant starts
with (default = plant name).

The following items are available by clicking the drop-down list box:

• Project name
• Controller name
• Plant name
• Replicate
• Counter
• Counter 1..n
• Counter A..Z
• Custom text

167 EN2Z-0937GE51 R0518


PLANTS DEFINITION AND MANAGEMENT CARE

Defining New Plant Names 4. In the Option 1 column of Pos 1 row, select Project name, for example. The
project name, in this case ´HVAC` is displayed in the Example column.

5. If you want to use the whole project name for the new plant name, check
checkbox in the Variable column.
If you want to use a part of the project name, uncheck the Variable checkbox
and define the part by selecting its start in the Start column and its length in the
Length column.

Example: Project name = Beta_Sec1, Start = 1, Length 4


Result = Beta

The result, in this case ´HVACBeta` is displayed at the bottom of


the dialog box.

6. If required, add new row(s) for further item(s) to be included into the new plant
name by clicking right mouse button and selecting Add Row.

7. Select third component for the new plant name in the Option 1 column of the
Pos 3 row. For example, select Custom text. As described for the second row,
where project name was selected, define whether the custom text should be
used as variable full text or as name with fixed length. Enter the custom text, for
example an underscore ´_`.

8. Select fourth component for the new plant name in the Option 1 column of the
Pos 4 row. For example, select Counter A..Z as alphabetical counter. In the
Option 2 column, set the increment for the counter. Define the Start of the
counting in the Start column.

Example: Option 1 = Counter A..Z, Option 2 = 1.00 (increment), Start = A

EN2Z-0937GE51 R0518 168


CARE PLANTS DEFINITION AND MANAGEMENT

RESULT: A counter in single-digit format starting with A and


incremental step of 1.

IMPORTANT
A counter must be used in any case the times to replicate is higher than 1.

9. Into the Number of Times to Replicate field, enter the number of times for
replication.

10. If the plant is replicated on controller level (see step 2), select the controller, to
which the replicated plants should be assigned from the Select Destination
Controller drop-down listbox.

11. If the plant is replicated on project level (see step 3), select the controller, to
which the replicated plants should be assigned from the Select Destination
Project drop-down listbox.

12. Continue with step 13 and define datapoint names for the replicated plants.

Defining New Datapoint Names 13. Click on Datapoint Name tab.

RESULT: CARE provides 3 rows by default.

14. Compose the new datapoint names in a corresponding fashion by following the
rules for composition you applied when composing the new plant names.

169 EN2Z-0937GE51 R0518


PLANTS DEFINITION AND MANAGEMENT CARE

NOTE: When using ´Generated Plant Name`, a replicate counter does not
have to be used.

15. Click OK.

RESULT: In the following cases, messages will be displayed to inform you


about inconsistencies in the replicated plants:

• plant and/or datapoint names are too long


• plant and/or datapoint names are not unique
• plant and/or datapoint names include invalid characters,
e.g. quotation marks

Nevertheless, the Confirm Generated Names dialog box is


displayed showing all generated plants in a tree.

16. If messages about inconsistencies were displayed before, open the tree to
check the result. Inconsistent names are displayed in bold.

17. To edit inconsistent names which are too long or non-unique or which include
invalid characters, highlight name and click on it.

18. If desired, edit correct names, which you want to edit explicitly.

19. Confirm by clicking OK.

RESULT: The replicated plants are now available in the controller,


respectively in the project.

NOTE: When using the Replicate command again, the last generated
rules are preset by default.

Background Process of BACnet Controllers

EN2Z-0937GE51 R0518 170


CARE PLANTS DEFINITION AND MANAGEMENT

Plants of BACnet controllers can have its datapoints assigned on panel I/O modules
and MS/TP devices.

For each type of target hardware, the general plant copy procedure which defines
the plant names and datapoint names is the first step to be done (see "General
Procedure For Any Controllers" section") first.

In the second step, CARE completes the copy process for the panel I/O modules
and the MS/TP devices in the background.

Panel I/O Modules Process The datapoints in the plant of the source controller will be copied and assigned to
panel I/O modules of the same type in the destination controller. If panel I/O
modules of the same type do not exist in the destination controller, they will be
created.

MS/TP Devices Process Essential prerequisites for copying MS/TP devices are:

• In the source controller: external reference points (BACnet objects) of the MS/TP
device are assigned to reference input or output points of the plant
• In the destination controller: MS/TP bus is available

The MS/TP device with its external reference points in the source controller will be
copied and added to the MS/TP bus in the destination controller. The associated
reference input and output points in the plant of the source controller will be copied
to the destination controller according to the settings for plant and datapoint names
defined in the general procedure.

NOTE: The background process for BACnet controllers does not apply to the
replicate plant function.

Additional Procedure For LON Controllers


IMPORTANT
Note that the restriction of the name length is 21 characters for NV
names and 16 characters for NV object names. Names longer than 21,
respectively 16 characters will abort the translation of the application
and must be reworked.

Defining New LON Object Names 1. Follow the General Procedure steps 1-19 and in addition...

2. ...Click on LON Object Name tab.

171 EN2Z-0937GE51 R0518


PLANTS DEFINITION AND MANAGEMENT CARE

3. Compose the new LON object names in a corresponding fashion by following


the composition rules you have applied when composing the new plant names
as described in the general procedure for any controllers.

4. Continue with step 5 and define new NV names for the replicated plants.

Defining New NV Names 5. Click on NV Name tab.

6. Compose the new NV names in a corresponding fashion by following the


composition rules you have applied when composing the new plant names as
described in the general procedure for any controllers.

7. Continue by defining new system names as described in the following:

Defining New System Names Note, that LON devices are arranged in the logical LON bus part of the network
tree, for example, LON devices controlling a floor may reside in the "Floor" folder. In
case you want to replicate, for example, the "Floor" folder with all its devices, the
following has to be considered:

CARE replicates the folder and all devices, bound or unbound, residing in the
folder.

IMPORTANT
CARE checks all system folders (default and subsystems) for bound
devices and takes that folder which hierarchically includes all
interconnected devices. Note, that unbound devices residing in the
included folders will be replicated too.

Example:

The "Floor" system should be replicated. Some devices residing in the "Floor"
folder are bound to the "SMART" controller. Since the SMART Controller resides
in the "Building" system lying one level above, the Building folder will be used as
top level folder and replicated too.

IMPORTANT
To avoid undesirable, confusing replication results, move the controller
device temporarily to the system folder you want to be replicated, in this
case to the Floor folder. After the replication has been finished, move it to
the original folder.

EN2Z-0937GE51 R0518 172


CARE PLANTS DEFINITION AND MANAGEMENT

8. Click on System Name tab.

9. Compose the new System names in a corresponding fashion by following the


composition rules you have applied when composing the new plant names as
described in the general procedure for any controllers.

10. Click on Device Name tab.

11. Compose the new device names in a corresponding fashion by following the
composition rules you have applied when composing the new plant names as
described in the general procedure for any controllers.

12. Click OK.

RESULT: The Confirm Generated Names dialog box is displayed showing all
generated names in a tree structure.

13. If any inconsistent bold names were generated, edit them.

14. Confirm by clicking OK.

NOTE: When using the Replicate command again, the last generated
rules are preset by default.

15. Attach the replicated plants to the controller.

RESULT: The replicated plants are now available in the controller,


respectively in the project.

NOTE: When using the Replicate command again, the last generated
rules are preset by default.

Additional Procedure For OPS Controllers


NOTE: The following OPS controller related tabs are only displayed if the current
controller is an OPS controller.

IMPORTANT
Note that the length for OPS subsystem names and OPS point names
is restricted to 32 characters, but multiple identical names are allowed.

173 EN2Z-0937GE51 R0518


PLANTS DEFINITION AND MANAGEMENT CARE

Defining new OPS Subsystem Names 1. Follow the General Procedure steps 1-19 and in addition...

2. ...Click on OPS Subsystem Name tab.

3. Compose the new OPS subsystem names in a corresponding fashion by


following the composition rules you have applied when composing the new
plant names as described in the general procedure for any controllers.

4. Continue with step 5 and define new OPS point names.

Defining new OPS Point Names 5. Click on OPS Point Name tab.

6. Compose the new OPS point names in a corresponding fashion by following


the composition rules you have applied when composing the new plant names
as described in the general procedure for any controllers.

7. Click OK.

RESULT: The Confirm Generated Names dialog box is displayed showing all
generated names in a tree structure.

8. If any inconsistent bold names were generated, edit them.

9. Confirm by clicking OK.

RESULT: The replicated plants are now available in the controller,


respectively in the project.

NOTE: When using the Replicate command again, the last generated
rules are preset by default.

Delete a Plant
Purpose Remove a plant from a project if it is no longer required.

Procedure 1. In the logical plant tree, click on the plant, you want to delete.

2. Click menu item Plant, then drop-down item Delete.


Or, click right mouse key and with left mouse key click on Delete in the context
menu.

EN2Z-0937GE51 R0518 174


CARE PLANTS DEFINITION AND MANAGEMENT

175 EN2Z-0937GE51 R0518


CONTROLLERS DEFINITION, ATTACHMENT AND MANAGEMENT CARE

CONTROLLERS DEFINITION, ATTACHMENT, AND MANAGEMENT


Purpose This chapter describes CARE functions that relate to controllers, for example,
defining new controllers and uploading and downloading them.

Chapter Contents
• Create New Controller
• Attach/Detach Plant
• Copy a Controller
• Rename Controller
• Delete Controller
• Display and/or Modify Controller Information
• Translate Controller
• Download Controller

See Also Appendix Plant and Controller Upgrades and Downgrades for details on changing
the OS version for a controller.

Create New Controller


Purpose Create a new controller

Procedure 1. In the logical plant tree, click on the project.

2. Click menu item Controller, then drop-down item New.


Or, click right mouse key and with left mouse key, click on Create Controller in
the context menu.

RESULT: The New Controller dialog box displays.

EN2Z-0937GE51 R0518 176


CARE CONTROLLERS DEFINITION, ATTACHMENT AND MANAGEMENT

3. Type a controller name (must be unique within the project). In this example,
CONT02.

Maximum 15 characters. Note that software uses only the first four characters
of the controller name followed by a 4-digit number to name the database files
for the controller. For example, the name controller_1 has associated data files
named cont0000. The name controller_2 has associated data files named
cont0001.

4. Tab to Bus Name (CARE XL-5000) or Subsystem/Subnet Name (CARE-


BACnet). This field allows to select the subfolders, where the controller should
be arranged. By default, software creates a folder named "Bus 1" (CARE XL-
5000) and “IP-Subnet 1” (CARE- BACnet).

5. Tab to Controller Number. Click down arrow and select a number from 1
through 30. It must be unique within the C-Bus segment, defined under C-Bus
name. In this example, 2.

NOTE: CARE- BACnet, please note if a controller offset has been issued
during project creation. If this is the case, only a controller number
higher than the entered offset can be set here.

For changing the controller number later, please refer to the


Display/Modify Controller Information section.

6. Tab to Controller Type. Tab to the next field to keep current type or click down
arrow to display and select a different type.

7. Tab to Controller OS Version (the version of OS that will be running in the


controller). Note that any plant attached to this controller must abide by the
rules of this version or you cannot attach the plant. Tab to the next field to keep
the current version or click down arrow to display and select a different version.
See Appendix for rules on upgrading/downgrading controller versions.

8. Tab to Country Code (CARE XL-5000) or Location (CARE- BACnet). The


operator interface is required to provide the correct language for the selected
country. The default depends on the Windows version installed. Tab to the
next field to keep it or click down arrow to display and select a different country.

NOTE: For Excel 500 Ver. 1.2 Controllers, the only valid country codes are
Germany and United States. Other countries appear in the list box,
but United States is always the selection if you select anything
other than Germany.

9. Tab to Default File Set. Select the appropriate default file for the selected
Controller OS Version. Alternate default files are created via the Default Text
Editor. See Appendix for details. A short description for the selected default file
set is given below the drop-down list box.

10. Tab to Units of Measurement. Select whether the controller should use
International (metric) or Imperial units in Control Strategy EMS icons. This
selection controls whether inputs are accepted in Celsius or Fahrenheit. Units
of measurement does not apply to Excel 600 and Excel ELink controllers.

11. Tab to Hardware Type (CARE- BACnet only). Select the hardware type.

12. Tab to Power Supply. Select desired module type. Power supply applies only to
Excel 800, 500 and 600 controllers.

13. Tab to Installation Type. Normal installation is the default selection. If the
controller has high-density digital inputs, select Cabinet Door Installation.
Installation Type applies only to Excel 800, 500 and 600 controllers.

14. Tab to Wiring type and select desired type (screw terminals or flat strip
cabling). Wiring type applies only to Excel 50 controllers.

15. Tab to LON (applies only to Excel 500 controllers OS version 2.04). Select
desired configuration:

177 EN2Z-0937GE51 R0518


CONTROLLERS DEFINITION, ATTACHMENT AND MANAGEMENT CARE

Shared / Open LON


Allows multiple controllers with its distributed I/O modules residing on one
physical LON-bus and/or integration of additional Open LON devices.

NOTE: For this configuration, the controller must contain the 3120E5 LON
chip. In Shared configuration only the following distributed I/O
modules can be used: XFL521B, XFL522B, XFL523B, XFL524B.

Local
Allows just one controller with its distributed I/O modules residing on one
physical LON-bus.

NOTE: For this configuration, controllers containing the 3120E5 LON chip and
earlier controller models containing the 3120B1 LON chip can be
used. In Local configuration the following distributed I/O modules can
be used: XFL521, XFL522A, XFL523, XFL524A. If B-types of
distributed I/Os shall be used, the backwards compatibility must be
enabled by pressing the service pin while turning hex switch.

For detailed information on the configuration, please refer to the Select


LonWorks Network Architecture section.

Refer to the Terminal Assignment chapter for assigning the neuron IDs to the
modules.

16. Click OK. (All fields must have an entry.)

RESULT: The dialog box closes and the controller is added once to the
logical plant tree and three times to the network tree.

EN2Z-0937GE51 R0518 178


CARE CONTROLLERS DEFINITION, ATTACHMENT AND MANAGEMENT

17. Continue with creating new plants or attaching already existing plants. For
creating new Plants, see PLANTS DEFINITION AND MANAGEMENT section.
For attaching plants see Attach/Detach Plant section.

Attach/Detach Plant
When creating a plant, you can instantly attach the plant to a controller or create it
unattached for later attachment. Attached plants can be detached from one
controller and instantly attached to another controller or can be left detached at the
project.

An attached plant is displayed below the controller level in the logical plant tree.
An unattached plant is displayed just below the project, respectively the first
controller in the logical plant tree.

A plant can easily be attached/detached by drag&drop.

Detached
plant

Attached
plant

Attach Plant to Controller


Purpose Assign a plant to a controller and determine I/O terminations required in the
controller.

Requirements The controller and the plant being attached must have the same units of measure
(that is, Imperial or International units).

Also, the plant’s OS version must be less than or equal to the controller’s OS
version. For example, if the controller is Ver. 2.06, the plant’s OS must be either
2.06 or 2.04.

If either one or both of these rules is violated, the plant can not be attached.

Check Summary Before you attach a plant to a controller, you may want to view a summary of
controller points to determine whether or not the controller can handle the plant
(menu item Controller, drop-down item Summary).

Plants with unique target hardware Hardware points will be assigned first to existing modules of the selected target

179 EN2Z-0937GE51 R0518


CONTROLLERS DEFINITION, ATTACHMENT AND MANAGEMENT CARE

(Excel 800, 500, Smart, and Excel 50) hardware (IP, Panel I/O or Distributed I/O). New modules will be created until the
maximum number of I/O modules have been reached. If not all points can be
attached, the max. number of hardware modules and points respectively have been
exceeded.

Plants with different target hardware Hardware points will be assigned first to existing modules of the selected target
(Excel 800, 500, Smart, and Excel 50) hardware (IP, Panel I/O, Distributed I/O, or Open LON = boardless points). New
modules will be created until the maximum number of I/O modules have been
reached. In case this limit is reached, remaining points will be attached to
eventually existing free terminals on modules of the other hardware type. If still not
all points can be attached, the max. numbers of hardware points have been
exceeded.

NOTE: If the application for an Excel 500/800 controller contains a point


type, which is not supported by distributed I/O modules such as
fast AI points, a standard I/O / Panel I/O module will be created,
even if Distributed I/O was selected.

IMPORTANT
When an Excel 500/800 controller is full, that is, the maximum number of
modules has been reached, a change in the plant target I/O hardware will not
be able to create any different module type. Therefore the actual hardware will
not change, even if the setting for the plant is changed on the Plant Properties
tab. In this case you have to do manual changes via the terminal assignment or
set the controller to the other target I/O hardware that will affect all plants.

Restrictions Certain point types are not supported by Open LON. When using OS 2.04, non-
supported types will be put on IP (Excel 500, 50) or distributed I/O modules (Excel
500, Smart), even if Open LON was selected. When using OS 2.06 or 3.0, non-
supported types will be indicated in red in the logical plant tree and must be put
manually on IP boards / Panel I/O boards.

Point types not supported by Open LON:

DO Pulsed Digital Output


FF Flex DO_Feedback_DI
FM Flex Multistage
FP Flex Pulse2
GA Global Analog
GD2 Global Digital 2state
GDn Global Digital Nstate
PT Pseudo Totalizer
TO Totalizer

Plant Replication You can replicate an attached or unattached plant (menu item Plant, drop-down
item Replicate). Replication of attached plants copies the modifications made in the
Datapoint Editor, for example, alarm limits, etc., as well as control strategies and
switching tables. Note that when you detach a plant, you lose any changes you
made with the Editors (see Editors chapter). Therefore, after you replicate an
unattached plant, you must use the Editors again to make the desired changes to
the original plant as well as each of the new plants.

IMPORTANT
LON data of the plant will not be copied when replicating it.

Assumption The schematic, control strategy, and switching logic for the plant are done. You
must exit these functions before attaching the plant.

NOTE: If the plant has control strategy loop(s) that are incomplete, the attach will
fail. Return to control strategy to complete them.

Procedure 1. In the logical plant tree, click on the unattached plant.

2. Drag the unattached plant to the controller, which you want attach the plant to,
and drop it.

RESULT: The Plant will be added one level below the controller in the logical
plant tree.

EN2Z-0937GE51 R0518 180


CARE CONTROLLERS DEFINITION, ATTACHMENT AND MANAGEMENT

Unused Software Points If there are unused software points in the plant schematic, the unused software
points dialog box displays with a list of those points and an option to delete them, if
desired. For example:

Click the points you want to delete (hold down the Shift key while you click to select
multiple points). Then click Delete for software to delete these unused points. (The
Delete key is not active until you select at least one point.)

Click Continue to close the dialog box. Points that you did not delete remain in the
plant.

Duplicate User Addresses If there is a duplicate user address, software displays a message box with the user
address in the title and allows you to enter a new address for it. Example:

181 EN2Z-0937GE51 R0518


CONTROLLERS DEFINITION, ATTACHMENT AND MANAGEMENT CARE

Type a unique address and click OK to change user address and close the dialog
box. Or, click Cancel to keep the user address as is.

If the point is common to all plants in the controller, you should leave the user
address as is.
Different Default File Sets If the default file sets of the controller and the plant(s) to be attached are different,
the following message displays:

Note, that the default file may be set different (multiple default file sets), although
the OS version of the controller and the plant(s) are the same.

Example:

OS Version 2.0 provides the default file set

xl_2_0

Detach Plant from Controller


Purpose Unassign a plant from a controller and erase its I/O terminations file so that you can
assign the plant to a different controller.

Procedure 1. In the logical plant tree, click on the attached plant, which you want detach.

2. Drag the plant to the project and drop it.

RESULT: The Plant is added on level below the project in the logical plant
tree.

EN2Z-0937GE51 R0518 182


CARE CONTROLLERS DEFINITION, ATTACHMENT AND MANAGEMENT

Detach Plant from one Controller and Attach it to another Controller


Purpose Unassign a plant from a controller and assign it concurrently to another controller.

Procedure 1. In the logical plant tree, click on the attached plant, which you want detach.

2. Drag the plant to the target controller and drop it.

RESULT: The Plant will be added one level below the target controller in the
logical plant tree.

Copy Controller
Purpose Create a new controller by copying the files of an existing controller.

Procedure 1. In the logical plant tree, click on controller, you want to copy.

2. Click menu item Controller, then drop-down item Copy.

Or, click right mouse button and with left mouse button, click on Copy
Controller in the context menu.

RESULT: The Copy Controller dialog box displays with the name of the
currently selected project, controller name, and controller number.
This information displays in the Source field.

183 EN2Z-0937GE51 R0518


CONTROLLERS DEFINITION, ATTACHMENT AND MANAGEMENT CARE

3. Select a project to receive the copy of the selected controller. The Target
Project field defaults to the currently selected project. Click the drop-down
listbox to display and select a different project.

4. In the New Controller Name field, enter a new name for the controller to be
created.

5. From the Bus Name drop-down listbox (CARE XL-5000 only), select the bus
system, in which the controller should be created in the network tree.

6. In the New Controller Number field, enter a number for the controller to be
created.

In the Modify Plant Names box, select whether or not you want software to
modify the plant names in the new controller. If the controller should be copied
in the same project, the plant names must be changed. If so, specify how
software should modify them:

Do not modify Software copies the plant names from the source controller
to the new controller as is. This selection results in
duplicate plant names in the CARE database.
Prefix Text Software modifies the plant names from the source
controller by prefixing them with the text that you enter in
the Text box. The modified names are used in the new
controller.
Append Text Software modifies the plant names from the source
controller by appending the text that you enter in the Text
field. The modified names are used in the new controller.

Click OK to begin the copy.

RESULT: Software displays a message box to remind you to ensure that all
user addresses are unique after the copy.

EN2Z-0937GE51 R0518 184


CARE CONTROLLERS DEFINITION, ATTACHMENT AND MANAGEMENT

CAUTION
In case the controller has bindings and is copied within the same project, all
bindings will be removed and the mappings will be kept

7. Click the OK button to acknowledge the messages.

CAUTION
In case bound LON devices of the controller have bindings to other Excel
5000 controllers these bindings will be broken. The Bindings Problems
dialog box informs you about that fact.

8. Click the Continue button in the Bindings Problems dialogbox if you want to
accept that the bindings will be broken, if not click the Cancel button.

RESULT: Software copies the source controller files to the selected target
project and names and numbers the controller as specified.

For LON controllers, the neuron IDs for the distributed I/O modules
of the copied controller are set to 0 by default.

185 EN2Z-0937GE51 R0518


CONTROLLERS DEFINITION, ATTACHMENT AND MANAGEMENT CARE

The channel and system/subsystem structures of the network tree


will also be copied.

IMPORTANT
Software copies the user addresses without changes. If unique
addresses are required, you must manually change the user addresses.
See Replicate Plant section.

9. On the Terminal Assignment tab, set the neuron IDs for the copied controller
modules.

Rename Controller
Purpose For changing the name of a controller, please refer to the Display/Change
Controller information section.

Delete Controller
Purpose Erase a controller.

Procedure 1. In the logical plant tree, click on the controller, you want to delete.

2. Click menu item Controller, then drop-down item Delete.


Or, click right mouse key and with left mouse key click on Delete in the context
menu.

RESULT: The controller will be deleted.

Display/Modify Controller Information


NOTE: This section applies to CARE XL-5000 only. For the corresponding
description for the FALCON and EAGLE controllers in CARE- BACnet,
please refer to the Display/Modify BACnet Controller Properties section.

Purpose View and/or change controller information such as OS Version, power supply,
installation type, and target I/O hardware.

Procedure 1. In the logical plant tree, click on the controller.

2. On the right pane, click on the Properties tab.

EN2Z-0937GE51 R0518 186


CARE CONTROLLERS DEFINITION, ATTACHMENT AND MANAGEMENT

3. Change Controller Name, if desired.

4. To change the controller number, click on the Change Number button.

RESULT: The Change Controller Number dialog box displays showing the
Name, Number, and Bus Name (C-Bus location) of the selected
controller and all controllers of the project.

187 EN2Z-0937GE51 R0518


CONTROLLERS DEFINITION, ATTACHMENT AND MANAGEMENT CARE

e. From the Change To drop-down listbox, select a different C-Bus


location where the controller should be moved to (CARE XL-5000 only,
optional).

f. Decide whether or not you want CARE to correct global references by


checking/unchecking the Correct Global References checkbox . The
default is to correct the references. If you let CARE correct the
references, it changes the controller number in the files for any other
controllers that link to this controller via global receptor and originator
points.

g. In the list, select a free number (13 in this example) you want to assign
to the currently selected controller (12 in this example).

h. To swap the number of the currently selected controller (12 in this


example) with another controller´s number, click the other controller´s
number in the list. For example if number 6 is assigned to the
XLSMART controller and you selected it, software assigns number 12 to
the XLSMART controller and number 6 to the CONT02 controller after
clicking OK.

i. Click OK.

RESULT: A message box displays reminding you that renumbering


the controller causes the controller application files to be
deleted and requests confirmation that you want to
continue.

f) Click Yes to continue with the renumbering.

5. Change Controller Type, if desired (Excel 800, 500 or 600 only).

EN2Z-0937GE51 R0518 188


CARE CONTROLLERS DEFINITION, ATTACHMENT AND MANAGEMENT

6. Change Controller OS Version (the version of OS that will be running in the


controller), if desired. Note that any plant attached to this controller must abide
by the rules of this version or you cannot attach the plant. Select desired
version.

NOTE: For results on changing OS versions refer to Appendix Plant and


Controller Upgrades and Downgrades for details on changing the
OS version for a controller.

7. Change Country Code, if desired. The operator interface is required to provide


the correct language for the selected country. The default depends on the
Windows version installed. Tab to the next field to keep it or click down arrow
to display and select a different country.

NOTE: For Excel 500 Ver. 1.2 Controllers, the only valid country codes are
Germany and United States. Other countries appear in the list box,
but United States is always the selection if you select anything
other than Germany.

8. Change Default File Set, if desired. Select the appropriate default file for the
selected Controller OS Version. Alternate default files are created via the
Default Text Editor. See Appendix for details. A short description for the
selected default file set is given below the drop-down list box.

9. Change Engineering Units, if desired. Select whether the controller should use
International (metric) or Imperial units in Control Strategy EMS icons. This
selection controls whether inputs are accepted in Celsius or Fahrenheit.

10. Click new power supply and/or installation type, as desired.

Normal installation is the default selection. If the controller has high-density


digital inputs, select Cabinet Door Installation. Installation refers only to Excel
500 and 600 Controllers.

11. Click new wiring type for Excel 50 controller, as desired.

12. Change system configuration, if desired, from Shared /Open LON to Local and
vice versa by clicking respective radio button.

IMPORTANT
When changing the system configuration from Shared/Open LON to Local
after a network interface had already been created, the network interface
will not be downloaded.

13. Change Target I/O Hardware, if desired (only applies to Excel 800 OS 3.0 and
Excel 500, Smart, and 50 controller with its relevant OS Versions, 2.0 and
higher):

NOTE: If not already done, you must set the controller OS version to 2.0 or
higher and confirm this by clicking OK, then select the Controller
Properties tab again and set the target hardware by clicking the
desired button:

Standard I/O (XF5..)


(applicable to Excel 500 and 50 with OS 2.0 - 2.06).
Hardware points of this plant will be assigned to XF5.. modules (IP bus).

Panel I/O (XF8..)


(applicable to Excel 800, OS 3.00 only)
Hardware points of this plant will be assigned to XF8.. modules (panel bus).

Distributed I/O (XFL5..)


(applicable to Excel 500 and Smart with OS 2.0 - 2.04).
Hardware points of this plant will be assigned to XFL5.. modules. (LonWorks-
bus).

Distributed I/O (XFL8..)


(applicable to Excel 800, OS3.00 only).

189 EN2Z-0937GE51 R0518


CONTROLLERS DEFINITION, ATTACHMENT AND MANAGEMENT CARE

Hardware points of this plant will be assigned to XFL8.. modules (LonWorks-


bus).

Open LON
Hardware points of this plant will be boardless, that is, unassigned (applicable
to Excel 800, 500, Smart, 50 with OS 2.06 and higher, and Excel 10)

RESULT: At once all plants will be automatically detached, all empty


hardware modules will be removed and the plant automatically
reattached to the selected target hardware. All datapoint attributes
remain unchanged except the technical address.

14. Click on the controller in the logical plant tree.

RESULT: Software saves the changes and closes the dialog box.

Restrictions Certain point types are not supported by Open LON. When using OS 2.04, non-
supported types will be put on IP (Excel 500, 50) or distributed I/O modules (Excel
500, Smart), even if Open LON was selected. When using OS 2.06 or 3.0, non-
supported types will be indicated in red in the logical plant tree and must be put
manually on IP boards / Panel I/O boards.

Point types not supported by Open LON:

DO Pulsed Digital Output


FF Flex DO_Feedback_DI
FM Flex Multistage
FP Flex Pulse2
GA Global Analog
GD2 Global Digital 2state
GDn Global Digital Nstate
PT Pseudo Totalizer
TO Totalizer

When Distributed I/O was selected for an Excel 500/800 controller and the
application contains a point type, which is not supported by distributed I/O modules,
these points will be put on standard I/O modules / panel I/O modules.

Controller Translation
Purpose Convert the files for an attached plant to a form suitable for download into a
controller.

Assumptions The schematic, control strategy, and switching logic for the plant are done. You
have exited those functions and the main CARE window is on display.

Plant attachment is done.

IMPORTANT
Integrated modem communication for CARE versions 1.5 and higher is
only possible for total application sizes of max. 100 kBytes.

Procedure 1. In the logical plant tree, click on the controller.

2. Click menu item Controller, then drop-down item Translate. Or, click the
Translate button.

RESULT: Software begins translation. As it translates, messages and


warnings display in the dialog box.

When the translation is complete, software displays the following


message at the bottom of the dialog box:

RACL generation completed successfully.

3. Check messages to verify proper translation.

EN2Z-0937GE51 R0518 190


CARE CONTROLLERS DEFINITION, ATTACHMENT AND MANAGEMENT

4. If desired, click Start button to re-start the translation.

5. If desired, click Print button to print the translation result. The CARE Translator
stores its messages in a printable file. Software names the file using the last
four letters of the controller name and appending four numbers. For example, if
the name of the controller is AHUCPU1, the name of the print file will be
CPU10001.LST.

6. Click End button to exit the translate function.

Translation Message Examples The following messages are examples for the type of information the translator
displays for a plant.
1. Loadable files
2. Point numbers and names (physical points, global points, pseudopoints,
flex points). There can be a maximum of 383 points in a controller (128
physical and 253 pseudo + EXECUTING_STOPPED, SHUTDOWN,
STARTUP). Pseudopoints and Flags in the Control Strategy chapter
describes the permissible number of pseudopoints.
3. Flags and formula names (from the mathematical editor). Formula names
and flags are not included in the 381 + 3 internal point maximum per
controller.
4. Control loops
5. Switching tables
6. Calculated execution times, including modules, control loops, switching
tables, and total execution time.

NOTE: CARE sets execution time depending on controller type and analog input
card type. If the controller is an Excel 600 and all analog input cards are
”fast”, CARE calculates the optimum cycle time. However, all analog input
points must be defined as ”fast”. If any points are defined as ”slow”, CARE
calculates cycle time as if the controller is an Excel 500 or Excel 800. This
cycle time could be six to eight times slower.

7. Excel code size (in bytes)


8. File sizes (parameter, Z-register, and T-register)
9. Excel program size
10. Total application size
11. Data point description size

Switching Tables Warning The warning ”Several switching tables for user address” may appear during a plant
translation. It means that more than one switching table commands the same point.
This situation is very common with analog points and sometimes with digital points.
It could be a problem if you have inadvertently created two switching tables
commanding the same point to do opposite actions. You may want to check your
tables.

Integrated Modem
Communication Warning When the total application size is bigger than 100 Kbytes, integrated modem
communication is not possible, which is shown by a message of the same name:

This concerns the CARE version 1.5 and higher ones.

NV Warning and
Translation Abortion Due to restrictions in LNS, CARE can only handle NVs of which names do not
exceed 21 characters. Any NV of which name exceeds 21 characters will abort the
translation. All such NVs are listed and must be reworked in the NV Editor to allow
the translation of the LON application.

Controller Download
See the Upload/Download procedures in the ONLINE SERVICE AND
COMMISSIONING chapter of this manual for details.

191 EN2Z-0937GE51 R0518


CONTROLLERS DEFINITION, ATTACHMENT AND MANAGEMENT CARE

Rename Datapoints

Purpose To rename double non-unique datapoint names within a project resulting, for
example, from controller copying.

Procedure 1. In the logical plant tree, right-click the controller of which datapoints you want to
rename, then click Rename Datapoint(s) in the context menu.

RESULT: The Rename Data Points dialog box displays. All datapoints of the
controller are listed. In the Select column, double datapoint names
are checked. Unique datapoint names are unchecked. In the Old
datapoint name column, the current datapoint names are
displayed. In the New datapoint name column, new datapoint
names are suggested on the basis of the old names and can be
edited.

2. Uncheck datapoint names you do not want to rename. Re-check datapoint


names you want to rename. You can check all datapoint names by clicking the
icon on the top and you can uncheck all datapoint names by clicking the
icon on the top.

3. To display all datapoint names, click icon on the top. To hide unique
datapoint names, click the icon on the top.

4. In the New datapoint name column, rename suggested names if desired.

5. Click Rename button.

RESULT: The datapoints are renamed and the new names are shown in the
logical plant tree.

Delete Unused Datapoints


Purpose To delete unused datapoints of the controller or plant.

Procedure 1. In the logical plant tree, right-click the controller or plant of which datapoints
you want to delete, and then click Delete Unused Datapoints in the context
menu.

RESULT: The Delete Unused Datapoints dialog box displays. All unused
datapoints of the controller respectively of the plant are listed. By
default, all datapoints are checked In the Select column for
deletion.

2. Uncheck datapoint names you do not want to delete, or re-check datapoint


names you want to delete. You can check all datapoint names by clicking the
icon on the top and you can uncheck all datapoint names by clicking the
icon on the top.

3. Click OK button.

RESULT: All checked datapoints are deleted from the controller or plant.

EN2Z-0937GE51 R0518 192


CARE

PLANT SCHEMATICS
Purpose This chapter describes how to develop and change plant schematics for a project. A
plant schematic defines the equipment in the plant and how it connects together.

IMPORTANT
For the FALCON and EAGLE controllers (CARE XL-Web) schematic
creation is not possible. The Schematics function works differently for
Excel 10 (2000series) applications. See Excel 10 Applications chapter.

Assumption This step assumes that you already selected or created a plant.

Chapter Contents Schematic Window Description

Segment Additions/Insertions

Segment Deletion

Macros (includes saving, loading, and deleting)

Physical Point Types (includes analog outputs, digital inputs, digital outputs,
totalizers, feedback points, extra user addresses)

Flex Points (includes DO_Feedback_DI points, Pulse_2 points, and multistage


points)

User Address Changes

Points Without a Graphic

Plant Information Summary (point count, user addresses, segment information,


extra text, I/Os)

Schematic Redraws

Schematic Function Exit

See Also ⇒ Getting Started chapter for procedures to start and exit CARE

Plants Definition and Management chapter for procedures to define and select a
plant

File Management chapter for procedures to back up and restore plant files.

Schematic Window Description


Purpose Define plant equipment and how it connects together.

Schematic Definition A plant schematic is a combination of segments such as boilers, headers, and
pumps. Segments consist of equipment such as sensors, status points, valves, and
pumps. Each segment has an associated minimum number of points required for
good control.

In the schematic workspace you can add or insert ysegments, delete segments,
and modify some point defaults such as type and user addresses. The CARE library
contains predefined segments called macros. You can use macros to more quickly
add segments to the schematic. You can also save segments that you create as
macros and put them in the library for future use.

Procedure 1. In the logical plant tree, click on the plant.

A window displays with the plant name in the title.

193 EN2Z-0937GE51 R0518


PLANT SCHEMATICS CARE

2. Click menu item Plant, then drop-down item Schematic. Or click the Schematic
button in the button bar below the menu bar.

RESULT: The schematic window displays.

Schematic Window The following diagram is an example of a workspace with the Segments menu item
selected.

Menu Items This section describes how to use these menu items as well as how to create and
modify a schematic.

File

End Close Schematic window.

About Display copyright information.

Edit

Insert mode
on/off Select whether to add a new segment to the end of the
schematic (off) or to insert the segment just before the
currently selected segment (on).

Delete Erase selected segment.

Load
macro Select and insert/add a previously saved segment.

Save
macro Save selected segment as a macro for use in other
plants and projects.

EN2Z-0937GE51 R0518 194


CARE PLANT SCHEMATICS

Delete
macro Erase a macro that is no longer useful.

Modify
hardware
point Change default attributes for analog outputs, digital
inputs, and digital outputs.

Feedback
point Create extra user addresses (digital inputs or outputs).

Modify user
address Change user address for a selected point.

Point without
graphic Add a point to the schematic without selecting a
segment.

Redraw
schematic Refresh schematic display.

View

Point
count Display the Plant summary window with the number of
available inputs and outputs as well as the types of
inputs and outputs.

User
address Display user addresses below their respective triangles
on the schematic.

Segment
list Display segment information related to the selected
segment. For example, for a supply fan, display its
options such as single speed, no volume control,
auxiliary contact.
Extra text Display extra text that relates to the selected segment.
Extra text is usually default values for a sensor or
actuator.

Segments Equipment types that you can select for the selected
plant. Different plant types have different segment types.
Help Display a topics list for the on-line user guide. Click a
topic to display related information.

Schematic Area The area below the menu bar is where the plant schematic appears as you select
segments. Schematic elements represent equipment such as fans, sensors, and
dampers. Dotted lines lead from equipment to the bottom of the schematic and end
with an arrowhead.

Arrow Heads The arrowheads at the bottom of the schematic represent points. They are color-
coded, directional (down is input; up is output), and marked with a symbol for
additional information:

Color Direction Symbol Point Type


within
triangle

Green downward — Digital input or totalizer


Red downward 0 Analog input
Blue upward — Digital output
Violet upward 0 Analog output
Light blue upward / Flex*

If a digital or analog point has switches, its — or 0 symbol changes to represent a


switch, _/ _ or pulsed. The following diagrams show other symbols that may appear:

195 EN2B-0182GE51 R0518


PLANT SCHEMATICS CARE

*Flex points represent one or more physical points. They can command and/or
display associated physical points and their values via an operator terminal. Flex
point types include Pulse_2, Multistage, and DO_Feedback_DI. The Flex Points
subsection later in this section describes how to create and modify these points.

User Address Display If you move the cursor over a triangle and press and hold the left-hand mouse
button down, the user address for the point displays. When you release the mouse
button, the display disappears. If the point is used in a control strategy and is
connected, the display includes a red block preceding the user address; otherwise,
the block is white.

Frame The schematic always includes a rectangle that “frames” the currently selected
segment. You can move the frame by clicking a different segment. Typically, you
must select a segment before you can perform an operation on it.
When you first open a schematic, the frame appears around the first segment.

Frame Examples

Frame (box)
around first segment
space

EN2Z-0937GE51 R0518 196


CARE PLANT SCHEMATICS

Frame around
second segment

Segment Additions and Insertions


Purpose Create or modify a plant schematic by adding and inserting segments
As a general rule, pick segments in sequence to flow from left to right. For example,
when building a VAV box controller, first pick the inlet arrangement (single duct or
dual duct), then the damper actuator, then the fan, then the heating coil, then the
space sensor.

Adding vs. Inserting When you “add” a segment to a schematic, software places it at the end of the
schematic.

When you “insert” a segment in a schematic, software places it just to the left of the
currently framed segment.

You control the add and insert functions via the Insert mode on/off option under the
Edit menu item:

• If Insert mode on/off is on, there is a check mark next to it. When you select a
segment, software inserts it. Insert mode remains on until you turn it off.

• If Insert mode on/off is off, there is no check mark next to it. When you select a
segment, software adds it. Insert mode remains off until you turn it on.

To turn Insert mode on and off, simply click it. If it is on, it turns off. If it is off, it turns
on.

Procedure 1. Select mode, insert or add, as described in the previous paragraphs.

2. If you are in insert mode, position segment frame as desired so that the new
segment appears where you want it. Software inserts new segments to the left
of the framed segment. For example, if you want to insert a new segment
between segments 2 and 3, click segment 3 to frame it.

3. Click menu item Segments.

RESULT: A list of segments displays.

4. Select desired segment by either clicking segment name or typing segment


number.

RESULT: A list of options displays.

5. Select desired option by either clicking option name or typing option number.

RESULT: Another list may display or a dialog box. For example:

197 EN2B-0182GE51 R0518


PLANT SCHEMATICS CARE

NOTE: To cancel the inclusion of the segment, click Cancel.

6. Click item (or type number), then click OK to select it. (Or, double-click item as
a shortcut).

Depending on the selected segment, additional windows may appear. Select


items as required.

RESULT: After you make the last selection, the segment list window closes
and the schematic work space reappears with a drawing of the new
segment to the left of the previously framed segment. The new
segment is framed.

7. You can continue selecting segment menu items and then specific
components.

When you are through with a plant schematic, you can end the Schematic
function (menu item File, drop-down item End) and create a control strategy for
it. See the Control Strategy chapter for details.

Example This section shows how to add a Supply Fan segment to an air conditioning plant.

1. Click menu item Segments, then drop-down item Fan.

RESULT: A drop-down list displays with a choice of four types, Single Supply
Fan, Single Return Fan, Multiple Supply Fans, and Multiple Return
Fans.

2. Click Single Supply Fan.

RESULT: The SaFanType segment list window displays with four options,
Single Speed, Single Speed with Vane Control, Two Speed, and
Variable Speed.

3. Double-click Single Speed.

RESULT: The SaFanDev window displays with four choices, Control with
Status, Control Only, Status Only, and No Control or Status.

4. Double-click Control with Status.

RESULT: A diagram of the fan displays in the schematic work space.


Examples:

EN2Z-0937GE51 R0518 198


CARE PLANT SCHEMATICS

The triangles represent points. To see point names, click View,


then drop-down item User address. Software displays default
names below the triangles:

Default Point Attributes Each point associated with a segment has an associated default file that assigns
various types of information to the point. For example, an analog point can have the
following defaults:

User Address sup_fan


CARE type S
Descriptor number 0
Access attribute 1
Engineering Unit 3
Characteristic number 0
Alarm Text number 0
Low Warning Limit 0
High Warning Limit 100
Low Alarm Limit 0
High Alarm Limit 100
Alarm Delay 360 sec
Suppress Alarm J
Critical/non-critical alarm U
Hide Point No

These default values are accessible via the Data Point Description Editor. This
editor provides point dialog boxes that list these default values as well as other
values that relate to point operation. The Editors chapter in this manual describes
the dialog boxes and how to change the point values.

199 EN2B-0182GE51 R0518


PLANT SCHEMATICS CARE

Segment Deletion
Purpose Modify a plant diagram by deleting equipment segments.

Procedure 1. Click segment diagram that you want to delete.

RESULT: Software frames the segment.

2. Check whether or not the segment contains points connected to a control loop
or switching logic. If there are connected points, first remove the points from
the control loop or switching logic. Otherwise, software issues an error
message when you try to delete the segment. See Control Strategy or
Switching Logic chapter in this manual for procedures.

3. Click Edit, then drop-down item Delete. Or, press the Delete key.

RESULT: Software displays a message asking for confirmation.

4. Click Yes to continue (or No to cancel).

RESULT: If you clicked Yes, software removes the segment from the
schematic.

Macros
Purpose If a segment and its components are used frequently in plant designs, you can save
the segment as a macro.

A macro describes a segment with all specified components, such as sensors,


status points, etc. When you use a macro, you do not need to make all the choices
that you do when you select a segment from the menu bar. For example, if you add
a single-speed supply fan with no volume control and auxiliary contact status to a
schematic and then save it as a macro, you can use that macro to quickly add that
type of fan to any schematic.

Each macro is stored under a unique, personalized name. You can recall it
repeatedly in multiple plants and projects.

Stored macros are available independent of selected plant type. For example, you
can use segments from a heating plant in air conditioning plants.

Save a Segment as a Macro


Procedure 1. Select the segment to be saved as a macro from the plant schematic.

RESULT: Software frames the segment.

2. Click Edit, then drop-down item Save macro. Or, press F3.

RESULT: The Save segment macro dialog box displays.

EN2Z-0937GE51 R0518 200


CARE PLANT SCHEMATICS

3. Type a new macro name in the Macro name editing field. The macro name
cannot already exist.

4. Click Save to save macro and close the dialog box. Or, Click Cancel to close
the dialog box without saving the macro.

Load a Macro
You can add or insert a segment, previously stored as a macro, anywhere in a plant
schematic.

Procedure 1. To add the macro segment to the end of the schematic, make sure Insert mode
is off (no check mark under Edit menu). To insert the macro segment within the
schematic, make sure the Insert mode is on (check mark under Edit menu) and
select the segment where you want the macro to appear.

2. Click Edit, then drop-down item Load macro. Or, press F2.

RESULT: The Load segment macro dialog box displays.

3. Select the desired macro from the existing macros in the list box.

4. Click Load to add or insert the segment in the plant schematic and close the
dialog box. Or, to close the dialog box without loading the macro, click Cancel.

Delete a Macro From the Library


Procedure 1. Click Edit, then drop-down item Delete macro. Or, press F4.

201 EN2B-0182GE51 R0518


PLANT SCHEMATICS CARE

RESULT: The Delete segment macro dialog box displays.

2. Select the macro to be deleted from the existing macros in the list box.

3. Click Delete. Or, click Cancel to just close the dialog box without continuing.

RESULT: Software asks whether or not you really want to delete it.

4. Click OK to delete the macro and close the dialog box. Or, click Cancel to
close the dialog box without deleting the macro.

Physical Point Types


Definition Physical points are the plant inputs and outputs from and to controllers.

CARE recognizes various types of physical points. If the type of point preassigned
by CARE does not agree with that which exists in the plant, you must modify point
type.

In the plant schematic, colored triangles represent the various physical points:

Green Digital input or totalizer


Red Analog input
Blue Digital output (normally open contact)
Violet Analog output (modulating)

(Light blue triangles represent flex points such as DO_Feedback_DI, Pulse_2,


and Multistage. See the Flex Points section for information on creating and
modifying these points.)

When you click a triangle to select a point it changes color to black.

If you double-click a triangle, the Datapoint information dialog box displays with
point type and user address.

You can modify analog inputs, analog outputs (continuous or three-position output
signal), digital inputs, totalizers, and feedback points. The following sections
describe the procedure for each type of point.

Maximums The maximum number of physical points varies per controller. For example, an
Excel 500 can have 128. An Excel 100 can have 36. An Excel 80 can have 24.

Analog Inputs

EN2Z-0937GE51 R0518 202


CARE PLANT SCHEMATICS

If an analog input must have either Balco 500 or PT3000sensors, select the fast
subtype and, optionally, change the user address.

Procedure 1. Click Edit, then drop-down item Modify hardware point. Or, press F5.

2. Select the analog input in the plant schematic by clicking on the red arrow
pointing down.

RESULT: The arrow head turns black. The Modify point dialog box displays
with analog input choices.

3. If desired, you can change user address by typing over the address.

User addresses must include one non-digit character and cannot include Tabs,
double quotes, ?, *, or space characters. All other ASCII characters are
allowable (A-Z, 0-9, +, -, _, etc). For example, 12A is a valid user address, but
12 is not.

For a point that requires Balco 500 or PT3000 sensors, select Subtype fast.

For other sensor types, select Subtype slow.

See the Analog Input Characteristics note for differences between the slow and
fast subtypes.

4. Click OK to save changes. Or, to close the dialog box without changing the
point, click Cancel.

RESULT: The arrow head remains black until you select another arrow head.

Board Types CARE assigns slow analog inputs to XF521A and XFL521 boards respectively and
fast analog inputs to XF526 Boards. Excel 80 and Excel 100 controllers can use
only slow analog inputs.

Analog Input Characteristics Each analog input point has an associated set of characteristics. These
characteristics describe the action of the associated sensor. When you select a
Subtype, software changes the types of characteristics available to the point. You
select the characteristics when you use the Data Point Description Editor to modify
point attributes (see the Editors chapter).

203 EN2B-0182GE51 R0518


PLANT SCHEMATICS CARE

The fast subtype can have the following types of characteristics:

The slow subtype can have the following types of characteristics:

Descriptions of these characteristics follow.

CARE Subtype Index XL-Online Index Characteristic


Slow Fast Name Specification
15 23 253 NTC Type F -58.0 to 302.0 F
Negative temperature coefficient
degrees F
11 11 255 NTC -50.0 to 150.0 C
Negative temperature coefficient
degrees C
12 12 254 LINEAR_GRAPH 0 to 10 V
13 19 249 PT1000 Type F/I -58.0 to 302.0 F
14 20 250 PT1000 Type C/I -50.0 to 150.0 C
17 247 PT1000 Type F/II 32 to 752.0 F
18 248 PT1000 Type C/II 0.0 to 400.0 C
21 251 PT100 Type F -58.0 to 302.0 F
22 252 PT100 Type C -50.0 to 150.0 C
15 245 PT3000 Type F -58.0 to 302.0 F
16 246 PT3000 Type C -50.0 to 150.0 C
13 243 BALCO Type F -58.0 to 302.0 F
14 244 BALCO Type C -50.0 to 150.0 C
24 241 0-10 V 0-10 V
25 242 2-10V = 0-100 % 2-10V = 0-100 %
26 237 NI 1000 TK5000 F -22.0 to 266.0 F
Positive temperature coefficient
degrees F
27 238 NI 1000 TK5000 -30.0 to 130.0 C
Positive temperature coefficient

EN2Z-0937GE51 R0518 204


CARE PLANT SCHEMATICS

degrees C
28 239 NTC-10 F -22.0 to 212.0 F
Negative temperature coefficient
degrees F
29 240 NTC-10 -30.0 to 130.0 C
Negative temperature coefficient
degrees C

Analog Outputs
If an analog output is to control an actuator in the plant, determine whether the
analog output should be a continuous or three position signal.

Procedure 1. Click Edit, then drop-down item Modify hardware point. Or, press F5.
.
2. Select the analog output in the plant schematic by clicking on the violet arrow
pointing up.

RESULT: The arrow head turns black. The Modify point dialog box displays
with analog output choices.

3. If desired, you can change user address by typing over the address.

User addresses must include one non-digit character and cannot include Tabs,
double quotes, ?, *, or space characters. All other ASCII characters are
allowable (A-Z, 0-9, +, -, _, etc). For example, 12A is a valid user address, but
12 is not.

For a continuous output signal, click Analog output.


For a three-position output signal, click 3 position output.
The With Switches check box indicates whether or not the analog output is on
a board with switches:

• If the analog output is on an XF522 with switches, the check box should
have a checkmark.
• If the analog output is on an XF527 board without switches, the check box
should be empty.

The XF522 board is a multipurpose board that has eight outputs (five with
switches and three without). When you select “With Switches”, software
specifies an XF522 board. When you disable “With Switches”, software
specifies an XF527 board. The XF527 board has eight outputs, all without
switches.

205 EN2B-0182GE51 R0518


PLANT SCHEMATICS CARE

An exception to this action is when a combination of with and without switches


is required. CARE then uses the XF522 board and places the “with switch”
outputs on the first five and the “without switch” outputs on the last three.

When the target hardware for the plant is DIO, CARE assigns any kind of
analog output to an XFL522 board with switches.

Excel 80 and Excel 100 Controllers do not support “With Switches”.

Click the check box to change it from checked to blank and vice versa.

4. Click OK to save changes.

RESULT: The arrow head remains black until you select another arrow head.

Excel 20 External 3-Pos Outputs During creation of the application it must be assured that the created board
addresses of CARE match the Excel 20 hardware. XL20 requires:

Point Type Board Type Board Technical Address


AI XF521A 1
AO *) XF522A 2
DI XF523A 3
DO XF524A 4
external 3-position *) XF522A 2

*) If an external 3-position output has to be used, it must reside on the AO board.

CARE creates the following configuration automatically during attach:

Point Type Board Type Board Technical Address


AI XF521A 1
AO XF522A 2
DI XF523A 3
DO XF524A 4
external 3-position XF525A 5

In case a three-position output is included in your application and therefore the


terminations created by the CARE attach do not match the XL20 hardware, use the
terminal assignment function.

Procedure 1. Drag the 3 position user addresses from the XF525 board to any free locations
on the XF522 board. It is mandatory that all 3-position points are swapped to
the analog board, to empty the XF525 board.

2. Click on the XF525 board, which is empty now with the right mouse button.
Select "Delete" from the context menu in order to delete the module.

3. Translate the controller.

Digital Inputs
Digital inputs can be normally open or normally closed. The default is normally
open. Use the following procedure to change it.

Procedure 1. Click Edit, then drop-down item Modify hardware point. Or, press F5.

2. Select the digital input in the plant schematic by clicking on the green arrow
pointing down.

RESULT: The Modify point dialog box displays with digital input choices.

EN2Z-0937GE51 R0518 206


CARE PLANT SCHEMATICS

3. If desired, you can change user address by typing over the address.

User addresses must include one non-digit character and cannot include Tabs,
double quotes, ?, *, or space characters. All other ASCII characters are
allowable (A-Z, 0-9, +, -, _, etc). For example, 12A is a valid user address, but
12 is not.

If the switch is normally open, click Digital input (NO).

If the switch is normally closed, click Digital input (NC).

4. Click OK to save changes. Or, to close the dialog box without changing the
point, click Cancel.

RESULT: The arrowhead remains black until you select another arrowhead.

Board Types CARE assigns digital inputs to XF523 and XFL523 boards respectively.

Digital Outputs
Digital outputs can be normally open or changeover. The default is normally open.
Use the following procedure to change it.

Procedure 1. Click Edit, then drop-down item Modify hardware point. Or, press F5.

2. Select the digital output in the plant schematic by clicking on the blue arrow
pointing up.

RESULT: The Modify point dialog box displays with digital output choices.

207 EN2B-0182GE51 R0518


PLANT SCHEMATICS CARE

3. If desired, you can change user address by typing over the address.

User addresses must include one non-digit character and cannot include Tabs,
double quotes, ?, *, or space characters. All other ASCII characters are
allowable (A-Z, 0-9, +, -, _, etc). For example, 12A is a valid user address, but
12 is not.

If the switch is normally open, click Digital output (NO).


If the switch is changeover, click Digital output (C/O).
The With Switches check box indicates whether or not the digital output is on a
board with switches:

• If the digital output is on an XF524 A, the check box is checked.


• If the digital output is on an XF529 board without switches, the check box
should be unchecked.

The XF524 board is a multipurpose board that has six outputs (five with
switches and one without). When you select “With Switches”, software
specifies an XF524 board. When you disable “With Switches”, software
specifies an XF529 board. The XF529 board has six outputs, all without
switches.

An exception to this action is when a combination of with and without switches


is required. CARE then uses the XF524 board and places the “with switch”
outputs on the first five and the “without switch” outputs on the last one.

When the target hardware for the plant is DIO, CARE assigns any kind of
digital output to an XFL54 board with switches

Excel 80 and Excel 100 Controllers do not support “With Switches”.

Click the check box to change it from checked to blank and vice versa.

The Pulsed check box indicates whether or not the output is a momentary
output. The duration of the output can be from 1 to 255 seconds. The following
diagram illustrates pulse action:

EN2Z-0937GE51 R0518 208


CARE PLANT SCHEMATICS

Click the check box to change it from checked to blank and vice versa.

NOTE: Do not select Pulsed if you select With Switches.

You can set the duration of the output later using the Data Point Description
Editor described in the Editors chapter.

4. Click OK to save changes.

Plant Attachment During plant attachment, CARE software assigns controller I/O terminations
according to preset rules. The digital IP output module XF524 has six outputs (five
normally closed, one normally open). The five normally closed (C/O) points have
five associated override switches. The digital DIO output module XFL524 has six
switches on its manual override module XFR524 to independently switch each of
the digital outputs OFF (0) or ON (1) or Automatic, which causes the channel to
operate normally.

To have a manual override switch on a particular digital output, use this Modify
Digital Outputs function to modify the output point from normally open to normally
closed.

Totalizers
Totalizer points can be fast or slow. The default is fast. Use the following procedure
to change it.

Procedure 1. Click Edit, then drop-down item Modify hardware point. Or, press F5.

2. Select the totalizer in the plant schematic by clicking on the green arrow
pointing down.

RESULT: The Modify point dialog box displays with totalizer choices.

3. If desired, you can change user address by typing over the address.

User addresses must include one non-digit character and cannot include Tabs,
double quotes, ?, *, or space characters. All other ASCII characters are
allowable (A-Z, 0-9, +, -, _, etc). For example, 12A is a valid user address, but
12 is not.

If the totalizer is slow, click Totalizer (slow).

If the totalizer is fast, click Totalizer (fast) (or leave as is).

4. Click OK to save changes. Or, to close the dialog box without changing the
point, click Cancel.

RESULT: The arrowhead remains black until you select another arrowhead.

209 EN2B-0182GE51 R0518


PLANT SCHEMATICS CARE

Feedback Points
Digital outputs can have feedback points as follows:

• Three extra user addresses via digital inputs


• Two extra user addresses via digital outputs

You can use the digital inputs to define feedback signals such as “Burner 1
switched on”.

You can use the digital outputs to connect alarm devices such as a horn or bell.

IMPORTANT
There are no physical or software connections to the digital output point,
that is, no correlation.

You need to establish an extra user address for each additional feedback point.

Procedure 1. Click Edit, then drop-down item Feedback point. Or, press F9.

2. Select the digital output to be modified from the plant schematic by clicking on
the blue arrow pointing up. The point selected must have a graphic.

RESULT: The Create/Edit extra point(s) dialog box displays.

3. Click a digital input or output check box to add it as a feedback point.

The Digital Input field allows you to select one, two, or three inputs and indicate
the type of contacts through which the feedback point connects, either C/O
(normally closed contacts) or NO (normally open contacts).

The Digital Output field allows you to select one or two outputs and indicate the
type of contacts through which the feedback point connects, N/Open (normally
open contacts) or C/Over (changeover contacts).

RESULT: A checkmark appears in the check box for the selected point.

To reset a check box selected in error, click the check box again (to
remove the checkmark).

EN2Z-0937GE51 R0518 210


CARE PLANT SCHEMATICS

4. Click the appropriate switching status for the selected point (C/O, NO, N/Open,
or C/Over).

5. Click the corresponding Extra address field to select it and type in a user
address for the point. Extra address fields are not selectable until you select a
digital input or output.

User addresses must include one non-digit character and cannot include Tabs,
double quotes, ?, *, or space characters. All other ASCII characters are
allowable (A-Z, 0-9, +, -, _, etc). For example, 12A is a valid user address, but
12 is not.

6. Repeat Steps 3 through 5 until you are through selecting all desired inputs and
outputs.

7. Click OK to save changes and close the dialog box.

Extra User Addresses Display


The extra user addresses do not display on the plant schematic. To view them,
double-click the digital output point triangle. The Datapoint information dialog box
displays with point type and user address for each point.

Flex Points
Purpose Flex points represent one or more physical points. They can command and/or
display associated physical points and their values via an operator terminal. Flex
point types include Pulse_2, Multistage, and DO_Feedback_DI.

To add flex points to a schematic, use the Point without graphic function under the
Edit menu. The Create/View point(s) without graphic dialog box includes the three
flex point types. Select desired type(s) and create as many as needed.

In some plant types, there is also a POINTS segment that allows you to create flex
point types in the same way as you create schematic segments.

After you add flex points to the schematic, you may want to change the defaults for
the points. The following sections describe each type of flex point, lists its defaults,
and describes how to change them.

DO_Feedback_DI Points
Purpose With DO_Feedback_DI points, one user address (the DO_Feedback_DI point, a
pseudopoint) can control up to three digital outputs with up to three digital inputs (all
six points are physical points). The digital inputs register the feedback of the
outputs 1 through 3 (Stages). The point assignments in CARE are permanent. The
digital output points are normally open (N.O.) and are only assigned to boards
without switches (for example, XI529).

For example, you can implement a three-stage switch using the following digital
outputs:

Status DO1 DO2 DO3

0 0 0 0
1 1 0 0
2 0 1 0
3 0 0 1

You can define the attributes of these points later using the Data Point Description
Editor described in the Editors chapter. The point type for these points in the Editor
is “Flex”.

211 EN2B-0182GE51 R0518


PLANT SCHEMATICS CARE

Deviation If a deviation occurs between the digital output and its associated digital input, then
the controller software will switch down this point type until a "non-alarm" state is
reached. In extreme cases and if the flex point has just 1 stage, it may be switched
to the off position.

Defaults The default for these points is three stages with digital inputs that are normally
open. To change the number of stages or the normally open default, use the
following procedure.

Procedure 1. Click Edit, then drop-down item Modify hardware point. Or, press F5.

2. Select the DO_Feedback_DI point in the plant schematic by clicking on the


light blue arrow pointing up.

RESULT: The Modify point dialog box displays.

3. Click the down arrow in the Stages box to display the three choices. Click
desired number of stages. Software assigns 1, 2, or 3 digital inputs and outputs
according to the number of stages you select.

4. To modify a digital input point from normally open to normally closed or vice
versa, click the down arrow in the Select point box to display point choices.
Click the name of the desired digital input point. Then click the down arrow in
the Modify point box to display the normally open/normally closed choices.
Click desired choice to select it.

If the Modify point text and box are gray, the Select point box has a digital
output point selected. You must select a digital input point to enable the Modify
point option.

5. Click Save to save changes, then click Cancel to close the dialog box.
To close the dialog box without changing the point, just click Cancel.

Pulse_2 Points
Purpose Pulse_2 points use two terminals with one user address (the Pulse_2 point) that
has momentary outputs. The digital output points are normally open (N.O.) and are
only assigned to boards without switches (for example, XI529). The following
diagram shows output action:

EN2Z-0937GE51 R0518 212


CARE PLANT SCHEMATICS

One pulse is generated per point status change (positive edge triggered). A
transition of 0 to 1 sets the pulse on DO2. A transition of 1 to 0 sets the pulse on
DO1.

A change of state of the value can retrigger all outputs.

You can define the attributes of these points later using the Data Point Description
Editor described in the Editors chapter. The point type for these points in the Editor
is “Flex”.

Defaults The default for these points is two normally open digital outputs. You cannot change
this selection. However, to see the user address for these points, you can display
the Modify Point dialog box. The following procedure describes how to do that.

The Pulse Duration default is one second. To modify the pulse duration, use the
Data Point Description Editor described in the Editors chapter.

Procedure 1. Click Edit, then drop-down item Modify hardware point. Or, press F5.

2. Select the Pulse_2 point in the plant schematic by clicking on the light blue
arrow pointing up.

RESULT: The Modify point dialog box displays.

3. Click the down arrow for the Select point drop-down list box to see the user
address of the other point..

4. Click Save to save changes, then click Cancel to close the dialog box.
To close the dialog box without changing the point, just click Cancel.

213 EN2B-0182GE51 R0518


PLANT SCHEMATICS CARE

Multistage Points
Purpose With Multistage points, one user address (the Multistage point, a pseudopoint) can
control up to six outputs (all six points are physical points). CARE positions all
physical points on the same hardware module and numbers them sequentially one
after the other. Multistage outputs can only be normally open (N.O.) and are only
assigned to boards without switches (for example, XI529).

Stage operation is:

Value Status of Stages

0 0 0 0 0 0 0
1 1 0 0 0 0 0
2 1 1 0 0 0 0
3 1 1 1 0 0 0
4 1 1 1 1 0 0
5 1 1 1 1 1 0
6 1 1 1 1 1 1

You can define the attributes of these points later using the Data Point Description
Editor described in the Editors chapter. The point type for these points in the Editor
is “Flex”.

Hysteresis For each analog command value of 0.0 through 6.0, there is a hysteresis value of
0.4. The following table lists ranges for each value:

Input Range Displayed Input Range


Switching Up Value Switching Down

0.00-0.699 0 0-0.299
.7-1.699 1 .3-1.299
1.7-2.699 2 1.3-2.299
2.7-3.699 3 2.3-3.299
3.7-4.699 4 3.3-4.299
4.7-5.699 5 4.3-5.299
5.7-higher 6 5.3-higher

Example:

There is no logic to prohibit the multistaged operator from being driven from one
end to the other. You may want to add a Ramp operator during the Control Strategy
process to prevent this action.

Defaults The default for these points is six output points. To change the number of output
points, use the following procedure.

Procedure 1. Click Edit, then drop-down item Modify hardware point. Or, press F5.

2. Select the Multistage point in the plant schematic by clicking on the light blue
arrow pointing up.

EN2Z-0937GE51 R0518 214


CARE PLANT SCHEMATICS

RESULT: The Modify point dialog box displays.

3. Click the down arrow in the Stages box to display the six choices. Click desired
number of stages. Software assigns the corresponding number of outputs
according to the number of stages you select.

4. To display the names of the output points, click the down arrow in the Select
point box.

The Modify point text and box are always gray because the Multistage points
are always N.O. output points.

5. Click Save to save changes, then click Cancel to close the dialog box.
To close the dialog box without changing the point, just click Cancel.

User Address Changes


Definition CARE preassigns default user addresses to all points. You can change these user
addresses, if desired.

You use the user addresses when creating the control strategy and switching logic.

You may want to change user addresses to provide for easier wild card searches at
operator terminals such as the Excel Building Supervisor operator terminal. Wild
card searches separate upper and lower case letters alphabetically, for example,
AHU1 and ahu1 do not sort the same.

Procedure 1. Select the point to be modified from the plant schematic.

RESULT: The point triangle changes color to black.

2. Click Edit, then drop-down item Modify user address. Or, press F7.

RESULT: The Modify user address dialog box displays showing the current
address.

215 EN2B-0182GE51 R0518


PLANT SCHEMATICS CARE

3. To enter a new user address, click the current address and type a new
address. To just add to the current address, click behind the current address to
place the cursor at the end of the address, and type new letters. To just change
part of the current address, highlight that part and type new letters.

To “highlight” letters, click just in front of the first letter you want to highlight,
hold down the mouse button, and drag the cursor over all the letters you want
to highlight (“select”). Release the mouse button when all the letters are
selected.

User addresses must include one non-digit character and cannot include Tabs,
double quotes, ?, *, or space characters. All other ASCII characters are
allowable (A-Z, 0-9, +, -, _, etc). For example, 12A is a valid user address, but
12 is not.

4. Click OK to save the address.

If you do not click OK, the new address is not saved. You can retrieve the
original user address by clicking Recover.

RESULT: The dialog box remains on display so you can continue changing
addresses.

5. To change another user address, select the point on the plant schematic and
click the editing field in the dialog box.

RESULT: The address for the newly selected point appears in the editing
field in the dialog box.

6. Enter the new user address and click OK. You can continue changing user
addresses in this way.

User addresses must include one non-digit character and cannot include Tabs,
double quotes, ?, *, or space characters. All other ASCII characters are
allowable (A-Z, 0-9, +, -, _, etc). For example, 12A is a valid user address, but
12 is not.

If you do not click OK, the new address is not saved. You can retrieve the
original user address by clicking Recover.

7. To end modifications to user addresses, double-click the Ventilator icon in the


upper left corner of the dialog box.

Or, click Schematic menu item Edit. Note that a check mark is next to Modify
user address to indicate that the function is active. Click Modify user address to
remove the check mark and stop the function.

Deselecting a Point To deactivate a point selected in error:

a. Move the mouse pointer to the point level on the plant schematic or to another
point.
b. Click the mouse button once.

RESULT: The point returns to its normal color.

EN2Z-0937GE51 R0518 216


CARE PLANT SCHEMATICS

Points Without a Graphic


Purpose The "Point without graphic" function allows you to add points to a plant schematic
even though no segment exists for the point.

A point without a graphic can be an input such as an occupancy sensor or a window


switch.

Procedure 1. Click Edit, then drop-down item Point without graphic. Or, press F8.

RESULT: The Create/View point(s) without graphic dialog box displays.

2. Select point type. Click New.

RESULT: The New Point dialog box displays.

This dialog box always contains the Number and User Address fields, but it
may also display other fields depending on the type of point selected.

3. Enter the number of data points of this type to be established as a "Point


without graphic" in the Number editing field. Tab to User address field.

4. Type a user address in the User address editing field. If you are adding more
than one point, software automatically numbers the corresponding user
addresses sequentially to guarantee unique user addresses. For example, if
you enter pt and request two points, software creates two points named pt1
and pt 2. Only use alphabetic characters. Do not use blanks. The user address
can be a maximum of 15 characters. Software adds an increment number to

217 EN2B-0182GE51 R0518


PLANT SCHEMATICS CARE

the end of the user address you enter. If it creates an address greater than 18
characters, software truncates enough characters at the end of the name to
reduce it to 15. For example, if you entered Room_one_space_tmp (18
characters) and wanted to make 20 points, software would create 20 points
named Room_one_space_1 (15 characters plus the increment number)
through Room_one_space_20.

User addresses must include one non-digit character and cannot include Tabs,
double quotes, ?, *, or space characters. All other ASCII characters are
allowable (A-Z, 0-9, +, -, _, etc). For example, 12A is a valid user address, but
12 is not.

If the dialog box contains With Switches and/or Pulsed check boxes, check
appropriate choices as described in the following text.

The With Switches check box indicates whether or not the digital output is on a
board with switches:

• If the digital output is on an XF524 board with hand/off/auto switches, the


check box should have an checkmark.
• Otherwise, the check box should be empty.

Click the check box to change it from checked to blank and vice versa.

The Pulsed check box indicates whether or not the output is a momentary
output. The duration of the output can be from 1 to 255 seconds. The following
diagram illustrates pulse action:

Click the check box to change it from checked to blank and vice versa.

NOTE: Do not select Pulsed if you select With Switches.

You can set the duration of the output later using the Data Point Description
Editor described in the Editors chapter.

5. Click OK to add the point(s) to the end of the plant schematic. Software always
adds the points to the end.

6. Click Cancel to close the dialog box and return to the schematic.

Alternative Points Some plant types have a segment called POINTS that is simply a point. Selecting a
POINTS segment allows you to place a point without a graphic anywhere in the
schematic, rather than just at the end of the graphic as the Point without graphic
function does.

Point Modification To change some default values for the points, use the Modify functions available
under the Edit menu item. See the Physical Point Types and/or the Flex Points
sections for more information about the types of modifications you can make.

Plant Information
Purpose Display and check plant information in case you need to make changes before
continuing with the next CARE step.

EN2Z-0937GE51 R0518 218


CARE PLANT SCHEMATICS

You can generate a point count for the controller, display assigned user addresses,
list segment blocks, view additional text, and display controller input/output
information.

Assumption This step assumes that you have already selected or created a plant and the CARE
window has project name, plant name, and plant type as well as a menu bar with
the Schematic menu item. See the Plants Definition and Management chapter for
procedure.

Point Count
Procedure 1. Click View, then drop-down item Point count.

RESULT: The Point Count window displays with the type of controller in the
title, the number of available inputs and outputs as well as the
types of inputs and outputs. Example:

2. To close the Point Count window, click Cancel.

Or, click View again. Note that a check mark appears next to the Point count
function to indicate that it is active. Click Point count to remove the check mark
and stop the function.

RESULT: The Point Count window closes.

User Addresses
Procedure 1. Click View, then drop-down item User address.

RESULT: The user addresses of the selected plant display under the plant
schematic.

219 EN2B-0182GE51 R0518


PLANT SCHEMATICS CARE

The first letter of every user address is just below the plant
schematic symbol for the input/output triangle to which the user
address belongs.

2. To end this function, click View again. Note that a check mark appears next to
the User address function to indicate that it is active. Click User address to
remove the check mark and stop the function.

RESULT: The user addresses disappear from the screen.

Single User Address Display If you move the cursor over a triangle and press and hold the left-hand mouse
button down, the user address for the point displays. When you release the mouse
button, the display disappears.

Segment Information
Purpose Display the list of components in a selected segment.

Procedure 1. Select the required segment from the plant schematic.

RESULT: Software frames the segment.

2. Click View, then drop-down item Segment list.

RESULT: The Segment list dialog box displays below the schematic.

3. To view the list of components for another segment, select the segment in the
plant schematic.

4. To end this function, double-click the Ventilator icon in the upper left corner of
the window.

EN2Z-0937GE51 R0518 220


CARE PLANT SCHEMATICS

Or, click View again. Note that a check mark appears next to the Segment list
function to indicate that it is active. Click Segment list to remove the check
mark and stop the function.

RESULT: The Segment list dialog box disappears from the screen.

Extra Text
Purpose Display additional information about a selected segment.

Procedure 1. Select the required segment from the plant schematic.

RESULT: Software frames the segment.

2. Click View, then drop-down item Extra text.

RESULT: The Extra text dialog box displays below the schematic. For
example, in the following dialog box, the extra text specifies the
default sensor type.

3. To view additional information for another segment, select the segment in the
plant schematic.

4. To end this function, double-click the Ventilator icon in the upper left corner of
the window.

Or, click View again. Note that a check mark appears next to the Extra text
function to indicate that it is active. Click Extra text to remove the check mark
and stop the function.

RESULT: The extra text disappears from the screen.

Controller Input/Output Information


Purpose Display information about controller inputs and outputs.

The type of input or output you select displays. All user addresses assigned to
these inputs or outputs display.

Procedure 1. Double-click desired input or output on the plant schematic.

RESULT: The Datapoint information dialog box displays.

221 EN2B-0182GE51 R0518


PLANT SCHEMATICS CARE

2. Click OK or Cancel to close the dialog box.

NOTE: Later when you set up control strategy and switching logic for the plant,
you use this dialog box to specify which user address to tie to a function.
The extra addresses for feedback points do not appear on the schematic,
so you need this dialog box to find and select them.

Schematic Redraws
Purpose Redisplay the plant schematic on the screen so all recent changes appear.

Procedure Click Edit, then drop-down item Redraw Schematic. Or, press F6.

RESULT: Software redraws the plant schematic .

Print Plant Schematic


To print a plant schematic see Print Documentation chapter.

Schematic Function Exit


Purpose Close the Schematic function and return to the CARE main window.

Procedure Click File, then drop-down item End.

RESULT: The main CARE window displays.

EN2Z-0937GE51 R0518 222


CARE CONTROL STRATEGY

CONTROL STRATEGY
NOTE: The Control Strategy chapter applies to CARE XL-5000 only.

Purpose The control strategy for a plant consists of control loops that monitor the
environment and adjust equipment operation to maintain comfort levels. For
example, a control loop for an air handling system can turn on a return air fan when
discharge air temperature in the return air duct is greater than or equal to 68F
(20 °C).

Control loops consist of a series of “control icons” that dictate a sequence of events.
Control icons provide preprogrammed functions and algorithms to implement
sequences of control in a plant schematic. Examples of control icons include a
Proportional-Integral-Derivative (PID) function and a Maximize function. Appendix A
lists the available control icons. Excel CARE Control Icons User Guide 74-5577
(US) / EN2B-0184 (Europe) provides complete descriptions and application
examples for each control icon.

Control Strategy Capacities


• Each plant can have more than one control loop.
• Each controller can have a maximum of 128 control icons for all plants attached
to the controller. In other words, if there are three plants, the total of control
icons used by all three plants cannot exceed 128.
• Each controller can have a maximum of 40 PID control icons for all plants
attached to the controller. In other words, if there are three plants, the total of
PID control icons used by all three plants cannot exceed 40.
• Free programming and XFMs must not be used together in one and the same
control loop.

Incomplete Loop Warning If you exit the Control Strategy function with incomplete control loops, you cannot
attach or translate the plant.

Chapter Contents Control Strategy Window

Control Loop Selection (New Control Loops or Existing Control Loops)

Control Loop Functions, including:


• Select and Place a Control Icon
• Connect Control Icons to Plant
• Connect Two Control Icons
• Examples
• Delete a Control Icon and Its Connections
• Delete a Completed Connection
• Delete an Incomplete Connection

Pseudopoints and Flags, including:


• Create/Assign New Pseudopoints and Flags
• Load/Assign Pseudopoints and Flags
• Search for Pseudopoints and Flags via Keyboard
• Modify Pseudopoint and Flag User Address
• Delete Pseudopoints and Flags
• Connect a Pseudopoint or Flag to a Control Loop
• Change a Pseudopoint or Flag User Address

XFMs, including:
• Map Software Point to XFM Parameter
• Map Software Point to an XFM Internal Datapoint
• Create User Address of the Same Name and Map to XFM Internal Datapoint
• Unmap Mapped Software Point from an XFM Parameter
• Modify XFM Parameter

Plant Information Displays

• Loop Management Functions, including:

223 EN2Z-0937GE51 R0518


CONTROL STRATEGY CARE

• Copy a Control Loop


• Delete a Control Loop
• Check a Control Loop
• Print a Control Loop
• Control Strategy Exit

See Also ⇒ Getting Started chapter for procedures to start and exit CARE

Plant Schematics chapter for procedures to create and/or modify a plant schematic

File Management chapter for procedures to back up and restore plant files

Control Strategy Window


Purpose Provide standard control functions for analog points in the plant schematic.

Assumption The plant schematic is done.

Procedure 1. In the logical plant tree, click on the plant.

2. Click menu item Plant, then drop-down item Control Strategy. Or click the
Control Strategy button in the button bar below the menu bar.

RESULT: The control strategy workspace displays. The following example


shows the workspace with a control loop that has two PID
operators and a Sequence operator connected to physical points
and a pseudopoint.

EN2Z-0937GE51 R0518 224


CARE CONTROL STRATEGY

Title Bar Plant name (in this case, ahu1) displays in the window title bar. To the right is a pair
of brackets where the control loop name appears. The brackets are empty until you
select or define a loop (menu item File, drop-down item New or Open).

Menu Bar The left arrow and View menu items are only available after you define or select a
control loop.
Left arrow Change control icon column to show other control
choices.

File New…
Create a new control loop.

Load…
Add an existing control loop to the plant.

Copy…
Copy selected control loop and^give it a new name.

Delete…
Delete unnecessary loop.

Check loop…
Verify control loop operation.

Print with Schematic


Output a print of the currentcontrol loop with schematic
Print with User Address
Output a print of the current control loop with user
addresses.

Exit
Stop control strategy function and return to main window.

Information…
Copyright and program authors.

Edit Modify Pseudo User Address


Change the user address for a selected pseudopoint.

Delete Symbol
Erase the currently selected control icon and all its
connections.

Connect Symbol…
Display the icon dialog box for the currently selected
symbol.

Symbol Parameters…
Display the parameters dialog box for the currently
selected symbol.

Load Software Points…


If pseudopoints are defined in the switching logic chapter
for inclusion in the plant control strategy, you must load
them into the control strategy. The pseudopoints and
Flags section explains how to use this function.

Delete Unused SW Points…


Display the unused software points window for a list of
unused software points. You can delete one or more, if
desired. See the Unused Software Points note for
details.

View Display physical user addresses or pseudopoint user


addresses.

225 EN2Z-0937GE51 R0518


CONTROL STRATEGY CARE

Help Display topic list for on-line user guide. The Getting
Started chapter describes the help function.

Plant Schematic This area displays the schematic created via the Schematic function.

Physical Point Bar This area displays the physical points required for the schematic.

If you move the cursor over a triangle and press and hold the left-hand mouse
button down, the user address for the point displays with either a red exclamation
symbol or a green check mark symbol. When you release the mouse button, the
display disappears. The red exclamation symbol appears for:

• hardware points with one allowable connection that are used in an XFM
• digital outputs that are connected to a symbol
• flex points that are connected to a symbol
• software points that are connected to an output pin of a symbol.

Once you display a physical address, you must “clear” the display mode before you
can display an address in the other point bar. To clear display mode, click the
triangle again, but this time with the right-hand mouse button.

If you double-click a triangle, the Datapoint information window displays for the
point.

Work Space This area is where you place control icons after you select them. You can assign a
control icon to each rectangle. You can connect the rectangles to each other, to
physical points, and to pseudomonas.

Softwarepoint Bar Display abbreviations for pseudopoints related to the control loop. These
abbreviations appear after you add a pseudopoint to the control loop.

If you move the cursor over an abbreviation and press and hold the left-hand mouse
button down, the user address for the point displays with either a red exclamation
symbol or a green check mark symbol. When you release the mouse button, the
display disappears.

The red exclamation symbol appears for software points that are connected to an
output pin of a symbol.

Control Icons Standard control functions available for assignment to the plant schematic.
Appendix A lists the available control icons. Excel CARE Control Icons User Guide
74-5577 (US) / EN2B-0184 (Europe) provides complete descriptions and
application examples for each control icon. This section describes how to place and
connect them.

Unused Software Points To delete unused software points, in other words, points which are not connected to
a control strategy symbol in the plant schematic, select menu item Edit, then drop-
down item Delete Unused SW Points.. The Delete Unused Software Points dialog
box displays with a list of those points and an option to delete them, if desired. For
example:

EN2Z-0937GE51 R0518 226


CARE CONTROL STRATEGY

Click the points you want to delete (hold down the Shift key while you click to select
multiple points). Then click Delete for software to delete these unused points. (The
Delete key is not active until you select at least one point.)

Click Continue to close the dialog box. Points that you did not delete remain in the
plant. Points assigned to the software bar but not connected become unassigned.

Control Loop Selection


Purpose Name a control loop. You must define a name for a loop or select an existing loop
before you can select any control icons.

There are two ways to name a loop. You can name a new loop and begin from
scratch. Or, you can load an existing control loop and modify as required.

New Control Loops


Purpose Name a new control sequence for the selected plant.

Procedure 1. Click File, then drop-down item New.


RESULT: The Create new control loop dialog box displays.

2. Type a new control loop name in the Name editing field.

3. Click OK.
Or, to close the dialog box without creating a loop, click Cancel.

RESULT: The control loop name displays, in brackets, next to the plant name
on the window title. You can now select the control icons down the
left hand window border. The Control Loops section provides
procedures.

Existing Control Loops


Purpose Use an existing control loop to speed creation of control functions for a plant.

Procedure 1. Click File, then drop-down item Load.

RESULT: The Load control loop dialog box displays.

227 EN2Z-0937GE51 R0518


CONTROL STRATEGY CARE

2. Select the control loop to be modified from the list of existing control loops.

3. Click OK.
Or, to not load the loop, click Cancel.

RESULT: The control loop name displays to the right of the plant name on
the window title bar. The loop icons display in the work space. You
can now modify the control loop as required. The next section,
Control Loop Functions, provides procedures.

Control Loop Functions


Purpose Build or modify a control loop by adding and deleting control icons and connecting
them together and with physical points and pseudopoints.

This section contains the following procedures:

• Select and Place a Control Icon


• Connect Control Icons to the Plant
• Connect Two Control Icons
• Examples (sample control loops with clear and confusing connections)
• Delete a Control Icon and its Connections
• Delete a Completed Connection
• Delete an Incomplete Connection

Select and Place a Control Icon


Procedure 1. Click a control icon symbol in the icon column.

RESULT: The mouse cursor assumes the shape of the control icon.

Tip ⇒ If you do not see the required control icon in the icon column, click
the left arrow, ←, in the menu bar. The column changes to show
other available icons.

2. Click a free rectangle in the control strategy work space to place the control
icon in the rectangle. See the Examples section for guidelines.

RESULT: Software places the symbol in the rectangle and changes its color
to red. It also places a thick gray bar around it to indicate it is the
currently selected icon.

Software may then display a dialog box that asks for “internal
parameter” information relevant to the control icon. For example,
the PID icon asks for proportional band, derivative time, integral
action, minimum output, and maximum output.

EN2Z-0937GE51 R0518 228


CARE CONTROL STRATEGY

Tip ⇒ To cancel selection of an icon that you have not yet placed, click
the right-hand mouse button.

3. If an internal parameters dialog box displays, type or select information as


required. Excel CARE Control Icons User Guide 74-5577 (US) / EN2B-0184
(Europe) provides complete descriptions and application examples for each
control icon.

Click OK to save the information and close the dialog box.

Or, click Cancel to close the dialog box without saving the information.

Tip ⇒ To redisplay an internal parameters dialog box, click the right-hand


mouse button when the cursor is over the desired icon. Or, click
menu item Edit, drop-down item Symbol parameters. The
parameters dialog box displays for the currently selected icon (a
gray box surrounds a selected icon).

4. Connect the icon to required inputs and outputs. Double-click the icon (left-
hand mouse button) to display an input/output dialog box that requests required
variables. The dialog box always shows output variables on the left, the control
icon in red, and input variables on the right.

For example, the PID icon displays the following dialog box:

The Y, X, and W variables need connection to either physical points,


pseudopoints, and/or other control icons. Variables on the left (Y in this case)
are outputs. Variables on the right (X and W in this case) are inputs. The PID
description in Excel CARE Control Icons User Guide 74-5577 (US) / EN2B-
0184 (Europe) defines the type of connection that is valid for each variable.

The two blank rectangles in the dialog box are editing fields where you can
enter values to replace the physical connections. For example, in the PID
dialog box, you can type an engineering unit table reference and value for the
W variable, instead of connecting W to a point or control icon. For engineering
unit, enter the corresponding index number. Appendix B lists engineering units
and their index numbers.

If a variable does not have editing fields next to it, you cannot type values for a
connection; you must connect to another icon or a point.

The following sections describe how to connect the variables.

Connect Control Icons to Plant


Purpose Make connections between control icons and the plant.

You can connect control icons to:

229 EN2Z-0937GE51 R0518


CONTROL STRATEGY CARE

• Physical points (each physical output point can connect to only one icon)
• Pseudopoints
• Flags
• Other control icons

See the Pseudopoints and Flags section for procedures to create and load
pseudopoints and flags. The section also defines these items.

Procedure The steps required depend on the type of control icon you select. Each type has a
different set of inputs and outputs. Excel CARE Control Icons User Guide 74-5577
(US) / EN2B-0184 (Europe) describes the requirements for each icon.

The following steps summarize typical operations that connect an icon to a plant via
points.

1. Select and place desired control icons in the control strategy work space. See
the previous section, Select and Place Control Icons, for procedure and tips.

RESULT: Icon symbols in the work space are red to indicate that they do not
yet have connections to required inputs and outputs. A thick gray
box surrounds the currently selected icon.
2. Click the arrow head of a point that is either an input to or output from one of
the control icons.

NOTE: Each physical output point can connect to only one icon.

Feedback
Points If the schematic has feedback points that you want to connect to
control icons, double-click the digital output point to access these
hidden points and their user addresses.

RESULT: The arrow head turns black.

3. Double-click the desired control icon in the work space.


Or, if the desired control icon is the currently selected icon (a gray box
surrounds it), click menu item Edit, then drop-down item Connect symbol.

RESULT: The control icon input/output dialog box that lists requirements for
inputs and outputs displays.

For example, the PID dialog box prompts for Y, X, and W:

4. Click the input/output type that corresponds to the point you selected.

EN2Z-0937GE51 R0518 230


CARE CONTROL STRATEGY

RESULT: A check mark appears in the check box to indicate its selection.
For example, if you click the Y variable in the PID dialog box:

No checkmark If a checkmark does not appear, you do not have the


appropriate point type for the variable. Close the dialog box
and select a different point.

Tip ⇒ To close the dialog box without selecting a variable, click the icon
symbol in the dialog box.

5. Click the control icon symbol in the dialog box.

RESULT: a. The dialog box closes.


b. The active control icon changes color to dark blue.
c. Software adds a short connecting line next to the icon on the left
(outputs are always on the left).
d. Two lines appear in the work space. One line is vertical; one is
horizontal. Where they intersect each other is the focus point for
mouse clicks. You can move these lines by moving the mouse:

– When you move the mouse left or right, the vertical line
moves left or right.
– When you move the mouse up or down, the horizontal
line moves up or down.

If these actions do not occur, the point you selected was not
appropriate for the variable you selected in the icon dialog box.
Select a different point arrow head or double-click the icon again
and select a different variable.

6. Move and click the intersection point to create connecting lines. See the
Routing Connecting Lines note for details. Move the intersection point over the
point arrow head until a cross, +, appears. Click the left-hand mouse button to
complete the connection.

RESULT: Software connects the point and icon. (If it doesn’t, see the No
Connection note following this procedure.)

231 EN2Z-0937GE51 R0518


CONTROL STRATEGY CARE

7. Repeat this sequence with the other inputs and outputs the control icon
requires.

RESULT: After all connections are done, the control icon changes color to
light blue to indicate that the loop is completely connected.

Routing Connecting Lines Connecting lines sometimes pass through other control icons or cross other
connecting lines. This may make the control strategy confusing.

To route connecting lines around icons:

a. Move the intersection point to just before an icon and click.

RESULT: Software creates a line just that long.

b. Move the intersection down below the icon and click again.

RESULT: Software creates another connecting line.

c. Move the intersection point past the icon and click again to create another
short line.

Every time you click, software creates a line. By moving the intersection point
around other icons and clicking at the angles, you can avoid crossing other icons
and lines.

Also see the Examples section for more tips on creating connections.

No Connection If you click new points before software has a chance to create a connecting line,
software may not be able to make the final connection when you reach the point
arrow head. To prevent this, wait after you click until a gray-colored line appears.
Then, move the intersection point to another point and click.

Also, make sure you line up the intersecting line and the last red line before you
click again. Otherwise, software cannot create the next line.

If you are in a situation where software is not making the final connection, delete all
lines that you made for this connection and start over again.

No Diagonals Connections can only run vertically or horizontally. They cannot run diagonally.

Connect Two Control Icons


Purpose Connect several control icons together so that the output from one icon is an input
to the second.

Procedure 1. Select the first control icon and place it in the work space.

2. Select a second control icon and place it in the work space.

3. Double-click each icon, in turn, from left to right, to display their input/output
dialog boxes.

EN2Z-0937GE51 R0518 232


CARE CONTROL STRATEGY

4. Select a variable from each box. One variable should be an output; the other,
an input.

5. Click the icon symbol in the dialog box on the left to close both dialog boxes.

RESULT: The icon on the left displays with a short connecting line. The
intersection lines display.

6. Move the intersection point over the left edge of the icon on the right.

7. Click to make the connection.

Example To connect the output of an Add icon with one of the PID controller inputs:

1. Place the PID controller icon in the work space.

2. Place the Add icon in the work space to the right of the PID controller icon.

3. Double-click the PID controller icon.

RESULT: The PID controller icon input/output dialog box displays.

4. Double-click the Add icon.

RESULT: The Add icon dialog box displays.

5. Click the Y check box in the Add icon dialog box.

RESULT: A check mark appears in the check box.

6. Click the X check box in the PID controller dialog box.

RESULT: A check mark appears in the check box.

7. Click the red PID controller icon in the PID controller dialog box.

RESULT: Both dialog boxes close. Both icons in the work space turn dark
blue. A short connecting line appears on the right side of the PID
icon. The intersection lines appear in the work space.

8. Place the intersection point on the Add icon. Move the mouse so the horizontal
line overlaps the short connecting line from the PID icon.

9. Click to complete the connection.

RESULT: Both control icons turn red and a line connects the two icons.

Dialog Box Closing In general, dialog boxes close when you select the icon symbol in the dialog box on
the left.

Multiple Inputs An output from a control icon can connect to many inputs of other control icons. For
example, continually click the YD check box of the digital output until it turns gray.
Make the connection as described in this procedure.

Examples
Plan the placement of control icons and pseudopoints so you can make necessary
connections clearly. This section presents examples of good connections and
confusing connections.
.
Placement Tips Position control icons just below their related equipment. It helps if output points or
icons are to the left of the control icon and input points or icons are to the right of
the control icon.

233 EN2Z-0937GE51 R0518


CONTROL STRATEGY CARE

Make connections to physical and pseudopoints as you place control icons. If you
place all the icons first, and then try to make connections, you may need to
reposition some icons to make less confusing connections.

Example with Clear Connections The following diagram includes three control icons with connections to physical
points, pseudopoints, and each other. Note that the connection lines cross a
minimum amount of times so that the control strategy is easy to read.

Example with
Confusing Connections The following diagram has the same three icons and points as the previous
example, but because of the placement of the icons and connections, it is very
confusing.

How to Cross Lines The following example presents a method of crossing lines that do not connect so
that it is obvious that they do not connect. The idea is to draw lines next to each
other for a short distance instead of directly crossing the lines.

EN2Z-0937GE51 R0518 234


CARE CONTROL STRATEGY

Delete a Control Icon and its Connections


Procedure 1. Click the icon you want to delete to select it (if not already selected).

RESULT: a gray box surrounds the currently selected icon.

2. Click Edit, then drop-down item Delete symbol.


Or, hold down Ctrl key and press Delete key.

RESULT: A Question dialog box displays that asks “Delete Symbol: Are you
sure?”

3. Click Yes to delete, or No to cancel the operation.

RESULT: If you click Yes, software deletes the control icon with all its
connections.

Delete a Completed Connection


Procedure 1. Double-click the control icon in the work space that has the connection to be
deleted.
Or, if the icon is the currently selected icon (a gray box surrounds it), click
menu item Edit, drop-down item Connect symbol.

RESULT: The related input/output dialog box displays.

2. Click the check box to which the connection was made until the check mark
disappears and the box is white.

3. Click the red control icon in the control icon dialog box.

RESULT: Software deletes the connection and closes the dialog box.

Delete an Incomplete Connection


1. Place the intersection point on the end point of a connection that is not yet
complete.

235 EN2Z-0937GE51 R0518


CONTROL STRATEGY CARE

2. Click the right-hand mouse button once.

RESULT: Software deletes the connection.

Each time you click the right-hand mouse button, software deletes
a further connection. You do not have to move the mouse.

The control icon turns red.

EN2Z-0937GE51 R0518 236


CARE CONTROL STRATEGY

Pseudopoints and Flags


Definition Pseudopoints and flags have no physical basis and, therefore, no technical
address. CARE calculates the value of a pseudopoint. You assign a user address
to a pseudopoint to be able to use and display them like physical points. The
difference between physical points and pseudopoints is that pseudopoints do not
have a technical address.

Example The calculated flow temperature setpoint of a heating plant is a pseudopoint.

Types There are seven types of pseudopoints and flags:

• VA for Pseudo analog


• VD for Pseudo digital
• VT for Pseudo totalizer
• GA for Global analog
• GD for Global digital
• FA for Flag analog
• FD for Flag digital

Pseudopoints can be analog, digital, or totalizer. They represent calculated values


within the controller. Flags can be analog or digital and represent z-registers within
the RACL application program.

Limitations Each controller can have a maximum of 256 pseudopoints. Three digital
pseudopoints are reserved (STARTUP, SHUTDOWN, and
EXECUTING_STOPPED), leaving 253 free for user assignment. The max limits
changed for controller OS > 2.03 to 253 + 3 internal.

There is no maximum number for flags.

Globals Global points are a type of pseudopoint (GA or GD) that can be either an input or
output. The purpose of global points is to share point information across controllers
on a bus.

Global inputs receive information from a point in another controller. Use a global
input when one controller has a point that should be global to many other
controllers.

Global outputs send information to other points in other controllers. Use a global
output when one controller has a point that is global to only one point in another
controller. You can also use global outputs for some control icons that only connect
to outputs and the output must be global. Global outputs can only be associated
with pseudopoints or output points (not input points).

Centrals Note Central PCs such as the Excel Building Supervisor (XBS) and Excel Building
Supervisor-Integrated (XBS-i) only read global originator points. The values of
global receiver points are only available via the B port of the controller.

Global Inputs Each global input is associated with a pseudopoint or physical point (originator
point) somewhere on the bus and has the same user address, controller number in
the technical address, engineering unit, and type (analog or digital) as the point.
The originator point cannot be a global point. The technical address for a
pseudopoint is 99.99.

237 EN2Z-0937GE51 R0518


CONTROL STRATEGY CARE

You select the correct type and enter the correct user address when you create the
global point. To set the appropriate controller number in the technical address and
the engineering unit, use the Data Point Description Editor described in the Editors
chapter in this manual. You can edit point data after you attach the plant.

Global Input Point Operation

The system updates global inputs every 2 minutes. It also updates global analog
inputs when the originator point changes significantly. If the point value is greater
than 20, the change must be at least 1 percent. If the point value is less than or
equal to 20, the change must be at least .2 units. For example:

Point Value Change

100 1
200 2
50 .5
10 .2
5 .2

For global digital points, a change of state triggers an update.

Global Outputs Each global output is associated with a pseudopoint or physical point (“receiver”
point) somewhere on the bus and has the same user address, technical address,
engineering unit, and type (analog or digital output) as the point. The technical
address for a pseudopoint is 99.99.

EN2Z-0937GE51 R0518 238


CARE CONTROL STRATEGY

You select the correct type and enter the correct user address when you create the
global point (next section, New Pseudopoints and Flags). To set the appropriate
technical address, output type, and engineering unit, use the Data Point Description
Editor described in the Editors chapter in this manual. You can edit point data after
you attach the plant.

To use a physical point as the originator, use the IDT icon to convert the physical
point value to a global point (GA or GD).

Global Output Point Operation

The system updates the receiver points when the global analog outputs change
significantly. If global value is greater than 20, the change must be at least 1
percent. If global value is less than or equal to 20, the change must be at least .2
units. For example:

Global Value Change

100 1
200 2
50 .5
10 .2
5 .2

For global digital points, a change of state triggers an update.


There is no automatic 2-minute refresh for global output points.

Flags Flags are pseudopoints that only appear in the CARE work space. They are not
accessible later through the Datapoint Editor and any other operator terminal but
through Live CARE.

Deletions Software displays a message that it will delete pseudopoints and flags that are not
required when the plant is assigned to a controller (Attach Controller function). You
can accept or reject the deletion. In addition, you can use the Delete unused
software points function under the Edit menu item in Control Strategy to delete
flags.

Special Pseudopoints There are three special pseudopoints, STARTUP, SHUTDOWN, and
EXECUTING_STOPPED, that CARE automatically attaches to each EXCEL 5000
controller. Each point has an engineering unit of Normal/Alarm. Following is a
description of each point. You can use the Data Point Editor to enhance these
points. For example, by making the STARTUP point an alarm point and changing
the active/passive flag, the point will go into alarm, if the application program stops.

NOTE: The following descriptions assume the controller application is both the
time schedules and the RACL code.

STARTUP has a value of 1 (alarm) when the controller application is running and a
value of 0 (normal) when the application is not running. When a database is
downloaded to the controller, the application attempts to start. If there are fatal CPU
errors, the application does not run. If there is a power failure and the battery
maintains the application in memory, the application again attempts to restart. You
can use the Stop Application function in XBS or XI584 to set this point to a zero
value. You can use the Start Application function in XBS or XI584 to attempt to
restart the application.

SHUTDOWN has a value of 0 (normal) when the controller application is running


and a value of 1 (alarm) when the controller application is not running. The only way
to get this point set to 1 (other than manually fixing it) is to use the Stop Application
function in XBS or XI584. If RACL software stops this point, the point remains set to
zero.

EXECUTING_STOPPED has a value of 0 (normal) when the RACL program in the


controller is running and a value of 1 (alarm) when RACL has stopped. If the
controller detects an error condition that will cause RACL to halt (such as a disabled
point), software sets the point to a value of 1. If you manually fix this point to a value
of 1, RACL execution halts and all outputs are frozen at their last value. You cannot
restart RACL by fixing this point back to zero or by putting it in the automatic mode.

239 EN2Z-0937GE51 R0518


CONTROL STRATEGY CARE

You can only restart RACL with a power reset or by using the Start Application
function in XBS or XI584.

A typical application of the STARTUP point is to stage loads when the controller
application program first starts. For example, if the RACL program in the controller
calls for three large chiller plants to be on after the first cycle when the controller
starts, you can use the STARTUP point in a switching table to delay the outputs
with different times to keep from starting all three chillers at exactly the same time.

Section Contents This section includes:

• General Steps
• Create New Pseudopoints and Flags
• Load/Assign Pseudopoints and Flags
• Search for Pseudopoints and Flags via Keyboard
• Modify Pseudopoint and Flag User Address
• Delete Pseudopoints and Flags
• Connect a Pseudopoint or Flag to a Control Loop
• Change a Pseudopoint or Flag User Address

General Steps
Working with pseudopoints and flags generally includes the following actions:

• Create a new pseudopoint/flag or load pseudopoints/flags


• Assign the created pseudopoint/flag to the software bar
• Connect the pseudopoint/flag to a control strategy symbol

Refer to the following sections for detailed descriptions.

Software Points Behavior on


Software Bar Existing pseudopoints/flags can be unassigned or assigned to the software point
bar. Assigned pseudopoints/flags appear with their point type abbreviations on the
software bar. Unassigned points can be accessed from a list (see following
sections). Assigned pseudopoints/flags should be connected to control strategy
symbols. Only assigned pseudopoints/flags can be connected to control strategy
symbols. After connection they are “used”.

Points are used when they are:

• connected to control icons


• used as internal points of XFMs
• mapped to XFM parameters
• contained in switching tables
• referenced in time programs

Unassigned pseudopoints/flags that are not used in the application are “unused”
software points. Unused software points can be deleted, used points cannot.

CARE automatically updates the software bar. It removes all points from the
software bar that are not connected to a control strategy symbol.

NOTE: The points are not deleted. They can still be accessed from a list via the
Edit/Load Software Points command.

The software bar will be automatically updated when:

• creating a control loop


• loading a control loop
• deleting a control loop
• deleting a control strategy symbol
• opening and closing the Delete Unused Software Points dialog box even if no
software point was deleted.

EN2Z-0937GE51 R0518 240


CARE CONTROL STRATEGY

Create/Assign New Pseudopoints and Flags


Purpose Create a new pseudopoint/flag and assign it to the software bar.

Procedure 1. Click on a free position in the software point bar where you want to place the
new pseudopoint/flag. Locate it near the relevant control icon(s).

RESULT: The Create/Select Software Address dialog box displays.

The selected software bar position is displayed at the bottom line


of the dialog box. The list displays all existing pseudopoints/flags
including unassigned, assigned and connected, assigned and
unconnected pseudopoints/flags. Unassigned and assigned
points/flags can be distinguished by the following symbols:

Assigned points: Pseudopoints/flags that reside on the software


bar.

Unassigned pseudopoints/flags or points in switching tables in


folder color with point abbreviation.

Unassigned software points mapped to internal datapoints of


XFMs.

Unassigned software points mapped to XFM parameters.

241 EN2Z-0937GE51 R0518


CONTROL STRATEGY CARE

Each pseudopoint/flag type has its own colored folder, which can
be empty or contain already created pseudopoints/flags. Folders
can be opened by clicking on the + symbol.

2. Click the desired pseudopoint/flag folder or any existing pseudopoint/flag in the


open folder.
3. Click right mouse button, and with left mouse button click New in the context
menu,

or

click menu item Edit, then drop-down item New.

RESULT: The New Software Datapoint dialog box displays.

4. Select a point subtype in the Subtype drop-down list box (if available and
desired).

5. Enter a user address in the User Address field.

User addresses must include one non-digit character and cannot include tabs,
double quotes, ?, *, or space characters. All other ASCII characters are
allowable (A-Z, 0-9, +, -, _, etc). For example, 12A is a valid user address, but
12 is not.

If you are creating a global point, enter a user address that matches the
pseudopoint or physical point that you want to associate with the global. Also,
select the type (analog [GA] or digital [GD]) that matches.

6. Click OK.

RESULT: The pseudopoint/flag is automatically assigned to the software


point bar and is shown with its abbreviation as follows:

EN2Z-0937GE51 R0518 242


CARE CONTROL STRATEGY

• VA for Pseudo analog


• VD for Pseudo digital
• VT for Pseudo totalizer
• GA for Global analog
• GD for Global digital
• FA for Flag analog
• FD for Flag digital

7. To connect a pseudopoint/flag to a control strategy symbol, see Connect a


Pseudopoint or Flag to a Control Loop section.

NOTE: Assigned pseudopoints/flags that are not connected to any control


strategy symbol become unassigned points when one of the following
is done:

• creating a control loop


• loading a control loop
• deleting a control loop
• deleting a control strategy symbol
• opening and closing the Delete Unused Software Points
dialog box even if no software point was deleted.

8. For creating further pseudopoints/flags, click on the desired position in the


software bar where the next point is to be created and repeat steps 2 through
6.

NOTE: If you do not select a software point bar position, the pseudopoint/flag
is created as unassigned pseudopoint/flag and has to be assigned to
the software point bar using the Assign to SW Bar command
separately (see Load/Assign Pseudopoints and Flags section).

Load/Assign Pseudopoints and Flags


Purpose Load existing pseudopoints or flags created via the switching logic function or from
other plants, and assign them to the software bar.

Procedure 1. Load a control loop (menu item File, drop-down item Load).

2. Open the Create/Select Software Address dialog box by clicking either on the
position in the software point bar where you want to place the pseudopoint/flag
or by selecting menu item Edit, then drop-down item Load Software Points.

243 EN2Z-0937GE51 R0518


CONTROL STRATEGY CARE

3. Open the pseudopoint/flag folder, and click the pseudopoint/flag you want to
assign to the software bar.

4. Select a position on the software bar by clicking left mouse button.

RESULT: The selected software bar position is shown at the bottom line of
the dialog box.

NOTE: If you do not select a position on the software bar before assigning the
point, CARE will ask you to select a position after step 5.

5. Click right mouse button, and with left mouse button click Assign to SW Bar in
the context menu, or

click menu item Edit, then drop-down item Assign to SW Bar.

RESULT: The pseudopoint/flag is assigned to the software bar and its


abbreviation appears as follows:

• VA for Pseudo analog


• VD for Pseudo digital
• VT for Pseudo totalizer
• GA for Global analog
• GD for Global digital
• FA for Flag analog
• FD for Flag digital

EN2Z-0937GE51 R0518 244


CARE CONTROL STRATEGY

In the Create/Select Software Address dialog box the


pseudopoint/flag gets the assigned symbol at the user address
name.

6. To connect a pseudopoint/flag to a control strategy symbol, see Connect a


Pseudopoint or Flag to a Control Loop section.

NOTE: Assigned pseudopoints/flags, which are not connected to any control


strategy symbol, become unassigned points when one of the
following is done:

• creating a control loop


• loading a control loop
• deleting a control loop
• deleting a control strategy symbol
• opening and closing the Delete Unused Software Points
dialog box even if no software point was deleted.

7. For assigning further pseudopoints/flags, click on the desired position on the


software point bar where the next point is to be created and repeat steps 4
through 5.

Search for Pseudopoints and Flags via Keyboard


Assumption The Create/Select Software Address dialog box is open.

Procedure 1. Type the complete name or single characters (search entry) of the name you
want to find.

RESULT: CARE automatically finds the first name that matches the
search entry. CARE searches from the VA through the FD
folder and finds matched datapoint names in closed folders too.

If a datapoint name you search for is not found, CARE


continues searching with the next search entry you enter.
CARE does not distinguish between upper-case and lower-case
letters except on vowel mutations or country specific
characters.

2. To find the next name that matches the same search entry, click the asterisk
(*).

Example:

The following datapoints are available in the Create/Select Software Address


dialog box:

L22_VA_Release (VA-folder)
L22_GA_Setpoint (GA-folder)

The search entry “L22” is entered.

CARE first finds the L22_VA_Release datapoint name. After entering the
asterisk (use SHIFT key) the L22_GA_Setpoint datapoint name is found.

3. To find a different datapoint name, enter the new search entry.

Modify Pseudopoint and Flag User Address


Purpose Modify pseudopoint or flag user address.

245 EN2Z-0937GE51 R0518


CONTROL STRATEGY CARE

Procedures There are two ways to modify a pseudopoint/flag user address:

A. By selecting the pseudopoint/flag on the software bar.


B. By selecting the pseudopoint/flag in the Create/Select Software Address dialog
box.

A. 1. Select the pseudopoint or flag to be modified from the software point bar.

2. Click menu item Edit, then drop-down item Modify Pseudo User Address, or
press F5.

RESULT: The Modify Pseudo User Address dialog box displays.

3. Type to change the address in the editing field.

User addresses must include one non-digit character and cannot include tabs,
double quotes, ?, *, or space characters. All other ASCII characters are
allowable (A-Z, 0-9, +, -, _, etc). For example, 12A is a valid user address, but
12 is not.

4. Click Modify to save changes. The dialog box remains open so that you can
select other pseudopoints or flags to modify.

5. Click Cancel or press F5 to end the Modify function.

B. 1. Open the Create/Select Software Address dialog box by clicking on a blank


position on the software point bar or by selecting menu item Edit, then drop-
down item Load Software Points.

EN2Z-0937GE51 R0518 246


CARE CONTROL STRATEGY

2. Open the pseudopoint/flag folder, and click the pseudopoint/flag you want to
modify.

3. Click right mouse button, and with left mouse button click Modify in the context
menu, or

click menu item Edit, then drop-down item Modify.

RESULT: The Modify Pseudo User Address dialog box displays.

4. Type to change the address in the editing field.

User addresses must include one non-digit character and cannot include tabs,
double quotes, ?, *, or space characters. All other ASCII characters are
allowable (A-Z, 0-9, +, -, _, etc). For example, 12A is a valid user address, but
12 is not.

5. Click Modify to save changes.

6. To modify further points/flags, repeat steps 2 through 5.

Delete Pseudopoints and Flags


Purpose Delete pseudopoint or flag.

NOTE: Used pseudopoints/flags cannot be deleted.

Points are used when they are:

• connected to control icons


• used as internal points of XFMs
• mapped to XFM parameters
• contained in switching tables
• referenced in time programs

Procedures There are two ways to delete pseudopoints/flags:

A. Via the Edit/Delete Unused Software Points command, you can delete one
or several pseudopoints/flags.
B. Via the Edit/Load Software Points command or by clicking on the software
bar, you can delete one pseudopoint/flag after another individually.

A. 1. Click menu item Edit, then drop-down item Delete Unused SW Points.

247 EN2Z-0937GE51 R0518


CONTROL STRATEGY CARE

RESULT: The Delete Unused Software Points dialog box displays.

2. Click the points you want to delete (hold down SHIFT key while you click to
select multiple points).

3. Click Delete.
RESULT: All selected software points are deleted. The deleted points are no
longer available on the software points bar.

4. Click Cancel to close the dialog box.

RESULT: Points that you did not delete remain in the plant

B. 1. Open the Create/Select Software Address dialog box by clicking on a blank


position on the software point bar or by selecting menu item Edit, then drop-
down item Load Software Points.

2. Open the pseudopoint/flag folder, and click the pseudopoint/flag you want to
delete.

EN2Z-0937GE51 R0518 248


CARE CONTROL STRATEGY

3. Click right mouse button, and with left mouse button click Delete in the context
menu, or

click menu item Edit, then drop-down item Delete.

RESULT: The selected pseudopoint/flag is deleted. The deleted


pseudopoint/flag is no longer available on the software points bar.

Connect a Pseudopoint or Flag to a Control Loop


NOTE: The control icon must already be selected and placed in the work space.

Procedure 1. Click the desired pseudopoint on the software point bar.


If you select a physical point on the physical data point bar, you cannot select a
pseudopoint.

When creating the connections, pseudopoint type and the control icon´s inputs
or outputs must match.

RESULT: The box turns red.

2. Double-click the control icon in the work space to which the pseudopoint
should connect.

Or, if the control icon is the currently selected icon (a gray box surrounds it),
click menu item Edit, then drop-down item Connect symbol.

RESULT: The input/output dialog box for the control icon displays.

3. Click the check box of the input or output to which the pseudopoint should
connect.

4. Click the red control icon in the input/output dialog box.

RESULT: The dialog box closes. The control icon turns dark blue. The
intersection lines appear.

5. Move the intersection point and click to connect the pseudopoint with the
control icon (same procedure as in the Connect Two Control Icons section).

XFMs
IMPORTANT
Free programming and XFMs must not be used together in one and the
same control loop.

Section Contents This section includes:

• Map Software Point to XFM Parameter


• Map Software Point to an XFM Internal Datapoint
• Create User Addresses of the Same Name and Map to XFM Internal Datapoint
• Unmap Mapped Software Point from an XFM Parameter
• Modify XFM Parameter

249 EN2Z-0937GE51 R0518


CONTROL STRATEGY CARE

Map Software Point to XFM Parameter


Purpose Assign (map) a software point to an XFM parameter. The following point types can
be mapped to an XFM parameter

• Pseudo analog (VA)


• Pseudo digital (VD)
• Pseudo totalizer (VT)

These points can be preassigned to the software point bar or unassigned. They can
already be mapped to an internal XFM datapoint.

Hardware points, global points and flags cannot be mapped to XFM parameters.

NOTE: Mapped parameters can be displayed and modified in XBS central


graphics. Graphics for a Central will be created with an appropriate
graphic software program, for example Designer. The user addresses
that reference a parameter will be placed in the graphics.

Procedures There are two ways to map a software point to an XFM parameter.

A. From the software points bar


B. From the Create/Select Software Address dialog box

Common Steps 1. With right mouse button, click on the XFM control strategy icon.

RESULT: The Submodule - Parameters <XFM name> dialog box displays.

2. In the list, click desired parameter to which you want to map the software point.

Software Points from the


Software Points Bar 1. On the software points bar click the software point you want to map to the XFM
parameter.

RESULT: For the parameter (highlighted) in the Submodule - Parameters


<XFM name> dialog box the software point selected is shown in
the Value/Mapped SW Point column. The previous unit of the
parameter is invalid indicated by three dashes (---).

EN2Z-0937GE51 R0518 250


CARE CONTROL STRATEGY

2. Click OK in the Submodule - Parameters <XFM name> dialog box .

RESULT: The software point is mapped to the parameter.

From the Create/Select


Software Address
Dialog Box 1. Open the Select User Address dialog box by clicking on the software points bar
or by the selecting menu item Edit, then drop-down item Load Software Points.

2. Click the software address (software point) you want to map to the XFM
parameter selected in step 2 (Common Steps). Software points can already be
assigned to the software point bar or unassigned indicated by the following
icons at the address:

251 EN2Z-0937GE51 R0518


CONTROL STRATEGY CARE

Assigned point on the software bar. This icon has priority over the others
meaning if e. g. a point is an XFM internal datapoint but at the same time
assigned to the software bar, this icon will display.

Unassigned software point in folder color with point abbreviation.

Unassigned software point mapped to an XFM internal datapoint.

3. For an assigned point finish with step 5. For an unassigned point continue with
step 4.

4. Click right mouse button and with left mouse button click Assign to XFM
Parameter in the context menu.

or

click menu item Edit, then drop-down item Assign to XFM Parameter.

RESULT: For the parameter (highlighted) in the Submodule - Parameters


<XFM name> dialog box the software point selected is shown in
the Value/Mapped SW Point column. The previous unit of the
parameter is invalid indicated by three dashes (---).

EN2Z-0937GE51 R0518 252


CARE CONTROL STRATEGY

5. Click OK in the Submodule - Parameters <XFM name> dialog box .

RESULT: The software point is mapped to the parameter. In the


Create/Select Software Address dialog box it is indicated by the
icon at the address name changing to the following shape:

This icon change concerns only software points, which are not
assigned to the software point bar. Assigned software points are
indicated with the following icon and keep this shape after they are
mapped to an XFM parameter.

Map Software Point to an XFM Internal Datapoint


Purpose Assign (map) software point to an XFM internal datapoint of the same type.
Software points can only be mapped to an XFM internal datapoint of the same type,
in other words, pseudo analog to pseudo analog or global analog, pseudo digital to
pseudodigital or global digital etc. Compatibility is checked by CARE.

The following point types can be mapped to an XFM internal datapoint, if the point
type matches:

• Hardware points
• Global analog (GA)
• Global digital (GD)
• Pseudo analog (VA)
• Pseudo digital (VD)
• Pseudo totalizer (VT)

These points can be preassigned to the software point bar or unassigned.

Flags cannot be mapped to XFM internal datapoints.

Procedures There are three ways to map a software point to an XFM internal datapoint.

1. From the software points bar


2. From the Create/Select Software Address dialog box
3. By creating and connecting user addresses of the same name to XFM
internal datapoints

253 EN2Z-0937GE51 R0518


CONTROL STRATEGY CARE

User Addresses from the


Software Points Bar 1. Double-click the XFM icon and select the Datapoints button in the XFM I/O
dialog box.

RESULT: The Datapoints From XFM <XFM name> dialog box displays
showing the internal datapoints.

2. Click the datapoint to which you want to map a software point (CARE point =
CARE user address).

3. On the software point bar click the desired software point (CARE point) you
want to map to the internal datapoint, or click on a hardware point.

RESULT: The CARE point is located next to the internal datapoint (CARE
User Address column).

4. Click OK to confirm.

RESULT: The CARE point is mapped.

NOTE: You can change the mapped point by mapping any other compatible
point to the XFM datapoint.

From the Select Software 1. Double-click the XFM icon and select the Datapoints button in the XFM I/O
Address Dialog Box dialog box.

RESULT: The Datapoints From XFM <XFM name> dialog box displays
showing the internal datapoints.

EN2Z-0937GE51 R0518 254


CARE CONTROL STRATEGY

2. Open the Create/Select Software Address dialog box by clicking on the


software points bar or by selecting menu item Edit, then drop-down item Load
Software Points.

3. Click on the software address (CARE point of the same type!) you want to map
to the XFM internal datapoint.

Software addresses can already be assigned to the software point bar or


unassigned indicated by the following icons at the user address:

Assigned points: Pseudopoints/flags that reside on the software bar.

Unassigned software point in folder color with point abbreviation.

Unassigned software point mapped to an XFM internal user address.

Unassigned software point mapped to an XFM parameter.

255 EN2Z-0937GE51 R0518


CONTROL STRATEGY CARE

4. Click right mouse button and click on Assign to XFM Datapoint in the context
menu.

or

click menu item Edit, then drop-down item Assign to XFM Datapoint.

RESULT: The CARE point is located next to the internal datapoint (CARE
User Address column).

5. Click OK to confirm.

RESULT: The software point is mapped to the XFM internal datapoint. In the
Create/Select Software Address dialog box it is indicated by the
icon at the address name changing to the following shape:

This icon change concerns only software addresses, which are not
assigned to the software point bar. Assigned software addresses
are indicated with the following icon and keep this shape after they
are mapped to an XFM internal datapoint.

NOTE: You can change the mapped point by mapping any other compatible
point to the XFM datapoint.

EN2Z-0937GE51 R0518 256


CARE CONTROL STRATEGY

Automatically Create User Addresses of the Same Name and Map to XFM Internal Datapoint
Purpose Create XFM internal user address of the same name and map it to XFM internal
datapoint. Using this function, it is possible to automatically create points for
exchange of information between XFMs.

Procedure 1. To open the Datapoints From XFM <XFM name> dialog box, double-click the
XFM icon and click the Datapoints button.

2. Click the Set button.

RESULT: The Question dialog box displays asking you for confirmation of
each XFM datapoint you want to connect to the CARE datapoint of
the same name.

NOTE: This dialog is only displayed, if a corresponding datapoint already


exists. If not, a point is automatically created without any question.

3. Click Yes, if you want to connect the XFM datapoint displayed with the existing
CARE point of the same name.

4. Click No, if you want to skip this datapoint for connection.

RESULT: The connections between XFM points and CARE datapoints are
established.

257 EN2Z-0937GE51 R0518


CONTROL STRATEGY CARE

5. Click OK to confirm.

RESULT: The CARE user addresses are mapped to their XFM internal
datapoints.

Unmap Mapped Software Point from an XFM Parameter


Purpose Unassign (unmap) a mapped software point from an XFM parameter.

Procedure 1. With right mouse button click on the XFM control strategy icon.

RESULT: The Submodule - Parameters <XFM name> dialog box displays.

2. In the list, click desired parameter, from which you want to unmap the software
point.

3. Click the Unmap button.

RESULT The mapped software point will be moved from the parameter and
the parameter gets his value and unit back. In the Create/Select
Software Address dialog box the “mapped” icon at the user
address disappears.

Modify XFM Parameter

EN2Z-0937GE51 R0518 258


CARE CONTROL STRATEGY

Procedure 1. With right mouse button click on the XFM control strategy icon.

RESULT: The Submodule - Parameters <XFM name> dialog box displays.

2. In the list box click on the parameter you want to modify.


3. Edit the parameter in the New Value field. You can use the Cut, Copy, Delete,
Paste and Undo functions from the context menu by clicking right mouse button
when the field is highlighted.

4. Change the engineering unit of the parameter in the New Unit field, if desired.

5. Click Modify to confirm the modified parameter.

6. Click OK to confirm the modification.

Plant Information Displays


You can display the following information:

• Physical points
• Physical point user addresses
• Pseudopoint user addresses

Physical Point Information

259 EN2Z-0937GE51 R0518


CONTROL STRATEGY CARE

Procedure 1. Double click (left-hand mouse button) the arrow head for the physical data
point.

RESULT: The Datapoint information window displays with user address and
point type.

2. Click OK to close window when done viewing the information.

User Addresses
Procedure 1. Click View, then drop-down item Physical user address for physical points or
Pseudo user address for pseudopoints.

RESULT: The user addresses for the selected type display under the plant
schematic. The first letter of every user address is directly beneath
the triangle to which the user address belongs.
Software places a check mark next to the Physical (or Pseudo)
user address function to indicate that it is on.

2. To end the function, click View, then drop-down item Physical (or Pseudo) user
address again.

RESULT: The check mark disappears and the user addresses disappear
from the screen.

Keyboard Commands You can hold down the Ctrl key and press p to display physical addresses or s to
display pseudopoint addresses. Repeat action to remove the address display.
Physical and Pseudo
Point Displays You cannot display physical point user addresses at the same time as pseudopoint
user addresses.

Single Address Display If you move the cursor over a triangle or pseudopoint abbreviation and press and
hold the left-hand mouse button down, the user address for the point displays with
either a red exclamation symbol or a green check mark symbol. When you release
the mouse button, the display disappears.

The red exclamation symbol appears for:

• hardware points (with one allowable connection) that are used in an XFM
• digital outputs that are connected to a symbol
• flex points that are connected to a symbol
• software points that are connected to an output pin of a symbol.

You cannot display a single address if the View Physical (or Pseudo) user address
function is on.

Loop Management
There are several functions that you can use to copy, check, delete, and print loops:

• Copy a Control Loop to reuse it with modifications (or as is).


• Delete a Control Loop if it is no longer necessary.
• Check the Control Loop to make sure all connections are complete.
• Print a Control Loop for documentation purposes.

This section provides procedures for these functions.

Copy a Control Loop


Purpose Make a copy of an existing control loop and save it under another name.

Procedure 1. Click File, then drop-down item Copy.

EN2Z-0937GE51 R0518 260


CARE CONTROL STRATEGY

RESULT: The Copy control loop dialog box displays.

2. Select the control loop name to be copied from the list of existing control loops.

RESULT: The selected control loop name displays in the Control loop editing
field.

3. Click the Save as through editing field

RESULT: The cursor appears in the editing field.

4. Enter the new control loop name in the editing field. The new control loop name
cannot already exist.

5. Click OK to copy and then close the dialog box.

Delete a Control Loop


Purpose Erase a control loop is no longer necessary.

Procedure 1. Click File, then drop-down item Delete.

RESULT: The Delete control loop dialog box displays.

261 EN2Z-0937GE51 R0518


CONTROL STRATEGY CARE

2. Select the control loop to be deleted from the list of existing control loops.

RESULT: The control loop name to be deleted displays in the Name editing
field.

3. Click OK to delete the loop and close the dialog box.

Check a Control Loop


Purpose Verify control loop operation. Software asks whether or not to run this function when
you exit the control loop function.

Procedure 1. Click File, then drop-down item Check loop.

RESULT: The Information dialog box displays with a message that the loop is
complete or incomplete.

2. Click OK.

RESULT: A dialog box displays the number of PID controllers per system.

3. Click OK to close dialog box.

Print a Control Loop


For printing a control loop see Print Documentation chapter.

Control Strategy Exit


Procedure 1. Click File, then drop-down item Exit.

RESULT: The End control strategy dialog box displays and asks whether or
not you want to check the control loop.

2. Click Yes to initiate a software check of the loop.


Or, click No to skip the check and exit the control strategy function.

RESULT: If Yes, software checks the control loops and displays the
Information dialog box with loop statistics or an error message
about the loop. Click OK close the message boxes, exit the control
strategy function, and display the CARE main window. Click
Cancel to remain in the function.

If No, software exits the control strategy function and displays the
CARE main window.

Incomplete Loop Warning If you exit the Control Strategy function with incomplete control loops, you cannot
attach the plant.

EN2Z-0937GE51 R0518 262


CARE SWITCHING LOGIC

SWITCHING LOGIC
NOTE: The Switching Logic chapter applies to CARE XL-5000 only. For information on
switching logic in CARE Excel Web, refer to the Control Loops and Switching Table
sections.

Purpose Switching logic provides a convenient means to implement digital (Boolean) logic
control of a point. An analog or digital point is commanded to a specific value or
state if a certain set of conditions are met. Time delays can also be added. For
example, switching logic can start a return air fan 30 seconds after a supply air fan
starts.

Assumption The plant schematic is done.

Priority Switching logic has a higher priority than the control strategy. Control strategy
cannot operate on a point when switching logic has control. When switching logic
releases the point, control strategy can then command the point.

Chapter Contents
• Switching Logic Window (areas and functions)
• Switching Table Description (rows, AND logic, OR logic, and time delays)
• Switching Table Creation (including multiple tables for a point, row deletion)
• Result Row (definition and modifications)
• Digital Condition Rows (definition and modifications)
• Analog Condition Rows (definition and modifications, hysteresis)
• MATH Rows (definition and modifications, hysteresis)
• Delays for a Logical AND (Column Delay)
• OR Columns and Exclusive OR Table (COL and XOR functions)
• Pseudopoints
• Switching Logic File Management (including saving, loading, deleting, restoring)
• Macros (including saving and loading)
• Plant Information Displays
• Print Switching Tables
• Switching Logic Function Exit

See Also ⇒ Getting Started chapter for procedures to start and exit CARE

File Management chapter for procedures to back up and restore plant files

Switching Logic Window


Purpose Provide logical switching actions for digital points in the plant schematic.

Assumption The plant schematic is done.

Procedure 1. In the logical plant tree, click on the plant.

2. Click menu item Plant, then drop-down item Switching Logic. Or click the
Switching Logic button in the button bar below the menu bar.

RESULT: The Switching logic window displays with menu items File,
Software points, View, and Help as well as a sidebar with logic
icons. Example:

263 EN2Z-0937GE51 R05118


SWITCHING LOGIC CARE

Title Bar Project and plant names display in the window title bar.

Menu Bar The File, Software points, View, and Help menu items provide the following
functions (you can also select these functions via the icons below the menu bar):

FILE

Delete Erase the displayed switching table.

Copy Copy the table to another point (physical or pseudo).

Save
macro Save the current switching table to the macro library.

Save Store the currently displayed switching table. Software


names it with the output result (for example, 0, 1, or
100.0)

Load macro Recall a saved macro from the macro library.

Restore Cancel changes made to the current switching table


since the last save.

New/Clear End work on current switching table and start another


table. Software prompts whether or not to save the
current table.

Exit Stop switching logic function and return to main window.

Print Output a copy of a switching table.

SOF
POINTS
List of pseudopoint, global, and flag types. Select a type
to create a new one.

EN2Z-0937GE51 R0518 264


CARE SWITCHING LOGIC

Also, an option to Delete Unused SW Points. See the


Unused Software Points note for more details.

VIEW

Physical user
address Display user addresses for physical points in the
schematic.

Show Control
Bar Display the File menu item icons below the menu bar.

Show Tool
Box Display the switching logic icons down the right-hand
side of the window.

HELP
Display the on-line user guide topic list. See Getting
Started, On-Line Help chapter, for details on using the
help function.

About Copyright and program authors.

265 EN2Z-0937GE51 R05118


SWITCHING LOGIC CARE

File Menu Items Line


(Control Bar) These symbols allow you to select File functions without clicking File and then
selecting a drop-down item. The symbols (from left to right) correspond to the
following File functions:

New/Clear

Save

Restore

Copy

Delete

Load macro

Save macro

End

Remove the control bar from the window.

Plant Schematic This area displays the schematic created via the Schematic function. Outputs for
which a switching table exists have white cross-hatching on the input/output
triangles.

Physical Point Bar This area displays the physical points required for the schematic. If an arrowhead is
white and cross-hatched, the point has a switching table. Click the arrow head to
display the switching table for the point.

If you move the cursor over a triangle and press and hold the left-hand mouse
button down, the user address for the point displays with either a red exclamation
symbol or a green check mark symbol. The red exclamation symbol appears for
inputs. The green check mark displays for outputs. When you release the mouse
button, the display disappears.

Work Space Switching logic tables appear in this area.

Switching Logic Icons


(Tool Box) Standard logic functions available for assignment:

-ROW Delete a row from the switching table. You cannot delete
the first row. Use the File, Delete function to completely
delete a table.

+COL Add a column to the right-hand side of the switching


table.

-COL Delete a column from the switching table.

+DELAY Add a delay time value to the output of a switching table.

-DELAY Remove the delay time value row from a switching table.
MATH Enter a formula for the determination of a value.
XOR Change multiple OR columns in a switching table to
Exclusive OR columns, that is, only one column can be
true to produce a true condition for the output. In a non-

EN2Z-0937GE51 R0518 266


CARE SWITCHING LOGIC

exclusive OR table, as long as just one column is true,


software produces a true condition for the output.

+XOR Add a new line to an Exclusive OR table.

-XOR Delete a line from an Exclusive OR table.

Unused Software Points To delete unused software points in the plant schematic, select menu item Software
points, then drop-down item Delete Unused SW Points. The Delete Unused
Software Points dialog box displays with a list of those points and an option to
delete them, if desired. For example:

Click the points you want to delete (hold down the Shift or Ctrl key while you click
to select multiple points). Then click Delete for software to delete these unused
points. (The Delete key is not active until you select at least one point.)

Click Cancel to close the dialog box. Points that you did not delete remain in the
plant.

Switching Table Description

Description Switching tables consist of rows and columns. Each row represents a point or
output condition and contains user addresses, values, and switching statuses.

First (or Result) Row The first row in a table always specifies the desired output result.

For example, the following line says to turn the Supply_Fan point on after a
minimum delay of 30 seconds:

The point must be an output point, pseudopoint, or flag. For digital outputs, the
desired result can be either zero or one. For analog outputs, the result is a value.
For example, the following line says to open a damper to 100 percent:

267 EN2Z-0937GE51 R05118


SWITCHING LOGIC CARE

You create the first row in a table by clicking the arrow head for an output point or
selecting the Software points menu item and then the desired pseudopoint or flag.
Or, if there are existing logic tables that were saved as macros, you can use the
Load macro function (under menu item File) to assign them to the plant.

Subsequent Rows Subsequent rows in a table specify the required conditions to implement the desired
output result. All row conditions must be met (“AND” logic) for software to initiate the
point change.

“AND” Logic
Software determines whether or not to implement the command in the result row by
using AND logic on the rows below the result row. In other words, all conditions in
those rows must be true for software to issue the command in the result row.

For example, the following table says to turn on the return air fan if the supply fan
has been on for 30 seconds AND the discharge air temperature is greater than or
equal to 68F (20C):

The 3.0 value in the last row, second column, creates a deadband of 3 degrees with
the 68.0 value to keep the return fan from short cycling due to small changes in
temperature. In other words, the temperature has to fall at least to 65 (68 minus 3)
to invalidate the condition.

You create subsequent rows in a table by clicking the arrow heads for input or
output points, or selecting the Software points menu item and then the desired
pseudopoints or flags.

The 1’s and 0’s in the True or False columns have specific meanings. For analogs,
a 1 is true; a 0 is false. For digitals, a 1 is closed for a digital input and powered
(energized) for a digital output, no matter what the engineering unit says. A 0 for a
digital input means open. A 0 for a digital output means deenergized (not powered).

Digital vs. Analog Rows A digital point occupies one row, while an analog point occupies two rows.

The first row for an analog point specifies user address and comparison type (for
example, greater than or equal to). The second row specifies test value and
deadband differential. Switching status is in the last column and applies to both
rows.

EN2Z-0937GE51 R0518 268


CARE SWITCHING LOGIC

Limits One switching table can contain a maximum of 11 digital or 5 analog control
conditions. Switching tables can only extend as far as the lower window border.

Switching tables can contain a mixture of digital and analog control conditions.

See Also ⇒ Result Row, Digital Condition Rows, Analog Condition Rows, and MATH Rows
sections for additional details

“OR” Logic
Tables can also include “OR” logic in additional columns. OR logic tells software to
initiate the desired result if just ONE condition is true.

For example, the following table says to turn on the return air fan if the supply fan
has been on for 30 seconds OR if the discharge air temperature is greater than or
equal to 68F (20C) with a 3.0-degree deadband:

Limit You can define a maximum of 10 OR columns for one point.

See Also ⇒ OR Columns and Exclusive OR Table section for additional details

Time Delays
Purpose Delay commands and set minimum times for conditions to exist before software
acts. Options include:

• Delay for a row condition


For example, a supply fan must be on for at least 30 seconds before software
can change its status to true.

• Delay for a logical AND (column delay)


For example, software must wait another 30 seconds after all conditions are met
in a column before issuing a command.

• Delay command to the output point of the switching table


For example, software must wait 2 minutes before issuing an OFF command to a
fan.

Example The following switching table shows all three timer options:

269 EN2Z-0937GE51 R05118


SWITCHING LOGIC CARE

The Air_cool._t_status point must be on for at least 10 seconds before software


changes its status to true.

The AND conditions in this column must be true for at least 15 seconds before
software can decide to issue the ON command to the Cooler_pump.

Software must then wait an additional 2 minutes to send the ON command to the
Cooler_pump.

Procedures You add delays in the second box of result and digital rows by clicking the box and
selecting delay type and time in the Select time period dialog box that displays. See
the Result Row section and/or the Digital Condition Rows section for procedure
details.

You add the additional delay in the bottom row by using the +DELAY function. See
the Delay for a Logical AND (Column Delay) section for procedures.

Restriction You cannot add delay time to analog rows.

Delay Types When you select a delay time, you also select a delay type. Delay types include On,
Off, and Cycle.

An On delay (Te) value delays the output of an ON command.

On Delay Operation Diagram

An Off delay(Ta) value delays the output of an OFF command.

Off Delay Operation Diagram

A Cycle delay (Tv) value cycles the ON and OFF times.

EN2Z-0937GE51 R0518 270


CARE SWITCHING LOGIC

Cycle Delay Operation Diagram

On Delay Example

The Supply_fan_cmd must be on for a continuous minimum period of 20 seconds


before its 1 appears in the table AND the Analog_condition must be true (delays
cannot be assigned to analog conditions) for its 1 to appear in the table AND the
Supply_fan_status must be made for a continuous period of 10 seconds before its 1
appears in the table.

All ANDs must be true (1) for a continuous minimum period of 15 seconds before
the Extract_fan_cmd receives the ON command. But, the Extract_fan_cmd is
delayed for a further 30 seconds before actually starting up.

OR, the Manual_override can start the extract fan with a delay of 30 seconds.

Off Delay Example

Supply_fan_status remains ON in the table unless its contact goes OFF for a
continuous minimum period of 10 seconds. Software then picks up the OFF signal
and switches the Extract fan off.

Cycle Delay Example Cycle a filter cleaner ON for 60 seconds and OFF for 60 seconds if the supply fan
command is ON AND the return fan command is ON.

Filter_cleaner Tv =60s 1
Supply _f an_cmd 1
Return_f an_cmd 1

Antibounce Example

271 EN2Z-0937GE51 R05118


SWITCHING LOGIC CARE

When the supply fan first starts, air flow can be intermittently strong and weak
causing the supply fan status contact to “bounce” on and off. The Off delay of 15
seconds for the Supply_fan_status causes software to wait for a positive indication
of constant air flow.

Control Strategy and


Switching Logic Interaction If a switching table and a control strategy are both commanding the same point, the
switching table has priority.

Example 1:

Damper Tv =1s 100.0


Fan 1

Control 50.0
Strategy Damper

In this example, the damper has a value of 100.0 as long as fan equals 1. When fan
is not 1, switching logic releases the damper and the control strategy commands
damper value to 50.0.

Example 2:
Warning_light Tv =1s 1
Smoke_alarm 1 -
Manual_cmd - 1

Control ON or OFF Warning


Strategy Light

If both the smoke alarm and the manual command are false (0), the control strategy
determines whether the warning light is ON or OFF. When the smoke alarm, for
example, goes true, the warning light is alternately commanded ON (by the
switching table) and commanded to the control strategy output state. So, if the
control strategy is outputting the OFF state, the warning light cycles ON for 1
second and OFF for 1 second. But, if control strategy output is ON, the light stays
ON continuously.

Switching Table Creation


Purpose Select output points and specify conditions that software should check to determine
whether or not to initiate a change to the output point.

This section presents a general procedure that explains how to set up a logic table
and then presents examples of specific tables to clarify the procedure.

Tip ⇒ This section explains how to set up a new table. To use an existing table that was
saved as a macro, see the Load Macro section.

General Procedure 1. Select the device to be controlled. The device can be a physical output point,
pseudopoint, or flag:

To select a physical output point, click the point arrow head on the physical
point bar. Output points have an upward-pointing arrow head.

To select an existing* pseudopoint or flag, click menu item Software points,


then click desired type. A dialog box displays with a list of available points.
Select the desired point/flag from the list. Click OK to select the point. Click
Cancel to close the dialog box.

RESULT: The result row for the new switching table displays in the space
below the schematic. The row shows the user address for the

EN2Z-0937GE51 R0518 272


CARE SWITCHING LOGIC

selected point, a blank column for a delay value, and the desired
status/value column with a default status/value for the point.
Analog points always have a default value of 0.

*To create a new pseudopoint or flag, use the procedure in the


Pseudopoints section, then you can select it.

2. Select other points to create rows in the switching table. You can select any
physical points, pseudopoints, or flags.

RESULT: New rows appear below the result row:

• Each digital point has one row that shows the user address
for the selected point, a blank column, and a status
column with a default status of -.
• Each analog point has two rows that show the user address
for the selected point, a default comparison symbol (>=), a
status column with a default status of -, and a second row
with zeroes.

3. Customize the switching table by setting up time delays, changing defaults,


adding OR columns, and/or adding mathematical formulas. Each row operates
a little differently. See the row sections for procedures (Result Row, Digital
Condition Rows, Analog Condition Rows, MATH Rows).

Multiple Tables for a Point


Purpose Allow an output point to be driven to multiple states or various logical conditions.

For example, a damper must be open when a fan is ON, but closed when there is a
fire. To ensure this, set up multiple switching tables for the damper point.

Digital Tables Tip Complementary digital switching tables should not be used unless a control
strategy also controls the digital point. Switching tables that command the point to
the one state automatically toggle the point to the zero state or to the control
strategy output when its conditions become false. When a control strategy controls
a digital point, a zero switching table is the only way to drive the point to the zero
state.

Example 1

Example 2

In Example 1, if condition goes to 0, the table sets Dig_out to 0 automatically.


In Example 2, if condition goes to 1, the table sets Dig_out to 0 automatically.

Zero digital switching tables DO NOT have this same feature.

Example 1

Example 2

273 EN2Z-0937GE51 R05118


SWITCHING LOGIC CARE

In Example 1, if condition goes to 0, Dig_out remains 0.


In Example 2, if condition goes to 1, Dig_out remains 0.
This feature is useful in an application where toggling is not desired, for example, in
the case of freeze alarms. If a freeze stat alarm causes a condition and the return-
to-normal of the freeze stat causes a condition, you would not want the command
result to toggle. Instead, you would require a manual override.

Table Identifiers Each switching table for a point has a different result command. The result
command is how software distinguishes the tables. For a digital command table,
there can only be two tables, 0 and 1. Analog command tables can have multiple
tables depending on the point’s range of values.

Procedure 1. Set up the first switching table for the point and save it via menu item File,
drop-down item Save.

RESULT: Software saves the table with the value of the output result (the
table is also associated with the output point). For example, if the
output result is 1, table name is 1.

2. To create another table for the same output point, change the result command.
For example, the following table commands a damper to 100 percent open:

To create another table for the damper point, click 100.0. Software turns the
background light blue. Type a new value, for example, 0.0.

Make other changes to the table as desired. For example, change Fan status
or add other conditions.

3. Use menu item File, drop-down item Save, to save the new table when done
with modifications.

RESULT: There are now two tables for the damper point.

To Recall a Table To display a specific table for a point with multiple tables:

1. Clear the window (menu item File, drop-down item New/Clear).

2. Click the arrow head for the point.

RESULT: Software displays the Function Value dialog box that lists the
available tables.

3. Select desired table by clicking a value in the Existing values list. Then click
OK.

EN2Z-0937GE51 R0518 274


CARE SWITCHING LOGIC

You can also select a value by clicking the down arrow next to the New Value
box and selecting the desired value.

RESULT: The Function value dialog box closes and the selected table
displays in the switching logic work space.

There are other options in the Function value dialog box that allow you to create
new tables for a point and display a different table. These options are not available
unless there is a table on display.

To redisplay the Function value dialog box from a table, click the value in the result
row. You may want to move the dialog box to see the table better. Click on the title
bar and hold down the mouse button as you move the dialog box to a different
position.

The types of actions that you can perform include:

• Erase all parameters in the current table (Clear current values).


• Copy the current table to another table with or without its parameter values
(Copy with values or Clear current values).
• Close current table and open another table that already exists (Load new table).

Procedures for each of these actions follow.

Erase all parameters


in the current table
• Do not change the table selection in the New Value field

• Select Clear current values, then click OK.

RESULT: Software asks first whether or not you really want to clear values. If
you click OK, software erases all parameters from all rows. For
example, if the following table was on display:

And you selected Clear current values, the dialog box closes and the table
redisplays as follows:

NOTE: If you do not change the table selection, the Copy with values and Load
new table options just close the dialog box and redisplay the current table.

Copy the current table


to another table
• To copy a table to another table, display the table you want to copy.

• Click the result row value to display the Function value dialog box.

• Select the table that you want to receive a copy of the displayed table.

Select Clear current values to copy the current table WITHOUT its values.
Select Copy with values to copy the current table WITH its values.
(If you select Load new table, software simply closes the current table and displays
the selected table.)

• Click OK.

275 EN2Z-0937GE51 R05118


SWITCHING LOGIC CARE

RESULT: Software first asks whether you want to clear or replace, as


appropriate. If you click OK, software copies as directed and
displays the changed table.

For example, if there were two tables representing values 100.0 and 50.0 (as
follows):

And you decided to copy the 100.0 table over the 50.0 table and keep the values
from the 100.0 table, the following table would display:

If you decided to copy over the 50.0 table WITHOUT the values in the 100.0 table,
the following table would display:

Close current table and


open another table
that already exists • Select a table number in the Existing values box.

• Select Load new table.

• Click OK.

RESULT: Software closes the current table and displays the selected table. If
you made changes to the current table, software asks first whether
or not it should save the changes before it closes it.

Damper/Fire Example The following example controls a damper with multiple tables (opposite states in
each table) to ensure action for a priority situation such as a fire.

EN2Z-0937GE51 R0518 276


CARE SWITCHING LOGIC

OFF and ON Tables If there are two tables for a point, one OFF and one ON, but no control strategy, the
ON table has priority and turns the point both ON and OFF. Therefore the OFF table
is unnecessary.

If there is a control strategy but no ON table (only an OFF table), the control
strategy operates the point unless the OFF table is triggered. Then, switching logic
turns the point off. Switching logic always takes precedence.

If there is only an OFF table (no ON table or control strategy), there is nothing to
turn the point back on after the OFF table turns it off.

Row Deletion
Purpose Eliminate an unnecessary row (other than the result row).

Procedure 1. Click the -ROW icon in the list down the right-hand side of the window.

RESULT: The switching table function turns red.

2. Select the input condition (row) to be deleted from the switching table.

RESULT: Software removes the input condition from the switching table. For
a digital input condition, the switching table becomes one row
shorter. For an analog input condition, it becomes two rows shorter.

To Cancel Without Deleting To cancel without deleting the row, click the -ROW icon with the right-hand mouse
button.

Restriction You cannot delete the result row with this function. Use menu item File, drop-down
item Delete, to erase the entire switching table.

Result Row

Purpose The result row specifies the output that software should command when table
conditions are true. It can also specify a time delay for a digital commands. The
result row is always the first row in a table.

Example For example, the following line says to turn the Supply_Fan point on after a
minimum delay of 30 seconds:

Point Type The point must be an output point, pseudopoint, or flag. For digital outputs, the
desired result can be either zero or one. For analog outputs, the result is a value.
For example, the following line says to open a damper to 100 percent:

Row Changes The following sections explain how to change the output command for the point
(digital or analog value) and how to set delay time.

Command Changes

277 EN2Z-0937GE51 R05118


SWITCHING LOGIC CARE

Purpose Modify the resulting command software sends to the selected point.

Digital Points Click the command in the row to change its value.
For example, the 1 in the following row is the click area to change the command
output for the table:

Whenever you click a command, it changes. For example, a two-position point


changes between 1 and 0. A multi-stage point can have seven states, so the
command can change from 0 to 1 to 2 to 3 to 4 to 5 to 6.

The command numbers (0, 1, etc) refer to the digital engineering unit table (see
Appendix B: Engineering Units, Digital section). For example, the first digital
engineering unit table entry assigns ON to 1 and OFF to 0. Therefore, a switching
table command to 1 in this example is an ON command and a command to 0 is an
OFF command.

This action assumes the Active State flag for the point is enabled. See the Editors
chapter, Point Attributes Dialog Boxes, for more details on the Active State attribute.

Analog Points 1. Click the command value.

RESULT: The background in the value box turns blue.

2. Type a new value.

RESULT: The new value displays in the box.

Analog Command Tip Actual analog output commands depend on point characteristics. The following
example illustrates this function.

Ana_out_1 I/O characteristics are:

2V = 0 percent
10V = 100 percent

If no other controls are acting on the Ana_out_1 point (for example, control strategy
or other switching logic), the following actions occur:

• If the condition is true, software commands Ana_out_1 to 50.0 (actual command


6V).

• If the condition is false, software commands Ana_out_1 to the lower value of the
point’s engineering unit range, 0 (2V).

If the point’s I/O characteristic were reversed:

2V = 100 percent
10V = 0 percent

Software would still command the point to 0 when the condition is false, but the
actual command would be 10V.

EN2Z-0937GE51 R0518 278


CARE SWITCHING LOGIC

As a further example, if the point’s I/O characteristic were 20 to 80 percent (4V to


7V), software would command the point to 20 (4V) when the condition is false.

Delay Command to a Digital Output Point


Purpose Add a delay for a digital command result in a switching table. For example, if a
switching table commands a supply fan on when conditions are met, you can add a
delay of 30 seconds before software actually issues the command.

This function only applies to digital outputs.

Procedure 1. Click the rectangle in the second column of the result row in the switching
table (top row). For example:

RESULT: The Select Time Period dialog box displays.

2. Type a number for the desired period of time in the Value box. Press Tab to go
to the Type box.

3. Click desired type of delay:


On delay—Minimum time (Te in table) that software should add a delay to a
start command.
Off delay—Minimum time (Ta in table) that software should add a delay to a
stop command.
Cyclic—Cycle time (Tv in table) tells software to alternate ON and OFF times.

4. Press Tab to go to the Unit box. Click desired unit of time (Seconds, Minutes,
or Hours).

5. Click OK to save changes and close dialog box. Or, to close the dialog box
without saving changes, click Cancel.

RESULT: The selected timer value with its value and unit displays. For
example, if you selected 30-second On delay:

To Delete Timer Value 1. Click the timer value to be deleted (in this example, Te=30s).

RESULT: The Select Time Period dialog box displays.

279 EN2Z-0937GE51 R05118


SWITCHING LOGIC CARE

2. Enter 0 (zero) in the Value field.

3. Click OK.

RESULT: Software deletes the selected timer value from the row.

See Also ⇒ Digital Condition Rows, Delay for a Row Condition subsection, for procedure to add
timer delays to digital conditions

Delay for a Logical AND (Column Delay) section for a procedure to add a delay time
to an AND Column

Switching Table Description, Time Delays subsection, for a summary of optional


delay actions.

Digital Condition Rows


Purpose Specify required digital conditions to implement the desired output result.

For example, the following table says to turn on the return air fan if the supply air
fan is on:

Row Changes The following sections explain how to set delay time and how to change the True or
False status for the row.

Delay for a Row Condition


Purpose Require a condition to be true for a minimum amount of time before software
changes its status to true. For example, a supply fan must be on for at least 30
seconds before software can change its status to true.

Procedure 1. Click the rectangle in the second column of the input condition. For example:

RESULT: The Select Time Period dialog box displays..

EN2Z-0937GE51 R0518 280


CARE SWITCHING LOGIC

2. Type a number for the desired period of time in the Value box. Press Tab to go
to the Type box.
3. Click desired type of delay:

On delay—Minimum time (Te in table) that a condition must be on before


software should change its status to true.
Off delay—Minimum time (Ta in table) that a condition must be off before
software should change its status to true.
Cyclic—Cycle time (Tv in table) tells software to alternate ON and OFF times.

4. Press Tab to go to the Unit box. Click desired unit of time (Seconds, Minutes,
or Hours).

5. Click OK to save changes and close dialog box. Or, to close the dialog box
without saving changes, click Cancel.

RESULT: The selected timer value with its value and unit displays in the
selected field. For example, if you added a 20-second On delay:

Multiple Row Conditions If a switching table has more than one digital condition and you assign delays to
each condition, the lowest delays may be irrelevant. For example, if digital 1 has a
delay of 10 seconds and digital 2 has a delay of 15 seconds, software cannot mark
the column as true for at least 15 seconds (the longest time) since all conditions
must be true (AND logic) for software to mark the column as true.
If a switching table has more than one digital condition plus OR columns, multiple
delay times may still be useful since an OR column needs only one condition to be
true.

Cycle Timer Cyclic timers have priority over Control Strategy loops only during the active
condition of their cycle. For example, the following figure shows a digital output
point, RaFan, being commanded by a switching table that is controlled by the staus
of a digital input called SaFanStatus. The RaFan point is also controlled by an EOV
operator in a Control Strategy loop.
.

281 EN2Z-0937GE51 R05118


SWITCHING LOGIC CARE

RaFan SaFanStatus

RaFan Tv =2s 1
SaFanStatus 1

Y D1
EOV

Scenario 1: SaFanStatus is true; EOV output is false.

RaFan turns on for 2 sec and then releases priority. This action has the effect of
turning the point off (standard switching table logic).

Scenario 2: SaFanStatus is true; EOV output is true.

RaFan stays on continuously because switching logic turns the output on for 2 sec
and then releases priority to the EOV, which wants the point on. Therefore, it looks
like the output is no longer cycling.

To Delete Timer Value 1. Click the timer value to be deleted in the switching table. In the previous
example, Te=20s.

RESULT: The Select Time Period dialog box displays.

2. Enter 0 (zero) in the Value field.

3. Click OK.

RESULT: Software deletes the selected timer value.

True or False Changes


Purpose Modify the required status for the point. This status determines how software ANDs
the rows.

For example, in the following table, if the supply fan status point
(STATUS_FAN_SUP) is on (1) AND the supply fan command point
(SUP_FAN_CMD) is on (1), software calculates a True value for the table. If either
point is off, software calculates a False value for the table.

If you change the required status for one of the points, software calculates the
True/False value differently. For example:

Now software calculates a True value only if the supply fan status point is off and
the supply fan command point is on.

EN2Z-0937GE51 R0518 282


CARE SWITCHING LOGIC

Procedure Click the status in the row to change it to another value. True is 1; False is 0; Not
applicable is -.

For example, if the following row were in a table and you clicked 1, the command
would change to 0. If you clicked again, it would change to -. Each time you clicked
it, it would change.

Analog Condition Rows


Purpose Specify required analog conditions to implement the desired output result.

Description Each analog condition requires two rows. The first row specifies user address and
comparison type (for example, greater than or equal to). The second row specifies
comparison value and deadband differential. Switching status is in the last column
and applies to both rows.

For example, the following table says to turn on the return air fan if the supply fan
has been on for 30 seconds AND the discharge air temperature is greater than or
equal to 68F (20C). The DISCH_AIR_TEMP row is the analog condition:

The 3.0 value in the last row, second column, creates a deadband of 3 degrees with
the 68.0 value to keep the return fan from short cycling due to small changes in
temperature. In other words, the temperature has to fall at least to 65 (68 minus 3)
to invalidate the condition.

Row Changes The following sections explain how to set comparison type (>=), comparison value,
and deadband value, and how to change the True or False status for the row.

Comparison Type
Purpose Select a less than or greater than comparison for the analog point.

Procedure Click the comparison symbol to change it to the other symbol. Only two are
available, >= (greater than or equal to) and <= (less than or equal to).

283 EN2Z-0937GE51 R05118


SWITCHING LOGIC CARE

RESULT: The symbol changes to the other symbol. Each click changes the
symbol back and forth.

Comparison Value
Purpose Select a point or enter a value for software to compare with the analog control point.

Procedure 1. Click the comparison value box. Initially, the box always shows 0. For example:

RESULT: The background in the box turns light blue.

2. Select a physical analog point or a pseudopoint, or enter a value, or enter a


mathematical formula using one of the following methods:

• To enter a value (for example, 68.0), type the value.

The value appears in the box and the blue disappears.

• To select a physical analog point, click the point arrow head on the physical
point bar.

The user address for the point appears in the box and the blue disappears.

NOTE: If you select an incompatible point (for example, a digital), nothing


happens.

• To select an existing* pseudopoint or flag, click menu item Software points,


then click desired type. A dialog box displays with a list of available points.
Select the desired point/flag from the list. Click OK to close the dialog box.

*To create a new pseudopoint or flag, use the procedure in the Pseudopoints
section, then you can select it.

The user address for the point appears in the box and the blue disappears.

• To use a mathematical formula for multiple analog points, select the MATH
icon. The Mathematical Editor window displays. Enter the required formula.
See Excel CARE Control Icons User Guide 74-5577 (US) / EN2B-0184
(Europe) for details on MATH operation. The formula name displays in the
comparison value field.

EN2Z-0937GE51 R0518 284


CARE SWITCHING LOGIC

Deadband (or Hysteresis) Value


Purpose Enter a value that creates a range for the comparison value.

For example, in the following table, discharge air temperature is compared to the
value 68.0. There is also a deadband (or hysteresis) of 3.0. The deadband value
tells software to mark this condition as true as long as discharge air temperature is
between 65 and 68. If discharge air temperature falls below 65, software invalidates
the condition. Using a deadband prevents frequent command changes.

As another example, you can control a fan based on a temperature as follows:

The following operation occurs:

If you reverse the TEMP_1 >= sign to <=:

285 EN2Z-0937GE51 R05118


SWITCHING LOGIC CARE

The following operation occurs:

Procedure 1. Click the deadband box.

RESULT: The background in the box turns light blue.

2. Select a physical analog point or a pseudopoint, or enter a value, or enter a


mathematical formula using one of the following methods:

• To enter a value (for example, 3.0), type the value.

The value appears in the box and the blue disappears.

• To select a physical analog point, click the point arrow head on the physical
point bar.

The user address for the point appears in the box and the blue disappears.

NOTE: If you select an incompatible point (for example, a digital), nothing


happens.

• To select an existing* pseudopoint or flag, click menu item Software points,


then click desired type. A dialog box displays with a list of available points.
Select the desired point/flag from the list. Click OK to close the dialog box.

*To create a new pseudopoint or flag, use the procedure in the Pseudopoints
section, then you can select it.

The user address for the point appears in the box and the blue disappears.

• To use a mathematical formula for multiple analog points, select the MATH
icon. The Mathematical Editor window displays. Enter the required formula.
See Excel CARE Control Icons User Guide 74-5577 (US) / EN2B-0184
(Europe) for details on MATH operation. The formula name displays in the
deadband field.

True or False Changes


Purpose Modify the required status for the point. This status determines how software ANDs
the rows.

For example, in the following table, if the supply fan status point
(STATUS_FAN_SUP) is on (1) AND discharge air temperature
(DISCH_AIR_TEMP) is greater than or equal to 65 (1), software calculates a True
value for the table. If the status point is off or discharge air temperature is below 65,
software calculates a False value for the table.

EN2Z-0937GE51 R0518 286


CARE SWITCHING LOGIC

If you change the required status for one of the points, software calculates the
True/False value differently. For example:

Now software calculates a True value only if the supply fan status point is off and
discharge air temperature is greater than or equal to 65.

Procedure Click the status in the row to change it to another value. True is 1; False is 0; Not
applicable is -.

For example, if the following row were in a table and you clicked 1, the command
would change to 0:

If you clicked again, it would change to -. Each time you clicked it, it would change.

MATH Rows
Purpose Create a calculated value to replace a variable in a switching table.

Procedure 1. To replace an existing variable in a switching table, click the variable


name/value to highlight it. Then, click the MATH icon in the Tool Bar to display
the Math Editor window.
To create an analog row in a switching table so that you have a variable to
replace with a calculated value, either create an analog pseudopoint or flag (via
the Software points menu item) or click a physical point in the schematic.

NOTE: After you create a math calculation for a variable, software replaces
the point/pseudopoint name with the name of the math variable.
Therefore, if you used a pseudopoint/flag, you can delete it during the
attach process since it is no longer needed. If you used a physical
point, no further action is required.

For example, the following switching table shows three variables, t1, 0, and 0.
The t1 variable can be a physical point or an analog pseudopoint or flag
defined via the Software points menu item. The zero values automatically
display when you create a pseudopoint/flag or click a physical point in a
schematic. You can highlight the zero values and click the MATH icon to create
calculated values for them, also.

do 1

t1 >=
1
0 0

RESULT: The Math Editor dialog box displays.

287 EN2Z-0937GE51 R05118


SWITCHING LOGIC CARE

TIP: You can also display the Math Editor dialog box by double-
clicking a formula.

2. Click New Variable to enter a new formula name or select an existing formula
from the box below New Variable. Click the down arrow in the box to display a
list of available variable names. Click one to select it. Its formula displays in the
box next to it.

You can now start selecting points from the hardware point triangles or
Software points menu, and mathematical functions or values from the
calculator pad. See Excel CARE Control Icons User Guide 74-5577 (US) /
EN2B-0184 (Europe) for MATH Control Icon details.

Example:

3. Click OK.

RESULT: The window closes and the switching table redisplays with the
math variable name instead of the original variable name (for
example, t1 or zero).

Delay for a Logical AND (Column Delay)


Purpose Add a delay for a column in a switching table. For example, if a switching table
commands a supply fan on when conditions are met, you can add a delay of 30
seconds before software actually issues the command.

Procedure 1. Click the +DELAY icon from the icon list in the right-hand column.

RESULT: Software adds a row for the timer value to the bottom of the
switching table.

EN2Z-0937GE51 R0518 288


CARE SWITCHING LOGIC

NOTE: If you insert more entries into the switching table later, software adds
them above the timer value entry.

2. Click the box below the column where you want to add a delay. For example:

RESULT: The Select time period dialog displays.

3. Type a number for the desired period of time in the Value box. Press Tab to go
to the Type box.

4. Click desired type of delay:

On delay—Minimum time (Te in table) that all column conditions must be true
before software should add the delay time to the switching table output ON
command.
Off delay—Minimum time (Ta in table) that all column conditions must be true
before software should add the delay time to the switching table output OFF
command.
Cyclic—Cycle time (Tv in table) tells software to alternate ON and OFF times.

5. Press Tab to go to the Unit box. Click desired unit of time (Seconds, Minutes,
or Hours).

6. Click OK to save changes and close dialog box. Or, to close the dialog box
without saving changes, click Cancel.

RESULT: The selected timer value with its value and unit displays in the
selected field.

To Delete Result Delay The -DELAY function is available only after you define a delay via the +DELAY
function.

• Click the -DELAY icon from the list down the right-hand window column.

Software removes the last row containing delay time.

OR Columns and Exclusive OR Columns


Purpose The OR function tells software to command a point when at least one of the
conditions in the switching table is true.

289 EN2Z-0937GE51 R05118


SWITCHING LOGIC CARE

For example, the following table says to command the supply fan on if there is a
manual override command (for example, from an operator), or Time program 1
commands it on, or the low limit sensor for frost is less than or equal to 2 (with a
deadband of 1):

Limits Each table can have a maximum of 10 OR columns and a maximum of eight rows.

Procedure 1. Click the +COL icon in the list down the right-hand window border.

RESULT: Software adds a new OR column to the right-hand edge of the


switching table.

2. Click the statuses in the columns to create the appropriate true (1), false (0),
and not applicable (-) statuses. Each click changes the status (0 to 1 to - and
back to 0).

To Remove a Column 1. Click the -COL icon in the list down the right-hand window border.

RESULT: The switching table function turns red.


2. Click the OR column that you want to delete.

RESULT: Software removes the column from the switching table.

Tip ⇒ To cancel a deletion, click the -COL icon again with the left-hand
mouse button.

Exclusive OR Tables
Purpose An Exclusive OR table only allows one true condition in a switching table with OR
columns.

A switching table must already have OR columns before you can define an
Exclusive OR table.

For example, if you have a switching table with the following OR columns:

You can click XOR to create the following table:

This table tells software to turn Dig_out on if ONLY ONE of the three conditions is
true. If any two are true, the table is false.

EN2Z-0937GE51 R0518 290


CARE SWITCHING LOGIC

Limits Each table can have a maximum of 10 XOR columns.

Procedure 1. Click the XOR icon in the list down the right-hand window border.

RESULT: The normal switching table disappears and the Exclusive OR table
appears.

2. You can modify the table:

• To change the True/False values, click any of the 0’s and 1’s. Each click
changes it to the opposite (0 to 1, 1 to 0).
• To insert a line in the table, click the +XOR icon in the list in the right-hand
window border.
• Software adds the new line to the end of the Exclusive Or table. All entries
are preassigned as zero.
• To delete a line from the table, click the -XOR icon in the right-hand window
border. The icon turns red.
• Click the line to be deleted in the Exclusive Or table. Software deletes the
line.
• To cancel deletion, click the -XOR icon again using the left-hand mouse
button.

Restriction You cannot delete the Exclusive Or table header (first row).

+XOR and -XORFunctions To use these functions after you establish an Exclusive OR table, redisplay the
table by clicking XOR. You can then select a function.
XOR Table Changes There is no indication in a switching table if there is an XOR table assigned to it.
The only way to know is to click the XOR button to see if a table appears.

If you change a switching table that has an Exclusive OR table assigned to it, the
resulting table action may not be acceptable. Always check whether there is a table
and then adjust the table to achieve the desired result.

For example, you can make changes to the following switching table and even
though it has an Exclusive OR table assigned, software does not warn you.

XOR table:

If you added an analog line as follows:

Software will AND the analog condition with the di_1 condition before doing the
Exclusive or.

291 EN2Z-0937GE51 R05118


SWITCHING LOGIC CARE

Pseudopoints
Definition A pseudopoint is a calculated value; it has no physical basis in the system. It
contains a process or control variable required by the switching logic or control
strategy. The controller calculates the value while the program is running.

Procedure 1. Click menu item Software points.

RESULT: The pseudopoint types list displays. Types include:

• Pseudo analog (VA)


• Pseudo digital (VD)
• Pseudo totalizer (VT)
• Global analog (GA)—see Globals note.
• Global digital (GD)—see Globals note.
• Flag analog (FA)
• Flag digital (FD)

2. Click required pseudopoint type.

RESULT: The Create/Select Software Point dialog box displays.

3. To create a new pseudopoint, type a new name in the New editing field. New
names cannot already exist. Click OK.

RESULT: The name of the newly created pseudopoint appears in the list box.

4. To select an existing pseudopoint (or your new one) for inclusion into the
currently displayed table, double-click its name. (Or, single-click the name and
then click OK.)

RESULT: Row(s) for the pseudopoint appear at the bottom of the switching
table. One row appears for digitals; two rows for analogs.

5. To end the pseudopoint function and close the dialog box, click Cancel.

NState Pseudo digital (VD) points have two subtype choices, 2State and NState. Select the
NState if the point has more than two states, for example, OFF, ON, Open, Close,
etc.

Globals When you create a global, you must match user address and type (analog or
digital) with the associated pseudopoint or physical point. The Pseudopoints and
Flags subsection in the Control Strategy chapter of this manual describes global
points in detail.

Control Strategy Tip If you save the switching table to a pseudopoint, you can also use the pseudopoint
in the Control strategy for the plant. For example, if you set up a switching table for
an analog pseudopoint so that software commands it to 50 under certain conditions,
you can then use the pseudopoint in the control strategy as an input to a function
for switching purposes.

EN2Z-0937GE51 R0518 292


CARE SWITCHING LOGIC

Switching table:

Control strategy:

Switch_pseudopt acts as an input switch to the control icon.

Switching Logic File Management


Purpose Save, load, delete, and restore switching tables. The File menu item provides drop-
down items for these functions:

• Save a Switching Table


• Copy a Switching Table to Another Point
• Load a Switching Table
• Delete a Switching Table
• Restore a Switching Table
• Start a New Switching Table

Save a Switching Table


Purpose Save the currently displayed switching table.

Procedure 1. Click File, then drop-down item Save.

RESULT: The Acknowledge dialog box displays.

2. Click OK.

RESULT: The arrow head associated with the output point is cross-hatched
in white.

Macro Option You can also save switching tables in the Macro library for later use in other
systems. See the Macros section for details.

Copy a Switching Table to Another Point


Purpose Copy the switching table and assign it to another point (physical or pseudo).

NOTE: The type of point (analog or digital, input or output) you select for
reassignment must be compatible with the type of point for which the
switching table was created.

Procedure to save
to a pseudopoint 1. Click File, then drop-down item Copy.

RESULT: Software highlights the switching table.

293 EN2Z-0937GE51 R05118


SWITCHING LOGIC CARE

2. Click menu item Software points.

RESULT: The list of pseudopoint types displays.

3. Select the required pseudopoint type .

NOTE: The type of point to which the switching table is assigned must be
compatible with the type of point for which the switching table was
created.

RESULT: The Software points dialog box displays.

4. Select an existing pseudopoint or create a new one.

NOTE: If you create a new point, you must also assign it a place on the
software bar in the Control strategy. See Control Strategy,
Pseudopoints and Flags section, for procedure. You can assign the
point after you complete the switching logic.

5. Click OK to assign the point.

RESULT: The Acknowledge dialog box displays, confirming the switching


table has been successfully saved. The switching table is no longer
highlighted.

NOTE: If the switching table is still highlighted, you selected an incompatible


point type. Select a compatible point.

6. Click OK.

7. Click Cancel.

Tip ⇒ To cancel the storage of the switching table before you finish, click
Cancel instead of OK in Step D. After the dialog box closes, click
the right-hand mouse button once. Software removes the
highlighting from the table.

Procedure to save
to a physical point 1. Click File, then drop-down item Copy.

RESULT: Software highlights the switching table.

2. Select the desired physical point from the plant schematic .

NOTE: The type of point you select must be compatible with the type of point
for which the switching table was created.

RESULT: The Acknowledge dialog box displays confirming successful


storage.

3. Click OK.

RESULT: Software removes the highlighting from the switching table. The
physical point symbol is cross-hatched in white.

Control Strategy Tip If you save the switching table to a pseudopoint, it is available in the Control
strategy for the plant.

Load a Switching Table


Purpose Redisplay a previously saved switching table to modify or view it. The outputs for
switching tables that already exist are recognizable by the white cross-hatching on
the physical point bar.

Procedure Click the desired output arrow head in the plant schematic.

EN2Z-0937GE51 R0518 294


CARE SWITCHING LOGIC

If there is only one switching table for the point, it displays.

If there is more than one table for the point, software displays a dialog box that lists
the names of the tables. Click desired table name, then click OK. Software displays
the selected table.

Delete a Switching Table


Purpose Remove an unnecessary switching table.

Procedure When the unnecessary table is on display in the window, click File, then drop-down
item Delete.

Software deletes the switching table.

See the Load a Switching Table section if you do not know how to display a desired
table.

Restore a Switching Table


Purpose Cancel modifications made to currently displayed switching table since it was last
saved.

Procedure Click File, then drop-down item Restore.

The stored version of the switching table displays.

Start a New Switching Table


Purpose End the processing of the current switching table and start a new one.

Procedure 1. Click File, then drop-down item New/Clear.

RESULT: The Note dialog box displays.

2. Click OK to save the current switching table and remove it from display.
Or, to remove it without saving, click Cancel.

3. Select a point to start a new table.

Macros
Purpose Save switching tables in a Macro library with descriptive names for reuse
throughout the system. All macros are available for all plant types.

Save the Switching Table as a Macro


Procedure 1. Click File, then drop-down item Save macro.

RESULT: The Macro name dialog box displays

295 EN2Z-0937GE51 R05118


SWITCHING LOGIC CARE

2. Click the Name editing field.

3. Enter the name of the macro in the Name editing field.

NOTE: The name may not already exist.

4. Click OK.

RESULT: The Acknowledge dialog box confirms the macro has been saved.

5. Click OK to close the dialog box.

Load a Macro
NOTE: You can only load a macro if no other switching table is currently in the
window. Use menu item File, drop-down item New/Clear to clear the
window.

Procedure 1. Click File, then drop-down item Load Macro.

RESULT: The Load Macro dialog box displays.

2. Select the macro to be copied from the list of existing macros.

3. Click OK.

RESULT: The switching table defined in the macro displays without a point
name in the result row.

4. Click menu item File, then drop-down item Copy.

RESULT: Software highlights the switching table.

5. Click the arrow head for the point you want in the result row, that is, the point
the switching table should control.

RESULT: The Acknowledge dialog box displays with a message that software
copied the switching table.

6. Click OK to close the dialog box.

RESULT: The switching table remains as is on the screen (no point in the
result row). To see the table with the point in the result row, clear
the screen (File, drop-down item New/Clear), then click the arrow
head of the point to display the new table.

7. If you use a macro that was created for a different plant, you must change the
user addresses stored in the macro to match the new plant. Select the user
address to be modified in the switching table.

NOTE: The user addresses included in the macro can be physical as well as
pseudopoints. You can only replace user addresses with compatible
point types. CARE does not accept incompatible types.

EN2Z-0937GE51 R0518 296


CARE SWITCHING LOGIC

RESULT: The selected field turns light blue.

8. Change the address in the same way you would if you were creating a new
switching table. For example:

• To assign a physical point, click the arrow head for the point in the physical
point bar.
• To assign a pseudopoint, click menu item Software points. The pseudopoint
types list displays. Select the required pseudopoint type. The Software
points dialog box displays. Select the required pseudopoint. Click OK, then
click Cancel.
• To assign or modify a mathematical relationship between analog user
addresses, click the MATH icon. The Mathematical Editor window displays.
Enter (or change) the formula. Click OK.

RESULT: The selected point user address displays in the selected field.

9. Make any other changes, as desired. Then, save the switching table as usual
(menu item File, drop-down item Save).

Plant Information Displays

Physical Point Information


Procedure 1. Double-click the physical point about which more information is required.

RESULT: The Data Point Information window displays.

2. Click OK to close dialog box after you finish viewing the information.

RESULT: The dialog box disappears from the screen.

User Addresses
Procedure 1. Click View, then drop-down item Physical user address.

RESULT: The user addresses display under the plant schematic. The initial
letter of the user address is located vertically below the physical
point to which it belongs.

2. To remove user addresses display, click View, then drop-down item Physical
user address again.

RESULT: The user addresses disappear from the screen.

Restriction You cannot select any switching logic functions while the user addresses are on
display.

Single Address Display If you move the cursor over a triangle and press and hold the left-hand mouse
button down, the user address for the point displays with either a red exclamation
symbol or a green check mark symbol. When you release the mouse button, the
display disappears.
The red exclamation symbol appears for:

• hardware points with one allowable connection that are used in an XFM
• digital outputs that are connected to a symbol
• flex points that are connected to a symbol
• software points that are connected to an output pin of a symbol.

297 EN2Z-0937GE51 R05118


SWITCHING LOGIC CARE

Print Switching Tables


For printing switching tables see Print Documentation chapter.

Switching Logic Function Exit


Purpose Return to the main CARE screen.

Procedure 1. Click File, then drop-down item Exit.

RESULT: The Note dialog box displays.

2. Click OK to save the switching table and exit.


Or, to exit without saving, click No.
Or, to remain in the Switching Logic function, click Cancel.

RESULT: The main CARE menu displays.

EN2Z-0937GE51 R0518 298


CARE EDITORS

EDITORS
Purpose CARE includes several Editors which provide the following:

Datapoint Editor
Assign and/or modify attributes to points. Attributes are, for example, texts defined
via Miscellaneous Text Editor (descriptors etc.), user address, technical address,
delay time, LON attribute etc. They depend on the point type.

NOTE: The Datapoint Editor is only available after a plant has been attached to a
controller. The Editors apply to items on a controller basis, not system-
wide.

See Datapoint Editor section.

Miscellaneous Text Editor


Define and/or edit default and custom texts as:

• Point descriptors
• Alarm texts
• Engineering units
• Characteristics
• Multi-state texts

See Miscellaneous Text Editor (CARE XL-5000) section for editing texts of Excel
50/80/100/500/600/800/Smart/ELink/XLink/OLink and OPS controllers.
See Miscellaneous Text Editor (CARE XL-Web) section for editing texts of the Excel
Web controller.

Network Variables (NV) Editor


Create/Edit network variables (NVs) for CARE datapoints. Map datapoints to NVs
and define value conversion tables for controllers.

See Edit Excel 500/800 Network Interface Manually section.

Time Program Editor


Create daily, weekly and yearly time programs (see Time Program Editor section).

Default Text Editor


Customize project defaults for use in a specific area or region (see Default Text
Editor section).

User Address Search Templates Editor


Define general search templates to enable operators using XI581/XI582 Bus-Wide
Operator Interface Terminals to quickly search for a set of user addresses (see User
Address Search Templates Editor section).

OPS Template Editor


Create templates for OPS controllers, consisting of subsystem drivers, subsystem
controllers, and subsystem points (see OPS Controller section).

Point Definitions A point is a variable that contains information about the system and provides control
over system operation. There are two types of points, physical and pseudo:

Physical vs. Pseudo Physical points refer to controller equipment such as sensors and actuators that
sample and modify the environment, for example, space temperature sensors,
heating and cooling valves, and dampers. Pseudopoints refer to calculation results
of software programs.

Point Types Points, called datapoints, can also be input or output as well as analog, digital, or
totalizer:

Input points represent sensors that measure and report conditions in the
environment (for example, temperature, relative humidity, airflow).

Output points represent actuators that perform some function in the environment (for
example, cooling valves, heating valves, dampers, start/stop relays).

299 EN2Z-0937GE51 R0518


EDITORS CARE

Analog points are controller inputs or outputs with a continuous signal characteristic,
that is, a range of values. For example, a thermometer can range from below 0 to
over 100. An analog point can be physical or pseudo, input or output, and/or global.

Digital points are controller inputs or outputs with a discrete signal characteristic,
that is, three or four states. For example, a pump can have two states, ON and OFF,
and a pulsed transducer can have electrical signals that monitor flow. A digital point
can be physical or pseudo, input or output, and/or global.

Totalizer points are controller inputs that process pulsed inputs up to 24V dc, for
example, metered utility consumption. Totalizer points are always input (not output).
A totalizer point can be physical or pseudo. It can also be global.

Globals Global points are a type of pseudopoint that can be either an input or output. The
purpose of global points is to share point information across controllers on a bus.
Global inputs receive information from a point in another controller. Use a global
input when one controller has a point that should be global to many other
controllers.

Global outputs send information to other points in other controllers. Use a global
output when one controller has a point that is global to only one point in another
controller. You can also use global outputs for some control icons that only connect
to outputs and the output must be global. Global outputs can only be associated with
pseudopoints or output points (not input points).

For more details on the operation of global points, see Global Analog Point Editor
Dialog Box later in this section.

Point Addresses The system tracks points via technical addresses that locate and define the point.
Operator's command and display points via user addresses.

User Address Point name (maximum of 18 alphanumeric characters)


assigned to a point for operator use in locating and
commanding the point. Examples: Rmtempfl1 and
FlotempG/fl. This name and the descriptor further define
the point. The name, not the descriptor, must be unique
within a controller.

User addresses must include one non-digit character and


cannot include Tabs, double quotes, ?, *, or space
characters. All other ASCII characters are allowable (A-
Z, 0-9, +, -, _, etc). For example, 12A is a valid user
address, but 12 is not.

Technical
Address Internal six-digit number that defines and locates a point
in the system. The number is composed of three pairs
representing controller number (0-30), module number
(1-16), and terminal number (1-12). Example: 010310
meaning Controller 1, Module 3, terminal 10.

Datapoint Editor
Purpose Define and/or modify attributes for points. Attributes are descriptive information for
points and depend on the type of point. For example, analog points specify high and
low warning and alarm limits, while digital points specify runtime values.

EN2Z-0937GE51 R0518 300


CARE EDITORS

Edit Datapoints
The Datapoint Editor is accessible via logical plant tree.

Procedure 1. In the logical plant tree, click on desired datapoint, you want to edit

RESULT: On the right pane, the Properties tab displays the datapoint
attributes.

2. For getting an introduction in datapoint editing, refer to the Basic Working


Techniques section. To firstly define/modify texts, see the Miscellaneous Text
Editor (CARE XL-5000) and Miscellaneous Text Editor (CARE XL-Web)
sections.

Basic Working Techniques


Tree and Information Display

Hierarchical Tree
In the logical plant tree, the project is available as hierarchical tree with the following
objects:

301 EN2Z-0937GE51 R0518


EDITORS CARE

Project (max. one)

Controller(s)

Plant(s)

Point Types

Single Points

Open and navigate through the tree via common Windows techniques, that is
double-clicking on the icon or the + and - symbols at the object icons.

In the Standard toolbar, the filter on/off icon allows to apply a freely definable
filter.

Information Display
Clicking on the desired object (project, controller, plant, point type, point) in the tree,
displays the corresponding information on the corresponding right-sided tab. The
information of an object can be displayed differently and depends on the selected
display type. You have the following possibilities:

• Itemized Display from within tree


• Grid Display (table)

EN2Z-0937GE51 R0518 302


CARE EDITORS

In the itemized display, you can do the following:

• Display project, controller, and plant information


• Edit attributes of individually selected points
• In addition to the possibility of editing points in itemized display, all points of the
same kind can be displayed and edited in grid display when selecting the
respective point type icon in the tree.

In the grid display you can do the following:

• Display all points of a project, plant, controller, or point type as grid and edit point
attributes in the grid (table).
• Optionally you can display a point in itemized display from within the grid.
• In addition to the possibility of editing all points in grid display, an individual point
is always displayed and can be edited in itemized display when selecting it in the
tree.

Examples:

Project in Itemized Display (Project Information)

303 EN2Z-0937GE51 R0518


EDITORS CARE

Point in Itemized Display (invoked from within tree)

EN2Z-0937GE51 R0518 304


CARE EDITORS

Controller in Grid Display

305 EN2Z-0937GE51 R0518


EDITORS CARE

Point in Itemized Display (invoked from within Grid Display)

The display type is set up by the grid configuration function (see Configure Grid
section).

Configure Grid

Purpose Configuring the grid includes the following:

• Set up kind of display, itemized or grid display


• Select columns to show in grid and number of frozen columns
• Set up zoom factor and filter line display

Procedure 1. Click on menu item Options, then drop-down item Grid Configuration

or,
click Configure Grid button on the toolbar

or,

EN2Z-0937GE51 R0518 306


CARE EDITORS

when in grid display, point cursor over the grid.


Click right mouse button, select Options and click on Grid in the context menu.

RESULT: The Configure Grid dialog box displays.

2. Select desired options under:

Select Columns for Show in Grid


Here you define which attributes for which point types will be displayed in the
columns. It is possible to select attributes to be displayed for all points and
individually for different point types. This provides the display of single attributes
(columns) for all points and to differentiate for which point types the general
selected attributes should be displayed or not.

Point Type
In the drop-down list select the point type for which you want to define the
attributes that should be displayed. In the attributes list below check the
attributes for the point type in the Show column. Use the default button, if you
want to check all attributes. Use the Clear all button, if you want to uncheck all
attributes.

In the grid, fields will be grayed and disabled for point types which have not the
attribute at all and/or have not checked the attribute for show in the grid.

Options: All (has priority), Analog Input etc.

The settings made for the All (has priority) option are valid for all points and
have priority over the settings made for individual point types. But attributes
checked for the All (has priority) option will only be displayed as columns, if the
same attributes are checked for minimum one point type.

Example:

If the characteristic is checked for the All (has priority) option and is not checked
for the Analog Input point type and Analog Output point type, the Characteristic
column will not be displayed. Vice versa the same is true, that is, even if the
characteristic is checked for the analog input and output point types, and for All
(has priority) the characteristic is not checked, the Characteristic column will not
be displayed.

307 EN2Z-0937GE51 R0518


EDITORS CARE

All (has priority) Characteristic checked All (has priority) Characteristic checked
Analog Input Characteristic checked Analog Input Characteristic checked
Analog Output Characteristic checked Analog Output Characteristic not checked

Points without
the Characteristic
attribute

Number of frozen Columns


In the drop-down list, select the number of frozen columns. These columns
remain and will always be displayed when you horizontally scroll in the grid. The
max. are 4 columns, but you also can select no columns to be frozen.

Zoom Factor
Select the zoom factor within the range of 60 through 135 %.

Default
To check all attributes for display in the grid, click this button.

Clear all
To uncheck all attributes, click this button. No attributes will be displayed in the
grid.

Font
To select a different font for the grid display, click this button and select desired
font in the Fonts dialog box

EN2Z-0937GE51 R0518 308


CARE EDITORS

Filterline in Grid
To display the filterline in the grid, check this option. To hide the filterline,
uncheck this option (see Use Filterline in Grid chapter).

3. Click OK to save settings.

4. Click on desired object (project, controller, plant, point type, point) in the tree.
The display is updated.

Edit Points in Grid Display

The grid displays all points of the project sorted in rows with their attributes ordered
in columns.

On the left point abbreviations bar the points are displayed by the following
abbreviations:

AI Analog Input
AO Analog Output
DI Digital Input
DO Digital Output
FA Flag Analog
FO Flag Digital
FF Flex DO_Feedback_DI
FM Flex Multistage
FP Flex Pulse2
GA Gobal Analog
GD2 Gobal Digital 2state
GDn Gobal Digital Nstate
PA Pseudo Analog

309 EN2Z-0937GE51 R0518


EDITORS CARE

PD2 Pseudo Digital 2state


PDn Pseudo Digital Nstate
PT Pseudo Totalizer
TO Totalizer

Change rows and column width

Point cursor between two row/column titles till the cursor turns into the divider
symbol. Change size as desired

Freeze columns

Click on menu item Options, then drop-down item Grid… to display the Configure
Grid dialog box.

Under Number of frozen columns select the number of columns you want always to
be displayed while scrolling horizontally within the grid.

Click OK.

Sort columns

You can sort certain columns alphabetically in ascending ( A to Z) or descending (Z


to A) order.

Double-click the column you want to sort. This affects the order of all other columns.

Edit fields
Formats
Disabled fields are grayed in all or their text is grayed. Negative values are red-
marked. Shared points are blue-marked. The thousand digit is displayed with a dot,
the hundred digit with a comma.

Field types
There are two different field types you can meet while working in the grid, the simple
fields, and the dynamic fields.

Simple fields
Simple fields do not show a down arrow. They typically display numeric values.
After pointing over the field a few seconds a yellow tool tip displays the range
the attribute value in the field can have, and the engineering unit. For example,
the tool tip below displays the min. and max. value for the High Warning Limit.

Locate the point in the point abbreviations bar.

Point a few seconds over the field in the row.

Click into the field and enter the value within the range displayed in the tool tip.

Click outside the field or press ENTER key to confirm.

NOTE: You cannot enter values outside the range.

Dynamic fields
At first glance dynamic fields look like simple fields.

EN2Z-0937GE51 R0518 310


CARE EDITORS

But after clicking them they get the behavior and look of a drop-down list. That
is, they get a down-arrow on the right side to display a drop-down list for
selecting an option. The list shows a detailed column wise description of the
choices for the attribute (e. g. ID, Unit, Format for the Engineering Unit field).

Click

After selecting an option the down arrow is still displayed.

After quitting the field, the down arrow disappears.

Select Options

Drop-down lists
To select an option from a drop-down list, click on the down arrow at the field and
select option from the list.

311 EN2Z-0937GE51 R0518


EDITORS CARE

Check boxes
To select an option via check boxes, click on the check box at the desired option.

Change of Engineering Units´ Format

The analog and digital engineering units´ format is displayed in a tool tip when
pointing over the field.

In case of changing the format for an engineering unit all corresponding fields
(indicated by the engineering unit next to the field) are updated instantly. According
to this the decimal places will be cut, if the engineering unit currently selected has
less decimal places than the prior selected engineering unit..

IMPORTANT
When changing an engineering unit of the same kind, for example, hrs into
min a conversion of the absolute values in the respective fields does not
take place. Change the absolute value.

Change of Characteristics

In case of changing a characteristic, either by selecting another characteristic or by


changing the reference values via Miscellaneous Text Editor, the high and low alarm
and warning limits will be updated due to that change.

IMPORTANT
Change values of the previous, but currently displayed limits, if they are not
within the range of the new and updated limits, caused by the change of
the characteristics.

Define and Edit texts

Texts are engineering units, descriptors, alarm texts, and characteristics and they
can be defined and edited in the Miscellaneous Text Editor.

Select controller in the logical plant tree.

Position mouse cursor over the grid.

Click right mouse button, and then MiscEdit in the context menu.

EN2Z-0937GE51 R0518 312


CARE EDITORS

or,

click on menu item Options, then drop-down item Edit Text, and desired text
(Analog. Eng. Units, etc.)

The Miscellaneous Text Editor dialog box displays.

For detailed description of the Miscellaneous Text Editor functions, please refer to
the Miscellaneous Text Editor section.

Save Changes

When working in the grid display, changes you have made, are automatically saved
without the need to confirm the changes.

MPORTANT
When closing the project or the Datapoint Editor, software asks if you want
to save or discard the last changes that have been done in the current grid
display. Note that even if you discard changes, points that were changed in
descriptors, alarm texts, engineering units, or I/O characteristics will be
saved anyway.

313 EN2Z-0937GE51 R0518


EDITORS CARE

Edit Points in Itemized Display from within Tree

Click on the point in the tree to display point attributes in itemized display. You exit
the dialog by selecting another object in the tree.

Edit fields
Formats
Disabled fields are grayed in all or their text is grayed. Negative values are red-
marked. The thousand digit is displayed with a dot, the hundred digit with a comma.

EN2Z-0937GE51 R0518 314


CARE EDITORS

Field types
There are two different field types you can meet while working in the itemized
display, the simple fields, and the dynamic fields..

Simple fields
Simple fields do not show a down arrow. They typically display numeric values.
After pointing over the field a few seconds a yellow tool tip displays the range
the attribute value in the field can have. For example, the tool tip below displays
the min. and max. value for the Sensor Offset. The meaning of +038 is
exponent superscript 38.

Locate the point in the point abbreviations bar.


Point a few seconds over the field in the row.

Click into the field and enter the value within the range displayed in the tool tip.

Click outside the field or press ENTER key to confirm.

NOTE: You cannot enter values outside the range.

Dynamic fields
At first glance dynamic fields look like simple fields.

But after clicking them they get the behavior and look of a drop-down list. That
is, they get a down-arrow on the right side to display a drop-down list for
selecting an option. The list shows a detailed column wise description of the
choices for the attribute (e. g. ID, unit, format for the Engineering Unit field).

After selecting an option the down arrow is still displayed.

After quitting the field, the down arrow disappears.

315 EN2Z-0937GE51 R0518


EDITORS CARE

Select Options

Drop-down lists
To select an option from a drop-down list, click on the down arrow at the field and
select option from the list.

Check boxes
To select an option via check, click on the check box at the desired option.

Radio buttons
To select an option via radio button, click on the radio button at the desired option.

Define and Edit texts

Texts are engineering units, descriptors, alarm texts, and characteristics and they
can be defined and edited in the Miscellaneous Text Editor.

Click on the datapoint in the tree.


On the Properties tab on the right, click dotted button in the Misc. Text Editor
area to open the Miscellaneous Text Editor dialog box.

EN2Z-0937GE51 R0518 316


CARE EDITORS

For detailed description of the Miscellaneous Text Editor functions, please refer to
the Miscellaneous Text Editor section.

Change of Engineering Units´ Format

The analog and digital engineering units´ format is displayed in a tool tip when
pointing over the field.
In case of changing the format for an engineering unit all corresponding fields
(indicated by the engineering unit next to the field) are updated instantly. According
to this the decimal places will be cut, if the engineering unit currently selected has
less decimal places than the prior selected engineering unit.

IMPORTANT
When changing an engineering unit of the same kind, for example, hrs into
min a conversion of the absolute values in the respective fields does not
take place. Change the absolute value.

Change of Characteristics

In case of changing a characteristic, either by selecting another characteristic or by


changing the reference values via Miscellaneous Text Editor, the high and low alarm
and warning limits will be updated due to that change.

IMPORTANT
Change values of the previous, but currently displayed limits, if they are not
within the range of the new and updated limits, caused by the change of
the characteristics.

Save Changes

When working in the itemized display from within the tree, changes you have made
are automatically saved without the need to confirm the changes.

IMPORTANT
When closing the project or the Datapoint Editor, software asks, if you want
to save or discard the last changes that have been done to the current
point displayed. Note that all changes that have been done to points prior
to the current point are already saved and cannot be discarded.

317 EN2Z-0937GE51 R0518


EDITORS CARE

Edit Points in Itemized Display from within Grid

Purpose Additional feature to edit a point in itemized display, when working in Grid display. .

Procedure 1. In the grid, double-click on the point in the point abbreviations bar.

RESULT: The corresponding dialog box is displayed showing all attributes


like in itemized display. In opposite to the Itemized display,
where changes are automatically saved, you must confirm your
changes by clicking OK.

Double-Click

EN2Z-0937GE51 R0518 318


CARE EDITORS

2. Edit the values as described in the Edit Point in Itemized Display section.

3. Confirm your actions by clicking OK.

Expand and Collapse the Tree

Purpose Quickly expanding or collapsing the tree.

Procedure Expanding/collapsing the whole tree

When expanding the whole tree every hierarchical level is displayed. When
collapsing the whole tree only the project name is visible.

1. Click any object in the tree (project, controller, etc.)

2. Click menu item Edit, then drop-down item Tree expand all or, click Tree
expand all icon on the toolbar, if you want to see all hierarchical levels of
the tree.

or,
click menu item Edit, then drop-down item Tree collapse all or, click Tree
collapse all icon on the toolbar, if you want to see only the project name in
the tree.

Procedure Expanding/collapsing parts of the tree

When expanding/collapsing parts of the tree every hierarchical level below the
object selected in the tree, is displayed/closed.

1. In the tree, click the object (project, controller, etc.), which hierarchical levels
below should be displayed/closed (not displayed)

2. Click menu item Edit, then drop-down item Tree expand from here or, click Tree
expand from here icon on the toolbar, if you want to see all hierarchical
levels below the object selected in the tree.

or,

Click menu item Edit, then drop-down item Tree collapse from here or, click
Tree collapse from here icon on the toolbar, if you want to close all
hierarchical levels below the object selected in the tree.

Navigate in the Tree

Purpose Navigate in the tree by moving from one object to the next/previous object.

Procedure Starting from the current cursor position in the tree, click on the

Next item icon , if you want to move downwards to the next object in the
tree.
or,
Previous item icon , if you want to move upwards to the previous object in
the tree.

Arrange Windows

Purpose When more than one project is opened, you can arrange the windows to fit your
needs.

319 EN2Z-0937GE51 R0518


EDITORS CARE

Procedure Click menu item Window, then desired drop-down item:

Cascade, if you want to display the windows in a cascade.


or,
Tile Horizontally, if you want to display the windows one below the other.
or,
Tile Vertically, if you want to display the windows side by side.
or,
Arrange Icons, to order the windows, which were closed before and displayed
as icons on the bottom of the screen.

View/Hide Toolbar

Purpose Display/Hide toolbar and/or status bar. The tool bar provides menu functions as
icons. The status bar displays messages of software actions, e.g. creating grid, etc.
Procedure Click menu item View, and then check/uncheck desired drop-down item:

Toolbar, if you want to display/hide the toolbar under the menu bar

and/or,

Status bar, if you want to display/hide the status bar on the bottom.

RESULT: Depending on the previous selection of the menu item (checked or


unchecked), the bar will be displayed or hidden.

EN2Z-0937GE51 R0518 320


CARE EDITORS

Point Descriptions

Point Descriptions
The following describes how to display and modify attributes for the different point
types.

Excel 500/800 Points

Analog Input Point

Purpose Display and/or modify the attributes for a selected analog input point.

Procedure In the tree, click desired point to display current values on the right Properties tab
(itemized display).

or,

in the tree, click on any object (project, controller, plant) which the point belongs to,
and which is in grid display.

To modify values, edit desired values in the fields, and/or select/deselect desired
options.

321 EN2Z-0937GE51 R0518


EDITORS CARE

Modules You can assign “slow” analog input points to slow or fast input modules (XF521and
XFL521 or XF526). You can assign “fast” analog input points only to fast input
modules (XF526) (see Terminal Assignment Tool chapter).

Attributes description User Address Point name (maximum of 18 alphanumeric characters)


assigned to a point for operator use in locating and
commanding the point. Examples: Rmtempfl1 and
FlotempG/fl. The user address and the descriptor further
define the point. This name must be unique within a
controller. User addresses must include one non-digit
character and cannot include Tabs, double quotes, ?, *,
or space characters. All other ASCII characters are
allowable (A-Z, 0-9, +, -, _, etc). For example, 12A is a
valid user address, but 12 is not.

IMPORTANT
Note that the max. length of the user address for Lon
points should not exceed 18 characters (see Lon point
attribute).

Behind the user address field the bus type (IP bus or
LON-bus) where the point resides, is displayed.

Technical Address Internal six-digit number that defines and locates a point
in the system. The technical address is composed of
three pairs representing controller number (0-30),
module number (1-16), and terminal number (1-12).
Example: 010310 meaning Controller 1, Module 3,
terminal 10. Operators use the User Address to refer to
points.

For LON points the module number is 90. When the


number of LON points (terminals) exceeds 99, the
module number will change to 91 and the next LON point
gets number 1.

To change the technical address see the Teminal


Assignment Function chapter.

Controller Name Name of controller where the point is assigned. Display


only. This assignment is done during plant attachment.

Plant Info Plant name

Point Role Point Role created via an external tool like Win EDS. The
point role can be edited.

Point ID Point ID created via an external tool like Win EDS.

Point Subtype Type of point. List of choices depends on input module


type where the point is assigned.

Lon Point Define whether the datapoint should be a LON point.


Select from the list under:

NV-Input
Creates input NV.

NV-Output
Creates output NV.

NV-Input & Output


Creates both, Input and output NV.

Manual Mapping
Provides selection of this datapoint for mapping to NVs in
the NV-Editor.

EN2Z-0937GE51 R0518 322


CARE EDITORS

NV Type Define the NV-type for the LON point. From the Input
and/or Output drop-down lists select desired type.

To edit a LON point, open the NV-Editor by clicking the


dotted button on the right.

VCT Displays whether or not a value conversion table (VCT)


is assigned to the NV-Input Type or NV-Output Type.

Engineering Unit List of choices displays engineering units with ID, unit,
and format.

To add and change units in the list, open the


Miscellaneous Text Editor by clicking the dotted button
on the right (see Miscellaneous Text Editor chapter)

Descriptor Supplemental point information (maximum of 32


characters). Each Excel Controller has a unique set of
descriptors (64 for Ver. 1.2 Controllers; 255 for Ver 1.3
and greater Controllers) that can be assigned to its user
addresses to further describe them. Example: user
address “Rmtempfl1” can have a descriptor of “Heating
circuit, West wing” to help define its location.
List of choices displays descriptors with ID and text.
To add and change descriptors in the list, open the
Miscellaneous Text Editor by clicking the dotted button
on the right (see Miscellaneous Text Editor chapter).

Alarm Text Alarm text that displays on point alarm.

List of choices displays alarm texts with ID and text.


To add and change alarm texts in the list, open the
Miscellaneous Text Editor by clicking the dotted button
on the right (see Miscellaneous Text Editor chapter).

Characteristic Input and output characteristics of the associated sensor.


List of choices displays characteristics with ID and text.

To add and change characteristics in the list, open the


Miscellaneous Text Editor by clicking the dotted button
on the right (see Miscellaneous Text Editor chapter).

Operator Access Level Access level (1 through 4) that an operator must have to
modify point data via an operator terminal. For example,
if a point has an Operator Access Level of 2, only
operators with Access Level 2 and higher can change
point attributes.

Initial. Value Value of the point on inital start-up.

Write Protect Priority Prevent lower-level operators from changing point


attributes that a higher-level operator changed. For
example, if a point has an Access attribute of 2 and an
operator with Access Level 3 changes an attribute,
software restricts future changes to operators with at
least Level 3 access. Write protection prevents any Level
1 operators from overwriting higher-level operator
changes. Default is 0. Valid range is 0 to 255.

Sensor Offset Sensor offset value. It can be set to 0.

IMPORTANT
When controller OS 2.06.00 – 2.06.04 has been chosen,
note the following resctrictions and malfunctions:

323 EN2Z-0937GE51 R0518


EDITORS CARE

Smart I/O modules


The sensor offset value entered here, is not processed
by the Smart I/O module. To assure proper working,
enter the sensor offset in the network tree for the UCPT.

Critical Alarm Type Whether the point alarm condition is critical or not.
Critical alarms display on the central PC when they
occur. Noncritical alarms do not display software only
writes them to the alarm printer and alarm history file.

Suppress Alarm Whether or not software should suppress alarm


messages for changes in Fixed Mode and exceeding the
alarm and warning limits.

Hide Point Whether the point is visible or hidden. If a point is hidden,


it will not be displayed to the user when performing
online wildcard search on a central (only for controller
OS greater Ver. 2.0).

High Alarm Limit


High Warning Limit
Low Warning Limit
Low Alarm Limit High (max) and low (min) limits for point value. Limit
values must be between the limits for the associated
Characteristics. Limit values must also maintain the
following relationship:

High Alarm ≥ High Warning > Low Warning ≥ Low Alarm

If you change the Characteristics assignment, the High


limits default to the maximum characteristic value (if
larger than the new max) and the Low limits default to
the minimum characteristic value (if smaller than the new
min). The limits change only if they are outside the range
of the new characteristic.

Alarm Delay How long (0 through 3600 seconds) an alarm condition


must exist before software generates an alarm.

Alarm Hysteresis Available for controller OS Ver. greater than 1.5. This
value is the amount that an analog point must change
before software reports an alarm or return-to-normal.
Value range is 0 or x to y where x is determined by the
engineering unit decimal position and y is determined by
the difference of the high warning limit - low warning.

Engineering Unit
Decimal Position Min. Value (x)
0 1.0
1 0.1
2 .01
3 .001

Diff: = high warning limit - low warning.

For example, if the analog point has the following values:

engineering unit = Degrees with one decimal point


high alarm limit = 85.0
high warning limit = 82.0
low warning limit = 68.0
low alarm limit = 65.0

Diff = 82.0 - 68.0 = 14.0

EN2Z-0937GE51 R0518 324


CARE EDITORS

Therefore, the valid range is .01 to 14.


Default varies between 1 and 5 depending on schematic
element. If the value is zero, fixed hysteresis applies.

Trend Hysteresis Available for controller OS Ver. greater than 1.5. The
value that the point must change (negative or positive)
before software writes it to the trend buffer. Valid range is
0 or x to 100,000,000 (selected by entering 99999999).
The value of x is determined by the engineering unit of
the point as follows:

Engineering Unit
Decimal Position Min. Value (x)
0 1.0
1 0.1
2 .01
3 .001

If the value is 0, the trend behaves as in OS Ver. lower


than 1.5 and is as follows:
If value is greater than 20, the change must be at least 1
percent. If the value is less than 20, the change must be
at least .2 units

Default is 0 for points that are not part of an element. To


lessen or turn off the transmission of trend data, assign a
high number to this value or assign a value to the Trend
Cycle field. The Trend Cycle value takes precedence
over the Trend Hysteresis value. Software sends trend
data based on either hysteresis value or time, not both.

Trend Cycle Available for controller OS greater than Ver. 2.03. This
value is similar to the Trend Hysteresis value, but is
based on time. The range is 0 to 65535 minutes.
A value of 0 disables time-based trending. Any value
greater than 0 enables time-based trending. Time-based
trending takes precedence over Trend Hysteresis value.
Software sends trend data based on either hysteresis
value or time, not both.

Comment Allows the input of a comment

325 EN2Z-0937GE51 R0518


EDITORS CARE

Analog Output Point

Purpose Display and/or modify the attributes for the selected analog output point.

Procedure In the tree, click desired point to display current values on the right Properties
tab(itemized display).

or,

in the tree, click on any object (project, controller, plant) which the point belongs to,
and which is in grid display.

To modify values, edit desired values in the fields, and/or select/deselect desired
options.

Modules You can assign analog output points only to analog output modules. If the point
requires a switch, you can assign the point only to a location that has a switch. If the
point does not require a switch, you can still assign it to a location with a switch and
later move it to a location without a switch.

Attributes Description User Address Point name (maximum of 18 alphanumeric characters)


assigned to a point for operator use in locating and
commanding the point. Examples: AO1 and
MADMPRFL1. This name and the descriptor further
define the point. This name must be unique within a
controller. User addresses must include one non-digit
character and cannot include Tabs, double quotes, ?, *,
or space characters. All other ASCII characters are

EN2Z-0937GE51 R0518 326


CARE EDITORS

allowable (A-Z, 0-9, +, -, _, etc). For example, 12A is a


valid user address, but 12 is not. Behind the user
address field the bus type (IP bus or LON-bus) where
the point resides, is displayed.

IMPORTANT
Note that the max. length of the user address for Lon
points should not exceed 18 characters (see Lon point
attribute).

Technical Address Internal six-digit number that defines and locates a point
in the system. The number is composed of three pairs
representing controller number (0-30), module number
(1-16), and terminal number (1-12).

Example: 010310 meaning Controller 1, Module 3,


terminal 10. Operators use the User Address to refer to
points.

For LON points the module number is 90. When the


number of LON points (terminals) exceeds 99, the
module number will change to 91 and the LON point gets
number 1.

To change the technical address see the Teminal


Assignment Function chapter.

Controller Name Name of controller where the point is assigned. This


assignment is done during plant attachment.

Plant Info Name of plant.

Point Role Point Role created via an external tool like Win EDS. The
point role can be edited.

Point ID Point ID created via an external tool like Win EDS.

Point Subtype Type of point. List of choices depends on output module


type where the point is assigned.

Lon Point Define whether the datapoint should be a LON point.


Select from the list under:

NV-Input
Creates input NV.

NV-Output
Creates output NV.

NV-Input & Output


Creates both, input and output NV.

Manual Mapping
Provides selection of this datapoint for mapping to NVs in
the NV-Editor.

NV Type Define the NV-type for the LON point. From the Input
and/or Output drop-down lists select desired type.

To edit a LON point, open the NV-Editor by clicking the


dotted button on the right.

VCT Displays whether or not a value conversion table (VCT)


is assigned to the NV-Input Type or NV-Output Type.

Engineering Unit List of choices displays engineering units with ID, unit,
and format.

327 EN2Z-0937GE51 R0518


EDITORS CARE

To add and change units in the list, open the


Miscellaneous Text Editor by clicking the dotted button
on the right (see Miscellaneous Text Editor chapter)

Descriptor Supplemental point information (maximum of 32


characters). Each Excel Controller has a unique set of
descriptors (64 for Ver. 1.2 Controllers; 255 for Ver 1.3
and greater Controllers) that can be assigned to its user
addresses to further describe them. Example: user
address “MADMPRFL1” can have a descriptor of “Mixed
air damper, Floor 1” to help define its location.

List of choices displays descriptors with ID and text.


To add and change descriptors in the list, open the
Miscellaneous Text Editor by clicking the dotted button
on the right (see Miscellaneous Text Editor chapter).

Characteristic Input and output characteristics of the associated sensor.


List of choices displays characteristics with ID and text.
To add and change characteristics in the list, open the
Miscellaneous Text Editor by clicking the dotted button
on the right (see Miscellaneous Text Editor chapter).

Operator Access Level Access level (1 through 4) that an operator must have to
modify point data via an operator terminal. For example,
if a point has an Operator Access Level of 2, only
operators with Access Level 2 and higher can change
point attributes.

Safety Position The safety position is the position the device is


commanded to if the controller does not deliver a value
(no response). It can be selected under:

-5%
- 50 %
- 100 %
- Last valid Position

The safety position is affected by the characteristic


used for the controller modules. For particular
characteristics there is no linear correlation
between percentage value and voltage output:

DP Listbox Characteristic Safety position (%)


Type number 0 50 100
in DP in
values Volts

AO 1..10 User defined 0 5 10


AO 9 0-100%=2-10V -25 37.5 0 5 10
100
AO 10 100-0%=2-10V 125 62.5 0 0 5 10
AO 12 LINEAR GRAPH 0 50 100 0 5 10
AO 24 0-10V=0-100% 0 50 100 0 5 10
AO 25 2-10V=0-100% 0 50 100 2 6 10
DO -- DO on AO OFF / ON 0 10
MOT 12 LINEAR GRAPH 0 50 100 0 5 10

NOTE: The user-defined characteristics 1 through 10 can be changed; in this


context, characteristics 3, 4, 5, 6, 9, 10 are pre-defined by CARE (default

EN2Z-0937GE51 R0518 328


CARE EDITORS

characteristics) and characteristics 1 and 2 are not pre-defined. The


default characteristics 3 through 6 are pressure input characteristics
which should not be used for an analog output.

In general, for the user-defined characteristics 1 through 10, the safety


positions 0%, 50%, 100% do always mean 0V, 5V, 10V; in this context
the datapoint values for characteristics 9 and 10 are deviant.

Initial. Value Value of point on initial start-up.

Write Protect Priority Prevent lower-level operators from changing point


attributes that a higher-level operator changed. For
example, if a point has an Access attribute of 2 and an
operator with Access Level 3 changes an attribute,
software restricts future changes to operators with at
least Level 3 access. This protection prevents any Level
1 operators from overwriting higher-level operator
changes. Default is 0. Valid range is 0 to 255.

Suppress Alarm Whether or not software should suppress alarm


messages for changes in Fixed Mode and exceeding the
alarm and warning limits.

Hide Point Whether the point is visible or hidden. If a point is hidden,


it will not be displayed to the user when performing
online wildcard search on a central (only for controller
OS greater than Ver. 2.0).

Time to Open Time (integer, 0 through 999 seconds) required for the
actuator of a three-position output to motor from the
closed to the open state.

Time to Close Time (integer, 0 through 999 seconds) required for the
actuator of a three-position output to motor from the open
to the closed state.

Trend Hysteresis Available for controller OS Ver. greater than 1.5. The
value that the point must change (negative or positive)
before software writes it to the trend buffer. Valid range is
0 or x to 100,000,000 (selected by entering 99999999).
The value of x is determined by the engineering unit of
the point as follows:

Engineering Unit
Decimal Position Min. Value (x)
0 1.0
1 0.1
2 .01
3 .001

If the value is 0, the trend behaves as in OS Ver. lower


than 1.5 and is as follows:
If value is greater than 20, the change must be at least 1
percent. If the value is less than 20, the change must be
at least .2 units.

Default varies between 1 and 5 depending on schematic


element.

To lessen or turn off the transmission of trend data,


assign a high number to this value or assign a value to
the Trend Cycle Minutes field. The Trend Cycle value
takes precedence over the Trend Hysteresis value.
Software sends trend data based on either hysteresis
value or time, not both.

329 EN2Z-0937GE51 R0518


EDITORS CARE

Trend Cycle Available for controller OS greater than Ver. 2.03. This
value is similar to the Trend Hysteresis value, but is
based on time. The range is 0 to 65535 minutes.
A value of 0 disables time-based trending. Any value
greater than 0 enables time-based trending. Time-based
trending takes precedence over Trend hysteresis value.
Software sends trend data based on either hysteresis
value or time, not both.

Comment Allows the input of a comment

EN2Z-0937GE51 R0518 330


CARE EDITORS

Digital Input Point

Purpose Display and/or modify the attributes for the selected digital input point.

Procedure In the tree, click desired point to display current values on the right Properties tab
(itemized display).

or,

in the tree, click on any object (project, controller, plant) which the point belongs to,
and which is in grid display.

To modify values, edit desired values in the fields, and/or select/deselect desired
options.

Modules You can assign digital input points only to digital input modules.

Attributes description User Address Point name (maximum of 18 alphanumeric characters)


assigned to a point for operator use in locating and
commanding the point.

Examples: DI1 and HWTRPUMPST. This name and the


descriptor further define the point. This name must be
unique within a controller.
User addresses must include one non-digit character and
cannot include Tabs, double quotes, ?, *, or space
characters. All other ASCII characters are allowable (A-

331 EN2Z-0937GE51 R0518


EDITORS CARE

Z, 0-9, +, -, _, etc). For example, 12A is a valid user


address, but 12 is not.

IMPORTANT
Note that the max. length of the user address for Lon
points should not exceed 18 characters (see Lon point
attribute).

Behind the user address field the bus type (IP bus or
LON-bus) where the point resides, is displayed.

Technical Address Internal six-digit number that defines and locates a point
in the system. The number is composed of three pairs
representing controller number (0-30), module number
(1-16), and terminal number (1-12). Example: 010310
meaning Controller 1, Module 3, terminal 10. Operators
use the User Addressto refer to points.

For LON points the module number is 90. When the


number of LON points (terminals) exceeds 99, the
module number will change to 91 and the LON point gets
number 1.

To change the technical address see the Teminal


Assignment Function chapter.

Controller Name Name of controller where the point is assigned. This


assignment is done during plant attachment.

Plant Info Name of plant.

Point Role Point Role created via an external tool like Win EDS. The
point role can be edited.

Point ID Point ID created via an external tool like Win EDS.

Point Subtype Type of point. List of choices depends on input module


type where the point is assigned.

Lon Point Define whether the datapoint should be a LON point.


Select from the list under:

NV-Input
Creates input NV.

NV-Output
Creates output NV.

NV-Input & Output


Creates both, input and output NV.

Manual Mapping
Provides selection of this datapoint for mapping to NVs in
the NV-Editor.

NV Type Define the NV-type for the LON point. From the Input
and/or Output drop-down lists select desired type.

To edit a LON point, open the NV-Editor by clicking the


dotted button on the right.

VCT Displays whether or not a value conversion table (VCT)


is assigned to the NV-Input Type or NV-Output Type.
Engineering Unit List of choices displays ID, number of states, and active
and passive state texts for the point, for example, On and

EN2Z-0937GE51 R0518 332


CARE EDITORS

Off. Software determines these texts from the assigned


engineering unit.

To add and change units in the list, open the


Miscellaneous Text Editor by clicking the dotted button
on the right (see Miscellaneous Text Editor chapter).

Descriptor Supplemental point information (maximum of 32


characters). Each Excel Controller has a unique set of
descriptors (64 for Ver. 1.2 Controllers; 255 for Ver 1.3
and greater Controllers) that can be assigned to its user
addresses to further describe them. Example: user
address “HWTRPUMPST” can have a descriptor of
“Heating circuit, West wing” to help define its location.

List of choices displays descriptors with ID and text.


To add and change descriptors in the list, open the
Miscellaneous Text Editor by clicking the dotted button
on the right (see Miscellaneous Text Editor chapter).

Alarm Text Alarm text that displays on point alarm.


List of choices displays alarm texts with ID and text.
To add and change alarm texts in the list, open the
Miscellaneous Text Editor by clicking the dotted button
on the right (see Miscellaneous Text Editor chapter).

Operator Access Level Access level (1 through 4) that an operator must have to
modify point data via an operator terminal. For example,
if a point has an Operator Access Level of 2, only
operators with Access Level 2 and higher can change
point attributes.

LED Mode Toggles the LED between status mode and alarm mode
with the following indication:

Status
Yellow = ON, No color = OFF

Alarm
Red = Alarm, Green = No alarm

This attribute applies to XF8.. and XFL8.. modules only.


The XF8.. panel modules can also be toggled in the
terminal assignment tool (TAF).

LED Mode applies to Excel 800 only.

Service Interval Number of log hours after which software generates a


maintenance alarm. Enter zero for no alarm message.
Runtime Enabled must be enabled (Yes). Note that
runtime accumulates only if the point is in the active
state.

Write Protect Priority Prevent lower-level operators from changing point


attributes that a higher-level operator changed. For
example, if a point has an Access attribute of 2 and an
operator with Access Level 3 changes an attribute,
software restricts future changes to operators with at
least Level 3 access. This protection prevents any Level
1 operators from overwriting higher-level operator
changes. Default is 0. Valid range is 0 to 255.

Critical Alarm Type Whether the point alarm condition is critical or not.
Critical alarms display on the central PC when they
occur. Noncritical alarms do not display; software only
writes them to the alarm printer and alarm history file

333 EN2Z-0937GE51 R0518


EDITORS CARE

Suppress Alarm Whether or not software should suppress alarm


messages.
Alarm Point Whether or not software should monitor point changes
from active to passive.

Hide Point Whether the point is visible or hidden. If a point is hidden,


it will not be displayed to the user when performing
online wildcard search on a central (only for controller
OS greater than Ver. 2.0).

Runtime Enabled Whether or not to maintain a count of hours run


(resolution one hour).
Alarm Delay Length of time (integer, 0 through 3600 seconds) an
alarm condition must exist before software generates an
alarm.

Active State State that determines which point state (Logic 0 or 1) is


the active (“normal”) state. The other state is the passive
(“alarm”) state.

The following table shows the relationship between


active and passive states and statuses as well as
between N.O. and N.C.

Logical State Active State Value


Hardware DI DI 0 1
Condition (NC) (NO)
No voltage at 1 0 Active Passive
screw terminal. Text, Text,
See Note 1. normal alarm
Voltage at 0 1 Passive Active
screw terminal. Text, Text,
See Note 2. alarm normal

NOTES:
1. On an Excel 500 or 100, this is an open contact. On
an Excel 80, this is a closed contact.
2. On an Excel 500 or 100, this is a closed contact. On
an Excel 80, this is an open contact.

The active state flag affects the alarm state and


engineering units that display for digital inputs. The point
type (NO/NC) affects the logical operation of the point.

Note that software monitors point state only if the Alarm


Point field is checked.

Active State only applies to controller OS Ver. lower than


2.04 (see Upgrade Controller to OS 2.04 section in
Appendix D)

Comment Allows the input of a comment

EN2Z-0937GE51 R0518 334


CARE EDITORS

Digital Output Point

Purpose Display and/or modify the attributes for the selected digital output point.

Procedure In the tree, click desired point to display current values on the right Properties tab
(itemized display).

or,

in the tree, click on any object (project, controller, plant) which the point belongs to,
and which is in grid display.

To modify values, edit desired values in the fields, and/or select/deselect desired
options.

Modules You can assign digital output points only to digital output modules. If the point
requires a switch you can assign the point only to a location that has a switch. If the
point does not require a switch, you can still assign it to a location with a switch and
later move it to a location without a switch.

Attributes Description User Address Point name (maximum of 18 alphanumeric characters)


assigned to a point for operator use in locating and
commanding the point. Example: DONOSWITCH1. This
name and the descriptor further define the point. This
name must be unique within a controller.

335 EN2Z-0937GE51 R0518


EDITORS CARE

User addresses must include one non-digit character and


cannot include Tabs, double quotes, ?, *, or space
characters. All other ASCII characters are allowable (A-
Z, 0-9, +, -, _, etc). For example, 12A is a valid user
address, but 12 is not.

IMPORTANT
Note that the max. length of the user address for Lon
points should not exceed 18 characters (see Lon point
attribute).

Behind the user address field the bus type (IP bus or
LON-bus) where the point resides, is displayed.

Technical Address Internal six-digit number that defines and locates a point
in the system. The number is composed of three pairs
representing controller number (0-30), module number
(1-16), and terminal number (1-12). Example: 010310
meaning Controller 1, Module 3, terminal 10. Operators
use the User Addressto refer to points.

For LON points the module number is 90. When the


number of LON points (terminals) exceeds 99, the
module number will change to 91 and the LON point gets
number 1.

To change the technical address see the Teminal


Assignment Function chapter.

Controller Name Name of controller where the point is assigned. This


assignment is done during plant attachment.

Plant Info Name of plant.

Point Role Point Role created via an external tool like Win EDS. The
point role can be edited.

Point ID Point ID created via an external tool like Win EDS.

Point Subtype Type of point. List of choices depends on output module


type where the point is assigned.

Lon Point Define whether the datapoint should be a LON point.


Select from the list under:

NV-Input
Creates input NV.

NV-Output
Creates output NV.

NV-Input & Output


Creates both, input and output NV.

Manual Mapping
Provides selection of this datapoint for mapping to NVs in
the NV-Editor.

NV Type Define the NV-type for the LON point. From the Input
and/or Output drop-down lists select desired type.

VCT Displays whether or not a value conversion table (VCT)


is assigned to the NV-Input Type or NV-Output Type.

Engineering Unit List of choices displays ID, number of states, and active
and passive state texts for the point, for example, On and

EN2Z-0937GE51 R0518 336


CARE EDITORS

Off. Software determines these texts from the assigned


engineering unit.

To add and change units in the list, open the


Miscellaneous Text Editor by clicking the dotted button
on the right (see Miscellaneous Text Editor chapter).

Descriptor Supplemental point information (maximum of 32


characters). Each Excel Controller has a unique set of
descriptors (64 for Ver. 1.2 Controllers; 255 for Ver 1.3
and greater Controllers) that can be assigned to its user
addresses to further describe them. Example: user
address “DONOSWITCH1” can have a descriptor of
“Main Floor Mixed Air Damper” to help define its location.
List of choices displays descriptors with ID and text.
To add and change descriptors in the list, open the
Miscellaneous Text Editor by clicking the dotted button
on the right (see Miscellaneous Text Editor chapter).

Operator Access Level Access level (1 through 4) that an operator must have to
modify point data via an operator terminal. For example,
if a point has an Operator Access Level of 2, only
operators with Access Level 2 and higher can change
point attributes.

Safety Position The safety position is the position the device is


commanded to if the controller does not deliver a value
(no response). It can be selected under:

- OFF (logical)
- ON (logical)
device is commanded to the selected logical state

- Last valid Position


device is commanded to the last valid position

Service Interval Number of log hours after which software generates a


maintenance alarm. Enter zero for no alarm message.
Runtime Enabled must be enabled (Yes). Note that
runtime accumulates only if the point is in the active
state.

Pulse Duration Time (sec) of momentary pulse output.).

Critical Alarm Type Whether the point alarm condition is critical or not.
Critical alarms display on the central PC when they
occur. Noncritical alarms do not display; software only
writes them to the alarm printer and alarm history file.

Suppress Alarm Whether or not software should suppress maintenance


alarm messages.

Hide Point Whether the point is visible or hidden. If a point is hidden,


it will not be displayed to the user when performing
online wildcard search on a central (only for controller
OS greater than Ver. 2.0).

Runtime Enabled Whether or not to maintain a count of hours run


(resolution one hour). Available only for non-pulsed DOs.
This item does not display for pulse-type points.

Active State State that determines which point state (Logic 0 or 1) is


the active (“normal”) state. The other state is the passive
(“alarm”) state.

337 EN2Z-0937GE51 R0518


EDITORS CARE

The following table shows the relationship between


active and passive states and statuses, as well as
between energized and deenergized.

Active State Value


Hardware Condition 0 1
Active Text, Passive Text,
Deenergized Logic 1 Logic 0
Passive Text, Active Text,
Energized Logic 0 Logic 1

The active state flag affects the logical operation and


engineering units of digital outputs. The point type
(NO/NC) only affects the terminal assignment during you
attach the plant.

Active State only applies to controller OS Ver. lower than


2.04 (see Upgrade Controller to OS 2.04 section in
Appendix D)

Comment Allows the input of a comment

EN2Z-0937GE51 R0518 338


CARE EDITORS

Flex Point

Purpose Display and/or modify the attributes for the selected flex point.

Procedure In the tree, click desired flex point, but not the associated physical point, which is
one level below the flex point. The current values are displayed on the right
Properties tab (itemized display).

or,

in the tree, click on any object (project, controller, plant) which the point belongs to,
and which is in grid display.

To modify values, edit desired values in the fields, and/or select/deselect desired
options.

Flex Point Definition Flex points are pseudopoints that represent one or more physical points. They can
command and/or display associated physical points and their values via an operator
terminal. Flex point types include Pulse_2, Multistage, and Point with Feedback.

The Flex Points subsection in the Plant Schematics chapter describes how to create
and modify these points.

This section describes the attributes dialog boxes that you can use to modify flex
point attributes.

Common Attributes Description The following are the common attributes similar to the attributes of other points:

User Address Flex point name (maximum of 18 alphanumeric


characters) assigned to a point for operator use in
locating and commanding the point. Examples: Flex1

339 EN2Z-0937GE51 R0518


EDITORS CARE

and MainRF. This name and the descriptor further define


the point. This name must be unique within a controller.
User addresses must include one non-digit character and
cannot include Tabs, double quotes, ?, *, or space
characters. All other ASCII characters are allowable (A-
Z, 0-9, +, -, _, etc). For example, 12A is a valid user
address, but 12 is not.

Controller Name Name of controller where the point is assigned. This


assignment is done during plant attachment.

Technical Address List of addresses for the points associated with the flex
point.

Engineering Unit List of choices displays ID, number of states, the state
and its corresponding text. Software determines these
texts from the assigned engineering unit.

To add and change units in the list, open the


Miscellaneous Text Editor by clicking the dotted button
on the right (see Miscellaneous Text Editor chapter).

Descriptor Supplemental point information (maximum of 32


characters). Each Excel Controller has a unique set of
descriptors (64 for Ver. 1.2 Controllers; 255 for Ver 1.3
and greater Controllers) that can be assigned to its user
addresses to further describe them. Example: user
address “DONOSWITCH1” can have a descriptor of
“Main Floor Mixed Air Damper” to help define its location.

List of choices displays descriptors with ID and text.


To add and change descriptors in the list, open the
Miscellaneous Text Editor by clicking the dotted button
on the right (see Miscellaneous Text Editor chapter).

Alarm Text Alarm text that displays on point alarm.

List of choices displays alarm texts with ID and text.


Applies only to DO_Feedback_DI points.

To add and change alarm texts in the list, open the


Miscellaneous Text Editor by clicking the dotted button
on the right (see Miscellaneous Text Editor chapter).

Comment Allows the input of a comment

Special Attributes Description Point Attribute


(Attribute, Value) List of special point attributes that apply to the flex point.
The Value column displays current editable values.
Read-only attributes are disabled (same color as
Attribute column) and cannot be edited.

Active State State that determines which point state (Logic 0 or 1) is


the active (“normal”) state. The other state is the “alarm”,
or passive, state. Applies to multistage points.

Oper. Access Level Access level (1 through 4) that an operator must have to
modify point data via an operator terminal. For example,
if a point has an Operator Access Level of 2, only
operators with Access Level 2 and higher can change
point attributes.

Suppr. Alarm Whether or not software should suppress alarm


messages for changes in Fixed Mode and exceeding the
alarm and warning limits. Click to change from Yes to No
and vice versa.

EN2Z-0937GE51 R0518 340


CARE EDITORS

Critical Alarm (Type) Whether the point alarm condition is critical or not.
Critical alarms display on the central PC when they
occur. Noncritical alarms do not display; software only
writes them to the alarm printer and alarm history file.
Click to change from critical to non-critical and vice
versa.
Runtime Enabl. Whether the point is pulsed or non-pulsed. When you
assign the point to a schematic, you set this value.

Service Interval Preset the number of hours that the run-time counter
uses.

Hide Point Whether the point is visible or hidden. If a point is hidden,


it will not be displayed to the user when performing
online wildcard search on a central (only for controller
OS greater than Ver. 2.0.

Write Protect Priority Access level (0-255) for operators at operator terminals.

Alarm Delay Software compares the status of the feedback with the
output status after this delay time. Applies only to digital
input points that are part of DO_Feedback_DI points.

Pulse Duration Time of the momentary pulse output. Applies only to


pulse_2 and DO_Feedback_DI points.

Delay Switch Up Waiting period between switching the stages of a staged


point. Delay time affects every stage. Applies only to
DO_Feedback_DI points.

Delay Switch Down Waiting period between switching down the stages of a
staged point. Delay time affects every stage. Applies only
to DO_Feedback_DI points.

Switching Down Sequence to use when switching down. Applies only to


DO_Feedback_DI points.
There are two sequences: <3,0,2,0,1,0> or <3,2,1,0>.

The <3,0,2,0,1,0> sequence switches down using the


OFF position. Use this setting for systems that have a
high inertia (for example, ventilators). When software
switches down one stage, it first turns the switch to OFF.
The <3,2,1,> sequence switches down to the next lower
stage directly. The OFF phase does not exist (for
example, electric air heaters).

Each stage is active for the Delay Switch Down,


independent of the mode of Switching Down.

Duration Off Off time value software uses in conjunction with


switching point state (down) with a switch to off between
states. Applies only to DO_Feedback_DI points.

Feedback Delay Time Length of time (in seconds) before software checks the
input to verify that it follows the associated output.
Applies only to DO_Feedback_DI points.

Number Of Stages Number of stages in this feedback point (1, 2, or 3).


Applies only to DO_Feedback_DI points.

Cycle Count-Active State Value of a counter that represents the number of times a
point is commanded to active state. This attribute is read-
only.

Global Points

341 EN2Z-0937GE51 R0518


EDITORS CARE

Purpose Display and/or modify the attributes for the selected global analog point.

Definition Global points are a type of pseudopoint that can be either an input or output. The
purpose of global points is to share point information across controllers on a bus.

Global inputs receive information from a point in another controller. Use a global
input when one controller has a point that should be global to many other
controllers.

Global outputs send information to other points in other controllers. Use a global
output when one controller has a point that is global to only one point in another
controller. You can also use global outputs for some control icons that only connect
to outputs and the output must be global. Global outputs can only be associated with
pseudopoints or output points (not input points).

Centrals Note Central PCs such as the Excel Building Supervisor (XBS) and Excel Building
Supervisor-Integrated (XBS-i) only read global originator points. The values of global
receiver points are only available via the B port of the controller.

C-Bus Tunneling Note From Controller OS 2.06 on, it is strongly recommended to use max. 25 global
points per system or project. Instead, NV-binding can be used to get global
communication between controllers.

Global Inputs Each global input is associated with a pseudopoint or physical point (“originator”
point) somewhere on the bus and has the same user address, controller number in
the technical address, engineering unit, and type (analog or digital) as the point. The
originator point cannot be a global point.

You select the correct type and enter the correct user address when you create the
global point. To set the appropriate controller number in the technical address and
the engineering unit, use this dialog box.

Global Input Point Operation

The system updates global inputs every 2 minutes. It also updates global analog
inputs when the originator point changes significantly. If point value is greater than
20, the change must be at least 1 percent. If point value is less than or equal to 20,
the change must be at least .2 units. For example:

Point Value Change

100 1
200 2
50 .5
10 .2
5 .2
For global digital points, a change of state triggers an update.

EN2Z-0937GE51 R0518 342


CARE EDITORS

Global Outputs Each global output is associated with a pseudopoint or physical point (“receiver”
point) somewhere on the bus and has the same user address, technical address,
engineering unit, and type (analog or digital output) as the point.

You select the correct type and enter the correct user address when you create the
global point. To set the appropriate technical address, point subtype,and
engineering unit, use this dialog box.

Global Output Point Operation

The system updates the receiver points when the global analog outputs change
significantly. If global value is greater than 20, the change must be at least 1
percent. If global value is less than or equal to 20, the change must be at least .2
units. For example:

Global Value Change

100 1
200 2
50 .5
10 .2
5 .2

For global digital points, a change of state triggers an update.

There is no automatic 2-minute refresh for global output points.

343 EN2Z-0937GE51 R0518


EDITORS CARE

Global Analog Point

Purpose Display and/or modify the attributes for the selected global analog point.

Procedure In the tree, click desired point to display current values on the right Properties tab
(itemized display).

or,

in the tree, click on any object (project, controller, plant) which the point belongs to,
and which is in grid display.

To modify values, edit desired values in the fields, and/or select/deselect desired
options.

Attributes description User Address Point name (maximum of 18 alphanumeric characters)


assigned to a point for operator use in locating and
commanding the point. Example: OaTemp. This name
and the descriptor further define the point. This name
must match the name of the point that is the receiver or
originator of information for this global point.

Technical Address Internal six-digit number that defines and locates a point
in the system. The number is composed of three pairs
representing controller number (1-30), module number
(1-16), and terminal number (1-12). Example: 010310
meaning Controller 1, Module 3, terminal 10. Operators

EN2Z-0937GE51 R0518 344


CARE EDITORS

use the User Address to refer to points.

Select and type over parts of address to change it.

Technical Address
If it is associated with a physical point, this address must
match the associated point. The globals definition at the
beginning of this section describes addressing rules.

Physical Address
If it is associated with a pseudo point, only the controller
number is issued. The other two fields can be blank, 0 or
99.

Controller Name Name of controller where the point is assigned. This


assignment is done during plant attachment.

Plant Info Name of plant.

Point Role Point Role created via an external tool like Win EDS. The
point role can be edited.

Point ID Point ID created via an external tool like Win EDS.

Point Subtype Type of point (input or output).

Engineering Unit List of choices displays engineering units with ID, unit,
and format.

To add and change units in the list, open the


Miscellaneous Text Editor by clicking the dotted button
on the right (see Miscellaneous Text Editor chapter)

Descriptor Supplemental point information (maximum of 32


characters. Each Excel Controller has a unique set of
descriptors (64 for Ver. 1.2 Controllers; 255 for Ver 1.3
and greater Controllers) that can be assigned to its user
addresses to further describe them. Example: user
address “OaTemp” can have a descriptor of “outdoor dry
bulb temp” to help define its location.

List of choices displays descriptors with ID and text.


To add and change descriptors in the list, open the
Miscellaneous Text Editor by clicking the dotted button
on the right (see Miscellaneous Text Editor chapter).

Operator Access Level Access level (1 through 4) that an operator must have to
modify point data via an operator terminal. For example,
if a point has an Operator Access Level of 2, only
operators with Access Level 2 and higher can change
point attributes.

Write Protect Priority Prevent lower-level operators from changing point


attributes that a higher-level operator changed. For
example, if a point has an Access attribute of 2 and an
operator with Access Level 3 changes an attribute,
software restricts future changes to operators with at
least Level 3 access. This protection prevents any Level
1 operators from overwriting higher-level operator
changes. Default is 0. Valid range is 0 to 255

Hide Point Whether the point is visible or hidden. If a point is hidden,


it will not be displayed to the user when performing
online wildcard search on a central (only for controller
OS greater than Ver. 2.0).

345 EN2Z-0937GE51 R0518


EDITORS CARE

Trend Hysteresis Available for controller OS Ver. greater than 1.5. The
value that the point must change (negative or positive)
before software writes it to the trend buffer. Valid range is
0 or x to 100,000,000 where x is determined by the
engineering unit of the point as follows:

Engineering Unit
Decimal Position Min. Value (x)
0 1.0
1 0.1
2 .01
3 .001

If the value is 0, the trend behaves as in OS Ver. lower


than 1.5 and is as follows:
If value is greater than 20, the change must be at least 1
percent. If the value is less than 20, the change must be
at least .2 units. Default is 0.
To lessen or turn off the transmission of trend data,
assign a high number to this value or assign a value to
the Trend Cycle Minutes field. The Trend Cycle Minutes
value takes precedence over the Trend Hysteresis value.
Software sends trend data based on either hysteresis
value or time, not both.

Trend Cycle Available for controller OS greater than Ver. 2.03. This
value is similar to the Trend Hysteresis value, but is
based on time. The range is 0 to 65535 minutes.

A value of 0 disables time-based trending. Any value


greater than 0 enables time-based trending. Time-based
trending takes precedence over Trend Hysteresis value.
Software sends trend data based on either hysteresis
value or time, not both.

Broadcast Hyst. Available for controller OS Ver. 1.5. This value is that
amount that a point must change before software
broadcasts it to other controllers. Value range is 0 or x to
100,000,000 where x is determined by engineering unit
decimal position as follows.

Engineering Unit
Decimal Position Min. Value (x)
0 1.0
1 0.1
2 .01
3 .001

If the value is 0, software constantly broadcasts to the


controllers. Default is 0. If several global points are
assigned to the same physical point, the lowest global
point broadcast hysteresis from the assigned global point
is used. This value can also be accessed by the RIA and
WIA control icons.

To lessen or turn off the frequency of broadcasts, assign


a high number to this value.

Comment Allows the input of a comment

EN2Z-0937GE51 R0518 346


CARE EDITORS

Global Digital Point

Purpose Display and/or modify the attributes for the selected global digital point.

See the Global Points section for a definition of globals and how they operate.

Procedure In the tree, click desired point to display current values on the right Properties tab
(itemized display).

or,

in the tree, click on any object (project, controller, plant) which the point belongs to,
and which is in grid display.

To modify values, edit desired values in the fields, and/or select/deselect desired
options.

Attributes Description User Address Point name (maximum of 18 alphanumeric characters)


assigned to a point for operator use in locating and
commanding the point. Example: global_dig. This name
and the descriptor further define the point. This name
must match the name of the point that is the receiver or
originator of information for this global point.

Technical Address Internal six-digit number that defines and locates a point
in the system. The number is composed of three pairs
representing controller number (1-30), module number
(1-16), and terminal number (1-12). Example: 010310
meaning Controller 1, Module 3, terminal 10. Operators
use the User Address to refer to points.

347 EN2Z-0937GE51 R0518


EDITORS CARE

Select and type over parts of address to change it, if


desired
Technical Address
If it is associated with a physical point, this address must
match the associated point. The globals definition at the
beginning of this section describes addressing rules.

Physical Address
If it is associated with a pseudo point, Only the controller
number is issued. The other two fields can be blank, 0 or
99.

Controller Name Name of controller where the point is assigned. This


assignment is done during plant attachment.

Plant Info Name of plant.

Point Role Point Role created via an external tool like Win EDS. The
point role can be edited.

Point ID Point ID created via an external tool like Win EDS.

Point Subtype Type of point (input or output).

Engineering Unit List of choices displays ID, number of states, and active
and passive state texts for the point, for example, On and
Off. Software determines these texts from the assigned
engineering unit.

To add and change units in the list, open the


Miscellaneous Text Editor by clicking the dotted button
on the right (see Miscellaneous Text Editor chapter).

Descriptor Supplemental point information (maximum of 32


characters). Each Excel Controller has a unique set of
descriptors (64 for Ver. 1.2 Controllers; 255 for Ver 1.3
and greater Controllers) that can be assigned to its user
addresses to further describe them. Example: user
address “global_dig” can have a descriptor of
“occupancy / vacancy mode” to help define its location.

List of choices displays descriptors with ID and text.


To add and change descriptors in the list, open the
Miscellaneous Text Editor by clicking the dotted button
on the right (see Miscellaneous Text Editor chapter).

Operator Access Level Access level (1 through 4) that an operator must have to
modify point data via an operator terminal. For example,
if a point has an Operator Access Level of 2, only
operators with Access Level 2 and higher can change
point attributes.

Write Protect Priority Prevent lower-level operators from changing point


attributes that a higher-level operator changed. For
example, if a point has an Access attribute of 2 and an
operator with Access Level 3 changes an attribute,
software restricts future changes to operators with at
least Level 3 access. This protection prevents any Level
1 operators from overwriting higher-level operator
changes. Default is 0. Valid range is 0 to 255

Hide Point Whether the point is visible or hidden. If a point is hidden,


it will not be displayed to the user when performing
online wildcard search on a central (only for controller
OS greater than Ver. 2.0).

EN2Z-0937GE51 R0518 348


CARE EDITORS

Comment Allows the input of a comment

349 EN2Z-0937GE51 R0518


EDITORS CARE

Pseudo Analog Point

Purpose Display and/or modify the attributes for the selected pseudo analog point.

Procedure In the tree, click desired point to display current values on the right Properties tab
(itemized display).

or,

in the tree, click on any object (project, controller, plant) which the point belongs to,
and which is in grid display.

To modify values, edit desired values in the fields, and/or select/deselect desired
options.

Attributes Description User Address Point name (maximum of 18 alphanumeric characters)


assigned to a point for operator use in locating and
commanding the point. Example: Room_Average.

EN2Z-0937GE51 R0518 350


CARE EDITORS

This name and the descriptor further define the point.


This name must be unique within a controller.

User addresses must include one non-digit character and


cannot include Tabs, double quotes, ?, *, or space
characters. All other ASCII characters are allowable (A-
Z, 0-9, +, -, _, etc). For example, 12A is a valid user
address, but 12 is not.

IMPORTANT
Note that the max. length of the user address for Lon
points should not exceed 18 characters (see Lon point
attribute).

Controller Name Name of controller where the point is assigned. This


assignment is done during plant attachment.

Plant Info Name of plant.

Point Role Point Role created via an external tool like Win EDS. The
point role can be edited.

Point ID Point ID created via an external tool like Win EDS.

Point Subtype None.

Lon Point Define whether the datapoint should be a LON point.


Select from the list under:

NV-Input
Creates input NV.

NV-Output
Creates output NV.

NV-Input & Output


Creates both, input and output NV.

Manual Mapping
Provides selection of this datapoint for mapping to NVs in
the NV-Editor.

NV Type Define the NV-type for the LON point. From the Input
and/or Output drop-down lists select desired type.

VCT Displays whether or not a value conversion table (VCT)


is assigned to the NV-Input Type or NV-Output Type.

Engineering Unit List of choices displays engineering units with ID, unit,
and format.

To add and change units in the list, open the


Miscellaneous Text Editor by clicking the dotted button
on the right (see Miscellaneous Text Editor chapter)

351 EN2Z-0937GE51 R0518


EDITORS CARE

Descriptor Supplemental point information (maximum of 32


characters). Each Excel Controller has a unique set of
descriptors (64 for Ver. 1.2 Controllers; 255 for Ver 1.3
and greater Controllers) that can be assigned to its user
addresses to further describe them. Example: user
address “Room_Average” can have a descriptor of “West
wing Aug temperature” to help define its location.

List of choices displays descriptors with ID and text.


To add and change descriptors in the list, open the
Miscellaneous Text Editor by clicking the dotted button
on the right (see Miscellaneous Text Editor chapter).

Alarm Text Alarm text that displays on point alarm.


List of choices displays alarm texts with ID and text.
To add and change alarm texts in the list, open the
Miscellaneous Text Editor by clicking the dotted button
on the right (see Miscellaneous Text Editor chapter).

Operator Access Level Access level (1 through 4) that an operator must have to
modify point data via an operator terminal. For example,
if a point has an Operator Access Level of 2, only
operators with Access Level 2 and higher can change
point attributes.

Initial. Value Value of the pseudopoint on initial start-up.

Write Protect Priority Prevent lower-level operators from changing point


attributes that a higher-level operator changed. For
example, if a point has an Access attribute of 2 and an
operator with Access Level 3 changes an attribute,
software restricts future changes to operators with at
least Level 3 access. This protection prevents any Level
1 operators from overwriting higher-level operator
changes. Display only; always defaults to No (0).

Critical Alarm Type Whether the point alarm condition is critical or not.
Critical alarms display on the central PC when they
occur. Noncritical alarms do not display; software only
writes them to the alarm printer and alarm history file.

Suppress Alarm Whether or not software should suppress alarm


messages for changes in Fixed Mode and exceeding the
alarm and warning limits.

Hide Point Whether the point is visible or hidden. If a point is hidden,


it will not be displayed to the user when performing
online wildcard search on a central (only for controller
OS greater than Ver. 2.0).

High Alarm Limit


High Warning LImit
Low Warning Limit
Low Alarm Limit. High (max) and low (min) limits for point value. Limit
values must maintain the following relationship:

High Alarm ≥ High Warning > Low Warning ≥ Low Alarm

Alarm Hysteresis Available for controller OS Ver. greater than 1.5. This
value is the amount that an analog point must change
before software reports an alarm or return-to-normal.
Value range is 0 or x to y where x is determined by the
engineering unit decimal position and y is determined by
the difference of the high warning limit - low warning.

EN2Z-0937GE51 R0518 352


CARE EDITORS

Engineering Unit
Decimal Position Min. Value (x)
0 1.0
1 0.1
2 .01
3 .001

Diff: = high warning limit - low warning.

For example, if the analog point has the following values:

engineering unit = Degrees with one decimal point


high alarm limit = 85.0
high warning limit = 82.0
low warning limit = 68.0
low alarm limit = 65.0

Diff = 82.0 - 68.0 = 14.0

Therefore, the valid range is .01 to 14.


Default varies between 1 and 5 depending on schematic
element. If the value is zero, fixed hysteresis applies.

Trend Hysteresis Available for controller OS Ver. greater than 1.5. The
value that the point must change (negative or positive)
before software writes it to the trend buffer. Valid range is
0 or x to 100,000,000 (selected by entering 99999999).
The value of x is determined by the engineering unit of
the point as follows:

Engineering Unit
Decimal Position Min. Value (x)
0 1.0
1 0.1
2 .01
3 .001

If the value is 0, the trend behaves as in OS Ver. lower


than 1.5 and is as follows:
If value is greater than 20, the change must be at least 1
percent. If the value is less than 20, the change must be
at least .2 units. Default is 0.

To lessen or turn off the transmission of trend data,


assign a high number to this value or assign a value to
the Minutes field. The Trend Cycle Minutes value takes
precedence over the Trend Hysteresis value. Software
sends trend data based on either hysteresis value or
time, not both.

Trend Cycle Available for controller OS greater than Ver. 2.03. This
value is similar to the Trend Hysteresis value, but is
based on time. The range is 0 to 65535 minutes.
A value of 0 disables time-based trending. Any value
greater than 0 enables time-based trending. Time-based
trending takes precedence over Trend Hysteresis value.
Software sends trend data based on either hysteresis
value or time, not both.

Comment Allows the input of a comment

353 EN2Z-0937GE51 R0518


EDITORS CARE

Pseudo Digital Point

Purpose Display and/or modify the attributes for the selected pseudo digital point.

Procedure In the tree, click desired point to display current values on the right Properties tab
(itemized display).

or,

in the tree, click on any object (project, controller, plant) which the point belongs to,
and which is in grid display.

To modify values, edit desired values in the fields, and/or select/deselect desired
options.

Attributes Description User Address Point name (maximum of 18 alphanumeric characters)


assigned to a point for operator use in locating and
commanding the point. Example: pseudo_dig. This
name and the descriptor further define the point. This
name must be unique within a controller.
User addresses must include one non-digit character and
cannot include Tabs, double quotes, ?, *, or space
characters. All other ASCII characters are allowable (A-
Z, 0-9, +, -, _, etc). For example, 12A is a valid user
address, but 12 is not.
IMPORTANT

EN2Z-0937GE51 R0518 354


CARE EDITORS

Note that the max. length of the user address for Lon
points should not exceed 18 characters (see Lon
point attribute).

Controller Name Name of controller where the point is assigned. This


assignment is done during plant attachment.
Plant Info Name of plant.

Point Role Point Role created via an external tool like Win EDS. The
point role can be edited.

Point ID Point ID created via an external tool like Win EDS.

Point Subtype Type of point. PD 2-State or PD-n-State can be selected.

Lon Point Define whether the datapoint should be a LON point.


Select from the list under:
NV-Input
Creates input NV.

NV-Output
Creates output NV.

NV-Input & Output


Creates both, input and output NV.

Manual Mapping
Provides selection of this datapoint for mapping to NVs in
the NV-Editor.

NV Type Define the NV-type for the LON point. From the Input
and/or Output drop-down lists select desired type.

VCT Displays whether or not a value conversion table (VCT)


is assigned to the NV-Input Type or NV-Output Type.

Engineering Unit List of choices displays ID, number of states, and active
and passive state texts for the point, for example, On and
Off. Software determines these texts from the assigned
engineering unit.
To add and change units in the list, open the
Miscellaneous Text Editor by clicking the dotted button
on the right (see Miscellaneous Text Editor chapter).

Descriptor Supplemental point information (maximum of 32


characters). Each Excel Controller has a unique set of
descriptors (64 for Ver. 1.2 Controllers; 255 for Ver 1.3
and greater Controllers) that can be assigned to its user
addresses to further describe them. Example: user
address “pseudo_dig” can have a descriptor of “Hot
water pump status” to help define its location.

List of choices displays descriptors with ID and text.


To add and change descriptors in the list, open the
Miscellaneous Text Editor by clicking the dotted button
on the right (see Miscellaneous Text Editor chapter).

Alarm Text Alarm text that displays on point alarm.

List of choices displays alarm texts with ID and text.


To add and change alarm texts in the list, open the
Miscellaneous Text Editor by clicking the dotted button
on the right (see Miscellaneous Text Editor chapter).

Operator Access Level Access level (1 through 4) that an operator must have to
modify point data via an operator terminal. For example,

355 EN2Z-0937GE51 R0518


EDITORS CARE

if a point has an Operator Access Level of 2, only


operators with Access Level 2 and higher can change
point attributes.

Inital. Value Value the point should have on inital start-up

Service Interval Number of log hours after which software generates a


maintenance alarm. Enter zero for no alarm message.
Runtime Enabled must be enabled.

Write Protect Priority Prevent lower-level operators from changing point


attributes that a higher-level operator changed. For
example, if a point has an Access attribute of 2 and an
operator with Access Level 3 changes an attribute,
software restricts future changes to operators with at
least Level 3 access. This protection prevents any Level
1 operators from overwriting higher-level operator
changes. Default is 0. Valid range is 0 to 255.
Critical Alarm Type Whether the point alarm condition is critical or not.
Critical alarms display on the central PC when they
occur. Noncritical alarms do not display; software only
writes them to the alarm printer and alarm history file.

Suppress Alarm Whether or not software should suppress alarm


messages for changes in Fixed Mode and exceeding the
alarm and warning limits.

Alarm Point Whether or not software should monitor point changes


from active to passive.

Hide Point Whether the point is visible or hidden. If a point is hidden,


it will not be displayed to the user when performing
online wildcard search on a central (only for controller
OS greater than Ver. 2.0).

Runtime Enabled Whether or not to maintain a count of hours run


(resolution one minute).

Active State State that determines which point state (Logic 0 or 1) is


the active (“normal”) state. The other state is the passive
(“alarm”) state.

The following table shows the relationship between


active and passive states and statuses, as well as logical
states.

Active State Value


Logical State 0 1
0 Active Text, normal Passive Text, alarm
1 Passive Text, alarm Active Text, normal

The active state flag affects the engineering units and


alarm state that displays for digital pseudopoints.

Active State only applies to controller OS Ver. lower than


2.04 (see Upgrade Controller to OS 2.04 section in
Appendix D)

Comment Allows the input of a comment

EN2Z-0937GE51 R0518 356


CARE EDITORS

Pseudo Totalizer Point

Purpose Display and/or modify the attributes for the selected pseudo totalizer input point.

Procedure In the tree, click desired point to display current values on the right Properties tab
(itemized display).

or,

in the tree, click on any object (project, controller, plant) which the point belongs to,
and which is in grid display.

357 EN2Z-0937GE51 R0518


EDITORS CARE

To modify values, enter desired values in the fields, and/or select/deselect desired
options.

Attributes Description User Address Point name (maximum of 18 alphanumeric characters)


assigned to a point for operator use in locating and
commanding the point. Example: pseudo_tot. This name
and the descriptor further define the point. This name
must be unique within a controller.

User addresses must include one non-digit character and


cannot include Tabs, double quotes, ?, *, or space
characters. All other ASCII characters are allowable (A-
Z, 0-9, +, -, _, etc). For example, 12A is a valid user
address, but 12 is not.

Controller Name Name of controller where the point is assigned. This


assignment is done during plant attachment.
Plant Info Name of plant.

Point Role Point Role created via an external tool like Win EDS. The
point role can be edited.

Point ID Point ID created via an external tool like Win EDS.

Point Subtype None.

Engineering Unit List of choices displays engineering units with ID, unit,
and format.

To add and change units in the list, open the


Miscellaneous Text Editor by clicking the dotted button
on the right (see Miscellaneous Text Editor chapter)

Descriptor Supplemental point information (maximum of 32


characters). Each Excel Controller has a unique set of
descriptors (64 for Ver. 1.2 Controllers; 255 for Ver 1.3
and greater Controllers) that can be assigned to its user
addresses to further describe them. Example: user
address “pseudo_tot” can have a descriptor of “West
wing pseudo totalizer” to help define its location.

List of choices displays descriptors with ID and text.


To add and change descriptors in the list, open the
Miscellaneous Text Editor by clicking the dotted button
on the right (see Miscellaneous Text Editor chapter).

Operator Access Level Access level (1 through 4) that an operator must have to
modify point data via an operator terminal. For example,
if a point has an Operator Access Level of 2, only
operators with Access Level 2 and higher can change
point attributes.

Write Protect Priority Prevent lower-level operators from changing point


attributes that a higher-level operator changed. For
example, if a point has an Access attribute of 2 and an
operator with Access Level 3 changes an attribute,
software restricts future changes to operators with at
least Level 3 access. This protection prevents any Level
1 operators from overwriting higher-level operator
changes. Display only; always defaults to No (0).

Scaling Factor Amount of measured unit per incoming transition (0


through 9,999,999).

Interval Limit Number of transitions for software to count (0.0 through


99,999,999.9) before generating an alarm.

EN2Z-0937GE51 R0518 358


CARE EDITORS

Critical Alarm Type Whether the point alarm condition is critical or not.
Critical alarms display on the central PC when they
occur. Noncritical alarms do not display; software only
writes them to the alarm printer and alarm history file.

Suppress Alarm Whether or not software should suppress alarm


messages for changes in Fixed Mode and exceeding the
alarm and warning limits.

Hide Point Whether the point is visible or hidden. If a point is hidden,


it will not be displayed to the user when performing
online wildcard search on a central (only for controller
OS greater than Ver. 2.0).

Comment Allows the input of a comment

359 EN2Z-0937GE51 R0518


EDITORS CARE

Totalizer Point

Purpose Display and/or modify the attributes for the selected totalizer input point.

Procedure In the tree, click desired point to display current values on the right Properties tab
(itemized display).

or,

in the tree, click on any object (project, controller, plant) which the point belongs to,
and which is in grid display.

To modify values, edit desired values in the fields, and/or select/deselect desired
options.

Attributes Description User Address Point name (maximum of 18 alphanumeric characters)


assigned to a point for operator use in locating and
commanding the point. Example: TOT1. This name and
the descriptor further define the point. This name must
be unique within a controller.

User addresses must include one non-digit character and


cannot include Tabs, double quotes, ?, *, or space
characters. All other ASCII characters are allowable (A-
Z, 0-9, +, -, _, etc). For example, 12A is a valid user
address, but 12 is not.

IMPORTANT

EN2Z-0937GE51 R0518 360


CARE EDITORS

Note that the max. length of the user address for Lon
points should not exceed 18 characters (see Lon point
attribute).

Behind the user address field the bus type (IP bus or
LON-bus) where the point resides, is displayed.

Technical Address Internal six-digit number that defines and locates a point
in the system. The number is composed of three pairs
representing controller number (0-30), module number
(1-16), and terminal number (1-12). Example: 010310
meaning Controller 1, Module 3, terminal 10. Operators
use the User Address to refer to points.

To change the technical address see the Teminal


Assignment Function chapter.

Controller Name Name of controller where the point is assigned. This


assignment is done during plant attachment.

Plant Info Name of plant.

Point Role Point Role created via an external tool like Win EDS. The
point role can be edited.

Point ID Point ID created via an external tool like Win EDS.

Point Subtype Type of point. List of choices depends on module type


where the point is assigned.

Lon Point Define whether the datapoint should be a LON point.


Select from the list under:

NV-Input
Creates input NV.

NV-Output
Creates output NV.

NV-Input & Output


Creates both, input and output NV.

361 EN2Z-0937GE51 R0518


EDITORS CARE

Manual Mapping
Provides selection of this datapoint for mapping to NVs in
the NV-Editor.

NV Type Define the NV-type for the LON point. From the Input
and/or Output drop-down lists select desired type.

VCT Displays whether or not a value conversion table (VCT)


is assigned to the NV-Input Type or NV-Output Type.

Engineering Unit List of choices displays engineering units with ID, unit,
and format.

To add and change units in the list, open the


Miscellaneous Text Editor by clicking the dotted button
on the right (see Miscellaneous Text Editor chapter)

Descriptor Supplemental point information (maximum of 32


characters). Each Excel Controller has a unique set of
descriptors (64 for Ver. 1.2 Controllers; 255 for Ver 1.3
and greater Controllers) that can be assigned to its user
addresses to further describe them. Example: user
address “TOT1” can have a descriptor of “West Wing
totalizer” to help define its location.
List of choices displays descriptors with ID and text.
To add and change descriptors in the list, open the
Miscellaneous Text Editor by clicking the dotted button
on the right (see Miscellaneous Text Editor chapter).

Operator Access Level Access level (1 through 4) that an operator must have to
modify point data via an operator terminal. For example,
if a point has an Operator Access Level of 2, only
operators with Access Level 2 and higher can change
point attributes.

Write Protect Priority Prevent lower-level operators from changing point


attributes that a higher-level operator changed. For
example, if a point has an Access attribute of 2 and an
operator with Access Level 3 changes an attribute,
software restricts future changes to operators with at
least Level 3 access. This protection prevents any Level
1 operators from overwriting higher-level operator
changes. Default is 0. Valid range is 0 to 255.

Scaling Factor Amount of measured unit per incoming transition (0.0


through 100,000,000.0; the number of decimal places
depends on the selected engineering unit).

Interval Limit Number of transitions for software to count (0 through


99,999,999) before generating an alarm.

Critical Alarm Type Whether the point alarm condition is critical or not.
Critical alarms display on the central PC when they
occur. Noncritical alarms do not display; software only
writes them to the alarm printer and alarm history file.

Suppress Alarm Whether or not software should suppress alarm


messages for changes in Fixed Mode and exceeding the
alarm and warning limits.

Hide Point Whether the point is visible or hidden. If a point is hidden,


it will not be displayed to the user when performing
online wildcard search on a central (only for controller
OS greater than Ver. 2.0).

Comment Allows the input of a comment

EN2Z-0937GE51 R0518 362


CARE EDITORS

Analog and Digital Flag Points

Analog and digital flags cannot and have not to be edited, except by entering a
comment.

363 EN2Z-0937GE51 R0518


EDITORS CARE

BACnet Points

Analog Points

Analog Input Point

Purpose Display and/or modify the attributes of the selected analog output point.

Procedure In the tree, click desired point to display current values on the right Properties tab
(itemized display).

or,

in the tree, click on any object (project, controller, plant) which the point belongs to,
and which is in grid display.

EN2Z-0937GE51 R0518 364


CARE EDITORS

To modify values, enter desired values in the fields, and/or select respectively
deselect desired options.

Attributes Description Datapoint Name Point name (maximum of 40 alphanumeric characters)


assigned to a point for operator use in locating and
commanding the point. This name must be unique within
a controller.

Point names must include one non-digit character and


cannot include Tabs, double quotes, ?, *, or space
characters. All other ASCII characters are allowable (A-
Z, 0-9, +, -, _, etc). For example, 12A is a datapoint
name, but 12 is not.

IMPORTANT
Note that the max. length of the datapoint name for Lon
points should not exceed 18 characters (see Lon point
attribute).

BACnet Object Type Displays the BACnet object type.

BACnet Object ID Displays the BACnet object type ID.

BACnet Instance number Displays the BACnet intance number.

Lon Point (Applies to FALCON controller only)


Define whether the datapoint should be a LON point or
not. List of choices displays:

NV-Input
Creates input NV.

Manual Mapping
Provides selection of this datapoint for mapping to NVs in
the NV-Editor.

Input NV Define the NV-type for the LON point.

Engineering Unit List of choices displays engineering units with ID and


unit.

Descriptor Supplemental point information. Each project and/or


plant has a unique set of descriptors that can be
assigned to its datapoint names to further describe them.

List of choices displays descriptors with ID and text.


To add and change descriptors in the list, open the
Miscellaneous Text Editor by clicking the dotted button
on the right (see Miscellaneous Text Editor chapter).

Alarm Text Alarm text that displays on point alarm. List of choices
displays alarm texts with ID and text.

To add and change alarm texts in the list, open the


Miscellaneous Text Editor by clicking the dotted button
on the right (see Miscellaneous Text Editor chapter).

IO Configuration To configure the connected terminal. List of choices


displays NTC, PT100 Type F, etc.

Analog input and output points must be configured prior


to their assignment to a particular terminal on a module.
By selecting a configuration such as NTC, PT100 Type
F, etc., the configuration properties of the datapoint are
automatically set.

365 EN2Z-0937GE51 R0518


EDITORS CARE

Configure the datapoint before you assign the datapoint


to a terminal on the terminal assignment tab. Otherwise
you need to rework the configuration properties
manually.

Characteristic Assign and/or build a characteristic (conversion table) if


the datapoint is to be mapped to a NV (see Lon point
attribute) and the engineering units of both do not match,
for example, the NV has °C and the datapoint has °F. To
create a characteristic, open the Characteristics
dialogbox by clicking the dotted button on the right (see
Create and Assign Characteristic to BACnet Point
section).

Read Access Determine whether the user can read datapoint values
Write Access respectively write values to the datapoint in the Web
Interface.

All users having a user level equal or higher than the


assigned read access respectively write access of the
datapoint, will have this access right enabled in the Web
Interface, all others will not (for further details, please
refer to the User Access Manager section).

Notification Class Enable alarming for the datapoint by selecting a


notification class with a given priority. By default, the
following notification classes with descending priority
can be selected:

- Urgent
- High
- Low
- Journal

Those default notification classes are especially


designed for the alarming to the EBI central (for
information on notification classes to be used for 3rd party
BACnet clients, please refer to the Notification Class
Manager section)

Each recipient which is assigned to this notification class


will receive the datapoint alarm triggered by the selected
notification. But, alarms will only be generated for the
enabled transitions (To-Normal, To-OffNormal, and/or
To-Fault) of a recipient. Each enabled transition will be
propagated with the selected notification. (For further
details please refer to the Notification Class Manager
section).

This connection has not to be mixed up with the


transitions selected under Reporting (see Reporting
description in the following).

Notify Type If the notification class Urgent, High, or Low has been
selected, the notify type Alarm must be used.

Suppress Alarm Whether or not software should suppress alarm


messages for changes in Fixed Mode and exceeding the
limits.

Alarm Delay Defines the time delay with which a ´To-Off-Normal`


(EAGLE and FALCON controllers) transition and a ´To-
Normal` transition (FALCON controller) will be set off.

Alarm Delay Normal Defines the time delay with which a ´To-Normal`
transition will be set off.

EN2Z-0937GE51 R0518 366


CARE EDITORS

High Limit Reporting If a high limit is exceeded and this condition remains
present for at least the defined alarm delay (time), than
an alarm of event type ´To-Off-Normal` is set off.
Define whether a high limit exceeding should be reported
or not.

Low Limit Reporting If the present value falls below the low limit and this
condition remains present for at least the defined alarm
delay (time), than an alarm of event type ´To-Off-Normal`
is set off.
Defines whether a low limit exceeding should be reported
or not.

Deadband Define the value of the deadband in order to set off an


alarm of event type ´To-Normal`. For this, the present
value must, for at least the defined alarm delay (time),
remain within the range:
Low limit plus deadband and high limit minus deadband.

Reporting Define which transition type ((To-Normal, To-OffNormal,


and/or To Fault) will be tracked by timestamping in the
Web Interface.

Point Role Point Role created via an external tool like XL Toolkit and
imported into CARE. The point role is selected from XL
Toolkit database.

Change of Value Define the change of the value increment (COV).


Increment The COV increment specifies the minimum change in
present value that causes the controller sending the
present value to the Web Interface or other recipients on
the BACnet bus (e.g. EBI).

Min. Present Value Define the minimum value of the graphical bar display in
the EBI. Defaults to the Low Limit Reporting value.

Max. Present Value Define the maximum value of the graphical bar display in
the EBI. Defaults to the High Limit Reporting value.

Communication failure (applies to EAGLE controller only)


In case of communication failure or application stop, the
device is commanded to one of the following positions if
the controller does not deliver a value (no response).

- Last Valid Value


device is commanded to the last valid position

- Safety Value
device is commanded to the value entered in Safety
Value

Safety Value (applies to EAGLE controller only)


Enter the safety value if Safety Value is selected under
Communication Failure

(applies to EAGLE controller only)

Sensor offset (applies to EAGLE controller only)


Enter the sensor offset.

Acked Transitions Allows observing the acknowledgement behavior of a


user for To-Off-Normal and To-Fault transition events of
the datapoint. CARE checks whether a transition event
has been acknowledged or not. If a transition event has
not been acknowledged within a definable delay time, an

367 EN2Z-0937GE51 R0518


EDITORS CARE

alarm based on an event enrollment (event enrollment


alarm) is sent to a supervisory recipient, for example EBI.

Click Observe button to display the Event Enrollment –


Acked Transitions dialog box.

In the Event Enrollment – Acked Transitions dialog box,


do the following:

EN2Z-0937GE51 R0518 368


CARE EDITORS

1. In the Name field, change the default name if


desired.
2. In the Description field, enter a meaningful
description if desired.
3. In the Event Type field, note the event type of
the event enrollment object is ´change of
bitstring`.
4. Under Event Parameters, select the transition
event(s) that should be checked for
acknowledgement. The List of Values shows the
possible logical values (checked=true,
unchecked=false, CARE verifies with negative
logic for the false condition) resulting from the
comparison of the selected transition event(s)
and the underlying bitstring mask. An event
enrollment alarm will be sent, if the transition
event will not be acknowledged within the delay
time.
5. In the Alarm Delay field, enter an alarm delay in
sec. The event enrollment alarm will be sent if the
transition event has not been acknowledged
within the delay time.
6. From the Notify Type drop-down listbox, select
the notify type.
7. From the Notification Class drop-down listbox,
select the notification class that defines the
supervisory recipient to which the event
enrollment alarm is sent after an
unacknowledged transition.
8. Under Reporting, check the transition event(s)
that should cause an event notification to the
supervisory recipient.

NOTE:
These settings refer to the event enrollment itself
not to the intrinsic reporting properties of the
datapoint:
To-Off-Normal = event notification is sent if the
acknowledgement is missing within the alarm
delay;
Back-To-Normal = event notification is sent if the
acknowledgement is sent after the alarm delay
has been expired.

If you do not check at least one transition event


and one event parameter, the observation is not
enabled.

9. After entering the values, click OK. On the


Properties tab of the datapoint, the Enabled
check box is checked.

Status Flags Allows observing status flags conditions. To enable


observing status flag conditions, click Observe button to
display the Event Enrollment – Status Flags dialog box.

369 EN2Z-0937GE51 R0518


EDITORS CARE

In the Event Enrollment – Status Flags dialog box, do the


following:

1. In the Name field, change the default name if


desired.
2. In the Description field, enter a meaningful
description if desired.
3. In the Event Type field, note that the event type
of the event enrollment object is ´change of
state`.

EN2Z-0937GE51 R0518 370


CARE EDITORS

4. Under Status Flags, select the flags of which


conditions should be observed. The List of
Values shows the possible logical values
(checked=true, unchecked=false) resulting from
the comparison of the selected status flags and
the underlying bitstring mask.
5. In the Alarm Delay field, enter an alarm delay in
sec. An event enrollment alarm will be sent for
each status flag that is enabled (checked) within
the alarm delay time.
6. From the Notify Type drop-down listbox, select
the notify type.
7. From the Notification Class drop-down listbox,
select the notification class that defines the
supervisory recipient to which the event
enrollment alarm is sent.
8. Under Transition Events, check the transition
event(s) that should cause an event notification to
the supervisory recipient.

NOTE:
These settings refer to the event enrollment itself
not to the intrinsic reporting properties of the
datapoint:
To-Off-Normal = event notification is sent if a
status flag is enabled within the alarm delay;
To-Normal = event notification is sent if a status
flag is disabled after the alarm delay has been
expired.

If you do not check at least one transition event


and one event parameter, the observation is not
enabled.

9. After entering the values, click OK. On the


Properties tab of the datapoint, the Enabled
check box is checked.

Warning Limits Allows defining warning limits for observing the present
value and sending event enrollment alarms in case the
present value increases or decreases the warning limits.
To define warning limits, click Define button to display
the Event Transitions dialog box.

371 EN2Z-0937GE51 R0518


EDITORS CARE

In the Warning Limits for Present Value dialog box, do


the following:

EN2Z-0937GE51 R0518 372


CARE EDITORS

1. In the Name field, change the default name if


desired.
2. In the Description field, enter a meaningful
description if desired.
3. In the Event Type field, note that the event type
of the event enrollment object is ´change of
state`.
4. In the High Warning Limit field, enter the high
warning limit value.
5. In the Low Warning Limit field, enter the low
warning limit value.

NOTE: The warning limits can be below or above


the high and low limit reporting values.

6. In the Deadband field, enter a deadband value.


This defines an additional trigger to set off an
alarm. The event enrollment alarm is sent if the
following condition is true:
present value must, for at least the defined alarm
delay (time), remain within the range: Low limit
plus deadband and high limit minus deadband.
7. In the Alarm Delay field, enter an alarm delay in
sec. The even enrollment alarm is sent if the
present value still increases or decreases the
warning limits after the time entered here has
been elapsed.
7. From the Notify Type drop-down listbox, select
the notify type.
8. From the Notification Class drop-down listbox,
select the notification class that defines the
supervisory recipient to which the event
enrollment alarm is sent.
9. Under Reporting, check the transition event(s)
that should cause an event notification to the
supervisory recipient.

NOTE:
These settings refer to the event enrollment itself
not to the intrinsic reporting properties of the
datapoint:
To-Off-Normal = event notification is sent if the
present value exceeds or falls below the high or
low warning limits within the alarm delay;
Back-To-Normal = event notification is sent if the
present value is within the high or low warning
limits after the alarm delay has been expired.

If you do not check at least one transition event


and one event parameter, the observation is not
enabled.

10. After entering the values, click OK. On the


Properties tab of the datapoint, the Enabled
check box is checked.

373 EN2Z-0937GE51 R0518


EDITORS CARE

Analog Output Point

Purpose Display and/or modify the attributes of the selected analog output point.

Procedure In the tree, click desired point to display current values on the right Properties tab
(itemized display).

or,

in the tree, click on any object (project, controller, plant) which the point belongs to,
and which is in grid display.

To modify values, enter desired values in the fields, and/or select respectively
deselect desired options.

Attributes Description Datapoint Name Point name (maximum of 40 alphanumeric characters)


assigned to a point for operator use in locating and

EN2Z-0937GE51 R0518 374


CARE EDITORS

commanding the point. This name must be unique within


a controller.

Point names must include one non-digit character and


cannot include Tabs, double quotes, ?, *, or space
characters. All other ASCII characters are allowable (A-
Z, 0-9, +, -, _, etc). For example, 12A is a datapoint
name, but 12 is not.

IMPORTANT
Note that the max. length of the datapoint name for Lon
points should not exceed 18 characters (see Lon point
attribute).

BACnet Object Type Displays the BACnet object type.

BACnet Object ID Displays the BACnet object type ID.

BACnet Instance number Displays the BACnet intance number.

Lon Point (Applies to FALCON controller only)


Define whether the datapoint should be a LON point or
not. List of choices displays:

NV-Input
Creates output NV.

Manual Mapping
Provides selection of this datapoint for mapping to NVs in
the NV-Editor.

Output NV Define the NV-type for the LON point.

Reliability status on the Excel Web HTML Interface:

In order to make sure that the Reliability property for the


present value works properly, the service type of the
point must be set to Acknowledged (Ackd). With
acknowledged service, controller - I/O module
disconnections are indicated by the relevant reliability
´No Sensor` or ´No Output`. Note, that if a large number
of outputs (e.g. all outputs of mutiple I/O modules) are
set to acknowledged servcice, the performance on the
LON bus may drastically decrease (see "Change Service
Type for Excel Web Datapoints" section).

Engineering Unit List of choices displays engineering units with ID and


unit.

NOTE:
This option must be selected before the point is bound to
the module. After the binding, the setting cannot be
changed.

Descriptor Supplemental point information. Each project and/or


plant has a unique set of descriptors that can be
assigned to its datapoint names to further describe them.

List of choices displays descriptors with ID and text.


To add and change descriptors in the list, open the
Miscellaneous Text Editor by clicking the dotted button
on the right (see Miscellaneous Text Editor chapter).

Alarm Text Alarm text that displays on point alarm. List of choices
displays alarm texts with ID and text.

375 EN2Z-0937GE51 R0518


EDITORS CARE

To add and change alarm texts in the list, open the


Miscellaneous Text Editor by clicking the dotted button
on the right (see Miscellaneous Text Editor chapter).

IO Configuration To configure the connected terminal. List of choices


displays NTC, PT100 Type F, etc.

Analog input and output points must be configured prior


to their assignment to a particular terminal on a module.
By selecting a configuration such as NTC, PT100 Type
F, etc., the configuration properties of the datapoint are
automatically set.

Configure the datapoint before you assign the datapoint


to a terminal on the terminal assignment tab. Otherwise
you need to rework the configuration properties
manually.

Characteristic Assign and/or build a characteristic (conversion table) if


the datapoint is to be mapped to a NV (see Lon point
attribute) and the engineering units of both do not match,
for example, the NV has °C and the datapoint has °F. To
create a characteristic, open the Characteristics
dialogbox by clicking the dotted button on the right (see
Create and Assign Characteristic to BACnet Point
section).

Read Access Determine whether the user can read datapoint values
Write Access respectively write values to the datapoint in the Web
Interface.

All users having a user level equal or higher than the


assigned read access respectively write access of the
datapoint, will have this access right enabled in the Web
Interface, all others will not (for further details, please
refer to the User Access Manager section).

Notification Class Enable alarming for the datapoint by selecting a


notification class with a given priority. By default the
following notification classes with descending priority can
be selected:

- Urgent
- High
- Low
- Journal

Those default notification classes are especially


designed for the alarming to the EBI central (for
information on notification classes to be used for 3rd party
BACnet clients, please refer to the Notification Class
Manager section)

Each recipient which is assigned to this notification class


will receive the datapoint alarm triggered by the selected
notification. But, alarms will only be generated for the
enabled transitions (To-Normal, To-OffNormal, and/or
To-Fault) of a recipient. Each enabled transition will be
propagated with the selected notification. (For further
details please refer to the Notification Class Manager
section).

This connection has not to be mixed up with the


transitions selected under Reporting (see Reporting
description in the following).

EN2Z-0937GE51 R0518 376


CARE EDITORS

Notify Type If the notification class Urgent, High, or Low has been
selected, the notify type Alarm must be used.

Suppress Alarm Whether or not software should suppress alarm


messages for changes in Fixed Mode and exceeding the
limits.

Alarm Delay Defines the time delay with which a ´To-Off-Normal`


(EAGLE and FALCON controllers) transition and a ´To-
Normal` transition (FALCON controller) will be set off.

Alarm Delay Normal Defines the time delay with which a ´To-Normal`
transition will be set off.

High Limit Reporting If a high limit is exceeded and this condition remains
present for at least the defined alarm delay (time), than
an alarm of event type ´To-Off-Normal` is set off.
Define whether a high limit exceeding should be reported
or not.

Low Limit Reporting If the present value falls below the low limit and this
condition remains present for at least the defined alarm
delay (time), than an alarm of event type ´To-Off-Normal`
is set off.
Defines whether a low limit exceeding should be reported
or not.

Deadband Define the value of the deadband in order to set off an


alarm of event type ´To-Normal`. For this, the present
value must, for at least the defined alarm delay (time),
remain within the range:
Low limit plus deadband and high limit minus deadband.

Reporting Define which transition type ((To-Normal, To-OffNormal,


and/or To Fault) will be tracked by timestamping in the
Web Interface.

Point Role Point Role created via an external tool like XL Toolkit and
imported into CARE. The point role is selected from XL
Toolkit database.

Change of Value Define the change of the value increment (COV).


Increment The COV increment specifies the minimum change in
present value that causes the controller sending the
present value to the Web Interface or other recipients on
the BACnet bus (e.g. EBI).

Relinquish Default Define the value that will be written to present value, if all
values in the priority list are invalid.

Min. Present Value Define the minimum value of the graphical bar display in
the EBI. Defaults to the Low Limit Reporting value.

Max. Present Value Define the maximum value of the graphical bar display in
the EBI. Defaults to the High Limit Reporting value.

Direct/Reverse (applies to EAGLE controller only)


Selection of the polarity which indicates the relationship
between the physical state of the input and the logical
state represented by the present value. If the polarity is
NORMAL, then the ACTIVE state of the present value is
also the ACTIVE or ON state of the physical input. If the
polarity is REVERSE, then the ACTIVE state of the

377 EN2Z-0937GE51 R0518


EDITORS CARE

present value is the INACTIVE or OFF state of the


physical Input.

Polarity Present Value Physical State of Input Physical State of Device


NORMAL INACTIVE OFF or INACTIVE not running
NORMAL ACTIVE ON or ACTIVE running
REVERSE INACTIVE ON or ACTIVE not running
REVERSE ACTIVE OFF or INACTIVE running

Communication failure In case of communication failure or application stop, the


device is commanded to one of the following positions if
the controller does not deliver a value (no response).

-0%
- 50 %
- 100 %
device is commanded to the selected percentage value

- Last Valid Value


device is commanded to the last valid position

The safety position is affected by the characteristic


used for the controller modules. For particular
characteristics there is no linear correlation
between percentage value and voltage output:

DP Listbox Characteristic Safety position (%)


Type number 0 50 100
in DP in
values Volts

AO 1..10 User defined 0 5 10


AO 9 0-100%=2-10V -25 37.5 0 5 10
100
AO 10 100-0%=2-10V 125 62.5 0 0 5 10
AO 12 LINEAR GRAPH 0 50 100 0 5 10
AO 24 0-10V=0-100% 0 50 100 0 5 10
AO 25 2-10V=0-100% 0 50 100 2 6 10
DO -- DO on AO OFF / ON 0 10
MOT 12 LINEAR GRAPH 0 50 100 0 5 10

NOTE: The user-defined characteristics 1 through 10 can be changed; in this


context, characteristics 3, 4, 5, 6, 9, 10 are pre-defined by CARE (default
characteristics) and characteristics 1 and 2 are not pre-defined. The
default characteristics 3 through 6 are pressure input characteristics
which should not be used for an analog output.

In general, for the user-defined characteristics 1 through 10, the safety


positions 0%, 50%, 100% do always mean 0V, 5V, 10V; in this context
the datapoint values for characteristics 9 and 10 are deviant.

Time to Open (applies to 3pos point of EAGLE controller only)


Defines the time in sec the motor should need to open
the controlled device when using a 3 Position Output

Time to Close (applies to 3pos point EAGLE controller only)


Defines the time in sec the motor should need to close
the controlled device when using a 3 Position Output

EN2Z-0937GE51 R0518 378


CARE EDITORS

With Switches Define whether the point transmittes a continous signa


3 Position Output and is on a board with switches or if the point is a 3
position output.

NOTE:
These options must be selected before the point is
bound to the module. After the binding, the settings
cannot be changed.

Acked Transitions Allows observing the acknowledgement behavior of a


user for To-Off-Normal and To-Fault transition events of
the datapoint. CARE checks whether a transition event
has been acknowledged or not. If a transition event has
not been acknowledged within a definable delay time, an
alarm based on an event enrollment (event enrollment
alarm) is sent to a supervisory recipient, for example EBI.

Click Observe button to display the Event Enrollment –


Acked Transitions dialog box.

379 EN2Z-0937GE51 R0518


EDITORS CARE

In the Event Enrollment – Acked Transitions dialog box,


do the following:

EN2Z-0937GE51 R0518 380


CARE EDITORS

1. In the Name field, change the default name if


desired.
2. In the Description field, enter a meaningful
description if desired.
3. In the Event Type field, note the event type of
the event enrollment object is ´change of
bitstring`.
4. Under Event Parameters, select the transition
event(s) that should be checked for
acknowledgement. The List of Values shows the
possible logical values (checked=true,
unchecked=false, CARE verifies with negative
logic for the false condition) resulting from the
comparison of the selected transition event(s)
and the underlying bitstring mask. An event
enrollment alarm will be sent, if the transition
event will not be acknowledged within the delay
time.
5. In the Alarm Delay field, enter an alarm delay in
sec. The event enrollment alarm will be sent if the
transition event has not been acknowledged
within the delay time.
6. From the Notify Type drop-down listbox, select
the notify type.
7. From the Notification Class drop-down listbox,
select the notification class that defines the
supervisory recipient to which the event
enrollment alarm is sent after an
unacknowledged transition.
8. Under Reporting, check the transition event(s)
that should cause an event notification to the
supervisory recipient.

NOTE:
These settings refer to the event enrollment itself
not to the intrinsic reporting properties of the
datapoint:
To-Off-Normal = event notification is sent if the
acknowledgement is missing within the alarm
delay;
Back-To-Normal = event notification is sent if the
acknowledgement is sent after the alarm delay
has been expired.

If you do not check at least one transition event


and one event parameter, the observation is not
enabled.

9. After entering the values, click OK. On the


Properties tab of the datapoint, the Enabled
check box is checked.

Status Flags Allows observing status flags conditions. To enable


observing status flag conditions, click Observe button to
display the Event Enrollment – Status Flags dialog box.

381 EN2Z-0937GE51 R0518


EDITORS CARE

In the Event Enrollment – Status Flags dialog box, do the


following:

1. In the Name field, change the default name if


desired.
2. In the Description field, enter a meaningful
description if desired.
3. In the Event Type field, note that the event type
of the event enrollment object is ´change of
state`.

EN2Z-0937GE51 R0518 382


CARE EDITORS

4. Under Status Flags, select the flags of which


conditions should be observed. The List of
Values shows the possible logical values
(checked=true, unchecked=false) resulting from
the comparison of the selected status flags and
the underlying bitstring mask.
5. In the Alarm Delay field, enter an alarm delay in
sec. An event enrollment alarm will be sent for
each status flag that is enabled (checked) within
the alarm delay time.
6. From the Notify Type drop-down listbox, select
the notify type.
7. From the Notification Class drop-down listbox,
select the notification class that defines the
supervisory recipient to which the event
enrollment alarm is sent.
8. Under Reporting, check the transition event(s)
that should cause an event notification to the
supervisory recipient.

NOTE:
These settings refer to the event enrollment itself
not to the intrinsic reporting properties of the
datapoint:
To-Off-Normal = event notification is sent if a
status flag is enabled within the alarm delay;
To-Normal = event notification is sent if a status
flag is disabled after the alarm delay has been
expired.

If you do not check at least one transition event


and one event parameter, the observation is not
enabled.

9. After entering the values, click OK. On the


Properties tab of the datapoint, the Enabled
check box is checked.

Warning Limits Allows defining warning limits for observing the present
value and sending event enrollment alarms in case the
present value increases or decreases the warning limits.
To define warning limits, click Define button to display
the Event Transitions dialog box.

383 EN2Z-0937GE51 R0518


EDITORS CARE

In the Warning Limits for Present Value dialog box, do


the following:

EN2Z-0937GE51 R0518 384


CARE EDITORS

1. In the Name field, change the default name if


desired.
2. In the Description field, enter a meaningful
description if desired.
3. In the Event Type field, note that the event type
of the event enrollment object is ´change of
state`.
4. In the High Warning Limit field, enter the high
warning limit value.
5. In the Low Warning Limit field, enter the low
warning limit value.

NOTE: The warning limits can be below or above


the high and low limit reporting values.

6. In the Deadband field, enter a deadband value.


This defines an additional trigger to set off an
alarm. The event enrollment alarm is sent if the
following condition is true:
present value must, for at least the defined alarm
delay (time), remain within the range: Low limit
plus deadband and high limit minus deadband.
7. In the Alarm Delay field, enter an alarm delay in
sec. The even enrollment alarm is sent if the
present value still increases or decreases the
warning limits after the time entered here has
been elapsed.
7. From the Notify Type drop-down listbox, select
the notify type.
8. From the Notification Class drop-down listbox,
select the notification class that defines the
supervisory recipient to which the event
enrollment alarm is sent.
9. Under Reporting, check the transition event(s)
that should cause an event notification to the
supervisory recipient.

NOTE:
These settings refer to the event enrollment itself
not to the intrinsic reporting properties of the
datapoint:
To-Off-Normal = event notification is sent if the
present value exceeds or falls below the high or
low warning limits within the alarm delay;
Back-To-Normal = event notification is sent if the
present value is within the high or low warning
limits after the alarm delay has been expired.

If you do not check at least one transition event


and one event parameter, the observation is not
enabled.

10. After entering the values, click OK. On the


Properties tab of the datapoint, the Enabled
check box is checked.

385 EN2Z-0937GE51 R0518


EDITORS CARE

Analog Value Point

Purpose Display and/or modify the attributes of the selected analog value point.

Procedure In the tree, click desired point to display current values on the right Properties tab
(itemized display).

or,

in the tree, click on any object (project, controller, plant) which the point belongs to,
and which is in grid display.

To modify values, enter desired values in the fields, and/or select respectively
deselect desired options.

Attributes Description Datapoint Name Point name (maximum of 40 alphanumeric characters)


assigned to a point for operator use in locating and

EN2Z-0937GE51 R0518 386


CARE EDITORS

commanding the point. This name must be unique within


a controller.

Point names must include one non-digit character and


cannot include Tabs, double quotes, ?, *, or space
characters. All other ASCII characters are allowable (A-
Z, 0-9, +, -, _, etc). For example, 12A is a datapoint
name, but 12 is not.

IMPORTANT
Note that the max. length of the datapoint name for Lon
points should not exceed 18 characters (see Lon point
attribute).

BACnet Object Type Displays the BACnet object type.

BACnet Object ID Displays the BACnet object type ID.

BACnet Instance number Displays the BACnet intance number.

Engineering Unit List of choices displays engineering units with ID and


unit.

Descriptor Supplemental point information. Each project and/or


plant has a unique set of descriptors that can be
assigned to its datapoint names to further describe them.

List of choices displays descriptors with ID and text.


To add and change descriptors in the list, open the
Miscellaneous Text Editor by clicking the dotted button
on the right (see Miscellaneous Text Editor chapter).

Alarm Text Alarm text that displays on point alarm. List of choices
displays alarm texts with ID and text.

To add and change alarm texts in the list, open the


Miscellaneous Text Editor by clicking the dotted button
on the right (see Miscellaneous Text Editor chapter).

Read Access Determine whether the user can read datapoint values
Write Access respectively write values to the datapoint in the Web
Interface.

All users having a user level equal or higher than the


assigned read access respectively write access of the
datapoint, will have this access right enabled in the Web
Interface, all others will not (for further details, please
refer to the User Access Manager section).

Notification Class Enable alarming for the datapoint by selecting a


notification class with a given priority. By default the
following notification classes with descending priority can
be selected:

- Urgent
- High
- Low
- Journal

Those default notification classes are especially


designed for the alarming to the EBI central (for
information on notification classes to be used for 3rd party
BACnet clients, please refer to the Notification Class
Manager section)

Each recipient which is assigned to this notification class


will receive the datapoint alarm triggered by the selected

387 EN2Z-0937GE51 R0518


EDITORS CARE

notification. But, alarms will only be generated for the


enabled transitions (To-Normal, To-OffNormal, and/or
To-Fault) of a recipient. Each enabled transition will be
propagated with the selected notification. (For further
details please refer to the Notification Class Manager
section).

This connection has not to be mixed up with the


transitions selected under Reporting (see Reporting
description in the following).

Notify Type If the notification class Urgent, High, or Low has been
selected, the notify type Alarm must be used.

Suppress Alarm Whether or not software should suppress alarm


messages for changes in Fixed Mode and exceeding the
limits.

Alarm Delay Defines the time delay with which a ´To-Off-Normal`


(EAGLE and FALCON controllers) transition and a ´To-
Normal` transition (FALCON controller) will be set off.

Alarm Delay Normal Defines the time delay with which a ´To-Normal`
transition will be set off.
High Limit Enable If a high limit is exceeded and this condition remains
present for at least the defined alarm delay (time), than
an alarm of event type ´To-Off-Normal` is set off.
Define whether a high limit exceeding should be
considered or not.

Low Limit Enable If the present value falls below the low limit and this
condition remains present for at least the defined alarm
delay (time), than an alarm of event type ´To-Off-Normal`
is set off.
Defines whether a low limit exceeding should be
considered or not.

Deadband Define the value of the deadband in order to set off an


alarm of event type ´To-Normal`. For this, the present
value must, for at least the defined alarm delay (time),
remain within the range:
Low limit plus deadband and high limit minus deadband.

Reporting Define which transition type ((To-Normal, To-OffNormal,


and/or To Fault) will be tracked by timestamping in the
Web Interface.

Point Role Point Role created via an external tool like XL Toolkit and
imported into CARE. The point role is selected from XL
Toolkit database.

Change of Value Define the change of the value increment (COV).


Increment The COV increment specifies the minimum change in
present value that causes the controller sending the
present value to the Web Interface or other recipients on
the BACnet bus (e.g. EBI).

Relinquish Default Define the value that will be written to present value, if all
values in the priority list are invalid.

EOH/EOV Optimisation Check whether the datapoint should be optimized or not,


in case the datapoint is used as setpoint for energy
optimized heating or ventilation (EOH/EOV).

EN2Z-0937GE51 R0518 388


CARE EDITORS

Setpoint Enables the direct change (override) of the current


datapoint value in the web interface and the controller
HMI without the necessisity of setting the datapoint into
manual mode.

Acked Transitions Allows observing the acknowledgement behavior of a


user for To-Off-Normal and To-Fault transition events of
the datapoint. CARE checks whether a transition event
has been acknowledged or not. If a transition event has
not been acknowledged within a definable delay time, an
alarm based on an event enrollment (event enrollment
alarm) is sent to a supervisory recipient, for example EBI.

Click Observe button to display the Event Enrollment –


Acked Transitions dialog box.

In the Event Enrollment – Acked Transitions dialog box,


do the following:

389 EN2Z-0937GE51 R0518


EDITORS CARE

1. In the Name field, change the default name if


desired.
2. In the Description field, enter a meaningful
description if desired.
3. In the Event Type field, note the event type of
the event enrollment object is ´change of
bitstring`.
4. Under Event Parameters, select the transition
event(s) that should be checked for
acknowledgement. The List of Values shows the
possible logical values (checked=true,
unchecked=false, CARE verifies with negative
logic for the false condition) resulting from the
comparison of the selected transition event(s)
and the underlying bitstring mask. An event
enrollment alarm will be sent, if the transition
event will not be acknowledged within the delay
time.
5. In the Alarm Delay field, enter an alarm delay in
sec. The event enrollment alarm will be sent if the
transition event has not been acknowledged
within the delay time.
6. From the Notify Type drop-down listbox, select
the notify type.
7. From the Notification Class drop-down listbox,
select the notification class that defines the
supervisory recipient to which the event
enrollment alarm is sent after an
unacknowledged transition.
8. Under Reporting, check the transition event(s)
that should cause an event notification to the
supervisory recipient.

NOTE:
These settings refer to the event enrollment itself
not to the intrinsic reporting properties of the
datapoint:
To-Off-Normal = event notification is sent if the
acknowledgement is missing within the alarm
delay;
Back-To-Normal = event notification is sent if the
acknowledgement is sent after the alarm delay
has been expired.

If you do not check at least one transition event


and one event parameter, the observation is not
enabled.

9. After entering the values, click OK. On the


Properties tab of the datapoint, the Enabled
check box is checked.

Status Flags Allows observing status flags conditions. To enable


observing status flag conditions, click Observe button to
display the Event Enrollment – Status Flags dialog box.

EN2Z-0937GE51 R0518 390


CARE EDITORS

In the Event Enrollment – Status Flags dialog box, do the


following:

1. In the Name field, change the default name if


desired.
2. In the Description field, enter a meaningful
description if desired.
3. In the Event Type field, note that the event type
of the event enrollment object is ´change of
state`.

391 EN2Z-0937GE51 R0518


EDITORS CARE

4. Under Status Flags, select the flags of which


conditions should be observed. The List of
Values shows the possible logical values
(checked=true, unchecked=false) resulting from
the comparison of the selected status flags and
the underlying bitstring mask.
5. In the Alarm Delay field, enter an alarm delay in
sec. An event enrollment alarm will be sent for
each status flag that is enabled (checked) within
the alarm delay time.
6. From the Notify Type drop-down listbox, select
the notify type.
7. From the Notification Class drop-down listbox,
select the notification class that defines the
supervisory recipient to which the event
enrollment alarm is sent.
8. Under Reporting, check the transition event(s)
that should cause an event notification to the
supervisory recipient.

NOTE:
These settings refer to the event enrollment itself
not to the intrinsic reporting properties of the
datapoint:
To-Off-Normal = event notification is sent if a
status flag is enabled within the alarm delay;
To-Normal = event notification is sent if a status
flag is disabled after the alarm delay has been
expired.

If you do not check at least one transition event


and one event parameter, the observation is not
enabled.

9. After entering the values, click OK. On the


Properties tab of the datapoint, the Enabled
check box is checked.

Warning Limits Allows defining warning limits for observing the present
value and sending event enrollment alarms in case the
present value increases or decreases the warning limits.
To define warning limits, click Define button to display
the Event Transitions dialog box.

EN2Z-0937GE51 R0518 392


CARE EDITORS

In the Warning Limits for Present Value dialog box, do


the following:

393 EN2Z-0937GE51 R0518


EDITORS CARE

1. In the Name field, change the default name if


desired.
2. In the Description field, enter a meaningful
description if desired.
3. In the Event Type field, note that the event type
of the event enrollment object is ´change of
state`.
4. In the High Warning Limit field, enter the high
warning limit value.
5. In the Low Warning Limit field, enter the low
warning limit value.

NOTE: The warning limits can be below or above


the high and low limit reporting values.

6. In the Deadband field, enter a deadband value.


This defines an additional trigger to set off an
alarm. The event enrollment alarm is sent if the
following condition is true:
present value must, for at least the defined alarm
delay (time), remain within the range: Low limit
plus deadband and high limit minus deadband.
7. In the Alarm Delay field, enter an alarm delay in
sec. The even enrollment alarm is sent if the
present value still increases or decreases the
warning limits after the time entered here has
been elapsed.
7. From the Notify Type drop-down listbox, select
the notify type.
8. From the Notification Class drop-down listbox,
select the notification class that defines the
supervisory recipient to which the event
enrollment alarm is sent.
9. Under Reporting, check the transition event(s)
that should cause an event notification to the
supervisory recipient.

NOTE:
These settings refer to the event enrollment itself
not to the intrinsic reporting properties of the
datapoint:
To-Off-Normal = event notification is sent if the
present value exceeds or falls below the high or
low warning limits within the alarm delay;
Back-To-Normal = event notification is sent if the
present value is within the high or low warning
limits after the alarm delay has been expired.

If you do not check at least one transition event


and one event parameter, the observation is not
enabled.

10. After entering the values, click OK. On the


Properties tab of the datapoint, the Enabled
check box is checked.

EN2Z-0937GE51 R0518 394


CARE EDITORS

Binary Points

Binary Input Point

Purpose Display and/or modify the attributes of the selected binary input point.

Procedure In the tree, click desired point to display current values on the right Properties tab
(itemized display).

or,

in the tree, click on any object (project, controller, plant) which the point belongs to,
and which is in grid display.

To modify values, enter desired values in the fields, and/or select respectively
deselect desired options.

395 EN2Z-0937GE51 R0518


EDITORS CARE

Attributes Description Datapoint Name Point name (maximum of 40 alphanumeric characters)


assigned to a point for operator use in locating and
commanding the point. This name must be unique within
a controller.

Point names must include one non-digit character and


cannot include Tabs, double quotes, ?, *, or space
characters. All other ASCII characters are allowable (A-
Z, 0-9, +, -, _, etc). For example, 12A is a datapoint
name, but 12 is not.

IMPORTANT
Note that the max. length of the datapoint name for Lon
points should not exceed 18 characters (see Lon point
attribute).

BACnet Object Type Displays the BACnet object type.

BACnet Object ID Displays the BACnet object type ID.

BACnet Instance number Displays the BACnet intance number.

Lon Point (Applies to FALCON controller only)


Define whether the datapoint should be a LON point or
not. List of choices displays:

NV-Input
Creates input NV.

Manual Mapping
Provides selection of this datapoint for mapping to NVs in
the NV-Editor.

Input NV Define the NV-type for the LON point.

Active/Inactive Text Assign text which will be displayed for the corresponding
active respectively inactive state of the point. List of
choices displays active/inactive (passive) texts with ID,
and number of states.
To add texts to the list, open the Miscellaneous Text
Editor by clicking the dotted button on the right (Excel
Web Controller, Miscellaneous Text Editor chapter).

Descriptor Supplemental point information. Each project and/or


plant has a unique set of descriptors that can be
assigned to its datapoint names to further describe them.

List of choices displays descriptors with ID and text.


To add and change descriptors in the list, open the
Miscellaneous Text Editor by clicking the dotted button
on the right (see Miscellaneous Text Editor chapter).

Alarm Text Alarm text that displays on point alarm. List of choices
displays alarm texts with ID and text.

To add and change alarm texts in the list, open the


Miscellaneous Text Editor by clicking the dotted button
on the right (see Miscellaneous Text Editor chapter).

Read Access Determine whether the user can read datapoint values
Write Access respectively write values to the datapoint in the Web
Interface.

All users having a user level equal or higher than the


assigned read access respectively write access of the
datapoint, will have this access right enabled in the Web

EN2Z-0937GE51 R0518 396


CARE EDITORS

Interface, all others will not (for further details, please


refer to the User Access Manager section).
Notification Class Enable alarming for the datapoint by selecting a
notification class with a given priority. By default the
following notification classes with descending priority can
be selected:

- Urgent
- High
- Low
- Journal

Those default notification classes are especially


designed for the alarming to the EBI central (for
information on notification classes to be used for 3rd party
BACnet clients, please refer to the Notification Class
Manager section)

Each recipient which is assigned to this notification class


will receive the datapoint alarm triggered by the selected
notification. But, alarms will only be generated for the
enabled transitions (To-Normal, To-OffNormal, and/or
To-Fault) of a recipient. Each enabled transition will be
propagated with the selected notification. (For further
details please refer to the Notification Class Manager
section).

This connection has not to be mixed up with the


transitions selected under Reporting (see Reporting
description in the following).

Notify Type If the notification class Urgent, High, or Low has been
selected, the notify type Alarm must be used

Suppress Alarm Whether or not software should suppress alarm


messages for changes in Fixed Mode and exceeding the
limits.

Alarm Delay Defines the time delay with which a ´To-Off-Normal`


transition will be set off.

Alarm Delay Normal Defines the time delay with which a ´To-Normal`
transition will be set off.

Alarm Value To set the status, 0 or 1, when an alarm should be


reported, in case the binary input value changes.

Reporting Define which transition type ((To-Normal, To-OffNormal,


and/or To Fault) will be tracked by timestamping in the
Web Interface.

Point Role Point Role created via an external tool like XL Toolkit and
imported into CARE. The point role is selected from XL
Toolkit database.

LED Mode (for EAGLE controller: applies to points on panel I/Os


only)
Toggles the LED between status mode and alarm mode
with the following indication:

Status
Yellow = ON, No color = OFF

Alarm
Red = Alarm, Green = No alarm

397 EN2Z-0937GE51 R0518


EDITORS CARE

This attribute applies to Excel 800 with XF8.. and XFL8..


modules only. The XF8.. panel modules can also be
toggled in the terminal assignment tool (TAF).

Polarity Selection of the polarity which indicates the relationship


between the physical state of the Input and the logical
state represented by the present value. If the polarity is
NORMAL, then the ACTIVE state of the present value is
also the ACTIVE or ON state of the physical input.

If the polarity is REVERSE, then the ACTIVE state of the


present value is the INACTIVE or OFF state of the
physical Input.

Present Value Polarity Physical State of Input Physical State of Device


INACTIVE NORMAL OFF or INACTIVE not running
ACTIVE NORMAL ON or ACTIVE Running
INACTIVE REVERSE ON or ACTIVE not running
ACTIVE REVERSE OFF or INACTIVE running

Communication failure (applies to EAGLE controller only)


In case of communication failure or application stop, the
device is commanded to one of the following positions if
the controller does not deliver a value (no response).

- Last Valid Value


device is commanded to the last valid position

- Safety Value
device is commanded to the value (logical state)
that can be selected in Safety Value

Safety Value (applies to EAGLE controller only)


Select the safety value if Safety Value is selected in
Communication Failure. The selectable values depend
on the state text definitions (see State Texts field
description).

Acked Transitions Allows observing the acknowledgement behavior of a


user for To-Off-Normal and To-Fault transition events of
the datapoint. CARE checks whether a transition event
has been acknowledged or not. If a transition event has
not been acknowledged within a definable delay time, an
alarm based on an event enrollment (event enrollment
alarm) is sent to a supervisory recipient, for example EBI.

Click Observe button to display the Event Enrollment –


Acked Transitions dialog box.

EN2Z-0937GE51 R0518 398


CARE EDITORS

In the Event Enrollment – Acked Transitions dialog box,


do the following:

399 EN2Z-0937GE51 R0518


EDITORS CARE

1. In the Name field, change the default name if


desired.
2. In the Description field, enter a meaningful
description if desired.
3. In the Event Type field, note the event type of
the event enrollment object is ´change of
bitstring`.
4. Under Event Parameters, select the transition
event(s) that should be checked for
acknowledgement. The List of Values shows the
possible logical values (checked=true,
unchecked=false, CARE verifies with negative
logic for false the condition) resulting from the
comparison of the selected transition event(s)
and the underlying bitstring mask. An event
enrollment alarm will be sent, if the transition
event will not be acknowledged within the delay
time.
5. In the Alarm Delay field, enter an alarm delay in
sec. The event enrollment alarm will be sent if the
transition event has not been acknowledged
within the delay time.
6. From the Notify Type drop-down listbox, select
the notify type.
7. From the Notification Class drop-down listbox,
select the notification class that defines the
supervisory recipient to which the event
enrollment alarm is sent after an
unacknowledged transition.
8. Under Reporting, check the transition event(s)
that should cause an event notification to the
supervisory recipient.

NOTE:
These settings refer to the event enrollment itself
not to the intrinsic reporting properties of the
datapoint:
To-Off-Normal = event notification is sent if the
acknowledgement is missing within the alarm
delay;
Back-To-Normal = event notification is sent if the
acknowledgement is sent after the alarm delay
has been expired.

If you do not check at least one transition event


and one event parameter, the observation is not
enabled.

9. After entering the values, click OK. On the


Properties tab of the datapoint, the Enabled
check box is checked.

Status Flags Allows observing status flags conditions. To enable


observing status flag conditions, click Observe button to
display the Event Enrollment – Status Flags dialog box.

EN2Z-0937GE51 R0518 400


CARE EDITORS

In the Event Enrollment – Status Flags dialog box, do the


following:

1. In the Name field, change the default name if


desired.
2. In the Description field, enter a meaningful
description if desired.
3. In the Event Type field, note that the event type
of the event enrollment object is ´change of
state`.

401 EN2Z-0937GE51 R0518


EDITORS CARE

4. Under Status Flags, select the flags of which


status should be observed. The List of Values
shows the possible logical values (checked=true,
unchecked=false) resulting from the comparison
of the selected status flags and the underlying
bitstring mask.
5. In the Alarm Delay field, enter an alarm delay in
sec. An event enrollment alarm will be sent for
each status flag that is enabled (checked) within
the alarm delay time.
6. From the Notify Type drop-down listbox, select
the notify type.
7. From the Notification Class drop-down listbox,
select the notification class that defines the
supervisory recipient to which the event
enrollment alarm is sent.
8. Under Reporting, check the transition event(s)
that should cause an event notification to the
supervisory recipient.

NOTE:
These settings refer to the event enrollment itself
not to the intrinsic reporting properties of the
datapoint:
To-Off-Normal = event notification is sent if a
status flag is enabled within the alarm delay;
To-Normal = event notification is sent if a status
flag is disabled after the alarm delay has been
expired.

If you do not check at least one transition event


and one event parameter, the observation is not
enabled.

9. After entering the values, click OK. On the


Properties tab of the datapoint, the Enabled
check box is checked.

Runtime
(Elapsed Active Time) Allows observing the state of the elapsed runtime. To
enable the observation of the state of the elapsed
runtime, click the Observe button to display the Alarming
for Elapsed Active Time dialog box.

EN2Z-0937GE51 R0518 402


CARE EDITORS

In the Alarming for Elapsed For Elapsed Active Time


dialog box, do the following:

403 EN2Z-0937GE51 R0518


EDITORS CARE

1. In the Name field, change the default name if


desired.
2. In the Static field, enter a meaningful description
if desired.
3. In the Event Type field, note that the event type
of the event enrollment object is ´change of
state`.
4. In the High Limit field, enter the high limit value
for the elapsed active (elapsed) runtime,
respectively the number of state count changes.
5. In the Low Limit field, enter ´0` for the elapsed
active (elapsed) runtime respectively the number
of state count changes.
6. In the Alarm Delay field, enter an alarm delay in
sec. An event enrollment alarm will be sent if the
elapsed active (elapsed) runtime, respectively the
number of state count changes increases the
high or low limit within the alarm delay time.
7. From the Notify Type drop-down listbox, select
the notify type.
8. From the Notification Class drop-down listbox,
select the notification class that defines the
supervisory recipient to which the event
enrollment alarm is sent.
9. Under Reporting, check the transition event(s)
that should cause an event notification to the
supervisory recipient.

NOTE:
These settings refer to the event enrollment itself
not to the intrinsic reporting properties of the
datapoint:
To-Off-Normal = event notification is sent if the
elapsed active (elapsed) runtime value,
respectively number of state count changes value
exceeds the high within the alarm delay;
To-Normal = event notification is sent if the
elapsed active (elapsed) runtime, respectively
number of state count changes takes a value
within the high or low limit after the alarm delay
has been expired.

If you do not check at least one transition event


and one event parameter, the observation is not
enabled.

10. After entering the values, click OK. On the


Properties tab of the datapoint, the Enabled
check box is checked.

Count Limits Allows observing the state of the count limits. To enable
the observation of the state of the elapsed runtime or
count limits, click the relevant Observe button to display
the Alarming for Change of State Count dialog box.

EN2Z-0937GE51 R0518 404


CARE EDITORS

In the Alarming for Change of State Count dialog box, do


the following:

405 EN2Z-0937GE51 R0518


EDITORS CARE

1. In the Name field, change the default name if


desired.
2. In the Description field, enter a meaningful
description if desired.
3. In the Event Type field, note that the event type
of the event enrollment object is ´change of
state`.
4. In the High Limit field, enter the high limit value
for the elapsed active (elapsed) runtime,
respectively the number of state count changes.
5. In the Low Limit field, enter ´0` for the elapsed
active (elapsed) runtime respectively the number
of state count changes.
6. In the Alarm Delay field, enter an alarm delay in
sec. An event enrollment alarm will be sent if the
elapsed active (elapsed) runtime, respectively the
number of state count changes increases the
high or low limit within the alarm delay time.
7. From the Notify Type drop-down listbox, select
the notify type.
8. From the Notification Class drop-down listbox,
select the notification class that defines the
supervisory recipient to which the event
enrollment alarm is sent.
9. Under Reporting, check the transition event(s)
that should cause an event notification to the
supervisory recipient.

NOTE:
These settings refer to the event enrollment itself
not to the intrinsic reporting properties of the
datapoint:
To-Off-Normal = event notification is sent if the
elapsed active (elapsed) runtime value,
respectively number of state count changes value
exceeds the high within the alarm delay;
To-Normal = event notification is sent if the
elapsed active (elapsed) runtime, respectively
number of state count changes takes a value
within the high or low limit after the alarm delay
has been expired.

If you do not check at least one transition event


and one event parameter, the observation is not
enabled.

10. After entering the values, click OK. On the


Properties tab of the datapoint, the Enabled
check box is checked.

EN2Z-0937GE51 R0518 406


CARE EDITORS

Binary Output Point

Purpose Display and/or modify the attributes of the selected binary output point.

Procedure In the tree, click desired point to display current values on the right Properties tab
(itemized display).

or,

in the tree, click on any object (project, controller, plant) which the point belongs to,
and which is in grid display.

To modify values, enter desired values in the fields, and/or select respectively
deselect desired options.

Attributes Description Datapoint Name Point name (maximum of 40 alphanumeric characters)


assigned to a point for operator use in locating and

407 EN2Z-0937GE51 R0518


EDITORS CARE

commanding the point. This name must be unique within


a controller.
Point names must include one non-digit character and
cannot include Tabs, double quotes, ?, *, or space
characters. All other ASCII characters are allowable (A-
Z, 0-9, +, -, _, etc). For example, 12A is a datapoint
name, but 12 is not.

IMPORTANT
Note that the max. length of the datapoint name for Lon
points should not exceed 18 characters (see Lon point
attribute).

BACnet Object Type Displays the BACnet object type.

BACnet Object ID Displays the BACnet object type ID.

BACnet Instance number Displays the BACnet intance number.

Lon Point (Applies to FALCON controller only)


Define whether the datapoint should be a LON point or
not. List of choices displays:

NV-Output
Creates output NV.

Manual Mapping
Provides selection of this datapoint for mapping to NVs in
the NV-Editor.

Output NV Define the NV-type for the LON point.

Reliability status on the Excel Web HTML Interface:

In order to make sure that the Reliability property for the


present value works properly, the service type of the
point must be set to Acknowledged (Ackd). With
acknowledged service, controller - I/O module
disconnections are indicated by the relevant reliability
´No Sensor` or ´No Output`. Note, that if a large number
of outputs (e.g. all outputs of mutiple I/O modules) are
set to acknowledged servcice, the performance on the
LON bus may drastically decrease (see "Change Service
Type for Excel Web Datapoints" section).

Active/Inactive Text Assign text which will be displayed for the corresponding
active respectively inactive state of the point. List of
choices displays active/inactive (passive) texts with ID,
and number of states.
To add texts to the list, open the Miscellaneous Text
Editor by clicking the dotted button on the right (Excel
Web Controller, Miscellaneous Text Editor chapter).

Descriptor Supplemental point information. Each project and/or


plant has a unique set of descriptors that can be
assigned to its datapoint names to further describe them.

List of choices displays descriptors with ID and text.


To add and change descriptors in the list, open the
Miscellaneous Text Editor by clicking the dotted button
on the right (see Miscellaneous Text Editor chapter).

Alarm Text Alarm text that displays on point alarm. List of choices
displays alarm texts with ID and text.

EN2Z-0937GE51 R0518 408


CARE EDITORS

To add and change alarm texts in the list, open the


Miscellaneous Text Editor by clicking the dotted button
on the right (see Miscellaneous Text Editor chapter).

Read Access Determine whether the user can read datapoint values
Write Access respectively write values to the datapoint in the Web
Interface.
All users having a user level equal or higher than the
assigned read access respectively write access of the
datapoint, will have this access right enabled in the Web
Interface, all others will not (for further details, please
refer to the User Access Manager section).

Notification Class Enable alarming for the datapoint by selecting a


notification class with a given priority. By default the
following notification classes with descending priority can
be selected:

- Urgent
- High
- Low
- Journal

Those default notification classes are especially


designed for the alarming to the EBI central (for
information on notification classes to be used for 3rd party
BACnet clients, please refer to the Notification Class
Manager section)

Each recipient which is assigned to this notification class


will receive the datapoint alarm triggered by the selected
notification. But, alarms will only be generated for the
enabled transitions (To-Normal, To-OffNormal, and/or
To-Fault) of a recipient. Each enabled transition will be
propagated with the selected notification. (For further
details please refer to the Notification Class Manager
section).

This connection has not to be mixed up with the


transitions selected under Reporting (see Reporting
description in the following).

Notify Type If the notification class Urgent, High, or Low has been
selected, the notify type Alarm must be used.

Suppress Alarm Whether or not software should suppress alarm


messages for changes in Fixed Mode and exceeding the
limits.

Alarm Delay Defines the time delay with which a ´To-Off-Normal`


(EAGLE and FALCON controllers) transition and a ´To-
Normal` transition (FALCON controller) will be set off.

Alarm Delay Normal Defines the time delay with which a ´To-Normal`
transition will be set off.

Reporting Define which transition type ((To-Normal, To-OffNormal,


and/or To Fault) will be tracked by timestamping in the
Web Interface.

Point Role Point Role created via an external tool like XL Toolkit and
imported into CARE. The point role is selected from XL
Toolkit database.

Polarity Selection of the polarity which indicates the relationship


between the physical state of the Input and the logical

409 EN2Z-0937GE51 R0518


EDITORS CARE

state represented by the present value. If the polarity is


NORMAL, then the ACTIVE state of the present value is
also the ACTIVE or ON state of the physical input.

If the polarity is REVERSE, then the ACTIVE state of the


present value is the INACTIVE or OFF state of the
physical Input.

Present_Value Polarity Physical State of Input Physical State of Device


INACTIVE NORMAL OFF or INACTIVE not running
ACTIVE NORMAL ON or ACTIVE Running
INACTIVE REVERSE ON or ACTIVE not running
ACTIVE REVERSE OFF or INACTIVE running
Communication failure In case of communication failure or application stop, the
device is commanded to one of the following positions if
the controller does not deliver a value (no response).

- Last Valid Value


device is commanded to the last valid position

- OFF (logical)
- ON (logical)
device is commanded to the selected logical state

with Switches Define whether the point transmittes a continous signal


and is on a board with switches or not.

Relinquish Default Define the value that will be written to present value, if all
values in the priority list are invalid.

Feedback Value Define the datapoint that should provide the value for
feedback control in case of BACnet fault and command
failure alarms. The feedback point must be a binary
input. The selected feedback point will not be available
on the controller HMI and web interface.

NOTE:
The feedback point must not be used in a control loop
since as a result the control loop will not be executed
properly.

Status Flags Allows observing status flags conditions. To enable


observing status flag conditions, click Observe button to
display the Event Enrollment – Status Flags dialog box.

EN2Z-0937GE51 R0518 410


CARE EDITORS

In the Event Enrollment – Status Flags dialog box, do the


following:

1. In the Name field, change the default name if


desired.
2. In the Description field, enter a meaningful
description if desired.
3. In the Event Type field, note that the event type
of the event enrollment object is ´change of
state`.

411 EN2Z-0937GE51 R0518


EDITORS CARE

4. Under Status Flags, select the flags of which


status should be observed. The List of Values
shows the possible logical values (checked=true,
unchecked=false) resulting from the comparison
of the selected status flags and the underlying
bitstring mask.
5. In the Alarm Delay field, enter an alarm delay in
sec. An event enrollment alarm will be sent for
each status flag that is enabled (checked) within
the alarm delay time.
6. From the Notify Type drop-down listbox, select
the notify type.
7. From the Notification Class drop-down listbox,
select the notification class that defines the
supervisory recipient to which the event
enrollment alarm is sent.
8. Under Reporting, check the transition event(s)
that should cause an event notification to the
supervisory recipient.

NOTE:
These settings refer to the event enrollment itself
not to the intrinsic reporting properties of the
datapoint:
To-Off-Normal = event notification is sent if a
status flag is enabled within the alarm delay;
To-Normal = event notification is sent if a status
flag is disabled after the alarm delay has been
expired.

If you do not check at least one transition event


and one event parameter, the observation is not
enabled.

9. After entering the values, click OK. On the


Properties tab of the datapoint, the Enabled
check box is checked.

Runtime
(Elapsed Active Time)
Allows observing the state of the elapsed runtime or the
count limits. To enable the observation of the state of the
elapsed runtime or count limits, click the relevant
Observe button to display the Alarming For Elapsed
Active Time dialog box.

EN2Z-0937GE51 R0518 412


CARE EDITORS

In the Alarming For Elapsed Active Time dialog box, do


the following:

413 EN2Z-0937GE51 R0518


EDITORS CARE

1. In the Name field, change the default name if


desired.
2. In the Static field, enter a meaningful description
if desired.
3. In the Event Type field, note that the event type
of the event enrollment object is ´change of
state`.
4. In the High Limit field, enter the high limit value
for the elapsed active (elapsed) runtime,
respectively the number of state count changes.
5. In the Low Limit field, enter ´0` for the elapsed
active (elapsed) runtime respectively the number
of state count changes.
6. In the Alarm Delay field, enter an alarm delay in
sec. An event enrollment alarm will be sent if the
elapsed active (elapsed) runtime, respectively the
number of state count changes increases the
high or low limit within the alarm delay time.
7. From the Notify Type drop-down listbox, select
the notify type.
8. From the Notification Class drop-down listbox,
select the notification class that defines the
supervisory recipient to which the event
enrollment alarm is sent.
9. Under Reporting, check the transition event(s)
that should cause an event notification to the
supervisory recipient.

NOTE:
These settings refer to the event enrollment itself
not to the intrinsic reporting properties of the
datapoint:
To-Off-Normal = event notification is sent if the
elapsed active (elapsed) runtime value,
respectively number of state count changes value
exceeds the high within the alarm delay;
To-Normal = event notification is sent if the
elapsed active (elapsed) runtime, respectively
number of state count changes takes a value
within the high or low limit after the alarm delay
has been expired.

If you do not check at least one transition event


and one event parameter, the observation is not
enabled.

10. After entering the values, click OK. On the


Properties tab of the datapoint, the Enabled
check box is checked.

Count Limits Allows observing the state of the elapsed runtime or the
count limits. To enable the observation of the state of the
elapsed runtime or count limits, click the relevant
Observe button to display the Alarming for Elapsed
Active Time respectively the Alarming for Change of
State Count dialog box.

EN2Z-0937GE51 R0518 414


CARE EDITORS

In the Alarming for Change of State Count dialog box, do


the following:

415 EN2Z-0937GE51 R0518


EDITORS CARE

1. In the Name field, change the default name if


desired.
2. In the Description field, enter a meaningful
description if desired.
3. In the Event Type field, note that the event type
of the event enrollment object is ´change of
state`.
4. In the High Limit field, enter the high limit value
for the elapsed active (elapsed) runtime,
respectively the number of state count changes.
5. In the Low Limit field, enter ´0` for the elapsed
active (elapsed) runtime respectively the number
of state count changes.
6. In the Alarm Delay field, enter an alarm delay in
sec. An event enrollment alarm will be sent if the
elapsed active (elapsed) runtime, respectively the
number of state count changes increases the
high or low limit within the alarm delay time.
7. From the Notify Type drop-down listbox, select
the notify type.
8. From the Notification Class drop-down listbox,
select the notification class that defines the
supervisory recipient to which the event
enrollment alarm is sent.
9. Under Reporting, check the transition event(s)
that should cause an event notification to the
supervisory recipient.

NOTE:
These settings refer to the event enrollment itself
not to the intrinsic reporting properties of the
datapoint:
To-Off-Normal = event notification is sent if the
elapsed active (elapsed) runtime value,
respectively number of state count changes value
exceeds the high within the alarm delay;
To-Normal = event notification is sent if the
elapsed active (elapsed) runtime, respectively
number of state count changes takes a value
within the high or low limit after the alarm delay
has been expired.

If you do not check at least one transition event


and one event parameter, the observation is not
enabled.

10. After entering the values, click OK. On the


Properties tab of the datapoint, the Enabled
check box is checked.

EN2Z-0937GE51 R0518 416


CARE EDITORS

Binary Value Point

Purpose Display and/or modify the attributes of the selected binary value point.

Procedure In the tree, click desired point to display current values on the right Properties tab
(itemized display).

or,

in the tree, click on any object (project, controller, plant) which the point belongs to,
and which is in grid display.

To modify values, enter desired values in the fields, and/or select respectively
deselect desired options.

Attributes Description Datapoint Name Point name (maximum of 40 alphanumeric characters)


assigned to a point for operator use in locating and

417 EN2Z-0937GE51 R0518


EDITORS CARE

commanding the point. This name must be unique within


a controller.

Point names must include one non-digit character and


cannot include Tabs, double quotes, ?, *, or space
characters. All other ASCII characters are allowable (A-
Z, 0-9, +, -, _, etc). For example, 12A is a datapoint
name, but 12 is not.

IMPORTANT
Note that the max. length of the datapoint name for Lon
points should not exceed 18 characters (see Lon point
attribute).

BACnet Object Type Displays the BACnet object type.

BACnet Object ID Displays the BACnet object type ID.

BACnet Instance number Displays the BACnet intance number.

Active/Inactive Text Assign text which will be displayed for the corresponding
active respectively inactive state of the point. List of
choices displays active/inactive (passive) texts with ID,
and number of states.
To add texts to the list, open the Miscellaneous Text
Editor by clicking the dotted button on the right (Excel
Web Controller, Miscellaneous Text Editor chapter).

Descriptor Supplemental point information. Each project and/or


plant has a unique set of descriptors that can be
assigned to its datapoint names to further describe them.

List of choices displays descriptors with ID and text.


To add and change descriptors in the list, open the
Miscellaneous Text Editor by clicking the dotted button
on the right (see Miscellaneous Text Editor chapter).

Alarm Text Alarm text that displays on point alarm. List of choices
displays alarm texts with ID and text.

To add and change alarm texts in the list, open the


Miscellaneous Text Editor by clicking the dotted button
on the right (see Miscellaneous Text Editor chapter).

Read Access Determine whether the user can read datapoint values
Write Access respectively write values to the datapoint in the Web
Interface.

All users having a user level equal or higher than the


assigned read access respectively write access of the
datapoint, will have this access right enabled in the Web
Interface, all others will not (for further details, please
refer to the User Access Manager section).

Notification Class Enable alarming for the datapoint by selecting a


notification class with a given priority. By default the
following notification classes with descending priority can
be selected:

- Urgent
- High
- Low
- Journal

Those default notification classes are especially


designed for the alarming to the EBI central (for
information on notification classes to be used for 3rd party

EN2Z-0937GE51 R0518 418


CARE EDITORS

BACnet clients, please refer to the Notification Class


Manager section)

Each recipient which is assigned to this notification class


will receive the datapoint alarm triggered by the selected
notification. But, alarms will only be generated for the
enabled transitions (To-Normal, To-OffNormal, and/or
To-Fault) of a recipient. Each enabled transition will be
propagated with the selected notification. (For further
details please refer to the Notification Class Manager
section).

This connection has not to be mixed up with the


transitions selected under Reporting (see Reporting
description in the following).

Notify Type If the notification class Urgent, High, or Low has been
selected, the notify type Alarm must be used.

Suppress Alarm Whether or not software should suppress alarm


messages for changes in Fixed Mode and exceeding the
limits.

Alarm Delay Defines the time delay with which a ´To-Off-Normal`


(EAGLE and FALCON controllers) transition and a ´To-
Normal` transition (FALCON controller) will be set off.

Alarm Delay Normal Defines the time delay with which a ´To-Normal`
transition will be set off.

Alarm Value To set the status, 0 or 1, when an alarm should be


reported, in case the binary input value changes

Reporting Define which transition type ((To-Normal, To-OffNormal,


and/or To Fault) will be tracked by timestamping in the
Web Interface.

Point Role Point Role created via an external tool like XL Toolkit and
imported into CARE. The point role is selected from XL
Toolkit database.

Relinquish Default Define the value that will be written to present value, if all
values in the priority list are invalid.

EOH/EOV Optimization Check whether the datapoint should be optimized or not,


in case the datapoint is used as setpoint for energy
optimized heating or ventilation (EOH/EOV).

Setpoint Enables the direct change (override) of the current


datapoint value in the web interface and the controller
HMI without the necessisity of setting the datapoint into
manual mode.

Acked Transitions Allows observing the acknowledgement behavior of a


user for To-Off-Normal and To-Fault transition events of
the datapoint. CARE checks whether a transition event
has been acknowledged or not. If a transition event has
not been acknowledged within a definable delay time, an
alarm based on an event enrollment (event enrollment
alarm) is sent to a supervisory recipient, for example EBI.

Click Observe button to display the Event Enrollment –


Acked Transitions dialog box.

419 EN2Z-0937GE51 R0518


EDITORS CARE

In the Event Enrollment – Acked Transitions dialog box,


do the following:

EN2Z-0937GE51 R0518 420


CARE EDITORS

1. In the Name field, change the default name if


desired.
2. In the Description field, enter a meaningful
description if desired.
3. In the Event Type field, note the event type of
the event enrollment object is ´change of
bitstring`.
4. Under Event Parameters, select the transition
event(s) that should be checked for
acknowledgement. The List of Values shows the
possible logical values (checked=true,
unchecked=false, CARE verifies with negative
logic for false the condition) resulting from the
comparison of the selected transition event(s)
and the underlying bitstring mask. An event
enrollment alarm will be sent, if the transition
event will not be acknowledged within the delay
time.
5. In the Alarm Delay field, enter an alarm delay in
sec. The event enrollment alarm will be sent if the
transition event has not been acknowledged
within the delay time.
6. From the Notify Type drop-down listbox, select
the notify type.
7. From the Notification Class drop-down listbox,
select the notification class that defines the
supervisory recipient to which the event
enrollment alarm is sent after an
unacknowledged transition.
8. Under Reporting, check the transition event(s)
that should cause an event notification to the
supervisory recipient.

NOTE:
These settings refer to the event enrollment itself
not to the intrinsic reporting properties of the
datapoint:
To-Off-Normal = event notification is sent if the
acknowledgement is missing within the alarm
delay;
Back-To-Normal = event notification is sent if the
acknowledgement is sent after the alarm delay
has been expired.

If you do not check at least one transition event


and one event parameter, the observation is not
enabled.

9. After entering the values, click OK. On the


Properties tab of the datapoint, the Enabled
check box is checked.

Status Flags Allows observing status flags conditions. To enable


observing status flag conditions, click Observe button to
display the Event Enrollment – Status Flags dialog box.

421 EN2Z-0937GE51 R0518


EDITORS CARE

In the Event Enrollment – Status Flags dialog box, do the


following:

1. In the Name field, change the default name if


desired.
2. In the Description field, enter a meaningful
description if desired.
3. In the Event Type field, note that the event type
of the event enrollment object is ´change of
state`.

EN2Z-0937GE51 R0518 422


CARE EDITORS

4. Under Status Flags, select the flags of which


status should be observed. The List of Values
shows the possible logical values (checked=true,
unchecked=false) resulting from the comparison
of the selected status flags and the underlying
bitstring mask.
5. In the Alarm Delay field, enter an alarm delay in
sec. An event enrollment alarm will be sent for
each status flag that is enabled (checked) within
the alarm delay time.
6. From the Notify Type drop-down listbox, select
the notify type.
7. From the Notification Class drop-down listbox,
select the notification class that defines the
supervisory recipient to which the event
enrollment alarm is sent.
8. Under Reporting, check the transition event(s)
that should cause an event notification to the
supervisory recipient.

NOTE:
These settings refer to the event enrollment itself
not to the intrinsic reporting properties of the
datapoint:
To-Off-Normal = event notification is sent if a
status flag is enabled within the alarm delay;
To-Normal = event notification is sent if a status
flag is disabled after the alarm delay has been
expired.

If you do not check at least one transition event


and one event parameter, the observation is not
enabled.

9. After entering the values, click OK. On the


Properties tab of the datapoint, the Enabled
check box is checked.

Runtime
(Elapsed Active Time) Allows observing the state of the elapsed runtime. To
enable the observation of the state of the elapsed
runtime, click the Observe button to display the Alarming
for Elapsed Active Time dialog box.

423 EN2Z-0937GE51 R0518


EDITORS CARE

In the Alarming for Elapsed For Elapsed Active Time


dialog box, do the following:

EN2Z-0937GE51 R0518 424


CARE EDITORS

1. In the Name field, change the default name if


desired.
2. In the Static field, enter a meaningful description
if desired.
3. In the Event Type field, note that the event type
of the event enrollment object is ´change of
state`.
4. In the High Limit field, enter the high limit value
for the elapsed active (elapsed) runtime,
respectively the number of state count changes.
5. In the Low Limit field, enter ´0` for the elapsed
active (elapsed) runtime respectively the number
of state count changes.
6. In the Alarm Delay field, enter an alarm delay in
sec. An event enrollment alarm will be sent if the
elapsed active (elapsed) runtime, respectively the
number of state count changes increases the
high or low limit within the alarm delay time.
7. From the Notify Type drop-down listbox, select
the notify type.
8. From the Notification Class drop-down listbox,
select the notification class that defines the
supervisory recipient to which the event
enrollment alarm is sent.
9. Under Reporting, check the transition event(s)
that should cause an event notification to the
supervisory recipient.

NOTE:
These settings refer to the event enrollment itself
not to the intrinsic reporting properties of the
datapoint:
To-Off-Normal = event notification is sent if the
elapsed active (elapsed) runtime value,
respectively number of state count changes value
exceeds the high within the alarm delay;
To-Normal = event notification is sent if the
elapsed active (elapsed) runtime, respectively
number of state count changes takes a value
within the high or low limit after the alarm delay
has been expired.

If you do not check at least one transition event


and one event parameter, the observation is not
enabled.

10. After entering the values, click OK. On the


Properties tab of the datapoint, the Enabled
check box is checked.

Count Limits Allows observing the state of the count limits. To enable
the observation of the state of the elapsed runtime or
count limits, click the relevant Observe button to display
the Alarming for Change of State Count dialog box.

425 EN2Z-0937GE51 R0518


EDITORS CARE

In the Alarming for Change of State Count dialog box, do


the following:

EN2Z-0937GE51 R0518 426


CARE EDITORS

1. In the Name field, change the default name if


desired.
2. In the Description field, enter a meaningful
description if desired.
3. In the Event Type field, note that the event type
of the event enrollment object is ´change of
state`.
4. In the High Limit field, enter the high limit value
for the elapsed active (elapsed) runtime,
respectively the number of state count changes.
5. In the Low Limit field, enter ´0` for the elapsed
active (elapsed) runtime respectively the number
of state count changes.
6. In the Alarm Delay field, enter an alarm delay in
sec. An event enrollment alarm will be sent if the
elapsed active (elapsed) runtime, respectively the
number of state count changes increases the
high or low limit within the alarm delay time.
7. From the Notify Type drop-down listbox, select
the notify type.
8. From the Notification Class drop-down listbox,
select the notification class that defines the
supervisory recipient to which the event
enrollment alarm is sent.
9. Under Reporting, check the transition event(s)
that should cause an event notification to the
supervisory recipient.

NOTE:
These settings refer to the event enrollment itself
not to the intrinsic reporting properties of the
datapoint:
To-Off-Normal = event notification is sent if the
elapsed active (elapsed) runtime value,
respectively number of state count changes value
exceeds the high within the alarm delay;
To-Normal = event notification is sent if the
elapsed active (elapsed) runtime, respectively
number of state count changes takes a value
within the high or low limit after the alarm delay
has been expired.

If you do not check at least one transition event


and one event parameter, the observation is not
enabled.

10. After entering the values, click OK. On the


Properties tab of the datapoint, the Enabled
check box is checked.

427 EN2Z-0937GE51 R0518


EDITORS CARE

Multi-State Points

Multi-State Input Point

Purpose Display and/or modify the attributes of the selected multi-state input point.

Procedure In the tree, click desired point to display current values on the right Properties tab
(itemized display).

or,

in the tree, click on any object (project, controller, plant) which the point belongs to,
and which is in grid display.

To modify values, enter desired values in the fields, and/or select respectively
deselect desired options.

EN2Z-0937GE51 R0518 428


CARE EDITORS

Attributes Description Datapoint Name Point name (maximum of 40 alphanumeric characters)


assigned to a point for operator use in locating and
commanding the point. This name must be unique within
a controller.

Point names must include one non-digit character and


cannot include Tabs, double quotes, ?, *, or space
characters. All other ASCII characters are allowable (A-
Z, 0-9, +, -, _, etc). For example, 12A is a datapoint
name, but 12 is not.

IMPORTANT
Note that the max. length of the datapoint name for Lon
points should not exceed 18 characters (see Lon point
attribute).

BACnet Object Type Displays the BACnet object type.

BACnet Object ID Displays the BACnet object type ID.

BACnet Instance number Displays the BACnet intance number.

Lon Point (Applies to FALCON controller only)


Define whether the datapoint should be a LON point or
not. List of choices displays:

NV-Input
Creates input NV.

Manual Mapping
Provides selection of this datapoint for mapping to NVs in
the NV-Editor.

Input NV Define the NV-type for the LON point.

State Texts Assign state texts which will be displayed for the
corresponding state of the point. List of choices displays
the number of states and the first two states of state
sequencies which may include mor than two states.
Further texts of state sequencies, will be shown by the
yellow tooltip. Entries are arranged by ID.
To add texts to the list, open the Miscellaneous Text
Editor by clicking the dotted button on the right (Excel
Web Controller, Miscellaneous Text Editor chapter).

Descriptor Supplemental point information. Each project and/or


plant has a unique set of descriptors that can be
assigned to its datapoint names to further describe them.

List of choices displays descriptors with ID and text.


To add and change descriptors in the list, open the
Miscellaneous Text Editor by clicking the dotted button
on the right (see Miscellaneous Text Editor chapter).

Alarm Text Alarm text that displays on point alarm. List of choices
displays alarm texts with ID and text.

To add and change alarm texts in the list, open the


Miscellaneous Text Editor by clicking the dotted button
on the right (see Miscellaneous Text Editor chapter).

Characteristic Assign a characteristic (conversion table) if the datapoint


is to be mapped to a NV (see Lon point attribute). For
Multi-State Inputs, the characteristic +1, for Multi-State
Outputs, the characteristic -1, is provided by CARE by

429 EN2Z-0937GE51 R0518


EDITORS CARE

default. These default characteristics must be used if the


multi-state points are considered to be mapped to NVs.

Read Access Determine whether the user can read datapoint values
Write Access respectively write values to the datapoint in the Web
Interface.

All users having a user level equal or higher than the


assigned read access respectively write access of the
datapoint, will have this access right enabled in the Web
Interface, all others will not (for further details, please
refer to the User Access Manager section).

Notification Class Enable alarming for the datapoint by selecting a


notification class with a given priority. By default the
following notification classes with descending priority can
be selected:

- Urgent
- High
- Low
- Journal

Those default notification classes are especially


designed for the alarming to the EBI central (for
information on notification classes to be used for 3rd party
BACnet clients, please refer to the Notification Class
Manager section)

Each recipient which is assigned to this notification class


will receive the datapoint alarm triggered by the selected
notification. But, alarms will only be generated for the
enabled transitions (To-Normal, To-OffNormal, and/or
To-Fault) of a recipient. Each enabled transition will be
propagated with the selected notification. (For further
details please refer to the Notification Class Manager
section).

This connection has not to be mixed up with the


transitions selected under Reporting (see Reporting
description in the following).

Notify Type If the notification class Urgent, High, or Low has been
selected, the notify type Alarm must be used.

Suppress Alarm Whether or not software should suppress alarm


messages for changes in Fixed Mode and exceeding the
limits.

Alarm Delay Defines the time delay with which a ´To-Off-Normal`


(EAGLE and FALCON controllers) transition and a ´To-
Normal` transition (FALCON controller) will be set off.

Alarm Delay Normal Defines the time delay with which a ´To-Normal`
transition will be set off.

Reporting Define which transition type ((To-Normal, To-OffNormal,


and/or To Fault) will be tracked by timestamping in the
Web Interface.

Point Role Point Role created via an external tool like XL Toolkit and
imported into CARE. The point role is selected from XL
Toolkit database.

EN2Z-0937GE51 R0518 430


CARE EDITORS

Multi-State Properties Check in which state the point should be in the Alarm
and/or in the Fault condition. If enabled, the alarm text of
the corresponding Reporting is displayed.(see Alarm
text).

Acked Transitions Allows observing the acknowledgement behavior of a


user for To-Off-Normal and To-Fault transition events of
the datapoint. CARE checks whether a transition event
has been acknowledged or not. If a transition event has
not been acknowledged within a definable delay time, an
alarm based on an event enrollment (event enrollment
alarm) is sent to a supervisory recipient, for example EBI.

Click Observe button to display the Event Enrollment –


Acked Transitions dialog box.

In the Event Enrollment – Acked Transitions dialog box,


do the following:

431 EN2Z-0937GE51 R0518


EDITORS CARE

1. In the Name field, change the default name if


desired.
2. In the Description field, enter a meaningful
description if desired.
3. In the Event Type field, note the event type of
the event enrollment object is ´change of
bitstring`.
4. Under Event Parameters, select the transition
event(s) that should be checked for
acknowledge-mint. The List of Values shows the
possible logical values (checked=true,
unchecked=false, CARE verifies with negative
logic for false the condition) resulting from the
comparison of the selected transition event(s)
and the underlying bitstring mask. An event
enrollment alarm will be sent, if the transition
event will not be acknowledged within the delay
time.
5. In the Alarm Delay field, enter an alarm delay in
sec. The event enrollment alarm will be sent if the
transition event has not been acknowledged
within the delay time.
6. From the Notify Type drop-down listbox, select
the notify type.
7. From the Notification Class drop-down listbox,
select the notification class that defines the
supervisory recipient to which the event
enrollment alarm is sent after an
unacknowledged transition.
8. Under Reporting, check the transition event(s)
that should cause an event notification to the
supervisory recipient.

NOTE:
These settings refer to the event enrollment itself
not to the intrinsic reporting properties of the
datapoint:
To-Off-Normal = event notification is sent if the
acknowledgement is missing within the alarm
delay;
Back-To-Normal = event notification is sent if the
acknowledgement is sent after the alarm delay
has been expired.

If you do not check at least one transition event


and one event parameter, the observation is not
enabled.

9. After entering the values, click OK. On the


Properties tab of the datapoint, the Enabled
check box is checked.

Status Flags Allows observing status flags conditions. To enable


observing status flag conditions, click Observe button to
display the Event Enrollment – Status Flags dialog box.

EN2Z-0937GE51 R0518 432


CARE EDITORS

In the Event Enrollment – Status Flags dialog box, do the


following:

1. In the Name field, change the default name if


desired.
2. In the Description field, enter a meaningful
description if desired.
3. In the Event Type field, note that the event type
of the event enrollment object is ´change of
state`.

433 EN2Z-0937GE51 R0518


EDITORS CARE

4. Under Status Flags, select the flags of which


status should be observed. The List of Values
shows the possible logical values (checked=true,
unchecked=false) resulting from the comparison
of the selected status flags and the underlying
bitstring mask.
5. In the Alarm Delay field, enter an alarm delay in
sec. An event enrollment alarm will be sent for
each status flag that is enabled (checked) within
the alarm delay time.
6. From the Notify Type drop-down listbox, select
the notify type.
7. From the Notification Class drop-down listbox,
select the notification class that defines the
supervisory recipient to which the event
enrollment alarm is sent.
8. Under Reporting, check the transition event(s)
that should cause an event notification to the
supervisory recipient.

NOTE:
These settings refer to the event enrollment itself
not to the intrinsic reporting properties of the
datapoint:
To-Off-Normal = event notification is sent if a
status flag is enabled within the alarm delay;
To-Normal = event notification is sent if a status
flag is disabled after the alarm delay has been
expired.

If you do not check at least one transition event


and one event parameter, the observation is not
enabled.

9. After entering the values, click OK. On the


Properties tab of the datapoint, the Enabled
check box is checked.

EN2Z-0937GE51 R0518 434


CARE EDITORS

Multi-State Output Point

Purpose Display and/or modify the attributes of the selected multi-state output point.

Procedure In the tree, click desired point to display current values on the right Properties tab
(itemized display).

or,

in the tree, click on any object (project, controller, plant) which the point belongs to,
and which is in grid display.

To modify values, enter desired values in the fields, and/or select respectively
deselect desired options.

Attributes Description Datapoint Name Point name (maximum of 40 alphanumeric characters)


assigned to a point for operator use in locating and

435 EN2Z-0937GE51 R0518


EDITORS CARE

commanding the point. This name must be unique within


a controller.

Point names must include one non-digit character and


cannot include Tabs, double quotes, ?, *, or space
characters. All other ASCII characters are allowable (A-
Z, 0-9, +, -, _, etc). For example, 12A is a datapoint
name, but 12 is not.

IMPORTANT
Note that the max. length of the datapoint name for Lon
points should not exceed 18 characters (see Lon point
attribute).

BACnet Object Type Displays the BACnet object type.

BACnet Object ID Displays the BACnet object type ID.

BACnet Instance number Displays the BACnet intance number.

Lon Point (Applies to FALCON controller only)


Define whether the datapoint should be a LON point or
not. List of choices displays:

NV-Output
Creates output NV.

Manual Mapping
Provides selection of this datapoint for mapping to NVs in
the NV-Editor.

Reliability status on the Excel Web HTML Interface:

In order to make sure that the Reliability property for the


present value works properly, the service type of the
point must be set to Acknowledged (Ackd). With
acknowledged service, controller - I/O module
disconnections are indicated by the relevant reliability
´No Sensor` or ´No Output`. Note, that if a large number
of outputs (e.g. all outputs of mutiple I/O modules) are
set to acknowledged servcice, the performance on the
LON bus may drastically decrease (see "Change Service
Type for Excel Web Datapoints" section).

Output NV Define the NV-type for the LON point.

State Texts Assign state texts which will be displayed for the
corresponding state of the point. List of choices displays
the number of states and the first two states of state
sequencies which may include mor than two states.
Further texts of state sequencies, will be shown by the
yellow tooltip. Entries are arranged by ID.
To add texts to the list, open the Miscellaneous Text
Editor by clicking the dotted button on the right (Excel
Web Controller, Miscellaneous Text Editor chapter).

Descriptor Supplemental point information. Each project and/or


plant has a unique set of descriptors that can be
assigned to its datapoint names to further describe them.

List of choices displays descriptors with ID and text.


To add and change descriptors in the list, open the
Miscellaneous Text Editor by clicking the dotted button
on the right (see Miscellaneous Text Editor chapter).

Alarm Text Alarm text that displays on point alarm. List of choices
displays alarm texts with ID and text.

EN2Z-0937GE51 R0518 436


CARE EDITORS

To add and change alarm texts in the list, open the


Miscellaneous Text Editor by clicking the dotted button
on the right (see Miscellaneous Text Editor chapter).
Characteristic Assign a characteristic (conversion table) if the datapoint
is to be mapped to a NV (see Lon point attribute). For
Multi-State Inputs, the characteristic +1, for Multi-State
Outputs, the characteristic -1, is provided by CARE by
default. These default characteristics must be used if the
multi-state points are considered to be mapped to NVs.

Read Access Determine whether the user can read datapoint values
Write Access respectively write values to the datapoint in the Web
Interface.

All users having a user level equal or higher than the


assigned read access respectively write access of the
datapoint, will have this access right enabled in the Web
Interface, all others will not (for further details, please
refer to the User Access Manager section).

Notification Class Enable alarming for the datapoint by selecting a


notification class with a given priority. By default the
following notification classes with descending priority can
be selected:

- Urgent
- High
- Low
- Journal

Those default notification classes are especially


designed for the alarming to the EBI central (for
information on notification classes to be used for 3rd party
BACnet clients, please refer to the Notification Class
Manager section)

Each recipient which is assigned to this notification class


will receive the datapoint alarm triggered by the selected
notification. But, alarms will only be generated for the
enabled transitions (To-Normal, To-OffNormal, and/or
To-Fault) of a recipient. Each enabled transition will be
propagated with the selected notification. (For further
details please refer to the Notification Class Manager
section).

This connection has not to be mixed up with the


transitions selected under Reporting (see Reporting
description in the following).

Notify Type If the notification class Urgent, High, or Low has been
selected, the notify type Alarm must be used.

Suppress Alarm Whether or not software should suppress alarm


messages for changes in Fixed Mode and exceeding the
limits.

Alarm Delay Defines the time delay with which a ´To-Off-Normal`


(EAGLE and FALCON controllers) transition and a ´To-
Normal` transition (FALCON controller) will be set off.

Alarm Delay Normal Defines the time delay with which a ´To-Normal`
transition will be set off.
Reporting Define which transition type (To-Normal, To-OffNormal,
and/or To Fault) will be tracked by timestamping in the
Web Interface.

437 EN2Z-0937GE51 R0518


EDITORS CARE

Point Role Point Role created via an external tool like XL Toolkit and
imported into CARE. The point role is selected from XL
Toolkit database.

Relinquish Default Define the value that will be written to present value, if all
values in the priority list are invalid.

Feedback Value Define the datapoint that should provide the value for
feedback control in case of BACnet fault and command
failure alarms. The feedback point must be a binary
input. The selected feedback point will not be available
on the controller HMI and web interface.

NOTE:
The feedback point must not be used in a control loop
since as a result the control loop will not be executed
properly.

Multi-State Properties Check in which state the point should be in the Alarm
and/or in the Fault condition. If enabled, the alarm text of
the corresponding Reporting is displayed.(see Alarm
text).

Status Flags Allows observing status flags conditions. To enable


observing status flag conditions, click Observe button to
display the Event Enrollment – Status Flags dialog box.

EN2Z-0937GE51 R0518 438


CARE EDITORS

In the Event Enrollment – Status Flags dialog box, do the


following:

1. In the Name field, change the default name if


desired.
2. In the Description field, enter a meaningful
description if desired.
3. In the Event Type field, note that the event type
of the event enrollment object is ´change of
state`.

439 EN2Z-0937GE51 R0518


EDITORS CARE

4. Under Status Flags, select the flags of which


status should be observed. The List of Values
shows the possible logical values (checked=true,
unchecked=false) resulting from the comparison
of the selected status flags and the underlying
bitstring mask.
5. In the Alarm Delay field, enter an alarm delay in
sec. An event enrollment alarm will be sent for
each status flag that is enabled (checked) within
the alarm delay time.
6. From the Notify Type drop-down listbox, select
the notify type.
7. From the Notification Class drop-down listbox,
select the notification class that defines the
supervisory recipient to which the event
enrollment alarm is sent.
8. Under Reporting, check the transition event(s)
that should cause an event notification to the
supervisory recipient.

NOTE:
These settings refer to the event enrollment itself
not to the intrinsic reporting properties of the
datapoint:
To-Off-Normal = event notification is sent if a
status flag is enabled within the alarm delay;
To-Normal = event notification is sent if a status
flag is disabled after the alarm delay has been
expired.

If you do not check at least one transition event


and one event parameter, the observation is not
enabled.

9. After entering the values, click OK. On the


Properties tab of the datapoint, the Enabled
check box is checked.

EN2Z-0937GE51 R0518 440


CARE EDITORS

Multi-State Value Point

Purpose Display and/or modify the attributes of the selected multi-state value point.

Procedure In the tree, click desired point to display current values on the right Properties tab
(itemized display).

or,

in the tree, click on any object (project, controller, plant) which the point belongs to,
and which is in grid display.

To modify values, enter desired values in the fields, and/or select respectively
deselect desired options.

Attributes Description Datapoint Name Point name (maximum of 40 alphanumeric characters)


assigned to a point for operator use in locating and

441 EN2Z-0937GE51 R0518


EDITORS CARE

commanding the point. This name must be unique within


a controller.

Point names must include one non-digit character and


cannot include Tabs, double quotes, ?, *, or space
characters. All other ASCII characters are allowable (A-
Z, 0-9, +, -, _, etc). For example, 12A is a datapoint
name, but 12 is not.

IMPORTANT
Note that the max. length of the datapoint name for Lon
points should not exceed 18 characters (see Lon point
attribute).

BACnet Object Type Displays the BACnet object type.

BACnet Object ID Displays the BACnet object type ID.

BACnet Instance number Displays the BACnet intance number.

State Texts Assign state texts which will be displayed for the
corresponding state of the point. List of choices displays
the number of states and the first two states of state
sequencies which may include mor than two states.
Further texts of state sequencies, will be shown by the
yellow tooltip. Entries are arranged by ID.
To add texts to the list, open the Miscellaneous Text
Editor by clicking the dotted button on the right (Excel
Web Controller, Miscellaneous Text Editor chapter).

Descriptor Supplemental point information. Each project and/or


plant has a unique set of descriptors that can be
assigned to its datapoint names to further describe them.

List of choices displays descriptors with ID and text.


To add and change descriptors in the list, open the
Miscellaneous Text Editor by clicking the dotted button
on the right (see Miscellaneous Text Editor chapter).

Alarm Text Alarm text that displays on point alarm. List of choices
displays alarm texts with ID and text.

To add and change alarm texts in the list, open the


Miscellaneous Text Editor by clicking the dotted button
on the right (see Miscellaneous Text Editor chapter).

Read Access Determine whether the user can read datapoint values
Write Access respectively write values to the datapoint in the Web
Interface.

All users having a user level equal or higher than the


assigned read access respectively write access of the
datapoint, will have this access right enabled in the Web
Interface, all others will not (for further details, please
refer to the User Access Manager section).

Notification Class Enable alarming for the datapoint by selecting a


notification class with a given priority. By default the
following notification classes with descending priority can
be selected:

- Urgent
- High
- Low
- Journal

EN2Z-0937GE51 R0518 442


CARE EDITORS

Those default notification classes are especially


designed for the alarming to the EBI central (for
information on notification classes to be used for 3rd party
BACnet clients, please refer to the Notification Class
Manager section)

Each recipient which is assigned to this notification class


will receive the datapoint alarm triggered by the selected
notification. But, alarms will only be generated for the
enabled transitions (To-Normal, To-OffNormal, and/or
To-Fault) of a recipient. Each enabled transition will be
propagated with the selected notification. (For further
details please refer to the Notification Class Manager
section).

This connection has not to be mixed up with the


transitions selected under Reporting (see Reporting
description in the following).

Notify Type If the notification class Urgent, High, or Low has been
selected, the notify type Alarm must be used.

Suppress Alarm Whether or not software should suppress alarm


messages for changes in Fixed Mode and exceeding the
limits.

Alarm Delay Defines the time delay with which a ´To-Off-Normal`


(EAGLE and FALCON controllers) transition and a ´To-
Normal` transition (FALCON controller) will be set off.

Alarm Delay Normal Defines the time delay with which a ´To-Normal`
transition will be set off.
Reporting Define which transition type ((To-Normal, To-OffNormal,
and/or To Fault) will be tracked by timestamping in the
Web Interface.

Point Role Point Role created via an external tool like XL Toolkit and
imported into CARE. The point role is selected from XL
Toolkit database.

Relinquish Default Define the value that will be written to present value, if all
values in the priority list are invalid.

EOH/EOV Optimization Check whether the datapoint should be optimized or not,


in case the datapoint is used as setpoint for energy
optimized heating or ventilation (EOH/EOV).

Setpoint Enables the direct change (override) of the current


datapoint value in the web interface and the controller
HMI without the necessisity of setting the datapoint into
manual mode.

Multi-State Properties Check in which state the point should be in the Alarm
and/or in the Fault condition. If enabled, the alarm text of
the corresponding Reporting is displayed.(see Alarm
text).

Acked Transitions Allows observing the acknowledgement behavior of a


user for To-Off-Normal and To-Fault transition events of
the datapoint. CARE checks whether a transition event
has been acknowledged or not. If a transition event has
not been acknowledged within a definable delay time, an
alarm based on an event enrollment (event enrollment
alarm) is sent to a supervisory recipient, for example EBI.

443 EN2Z-0937GE51 R0518


EDITORS CARE

Click Observe button to display the Event Enrollment –


Acked Transitions dialog box.

In the Event Enrollment – Acked Transitions dialog box,


do the following:

EN2Z-0937GE51 R0518 444


CARE EDITORS

1. In the Name field, change the default name if


desired.
2. In the Description field, enter a meaningful
description if desired.
3. In the Event Type field, note the event type of
the event enrollment object is ´change of
bitstring`.
4. Under Event Parameters, select the transition
event(s) that should be checked for
acknowledgement. The List of Values shows the
possible logical values (checked=true,
unchecked=false, CARE verifies with negative
logic for false the condition) resulting from the
comparison of the selected transition event(s)
and the underlying bitstring mask. An event
enrollment alarm will be sent, if the transition
event will not be acknowledged within the delay
time.
5. In the Alarm Delay field, enter an alarm delay in
sec. The event enrollment alarm will be sent if the
transition event has not been acknowledged
within the delay time.
6. From the Notify Type drop-down listbox, select
the notify type.
7. From the Notification Class drop-down listbox,
select the notification class that defines the
supervisory recipient to which the event
enrollment alarm is sent after an
unacknowledged transition.
8. Under Reporting, check the transition event(s)
that should cause an event notification to the
supervisory recipient.

NOTE:
These settings refer to the event enrollment itself
not to the intrinsic reporting properties of the
datapoint:
To-Off-Normal = event notification is sent if the
acknowledgement is missing within the alarm
delay;
Back-To-Normal = event notification is sent if the
acknowledgement is sent after the alarm delay
has been expired.

If you do not check at least one transition event


and one event parameter, the observation is not
enabled.

9. After entering the values, click OK. On the


Properties tab of the datapoint, the Enabled
check box is checked.

Status Flags Allows observing status flags conditions. To enable


observing status flag conditions, click Observe button to
display the Event Enrollment – Status Flags dialog box.

445 EN2Z-0937GE51 R0518


EDITORS CARE

In the Event Enrollment – Status Flags dialog box, do the


following:

1. In the Name field, change the default name if


desired.
2. In the Description field, enter a meaningful
description if desired.
3. In the Event Type field, note that the event type
of the event enrollment object is ´change of
state`.

EN2Z-0937GE51 R0518 446


CARE EDITORS

4. Under Status Flags, select the flags of which


status should be observed. The List of Values
shows the possible logical values (checked=true,
unchecked=false) resulting from the comparison
of the selected status flags and the underlying
bitstring mask.
5. In the Alarm Delay field, enter an alarm delay in
sec. An event enrollment alarm will be sent for
each status flag that is enabled (checked) within
the alarm delay time.
6. From the Notify Type drop-down listbox, select
the notify type.
7. From the Notification Class drop-down listbox,
select the notification class that defines the
supervisory recipient to which the event
enrollment alarm is sent.
8. Under Reporting, check the transition event(s)
that should cause an event notification to the
supervisory recipient.

NOTE:
These settings refer to the event enrollment itself
not to the intrinsic reporting properties of the
datapoint:
To-Off-Normal = event notification is sent if a
status flag is enabled within the alarm delay;
To-Normal = event notification is sent if a status
flag is disabled after the alarm delay has been
expired.

If you do not check at least one transition event


and one event parameter, the observation is not
enabled.

9. After entering the values, click OK. On the


Properties tab of the datapoint, the Enabled
check box is checked.

447 EN2Z-0937GE51 R0518


EDITORS CARE

Pulse Converter Point

Purpose Display and/or modify the attributes of the selected pulse converter point.

Procedure In the tree, click desired point to display current values on the right Properties tab
(itemized display).

or,

in the tree, click on any object (project, controller, plant) which the point belongs to,
and which is in grid display.

To modify values, enter desired values in the fields, and/or select respectively
deselect desired options.

Attributes Description Datapoint Name Point name (maximum of 40 alphanumeric characters)


assigned to a point for operator use in locating and
commanding the point. This name must be unique within
a controller.

Point names must include one non-digit character and


cannot include Tabs, double quotes, ?, *, or space
characters. All other ASCII characters are allowable (A-
Z, 0-9, +, -, _, etc). For example, 12A is a datapoint
name, but 12 is not.

EN2Z-0937GE51 R0518 448


CARE EDITORS

IMPORTANT
Note that the max. length of the datapoint name for Lon
points should not exceed 18 characters (see Lon point
attribute).

BACnet Object Type Displays the BACnet object type.

BACnet Object ID Displays the BACnet object type ID.

BACnet Instance number Displays the BACnet intance number.

Lon Point (Applies to FALCON controller only)


Define whether the datapoint should be a LON point or
not. List of choices displays:

NV-Input
Creates input NV.

Manual Mapping
Provides selection of this datapoint for mapping to NVs in
the NV-Editor.

Input NV Define the NV-type for the LON point.

Engineering Unit List of choices displays engineering units with ID and


unit.

Descriptor Supplemental point information. Each project and/or


plant has a unique set of descriptors that can be
assigned to its datapoint names to further describe them.

List of choices displays descriptors with ID and text.


To add and change descriptors in the list, open the
Miscellaneous Text Editor by clicking the dotted button
on the right (see Miscellaneous Text Editor chapter).

Alarm Text Alarm text that displays on point alarm. List of choices
displays alarm texts with ID and text.

To add and change alarm texts in the list, open the


Miscellaneous Text Editor by clicking the dotted button
on the right (see Miscellaneous Text Editor chapter).

Scaling Factor Assign and/or create a scaling factor (characteristic), if


the datapoint is mapped to a NV (see Lon point
attribute). To create a scaling factor, open the
Characteristics dialogbox by clicking the dotted button on
the right (see Create and Assign Characteristic to
BACnet Point section).

Read Access Determine whether the user can read datapoint values
Write Access respectively write values to the datapoint in the Web
Interface.
All users having a user level equal or higher than the
assigned read access respectively write access of the
datapoint, will have this access right enabled in the Web
Interface, all others will not (for further details, please
refer to the User Access Manager section).

Notification Class Enable alarming for the datapoint by selecting a


notification class with a given priority. By default the
following notification classes with descending priority can
be selected:

- Urgent

449 EN2Z-0937GE51 R0518


EDITORS CARE

- High
- Low

Those default notification classes are especially


designed for the alarming to the EBI central (for
information on notification classes to be used for 3rd party
BACnet clients, please refer to the Notification Class
Manager section)

Each recipient which is assigned to this notification class


will receive the datapoint alarm triggered by the selected
notification. But, alarms will only be generated for the
enabled transitions (To-Normal, To-OffNormal, and/or
To-Fault) of a recipient. Each enabled transition will be
propagated with the selected notification. (For further
details please refer to the Notification Class Manager
section).

This connection has not to be mixed up with the


transitions selected under Reporting (see Reporting
description in the following).

Notify Type If the notification class Urgent, High, or Low has been
selected, the notify type Alarm must be used.

Suppress Alarm Whether or not software should suppress alarm


messages for changes in Fixed Mode and exceeding the
limits.

Alarm Delay Defines the time delay with which a ´To-Off-Normal`


(EAGLE and FALCON controllers) transition and a ´To-
Normal` transition (FALCON controller) will be set off.

Alarm Delay Normal Defines the time delay with which a ´To-Normal`
transition will be set off.

High Limit Enable If a high limit is exceeded and this condition remains
present for at least the defined alarm delay (time), than
an alarm of event type ´To-Off-Normal` is set off.
Define whether a high limit exceeding should be
considered or not.

Low Limit Enable If the present value falls below the low limit and this
condition remains present for at least the defined alarm
delay (time), than an alarm of event type ´To-Off-Normal`
is set off.
Defines whether a low limit exceeding should be
considered or not.

Deadband Define the value of the deadband in order to set off an


alarm of event type ´To-Normal`. For this, the present
value must, for at least the defined alarm delay (time),
remain within the range:
Low limit plus deadband and high limit minus deadband.

Reporting Define which transition type ((To-Normal, To-OffNormal,


and/or To Fault) will be tracked by timestamping in the
Web Interface.

Point Role Point Role created via an external tool like XL Toolkit and
imported into CARE. The point role is selected from XL
Toolkit database.

Change of Value Define the change of the value increment (COV).


Increment The COV increment specifies the minimum change in
present value that causes the controller sending the

EN2Z-0937GE51 R0518 450


CARE EDITORS

present value to the Web Interface or other recipients on


the BACnet bus (e.g. EBI). Defines the amount of time in
seconds between the periodic transmissions of the
present value. This property can be used alone or in
combination with the Increment property. When the
period property is used in combination with the increment
property, the present value will always be updated
periodically independent on the transmissions of the
present value due to the COV setting.

Example:

Increment Period Present Value Update


0,2 K when present value has
changed by 0,2 K or more
3s every 3 s
0,2 K 3s every 3 s and when present
value has changed by 0,2 K
or more

Acked Transitions Allows observing the acknowledgement behavior of a


user for To-Off-Normal and To-Fault transition events of
the datapoint. CARE checks whether a transition event
has been acknowledged or not. If a transition event has
not been acknowledged within a definable delay time, an
alarm based on an event enrollment (event enrollment
alarm) is sent to a supervisory recipient, for example EBI.

Click Observe button to display the Event Enrollment –


Acked Transitions dialog box.

451 EN2Z-0937GE51 R0518


EDITORS CARE

In the Event Enrollment – Acked Transitions dialog box,


do the following:

EN2Z-0937GE51 R0518 452


CARE EDITORS

1. In the Name field, change the default name if


desired.
2. In the Description field, enter a meaningful
description if desired.
3. In the Event Type field, note the event type of
the event enrollment object is ´change of
bitstring`.
4. Under Event Parameters, select the transition
event(s) that should be checked for
acknowledgement. The List of Values shows the
possible logical values (checked=true,
unchecked=false, CARE verifies with negative
logic for the false condition) resulting from the
comparison of the selected transition event(s)
and the underlying bitstring mask. An event
enrollment alarm will be sent, if the transition
event will not be acknowledged within the delay
time.
5. In the Alarm Delay field, enter an alarm delay in
sec. The event enrollment alarm will be sent if the
transition event has not been acknowledged
within the delay time.
6. From the Notify Type drop-down listbox, select
the notify type.
7. From the Notification Class drop-down listbox,
select the notification class that defines the
supervisory recipient to which the event
enrollment alarm is sent after an
unacknowledged transition.
8. Under Reporting, check the transition event(s)
that should cause an event notification to the
supervisory recipient.

NOTE:
These settings refer to the event enrollment itself
not to the intrinsic reporting properties of the
datapoint:
To-Off-Normal = event notification is sent if the
acknowledgement is missing within the alarm
delay;
Back-To-Normal = event notification is sent if the
acknowledgement is sent after the alarm delay
has been expired.

If you do not check at least one transition event


and one event parameter, the observation is not
enabled.

9. After entering the values, click OK. On the


Properties tab of the datapoint, the Enabled
check box is checked.

Status Flags Allows observing status flags conditions. To enable


observing status flag conditions, click Observe button to
display the Event Enrollment – Status Flags dialog box.

453 EN2Z-0937GE51 R0518


EDITORS CARE

In the Event Enrollment – Status Flags dialog box, do the


following:

1. In the Name field, change the default name if


desired.
2. In the Description field, enter a meaningful
description if desired.
3. In the Event Type field, note that the event type
of the event enrollment object is ´change of
state`.

EN2Z-0937GE51 R0518 454


CARE EDITORS

4. Under Status Flags, select the flags of which


conditions should be observed. The List of
Values shows the possible logical values
(checked=true, unchecked=false) resulting from
the comparison of the selected status flags and
the underlying bitstring mask.
5. In the Alarm Delay field, enter an alarm delay in
sec. An event enrollment alarm will be sent for
each status flag that is enabled (checked) within
the alarm delay time.
6. From the Notify Type drop-down listbox, select
the notify type.
7. From the Notification Class drop-down listbox,
select the notification class that defines the
supervisory recipient to which the event
enrollment alarm is sent.
8. Under Reporting, check the transition event(s)
that should cause an event notification to the
supervisory recipient.

NOTE:
These settings refer to the event enrollment itself
not to the intrinsic reporting properties of the
datapoint:
To-Off-Normal = event notification is sent if a
status flag is enabled within the alarm delay;
To-Normal = event notification is sent if a status
flag is disabled after the alarm delay has been
expired.

If you do not check at least one transition event


and one event parameter, the observation is not
enabled.

9. After entering the values, click OK. On the


Properties tab of the datapoint, the Enabled
check box is checked.

Warning Limits Allows defining warning limits for observing the present
value and sending event enrollment alarms in case the
present value increases or decreases the warning limits.
To define warning limits, click Define button to display
the Event Transitions dialog box.

455 EN2Z-0937GE51 R0518


EDITORS CARE

In the Warning Limits for Present Value dialog box, do


the following:

EN2Z-0937GE51 R0518 456


CARE EDITORS

1. In the Name field, change the default name if


desired.
2. In the Description field, enter a meaningful
description if desired.
3. In the Event Type field, note that the event type
of the event enrollment object is ´change of
state`.
4. In the High Warning Limit field, enter the high
warning limit value.
5. In the Low Warning Limit field, enter the low
warning limit value.

NOTE: The warning limits can be below or above


the high and low limit reporting values.

6. In the Deadband field, enter a deadband value.


This defines an additional trigger to set off an
alarm. The event enrollment alarm is sent if the
following condition is true:
present value must, for at least the defined alarm
delay (time), remain within the range: Low limit
plus deadband and high limit minus deadband.
7. In the Alarm Delay field, enter an alarm delay in
sec. The even enrollment alarm is sent if the
present value still increases or decreases the
warning limits after the time entered here has
been elapsed.
7. From the Notify Type drop-down listbox, select
the notify type.
8. From the Notification Class drop-down listbox,
select the notification class that defines the
supervisory recipient to which the event
enrollment alarm is sent.
9. Under Reporting, check the transition event(s)
that should cause an event notification to the
supervisory recipient.

NOTE:
These settings refer to the event enrollment itself
not to the intrinsic reporting properties of the
datapoint:
To-Off-Normal = event notification is sent if the
present value exceeds or falls below the high or
low warning limits within the alarm delay;
Back-To-Normal = event notification is sent if the
present value is within the high or low warning
limits after the alarm delay has been expired.

If you do not check at least one transition event


and one event parameter, the observation is not
enabled.

10. After entering the values, click OK. On the


Properties tab of the datapoint, the Enabled
check box is checked.

Reference Datapoints

If your control and monitoring system contains more than one controller, the con-
trollers communicate with one another via BACnet/IP and/or via BACnet MS/TP.
This enables one controller both to read and set the datapoints from other

457 EN2Z-0937GE51 R0518


EDITORS CARE

controllers, and to read values of 3rd-party BACnet devices of the project and
external BACnet devices which are not in the project.

This data communication is realized via so-called reference input/output points.


They always originate in or write to another plant and may originate in or write to
another controller. For data communication between 2 controllers or between a
controller and 3rd party devices, reference datapoints can be used in control loops
(see "Working with Reference Datapoints" in the CONTROL LOOPS chapter).
Data communication between a controller and 3rd party devices can also be
established by assigning BACnet datapoint objects to reference datapoints of the
controller (see "Create BACnet 3rd Party Device" in the BACnet NETWORK
ENGINEERING chapter).

BACnet-Bus Data

CONTROLLER A CONTROLLER B / 3rd Party DEVICE


Data

Plant A1 Plant A2 Plant B1

Source Point Receiver Point Source Point

Physical Point or Reference Physical Point or


Value Point Input Point Value Point

NOTE: Controllers / 3rd Pary Devices can be in the same or in different projects.

Example: data exchange via reference input datapoint

Reference Input Point

Purpose Display and/or modify the attributes of the selected reference input point.

Procedure In the tree, click desired point to display current values on the right Properties tab
(itemized display).

or,

in the tree, click on any object (project, controller, plant) which the point belongs to,
and which is in grid display.

To modify values, enter desired values in the fields, and/or select respectively
deselect desired options.

Attributes Description Datapoint Name Point name (maximum of 40 alphanumeric characters)


assigned to a point for operator use in locating and

EN2Z-0937GE51 R0518 458


CARE EDITORS

commanding the point. This name must be unique within


a controller.

Point names must include one non-digit character and


cannot include Tabs, double quotes, ?, *, or space
characters. All other ASCII characters are allowable (A-
Z, 0-9, +, -, _, etc). For example, 12A is a datapoint
name, but 12 is not.

IMPORTANT
Note that the max. length of the datapoint name for Lon
points should not exceed 18 characters (see Lon point
attribute).

BACnet Object ID Displays the BACnet object ID.

BACnet Object Type Displays the BACnet object type.

BACnet Intance Number Displays the BACnet instance number.

Reference Select reference (source) point, the reference input


(receiver) should be assigned to.
To add a point, click Add button right to the Property
field.

In the Select Reference Point dialog box displayed,


expand the project tree.

459 EN2Z-0937GE51 R0518


EDITORS CARE

Select the point, and then click OK.

NOTE:
If the reference point is already assigned to a source
point, the source point is highlighted in the project tree.
You can select another source point in the tree.

The assigned source point is displayed in the Reference


field on the Properties tab of the reference input.

EN2Z-0937GE51 R0518 460


CARE EDITORS

To delete a point, click Del button and select the point in


the same way as for adding a point in the Select
Reference Point dialog box.

Property Displays the present value property

Initial Value Enter an initial value, which will be utilized at system


startup if the reference input has not yet received a value
from the connected point.

Individual Check the check box to enter the value for the poll rate.

Poll rate In case the connected datapoint does not support COV,
the poll rate defines the interval in sec, that the reference
input polls the connected data point.
If the connected data point does support COV, then the
poll rate has no effect. So the poll rate does not ensure a
fault signal within the poll rate time when a connection is
lost. In case of a loss of communication, the fault flag will
be set latest after 30 minutes

Read Access Level Determine whether the user can read datapoint values
Write Access Level respectively write values to the datapoint in the Web
Interface.

All users having a user level equal or higher than the


assigned read access respectively write access of the
datapoint, will have this access right enabled in the Web
Interface, all others will not (for further details, please
refer to the User Access Manager section).

Reference Output Point

Purpose Display and/or modify the attributes of the selected reference output point.

Procedure In the tree, click desired point to display current values on the right Properties tab
(itemized display).

or,

461 EN2Z-0937GE51 R0518


EDITORS CARE

in the tree, click on any object (project, controller, plant) which the point belongs to,
and which is in grid display.

To modify values, enter desired values in the fields, and/or select respectively
deselect desired options.

Attributes Description Datapoint Name Point name (maximum of 40 alphanumeric characters)


assigned to a point for operator use in locating and
commanding the point. This name must be unique within
a controller.

Point names must include one non-digit character and


cannot include Tabs, double quotes, ?, *, or space
characters. All other ASCII characters are allowable (A-
Z, 0-9, +, -, _, etc). For example, 12A is a datapoint
name, but 12 is not.

IMPORTANT
Note that the max. length of the datapoint name for Lon
points should not exceed 18 characters (see Lon point
attribute).

BACnet Object ID Displays the BACnet object ID.

BACnet Object Type Displays the BACnet object type.

BACnet Intance Number Displays the BACnet instance number.

Reference Select reference point, the reference input should be


assigned to. To add or delete a point, please refer to the
corresponding description of the reference input point.

Initial Value Enter an initial value, which will be utilized at system


startup if the reference output has not yet received a
value from the connected point.

Individual Check the check box to enter then values for max. send
time and/or Send on delta.

Max. send time The max. send time defines the maximum period of time
in sec. that must be expired before the datapoint
automatically transmits the current value.
Send on delta Send on delta determines the minimum amount of
change of the sensed value before a new value is sent

Priority for Writing Select the priority for writing.

Read Access Level Determine whether the user can read datapoint values
Write Access Level respectively write values to the datapoint in the Web
Interface.

All users having a user level equal or higher than the


assigned read access respectively write access of the
datapoint, will have this access right enabled in the Web
Interface, all others will not (for further details, please
refer to the User Access Manager section).

EN2Z-0937GE51 R0518 462


CARE EDITORS

Copy Attribute Values within the Grid


Purpose Copy one or a number of attribute values from one or several points to one or more
other points. Values can be numeric values, for example delay time, or text, for
example, alarm text. The source and target point must be of the same kind, that is, it
is possible to copy attributes from analog inputs to analog inputs but you cannot
copy attributes from analog inputs to analog outputs, etc. You also cannot copy the
same kind of attribute value from different points to another point. That is, you
cannot copy the sensor-offset values of two different analog inputs to another
analog input.

Procedure 1. In the grid, click the attribute you want to copy.

2. If you want to copy a number of attributes, press STRG key and hold it while
clicking further attributes.

3. Release STRG key.

4. Select menu item Edit, and click Copy

or,

with right mouse button, click outside the last field you have selected, and then
Copy in the context menu.

5. In the point abbreviations bar, click the target point(s) you want the selected
attributes copy to.

RESULT: The rows are highlighted.

6. Click right mouse button and then Paste in the context menu or, select menu
item Edit, then drop-down item Paste.

RESULT: In the selected rows, the attributes are pasted into the
corresponding fields.

463 EN2Z-0937GE51 R0518


EDITORS CARE

Simply Copy Values and Texts without Validity Checking


To simply copy a value or text from one field to another without validity checking you
can use the Copy, Cut and Paste icons on the button bar.

IMPORTANT
When using the Copy, Cut and Paste icons for copying values/texts,
software does not perform validity checking, that is, you have to realize
which value/text you are copying to which field.

Procedure 1. In the grid, click the field from which you want to copy (or cut) the value or text.

NOTE: When using the Cut icon, the value/text will be deleted in the field.

2. On the button bar, click copy (or cut) icon.

3. In the grid, click the field to which you want to paste the value or text.

4. On the button bar, click Paste icon.

RESULT: The copied and cut value/text respectively is pasted into the
field. The current value/text will be overwritten.

5. To copy the same value/text to further fields repeat steps 3 to 4.

Copy Attribute Values per Drag and Drop within the Tree
Purpose Copy one or max. all attributes values from one point to one or more other points of
the same kind. The source and target point(s) must be of the same kind, that is, it is
possible to copy attributes from analog inputs to analog inputs but you cannot copy
attributes from analog inputs to analog outputs, etc. This function is suitable for
quickly copying many (at most all) attributes of one point to another point or a high
number of points.

Procedure 1. In the tree, select the point, which you want to copy the attributes from.

2. On the right, check the attribute values and correct some, if desired.

3. With left mouse button, click already selected point in the tree, and drag it to the
desired target point of the same kind. While dragging, a plus symbol is
displayed at the cursor indicating that dropping of the attributes on the point
where the cursor currently stands, is possible. The current technical addresses
are displayed in tool tips. Invalid target points where attributes cannot be
dropped on are indicated by the forbidden symbol at the cursor.

EN2Z-0937GE51 R0518 464


CARE EDITORS

4. Over the target point, release left mouse button.

RESULT: The Configure Drag and Drop dialog box displays.

5. In the list, select the attributes you want to drop on the target point by checking
the corresponding check boxes. Use Default button to select all attributes. Use
Clear All button to deselect all attributes and reselect desired attributes.

RESULT: The selected attributes are dropped on the target point (cursor
position). In grid display, the grid will be concurrently updated.

To generally configure Drag and Drop options for point types, please refer to the
Configure Drag and Drop section.

Search and Replace Attribute Settings


Purpose Modify all or selected attribute settings in a controller by searching and replacing.
Attribute values can be of very different type, for example: Alarm Text = Firealarm,
Alarm Delay = 10 sec, Hide Point = checked, etc. You can search for any type of
attribute and replace its setting. For example, you can search for points that have
the alarm delay of 10 sec and replace it with 5 sec.
Examples:

465 EN2Z-0937GE51 R0518


EDITORS CARE

Selected Attribute Search Entry / Selection Replace Entry


Alarm Text Firealarm or *F Phone 733
Alarm Delay 10 5
Hide Point = checked =unchecked

Procedure 1. In the logical plant tree, click on desired controller in the tree.

2. Click menu item Edit, then drop-down item Search & Replace…

RESULT: The Search & Replace dialog box displays.

3. Click into the Attribute field and select desired attribute, you want to change the
settings for.

4. In the Search field, enter the search string (whole term or part of the term) for
the attribute setting.

5. In the Replace field, enter/select the setting you want to replace with.

EN2Z-0937GE51 R0518 466


CARE EDITORS

6. Check Match Case, if you want to consider the case (only applicable for user
address attribute, see Rename Points and NVs section).

7. Check Rename Global Points, if desired (only applicable for user address
attribute, see Rename Points and NVs section).

8. Check only use selected controller if you only want to search in the selected
Controller. If this option is unchecked, software searches in the whole tree
including all controllers.

9. Check Rename mapped NVs if you want to rename NVs in the same way as
the mapped datapoints (only applicable for user address attribute, see Rename
Points and NVs section).

IMPORTANT
When only "use selected Controller" is checked and "Rename Global Points"
too, global points may not find the referenced points in the other controller.

10. Click OK to initiate the first Search.

RESULT: If software does not find any matches, it displays a message to that
effect. You can change the search string to initiate other searches.
If software finds a matching setting, the Search and Replace dialog
box opens showing the point with the setting you have searched
for. Depending on the selected attribute the Search & Replace
dialog box displays different results:

For attributes with simple values, for example alarm delay, the respective
values will be shown.

For attributes which can have two alternative states, for example, checked or
unchecked, the state will be shown as 1 for checked and 0 for unchecked.

467 EN2Z-0937GE51 R0518


EDITORS CARE

11. To change the setting for the found user address as specified in the Replace
string, click Replace.

To find the next user address that matches the criteria, click Find Next.

To change the found user address plus all other addresses that match the
criteria , click Replace All.

RESULT: Software changes the attribute settings as specified.

Rename Points and NVs

Purpose Modify all or selected user addresses in a controller either by searching for strings
(whole user address or alphanumerical items: e.g. L22, RoomTemp, etc.) and
replacing them or by adding characters to the beginning or end of user addresses.
To directly rename a point, refer to the Edit User Address section.

Procedure 1. In the logical plant tree, click on desired controller in the tree.

2. Click menu item Edit, then drop-down item Search & Replace…

RESULT: The Search & Replace dialog box displays.

3. Check Match Case if character strings should be find that match upper and
lower case letters. For example, if you check Match Case and enter a search
string of Oa, software does not find OA or oa.

4. Check Rename Global Points, if global datapoints should be renamed too.

5. Check only use selected Controller if only the names in the currently selected
controller should be changed.

IMPORTANT
When "only use selected Controller" is checked and "Rename Global Points"
too, global points may not find the referenced points in the other controller.

EN2Z-0937GE51 R0518 468


CARE EDITORS

6. Check Rename mapped NVs if mapped NVs should be changed in the same
way as their datapoints.

Example:

User address of datapoint: BaTemp becomes DaTemp


NV name of mapped datapoint: nviaBaTemp becomes nviDaTemp

7. Choose whether to search for and replace special strings in user addresses or
just add characters to the beginning or to the end of user addresses by using
the corresponding option under:

Replacement
If this option is selected, the string (characters) of user addresses entered in the
Search field will be replaced with the string entered in the Replace field.

Example:

In the Search field, type *Oa to search for all user addresses that contain the
letters Oa. In the Replace field, type the characters you want to substitute when
software finds the search string. For example, type Ra to replace the string Oa.

Prefix
If this option is selected, the user addresses that match the string (characters)
entered in the Search field will be prefixed with the string entered in the Replace
field. That is, the string entered in the Replace field will be added to the
beginning of user addresses.

Example:

In the Search field, type *L22, and in the Replace field, type CPU1_. The item
CPU1 is added to the beginning of the user address that matches the criteria
L22, independent where L22 stands within the user address.

Append
If this option is selected, the string entered in the Replace field will be appended
to the end of the user addresses that match the string (characters) entered in
the Search field.

Example:

In the Search field, type *L22, and in the Replace field, type _DEMO. The item
Demo is added to the end of the user address that matches the criteria L22,
independent where L22 stands within the user address.

8. Click into the Attribute field and select User Address.

9. In the Search field, enter the search string (whole or part of the user address),
and in the Replace field, enter the string, which should replace the search string
or should be added to the beginning (Prefix) or to the end (Append) of the user
address.

Search String Conventions


To search successfully, you must either enter the whole name of the user
address or use the wildcard ? or the joker * for a string, which is naturally
shorter than to enter the whole user address. The joker * stands for any number
of characters, the wildcard ? stands for one character. When using the wildcard
?, the string including the ? must match the exact wording and sequence as it is
in the user address. They have to be entered in one of the following ways:

Example:

Search (within) the string LMM22:

*LMM22
?MM22
LMM2?
?M?2?

469 EN2Z-0937GE51 R0518


EDITORS CARE

IMPORTANT
Although when creating user addresses * and ? cannot be used, this joker
and wildcard has to be used for the Search string. Do not use them for the
Replace string.

When searching for and replacing user addresses, the search string will be
found at any location within the user address (see Valid User Addresses
Note at the end of this section). For example, when applying the search
criterion "D*", both, user addresses such as DO_Feedback where the "D"
appears at the beginning and user addresses such as "L08Zone1Dmpr"
where the "D" appears in the middle will be found. When using the Replace
All button then it may result in undesired user addresses.

10. Enter desired criteria for renaming the user addresses. Keep in mind the rules
for user address name; see the Valid User Addresses note that follows this
procedure.

11. Click OK to initiate the first Search.

RESULT: If software does not find any matches, it displays a message to that
effect. You can change the search string to initiate other searches.

If software finds a matching user address, it displays it in the


Search and Replace dialog box. The search results are different
depending on the option, which was selected (Replacement, Prefix,
Append).

Search result examples:

Replacement function

EN2Z-0937GE51 R0518 470


CARE EDITORS

Prefix function

Append function

12. To change the found user address as specified in the Replace string, click
Replace.

To find the next user address that matches the criteria, click Find Next.

To change the found user address plus all other addresses that match the
criteria , click Replace All.

RESULT: Software changes the user addresses as specified.

Valid User Addresses User addresses can be a maximum of 18 characters and must include one non-digit
character. They cannot include Tabs, double quotes, ?, *, or space characters. All
other ASCII characters are allowable (A-Z, 0-9, +, -, _, etc). For example, 12A is a
valid user address, but 12 is not.

Quick Search in Tree


Purpose Quickly search in the tree. You can search for user addresses, projects, controllers,
plants, names of NVs, CPTs, and program Ids and neuron Ids of devices.

Procedure 1. In the logical plant tree or in the network tree, click on desired item (project,
controller, etc.) where the search should start.

2. Click on menu item Edit, then drop-down item Quick Search

or,
when in grid display, point cursor over the grid.
Click right mouse button and click on Quick Search in the context menu.

RESULT: The Quick Search dialog box displays.

471 EN2Z-0937GE51 R0518


EDITORS CARE

3. In the Find what field, enter the item you want to search for.

4. Select desired options under:

Whole Word only


If this option is checked, software searches for occurrences that are whole
words, and not part of a larger word. If this option is unchecked, software
searches for occurrences of the search item in any word that includes the
search item.

Case sensitive
If this option is checked, software distinguishes between upper and lower case
letters.

Including

Project Name
If this option is checked, all project names are included in the search.

Controller Names
If this option is checked, all controller names are included in the search.

Plant Names
If this option is checked, all plant names are included in the search.

Datapoint Names
If this option is checked, all datapoints (user addresses) are included in the
search.

Direction
Check desired direction, Up or Down, by clicking the corresponding radio
button. The search starts from the highlighted item in the tree.

EN2Z-0937GE51 R0518 472


CARE EDITORS

Network Tree
By selecting one of the options in the Look for drop-down listbox, you can
search for items in the network tree, such as names of NVs, CPTs etc., and
program Ids and neuron Ids of devices that reside in the network tree.

5. Click Find button.

NOTE: Make sure that you have selected the appropriate tree (logical plant
tree, network tree) and the desired item in the network tree (e.g.
project, controller) to which the software should apply the search.

RESULT: In the toolbar, the search item is displayed in the Quick Search
field.

The Quick Search field allows searching more quickly later without
opening the Quick Search dialog box from the Edit menu. When
using this function keep in mind the settings of the Quick Search
dialog box.

If the search is successful, the Quick Search dialog box closes, and
software highlights the first found item in the tree or grid.

If no text is found, that matches the search item, a corresponding


message is displayed. Confirm the message and try again by
entering a new search item in the Find what field.

6. To continue a successful search with the same search item, press ENTER key.
If more items match the search criteria, the next found item is highlighted, etc.

Use Filters
Purpose Display points which have equal attribute settings. For example, you can display all
hidden points, all points, which reside on module 3, or all points that have a delay
time of 10 sec. The filter function can be used in both, the tree and the grid, and they
can be used together. The filter function for the tree is more extensive whereas the
filter function for the grid can be used quicker. Refer to the following sections for
detailed descriptions of the filter functions.

Apply Filter in Tree

Purpose Display points which have equal attribute settings. For example, you can display all
disabled points, or all points that have a delay time of < 10 sec, or a trend hysteresis
value of >15 °C, etc. You can also combine filter criteria that is for example, you can
display all disabled points, which have a delay time of < 10 sec. In addition to the
operator =, the operators <, >, ≤, ≥, not= can be used. .In opposite to the filter
function in the grid, you can define filters and save them for reuse. Saved filters can
be deleted.

Procedure 1. In the logical plant tree, click on the project, controller or plant.

2. Click on menu item Options, then drop-down item Filter Configuration

or,
click Configure Filter button on the toolbar

or,

when in grid display, point cursor over the grid.


Click right mouse button, select Options and click on Filter in the context menu.

RESULT: The Filter dialog box is displayed.

473 EN2Z-0937GE51 R0518


EDITORS CARE

3. In the first line, click in the Attribute field and select desired attribute.

Example:

You want to display all hidden points, that is, all points, which have the attribute
´Hide Point` checked.

Select Hide Point in the Attribute field.

4. In the Operator field, select the operator. Operators are depending on the
selected attribute. For the attribute Hide Point the operator = is available.

5. In the Value(s) field, enter/select the value the attribute should have. Values are
depending on the selected attribute. To display hidden points in the tree, check
the check box in the Value(s) field.

RESULT: In the filterline below, the term entered in line one is indicated by its
line number (1). When entering additional lines, the terms (lines)
will be automatically combined via ANDs and displayed, for
example, as follows: 1 and 2 (see AND and OR combination at the
end of the section).

The filter is defined as temporary filter. This is shown by the word


temporary Filter in the top list box field. A temporary filter will not be
saved when closing the dialog box by clicking OK. It must be
redefined for the next application.

6. To save the filter, click into the top list box field, highlight current entry, press
key, and enter the name for the filter you want to define, e.g. hidden points.

EN2Z-0937GE51 R0518 474


CARE EDITORS

7. Confirm by clicking OK.

8. In the Standard toolbar, click on the filter on/off icon .

RESULT: All points matching the defined filter, in this case, all hidden points,
are displayed in the tree.

Delete Filter Select filter in the drop-down list box and click Delete this Filter.

AND and OR combination When entering more than one line, the lines are automatically combined via ANDs.
But, lines can also be combined via ORs. To combine two lines via OR, click into the
line, delete “and” and enter “or”. It is recommended to use brackets.

Example:

(1 or 2) and 3

475 EN2Z-0937GE51 R0518


EDITORS CARE

Apply Filter in Grid

Purpose Display point s, which have equal attribute settings. For example, you can display all
disabled points, all points that have a delay time of 10 sec, or a trend hysteresis
value of 15 °C, etc. In opposite to the filter function in the tree, you cannot define
filters and save them for reuse. After quitting the current grid by selecting another
object in the tree, the filter will be discharged. You can use the operators <, >, ≤, ≥,
and not=..

Procedure 1. Select menu item Options, then drop-down item Grid configuration to open the
Configure Grid dialog box.

2. Check Filterline in Grid.

3. If not already done, display the desired grid by selecting the corresponding
object in the tree (see Tree and Information Display section).

RESULT: In the first row of the grid, the Filter line is displayed.

In the Filter line you can enter the filter criteria into the respective attribute
fields. When entering more than one criterion they will be combined to an AND.
Grayed fields are disabled.

Example:

You want to display all points on module 4, which have active state = 1.

4. In the Filter line, click on the Techn. Address field and replace the two jokers in
the middle with 04.

5. With scroll bar on the bottom, scroll to the Active State column.

6. In the Filter line, click on the Active State field and select 1.

RESULT: Just after leaving the Techn. Address field and while editing the
Active State field, all points on module 4 are displayed.

EN2Z-0937GE51 R0518 476


CARE EDITORS

After leaving the Active State field with desired selection, all points
on module 4 with the Active State attribute set to 1, are displayed in
the grid.

7. To discard the filter, enter/select the original settings or, click on any object in
the tree.

Create Report
Purpose In large applications it can be necessary to find specific information of datapoints.
You can search for the usage of datapoints on project, controller, plant and control
loop level. Found datapoints can be detected in the control loop by double-clicking
from within the report displayed.

Procedure

1. Right-click the level (project, controller, plant or control loop) in which you want
to search for the used datapoints, and then click Show datapoints usage in
the context menu.

RESULT: The Find dialog box displays.

477 EN2Z-0937GE51 R0518


EDITORS CARE

2. In Information Type, the applied search command is pre-selected. The


information type Datapoints usage searches for datapoints that match the
datapoint type pre-selection and the filter criteria (see below). If datapoint
attributes are part of functions or time programs the functions and time
programs will also be listed.

3. From the Datapoint Type drop-down listbox, you can select a datapoint type
for which you want to search specifically.

4. In Filter, you can enter a search string using wildcards to narrow down further
the result.

5. In Search Context, select the level (project, controller, plant and control loop)
on which the search should be executed. Note that software searches in the
selected level and automatically in the levels that are hierarchically below the
selected level. Under Search Context on the right, the levels are displayed.

RESULT: Under Search Result the found items are displayed and
automatically updated according to the selected information
type. The following properties are shown:

• Function
function type
• Symbol
instance name
• Datapoint
datapoint name
• Control loop
control loop the found item belongs to
• Plant
plant the found item belongs to

EN2Z-0937GE51 R0518 478


CARE EDITORS

• Controller
controller the found item belongs to

6. To detect a found item in the control loop, double-click the item in the list.

RESULT: The item is selected in the control loop.

7. To apply various searches, change the search criteria under Find as desired.

RESULT: The list will be updated automatically.

Configure Drag and Drop


Purpose Define attributes, which should be copied from one, point to one or more other
points of the same kind via drag and drop function within the tree.

Procedure 1. Click on menu item Options, then drop-down item Drag and Drop…

or,
click Configure Drag and Drop button on the toolbar

or,

when in grid display, point cursor over the grid.

Click right mouse button, select Options and click on Drag and Drop in the
context menu.

RESULT: The Configure Drag and Drop dialog box displays.

2. In the drop-down list, select the point type.

RESULT: The Attributes for the point type display in a list.

479 EN2Z-0937GE51 R0518


EDITORS CARE

3. In the drop column check the attributes, which should be dropped on the target
point(s). Use Default button to select all attributes. Use Clear All button to
deselect all attributes and reselect desired attributes.

4. Check Not display this Dialog on Drag and Drop, if you do not want to display
the Configure Drag and Drop dialog box during Dragging and Dropping. In this
case keep in mind, which attributes are enabled/disabled for drag and drop.

or,

uncheck Not display this Dialog on Drag and Drop, if you want to display the
Configure Drag and Drop dialog box during every Dragging and Dropping. In
this case, you can check, which attributes are enabled/disabled before finally
dropping the attributes to target point(s). If desired, you can change settings.

5. Confirm by clicking OK.

EN2Z-0937GE51 R0518 480


CARE EDITORS

For detailed instructions of the Drag and Drop function, please refer to the Copy
Attribute Values per Drag and Drop within the Tree section

Assign Color Map to Datapoint


Purpose Assign a color map to a datapoint. Color maps provide the possibility to assign
colors to different states of a datapoint. When viewing the datapoint on a central, the
datapoint is visualized in colors depending on its current state.

Prerequisites The color map must be created using the Miscellaneous Text Editor (see
"Miscellaneous Text Editor (CARE BACnet" section) before you can assign it to a
datapoint.

Procedure 1. In the logical plant tree, right-click the datapoint, and then click Assign Color
Map ... in the context menu.

RESULT: The Assign Color Maps dialog box displays.

2. In the Color map name column, select the color map from the drop-down list
box.

RESULT: On the right, the color map properties (State, Min Value, Max
Value, and Color) are displayed. If the values need to be
changed, invoke the Miscellaneous Text Editor and change the
color map as desired.

3. Click OK.

RESULT: The dialog box is closed and the color map is assigned to the
datapoint.

Print Datapoint Descriptions


To print Datapoint descriptions see Print Documentation chapter.

481 EN2Z-0937GE51 R0518


EDITORS CARE

Miscellaneous Text Editor (CARE XL-5000)


Purpose Provide functions to define, edit, copy, and replace Engineering Units, Point
Descriptors, Alarm Texts, and Characteristics. These functions can only be
accessed from within the Datapoint Editor in three ways:

• via menu Options, drop-down item Edit Text


• from within the itemized display for a point
• from within the grid via right mouse button

General Procedure 1. Select the controller in the logical plant tree.

2. Click on menu item Options, then drop-down item Edit Text, and text type
(Analog Eng. Units, Descriptors, etc.) you want to edit.

or,

if you are working on a point in itemized display, click corresponding dotted


button in the Misc. Text Editor area.

or,

if you are working in the grid, select corresponding text field (Engineering unit,
Descriptor, etc.), click right mouse button, and then MiscEdit in the context
menu.

RESULT: The Miscellaneous Text Editor dialog box is displayed. The dialog
box title is named according to the text type selected in the Edit
Text menu or where the dotted button refers to. The corresponding
texts are listed and indicated by their IDs. For characteristics, the
reference points are displayed additionally. Default texts are
displayed with a check mark in the Default column, customized
texts do not. Texts, which are already used by at minimum one
point are displayed with a check mark in the Used column (only
display). Both, used and unused texts can be edited.

Create new text 3. To create a new text, select an empty line and enter desired text. For
engineering units select options in the additional fields (decimal places, number,
and state). For characteristics enter reference point values.

Edit text 1. Make step 1 of General Procedure.

EN2Z-0937GE51 R0518 482


CARE EDITORS

2. Make step 2 of General Procedure.

3. To edit text, locate line, click into the field and write over text.

and/or,

change options for engineering units in the additional fields (decimal places,
number, and state). For characteristics change reference point values.

NOTE: If the text is originally indicated as default text (checked check box in
the Default column), then any changes and deletions (blank text field)
are indicated by an unchecked check box in the Default column.

4. To display and edit different texts than currently displayed, click down arrow at
the top and select desired text type.

RESULT: A Message is displayed asking for the storage of your changes.

5. Click Yes, if you want to save the changes you did to the previously selected
text type.

Click No, if you want to discard the changes you did to the previously selected
text type.

RESULT: The Miscellaneous Text Editor dialog box displays the new text
type.

Replace text 1. Make step 1 of General Procedure.

2. Make step 2 of General Procedure.

3. Select text, you want to replace by clicking on the tiled bar on the left.

4. Click Default button.

5. Confirm by clicking OK.

NOTE: You cannot remove any of the default texts from the system. You can
only replace the default text with custom text. When you select a text
and click Default button, software replaces the custom text with the
original default text. This is indicated by a checked check box in the
Default column.

Copy texts from other controllers 1. Make step 1 of General Procedure.

2. Make step 2 of General Procedure.

3. If you want to copy texts from other controllers of the same project or from other
projects, check the other Sources check box.

RESULT: The dialog box is expanded and all controllers (projects) are
available in a tree on the right side.

483 EN2Z-0937GE51 R0518


EDITORS CARE

4. Open project with desired controller and click on the controller (source).

RESULT: The corresponding texts are displayed below.

5. In the list on the right, select the text you want to copy to the controller (target)
you currently work with by clicking on the tiled bar. Press SHIFT key, if you
want to select more than one text.

6. In the list on the left, click the line where the text should be copied to (target). If
you have selected more than one text for copying, you must select the same
number of lines in the left list.

NOTE: If the lines you selected on the left show already texts, these will be
overwritten by the ones from the source controller.

EN2Z-0937GE51 R0518 484


CARE EDITORS

7. Click on the button with the double arrow.

or,

click on the Copy all button, if you want to copy all texts from the source
controller to the current target controller.

RESULT: The texts are copied.

8. Click OK to confirm the copying.

For detailed descriptions of creating, editing, and deleting analog and digital
engineering units, descriptors, alarm texts, and characteristics, refer to the
respective following sections.

485 EN2Z-0937GE51 R0518


EDITORS CARE

Analog Engineering Units


Create Analog Engineering Units
Edit Analog Engineering Units
Copy Analog Engineering Units from Other Controllers
Replace Analog Engineering Units

Purpose Create, edit, copy, and/or replace analog units of measurement. Analog engineering
units specify an abbreviation for a unit of measurement (for example, degrees,
inches, centimeters) and the number of decimal places allowable for the
measurement.

For example, an analog input for a temperature sensor can be in Fahrenheit with an
accuracy of two decimal places.

This dialog box defines the text that displays for each engineering unit as well as its
decimal places. There are a maximum of 254 analog engineering units.

Procedure 1. In the logical plant tree, click on the controller. Click menu item Options, then
drop-down item Edit Text, and then Analog Eng. Units.

RESULT: The Miscellaneous Text Editor / Analog Engineering Units dialog


box is displayed. Default engineering units are displayed with a
check mark in the Default column, customized engineering units do
not. Engineering units, which are already used by at minimum one
point are displayed with a check mark in the Used column (only
display). Both, used and unused engineering units can be edited.

Create new analog engineering unit 2. Select an empty line and enter the text into the Unit field.

3. In the Dec.Places column, click into the field and select the format.

4. Confirm by clicking OK.

Edit analog engineering unit 1. Make step 1 of Procedure.

2. Locate engineering unit, you want to edit.

3. In the Unit column, click into the field and write over the existing text.

4. In the Dec.Places column, click into the field and select another format.
NOTE: If the unit is originally indicated as default text (checked check box in
the Default column), then any changes or deletion (blank field) in the

EN2Z-0937GE51 R0518 486


CARE EDITORS

Unit or Dec.Places field are indicated by an unchecked check box in


the Default column.

5. Confirm by clicking OK.

Copy analog engineering units 1. Make step 1 of Procedure.


from other controllers
2. If you want to copy analog engineering units from other controllers of the same
project or from other projects, check the other Sources check box. For detailed
instructions, please refer to “Copy texts from other controllers” in the “General
Procedure” section.

Replace analog engineering unit 1. Make step 1 of Procedure.

2. Select engineering unit, you want to replace by clicking on the tiled bar on the
left.

3. Click Default button.

4. Confirm by clicking OK.

NOTE: You cannot remove any of the default units from the system. You can
only replace the default unit with the custom unit. When you select an
engineering unit and click Default button, software replaces the
custom unit with the original default unit. This is indicated by a
checked check box in the Default column.

Digital Engineering Units


Create Digital Engineering Units
Edit Digital Engineering Units
Copy Digital Engineering Units from Other Controllers
Replace Digital Engineering Units

Purpose Create, edit, copy, and/or replace digital units. Digital engineering units identify the
switching status of a digital point. A digital point can either be active (“normal”) or
passive (“alarm”). Active state can be 0 or 1 depending on the Active State attribute
for the point.

For example, a digital output connected to a pump can indicate ON when active
(normal) and OFF when passive (alarm).

Points can have more than two states. For example, OFF/ON is two states. OFF,
ON, POS-1, POS-2, and POS-3 are five states.

This dialog box defines the text that displays for each state. There are 20 default
sets of texts (listed in Appendix).

Maximum Number of Engineering Units


The range of numbers varies depending on controller version. For Ver. 1.2
Controllers, the range is 1-20. For Ver. 1.3 and greater Controllers, the
maximum range is 1-127. The actual range depends on the total number of
states assigned to the units. If all units are two-state, then you can assign 127
digital engineering units. If some units are three-state, the number is reduced by
the number of extra states used. For example, if engineering units 1 and 2 are
three-state units, then the maximum number of units is reduced by two to 125.
Software keeps track of the total number of states (maximum 255) and displays
a warning message, if you try to assign an engineering unit after the total
number of states is reached. The range of numbers always shows 1-127 even
though you may have already used all 255 states. After the warning message is
displayed, you must delete a line with the DELETE key, not with the Default
button, which does not necessarily reduce the states.

Procedure 1. In the logical plant tree, click on the controller. Click menu item Options, then
drop-down item Edit Text, and then Digital Eng. Units.

487 EN2Z-0937GE51 R0518


EDITORS CARE

RESULT: The Miscellaneous Text Editor / Digital Engineering Units dialog


box is displayed. Default engineering units are displayed with a
check mark in the Default column, customized engineering units do
not. Engineering units, which are already used by at minimum one
point are displayed with a check mark in the Used column (only
display). Both, used and unused engineering units can be edited.

Create new digital engineering unit 2. Select an empty line.

3. In the Number column, select the number of states.

4. In the State column, select the first number, and enter the corresponding text in
the text field beside.

5. Assign text to all other states analogously as described in step 4.

6. Confirm by clicking OK.

Edit digital engineering unit 1. Make step 1 of Procedure.

2. Locate engineering unit, you want to edit.

3. You can edit a digital engineering unit in one of the following ways:

Change state by selecting another state in the State column.

and/or,

change text for a state by overwriting the existing text.

and/or,

change the number of states in the Number column. In the State column,
select the additional numbers one after the other and assign the texts in the
Text field beside. Select from the newly created states in the State column.

NOTE: If the unit is originally indicated as default text (checked check box in
the Default column), then any changes or deletion (blank field) in the
Number or Text field are indicated by an unchecked check box in the
Default column.

4. Confirm by clicking OK.

Copy digital engineering units 1. Make step 1 of Procedure.

EN2Z-0937GE51 R0518 488


CARE EDITORS

from other controllers


2. If you want to copy digital engineering units from other controllers of the same
project or from other projects, check the other Sources check box. For detailed
instructions, please refer to “Copy texts from other controllers” in the “General
Procedure” section.

Replace digital engineering unit 1. Make step 1 of Procedure.

2. Select engineering unit, you want to replace by clicking on the tiled bar on the
left.

3. Click Default button.

4. Confirm by clicking OK.

NOTE: You cannot reduce the number of default units in the system. There
are 20 sets of text for Ver. 1.2 Controllers; 255 sets (range 1-127) for
Ver. 1.3 and greater Controllers. You can only replace the default unit
with the custom unit and change the number of states a unit can have.
When you select a line and click Default button, software replaces the
custom unit with the original default unit. This is indicated by a
checked check box in the Default column.

Point Descriptors
Create Point descriptors
Edit Point descriptors
Copy Point descriptors from Other Controllers
Replace Point descriptors

Purpose Create, edit, copy, and/or replace point descriptors. Point descriptors are descriptive
information that you can add to user addresses. For example, you can assign
“CHILLER1” to a point to more fully specify point location.

Procedure 1. In the logical plant tree, click on the controller. Click menu item Options, then
drop-down item Edit Text, and then Point Descriptors.

RESULT: The Miscellaneous Text Editor / Point Descriptors dialog box is


displayed. Default point descriptors are displayed with a check
mark in the Default column, customized point descriptors do not.
Point descriptors, which are already used by at minimum one point
are displayed with a check mark in the Used column (only display).
Both, used and unused point descriptors can be edited.

489 EN2Z-0937GE51 R0518


EDITORS CARE

Create new point descriptor 2. Select an empty line and enter the text into the Descriptor field.

3. Confirm by clicking OK.

Edit point descriptor 1. Make step 1 of Procedure.

2. Locate point descriptor, you want to edit.

3. In the Descriptor column, click into the field and write over the existing text.

4. Confirm by clicking OK.

NOTE: If the descriptor is originally indicated as default text (checked check


box in the Default column), then any changes or deletion (blank field)
in the Descriptor field are indicated by an unchecked check box in the
Default column.

Copy point descriptors 1. Make step 1 of Procedure.


from other controllers
2. If you want to copy point descriptors from other controllers of the same project
or from other projects, check the other Sources check box. For detailed
instructions, please refer to “Copy text from other controllers” in the “General
Procedure” section.

Replace point descriptor 1. Make step 1 of Procedure.

2. Select point descriptor, you want to replace by clicking on the tiled bar on the
left.

3. Click Default button.

4. Confirm by clicking OK.

NOTE: You cannot remove any of the descriptors from the system. There are
always 64 descriptors with OS Version 1.2; with Version 1.3 and
higher, there are 255 descriptors. You can only replace the default
descriptor with the custom descriptor. When you select a descriptor
and click Default button, software replaces the custom descriptor with
the original default descriptor. This is indicated by a checked check
box in the Default column.

EN2Z-0937GE51 R0518 490


CARE EDITORS

Alarm Texts
Create Alarm Texts
Edit Alarm Texts
Copy Alarm Texts from Other Controllers
Replace Alarm Texts

Purpose Create, edit, copy, and/or replace alarm texts. Alarm texts are information for
operators to see when alarms occur. These alarms appear on the operator interface
connected to the controller (varies according to system). For example, you can
specify a phone number to call or a person to contact.

Procedure 1. In the logical plant tree, click on the controller. Click menu item Options, then
drop-down item Edit Text, and then Alarm Texts.

RESULT: The Miscellaneous Text Editor / Alarm Texts dialog box is


displayed. Default alarm texts are displayed with a check mark in
the Default column, customized alarm texts do not. Alarm texts,
which are already used by at minimum one point are displayed with
a check mark in the Used column (only display). Both, used and
unused alarm texts can be edited.

Create new alarm text 1. Make step 1 of Procedure.

2. Select an empty line and enter the text into the Alarm Text field.

3. Confirm by clicking OK.

Edit new alarm text 1. Make step 1 of Procedure.

2. Locate alarm text, you want to edit.

3. In the Alarm Text column, click into the field and write over the existing text.

NOTE: If the alarm text originally indicated as default text (checked check box
in the Default column), then any changes or deletion (blank field) in
the Alarm Text field are indicated by an unchecked check box in the
Default column.

4. Confirm by clicking OK.

Copy alarm texts 1. Make step 1 of Procedure.


from other controllers
2. If you want to copy alarm texts from other controllers of the same project or
from other projects, check the other Sources check box. For detailed

491 EN2Z-0937GE51 R0518


EDITORS CARE

instructions, please refer to “Copy text from other controllers” in the “General
Procedure” section.

Replace alarm text 1. Make step 1 of Procedure.

2. Select alarm text, you want to replace by clicking on the tiled bar on the left.

3. Click Default button.

4. Confirm by clicking OK.

NOTE: You cannot remove any of the alarm texts from the system. There are
always 128 possible messages in a Ver. 1.2 controller; Ver. 1.3 and
greater controllers have 255. You can only replace the default alarm
text with the custom alarm text. When you select an alarm text and
click Default, software replaces the custom alarm text with the original
default alarm text. This is indicated by a checked check box in the
Default column.

Characteristics
Create Characteristics
Edit Characteristics
Copy Characteristics from Other Controllers
Replace Characteristics

Purpose Create, edit, copy, and/or replace input/output characteristics. This dialog box allows
you to define conversion values for analog points to match the characteristics of
their sensors and assign the appropriate characteristics to analog points when
required.

. Procedure 1. In the logical plant tree, click on the controller. Click menu item Options, then
drop-down item Edit Text, and then Input/Output Characteristics.

RESULT: The Miscellaneous Text Editor / Input/Output Characteristics dialog


box is displayed.

In the list below, the default characteristics (max. of 10) are listed.
Each characteristic has an ID (1 through 10), the name, for
example, Sun sensor 0…5 V, and a maximum of four reference
points (V=values that determine the characteristic curve) .
Respective reference points are displayed after selecting the
characteristic in the list. A minimum of two reference points can

EN2Z-0937GE51 R0518 492


CARE EDITORS

define a linear characteristic. A maximum of four reference points


can define a nonlinear characteristic. Default characteristics are
displayed with a check mark in the Default column, customized
characteristics do not. Characteristics, which are already used by at
minimum one point are displayed with a check mark in the Used
column (only display). Both, used and unused characteristics can
be edited.

Create new characteristic 2. Select an empty line and enter the text into the I/O Characteristic field. Type a
name that is easy to recall, for example, Pressure 0-3” stands for differential
pressure, zero through three inches.

3. In the Reference Points fields, type desired values. Values represent reference
points that determine sensor value at various points in its range. Enter sets of
values from the smallest to the largest (or largest to smallest). You should enter
values in all four sets. If you have only two reference points, enter only two sets,
for example, for a linear characteristic of -40 to 100 °C and 0 through 10 V.
0 V - 40
10 V 100
4. Confirm by clicking OK.

Edit new characteristic 1. Make step 1 of Procedure.

2. Locate characteristic, you want to edit.

3. In the I/O Characteristic column, click into the field and write over the existing
text.

and/or,

in the Reference Points fields, change corresponding values.

NOTE: If the characteristic is originally indicated as default text (checked


check box in the Default column), then any changes or deletion (blank
field) in the Reference Points or I/O Characteristic field are indicated
by an unchecked check box in the Default column.

4. Confirm by clicking OK.

Copy characteristics 1. Make step 1 of Procedure.


from other controllers
2. If you want to copy characteristics from other controllers of the same project or
from other projects, check the other Sources check box. For detailed
instructions, please refer to “Copy text from other controllers” in the “General
Procedure” section.

Replace characteristic 1. Make step 1 of Procedure.

2. Select characteristic, you want to replace by clicking on the tiled bar on the left.

3. Click Default button.

4. Confirm by clicking OK.

NOTE: You cannot remove any of the characteristics from the system. There
are always 10 characteristics. You can only replace a default
characteristic with a custom characteristic. When you select a line and
click Default button, software replaces the custom characteristic with
the original default characteristic. This is indicated by a checked check
box in the Default column.

Default Characteristics Default characteristics are delivered with the software, but they can be edited with
the Default Text Editor to meet local requirements. The following shows examples:
1 Pressure 0-3 ” 0 to 11.0 V
3 Pressure ±0.25 ” 0 to 11.0 V
4 Pressure 0-5 ” 0 to 11.0 V
9 Direct Out 0-100 % 0 to 11.0 V
10 Reverse Out 0-100 % 11.0 to 0 V

493 EN2Z-0937GE51 R0518


EDITORS CARE

Note that the voltage ranges are wider than actual device input to account for
possible miscalibration of the device. Devices 1 through 4 and 9 range from 2 to
10 V. Device 10 ranges from 10 to 2 V.

Fixed Characteristics The following fixed characteristics cannot be edited in the Miscellaneous Text Editor.
They can only be selected and assigned to points in the Datapoint Editor, and are
available under the IDs 11 through 15 for slow subtype points, and under the IDs 11
through 29 for fast subtype points.

CARE Subtype Index XL-Online Index Characteristic


Slow Fast Name Specification
15 23 253 NTC Type F -58.0 to 302.0 F
Negative temperature coefficient
degrees F

11 11 255 NTC -50.0 to 150.0 C


Negative temperature coefficient
degrees C
12 12 254 LINEAR_GRAPH 0 to 10 V
13 19 249 PT1000 Type F/I -58.0 to 302.0 F
14 20 250 PT1000 Type C/I -50.0 to 150.0 C
17 247 PT1000 Type F/II 32 to 752.0 F
18 248 PT1000 Type C/II 0.0 to 400.0 C
21 251 PT100 Type F -58.0 to 302.0 F
22 252 PT100 Type C -50.0 to 150.0 C
15 245 PT3000 Type F -58.0 to 302.0 F
16 246 PT3000 Type C -50.0 to 150.0 C
13 243 BALCO Type F -58.0 to 302.0 F
14 244 BALCO Type C -50.0 to 150.0 C
24 241 0-10 V 0-10 V
25 242 2-10V = 0-100 % 2-10V = 0-100 %
26 237 NI 1000 TK5000 F -22.0 to 266.0 F
Positive temperature coefficient
degrees F
27 238 NI 1000 TK5000 -30.0 to 130.0 C
Positive temperature coefficient
degrees C
28 239 NTC-10 F -22.0 to 212.0 F
Negative temperature coefficient
degrees F
29 240 NTC-10 -30.0 to 130.0 C
Negative temperature coefficient
degrees C

Miscellaneous Text Editor (CARE-BACnet)


Purpose Provide functions to create, edit, copy, and delete state texts, descriptors, alarm
texts and color maps for datapoints. The following table shows the availability of
text types for the various datapoint types.

Analog Points Binary Points Multi-State Points


State Texts x x
Descriptors x x x
Alarm Texts x x x
Color Maps x x x

EN2Z-0937GE51 R0518 494


CARE EDITORS

The various text functions can be applied on database, project and plant levels.
The BACnet Miscellaneous Text Editor can be accessed in three ways:

• via menu Database, drop-down item Edit Texts ("Project" selected in tree)
• via menu Project, drop-down item Edit Texts (Project selected in tree)
• via menu Plant, drop-down item Edit Texts (Plant selected in tree)

For all levels the procedures are the same. Only invoking the Miscellaneous Text
Editor in the first step is different (see above).

Procedure 1. In the logical plant tree, select the level (folder) for which you want to define/edit
texts. E.g. select the project folder if you want to work with texts included in the
project.

2. In accordance with the selected level (database, project or plant), click on the
menu item Project, Database, or Plant, then submenu item Edit Texts, and
then the text type (State Texts, Descriptors, etc.).

RESULT: The Miscellaneous Text Editor dialog box is displayed. The dialog
box title is named according to the text type selected in the Edit
Texts menu.

495 EN2Z-0937GE51 R0518


EDITORS CARE

In the example above, ´State Texts` has been selected in the


Project/Edit Texts submenu. In the title line and the drop-down
listbox on the top the name of the selected text type is shown. If
desired, at this point another text type can still be selected from the
drop-down listbox.

NOTE: Engineering Units can be selected but cannot not be edited on any
level.

According to the selection in the CARE project tree, the


corresponding folder is highlighted below the text selection drop-
down listbox.

At this point you can still select other levels such as a plant or the
database by expanding the tree and clicking the corresponding
folder.

EN2Z-0937GE51 R0518 496


CARE EDITORS

Note that the database level is represented by the Global icon.

In the following, the handling of the different text types is shortly


described.

State Texts
If the type ´State Texts` is selected, all state text items are
summarized in a table in the area below the tree.

All text types, which are already used by at minimum one point are
displayed with a check mark in the Used column (only display).
Both, used and unused texts can be edited. Used text types cannot
be deleted.

In the area below the Summary table, the texts of the highlighted
item in the Summary table are displayed in a Details table. They
can be edited in this table.

497 EN2Z-0937GE51 R0518


EDITORS CARE

For state texts of binary and multi-state datapoints, the states count
(2 …32) can be defined in the States Count column of the upper
Summary table.

Descriptors
Point descriptors are displayed in a Summary table only and can be
edited directly in this table.

Alarm Texts
As state texts, alarm texts are shown in a Summary and Details
table. In the Event Object Type column of the Summary table, you
can select alarm texts for analog or digital datapoints. In the lower
Details table, you can enter/change the alarm texts for the different
events.

EN2Z-0937GE51 R0518 498


CARE EDITORS

Color Maps
Color maps provide the possibility to assign colors to different
states of a datapoint. When viewing the datapoint on a central, the
datapoint is visualized in colors depending on its current state. As
state texts, color maps are shown in a Summary and Details table.

499 EN2Z-0937GE51 R0518


EDITORS CARE

In the Name column of the upper Summary table, you can enter a
name for the color map. In the States Count column, you can
define the number of states of the datapoint to which the color map
will be mapped.

In the lower Details table, you enter min and max values for each
state and select a color to be assigned to each state.

Create New Text 3. To create a new text entry, click the New button. An empty row is inserted In
the Summary table.

4. In case of text type ´State Texts`, select the number of states from the States
Count drop-down listbox. In the Details table, assign the texts to the states by
entering the texts in the Text column (see figures in "State Texts" section
above).

5. In case of text type ´Descriptors`, enter the descriptive text in the Descriptor
column of the Summary table (see figure in "Descriptors" section above).

6. In case of text type ´Alarm Texts`, select the type, ´Analog` or `Digital`, from the
Event Object Type drop-down listbox. In the Details table below, enter the
alarm texts in the Alarm Text column (see figure in "Alarm Texts" section
above)

7. In case of text type ´Color Maps`, enter the name in the Name column of the
upper Summary table. In the States Count column, define the number of states
of the datapoint to which the color map will be mapped. In the lower Details
table, enter Min Value and Max Value for each state and map a color by
clicking the Select button in the Selection column (see figure in "Color Maps"
section above).

8. Click OK.

RESULT: The Miscellaneous Text Editor dialog box saves the settings
and is closed.

Edit Text 9. Apply the desired steps of the previous Procedure.

10. To edit text, locate the row, click into the field and write over the text.

EN2Z-0937GE51 R0518 500


CARE EDITORS

11. To display and edit different texts than currently displayed, click drop-down
arrow at the top and select the desired other text type.

RESULT: A message is displayed asking for the storage of your changes.

12. Click Yes, if you want to save the changes you did to the previously selected
text type.

Click No, if you want to discard the changes you did to the previously selected
text type.

RESULT: The Miscellaneous Text Editor dialog box displays the new text
type.

Copy Texts from Other Projects or


Plants 13. Open the source project from which you want to copy the texts.

14. Make the target project to which you want copy the texts the active project.

15. Apply the desired steps of the previous Procedure.

16. Check the Other Sources check box.

RESULT: The dialog box is expanded and all opened projects are available in
a tree on the right side.

501 EN2Z-0937GE51 R0518


EDITORS CARE

17. In the left tree, select the target, database (Global), project or plant to which you
want to copy the source texts.

RESULT: The available texts are displayed on the bottom.

18. Open the right tree and navigate to the source project or plant.

RESULT: The available texts are displayed on the bottom.

NOTE: When copying texts from a source, the target texts can be kept or
overwritten.

19. If the target texts should be kept, add the corresponding number of new rows by
clicking the New button repeatedly.

EN2Z-0937GE51 R0518 502


CARE EDITORS

20. On the right, highlight the source texts. Multi-selection by using the STRG or
SHIFT key simultaneously is possible.

503 EN2Z-0937GE51 R0518


EDITORS CARE

21. On the left, highlight the (empty) target rows to which the texts should be
copied. Multi-selection by using the STRG or SHIFT key simultaneously is
possible.

NOTE: If the selected rows on the left already show texts, these texts will be
overwritten by the source texts.

EN2Z-0937GE51 R0518 504


CARE EDITORS

22. Click the Copy button .

RESULT: The texts are copied. Selected empty rows on the left will
contain the new copied texts. Selected rows with existing texts
will be overridden with the copied texts.

23. Click OK to confirm the copying.

505 EN2Z-0937GE51 R0518


EDITORS CARE

Configure BACnet Point


Purpose Configuration of analog input and analog output points. Analog input and output
points must be configured prior to their assignment to a terminal on a hardware
module on the terminal assignment tab. By selecting a configuration such as NTC,
PT100 Type F, etc., the corresponding configuration properties of the datapoint are
automatically set correctly for the terminal.

IMPORTANT
Configure the datapoint before you assign the datapoint to a terminal on the
Terminal Assignment tab. Otherwise you need to rework the configuration
properties manually.

Procedure 1. Select the datapoint in the logical plant tree.

RESULT: On the Properties tab on the right, the properties are displayed.

EN2Z-0937GE51 R0518 506


CARE EDITORS

2. From the I/O Configuration drop-down listbox, select the configuration for the
datapoint. Default is 0-10V.

Create and Assign Characteristic to BACnet Point


Purpose When selecting an IO configuration, an appropriate characteristic is automatically
assigned if provided by CARE. But, for particular application scenarios, the usage
and creation of specific characteristics might become necessary.

Examples:

• customizing a default characteristic provided by CARE


• converting different engineering units used by a datapoint and its mapped NV
• building a value conversion table for a datapoint and its mapped Modbus point

These characteristics can be defined by the user to fulfill the requirements of the
particular application scenario.

Notes for Special Datapoints For the multi-state input and output points, please refer to the Multi-State
Input/Output Note and for the scaling factor of a pulse converter point, please refer
the Scaling Factor for Pulse converters Note at the end of the procedure.

Example A: An analog input datapoint is mapped to an NV and their


temperature engineering units (°C and °F) are different. The
Input NV has °C, the analog input datapoint should display the
values in °F. Hence, the engineering unit °C must be converted

507 EN2Z-0937GE51 R0518


EDITORS CARE

into the engineering unit °F. The conversion will be defined by


creating a new characteristic that contains a conversion table for
the engineering units.

Procedure see below (page 508)

Example B: A pressure sensor is connected to an analog input terminal that


is configured as 0-10 V w/o pull-up (IO configuration). The
corresponding analog input datapoint should convert the voltage
into a pressure with the range of 0 through 1000 Pa.

Procedure see page 511

Procedure Example A 1. Click the dotted button on the right of the Characteristic drop-down listbox.

RESULT: The Characteristics dialog box displays.

In the Name drop-down listbox, all default characterics provided


by CARE and user defined characteristics are selectable. Since
you want to create a new characteristic, continue with step 2.

EN2Z-0937GE51 R0518 508


CARE EDITORS

2. Click the New button.

RESULT: The New Characteristic dialog box displays.

3. In the Name field, enter a name for the new characteristic.

4. From the Direction drop-down listbox, select Input for inputs respectively input
NVs, or Output for outputs respectively output NVs.

5. In the Description field, enter an additional description if desired.

509 EN2Z-0937GE51 R0518


EDITORS CARE

6. From the NV Engineering Unit drop-down listbox, select the same engineering
unit (source) as assigned to the NV via the Input NV respectively Output NV
drop-down listbox under Lon Mapping on the Properties tab.

7. From the DP Engineering Unit drop-down listbox, select the engineering unit
to which the source engineering should be converted (target).

8. If values outside the minimum and maximum limits as displayed in the table
(see next step) should be considered, check the Exceed Min/Max Limit check
box.

9. In the Reference Points fields, enter the value pairs (left = NV value,
right=datapoint value).

NOTE: Negative values will be highlighted in red.

10. Click OK.

RESULT: The User Defined Characteristics dialog box redisplays.

EN2Z-0937GE51 R0518 510


CARE EDITORS

RESULT: The characteristic can now be selected from the Characteristic


drop-down listbox.

11. Assign the characteristic by selecting it.

RESULT: The destination engineering unit is displayed in the Engineering


Unit field.

Procedure Example B 1. From the IO Configuration drop-down list box, select ´AI 0..10V w/o pull-up`.

511 EN2Z-0937GE51 R0518


EDITORS CARE

2. Click the dotted button on the right of the Characteristic drop-down listbox.

RESULT: The User Defined Characteristics dialog box displays. In the


Name drop-down listbox, a default characteristic is selected
which converts % into V.

3. Click the New button.

RESULT: The New Characteristic dialog box displays.

EN2Z-0937GE51 R0518 512


CARE EDITORS

4. In the Name field, enter a name for the new characteristic.

5. In the Description field, enter an additional description if desired.

6. From the Source Engineering Unit drop-down listbox, select the same source
engineering unit as assigned by the default characteristic, in this case ´%` .

7. From the Destination Engineering Unit drop-down listbox, select the


engineering unit in which the source should be converted, in this case ´Pa`.

8. If values outside the minimum and maximum limits as displayed in the table
(see next step) should be considered, check the Exceed Min/Max Limit check
box.

9. In the Reference Points fields, enter the value pairs (left = source value,
right=destination value).

NOTE: Negative values will be highlighted in red.

513 EN2Z-0937GE51 R0518


EDITORS CARE

9. Click OK.

RESULT: The User Defined Characteristics dialog box redisplays.

10. Click OK.

RESULT: The characteristic can now be selected from the Characteristic


drop-down listbox.

EN2Z-0937GE51 R0518 514


CARE EDITORS

11. Assign the characteristic by selecting it.

RESULT: The destination engineering unit is displayed in the Engineering


Unit field.

Scaling Factor for Pulse For the definition of the scaling factor for a pulse converter point, the following must
Converter´s Note be considered:

• Since the SNVTs of a pulse converter point do not have an engineering unit, an
engineering unit has not to be selected here.
• The DP Engineering Unit must be the same as the one selected on Properties
tab of the point.
• The first reference point pair must be 0,0000 – 0,0000
• It is sufficient to enter one second reference point pair to define the scaling
factor.

515 EN2Z-0937GE51 R0518


EDITORS CARE

Multi-State Input/Output Note For Multi-State Inputs, the characteristic +1, for Multi-State Outputs, the
characteristic -1, is provided by CARE by default. These default characteristics must
be used if the multi-state points are considered to be mapped to NVs.

Default Text Editor


Purpose Customize project defaults for use in a specific area or region. After you create a
modified file, you can use it for any project created by that CARE PC.

Default files have a file extension of ID. Default files correspond to different versions
of controllers. For example, the default file for Excel 500 Controllers, OS Version
1.2, is called xl_1_2.id. For OS Version 1.3, the file is called xl_1_3.id.

Procedure 1. Click menu item Database, then submenu item Default Editor.

RESULT: The Default Text Editor window displays. Example:

OS version List of OS versions that you can choose (down arrow):

Controller OS
1.0 1.01 1.1 1.2 1.3/1.4 IRC-Map 1.5 2.0/2.1 2.03 2.04 2.06 3.00
XL50 x x x x
XL80 x x x x x
XL100 x x x x x x x x x
XL500 x x x x x x x x x
XL600 x x
XL800 x
XL Smart x x x x
ELINK x x

Default
files List of default files available for the selected OS Version. The
xl_1_2.id file is the standard default file for Excel 500 OS
version 1.2. You can change this list by selecting a different
OS version (previous field).

XFM

EN2Z-0937GE51 R0518 516


CARE EDITORS

location XFMs are installed in subdirectories under the CARE


directory. This field shows the location (subdirectory) where
the XFMs are located.

For example, the standard location is named ORIGINAL:

CARE
XFM
ORIGINAL
xf m.csd
xdm1.csd

You can create additional subdirectories under CARE\XFM if


a different subset of XFMs is required, but they must be
located in the CARE\XFM\ directory. Example with a new
subdirectory called CUSTOM:

CARE
XFM
ORIGINAL
xf m.csd
xdm1.csd
CUSTOM
cust_xf m.csd
cus_xf m1.csd

The CUSTOM subdirectory displays in the XFM location field.


You can have a custom set of XFMs for each default file, if
required.

Save Use the currently selected default file and open the Default
Text Editor main window after selecting Close. You can now
edit the selected file.

Copy Create a new default file by copying the selected default file.
You can then name and edit the new file to have different
defaults. The Copy Default Files window displays. Example:

Enter a name for the new file in the highlighted Target File
Name box. Click OK to save and then open the main Default
Text Editor window.

Delete Erase the currently selected default file.

Close Close this window.

Help Display the on-line help topic for this window.

Original... Information line about the currently selected default file.

2. Select a default file, click Save and Close. Or, Copy a default file.

517 EN2Z-0937GE51 R0518


EDITORS CARE

RESULT: The main CARE Default Editor window displays so you can edit the
selected/new file. File name displays in the title bar. Example:

File Two drop-down items display:

Select redisplays the first Default Text Editor window so you


can choose a different default file.

Exit closes the Default Text Editor and returns to CARE.

Edit The following dropdown items display so you can edit the
default text values for the selected file.

Engineering Unit (analog and digital)


I/O Characteristics
Point Descriptors
Alarm text
System Alarm
*XL10 Alarms

The edit windows that display are the same as the ones
described in the Editors chapter of this manual. See that
chapter for details.

*XL10 Alarms only applies when ELINK 1.01 was selected.


This item allows for changes to the standard alarm messages
that are part of the new VAV2 Controllers programmed by the
E-Vision tool. This item allows you to change the text in the
alarm messages to a different language, if required.

Help Two dropdown items display:

Help displays the on-line help topic for this window.

About displays the About dialog box that shows software


version number and available memory.

3. Select each Edit item and modify as desired. When through, click File, Exit to
close this window and return to CARE.

CARE User Address Search Templates Editor


NOTE: This function applies to CARE XL-5000 only, but cannot be used for the
ELink, OLink and XLink controllers in CARE XL-5000.

Purpose Define general search templates to enable operators using XI581/XI582 Bus-Wide
Operator Interface search templates to search for a set of user addresses. See
XI581AH/XI582AH Operator Terminals Operator Manual 74-3554 for details on
using search templates.

Procedure 1. In the logical plant tree, click on the controller.

2. Click menu Controller, then drop-down item Edit/Search Templates.

RESULT: The CARE User Address Search Templates Editor window


displays. Example:

EN2Z-0937GE51 R0518 518


CARE EDITORS

Initially, the List of Templates is blank. In this example, there are two entries, AH1_*
and AH2_*, to show what templates look like. The selected controller, CN1, has two
fan systems (plants), AH1 and AH2. User addresses have the plant name as a
prefix (AH1_, AH2_). All user addresses in the controller display in the Available
User Addresses column.
In this case, the AH2_* template tells the operator terminal to find all user addresses
that begin with ”AH2_”. The Matched User Addresses column shows what
addresses fit the template.

In general, to define templates:

a. Click a suitable address in the Available User Addresses column. The


address appears in the Template box below the column.
b. Edit the selected address so that it applies to a group of points. An
asterisk, *, is a wild card that represents any number of characters. You
can also use a question mark, ?, to represent just one character. For
example, the template AH?_C* selects all AH1 and AH2 command
addresses.
c. When the template is complete, click New. The new template appears in
the List of Templates column.
d. Highlight a template to display the user addresses that match it in the
Matched User Addresses column. If the matched addresses are not
what you want, click Modify to change the template until it produces the
correct list.
e. Save the template(s) by clicking the Save icon in the button bar (first
icon), or clicking File, Save.
f.
The following text describes the window in detail.
Menu Bar The menu bar provides the following additional functions.

File Display two drop-down menu items:

Save saves the newly defined templates.

Exit closes this windows and returns to CARE.

Edit Provide editing functions (Undo, Cut, Copy, and Paste) in the
Template box to aid in editing new template names. For
example, you can copy part of a template name and paste it
back in the template name if you need a name with duplicate
parts such as AH2_AH2_.

Tools Provide a Copy From Controller function to copy existing


templates from another controller to this one. This function is a
convenient shortcut.

519 EN2Z-0937GE51 R0518


EDITORS CARE

Help Display two drop-down menu items:


Contents displays the on-line help file for this window.

About displays the About box for this software. The About box
shows software version.

Button Bar The button bar provides clickable buttons for the menu bar and window functions in
the following order:

Save (templates)
Cut (text in Template box)
Copy (text in Template box)
Paste (text in Template box)
Undo (text changes in Template box)
Copy templates from another controller
Display About box
Exit window

Work Area The window’s work area contains the following information and fields.

Project and
Controller The names of the selected Project and Controller. The templates
you create are unique to these selections.

List of
Templates List of all templates for the selected controller.

Available User
Addresses All user addresses in the selected controller.

Matched User
Addresses List of user addresses in the controller that match the highlighted
template in the List of Templates.

Template Edit box for the entry of a new template name and editing.

Command Buttons Command buttons for the following functions:

New Add template from the Template box to the List of Templates.

Modify Copy selected template from the List of Templates to the


Template box to edit it.

Delete Erase the template selected in the List of Templates.

Exit Close the window and return to CARE.

Status Line The status line displays messages as you move the cursor over the window and as
software performs functions.

EN2Z-0937GE51 R0518 520


CARE TIME PROGRAM EDITOR

TIME PROGRAM EDITOR


NOTE: The Time Program Editor chapter applies to CARE XL-5000 only. For information
on time programming in CARE Excel Web, refer to the Schedules and Calendars
section.

Purpose Create time sequences for controller operation of devices. For example, set HVAC
start and stop times.

Time Programs implement these command schedules. A controller can have a


maximum of 20 Time Programs.

Each Time Program specifies a list of points to command and a Weekly Program.
This Weekly Program defines the normal daily activity of the system by specifying
which Daily Programs a controller should use for each day of the week (Sunday
through Saturday). The Weekly Program applies for each week of the year. There is
only one Weekly Program per Time Program.

Daily Programs list points and point actions and times for the controller to
implement.

Yearly Programs define time periods with special daily programs. Yearly programs
are suited to consider specific local conditions, for example, regional vacation and
public /religious festivals. Yearly programs can be defined for more than one year.

Required Steps Use the Editors (see Editors chapter) to establish required point types before
setting up Time Programs.

⇒ The Editors (Time Program Editor included) are only available after a plant
has been attached to a controller.

Example Controller 1
Time Program 1
Point Assignments
hvac_ctrl
min_hvac

Weekly Program Daily Program Name


Monday normal_daily
Tuesday normal_daily
Wednesday normal_daily
Thursday normal_daily
Friday normal_daily

Saturday Weekend
Sunday Weekend

Where the normal_daily Daily Program includes the following items


(time, user address, command):

06:00 hvac_ctrl on
18:00 hvac_ctrl off

And the Weekend Daily Program includes the following items (time, user
address, command):

12:01 min_hvac on
23:59 min_hvac off

You can also assign Time Programs 2 through 20 to the controller. For each Time
Program, you assign a set of points and a set of Daily Programs for its Weekly
Program.

Holidays Each Time Program can also specify a list of holidays and which Daily Program
each holiday should use.

521 EN2Z-0937GE51 R0518


TIME PROGRAM EDITOR CARE

If a holiday occurs that is not in the Time Program holiday list, the system uses the
normal Daily Program for the day of the week the holiday falls on.

Point Restriction Time programs cannot include analog input, digital input, or totalizer points.

Daily Programs Daily programs can only specify points assigned to the controller.

Flowchart The following flowchart summarizes the menu structure and procedure for the Time
Program function.

Initiate Time Program


Function

Time Program Editor


(1)

Click Edit

Time Program dialog


box

Select/Edit ONE Time


Program

Time Program Editor


(2)

Select menu item


(initially from left to right
when creating the first
time program)

User Address Daily Program Weekly Program Holiday Program Yearly Program

Select User Address Daily Program dialog Assign Daily program(s) Holiday Programs dialog Yearly Program dialog
dialog box box to Week Days dialog box box
box

Select user address(es) Add/Select daily Assign daily program to Assign daily program to Add (define) yearly
program weekday holiday program

Edit daily program Select Daily Program Select Daily Program Add / Edit Date Override
dialog box dialog box dialog box

Edit Daily Program


dialog box Select daily program Select daily program Enter period and assign
daily program

Add/Edit point(s).
Assign time and Assign yearly program
conditions/values to
point(s)
Select Daily Program
dialog box

Select daily program

EN2Z-0937GE51 R0518 522


CARE TIME PROGRAM EDITOR

Examples Time Program Editor functions:

Initiate Time Program Function


Purpose Begin Time Program functions such as adding, changing, and deleting Time
Programs, point assignments, and schedules.

Assumption The currently selected plant is attached to a controller and translated. You cannot
use the Time Programs function on a plant that is not already attached to a
controller and translated. After a plant is attached, the Schematic, Control Strategy,
and Switching Logic functions are not available.

Procedure 1. In the logical plant tree, select the controller:

2. Click menu item Controller, then submenu items Edit, Time Program Editor.

Or, click the Time Program Editor button in the button bar below the menu bar.

RESULT: The Time Program window displays with two menu items:

File
Display the following dropdown items:

Print to
File Output selected Time Program(s) to an ASCII
text file.

Print to

523 EN2Z-0937GE51 R0518


TIME PROGRAM EDITOR CARE

Printer Print selected Time Program(s).

Change
Printer Select a different printer.

Exit Close the Time Program function and return to


the CARE window.

Edit
Create, modify, and delete Time Programs. The Time
Program dialog box displays to select, create, rename, edit,
or delete a Time Program. The next section describes these
procedures.

Help
Display the following dropdown items:

About Display the About dialog box.

Help Display the help topic for Time Programs.

EN2Z-0937GE51 R0518 524


CARE TIME PROGRAM EDITOR

Select a Time Program

Create Time Programs

Rename Time Programs

Modify Time Programs

Delete Time Programs

Purpose Select, create, rename, modify, and/or delete Time Programs.

Subsections This section also contains the following procedures that are available after you
select a Time Program:

• Assign/Unassign User Addresses (User Address function)


• Define and/or Modify Daily Programs (Daily program function)
• Define and/or Modify Weekly Program (Weekly program function)
• Assign/Unassign Holidays (Holiday program function)
• Define and/or Modify Yearly Program (Weekly program function)
• Exit Time Program Editor (Return function)

Procedure 1. In the Time Program window, click menu item Edit. (See Initiate the Time
Program Function procedure to display the window, if not already done.)

RESULT: The Time Program dialog box displays with a list of existing Time
programs. If there are none, the list box is empty.

2. To create a new Time Program:

a. Click Add.
The Add Time Program dialog box displays.

525 EN2Z-0937GE51 R0518


TIME PROGRAM EDITOR CARE

b. Type a descriptive name for the new Time Program, for example,
weekend or weekday.

The ACTIVE holiday button enables the Holiday Program. To disable the Holiday
Program, click the INACTIVE holiday button. If holiday is inactive, this Time
Program uses the Daily Programs, as set up by the Weekly Program, on holidays.

Click OK to add the Time Program. (Or, click Cancel to close the dialog
box without saving the new Time Program name.)
If you click OK, the Time Program dialog box redisplays with the new
Time Program name highlighted.

c. Click Edit to begin the process of assigning schedules to the Time


Program.
The Time Program Editor window displays with the User Address, Daily
program, Weekly program, Holiday program, Yearly program, and
Return menu items. See the following sections for procedures.

To rename an existing Time Program:

a. Click Time Program name in the list box to select it. Then, click
Rename.
The Rename Time Program dialog box displays with the old name and
a box to enter a new name.

b. Type a new name. Click OK.


Or, click Cancel to close the dialog box without saving the new Time
Program name.
If you click OK, the Time Program dialog box redisplays with the new
Time Program name highlighted.

c. Click Edit to modify the Time Program, if desired.


The Time Program Editor window displays with the User Address, Day,
Week, Holiday, and Return menu items. See the following sections for
procedures.
Or, click Close to close this dialog box and return to the main Time
Program window.

To delete a Time Program:

a. Click a Time Program name in the list box to select it. Then, click
Delete.
A confirmation dialog box displays to check whether or not you really
want to erase the Time Program.

b. Click Yes to erase, No to cancel.


If you click Yes, the Time Program dialog box redisplays without the
deleted Time Program. If you click No, the Time Program dialog box
redisplays and still has the selected Time Program.

To modify a Time Program or assign schedules to a new Time Program:

EN2Z-0937GE51 R0518 526


CARE TIME PROGRAM EDITOR

Click Time Program name to select it. Then, click Edit. (Or, double-click Time
Program name.)

The Time Program Editor window displays with the User Address, Daily
program, Weekly program, Holiday program, Yearly Program and Return menu
items:

User
address Assign points to the selected Time Program.

Daily
program Create and/or modify Daily Programs that specify points,
times, and commands.
Weekly
program Assign Daily Programs to the Weekly Schedule for the
controller.
Holiday
program Assign Daily Programs to system holidays. Holidays are
preset. You cannot change them with CARE.
Yearly
program Define time periods with special daily programs for local
and national needs (vacation, festivals).

Return Exit the Edit function.

The following sections describe these functions.

3. To close this dialog box and return to the main Time Program window, click
Close.

User Address Function


Assign/Unassign User Addresses

Purpose Assign and unassign points to and from a time Program. Each time program must
have a list of assigned points before you can set up Daily Programs....

Procedure 1. Select desired Time Program (see Select a Time Program section for
procedure).

RESULT: The Time Program Editor window displays with the User Address
menu item.

2. Click User Address.

RESULT: The Select User Address dialog box displays with a list of existing
user addresses. The user addresses were previously specified
using the data point editor (see the Editors chapter for procedure).

User Addresses marked with a pound sign, are already assigned to


the selected Time Program.

527 EN2Z-0937GE51 R0518


TIME PROGRAM EDITOR CARE

You can assign each user address to only one Time Program. Click
Reference to display user addresses that are already assigned
(User Address Reference List dialog box)

Click Cancel to close the dialog box when through checking the
point assignments..

3. To assign an unassigned address (no pound sign, #), click user address name.
Then click (De)Select The (De)Select button acts as a Select when you click
unassigned addresses.

Tip ⇒ Double-clicking an address selects and deselects it.

RESULT: Software assigns the user address to the Time Program and adds
a pound sign, #, next to the selected user address to mark it as
assigned.

4. To unassign assigned user addresses, click user address name and then click
(De)Select. The (De)Select button acts as a Deselect when you click assigned
addresses.

Tip ⇒ Double-clicking an address selects and deselects it.

EN2Z-0937GE51 R0518 528


CARE TIME PROGRAM EDITOR

RESULT: Software unassigns the user address from the Time Program and
removes the pound sign, #, next to it. Software does not delete the
user address from the point description file.

5. Click Close to end the function.

RESULT: Software closes the dialog box. The Time Program Editor window
redisplays. You can now select the Daily program function to define
Daily Programs.

Daily Program Function


Create Daily Program

Rename Daily Programs

Delete Daily Programs

Copy Daily Programs

Modify Daily Programs

Purpose Define, rename, delete, copy, and/or modify Daily Programs and assign point
commands and command times to each Daily Program. Each Daily Program covers
a 24-hour period.

Daily Programs specify switching times, setpoints, and switching status for selected
points.

Procedure 1. Select desired Time Program (see Select a Time Program section for
procedure).

RESULT: The Time Program Editor window displays with the Day menu item.

2. Click Daily program.

RESULT: The Daily Program dialog box displays.

3. To create a new Daily Program:

a. Click Add.
The Add Time Program dialog box displays.

b. Type a descriptive name for the new program, for example, Saturday or
Sunday. Then, click OK.
The dialog box closes and the Daily Program dialog box redisplays with
the new name highlighted.

529 EN2Z-0937GE51 R0518


TIME PROGRAM EDITOR CARE

c. To begin defining times, setpoints, and statuses for the new Daily
Program, go to Step d and just click Edit (the Daily Program is already
selected).

To rename a Daily Program:

a. Click its name to select it. Then, click Rename.


The Rename dialog box displays.

b. Type a new name. Name can be a maximum of 18 characters and must


be unique to the selected Time Program.

c. Click OK to save the new name.


The dialog box closes and the Daily Program dialog box redisplays with
the new name highlighted.

d. To modify times, setpoints, and statuses for the Daily Program, go to


Step d and just click Edit (the Daily Program is already selected).

Or, Click Close to close this dialog box and return to the Time Program main
window.

To delete a Daily Program:

a. Click its name, then click Delete.


Software asks whether or not you really want to delete the entry. Click
Yes to delete; No to cancel. The name disappears from the list box.
When software deletes a program, it deletes all its data.

b. Click Close to close this dialog box and return to the Time Programs
main window. Or, continue with other Time Program modifications.

4. To select and modify a Daily Program:

Click its name and then click Edit. (Or, double-click name.)

Tip ⇒ To select a name, type the first letter of the name, then the second
letter, and so on, until software highlights the desired name.

The Edit Daily Program dialog box displays with the current list of times, points,
and commands assigned to the selected Daily Program.

If there are no time, points, and commands assigned to the Daily Program, the
Copy Daily Program dialog box displays (unless there are no other Daily
Programs):

5. If the Copy Daily Program dialog box displays, select one of the following
actions:

a. Click Insert New, then OK to close the dialog box and return to the Edit
Daily Program dialog box to assign all new items.

b. Click Make Copy From, then click the down arrow in the box to the
right to display a list of Daily Programs.

EN2Z-0937GE51 R0518 530


CARE TIME PROGRAM EDITOR

c. Click desired program name. Click scroll bars and/or arrows to display
other Daily Program names if the name you want is not in the list box.
Click OK. (Or, click Cancel to close the dialog box without selecting a
program.)

The dialog box closes and the Edit Daily Program dialog box redisplays
with the copied entries from the selected Daily Program. You can
change the entries as desired.

d. Click Cancel to just close the dialog box and return to the Edit Daily
Program dialog box.

RESULT: The Edit Daily Program dialog box displays. If you copied a Daily
Program, its commands display in the list box. Each line in the list
box represents one command. Each command specifies time, user
address, and value or status command.

6. Delete existing entries by clicking the line you want to delete and then clicking
Delete.

All command data in the Daily Program for the point is gone. The dialog box
remains so you can continue adding, changing, and deleting other entries.

Create new entries by clicking Add.

RESULT: The Add point to daily program dialog box displays.

531 EN2Z-0937GE51 R0518


TIME PROGRAM EDITOR CARE

e. Select user address in the User Address dropdown list box and enter
value in the Value field.

f. Enter time in the Time field and select appropriate radio button AM or
PM.

g. For switching points select optimization or not by clicking the


corresponding item in the dropdown list box Optimized.

Change existing entries by clicking Edit.

RESULT: The Edit point in daily program dialog box displays.

7. Type a time value, for example, 06:30. Time format can be in 12- or 24-hour
format (Windows Control Panel setting). Hours and minutes must be two
digits, not one. For example, 06, not 6. Time can only include hours and
minutes (no seconds).

Press Tab to go to the User Address box. Click the down arrow to display the
list of user addresses assign to this Time Program (see User Address
function). Click desired address to select it.

Press Tab to go to the Value box. Type a status if the point is digital (for
example, ON or OFF). Type a value if the point is analog (for example, 3).

The Low limit and High limit values display only for analog points. The
characteristic for the point determines limits. If there is no characteristic, there
are no limits.

8. Click OK to save your entries.


Or, Cancel to close the dialog box without saving.

RESULT: Software saves the entry. See Engineering Unit note.

The Edit Daily Program dialog box redisplays for entry and/or
modification of other points and commands.

9. Click OK to save the new Daily Program with the currently displayed entries
and close the dialog box.
Or, click Cancel to close the dialog box without saving the changes.

RESULT: The Daily Program dialog box redisplays.

Engineering Unit Default If no engineering unit is assigned to the point, software assigns spaces and three
decimal places to analog points and the strings “State text 0”, “State text 1”, etc, to
digital points.

EN2Z-0937GE51 R0518 532


CARE TIME PROGRAM EDITOR

Weekly Program Function


Define Weekly Program

Modify Weekly Program

Purpose Assign and unassign Daily Programs to days of the week.

Every Time Program has one Weekly Program that specifies a Daily Program for
each day of the week.

Software uses the Weekly Program to generate the annual program. The Annual
Program is a repeat of the Weekly Programs for each week of the year.

Default Daily Program If you do not assign a Daily Program to a weekday, the Time Program uses the
Daily Program for the previous weekday. The default assignments display after you
exit the Weekly program function and then reselect it.

Procedure 1. Select desired Time Program (see Select a Time Program section for
procedure).

RESULT: The secondary Time Programs window displays with the Weekly
program menu item.

2. Click Weekly program.

RESULT: The Assign daily program(s) to weekdays dialog box displays. The
existing daily programs assigned to the weekdays for the selected
Time Program display in the list box. For a new Weekly Program,
there are no daily program assignments.

3. To assign a Daily Program to a weekday , click Daily Program name, then click
Assign. (Or, double-click Daily Program name.)

RESULT: The Select Daily Program dialog box displays. The existing daily
programs for the Time Program display in the list box.

533 EN2Z-0937GE51 R0518


TIME PROGRAM EDITOR CARE

Click desired program name, then click OK to complete the selection. Click
scroll bars and/or arrows to display other Daily Program names if the name you
want is not in the list box. (Or, click Cancel to close the dialog box without
selecting a program.)

RESULT: The dialog box closes and the Assign daily program(s) to
weekdays dialog box redisplays. The new Daily Program
assignment is in the list box.

4. To delete an assignment, click Weekday item in the list box. Then click Delete.

RESULT: Software unassigns the Daily Program. After you finish assigning
Daily Programs and close the dialog box, software replaces all
default assignments with the Daily Program for the previous day.

5. To make changes to a Daily Program without exiting this function and going to
the Day function, click the desired Daily Program name in the list box and then
click Edit.

RESULT: The Edit daily program dialog box displays. Modify Daily Program
as desired. See Daily Program Function section for procedure.
When you exit, the Assign daily program(s) to weekdays dialog box
redisplays.

6. When through assigning Daily Programs, click OK.

RESULT: The dialog box closes and software assigns the last-assigned Daily
Program to the weekdays that were not specified. For example:

Monday Weekday
Tuesday Holiday
Wednesday
Thursday
Friday
Saturday
Sunday

Software assigns “Holiday” to Wednesday through Sunday


because Holiday was the last Daily Program assigned.

The Time Program window redisplays. To see what all the weekday
assignments are, reselect the Weekly program function.

EN2Z-0937GE51 R0518 534


CARE TIME PROGRAM EDITOR

Holiday Program Function


Define Holiday Program

Modify Holiday Program

Inactivate Holiday Program

Purpose Assign and unassign Daily Programs to holidays such as Christmas and Easter.
Since holidays usually do not require occupancy-type schedules, software uses
Holiday Program assignments for holidays instead of the Weekly Program
schedules. The daily program will then apply on a holiday every year.

NOTE: “Spare day” holidays are NOT available for programming specific
holidays.

Default Daily Program If you do not assign a Daily Program to a holiday, the Weekly Program uses the
Daily Program for that weekday.

Procedure 1. Select desired Time Program (see Select a Time Program section for
procedure).

RESULT: The secondary Time Programs window displays with the Week
menu item.

2. Click Holiday program.

RESULT: The Holiday Programs dialog box displays. The existing daily
programs assigned to the holidays for the selected Time Program
display in the list box. If you do not assign a Daily Program to a
holiday, the Weekly Program uses the Daily Program for that
weekday. ).

3. To assign a Daily Program to a holiday , click Daily Program name, then click
Assign. (Or, double-click Daily Program name.)

RESULT: The Select Daily Program dialog box displays. The existing daily
programs for the Time Program display in the list box.

535 EN2Z-0937GE51 R0518


TIME PROGRAM EDITOR CARE

Click desired program name, then click OK to complete the selection. Click
scroll bars and/or arrows to display other Daily Program names if the name you
want is not in the list box. (Or, click Cancel to close the dialog box without
selecting a program.)

RESULT: The dialog box closes and the Holiday Programs dialog box
redisplays. The new Daily Program assignment is in the list box.

4. To delete an assignment, click Holiday item in the list box. Then click Delete.

RESULT: Software unassigns the Daily Program.

5. To make the Holiday Program inactive for this Time Program, click Status.

RESULT: The Holiday Program Status dialog box displays.

The Active button enables the Holiday Program.

The Inactive button disables the Holiday Program so that this Time Program
uses the Daily Programs as set up by the Weekly Program.

Click desired status button.


Then, click OK to save change and exit.
Or, click Cancel to exit without saving change.

6. To make changes to a Daily Program without exiting this function and going to
the Daily program function, click the desired Daily Program name in the list box
and then click Edit. (Or, double-click Daily Program name.)

RESULT: The Edit Daily Program dialog box displays. Modify Daily Program
as desired. See Daily Program Function section for procedure.
When you exit, the Holiday Programs dialog box redisplays.

7. When through assigning Daily Programs, click Close.

RESULT: The dialog box closes and the Time Program window redisplays.

EN2Z-0937GE51 R0518 536


CARE TIME PROGRAM EDITOR

Yearly Program Function


Define Yearly Program

Modify Yearly Program

Delete Yearly Program

Import File

Purpose Define time periods with special daily programs. Yearly programs are suited to
consider specific local conditions, for example, regional vacation and public
/religious festivals. Yearly programs can be defined for more than one year. It is
therefore not necessary to define a yearly program every new year as you have to
do with the holiday program function. Yearly programs have higher priority than the
weekly program, which is used to generate the annual program.

Procedure 1. Select desired Time Program (see Select a Time Program section for
procedure).

RESULT: The secondary Time Programs window displays with the Yearly
Program menu item.

2. Click Yearly program.

RESULT: The Yearly Program dialog box displays. The existing yearly
programs with their assigned daily program are summarized.

3. To define a new Yearly Program and assign a daily program to it, click Add.

RESULT: The Add/Edit Date Override dialog box displays.

537 EN2Z-0937GE51 R0518


TIME PROGRAM EDITOR CARE

Enter the time range into the Period From and To fields. Select the desired
daily program from the Daily program dropdown list box, then click OK.

RESULT: The dialog box closes and the Yearly Program dialog box
redisplays. The new Yearly Program is in the list box.

3. To assign another Daily Program to an existing Yearly program , click Yearly


Program name, then click Assign.

RESULT: The Select Daily Program dialog box displays. The existing daily
programs for the Time Program display in the list box.

EN2Z-0937GE51 R0518 538


CARE TIME PROGRAM EDITOR

4. Click desired daily program and click OK.

RESULT: Software assigns the selected Daily Program to the Yearly


Program.

5. To delete an Yearly Program, click program item in the list box. Then click
Delete.

RESULT: Software deletes the Yearly Program.

6. To make changes to a Yearly Program without exiting this function, click the
desired Yearly Program in the list box and then click Edit.

RESULT: The Add / Edit Date Override dialog box displays. Modify the Yearly
Program as desired.

Click OK to return to the Yearly Program dialog box.

7. To use yearly programs through a range of several years, click the Import file…
button and open the predefined text file, for example, yrly_prgr.txt.

539 EN2Z-0937GE51 R0518


TIME PROGRAM EDITOR CARE

To define a text file for import see Imported File example at the end of this
section.

After opening the *.txt file you will get the following message, if you have
already defined yearly programs:

Click OK.

RESULT: If a daily program defined for a yearly program in the *.txt file does
not still exist in the time program, the following message dialog box
displays.

Clicking the Add… button opens the Daily Program dialog box to add the
missing daily program to the time program. After adding the daily program you
can assign this or a different, existing daily program to the yearly program
defined in the txt.file.

Clicking the Assign… button opens the Select Daily Program dialog box to
assign a daily program to the yearly program that corresponds to the daily
program displayed in the message dialog box. Only daily programs other than
the one displayed can be assigned to the corresponding yearly program
because the daily program displayed is not yet added. Use Add… button to add
the appropriate daily program.

Clicking the Assign to all… button opens the Select Daily Program dialog box
to assign one daily program to all yearly programs defined in the *.txt file.

EN2Z-0937GE51 R0518 540


CARE TIME PROGRAM EDITOR

NOTE: The daily program is only assigned to yearly programs, which do not
yet have daily programs, assigned to them.

Clicking the Skip entry button ignores the entry indicated with the daily program
in the message dialog box and continues with the next entry.

Clicking the Cancel button returns to the Yearly Program dialog box. All the
yearly programs will be inserted into the list to which daily programs were
assigned (as defined in the txt.file or different ones).

8. When through defining Yearly Programs, click OK.

Imported File example To define repeatedly yearly programs that may last over a period of several years,
you create a txt.file with a text editor like Notepad. See the following description
included in the text file example for creating yearly program entries.

;***********************************************************************************************
*****

; YRLY_PRG.txt Example Definition File for Yearly Time Program

;***********************************************************************************************
*****

; This txt file is an example import file for the yearly time program.
; Each date override entry with its fields from, to and daily program have to list in
one line.
; The fields are separated with spaces or tabs. The order is from, to, daily_program
name.
; Syntax: From_Date To_Date [Daily_Prog_Name]
; The daily program name is optional. If the daily program name is omitted or
; if the given name does not yet exist upon definition file import, the time program
editor
; asks for resolution of the conflict.
; The date format is dd/mm/[yyyy]
; If the year is omitted, the date override is repeated for the next 5 years.
; The timeframe for repetition of date overrides can be adjusted by changing the
"RepeatCounter" setting.
; A comment-line starts with ';'.

; Examples:

RepeatCounter=5
;The above line specifies that a date override is repeated for the next 5 years,
;in case the year is omitted in the data specification

19.5.1997 19.5.1997 offday


; the above line shows how to insert a date override on May/19th/1997 with daily
program offday

1.5 1.5 may1


; a date override on May, 1st. for the next five years with daily program may1

2.5.1997 6.5.1997 holiday


; date override from May/2nd/1997 to May/6th/1997 with daily program holiday

7.2 11.2
; date override from Feb/7th to Feb/11th for the next five years,
; Import will ask for user interaction to assign/create daily program

541 EN2Z-0937GE51 R0518


TIME PROGRAM EDITOR CARE

Return Function
Exit Edit

Purpose Save Time Program changes and exit the Time Program function.

Procedure 1. Click menu item Return.

RESULT: The Time Program editor window displays.

2. Click File, dropdown item Exit to close the Time Program Editor and return to
the main CARE window.

Or, click File and one of the Print dropdown items to print selected Time
Program(s). See the next section for procedures.

Print Time Programs


To print time programs see Print Documentation chapter.

EN2Z-0937GE51 R0518 542


CARE TERMINAL ASSIGNMENT FUNCTION

TERMINAL ASSIGNMENT
The Terminal Assignment Function (TAF) is a graphical tool that can be used to
display and modify existing controller target I/O hardware configurations.

The Terminal Assignment Function supports Excel 50, 80, 100, 500, 600, 800,
Excel Smart, and Excel Web as well as Honeywell and 3rd party LON devices and
allows:

• Adding controller housings


• Inserting modules into housings
• Adding and connecting LON devices
• Copying LON devices
• Changing the position and the types of Excel 800/500/600 modules (for
example, DO with switches by DO without switches)
• Setting/Changing neuron IDs of distributed I/O modules
• Assigning points to modules or shifting points between modules
• Mapping datapoints/NVs to NVs

Module types in Excel 50, 80, and Excel 100 controllers are fixed and, therefore, not
changeable.

Invoke TAF
Procedure 1. In the logical plant tree, click on the controller

2. On the right pane, click on the Terminal Assignment tab.

RESULT: The current terminal Assignment of the selected controller is


displayed.

543 EN2Z-0937GE51 R0518


TERMINAL ASSIGNMENT FUNCTION CARE

Using the Context Menu


The important functions you need for working within the TAF are quickly available
via context menu, which is displayed by clicking the right mouse key at the
appropriate position on the terminal assignment tab.

Working With Housings


A controller contains at least one housing, a basic housing with a power supply
(PS), a central processing unit (CPU), and at least one module.

In order to take in further modules, the following housing types can be added to the
existing basic housing:

• Standard housings for max. 4 IP modules (XF521 etc)


• LON housings for max. 10 DIO modules (XFL521 etc)
• XF528 housings for max. 5 high-density I/O modules (XF528)

A maximum of 16 modules (IP, DIO, and/or high density modules) can be inserted
into the appropriate housings in total.

Housings can be removed as well. Before removing the housing, the existing
modules of the housing to be removed have to be moved to another housing,
otherwise the assigned points will automatically get boardless.

NOTE: The basic housing can never be removed.

EN2Z-0937GE51 R0518 544


CARE TERMINAL ASSIGNMENT FUNCTION

Add Housing
Purpose Add housing. Each housing to be added is an empty housing, except the XF528
housing, and can take in the maximum module number of the corresponding
module types.

Procedure 1. Click right mouse key on the terminal assignment tab, then click desired Add
command in the context menu, or

click Add Housing button on the button bar, then click desired Add command
in the context menu.

RESULTS:

Add Housing adds a standard housing with 4 empty slots to insert up to 4 IP


modules.

Add a XF528 Module adds a XF528 housing with one XF528 high-density
module already inserted and 4 empty slots. Up to 4 further XF528 modules can
be inserted.

IMPORTANT
An empty slot in a XF528 housing means that the corresponding DIP-
switches of this module have to be switched off.

Add LON Housing adds a LON housing with 10 empty slots to insert up to 10
DIO modules.

Remove Housing
Purpose Remove housing. Both, empty as well as filled housings can be removed. When
removing a filled housing, all points will get boardless.

NOTE: When exiting TAF, all empty housings will be removed automatically.

Procedure 1. If you want to empty the housing before removing it, move any inserted
modules to another housing.

2. Position the cursor on the housing you want to remove, click right mouse key,
then click Remove Housing, or

Click Remove Housing button on the button bar, then click the housing you
want to remove. The housings are displayed with their names and numbers.

RESULT: TAF removes the housing.

For moving or removing modules, refer to Working With Modules section.

Working With Modules


Modules can be inserted in housings, moved in or between housings, or removed
from housings. TAF supports standard modules like XF521, XF522, LON modules
like XFL521, XF522, and the special XF528 module.

Insert Standard Module


Purpose Insert standard module. Standard modules are modules of the type XF521, XF522
etc. Standard modules can be inserted into empty slots of a standard and the basic
housing.

Procedure 1. Click right mouse key in appropriate housing slot, then click Insert Module
(highlighted).

545 EN2Z-0937GE51 R0518


TERMINAL ASSIGNMENT FUNCTION CARE

NOTE: The basic housing provides only two slots in which default modules
can be inserted, because it always contains a power supply and a
central processing unit.

RESULT: TAF displays a module type dialog box to select a valid module
type for the currently selected slot. When inserting modules into
basic housings, the dialog box displays different module types than
when inserting modules into an empty standard housing.

Module type dialog box for basic housings:

Module type dialog box for standard housings:

2. Select appropriate module type and click OK.

RESULT: TAF inserts the selected module into the housing and assigns a
module number to the inserted module automatically.

For changing module number, refer to Modify Module Number section.

For changing module type, refer to Modify Module Type section.

For assigning points to the inserted module, refer to Working with Points section.

Insert LON Module


Purpose Insert LON module into empty slots of a LON housing. LON modules are modules
of the type XFL521, XFL522 etc.

Procedure 1. Click right mouse key in appropriate housing slot, then click Insert Module
(highlighted).

RESULT: TAF displays a module type dialog box to select a valid module
type for the currently selected slot.

EN2Z-0937GE51 R0518 546


CARE TERMINAL ASSIGNMENT FUNCTION

2. Select appropriate module type and click OK.

RESULT: TAF inserts the selected module into the housing and assigns a
module number to the inserted module automatically.

For changing module number, refer to Modify Module Number section.

For changing module type, refer to Modify Module Type section.

For assigning points to the inserted module, refer to Assign Point section.

Insert XF528 Module


Purpose Insert XF528 module. The XF528 module is a special module providing five
modules of the type XF523 each in a single slot in the XF528 housing.

Procedure 1. Click right mouse key in appropriate housing slot, then click Insert Module
(highlighted).

RESULT: TAF inserts a XF528 (XF523) module into the housing and assigns
a module number to the inserted module automatically.

For changing module number, refer to Modify Module Number section.

For changing module type, refer to Modify Module Type section.

For assigning points to the inserted module, refer to Assign Point section.

Modify Module Type


Purpose Modify module type. Standard and LON modules can be changed to modules of the
same or different family.

To change a module type to a module of the same family, in other words, Standard
to Standard or LON to LON, the modules have to be free from points, except the
XF521 module, which can be changed directly to the XF526 module even if there
are points assigned to it.

To change a module type to a module of a different family, in other words, Standard


to LON or vice versa, the modules do not have to be free from points.

Module type XF521 with assigned points can only be changed to module type
XF526.

Module type XF529 can be changed to module type XF524 if no pulsed point is
assigned to it.

For further information, refer to Combine Point and Module section.

547 EN2Z-0937GE51 R0518


TERMINAL ASSIGNMENT FUNCTION CARE

Set/Modify Neuron ID for DIO Module


In a shared system architecture every distributed I/O module must have its unique
twelve-digit neuron ID. The neuron ID is displayed at the bottom of the module. By
default the neuron ID is set to 0, in other words, to a 12-digit number of 0. The
neuron ID can be changed and will be kept even when changing the target I/O
hardware from DIO to Standard I/O.

Procedure 1. Point on LON module, then click right mouse key.

2. Click Modify Neuron ID.

RESULT: TAF displays the Modify Neuron ID dialog box.

3. In the New ID field, enter the desired neuron ID for the module, then click OK.

NOTE: The neuron ID must have twelve digits.

RESULT: TAF displays the modified Neuron ID at the bottom of the module.

Modify Module Type to Same Family of Module

Purpose Modify standard module type to any other standard module type, e.g. XF522 to
XF527 and modify LON module type to any other LON module type, e.g. XFL522 to
XFL524.

Procedure 1. Free module from points (see Move Point section; not necessary for XF521
and XF529 modules).

2. Click right mouse key on the module to be modified, then click Modify Module
Type (highlighted).

RESULT: TAF displays a module type dialog box showing all module types to
which the selected module can be changed.

Module type dialog box for basic housings:

Module type dialog box for standard housings:

EN2Z-0937GE51 R0518 548


CARE TERMINAL ASSIGNMENT FUNCTION

Module Type dialog box for LON housings:

3. Select the appropriate module type and click OK.

RESULT: TAF replaces the module type with the selected new module type.

After changing the module type, points have to be assigned to the module (refer to
Assign Point section).

Modify Module Type to Different Family of Module

Purpose Modify standard module type to equivalent LON module type, e.g. XF522 to XFL522
or vice versa, by moving the module into a different housing type (standard housing
and LON housing respectively).

The following list shows the movement possibilities:

Standard XF528 LON

XF523 ↔ XF528 ↔ XFL523

XF521 ↔ ↔ ↔ XFL521
XF522 ↔ ↔ ↔ XFL522
XF523 ↔ ↔ ↔ XFL523
XF524 ↔ ↔ ↔ XFL524

XF526 → → → XFL521
XF527 → → → XFL522
XF529 → → → XFL524

Procedure 1. Click left mouse key on the module (e.g. standard) to be modified, drag it to an
empty slot of the different housing type (LON), and then drop it.

549 EN2Z-0937GE51 R0518


TERMINAL ASSIGNMENT FUNCTION CARE

RESULT: TAF changes the module type and all points remain on their
original terminations as far as possible. If modifying a module
results in any invalid point assignments, the corresponding points
will automatically get boardless as indicated in the logical plant
tree.

Modify Module Number


Purpose Modify module number.

Procedure 1. Click right mouse key on the module for which the module number has to be
modified, then click Modify Module Type (highlighted).

RESULT: TAF displays the module number dialog box to select the new
module number.

2. Select appropriate module number and click OK.

RESULT: TAF modifies the module number of the selected module. If the
module number already exists, TAF opens the Swap Numbers ?
dialog box.

3. Select YES if numbers should be swapped, or select NO and choose another


number not used before.

NOTE: TAF explains where the selected module number has been defined
before to allow swapping of the numbers.

RESULT: TAF swaps the module numbers of the appropriate modules.

Move Module
Purpose Move a module from one slot of a housing to any other empty slot of the same or
another housing by Drag&Drop.

You can move standard modules from their housings to LON housings or XF528
module housings, and vice versa.

The following list shows the movement possibilities:

EN2Z-0937GE51 R0518 550


CARE TERMINAL ASSIGNMENT FUNCTION

Standard XF528 LON

XF523 ↔ XF528 ↔ XFL523

XF521 ↔ ↔ ↔ XFL521
XF522 ↔ ↔ ↔ XFL522
XF523 ↔ ↔ ↔ XFL523
XF524 ↔ ↔ ↔ XFL524

XF526 → → → XFL521
XF527 → → → XFL522
XF529 → → → XFL524

Moving modules between LON and standard housings results in the following:

TAF changes the module type and all points remain on their original terminations as
far as possible. In case module modifying results in any invalid point assignment,
the corresponding points will automatically get boardless as indicated in the logical
plant tree.

Procedure 1. Drag module by clicking and holding the left mouse key on the appropriate
module. Drag the module to the target slot, then drop it by releasing the mouse
key.

NOTE: A module cannot be inserted into an occupied slot or outside a


housing.

The cursor will change to ″Prohibited″ to indicate that dropping is not


possible.

551 EN2Z-0937GE51 R0518


TERMINAL ASSIGNMENT FUNCTION CARE

RESULT: TAF inserts the selected module with its points in the target slot.

EN2Z-0937GE51 R0518 552


CARE TERMINAL ASSIGNMENT FUNCTION

553 EN2Z-0937GE51 R0518


TERMINAL ASSIGNMENT FUNCTION CARE

Remove Module
Purpose Remove module. When removing a module where datapoints are still assigned to,
they will be removed.

The necessary re-assignment may be avoided by assigning the points to another


module before removing the module.

Procedure 1. Click right mouse key on the module to be removed, then click Remove
Module (highlighted).

RESULT: If points are still remaining on the module, they will be concurrently
removed with the module and indicated in the logical plant tree as
follows:

On board black
Boardless white
On board and mapped yellow
Boardless and mapped yellow
Boardless Flexpoint red

Working With Points


Points can be assigned to modules, removed from modules, and shifted between
modules or between terminals on the same module. In addition their types can be
changed.

Depending on their status, points are displayed in different colors in the logical plant
tree:

Point Display Point status/type Color


On board black
Boardless white
On board and mapped yellow
Boardless and mapped yellow
On board, mapped and bound green
Boardless, mapped and bound green
Boardless Flexpoint red

EN2Z-0937GE51 R0518 554


CARE TERMINAL ASSIGNMENT FUNCTION

Assign Point to IP or DIO Module


Purpose Assign a point to a module. Points can be assigned manually from the logical plant
tree to a module by Drag&Drop.

NOTE: Points of an XF528 module can be assigned to an XF523 module and vice
versa. For combinations of points and modules, refer to Combine Point
and Module section.

Procedure 1. In the logical plant tree, click on the datapoint you want to assign to a physical
terminal.

2. Drag it to the desired terminal.

RESULT: When moving the datapoint over the terminals, any terminal that
matches to the datapoint is displayed in green. Non-matching
terminals show the "Prohibited" symbol.

3. Drop the point at the desired terminal.

Assign Point/NV to LON device


Purpose The assignment of CARE points or NVs to a LON device is the basic procedure to
connect LON devices with each other (see Connect CARE datapoints/NVs to NVs
section).

Move Point
Purpose Move point.

Points can be moved from one terminal to another by using Drag&Drop.

• Points can be dragged and dropped on a free terminal on the same or another
identical module.
• Points can be dragged and dropped on different module types, which results in
setting of the corresponding subtypes.
• Points will automatically get boardless if the module is deleted by removing.

NOTE: A point cannot be moved to:

• An occupied terminal
• A free terminal on another module not the same family of
type
• Another place in the module graphic
• Outside a housing

555 EN2Z-0937GE51 R0518


TERMINAL ASSIGNMENT FUNCTION CARE

For combinations of points and modules, refer to Combine Point and Module
section.

Procedure 1. Drag point by clicking and holding the left mouse key on the appropriate
terminal. Drag the point to the free target terminal, then drop it by releasing the
mouse key.

NOTE: A point can only be moved on a free module terminal. The cursor will
change to ″Prohibited″ to indicate that dropping is not possible.

RESULT: TAF inserts the selected point on the target terminal, in this case
terminal 7 on module 2. The original terminal number will be kept
highlighted as long as no other point has been clicked.

Remove Point
Purpose Remove point from module/LON device. The point will get boardless.

Procedure 1. Click on the point on the module.

2. Click right mouse key and with left mouse key, click on Remove Point in the
context menu.

RESULT: The point is removed from the module and indicated in the logical
plant tree as follows:

Point status/type Color


On board black
Boardless white
On board and mapped yellow
Boardless and mapped yellow
On board, mapped and bound green
Boardless, mapped and bound green
Boardless Flexpoint red

EN2Z-0937GE51 R0518 556


CARE TERMINAL ASSIGNMENT FUNCTION

Display/Change Point Type


Purpose Display/Change point type of points placed in a module.

Procedure 1. Click right mouse key on a the point.

2. If the point resides on a module, click Change Point Type (highlighted).

RESULT: TAF displays the Change Point Type dialog box of the appropriate
point and the current point type is displayed.

3. To change point type, select the appropriate point type from the New Type
drop-down list box.

557 EN2Z-0937GE51 R0518


TERMINAL ASSIGNMENT FUNCTION CARE

4. Click OK.

RESULT: TAF assigns the point to the appropriate module terminal.

For combinations of points and modules, refer to Combine Point and Module
section.

EN2Z-0937GE51 R0518 558


CARE TERMINAL ASSIGNMENT FUNCTION

Combine Point and Module


Combinations between possible points and modules are listed in the following
tables.

Modules of Excel 500/600 Controllers.

IP Modules
XF521 Slow analog input card
XF526 Fast analog input card
XF522 Analog output card with switches
XF527 Analog output without switches
XF523 Lo digital input card
XF528 Hi digital input card
XF524 Digital output card with switches
XF529 Digital output without switches
XF525 Mot card ( 3 position)

DIO Modules
XFL521 Slow analog input card
XFL522 Analog output card
XFL523 Digital input card
XFL524 Digital output card

Basic Modules
XP501,XP502 Power supply cards
XC5010C, XCL5010, CPU cards
XC6010

Assigned Points of Excel 500/600 Controllers

Module Type Point Type Care Subtype Point Other Possible Other Possible Valid
Module Subtypes Care Types Terminals
Type

IP (normal bus modules)


XF521 AI AI_SLOW - - - 1-8
Slow AI DI_NC - - - DI_NO 1-8
DI_NO - - - DI_NC 1-8

XF526 AI AI_SLOW - AI_FAST - 1-8


Fast AI AI_FAST - AI_SLOW - 1-8
DI_NC - - - DI_NO 1-8
DI_NO - - - DI_NC 1-8

559 EN2Z-0937GE51 R0518


TERMINAL ASSIGNMENT FUNCTION CARE

Module Type Point Type Care Subtype Point Other Possible Other Possible Valid
Module Subtypes Care Types Terminals
Type

IP (normal bus modules)

XF522 AO - W - MOT 1-5


AO with - O - MOT 1-8
switches CHANGE PULSED O NOT_PULSED - 1-8
NOT_PULSED W - - 1-5
O PULSED - 1-8

SWITCH PULSED O NOT_PULSED - 1-8


NOT_PULSED W - - 1-5
O PULSED - 1-8
MOT - - - AO 1-8

XF527 AO - O - MOT 1-8


AO CHANGE PULSED O NOT_PULSED - 1-8
without NOT_PULSED O PULSED - 1-8
switches SWITCH PULSED O NOT_PULSED - 1-8
NOT_PULSED O PULSED - 1-8
MOT - - - AO 1-8

XF523 DI_NC - - - DI_NO 1-12


DI DI_NO - - - DI_NC 1-12
S_COUNT - - - - 1-12
F_COUNT - - - - 1-2

XF528 DI_NC - - - DI_NO 1-12


DI high DI_NO - - - DI_NC 1-12
density S_COUNT - - - - 1-12
F_COUNT - - - - 1-2

XF524 CHANGE NOT_PULSED W - - 1-5


DO with O - - 1-5
switches SWITCH PULSED O - - 6
NOT_PULSED W - - 1-6
O - - 1-6

XF529 CHANGE PULSED O PULSED - 1-5


DO NOT_PULSED O NOT_PULSED - 1-5
without SWITCH PULSED O NOT_PULSED - 1-6
switches NOT_PULSED O PULSED - 1-6

XF525 MOT - - - - 1-3


3 Pos -

EN2Z-0937GE51 R0518 560


CARE TERMINAL ASSIGNMENT FUNCTION

Module Type Point Type Care Subtype Point Other Possible Other Possible Valid
Module Subtypes Care Types Terminals
Type

DIO (LON bus modules)


XFL521 AI AI_SLOW 1-8
AI DI_NC DI_NO 1-8
DI_NO DI_NC 1-8

XFL522 AO W MOT 1-8


AO O MOT 1-8
with switches CHANGE PULSED O NOT_PULSED CHANGE 1-8
PULSED SWITCH 1-8
NOT_PULSED SWITCH 1-8
NOT_PULSED W NOT_PULSED SWITCH 1-8
O PULSED CHANGE 1-8
PULSED SWITCH 1-8
NOT_PULSED SWITCH 1-8
SWITCH PULSED O NOT_PULSED SWITCH 1-8
PULSED CHANGE 1-8
NOT_PULSED CHANGE 1-8
NOT_PULSED W NOT_PULSED CHANGE 1-8
O PULSED SWITCH 1-8
PULSED CHANGE 1-8
NOT_PULSED CHANGE 1-8
MOT AO 1-8

XFL523 DI_NC DI_NO 1-12


DI DI_NO DI_NC 1-12
low S_COUNT F_COUNT 1-12
F_COUNT S_COUNT 1-12

XFL524 CHANGE O NOT_PULSED CHANGE


DO PULSED SWITCH
with switches NOT_PULSED SWITCH
NOT_PULSED W NOT_PULSED SWITCH 1-6
O PULSED SWITCH 1-6
NOT_PULSED SWITCH 1-6
PULSED CHANGE 1-6
SWITCH PULSED O NOT_PULSED CHANGE 1-6
PULSED CHANGE 1-6
NOT_PULSED SWITCH 1-6
NOT_PULSED W NOT_PULSED CHANGE 1-6
O NOT_PULSED CHANGE 1-6
PULSED CHANGE 1-6
PULSED SWITCH

561 EN2Z-0937GE51 R0518


TERMINAL ASSIGNMENT FUNCTION CARE

W: Point module type with switches


O: Point module type without switches

NOTE: Point Module Type can generally be changed from W to O and vice
versa for all point types and CARE sub types that can have a module
type, except for CARE sub type “PULSED”; this sub type can only be
used together with module type “without switches”.

Flexible subpoints will be treated like the corresponding digital outputs or


inputs. However, for the outputs, only the combination
"SWITCH/NOT_PULSED/without switches" is supported.

EN2Z-0937GE51 R0518 562


CARE TERMINAL ASSIGNMENT FUNCTION

Unassigned Points of Excel 500/600 Controllers

Module Point CARE Subtype Point Other Possible Other Possible Terminals Other
Type Type Module Subtypes CARE Types Module
Type Type
Unassign. AI AI_SLOW - AI_FAST - n/a n/a
AI AI_FAST - AI_SLOW - n/a n/a
Unassign. AO - W - AO n/a O
AO - O AO n/a W
- W MOT n/a n/a
- O MOT n/a n/a
Unassign. MOT - - - AO n/a O
3 Pos
Unassign. DI_NC - - - DI_NO n/a n/a
DI DI_NO - - - DI_NC n/a n/a
S_COUNT - - - F_COUNT n/a n/a
F_COUNT - - - S_COUNT n/a n/a
Unassign. CHANGE PULSED O PULSED SWITCH n/a O
DO PULSED O NOT_PULSED CHANGE n/a O
PULSED O NOT_PULSED CHANGE n/a W
PULSED O NOT_PULSED SWITCH n/a O
PULSED O NOT_PULSED SWITCH n/a W
NOT_PULSED O NOT_PULSED SWITCH n/a O
NOT_PULSED O NOT_PULSED CHANGE n/a W
NOT_PULSED O NOT_PULSED SWITCH n/a W
NOT_PULSED O PULSED CHANGE n/a O
NOT_PULSED O PULSED SWITCH n/a O
NOT_PULSED W NOT_PULSED SWITCH n/a W
NOT_PULSED W NOT_PULSED CHANGE n/a O
NOT_PULSED W NOT_PULSED SWITCH n/a O
NOT_PULSED W PULSED CHANGE n/a O
NOT_PULSED W PULSED SWITCH n/a O
SWITCH PULSED O PULSED CHANGE n/a O
PULSED O NOT_PULSED SWITCH n/a O
PULSED O NOT_PULSED SWITCH n/a W
PULSED O NOT_PULSED CHANGE n/a O
PULSED O NOT_PULSED CHANGE n/a W
NOT_PULSED O NOT_PULSED CHANGE n/a O
NOT_PULSED O NOT_PULSED SWITCH n/a W
NOT_PULSED O NOT_PULSED CHANGE n/a W
NOT_PULSED O PULSED SWITCH n/a O
NOT_PULSED O PULSED CHANGE n/a O
NOT_PULSED W NOT_PULSED CHANGE n/a W
NOT_PULSED W NOT_PULSED SWITCH n/a O
NOT_PULSED W NOT_PULSED CHANGE n/a O
Unassign. SWITCH NOT_PULSED W PULSED SWITCH n/a O
DO NOT_PULSED W PULSED CHANGE n/a O

563 EN2Z-0937GE51 R0518


TERMINAL ASSIGNMENT FUNCTION CARE

W: Point module type with switches


O: Point module type without switches

NOTE: Point Module Type can generally be changed from W to O and vice
versa for all point types and CARE sub types that can have a module
type, except for CARE sub type “PULSED”; this sub type can only be
used together with module type “without switches”.

Flexible subpoints will be treated like the corresponding digital outputs or


inputs. However, for the outputs, only the combination
"SWITCH/NOT_PULSED/without switches" is supported.

Points of Excel 80/100 Controllers

Module Type Point Type Valid Differences for XL80 Controllers


Terminals
Module One (AI) AI Slow 1-8 -
DI Normally Closed 1-8
DI Normally Open 1-8
Module Two (AI) AI Slow 1-4 -
DI Normally Closed 1-4
DI Normally Open 1-4
Module Three (DI) DI Normally Closed 1-12 Module does not exist in XL80 controllers
DI Normally Open 1-12
Totalizer Slow 1-12
Totalizer Fast 1-2
Module Four (AO) AO Continuous 1-8 -
DO Change Over, pulsed Without Switches 1-8
DO Change Over, not pulsed Without Switches 1-8
DO Normally Open, pulsed Without Switches 1-8
DO Normally Open, not pulsed Without 1-8
Switches
AO 3 Pos 1-8
Module Five (AO) AO Continuous 1-4 -
DO Change Over, pulsed Without Switches 1-4
DO Change Over, not pulsed Without Switches 1-4
DO Normally Open, pulsed Without Switches 1-4
DO Normally Open, not pulsed Without 1-4
Switches
AO 3 Pos 1-4

Flexible points of the types Multistage and Pulse2 and the DO subpoints of
DO_FEEDBACK_DI flexpoints are handled like normal points of the following type:

“DO Normally Open, not pulsed Without Switches”

The DI subpoints of DO_FEEDBACK_DI flexpoints can have the following types


and are handled like normal points of the same type:

“DI, Normally Open”


“DO, Normally Closed”

EN2Z-0937GE51 R0518 564


CARE TERMINAL ASSIGNMENT FUNCTION

Working With LON Devices


In addition to the physical assignment of CARE datapoints to IP or distributed I/O
modules, the logical assignment of LON devices will be performed on the terminal
assignment tab.

Configure Display
Purpose To configure the display of LON devices on the terminal assignment tab.

The display configuration can be varied by the following concurrently applicable


means:

• Zoom, to reduce or enlarge the display with a magnification between 50 and 100
percent
• Column configuration to define the number of devices per row
• Sort order of devices by name, channel and system

NOTE: Zoom also applies to the variable display of LON housings with DIO
modules.

Procedures 1. To determine the zoom, select the magnification from the Zoom drop-down
listbox in the toolbar. When the magnification once has been selected in the
drop-down listbox you can use the mouse wheel for continuously adjusting the
magnification.

RESULT: The devices will be displayed according to the selected


magnification and to the configured number of columns.
In case Auto has been selected for the column configuration,
CARE optimizes the column number so that no device will be
cut vertically from display. You might scroll vertically to view
further devices. In case a certain number of columns (4 to 10 by
default, a user-defined number can be entered) has been
selected, CARE always displays the devices in that defined
column number independent from the magnification.

565 EN2Z-0937GE51 R0518


TERMINAL ASSIGNMENT FUNCTION CARE

2. To determine the column number, select the number from the Column Number
drop-down listbox in the toolbar. When the column number once has been
selected in the drop-down listbox you can use the mouse wheel for
continuously selecting the column number.

RESULT: The devices will be displayed according to the selected column


number and magnification. In case Auto has been selected for
the column configuration, CARE optimizes the column number
so that no device will be cut vertically from display. In case a
certain number of columns (4 to 10) has been selected, CARE
always displays the devices in that defined column number
independent from the magnification.

EN2Z-0937GE51 R0518 566


CARE TERMINAL ASSIGNMENT FUNCTION

3. To determine the sort order, select desired option from the Sort Order drop-
down listbox in the toolbar:

Name
All bound devices of the controller will sorted by name

Channel
All bound devices of the controller will be sorted by their channel assignment.

System
All bound devices of the controller will be sorted by their system assignment

When the sort order once has been selected in the drop-down listbox you can
use the mouse-wheel for continuously changing the sort order.

RESULT: The devices will be displayed according to the selected sort


order option whereas the magnification and the column
configuration applies concurrently.

567 EN2Z-0937GE51 R0518


LON device is
concurrently
added TERMINAL
to ASSIGNMENT FUNCTION CARE
three
locations
s concurrently
dd d t

The devices are


sorted by System
as follows;

Default System
Subsystem_A

Logical Assignment of LON devices


For the logical assignment of LON devices, please refer to the Assign LON devices
(Binding) section.

EN2Z-0937GE51 R0518 568


CARE FILE MANAGEMENT

FILE MANAGEMENT
Chapter Contents This chapter includes the following procedures.

Back Up Functions

CARE Database (including projects, plants and device library)


Projects (including plants)

Restore Functions

CARE Database (including plants and device library)


Projects (including plants)

Import/Export Functions

Import/Export the Element Library (CARE XL-5000 only)

Import Controller Files (to copy operator changes made to controller files,
CARE XL-5000 only)

Export Grapic Files (Schematic, Control Strategy, Switching Logic,


CARE XL-5000 only).
For graphic files export, please refer to the DOCUMENTATION chapter.

Controller Upload/Download

For controller upload/download information, please refer to the ONLINE


SERVICE AND COMMISSIONING chapter.

Backups / Restores The CARE database contains files that pertain to all projects and plants as well as
files that pertain to individual projects and plants.

When you back up the CARE database, software copies all necessary files for
current projects and plants in CARE and creates a single file named CARExxxx.DB
where xxxx is a sequencing number to allow more than one database backup to
exist in a directory.

When you back up a project, software copies all the files relevant to just that project
and creates a backup file with an extension of .PJT.

NOTE: It is recommended to backup the database, or at least the project after


any CARE session to avoid the loss of work.

For backups and restores in CARE the following files can be purposefully
included/excluded from the backup and restore process

• Pic files (segment graphics in the plant schematics)


• Default files
• Controller files
• XFMs
• Element library

By default the files necessary for the respective backup will be included. By default
all files which were backed up will be automatically included in the respective
restore.

Restoring old Backups When backupping databases, projects, or plants in CARE versions lower than
3.01.00, the above-mentioned files were not backed up automatically.

If any of these files are missing or different to the corresponding files of CARE
3.01.00 it may become necessary to copy it separately into the respective folders
under the CARE directory to complete the restore process and get the desired
results.

569 EN2Z-0937GE51 R0518


FILE MANAGEMENT CARE

Back Up the CARE Database


Purpose Copy CARE database files in case they are needed to replace corrupted database
files. When you back up the CARE database, software copies all necessary files for
current projects and plants in CARE and creates a single file named CARExxxx.DB
where xxxx is a sequencing number to allow more than one database backup to
exist in a directory.

Procedure 1. Click menu item Database, then drop-down item Backup.

RESULT: The Backup Database dialog box displays. The target folder
displayed in Save in is the folder that will receive the copies of the
files. The target folder can be defined as default in the Global
Options dialog, see “Set Global CARE Options” section.

2. In Save in, select a different drive and/or folder if desired. If you want to save
the files in subfolders that may be displayed in the list, double-click the desired
subfolder.

3. In File Name, enter the name for the backup file.

4. Under XL500 Settings, all those files are checked which have been pre-
defined for inclusion in the Global Options dialog (see “Set Global CARE
Options” section). If desired, uncheck files you want to be excluded from the
database backup.

EN2Z-0937GE51 R0518 570


CARE FILE MANAGEMENT

NOTE: It is recommended to include all files.

5. Under BACnet Settings, the Include Graphic Files option is checked which
saves all graphic files in the database backup. If desired, uncheck this option if
you want graphic files to be excluded from the database backup.
6. Under Backup Description, enter additional information about the database
you want to backup, if desired.

7. Click OK to initiate backup.

RESULT: A Backup window displays with percentage (or number of records)


completed as well as an Abort button in case you want to stop the
process. When the backup is complete, the message box
disappears and the main CARE window redisplays.

Back Up a Project
Purpose Copy project files to a backup directory or diskette. Keeping a ”good” copy of
project files is useful if the project is changed incorrectly or if the files become
corrupt. Use the Restore a Project procedure to retrieve these files when required.

Procedure 1. Click menu item Project, then drop-down item Backup.

RESULT: The Backup Project dialog box displays. The name of the currently
selected project is shown under Source project in the middle left
area. The target folder displayed in Save in is the folder that will
receive the copies of the files. The target folder can be defined as
default in the Global Options dialog, see “Set Global CARE
Options” section.

571 EN2Z-0937GE51 R0518


FILE MANAGEMENT CARE

2. In Save in, select a different drive and/or folder if desired. If you want to save
the files in subfolders that may be displayed in the list, double-click the desired
subfolder.

3. In File Name, enter the name for the backup file.

4. Under XL500 Settings, all those files are checked which have been pre-
defined for inclusion in the Global Options dialog (see “Set Global CARE
Options” section). If desired, uncheck files you want to be excluded from the
database backup.

NOTE: It is recommended to include all files.

5. Under BACnet Settings, the Include Graphic Files option is checked which
saves all graphic files in the database backup. If desired, uncheck this option if
you want graphic files to be excluded from the database backup.

6. Under Backup Description, enter additional information about the project you
want to backup, if desired.

7. Click OK to initiate backup.

RESULT: A Backup window displays with percentage (or number of records)


completed as well as an Abort button in case you want to stop the
process. When the backup is complete, the message box
disappears and the main CARE window redisplays.

Naming Convention Backup software uses the project name to create a file name with the first five
characters of the project name, a sequencing number, and an extension of PJT.
Examples:

Project Name Backup File Name

STD1 STD1001.PJT
HONEYWELL HONEY003.PJT

Each time you back up a project, software increments the numbers in the file name,
for example, the first backup for the STD1 project is STD1001.PJT; the next backup
is STD1002.PJT; the next, STD1003.PJT, etc. Each file is a different version of the
same project.

Restore the CARE Database


Purpose Replace CARE database files with the backup copies made with the Back Up the
CARE Database procedure.

Restoring old Backups If you restore a CARE database that was backed up with CARE software prior to
Version 1.4.1, CARE first does a complete database backup before the restore
operation is attempted. This action is done so that in case of a restore failure or
user abort, the database can be restored to its state before the restore was
attempted.

If there is a restore failure or user abort, restore software initiates a new restore
from the automatic backup. A message displays that a restore of the backup file is
occurring.

If there is a catastrophic failure (PC is turned off or an application generates a


General Protection Fault error and only Windows or DOS is active), the restore
will not have time to retrieve the backup. In that case, restart CARE and first do a
restore of the backup since the CARE database may be corrupt. To restore the
backup, use the standard restore procedure described in this section and navigate
to the CARE\TEMP directory. That directory holds the automatic backup that restore
originally did.

Restores of backups done with software Version 1.4.1. or later are also protected
but with a different, more efficient mechanism.

EN2Z-0937GE51 R0518 572


CARE FILE MANAGEMENT

When backupping databases in CARE versions lower than 3.01.00, the following
files were not backed up automatically:

• Element library
• Pic files (segment graphics in the plant schematics)
• Default files
• Controller files
• XFMs

If any of these files are missing or different to the corresponding files of the CARE
version 3.01.00 or higher it may become necessary to copy it separately into the
respective folders under the CARE directory to complete the restore process and
get the desired results.

Directories

Pic files <drive:>\care\pic


Default files <drive:>\care\pcbstd
Xfms <drive:>\care\xfm\original
Controller files <drive:>\care\<project name>
Element library If the import of an element library of previous version is
necessary it must be done via the Import Element library menu
item. Please refer to the Import Element Library section.

Restoring CARE Backups of Since CARE Ver. 3.01.00 it is up to you to include/exclude certain files such
Ver. 3.01.00 and higher as the element library, pic files (segment graphics in the plant schematics), default
files, XFMs, and controller files for the backup process. Any file that was backed up
will be automatically restored unless you exclude it.

Procedure 1. Click menu item Database, then drop-down item Restore.

RESULT: The Restore Database dialog box displays with the default source
folder as defined in the Global Options dialog, see “Set Global
CARE Options” section. The default folder as defined in the Global
Options dialog should contain the backup files.

573 EN2Z-0937GE51 R0518


FILE MANAGEMENT CARE

2. If the database backup file is in another folder, open the folder by using the
Find in field and selecting a different drive and/or main folder if desired. If the
database backup file is in a subfolder displayed in the list, double-click the
desired subfolder.

RESULT: Under Database backup, all available .DB files are shown with
date, time, and DB-Version.

EN2Z-0937GE51 R0518 574


CARE FILE MANAGEMENT

3. Click the date, time, and version line of the backup that you want to copy.

4. Under XL500 Settings, all those files are checked which have been pre-
defined for inclusion in the Global Options dialog (see “Set Global CARE
Options” section). If desired, uncheck files you want to be excluded from the
database restore.

NOTE: It is recommended to include all files.

5. Under BACnet Settings, the Include Graphic Files option is checked which
restores all graphic files included in the database. If desired, uncheck this
option if you want graphic files to be excluded from the database restore.

6. Click OK to initiate backup.

NOTE: It is recommended to include all files.

7. Click OK to initiate restore.

RESULT: A Restore window displays with percentage (or number of records)


completed as well as an Abort button. The Abort button is gray
(disabled) because once the database restore begins, no recovery
to the original database contents is possible (unless the original
database was backed up before the restore was attempted).

When the restore is complete, the message box disappears and


the main CARE window redisplays.

Delete Button You can also delete a backup file by selecting it and clicking the Delete button.

Delete Button You can also delete a backup file by selecting it and clicking the Delete button.

575 EN2Z-0937GE51 R0518


FILE MANAGEMENT CARE

Restore a Project
Purpose Retrieve a copy of a project to place it in the PC. This procedure is useful if the PC
files are corrupt or if changes were made that need to be erased.

Cannot Replace
Current Project Files Software does not restore a project to a directory if there are already project files
with the same name in the directory. Either delete the project that already exists or,
to get another copy of that project, change the name of the Target project in the
Restore Project dialog box (see Procedure).

Restoring old Backups If you restore a project that was backed up with CARE software prior to Version
1.4.1, CARE first does a complete database backup before the restore operation is
attempted. This action is done so that in case of a restore failure or user abort, the
database can be restored to its state before the restore was attempted.

If there is a restore failure or user abort, restore software initiates a new restore
from the automatic backup. A message displays that a restore of the backup file is
occurring.

If there is a catastrophic failure (PC is turned off or an application generates a


General Protection Fault error and only Windows or DOS is active), the restore
will not have time to retrieve the backup. In that case, restart CARE and first do a
restore of the backup since the CARE database may be corrupt. To restore the
backup, use the standard restore procedure described in this section and navigate
to the CARE\TEMP directory. That directory holds the automatic backup that restore
originally did.

Restores of backups done with software Version 1.4.1. or later are also protected
but with a different, more efficient mechanism.

When backupping projects in CARE versions lower than 3.01.00, the following files
were not backed up automatically:

• Element library
• Pic files (segment graphics in the plant schematics)
• Default files
• Controller files
• XFMs

If any of these files are missing or different to the corresponding files of CARE
version 3.01.00 or higher it may become necessary to copy it separately into the
respective folders under the CARE directory to complete the restore process and
get the desired results.

Directories

Pic files <drive:>\care\pic


Default files <drive:>\care\pcbstd
Xfms <drive:>\care\xfm\original
Controller files <drive:>\care\<project name>
Element library If the import of an element library of previous version is
necessary it must be done via the Import Element library menu

Procedure 1. Click menu item Project, then drop-down item Restore.

RESULT: The Restore Project dialog box displays with the default source
folder as defined in the Global Options dialog, see “Set Global
CARE Options” section. The default folder as defined in the Global
Options dialog should contain the backup files.

EN2Z-0937GE51 R0518 576


CARE FILE MANAGEMENT

2. If the project backup file is in another folder, open the folder by using the Find
in field and selecting a different drive and/or main folder if desired. If the project
backup file is in a subfolder displayed in the list, double-click the desired
subfolder.

RESULT: Under Project backup, all available .PJT files are shown with name,
date, time, and DB-Version.

577 EN2Z-0937GE51 R0518


FILE MANAGEMENT CARE

3. Click name of project that you wish to use as source.

RESULT: Software writes the name in Target project.

4. To change the name of the resulting project, type a new name in Target
project.

5. Select the desired project backup file.

RESULT: If the backup file is lower than Version 10.08.01, the Upgrade
button becomes active and the Restore button becomes inactive.

6. If the Upgrade button is active, click it to convert the lower version file to the
current CARE version.

RESULT: Software adds a converted backup file of the current version to the
list in the Project backup field.

7. Under XL500 Settings, all those files are checked which have been pre-
defined for inclusion in the Global Options dialog (see “Set Global CARE
Options” section). If desired, uncheck files you want to be excluded from the
project restore.

NOTE: It is recommended to include all files.

8. Under BACnet Settings, the Include Graphic Files option is checked which
restores all graphic files of the project. If desired, uncheck this option if you
want graphic files to be excluded from the project restore.

EN2Z-0937GE51 R0518 578


CARE FILE MANAGEMENT

9. Click Restore to initiate restore.

RESULT: A Restore window displays with percentage (or number of records)


completed as well as an Abort button in case you want to stop the
process. When the restore is complete, the dialog box redisplays in
case you want to do more restores.

If a message displays that there is missing element information and


the restore fails, you need to import the missing elements from the
CARE database where the project originated. See the Import the
Element Library section for details.

NOTE: If the project is already in the directory, software displays a message that it
already exists. Click OK to close the message box and return to the
Project restore dialog box.

10. Click Close to remove the Project restore dialog box and return to the CARE
main window.

Export the Element Library


NOTE: This section applies to CARE XL-5000 only.

Purpose Output element records from the CARE database for use in other CARE databases.

”Elements” are source records for the segments that are available for each type of
plant. For example, an air conditioning plant can have fan, sensor, and damper
segments. The fan segment can include return and supply air fans in single and
multiple configurations.
CARE Element Editor software (a separate software package) provides functions to
modify elements and/or create new elements. You use this Export function to create
a backup file of element records that can be copied to other CARE databases. See
the Import the Element Library section for details.

Procedure 1. Click menu item Database, then drop-down items Export, Element Library.

RESULT: The Element Library Export dialog box displays. The Target
directory is the drive and directory that will receive copies of the
files. The dialog box example shows c:\care.

579 EN2Z-0937GE51 R0518


FILE MANAGEMENT CARE

2. In the Plant Type list all plant types are selected. Click on plant types you do
not want to export. Use Select All and Select None buttons to select/deselect
desired plant types.

3. Typically, you export to a diskette so you can transport the elements to another
CARE database on another PC. To select a different drive and directory, use
Windows techniques.

RESULT: The Target directory shows the desired drive and directory name.

4. Click OK to initiate export.

RESULT: An Export window displays with percentage (or number of records)


completed as well as an Abort button in case you want to stop the
process. When the export is complete, the message box
disappears and the main CARE window redisplays.

Import the Element Library


NOTE: This section applies to CARE XL-5000 only.

Purpose Read an Element Library file that was exported from a CARE database to obtain
new element records and place them in another CARE database for use in the
Schematic function..

”Elements” are source records for the segments that are available for each type of
plant. For example, an air conditioning plant can have fan, sensor, and damper
segments. The fan segment can include return and supply air fans in single and
multiple configurations.

CARE Element Editor software (a separate software package) provides functions to


modify elements and/or create new elements. If you want to copy the new elements
you create to other CARE databases, you can use this Import function to merge

EN2Z-0937GE51 R0518 580


CARE FILE MANAGEMENT

new elements from the modified CARE database with element records in another
CARE database.

Import Process The Import process only copies backup elements that are new to the target
database. It does not copy backup elements that are already in the target database,
but are changed in the backup. The rules for considering an element ”new” to a
database are:

1. If any of the following fields in a backup element are different from those for
any element in the target database:

a. Plant type
b. Main group name or group name
c. Element name
d. PIC file name
e. Width of element
f. Text that displays in the segment menu
g. Next-group name (that is, the drop-down if the element has one)
h. CARE type and user address for each default point in the element

2. If plant type is missing, software assumes it to be a new plant type and


creates it in the target database.

3. If main group name or group name is missing (within a plant type), software
assumes the group to be new and creates it in the target database.

4. If element name is missing (within a group and plant type), software


assumes it to be a new element and creates it in the target database along
with all its default point information.

If plant type, group name, and element name match but any of the other criteria fail
to match, software creates a new element under the same plant type and group.
Software assigns a new name to this element by prefixing the old name with an x_.
The new element includes the same default point information as the backup
element.

If the above criteria match exactly, software does NOT write the element to the
target database.

For example, if a backup element only has a different engineering unit from a target
database element, software will NOT overwrite the target database element.

Restore Failures CARE project and plant restores can fail because the backup file may not contain
all the necessary element information. CARE project and plant backups only
contain element information to restore element connection at restore time. If you try
to restore a project or plant to a CARE database that does not contain the
appropriate elements, the restore fails. This situation may occur if you were trying to
share a project or plant backup with another user who does not have an up-to-date
Element Library.

To enable a successful restore, perform the following steps:

1. Export the Element Library from the CARE database where the original
project or plant resided. Export to a diskette. The next section, Export the
Element Library, explains this process.
2. Import the Element Library to the target database from the export diskette
generated in Step 1. Use the following procedure.

Procedure 1. Insert the diskette that contains the exported Element Library into a PC drive.

2. Click menu item Database, then drop-down items Import, Element Library.

RESULT: The Element Library Import dialog box displays with a default
Source directory (usually, the CARE directory) and a list of
available backup files (date, time, version number) in the Source
directory.

581 EN2Z-0937GE51 R0518


FILE MANAGEMENT CARE

3. To select a different Source directory, in this case, the diskette, click the drive
name where you inserted the diskette. Use other Windows techniques as
necessary to display the appropriate Source directory and Element Library
backup data.

RESULT: The Source directory shows the desired drive and directory name.
The Database backup box shows the date, time, and version of the
backup files you want.

4. If the source files were created with CARE 2.02 or a lower version, click
Upgrade to convert the files to the current CARE version, in this case to
version 3.00.00.

RESULT: Two backup sets display in the dialog box, one for the lower CARE
version and one for 3.00.00.

5. Click the date, time, and version line of the backup that you want to copy.

6. Click Import to initiate import.

RESULT: An Import window displays with percentage (or number of records)


completed as well as an Abort button in case you want to stop the
process. Software first decompresses the backup files (0-100%),
then does the restore (0-100%). When the import is complete, the
message box disappears and the main CARE window redisplays.

EN2Z-0937GE51 R0518 582


CARE FILE MANAGEMENT

Import Controller Files


NOTE: This section applies to CARE XL-5000 only.

Purpose Update controller files in the CARE database based on uploaded files from a
controller. Or, you can just create a report of the differences between the controller
files and the CARE database files for the controller.
Operators can change point, parameter, and Time Program data in controller data
files via Excel Online, or Excel Building Supervisor (XBS) operator terminals.

You can use this Import function to copy those changes into the original CARE
database for the controller. If you subsequently need to reload the controller from
CARE, the reload will include the operator changes. See Appendix: Point Attributes
Tables for information about the types of point information that are available to the
import function.

Parameter Mismatches Parameter mismatches occur if outdated controller files are imported. If the
controller files in the CARE database have been changed and/or retranslated but
not downloaded to the controller, a mismatch of parameters could occur after an
import of the uploaded, out-of-date controller files. The translation procedure can
change the file number and index number of a plant parameter, so that CARE
would no longer have the correct mapping of parameters to switching tables and
control loops and could put the parameters in the wrong place.

Verify that the controller files are the current translation of the CARE controller files
before uploading and importing them.

Controller Files Upload via XI584 For CARE versions lower 4.01.00 only running on Windows 95/98, the controller
files upload was performed using the XI584 operator tool. For detailed description
on the upload and import procedures, please refer to the Online help and/or the
user guide of the corresponding CARE version 74-5587–3 GE51 R0998, and the
Controller Data File Changes section in the XI584 Operator Manual 74-3555.
The procedure described in the following only applies to the Excel Online usage.

RACL Parameter Imports CARE 8.03.00 imports all editable (on-line and off-line) point attributes and time
programs. It can also import the Recursive Algorithmic Control Language (RACL)
parameters in certain circumstances. RACL parameters are used to generate the
RACL control programs that run in a controller.

IMPORTANT
The RACL parameters are not imported if the control strategies and
switching tables for the controller are not available in the target CARE
database, for example, if the controller was originally engineered in or
restored from a different CARE database from where you are currently
importing it (see following description of the two scenarios).

Scenario 1 CARE can import the RACL parameters if you are importing controllers (Ver. 1.1
and 1.2 OS) that were engineered with CARE 1.3.x or 1.4.x into the same CARE
database (upgraded to 8.03.00) where they were engineered or restored.

After the import, when you translate the imported controllers, CARE creates Ver.
1.2 OS controllers just as it does for non-imported controllers. CARE supports
upward compatibility (Ver. 1.1 controllers become Ver 1.2) but not downward
compatibility (cannot create Ver. 1.1 controllers).

Note that CARE does not "reverse engineer" control strategies and switching tables
from generated RACL programs (equivalent to trying to generate source code from
compiled C code). Reverse engineering is not necessary as long as the control
strategies and switching tables are still in the database. All CARE functions are
available for controllers imported to their original database.

Scenario 2 CARE cannot import the RACL parameters if you are importing controllers into a
different CARE database from the one where they were engineered or restored. To
be able to import RACL parameters, CARE must have the control strategies and
switching tables from which they are generated. Since the controllers were
originated elsewhere, the control strategies and switching tables are not available in
the database.

583 EN2Z-0937GE51 R0518


FILE MANAGEMENT CARE

The only CARE functions available for this kind of imported controller are the
Editors, Documentation, and Translation only of the point files (IPL generation
The Schematic, Control Strategy, Switching Table, and Translation of RACL
parameters (RACL generation) functions are not possible.

The following flowchart and procedure only applies to the import of the controller
files using Excel Online. For Controller Files Upload via XI584, please refer to the
Controller Files Upload via XI584 Note in the previous sections.

Import Controller Files Flowchart

Verify that controller is translated and controller


files are in relevant project directory

Backup CARE database

Use Excel Online to upload controller files from


controller into project directory

Return to CARE and select controller to be


imported

Click menu item „Database“, then submenu item


„Import“, and then „Controller Files“

In „Import Controller Data into CARE“ dialog box,


select target directory and project, and specifiy
the files to be uploaded

Check „Generate Impact Report only“ option and


initiate Import by clicking OK.

Analyze Impact Report to verify that changes are


made (file is stored with format .RPT in project
directory)

If Impact Report shows desired changes,


uncheck „Generate Impact Report only“ option
and again initiate Import by clicking OK.

Go to Editors, Control Strategy, and/or Switching


Logic functions to verify that controller files
changes are imported correctly

EN2Z-0937GE51 R0518 584


CARE FILE MANAGEMENT

Procedure

1. Make sure that you have translated the controller and that the controller files for
the controller you want to import are in the project folder. As a precaution, back
up the CARE database (see Back Up CARE Database section).

2. Use Excel Online to upload the controller files. See Upload Controller in
ONLINE SERVICE AND COMMISSIONING section for details.

3. If not already done, open the project in CARE and then select the controller.

4. Click menu item Database, then drop-down items Import and Controller.

RESULT: The Import Controller Data into CARE dialog box displays.

In Controller Root displays the name of the currently selected controller. This
name should be the destination controller. In Project List field, the associated
project name should be displayed.

5. In Drives, select the drive and in Directories, browse to the directory where
the desired uploaded controller files are stored. The directory defaults to the
project directory of the selected controller.

6. In Specification, click the types of files that you want to import (copy) or check
via impact report (see next step).

7. Check From CARE 1.4.0 if the controller files originate from a project created
with CARE 1.4.0. If the controller files originate from projects created with any
other CARE version, this option must be unchecked.

8. Check Generate Impact Report Only to firstly create an impact report before
importing the changes. The impact report summarizes the differences between
the CARE database files and the uploaded controller files. See the Impact
Report Example Note following the procedure.for a sample report.

IMPORTANT
It is strongly recommended to always run and analyze an impact
report before doing an import.

9. Click OK to generate the impact report.

585 EN2Z-0937GE51 R0518


FILE MANAGEMENT CARE

RESULT: When the import is done, an information box displays stating


´Import complete`. The impact report is saved as text file with .RPT
format (<application name>000. rpt) in the project folder along with
the later imported controller files.

10. Click OK to close the message box.

11. Open the .rpt file and review the report result with a text reader program, e.g.
Notepad.

12. If the result is satisfactory, uncheck Generate Impact Report Only, and then
click OK to import the controller files.

RESULT: When the import is done, an information box displays stating


´Import complete`.

13. Click OK to close the message box. Then, click Close to close the Import
Controller Data into CARE dialog box.

14. Go to the Editors, Control Strategy, and/or Switching Logic functions to verify
that the changes in the controller were imported correctly into the CARE
database.

Impact Report Example

Import Controller Impact Report

Date: 7-7-2008
Project: Honeywell Center
Controller: Third_Floor
Imported Controller File: CNTRL03

Point Data (.IPL) Report

Point Name: Outside Air Temperature


Technical Address: 1-3-1
Point Type : Analog Input

Data Field Originally Updated to


Descriptor Room 301 point 10 Room 302 point 10
Engineering Units Degree F Percent
Operating Mode Manual Automatic
Suppress Alarm Enabled Disabled
Alarm Text Shut Down System Call For Help
Alarm Delay 1 2
High Alarm Limit 100 90
High Warning Limit 95 85
Low Warning Limit 40 50
Low Alarm Limit 30 40

User Address: Damper Setpoint


Technical Address: 1-4-1
Point Type : Analog Output

Data Field Originally Updated to


Descriptor Room 101 point 10 Room 102 point 10
Engineering Units Degree F Percent
Operating Mode Manual Automatic
Suppress Alarm Enabled Disabled
Close to Open Time 0700 0600
Open to Close Time 1700 1800

Point Name: Calculated BTU


Technical Address: 30,1,1,11,1
Point Type : Pseudo Analog

EN2Z-0937GE51 R0518 586


CARE DOCUMENTATION

DOCUMENTATION
Purpose Print reports showing system operation and parameters. Also, you can output a
variety of file types to supplement job documentation. For example, you can create
graphic metafiles (.WMF extension) that are a plant’s schematics, control loops,
and switching tables. You can also create spreadsheet files that contain information
useful for pricing (Data Export function).

Report Inclusions The documentation function is available after the selection of a project. You can
print reports for a project, one or more plants (whether attached or unattached),
and/or one or more controllers. The scope of each report depends on report type
and the current selections (project, plant, and/or controller). The following table
describes these conditions and their results.

Current Selection
Project Only Project and Project and Project,
Report Type Controller Unattached Plant Controller, and
Attached Plant
Project Project Datasheet always the selected project
Controller Controller Summary, all controllers in selected all controllers in selected
Parameter Lists, selected project controller selected project controller
Termination,
Point Data,
Plant to Controller
Plant Plant Schematic, all plants in all plants for selected plant selected plant
Control Strategy, selected project selected
Switching Logic, controller
Math Function

Chapter Contents Export Graphic Files


Print Documentation
Technical Information
Point Type Abbreviations
Frequently Asked Questions

Export Graphic Files


Purpose Create graphic files in a metafile format (.WMF) from a plant’s schematic, control
strategy loops, and switching tables. These graphic files can be used in a CADCAM
operation or opened by software such as Micrografx Designer. The files provide a
form of documentation in addition to printed reports.

NOTE: If a control loop is multiple pages long, applications such as Designer


cannot display the exported graphic file.

Procedure 1. Click menu item Database, then dropdown items Export, Graphic.

RESULT: A list displays for selection of schematic, control strategy, or


switching logic files.

3. Click desired information type.

RESULT: An export dialog box displays that is related to the information type.
Following are examples of each type of dialog box. The dialog
boxes are very similar. They differ in the print options available to
the function. For example, you can export a schematic with or
without its user addresses. You can select the control loop to
export and also whether or not to export it with its user addresses,
schematic, or neither item. You can select the switching table to
export and whether or not to export it with its schematic.

587 EN2Z-0937GE51 R0518


DOCUMENTATION CARE

Schematic Export Dialog Box

Control Loop Export Dialog Box

EN2Z-0937GE51 R0518 588


CARE DOCUMENTATION

Switching Table Export Dialog Box

4. Select desired plant name. Click down arrow to display list of available plants.

5. Select desired options for the information type (with/without user addresses,
control loop and its options, or switching table and its options).

6. Click Output File Name and type a name for the exported file. The file must
have the WMF file extension.

The directory where software will save the file is listed under the word
Directories. If it is not the directory you want, use the listbox below it to choose
a different directory (and drive, if desired).

The Export Format defaults to metafiles (*.wmf). You should not change this
setting.

7. Click OK to begin the export process.

RESULT: A Graphic Export message box displays while software creates the
file. When done, it displays the message “Export is completed”.

8. Click OK to close the message box.

RESULT: The export dialog box remains on display.

9. Click Close to close the export box. Or, select another file to export and repeat
the process.

589 EN2Z-0937GE51 R0518


DOCUMENTATION CARE

Print Documentation
Purpose CARE provides printing of:

• Complete projects
• Controller(s) with attached plants
• Individual attached or unattached plants

IMPORTANT!
For printing complete projects with multiple controllers it is recommended
to print individual files for each controller because otherwise it would result
in Word documents that may exceed 1000 pages and file in excess of 40
Megabytes. Such large documents may cause Word for Windows to
become very slow.

Procedure 1. Click menu item Database, then submenu item Print.


Or, in the logical plant tree, right-click on the controller, plant or project and with
left mouse key, click on Print in the context menu.

RESULT: The printout main dialog box is displayed showing the options for
printout.

NOTE: Depending on the CARE version, XL5000 or BACnet and the item
(project, plant, and controller) selected, not all options are
available.
For example, for plants you can only print the table of contents,
project data sheet, plant schematic, control strategy loops,
switching logic tables and parameter list sorted by usage. In
XL5000, fast access lists are not available.

Fig. 1 Print Documentation dialog box of XL 5000 project

EN2Z-0937GE51 R0518 590


CARE DOCUMENTATION

Fig. 2 Print Documentation dialog box of BACnet project

2. If the project is selected and you want to print information of individual


controllers, click the Controllers… button and select /unselect the
controllers.

3. For printing complete projects with multiple controllers it is recommended to


print into individual files for each controller. Therefore, check Individual File
for Each Controller.

4. If you want to print directly to a printer, click the Printer Setup… button
, select the printer and define the printer settings in the Print Setup
dialog box.

5. Check the options that you want to print (refer to Select Print Options section
for detailed description). Or, use the Uncheck All button and re-
check individual options for changing the option choice.

6. Click the Browse button at the corresponding options to specify details of


an option.

7. Do any of the following:

To print directly to a printer, click the Print button

591 EN2Z-0937GE51 R0518


DOCUMENTATION CARE

Or, to print into file, click the File Output... button , and save the
print as rtf. file that can be edited in Word.

NOTES: You may want to have different page breaks or change the layout of
tables, etc. To optimize the page breaks and document layout,
Microsoft Word for Windows can be used to edit the document.

RTF (Rich Text Format) is a text format that can be accessed by


Word. This format has been selected for the printout, because it is
much more reliable than the DOC format. After loading a file into
Word, it might be saved also as DOC or any other Word supported file
format (refer to the Word user’s manual).

Select General Pre-Settings


Before selecting the specific options you want to print such as Table of Contents,
Project Datasheet, etc., you adjust the following general settings:

• setup printer
this should be done in case of direct printing
• select controllers
this can be done in case you want to print documentation of particular controllers
only
• single file or multiple file output
this should be applied in case of file output print mode usage.

Printer Setup

For direct printing on a printer, the printer can be selected and configured.

Procedure 1. Click Printer Setup... button in the Print documentation for


Project… dialog box to open the Print Setup dialog box.

NOTE: The Print Setup dialog box is a standard Windows feature and
always displays in the language of the installed Windows version.

2. In Name, select the printer.

EN2Z-0937GE51 R0518 592


CARE DOCUMENTATION

3. Under Orientation, select the printing format (Portrait or Landscape).

NOTE: Word always prints in landscape format, even if portrait is selected.


This is defined by the printout templates and is necessary because of
the size of the printout.

4. Under Paper, select the Paper size and the Source (tray) to be used. The
following paper sizes are supported: DIN A4, Letter and “User defined” paper
size. All paper sizes other than DIN A4 and Letter, which are available in the
dropdown list box, are seen as User defined. Each of these three paper sizes
can be set by default in the caredoc.ini file. When opening the Print Setup
dialog box, the caredoc.ini file default setting is displayed. If you now change
the size, it will be saved in the caredoc.ini file. When opening the Print Setup
dialog box next time, this setting is displayed by default (see the Technical
Information/Special Printer section).

5. The Properties... button may be used to set further printer options.

6. The Network... button may be used to connect to a network printer.

NOTE: The selection of the printer type is stored in the caredoc.ini file and
recovered when the printout is used the next time.

7. Click OK to confirm the settings.

Select Individual Controllers from a Project

If the project is selected for printout, all controllers of the project will be pre-selected
by default. This function allows printing documentation of individual controllers.

NOTE: The Controllers... button is grayed, if only a single controller has


been selected before calling the printout.

Procedure 1. Click the Controllers… button in the Print documentation for


Project… dialog box to open the Controller Selection:… dialog box.

Selected controller names display in white characters on blue


background. Unselected controller names display in black
characters on white background.

2. Select an unselected controller by clicking on it with the left mouse button.

3. Deselect a selected controller by clicking on it with the left mouse button.

4. Use the Tag All/Untag All button to select/deselect all controllers.

5. Click OK.

593 EN2Z-0937GE51 R0518


DOCUMENTATION CARE

Select Individual File for Each Controller

For printing complete projects with multiple controllers it is recommended to print


individual files for each controller because otherwise it would result in Word
documents that may exceed 1000 pages and file in excess of 40 Megabytes.

Procedure 1. In the Print documentation for Project… dialog box, check Individual File for
Each Controller.

Printing Modes
You can either print directly to a printer (Print button) or into a file (File Output… button).

Direct Print Procedure 1. Click the Print button in the Print Documentation for Project… dialog box.

RESULT: CARE generates a file called "PRINTOUT.RTF" in the CARE


directory. During file creation, the currently generated application
part from CARE is displayed in a status window (for example,
"Printing Action: Time Programs..."). The percentage of completion
is also displayed.

After finishing with the rtf. file creation, Word is started and you can
print the file.

File Output Procedure 1. Click the File Output... button in the Print Documentation for Project… dialog
box.

RESULT: The Save As dialog box displays.

EN2Z-0937GE51 R0518 594


CARE DOCUMENTATION

2. Enter a filename or select an existing file.

RESULT: CARE generates the file. During file creation, the currently
generated application part from CARE is displayed in a status
window (for example, "Printing Action: Time Programs..."). The
percentage of completion is also displayed.

3. Open the Word file and print it.

Select Print Options


Before printing, you have to decide which information you want to print.

After selecting Database/Print... the Print Documentation for Project… dialog box is
displayed with its various selection possibilities.

595 EN2Z-0937GE51 R0518


DOCUMENTATION CARE

Fig. 1 Print Documentation dialog box of XL 5000 project

Fig. 2 Print Documentation dialog box of BACnet project

Each selection checkbox is described in detail in the subsequent sections.

EN2Z-0937GE51 R0518 596


CARE DOCUMENTATION

Print Table of Contents

If this checkbox is marked, a table of contents is printed as the first chapter in the
documentation. The table of contents is a Word field and, therefore, it can be
automatically updated, if the page breaks change.

NOTE: Through the caredoc.ini file, the printout of the table of contents can be
adjusted to be printed without page numbers. To do so, find the section
[Table Of Contents] and set Page Numbers= NO.

The following Word operations can be used to work with the table of contents (refer
to the Word user manual for details).

Update Table of Contents 1. Click on the table of contents with the right mouse button
2. From the context menu, select Update Field.
3. From the dialog box, determine whether you want to update only the page
numbers or whether you want to create a new table of contents.
4. Click OK to perform operation.

Change Layout The layout of the table of contents may be changed (for example, to display
more/less levels of detail, display or remove page numbers, etc.).

1. Select the table of contents by clicking on it with the left mouse button.
2. Select Insert/Index and Tables.
3. In the subsequent dialog box, adjust the layout of the table of contents as you
like.
4. Click OK to accept your selections.
5. Word asks, if you want to replace the existing table of contents. Click YES.

RESULT: The existing table of contents is updated to the new format.

Project Data sheet

The project data sheet contains general information about the project. This
information has been entered in CARE upon creation of the project.

Example:

Project: PH Exhibition
Project Description: Air_Handling_Units_Sect5
Project Reference Number: 1273634
Client: Trade PH
Order Number: 213434534
Percent Discount: 0
Job Factor: 1.5
Project Engineer: B. McNeal
Date: 03.06.98
Project Default Engineering Unit: International
Project Subdirectory PH
Plant Schematic

If this checkbox is marked, the plant schematics are printed.

The printout of the plant schematics may be adjusted by clicking on the >> button,
which opens the Printing Format for Plant Schematics dialog box:

597 EN2Z-0937GE51 R0518


DOCUMENTATION CARE

Print Terminations

With User Address prints the plant schematic with the user addresses
assigned to each hardware point.

Without User Address prints the plant schematic without user


addresses.

Big Schematics

Divide automatically splits the schematic across multiple pages.

Fit to Page rescales the schematics so that they fit on one page.

The following is an example of a plant schematic printout without user addresses.

EN2Z-0937GE51 R0518 598


CARE DOCUMENTATION

The following is an example of a plant schematic printout with user addresses. User
addresses (and their descriptors, if available) are printed vertically next to the
corresponding input or output hardware point.

(Building West Outdoor Temp)


OaTemp1(AI_S)
(Supply Duct)
OaDmpr1(AO)

(Supply Duct)
DaFiltAlm(DI_NO)

(Air Heater)
HtgPump1(DO_NO)

(Air Heater)
HtgVlv1(AO)

(Air Cooler)
ClgPump(DO_NO)

(Air Cooler)
ClgVlv(AO)
(Supply Fan)
SaFanLo(DO_NO)
(Supply Fan)
SaFanStatus2(DI_NO)
(Supply Fan)
SaFanHi(DO_NO)
(Supply Duct)
DaTemp(AI_S)

RmTemp(AI_S)
(Meters in Cellar)
TotWater(TOT_S)
(Meters in Cellar)
TotCurrent(TOT_F)
Control Strategy Loops

If this checkbox is marked, the control strategy loops are printed.

The printout may be adjusted by clicking on the >> button, which opens the
Printing Format for Control Strategy Loops dialog box:

Printing Format

With Schematic prints the plant schematic. User addresses are only
printed for software points.

Without Schematic does not print the plant schematics, but only the
datapoints and their assigned user addresses.

Big Schematics

Divide automatically splits the control loop across multiple pages.

Fit to Page rescales the control loop so that it fits on one page.

599 EN2Z-0937GE51 R0518


DOCUMENTATION CARE

The following is an example of a control strategy printout with schematic. The


schematic is printed above the control strategy. User addresses (and their
descriptors, if available) are printed only for software points.

HONEYWELL PROJECT PRINTOUT


PRINTING DATE: 5/13/98 CONTROLLERNAME:M C05 PROJECT NAME: CARE_T2
PRINTING TIME: 4.4 PM6 CONTROLLER NO: 5 OS VERSION: 2.0
3.8.2.2.2 CONTROL STRATEGY SIMULATION

x f m _ 7 0 n

( 2 . 2 )

x f m _ 4 5 n

( 1 . 3 ) ( 2 . 3 )

V A V A V D V A V D F A V D
(XFM Internal User Address)
L02VA_OutdoorTemp

(XFM Internal User Address)


L02VX_wCalcRt

Reset_Alarm

max

Alarm_AirHandl

dummy

Filter_Alarm
___________________________________________________________________________________________________
Printout Tool Version No.: 2.01.99 Filename: C:/CARE/SIMPRINT/P2035TS1.RTF Page 31 of 61

The following is an example of a plant schematic printout with user addresses and
plant schematic. User addresses and type abbreviation (and their descriptors, if
available) are printed vertically next to the corresponding hardware or software
point.

EN2Z-0937GE51 R0518 600


CARE DOCUMENTATION

(Building West Outdoor Temp)


OaTemp1(AI_S)

(Supply Duct)
DaTemp(AI_S)

RmTemp(AI_S)
x f m _ 7 0 n

( 2 . 2 )

x f m _ 4 5 n

( 1 . 3 ) ( 2 . 3 )

V A V A V D V A V D F A V D
(XFM Internal User Address)
L02VA_OutdoorTemp

(XFM Internal User Address)


L02VX_wCalcRt

Reset_Alarm

max

Alarm_AirHandl

dummy

Filter_Alarm
See the Point Type Abbreviations appendix for point type abbreviations.

XFMs with Internal


User Addresses If a control strategy contains XFMs with internal user addresses, a table with the
internal user addresses is printed as part of the control strategy loop.

The following table contains: The XFM name, (submodule name), the XFM position,
the type of the internal user address, the name of the internal XFM default user
address, the name of the connected CARE user address and the CARE descriptor
for this user address.

Example:

Sub Position Type XFM Internal User CARE User Address CARE Descriptor
module Address
xfm_70n 2.2 VA L00VA_Aussentemp L02VA_OutdoorTemp XFM Internal User Address
VA L00VZ_SwAbTemp L02VZ_wRt XFM Internal User Address
VD L00VD_BetriebAnl L02VD_PlantRuns XFM Internal User Address
VA L00VA_XcTemp L02VA_SeqCntrl XFM Internal User Address
xfm_45n 2.3 VA L00VZ_FrgStufen L02VZ_FanDemand XFM Internal User Address
VD L00VZ_BelegOptim L02VZ_PlantOn XFM Internal User Address
VA L00VA_Aussentemp L02VA_OutdoorTemp XFM Internal User Address
VA L00VX_ErrSwRt L02VX_wCalcRt XFM Internal User Address
VD L00VS_Störung L02VS_Alarm XFM Internal User Address
VD STARTUP STARTUP
VD L00VD_BetriebAnl L02VD_PlantRuns XFM Internal User Address
VA L00VA_AutoAnlage L02VA_AutoPlant XFM Internal User Address
VD L00VD_FrgMikl L02VD_EnblDamp XFM Internal User Address
VD L00VD_FrgLh L02VD_EnblAH XFM Internal User Address
VD L00VD_FrgLkT L02VD_EnblACT XFM Internal User Address

Mathematical Functions If a control strategy contains mathematical functions and the printout of
mathematical functions is enabled, the functions are printed as part of the control
strategy (Refer also to Mathematical Functions section.

601 EN2Z-0937GE51 R0518


DOCUMENTATION CARE

Example:

Average = ("Temp_1"+"Temp_2"+"Temp_3")/3
Smooth = INRT["difference",128,1440m]
difference = "DelayedOutdoorTemp"-"CurrentOutdoorTemp"

Parameters If Parameters sorted by Usage is enabled, the parameters of each icon are printed
as part of the control strategy. Refer to Parameters Sorted by Usage section.

The Parameters of WIA/RIA icons are listed in a separate table as part of the
control strategy, if Parameters sorted by Usage or Sorted by Parameter is
enabled.

NOTE: The Math Icon internal parameters are not printed as part of the control
strategy.

Parameters are printed with the statement position and type, the description of the
parameter, the parameter value and engineering unit , the parameter file number,
the parameter index and the user address of the software point, which the
parameter is mapped to.

Example:

Position Type Description Value Eng./ User Parameter Parameter Point Mapping
Unit Value File Index onto:
2.1 SEQ Min value sequence 1 10.000 1 3 SW_Point_Test1
2.1 SEQ Max value sequence 1 100.000 1 5 SW_Point_Test2
2.1 SEQ Slope sequence 1 0.900 1 4 SW_Point_Test4
2.1 SEQ y-axis intersection sequence 1 10.000 1 1 SW_Point_Test3
2.1 SEQ Min value sequence 2 100.000 1 8 SW_Point_Test7
2.1 SEQ Max value sequence 2 10.000 1 9 SW_Point_Test6
2.1 SEQ Slope sequence 2 -0.900 1 2 SW_Point_Test5
2.1 SEQ y-axis intersection sequence 2 100.000 (Not
Generated)*
2.1 SEQ Min value sequence 3 100.000 (Not
Generated)*
2.1 SEQ Max value sequence 3 10.000 (Not
Generated)*
2.1 SEQ Slope sequence 3 -0.900 (Not
Generated)*
2.1 SEQ y-axis intersection sequence 3 100.000 (Not
Generated)*
2.1 SEQ Internal Parameter 10/12 100.000 (Not
Generated)*

NOTES:
1. *If optional parameters exist for a statement (such as for example input
parameters), and the user does not use these parameters, the printout
shows the entry "Not Generated". The printout of not generated parameters
can be suppressed by the caredoc.ini file.
2. Engineering units for parameters in the control strategy are only printed for
XFMs.

Switching Logic Tables

If this checkbox is marked, the switching tables are printed.

The printout may be adjusted by clicking on the >> button, which opens the
Printing Format for Switching Logic Tables dialog box:

EN2Z-0937GE51 R0518 602


CARE DOCUMENTATION

Print Terminations

With Schematic prints the plant schematic. The points that are
controlled by switching tables are marked with the number of the
switching table.

Without Schematic does not print the plant schematics, but only the
switching tables.

Big Schematics

Divide automatically splits the control loop across multiple pages.

Fit to Page rescales the control loop so that it fits on one page.

The following is an example of a switching table printout with schematic. Each


hardware point that is controlled by a switching table is marked with the number of
the switching table.

1 2

NOTE: The switching tables are headed with


— output point user address
— output point type abbreviation *)
— output point descriptor
— output value

Each user address shows type abbreviation and descriptor (if assigned) in
round brackets.

See the Point Type Abbreviations section for point type abbreviations

Examples:

Switching Table 1 : SaFanLo (DO_NO)(Supply Fan) = 1

603 EN2Z-0937GE51 R0518


DOCUMENTATION CARE

SaFanLo (DO_NO) 1 [9][3]


(Supply Fan)
Filter_Alarm (VD) 0

Switching Table 2 : SaFanHi (DO_NO)(Supply Fan) = 1

SaFanHi (DO_NO) 1 [10][3]


(Supply Fan)
Filter_Alarm (VD) 0

Switching Table 3 : Alarm_AirHandl (VD) = 1

Alarm_AirHandl (VD) Te = 10s [11][6] 1 [11][7]

DaTemp (AI_S) >= 1 *)


(Supply Duct)
38 [11][5] hysteresis

NOTE: The last column of the switching table is smaller for tables with XOR tables
than for tables without XOR tables.

Mathematical Functions If a switching table contains mathematical functions in a condition row and the
printout of mathematical functions is enabled, the functions are printed as part of
the switching tables (Refer also to Mathematical Functions section).

Example:

hysteresis = "DaTemp"*0.1

Parameters In switching tables, the parameter file number and index is displayed in square
brackets directly behind the corresponding parameter. The first value in brackets
represents the file number and the second value in brackets represents the
parameter index.

Example:

Alarm_AirHandl (VD) Te = 10s [11][6] 1 [11][7]

DaTemp (AI_S) >= 1


(Supply Duct)
38 [11][5] hysteresis

Te = 10s [11][6] means that the on delay value of 10 seconds is stored in


parameter file 11 in parameter number 6.

If Sorted by Parameter is enabled, the parameters of the complete controller are


printed in a separate table with description of the parameter usage.

NOTE: The Math equations internal parameters are not printed as part of the
switching tables.

Parameter List

If this checkbox is marked, the application parameters are printed.

NOTE: The Printout function supports the ANSI character set in the parameter list.

Parameter lists can be printed Sorted by Parameter and Sorted by Usage. The
selection can be made from a dropdown list box.

EN2Z-0937GE51 R0518 604


CARE DOCUMENTATION

Sorted by Parameter If this selection is made, the parameters are printed in a separate chapter and not
as part of each control strategy. Only those parameters that are available in the
controller are printed.

NOTE: Printout sorted by parameter requires translation of the controller in CARE


prior to the printout attempt, because during translation the <controller>.txt
file is created which is used as an input file for the parameter printout.

The parameter tables are sorted by parameter file number.

Examples:

Parameter table of the main module.


• The header contains the main module name and the parameter file number 0.
• The column P. No. contains the parameter number.
• The column Description contains the parameter description.
• The column Value + Eng. Unit contains the parameter value and engineering
unit (only for XFMs)
• The column Symbol Reference, Plant, Control Strategy contains the position and
the input number of the control icon that uses the parameter (for example 4 - 2.3
means this parameter is used for input number 4 of a control statement on the
position 2.3 [the second column and the third row of the corresponding control
strategy]), the plant reference and the control strategy name.

NOTE: User Value is an extra blank column. The startup technician can use it to
fill in the values he changes during plant startup.

605 EN2Z-0937GE51 R0518


DOCUMENTATION CARE

Main module Parameter file number


M0 0

P.No. Description Value + Eng.Unit User Value Symbol Reference, Plant, Control Strategy
1 Internal use 0.000
2 Internal use 1.000
3 Input 1 1.000 1- 2.2, STARTUP_5, STARTUP
4 Input 3 50.000 3- 2.2, XL20_5, AirConStrategy
5 Input 3 0.000 3- 2.3, XL20_5, AirConStrategy
6 Input 4 0.000 4- 2.3, XL20_5, AirConStrategy
7 Input 2 -50.000 2- 2.2, XL20_5, CoolerFan
8 Input 1 50.000 1- 2.2, XL20_5, HeaterDamper
9 Input 2 50.000 2- 2.2, XL20_5, HeaterDamper
10 Input 1 -50.000 1- 1.1, XL20_5, HeaterDamper
11 Input 3 -50.000 3- 1.1, XL20_5, HeaterDamper

Parameter table of a control strategy sub module.


• The header contains the plant name, the sub module name (only for XFMs), the
control loop name and the parameter file number.
• The column P. No. contains the parameter number.
• The column Description contains the parameter description.
• The column Value + Eng. Unit contains the parameter value and engineering
unit (only for XFMs).
• The column Symbol Reference contains the position and the input number of the
control icon that uses the parameter, for example 4 - 2.3 means this parameter
is used for input number 4 of a control statement on the position 2.3 (the 2nd
column and the 3rd row of the corresponding control strategy).
• The column Mapped SW Point contains the user address name of the software
point, which the parameter is mapped to.
NOTE: User Value is an extra blank column. The startup technician can use it to
fill in the values he changes during plant startup.

Plant Sub module Control loop Parameter file number


STARTUP xfm_90.csd STARTUP 1
P.No. Description Value + Eng.Unit User Value Symbol Reference Mapped SW Point
1 Delay Time 60.000 s 2.2 TestPoint_01
2 Version 1.000 I 2.2 TestPoint_06
3 XFM_Number 90.000 I 2.2 TestPoint_11

Parameter table of a switching table sub module.


• The header contains the plant name, the switching table name (name of the
switched point) and the parameter file number.
• The column P. No. contains the parameter number.
• The column Description contains the parameter description.
• The column Value + Eng. Unit contains the parameter value and engineering
unit (only for XFMs).
• The column Symbol Reference contains the line of the switching table that
contains the parameter, where 0 means the table header and 1 means the 1st
line.
NOTE: User Value is an extra blank column. The startup technician can use it to
fill in the values he changes during plant startup.

Plant Switching table Parameter file number


XL20_3 Alarm_AirHandl 11
P.No Description Value + Eng.Unit User Value Symbol Reference
.
1 Internal use 0.000
2 Internal use 1.000
3 Internal use 48.000 1
4 Hysteresis (MAT) Line 1 Table 1 0.100 1
5 Comparison Value 2 Line 1 Table 1 38.000 1
6 Comp. Value 2 (MAT) Line 2 Table 1 10.000 2
7 Output On-Delay Table 1 10.000 0
8 Output Value Table 1 1.000 0

EN2Z-0937GE51 R0518 606


CARE DOCUMENTATION

NOTE: Engineering units for parameters are only printed for XFMs.

Sorted by Usage If this selection is made, the parameters are printed as part of the control strategy to
which they belong.

NOTE: Parameters Sorted by Usage can only be selected, if control strategy or


switching table printout was selected previously.

For switching tables, the parameter file number and index is printed directly behind
the corresponding parameter, so that in this case no separate parameter table is
required.

Parameters are printed with the statement position and type, the description of the
parameter, the parameter value and engineering unit , the parameter file number,
the parameter index and the user address of the software point, which the
parameter is mapped to.

NOTE: There is an extra column User Value that is blank. The startup technician
can fill in the values he changes during plant startup.

Example:

Position Type Description Value Eng./ User Parameter Parameter Point Mapping
Unit Value File Index onto:
2.1 SEQ Min value sequence 1 10.000 1 3 SW_Point_Test1
2.1 SEQ Max value sequence 1 100.000 1 5 SW_Point_Test2
2.1 SEQ Slope sequence 1 0.900 1 4 SW_Point_Test4
2.1 SEQ y-axis intersection sequence 1 10.000 1 1 SW_Point_Test3
2.1 SEQ Min value sequence 2 100.000 1 8 SW_Point_Test7
2.1 SEQ Max value sequence 2 10.000 1 9 SW_Point_Test6
2.1 SEQ Slope sequence 2 -0.900 1 2 SW_Point_Test5
2.1 SEQ y-axis intersection sequence 2 100.000 (Not
Generated)*
2.1 SEQ Min value sequence 3 100.000 (Not
Generated)*
2.1 SEQ Max value sequence 3 10.000 (Not
Generated)*
2.1 SEQ Slope sequence 3 -0.900 (Not
Generated)*
2.1 SEQ y-axis intersection sequence 3 100.000 (Not
Generated)*
2.1 SEQ Internal Parameter 10/12 100.000 (Not
Generated)*

NOTES:
1. *If optional parameters exist for a statement (for example input parameters),
and the user does not use these parameters, the printout shows the entry
“Not Generated”.
2. Engineering units for parameters in the control strategy are only printed for
XFMs.
3. Parameters sorted by Usage does not print the parameters of
mathematical functions.

Parameters of WIA/RIA If Control Strategy is enabled, the parameters of WIA/RIA are printed as part of the
control strategy loop for each option, sorted by parameters or sorted by usage.

Icon Type Position Connected User Address Type Descriptor Attribute


WIA 1.1 L02VD_PlantRuns_5 VD 1: Operational Mode
2: Hide Point
3: No Response
RIA 1.2 L02VA_SeqCntrl_5 VA 1: Operational Mode
2: No Response
3: IO Remote

Plant to Controller

607 EN2Z-0937GE51 R0518


DOCUMENTATION CARE

If this checkbox is marked, the plants that are assigned to the selected controller
are printed as shown below.

The printed table contains:

• All plant names that belong to the specific controller


• The corresponding type (for example, Air Conditioning/Hot Water) for each plant
name
• All assigned control strategies for each plant

Example:

Plant name Plant Type Control Strategy Name


STARTUP Air Conditioning STARTUP
XL20_3 Air Conditioning AirConStrategy
CoolerFan
Plant Feedback
HeaterDamper

Mathematical Function

Mathematical functions can be found in control strategies and/or switching tables. If


there is not any mathematical function in control strategies and/or switching tables,
this checkbox cannot be enabled. In case of existing mathematical functions, they
are only printed, if Control Strategy Loops and/or Switching Logic Tables is
enabled.

Control Strategies If a control strategy contains mathematical functions and the printout of
mathematical functions and control strategy loops is enabled, the functions are
printed as part of the control strategy (Refer also to Control Strategy Loop section).

Example:

Average = ("Temp_1"+"Temp_2"+"Temp_3")/3
Smooth = INRT["difference",128,1440m]
Difference = "DelayedOutdoorTemp"-"CurrentOutdoorTemp"

Switching Tables If a switching table contains mathematical functions in a condition row and the
printout of mathematical functions and of switching tables is enabled, the functions
are printed as part of the switching tables (Refer also to Switching Logic Tables
section).
Example:

hysteresis = "DaTemp"*0.1

Controller Summary

If this checkbox is marked, a summary for each selected controller is printed. The
controller summary shows which module type is plugged into which housing. For
each I/O module, the technical address of the module is printed (refer to Terminal
Assignment Function).

Example:

EN2Z-0937GE51 R0518 608


CARE DOCUMENTATION

ÎP Housing 1 IP Housing 2

XP502 XF521 XF522 XC5010 XF523 XF524 ( Empty ) ( Empty )

No : 1 No : 2 No : 3 No : 4
Note: Number states technical address of module.

XF528 Housing 2

XF528(1) XF528(2) XF528(3) XF528(4) XF528(5)

No : 7 No : 8 No : 9 No : 10 No : 11
Note: Number states technical address of module.

LON Bus Housing 1

XFL523 XFL523 XFL523 XFL521 XFL522 XFL523 XFL524 → Slot 7-10


graphically
not presented
No : 7 No : 8 No : 9 No : 10 No : 11 No : 12 No : 13
Note: Number states technical address of module.

609 EN2Z-0937GE51 R0518


DOCUMENTATION CARE

Terminations

If this checkbox is marked, all terminations of the selected controller(s) are printed.

Example for standard module terminations:

Device/ Terminal Installation Cable Type Cable No. Wire Identification Housing Number 1
Module Number 5
Module Type XF521
 01 AC1MaTemp ( 22 / 5 / 1 )
 02 COM
 03 AC1OaTemp ( 22 / 5 / 2 )
 04 COM

 05 AC1RmTemp ( 22 / 5 / 3 )
 06 COM
Coding Pin  07
 08 AC1SolarHeat ( 22 / 5 / 4 )
 09 COM
 10
 11 COM
 12
 13 COM
 14
 15 COM
 16
 17 COM
 18 10 V

Example for LON module terminations:

Cable Type Cable No. Wire Identification Module Number 1


Module Type XFL521 on XSL513
PE 35
36 18
37 19 1 L22_MW_DischarTemp ( 22 / 1 / 1 )
38 20 2 L22_MW_Frosttemp ( 22 / 1 / 2 )
39 21 3 L22_MW_OaTemp ( 22 / 1 / 3 )
40 22 4 L22_MW_RoomTemp ( 22 / 1 / 4 )
41 23 5 L22_MW_SupplyTemp ( 22 / 1 / 5 )
42 24 6
43 25 7
44 26 8
45 27 9 10 V
46 28 10 10 V
47 29 11 10 V
48 30 12 10 V
49 31 13 10 V
50 32 14 10 V
51 33 15 10 V
52 34 16 10 V
17 10 V

System Ground
Auxiliary Termination Block used for:
Protection Earth

Example for Excel 50 terminations (screw terminals):

EN2Z-0937GE51 R0518 610


CARE DOCUMENTATION

Port A
Power 24Vac- 24Vac+
24VAC 1 2
Relay 24VAC 24VAC Datapoint Name Descriptor Field Device
outputs
DO1 3 4 do_fb_di_1 ( 2/ 4/ 1)
DO2 5 6 do_fb_di_1 ( 2/ 4/ 2)
DO3 7 8 do_fb_di_1 ( 2/ 4/ 3)
DO4 9 10 do_fb_di_2 ( 2/ 4/ 4)
DO5 11 12 do_fb_di_2 ( 2/ 4/ 5)
DO6 13 14 do_fb_di_2 ( 2/ 4/ 6)
Port B
Control Y COM 24VAC Datapoint Name Descriptor Field Device
Outputs
AO1 15 16 & 1 2
AO2 17 18 & 1 2
AO3 19 20 & 1 2
AO4 21 22 & 1 2
Contacts Y COM COM Datapoint Name Descriptor Field Device
Input (dry (powered
contact) contact)

DI1 23 32 24 do_fb_di_2 ( 2 / 3/ 1)
DI2 25 32 26 do_fb_di_1 ( 2 / 3/ 2)
DI3 27 32 28 do_fb_di_1 ( 2 / 3/ 3)
DI4 29 32 30 do_fb_di_1 ( 2 / 3/ 4)
Universal Y COM 24VAC or Datapoint Name Descriptor Field Device
Inputs URef
UI1 33 34 & 1* 2* (31**) do_fb_di_2 ( 2 / 1 / 1 )
UI2 35 36 & 1* 2* (31**) do_fb_di_2 ( 2 / 1 / 2 )
UI3 37 38 & 1* 2* (31**)
UI4 39 40 & 1* 2* (31**)
UI5 41 42 & 1* 2* (31**)
UI6 43 44 & 1* 2* (31**)
UI7 45 46 & 1* 2* (31**)
UI8 47 48 & 1* 2* (31**)
*Non NTC sensors means active sensor
**for DI on AI board

611 EN2Z-0937GE51 R0518


DOCUMENTATION CARE

Point Data

If this checkbox is enabled, an overview of the point data and the datapoint
description for all points are printed.

Overview If this checkbox is marked, the quantity of each module and the quantity of the
physical datapoints on the corresponding module are printed.

Example:

Quantity of Modules Quantity of Physical Data points


Quantity DI Modules (XF523) 5 Quantity Digital Inputs 49
Quantity DO Modules (XF524) 4 Quantity Analog Inputs 24
Quantity 3 Position Modules (XF525) 0 Quantity Analog Outputs 20
Quantity AI Modules (XF521) 3 Quantity 3 Position Outputs 0
Quantity AO Modules (XF522) 4 Quantity Totalizers (fast) 0
Quantity Fast AI Modules (XF526) 0 Quantity Totalizers (slow) 0
Quantity AO Modules (w/o switches) (XF527) 0 Quantity Digital Outputs (NO) 0
Quantity DO Modules (w/o switches) (XF529) 0 Quantity Digital Outputs (C/O) 17
Quantity High Density DI Modules (XF528) 0
Total IP-Bus Modules 16 Total Physical Datapoints 110

Quantity AI LON Modules (XFL521) 0 Quantity Pseudo Analog Points 0


Quantity DI LON Modules (XFL522) 0 Quantity Pseudo Digital Points 3
Quantity AO LON Modules (XFL524) 0 Total Pseudo Data Points 3
Quantity DO LON Modules (XFL523) 0
Total LON Modules 0 Quantity Global Analog Points 1
Quantity Global Digital Points 1
Total IO Modules 16 Total Global Points 2

Quantity Control Loops 0 Quantity DO_Feedback_DI Points* 0


Quantity PID Controllers 0 Quantity Multi_Stage_Points* 0
Country Code GERMANY Quantity Puls_2 Points* 0
Engineering Units International Total Special Points 0
Default File Set xl_1_5
Installation Normal Quantity Analog Flags 1
Power Supply XP 502 Quantity Digital Flags 1

NOTE: The subpoints of these special points are included in the quantity of physical datapoints.

Datapoint Description If this checkbox is marked, the datapoint description of the selected controller is
printed. The printout may be adjusted by clicking on the >> button.
If a project was selected for printout, clicking on the >> button opens the Controller
Selection dialog box to select controllers for printout.

EN2Z-0937GE51 R0518 612


CARE DOCUMENTATION

Highlight desired controller(s) you want to print datapoint description for and click
the User Addresses... button to open the User Address Selection dialog box for
the selected controllers.

If a single controller or attached plant was selected for printout, clicking on the >>
button opens the User Address Selection dialog box directly:

By default all user addresses are highlighted for printing. Deselect addresses you
do not want to print by clicking on with left mouse key, or reselect. Use Untag/Tag
button for (de)selection of all addresses.

In addition to the User Address Selection dialog box, the printing Format, Point
Type or Controllers can be selected.

With the Format radio buttons, the user can select Detailed or Short format for the
printout:

Detailed Format
The detailed format prints a table for each datapoint that contains all its attributes
and their values.

The user addresses for each selected point type are printed. Within each point
type, the user addresses are sorted by alphabetical order.

If no datapoint exists for a selected type, the corresponding chapter is not printed.

For flags the user address, the z-register file and index numbers are printed. If there
is no valid file and index number available, the flag is indicated as “not assigned.

Short Format
The short format prints no attributes of the datapoints. The printout is sorted by
alphabetical order.

Controllers…
After clicking on the Controllers... button, the user can switch to the Controller
Selection dialog box (only possible, if a project with multiple controllers has been
selected for printout).

Point Type…
After clicking on the Point Type… button the Point Type Selection dialog box is
displayed.

613 EN2Z-0937GE51 R0518


DOCUMENTATION CARE

In the Point Type Selection box, datapoints can be (de)selected by type (for
example all AIs, all DIs and/or all Multistage Global Digital points). Only selected
point types will be shown in the User Address Selection dialog box.

See Point Type Abbreviations section for a list of point type abbreviations.

Click OK to close the Point Type dialog box.

Clicking OK in the User Address Selection dialog box prints the following:

• User Address
• Descriptor
• Point Type Abbreviation
• Technical Address

Example: Datapoint Description (Short Format)

User Address Descriptor Point Technical


Type Address
DaTemp Supply Duct AI_S 1/ 1/ 1
OaTemp1 Building West Outdoor Temp AI_S 1/ 1/ 2
RmTemp AI_S 1/ 1/ 3
ClgVlv Air Cooler AO 1/ 2/ 1
HtgVlv1 Air Heater AO 1/ 2/ 2
OaDmpr1 Supply Duct AO 1/ 2/ 3
L02VA_AutoPlant XFM Internal User Address VA
L02VA_OutdoorTemp XFM Internal User Address VA
L02VA_SeqCntrl XFM Internal User Address VA
L02VA_SuplDemand XFM Internal User Address VA
L02VX_wCalcRt XFM Internal User Address VA
L02VZ_FanDemand XFM Internal User Address VA
L02VZ_wRt XFM Internal User Address VA
GA GA_I 0/ 0/ 0
DaFiltAlm Supply Duct DI_NO 1/ 3 / 12
SaFanStatus2 Supply Fan DI_NO 1/ 3 / 11
ClgPump Air Cooler DO_NO 1/ 4/ 1
HtgPump1 Air Heater DO_NO 1/ 4/ 2
SaFanHi Supply Fan DO_NO 1/ 4/ 5
SaFanLo Supply Fan DO_NO 1/ 4/ 4
Alarm_AirHandl VD
EXECUTING_STOPPED VD
Filter_Alarm VD
L02VD_EnblACT XFM Internal User Address VD
L02VD_EnblAH XFM Internal User Address VD
L02VD_EnblDamp XFM Internal User Address VD
L02VD_PlantRuns XFM Internal User Address VD
L02VS_Alarm XFM Internal User Address VD
L02VZ_Maintenance XFM Internal User Address VD

EN2Z-0937GE51 R0518 614


CARE DOCUMENTATION

User Address Descriptor Point Technical


Type Address
L02VZ_PlantOn XFM Internal User Address VD
ManOff VD
Reset_Alarm VD
SHUTDOWN VD
STARTUP VD
TotCurrent Meters in Cellar TOT_F 1/ 3/ 1
TotWater Meters in Cellar TOT_S
Dummy_yFO FA
Dummy_St3 FD
FD FD
ZERO FD

Example: Datapoint Description for Flags

L22FD_Release (unassigned)
L22FD_Temp (FileNo.: 5/IndexNo. 8)

Time Programs

If this checkbox is marked, the time programs of the selected controllers are
printed.

The printout may be adjusted by clicking on >> button.

If a project was selected for printout, clicking on the >> button opens a dialog box to
select controllers for printout.

From this dialog box, the Time Programs button opens the Time Program
Selection dialog box for the selected controllers.

If a single controller or attached plant was selected for printout, clicking on the >>
button opens the Time Program Selection dialog box directly:

615 EN2Z-0937GE51 R0518


DOCUMENTATION CARE

In the Time Program Selection dialog box, the user can make multiple selections:

• From the list of available time programs, the user can deselect time programs
from printing by clicking on already highlighted items with the left mouse button.
• With the Format radio buttons, the user can select Detailed or Short format for
the printout (see below).
• With the Controllers... button, the user can switch to the Controller Selection
dialog box (only possible, if a project with multiple controllers has been selected
for printout).

Detailed Format The detailed format prints a table with the following information for each time
program:

• A list of all points that are assigned to this time program with
– user address
– descriptor
– type of each point.

• A list of all daily programs that belong to the time program with
– daily program name
– switching time
– user address of the point that is switched
– descriptor of the point that is switched in round brackets behind the user
address
– value/status to which the point is commanded.
– optimized status for switching points.

• A list of the weekdays (Monday to Friday) with the corresponding daily programs
assigned to them.
• A list of public holidays with the corresponding daily programs assigned to them.

NOTE: The holiday program table is only printed, if there is a daily program
assigned to one of the holidays.

Short Format The short format prints a table with the following information for each time program:

• A list of all points that are assigned to this time program with
– user address
– descriptor
– type of each point.

• A list of all daily programs that belong to the time program with
– daily program name
– switching time
– user address of the point that is switched

EN2Z-0937GE51 R0518 616


CARE DOCUMENTATION

– descriptor of the point that is switched in round brackets behind the user
address
– value/status to which the point is commanded.
• A list of the weekdays (Monday to Friday) with the corresponding daily programs
assigned to them and for each daily program:
– switching time
– user address of the point that is switched
– descriptor of the point that is switched in round brackets behind the user
address
– value/status to which the point is commanded.
– optimized status for switching points.

• A list of public holidays with the corresponding daily programs assigned to them

NOTE: The holiday program table is only printed, if they have a daily program
assigned to one of the holidays

Example (weekly schedule in short format):

Weekday (Daily program Time User Address of Switching Point Value/State Optim
name)
Monday (everyday) 06:00 L02VZ_PlantOn ( XFM Internal User Address ) Occupied YES
22:00 L02VZ_PlantOn ( XFM Internal User Address ) Unoccupied YES
Tuesday (everyday) 06:00 L02VZ_PlantOn ( XFM Internal User Address ) Occupied NO
22:00 L02VZ_PlantOn ( XFM Internal User Address ) Unoccupied YES
Wednesday (everyday) 06:00 L02VZ_PlantOn ( XFM Internal User Address ) Occupied YES
22:00 L02VZ_PlantOn ( XFM Internal User Address ) Unoccupied YES
Thursday (everyday) 06:00 L02VZ_PlantOn ( XFM Internal User Address ) Occupied YES
22:00 L02VZ_PlantOn ( XFM Internal User Address ) Unoccupied YES
Friday (everyday) 06:00 L02VZ_PlantOn ( XFM Internal User Address ) Occupied YES
22:00 L02VZ_PlantOn ( XFM Internal User Address ) Unoccupied YES
Saturday (weekend) 00:00 L02VZ_PlantOn ( XFM Internal User Address ) Unoccupied YES
Sunday (weekend) 00:00 L02VZ_PlantOn ( XFM Internal User Address ) Unoccupied NO

NOTE: It is recommended that the time programs are printed in short format to
save paper.

Controllers… After clicking on the Controllers… button the Controller Selection dialog box is
displayed to select controllers for which the time programs will be printed.

Module Graphics

If this checkbox is enabled, standard and LON modules respectively are printed as
a graphic. The graphic shows which user address resides on which switch or lamp,
so that the operator can easily find datapoints on the controller. The printout may be
put in the cabinet for easy reference to the datapoints. Additionally, the setting of
the HEX address switch is displayed.

Module graphics can be printed with or without point descriptors. The printout of
modules with point descriptors consumes more space and therefore only two
modules are printed per page. The printout without point descriptors prints four
modules on the same page.

Click the >> button to select the format in the Printing Format for Module Graphics
dialog box.

617 EN2Z-0937GE51 R0518


DOCUMENTATION CARE

Example (standard module graphics without descriptors):

Module Graphics for Housing 1

S1 : Power Off S1 : ClgVlv


0
1
S1 Power On 0
1
S1 S2 : HtgVlv1
auto
S3 : OaDmpr1
0 S2
1
auto

0 S3
1
auto

0 S4
1
auto

0 S5
1
auto
L1 : ClgVlv L1 Executing
L2 : HtgVlv1 L2 Alarm
L1 L1 Net Supply L1 L3 : OaDmpr1 L1 L3 OI Transmit
L2 L2 L2
L3
L2 Watchdog L3 L3
L4 OI Receive
L3 Battery Operation L4
L5
L4
L5
L5 Bus Transmit
L6 L6 Bus Receive
XP 502 XF 521 A XF 522A XC 5010B

< Left side of housing 1 Right side of housing 1 >

Example (LON module graphics without descriptors):

Module Graphics for LON module No.: 1


POWER Lon Bus

L L L L L
1 2 3 4 5

XFL521

1 2 3 4 5 6 7 8 9 10 11 12

L22 MW DischarTemp ( 22 / 1 / 1
L22 MW Frosttemp ( 22 / 1 / 2 )
L22 MW OaTemp ( 22 / 1 / 3 )
L22 MW RoomTemp ( 22 / 1 / 4 )
L22 MW SupplyTemp ( 22 / 1 / 5 )

EN2Z-0937GE51 R0518 618


CARE DOCUMENTATION

Module Graphics for LON module No.: 2


POWER Lon Bus

L L L L L
1 2 3 4 5

XFL522

1 2 3 4 5 6 7 8 9 10 11 12

L22 ST EH Valve ( 22 / 2 / 1 )
L22 ST KL DistrAir ( 22 / 2 / 2 )
L22 ST KL Mixer ( 22 / 2 / 3 )
L22 ST KL SupplAir ( 22 / 2 / 4 )
L22 ST KÜ Valve ( 22 / 2 / 5 )

Example (Excel 50 Screw Terminals):

2:24 V AC 1:24 V AC (Common)


4:24 V AC 3:do_fb_di_1 ( 2 / 4 / 1 )
6:24 V AC 5:do_fb_di_1 ( 2 / 4 / 2 )
8:24 V AC 7:do_fb_di_1 ( 2 / 4 / 3 )
10:24 V AC 9:do_fb_di_2 ( 2 / 4 / 4 )
12:24 V AC 11:do_fb_di_2 ( 2 / 4 / 5 )
14:24 V AC 13:do_fb_di_2 ( 2 / 4 / 6 )

16:GND 15:
18:GND 17:
20:GND 19:
22:GND 21:
24:GND 23:do_fb_di_2 ( 2/ 3/ 1)
26:GND 25:do_fb_di_1 ( 2/ 3/ 2)
28:GND 27:do_fb_di_1 ( 2/ 3/ 3)
30:GND 29:do_fb_di_1 ( 2/ 3/ 4)
32:DI-Power 31:+10V Ref
34:GND 33:do_fb_di_2 ( 2/ 1/ 1)
36:GND 35:do_fb_di_2 ( 2/ 1/ 2)
38:GND 37:
40:GND 39:
42:GND 41:
44:GND 43:
46:GND 45:
48:GND 47:

619 EN2Z-0937GE51 R0518


DOCUMENTATION CARE

Module Labels

CARE allows you to print both standard and LON module labels for the module front
plates. These labels can be printed on self-adhesive stickers and put on the
modules to describe the individual I/Os.

The labels contain the input/output user address for each terminal. For labels with
switches, holes are marked. These holes can be cut out using a special cutting tool.
Alternatively, the individual user addresses can be cut from the sticker and can be
put on the front plate individually.

NOTES: It is possible that the user addresses are too long for a module label,
causing the module label text to look scrambled. In which case, you can
edit the printout file that contains the module labels before printing to the
self-adhesive stickers. For example, a smaller font can be used or the user
address can be abbreviated.

Module label printing for Excel 80/100 controllers is not available

Select the Module Labels checkbox to print module labels.

RESULT: All other options from the Print Documentation… dialog box are
disabled, because module labels require self-adhesive stickers to be
put in the printer.

Click >> button to open the Module Labels dialog box.

EN2Z-0937GE51 R0518 620


CARE DOCUMENTATION

Select the orientation (horizontal or vertical).

Select, if you want to print with or without descriptors.

Check Export to Microsoft Excel, and then check the options you want to be appear
in the Excel sheet.

Click OK to confirm.

621 EN2Z-0937GE51 R0518


DOCUMENTATION CARE

Example (Vertical standard module labels with descriptors):

ContrNo.:22 ModuleNo.:5 ContrNo.:22 ModuleNo.:6


1:AC1MaTemp 1:AC1ClgVlv

0V
2:AC1OaTemp S1
10V
auto
3:AC1RmTemp

2:AC1FloDmpr
4:AC1SolarHeat
0V
S2
10V
5:.........
auto

6:......... 3:AC1MaDmpr

0V
7:......... S3
10V
auto
8:.........

4:.........

0V
S4
10V
auto

5:.........

0V
S5
10V
auto

Example (Vertical LON module labels with descriptors):

ContrNo.:22 ContrNo.:22 ContrNo.:22


ModuleNo.:2 ModuleNo.:3 ModuleNo.:4

1:L22_ST_EH_Valve 1:L22_BM_ElectrMeter
text 44 ELECTRICITY_METER-OFFICEBUILDING
1:L22_SB_UP_Chiller
COOLING INDEX
2:L22_ST_KL_DistrAir 2:L22_BM_But_Climate
VENTILATIONPLANT-OFFICE VENTILATIONPLANT-OFFICE
2:L22_SB_UP_Heater
text 49
3:L22_ST_KL_Mixer 3:L22_BM_FireAlarm 3:L22_SB_Vent_DcAir
VENTILATIONPLANT-OFFICE VENTILATIONPLANT-OFFICE

4:L22_ST_KL_SupplAir 4:L22_SM_Frostwatch 4:L22_SB_Vent_SupAir


VENTILATIONPLANT-OFFICE VENTILATIONPLANT-OFFICE

5:L22_ST_KÜ_Valve 5:L22_SM_Smokedetect
text 45 VENTILATIONPLANT-OFFICE
5:.........

6:......... 6:L22_SM_UP_Heater
VENTILATIONPLANT-OFFICE
6:.........

7:......... 7:L22_SM_Vent_DcAir
VENTILATIONPLANT-OFFICE
7:.........

8:......... 8:L22_SM_Vent_SupAir
VENTILATIONPLANT-OFFICE
8:.........

9:L22_SM_Watch_Sp_Dc
VENTILATIONPLANT-OFFICE
9:.........

10:L22_BM_WaterMeter
WATERMETER-OFFICEBUILDING
10:.........

11:......... 11:.........

12:......... 12:.........

XFL522 XFL523 XFL524

NOTE: First print the module labels to a file, then put the self-adhesive paper for
the stickers into the printer and print them one by one.

EN2Z-0937GE51 R0518 622


CARE DOCUMENTATION

Example (Export to Microsoft Excel):

Honeywell Contr:11 Bus:2 Module:1 Honeywell Contr:11 Bus:2 Module:1 XF823A


XFR822A
1: AHU01_Warn_FiltOutAir / AHU01 Warning Outside Air Filter
1: 5HI75712SM2 / Spjæld kold kanal
2: AHU01_Alarm_HtgPu / AHU01 Alarm Heating Pump
2: 5HI75712SM4 / Spjæld varm kanal
3: AHU01_Alarm_Frost / AHU01 Alarm Freeze Protection
3: AHU01_Htg_Vlv / AHU01 Heating Valve
4: AHU01_Alarm_SaFan / AHU01 Alarm Supply Air Fan
4: AHU01_Clg_Vlv / AHU01 Cooling Valve
5: AHU01_Alarm_Rep_SaFan / AHU01 Supply Air Fan Repair Switch
5: AHU01_Hum_Vlv / AHU01 Humidifier Valve
6: AHU01_AlarmPD_SaFan / AHU01 Supply Air Fan Difference Pressure
6: AHU01_Econovent / AHU01 Control Econovent
7: AHU01_Feedb_SaFan / AHU01 Feedback Supply Air Fan
7: .........
8: AHU01_Count_Htg / AHU01 Energy meter
8: .........
9: .........

10: .........

11: .........

12: .........

Text Lists

If this checkbox is enabled, the text lists of the selected controllers are printed.

The different text lists can be selected in the Text List Selection dialog box by
clicking on the >> button.

Controller Specific Text Lists prints the text as they have been defined in the
miscellaneous editor.

Default Text Lists prints the texts that are stored in the EXCEL default files in the
PCBSTD directory.

For either choice, the following information may be printed:


• Descriptors
• Alarm Texts
• Analog Engineering Units

623 EN2Z-0937GE51 R0518


DOCUMENTATION CARE

• Digital Engineering Units


• I/O Characteristics
• Search Templates (for controller specific text lists only)

Reference List

If this checkbox is enabled, reference data of the selected controllers are printed.
Reference data include used XFMs per project, per controller and a user address
reference table that shows for each point in which plant, control strategy, switching
table and time program it is used.

NOTE: Printing a reference list can take time. “Don´t worry, be patient or print
separately”.

Clicking the >> button at the Reference List item opens the Reference Lists dialog
box where different reference lists can be selected.

XFMs per project This option is only available, if a project was selected in CARE for printing out.
Enabling this check box creates a table showing used XFMs with their names and
corresponding paths/filenames for the selected project.

Example:

XFMs used in this Project

XFM Name Path/Filename


ramp C:/CARE/XFM/ORIGINAL/ramp
enth C:/CARE/XFM/ORIGINAL/enth
gndda01a C:/CARE/XFM/ORIGINAL/gndda01a

XFMs per Controller Enabling this check box creates a table showing used XFMs with their names and
corresponding paths/filenames for the selected controller(s).

Example:

XFMs used in Controller BWMMI_MUKO

XFM Name Path/Filename


ramp C:/CARE/XFM/ORIGINAL/ramp
enth C:/CARE/XFM/ORIGINAL/enth
gndda01a C:/CARE/XFM/ORIGINAL/gndda01a

User Address Reference Enabling this check box creates a table showing the locations for each user
address in the corresponding plant, switching table, control strategy and time
program.
If a project was selected for printout, clicking on the >> button opens the Controller
Selection dialog box to select controllers for printout.

EN2Z-0937GE51 R0518 624


CARE DOCUMENTATION

Highlight desired controller(s) you want to print reference lists for and click the User
Addresses... button to open the User Address Selection dialog box for the
selected controllers.

If a single controller or attached plant was selected for printout, clicking on the >>
button opens the User Address Selection dialog box directly:

By default all user addresses are highlighted for printing. Deselect addresses you
do not want to print by clicking on with left mouse key, or reselect. Use Untag/Tag
button for (de)selection of all addresses.

Controllers…
After clicking on the Controllers... button, the user can switch to the Controller
Selection dialog box (only possible, if a project with multiple controllers has been
selected for printout).

Point Type…
After clicking on the Point Type… button the Point Type Selection dialog box is
displayed.

625 EN2Z-0937GE51 R0518


DOCUMENTATION CARE

In the Point Type Selection box, datapoints can be (de)selected by type (for
example all AIs, all DIs and/or all Multistage Global Digital points). Only selected
point types will be shown in the User Address Selection dialog box.

See Point Type Abbreviations section for a list of point type abbreviations.

Click OK to close Point Selection dialog box and click OK to close User Address
Selection dialog box.

Clicking OK in the Reference Lists dialog box prints the following for each selected
user address.

Example:

User Address ReferenceBWMMI_MUKO

User Address Plant Switching Table Control Strategy Time Programs


(Daily Programs)
Analog Input Points
AC1MaTemp AC1 klima
AC1OaTemp AC1 klima
L22_MW_DischarTemp OFFICE_BUILD_VENTILATSimulation Simulation Restaurant
(Monday)
L22_MW_Frosttemp OFFICE_BUILD_VENTILATSimulation Simulation Restaurant
(Monday)
L22_MW_OaTemp OFFICE_BUILD_VENTILATSimulation Simulation Restaurant
(Monday)
L22_MW_RoomTemp OFFICE_BUILD_VENTILATCascade_Temperature Caskade_Temperature Room_01
(workday)
OFFICE_BUILD_VENTILATL22_ST_EH_Valve L22_ST_EH_Valve
OFFICE_BUILD_VENTILATL22_SB_Vent_SupAir L22_SB_Vent_SupAir
L22_MW_SupplyTemp OFFICE_BUILD_VENTILATSimulation Simulation

Analog Output Points


AC1ClgVlv AC1 klima
AC1FloDmpr AC1 klima
AC1MaDmpr AC1 klima
L22_ST_EH_Valve OFFICE_BUILD_VENTILATCascade_Temperature Caskade_Temperature Room_01
(workday)
OFFICE_BUILD_VENTILATL22_ST_EH_Valve L22_ST_EH_Valve
OFFICE_BUILD_VENTILATL22_SB_UP_Heater L22_SB_UP_Heater
L22_ST_KL_DistrAir OFFICE_BUILD_VENTILATCascade_Temperature Caskade_Temperature Room_01
(workday)
OFFICE_BUILD_VENTILATL22_ST_KL_DistrAir L22_ST_KL_DistrAir
L22_ST_KL_Mixer OFFICE_BUILD_VENTILATCascade_Temperature Caskade_Temperature Room_01
(workday)
OFFICE_BUILD_VENTILATL22_ST_KL_Mixer L22_ST_KL_Mixer
L22_ST_KL_SupplAir OFFICE_BUILD_VENTILATCascade_Temperature Caskade_Temperature Room_01
(workday)
OFFICE_BUILD_VENTILATL22_ST_KL_SupplAir L22_ST_KL_SupplAir
L22_ST_KÜ_Valve OFFICE_BUILD_VENTILATCascade_Temperature Caskade_Temperature Room_01
(workday)
OFFICE_BUILD_VENTILATL22_ST_KÜ_Valve L22_ST_KÜ_Valve

EN2Z-0937GE51 R0518 626


CARE DOCUMENTATION

User Address Plant Switching Table Control Strategy Time Programs


(Daily Programs)
OFFICE_BUILD_VENTILATL22_SB_UP_Chiller L22_SB_UP_Chiller

LON Interface

If this checkbox is enabled, the LON interface information of the selected controllers
is printed. LON interface data may include

• Overview of the system and the channels


• Lists of network variables, network variables types, devices, and configuration
properties
• value conversion tables
• and LON bindings.

Clicking the >> button at the LON interface item opens the LON Interface dialog box
where LON Interface data can be selected.

System Overview Enabling this checkbox prints out a system overview of the project

Subsystem LON-Works

Subsystem
VW_H45_Kälte

Subsystem VW_H45_Kälte

627 EN2Z-0937GE51 R0518


DOCUMENTATION CARE

Subsystem Subsystem
Subsystem_ISP01 Subsystem_ISP02

Subsystem Subsystem_ISP01

Device
B742CP03
Subsystem Subsystem
Sch_ISP01 KM_ISP01 Neuron ID:000435144301

Device List Enabling this checkbox prints out a list of all devices of the project.

Device System Path Channel Neuron ID:


B742CP03 LON-Works.VW_H45_Kälte.Subsystem_ISP01 VW_H42 000435144301
XFL521 05 LON-Works.VW_H45_Kälte.Subsystem_ISP01.Sch_ISP01 VW_H42 00A116745501
KM LON-Works.VW_H45_Kälte.Subsystem_ISP01.KM_ISP01 VW_H42 000867564000
B742CP04 LON-Works.VW_H45_Kälte.Subsystem_ISP02 VW_H42 00A115561301
XFL523 14 LON-Works.VW_H45_Kälte.Subsystem_ISP02.Sch_ISP02_FU VW_H42 043B0C8F0100
XFL524 15 LON-Works.VW_H45_Kälte.Subsystem_ISP02.Sch_ISP02_FU VW_H42 046194DE0000
XFL524 16 LON-Works.VW_H45_Kälte.Subsystem_ISP02.Sch_ISP02_FU VW_H42 04BB9ADE0000
VLT 01 LON-Works.VW_H45_Kälte.Subsystem_ISP02.Sch_ISP02_FU VW_H42 046F5BE10000
VLT 02 LON-Works.VW_H45_Kälte.Subsystem_ISP02.Sch_ISP02_FU VW_H42 04CBA1D20000
XFL521 02 LON-Works.VW_H45_Kälte.Subsystem_ISP02.Sch_ISP02_Bestand VW_H42 00A122370801
XFL523 03 LON-Works.VW_H45_Kälte.Subsystem_ISP02.Sch_ISP02_Bestand VW_H42 047934F20000
XFL523 04 LON-Works.VW_H45_Kälte.Subsystem_ISP02.Sch_ISP02_Bestand VW_H42 04431DF30000
XFL524 05 LON-Works.VW_H45_Kälte.Subsystem_ISP02.Sch_ISP02_Bestand VW_H42 0445A7D40000
XFL524 06 LON-Works.VW_H45_Kälte.Subsystem_ISP02.Sch_ISP02_Bestand VW_H42 047F3B020100
XFL523 08 LON-Works.VW_H45_Kälte.Subsystem_ISP02.Sch_ISP02_Bestand VW_H42 042ABFAD0100
XFL523 09 LON-Works.VW_H45_Kälte.Subsystem_ISP02.Sch_ISP02_Bestand VW_H42 04F434F20000
XFL524 10 LON-Works.VW_H45_Kälte.Subsystem_ISP02.Sch_ISP02_Bestand VW_H42 04F2BAD30000
XFL524 11 LON-Works.VW_H45_Kälte.Subsystem_ISP02.Sch_ISP02_Bestand VW_H42 044195DE0000
XFL522 13 LON-Works.VW_H45_Kälte.Subsystem_ISP02.Sch_ISP02_Bestand VW_H42 04B8028F0100
XFL521 01 LON-Works.VW_H45_Kälte.Subsystem_ISP02.Sch_ISP02_Bestand VW_H42 00C049353301
XFL521 07 LON-Works.VW_H45_Kälte.Subsystem_ISP02.Sch_ISP02_Bestand VW_H42 000468181201
XFL521 12 LON-Works.VW_H45_Kälte.Subsystem_ISP02.Sch_ISP02_Bestand VW_H42 000468139901

EN2Z-0937GE51 R0518 628


CARE DOCUMENTATION

Channel Overview Enabling this checkbox prints out a graphical channel overview.

Channel VW_H42

Device Device Device


XFL523 14 XFL524 15 XFL524 16

629 EN2Z-0937GE51 R0518


DOCUMENTATION CARE

Device Device Device


VLT 02 XFL521 02 XFL523 03

Device Device Device


XFL524 05 XFL524 06 XFL523 08

Network Variable List Enabling this checkbox prints out all network variables of the controller.

NV name: nviRequest NV type: SYS_nviRequest Direction: input


Selfdoc String Config Class: <none>
failure detec x auth_config x priority_conf x service_type offline polled sync x ext_rec

List of Configuration Properties Enabling this checkbox prints out the configuration properties.

LON Object Open Loop Sensor 1

CP Name: UCPTSensorConfig NV type: 80000C050103040E_UCPT_1


Description
Selfdoc String Config Class: <none> Value 0..10 V with pullup

CP Name: UCPTSendOnDelta NV type: 80000C050103040E_UCPT_2


Description
Selfdoc String Config Class: <none> Value 2

CP Name: UCPTWireOffset NV type: 80000C050103040E_UCPT_3


Description
Selfdoc String Config Class: <none> Value 0

Lon bindings Enabling this checkbox prints out the Lon bindings.

Controller B742CP03 Device XFL521 05


Data point Value NV name: NV name: NV type: LON Object
conversion
KW42-01-MW44a nviKW42_01_MW05b1 nvoAiTemp[1] SNVT_temp_p Open Loop Sensor 2

EN2Z-0937GE51 R0518 630


CARE DOCUMENTATION

KW42.01-MW03 nviKW42_01_MW03 nvoAiTemp[2] SNVT_temp_p Open Loop Sensor 3


KW42-01-MW05 nviKW42_01_MW05 nvoAiTemp[3] SNVT_temp_p Open Loop Sensor 4
KW42-01-MW44b nviKW42_01_MW05b2 nvoAiTemp[4] SNVT_temp_p Open Loop Sensor 5
KW42-01-MW44c nviKW42_01_MW05b3 nvoAiTemp[5] SNVT_temp_p Open Loop Sensor 6
KW42-01-MW44d nviKW42_01_MW05b4 nvoAiTemp[6] SNVT_temp_p Open Loop Sensor 7
The subscripts in this table indicate multiple bindings of a data point.

Conversion Tables Enabling this checkbox prints out the definition of value conversion tables.

VCT Name: DI_TEST Direction: input NV type: SNVT_lev_percent


Description:
NV Value: DP Value:
= 1.00 1.00
>= 1.00 1.00
>= 4.00 8.00
>= 6.00 12.00
>= 8.00 24.00
>= 10.00 40.00
>= 20.00 80.00

Network Variable Type List Enabling this checkbox prints out a detailed description of the network variable
types.

NVT Name:: UNVT_ubyte Type: UNVT Basic Type: Integer


Detailed Description: Unsigned Short (8 bit)
Selfdoc NVT Index: 0 Internal NVT Index: 0 Eng. Unit:
System NVT: NO Size: 1 Hidden: NO
Initial Value: 0 Minimum Value: 0 Maximum Value: 254

OPS Interface

Network Variable Type List Enabling this checkbox prints out the interface of the OPS controller.

OPS data for Controller PM500_EZ

Subsystem Driver Name: MBUS OPS Ports Assignment: RS485(DBUSCU)


Initialization Block: 024,E,8,03,000000000,1

Subcontroller Name: 2WR5_231 Subcontroller Address: 231,1,0,0,0,0,0

User Address OPS Point Name:CntPnt_2WR5 Subpoint Address: 0,0,0,0,0


Value Format: Float(65) Scaling Factor: 1.000000 Scaling Offset: 0.000000
Scan Priority: 1 Access Mode: Readable, Writable

User Address OPS Point Name:Energy_St0_T0_____ Subpoint Address: x0C06,0,0,0,2


Value Format: Float(65) Scaling Factor: 1000.000000 Scaling Offset: 0.000000
Scan Priority: 1 Access Mode: Readable

User Address OPS Point Name:Power___ Subpoint Address: x0B2E,0,0,0,2


Value Format: Float(65) Scaling Factor: 1.000000 Scaling Offset: 0.000000
Scan Priority: 1 Access Mode: Readable

631 EN2Z-0937GE51 R0518


DOCUMENTATION CARE

Technical Information
CAREDOC.INI File Settings Each user has local or personal preferences regarding the kind of information he
wants to print. To satisfy these individual requirements, the CARE printout is
configurable via an INI file.

NOTE: The INI file for the printout is called "CAREDOC.INI" and is located in the
CARE directory.

Default Selections
As each user may require different information for the printout, the caredoc.ini file
allows one to specify the default selections, which are made when the printout main
dialog box is started. Default selections specify which checkboxes or radio buttons
are selected by default.

The default selections are adjustable via the entries in the [selections] section.

1. Open the CAREDOC.INI file.


2. Look for the [selections] section.
3. Change the items you want to select by default to YES. Change the items
you want to deselect by default to NO.
4. Save the CAREDOC.INI file.

The following checkboxes and radio buttons can be set as defaults:

[Selections]
Table of Contents=YES YES: selects table of contents
Project Datasheet=YES YES: selects project datasheet
Plant Schematics=YES YES: selects plant schematic
Control Strategy=YES YES: selects control strategies
Switching Logic=YES YES: selects switching logic tables
Parameter List=YES YES selects parameter list
Plant to Controller=YES YES: selects plant to controller table
Mathematical Functions=YES YES: selects mathematical functions
Controller Summary=YES YES: selects controller summary
Terminations=YES YES: selects terminations
Point Data=YES YES: selects point data
Default Datapoint Overview=YES YES: selects the default point data overview
Default Datapoint Description =YES YES: selects the default point data
Description
Overview=YES YES: selects the point data overview
(only valid, if Point Data is also selected)

Datapoint Description=YES YES: selects the point datapoint description


(only valid, if Point Data is also selected)
Time Programs=YES YES: selects the time programs
Module Labels=NO YES: selects module labels.
LON Module Labels Horizontal=NO YES: selects horizontal orientation
No: selects vertical orientation
Module Labels with descriptor=YES YES: selects module labels with
descriptor
NO: selects module labels without
descriptor
Module Graphics=YES YES: selects the module graphics
Module Graphics with Descriptor=NO YES: selects module graphics with
descriptor
NO: selects module graphics without
descriptor
Important
If module labels are selected, all other items are automatically deselected.
Text List=YES YES: selects text lists
XL10 Reports Detailed=YES YES: Select detailed XL10 reports
XL10 Reports Short=YES YES: Selects short format XL10 reports
ELink Reports=YES YES: Selects ELink mapping and
commissioning reports

EN2Z-0937GE51 R0518 632


CARE DOCUMENTATION

Important
The following settings are ignored, if Text List is not YES:

Default Text List=YES YES: Selects default text lists


Controller Specific Text List=YES YES: Selects controller specific text lists

Important
The following settings are ignored, if the Default Text List is not set to
YES:

Default Descriptors=YES YES: Selects the default descriptors


Default Alarms=YES YES: Selects the default alarm texts
Default Ana Eng Units=YES YES: Selects the default analog
engineering units
Default DEU Eng Units=YES YES: Selects the default digital engineering
units
Default IO Characteristic=YES YES: Selects the default I/O characteristics
Search Templates=YES YES: Selects the search templates

Important
The following settings are ignored, if the Controller Specific Text List is
not set to YES:

Contr Spec Descriptors=YES YES: Selects the controller specific


descriptors
Contr Spec Alarms=YES YES: Selects the controller specific alarms
Contr Spec Ana Eng Units=YES YES: Selects the controller specific analog
engineering units
Contr Spec DEU Eng Units=YES YES: Selects the controller specific digital
engineering units
Contr Spec IO Characteristic=YES YES: Selects the controller specific I/O
characteristics

Important
The following setting is ignored, if the Time Programs entry is not set to
YES:

Format Time Programs Detailed=YES YES: Selects detailed format for the time
program
NO: Selects short format for the time
program

Important
The following setting is ignored, if the Datapoint Description entry is not
set to YES:

Format User Addresses Detailed=YES YES: Selects detailed format for the
datapoint description.
NO: Selects short format for the datapoint
description

Important
The following settings are ignored, if the Plant Schematics entry is not set
to YES:

Format Plant Schematic with User Addresses=NO YES: Selects schematic with
user addresses
NO: Selects schematic with
plant graphic

Format Plant Schematic Divide=NO YES: Divides big schematics


and spreads them over several
pages
NO: Rescales schematics so
that they fit on one page

Important
The following settings are ignored, if the Control Strategy entry is not set
to YES:

633 EN2Z-0937GE51 R0518


DOCUMENTATION CARE

Format Control Strategy with Schematic=NO YES: Prints control strategies with
schematic
NO: Prints control strategies with
user addresses

Format Control Strategy Divide=NO YES: Divides big control strategies


and spreads them over several
pages
NO: Rescales control strategies so
that they fit on one page

Important
The following settings are ignored, if the Switching Logic entry is not set
to YES:

Format Switching Logic Tables with Schematic=NO YES: Prints a schematic for
the switching tables
NO: Prints only the switching
tables

Format Switching Logic Tables Divide=NO YES: Divides big schematics


and spreads them over
several pages
NO: Rescales schematics so
that they fit on one page

Important
The following settings are ignored, if the Datapoint Description entry is
not set to YES:

Pseudo Totalizers=YES YES: Prints the pseudo totalizers as part of


the datapoint description
Analog Input=YES YES: Prints the analog inputs as part of the
datapoint description
Analog Output=YES YES: Prints the analog outputs as part of the
datapoint description
Digital Input=YES YES: Prints the digital inputs as part of the
datapoint description
Digital Output=YES YES: Prints the digital outputs as part of the
datapoint description
Flag Analog=YES YES: Prints the analog flags as part of the
datapoint description
Flag Digital=YES YES: Prints the digital flags as part of the
datapoint description
Flex=YES YES: Prints the flexible points as part of the
datapoint description
Global Analog=YES YES: Prints the global analog points as part
of the datapoint description
Multistage Global Dig=YES YES: Prints the multistage global digital
points as part of the datapoint description
Global Digital=YES YES: Prints the global digital points as part
of the datapoint description
Pseudo Analog=YES YES: Prints the pseudo analog points as part
of the datapoint description
Pseudo Digital=YES YES: Prints the pseudo digital points as part
of the datapoint description
Multistage Pseudo Dig=YES YES: Prints the multistage pseudo digital
points as part of the datapoint description
Totalizer=YES YES: Prints the totalizers as part of the
datapoint description
Reflist Pseudo Totalizers=YES YES: Prints the pseudo totalizers as part of
the reference list
Reflist Analog Input=YES YES: Prints the analog inputs as part of the
reference list
Reflist Analog Output=YES YES: Prints the analog outputs as part of the
reference list
Reflist Digital Input=YES YES: Prints the digital inputs as part of the
reference list

EN2Z-0937GE51 R0518 634


CARE DOCUMENTATION

Reflist Digital Output=YES YES: Prints the digital outputs as part of the
reference list
Reflist Flag Analog=YES YES: Prints the analog flags as part of the
reference list
Reflist Flag Digital=YES YES: Prints the digital flags as part of the
reference list
Reflist Flex=YES YES: Prints the flexible points as part of the
reference list
Reflist Global Analog=YES YES: Prints the global analog points as part
of the reference list
Reflist Multistage Global Dig=YES YES: Prints the multistage global digital
points as part of the reference list
Reflist Global Digital=YES YES: Prints the global digital points as part
of the reference list
Reflist Pseudo Analog=YES YES: Prints the pseudo analog points as part
of the reference list
Reflist Pseudo Digital=YES YES: Prints the pseudo digital points as part
of the reference list
Reflist Multistage Pseudo Dig=YES YES: Prints the multistage pseudo digital
points as part of the reference list
Reflist Totalizer=YES YES: Prints the totalizers as part of the
reference list
Auto Exit CARE Doc=YES YES: Printout main dialog box is closed
automatically after successful printout
NO: Printout main dialog box remains open
until closed by user

Printing Order
As in most affiliates, customer documentation is provided in a standardized binder
with standardized chapters in which the order of specific chapters of the printout
can be adjusted individually.

The printing order is adjustable through entries in the "[printing order]" section and
other subsequent sections.

A figure defines the location of the corresponding chapter within the document:
• Datapoint Description=1 means that the datapoint description is the first
chapter to be printed after the table of contents.
• Datapoint Description=4 means that the datapoint description is the fourth
chapter to be printed after the table of contents.

NOTE: If NO is entered instead of a number, the corresponding chapter is never


printed, even though it might be selected.

1. Open the CAREDOC.INI file.


2. Look for the [printing order] section or subsequent order sections.
3. Change the printing order by changing the numbers.

NOTE: Make sure that no number is repeated and that no figure is missing in the
sequence. Otherwise an error message will occur during printout and the
default printing order will be used.

4. Save the CAREDOC.INI file.

Printing Order (“main chapter”) This section defines the order of the main chapters.

[Printing Order]
Controller Summary=1
Point Data Overview=2
Terminations=3
Plant To Controller=4
Time Programs=5
Datapoint Description=6
Module Labels=7
Plant Related Data=8
Parameter List=9

635 EN2Z-0937GE51 R0518


DOCUMENTATION CARE

E Link Long=10
Text List=11
XFMs per Controller=12
UAReferenc=13

Plant Printing Order This section defines the order within the plant related data.

[Plant Printing Order]


Plant Schematic=1
Control Strategy=2
Switching Logic=3
XL10 Short=4 NOTE: This entry has no specific function and is only used to
ensure compatibility to older versions
XL10 Long=5 NOTE: This entry has no specific function and is only used to
ensure compatibility to older versions

Control Strategy Printing Order This section defines the order within the control strategy related data.

[Control Strategy Printing Order]


Control Strategy=1
User Address=2
Mathematical Functions=3
Parameter List=4
WIA RIA=5

Switching Logic Printing Order This section defines the order within the switching logic related data.

[Switching Logic Printing Order]


Switching Logic=1
Mathematical Functions=2
Parameter List=3

Time Program Printing Order These sections define the order within the time programs’ related data. There are
separate sections for long and short formats.

[Time Program Short Printing Order]


Assigned Points=1
Daily Schedule=2
Weekly Schedule=3
Holiday Programs=4

[Time Program Long Printing Order]


Assigned Points=1
Daily Schedule=2
Weekly Schedule=3
Holiday Programs=4

Datapoint Description
Printing Order This section defines the order within the datapoint description and is valid for both
short and detailed formats.

[Datapoint Description Printing Order]


Analog Inputs=1
Analog Outputs=2
Pseudo Analog=3
Global Analog=4
Digital Inputs=5
Digital Outputs=6
Pseudo Digital=7
Multistage Pseudo Digital=8
Global Digital=9
Multistage Pseudo Digital=10
Totalizer=11
Pseudo Totalizer=12
Flex DO Feedback DI=13
Flex Pulse 2=14
Flex Multistage=15
Flag Analog=16
Flag Digital=17

EN2Z-0937GE51 R0518 636


CARE DOCUMENTATION

Text List Printing Order This section defines the order within the text lists for both controller related texts
and default texts.

[Text List Printing Order]


Descriptors=1
Alarm Text=2
Analog Engineering Units=3
Digital Engineering Units=4
IO Characteristic=5
Search Templates=6
Default Descriptors=7
Default Alarm Text=8
Default Analog Engineering Units=9
Default Digital Engineering Units=10
Default IO Characteristic=11

UARef List Order This section defines the order within the reference list.

[UARef List Order]

Analog Input=1
Analog Output=2
Digital Input Normally Open=3
Digital Input Normally Closed=4
Digital Output Switch=5
Digital Output Change=6
Mot=7
Pseudo Digital=8
Pseudo Analog=9
Global Analog=10
Global Digital=11
Pseudo Totalizer=12
Fast Totalizer=13
Slow Totalizer=14
Flag Analog=15
Flag Digital=16
Flex=17
Multistage Global Digital=18
Multistage Pseudo Digtial=19
Pseudo Puls=20

Print Table of Contents


The table of contents can be printed with or without page numbers. This can be
adjusted through an CAREDOC.INI file setting.

1. Open the CAREDOC.INI file.


2. Look for the [Table Of Contents] section.
3. If you want to print the table with page numbers, set Page Numbers= YES.
If you want to print the table without page numbers, set Page Numbers=
NO.
4. Save the CAREDOC.INI file.

Suppress "Not Generated" Parameters


When printing parameters sorted by usage, usually all parameters of all statements
are printed. However, some statements contain optional parameters that may or
may not be used by the CARE programmer. Those parameters that are optional
and are not used by the CARE programmer are marked with an entry Not
Generated in the printout (refer to chapter Parameters sorted by usage). These
parameters do not show up in the controller.

The INI file allows suppression of the printout of not generated parameters by a
special setting to reduce the paper consumption significantly.

637 EN2Z-0937GE51 R0518


DOCUMENTATION CARE

1. Open the CAREDOC.INI file.


2. Look for the [Parameters by Usage] section.
3. If you want to suppress the Not Generated parameters, set Suppress Not
Generated Parameters= YES.

If you want to print the Not Generated parameters, set Suppress Not
Generated Parameters= NO.
4.
5. Save the CAREDOC.INI file.

Printer Settings
The printer settings in the caredoc.ini file are automatically created and saved
according to the settings selected in the Print Setup dialog box. On the other hand,
the settings in the ini.file can be edited and these default the settings for the Print
Setup dialog box when restarting the printout.

The settings are automatically saved in the following section:

[Special Printer]
Driver=(retrieved from Print Setup or manually entered)
Device=(retrieved from Print Setup or manually entered)
Port=(retrieved from Print Setup or manually entered)
Default Printer= (0=specific printer, 1=default printer)
Paper Format=(DIN A4 or Letter or User defined)
UserDefinedPaperLength=(only valid when Paper format=User defined, value in
mm)
UserDefinedPaperWidth=(only valid when Paper format=User defined, value in mm)

EN2Z-0937GE51 R0518 638


CARE DOCUMENTATION

Point Type Abbreviations


To distinguish point types more exactly, a type abbreviation is included in some
parts of the printout:

• In the plant graphics in round brackets behind the user address


• In the switching tables in round brackets behind the user address
• In the datapoint description/short format in the point type field
• In the datapoint description detailed format in the point subtype field

The point type abbreviations are defined as follows:

Abbreviation Definition
DI_NO Digital Input (normally open)
DI_NC Digital Input
DO_NO Digital Output (NO)
DO_CO Digital Output (C/O)
AI_S Analog Input Slow
AI_F Analog Input Fast
AO Analog Output
3POS (MOT) 3 Position Output
VD Pseudo Digital
VA Pseudo Analog
VT Analog Input Fast
GD_I Global Digital Input
GD_O Global Digital Output
GA_I Global Analog Input
GA_O Global Analog Output
FA Flag Analog
FD Flag Digital
MS Multistage
P2 Pulse_2
DO_F_DI DO_Feedback_DI
TOT_F Fast Totalizer Point
TOT_S Slow Totalizer Point
MGD_I Multistage Global Digital Input
MGD_O Multistage Global Digital Output
MVD Multistage Pseudo Digital

639 EN2Z-0937GE51 R0518


DOCUMENTATION CARE

Frequently Asked Questions

Question 1 Sometimes, if I print a project or controller the “Parameter” chapter is not printed,
yet the corresponding Parameter Sorted by... checkbox has been enabled. Why is
this?

Answer The parameters can only be printed, if the <CPU name>.txt file exists in the CARE
directory. Translate the corresponding controller by selecting Controller/Translate
in CARE.

Question 2 The printout of parameters “sorted by usage” sometimes shows “not generated”
instead of the parameter filenumber/index. I do not understand this text. The
customer should not see such an entry. Can this be prevented?

Answer Some CARE icons provide the capability to enter a parameter value for an input.
You can either enter a parameter or connect the input to the output of another icon.
When connecting the input to another icon, the parameter is not used and the
CARE printout shows “not generated.” The printing of “not generated” parameters
can be suppressed by setting Suppress not generated parameters=Yes in the
caredoc.ini file.

Question 3 Sometimes when trying to print to a file, an existing destination file is overwritten
without warning. Can this be prevented?

Answer This happens only, if the filename is longer than 8 characters (an invalid DOS
filename). This problem will be solved in an upcoming release.

Question 4 When printing a reference list, the printing process seems to stop and one could
think, CARE seemed to be crashed.

Answer Printing reference lists takes a long time.

EN2Z-0937GE51 R0518 640


CARE

CONTROLLERS
EXCEL 800 / 600 / 500 / SMART / 100 / 80 / 50 CONTROLLERS
EXCEL 10 (ELINK, XLINK, AND VAV2) CONTROLLERS
EXCEL OLINK CONTROLLER
EXCEL OPS CONTROLLER
FALCON/EAGLE CONTROLLER

641 EN2Z-0937GE51 R0518


CARE

EN2Z-0937GE51 R0518 642


CARE EXCEL 800 / 600 / 500 / SMART / 100 / 80 / 50 CONTROLLERS

EXCEL 800 / 600 / 500 / SMART / 100 / 80 / 50 CONTROLLERS


The engineering process of the Excel 800 / 600 / 500 / Smart / 100 / 80 / 50
controllers in CARE XL-500 are as follows:

1. Create Project
2. Set Global CARE Options
3. Create Controller
4. Create Plant
5. Create Plant Schematic
6. Modify Datapoints
7. Assign Datapoints to Controller
8. Develop Control Strategy
9. Develop Switching Logic
10. Create Time Program
11. Design and Configure C-Bus
12. Startup Controller
13. Generate Documentation

For a brief introduction to these procedures, please refer to the Quick Tours
chapter.

For further information, please refer to the following chapters:

● PROJECT DEFINITION AND MANAGEMENT for detailed information on project


management
● SET GLOBAL CARE OPTIONS for setting default settings for the project and the
Excel 500 controller
● CONTROLLER DEFINITION, ATTACHMENT AND MANAGEMENT for detailed
information on controller management
● PLANT DEFINITION AND MANAGEMENT for detailed information on plant
management
● PLANT SCHEMATICS for detailed information of creation on plant schematics
● EDITORS chapter for detailed information on the assignment and editing of
datapoint attributes
● TERMINAL ASSIGNMENT FUNCTION chapter for detailed information on the
display and modification of controller hardware configurations
● CONTROL STRATEGY for detailed information on control strategy development
● SWITCHING LOGIC for detailed information on switching logic development
● TIME PROGRAM EDITOR for detailed information on time program creation
● DOCUMENTATION for detailed information on generating documentation
● LONWORKS NETWORK ENGINEERING chapter for detailed information on the
engineering process of LON controllers

643 EN2Z-0937GE51 R0518


EXCEL 800 / 600 / 500 / SMART / 100 / 80 / 50 CONTROLLERS CARE

EN2Z-0937GE51 R0518 644


CARE EXCEL 10 CONTROLLERS

EXCEL 10 CONTROLLERS

Q7752A2 Zone Manager Controller / ELink Controller


To provide communication between the EXCEL 5000 C-bus and an E-Bus
with Excel 10 Controllers an Excel 10 Zone Manager Controller is used as
interface.
To provide point mapping between the C-bus and the E-Bus, the Excel 10
Zone Manager Controller has the functionality of an Excel 100, except that
it has no physical points.

Excel 10 applications cover the Q7750A1xxx (1000-series) devices used


with VAV 1 (Standard VAV) applications and the 2000-series including the
Q7752A2xxx Zone Manager and its corresponding controllers such as VAV
2 and FCU.

The CARE process for Excel 10 applications is substantially different from


that for other Excel Controllers.

CARE 4.00.00 and higher can only be applied to the engineering of 2000-series
applications. The process is partly done in CARE and completed within the E-Vision
software tool.

Purpose Applications using the C- and E-Bus need to be done within CARE and the
E-Vision software tool. The CARE part is to define the C-Bus portions. This
includes the following:

• Restore (Mapping) plants


• Time schedules
• Control strategíes
• Switching tables
• Export to E-Vision

The E-Vision part includes the rest of the process like:

• Configuration
• Commissioning
• Check out
• Calibration

See the E-Vision User Guide 74-2588 for an overview of the use of both CARE and
E-Vision for 2000-series Excel 10 applications. The following sections describe the
CARE steps.

645 EN2Z-0937GE51 R0518


EXCEL 10 CONTROLLERS CARE

Step and Action CARE Window and Excel 10 Considerations


Menu Item Selections

1. Install a CARE version The E-Vision installation saves mapped point plant
lower than 3.00.00 and backups in the CARE directory.
E-Vision on your PC

2. Start CARE and create Main window: Unique is recommended.


an Excel 10-ZM project. Project, New ...

3. Restore Excel 10 Project window: The E-Vision installation saves mapped point plant
Mapped Point Plant Plant, Restore backups in the CARE directory. Type the name of the
Backup. target plant (use upper case characters), select the
For example: CVA1S. particular plant to restore based on the XL10 device type,
and select the Use plant backups radio button. Restore
all plants

EN2Z-0937GE51 R0518 646


CARE EXCEL 10 CONTROLLERS

4. Backup the Excel 10-ZM Main window: The project backup provides the restored plants for a
project Project, Backup ... CARE project since in CARE 4.00.00 a plant restore is
no longer possible

5. De-install current CARE


version and install
CARE version 4.00.00
or higher
6. Restore the Excel 10- Main window: The project restore provides the backupped plants of
ZM project Project, Restore ... CARE version lower than 3.00.00
7. Create new project Project window: The plants can be copied to the new project by the
Project, New ... Replicate function.
8. Create the Excel 10-ZM Project window: Use upper case characters for controller name. Set
Controller. Controller, New ... Controller Type equal to Elink. Choose Version 1.01 for
For example: ELINK1. Controller OS. The Power Supply and Installation Type
fields are gray because you do not define them for Excel
10-ZM Controllers. Select alarm files as E-VISION
(default file setting).
9. Create an Elink Plant. Project window: Use upper case characters for plant name. Set Plant
For example: ELNKPLT. Plant, New ... Type equal to Elink. Choose Version 1.01 for Controller
OS. This plant is used for control strategy and switching
logic.

10. Customize Excel 10 Points can be deleted Enter the Switching Logic screen and use the “Delete
Mapping Points in the using any of the CARE unused SW points” function to reduce the list to the
mapped plant (in this Delete Software Point desired mapped points. Use this plant as a template for
example, CVA1S). functions. replication. Plant must be replicated to create unique user
addresses in CARE.
11. Replicate Mapped Plant window: Replicate the Excel 10 plant as many times as the job
Plant (in this example, Plant, Replicate requires. The plant replicate operation prefixes the user
CVA1S). addresses in the plant with the target plant name,
ensuring uniqueness of user addresses in CARE. Note
that Excel 10 Controllers use some of the same user
addresses, for example, a VAV II and a CVAHU can both
use FAN_OUT. To make sure the user addresses are
unique, replicate the plants (VAV II or CVAHU) and attach
the replicated plants to the Excel 10-ZM Controller.
12. Attach Excel 10 Controller window: Select one or more plants to attach to the selected Excel
Mapping Plant (in this Controller, Edit, 10-ZM Controller. During the attach, CARE prompts you
example, CVA1S) to Attach/Detach Plants to delete unused software points. Select Cancel for each
Excel 10-ZM Controller. plant.
13. Customize Excel 10 Controller window: Points in mapping plants supplied with E-Vision come
Point Attributes in the Controller, Edit, Data preset with analog and digital engineering units.
mapped plant (in this Point Editor
example, CVA1S).

14. Attach Elink Plant (in Controller window: Select one or more plants to attach to the particular Zone
this example, Controller, Edit, Manager controller. During attach, software detects any
ELNKPLT) to Zone Attach/Detach Plants duplicate user addresses and prompts you to make them
Manager Controller (in unique.
this example, ELINK1).

647 EN2Z-0937GE51 R0518


EXCEL 10 CONTROLLERS CARE

15. Create Custom Control Plant window: Create control strategies only when confident that the
Strategy (if required). Plant, Control selection of mapped points is correct. Create all custom
In this example, in Strategy control strategies in a separate Elink plant, not directly in
ELNKPLT. the Excel 10 Mapping Plants. Create a new control loop
by selecting File, New, and specifying a name for the new
control loop. Place software points on the Zone Manager
controller software bar by selecting Edit, Load Existing
Software Points, selecting the appropriate point type,
and selecting the point of interest from the list box of
available points of the specified type. After you place a
software point on the software bar, it can be used in a
control strategy the same way as other software points.

Software points to be used as the source of a Command


Multiple Point relationship, or the destination of a Read
Multiple Points relationship, are also created in control
strategy by selecting a location on the software bar,
selecting the desired point type, and providing a user
address for the software point.
16. Create Custom Plant window: Create custom Switching Logic tables in a separate Elink
Switching Logic (if Plant, Switching Logic plant, not directly in the Excel 10 Mapping Plants.
required). Software points in the Excel 10-ZM Controller can then
In this example, in be used in a switching table by selecting Software
ELNKPLT. Points, selecting the point type of the desired point, and
selecting the point of interest from the list box of available
points of the specified type.
17. Create Custom Time Controller window or Specify Time programs to control the software points in
Programs (if required). attached plant window: the Excel 10-ZM Controller.
In this example, in Plant, Time Programs See the CARE Time Schedules section (Page 650) for
ELNKPLT. methods to create time schedules that control Excel 10s.
18. Translate Excel 10-ZM. Controller window or Translate generates the C-Bus controller files and
In this example, ELINK1. attached plant window: skeleton E-bus controller files that are later populated by
Controller, Translate E-Vision.
19. Export C-Bus Mapped Project, Export to E- Select the Excel 10-ZM project to export. The Export
Point Information from Vision Zone Manager dialog box displays. See the next section
CARE. for a description. Exported files have the extension .ZMX
and are stored in the CARE directory.

Mapped Point Plant Note The Excel 10 Mapped Point Plant Backup file is a predefined CARE plant
that contains standard point mappings. When E-Vision is installed, it places
one backup file for each Excel 10 controller type into the CARE directory.
Plants are named the same as the controller they represent with a PLT
extension, for example, FCU2S.PLT (Fan Coil unit) and CVA1E.PLT
(Constant volume AHU). Note that the 5th character is either S for
International System of Units (SI, also known as metric) or E for English
units of measurement.

In addition there are new “default” files required to work with these plants. These
default files are as follows:

• E-VISION.ADL
• E-VISION.ALX
• E-VISION.ID
• E-VISION.KDX
• E-VISION.KLX
• E-VISION.PHX

These default files are installed in C:\CARE\PCBSTD\El_1.1 by the E-Vision


installation program.

Plant Name Changes If a plant name is changed in CARE and reimported into E-Vision, E-Vision
cannot track this change and mapping errors will result in the plant to device
C-bus point mapping. If it is necessary to rename a plant in CARE,

EN2Z-0937GE51 R0518 648


CARE EXCEL 10 CONTROLLERS

manually unmap the plant in E-Vision from all relationships, then reimport
the modified CARE data. Complete the plant to device C-bus point mapping
as necessary.

Export Zone Manager File to E-Vision


Purpose Export all points from one or more Zone Managers to a user-defined file.
The information in this file is used to map between C-Bus points and E-Bus
points..

Procedure 1. Within CARE, open the Excel 10-ZM project. Select menu items
Project, Export to E-Vision.

RESULT: The Export Zone Manager dialog box appears. File


Directory displays the location of the export file; its default
is the location where CARE is installed.

2. Enter or select the desired file name for the controller in E-Vision. The Existing
Export box lists all ZMX files in the CARE directory. Name must be between 2
and 8 characters long and a valid DOS file name. File extension is .ZMX (for
Zone Manager Export). The Export button is disabled if the file name is invalid.

3. In the Project field, select the CARE project that has the Excel 10-ZM
Controller. Click the down arrow to view a list of projects.

RESULT: The Zone box lists all the Zone Managers within the
project. Note that any Zone Managers that have VAV 1
controllers (Standard) assigned to them in CARE are not
in this list. This omission means that you cannot create a
Zone Manager in CARE, assign VAV 1 Controllers to the
Zone Manager, and then also use E-Vision to assign
other devices to that same Zone Manager.

4. Select one or more desired Zone Managers. To select all, click Tag All. To
deselect all, click Untag All.

5. Click Export to perform the export. The Export button is enabled when a valid
file name is entered and one or more Zone Managers are selected.

RESULT: Software creates the desired export file. If one already


exists with the same name, a warning message appears.

Stand-alone Operation You can initiate Export Zone Manager outside of CARE by executing the
EXPEV.EXE file in the E-Vision directory.

649 EN2Z-0937GE51 R0518


EXCEL 10 CONTROLLERS CARE

CARE Time Schedules


There are two acceptable methods to create time schedules to control Excel 10s.
The first method is a Command Multiple relationship. The second method places
points from each mapping plant directly in a time schedule.

Command Multiple Mechanism


1. Always remove points to be used in a Command Multiple relationship from the
Mapping Plants. If a point is MAPPED, it cannot be used in a Command
Multiple relationship. For instance, if SchedOcc for the CVAHU is to be used in
a Command Multiple relationship, it must be deleted from the mapping plant.
Follow the CARE procedure outlined earlier in this section.
2. Use the Switching Logic mode to add a VD point. Match the number of states
and digital engineering units to the Excel 10 points to be controlled.
3. Place this point in a time schedule following the Time Schedule procedure
outlined in the CARE literature.
4. Translate and export to E-Vision.
5. Launch E-Vision. Create and configure the network.
6. Import from CARE.
7. Select Command Multiple from the Network menu.
8. Set up a Command Multiple relationship for the time schedule point..

Time Schedule Controlling


a Mapped Point Directly
1. DO NOT delete the point to be controlled by the time schedule from the
mapping plant.
2. Place this point directly in a time schedule. Multiple points can be placed in a
single time schedule. Follow the Time Schedule procedure outlined in the
CARE literature.
3. Translate and export to E-Vision.
4. Launch E-Vision. Create and configure the network.
5. Import from CARE.
6. Select Map C-Bus Points from the Network menu to verify that the point was
automapped.

CAUTION
A Command Multiple relationship can only be used for controllers of the
same type. For example, CVAHU and FCU controllers cannot be
commanded by the same time schedule point.

DO NOT create a time schedule point that controls a number of Excel 10


controllers from switching logic tables. The point DestSchedOcc is related to
other points. Tuncos and TodEventNext are automatically updated by the
time schedule program. The point DestSchedOcc must be controlled directly
from a time schedule or via a command multiple relationship in order for
Tuncos and TodEventNext to update correctly.

EN2Z-0937GE51 R0518 650


CARE EXCEL 10 CONTROLLERS

651 EN2Z-0937GE51 R0518


EXCEL 10 CONTROLLERS CARE

EXCEL LINK (XLINK) CONTROLLER


Purpose Process description of engineering an Excel Link (XLink) application. Excel
Link enables the connection of controllers on a Honeywell Control Network
Automation Protocol ("C-NAP' or "CNAP") bus to an EXCEL 5000 C-bus. C-
NAP bus controllers can include Excel MicroCel, Excel MacroCel, Excel
W7620, and W7600 Controllers.

Requirements You must be familiar with CARE software and either M-PPT software for
MicroCel/MacroCel Controllers or ZM 7601, 3, or 4 software for
W7620/W7600 Controllers.

Steps

Step 1 CARE configuration of Excel Link plant and subsystem plants


Step 2 Subsystem controller configuration
Step 3 Excel Link Configurator/Mapper
Step 4 Subsystem site backup
Step 5 Excel Link CPU and SSI download
Step 6 Subsystem controller download

Steps 1 through 4 are "off-line" procedures that you can do without the
controller. Steps 5 and 6 are "on-line" procedures that require the controller.
Excel Link Flowchart The following flowchart diagrams the necessary steps and sub steps.

EN2Z-0937GE51 R0518 652


CARE EXCEL 10 CONTROLLERS

STEP 1 CARE CONFIGURATION

Step 1A Build XLink Plant

Step 1B Build Subsystem Plants

Step 1C Replicate Subsystem Plants

Step 1D Attach All Plants

Step 1E Edit Miscellaneous Text

Step 1F Edit Data Points

Step 1G Edit Time Programs

Step 1H Translate XLink

Step 1I Print Documentation

Step 1J Back Up Project

STEP 2 SUBSYSTEM CONTROLLER CONFIG

Step 2A Configure XLink SSI


Step 2B Configure MicroCels/MacroCels

Step 2C Configure W7600s/W7620s

STEP 3 XLINK MAPPER

Step 3A
Map Plants (Automapping)
Step 3B
Map Points (Manual Mapping)
Step 3C
Map Engineering Units

Step 3D
Cross-check Mapping

STEP 4 SITE BACKUP

STEP 5 CPU & SSI DOWNLOAD

STEP 6 SUBSYSTEM DOWNLOAD

Step 1 CARE Configuration

Purpose Define an Excel Link plant and its schematic, control strategy, and switching
logic. Then, define subsystem plants (MicroCel/MacroCel, W7600, and/or
W7620) and their schematics. Control strategies and switching logic for the

653 EN2Z-0937GE51 R0518


EXCEL 10 CONTROLLERS CARE

subsystem plants are not necessary. Finally, complete the CARE process
through the documentation step and back up the completed project.
This section details the required CARE steps as follows:

Step 1A Build the Excel Link plant.


Step 1B Build the subsystem plants.
Step 1C Replicate the subsystem plants.
Step 1D Attach the plants to the Excel Link controller.
Step 1E Edit Excel Link descriptors, messages, engineering units, and
I/O characteristics in the Excel Link controller.
Step 1F Edit Excel Link points.
Step 1G Set up Time Programs in the Excel Link controller.
Step 1H Translate Excel Link controller.
Step 1I Print documentation.
Step 1J Back up project.

Step 1A Build the Excel Link Plant


Procedure The CARE process for Excel Link controllers is nearly the same as for other
C-bus controllers.
The following paragraphs detail the CARE process and note where there
are Excel Link options.

Project and Plant Definition Define a project as usual.

Define a plant as usual. Select XLINK as plant type. It may be useful to


name the plant to identify it as the Excel Link plant, for example, XLINK01.

This plant is optional and contains the "system" points to be mapped from
the C-bus to the C-NAP bus and vice versa. Typical mapping points are
outdoor air temperature, discharge air temperature, bypass, morning warm-
up, min/max/average space temperature, occupancy/nonoccupancy, and
restore/shed. Later, you manually map these points via the XLink
Configurator/Mapper.

Schematic Create a plant schematic by selecting segments that meet the point
requirements of the subsystem. These segments (listed by controller type)
have simple elements that represent the points you need to map to and
from the C-bus. Use the Point without graphic function if you need to map a
point not represented in the segment lists.

If there are global input points (for example, DaTemp, Warmup) in the Xlink
CPU that come from another C-bus controller, they cannot be directly
mapped to a C-NAP point. You must run them into IDT icons and out to a
pseudopoint. Then, map the pseudopoint to the C-NAP point.

Control Strategy If required, create a control strategy for the plant. Control strategy rules are
the same for Excel Link plants as they are for other plants. Control
sequences that cannot be accomplished in the subsystem controllers can
reside in this plant.

You cannot directly map global input points (for example, DaTemp,
Warmup) in the Xlink CPU that come from a C-bus controller to a C-NAP
point. You must input them to IDT icons and output them to a pseudopoint.
Then, map the pseudopoint to a C-NAP point.

EN2Z-0937GE51 R0518 654


CARE EXCEL 10 CONTROLLERS
Das verknüpfte Bild kann nicht angezeigt werden. Möglicherweise wurde die Datei verschoben, umbenannt oder gelöscht. Stellen Sie sicher, dass die Verknüpfung auf die korrekte Datei und den korrekten Speicherort zeigt.

Switching Logic If required, create switching logic for the plant. Switching logic rules are the
same for Excel Link plants as they are for other plants.

Step 1B Build the Subsystem Plants


Procedure The CARE process for subsystem controllers is similar to that for other C-
bus controllers. Note that control strategy and switching logic are not
required.
Project and Plant Definition Use the same project as set up for the Excel Link plant.

Define a new plant as usual. Name the plant the same as (or similar to) its
corresponding controller on the C-NAP bus. For example, name the plant
Rm102 for a C-NAP controller located in Room 102. To save time later,
make the plant and controller names identical. If the names are not
identical, you have to match each plant to its corresponding controller when
you use the Excel Link Configurator/Mapper.

• Plant name plus any point user addresses within the plant must not
exceed 18 characters. CARE truncates user addresses to 18
characters. The Replicator (Step 1C) combines each point user address
with its plant name to form a complete user address.

Select the appropriate plant type (W7620 VAV, W7620 WSHP,


MicroCel, or MacroCel). Use standard Air Conditioning or Chiller Water
plants for W7600 applications.

655 EN2Z-0937GE51 R0518


EXCEL 10 CONTROLLERS CARE

• Points generated in these plant schematics are associated with specific


C-NAP point numbers. If you use custom programs or modified
standard programs in a C-NAP controller, automapping (Step 3) may
not be accurate.

The following tables list the C-NAP point numbers associated with each
CARE element that is automapped in ZM5001. The CARE User Address
column lists default user addresses. You can modify these addresses in
CARE without affecting the automapping function.
Table 1.: MacroCel Automapping
Table 2.: MicroCel Automapping
Table 3.: W7620 Variable Air Volume (VAV) Automapping
Table 4.: W7620 Water Source Heat Pump (WSHP) Automapping

Schematic Create a plant schematic. Select segments that represent the equipment
the zone controller is handling. Excel Link can map a total of 768 points. Do
not exceed this number when building the schematics.
For W7620, MicroCel, and MacroCel controllers only, use the Optional
Points segment to add other points associated with the controller.

Use Modify user address under the Edit menu item to change default user
addresses, if needed. As noted in the Project and Plant Definition note, the
Replicator combines plant name and user addresses. The combination user
address must not exceed 18.

Use Point Without Graphic under the Edit menu item to add points not
represented by a standard segment.

Control Strategy Not required for W7600, W7620, MicroCel, and MacroCel plant types. The
subsystem controller is self-sufficient.

Switching Logic Not required for W7600, W7620, MicroCel, and MacroCel plant types. The
subsystem controller is self-sufficient. If you need to create pseudopoints
that are not covered in a schematic element, Switching Logic is a
convenient place to do so. Select Software Points, create the names, and
exit Switching Logic without saving the switching table.

TABLE 1: MACROCEL AUTOMAPPING

Segment Name CARE Schematic Element Name CARE User CNAP Pt.
Address No.
Dampers 1. Outdoor Air Modulating MaDmpr 22
2. Outdoor Air 2-Position MaDmpr 8
3. Outdoor Air Floating Series 60 MaDmpr 61

Coils-Pre Heat 1. Analog Modulating PrehtVlv 71


2. Analog Floating (series 60) PrehtVlv 71

Coils-Heating 1. Analog Modulating HtgVlv 71


2. Analog Floating (series 60) HtgVlv 71

Coils-Cooling 1. Analog Modulating ClgVlv 70


2. Analog Floating (series 60) ClgVlv 70

Supply Fan 1. Digital Status SaFanStatus 56


2. Variable Volume SaFanVane 23
2. Analog Sensor SaFanDiffPres 11

EN2Z-0937GE51 R0518 656


CARE EXCEL 10 CONTROLLERS

Segment Name CARE Schematic Element Name CARE User CNAP Pt.
Address No.
Return Fan 1. Digital Status RaFanStatus 58
2. Variable Volume RaFanVane 17
2. Analog Sensor RaFanDiffPres 40

Time-EMS 1. Standard Stop/Stop Schedules 1 SsSched1 95


2. Standard Stop/Stop Schedules 2 SsSched2 96
3. Unoccupied Override via Mark UnoccOvrd 32
Time
4. Unoccupied Override via PB UnoccOvrd 3
5. Night Cycle Control NightCycle 87

Filter-Return Air 1. Status/Alarm Contact RaFiltAlm 62


2. Differential Pressure Sensor RaFiltPres 37

Filter-Supply Air 1. Status/Alarm Contact SaFiltAlm 62


2. Differential Pressure Sensor SaFiltPres 37

Humidifier 1. Humidifier DaHumidVlv 19

Discharge Air Setpoints (SPTS) 1. Outdoor Air Reset High OaRstHi 75


2. Outdoor Air Reset Low OaRstLo 76
3. Reset Setpoint High DaRstHi 74
4. Reset Setpoint Base DaRstBase 73
5. Return Air Reset High RaRstHi 75
6. Return Air Reset Low RaRstLo 76
7. Discharge Reset Enable DaRstEn 77
8. Auto Setpoint DaTempAutoStpt 72
9. Manual Setpoint DaTempManStpt 73

Mixed Air Setpoints (SPTS) 1. Outside Air Reset High MaOaRstHi 66


2. Outside Air Reset Low MaOaRstLo 67
3. Reset Setpoint High MaRstHi 65
4. Reset Setpoint Base MaRstBase 64
5. Return Air Reset High MaRaRstHi 66
6. Return Air Reset Low RaMaRstLo 67

Temperature Sensors 1. Mixed Air MaTemp 49


2. Discharge Air DaTemp 50
3. Return Air RaTemp 55
4. Outside Air OaTemp 48
5. Space RmTemp 53
Humidity Sensors 1. Return Air RaRh 25
2. Discharge Air DaRh 14
3. Outside Air OaRh 31

Static Pressure Sensor 1. Discharge DaPres 11

657 EN2Z-0937GE51 R0518


EXCEL 10 CONTROLLERS CARE

Segment Name CARE Schematic Element Name CARE User CNAP Pt.
Address No.

CO2 Sensors 4. Return Air CO2 Sensor RaCo2 34

Safeties 1. Freezestat Alarm LoTempLim 38


2. Fire Stat or High Temp Status HiTempLim 26

TABLE 2: MICROCEL AUTOMAPPING

Segment Name CARE Schematic Element Name CARE User CNAP Pt.
Address No.
Single Duct Pressure 1. Flow Only DuctFlo 60
Independent
2. Setpoint Only DuctFloStpt 61
3. Flow + Setpoint DuctFlo 60
3. Flow + Setpoint DuctFloStpt 61

Single Duct Pressure 1. Flow Setpoint (Damper) DmprFlowStpt 61


Dependent

Dual Duct Pressure 1. Cold + Hot Duct Flow Only ClgDuctFlo 60


Independent
1. Cold + Hot Duct Flow Only HtgDuctFlo 69
2. Cold + Hot + Total Flow Only ClgDuctFlo 60
2. Cold + Hot + Total Flow Only HtgDuctFlo 69
2. Cold + Hot + Total Flow Only DuctFlo 59
3. Cold + Hot Duct Setpoint Only ClgDuctStpt 61
3. Cold + Hot Duct Setpoint Only HtgDuctStpt 70
4. 2 + 3 ClgDuctFlo 60
4. 2 + 3 HtgDuctFlo 69
4. 2 + 3 ClgDuctFloStpt 61
4. 2 + 3 HtgDuctFloStpt 70
4. 2 + 3 DuctFlo 59
5. Total Flow Only DuctFlo 59

Single Duct Damper Actuator 1. Position Only DuctDmprPos 62


2. Control Only DuctDmprCtrl 63
3. Position + Control DuctDmprPos 62
3. Position + Control DuctDmprCtrl 63

Dual Duct Damper Actuator 1. Position Only ClgDmprPos 62


1. Position Only HtgDmprPos 71
2. Control Only ClgDmprCtrl 63
2. Control Only HtgDmprCtrl 72
3. Position + Control ClgDmprCtrl 63
3. Position + Control HtgDmprCtrl 72
3. Position + Control ClgDmprPos 62
3. Position + Control HtgDmprPos 71

EN2Z-0937GE51 R0518 658


CARE EXCEL 10 CONTROLLERS

Segment Name CARE Schematic Element Name CARE User CNAP Pt.
Address No.

Terminal Fan - Series 1. Output By Point 8 TermFan 8


2. Output By Point 16 TermFan 16

Terminal Fan - Parallel 1. Output By Point 8 TermFan 8


2. Output By Point 16 TermFan 16

Terminal Heat - Electric 1. One Stage HtgStg1 9


2. Two Stages HtgStg1 9
2. Two Stages HtgStg2 16
3. Three Stages HtgStg1 9
3. Three Stages HtgStg2 16
3. Three Stages HtgStg3 17

Terminal Heat - Modulating 1. Position Only HtgVlvPos 70


2. Control Only HtgVlvCtrl 71
3. Position + Control HtgVlvCtrl 71
3. Position + Control HtgVlvPos 70

Room Temperature 1. Temperature Only RmTemp 49


2. Setpoint Only RmTempStpt 50
3. Temperature + Setpoint RmTemp 49
3. Temperature + Setpoint RmTempStpt 50

Miscellaneous - Flow Setpoints 1. Max Cooling Setpoint MaxClgStpt 64


2. Min Cooling Setpoint MinClgStpt 65
3. Reheat (Max) Heat Setpoint MaxHtgStpt 66
4. Min Heating Setpoint MinHtgStpt 67
5. Fan Flow Control Setpoint FanFloStpt 68

Miscellaneous - Temperature 1. Local Setpoint LocRmStpt 51


Setpoints
2. Remote Setpoint RmTempRemStpt 2
3. Occupied Cooling Setpoint OccClgStpt 51
4. Unoccupied Cooling Setpoint UnoccClgStpt 53
5. Occupied Heating Setpoint OccHtgStpt 52
6. Unoccupied Heating Setpoint UnoccHtgStpt 54

Miscellaneous - Energy 1. Cooling BTU ClgBtu 72


Monitoring
2. Heating BTU HtgBtu 73
3. Override Runtime (Cooling) ClgOvrdRunTime 74
4. Override Runtime (Heating) HtgOvrdRunTime 75
5. Percent Terminal Load PctTermLoad 94

659 EN2Z-0937GE51 R0518


EXCEL 10 CONTROLLERS CARE

Segment Name CARE Schematic Element Name CARE User CNAP Pt.
Address No.

Miscellaneous 1. Occupied Status OccStatus 55


2. Control Status HtgClgStatus 47
3. Override Max Duration OvrdMaxDur 57

TABLE 3.: W7620 VARIABLE AIR VOLUME (VAV) AUTOMAPPING

Segment Name CARE Schematic Element CARE User CNAP Pt.


Name Address No.
Single Duct Pressure 1. Flow Only DuctFlo 61
Independent
2. Setpoint Only DuctFloStpt 62
3. Flow and Setpoint DuctFlo 61
3. Flow and Setpoint DuctFloStpt 62

Dual Duct Pressure Independent 1. Cold + Hot Deck Flow Only ClgDuctFlo 61
1. Cold + Hot Deck Flow Only HtgDuctFlo 65
2. Cold + Hot Deck + Total Flow ClgDuctFlo 61
Only
2. Cold + Hot Deck + Total Flow HtgDuctFlo 65
Only
2. Cold + Hot Deck + Total Flow DuctFlo 60
Only
3. Cold + Hot Deck Setpoint Only ClgDuctStpt 62
3. Cold + Hot Deck Setpoint Only HtgDuctStpt 66
4. 2 And 3 ClgDuctFlo 61
4. 2 And 3 HtgDuctFlo 65
4. 2 And 3 ClgDuctFloStpt 62
4. 2 And 3 HtgDuctFloStpt 66
4. 2 And 3 DuctFlo 60

Single Duct-Damper Actuator 1. Position Only DuctDmprPos 63


2. Control Only DuctDmprCtrl 64
3. Position And Control DuctDmprPos 63
3. Position And Control DuctDmprCtrl 64

Dual Duct-Damper Actuator 1. Position Only ClgDmprPos 63


1. Position Only HtgDmprPos 67
2. Control Only ClgDmprCtrl 64
2. Control Only HtgDmprCtrl 68
3. Position + Control ClgDmprCtrl 64
3. Position + Control HtgDmprCtrl 68
3. Position + Control ClgDmprPos 63
3. Position + Control HtgDmprPos 67

EN2Z-0937GE51 R0518 660


CARE EXCEL 10 CONTROLLERS

Segment Name CARE Schematic Element CARE User CNAP Pt.


Name Address No.
Terminal Fan-Series 1. Program S1 TermFan 9
2. Program S2 TermFan 8
3. Program S3 TermFan 18
4. Program S4 TermFan 7

Terminal Fan-Parallel 1. Program S1 TermFan 9


2. Program S2 TermFan 8
3. Program S3 TermFan 18
4. Program S4 TermFan 7

Terminal Heat-Electric 1. One Stage HtgStg1 8


2. Two Stages HtgStg1 8
2. Two Stages HtgStg2 16
3. Three Stages HtgStg1 8
3. Three Stages HtgStg2 16
3. Three Stages HtgStg3 17

Terminal Heat-Modulating 1. Position Only HtgVlv 67


2. Control Only HtgVlvCtrl 68
3. Position + Control HtgVlvCtrl 68
3. Position + Control HtgVlv 67

Space Sensor 1. Temperature Only RmTemp 1


2. Setpoint Only RmTempStpt 50
3. Temperature + Setpoint RmTemp 1
3. Temperature + Setpoint RmTempStpt 50

Optional-Flow Setpoints 1. Maximum Cooling Setpoint MaxClgFloStpt 71


2. Minimum Cooling Setpoint MinClgFloStpt 72
3. Maximum Reheat Setpoint MaxRhtFloStpt 73
4. Minimum Reheat Setpoint MinRhtFloStpt 74

Optional-Temperature Setpoints 1. Local Temp Setpoint LocTempStpt 50


2. Remote Temp Setpoint RemTempStpt 2
3. Occupied Heating Setpoint OccHtgStpt 52
4. Unoccupied Heating Setpoint UnoccHtgStpt 54
5. Unoccupied Cooling Setpoint UnoccClgStpt 53
6. Occupied Cooling Setpoint OccClgStpt 51

Optional-Miscellaneous 1. Heating/Cooling Mode HtgClgMode 47


2. Occupied Status OccStatus 56
3. Terminal Load TermLoad 59

TABLE 4.: W7620 WSHP AUTOMAPPING

661 EN2Z-0937GE51 R0518


EXCEL 10 CONTROLLERS CARE

Segment Name CARE Schematic Element CARE User CNAP Pt.


Name Address No.
Water Coil 1. Water Coil HtgClgMode 47
1. Water Coil StagesOn 96

Zone Coil 1. Fan Start/Stop DO #6 HtgPumpFan 6


2. Fan Start/Stop DO #16 HtgPumpFan16 16

Space Sensor 1. Temperature Only RmTemp 1


2. Setpoint Only RmTempStpt 50
3. Temperature + Setpoint RmTemp 1
3. Temperature + Setpoint RmTempStpt 50

Optional Points 1. Resistive Input A RstrInptA 10


2. Voltage Input A VoltInA 11
3. Digital Input A DigInA 12
4. Resistive Input B RstrInptB 13
5. Voltage Input B VoltInB 14
6. Digital Input B DigInB 15
7. Remote Temp Setpoint RmtRmStpt 2
8. Occupied Clg Setpoint OccClgStpt 51
9. UnOccupied Clg Setpoint UnoccClgStpt 53
A. Occupied Htg Setpoint OccHtgStpt 52
B. UnOccupied Htg Setpoint UnoccHtgStpt 54
C. Setpoint Select StptSelect 48

Step 1C Replicate the Subsystem Plants


Purpose To easily create more subsystem plants, duplicate the ones you created
Step 1B. This step is optional; use if convenient.

Procedure For more details and examples of the replication process, please refer to
the "Replicate Plants" section

Step 1D Attach the Plants to the Excel Link Controller


Purpose Attach the Excel Link plant and the replicated plants to the Excel Link
controller.

When creating a plant it is automatically attached to the selected controller. When


replicating attached plants they will be automatically detached and must be re-
attached afterwards. To create unattached plants in the beginning, the project,
instead of the controller must be selected. Plants can be detached or re-attached by
simply dragging&dropping them to the desired destination (controller, project)

Procedure 1. To attach a plant, click on the unattached plant in the logical plant tree,

2. Drag the unattached plant to the controller, which you want attach the plant to,
and drop it.

RESULT: The Plant will be added one level below the controller in the
logical plant tree.

Software creates links between the Excel Link plant and the
subsystem plants.

EN2Z-0937GE51 R0518 662


CARE EXCEL 10 CONTROLLERS

For detailed information on attaching/detaching plants, see "Attach/Detach Plant"


section.

Step 1E Edit Excel Link Point Characteristics


Purpose Customize point descriptors, alarm messages, engineering units, and I/O
characteristics as desired.

Procedure See "Miscellaneous Text Editor" section.

I/O Characteristics Make sure there are linear I/O characteristics that cover the types of ranges
that can occur for each analog input and analog output point to be attached
to the Excel Link controller. If you have VAV boxes, you need to create a
characteristic with a span which covers the CFM range of your job.

Step 1F Edit Excel Link Points


Purpose Customize point attributesas desired.
Procedure see "Datapoint Editor" section for details.

Alarm Delays All CARE points that are mapped to a C-NAP alarming point must have the
CARE ´Alarm Delay` attribute set to ZERO seconds. This rule applies to
digital alarm points and analog input points with high and low limits. The
Excel Link SSI controller has an inherent unprogrammable alarm delay of
approximately 1 to 120 seconds, depending on the size of the application
and when the alarm point was last read by the SSI. Digital points for status,
not alarm, can have a time delay as usual.

Engineering Units All points require an engineering unit. You can set up bus-to-bus
engineering unit conversion in Step 3C. For example, a point can read in
degrees Fahrenheit on the C-NAP bus and in degrees Celsius on the C-
bus.
I/O Characteristic Choose an I/O characteristic that has a span that covers the range of the C-
NAP point.

Alarm Delay If a point will be generating an alarm, the delay time MUST be set to zero.

Other Point Attributes All other point attributes, for example, trending, runtime, descriptors, alarm
limits, apply to Excel Link points in the same way as C-bus points.

Step 1G Set Up Time Prog in Excel Link Controller


Purpose Set up scheduling functions as desired.

Procedure See "Time Program Editor" section for details.

NOTE Set up Time Programs just as you would for non-Excel Link plants. Time
Programs for the central air handling unit plant(s) that serve the
subsystem controllers attached to the Excel Link plant must reside here
(if you are using SSI TOD Programs). The C-NAP subsystem controllers
need the occupancy/nonoccupancy points associated with these Time
Programs.

IMPORTANT
The SSI TOD program assumes its CARE schedule point's active state
represents occupied mode whether the active state attribute is 1 or 0. This
assumption cannot be changed.

For the CARE schedule point, assign CARE engineering unit 17


(Occupied/active, Unoccupied/passive). It is recommended to set the
CARE schedule point's active state to 1 to correctly match the C-NAP NFO
point and set up these values: Occ=1=Active=On and
Unocc=0=Passive=Off.

663 EN2Z-0937GE51 R0518


EXCEL 10 CONTROLLERS CARE

Step 1H Translate Excel Link Controller


Purpose Convert the plants to code.
Procedure See "Translate Controller" in "Quick Tours" section.

Step 1I Print Documentation


See "Documentation" section for details on documentation in general.

Step 1J Back Up Excel Link Project


Purpose Copy ("back up") project to disk to save it before proceeding to the next
step.

This step is not required, but is recommended.

See "File Management" section for procedure.

IMPORTANT
If you make CARE and ZM7604 backups to be restored together later,
make sure they are backed up together. If you back up one and then make
changes to the other and back it up, the Excel Link may produce numerous
alarms during start-up.

Step 2 Subsystem Controller Configuration

Purpose Set up the files for the subsystem controllers. Depending on controller
types, there are two or three steps to do this with Step 2A required in all
cases:

Step 2A Subsystem Interface Setup


Set up the Excel Link controller subsystem interface (SSI). This step is
required no matter which subsystem controllers are on the C-NAP bus.
Step 2B MicroCel/MacroCel Controller Setup
If there are MicroCel/MacroCel controllers on the C-NAP bus, do "MPPT"
application programming, configuration, and loading.

Step 2C W7620 Controller Setup


If there are W7600 or W7620 controllers on the C-NAP bus, set up the files
for these controllers.

Requirement The starting point for each step is the Excel Link controller, that is, first
select the Excel Link controller in the logical plant tree.

Step 2A Subsystem Interface Setup


Purpose Set up the Excel Link controller (SSI) for the interface to the subsystem
controllers. This step is required no matter which subsystem controllers are
on the C-NAP bus. See ZM7604 Excel Link SSI CNAP Configurator and
ZM5001 CNAP Configurator User's Guide 74-5588 for more information.

Procedure 1. Select the Excel Link controller in the logical plant tree. Click the
Controller menu item, then drop-down items Tools, Xlink ZM 7604
Configuration.

RESULT: The main menu displays.

2. Select Configure, then drop-down item Site.

3. Enter a new site name, for example, XLink01. A site corresponds to one C-NAP
bus.

Rules: Project name must be exactly the same as the project


name in CARE.

EN2Z-0937GE51 R0518 664


CARE EXCEL 10 CONTROLLERS

Site Name can be the same as the Excel Link controller


name in CARE to clarify the relationship.

4. Select menu item Configure, then drop-down item System. This information
applies only to the PC software, not the controllers. Change if necessary.

5. Select menu item Configure, then drop-down item Communications. Click the
appropriate communication port. This setting is for downloading (writing) to the
Excel Link controller.

6. Select menu item File, then drop-down item Open Site. Select the Excel Link
site.

7. Select menu item Configure, then drop-down item Controller. Select New
Controller. Type equal to XLink.

The Excel Link controller name can be the same as the site name.

Type the C-NAP Network Number (same as C-bus node number), range is 1-
30. C-NAP Node Number range is 1-3. Always use 1 because the Excel Link
must be the C-NAP master. These settings must match the DIP switches on the
SSI hardware.

Program the Global Assignments for points such as outdoor air temperature,
discharge air temperature, bypass, morning warm-up,
occupancy/nonoccupancy, and restore/shed. There are defaults for these
points. Modify them, as necessary.

CAUTION
If you are going to program global points in M-Cel Point Programming
(MPPT, Step 2B), be aware that they use the same global point numbers as
listed in the SSI. There will be a conflict if you configure a global point
function in MPPT that uses a number already being used for a different
function in the SSI.

8. At this point, configure the subsystem controllers as described in "Step 2B


MicroCel/MacroCel Controller Setup" and "2C". Then, return to this procedure
and complete Steps 9 through 12.

9. Select menu item Configure, then drop-down item Controller Groups. Group
controllers in a logical manner, for example, by AHU or zone.

10. If desired, select menu item Configure, then drop-down item Point Groups.
This step is optional. You can use point groups to view one group of points by
selecting only one point, using the ZM7604 software on-line.

11. Select menu item Configure, then drop-down item Controller. Select XLink. In
the Command Center, set up Alarm Conditions as usual for C-NAP. Use this
window to configure unmapped point alarms to show up as critical alarms on
the C-bus. Otherwise, unmapped point alarms show up as noncritical on the C-
bus. See ZM7604 Excel Link SSI CNAP Configurator and ZM5001 CNAP
Configurator User's Guide 74-5588 for more details.

Alarm messages operate as follows:

Only the present value of a subsystem (C-NAP) point transfers across the Excel
Link to the C-bus. You program all alarming attributes (high alarm, low alarm,
etc.) in CARE. For a type of alarm like Sensor Open, the C-NAP generic alarm
text and C-bus system alarm descriptor appears on the C-bus. A user must
connect to the site with ZM7604 to pinpoint the problem sensor.

12. Also in the Command Center, select TOD Input/Output. Create a time-of-day
(TOD) program for each zone, or controller group, as necessary. TOD
programs apply only to W7620 Controllers, not MicroCel/MacroCels.

13. Also in the Command Center, set up Data Sharing as usual for C-NAP bus
points ONLY. Data Sharing here does not apply to mapped points. See Excel
Link System Engineering Manual 74-5591 for details on data sharing.

665 EN2Z-0937GE51 R0518


EXCEL 10 CONTROLLERS CARE

Step 2B MicroCel/MacroCel Controller Setup


Purpose Set up the MicroCel/MacroCel controller files for the interface to the Excel
Link. This step is required only when MicroCel/MacroCel controllers are on
the C-NAP bus.
Note that DeltaNet M-Cel PPT (MPPT) software must be properly installed
and your PC must have sufficient base memory in order to run MPPT.
Procedure 1. Select the Excel Link controller in the logical plant tree. Click the
Controller menu item, then drop-down items Tools, Xlink MPPT
Configuration.

RESULT: The M-PPT window opens.

2. Perform typical off-line application programming, configuration, and loading as


detailed in DeltaNet M-Cel PPT Software User Guide 77-0165, "Excel Link"
Mapper section.

Give each controller the exact same name as its corresponding Plant Name
assigned in CARE when you replicated the plants, if you plan to automap the
MicroCel/MacroCel points.

Remember that MPPT point programming must match the CARE schematic for
automapping to be accurate. If you do not use standard MicroCel/MacroCel
programs, do not plan on automapping.

Step 2C W7600/W7620 Controller Setup


Purpose Set up the W7600/W7620 controller files for the interface to the Excel Link.
This step is required only when W7600 or W7620 controllers are on the C-
NAP bus.

Procedure 1. Select the Excel Link controller in the logical plant tree. Click the
Controller menu item, then drop-down items Tools, Xlink ZM 7604
Configuration.

RESULT: The ZM7604 main menu displays.

2. Select File, then drop-down item Open Site. Select the Excel Link site.

RESULT: The ZM7604 main menu redisplays.

3. Select menu item Configure, then drop-down item Controller. Select New
Controller. Select applicable Controller Type. Assign the controller the same
name as the plant name assigned in CARE when you replicated the plants.

NOTE: For W7600s, see ZM7604 User Guide 74-5588 for configuration
information. The rest of this step applies to W7620s.

Assign Serial Number and C-NAP Node Number.

Choose the Algorithm and Copy Sample as required. Choices here must match
the choices made when creating the plant in the CARE schematic. If not, there
will be errors when writing (downloading) the software application to the
controller because the software application will not match the hardware
configuration.

4. Select Globals and click Add to assign them to the corresponding controller
points. Scroll through the Global list box to find the appropriate points.

Set the Global Assignment Mode to ´All W7620's` in a Controller Group to


repeat this function for all controllers in the same controller group. After you set
this field, you only need to enter this window once for each controller group.

5. Program the Setpoints, Parameters, Inputs, and Outputs as required.

EN2Z-0937GE51 R0518 666


CARE EXCEL 10 CONTROLLERS

To copy this controller configuration to others in the same controller group,


create a New Sample of the one just programmed, back out, and make a New
Controller and then for that new controller, do a Copy Sample of the original.
Repeat as many times as necessary. This step is optional.

6. Exit.

Step 3 Excel Link Configurator/Mapper

Purpose Match CARE plants to their corresponding C-NAP controllers. You can also
manually map points that were not automatically mapped during the plant-
controller matchup and convert engineering units, for example, English to
Metric and vice versa. Finally, you can cross-check to verify the Excel Link
Configurator/Mapper actions.

The following sections detail Excel Link Configurator/Mapper functions.

Perform each one in the order listed:

Step 3A Plant-Controller Matchup


Step 3B User Address-Point Manual Mapping
Step 3C C-NAP to Eng Unit Conversion Mapping
Step 3D Configurator Cross-Check
The starting point for each step is the Excel Link controller, that is, first
select the Excel Link controller in the logical plant tree.

CAUTION
If, after mapping is complete, you use CARE or ZM7604 to make changes to
the database that affect point mapping (for example, detach a plant, add a
point), you must RE-DO the mapping.

Step 3A Plant-Controller Matchup


Purpose Match CARE plants and C-NAP controllers. During this process, the
software automatically maps points between the plants and controllers.
Only W7620, MicroCel, and MacroCel controllers can be automapped;
W7600s cannot.

CAUTION
Automapping only works correctly if the subsystem controller points match
the tables in Step 1B.

Procedure 1. Select the Excel Link controller in the logical plant tree. Click the
Controller menu item, then drop-down items Tools, Xlink ZM 5001
Mapper.

RESULT: A Configurator dialog box displays for entry of a project


name and Excel Link controller name.

2. Enter appropriate project name and Excel Link controller name.

RESULT: The Mapper window displays.

3. Click Plants.

RESULT: A dialog box displays. The upper two list boxes are the
CARE plants and C-NAP controllers that are not yet
matched. The lower list box shows successfully matched
plants and controllers.

4. If the CARE plants and C-NAP controllers have identical names, click Match
Names, then click OK button.

RESULT: The lower box displays the matches.

667 EN2Z-0937GE51 R0518


EXCEL 10 CONTROLLERS CARE

If the CARE plants and C-NAP controllers do not have identical names,
highlight the CARE plant, highlight its corresponding C-NAP controllers, then
click Add.
RESULT: The lower box displays the match.

5. To unmatch a plant and controller combination, highlight the matched pair in the
lower list box and click Remove.

RESULT: The CARE plant moves back to the upper left-hand list
box and the C-NAP controller moves back to the upper
right-hand list box.

6. When done, click OK to close the window and save the changes. Or, click
Cancel to close the window without saving the changes.

RESULT: The window closes. If you made matches, software maps


the points in the CARE plant(s) with the corresponding
points in the C-NAP controller(s).

Step 3B User Address-Point Manual Mapping


Purpose Map points that were not automatically mapped during the preceding step.

Procedure 1. Select the Excel Link controller in the logical plant tree. Click the
Controller menu item, then drop-down items Tools, Xlink ZM 5001
Mapper.

RESULT: A Mapper dialog box displays for entry of a project name


and Excel Link controller name.

2. Enter the XLink and choose menu item Points. Scroll through the CARE Plant
Name box in the upper left-hand list box to choose a plant. The All user
addresses choice is a comprehensive display.

RESULT: The CARE User Addresses box shows all unmapped


points for the chosen plant. If you added points to the
schematic for a subsystem controller using the Point
Without Graphic option, software does not automatically
map those points. The Point Without Graphic points
display here. The bottom box shows all mapped points for
the chosen plant (with their corresponding C-NAP points).

3. To manually map these points, highlight the CARE user address, highlight its
corresponding C-NAP point, and click Add.

RESULT: The points move to the lower box.

4. To unmap a pair of points, highlight the mapped pair in the lower list box and
click Remove.

RESULT: The CARE user address moves back to the upper left-
hand list box and the C-NAP point moves back to the
upper right-hand list box.

C-NAP Groups/Wildcard Points Box The Groups/Wildcard points box provides four options for accessing C-NAP
points:

1. Controller Groups displays the names of all controller groups built during "Step
2, Subsystem Controller Configuration". To map a C-bus point to a controller
group point using the Many-to-one logical statements (that is, OR, AND, AVE,
MAX, and MIN), highlight the C-bus point, highlight the controller group, and
click Add. A field of asterisks, *, displays in the mapped point area for the C-
NAP point name. Double-click the controller group again and the controllers
within the group display. Double-click on any controller and its list of points
displays. Click the desired point, then click Add. Software maps the highlighted
C-bus point to this C-NAP point on all controllers within the controller group.

EN2Z-0937GE51 R0518 668


CARE EXCEL 10 CONTROLLERS

2. Point Groups displays the names of all point groups built during "Step 2,
Subsystem Controller Configuration". Point groups are for viewing only; do not
map these.

3. Global Points lists all C-NAP global points built during "Step 2, Subsystem
Controller Configuration". To map a C-bus point to a C-NAP global point,
highlight the C-bus point, click Global Points, highlight the corresponding C-
NAP point, then click Add.

NOTE: You cannot map globals on the C-bus directly to globals on the C-NAP
bus.

4. Controller: Point Wildcard Search is an easy way to use wild cards to find points
on C-NAP. Use it, where it will save time, when doing manual mapping.

Step 3C C-NAP to Eng Unit Conversion Mapping


Purpose Set up engineering unit conversions for points mapped from the C-NAP bus
to the C-bus. For example, if a C-NAP point uses degrees Fahrenheit and
you want the central PC to display in degrees Celsius, use this procedure to
establish the conversion. All points that read in degrees F on C-NAP will
read in degrees C on the C-bus.

You can also set up automatic mapping of engineering units, that is, all
units convert English to Metric, or vice versa.

Procedure 1. Select the Excel Link controller in the logical plant tree. Click the
Controller menu item, then drop-down items Tools, Xlink ZM 5001
Mapper.

RESULT: A Mapper dialog box displays for entry of a project name


and Excel Link controller name.

2. Enter the XLink and choose menu item Engineering Units. To map a C-NAP
engineering unit to a CARE engineering unit, highlight the C-NAP engineering
unit, highlight the corresponding CARE engineering unit, and click Add.

RESULT: The mapped pair displays in the lower list box.

3. To unmap a pair of engineering units, highlight the mapped pair in the lower list
box and click Remove.

RESULT: The CARE engineering unit moves back to the upper left-
hand list box and the C-NAP engineering unit moves
back to the upper right-hand list box.

4. To set up system-wide auto-mapping, select the appropriate CARE Units. You


configured the C-NAP units during "Step 2, Subsystem Controller
Configuration".

Step 3D Configurator Cross-Check


Purpose Verify XLink Configurator/Mapper steps.
Procedure 1. Click Configurator Cross-Check.

RESULT: Results display. When good, back out to the Xlink


Options menu.

Step 4 Subsystem Site Backup

Purpose Save all subsystem and Excel Link Configurator/Mapper data to


diskette/CD. You commission the systems from the medium via a portable
PC.

669 EN2Z-0937GE51 R0518


EXCEL 10 CONTROLLERS CARE

Procedure 1. Select the Excel Link controller in the logical plant tree. Click the
Controller menu item, then drop-down items Tools, Xlink ZM 7604
Configuration.

RESULT: The ZM7604 main menu displays.

2. Click Utilities, then drop-down item Site Backup from the main menu. Follow
instructions on the screen.

IMPORTANT
Make sure your ZM7604 and CARE backups are done together as
compatible databases. Restoring incompatible backups can cause
numerous alarms during Excel Link start-up.

Step 5 Excel Link CPU and SSI Download

Purpose Copy each Excel Link application program into the appropriate controller
CPU. See Excel Link Checkout & Test 74-3557 for more details.
Procedure 1. Using the PC-to-Excel communication cable, connect the portable PC
serial port (COM1 or COM2) to the Excel Link RS-232 port (see
"Physically Connect to Controller" section).

2. In CARE, with the Excel Link as the currently selected Controller, click menu
item Controller, then submenu items Tools and XL Online (see "Download
Controller" section).

3. For the SSI download, set the C-NAP bus node switch on the SSI hardware to
match the selections made in the CPU commissioning and ZM7604 SSI
configuration screens.

4. Click menu item Controller, then drop-down items Tools and Excel Link ZM
7604 Configuration.

5. Click menu item File, then drop-down item Open Site.

6. Select Excel Link site name and click OK.

7. Click menu item File, then drop-down item Connect.

RESULT: The Site box displays.

8. Click OK button.

RESULT: The word ´Connected` appears on the top line of the


screen after a successful connection.

9. Click menu item File, then drop-down item Write Controller. Select ´Excel
Link`.

10. In the Write to Controller box, select Excel Link controller name. Click the All
Files button. Click OK button.

RESULT: An In Progress box shows the number of requests


pending.

11. Wait until all data is downloaded to the SSI controller (about 7 minutes). The In
Progress box displays "No requests pending" when complete. Check Total
Errors. If not zero, retrace steps and repeat download.

If download is complete and there are no errors, click Cancel.

If there are problems, refer to Excel Link System Engineering Manual 74-5591
or Q7645A Excel Link Checkout & Test 74-3557.

EN2Z-0937GE51 R0518 670


CARE EXCEL 10 CONTROLLERS

12. Exit ZM7604 by selecting, in sequence, Disconnect, Close Site, and Exit
under the File menu item.

RESULT: The SSI download is complete and the CARE window


redisplays.

Step 6 Subsystem Controller Download

Purpose Download subsystem controller application programs as necessary.

MicroCel/MacroCel controllers may not require a download at this time if,


during their configuration in "Step 2, Subsystem Controller Configuration",
they were downloaded. When the Excel Link starts running, the C-NAP bus
activates and the MicroCels and MacroCels begin communicating.
For W7600 and W7620 Controller downloads, use the following procedure.

Procedure 1. While still connected to the Excel Link RS-232 port (previous Step 5),
start CARE on the portable PC. Select the Excel Link plant. Select
menu item Controller, drop-down item Xlink ZM 7604 Configuration.
RESULT: The ZM7604 main menu displays.

2. Open the site, connect to the site, and write to subsystem controllers
(procedure is the same as that in Step 5 for writing to the Excel Link SSI
controller).

3. Refer to Q7645A Excel Link Checkout & Test 74-3557 to verify functionality.

671 EN2Z-0937GE51 R0518


EXCEL 10 CONTROLLERS CARE

EN2Z-0937GE51 R0518 672


CARE EXCEL 10 CONTROLLERS

Excel VAV2 Controller


The W7751D,F,H are Variable Air Volume (VAV) Controllers in the Excel 10
family product line. These VAV systems provide pressure independent or
pressure dependent air flow control and series or induction fan control using
single and dual duct applications. VAV systems generally provide cool air
only to the zones. The W7751 controllers provide additional outputs that
control VAV terminal reheat coils. The heaters can be staged electric or
modulating hot water. Supply and exhaust pressurization control are
provided on a zone basis.

They can be used in stand-alone applications or be used in combination with Excel


10 Zone Manager (FTT), other Excel Controllers, and the Excel Building Supervisor,
to provide a complete room control solution for small to large commercial
buildings.

NOTE: This chapter only deals with controllers configured as pressure


independent systems. For further application details, please refer to the
Plug-In online help and the Excel 10 W7751 product literature.

Chapter Overview
• Technical Overview: Airflow Sensing
• Flow Sensor Calibration
• Configuration
• Balancing
• Engineering Scenarios
• Procedures You Should Know
• 1. Flow Sensor Calibration
• 2. Balancing
• 3a. Engineering OEM Balanced Controller
• 3b. Engineering On-Site Controller (Controller Replacement)

Technical Overview: Airflow Sensing


General Sensing Airflow begins with the sensing of the pressure within the airflow
stream. In its simplest form, the measurement of airflow involves the
sensing of the upstream pressure (referred to as the total system pressure),
and the sensing of the system static pressure. Figure 1 diagrams a simple
sensing device incorporated in most VAV Terminals on the market today.

Airflow

Figure 1: Airflow Sensing Device

The airflow-sensing device shown in figure 1 includes a mechanism that gathers and
transmits the upstream pressure of the airflow. This device usually incorporates a
group of openings that point upstream and allows the total system pressure to enter.
The multiple openings in the upstream sensor are intended to provide an overall
average of the upstream pressure. The second mechanism included in the airflow
sensing device gathers and transmits the downstream or static pressure. This
second mechanism sometimes incorporates more than one opening. By subtracting
the downstream pressure from the upstream pressure, a new pressure called
velocity pressure is created.

The configuration shown in figure 1 demonstrates the use of two mechanical


devices for sensing the pressures within an airflow stream, but the information
transmitted by the devices does not allow the actual value of the pressure to be
calculated. In order to utilize this information, it must be converted into a value that

673 EN2Z-0937GE51 R0518


EXCEL 10 CONTROLLERS CARE

represents the actual velocity pressure. Velocity pressure is easily determined by


attaching a simple mechanical gauge that will measure the difference between the
two pressures and provides a value representing this difference as figure 2 shows.

Airflow

Figure 2: Airflow Sensing Device with Pressure Gauge

If a plot is made of the velocity pressure vs. the actual velocity, a graph is created
similar to the graph shown in figure 3. The charts in figure 3 show the resultant
velocity as the pressure is varied between 0.0 and 1.0 inches of H2O (0 to 249 Pa).
Here an important fact about the relationship between pressure and velocity is
demonstrated; the relationship is a nonlinear function.

Velocity Vs. Velocity Pressure (SI Units)

25

20
Velocity (m/s)

15

10

0
55

46

37

28

19
0

1
9.
.9

.8

.7

.6

4.

9.

4.

9.

4.
24

49

74

99

24
12

14

17

19

22

Velocity Pressure (Pa)

Figure 3: Graph of Velocity Pressure vs. Velocity in SI Units

VAV2 Controller Behavior The VAV2 controller provides the ability of converting a velocity pressure
value into a velocity value and acting upon this value.

In its simplest form, the controller senses the velocity pressure, converts the
pressure into a velocity, applies the field balancing correction to the velocity and
finally provides this velocity to the control algorithms. The controller also transmits
airflow information to users or other controllers through an array of controller
network points. A basic information flow diagram, shown in figure 4, outlines the
airflow sensing process.

Calibration Configuration/Balancing

Convert Convert Control


Physical Apply
Sensor Signal Pressure and
Flow Air Balancing
into into User
Sensor Results
Pressure Velocity Results

Factory Field

EN2Z-0937GE51 R0518 674


CARE EXCEL 10 CONTROLLERS

Figure 4: Airflow Sensing Process

The process outlined in figure 4 can be divided into two procedures, calibration and
configuration/balancing. These processes are performed during two stages, factory
and field.

NOTE: OEM manufacturers do the Balancing in the factory.

Flow Sensor Calibration

Procedure Site Factory


Convert Sensor Signal into PressureAfter the VAV2 controller is manufactured, the pressure sensor is calibrated
before the controller is released for shipping. The sensor is calibrated to
sense pressures between 0.0 to 2.0 inches of H2O (0 to 498 Pa). This
calibration involves a set of parameters, referred to as gain and offset,
defining a linear scaling of the sensor as it relates to pressure.

The value calculated by the controller is not in standard pressure units, but in units
of volts. The calculated voltage value is related to pressure through the following
second set of factor parameters:

Pressure Parameter
0.0 inches H2O (0 Pa) Flow Volts Zero
1.0 inches H2O (249 Flow Volts Mid
Pa)
2.0 inches H2O (498 Flow Volts High
Pa)

The ideal values for the flow volts variables can be graphically represented and is
shown in the chart in figure 5.

2.0000
(498) Offset
Pressure, in. H2O (Pa)

Scaling
g
alin
Sc
in
Ga
1.0000
(249)

0.0000
0.5000 2.7500 4.5000
(Lo Volts) (Mid Volts) (Hi Volts)
Voltage (Ideal)

Figure 5: Pressure Vs. Ideal Voltage for Pressure Sensor

The parameters determined during factory calibration are retained in the controller’s
memory and can be accessed through the network variables:

• nciFactoryCal.FlowGain
• nciFactoryCal.FlowOffset
• nciFactoryCal.FlowVoltsZero
• nciFactoryCal.FlowVoltsMid
• nciFactoryCal.FlowVoltsHigh

675 EN2Z-0937GE51 R0518


EXCEL 10 CONTROLLERS CARE

It is very important that the parameters determined during manufacturing of the


controller are never changed. The information is specific to each controller and
cannot be recovered. However, access to the parameters can assist in trouble-
shooting airflow issues during installation and startup. They are provided as a
reference. The final factory state action stores the resulting pressure in units of volts
in the network point nvoIO.FlowVolts for information and further processing.

Configuration

Procedure Site OEM Factory, or at the Site

Configuration of the VAV2 controller for airflow control is essential for accurate
measurement and control. When a controller is configured as a pressure
independent system, the minimum configuration includes the airflow pressure
sensor and damper actuator as shown in figure 6 below.

Honeywell

Figure 6: VAV Terminal & Controller Configured as Pressure Independent


System

With the pressure independent operation selected, the following configuration


parameters are of primary concern:

• Controller Type (Pressure Independent, as mentioned)


• Flow Pickup Table
• Duct Area
• Airflow setpoints
• Proportional Reheat

Flow Pickup Table


Convert Pressure into Velocity Unlike many control systems currently used on VAV Terminals, the VAV2
controller allows the airflow characteristics to be defined as a flow
characteristics curve, so-called flow pickup table. The flow pickup table
converts the pressure signal (kPA) into a velocity (m/s) signal. This is
accomplished with the application of the unique VAV Terminal flow data
provided by the manufacturer. The flow pickup table allows the VAV
Terminal velocity to be defined by ten unique points representing a velocity
curve similar to the one shown in figure 3.

This detailed definition of airflow velocity results in very high accuracy in the area of
VAV Terminal airflow velocity sensing. The actual table values are stored in twenty
network variables representing the airflow curve; The flow pickup variable names
are:

Point Pressure Variable Velocity Variable


Number (kPa) (m/s)
PT 1 nciVoltsCal.ubS5[0] nciFlowCal.siS3[0]
PT 2 nciVoltsCal.ubS5[1] nciFlowCal.siS3[1]
PT3 nciVoltsCal.ubS5[2] nciFlowCal.siS3[2]

EN2Z-0937GE51 R0518 676


CARE EXCEL 10 CONTROLLERS

Point Pressure Variable Velocity Variable


Number (kPa) (m/s)
PT 4 nciVoltsCal.ubS5[3] nciFlowCal.siS3[3]
PT 5 nciVoltsCal.ubS5[4] nciFlowCal.siS3[4]
PT 6 nciVoltsCal.ubS5[5] nciFlowCal.siS3[5]
PT 7 nciVoltsCal.ubS5[6] nciFlowCal.siS3[6]
PT 8 nciVoltsCal.ubS5[7] nciFlowCal.siS3[7]
PT 9 nciVoltsCal.ubS5[8] nciFlowCal.siS3[8]
PT 10 nciVoltsCal.ubS5[9] nciFlowCal.siS3[9]

Typically, the user defines a flow curve based on velocity in m/s vs. pressure in kPa;
however, the controller uses the equivalent voltage to represent pressure as shown
in the point list above. Most tools that configure the VAV2 controller perform the
transformation from pressure to voltage for the user. Be aware that voltage values
are being displayed when viewed directly in the controller, not pressure values.

The first action during conversion is to adjust the flow volts velocity results from the
factory stage by subtracting the zero adjust parameter. This parameter,
nciFlowVoltsOffsetS12, is determined whenever the controller is zeroed.

The next action is to locate the flow volts on the flow pickup table.

The installer must either select an existing flow pickup table based on the
manufacturer of the VAV Terminal from predefined choices in the configuration tool
(easiest method), or define a custom flow pickup table in order for this operation to
provide accurate velocity (for detailed information on this method please refer to the
VAV2 Controller Plug-in Online Help). Once the flow volts variable has been located
on the table, the controller determines velocity by interpolating between the two
closest points on the flow pickup table.

If the flow pickup table is defined directly from the manufacturer’s current flow data
for the type of VAV Terminal the controller is installed on, the flow values will be very
close to the real value. However, installation of the VAV Terminal may introduce
unexpected variations in the pressure sensing. To compensate for variations in the
actual field conditions and installation, the VAV2 controller allows for a final field
calibration, so-called balancing that corrects for these variations.

The flow pickup table is based on the following guidelines.

• Air Volume for the first table entry is always zero. This is a fixed
requirement; point 1 must be zero flow and pressure.
• The last or tenth table entry should be the maximum allowable flow
allowed for the VAV Terminal.
• The second table entry should be the minimum controllable flow allowed
for the VAV Terminal.
• The ninth table entry should be between 1.25 times the maximum
airflow setpoint selected for the controller.
• The remaining six points should be selected as incremental values
between table entries two and nine.

Duct Area
The duct area is defined as the cross sectional area of the duct at the location of the
flow sensor. This is graphically shown in figure 7.

677 EN2Z-0937GE51 R0518


EXCEL 10 CONTROLLERS CARE

Duct Area

Airflow
Duct Diameter

Figure 7: Diagram Defining Duct Area

The duct area is required for the controller so information calculated by the controller
can be presented in volume as well as velocity. Airflow volume is the most common
way airflow is represented for users. Balancing and other operations are
represented in the controller as airflow volume in the units of meters cubed/ hour,
m3/h or liters/second (US units are cubic feet per minute, cfm). It is necessary that
an accurate area be entered for the duct area in order to minimize errors in the
configuration and setup of the controller.
The VAV Terminal manufacturer will list this information in the appropriate units on
the VAV terminal itself or in the literature included with the VAV terminal. In either
case, the information must be configured in the controller using the correct units for
the application, m2 for SI or ft2 for US. The configuration tool may allow the area to
be selected from a standard list of round duct diameters, in which case the tool
calculates the correct area.
If the duct where the flow sensor is placed is a non-standard shape or size, then the
area may need to be calculated manually. The area can be calculated for standard
shapes as follows:

Rectangle:

DuctArea = Length × Height


where length and height are meters for SI, feet for US.

Round Duct:

3.1416 × (diameter )
2
DuctArea =
4
where diameter is meters for SI, feet for US.

Airflow Setpoints
Airflow setpoints are the values used by the controller to make control decisions.
With the use of a set of airflow setpoints, a wide range of control options become
available. Typically, airflow setpoints are determined for each unique installation. It
is the responsibility of the installer to obtain or determine the appropriate setpoints
for each installation.

Depending on the configuration of the controller, there are four basic airflow
setpoints that can be configured in the controller. The setpoints and their purpose
are listed as:

• Maximum Airflow Setpoint


The maximum airflow volume (SI m3/h, US cfm) that the controller will
deliver in the cooling mode (or heating mode for dual duct, dual
controller installations).

• Minimum Airflow Setpoint


The minimum airflow volume (SI m3/h, US cfm) that the controller will
deliver in the cooling mode (or heating mode for dual duct, dual
controller installations).

EN2Z-0937GE51 R0518 678


CARE EXCEL 10 CONTROLLERS

• Standby Airflow Setpoint


This becomes the maximum airflow volume (SI m3/h, US cfm) setpoint
whenever the controller is placed in the standby mode.

• Reheat Airflow Setpoint


The fixed airflow volume (SI m3/hm, US cfm) maintained by the
controller whenever current controller mode is reheat. This parameter
typically applies to single controller installation, and is not part of the
dual duct, dual controller installations. If this parameter is not enabled
for a controller configuration, check that some form of mechanical
reheat has been configured.

The setpoints are typically set through a configuration tool, but direct access is
possible through the network variables:

Airflow setpoint Network Variable


Maximum Setpoint nciMaxFlow
Minimum Setpoint nciMinFlow
Standby Setpoint nciMinFlowStdby
Reheat Setpoint nciMaxFlowHeat

If the setpoints are entered through the configuration tool, a set of rules is applied
that prevent incorrect values from being entered. However, if the values are entered
directly into the network variable, the user must apply a set of rules to prevent an
invalid setpoint error from being generated at the controller. The rules are listed as:

• Minimum Airflow Setpoint < Maximum Airflow Setpoint


• Minimum Airflow Setpoint < Reheat Airflow Setpoint
• Standby Airflow Setpoint < Maximum Airflow Setpoint
• Reheat Airflow Setpoint < Maximum Airflow Setpoint

Proportional Reheat
One misunderstood and overlooked parameter affecting the operation of airflow
control is the proportional reheat parameter. This parameter is a simple check box in
most configuration tools that enables proportional reheat when checked. The
controllers network variable, nciConfig.ReheatPropControl, can be set directly by
simply setting the variable to true or false. This parameter affects the operation of
single duct, single controllers, with pressure independent configurations.
The effects of proportional reheat can best be explained by examining the VAV2
controller’s airflow control setpoint reaction to changes in the space temperature
with respect to the space temperature setpoints. The default configuration is
proportional reheat disabled or the network parameter value set to false. In this
configuration the operation of the airflow control setpoint is outlined in figure 8. In
this diagram, the colored lines represent the airflow setpoint with respect to the
current space temperature and setpoints.

679 EN2Z-0937GE51 R0518


EXCEL 10 CONTROLLERS CARE

Heating Deadband Cooling Max Flow


Stp

Rhtg Flow

Air Flow
Stp
Reheat
On or
Open
Min Flow Min Flow
Stp Stp

Decreasing Htg Clg Increasing


Stp Stp

Space Temperature

Figure 8: Diagram of Airflow Control Setpoint vs. Space Temperature

Figure 8 clearly illustrates that when the space temperature is above the cooling
setpoint, the controller is in the cooling mode and the airflow control setpoint follows
the blue line. As the space, temperature falls below the cooling setpoint but is still
above the heating setpoint, the controller remains in the cooling mode and the
airflow control setpoint is fixed at the minimum airflow setpoint. When the space
temperature falls below the heating setpoint, the controller’s mode is changed to
reheat and the airflow control setpoint follows the red line. This has the effect of
fixing the airflow control setpoint equal to the reheat airflow airflow setpoint. This
fixed setpoint remains in effect until the space temperature rises above the space
cooling setpoint. Note that whenever the space temperature is in the deadband
region, no mechanical heating is provided.

In some applications, a fixed reheat airflow setpoint can cause temperature swings
and cycle the mechanical heating system when excessive unconditioned air is
introduced into the space. One method to correct this issue is by setting the
proportional reheat parameter to enable or true. With the proportional reheat
parameter enabled, the Airflow control setpoint algorithm is modified and the airflow
control setpoint value follows the diagram in figure 9.

Heating Deadband Cooling Max Flow


Stp

Rhtg Flow
Air Flow

Stp
Reheat
On or
Open
Min Flow Min Flow
Stp Stp

Decreasing Htg Clg Increasing


Stp Stp

Space Temperature

Figure 9: Diagram of Airflow Control Setpoint with Proportional Reheat

With the proportional reheat parameter set to enable, the airflow control setpoint
follows the red line when the controller is in the reheat mode. When the space
temperature is in the deadband region, the airflow control setpoint is modulated
between the reheat airflow setpoint and the minimum airflow setpoint. This can
introduce some stability in the deadband region during heating periods.
It should be noted that when the VAV Terminal includes a series reheat fan, the
proportional reheat parameter should be set to disable or false.

EN2Z-0937GE51 R0518 680


CARE EXCEL 10 CONTROLLERS

Balancing

Procedure Site OEM Factory, or at the Site

Airflow Balancing is the final action required to complete the VAV2


controller installation and startup. Balancing is required for a variety of
reasons that range from unusual installation conditions, to inaccuracies in
the flow pickup table. Through balancing, these installation specific
conditions that affect the airflow sensing can be removed.

Prerequisites This phase assumes that the VAV2 controller has been configured and
checked for proper operation.

Network Variables Balancing, is performed by measuring the actual airflow volume and
correcting the controllers sensed airflow velocity. This is done by comparing
the controller’s sensed uncorrected (apparent) airflow velocity against the
actual velocity measured. The balancing is performed at two flow values,
typically maximum and minimum airflow setpoints. The results are stored in
a group of field calibration network points and are accessible through the
network variable names:

• nciFld3PtCal.siCalActualLowS3
• nciFld3PtCal.siCalApparentLowS3
• nciFld3PtCal.siCalActualMidS3
• nciFld3PtCal.siCalApparentMidS3
• nciFld3PtCal.siCalActualHiS3
• nciFld3PtCal.siCalApparentHiS3

NOTE: OEM manufacturers perform the balancing in the factory.

When the balancing is complete, the network variables contain the results of the
calibration in terms of velocity. These six points provide a correction factor to the
controller’s air velocity that can best be understood in terms of a chart as shown in
figure 10.

Actual Flow Velocity (m/s)


Flow Volume (m3)
Default (Sensor) Calibration during
production at factory (1)

Balancing at OEM factory (2a) or at the


site (2b, 3b) including linearization
through flow pickup table

Max. allowed flow of terminal

Max. airflow control setpoint 1.25 times of Max. control setpoint

Standby and Reheat


airflow control setpoints
Min. airflow control setpoint

Airflow control setpoints,


defined during application
selection (3a, 3b)

"Zeroed" Controller, 0 Min. Max.


set during balancing Airflow setpoints, defined 100 Damper Position (%)
(2a, 2b, 3b) during balancing (2a, 2b, 3b) Apparent Flow Velocity (m/s)

Figure 10: Apparent Controller Velocity Vs. Actual Measured Velocity

The chart shows the controller creating a 3-point correction to the sensed velocity.
For sensed velocities that lay between the calibration points, the controller
interpolates the velocity based on the closest two calibration points.

681 EN2Z-0937GE51 R0518


EXCEL 10 CONTROLLERS CARE

It must be stated here, if power is cycled on the VAV2 controller, no attempt should
be made to zero or calibrate the controller for a period of not less than 5 minutes.
During this period, the sensing process within the controller has not yet stabilized.
Any balancing or zeroing of the controller may result in erroneous values and poor
accuracy.

In addition, the flow pickup table must have point 1 defined as zero flow and
pressure. Erroneous zero offset value will occur without this definition. The flow zero
offset value is not an indication of the accuracy of the flow sensor; it is simply the
results of comparing the flow volts signal to the flow pickup table zero pressure
point.

Process Steps A diagram of the balancing (calibration) process is shown in figure 11. Note
the "repeat ? " feedback item in the diagram. If more than one repeat is
required to obtain accurate airflow measurement, the configuration, testing,
and calibration process should be reviewed.

Maximum Flow Minimum Flow


START Zero Calibration STOP
Calibration Calibration

Repeat ?

Figure 11: Airflow Balancing Process Diagram

Setting Pressure Sensor Zero


The first step that is required for balancing is to zero the pressure sensor. This
places the controller in the manual mode and closes the VAV Terminal damper.
Once the damper is closed, the sensor voltage value is compared to the flow pickup
table point 1 voltage value and the difference is stored in the network variable
nciFlowVoltsOffsetS12. Once the controller has been zeroed, airflow sensing can be
calibrated (balancing). The zeroing operation is only required once for the balancing
process. Once a good controller zero has been established, the controller will
automatically make minor corrections to the zero offset value.

Airflow Balancing
Airflow Balancing is a two-step process: Calibration at Maximum Airflow and
Minimum Airflow. These two calibration points are required for proper airflow
sensing. Though the order of calibration is not important for most applications, it is
recommended that the maximum airflow be performed first.

Maximum Airflow Balancing


This process begins by fixing the airflow control setpoint equal to the maximum
airflow setpoint. If the maximum calibration airflow is different from the maximum
airflow setpoint, the setpoints can be modified. Begin the calibration process with
maximum airflow calibration. The controller will begin to control at the maximum
airflow setpoint. Once the configuration tool has determined that stable flow has
been reached, the tool will request an independent airflow measurement. This
measurement, along with the sensed airflow, will be recorded in the field "calibration
network points".

Minimum Airflow Balancing


As stated in the beginning, airflow calibration is a two-step process; the minimum
calibration is required. If the controller configuration maintains a fixed airflow
setpoint, it is still required that a minimum calibration be performed. It is also
recommended that the minimum calibration setpoint be less then half of the
maximum calibration setpoint, with a minimum low limit velocity at the flow sensor of
200 fpm (1.016 m/s). Proceed the calibration with minimum airflow calibration. The
controller will begin to control at the minimum airflow setpoint. Once the
configuration tool has determined that stable flow has been reached, the tool will
request an independent airflow measurement. This measurement, along with the
sensed airflow, will be recorded in the field "calibration network points".

EN2Z-0937GE51 R0518 682


CARE EXCEL 10 CONTROLLERS

Engineering Scenarios
Procedures You Should Know

You should you be familiar with the basic VAV2 airflow sensing aspects described in
the previous sections. In addition, for proper engineering of VAV2 controllers, you
should have basic knowledge of LonWorks Network Engineering in CARE. Please
refer especially to the following sections:

• CARE and LNS


• Commission LON device /LonWorks network
• Synchronize with LNS
• Upload Parameters
• LNS Plug-Ins
• The Device Library
• Replace Device
• Configure LON Bus
• EBI Settings
• Keep Device Configuration

In the following, the two basic engineering paths (see diagram next page) including
step-by-step procedures for a VAV2 pressure independent air sensing contol system
are described.

683 EN2Z-0937GE51 R0518


EXCEL 10 CONTROLLERS CARE

VAV 2 Process Overview

1
FLOW SENSOR CALIBRATION
(done by Final Device Test at Factory)

New Plants Existing Plants

FACTORY
2a
OEM BALANCING

Mounting and Flow Balancing at


OEM Box-Manufacturer:
 Entering Flow Parameters
 Flow Balancing on Test-Rig
 Complete Unit Test

3a 2b
ENGINEERING / START-UP ON-SITE BALANCING

OFFLINE (Office or On-Site): Mounting and Flow Balancing


 Creating Bindings and directly at the Site, e.g. for
Mappings Controller Replacement
 Checking "Keep Device
Configuration" option

ONLINE (On-Site):
 Getting Service Pin and
Uploading Parameters
 Checking/verifying uploaded 3b
SCPTs
 Selecting "Enable CARE
ENGINEERING / START-UP
Controlled Flow Parameters
for Honeywell VAV2 Devices"
OFFLINE (Office or On-Site):
flag
 Selecting "Enable CARE
 Deleting old temporary LNS
Controlled Flow Parameters
DBs
for Honeywell VAV2 Devices"
 Launching Plug-In and
flag
FIELD Uploading last Configuration
 Checking Application Settings
(Plug-In Online only)
and Flow Parameters with
 Setting "OEM Flag" flag
Plug-In
(optional)
 Creating Bindings and
 Selecting Application (use
Mappings
correct sensor type and flow
pick up table as provided by
ONLINE (On-Site):
the manufacturer)
 Replacing Device with CARE
 Commissioning
 Commissioning with CARE
 Checkout an Test
 Selecting "Enable CARE
 Selecting "Enable CARE
Controlled Flow Parameters
Controlled Flow Parameters
for Honeywell VAV2 Devices"
for Honeywell VAV2 Devices"
flag
flag
 Downloading Flow Pickup
 Synchronizing with LNS
Table
 Do Flow Balancing
 Checkout an Test
 Selecting "Enable CARE
Controlled Flow Parameters
for Honeywell VAV2 Devices"
flag
 Synchronizing with LNS

Figure 12: VAV 2 Process Overview

EN2Z-0937GE51 R0518 684


CARE EXCEL 10 CONTROLLERS

1 Flow Sensor Calibration

For details on general technical aspects on flow sensor calibration, please refer to
"Technical Overview: Airflow Sensing" section.

2 Balancing

For details on general technical aspects on balancing, please refer to


"Configuration" and "Balancing" sections.

Balancing of a VAV2 controller installed on a terminal is required for two basic


reasons:

• Firstly, to resolve the inconsistencies between laboratory settings by


which the terminal flow tables were developed and the actual conditions
of the terminal´s construction and installation.
• Secondly, to resolve electronic variances in the VAV2 controller.

Configuration Parameters The following configuration parameters affect the control of the air flow and
must be adjusted during the balancing procedure:

• Controller Pressure Type


• Flow Pickup Table
• Duct Area
• Airflow setpoints
• Proportional Reheat Flow

Airflow Balancing Rules Controller Pressure Type


The VAV2 applications chapter in this User Guide applies to pressure independent
control systems only.

Flow Pickup Table


The flow pickup table is composed of ten groups of two values, pressure and
velocity. The easiest method for configuring a flow pickup table is to select one of
the standard tables listed in the configuration tool (Plug-In). This selection is based
on the manufacturer of the VAV Terminal and is indexed to the model type installed.
The second and final method to configure the flow pickup table is by creating a
custom flow table within the configuration tool. For detailed instructions on this item,
please refer to the VAV2 Controller Online Help. For both methods, the following
rules are valid:

• Air Volume for the first table entry is always zero. This is a fixed
requirement; point 1 must be zero flow and pressure
• The last or tenth table entry should be the maximum allowable flow
allowed for the VAV Terminal
• The second table entry should be the minimum control setpoint resulting
in a velocity of at least 1.016 m/s (better than 2.0 m/s)
• The ninth table entry should be between 1.25 times the maximum
airflow setpoint selected for the controller
• The remaining six points should be selected as incremental values
between table entries

Flow Pickup Table Download


When downloading the flow pickup table, values are converted from pressure into
voltage. In addition, there will be new values calculated from the converted values
and the factory calibration values coming online from the controller.

NOTE: Due to these facts, each controller is unique from its software
configuration and neither can easily be replaced or copied, nor its
EPROM can be changed.

Duct Area and Airflow Setpoints


For the duct area and airflow setpoints, the following values must be noted:

685 EN2Z-0937GE51 R0518


EXCEL 10 CONTROLLERS CARE

• Max. duct area allowed = 0,372 m²


• Maximum airflow setpoint must not result in a duct velocity greater then
3500 17.78 m/s (fpm)
• Minimum airflow setpoint must not result in a duct velocity less than
1.016 m/s (200 fpm).

Available airflow setpoints (Application: 3a, 3b)


• Max airflow setpoint: Maximum control setpoint allowed for the controller
• Min airflow setpoint: Minimum control setpoint allowed for the controller
• Standby airflow setpoint: Minimum control setpoint during standby mode
• Reheat airflow setpoint: Fixed control setpoint during reheat mode

Airflow setpoint Rules (Application: 3a, 3b)


• Minimum airflow setpoint < Maximum airflow setpoint
• Minimum airflow setpoint < Reheat airflow setpoint
• Standby airflow setpoint < Maximum airflow setpoint
• Reheat airflow setpoint < Maximum airflow setpoint

IMPORTANT
The application setpoints are independent of the balancing values. The
airflow setpoint rules are independent of the used tool.

All VAV2 controllers must be balanced for zero, minimum and maximum
flow. If the controller’s final configuration is a constant volume unit, a
minimum flow balancing is still required. Apply the following rules to the flow
volume setpoints for any controller, even if the calibration setpoints are not
the final configuration setpoints.

• Minimum airflow setpoint must be less then 80 % and greater then 20 %


of the Maximum airflow setpoint.

NOTE: The more accurate the flow pickup table, the wider the range for the
Minimum airflow setpoint. If the controller does not have a minimum
airflow setpoint, then a good starting point for a balancing minimum
airflow setpoint would be 50 % of the maximum airflow setpoint.

IMPORTANT
Minimum airflow setpoint must not be set to zero for balancing.

• After airflow balancing has been completed, the airflow setpoints can be
set to any value that does not violate the required setpoint rules.

Proportional Reheat
When checked, this parameter enables proportional reheat by affecting the
operation of single duct, single controllers, with pressure independent
configurations. For detailed description, please refer to the "Proportional Reheat"
section.

Tools and Equipment


The following figure shows the common equipment setup:

The actual pressure of the flow velocity is converted into a raw electrical sign
through the hot-wire mass flow sensor.

EN2Z-0937GE51 R0518 686


CARE EXCEL 10 CONTROLLERS

2a OEM Balancing
Tools At the OEM factory, the Honeywell OEM VAV Tool and a reference
pressure meter is used for balancing the VAV2 Controller/Terminal.

Honeywell OEM VAV Tool Features


• Designed for use at OEM Factory
• Production orientated
• Works on the Zero Domain only
• Access of all controllers within one segment via Neuron ID

• Allows complete balancing procedure including download of flow pickup


table and functional (accuracy) test of the VAV Terminal unit.
• Uses own DB-format for Terminal-Templates etc.

687 EN2Z-0937GE51 R0518


EXCEL 10 CONTROLLERS CARE

• 2 Different modes for flow pickup table creation (“automatic” based on C-


Factor and manual entering)

• τwo different operator modes are available


Supervisor mode (customize the process and create Terminal
Templates; password protected)
Operator mode (airflow balancing process on the VAV terminal)

EN2Z-0937GE51 R0518 688


CARE EXCEL 10 CONTROLLERS

Procedure 1. Select a predefined Project and Terminal Template from the drop-
down list box.

2. Enter the unique Job ID received from the Supervisor.

3. Since the template contains all the configuration information for balancing a
terminal, you need to click the Calibrate button to load the information into the
terminal. It is always a 3-point airflow balancing performed on the terminal
irrespective of the method chosen: 1. Controller zeroing, 2. Max airflow setpoint
and 3. Min airflow setpoint

4. In order to balance the terminal you first acquire the current terminal’s flow and
damper position based on the setpoints. Begin with controller zeroing and
proceed with max airflow setpoint, then finish with min airflow setpoint (see
steps 5 to 7).
5. After the flow and damper positions stabilize, take the actual flow reading from
a reference meter and enter that in the tool.

6. Press Calibrate button. The tool will write the balanced flow offset.

7. Repeat this for min airflow setpoint.

8. If the supervisor has selected Test menu option, a test of the balancing
accuracy can be performed by clicking the Test button.

9. Connect the next terminal and repeat beginning with step 1.

10. Continue with Engineering / Startup the VAV2 controller as described in the "3a
Engineering OEM Balanced Controller" section.

2b On-Site Balancing
Tools XL 10 VAV2 LNS Plug-In and reference pressure meter. This method is
used when the VAV terminal has to be balanced at the site. This procedure
is typically part and applied when a VAV2 controller must be replaced.
Please refer to the "3b Engineering On-Site Controller (Controller
Replacement)" section.

689 EN2Z-0937GE51 R0518


EXCEL 10 CONTROLLERS CARE

3a Engineering OEM Balanced Controller

OFFLINE at office, or at site Do the following:

1. In CARE, do the bindings and mappings of the VAV2 controller and the relevant
devices.

2. Check the Keep Device Configuration flag. This avoids impermissible or


unintentional overwritings of the actual device configuration by keeping the
actual configuration of the device. The actual configuration of the device cannot
be overwritten by CARE (LNS synchronization) as long as the parameters have
not been uploaded from the device. In case the Keep Device Configuration
flag is checked, the plug-in cannot be invoked from within the device and the
device cannot be commissioned as long as the parameters have not been
uploaded.

IMPORTANT
The flow pickup table and the controller type are not uploaded.

3. Uncheck the Enable CARE Controlled Flow Parameters for Honeywell


VAV2 Devices flag, if you want to update the LNS database with the current
CARE values of the flow parameters ´duct area`, ´flow setpoint minimum` and
´flow setpoint maximum`.

ONLINE at site Continue by doing the following:

4. In CARE, go Onnet.

5. Get the Service Pin of the VAV2 controller.

6. Upload the parameters from the of the VAV2 controller into CARE. The Keep
Device Configuration flag is now unchecked, because the device is updated
with the current parameters.

7. Check/verify uploaded SCPTs.

8. Check the Enable CARE Controlled Flow Parameters for Honeywell VAV2
Devices flag.

EN2Z-0937GE51 R0518 690


CARE EXCEL 10 CONTROLLERS

9. In CARE, go Offnet.

10. Right-click on the VAV2 controller and select Plug-Ins Offline in the context
menu.

11. In the Launch LNS Plugin dialog box, select VAV2 Configure…

12. Click Launch button.

RESULT: The Configuration Screen is displayed.

13. On the Configuration tab, make sure the Controller Type is set to the
appropriate type, Standard/OEM or Smart Actuator. This is important if
choosing an online option of the Plug-in. If the controller type is not set
correctly, the online communication with the Plug-in is not possible as the
following message box displays.

691 EN2Z-0937GE51 R0518


EXCEL 10 CONTROLLERS CARE

Standard Users 14. (Optional) If you are a standard user with basic or less knowledge of all
the configuration settings, check OEM Preconfigured flag. This will
prevent overriding values that have already been entered by the OEM
terminal manufacturer during the application selection. These values
are grayed in the Plug-in as long as this flag is checked. If you are an
advanced user with detailed knowledge of all the configuration settings,
continue with step 16.

WARNING
DO NOT DOWNLOAD THE FLOW PICKUP TABLE WHEN THE OEM
PRECONFIGURED FLAG IS SELECTED. THIS RESULTS IN
MALOPERATION OF THE DEVICE.

15. Set the appropriate application settings on the relevant tabs of the Configuration
screen and continue with step 17.

Advanced Users 16. If you are an advanced user with detailed knowledge of all the
configuration settings, you may do one of the following (see the
following 3 screens):

Change airflow setpoint values (Control Parameters tab) according to


the actual plant conditions
Adjust duct area diameter according to selected sensor type (Control
Parameters tab)
Select sensor type (Flow Pickup Table tab)
(Re-)enter the correct Flow Pickup Table (Flow Pickup Table tab)

IMPORTANT
The last two steps are strongly recommended to minimize maintenance
effort and avoid maintenance problems.

EN2Z-0937GE51 R0518 692


CARE EXCEL 10 CONTROLLERS

693 EN2Z-0937GE51 R0518


EXCEL 10 CONTROLLERS CARE

17. Click Apply button.

18. Click OK button.

19. Commission the VAV2 controller.

20. Do the function test using CARE.

21. (Optional) Check the Enable CARE Controlled Flow Parameters for
Honeywell VAV2 Devices flag if you want to update the LNS database during
the Synchronize with the current CARE values of the flow parameters ´duct
area`, ´airflow setpoint minimum` and ´airflow setpoint maximum`.

NOTE: This option is global and applies to all VAV2 controllers of the project.

22. (Optional) Perform a Synchronize.

3b Engineering On-Site Controller (Controller Replacement)

OFFLINE at office, or at site Do the following:

1. In CARE, check the Enable CARE Controlled Flow Parameters for


Honeywell VAV2 Devices flag.

2. Do the bindings and mappings of the VAV2 controller and the relevant devices.

3. Right-click on the VAV2 controller and select Plug-Ins Offline in the context
menu.

4. In the Launch LNS Plugin dialog box, select VAV2 Configure…

EN2Z-0937GE51 R0518 694


CARE EXCEL 10 CONTROLLERS

5. Click Launch button.

RESULT: The Configuration Screen is displayed.

6. On the Configuration tab, make sure the Controller Type is set to the
appropriate type, Standard/OEM or Smart Actuator. This is important if
choosing an online option of the Plug-in. If the controller type is not set
correctly, the online communication with the Plug-in is not possible.

7. On the Control Parameters and Flow Pickup Table tabs, check the application
settings, especially the balancing parameters, such as max. flow setpoints, duct
area and sensor type.

8. Check the Enable CARE Controlled Flow Parameters for Honeywell VAV2
Devices option if you want to update the LNS database during the Synchronize
with the current CARE values of the flow parameters ´duct area`, ´airflow
setpoint minimum` and ´airflow setpoint maximum`.

ONLINE at site Continue by doing the following:

9. In CARE, go Onnet.

695 EN2Z-0937GE51 R0518


EXCEL 10 CONTROLLERS CARE

10. Replace the VAV2 controller.

11. Commission the VAV2 controller.

12. Check the Enable CARE Controlled Flow Parameters for Honeywell VAV2
Devices flag.

13. In CARE, go Offnet.

14. Right-click on the VAV2 controller and select Plug-Ins Online in the context
menu.

15. In the Launch LNS Plugin dialog box, select VAV2 Download Flow Pickup
Table…, then click Launch button.

16. Confirm message box by clicking OK button.

RESULT: The flow pickup table is downloaded into the physical


VAV2 controller. When downloading the flow pickup
table, values are converted from pressure into voltage. In
addition, there will be new values calculated from the
converted values and the factory calibration values
coming online from the controller.

17. Proceed with airflow balancing by selecting VAV2 Calibrate in the Launch LNS
Plugin dialog box.

EN2Z-0937GE51 R0518 696


CARE EXCEL 10 CONTROLLERS

RESULT: The Sensor Calibration Screen is displayed.

18. Select Flow Calibration tab.

RESULT: Here the control setpoint values of the application set in


the Plug-In are displayed in the Max. Flow Setpoint and
Min. Flow Setpoint fields.

19. (Optional) If the actual plant configuration requires or allows other max. and min
values, enter the corresponding values and click Set button. For proper values,
please note the Airflow Balancing Rules as described in the "2. Balancing"
section.

IMPORTANT
When changing min and/or max values, the corresponding values must be
changed in the application too, and the VAV2 controller must be
commissioned.

20. Proceed with with zeroing by clicking Zero radio button, then clicking Start
button.

697 EN2Z-0937GE51 R0518


EXCEL 10 CONTROLLERS CARE

21. After zeroing is finished, click Calibrate button.

22. Proceed with calibrating at maximum by selecting Maximum radio button and
clicking Start button.

23. After stable flow is reached, enter the flow reading from the reference meter into
the Measured Flow field and click Calibrate.

24. Proceed with calibrating at minimum by selecting Minimum radio button and
clicking Start button.

25. After stable flow is reached, enter the flow reading from the reference meter into
the Measured Flow field and click Calibrate.

EN2Z-0937GE51 R0518 698


CARE EXCEL 10 CONTROLLERS

26. If the result is not “good enough” for some reason, reset the controller to factory
defaults, download the correct flow pickup table and redo the airflow balancing
procedure.

27. Close the Plug-In.

28. If not set, check the Enable CARE Controlled Flow Parameters for
Honeywell VAV2 Devices option if you want to update the LNS database
during the Synchronize with the current CARE values of the flow parameters
´duct area`, ´airflow setpoint minimum` and ´airflow setpoint maximum`.

NOTE: This option is global and applies to all VAV2 controllers of the project.

29. Synchronize the LonWorks network.

699 EN2Z-0937GE51 R0518


EXCEL 10 CONTROLLERS CARE

Excel 10 Commissioning
The commissioning procedure applies to the following Excel 10 controllers:

• W7750 CVAHU
• W7751 VAV2
• W7752 FCU
• W7754 FCU
• W7753 Unit Vent
• W7761 RIO
• W7762 HYD and
• W7763 CHC

Excel10 controllers are configured with the "Plug-ins Offline" function using the
same procedure as all other Excel10 devices. The default engineering units for the
plug-ins is Metric. If you want to change this to English, do the following:

Procedure 1. Select Plug-ins Offline

2. Choose Honeywell Project Settings and select English. This task is done
once and changes the engineering units for all Honeywell Plug-ins used in this
project.

3. Configure the Excel 10 Controller as follows:

a. Launch Plug-ins Offline


b. Select Honeywell XL10 Configure.
c. The plug-in will present information in a similar format to E-Vision
or LonSpec Software.
d. Make sure the Controller Type on the Configuration tab is set to
appropriate type, Standard/OEM or Smart. Enter also the flow
pickup table and duct area.
e. Click OK.

EN2Z-0937GE51 R0518 700


CARE EXCEL 10 CONTROLLERS

f. Power up the controller(s) and connect each controller via the


LonWorks network to the CARE PC.
g. In CARE, open the project and go Onnet.
h. Get the service pin for the Excel 10 controller.
This will allow you to hit the service pin on the Excel10 to set the
Neuron ID. If the service pin has successfully been read, half of the
XL10 controller icon will turn green.

NOTE: The bypass button on the wall module does not send the service pin
for the Excel 10 controllers when used with CARE or LonMaker.
Pushing the service pin on the controller or manually typing the neuron
ID is required. The bypass button service pin functionality will return
with future Excel 10 controller firmware upgrades.

701 EN2Z-0937GE51 R0518


EXCEL 10 CONTROLLERS CARE

i. Commission each Excel 10 controller individually or all at the same


time.
j. Go Offnet.

EN2Z-0937GE51 R0518 702


CARE OPEN LINK CONTROLLER

OPEN LINK CONTROLLER


General The OpenLink (OLink) Controller is an application level integrator that facilitates
interfacing third party HVAC controller networks (subsystem networks) into the
Honeywell EXCEL 5000 system. Equipped with the appropriate vendor network
interface (VNI), an OpenLink Controller provides control and/or monitoring of
controller points for the subsystem controllers.

The OpenLink controller appears on the C-Bus network as any other Excel 500
controller (rev. 1.2), and occupies one of the standard 30 nodes. There can be up to
30 OpenLink controllers on a C-bus tied to 30 subsystem networks, each
subsystem network can support 30 subsystem controllers.

The OpenLink Controller´s CPU is configured using CARE and supports the same
features as other C-Bus controllers, including schematics, control strategy, and
switching logic (optional). A maximum of 768 CARE points (user addresses) can be
configured in the OpenLink CPU.

The connection between the OLink controller and the subsystem network is
established by the OLink interface that includes the VNI information. The OLink
interface data can be stored as a template and then be reused for controllers with
equivalent hardware configuration.

The OLink controller will be downloaded via B-port.

XL500 (50) Controller

C-Bus

OLink Controller OLink Controller

M-Bus 3rd Party Bus

Water- Heat- E-Bus E-Bus


Meter Meter Device Device

OLink Interface/OLink Template)


The OLink interface represents a vendor-specific subsystem hardware configuration
and consists of the following components:

• Subsystem driver (e.g. M-bus)


• Subsystem controllers (e.g. water meter, heat meter)
• Subsystem points = OLink points (e.g. watstat01, heatstat01)

That configuration data may be provided by the vendor via the VNI data (VNI file).
The OLink interface can be stored as an OLink template for reusing the hardware
configuration many times.

703 EN2Z-0937GE51 R0518


OPEN LINK CONTROLLER CARE

OLink Controller

CARE Datapoints
MAPPING

Subsystem Points

Subsystem Driver
OLink Interface / OLink Template

Heat- Water
Subsystem Controller
Meter Meter

OLink templates can be created in the device library. To create a template see
"LonWorks Network Engineering" section.

EN2Z-0937GE51 R0518 704


CARE OPEN LINK CONTROLLER

Engineering Process
OLink controller engineering is to be done by the following steps:

705 EN2Z-0937GE51 R0518


OPEN LINK CONTROLLER CARE

Create OLink controller see "Create OLink Controller" section

see "Create OLink Controller" and


Assign OLink template to
Create OLink template "LonWorks Network Engineering"
OLink controller
sections

Create plant see "Quick Tours" section

Create control strategy

Create Switching Logic

see "Quick Tours", "Editors", "Plant


Create datapoints Schematic", "Control Strategy", and
"Switching Logic" sections
HW/SW points
Plant schematic
without graphic

Attach plant to OLink see "Controllers, Definition


controller Attachment, and Management"
section

Create OLink see "Create OLink Subsystem


subsystem controller Controller" section

Create OLink points see "Create OLink Point(s)" section

Map CARE datapoints to see "Map CARE Datapoints to OLink


OLink points Points" section

see "Plants, Definition and


Replicate plant
Management" section

Translate and download


see "File Management" section
OLink controller

Start-up

EN2Z-0937GE51 R0518 706


CARE OPEN LINK CONTROLLER

CARE Environment View


The following flowchart explains where the OLink specific steps are to be done in
the CARE environment.

Logical Plant Tree


Create OLink controller Assign OLink Template

Create control
strategy
Create Plant
Create = optional
switching logic

Create Datapoints

HW/SW
Plant Points
schematic without
Graphic
MAPPING

Automatic creation
Network Tree Device Library

OLink controller (device) OLink Template

Create OLink device

Create OLink
subsystem controller

comes with template Create OLInk


subsystem controller Import VNI Interface via opt. file
subcontroller name
= plant name

Create OLlink point(s)

come with template


Create OLink point(s)

Create OLink Template


OLink templates are created in the device library and include basically the same
steps as creating the OLink subsystem in the C-bus part of the network tree. To
create a template see "LonWorks Network Engineering" section. To create the
OLink subsystem in the Bus part of the network tree, continue with "Create OLink
Controller" section

Create OLink Controller

707 EN2Z-0937GE51 R0518


OPEN LINK CONTROLLER CARE

Procedure 1. Select menu item Controller, then submenu item New.

RESULT: The New Controller dialog box displays.

2. Into the Controller Name field, enter controller name.

3. From the Bus Name drop-down listbox, select the folder where the OLink
controller should be saved.

4. From the Controller Type drop-down listbox, select ´OLink`.

5. From the OLink template drop-down list box, select a template (to create a
template see "LonWorks Network Engineering" section).

6. Confirm by clicking OK button.

RESULT: The OLink controller (device) is added to the logical plant tree
and to the Bus part of the network tree.

7. Click on the OLink device in the Bus part of the network tree and enter basic
information on the Properties tab on the right as follows:

OLink Device Name


Name can be changed

Vendor Name
Name of vendor of which subsystem is to be connected to the C-Bus

Initialization Block
Contains communication and setup parameters

EN2Z-0937GE51 R0518 708


CARE OPEN LINK CONTROLLER

NOTE: In the Bus part of the network tree you can now add new OLink
subsystem controllers and OLink points (right-click to open context
menu).

IMPORTANT
Changes on the template done in the Bus part of the network tree or in the
device library are not reflected in a template already assigned to a
controller. After the template has been assigned to the controller, it cannot
be unassigned and replaced by another template.

8. Continue by creating datapoints as described in the "Create OLink Point(s)"


section.

9. Continue by creating a plant as described in the "Create OLink Plant" section.

Create OLink Plant


Engineering of the plant including schematic, control strategy switching logic and
datapoints is done in the same way as for a standard Excel 500 controller. The
OLink plant can be of any type.

For detailed information on how to create a plant, refer to the "Quick Tours" section.

Continue by creating datapoints as described in the "Create CARE Datapoints"


section.

Create CARE Datapoints


CARE datapoints for mapping to OLink points can be created as follows:

• Create a plant schematic


• Directly create hardware/software points without a plant schematic

Refer to the "Quick Tours" section for detailed information on these items.

Create Control Strategy and Switching Logic


Control Strategies and Switching Logics for an OLink controller are optional and
can be done in the same way as for a standard Excel 500 controller. For detailed
information on these items, please refer to the "Control Strategy" and "Switching
Logic" sections.

709 EN2Z-0937GE51 R0518


OPEN LINK CONTROLLER CARE

Create OLink Subsystem Controller


Prerequisites The OLink controller has been created.

Procedure 1. In the Bus part of the network tree, click on the OLink controller.

2. Click right mouse key and with left mouse key, click on Create OLink
Subsystem Controller in the context menu

Or, click menu item Controller, then submenu items OLink and Create OLink
Subsystem Controller.

RESULT: The OLink subsystem controller is assigned to the OLink


controller in the Bus part of the network tree.

3. On the Properties tab on the right, enter a name in the Description field.

4. In the list below, enter names and values for the OLink interface in the Value
and Name fields. Therefore you need the VNI description from the vendor
which typically includes the list of points which are to be mapped to the C-bus,
the engineering units, etc.

5. Check the Keep Points Read Only checkbox, if desired. In this case, point
values cannot be overwritten.

6. Continue by creating OLink points as described in the "Create OLink Point(s)"


section.

Create OLink Point(s)

Procedure 1. In the Bus part of the network tree, click on the OLink subsystem controller.

2. Click right mouse key and with left mouse key, click on Create OLink Point in
the context menu

Or, click menu item Controller, then submenu items OLink and Create OLink
Point.

RESULT: The OLink point is assigned to the OLink subsystem controller


in the Bus part of the network tree.

EN2Z-0937GE51 R0518 710


CARE OPEN LINK CONTROLLER

3. On the Properties tab on the right, define settings as follows:

Description
Enter a point name

Point Type
Select point type from drop-down list box

Value Format
Select value format from drop-down list box

Engineering Unit
Select engineering unit from drop-down list box, if desired. Here only those
engineering units can be selected which have been especially defined for the
OLink subsystem controller of the point. For more information on how to create
engineering units for an OLink subsystem controller, refer to the "Define OLink
Engineering Units" section.

Periodic Write
Check the checkbox, if you want the value to be written periodically.

Parameters
Enter names and values for the OLink interface in the Name and Value fields.
Therefore you need the VNI description from the vendor which typically
includes the list of points which are to be mapped to the C-bus, the engineering
units, etc.

Point Mapping
In this area, CARE points are available which have been previously defined as
"OLink Manual Mapping" in order to be mapped to OLink points. From the
CARE Datapoint drop-down listbox, select a datapoint you want to map to the
OLink point.

711 EN2Z-0937GE51 R0518


OPEN LINK CONTROLLER CARE

Define OLink Engineering Units


For each OLink controller, engineering units can be defined which allow converting
OLink subsystem engineering units to C-bus engineering units through conversion
tables.

Procedure 1. In the Bus part of the network tree, click on the OLink controller.

2. Click menu item Controller, then submenu items OLink and OLink
Engineering Units.

RESULT: The OLink Engineering Units dialog box displays.

3. To define an engineering unit, click in the line and enter the unit.

4. To save the engineering units list, click the OK button.

RESULT: Engineering units will be available on OLink point level (see


"Create OLink Point(s)" section.) and for use in conversion
tables (see "Create OLink Conversion Table" section)

Create OLink Conversion Table


For each OLink controller, a conversion table can be defined. Conversion tables
may be necessary for converting engineering units between the OLink subsystem
and the C-Bus system. For example, the VNI file provides the temperature in
Fahrenheit according to the U.S. American (Imperial) system and the C-bus
provides centigrade according to the European (Metric) system.

Procedure 1. In the Bus part of the network tree, click on the OLink controller.

2. Click menu item Controller, then submenu items OLink and OLink
Conversion Tables.

RESULT: The OLink Conversion Tables dialog box displays.

EN2Z-0937GE51 R0518 712


CARE OPEN LINK CONTROLLER

3. To create a new conversion table, click on the New button

4. Under Conversion, select OLink subsystem unit engineering unit, for example
Deg (F), from the From drop-down listbox.

5. Select C-bus engineering, for example Celsius, from the To drop-down listbox.

6. In the Slope field, enter the slope for the conversion, for example 0.55.

7. In the Offset field, enter the offset for the conversion, for example -32.

8. To delete the currently displayed conversion table, click Delete button.

9. To build further conversion tables, repeat procedure starting with step 3.

10. To save conversion table(s), click the OK button.

713 EN2Z-0937GE51 R0518


OPEN LINK CONTROLLER CARE

Map CARE Datapoints to OLink Points


Mapping CARE datapoints to OLink points can be done in the following two ways:

• Automatic Mapping by assigning the ´OLink` Attribute to the CARE datapoint


(logical plant tree). When mapping a CARE point automatically, the datapoint
will be mapped to an unmapped OLink point with the same name as the CARE
user address. If such an OLink point does not exist, it will be automatically
created.
• Manual Mapping by assigning the ´OLink Manual Mapping` attribute to the
CARE datapoint (logical plant tree). OLink Manual Mapping is a pre-definition.
The datapoint can be mapped later to any unmapped OLink point available in
the OLink controller (Bus part of the network tree).

Logical plant tree C-Bus part of network tree

Attribute Selection

OLink None
CARE datapoint OLink point OLink point
(Automatic Mapping) automatically
created
on
cti
Sele
in t
Po

OLink Manual Mapping CARE datapoint Point Selection


CARE datapoint OLink point
(Manual Mapping) for mapping
from OLink
template
Po
in tS
ele
cti
on

OLink point
manually
created

Automatic Mapping
Automatic Mapping between CARE datapoints and OLink points includes the
following 2 steps:

a. Assign OLink attribute to the datapoint in the logical plant tree.


b. Open OLink Point Information dialog box or shift to Bus part of the
network tree and enter OLink point attributes such as point type, value
format, etc.

Procedure 1. In the logical plant tree, click on the datapoint, you want to have made an
OLink point for, in this case for AI1.

RESULT: On the right, the datapoint attributes are displayed in itemized


display.

EN2Z-0937GE51 R0518 714


CARE OPEN LINK CONTROLLER

2. From the OLink Point drop-down listbox, select ´OLink`

RESULT: The datapoint will be automatically mapped to an existing or newly


created OLink point with the same name as the datapoint.

In the logical plant tree, the mapped CARE datapoint is displayed


in yellow. In the Bus part of the network tree, the mapped OLink
point is added. Mapping status is indicated by a blue icon.

715 EN2Z-0937GE51 R0518


OPEN LINK CONTROLLER CARE

3. To complete OLink interface creation, additional attributes need to be entered


by doing one of the following:

In the itemized display of the CARE datapoint, click on the dotted button
right to the OLink Point drop-down listbox.

RESULT: The OLink Point Information dialog box displays.

Enter point type, value format, engineering unit and parameter values and save
settings by clicking OK button. For detailed description of these attributes, refer
to the "Create OLink Point(s)" section.

Or,

To access all OLink points for editing, go to the Bus part of the network tree,
browse to the OLink subsystem controller and click on the desired OLink point.

EN2Z-0937GE51 R0518 716


CARE OPEN LINK CONTROLLER

For detailed description of the attributes, refer to the "Create OLink Point(s)"
section.

Manual Mapping
Manual Mapping between CARE datapoints and OLink points includes the
following 3 steps:

a. Assign ´OLink Manual Mapping` attribute to the datapoint in the logical


plant tree.
b. Go to the Bus part of the network tree and map particular OLink point to
this CARE datapoint.
c. Enter OLink attributes such as point type, engineering unit, etc. for the
OLink point.

Procedure 1. In the logical plant tree, click on the datapoint, you want to have made an
OLink point for, in this case AI10.

RESULT: On the right, the datapoint attributes are displayed in itemized


display.

717 EN2Z-0937GE51 R0518


OPEN LINK CONTROLLER CARE

3. From the OLink Point drop-down listbox, select ´OLink Manual Mapping`.
´OLink Manual Mapping `is a pre-definition. The datapoint can be mapped later
to any unmapped OLink point available in the OLink controller (Bus part of the
network tree).

NOTE: No OLink point will be created.

4. Browse to the OLink subsystem controller in the Bus part of the network tree.

EN2Z-0937GE51 R0518 718


CARE OPEN LINK CONTROLLER

5. In the Bus part of the network tree, select the OLink point to be mapped. An
OLink point can originate from the OLink template, the manual creation in the
Bus part of the network tree or by automatic creation.

Mapped points are indicated by a blue icon, unmapped points are indicated
by a icon.

6. Under Point Mapping, select CARE datapoint from the CARE Datapoint drop-
down listbox.

RESULT: The CARE datapoint is mapped to the OLink point. In the Bus part
of the network tree, the mapped point is indicated by the blue
icon.

Unmap OLink Points

Procedures

Logical Plant Tree 1. In the logical plant tree, click on point you want to unmap.

RESULT: On the right, the datapoint attributes are displayed in itemized


display

719 EN2Z-0937GE51 R0518


OPEN LINK CONTROLLER CARE

2. From the OLink Point drop-down listbox, select ´None`.

RESULT: The OLink point will be unmapped.

Bus Part of the network tree 1. In the Bus part of the network tree, click on point you want to unmap.

RESULT: On the right, the OLink point attributes are displayed in itemized
display.

EN2Z-0937GE51 R0518 720


CARE OPEN LINK CONTROLLER

2. From the CARE Datapoint drop-down listbox, select ´None`

RESULT: The CARE datapoint will be unmapped.

Move OLink Point


In the Bus part of network tree, OLink points can be moved between OLink
subsystem controllers by Drag&Drop.

Procedure 1. Browse to the OLink subsystem controller (source) in the Bus part of the
network tree.

2. Click on OLink point and move it by Drag&Drop to the desired OLink


subsystem controller (target).

Delete OLink Subsystem Controller/OLink Point


In the Bus part of the network tree, OLink subsystem controllers and points can be
deleted. OLink points can be mapped or unmapped. When deleting a mapped
OLink point, the CARE datapoint gets unmapped. This applies also to an OLink
subsystem controller deletion.

Procedure 1. In the Bus part of the network tree, click on the OLink subsystem controller
respectively the OLink point you want to delete.

721 EN2Z-0937GE51 R0518


OPEN LINK CONTROLLER CARE

2. Click right mouse key and with left mouse key, click on Delete in the context
menu.

Replicate Plant
For streamlining the engineering process of OLink controllers, a plant can be
replicated multiple times after the mapping has been done.

Replication will include:

• CARE datapoints
• Control strategies and switching tables, if assigned to the plant.
• Subsystem controllers and OLink points

After replication the plants will be available as unattached plants. After attaching the
plants a "big" OLink interface will have been created.

CARE Datapoints

OLink Controller O-Link

OLink Interface o1 o2 o4 o3 o10 o11 o12 o13 o20 o21 o22 o23

M-Bus M-Bus M-Bus

Water- Heat- Water- Heat-


Water- Heat-
Meter Meter Meter Meter
Meter Meter
2 2 3 3

EN2Z-0937GE51 R0518 722


CARE OPEN LINK CONTROLLER

CARE Datapoints

OLink Controller

o1 o2 o4 o3 o10 o11 o12 o13 o20 o21 o22 o23


OLink Interface

M-Bus M-Bus

Water- Heat- Water- Heat-


Water- Heat-
Meter Meter Meter Meter
Meter Meter
2 2 3 3

Please, refer to the "Plants, Defintion and Management" section for detailed
information on how to replicate a plant.

Import/Export OLink Controller


An OLink controller can be imported, respectively exported at two points:

• From within the Bus part of the network tree


• From within the device library

When importing/exporting the OLink controller from within the device library, a pure
template without any mapping information will be imported/exported whereas when
importing/exporting the OLink controller from within the Bus part of the network tree,
an OLink controller (OLink device) including all mappings will be imported/exported.

For the import into the OLink controller it means that all current OLink points will be
deleted and replaced by the imported OLink points. Mappings between imported
OLink points and CARE datapoints of the same name will be re-established.

For the import into the OLink template it means that the current OLink template data
are deleted and replaced by the imported OLink controller data. No mapping
information will be imported.

Import OLink Controller


Migration Strategy Note If the Import OLink controller function is part of the migration strategy, first perform
steps 1 through 7 from the "Migration Procedure" section.

Import into Current OLink Controller 1. To import OLink controller data into the current OLink controller, browse to the
OLink controller in the Bus part of the network tree.

2. Continue with "Common Steps".

723 EN2Z-0937GE51 R0518


OPEN LINK CONTROLLER CARE

Import into OLink Template 1. To import OLink controller data into an OLink template, open the device library
and browse to the OLink controller (see "LonWorks Network Engineering"
section).

2. Continue with "Common Steps".

Common Steps 3. In the Bus part of the network tree and device library tree respectively, click on
the OLink controller.

4. Click right-mouse key and with left mouse key, click on Import OLink
Controller in the context menu.

RESULT: The Import OLink Controller dialog box displays.

5. Navigate to the folder where the OPT file resides and select it.

6. Check the Open as read-only checkbox if desired. .

7. Click Open button.

RESULT: The Import OLink Controller Options dialog box displays.

8. Select desired option.

RESULT: A message box displays. Note that the existing OLink device
(controller) data will be overwritten when selecting Yes.

9. Click Yes.

RESULT: If the import was successful, a message box informs you about
that.

10. Click OK button.

RESULT: The OLink information imported is displayed in the tree on the


left.

Export OLink Controller


Based on Current OLink Controller 1. To export the OLink controller data based on the current OLink controller, first
translate the OLink controller.

EN2Z-0937GE51 R0518 724


CARE OPEN LINK CONTROLLER

2. Browse to the OLink controller in the Bus part of the network tree.

3. Continue with "Common Steps".

Based on OLink Template 1. To export the OLink controller data based on the OLink template, open the
device library and browse to the OLink controller (see Device Library section).

2. Continue with "Common Steps".

Common Steps 3. In the Bus part of the network tree and device library tree respectively, click on
the OLink controller.

4. Click right-mouse key and with left mouse key, click on Export OLink
Controller in the context menu.

RESULT: The Export OLink Controller dialog box displays.

5. Navigate to the folder where the OPT file should be saved.

6. Into the file name field, enter OPT file name.

7. Click Save button.

RESULT: A message box informs you about the successful export of the
OLink controller.

8. Click Save button.

725 EN2Z-0937GE51 R0518


OPEN LINK CONTROLLER CARE

Migration Strategy
CARE 4.02.00 and higher allows upgrading of old OLink projects to CARE 4.02.00
OLink projects. The exported data of the existing OLink project data can be
imported in the same file format (OPT). An old OLink project consist of two main
elements:

• The CARE database (version 2.01.00 or lower) where the OLink controllers and
also the datapoints are stored.
• The ZM 5002 database (ZM 5002 project) which fits to this CARE project.

During the upgrade the XLink controller will be transformed to the OLink controller
type (see steps 7 and 8). The technical address remains the same.

Migration Procedure

CARE 2.01.00 or lower Modified / ZM 5002 Tool

Datapoint Information Import

CARE 2.01.00 ZM 5002


Database Database
Backup Backup

OLink File Generation


RACL Generation

Controller Files

OPT File
IPL File

RAL File

1. You need to have CARE 2.01.00 installed first with the OLink controller project
in the database.

2. Translate the controller.

EN2Z-0937GE51 R0518 726


CARE OPEN LINK CONTROLLER

3. Start the modified ZM 5002 Tool, which will be provided by the CARE Team
and select the corresponding site.

4. In the modified ZM 5002 tool an additional menu item will be available which
allows creating (export) the OPT file.

5. Make a database backup of the CARE 2.01.00 database or a project backup.

6. Install CARE 4.02.00 or higher (CARE with OLink support).

7. Within the installed CARE version upgrade the CARE 2.01.00 database (or
project) to the highest CARE version and then restore this database (or
project).

RESULT: If an old XLink or OLink controller was found during the


upgrade, the Select XLink, OLink or OPS controller type
dialog box displays. An old XLink controller can be kept as
XLink type or transformed to an OLink or OPS controller.

8. Select OLink, or, if you want to transform the controller to the OPS type, select
OPS.

9. Click OK button.

RESULT: The upgrade will be finished.

727 EN2Z-0937GE51 R0518


OPEN LINK CONTROLLER CARE

CARE 2.01.00 or lower

CARE 2.01.00
Database

CARE Database or Project Upgrade and Restore

Modified / ZM 5002 Tool

ZM 5002
Database
Backup

OPT File

o rt
nk Imp
CARE 4.02.00 OLi

CARE 4.02.00
Database

10. In the Bus part of the network tree, click on the OLink controller.

11. Click right mouse key and with left mouse key click on Import OLink
Controller in the context menu (see "Import OLink Controller" section).

12. Import the OPT file. All mappings between datapoints to OLink points will now
be available.

RESULT: Migration is completed.

EN2Z-0937GE51 R0518 728


CARE OPS CONTROLLER

OPS CONTROLLER
Prerequisites To work with OPS controllers when already using CARE 3.01.00 or higher, you
must order a license key from Honeywell, which enables the OPS controller and
Replicate functionality. Click menu item Help, then submenu item Registration and
check License Key Info. If OPS and Replicate plant is shown as in the following
dialog, you are allowed to work on OPS controllers. If not, order a license key from
Honeywell as described in the "Ordering and Registering" section.

General CARE 3.01.00 and higher supports the OPS (Open Link Point Server) controller as
the successor of the OpenLink controller. This controller is a gateway for integrating
3rd party devices of a subsystem running on busses such as Meter-bus or E-bus
with the C-bus. The OPS controller is freely programmable in the same way as a
standard XL500 controller. Engineering is done in a common way that 3rd party bus
information can be mapped easily onto CARE datapoints (see also Migration
Strategy section). The OPS controller can have at max. 970 pseudo points, or 128
hardware points of each type. Due to the different datapoint description size of
hardware points and pseudopoints, when mixing hardware points and peudopoints,
it´s not possible to simply calculate the max. number of the mixture by adding them
in a one-to-one correspondence. When the RAM size max. of 64 K is exceeded,
then datapoints need to be removed. The connection between OPS controller and
the subsystem is established by the OPS interface. OPS interface data can be
stored as a template and then be reused for controllers with equivalent hardware
configuration.

729 EN2Z-0937GE51 R0518


OPS CONTROLLER CARE

XL500 (50) Controller

C-Bus

OPS Controller OPS Controller

M-Bus 3rd Party Bus

Water- Heat- E-Bus E-Bus


Meter Meter Device Device

OPS Interface (Template)


The OPS interface represents a special hardware configuration and consists of the
following components:

• Subsystem driver (e.g. M-bus)


• Subsystem controllers (e.g. water meter, heat meter)
• Subsystem points = OPS points (e.g. watstat01, heat01)

The OPS interface can be stored as a template for reusing hardware configuration
many times.

OPS Controller

CARE Datapoints
MAPPING

Subsystem Points

Subsystem Driver
OPS Interface / OPS Template

Heat- Water-
Subsystem Controller
Meter Meter

OPS templates are created by using the device library and the OPS Template
Editor (see "LonWorks Engineering" and "OPS Template Editor" sections)

EN2Z-0937GE51 R0518 730


CARE OPS CONTROLLER

Engineering Process
OPS controller engineering is done by the following steps:

Create OPS controller see "Create OPS Controller" section

Assign OPS template to OPS see "Create OPS Controller" and "OPS
Create OPS template controller Template Editor" sections

Create plant see "Basic Steps" section

Create control strategy

Create Switching Logic

see "Basic Steps", "Editors", "Plant


Create datapoints Schematic", "Control Strategy", and
"Switching Logic" sections
HW/SW points
Plant schematic
without graphic

see "Controllers, Definition


Attach plant to OPS controller Attachment, and Management"
section

Create OPS see "Create OPS Subsystem


subsystem controller Controller" section

Create OPS points see "Create OPS Point(s)" section

Map CARE datapoints to OPS see "Map CARE Datapoints to OPS


points Points" section

see "Plants, Definition and


Replicate plant
Management" section

Translate and download OPS


see "File Management" section
controller

Start-up

731 EN2Z-0937GE51 R0518


OPS CONTROLLER CARE

OPS Template Editor


An OPS template represents a hardware configuration consisting of one subsystem
driver, one or several subsystem controllers and subsystem points. By saving OPS
templates, the same hardware configuration can be used many times.

The OPS Template Editor supports the following functions:

• Creating, deleting and renaming of

– OPS templates
– Subsystem drivers
– Subsystem controllers
– Subsystem points

• Importing/Exporting OPS controllers


• Moving subsystem points between subsystem controllers

Create OPS Template


An OPS template is created by creating an OPS device in the device library first
and then editing the OPS device as template in the OPS Template Editor.

Procedures

Create OPS device 1. On the CARE toolbar, click on the Device Library icon .

RESULT: The Library dialog window displays.

2. Right-click on the folder, in which you want to create the OPS device
(template), in this case, the default folder OPS, and click on Create LON
device in the context menu.

RESULT: The OPS device is inserted into the tree.

3. On the Library toolbar on the top, click the icon.

RESULT: The OPS Template Editor displays and the OPS device is
shown in the tree.

4. On the right pane, edit the Template Name and enter the subsystem driver into
the Subsystem Driver field.

5. From the Port Assignment drop-down listbox, select hardware interface.

6. Into the Initialization Block field, enter initialization block description. The
initialization block contains communication and other setup parameters.

7. If desired, create new subsystem controllers and/or subsystem points as


described in the following steps.

Create OPS Subsystem Controller 8. In the tree, click on controller icon, if not already selected.
9. Click on icon.

RESULT: The Enter Subsystem Controller Name dialog box displays.

EN2Z-0937GE51 R0518 732


CARE OPS CONTROLLER

10. Enter subsystem controller name.

11. Confirm by clicking OK button.

RESULT: The subsystem controller (point group) is created and assigned


to the OPS device previously selected. On the right, its name
and address is displayed.

12. In the Sub Controller Address field on the right, enter/change sub controller
address.

13. Continue by creating subsystem points as described in the following steps.

Create Subsystem Point 14. In the tree, click on subsystem controller, which you want to create the
subsystem point for.

15. On the OPS Template Editor toolbar, click on .

RESULT: The Enter Point Name dialog box displays.

16. Enter point name.

17. Confirm by clicking OK button.

RESULT: The subsystem point is created and assigned to the subsystem


controller previously selected.

18. In the Address field on the right, enter address for subsystem point.

733 EN2Z-0937GE51 R0518


OPS CONTROLLER CARE

19. Under Scaling, enter value for:

Factor
Defines factor for measurement value amplification

Offset
Defines value for Offset

Value Format
Defines format necessary for compatibility with OpenLink projects.

Scan Priority
Defines whether the point should be scanned with higher priority than others,
1: = normal, >1: = high priority

20. Under Enhanced, check desired options by clicking corresponding check box.

Readable
From OPS point of view, the value is readable

Writeable
From OPS point of view, the value is writeable

Periodic Write
From OPS point of view, the value will be periodically written

21. To save the OPS template, click OK button.

RESULT: The Library dialog windows redisplays and the OPS device is
indicated as template by the icon in the tree.

EN2Z-0937GE51 R0518 734


CARE OPS CONTROLLER

22. Click Exit button in the Library dialog window.

RESULT The template is now available for selection when creating a new
OPS controller (see "Create OPS Controller" section)

Save OPS Templates

Procedure 1. On the OPS Template Editor toolbar, click on or click OK button.

RESULT: All templates will be saved.

Rename OPS Template, Subsystem Controller, Subsystem Point


Procedure 1. In the tree, click on item, you want to rename.
2. On the OPS Template Editor toolbar, click on and rename the item in the
tree.

Delete OPS Template, Subsystem Controller, Subsystem Point


Procedure 1. In the tree, click on item, you want to delete.
2. On the OPS Template Editor toolbar, click on .

RESULT: The item will be deleted.

Expand and Collapse the Tree


Purpose Quickly expanding or collapsing the tree.

Procedure Expanding/collapsing the whole tree

When expanding the whole tree every hierarchical level is displayed. When
collapsing the whole tree only the project name is visible.

1. Click any object in the tree (project, controller, etc.)

2. Click menu item Edit, then drop-down item Tree expand all or, click Tree
expand all icon on the toolbar, if you want to see all hierarchical levels of
the tree.

735 EN2Z-0937GE51 R0518


OPS CONTROLLER CARE

or,
click menu item Edit, then drop-down item Tree collapse all or, click Tree
collapse all icon on the toolbar, if you want to see only the project name in
the tree.

Procedure Expanding/collapsing parts of the tree

When expanding/collapsing parts of the tree every hierarchical level below the
object selected in the tree, is displayed/closed.

1. In the tree, click the object (project, controller, etc.), which hierarchical levels
below should be displayed/closed (not displayed)

2. Click menu item Edit, then drop-down item Tree expand from here or, click
Tree expand from here icon on the toolbar, if you want to see all
hierarchical levels below the object selected in the tree.

or,

Click menu item Edit, then drop-down item Tree collapse from here or, click
Tree collapse from here icon on the toolbar, if you want to close all
hierarchical levels below the object selected in the tree.

Create OPS Controller


Procedure 1. Select menu item Controller, then submenu item Create.

RESULT: The New Controller dialog box displays.

EN2Z-0937GE51 R0518 736


CARE OPS CONTROLLER

2. Into the Controller Name field, enter controller name.

3. From the C-Bus drop-down listbox, select the folder where the OPS controller
should be saved.

4. From the Controller Type drop-down listbox, select OPS.

5. From the OPS Template drop-down list box, select a template.

6. Confirm by clicking OK button.

RESULT: The OPS device is added to the logical plant tree and the C-bus
part of the network tree. The subcontroller and points are
displayed as defined in the template.

NOTE: In the C-bus part of the network tree you can now add new subsystem
controllers and OPS points (right-click to open context menu).

IMPORTANT
Changes on the template done in the C-bus part of the network tree or in
the OPS Template Editor are not considered for a template already
assigned to a controller. After the template was assigned to the controller,
it cannot be unassigned and replaced by another template.

Create OPS Plant


Engineering of the plant including schematic, control strategy switching logic and
datapoints is done in the same way as for a standard Excel 500 controller. The OPS
plant can be of any type.

For detailed information on how to create a plant, refer to the "Quick Tours" section.

Continue by creating datapoints as described in the "Create CARE Datapoints"


section.

Create CARE Datapoints


CARE datapoints for mapping to OPS points can be created as follows:

• Create a plant schematic


• Directly create hardware/software points without a plant schematic

Refer to the "Quick Tours" section for detailed information on these items.

Create Control Strategy and Switching Logic


Control Strategies and Switching Logics for an OPS controller are optional and can
be done in the same way as for a standard Excel 500 controller. For detailed

737 EN2Z-0937GE51 R0518


OPS CONTROLLER CARE

information on these items, please refer to the "Control Strategy" and "Switching
Logic" sections.

Create OPS Subsystem Controller


Prerequisites The OPS controller has been created.

Procedure 1. In the C-bus part of the network tree, click on the OPS controller.

2. Click right mouse key and with left mouse key, click on Create OPS
Subsystem Controller in the context menu

Or, click menu item Controller, then submenu items OPS and Create OPS
Subsystem Controller.

RESULT: The OPS subsystem controller is assigned to the OPS


controller in the C-bus part of the network tree.

3. On the OPS Properties tab on the right, enter/change name in the Sub
Controller Name field.

4. In the Sub Controller Address field, enter/change subcontroller address.

5. Continue by creating OPS points as described in the "Create OPS Point(s)"


section.

Create OPS Point(s)

Procedure 1. In the C-bus part of the network tree, click on the OPS subsystem controller.

2. Click right mouse key and with left mouse key, click on Create OPS Point in
the context menu

Or, click menu item Controller, then submenu items OPS and Create OPS
Point.

RESULT: The OPS point is assigned to the OPS subsystem controller in


the C-bus part of the network tree.

EN2Z-0937GE51 R0518 738


CARE OPS CONTROLLER

3. On the OPS Properties tab on the right, define settings as follows:

4. In the Address field on the right, enter address for OPS point.

5. Under Scaling, enter value for:

Factor
Defines factor for measurement value amplification

Offset
Defines value for Offset

Value Format
Defines format necessary for compatibility with OpenLink projects.

Scan Priority
Defines whether the point should be scanned with higher priority than others,
1: = normal, >1: = high priority

6. Under Enhanced, check desired options by clicking corresponding check box.

Readable
From OPS point of view, the value is readable

Writeable
From OPS point of view, the value is writeable

Periodic Write
From OPS point of view, the value will be periodically written

739 EN2Z-0937GE51 R0518


OPS CONTROLLER CARE

Map CARE Datapoints to OPS Points


Mapping CARE datapoints to OPS points can be done in the following two ways:

• Automatic Mapping by assigning the OPS Attribute to the CARE datapoint


(logical plant tree). When mapping a CARE point automatically, the datapoint
will be mapped to an unmapped OPS point with the same name as the CARE
user address. If such an OPS point does not exist, it will be automatically
created.

• Manual Mapping by assigning the OPS Manual Mapping attribute to the CARE
datapoint (C-bus part of the network tree) OPS Manual Mapping is a Pre-
Definition. The datapoint can be mapped later to any unmapped OPS point
available in the OPS controller (logical plant tree).

Logical plant tree C-Bus part of network tree

Attribute Selection

OPS None (default)


CARE datapoint OPS point OPS point
(Automatic Mapping) automatically
created
on
lecti
e
in tS
Po

OPS Manual Mapping CARE datapoint Point Selection


CARE datapoint OPS point
(Manual Mapping) for mapping
from OPS template
Po
in tS
ele
cti
on

OPS point
manually
created

OPS Point Naming Terminology


Regarding the Mapping any OPS point is defined by the following attributes:

• Description
• Address
• ID
• Mapped CARE datapoint

The most important attribute is the unique ID number, which will be automatically
defined for the OPS point when it was created.

EN2Z-0937GE51 R0518 740


CARE OPS CONTROLLER

The ID number cannot be changed, whereas the description, the address and the
CARE datapoint assignment can be changed.

This results in the following:

A CARE datapoint can only be mapped to one specific OPS point (ID). For this
OPS point, the description, the address and the CARE datapoint assignment can
be changed. Two different OPS points can have the same description and/or user
address, but one CARE datapoint cannot be mapped to multiple OPS points.

When creating an OPS point automatically, the datapoint will be mapped to an


unmapped OPS point with the same name as the CARE user address. If such an
OPS point does not exist, it will be automatically created.

Automatic Mapping

Automatic Mapping between CARE datapoints and OPS points includes the
following 2 steps:

a. Assign ´OPS` attribute to the datapoint in the logical plant tree.

b. Open OPS Point Information dialog box or shift to C-bus part in the C-
bus part of the network tree and enter OPS attributes such as address,
Offset, etc. for the OPS point.

Procedure 1. In the logical plant tree, click on the datapoint, you want to have made an OPS
point for, in this case for AI1.

RESULT: On the right, the datapoint attributes are displayed in itemized


display.

2. From the OPS Point drop-down listbox, select OPS Point.

RESULT: The datapoint will be automatically mapped to an existing or newly


created OPS point with the same name as the datapoint. In the
logical plant tree, the CARE datapoint is displayed in yellow. In the
C-bus part of the network tree, the created OPS point is added and
indicated by a blue icon. To complete OPS interface creation,
additional attributes need to be entered by doing one of the
following:

4. Click on the dotted button right to the OPS point drop-down listbox.

RESULT: The OPS Point Information dialog box displays.

5. Enter Address, Scaling and Enhanced attributes. For detailed description of


the attributes refer to the "Create Subsystem Point" section.

Or,

6. To access all OPS points for editing, go to the C-bus part in the C-bus part of
the network tree, browse to the subsystem controller and click on the OPS
point.

Manual Mapping

Manual Mapping between CARE datapoints and OPS points includes the following
3 steps:

a. Assign ´OPS Manual Mapping` attribute to the datapoint in the logical


plant tree.

741 EN2Z-0937GE51 R0518


OPS CONTROLLER CARE

b. Go to the C-bus part of the network tree and map particular OPS point
to this CARE datapoint.
c. Enter OPS attributes such as address, offset, etc. for the OPS point.

Procedure 1. In the logical plant tree, click on the datapoint, you want to have made an OPS
point for, in this case AI2.

RESULT: On the right, the datapoint attributes are displayed in itemized


display.

3. From the OPS Point drop-down listbox, select ´OPS Manual Mapping`. OPS
Manual Mapping is a pre-definition. The datapoint can be mapped later to any
unmapped OPS point available in the OPS controller (C-bus part of the network
tree).
NOTE: No OPS point will be created.

4. Browse to the OPS subsystem controller in the C-bus part of the network tree.

5. In the tree, select OPS point to be mapped. OPS point can originate from the
OPS template, manual creation in the tree or by automatic creation.

Mapped points are indicated by the blue icon, unmapped points are
indicated by the icon.

6. On the right under Point Mapping, select CARE datapoint from the CARE
Datapoint drop-down listbox.

RESULT: The CARE datapoint is mapped to the OPS point. In the C-bus part
of the network tree, the mapped point is indicated by the blue
icon.

Unmap OPS Points


Procedures

Logical Plant Tree 1. In the logical plant tree, click on point you want to unmap.

RESULT: On the right, the datapoint attributes are displayed in itemized


display.

EN2Z-0937GE51 R0518 742


CARE OPS CONTROLLER

2. From the OPS Point drop-down listbox, select ´None`.

RESULT: The OPS will be unmapped.

C-bus part of the network tree 1. In the C-bus part of the network tree, click on point you want to unmap.

RESULT: On the right, the OPS point attributes are displayed in itemized
display.

743 EN2Z-0937GE51 R0518


OPS CONTROLLER CARE

2. From the CARE Datapoint drop-down listbox, select ´None`

RESULT: The OPS will be unmapped.

EN2Z-0937GE51 R0518 744


CARE OPS CONTROLLER

Move Subsystem Point


Subsystem points can be moved between subsystem controllers by Drag&Drop in
the C-bus part of the network tree.

Procedures 1. To move points in the current OPS controller, browse to the OPS subsystem
controller in the C-bus part of the network tree.

2. Click on OPS point and move it by Drag&Drop to the desired subsystem


controller.

Replicate Plant
For streamlining the engineering process of OPS controllers, a plant can be
replicated multiple times after the mapping has been done.

Replication will include:

• CARE datapoints
• Control strategies and switching tables, if assigned to the plant.
• OPS Subsystem controllers and OPS points

After replication the plants will be available as unattached plants. After attaching the
plants a "big" OPS interface will have been created.

CARE Datapoints

OPS Controller O-Link

OPS Interface o1 o2 o4 o3 o10 o11 o12 o13 o20 o21 o22 o23

M-Bus M-Bus M-Bus

Water- Heat- Water- Heat-


Water- Heat-
Meter Meter Meter Meter
Meter Meter
2 2 3 3

745 EN2Z-0937GE51 R0518


OPS CONTROLLER CARE

CARE Datapoints

OPS Controller

o1 o2 o4 o3 o10 o11 o12 o13 o20 o21 o22 o23


OPS Interface

M-Bus M-Bus

Water- Heat- Water- Heat-


Water- Heat-
Meter Meter Meter Meter
Meter Meter
2 2 3 3

Please, refer to the "Plants, Defintion and Management" section for detailed
information on how to replicate a plant.

Import/Export OPS Controller


An OPS controller can be imported, respectively exported at two points:

• From within the OPS Template Editor


• From within the C-bus part of the network tree.

When importing/exporting the OPS controller from the OPS Template Editor a pure
template without any mapping information will be imported/exported whereas when
importing/exporting the OPS controller from within the C-bus part of the network
tree an OPS controller (OPS device) including all mappings will be
imported/exported.

This means for importing into the OPS device that all current OPS points will be
deleted and replaced by the imported OPS points. Mappings between imported
OPS points and CARE datapoints of the same name will be re-established.

For importing into the OPS template, the current OPS template data are deleted
and replaced by the imported OPS controller data. No mapping information will be
imported.

Import OPS Controller


Migration Strategy Note If the Import OPS controller function is part of the migration strategy, first perform
steps 1 through 7 from the "Migration Procedure" section.

Import into Current OPS Controller 1. To import OPS controller data into the current OPS controller, browse to the
OPS controller in the C-bus part of the network tree.

2. Continue with "Common Steps".

EN2Z-0937GE51 R0518 746


CARE OPS CONTROLLER

Import into OPS Template 1. To import OPS controller data into the OPS template, open the OPS Template
Editor (see "OPS Template Editor" section).

2. Continue with "Common Steps".

Common Steps 3. In the C-bus part of the network tree respectively in the OPS template editor
tree, click on OPS controller, respectively on OPS template.

4. On the OPS toolbar, click .

RESULT: The Import OPS Controller dialog box displays.

5. Navigate to the folder where the OPT file resides and select it.

6. Click Open button.

RESULT: The Import OPS Controller Options dialog box displays.

7. Select desired option.

RESULT: A message box displays. Note that the existing OPS device
(controller) data will be overwritten when selecting Yes.

8. Click Yes button.

RESULT: If the import was successful, the following message box informs
you about that .

9. Click OK button.

RESULT: The OPS information imported is displayed in the tree on the


left.

Export OPS Controller


Based on Current OPS Controller 1. To export the OPS controller data based on the current OPS controller, first
translate the OPS controller.

2. Browse to the OPS controller in the C-bus part of the network tree.

747 EN2Z-0937GE51 R0518


OPS CONTROLLER CARE

3. Continue with "Common Steps".

Based on OPS Template 1. To export the OPS controller data based on the OPS template, open the OPS
Template Editor (see OPS Template Editor section).

2. Continue with "Common Steps".

Common Steps 3. In the C-bus part of the network tree respectively in the OPS template editor
tree, click on OPS controller, respectively on OPS template.

4. On the OPS toolbar, click .

RESULT: The Export OPS Controller dialog box displays.

5. Navigate to the folder where the OPT file should be saved.

6. Into the File Name field, enter file name.

7. Click Save button.

RESULT: A message box informs you about the successful export of the
OPS controller.

8. Click Save button.

Migration Strategy
CARE 3.01.00 and higher allows upgrading existing OLink projects to OPS projects.
The exported data of the old OLink project data can be imported in the same file
format (OPT).

EN2Z-0937GE51 R0518 748


CARE OPS CONTROLLER

An old OLink Project consist of two main elements:

• The CARE database (version 2.01.00 or lower) where the OLink controllers and
also the datapoints are stored.
• The ZM 5002 database (ZM5002 project) which fits to this CARE project.

During the Upgrade the attached XLink plant including control strategies and
switching logics gets to Air-conditioning. The XLink controller will be transformed to
the OPS controller type and the XLink datapoint technical address gets to standard
technical address (see steps 7 and 8).

NOTE: An unattached XLink plant will no longer be supported.

Migration Procedure

CARE 2.01.00 or lower Modified / ZM 5002 Tool

Datapoint Information Import

CARE 2.01.00 ZM 5002


Database Database
Backup Backup

OLink File Generation


RACL Generation

Controller Files

OPT File
IPL File

RAL File

1. You need to have CARE 2.01.00 installed first with the OLink controller project
in the database.

2. Translate the controller.

3. Start the modified ZM 5002 Tool, which will be provided by the CARE Team
and import the CARE controller files.

4. In the modified ZM 5002 tool an additional menu item will be available which
allows creating (export) the OPT file (opt file = ops file plus binary code).

5. Make a database backup of the CARE 2.01.00 database or a project backup.

6. Install CARE 3.01.00 or higher (CARE with OPS support).

749 EN2Z-0937GE51 R0518


OPS CONTROLLER CARE

7. Within the installed CARE version upgrade the CARE 2.01.00 database (or
project) to the highest CARE version and then restore this database (or
project).

RESULT: If an old XLink controller was found during the upgrade, the
Select XLink, OLink or OPS controller type dialog box
displays. An old XLink controller can be kept as XLink type or
transformed to an OLink or OPS controller.

8. Select OPS, or, if you want to transform the controller to the OLink type, select
OLink.

9. Click OK button.

RESULT: The upgrade will be finished.

EN2Z-0937GE51 R0518 750


CARE OPS CONTROLLER

CARE 2.01.00 or lower

CARE 2.01.00
Database

CARE Database or Project Upgrade and Restore


Modified / ZM 5002 Tool

ZM 5002
Database
Backup

OPT File

o rt
nk Imp
CARE 3.01.00 or higher OLi

CARE 3.01.00
or higher
Database

10. In the C-bus part of the network tree, click on the OLink controller.

11. Click right mouse key and with left mouse key click on Import OPS Controller
in the context menu (see "Import OPS Controller" section).

12. Import the OPT file. All mappings between datapoints to OLink points will now
be available.

13. From menu item Controller, click drop-down item Tools, then submenu item
NO/NC Upgrade, since the OPS controller is only supported by the new
NO/NC mechanism.

RESULT: Migration is completed.

751 EN2Z-0937GE51 R0518


OPS CONTROLLER CARE

EN2Z-0937GE51 R0518 752


CARE FALCON AND EAGLE CONTROLLERS

FALCON AND EAGLE CONTROLLERS


CARE supports two BACnet controllers, the FALCON and the EAGLE controller.

System Architecture FALCON and EAGLE controllers provide basic BACnet functions for plant controls.
The FALCON controller allows plant control on BACnet IP level. The EAGLE
controller allows plant control on BACnet IP and additionally on BACnet MS/TP
(Master Slave Token Passing) level. Both controllers also support LonWorks
building technology. For this, the EAGLE controller uses an external IF-LON
interface.

For detailed information on the features and differences of these two controllers,
please refer to the corresponding Product Data, EN0Z-0962GE51 (EAGLE
controller) and EN0Z-970GE51 (FALCON controller).

The FALCON and EAGLE controllers as part of the CentraLine System BACnet
Architecture are shown in the following schematic.

CARE Steps For BACnet controller engineering, some steps are common with the CARE
standard steps such as:

• Creating project
• Creating datapoints
• Terminal assignment
• Assigning panel I/O modules / LON devices to controller

And yet, other individual steps will be performed differently when engineering an
HVAC application running in a BACnet controller, for example:

• Creating controller

753 EN2Z-0937GE51 R0518


FALCON AND EAGLE CONTROLLERS CARE

• Creating plant
• Defining general BACnet-bus properties
• Representing the BACnet topology by creating a skeletal network architecture
consisting of subsystems, subnets and channels
• Defining IP address ranges for controllers
• Modeling the network architecture by creating, moving or deleting subsystems,
subnets, channels and 3rd party BACnet devices
• Creating schedules and calendars
• Creating control strategy and switching logic
• Configure system status properties
• Configure email alarming
• Setting up controllers
• Defining notification classes for adapting the alarming to the ARENA AX Central
and 3rd party BACnet clients
• Defining user access rights

The common and individual engineering steps of the two controllers are described in
the following sections.

NOTE: Before starting the engineering of BACnet controllers with CARE, we strongly
recommend to get familiar with BACnet technology by reading appropriate basic
literature.

Create BACnet Project


Please refer to the PROJECTS DEFINITION AND MANAGEMENT chapter for
detailed information on how to create and edit a project.

Create BACnet Controller


NOTE: It is recommended to represent the network topology (BACnet IP, BACnet
IP - BACnet MS TP, BACnet MS TP) of the building by defining the
subsystems/subnets in the network tree before creating controllers. This
ensures that you can select the dedicated target network, subsystem and
subfolder for the controller when creating the controller. Otherwise, you
eventually must position the controller in the network tree manually if the
target location was not available from the beginning (see "BACnet
Network Engineering" section for detailed information on subnets,
subsystems and channels)

Purpose To create a BACnet controller. The BACnet controller will be placed into a BACnet
IP Bus subnet selectable when creating the controller. By default, the subnet called
´IP-Subnet 1` is available and can be selected.

Procedure 1. Click menu item Controller, then submenu item New.

Result: The New Controller dialog box displays.

EN2Z-0937GE51 R0518 754


CARE FALCON AND EAGLE CONTROLLERS

2. In the Controller Name field, enter the controller name.

3. From the Subsystem/Subnet Name drop-down list box, select the desired
subnet. By default, IP-Subnet 1 is selected (see "BACnet Network Engineering"
section for detailed information on subnets, subsystems and channels).

4. From the Controller Number drop-down list box, select the controller number.

5. From the Controller Type drop-down list box, select the controller type.

6. (applies to FALCON controllers only):


Check FALCON 2.0 application format if you want to apply event enrollments to
any of the following items: plant, controller, email alarming, and datapoints,
enable email alarming in general, and/or if you want to use the default schedule
function for schedules. Check FALCON 1.0 application format if
you use controller versions lower than 2.0.

NOTE: Once the Excel 2.0 application format is selected you cannot switch
back to the Excel 1.0 application format after the controller was
created.

755 EN2Z-0937GE51 R0518


FALCON AND EAGLE CONTROLLERS CARE

7. From the Location drop-down list box, select the country code.

8. Under Units of Measurement, select the measurement units under International


and Imperial by selecting the corresponding radio button.

9. Under Interfaces, select the buses for the RS485 1 and RS485 2 interfaces by
selecting Panel Bus, BACnet MS/TP Bus, or Modbus from the drop-down list
boxes. You can select ´None` if the interface should not be connected. Please
refer to the "BACnet Network Engineering" and the "Set Global CARE Options"
sections that describe the effects on the network structure depending on the
selection here.

10. Check the Support LON checkbox if the controller should control LON devices
additionally.

11. Check the Support M-Bus checkbox if the controller should control M-Bus
devices additionally.

12. Click the OK button.

RESULT: The controller is added to the logical plant tree on the left. Its
interfaces are added to the Interfaces folder below the controller
icon. On the Properties tab on the right, the properties of the
controller are displayed. To modify properties, please refer to the
"Display/Modify BACnet Controller Properties" section.
The System Status, E-Mail Alarming, Grid, Setup and Terminal
Assignment tabs provide further mandatory and optional
functions of the created controller. Please refer to the
corresponding sections for detailed information.

EN2Z-0937GE51 R0518 756


CARE FALCON AND EAGLE CONTROLLERS

Display/Modify BACNet Controller Properties


Purpose View and/or change controller information such as name, controller number, units of
measurement, counts, execution speed categories, interfaces, LON support and
target I/0 hardware.

Procedure 1. In the logical plant tree, click on the controller.

2. On the right pane, click on the Properties tab.

RESULT: On the Properties tab on the right, the following properties of the
controller are displayed:

757 EN2Z-0937GE51 R0518


FALCON AND EAGLE CONTROLLERS CARE

Controller Name
Change the name if desired.

Controller Number
To change the controller number, see step 3.

Subsystem Name
Displays the name of the subsystem.

Subnet name
Displays the name of the subnet.

Controller Type
Displays the controller type.

Location
To change the country code, select desired country code from
the drop-down listbox.

Units of Measurement
To change the measurement units, select desired radio button.

Hardware Type
Displays selected controller hardware type (for details see
Product Data EN0B-0970GE51).

Counts
Displays the counts of datapoint types such as AIs, BIs etc, the
number of hardware points and the number of schedules.

Execution Speed Categories

EN2Z-0937GE51 R0518 758


CARE FALCON AND EAGLE CONTROLLERS

Displays the speed categories in ms. An execution speed


category (target cycle time) defines how often the loop will be
automatically executed by the controller. Execution speed
categories are grouped in the following categories: Slow,
Medium, Fast, Very Fast. Each control loop is assigned to one of
these categories (see “Set Execution Speed Categories”
section).

NOTE:
The execution speed category should not be exceeded during
control loop execution. Any changes will affect all control loops
assigned to the corresponding category.

If a category's actual execution time displayed in the Eagle


HTML Interface is permanently greater than the corresponding
execution speed category, the controller is overloaded and the
execution speed category should be changed by increasing it to
higher values than the actual execution time.

To change a speed category, enter the desired value. Note that


the default values can only be increased but not decreased.

High Priority
For small application parts with few IOs only, the Very Fast
RACL execution category should have the highest priority. For
this purpose, the "Very Fast" execution speed defined on the
Controller Properties tab can be set to the highest priority by
checking the "High Priority" check box.

Interfaces
Displays the buses connected to the RS485 1 and RS485 2
interfaces (Panel Bus, BACnet MS/TP Bus, Modbus or None).

Support LON
Check the Support LON checkbox if the controller should control
LON devices additionally. Uncheck the Support LON checkbox if
the controller should not support LON functionalities.

Support M-Bus
Check the Support M-Bus checkbox if the controller should
control M-Bus devices additionally. Uncheck the Support M-Bus
checkbox if the controller should not support M-Bus
functionalities.

Enable Web Server


If checked, this option provides access to a BACnet controller
via Web Interface.

Enable Comfortable Login


If checked, this option provides the login to the web interface
without the necessity to enter user name and password each
time you are logging in.

CAUTION
If checked, make sure that the controller is operated in a
closed network or VPN to avoid misuse through cyber
attacks or easy login by other persons not knowing your
password and user name.

Enable QVGA Pages If checked, the web pages will be


displayed in QVGA (quarter VGA = 320 pixels by 240 pixels)
resolution. This is necessary for the proper display of the web
pages in the CL Touch panel.

759 EN2Z-0937GE51 R0518


FALCON AND EAGLE CONTROLLERS CARE

Modify Target I/O Hardware


Change the target I/O hardware for the EAGLE controller if
desired as described in the following.

4. To change target I/O hardware, click desired button:

Panel I/O (CLIOP8..)


(applicable to EAGLE only)
Hardware points of this plant will be assigned to CLIOP8.. modules (panel bus).

On Board I/O
(applicable to EAGLE only).
Hardware points of this plant will be assigned to the controller's internal on
board I/O terminals.

Distributed I/O (CLIOL8..)..


(applicable to EAGLE only).
Hardware points of this plant will be assigned to CLIOL8.. modules (LonWorks-
bus).

Open LON
(applicable to EAGLE only).
Hardware points of this plant will be boardless, that is, unassigned

RESULT: At once all plants will be automatically detached, all empty


hardware modules will be removed and the plant automatically
reattached to the selected target hardware. All datapoint attributes
remain unchanged except the technical address.

5. Click on the controller in the logical plant tree.

Set Execution Speed Categories

The execution speed category (also called cycle time category in the Eagle HTML
Interface) defines the (target) time in ms after a control loop is restarted
automatically.

Execution speed categories are grouped in the following types with descending
priority:

• Very Fast.
• Fast
• Medium
• Slow

In other words, a control loop which has the very fast category assigned, is executed
more often in the same time than a control loop which has a lower category
assigned, for example medium.

Each control loop is assigned to one of these categories. Any changes done to the
execution speed category will affect all control loops assigned to the corresponding
category.

The controller executes multiple control loops simultaneously (multitasking). There is


a dynamic relation between the execution speed categories as shown in the
following diagram:

EN2Z-0937GE51 R0518 760


CARE FALCON AND EAGLE CONTROLLERS

Execution
Speed
Category

Very Fast
Execution speed category (400 msec) 100 100 100 100 100
Actual Execution Time (300 msec)

Slow
Execution speed category (2000 msec) Time (msec)
Actual Excecution Time (500 msec) 500 1000 1500 2000

Execution Speed Category

Actual Excecution Time

100 msec remaining time in Very Fast category =>


500 msec execution time in Slow category

The diagram illustrates, that the degree of execution of a control loop having a slow
category assigned, depends on the remaining time (=execution speed category
time minus actual execution time) provided by a control loop executed in very fast
category.

The execution speed category should not be exceeded during control loop
execution. If a category's actual execution time is permanently greater than the
corresponding execution speed category, the controller is overloaded and the
execution speed category should be changed by increasing it to higher values than
the actual execution time.

IMPORTANT
It is recommended to set the execution speed categories to between 30 %
and 50 % higher than the actual execution times in order to make sure that
control loops having medium and slow execution speed categories
assigned can be executed in the appropriate time.

NOTE: The settings done in the Eagle HTML interface will be overwritten after a
download with CARE. Hence, upload the application into CARE using
Excel XW Online after the plant has been setup.

Upgrade FALCON Controller


Purpose Upgrade a FALCON controller to an EAGLE controller.

Procedure 1. In the logical plant tree, click on the controller.

2. On the right pane, click on the Properties tab.

761 EN2Z-0937GE51 R0518


FALCON AND EAGLE CONTROLLERS CARE

3. On the Properties tab on the right, select ´Eagle` from the Controller Type drop-
down list box.

RESULT: The Upgrade Controller dialog box displays.

EN2Z-0937GE51 R0518 762


CARE FALCON AND EAGLE CONTROLLERS

4. In the Upgrade Controller dialog box, select the Subsystem/Subnet, the


controller type and the Interface.

5. Click OK button.

RESULT: The Properties tab re-displays. The controller type has been
changed to Eagle as indicated in Controller Type. But the name
of the controller is still the name of the upgraded FALCON
controller.

6. Change the name of the upgraded controller in Controller Name.

763 EN2Z-0937GE51 R0518


FALCON AND EAGLE CONTROLLERS CARE

Create Plant

Purpose Define a plant name and the units of measurement.

When creating a plant, you can instantly attach the plant to a controller or create it
unattached for later attachment.

For detailed information on the plant attachment process, please refer to the
"Attach/Detach Plant" section in the CONTROLLERS DEFINITION, ATTACHMENT,
AND MANAGEMENT chapter.

Procedure 1. In the logical plant tree, click on the controller, to which you want attach the
plant.
Or, if you want to create an unattached plant for later attachment, click on the
project.

NOTE: If the plant is created on controller level, it is not possible to select the
units of measurement. Those plant properties can only be selected if
the plant is created on project level (not attached to any controller).

2. Click menu item Plant, then drop-down item New.

RESULT: The New Plant dialog box displays.

3. Type a plant name in the Name field.

4. Type a description in the Description field if desired.

EN2Z-0937GE51 R0518 764


CARE FALCON AND EAGLE CONTROLLERS

5. Under Units of Measurement, select the desired type for the plant, International
(metric) or Imperial. This selection tells the Control Strategy functions which
type of inputs to accept, Celsius or Fahrenheit. Units of Measurement can only
be selected if the plant is not attached to the controller yet.

6. From Preferred Target Hardware select the target hardware under Panel I/O
(CLIOP8..), Distributed I/O (CLIOL8..) and Open LON. Distributed I/O
(CLIOL8..) and Open LON can only be selected if the controller supports LON
functionalities (Support LON must be checked in the Controller Properties tab).

– Distributed IO: XFL modules with automatic assignment


– OPEN LON: XFL modules with manual assignment

7. Click OK.

RESULT: If the new name is acceptable, software closes the dialog box. In
the logical plant and network tree, the plant is added below the
controller (plant attached) or below the project (plant unattached).
Below the plant level, the Schedules and Control Loops folders are
automatically created. For applying these functions please refer to
the Schedules and Calendars and the Control Loops sections.

765 EN2Z-0937GE51 R0518


FALCON AND EAGLE CONTROLLERS CARE

Create Datapoints

Procedure 1. If not already highlighted in the logical plant tree, select the plant.

2. Click menu item Plant, then drop-down item Create HW/SW Points.

Or, click right mouse key and with left mouse key, click on
Create HW/SW Point(s) in the context menu.

RESULT: The New Point dialog box displays.

3. From the Type drop-down listbox, select the datapoint type.

4. In the Number field, enter the number of points to be created and in the User
Address fields enter the name of the datapoint(s) to be created. If you are
adding more than one point, software automatically numbers the corresponding
user addresses sequentially to guarantee unique user addresses. For example,
if you enter pt and request two points, software creates two points named pt1
and pt 2. Only use alphabetic characters. Do not use blanks.

5. From the Default HW Interface drop-down listbox, select the interface to which
the datapoints should be assigned by default:

– On board
points will be assigned to the appropriate board according to the point
type

– Panel bus <RS Interface name>


points will be assigned to the RS interface

– First free terminal


applies to DI points and Mixed I/O board usage. If this option is selected,
DI points will be assigned to the first free terminals on AI boards without
the creation of new DI boards.

– Boardless
points will not be assigned to boards (strongly recommended for M-Bus
configurations)

6. Click OK.

RESULT: In the upper example, the datapoints are added to the Analog Input
type folder in the logical plant tree.

EN2Z-0937GE51 R0518 766


CARE FALCON AND EAGLE CONTROLLERS

7. Depending on the chosen Default HW Interface, the datapoints are


automatically assigned to the appropriate module(s). If LON modules are used,
continue by mapping datapoints to NVs of appropriate devices as described
under "Assign LON devices (Binding)" section.

Add Control Strategy / Switching Logic to Plant


For detailed information please refer to the CONTROL LOOPS section.

Create Fast Access Lists


Purpose Fast access lists are created in CARE for representing suited information to
dedicated users (e.g. electrician, project engineer, and tenant) on the controller HMI
and web interface.

Fast access lists are lists of grouped datapoints and/or parameters mostly
representing a logical part of the application. This allows quick access to a particular
part of the application on the controller HMI and web interface via the corresponding
datapoints and/or parameters.

A fast access list can be a list of certain datapoints, e.g. all outputs by using a filter
template, or a list showing the impact of selected parameter values on datapoints.

Fast access lists can be created on controller level and on plant level. In plant
related fast access lists, you can only view datapoints/parameters of this particular
plant whereas controller related fast access lists can comprise
datapoints/parameters of different plants of the controller.

Fig. 1. Fast access lists overview on controller HMI

767 EN2Z-0937GE51 R0518


FALCON AND EAGLE CONTROLLERS CARE

Fig. 2. Single fast access list on web interface

Fig. 3. Fast access list creation in CARE

Procedure

1. To create the fast access list, expand the tree and browse to the controller.

2. Click the Fast Access Lists folder in the tree.

RESULT: On the right pane, the Fast Access Lists tab displays which
shows all fast access lists created. The Fast Access Lists tab
corresponds to a so-called "container" fast access list. The name
of the container fast access list is not visible on the controller
HMI or on the web interface. But each "real" fast access list
subsequently created is embedded in the container fast access
list and will be visible on the controller HMI and the web
interface.

EN2Z-0937GE51 R0518 768


CARE FALCON AND EAGLE CONTROLLERS

3. Right-click the Fast Access Lists folder in the tree, and then click Create Fast
Access List.

RESULT: A blank fast access list is created. On the right pane you will
define the fast access properties and its column configuration.

On the Properties tab, you will do the following:

769 EN2Z-0937GE51 R0518


FALCON AND EAGLE CONTROLLERS CARE

• enter a name
• define access rights
• set the fast access list type (Filter Template or Selected Points/Parameters)
• add datapoints and parameters (Selected Points/Parameters only)

On the Columns Configuration tab, you will do the following:

• enable/disable columns for datapoints and parameters to be displayed or


hidden in the web interface and the controller HMI

4. On the Properties tab, rename the fast access list in the Name field, e.g. enter
´Main`

5. From the Read Access Level and Write Access Level drop-down list boxes,
select the user levels that should have read and write access of the fast access
list. Note that only users logged in with the same or a higher password level
than the defined access level can view or edit this fast access list on the
controller HMI and web interface.

6. Define the fast access list type by doing one of the following:

a. select Selected Points/Parameters radio button (default).


This option allows watching the impact of changed parameter values on
datapoints. The parameter values will be changed online.
b. select Filter Template.
This option allows quickly displaying certain datapoints of plants

7. If you have selected the fast access list type ´Selected Points/Parameters`,
continue with step 8. If you have selected the fast access list type ´Filter
Template`, continue with step 21.

8. If you have selected the fast access list type ´Selected Points/Parameters`, click
Add under Datapoints.

RESULT: The Select data points dialog box displays.

EN2Z-0937GE51 R0518 770


CARE FALCON AND EAGLE CONTROLLERS

9. Expand the tree, and then select the datapoints.

10. Click OK.

RESULT: The selected datapoins are added to the Datapoints list. The
following properties are displayed:

• plant name
• point type
• point name
• alias name (optional)

771 EN2Z-0937GE51 R0518


FALCON AND EAGLE CONTROLLERS CARE

11. If desired, enter alias names for the datapoints by clicking in the corresponding
cell and entering the alias name. If an alias name is entered, only the alias
name but not the point name will be visible on the controller HMI and web
interface.

12. If desired, you can define a filter for each property (Plant Name, Point Type
etc.) of the Datapoints list by entering a search string or by selecting criteria
from a list in the first row below the column title. By default, no filter is set as
indicated by an asterisk *.

The filter is case-sensitive and wildcards (*) and jokers (?) can be used. The
asterisk * can only be used at the beginning or the end of the search entry. By
default, the filter shows *, displaying all items. If any text is entered without
wildcards, software searches for the exact match.

13. Under Parameters, click Add.

RESULT: The Select parameters dialog box displays.

EN2Z-0937GE51 R0518 772


CARE FALCON AND EAGLE CONTROLLERS

14. Expand the tree, and then select the parameters.

15. Click OK.

RESULT: The selected parameters are added to the Parameters list. The
following properties are displayed:

• plant name
• control loop name
• parameter name
• symbol (type
• parameter path
• alias name (optional)

773 EN2Z-0937GE51 R0518


FALCON AND EAGLE CONTROLLERS CARE

16. If desired, enter alias names for the parameters in the same way as described
for the datapoints in step 11.

17. If desired, you can define a filter for each property in the same way as
described for datapoints in step 12.

18. Under Loop Object Parameters, click Add.

RESULT: The Select parameters dialog box displays.

19. Expand the tree, and then select the parameters.

EN2Z-0937GE51 R0518 774


CARE FALCON AND EAGLE CONTROLLERS

20. Click OK.

RESULT: The selected parameters are added to the Loop Object


Parameters list. The following properties are displayed:

• plant name
• loop object name
• parameter name
• alias name (optional)

21. If desired, enter alias names for the loop object parameters in the same way as
described for the datapoints in step 11.

22. If desired, you can define a filter for each property in the same way as
described for datapoints in step 12.

23. Continue by configuring the columns display for the web interface and controller
HMI as described in step 30.

24. To save the fast access list settings, click on any spot outside the pane.

25. If you have selected the fast access list type ´Filter Template`, the following
pane displays.

Under Template Configuration, you can filter for datapoints of particular plants
to be used in the fast access list. By default, all plants and all datapoint types
are shown and pre-selected in Plant and Type. In Name, the asterisk* indicates
that no datapoints with a particular name are already filtered for display. Under

775 EN2Z-0937GE51 R0518


FALCON AND EAGLE CONTROLLERS CARE

Datapoints, the datapoints of the controller are displayed according to the filter
settings. All datapoints displayed will be part of the template (fast access list). In
Sort Order, you can sort the list of datapoints.

26. To configure the template by defining a filter, do any of the following:

a. Under Plant, select plant(s) of which datapoints you want to be displayed.


b. Under Type, select specific datapoint types to be included/excluded from the
filter.
Multi-selection by using the CTRL or the SHIFT key while selecting with the
mouse is possible.

c. Under Name, specific datapoint names can be filtered by entering a search


text. By default, all datapoints will be displayed as indicated by an asterisk *.
To display specific datapoint (names), enter the appropriate search text.
27. Click Apply.

RESULT: In Datapoints, all datapoints matching the filter criteria will be


displayed.

28. Under Sort Order, define the sort order for the datapoint list on the controller
HMI and the web interface. You can define the sort order for three columns
(First by, Then by, Then by). For each column, you can apply ascending or
descending sorting mode. Even if under Datapoints, the three columns ´Plant
Name`, ´Point Type` and ´Point Name` are permanent, you can sort for any
column provided on the Columns Configuration tab, but not displayed as
columns under Datapoints. For example, you can sort for event state, status
flags etc. (see Columns Configuration tab description, step 21).

EN2Z-0937GE51 R0518 776


CARE FALCON AND EAGLE CONTROLLERS

29. After setting the sort order options, click Apply.

RESULT: In Datapoints, the datapoints are sorted according to the


defined sort order. Note that only sort order definitions of plant
name, point type and point name will be updated in the
Datapoints list immediately. All other selections will be valid
later on the controller HMI and the web interface.

30. To configure the columns display for datapoints and parameters of the fast
access list in the controller HMI and web interface, click Columns Configuration
tab.

777 EN2Z-0937GE51 R0518


FALCON AND EAGLE CONTROLLERS CARE

By default, particular columns are checked for display in the controller HMI or
web interface. Unchecked columns will be removed (hidden) and not displayed.
Columns marked with a (*) cannot be unchecked for removal.

For the datapoints and parameter columns, check the columns you want to be
displayed and uncheck the columns you do not want to be displayed.

31. To change the order of the columns, move column(s) within the list by selecting
column in the list and clicking Move up button once, to move it one step
upward, or by clicking Move down button once to move it one step downward
doing. Multi-selection by using the CTRL or the SHIFT key while selecting with
the mouse is possible. Multiple clicking the buttons moves the column multiple
steps upwards or downwards.

EN2Z-0937GE51 R0518 778


CARE FALCON AND EAGLE CONTROLLERS

32. To save the fast access list and show the fast access list overview, click on the
Fast Access Lists folder in the tree. On the Fast Access Lists tab the newly
created fast access list is displayed. If desired, you can define a filter for each
property (Fast Access List, Type, etc.) by entering a search string or by
selecting criteria from a list in the first row below the column title. By default, no
filter is set as indicated by an asterisk *.

The filter is case-sensitive and wildcards (*) and jokers (?) can be used. The
asterisk * can only be used at the beginning or the end of the search entry. By
default, the filter shows *, displaying all items. If any text is entered without
wildcards, software searches for the exact match.

Terminal Assignment
Terminal assignment for the FALCON and EAGLE controllers follows the same
basic rules as for any other devices in CARE. For detailed information please refer
to the TERMINAL ASSIGNMENT section.

Show Datapoints in Grid


Datapoints can be displayed in a grid on the Grid tab for overviewing and editing
their properties. This can be done on project, plant, controller and datapoint type
level.

Example: Datapoints in Grid on Controller Level

779 EN2Z-0937GE51 R0518


FALCON AND EAGLE CONTROLLERS CARE

For detailed information on how to edit datapoint properties in Grid view, please
refer to Edit Points in Grid Display in the "Datapoint Editor section"

BACnet Network Engineering

BACnet Topologies
CARE supports 2 BACnet topologies based on the 2 major BACnet communication
protocols, BACnet IP and BACnet MS / TP.

NOTE: The BACnet MS/TP protocol is only supported by the EAGLE controller.

Legacy and 3rd Party Integration For integrating EAGLE controllers and BACnet 3rd party devices based on an
already existing wired building channel, a pure BACnet MS / TP bus topology will be
applied.

Plant Control To control plants by taking advantage from the complete EAGLE controller
functionality (Panel Bus, MS / TP bus), you apply the
basic BACnet / IP bus topology. If an EAGLE controller running on the BACnet IP
bus uses also the BACnet MS /TP channel via RS485 interface, it works as a router
routing packets to the BACnet devices connected to the subordinate channel.

EN2Z-0937GE51 R0518 780


CARE FALCON AND EAGLE CONTROLLERS

For detailed information on how to work with the BACnet bus topologies in CARE,
please refer to the subsequent sections.

BACnet Network Structure


By default, a BACnet project shows the BACnet bus and the LON-Works bus in the
network tree.

LonWorks For detailed information on basics of the LonWorks network structure and LonWorks
Engineering, please refer to the LonWorks Network Engineering chapter

BACnet-Bus The BACnet network as part of a project is divided in two major bus types:

• BACnet IP and
• BACnet MS/TP

BACnet IP is used for controllers with the main interface on the Ethernet. If they
have connected BACnet MS/TP channels, those are located directly under the
controller itself.

BACnet MS/TP is used for controllers with the main interface on BACnet MS/TP.

The BACnet IP Bus can be further arranged by adding any of the following
components:

781 EN2Z-0937GE51 R0518


FALCON AND EAGLE CONTROLLERS CARE

• Subsystems
• Subnets

By default, the BACnet IP Bus contains the Subnet 1.

The BACnet MS/TP bus can be further arranged by adding channels. By default the
BACnet MS/TP bus is empty. A channel must be added manually. The first added
channel is named ´BACnet MS/TP` bus by default.

Subnets represent the BACnet infrastructure of the building and contain the BACnet
controllers/devices which control that segment of the building. Subsystems are a
logical hierarchical level for grouping multiple subnets to a system requiring
communication between the different subnets.

Subnets can be created below subsystems or directly on the BACnet IP-Bus level.
Channels can be created on BACnet MS/TP level only. BACnet controllers and
devices can be placed in IP subnets and MS/TP channels only.

EN2Z-0937GE51 R0518 782


CARE FALCON AND EAGLE CONTROLLERS

By default, the BACnet IP Bus folder contains the ´IP Subnet 1` folder and no
Subsystem folder. Further created folders will be numbered continuously, for
example ´Subnet 2`, ´Subnet 3`, ´Subsystem ´1`, etc. The same applies to the
BACnet MS/TP channels.

NOTE: The default subsystems, subnets, channels and device names are freely
editable.

Design and Configure BACnet Network


Purpose To structure the BACnet network according to conditions in the building.

This includes:

• Definition of general BACnet-bus properties


• Definition of BACnet IP bus properties
• Definition of BACnet MS/TP bus properties
• Creation of subsystems (optional)
• Creation of subnets and definition of IP address ranges for controllers
• Creation of controllers
• Creation of BACnet 3rd party devices
• Arrangement of controllers and BACnet 3rd party devices in this structure

Define General BACnet Bus Properties

Purpose To define the BACnet-Bus settings (e.g., APDU length, APDU time out, etc.) for the
BACnet controller(s) and 3rd party BACnet devices.

Procedure 1. With left mouse button, select the BACnet icon in the network tree.

RESULT: The general BACnet-bus properties are displayed on the right


Properties pane.

783 EN2Z-0937GE51 R0518


FALCON AND EAGLE CONTROLLERS CARE

2. Enter/change values and select options for the following general BACnet bus
properties:

NOTE: When changing any of the following properties, you must update the
controller by downloading the settings and/or application.

MaxAPDU Length
The max. size of data in one packet. For BACnet/IP, the maximum is 1476, for
BACnet MS/TP, the maximum is 480. It may be necessary to reduce the size if
packets are transmitted over routers or tunnelling to MS/TP devices.

APDU Segment Timeout


The timeout in msec for one single packet (of a segmented) message.

APDU Timeout
The timeout in msec for the whole message (all packets). For proper
communication with EBI, the value must be set to 5800 msec.

Number of APDU Retries


Number of retries sent by the BACnet controller to another device if this device
does not answer. Too many retries will slow down communication.

Max. Segments Accepted


The maximum number of packets for a segmented message. The product of
Max Segments Accepted * Max APDU Length shall not exceed a limit of 16000
bytes.

Segmentation Supported
Specifies if the BACnet controller supports messages with more than one
packet:
– Both = segmentation in both directions
– Transmit = BACnet controller cannot receive segmented messages
– Receive = BACnet controller can receive but not send segmented
messages
– None = BACnet controller can neither receive nor send segmented
messages

EN2Z-0937GE51 R0518 784


CARE FALCON AND EAGLE CONTROLLERS

Object synchronization max. send time


The Object synchronization max. send time indicates the maximum period of
time that expires before a sync message is sent. The max. period of time before
a synchronization is repeated, is

object synchronization max. send time * (number of calendars + number of


users + 2)

The calendar and user objects will be automatically synchronized by the


controllers. Checking ´Disable` disables the synchronization.

In CARE projects with multiple BACnet controllers, each controller instantly


sends a private transfer broadcast message if calendar or user data are
created, changed or deleted. In addition, synchronization messages are sent
cyclically with the max. send time. This keeps all other controllers up-to-date but
may cause high bus load in huge plants with multiple controllers. If the CARE
project contains only one controller is recommended to disable the
synchronization for objects.

Alarm synchronization max. send time


The Alarm synchronization max. send time indicates the maximum period of
time that expires before the alarms will be automatically synchronized by the
controllers. Checking ´Disable` disables the synchronization.

In plants with multiple BACnet controllers, each controller instantly sends a


private transfer broadcast message if the number of point in alarms changes
from 0 to >0 or >0 to 0. In addition, the number of points in alarm in a controller
is broadcasted cyclically with the max send time. This keeps all other controllers
up-to-date (synchronization) but may cause high bus load in huge plants with
multiple controllers. If the CARE project contains only one controller is
recommended to disable the synchronization.

With these functions you can control the bus load in order to avoid a high bus
load which often results in limited performance. If negative effects are noticed
on the bus, the value(s) should be increased.

Define BACnet IP Bus Properties

Purpose To define the settings for the BACnet IP network (e.g. network number, ports, etc.).

Procedure 1. With left mouse button, select the BACnet IP Bus icon in the network tree.

RESULT: The BACnet IP network properties are displayed on the right


Properties pane.

785 EN2Z-0937GE51 R0518


FALCON AND EAGLE CONTROLLERS CARE

2. Enter/change text or values and select options for the following BACnet IP Bus
properties:

NOTE: When changing any of the following properties, you must update the
controller by downloading the settings and/or application.

Description
Additional descriptive text for the BACnet-Bus

Network Number
The number of the network. Network numbers must be unique in a BACnet
system.

Port Number
The number of the UDP port for BACnet IP communication

IP Port Settings
Enables or disables the ports for incoming traffic of various IP protocols.

FTP (File Transfer Protocol)


is a standard network protocol used to transfer computer files from
one host to another host over a TCP-based network, such as the
Internet.

SSH (Secure Shell)


is a cryptographic network protocol for secure data communication,
remote command-line login, remote command execution, and other
secure network services between two networked computers.

RPC Portmapper, RPC (Remote Procedure Call)


A very general mechanism for client-server applications is provided
by RPC package including a collection of tools and library functions.

LONSOCK
CARE supports LON IP Interfaces for the use of IP852 and LonSock
Remote Server. Both IP852 and LonSock Remote Server are
based on LonSock2 which is the basis for CARE software. IP852
allows the direct and remote diagnostic of networks based on IP852
standard. LonSock Remote Server allows remote access to PCs
and Excel Web controllers with a shared network interface on which
the RNI server is running

EN2Z-0937GE51 R0518 786


CARE FALCON AND EAGLE CONTROLLERS

HTTP (Hypertext Transfer Protocol)


HTTP is an application protocol for distributed, collaborative,
hypermedia information systems and is the foundation of data
communication for the World Wide Web. Hypertext is structured text
that uses logical links (hyperlinks) between nodes containing text.
HTTP is the protocol to exchange or transfer hypertext.

HTTPS (Hypertext Transfer Protocol Secure)


HTTPS is a communications protocol for secure communication
over a computer network, with especially wide deployment on the
Internet. Technically, it is not a protocol in and of itself; rather, it is
the result of simply layering the Hypertext Transfer Protocol (HTTP)
on top of the SSL/TLS protocol, thus adding the security capabilities
of SSL/TLS to standard HTTP communications.

BACnet/IP
The BACnet protocol provides mechanisms by which computerized
equipment of arbitrary function may exchange information,
regardless of the particular building service it performs. As a result,
the BACnet protocol may be used by head-end computers, general-
purpose direct digital controllers, and application specific or unitary
controllers with equal effect.

The BACnet protocol specifies transport over a number of datalink


layers including ARCNET, MS/TP (RS-485), PTP (RS-232),
LonTalk, and Ethernet. BACnet also specifies communication over
UDP/IP which is known as BACnet/IP.

BACnet/IP uses UDP as its transport protocol. The default UDP port
for BACnet traffic is 47808, but depending on the project
specification other ports are also possible.

DHCP Client / DHCP Server (Dynamic Host Configuration


Protocol)
DHCP is a standardized networking protocol used on Internet
Protocol (IP) networks for dynamically distributing network
configuration parameters, such as IP addresses for interfaces and
services. With DHCP, computers request IP addresses and
networking parameters automatically from a DHCP server, reducing
the need for a network administrator or a user to configure these
settings manually.

User-Defined TCP Ports


After enabling this option, you can enter any port numbers,
e.g. 602, 710-720

User-Defined UDP Ports


After enabling this option,you can enter any port numbers,
e.g. 800, 901-909

Define BACnet MS/TP Bus Properties

Purpose To define the settings for the BACnet MS/TP network (e.g. network number,
baudrate, etc.).

Procedure 1. With left mouse button, select the BACnet MS/TP Bus icon in the network tree.

RESULT: The BACnet MS/TP bus properties are displayed on the right
Properties pane.

787 EN2Z-0937GE51 R0518


FALCON AND EAGLE CONTROLLERS CARE

2. Enter/change text or values and select options for the following BACnet IP Bus
properties:

NOTE: When changing any of the following properties, you must update the
controller by downloading the settings and/or application.

MS/TP Channel Name


The name of the MS/TP network

Description
Additional descriptive text for the BACnet-Bus

Baud Rate
Baud rate for data transmission

Max Master
Defines the highest MS/TP master address that can participate in the token-
passing.

Max Info Frames Router


Indicates the largest number of frames that will be sent by the router before it
releases the token.

Max Info Frames Device


Indicates the largest number of frames that will be sent by the device before it
releases the token.

Create BACnet Subsystem

Purpose To create subsystems for structuring the network logically, e.g. to provide a
hierarchy level for the integration of multiple subnets that communicate among
themselves.

Procedure 1. With left mouse button, select the physical BACnet-Bus folder in the network
tree.

2. Click right mouse button and with left mouse button, click Create Subsystem in
the context menu.

EN2Z-0937GE51 R0518 788


CARE FALCON AND EAGLE CONTROLLERS

RESULT: The new subsystem folder will be inserted into the tree.

3. On the Properties tab on the right pane, edit the name in the Subsystem Name
field, if desired.

4. If desired, enter an additional description in the Description field. and click on


the created subsystem folder in the tree.

5. Click on the created subsystem folder in the tree.

RESULT: The newly named subsystem folder displays.

6. To create subnets for the BACnet-bus, please refer to the Create BACnet-Bus
Subnet section.

Create BACnet Subnet / Allocate IP Addresses to Controllers

Purpose To create subnets for representing the physical network of the building and to
allocate IP addresses to the controllers located in the subnet.

IMPORTANT:
Contact the network administrator to get the network address(es), the
subnet mask(s) and the gateway address(es) for the subnet(s).

You can either define IP address ranges and CARE automatically allocates IP
addresses to the controllers while the controllers will be created, or you manually
allocate particular IP addresses to controllers. A combination of these two ways is
possible.

NOTE: At that time, an IP address has not yet been allocated to the physical
controller. The physical controller does not get the IP address until the
controller has been setup.

The IP addresses must match the real IP addresses, which you have
obtained from the network administrator.

789 EN2Z-0937GE51 R0518


FALCON AND EAGLE CONTROLLERS CARE

Procedure 1. Depending on where you want to place the subnet, below the BACnet-IP Bus
folder or below a subsystem, select the BACnet-IP Bus folder respectively the
corresponding subsystem folder with the left mouse button.

2. Click right mouse button and with left mouse button, click Create Subnet in the
context menu.

RESULT: The new subnet folder will be inserted into the tree and on the
right pane, the Properties tab shows the properties to be
defined.

3. Define the properties for the subnet as follows:

4. Under General, edit subnet name and enter an additional description if desired.

5. Under Ethernet, you will ensure the proper allocation of IP addresses to the
controllers. While creating a controller, CARE automatically allocates an IP
address to each controller that is located in the subnet. The IP addresses will
be consecutively issued according to the defined ranges.

Example:

By default CARE defines the network address to "192.168.1.0 / 24" and the
gateway address to "192.168.1.1". Under IP Address Ranges, the first range is
inserted accordingly. The range can be further divided into sub ranges.

EN2Z-0937GE51 R0518 790


CARE FALCON AND EAGLE CONTROLLERS

One Range In the default example, the network ID "192.168.1.0 / 24” defines the following
IP address range and subnet mask:

IP address range (Range 1):


192.168.1.001 (First Address) to 192.168.001.254 (Last Address)
There are 254 IP addresses. The IP addresses will be consecutively issued
when creating the controllers as follows:

192.168.1.001
192.168.1.002
192.168.1.003
etc.

A particular IP address of a controller can be changed as long as it is within the


IP address range.

Subnet mask:
255.255.255.0.
The number 24 corresponds to a 3-byte subnet ID, and a one-byte host ID. This
is the widely-used subnet mask of class-C networks, which the Eagle Controller
typically uses. A class-C network allows up to 254 BACnet devices per system.

Sub ranges If you want to factor out particular ranges, you can divide range 1 into sub
ranges. For example (see screenshot):

791 EN2Z-0937GE51 R0518


FALCON AND EAGLE CONTROLLERS CARE

In the above example, IP addresses, which are within the IP address ranges,
will be consecutively issued beyond all ranges when creating the controllers:

192.168.1.001

192.168.1.040

192.168.1.081

192.168.1.120

192.168.1.161

192.168.1.240

The following IP addresses cannot be assigned to controllers:

192.168.001.041 to 192.168.001.080
192.168.001.121 to 192.168.001.159

NOTE To divide a range into sub ranges, the complete range (automatically
defined by the network ID) must become part of the sub ranges and
hence it must be edited first in the Range 1 line.

6. Under Ethernet, you can also enter the IP addresses for DNS (Domain Name
System) servers if the Eagle should support Email alarming. DNS server IP
addresses must be entered here if you have selected the SMTP Server option

EN2Z-0937GE51 R0518 792


CARE FALCON AND EAGLE CONTROLLERS

and have entered the SMTP server name under Server Settings on the Email
Alarming tab.

Enter at least the IP address for DNS Server1. It is recommended to enter an


additional IP address for DNS server2 as fallback position if DNS server1 is not
in operation.

7. To continue with setting up a controller, please refer to the Setup Eagle


Controller section.

Create BACnet MS/TP Bus

The MS/TP bus can have a pure BACnet MS/TP topology for integrating EAGLE
controllers and BACnet 3rd party devices, or it can be part of a BACnet IP network
including panel bus and MS/TP bus (mixed BACnet IP / BACnet MS/TP topology).

The BACnet controller allocation in the BACnet network structure is based on


procedures to be performed in the following CARE environment:

• New Controller dialog


• BACnet network tree
• Controller Properties tab

New Controller dialog


When creating a BACnet controller (see "Create BACnet Controller" section), the
allocation of the controller in the BACnet network can be pre-defined according to
the desired topology. The definition will be done by selecting the
subsystem/subnet and the RS485 interface settings in the New Controller dialog.

BACnet network tree


In a blank BACnet project, the initial status of the network configuration is as follows:

The BACnet network is divided in the BACnet IP Bus with a default IP-Subnet1 and
the BACnet MS/TP bus. Both busses are empty.

793 EN2Z-0937GE51 R0518


FALCON AND EAGLE CONTROLLERS CARE

The result of the pre-definition in the New Controller dialog can be changed
afterwards in the network tree by

• adding and deleting additional subsystems, subnets, MSTP busses and devices
• by moving controllers and devices within the folders of the network

• Or, it can be changed on the controller´s Properties tab by


selecting a MS/TP or Panel bus for an unassigned RS485 interface (None) under
Interfaces. An assigned interface can be made unassigned by deleting the
MS/TP bus in the network tree. Then it will be free for a new assignment of a
MS/TP bus.

EN2Z-0937GE51 R0518 794


CARE FALCON AND EAGLE CONTROLLERS

In the following, the BACnet MS/TP bus handling is described. For BACnet IP bus
description, please refer to the previous "Create BACnet Subnet / Allocate IP
Addresses to Controller" and the "Create BACnet Subsystem" sections.
For information on device management such as max. number of devices and
assignment of addresses and IDs, please refer to the BACnet Controller tab
description in the "Set Global CARE Options" section.

BACnet MS/TP Bus Scenarios Mixed BACnet IP / MS/TP topology


For a mixed BACnet IP / MS/TP topology, the pre-definition when creating the
controller can be any of the following:

Example 1: Controller with one MS/TP bus and one panel bus
- subsystem/subnet = IP-Subnet 1 (initial default)
- RS485 1 = BACnet MS/TP bus, RS485 2 = Panel bus

795 EN2Z-0937GE51 R0518


FALCON AND EAGLE CONTROLLERS CARE

The controller will be placed in the default BACnet IP Subnet and a BACnet MS/TP
bus assigned via RS 485-1 will be added to the controller.

NOTE: In this example, it is not possible to create a second BACnet MS/TP bus
for the controller via RS485-2 since all interfaces are assigned. For re-
assigning MS/TP or panel busses to an RS485 interface (1,2), the
interfaces must be made unassigned by deleting the corresponding
MS/TP bus (1, 2) in the network tree. If an interface is defined as Panel
bus, the interface cannot be made unassigned belatedly.

Rules (Mixed BACnet IP / MS/TP topology)

You can:
• add BACnet devices to the BACnet IP subsystem/subnet as well as to the
BACnet MS/TP bus
• add further subsystem and subnets which will be available for further placement
of controllers (New Controller dialog) and devices( network tree)
• move controllers and devices between different subsystems and subnets
• move devices between different BACnet MS/TP busses
• delete an MS/TP bus in the network tree and re-assign an MS/TP or panel bus
on the controller´s Properties tab.

You cannot
• move devices between IP-subsystem/subnets and BACnet MS/TP busses

Example 2: Controller with two MS/TP busses


- subsystem/subnet = IP-Subnet 1 (initial default)
- RS485 1 = BACnet MS/TP bus, RS485 2 = BACnet MS/TP bus

EN2Z-0937GE51 R0518 796


CARE FALCON AND EAGLE CONTROLLERS

NOTE: For this controller it is not possible to delete any of the two BACnet
MS/TP busses.

Rules (Mixed BACnet IP / MS/TP topology)


see rules of Example 1.

NOTE: Any combinations of controller configurations as a result of selecting


different subsystems/subnets and/or interfaces are possible and follow
the same rules as described in the above examples.

Pure BACnet MS/TP topology


For a pure MS/TP topology, the MS/TP bus must created in the network tree before
you can place controllers in it.

Example: Steps for creating a MS/TP bus, a controller and devices

a. Create MS/TP bus in the network tree.

The BACnet MS/TP bus is added to the network

797 EN2Z-0937GE51 R0518


FALCON AND EAGLE CONTROLLERS CARE

b. Create a new controller.


c. In the New Controller dialog, select the previously created BACnet
MS/TP bus as subsystem/subnet.
d. Select a BACnet MS/TP bus for one of the R485 interfaces
(mandatory).

The controller will be placed in the BACnet MS/TP bus.

e. Create a device in the BACnet MS/TP bus.

EN2Z-0937GE51 R0518 798


CARE FALCON AND EAGLE CONTROLLERS

Rules (Pure BACnet MS/TP topology)


• You can add further BACnet MS/TP busses which will be available for further
placement of controllers (New Controller dialog) and devices (network tree).
• You can move controllers and devices between different BACnet MS/TP busses
of a pure MS/TP network
• You can move devices between MS/TP busses of mixed and pure topologies
• You can move a MS/TP controller from a pure MS/TP network to a BACnet IP
subnet.
• You cannot move controllers and devices between a BACnet IP bus and a
BACnet MS/TP bus.

View Panel Bus Cycle Time

Large panel bus applications need higher cycle times than small and fast panel bus
applications (e.g. light control). Hence, the panelbus cycle time will be adopted by
the controller. It should not be changed in CARE. If problems occur in the controller,
the cycle time can be increased using the Excel Web HTML interface.

Procedure 1. Expand the Interfaces folder, and then click the Panel Bus folder.

2. On the right pane, click the Properties tab. The default cyle time of 250 msec is
displayed.

3. If desired, change the cycle time using the Excel Web HTML interface.
4. If desired, upload the application for updating CARE with the current cycle time
executed in the controller.

799 EN2Z-0937GE51 R0518


FALCON AND EAGLE CONTROLLERS CARE

Set Send On Delta Resolution for Panel Bus AI Points

The ´send on delta` setting (resolution) for Panelbus AI points defines the threshold
for sending value changes coming from the assigned sensors.

The send on delta resolution can be selected from three categories:

• High: no threshold
• Medium: threshold = 0.1 K / 50 mV
• Low: 0.5 K / 100 mV
Low resolution results in less load on the Panelbus and in the controller CPU.

Procedure 1. Expand the Interfaces folder, and then click the Panel Bus folder.

2. On the right pane, click the Properties tab. The default Send on Delta
Resolution ´Middle` is selected.

3. If desired, change the Send on Delta Resolution by selecting ´High` or ´Low`.

Create BACnet 3rd Party Device

Purpose To create a BACnet 3rd party device and define its general network specific settings
such as Ethernet (LAN) parameters.

Procedure 1. With left mouse button, select the BACnet-Bus IP-Subnet in the network tree.

2. Click right mouse button and with left mouse button, click Create Device in the
context menu.

EN2Z-0937GE51 R0518 800


CARE FALCON AND EAGLE CONTROLLERS

RESULT: The new device will be inserted into the tree.

3. Under General, enter/view information such as:

Device name
Default name can be edited

Device ID
Object identifier of the BACnet device object. This is a unique ID for any device
on the BACnet bus. If the BACnet device is an Eagle controller, the device ID is
the same as the controller number.

NOTE:
When integrating 3rd party BACnet devices, it must be ensured that no identical

801 EN2Z-0937GE51 R0518


FALCON AND EAGLE CONTROLLERS CARE

device IDs exist in the whole BACnet system. For that reason, an offset can be
defined. Adding this offset to the controller number generates the device ID.

BACnet Object Type


Name of the BACnet object type according to BACnet convention.

Description
Additional descriptive Text for the device

Location
Additional Text for the device, which indicates the location of the device, e.g.
Floor 4, Section Nord.

4. Under Objects, you can define external reference points, which can be used to
share point information across BACnet controllers. This can also be done via
the "Import from EDE file" function in the device library

5. Click the New button.

RESULT: The Create/Edit External Reference Point dialog box displays.

6. In the Object field, enter the object name.

7. Each of the following two options can be used for addressing the device in the
BACnet network:

• BACnet Object ID or
• BACnet Object Type and its Instance Number

The settings must be provided by or to the project engineer/vendor who is


responsible for the 3rd party BACnet device to be added to the CARE project.

The BACnet object ID is a unique ID within a BACnet device and within a CARE
project. It is calculated within CARE by the following Standard BACnet formula:

BACnet object ID = BACnet object type x 222 + Object


Instance number

EN2Z-0937GE51 R0518 802


CARE FALCON AND EAGLE CONTROLLERS

Hence, if the BACnet object ID is not known, you can use the BACnet Object
Type and its Instance Number. CARE calculates the BACnet Object ID using
these data.

Select the BACnet Object ID radio button and enter the BACnet Object ID into
the field.

Or, select the BACnet Object Type/Instance Number radio button. From the
drop-down listbox, select the BACnet object type and enter the instance number
into the field below.

8. Click the OK button.

RESULT: The object is inserted into the list. To edit an object, select the
object in the list and click the Edit button. To delete an object,
select the object in the list and click the Delete button.

9. The created object can now be selected under the Reference Input and
Reference Output point types of any BACnet controller of the project.

10. To assign an object to a BACnet controller, expand the logical plant tree and
then select the reference input, respectively the reference output point.

11. On the Properties tab, click the Add button.

RESULT: The Select Reference Point dialog box displays.

803 EN2Z-0937GE51 R0518


FALCON AND EAGLE CONTROLLERS CARE

12. Expand the tree and select the external reference point, and then click OK
button.

RESULT: The reference point will now use the value that the object
passes.

NOTE: You can add values from any kind of BACnet object or datapoint
available in the project.

EN2Z-0937GE51 R0518 804


CARE FALCON AND EAGLE CONTROLLERS

Set Controller as BBMD Device

When attaching BACnet devices to IP networks, the IP network can be sub-netted to


BACnet devices by using IP routers. Most IP routers will not pass broadcast
messages which are crucial to BACnet operation.

The solution is to incorporate BACnet/IP Broadcast Management Device (BBMD)


functionality within the BACnet / IP network. This can be accomplished by enabling
BBMD on the IP Router.

In CARE, the EAGLE controller supporting both, BACnet IP and BACnet MS/TP bus
via RS485 interface works as a router routing packets to the BACnet devices
connected to the subordinate channel.

NOTE: Per subnet, max. one EAGLE controller can incorporate BBMD
functionality.

Procedure 1. Expand the network tree and browse to the IP-Subnet where the controller is
located.

2. Right-click on the controller, and then click Set as BBMD in the context menu.

RESULT: The controller is indicated as BBMD device by a tiny red B in the


icon.

3. To remove the BBMD functionality from a controller, right-click on the controller,


and then click Remove BBMD in the context menu.

805 EN2Z-0937GE51 R0518


FALCON AND EAGLE CONTROLLERS CARE

RESULT: The BBMD functionality and the tiny red B is removed from the
controller.

Move BACnet Devices in the Network Tree by Drag&Drop

IMPORTANT
Do not move BACnet devices which are already bound to a controller. First,
move the controller and then do the binding.

In the BACnet-Bus part of the network tree, controllers and devices can be moved
between different subsystem folders.

Procedure 1. In the source folder, select the item (controller or device), drag it to the desired
target folder and drop it.

In this example, Eagle3 controller has been moved from the ´IP-Subnet 1` to
the´IP-Subsystem1 - IP-Subnet 1` folder

EN2Z-0937GE51 R0518 806


CARE FALCON AND EAGLE CONTROLLERS

Delete BACnet Subsystem, Subnet, or Device.

To delete a subsystem or a subnet, it must first be emptied before. That is, to delete
a subnet, delete all devices of the subnet. To delete a subsystem, delete all subnets
of the subsystem.

Procedure 1. In the BACnet network tree, select the item (subsystem, subnet, or device), you
want to delete.

2. Click right mouse button and with left mouse button click on Delete in the
context menu.

Setup BACnet Controller


Setting up a BACnet controller includes the following initial steps:

• Establish physical connection to BACnet controller


• Connect to BACnet controller
• Download settings
• Download firmware
• Download application

The following steps may be necessary during or after initial setup:

• Stop/start controller
• Upload application
• Download firmware (upgrade)
• Download Linux (upgrade, EAGLE controller only)
• Download settings

Establish Physical Connection to BACnet Controller


For setting up the controller, controller must firstly be connected to the CARE PC in
one of the following ways:

• LAN (remote access)


The controller can be accessed remotely via LAN by allocating a valid IP address
to the controller, which is reachable within the LAN.
The LAN connection type is recommended and mandatory when using a platform
hosting (ARENA AX) for e.g. viewing and editing time programs, trending values,
etc. of the other devices of the BACnet/IP network.

Procedure: see "Establish Remote LAN Connection to BACnet Controller"


section.

• Crossover cable (local access, FALCON controller only)


To locally connect to the FALCON controller via Ethernet, a crossover cable can
be used.
The crossover cable connection type has the highest transfer rate (100 Mbit/s),
but when applied, the IP address settings of the CARE PC need to be changed.
Hence, it has temporarily no connection to any other network and the FALCON
controller is not reachable in the network.

Procedure: see "Establish Local Ethernet Connection to BACnet Controller via


Crossover Cable" section.

• Remote (EAGLE controller only)


Allows the setup of a remote controller that resides in an external network by
entering the IP address, domain name or host name of the controller.

• USB (local access)


To locally connect to the controller via USB interface, an USB cable of type A
standard together with a D-Link DUB E100 adapter can be used for the FALCON

807 EN2Z-0937GE51 R0518


FALCON AND EAGLE CONTROLLERS CARE

controller and an USB cable of type B standard can be used for the EAGLE
controller .
The USB connection type is mandatory for the initial setup of a BACnet controller
due to a reasonable transfer rate (2 Mbit/s) and because no IP address changes
are necessary after installation. The LAN connection can be used further on.

Procedure: see "Establish Local Connection to BACnet Controller via USB


Cable" section.

For USB connection, the corresponding USB driver must be installed before.
Please refer to the "USB Driver Installation for Windows XP" and the "USB Driver
Installation for Windows 7" sections in the CARE Installation Guide
EN1Z-0964GE51 for detailed instructions.

IP Address Allocation To establish any of the provided connections, IP addresses must be allocated to the
relevant network components such as CARE PC, BACnet controller(s), network and
USB adapters.

IMPORTANT
Ask the network administrator for the dedicated IP addresses (IP address
ranges) that are allowed for the network components.

During engineering, the typical procedure to connect to a BACnet controller is as


follows:

• Initial access to the controller by connecting via USB cable. When delivering the
FALCON or EAGLE controller it has only the default factory IP address allocated
that normally do not fit to the IP address range of the customer network. So, in
this state, it cannot be accessed via LAN.

• Allocating the dedicated IP address to the controller by downloading the settings


into the controller. Now the controller has a valid IP address and it can be
reached within the LAN.

• Continual access to the engineered controller by connecting via LAN.

Establish Local Connection to BACnet Controller via USB Cable

For connecting the FALCON controller to the CARE PC you need a D-Link DUB
E100 USB adapter and a standard LAN cable.

For connecting the EAGLE controller to the CARE PC you need a USB cable of type
A Male to type B Male (Type B standard).

For each USB connection, the corresponding USB driver must be installed before.
For detailed instructions, please refer to the "USB Driver Installation for Windows
XP" and the "USB Driver Installation for Windows 7" sections in the CARE
Installation Guide EN1Z-0964GE51.

Procedure 1. After successful installation of the USB driver (see CARE Installation Guide
EN1Z-0964GE51), connect the CARE PC and the controller as shown in the
following figures:

EN2Z-0937GE51 R0518 808


CARE FALCON AND EAGLE CONTROLLERS

USB Connection of FALCON Controller

USB Connection of EAGLE Controller

2. Continue with connecting to the controller as described in the "Connect to


BACnet Controller" section.

Establish Local LAN connection to BACnet Controller via Crossover Cable

NOTE: This connection type applies to the FALCON controller only.

Procedure 1. Take the crossover cable and connect CARE PC and FALCON controller via
Ethernet inferface jacks as shown in the following figure:

2. On the CARE PC, start the Control Panel by clicking Start menu, then submenu
item Settings.

3. In the Control Panel window, double-click on the Network and Dial-up


connections icon.

RESULT: The Network and Dial-up Connections window displays.

4. In the Network and Dial-up Connections window, right-click on the LAN


connection of the CARE PC and with left mouse button, click on Properties.

RESULT: The Local Area Connection Properties dialog box displays.

809 EN2Z-0937GE51 R0518


FALCON AND EAGLE CONTROLLERS CARE

5. In the list, select Internet Protocol (TCP/IP).

6. Click right mouse button, and with left mouse button, click on Properties.

RESULT: The Internet Protocol (TCP/IP) Properties dialog box displays.

7. Select the Use the following IP address radio button and enter the following IP
address: 192.168.253.21.

8. Click the OK button.

EN2Z-0937GE51 R0518 810


CARE FALCON AND EAGLE CONTROLLERS

9. The Local Area Connection Properties dialog box re-displays.

10. Click the OK button.

RESULT: The CARE PC now cannot connect to the Internet or to another


network. After connecting to the FALCON controller with CARE
and completing the required actions, you will have to change
the configuration back to the previous settings in order to
(subsequently) operate on the office LAN network (again).

11. Continue with connecting to the controller as described in the "Connect to


BACnet Controller" section.

Establish Remote LAN Connection to BACnet Controller

Prerequisites To establish a LAN connection, a dedicated IP address must have been assigned to
the controller before by using a USB or crossover cable (see "Establish Local
Connection to BACnet Controller via USB Cable" and "Create BACnet Bus Subnet"
sections).

Procedure 1. Assign an IP address to the BACnet controller as described in the "Establish


Local Connection to BACnet Controller via USB Cable" and the "Create BACnet
Bus Subnet" sections.

2. Physically connect the CARE PC with the controller via LAN as shown in the
following figure.

2. Continue with connecting to the controller as described in the "Connect to


BACnet Controller" section.

Connect to BACnet Controller


Purpose To connect to the controller in order to setup or update the controller by performing
the appropriate download function for settings, application, controller firmware, or
Linux. After connection the application can also be uploaded.

Prerequisites A physical connection between controller and CARE PC must be established (see
"Establish Physical Connection to BACnet Controller" section).

Procedure 1. In the BACnet-Bus part of the network tree, navigate to the subsystem/subnet
and click on the BACnet controller to which you want to connect.

2. On the right pane, select the Setup tab.

811 EN2Z-0937GE51 R0518


FALCON AND EAGLE CONTROLLERS CARE

Connect to FALCON Controller

Connect to EAGLE Controller

EN2Z-0937GE51 R0518 812


CARE FALCON AND EAGLE CONTROLLERS

According to your needs, you have the choice to connect to the controller in one
of the following ways:

• LAN
Allows continual remote access to the controller once the controller has been
accessed via USB or crossover cable connection and has gotten its
dedicated IP address by the download of the controller settings. Next time
when accessing the Setup pane, the controller's IP address is displayed at
the LAN radio button.

If you need to remotely connect to a setup controller with a valid IP address


in a running system or test environment in order to do changes to the
controller, or if the IP address of a controller has been changed by the
network administrator, you can do that by entering the dedicated IP address
of the controller on the Properties pane and clicking the Confirm button. This
displays the IP address at the LAN radio button.
Note, that by default a BACnet controller has no IP address allocated in
delivery state, except its default factory IP addresses (see USB below).
Therefore, it cannot be accessed via LAN and the LAN option is disabled.

• X-OVR (Crossover cable, FALCON controller only)


Allows initial setup of the controller by local access like with USB cable, but
with higher speed and temporary disconnection to the network.

• Remote (EAGLE controller only)


Allows the setup of a remote controller that resides in an external network by
entering the IP address, domain name or host name of the controller.

• USB
For initial access to the controller, you must connect via USB. The CARE PC
will connect to the controller via USB using the default factory IP address of
the BACnet controller (FALCON = 192.168.252.20 and EAGLE =
192.168.255.241). This address is displayed at the USB radio button. The
default factory IP addresses are fix and cannot be changed.

3. Select the connection type, USB (recommended local access for initial setup),
crossover cable (local access for initial setup), or LAN (continual remote
access), and click the Connect button.

RESULT: CARE connects to the controller. If the connection is successful,


the following information is displayed:

• Communication Settings
• Version Information
• Clock Settings

Settings displayed in black can be changed, settings displayed


in gray cannot be changed.

IMPORTANT
The shown data is the data of the selected controller in CARE, not the data
of the physical controller. Although CARE reads the data from the physical
controller, it does not import the data into CARE but compares it with the
data of the controller selected in CARE you want do the setup for.

813 EN2Z-0937GE51 R0518


FALCON AND EAGLE CONTROLLERS CARE

FALCON Controller Settings

EAGLE Controller Settings

EN2Z-0937GE51 R0518 814


CARE FALCON AND EAGLE CONTROLLERS

Any data variations in the selected controller in comparison to the


physically connected controller are indicated by an asterisk (*).

4. To view sub items, expand the tree by clicking the plus icon at the item.

5. To change settings (non-changeable settings are displayed in gray), click in the


corresponding item line in the right column.

Example: Expand the Serial Interfaces item and Port 3 subitem, then click
in the right column of the Baudrate line and select the desired
baudrate.

NOTE: Any changes will be indicated by an asterisk (*).

Communication Settings
Serial Interfaces, Port 2, 3, Baudrate
Defines the baudrate for direct connection of CARE (port 2) and modem
connection (port 3).

Modem Setup, Dial out


Defines the dial out settings such as wait for dial tone, dial method, idle time,
command string and speaker.

TCP
Displays TCP/IP settings such as IP address, subnet mask, gateway address,
and host name.

Web Interface
Defines logout time, which sets the time after which you will be automatically
logged out if no action has been taken in the meantime.

BACnet
Displays the UDP number which will be used for communication and the
network number (see BACnet-Bus Properties).

LonWorks
Displays the neuron ID of the controller.

Clock Settings
Defines the values for local time, local date and time zone and displays

GMT (UTC) Offset (h), Has daylight savings

815 EN2Z-0937GE51 R0518


FALCON AND EAGLE CONTROLLERS CARE

Displays the offset of the Greenwich Mean Time (Universal Time Conversion)
and whether the controller has daylight savings or not.

Version Information
XL-Web
Displays the version of the operating system Linux and the BACnet firmware.

6. For further information and/or functions, look at the bottom of the Setup tab.
Under Controller Status, the current application status is displayed. When
CARE has successfully connected to the controller, the application is
automatically started as displayed by the permanent icon indication WALK in
green color and the selected Start radio button. If for any reason, the application
cannot be started, the radio button switches to Stop and the icon displays
DON´T WALK in red color. You can stop or start the application manually by
clicking the corresponding radio button.

Control Functions of (FALCON) Controller

7. Under Application you can translate, download or upload the application (see
"Translate Controller", "Download Application into BACnet Controller" and
"Upload Controller Application from BACnet Controller" sections). Under
Controller you can download the actual displayed communication and clock
settings into the controller (see "Download Settings into BACnet Controller"
section) and download the controller firmware (see "Download Firmware into
BACnet Controller (Upgrade)" section).

8. Continue by downloading the settings into the controller as described in the


"Download Settings into BACnet Controller" section.

Connect to Particular BACnet Controller


Purpose To connect to a setup controller that is reachable in a running system or test
environment in order to:

• do remote changes to a particular setup controller of which IP address you know


• remotely connect to a controller whose IP address has been changed e.g. by the
network administrator

Note that the IP address must be in the IP address range as defined by the network
address.

This procedure makes the local connection via USB unnecessary.

1. In the BACnet-Bus network tree, click on the controller.

2. In the IP Address field on the Properties tab, enter the IP address of the
controller to which you want to connect.

EN2Z-0937GE51 R0518 816


CARE FALCON AND EAGLE CONTROLLERS

3. Click the Confirm button.

RESULT: One of the following message boxes displays:

If this message box displays, check if the gateway address is


correct in order to reach the controller via this IP address, or
contact the network administrator for a valid IP address.

If this message box displays, the controller has already been


setup and been reached once at a valid IP address. Make sure
that the controller can be reached via the IP address you have
issued. If you are sure, then click the OK button.

If this message box displays, make sure that the controller can
be reached via the IP address you have issued. If you are sure,
then click the OK button and continue by setting up the
controller.

817 EN2Z-0937GE51 R0518


FALCON AND EAGLE CONTROLLERS CARE

4. To setup the controller, please refer to the Setup BACnet Controller section.

Connect to Remote BACnet Controller


Purpose To connect to a remote controller that resides in an external network by entering the
IP address, domain name or host name of the controller.

NOTES The IP address has not to be in the IP address range of the subnet.

It is possible to add a different SSH port by adding it after a colon.


For example, controller1.honeywell.com:23 will connect on port 23 at the
URL controller1.honeywell.com.

1. In the BACnet-Bus network tree, click on the controller.

2. In the Remote Address field on the Properties tab, enter the IP address, the
domain name or host name of the controller to which you want to connect.

3. Click the Setup tab (see next page).

EN2Z-0937GE51 R0518 818


CARE FALCON AND EAGLE CONTROLLERS

RESULT: The remote address of the controller is shown under


Connection

4. Select the Remote radio button.

5. Connect to the controller by clicking the Connect button.

Download Settings into BACnet Controller


Purpose To download the actual communication and clock settings as displayed on the Setup
tab into the physical controller. This function must be performed to continue the
initial setup of a BACnet controller, and it can be used for updating the controller in
case of changes in the communication or clock settings since the latest download of
the settings. After the download, the controller has gotten its dedicated IP address,
which allows the continual remote access to the controller. Next time when
accessing the Setup pane, the controller's IP address is displayed at the LAN radio
button.

819 EN2Z-0937GE51 R0518


FALCON AND EAGLE CONTROLLERS CARE

Prerequisites The controller must be physically connected to the CARE PC as described in the
"Establish Physical Connection to BACnet Controller" section.

Procedure 1. If not already done, connect to the controller as described in the "Connect to
BACnet Controller" section.

2. Click the Download Settings button.

RESULT: The following message box displays.

3. Click the Yes button.

RESULT: The settings are downloaded into the controller.

Download Application into BACnet Controller


Purpose To copy the application files into the physical controller.

Prerequisites The controller must be physically connected to the CARE PC (see "Establish
Physical Connection to BACnet Controller" section) and the controller must be
translated (see "Translate Controller" section). Please make sure that the connected
controller matches the selected controller hardware type in CARE (e.g. for FALCON
it is CLFA50LB0C, CLFA100LB0C, CLFA300LB0C, CLFA600LB0C).

All data of a BACnet project are exportable. Data may include:

• Plant graphics
• Alarm limits, parameters, and schedules
• etc.

The following data is not part of the application:

• Trend objects will be recovered from the Flash card after export
• All controller runtime data (e.g. present value of a datapoint, last execution time
of a control loop object. Those data are re-initialized after export.
• Elapsed active time will be recovered by the battery buffered RAM.

A controller application can only be exported in whole. Parts of an application cannot


be exported separately.

Procedure 1. Connect to the controller as described in the "Connect to BACnet Controller"


section.

EN2Z-0937GE51 R0518 820


CARE FALCON AND EAGLE CONTROLLERS

2. Under Application, click the Download button.

RESULT: The Transfer: Application Download dialog box displays


showing information such as file name, target, name and
version of the components.

3. Select whether the application should be started after the export or not by
checking/unchecking the Start XL Web after transfer checkbox.

4. Select whether the network should be commissioned after download or not by


checking/unchecking the Do LON Commissioning checkbox. This option is only
enabled for selection, when being Onnet with CARE.

5. Click the OK button.

RESULT: The controller is stopped and the application will be


downloaded. Status of the export is displayed in the process
window. After application download is finished and controller
start after transfer was selected, the controller is automatically
started as indicated by the Controller Status ´Start`.

821 EN2Z-0937GE51 R0518


FALCON AND EAGLE CONTROLLERS CARE

Upload Controller Application from BACnet Controllers


Upload Controller Application from FALCON Controller

Purpose To update the CARE database with the application files currently loaded in the
controller.

A controller application can only be imported in whole. Parts of an application cannot


be imported separately.

WARNING
When uploading an application, all changes, except newly added datapoints,
done to the application in the meantime in CARE will be lost.

Prerequisites The controller must be physically connected to the CARE PC (see "Establish
Physical Connection to BACnet Controller" section) and the application must be
downloaded once.

Procedure 1. Connect to the controller as described in the "Connect to BACnet Controller"


section.

2. Under Application, click the Upload button.

RESULT: The Transfer: Application Upload dialog box displays showing


information such as file name, target, name and version of the
components.

3. Click the OK button.

RESULT: The following message box displays.

EN2Z-0937GE51 R0518 822


CARE FALCON AND EAGLE CONTROLLERS

4. Click the OK button.

RESULT: The application will be imported into CARE. Status of the import
is displayed in the process window.

Upload Controller Application from EAGLE Controller

Purpose To update the CARE database with the application files currently loaded in the
controller.

WARNING
When uploading an application, all changes, except newly added datapoints,
done to the application in the meantime in CARE will be lost.

Prerequisites The controller must be physically connected to the CARE PC (see "Establish
Physical Connection to BACnet Controller" section) and the application must be
downloaded once.

Procedure 1. Connect to the controller as described in the "Connect to BACnet Controller"


section.

2. Under Application, click the Upload button.

RESULT: The following message box displays if the name of the physical
controller does not match the controller name in the CARE
project.

3. Click the Yes button if you want to upload anyway.

RESULT: The Controller Application Upload dialog box displays.

823 EN2Z-0937GE51 R0518


FALCON AND EAGLE CONTROLLERS CARE

On the top, the uploadable items are shown.

4. Check the items you want to upload. CARE instantly previews the found items
in the table below by Name, Type and Status.

NOTE: The listed items are previewed and not uploaded yet. Upload will
not be started unless clicking the Import button.

Example: In the following figure, calendars and control loop parameters


are selected and previewed. In the Name column, the name of
the calendar, schedule or control loop parameter is shown. In
the Type column, the selected type ´Calendar´ or ´Schedule` is
shown.

EN2Z-0937GE51 R0518 824


CARE FALCON AND EAGLE CONTROLLERS

If there is no difference between the uploadable application


items in the controller and the items in the CARE application, it
is indicated by a red message in the Name column, e.g. No
control loop parameter changed !

In the Status column, the type of action that will be applied to


the uploadable item is shown. The following actions are
possible:

Add
Item will be created in the CARE application

Replace
Item will be replaced in the CARE application

Delete
Item will be deleted in the CARE application

825 EN2Z-0937GE51 R0518


FALCON AND EAGLE CONTROLLERS CARE

NOTE: Please note the hint at the bottom saying that during first upload,
parameters could be listed which where not changed by the user
but changed by the application start.

5. If you are sure to upload the items previewed in the table, click the Import
button. If you want to exclude items from the import, uncheck the corresponding
items on the top before clicking the Import button. The table will be updated
accordingly.

RESULT: After the import has been finished, the Status column will show
the results as follows:

Successfully added (created), replaced or deleted items will be


indicated by green text messages, e.g.
Created in CARE project.

If an item could not have been created, replaced or deleted, it is


skipped from the upload as indicated by a red warning
message, e.g.
Warning: Schedule upload is skipped in CARE
project.

EN2Z-0937GE51 R0518 826


CARE FALCON AND EAGLE CONTROLLERS

6. After the import (upload) is finished, click the Close button.

Creating and Uploading Log Files of Controller

The controller can save various important data in log files which can be used for
support purpose.

In order to provide the appropriate log files to the Honeywell support, you can
configure the connected controller by defining which log files should be logged.

The following log files can be logged:

• System Logs
• Interface Logs
• BACnet device lists
• COV Subscriptions

The log files collection includes 3 steps:

• Defining the log files that should be logged


• Starting the logging
• Uploading the log files into the CARE directory

Procedure 1. Select the Setup tab of the controller.

827 EN2Z-0937GE51 R0518


FALCON AND EAGLE CONTROLLERS CARE

2. Connect to the controller.

3. Click Configure under Log Files.

4. Select desired options under Upload Log Files:

• System Logs
System log files can contain the standard system files or an enhanced set of
system log files which include more detailed information additionally.

EN2Z-0937GE51 R0518 828


CARE FALCON AND EAGLE CONTROLLERS

• Device List
There are 2 types of BACnet device lists. A small one that includes all
BACnet devices the controller has "talked" to and a bigger one that includes
all BACnet devices on the same bus where the controller resides.
• Interface Logs
These are the log files of the ports. Each port can be individually selected for
logging.
• COV Subscriptions
COV subscriptions

5. Select desired options under Configure Interface Logs:

• Status
Shows whether file logging for the port is currently running (checked) or not
(unchecked)
• Select
Check the port for which log files should be created.
• Bus
Shows the various bus ports
• Next File
Shows the maximum file size in bytes of the corresponding log file.
• File count
Shows the maxiumum number of log files before the oldest file will be
overwritten
• Compress
Check whether you want to compress the completed log file or not.
Compressed and completed log files will be enhanced with timestamp when
creating the compressed file. File names of uncompressed log files are
extended with numbers 0 … filecount-1.
• Buffer type
Click in the field to select the buffer type.
− Ringbuffer
When the file count is exceeded, the oldest file be overwritten.

NOTE: If the log file will be compressed (see "Compress" column),


there is no limit, that is, logging will be repeated indefinitely
− Stop when full
The log stops when the file count is exceeded

• Filter
Applies to the Ethernet port only. Shows the default udp port 47808 through
which BACnet traffic is logged on Ethernet.

6. Click Start button to start the logging function in the controller.

7. When logging is finished, click the Upload button.

829 EN2Z-0937GE51 R0518


FALCON AND EAGLE CONTROLLERS CARE

The log files are uploaded and saved in the "Logs" sub folder of the project.

Uploading Log Files of All Controllers in Project

Each controller in a project can be individually configured which log files it should
create and log (see "Creating and Uploading Log Files of Controller" section).
After controllers have been configured for logging, you can upload the log files of all
configured controllers in a project. You can select which log files of which controller
you want to upload and which not.

Procedure 1. Connect to the controller.

2. Right-click the Project folder, and then click Get Log Files in the context menu.

EN2Z-0937GE51 R0518 830


CARE FALCON AND EAGLE CONTROLLERS

The Upload Log Files dialog box displays. It shows all controllers of the project
with their name and IP address.

3. Under Selection, check the controllers of which log files you want to upload.
Uncheck the controllers of which log files you do not want to upload.

4. Under Upload Log Files, select the log files you want to upload for the selected
controllers:

• System Logs
System log files can contain the standard system files or an extended set of
system log files which include more detailed information additionally.
• Device List
There are 2 types of BACnet device lists. A small one (Required) that
includes all BACnet devices the controller has "talked" to and a bigger one
(All) that includes all BACnet devices on the same bus where the controller
resides.
• Interface Logs
These are the log files of the ports. Each port can be individually selected for
logging.

831 EN2Z-0937GE51 R0518


FALCON AND EAGLE CONTROLLERS CARE

• COV Subscriptions
COV subscriptions

5. Click the Start upload button.


The upload process is starting. The controllers will be processed consecutively
by connecting and then uploading the log files. In the Status column, the
current status is displayed with messages.

6. To stop the upload, click the Stop upload button.

7. When logging is finished, click the Close button.

For each controller, the log files are saved in the "Logs" sub folder of the
project.

Stop/Start Application
Purpose To stop or start the application in the controller.

Prerequisites The controller must be physically connected to the CARE PC (see "Establish
Physical Connection to BACnet Controller" section).

Procedure 1. Connect to the controller as described in the "Connect to BACnet Controller"


section.

2. To stop the application in the controller, click the Stop radio button.

RESULT: The icon displays DON´T WALK in red color.

EN2Z-0937GE51 R0518 832


CARE FALCON AND EAGLE CONTROLLERS

3. To start the application in the controller, click the Start radio button.

RESULT: The icon displays WALK in green.

Download Firmware into BACnet Controller (Upgrade)


Purpose To download updated firmware in the controller.

Prerequisites The controller must be physically connected to the CARE PC (see "Establish
Physical Connection to BACnet Controller" section).

Procedure 1. Connect to the controller as described in the "Connect to BACnet Controller"


section.

2. Click the Download Firmware button.

RESULT: The Open dialog box displays.

833 EN2Z-0937GE51 R0518


FALCON AND EAGLE CONTROLLERS CARE

FALCON Firmware File Selection

EAGLE Firmware File Selection

3. Navigate to the folder where the firmware file (.xwa) resides and select it.

4. Click the Open button.

RESULT: The Transfer: User Upgrade dialog box displays showing


information such as target, name and version of the
components.

EN2Z-0937GE51 R0518 834


CARE FALCON AND EAGLE CONTROLLERS

FALCON Firmware Upgrade

EAGLE Firmware Upgrade

3. Select whether the application should be started after the upgrade or not by
checking/unchecking the Start XL Web after transfer checkbox.

4. For the FALCON controller, select whether the controller should be cleaned up
or not by checking/unchecking the Cleanup XL Web checkbox. When cleaning
the controller, all applications other than the application to be downloaded will
be deleted from the flash memory. It is recommended to check the option to
save flash memory.

5. Click the OK button.

RESULT: The controller is stopped and the controller firmware will be


downloaded. Status of the export is displayed in the process
window.

835 EN2Z-0937GE51 R0518


FALCON AND EAGLE CONTROLLERS CARE

Reset BACnet Controller Configuration


NOTE: This function applies to the EAGLE controller only.

Purpose To set the controller to the factory delivery state. This includes the removal of the
settings and the application which must be downloaded again after the reset.

Prerequisites The Reset function is disabled if the CARE PC is physically connected to the
BACnet controller via LAN cable even if the USB connection is currently the active
connection between the two devices. To enable the function, remove the LAN
connection by unplugging the LAN cable from the controller and/or CARE PC.

Procedure 1. Connect to the controller as described in the "Connect to BACnet Controller"


section.

2. Click the Reset Configuration button.

RESULT: The Open dialog box displays.

3. Navigate to the folder where the firmware file (.xwa) resides and select it.

4. Click the Open button.

RESULT: CARE is checking the firmware image.

EN2Z-0937GE51 R0518 836


CARE FALCON AND EAGLE CONTROLLERS

After successful check, the Transfer: User Upgrade dialog box


displays showing the components. No components can be
selected.

5. Check Disconnect controller after download if you want to reset multiple


controllers. Uncheck Disconnect controller after download if you want to
continue immediately with the same controller.

6. Click the OK button to start the configuration reset.

RESULT: After the reset has been successfully finished, the following
message box is displayed.

Create Certificate
Prerequisites In the following, basic knowledge of the management of certificates is presumed.
Hence, please get familiar with basic knowledge of certificates management by
reading the appropriate literature.

837 EN2Z-0937GE51 R0518


FALCON AND EAGLE CONTROLLERS CARE

In CARE, certificates management includes the following steps:

1. add certificate properties


2. create certificate

The properties for certificates can be defined on project and controller level. The
certificate properties on project level will automatically applied to all newly created
controllers of the project. The properties for a controller are only valid for this
particular controller. If the properties on project level are changed they will be not
reflected in existing controllers.

NOTE: The certificate properties to be entered on the Certificates tab, should be


the data of the network domain owner or the operator not the data of the
CARE engineer because the network domain owner or operator is the
owner of the controller and the server certificate option.

Procedure 1. In the logical plant tree, select the project or the controller.

2. On the right pane, select the Certificates tab.

3. Enter the following properties:

• Internal Name
• Country Name
• State of Province Name
• Locality Name
• eMail Address
• Organisation Name
• Organisational Unit Name
• Common Name

4. In Subject Alternative Name, click Edit… button to define the subject


alternative name as follows:

EN2Z-0937GE51 R0518 838


CARE FALCON AND EAGLE CONTROLLERS

a. In the Type column, click into the cell, and then select the type:

b. In the Content column, enter an address (name).


c. To add further alternative names, click the Add button and repeat steps
a and b.
d. To delete a row, highlight the row, and then click the Delete button.
e. Click OK to save settings.

5. From the Begin Date drop- down listbox, select a start date in the calendar
which defines the start of the valid period for the certificate.

6. In the Time Range field, enter the number of months (default = 120 months).

7. Select the controller.

8. On the right pane, select the Setup tab.

9. Connect to the controller.

10. Under Certificates, click the Create button.

11. In the Create Certificate dialog box, check Create new private key if you want
to create a new private key.When checking this option, the creation will take
longer.

839 EN2Z-0937GE51 R0518


FALCON AND EAGLE CONTROLLERS CARE

12. Click OK to start the creation process. The controller is creating the certificate.

13. The following message box displays after the successful creation.

14. Click OK to confirm the message.

15. Click OK to close the message box.

16. Continue by downloading the settings and the application.

Modbus Support
Purpose Configure BACnet controller for Modbus operation.

EN2Z-0937GE51 R0518 840


CARE FALCON AND EAGLE CONTROLLERS

Modbus operation is based on a master-slave communication between one Modbus


Master device and one or up to 63 Modbus slave devices. Communication between
the master and the slave devices will be established via a modbus interface that is
defined through bit-addressable data items (Discrete Inputs, Coils) and word-
addressable data items (Input Registers, Holding Registers) which can be mapped
to datapoints of the BACnet controller application.

NOTE: By default, the BACnet controller operates as a Modbus Master and


Modbus devices operate as Modbus slaves. The BACnet controller
cannot operate as Modbus slave.

Fig. 4. Modbus Interface / Addressing Model

The following table shows the Modbus data model:

Data Item Addressing-Type Read-Write


Discrete Inputs Bit Read-Only
Coils Bit Read-Write
Input Registers “Word” (16 Bit or 32 Bit) Read-Only
Holding Registers ”Word” (16 Bit or 32 Bit) Read-Write

The physical Modbus communication can be established via the RS485 1 or the
RS485 2 interface.

CARE Engineering In CARE, you create the Modbus master and slave device(s) and map the
datapoints of the CARE application to the registers of the Modbus devices. The
mappings will be downloaded with the application.

Prerequisites
Please make yourself familiar with common Modbus standards and technology by
reading the corresponding standard work:

• The Modbus protocol is described in the below listed two documents, which can
be found at www.modbus.org :
– Modbus_over_serial_line_V1_02.pdf
– Modbus_Application_Protocol_V1_1b.pdf

841 EN2Z-0937GE51 R0518


FALCON AND EAGLE CONTROLLERS CARE

• The MVC Modbus Troubleshooting Guide can help you also.

NOTE: Use the up-to-date versions of the documents.

Procedure

1. Create the BACnet controller with ´Modbus` selected for either the RS485-1 or
RS485 2 interface. Note that only one RS 485 (1 or 2) interface can be used for
Modbus communication.

RESULT: The controller will be created as master controller. The Modbus


interface is created and added to the Interface folder in the tree.
The controller properties are displayed on the Properties pane.

2. In the project tree, select the Modbus interface.

EN2Z-0937GE51 R0518 842


CARE FALCON AND EAGLE CONTROLLERS

3. On the Properties pane, define the Modbus channel properties as follows:

a. In Modbus Channel Name, enter a name for the channel.


b. In Baud Rate, select the baud rate.
c. In Message Timeout (20 ..50000 ms), do not change the default value of
200 ms, unless you need to do so in order to cure response issues with the
Modbus slaves. The message timeout is the max. waiting time in ms of a
master for a poll response message from a slave. Standard slaves response
within 50-100 ms. Please check the documentation of the slave device.
d. In Inter Message Delay (0 ..1000 ms), leave the default setting or change it
if you want to cure response issues with the Modbus slaves. The inter
message delay is the time in ms the master waits before it sendes the next
request. The set value affects bus performance and stability with reciprocal
effect. Entering values between 0 ms and 200 ms are suitable for
experimenting with performance and stability. When entering 0 ms, you will
have the best performance but irregularities in the master-slave
communication may occur which results in worse stability. When entering
values greater than 200 ms, you will have a high stability but the
performance might slow down to an inappropriate level. The default value of
200 ms can be a good value considering both, performance and stabiltiy.

e. In Parity, select the parity for communication error checking from:


– No
– Even
– Odd

f. In Number of Stop Bits, select the number of stop bits:


– 1 Bit
– 2 Bits

g. In Live Check Repeat Count, enter the number of live check repeats (1..10)

h. In Live Check, enter the repeat time for a missing response message when
the live check repeat count is not off (1.. 20 s).

843 EN2Z-0937GE51 R0518


FALCON AND EAGLE CONTROLLERS CARE

i. In Live Check if Offline, enter the repeat time for a missing message when
the live check count is off (2.. 60 s).

j. In Default Byte Order, do not change the default value, unless you need to
do so in order to cure response issues with Modbus slaves.
If so, select the default byte order from:
– Most significant Byte First
– Lower significant Byte First

The byte order is a function of the Modbus device which defines


whether the lower or the most significant byte is processed first by the
BACnet controller. Each individual slave device may communicate with
a different byte order to the BACnet controller for proper operation.
The default byte order selection pre-defines the same byte order for all
slave devices subsequently created (see following steps). A different
byte order can be configured in the Default Byte Order menu of each
individual slave device.

k. In Default Word Order, do not change the default value, unless you need to
do so in order to cure response issues with slave devices. If so, select the
default word order from:
– Most significant Byte First
– Lower significant Byte First

The word order is a function of the slave device which defines whether
the lower or the most significant byte is processed first by the BACnet
controller. Each individual slave device may communicate with a
different word order to the BACnet controller for proper operation. The
default word order selection pre-defines the same byte order for all
slave devices subsequently created (see following steps). A different
byte order can be configured in the Default Byte Order menu of each
individual slave device.

4. Create a slave device, by doing one of the following:


– Insert an existing Modbus device from the Device Library (see “Insert
Modbus device from Device Library” section.
or
– Create a Modbus slave device manually as described in the following
steps.

5. Right-click on the Modbus interface, and then click Create Modbus Device.

RESULT: The slave device is created and its properties are displayed on
the Properties pane.

EN2Z-0937GE51 R0518 844


CARE FALCON AND EAGLE CONTROLLERS

6. On the Properties pane, define the properties for the slave device as follows:

a. In Device Name, enter a name for the slave device.


b. In Device ID, enter the Modbus ID of the slave device. One and the same
device ID must not be assigned to multiple devices.
c. In Description, enter a more detailed description if desired.
d. In Poll Rate, enter the time for polling values/states in the slave device (0 ..
6000 s). When entering 0, the devices are polled with 100 ms.
e. In Byte Order, the default byte order as defined for the channel is pre-
selected (see Interface properties). Dependent on the slave device
specification, change the byte order if necessary and select from:
– Most significant Byte First
– Lower significant Byte First

The byte order is a function of the slave device which defines whether
the lower or the most significant byte should be processed first by the
BACnet controller. Each individual slave device will communicate with
its byte order to the BACnet controller for proper operation.

f. In Word Order, the default word order as defined for the interface is pre-
selected (see Interface properties). Dependent on the slave device
specification, change the word order if necessary and select from:
– Most significant Byte First
– Lower significant Byte First

The word order is a function of the slave device which defines whether
the lower or the most significant byte should be processed first by the
BACnet controller. Each individual slave device will communicate with
its word order to the BACnet controller for proper operation.

7. Double-click on the slave device to show its data items (coils, inputs and
registers).

845 EN2Z-0937GE51 R0518


FALCON AND EAGLE CONTROLLERS CARE

8 For the coils and discrete input data items, the addressing register type is pre-
defined to ´16 Bit Register` and cannot be changed. For the holding and input
registers data items, the addressing register type can be defined to 16 Bit or 32
Bit.

9. To define the addressing register type for registers, click the Holding Registers
or Input Registers data item in the tree, and then select the addressing register
type from the Addressing Register Type drop-down listbox.

NOTE: The addressing register type selection is only possible before modbus
points have been created.The selection of the addressing register type
pre-defines the choice for the data structure of the modbus points
created later. The ´32 Bit Register` type only allows 32 Bit data types.
The ´16 Bit Register` type allows 16 Bit and 2 Bit data types.

If the addressing register type is set to ´16 Bit Register` and later the
data type for a modbus point is set to ´int32`, ´uint 32`, or ´float`, 2
physical addresses will be occupied.

10. For each data item (coil, discrete input, register) you can:
– create Modbus points
– address Modbus points
– define the data structure of Modbus points

11. For holding and input registers you can:


– map analog input points to Modbus points

12. For coils and discrete inputs you can:

– map binary input points to Modbus points

13. Firstly, right-click on the data item, for example, Holding Registers and then
click Create Modbus Point(s)….

EN2Z-0937GE51 R0518 846


CARE FALCON AND EAGLE CONTROLLERS

RESULT: The New Modbus point dialog box displays.

14. Create Modbus points as follows:

a. In Number to add, enter the number of points you want to create.

b. In Decimal, enter the decimal start number for the first physical address. The
addresses will be enumerated consecutively starting with the value entered.
In Hexadecimal the decimal number is displayed in hexadecimal format. The
decimal value will be basis for the register number and vice versa.

c. In Register Number, for holding registers the number is pre-defined in the


range of 40001 and 49999 based on the value of the Decimal physical
address and increased by 1. You can enter a higher value if desired. The
registers will be enumerated consecutively starting with the value entered.

d. In Register Name, enter an additional description if desired. The physical


addresses plus the register names will be displayed in the tree.

e. In Data Type, select the data type from:


– bool
– int16

847 EN2Z-0937GE51 R0518


FALCON AND EAGLE CONTROLLERS CARE

– uint16
– int32
– uint32
– float

NOTE: If the addressing register type defaults to ´16 Bit Register` and the
data type is set to ´int32`, ´uint 32`, or ´float`, 2 physical address
entries will be occupied.

RESULT: The Modbus points are added to the Holding Registers folder.

15. To continue by defining properties, click the Modbus point in the tree.

EN2Z-0937GE51 R0518 848


CARE FALCON AND EAGLE CONTROLLERS

16. On the Properties pane, define the Modbus point properties as follows:

NOTE: Not all properties are available for each data type item.

a. In Register Type, the register type is displayed.

b. In Physical Address, you can change the physical address.

c. In Register Number, you can change the number of the register.

Please refer to descriptions in step 14 for information on dependencies of


physical address and register number.

d. In Register Name, enter an additional description for the point if desired.


The physical address plus the register name is displayed in the tree and will
be changed accordingly.

e. In Data Type, you can change the data type by selecting from:
– bool
– int16
– uint16
– int32
– uint32
– float

849 EN2Z-0937GE51 R0518


FALCON AND EAGLE CONTROLLERS CARE

NOTE: If the addressing register type defaults to ´16 Bit Register` and the
data type is set to ´int32`, ´uint 32`, or ´float`, 2 physical address
entries will be occupied.

f. In Bit Unpack, the unpack bit is displayed.


g. In Message Type, select the message type from:
– Read Only
– Read and Write
– Write Only

h. In CARE Datapoint, select a CARE datapoint for point mapping.


As long as no datapoint has been mapped to a Modbus point, the point icon
in the tree will demonstrate this by showing a yellow question mark in its icon
.
i. In Heatbeat, enter a value in sec. The heartbeat defines the regular time
interval in which the datapoint value is sent on the Modbus even if the value
has not change. Applies to ´write only` message type for coils and holding
registers only.

RESULT: The mapped CARE datapoint is added to the Modbus point


name and will be shown in the tree as follows:

Modbus point name:<CARE point name>

Example:
0001:Temp1:<AI5>

(in this example, the register is named to Temp1)

Insert Modbus Device from Device Library


For general introduction into the device library functions, please read the “Device
Library” section.

Procedure
1. Open the Device Library by clicking the device library icon in the CARE
tool bar.
RESULT: The Library displays.

EN2Z-0937GE51 R0518 850


CARE FALCON AND EAGLE CONTROLLERS

2. Expand the Device Library tree and browse to the Modbus Devices folder.

3. Select the Modbus device and drag&drop it to the Modbus interface in the
project tree.

851 EN2Z-0937GE51 R0518


FALCON AND EAGLE CONTROLLERS CARE

RESULT: The Modbus device is inserted to the interface.

4. If desired, you can change the Modbus device properties as described in the
basic procedure for creating a Modbus device in the “Modbus Support” chapter.

Create Modbus Devices in the Device Library


Procedure

1. In the Library, expand the DeviceLibrary tree.


2. Do one of the following:

a. Right-click the Modbus Devices folder, and then click Create Modbus
device.
b. Or, select a Modbus device in the project tree and drag&drop it onto the
Modbus Devices folder in the Library.

RESULT: A new Modbus device is added to the Modbus Devices folder.

EN2Z-0937GE51 R0518 852


CARE FALCON AND EAGLE CONTROLLERS

3. Right-click the Modbus Device, and then click ModbusEditor.

RESULT: The Modbus Template Editor displays.

4. Double-click the Modbus Device.

RESULT: On the Modbus Device pane on the right, the general properties
are displayed. In the tree on the left, the device functions are
displayed.

853 EN2Z-0937GE51 R0518


FALCON AND EAGLE CONTROLLERS CARE

5. Configure the Modbus device in the same way as described in the basic
procedure in the “Modbus Support” chapter.

After you have finished the creation of the Modbus device via Modbus Template
Editor in the Device Library, you can add the device to the Modbus project as
described in the “Insert Modbus Device from Device Library” section.

M-Bus Support
Purpose Configure BACnet controller for M-Bus operation.

M-Bus operation is based on a master-slave communication between one M-Bus


Master device (BACnet controller) and one or multiple M-Bus slave devices
(sensors, actuators). Communication between the master and the slave devices will
be established via M-Bus interface that is defined through data records (e.g. energy
volume, flow temperature) which can be mapped to datapoints of the BACnet
controller application.

The physical M-bus communication is established via the RS232 interface.

Prerequisites
Please make yourself familiar with common M-bus standards and technology by
reading the corresponding standard work provided on the following website:

http://www.m-bus.com/default.php

CARE Engineering In CARE, you create the M-bus master (BACnet controller) and read the information
of the slave device(s) from the M-bus. Then you map the datapoints of the CARE
application to the data records of the M-bus devices. The mappings will be
downloaded with the application.

Main Procedure

1. Create the BACnet controller with the ´Support M-bus` option selected.

EN2Z-0937GE51 R0518 854


CARE FALCON AND EAGLE CONTROLLERS

RESULT: The controller and the M-bus interface are created and added to
the tree. The controller properties are displayed on the
Properties pane.

2. In the project tree, select the M-bus interface.

855 EN2Z-0937GE51 R0518


FALCON AND EAGLE CONTROLLERS CARE

3. On the Properties pane, define the M-bus channel properties as follows:

a. In M-bus Channel Name, enter a name for the channel.


b. In Max. Number of Devices, select the max. number of devices that should
be supported by the M-bus channel.

4. Right-click on the M-bus interface, and then click Scan M-Bus Device.

RESULT: The M-Bus Scan and Commission dialog displays. Please make
sure that the M-Bus devices are properly wired to the M-Bus
using an M-Bus interface such as PW3 and the PC is connected
to the M-Bus via RS232 interface.

5. In Scan Options, select desired option from:

– Scan device by broadcast address


M-Bus will be scanned for devices knowing the broadcast address 254.
will be found.

EN2Z-0937GE51 R0518 856


CARE FALCON AND EAGLE CONTROLLERS

– Scan device by primary address


M-Bus will be scanned for devices having a particular primary address
which can be selected from a drop-down listbox.
If multiple devices have the same primary address, only the device found
first will be displayed.

NOTE:
If multiple devices that have the same primary address due to their
factory setting should be used on the M-Bus, it is strongly recommended
to connect, scan and commission each device separately.

– Scan all devices


M-Bus will be scanned sequentially for devices with address 1 through
250.

6. In Communication Parameters, do the following:

– PC Interface
By default, COM1 is selected as PC interface to the M-Bus.

– Baud rates
Check the baudrate in bit/s from:
300, 2400, 9600, AUTO. Auto sequentially scans the M-Bus using the
other baud rate options.

7. Click Start Scan button.

857 EN2Z-0937GE51 R0518


FALCON AND EAGLE CONTROLLERS CARE

RESULT: All found devices are listed with their major properties under
Devices. The most relevant data records of the currently
highlighed device are diplayed in the list below. The Visible
column defines which data records will be visible in the project
tree after the device has been added to the project.
By default, all data records are checked for display.
Please refer to the M-Bus website and/or the manufacturer
information for detailed description of the device properties and
data records properties. In the Logs area at the bottom, the
executed actions are shown. To clear the Logs area, click the
Clear Log button.

8. In the Visible column check/uncheck the data records that should be


visible/hidden in the project tree and on the terminal after the addition of the
device.

NOTE: Hidden data records are still available in the device. To make data
records visible again, please refer to the "Terminal Assignment of M-
Bus device" section.

9. For protocolling, you can save the logged actions in a .TXT file. To do so, click
the Export Log button, and then click Save in the Save as dialog box.

10. If you want to change the primary address of the selected device, click the cell
in the Primary column, and then select the desired address from the drop-down
listbox.

11. Check the device in the Select column or, click the Select all devices icon for
selecting all devices.
.

EN2Z-0937GE51 R0518 858


CARE FALCON AND EAGLE CONTROLLERS

12. Then, click Commission devices button if you have changed the primary
address of the device. Confirm the message box displayed by clicking OK.

13. Click Add devices in CARE button.

14. Click Close button to exit the M-Bus Scan and Commission dialog.

RESULT: The commissioned device is added to the M-Bus interface in the


tree. On the right pane, the device properties are shown on the
Properties tab. In the tree, the data records are displayed.

15. On the Properties tab you can do one of the following:

a. In Primary Address, select a different primary address.


b. In Device Name, change the device name.
c. In Description, enter an additional description
d. In Baud Rate, select the baud rate in bits/sec with which the device should
communicate with the BACnet controller.
e. In Measurement Cycle, enter the value in sec with which the M-bus device
should be repeatedly polled by the BACnet controller.

NOTE: If you change properties of the device, the device will be set into
uncommissioned state and you must re-commission the device.
An uncommissioned device is indicated by 4 red corners at its border.

16. To re-commission a device of which properties have been changed, please


refer to the "Commission M-Bus Device in M-Bus Channel" section .

17. To map datapoints to data records, do the following:

a. In the tree, click the data record.

859 EN2Z-0937GE51 R0518


FALCON AND EAGLE CONTROLLERS CARE

b. On the Properties tab on the right, select the datapoint from the Data Point
drop-down listbox.

NOTES: Data records can only be mapped to boardless analog input points.
Datapoints can also be mapped to data records on the terminal
assignment tab (see '"Terminal Assignment of M-Bus Device" section).

18. If desired change the name of the data record in the Data Record Name field.

Commission M-Bus Device in M-Bus Channel


Procedure

1. To commission a changed device or a device added from the device library,


right-click the device in the M-Bus channel and click Commission in the
context menu.

RESULT: The M-Bus Scan and Commission dialog displays.

EN2Z-0937GE51 R0518 860


CARE FALCON AND EAGLE CONTROLLERS

2. Click Start Scan and Commission in the context menu.

RESULT: The device will be commissioned.

3. Confirm the message box indicating the successful commissioning by clicking


OK.

4. Click Close button to exit the M-Bus Scan and Commission dialog.

RESULT: The commissioned device is displayed without red corners at its


border.

Terminal Assignment of M-Bus Device


The terminal assignment of the M-Bus device by default and initially shows all data
records of the device. On the terminal assignment tab, you can then map CARE
datapoints (analog inputs) to the data records of the device. Data records can be
made visible or hidden.

Procedure

1. In the project tree, click the M-Bus channel.

RESULT: On the right the Terminal Assignment tab displays all M-Bus
devices with their terminal assignments.

861 EN2Z-0937GE51 R0518


FALCON AND EAGLE CONTROLLERS CARE

2. To change the display of the data records assigned to the terminals, double-
click the device.

RESULT: The device properties are shown. In this dialog you can define
which data records should be visible or hidden and the
alphabetic order of the data records on the terminals.

3. In the Visible column check/uncheck the data records that should be


visible/hidden on the terminal and in the project tree. Use the and
icons for selection if desired.

NOTE: Hidden data records are still available in the device.

4. To sort the data records alphabetically, do the following:

a. Click the column by which the data records should be sorted, e.g. Name.

EN2Z-0937GE51 R0518 862


CARE FALCON AND EAGLE CONTROLLERS

b. Click the sort order icon for ascending sort order, or the sort order icon
for descending sort order.

c. Click OK button to close the dialog

RESULT: The Terminal Assignment tab redisplays.

5. To map datapoints to the data records, expand the plant and browse to the
Analog Input folder.

863 EN2Z-0937GE51 R0518


FALCON AND EAGLE CONTROLLERS CARE

6. Drag&drop the datapoint to the terminal.

RESULT: The datapoint is mapped to the data record. The mapped


datapoint is indicated by gray color on the terminal and in the
Analog Input folder.

M-Bus Devices Procedures in Device Library


The device library provides the following functions for M-Bus devices:

• Add M-bus device to device library via M-Bus-Scan or via drag&drop from the M-
Bus channel
• Add M-Bus device from device library to M-Bus channel.

For general introduction into the device library functions, please read the “Device
Library” section.

Procedure
1. Open the Device Library by clicking the device library icon in the CARE
tool bar.

EN2Z-0937GE51 R0518 864


CARE FALCON AND EAGLE CONTROLLERS

RESULT: The Library displays.

2. To add a device to the device library by scanning the M-.bus, continue with the
procedure described in the "Add M-Bus Device to Device Library via M-Bus
Scan" section.

3. To add a device from the M-Bus channel to the device library, continue with the
procedure described in the "Add M-Bus Device from M-Bus Channel to Device
Library" section.

4. To add a device from the device library to the M-Bus channel, continue with the
procedure described in the "Add M-Bus Device from Device Library to M-Bus
Channel" section.

865 EN2Z-0937GE51 R0518


FALCON AND EAGLE CONTROLLERS CARE

Add M-Bus Device to Device Library via M-Bus Scan

Procedure

1. Open the device library as described in the "M-Bus Devices Procedures in


Device Library" section.

2. In the Device Library tree, right-click the M-Bus Devices folder, and then click
Scan M-Bus over PC COM-Port in the context menu.

RESULT: The M-Bus Scan and Commission Dialog displays.

3. Please make sure that the M-Bus devices are properly wired to the M-Bus
using an M-Bus interface such as PW3 and the PC is connected to the M-Bus
via RS232 interface.

EN2Z-0937GE51 R0518 866


CARE FALCON AND EAGLE CONTROLLERS

4. For detailed information on the Scan Options and Communication Parameters,


please refer to the Procedure step 5 et seq. in the "M-Bus Support" section

5. Click Start Scan button.

867 EN2Z-0937GE51 R0518


FALCON AND EAGLE CONTROLLERS CARE

RESULT: All found devices are listed with their major properties under
Devices. The most relevant data records of the currently
highlighed device are diplayed in the list below.

6. To add the device to the device library, check the device in the Select column
or for selecting all devices, click the Select all devices icon.
.

7. Then, click Add devices in Device Library button.

RESULT: The devices are added to the device library as indicated by the
following message box.

EN2Z-0937GE51 R0518 868


CARE FALCON AND EAGLE CONTROLLERS

8. Click OK button to close the message box, and then click Close button in the
M-Bus Scan and Commission Dialog to return to the device library.

RESULT: The added device is displayed in the M-Bus Devices folder.


Note that devices in the device library are uncommissioned and
must be commissioned in the M-Bus channel of the project tree.

9. To view and change properties of the device, select the device and then click
the Moore>> button.

RESULT: The M-Bus Device tab displays on the right.

10. If desired, change the name, the description and/or the measurement cycle.

11. To view properties of data records, double-click on the device and then select
the data record in the tree.

RESULT: The M-Bus DataRecord tab displays on the right.

12. If desired, change the name of the data record in the Data Record Name field.

869 EN2Z-0937GE51 R0518


FALCON AND EAGLE CONTROLLERS CARE

13. Click <<Moore button to close the Properties view, and then click Exit button
to close the device library.

Add M-Bus Device from M-Bus Channel to Device Library

Procedure

1. Open the device library as described in the "M-Bus Devices Procedures in


Device Library" section.

2. In the project tree, select the device and drag&drop it to the M-Bus Devices
folder in the Device Library tree.

RESULT: The device is added to the M-Bus Devices folder. It is


uncommissioned.

3. To view and change properties of the device, please refer to the "Add M-Bus
Device to Device Library via M-Bus Scan", step 9 et seq.
.

Add M-Bus Device from Device Library to M-Bus Channel

Procedure

1. Open the device library as described in the "M-Bus Devices Procedures in


Device Library" section.

2. In the Device Library tree, expand the M-Bus Devices folder.

3. Select the device and drag&drop it to the M-Bus channel in the project folder.

EN2Z-0937GE51 R0518 870


CARE FALCON AND EAGLE CONTROLLERS

RESULT: The uncommissioned device is added to the M-Bus channel.

4. If desired, change device properties on the Properties tab as described in step


15 et seq. of the Main Procedure of the "M-Bus Support" section .

5. Commission the device as described in the "Commission M-Bus Device in M-


Bus Channel" section .

Read M-Bus Records from M-Bus Device


Purpose To read M-Bus records from the M-Bus device by the controller.

There are two ways to read M-Bus records from an M-Bus device by the controller:

• Time-interval-based Reading
You can set a particular time interval with which the M-Bus records will be read.
E.g. when setting the time interval to 3600 sec, an M-Bus record will be read
every 3600 sec beginning after application start and continueing as long as the
application is running. This mode can cause irregularities in the M-Bus record
times, e.g. in case of application interrupts and re-starts due to changed
controller operation status.

• Clock-time-based Reading
You can set a fixed clock-time (trigger) in the time program at which the M-Bus
records will be read. E.g. when setting the clock-time to 6:00, an M-Bus record
will be read at 6:00 a.m., when setting the clock-time to 18:00, an M-Bus record
will be read at 6:00 p.m. This results in a synchronous reading process
independent of the current application and controller operation status
respectively.

Both methods can be applied simultaneously.

NOTE: The time-interval-based reading method can also be applied in the Web
Interface

871 EN2Z-0937GE51 R0518


FALCON AND EAGLE CONTROLLERS CARE

Procedures

Time-interval-based Reading 1. On the Properties tab of the M-Bus device, enter the time interval in
Measurement Cycle.

NOTE: The default setting is 900 sec. Disable time-interval based reading by
entering ´0` if you want to exclusively use clock-time-based reading.

Clock-time-based Reading 1. Clock-time-based reading is based on:

• a binary value datapoint which defines the fixed clock-time in the time
program
• an IDT icon in the control loop that provides the trigger function. In the IDT
icon, the binary value datapoint is linked from the input to the trigger function
at the output.

For basic descriptions of datapoints, schedules and control loops procedures,


please refer to the "Create Datapoints", the "Schedules " and the "Control Loops"
sections.

2. Create a binary value datapoint.

EN2Z-0937GE51 R0518 872


CARE FALCON AND EAGLE CONTROLLERS

3. Create a schedule and assign the binary value datapoint to the switched
datapoint properties.

873 EN2Z-0937GE51 R0518


FALCON AND EAGLE CONTROLLERS CARE

4. Select the schedule default value ´OFF`.

IMPORTANT!
Note that the trigger for reading an M-Bus record is based on an OFF-ON
transition. ON-OFF transitions will not be considered.

EN2Z-0937GE51 R0518 874


CARE FALCON AND EAGLE CONTROLLERS

5. In the weekly program, create a switchpoint that defines the fixed time when the
OFF-ON transition occurs that triggers the M-Bus record reading.

6. Copy the switchpoint to the days when M-Bus record reading should be
executed.

7. Create a control loop and add an IDT icon to the workspace.

875 EN2Z-0937GE51 R0518


FALCON AND EAGLE CONTROLLERS CARE

8. On the Input tab, select Datapoint attribute type and then select the binary
value datapoint in Datapoint.

9. On the Output tab, select System data type and then select M-Bus trigger.

EN2Z-0937GE51 R0518 876


CARE FALCON AND EAGLE CONTROLLERS

10. Close all tabs and confirm finally by clicking OK to close the IDT icon.

RESULT: The binary value datapoint is assigned to the input and the
M-Bus trigger is assigned to the output. Based on the schedule
configuration in this example, M-Bus records will be read daily at
6:00 a.m.

User Access Manager


Purpose To define user rights according to the required functions. This will be done by
creating the users and issuing the functions they should have permission for in the
Web Interface (user access scheme). In addition to define the language and decimal
places of values to display in the Web Interface for each user.

NOTE: All users can operate all controllers of a project.

Copy Users Copying users is not part of the Use Access Manager, but will be done with the
Copy users function (see Copy Users section following the User Access Manager
functions descriptions)

Access Rights List An access rights list for a complete project will be created by assigning predefined
access levels to all executable functions (access rights) of the Web Interface. An
access rights list may look as follows:

Access Right Access level

877 EN2Z-0937GE51 R0518


FALCON AND EAGLE CONTROLLERS CARE

Change Communication Settings System Admin


Create and Delete Schedules Building Engineer
Create and Delete Trends Building Engineer
Display Diagnostics Tenant
etc. etc.

The predefined access levels are arranged hierarchically and the sequence with
descending priority is as follows:

• System Admin (128)


• Project Admin (115)
• Building Engineer (96)
• Operator (64)
• Tenant (32)
• Guest (0)

Example:
When assigning ´Operator` to ´Create & Delete Calendars`, a user having an access
level below ´Operator`, for example ´Tenant` or ´Guest`, is not able to create and
delete calendars. A user having a user access level equal to or higher than
´Operator`, for example ´Building Engineer` or ´Project Admin` is able to create and
delete calendars.

NOTE: When creating a project, the System Admin level is automatically


assigned to the user who has created the project. Only the user who has
System Admin access level can create new users, edit, or delete existing
users.

User Profile For each user within a project, a user profile with the following properties will be
created:

• User name
• Access level
• Language
• Decimal places
• Password
• Access rights
• Email address(es)

A user is identified by its user name. One of the predefined access levels will be
appropriately assigned to the user (name).

Due to the access rights list definitions, this assignment automatically determines
the set of access rights which the user is allowed to execute in the Web Interface.

All users having an access level higher than or equal to the assigned access level
will have this access right enabled in the Web Interface, all others will not.

NOTE: A user can carry out his/her assigned access rights in all controllers of the
project.

In addition, the user profile includes the settings of the language in which the Web
Interface is displayed and the number of decimal places of values to be displayed in
the Web Interface.

Finally, a password for each user must be issued for secure operation of the Web
Interface.

EN2Z-0937GE51 R0518 878


CARE FALCON AND EAGLE CONTROLLERS

USER PROFILE

PASSWORD

**********

USER NAME ACCESS LEVEL ACCESS RIGHTS (FUNCTIONS)

John Q. Public SystemAdmin Create and Delete Calendars


etc. Building Engineer Create and Delete Trends
Tenant Display Diagnostics
etc. etc.

LANGUAGE

English (U.S.)
etc.

DECIMAL
PLACES
2
3
etc.

Email Address
[email protected]
„second email address
„max. 5 email addresses“

Start User Access Manager


Procedure 1. Click menu item Project, then submenu item User/Access Manager.

RESULT: The User Access Manager dialog box displays.

879 EN2Z-0937GE51 R0518


FALCON AND EAGLE CONTROLLERS CARE

On the Users tab, users can be newly created, edited and


deleted. In addition, the user's password can be changed. By
default the SystemAdmin, the Guest, the xwadmin and the root
users are already available. For each user, the following
properties are shown:

• User Name
• Access Level
• Language
• Decimal Places
• Full Name
• E-Mail Address

For detailed information on the properties, please refer to the


"Create New User" section.

On the Access Rights tab, the access rights for all users will be
defined by assigning the predefined access levels to the
executable functions (see Create Access Rights section).

Create Access Rights List

Purpose To assign predefined access levels to all functions to be executed in the Web
Interface (access rights).

NOTE: Only the user who has System Admin or Project Admin access level can
create or edit access rights.

Procedure 1. In the User Access Manager dialog box, select the Access Rights tab.

EN2Z-0937GE51 R0518 880


CARE FALCON AND EAGLE CONTROLLERS

2. To each function as described in the Description column, assign the appropriate


access level by selecting it in the corresponding line in the Access level column.

Note that the access levels are arranged hierarchically with the following
sequence of descending priority:

• System Admin (128)


• Project Admin (115)
• Building Engineer (96)
• Operator (64)
• Tenant (32)
• Guest (0)

3. Click OK button to save settings.

4. To create a new user, continue as described under the Create New User
section.

Create New User

Purpose To create a new user.

NOTE: Only the user who has System Admin access level can create new users,
edit, or delete existing users.

Procedure 1. In the User Access Manager dialog box, select the Users tab.

881 EN2Z-0937GE51 R0518


FALCON AND EAGLE CONTROLLERS CARE

2. Click the New button.

RESULT: The Create/Edit User dialog box displays.

3. In the User Name field, enter a short form of the full user name.

EN2Z-0937GE51 R0518 882


CARE FALCON AND EAGLE CONTROLLERS

4. In the Full Name field, enter the full user name.

5. In the Password field, enter the password for the user.

6. In the Confirm Password field, confirm the new password by entering the
password again.

7. In the HMI Pin field, enter a 4-digit pin number the user should enter in order to
access the BACnet controller via Onboard HMI.

8. In the Confirm HMI Pin field, confirm the pin by entering the same number.

9. From the Access Level drop-down list box, select the access level.

Note that the access levels are arranged hierarchically with the following
sequence of descending priority:

• System Admin (128)


• Project Admin (115)
• Building Engineer (96)
• Operator (64)
• Tenant (32)
• Guest (0)

Due to the access rights list definitions (see Create Access Rights section), this
assignment automatically determines the set of access rights which the user is
allowed to execute in the Web Interface.

10. From the Language drop-down list box, select the language in which the Web
Interface should be displayed for the user.

Date Format
Displays the date format. It may be either dd.mm.yyyy or mm/dd/yyyy. The
controller stores the date format along with the language setting.

Time Format
Displays the time format. The controller stores the time format along with the
language setting.

11. From the Decimal drop-down list box, select the number of decimal places for
the display of values.

12. By default, the "Verify project password" option is checked. In this case, the
password will be verified when opening the project. Entering a wrong password
will disable project access.

Uncheck this option if you do not want CARE to proof for correct password input
when opening the project. In this case, project access is possible for all users
having system admin access level even if the password entered was wrong or
is missing.

The selected setting of this option applies to all users having SystemAdmin
access level.

13. Right to the E-Mail Address field, click the New button, if you want to add the
email address of the user. This step is mandatory if you want apply the Email
Alarming function for the controller (see "Email Alarming" section for details).

RESULT: The E-Mail Address dialog box displays.

883 EN2Z-0937GE51 R0518


FALCON AND EAGLE CONTROLLERS CARE

14. Enter the email address, and then click OK.

RESULT: The Create/Edit User dialog box redisplays. The email address
is added under E-Mail Address.

15. Click OK.

RESULT: The User Access Manager box redisplays. The email address is
assigned to the user as displayed in the E-Mail Address column
of the selected user.

EN2Z-0937GE51 R0518 884


CARE FALCON AND EAGLE CONTROLLERS

16. In the User Access Manager dialog box, click the OK button to save changes.

Edit User

Purpose To edit user name, access level and corresponding access rights, language, or
decimal places for a user.

NOTE: Only the user who has System Admin access level can create new users,
edit, or delete existing users.

Procedure 1. In the User Access Manager dialog box, select the Users tab.

2. Select the user you want to edit in the list and click the Edit button.

RESULT: The Create/Edit User dialog box displays.

885 EN2Z-0937GE51 R0518


FALCON AND EAGLE CONTROLLERS CARE

3. If desired, change the user name and/or the full name in the fields of the same
name.

4. If desired, change the access level by selecting another level from the Access
Level drop-down list box.

When changing the access level, note the sequence of descending priority of
access levels:

• System Admin (128)


• Project Admin (115)
• Building Engineer (96)
• Operator (64)
• Tenant (32)
• Guest (0)

If the access level has been changed, you should note the current access rights
definitions on the Access Rights tab in the User Access Manager dialog box.

5. If desired, change the language in which the Web Interface should be displayed
for the user by selecting another language from the Language drop-down list
box

6. If desired, change the number of decimal places for the display of values in the
Web Interface by selecting another value from the Decimal drop-down list box.

7. If desired, add a new email address by clicking the New button (see step 13 in
"Create New User" section. Or if you want the delete an email address, select
the email address in the list, and then click the Delete button.

EN2Z-0937GE51 R0518 886


CARE FALCON AND EAGLE CONTROLLERS

8. Click the OK button to save settings.

9. In the User Access Manager dialog box, click the OK button to save changes.

Delete User

Purpose To delete a user.

NOTE: Only the user who has System Admin access level can create new users,
edit, or delete existing users.

Procedure 1. In the User Access Manager dialog box, select the Users tab.

887 EN2Z-0937GE51 R0518


FALCON AND EAGLE CONTROLLERS CARE

2. Select the user you want to delete in the list and click the Delete button.

RESULT: The user is deleted from the list.

3. Click the OK button to save settings.

Change Password of "Standard" User

Purpose To change the password of a "standard" user. Standard users are all users
except the xwadmin and root users.

Procedure 1. In the User Access Manager dialog box, select the Users tab.

2. Select the user in the list and then click the Change Password button.

RESULT: The Edit Project Password dialog box displays.

3. In the New Password field, enter the new password.

4. In the Verify field, enter the same password.

5. Click the OK button to save settings.

CAUTION
For the user ´Guest` or ´guest` it is not allowed to issue the password
´Guest` or ´guest`. Login into the HTML interface using any of those
combinations is prohibited in order to protect the controller against cyber
attacks. Login is possible using a different user name or a different
password.

EN2Z-0937GE51 R0518 888


CARE FALCON AND EAGLE CONTROLLERS

Change Password of Root, FTP and Xwadmin Users

CAUTION
For old projects that include Excel web controllers with firmware earlier than
2.02.12 or Excel web II controllers with firmware earlier than 3.02.00 it is
strongly recommended to change the default passwords for the root, ftp, and
Xwadmin users in order to protect the controllers from cyber attacks.It is
recommended to change these passwords instantly when prompted after
opening the project. Otherwise the passwords should be changed here.

Purpose To change the password of the Root, FTP, and XWAdmin user.

Procedure 1. In the User Access Manager dialog box, select the Users tab.

2. Select the root user, ftpuser or xwadmin user in the list and then click the
Change/Show Password button.

RESULT: The Edit User Password dialog box displays. The old password
is shown.

3. In the New Password field, enter the new password.

4. Click the OK button to save settings.

889 EN2Z-0937GE51 R0518


FALCON AND EAGLE CONTROLLERS CARE

Change HMI Pin of User

NOTE: Only the user who has System Admin access level can change the HMI
Pin of a user.

Purpose To change the HMI Pin of a user.

Procedure 1. In the User Access Manager dialog box, select the Users tab.

2. Select the user in the list, and then click the Change HMI Pin button.

RESULT: The Edit HMI Pin dialog box displays.

3. In the New HMI Pin field, enter the new pin number.

4. In the Verify field, enter the same pin number.

5. Click the OK button to save settings.

Copy Users
Purpose Copying users between different projects.

Procedure 1. Open the source project from which you want to copy the users.

2. Click menu item Project, then submenu item Copy Users.

RESULT: The Copy Users dialog box displays. All users of the source
project are displayed in the list. By default, all users are
checked for copying in the Copy column.

EN2Z-0937GE51 R0518 890


CARE FALCON AND EAGLE CONTROLLERS

3. Uncheck the users you do not want to copy. Re-check users you want to copy.
You can check all users by clicking the check icon on the top and you can
uncheck all users by clicking the blank icon on the top.

4. From the Target Project drop-down listbox, select the project to which you want
to copy the users.

5. Click the OK button.

RESULT: The Copy Users dialog box is closed. The selected users are
copied to the target project and can be administered in the user
access manager opened in the target project.

Notification Class Manager


Purpose To adapt alarming to the central and 3rd party BACnet clients according to the
requirements.

This will be done by creating, editing and deleting notification class objects.
Notification class objects will be assigned to datapoints in order to enable alarming
for datapoints.

About the Notification Class Notification class objects represent and contain information required for the
Object Types distribution of event notifications within a BACnet system.
Notification Classes are useful for event-initiating objects that have identical needs
in terms of how their notifications should be handled, what the recipient(s) for their
notifications should be, and how they should be acknowledged.

A notification class defines how event notifications shall be prioritized in their


handling according to TO-OFFNORMAL, TO-FAULT, and TO-NORMAL events;
whether these categories of events require acknowledgment (nearly always by a
human operator); and what recipient devices (e.g. FALCON and EAGLE Web
Interfaces) or processes should receive notifications.

The purpose of prioritization is to provide a means to ensure that alarms or event


notifications with critical time considerations are not unnecessarily delayed. The
possible range of priorities is 0 - 255. A lower number indicates a higher priority.
Priorities may be assigned to TO-OFFNORMAL, TO-FAULT, and TO-NORMAL
events individually within a notification class.

The purpose of acknowledgment is to provide assurance that a notification has been


acted upon by some other agent, rather than simply having been received correctly
by another device. In most cases, acknowledgments come from human operators.

TO-OFFNORMAL, TO-FAULT, and TO-NORMAL events may, or may not, require


individual acknowledgment within a notification class.

It is often necessary for event notifications to be sent to multiple recipients or to


different recipients based on the time of day or day of week. Notification Classes
may specify a list of recipients, each of which is qualified by time, day of week, and
type of handling. A recipient is specified by a set of days of the week (Monday
through Sunday) during which the recipient is considered viable by the Notification
Class object. In addition, each recipient has a FromTime and ToTime, which specify
a window, on those days of the week, during which the recipient is viable. If an event
that uses a Notification Class object occurs and the day is one of the days of the
week that is valid for a given recipient and the time is within the window specified for
the recipient, then the recipient shall be sent a notification. Recipients may be
further qualified, as applicable, by any combination of the three event transitions TO-
OFFNORMAL, TO-FAULT, or TO-NORMAL.

The recipient also defines the device to receive the notification and a process within
the device. Processes are identified by numeric handles that are only meaningful to
the recipient device. The administration of these handles is a local matter. The
recipient device may be specified by either its unique Device Object_Identifier or its
BACnetAddress. In the latter case, a specific node address, a multicast address, or

891 EN2Z-0937GE51 R0518


FALCON AND EAGLE CONTROLLERS CARE

a broadcast address may be used. The recipient further specifies whether the
notification shall be sent using a confirmed or unconfirmed event notification.

How the notification class assignment is handled in CARE: please see the following
graphic.

NOTIFICATION CLASSES AND EVENT HANDLING

HTML CARE
INTERFACE
CLIENT

RECIPIENT A

Notification = High TRANSITIONS


To-OffNormal
To-Fault

DATAPOINT NOTIFICATION CLASS To-Normal

Analog Input Urgent


High
ALARMING (NOTIFICATION)
Low
Urgent
RECIPIENT B
High
Low Notification = High TRANSITIONS
To-OffNormal
To-Fault
TIMESTAMP TRANSITION EVENT
To-Normal
To-Normal To-OffNormal
To-Fault To-Fault
To-Normal

Start Notification Class Manager


Procedure 1. Click menu item Project, then submenu item Notification Class Manager.

RESULT: The Notification Classes dialog box displays.

EN2Z-0937GE51 R0518 892


CARE FALCON AND EAGLE CONTROLLERS

In the Notification Classes dialog box, the Urgent, High, and


Low notification classes are available by default.

NOTE: The default notification classes "urgent", "high", and "low" are
especially designed for the alarming to the central. In this case,
priorities must not be changed. For 3rd party BACnet clients,
new notification classes should be created if the default
notification classes do not meet exactly the requirements.

You can create new notification class objects, edit and delete
notification class objects (see respective sections in the
following).

Notification Class JOURNAL Usage


IMPORTANT
Any application that has been engineered by using the notification class
JOURNAL will not lose it. After application upload into CARE, all
notification classes which have been previously defined will be available in
CARE for further engineering and download.

Create New Notification Class Object

Purpose To create a new notification class in order to adapt the alarming to a 3rd party
BACnet client. The default notification classes "urgent", "high", and "low" are
especially designed for the alarming to the central.

Procedure 1. To create a new notification class object, click the New button in the Notification
Classes dialog box.

RESULT: The Create/Edit Notification Class dialog box displays.

893 EN2Z-0937GE51 R0518


FALCON AND EAGLE CONTROLLERS CARE

2. In the Name field, enter the name for the notification class object.

3. In the Description field, enter a description if desired.

4. In the Start Alarm time field, enter a time during which the notification of alarms
is suppressed. The start alarm time will become effective upon every
start/restart of the FALCON controller, e.g. power-on, application start, etc.
Entering a start alarm time is requested to prevent alarm shower at start/restart
of the controller.

5. Under Priority, enter the priority for the transitions. The following table may be
helpful for prioritizing:

Transitions
Event (Alarm) Category To Normal To Off-Normal To Fault
Urgent (range 0…84) 83 0 42
High (range 85…169) 168 86 127
Low (range 170…250) 250 171 210

6. Under Recipients, the destination devices that should receive the notification
will be created and can be edited and deleted.

7. To create a new recipient, click the New button.

RESULT: The Create/Edit Recipient dialog box displays.

EN2Z-0937GE51 R0518 894


CARE FALCON AND EAGLE CONTROLLERS

8. From the Recipient drop-down list box, select the recipient. The recipient is
shown by its path and device name, for example Subnet1 Falcon. Herewith
Subnet 1 is the path and Falcon the device name as shown in the network tree.

9. Under Valid Days, check the days on which the notification should be sent by
clicking the corresponding checkboxes.

10. Under Window of Time, check the time period, during which the notification
should be sent. Select All day to send the notification all day long. Enter the
time in the From Time and Time fields, if the notification should be sent during a
time period shorter than the whole day.

11. Under Transitions, check the transitions that should be sent by selecting the
corresponding checkboxes at:

To Off-Normal
The alarm reaches off-normal state, that is, the datapoint value exceeds the
high limit, respectively remains under the low limit.

To Fault
The alarm originates in a fault such as sensor break, etc.

To-Normal
The alarm is going to normal state, that is, the value of the datapoint remains
under the high limit, respectively exceeds the low limit.

12. Click the OK button to save settings.

RESULT: The Create/Edit Notification Class dialog box redisplays.

895 EN2Z-0937GE51 R0518


FALCON AND EAGLE CONTROLLERS CARE

Under Recipients, the device is inserted.

13. Click the OK button to save settings.

RESULT: The Notification Classes dialog box redisplays.

EN2Z-0937GE51 R0518 896


CARE FALCON AND EAGLE CONTROLLERS

In the list, the currently available notification class objects are


shown by name and description

14. Click the OK button to save settings.

RESULT: The Notification classes are now available for assignment to


datapoints.

Edit Notification Class Object

Purpose To edit a notification class object in order to adapt the alarming to a 3rd party
BACnet client.

NOTE: The default notification classes "urgent", "high", and "low" are especially
designed for the alarming to the central and must not be changed.

Procedure 1. In the Notification Classes dialog box, select the notification class object in the
list and click the Edit button.

897 EN2Z-0937GE51 R0518


FALCON AND EAGLE CONTROLLERS CARE

RESULT: The Create/Edit Notification Class dialog box displays.

EN2Z-0937GE51 R0518 898


CARE FALCON AND EAGLE CONTROLLERS

2. Change the desired options and/or values such as Name or Priority. Edit the
recipients list by changing recipients data or deleting recipients from the list (for
detailed description of the items see Create New Notification Class Object
section).

Delete Notification Class Object

Purpose To delete a notification class object.

Procedure 1. In the Notification Classes dialog box, select the notification class object in the
list and click the Delete button.

RESULT: The notification class object is deleted from the list.

2. Click the OK button to save settings.

899 EN2Z-0937GE51 R0518


FALCON AND EAGLE CONTROLLERS CARE

Application Generator
Purpose With the application generator you can automatically create applications (control
loops) for plants of Excel toolkit projects.

This includes the connection of macros to datapoints with point roles according to
defined rules.

Applications can be created for a single controller with all its plants or the project
which creates applications for all plants of the project.

Prerequisites Excel toolkit automation file (XLT) must be available and the macro library must be
part of the CARE database.

Procedure 1. In the tree, select the controller, for which you want to create applications. Or,
select the project if you want to create applications for all controllers.

2. Click menu item Controller, then submenu item Application Generator.

RESULT: The Open dialog box displays.

3. Browse to the folder where the XLT file is saved.

4. Select the XLT file and click Open.

RESULT: If datapoints must be manually connected to macros, the


Connect Datapoints dialog box displays.

EN2Z-0937GE51 R0518 900


CARE FALCON AND EAGLE CONTROLLERS

On the top, the name of the current plant and its control loop is
shown in bold. In the tree, the plants (main entries of the tree)
and their datapoints (subentries of the tree) are shown. When a
plant shows multiple datapoints, all datapoints have the same
role. The same role can be assigned to multiple datapoints in
different plants.

5. Select the datapoint in the tree, and then do one of the following:

d. To connect the selected datapoint, click Connect.


e. To connect all datapoints of the plant having the same EDK, will be
connected without any further request, click Connect all.
f. To skip the connection of a datapoint, click Skip Point.
g. To skip the connection of the complete control loop, click Skip Loop.
h. To skip the whole connecting process, click Cancel.

RESULT: After the datapoints have been successfully connected, the


Application Generator Action-Log dialog box displays showing
log categories errors, warnings and actions with their messages
, caused by the connecting process. Errors have a higher
severity than warnings. For example, errors result from the
failure of creating a control loop at all, whereas warnings may
result from unoccupied inputs or outputs. Actions have no
negative impact on the application generation result.

901 EN2Z-0937GE51 R0518


FALCON AND EAGLE CONTROLLERS CARE

6. To hide a log category, uncheck the corresponding checkbox.

7. To save the action log as TXT file, click ActionLog on top and click Export.

8. In the Save As dialog box, browse to the destination folder, enter a file name in
the File name field, and then click Save.

9. Click Exit.

RESULT: If the application generation is successfully done, the control


loops are created for the plants.

EN2Z-0937GE51 R0518 902


CARE FALCON AND EAGLE CONTROLLERS

Event Enrollment Objects / Algorithmic Change Reporting


Event Enrollment Objects

The primary purpose for Event Enrollment objects is to define an event and to
provide a connection between the occurrence of an event and the transmission of a
notification message to one or more recipients.
The Event Enrollment object contains the event-type description, the parameters
needed to determine if the event has occurred (Algorithmic Change Reporting), and
a device to be notified. Alternatively, a Notification Class object may serve to identify
the recipients of event notifications. A device is considered to be "enrolled for event
notification" if it is the recipient to be notified or one of the recipients in a Notification
Class object referenced by the Event Enrollment object. Event Enrollment objects
are the basics for algorithmic change reporting.

Algorithmic Change Reporting

Algorithmic change reporting enables a BACnet device to provide one or more alarm
or event sources, defined by Event Enrollment objects, to generate alarm or event
notifications that may be directed to one or more recipients. Any of the
standardized algorithms may be used to establish criteria for change reporting.
Once established, occurrences of change may be reported to one or more recipients
based on further criteria. Changes of value of specific properties of an object may be
programmed to trigger event notifications to be sent to one or more recipients based
on a notification class. Typically, event notifications are sent to application programs
represented by processes within a notification-client device. The object(s) whose
properties are referred to is known as the Reference Object(s). The criteria used to
ascertain that an event has occurred are determined by the Event Type, for
example, CHANGE OF BITSTRING, CHANGE OF STATE etc.

Enable Event Enrollment Alarming for Plant


Purpose Enable the Event Enrollment Alarming for the plant. This allows algorithmic change
reporting based on the event enrollment object type. For basic information on Event
enrollments, please refer to the “Event Enrollment Objects” section.

Procedure 1. In the logical plant tree, click on the plant.

2. On the right pane, click on the Alarming tab.

RESULT: On the Alarming tab on the right, do the following:

903 EN2Z-0937GE51 R0518


FALCON AND EAGLE CONTROLLERS CARE

3. In the Name field, change the default name.

4. In the Description field, enter a meaningful description.

5. In the Event Type field, note that the event type of the event enrollment object
for the plant alarming is ´change of state`.
6. Under Program Object States, the Normal and Off-Normal States the plant
can have are displayed. This is for display only. Event enrollment alarms can be
triggered by enabling transitions from Normal to Off-Normal and vice verse
under Transition Events on this tab.

7. In the Alarm Delay field, enter an alarm delay in sec. The event enrollment
alarm will be sent after the time entered here has been elapsed.

8. From the Notify Type drop-down listbox, select the notify type.

9. From the Notification Class drop-down listbox, select the notification class that
defines the recipient to which the event enrollment alarm is sent after a
transition has occurred.

10. Under Transition Events, check the transition events that should trigger the
event enrollment alarming. For plants, the ´To-Off-Normal` and the ´Back to
Normal` transitions can be selected. Refer to the relevant states listed under
Program Object States.

EN2Z-0937GE51 R0518 904


CARE FALCON AND EAGLE CONTROLLERS

Example: When selecting ´To-Off-Normal`, each transition from


´RUNNING` (Normal State) to any of the Off-Normal States, for
example ´HALTED`, will cause an event enrollment alarm.

Enable Event Enrollment Alarming for Controller System Status


Purpose Enable the Event Enrollment Alarming for the controller. This allows algorithmic
change reporting based on the event enrollment object type. For basic information
on Event enrollments, please refer to the “Event Enrollment Objects” section. .

Procedure 1. In the logical plant tree, click on the controller.

2. On the right pane, click on the System Status tab.

RESULT: On the System Status tab on the right, do the following:

3. In the Name field, change the default name if desired.

4. In the Description field, enter a meaningful description.

5. In the Event Type field, note that the event type of the event enrollment object
for the controller is ´change of state`.

6. Under Device Object States, the Normal and Off-Normal States the controller
can have, are displayed. This is for display only. Event enrollment alarms of the
controller can be triggered by enabling transitions from Normal to Off-Normal
and vice verse under Transition Events on this tab.

7. In the Alarm Delay field, enter an alarm delay in sec. The event enrollment
alarm will be sent after the time entered here has been elapsed.

8. From the Notify Type drop-down listbox, select the notify type.

905 EN2Z-0937GE51 R0518


FALCON AND EAGLE CONTROLLERS CARE

9. From the Notification Class drop-down listbox, select the notification class
that defines the recipient to which the event enrollment alarm is sent after the
selected transition has occurred.

10. Under Transition Events, check the transition events that should trigger the
event enrollment alarming. For the controller, the ´To-Off-Normal` and the ´To
Normal` transitions can be selected. Refer to the relevant states listed under
Device Object States.

Example: When selecting ´To-Off-Normal`, each transition from


´RUNNING` (Normal State) to any of the Off-Normal States, for
example ´HALTED`, will cause an event enrollment alarm.

Email Alarming
Purpose Sending an email to a definable email-recipient in case of alarms of selectable
datapoints. Alarms may be generated for each datapoint that has the appropriate
notification class assigned and the alarm reporting enabled. The email includes an
attachment (.TXT) that shows a detailed description of the alarm data, for example:

Democase_Controller
http://192.168.200.10
URGENT (193)
Outdoor_Temperature
2008-March-12 We 14:29:16
Notify Type: Alarm
Event Type: Out Of Range
Description: Smart_IO_AI2
Present Value: 50 °C
Low Limit: 3 °C - High Limit: 40 °C

Steps Setting up the email alarming process includes the following major steps
summarized in the following procedure:

In CARE

a. Assign email address to the user that receives the alarm email(s)
(recipient)
b. Assign recipient and email address to the notification class
c. Define alarming conditions for datapoint(s) that should send alarm
emails
d. Enable enhanced BACnet properties for the controller
e. Enter E-Mail alarming properties
f. Connect to controller
g. Translate and download application
h. Download controller settings

In the Web Interface

i. Send Test Email

Procedure 1. In CARE, click menu item Project, then submenu item User/Access Manager.

RESULT: The User Access Manager dialog box displays.

EN2Z-0937GE51 R0518 906


CARE FALCON AND EAGLE CONTROLLERS

2. Select the user in the list, and then click Edit button.

RESULT: The Create / Edit User dialog box displays.

907 EN2Z-0937GE51 R0518


FALCON AND EAGLE CONTROLLERS CARE

3. Click New button.

RESULT: The E-Mail Address dialog box displays.

4. Enter the email address, and then click OK.

RESULT: The Create / Edit User dialog box redisplays. The email address
is added under E-Mail Address.

EN2Z-0937GE51 R0518 908


CARE FALCON AND EAGLE CONTROLLERS

5. Click OK.

RESULT: The User Access Manager box redisplays. The email address is
assigned to the user as displayed in the E-Mail Address column
of the selected user.

6. Click OK.

7. Click menu item Project, then submenu item Notification Class Manager.

RESULT: The Notification Classes dialog box displays.

909 EN2Z-0937GE51 R0518


FALCON AND EAGLE CONTROLLERS CARE

8. Double-click the notification class that you want to apply for sending the email
alarm, for example, URGENT.

RESULT: The Create/Edit Notification Class dialog box displays.

EN2Z-0937GE51 R0518 910


CARE FALCON AND EAGLE CONTROLLERS

9. Click New button to create the recipient that should receive the alarms of the
selected notification class.

RESULT: The Create/Edit Recipient dialog box displays.

911 EN2Z-0937GE51 R0518


FALCON AND EAGLE CONTROLLERS CARE

10. Select E-Mail Address radio-button.

11. From the Users drop-down listbox, select the user.

RESULT: The email address of the selected user as assigned in the User
Access Manager is displayed in the E-Mail Address list.

12. Click the ´Double-Arrow` button right to the list.

RESULT: The email is inserted in the E-Mail Address field above the E-
Mail Address list.

EN2Z-0937GE51 R0518 912


CARE FALCON AND EAGLE CONTROLLERS

13. Choose options and enter values under Valid Days, Windows of time,
Transitions, and Process ID according to your needs (for details see
“Notification Class Manager” section of this User Guide).

14. Click OK.

RESULT: The Create/Edit Notification Class dialog box redisplays. The


new recipient with its email address is added under Recipients.

913 EN2Z-0937GE51 R0518


FALCON AND EAGLE CONTROLLERS CARE

15. Click OK.

16. In the Notification Classes dialog box, click OK.

17. In the Logical Plant tree, expand the tree and select the datapoint for which you
want to send emails in case the point gets in alarm.

18. Under Alarming you set the basic prerequisites for a selected point enabling
the controller sending an alarm for the point.

EN2Z-0937GE51 R0518 914


CARE FALCON AND EAGLE CONTROLLERS

19. From the Notification Class drop-down listbox, select the same notification
class you have assigned to the email recipient.
NOTE: You must select a notification class in order to enable email alarming.
If you do not select the same notification class as assigned to the
email recipient, alarm emails will not reach the email recipient.

20. In the Alarm Delay field, enter an alarm delay value in second if desired. The
alarm delay is the time interval the alarm is sent after the alarm has occurred.

21. Check the High Limit Reporting and/or Low Limit Reporting check boxes,
and if desired change the values.

NOTE: You must enable High Limit Reporting and/or Low Limit Reporting
in order to enable email alarming.

22. Enter/change individual alarm values for the datapoint, for example, for analog
inputs, the deadband in the Deadband field (see “BACnet Point Descriptions”
section for details on datapoint properties).

23. From the Notify Type drop-down listbox, select the type of notification, alarm or
event.

24. Under Transition Events, check the transition events that should be time
stamped in the Web Interface.

NOTE: Enabling transition events is no prerequisite for the email alarming


function.

25. In the Logical Plant tree, expand the tree and select the controller you want to
send emails in case of alarms.

26. On the right pane, click the Properties tab, and check the FALCON 2.0
application format check box. Besides other functions, this provides the email
alarming function for the controller.

27. On the right pane, click the E-Mail Alarming tab, and enter the following
properties:

915 EN2Z-0937GE51 R0518


FALCON AND EAGLE CONTROLLERS CARE

NOTE: For detailed information on data to be entered here, please ask your
network administrator or the responsible person who is in charge of
the I.T. environment. Note that, depending on your requirements and
your local I.T. environment, not all fields must be filled out.

E-Mail Mode

Select the connection type from:

• Network
Alarm emails are sent via network to the recipient.
• Dialup (not applicable to EAGLE controller)
Alarm emails are sent via modem to the recipient.
• Disabled
No data can be entered on this tab and the controller will not be able to
perform email alarming.

E-Mail Alarming

E-Mail Address (Sender)


Enter the email address of the sender.

Crash E-Mail Address


Enter the email address that should receive an email in case the controller
crashes.

EN2Z-0937GE51 R0518 916


CARE FALCON AND EAGLE CONTROLLERS

E-Mail Subject Prefix String


This is the default prefix of the email subject name. Default is ´Alarm`. Change
the prefix if desired.

E-Mail Send Repeat Time (Minutes) ... Enabled


Checking the Enabled check box enables the controller sending emails when
alarms occur.

If E-Mail alarming is enabled, enter the time interval in minutes, the email
should be repeatedly sent to the recipient.

NOTE: When firstly setting up the email alarming function, do not check this
option unless you have performed the email test with the FALCON
HTML Interface. It is recommended to check this option only when you
are sure that the entered data are correct and emails will be sent to the
right recipient, by using the existing and already tested ´email send
path`.

Example:
Reuse of the established email send path after application modifications and
subsequent application download

Observe E-Mail Alarming


(for details, see “Observe E-Mail Alarming” )

Server Settings (´Network` E-Mail Mode only)

SMTP Server
Select this option, and enter the name of the SMTP server.

NOTE: The addresses for the DNS Server(s) must be entered on the subnet
level in the BACnet network tree.

IP Address
Select this option, and enter the IP address of the SMTP server.

Port Settings

Default
Check this checkbox if you want to use port 25. Uncheck this checkbox if you
want use another port.

Port
Uncheck the Default checkbox, and enter the port number.

Authentication

Secure Authentication
Uncheck this checkbox if the server does not need authentication.
Check this checkbox, if the server needs authentication, and then enter user
name and password.

Security
Select one of the following options for email communication:

• Never
no security is provided
• TLS (Transport Layer Security)
This is the successor of SSL
• SSL (Secure Socket Layer)
This is the predecessor of TLS

There are slight differences between TLS and SSL, but they are essentially
the same.

917 EN2Z-0937GE51 R0518


FALCON AND EAGLE CONTROLLERS CARE

Dialup Settings (´Dialup` E-Mail Mode only; applies to FALCON controller


only)

ISP Phone Number


Enter the phone number of the ISP (Internet Service Provider).

ISP User Name


Enter the user name of the ISP (Internet Service Provider).

ISP Password
Enter the password of the ISP (Internet Service Provider).

28. On the right pane, click the Setup tab.

29. Connect to the controller by clicking the Connect button. Make sure the IP
address of the controller is correct in case you have problems connecting to the
controller.

30. If not already done, translate and/ or download the application by clicking the
Translate respectively the Download button under Application.

31. Click the Download Settings button under Controller.

32. Confirm the message box for updating by clicking OK.

33. Confirm the following message box by clicking OK.

34. Re-Connect to the controller by clicking the Connect button.

RESULT: The settings of the controller are updated with the email
alarming settings.

35. To check for correct communication settings, click the plus icon at TCP and
check if the data displayed are consistent with the data you have entered on the
E-Mail Alarming tab. If not, check the data on the E-Mail Alarming tab, modify if
necessary, and download the settings again.

EN2Z-0937GE51 R0518 918


CARE FALCON AND EAGLE CONTROLLERS

36. Start the Web Interface and perform steps as described in the "Email Alarming"
section in the Excel Web User Guide EN2B-0289GE51 and EAGLE Web
Interface User Guide EN2Z-0970GE51.

Enable Event Enrollment Alarming for Controller E-Mail Alarming


Purpose Enable the Event Enrollment for the Email Alarming of the controller. This allows
algorithmic change reporting based on the event enrollment object type for the email
alarming. For basic information on Event enrollments, please refer to the “Event
Enrollment Objects” section. .

Procedure 1. On the E-Mail Alarming tab, click Edit button.

RESULT: The Event Enrollment dialog box displays.

919 EN2Z-0937GE51 R0518


FALCON AND EAGLE CONTROLLERS CARE

2. Enable the alarming as follows:

j. In the Name field, change the default name.


k. In the Description field, enter a meaningful description.
l. In the Event Type field, note that the event type of the event
enrollment object for the email alarming is ´change of state`.
m. Under E-Mail Send States, the Normal and Off-Normal States the
email alarming can have, are displayed. This is for display only.
Alarms can be triggered by enabling transitions from Normal to Off-
Normal and vice verse under Transition Events on this tab.
n. In the Alarm Delay field, enter an alarm delay in sec. The event
enrollment alarm will be sent after the time entered here has been
elapsed.
o. From the Notify Type drop-down listbox, select the notify type.
p. From the Notification Class drop-down listbox, select the
notification class that defines the recipient to which the alarm is sent
after a transition has occurred.
q. Under Transition Events, check the transition events that should
trigger the event enrollment alarming. For email alarming, the ´To-
Off-Normal` and the ´Back to Normal` transitions can be selected.
Refer to the relevant states listed under E-Mail Send States.

Example: When selecting ´To-Off-Normal`, each transition from ´EMAIL_


INPROCESS` (Normal State) to any of the Off-Normal States,
for example EMAIL_FAILED, will cause an event enrollment
alarm.

EN2Z-0937GE51 R0518 920


CARE BACNET

Control Loops
NOTE: This section applies to the FALCON and EAGLE controllers only.

Purpose The data processing of the controller is programmed in control loops. They are
defined by authorized users, using the CARE-software. CARE comes with basic
functions; you may order more extensive macros from Honeywell.

A control loop receives the input values from sensors and other hardware
components. The controller calculates with these values and determines if a
regulation is necessary. In such a case, the controller initiates the predefined
reaction by switching the connected hardware on.

Types There are three types of functions:


• Functions
• Functions are basic logic elements with which you can build macros. They
cannot be created, edited or removed.
• Macros in plant
• Macros are software modules programmed from functions.
Macros in a plant are available in a single plant. It is in the user’s hand to create,
edit or remove such macros.
• System Macros
System Macros are provided by Honeywell.
They are available for all projects of the Database. These macros are protected
against editing and removing.

Mouse and Function Keys


Purpose Additional navigation tools to the standard window functions are available for more
comfortable handling of the macros.

Prerequisites 1. The user is logged in.

Procedure 1. Enter any Macro window:

• Macro window of a control loop.


• Macro window of a macro.
• Macro window of a global macro.

921 EN2Z-0937GE51 R0518


BACNET CARE

2. Click once into the free space of the Macro window.

RESULT: The Macro window is selected.

Macro window

3. Use the following function keys as needed.


Denotation of the function keys:

• F1
Opens the online-help window conform
• F2
Displays the area around the mouse-cursor in the middle. E.g. If the mouse
cursor is on the left side, the view will be moved to the right side.
• F3
Zooms out to display the whole window so all used icons are visible.
• F4
Switches the zoom mode on and off.
• F5
Opens the Loop Properties or Macro Properties dialog box.
• F7
Creates a new macro, including all present selected functions and macros.
• F8
Opens the Edit Flags dialog box.
• F9
Sets execution order of control icons manually.
• CTRL + A
Selects all control icons.
• CTRL + F
Opens the Find dialog box.
• CTRL + L
Aligns all selected icons to the left

EN2Z-0937GE51 R0518 922


CARE BACNET

• CTRL + T
Aligns all selected icons to the top
• CTRL + R
Autoroutes selected lines

• Mouse functions:
• Shift + mouse wheel
Hold the Shift key pressed and then scroll with the mouse wheel the view to
the left and to the right.
• Shift + Ctrl + mouse wheel
Hold the Shift and the Ctrl key pressed and then use the mouse to zoom
with wheel the view in and out the area around the mouse cursor.
• Shift + left mouse key
Hold the Shift key pressed and then click on icons you want to select.

Toolbar Buttons

Displayed and changed the numerous zoom factor in percent of the whole view,
centered by the opened window.

Enables Zoom mode, in which you can zoom the selected items and zooms in the
workspace/selected area.

Enables the Move mode, in which you can move the view of the macro window.

Enables the Select/Edit mode, in which you can you can select and move
elements in the Macro window, draw connections between outputs and inputs and
insert text into the Macro window.

Switches to the previous view. The last change of the view is reverted.

Switches to the next view. The last undo of the view is reverted.

Opens the global macro library.

General Functions
Insert Text
You may insert text in all the editor views. To insert text, right-click to open the
context menu and select “insert text”. A dialog opens in which you can type the
text and select text attributes.

Mirrored
Control icons can be mirrored. Right-click the context menu and select “mirrored”.
To insert all icons by default mirrored, select in the main menu “Plant > Control
Editor > Add new icons mirrored.”

Background
The background is divided into squares. Each square represents the area of one
page in the project documentation.

923 EN2Z-0937GE51 R0518


BACNET CARE

Execution Order
The numbers in brackets, e.g. [15], underneath the icons show the priority of the
execution order. The priorities are generated on saving and leaving the control
editor. The priorities can be changed

Datapoints
Datapoints can be dragged directly from the project tree and dropped into the
control editor. If the datapoint is output or variable the context menu of the
datapoint icon allows the toggle between read or write.

IDT Function
The IDT icon has two kinds of views. Regularly the IDT icon has an input and an
output. If you set input or output on connection, and the other not, the view of the
icon changes to a special view without the title bar (as used for datapoints
dropped from the project tree).

Grid Lines
Grid lines can be shown or blanked.
Select in the main menu "Plant > Control Editor > Show grid lines" to toggle
between the grid line display mode.

Autorouting Connection Lines


By default, connection lines between control icons are autorouted when they are
created and when control icons are moved, that is, they will be optimized for
display (short, space consuming). Selected connection lines can be autorouted
explicitly, if desired. To autoroute one particular connection line, select the
connection line, click right button and click on Autoroute in the context menu, or,
to autoroute multiple connection lines, select them and press CTRL + R keys.

Create Control Loop


Prerequisites 1. The user is logged in.
2. A project is open.
3. The open project has at least one controller and one plant.

Procedure 1. Expand the view of the plant, you want assign a control loop to.

2. Click with the right mouse button on the “Control Loops”-icon.

RESULT: The context menu to create a control loop opens.

3. Click on it with the left mouse button.

RESULT: A new icon “New Control Loop” opens on the left pane.

4. Double-click on the icon of the new control loop.

RESULT: The macros window of the control loop opens on the right pane.

5. Click on the tab “New Control Loop”.

RESULT: The Properties window of the control loop opens on the right
pane.

EN2Z-0937GE51 R0518 924


CARE BACNET

Fill in the fields according to your requirements:

• Loop Name
Unique name of the loop. The name should consist of up to 40 characters
and/or digits and/or ASCII special characters.
• Description
Description of the loop, e.g. what’s the function of the loop or which special
functions are used within this loop.
• Speed Class
Defines how often the loop will be automatically executed by the controller.
The time slice of the speed class is defined in the property sheet of the
controller (see “Display/Modify Controller Properties” and “Set Execution
Speed Categories” sections).
• Write Priority (only displayed)
Datapoints for data transfer include a “Write Priority”. In case some
components write to the same data point, only the value, unequal to zero,
with the highest priority will written to the output. All other values will be
stored, but they have no influence for regulation.
• Read Access Level
Someone with these, or higher access rights can view this loop (via web-
interface).
• Write Access Level
Someone with these, or higher access rights can edit this loop (via web-
interface).
Fill the input fields according to your requirements.

RESULT: All Inputs are automatically saved.

Now can you define the logic of the new control loop.

925 EN2Z-0937GE51 R0518


BACNET CARE

Edit Control Loop Properties


Prerequisites 1. The user is logged in.
2. A project is open.
3. The open project has at least one controller, one plant and one control loop.

Procedure 1. Expand the tree view of the control loops of the plant, the control loop is
assigned to.

2. Double-click on the icon of the control loop you want to edit.

RESULT: The macros window of the control loop opens in the right pane.

3. Click on tab “<name of the control loop>”.

RESULT: The properties of the control loop are open in the right pane.

Change the entries in the following input fields according to your requirements:

• Loop Name
Unique name of the loop. The name should consist of up to 40 characters
and/or digits and/or ASCII special characters.
• Description
Description of the loop, e.g. what’s the function of the loop or which special
functions are used within this loop.
• Speed Class
Defines how often the loop will be automatically executed by the controller.
The time slice of the speed class is defined in the property sheet of the

EN2Z-0937GE51 R0518 926


CARE BACNET

controller. (see “Display/Modify Controller Properties” and “Set Execution


Speed Categories” sections).
• Write Priority (only displayed)
Datapoints for data transfer include a “Write Priority”. In case some
components write to the same data point, only the value, unequal to zero,
with the highest priority will written to the output. All other values will be
stored, but they have no influence for regulation.
• Read Access Level
Someone with these, or higher access rights can view this loop (via web-
interface).
• Write Access Level
Someone with these, or higher access rights can edit this loop (via web-
interface).

RESULT: All Inputs are automatically saved.

Create and Edit control Loop Logic


Prerequisites 1. The user is logged in.
2. A project is open.
3. The open project has at least one controller and one plant and one control
loop.

Procedure 1. Expand the tree view of the plant for which you want create or edit a control
loop.

2. Double-click on the icon of the control loop you want to edit.

RESULT: The Macro window of the control loop opens in the right pane.

927 EN2Z-0937GE51 R0518


BACNET CARE

3. Define the content of the loop as desired. Assign functions or


hardware/software points to the loop by using the window known function of
drag & drop:
• Click once on the desired icon and hold the left mouse-button pressed.
• Move the cursor into the Macro window. The cursor becomes a “No
Parking”-sign if it is moved in areas, you cannot drop the component into.
• Release the left mouse button.

You are able to transfer elements from the following windows into the Macro
window:
• From the controllers view (upper left from the macro window).
• From the functions view (down left from the macro window).
• From the Macros in plant view. To open the Macros in plant view, move the
mouse cursor on the sensitive field in the upper left corner of the macro
window:

• From the Global Macro Library. To open the Global Macro library, click
menu item Database, then submenu item Macro Library… , or click on
button:

RESULT: The function or component displays in the Macro window.

Meaning of the colours:


• red
The setup of the icon is incomplete. All inputs must get a value, e.g. by
connecting it to an output or by defining it as a constant.
• blue
The icon is selected.
• none colored (light grey)
The setup of the icon is accomplished, no errors are expected.

For setting up a connection between input and output, see step 8.

EN2Z-0937GE51 R0518 928


CARE BACNET

4. Apply the procedure written above with all components and functions you want
to combine in this loop.

• All icons in the Macro window can be moved via drag & drop.
• You can use the windows known short keys, e.g. “Ctrl + A” for selecting all
elements in the active window.
• To enter the menu Plant, make sure, the Macro window is still selected:
Click once with the left mouse button in the Macro window.

RESULT: The following buttons and drop-down list in the taskbar are
activated (from left to the right):

- Zoom:
Display and change the numerous zoom factor of the whole
view, centered by the opened window.
- Zoom:
Use this button(s) to zoom in a selected area.
- Move all:
The cursor becomes changed to a hand and you can move the
view of the Macro window.
- Select and edit:
The cursor becomes changed to standard and you can select
elements in the Macro window, draw connections between
outputs and inputs and insert text into the Macro window.
- Last view
The last change of the view is reverted.
- Next view
The last undo of the view is reverted.

The elements in the Macro window are displayed in the


following manner:
Hardware/software point, in most cases a real input or output of
the controller.

Function, indicated by the separated header and input and


output ports. The name of the function is displayed in this
header.

You can always connect an analog and digital port. The input
port translates the input signal into his own format (analog or
binary) some information may be lost. A warning informs you
about a data mismatch, if you set up a connection between
analog and digital ports that have different signal formats.

Digital port. Can have two values: TRUE (1) or FALSE (0).

Any port, this port is not predefined as an analog or digital


input. The type of data depends on the further processing.

929 EN2Z-0937GE51 R0518


BACNET CARE

Some types of I/O connections are shown with one or two


letters in the connector box. The meanings of these letters are
described in the following table:

Letters Meaning
“P” Parameter
“I” Macro input
“O” Macro output
“C” Constant
“D” Datapoint property
“Pr” Point role
“S” System data
“pr” Function p register
“ur” Function u register
“F” Flag point

The black point in the header indicates the side of the output
ports.

A line at the bottom of the icon indicates hidden (invisible)


ports. You can make them visible using the Properties window
of these ports.

Input ports are red coloured, if they are not connected, if they
do not get any input. The color green indicates the accurate
connection of the port. Pointroles are not a valid connection and
must be changed for translation. Thus pointroles are also red.

The configuration of inputs is indicated as follows:


If an input port is configured as datapoint attribute, the default
datapoint property "Present Value" is displayed in the tooltip of
the port. If any other property is selected as datapoint attribute,
e.g. Polarity, this is shown in the tooltip and additionally in
brackets at the port.

EN2Z-0937GE51 R0518 930


CARE BACNET

5. Setup the properties of the functions and hardware/software points as follows:

• Click with right mouse button on the element, you want to set up.

RESULT: The context menu of the element displays.

• Click on Properties.

RESULT: The Function properties:<name> dialog box of the element


opens.

a. In tab General are the following input fields:


• Name
Alias of this element. The alias can consist of up to 32
characters and/or digits. This alias is displayed in the tab
Internal Parameter of parent macros (only if the alias-
element includes parameters).
• No. of inputs
Number of input (in some cases output) connections of the
element.

You have to apply changes of the input/output count before you can view the
changed number in the input/output tab.

931 EN2Z-0937GE51 R0518


BACNET CARE

An input always must be filled with a value. The value could be e.g. a connection (to
the output of another element) or a data point or system data. It is possible to hide
an input/output if it is not a connection.

The available input connections are displayed in the tab Input.

Select the tab.

Select the properties of the input by double-clicking into the desired row of the
table.

RESULT: The configuration dialog box for selecting type and target for
the input opens.

EN2Z-0937GE51 R0518 932


CARE BACNET

- Connection
The input is defined as a connection to one output of another
element of this loop. This input will be always displayed in the
Macro window.

- Constant
The input is always set up to this value. It is possible to hide
this input in the Macro window.
- Loop/Macro Parameter (not available while editing control loop)
A parameter can be used by all functions and macros of this
loop/macro without being connected. So it is possible to simplify
the displayed connections. The input becomes this value.
It is possible to hide this input in the Macro window.
- Macro input (not available while editing control loop)
- Macro output (not available while editing control loop)
- Data point attribute
The input becomes a value of a data point attribute. Datapoints
are hardware/software points, e.g. sensors. The list of available
attributes depends on the type of the datapoint and if this
attribute is used for an input or output. It is possible to hide this
input in the Macro window. For detailed descriptions of the
Datapoint attributes, please refer to the Excel Web User Guide
EN2B-0289GE51 and the EAGLE Web Interface User Guide
EN2Z-0970GE51.
- System data
The input becomes the value of the system function, such as
´clock`. The following system values are stored:

- Alarm status LED


reads the value of the red alarm LED
0 = Off (no alarm)
1 = license status error
2 = USB error (connected USB device draws more than
500 mA)
4 = panel bus error (e.g. I/O module missing)
8 = LON bus error (e.g. I/O module missing)
16 = sensor error on universal input which is used by the
application (e.g. sensor short, break)
combinations of values are possible (e.g. 4+8=12: panel bus
error and LON bus error at the same time)

- Application LED
reads and writes the status of the application LED
0 = Off
1 = On: permanently

933 EN2Z-0937GE51 R0518


BACNET CARE

2 = On: continuously blinking (on-off)


3 = On: 2 times continuously blinking (2 x (on-off), pause ..)
4 = On: 3 times continuously blinking (3 x (on-off), pause ..)
5 = On: 4 times continuously blinking (4 x (on-off), pause ..)
6 = On: 5 times continuously blinking (5 x (on-off), pause ..)

- Cycle Time
reads the set current cyle time of the application part in sec

- Day and month


actual date (=100*month+day)

- Day of week
actual day of the week (monday(1)…saturday(7))

- Hours and minutes


actual time (=100*hours+minutes)
- Minutes since midnight
number of minutes after midnight

- Startup flag
indicates, if the system has been restarted

- Year
actual year

It is possible to hide this input in the Macro window.


- Pointrole
Datapoints can be combined in so called pointroles. It is easier
to sort the datapoints by their main properties. Select a data
point from the pointrole.
It is possible to hide this input in the Macro window.
- Function parameter
The input changes to the value of a parameter of one
function/macro (which includes parameters) included in this
control loop. Only functions with parameters are listed. If a
function has no (alias) name, an identifier (‘$’ followed by a
unique number) is assigned. This identifier is also displayed
below the symbol as long as no name is set.
It is possible to hide this input in the Macro window.
- Function register
The output sets the hidden stored value of one function/macro
included in this macro. If a function has no (alias) name, an
identifier (‘$’ followed by a unique number) is assigned. This
identifier is displayed below the symbol as long as no name is
set.
- Flag Point
Flags are points for transferring data between loops of one
plant. The input is always set up to this value.
It is possible to hide this input in the Macro window.
- Invisible (do not show as in - or output in editor)
Hides the input or output of the control icon for all types other
than "Connection". A line at the bottom of the icon indicates
invisible ports.

EN2Z-0937GE51 R0518 934


CARE BACNET

The available output connections are opened in the tab Output.

Select the tab.

Select the properties of the output by double-click into the desired rows of the table:

RESULT: The configuration dialog box for selecting type and target for
the output opens.

- Connection

935 EN2Z-0937GE51 R0518


BACNET CARE

The output is defined as a connection to one or more inputs of


another element of this loop. This output will be always opened
in the Macro window.
- Constant
The output always sets up this value. It is possible to hide this
output in the Macro window.
- Loop/Macro Parameter
A parameter can be used by all functions and macros of this
loop/macro without being connected. It is possible to simplify
the displayed connections. The output sets this value.
It is possible to hide this output in the Macro window.
- Data point attribute
The input becomes a value of a data point attribute. Datapoints
are hardware/software points, e.g. sensors. The list of available
attributes depends on the type of the datapoint and if this
attribute is used for an input or output. It is possible to hide this
input in the Macro window. For detailed descriptions of the
Datapoint attributes, please refer to the Excel Web User Guide
EN2B-0289GE51 and the EAGLE Web Interface User Guide
EN2Z-0970GE51.
- System data
The output sets a system data. The only possible data are:

Application LED
reads and writes the status of the application LED
0 = Off
1 = On: permanently
2 = On: continuously blinking (on-off)
3 = On: 2 times continuously blinking (2 x (on-off), pause ..)
4 = On: 3 times continuously blinking (3 x (on-off), pause ..)
5 = On: 4 times continuously blinking (4 x (on-off), pause ..)
6 = On: 5 times continuously blinking (5 x (on-off), pause ..)

- Startup flag
indicates, if the system has been restarted

- M-Bus trigger
allows the controller reading M-Bus records at a particular
time (trigger) defined in the time program. This secures the
synchronization of M-Bus records reading process
independant of controller operation status.

It is possible to hide this output in the Macro window.


- Pointrole
Datapoints can be combined in so called pointroles. It is easier
to sort the datapoints by their main properties. Select a data
point from the pointrole.
It is possible to hide this output in the Macro window.
- Function parameter
The output sets the value of a parameter of one function/macro
(which includes parameters) included in this control loop. Only
functions with parameters are listed. If a function has no (alias)
name, an identifier (‘$’ followed by a unique number) is
assigned. This identifier is also displayed below the symbol as
long as no name is set.
It is possible to hide this output in the Macro window.
- Function register
The output sets the hidden stored value of one function/macro
included in this macro. If a function has no (alias) name, an
identifier (‘$’ followed by a unique number) is assigned. This
identifier is displayed below the symbol as long as no name is
set.
- Flag Point
Flags are points for transferring data between loops of one
plant. The output always sets up this value.
It is possible to hide this output in the Macro window.
- Invisible (do not show as in - or output in editor)

EN2Z-0937GE51 R0518 936


CARE BACNET

Hides the input or output of the control icon for all types other
than "Connection". A line at the bottom of the icon indicates
invisible ports.

For some elements it is possible to set up Parameters in the so named tab. Select
the tab and then double-click on the value field of the parameter table to edit them.

6. Now connect the input and output ports:

• Click once on the first port, you want to connect.


• Move the cursor to the second port and click on it.
• A line will connect the two ports (only in case they are corresponding). One
output port can be connected to many input ports. But one input port can
always be connected to only one output port.
• Customize the connecting line. While creating the connection you can click
the left mouse button into free space and the line becomes a corner there.
Clicking the right mouse button removes the last corner.
• After creating you can click the right mouse button at the line and the
context menu to split (adding one corner) and to delete segments displays.
After selecting the line via clicking on it, each single segment (between two
corners) can be moved by clicking on it.

937 EN2Z-0937GE51 R0518


BACNET CARE

7. Make sure, you have connected all inputs and outputs. Unconnected points are
red coloured; all points have to be coloured green.

8. Now translate the loop so it can be executed by the controller:

a. Select the controller by double-click on it.


b. Click on menu item Controller.

EN2Z-0937GE51 R0518 938


CARE BACNET

c. Click on submenu item Translate.

RESULT: The Honeywell CARE DDC-Translator window opens.

• You receive a log with the result of the translation.


• If the translation failed, use the log in the translation window
to identify the mistake(s). Correct them and start the
translation again.
• Transfer the software to the controller if the translation was
successful.

Set Execution Order of Control Loop Logic


CARE software calculates the execution order of all functions of the control loop in
order to optimize the execution time of the complete control loop. The execution
order of the control functions and macros are indicated as number in brackets
below each icon. For example, the following icon has the execution number 10
which means, that 9 other functions will be calculated before:

The following picture shows the execution order numbers of multiple functions of a
control loop section.

939 EN2Z-0937GE51 R0518


BACNET CARE

Besides the automatic calculation and optimization of the control loop execution,
CARE software allows manually setting the execution order of particular control
functions.

Example: The following control functions will be executed according to


their manual order which is indicated by the yellow highlighted
numbers. The order is relative, since between each two steps
other functions which are not selected manually, are executed
due to the optimization by the software. But, the order between
two following steps is absolute.

EN2Z-0937GE51 R0518 940


CARE BACNET

Procedure 1. Select the control functions you want to order manually.

RESULT: The selected control functions are highlighted in blue.

The original order is Cycle = 1, Comparison = 7, and Multi-


Switch In = 15.

2. Click on Plant>Control Editor>Manual Execution Order>Set Order, or press F9


key.

RESULT: The Manual execution order dialog box displays. The list shows
the optimized order for the selected functions.

941 EN2Z-0937GE51 R0518


BACNET CARE

3. By default, only the current selected functions (option "Selection" is checked),


will be manually ordered and labelled accordingly in the macro logic. To include
icons into the ordering, which have been previously but are not currently
selected, click the All used radio button.

4. To preview the order of the functions in the control logic, click on the Show
button.

RESULT: The functions in the list (selected or all used) are labeled in the
control logic.

5. To change the order, select the function in the list and click the Up or Down
button. Multiselection by using SHIFT or CTRL keys and left mouse button is
possible.

6. To remove a function from manual ordering, select the function in the list and
click the Remove button. Multiselection by using SHIFT or CTRL keys and left
mouse button is possible.

7. If changes have been done in the list, preview the new order of the functions in
the control logic by clicking the Show button again.

RESULT: The functions in the list (selected or all used) are labeled in the
control logic.

8. To confirm the previewed order, click the OK button.

RESULT: The control loop will be executed according to the defined


order.

Delete Control Loop


Prerequisites 1. The user is logged in.
2. A project is open.
3. The opened project has at least one controller, one plant and one control loop.

Procedure 1. Expand the tree view of the control loops of the plant, the control loop is
assigned to.

2. Click with the right mouse button on the icon of the control loop you want to
delete.

RESULT: The context menu displays.

EN2Z-0937GE51 R0518 942


CARE BACNET

3. Click on Delete with the left mouse button.

RESULT: The icon of the selected control loop will be removed.

NOTE: The control loop will be removed finally. You cannot use the submenu
undo.

Find Element in Control Loop


Prerequisites 1. The user is logged in.
2. A project is open.
3. The opened project has at least one controller, one plant and one control loop.

Procedure 1. Click main menu Plant, then submenu Control Editor, then submenu item Find,
or press CTRL + F keys.

RESULT: The Find dialog box displays.

2. From the Search drop-down listbox, select the item you want to find in the
control loop displayed.

RESULT: In the list below, all available elements of the selected search
item are displayed.

3. To apply a filter to the search result of the list, enter a string in the Filter drop
down listbox. By default all elements of the control loop are displayed as
indicated by an asterisk *.

4. To find a particular element in the control loop, click on in the list.

943 EN2Z-0937GE51 R0518


BACNET CARE

RESULT: The found element will be highlighted. In this case, an AND


Function call has been selected in the list and is highlighted in
the control loop.

Create Report
Purpose In large applications it can be necessary to find specific information of datapoints.
You can search for the usage of datapoints on project, controller, plant and control
loop level. Found datapoints can be detected in the control loop by double-clicking
from within the report displayed.

Procedure

1. Right-click the level (project, controller, plant or control loop) in which you want
to search for the used datapoints, and then click Show datapoints usage in
the context menu.

RESULT: The Find dialog box displays.

EN2Z-0937GE51 R0518 944


CARE BACNET

2. In Information Type, the applied search command is pre-selected. The


information type Datapoints usage searches for datapoints that match the
datapoint type pre-selection and the filter criteria (see below). If datapoint
attributes are part of functions or time programs the functions and time
programs will also be listed.

3. From the Datapoint Type drop-down listbox, you can select a datapoint type
for which you want to search specifically.

4. In Filter, you can enter a search string using wildcards to narrow down further
the result.

5. In Search Context, select the level (project, controller, plant and control loop)
on which the search should be executed. Note that software searches in the
selected level and automatically in the levels that are hierarchically below the
selected level. Under Search Context on the right, the levels are displayed.

RESULT: Under Search Result the found items are displayed and
automatically updated according to the selected information
type. The following properties are shown:

• Function
function type
• Symbol
instance name
• Datapoint
datapoint name
• Control loop
control loop the found item belongs to
• Plant
plant the found item belongs to

945 EN2Z-0937GE51 R0518


BACNET CARE

• Controller
controller the found item belongs to

6. To detect a found item in the control loop, double-click the item in the list.

RESULT: The item is selected in the control loop.

7. To apply various searches, change the search criteria under Find as desired.

RESULT: The list will be updated automatically.

Positioning Icons
Icons can be dragged and placed to any desired position in the wire sheet.
If desired, supporting grid lines can be shown. In addition, icons can be jogged in
definite steps within the grid and dropped at definite positions. When jogging an
icon, it snaps 5 times between grid lines. These definite snapping steps are
programmed in CARE and cannot be changed.

Procedures

Dragging Icon 1. With left mouse button, click on the icon.

2. With pressed left mouse button, move it to the desired position.

3. At the desired position, release the mouse button.

Jogging Icon 1. With left mouse button, click on the icon.

2. With left mouse pressed, simultaneously press the ALT key and move the icon.
While moving the icon, it will snap.

3. At the desired position, release the mouse button and the ALT key.

Connecting Icons
Connecting Icons by Drawing
Connecting lines The following icons can be connected to each other by using connecting lines:

• Function
• XMF
• Datapoint
• Flag

NOTES: Parameters can only be connected to RIA and WIA icons. Please refer to
the “Parameters” section.

One output can be connected to several inputs, but one input can be
connected to max. one output.

Inputs of Function icons cannot be connected to inputs of other Function


icons. This applies to outputs in the same way.

Inputs/outputs of datapoints must be connected to inputs/outputs of


Functions and XFM icons.

Example:

The following figure shows the connection between the output Y of the PID icon (1)
and the input M of the Subtract icon (2) by the drawn connection line (3).

EN2Z-0937GE51 R0518 946


CARE BACNET

If the data type (analog, digital) of the connected input and output do not
match, a Data Mismatch warning is displayed. But the connection is
established nevertheless. For universal inputs/outputs of the IDT icon, no
warning will be displayed.

Connections are indicated by colors as follows:

• Colors
– gray = input/output is unconnectable
– green = input/output is connected, or unconnected for optional
connections
– red = input/output is unconnected for mandatory connections
– yellow = “highlighted”

For general descriptions of icons, please refer to the Graphical Function


Representation note in the “Adding Functions and XMFs to Control Loop Pane”
section.

Procedure 1. With the cursor, point on the output/input, e.g. Y of the first icon, e.g. PID, until
the output/input symbol changes to yellow (tooltip display).

2. Click once. The cursor changes to a cross.

3. With holding left mouse button pressed, draw a connection line to the
input/output you want to connect, e.g. M of the Subtract icon.

947 EN2Z-0937GE51 R0518


BACNET CARE

4. When the cursor changes to a cross while pointing on the target input/output,
click once.

RESULT: The output/input is connected to the input/output as indicated by


the blue completed connection line and the green color of both,
the output and the input symbol.

5. Continue with connecting all inputs/outputs of the icon.

Drawing Methods You can draw connecting lines in different ways.

A) As described in the procedure above, you can draw a line in one step by clicking
once on the start symbol (input or output) and then clicking a second time on the
end symbol (output or input).

B) You can create intermediate points while drawing the connection line as follows:

1. First, click the starting point of the connection line (input/output symbol).
2. Draw the connection line.
3. Click at some intermediate point.
4. Repeat steps 2 and 3 as often as desired.
5. To finish, click the end point (output/input symbol) of the connection line.

RESULT: The connection line is devided into segments (a, b, c) caused by


the intermediate point clicks (1, 2), see also “Manipulating
Connecting lines” section.

Connecting lines are always right-angled. That is, connections can only run
vertically or horizontally. They cannot run diagonally. A connection line will be
“straight” if start and end point between two clicks allow this by accident.

If a connection line crosses an icon, the connection line passes around on the top
or at the bottom of the icon. In this case, segments are automatically created.

Cancel Drawing Pressing the ESC key, cancels the drawing process and removes the whole
connection line unless the connection is not completed yet (to delete a completed
connection, see “Manipulating Connecting lines” section).

Autorouting Connecting lines When connecting 2 icons or moving icons within a control loop, software optimizes
the display of connecting lines by drawing the shortest connection line, saving
space, and avoiding crossing the icon where the connection line has started.

EN2Z-0937GE51 R0518 948


CARE BACNET

Connecting lines can be autorouted explicitly if desired. To autoroute one particular


connection line, select the connection line, right-click and then click on Autoroute
in the context menu. To autoroute multiple connecting lines, select them and press
STRG+R keys simultaneously.

Procedure

Example: Autorouting a connection line that crosses an icon

a. Click the blue connection line. The selected connection line gets thick.

b. Right-click the connection line, and then click Autoroute in the context menu.

RESULT: The connection line is autorouted and passes the control loop icon.

Besides autorouting, you can manually re-position connecting lines as described in


the “Manipulating Connecting lines” section.

Manipulating Connecting lines Connecting lines sometimes pass through other control loop icons or cross other
connecting lines. This may make the control strategy confusing.

949 EN2Z-0937GE51 R0518


BACNET CARE

To optimize the run of the connecting lines, you can manipulate them manually by
moving the horizontal and vertical segments individually to the desired position.
In addition, you can insert a further segment by splitting a segment into two
segments.

Procedures

Move Segment

To move horizontal segments up or down or vertical segments to left or right:

Example: Vertical segment movement

a. Click the blue connection line. The selected connection line gets thick.
Then move the cursor along the segment until a double-arrow shows up.

b. Click again, and with left mouse button pressed down, move the segment to
the desired direction as indicated by the double-arrow cursor.

c. At the final position, release the mouse button.

RESULT: The connection line run has changed.

Split Segment

To split a segment into 3 segments by the insertion of one new segment:

EN2Z-0937GE51 R0518 950


CARE BACNET

Example: Horizontal segment splitting

a. Click the blue connection line. The selected connection line gets thick.

b. Right-click the section at the point where you want to split the segment. Right-
clicking a horizontal segment adds a vertical segment and vice versa.

c. In the context menu, click Split segment.

RESULT: The horizontal segment is split into three segments by the insertion
of a new vertical segment into the horizontal segment.

Delete Segment

To delete a segment:

Example: Vertical segment deletion

a. Click the connection line. The selected connection line gets thick.

b. Right-click the section you want to delete.

c. In the context menu, click Delete segment.

RESULT: The segment is deleted.

Delete Completed Connection – Remove Connection

Deletion/removal of a completed connection can be done in one of the following


ways:

951 EN2Z-0937GE51 R0518


BACNET CARE

A) 1. Click the connection line you want to delete. The selected connection line gets
thick.

2. Press DELETE key.

RESULT: The connection line is deleted.

B) 1. Right-click the input or output symbol on the control loop icon, e.g. Y of the
Switch icon.

2. In the context menu, click Remove connection.

RESULT: The connection line is removed.

Delete Incompleted Connection

1. Press ESC key while drawing the connection line.

RESULT: The whole connection line is removed unless the connection is not
completed yet.

Replace a Connection
An established connection will be replaced when connecting a free input/output
from another icon to the occupied input/output of the already connected icon.

1. Connect the free input or output to the desired occupied input or output.

EN2Z-0937GE51 R0518 952


CARE BACNET

RESULT: The established connection is removed and the new connection is


created.

Assign Constant

Purpose To connect (assign) a constant to an input of a Function or XFM icon. Constants do


not appear in the controller and cannot be changed online.

Procedure 1. Right-click the input symbol

2. Click Select data source in the context menu.

RESULT: The Select data source/target dialog box displays.

3. Under Type selection, select Constant.

953 EN2Z-0937GE51 R0518


BACNET CARE

4. Under Target definition, enter a value, and from the drop-down listbox, select
an engineering unit if desired.5
5. Click OK to save settings.

RESULT: The value of the constant is displayed at the input symbol and the
input symbol contains a ´C` indicating that the connection is of type
´Constant`.

Quick Assignment of Constants


Depending on the input (analog, binary) you can quickly assign an analog contant
´0`, ´1`, 100`, ´999` or binary constant ´0` or ´1` to an input as follows:

1. Right-click the input symbol

2. Click Contant in the context menu, and then click the value (0, 1, 100, or 999)

RESULT: The value of the constant is displayed at the input symbol and the
input symbol contains a ´C` indicating that the connection is of type
´Constant`.

Convert Connection to Register

Purpose To convert a connection (connecting line) into registers and display the register
numbers at the input and output. This can be helpful for identifying two control icons
with a badly traceable connecting line in a complex schematic.

Procedure 1. Right-click the connecting line.

2. Click Convert to Register in the context menu.

EN2Z-0937GE51 R0518 954


CARE BACNET

RESULT: The connecting line is removed and at the input and output, the
same assigned register number is displayed.

955 EN2Z-0937GE51 R0518


BACNET CARE

Macros
Purpose Macros are functions, built from other functions by the CARE-user (like a loop within
a loop). Macros can be used to carry out recommended special functions, e.g.
freeze protection (not included in CARE software basic version). The macros can
be built and used like a control loop, and can be assigned to a single plant, to a
whole project or to the all projects of the data base. Macros are stored in the global
macro library, to ensure the transfer between data bases.

Types There are three types of macros:


• Macros in plant
Macros that are software modules programmed from functions. Macros in plant
that are only available in a single plant. It is in the user’s hand to create, edit or
remove such macros. You can copy the macros of a plant into the global macro
library.
• System Macros
System Macros are mostly provided by Honeywell. They are available for all
projects of a database. Only authorized users have access to these macros.
• Global Macros
Global Macros are stored in the global macro library.
They are available for all projects of the database. Use the macro library to
create, edit, remove and organize these macros.

EN2Z-0937GE51 R0518 956


CARE BACNET

Create Macro
Prerequisites 1. The user is logged in and has a license that includes the “XL Web Macro
administrator feature”.
2. A project is open.
3. The opened project has at least one controller, one plant and one control loop.

Procedure 1. Expand the tree view of the control loops of the plant, the control loop is
assigned to.

2. Double-click on the icon of the control loop for which you want to create a
macro.

RESULT: The Macro window of the control loop opens in the right pane.

3. Select the functions, you want to move into a macro:


a. Select a single function by clicking on it.
b. Select some single functions by clicking on them and hold the Shift-key
pressed.
c. Select a couple of functions by holding the left mouse button pressed
and drawing a rectangle, covering the functions.
d. If nothing is selected, the macro stays empty.

RESULT: The selected functions are colored blue.

957 EN2Z-0937GE51 R0518


BACNET CARE

4. Click menu item Plant, then submenu item Control Editor and then submenu
Create new macro… (or press F7)

RESULT: The Macro overview dialog box of the macro opens.

EN2Z-0937GE51 R0518 958


CARE BACNET

Fill out the fields according to your requirements:


• Please enter a name:
Unique name of the macro.
• Description
Description of the macro, e.g. what’s the function of it or which special
input/output or parameters are used in this macro.
• Tooltip
Descriptive information that will be displayed in the yellow tooltip which
displays when moving the cursor over the macro icon.
• System macro
Select the checkbox if the macro should be included in the folder “Global
System Macros”. The macros of this folder are usable for all control loops of
this database. Only authorized users can create or access System macros.
• Version info (read only, set automatically)
Some information about the macro, similar to file information known from
MS-window.

5. Click the Next button.

RESULT: The Macro Inputs dialog box of the macro opens. The inputs of
the selected functions are predefined as inputs of the macro.

959 EN2Z-0937GE51 R0518


BACNET CARE

6. Set up the properties of the inputs of the macro by clicking twice into the
desired fields of the table:

Meaning of the columns:


• Input
Name of the input(s). Click twice into the row of the desired input to change
its name.
• Type
Type of the input(s). Click twice into the row of the desired input to get the
choice between the three input types (analog, binary, universal, or
datapoint).
• Unit
Unit of the value (e.g. liters, volt, minutes, …).

Meaning of the buttons:


• Up
Use this button to place the selected input one step up.
• Down
Use this button to place the selected input one step down.
• New
Use this button to create a new input of the macro.

EN2Z-0937GE51 R0518 960


CARE BACNET

• Delete
The selected input will be removed. Pay attention, only unused inputs can
be removed and no undo is possible.
• Mark unused
All entries are selected (to delete them).

7. Click the Next button.

RESULT: The Macro Outputs dialog box of the macro opens. The outputs
of the selected functions are predefined as outputs of the
macro.

8. Set up the properties of the outputs of the macro by clicking twice into the
desired rows of the table:

• Output
Name of the output(s). Click twice into the row of the desired output to
change its name.
• Type
Type of the output(s). Click twice into the row of the desired output to get the
choice between the three output types (analog, binary, universal, or
datapoint).

961 EN2Z-0937GE51 R0518


BACNET CARE

• Unit
Unit of the value (e.g. liters, volt, minutes, …).

Meaning of the buttons:


• Up
Use this button to place the selected output one step up.
• Down
Use this button to place the selected output one step down.
• New
Use this button to create a new output of the macro.
• Delete
The selected output will be removed. Pay attention, only unused outputs can
be removed and no undo is possible.
• Mark unused
All entries are selected (to delete them).

9. Click the Next button.

RESULT: The Macro Parameters dialog box of the macro opens.

10. Set up the properties of the parameters of the macro by clicking twice into the
desired rows of the table:

EN2Z-0937GE51 R0518 962


CARE BACNET

Meaning of the columns:


• Parameter
Name of the parameter(s). Click twice into the row of the desired parameter
to change its name.
• Default
Default value of the parameter(s).
• Min
Minimum value of the parameter(s).
• Max
Maximum value of the parameter(s).
• Unit
Unit of the value (e.g. liters, volt, minutes, …).

Denotation of the buttons:


• Up
Use this button to place the selected parameter one step up.
• Down
Use this button to place the selected parameter one step down.
• New
Use this button to create a new parameter of the macro.
• Delete
The selected parameter will be removed. Pay attention, only unused
parameters can be removed and no undo is possible.
• Mark unused
All entries become selected (to delete them).

11. Click the Next button.

RESULT: The Macro Registers dialog box opens.

963 EN2Z-0937GE51 R0518


BACNET CARE

12. Set up the properties of the registers of the macro by clicking twice into the
desired rows of the table:

Meaning of the columns:


• Register
Name of the register(s). Click twice into the row of the desired register to
change its name.

Denotation of the buttons:


• Up
Use this button to place the selected register one step up.
• Down
Use this button to place the selected register one step down.
• New
Use this button to create a new register of the macro.
• Delete
The selected register will be removed. Pay attention, only unused registers
can be removed and no undo is possible.
• Mark unused
All entries become selected (to delete them).

13. Click the Next button.

RESULT: The Save Macro dialog box of the macro opens.

EN2Z-0937GE51 R0518 964


CARE BACNET

NOTE: Please note the information, that connected datapoint properties will
be removed.

14. Click the Finish button.

RESULT: The macro is placed into the macro window.

15. To view the macro logic, select it, click right mouse button and click on open
macro in editor in the context menu.

RESULT: The macro logic is shown in the macro window. Note that in the
following picture, the removed datapoint property has already
been reworked by selection of another connection type, e.g.
"Constant".

965 EN2Z-0937GE51 R0518


BACNET CARE

EN2Z-0937GE51 R0518 966


CARE BACNET

Edit Macro Properties


Prerequisites 1. The user is logged in.
2. A project is open.
3. The opened project has at least one controller and one plant, one loop and one
macro.

Procedure 1. Expand the tree view of the control loops of the plant, the macro is assigned to.

2. Double-click on one of the icons of the control loop, the macro is assigned to.

RESULT: The macro window of the control loop opens in the right pane.
The icon of the macro is displayed in this macro window.

3. Right-click on the macro icon in the right pane.

RESULT: The context menu of the macro opens.

4. Click on Properties.

RESULT: The properties box of the macro opens.

Fill in the fields according to your requirements:


• Name:
Alias of this element. The alias can consist of up to 32 characters and/or
digits. This alias will be displayed on the tab Internal Parameter of the
parent macros (only if the alias-element includes parameters).
• No. of inputs (read only)
Number of input connections of the macro.
• Conditional Call
Select the checkbox if the condition “macro switch able” should be activated.
If selected, the macro will be extended by a further input called !Enable. The
macro will not be executed, if !Enable equals FALSE(0). It is not possible to
use !Enable as an input of functions inside the macro.

967 EN2Z-0937GE51 R0518


BACNET CARE

• Description (read only)


Description of the macro, e.g. what’s the function of it or which special
input/output or parameters are used in this macro.

An Input always must be filled with a value. The value could be e.g. a connection (to
the output of another element), a data point or system data. It is possible to hide an
input/output if it is not a connection.

5. The available input connections are displayed in the tab Input. Select the tab.

6. Double-click into the desired rows of the table to set up the properties of the
inputs of the macro.

RESULT: The configuration dialog box for selecting type and target for
the input opens.

EN2Z-0937GE51 R0518 968


CARE BACNET

• Connection
A connection is defined as the connection from an input to one output of
another element of the loop. This input will be always displayed in the macro
window.
• Constant
The input is always set up to this value. It is possible to hide this input in the
Macro window.
• Loop/Macro Parameter
The input reads from a parameter of a control loop. If you select the option
Loop/Macro Parameter you can select from the existing parameters.
• Macro input)
To select this option, you have to be in the macro view. If you select this
option you can select from the existing inputs.
• Macro output
To select this option, you have to be in the macro view. If you select this
option you can select from the existing outputs.
• Datapoint attribute
The input becomes a value of a data point attribute. Datapoints are
hardware/software points, e.g. sensors. The list of available attributes
depends on the type of the datapoint and if this attribute is used for an input
or output. For detailed descriptions of the Datapoint attributes, please refer
to the Excel Web User Guide EN2B-0289GE51 and the EAGLE Web
Interface User Guide EN2Z-0970GE51.
It is possible to hide this input in the Macro window.
• System data
The input becomes the value of the system function, such as clock. The
following system values are stored:

- Alarm status LED


reads the value of the red alarm LED
0 = Off (no alarm)
1 = license status error
2 = USB error (connected USB device draws more than
500 mA)
4 = panel bus error (e.g. I/O module missing)
8 = LON bus error (e.g. I/O module missing)
16 = sensor error on universal input which is used by the
application (e.g. sensor short, break)
combinations of values are possible (e.g. 4+8=12: panel bus
error and LON bus error at the same time)

Application LED
reads and writes the status of the application LED
0 = Off
1 = On: permanently
2 = On: continuously blinking (on-off)
3 = On: 2 times continuously blinking (2 x (on-off), pause ..)
4 = On: 3 times continuously blinking (3 x (on-off), pause ..)
5 = On: 4 times continuously blinking (4 x (on-off), pause ..)
6 = On: 5 times continuously blinking (5 x (on-off), pause ..)

- Cycle Time
reads the set current cyle time of the application part in sec

- Day and month


actual date (=100*month+day)

- Day of week
actual day of the week (monday(1)…saturday(7))

- Hours and minutes


actual time (=100*hours+minutes)
- Minutes since midnight
number of minutes after midnight

- Startup flag

969 EN2Z-0937GE51 R0518


BACNET CARE

indicates, if the system has been restarted

- Year
actual year

It is possible to hide this input in the Macro window.


• Pointrole
Datapoints can be combined in so called pointroles. So it is easier to
arrange the datapoints by their main properties. Select a data point from the
pointrole.
It is possible to hide this input in the Macro window.
• Function parameter
The input becomes the value of a parameter of one function/macro (which
includes parameters) included in this control loop. Only functions with
parameters are listed. If a function has no (alias) name, an identifier (‘$’
followed by a unique number) is assigned. This identifier is also displayed
below the symbol as long as no name is set.
It is possible to hide this input in the Macro window.
• Function register
The output sets the hidden stored value of one function/macro included in
this macro. If a function has no (alias) name, an identifier (‘$’ followed by a
unique number) is assigned. This identifier is displayed below the symbol as
long as no name is set.
It is possible to hide this output in the Macro window.
• Flag Point
Flags are points for transferring data between loops of one plant. The input
is always set up to this value.
It is possible to hide this input in the Macro window.
• Invisible (do not show as in - or output in editor)
Hides the input or output of the control icon for all types other than
"Connection". A line at the bottom of the icon indicates invisible ports.

7. Click the OK button to leave the window with saving the settings or click the
Cancel button to leave the window without saving the settings.

8. The available output connections are displayed in the tab Output. Select the
tab.

EN2Z-0937GE51 R0518 970


CARE BACNET

9. Set up the properties of the outputs of the macro by double-clicking into the
desired fields of the table:
RESULT: The configuration dialog box for selecting type and target for
the output opens.

• Connection
The output is defined as a connection to one input of another element of this
loop. This output will be always displayed in the Macro window.
• Constant
The output is always set up to this value. It is possible to hide this output in
the Macro window.

971 EN2Z-0937GE51 R0518


BACNET CARE

• Loop/Macro Parameter
The input reads from a parameter of a control loop. If you select the option
Loop/Macro Parameter you can select from the existing parameters.
• Macro input)
To select this option, you have to be in the macro view. If you select this
option you can select from the existing inputs. This option is not available if
you are in the tab output.
• Macro output
To select this option, you have to be in the macro view. If you select this
option you can select from the existing outputs.
• Datapoint attribute
The input becomes a value of a data point attribute. Datapoints are
hardware/software points, e.g. sensors. The list of available attributes
depends on the type of the datapoint and if this attribute is used for an input
or output. For detailed descriptions of the Datapoint attributes, please refer
to the Excel Web User Guide EN2B-0289GE51 and the EAGLE Web
Interface User Guide EN2Z-0970GE51.
It is possible to hide this input in the Macro window.
• System data
The output sets a system data. The only possible data are:

- Application LED
reads and writes the status of the application LED
0 = Off
1 = On: permanently
2 = On: continuously blinking (on-off)
3 = On: 2 times continuously blinking (2 x (on-off), pause ..)
4 = On: 3 times continuously blinking (3 x (on-off), pause ..)
5 = On: 4 times continuously blinking (4 x (on-off), pause ..)
6 = On: 5 times continuously blinking (5 x (on-off), pause ..)

- Startup flag
indicates, if the system has been restarted

- M-Bus trigger
allows the controller reading M-Bus records at a particular
time (trigger) defined in the time program. This secures the
synchronization of M-Bus records reading process
independant of controller operation status.

Pointrole
Datapoints can be combined in pointroles. This makes it easier to arrange
the datapoints by their main properties. Select a data point from the
pointrole.
It is possible to hide this output in the Macro window.
• Function parameter
The output is a value of a parameter of one function/macro included in this
control loop. Only functions with parameters are listed. If a function has no
(alias) name, an identifier (‘$’ followed by a unique number) is assigned.
This identifier is displayed below the symbol as long as no name is set.
It is possible to hide this output in the Macro window.

EN2Z-0937GE51 R0518 972


CARE BACNET

• Function register
The output sets the hidden stored value of one function/macro included in
this macro. If a function has no (alias) name, an identifier (‘$’ followed by a
unique number) is assigned. This identifier is displayed below the symbol as
long as no name is set.
It is possible to hide this output in the Macro window.
• Flag Point
Flags are points for transferring data between loops of one plant. The output
is always set to this value.
It is possible to hide this output in the Macro window.
• Invisible (do not show as in - or output in editor)
Hides the input or output of the control icon for all types other than
"Connection". A line at the bottom of the icon indicates invisible ports.

10. Click the button OK to leave the window with saving the settings or click the
button Cancel to leave the window without saving the settings.

11. The available parameters are displayed in the tab Parameter. First select the
tab and then double-click on the parameter to edit its properties.

RESULT: The value can be changed.

13. The available internal parameters are displayed in the tab Internal Parameter.
Select the tab.

973 EN2Z-0937GE51 R0518


BACNET CARE

In this view the parameters of named macros and functions of the macro are
displayed. It is possible to hide parameters which should not be changed.
Named functions/macros without parameters will not be displayed.

14. Double-click on the value field of the parameter table to set up the properties of
the internal parameters of the macro.

RESULT: The value can be changed.

15. Click the button OK to leave the window with saving the settings. Click the
button Cancel to leave the window without saving the settings. Click the button
Apply to save the settings, or click on any other tab to edit further properties of
the macro.

EN2Z-0937GE51 R0518 974


CARE BACNET

Edit the Properties of Inputs/Outputs/Parameters/Registers of a Macro


Prerequisites 1. The user is logged in.
2. A project is open.
3. The opened project has at least one controller and one plant, one loop and one
macro.

Procedure 1. Expand the tree view of the control loops of the plant, the macro is assigned to.

2. Double-click on one of the icons of the control loops, the macro is assigned to.

RESULT: The Macro window of the control loop opens in the right pane.
The icon of the macro is displayed in the Macro window.

3. Right-click on the macros icon in the right pane.

RESULT: The context menu of the macro opens.

4. Click on Open macro in editor.

RESULT: The Macro window switches from control loop-view to macro-


view.

NOTE: The always displayed Properties tab does not change to macro-view.
Here the properties of the control loop are displayed.

5. Click menu item Plant > Control Editor > Macro Properties….

RESULT: Tab Macro overview of the Macro properties dialog box of the
macro opens.

975 EN2Z-0937GE51 R0518


BACNET CARE

Fill in the fields according to your requirements:

• Please enter a name:


Unique name of the macro.
• Description
Description of the macro, e.g. what’s the function of it or which special
input/output or parameters are used in this macro.
• Tooltip
Descriptive information that will be displayed in the yellow tooltip which
displays when moving the cursor over the macro icon.
• System macro
Select the checkbox if the macro should be included in the folder “Global
System Macros”. The macros of this folder are usable for all control loops of
this database. Only authorized users can create or access System macros.
• Version info (read only, set automatically)
Some information about the macro, similar to file information known from
MS-window.

6. The available inputs are displayed in the tab Macro Inputs. Select the tab.

EN2Z-0937GE51 R0518 976


CARE BACNET

7. Click twice into the rows of the table to set up the properties of the input
datapoints of the macro:

Denotation of the columns:


• Input
Name of the input(s). Click twice into the row of the desired input to change
its name.
• Type
Type of the input(s). Click twice into the row of the desired input to get the
choice between the three input types (analog, binary, universal, or
datapoint).
• Unit
Unit of the value (e.g. liters, volt, minutes, …).

Meaning of the buttons:


• Up
Use this button to place the selected input one step up.
• Down
Use this button to place the selected input one step down.
• New
Use this button to create a new input of the macro.

977 EN2Z-0937GE51 R0518


BACNET CARE

• Delete
The selected input will be removed. Pay attention, only unused inputs can
be removed and no undo is possible.
• Mark unused
All entries are selected (to delete them).

8. The available outputs are displayed in the tab Macro Outputs. Select the tab.

9. Click twice into the rows of the table to set up the properties of the output
datapoints of the macro:

Denotation of the columns:


• Output
Name of the output(s). Click twice into the row of the desired output to
change its name.
• Type
Type of the output(s). Click twice into the row of the desired output to get the
choice between the three output types (analog, binary or universal).
• Unit
Unit of the value (e.g. liters, volt, minutes, …).

Meaning of the buttons:


• Up
Use this button to place the selected output one step up.

EN2Z-0937GE51 R0518 978


CARE BACNET

• Down
Use this button to place the selected output one step down.
• New
Use this button to create a new output of the macro.
• Delete
The selected output will be removed. Pay attention, only unused outputs can
be removed and no undo is possible.
• Mark unused
All entries are selected (to delete them).

10. The available parameters are displayed in the tab Macro Parameters. Select
the tab.

11. Click twice into the rows of the table to set up the properties of the parameters
of the macro:

Meaning of the columns:


• Parameter
Name of the parameter(s). Click twice into the row of the desired parameter
to change its name.
• Default
Default value of the parameter(s).
• Min
Minimum value of the parameter(s).
• Max
Maximum value of the parameter(s).
• Unit
Unit of the value (e.g. liters, volt, minutes, …).

Denotation of the buttons:

979 EN2Z-0937GE51 R0518


BACNET CARE

• Up
Use this button to place the selected parameter one step up.
• Down
Use this button to place the selected parameter one step down.
• New
Use this button to create a new parameter of the macro.
• Delete
The selected parameter will be removed. Pay attention, only unused
parameters can be removed and no undo is possible.
• Mark unused
All entries become selected (to delete them).

12. The available registers are displayed in the tab Macro Registers. Select the
tab.

13. Click twice into the rows of the table to set up the properties of the registers of
the macro:

Denotation of the columns:


Meaning of the columns:
• Register
Name of the register(s). Click twice into the row of the desired register to
change its name.

Denotation of the buttons:


• Up
Use this button to place the selected register one step up.
• Down
Use this button to place the selected register one step down.
• New
Use this button to create a new register of the macro.

EN2Z-0937GE51 R0518 980


CARE BACNET

• Delete
The selected register will be removed. Pay attention, only unused registers
can be removed and no undo is possible.
• Mark unused
All entries become selected (to delete them).

14. Click the button OK to leave the window with saving the settings. Click the
button Cancel to leave the window without saving the settings. Click the button
Apply to save the settings, or click on any other tab to edit further properties of
the macro.

RESULT: The Macro window of the macro opens if you click on button
OK or Cancel.

15. To leave the macro-view and return to the control loop-view, click the right
mouse button.

RESULT: The context menu of the macro opens.

16. Click on Open parent macro.

RESULT: The Macro window changes from macro- to control loop-view or


the macro above. (An indefinite number of macro levels is
possible).

Double-click on any other element to change the view to it.

981 EN2Z-0937GE51 R0518


BACNET CARE

Create and Edit Macro Logic


Prerequisites 1. The user is logged in.
2. A project is open.
3. The opened project has at least one controller, one plant, one loop and one
macro.

Procedure 1. Expand the tree view of the control loop of the plant, the macro is assigned to.

2. Double-click on one of the icons of the control loops, the macro is assigned to.

RESULT: The Macro window of the control loop opens in the right pane.
The icon of the macro is displayed in this Macro window.

3. Right-click on the macros icon in the right pane.

RESULT: The context menu of the macro opens.

4. Click on Open macro in editor.

RESULT: The Macro window changes from control loop-view to macro-


view.

NOTE: The always displayed Properties tab does not change to macro-view.
Here the properties of the control loop are displayed.

5. Define the content of the macro as desired (similar to the creation of a loop
logic). Assign functions or hardware/software points to the macro by using drag
& drop:

EN2Z-0937GE51 R0518 982


CARE BACNET

6. Click once on the icon and hold the left mouse-button pressed.

7. Move the cursor into the Macro window. The cursor changes to a “No Parking”-
sign if it is moved in areas, you cannot drop the component into.

8. Release the left mouse button.

RESULT: The function or component is displayed in the Macro window.

Denotation of the colours:


• red
The setup of the icon is incomplete. All inputs must have a value, e.g. by
connecting it to an output or by defining it as a constant.
• blue
The icon is selected.
• none colored (light grey)
The setup of the icon is accomplished, no errors expected.

For setting up a connection between input and output, see step 8.

9. Apply the described procedure written above with all components and functions
you want to combine in this macro.

• All icons in the Macro window can be moved via drag & drop.
• You can use the windows known short keys, e.g. “Ctrl + A” for selecting all
elements in an active window.
• To enter the menu Plant, make sure, the Macro window is still selected:
Click once with the left mouse button in the Macro window.

983 EN2Z-0937GE51 R0518


BACNET CARE

RESULT: The following button and drop-down list in the taskbar (from left
to the right) are activated:

- Zoom per %:
Display and change the numerous zoom factor of the whole
view, centered by the displayed window.
- Zoom +:
Use this button(s) to zoom in a selected area.
- Move all:
The cursor changes to a hand and you can move the view of
the Macro window.
- Select and edit:
The cursor changes to standard and you can select elements in
the Macro window, draw connections between outputs and
inputs and insert text into the Macro window.
- Last view
The view reverts prior to the last change.
- Next view
The last undo of the view is reverted.

The elements in the Macro window are displayed in the


following manner:
Hardware/software point, in most cases a real input or output of
the controller.

Function, indicated by the separated header and input and


output ports. The name of the function is displayed in this
header.

Analog port, it is possible to connect analog and binary ports.


The input port translates the input signal into his own format
(analog or binary) information may be lost. If you set up a
connection between analog and binary ports, an error message
informs you about a data mismatch.

The binary port has two values: TRUE (1) or FALSE (0).

Any port, this port is not predefined as an analog or binary


input. The type of data depends on further processing.

The black point in the header indicates the side of the output
ports.

A line under the ports indicates hidden (invisible) ports. You can
make them visible using the Properties window of these ports.

EN2Z-0937GE51 R0518 984


CARE BACNET

Input ports are red coloured, if they are not connected. The
color green indicates the accurate connection of the port.

The configuration of inputs is indicated as follows:


If an input port is configured as datapoint attribute, the default
datapoint property "Present Value" is displayed in the tooltip of
the port. If any other property is selected as datapoint attribute,
e.g. Polarity, this is shown in the tooltip and additionally in
brackets at the port.

10. Setup the properties of the functions and hardware/software points as follows:

• Right-click on the element you want to setup.

RESULT: The context menu of the element opens.

• Click on Properties.

RESULT: The Function properties:<name> dialog box of the element


opens.

985 EN2Z-0937GE51 R0518


BACNET CARE

In tab General are the following input fields:


• Name
Alias of this element. The alias can consist up to 32 characters and/or
digits. This alias will be displayed on the tab Internal Parameter of the
parent macros (only if the alias-element includes parameters).
• No. of inputs
Number of input (in some cases output) connections of the element.

You have to apply changes of the input/output count before you can see the
changed number in the input/output tab.

An Input must be always filled with a value. The value could be e.g. a connection (to
the output of another element), a data point, or system data. It is possible to hide an
input/output if it is not a connection.

The available input connections are displayed in the tab Input. Select the tab,

EN2Z-0937GE51 R0518 986


CARE BACNET

Select the properties of the input by double-clicking on the rows of the table.

RESULT: The configuration dialog box for selecting type and target for
the input opens.

- Connection
The input is defined as a connection to one output of another
element of this loop. This input will be displayed in the Macro
window.
- Constant
The input is set to this value. It is possible to hide this input in
the Macro window.

987 EN2Z-0937GE51 R0518


BACNET CARE

- Loop/Macro Parameter
A parameter can be used by all functions and macros of the
loop/macro without being connected. So it is possible to simplify
the displayed connections. The input turns to this value.
It is possible to hide this input in the Macro window.
- Macro input
The input is the value of a macro’s input.
It is possible to hide this input in the Macro window.
- Macro output
The input is the value of a macro’s output. In this case, the
output of the macro is used as a data point.
- System data
The input becomes the value of the system function, such as
´clock`. The following system values are stored:

- Alarm status LED


reads the value of the red alarm LED
0 = Off (no alarm)
1 = license status error
2 = USB error (connected USB device draws more than
500 mA)
4 = panel bus error (e.g. I/O module missing)
8 = LON bus error (e.g. I/O module missing)
16 = sensor error on universal input which is used by the
application (e.g. sensor short, break)
combinations of values are possible (e.g. 4+8=12: panel bus
error and LON bus error at the same time)

Application LED
reads and writes the status of the application LED
0 = Off
1 = On: permanently
2 = On: continuously blinking (on-off)
3 = On: 2 times continuously blinking (2 x (on-off), pause ..)
4 = On: 3 times continuously blinking (3 x (on-off), pause ..)
5 = On: 4 times continuously blinking (4 x (on-off), pause ..)
6 = On: 5 times continuously blinking (5 x (on-off), pause ..)

- Cycle Time
reads the set current cyle time of the application part in sec

- Day and month


actual date (=100*month+day)

- Day of week
actual day of the week (monday(1)…saturday(7))

- Hours and minutes


actual time (=100*hours+minutes)
- Minutes since midnight
number of minutes after midnight

- Startup flag
indicates, if the system has been restarted

- Year
actual year
- Function parameter
The input is the value of a parameter of one function/macro
included in this control loop. Only functions with parameters are
listed. If a function has no (alias) name, an identifier (‘$’
followed by a unique number) is assigned. This identifier is also
displayed below the symbol as long as no name is set.
It is possible to hide this input in the Macro window.
- Function register
The output sets the hidden stored value of one function/macro
included in this macro. If a function has no (alias) name, an
identifier (‘$’ followed by a unique number) is assigned. This
identifier is displayed below the symbol as long as no name is

EN2Z-0937GE51 R0518 988


CARE BACNET

set.
It is possible to hide this output in the Macro window. It is
possible to hide this input in the Macro window.
- Invisible (do not show as in - or output in editor)
Hides the input or output of the control icon for all types other
than "Connection". A line at the bottom of the icon indicates
invisible ports.

Note: Datapoint attributes, Point roles and Flags are not available within macros.
The available output connections are displayed in the tab Output. Select the tab.

Double-click into the rows of the table.

RESULT: The configuration dialog box for selecting type and target for
the output opens.

989 EN2Z-0937GE51 R0518


BACNET CARE

- Connection
The output is defined as a connection to one or more inputs of
another element of this loop. This output will be displayed in the
Macro window.
- Constant
The output sets up this value. It is possible to hide this output in
the Macro window.
- Loop/Macro Parameter
A parameter can be used by all functions and macros of this
loop/macro without being connected. So it is possible to simplify
the displayed connections. The output sets this value.
It is possible to hide this output in the Macro window.
- Macro output
The input is the value of a macro’s output. In this case, the
output of the macro is used as a data point.
- System data
The output sets a Startup flag or the application LED:

Application LED
reads and writes the status of the application LED
0 = Off
1 = On: permanently
2 = On: continuously blinking (on-off)
3 = On: 2 times continuously blinking (2 x (on-off), pause ..)
4 = On: 3 times continuously blinking (3 x (on-off), pause ..)
5 = On: 4 times continuously blinking (4 x (on-off), pause ..)
6 = On: 5 times continuously blinking (5 x (on-off), pause ..)

- Startup flag
indicates, if the system has been restarted

- M-Bus trigger
allows the controller reading M-Bus records at a particular
time (trigger) defined in the time program. This secures the
synchronization of M-Bus records reading process
independant of controller operation status.

It is possible to hide this output in the Macro window.

- Function parameter
The output sets the value of a parameter of one function/macro
included in this control loop. Only functions with parameters are
listed. If a function has no (alias) name, an identifier (‘$’
followed by a unique number) is assigned. This identifier is also

EN2Z-0937GE51 R0518 990


CARE BACNET

displayed below the symbol as long as no name is set.


It is possible to hide this output in the Macro window.
- Function register
The output sets the hidden stored values (default the previous
values of input, output and parameters) of an input, output or
parameter of one function/macro included in this macro.
It is possible to hide this output in the Macro window. Only
functions with parameters are listed. If a function has no (alias)
name, an identifier (‘$’ followed by a unique number) is
assigned. This identifier is also displayed below the symbol as
long as no name is set.
- Invisible (do not show as in - or output in editor)
Hides the input or output of the control icon for all types other
than "Connection". A line at the bottom of the icon indicates
invisible ports.

NOTE: Datapoint attributes, Point roles and Flags are not available within
macros.
For some elements it is possible to set up Parameters in the so named tab. Select
the tab.

Parameter update
If you change the parameter of an icon in a macro, the dialog “Apply parameter
changes” opens.

991 EN2Z-0937GE51 R0518


BACNET CARE

You can select in the check boxes for which parameter the change should apply.
The option “Only current macro” applies your changes only to the current macro.
The option “All macros” applies the changes to all calls of this macro. With the
button “OK” you confirm the made changes. With the button “Don’t change” your
changes are deleted.

11. Now connect the input and output ports:

• Click once on the first port, you want to connect.


• Move the cursor to the second port and click on it.
• A line will connect the two ports (only in case they are corresponding). One
output port can be connected to many input ports. But one input port can be
connected to only one output port.
• Customize the connecting line. While creating you can click the left mouse
button into free space and the line becomes a corner there. Clicking the
right mouse button removes the last corner and cancels line editing when
the start point will be removed. Hitting the Space bar toggles the routing
direction.
• After creating you can click the right mouse button at the line and the
context menu to split (adding one corner) and to delete segments displays.
After selecting the line via clicking on it, each single segment (between two
corners), except the first and last one, can be moved by clicking on them.

12. Make sure, you have connected all inputs and outputs. Unconnected points are
red coloured; all points have to be coloured green.

NOTE: Please note the definition of the macros inputs and outputs. As they
are not displayed they easily could be left undefined.

EN2Z-0937GE51 R0518 992


CARE BACNET

13. To leave the macro-view and return to the control loop-view, click the right
mouse button.

RESULT: The context menu of the macro displays.

14. Click on Open parent macro.

RESULT: The Macro window changes from macro- to control loop-view.

Double-click on any other element to change the view of it.

Use Pre-configured Macros


CARE provides pre-configured macros in an HVAC Application Library. These
macros can be used for general purpose (e.g. startup and exercise) or for specific
air conditioning applications.

By default, the HVAC application library macros are protected against editing. If you
want to edit a macro it can be converted to an editable variant. For protected
macros, Honeywell offers technical support but for converted macros, Honeywell
does not offer support.

993 EN2Z-0937GE51 R0518


BACNET CARE

Prerequisites 1. The user is logged in.


2. A project is open.
3. The open project has at least one controller and one plant and one control
loop.

Procedure 1. Expand the tree view of the plant.

2. Double-click on the icon of the control loop you want to edit.

RESULT: The Macro window of the control loop opens in the right pane.

EN2Z-0937GE51 R0518 994


CARE BACNET

3. In the Functions/Macros view (down left from the macro window) expand the
Global System Macros folder and navigate to the folder, Air Conditioning and/or
General folder, that contains the pre-configured macro(s) you want to use.

4. Select the macro and drag&drop it to the Macro window.

NOTE: You can also add pre-configured macros from the Global Macro
Library (see "Open Global Macro Library") section.

5. Connect datapoints to the macro inputs and/or outputs.

6. If desired, edit macro properties in the same way as described in the "Edit
Macro Properties" section.

7. If you want to edit the inherent macro logic functions, the macro must be
converted to its editable variant. Please note that for such edited macros, no
support is provided by Honeywell.

8. To convert a protected macro into its editable variant, please refer to the
"Convert Protected Macro to Editable Macro" section.

Convert Protected Macro into Editable Macro


By default, the HVAC application library macros are protected against editing. If you
want to edit a macro, it can be converted to an editable variant. For protected
macros, Honeywell offers technical support but for converted macros, Honeywell
does not offer support.

995 EN2Z-0937GE51 R0518


BACNET CARE

Procedure 1. In the Macro Window, right-click the Macro and then click Convert to own
macro… in the context menu.

RESULT: The Convert to own macro dialog box displays.

2. In Macro name, change the name if desired.

3. Keep the Apply for current plant option if you want to apply the conversion to
all macros of this type in the current plant.
or, select Apply for current project if you want to apply the conversion to all
macros of this type in the current project.

NOTE: Converted macros cannot be reverted and Honeywell does not


provide support for converted and changed macros.

4. Click OK button.

EN2Z-0937GE51 R0518 996


CARE BACNET

5. Click OK button.

RESULT: The macro can now be edited.

6. To do so, right-click the macro, and then click Open macro in editor in the
context menu.

RESULT: The macro logic is displayed. This can show functions and/or
further protected macros.

7. Continue by editing the macro logic as desired, e.g. by changing macro


properties, converting macros, and/or editing functions.

Delete Macro
Procedure Macros will be automatically removed, if they are no longer used in any control
loop.

Or, you can delete a macro manually as follows:

1. In the control loop pane, select the macro, and then press the DELETE key on
the keyboard.

997 EN2Z-0937GE51 R0518


BACNET CARE

Flags
Purpose Flags are independent memory addresses defined for one plant. Each element
(hardware/software point, function or macro) of any control loop of this plant is able
to setup the value of such a flag with an output or setup the value of an own input
with the value of such a flag. So it is possible to transmit data between the control
loops of one plant without using a hardware/software point.

NOTE: It is not possible to use flags if the element is included in a macro.

Create and Edit Flags


Purpose Use Flags for easy data transfer between elements (hardware/software point,
function or macro) of a single control loop.

Prerequisites 1. The user is logged in.


2. A project is open.
3. The opened project has at least one controller, one plant and one control loop.

Procedure 1. Expand the tree view of the control loops of the plant, the control loop is
assigned to.

2. Double-click on the icon of the control loop you want to setup Flags for.

RESULT: The Macro window of the control loop opens in the right pane.

EN2Z-0937GE51 R0518 998


CARE BACNET

3. Click once into the free space of the Macro window.

RESULT: The Macro window of the control loop is selected.

4. Click menu item Plant > Control Editor, > Flags… .

RESULT: The Edit Flag’s dialog box opens.

5. Sort flags by clicking on the radio buttons, by Flag or by control loop, on the
right.

RESULT: If sorted by flag, all Flags and the control loops, which include
these flags, are displayed.

RESULT: If sorted by control loop, all control loops with their connected
flags are displayed.

999 EN2Z-0937GE51 R0518


BACNET CARE

Denotation of the buttons:


• Add
Click on Add to create a new flag.
It is not possible to create Flags if the view of the Flags is sorted “by control
loop”.
The name of the flag must consist of at least one letter. For the name of the
flag do not use special characters like “, /, ?, * and blank.
• Delete
Click on Delete to remove the selected flag.
Only unused (not assigned to a control loop) flags can be removed.
• OK
Click on OK to leave the window.

EN2Z-0937GE51 R0518 1000


CARE BACNET

Click twice on the name of a flag to rename it.

RESULT: The name becomes highlighted and changeable.

1001 EN2Z-0937GE51 R0518


BACNET CARE

Global Macro Library


Purpose The Global Macro Library provides macros that can be used globally in any
projects. Global macros can be used independently from any project or control loop.

Macros can be transferred between projects via drag&drop from/to the macro
window in the project and the macro library.

In addition, you can update a global macro used in projects with changes done to
this macro in the macro library.

Macro Conflict
Whenever the contents or properties of a macro are changed, the version and the
date of the macro are modified. This may lead to a conflict. The conflict arises
when you drop a macro in an editor where the same macro with a different version
or date is already in use. The dialog macro conflict opens.

More than one macro may be shown in the dialog, because of the macro
dependencies.
You have three options to resolve the conflict as described in the dialog. Double-
click on one of the listed conflicts to mark it. Select your solution in the drop-down
list “How to solve”. As long as not all macro conflicts are resolved, the button “OK”
stays inactive.
Double-click on one of the listed conflicts and then on the button “Compare” to see
the differences between the conflicting macros.

EN2Z-0937GE51 R0518 1002


CARE BACNET

Open Global Macro Library

Procedure 1. Click menu item Database > Macro Library… , or click on button .

RESULT: The Global Macro Library window opens.

The Global Macro Library window provides the following:

In the upper area, you will see the HVAC Application Library providing pre-
configured macros for general purpose and specific air conditioning macros.

1003 EN2Z-0937GE51 R0518


BACNET CARE

By default, an empty folder named ´MacroLibrary` is available.

In the Global Macro Library window, you can do the following:

• Arrange libraries, folders and macros in a hierarchical tree structure by applying


the following:
– Create, delete and rename global macro libraries respectively folders
– Create, copy and delete macros

In addition, you can do the following:

• Edit and update macros


• Create, import and export libraries

In the lower area, the HVAC application library is also provided as global system
macros. In addition, control functions are available.

In this area, you cannot edit items or execute commands as in the upper area. But,
you can add system macros and functions to the control loop pane via drag&drop.

EN2Z-0937GE51 R0518 1004


CARE BACNET

Create Global Macro Library


NOTE: Libraries will always be created on the highest tree level. Folders can be
created on any level lower than the library level.

By default, there is an empty library provided named ´MacroLibrary`.

Procedure 1. In the Library menu, click Create Library.

RESULT: The new library is created on the level of the default library and
is named MacroLibrary_1. Further libraries will be named
MacroLibrary_2, MacroLibrary_3, etc. The name of the library
can be changed by renaming (see “Rename Folder” section).

2. Add folder(s) to the library and macros as desired and as described in the
following sections.

Rename Global Macro Library


See “Rename Folder” section.

Delete Global Macro Library


See “Delete Folder” section.

Create Folder
Procedure 1. Click on the library folder or any other folder where the new folder should be
created. In the Library menu, click Create Folder.

1005 EN2Z-0937GE51 R0518


BACNET CARE

2. Or, right-click on the library folder or any other folder where the new folder
should be created. In the context menu, click Create Folder.

3. In the Create new folder dialog box, enter the name, and then click OK.

RESULT: The new folder is created below the selected folder.

Rename Folder
Procedure 1. Click on the folder that you want to rename. In the Library menu, click Rename.

2. Or, right-click on the folder that you want to rename. In the context menu, click
Rename Folder.

3. In the Rename folder dialog box, change the name, and then click OK.

Delete Folder
Procedure 1. Click on the folder that you want to delete. In the Library menu, click Delete.

2. Or, right-click on the folder that you want to delete. In the context menu, click
Delete folder. The selected folder and all macros in this folder

NOTE: Other then handling of macros in the control loops view, unused and
used macros will be deleted. The used ones are available in the
control loop, but no longer stored in the macro library.

EN2Z-0937GE51 R0518 1006


CARE BACNET

Create Global Macro


Prerequisites 1. The user is logged in. A library and/or additional folders are created for good
navigation.

Procedure 1. Select the functions, and then click menu item Database > Macro Library… , or

click on button .

RESULT: The Global Macro Library window opens.

2. In the Macro menu, select Create, or right-click on the Macro Library folder in
the tree (or each other folder).

3. In the context menu, click Create.

RESULT: The Macro overview dialog box of the macro opens.

1007 EN2Z-0937GE51 R0518


BACNET CARE

Fill in the fields according to your requirements:


• Please enter a name:
Unique name of the macro.
• Description
Description of the macro, e.g. what’s the function of it or which special
input/output or parameters are used in this macro.
• Tooltip
• Descriptive information that will be displayed in the yellow tooltip which
displays when moving the cursor over the macro icon.
• System macro
Select the checkbox if the macro should be included in the folder “Global
System Macros”. The macros of this folder can be used for all control loops
of the database. Only authorized users can access System macros.
• Version info (read only, managed automatically)
Information about the macro

4. Click Next.

RESULT: The Macro Inputs dialog box of the macro opens.

EN2Z-0937GE51 R0518 1008


CARE BACNET

5. Click twice into the desired fields of the table to set up the properties of the
input datapoints of the macro:

Denotation of the columns:


• Input
Name of the input(s). Double-click into the row of the desired input to
change its name.
• Type
Type of the input(s). Double-click into the row of the input to choose
between the three input types (analog, binary, universal, or datapoint).
• Unit
Property dialog box of the connections unit of the value (e.g. liters, volt,
minutes, …).

1009 EN2Z-0937GE51 R0518


BACNET CARE

• Default
In the default column you can select the type of connection, which will be
used when you drop the macro from the Global Library into your editor. If
the type pointrole is used, and exactly one datapoint is found with the same
pointrole, it is automatically replaced. Otherwise the pointrole type stays the
same and should be changed manually.
For default types only one of the following options can be selected:
– Connection
– Constant
– System Data
– Pointrole
– Flagpoint
All options other than "Connection" may be invisible too.

Denotation of the buttons:


• Up
Use this button to place the selected input one step up.
• Down
Use this button to place the selected input one step down.
• New
Use this button to create a new input of the macro.
• Delete
The selected input will be removed. Please note, only unused inputs can be
removed and no undo is possible.
• Mark unused
All entries not used by the control strategy of the macro are selected (to
delete them).

6. Click Next.

RESULT: The Macro Outputs dialog box of the macro opens.

EN2Z-0937GE51 R0518 1010


CARE BACNET

7. Click twice into the rows of the table to set up the properties of the output
datapoints of the macro:

Denotation of the columns:


• Input
Name of the output(s). Double-click into the row of the desired output to
change this name.
• Type
Type of the output(s). Double-click into the row of the desired output to
choose between the three output types (analog, binary, universal, or
datapoint).
• Unit
Unit of the value (e.g. liters, volt, minutes, …).
• Default
In the default column you can select the type of connection, which will be
used when you drop the macro from the Global Library into your editor. If
the type pointrole is used, and exactly one datapoint is found with the same
pointrole, it is automatically replaced. Otherwise the pointrole type stays the
same and should be changed manually.
For default types only one of the following options can be selected:
– Connection
– Constant

1011 EN2Z-0937GE51 R0518


BACNET CARE

– System Data
– Pointrole
– Flagpoint

All options other than connection may be invisible too.

Denotation of the buttons:


• Up
Use this button to place the selected output one step up.
• Down
Use this button to place the selected output one step down.
• New
Use this button to create a new output of the macro.
• Delete
The selected output will be removed. Please note, only unused outputs can
be removed and an undo is not possible.
• Mark unused
All entries not used by the control strategy of the macro are selected (to
delete them).

8. Click the button Next.

RESULT: The Macro Parameters dialog box of the macro opens.

EN2Z-0937GE51 R0518 1012


CARE BACNET

9. Click twice into the desired fields of the table to set up the properties of the
parameters of the macro:

Meaning of the columns:


• Parameter
Name of the parameter(s). Double-click into the row of the desired
parameter to change its name.
• Default
Default value of the parameter(s).
• Min
Minimum value of the parameter(s).
• Max
Maximum value of the parameter(s).
• Unit
Unit of the value (e.g. liters, volt, minutes, …).

Denotation of the buttons:


• Up
Use this button to place the selected parameter one step up.
• Down
Use this button to place the selected parameter one step down.

1013 EN2Z-0937GE51 R0518


BACNET CARE

• • New
Use this button to create a new parameter of the macro.
• Delete
The selected parameter will be removed. Please note, only unused
parameters can be removed and an undo is not possible.
• Mark unused
All entries not used by the control strategy of the macro are selected (to
delete them).

10. Click the button Next.

RESULT: The Macro Registers dialog box of the macro opens.

11. Click twice into the desired fields of the table to set up the properties of the
registers of the macro:

Meaning of the columns:


• Register
Name of the register(s). Click twice into the row of the desired register to
change its name.

Denotation of the buttons:

EN2Z-0937GE51 R0518 1014


CARE BACNET

• Up
Use this button to place the selected register one step up.
• Down
Use this button to place the selected register one step down.
• New
Use this button to create a new register of the macro.
• Delete
The selected register will be removed. Please note, only unused register
can be removed and an undo is not possible.
• Mark unused
All entries not used by the control strategy of the macro are selected (to
delete them).

12. Click the button Next.

RESULT: The Save Macro dialog box of the macro opens.

13. Click Finish.

RESULT: The macro is added to the Global macro Library window.

1015 EN2Z-0937GE51 R0518


BACNET CARE

14. Continue with creating the macro logic by clicking More>>, and then adding
and linking the functions.

EN2Z-0937GE51 R0518 1016


CARE BACNET

15. From now on, the macro is stored in the global macro library and can be
transferred into any project, database and is available for any control loop.

Create Global Macro Logic


Several macros have the attribute System Macro. To see if your macro is defined
as a System Macro, open the Macro properties dialog and check if the option
“System Macro” is active. System Macros cannot be edited, deleted or moved within
the Global Macro Library. A special license is required to create System Macros.

1017 EN2Z-0937GE51 R0518


BACNET CARE

Prerequisites 1. The user is logged in.

Procedure 1. Click menu item Database > Macro Library…, or click on button .

RESULT: The Global Macro Library window opens.

2. Expand the tree view of the folder, the macro is assigned to.

3. Click More>>.

RESULT: The Macro window of the folder opens in the right pane.

4. Double-click on the macro.

RESULT: The logic of the macro opens in the Macro window.

NOTE: The editor pane will be displayed automatically if not already visible.

EN2Z-0937GE51 R0518 1018


CARE BACNET

5. Define the content of the macro and connect the input and output ports as
described in the previous sections.

6. Make sure, you have connected all inputs and outputs. Unconnected points are
red coloured; all points have to be coloured green.

NOTE: Please note the definition of the macro´s inputs and outputs. As they
are not displayed they easily could be left undefined.

The button “More >>” changed to “<< Less”. Use the Save key in the toolbar to save
the changes. Leave the edit mode by clicking on “<< Less” or double-clicking
another macro to apply changes. Otherwise old settings are copied when you use
drag & drop.

Add a Macro of a Control Loop to the Global Macro Library


Prerequisites 1. The user is logged in.
2. A project is open.
3. The opened project has at least one controller, one plant, one loop and one
macro.

Procedure 1. Expand the tree view of the control loop of the plant, the macro is assigned to.

2. Double-click on one of the icons of the ccontrol loops, the macro is assigned to.

RESULT: The Macro window of the control loop opens in the right pane.
The icon of the macro is displayed in this Macro window.

3. Open the Global Macro library:


a. Click menu item Database,

1019 EN2Z-0937GE51 R0518


BACNET CARE

b. Then submenu item Macro Library… ,


c. Or click on button:

RESULT: The Global Macro Library window opens.

4. Transfer the desired macro to the Global Macro Library, by using the window
function drag & drop:
a. Move the mouse cursor above the sensitive field in the upper left corner
of the macro window:

RESULT: The view expands by the macros in the loop.

b. Click once on the desired macro and hold the left mouse-button
pressed.
c. Move the cursor into the Global Macro Library window. The cursor
changes to a “No Parking”-sign if it is moved in areas, you cannot drop
the macro into.
d. Release the left mouse button.
Drag & drop is only possible between folders. The library must not contain any
system macros, except you have the proper license,

RESULT: The macro is dropped into the Global Macro Library.

EN2Z-0937GE51 R0518 1020


CARE BACNET

Edit Global Macro Properties


Prerequisites 1. The user is logged in.
2. There must be at least one global macro.

Procedure 1. Click menu item Database > Macro Library… , or click on button .

RESULT: The Global Macro Library window opens.

2. Right-click the macro.

3. In the context menu, click Macro Properties.

RESULT: The Macro properties dialog box displays.

1021 EN2Z-0937GE51 R0518


BACNET CARE

4. Change properties as desired. For detailed descriptions of the properties,


please refer to the “Create Global Macro” section.

Copy Global Macro


Prerequisites 1. The user is logged in.
2. There must be at least one global macro.

Procedure 1. Click menu item Database > Macro Library… , or click on button .

RESULT: The Global Macro Library window opens.

2. Right-click the macro you want to copy.

3. In the context menu, click Copy Macro.

4. Confirm the message box by clicking OK.

RESULT: The selected macro will be copied.

EN2Z-0937GE51 R0518 1022


CARE BACNET

5. Change the name of the macro if desired as described in the “Edit Macro
Properties” section.

Update Global Macro in Project


Global macros used in projects can be updated if the original macro in the global
macro library is changed.

Prerequisites 1. The user is logged in.


2. There must be at least one global macro.

Procedure 1. Click menu item Database > Macro Library… , or click on button .

RESULT: The Global Macro Library window opens.

2. Right-click the macro you want to update.

3. In the context menu, click Update Macro in Project.

RESULT: The Select Target Project dialog box displays. The macro will be
updated in the selected project.

4. From the Target Project drop-down listbox, select the target project, and then
click OK.

RESULT: The macro will be updated in the selected project.

1023 EN2Z-0937GE51 R0518


BACNET CARE

Delete Global Macro


Prerequisites 1. The user is logged in.
2. There must be at least one global macro.

Procedure 1. Click menu item Database > Macro Library… , or click on button .

RESULT: The Global Macro Library window opens.

2. Right-click the macro you want to delete.

3. In the context menu, click Delete Macro.

4. Confirm the message box by clicking OK.

RESULT: The selected macro will be removed.

NOTE: Other then the handling of macros in the control loops view, unused
and used macros will be deleted. The used ones are available in the
control loop, but no longer stored in the macro library.

Dataexchange between Controllers and 3rd Party Devices / Working with Reference
Datapoints
On the BACnet bus, dataexchange can occur between BACnet controllers and/ or a
BACNet controller and 3rd party devices by using reference datapoints.

Reference datapoints will be mapped to any other physical or software (value)


datapoint type and read or write the value of the assigned datapoint.

The mapping can be performed either


• on the Properties tab of the reference datapoint (see reference datapoint
properties description in the "BACnet Points" section), or
• in the control loop by connecting datapoints of the controller or BACnet objects
of a 3rd party device to inputs or outputs of a control icon

Procedure 1. Display the control icon of the control loop.


2. For assigning hardware points of the controller, expand the project tree and
navigate to the plant that includes the input, output or value datapoint you want
to map to a reference point.

EN2Z-0937GE51 R0518 1024


CARE BACNET

3. Or, for assigning a BACnet object of a 3rd party device, expand the network tree
and navigate to the device that includes the BACnet object, you want to map to
a reference point.

4. In the corresponding tree, select the datapoint or BACnet object, and then
drag&drop it to the input or output of the control icon.

RESULT: The Create new reference point dialog box displays. The name
of the new reference point which will be mapped to the
datapoint is displayed. It´s name reads according to the
terminology as follows: Ref_<datapoint name> or Ref_<BACnet
object name>

1025 EN2Z-0937GE51 R0518


BACNET CARE

5. Click OK.

RESULT: The reference point is created and mapped to the referencing


datapoint or BACnet object.

The name of the reference point or BACnet object is shown at


the input or output of the control icon. In the tree, the reference
point or reference BACnet object is added to corresponding
folder (Reference Input or Reference Output).
The folder location depends on whether the datapoint or
BACnet object has been connected to an input or to an output
of the control icon. It is not dependent on the datapoint or
BACnet object type (input, output) that has been connected.

NOTE: If the datapoint or BACnet object that should be mapped to the control
icon is already mapped to a reference point or BACnet object, the pre-
defined name must be changed or the reference must be kept by
mapping the datapoint to the existing reference point or the BACnet
object to the existing BAC net object.

Example 1: Referenced datapoint will be mapped to new reference point


with changed name

Example 2: Referenced datapoint will be mapped to existing reference point


with same name as before

EN2Z-0937GE51 R0518 1026


CARE BACNET

Find Referenced Datapoint / BACnet Object

Purpose Displaying the referenced datapoint / BACnet object of a reference input or output
datapoint.

NOTE: In the following the procedure of finding a referenced datapoint is


described. The same procedure can applied for finding a referenced
BACnet object.

Procedure 1. A referenced datapoint can be found in the project tree as follows:

a. Expand the tree and navigate to the plant that includes the reference
datapoint.

b. In the tree, right-click the reference point, and then select Goto
Reference in the context menu.

Import Datapoint Information from 3rd Party BACnet Device into Eagle Controller
Purpose Import datapoint information from 3rd Party BACnet Device into Eagle Controller for
using it in the control strategy.

Prerequisites CARE PC must be connected to the BACnet network via IP network interface.
Scanning a BACnet IP network via USB connection is not possible.

Procedure 1. Click on BACShark program icon in the CARE toolbar.

RESULT: BACShark is invoked.

1027 EN2Z-0937GE51 R0518


BACNET CARE

2. In the BACShark menu bar, select the ethernet network interface.

RESULT: BACShark is scanning the network and displays all available


BACnet devices in the left pane.

3. Expand the tree and browse to the BACnet 3rd party device of which
information you want to import into the Eagle controller of your CARE project.

4. Right-click the BACnet 3rd party device, and then click Create EDE File in the
context menu.

RESULT: The Save As dialog box displays.

EN2Z-0937GE51 R0518 1028


CARE BACNET

5. In File name enter a file name for the .EDE file, and then click Save.

RESULT: The .EDE file will be created and saved to the selected folder.
The following message box finally displays.

6. Click OK, and then close BACShark.

7. Open the CARE project.

8. Open the Device Library.

9. In the Device Library, expand the BACnet Devices folder.

1029 EN2Z-0937GE51 R0518


BACNET CARE

10. Right-click the IP Devices folder, and then click Create BACnet Device in the
context menu.

RESULT: A blank device is added to the IP Devices folder.

11. Right-click the device, and then click Import from EDE file in the context
menu.

RESULT: The Open dialog box displays.

EN2Z-0937GE51 R0518 1030


CARE BACNET

12. Locate the .EDE file, select it, and then click Open.

RESULT: The Message Summary dialog box displays. In this, the


imported information of the BACnet device is listed. The
successful import of the .EDE file is indicated at the end of the
summary.

In the Device Library the BACnet device is named accordingly.

1031 EN2Z-0937GE51 R0518


BACNET CARE

The device information can now be used in the control strategy


using reference point functionality.

13. From the device library, add the imported 3rd party BACnet device to the
BACnet IP subnet via drag&drop.

14. Open the control loop, and then drag&drop the BAcnet object(s) of the BACnet
3rd party device from the network tree to the control loop pane as described in
the "Data exchange between Controllers and 3rd Party Devices / Working with
Reference Datapoints" section.

EN2Z-0937GE51 R0518 1032


CARE BACNET

15. For IP devices, check the device ID and IP address and change them
according to your requirements if necessary.

16. For MS/TP devices, check the device ID and MAC address and change them
according to your requirements if necessary.

Read and Use Status Flags from Remote Devices


Purpose Read status flags from a point of a remote device using the reference input in order
to use the status flag information in the application of the controller. The following
status flags can be read:

• in alarm
• in fault
• out of service
• overridden

1033 EN2Z-0937GE51 R0518


BACNET CARE

The status flag information is coded as a BitString with 4 bits (0..3) in a proprietary
property. The property can be read via BACnet and in DDC programs.

Prerequisites Use an existing reference input point or create a new reference input point in the
controller which reads the status flags of the point in the remote device.
In the controller, add the remote point to the reference input point and create 4
binary value points, each for reading one status flag value.

The following procedure describes an example on how to read and use status flag
information by using the reference input, the Split function and 4 binary value points
for using the status flag values in the application.

Procedure 1. Add the reference input point, the Split function and the four binary value points
to the control loop pane.

2. Double-click the reference input point and select the Input tab in the Function
properties dialog box.

3. Double-click the reference input point.

4. In the Input dialog box, select the ´Remote Status Flags` property from the
Property drop-down listbox.

EN2Z-0937GE51 R0518 1034


CARE BACNET

5. Click OK.

RESULT: The Function properties dialog box redisplays

6. Click OK.

RESULT: The reference input indicates the [Remote Status Flags]


property selection.

7. Connect the reference input point with the input of the Split function. Make sure
that the Split function has at least four outputs Y1..Y4. For detailed description
on the Split function, please refer to the Control Icons User Guide,
EN2Z-0940GE51.

8. Toggle read/write for each of the binary value points.

1035 EN2Z-0937GE51 R0518


BACNET CARE

9. Connect the outputs (Y1..Y4) of the Split function to the binary value points.

The transmission of the status flag value (4Bitstring) via input X is as follows:

Y1: bit 0 (1 = in alarm)


Y2: bit 1 (2 = in fault)
Y3: bit 2 (4 = overridden)
Y4: bit 3 (8 = out of service)

10. Confirm the message box always displayed by clicking OK.

EN2Z-0937GE51 R0518 1036


CARE BACNET

Import Text Macro (XFM)


XMFs can be reused in the FALCON or EAGLE controller by importing them into
the Global Macro Library. Note, that this function is restricted to users that have
administrator rights. Before importing an XFM in CARE, it must be converted into a
text file by using the XFM to Text Converter.

Procedure 1. In the CARE folder, navigate to the folder ´csd2txt`and double-click on


csd2txt.exe.

RESULT: The XFM to text convert dialog box displays.

2. From the Unit Conversion table drop-down listbox, select the unit conversion
table. The list shows all table names which were found in the UNITCONV.INI. It

1037 EN2Z-0937GE51 R0518


BACNET CARE

may be necessary to create or change this table in the UNITCONV.INI file


before starting the application

3. Check Prefix Parameter name (Px…) if a prefix "Px" should be added to all
parameters in the text file, with 'x' replaced by the parameter index.

4. Check Keep Parameter global if all XFM parameter will be kept as global
macro parameters, even if they would become local function parameters.

5. Click the Create ID button if you want to create a new macro id, which will be
shown in the text field right to the button.

6. Click File... button, select the XFM (csd file) you want to convert to a txt file in
the Open dialog box and click the OK button. It is recommended to have the
RACL Editor source file of the selected XFM (same name, but extension MCS)
stored in the same directory. Then the XFM to text converter is able to read the
statement comments from the source file and add them to the text output.

RESULT: In the XMF to text converter dialog box, the selected csd file
name is displayed in the Source field. In the Output field, the
converted txt file name is displayed. The result of the converion
is displayed under Result of conversion.

EN2Z-0937GE51 R0518 1038


CARE BACNET

7. Check the conversion result for errors. If successful, the created text file would
be saved in the same directory where the XFM was loaded from, with the same
name but an additional extension TXT, for example, the XFM
"AHCSA02A.CSD" will be saved to " AHCSA02A.CSD.txt".

8. Click the Exit button.

9. Start CARE and open the project.

10. Open the control loop.


11. Open the Global Macro Library by clicking the Global Macro Library icon .

RESULT: The Global l Macro Library window displays.

12. In the upper area, click on a folder to which the macro should be imported.

13. Click right mouse button and click on Import Text Macro in the context menu.

RESULT: The Text import dialog box displays.

1039 EN2Z-0937GE51 R0518


BACNET CARE

14. Click Textfile... button, select the XFM (csd file) you want to import in the Open
dialog box and click the OK button.

RESULT: After the file has been read short information of the read
procedure is displayed and in the upper area are all macros are
listed that could be read from the file.

EN2Z-0937GE51 R0518 1040


CARE BACNET

If multiple macros have been imported (see next graphic), the


tree structure represents the macro dependencies.

15. Check the macros you want to import. Some macros may be checked
automatically if they were needed for other macros you want to import. All
macros you want to import must not already exist in the selected macro library.
Otherwise and error message will occur and the import fails. If there are errors
in the text file, the information text will display a brief description of the error
and where it was found in the text.

16. If the text import has been executed properly, click the Import Macro(s) button.

RESULT: The macro (XFM) is imported and displayed in the tree in the
Global Macro Library window.

17. Click the More>> button and double-click on the macro icon in the upper tree
for viewing the macro logic on the right pane.

1041 EN2Z-0937GE51 R0518


BACNET CARE

18. If desired, edit the macro logic on the right pane.

19. Click the Exit button.

EN2Z-0937GE51 R0518 1042


CARE BACNET

Loop Objects
Purpose A loop object provides the PID control function and allows access of parameters in
control loops and control macros via BACnet. The loop object can only be used in
one and the same controller.

The loop object has the following BACnet properties which are described in detail in
the "Create Loop Object" section:

Values
• Controlled Variable (X)
• Setpoint (W)
• Manipulated Variable (Y)

Parameters
• Proportional Constant (Xp)
• Integral Constant (Tn)
• Derivative Constant (Tv)
• Bias
• Maximum Output
• Minimum Output

Miscellaneous

• Action (direct, reverse)


• Priority of writing
• Speed class
• COV
• Object type
• Object ID
• Instance number
• Descriptor
• Alarm text
• Access Rights
• Alarming
• Event Enrollments

Functional Modes The Loop Object can be set into 2 different functional modes:

1. as PID controller executing its intrinsic PID function. In this case the BACnet
client / HTML Web Interface has only access to the loop object and not to
parameters in control loops / macros (applies to CARE 10.05.00 and higher)

2. as interface which works as a shell for accessing parameters in control


loops and macros by a BACnet client / HTML Web Interface without
executing the PID function (available in CARE 10.08.00 and higher)

In the following, only the main Interface function of the loop object allowing the
access of control loop / macro parameters by the BACnet client / HTML Web
Interface will be described.

For a general description of the PID control function, please refer to the Control
Icons User Guide EN2B-0184GE51. For descriptions of BACnet terms, please refer
to standard BACnet documentation (e.g. the BACnet ANSI / ASHRAE Standard).

Create Loop Object


Prerequisites The Loop Object must be available in the control loop by enabling the "Support new
BACnet features ..." option on the BACnet tab in the Global Options dialog.

1043 EN2Z-0937GE51 R0518


BACNET CARE

(...continued on next page)

EN2Z-0937GE51 R0518 1044


CARE BACNET

General Procedure 1. This procedure describes the general steps and possible settings when
creating a loop object. For applying the loop object with its preferred function
as interface for parameter access, particular settings are necessary which are
also described in detail in the "BACnet Parameter Access via Loop Object"
section.

2. Expand the project in the tree view and browse to the Loop Objects folder.

3. Right-click the Loop Objects folder, and then click Create Loop Object.

RESULT: The loop object is created and its properties are displayed on
the Properties tab on the right.

1045 EN2Z-0937GE51 R0518


BACNET CARE

4. Enter/select loop object properties by doing any of the following:

a. In Name, enter a name.


b. In Descriptor, select a descriptor by clicking the dotted button on the right.
This invokes the Miscellaneous Text Editor. Please refer to the
Miscellaneous Text Editor chapter for details on how to add and change
descriptors.
c. In Alarm Text, select a set of alarm texts by clicking the dotted button on the
right. This invokes the Miscellaneous Text Editor. Please refer to the
Miscellaneous Text Editor chapter for details on how to add and change
alarm texts.
d. In Read Access Level select the access rights for reading values of the loop
object in the Web Interface.
e. In Write Access Level, select the access rights for writing values to the loop
object in the Web Interface.
All users having a user level equal or higher than the
assigned read access respectively write access level of the
loop object will have this access right enabled in the Web
Interface, all others will not (for further details, please refer
to the User Access Manager section).

f. In Controlled Variable Reference (X), assign the controlled input datapoint


by clicking the Add button, then selecting the point in the Select Controlled
Variable Reference dialog box, and then clicking OK.

EN2Z-0937GE51 R0518 1046


CARE BACNET

The assigned input point is displayed in the Controlled


Variable Reference (X) field.

g. In Manipulated Variable Reference (Y), assign the manipulated output


datapoint in the same way as described for the Controlled Variable
Reference (X).

h. If you want to undo an assignment, click the Del button to remove the
datapoint.
i. In Setpoint Reference (W), assign the input datapoint for the setpoint in the
same way as described for the Controlled Variable Reference (X). Or, enter
a value in the Value field alternatively. If you want to read and also write to
the setpoint via BACnet, leave its Read Only flag unchecked. If you want to
read and write to the setpoint via control loop (RACL) but not to write to it via
BACnet, check its Read Only flag (not available if a datapoint was assigned
via Add button).

1047 EN2Z-0937GE51 R0518


BACNET CARE

j. Check the Disable Loop Object Execution checkbox if you want to enable
the usage of the loop object as interface for parameter access in control
loops and macros, or leave the checkbox unchecked if you want to use the
intrinsic PID function of the loop object.

k. In Notification Class, enable alarming for the datapoint by selecting a


notification class with a given priority. By default the following notification
classes with descending priority can be selected:
- Urgent
- High
- Low
- Journal

Each recipient which is assigned to this notification class


will receive the datapoint alarm triggered by the selected
notification. But, alarms will only be generated for
enabled transitions (To-Normal, To-OffNormal, and/or
To-Fault) of a recipient. Each enabled transition will be
propagated with the selected notification. (For further
details please refer to the Notification Class Manager
section).

This connection has not to be mixed up with the


transitions selected under Reporting (see Reporting
description below).

l. In Notify Type, select the notify type.


m.Check Suppress Alarm if alarms should not be generated. Or, uncheck
Suppress Alarm if alarms should be generated. In case of the generation of
alarms setting an alarm delay time is recommended in order to avoid alarms
in case of overshoots.
n. In Alarm Delay, enter an alarm delay (only enabled if Suppress Alarm is
disabled).In Error Limit, enter the absolute value for the difference between
the controlled variable value and the setpoint (error) that must be exceeded
before a ´To Offnormal` event is generated. Please consider the input of an
alarm delay.
p. In Deadband, define the value of the deadband in order to set off an alarm
of event type ´To-Normal`. For this, the present value must, for at least the
defined alarm delay (time), remain within the range:
Low limit plus deadband and high limit
minus deadband.

q. Under Reporting, check which transition type (To-OffNormal, To Fault


and/or Back To-Normal) will be tracked by timestamping.

EN2Z-0937GE51 R0518 1048


CARE BACNET

r. Under Event Enrollments, define which events should be observed by


clicking the corresponding Observe button.

Acked Transitions
Allows observing the acknowledgement behavior of a user for To-Off-
Normal and To-Fault transition events of the datapoint. CARE checks
whether a transition event has been acknowledged or not. If a transition
event has not been acknowledged within a definable delay time, an alarm
based on an event enrollment (event enrollment alarm) is sent to a
supervisory recipient, for example EBI.

To enable observing status flag conditions, click the Observe button to


display the Event Enrollment – AckedTransitions dialog box

In the Event Enrollment – Acked Transitions dialog box,


do the following:

1049 EN2Z-0937GE51 R0518


BACNET CARE

1. In the Name field, change the default name if


desired.
2. In the Description field, enter a meaningful
description if desired.
3. In the Event Type field, note the event type of
the event enrollment object is ´change of
bitstring`.
4. Under Event Parameters, select the transition
event(s) that should be checked for
acknowledgement. The List of Values shows the
possible logical values (checked=true,
unchecked=false, CARE verifies with negative
logic for the false condition) resulting from the
comparison of the selected transition event(s)
and the underlying bitstring mask. An event
enrollment alarm will be sent, if the transition
event will not be acknowledged within the delay
time.
5. In the Alarm Delay field, enter an alarm delay in
sec. The event enrollment alarm will be sent if
the transition event has not been acknowledged
within the delay time.
6. From the Notify Type drop-down listbox, select
the notify type.
7. From the Notification Class drop-down listbox,
select the notification class that defines the
supervisory recipient to which the event
enrollment alarm is sent after an
unacknowledged transition.
8. Under Reporting, check the transition event(s)
that should cause an event notification to the
supervisory recipient.

NOTE:
These settings refer to the event enrollment itself
not to the intrinsic reporting properties of the
datapoint:
To-Off-Normal = event notification is sent if the
acknowledgement is missing within the alarm
delay;
Back-To-Normal = event notification is sent if the
acknowledgement is sent after the alarm delay
has been expired.

If you do not check at least one transition event


and one event parameter, the observation is not
enabled.

9. After entering the values, click OK. On the


Properties tab of the datapoint, the Enabled
check box is checked.

Status Flags
Allows observing status flags conditions. To enable observing status flag
conditions, click the Observe button to display the Event Enrollment –
Status Flags dialog box.

EN2Z-0937GE51 R0518 1050


CARE BACNET

In the Event Enrollment – Status Flags dialog box, do the


following (next page):

1051 EN2Z-0937GE51 R0518


BACNET CARE

1. In the Name field, change the default name if


desired.
2. In the Description field, enter a meaningful
description if desired.
3. In the Event Type field, note that the event type
of the event enrollment object is ´change of
state`.
4. Under Status Flags, select the flags of which
conditions should be observed. The List of
Values shows the possible logical values
(checked=true, unchecked=false) resulting from
the comparison of the selected status flags and
the underlying bitstring mask.
5. In the Alarm Delay field, enter an alarm delay in
sec. An event enrollment alarm will be sent for
each status flag that is enabled (checked) within
the alarm delay time.
6. From the Notify Type drop-down listbox, select
the notify type.
7. From the Notification Class drop-down listbox,
select the notification class that defines the
supervisory recipient to which the event
enrollment alarm is sent.
8. Under Reporting, check the transition event(s)
that should cause an event notification to the
supervisory recipient.

NOTE:
These settings refer to the event enrollment itself
not to the intrinsic reporting properties of the
datapoint:
To-Off-Normal = event notification is sent if a
status flag is enabled within the alarm delay;
To-Normal = event notification is sent if a status
flag is disabled after the alarm delay has been
expired.
If you do not check at least one transition event
and one event parameter, the observation is not
enabled.

9. After entering the values, click OK. On the


Properties tab of the datapoint, the Enabled
check box is checked.

s. In Priority for Writing, select the priority.


t. In Speed Class, select the speed class. The speed class defines how
often the loop will be automatically executed by the controller. The time
slice of the speed class is defined in the property sheet of the controller
(see “Set Execution Speed Categories” sections).
u. In Change of Value Increment, enter the COV value.
v. In Action, select the acting (direct or reverse) that the controller should
perform. The output of a direct-acting controller goes lower as the sensed
value becomes smaller. The output of a reverse-acting controller goes
higher as the sensed value becomes smaller.
w. In Proportional Constant (Xp), enter the value for the proportional band.
x. In Integral Constant (Tn), enter the value for the integral action time.
y. In Derivative Constant (Tv), enter the value for the derivative time.
z. In Bias, enter an offset value if desired.
aa. In Maximum Output, enter the maximum value.
bb. In Minimum Output, enter the minimum value.
cc. If you want to read and also write to a parameter via BACnet, leave its
Read Only flag unchecked. If you want to read and write to a parameter
via control loop (RACL) but not to write via BACnet, check its Read Only
flag.

EN2Z-0937GE51 R0518 1052


CARE BACNET

BACnet Parameter Access via Loop Object


Prerequisites Before applying the procedures described in the following sections, please get
familiar with the basics of control loop engineering by reading the previous sections
in the CARE user guide:

• Control Loops
• Macros

Macro Input and Output Types When creating a new macro (see "Create Macro" section), you add inputs,
outputs, control parameters, and registers to the empty macro. The inputs and
outputs can be configured by assigning one of the following connection types:

• analog
• digital
• universal
• object

These distinctions will be used to avoid input - output mismatches when assembling
the macro and connecting it to other logical components.

The "analog", "digital", and "universal" types allow writing and reading values only.

The "object" type allows writing and reading all properties of the loop object or of
a datapoint connected to the input or output. Hence, the "object" type allows
accessing multiple parameters through one connection. The accessed parameters
are defined in the macro.

Object inputs and outputs at the icon are indicated by darker green and red color
than all the other input and output types.

1053 EN2Z-0937GE51 R0518


BACNET CARE

Functional Modes The Loop Object can be set into 2 different functional modes:

3. as PID controller executing its intrinsic PID function. In this case the BACnet
client / HTML Web Interface has only access to the loop object and not to
parameters in control loops / macros (applies to CARE 10.05.00 and higher)

4. as interface which works as a shell for accessing parameters in control


loops and macros by a BACnet client / HTML Web Interface without
executing the PID function (available in CARE 10.08.00 and higher)

The following figures show the 2 different functional modes:

BACnet CLIENT
PARAMETER

WRITE
READ

LOOP OBJECT

DP DP
X Y

W
PID

Loop Object (PID) Function is enabled.


BACnet client can read / write to Loop object.
Parameters No Parameters of Control Loop / Macro are
Xp, Tn, Tv, ...
accessible.
ACCESS

CONTROL LOOP

DP DP
X Y

W
Control Function
DP

Parameters
Xp, Tn, Tv, ...

Fig. 1. Intrinsic PID Function of Loop Object

EN2Z-0937GE51 R0518 1054


CARE BACNET

In order to use the loop object as Interface, the intrinsic PID function must be
disabled on the Properties pane by checking the Disable Loop Object Execution
option (see Fig. 2).

BACnet CLIENT

PARAMETER

WRITE
READ

LOOP OBJECT

DP DP
X Y

W
PID
Loop Object (PID) Function is disabled.
Loop Object operates as Interface.
Parameters of Control loop / macro
Parameters are accessible.
Xp, Tn, Tv, ...
ACCESS

WRITE
READ

CONTROL LOOP

DP DP
X Y

W
Control Function
DP

Parameters
Xp, Tn, Tv, ...

Fig. 2. Parameter Access via Loop Object Interface

In the following sections, the main Interface function of the loop object will be
described.

Parameter Access in Control Loops and Macros

Basic Steps In order to access parameters of a control loop or macro, the following steps must
be executed in the loop object and in the control loop or macro respectively.

Loop Object
• Disable Loop Object Execution (mandatory)
• Check read only flags for parameters and setpoint (optional and dependant on
requirements / scenario)

Control Loop / Macro


• Configure control variable reference X and manipulated variable reference Y by
assigning datapoints (mandatory)
• Configure setpoint reference W by assigning datapoint or entering value
(mandatory)
• Map parameters of control loop/macro to parameters of loop object.

1055 EN2Z-0937GE51 R0518


BACNET CARE

• Assigning object identifiers and units of datapoints to loop object variables (X, Y)

The individual steps for control loops and macros are described in detail in the
"Parameter Access in Control Loops" and "Parameter Access in Macros" sections.

Parameter Access in Control Loops

Purpose To access parameters in control functions, e.g. PID Plus of control loops by using
the loop object as interface.

Main Rules The following steps are required for a successful access of control loop parameters
using the loop object.

Loop Object Settings

• Disable Loop Object Execution (A)


Enable this loop object property.

• Writeable Parameters via BACnet (B)


Define the parameters Xp, Tn, and Tv to be writeable via BACnet (see also C
below)

• Read-Only Parameters (C)


Define the parameters that should be read only and not writeable via BACnet.
Except the parameters Xp, Tn, and Tv, all parameters should be writeable via
control loop and read-only via BACnet. Some of them can also be set to
constant values.

Control Loop Engineering Steps

• Parameter Mapping (D)


All parameters which should be accessible in the control loop must be assigned
to their counterparts in the loop object. Depending on the home position, the
direction is either read or write (see figure 3).

• Datapoint Assignment (E)


According to BACnet guidelines, the X, Y reference variables must be
configured. This is done by using object IDs of the application datapoints
(reference mappings).

• Setpoint Reference W Configuration (F)


According to BACnet guidelines, the Setpoint W must be configured. This is
done by writing the setpoint from the application datapoint to the loop object
setpoint parameter.

Steps A through C must be established in the loop object, steps D through F must
be established in the control loop. Both kind of procedures are described in the
following.

Schematic Overview First, please refer to the figure on the next page which gives a schematic overview
of the actions A through F of the engineering process

EN2Z-0937GE51 R0518 1056


CARE BACNET

BACnet CLIENT

PARAMETER

WRITE
READ
LOOP OBJECT A
X Y
PID * B C
W
*

Parameters
Xp, Tn, Tv, ...
*

Datapoint E Parameter
Assignment
F D Mapping
ACCESS

WRITE
READ

CONTROL LOOP

DP
X Y
DP **
W
Control Function
DP

Parameters
Xp, Tn, Tv, ...

* Selection dependant on requirement / scenario


** optional

Fig. 3. Schematic Overview of Parameter Access in Control Loop via Loop Object Interface

The following sections describe in detail the steps A through C in the loop object
and D through F in the control loop using a PID Plus control function as an
example.
The PID Plus control function is the counterpart of the intrinsic PID loop object
function.

Read and Write Directions When mapping parameters between the loop object and the control function (D),
the parameter values can be written either from the loop object to the control loop
or vice versa (see next figure).

1057 EN2Z-0937GE51 R0518


BACNET CARE

LOOP OBJECT

DP X Y DP

W
PID

Xp

Tn

WRITE
Tv

Maximum Output

...
PARAMETER

WRITE
READ

ACCESS

CONTROL LOOP

WRITE
DP X Y DP

W
PID Plus
DP

Xp

Tn

Tv

Maximum Output

... *

Fig. 4. Read and Write Directions of Mapped Parameters in Loop Object and Control Loop

EN2Z-0937GE51 R0518 1058


CARE BACNET

Loop Object Settings

This section describes the actions A through C to be done in the loop object for the
PID Plus example.

Procedure 1. Click the Loop Object in the tree to display the Properties tab on the right.

2. On the Properties pane on the right, do the following:

3. For step A, check the Disable Loop Object Execution checkbox. This results
in disabling the PID function of the loop object and enables the usage of the
loop object as interface.

4. For step B, leave the Read Only parameters unchecked for Proportional
Constant (Xp), Integral Constant (Tn) and Derivative Constant (Tv). This
results in writing these parameters by the BACnet client / HTML Web Interface.

5. For step C, check the Read Only options for the parameters Bias, Maximum
Input and Maximum Output. This results in reading and writing these
parameters via the control function (in this case PID Plus) but only reading
these parameters via BACnet. Parameters such as Bias can also be set to
constant values. Constant values cannot be overwritten by the control loop,
BACnet client / HTML Web Interface, or HTML Web Interface.

6. Leave or check the Read Only option for Setpoint Reference (W). For the PID
Plus example used in this scenario, this setting is freely selectable.

7. From the Action drop-down listbox, select ´Direct` or ´Reverse`. This setting is
not relevant for the parameter access behavior.

1059 EN2Z-0937GE51 R0518


BACNET CARE

See also the "Basic Steps" section for the general description of the loop object

Control Loop Engineering Steps

This section describes the steps D through F to be done in the control loop for the
PID Plus example.

Procedure 1. Click the control loop in the tree to display the control loop on the right pane.

2. Perform the actions D trough F which are described in the following:

EN2Z-0937GE51 R0518 1060


CARE BACNET

Parameter Mapping (D)


In area D (see next figure), the parameter mappings are shown. Parameters
can be either written from the control loop (PID Plus control function) to the
loop object or vice versa.
Read-only-parameters such as bias or maximum input and maximum output
are written from the control loop (PID Plus control function) to the loop object.

The writeable parameters Xp, Tn, and Tv are written from the loop object to the
control loop (PID Plus control function).

Fig. 5. Parameter Mapping in Control Loop

Datapoint Assignment (E)


In area E (see next figure), the controlled variable X and manipulated variable
Y are configured by mapping the Object IDs of the corresponding application
datapoints at the inputs to the reference variables of the loop object at the
outputs.

1061 EN2Z-0937GE51 R0518


BACNET CARE

Fig. 6. Datapoint Assignment via Reference Mappings

Setpoint Reference W Configuration (F)


In area F, the setpoint W is configured by mapping the present value of the
application datapoint at the input to the setpoint reference W of the loop object
at the output.

Fig. 7. Setpoint Configuration

Parameter Access in Macros

Purpose To access the control parameters of macros that can include multiple control
functions (e.g. EPID) by using the loop object as interface.

Main Rules A macro can have multiple inputs and outputs, control parameters and registers.
The loop object is designed to allow access to the control parameters of the parent
macro but not to the parameters of its build-in functions. The parameters of the
build-in functions are connected to the inputs, outputs and control parameters
according to the control logic programmed by the developer.

Read - Write Behavior of Macro Inputs and Macro Outputs


Via object input, parameters can be read, and via object output, parameters can be
read and written. At least one output must be configured as ´Object` type (see
"Parameter Access in Control Loops and Macros" section).

As a prerequisite, the loop object must be allocated to the object output. This
assures that the control parameters can be read and written by the BACnet client /
HTML Web Interface. The object output can be seen as a tunnel providing the
macro control parameter values transmission. Based on the usage of the loop
object output, the macro control parameters and the loop object parameters must
be assigned to each other according to the requirements of the logic (Macro -Loop
Object - Properties Assignment). This is done on macro level.

EN2Z-0937GE51 R0518 1062


CARE BACNET

BACnet CLIENT

PARAMETER

WRITE
READ
LOOP OBJECT A
X
PID
Y
* B C
W

ACCESS

WRITE
READ

Allocation

MACRO
DP D Input X Loop Object Output L

Y Output D DP

Macro – Loop Object – Properties Assignment

Input Values Parameters Output Values


W

E D F E
* Selection dependant on requirement / scenario

Fig. 8. Schematic Overview of Parameter Access in Macro via Loop Object Interface

Configure Macro Output

Configure at least one output of the macro as object type as described in the
"BACnet Parameter Access via Loop Object" section.

Loop Object Settings

Configure the loop object (indicated by A, B, and C in the previous figure) in the
same way as for the control loop access described in the "Loop Object Settings"
section, p. 1058.

1063 EN2Z-0937GE51 R0518


BACNET CARE

Allocate Loop Object to Macro

Procedure 1. Drag&drop the loop object onto the macro object output.

RESULT: The loop object is allocated to the object output indicated by the
L in the output sympol and the Loop Object name at the macro
output.

Macro Engineering Steps

This section describes the steps D through F to be done in the macro in order to
make the control parameters available to the loop object (BACnet client / HTML
Web Interface).

Procedure 1. Click the control loop in the tree to display the macro on the right pane.

2. Right-click the macro and then click on Open macro in editor.

EN2Z-0937GE51 R0518 1064


CARE BACNET

RESULT: The macro functions are displayed. For allowing access to the
control parameters of the parent macro, the build-in macro logic
can and should be left unchanged. Only particular steps
including the assignments to the loop object output must be
done which are shown as an example in the following figure.

3. Perform the steps D trough F which are described as an example in the


following:

Parameter Mapping (D)


In area D (see next figure), the parameter mappings are shown. Parameters
can be either written from the control loop to the loop object or vice versa.
Read-only-parameters such as bias or maximum input and maximum output
are written from the control loop (PID Plus control function) to the loop object.

The writeable parameters Xp, Tn, and Tv are written from the loop object to the
control loop (PID Plus control function).

1065 EN2Z-0937GE51 R0518


BACNET CARE

Fig. 10. Parameter Mapping in Macros

Datapoint Assignment (E)


In area E, the controlled variable X and manipulated variable Y are configured
by mapping the Object IDs of the corresponding application datapoints at the
inputs to the reference variables of the loop object at the outputs.

EN2Z-0937GE51 R0518 1066


CARE BACNET

Fig. 11. Datapoint Assignment via Reference Mappings

Setpoint Reference W Configuration (F)


In area F, the setpoint W is configured by mapping the control parameter of the
parent macro at the input to the setpoint at the output.

Fig. 12. Setpoint Configuration

1067 EN2Z-0937GE51 R0518


BACNET CARE

Graphics Editor
The Graphics Editor is a graphic tool for the development of graphic pages that can
be used for for navigation and display when operating the BACnet controller via
Web Interface.

The Graphic Editor provides built-in static and dynamic graphic symbols (elements
and images) which allow you to create interactive plant graphics in which you can
display and change values. Plant graphics typically show the application, including
boilers, heat pumps, water pipes, etc. and attached dynamic display fields which will
show the actual datapoint or setting values in the Web Interface.

Plant graphics can be enhanced with “animated” graphic elements. Pages on


different hierarchical levels can be linked using linking hotspots. “Real” images can
be used as background image for getting a more picturesque style.
The Graphic Editor supports:

• creation of plant graphics


• creation of background images
• graphic symbols library containing static images and dynamic elements
• creation of user-defined graphic symbols
• creation of text blocks
• copy and paste of graphic symbols including databindings
• binding of datapoints to HVAC and custom graphic symbols
• linking of buttons to schedules, calendars, trends and graphic pages (web
pages)
• window function for historic trends
• gif, jpg, and png graphic formats
• import and export of graphic binding definitions in xml format

Via common CARE functions, the following is provided:

• download of the graphic pages including bindings into the controller


• backup and restore of the graphic pages
• Copy graphics including bindings via plant copy function

Background Knowledge
This section describes the file and folder structures and how CARE handles the
files during project and graphic creation in the background. This includes:

• graphic files
• logos
• xml files

EN2Z-0937GE51 R0518 1068


CARE BACNET

• language files its modification

You can skip this section and start with the "Preparation Notes" section if you do not
need to know any information about file management in the background.

File and Folder Structures Graphics Folder

With CARE 10.05.00 and higher, a common project-wide Graphics folder will be
installed by default.

The Graphics folder contains the following sub folders with an original file set which
will be shared among all projects:

Background
background images (GIFs)

Elements
dynamic graphic symbols to be used for binding to datapoints and its relevant XML
files that define the function of the elements.

header*
dummy file. Allows adding a header logo for the web interface

ImageElements
static graphic symbols to be used for drawing a plant schematic

login*
dummy file. Allows adding a login logo for the web interface

original_xml*
country-specific files containing the names (lookup) for elements and buttons

*When creating a graphic, the following folders with its files are copied from the
default Graphics folder to the individual project folder:

• header
• login
• original_xml

1069 EN2Z-0937GE51 R0518


BACNET CARE

Logos Handling By default, CARE provides dummy header and login logos in the folders

• header
• login

of the common project-wide Graphics folder before project creation and as copies in
the individual project folder.

If you want to use customized header and login logos it is recommended to set the
GIF files to the following size:

• headerlogo.gif
360 x 30 pixels
path in web server: usr/local/web/standard/header
• loginlogo.gif
257 x 120 pixels,
path in web server: usr/local/web/standard/login

If the project has not been created yet, copy the custom logo files to the common
Graphics folder.

If the project has already been created, copy the custom logo files to the individual
project folder.

For details on the CARE folder structure, please refer to the previous ""File and
Folder Structures" section.

To complete the logo handling successfully, please select the controller and the
plant that contains the start graphic (first graphic) in the project and select the logos
on the Properties tab under Logos.

NOTE: For the use of this function browser, controller ffirmware 3.04.01 or
higher is required

EN2Z-0937GE51 R0518 1070


CARE BACNET

Languages and Folders By default, CARE provides a localized language dictionary per country where the
customized texts are stored in a list.

According to the country code, the customized texts are stored in the file:

graphic_10xx.xml

The following country-specific files are provided:

• graphic_1030 = Danish
• graphic_1031 = German
• graphic_1033 = English - United States
• graphic_1034 = Spanish (Intern.)
• graphic_1035 = Finnish
• graphic_1036 = French (France)
• graphic_1040 = Italian
• graphic_1043 = Dutch
• graphic_1044 = Norwegian
• graphic_1049 = Russian
• graphic_1053 = Swedish
• graphic_2057 = English - United Kingdom

All these files are provided as original file set in the following folder:

CARE\Graphics

When the project is created, the country-specific xml files will be copied from the
original folder:

CARE\Graphics

to the project-specific folder:

CARE\project\graphic

Modifications of Dictionaries Modifications of buttons and commands or the creation of new buttons and
commands in a particular language are always stored in all country-specific XML
files in the project subfolder.

To display the buttons and commands in the desired language in CARE and in the
web interface, you must select the corresponding language for the user in the User
Administration (typically for the SytemAdmin user).

Preparation Notes
Graphic Resolution – Scaling factor A graphic can be adjusted for different graphic resolutions. This is possible when
creating the graphic initially or later at any time.

The following resolutions and scaling factors are available:

• 800 x 600 scaling factor = 1


• 1024 x 768 scaling factor = 1,28
• 1152 x 864 scaling factor = 1,44
• 1280 x 960 scaling factor = 1,6
• 1600 x 1200 scaling factor = 2
• 1920 x 1440 scaling factor = 2,4

Options for Graphic Size Definition By default, the size when creating the graphic is 1020 x 645 which corresponds to
the resolution of 800 x 600.

You can adjust the graphic size in the following two ways:

5. Select a different resolution/scaling factor (see above list)

or,

1071 EN2Z-0937GE51 R0518


BACNET CARE

6. Create a background graphic that will fit to the available space in the web
interface on the customer PC. Do this as follows:

c. Measure the available space and subtract 30 pixels from X- and Y-


coordinate

Example:
Measured = 1050 x 840
Size of background image = 1020 x 810

d. Save the image under:


C:\Care_10_04xx\Graphics\Background

Logos Files Prepare you GIF files for logos if required according to the description under Logos
Handling in the previous "Basic Knowledge" section.

Graphic Components
A graphic is composed of the following parts:

• background image
• graphic page

Background Image The background image can be a blank uni-colored background or any kind of
created plant schematic. Background images can created by using any graphic tool,
e.g. Viso, or by creating the image in CARE using the static Images provided from
the Graphic library.

EN2Z-0937GE51 R0518 1072


CARE BACNET

Blank uni- colored background image

Plant schematic draw as background image

Graphic Page The graphic page is created by adding static images, dynamic elements, linking
buttons and text blocks to the background image.

Static images
Static images are images and symbols which cannot be bound to
datapoints, e.g. ducts, dampers, fans etc. Static images can also be used
to build a background graphic.

1073 EN2Z-0937GE51 R0518


BACNET CARE

Dynamic elements
Dynamic elements are images and symbols that can and must be linked to
datapoints such as valves, fans, dampers, switches and value fields. These
kind of symbols are used for the display of the changing values in the web
browser

NOTE: Static images and dynamic elements can be of the same category.
For example, there a static and dynamic fans, boilers, valves etc.

Links
can be created and added to graphic pages for referencing to:

– other graphic pages


– external graphic pages
– trends
– schedules
– calendars

HOME SCHEDULE
Text Blocks
Text blocks allow adding any kind of individual descriptions.

Setpoint

Databinding For displaying current and updated datapoint values in the online graphic in the web
interface, each dynamic element must be bound to a datapoint .

Graphic Example The following figure shows an example of a graphic consisting of the plant
schematic in the background and the graphic consisting of elements, buttons and
text blocks in front.

NOTE: Databindings of dynamic elements are not visible in the graphic. To


display databindings, double-click the dynamic element to open the
Properties dialog box.

EN2Z-0937GE51 R0518 1074


CARE BACNET

The Workspace Environment


The workspace environment for creating graphics includes the following
components:

• graphic page selection in the logical plant tree


• drawing pane
• context menu commands
• graphic library

Graphic Page and Drawing Pane

When selecting the graphic in the logical plant tree, the drawing pane on the right
provides the area for drawing the graphic by adding static images, dynamic

1075 EN2Z-0937GE51 R0518


BACNET CARE

elements, and linking buttons from the graphic library and applying commands via
context menu, e.g. creating text blocks.

Context Menu Commands


When right-clicking in the drawing pane, the following commands are available in a
context menu:

• Center under mouse (F2)


Displays the area around the mouse-cursor in the middle. E.g. If the mouse
cursor is on the left side, the view will be moved to the right side.

• Show all (F3)


Zooms out to display the whole window so all used items of the graphic are
visible.

• Undo (CTRL+Z)
Reverts the latest action

• Redo (CTRL+Y)
Repeats the latest action

• Select all (CTRL+A)


Selects all items

• Copy (CTRL+C)
Copies the selected item(s)

• Paste (CTRL+V)
Pastes the selected item(s)

• Cut (CTRL+X)
Removes the selected item(s)

• Delete (Del)
Deletes the selected item(s)

• Save Graphic (CTRL+S)


Saves the graphic

EN2Z-0937GE51 R0518 1076


CARE BACNET

• Import Graphic…
Imports a graphic from …

• Export Graphic…
Exports a graphic to …

• Edit Texts…
Opens a multi-language dictionary Editor, to which you can add new texts.

• Show grid lines


Displays grid lines

• Snap to grid
Adjusts selected items to the grid

• Show Graphic Library


Displays the graphic library

• Create Text Block


Inserts descriptive text at the cursor location

Graphic Library

The graphic library provides default graphic symbols, such as:

• dynamic elements such as analog and digital symbols and animated


equipment (e.g. fans)
• static images such as ducts, fans, coils etc.
• commands for creating linking buttons

The graphic symbols will be added to the drawing space by simple drag&drop.
New graphic symbols (dynamic elements, static images) can be created by adding
default or new graphic symbols and modifying their properties after the addition.

Dynamic Elements in Graphic Library

1077 EN2Z-0937GE51 R0518


BACNET CARE

Static Images in Graphic Library

Linking Button Commands in Graphic Library

EN2Z-0937GE51 R0518 1078


CARE BACNET

Basic Working Techniques for Selection, Adjustment and Editing


Selecting Items

A selected item is indicated by changing the color of its outer frame to blue.

Selecting Single Items

In the drawing pane, do the following:

• with left mouse button, click on the item

Selecting Particular Multiple Items

In the drawing pane, do any of the following:

press CTRL or SHIFT key and simultaneously click with left mouse button on
the items

Selecting All Items

In the drawing pane, do any of the following:

• Press left mouse button and with left mouse button pressed, draw a frame
around all items
• right-click and then click Select all in the context menu
• press CTRL+A keys

• Center under mouse (F2)


Displays the area around the mouse-cursor in the middle. E.g. if the mouse
cursor is on the left side, the view will be moved to the right side.

• Show all (F3)


Zooms out to display the whole window so that all used items of the graphic
are visible.

• Undo (CTRL+Z)
Reverts the latest action

• Redo (CTRL+Y)
Repeats the latest action

1079 EN2Z-0937GE51 R0518


BACNET CARE

• Select all (CTRL+A)


Selects all items

• Copy (CTRL+C)
Copies the selected item(s)

• Paste (CTRL+V)
Pastes the selected item(s)

• Cut (CTRL+X)
Removes the selected item(s)

• Delete (Del)
Deletes the selected item(s)

• Show grid lines


Displays grid lines

• Snap to grid
Adjusts selected items to the grid

Zoom

Press SHIFT or CTRL key and with the key pressed, turn the mouse wheel forward
to zoom in, or turn the mouse wheel backward to zoom out.

Copy and Paste Items

Purpose Remove unnecessary items from the graphic. Items can be:

• dynamic elements
• static images
• linking buttons
• text blocks
• other

Procedure 1. In the drawing pane, select the item(s) you want to copy.

2. Press CTRL+C keys, or right-click and then click Copy in the context menu.

3. In the current graphic or in another graphic selected, press CTRL+V keys, or


right-click and then click Paste in the context menu.

Cut and Paste Items

Purpose Remove unnecessary items from the graphic. Items can be:

• dynamic elements
• static images
• linking buttons
• text blocks
• other

Procedure 1. In the drawing pane, select the item(s) you want to cut.

2. Press CTRL+X keys, or right-click and then click Cut in the context menu.

3. In annother graphic selected, press CTRL+V keys, or right-click and then click
Paste in the context menu.

EN2Z-0937GE51 R0518 1080


CARE BACNET

Delete Items

Purpose Remove unnecessary items from the graphic. Items can be:

• dynamic elements
• static images
• linking buttons
• text blocks
• other

Procedure 1. In the drawing pane, select the item you want to delete by clicking or by
drawing a frame around. Multi-selection using left mouse button and pressing
CTRL or SHIFT key is possible or by drawing the frame around multiple items.

2. Or, to select all items, right-click and then click Select all in the context menu,
or press CTRL+A keys.

3. Right-click and then click Delete Symbol in the context menu, or press
DELETE key.

Undo / Redo Actions

Undo Action
To revert the latest action, do the following:

1. Press CTRL+Z keys, or right-click and then click Undo (CTRL+Z) in the
context menu

Redo Action
To repeat the latest action, do the following:

1. Press CTRL+Y keys, or right-click and then click Redo (CTRL+Y) in the
context menu

Adjust Graphic

Center Items
You can adjust selected items into the center of the drawing pane based on the
mouse cursor position.

2. Select item(s)

1081 EN2Z-0937GE51 R0518


BACNET CARE

3. Press F2 key or right-click and then click Center under mouse (F2) in the
context menu

Example: If the mouse cursor is on the left side, the view will be moved to
the right side

Show All Items


You can show all used items of the graphic as follows:

1. Press F3 key or right-click and then click Show all (F3) in the context menu

Show Grid Lines – Snap to Grid

Purpose Show grid lines and adjusting graphic symbols

Procedure 1. Right-click in the drawing pane, and then click Show Grid Lines in the context
menu.

RESULT: The grid lines are displayed. You can now better position
graphic symbols when moving them in the drawing pane or
dragging&dropping them from within the graphic library.

2. To adjust all graphic symbols to the grid, right-click in the drawing pane, and
click Snap to Grid in the context menu.

RESULT: All graphic symbols not adjusted to the grid yet will now be
adjusted to the grid.

Show Graphic Library

Purpose Show graphic library if it has been closed by accident or explicitly.

EN2Z-0937GE51 R0518 1082


CARE BACNET

Procedure 1. Right-click in the drawing pane, and click Show Graphic Library in the context
menu.

RESULT: The graphic library is displayed.

Basic Steps in Creating a Graphic


Creating a graphic includes the following basic steps:

a. Create new graphic including the setting of graphic properties (graphic


ID, resolution, background image)
b. Add elements, images and butttons from graphic library
c. Set properties for elements and buttons
d. Add text blocks

Create New Graphic

Procedure 1. In CARE, expand the project folder and navigate to the plant for the creation of
graphics on plant level.

Or, expand the project folder and navigate to the controller for the creation of
one single start graphic on controller level (see "Start Graphic and Plant
Graphics").

2. Right-click the Graphics folder, and then click New Graphic… in the context
menu

1083 EN2Z-0937GE51 R0518


BACNET CARE

RESULT: The New Online Graphic dialog box displays.

3. In Graphic Name, enter a name. By default the name is


Graphic_<consecutive number>.

In Xml File Name, the created graphic file is shown. It is named according to
the default graphic name. To each Xml file a graphic ID is assigned according
to the consecutive number of the default graphic name. The graphic ID is used
by the software for interlinking multiple graphic pages properly.

4. To change the default Graphic ID, select another ID from the Graphic ID drop-
down listbox.

5. From the Background drop-down listbox, select the background image to be


used by default for this graphic and for each newly created graphic.

6. To add a particular background to the current graphic file this time only, check
Add Background check box and click File… button.

7. In the Select Background Graphic dialog box, click the File… button.

8. In the Open dialog box, select the file, and then click the Open button.

EN2Z-0937GE51 R0518 1084


CARE BACNET

RESULT: The path of the image is added to the field. The width and height
of the selected and enabled graphic is displayed in the Graphic
Width and Graphic Height fields.

9. From the Resolution drop-down listbox, select the resolution. Depending on


the resolution the scaling factor is updated in the Scaling Factor field.

10. Click OK.

RESULT: An "empty" graphics page is created and displayed on the


Online Graphic tab. On the Properties tab, you can change
properties if desired at any time.

Empty Graphic with Template Graphic as Background

1085 EN2Z-0937GE51 R0518


BACNET CARE

Empty Graphic with Plant Schematic as Background

11. Continue with adding dynamic elements, static images and buttons to the
graphic as described in the "Add Elements, Images, and Buttons from Graphic
Library to Drawing Pane" section.

Start Graphic and Plant Graphics

A basic application scenario is the following:

Start graphic
On controller level, one start graphic is created. Then graphic links will be added
which link to plant graphics. The start graphic can also contain links to datapoints.
The start graphic will be loaded after login to the web interface.

NOTE: If you create graphics, the creation of a start graphic is mandatory.

Plant Graphics
On plant level, multiple graphics can be created to which the start graphic links.
The start graphic can also contain graphic links and links to datapoints.

EN2Z-0937GE51 R0518 1086


CARE BACNET

Logos Selection for Start Page In case a start graphic on controller level is used, you can select a header
and/or login logo which will be displayed on the start page in the web interface.

For details on the logos handling, please refer to the "Basic Knowledge"
section.

Add Elements, Images, and Buttons from Graphic Library to Drawing Pane

Procedure 1. Navigate to the plant, or to the controller.

2. In the Graphics folder, click the graphic.

RESULT: The online graphic and the graphic library displays on the right
pane.

1087 EN2Z-0937GE51 R0518


BACNET CARE

3. In the Graphic library do any of the following:

a. Select t the Elements, Images, or Buttons tab.


b. Expand the corresponding tree.
c. Select the graphic symbol, drag it to the drawing pane and drop it at the
desired place.

4. Continue with setting properties for dynamic elements and buttons as


described in the "Set Properties for Elements and Buttons" section

EN2Z-0937GE51 R0518 1088


CARE BACNET

Set Properties for Elements and Buttons

Procedure 1. On the drawing pane, double-click the dynamic element.

RESULT: The Properties dialog box displays.

Dynamic Element Properties

Dynamic Element Properties (e.g. digital point) with databinding object

1089 EN2Z-0937GE51 R0518


BACNET CARE

Button Properties (e.g. Calendar) with referencing object

2. In the Object Type field, the object type to which the element or button can be
bound, is displayed.

3. From the Object drop-down listbox, select the datapoint (for dynamic element),
or the reference (for button).

4. For a dynamic element, select the text that indicates the function of the
element from the Text Behind Point Value drop-down listbox,.

5. From the Text on Button drop-down listbox, select the text to be displayed on
the button (not applicable to individual symbol button type).

6. To edit text in the language dictionary, click the Edit… button (see "Edit Text"
section for details)

7. For a dynamic element, select the position of the text in relation to the element
from the Text Position drop-down listbox,.

8. If you want to format the text other than the default settings, click the Text
color… button and/or Set Font… buttons and define the desired settings.

9. For a button, click the BG Color… button and define the desired setting If you
want to change the background color.

10. In Mouse over text, enter a text that will be displayed in a tooltip when
hovering the mouse over the button.

11. Click the Apply button to view the result in the drawing pane. If your settings
fulfill your requirements, click the OK button to close the Properties dialog box.

12. Continue by adding text blocks as described in the "Create Text Block" section.

RESULT: The graphic is completed.

EN2Z-0937GE51 R0518 1090


CARE BACNET

Completed Online Graphic

Create Text Block

Purpose Inserts descriptive text at the cursor location

Procedure 1. Right-click in the drawing pane, and click Create Text Block in the context
menu.

1091 EN2Z-0937GE51 R0518


BACNET CARE

RESULT: The Text properties dialog box displays.

2. Enter the text.

3. From the Alignment drop-down listbox, select the alignment for the text.

4. If you want to format the text other than the default settings, click the Text
color… and/or Set Font… buttons and define the desired settings.

5. Click the Apply button to view the result in the drawing pane. If your settings
fulfill your requirements, click the OK button to close the dialog box.

EN2Z-0937GE51 R0518 1092


CARE BACNET

Save Graphic

Purpose To save the changes in the selected graphic.

A graphic will be automatically saved each time you leave the page.

You can explicitly save the graphic as follows:

Procedure 1. Right-click in the drawing pane, and click Save Graphic in the context menu,
or press CTRL+S keys.

Change Graphic Properties

Procedure 1. In CARE, expand the project folder and navigate to the plant or controller that
contains the graphic.

2. In the Graphics folder, click the graphic .

RESULT: On the right, the graphic is displayed on the Online Graphic tab.

3. Select the Propertiest tab .


The following properties can be changed:

1093 EN2Z-0937GE51 R0518


BACNET CARE

– graphic name
– description
– background image
– resolution of background image

4. Change desired properties. For descriptions of the properties, please refer to


the previous steps in the "Create New Graphic" section.

Download Graphic

Purpose Download graphics into the controller.

Prerequisites In order to download the graphic successfully, the databindings and button links
must be correct, i.e. every dynamic element must have a datapoint assigned and
every linking button must reference to a target. CARE interrupts the controller
translation if any databindings or referencing links are missing. In addition, the
application containing the assigned datapoints and referenced targets of the
graphic must be downloaded in the controller prior to the graphic download.

a. Test if the databindings are correct by right-clicking the controller, and


clicking Check graphic bindings in the context menu.

EN2Z-0937GE51 R0518 1094


CARE BACNET

b. If there are missing databindings or links, solve the error by double-


clicking the number in the protocol and correcting the error in the
graphic .

c. Close the dialog box and re-translate the controller.


d. Download the application into the controller

NOTE: An application download will not update a graphic in the controller.

Procedure 1. In the logical plant tree, click the controller, and then select the Setup tab.

2. Connect to the controller by selecting any of the Connection options (LAN,


Remote, or USB) and then clicking Connect.

RESULT: CARE is connecting to the controller.

1095 EN2Z-0937GE51 R0518


BACNET CARE

3. Under Graphics, click Download.

RESULT: The Graphic Download Options dialog box displays.

By default, the graphic pages (XML files, background image, all


standard elements and images and texts are checked and will
be downloaded automatically. If the graphic contains user-
defined elements, images or logos, these options must be
seleted explicitly (see next steps).

EN2Z-0937GE51 R0518 1096


CARE BACNET

4. Check Logos (header and login) if you want to download logos the first time
or when logos had been changed.

5. Check Elements and Images if you have created any own elements and
images you want to download and if this is your first download.

6. Click OK.

RESULT: CARE is downloading the files into the controller.

If the downoad was successful, a message box displays.

7. Click OK.

8. Login to the controller via web browser and check databindings and positions
of elements

Possible errors are:


– Names are missing on buttons
(will not be checked during translate)
– Wrong- / missing datapoint bindings despite the translate check:
• Elements without databinding have a red frame
• Elements with databinding have a blue frame

View / Change Databinding or Links


Purpose View or change the databinding of a dynamic element or the link of a button.

Procedure 1. On the drawing pane, double-click the dynamic element or the linking button.

RESULT: The Properties dialog box displays.

1097 EN2Z-0937GE51 R0518


BACNET CARE

Example: Dynamic Element Properties

Example: Linking Button Properties (Calendar)

2. For dynamic elements, select the datapoint to be assigned from the Object
drop-down listbox .

3. For buttons, select the link (calendar, schedule, graphic page, external graphic
page, and trend) from the Object drop-down listbox .

4. Click the OK button to close the Properties dialog box.

The Graphic Library


Purpose For composing a graphic or a background image, the graphic library provides the
following graphic symbol types:

• default dynamic elements (e.g. analog and digital symbols and animated
equipment) that must be bound to datapoints
• static images (e.g. ducts, fans, coils etc.) without binding behavior
• buttons that must be linked to a target

EN2Z-0937GE51 R0518 1098


CARE BACNET

Graphic Composition
The graphic symbols will be added to the drawing space by simple drag&drop.

Creation of New Elements and Images


New dynamic elements can be created and new static images can be added by
using default or new graphic symbols and modifying their properties.

For the creation of new elements and the addition of new images, the graphic
library provides the following functions:

• Creating groups and renaming (sub folders) for structuring the library tree
• Creating custom element for analog points
• Creating standard element for analog points
• Creating state element (with image) for digital points
• Creating value element (without image) for digital points
• Adding image element(s)
• Editing elements and images
• Deleting elements, images and groups

Create and Rename Group

Purpose Provides structuring the pre-defined library tree by adding new groups. This is done
by adding new sub folders which can named as group.

Procedure 1. In the Graphic library dialog, right-click the group (folder) to which you want to
add a new group (sub folder), and then click Create group in the context
menu.

1099 EN2Z-0937GE51 R0518


BACNET CARE

RESULT: The group is added as sub folder to the selected folder and is
named New Group.

2. Rename the New Group sub folder by right-clicking the sub folder.

3. Then clicking Rename in the context menu.

4. And then changing the name of the highlighted entry.

EN2Z-0937GE51 R0518 1100


CARE BACNET

Add Dynamic Elements to Graphic

By default, there is a fixed set of dynamic elements available:

• Elements with background image


• Per type one element without a background image

Analog
• Only elements are available to display the value
• Default setting: engineering unit will be displayed

Digital
• Display State Text
• Color change on state change
• Display animated gif’s

Multistate
Multistate with (default) or without drop-down listbox

1101 EN2Z-0937GE51 R0518


BACNET CARE

Value-Dependant
In addition there are elements from different libraries where the graphic does
change depending on the datapoint value, e.g. Boiler Buderus:

Procedure 1. If not already opened, open the graphic library by right-clicking in the drawing
pane, and then clicking Show Graphic Library in the context menu.

2. In the Graphic Library, select the Elements tab.

3. Expand the tree, select the element and drag&drop it to the drawing pane.

4. Double-click the element and define the properties in the Properties dialog box.

5. From the Object drop-down listbox, select the datapoint to be assigned.

6. Set further properties as desired.

EN2Z-0937GE51 R0518 1102


CARE BACNET

Add Static Image Elements to Graphic

By default, there is a fixed set of static images available. You can create an
individual group first and add your custom images to it.

Procedure 1. If not already opened, open the graphic library by right-clicking in the drawing
pane, and then clicking Show Graphic Library in the context menu.

2. In the Graphic Library, select the Images tab.

3. Expand the tree, select the image and drag&drop it to the drawing pane.

Create Buttons

Linking via buttons provides the following functionalities:

• graphic navigation via hotspots between multiple graphic pages of the same
project or another project

1103 EN2Z-0937GE51 R0518


BACNET CARE

• graphic display of an external web page


• displaying a single time program
• showing a calendar
• showing a trend display Group and an active trend

Linking buttons are provided in the graphic library. They are arranged in the
following 5 groups.

Each button group, except the Calendar button group, provides 3 different
types of button:

– Graphic Custom Button


can be customized by changing text color, background color and font
and can be resized, round rectangular shape

– Graphic Standard Button


cannot be customized and resized, trapezoid-rectanglar shape

– Individual Symbol Button


pre-defined non-changeable symbol, can be resized, individual button,
group-dependant shape

EN2Z-0937GE51 R0518 1104


CARE BACNET

In the following general procedure, the creation of a custom and a standard graphic
button is described as an example. The creation of other linking buttons can be
performed in the same way.

General Procedure 1. If not already opened, open the graphic library by right-clicking in the drawing
pane, and then clicking Show Graphic Library in the context menu.

1105 EN2Z-0937GE51 R0518


BACNET CARE

RESULT: The Graphic Library displays.

2. In the Graphic Library, select the Buttons tab.

3. Expand the Buttons group from which you want to create a linking button, e.g.
the Graphic Buttons group.

4. Select the button type and drag&drop it to the drawing pane.

RESULT: The Button Properties dialog box displays.

EN2Z-0937GE51 R0518 1106


CARE BACNET

Button Properties of Custom Button

Button Properties of Standard Button

1107 EN2Z-0937GE51 R0518


BACNET CARE

Button Properties of Individual Symbol Button

5. From the Object drop-down listbox, select the graphic page to which the button
should refer.

6. From the Text on Button drop-down listbox, select the text to be displayed on
the button (not applicable to individual symbol button type).

7. If you want to format the text other than the default settings, click the Text
color… button and/or Set Font… button and define the desired settings (only
applicable to custom button type).

8. If you want to change the background color, click the BG Color… button and
define the desired setting (only applicable to custom button type).

NOTE: The web browser adds automatic style options to the custom button. If
the background color is set, these style options will not work anymore.

9. In Mouse over text, enter a text that will be displayed in a tooltip when hovering
the mouse over the button.

10. Click Apply button to view the result in the drawing pane. If the result fulfills
your requirement, click OK button to close the dialog box.

RESULT: The button is added to the drawing pane.

11. If desired, resize the button using the mouse.

Button Command Functions Overview The following screenshots show the main difference in the Custom Button type
dialogs as example for the different functions of the linking buttons:

• Create Calendar Button


Creates a button that links to a calendar.

EN2Z-0937GE51 R0518 1108


CARE BACNET

Create the button in the same way as described in the General Procedure.

• Create External Link Button


Creates a button that links to a graphic page of.

Create the button in the same way as described in the General Procedure.

• Create Graphic Button


Creates a button for navigation via hotspots between multiple graphic pages of
the same project or different projects

Create the button as described in the General Procedure.

• Create Schedules Button


Creates a button that links to a specific time program. This allows operating a
time program/time program overview directly from the graphic.

1109 EN2Z-0937GE51 R0518


BACNET CARE

Create the button in the same way as described in the General Procedure.

• Create Trend Button


Creates a button that links to a trend display Group and displays the
corresponding active trend.

Create the button in the same way as described in the General Procedure.

Create New Dynamic Element in Graphic Library

Purpose In the graphic library, new dynamic elements are created by using:

• default elements
• new graphic symbols drawn by your own
• graphic symbols received from another source

and then

• modifying their properties.

Analog dynamic elements can either display the value in a:

• rectangular field (Standard value)


• plain graphic created by the user (Custom value)

Digital dynamic elements can either display the value in a:

• rectangular field (Value)


• multi-part switchable graphic created by the user (State)

Create Standard Value Element for Analog Point

Purpose Create a dynamic element in the library that will display the analog value in a
standard rectangular field.

EN2Z-0937GE51 R0518 1110


CARE BACNET

Recommendation Before creating the new elements, create new groups for the new elements. In this
case, you can better distinguish between standard and custom elements (see
"Create and Rename Group" section for details).

Procedure 1. In the Graphic Library, right-click the group (folder) in which you want to create
the standard value element, and then click Create standard value element for
analog points in the context menu.

RESULT: In the library tree, a pre-defined rectangular field is added and


simultaneously the Edit Graphic Element displays.

1111 EN2Z-0937GE51 R0518


BACNET CARE

2. In the Edit Graphic Element dialog box, set the properties for the standard
value element as follows:

Image

Name
Defaults to a number.

Width, Height
Size of original GIF file.

Type
Analog

Source
analog_nographic which means a rectangular field without a graphic for the
display of analog values

Value

Display value
Displays value and engineering unit

Position
Position related to a graphic element

BG Color
Background color of text. Click Select… button to select a color.

Name

Width
Text length

Unit Offset X
Position related to a graphic element

Font
Font, font style and size. Click Set Font… button to define font settings.

Alarm

Width
Width of alarm GIF in graphic

Height
Height of alarm GIF in graphic

Offset X, Y
Position related to image size

Overlay
File name that is displayed as tooltip when hovering over the alarm symbol.
If there should be no overlay, the field must be empty.

Manual

Width
Width of manual symbol GIF in graphic

Height
Height of manual symbol GIF in graphic

Offset X, Y
Position related to image size

EN2Z-0937GE51 R0518 1112


CARE BACNET

Overlay
File name that is displayed as tooltip when hovering over the manual
symbol icon. If there should be no overlay, the field must be empty.

3. Click OK button to save settings.

RESULT: The dialog box closes and the defined standard value element is
added to the library tree.

Create Custom Value Element for Analog Point

Purpose Create a dynamic element in the library that will display the analog value in a
customized graphic. The source graphic can be picked from the default set of the
graphic library or created by your own.
Recommendation Before creating the new elements, create new groups for the new elements. In this
case, you can better distinguish between standard and custom elements (see
"Create and Rename Group" section for details).

Procedure 1. In the Graphic Library, right-click the group (folder) in which you want to create
the custom value element, and then click Create custom value element for
analog points in the context menu.

RESULT: The Open dialog box displays showing the default elements of
the library.

1113 EN2Z-0937GE51 R0518


BACNET CARE

2. Select the element you want to use in this folder, or browse to the folder where
you have saved your own images.

3. Click Open button.

RESULT: In the library tree, the pre-defined element is added and


simultaneously the Edit Graphic Element displays.

EN2Z-0937GE51 R0518 1114


CARE BACNET

4. In the Edit Graphic Element dialog box, set the properties for the custom value
as follows:

Image

Name
Defaults name.

Width, Height
Size of original GIF file.

Type
Analog

Source
name of the GIF file

Value

Display value
Displays value and engineering unit

Position
Position related to a graphic element

BG Color
Background color of text. Click Select… button to select a color.

1115 EN2Z-0937GE51 R0518


BACNET CARE

Name

Width
Text length

Unit Offset X
Position related to a graphic element

Font
Font, font style and size. Click Set Font… button to define font settings.

Alarm

Width
Width of alarm GIF in graphic

Height
Height of alarm GIF in graphic

Offset X, Y
Position related to image size

Overlay
File name that is displayed as tooltip when hovering over the alarm symbol.
If there should be no overlay, the field must be empty.

Manual

Width
Width of manual symbol GIF in graphic

Height
Height of manual symbol GIF in graphic

Offset X, Y
Position related to image size

Overlay
File name that is displayed as tooltip when hovering over the manual
symbol icon. If there should be no overlay, the field must be empty.

5. Click OK button to save settings.

RESULT: The dialog box closes and the defined custom value element is
added to the library tree.

Create Value Element for Digital Point

Purpose Create a dynamic element in the library that will display the digital value in a
rectangular field.

Recommendation Before creating the new elements, create new groups for the new elements. In this
case, you can better distinguish between value and state elements (see "Create
and Rename Group" section for details).

EN2Z-0937GE51 R0518 1116


CARE BACNET

Procedure 1. In the Graphic Library, right-click the group (folder) in which you want to create
the value element, and then click Create value element for digital points in
the context menu.

RESULT: In the library tree, a pre-defined rectangular field is added and


simultaneously the Edit Graphic Element displays.

2. In the Edit Graphic Element dialog box, set the properties for the standard
value element as follows:

Image

Name
Default name

Width, Height
Size of original GIF file.

1117 EN2Z-0937GE51 R0518


BACNET CARE

Type
Digital

Source
digital_nographic which means a rectangular field without a graphic for the
display of digital values

Value

Display value
Displays value and engineering unit

Position
Position related to a graphic element

BG Color
Background color of text. Click Select… button to select a color.

Name

Width
Text length

Unit Offset X
Position related to a graphic element

Font
Font, font style and size. Click Set Font… button to define font settings.

Alarm

Width
Width of alarm GIF in graphic

Height
Height of alarm GIF in graphic

Offset X, Y
Position related to image size

Overlay
File name that is displayed as tooltip when hovering over the alarm symbol.
If there should be no overlay, the field must be empty.

Manual

Width
Width of manual symbol GIF in graphic

Height
Height of manual symbol GIF in graphic

Offset X, Y
Position related to image size

Overlay
File name that is displayed as tooltip when hovering over the manual
symbol icon. If there should be no overlay, the field must be empty.

3. Click OK button to save settings.

RESULT: The dialog box closes and the defined value element is added to
the library tree.

EN2Z-0937GE51 R0518 1118


CARE BACNET

Create State Element for Digital Point

Purpose Create a dynamic element in the library that will display the digital values in a multi-
part switchable graphic. The source graphics can be picked from the default set of
the graphic library or created by your own.

Example: Creation of a multistate graphic element that displays the point


states graphically.

Prerequisites For multipart switchable default elements, CARE provides pre-defined appropriate
graphics. These files are named according to the following conventions:

<filename>_0.gif = displays element on point state 0


<filename>_1.gif = displays element on point state 1
<filename>_2.gif = displays element on point state 2

If you want to create your own graphics, you must follow these naming conventions
by saving the graphic files accordingly.

Default Multistate Element displaying 3 Point States

NOTE: When creating the new state element as described in the following
procedure, you do not need to use one element for each state, instead
you have to use and define only one element from the library.
The controller automatically knows which element to display depending
on the point state.

Recommendation Before creating the new elements, create new groups for the new elements. In this
case, you can better distinguish between standard and custom elements (see
"Create and Rename Group" section for details).

Procedure 1. In the Graphic Library, right-click the group (folder) in which you want to create
the state element, and then click Create state element for digital points in
the context menu.

RESULT: The Open dialog box displays showing the default elements of
the library.

1119 EN2Z-0937GE51 R0518


BACNET CARE

2. Select the element you want to use in this folder, or browse to the folder where
you have saved your own images, and select it there.

3. Click Open button.

RESULT: In the library tree, the pre-defined element is added and


simultaneously the Edit Graphic Element displays.

EN2Z-0937GE51 R0518 1120


CARE BACNET

4. In the Edit Graphic Element dialog box, set the properties for the custom value
as follows:

Image

Name
Default name.

Width, Height
Size of original GIF file.

Type
Analog

Source
Name of the GIF file

Value

Display value
Displays value and engineering unit

Position
Position related to a graphic element

BG Color
Background color of text. Click Select… button to select a color.

1121 EN2Z-0937GE51 R0518


BACNET CARE

Name

Width
Text length

Unit Offset X
Position related to a graphic element

Font
Font, font style and size. Click Set Font… button to define font settings.

Alarm

Width
Width of alarm GIF in graphic

Height
Height of alarm GIF in graphic

Offset X, Y
Position related to image size

Overlay
File name that is displayed as tooltip when hovering over the alarm symbol.
If there should be no overlay, the field must be empty.

Manual

Width
Width of manual symbol GIF in graphic

Height
Height of manual symbol GIF in graphic

Offset X, Y
Position related to image size

Overlay
File name that is displayed as tooltip when hovering over the manual
symbol icon. If there should be no overlay, the field must be empty.

5. Click OK button to save settings.

RESULT: The dialog box closes and the defined state element is added to
the library tree.

6. In the graphic, assign a digital datapoint to the element.

Add New Static Image(s) to Graphic Library

Purpose New user-defined static images can be added to the graphic library.

Recommendation Before adding the new images to the library, create new groups for the new images.
In this case, you can better distinguish between default images provided by CARE
and your own images (see "Create and Rename Group" section for details). Copy
the new images to the C:\Care\Graphics\ImageElements folder.

Procedure 1. In the Graphic Library, right-click the group (folder) to which you want to add
the static images, and then click Add image element(s) in the context menu.

EN2Z-0937GE51 R0518 1122


CARE BACNET

RESULT: The Open dialog box displays.

2. Select the image element(s). Multiselection using the CTRL or SHIFT key and
mouse button simultaneously is possible.

3. Click the Open button.

RESULT: The image element(s) are added to the group.

1123 EN2Z-0937GE51 R0518


BACNET CARE

4. To modify the properties of the image element, double-click it in the library tree.

RESULT: The Edit Image Element dialog box displays..

5. Change Name, Width or Height as desired, and then click OK.

Edit Elements, Images, and Buttons in Graphic Library

Purpose The following graphic symbols can be edited in the graphic library:

• Elements
• Images
• Custom Buttons and
• Individual Symbol Buttons

NOTE: The original properties of dynamic elements, static images and buttons
can only be edited in the graphic library but not in the graphic in the
drawing pane. In the graphic of the drawing pane, you can modify
properties such as the databinding and text definition of dynamic
elements and buttons (see " Show / Modify Properties of Elements and
Buttons" section).

Procedure 1. In the graphic library, right-click the item you want to edit, and then click Edit in
the context menu, or double-click the item.

RESULT: The corresponding Edit… dialog box displays.

EN2Z-0937GE51 R0518 1124


CARE BACNET

Graphic Element Edit dialog box

2. Modify the properties as desired and described in the sections:

• Create Standard Value Element for Analog Point


• Create Custom Value Element for Analog Point
• Create Value Element for Digital Point
• Create State Element for Digital Point

Image Element Edit dialog box

3. Modify the properties as desired and described in the section:

• Add Image Element(s) to Graphic Library

1125 EN2Z-0937GE51 R0518


BACNET CARE

Custom Button Edit dialog box

4. Modify the properties as desired and described in the section:

• Create Linking Buttons

5. Click OK to save settings.

Delete Items in the Graphic Library

Purpose Delete items (elements, images, groups, and buttons) in the graphic library.

Procedure 1. Select the Elements, Images, or Buttons tab.

2. Right-click the item you want to delete.

3. In the context menu, click Delete.

Example: Element Deletion

RESULT: The selected item is deleted.

EN2Z-0937GE51 R0518 1126


CARE BACNET

Show / Modify Properties of Elements and Buttons

Purpose In the graphic in the drawing pane you can modify properties such as the
databinding and text definition of dynamic elements and buttons.

NOTE: The original properties (template) of dynamic elements or buttons can


only be edited in the graphic library but not in the graphic in the drawing
pane (see "Edit Elements, Images, and Buttons in Graphic Library"
section).

Procedure 1. Right-click the dynamic element or button in the graphic, and then click
Properties in the context menu, or double-click it.

RESULT: The Properties dialog box displays.

2. Modify the properties as desired and described in the "Set Properties for
Elements and Buttons" and "Create Linking Buttons" sections.

Edit Texts
Texts of buttons and commands are stored in a country-specific language
dictionary. All language dictionaries are based on a common set of reference terms
called ´Lookup`. Each language dictionary is composed of language pair entries
using the common lookup.

Modifications of texts or the creation of new texts in a particular language are


always stored in all language dictionaries.

NOTE: To provide the selection of the texts in the desired language in CARE,
you must select the corresponding language for the user in the User
Administration.

1127 EN2Z-0937GE51 R0518


BACNET CARE

Procedure 1. Right-click in the graphic in the drawing pane, and then select Edit Texts… in
the context menu.

RESULT: The Edit Localized Dictionaries dialog box is displayed. In the


Language drop-down listobox, the dictionary can be selected.
In the Lookup and Text columns, the language pair of the
selected language is displayed. The Used column shows
whether the text is already used in the graphic (checked) or not
(unchecked).

EN2Z-0937GE51 R0518 1128


CARE BACNET

2. From the Language drop-down listbox, select the dictionary you want to modify.

3. To change an entry, click twice in the field(s), then delete the text or characters,
and then enter the new text.

NOTE: For lookups no space or special characters are allowed.

4. To add a new language pair, scroll to the end of the list till the blank row with
the asterisk is displayed.

5. Click once in the field(s), and then enter the new text.

6. To delete an entry, click on the first column with the arrow.

1129 EN2Z-0937GE51 R0518


BACNET CARE

NOTE: Texts that are used in the current graphic are checked as used in the
Used column. When deleting an unused text in the current graphic
that may be used in another graphic, it does not work anymore in the
other graphic where it was used.

7. Click the Delete button.

RESULT: The seletected language pair is deleted from the dictionary. All
modifications of texts done in this particular dictionary are stored
in all other country-specific dictionaries (XML files).

8. Click OK button so save settings.

Fast Editing of Lookup Names

Purpose For each individual symbol, an existing lookup name can be edited or a new lookup
name can be created. The edited and new lookup name will automatically added to
the Localized Dictionaries.

Procedure 1. Right-click the symbol and in the context menu, select Edit Text.

2. In the Create/Edit Loop dialog box, change the text if you want to change an
existing lookup.

3. Or, check the Create new lookup checkbox if you want to create a new
lookup.

EN2Z-0937GE51 R0518 1130


CARE BACNET

4. Enter the new text in Text and the lookup name (string) in Lookup.

In the Edit ocalized Dictionaries dialog box, an edited lookup is


updated and a new look up is added for reuse.

Copy Graphic
Graphics can be copied in the following ways:

• Copy graphic between plants of the same controller or another controller


• Import graphic
• Copy plant
• Copy controller

Graphic Description and Databindings Besides general data such as size etc, for each graphic the content and function of
the included elements and images is described in the corresponding XML file. This
includes the definition of the bindings between dynamic elements and datapoints
(databindings). The databinding between an element and a datapoint is established
via the BACnet object ID of the datapoint. The BACnet object ID is used for
displaying the datapoint value.

For a successful copy process the databindings must be kept.

Graphics can be copied either by context menu commands, keyboard shortcuts


usage or drag&drop.

Copy Graphic Between Plants of Same or Other Controller

Scenario 1 Copying between same or different plant of same controller

Method 1
Usage of context menu commands or keyboard shortcuts.

1131 EN2Z-0937GE51 R0518


BACNET CARE

When using the context menu commands or the corresponding keyboard shortcuts,
the process copies the elements and images only. The background image must be
assigned separately. This method allows copying a graphic within the same plant
and different plants of the controller.

Procedure 1. In the same or different plant, create a new graphic.

2. Set the same resolution as in the source graphic and assign the background
image.

3. Open the source graphic.

4. Select all elements by right-clicking in the drawing pane and selecting Select
all in the context menu, or by pressing CTRL+A keys.

5. Copy the selected elements by right-clicking in the drawing pane and selecting
Copy in the context menu, or by pressing CTRL+C keys.

6. Select the new graphic, and paste the copied elements by right-clicking in the
drawing pane and selecting Paste in the context menu, or by pressing CTRL+V
keys.

7. Reposition all elements as required.

Procedure 1. In the drawing pane, select the item you want to delete by clicking or by
drawing a frame around. Multi-selection using left mouse button and pressing
CTRL or SHIFT key is possible or by drawing the frame around multiple items.

2. Or, to select all items, right-click and then click Select all in the context menu,
or press CTRL+A keys.

Method 2
Via Drag&Drop.

When copying via drag&drop, the complete graphic including the background
image is copied. A

Procedure 1. In the source plant, select the graphic in the Graphics folder.

2. Drag&drop it to the Graphics folder in the different target plant.

Bindings Result As long as the target graphic is inside the same controller, the data bindings will
remain.

Scenario 2 From plant in one controller to plant in another controller

The copy steps are done in the same way using method 1 or 2 as when copying
graphics within the same controller (see previous procedures). But the binding
result is different.

Bindings Result When copying a graphic from a plant in one controller to a plant in another
controller, the bindings will be lost.

Copy Graphic via Copy Plant

The plant copy function copies:

• Datapoints
• Control loop
• Fast access list
• Graphics

Bindings Result When copying a plant, the datapoints can be renamed and the bindings will
remain.

EN2Z-0937GE51 R0518 1132


CARE BACNET

Copy Graphic via Copy Controller

Bindings Result When copying a graphic via controller copy, the datapoints can be renamed and
the bindings will remain.

Copy Graphic via Graphic Import / Export

Purpose To copy a graphic from one project / application(source) to another project /


application (target).

Please refer to the "Import / Export" Graphic section.

Import / Export Graphic


Purpose To copy a graphic from one project / application(source) to another project /
application (target).
For a successful import of a graphic with its bindings, the target CARE application
and the source XML files must match. Normally, an XML file from a CARE
application A (source) does not fit to an XML file of a CARE application B (target).

If the XML file from the CARE application A should be used for the CARE
application B, all bindings need to be checked and re-assigned.

NOTE: When exporting and importing a graphic, the background image will not
be exported and imported respectively.

Procedure 1. Open the source application and select the graphic.

2. Right-click in the drawing pane and click Export Graphic in the context menu.

3. In the Open dialog box, navigate to the target folder, enter a name for the XML
file, and then click the Open button.

4. Open the target application and create a new graphic.

5. Right-click in the drawing pane and click Import Graphic in the context menu.

1133 EN2Z-0937GE51 R0518


BACNET CARE

6. In the Open dialog box, navigate to the target folder of the source application,
select the XML file, and then click the Open button.

7. Re-assign the bindings between elements and datapoints.

Project Backup and Restore


When backing up a project, the following graphic parts are saved in the backed up
project:

• background image
• logos
• lookup texts

Standard elements, images and buttons are not backed up since they are available
in CARE by default.

If you have created own elements and images, they will not be backed up.

When restoring a project, the following graphic parts will be included in the restored
project:

• background image
• logos
• lookup texts

Because own elements and images are not backed up, they cannot be restored and
must be added to the restored project manually.

EN2Z-0937GE51 R0518 1134


CARE BACNET

Schedules and Calendars


Purpose To create time sequences for controller operation of devices. For example, set
HVAC start and stop times.

Overview

Schedules Schedules are assigned to plants and implement these command programs. Each
plant of a controller can have multiple schedules assigned and each schedule can
command devices of other controllers.

On a weekly basis, each schedule specifies a datapoint or a list of multiple


datapoints. Each datapoint includes switchpoints to command the present value of
the datapoint (switched properties). The week program defines the normal daily
activity of the system by specifying which switchpoints are to be commanded each
day of the week. The week program applies to a definable time period. There is only
one week program per schedule.

Besides the week program, specific programs called exceptions can be created.
Exceptions have higher priority than the week program and will overwrite the week
program for a definable time period. Exceptions can have one of the following time
periods:

• Specific Date
e.g. Christmas Eve or 5.5., the whole of May, or the whole year of 2004

• Date Range
e.g. Summer holidays from 29.7-7.9.2004

• Recurring Event
e.g. every last Friday of every month

• Calendar Reference
A project-wide calendar provides dates, e.g. regional holidays and
public/religious festivals or any other particular date. The time period can be a
specific date, a date range or a recurring event.

Calendars Via exceptions which reference to a project-wide calendar, CARE provides global
scheduling because calendar dates are executed in each controller of the project
which references to the calendar. Changes in multiple particular controller
schedules can be quickly made by simply changing the referenced calendar.

The schedule-calendar reference provides specific scheduling of a plant by parallel


access to the project-wide calendar data.

1135 EN2Z-0937GE51 R0518


BACNET CARE

PROJECT CALENDAR

Specific Date

Date Entries Date Range

Calendar Reference Recurring Event

Global Scheduling

CONTROLLER 1

PLANT SCHEDULE

Time Period

Datapoints/Switched Week Program


Properties

Switchpoints

Overridde
Specific Date

Date Range
Exception
Recurring Event
Switchpoints
Calendar Reference
CONTROLLER n

PLANT SCHEDULE

Specific Date

Datapoints/Switched Date Range


Exception
Properties
Recurring Event
Switchpoints
Calendar Reference

Fig. P1: Calendars and Schedules Overview

EN2Z-0937GE51 R0518 1136


CARE BACNET

Schedules
In general, an application program includes multiple schedules, each having one
datapoint (input and value datapoints only) assigned. In certain cases, a schedule
can have multiple datapoints assigned (Enhanced Assignment). Each datapoint
includes switchpoints (time and value) which command the present value of the
datapoint (switched properties). In addition, each schedule has a schedule default
value which is valid at 00:00 (midnight), or when the switchpoint is NULL. The
switchpoints are part of the regular week program or of exceptions. Each schedule
writes the value of the switchpoint or the schedule default into the priority array
along with a definable priority for writing (1..16). Finally, the priority array delivers
the present value of the datapoint according to the array´s prioritization mechanism.
Both, the switchpoint value and the schedule default value can be a real value (i.e.
any value except NULL) or NULL. For each schedule a priority for writing (into the
priority array) must be defined.

NOTE: For schedules, it is recommended to assign priorities for writing in the


range of 10 through 16. It is strongly recommended not to assign the
same priority for writing to different schedules that command the same
property.

SCHEDULE
(Name / Description / Access Rights / Time Range / BACnet Information)

Schedule Default Week Program Exception(s)

Switchpoint 1 Switchpoint 1
Switchpoint n Switchpoint n

Present Value
Real Value or NULL

Priority for Writing (1 .. 16)

1 (high)

Present Value

Priority Array
16 (low)

Datapoint

Fig. P2: Present Value Generation Mechanism of Datapoint

Excursus: Present Value / Priority Array The present value is controlled by a command prioritization mechanism which is
based upon a fixed number of priorities that are assigned to command – issuing

1137 EN2Z-0937GE51 R0518


BACNET CARE

entities (BACnet tasks, schedules, control strategy, manual operator inputs, etc.).
Each of these entities writes to the present value with its assigned priority level. The
number of priorities is arranged in a priority array (list) of descending priority (1..16).
The priority array can include max. 16 values and will be continuously updated by
written values caused by the command-issuing entities.

The present value is determined in the associated priority array of the datapoint by
scanning the priority entries downwards from priority 1 through 16. The entry with
the highest priority showing a real value dominates all other entries with lower
priorities and is always written to the present value. Blank entries (NULL, indicated
by dash in the Excel HTML Interface) are ignored. If the priority array is empty (all
entries are blank) then the relinquish default value becomes valid and is written to
the present value. The relinquish default value cannot be set to NULL and allows
starting up a control system with a defined status/value.

Priority Array Example:

Priority Level Value


1 Manual Life Safety -
2 -
3 -
4 -
5 Critical Equipment Control 19,5 °C
6 Minimum On Off
7
8 Manual Operator 21,0 °C
9 -
10 -
11 -
12 -
13 -
14 -
15 Control Program -
16 -
Relinquish Default 20,0 °C

In the example, Critical Equipment Control has the highest priority and is written to
the present value. Note that Manual Life Safety has a higher priority but no value
(blank, NULL). Writing NULL to the present value results in a relinquish operation in
the priority array and “deletes” the entry at the corresponding position. As soon as
the priorities 5 and 8 are relinquished e.g. via BACnet service, the relinquish default
of 20,0°C will be valid for the present value.

Prioritization within Schedule(s) The present value of a datapoint is controlled by the writing priorities of all the
command issuing entities (BACnet tasks, control strategy, schedules etc.). In
addition, within schedules there is also a prioritization mechanism for evaluating
the present value before passing it into the priority array.

The following schedule items can be involved in the evaluation of the present value
(descending priority):

1. Manual value operation


2. Exceptions
3. Week program
4. Schedule default

EN2Z-0937GE51 R0518 1138


CARE BACNET

Manual Value
(Out of Service)

Value Priority
Calendar Reference

Exception Priority
Specific Date
Exception A (e.g.: prio 3)
Date Range

Recurring Event

Calendar Reference

Specific Date
Exception n (e.g.: prio 5)
Date Range

Recurring Event

Week Program
Mo Tue Wed Thu Fri Sa Su

Schedule Default

PRESENT VALUE

Fig. P3: Present Value Evaluation Mechanism within Schedule

The above graphic shows the following:

Manual value operation


Putting the schedule in manual operation (out of service) has the highest writing
priority level (possible in the EAGE Web Interface or via BACnet).

Exceptions
Exceptions associated with a schedule have the second writing priority level.
Exceptions must also be prioritized by exception priority assignment.

NOTES: The exception priority should not be mixed up with the writing for priority
of the schedule itself.

It is strongly recommended not to assign the same priority to different


exceptions.

If multiple exceptions are defined within a schedule, the active exceptions are
executed according to their priority. That is, only the active exception with the

1139 EN2Z-0937GE51 R0518


BACNET CARE

highest exception priority is executed. The exceptions with lower priority are ignored
as long as the high prioritiy exception delivers a real value and not NULL.

The valid periods of an exception should be seen in the following hierarchical order:

• Calendar Reference
• Specific Date
• Date Range
• Recurring Event

Hence, it is recommended to define the priorities of the exception accordingly. In


other words, if you have set, for example, ´calendar reference` for an exception, you
should assign a higher exception priority to this exception than to a second
exception for which you have set e.g. date range as valid period.

Each exception starts with its first switchpoint and usually runs until midnight
(schedule default). To enable an exception, the first switchpoint value mus be a real
value. To disable an exception, the last value must be NULL.

Week Program
The week program has the third writing priority level.

Schedule default
Schedule default has the fourth writing priority level and is only valid if all levels
above are NULL.

Time Frames of Schedules


and Exceptions Each and every schedule is terminated at midnight (00:00h) and the present value
of the datapoint is set to the schedule default. As a consequence this meams: If you
want the value to stay at its programmed level continuing into the next day, you
explicitly must set the original datapoint value at 00:00h.
Each Exception is terminated at midnight (00:00h) on the day of its activation. If the
same exception is reactivated for the following day, it starts with NULL (unless there
is no defined value programmed at 0:00h).

View Schedules

Procedure 1. In the logical plant tree, navigate to the plant and click on Schedules.

RESULT: On the right pane, the Properties (Schedule Name, Switched


Properties and Description) of the schedules are shown.

Schedules can be newly created, edited, copied and deleted.

EN2Z-0937GE51 R0518 1140


CARE BACNET

Create New Schedule

Procedure 1. On the Properties tab, click the New button.

RESULT: The Create & Edit Schedule dialog box displays.

On the Switched Properties tab, the switched properties will be selected.

Datapoints can be switched in two ways:

Standard
Just a single datapoint with its present value property can be switched. By
default, a datapoint has the present value property assigned.

Enhanced
Multiple datapoints and/or other properties than the present value can be
switched.

Under Datapoint Filter, a filter for listing certain datapoints to be switched can
be defined You can select datapoints from different plants of the same
controller (controller name displayed in the Controller field) or from a different
controller (switching remote datapoints). To do so, click the Plant/Device>>
button, and then select the datapoint from the plant/controller in the Select
plant/data point dialog box.

The filtered datapoints will be listed below in the Assignable Datapoints list. By
default, all datapoints of the originator plant are available in the list. Once
selected, the datapoint will be inserted in the Properties field under Switched

1141 EN2Z-0937GE51 R0518


BACNET CARE

Properties. Under Eng. Unit / State text, its engineering unit respectively the
state text is displayed.

By clicking the corresponding Details button, the datapoint´s details can be


viewed/edited, either of the filtered datapoint/property or the selected
datapoint/switched property.

Select Datapoints/Switched Properties 2. To filter certain datapoints, do one of the following:

From the Point Type drop-down list box, select the point type to be filtered.

NOTE: Inputs cannot be switched.

and/or

In the Point Name field, enter a search text to display specific datapoint names.
Wildcards can be used. By default, all datapoints will be displayed as indicated
by an asterisk (*). A blank field is interpreted as *. The filter function is not case
sensitive.

If you want select datapoints from another plant or controller, click the
Plant/Device>> button. In the Select plant/data point dialog box, select the
datapoint from the plant or controller in the Select plant/data point dialog box.
You can filter for datapoints to be selected by clicking the Filter check box, and
then selecting the datapoint type from the drop-down listbox or entering a
search text to display specific datapoint names. Wildcards can be used. By
default all datapoints will be displayed as indicated by an asterisk (*). A blank
field is interpreted as *. The filter function is not case sensitive. In the Select
plant/data point dialog box, click the Apply button to display the found
datapoints.

NOTES: By selecting datapoints of another controller you can switch those


datapoints in that controller remotely.

Inputs cannot be switched.

3. Click the Go button to apply the filter. All datapoints matching the filter criteria
will be displayed under Assignable Datapoints.

4. Select the datapoint you want to be switched and click the Select button.

RESULT: The datapoint will be inserted in the Properties field under


Switched Properties.

EN2Z-0937GE51 R0518 1142


CARE BACNET

5. To edit details of a datapoint that is selected in the list, click the Details button.

NOTE: By using the Select button, only one datapoint can be switched
(Standard Mode). To switch multiple datapoints and/or other
properties than the present value, click the Enhanced button
(Enhanced Mode).

6. If you want to use the Enhanced mode, continue with step 8.

or

7. If you want to proceed with creating the schedule, continue with step 16.

8. Click the Enhanced button.

RESULT: The Enhanced property selection dialog box displays.

1143 EN2Z-0937GE51 R0518


BACNET CARE

9. To filter certain datapoints, do one of the following:

If you want select datapoints from another plant or controller, click the
Plant/Device>> button. In the Select plant/data point dialog box, select the
datapoint from the plant or controller in the Select plant/data point dialog box.
You can filter for datapoints to be selected by clicking the Filter check box, and
then selecting the datapoint type from the drop-down listbox or entering a
search text to display specific datapoint names. Wildcards can be used. By
default all datapoints will be displayed as indicated by an asterisk (*). A blank
field is interpreted as *. The filter function is not case sensitive. In the Select
plant/data point dialog box, click the Apply button to display the found
datapoints.

NOTES: By selecting datapoints of another controller you can switch those


datapoints in that controller remotely.

Inputs cannot be switched.

On the Switched Properties tab, select the point type to be filteredfrom the
Point Type drop-down list box.

If multi-state points (MO, MV) have been selected from the Point Type drop-
down list box, enter the number of stages in the Number of Stages field.

and/or

In the Point Name field, enter a search text to display specific datapoint names.
Wildcards can be used. By default all datapoints will be displayed as indicated
by an asterisk (*). A blank field is interpreted as *. The filter function is not case
sensitive.

and/or

From the Property drop-down list box, select the property of the datapoints to
be searched for.

EN2Z-0937GE51 R0518 1144


CARE BACNET

10. Click the Go button to apply the filter. All datapoints/properties matching the
filter criteria will be displayed in the Datapoints list under Select Properties to
Switch. Datapoints/properties can be put into into switching status and vice
versa by moving them between the Datapoints and the Switched Properties list.

11. To move datapoints/properties between the two lists, that is, to make them to
be switched or not, do one of the following:

To move certain datapoints/properties:

1145 EN2Z-0937GE51 R0518


BACNET CARE

highlight the datapoints/properties to be moved in the Datapoints list


respectively in the Switched Properties list. Multiselection by using the CTRL,
respectively the SHIFT key is possible.

Click the Single Arrow button with desired direction.

Or,

To move all datapoints in one step:


Click the Double Arrow button with desired direction.

NOTE:
Software performs consistency checking for datapoint type, property and
engineering unit for the datapoints that have been selected and moved into the
switching status.

Consistency checking assures that the same schedule does not switch
datapoints:

• of different types, e.g. AO and BO


• with different properties, e.g. present value and low alarm limit
• of which engineering unit does not correspond to the property to be
switched

If one of these items do not match, the inconsistency is indicated in red with the
corresponding comment number in the OK column of the point name.

In addition, a warning displays in case you want to continue by clicking the OK


button.

12. Confirm the message by clicking the OK button.

EN2Z-0937GE51 R0518 1146


CARE BACNET

13. Remove inconsistent properties from the Switched Properties list (see step 14).
14. Click the OK button in the Enhanced Property Selection dialog box.

RESULT: In the Create & Edit Schedule, the properties will be inserted in
the Properties list under Switched Properties. The Details, Week
and Exceptions tabs are now available for completing the
schedule.

Define Details 15. Click the Details tab.

1147 EN2Z-0937GE51 R0518


BACNET CARE

Here you can enter the following details of the schedule:

• Name
• Description
• Valid period
• Priority for writing
• Access rights
• BACnet Object Information
• Schedule default

16. In the Schedule Name field, enter the name for the schedule.

17. In the Description field, enter an additional description if desired.

18. The valid period for the schedule will be defined by selecting the start and end
date under Valid from and Valid until. By default, the schedule is valid one year
from the current date on.

To define the valid period of the schedule, do the following:

Click the Valid From checkbox and select the start date from the drop-down list
box.

EN2Z-0937GE51 R0518 1148


CARE BACNET

NOTE: If the checkbox is unchecked, no start date can be selected. This


means that the schedule is valid on any date up to and including the
end date.

Click the Valid Until checkbox and select the end date from the drop-down list
box.

NOTE: If the checkbox is unchecked, no end date can be selected. This


means that the schedule is valid on any date from the start date on.

NOTE: If both checkboxes are disabled, the schedule is always valid.

19. From the Priority for Writing drop-down list box, select the priority between 9
and 16 (lowest). The priority defines which priority the schedule will have in the
BACnet priority array.

20. From the Read Access level drop-down list box, select the user level that
should have read access for the schedule.

Schedules will only be displayed in the EAGLEWeb Interface if the read access
level of the user is equal to or higher than the read access level of the
schedule.

21. From the Write Access level drop-down list box, select the user level that
should have write access for the schedule.

Creating, editing, deleting and copying of schedules in the EAGLE Web


Interface is only possible if the user's write access level is equal or higher than
the write access level of the schedule.

22. In the Schedule Default Value field, you must enter a schedule default value.
The schedule default value is used at 00.00 (twelve midnight) as present value
of all switched properties when no other value is in effect. The schedule default
value can be NULL or any value, for example, ´value in %` for analog outputs,
or ´running` for digital outputs. The NULL value removes the current value entry
of the switched properties from the priority array. Then the next lower value in
the priority array becomes the present value of the switched properties.

Enter the value in the Schedule Default Value field, or check the NULL
checkbox.

Create Week Program 23. Proceed the creation of the schedule by clicking the Week tab.

1149 EN2Z-0937GE51 R0518


BACNET CARE

On each “Day” tab, you can


enter time-value pairs.

On the Week tab, you can


enter switchpoint blocks.

RESULT: On the Week tab, you create the weekly program that should be
performed during the schedule period (see Details tab).

In the main area of the Week tab, an empty one-week time


period is displayed twice: one Week tab including all days and
one separate tab for each day

In the Properties list under Switched Properties, the switched


properties are displayed. The corresponding engineering unit /
state text of the selected property is shown on the right under
Eng. Unit / State Text.

To view/edit a datapoint´s details selected in the list, click the


Details button.

The week program will be created by defining switchpoints. Switchpoints are


time-value pairs per day that determine the time when the schedule sets a
certain value. There are two ways to create switchpoints:

• by entering the time-value pairs in a table


• by creating switchpoint blocks graphically

RESULT: The switchpoints are shown in the daily time scale with start
time and value. The end time of a switchpoint is determined by
the starttime of the consecutive switchpoint. The period between
two switchpoints is called a switchpoint block, that is, a week is
normally divided into consecutive switchpoint blocks. Each
switchpoint block has its special value which changes with the
start time of the next switchpoint. A switchpoint block is valid, at
the longest, until 00.00 (twelve midnight) when the schedule
default value becomes valid. The schedule default value is then

EN2Z-0937GE51 R0518 1150


CARE BACNET

valid until the next switchpoint. The schedule default value can
be deleted by defining a switchpoint at 00.00.

Example (see next figure):


Switchpoint block 1 is defined by switchpoint 1 (Sw.P.1)
starting on Monday 06.00 and ending on Monday 12.00 with a
value of 20.00. Switchpoint block 2 is defined by switchpoint 2
(Sw.P.2) starting on Monday 12.00 and ending on Monday
22.00 with a value of 23.00. Switchpoint block 3 is defined by
switchpoint 3 (Sw.P.3) starting on Monday 22.00 and ending on
Monday 22.59 with a value of 16.00. At 00:00 the schedule
default value, in this case NULL, becomes valid. Switchpoint
block 4 is defined by “switchpoint4” (S.D.V.4 = schedule
default value) starting at 00:00 and ending on Tuesday 6.00
with the actual value of the priority array (EAGLE Web
Interface). Switchpoint block 5 is defined by switchpoint 5
(Sw.P.5) starting on Tuesday 06.00 and ending on Tuesday
12.00 with a value of 20.00.

S.D.V.4

Sw.P.1 Sw.P.5

5
1
Sw.P.2 Sw.P.6

Sw.P.3

Define Switchpoints in Table 24. Click on the Mon tab, for example.

1151 EN2Z-0937GE51 R0518


BACNET CARE

25. Click the New button.

26. Enter the time in the Time cell and press the ENTER key.

27. Enter the value in the Value cell and press the ENTER key.

28. If desired, enter further time-value pairs as described in steps 23 - 27.

To copy the switchpoint of this day to one or multiple other day(s), click the
Copy day to button.

RESULT: The Copy Switch Points dialog box displays.

EN2Z-0937GE51 R0518 1152


CARE BACNET

Under Source weekday, the currently selected day is displayed.

29. Under Target weekdays, click on the day(s) you want the source day to be
copied to. Click the Select All button to select all target weekdays. Click on
single days to deselect them, or click the Release All button to deselect all
target weekdays.

30. Under Mode, define the copy mode by selecting the desired option under:

Overwrite complete day(s)


All switchpoints (time-value pairs) of the target days will be deleted and
overwritten with the source day's switchpoints.

Overwrite duplicates
Switchpoints of the target day(s) which are at the same time (duplicates) as the
source switchpoint will be overwritten with the source switchpoint values. New
switchpoints of the source day will be copied to the target days.

Do not overwrite duplicates


Switchpoints of the target day(s) which are at the same time as the source
switchpoint will not be overwritten with the source switchpoint values. New
switchpoints of the source day will be copied to the target days.

31. Click the OK button and click on the Week tab.

Define Switchpoints Graphically 32. On the Week tab, move cursor to the day and time where you want to insert the
switchpoint.

33. Click right mouse button and click on New in the context menu.

RESULT: The Create/Edit Switchpoint dialog box displays.

1153 EN2Z-0937GE51 R0518


BACNET CARE

34. In the From field, enter the start value for the switchpoint.

34. In the upper Value field, enter the start value for the switchpoint.

35. Check the NULL check box if you want to remove the current value at the start
switching time from the priority array (EAGLE Web Interface).

36. By default, the start value will be valid until the consecutive switchpoint as
indicated by the checked next Sw.Point checkbox (displayed in the disabled
To field). If you want to create a switchpoint prior to the next switchpoint,
uncheck the next Sw. Point check box and enter the time into the To field.
Note that the end time can only be set for the same day, at 23.59 p.m. at the
longest. In the lower Value field, enter the value for the switchpoint, which
starts at the time entered in the To field.

37. Check the NULL check box if you want to remove the current value at the end
switching time from the priority array ( EAGLE Web Interface).

38. Click the OK button.

RESULT: The new switchpoint is added to the Week tab.

EN2Z-0937GE51 R0518 1154


CARE BACNET

39. Continue by doing one the following:

• Copy switchpoint(s), (see Copy Switchpoints Graphically section)


• Edit switchpoint (see Edit Switchpoint Graphically section)
• Delete switchpoint (see Delete Switchpoint Graphically section)
• Proceed with the creation of an Exception (see step 40)

Create Exception 40. Click the Exceptions tab.

1155 EN2Z-0937GE51 R0518


BACNET CARE

An exception is a special daily switching program that differs from the weekly
program. Any exception has a higher priority than the weekly program.
Exceptions themselves can be prioritized to define the processing sequence in
case exceptions have overlapping time periods. If the current date enters the
valid period of the exception, the exception overwrites the daily program of that
day. Exceptions can be executed on particular dates, date ranges, as a
recurrent event or on predefined calendar dates.

41. Click the New button.

RESULT: The Create & Edit Exception dialog box displays. On the
Switched Properties tab, the switchpoints that will be switched
by the exception are displayed. The engineering unit/state text
of a selected switched property is shown on the right. To edit
details of a switched property that is selected in the list, click the
Details button.

EN2Z-0937GE51 R0518 1156


CARE BACNET

42. From the Exception Priority drop-down list box, select the priority.
The priority defines the processing sequence in case exceptions have
overlapping validity ranges. Priorities are from 1 (highest) to 16 (lowest).

Switchpoints can be created in a table or graphically. By default, the table


option Show as Table is enabled.

43. To create a new switchpoint in a table, click the New button.

44. Enter the time in the Time cell and press the ENTER key.

45. Enter the value in the Value cell and press the ENTER key.

46. If desired, enter further time-value pairs as described in steps 43-45.

To delete a switchpoint, select the switchpoint in the table and click the Delete
button.

1157 EN2Z-0937GE51 R0518


BACNET CARE

47. To create switchpoints graphically, check the Show as Graphic option.

To create a switchpoint graphically, please refer to the Define Switchpoints per


Switchpoint Blocks and Edit Switchpoints Graphically sections.

48. Click the Valid Period tab.

EN2Z-0937GE51 R0518 1158


CARE BACNET

49. Under Validity Type, select one of the following options by clicking the
corresponding radio button:

Specific Date
Time period is one specific date (day, month, year) is to be defined, e.g.
Christmas Eve or 5.5., the whole of May, or the whole year of 2004 (see step 8
for completion).

Date Range
Time period is a date range is to be defined, e.g. Summer holidays from 29.7-
7.9.2004 (see step 10 for completion).

Recurring Event
Time period is a recurring event is to be defined, e.g. every last Friday of every
month (see step 12 for completion)

Calendar Reference
A project-wide calendar can be selected that provides the specific dates, that
is, the exception will be valid for all calendar entries of the referenced calendar

50. In the Name field, enter a name for the exception.

51. If Specific Date has been selected:

1159 EN2Z-0937GE51 R0518


BACNET CARE

From the Specific Date drop-down list box, select the specific date, e.g.
5.5.2004. If the chosen date should be on a regular basis, for example, every
day, month or year, etc., check the corresponding check box from:

• last day of month (#)


• every day (x)
• odd month (!)
• even month (=)
• every month (*)
• every year (*)

A selected regular option is indicated by a special character as shown above in


brackets (#, x, !=, *) in the selected specific date, for example, 5.*.2004, if the
every month option has been checked. In this case the specific date is valid
on every fifth of every month as indicated by the asterisk.

Combinations of the options are possible.

52. Click the OK button to save specific date.

53. If Date Range has been selected:

Check the checkboxes at Date Range from and Date Range to and select
start and end date from the drop-down list boxes.

NOTE:
If the Date Range from checkbox is unchecked, the drop-down listbox is
disabled. This means, that the date range will be any date up to and including
the end date.

If the checkbox Date Range to is unchecked, the drop-down listbox is


disabled. This means, that the date range will be on any date from the start
date on.

If both drop-down listboxes are disabled, the date range will be all the time.

EN2Z-0937GE51 R0518 1160


CARE BACNET

54. Click the OK button to save the date range.

55. If Recurring Event has been selected:

From the Recurring on drop-down list boxes, select the date options that define
the recurring event.

56. Click the OK button to save the recurring event.

57. If Calendar Reference has been selected:

Under Referenced calendar, select the calendar from the drop-down list box.

RESULT: Under Calendar Entries, the entries of the selected calendar are
shown by name and date.

58. If desired, click Show References button to view existing schedules which
reference to the selected calendar.

59. If desired, create additional entries by clicking the New Entry button.

RESULT: The New & Edit Calendar Entry dialog box displays.

1161 EN2Z-0937GE51 R0518


BACNET CARE

60. Define the time period of the calendar entry (see steps 48-50 for detailed
information).

61. Click the OK button.

62. If desired, continue by creating additional entries.

63. To delete calendar entries on the Valid Period tab, mark the entries in the table
and click the Delete button.

64. To create a new Calendar on the Valid Period tab, click the New button (see
Calendars section for detailed information).

65. To save the Exception, click on the OK button.

RESULT: The Create & Edit Schedule dialog box redisplays. The
Exception is listed by its name and priority. Exceptions can be
copied, edited and deleted.

EN2Z-0937GE51 R0518 1162


CARE BACNET

Edit Schedule

Procedure 1. In the logical plant tree, browse to the plant folder and click on Schedules.

RESULT: On the right pane, the Properties tab shows all schedules of the
plant.

2. Double-click on the schedule in the list or select the schedule in the list and
click the Edit button.

RESULT: The Create & Edit Schedule dialog box displays. To edit the
Schedule, please refer to tab descriptions and steps in the
Create New Schedule section. Further editing steps are
described in the following sections.

1163 EN2Z-0937GE51 R0518


BACNET CARE

Copy Switchpoint(s) Graphically

When copying a switchpoint, only the switchpoint itself defined by its time and value
is copied, not the complete switchpoint block which extends to the next switchpoint.
This means, for copying all switchpoints of a day, the switchpoint block of the last
switchpoint that extends to the next day, must be selected.

Procedures

Copy Single Switchpoint 1. On the week tab, click on the switchpoint.

RESULT: The switchpoint block is marked with a double-lined rectangle.

2. Click right mouse button and with left mouse button, select Copy to, then click
on the destination, day or whole week.

EN2Z-0937GE51 R0518 1164


CARE BACNET

RESULT: The switchpoint is copied to the destination, in this case the


switchpoint at 6.00 is copied to Tuesday. The copied switchpoint
value is valid until the next switchpoint. Existing switchpoints of
that day will be kept (see "Copy all Switchpoints of a Day"
section).

1165 EN2Z-0937GE51 R0518


BACNET CARE

Copy All Switchpoints of a Day

IMPORTANT
When copying all switchpoints of a day, all switchpoints of the target
day(s), to which the switchpoints are copied, will be deleted.

1. On the week tab, click on the first switchpoint of the day.

RESULT: The switchpoint block is marked with a double-lined rectangle.

EN2Z-0937GE51 R0518 1166


CARE BACNET

2. Click right mouse button and with left mouse button, select select, then click on
this day in the context menu.

3. Move cursor over the marked switchpoints, click right mouse button and with
left mouse button select Copy to, then click on the destination, day or whole
week.

1167 EN2Z-0937GE51 R0518


BACNET CARE

RESULT: All switchpoints of the day are copied to the destination are
copied.

EN2Z-0937GE51 R0518 1168


CARE BACNET

Edit Switchpoint Graphically

The time period of a switchpoint block can be reduced or prolonged by moving the
start and end points (start and end time) up or down. In addition, the complete
switchpoint block can be moved up or down so that the start and end time will be
modified by the same time range.

Procedures

Change Start Or End Time 1. On the Week tab, click on the switchpoint.

1169 EN2Z-0937GE51 R0518


BACNET CARE

2. Move cursor over the desired start time respectively end time until a double
arrow displays.

3. Move cursor up or down to the new position.

NOTE: Software allows change steps with the constant time interval of 5
minutes only.

RESULT: The adjacent switchpoint blocks will be moved and changed


accordingly. In this case, the switchpoint block of the switch
point starting at 6.00 has been prolonged from 22.00 to 23.25.
This results in the reduction of the time period of the adjacent
switchpoint block which previously started at 22.00.

EN2Z-0937GE51 R0518 1170


CARE BACNET

Change Start And End Time 1. On the Week tab, click on the switchpoint (block) and, by keeping the mouse
button pressed, move the switchpoint block to the desired position.

NOTE: Software allows change steps with the constant time interval of 5
minutes only.

1171 EN2Z-0937GE51 R0518


BACNET CARE

2. Release the mouse button.

RESULT: The complete switchpoint block has been moved and both, the
start and end time have been changed. The adjacent
switchpoint blocks will be moved and changed accordingly.

Change Switchpoint Value 1. On the Week tab, click on the switchpoint you want to edit.

2. Click right mouse button, and with left mouse button, click on Edit in the
context menu.

Or, double-click on the switchpoint.

RESULT: The New/Edit Switchpoint dialog box displays.

2. In the Value field, enter the new value.

EN2Z-0937GE51 R0518 1172


CARE BACNET

3. If desired, change the start and end time of the switchpoint block in the From
and/or To fields.

4. Click the OK button.

RESULT: The updated value will be displayed on the Week tab.

Delete Switchpoint(s) Graphically


Procedures

Delete Multiple Switchpoints 1. On the Week tab, click on the switchpoint. To select multiple switchpoints, use
the CTRL key simultaneously.

RESULT: The switchpoint blocks are marked with a double-lined


rectangle.

2. Click right mouse button and with left mouse button click on Delete in the
context menu.

RESULT: The switchpoints are deleted.

1173 EN2Z-0937GE51 R0518


BACNET CARE

Delete All Switchpoints


by Keeping Few Switchpoints
1. On the Week tab, multi-select the switchpoints you want to keep by pressing
CTRL key and left mouse button concurrently.

RESULT: The switchpoint blocks are marked with a double-lined


rectangle.

2. Click right mouse button and click Invert in the context menu.

EN2Z-0937GE51 R0518 1174


CARE BACNET

RESULT: All the other switchpoint blocks are now marked with a double-
lined rectangle.

3. Click right mouse button and click Delete in the context menu.

RESULT: The marked switchpoint blocks are deleted. In this case all
switchpoints originally selected on Thursday have been kept.

1175 EN2Z-0937GE51 R0518


BACNET CARE

Delete All Switchpoints 1. On the Week tab, click right mouse button and with left mouse button, select
Select, then click on All in the context menu.

RESULT: All switchpoints are marked with a double-lined rectangle.

2. Click right mouse button and with left mouse button, click on Delete in the
context menu.

EN2Z-0937GE51 R0518 1176


CARE BACNET

RESULT: All switchpoints are deleted.

Join Switchpoints

Multiple consecutive switchpoints which have the same value can be joined to one
switchpoint (block).

Procedure 1. On the Week tab, multi-select the switchpoints you want to join.

1177 EN2Z-0937GE51 R0518


BACNET CARE

2. Click right mouse button and with left mouse button, click on Join in the context
menu.

RESULT: The selected switchpoints will be joined to one switchpoint


(block).

EN2Z-0937GE51 R0518 1178


CARE BACNET

Delete Switchpoint in the Table

Procedure 1. Click on the day's tab.

RESULT: The selected switchpoints are listed with their time and values.

1179 EN2Z-0937GE51 R0518


BACNET CARE

2. Mark the switchpoints you want to delete. Multiple switchpoints can be selected
by simultaneously using the CTRL key. To delete all switchpoints, use the
Select All button.

EN2Z-0937GE51 R0518 1180


CARE BACNET

3. Click the Delete button.

RESULT: The selected switchpoints are deleted.

Copy Exception

Procedure 1. On the Exceptions tab in the Create & Edit Schedule dialog box, select the
Exception in the table. Multiple entries can be selected by using the CTRL key
concurrently.

2. Click the Copy button.

RESULT: The copied exceptions are added to the table.

Edit Exception

Procedure 1. On the Exceptions tab in the Create & Edit Schedule dialog box, select the
Exception in the table.

2. Click the Edit button.

RESULT: The Create & Edit Exception dialog box displays.

1181 EN2Z-0937GE51 R0518


BACNET CARE

For detailed information on editing an exception, please refer to steps 38 et


sqq.

Delete Exception

Procedure 1. On the Exceptions tab in the Create & Edit Schedule dialog box, select the
Exception in the table. Multiple entries can be selected by using the CTRL key
concurrently.

2. Click the Delete button.

RESULT: The selected exceptions are deleted from the table.

EN2Z-0937GE51 R0518 1182


CARE BACNET

Calendars

View Calendars

Procedure 1. In the logical plant tree, click on Calendars.

RESULT: On the right pane, the Properties (Name and Description) of


the calendars are shown.

Calendars can be newly created, edited, copied and deleted. In addition, all
schedules that reference to one particular calendar can be displayed.

Create New Calendar

Procedure 1. On the Properties tab, click the New button.

RESULT: The Create & Edit Calendar dialog box displays.

1183 EN2Z-0937GE51 R0518


BACNET CARE

2. Under Calendar Properties, enter the Name and a Description in the fields of
the same name.

3. Under Access Rights, define the Read Access Level and Write Access Level
by selecting it from the corresponding drop-down list box. For detailed
information on access rights, please refer to the User Access Manager section.

4. Under List of Dates, enter the calendar date entries the calendar should
include by clicking the New button.

RESULT: The New & Edit Calendar Entry dialog box displays.

EN2Z-0937GE51 R0518 1184


CARE BACNET

5. Under Validity Type, select one of the following options by clicking the
corresponding radio button:

Specific Date
Time period is one specific date (day, month, year) is to be defined, e.g.
Christmas Eve or 5.5., the whole of May, or the whole year of 2004 (see step 8
for completion).

Date Range
Time period is a date range is to be defined, e.g. Summer holidays from 29.7-
7.9.2004 (see step 10 for completion).

Recurring Event
Time period is a recurring event is to be defined, e.g. every last Friday of every
month (see step 12 for completion)

6. Under Date, enter a name for the calendar entry.

7. If Specific Date has been selected, select the specific date, e.g. 5.5.2004. from
the Specific Date drop-down list box. If the chosen date should be valid every
day, check the every day checkbox. In this case, the specific date includes
every day of May in 2004 indicated by an asterisk, *.5.2004. If the chosen date
should be valid every month, check the every month checkbox. In this case,
the specific date is on every fifth of every month indicated by an asterisk,
5.*.2004. If the chosen date should be valid every year, check the every year
checkbox. In this case, the fifth of May every year will be the specific date
indicated by an asterisk, 5.5.*. Combinations of the three options are possible,
e.g. assuming the 5.5.2004 sample, the selection of the every day of every
year options determines the valid date to *5*, that is every May of every year.

8. Click the OK button to save the specific date.

1185 EN2Z-0937GE51 R0518


BACNET CARE

9. If Specific Date has been selected:

Check the checkboxes at Date Range from and Date Range to and select
start and end date from the drop-down list boxes.

NOTE:
If the Date Range from checkbox is unchecked, the drop-down listbox is
disabled. This means, that the date range will be any date up to and including
the end date.

If the checkbox Date Range to is unchecked, the drop-down listbox is


disabled. This means, that the date range will be on any date from the start
date on.

If both drop-down listboxes are disabled, the date range will be all the time.

10. Click the OK button to save the date range.

11. If Recurring Event has been selected, select the date options from the
Recurring on drop-down list boxes.

EN2Z-0937GE51 R0518 1186


CARE BACNET

12. Click the OK button to save the recurring event.

RESULT: The Create & Edit Calendar dialog box redisplays.

13. If desired, continue with the creation of further calendar entries.

1187 EN2Z-0937GE51 R0518


BACNET CARE

15. Click the OK button to save settings.

RESULT: The Calendars Properties tab redisplays listing the newly


created calendar.

Edit Calendar

Procedure 1. On the Properties tab, select the calendar to be edited in the list and click the
Edit button.

RESULT: The Create&Edit Calendar dialog box displays.

EN2Z-0937GE51 R0518 1188


CARE BACNET

2. Edit the calendar by doing one of the following:

Under Calendar Properties, change the Name and the Description in the
fields of the same name.

Under Access Rights, redefine the Read Access Level and Write Access
Level by selecting it from the corresponding drop-down list box. For detailed
information on access rights, please refer to the User Access Manager section.

Under List of Dates, add additional calendar date entries by clicking the New
button. Or edit entries by selecting the entry and clicking the Edit button (see
Create New Calendar section). Or, delete a calendar entry by selecting it and
clicking the Delete button. For selection/deselection, the Select all/Unselect
all button, for multiselection, simultaneously clicking the mouse and the CTRL
or SHIFT key can be used.

1189 EN2Z-0937GE51 R0518


BACNET CARE

Copy Calendar

Procedure 1. On the Properties tab, select the calendar to be copied in the list and click the
Copy button.

RESULT: The calendar will be copied. The new calendar name is


indicated by the ∼ symbol and a consecutive number, e.g.
Reception ∼1.

Delete Calendar

Procedure 1. On the Properties tab, select the calendar to be deleted from the list and click
the Delete button.

RESULT: The calendar will be deleted.

Show References

Purpose To view all schedules of any controllers that refer to the selected calendar.

Procedure 1. On the Properties tab, highlight the calendar and click the Show References
button.

RESULT: The Calendar References dialog box displays listing all


controllers with their referencing schedule (object).

EN2Z-0937GE51 R0518 1190


CARE BACNET

2. Click the OK button to close the dialog box.

Copy Calendars

Purpose Copying calendars between different projects.

Procedure 1. Open the source project from which you want to copy the calendars.

2. Click menu item Project, then submenu item Copy Calendars.

RESULT: The Copy Calendars dialog box displays. All calendars of the
source project are displayed in the list. By default, all calendars
are checked for copying in the Copy column.

1191 EN2Z-0937GE51 R0518


BACNET CARE

3. Uncheck the calendars you do not want to copy. Re-check calendars you want
to copy. You can check all calendars by clicking the check icon on the top and
you can uncheck all users by clicking the blank icon on the top.

4. From the Target Project drop-down listbox, select the project to which you want
to copy the calendars.

5. Click the OK button.

RESULT: The Copy Calendars dialog box is closed. The selected


calendars are copied to the target project and can be displayed
and edited on the Calendars Properties tab.

EN2Z-0937GE51 R0518 1192


CARE

LONWORKS ENGINEERING

1193 EN2Z-0937GE51 R0518


CARE

EN2Z-0937GE51 R0518 1194


CARE LONWORKS NETWORK ENGINEERING

LONWORKS NETWORK ENGINEERING


Before engineering a LonWorks network, it is strongly recommended to get familiar
with LonWorks technology by reading the Excel 50/500 LonWorks Mechanisms
Interface Description, form number EN0B-0270 and the relevant Echelon
documentation.

Prerequisites The controller, the plant and the datapoints have been created in the logical
plant tree (see the CARE ENVIRONMENT, BASIC STEPS,
CONTROLLERS DEFINITION AND MANAGEMENT, PLANTS
DEFINITION AND MANAGEMENT and EDITORS chapters).

A LON application running on a LonWorks network is to be engineered in the


network tree in interaction with the logical plant tree. LonWorks network engineering
may include the following tasks:

• Model physical LonWorks structure by defining a channel structure


• Creation of routers
• Configuration of the network components, e.g. transceiver type for LON-
channels, LON network interface, etc., routers
• Logical arrangement of controllers and LON devices
• Editing of the controller network interface by
– Creating and deleting LON objects
– Creating and deleting input and output NVs of standard and
structured type
– Creating and Mapping NVs to datapoints
– Building and assigning value conversion tables

• Assignment of LON devices (Binding)


• Onnet network tuning

Excel 800/500/50 Controller Network Interface

CARE provides all necessary functions to enable a CARE application running on a


LonWorks network. The following sections shortly describe the interaction and
relation between the "datapoint world of CARE" and the "network variables world of
LON".

The network interface provides the information needed for installation and binding.
The network interface is composed of the following key elements:

• Node object
• Generic LonMark objects
• Application specific LonMark objects such as sensor, actuator, or
controller object
• Network variables
• Configuration parameters

CARE provides the network interface by creating the XIF file (External Interface file)
for each controller (device) of the CARE project. The XIF file is automatically
generated along with the application translation.

The “interface” between the CARE application and the network interface is
implemented via mapping functionality between datapoints and NVs. Mapping can
be created manually or automatically within CARE.

1195 EN2Z-0937GE51 R0518


LONWORKS NETWORK ENGINEERING CARE

CARE

Network Interface

Translation
Datapoints MAPPING Network Variables

XIF File

LON Application

Changes on the Controller Network Interface/CARE Application


When using CARE Versions lower 4.00.00 respectively controller OS versions
lower 2.06, changes on the controller network interface should be done as little as
possible, since it affects the bindings. This means as soon as

• NVs are deleted or added


• Objects are deleted or added
• NVs have been moved between objects
• NV types have been changed
• Input NV has been changed into output NV and vice versa
• NV name has been changed
• Changing the mapping of datapoints to NVs
• NV self documentation has been changed
• Flags have been changed
• Value conversion tables have been added or changed

the network interface (XIF file) will be changed.

IMPORTANT
When using OS 2.04 and downloading an application of which network
interface was changed, the bindings will be eliminated and have to be re-
done with a separate LON tool. When using OS 2.06 bindings will be kept
when changing the network interface and therefore no bindings must be re-
done.

NOTE: The program ID will be kept even if the network interface was changed.
Then, the LON device template with the program ID must be deleted in
the LON tool.

The most actions mentioned above are exclusively applicable in the logical LON-bus
part of the network tree. Any changes done in the logical plant tree will not affect the
network interface. Thus, the following actions will not affect the network interface:

EN2Z-0937GE51 R0518 1196


CARE LONWORKS NETWORK ENGINEERING

• Changing datapoint names


• Changing time programs
• Changing the datapoint description
• Adding/Deleting or Editing C-Bus datapoints
• Changing control strategies and switching tables

IMPORTANT
As long as a network interface remains the same, for OS 2.04 LON
applications can be downloaded without elimination of the bindings.

Using a LNS tool additionally If a LON network interface has to be changed – because the LON
application needs to be changed – when using a LNS tool, the following
steps need to be taken:

1. Delete the LON device (controller) in LonMaker®


This means that all bindings will be deleted and gone.
2. Delete the LON template in LonMaker®
Download the changed application into the controller
3. Install a new LON device (controller) in LonMaker ® by getting the
information from the controller or the XIF file.
4. Re-do all bindings!

If a LON device like a controller has been deleted in LonMaker®, then the controller
will restore the LON bindings after 3 minutes automatically, if no new or changed
bindings will be done in LonMaker®.

When using OS 2.06 in CARE the following steps need to be taken in case of
necessary interface changes:

1. Translate the controller


2. Download the controller
3. Commission the controller
4. Synchronize with LNS (only when using additional LNS tools)

Mapping and Binding


Mapping is the process of assigning a LON network variable (NV) to an Excel
50/500/800 datapoint. Mapping allows the use of LonWorks network information in
Excel 800, 500 and 50 datapoints. Mapping has not to be mixed up with Binding.

Binding is defined as the process of interconnecting NVs (devices) on a LonWorks


network. This is a standard functionality provided by LON tools and CARE.

Mapping Binding

LON Controller LON device A LON device B

Datapoint nvi nvo nvi

1197 EN2Z-0937GE51 R0518


LONWORKS NETWORK ENGINEERING CARE

Mapping Types Within CARE the following mapping types are possible:

Mapping Types

Datapoint1
Software points can be of any type (input and output). Hardware points must be of the
nvi1 same type. Input NVs can also be mapped to multiple datapoints (see Many-to-one
mapping).

Software points can be of any type (input and output). Hardware points must be of the
same type. Output NVs can only be mapped to one datapoint.
Datapoint1
nvo1

Allows to map a maximum of one input NV and one output NV to the same software
nvi1
point.
Datapoint1

nvo1

Datapoint1
For input NVs there are 2 different binding types on the LON part:
nvi1 One-To-One (1-1): The value of the input NV corresponds to the value of one bound
Datapoint2
output NV
Many-To-One (n-1): The value of the input NV corresponds to a mathematical function
(recent, min, max, average, sum, or number of devices) of all bound output NVs.

Binding via LON tool Mapping via CARE

LON Devices LON Controller

sensor 1

nvo Datapoint 1 MTO=MIN


tem
p.
detect time: 20 sec =
5 o
C
Datapoint 2 MTO=MAX
sensor 2
temp. = 10 oC
nvo nvi Datapoint 4 MTO=RECENT

detect time: 5 sec.


Datapoint 3 MTO=AVERAGE
oC
8
sensor 3 =1
p.
tem
nvo Datapoint 5 MTO=SUM

detect time: 10 sec.


MTO=NUMBER
Datapoint 6
ACT.DEVICE

MTO: Many-To-One

On the CARE part, an input NV can be mapped to multiple datapoints. For each

EN2Z-0937GE51 R0518 1198


CARE LONWORKS NETWORK ENGINEERING

Mapping Types
mapping one mathematical function out of all possible functions can be applied.
However, for all mappings, the same value conversion table is used.

The available functions are:

None: Default
Recent: Latest updated value of all bound output NVs is used
Min: Minimum value of all bound NVs is used
Max: Maximum value of all bound output NVs is used
Average: Arithmetic average of all bound output NVs is calculated
Sum: The sum of all incoming values is calculated
Number of
active devices: The number of active devices that deliver values via their bindings.

The following point types cannot be mapped:

FF Flex DO_Feedback_DI
FM Flex Multistage
FP Flex Pulse2
GA Global Analog
GD2 Global Digital 2state
GDn Global Digital Nstate
TO Totalizer

Binding Types

Via LON tool the following two types of binding are possible:

nvo nvi
One-To-One (OTO): One nvo is connected to one nvi.

The value of the input NV corresponds to the value of the bound output NV. This is the
Standard binding type.

nvo
Many-To-One (MTO): Multiple output NVs are bound to one input NV and vice
versa.
nvo nvi

This results in the choice to analyze different mathematical calculations of the bound
nvo output NVs for the nvi. The value of the input NV corresponds to the chosen
mathematical function (in, max, average. sum, recent, number of devices) of all bound
output NVs. The results can be transferred to up to many datapoints via point mapping
done in CARE.

Regarding the use of distributed I/O modules and additional LON devices with Excel
800, 500 and Smart controllers on a LonWorks network, the following binding
mechanisms are possible:

Controller Autobinding When using an Excel 800, 500 or Smart controller with its distributed I/O
modules residing on one physical LON-bus, the controller generates the
NVs for the application itself and assigns them to the respective datapoints.
After this, the controller also performs the binding of the NVs automatically
(Autobinding). Mapping and Autobinding are proprietary to Honeywell. Due
to this controller capability, no mapping needs to be done in CARE and no
LON tool for manual binding is necessary.

1199 EN2Z-0937GE51 R0518


LONWORKS NETWORK ENGINEERING CARE

Controller DIO module

Connection 1
Datapoint nvo nvi

Mapping Autobinding
Datapoint nvi nvo
Connection 2

Controller

Manual Binding There are several cases in which it is necessary to manually bind the NVs
of the Distributed I/O modules to their respective controller(s).

Autobinding can be used to bind the NVs of a maximum of 16 Distributed


I/O modules per controller, only. If the application requires more than 16
Distributed I/O modules per controller, you must use CARE to allocate
those additional NVs requiring mapping with data points and bind the NVs
of the additional modules to the controller.

When the NVs of other devices on the LON bus (other than the host Excel
50/500/800 controller) require binding to Distributed I/O modules,
autobinding cannot be used.
A LON tool (e.g. CARE) is required to bind all of the Distributed I/O
modules' NVs.

Controller DIO module


LON Device 1 LON Device 2

Connection 1
Datapoint nvo nvi

Mapping Manual Binding


Datapoint nvi nvo
Connection 2

CARE

CARE Autobinding In an Open LON configuration, CARE provides the integration of additional
Honeywell LON devices other than DIO modules such as the M7410G
actuator with LON capabilities and/or 3rd party LON devices. In this case,
the DIO modules are not assigned to the controller by autobinding. Instead,
all datapoints are boardless as a rule and each DIO module must be
assigned to the controller by connecting datapoints of the controller to NVs
of the LON device (CARE Autobinding). CARE creates the mapped NVs for
the datapoints automatically during the Binding procedure. In addition,
matching LON devices can be bound to each other by interconnecting their
corresponding NVs.

EN2Z-0937GE51 R0518 1200


CARE LONWORKS NETWORK ENGINEERING

Controller DIO module


LON Device 1 LON Device 2

Connection 1
Datapoint nvo nvi

Mapping Autobinding
Datapoint nvi nvo
Connection 2

CARE

Design and Configure Network


Purpose To structure the C-bus and LonWorks network according to conditions in
the building.
This includes:
• Set global settings (Default LON Properties).
• Creation of a skeletal structure consisting of Default and subsystems
• Physical and logical arrangement of controllers and LON devices in
these systems
• Configuration of the network components, e.g. transceiver type for LON-
channels, LON network interface, etc.

For information on the BACnet-Bus network structure, please refer to the "BACnet
Network Structure"section.

Set Default LON Properties


To set default LON properties, please refer to the “Set Global CARE
Options” section.

Change Service Type for BACnet Datapoints


Applies to analog, binary and multi-state output point types of the Excel Web
controller.

In order to make sure that the Reliability property for the present value works
properly, the service type of the point must be set to Acknowledged (Ackd). With
acknowledged service, controller - I/O module disconnections are indicated by the
relevant reliability ´No Sensor` or ´No Output`.

NOTE: If a large number of outputs (e.g. all outputs of mutiple I/O modules) are
set to acknowledged servcice, the performance on the LON bus may
drastically decrease.

Procedure 1. Expand the LON-bus part of the network tree and navigate to the output
point in the plant.

1201 EN2Z-0937GE51 R0518


LONWORKS NETWORK ENGINEERING CARE

2. Click on the connection.

3. On the Properties tab on the right, uncheck Auto at Service type and select
Ackd from the drop-down listbox.

The Default Network Structure


NOTE: For information on the BACnet-Bus network structure, please refer to the
"BACnet Network Structure" section.

By default, the network tree shows the two basic bus types, Bus and LON-
Works.

Each bus is sub-divided by default to allow an arrangement of the network


components according to the physical conditions in the building.

EN2Z-0937GE51 R0518 1202


CARE LONWORKS NETWORK ENGINEERING

The Bus folder contains the Bus 1 subfolder by default. Further created subfolders
will be numbered continuously. The subfolders represent the physical C-Bus
network structure of the project and contain the C-bus controllers, which control that
segment of the building.

NOTE: The subfolder names are examples and freely editable. For example, the
default Bus 1 subfolder can be named into Area1 or Block A.

The LON-Works folder represents the network interface of the LON-Bus and is
subdivided by default into a physical part, called Channels and a logical part, called
Default System.

The Channels folder contains the Channel_1 subfolder by default. Additional


channels can be created and their names are freely editable.

A channel arranged in the Channels folder, represents the physical medium, for
example twisted-pair cable, and lists all LON devices attached to this cable.
Controllers can be shifted between channels to model the physical conditions in the
building.

The Default System as the top-level system of the logical LON-Bus part provides all
software functions necessary to work on LON devices, LON objects, NVs etc. It
might contain the following components:

1203 EN2Z-0937GE51 R0518


LONWORKS NETWORK ENGINEERING CARE

• Subsystems (to be created below the Default System)


• LON devices
• LON objects
• NVs (network variables)
• SCPTs (standard configuration property types)

NOTE: The Default System and subsystems can have further subsystems.
Names as "Default System" and "Subsystem" are examples and freely
editable.

Create C-Bus Subsystems


NOTE: For information on the BACnet-Bus network structure, please refer to the
"BACnet Network Structure" section.

Procedure 1. With left mouse key, select the physical Bus folder in the network tree.

2. Click right mouse key and with left mouse key, click Create Bus in the context
menu.

RESULT: The new subsystem folder will be added below the Bus
folder, in this case called Bus 2. On the Properties tab on
the right pane, the following properties can be defined:

EN2Z-0937GE51 R0518 1204


CARE LONWORKS NETWORK ENGINEERING

(Sub)System Name
Edit the name, if desired.

C-Bus, C-bus baud rate


If the controllers communicate via physical C-Bus, click the C-Bus radio button
and select the C-bus baud rate from the drop-down listbox.

LON-Bus, Bus ID
If the controllers communicate via Building Management Functionality over LON
(explicit messaging), click the LON-Bus radio button and select a bus ID from
the drop-down listbox. The C-Bus architecture allows max. 30 controllers per
physical C-Bus. Hence, a subsystem can include 30 controllers at maximum.
For the 31th C-Bus controller a new subsystem must be created.

Remote Host Name


In case you want to download an application remotely, enter the host name or
the IP address.

Remote Bus ID
For remote application download, enter the Cbus ID.
To view the Cbus ID, open the Windows Control Panel and double-click the
CBUS icon on the remote PC (see "Download Application Remotely"
section)

3. To position controllers in Bus subsystems, please refer to the Create and Place
Controller in the Network tree section.

Create Channel
Procedure 1. With left mouse key, click on the Channels folder.

2. Click right mouse key and with left mouse key, click Create Channel in the
context menu.

RESULT: The new folder will be added to the Channels folder.

1205 EN2Z-0937GE51 R0518


LONWORKS NETWORK ENGINEERING CARE

3. On the Properties tab on the right pane, edit the name in the Channel Name
field and select the transceiver from the Transceiver Type drop-down listbox.

4. To position controllers in channels, please refer to the Create and Place


Controller in the Network tree section.

Connect Channels via Router


IMPORTANT
If two channels are used, they must be connected via router.

Procedure 1. With left mouse key, click on the channel you want to connect via
router, respectively on the Default System or a subsystem folder.

2. Click right mouse key and with left mouse key, click Create Router in the
context menu.

RESULT: The New Router dialog box displays.

EN2Z-0937GE51 R0518 1206


CARE LONWORKS NETWORK ENGINEERING

3. Enter the name in the Router Name field and select the Near Side and the Far
Side for the router in the corresponding Channel drop-down listboxes.

RESULT: The router is assigned to the Default System, respectively


subsystem folder and it appears in each channel.

4. In the network tree, click on the router to display router properties on the right
pane.

1207 EN2Z-0937GE51 R0518


LONWORKS NETWORK ENGINEERING CARE

5. On the Properties tab, enter description and values for Node Selfdoc String,
Ping Interval, Individual Program ID, Location String in ASCII code and the
neuron Ids for the Near Side and the Far Side. For detailed descriptions on the
items, please refer to relevant Echelon documentation.

Set Default Channel

Purpose To define the default channel where a created controller will be inserted and
where a device will be inserted out of the device library when dragging it on
the Terminal Assignment tab. The presetting for the channel is
“Channel_01”. Note that only one single channel can be the default
channel. The default channel can also be used as network interface
channel (see Set Network Interface Channel section).

Procedure 1. In the LON-bus part of the network tree, right-click on the Channel and
click on Default channel in the context menu.

Das verknüpfte Bild kann nicht angezeigt werden. Möglicherweise wurde die Datei verschoben, umbenannt oder gelöscht. Stellen Sie sicher, dass die Verknüpfung auf die korr

RESULT: The defined default channel gets a red checkmark . Next


time, when creating a controller or dragging a LON device
onto the Terminal Assignment tab, it will be inserted into the
defined default channel.

EN2Z-0937GE51 R0518 1208


CARE LONWORKS NETWORK ENGINEERING

Set Network Interface Channel

IMPORTANT
This function is of high importance when using multiple channels, which are
connected via routers. Make sure to connect physically to that channel
which has been set as the network interface channel in CARE.

Purpose To define the channel via which the CARE PC should connect to the
LonWorks network. Note that only one single channel can be the interface
channel. The network interface channel can also be used as default
channel (see Set Default Channel section).

Procedure 1. In the LON-bus part of the network tree, right-click on the Channel and
click on NI Channel in the context menu.

RESULT: The selected channel gets green and is now the interface
channel via which CARE connects to the LonWorks network
when going Onnet.

Create LON-Bus Subsystems


Purpose To arrange the network components according to the physical conditions in
the building.

Procedure 1. With left mouse key, select the Default System folder or an existing
subsystem folder where you want to create another subsystem for.

2. Click right mouse key and with left mouse key, click Create Subsystem in the
context menu.

RESULT: The new subsystem folder will be added to the logical


LON-Bus part of the network tree.

3. On the Properties tab on the right pane, edit the name in the (Sub)System
Name field, if desired, and click on the created subsystem folder in the logical
LON-Bus network tree.

RESULT: The newly named subsystem folder displays.

1209 EN2Z-0937GE51 R0518


LONWORKS NETWORK ENGINEERING CARE

NOTE: Top-level systems as the Default System and subsystems can have
further subsystems.

4. If desired, continue creating further subsystems on the same or lower level by


repeating step 1 ff. with the appropriate selected folder you want to create the
subsystem for.

Create and Place Controller in the Network tree


When creating a controller, the C-Bus subsystem and the LON-Bus
subsystem, where the controller should be placed, can be pre-defined.

Set C-Bus Default

Purpose To define the C-Bus where a created controller should be inserted by


default. The presetting for the default system is “Bus 1”.

Procedure 1. When creating the new controller by menu item Controller and
submenu item New, select the default Bus system in the Bus name
drop-down listbox.

NOTE: After creation of the controller, it can also be moved between different
subsystems by Drag&Drop.

Set LON-bus Default System

Purpose To define the LON-bus system where a created controller should be


inserted by default. The presetting for the default system is “Default
System”.
Procedure 1. In the LON-bus part of the network tree, right-click on the subsystem
folder, in this case Block A, and click on Set as Default System in the
context menu.

EN2Z-0937GE51 R0518 1210


CARE LONWORKS NETWORK ENGINEERING

RESULT: When creating a controller next time, it will be inserted


into the folder, defined as default system. The LON-bus
default system is indicated by a checkmark.

NOTE: After creation of the controller, it can also be moved between different
subsystems by Drag&Drop.

Move Controllers in the Network Tree by Drag&Drop


IMPORTANT
Do not move controllers, which are already bound to other devices. First,
move the controller and then do the binding.
When moving controllers between different channels, the channels must be
connected via routers.

In the C-Bus part of the network tree, controllers can be moved between different
subsystem folders.

In the logical LON-Bus part of the network tree, controller devices can be moved
between the top-level system and/or subsystem folders.

Procedure 1. In the source folder, select controller (controller device), drag it to the
desired target folder and drop it.

Move
CONT2 to
the Bus 2

Example 1: Move C-Bus Controller between Bus Subsystems

Configure Channel

Purpose Configuration of the physical part(s) of the LON-Bus includes the naming,
description (optional) and the definition of the transceiver type.

Procedure Refer to the Create Channel section.

Configure LON-Bus
Purpose Configuring the LON-Bus includes the definition of the:

• network interface type

1211 EN2Z-0937GE51 R0518


LONWORKS NETWORK ENGINEERING CARE

• domain settings
• LNS settings
• EBI settings.

Procedure 1. In the network tree, click on the LON-Works folder.

2. On the Properties tab on the right pane, select the network interface from the
Network Interface drop-down list box.

3. In the Id Size field, set the Id size in bytes format and enter the domain Id into
the ID field. If you want to get a randomly generated domain ID, click the
Generate Domain ID randomly button. In this case the Id Size previously
selected must be higher than 0.

4. Check the LNS Controlled checkbox if you want to enable the LNS Controlled
mode which allows the incremental updating of the LNS database with changed
information done in CARE. For detailed information on this topic and on the
Extended LNS Options button, please refer to the "CARE and LNS" section.

5. Check the CARE Controlled Flow Parameters for Honeywell VAV2 Devices
checkbox if want to update the LNS database with the current CARE values of
the flow parameters ´duct area`, ´flow setpoint minimum` and ´flow setpoint
maximum`.

6. In the NV Poll Interval, enter the interval in seconds in which all NVs will be
polled by the EBI LON point server. For each NV, the poll interval can also be
set individually (see "EBI Settings" section).

Configure Lon Interface


CARE supports LON IP Interfaces for the use of IP852 and LonSock Remote
Server. Both IP852 and LonSock Remote Server are based on LonSock2 which is
the basis for CARE, COACH and ARENA software. CARE allows the administration
of LON IP Interfaces by new creation, selection and deletion.

IP852

EN2Z-0937GE51 R0518 1212


CARE LONWORKS NETWORK ENGINEERING

Allows the direct and remote diagnostic of networks based on IP852 standard.
Ideally a router is used as network interface and the mandatory configuration server
(CS) service is running in the router.

LonSock Remote Server


Allows remote access to PCs and the Excel Web controller with a shared network
interface on which the RNI server is running.

Procedure 1. Click menu item Lon, then submenu item Lon Interface
Configuration, or click in the configuration toolbar.

RESULT: The Lon Interface Configuration dialog box is displayed.

2. To create a new interface, click on desired type, IP-852 or Lon Sock Remote
Server in the tree.

3. Click the New button,

RESULT: If an IP852 interface is selected, the properties as


described in step 4 et seq. are displayed on the right pane
for entering the appropriate information.

If a LonSock Remote Server interface is selected, the


properties as described in step 8 et seq. are displayed on
the right pane for entering the appropriate information.

4. Enter an Interface Name.

5. Enter the Configuration Server Address and Port number (if necessary).

6. Select the Local IP Address and enter the Port number (if necessary).

7. Click Apply button, then click Exit button.

8. Enter an Interface Name.

9. Enter the LonSock Remote Host Address and Port number (if necessary).

10. Select the Remote Host Address Interface. This interface must be available on
the Host PC and the RNI server must be running (shared network interface).

11. Click Apply button, then click Exit button.

Reset Second Domain


Purpose To set the second domain to zero for controllers that use two domains such
as:

• Excel Web
• Excel 50/500/800 Smart (CentraLine CARE only)

For successful remote commissioning of Excel Web projects created with


CARE versions lower than 8.03.00, you must reset the second domain to
zero before starting the commissioning.

Procedure 1. Right-click the LonWorks folder in the network tree, and then click
Reset Second Domain in the context menu.

RESULT: The second domain is set to zero.

Network Topologies for Excel 800, 500 and Smart Controllers

1213 EN2Z-0937GE51 R0518


LONWORKS NETWORK ENGINEERING CARE

Regarding the use of distributed I/O modules and additional LON devices with Excel
800, 500 and Smart controllers on a LonWorks network, several topologies
dependent on the used OS are possible:

Local OS 2.0/2.01 - 2.04


A "Local" topology allows the attachment of just one Excel 500 or Smart controller to
its (max. 16 ) DIO modules on a single LonWorks network. No other devices co-exist
on that bus. The DIO modules are assigned to their host Excel 500 or Smart
controller automatically, and autobinding is performed. Both, the XFL52x and
XFL52xB module types can be used.

NOTE: For OS 2.0/2.1 and OS 2.03, the topology of the LonWorks network is
always “Local” although it cannot be selected explicitly when creating a
new controller.

Local Topology (OS 2.0/2.01 to 2.04)

C-Bus

IP Modules IP Modules IP Modules

Controller A Controller B Controller C

LonWorks

DIO Modules
(XLF52x and XFL52xB types)

Shared OS 2.04
A "Shared" topology allows the attachment of multiple Excel 500 and Smart
controllers to their DIO modules on a single LonWorks network. But,
multiple controllers cannot process datapoints on the same DIO module.
The Shared topology does not allow the integration of additional 3rd party or
other Honeywell LON devices. Autobinding may still be used for the NVs of
a maximum of 16 Distributed I/O modules assigned exclusively to the host
Excel 500 or Smart controller.

NOTE: It is recommended that you use CARE for assigning the DIO modules to
their dedicated Excel 500 or Smart controller by entering the DIO
modules' Neuron IDs. The alternative is to assign them using the MMI.
Only the XFL52xB module types can be used.

EN2Z-0937GE51 R0518 1214


CARE LONWORKS NETWORK ENGINEERING

Shared Topology (OS 2.04)

C-Bus

IP Modules IP Modules IP Modules

Controller A Controller B Controller C

LonWorks

N-ID:166322318989 N-ID:164323189899
N-ID:266349189890 N-ID:133323189889

Assigned to
N-ID:111349189890 Controller A
N-ID:977322318989 N-ID:778693189890
N-ID:812422318989

Assigned to
N-ID:333422318989 Controller A
N-ID:288822318989 N-ID:812853189890
Assigned to
Assigned to Assigned to
Controller A
Controller B Controller C

DIO Modules
(only XFL52xB types)

Open LON OS 2.04


When using OS 2.04, an "Open LON" topology refers to an interoperable
LONW ORKS system in which CARE will be used to generate a LONMARK-
compliant network interface file capable of providing NVs which can be
bound to other devices (which may include other Excel 500 controllers with
their own DIO modules, Excel 50 or Excel 10 controllers, or third-party
devices). The NVs of the DIO modules exceeding 16 must be bound
manually using a LON tool (an LNS-based tool capable of using Honeywell
plug-ins is recommended). For OS 2.04, the "Open LON" operating mode is
combined with the "Shared" operating mode to allow multiple controllers
with DIO modules and further Open LON devices on a single LonWorks bus
(see next section).

Shared/Open LON OS 2.04


When using OS 2.04, the "Shared" and the "Open" operating modes can be
in effect simultaneously for the integration of additional 3rd party or other
Honeywell LON devices. In this case, autobinding is performed for the NVs
of a maximum of 16 DIO modules, while the data points of additional DIO
modules must be manually mapped with shared NVs and the NVs of the
additional DIO modules must be bound manually using an LNS-based tool
(Manual Binding).

NOTE: To avoid using a separate software tool for the Binding procedure, it is
recommended to integrate Open LON devices by using OS 2.06, since
CARE can be used for creating the bindings (CARE Autobinding).

1215 EN2Z-0937GE51 R0518


LONWORKS NETWORK ENGINEERING CARE

Shared/Open LON Topology (OS 2.04)

C-Bus

IP Modules IP Modules IP Modules

Controller A Controller B Controller C


Binding of DIOs across
router possible via Open LON

LonWorks
Router

N-ID:266349189890 N-ID:166322318989 N-ID:164323189899


Assigned to
Controller A
N-ID:111349189890
N-ID:812422318989 N-ID:977322318989 N-ID:778693189890

N-ID:661322318989 N-ID:1267722318989 Assigned to


Controller A
N-ID:333422318989 Bound to
N-ID:288822318989 N-ID:812853189890
Assigned to Controller C
Controller A Assigned to Assigned to
N-ID:5567722318989
Controller B Controller C
Bound to
Controller A

DIO Module
N-ID:266349189890

3rd Party LON Device


N-ID:566322318989

Open LON OS 2.06/3.0


When using OS 2.06 or 3.0, an "Open LON" topology allows an interoperable
LONW ORKS system in which CARE will be used to generate a LONMARK-compliant
network interface file for each device, capable of providing NVs which can be bound
to other devices. These devices may include Excel 800, 500 controllers with their
DIO modules or Smart I/O modules, Excel 50 or Excel 10 controllers, and additional
3rd party or other Honeywell LON devices such as the Honeywell actuator with LON
capabilities. Multiple controllers can process one and the same datapoint/NV on a
DIO, Smart I/O module or any other LON device.

The bindings will be done in CARE (CARE Autobinding). For the integration
of Honeywell or 3rd party LON devices no separate binding tool such as
LonMaker is necessary. The DIO modules will be handled as any other
LON device, that is, they must be bound to the controller. Controller
Autobinding no longer takes place.

NOTES: For OS 2.06 and 3.0 the DIO modules must be assigned to their Excel
500/800 controller by entering the Neuron ID in CARE. A later
assignment via MMI is not possible.

EN2Z-0937GE51 R0518 1216


CARE LONWORKS NETWORK ENGINEERING

Open LON Topology (OS 2.06 / 3.0)

C-Bus

IP / Panel Modules IP / Panel Modules IP / Panel Modules

Controller A Controller B Controller C


Binding of DIOs across router possible

LonWorks
Router

N-ID:266349189890 N-ID:166322318989 N-ID:164323189899


Assigned to
Controller C
N-ID:111349189890
N-ID:812422318989 N-ID:977322318989 N-ID:778693189890

N-ID:661322318989 N-ID:1267722318989 Assigned to


Controller A
N-ID:333422318989 Bound to
N-ID:288822318989 N-ID:812853189890
Assigned to Controller A and C
Controller A and B Assigned to Assigned to
N-ID:5567722318989
Controller B Controller B and C
Bound to
Controller A

DIO Module (only XFL52xB types)


N-ID:266349189890

Smart IO Module
N-ID:266349189890

3rd Party LON Device


N-ID:566322318989

Excel 500/Smart Controller with DIO Modules on Local Topology

NOTE: Applies to OS 2.0/2.02 - 2.04.

Binding When using an Excel 500 or Smart controller with its distributed I/O
modules in Local topology, the controller performs the Mapping and
Autobinding.
Due to this controller capability, no mapping needs to be done in CARE and
no separate LON tool for binding is necessary.

Physical Assignment For proper physical assignment of the DIO modules to the single controller,
the module address in CARE must match the hex switch setting.

NOTE: NVs generated by the controller cannot be edited within CARE and are
not visible in any LON tool.

1217 EN2Z-0937GE51 R0518


LONWORKS NETWORK ENGINEERING CARE

Excel 500/Smart Controllers with DIO Modules on Shared/Open LON Topology (OS 2.04)

NOTE: Applies to OS 2.04.

Binding As in Local topology, the controllers perform Autobinding. To physically


assign the corresponding DIO modules to their dedicated controllers, the
following steps have to be done:

Physical Assignment
• Enter Module address according to hex switch setting.
• Enter Neuron ID in TAF (optional). The Neuron ID can also be selected
via
XI 581/2 later.

Excel 500, 50, 10, Smart Controllers with DIO Modules and other Honeywell / 3rd party LON devices on Shared/Open
LON Topology (OS 2.04)

NOTE: Applies to OS 2.04.

Binding To integrate additional LON devices other than distributed I/O modules, the
following steps have to be done:

1. In CARE, create LON network interface that fits to the desired


Honeywell LON device and 3rd party LON device, respectively, by
mapping CARE datapoints to NVs.

2. With a LON tool, e.g. CARE, bind the mapped NVs to the
corresponding NVs of the Honeywell and 3rd party LON device,
respectively (Manual Binding)

IMPORTANT
When using OS 2.04, the Integration of additional LON devices is only
possible in the Shared/Open LON topology.

Excel 800, 500, 50, 10, Smart Controllers with DIO Modules and other Honeywell / 3rd party LON devices on
Shared/Open LON Topology (2.06/3.0)

NOTE: This applies to OS 2.06 and 3.0 only.

Logical Assignment If the system is set to the Open LON topology, CARE 7.03.00 provides the
integration of additional Honeywell LON devices other than DIO modules
such as the M7410G actuator with LON capabilities and/or 3rd party LON
devices. When using Open LON, the DIO modules will be handled as any
other LON device. They must be imported from a device library. That is,
when using OS 2.06 or 3.0, the DIO modules are not assigned to the
controller by controller autobinding. Instead, all datapoints are boardless as
a rule and each DIO module must be assigned to the controller by
connecting datapoints of the controller to NVs of the LON device (CARE
Autobinding). CARE creates the mapped NVs for the datapoints
automatically. In addition, matching LON devices can be bound to each
other by interconnecting their corresponding NVs.

To bind a LON device to an appropriate Excel controller (Excel 800, 500,


50, 10, Smart) or to another LON device, the following steps have to be
done on the Terminal Assignment tab:

1. Import the LON device from the device library.

2. Enter the neuron ID (later assignment via MMI not possible).

3. Depending on the LON device (1) (Excel controller, e.g. DIO module,
3rd party LON device), which the imported LON device should be

EN2Z-0937GE51 R0518 1218


CARE LONWORKS NETWORK ENGINEERING

connected to, connect the controller datapoints, respectively the NVs


of the other LON device (1) with the matching NVs of the imported
LON device (2).

Excel 50 on Shared/Open LON Topology

NOTE: Applies to OS 2.04.

The Excel 50 freely programmable controller can be used only in Shared/Open LON
Topology. CARE sets this automatically.

Which Target I/O Hardware do you prefer first?

From the CARE point of view, the following table shows the possible
Controller - OS – Target I/O hardware combinations for Excel 800, 500 and
50 controllers with LON capabilities:

Controller
OS Possible Target I/O Excel 800 Excel 500 Excel Excel 50
Smart
IP (XF5..) - x - x
2.0/2.01, Distributed I/O (XFL5..) - x x -
2.03
Open LON * - - - -

IP (XF5..) - x - x
2.04 Distributed I/O (XFL5..) - x x -
Open LON * - x x x
2.06 IP (XF5..) - x - x
Distributed I/O (XFL5..) - x - -
Open LON * - x x x
3.0 Panel I/O (XF8..) x - - -
Distributed I/O (XFL8..) x - - -
Open LON * x - - -
* no physical hardware

As the table shows, the respective controllers can work with a unique hardware
configuration of just the same module type or, depending on controller type, with up
to three different target hardware types:

• IP modules (Standard) of type XF5.. or Panel I/O modules of type XF8..


• Distributed I/O (DIO) modules of type XFL5.. or XFL8..
• Open LON (boardless points)

CARE Process Regarding the hardware configuration, the following basic steps in CARE
have a decisive influence:

Define controller
Includes the definition of the system architecture in principle, Shared / Open LON or
Local.

Define plant
Includes the definition of the preferred target I/O hardware configuration for the
plant, IP/Panel I/O, Distributed I/O or Open LON (see IMPORTANT hint).

Attach plant to controller


When attaching the plant(s) to the controller, CARE assigns the hardware points to
the corresponding modules as defined for the plant(s) by the target I/O hardware

1219 EN2Z-0937GE51 R0518


LONWORKS NETWORK ENGINEERING CARE

selection (Preferred Target Hardware in New Plant dialog box). This results in a
unique hardware configuration if all plants have the same target I/Os or in a mixed
hardware configuration if the plants have different target I/Os.

NOTE: The preferred target I/O hardware configuration selected first can be
changed afterwards at any time, either for the plants separately (Plant
Properties tab) or in a single step for the complete controller, which
affects all plants (Modify Target I/O Hardware on the Controller Properties
tab).

IMPORTANT
Note, that setting the preferred target I/O hardware means just a pre-
definition of the target hardware. The final configuration needs to be done
on the Terminal Assignment Tab.

The following table summarizes the selection of the target I/O hardware and the
corresponding assignment on the Terminal Assignment tab.

OS Physical Target I/O Preferred Target I/O Assignment in TAF


Modify Target I/O Hardware
2.0/201, 2.03 IP (XF5..) Standard I/O (IP) All Points are assigned to IP
modules
Distributed I/O (XFL5..) Distributed I/O All Points are assigned to
distributed I/O modules
2.04 IP (XF5..) Standard I/O (IP) All Points are assigned to IP
modules
Distributed I/O (XFL5..) Distributed I/O All Points are assigned to
distributed I/O modules
2.06 IP (XF5..) Standard I/O (IP) All Points are assigned to IP
modules
Distributed I/O (XFL5..) Open LON All* Points are boardless and
must be bound manually to
distributed I/O modules
3rd party LON devices Open LON All* Points are boardless and
and/or other Honeywell must be bound manually to
LON devices NVs of the appropriate LON
device
3.0 Panel I/O (XF8..) Panel I/O All Points are assigned to
Panel I/O modules
Distributed I/O (XFL8..) Distributed I/O All Points are assigned to
distributed I/O modules
3rd party LON devices Open LON All* Points are boardless and
and/or other Honeywell must be bound manually to
LON devices NVs of the appropriate LON
device

Restrictions* Point types which are not supported by Open LON will be assigned to
distributed I/O or Standard I/O modules.

Point types not supported by Open LON:

DO Pulsed Digital Output


FF Flex DO_Feedback_DI
FM Flex Multistage
FP Flex Pulse2
GA Global Analog
GD2 Global Digital 2state
GDn Global Digital Nstate
PT Pseudo Totalizer
TO Totalizer

EN2Z-0937GE51 R0518 1220


CARE LONWORKS NETWORK ENGINEERING

Mapping Scenarios for OS 2.04

Assumption To create a LonWorks network interface for integration of additional LON


devices, the following will be assumed:

• OS 2.04 or higher had been selected


• LON topology was set to Shared/Open LON

Then, NVs can be mapped to:

• Physical hardware points (standard I/O or Distributed I/O)


• Boardless datapoints (Open LON)
• Software points

Using Standard I/O If a datapoint had been mapped to an NV and standard I/O hardware has
been selected as target I/O hardware, this datapoint will have a double
assignment, to
the IP-bus connection via hardware module and to the LonWorks network
connection via NV. For value processing of these kinds of mapped
datapoints, please refer to the Data Priority of NVs and Datapoints section.

Using Distributed I/O If a datapoint had been mapped to an NV and distributed I/O hardware has
been selected as target I/O hardware, this datapoint will have a double
assignment, to
the LonWorks network connection via hardware module and to the
LonWorks network connection via NV. For value processing of these kinds
of mapped datapoints, please refer to the Data Priority of NVs and
Datapoints section.

Using Open LON For integration of additional LON devices, Open LON is recommended as
preferred target hardware. This results in creation of boardless points (see
restrictions), which do not belong to any board.

Boardless points will have the same behavior as normal hardware points, e.g.
Alarming etc.

For value processing of mapped datapoints, please refer to the Data Priority
of NVs and Datapoints section.

Software Points Software points can also be mapped to datapoints, but these points are not
visible on the Terminal Assignment tab.

Manual Mapping of On a Shared/Open LON architecture, distributed I/O modules can be bound
Distributed I/O Modules to the Excel 500 or Smart controller like any other LON devices.

IMPORTANT
NVs generated by CARE take precedence over NVs generated by the
controller during Autobinding. That is, if DIO modules are bound to the
controller via Manual Mapping and Binding, Autobinding does not take
place.

Routers and Repeaters Use

Autobinding will be performed in the Local as well as in the Shared/Open LON


architecture. For both topologies, routers restrict autobinding, since DIO modules
have to reside within the same router segment as its dedicated controller.

In contrast to routers, autobinding across repeaters is possible.

Routers can be used in a Shared / Open LON topology, if distributed I/Os


were manually mapped in CARE and manually bound via LON tool.

Define/Modify Target I/O Hardware Configuration

1221 EN2Z-0937GE51 R0518


LONWORKS NETWORK ENGINEERING CARE

Purpose Define/Modify I/O hardware module type for Excel 500, Smart and Excel 50
controllers. For the Excel 500 controller, target I/O hardware can be
changed for OS Versions 2.0 and higher. For the Excel 800 controller,
target I/O hardware can be changed for OS Versions 3.0 and higher. For
the Excel 50 and Excel Smart controllers, hardware can be changed only, if
OS 2.04 or higher is applied. The target I/O hardware configuration can be
changed according to the following table.

Module Type Excel 500/800 Excel Smart Excel 50


IP I/O / Panel I/O** x - x
DIO x x -
Open LON* x x x
(boardless)
* no physical hardware.
** Panel I/O modules are not applicable to Excel Smart and Excel 50 controllers.

The table shows that for Excel 800/500, the target hardware can be changed from
any type to any type, whereas for Excel Smart, only a change from DIO modules to
Open LON and vice versa, and for Excel 50 a change from IP I/Os to Open LON
and vice versa is possible.

This provides the creation of unique as well as mixed hardware configurations for
the controllers. Creating a unique hardware configuration means that all plants
will be assigned to the same I/O module type, IP/Panel I/O, Distributed I/O, or Open
LON. Creating a mixed hardware configuration means that IP/Panel I/O modules,
Distributed I/O modules, and/or boardless points will reside on the same controller.

NOTE: The preferred target I/O hardware configuration selected first can be
changed afterwards at any time, either for the plants separately (Plant
Properties tab) or in a single step for the complete controller, which
affects all plants (Modify Target I/O Hardware on Controller Properties
tab).

IMPORTANT
Note that setting the preferred target I/O hardware means just a pre-
definition of the target hardware. The final configuration need to be done on
the Terminal Assignment tab.

Restrictions Certain point types are not supported by Open LON. When using OS 2.04,
non-supported types will be put on IP (Excel 500, 50) or distributed I/O
modules (Excel 500, Smart), even if Open LON was selected. When using
OS 2.06 or 3.0, non-supported types will be indicated in red in the logical
plant tree and must be put manually on IP boards or panel I/O boards.

Point types not supported by Open LON:

DO Pulsed Digital Output


FF Flex DO_Feedback_DI
FM Flex Multistage
FP Flex Pulse2
GA Global Analog
GD2 Global Digital 2state
GDn Global Digital Nstate
PT Pseudo Totalizer
TO Totalizer

When Distributed I/O was selected for an Excel 500/800 controller and the
application contains a point type, which is not supported by distributed I/O modules,
these points will be put on standard/panel I/O modules.

IMPORTANT
When an Excel 500/800 controller is full, that is, the maximum number of
modules has been reached, a change in the plant target I/O hardware will
not be able to create any different module type. Therefore the actual
hardware will not change, even if the setting for the plant is changed on the
Plant Properties tab. In this case you have to do manual changes via the

EN2Z-0937GE51 R0518 1222


CARE LONWORKS NETWORK ENGINEERING

terminal assignment or set the Controller to the other target I/O hardware
that will affect all plants.

Attachment When attaching a plant, CARE assigns all hardware points of the plant to
the target I/O hardware that is selected for the plant. The target hardware
can be changed for attached as well as for unattached plants.

Define Unique Target I/O Hardware Configuration

Purpose Define unique target I/O hardware modules (Standard I/O / Panel I/O or
Distributed I/O, or Open LON) for Excel 500/800, Smart, or 50 controllers.
Procedures This can to be done by selecting the same target hardware (Standard I/O /
Panel I/O or Distributed I/O, or Open LON) for any plants when defining the
plants.

or

by setting the target hardware for a controller to Standard I/O / Panel I/O or
Distributed I/O, or Open LON. In this case, the controller has plants with each of two
or three module types already attached (see Modify Target I/O Hardware for a
Complete Controller section). This affects all plants attached to the controller.

Define Plants with Unique Target I/Os1. In the logical plant tree, click on the controller.

2. Click menu item Plant, then drop-down item New.

RESULT: The New Plant dialog box displays.

3. Enter plant name and select plant type.

4. Select OS version. If Distributed I/O modules are used for Excel 500, select OS
2.0 - 2.04. If Open LON is used, select OS 2.06 or higher.

5. Select units of measurement.

6. Under Preferred Target Hardware, select desired hardware by clicking the


corresponding radio button:

Standard I/O (XF5..)

1223 EN2Z-0937GE51 R0518


LONWORKS NETWORK ENGINEERING CARE

(applicable to Excel 500 and 50 with OS 2.0 - 2.06).


Hardware Points of this plant will be assigned to XF5.. modules (IP bus).

Panel I/O (XF8..)


(applicable to Excel 800, OS 3.00 only)
Hardware points of this plant will be assigned to XF8.. modules (panel bus).

Distributed I/O (XF5..)


(applicable to Excel 500 and Smart with OS 2.0 - 2.04).
Hardware Points of this plant will be assigned to XF5.. modules. (LonWorks-
bus).

Distributed I/O (XF8..)


(applicable to Excel 800, OS 3.00 only).
Hardware Points of this plant will be assigned to XF8.. modules (LonWorks-
bus).

Open LON
Hardware points of this plant will be boardless, that is, unassigned (applicable
to Excel 800 OS 3.0, Excel 500, Smart, 50 with OS 2.06 and higher, and Excel
10)

7. Click OK.

8. Select the same target I/O hardware for all other plants you want to define and
attach the plants.

RESULT: All hardware points of the plants are assigned to the


appropriate hardware modules of the same kind of target
hardware.
The points will be attached to existing modules of the
selected target hardware first. New modules will be created
until the maximum number of I/O modules is reached. If not
all points can be attached, the max. number of hardware
points has been exceeded.

Restrictions Certain point types are not supported by Open LON. When using OS 2.04,
non-supported types will be put on IP (Excel 500, 50) or distributed I/O
modules (Excel 500, Smart), even if Open LON was selected. When using
OS 2.06 or 3.0, non-supported types will be indicated in red in the logical
plant tree and must be put manually on IP boards.

Point types not supported by Open LON:

DO Pulsed Digital Output


FF Flex DO_Feedback_DI
FM Flex Multistage
FP Flex Pulse2
GA Global Analog
GD2 Global Digital 2state
GDn Global Digital Nstate
PT Pseudo Totalizer
TO Totalizer

When Distributed I/O was selected for an Excel 500 / 800 controller and the
application contains a point type, which is not supported by distributed I/O modules,
these points will be put on standard I/O / Panel I/O modules.

Modify Target I/O Hardware 1. In the logical plant tree, click on controller.
for a Complete Controller
2. On the right pane, select the Properties tab.

EN2Z-0937GE51 R0518 1224


CARE LONWORKS NETWORK ENGINEERING

3. Upgrade the controller, if not already done, by changing the Controller OS


Version to Version 2.0 or higher. If the controller is already upgraded, continue
with step 4.

Conditions for Changing Target I/O Hardware


For Excel 50 and Excel Smart, OS version have to be 2.04.
For Excel 500, OS version have to be higher than 2.0. For change to Open
LON, the OS have to be 2.06 or higher.

4. When using OS 2.04 for Distributed I/O modules select topology Shared/Open
LON or Local, by clicking desired radio button.

5. Under Modify Target I/O Hardware click the desired button:

Standard I/O (XF5..)


(applicable to Excel 500 and 50 with OS 2.0 - 2.06).
Hardware points of this plant will be assigned to XF5.. modules (IP bus).

Panel I/O (XF8..)


(applicable to Excel 800, OS 3.00 only)
Hardware points of this plant will be assigned to XF8.. modules (panel bus).

Distributed I/O (XF5..)


(applicable to Excel 500 and Smart with OS 2.0 - 2.04).
Hardware points of this plant will be assigned to XF5.. modules. (LonWorks-
bus).

Distributed I/O (XF8..)


(applicable to Excel 800, OS3.00 only).

1225 EN2Z-0937GE51 R0518


LONWORKS NETWORK ENGINEERING CARE

Hardware points of this plant will be assigned to XF8.. modules (LonWorks-


bus).

Open LON
Hardware points of this plant will be boardless, that is, unassigned (applicable
to Excel 800 OS 3.0, Excel 500, Smart, 50 with OS 2.06 and higher, and Excel
10).

RESULT: All plants will be automatically detached and the plant


automatically reattached to the selected target hardware. All
datapoint attributes remain unchanged except the technical
address.

Restrictions Certain point types are not supported by Open LON. When using OS 2.04,
non-supported types will be put on IP (Excel 500, 50) or distributed I/O
modules (Excel 500, Smart), even if Open LON was selected. When using
OS 2.06 or 3.0, non-supported types will be indicated in red in the logical
plant tree and must be put manually on IP boards or panel I/O boards.

Point types not supported by Open LON:

DO Pulsed Digital Output


FF Flex DO_Feedback_DI
FM Flex Multistage
FP Flex Pulse2
GA Global Analog
GD2 Global Digital 2state
GDn Global Digital Nstate
PT Pseudo Totalizer
TO Totalizer

When Distributed I/O was selected for an Excel 800/500 controller and the
application contains a point type, which is not supported by distributed I/O modules,
these points will be put on standard I/O / panel I/O modules.

Define Mixed Target Hardware Configuration

Purpose Define mixed target I/O hardware configuration (Standard I/O / Panel I/O
and/or Distributed I/O, and/or Open LON) for Excel 800, 500, Smart, or 50
controllers. Possible configurations depend on controller type and OS
version.
Procedures This can to be done by selecting different target hardware (Standard I/O /
Panel I/O, Distributed I/O, or Open LON) for plants when defining the plants

or

by modifying the target hardware of plants already defined and attached

or

by modifying modules to a different type and/or swapping points between different


module types by using the terminal assignment function (see TERMINAL
ASSIGNMENT chapter).

Define Plants with Different Target I/Os1. In the logical plant tree, click on controller, you want to create the
plant for.

2. Click menu item Plant, then drop-down item New.


RESULT: The New Plant dialog box displays.

EN2Z-0937GE51 R0518 1226


CARE LONWORKS NETWORK ENGINEERING

3. Enter the plant name and select plant type.

4. Select OS version. If Distributed I/O modules are used, select OS 2.0 - 2.04. If
Open LON is used, select OS 2.06 or higher.

5. Select units of measurement.

6. Under Preferred Target I/O select desired target I/O hardware by clicking the
corresponding radio button:

Standard I/O (XF5..)


(applicable to Excel 500 and 50 with OS 2.0 - 2.06).
Hardware Points of this plant will be assigned to XF5.. modules (IP bus).

Panel I/O (XF8..)


(applicable to Excel 800, OS 3.00 only)
Hardware points of this plant will be assigned to XF8.. modules (panel bus).

Distributed I/O (XF5..)


(applicable to Excel 500 and Smart with OS 2.0 - 2.04).
Hardware Points of this plant will be assigned to XF5.. modules. (LonWorks-
bus).

Distributed I/O (XF8..)


(applicable to Excel 800, OS 3.00 only).
Hardware Points of this plant will be assigned to XF8.. modules (LonWorks-
bus).

Open LON
Hardware points of this plant will be boardless, that is, unassigned (applicable
to Excel 800 OS 3.0, Excel 500, Smart, 50 with OS 2.06 and higher, and Excel
10)

7. Click OK.

8. For further plant(s), select different target I/O hardware and attach the plants.

RESULT: The hardware points of the plants will be assigned to existing


hardware modules of the selected target hardware. New
modules will be created until the maximum number of I/O
modules is reached. If this limit is reached, remaining points

1227 EN2Z-0937GE51 R0518


LONWORKS NETWORK ENGINEERING CARE

will be attached to eventually existing free terminals on


modules of the different hardware type.
If all points can still not be attached, the max. numbers of
hardware modules and points respectively have been
exceeded. In this case, reduce the number of hardware
points to the maximum number of available hardware points
for the particular hardware modules.

Restrictions Certain point types are not supported by Open LON. When using OS 2.04,
non-supported types will be put on IP (Excel 500, 50) or distributed I/O
modules (Excel 500, Smart), even if Open LON was selected. When using
OS 2.06 or 3.0, non-supported types will be indicated in red in the logical
plant tree and must be put manually on IP boards or panel I/O boards.

Point types not supported by Open LON:

DO Pulsed Digital Output


FF Flex DO_Feedback_DI
FM Flex Multistage
FP Flex Pulse2
GA Global Analog
GD2 Global Digital 2state
GDn Global Digital Nstate
PT Pseudo Totalizer
TO Totalizer

When Distributed I/O was selected for an Excel 500/800 controller and the
application contains a point type, which is not supported by distributed I/O / Panel
I/O modules, these points will be put on standard I/O modules / panel I/O modules.

Modify Target I/O Hardware 1. In the logical plant tree, click on the plant.
for a Plant
2. Click on the Properties tab on the right.

3. Under Preferred Target Hardware select desired target hardware:

Standard I/O (XF5..)


(applicable to Excel 500 and 50 with OS 2.0 - 2.06).
Hardware points of this plant will be assigned to XF5.. modules (IP bus).

EN2Z-0937GE51 R0518 1228


CARE LONWORKS NETWORK ENGINEERING

Panel I/O (XF8..)


(applicable to Excel 800, OS 3.00 only
Hardware points of this plant will be assigned to XF8.. modules (panel bus).

Distributed I/O (XF5..)


(applicable to Excel 500 and Smart with OS 2.0 - 2.04).
Hardware points of this plant will be assigned to XF5.. modules. (LonWorks-
bus).

Distributed I/O (XF8..)


(applicable to Excel 800, OS 3.00 only).
Hardware points of this plant will be assigned to XF8.. modules (LonWorks-
bus).

Preserve technical address refers to modification of the target hardware via the
standard I/0 and distributed I/O radio buttons, if point changes in the TAF have
already been made before (only applies to Excel 500 controller OS Versions 2.0
and higher).

Enabling this checkbox when changing the target hardware results in the
following:

Points that are already assigned to that target hardware type, which will be
changed to, preserve their technical address on the corresponding module.

Disabling this checkbox when changing the target hardware results in the
following:

Points that are already assigned to that target hardware type, which will be
changed to, may lead to a change of the technical address on the
corresponding module. The Attach process optimizes for best use of modules.

5. Click OK to confirm.

RESULT: An attached plant will be automatically detached and the


plant automatically attached to the selected target hardware.

Restrictions Certain point types are not supported by Open LON. When using OS 2.04,
non-supported types will be put on IP (Excel 500, 50) or distributed I/O
modules (Excel 500, Smart), even if Open LON was selected. When using
OS 2.06 or 3.0, non-supported types will be indicated in red in the logical
plant tree and must be put manually on IP boards or Panel I/O boards.

Point types not supported by Open LON:

DO Pulsed Digital Output


FF Flex DO_Feedback_DI
FM Flex Multistage
FP Flex Pulse2
GA Global Analog
GD2 Global Digital 2state
GDn Global Digital Nstate
PT Pseudo Totalizer
TO Totalizer

When Distributed I/O was selected for an Excel 500/800 controller and the
application contains a point type, which is not supported by distributed I/O modules,
these points will be put on standard I/O modules / Panel I/O modules.

IMPORTANT
When an Excel 500/800 controller is full, that is, the maximum number of
modules has been reached, a change in the plant target I/O hardware will
not be able to create any different module type. Therefore the actual
hardware will not change, even if the setting for the plant is changed on the
Plant Properties tab. In this case you have to do manual changes via the
terminal assignment or set the Controller to the other target I/O hardware
that will affect all plants.

1229 EN2Z-0937GE51 R0518


LONWORKS NETWORK ENGINEERING CARE

Data Priority of NVs and Datapoints


This section describes the priority between the network variables and the datapoints
in the application. A valid network input value always has priority over the value from
a sensor or switch wired directly to the controller or the values from the internal
control algorithm or Time Program.

When a network input variable is not bound and its value is INVALID, then the value
is ignored and the value from the local sensor/switch, the control algorithm, or the
Time Program is written to the datapoint.

When a network input variable is not bound and has valid data, then the data is
written to the mapped datapoint. The datapoint will then work in the Manual mode,
and values from the internal algorithm, Time Program, or local sensor/switch are
ignored.

When a network input variable is bound and its value is INVALID, then the value is
ignored and the value from the local sensor/switch, the control algorithm, or the
Time Program is written to the datapoint.

When a network input variable is bound and has valid data, then the data is written
to the mapped datapoint. The datapoint will then work in Auto mode, and values
from the internal algorithm, Time Program, or local sensor/switch are ignored.

When a network input variable is bound and reports NO RESPONSE (sending


device or communication failure), then the latest value from the network is written to
the mapped datapoint. The datapoint will then work in Auto mode, and values from
the internal algorithm, Time Program, or local sensor/switch are ignored.

Enter Program ID
Purpose The program ID is provided in the XIF file and is used by a network
management tool to identify the type of device (network interface). The
program ID is a unique ID for one special type of device. The same device
type can be used multiple times within one project; the program ID will then
be the same for every device. When using different devices having different
network interfaces in one or more projects, the program ID has to be
different.

The program ID consists of two parts. One part is calculated due to


controller type related data. The second part consists of an offset you can
enter for the project, and the controller number that is freely editable.

Procedure 1. Enter project Offset as described in the Enter Project Offset section.

2. In the logical LON-bus part of the tree, click on the controller.

RESULT: On the Properties tab on the right, the calculated part of


the program ID is displayed in the Program ID field.

EN2Z-0937GE51 R0518 1230


CARE LONWORKS NETWORK ENGINEERING

3. By default the controller number is taken over and displayed in the Individual
drop-down listbox at the right. Select desired value (optional).

1231 EN2Z-0937GE51 R0518


LONWORKS NETWORK ENGINEERING CARE

Assign LON devices (Binding)


The assignment of LON devices will be performed on the Terminal Assignment tab
by interaction between the logical plant tree and the logical LON-bus part of the
network tree.

Click on Terminal Assignment tab to display assigned

From logical plant tree,


these two CARE
datapoints are
connected (bound) by
Bus Drag&Drop to
appropriate NVs on the

In logical LON bus These two LON devices are assigned to


part of network CONT01
tree, double-click
on (controller)
device (CONT01), The assignment of LON devices includes two main steps:
to display
assigned devices 1. Add LON device to the network
2. Connect CARE datapoints, respectively NVs to NVs (Binding)

Add LON Device to the Network


To add LON devices to the network, they will be imported out of a device library. In
this device library you can:

• Create new devices


• Import devices via XIF file or Online
• Copy devices
• Rename devices
• Delete devices

Procedure 1. In the logical LON-Bus part of the network tree, double-click on the LON
device, e.g. controller device, you want to assign a LON device to.

EN2Z-0937GE51 R0518 1232


CARE LONWORKS NETWORK ENGINEERING

RESULT: The controller is highlighted in yellow.

2. On the right pane, select the Terminal Assignment tab.

3. On the Terminal Assignment pane, click right mouse key, then click Device
Library in the context menu.

RESULT: The Library dialog box displays.

1233 EN2Z-0937GE51 R0518


LONWORKS NETWORK ENGINEERING CARE

4. Open the Device Library tree, to display the available devices.

NOTE: Creating, deleting and renaming folders can structure the tree.

5. Select the device in the DeviceLibrary tree, drag it to a blank spot on the
Terminal Assignment tab and drop it there.

EN2Z-0937GE51 R0518 1234


CARE LONWORKS NETWORK ENGINEERING

RESULT: The LON device is concurrently added to three locations:

- to the terminal assignment tab


- to the channel where the selected LON device resides
- in the logical LON-Bus part of the network tree, to the
folder
where the selected LON device resides

1235 EN2Z-0937GE51 R0518


LONWORKS NETWORK ENGINEERING CARE

LON device is
concurrently
added to three
locations

6. To assign the device, continue by interconnecting the devices as described


under the Connect CARE Datapoints/NVs to NVs section.

On the top of the LON device the name is displayed. The terminals display the
NV name. Input-NVs are indicated on the left as green arrows, Output-NVs are
indicated on the right as red arrows. Upward- and downward scroll arrows on
the right top and at the bottom allow to scroll through all available NVs of the
device. Scrolling is also possible when dragging a datapoint/NV onto a terminal
by positioning the datapoint/NV over the upward or downward scroll arrow.
Right to the terminal a combined upward-downward arrow allows to display
bound NV/datapoint names. Right to the upward-downward arrow, a field allows
displaying the current online value of the NV. A tool tip displays the engineering
unit when moving the cursor over the field. When setting the terminal online, the
field is white. When setting the terminal offline, the field is gray. A plus symbol
at an NV indicates components of a structured NV. In the middle at the bottom,
the neuron ID is displayed. On the left at the bottom the color of the LON device
status icon indicates the current status of the device (white = unknown-not
initialized, green = application is running, red = not available-application
stopped). Fully-colored means that the current status in CARE and the device
status is the same. Half-colored means "Updates pending". Certain devices
such as distributed I/O modules and Smart I/O modules can be displayed in two
different modes (see Show LON device as Open LON section).

LON device
name Upward
Scroll arrow

NV name

Scroll

Output
Input

Online

LON device
Neuron Downward
Scroll arrow
EN2Z-0937GE51 R0518 1236
CARE LONWORKS NETWORK ENGINEERING

To display assigned devices for one particular device, please refer to the Display
Connected Devices section.

Show LON Device as Open LON

Some devices such as Smart I/O modules or distributed I/O modules can be
displayed in two different modes, as:

• Standard mode
• Open LON mode

A Smart I/O module such as XFC2D05001 shows the terminals in standard mode as
follows:

A distributed I/O module such as XFL 521 of B-type shows the terminals in standard
mode as follows:

1237 EN2Z-0937GE51 R0518


LONWORKS NETWORK ENGINEERING CARE

As Open LON, the NVs residing on the device terminals are shown:

IMPORTANT
When connecting CARE datapoints to a distributed I/O or Smart I/O
module in the standard mode, that is no NVs are shown, CARE
automatically creates the proper connections through the CARE
Autobinding mechanism. Hence, the standard mode is recommended for
the binding of distributed I/O or Smart I/O modules to an Excel 500
controller. Do not display distributed I/O or Smart I/O modules as Open
LON when binding them to an Excel 500 controller. The Open LON display
mode is recommended if NVs from Open LON devices should be
connected to a distributed I/O or Smart I/O module.

Procedure 1. To toggle between the Standard and the Open LON mode, do the
following:

EN2Z-0937GE51 R0518 1238


CARE LONWORKS NETWORK ENGINEERING

2. Move cursor over the device.

3. Click right mouse key and with left mouse key, click on Show as Open LON to
check/uncheck the option.

RESULT: The device is displayed in Open LON mode (Show as Open


LON checked), respectively standard mode (Show as Open
LON unchecked).

Connect CARE Datapoints/NVs to NVs


Assigning LON devices to others will be done by connecting the appropriate NVs of
the two devices. If one LON device is an Excel 50 or 500 or 800 controller,
assignment will simply be done by connecting the CARE datapoints to the
appropriate NVs of the LON device (CARE Autobinding). When connecting
datapoints to NVs, CARE internally creates the corresponding NVs of the same
name (Mapping). In case of the assignment of two LON devices, the NVs of the
corresponding devices will be directly connected. In case the output and input NV
resides on the same device, a turnaround binding will be executed.

Procedure 1. Make sure that the LON device to which you want assign another
device or on which you want to create a turnaround binding, has been
selected by double-clicking in the network tree (highlighted in yellow)
and the Terminal Assignment tab has been selected on the right pane.

RESULT: On the terminal assignment tab, already assigned LON


devices are displayed (see Add LON device to the
Network section).

2. If the LON device you want to assign is not available, add desired device to the
network by Drag&Drop of the LON device from either the logical LON-Bus part
of the network tree or the device library (see Add LON device to the Network
section). In case of turnaround binding creation, it is the same device.

3. In the logical plant tree, click on the datapoint.

Or, if the datapoint is also assigned to a module, click on the terminal on the
terminal assignment tab on the right.

Or, when assigning two Open LON devices to each other, click on the NV in the
logical LON-Bus part of the network tree, you want to connect to the LON
device displayed on the terminal assignment tab.

Or, when creating a turnaround binding on one and the same device, click on
the NV in the logical LON-Bus part of the network tree.

4. Drag it to the desired terminal on the LON device and drop it.

RESULT: When moving the datapoint/NV over the LON device,


CARE shows any NV type in green that matches to the
datapoint/NV. In the status line at the bottom, the
corresponding NV name, NV type and the LON object,
which the NV belongs to, is displayed.

1239 EN2Z-0937GE51 R0518


LONWORKS NETWORK ENGINEERING CARE

Datapoint
“MaTemp” can be
dragged from both
locations

In logical LON bus


part of network
tree, double-click
on destination
device (CONT01),
to display
assigned source

Example 2: Connection of CARE Datapoint to NV of an Open LON Device (Excel 500 to Excel 10 Hydronic
controller)

EN2Z-0937GE51 R0518 1240


CARE LONWORKS NETWORK ENGINEERING

Example 3: Connection of NVs of two Open LON Devices

RESULT: The connection is indicated as follows:

When a CARE datapoint was connected, CARE


automatically creates a NV of the same name, in the

1241 EN2Z-0937GE51 R0518


LONWORKS NETWORK ENGINEERING CARE

previous case (see figure, respectively Example 2)


nvoMaTemp for the datapoint MaTemp. On the device in
the terminal assignment tab, the connected datapoint with
the newly created NV name is shown as "terminal"
covering the NV where the datapoint has been dropped.
A small green, respectively red arrow indicates the NV
type, input or output NV.

You can toggle between the display of the datapoint name


and the corresponding NV name, for example, MaDmpr ↔
nvoMaDmpr by clicking the dark upward-downward arrows
right at the terminal.

If multiple datapoints or NVs have been dropped onto the


same terminal, you can scroll with the dark upward-
downward arrows and all of them will be displayed with
their datapoint name and NV name.

If (only) two NVs are mapped to a each other, see figure,


respectively Example 3, toggling is not possible.

In the LON-Bus part of the network tree, any bound NV is


indicated by its blue background, which previously was
yellow in the unbound state.

For a connection between two NVs, in the status line at


the bottom, the NV name and NV type of the moved NV
(left side), the NV name, NV type and the LON object
where the NV has been dropped (right side), is displayed.

Example 4: Status display of two connected NVs

For a connection between CARE datapoint and NV, in the


status line at the bottom, the datapoint type and subtype
(left side), the NV name, NV type and the LON object,
where the datapoint has been dropped (right side) is
displayed.

Example 5: Status display of connected CARE Datapoint and NV

Datapoint Display Depending on their status/type, datapoints are displayed in different colors
in the logical plant tree:

EN2Z-0937GE51 R0518 1242


CARE LONWORKS NETWORK ENGINEERING

Point Status/Type Color


On board black
Boardless white
On board and mapped yellow
Boardless and mapped yellow
On board, mapped and green
bound
Boardless, mapped and green
bound
Boardless Flexpoint red

NV and LON Object Display Depending on their status, NVs and LON objects are displayed in different
colors in the LON-bus part of the network tree:

Tree Item Status Color


NV Unbound Yellow background with green left-
handed arrow (inputs) and red right-
handed arrow (outputs)
Bound Dark blue background with green
left-handed arrow (inputs) and red
right-handed arrow (outputs)
LON Object No bound NVs Green background with green left-
included handed arrow and red right-handed
arrow
At least one bound Bright blue background with green
NV included left-handed arrow and red right-
handed arrow

NOTE: How connections are displayed in the logical LON part of the network
tree, please refer to the Show Connections of Devices section.

What Kind of NV Types can be bound together?

1243 EN2Z-0937GE51 R0518


LONWORKS NETWORK ENGINEERING CARE

The following describes the different ways of binding mechanisms for Excel 800,
500, 50 and Smart controllers depending on the provided network variables types of
the used devices.
Autobinding can only be applied to a certain number of standard network variable
types (SNVTs) and user-defined network variable types (UNVTs). This is a subset of
the total number of NV types supported by CARE.

Autobinding of unstructured
SNVTs and UNVTs supported
by the controller Standard network variable types (SNVTs) that are supported by Excel 800,
500, 50 or Smart controller can only be bound together if they are of the
same type.

Example: An output NV of type SNVT_temp can only be bound to an


input NV of type SNVT_temp and vice versa. CARE considers
this automatically when binding a CARE datapoint to a NV of
another LON device (autobinding).

Autobinding of structured
SNVTs and UNVTs supported
by the controller Mainly for autobindings to Excel 10 controllers, CARE provides a couple of
special structured UNVTs. All those NV types are indicated by ´80000` at
the beginning of their name, for example,
80000C5007030403_nvoAlarmStatus_XL500.

For the Excel 800, 500, 50 and Smart controller, CARE provides some
special adapted variants of structured LonMark SNVTs that the controller
can use either for autobinding or manual binding. All those SNVTs are
indicated by the suffix ´_XL500`, for example, SNVT_switch_XL500 or
SNVT_switch_struct_XL500.

Compact structured SNVTs


For autobinding the structured SNVTs are of type ´compact´ and consist of
multiple components, for example the NVT_switch_XL500 consists of the
two components value and state. Structured compact SNVTs are indicated
by the suffix ´_XL500`.

Compact ´_XL500` SNVTs are designed for autobinding between one


datapoint and one NV without the necessity of mapping each component to
one separate datapoint.

When applying a compact ´_XL500` SNVT, the controller automatically calculates


the proper result out of the components according to the implemented controller
algorithm.

Mappable structured SNVTs


In comparison to the structured compact SNVTs to be used for autobinding,
CARE provides structured SNVTs for manual binding. In this case, each
component of the SNVT can be mapped to a separate datapoint. Structured
SNVTs to be used for manual binding are indicated by the suffix
´_struct_XL500`, for example SNVT_tod_event_struct_XL500. Structured
SNVTs with mappable components can be used in case the automatic
algorithm of the controller should be evaded and specific engineering
should be applied.

For all above mentioned structured SNVTs and UNVTs, CARE


automatically assigns the appropriate structured NV type to a datapoint
when the datapoint is connected to corresponding structured NV
respectively component.

Manual binding of
structured UNVTs or SNVTs
supported by the controller For the Excel 800, 500, 50 and Smart controller, CARE provides some
special adapted variants of structured LonMark SNVTs that the Excel 800,
500, 50 and Smart controller can use for manual binding.

For detailed description, please refer to the "Autobinding of structured SNVTs and
UNVTs supported by the controller" section.

EN2Z-0937GE51 R0518 1244


CARE LONWORKS NETWORK ENGINEERING

Manual Binding of
unstructured SNVTs
and UNVTs not supported
by the controller If non-supported unstructured SNVTs or UNVTs from another LON device
should be bound to the Excel 800, 500, 50 or Smart controller, user-defined
network variable types (UNVTs) must be applied for the controller in CARE.

NOTE: The CARE autobinding mechanism is not possible.

The following UNVTs are provided by CARE:

• UNVT_byte
• UNVT_ubyte
• UNVT_word
• UNVT_uword
• UNVT_long
• UNVT_ulong
• UNVT_float

The UNVTs consist of 1, 2 or 4 bytes and are signed or unsigned (u). The scale
factor for all CARE UNVTs is as follows: a = 1, b = 0, c = 0.

IMPORTANT
In order to bind an UNVT to a non-supported SNVT or UNVT, they must
have the same byte size (contact device manufacturer for detailed
information of NV structure). The type definition such as integer, floating
(including the algebraic sign) and the scale factor is not checked for
plausibility. Hence, you should consider the scale factors and the type
definitions of the SNVT and the UNVT in order to get a proper result.

Example: An input NV of type SNVT_volt_kilo can be bound to an output


UNVT of type UNVT_word. Both have a byte size of 2, both are
signed, but the scale factor is as follows: a = 1, b = -1, c = 0.

Manual binding of
structured UNVTs or SNVTs
not supported by the controller If non-supported structured SNVTs or UNVTs from another LON device
should be bound to the Excel 800, 500, 50 or Smart controller, user-defined
network variable types (UNVTs) must be applied in CARE for the controller.

To bind non-supported structured SNVTs or UNVTs from another LON


device, CARE provides a set of structured UNVTs that consist of 1 to 31
components.

Each component is of type UNVT_ubyte (u=unsigned) with the byte size =


1.

The structured UNVTs are named as follows:

• UNVT_struct1_XL500
• UNVT_struct2_XL500
.
..

• UNVT_struct31_XL500

The binding is done as follows:

1. Check the byte size of the non-supported structured NV, you want
the Excel 800, 500, 50 or Smart controller NV bind to.
2. For the controller, create a structured NV of type
UNVT_struct"xx"_XL500 of the same byte size.

1245 EN2Z-0937GE51 R0518


LONWORKS NETWORK ENGINEERING CARE

3. Connect the structured NV (nvi or nvo icon in the LON-bus part of


the network tree) to the NV on the device terminal.
4. Manually map a datapoint to each component of the created
structured NV. This provides the further processing of the values by
assigning switching tables or mathematical functions via the
Switching Logic feature of CARE.

IMPORTANT
Before mapping the components to datapoints, you should know the type
definition structure (see LonMark SNVT master list respectively get the
UNVT structure definition from the device manufacturer).

Note, that the type definition structure of the NV as it is displayed on the


device on the terminal assignment tab is decisive regarding the byte-byte
assignment, not the alphanumerical components´ sequence displayed in
the LON-bus part of the network tree.

In order to bind a self-defined structured UNVT to a non-supported


structured UNVT or SNVT, they must have the same byte size. The type
definition such as integer, floating (including the algebraic sign) and the
scale factor is not checked for plausibility. Hence, you should consider the
scale factors and the type definitions of the components to be connected
in order to get a proper result.

Manual Binding of
Structured UNVTs or
SNVTs with bit field components To bind CARE datapoints to structured UNVTs or SNVTs that contain bit
fields, in general the same procedure as for the manual binding of
structured UNVTs or SNVTs has to be applied. In addition, you must
consider to arrange the bit fields in byte groups. Bit fields can be further
processed via switching tables and/or XMFs and can be used for controlling
the status of bound LON devices via Excel 50/500/800 Controller time
programs.

How to Control the Status of a bound LON Device via an Excel


800/500/50 Controller Time Program?

The status of a LON device bound to an Excel 50, 500, or 800 controller, for
example, the occupied/unoccupied status of an Excel 10 controller, can be
controlled by the time program of the Excel 800, 500 or Excel 50 controller.

This is to be done by mapping the relevant datapoints of the Excel controller and the
NVs of the LON device to each other whereby the datapoint must be a switchpoint
of the Excel controller´s time program

One of the following connections must be applied:

Point Type in Time program of Excel NV Type in LON Device


50/500/800 Controller
1 Digital Multistage point SNVT_tod_event_XL500
SNVT_tod_event_struct_XL500
1 Digital Multistage Point - Current_state datafield:
to be mapped on a datapoint
that
1 Digital Multistage Point contains current state
- Next_state datafield:
to be mapped on a datapoint
1 Pseudo Analog Point that
contains next state
- Time_to_next_state datafield:
to be mapped to a datapoint
which is switched by the
controller´s time program

EN2Z-0937GE51 R0518 1246


CARE LONWORKS NETWORK ENGINEERING

Create Turnaround Binding

Purpose To create at turnaround binding, that is, to bind an input NV to an output NV


or vice versa of the same device. For the procedure, please refer to the
Connect CARE Datapoints/NVs to NVs section and connect the two NVs on
the same device.

Create Multiple Bindings

Purpose To create multiple bindings between one particular NV of a source device


and NVs of the same type in multiple target devices.

Procedure 1. In the network tree, navigate to the source device and select the NV
you want to create the multiple bindings for.

2. Click right mouse button and with left mouse button, click on Multiple Binding in
the context menu.

RESULT: The Select target NV and template connection properties


dialogbox displays.

1247 EN2Z-0937GE51 R0518


LONWORKS NETWORK ENGINEERING CARE

3. Expand the tree and navigate to the target NV. Non-compatible devices
respectively NVs cannot be selected as target.

EN2Z-0937GE51 R0518 1248


CARE LONWORKS NETWORK ENGINEERING

4. To alter the default NV connection properties, change the Template connection


properties on the right. Refer to the relevant Echelon documentation for details
on these settings.

5. Click the Next button.

RESULT: All compatible target devices are displayed.

1249 EN2Z-0937GE51 R0518


LONWORKS NETWORK ENGINEERING CARE

6. Select devices by clicking on them. Use CTRL key for multi-selection.

7. Click the Finish button.

RESULT: In case the bindings cannot be created properly the


Binding problems dialogbox displays.

EN2Z-0937GE51 R0518 1250


CARE LONWORKS NETWORK ENGINEERING

8. Click the Continue button, if you want CARE to create the bindings anyway.

RESULT: In case there were binding problems, CARE will perform


all steps that are possible in creating multiple bindings.

9. Click the Cancel button, if you want CARE to cancel the multiple binding
procedure.

Multiple Bindings (Group Binding) may cause problems during LNS Syncronize.
Please notice the Default LON Properties tab description in the Set Global CARE
Options section for more information.

Display Connected Devices


When interconnecting LON devices, you will select a destination device to which you
can assign up to multiple source devices.
Assignment
Destination Source

LON Device S1

LON Device D LON Device S2

LON Device S3

1251 EN2Z-0937GE51 R0518


LONWORKS NETWORK ENGINEERING CARE

Idea To display all assigned devices of one particular device, either destination
or source device, imagine you are sitting in the LON device selected by
double-click in the logical LON-Bus part of the network tree. Imagine you
are looking outside. You will then see all connected devices on the terminal
assignment tab.

Network Tree Terminal Assignment Tab

LON device

LON device

Excel 10

LON device

Excel 500 Oh, I don´t know


what devices are
assigned to me

Smart I/O module

EN2Z-0937GE51 R0518 1252


CARE LONWORKS NETWORK ENGINEERING

Click on Terminal
Assignment tab to display

These two source devices are assigned to

Example 6: Display of assigned devices

If a device is connected to multiple devices, the connected datapoints/NVs are


shown in dark gray. In the following example, the controller CONT1 is connected to
the Hydronic controller currently selected in the network tree. This is indicated by the
nvoHeatOutput terminal. In addition CONT1 is connected to another device, which is
indicated by the dark gray nviDaTemp terminal.

1253 EN2Z-0937GE51 R0518


LONWORKS NETWORK ENGINEERING CARE

Example 7: Display of a multiple connected device

Permanent and Temporary Display of Devices


The assignment of LON devices includes two main steps:

1. Add LON device to the network


2. Connect CARE datapoints, respectively NVs to NVs (Binding)

When adding the device to the network in step 1, the device is permanently
inserted and displayed into the network tree, but temporarily added and displayed
on the terminal assignment tab.

IMPORTANT
If the destination device in the network tree will be de-selected, before the
source device has been bound in step 2, the temporary device will be
removed from the terminal assignment tab. The temporary source device
on the terminal assignment tab will only be displayed permanently after
step 2 has been done.

Once the device has been imported from the device library, it is still
available in the network tree. Do not import the device twice from the
device library. Instead, drag&drop it from the network tree to the terminal
assignment tab.

Show Connections of Devices


See next page.

EN2Z-0937GE51 R0518 1254


CARE LONWORKS NETWORK ENGINEERING

These datapoints are


connected to the XFL
521 module, terminals

Connections are
indicated for the
matching NVs created:

1. In the plant´s LON


object of the
destination device
where the datapoints
belong to.
2. In the LON objects
"Open Loop Sensor
2" and "Open Loop
Sensor 3" of the
target device

For each binding done between datapoint to NV or NV to NV, the connection is


indicated in the logical LON-bus part of the network tree.

1255 EN2Z-0937GE51 R0518


LONWORKS NETWORK ENGINEERING CARE

By double-clicking on the connection on the Properties tab on the right pane, the
connection structure (hub-target) is displayed graphically. For example, the following
Hubs/Targets field for the Connection 4 (Target) shows:

• Controller CONT01 is bound to XFL521


• via the nviCool1 (Target) belonging to the AHU1 LON object and
the nvoAiValue(2)(Hub) belonging to the Open Loop Sensor 3 LON
object

The reverse way is also possible:

In the connection structure you can double-click on an NV to display the


corresponding hub/target of the assigned device in the logical LON-bus part of the
network tree.

NOTE: If you would like to configure connection properties, it is strongly


recommended to get familiar with the relevant Echelon documentation.

Configure Connection
Purpose To define settings for a connection between 2 NVs.

NOTE: If you would like to configure connection properties, it is strongly


recommended to get familiar with the relevant Echelon documentation.

Procedure 1. In the LON-bus part of the network tree, click on the connection.

RESULT: On the right pane, the connection properties are


displayed. Settings include, for example, the service type,
broadcast-multicast mode, timers and counts. Below

EN2Z-0937GE51 R0518 1256


CARE LONWORKS NETWORK ENGINEERING

under Hubs/Targets the devices, LON objects and NVs


building up the connection are hierarchically displayed.

2. Select desired options from the corresponding drop-down listboxes. If the Auto
checkbox is checked for an option, CARE will use the value resulting from the
actual peripheral conditions of the NVs building up the connection.

NOTE: It is strongly recommended not to change the AUTO settings without


having advanced knowledge of relevant Echelon technology. For detailed
information, please refer to the relevant Echelon documentation.

Delete Connection / Remove Binding


Deleting a connection removes the binding between two NVs.

Procedure 1. In the logical LON-bus part of the network tree, double-click on the
destination device to display assigned devices on the terminal
assignment tab on the right pane.

2. With right mouse key click on the connection in the logical LON-bus part of the
network tree.

1257 EN2Z-0937GE51 R0518


LONWORKS NETWORK ENGINEERING CARE

3. With left mouse key, click Delete in the context menu.

RESULT: The connection is deleted in the tree and the datapoint


and the NV is removed from the terminal on the device.
Note, that the mapping between NV and datapoint still
remains as the NV is displayed in the tree, in this case
the nviDuctStatic. In the logical plant tree, the datapoint is
displayed in yellow indicating that is already mapped.

EN2Z-0937GE51 R0518 1258


CARE LONWORKS NETWORK ENGINEERING

Remove Datapoint / NV from Terminal


In comparison to the deletion of a connection where the mapping between a NV and
a datapoint is kept, the binding and mapping is deleted when removing a
datapoint/NV from a device terminal.

Procedure 1. In the logical LON-bus part of the network tree, double-click on the
destination device to display assigned devices on the terminal
assignment tab on the right pane.

2. With right mouse key, click on the terminal of which datapoint/NV you want to
remove.

1259 EN2Z-0937GE51 R0518


LONWORKS NETWORK ENGINEERING CARE

3. With left mouse key, click Remove in the context menu or press DELETE key
on the keyboard.

RESULT: The datapoint/NV is removed from the terminal on the


device and the connection and the NV itself is deleted in
the tree. Note, that the binding is removed and the
mapping between NV and datapoint too indicated by the
white display of the datapoint in the logical plant tree.

EN2Z-0937GE51 R0518 1260


CARE LONWORKS NETWORK ENGINEERING

Indicate bound Datapoint on LON Device / Show Bound LON Device of Datapoint
Datapoints which are bound to a LON device are automatically indicated on the LON
device in dark gray when the datapoint is selected in the logical plant tree.

Hence, all bound LON devices can automatically be seen by simply selecting the
datapoint.

Procedure 1. In the logical plant tree, click on the bound datapoint of which bound
LON devices you want to see.

RESULT: On the terminal assignment tab, the bound datapoint is


indicated in dark gray on the corresponding terminal.
Terminals which have bound datapoints to another LON
controller are indicated “anonymously” without the
datapoint name by a dark gray bar.

1261 EN2Z-0937GE51 R0518


LONWORKS NETWORK ENGINEERING CARE

Datapoint ai1 selected in the logical plant


tree is indicated on two terminals

These three
terminals show
“anonymous”
datapoints of

View Bound LON Devices on Plant Level


Purpose To view all bound LON devices of a plant. LON devices of a plant can be
displayed in two ways, either in the logical plant tree or in the network tree
on LON object level

Procedure 1. In the logical plant tree, click on the plant and select the Terminal
Assignment tab.

Or, navigate to the corresponding LON object of the plant in the network tree
and double-click on it.

RESULT: All bound LON devices are displayed.

EN2Z-0937GE51 R0518 1262


CARE LONWORKS NETWORK ENGINEERING

Either in the logical plant tree or in the


network tree, the plant can be selected for
displaying its bound LON devices

View Bound LON Devices on LON Object Level


Purpose To view on LON object level which other LON device is bound to the LON
device. When viewing assigned LON devices of a particular device in the
network tree by double-clicking on its device icon all LON devices
bound to it are displayed on the terminal assignment tab. When double-
clicking on a particular LON object of a device, only the corresponding LON
device, which is connected to that LON object, is displayed on the terminal
assignment tab.

Example: An XFL521 Analog input module is assigned to two


controllers, Cont1 and Cont3. Compare the displays as
described in the following procedure.

Procedure 1. Double-click on the LON device in the network tree and select the
Terminal assignment tab.

RESULT: Both controllers, Cont1 and Cont3, which are bound to the
XFL521 Analog input module, are displayed.

1263 EN2Z-0937GE51 R0518


LONWORKS NETWORK ENGINEERING CARE

2. In the network tree, double-click on the Open Loop Sensor 1 LON object of the
LON device.

RESULT: In this case, only CONT1 is shown on the terminal


assignment tab, that is CONT1 is bound via the Open Loop
Sensor 1 object to the XFL521 Analog input module.

EN2Z-0937GE51 R0518 1264


CARE LONWORKS NETWORK ENGINEERING

3. To view details on which NV is used for the connection, open the Open Loop
Sensor 1 object by clicking on the plus symbol.

1265 EN2Z-0937GE51 R0518


LONWORKS NETWORK ENGINEERING CARE

RESULT: The used NV, in this case nvoAIValue(0) is indicated in


dark blue.

4. Click on the nvoAIValue(0) NV.

RESULT: On the terminal assignment tab the corresponding


terminal highlighted in dark grey.

5. In this example the CONT1 is additionally bound via the Open Loop Sensor 2, 3
and 4 objects. CONT3 is bound via the Open Loop Sensor 5 and 6 objects. To
view details about those bindings repeat steps 2 to 4.

Copy LON Devices


Purpose To copy a LON device (Honeywell LON device or 3rd party LON device)
including its bindings to a LON controller.

NOTE: LON devices can only copied in the same terminal assignment view, that
is, LON devices cannot be copied between different LON controllers.
LON controllers cannot be copied in the TAT. To copy LON controllers,
please refer to the Copy Controller section under CONTROLLERS
DEFINITION, ATTACHMENT, AND MANAGEMENT.

Procedure 1. On the Terminal Assignment tab, display the device you want to copy
by double-clicking on the bound LON controller in the logical plant tree
or in the network tree.

EN2Z-0937GE51 R0518 1266


CARE LONWORKS NETWORK ENGINEERING

2. On the right pane, select the Terminal Assignment tab.

RESULT: All bound LON devices are displayed.

3. Click on the LON device you want to copy.

RESULT: The device is marked in dark-gray.

4. Click right mouse button and with left mouse button click on Copy in the context
menu or press CTRL+C keys.

5. On any position in the terminal assignment tab, click right mouse button and
with left mouse button click on Paste in the context menu or press CTRL+V
keys.

RESULT: The LON device is copied and placed in the terminal


assignment tab. Every copied device is consecutively
numbered as _0, _1, _2 etc. In the network tree, the copied
device is added to the same LON channel respectively to the
same system/subsystem. The bindings of the copied device
are copied as multicast to the existing NVs of the source
device and they have the same binding properties as the
source bindings.

1267 EN2Z-0937GE51 R0518


LONWORKS NETWORK ENGINEERING CARE

Show associated NV of Bound Datapoint


Purpose To show the associated NV of a bound datapoint.

Procedure 1. In the logical plant tree, click on the datapoint.

2. Click right mouse button and with left mouse button click Go to NV in the
context menu.

RESULT: The network tree will be expanded and the associated NV


wil be marked.

EN2Z-0937GE51 R0518 1268


CARE LONWORKS NETWORK ENGINEERING

3. Click on the plus symbol at the associated NV and click on the connection icon.

4. On the right pane, select the Properties tab.

RESULT: Under Hub/Target you can view the corresponding


destination NVs that has caused the binding.

1269 EN2Z-0937GE51 R0518


LONWORKS NETWORK ENGINEERING CARE

The Device Library


The device library stores LON devices for adding them to the network tree,
respectively to the terminal assignment tab. By default, it includes all currently
available Honeywell LON devices. 3rd party LON devices can be imported via XIF
file into the library additionally. In addition, OLink and OPS devices can be created.
In addition, devices can be copied from the network tree to the device library.

The device library dialog window looks as follows:

EN2Z-0937GE51 R0518 1270


CARE LONWORKS NETWORK ENGINEERING

The devices are arranged in a hierarchical tree. The icons in the device library tree
have the following meaning:

= Device library

= Folder

= LON Device

As any hierarchical tree, the device library tree can be structured by creating,
deleting, copying and renaming folders and LON devices.

Click the More button to display details for the selected tree item, in this case for the
XFL521 Analog Input.

1271 EN2Z-0937GE51 R0518


LONWORKS NETWORK ENGINEERING CARE

The device library provides the following functions:

• Create LON devices by importing data from XIF files or Online


• Create OPS devices by using the OPS Template Editor
• Import LON objects from XIF files or Online
• Edit devices
• Assign value conversion tables to devices
• Rename devices
• Copy devices
• Delete devices
• Export and import device library
• Set Values for NVs, SCPTs/UCPTs and NCIs (see Set Values for NVs,
SCPTs/UCPTs and NCIs section)

Structure Device Library Tree


The device library tree can be structured by creating, deleting, copying and
renaming folders and LON devices.

EN2Z-0937GE51 R0518 1272


CARE LONWORKS NETWORK ENGINEERING

Create Folder

Procedure 1. In the tree, right-click on the device library icon or an existing folder,
where the new folder should be created.

2. In the context menu, click on Create Folder.

RESULT: The new folder named NewFolder is created.

3. To name the folder individually, rename the flashing name in the tree.
Or, on the bottom of the Device Library window, click the More button and
rename the folder in the Folder Name field on the right pane. Add a description,
if desired.

Rename Folder

Refer to step 3 of the Create Folder section.

Copy Folder

Procedure 1. In the tree, right-click on the folder, you want to copy and click Copy in
the context menu.

1273 EN2Z-0937GE51 R0518


LONWORKS NETWORK ENGINEERING CARE

2. In the tree, right-click on target folder you want to copy the selected folder to
and click on Paste in the context menu.

RESULT: The folder is copied.

Delete Folder

Procedure 1. In the tree, right-click on the folder, you want to delete and click Delete
in the context menu.

EN2Z-0937GE51 R0518 1274


CARE LONWORKS NETWORK ENGINEERING

Create LON Device


Procedure 1. Click on the More button on the bottom of the Device Library window.

2. In the tree, right-click on the folder, in which you want to create the LON
device and click on Create LON device in the context menu.

RESULT: The LON device is inserted into the tree.

3. Issue a name and enter a description if desired on the right pane.

4. Select the ping intervall from the Ping Intervall drop-down listbox.
The ping interval determines how often a device is pinged by the LNS Server to
ensure it is still operating and in communication with the network. Set the ping
interval based on the expected attachment of the device to the network. If you
expect that the device will never move on the network, select Never. Set the
interval to 15 minutes for a device you expect will move rarely, to 2 minutes for
a device you expect will move fairly often, and to 1 minute for a device you
expect will move very often. The default ping interval is 1 Minute.

5. Enter the location string in ASCII format into the Location field, if desired.

6. Check the Keep Device Configuration checkbox if you want to keep the
configuration parameters of the device when applying one of the following
functions: plug-in offline or online, commissioning or synchronizing with LNS.
Setting this option prevents unintentional overwritting of the current
configuration of the physical device. The above functions are not available until
the parameters have been uploaded from the device. When setting this option,
each device of this type will have the “Keep Device Configuration” automatically
checked when it will be added to the network tree, respectively to the terminal

1275 EN2Z-0937GE51 R0518


LONWORKS NETWORK ENGINEERING CARE

assignment tab (for further information, please refer to the Keep Device
Configuration section).

7. Right-click on the device icon in the tree.

8. Click on Import LON object and from XIF file if the XIF file is available.
Or, click on From Online, if you want to import the information online directly
from the device connected to the LonWorks network.

RESULT: If the “From XIF file” option has been selected, the Open
dialog box is displayed.

9. Browse to the folder where the XIF file has been saved, select the XIF file and
click the Open button.

RESULT: The corresponding LON objects are imported and


displayed in the tree. The LON device name is re-named
by the name saved in the XIF file, in this case Elm
Echelon Case Controller.

EN2Z-0937GE51 R0518 1276


CARE LONWORKS NETWORK ENGINEERING

RESULT: If the “From Online” option has been selected, the Get
Service Pin dialog box is displayed.

10. Press the service pin on the hardware.

RESULT: The corresponding LON objects are imported and


displayed in the tree. The LON device name is re-named
by the name saved in the XIF file, in this case Elm
Echelon Case Controller.

IMPORTANT
The ´From Online` option should only be used if the device´s XIF file is not
available and/or the CARE database is not to be synchronized with LNS.

Create OLink Template


The device library provides the creation of OLink templates for multiple use of OLink
hardware configurations. Templates can be created by step-by-step procedure or
automatically by importing the vendor network interface via opt file.

IMPORTANT
Changes on an OLink template done in the device library are not reflected
in a template already assigned to a controller. After the template has been
assigned to the controller, it cannot be unassigned and replaced by another
template.

Creating an OLink template, includes the following steps:

• Create OLink controller (device)


• Create OLink subystem controller
• Create OLink point(s)

Procedures
Create OLink device 1. On the CARE toolbar, click on the Device Library icon

RESULT: The Library dialog window displays.

2. At the bottom, click on the More >> button to activate the itemized display for
items selected in the tree.

1277 EN2Z-0937GE51 R0518


LONWORKS NETWORK ENGINEERING CARE

3. Right-click on the folder, in which you want to create the OLink device
(template), in this case, the default folder Honeywell Integration Devices (OPS)
and click on Create OLink device in the context menu.

RESULT: The OLink device is inserted into the tree.

4. Enter basic information on the OLink Device tab on the right as follows:

OLink Device Name


Name of device

Vendor Name
Name of vendor of which subsystem is to be connected to the C-Bus

Initialization Block
Communication and setup parameters

5. Continue by creating OLink subsystem controller(s) as described in the


following steps.

Create OLink Subsystem Controller 6. In the network tree, click on the OLink device.

7. Click right mouse key and with left mouse key, click on Create OLink
Subsystem Controller in the context menu

RESULT: The OLink subsystem controller is assigned to the OLink


controller in the tree.

8. On the OLink Subcontroller tab on the right, enter a name in the Description
field.

9. In the list below, enter names and values for the OLink interface in the Value
and Name fields. Therefore you need the VNI description from the vendor,
which typically includes the list of points which are to be mapped to the C-bus,
the engineering units, etc.

EN2Z-0937GE51 R0518 1278


CARE LONWORKS NETWORK ENGINEERING

10. Check the Keep Points Read Only checkbox, if desired. In this case, point
values cannot be overwritten.

11. Continue by creating OLink points as described in the following steps.

Create OLink Point 12. In the tree, click on the OLink subsystem controller.

13. Click right mouse key and with left mouse key, click on Create OLink Point in
the context menu

RESULT: The OLink point is assigned to the OLink subsystem


controller in the tree.

14. On the OLink Point tab on the right, define settings as follows:

Description
Enter a point name

Point Type
Select point type from drop-down list box

Value Format
Select value format from drop-down list box

Engineering Unit
Select engineering unit from drop-down list box, if desired. For more information
on how to create engineering units for an OLink controller, refer to the "Define
OLink Engineering Units" section.

Periodic Write
Check the checkbox, if you want the value to be written periodically

Parameters
Enter names and values for the OLink interface in the Name and Value fields.
Therefore you need the VNI description from the vendor which typically includes
the list of points which are to be mapped to the C-bus, the engineering units,
etc.

15. To save the template, click Exit button at the bottom of the Device Library
window.

Create OPS Device

1279 EN2Z-0937GE51 R0518


LONWORKS NETWORK ENGINEERING CARE

Procedure 1. In the tree, right-click on the folder, in which you want to create the OPS
(Open Point Server) device and click on Create device in the context
menu.

RESULT: The LON device is inserted into the tree.

2. In the Toolbar, click on the OPS Editor icon to invoke the OPS Template Editor.

For detailed description on how to edit the OPS device in the OPS Template Editor,
please refer to the OPS Editor section.

3. When finished creating the OPS data, click OK button to close the OPS
Template Editor.

Configure NV List Display


Purpose To define which NVs should be displayed for a LON device in the device
library tree.

NOTE: The same functionality is available for a particular device displayed on the
terminal assignment tab.

Procedure 1. In the tree, double-click on the LON device to display its LON objects.

2. Double-click on the LON object(s) whose NVs you want to display.

EN2Z-0937GE51 R0518 1280


CARE LONWORKS NETWORK ENGINEERING

3. Right-click on the LON device and click on NV-Devlib-List in the context menu.

RESULT: The NV-Devlib-List dialog box displays. For all NVs of the
selected LON device, the following is shown:

NV name
e.g. nviRequest

LON object
LON object which the NV belongs to, e.g. Node object
NV Type
SNVT_object_request

I/O
Type of NV, input or output

CARE Visual

1281 EN2Z-0937GE51 R0518


LONWORKS NETWORK ENGINEERING CARE

Whether the NV should be displayed on the Terminal


Assignment Tab in CARE or not, that is, whether the NV
should be displayed for the LON device in the device library
tree and the LON network tree or not. Check/uncheck the
corresponding checkbox(es) for the desired result. To
select/deselect all NVs, highlight the column and click the

/ icon.

Central Usage (for future use)


Whether the NV should be used on a central, such as
XBS or not. Check/uncheck the corresponding
checkbox(es) for the desired result.

XLT (for future use)


Whether the NV should be used for the Excel toolkit or
not. Check/uncheck the corresponding checkbox(es) for
the desired result.

To select/deselect all NVs of a column, highlight the


corresponding column and click the / icon.

To sort a column ascending/descending, highlight the

corresponding column and click the / icon.

4. Confirm your settings by clicking OK.

Assign Value Conversion Table


Purpose To assign a value conversion table to a LON device. This can be applied
especially to the Excel 500 - Smart I/O autobinding. When binding a Smart
I/O module that has value conversion table assigned, for example, to an
Excel 500 controller, the value conversion table will be used automatically
by the Excel 500 controller.

EN2Z-0937GE51 R0518 1282


CARE LONWORKS NETWORK ENGINEERING

Procedure 1. In the tree, right-click on the LON device and click on


ValueConversionTable in the context menu.

RESULT: The Value Conversion Table dialog box displays.

For detailed description on how to build a value conversion table, please refer
to the Build Conversion Table section.

1283 EN2Z-0937GE51 R0518


LONWORKS NETWORK ENGINEERING CARE

Rename LON Device


Procedure 1. In the tree, right-click on the LON device and click on Rename Device
in the context menu. Rename the flashing name in the tree.

Or, on the bottom of the Device Library window, click the More button and
rename the folder in the Folder Name field on the right pane. Add a description,
if desired.

Copy LON Device


A LON device can be copied within the device library with its default configuration or
by dragging&dropping it from within the LON-bus part of the network tree. In this
case individually configured devices, either by plug-in or by CPs change, can be
added to the device library for re-use (see Import device library and Export device
library sections).

Copy Default LON Device within Device Library

Procedure 1. In the tree, right-click on the LON device, you want to copy and click
Copy in the context menu.

2. In the tree, right-click on target folder to which you want to copy the selected
device and click on Paste in the context menu.

EN2Z-0937GE51 R0518 1284


CARE LONWORKS NETWORK ENGINEERING

RESULT: The device is copied.

Copy Configured Device into Device Library

Purpose To copy individually configured device from within the logical LON-bus part
of the network tree to the device library.

Procedure 1. In the logical LON-bus part of the network tree, configure device via
plug-in or by editing CPs directly.

2. Open the device library and browse to the target folder you want to copy the
LON device to.

3. In the logical LON-bus part of the network tree, click on the device.

4. Drag it to the device library and drop it to the target folder.

RESULT: In the above example, the Honeywell Fire/Smoke


Damper Controller is copied to the Customized folder.

1285 EN2Z-0937GE51 R0518


LONWORKS NETWORK ENGINEERING CARE

Delete LON Device


Procedure 1. In the tree, right-click on the LON device, you want to delete and click
Delete in the context menu.

Export Device Library


Purpose To backup a device library for repeatedly or multiple use, for example, on a
laptop PC.

Procedure 1. In the device library window, select the device library in the tree and
click on the Export Device Library icon

EN2Z-0937GE51 R0518 1286


CARE LONWORKS NETWORK ENGINEERING

RESULT: The Export Device Library dialog box displays.

2. Under Target directory, select the target directory where the device library
should be saved.

3. Under Device Library Description, enter a description, if desired.

4. Click OK.

RESULT: The Export is starting as the following dialog box


displays.

5. Confirm the Export by clicking OK in the Backup / Restore dialog box.

1287 EN2Z-0937GE51 R0518


LONWORKS NETWORK ENGINEERING CARE

Import Device Library


Purpose To restore a backupped device library. Copies can be created by importing
the library multiple times and saving it under different target library names.

Procedure 1. In the device library window, click on the Import Device Library icon

RESULT: The Import Device Library dialog box displays.


The device library is saved with its name as it is shown as
top-level folder in the device library tree, in this case
DeviceLibrary.

2. Under Source directory, browse to the directory where the device library had
been saved.

3. In the Device Library´s list below, click on the library you want to import.

4. In the Target Device Library Name field, enter a new name for the library.

NOTE: The same source library can be imported multiple times


(copy) by saving it under different target names.

5. Click the Import button.

RESULT: The Import is starting as the following dialog box displays.

6. Confirm the Import by clicking OK in the Backup / Restore dialog box.

RESULT: The Import Device Library dialog box re-displays.

EN2Z-0937GE51 R0518 1288


CARE LONWORKS NETWORK ENGINEERING

7. Click the Close button.

RESULT: The Device Library will be initialized.

RESULT: Finally the device library is added to the tree in the


Device Library window.

1289 EN2Z-0937GE51 R0518


LONWORKS NETWORK ENGINEERING CARE

Import Single LON Device into the Device Library

Purpose To import a single LON device into the device library.

Procedure 1. Import the source device library that contains the LON device you want
to import (see Import Device Library section).

2. Open the copied source device library tree and copy the particular device to the
target device library (see Copy LON device section).

3. Delete the source device library (see Delete Folder section).

Troubleshooting on Errors If the device library import has any errors importing a 3rd party device, the
object
during Import into the Device Libraryserver log will capture the errors if the TRACE=1 is added under the object
server header in the CARE.INI file.

EN2Z-0937GE51 R0518 1290


CARE LONWORKS NETWORK ENGINEERING

Copy LON Device Settings

Copy NV Settings
Purpose To copy the NV settings of a single device to one or multiple other devices
of the same type. You can set the display of NVs on the device in the
terminal assignment tab. In addition, the online availability of NVs can be
defined when you are Onnet with CARE.

Procedure 1. In the logical LON-bus part of the network tree, click on the LON device
of which NV settings you want to copy.

2. Click right mouse button and with left mouse button click on Copy NV Settings
in the context menu.

RESULT: The Select NVs dialog box displays showing the following
properties for all NVs:

1291 EN2Z-0937GE51 R0518


LONWORKS NETWORK ENGINEERING CARE

CARE Visual
Whether the NV should be displayed in CARE on the
Terminal Assignment Tab. Check/uncheck the
corresponding NVs for the desired result.

Online
Whether the current value of the NV should be displayed
in the Online field on the device.

NV name
e.g. nviRequest

LON object
LON object which the NV belongs to, e.g. Node object

NV Type
SNVT_object_request

EN2Z-0937GE51 R0518 1292


CARE LONWORKS NETWORK ENGINEERING

I/O
Type of NV, input or output

3. In the Copy column by default all NVs are checked for copying. To uncheck a
selected NV, click the check bar. To uncheck all NVs, click the icon at the
top. To check all NVs, click the icon at the top.

4. Click the Next button.

RESULT: The Select Target Devices dialog box displays all devices
which are of the same type as the source device. For each
device, the channel and the path is shown, that is where the
target device resides in the physical and logical structure in
the network tree.

1293 EN2Z-0937GE51 R0518


LONWORKS NETWORK ENGINEERING CARE

5. In the Apply column, check the devices to which the NV settings should be
copied. To check all devices, click the icon at the top. To uncheck all
devices, click the icon at the top.

6. Click the Finish button.

RESULT: The Select Target Devices dialog box closes and the NV
settings were copied to the selected target devices.

Copy CPs and NCIs


Purpose To copy the configuration values of a device to one or multiple other
devices of the same type. Hence, LON device configuration via Plug-In
must to be done only once. Configuration values can be CPs (standard and
user defined configuration parameter types) and NCIs (network variables
using the config class keyword for configuration).

NOTE CPs and NCIs of Excel 500/800 controllers as well as extension records
cannot be copied.

Procedure 1. In the logical LON-bus part of the network tree, click on the LON device
of which CPs and NCIs you want to copy.

2. Click right mouse button and with left mouse button click on Copy CPs/NCIs in
the context menu.

RESULT: The Select CPs/NCIs dialog box displays showing the


following properties:

EN2Z-0937GE51 R0518 1294


CARE LONWORKS NETWORK ENGINEERING

CP name
Name of configuration parameter/NCI, e.g.
SCPTdelayTime

LON object
LON object which the CP/NCI belongs to, e.g. Open Loop
Actuator 1
NV Type
NV type which the CP/NCI belongs to, e.g.
SCPTdelayTime

Type
CP type, e.g. CP

Value
CP value. 0-10V Output

1295 EN2Z-0937GE51 R0518


LONWORKS NETWORK ENGINEERING CARE

3. In the Copy column by default all CPs/NCIs are checked for copying. To
uncheck a selected CPs/NCI, click the check bar. To uncheck all CPs/NCIs,
click the icon at the top. To check all CPs/NCIs, click the icon at the top.

4. Click the Next button.

RESULT: The Select Target Devices dialog box displays all devices
which are of the same type as the source device. For each
device, the channel and the path is shown, that is where the
target device resides in the physical and logical structure in
the network tree.

5. In the Apply column, check the devices to which the CPs/NVIs should be
copied. To check all devices, click the icon at the top. To uncheck all
devices, click the icon at the top.

6. Click the Finish button.

EN2Z-0937GE51 R0518 1296


CARE LONWORKS NETWORK ENGINEERING

RESULT: The Select Target Devices dialog box closes and the
CPs/NCIs were copied to the selected target devices.

Edit Excel 500/800 Controller Network Interface Manually


The following main functions will change the network interface of an Excel 500/800
Controller:

• Creating and Mapping NVs to datapoints


• Creating and deleting LON objects
• Creating and deleting input and output NVs of standard and structured
type
• Move NVs between LON objects
• Building and Assigning value conversion tables

Refer to the "Changes on the Controller Network Interface/CARE Application" for


actions to be performed if the network interface has been changed.

Create and Manually Map NV to Datapoint


Purpose NVs can simply be created and mapped to a datapoint by assigning LON
attributes to the datapoint. LON attributes are:

• LON point type (input, output, input&output, manual mapping)


• NV type (SNVT_temp_P, UNVT_byte, Boolean etc.)

Procedure 1. In the logical plant tree, click on the datapoint, you want to create a NV
for and to be mapped to it.

RESULT: On the right, the datapoint attributes are displayed in


itemized display.

1297 EN2Z-0937GE51 R0518


LONWORKS NETWORK ENGINEERING CARE

2. From the Lon Point drop-down listbox, select where the datapoint should be
mapped to:

IMPORTANT
Note that the length of the user address of the datapoint
should not exceed 18 characters when creating Lon points,
since the length for NV names when using LNS tools is
restricted to 21 characters. NVs names longer than 21
characters will abort the translation of the application and
must be reworked.

The value is set to 21 by default in the CARE.INI file and


can be changed if longer names are desired for exclusive
use in CARE.

EN2Z-0937GE51 R0518 1298


CARE LONWORKS NETWORK ENGINEERING

• NV-Input
Datapoint is mapped to an input NV with the prefix nvi at the
datapoint name, e.g. nviMW_OaTemp.
• NV-Output
Datapoint is mapped to an output NV with the prefix nvo at the
datapoint name, e.g. nvoMW_OaTemp.
• NV-Input & Output
Datapoint is mapped to both an input NV and an output NV. Two
NVs will be created with its corresponding prefixes, e.g.
nviMW_OaTemp and
nvoMW_OaTemp.
• Manual Mapping
Pre-Definition. Datapoint can be mapped to an input NV created.
Select Manual mapping if you want to consider this datapoint for
many to one mapping or if you want to map it to another NV.

NOTE: No NV will be created.

4. From the NV-Type drop-down listbox(es), select NV-Type.

RESULT: The created NV with its assigned type is created and added
to the plant object in the logical LON-Bus part (Default
System folder) of the network tree. The NV can also be
displayed and edited directly by clicking on the dotted button
right to the Output drop-down listbox. This dialog
provides working on a single Lon point/NV in more detail
whereas in the network tree all created NVs can be
displayed in an overall view.

1299 EN2Z-0937GE51 R0518


LONWORKS NETWORK ENGINEERING CARE

Datapoint "MaDmpr"
is indicated in yellow
as mapped

This pane shows the


NV properties for
nviMaDmpr (selected
in network tree)

NV "nviMaDmpr" is
created and
mapped to datapoint
"M D "

Lon Dialog accessible by selecting created NV in logical LON-bus part of


network tree

EN2Z-0937GE51 R0518 1300


CARE LONWORKS NETWORK ENGINEERING

Lon Dialog invoked by clicking dotted button for displaying/editing one


single Lon point/NV

Regarding a single Lon point/NV, the functionality is slightly different for both
dialogs.

Create LON Object


Purpose LON objects can be used for hierarchical structuring of the controller
network interface. The following two LON objects are created automatically
and will be displayed in the logical LON-bus part.

• Node Object
• Controller (no NVs by default)

1301 EN2Z-0937GE51 R0518


LONWORKS NETWORK ENGINEERING CARE

When creating new LON objects, they will be assigned to the LON device (controller
icon). Hierarchically they are positioned below the LON device. The node object
includes pre-defined network variables and provides the “communication” between
the objects belonging to a LON device (node).

When creating NVs for a datapoint in the logical plant tree, a LON object with the
plant name, which the LON point belongs to, is automatically created.

Any object can be deleted, except the node object.

Procedure 1. In the logical LON-bus part of the network tree, click on the controller
symbol , which you want, assign the new LON object to.

2. Click menu item Controller, then submenu item LON and Create LON-object.

Or, click Create LON object icon .

Or, click right mouse key and with left mouse key click on Create LON-object in
the context menu.

RESULT: The LON object is created as pre-defined name in the tree.

3. On the right pane, enter desired name for the LON object in the
LonObjectName field.

4. Enter a description if desired in the Description field.

Create/Edit Input - / Output NV


Procedure 1. In the logical LON-bus part of the network tree, click on a LON object or
NV, but not the Node object.

EN2Z-0937GE51 R0518 1302


CARE LONWORKS NETWORK ENGINEERING

2. To create an Input Network Variable (NV-IN), click menu item Controller, then
submenu item LON and Create NV-IN.

Or, click Create NV-IN icon .

Or, click right mouse key and with left mouse key click on Create NV-IN in the
context menu.

3. To create an Output Network Variable (NV-OUT), click menu item Controller,


then submenu item LON and Create NV-OUT.

Or, click Create NV-OUT icon .

Or, click right mouse key and with left mouse key click on Create NV-OUT in
the context menu.

RESULT: Below the controller object in the tree, the NVs are created
with its respective prefix nvi or nvo. On the Properties tab on
the right pane, the newly created NV can be edited as
follows:

- Enter name
- Define NV type
- Enter Selfdoc string
- Map datapoint(s) to the NV
- Define max. bindings for the NV
- Assign value conversion table

1303 EN2Z-0937GE51 R0518


LONWORKS NETWORK ENGINEERING CARE

Enter Name for NV 4. Under Input NV and Output NV, respectively, the default name as
created in the tree is displayed in the NV field. Change the item to a
meaningful name according to your needs, for example nviSensor.

IMPORTANT
Note that the length for NV names is restricted to 21
characters. NV names longer than 21 characters will abort
the translation of the application and must be reworked.

Select NV Type 5. From the NV Type drop-down listbox select the desired NV type.

NOTE: Pre-defined input and output NVs are delivered with CARE. The user
cannot create NV types by herself/himself. When selecting structured
NV types (SNVT_setting and SNVT_preset), refer to the Select Input -
/ Output NV of structured type section.

Enter Selfdoc string 6. In the Selfdoc string field, enter the self-documentation string. The self
documentation string is used to map object indices defined on the node
to their LonMark object types. It has the following structure.

EN2Z-0937GE51 R0518 1304


CARE LONWORKS NETWORK ENGINEERING

Example:
The node has the following five LonMark Objects defined within it: one node
object (type 0); and four closed loop sensor objects (type 2). Suppose that the
developer plans to include additional installation information about the node, in
this case “Installation Text”. The entry would be the following:

&3.2@0,2,2,2,2;Installation Text

IMPORTANT
In this field only text to be defined as additional textual information after the
semicolon can be entered.

Map Datapoint 7. Under Point Mapping you can assign (map) one to several points to the
NV, if desired.

NOTE: Only points, which were set to Manual Mapping in the logical plant
tree, are selectable from the drop-down listbox. Several points can
only be mapped if the NV-Booster check box is checked and the max.
bindings are set (refer to Many-to-One Mapping/NV-Booster section).

In the first row of the Datapoint column, select the datapoint you want to map
to the NV from the drop-down list.

In the Inv.match column, select whether the mapped datapoint should be


checked for invalidity (Yes) or not (No).

Checking for Invalid match makes sure that in case an invalid information
comes from an NV or datapoint, the controller will still work with a "defined
value". The invalidity check works as follows:

Input NVs
In the Inv.match field, select Yes. Enter a datapoint value into the Inv.Value field
in case the Input NV gets invalid (FF). The controller checks the Input NV value
for invalidity. If the Input NV value is invalid, the datapoint will take the set
datapoint value.

Example

An Input NV of type "unsigned byte" is mapped to a datapoint. Invalid match is


set to Yes and the datapoint value is set to 5. As soon as the Input NV value
becomes invalid (e.g. because the mapping is broken) the datapoint value will
be 5.

Output NVs
In the Inv.match field select an operator. Enter a comparison value into the
Inv.Value field. The controller compares the datapoint value with the
comparison value, using the comparison operator. If the comparison result is
TRUE, than the Output NV will take the invalid value (FF).

Possible operators for invalid match are: Exact, Lower, Greater, Lower or
Greater, Lower or Equal, Greater or Equal, Auto.

NOTE: For the Auto operator, the output NV always sends Invalid.

Example

1305 EN2Z-0937GE51 R0518


LONWORKS NETWORK ENGINEERING CARE

A Output NV of type unsigned byte is mapped to a datapoint. Invalid match is


set to ´Lower`. The comparison value is set to 5. As soon as the datapoint´s
value drops below 5, the Output NV´s value will become invalid.

In the Inv.Value column, enter the value that should be used for Invalid Match
checking of the mapped datapoint.

In the Al.No., enter the alarm number (5 - 23, or none) for the datapoint.
Applies to AI, PA and DI points only.

In the Many.t.One column select one the following options to be applied for the
mapped datapoint:

Recent
Latest updated value of the bound output NVs is taken into the data Pont

Min
Minimum value of the bound output NVs is taken into the datapoint

Max
Maximum value of the bound output NVs is taken into the datapoint

Average
Average value of the bound output NVs is taken into the datapoint

Sum
Sum value of the bound output NVs is taken into the datapoint

Number Active Devices


Number Active Devices of the bound output NVs is taken into the datapoint

If desired, map further datapoint(s), starting with the Datapoint column.

Set max. Bindings 8. Check NV-Booster checkbox if you want to display/set the max.
bindings the
(NV-Booster ) input NV can get via LON tool. This selection is for pre-setting memory
in the controller (see Many-to-One Mapping/NV-Booster). From the
drop-down listbox select desired number.

Set Heartbeat for NV 9. Check/uncheck Heartbeat checkbox if you want the controller to
cyclically check if the heartbeat activation is still alive/or not.

The heartbeat can be activated or deactivated for every single NV.


If heartbeat is checked for an input NV, this NV is to be checked according to
nciHrtBtRcv, and all mapped NVs are sent in this way by default. If the con-
troller does not receive an update within the specified interval, it will try to poll
the output NV from the source device. In this way, the heartbeat mechanism
also works for devices without periodic updates. If the polling also fails, the data
point mapped with this NV is set to NO RESPONSE and the invalid value (if
specified) is adopted. Additionally, if alarming has been enabled for the data
point, a NO RESPONSE alarm will be issued. If the value of nciHrtBtRcv is
changed using a LONW ORKS network management tool, and if the application is
saved to Flash memory, the value is saved as well.

If heartbeat is checked for an output NV, this NV is to be sent periodically, and


all mapped NVs are sent in this way by default. If the value of nciHrtBtSnd is
changed using a LONW ORKS network management tool, and if the application is
saved to Flash memory, the value is saved as well.

For all mapped input NVs and output NVs, heartbeat defaults to
checked.

EN2Z-0937GE51 R0518 1306


CARE LONWORKS NETWORK ENGINEERING

Set Flags for NV 10. Check Enhanced checkbox if you want to display/edit one of the
following flags for the NV:

auth_config
Defines whether the authentification of the NV may be modified by a LONW ORKS
network management tool (checked) or not (unchecked). Defaults to checked.

priority conf
Defines whether the priority of the NV may be modified by a LONW ORKS network
management tool (checked) or not (unchecked). Defaults to checked.

service type
Defines whether the service type of the NV may be modified by a LONW ORKS
network management tool (checked) or not (unchecked). Defaults to checked.

offline
Defines whether a NV can only be changed in Offline mode (checked) or not
(unchecked). Defaults to unchecked.

polled
Defines whether the NV can be bound (unchecked) or not (checked). Defaults
to unchecked.

sync
Defines whether the NV is synchronous (checked) or not (unchecked). Defaults
to unchecked.

ext_rec
Defines whether the NV has an extension record following the node´s self-
documentation string (checked) or not (unchecked). Defaults to checked and
cannot be changed.

11. Check/uncheck desired flags described in step 9.

Assign Value Conversion Table 12. First read the general information about conversion tables in the Build a
Conversion Table section.

13. From the Conversion Table drop-down list box, select desired conversion table.
The conversion table is displayed.

1307 EN2Z-0937GE51 R0518


LONWORKS NETWORK ENGINEERING CARE

NOTE: In the list, only conversion tables of the same NV type as selected in
the NV Type field above, are selectable.

The conversion table is applied to all points displayed in the Point Mapping list.
When selecting a special datapoint, the datapoint values of the conversion table
change depending on the datapoint type. When selecting no datapoint, the
conversion table is displayed with its "original values" as they were entered
when building the table. Refer to the Build Conversion Table section for detailed
information.

Select Input - / Output NV of structured type


Structured NV types consist of components with pre-assigned NV types, then called
component types, which cannot be edited. Pre-defined Structured input and output
NV types are delivered. with CARE. The user cannot create Structured input and
output NV types by herself/himself. To each component a single datapoint can be
mapped. In the logical plant tree, for this mapped datapoint, the NV-type, not the
component type of the structured NV is displayed.

IMPORTANT
Note, that once a structured NV type was selected for the NV, it cannot be
reverted to a NV type of other type, e.g. to float or integer etc.

Procedure 1. In the logical LON-bus part of the network tree, click on the NV.

2. From the NV Type drop-down list on the right, select structured NV type.

EN2Z-0937GE51 R0518 1308


CARE LONWORKS NETWORK ENGINEERING

RESULT: A message is displayed asking if you really want to use only


the structured NV type.

3. Confirm by clicking OK for creating the structured NV type.

RESULT: In the tree, the components are displayed below the NV. On
the right, point mapping can be done. To each component
one single datapoint, which has previously been set to
"Manual Mapping" in the logical plant tree, can be mapped.
Many-to-One mapping is not possible. As the figure shows,
Invalid match checking and Alarm No functions can be
applied.

1309 EN2Z-0937GE51 R0518


LONWORKS NETWORK ENGINEERING CARE

When selecting the mapped datapoint in the logical plant


tree, the NV-type, not the component type of the structured
NV is displayed on the Properties tab.

EN2Z-0937GE51 R0518 1310


CARE LONWORKS NETWORK ENGINEERING

For the datapoint "MaTemp" the


mapped NV
"SNVT_obj_status_XL500" is
displayed even if the component
"object id" was previously selected

NOTE: For structured NVs, a conversion table cannot be applied.

Many-to-One Mapping/NV-Booster®
Honeywell’s NV-Booster allows binding all of the output NVs to a single input NV
with a many-to-one binding (for details refer to Mapping and Binding section). The
controller keeps a background copy of the input NV for each of the different
controller output NVs bound to it for performing the mathematical functions. For pre-
setting the memory of the controller, it has to be defined how many bindings at max.
the controller should allow.

The input NV can be mapped to multiple datapoints. For each mapped datapoint
one of the following mathematical functions can be applied.

Recent: Latest updated value of all bound output NVs is used


Min: Minimum value of all bound NVs is used
Max: Maximum value of all bound output NVs is used
Average: Arithmetic average of all bound output NVs is calculated
Sum: The sum of all incoming values is calculated
Number of
active devices: The number of active devices that deliver values via their
bindings.

1311 EN2Z-0937GE51 R0518


LONWORKS NETWORK ENGINEERING CARE

Procedure 1. In the logical LON-bus part of the network tree, select input NV.

2. On the right, check NV-Booster checkbox, and select max. Bindings from the
drop-down listbox.

3. In the Datapoint column, select datapoint you want to map the input NV to.

4. In the Man.t.One column, select mathematical function, which should be


applied.

Arrange NVs
Purpose By default the LON device comes with the node and the controller object.
When creating the network interface by mapping NVs to datapoints, newly
created NVs are automatically assigned to the respective controller object.
If desired, NVs can be grouped and allocated to self-defined objects. This
function allows to structure the LON device according to your needs. It is
only applicable when working in the logical LON-bus part of the network
tree.

Procedure 1. Create LON object(s), if not already done.

2. Move existing NVs to the desired object(s) per drag&drop. When creating new
NVs, select the object that the NVs should be allocated to.

NOTE: Even if NVs are grouped in certain self-defined objects, all NVs belong
to one controller.

Delete NV/LON Object


NOTE The network interface should be changed as little as possible. Therefore
deleting NVs should be as few as possible. NVs can only be deleted in the
logical LON-bus part of the network tree. When removing the LON attribute
or changing the NV type in the Datapoint Editor view, a NV will not be

EN2Z-0937GE51 R0518 1312


CARE LONWORKS NETWORK ENGINEERING

deleted. NVs from the Node object can be deleted on no account (refer to
Changes on the Network Interface/CARE Application section).

Procedure 1. In the logical LON-bus part of the network tree, click on the NV/LON
object you want to delete.

2. Click menu item Controller, then submenu item Lon and Delete LON-object/NV.

Or, click Delete icon .

RESULT: The NV/LON object is deleted from the tree.

NOTE: The Node and the controller objects cannot be deleted.

Build Conversion Table


Purpose When mapping datapoints to NVs a conversion between NV and datapoint
values can be done. Therefore two conversion table types are known, the
discrete and the linear characteristic conversion tables. It can be used for
both, input and output NVs. But, value conversions are direction sensitive:
Value conversions for input NVs cannot be used for output NVs and vice
versa. In addition the NV type, e.g. SNVT_hvac_mode must match. For a
single NV max. one conversion table, characteristic or discrete, can be
used. A conversion table either for input NVs or output NVs is always
applied to the whole controller – in other words, each controller needs its
own conversion tables.
By default pre-defined conversion tables are shipped with CARE. In
addition own conversion tables can be created.

The following conversions are possible:

NV Datapoint
Analog Discrete
Discrete Discrete

Procedure 1. In the logical LON-bus part of the network tree, click on the controller.

2. Click menu item Controller, then submenu item Lon and Value Conversion
Table.

Or, click Conversion tables icon .

RESULT: The Value Conversion Table dialog box displays.

1313 EN2Z-0937GE51 R0518


LONWORKS NETWORK ENGINEERING CARE

3. To build a new conversion table, click the New button and enter a name into the
Name field.

4. From the Direction drop-down listbox, select whether the conversion direction is
from NV to datapoint, then select Input, or from datapoint to NV, then select
Output.

5. From the NV-Type drop-down listbox, select the NV type.

6. From the VC-Type (value conversion type) drop-down listbox, select type. It can
be of analog or discrete type.

RESULT: When a discrete NV type was selected and the direction is


Input, the Value Conversion Table dialog box displays as
follows:

EN2Z-0937GE51 R0518 1314


CARE LONWORKS NETWORK ENGINEERING

The NV value column displays the discrete LON states. In the


DP value column, you can enter the corresponding values the
datapoint should have. The conversion is characterized by the
= operator which means that each discrete state of the NV
corresponds to a defined discrete state indicated by its number
of the mapped datapoint.

7. To discard a value, select cell and empty the cell by pressing the EmptyCell
button.

IMPORTANT
Depending on the datapoint type that is mapped to the NV, the conversion
table values of the datapoint are processed differently for the mapped
point. The following tables give examples how the entered values will be
processed by CARE:

Discrete NV mapped to digital datapoint

Operator NV value Entered datapoint (DP) value Processed value in mapped datapoint
= HVAC_AUTO 1 ON
= HVAC_HEAT 5 OPERATION
= HVAC_MRNG_WR 3 MALFUNCTION
= HVAC_COOL 9 PRESENT
= HVAC_NIGHT_PU 10 OPERATING
= HVAC_PRE_COOL 6 OPEN
= HVAC_OFF 2 OFF
= HVAC_TEST 8 STAGE N
= HVAC_EMERG_HE 4 ALARM
= HVAC_FAN_COIL 7 CLOSED

When building a conversion table using a discrete NV type the corresponding


datapoint values are assigned by entering the state numbers into the DP column. If
there is no DP value assigned, the NV value will be deleted later when the NV is
mapped to the datapoint. If a value greater than the max. states number is entered,
e.g. 12 for the above example, this number is displayed in the Value Conversion
field.

RESULT: When an analog NV type was selected and the direction is


Input, the Value Conversion Table dialog box displays as
follows:

1315 EN2Z-0937GE51 R0518


LONWORKS NETWORK ENGINEERING CARE

For analog NV types, e.g. UNVT_byte, a Characteristic or


discrete Level Map can be selected. When using a
characteristic the Value Conversion Table dialog box
displays as follows:

Analog NV with characteristic mapped to analog datapoint

NV value Entered datapoint (DP) value


0 0
10 100

When the NV is mapped to an analog datapoint, the entered values for the datapoint
will be processed depending on the engineering unit as follows:

EN2Z-0937GE51 R0518 1316


CARE LONWORKS NETWORK ENGINEERING

If the engineering unit has no digits after the colon, the values will be rounded and
the digits entered after the colon are cut. If the engineering unit has digits after the
colon the digits are considered as they were entered.

When using a discrete Level Map, the Value Conversion Table dialog box displays
as follows (next page):

When building a conversion table using an analog NV type and converting it via
discrete level map the corresponding datapoint values are assigned by entering the
state numbers into the DP column. If there is no DP value assigned, the NV value
will be deleted later when the NV is mapped to the datapoint.

IMPORTANT
Note that the operator for the NV values is >=

Analog NV mapped to digital datapoint with discrete level map

Operator NV value Entered datapoint (DP) value Processed value in mapped datapoint
< -40 1 Sensor Break
>= -40 2 Heating OFF
>= 30 3 Heating ON
>= 110 4 Malfunction

8. When finishing the conversion table, click OK to confirm.

1317 EN2Z-0937GE51 R0518


LONWORKS NETWORK ENGINEERING CARE

Copy Conversion Table


Purpose To copy a conversion table from one LON device to one or multiple other
LON devices. A conversion table can be assigned to each kind of LON
device but only an Excel 500/800 controller is able to analyze the data. For
detailed information on conversion table creation and usage, please refer to
the Build Conversion Table section. The Copy function for Conversion
tables is also available in the device library.

Procedure 1. In the logical LON-bus part of the network tree, click on the LON device
of which conversion table you want to copy.

2. Click right mouse button and with left mouse button click on Copy Value
Conversion Table in the context menu.

RESULT: The Select Conversion Table dialog box displays showing


the following conversion table properties column wise:

Name
Name of the conversion table

Direction
IN (input) = value conversion table was created for inputs,
or OUT (output) = value conversion table was created for
outputs,

NV Type
e. g. SNVT_hvac_mode

VC Type
Type of the value conversion table, discrete or linear
characteristic
Description
Additional information about the value conversion table.

EN2Z-0937GE51 R0518 1318


CARE LONWORKS NETWORK ENGINEERING

In the Copy column by default all conversion tables are


checked for copying. To uncheck a selected conversion
table, click the check bar. To uncheck all conversion tables,
click the icon at the top. To check all conversion tables,
click the icon at the top.

3. Click the Next button.

RESULT: The Select Target Devices dialog box displays all devices of
the project as they are arranged in the system. A hierarchical
tree structure can be expanded to view all devices.

1319 EN2Z-0937GE51 R0518


LONWORKS NETWORK ENGINEERING CARE

4. Click on the device to which the conversion table should be copied.


Multiselection is possible by concurrent usage of the STRG key.

5. Click the Finish button.

RESULT: The Select Target Devices dialog box closes and the
conversion table was copied to the selected target devices.

EN2Z-0937GE51 R0518 1320


CARE LONWORKS NETWORK ENGINEERING

Onnet Tuning
Prerequisites To perform onnet tuning you must have installed the corresponding PC-
LON-interface (SLTA 10, PCLTA-10 FT-10, PCLTA-20 PCI 20, LonDongle)
and drivers from Echelon on the PC and the connection between PC and
the LonWorks network via COM1 or COM2 must be established (see
Echelon documentation).

To perform onnet tuning you have to go onnet. When being onnet you can do one of
the following procedures:

• Commissioning/Decommissioning devices
• Addressing Devices
• Setting certain devices online/offline
• Resetting devices
• Winking devices
• Testing devices
• Replacing Devices
• Configuration and monitoring of devices via Plug-Ins (offline and online)
• Get online values of NVs
• Set values for NVs, SCPTs, UCPTs and NCIs
• Modify configuration parameters
• Synchronize with LNS
• Downloading Firmware

IMPORTANT
Certain functions are restricted respectively workarounds have to be
applied if a Synchronization with LNS is to be considered and a LNS tool is
used in parallel for the LonWorks network engineering. For detailed
information, please refer to the Synchronize with LNS section.

Go Onnet
Going onnet is the first step before any onnet tuning procedure can be done.

Procedure 1. With left mouse key, click on the LonWorks folder in the logical LON-
bus part of the network tree.

2. Click right mouse key and with left mouse key click Onnet in the context
menu.

RESULT: You are now onnet. CARE is checking the current state of all
devices in the network tree. Depending on the current state,
devices are displayed in different colors (see Status of
Devices section). The status may not instantly be visible
since it is updated in the background.

1321 EN2Z-0937GE51 R0518


LONWORKS NETWORK ENGINEERING CARE

Status of Devices
Prerequisites To view the status of devices, you have to be onnet (see Go Onnet section).

The status of a device is indicated three times:

• In the channel folder of the network tree


• In the logical LON-bus part of the network tree
• On the device located on the terminal assignment tab

EN2Z-0937GE51 R0518 1322


CARE LONWORKS NETWORK ENGINEERING

Colorfully
status display

LON device
status icon

The states can be described via the following table:

Status of Device
Color Half-colored Fully-colored
(Different status of CARE and device, (Same status between CARE and
Updates pending) device)
White Unknown, not initialized
Green Application is running
Red Not available (damaged), applicationless

Go Offnet
To work offline, you have to go offnet in CARE.
Procedure 1. With left mouse key, click on the LonWorks folder in the logical LON-
bus part of the network tree.

2. Click right mouse key and with left mouse key click Offnet in the context
menu.

RESULT: You are now offnet. All devices in the network tree are
displayed in fully or half-white depending on their status.

1323 EN2Z-0937GE51 R0518


LONWORKS NETWORK ENGINEERING CARE

Address Device
Prerequisites You have to be onnet (see Go Onnet section).

Addressing is the first step of the commission procedure. Addressing can be done
by

• Entering the neuron ID on the device


• Get the neuron ID by pressing the service pin
• Uploading devices by scanning the network

Enter Neuron ID on Device

Procedure 1. With right mouse key, click on the device on the terminal assignment
tab.

2. With left mouse key, click on Modify Neuron ID in the context menu.

EN2Z-0937GE51 R0518 1324


CARE LONWORKS NETWORK ENGINEERING

RESULT: The Modify Neuron ID dialog box displays.

3. Enter the neuron ID for the device and confirm by clicking OK.

RESULT: The neuron ID is assigned to the device and displayed on


the bottom of the device.

1325 EN2Z-0937GE51 R0518


LONWORKS NETWORK ENGINEERING CARE

Get Neuron ID by Pressing Service PIN

If the neuron ID is not known, it can be get by pressing the service pin at the
device.

Procedure 1. In the logical LON-bus part of the network tree, click on the device.

2. Click right mouse key and with left mouse key, click on Get Service Pin in the
context menu.

RESULT: The Get Service Pin:<name of device> dialog box is


displayed.

3. Press the service pin at the device.

RESULT: The dialog box is closed. The neuron ID is assigned to the


device and displayed on the bottom of the device.

Scan Network

With this function CARE automatically uploads all devices to the network tree
residing on the current domain that is set on the LonWorks folder properties tab. For

EN2Z-0937GE51 R0518 1326


CARE LONWORKS NETWORK ENGINEERING

example, these can be devices from another project. The current states and
configurations of the uploaded devices are indicated by the appropriate color (see
Status of Devices section).

Procedure 1. In the network tree, click on the LON-Works folder.

2. Click right mouse key and with left mouse key, click on Scan Lon-Network.

RESULT: The network is scanned and devices are uploaded and add
to the network tree. When scanning the network the first
time, an Uploaded Devices folder is created and the
uploaded devices will be put in there. All devices show a
half-colored status that means that they need to be
addressed and/or commissioned.

Already uploaded devices will not be uploaded twice during


further scanning.
They can be moved to other folders in the logical LON-bus
part of the network tree.

Commission Device(s) It is possible to commission a single device or all devices of a system (top
level system such as the Default System or subsystem) or the complete
LonWorks network.

When commissioning all devices of a system or the network, only those devices will
be commissioned which network interface, configuration or bindings had been
changed in CARE since the latest commissioning, that is, the current state of the
device is different to the current state in CARE.

NOTE: When performing onnet binding changes (hotbinding) on devices other


than Excel 50/500/800 controllers, the devices are instantly
commissioned. When performing offnet binding changes on devices other
than Excel 50/500/800 controllers, you must go onnet again and
commission, respectively recommission the corresponding devices again.
Excel 50/500/800 controllers need to be commissioned, respectively
recommissioned again in any case.

Prerequisites Devices must be addressed (see Address Device section) and you have to
be onnet (see Go Onnet section).

Procedures A) Commission all devices of the network

1. With left mouse key, click on the LonWorks folder in the logical LON-
bus part of the network tree.

2. Click right mouse key and with left mouse key click Commission in the
context menu.

RESULT: For any device, which is not addressed yet, the Get Service
Pin dialog box displays asking you to press the service pin.
Press the service pin and Click OK. After all devices have
been addressed, they will be commissioned. Commissioned
devices are indicated by the fully colored green display of the
devices in the network tree as well as on the device status
icon on the devices.

B) Commission all devices of a system (top level or subsystem)


1. With left mouse key, click on the system folder (top level = Default
System or another individually named subsystem folder) in the logical
LON-bus part of the network tree.

1327 EN2Z-0937GE51 R0518


LONWORKS NETWORK ENGINEERING CARE

2. Click right mouse key and with left mouse key click Commission in the
context menu.

RESULT: For any device, which is not addressed yet, the Get Service
Pin dialog box displays asking you to press the service pin.
Press the service pin and Click OK. After all devices have
been addressed, they will be commissioned. Commissioned
devices are indicated by the fully colored green display of the
devices in the network tree as well as on the device status
icon on the devices.

C) Commission single device

1. With left mouse key, click on the device in the logical LON-bus part of
the network tree.

2. Click right mouse key and with left mouse key, click Commission in the
context menu.

RESULT: If the device which is not addressed yet, the Get Service Pin
dialog box displays asking you to press the service pin.
Press the service pin. After the device has been addressed,
it will be commissioned. The commissioned devices are
indicated by the fully colored green display of the device in
the network tree as well as on the device status icon on the
device.

Recommission All Devices It is possible to recommission devices of a system (top level system such as
the default System or subsystem) or the complete LonWorks network.

When recommissioning all devices of a system or the network, all devices will be
commissioned despite of their current states. That means, that even those devices
will be commissioned of which network interface, bindings or configuration had not
been changed since the latest commissioning.

NOTE: When performing onnet binding changes (hotbinding) on devices other


than Excel 50/500/800 controllers, the devices are instantly
commissioned. When performing offnet binding changes on devices other
than Excel 50/500 controllers, you must go onnet again and commission,
respectively recommission the corresponding devices again. Excel
50/500/800 controllers need to be commissioned, respectively
recommissioned again in any case.

Prerequisites Devices must be addressed (see Address Device section) and you have to
be onnet (see Go Onnet section).

Procedures A) Recommission all devices of the network


1. With left mouse key, click on the LonWorks folder in the logical LON-
bus part of the network tree.

2. Click right mouse key and with left mouse key click Recommission All in
the context menu.

RESULT: For any device, which is not addressed yet, the Get Service
Pin dialog box displays asking you to press the service pin.
Press the service pin and Click OK. After all devices have
been addressed, they will be recommissioned.
Recommissioned devices are indicated by the fully colored
green display of the devices in the network tree as well as on
the device status icon on the devices.

B) Recommission all devices of a system (top level or subsystem)

1. With left mouse key, click on the system folder (top level = Default
System or another individually named subsystem folder) in the logical
LON-bus part of the network tree.

EN2Z-0937GE51 R0518 1328


CARE LONWORKS NETWORK ENGINEERING

2. Click right mouse key and with left mouse key click Recommission All in
the context menu.
RESULT: For any device, which is not addressed yet, the Get Service
Pin dialog box displays asking you to press the service pin.
Press the service pin and Click OK. After all devices have
been addressed, they will be recommissioned.
Recommissioned devices are indicated by the fully colored
green display of the devices in the network tree as well as on
the device status icon on the devices.

Decommission Device Single devices can be decommissioned which results in an unconfigured


"virgin" device.

NOTE: Routers have not to be decommissioned.

Prerequisites The device must be commissioned (see Commission Device(s) section) and
you have to be onnet (see Go Onnet section).

Procedure 1. With left mouse key, click on the device in the logical LON-bus part of
the network tree.

2. Click right mouse key and with left mouse key click Decommission in
the context menu.

RESULT: The device is decommissioned indicated by a half-colored


white display.

Set Device(s) Offline/Online


Devices can be set online/offline. Setting devices offline means that the device is
switched into a kind of "Standby mode". In this mode, the communication between
the application and the neuron chip of the device is interrupted and the device sends
no data on the bus. Setting devices offline is helpful, for example, in order to avoid
interfering bus traffic when testing particular sections/devices of the network. You
can set all devices or a certain device offline/online.

Prerequisites Devices must be addressed (see Address Device section) and you have to
be onnet (see Go Onnet section).

Procedures A) Set all devices offline/online

1. With left mouse key, click on the top level (e.g. Default System) folder
of the logical LON-bus part in the network tree.

2. Click right mouse key and with left mouse key,

click Set devices offline in the context menu, if you want to set all devices
offline, respectively

click Set devices online in the context menu. if you want to set all
devices online.

RESULT: All devices are set offline, respectively online. Each device
set offline, is displayed in fully or half-white color. Each
device set online, is displayed in its original color (see Status
of Devices section).

B) Set single device offline/online

1. With left mouse key, click on the device in the logical LON-bus part of
the network tree.

2. Click right mouse key and with left mouse key,

click Set device offline in the context menu, if you want to set the device offline,

1329 EN2Z-0937GE51 R0518


LONWORKS NETWORK ENGINEERING CARE

respectively

click Set device online in the context menu. if you want to set the device
online.

RESULT: The device is set offline, respectively online. A device set


offline, is displayed in fully or half-white color. A device set
online, is displayed in its original color (see Status of Devices
section).

Reset Device(s)
Resetting a device means an application restart in the device.

Prerequisites Devices must be commissioned (see Commission Device(s) section) and


you have to be onnet (see Go Onnet section).

Procedures A) Reset all devices


1. With left mouse key, click on the LonWorks folder or on the top level
(e.g. Default System) folder of the logical LON-bus part in the network
tree.

2. Click right mouse key and with left mouse key, click Reset in the context menu.

RESULT: The application in each device will be restarted.

B) Reset single device

1. With left mouse key, click on the device in the logical LON-bus part of
the network tree.

2. Click right mouse key and with left mouse key, click Reset in the context menu.

RESULT: The application in the node will be restarted.

Wink Device(s)

NOTE: The device must support the wink command feature.

Prerequisites Devices must be commissioned (see Commission Device(s) section) and


you have to be onnet (see Go Onnet section).

Procedures A) Send Wink to all devices


1. With left mouse key, click on the LonWorks folder or on the top level
(e.g. Default System) folder of the logical LON-bus part in the network
tree.

2. Click right mouse key and with left mouse key, click Wink in the context menu.

RESULT: A Wink command has been sent to the selected devices.

B) Send Wink to single device


x
1. With left mouse key, click on the device in the logical LON-bus part of
the network tree.

2. Click right mouse key and with left mouse key, click Wink in the context menu.

RESULT: A wink command has been sent to the selected device.

EN2Z-0937GE51 R0518 1330


CARE LONWORKS NETWORK ENGINEERING

Test Device(s)
Prerequisites Devices must be commissioned (see Commission Device(s) section) and
you have to be onnet (see Go Onnet section).

Procedures A) Test all devices

1. With left mouse key, click on the LonWorks folder or on the top level
(e.g. Default System) folder of the logical LON-bus part in the network
tree.

2. Click right mouse key and with left mouse key, click Test in the context menu.

RESULT: The commission and online state for all devices will be
checked and updated. View state changes on the
Properties tab of the corresponding devices and note
eventual color changes of the devices in the logical LON-
bus part of the network tree.

B) Test a single device

1. With left mouse key, click on the device in the logical LON-bus part of
the network tree.

2. Click right mouse key and with left mouse key, click Test in the context menu.

1331 EN2Z-0937GE51 R0518


LONWORKS NETWORK ENGINEERING CARE

RESULT: The commission and online state for the device will be
checked and updated. View state changes on the
Properties tab of the corresponding device and note
eventual color changes of the device in the logical LON-
bus part of the network tree.

Replace Device
In case a device has been replaced physically, it must be replaced in CARE too.
Devices must match each other, that is, their program IDs must correspond.
Prerequisites Devices must be addressed (see Address Device section) and you have to
be onnet (see Go Onnet section).

Procedure 1. In the logical LON-bus part of the network tree, click on the device, you
want to replace.

2. Click right mouse key and with left mouse key, click Replace Device.

RESULT: The Replace Device dialog box is displayed.

In the Status field, the current status and in the Neuron ID


field, the neuron ID of the device to be replaced is
displayed. The device will be decommissioned.

3. Click the Get Service Pin button.

RESULT: The Get Service is displayed.

EN2Z-0937GE51 R0518 1332


CARE LONWORKS NETWORK ENGINEERING

4. At the new device, press the service pin button.

RESULT: The neuron ID of the new device is displayed in the Neuron


ID field.

5. Click OK to finish the replacement.

Upload Parameters
It is possible to upload the current configuration parameters into CARE from:

• all devices of the complete LonWorks network


• all devices of a system (top level system such as the Default System or
subsystem)
• a single device

If CARE is in LNS controlled mode, the parameters will be uploaded from the device
via LNS database.

Prerequisites Devices must be addressed (see Address Device section) and you have to
be onnet (see Go Onnet section).
Procedures A) Upload parameters from all devices of the complete network

1. With left mouse key, click on the LonWorks folder in the logical LON-
bus part of the network tree.

2. Click right mouse key and with left mouse key click Upload Parameters
in the context menu.

RESULT The current parameters from all devices of the complete


network will be uploaded into CARE.

B) Upload parameters from all devices of a system (top level or


subsystem)

1. With left mouse key, click on the system folder (top level = Default
System or another individually named subsystem folder) in the logical
LON-bus part of the network tree.

2. Click right mouse key and with left mouse key click Upload Parameters
in the context menu.

1333 EN2Z-0937GE51 R0518


LONWORKS NETWORK ENGINEERING CARE

RESULT: The current parameters from all devices residing in the


selected system will be uploaded into CARE.
C) Upload parameters from a single device

1. With left mouse key, click on the device in the logical LON-bus part of
the network tree.

2. Click right mouse key and with left mouse key, click Upload Parameters
in the context menu.

RESULT: The current parameters from the selected device will be


uploaded into CARE.

Get Online Value of NV


Purpose To get the current value of a bound NV from the LON-bus.
Prerequisites Devices must be addressed (see Address Device section) and you have to
be onnet (see Go Onnet section).

Procedure 1. In the LON-Bus part of the network tree, double-click on the LON
device.

2. On the right pane, click on the terminal assignment tab to display the device.

3. Right-click on the field of the NV (terminal) and click on Set Online in the
context menu.

NOTE When moving the cursor over the field, a tool tip displays the
corresponding engineering unit.

EN2Z-0937GE51 R0518 1334


CARE LONWORKS NETWORK ENGINEERING

Right-Click

RESULT: The field gets white and the current value of the NV is
displayed.

1335 EN2Z-0937GE51 R0518


LONWORKS NETWORK ENGINEERING CARE

NOTE: When being Offnet (see Go Offnet section) and setting the NV online,
the field gets grayed and the latest value displayed will be reloaded.

Set NV Offline
Purpose To hide current value of a bound NV.
Prerequisites NV (terminal) must be in online mode.

Procedure 1. Right-click on the field of the NV (terminal) and click on the checked
“Set Online” command in the context menu.

RESULT: The field gets grayed and no value is displayed.

Set Values for NVs, SCPTs/UCPTs and NCIs

CARE allows to enter values for Input NVs (network variables), SCPTs (standard
configuration parameter types) and NCIs (network variables using the config class
keyword for configuration). Values can be entered online or offline as the following
table shows:

Input NVs NCIs SCPTs


Online + + +
Offline - + +

Set Value for NV

Prerequisites Device must be commissioned (see Commission Device(s) section) and


you have to be onnet (see Go Onnet section), respectively the device must
be online.

Procedure 1. In the LON-bus part of the network tree, click on the input NV.

2. On the right pane, click on the Value(s) tab.

3. In case the NV is structured and has components, select the component in the
Value(s) tree.

EN2Z-0937GE51 R0518 1336


CARE LONWORKS NETWORK ENGINEERING

4. In the Value field, enter the value.

RESULT: The value is written into the device.

Set Value for SCPT

For SCPTs values can be set in online or offline mode and either in the
device library of in the LON-bus part of the network tree. Values that had
been set in offline mode will be issued as soon as the device has been set
online.

Prerequisites In case you want to set the value online, the device must be commissioned
(see Commission Device(s) section) and you have to be onnet (see Go
Onnet section).

Procedure 1. In the LON-bus part of the network tree, respectively in the device
library tree, click on the SCPT.

2. On the right pane, click on the Value(s) tab and enter the value into the Value
field.

Example 8: Value input in LON-bus part of network tree


RESULT: The value is written into the device as soon as the device
is online.

1337 EN2Z-0937GE51 R0518


LONWORKS NETWORK ENGINEERING CARE

Set Value for NCI

For NCIs values can be set in online or offline mode and either in the device
library or in the LON-bus part of the network tree. Values that had been set
in offline mode will be issued as soon as the device has been set online.

Prerequisites In case you want to set the value online, the device must be commissioned
(see Commission Device(s) section) and you have to be onnet (see Go
Onnet section).

Procedure 1. In the LON-bus part of the network tree, respectively in the device
library tree, click on the NCI.

2. On the right pane, click on the Value(s) tab and enter the value into the Value
field, respectively select the value from the drop-down listbox.

Example 9: Value input in device library tree

RESULT: The value is written into the device as soon as the device
is online.

Integrate Third Party Devices


Main Steps The integration of third party devices includes the following main steps:

1. Import the XIF file into the device library (see Add LON Device to the
Network section)
2. Add the device to the NI channel in the network tree (see Add LON
Device to the Network and Set Network Interface Channel sections)
3. Install the plug-in for the device
4. Go onnet and start the plug-in (see Plug-In Online Functions in
CARE Controlled Mode section)

Troubleshooting on Errors If the device library import has any errors importing a 3rd party device, the
object
during Import into the Device Libraryserver log will capture the errors if the TRACE=1 is added under the object
server header in the CARE.INI file.

Troubleshooting on unknown CPs When starting the plug-in (step 4), some unknown CPs may not be
identified and displayed properly. Those CPs will be listed in a log file which
is displayed when invoking the plug-in. The unknown status can also be
viewed as Description on the Properties tab by clicking on the device in the
network tree.

EN2Z-0937GE51 R0518 1338


CARE LONWORKS NETWORK ENGINEERING

Example: Description and value of an unknown CP

If unknown CPs were detected, please check whether they should be used
in your application or not.

If the CPs will not be used at all, you can ignore the message and no further actions
have to be done.

If you want to use unknown CPs, it is recommended to send the drf file set to the
Honeywell Technical Assistant Center (TAC) in Schönaich.

TAC will check the drf file set and update the NVT_list.ltc file with proper CP
information for the corresponding device.

1. After receiving the updated NVT_list.ltc file, do the following:

2. Copy the updated NVT_list.ltc file to the CARE folder.

RESULT: The current NVT_list.ltc file will be overwritten.

NOTE: The current NVT_list.ltc file version can be viewed in the


NV Type List Version field of the Default LON Properties
dialog box (see "Set Global Options" section).

3. Backup the database by clicking menu item Database, then


submenu item Backup.

4. Restore the database by clicking menu item Database, then


submenu item Restore.

RESULT: From now on, CARE will use the updated NVT_list.ltc file.

IMPORTANT
Before you continue to work with the new and proper CP information
(updated NVT_list.ltc file), delete the corresponding device in the device
library and in the network tree. Then add the device to the device library
and to the network tree again.

1339 EN2Z-0937GE51 R0518


LONWORKS NETWORK ENGINEERING CARE

CARE and LNS


In large installations with several different crafts e.g. HVAC, security or light, LNS is
used as common standard. CARE supports LNS by providing the transfer of binding
and configuration information of a LonWorks network from CARE to LNS via the
Synchronize with LNS mechanism.

Synchronize with LNS


Purpose The Synchronize with LNS mechanism (LNS Controlled mode) allows the
incremental updating of the LNS database with changed information done
in CARE.

The communication between CARE and the LNS database can be in the following
ways:

• Remote mode via LAN: CARE and LNS-based software including the
LNS database are on different PCs.
• Local mode: CARE and the LNS database is on the same PC.

In LNS controlled mode, CARE has no longer commissioning control on the remote
network. Instead the LNS-based software controls and commissions the network.

Synchronization in LNS Controlled Mode

CARE PC REMOTE PC
LonWorks LonWorks

LOCAL Connection CARE LAN Connection

LNS Server LNS-based Software (e.g. EBI)

LNS CARE LNS


SYNCHRONIZE SYNCHRONIZE
database database database

The most common way is the remote mode with two different PCs, one
client PC with CARE running (CARE PC) and another host PC (Remote
PC) with an LNS-based application such as EBI, SymmetrE or LonMaker
running on it. The PCs communicate via LAN remotely.

To setup a proper working system, the following requirements must be fulfilled:

Assumptions and Prerequisites Remote Mode

CARE PC
Fully licensed CARE 8.xx.xx and LNS 3.23 turbo must be installed. CARE must be
running.

Remote PC
LNS 3.23 turbo and Remote Sync Server (RSS) must be installed. Normally these
two software applications come with EBI and SymmetrE.

On the remote PC Make sure that sufficient LNS credits are available for the LON
devices included in the CARE project (see LNS Credits Handling section).

EN2Z-0937GE51 R0518 1340


CARE LONWORKS NETWORK ENGINEERING

Ask the I.T administrator for the remote PC address, host name or IP address, and
port number and note it down.

IMPORTANT
By default, for LNS, ports 2540 and 2541, for RSS port 3500 will be used.
These ports must be opened in the PC firewall to ensure proper remote
operation.

Local Mode
Fully licensed CARE 8.xx.xx and LNS 3.23 turbo must be installed. CARE
must be running.

On the CARE PC, make sure that sufficient LNS credits are available for the LON
devices included in the CARE project (see LNS Credits Handling section).

IMPORTANT
For all LON devices which are not included in the CARE device library by
default, you must provide the corresponding XIF files for LNS
synchronization.

Multiple Bindings (Group Binding) and Address Table Entries Allocation

Group Binding may cause problems during Syncronize. Please notice the Default
LON Properties tab description in the Set Global CARE Options section for more
information.

Procedures

Remote PC (LAN Mode) 1. Start Windows control panel and double-click on the Remote Sync
Server icon in the control panel.

RESULT: The Remote Sync Server Configuration dialog box


displays.

1341 EN2Z-0937GE51 R0518


LONWORKS NETWORK ENGINEERING CARE

2. In the New Password field, enter the password.

3. In the Confirm New Password field, enter the same password.

4. In the Port Number field, keep the default port number 3500.

IMPORTANT
Make sure that the server port number displayed by default, has been
enabled by the I.T. administrator. If the I.T. administrator has enabled
another port, enter the provided port number.

5. Note down the password, the port number, and the server address (IP or host
name) for later use on the CARE PC.

6. Under Remote Sync Server, click the Start radio button if the service is stopped.

7. Click the Close button.

CARE PC (Local Mode and LAN Mode)1. In the physical LON bus part of the network tree, click on LonWorks.

EN2Z-0937GE51 R0518 1342


CARE LONWORKS NETWORK ENGINEERING

2. On the Properties tab on the right, set the following settings:

Check the LNS Controlled checkbox. In LNS controlled mode, CARE has no
longer commissioning control. Instead LNS controls and commissions the
network.

Check the CARE Controlled Flow Parameters for Honeywell VAV2 Devices
checkbox if want to update the LNS database with the current CARE values of
the flow parameters ´duct area`, ´flow setpoint minimum` and ´flow setpoint
maximum`.

In the NV Poll Interval, enter the interval in s by which all NVs will be polled by
the EBI LON point server. For each NV, the poll interval can also be set
individually (see "EBI Settings" section).

3. Click the Extended LNS Options button.

RESULT: The LNS Options dialog box displays.

1343 EN2Z-0937GE51 R0518


LONWORKS NETWORK ENGINEERING CARE

4. Under Connection, click the LAN radio button, if CARE and the LNS-based
software including the LNS database are on different PCs.
Or, click on the Local radio button, if CARE and the LNS database is on the
same PC.

5. From the LNS Network Name drop-down listbox, select the LNS network name.
It is defaulted to the same name as the project.

6. To create a LNS network other than the default, click the New button.

RESULT: The New LNS Network dialog box displays.

IMPORTANT FOR LAN CONNECTION


During testing it may be typically that multiple networks have been opened
on the remote PC. Because LNS does not allow having multiple remote
LAN connections, the following message displays if the networks are
different:

EN2Z-0937GE51 R0518 1344


CARE LONWORKS NETWORK ENGINEERING

To resolve the conflict, manually shut down all LNS databases on the
remote PC and make sure that only one single network and the same
network is opened on the remote PC as on the CARE PC. Having one and
the same network on the CARE and the remote PC is presumed for an
error-free running in normal operation mode (see also CARE and EBI
Upgrades section).

7. Enter a name in the Network Name field.

8. Click the OK button.

9. From the Local LNS NI drop-down listbox, select the network interface
that LNS should use for connection to the LON network.

10. From the LNS NI Channel drop-down listbox, select the NI (network interface)
channel that LNS should use for connection to the LON network (locally or
remotely). The NI channel is the segment of a LON network where CARE/LNS
is physically connected to.

Note that the network interface channel on the CARE and Remote PC can be
different. Often EBI on the remote PC may be connected to the backbone and
CARE PC is connected to another channel.

11. Under Domain Settings, set the Id size in bytes format the Id Size field and
enter the domain Id into the ID field. If you want to get a randomly generated
domain ID, click the Generate Domain ID randomly button. In this case the Id
Size previously selected must be higher than 0. It is recommended to use a
different domain as in the CARE project.

12. Under CARE Remote Configuration, enter the host name or IP address
of the remote PC into the Hostname / IP field.

13. In the Port Number field, enter the same port number as defined in RSS
application (see steps 1 to 6 of the Remote PC Procedure) on the remote PC.

14. In the Password field, enter the same password as defined in RSS application
(see steps 1 to 6 of the Remote PC Procedure) on the remote PC.

15. Click the Load Remote NI (network interface) button, to enable the selection of
the remote LNS NI from the drop-down listbox. By clicking the Load Remote NI
button CARE automatically checks the communication between the CARE PC
and the Remote PC. In case the communication works properly, the network
interface of the remote PC can be selected from the Remote LNS NI drop-down
listbox. In the Status line, the current status and errors that may occurred are
displayed.

1345 EN2Z-0937GE51 R0518


LONWORKS NETWORK ENGINEERING CARE

16. Click the OK button.

RESULT: The settings are saved. Whenever starting the


synchronize process from now on, CARE will use the
settings defined here.

17. Click the Synchronize with LNS icon on the toolbar.


Or, click on the LON-Works folder in the network tree, the click right mouse
button and with left mouse button click on Synchronize with LNS in the context
menu.

EN2Z-0937GE51 R0518 1346


CARE LONWORKS NETWORK ENGINEERING

RESULT: The LNS Network Synchronization dialog box displays.


On the top the network status is displayed by connection
type (LAN, Local) and the network name. The /
plug icon status indicates whether the network interface of
the remote PC is physically connected to the network
or not respectively whether it is working properly or
not.

In the second line, the number of inconsistent database


items to be synchronized, and the number of credits
needed for synchronization as well as the number of
available credits are listed (see LNS Credits Handling
section).

In the third line on the right, the estimated time to execute


the synchronize process is shown.

IMPORTANT
CARE cannot consider manipulations of the LNS database
done with 3rd party LNS-based software. To get those kind of
changes reported, please use the Consistency Check function
(see Consistency Check section).

In the list, the name of the inconsistent database items


and the corresponding operation to be executed are
listed.

1347 EN2Z-0937GE51 R0518


LONWORKS NETWORK ENGINEERING CARE

18. To start Synchronizing, click the Start Sync button.

EN2Z-0937GE51 R0518 1348


CARE LONWORKS NETWORK ENGINEERING

RESULT: The inconsistent items will be synchronized. Successful


execution of an operation is indicated by a green
checkmark. Abortive execution is indicated by a red cross
and the status/reason in described In the Status column.
Successfully modified devices are automatically set to
online. Changes made in EBI during synchronization are
not written to the devices until the synchronization has
been finished.

Abortive execution messages are displayed in parallel in


the LNS Synchronization dialog box.

1349 EN2Z-0937GE51 R0518


LONWORKS NETWORK ENGINEERING CARE

19. To print the status messages, click the Print button, then click the Close button.

20. To perform a successful synchronization, solve the problems as described in


the status messages and synchronize again.

RESULT: A successful synchronization is indicated by an empty


items list and the message “ LNS is synchronized” in the
LNS Network Synchronization dialog box.

Controller Application When starting Synchronization, CARE verifies whether the currently running
Verification Note applications in the controllers are consistent with the applications to be
used for synchronization. In case of application inconsistencies, the
following message box displays.

Click the OK button. To make the applications consistent, translate the controller
and download the application into the controller.

In case LNS cannot read the controller version due to communication problems or
an uncommissioned network, the following message box displays.

EN2Z-0937GE51 R0518 1350


CARE LONWORKS NETWORK ENGINEERING

Click the OK button. Connect the controller to the network. Download the correct
application into the controller and commission the network.

Available Functions and RestrictionsWhen CARE is in the Synchronized mode by checking the LNS controlled
option on the LON-Works Properties tab, you cannot apply any of the
following onnet functions:

• LON network scanning


• Set device offline/online
• Commission device/network
• Recommission complete network
• Decommission device
• Replace device
• Test device
• Upload Parameters directly into CARE

In synchronized mode, the following CARE functions are still available when being
onnet:

• Get service pin


• Reset device
• Wink device
• Monitor NV values (in NI Channel only)

Create LNS Device Template


For proper LNS synchronization, the LNS database must include all device
templates of the LON devices included in the project. A template will be created
during Plug-In registration or by importing the information from the XIF file. For all
currently available Honeywell Plug-Ins/LON devices, CARE provides an "empty"
template database that includes the corresponding device templates. Hence, during
LNS Synchronization, separate Plug-In registration or importing XIF file information
is not necessary.
Device templates of 3rd party devices are not saved in the template database.
During the first LNS synchronization of the project, those device templates will be
registered in a separate step per device in any case. After the first synchronization,
all created device templates, Honeywell device templates and 3rd party device
templates are saved with the project.

During Synchronization for any device type, which no device template has been
created for in the LNS database, the Create LNS Device Template dialog box
displays. The device template can be created either by the Plug-In registration or
importing XIF file information.

1351 EN2Z-0937GE51 R0518


LONWORKS NETWORK ENGINEERING CARE

Create Template by Plug-In Registration 1. Click the By Plug-In button, if you want to create the device
template by registering the plug-in.

RESULT: The Plug-In Registration dialog box displays.

2. In the "Not Registered" list, select desired plug-in(s) and click Add button.

RESULT: The plug-in is added to the "To Be Registered" list.

3. Click Register button.

RESULT: The registration process starts and creates the device


template.

4. Confirm message boxes, which might be generated and displayed by the plug-
in.

NOTE: A plug-in, which is already registered as listed under the "Already


Registered" list, can be reregistered in case it does not work properly.
To reregister a plug-in, select it in the "Already Registered" list, add it
to the "To Be Reregistered" list by clicking the Add button and click
Register button.

Create Template from XIF File 1. Click the From XIF button, if you want to create the device template by
using XIF file information.
RESULT: The Open XIF File dialog box displays.

2. Browse to folder where the XIF file is saved.

3. Select the XIF file in the list and click Open button.

RESULT: The device template is created by using XIF file information.

Resynchronize Complete LNS Network

Purpose To synchronize the complete LNS network not only inconsistent LON
information.

Local Delete the LNS project on the CARE PC and synchronize again (see Delete
LNS Projects section).

Remote Delete LNS project manually on the Remote PC and synchronize again.

Consistency Check
Purpose To verify whether the CARE database and the LNS database are consistent
or not. Especially to check if the LNS database has been modified with
another LNS-based application (e.g. LonMaker) which causes manual re-
engineering to be done in CARE.

CARE compares the following items:

• CARE and LNS database versions


• Channel, subsystem definitions
• Devices and device interfaces
• Parameters
• Bindings
• Additional or other items in LNS database than in CARE database

NOTE: It is recommended to perform a consistency check after a synchronization


and not before, in order to minimize the detectable inconsistencies.

EN2Z-0937GE51 R0518 1352


CARE LONWORKS NETWORK ENGINEERING

In some cases it may need a resynchronization of the project to get


consistent. But a consistency check may take the same amount of time or
more than a resynchronization of the project. Changes of device statuses
(e.g. from online to offline), NV values (except CPs and NCIs) are not
considered to be relevant.

Procedure 1. In the toolbar, click the Consistency Check icon .

RESULT: The Consistency Check dialog box displays.

On the top the network status is displayed by connection


type (LAN, Local) and the network name. The /
plug icon status indicates whether the network interface of
the remote PC is physically connected to the network
or not respectively whether it is working properly or
not.

2. Click the Check Configuration Parameters checkbox, if you want to check the
configuration parameters in addition. Note, that this takes additional time.

NOTE: The Click the Display Cross Reference option is for internal use only.

3. Click the Run Check button.

RESULT: Status of analyzing is displayed in the Status field above


the lists areas. On the left list area, the analyzed network
is displayed as hierarchical structure. If all items of the
network are consistent the components are displayed in
green. If at least one item is not inconsistent, the network
name icon is displayed in red.

1353 EN2Z-0937GE51 R0518


LONWORKS NETWORK ENGINEERING CARE

On the right list area, by default the analyzed items of the


highest tree level, that is, the network, are displayed by
Name, LNS Value, CARE Value and Comment.
Consistent items are indicated by a green checkmark,
inconsistent items are displayed by a red cross and a
corresponding comment.

To display analyzed items of lower network components,


select the corresponding component in the tree on the left.

When consistency check is finished, the message “End of


Report” is displayed in the Status field above the report
list.

4. Click the Save button and save the report as csv. file.

5. Print the report and resolve the conflicts described in the report either by
manual operation in CARE or by LNS-based software usage on the LNS
database.

6. Click the Cancel button to close the Consistency Check dialog box.

Apply “Sandbox” Channel


Purpose To control one particular channel while LNS has control over the complete
network. This may necessary for testing purposes and starting up in case of
major structural changes of the network. Although the network is LNS
controlled, for the sandbox channel, all CARE Onnet functions can be
applied as follows:

• Set device offline/online


• Commission network/device
• Recommission network
• Decommission device
• Test device
• Replace device
• Upload Parameters directly into CARE

IMPORTANT
When setting the channel to sandbox, the devices in the channel will be
automatically decommissioned. Henc, after setting the channel to sandbox,
it is strongly recommended to commission the “ownerless” devices
immediately in order to restore normal control functionality.

EN2Z-0937GE51 R0518 1354


CARE LONWORKS NETWORK ENGINEERING

LNS Server CARE

Channel 1

in LNS Controlled
Channel 2 Make Sandbox Channel Mode

Commission network
(should be done always and

Do Modifications
immediately!)

Channel 3 Commission device


Set device offline/online
Recommission network
Decommission device
Test device
Replace device
Upload Parameters directly
into CARE

Channel 1 x

Channel 2 = Sandbox channel

Channel 3
CARE

Channel 1

Channel 2 Release Sandbox Channel


in LNS Controlled
Mode
Synchronize with LNS

Channel 3

1355 EN2Z-0937GE51 R0518


LONWORKS NETWORK ENGINEERING CARE

Restrictions Plug-ins functionality is restricted to the offline start of a plug-in. Only one
channel can be defined as sandbox channel. Devices of other channels
cannot be reached via routers and therefore bindings between devices of
different channels will not work. Routers cannot be modified or
commissioned. This will be done during the following Synchronize process.

Domain Settings It is recommended to use different domain settings as LNS.

Procedure 1. In the physical part of the LON-Works bus, click on the channel you
want to make the sandbox channel.

2. With right mouse button, click on the channel you want to make the sandbox
channel and with left mouse button click on "Sandbox" Channel in the context
menu.

3. Click right mouse button and with left mouse button click on Onnet.

RESULT: The following functions are now enabled for working on


the channel´s devices:

• Set device offline/online


• Commission network/device
• Recommission network
• Recommission device
• Test device
• Replace device
• Upload Parameters

The sandbox channel is automatically defined as NI channel.

4. Select the channel and commission the channel by selecting Commission in the
context menu.

5. Make the changes to the channel´s devices and do the testing and startup.

6. Release the channel to the normal state by disabling the “Sandbox” Channel
option in the context menu.

7. Synchronize the CARE database with the LNS database as described in the
Procedures of the Synchronize with LNS section.

EN2Z-0937GE51 R0518 1356


CARE LONWORKS NETWORK ENGINEERING

Upload Parameters from LNS Database


Purpose To upload parameters directly modified in the devices by usage of e.g. a
handheld calibration tool or EBI. CARE allows uploading of the complete
set of parameters such as CPs, NCIs including related extension records.

Uploading can be done for a single device, all devices of a subsystem, a channel or
the LNS database.

NOTE: Uploading parameters of a complete subsystem or network may lead to a


very high busload. Hence, it is strongly recommended to upload
parameters only from changed devices.

For procedure please refer to the Upload Parameters section.

LON Device Monitoring


When the LNS tool/workstation is already running, you can go Onnet with CARE
and perform the following action:

• Monitor online values in the terminal assignment tool

NOTE: This works only for the NI Channel and when using the same domain ID
as LNS.

EBI Settings
For the communication with the EBI, general settings which apply to all NVs and
individual settings which apply to particular NVs, can be selected.

The settings are as follows:

Settings for All NVs

• NV Poll Interval
Defines the NV Poll Interval in s in which all NVs will be polled by the EBI
LON point server.

Settings for Particular NVs

• NV Poll Interval
Defines the NV Poll Interval in s by which a NVs will be polled by the EBI
LON point server.

• Report by Exception
For a particular NV, LNS uses a report by exception message transfer as
opposed to a polling mechanism to the LNS client. In this case the
LonWorks Point Server is the LNS client. It is recommend that this bit is
always set and perhaps this option should not even be shown.

• Use Bound Updates


Binds the respective network variable to the host network interface (host
binding).

Select NV Poll Intervall for all NVs Procedure

1. In the network tree, click on the LON-Works folder.

1357 EN2Z-0937GE51 R0518


LONWORKS NETWORK ENGINEERING CARE

2. On the Properties tab on the right pane, enter the interval in the NV Poll Interval
field.

Select Settings for Particular NV Procedure

1. Expand the network tree, navigate to the NV and select it.

EN2Z-0937GE51 R0518 1358


CARE LONWORKS NETWORK ENGINEERING

2. On the Properties tab on the right pane, select the desired options under EBI
Settings.

3. Apply settings to further NVs if desired.

CARE and EBI Upgrades

When upgrading CARE and/or EBI, please note the following essential information:

CARE Upgrade from Ver. 5 to 7.01


CARE Version >= 7.x supports the synchronization of EBI LNS settings. If EBI
version < 300.3 is part of the project, the EBI settings should be uploaded into the
CARE database to keep the current settings of the EBI. The upload is possible via
the "Upload EBI Settings" option in the context menu (see "Upload EBI Settings"
section). Further changes of the EBI settings should then only be done in CARE.
When synchronizing to LNS next time, all changed parameters are updated in LNS.

CARE Upgrade from Ver. 5 to 7.01 and EBI Upgrade from Ver. < 300.3 to 310
With LNS Turbo Edition it is possible to synchronize multiple CARE projects to the
same LNS server. EBI 310 can access each project simultaneously (multiple LON
point server). CARE Version >= 7.x is a prerequisite for EBI R310 support. Before
upgrading the EBI, the EBI settings must also be uploaded as described in the
above scenario.

1359 EN2Z-0937GE51 R0518


LONWORKS NETWORK ENGINEERING CARE

Upload EBI Settings

To avoid problems when upgrading CARE and/or EBI, it is highly recommended to


upload the EBI settings into CARE before doing the upgrade (see also "CARE and
EBI Upgrades" section).

Procedure 1. In the logical LON-bus part of the network tree, right-click on the
LonWorks folder and click on Upload EBI Settings in the context menu.

RESULT: The parameters NV Poll Interval, Report by Exception


and Use Bound Updates will be uploaded.

LNS Plug-Ins
CARE provides access to Honeywell LNS-based Plug-Ins in order to configure,
calibrate and/or monitor the corresponding LON devices.

LNS Plug-Ins will be installed with their own setup program and can then be
executed from within CARE for the selected device.

LNS Plug-Ins can be invoked locally on the CARE PC and remotely on a PC


connected via LAN. For details, please refer to the Synchronize with LNS section.

Honeywell Plug-Ins can be downloaded from “http://www.honeywell.de/plugin”.

Plug-In Registration

To use a Plug-In it must be registered first in the LNS database. Inter alia the
registration process creates the necessary device template for the corresponding
LON device. For Honeywell Plug-Ins/LON devices, CARE provides an "empty"
template database that includes all current device templates.

NOTE: Registration depends on the LNS network status, which indicates the
connection mode, local or remote. For both connection modes, local and
remote, a plug-in must be registered separately one-time.

EN2Z-0937GE51 R0518 1360


CARE LONWORKS NETWORK ENGINEERING

Procedure 1. In the logical LON-bus part of the network tree, right-click on the
LonWorks folder and click on Plug-In Registration in the context menu.

RESULT: The Plug-In Registration dialog box displays.

On the top the network status is displayed by connection


type (LAN, Local) and the network name. The /
plug icon status indicates whether the network interface is
physically connected to the network or not
respectively whether it is working properly or not.

Note that if CARE is not in LNS controlled mode, the


connection type is always local.

In the upper left, the Already Registered list shows all


plug-ins which have been already registered. In case of
plug-in updates they can be re-registered. In the lower
left, the Not registered list shows all plug-ins which have
not been registered yet.

2. In the corresponding list(s), select the plug-ins to be registered and click the
Add button(s).

1361 EN2Z-0937GE51 R0518


LONWORKS NETWORK ENGINEERING CARE

3. If remote operation of the plug-in is required, click the Load Resource Files
button.

NOTE: Loading resource files is only possible via LAN connection mode not
via LON.

RESULT: The Install Remote Resource Files displays.

EN2Z-0937GE51 R0518 1362


CARE LONWORKS NETWORK ENGINEERING

4. Browse to the folder where the resource files are located and select the file.

5. Click the Open button.

6. Click the Register button.

RESULT: The registration process starts and creates the device


templates for the plug-ins. If the resource files have been
loaded, they will be installed on the remote PC.

7. During the registration process, confirm message boxes, which might be


generated and displayed by the plug-in.

Plug-In Functions

Plug-ins provide configuration, calibration and monitoring functions


dependent on the device the plug-in is designed for. The kind of access to
the various plug-In functions such as depends on the LNS Controlled option
setting.

LNS Controlled Mode In LNS Controlled mode, the full functionality as designed for the plug-in is
available while LNS is running.

CARE Controlled Mode In CARE Controlled Mode, LNS Plug-In functions are restricted. While LNS
is running by the parallel use of a LNS tool, proper operation is only
possible for

• Configuration
• Calibration

While LNS is running,


• Monitoring
does not work properly because the device will be operated standalone without
any bindings. Hence, if a LNS tool is used in parallel for the LonWorks network
engineering, it is not allowed to go Onnet with CARE and monitor devices via
Plug-In Online if the LNS tool is already running.

In CARE Controlled Mode plug-in functions can be executed in offline and/online


mode as follows:

• Configuration (offline or online)


• Calibration (online)
• Monitoring (Test and Diagnostic, online)

As the list shows, configuration can be done offline as well online, whereas
calibration and monitoring can only be done online.

Normally, configuration will be the first step, then the device can be calibrated and/or
monitored.

Depending on the mode, offline or online, the interaction between CARE (database),
LNS database, Plug-In and LON device will be different for the procedures (see
"Plug-In Offline Functions in CARE Controlled Mode (Configuration)" and "Plug-In
Online Functions in CARE Controlled Mode (Configuration, Calibration, Monitoring)"
sections.

Prerequisites The plug-in must be installed and registered on the CARE PC. For remote
plug-in operation on a PC connected via LAN, the device templates and the
DRF files must be installed on the remote PC. This will be done remotely
during registering the plug-in on the CARE PC (see Plug-In Registration
section).

Re-registering is also possible in the same way.

1363 EN2Z-0937GE51 R0518


LONWORKS NETWORK ENGINEERING CARE

Plug-In Functions in LNS Controlled Mode

In LNS Controlled mode, the full functionality (calibration, configuration and


monitoring) of the plug-in is available while LNS is running (offline or
online).

NOTE: It is recommended to perform a Synchronize with LNS before launching


the Plug-in.

The CARE process when working in LNS controlled mode is as follows:

Plug-In in LNS Controlled Mode

1
Synchronize Logical Device*
LNS database** CARE
e.g. XL 12

START

Configuration

Calibration

Monitoring
CARE database
XL12
... XL12
... VAV2
... DIO

Plug-In starting:
Export data of single
device to LNS database 3
Plug-In exiting: Plug-In
Write data of single
device to CARE
database

rite
ead/W
R
LNS database**

...XL12
XL12 Configuration, calibration, monitoring data

Rea
d/
Wri
te

Com
miss
ionin
g
Physical Device
XL 12

* Device in network tree


** One and and the same LNS database

EN2Z-0937GE51 R0518 1364


CARE LONWORKS NETWORK ENGINEERING

Prerequisites see Prerequisites in Plug-In Functions section.

Procedure 1. If not already done, install the LNS software and the Plug-In.

2. Set CARE into LNS controlled mode and Synchronize with LNS as described in
the Synchronize with LNS section.

3. In the logical LON-bus part of the network tree, click on the device, of which
plug-in you want to start.

4. Click right mouse key and with left mouse key, click Plug-Ins.

RESULT: The Launch LNS Plugin dialog box displays.

5. Select desired option, in this case, under Configure, Monitor, and Honeywell
project settings.

NOTE: The Honeywell project settings allow defining global settings such as
engineering unit, fail detect time, etc., for example, for each XL 10
controller type. Those global settings are saved in the LNS project and
not in the CARE database. Hence, when changing such a global
setting via plug-in, the changed value is not taken over after the plug-in
has been closed.

6. Click the Launch button.

RESULT: The plug-in is started. The physical device is


commissioned.

7. In the Plug-In, define the settings

RESULT: The data are saved to the physical device and to the
logical device respectively to the LNS and to the CARE
database.

8. Exit the Plug-In.

Plug-In Offline Functions in CARE Controlled Mode (Configuration)

Configuring a device means to define device-specific settings, for example "the time
to open / time to close a valve" in an air handling unit. The configuration can be
done offline or online and is saved in the LNS, respectively in the CARE database.
When the logical device (logical device=device in network tree) has been configured
offline, the configuration data must then be saved to the physical device by
commissioning in a second step.

When the logical device has been configured online, the configuration data is
automatically saved to the physical device.

1365 EN2Z-0937GE51 R0518


LONWORKS NETWORK ENGINEERING CARE

The CARE process when working offline on a Plug-In is as follows:

Plug-In Offline in CARE-Controlled Mode

Logical Device*
CARE
e.g. XL 12

START

Configuration
CARE database
XL12
... XL12
... VAV2
... DIO

Plug-In starting:
Export data of single
device to new LNS project
2
Plug-In
Plug-In exiting:
Write data of single device to
CARE database

rite
d/W
Temporary Rea
Configuration data
LNS database**

...XL12
XL12

* Device in network tree


** Not the LNS database used for Synchronize

Prerequisites see Prerequisites in Plug-In Functions section.

NOTE: If DIO/Smart I/O Plugins are used, the point attributes will not be updated.

Procedure 1. If not already done, install the LNS software and the Plug-In.

2. In the logical LON-bus part of the network tree, click on the device, you want to
configure.

3. Click right mouse key and with left mouse key, click Plug-Ins Offline.

RESULT: The Launch LNS Plugin dialog box displays.

EN2Z-0937GE51 R0518 1366


CARE LONWORKS NETWORK ENGINEERING

4. Select the Configure option.

5. Click Launch button.

RESULT: The plug-in is started.

6. Configure the device.

RESULT: The configuration data are saved to the logical device


respectively to the LNS and to the CARE database.

7. Exit the Plug-In.

8. To save the configuration data in the device, commission the device as


described in the "Commission Device(s)" section.

Plug-In Online Functions in CARE Controlled Mode (Configuration, Calibration, Monitoring)

Plug-In online operation can properly be used for calibration and


configuration only. The monitoring does not work properly because the
device will be operated standalone without any bindings.

The CARE process when working online on a Plug-In is as follows:

1367 EN2Z-0937GE51 R0518


LONWORKS NETWORK ENGINEERING CARE

Plug-In Online in CARE-Controlled Mode

Logical Device*
CARE
e.g. XL 12

START

Configuration

Monitoring***
Calibration
CARE database
XL12
... XL12
... VAV2
... DIO

Plug-In starting:
Export data of single
device to new LNS project
2
Plug-In
Plug-In exiting:
Write data of single device to
CARE database

rite
d/W
Rea
Temporary
LNS database**
Configuration, calibration, monitoring data***
...XL12
XL12
Rea
d/
Wri
te

Com
miss
ionin
g
Deco Physical Device
mmis
sioni XL 12
ng

* Device in network tree


** Not the LNS database used for Synchronize
*** Proper Monitoring not possible due to standalone
status of commissioned device

Prerequisites see Prerequisites in Plug-In Functions section.

Procedure 1. If not already done, install the LNS software and the Plug-In.

2. In the logical LON-bus part of the network tree, click on the device, you want to
monitor.

3. Click right mouse key and with left mouse key, click Plug-Ins Online.

RESULT: The LNS Plugin dialog box displays.

EN2Z-0937GE51 R0518 1368


CARE LONWORKS NETWORK ENGINEERING

4. Select desired option, in this case, under Configure, Monitor, and Honeywell
project settings.

NOTE: The Honeywell project settings allow defining global settings such as
engineering unit, fail detect time, etc., for example, for each XL 10
controller type. Those global settings are saved in the LNS project and
not in the CARE database. Hence, when changing such a global
setting via plug-in, the changed value is not taken over after the plug-in
has been closed.

5. Click the Launch button.

RESULT: The plug-in is started. The physical device is


commissioned.

6. In the Plug-In, define the settings

RESULT: The data are saved to the physical device and to the
logical device respectively to the LNS and to the CARE
database.

7. Exit the Plug-In.

RESULT: The device is decommissioned.

Replace Device in LNS Controlled Mode


Devices can be replaced in the LNS database without using any additional credits. A
device can be replaced by simply changing the neuron ID on the Properties tab of
the device.

1369 EN2Z-0937GE51 R0518


LONWORKS NETWORK ENGINEERING CARE

During the next synchronization, LNS replaces the device by commissioning the
new device and decommissioning the old device.

Restore CARE Projects


When restoring a project created with an older CARE version than 5, the default
status of the project regarding LNS is “not yet synchronized”.

When restoring an old CARE project which has been changed and synchronized in
the meanwhile, it may result in the need to start again. That is, the LNS project must
be deleted in CARE respectively on the Remote PC and the restored project must
be synchronized.

When back upping a project, LNS extensions will be included, but LNS related files
such as XIF; DRF and LNS database files will not.

Delete LNS Project(s)


Whenever synchronizing the LNS database with the CARE database, the CARE
project is stored as LNS project for usage within the LNS-based tool.

In case the CARE project name is changed and the corresponding LonWorks
network is synchronized again, the old LNS project can be deleted to save disk
space.

Depending on the LNS controlled mode (Local or LAN), that is, whether CARE and
the LNS server reside on the same PC or on different PCs, LNS projects are to be
deleted in different ways.

See also "LNS Credits Handling" section.

Procedure (Local LNS Server) 1. Click menu item Database, then submenu item Delete LNS Project(s).

RESULT: The Delete LNS Project dialog box displays.

2. Select the project from the Please select a Project drop-down listbox.

EN2Z-0937GE51 R0518 1370


CARE LONWORKS NETWORK ENGINEERING

3. Click the Delete button.

Procedure (Remote LNS Server) 1. Start Windows control panel and double-click on the Remote Sync
Server icon in the control panel.

RESULT: The Remote Sync Server Configuration dialog box


displays.

2. Under Remote Sync Server, click the Stop radio button.

3. Under LNS Server, click the Stop radio button.

4. From the LNS Network´s drop-down listbox, select the network (project) you
want to delete and click the Delete button.

5. Click the Close button.

1371 EN2Z-0937GE51 R0518


LONWORKS NETWORK ENGINEERING CARE

LNS Credits Handling


IMPORTANT
By default CARE provides one credit necessary for the Plug-Ins Online
function. Hence, make sure that least one credit is always available in the
LNS database. Also make sure, that the job specific number of credits has
been ordered before starting the Synchronize with LNS function.

The credits count will be affected when applying one of the following functions:

Synchronization with LNS


In case devices have been added, for each device one credit will be subtracted from
the credits count available. In case devices have been deleted, for each device one
credit will be returned. The credits will be count on the PC where the LNS database
is installed.

Delete LNS Project


When deleting an LNS project, the credits that have been substracted during LNS
Synchronization will be returned.

Plug-In Online
When working Online with a LNS Plug-In, one credit will be issued during
commissioning and returned after decommissioning (temporary issue).

Incremental LonWorks Engineering


Workflow Incremental engineering means that CARE will be used in combination with
a LNS-based software such as EBI whereas CARE is running in LNS
controlled mode in which the LNS-based software is controlling the
LonWorks network. The following diagram describes the engineering
workflow during incremental engineering:

EN2Z-0937GE51 R0518 1372


CARE LONWORKS NETWORK ENGINEERING

CARE LNS-based Software (e.g. EBI)

Offnet/Onnet: Engineering Running and connected to LonWorks

1
Onnet:
Commissioning, A
Monitoring and
Configuration

Sy
Switch to: nch
ro niz
LNS Controlled Mode e

Offnet Engineering Recommissioning


Recommissioning
or
"Sandbox channel"
operation
B
2 1

Sy
nch
ro niz
e

Offnet Engineering Recommissioning

C
3 2

Sy
nch
ro niz
e

3
Cutline:

step LNS CARE


database database

A. The initial engineering is done with CARE in Offnet mode respectively in Onnet
mode. Usually in Offnet mode, you structure the LON network and do the
bindings. Then you go Onnet, commission and configure the devices/LON
network. To bring the LNS database into the actual state, you switch CARE into
LNS Controlled mode. Then you synchronize the LNS network/database with
the CARE network/database. The LNS-based software gets Online and
recommissions the complete network. All LON devices are displayed on the
workstation.

B. As it is typical for incremental project engineering, you may add and configure
some new components, such as LON devices, channels, and/or routers in
CARE. This can be done offnet or onnet. In order to apply the full set of CARE

1373 EN2Z-0937GE51 R0518


LONWORKS NETWORK ENGINEERING CARE

onnet functions, the respective channel can be separated as a “sandbox”


channel, even if the LNS-based software is running and controlling the network.

After completing the changes and still in LNS controlled mode,


you synchronize the LNS network with the CARE network again. The LNS
database will be updated with changed information done in CARE.

C. Repetition of step B, and so forth.

Architectures

For big jobs it is possible to startup the plant incrementally. In this case, some
precautions need to be taken as described in the following sections.

Example Architecture

Router
Channel1

Device Device Device Device Device

Router
Channel2
Backbone

Device Device Device Device Device

Router
Channel3

Device Device Device Device Device

Initial Engineering

Procedure 1. Connect the CARE PC to any channel of the LON network and set this
channel to the network interface channel (NI channel).

2. Do complete network startup with CARE using the complete CARE onnet
functions.

EN2Z-0937GE51 R0518 1374


CARE LONWORKS NETWORK ENGINEERING

CARE
Router
Channel1

Device Device Device Device Device

Router
Channel2

Backbone
Device Device Device Device Device

3. Disconnect CARE from the LON network by setting it Offnet.

4. Connect the PC with the LNS-based software, e.g. EBI, physically to the
backbone and open the LNS network.

5. In CARE (Extended LNS Options), make the backbone channel to the LNS NI
channel.

6. Synchronize the LNS network with the CARE network.

Synchronize with LNS

LNS-based Software CARE (offnet)

Router
Channel1

Device Device Device Device Device

Router
Channel2
Backbone

Device Device Device Device Device

Adding a Channel

If a new channel should be added, it must be engineered offnet with CARE.

1375 EN2Z-0937GE51 R0518


LONWORKS NETWORK ENGINEERING CARE

LNS-based Software

Router
Channel1

Device Device Device Device Device

Router
Channel2
Backbone

Device Device Device Device Device

Router
Channel3

Device Device Device Device Device

CARE

1. Engineer the new channel in CARE.

2. Connect CARE PC physically to the new channel.

3. In CARE, make the new channel to the “sandbox” channel.

4. Do the complete startup of this channel with full onnet functionality of CARE.

NOTE: Bindings between new channel(s) and existing channels that had been
synchronized will not work during this start-up.

5. Disconnect the CARE PC from the LON network by setting it offnet.

6. Release the sandbox channel.

7. Synchronize the LNS network with the CARE network.

8. Integrate the new channel into the LNS-based software.

EN2Z-0937GE51 R0518 1376


CARE LONWORKS NETWORK ENGINEERING

Synchronize with LNS

LNS Based Tool CARE (offnet)

Router
Channel1

Device Device Device Device Device

Channel2
Router
Backbone

Device Device Device Device Device

Router
Channel3

Device Device Device Device Device

Download Firmware
Prerequisites The device must be commissioned (see Commission Device(s) section) and
you have to be onnet (see Go Onnet section).

NOTE: Only .APB files can be downloaded and downloading is only possible, if
the existing program ID, the chip version and the firmware version match
the application file to be downloaded. If not, error messages occur, for
example:

Procedure 1. In the tree, click on the device, you want to download an application to.

2. Click right mouse key, and with left mouse key click on Firmware Download.

RESULT: The Open dialog box displays.

1377 EN2Z-0937GE51 R0518


LONWORKS NETWORK ENGINEERING CARE

3. Browse to folder and select desired application file.

4. Click Open button.

RESULT: CARE starts downloading firmware.

The process window disappears when download is


finished and the device gets white-colored in the network
tree.

EN2Z-0937GE51 R0518 1378


CARE LONWORKS NETWORK ENGINEERING

Download Application Remotely (Excel Online Remote)


Purpose To download and start an application remotely. In addition, status
information and values can be viewed. The application will be downloaded
from the CARE PC to the Remote PC (EBI, SymmetrE) which is connected
to the controller.

Prerequisites To enable the remote download function (Excel Online Remote), the
following prerequisites must be fulfilled:

• The application must be translated and loaded into the controller


• LAN connection between CARE PC and Remote PC must be working
• Remote PC must have access to the controller via e.g. XPC500, BNA,
LON, etc.
• Server on Remote PC must be running
• Excel 500 point server service (C-Bus driver service) must be running on
the Remote PC. In general, the service is running as soon as EBI has
been started. For information on the Cbus address, see Procedure.

Access Principle of
Excel Online Remote After the LAN connection between CARE PC and remote PC is established,
a service of the Remote PC is used to access the XL500 controller. Starting
Excel Online Remote is independent on the connection (interface) type
(XPC500, BNA, LON, etc.). As soon as the controller and datapoint online
changes can be seen on the Remote PC, Excel Online Remote can be
started.

Procedure (Remote PC) 1. In the Windows Control Panel, double-click the CBUS icon.

RESULT: The Honeywell Cbus Configuration dialog box displays.

2. To create a connection, click the Add button. A connection is inserted


named cbus1 in the Cbus column. When adding further connections,
the names are consecutively numbered as cbus2, cbus3, etc. The Cbus

1379 EN2Z-0937GE51 R0518


LONWORKS NETWORK ENGINEERING CARE

entry represents the remote Cbus ID, e.g. for cbus1 the remote bus ID
is 1, and so on. This remote bus ID is needed in CARE for providing a
proper remote download.

3. Click on the entry in the Cbus column and select the connection from
the Type drop-down listbox, e.g. LON.

4. If a LON connection is selected, click the Initialize button to initialize the


LNS database.

5. Click the OK button.

Procedure (CARE PC) 6. Expand the network tree, and click on the subsystem of the C-bus
network, which includes the controller.

7. On the Properties tab on the right, select the connection, C-Bus or LON-bus.

8. In the Remote Host Name field, enter the host name or the IP address of the
remote PC.

9. In the Remote Bus ID field, enter the remote bus ID (see Step 2).

10. Translate the controller if not already done.

11. Translate the controller if not already done.

12. In the physical LON bus part of the network tree, click on the controller.

13. In the CARE toolbar, click the icon.

RESULT: Excel Online Remote is started.

14. Download the controller as described in the ONLINE SERVICE AND


COMMISSIONING section.

Restrictions MMI Emulation and all related functions do not work. Alarms are received
but the alarm buffer cannot be uploaded. Firmware cannot be downloaded.

EN2Z-0937GE51 R0518 1380


CARE LONWORKS NETWORK ENGINEERING

Keep Device Configuration

Purpose To avoid impermissible or unintentional overwrittings of actual device


configurations, the configuration of each device can optionally be kept. The
actual configuration of the device cannot be overwritten as long as the
parameters have not been uploaded from the device.

After the parameters have been uploaded, the configuration can be overwritten by
usage of one of the following functions:

• Plug-In online or offline


• Commissioning
• Synchronization with LNS.

The Keep Device Configuration property can be assigned to the LON device in the
network tree as well as in the device library. When setting the property for a device
in the device library, each imported device out of the library will have it automatically
checked as it was added to the network tree/terminal assignment tab.

IMPORTANT
When upgrading a project created with a CARE version lower than 5.0,
CARE automatically sets the property of any device to not “Keep Device
Configuration” and assumes that the parameters are already uploaded. If
the upgraded project includes physically pre-configured devices such VAV
2 it is strongly recommended to check the property of the device(s) to
“Keep Device Configuration”, or to upload the parameters prior to using any
of the above-mentioned functions in order to change a device´s
configuration.

Plug-In Online and


Plug-In Offline Behavior In case the Keep Device Configuration property is checked for a single
device, the plug-in cannot be invoked from within the device as long as the
parameters have not been uploaded.

Commissioning Behavior In case the Keep Device Configuration property is checked for a single
device, commissioning cannot be done for a single device as long as the
parameters have not been uploaded. Unexported devices will be shown in a
list.

Synchronize to LNS Behavior In case the Keep Device Configuration property is checked for a single
device, Synchronize with LNS is possible but the corresponding device will
not be exported/synchronized as long as the parameters have not been
uploaded. A system/subsystem can be commissioned whereas only the
devices which have the Keep Device Configuration property not assigned
will be commissioned and the uncommissioned devices will be shown in a
list.

Procedure 1. In the logical LON part of the network tree, click on the device.

2. On the Properties pane on the right, check the Keep Device Configuration
checkbox.

1381 EN2Z-0937GE51 R0518


LONWORKS NETWORK ENGINEERING CARE

For the procedure in the Device Library please refer to the Create LON Device
section under Device Library.

EN2Z-0937GE51 R0518 1382


CARE LONWORKS NETWORK ENGINEERING

Excel Web Remote LON Commissioning


Prerequisites For commissioning Excel Web projects created with CARE version lower
than 8.03.00, the old project must be upgraded and restored, the second
domain must be reset and the application in the controller must be running.

Procedure 1. Perfom prerequisites mentioned above.

2. Click menu item Lon, then submenu item Lon Interface Configuration, or click
in the configuration toolbar.

RESULT: The Lon Interface Configuration dialog box is displayed.

3. To create a new interface, click on Lon Sock Remote Server in the tree.

4. Click the New button.

RESULT: The properties for entering the appropriate information are


displayed on the right pane.

5. In Interface Name, enter an interface name.

6. In LonSock Remote Host Address, enter the IP address of the Excel Web
controller

7. In Port, enter the port number 3830 if not displayed.

8. In Remote Host Address Interface, select /dev/lon.

9. Click Apply button

10. Confirm the message box by clicking OK button, and then click Exit button.

11. Confirm the message box by clicking OK button, and then click Exit button.

12. Select the Lon interface on the Properties pane of the LonWorks node.

13. Expand the LON-bus part of the network tree and commission the Excel Web
controller.

14. Commission the LON devices connected to the commissioned Excel Web
controller.

1383 EN2Z-0937GE51 R0518


LONWORKS NETWORK ENGINEERING CARE

EN2Z-0937GE51 R0518 1384


CARE

ONLINE SERVICE AND COMMISSIONING

1385 EN2Z-0937GE51 R0518


CARE

EN2Z-0937GE51 R0518 1386


CARE ONLINE SERVICE AND COMMISSIONING

ONLINE SERVICE AND COMMISSIONING

Overview
XL Online provides the following commissioning and service functions online:

• Changing datapoint values


• Viewing datapoints in a watch list
• Setting parameters
• Monitoring z and x/y registers
• Set RACL cycle time
• Start/stop application
• Editing time programs
• Set system clock
• Saving and erasing application in the Flash EPROM
• Point trending
• Up-/downloading controller application
• Changing controller number and viewing bus configuration
• Downloading firmware
• Download Application Remotely
• Viewing alarms
• Repair PRA file

Getting started
To perform online commissioning and service functions, the following steps have to
be done before:

• Physically connect to the controller


• Get the controller files on digital media (CD, floppy disk) and/or translate the
controller in CARE (only if a download is necessary)

Physically Connect to Controller


Purpose Physically connect controller to Personal Computer (PC).

Requirements The PC must be within 49 ft. (15m) of the controller. At greater distances (up to
3281 ft. [1000m]), you must add a line driver.

Use a XW585 Connection Cable.

Procedure 1. Insert plug on the XW585 connection cable into the socket on the front of the
controller computer module.

2. Insert the other plug on the XW585 connection cable to the serial interface
socket on the back of the PC (COM 1 or COM 2).

3. Power on the PC.

4. Start XL Online as described in the "Start XL Online" section.

1387 EN2Z-0937GE51 R0518


ONLINE SERVICE AND COMMISSIONING CARE

Start XL Online
Start separately

Procedure 1. If XL Online has been ordered and registered separately, click on XL Online
icon in the Windows Start menu.

RESULT: If XL Online has not been registered yet, the Registration dialog
box displays.

2. Register XL Online as described in the "Registering the first Time" section.

RESULT: The XL Online main window displays. Software tries to connect


to the port according to the settings defined in the XL Online
Options dialog box (see "Port Settings" section).

If no controller is connected to the port or software cannot


connect to the controller due to wrong port settings, the XI
581/2 MMI is gray and the status message "No connection" is
displayed.

If the connection is completed, the MMI is displayed in blue. If


no text is displayed, click on another tab or click the ESC button
on the MMI emulation.

3. Continue with step 3 of the "Start from within CARE procedure".

Start from within CARE

Procedure 1. If XL Online has been registered within a CARE license, select the controller in
the logical plant tree in CARE.

2. Click menu item Controller, then submenu items Tools and XL Online.

RESULT: The XL Online main window displays. Software tries to connect


to the port according to the settings defined in the XL Online
Options dialog box (see "Port Settings" section).

If no controller is connected to the port or software cannot


connect to the controller due to wrong port settings, the XI
581/2 MMI is gray and the status message ´No connection` is
displayed.

If the connection is completed, the MMI is displayed in blue. If


no text is displayed, click on another tab and back or click the
ESC button on the MMI emulation.

3. If ´no connection` is displayed in the status line, connect the controller to the
port as follows:

4. Click menu item File, then submenu item Connection.


Or, click on the Change serial port settings icon on the button bar.

RESULT: The Connect dialog box displays.

EN2Z-0937GE51 R0518 1388


CARE ONLINE SERVICE AND COMMISSIONING

5. Select the serial port and the baud rate by clicking the corresponding radio
buttons. Select Auto detect, if you do not know the baud rate (default setting).

6. Click the Connect button.

RESULT: If the connection could not be completed, the following status


report is displayed.

1389 EN2Z-0937GE51 R0518


ONLINE SERVICE AND COMMISSIONING CARE

RESULT: If the connection could be completed, the MMI is displayed in


blue. If no text is displayed, click on another tab and back or
click the ESC button on the MMI emulation.

7. Click the Controller tab.

RESULT: Controller status information is listed.

EN2Z-0937GE51 R0518 1390


CARE ONLINE SERVICE AND COMMISSIONING

8. Check the information.

1391 EN2Z-0937GE51 R0518


ONLINE SERVICE AND COMMISSIONING CARE

The XL Online Main Window

The main window is designed as follows:

Tabs The main functions are provided on the following tabs:

MMI
Allows changing values in the controller via XI581/82 emulation

Trend
Allows trending datapoints

Datapoints
Allows changing datapoint attributes, writing them to the controller, and invoking a
watch list for certain datapoints.

Controller
Displays controller information. Allows printing the controller information in HTML
format. Allows up-/downloading a controller application, downloading firmware,
changing the controller number, and viewing bus configuration.

Alarms
Displays critical and non-critical alarms

When selecting a tab, the corresponding menu is enabled in the menu bar
providing the appropriate submenu items:

EN2Z-0937GE51 R0518 1392


CARE ONLINE SERVICE AND COMMISSIONING

Menus File

Provides submenu items to:


• Connect to the controller including port and baud rate selection and detection
• Set default options for XL Online
• Repair PRA file
• Print controller information in HTML format
• Exit XL Online

View

Provides submenu items to:


• Enable/disable the bars display
• Select tabs
• Invoke watch list

General

Provides submenu items to:


• Set parameters, z and x/y register, RACL cycle time, system clock
• Start/stop the application in the controller
• Edit time programs
• Save and erase application in the Flash EPROM

Trend

Provides submenu items to:


• Perform trend sessions
• View and export records

Datapoints

Provides submenu items to:


• Write value changes to the controller
• Add points to a watch list
• Select/deselect points in manual mode

Controller

Provides submenu items to:


• Display controller information
• Up-/download controller
• Download firmware
• Change controller number and view bus configuration

Alarms

• Clear alarms

Help

• Invoke Online-Help
• Register XL Online
• Display About information

Button Bar Depending on the current tab selection, the button bar provides the following
functions:

Connect to the controller and change serial port settings for an online
session.

Detect baud rate of current serial port

1393 EN2Z-0937GE51 R0518


ONLINE SERVICE AND COMMISSIONING CARE

Show/hide parameter dialog box

Show/hide z-register dialog box

Show/hide x/y-register dialog box

Open time program editor

Show/hide datapoint watch list

Show/hide line info window

Open new trend data file

Open existing trend data file

Select datapoints for trend recording

Start/stop trend recording

Reload datapoint list/Refresh controller info

Add selected datapoints to watch list

Upload controller application

Download controller application

Status Line Displays port, current status, e.g. Online, baud rate = 9600 etc., or the current trend
file.

Exit XL Online
Procedure 1. Click menu item File then submenu item Exit, or click on default Windows
Close icon at the top right corner.

RESULT: XL Online is closed.

EN2Z-0937GE51 R0518 1394


CARE ONLINE SERVICE AND COMMISSIONING

Procedures

Define Default Settings


For the following default settings can be defined:

• Port
• Alarms
• Controller
• Font
• General

Port Settings

Purpose Define default settings for the port and baud rate XL Online should use when
starting it. After the start, XL Online searches automatically for the port and the
baud rate defined in this dialog box. If the port configuration matches, the MMI
displays. If the port configuration is different, the MMI remains gray and displays the
status ´No connection` in the status line.

Procedure 1. Click menu item File, then submenu item Options.

RESULT: The XL Online Options dialog box is displayed.

2. Under Serial port and Baudrate, select desired port respectively baud rate
which software should use as default connection settings.

3. To increase the download/upload speed after the connection has been


completed, check the Switch to 38400 baud on connect check box, to
increase the baud rate to 38400 baud.

NOTE: For an automatic baud rate switch, the controller OS must be 2.04 or
higher.

4. Check the Switch to 9600 baud on exit check box, to reset the baud rate to
9600 baud when XL Online is closed.

1395 EN2Z-0937GE51 R0518


ONLINE SERVICE AND COMMISSIONING CARE

NOTE: If the controller supports a baud rate of 38400 baud , it is


recommended to check both, the Switch to 38400 baud on connect
and the Switch to 9600 baud on exit option.

5. Click OK button to confirm settings.

Alarm Settings

Purpose Define default settings for the alarm display.

Procedure 1. Click menu item File, then submenu item Options.

RESULT: The XL Online Options dialog box is displayed.

2. Click the Alarms tab.

3. To let the alarms be inserted at the top of the list on the Alarm tab, check the
Insert alarms on top check box.

4. To let an additional popup alert display, check the Popup alert checkbox on
the Alarm tab. The following popup alert will then display when new alarms
arrive.

5. To let the alarms be saved into a log file, check the Write alarms to log file
check box. The alarms will be saved into a .TXT file. The name of the file can

EN2Z-0937GE51 R0518 1396


CARE ONLINE SERVICE AND COMMISSIONING

be changed in the Log file name field and an existing file can be used by
clicking the Select button and selecting it. New alarms will be added
continuously to the end of the log file.

6. Click OK to confirm settings.

Controller Upload-/Download Settings

Purpose Set whether the controller should be stopped or not when uploading the application.

Set whether the settings of the controller number, bus baud rate and bus ID issued
during engineering in CARE should be used when downloading an application. For
detailed information on these items, please refer to the "LonWorks Network
Engineering" section in the CARE User Guide EN2B-0182 (Europe) / 74-5587 (U.S)
and the LonWorks Mechanisms Interface Description EN0B-0270.

In addition, the option whether a warning should be displayed or not when an


application with a changed LON interface will be downloaded, can be set.

Procedure 1. Click menu item File, then submenu item Options.

RESULT: The XL Online Options dialog box is displayed.

2. Click the Controller tab.

3. Check one of the following options:

Stop controller during upload


Defines whether the application should be stopped during upload or not.

Display LON interface change warning


Defines whether warning messages are to be displayed or not in case a
changed LON network interface will be downloaded.

Enabling the option is recommended when using controller OS lower than 2.06
and bindings might be deleted. Disabling the option is recommended when
using controller OS 2.06 where any bindings will be kept even if the LON
interface has been changed.

1397 EN2Z-0937GE51 R0518


ONLINE SERVICE AND COMMISSIONING CARE

Set Controller no. automatically


Defines whether the controller number set in CARE should be used or not
when downloading the application.

Set Bus baudrate automatically


Defines whether the C-bus baud rate set in CARE should be used or not when
downloading the application.

Set Bus ID automatically


Defines whether the LON ID set in CARE should be used or not when
downloading the application.

Inter-section delay
Defines a delay while burning the sections of the FLASH EPROM. Default is
1000 msec. The range is between 0 and 9999 msec. The time should be
increased if the firmware download repeatedly stops on one and the same
section.

7. Click OK button to confirm settings.

For further instructions, refer to the "What kind of application to download?" section.

Font Settings

Purpose Define default settings for the MMI font display. Font modification can be used, for
example, to match country specific (e.g. Japanese or Cyrillic) controller operating
sequences with the MMI display and/or in case a notebook is used.

By default, XL Online uses a bold true type font with fixed width, indicated by
´Default` in the MMI field. Note, that ´Default` cannot be re-selected after another
font had been selected. To get a font similar to the default font, it is recommended
to select the ´Courier new` font as it is described in the procedure.

Procedure 1. Click menu item File, then submenu item Options.

RESULT: The XL Online Options dialog box is displayed.

2. Click the Fonts tab.

3. To select another font than the "default font", click the button.

EN2Z-0937GE51 R0518 1398


CARE ONLINE SERVICE AND COMMISSIONING

RESULT: The Font dialog box is displayed.

4. Select the desired font (the font size is not relevant) and click OK button.

RESULT: The font is displayed in the MMI field on the Fonts tab.

5. Click OK button to confirm settings.

General XL Online Settings

Purpose Define general settings for XL Online.

1399 EN2Z-0937GE51 R0518


ONLINE SERVICE AND COMMISSIONING CARE

Procedure 1. Click menu item File, then submenu item Options.

RESULT: The XL Online Options dialog box is displayed.

2. Click the General tab.

3. Select options under:

Allow starting multiple instances


Defines whether XL Online can be opened in multiple instances or not. Multiple
instances of XL Online can be used for example, to communicate with multiple
controllers at the same time or to compare an old trend with a currently running
trend.

Restore last window position


Defines whether XL Online should be opened with the last window position and
size on the desktop. When unchecked, XL Online opens with the default
position and size.

Device no. to use for virtual CBus


Defines the buswide free device (controller) no. that must be used when
connecting XL Online to a virtual C-Bus system. The default setting -1 must be
used if all device numbers have already been allocated. Any other number
known to be free on the C-Bus, can also be used. Note that when connecting
using the default device no. -1, flash functions may not work properly. In this
case, use another free buswide device no. If the device no. has been changed,
restart XL Online.

4. Confirm settings by clicking OK button.

EN2Z-0937GE51 R0518 1400


CARE ONLINE SERVICE AND COMMISSIONING

Download Controller
Purpose Copy translated files to a controller (step 2 of commissioning procedure).

NOTE: Make sure that the controller number in CARE and in the MMI is the
same. If they are different, set them equal either in CARE or in the
MMI or by Set controller no. command (see "Set Controller Number"
section). For operating instructions of the MMI refer to the XI581/2
Operator Terminal Manual.

Procedure 1. Physically connect to controller as described in the "Connect to Controller"


section.

2. Start XL Online as described under the "Start XL Online section".

3. Click menu item Controller, then submenu item Download


or,
click on Download to Controller icon on the toolbar.

RESULT: The Application download dialog box displays.

RESULT: At the top, the path of the previously downloaded application is


displayed.

4. If you want to download a new application, click Application button and select
the desired application (.PRA file).

5. Click Start download button if you want to download the previously


downloaded application or the new application.

RESULT: Depending on the kind of application you want to download,


different messages can appear (see "What kind of Application
to Download" section).

1401 EN2Z-0937GE51 R0518


ONLINE SERVICE AND COMMISSIONING CARE

The download starts. Action and status messages will be listed


while the download proceeds.

EN2Z-0937GE51 R0518 1402


CARE ONLINE SERVICE AND COMMISSIONING

6. Click the Close button when the download is finished.

RESULT: Eventually alarms are generated as indicated by the flashing


Alarm icon on the Alarms tab.

7. Click the Alarms tab, check the messages and perform appropriate trouble-
shooting procedures if necessary.

What Kind of Application to Download?

When using controller OS 2.06 for binding LON devices, the bindings will be kept
when downloading an application with a changed LON network interface.

When using controller OS lower than 2.06 in combination with a separate LON tool
for creating the bindings, different messages will occur when downloading a
changed interface. In XL Online, it is possible to enable/disable the display of the
corresponding warning messages generally.

Enable/Disable LON Interface In XL Online, click menu item File, then submenu item Options to open the
Change Warning XL Online Options dialog box.

Click Controller tab.

Check the Display LON interface change warning check box if you want to get
the warning messages in case a changed LON network interface will be
downloaded. Enabling the option is recommended when using controller OS lower
than 2.06 and bindings might be deleted.

Uncheck the Display LON interface change warning check box if warning
messages should not be displayed when downloading a changed LON network
interface. Disabling the option is recommended when using controller OS 2.06
where any bindings will be kept even if the LON interface has been changed.

LON Interface Change Warning Enabled As CARE allows the creation of LON applications, it has to be considered, whether
the application you want to download is a LON application having a LON network
interface or whether it is a "normal" application without a LON network interface.
CARE allows the partial download of a LON application, where changes had been
made to the CARE application itself, with keeping an unchanged LON network
interface.

IMPORTANT

1403 EN2Z-0937GE51 R0518


ONLINE SERVICE AND COMMISSIONING CARE

It is of high importance to know what kind of application you want to


download and what kind of application is currently running in the controller,
since CARE allows the choice of keeping or eliminating the bindings.

Although CARE compares the controller application and the application to


be downloaded regarding the LON network interface, you should also
know, whether the LON network interface and/or the CARE application had
been changed or not.

The following table summarizes the different possibilities when downloading


"normal" applications and LON applications:

Download of Normal Application without LON Network Interface


Controller CARE
No application in controller Download without response
Normal application in controller Download without response
LON application in controller Download with response asking:
The LON interface of this application has changed. If you
download now, your existing bindings will get lost.
When confirming with OK, the bindings will get lost and need
to be re-done with a LON tool. The (modified) CARE
application will be downloaded.
When canceling the download, the bindings will be kept and
the CARE application will not be downloaded.
Download of LON Application
Controller CARE
No application in controller Download without response
Normal application in controller Download without response
LON application in controller Download with response. Message depends on, whether the
network interface was changed or not.
If Network interface had been changed:
The LON interface of this application has changed. If you
download now, your existing bindings will get lost.
When confirming with OK, the bindings will get lost. The
(modified) CARE application will be downloaded.
When canceling the download the bindings will be kept. The
CARE application will not be downloaded.
If LON interface had not been changed:
Do you want to keep existing NV bindings. If you select NO,
then all bindings will get lost.
When confirming with OK, the bindings will be kept. The
(modified) CARE application will be downloaded (partial
download).
When confirming with NO, the bindings will get lost and need
to be re-done with a LON tool. The (modified) CARE
application will be downloaded.
When canceling the download the bindings will be kept. The
CARE application will not be downloaded.

Upload Controller

Check Upload setting in the XL Online Options dialog box (see " Controller Upload-
/Download Settings" section).

1. If not already connected to the controller, follow steps 1 to 10 of the Download


Controller procedure.
2. Click menu item Controller, then submenu item Upload

EN2Z-0937GE51 R0518 1404


CARE ONLINE SERVICE AND COMMISSIONING

or,
click on Upload from Controller icon on the toolbar.

RESULT: The upload starts. Action and status messages will be listed
while the upload proceeds.

1405 EN2Z-0937GE51 R0518


ONLINE SERVICE AND COMMISSIONING CARE

3. Click the Close button to finish the Upload.

Detect Baud rate

Purpose Scan for baud rate of the port where the controller is connected. This function can
be used if the connection to the controller is completed after XL Online has been
started, but the baud rate does not match.

Procedure 1. Click menu item File, then submenu item Detect Baudrate.

or,
click on Detect baudrate for current serial port icon on the toolbar.

RESULT: Software scans for baud rates and autodetects the baud rate
that matches to the baud rate of the controller.

NOTE: While detecting the baud rate, the ´Wait cursor` symbol appears and
no actions are possible.

Cancel Up- / Download

Purpose To correctly finish the up- or download, if for example, the communication was
interrupted during the process or, if you want to definitely cancel the up- or
download.

Procedure 1. In the Download application or Upload application dialog box, click the Cancel
button.

RESULT: A message is displayed asking, if you really want to cancel the


up- or download.

EN2Z-0937GE51 R0518 1406


CARE ONLINE SERVICE AND COMMISSIONING

RESULT: The current up- or download process is cancelled.

2. Click Yes button to cancel.

RESULT: The current up- or download process is cancelled.

Repair PRA File

Purpose To repair a corrupted PRA file. The repaired PRA file can then be used for proper
download.

Procedure 1. Click menu item File, then submenu items Support and Repair PRA file.

RESULT: The Repair PRA file dialog box displays.

1407 EN2Z-0937GE51 R0518


ONLINE SERVICE AND COMMISSIONING CARE

2. Open the corrupted PRA file by clicking the Open button and selecting it in the
Open dialog box.

RESULT: The PRA file data is displayed.

IMPORTANT
Check the data and make sure that they are correct by entering/selecting
the appropriate settings.

3. Normally controller and program name are the same. To change the program
name use check Program name checkbox and change program name.

4. The Sequence value is typically ´0`.

5. For all controller OS´s lower than 2.04, select ´1.00.xx … 1.01.xx` from the
Controller OS drop-down listbox.

6. Save the PRA file by clicking the Save button and saving it in the Save as
dialog box.

RESULT: The PRA file is repaired.

7. Click Close button.

EN2Z-0937GE51 R0518 1408


CARE ONLINE SERVICE AND COMMISSIONING

View/Change Application Parameters


Purpose To view and/or change parameters of the controller parameter file (.RAP).

Procedure 1. Click menu item General, then submenu items Application and Parameter.

Or, click the Show/hide parameter dialog button .

RESULT: The Application Parameter dialog box displays and software is


checking the parameter files (may take a few seconds). Finally
in the list at the top, the used parameter files are displayed.

2. To display the parameters for a parameter file, select the file in the top list and
click the Read Parameter button, or double-click on the file in the top list.

RESULT: In the list at the bottom, the parameters for the parameter file
are displayed.

1409 EN2Z-0937GE51 R0518


ONLINE SERVICE AND COMMISSIONING CARE

3. To display the descriptions for the displayed parameters, click the Import
Parameter Info button.

RESULT: The descriptions are displayed in the Description column in


the list at the bottom.

IMPORTANT
There is no consistency check for the matching text file. Selecting a wrong
text file results in wrong display.

EN2Z-0937GE51 R0518 1410


CARE ONLINE SERVICE AND COMMISSIONING

4. To view updated values generated during a RACL cycle, click the Refresh
Parameters button.

RESULT: The current parameter values will be displayed.

5. To change a parameter value, select the parameter in the list at the bottom.

6. Click the Value column, change the value and press ENTER key.

RESULT: The changed value has been written to the selected parameter
file.

1411 EN2Z-0937GE51 R0518


ONLINE SERVICE AND COMMISSIONING CARE

Monitor Z-Registers
Purpose Display of a selected z-register value as it changes in the controller and change the
value of a z-register. Z-registers can be accessed in general, from special flag
points, and from XFMs. When debugging XFMs, open the relevant application with
the RACL Editor in parallel. With the procedure described in this section you can
select and monitor any existing z-register.

Procedure 1. Click menu item General, then submenu item Z-register.

Or, click the Show/hide z-register dialog button .

RESULT: The Z-Register dialog box displays. The dialog box can be
displayed permanently while performing other functions in XL
Online.

2. To monitor a z-register, select the submodule and the z-register (index number)
in the fields of the same name and click the Add button. Max. 10 z-registers
can be monitored concurrently and displayed in the dialog box.

RESULT: The z-register is added to the list. Software polls the z-register
and displays updated values.

EN2Z-0937GE51 R0518 1412


CARE ONLINE SERVICE AND COMMISSIONING

3. To check z-register functions, select the z-register in the list.

4. Click the Value column, enter the value and press ENTER key.

RESULT: The value is written to the z-register. Software polls the z-


register and displays updated values. Note value changes

5. To remove a z-register, select the z-register in the list and click the Remove
button.

6. To end monitoring, close the dialog box.

NOTE: A changed z-register may be overwritten immediately by the


application.

Monitor X/Y-Registers
Purpose Display of a selected x/y register value as it changes in the controller and change
the value of an x/y register. X/Y registers can be accessed in general, from special
flag points, and from XFMs. When debugging XFMs, open the relevant application
with the RACL Editor in parallel. With the procedure described in this section you
can select and monitor any existing x/y register.

NOTE: For this you must know the submodule, the column and the index
number from the x/y register you want to monitor.

1413 EN2Z-0937GE51 R0518


ONLINE SERVICE AND COMMISSIONING CARE

Procedure 1. Click menu item General, then submenu item X/Y register.
Or, click the Show/hide x/y register dialog button .

RESULT: The X/Y Register dialog box displays. The dialog box can be
displayed permanently while performing other functions in XL
Online.

2. Click X or Y radio button dependent on which registers, x or y registers you


want to monitor.

3. Enter the submodule, column and register (index number) for the register in the
fields of the same name and click the Add button. Max. 10 x and 10 y registers
can be monitored concurrently and displayed in the dialog box.

RESULT: The x/y register is added to the list. Software polls the x/y
register and displays updated values.

4. To check x/y register functions, check the check box in the line.

EN2Z-0937GE51 R0518 1414


CARE ONLINE SERVICE AND COMMISSIONING

5. Click the Value column, enter the value and press ENTER key.

RESULT: The value is written to the x/y register. Software polls the x/y
register and displays updated values. Note value changes.

IMPORTANT
As long as the register is checked, the setting is permanent and the
controller cannot overwrite the value, even if XL Online is closed.

6. To remove an x/y register, select the x/y register in the list and click the
Remove button.

7. To end monitoring, close the dialog box.

Set RACL Cycle time

Procedure 1. Click menu item General, then submenu items Application and RACL
Cycletime.

RESULT: The RACL cycletime dialog box displays.

1415 EN2Z-0937GE51 R0518


ONLINE SERVICE AND COMMISSIONING CARE

2. To change the current cycle time, enter desired value in the New cycletime
field and click Set cycletime button.

3. To view the last ten RACL cycles that have been taken longer than the set
cycle time, click the Refresh statistics button

RESULT: If the case, the last ten RACL cycles are displayed with
execution time (duration) and start time in the Cycletime
statistics list.

EN2Z-0937GE51 R0518 1416


CARE ONLINE SERVICE AND COMMISSIONING

NOTE: For controller OS 2.0 and higher, the cycle time is automatically
adapted to the execution time, that is a set value may then be
changed.

Start / Stop Application


Purpose To start or stop the application running in the controller.

Procedure 1. Click menu item General, then submenu items Application and Start /Stop.

RESULT: The Start / Stop application dialog box displays. The current
status of the application parts are displayed.

2. To start a stopped application, click the Start button.

3. To stop a running application, click the Stop button.

RESULT: The application is stopped.

4. When stopping and starting the application, note alarms that may occur on the
Alarms tab and in the popup alert (if enabled in the XL Online Options dialog
box).

1417 EN2Z-0937GE51 R0518


ONLINE SERVICE AND COMMISSIONING CARE

5. Check Protocol check box if you want to save the start/stop changes
continuously in a log file called StartStop.log (saved in the current directory,
normally the CARE root directory).

NOTE: The data will only be saved to the log file as long as the Start / Stop
Application dialog box is opened.

View/Modify Time Programs


Purpose Display and modify time sequences for controller operation. For example, set HVAC
start and stop times.
Time Programs implement these command schedules. A controller can have a
maximum of 20 Time Programs.
Each Time Program specifies a list of points to command and a Weekly Program.
This Weekly Program defines the normal daily activity of the system by specifying
which Daily Programs a controller should use for each day of the week (Sunday
through Saturday). The Weekly Program applies for each week of the year. There is
only one Weekly Program per Time Program.
Daily Programs list points and point actions and times for the controller to
implement. Operators assign Daily programs to Weekly programs or as date
override to provide for automatic operations on scheduled dates.
Yearly Programs define time periods with special daily programs. Yearly programs
are suited to consider specific local conditions, for example, regional vacation and
public /religious festivals. Yearly programs can be defined for more than one year.

Example:

Controller 1
Time Program 1
Point Assignments
hvac_ctrl
min_hvac

Weekly Program Daily Program Name


Monday normal_daily
Tuesday normal_daily
Wednesday normal_daily
Thursday normal_daily
Friday normal_daily

Saturday Weekend
Sunday Weekend

Where the normal_daily Daily Program includes the following items


(time, user address, command):

06:00 hvac_ctrl on
18:00 hvac_ctrl off

And the Weekend Daily Program includes the following items (time, user
address, command):

12:01 min_hvac on
23:59 min_hvac off

EN2Z-0937GE51 R0518 1418


CARE ONLINE SERVICE AND COMMISSIONING

Today (Point) Overrides You can assign different commands and times to selected points within a time
program. These changes are "today overrides".

Date Overrides You can also assign temporary schedules to replace daily schedules when holidays
or other events occur that require different times and commands. These schedules
are "date overrides".

Open Time Program Editor

Procedure 1. Click menu item General, then submenu items Application and Time
Program.

RESULT: The Time program main window displays.

2. Open the tree on the left to display the available time programs. In this case
the time program ´Reception` is displayed.

1419 EN2Z-0937GE51 R0518


ONLINE SERVICE AND COMMISSIONING CARE

Close Time Program Editor

Procedure 1. In the Time program main window, click the Close button.

Override Today Schedule

Purpose Override a normal day´s activity for a selected point.

Procedure 1. Open the time program editor as described in the "Open Time Program Editor"
section.

2. In the tree, open the Today overrides folder and click on the point you want to
override.

RESULT: At the bottom, the status message and on the right, a pencil
icon indicates that the point has currently no override and can
be edited for overriding the today schedule.

EN2Z-0937GE51 R0518 1420


CARE ONLINE SERVICE AND COMMISSIONING

3. Click in the Start time column


Or, click menu item Override, then submenu item Edit Start time.

4. Enter the time when the override should start (the blue checkmark indicates the
editing mode of the field).

5. Press ENTER key.

6. Continue by setting the end time, the value and the optimize status in the
corresponding fields in the same manner as described in steps 3 through 5.
Use appropriate submenu items in the Override menu alternatively.

7. If desired, edit further points for overriding the schedule for today.

IMPORTANT
Once a Today schedule override has been set, it cannot be deleted. In
case you want to "delete" an override, set the start-end time difference to 1
min.

Modify Daily Schedule

Purpose Edit, create, rename or delete a daily schedule.

Procedures …

1421 EN2Z-0937GE51 R0518


ONLINE SERVICE AND COMMISSIONING CARE

Edit daily schedule 1. Open the time program editor as described in the "Open Time Program Editor"
section.

2. In the tree, open the Daily schedules folder and click on the daily program you
want to modify.

RESULT: On the right, all points assigned to the daily program are
displayed.

3. Select the point in the list.

4. Set the time, the value and the optimize status in the corresponding fields in
the same manner as described in steps 3 through 5 of the "Override Today
Schedule" section.

Add New Point 1. Click daily schedule in the tree.

2. Click menu item Switchpoint then submenu item Add and select the point.

EN2Z-0937GE51 R0518 1422


CARE ONLINE SERVICE AND COMMISSIONING

RESULT: The point is added to the list.

3. Set the time, the value and the optimize status in the corresponding fields in
the same manner as described in steps 3 through 5 of the "Override Today
Schedule" section.

Delete Point 1. To delete a point from the daily schedule, select the point in the list.

2. Click right mouse key and with left mouse key click Delete in the context menu.
Or, click menu item Switchpoint, then submenu item Delete.

RESULT: The point is deleted from the list.

1423 EN2Z-0937GE51 R0518


ONLINE SERVICE AND COMMISSIONING CARE

Overwrite Daily Schedule All points will be deleted. You can only overwrite a daily schedule that is not
used in any weekly, holiday or yearly program. To overwrite a daily schedule
with another daily schedule do the following

1. In the tree, click the daily schedule you want to overwrite.

2. Click right mouse key and with left mouse key, click on Overwrite with copy
from and select the daily schedule, in this case Weekday in the context menu.

Or, click menu item Daily, then submenu item Overwrite with copy from and
select the daily schedule.

RESULT: The selected daily schedule points will delete the current points.

Create New Daily Schedule 1. To create a new daily schedule, click on the Daily schedules folder in the tree.

2. Click right mouse key and with left mouse key, click on Create in the context
menu.
Or, click menu item Day, then submenu item Create.

3. In the folder, enter the name for the new daily schedule, e.g. ´Sunday`.

4. Add points to the new daily schedule by clicking menu Switchpoint, then
submenu item Add and selecting the desired point (see "Edit Daily Schedule"
section).

Rename Daily Schedule 1. To rename a daily schedule, click on the schedule in the tree.

2. Click right mouse key and with left mouse key, click on Rename in the context
menu.
Or, click menu item Day, then submenu item Rename.

3. Rename the flashing folder name.

EN2Z-0937GE51 R0518 1424


CARE ONLINE SERVICE AND COMMISSIONING

Delete Daily Schedule 1. To delete a daily schedule, click on the daily schedule.

2. Click right mouse key and with left mouse key, click on Delete in the context
menu.
Or, click menu item Day, then submenu item Delete.

NOTE: You can only delete a daily schedule that is not used in any weekly,
holiday or yearly program.

Modify Weekly Schedule

Purpose Define the weekly schedule for a controller be selecting the daily schedules the
controller should use each day (Sunday through Saturday) of a normal week.

Procedure 1. Open the time program editor as described in the "Open Time Program Editor"
section.

2. In the tree, click on the Weekly schedules folder.

RESULT: On the right, the week with its assigned daily schedules is
displayed.

3. To assign another daily schedule to a weekday, click on the weekday in the


Daily schedule column.

4. Select the desired daily schedule and press ENTER key.

NOTE: It is also possible to remove an assigned daily schedule by selecting


<not set>. This means, that on that day no daily schedule is executed.

1425 EN2Z-0937GE51 R0518


ONLINE SERVICE AND COMMISSIONING CARE

Modify Holiday Schedules

Purpose Holiday schedules are saved with the application and can be enabled or disabled
as a whole since they are country specific. To each holiday a daily schedule can be
assigned.

Procedure 1. Open the time program editor as described in the "Open Time Program Editor
section".

2. In the tree, click on the Holiday schedules folder.

RESULT: On the right, all holidays with its assigned daily schedules are
displayed. Note that the blue checkmark appears for the
enabled as well as for the disabled mode.

Enable/Disable Holiday Schedules 3. Click right mouse key and with left mouse key, click on Enable, respectively
Disable.

Assign Daily Schedules 5. To assign another daily schedule to a holiday, click on the holiday in the Daily
schedule column.

6. Select the desired daily schedule and press ENTER key.

NOTE: It is also possible to remove an assigned daily schedule by selecting


<not set>.

Modify Yearly Schedules

Purpose Setup exception for specific days (period) of the year.

Procedure 1. Open the time program editor as described in the "Open Time Program Editor"
section.

EN2Z-0937GE51 R0518 1426


CARE ONLINE SERVICE AND COMMISSIONING

2. In the tree, click on the Yearly schedules folder.

3. Click right mouse key and with left mouse key, click on Load in the context
menu.
Or, click menu item Year, then submenu item Load.

RESULT: The Yearly schedule range dialog box is displayed.

4. Open calendar by clicking the Start date drop-down listbox and define the start
date of the range.

5. Under period, define the desired duration by clicking the corresponding radio
button.

RESULT: On the right, the current yearly schedule is displayed for the
defined period. The weekdays show their assigned daily schedules.
For the assigned daily schedule, the following descending priority
is used: yearly schedule → holiday schedule → weekly schedule.

That is, by default a weekday has the daily schedules of the week
schedule assigned. If a weekday has a holiday schedule assigned,
the daily schedule of that holiday is used and the name of the
holiday is shown in the source column. Note, that in this case
holidays must be enabled. If a weekday is part of a yearly schedule
period, the daily schedule defined for that period is used. In the
source column ´Yearly schedule´ is displayed.

For each weekday the source of the assigned daily schedule is


indicated by the following icons and a description in the source
column:

Icon Assigned daily schedule Source Display


"according to the weekly schedule" "No display"

"according to the holiday schedule" Name of holiday

"according to the yearly schedule" Yearly schedule

IMPORTANT
When changing the daily schedule for a weekday, the weekday gets
always part of the yearly schedule as indicated by the source description
"yearly schedule" and the icon.

1427 EN2Z-0937GE51 R0518


ONLINE SERVICE AND COMMISSIONING CARE

6. To assign another daily schedule to a weekday, click on the weekday in the


Daily schedule column.

7. Select the desired daily schedule and press ENTER key.

NOTE: It is also possible to remove an assigned schedule by selecting <not


set>.

RESULT: In this case, for the defined period, on Wednesday 10.04.2002,


the daily schedule ´Sunday` will be used.

Reload Tree

Purpose Load the current schedules from the controller.

Procedure 1. In the Time program main window, click the Reload button.

RESULT: The tree is collapsed and the current schedules from the
controller were loaded.

EN2Z-0937GE51 R0518 1428


CARE ONLINE SERVICE AND COMMISSIONING

Set System Clock


Purpose To set the controller clock.

Procedure 1. Click menu item General, then submenu item System Clock.

RESULT: The Set controller clock dialog box displays.

Under Current controller clock, the current time in the controller


and whether the daylight saving time is enabled or disabled, is
displayed.

1429 EN2Z-0937GE51 R0518


ONLINE SERVICE AND COMMISSIONING CARE

2. To set a new time do one of the following:

To use the current PC clock as new time, check the Use PC clock checkbox
(default) and click the Set clock button.

RESULT: The controller clock is set to the current PC clock.

To set an individual time, uncheck the Use PC clock checkbox.


Into the Date and Time field, enter the desired time (each item part separately).

Or, click on the drop-down arrow at the Date field and select data in the
calendar (use keyboard arrows to scroll through). Close the calendar by
clicking on any location outside the calendar.
Or, use the scroll arrows at the time field to set the time.
Click the Set clock button

RESULT: The controller clock is set to the new individually set time.

3. To set daylight saving time (DST) do the following:

Check the Enable DST checkbox.

Under Daylight saving time, set the time in the From and To fields.
Click the Set DST button.

RESULT: The controller uses the set DST.

EN2Z-0937GE51 R0518 1430


CARE ONLINE SERVICE AND COMMISSIONING

Save Application in Flash ROM

Procedure 1. Click menu item General, then submenu items Flash ROM and Save
Application.

RESULT: The following dialog box displays.

2. To save the application in the Flash ROM, click OK button.

3. Confirm the following message.

NOTE: Saving an application to the Flash ROM can take up to 30 seconds.

Erase Flash ROM


Procedure 1. Click menu item General, then submenu item Flash ROM and Erase.

RESULT: The following dialog box displays.

2. To erase the Flash ROM, click OK button.

3. Confirm the following message.

NOTE: Erasing the Flash ROM can take up to two minutes.

1431 EN2Z-0937GE51 R0518


ONLINE SERVICE AND COMMISSIONING CARE

Work with MMI


XL Online provides an emulation of the XI581 AH / XI582 AH bus wide operator
interface to change basic information programmed into the Excel controller. For
detailed description on those functions, please refer to the XI581 AH/ XI582 AH
user guide, form EN2B-0126 (European) / 74-3554 (U.S.).

Start MMI Click on the MMI tab in the XL Online main window. The XL Online main window
displays. Software tries to connect to the port according to the settings defined in
the XL Online Options dialog box (see "Port Settings" section).

Connection and Display Problems If no controller is connected to the port or software cannot connect to the controller
due to wrong port settings, the MMI is gray and the status message No connection
is displayed. If a connection is completed and no application is running, the MMI is
blue and blank. If an application is running, the MMI is blue and the initial text is
shown.

Procedures 1. If the MMI is gray, connect the controller to the port as follows:

2. Click menu item File, then submenu item Connection.


Or, click on the Change serial port settings icon on the button bar.

3. In the Connect dialog box, select the serial port and the baudrate by clicking
the corresponding radio buttons. Select Auto detect, if you do not know the
baudrate (default setting).

4. Click the Connect button.

RESULT: If the connection is completed, the MMI is displayed in blue. If


no text is displayed, click on another tab or click the ESC button
on the MMI emulation.

5. Make sure that the controller number in CARE and in the MMI is the same. If
they are different, set them equal either in CARE or in the MMI or by Set
controller no. command (see "Set Controller Number and View Bus
Configuration" section). For operating instructions of the MMI refer to the
XI581/2 Operator Terminal Manual.

EN2Z-0937GE51 R0518 1432


CARE ONLINE SERVICE AND COMMISSIONING

Initial Screen

To work with the MMI, the buttons at the bottom must be used. Note that you cannot
click on selected items in the screen displays.

Example: To get from the initial screen (see above) to the next screen
(Continue item is highlighted) you must click the Enter button.

In the following, the operating buttons of the MMI emulation will be explained.

1433 EN2Z-0937GE51 R0518


ONLINE SERVICE AND COMMISSIONING CARE

Button Key Scroll Description


Escape, End the task you are performing and return to a previous display
delete, window.
backspace If you click this key after you modify a field, but before clicking
Enter, √, the XI581/2 erases any new information you input and
retains the original information.
If you click this key after you modify a field and press Enter, √,
the XI581/2 retains the new information you input.
left arrow Within a menu or a line of items, the left arrow moves the cursor
from one column (or item) to another.
Within a data field, the left arrow moves the cursor to the left one
digit.
up arrow Move the cursor to the previous field, the previous column, or to
the previous line in a column.

down arrow Move the cursor to the next field, the next column, or to the next
line in a column.

right arrow Within a menu or a line of items, the right arrow moves the
cursor from one column (or item) to another.
Within a data field, the right arrow moves the cursor to the right
one digit.

plus Increase the value of a digit by one (for example, from 2 to 3).
You can also use this key to change the condition of a digital
point. For example, click this key to flip a digital point from OFF
to ON.

minus Decrease the value of a digit by one (for example, from 2 to 1).
You can also use this key to change the condition of a digital
point. For example, click this key to flip a digital point from OFF
to ON.

Enter Enter and confirm input values or command choices for the
controller. When you click this key, it allows modification of the
highlighted field. Clicking Enter again stores the value in
memory.

Moving Between Columns To move horizontally between columns in a menu or list, press the down arrow key,
τ, until you reach the bottom of the column. When you click the down arrow key
again, the cursor automatically jumps to the first item in the next column.1
If the cursor is on the first item in the first column, clicking the right arrow key, ,
moves the cursor to the first item in the second column. If the cursor is on the last
item in the second column, clicking the down arrow key, τ, moves the cursor to the
first item in the first column.1
1 NOTE: In case not all entries are displayed (e.g. no password entered), this may
differ slightly.

Modifying a Field To change information in a field, first use the arrow keys to move to and highlight
the field. Then click, √. After the change is made, the Enter button must be clicked
again to confirm the change.

Moving From Field to Field Once you begin modifying the digits in a field, you can move from digit to digit within
that field using the arrow keys. However, to move to a different field, you must click
Enter, √, after making your last change to the field. The field is then highlighted. You
can then use the arrow keys to move to and highlight the next field you wish to
modify.

EN2Z-0937GE51 R0518 1434


CARE ONLINE SERVICE AND COMMISSIONING

Point Order in Lists Points are listed according to hardware type. In other words, all analog points
appear first, followed by digital points, and finally totalizer points.

Monitor Points

Load Points

Purpose To upload and view points from the controller

Procedure 1. Click on the Datapoints tab.


2. Click menu item Datapoints then submenu item Load points or click
button.

RESULT: All points except hidden points will be uploaded from the
controller and displayed.

1435 EN2Z-0937GE51 R0518


ONLINE SERVICE AND COMMISSIONING CARE

Apply Filter

You can apply a filter using wildcards (?) and jokers (*) to list certain points
according to their user address. The filter is case-sensitive. When composing the
search name, the list is instantly updated. By default all points are listed with the
joker * in the drop-down list. The user addresses can be sorted ascending or
descending by clicking on the User address column title.

Procedure 1. Into the drop-down listbox at the top, enter search name using wildcards and/
or jokers.

Example: In the following, all user addresses beginning with ´S` are displayed.

EN2Z-0937GE51 R0518 1436


CARE ONLINE SERVICE AND COMMISSIONING

Edit Points

Purpose Edit point values and write them to the controller.

Procedure 1. In the list on the left, click on datapoint.

RESULT: On the right pane, the datapoint´s attributes with value and unit
are displayed. The pencil icon indicates attributes that can be
edited. The lock icon indicates read-only attributes. In the
yellow field at the top the user address name is displayed.

NOTE: The points will not be polled. To refresh point values, double-click on
the point in the left list.

1437 EN2Z-0937GE51 R0518


ONLINE SERVICE AND COMMISSIONING CARE

2. In the left list, click on the point, you want to edit.

3. On the right pane, click into the Value column of the attribute.

4. Enter value and press ENTER key or click button.

RESULT: The value is written to the controller.

5. Note, that alarms that may occur and be displayed on the Alarms tab and/or in
the Alarm popup alert.

Set Points to Manual Mode Changing a point value via XL Online is handled by the controller internally as
follows:

The changed value is written to the Auto value field and by default automatically
copied to the Manu value field. RACL writes to the Auto value field and reads from
Manu value field. To disable the automatic copy, the manual mode option can be
set. In this case RACL always reads the given manual point value, which may differ
from the automatic point value.

Examples:

For a pseudopoint, use the automatic point value attribute and write a constant
value to the controller, e.g. room temperature = 26 degrees C.

For a digital output, set the manual mode and switch on a pump constantly by
setting the manual point value to ON.

Controller XL Online

RACL Point Edit Point Attributes


Writing Writing
Auto value Automatic point value

Set Manual Mode

Reading Writing
Manu value Manual point value

To set the manual mode, check the Manual Mode checkbox.

To enter a manual value, click into the Value field of the Manual point value
attribute and enter desired value.

EN2Z-0937GE51 R0518 1438


CARE ONLINE SERVICE AND COMMISSIONING

Set Point to Manual Mode

Procedure 1. Check Manual Mode checkbox to put a point into manual mode.

2. Note alarms that may occur and be displayed on the Alarms tab and/or in the
Alarm popup alert.

Select Points in Manual Mode

Purpose Highlights all points currently displayed that are in manual mode. Note, in case a
filter is applied, points will be searched only in the currently displayed list.

Procedure 1. Click menu item Datapoints, then submenu item Select points in manual
mode.

RESULT: Software is scanning and all found points are highlighted in


gray in the list.

1439 EN2Z-0937GE51 R0518


ONLINE SERVICE AND COMMISSIONING CARE

Clear Manual Mode for Selection

Purpose Sets all points that are in manual mode into automatic mode.

Procedure 1. Click menu item Datapoints, then submenu item Clear manual mode for
selection.

RESULT: Software is setting automatic mode for all selected points.

2. Note alarms that may occur and be displayed on the Alarms tab and/or in the
Alarm popup alert.

Add Points to Watch list

Purpose Add selected points to a watch list. In this watch list certain states for the points will
be polled and displayed. Points can be removed from the watch list and new points
can be added to the watch list. Multiple points can be added and saved to a group
for re-use. This group can also be used for trending.

Procedure 1. In the list select points by using left mouse key and STRG key, respectively
SHIFT key.

2. Click menu item Datapoints, then submenu item Add point to watchlist or
click button.

RESULT: In the Datapoint watch list window selected points are


displayed. Max. four points are polled and updated concurrently
as indicated by the flashing yellow light icon. The following
states are continuously updated:

Value
Displays the current value of the point.

Alarm
Shows whether the point is in alarm or not

Manual
Displays whether the point is in manual operation or not

Health status
Shows whether the I/O module, the point is assigned to,
communicates with the controller or not. ´No response` means
that there is no communication.

Local mode
Shows whether the point is in manual override or not.

Remove Point(s) from Watch list 1. In the Datapoint watchlist window, select points by using left mouse key and
STRG key, respectively SHIFT key.

2. Click menu item Datapoints, then submenu item Remove or press DEL key.

EN2Z-0937GE51 R0518 1440


CARE ONLINE SERVICE AND COMMISSIONING

RESULT: The selected points are removed from the list.

Save Point(s) in Group 1. Click menu item Groups, then submenu item Save as.

2. In the Save as dialog box, save the file.

RESULT: All points are saved in the .HGF file and can be re-used later.

Load Point Group 1. Click menu item Groups, then submenu item Load.

2. In the Open dialog box, open the .HGF file.

RESULT: The points of the group are displayed in the watch list and will
be polled. All previously loaded point will be removed from the
list.

Show Attributes for Watched 1. For a watched point in the Datapoint watchlist window, the attributes for the
Point on Datapoints tab point can be viewed concurrently on the Datapoints tab in the XL Online main
window.

2. In the Datapoint watchlist window, double-click on the point.

RESULT: In the following example, the ´DaTemp` datapoint has been


double-clicked. On the Datapoints tab, the point is highlighted
and its attributes are shown.

1441 EN2Z-0937GE51 R0518


ONLINE SERVICE AND COMMISSIONING CARE

View Watch list

Procedure 1. Click menu item View, then submenu item Watchlist.

RESULT: The Datapoints watchlist window displays showing the


previously watched points. Polling starts. Points not being found
in the controller, will be indicated by a green question mark
icon.

Trend Points
Purpose To graphically record point value changes. Datapoints to be recorded will be
defined and saved in an .HTF file. For the recorded trend data, time and used
datapoints are continuously saved block by block into a history file and can be
exported as .CSV file to MS Excel.

A trending session includes the following steps:

1. Initiate trending by creating a new or open an existing . HTF file


2. Select datapoints for recording
3. Start recording
4. Stop recording
5. Close trending

NOTE: Steps 1 to 4 create one block in the history file and can be repeatedly
done for different datapoint combinations (.HTF files). For one and the
same .HTF file, it is not possible to continue a stopped recording at
the same point (value/time) where is was finished. The new recording
starts from scratch. But, every record is saved as block in the history
file.

Procedure 1. Click Trend tab.

RESULT: The recording pane shows the recording status ´No Data` and
the Line info is empty.

EN2Z-0937GE51 R0518 1442


CARE ONLINE SERVICE AND COMMISSIONING

2. If you want to start the session with a new combination of datapoints, click
menu item Trend, then submenu item New.

3. In the Save as dialog box, enter the file name, e.g. AREA_EF and click Save
button.

Or,

If you want to open an already recorded combination of datapoints, click menu


item Trend, then submenu item Open.

In the Save as dialog box, select the file and click Save button.

RESULT: On the pane the recording status ´Stopped` is displayed. The


status line shows the .HTF file name, in this case
AREA_EF.HTF.

1443 EN2Z-0937GE51 R0518


ONLINE SERVICE AND COMMISSIONING CARE

4. Click menu item Trend, then submenu item Select datapoints.

RESULT: The Select Trend Points dialog box displays.

EN2Z-0937GE51 R0518 1444


CARE ONLINE SERVICE AND COMMISSIONING

5. Select datapoints for recording by checking the corresponding checkboxes. If


desired, use a filter by checking the Use filter checkbox and entering the filter
criteria in the same manner as described under the "Apply Filter section".

Or, select a point group previously created for the watch list as follows:
Click the Select group button. In the Open dialog box, enter the file name, e.g.
myGroup.HGF and click Open button. Note, that if a group is selected
datapoints previously checked as described in step 5 will be de-selected.

6. If desired, change the polling cycle time for points as follows:


Click into the Polling cycle time column for the point, select the value and
press the ENTER key.

7. Click Start button

RESULT: The points are copied to the Line info window. Software starts
trending as indicated by the recording status ´Recording`. The
actual record start time is centered in the yellow time scale at
the bottom.

8. In the Line info window, check the datapoints you want to display by clicking
the corresponding checkbox.

RESULT: In the Line info window, each point gets a display color by
accident and the current values are continuously displayed in
the Value column. On the recording pane, a colored line
graphically displays the point´s values. Start and end of the line
are enlarged.

1445 EN2Z-0937GE51 R0518


ONLINE SERVICE AND COMMISSIONING CARE

NOTE: All points will be recorded, even a point was not selected for graphical
display.

9. When recording multiple points, it is recommended to move the recording lines


by customizing the scales (see "Customize Scales" section).

10. To stop recording, click menu item Trend, then uncheck submenu item Start /
Stop recording or press button.

NOTE: It is not possible to continue a stopped recording at the same point


(value/time) where is was finished. The new recording starts from
scratch. But, every record is saved as block in the history file.

11. To directly start a new recording for the same datapoint combination press
button.

12. To start a new recording with a different datapoint combination, repeat steps 2
to 10.

13. To end the trend session, click menu item Trend, then submenu item Close.

Show/Hide Line Info Window

Procedure 1. To view/hide the Line info window, check/uncheck the Show Info submenu
item in the Trend menu.

EN2Z-0937GE51 R0518 1446


CARE ONLINE SERVICE AND COMMISSIONING

Customize Scales

The horizontal time scale and the vertical value scale can be customized while
recording and after the recording has been stopped. In case of multiple point
recording, the recording lines can be individually displayed by setting individual
scales for the points.

Customize Time Scale

The time scale can be set to three different time ranges and for each range different
resolutions can be adjusted.

Set Time Range With right mouse key, click on the gray area of the recording pane.

With left mouse key, click Time scaling, and then click desired time range in the
context menu:

1 hour
Displays 1 hour in the format hh.mm.ss (seconds not used and set to 00)

1 day
Displays 1 day in the format hh.mm.ss (seconds not used and set to 00)

Full range
Displays range covering the first and the last value in the format hh.mm.ss

Center Scale With left mouse key, double-click on the time scale to center the scale around the
current PC time.

Move View To move the viewed area to the left or right do the following:
Click on the coordinate axis area till a double arrow appears and move the line to
the left or right.

At the desired position, release left mouse key.

Change Resolution To change the resolution, click right mouse key over the time scale till the
magnifying glass symbol displays.

With pressed right mouse key, move the magnifying glass symbol horizontally to
the left or right and release right mouse key as soon as the desired resolution is
shown on the scale. Pressing SHIFT key concurrently speeds up the movement by
factor 3.

Examples: Range = full scale, resolution = 10, 15, 20 seconds

1447 EN2Z-0937GE51 R0518


ONLINE SERVICE AND COMMISSIONING CARE

Customize Value Scale


When starting a recording session, the value scale is set to default values, which
depend on the source of the datapoints (new selected points or a block from a
history file). For example, when starting a session from scratch, the minimum scale
value is ´-25` and the maximum value is ´100`. The recording lines start at the
shifted origin ´0`. The origin can be restored which means that the scale starts with
the value ´0` at the origin of the coordinate axes.

For each datapoint´s recording line, the scale values can be set individually. Scale
settings can be copied from one datapoint to another.

Set Min and Max Value In the Line info window, click into the Min. scale, respectively Max. scale column.
Type in value and press ENTER key.

Or, with left mouse key, click on the line.


On the left, the value scale appears.
Click on the coordinate axis area till a double arrow appears and move the line
up or down.
At the desired position, release the left mouse key.
Pressing SHIFT key concurrently speeds up the movement by factor 3.

Or, with left mouse key, click on the line.


Click right mouse key and with left mouse key, click on Full scale in the
context menu.
The scale is set to the range covering all recorded values of this time.

Note the min and max scale value changes in the Line info window.

NOTE: If a recording line cannot be clicked on, since it is not visible in the
recording pane, select the datapoint in the Line info window and set
proper scale values for re-display.

EN2Z-0937GE51 R0518 1448


CARE ONLINE SERVICE AND COMMISSIONING

Copy Scale Setting To copy a scale setting from one point to another do the following:

Click on the recording line, in this case the lower one, or select datapoint in the Line
info window.

Click right mouse key, and with left mouse key click Value scaling and Copy in the
context menu.

Click on the recording line, in this case the upper one, or select datapoint in the
Line info window to which you want to copy the scale setting.

1449 EN2Z-0937GE51 R0518


ONLINE SERVICE AND COMMISSIONING CARE

Click right mouse key, and with left mouse key click Value scaling and Paste in the
context menu.

RESULT: The upper line gets the scale settings of the below line which is
now covered.

Move baseline To move the baseline of a recording line upwards or downwards do the following:

Click on the recording line.


On the left, click on the coordinate axis area of the value scale till a double arrow
appears and move the line up or down.
At the desired position, release the left mouse key.
Pressing SHIFT key concurrently speeds up the movement by factor 3.

EN2Z-0937GE51 R0518 1450


CARE ONLINE SERVICE AND COMMISSIONING

Change Resolution Changing the resolution for the value scale can be done in the same manner as
described for the Time scale.

Restore Baseline Click on the recording line.

RESULT: On the left, the value scale displays.

1451 EN2Z-0937GE51 R0518


ONLINE SERVICE AND COMMISSIONING CARE

Double-click on the value scale.

RESULT: The baseline is set to the origin, that is, the scale starts with the
value ´0` at the origin of the coordinate axes.

EN2Z-0937GE51 R0518 1452


CARE ONLINE SERVICE AND COMMISSIONING

View Record History

Purpose To view recording blocks by time and datapoints.

Procedure 1. Click menu item Trend, then submenu item History.

RESULT: The Trend data history dialog box displays. The recordings are
displayed with start time (First value) and end time (Last
value) in the Recordings in file list field.

2. To view the recorded datapoints of a record, click on the record in the list.

RESULT: In the Datapoints in record field, the datapoints, which are


recorded in this time frame, are displayed.

1453 EN2Z-0937GE51 R0518


ONLINE SERVICE AND COMMISSIONING CARE

3. Close the Trend data history dialog box by clicking OK or Cancel button.

Export Record Data

Purpose To export records as .CSV file to e.g. MS Excel.

Procedure 1. Click menu item Trend, then submenu item Data Export.

RESULT: The Export data dialog box displays. The recordings are listed
with start time (First value) and end time (Last value) in the
Recordings in file list field.

EN2Z-0937GE51 R0518 1454


CARE ONLINE SERVICE AND COMMISSIONING

2. To view the recorded datapoints of a record, click on the record in the list.

RESULT: In the Datapoints in record field, the datapoints are displayed.

3. If you want to except a datapoint´s data from the export, uncheck the point.

4. If you want to export not the complete time frame of a record, uncheck the
Export all checkbox and set the time frame in the From and To fields on the
right.

5. Click the Export button.

6. In the Save as dialog box, enter the name for the .CSV file and click the Save
button.

View Alarms
Purpose View critical and non-critical alarms.

Critical alarms are controller system alarms and alarms that arise for points that
have the critical alarm attribute assigned. Non-critical alarms arise for points that
have the non-critical alarm attribute assigned.

Datapoint attribute related alarms arise due to limiting value exceeding or


undershooting of either the critical or non-critical attribute value.

When controllers report alarms, they report critical alarms first, then any non-critical
alarms they may have.

NOTE: Alarms are displayed. They can be cleared but not acknowledged.
Alarms can be saved into a printable log file. New alarms will be added
continuously to the end of the log file. An alarm history file is not
available.

Alarms will be displayed on the Alarms tab by default and in an additional popup
alert (optional).

1455 EN2Z-0937GE51 R0518


ONLINE SERVICE AND COMMISSIONING CARE

Check the general alarm settings (see "Alarms Settings" section) for new alarm
insertion, popup alert display and log file creation.

Procedure 1. Click on the Alarms tab.

NOTE: The Alarms icon is flashing on the Alarm tab as long as the
tab has not been selected yet.

RESULT: The alarms are displayed as follows:

Critical alarms are indicated by the red icon, non-critical alarms


are indicated by the icon. For each alarm the following
information is displayed:

Time
Time when the alarm was generated

EN2Z-0937GE51 R0518 1456


CARE ONLINE SERVICE AND COMMISSIONING

Alarm text
System alarm text of the controller

Datapoint
Name of datapoint

Datapoint value
Value of the datapoint when the alarm was generated

User text
Alarm text attribute defined for the datapoint.

2. To clear the list from certain alarms, select alarms by using STRG and/or
SHIFT key and click menu item Alarm, then submenu item Clear selection.

3. To clear the list completely, click menu item Alarm, then submenu item Clear
all.

View Alarms in Popup Alert

Purpose To display new alarms in an additional popup alert.

Procedure 1. To enable the popup alert display, see "Alarms Settings" section.

RESULT: New alarms will be displayed additionally in a popup alert. Both,


critical and non-critical alarms are displayed one after the other
with time, alarm text, datapoint name, value and user-defined
text.

2. Check and respond to the alarms.

3. To clear an alarm, click the OK button.

4. To clear all alarms, close the dialog by clicking the Close icon at the top right
corner.

NOTE: The yellow icon on the right remains the same for both, critical and
non-critical alarms.

View Alarm History Buffer

Purpose To display the alarm messages saved in the alarm history buffer.

Procedure 1. Click menu item Alarm, then submenu item Alarm History Buffer.

RESULT: At max. the last 99 messages from the alarm history buffer are
displayed (use scroll buttons on the left).

1457 EN2Z-0937GE51 R0518


ONLINE SERVICE AND COMMISSIONING CARE

2. To view just the currently active alarms, click Active Alarms button.

View Controller Status


Purpose To view controller status information such as:

• Controller name, number, device type


• Application status and parts
• Hardware configuration

Procedure 1. Click on the Controller tab in the XL Online main window.

EN2Z-0937GE51 R0518 1458


CARE ONLINE SERVICE AND COMMISSIONING

2. Check controller status information.

3. To print the controller status information in HTML format, click menu item File,
then submenu item Print.

NOTE: Under IP Bus hardware configuration only those modules are listed
that are physically connected and used by the application.

1459 EN2Z-0937GE51 R0518


ONLINE SERVICE AND COMMISSIONING CARE

Refresh Controller Status


Procedure 1. To refresh the controller status information on the Controller tab, click menu
item Controller, then submenu item Refresh Info, or click the icon on the
button bar or press F5 key.

RESULT: The controller status display on the Controller tab is refreshed.

Set Controller Number/View Bus Interface Configuration


Purpose To set the controller number the same as in the
translated application if they are different. To view the bus interface
configuration such as bus ID and baudrate.

NOTE: The controller number of EXCEL 5000 controllers can only be changed
for OS 2.04 and higher. For controller OS lower 2.04 the MMI emulation
must be used. For the OPS controller, the controller number cannot be
set.

Bus configuration data are only displayed for OS 2.06.02 and higher

Procedure 1. Click menu item Controller, than submenu item Bus configuration.

RESULT: The Bus interface configuration dialog box is displayed.

2. From the New controller no. drop-down listbox, select the controller number
you want to change the controller to.

3. Click the Set and then the Close button.

Download Firmware
Purpose Download firmware, e.g. in case of firmware updates, into an Excel controller with
flash EPROM.

Procedure 1. Click menu item Controller, then submenu item Firmware download.

EN2Z-0937GE51 R0518 1460


CARE ONLINE SERVICE AND COMMISSIONING

RESULT: The Firmware download dialog box displays.

1461 EN2Z-0937GE51 R0518


ONLINE SERVICE AND COMMISSIONING CARE

RESULT: Under current controller firmware, the status information of the


firmware is displayed.

2. If you want to download a new firmware, click File button and select the desired
firmware (.XXC file).

NOTE: xx are the last two digits of the OS Version.

Example: XL500204.02c for OS 2.04.02 of Excel 500 controller

3. Click Start Download button if you want to download the firmware.

RESULT: The download process is displayed under the Download


status fields.

4. After download is finished, click the Close button.

Download Application Remotely


For detailed information please refer to the Download Application Remotely
subsection in the LONWORKS NETWORK ENGINEERING section.

EN2Z-0937GE51 R0518 1462


CARE

APPENDIX
APPENDIX A: CONTROL ICONS
APPENDIX B: ENGINEERING UNITS
APPENDIX C: POINT ATTRIBUTES TABLES
APPENDIX D: PLANT CONTROLLER UPGRADES AND DOWNGRADES
APPENDIX E: CHECK UTILITY
APPENDIX F: ERROR MESSAGES

1463 EN2Z-0937GE51 R0518


CARE

EN2Z-0937GE51 R0518 1464


CARE APPENDIX A: CONTROL ICONS

APPENDIX A: CONTROL ICONS


Purpose Control icons provide preprogrammed functions and algorithms to
implement sequences of control in a plant schematic.
Control icon symbols list in the left-hand column of the control strategy
window.

Celsius vs. Fahrenheit Some control icons use metric units, for example, Celsius instead of
Fahrenheit for temperatures. If you want to use English units, you must
convert any English inputs to metric units before input to a control icon or
switching logic. Use the MAT editor to perform the conversion.

If the icons in a control loop use consistent engineering units for all inputs
and outputs, it is not necessary to perform a conversion.
Control Icon Manual For a complete description of each control icon as well as application
examples, see Excel CARE Control Icons User Guide EN2Z-0940 (Europe).

1465 EN2Z-0937GE51 R0518


APPENDIX C: POINT ATTRIBUTES TABLES CARE

APPENDIX B: ENGINEERING UNITS


NOTE: This section applies to CARE XL-5000 only.

Purpose This chapter lists engineering units available in the system for points and
pseudopoints. There are two types: analog and digital.

Analog

Index Decimal Example


Numbe Eng. Unit Places Dec. Pl. Description
r
1 0 x BLANK
2 °C 0 x Celsius (no decimal)
3 °C 1 x.x Celsius (one decimal)
4 °C 2 x.xx Celsius (two decimal)
5 °C 3 x.xxx Celsius (three decimal)
6 K 0 x Kelvin (no decimal)
7 K 1 x.x Kelvin (one decimal)
8 K 2 x.xx Kelvin (two decimal)
9 K 3 x.xxx Kelvin (three decimal)
10 Deg 0 x degrees Fahrenheit (no
decimal
11 Deg 1 x.x degrees Fahrenheit (one
decimal)
12 Deg 2 x.xx degrees Fahrenheit (two
decimal)
13 Deg 3 x.xxx degrees Fahrenheit (three
decimal)
14 Inw 0 x inches of water column (no
decimal)
15 Inw 1 x.x inches of water column (one
decimal)
16 Inw 2 x.xx inches of water column (two
decimal)
17 Inw 3 x.xxx inches of water column
(three decimal)
18 GPM 0 x Gallons per minute (no
decimal)
19 GPM 1 x.x Gallons per minute (one
decimal)
20 CFM 0 x Cubic feet per minute (no
decimal)
21 CFM 1 x.x Cubic feet per minute (one
decimal)
22 KFM 0 x 1000 cubic feet per minute
(no decimal)
23 KFM 1 x.x 1000 cubic feet per minute
(one decimal)
24 KFM 2 x.xx 1000 cubic feet per minute
(two decimal)
25 FPM 0 x Feet per minute (no
decimal)
26 FPM 1 x.x Feet per minute (one
decimal)
27 Hr 0 x Hours (no decimal)

EN2Z-0937GE51 R0518 1466


CARE APPENDIX C: POINT ATTRIBUTES TABLES

28 Hr 1 x.x Hours (one decimal)


29 Min 0 x Minutes (no decimal)
30 Min 1 x.x Minutes (one decimal)
31 Sec 0 x Seconds (no decimal)

1467 EN2Z-0937GE51 R0518


APPENDIX C: POINT ATTRIBUTES TABLES CARE

32 Day 0 x Day (no decimal)


33 Day 1 x.x Day (one decimal)
34 Cnt 0 x Count (no decimal)
35 kW 0 x Kilowatt (no decimal)
36 kW 1 x.x Kilowatt (one decimal)
37 kW 2 x.xx Kilowatt (two decimal)
38 kW 3 x.xxx Kilowatt (three decimal)
39 MW 0 x Megawatts (no decimal)
40 MW 1 x.x Megawatts (one decimal)
41 MW 2 x.xx Megawatts (two decimal)
42 MW 3 x.xxx Megawatts (three decimal)
43 kWH 0 x Kilowatt hours (no decimal)
44 kWH 1 x.x Kilowatt hours (one decimal)
45 kWH 2 x.xx Kilowatt hours (two decimal)
46 kWH 3 x.xxx Kilowatt hours (three
decimal)
47 MWH 0 x Megawatts per hour (no
decimal)
48 MWH 1 x.x Megawatts per hour (one
decimal)
49 MWH 2 x.xx Megawatts per hour (two
decimal)
50 MWH 3 x.xxx Megawatts per hour (three
decimal)
51 Pos 0 x Position (no decimal)
52 Pos 1 x.x Position (one decimal)
53 Pos 2 x.xx Position (two decimal)
54 Pct 0 x Percent (no decimal)
55 Pct 1 x.x Percent (one decimal)
56 Pct 2 x.xx Percent (two decimal)
57 Val 0 x Value (no decimal)
58 Tot 0 x Totalizer (no decimal)
59 PSI 0 x Pounds per square inch (no
decimal)
60 PSI 1 x.x Pounds per square inch
(one decimal)
61 PSI 2 x.xx Pounds per square inch
(two decimal)
62 V 0 x Volts (no decimal)
63 V 1 x.x Volts (one decimal)
64 V 2 x.xx Volts (two decimal)
65 mA 0 x Milliamperes (no decimal)
66 mA 1 x.x Milliamperes (no decimal)
67 A 0 x Amperes (no decimal)
68 A 1 x.x Amperes (one decimal)
69 A 2 x.xx Amperes (two decimal)
70 BTU 0 x British Thermal Unit (no
decimal)
71 BTU 1 x.x British Thermal Unit (one
decimal)
72 W 0 x Watts (no decimal)
73 RH 0 x Relative humidity (no
decimal)
74 RH 1 x.x Relative humidity (one
decimal)
75 Hz 0 x Hertz (no decimal)

EN2Z-0937GE51 R0518 1468


CARE APPENDIX C: POINT ATTRIBUTES TABLES

76 WBF 0 x Wet-bulb fahrenheit (no


decimal)
77 WBF 1 x.x Wet-bulb fahrenheit (one
decimal)
78 Ton 0 x Tons (no decimal)
79 Ton 1 x.x Tons (one decimal)
80 TnH 0 x Tons per hour (no decimal)
81 TnH 1 x.x Tons per hour (one decimal)
82 DPT 0 x Dew-point temperature (no
decimal)
83 BPH 0 x BTU per hour (no decimal)
84 MBH 0 x 1000 BTU per hour (no
decimal)
85 PPH 0 x Parts per hour (no decimal)
86 m/K 0 x Meters per Kelvin
87 m/K 1 x.x Meters per Kelvin
88 %/K 0 x Percent per Kelvin
89 %/K 1 x.x Percent per Kelvin
90 gkg 0 x Gram per kilogram
91 gkg 1 x.x Gram per kilogram
92 gkg 2 x.xx Gram per kilogram
93 gkg 3 x.xxx Gram per kilogram
94 Wm2 0 x Watts per square meter
95 h_m 2 x.xx hours and minutes
96 m_s 2 x.xx minutes and seconds
97 GWh 0 x Gigawatthours
98 GWh 1 x.x Gigawatthours
99 GWh 2 x.xx Gigawatthours
100 GWh 3 x.xxx Gigawatthours
101 GW 0 x Gigawatts
102 GW 1 x.x Gigawatts
103 GW 2 x.xx Gigawatts
104 GW 3 x.xxx Gigawatts
105 W 0 x Watts
106 W 1 x.x Watts
107 W 2 x.xx Watts
108 W 3 x.xxx Watts
109 J 0 x Joules
110 J 1 x.x Joules
111 J 2 x.xx Joules
112 J 3 x.xxx Joules
113 KJ 0 x Kilojoules
114 KJ 1 x.x Kilojoules
115 KJ 2 x.xx Kilojoules
116 KJ 3 x.xxx Kilojoules
117 MJ 0 x Megajoules
118 MJ 1 x.x Megajoules
119 MJ 2 x.xx Megajoules
120 MJ 3 x.xxx Megajoules
121 GJ 0 x Gigajoules
122 GJ 1 x.x Gigajoules
123 GJ 2 x.xx Gigajoules
124 GJ 3 x.xxx Gigajoules

1469 EN2Z-0937GE51 R0518


APPENDIX C: POINT ATTRIBUTES TABLES CARE

125 TJ 0 x Terajoules
126 TJ 1 x.x Terajoules
127 TJ 2 x.xx Terajoules
128 TJ 3 x.xxx Terajoules
129 0 x
130 Pa 0 x Pascals
131 Pa 1 x.x Pascals
132 Pa 2 x.xx Pascals
133 Pa 3 x.xxx Pascals
134 kPa 0 x KiloPascals
135 kPa 1 x.x KiloPascals
136 kPa 2 x.xx KiloPascals
137 kPa 3 x.xxx KiloPascals
138 bar 0 x Bar
139 bar 1 x.x Bar
140 bar 2 x.xx Bar
141 bar 3 x.xxx Bar
142 N/m 0 x Newtons per meter
143 N/m 1 x.x Newtons per meter
144 N/m 2 x.xx Newtons per meter
145 N/m 3 x.xxx Newtons per meter
146 p 0 x Pound
147 p 1 x.x Pound
148 p 2 x.xx Pound
149 p 3 x.xxx Pound
150 kp 0 x Kilopound
151 kp 1 x.x Kilopound
152 kp 2 x.xx Kilopound
153 kp 3 x.xxx Kilopound
154 Mp 0 x Megapound
155 Mp 1 x.x Megapound
156 Mp 2 x.xx Megapound
157 Mp 3 x.xxx Megapound
158 N 1 x.x Newtons
159 N 2 x.xx Newtons
160 N 3 x.xxx Newtons
161 g 0 x Grams
162 g 1 x.x Grams
163 g 2 x.xx Grams
164 g 3 x.xxx Grams
165 Kg 0 x Kilograms
166 Kg 1 x.x Kilograms
167 Kg 2 x.xx Kilograms
168 Kg 3 x.xxx Kilograms
169 t 0 x Metric ton
170 t 1 x.x Metric ton
171 t 2 x.xx Metric ton
172 t 3 x.xxx Metric ton
173 mm 0 x Millimeters
174 cm 0 x Centimeters
175 m 1 x.x Meters
176 m 2 x.xx Meters
177 m 3 x.xxx Meters

EN2Z-0937GE51 R0518 1470


CARE APPENDIX C: POINT ATTRIBUTES TABLES

178 km 0 x Kilometers
179 km 1 x.x Kilometers
180 km 2 x.xx Kilometers
181 km 3 x.xxx Kilometers
182 m/s 0 x Meters per second
183 m/s 1 x.x Meters per second
184 kmh 0 x Kilometers per hour
185 kmh 1 x.x Kilometers per hour
186 spG 3 x.xxx Specific weight
187 Ent 1 x.x Enthalpy
188 Ent 2 x.xx Enthalpy
189 Ent 3 x.xxx Enthalpy
190 SpW 2 x.xx Specific heat
191 W1z 3 x.xxx Heat number
192 m2 3 x.xxx Square meters
193 m3 0 x Cubic meters
194 m3 1 x.x Cubic meters
195 m3h 0 x Cubic meters per hour
196 m3h 1 x.x Cubic meters per hour
197 m3s 0 x Cubic meters per second
198 m3s 1 x.x Cubic meters per second
199 0 x Blank
!200 Hr 0 x Hours (no decimal)
!201 Min 0 x Minutes (no decimal)
!202 Sec 0 x Seconds (no decimal)
!203 Pct 0 x Percent (no decimal)
!204 K/K 1 x.x Kelvin per Kelvin
!205 K/K 2 x.xx Kelvin per Kelvin
!206 K/K 3 x.xxx Kelvin per Kelvin
!207 kHz 1 x.x Kilohertz
!208 kHz 2 x.xx Kilohertz
!209 kHz 3 x.xxx Kilohertz
210 kVa 1 x.x Kilo Voltamperes
211 kVa 2 x.xx Kilo Voltamperes
212 kVa 3 x.xxx Kilo Voltamperes
213 VA 0 x Voltamperes
214 VA 1 x.x Voltamperes
215 VAR 0 x
216 VAR 1 x.x
217 kV 0 x Kilovolts
218 kV 1 x.x Kilovolts
219 0 x
220 con 0 x Constant
221 con 1 x.x Constant
222 con 2 x.xx Constant
223 con 3 x.xxx Constant

1471 EN2Z-0937GE51 R0518


APPENDIX C: POINT ATTRIBUTES TABLES CARE

224 0 x
225 I/O 0 x Input/Output
226 klx 0 x Kilolux
227 klx 1 x.x Kilolux
228 k/h 0 x Kelvin per hour
229 k/h 1 x.x Kelvin per hour
230 I 0 x Blank
231 I 1 x.x Blank
232 I 2 x.xx Blank
233 I 3 x.xxx Blank
234 I 0 x Blank

EN2Z-0937GE51 R0518 1472


CARE APPENDIX C: POINT ATTRIBUTES TABLES

Digital

Index Number Active Status Passive Status


Text Text
1 Normal Alarm
2 Night Day
3 Disable Enable
4 Heating Cooling
5 Local Remote
6 Manual Auto
7 Unoccupied Occupied
8 Off On
9 Open Close
10 Winter Summer
11 Slow Fast
12 Low High
13 On Off
14 Alarm Normal
15 Close Open
16 Enable Disable
17 Occupied Unoccupied
18 on off
19 on off
20 on off

1473 EN2Z-0937GE51 R0518


APPENDIX C: POINT ATTRIBUTES TABLES CARE

EN2Z-0937GE51 R0518 1474


CARE APPENDIX C: POINT ATTRIBUTES TABLES

APPENDIX C: POINT ATTRIBUTES TABLES


NOTE: This section applies to CARE XL-5000 only.

Each point in a controller has associated attributes such as user address, technical
address, and descriptor. The Data Point Editor described in the Editors chapter of
this manual provides dialog boxes that specify attributes (fields and values) for each
point type in a controller.
Point attributes in the CARE database may not be available for editing in an off-line
editor such as the Excel Building Supervisor (“XBS”) operator terminal or the
XI518/XI582 operator terminals. Likewise, some attributes may be in controller files,
but not available for import from the controller into the CARE database.

This chapter contains tables for each point type. The tables list point attributes and
presents the following information for each:

• Field description specifies either the attribute name in the related point
editor dialog box or the use of the field in CARE.
• Field range specifies the possible values of the field.
• In CARE Database specifies whether or not it is stored in CARE
databases that are Version 1.5.1 or later. Previous database versions do
not necessarily store the same fields.
• Whether or not the attribute is available for off-line editing. “Off-line”
editing refers to changes made to database values while the controller is
not active in the system. In other words, when you are using CARE to
change copies of controller files, not the files in the actual controller.
• Whether or not the attribute is available for on-line editing. “On-line”
editing refers to changes made to controller files while the controller is
active. For example, if you are using an XBS operator terminal to change
field values in a controller while it is operating.
• Whether or not the attribute can be imported via the Import Controller
function (menu item Database, dropdown items Import, Controller).
Import Controller Files in the File Management chapter describes the
import procedure.

This information is useful when you are importing controller files or setting initial
values for attributes that can be changed in an on-line editor.

Table Definitions User address and technical address are attributes that apply to every point.
Following are definitions and ranges for each field.

User
Address Point name (maximum of 18 alphanumeric characters)
assigned to a point for operator use in locating and
commanding the point. Examples: Room temp floor 1 and
Flow temp G/floor. This name and the descriptor further
define the point. This name must be unique within a
controller.

User addresses must include one non-digit character and


cannot include Tabs, double quotes, ?, *, or space
characters. All other ASCII characters are allowable (A-Z,
0-9, +, -, _, etc). For example, 12A is a valid user address,
but 12 is not.

Technical
Address Internal six-digit number that defines and locates a point
in the system. The number is composed of three pairs
representing controller number (0-30), module number (1-

1475 EN2Z-0937GE51 R0518


APPENDIX C: POINT ATTRIBUTES TABLES CARE

16), and I/O number (1-12). Example: 010310 meaning


Controller 1, Module 3, I/O 10.
Analog Input Point Type
Datapoint Editor Attributes
Field Description Field In CARE Off-line On-line Imported?
Range Database Editing? Editing?
User Address 18 yes yes no no (create)
alphanumeri
c characters
Technical Address of point 6 digits yes yes, with no yes (for
(controller, board, point) Technical nonexistent
Address only)
dialog box
Descriptor (index into table of point 0 to 64 yes yes XBS yes
descriptors)
Operator Access Level 1 to 4 yes yes no yes
Write Protect Priority 0 to 3 yes no no yes
Engineering Unit (index into table of 0 to 235 yes yes no yes
analog engineering units)
Characteristic (index into table of 0 to 255 yes yes no yes
linearization tables)
Alarm Text (index into table of alarm 0 to 128 yes yes XBS yes
text strings)
Low Alarm Limit (lower alarm limit) yes (as yes (as XBS (as yes
float) float) float)
Low Warning Limit (lower warning yes (as yes (as XBS (as yes
limit) float) float) float)
High Warning Limit (upper warning yes (as yes (as float XBS (as yes
limit) float) float)
High Alarm Limit (upper alarm limit) yes (as yes (as XBS (as yes
float) float) float)
Alarm Delay (time in seconds) 0 to 65535 yes yes XBS yes
Suppress Alarm (indicates alarm 0 or 1 yes yes XBS yes
disabled [1] or enabled [0])
Alarm Type (indicates critical [1] or 0 or 1 yes yes XBS yes
non-critical)
Point Subtype 0 to 255 yes no no yes (for
nonexistent
only)
Hide Point (indicates, if point is 0 or 1 yes yes yes yes
visible=no [0] or hidden=yes [1]
Trend cycle (time in minutes) 0-65535 yes yes yes yes

Other Attributes
Field Description Field In CARE Off-line On-line Imported?
Range Database Editing? Editing?
number of technical addresses 0 to 255 yes no no yes
(future)
manual point value 0 to 4095 yes (initial no XBS yes
value stored
as a float)
current point value 0 to 4095 yes no no yes
last modification date yes no no yes
indicates negative slope for 0 or 1 yes no no no
linearization table
indicates manual mode (1) 0 or 1 yes no XBS yes
indicates if point is in alarm (1) 0 or 1 yes no no yes
indicates if trend is enabled (1) 0 or 1 yes no 581 yes
indicates if point should be refreshed 0 or 1 yes no XBS no
(1) (trending)
A/D (sensor) offset* for ai point -32767 to yes (as yes XBS (as float) yes
32768 float)

EN2Z-0937GE51 R0518 1476


CARE APPENDIX C: POINT ATTRIBUTES TABLES

No Response (indicates, if 0 or 1 no no no no
communication between controller
and DIO module is interrupted, yes
[1], no [0])
DIO Remote (indicates, if point is in 0 or 1 no no no no
manual override by a DIO module,
yes [1], no [0])
* A/D offset must be imported with current value because the offset is stored in the controller as a number of counts
that is relative to the "current" value.

Analog Output Point Type


Datapoint Editor Attributes
Field Description Field In CARE Off-line On-line Imported
Range Database Editing? Editing? ?
User Address 18 yes yes no no
alphanumeri (create)
c characters
Technical Address of point 3 digits yes yes, with no yes (for
(controller, board, point) Technical nonexiste
Address nt only)
dialog box
Descriptor (index into table of point 0 to 64 yes yes XBS yes
descriptors)
Operator Access Level 1 to 4 yes yes no yes
Write Protect Priority 0 to 3 (1- yes no XBS yes
255)
Engineering Unit (index into table of 0 to 235 yes yes no yes
analog engineering units)
Characteristic (index into table of 0 to 255 yes yes no yes
linearization tables)
Point Subtype 0 to 255 yes no no yes (for
nonexiste
nt only)
Time to Close (in seconds) yes yes XBS yes
Time to Open (in seconds) yes yes XBS yes
Suppress Alarm (indicates alarm 0 or 1 yes yes XBS yes
disabled [1])
Hide Point (indicates, if point is 0 or 1 yes yes yes yes
visible=no [0] or hidden=yes [1]
Trend cycle (time in minutes) 0-65535 yes yes yes yes

Other Attributes
Field Description Field In CARE Off-line On-line Imported
Range Database Editing? Editing? ?
number of technical addresses 0 to 255 yes no no yes
manual point value 0 to 4095 yes (initial no XBS yes
value stored
as float)
current point value 0 to 4095 yes no no yes
indicates manual mode (1) 0 or 1 yes no XBS yes
indicates if trend is enabled (1) 0 or 1 yes no XI581/XI582 yes
indicates if point should be 0 or 1 yes no XBS no
refreshed (1) (trending)
No Response (indicates, if 0 or 1 no no no no
communication between controller
and DIO module is interrupted, yes
[1], no [0])
DIO Remote (indicates, if point is in 0 or 1 no no no no
manual override by a DIO module,
yes [1], no [0])

1477 EN2Z-0937GE51 R0518


APPENDIX C: POINT ATTRIBUTES TABLES CARE

Pseudo Analog Point Type


Datapoint Editor Attributes
Field Description Field In CARE Off-line On-line Imported?
Range Database Editing? Editing?
User Address 18 yes yes no no
alphanumeri
c
characters*
Descriptor (index into table of point 0 to 64 yes yes XBS yes
descriptors)
Operator Access Level 1 to 4 yes yes no yes
Write Protect Priority 0 to 3 (1- yes no XBS yes
255)
Initialization Value (manual point yes (initial yes XBS yes
value) value
stored as
float)
Engineering Unit (index into table of 0 to 235 yes yes no yes
analog engineering units)
Alarm Text (index into table of alarm 0 to 128 yes yes XBS yes
text strings)
Low Alarm Limit (lower alarm limit) yes yes XBS yes
Low Warning Limit (lower warning yes yes XBS yes
limit)
High Warning Limit (upper warning yes yes XBS yes
limit)
High Alarm Limit (upper alarm limit) yes yes XBS yes
Suppress Alarm (indicates alarm 0 or 1 yes yes XBS yes
disabled [1])
Alarm Type (indicates critical [1] or 0 or 1 yes yes XBS yes
non-critical [0])

Hide Point (indicates, if point is 0 or 1 yes yes yes yes


visible=no [0] or hidden=yes [1]
Trend cycle (time in minutes) 0-65535 yes yes yes yes

Other Attributes
Field Description Field In CARE Off-line On-line Imported?
Range Database Editing? Editing?
Technical address of point 5 digits yes no no yes (for
(controller, board, point) nonexistent
only)
current point value yes no no yes
date of last modification yes no no yes
point subtype 0 to 255 yes no no yes (for
nonexistent
only)
indicates manual mode (1) 0 or 1 yes no XBS yes
indicates if point in alarm (1) 0 or 1 yes no no yes
indicates if trend is enabled (1) 0 or 1 yes no XI581/XI582 yes
indicates if point should be refreshed 0 or 1 yes no XBS no
(1) (trending)

EN2Z-0937GE51 R0518 1478


CARE APPENDIX C: POINT ATTRIBUTES TABLES

Digital Input Point Type


Datapoint Editor Attributes
Field Description Field In CARE Off-line On-line Imported?
Range Database Editing? Editing?
User Address 18 yes yes no no (create)
alphanumeri
c characters
Technical Address of point 6 digits yes yes, with no yes (for
(controller, board, point) Technical nonexistent only)
Address
dialog box
Descriptor (index into table of point 0 to 64 yes yes XBS yes
descriptors)
Operator Access Level 1 to 4 yes yes no yes
Write Protect Priority 0 to 3 (1- yes no XBS yes
255)
Alarm Text (index into table of alarm 0 to 128 yes yes XBS yes
text strings)
Engineering Unit (index into table of 0 to 20 yes yes no yes
digital engineering units)
Alarm Delay (time in seconds) 0 to 65535 yes yes XBS yes
Service Interval (for runtime hours) 0 to 65535 yes yes XBS yes
Point Subtype 0 to 255 yes no no yes (for
nonexistent only)
Suppress Alarm (indicates alarm 0 or 1 yes yes XBS yes
disabled [1])
Alarm Type (indicates critical [1] or 0 or 1 yes yes XBS yes
non-critical)
Runtime Enabled (indicates if 0 or 1 yes yes XBS yes
runtime is enabled [1])
Active State of point (0 or 1) 0 or 1 yes yes no yes
Alarm Status (enable alarm 0 or 1 yes no XBS yes
checking upon change of point
value)
Hide Point (indicates, if point is 0 or 1 yes yes yes yes
visible=no [0] or hidden=yes [1]

Other Attributes
Field Description Field In CARE Off-line On-line Imported?
Range Database Editing? Editing?
number of technical addresses 0 to 255 yes no no yes
(future)
manual point value 0 to 255 yes (initial no XBS yes
value)
current point value 0 to 255 yes no no yes
highest value for n-state point 0 to 255 yes no no yes
runtime in minutes(accumulated) yes no XBS yes
last modification date yes no no yes
counter of runtime between service yes no XBS yes
intervals (mins)
cycle count to active state yes no no yes
indicates manual mode (1) 0 or 1 yes no XBS yes
indicates if point is in alarm (1) 0 or 1 yes no no yes
indicates if trend is enabled (1) 0 or 1 yes no XI581/XI582 yes
indicates if point should be refreshed 0 or 1 yes no XBS no
(1) (trending)
No Response (indicates, if 0 or 1 no no no no
communication between controller
and DIO module is interrupted, yes
[1], no [0])
DIO Remote (indicates, if point is in 0 or 1 no no no no
manual override by a DIO module,
yes [1], no [0])

1479 EN2Z-0937GE51 R0518


APPENDIX C: POINT ATTRIBUTES TABLES CARE

Digital Output Point Type


Datapoint Editor Attributes
Field Description Field In CARE Off-line On-line Imported?
Range Database Editing? Editing?
User Address 18 yes yes no no
alphanumer
ic
characters
Technical Address of point 6 digits yes yes, with no yes (for
(controller, board, point) Technical nonexistent
Address only)
dialog box
Descriptor (index into table of point 0 to 64 yes yes XBS yes
descriptors)
Operator Access Level 1 to 4 yes yes no yes
Write Protect Priority 0 to 3 (1- yes no XBS yes
255)
Engineering Unit (index into table of 0 to 235 yes yes no yes
digital engineering units)
Service Interval for runtime hours 0 to 65535 yes yes XBS yes
Point Subtype 0 to 255 yes no no yes (for
nonexistent
only)
Suppress Alarm (indicates alarm 0 or 1 yes yes XBS yes
disabled [1])
Alarm Type (indicates critical [1] or 0 or 1 yes yes XBS yes
non-critical [0])
Runtime Enabled (indicates if 0 or 1 yes yes XBS yes
runtime is enabled [1])
Active State 0 or 1 yes yes no yes
Hide Point (indicates, if point is 0 or 1 yes yes yes yes
visible=no [0] or hidden=yes [1]

Other Attributes
Field Description Field In CARE Off-line On-line Imported?
Range Database Editing? Editing?
number of tech addr (future) 0 to 255 yes no no yes
manual point value yes (initial no XBS yes
value)
current point value yes no no yes
highest value for n-state pt 0 to 255 yes no no yes
runtime in minutes yes no XBS yes
date of last modification yes no no yes
counter of runtime between service yes no XBS yes
intervals (mins)
cycle count to active state yes no no yes
indicates manual mode (1) 0 or 1 yes no XBS yes
indicates if trend is enabled (1) 0 or 1 yes no XI581/XI582 yes
switching down has an OFF phase (0) 0 or 1 yes no no yes
indicates if point should be refreshed 0 or 1 yes no no no
(1)
delay time for OFF phase (secs) 0 to 255 yes yes XBS yes
delay time switching up (secs) 0 to 255 yes no no yes
delay time switching down (secs) 0 to 255 yes no no yes
No Response (indicates, if 0 or 1 no no no no
communication between controller and
DIO module is interrupted, yes [1], no
[0])
DIO Remote (indicates, if point is in 0 or 1 no no no no
manual override by a DIO module, yes
[1], no [0])

EN2Z-0937GE51 R0518 1480


CARE APPENDIX C: POINT ATTRIBUTES TABLES

Pseudo Digital Point Type


Datapoint Editor Attributes
Field Description Field In CARE Off-line On-line Imported?
Range Database Editing? Editing?
User Address 18 yes yes no no (create)
alphanumeri
c characters
Descriptor (index into table of point 0 to 64 yes yes XBS yes
descriptors)
Operator Access Level 1 to 4 yes yes no yes
Write Protect Priority 0 to 3 (1- yes no XBS yes
255)
Initial value (manual point value) 0 to 255 yes (initial yes XBS yes
value)
Engineering Unit (index into table of 0 to 20 yes yes no yes
digital engineering units)
Alarm Text (index into table of alarm 0 to 128 yes yes XBS yes
text strings)
Service Interval for runtime hours 0 to 65535 yes yes XBS yes
Suppress Alarm (indicates alarm 0 or 1 yes yes XBS yes
disabled [1])
Alarm Type (indicates critical [1]or 0 or 1 yes yes XBS yes
non-critical)
Runtime Enabled (indicates if 0 or 1 yes yes XBS yes
runtime is enabled [1])
Active State of point (0 or 1) 0 or 1 yes yes no yes
Alarm Status (enable alarm 0 or 1 yes no XBS yes
checking upon change of point
value)
Hide Point (indicates, if point is 0 or 1 yes yes yes yes
visible=no [0] or hidden=yes [1]

Other Attributes
Field Description Field In CARE Off-line On-line Imported?
Range Database Editing? Editing?
technical address yes no no yes (for
nonexistent
only)
current point value 0 to 255 yes no no yes
highest value for n-state point 0 to 255 yes no no yes
runtime in minutes yes no XBS yes
last modification date yes no no yes
counter of runtime between service yes no XBS yes
intervals (mins)
cycle count to active state yes no no yes
point subtype 0 to 255 yes no no yes (for
nonexistent
only)
indicates manual mode (1) 0 or 1 yes no XBS yes
indicates if point is in alarm (1) 0 or 1 yes no no yes
indicates if trend is enabled (1) 0 or 1 yes no XI581/XI582 yes
indicates if point should be 0 or 1 yes no XBS no
refreshed (1) (trending)

1481 EN2Z-0937GE51 R0518


APPENDIX C: POINT ATTRIBUTES TABLES CARE

Totalizer Point Type


Datapoint Editor Attributes
Field Description Field In CARE Off-line On-line Imported?
Range Database Editing? Editing?
User Address 18 yes yes no no (create)
alphanumer
ic
characters
Technical Address of point 6 digits yes yes, with no yes (for
(controller, board, point) Technical nonexistent
Address only)
dialog box
Descriptor (index into table of point 0 to 64 yes yes XBS yes
descriptors)
Operator Access Level 1 to 4 yes yes no yes
Write Protect Priority 0 to 3 (1- yes no XBS yes
255)
Engineering Unit (index into table of 0 to 20 yes yes no yes
analog engineering units)
Interval Limit to report a message yes yes no yes
Scaling Factor for number of pulses yes yes XBS yes
Totalizer type 0 to 255 yes no no yes (for
nonexistent
only)
Suppress Alarm (indicates alarm 0 or 1 yes yes XBS yes
disabled [1])
Alarm Type (indicates critical [1] or 0 or 1 yes yes XBS yes
non-critical)
Hide Point (indicates, if point is 0 or 1 yes yes yes yes
visible=no [0] or hidden=yes [1]

Other Attributes
Field Description Field In CARE Off-line On-line Imported?
Range Database Editing? Editing?
number of technical addresses 0 to 255 yes no no yes
manual point value yes (initial no XBS yes
value)
current point value yes no no yes
last value of HW counter 0 to 255 yes no no yes
last value of slow HW counter 0 to 255 yes no no yes
last reported refresh value 0 to 255 yes no no yes
interval counter for pulses specified yes no no yes
in attrib "interval"
indicates manual mode (1) 0 or 1 yes no XBS yes
indicates if trend is enabled (1) 0 or 1 yes no XI581/XI582 yes
indicates if point should be refreshed 0 or 1 yes no no no
(1)
No Response (indicates, if 0 or 1 no no no no
communication between controller
and DIO module is interrupted, yes
[1], no [0])
DIO Remote (indicates, if point is in 0 or 1 no no no no
manual override by a DIO module,
yes [1], no [0])

EN2Z-0937GE51 R0518 1482


CARE APPENDIX C: POINT ATTRIBUTES TABLES

Pseudo Totalizer Point Type


Datapoint Editor Attributes
Field Description Field In CARE Off-line On-line Imported?
Range Database Editing? Editing?
User Address 18 yes yes no no (create)
alphanumeri
c characters
Descriptor (index into table of point 0 to 64 yes yes XBS yes
descriptors)
Operator Access Level 1 to 4 yes yes no yes
Write Protect Priority 0 to 3 (1- yes no no yes
255)
Engineering Unit (index into table of 0 to 20 yes yes no yes
analog engineering units)
Interval Limit to report a message yes yes no yes
Scaling Factor for number of pulses yes yes XBS yes
Suppress Alarm (indicates alarm 0 or 1 yes yes XBS yes
disabled [1])
Alarm Type (indicates critical [1] or 0 or 1 yes yes XBS yes
non-critical)
Hide Point (indicates, if point is 0 or 1 yes yes yes yes
visible=no [0] or hidden=yes [1]

Other Attributes
Field Description Field In CARE Off-line On-line Imported?
Range Database Editing? Editing?
technical address of point 6 digits yes no no yes (for
(controller, board, point) nonexistent
only)
manual point value yes (initial no XBS yes
value)
current point value yes no no yes
last reported refresh value 0 to 255 yes no no yes
interval counter for pulses specified yes no XBS yes
in attrib "interval"
indicates manual mode (1) 0 or 1 yes no XBS yes
indicates if trend is enabled (1) 0 or 1 yes no XI581/XI582 yes
indicates if point should be 0 or 1 yes no XBS no
refreshed (1) (trending)

1483 EN2Z-0937GE51 R0518


APPENDIX C: POINT ATTRIBUTES TABLES CARE

Global Analog and Digital Point Types


Datapoint Editor Attributes
Field Description Field In CARE Off-line On-line Imported?
Range Database Editing? Editing?
Point Subtype (input or output) yes yes no yes (for
nonexistent
only)
User Address 18 yes yes no no (create)
alphanumeri
c characters
Technical Address 6 digits yes yes no yes (for
nonexistent
only)
Descriptor (index into table of point 0 to 64 yes yes XBS yes
descriptors)
Operator Access Level 1 to 4 yes yes no yes
Write Protect Priority 0 to 3 (1- yes no XBS yes
255)
Engineering Unit (index into table of 0 to 20 yes yes no yes
engineering units) (digital) 0 to
235 (analog)
Hide Point (indicates, if point is 0 or 1 yes yes yes yes
visible=no [0] or hidden=yes [1]
Trend cycle (time in minutes) 0-65535 yes yes yes yes

Other Attributes
Field Description Field In CARE Off-line On-line Imported?
Range Database Editing? Editing?
manual value yes (initial no XBS yes
value)
current point value yes no no yes
1 if controller is down 0 or 1 yes no no no
indicates manual mode (1) 0 or 1 yes no XBS yes
1 if controller is slave 0 or 1 yes no no yes
active state (for digital points only) 0 or 1 yes yes no yes
indicates if point should be refreshed 0 or 1 yes no XBS no
(1) (for analog pts only) (trending)

EN2Z-0937GE51 R0518 1484


CARE APPENDIX C: POINT ATTRIBUTES TABLES

DO Feedback DI Point Type


Datapoint Editor Attributes
Field Description Field Range In CARE Off-line On-line Imported?
Databas Editing? Editing
e ?
User Address 18 yes yes no no
alphanumeric
characters
Descriptor (index into table of point 0 to 64 yes yes XBS yes
descriptors)
Alarm Text (index into table of alarm text 0 to 128 yes yes XBS yes
strings)
Engineering Unit (index into table of digital 0 to 20 yes yes no yes
engineering units)
Operator Access Level 1 to 4 yes yes no yes
Write Protect Priority 0 to 3 (1-255) yes yes XBS yes
Cycle Count to active state yes no no yes
Duration Off phase (secs) 0 to 255 yes yes no yes
Delay Switch Up (secs) 0 to 255 yes yes no yes
Delay Switch Down 0 to 255 yes yes no yes
Feedback Delay (time) for signal 0 to 255 yes yes no yes
Service Interval (user specified 0 to 65535 yes yes XBS yes
maintenance interval in hours)
Suppress Alarm (indicates alarm disabled 0 or 1 yes yes XBS yes
[1])
Alarm Type (indicates critical [1] or non- 0 or 1 yes yes XBS yes
critical)
Runtime Enabled 0 or 1 yes yes XBS yes
Switching Down (OFF phase when value is 0 or 1 yes yes no yes
1)
Hide Point (indicates, if point is visible=no 0 or 1 yes yes yes yes
[0] or hidden=yes [1]

Other Attributes
Field Description Field In CARE Off-line On-line Imported?
Range Database Editing? Editing?
subtype of assigned points (DO) 0 to 255 yes no no yes ( for
nonexistent
only)
subtype of feedback points (DI) 0 to 255 yes no no yes (for
nonexistent
only)
manual point value 0 to 255 yes no XBS yes
current point value 0 to 255 yes no no yes
max for manual/current point values 0 to 255 yes no no yes
accumulated runtime (mins) yes no XBS yes
time within a maintenance interval yes no XBS yes
(time since last service)
last modification date yes no no yes
indicates manual mode (1) 0 or 1 yes no XBS yes
indicates if point is in alarm (1) 0 or 1 yes no no yes
indicates if trend is enabled (1) 0 or 1 yes no XI581/XI582 yes
enable runtime accumulation 0 or 1 yes yes XBS yes
indicates if point should be 0 or 1 yes no no no
refreshed (1)
technical address of DO point 6 digits yes no no yes
technical address of DI point 6 digits yes no no yes
No Response (indicates, if 0 or 1 no no no no
communication between controller
and DIO module is interrupted, yes
[1], no [0])

1485 EN2Z-0937GE51 R0518


APPENDIX C: POINT ATTRIBUTES TABLES CARE

DIO Remote (indicates, if point is in 0 or 1 no no no no


manual override by a DIO module,
yes [1], no [0])

Pulse 2 Point Type


Datapoint Editor Attributes
Field Description Field In CARE Off-line On-line Imported?
Range Database Editing? Editing?
User Address 18 yes yes no no (create)
alphanumeri
c characters
Descriptor (index into table of point 0 to 64 yes yes XBS yes
descriptors)
Engineering unit (index into table of 0 to 20 yes yes no yes
digital engineering units)
Operator Access Level 1 to 4 yes yes no yes
Write Protect Priority 0 to 3 (1- yes yes XBS yes
255)
Cycle Count to active state yes yes no yes
Pulse Duration (secs) 0 to 255 yes yes XBS yes
Service Interval (user-specified 0 to 65535 yes yes XBS yes
maintenance interval in hours)
Suppress Alarm (indicates alarm 0 or 1 yes yes XBS yes
disabled [1])
Alarm Type (indicates critical [1] or 0 or 1 yes yes XBS yes
non-critical)
Runtime Enabled 0 or 1 yes yes XBS yes
Hide Point (indicates, if point is 0 or 1 yes yes yes yes
visible=no [0] or hidden=yes [1]

Other Attributes
Field Description Field In CARE Off-line On-line Imported?
Range Database Editing? Editing?
point subtype 0 to 255 yes no no yes (for
nonexistent
only)
technical address of first point yes no no yes
manual point value 0 to 255 yes no XBS yes
current point value 0 to 255 yes no no yes
accumulated runtime (mins) yes no XBS yes
time within a maintenance interval yes no XBS yes
(time since last service)
last modification date yes no no yes
indicates manual mode (1) 0 or 1 yes no XBS yes
indicates if trend is enabled (1) 0 or 1 yes no XI581/XI582 yes
indicates if point should be refreshed 0 or 1 yes no no no
(1)
No Response (indicates, if 0 or 1 no no no no
communication between controller
and DIO module is interrupted, yes
[1], no [0]), for OS 2.0 only
DIO Remote (indicates, if point is in 0 or 1 no no no no
manual override by a DIO module,
yes [1], no [0])

EN2Z-0937GE51 R0518 1486


CARE APPENDIX C: POINT ATTRIBUTES TABLES

Multistage Point Type


Datapoint Editor Attributes
Field Description Field In CARE Off-line On-line Imported?
Range Database Editing? Editing?
User Address 18 yes yes no no
alphanumeri
c characters
Descriptor (index into table of point 0 to 64 yes yes XBS yes
descriptors)
Engineering Unit (index into table of 0 to 20 yes yes no yes
digital engineering units)
Technical address of first point 6 digits yes no no yes
Operator Access Level 1 to 4 yes yes no yes
Write Protect Priority 0 to 3 (1- yes yes XBS yes
255)
Cycle Count to active state yes no no yes
Service Interval (user-specified 0 to 65535 yes yes XBS yes
maintenance interval in hours)
Suppress Alarm (indicates alarm 0 or 1 yes yes XBS yes
disabled [1])
Alarm Type (indicates critical [1] or 0 or 1 yes yes XBS yes
non-critical)
Runtime Enabled 0 or 1 yes yes XBS yes
Active State (1) 0 or 1 yes yes no yes
Hide Point (indicates, if point is 0 or 1 yes yes yes yes
visible=no [0] or hidden=yes [1]

Other Attributes
Field Description Field In CARE Off-line On-line Imported?
Range Database Editing? Editing?
point subtype 0 to 255 yes no no yes (for
nonexistent
only)
manual point value 0 to 255 yes no XBS yes
current point value 0 to 255 yes no no yes
max value of point 0 to 255 yes no no yes
accumulated runtime (mins) yes no XBS yes
time within a maintenance interval yes no XBS yes
(time since last service)
last modification date yes no no yes
indicates manual mode (1) 0 or 1 yes no XBS yes
indicates if trend is enabled (1) 0 or 1 yes no XI581/XI582 yes
indicates if point should be 0 or 1 yes no no no
refreshed (1)
No Response (indicates, if 0 or 1 no no no no
communication between controller
and DIO module is interrupted, yes
[1], no [0])
DIO Remote (indicates, if point is in 0 or 1 no no no no
manual override by a DIO module,
yes [1], no [0])

1487 EN2Z-0937GE51 R0518


APPENDIX D: PLANT AND CONTROLLER UPGRADES AND DOWNGRADES CARE

APPENDIX D: PLANT AND CONTROLLER UPGRADES AND DOWNGRADES


NOTE: This section applies to CARE XL-5000 only.

Multiple Operating System Handling


Purpose Multiple Operating System Handling is a feature of CARE allowing to
upgrade/downgrade operating system versions for Excel 5000 controllers.
CARE supports the operating system versions:

• OS 1.1(Europe and Latin America only)


• OS 1.2
• OS 1.3/1.4
• OS XLIRC (Europe and Latin America only)
• OS 1.5
• OS 2.0
• OS 2.03
• OS 2.04
• OS 2.06
• OS 3.00

CARE capabilities vary for each version as shown in the following table.

Feature Ver. Ver. Ver 1.5 Ver Ver 3.00


1.1/1.2 1.3/1.4/XLIRC 2.0/2.03/2.04/2.06
Point descriptors 64 255 255 255 255
Alarm messages 128 255 255 255 255
Analog engineering units 234 234 254 254 254
Digital engineering units 20 127* 127* 127 127
Global digital points 2-state 2-state and multi- 2-state and 2-state and multi- 2-state and
state multi-state state multi-state
Global analog update fixed** fixed** programmable programmable Programm-
able
Trend hysteresis fixed** fixed** programmable programmable Programm-
able
Alarm hysteresis fixed fixed programmable programmable Programm-
able
LON points via point mapping via point
to NVs mapping to
NVs
NVs Excel 50: Excel 50:
max. 46 max. 46
Excel 500: Excel 500:
max. 512 max. 512
Hardware points 128 384
Software points of one 128 (253 + 3 internal if OS > 2.03) 384 –
type 3 internal
Software points of all 256 384
types
Global points 128 384
Maximum number of 384 384
points:
(Hardware-, software,
internal- and global
points)

EN2Z-0937GE51 R0518 1488


CARE APPENDIX D: PLANT AND CONTROLLER UPGRADES AND DOWNGRADES

NOTE: *There is a limit of 255 states, therefore, 127 implies that each point has
two states (pairs). If a point has more than two states, the total number is
reduced.
**If global value is greater than 20, the change must be at least 1 percent.
If the value is less than 20, the change must be at least .2 units.

Upgrading is possible from a current version to any higher version without


intermediate steps, for example you can upgrade from OS Version 1.3/1.4 to OS-
Version 2.06 without upgrading to OS-Version 1.5 as intermediate step. Analogously
the same is valid for downgrading, except Excel 800 OS 3.00. This controller cannot
be downgraded. For details on upgrading an Excel 500 controller to an Excel 800
controller, please refer to the Upgrade Excel 500 Controller to Excel 800 Controller
section.

Restrictions Upgrading from older OS versions uses all restrictions required for the older
OS version. Downgrading to an older OS version will be allowed as long as
the application remains within the restrictions of the target OS. If
downgrading of a controller is not possible because of controller or plant
restrictions, CARE displays the appropriate error message and does not
change the OS version.

Procedures Upgrading or downgrading a controller applies to the controller and its


attached plants only. When replacing its OS all attached plants are
upgraded/downgraded automatically.

NOTE: The OS number of one single attached plant cannot be changed. The OS
number of an unattached plant can be changed. When attaching a plant
with a different OS version number as the controller, the OS version
number of the plant gets the OS version number of the controller.

Change Controller OS Version 1. In the logical plant tree, click on the controller.

2. On the right pane, click on the Properties tab.

1489 EN2Z-0937GE51 R0518


APPENDIX D: PLANT AND CONTROLLER UPGRADES AND DOWNGRADES CARE

NOTES: All plants attached to the controller will be upgraded/downgraded by


upgrading/downgrading the controller.

If downgrading of a controller is not possible because of controller or


plant restrictions, CARE displays the appropriate error message and
does not change the OS version.

3. Click the down arrow next to Controller OS Version list box and select desired
version.

4. If messages occur, follow the instructions and correct the conditions displayed.

Change Plant OS Version 1. In the logical plant tree, click on the unattached plant.

NOTE: Attached plants cannot be upgraded/downgraded.

2. On the right pane, click on the Properties tab.

EN2Z-0937GE51 R0518 1490


CARE APPENDIX D: PLANT AND CONTROLLER UPGRADES AND DOWNGRADES

3. Click the down arrow next to Plant OS Version list box and select desired
version.

The Preserve Technical Address checkbox refers to modification of the target


hardware, if point changes in the TAF have already been made before.

Enabling this checkbox results in the following:

Points that are already assigned to that target hardware type, which will be
changed to, preserve their technical address on the corresponding module.

Disabling this checkbox results in the following:

Points that are already assigned to that target hardware type, which will be
changed to, may not necessarily preserve their technical address on the
corresponding module.

4. If messages occur, follow the instructions and correct the conditions displayed.

Disposition of Templates If you enter search templates for a Ver. 1.3 or 1.5 controller and then
downgrade the controller to Ver.1.2, there is no warning message during
the downgrade pertaining to the templates. The templates remain in the
database in case the controller is upgraded to Ver. 1.3. or 1.5. When the
database is translated to the Ver. 1.2 controller with the “hidden” templates,
the templates are not translated into the controller files.

Upgrade Excel 500 Controller to Excel 800 Controller


The following steps show the upgrade strategy of Excel 500 to Excel 800
applications:

Procedure 1. Detach the plant from the Excel 500 controller.

2. Change the plant version to OS 3.0.

RESULT: The time program will be lost.

3. Create an Excel 800 controller.

1491 EN2Z-0937GE51 R0518


APPENDIX D: PLANT AND CONTROLLER UPGRADES AND DOWNGRADES CARE

4. Re-attach the plant to the 800 controller.

RESULT: The datapoints will be automatically assigned to panel I/O


modules. Open Lon points will be not assigned.

Upgrade Controller to OS 2.04 and higher

NO/NC Processing
For OS 2.04 and higher the NO/NC* handling is completely reworked. When using
previous projects CARE performs an automatic upgrade for datapoints regarding the
NO/NC behavior. The upgrade result may show points which have to be reworked
either in the control strategy or to be defined as status or alarm point. To understand
what to do in the upgrade dialog, the old NO/NC handling (OS version lower than
2.04) and the new NO/NC handling for OS 2.04 and higher will be compared for
digital points in the following sections.

*NO/NC means Normally Open/Normally close.

Old NO/NC Mechanism

For OS lower than 2.04 the NO/NC mechanism is as follows:

Global Data
Transfer

NO / NC Handling in Alarm Point*


DI RACL Logical State 0

0
&
0
Point Alarm
0
=1 in RACL 0
NC 0

as Care 0

Attribute
IBIT/NBIT in
RACL

0
=1
0 0
Active State* & Runtime Counter
0 0 0
Runtime Enable* & Runtime Alarm
0 0

Passive Text 0

0 MUX Display Supress Alarm*


Active Text
1

* Point Attributes

Have decisive influence on results of logical processing

The logical behavior provides several interactive spots. The following table shows
the dependence.

EN2Z-0937GE51 R0518 1492


CARE APPENDIX D: PLANT AND CONTROLLER UPGRADES AND DOWNGRADES

DI Voltage NO/NC as Logical State Logical state for Active Text Alarm Runtime Hours run
CARE in Control Global Transfer State Displayed Enable accumulation
attribute Strategy
in (RACL)
schematic
<2,5V NC 1 0 0 Active RTN
>5V NC 0 1 0 Passive ALM
<2.5V NC 1 0 1 Passive ALM
>5V NC 0 1 1 Active RTN
<2.5V NO 0 0 0 Active RTN
>5V NO 1 1 0 Passive ALM
<2.5V NO 0 0 1 Passive ALM
>5V NO 1 1 1 Active RTN
Alarm direction: ALM = Alarm, RTN = Alarm Return to Normal

DI Voltage: Terminal logic state (open < 2.5 V = 0, closed > 5 V = 1)


NO/NC as CARE attribute: NO = 0, NC = 1
Active State: DI is active at 0 or 1

The results are the following:

• Via Active State attribute it is possible to invert the alarm direction, the
corresponding active/passive text pair, and the runtime counter.

• The logical state of global points provided for global data transfer can be
different to the logical state in the control strategy (RACL) if NO was
chosen for the point. In addition when NC and Active State = 0 or NO
and Active State = 1 was chosen, the active-passive text pairs were
inverted.

• In general negative logic could lead to problems.

New NO/NC Mechanism

For OS 2.04 and higher the NO/NC mechanism is as follows:

1493 EN2Z-0937GE51 R0518


APPENDIX D: PLANT AND CONTROLLER UPGRADES AND DOWNGRADES CARE

Global Data
Transfer

DI
0
=1 RACL
0
NC*
0 Alarm Point*

0
& Point Alarm
Logical State = 0 0

Alarm State 0

0
Runntime
&
Counter
0 0
Runtime Enable* & Runtime Alarm
0 0

Pasive Text 0

0 MUX Display Supress Alarm*


Active Text
1

* Point Attributes
Have decisive influence on results of logical processing

DI Voltage: Terminal logic state (open < 2.5 V = 0, closed > 5 V = 1)


NO/NC as CARE attribute: NO = 0, NC = 1

Assumption: positive logic and relay contact model

Digital Input NO Digital Input NC


Contact Voltage at Input Logical Status Contact Voltage at Input Logical Status
position position
Open <2.5V 0 Open <2.5V 1
Closed >5V 1 Closed >5V 0

The new NO/NC handling for OS 2.04 or higher provides the following:

The NO/NC attribute will firstly be set in the schematic as before, but can be
changed in the Datapoint Editor offline as well as online via XI 581AH/582AH. The
Active State attribute is no longer available. There will be no possibility to invert this
logic. Results are shown in the following tables:

Logical state in Unit Text Text Display Value Generated alarm


control strategy displayed change
0 passive OFF 0->1 Return to normal (RTN)
1 active ON 1->0 Alarm coming (ALM)

The logical state of a DI point (0 or 1 in control strategy) depends only on the setting
of the normally open/normally closed attribute set in the Datapoint Editor. The alarm
state, the state for the runtime counter and for the global point transfer follows the
logical state in the control strategy.

The hours run are always counted when the control strategy logical state is 1. As
outlined above, this depends only on the setting on the NO/NC attribute. Hours run
in general are only counted if the Runtime Enabled attribute is set to yes.

EN2Z-0937GE51 R0518 1494


CARE APPENDIX D: PLANT AND CONTROLLER UPGRADES AND DOWNGRADES

DI NO/NC as Logical Logical state Text Alarm Runtime Hours run


VOLTAGE CARE state in for Global Displaye Enable accumulation
attribute in control Transfer d
schematic strategy
<2.5V NO 0 0 Passive RTN Yes No
>5V NO 1 1 Active ALM Yes Yes
<2.5V NC 1 1 Active ALM Yes Yes
>5V NC 0 0 Passive RTN Yes No
<2.5V NO 0 0 Passive RTN No No
>5V NO 1 1 Active ALM No No
<2.5V NC 1 1 Active ALM No No
>5V NC 0 0 Passive RTN No No
Alarm direction: ALM = Alarm, RTN = Alarm Return to Normal

Upgrading to OS 2.04 and higher / Status point or Alarm point

When upgrading from a previous OS to OS 2.04 or higher CARE is checking each


digital, pseudo digital, and global digital point, whether it can be upgraded without
loosing the correct logical behavior. To keep the logical behavior means that both
the logical value for Data processing and the logical value for Alarming will be the
same as before. If this is the case the point will be automatically upgraded.

For some reasons certain points cannot be upgraded automatically. If e.g. the Active
State attribute was inverted in the application to be upgraded, points cannot keep
both the correct Data processing value and the correct Alarming value. In this case
the user has to decide whether the point should be a Status point for which the data
processing value of the control strategy will be considered and the alarming will be
wrong, or if the point should be an Alarm Point for which the Alarming value will be
considered and the data processing will be wrong. This can be done in the NO/NC
Upgrade dialog box.

In general status points are set to NO, alarm points are set to NC.
Global points have to be reworked completely in the control strategy and/or
switching logic and certain pseudopoints need to be corrected regarding the
alarming direction in any case.

For each point to be upgraded manually, a description is displayed in the NO/NC


Upgrade dialog box, which indicates what to do.

IMPORTANT
The Upgrade to OS 2.04 and higher cannot be done without loosing
compatibility in some cases

Upgrading is done by the rules listed in the following table:

1495 EN2Z-0937GE51 R0518


APPENDIX D: PLANT AND CONTROLLER UPGRADES AND DOWNGRADES CARE

Attributes OS < 2.04 OS 2.04


Point NO / NC Contact Relay Active Logical Alarm Unit text Logical Alarm Unit text
Types: Attributes: position: On/Off: State status*3 displayed: status:*1*3 displayed:
DI NO Open (<2.5V) 0 0 RTN Active 0 RTN Passive
DI NO Closed (>5V) 0 1 ALM Passive 1 ALM Active
DI NO Open (<2.5V) 1 0 ALM Passive 0 RTN Passive
DI NO Closed (>5V) 1 1 RTN Active 1 ALM Active
DI NC Open (<2.5V) 0 1 RTN Active 1 ALM Active
DI NC Closed (>5V) 0 0 ALM Passive 0 RTN Passive
DI NC Open (<2.5V) 1 1 ALM Passive 1 ALM Active
DI NC Closed (>5V) 1 0 RTN Active 0 RTN Passive
AI>DI*2 NO Open (<2.5V) 0 0 RTN Active 0 RTN Passive
AI>DI*2 NO Closed (>5V) 0 1 ALM Passive 1 ALM Active
AI>DI*2 NO Open (<2.5V) 1 0 ALM Passive 0 RTN Passive
AI>DI*2 NO Closed (>5V) 1 1 RTN Active 1 ALM Active
AI>DI*2 NC Open (<2.5V) 0 1 RTN Active 1 ALM Active
AI>DI*2 NC Closed (>5V) 0 0 ALM Passive 0 RTN Passive
AI>DI*2 NC Open (<2.5V) 1 1 ALM Passive 1 ALM Active
AI>DI*2 NC Closed (>5V) 1 0 RTN Active 0 RTN Passive
DO NO On 1 1 Active 1 Active
DO NO Off 1 0 Passive 0 Passive
DO NC On 0 0 Active 0 Passive
DO NC Off 0 1 Passive 1 Active
PD_2 n/a 0 0 RTN Active 0 RTN Passive
PD_2 n/a 0 1 ALM Passive 1 ALM Active
PD_2 n/a 1 0 ALM Passive 0 RTN Passive
PD_2 n/a 1 1 RTN Active 1 ALM Active
PD_n n/a X (0,1,2…) StateX
GD_2 n/a 0 RTN Passive
GD_2 n/a 1 ALM Active
GD_n n/a X (0,1,2…) StateX

*1
Runtime folllows the Logical status (Logical Status = 1 means runtime logging)
*2
At DI Subtype AI the pull up resistor will be switched off as default for new HW Points only for OS 2.04
*3
State in Control Strategy (RACL)

Procedure

IMPORTANT
Note, that the Upgrade cannot be performed explicitly. The upgrade will be done
automatically when upgrading a controller OS lower than 2.04 to 2.04.
Nevertheless after once the upgrade was performed the points that need to be
reworked/defined as status or alarm points can be edited in the NO/NC Upgrade
dialog box in as many sessions as you like.

1. Open Controller Information dialog box by clicking menu item


Controller, then submenu item Information.

2. From the controller OS Version drop-down listbox, select OS 2.04 or


higher.

3. Click OK.

RESULT: Observe the following message and click OK if you really


want to upgrade to OS 2.04 or higher.

4. Confirm next message box.

EN2Z-0937GE51 R0518 1496


CARE APPENDIX D: PLANT AND CONTROLLER UPGRADES AND DOWNGRADES

5. Confirm next message box. It is recommended to print the problem


points
report.

RESULT: The NO/NC Upgrade dialog box is displayed.

On the left, all points, which were not automatically


upgraded are shown. When selecting a point, note the
point description on the right. Points, which can be
defined as status or alarm point, are displayed in black.
Global points and pseudopoints, which have wrong alarm
direction, will displayed green when selecting them.

6. Copy the points to the clipboard and paste them into a word processing
program. Print out the list. Do this every time before you close the dialog box to
keep the result of the points edited.

7. Select a point displayed in black and define if it should be a status point (NO) or
an alarm point (NC) by selecting respective radio button. Note the results in the
field under New on the right.

1497 EN2Z-0937GE51 R0518


APPENDIX D: PLANT AND CONTROLLER UPGRADES AND DOWNGRADES CARE

RESULT: The point gets green in the list.

8. Continue with next point(s).

9. Before closing the dialog box, copy the points to the clipboard and paste them
into a word processing program for printing your result.

10. Click Save button.

RESULT: All points defined as status or alarm point are now


upgraded. When opening the NO/NC Upgrade dialog box
next time, they will not be displayed anymore. Go for
reworking global points and pseudopoints.

Upgrade Controller to OS 2.06 when using Multistage or DO_Feedback_DI Points on DIO


IMPORTANT
When using Multistage DO or DO_Feedback_DI Points (Flex points) that
reside on distributed I/O modules, the points must be shifted to IP modules
before upgrading the controller to OS 2.06 in order to avoid damage of the
controlled equipment. As long as the controller OS is lower than 2.06, for
example 2.04, the application need not to be changed even if the controller
unit supports OS 2.06.

EN2Z-0937GE51 R0518 1498


CARE APPENDIX D: PLANT AND CONTROLLER UPGRADES AND DOWNGRADES

Controller OS 2.06 usage and functionality in CARE 4 and


CARE- XL500 10.08.01
The behavior of the controller OS 2.06 in CARE 4 and CARE-XL500 10.08.01 differ
strongly regarding the following functions:

• Sensor Offset
• NO/NC
• Characteristics
• Actuator runtime

The following table shows the relationship between controller hardware OS,
controller OS in CARE, and the CARE version.

Controller OS Version Controller OS Version CARE Version


(Hardware) (CARE)
2.06.00 – 2.06.04 2.06. Version 4
2.06.00 – 2.06.04 2.06 Version XL500 10.08.01
2.06.05

For the usage of open LON I/O modules (Smart I/O modules and Distributed I/O
modules), the hardware controller OS 2.6.05 includes the following enhancements:

• Sensor offset applicable for all characteristic types


• Normally open / Normally Closed attribute active in controller
• Default characteristics enabled and calculated by the controller
• Actuator run time handling optimized for open LON I/O modules

When upgrading a CARE 4 project to a CARE-XL500 10.08.01 project using


controller OS 2.06, the CARE version dependent behavior of each of these functions
have to be clearly understood as described in the following.

Sensor Offset Handling


The sensor offset compensates value deviations caused, for example, by voltage
drop on the cable. The following example shows how the sensor offset is calculated:

Example:

Displayed Original Value 20 K


Entered Sensor Offset -2K
Value
Displayed New Value 18 K

CARE 4 and OS 2.06.00 – 2.06.04

• Sensor offset handling is done in the open LON I/O module.


• Sensor offset value entered in the datapoint (Datapoint Editor) is ignored
and has to be set via UCPT in the LON-Works part of the network tree,
or the module has to be configured via plug-in.
• Sensor offset is supported for PT1000 only.
• Sensor offset is handled differently for Distributed I/O modules and
Smart I/O modules:
For Distributed I/O modules, sensor offset is entered as value in Ohm to
be calculated according to the characteristic of the sensor
For Smart I/O modules, sensor offset is entered as direct value without
the need of referring to the characteristic
• Online Sensor offset changes via MMI or Excel Online are ignored

1499 EN2Z-0937GE51 R0518


APPENDIX D: PLANT AND CONTROLLER UPGRADES AND DOWNGRADES CARE

CARE-XL500 7.01.02 and OS 2.06.05 and higher

• Sensor offset handling is done in the controller:


• Sensor offset value entered in the datapoint (Datapoint Editor) will be
valid and executed
• Sensor offset is entered as a real value (+ or -) for both module types
and other relevant Honeywell devices such as Excel 10
• Sensor offset is applicable to all characteristics (NTC, PT1000, PT100,
0-10 V input) in combination with open LON devices.
• Sensor offset input can still be done as in CARE 4.
• The sensor offset should be done only in one place, either in the
datapoint of the controller (Datapoint Editor) or in the UCPT of the open
LON module (LON-Works part of the network tree)
• Online sensor offset changes via MMI are ignored but via Excel Online
are executed
• Plug-in for configuration is no longer needed

CARE 4 / CARE-XL500 10.08.01 Upgrade and OS 2.06.05 and higher

When upgrading a CARE 4 project in CARE-XL500 10.08.01, sensor offset values


set in the open LON I/O module and in the controller will be added.

Example:

Real Value Sensor Offset 1 Sensor Offset 2 Value Display


(Sensor) (I/O Module) (Controller) (MMI)
22 K 2K 2K 26 K

Work around
Check the sensor offset value of the datapoint and set the value to 0.

CARE 4 / CARE-XL500 10.08.01 Upgrade and OS 2.06.00 - 06.04

When still using OS 2.06.00 - 2.06.04 in an upgraded project in CARE-XL500


10.08.01, the sensor offset handling is the same as in CARE 4.

NO/ NC Attribute Handling


CARE 4 and OS 2.06.00 – 2.06.04

• NO/NC handling is done in the open LON I/O modules


• NO/NC handling of digital Smart I/O and Distributed I/O modules are
different via plug-in access in CARE
• Changing NO/NC status in CARE requests new bindings
• Online changes of NO/NC status for digital Smart I/O and Distributed I/O
modules can be entered, but are ignored.
• Online changes of NO/NC status for internal digital I/O modules (XF-
modules) can be entered and are executed.

CARE-XL500 10.08.01 and OS 2.06.05

• NO/NC handling for digital Smart I/O and Distributed I/O modules is
shifted into the controller:
Contact state is converted inside the controller, not in the module

EN2Z-0937GE51 R0518 1500


CARE APPENDIX D: PLANT AND CONTROLLER UPGRADES AND DOWNGRADES

• NO/NC handling for digital Smart I/O and Distributed I/O modules is the
same.
• NO/NC status can be edited in the datapoint Attribute ´Point Subtype`
(Datapoint Editor)
• When changing NO/NC status, re-binding or module re-configuration is
no longer required in CARE
• Online changes of NO/NC status are blocked for digital Smart I/O and
Distributed I/O modules. MMI shows *******
• Online changes of NO/NC status for internal digital I/O modules can be
entered and are executed

CARE 4 / CARE-XL500 10.08.01 Upgrade and OS 2.06.05 and higher

When upgrading a CARE 4 project in CARE-XL500 10.08.01, take care of the


following:
Check if value conversation tables have been used for Distributed I/O modules.
If yes, remove any of them.

Check digital inputs which are configured as NC in the Smart I/O module (in CARE
4, digital inputs of a Smart I/O module are automatically set to NC if a datapoint of
subtype NC is bound to the Smart I/O terminal).
Reset all NC states of the Smart I/O module to NO states with the plug-in.

Characteristics Handling
CARE supports the following characteristic types:

Default Characteristics Default characteristics are delivered with CARE and they can be edited with
the Default Text Editor to meet local requirements. The following shows
examples:

Default Range of Open LON I/O Module


Characteristic
1 Pressure 0-3 ” 0 to 11.0 V
3 Pressure ±0.25 ” 0 to 11.0 V
4 Pressure 0-5 ” 0 to 11.0 V
9 Direct Out 0-100 % 0 to 11.0 V
1 Reverse Out 0-100 % 11.0 to 0 V
0

Note that the voltage ranges are wider than actual open LON I/O module input to
account for possible miscalibration of the module. Modules 1 through 4 and 9 range
from 2 to 10 V. Device 10 ranges from 10 to 2 V.

Fixed Characteristics Fixed characteristics are delivered with CARE, but cannot be edited in the
Miscellaneous Text Editor. They can only be selected and assigned to
points in the Datapoint Editor, and are available under the IDs 11 through
15 for slow subtype points, and under the IDs 11 through 29 for fast
subtype points.

CARE Subtype Index XL-Online Index Characteristic


Slow Fast Name Specification
15 23 253 NTC Type F -58.0 to 302.0 F
Negative temperature coefficient
degrees F
11 11 255 NTC -50.0 to 150.0 C
Negative temperature coefficient
degrees C

1501 EN2Z-0937GE51 R0518


APPENDIX D: PLANT AND CONTROLLER UPGRADES AND DOWNGRADES CARE

12 12 254 LINEAR_GRAPH 0 to 10 V
13 19 249 PT1000 Type F/I -58.0 to 302.0 F
14 20 250 PT1000 Type C/I -50.0 to 150.0 C
17 247 PT1000 Type F/II 32 to 752.0 F
18 248 PT1000 Type C/II 0.0 to 400.0 C
21 251 PT100 Type F -58.0 to 302.0 F
22 252 PT100 Type C -50.0 to 150.0 C
15 245 PT3000 Type F -58.0 to 302.0 F
16 246 PT3000 Type C -50.0 to 150.0 C
13 243 BALCO Type F -58.0 to 302.0 F
14 244 BALCO Type C -50.0 to 150.0 C
24 241 0-10 V 0-10 V
25 242 2-10V = 0-100 % 2-10V = 0-100 %
26 237 NI 1000 TK5000 F -22.0 to 266.0 F
Positive temperature coefficient
degrees F
27 238 NI 1000 TK5000 -30.0 to 130.0 C
Positive temperature coefficient
degrees C
28 239 NTC-10 F -22.0 to 212.0 F
Negative temperature coefficient
degrees F
29 240 NTC-10 -30.0 to 130.0 C
Negative temperature coefficient
degrees C

Characteristics can either be calculated in the open LON I/O module or in the
controller. Depending on the controller OS and the CARE version, the handling of
characteristics is as follows:

CARE 4 and OS 2.06.00 - 2.06.04

• Fixed characteristics such as PT1000 are calculated inside the open


LON I/O module.
• Default characteristics such as Pressure 0-3 ” cannot be calculated by
the open LON I/O module and are ignored by the controller too, although
they are selectable in CARE.
• In case a fixed characteristic has been selected, the input NV value
delivered by the open LON I/O module is properly displayed as datapoint
value.
• In case a default characteristic has been selected, the datapoint in most
cases shows a value in the range of 0 - 10 based on the default
characteristic input range of 0 - 10 V. To correct that wrong display and
assure right input NV-to-datapoint value conversion, a conversion table
has to be allocated to the controller.
• Default characteristics can be changed, deleted and newly created
("user-definable default characteristics").

CARE-XL500 10.08.01 and OS 2.06.05 and higher

• Fixed characteristics such as PT1000 are calculated inside the open


LON I/O module.
• Default characteristics such as Pressure 0-3 ” are enabled in CARE and
calculated by the controller.

EN2Z-0937GE51 R0518 1502


CARE APPENDIX D: PLANT AND CONTROLLER UPGRADES AND DOWNGRADES

• In case a fixed characteristic is selected, the NVi value delivered by the


open LON I/O module is properly displayed as datapoint value.
• In case a default characteristic is selected, the datapoint value is
displayed properly as datapoint value. No additional conversion table is
required.
• Default characteristics can be changed, deleted and newly created
("user-definable default characteristics").
Benefit and Limitation of "User-Definable Default Characteristics" in CARE 4
and XL500 10.08.01

Benefit
Allows the creation of non-linear characteristics by definition of up to four
reference points.

Limitation
Controller characteristic input allows max. input values of 0-11.

Work around
Add a value conversion table that fits the NV input value to the max.
input range of 0 - 11.

Example: Smart I/O module with 0 – 10 V humidity sensor


connected

Inputsignal NVO – Value Value Conversion Table Characteristic Value Display


(Sensor) (I/O Module) (Controller NV) (Datapoint) (Datapoint on MMI)
0 – 10 V SNVT_lev_percent: 0 – 100 %
0 – 100 %

CARE 4 / CARE-XL500 10.08.01 Upgrade and OS 2.06.05 and higher

When upgrading a CARE 4 project in CARE-XL500 10.08.01, previously ignored


default characteristics become active and are calculated by the controller. If, as in
most cases, a conversion table had been assigned additionally, the datapoint shows
wrong values.

Workaround
Check if a conversion table is allocated to the controller. If yes, delete it.
Check the values (reference points) of the characteristic in order to assure a
correct datapoint value display.

Actuator Run Time Handling


The actuator runtime handling is still located in the LON I/O modules but is
optimized as the following comparison shows:

CARE 4 and OS 2.06.00 - 2.06.04

• Changing the actuator runtime in CARE deletes existing bindings and


requests a re-binding
• Online changes of the actuator runtime for internal I/O modules can be
entered and are executed

1503 EN2Z-0937GE51 R0518


APPENDIX D: PLANT AND CONTROLLER UPGRADES AND DOWNGRADES CARE

• Online changes of the actuator runtime for open LON I/O modules can
be entered, but are ignored

CARE-XL500 10.08.01 and OS 2.06.05

• Change of the actuator runtime datapoint attribute in CARE is written into


the UCPT without deleting the binding
• Online changes of the actuator runtime for internal I/O modules can be
entered and are executed
• *Online changes of the actuator runtime for open LON I/O modules are
blocked. MMI displays *******

*Also supported for open LON applications using OS 2.06.05 in CARE 4.

OS XLIRC Support
A feature of CARE 3.0.00 is the support of mapping IRC controller configurations on
Excel 500 controllers (OS XLIRC), which provides basically the same functionality
as Excel OS 1.3 except active bus wide MMI tool functionality (BMMI).

CARE offers the ability to map a defined set of IRC Multicontroller fixed application
registers to Excel 5000 system user addresses that are accessible via an XBS
central or local user interfaces. If defined, room specific time programs can be
downloaded to an IRC Multicontroller.

The new features are added to the CARE Default Text Editor and to the
Miscellaneous Text Editor.

Default Text Editor


CARE provides sets of default files available for each new controller, which can be
edited or created by the Default (Text) Editor (DEFT). Creating of new default files is
only possible by copying an existing file set and then editing this copy.

This Editor of menu bar item Database is enhanced by two additional features for
editing Register Class Names and the Engineering Units Mapping Table in an OS
XLIRC default .ADL file.

When the selected default file set has OS version OS XLIRC, the new item OS
XLIRC of DEFT menu bar item Edit opens with a sub menu containing the two items
Register Class Names and Engineering Units Mapping Table.

For default text editing refer to Appendix: Default Text Editor.

Purpose Select default file of IRC Multicontroller configuration


Procedure 1. Dropdown menu bar item Database and select Default Editor.

CARE opens Default Text Editor box.

EN2Z-0937GE51 R0518 1504


CARE APPENDIX D: PLANT AND CONTROLLER UPGRADES AND DOWNGRADES

2. Pull down OS version window and select XL500 IRC-Map.

CARE displays all the default files available for OS version XL500 IRC-
Map (OS XLIRC).

3. Select specific default file, confirm with Save and select Close.

RESULT: CARE provides with specific IRC multicontroller default file to


be edited.

To edit the specific XLIRC features refer to IRC Register Class Names (DEFT) or
IRC Engineering Units (DEFT) to edit other default features refer to the main body of
this manual.

Default files can be edited or copied to create a new file, default file set(s) can be
deleted.

Purpose Create new default file for IRC Multicontroller configuration

Procedure 1. Dropdown menu bar item Database and select Default Editor.

2. Pull down OS version window and select XL500 IRC-Map.

3. Select specific default file and click Copy.

CARE displays the Copy Default Files box with the selected file name as
Source File Name and the same name for Target File Name.

1505 EN2Z-0937GE51 R0518


APPENDIX D: PLANT AND CONTROLLER UPGRADES AND DOWNGRADES CARE

4. Enter new target file name and confirm with OK.

CARE returns to Default Text Editor box.

5. Pull down OS version window and select XL500 IRC-Map again.

CARE displays all the default files including the new file available for OS
version XL500 IRC-Map (OS XLIRC).

6. Select new default file in the Default Text Editor box, confirm with Save and
select Close.

RESULT: CARE returns to Default Text Editor for editing the selected
new file.

In order to edit the specific XLIRC features refer to IRC Register Class Names or
IRC Engineering Units, to edit other default features refer to the main body of this
manual.

IRC Register Class Names (DEFT)


After selecting an IRC multicontroller default file, the class names of the IRC
registers can be modified.

Purpose Modify IRC register class name

Procedure 1. Pull down menu bar item Edit of CARE Default Editor and select
Register Class Names of item OS XLIRC.

NOTE: Item OS XLIRC only occurs if default file is of version XLIRC.

CARE Default Editor displays the IRC Register Class Names box.

2. Select the register class name to be modified.

EN2Z-0937GE51 R0518 1506


CARE APPENDIX D: PLANT AND CONTROLLER UPGRADES AND DOWNGRADES

CARE Default Editor displays selected register class name in the Modify
Register Class Name window.
3. Edit register class name and click Modify to confirm the modification.

4. Select another register class name to be modified or click Close to close the
box.

RESULT: The default file contains modified register class names,


which are available for each new controller.

NOTE: Opening the IRC Register Class Names box at another time, the new
IRC register class names occur in the Register Class Names windows
Available and Translated.

IRC Engineering Units (DEFT)


After selecting an IRC multicontroller default file, the texts of the IRC engineering
units can be mapped to another number.

Purpose Modify mapping of IRC engineering unit

Procedure 1. Pull down menu bar item Edit of the CARE Default Editor and select
Engineering Units Mapping Table of item OS XLIRC.

NOTE: Item OS XLIRC only occurs if default file is of version XLIRC.

CARE Default Editor displays the Engineering Units Mapping Table box.

2. Select the IRC engineering unit in the IRC Engineering Unit window.

CARE Default Editor marks the selected IRC engineering unit and the CARE
engineering unit opposite, and displays the appropriate unit texts.

3. Select a CARE engineering unit of the same type with another number in the
CARE Engineering Unit window and click Modify to confirm the modification.

4. Select another IRC engineering unit to be remapped or click Close to close the
box.

RESULT: The IRC engineering unit is mapped on another CARE engineering unit.

IRC Register Class Names (MISC)


After selecting a current IRC multicontroller, the class names of the IRC registers
can be modified.

Purpose Modify IRC register class name

Procedure 1. Pull down menu bar item Edit of CARE Miscellaneous Text Editor and
select Register Class Names of item OS XLIRC.

NOTE: Item OS XLIRC only occurs when the selected controller is of version
XLIRC.

CARE Miscellaneous Text Editor displays the IRC Register Class Names box
for the selected controller.

1507 EN2Z-0937GE51 R0518


APPENDIX D: PLANT AND CONTROLLER UPGRADES AND DOWNGRADES CARE

2. Select the register class name to be modified.

CARE Miscellaneous Text Editor displays selected register class name in the
Modify Register Class Name window

3. Edit register class name and click Modify to confirm the modification.

4. Select another register class name to be modified or click Close to close the
box.

RESULT: The controller files now contain modified register class names, which are
available for the selected controller.

NOTE: Opening the IRC Register Class Names box at another time, the new IRC
register class names occur in the Register Class Names windows Available
and Translated.

IRC Engineering Units (MISC)


After selecting a current IRC multicontroller, the IRC engineering units can be
mapped to another number.

Purpose Modify mapping of IRC engineering unit

Procedure 1. Pull down menu bar item Edit of the CARE Miscellaneous Text Editor
and select Engineering Units Mapping Table of item OS XLIRC.

NOTE: Item OS XLIRC only occurs when the selected controller is of version
XLIRC.

CARE Miscellaneous Text Editor displays the Engineering Units Mapping Table
box.

EN2Z-0937GE51 R0518 1508


CARE APPENDIX D: PLANT AND CONTROLLER UPGRADES AND DOWNGRADES

2. Select the IRC engineering unit in the IRC Engineering Unit window.

CARE Miscellaneous Text Editor marks the selected IRC engineering unit and
the CARE engineering unit opposite, and displays the appropriate unit texts.

3. Select a CARE engineering unit of the same type with another number in the
CARE Engineering Unit window and click Modify to confirm the modification.

4. Select another IRC engineering unit to be remapped or click Close to close the
box.

RESULT: The IRC engineering unit is mapped on another CARE


engineering unit.
S 1.1/1.1.30 Support
A feature of CARE 10.08.01 is the support of downgrading controller configurations
to OS version 1.1 and creating controllers and plants with OS version 1.1.30.

CARE offers the ability to downgrade controller configurations as long as the


engineered controller allows you to do so. If there are controller or plant restrictions,
which do not allow to downgrade, CARE displays the appropriate error message
and does not change the OS version.

Refer to the introduction of this appendix:

• For all other processes corresponding to downgrading a controller


configuration.
• To create controllers and plants with OS version 1.1.30.
• For information about general restrictions for creating and downgrading
of controllers and plants with this version.

Special restrictions for plants with this OS version include no support of:

1509 EN2Z-0937GE51 R0518


APPENDIX D: PLANT AND CONTROLLER UPGRADES AND DOWNGRADES CARE

• Flexible Multistage Points


• Flexible DO_Feedback_DI Points
• Flexible Pulse_2 Points
• Fast AI Points
• Fast Analog Input Points
• Pulsed Digital Output Points

NOTE: Unattached plants containing those points cannot be attached to a


controller with OS version 1.1.30.

EN2Z-0937GE51 R0518 1510


CARE APPENDIX G: ERROR MESSAGES

APPENDIX E: CHECK UTILITY


NOTE:
This section applies to CARE XL-5000 only.

Purpose This chapter describes the check utility that looks at multiple selected
projects to find non-unique user addresses and controller names.

Procedure 1. Click menu item Project, then submenu item Check User Addresses.

RESULT: The CHECK Windows Application Check window displays.


Example:

The Menu Bar Description note following this procedure


describes menu bar and button bar options.

2. Click menu bar item Select, then dropdown item Projects. Or, click the select
project button in the button bar (second button from the left).

RESULT: The Project Selection dialog box displays with a list of all
projects in the CARE database.

3. Click one or more project names to select them to be checked. Click OK to


begin the check process.

NOTE: After you click OK, you cannot return to this selection dialog box and
select other projects. You must exit the check utility and restart it to
check other projects.

To deselect a project, click it again. To exit without selecting any projects, click
Cancel.

RESULT: When the check utility is through, the results display in the
check window. Example:

1511 EN2Z-0937GE51 R0518


APPENDIX G: ERROR MESSAGES CARE

The first section of the display lists controller names that


were found in more than one project. In this example, the
name CPU1 was found in a project named AnothProject and
also in a project named TwinTowers.

The next section of the display lists user addresses found in


more than one project. In this example, user address
MaDmpr was found in both the AnothProject and the
TwinTowers project.

The end of the display is labeled with the words


COMPARISON COMPLETE.

4. You can print the results, save them to a file, and/or exit the utility.

To print the results, click menu bar item File, then dropdown item Print. Or, click
the print button in the button bar (third from the left). The Print dialog box
displays so you can select print options.

To save the results to a file, click menu bar item File, then dropdown item Save
As. Or, click the save as button in the button bar (first one on the left). The Save
As dialog box displays so you can enter a file name and location where
software should save the file.

To exit the utility, click menu bar item File, then dropdown item Exit. Or, double-
click the Ventilator icon in the upper left-hand corner of the window.

Menu Bar Description The menu bar contains three items, File, Select, and Help. The button bar
contains buttons that provide a shortcut to selecting the menu bar items.
The following text describes each menu bar item and shows its associated
button, if one exists.
File The File menu bar item provides the following dropdown items:

Save As Display the Save As dialog box to specify a file name and location where
software should save the check results.

EN2Z-0937GE51 R0518 1512


CARE APPENDIX G: ERROR MESSAGES

Print Display the Print dialog box to select print options (range of pages to print,
number of copies, etc) and print the check results. Shortcut keys: Ctrl P.

Print Preview Display the check results in a preview window as they would appear if
printed. The print preview window replaces the check window and allows
you to view either one or two pages at a time; move through the document;
zoom in and out of pages; and initiate a print.

Print Setup Display the Print Setup dialog box to specify a printer and other print
options. You can also display this dialog box from the Print dialog box (Print
dropdown item).

Exit Close the check utility function. You can also double-click the Ventilator icon
in the upper left-hand corner of the window to end the check session. Or,
use the shortcut keys (Alt F4).

Select The Select menu bar item provides one dropdown item, Projects. This item
displays the Project Selection dialog box that lists all current CARE projects.
You use this dialog box to specify which projects you want the check utility
to search. See Step C in the previous procedure for more details and a
dialog box example.

Help The Help menu bar item provides three dropdown items:

Index Display the Table of Contents topic in the on-line help file for the check
utility. See On-Line Help in the Getting Started chapter of this manual for
details on help files.
Using Help Display the Table of Contents topic in the on-line help file for the check
utility. See On-Line Help in the Getting Started chapter of this manual for
details on help files.

About CHECK Display the About dialog box to view the version number of the check utility.

Context-Sensitive Help

The button bar provides a context-sensitive button that changes the cursor
to a help question mark. Move the help cursor to the area of the window
where you want more information and click the mouse button. The help
topic related to that area of the window displays.

Troubleshooting The following text lists problems that may occur and suggests actions you
can take.

Incomplete Reports A report may not display in its entirety because software generated more
data than can fit in the window buffer. You can view the entire report by
printing it or saving the results to a file and then printing or viewing the file.
Or, you can run the check utility again but with fewer projects selected. Edit
the projects in CARE to remove duplications and run the check utility again.

Memory Exceeded Message Software generated more data than can fit in available memory. Run the
check utility again but with fewer projects selected. Edit the projects in
CARE to remove duplications and run the check utility again.

1513 EN2Z-0937GE51 R0518


APPENDIX G: ERROR MESSAGES CARE

No Data Base The check utility executable file (CHECK.EXE) must reside in the same
directory as the CARE database. If it is not, copy CHECK.EXE into the
same directory as CAREMAN.EXE.
No Projects Found in Data Base Software found a CARE database, but it does not contain any projects.
Verify that the check utility is in the correct directory (CHECK.EXE must be
in the same directory as CAREMAN.EXE) and that the correct version of
the CARE database is also there.

EN2Z-0937GE51 R0518 1514


CARE APPENDIX G: ERROR MESSAGES

APPENDIX F: ERROR MESSAGES


NOTE: This section applies to CARE XL-5000 only.

Purpose This chapter lists error messages that can appear during various CARE
functions (alphabetically arranged) and a list of error messages that can
occur during RACL generation.

General Errors

Message Description

Alarm Message An Alarm message dialog box may display after a controller
download. The box displays date and time, user address and
value/status (if relevant), and an alarm message. This
Appendix lists some of the alarm messages that can display.
Communication problems When you exit CARE, the serial port used for communication
with controllers may remain in use and thus be unavailable to
other software applications.

You can use the Control Panel 386 Enhanced function to issue
a warning message whenever two applications attempt to
control the same COM port. The 386 Enhanced function dialog
box lists available COM ports in the Device Contention box.
Select the COM port CARE uses and enable the Always Warn
option.

When the warning message occurs, reset the serial port. The
Windows Terminal function can usually release the serial port
and make it available for the next application. Start the
Terminal function. The Terminal window displays with a menu
bar that includes a Settings item. Select Settings, then the
Communications dropdown item. When the Communications
dialog box displays, select the COM port in question, click OK,
and then exit the Terminal function.

Try running the new application. If the application will not


communicate (for example, no data is available), close the
application, reboot the PC, and restart the application.
Controller already exists While establishing a new controller, you entered the name and
number of an existing controller. Change the name and
number.
Control loop is incomplete
or
Control strategy is incomplete The control loop created is not completely connected. Check
out the control loop.
Duplicate math output name.
Names must be unique. If you enter a new formula name in the New Variable Name
dialog box and another formula already exists with that name,
this message displays. All formula names must be unique
within a controller. The New Variable Name dialog box displays
from the Math Editor dialog box. See Switching Logic, MATH
Rows section for an example of the Math Editor dialog box.
Error establishing data Internal database error. This error cannot be eliminated.
Hardware point cannot be The physical point type selected cannot be modified.
modified
HW Config. failure This message may display in an Alarm Message dialog box
after a download to a controller. The message means that
there are not enough hardware modules or enough of the right
type of hardware modules to support the database. For
example, there may be digital output points in the database but
no digital output modules in the controller.

1515 EN2Z-0937GE51 R0518


APPENDIX G: ERROR MESSAGES CARE

HW Conf. too large This message may display in an Alarm Message dialog box
after a download to a controller. The message means that the
database requires less hardware than the controller physically
has. For example, an Excel 500 controller may have two
analog input boards, but the database requires only one. This
alarm always appears when loading an Excel 80A or 100A
controller if the points required are less than or equal to one
Excel 500 module. For example, an Excel 100A can have 12
analog inputs but if the database has 8 or less inputs (the size
of an XF521 or XF526 board), the alarm displays.
Illegal character in math
expression These messages display after entry of a math formula in the
Illegal character in User Address Math Editor dialog box. See Switching Logic, MATH Rows
section for an example of the Math Editor dialog box. See
Excel CARE Control Icons User Guide 74-5577 (US) / EN2B-
0184 (Europe) for rules for formula entry.
Insufficient hard disk capacity to
print The Windows print spooler could not establish the spooler file
on the PC disk. As a result, the printing operation will take
longer. Delete unnecessary files from the PC disk.
Insufficient memory
or
Insufficient memory space There is insufficient memory available for the selected function.
Divide the action into several steps and repeat.
Insufficient memory to print The main computer memory is inadequate to print. Increase
the main computer memory.
Invalid entry The entry made in the mathematical editor is incorrect. Correct
the mathematical formula.
Invalid password The password entered is incorrect. Repeat password entry.
Invalid user address The user address entered is incorrect. Only letters and
numbers may be used.
Macro cannot be deleted The selected macro cannot be deleted.
Macro name already exists An attempt has been made to overwrite an existing macro.
Select another name, one that does not exist, in order to save
the macro.
Macro name does not exist The macro name given does not exist in the database.
Mathematical function could not
be saved The formula in the mathematical editor could not be saved. Try
to save again.
Maximum number of hardware
points reached in controller
or
Maximum number of hardware
points reached in plant The maximum number of physical points for a controller has
been exceeded. A maximum of 128 different physical points
may be specified.
Maximum number of modules
exceeded
or
Maximum number of modules
reached in the controller The maximum number of modules for a controller has been
exceeded. One EXCEL 500 Controller can contain a maximum
of 16 input/output modules.
Maximum number of PID
controllers per plant has been
reached
or
Maximum number of PID The maximum number of controllers in the plant have been
controllers exceeded exceeded. Maximum number of controllers per plant is 20.
Maximum number of software
points exceeded The maximum number of pseudopoints for the controller has
been exceeded. A maximum of 256 different pseudopoints
may be defined.
Minimum value > maximum value While entering internal parameters, the lower limit has been set
above the upper limit.

EN2Z-0937GE51 R0518 1516


CARE APPENDIX G: ERROR MESSAGES

Missing double quote This message can display after entry of a math formula in the
Math Editor dialog box. All user addresses in a formula must
be surrounded by double quotes. See Switching Logic, MATH
Rows section for an example of the Math Editor dialog box.
See Excel CARE Control Icons User Guide 74-5577 (US) /
EN2B-0184 (Europe) for rules for formula entry.
More than 128 T-registers in The maximum number of T-registers (time registers) has been
module exceeded. Maximum number of T-Registers is 128.
More than 128 X
or
Y-Registers in module The maximum number of X-registers or Y-registers has been
exceeded. Maximum number of X or Y-registers is 128.
Name/Number/Type conflict The name or the number of the new controller created already
exists.
No controller assignment for The selected controller has not been used in the selected
project project.
No controller in database CARE cannot find the controller in the database.
No controller in the project A controller has not been established for this project.
No control loop found No control loop has been created for the plant selected.
No control loop symbol found CARE cannot find the control loop icon. Exit from the control
strategy. Recall the control strategy again.
No element information CARE cannot find any information about the elements of the
selected segment.
No memory for polynomial There are too many pivot points. Reduce the number of pivot
points.
No more memory available CARE has exceeded the memory. Increase the memory size of
the computer.
No plant for the controller No plant has been assigned to the selected controller.
No plant in database CARE cannot find a plant in the database belonging to the
project.
No plant type in database
or
No plant type exists CARE cannot find a plant type in the database for the plant
selected.
No printer found in WIN.INI No printer has been entered in the WIN.INI file. Please install
the printer and then recall the function again.
No software point exists A pseudopoint has not been created for the plant selected.
No software point has been
selected A pseudopoint box has not been selected on the pseudopoint
bar. Select a box on the pseudopoint bar to eliminate the error.
No switching table exists
or
No switching table found No switching table has been created for the plant selected.
No text selected If you click a Copy or Cut button and you have not highlighted
any text to copy or cut, this message displays. For example,
the Math Editor dialog box has Cut, Copy, and Paste functions
that would generate this error. See Switching Logic, MATH
Rows section for an example of the Math Editor dialog box.
Now removing controller
application files due to changes
in database. Please retranslate
this controller. This notice means that the controller has been translated but
changes have been made to its files. These changes were
made with one of the editors (Miscellaneous Text, Data Point
Description, or Time Program). This notice appears when you
exit an editor. You should retranslate the controller.
Number of columns > 128 in one
module The maximum number of columns has been exceeded.
Maximum number of columns is 128.
Number of parameter
registers in Module > 128 The maximum number of parameter registers has been
exceeded. Maximum number of parameter registers is 128.
Number of submodules > 127 The maximum number of submodules (subprograms) has been
exceeded. Maximum number of submodules is 128.
Number of Z-registers in module
> 128 The maximum number of Z-registers (dynamic registers) has
been exceeded. Maximum number of Z-registers is 128.

1517 EN2Z-0937GE51 R0518


APPENDIX G: ERROR MESSAGES CARE

Paste buffer is empty If you click a Paste button and you have not copied or cut any
text, this message displays. For example, the Math Editor
dialog box has Cut, Copy, and Paste functions that would
generate this error. See Switching Logic, MATH Rows section
for an example of the Math Editor dialog box.
Plant already exists The newly created plant has been given the name of a plant
that already exists. Select a new name that does not already
exist.
Plant could not be assigned
to controller <Controller Name> The desired controller could not be assigned to the plant.
Assign another controller to the plant.
Plant segment cannot be added The maximum number of plant segments has been reached.
Price data not available The calculation routine in CARE cannot find the price data.
Copy the price data file (CAREKALK.DAT) from the diskette
into the CARE directory on your PC disk.
Printer set for portrait format. Do
you want landscape format? If portrait format is preselected, this question displays before
printing the plant graphics. Landscape format can then be
reset.
Project already exists An attempt has been made to assign an existing project name
to a new project. Please choose another name that does not
already exist.
Project <Name> does not exist The selected project does not exist.
Segment cannot be deleted. It is
still connected The segment to be deleted from the plant is still in use
elsewhere in the plant. This segment can only be deleted once
it has been removed from all relevant control loops or switching
tables.
Several switching tables for user
address This warning may appear during a plant translation. It means
that more than one switching table commands the same point.
This situation is very common with analog points and
sometimes with digital points. It could be a problem if you have
inadvertently created two switching tables commanding the
same point to do opposite actions. You may want to check
your tables.
Software address already exists A new pseudopoint user address already exists. Please select
a new user address.
Software point could not be
established The pseudopoint cannot be generated because an existing
user address has been used. Modify the user address.
Switching table not included in
macro library The switching table cannot be included in the macro database.
Repeat the save as a macro.
Switching table not saved due to
missing user address The user address for the control device has been omitted from
the switching table being loaded as a macro.
This user address already exists
or User address already exists in
controller. Modify? Two plants have been assigned to one controller. In both
plants, at least one user address is identical so the controller
does not know which plant to associate with it.
Take care to ensure that identical user addresses are not used
when a controller controls more than one plant.
Translate function gray If the Translate item is gray (unavailable) under the Controller
menu, one or more of the control strategies for the current
plant may be incomplete.
Unknown point type CARE does not recognize the selected plant type. Perhaps a
blank space has been included in the new name during
renaming or copying? Currently, only the heating and air
conditioning plant types exist.
WIN.INI error. Change printer There is an error in the WIN.INI file. Call up the "Change..."
function in the printer menu.

EN2Z-0937GE51 R0518 1518


CARE APPENDIX G: ERROR MESSAGES

RACL Generation Errors


RACL generation errors are usually a result of insufficient memory or wrong
data from the database. Suggestions:

• Check the following list of messages.


• Try closing other open applications and/or rebooting the PC.
• For database problems, try retranslating the controller and/or detaching
and attaching the controller.

If an internal error displays, the real cause may stem from other software
applications in Windows or DOS rather than from RACL. Again, rebooting
may help.

Message Description

!!! No control loop found !!! No control loop has been defined in CARE. This is a
warning.
No control loop icon found An empty control loop has been found. Loading does
not make sense.
Insufficient memory More memory is required.
Memory lock error A memory block could not be locked. This error should
not occur in Windows 3.1
Error in data base function A database function returned an error code.
Nullpointer in parameter list A local memory handler function in RACLGEN got a
null pointer. This error should never occur in a final
version.
Invalid parameter list handler This text is wrong. It should be “Invalid handle in
parameter". It says that a memory block handle
passed to a RACLGEN memory handler function is
null.
Memory reallocate error Error in memory handler.
Inconsistency in CARE database The data from the CARE database is not plausible.
Possible causes:

- an empty input connection in a control loop.


- unknown delay type in a switching table
Parameter error in function This message is no longer in use.
Array overload error This message is no longer in use.
!!! No switching table found !!! No switching table has been defined in CARE. This is
a warning.
Specified memory size > 64K A memory block greater than 64 has been requested.
Possible causes:

--a large application in CARE


- wrong database connection information which leads
to an
open connection in RACL.
Module: more than 128 T-registers
More than 128 X or Y-registers in modules
Number of module parameter registers > 128 Too many registers of the specified type required for
Number of module Z-registers > 128 the application.
Trying to connect outside of a symbol Attempt to connect two RACL symbols where the
requested input/output is above the existing
connectors.
Trying to connect two data points without I/O statement Internal RACL error that should never occur.

1519 EN2Z-0937GE51 R0518


APPENDIX G: ERROR MESSAGES CARE

Internal memory inconsistant A plausibility check of RACLGEN's internal database


detected an error. Possible causes:

- any input connection at a MAT symbol.


- an undefined input type in the internal RACL chart.
- an undefined output type in the internal RACL chart.
- attempt to connect two RACL symbols, which do not
have
the appropriate number of inputs and outputs.
- an unknown point type when loading the .IPL file.

For example, if you use a Math statement that includes


a flag in a control loop that also uses an XFM, software
generates incorrect code during plant translation. See
the Control Strategy chapter, Pseudopoints and Flags,
for details.
Switching table overflow (too many rows, columns or A switching table has too many rows, columns, or
XOR's) XORs.
User address or address type not found A point name has been referenced that cannot be
found in the data read from the .IPL file. In many
cases, this error is a result of a reversed notation in a
MAT function.
Invalid type for input data point Attempt to access input in a way that is only allowed
for outputs. This error does not normally display. If it
does, there may be an error in the database data.
Invalid type for output data point Attempt to access output in a way that is only allowed
for inputs. This error does not normally display. If it
does, there may be an error in the database data.
Mathematical function stack underflow Internal MAT function stack underflow. This error
should never occur.
Error interpreting the mathematical function row Usually, this error means there is wrong data in the
database.
Error: Recursion in mathematical function row Another MAT function is referenced in a MAT function.
Invalid type of CARE symbol conversion An unknown symbol has been read from a control
loop.
Function not supported This message is no longer in use.
Type of data point used in this location not permitted The type connected to the symbol must be a point.
No plant for the active controller available No plant found in the database. This error does not
usually occur.
Program stack overflow Too many recursions have been made to convert a
MAT function.
Number of submodules > 127
Number of columns in a module > 128 Excessive number of submodules or columns in a
module.
RACL opcode not supported An internal error in RACLGEN that should not occur.
Too few internal parameter in CARE symbol Too few parameters for a control loop symbol from the
CARE database.
Too few X-registers in symbol An internal error in RACLGEN that should not occur.
No columns in switching table
No rows in switching table
XOR tables with only one column or row forbidden
Multiple columns with only one row forbidden Invalid switching table read from the database.
Inputs must be continuously connected Inputs of a control loop symbol have not been
continuously connected.
No more space for message Message listbox overflow.
Switching table function values buffer overflow Too many switching tables defined for one point.
The index definitions for standard files missing This text is wrong. It displays when the directory for the
XI584 standard files is not defined in the CARE.INI file.

EN2Z-0937GE51 R0518 1520


CARE APPENDIX G: ERROR MESSAGES

The index definitions for XI583 missing This text is wrong. It displays when the directory for the
XI584 and CARE.EXE files is not defined in the
CARE.INI file.
The standard files name definitions missing The name for the standard files is missing in the
CARE.INI file.
Warning. Application is too big The sum of all application parts exceeds the maximum
defined in RGWRFILE.C. The algorithm is also in
RGWRFILE.C
Error opening or reading XL100, XL80 intermediate file
Data point description file not found These messages are no longer in use.
Error opening temporary switching table file
Error generating temporary switching table file
Error reading temporary switching table file
Error writing to temporary switching table file
Error deleting temporary switching table file
Error writing to temporary control loop file
Error reading the temporary control loop file RACLGEN creates a temporary file for each switching
Error deleting the temporary control loop file table and control loop. These messages indicate file
I/O errors.
Error generating the loadable T-register file
Error generating the loadable Z-register file
Error generating the loadable P-register file
Error generating the loadable EXCEL code file
Error generating the loadable EXCEL code or P-register
file File I/O error in the last pass in RGWRFILE.C
Error generating the loadable EXCEL code file
Error copying the XI583 standard files
Error opening the project file
Error reading the project file These messages are no longer in use.
Error generating the reference file The function for writing the reference file is in
RGWRFIL1.C, but the error is in RGWRFILE.C based
on the return code.
Error whilst loading engineering units The function for reading engineering units is in
RGINIT.C, but the error is in RGWRFILE.C based on
the return code.
User address (or value of operand) >127 A plausibility check message in RGWRFILE.C while
creating the RACL code file. It always indicates an
internal error where the real cause may stem from
other software applications in Windows or DOS
rather than from RACL. Rebooting may help.
Error in submodule file An error while loading and linking an XFM in
RGWRFILE.C.
Error in Input assignment! An illegal connection between control symbols was
Error in Output assignment! found in RGSETSYM.C. The problem is usually wrong
data from the database.
Error in internal XFM-Symbol parameters! An empty file name or wrong version of an XFM was
found in the database.
Datapoint for XFM->CSD assignment not found! An XFM references a point that cannot be found in the
point list of RACLGEN, normally the contents of the
.IPL file plus CARE flags and mathematical function
names.
Different version of XFM symbol and .CSD file! The version of an XFM in the database and the
referenced file does not match.
File is not a .CSD file for Honeywell-CARE! Illegal file header found in a .CSD file.
Too much datapoints in .CSD File! The number of points in a .CSD file exceeds 255.
Error in Command Line Syntax error in run-time command line of RACLGEN.
Illegal project name! No project name passed via run-time command line.
Illegal target controller name! No target controller passed via run-time command line.

1521 EN2Z-0937GE51 R0518


APPENDIX G: ERROR MESSAGES CARE

Error opening data point description (.IPL)


Error opening data point text description (.KFX) Open error in RGPCB_IN.C.
Maximum number of software points exceeded More than 128 software points found in RGPCB_IN.C.
There was an error accessing the Environment Record
There was an error creating the Alarm Text File
There was an error creating the Analog Eng Units File
There was an error creating the Digital Eng Units File
There was an error creating the Point Descriptor File
There was an error creating the Time Program File
There was an error creating the Characteristics File Database and file I/O errors in RGMKFILE.C.
Illegal or duplicate datapoint access! Writing access to one point has been attempted:
- from more than one symbol in one or more control
loops
- from an internal XFM reference and from anywhere
outside
- from more than one switching table.

EN2Z-0937GE51 R0518 1522


CARE

INDEX

1523 EN2Z-0937GE51 R0518


CARE

EN2Z-0937GE51 R0518 1524


CARE INDEX

INDEX

Alarm hysteresis
set for analog input, 324, 352
+ Alarm Number, 1305
+XOR table changes, 291 Alarm point
select for pseudo digital point, 356
set for digital input, 334
3 Alarm text
3 position output BACnet analog input, 365
BACnet analog output, 373, 379, 383, 392, 462 BACnet analog output, 375
BACnet analog value, 387
BACnet binary input, 396
A BACnet binary output, 408
BACnet binary value, 418
Abbreviations
BACnet multi-state input, 429
grid, 309
BACnet multi-state output, 436
Access rights list, 877, 1191
BACnet multi-state value, 442
create, 880
BACnet pulse converter, 449
Active state
copy, 491
set for digital input, 334
create, 491
set for digital output, 337
display, 491
set for flex point, 340
edit, 491
set for pseudo digital point, 356
replace, 491
active/inactive text
select for analog input, 323
BACnet binary input, 396
select for flex point, 340
BACnet binary value point, 418
select for pseudo analog point, 352
Add
select for pseudo digital point, 355
delay for a digital command result, 279
Alarm texts (BACnet)
dynamic elements, 1101
copy, 495
housing, 545
create, 495
LON device to the network, 1232
delete, 495
new static images to graphic library, 1122
edit, 495
point
Alarm type
to daily program, 531
critical/noncritical, 333, 337
segment, 197
select for digital input, 333
static image elements, 1103
select for digital output, 337
time program, 525
Alarm value
Add point
BACnet binary input, 397
to daily program, 531
Alarming
Additional information about selected segment, 221
enable for BACnet analog input, 366
Address LON device, 1324, 1326, 1327
enable for BACnet analog output, 376
Address table entries allocation and Syncronize, 75, 1341
enable for BACnet analog value, 387
Adjust graphic
enable for BACnet binary input, 397
graphics editor, 1082
enable for BACnet binary output, 409
Air conditioning
enable for BACnet binary value, 418
plant type, 87, 158
enable for BACnet multi-state input, 430
Alarm delay
enable for BACnet multi-state output, 437
BACnet analog input, 366, 367, 377, 388, 409, 419, 430,
enable for BACnet multi-state value, 442
437, 443, 450
enable for BACnet pulse converter, 449
BACnet binary input, 397
Allocate
set for analog input, 324
IP address to BACnet controller, 789, 790, 808
set for digital input, 334
Analog condition rows, 283
set for flex point, 341
Analog engineering units, 1466
Alarm delay normal
copy, 486
BACnet analog input, 366, 388
create, 486
BACnet analog output, 377
display, 486
BACnet binary input, 397
edit, 486
BACnet binary output, 409
maximum, 486
BACnet binary value, 419
replace, 486
BACnet multi-state input, 430
Analog input
BACnet multi-state output, 437
attributes table, 1476
BACnet multi-state value, 443
board types, 203, 321
pulse converter, 450
characteristics, 203

1525 EN2Z-0937GE51 R0917


INDEX CARE

critical alarm type, 324 particular IP address to controller, 816, 818


display attributes, 321 point to terminal (TAF), 555
hide, 324 pseudopoint to software point bar, 241, 243
initialization value, 323 user address to time program, 116, 527
modify, 203 value conversion table, 1307
modify attributes, 321 value conversion table to LON device, 1282
point ID, 322 assignment
point role, 322 local mode, 1214
point subtype, 322 Attach
select alarm text, 323 plant to a controller, 179
select characteristic, 323 Attribute
select descriptor, 323 Normally Open/Normally Closed, 1492
select engineering unit, 323 Attribute settings
select operator access level, 323 search and replace, 465
set alarm delay, 324 Attributes
set alarm hysteresis, 324, 352 analog input, 1476
set high alarm limit, 324 analog output, 1477
set high warning limit, 324 copy values in grid, 463
set low alarm limit, 324 copy values in tree, 464
set low warning limit, 324 digital input, 1479
set sensor offset, 324 digital output, 1480
set trend cycle minutes, 325 DO feedback DI point, 1485
set trend hysteresis, 325 drag and drop in tree, 464
set write protect priority, 323 global analog point, 1484
suppress alarm, 324 global digital point, 1484
Analog input point multistage, 1487
BACnet object type, 365 pseudo analog point, 1478
Analog inputs on panel bus pseudo digital point, 1481
send on delta resolution pseudo totalizer point, 1483
Analog output pulse 2 point, 1486
attributes table, 1477 totalizer point, 1482
board types, 205, 326 autobinding
display attributes, 326 local mode, 1214
hide, 329 shared/open modes, 1215
initialization value, 329 Autobinding, 1199, 1217, 1218
modify, 205 datapoint to NV, 1239
modify attributes, 326 Autodetect settings, 1395
point ID, 327 Automapping, 1199, 1217, 1218
point role, 327 Automatic mapping
select descriptor, 328 between CARE datapoints and OLink points, 714, 717
select engineering unit, 328 between CARE datapoints and OPS points, 741
select operator access level, 328 Automatically create
set time to close, 329 user addresses of the same name, 257
set time to open, 329 Autoroute
set trend hysteresis, 329 connecting lines, 949
set write protect priority, 329
suppress alarm, 329
Analog output point
B
BACnet object type, 375 Back up
Analog row CARE database, 570
switching table, 268 project, 571
Analog value point Backup
BACnet object type, 387 project (graphics handling), 1134
Application BACnet
download into BACnet controller, 820 copy alarm texts, 495
upload into BACnet controller, 822, 823 copy color maps, 495
Arrange copy descriptors, 495
NVs, 1312 copy state texts, 495
windows, 319 create alarm texts, 495
Assign create color maps, 495
color map to datapoint, 481 create descriptors, 495
Conversion table, 1302, 1307 create state texts, 495
daily program to holiday, 535 default network structure, 781
daily program to week day, 120, 533 delete alarm texts, 495
daily program to yearly progam, 537 delete color maps, 495
flag to software point bar, 241, 243 delete descriptors, 495
LON devices, 1232 delete state texts, 495

EN2Z-0937GE51 R0917 1526


CARE INDEX

edit alarm texts, 495 deadband, 388


edit color maps, 495 descriptor, 387
edit descriptors, 495 determine Read access for web interface, 387
edit state texts, 495 enable alarming, 387
Graphics Editor, 1068 engineering unit, 387
network engineering, 754 high limit enable, 388
BACnet analog input low limit enable, 388
alarm delay, 366, 377, 388, 409, 419, 430, 437, 443, notify type, 388
450 point role, 388
alarm delay, 367 suppress alarm, 388
alarm delay normal, 366, 388 transition event, 388
alarm text, 365 BACnet analog value point
assign characteristic, 366, 507 display attributes, 386
assign notification class, 366 modify attributes, 386
change of value (COV), 367 BACnet binary input
create characteristic, 366, 507 active/inactive text, 396
deadband, 367 alarm delay, 397
descriptor, 365 alarm delay normal, 397
determine Read access for web interface, 366 alarm text, 396
enable alarming, 366 alarm value, 397
engineering unit, 365 assign notification class, 397
high limit enable, 367 descriptor, 396
low limit enable, 367 determine Read access for web interface, 396
map to NV-Input, 365 enable alarming, 397
max. present value t, 367 map to NV-Input, 396
min. present value, 367, 398 notify type, 397
notify type, 366 point role, 397
point role, 367 suppress alarm, 397
safety value, 367 transition event, 397
sensor offset, 367 BACnet binary input point
suppress alarm, 366 display attributes, 395
transition event, 367 modify attributes, 395
BACnet analog input point polarity, 398
display attributes, 364 BACnet binary output
modify attributes, 364 alarm delay normal, 409
BACnet analog output alarm text, 408
3 position output, 373, 379, 383, 392, 462 assign notification class, 409
alarm delay normal, 377 descriptor, 408
alarm text, 375 determine Read access for web interface, 409
assign characteristic, 376 enable alarming, 409
assign notification class, 376 feedback value, 410
change of value (COV), 377 map to NV-Input, 408
Continuous with switch, 373, 379, 383, 392, 462 notify type, 409
create characteristic, 376 point role, 409
deadband, 377 suppress alarm, 409
descriptor, 375 transition event, 409
determine Read access for web interface, 376 BACnet binary output point
enable alarming, 376 display attributes, 407
engineering unit, 375 modify attributes, 407
high limit enable, 377 polarity, 410
low limit enable, 377 relinquish default, 414
map to NV-Input, 375 BACnet binary value
max. present value t, 377 alarm delay normal, 419
min. present value, 377 alarm text, 418
notify type, 377 assign notification class, 418
optimization, 388 descriptor, 418
point role, 377 determine Read access for web interface, 418
relinquish default, 377, 388, 389, 419, 443 enable alarming, 418
suppress alarm, 377 notify type, 419
transition event, 377 optimization, 428
BACnet analog output point point role, 419
display attributes, 374 relinquish default, 419
modify attributes, 374 suppress alarm, 419
BACnet analog value transition event, 419
alarm text, 387 BACnet binary value point
assign notification class, 387 active/inactive text, 418
change of value (COV), 388 display attributes, 417

1527 EN2Z-0937GE51 R0917


INDEX CARE

modify attributes, 417 suppress alarm, 437


BACnet controller transition event, 437
allocate IP address, 789, 790, 808 BACnet multi-state output point
connect remotey to particular controller, 816 display attributes, 435
connect to, 811 modify attributes, 435
connect to particular controller, 818 BACnet multi-state value
connect to remote controller, 818 alarm delay normal, 443
create certificate, 838 alarm text, 442
crossover cable connection, 807, 808, 809 assign notification class, 442
display properties, 757 descriptor, 442
download application, 820 determine Read access for web interface, 442
download firmware, 833 enable alarming, 442
download settings, 819 multi-state properties, 443
global options, 72 notify type, 443
LAN connection, 807, 811 optimization, 443
Mlodbus support, 840 point role, 443
modify properties, 757 suppress alarm, 443
remote, 818 transition event, 443
remove BBMD functionality, 805 BACnet multi-state value point
set as BBMD device, 805 state texts, 442
settings, 813 BACnet multi-state value point
setup, 807 display attributes, 441
start application, 832 modify attributes, 441
stop application, 832 BACnet network
upload application, 822, 823 configure, 783
USB connection, 808 design, 783
BACnet controller configuration BACnet object type
reset, 836 analog input point, 365
BACnet device analog output point, 375
create, 800 analog value point, 387
delete, 807 binary input point, 396
move in network, 806 binary output point, 408
BACnet device ID schema, 78 binary value point, 418
BACnet ID multi-state input point, 429
datapoint property description, 803 multi-state output point, 436
BACnet Miscellanous Text Editor, 494 multi-state value point, 442
BACnet multi-state input pulse converter point, 449
alarm delay normal, 430 reference input point, 459, 462
alarm text, 429 BACnet object type multi-state value point, 442
assign notification class, 430 BACnet pulse converter
descriptor, 429 alarm text, 449
determine Read access for web interface, 430 assign characteristic, 449
enable alarming, 430 assign notification class, 449
map to NV-Input, 429 change of value (COV), 451
multi-state properties, 431, 441 COV period, 451
notify type, 430 create characteristic, 449
point role, 430 descriptor, 449
state texts, 429 determine Read access for web interface, 449
suppress alarm, 430 enable alarming, 449
transition event, 430 engineering unit, 449
BACnet multi-state input point high limit enable, 450
display attributes, 428 low limit enable, 450
modify attributes, 428 map to NV-Input, 449
BACnet multi-state output notify type, 450
alarm delay normal, 437 point role, 450
alarm text, 436 transition event, 450
assign characteristic, 507 BACnet pulse converter point
assign notification class, 437 display attributes, 448
create characteristic, 507 modify attributes, 448
descriptor, 436 BACnet pulse convertoer
determine Read access for web interface, 437, 461, 462 deadband, 450
enable alarming, 437 BACnet reference input point
feedback value, 438 display attributes, 458, 461
map to NV-Input, 436 modify attributes, 458, 461
notify type, 437 BACnet reference output point
point role, 438 property, 448
state texts, 436 BACnet subnet

EN2Z-0937GE51 R0917 1528


CARE INDEX

create, 789 database


delete, 807 backup, 570
Ethernet settings, 790 database restore, 572
IP address ranges, 790 Time schedules, 650
BACnet subsystem CARE application
create, 788 change, 1196
delete, 807 CARE datapoints
BACnet-bus properties automatic mapping, 714, 717, 741
define, 783, 785, 787 map to OLink points, 714
BACShark map to OPS points, 740
create EDE file, 1027 unmap from OLink points, 719
Balco 500, 203 unmap from OPS points, 742
Baudrate CAREDOC.INI file
change, 1395 settings, 632
scan, 1406 C-bus default
set, 1395 set when creating controller, 1210
BBMD C-bus mapping errors, 649
remove from BACnet controller, 805 C-bus name, 1210
set BACnet controller as BBMD device, 805 C-bus subsystem
BBMD functionality, 805 create, 1204
Binary input point Celsius
BACnet object type, 396 use for control icons, 1465
Binary output point Certificate
BACnet object type, 408 create for BACnet controller, 838
Binary put point Certificates, 838
BACnet object type, 408 Change
Binary value point +XOR table, 291
BACnet object type, 418 baudrate, 1395
Binding controller information, 186
LON devices, 1232 Controller number, 187
remove, 1257 HMI pin, 879, 890
Binding NVs, 1197 password, 879, 889
Binding types plant Information, 160
for NVs, 1244 plant name, 649
Board types point type (TAF), 557
for analog inputs, 203, 321 project name, 152
for analog outputs, 205, 326 project password, 148
for digital inputs, 207, 331 switchpoint start/end time, 1169, 1171
for digital outputs, 208, 335 switchpoint value, 1172
Broadcast hysteresis target I/O hardware, 1219, 1222
set for global analog point, 346 user address, 215
Broadcast type, 75, 1341 Change of value (COV)
Build BACnet analog input, 367
value conversion table, 1313 BACnet analog output, 377
Build control loop, 228 BACnet analog value, 388
Buttons BACnet pulse converter, 451
modify properties (graphic editor), 1127 Change system configuration, 189
Buttons Changes
add to drawing pane, 1087 on CARE application, 1196
create, 1103 on network interface, 1196
edit (graphic library), 1124 Channel
set properties, 1089 configure, 1211
show properties (graphic editor), 1127 create, 1205
set default, 1208
Channels
C connect, 1206
Calculated value, 287 Characteristic
Calendar assign to BACnet analog input, 366, 507
copy, 1190 assign to BACnet analog output, 376
create, 1183 assign to BACnet multi-state output, 507
delete, 1190 assign to BACnet pulse converter, 449
edit, 1188 create for BACnet analog input, 366, 507
show references, 1190 create for BACnet analog output, 376
Calendars, 1135, 1183 create for BACnet multi-state output, 507
view, 1183 create for BACnet pulse converter, 449
Cancel up- or download, 1406 select for analog input, 323
CARE Characteristic curve, 492

1529 EN2Z-0937GE51 R0917


INDEX CARE

Characteristics display, 1251


copy, 492 Connecting lines, 946
create, 492 autorouting, 949
display, 492 delete completed connection, 951
edit, 492 delete segment, 951
reference points, 492 drawing methods, 948
replace, 492 manipulating, 949
Check move segment, 950
control loop, 262 routing, 949
non-unique controller names, 1511 split segment, 950
non-unique user addresses, 1511 Connection
Check utility, 1511 configure, 1256
Chilled water connecting lines, 946
plant type, 87, 158 convert, 954
Client, 142 delete, 1257
Clock-time-interval-based Reading, 871 delete completed, 951
Close drawing methods, 948
control strategy, 262 remove, 951
plant schematic, 222 type, 946
switching logic, 298 Connection type
switching table, 276 ´connection`, 946
C-NAP Groups/Wildcard Points Box, 668 constant, 953
Color map Connections
assign to datapoint, 481 show for devices, 1255
Color maps (BACnet) Constant
copy, 495 connection type, 953
create, 495 Context menu, 544
delete, 495 graphics editor, 1076
edit, 495 Continuous output signal, 205
Column width Continuous with switch
change in grid, 310 BACnet analog output, 373, 379, 383, 392, 462
COM settings, 1395 Control icon
Command changes connect to another control icon, 232
switching table, 278 connect to plant, 229
Commission connection examples, 233
devices, 1327 delete, 235
Common points, 142 multiple inputs, 233
Comparison type, 283 place, 228
Comparison value, 284 Control icons
Computer Aided Regulation Engineering, 20 use of celsius, 1465
Condition rows use of Fahrenheit, 1465
analog, 283 Control loop
digital, 280 check, 262
Configuration parameters, 1195 copy, 260
Configure create, 227
BACnet network, 783 delete, 261
channel, 1211 incomplete, 262
columns for fast access list, 770 load, 227
connection, 1256 loop object settings, 1059
drag and drop, 465, 479 management, 260
grid, 306 parameter access, 1055, 1056
LON-bus, 1212 select, 227
network, 1201 Control Loop
NV list display, 1280 build, 228
Connect modify, 228
CARE datapoint to NV, 1239 Control loop engineering steps
channels, 1206 loop object, 1060
NVs together, 1239 Control macro
to BACnet controller, 811 parameter access, 1055, 1062
to controller, 125 Control strategy
to particular BACnet controller, 818 close, 262
to remote BACnet controller, 818 exit, 262
Connect control icon to plant, 229 interaction with switching logic, 272
Connect flag to control loop, 249 overview, 98, 223
Connect pseudopoint to control loop, 249 physical point bar, 226
Connect two control icons, 232 software point bar, 226
Connected devices unused software points, 226

EN2Z-0937GE51 R0917 1530


CARE INDEX

window, 224 display, 187, 188


Control Strategy Controller OS version
capacities, 223 display, 189
Control strategy loops modify, 189
print, 599 set, 85, 177
Controller Controller power supply
change country code, 189 define, 85, 177
change default file set, 189 display, 189
change engineering units, 189 modify, 189
change installation type, 189 Controller system status
change OS version, 189, 1489 event enrollment alaming, 905
change power supply, 189 Controller type
change type, 188 define, 85, 177
check non-unique names, 1511 display, 188
connect, 125 modify, 188
copy, 183 Conversion
copy graphic, 1133 values for analog points, 492
create, 176 Conversion Table
create and place in network tree, 1210 build and assign, 1302, 1307
define, 84 Convert
define installation type, 85, 177 connection, 954
define mixed target I/O hardware, 1226 to register, 954
define name, 84, 177 Copies
define number, 84, 177 of a plant, 165
define power supply, 85, 177 Copy
define type, 85, 177 alarm text, 491
define unique target I/O hardware, 1223 analog engineering units, 486
define units of measurement, 85, 177 calendar, 1190
delete, 186 CARE database files, 570
display country code, 189 characteristics, 492
display default file set, 189 control loop, 260
display engineering units, 189 controller, 183
display installation type, 189 controller, 1133
display OS version, 189 default files, 516
display power supply, 189 digital engineering units, 487
display type, 188 exception, 1181
download, 25 folder within device library, 1273
import files, 583 graphic (graphic editor), 1131
input/output information, 221 LON device within device library, 1284
move in network, 1211 plant, 165
neuron ID, 186, 1270 plant, 1132
print summary, 608 project files to backup directory, 571
select default file set, 85, 177 switching table, 275
set country code, 85, 177 switching table to another point, 293
set OS version, 85, 177 switchpoints graphically, 1164
translate, 126 user, 890
Controller configuration copy items
reset, 836 graphics editor, 1080
Controller default file set Count points, 219
display, 189 Country code
modify, 189 change, 189
select, 85, 177 display, 189
Controller download, 191 set, 85, 177
Controller information COV period
device ID, 801 BACnet pulse converter, 451
display, 186 Create
modify, 186 access rights list, 880
Controller input/output information, 221 alarm text, 491
Controller installation type analog engineering units, 486
define, 85, 177 BACnet device, 800
modify, 189 BACnet subnet, 789
Controller name BACnet subsystem, 788
define, 84, 177 buttons, 1103
display, 187, 188 calendar, 1183
Controller number C-bus subsystem, 1204
change, 187 channel, 1205
define, 84, 177 characteristics, 492

1531 EN2Z-0937GE51 R0917


INDEX CARE

control loop, 227 switching table, 276


controller, 176 Data priority
Conversion table, 1302 NVs and datapoints, 1230
custom value element (AI), 1113 Database
default files, 516 restore, 572
digital engineering units, 487 Databinding
dynamic element, 1110 change (graphics editor), 1097
flag, 241 graphics editor, 1074
folder within device library, 1005, 1273 view (graphics editor), 1097
LON object, 1301 Datapoint
LON-bus subsystems, 1209 autobinding, 1239
notification class, 892, 893 color display, 1242
NV manually, 1297 connect to NV, 1239
OLink controller, 708 information, 221
OPS controller, 736 map to NV manually, 1297
OPS template, 732 mapped, 253, 257
Output NV, 1302 Mapping to NV, 1197
project, 139 print description, 612
pseudopoint, 241 remove from terminal, 1259
recipient, 894 Datapoint descriptions
reports, 477, 944 print, 481
standard value element (AI), 1110 Datapoint editor
state element (DI), 1119 configure grid, 306
subsystem controller, 732 displays, 301
subsystem point, 733 grid display, 302
switching table, 272 itemized display from within tree, 302
time program, 525 start, 300
user, 879, 881 tree, 301
value conversion table, 1313 Datapoint information, 221
value element (DI), 1116 Datapoint name
Create graphic display, 365, 375, 387, 396, 408, 418, 429, 436, 442,
basic steps, 1083 448, 459, 462
Create group modify, 365, 375, 387, 396, 408, 418, 429, 436, 442,
graphic library, 1099 448, 459, 462
Create loop object, 1043 Datapoint property description
Create new graphic BACnet object ID, 803
graphics editor, 1083 initial value, 461, 462
Critical alarm type polarity, 378
analog input, 324 relinquish default, 1138
flex point, 341 Date
pseudo analog point, 352 new project, 142
Crossover cable connection Deadband
to BACnet controller, 807, 808, 809 BACnet analog input, 367
Customer name, 141 BACnet analog output, 377
Cut items BACnet analog value, 388
graphics editor, 1080 BACnet pulse converter, 450
Cycle time category, 761 Deadband (or hysteresis) value, 285
Cycle timer, 281 Decommission
Cycle times devices, 1329
target cycle time, 761 Default daily program, 120, 533, 535
Default file set, 182
controller, 85, 177, 189
D plant, 88, 158
Daily program Default files
add point, 531 copy, 516
assign to holiday, 535 create, 516
assign to week day, 120, 533 delete, 516
assign to yearly program, 537 Default point attributes, 199
default, 120, 533, 535 Default properties
delete, 120, 533, 535, 537 LON, 72
edit, 120, 533, 535, 537, 539 Default text editor, 516, 1504
edit point, 532 Define
optimized, 531 BACnet-bus properties, 783, 785, 787
unassign from holiday, 535 controller, 84
unassign from week day, 120, 533 holiday program, 535
unassign from yearly program, 537 LonWorks network architecture, 1199, 1214
Damper/fire example NV type, 1302

EN2Z-0937GE51 R0917 1532


CARE INDEX

plant, 86, 157, 764 BACnet multi-state value, 442


project, 66 BACnet pulse converter, 449
target I/O hardware, 1219, 1222 select for analog input, 323
yearly program, 537 select for analog output, 328
Delay select for digital input, 333
command to digital output point, 279 select for flex point, 340
commands and set minimum times, 269 select for global analog point, 345
examples, 271 select for global digital point, 348
for logical AND (dolumn delay), 288 select for pseudo analog point, 352
for row condition, 280 select for pseudo digital point, 355
operation diagrams, 270 select for pseudo totalizer, 358
types, 270 select for totalizer point, 362
Delete Descriptors (BACnet)
BACnet device, 807 copy, 495
calendar, 1190 create, 495
completed connection, 951 delete, 495
connected control icon, 235 edit, 495
connection, 1257 Design
control loop, 261 BACnet network, 783
controller, 186 network, 1201
daily program, 120, 533, 535, 537 Detach
default files, 516 plant from controller, 182, 183
exception, 1182 Device ID
flag, 239, 247 controller information, 802
folder within device library, 1274 Device library
incomplete connection, 235 copy folder, 1273
items (graphic library, 1126 copy LON device, 1284
LNS project, 1370 create folder, 1005, 1273
LON device from device library, 1286 create LON device, 1275
LON object, 1313 create OPS device, 1280
macro from library, 202 delete folder, 1274
notification class, 892, 899 delete LON device, 1286
NV object, 1313 export, 1286
OPS template, 735 import, 1288
Output NV, 1302 import single LON device, 1290
plant, 174 rename folder, 1273
project, 152 rename LON device, 1284
pseudopoint, 247 Device library
recipient, 894 structure tree, 1005
result delay, 289 Device library
row, 277 structure tree, 1006
segment, 200 Device library
subnet, 807 import EDE file, 1027
subsystem, 807 Device library, 1232
subsystem controller, 735 Device library, 1270
subsystem point, 735 Device library
switching table, 295 structure tree, 1272
switchpoint graphically, 1173 Device template
switchpoint in table, 1179 create from XIF file, 1352
time program, 525 create via plug-in registration, 1352
timer value, 279, 282 Devices
unused software points, 267 commission, 1327
user, 879, 887 decommission, 1329
yearly program, 537 display permanently, 1254
Delete items display temporarily, 1254
graphics editor, 1081 recommission, 1328
Description show connections, 1255
project, 141 Dictionaries
Descriptor graphics editor, 1071
BACnet analog input, 365 Difficulty factor, 142
BACnet analog output, 375 Digital condition rows, 280
BACnet analog value, 387 Digital engineering units, 1473
BACnet binary input, 396 copy, 487
BACnet binary output, 408 create, 487
BACnet binary value, 418 display, 487
BACnet multi-state input, 429 edit, 487
BACnet multi-state output, 436 replace, 487

1533 EN2Z-0937GE51 R0917


INDEX CARE

Digital input datapoint name, 365, 375, 387, 396, 408, 418, 429, 436,
alarm point, 334 442, 448, 459, 462
attributes table, 1479 devices permanently, 1254
board types, 207, 331 devices temporarily, 1254
enable/disable runtime, 334 digital engineering units, 487
hide, 334 digital output point attributes, 335
modify, 206 flex point attributes, 339
point subtype, 332 global digital point attributes, 347
select alarm type, 333 global point attributes, 342
select descriptor, 333 LON object, 1243
select engineering unit, 333 NV, 1243
select operator access level, 333 physical address (global analog), 345
set active state, 334 physical address (global digital), 348
set alarm delay, 334 plant information, 160
set service interval, 333 point type (TAF), 557
set write protect priority, 333 project information, 152
Digital input module choice, 206 pseudo digital point attributes, 354
Digital output pseudo totalizer point attributes, 357
attributes table, 1480 specific switching table for point with multiple tables, 274
board types, 208, 335 technical address for analog input, 322
delay command, 279 technical address for analog output, 327
display attributes, 335 technical address for digital input, 332
enable/disable runtime, 337 technical address for digital output, 336
hide, 337 technical address for global analog point, 345
modify, 207 technical address for global digital point, 348
modify attributes, 335 totalizer point attributes, 360
point subtype, 336 user address, 322, 326, 331, 340, 344, 347, 351, 354,
pulse duration, 337 358, 360
select alarm type, 337 DO_feedback_DI point
select engineering unit, 337 attributes table, 1485
select operator access level, 337 modify, 211
set active state, 337 DO_Feedback_DI Points
set service interval, 337 Upgrade to OS 2.06, 1498
suppress alarm, 337 Documentation
Digital row export graphic files, 587
switching table, 268 overview, 134, 587
Digital switching table, 273 print, 134, 135, 590, 591, 592
DIO assignment print control strategy loops, 599
in local configuration, 1217 print controller summary, 608
in Shared Open LON I/O configuration, 1218 print datapoint description, 612
Disable runtime print LON interface, 627
for digital input, 334 print math. functions, 608
for digital output, 337 print module graphics, 617
for pseudo digital point, 356 print module labels, 620
Discount, 142 print parameter list, 604
Display print plant schematic, 597, 608
alarm text, 491 print point data overview, 612
analog engineering units, 486 print reference list, 624
analog input point attributes, 321 print switching logic tables, 602
analog output point attributes, 326 print table of contents, 597
BACnet analog input point attributes, 364 print table project data sheet, 597
BACnet analog output point attributes, 374 print text lists, 623
BACnet analog value point attributes, 386 print time programs, 615
BACnet binary input point attributes, 395 print to file, 594
BACnet binary output point attributes, 407 print to printer, 594
BACnet binary value point attributes, 417 Domain settings
BACnet controller properties, 757 LON-bus, 1212
BACnet multi-state input point attributes, 428 Download
BACnet multi-state output point attributes, 435 cancel, 1406
BACnet multi-state value point attributes, 441 graphic, 1094
BACnet pulse converter point attributes, 448 LON application, 1404
BACnet reference input point attributes, 458, 461 LON network interface, 1404
characteristics, 492 partial, 1404
connected devices, 1251 to controller, 25
controller information, 186 Download firmware, 1377
datapoint, 1242 Drag and drop
Datapoint editor, 301 configure, 479

EN2Z-0937GE51 R0917 1534


CARE INDEX

Drawing BACnet pulse converter, 449


connecting lines, 948 change format, 312, 317
Drawing pane default (time program), 532
graphics editor, 1076 select for analog input, 323
Duplicate nonglobal, uncommon points, 142 select for analog output, 328
Duplicate user addresses, 181 select for digital input, 333
Dynamic elements select for digital output, 337
graphics editor, 1074 select for flex point, 340
select for global analog point, 345
select for global digital point, 348
E select for pseudo analog point, 351
EBI settings, 1212 select for pseudo totalizer point, 358
EBI Settings, 1357 Engineering units, 663
EDE file analog, 1466
create, 1027 digital, 1473
import, 1027 display, 189
Edit IRC, 1507, 1508
alarm text, 491 modify, 189
analog engineering units, 486 Enter
buttons, 1124 NV name, 1302
calendar, 1188 program ID, 1230
characteristics, 492 project offset, 153
daily program, 120, 533, 535, 537, 539 selfdoc string, 1302
digital engineering units, 487 Enter neuron ID, 1324
elements, 1124 Error messages
Excel 500 network interface manually, 1297 general, 1515
exception, 1181 RACL, 1519
images, 1124 Ethernet settings
notification class, 892, 897 BACnet subnet, 790
point of daily program, 532 gateway address, 790
project password, 68, 143, 144, 146 network address, 790
recipient, 894 Event enrollment alaming
schedule, 1163 controller system status, 905
switchpoints graphically, 1169 plant, 903
texts (graphic editor, 1127 Event enrollment alarming
user, 879, 885 email alaming, 919
Editors, 299 Event handling
Element library notification classes, 891
export, 579 Excel 10 applications, 20, 645
Elements Excel 500 network interface
add to drawing pane, 1087 edit manually, 1297
add to graphic, 1101 Excel 500/600 controllers
create in graphic library, 1110 unassigned points, 563
custom value element for AI, 1113 Excel 80/100 controllers
edit (graphic library), 1124 points, 564
modify properties (graphic editor), 1127 Excel Link Applications, 20
set properties, 1089 Excel Olink controller, 20
show properties (graphic editor), 1127 Excel OPS controller, 20
standard value element for AI, 1110 Excel Web II
state element for DI, 1119 create fast access list, 768
value element for DI, 1116 Excel Web II controller HMI
Eliminate unnecessary row, 277 fast access lists, 767
Elink Excel Web II HTML interface
plant type, 87, 158 fast access lists, 767
Email alarming Exception
event enrollment alaming, 919 copy, 1181
Email alarming, 906 delete, 1182
Enable runtime edit, 1181
for digital input, 334 Exclusive OR columns, 289
for digital output, 337 Exclusive OR table, 290
for pseudo digital point, 356 EXECUTING_STOPPED, 237, 239
Enable web server, 147 Execution speed category
Engineer, 142 see also cycle time category, 761
Engineering unit Exit
BACnet analog input, 365 control strategy, 262
BACnet analog output, 375 switching logic, 298
BACnet analog value, 387 time program, 542

1535 EN2Z-0937GE51 R0917


INDEX CARE

Expand and collapse the tree Flags for NV, 1307


OPS template, 735 Flex point
Export active state, 340
device library, 1286 alarm delay, 341
element library, 579 critical alarm type, 341
graphic (graphic editor, 1133 display attributes, 339
graphic (graphic editor), 1133 hide, 341
graphic files, 587 modify, 211
OLink controller, 724 modify attributes, 339
OPS controller, 747 number of stages, 341
Export zone manager file to E-Vision, 649 operator access level, 340
External Interface File, 1195 select alarm text, 340
Extra text about segment, 221 select descriptor, 340
Extra user address select engineering unit, 340
feedback point, 210, 211 service interval, 341
Folder
copy within device library, 1273
F create within device library, 1005, 1273
FA for Flag analog, 237 delete within device library, 1274
Fahrenheit rename within device library, 1273
use for control icons, 1465 Folder structure
FALCON controller graphics editor, 1069
upgrade, 761 Formats
Fast access list fields in grid, 310
columns configuration, 770 fields in itemized display, 314
create, 768 Freeze columns, 310
filter template, 770, 776 Frequently asked questions, 640
read/write access level, 770 Functional modes
selected points/parameters, 770 loop object, 1043, 1054
Fast access lists
Excel Web II controller HMI, 767 G
Excel Web II HTML interface, 767
FD for Flag digital, 237 GA for Global analog, 237
Feedback point Gateway address
extra user address, 210, 211 Ethernet settings, 790
modify, 210 GD for Global digital, 237
Feedback value Generic LonMark object, 1195
BACnet binary output, 410 Get neuron ID, 1326
BACnet multi-state output, 438 Get online value
Field types NV, 1334
grid, 310 Glob options
itemized display, 315 BACnet controller, 72
File project, 72
print into, 594 XL 500, 72
File management Global analog point
control strategy, 260 attributes table, 1484
switching logic, 293 hide, 345
File structure modify technical address, 345
graphics editor, 1069 point subtype, 345
Filter select descriptor, 345
apply in tree, 473 select engineering unit, 345
use in grid, 476 select operator access level, 345
Filter template set broadcast hysteresis, 346
fast access list, 770 set trend cycle minutes, 346
Filters, 473 set trend hysteresis, 346
Firmware set write protect priority, 345
download into BACnet controller, 833 Global digital point
Firmware download, 1377 attributes table, 1484
Flag display attributes, 347
assign to software point bar, 241, 243 hide, 349
connect to control loop, 249 modify attributes, 347
create, 241 modify technical address, 348
delete, 239, 247 point ID, 348
icon, 102, 241 point role, 348
load, 243 point subtype, 348
modify, 245 select descriptor, 348
unassigned, 240, 243, 245 select engineering unit, 348

EN2Z-0937GE51 R0917 1536


CARE INDEX

select operator access level, 348 background knowledge, 1068


Global input, 237 BACnet, 1068
Global output, 237 basic working techniques, 1079
Global point change databinding, 1097
analog, 237 change graphic properties, 1093
digital, 237 change links, 1097
display attributes, 342 context menu, 1076
modify attributes, 342 copy items, 1080
Global points create graphic (basic steps, 1083
switching logic, 292 create new graphic, 1083
Global references, 188 create text block, 1091
Going offnet, 1323 cut items, 1080
Going onnet, 1321 databinding, 1074
Graphic delete items, 1081
add elements, 1101 download graphic, 1094
add static image elements, 1103 drawing pane, 1076
copy (controller copy), 1133 dynamic elements, 1074
copy (graphic editor), 1131 file and folder structure, 1069
copy (plant copy), 1132 graphic components, 1072
create buttons, 1103 graphic library, 1077, 1098
export, 1133 graphic size definition, 1071
import, 1133 grid lines, 1082
save (graphics editor), 1093 language dictionaries, 1071
Graphic components languages, 1070
graphics editor, 1072 links, 1074
Graphic download logos handling, 1070
graphics editor, 1094 logos selection for start page, 1087
Graphic editor paste items, 1080
copy graphic, 1131 plant graphics, 1086
edit texts, 1127 redo command, 1081
export graphic, 1133 resolution, 1071
import graphic, 1133, 1134 save graphic, 1093
modify properties of button, 1127 scaling factor, 1071
modify properties of element, 1127 selecting items, 1079
show properties of button, 1127 set properties for butttons, 1089
show properties of element, 1127 set properties for elements, 1089
Graphic files show graphic library, 1083
export, 587 snap to grid, 1082
Graphic library start graphic, 1086
add dynamic elements, 1101 static images, 1073
add new static images, 1122 undo command, 1081
add static image elements, 1103 view databinding, 1097
create buttons, 1103 view links, 1097
create custom value element (AI), 1113 workspace environment, 1075
create dynamic elements, 1110 Grid
create group, 1099 change column width, 310
create standard value element (AI), 1110 change engineering units´ format, 312
create state element (DI), 1119 change rows, 310
create value element (DI), 1116 copy attribute values, 463
delete items, 1126 edit point, 309
edit buttons, 1124 field formats, 310
edit elements, 1124 field types, 310
edit images, 1124 freeze columns, 310
graphics editor, 1077, 1083, 1098 frozen columns, 308
rename group, 1099 open itemized display, 318
Graphic properties show columns, 307
change (graphics editor), 1093 sort columns, 310
Graphic size zoom factor, 308
graphics editor, 1071 Grid display
Graphics Datapoint editor, 302
project backup, 1134 Grid lines
project restore, 1134 graphics editor, 1082
Graphics Editor Grid snap
add buttons to drawing pane, 1087 graphics editor, 1082
add elements to drawing pane, 1087 Group Binding, 75, 1341
add images to drawing pane, 1087
adjust graphic, 1082

1537 EN2Z-0937GE51 R0917


INDEX CARE

H Impact report, 585


Import
Hardware point controller files, 583
modify, 203, 205, 206, 207, 209, 210, 211, 212, 214 device library, 1288
Hardware point types, 202 element library, 580
symbols, 202 graphic (graphic editor), 1133
Heartbeat activation graphic (graphic editor), 1133
NV, 1306 single LON device into device library, 1290
Hide Import file for yearly program, 537
analog input, 324 Inactivate holiday program, 535
analog output, 329 Inactive holiday, 115, 526
digital input, 334 Incomplete connection, 235
digital output, 337 Incomplete control loop, 262
flex point, 341 Incremental LonWorks engineering, 1374
global analog point, 345 Information
global digital point, 349 datapoint, 221
pseudo analog point, 352 inputs/outputs of controller, 221
pseudo digital point, 356 physical points, 260, 297
pseudo totalizer point, 359 plant, 218
totalizer point, 362 pseudopoints, 260
High alarm limit segment, 220
set for analog input, 324 Initial value
High limit enable datapoint property description, 461, 462
BACnet analog input, 367 Initialization value
BACnet analog output, 377 analog input, 323
BACnet analog value, 388 analog output, 329
BACnet pulse converter, 450 pseudo analog point, 352
High warning limit pseudo digital point, 356
set for analog input, 324 Input
HMI pin analog, 203
change for user, 879, 890 digital, 206
Holiday program global, 237
assign daily program, 535 Input NV, 327, 332, 336, 351, 355, 362
define, 535 map to BACnet analog input, 365
inactivate, 535 map to BACnet analog output, 375
modify, 535 map to BACnet binary input, 396
status, 536 map to BACnet binary output, 408
unassign daily program, 535 map to BACnet multi-state input, 429
Hot water map to BACnet multi-state output, 436
plant type, 87, 158 map to BACnet pulse converter, 449
Housing structured, 1308
add, 545 Input NV, 1299
remove, 545 Input/output information, 221
Housings Insert
work with, 544 LON module, 546, 548
Hysteresis, 285 segment, 197
Hysteresis value, 214 standard module, 545
XF528 module, 547
Insert mode, 197
I Installation type, 85, 177
I/O terminations change, 189
file, 182, 183 display, 189
required in the controller, 179 Integrate
Icon third party devices, 1338
flag, 102, 241 Integrated modem communication
pseudopoint, 102, 241 translation warning, 191
Icons Integration of additional LON devices, 1216
positioning, 946 Internal datapoint
ID schema, 78 mapped, 253, 257
Identifier Internal parameters of control icons, 229
switching table, 274 Interval limit
Image elements set for pseudo totalizer point, 358
add to graphic, 1103 set for totalizer point, 362
Images Invalid Match, 1305
edit (graphic library), 1124 Invalid Value, 1305
Imagess IP address
add to drawing pane, 1087 allocate to BACnet controller, 789, 790, 808

EN2Z-0937GE51 R0917 1538


CARE INDEX

IP address ranges copy within device library, 1284


BACnet subnet, 790 delete from device library, 1286
IRC engineering units, 1507, 1508 monitoring, 1357
IRC register class names, 1506, 1507 rename within device library, 1284
Itemized display LON device
change engineering units´ format, 317 assign value conversion table, 1282
edit texts, 316 create within device library, 1275
field formats, 314 description, 1236
field types, 315 show as Open LON, 1237
open from within grid, 318 LON device
Itemized display from within grid address, 1324
edit point, 318 LON device
Itemized display from within tree address, 1324
edit point, 314 LON device
Itemized display from witin tree address, 1326
datapoint editor, 302 LON device
address, 1327
LON devices
J add to the network, 1232
Job factor, 142 assign, 1232
Join binding, 1232
switchpoint to other switchpoint, 1177 replace, 1332
reset, 1330
set offline, 1329
L set online, 1329
LAN connection status, 1322
to BACnet controller, 807, 811 test, 1331
Languages wink, 1330
graphics editor, 1070 LON Devices
Limits Logical Assignment, 555, 568
switching table, 269 LON interface
Links print, 627
change (graphics editor), 1097 LON module
graphics editor, 1074 insert, 546
view (graphics editor), 1097 LON network
List of components in segment, 220 scan, 1324, 1327
Literature, 19 LON network interface
LNS controlled, 1212 download, 1404
LNS project LON object
delete, 1370 color display, 1243
LNS properties create, 1301
set defaults, 1351 delete, 1313
LNS settings, 1212 LON Point, 322, 327, 332, 336, 351, 355, 362
Load BACnet analog input, 365
control loop, 227 BACnet analog output, 375
flag, 243 BACnet binary input, 396
pseudopoint, 243 BACnet binary output, 408
segment macro, 201 BACnet multi-state input, 429
switching table, 294 BACnet multi-state output, 436
switching table macro, 296 BACnet pulse converter, 449
Local Direct connection, 77 LON-bus
Local system configuration, 189 configure, 1212
Local X-Over connection, 77 domain settings, 1212
Log files set network interface, 1212
create and upload of controller, 827 LON-bus default system
upload of all controllers, 830 set, 1210
Logical Assignment of LON Devices, 555, 568 LON-bus subsystems
Login create, 1209
comfortable for web interface, 147 LonWorks engineering
Logos incrementally, 1374
graphics editor, 1070 LonWorks network architecture
LON define, 1199, 1214
default network structure, 1202 Local configuration, 1199, 1214
default properties, 72 Shared configuration, 1199, 1214
LON application Loop object
download, 1404 allocate to macro, 1064
LON device control loop engineering steps, 1060

1539 EN2Z-0937GE51 R0917


INDEX CARE

functional modes, 1043, 1054 NV to datapoint, 1197


macro engineering steps, 1064 software points, 1221
macro input types, 1053 types, 1198
macro output types, 1053 Mapping scenarios, 1221
parameter access, 1055 MATH Editor, 287
Loop Object Math functions
create, 1043 print, 608
Loop object settings MATH rows, 287
control loop, 1059 Max. Bindings for NV, 1302
macro, 1063 Max. Present Value
Loop Objects, 1043 BACnet analog input, 367
Low alarm limit BACnet analog output, 377
set for analog input, 324 Maximum number
Low limit enable physical points, 202
BACnet analog input, 367 Maximum plants, 157
BACnet analog output, 377 M-Bus
BACnet analog value, 388 read records, 871
BACnet pulse converter, 450 M-Bus records
Low warning limit Clock-time-interval-based reading, 871
set for analog input, 324 Time-interval-based Reading, 871
Menu items
plant schematic, 194
M switching logic, 264
Macro Metric units, 1465
allocate loop object, 1064 Microcel Automapping Table, 658
delete from library, 202 Migration strategy
load and insert, 201, 295 OLink controller to OLink controller, 726
loop object settings, 1063 OLink controller to OPS controller, 749
save, 200, 295 Min. Present Value
Macro engineering steps BACnet analog input, 367, 398
loop object, 1064 BACnet analog output, 377
Macro input types Miscellaneous Text Editor
loop object, 1053 general, 482
Macro inputs Miscellanous Text Editor
read-write behavior, 1062 BACnet, 494
Macro output types Mixed target I/O hardware
loop object, 1053 define for controller, 1226
Macro outputs Mlodbus support, 840
read-write behavior, 1062 Modbus support
Macrocel Automapping Table, 656 BACnet controller, 840
Manipulating Modify
connecting lines, 949 analog input point, 203
Manual Mapping, 718, 742, 1299 analog input point attributes, 321
BACnet analog input, 365 analog output point, 205
BACnet analog output, 375 analog output point attributes, 326
BACnet binary input, 396 BACnet analog input point attributes, 364
BACnet binary output, 408 BACnet analog output point attributes, 374
BACnet multi-state input, 429 BACnet Analog value point attributes, 386
BACnet multi-state output, 436 BACnet binary input point attributes, 395
BACnet pulse converter, 449 BACnet binary output point attributes, 407
Manual override switch BACnet binary value point attributes, 417
on digital output, 209 BACnet controller properties, 757
Many-to-One Binding, 1302, 1311 BACnet multi-state input point attributes, 428
Many-to-One Mapping, 1199, 1302, 1311 BACnet multi-state output point attributes, 435
Map BACnet multi-state value point attributes, 441
between C-Bus points and E-Bus points, 649 BACnet pulse converter point attributes, 448
CARE datapoints to OLink points, 714 BACnet reference input point attributes, 458, 461
CARE datapoints to OPS points, 740 control loop, 228
datapoint to NV manually, 1297 datapoint name, 365, 375, 387, 396, 408, 418, 429, 436,
NV to datapoint manually, 1297 442, 448, 459, 462
OLink points to CARE datapoints, 714 digital input point, 206
OPS points to CARE datapoints, 740 digital output point, 207
Mapped internal datapoint, 253 digital output point attributes, 335
Mapped parameter, 250 DO_feedback_DI point, 211
Mapped point plant, 648 feedback point, 210
Mapping, 1195, 1239 flag, 245
datapoint to NV, 1197 flex point, 211

EN2Z-0937GE51 R0917 1540


CARE INDEX

flex point attributes, 339 Multi-state value point


global digital point attributes, 347 BACnet object type, 442
global point attributes, 342
hardware point, 203, 205, 206, 207, 209, 210, 211, 212,
214
N
holiday program, 535 Name
module type, 547, 548, 549 controller, 84, 177
multistage point, 214 plant, 87, 158, 764
Neuron ID, 548 project, 141
project information, 152 Name a new control sequence, 227
properties of button (graphic editor, 1127 Naming convention
properties of element (graphic editor, 1127 backup project, 572
pseudo digital point attributes, 354 Naming terminology for OPS points, 740
pseudo totalizer point attributes, 357 Navigate in tree, 319
pseudo user address, 246 NCI
pseudopoint, 245 set value, 1336
pulse_2 point, 212 Network
resulting command, 278 configure, 1201
technical address of global analog point, 345 create and place controller, 1210
technical address of global digital point, 348 design, 1201
time program, 525 move BACnet device, 806
totalizer point, 209 move controller, 1211
totalizer point attributes, 360 set interface channel, 1209
user address, 322, 326, 340, 344, 347, 351, 354, 358, Network engineering
360 BACnett, 754
XFM parameter, 259 Network interface, 1195
yearly program, 537 change, 1196
Module Network interface channel
move, 550 set, 1209
remove, 554 Network interface, set, 1212
Module graphics Network structure
print, 617 default, 781, 1202
Module labels Network variables, 1195
print, 620 Neuron ID
Module type controller, 186, 1270
modify, 547, 548, 549 set/modify, 548
Modules Neuron IDs, 1214
terminal assignment function, 545 New project
Monitoring Create, 139
LON device, 1357 define, 66
Move Niagara
module, 550 project export, 155
point (TAF), 555 NIDEC file
Multiple Bindings, 75, 1341 project export, 155
Multiple inputs NO/NC
connect control icons to each other, 233 attribute, 1492
Multiple row conditions, 281 NO/NC
Multiple tables new mechanism, 1492
switching logic, 273 old mechanism, 1492
Multistage point Processing, 1492
attributes table, 1487 Node object, 1195
modify, 214 Normally Open/Normally Closed
Multistage points attribute, 1492
Upgrade to OS 2.06, 1498 new mechanism, 1492
Multi-state input point old mechanism, 1492
BACnet object type, 429 processing, 1492
Multi-state input point Notification
BACnet object type, 429 assign to BACnet analog input, 366
Multi-state output point assign to BACnet analog output, 376
BACnet object type, 436 assign to BACnet analog value, 387
Multi-state output point assign to BACnet binary input, 397
BACnet object type, 436 assign to BACnet binary output, 409
Multi-state output point assign to BACnet binary value, 418
BACnet object type, 436 assign to BACnet multi-state input, 430
Multi-state properties assign to BACnet multi-state output, 437
BACnet multi-state input, 431, 441 assign to BACnet multi-state value, 442
BACnet multi-state value, 443 assign to BACnet pulse converter, 449

1541 EN2Z-0937GE51 R0917


INDEX CARE

Notification class NV type


create, 892, 893 define, 1302
delete, 892, 899 NV-Booster, 1302, 1311
edit, 892, 897 NVI, 322, 327, 332, 336, 351, 355, 362
Notification Class Manager, 891 NV-Input, 322, 327, 332, 336, 351, 355, 362, 1299
start, 892 NVO, 322, 327, 332, 336, 351, 355, 362
Notification class object type NV-Output, 322, 327, 332, 336, 351, 355, 362, 1299
To-Fault, 891, 895 NVs
To-Normal, 891, 895 arrange, 1312
To-Offnormal, 891, 895 binding types, 1244
Notification class object types, 891, 895 NVs and datapoints
Notification classes data priority, 1230
event handling, 891 NV-Type, 1299
Notifiy type
BACnet analog input, 366
BACnet analog output, 377
O
BACnet analog value, 388 Off and On
BACnet binary input, 397 switching tables, 277
BACnet binary value, 419 OLink, 703
BACnet multi-state input, 430 OLink controller
BACnet multi-state output, 437 create, 708
BACnet multi-state value, 443 engineering process, 705
BACnet pulse converter, 450 migration strategy, 726, 749
Notify type OLink points
BACnet binary output, 409 automatic mapping, 714, 717
Nstate subtype map to CARE datapoints, 714
switching table, 292 unmap from CARE datapoints, 719
Number of MS/P devices, 80 OLink template, 703
Number of stages One-to-One Mapping, 1199
flex point, 341 Onnet tuning, 1321
NV Open
Binding, 1197 project, 148, 306, 307, 473, 479
Mapping to datapoint, 1197 switching table, 276
NV Open LON mode
mapping to software point, 1221 LON device, 1237
NV Operator access level
connect to datapoint, 1239 select for analog input, 323
NV select for analog output, 328
connect to NV, 1239 select for digital input, 333
NV select for digital output, 337
autobinding, 1239 select for flex point, 340
NV select for global analog point, 345
color display, 1243 select for global digital point, 348
NV select for pseudo analog point, 352
remove from terminal, 1259 select for pseudo digital point, 356
NV select for pseudo totalizer, 358
map to datapoint manually, 1297 select for totalizer point, 362
NV OPS controller
create manually, 1297 create, 736
NV engineering process, 731
max. bindings, 1302 general, 729
NV migration strategy, 749
heartbeat activation, 1306 prerequisites, 729
NV technical literature, 729
flags, 1307 template editor, 732
NV working on within Datapoint Editor, 738
get online value, 1334 OPS device
NV create within device library, 1280
set offline, 1336 OPS interface, 730
NV list display OPS point
configure, 1280 naming terminology, 740
NV name OPS points
enter, 1302 automatic mapping, 741
NV object map to CARE datapoints, 740
delete, 1313 unmap from CARE datapoints, 742
NV Poll Interval, 1212 OPS template, 730
NV Poll Interval, 1357 create, 732

EN2Z-0937GE51 R0917 1542


CARE INDEX

delete, 735 PID controllers per system., 262


expand and collapse the tree, 735 PJT, 569
save, 735 Place
OPS template editor, 732 control icon, 228
Optimization Plant
BACnet analog output, 388 attach replicated plants, 180
BACnet binary value, 428 attach to a controller, 179
BACnet multi-state value, 443 CARE concept, 21
Optimize daily program, 531 change information, 160
OR columns, 289 connect control icon to, 229
Order number, 142 copy, 165
OS 1.1/1.1.30 support, 1509 copy graphic, 1132
OS version define, 86, 157, 764
controller, 85, 177 define name, 87, 158, 764
plant, 87, 158 define type, 87, 158
OS XLIRC support, 1504 delete, 174
Output detach from a controller, 182, 183
analog, 205 display information, 160
digital, 207 display user addresses, 219
global, 237 event enrollment alaming, 903
Output NV, 327, 332, 336, 351, 355, 362 information, 218
structured, 1308 information displays, 259, 297
Output NV, 1299 remove from a project, 174
Overview replicate, 165
control strategy, 98, 223 schematic, 21, 24
plant schematic, 193 select default file set, 88, 158
switching logic, 106, 263 select target I/O hardware, 88, 159
set OS version, 87, 158
set units of measurement, 88, 159, 765
P translation, 190
Parameter Plant default file set, 88, 158
mapped, 250 Plant graphics
unmapped, 258 graphics editor, 1086
Parameter access Plant information displays, 259, 297
control loop, 1055, 1056 Plant name
control macro, 1055, 1062 change, 649
loop bject, 1055 define, 87, 158, 764
Parameter list Plant OS version, 87, 158
print, 604 Plant replication, 180
Parameter mismatches, 583 Plant schematic
Parameters close, 222
upload, 1333 definition, 193
Partial download display user addresses, 196
LON application, 1404 exit, 222
Particular IP address of controller menu items, 194
assign, 816, 818 overview, 193
Password print, 597, 608
Change, 148 redisplay, 222
change for user, 879, 889 redraw, 222
Paste items switching logic, 266
graphics editor, 1080 window, 193
Physical address Plant type
global analog point, 345 air conditioning, 87, 158
global digital point, 348 chilled water, 87, 158
Physical point define, 87, 158
information, 260, 297 Elink, 87, 158
Physical point bar hot water, 87, 158
control strategy, 226 Plug-in
switching logic, 266 registration, 1352
Physical point information, 260, 297 Point
Physical point types, 202 abbreviations in grid, 309
symbols, 202 assign (TAF), 555
Physical points, 202 attributes tables, 1475
datapoint editor, 299 change type (TAF), 557
maximum number, 202 display type (TAF), 557
Physical user addresses edit in grid display, 309
view, 297 edit in itemized display, 314

1543 EN2Z-0937GE51 R0917


INDEX CARE

edit in itemized display from within grid, 318 plant schematic, 597, 608
move (TAF), 555 point data overview, 612
Point address, 300 print overview, 134, 135, 590, 591, 592, 593, 594, 595
Point attributes, 199, 663 printer setup, 592
Point attributes tables, 1475 project datasheet, 597
Point count, 219 reference list, 624
Point data overview select possibilities, 595
print, 612 settings CAREDOC.INI file, 632
Point filter switching logic tables, 602
define for fast access list, 770 table of contents, 597
Point ID text lists, 623
analog input, 322 time programs, 615
analog output, 327 to file, 594
global digital point, 348 to printer, 594
pseudo digital point, 355 Printer
Point role setup, 592
analog input, 322 Program ID
analog output, 327 enter, 1230
BACnet analog input, 367 Program ID offset, 147
BACnet analog output, 377 Project
BACnet analog value, 388 backup, 571
BACnet binary input, 397 backup (graphics handling), 1134
BACnet binary output, 409 client, 142
BACnet binary value, 419 date, 142
BACnet multi-state input, 430 definition, 139
BACnet multi-state output, 438 delete, 152
BACnet multi-state value, 443 description, 141
BACnet pulse converter, 450 discount, 142
global digital point, 348 display information, 152
Point subtype engineer, 142
analog input, 322 export as NIDEX file, 155
digital input, 332 export to Niagara, 155
digital output, 336 global options, 72
global analog point, 345 job factor, 142
global digital point, 348 modify information, 152
totalizier point, 361 name, 141
Point type non-unique user addresses, 142
abbreviations, 639 open, 148, 306, 307, 473, 479
Point types order number, 142
hardware, 202 reference number, 141
physical, 202, 299 rename, 152
pseudo, 299 restore, 576
Points restore (graphics handling), 1134
Excel 80/100 controllers, 564 retrieve copy, 576
without graphic, 217 subdirectory, 143
Polarity unique user addresses, 142
BACnet binary input point, 398 units of measurement, 143
BACnet binary output point, 410 Project datasheet
datapoint property description, 378 print, 597
Port, 1395 Project information
Port settings, 1395 display, 152
Positioning modify, 152
icons, 946 Project offset, 153
Power supply, 85, 177 Property
change, 189 BACnet reference output point, 448
display, 189 Pseudo analog point
Print attributes table, 1478
control strategy loops, 599 critical alarm type, 352
controller summary, 608 hide, 352
datapoint description, 612 initialization value, 352
datapoint descriptions, 481 select alarm text, 352
LON interface, 627 select descriptort, 352
math functions, 608 select engineering unit, 351
module graphics, 617 select operator access level, 352
module labels, 620 set trend hysteresis, 353
options, 595 set write protect priority, 352
parameter list, 604 suppress alarm, 352

EN2Z-0937GE51 R0917 1544


CARE INDEX

Pseudo digital point R


attributes table, 1481
display attributes, 354 RACL Editor
enable/disable runtime, 356 General, 19
initialization value, 356 Overview, 19
modify attributes, 354 RACL parameter imports, 583
point ID, 355 Read access for web interface
select alarm point, 356 determine for BACnet analog input, 366
select alarm text, 355 determine for BACnet analog output, 376
select descriptor, 355 determine for BACnet analog value, 387
select operator access level, 356 determine for BACnet binary input, 396
set active state, 356 determine for BACnet binary output, 409
set service interval, 356 determine for BACnet binary value, 418
set write protect priority, 356 determine for BACnet multi-state input, 430
suppress alarm, 356 determine for BACnet multi-state output, 437, 461, 462
Pseudo digital point output determine for BACnet multi-state value, 442
hide, 356 determine for BACnet pulse converter, 449
Pseudo totalizer point Read/write access level
attributes table, 1483 fast access list, 770
display attributes, 357 Read-write behavior
hide, 359 macro inputs, 1062
modify attributes, 357 macro outputs, 1062
select descriptor, 358 Recall switching table, 274
select engineering unit, 358 Recipient
select operator access level, 358 create, 894
set interval limit, 358 delete, 894
set scaling factor, 358 edit, 894
set write protect priority, 358 Recommission
suppress alarm, 359 devices, 1328
Pseudopoint Redisplay
analog, 237 plant schematic, 222
assign to software point bar, 241, 243 Redisplay
connect to control loop, 249 saved switching table, 294
create, 241 Redo command
delete, 247 graphics editor, 1081
digital, 237 Redraw
flag analog, 237 plant schematic, 222
global analog, 237 Reference datapoint
gobal digital, 237 general, 458
icon, 102, 241 Reference input point
information, 260 BACnet object type, 459, 462
load, 243 Reference list
map to XFM internal datapoint, 253 print, 624
map to XFM parameter, 250 Reference number, 141
modify, 245 Reference points, 492
totalizer, 237 References
unassigned, 240, 243, 245 show of calendar, 1190
unmap from XFM parameter, 258 Register
Pseudopoint information, 260 convert, 954
Pseudopoints Register class names
datapoint editor, 299 IRC, 1506, 1507
in switching logic, 292 Registration
specials, 239 plug-in, 1352
PT3000, 203 Reliability
Pulse 2 point point BACnet analog output, 375
attributes table, 1486 BACnet binary output, 408
Pulse converter BACnet datapoints, 1201
alarm delay normal, 450 BACnet multi-state output, 436
suppress alarm, 450 Relinqish default, 1138
Pulse converter point BACnet analog output, 377, 388, 389, 419, 443
BACnet object type, 449 Relinquish default
Pulse duration BACnet binary output point, 414
digital output, 337 datapoint property description, 1138
Pulse_2 point Relinquish default
modify, 212 BACnet binary value, 419
Remote BACnet controller, 818
Remote devices

1545 EN2Z-0937GE51 R0917


INDEX CARE

read status flags, 1033 switching table as macro, 295


Remotely connect switching tables in a macro library, 295
to particular BACnet controller, 816 Scaling factor
Remove graphics editor, 1071
binding, 1257 set for pseudo totalizer point, 358
datapoint from terminal, 1259 set for totalizer point, 362
housing, 545 Scan
module, 554 baudrate, 1406
NV from terminal, 1259 ports, 1406
plant from a project, 174 Scan LON network, 1324, 1327
Rename Schedule
folder within device library, 1273 edit, 1163
LON device within device library, 1284 Schedules, 1135
project, 152 view, 1140
time program, 525 Schematic
Rename group definition, 89, 193
graphic library, 1099 of a plant, 21, 24
Rename points window, 193
search string conventions, 469 Search
Replace flag via keyboard, 245
alarm text, 491 pseudopoint via keyboard, 245
analog engineering units, 486 Search and replace attribute settings, 465
CARE database files, 572 Search string conventions, 469
characteristics, 492 Segment
digital engineering units, 487 add, 197
LON devices, 1332 delete, 200, 951
variable in switching table, 287 extra text, 221
Replicate information, 220
plant, 165 insert, 197
Report by Exception, 1357 list of components, 220
Reports load as macro and insert, 201
create, 477, 944 move, 950
Reset save as macro, 200
BACnet controller configuration, 836 split, 950
LON devices, 1330 Select
Resolution control loop, 227
graphics editor, 1071 project, 148
Restore time period, 279, 280
CARE database, 572 time program, 525
project, 576 Selected points/parameters
project (graphics handling), 1134 fast access list, 770
switching table, 295 Selecting items
Restrictions graphics editor, 1079
time programs, 522 Selfdoc string
Result delay enter, 1302
delete, 289 Send On Delta Resolution
Result row set for analog inputs on panel bus, 800
switching table, 267, 277 Sensor offset
Retrieve BACnet analog input, 367
copy of project, 576 set, 324
Router Service interval
connect channels via…, 1206 set for digital input, 333
Routing connecting lines, 232, 949 set for digital output, 337
Row set for flex point, 341
delete, 277 set for pseudo digital point, 356
Rows Service type, 1256
change in grid, 310 BACnet datapoints, 375, 408, 436, 1201
RS 232 connection, 77 Set
baudrate, 1395
C-bus default, 1210
S default channel, 1208
Safety value default LNS properties, 1351
BACnet analog input, 367 LON devices offline, 1329
Save LON devices online, 1329
macro, 200 LON-bus default system, 1210
OPS template, 735 NCI value, 1336
switching table, 293 network interface channel, 1209

EN2Z-0937GE51 R0917 1546


CARE INDEX

NV offline, 1336 Step 3A Plant-Controller Matchup (XLink), 667


SCPT value, 1336 Step 3B User Address-Point Manual Mapping (XLink), 668
UCPT value, 1336 Step 3C C-NAP to Eng Unit Conversion Mapping (XLink),
Settings 669
BACnet controller, 813 Step 3D Configurator Cross-Check (XLink), 669
download into BACnet controller, 819 Step 4 Subsystem Site Backup (XLink), 669
Setup Step 5 Excel Link CPU and SSI Download, 670
BACnet controller, 807 Step 6 Subsystem Controller Download (XLink), 671
Shared / Open LON system configuration, 189 Stop
Shared/Open LON configuration, 1216 application in BACnet controller, 832
Show Structured input NV, 1308
LON device as Open LON, 1237 Structured output NV, 1308
properties of button (graphic editor, 1127 Subdirectory, 143
properties of element (graphic editor, 1127 Subsequent row
SHUTDOWN, 237, 239 switching table, 268
Software point Subsystem controller
map to XFM parameter, 250 create, 732
map to XFM internal datapoint, 253 delete, 735
unmap from XFM parameter, 258 Subsystem point
mapping to NV, 1221 create, 733
Software point bar delete, 735
control strategy, 226 Suppress alarm
Sort columns, 310 analog input, 324
Standard mode analog output, 329
LON device, 1237 BACnet analog input, 366
Standard module BACnet analog output, 377
insert, 545 BACnet analog value, 388
Start BACnet binary input, 397
application in BACnet controller, 832 BACnet binary output, 409
new switching table, 295 BACnet binary value, 419
notification class manager, 892 BACnet multi-state input, 430
user access manager, 879 BACnet multi-state output, 437
Start alarm time, 894 BACnet multi-state value, 443
Start graphic digital output, 337
graphics editor, 1086 pseudo analog point, 352
logos selection, 1087 pseudo digital point, 356
STARTUP, 237, 239 pseudo totalizer point, 359
State texts pulse converter, 450
BACnet multi-state input, 429 totalizer point, 362
BACnet multi-state output, 436 Suppress"Not Generated" parameters, 637
BACnet multi-state value point, 442 Switch is changeover, 208
State texts (BACnet) Switch is normally closed, 207
copy, 495 Switch is normally open, 207, 208
create, 495 Switching logic
delete, 495 CARE concept, 24
edit, 495 close, 298
Static images close switching table, 276
graphics editor, 1073 copy switching table, 275
Status create switching table, 272
LON devices, 1322 exit, 298
Status flags file management, 293
read from remote devices, 1033 global points, 292
Step 1A Build the Excel Link Plant (XLink), 654 interaction with control strategy, 272
Step 1B Build the Subsystem Plants (XLink), 655 load macro, 296
Step 1C Replicate the Subsystem Plants (XLink), 662 menu items, 264
Step 1D Attach the Plants to the Excel Link Controller, 662 multiple tables for a point, 273
Step 1E Edit Excel Link Point Char, 663 of plant schematic, 266
Step 1F Edit Excel Link Points, 663 Off and On tables, 277
Step 1G Set Up Time Prog in Excel Link Controller, 663 open switching table, 276
Step 1H Translate Excel Link Controller, 664 overview, 106, 263
Step 1I Print Documentation (XLink), 664 physical point bar, 266
Step 1J Back Up Excel Link Project, 664 pseudopoints, 292
Step 2 Subsystem Controller Configuration (XLink), 664 recall switching table, 274
Step 2A Subsystem Interface Setup (XLink), 664 standard functions, 266
Step 2B MicroCel/MacroCel Controller Setup (XLink), 666 table, 267
Step 2C W7600/W7620 Controller Setup (XLink), 666 window, 263
Step 3 XLink Configurator/Mapper, 667 Switching logic tables

1547 EN2Z-0937GE51 R0917


INDEX CARE

print, 602 T
Switching table, 267
analog condition rows, 283 Table of contents
analog row, 268 print, 597
change +XOR table, 291 TAF, 543
close, 276 Target cycle time
command changes, 278 cycle times, 761
comparison type, 283 Target I/O hardware
comparison value, 284 change, 1219
copy, 275 define, 1219
copy to another point, 293 define for plant, 88, 159
create, 272 Technical address
cycle timer, 281 display for analog input, 322
damper/fire example, 276 display for analog output, 327
deadband (or hysteresis) value, 285 display for digital input, 332
delay command, 279 display for digital output, 336
delay for logical AND, 288 display for global analog point, 345
delay for row condition, 280 display for global digital point, 348
delay types, 270 display for totalizer point, 361
delete, 295 modify for global analog point, 345
delete result delay, 289 modify for global digital point, 348
delete timer value, 282 Template configuration
delete timer value, 279 define for fast access list, 776
digital, 273 Template database, 1351
digital condition rows, 280 Template editor
digital row, 268 OPS, 732
erase parameters, 275 Terminal assignment, 543
exclusive OR, 290 Terminal assignment function
exclusive OR columns, 289 add housing, 545
identifier, 274 assign point to terminal, 555
limits, 269 change point type, 557
load, 294 context menu, 544
MATH rows, 287 display point type, 557
multiple row conditions, 281 insert LON module, 546
Nstate subtype, 292 insert standard module, 545
Off and ON, 277 insert XF528 module, 547
open, 276 modify module type, 547, 548, 549
OR columns, 289 move module, 550
recall, 274 move point, 555
redisplay, 294 remove housing, 545
replace variable, 287 remove module, 554
restore, 295 set/modify neuron ID, 548
result row, 267, 277 work with housings, 544
save, 293 work with modules, 545
save as macro, 295 Test
select time period, 279, 280 LON devices, 1331
start, 295 Text block
subsequent row, 268 create (graphics editor), 1091
time delays, 269 Text lists
true or false changes, 282, 286 print, 623
Switching tables Texts
translation warning, 191 edit (graphic editor, 1127
Switchpoint edit in itemized display, 316
change start/end time, 1169, 1171 Third party devices
change value, 1172 integrate, 1338
delete graphically, 1173 Three-position output signal, 205
delete in table, 1179 Time delays
join to other switchpoint, 1177 switching table, 269
Switchpoints Time period
copy graphically, 1164 select, 279, 280
edit graphically, 1169 Time program
Synchronize add, 525
address table entries allocation, 75, 1341 assign user address, 116, 527
System configuration copy daily program, 529
Local, 189 create, 525
Shared / Open LON, 189 define holiday program, 535
define yearly program, 537

EN2Z-0937GE51 R0917 1548


CARE INDEX

delete, 525 BACnet pulse converter, 450


delete yearly program, 537 Translate, 126, 190
engineering unit, 532 controller, 126
exit, 542 Tree
import Device library, 1005, 1006, 1272
file for yearly program, 537 Tree
inactivate, 535 configure drag and drop, 465
inactive holiday, 115, 526 copy attribute values, 464
modify, 525 datapoint editor, 301
modify holiday program, 535 drag and drop attribute values, 464
modify yearly program, 537 navigate, 319
rename, 525 Trend cycle minutes
select, 525 set for analog input, 325
unassign user address, 116, 527 set for global analog point, 346
user address reference list, 528 Trend hysteresis
Time program function set for analog input, 325
initiate, 523 set for analog output, 329
Time programs set for global analog point, 346
CARE concept, 24 set for pseudo analog point, 353
flowchart, 522 True or false changes, 282, 286
overview, 113, 521 Tuning
point restriction, 522 onnet, 1321
print, 615 Type
Time schedules for Excel 10 controllers, 650 controller, 85, 177, 187, 188
Time to close plant, 87, 158
set for analog output, 329
Time to open
set for analog output, 329
U
Time-interval-based Reading, 871 UCPT
Timer value set value, 1336
delete, 279, 282 Unassign
To-Fault daily program from holiday, 535
notification class object type, 891, 895 daily program from week day, 120, 533
transition, 895 daily program from yearly program, 537
To-Normal user address from time program, 116, 527
notification class object type, 891, 895 Unassigned flag, 240, 243, 245
transition, 895 Unassigned points
To-Offnormal Excel 500/600 controllers, 563
notification class object type, 891, 895 Unassigned pseudopoint, 240, 243, 245
transition, 895 Undo command
Totalizer point graphics editor, 1081
attributes table, 1482 Unique target I/O hardware
display attributes, 360 define for controller, 1223
hide, 362 Units of measurement
modify, 209 define for controller, 85, 177
modify attributes, 360 define for plant, 88, 159, 765
select descriptor, 362 define for project, 143
select operator access level, 362 Units of Measurement, 88, 159
set interval limit, 362 Unmap
set scaling factor, 362 CARE datapoints from OLink points, 719
set write protect priority, 362 CARE datapoints from OPS points, 742
subtype, 361 Unmapped parameter, 258
suppress alarm, 362 Unused software points, 181, 267
Transition in control strategy, 226
To-Fault, 895 Up- or download
To-Normal, 895 cancel, 1406
To-Offnormal, 895 Update controller files in the CARE database, 583
Transition event Upgrade
BACnet analog input, 367 FALCON controller, 761
BACnet analog output, 377 Upgrade to OS 2.06
BACnet analog value, 388 DO_Feedback_DI Points restriction, 1498
BACnet binary input, 397 Multistage points restriction, 1498
BACnet binary output, 409 Upload
BACnet binary value, 419 cancel, 1406
BACnet multi-state input, 430 log files of all controllers, 830
BACnet multi-state output, 437 log files of controller, 827
BACnet multi-state value, 443 parameters, 1333

1549 EN2Z-0937GE51 R0917


INDEX CARE

Upload LON device, 1324 W7620 WSHP Automapping Table, 661


USB connection Web interface
to BACnet controller, 808 enable comfortable login, 147
USB connection, 77 Webserver
Use Bound Updates, 1357 enable, 147
User Weekly program
change HMI pin, 879, 890 assign daily program, 120, 533
change password, 879, 889 unassign daily program, 120, 533
copy, 890 Windows
create, 879, 881 arrange, 319
delete, 879 Wink
detete, 887 LON devices, 1330
edit, 879, 885 WMF, 587
User access manager, 877, 1191 Working techniques
start, 879 graphics editor, 1079
User address Workspace environment
change, 215 graphics editor, 1075
datapoint editor, 300 Write protect priority
display, 322, 326, 331, 340, 344, 347, 351, 354, 358, select for global analog point, 345
360 set for analog input, 323
display in plant schematic, 196 set for analog output, 329
modify, 322, 326, 331, 340, 344, 347, 351, 354, 358, set for digital input, 333
360 set for pseudo analog point, 352
reference list, 528 set for pseudo digital point, 356
User address of the same name set for pseudo totalizer point, 358
map to XFM internal datapoint, 257 set for totalizer point, 362
User address reference list, 528
User address search templates editor, 518
User addresses
X
check non-unique names, 1511 XBS, 142
display for plant, 219 XF528 module
unique or non-unique for project, 142 insert, 547
User addresses of the same name XFM
create, 257 mapped internal datapoint, 253
User profile, 877, 1191 mapped parameter, 250
modify parameter, 259
V unmap parameter, 258
XIF file, 1195
VA for Pseudo analog, 237 create device template from, 1352
Value conversion table XL 500
assign to LON device, 1282 global options, 72
build, 1313 XOR, 291
build and assign, 1307 XW567 connection cable, 125, 1387
VAV 2 applications, 645
VD for Pseudo digital, 237
Verify control loop operation, 262
Y
View Yearly program
calendars, 1183 assign daily program, 537
physical user addresses, 297 define, 537
schedules, 1140 delete, 537
VT for Pseudo totalizer, 237 import file, 537
modify, 537
W unassign daily program, 537
Yes, if group, 75, 1341
W7620 Variable Air Volume (VAV) Automapping, 660

EN2Z-0937GE51 R0917 1550


EN2Z-0937GE51 R0518
Manufactured for and on behalf of the Environmental and Energy Solutions Division of Honeywell Technologies Sàrl, Rolle, Z.A. La Pièce 16, Switzerland by its Authorized Representative:

CentraLine
Honeywell GmbH
Böblinger Strasse 17
71101 Schönaich, Germany
Phone +49 (0) 7031 637 845
Fax +49 (0) 7031 637 740
[email protected] Subject to change without notice
www.centraline.com EN2Z-0937GE51 R0518

You might also like