Brochure Relay
Brochure Relay
Manufactured by:
Spain
Protection, Control and
Measurement
Complete Protection Solutions
pazifik
power
www.ppi.ph
INGEPAC EF MD GENERAL DESCRIPTION
Relay Insulation and Electromagnetic Test
Dielectric strength IEC 60255-5
Protection and Control Insulation resistance IEC 60255-5
The family of numerical technology protection, control and measurement Impulse voltage IEC 60255-5
equipment has been designed to provide comprehensive protection Earth continuity IEC 61131-2
and automation solutions for different elements in an electrical grid. Leakage current IEC 60990
It offers a wide range of models with different functional features, 1 MHz damped wave immunity test IEC 60255-22-1
making it possible to adapt to the needs and costs of each application. Damped oscillatory wave immunity test IEC 61000-4-12
All of the equipment has been designed to work uninterruptedly in Electrostatic discharge immunity test IEC 61000-4-2
electrical substations and the most demanding environments, in Electrical fast transients immunity test IEC 61000-4-4
compliance with the most stringent standards and requirements in the Surge pulses immunity test IEC 61000-4-5
field of industrial electronics. Immunity to interruptions, dips & variations in DC IEC 61000-4-29/
power supply IEC 60255-11
The equipment complies with the most renowned communications Ripple immunity in DC power supply IEC 61000-4-17
standards for integration into substation automation systems. It Harmonics IEC 61000-4-7
also offers comprehensive realtime information and an events log on
Immunity to industrial frequencies IEC 60255-22-7
controlled / protected elements using the software tools:
Safety in equipment electrically connected to
IEC 62151
communications network
The INGEPAC EF MD family is composed of multifunctional protection
Surge Withstand Capability (SWC) IEEE C37.90-3
and control devices for high and medium voltage equipment. Its design
is compliant with all the requirements of standards in the electrical Electromagnetic radiation IEEE C37.90.2
sector, including IEC 61850. Besides having powerful logging features, Electromagetic discharge test IEEE C37.90-3
it provides comprehensive, detailed information, making it possible to IEC 60255-25
Radioelectrical emission measurement
monitor and analyse events, these being fundamental elements in an EN 55022/55011
electrical grid’s continuous improvement process. ENV 50204
Immunity to radiofrequency radiated fields
IEC 61000-4-3
Immunity to radiofrequency induced signals IEC 61000-4-6
Main features
Immunity to 50Hz magnetic fields IEC 61000-4-8
• Single protection and control platform
Immunity to pulsing magnetic fields IEC 61000-4-9
• IEC 61850 native platform Immunity to damped scillatory magnetic fields IEC 61000-4-10
• Extensive dynamic range in current inputs, enabling
connection to 1A and 5A current transformers Climatic
• Application software specifically designed for simple and Cold low temperature test IEC 60068-2-1
user-friendly access to the equipment Dry heat test IEC 60068-2-2
• Graphical and textual logic programming based on IEC Humid heat continuous test IEC 60068-2-78
61131-3 Cyclical humid heat IEC 60068-2-30
• Different hardware configuration variants allowing you to Thermal shock IEC 60068-2-14
define suitable equipment for the application External protection level IEC 60529
• Complementary functions for responding to primary element
failures (switch failure and winding supervision) Mechanical
Vibration test IEC 60255-21-1
• Chronological logging of events, failure reports and
oscillographs facilitates the complete analysis of events Shock and bump test IEC 60255-21-2
Seismic tests IEC 60255-21-3
• Measurement log for current (demand), voltage and powers,
allowing you to obtain load curves
• 6 setting groups, making it possible to instantaneously re-
program the equipment when the grid’s condition are re-
configured
• Equipment synchronisation from a global reference through
the communications protocol or the demodulated IRIG-B
input protocol
• Switch monitoring
• Measurement: Current, voltage, power, power factor,
frequency, sequence current, demand maximeter,
harmonics, THD
• Bi-directional active and reactive energy counters
• Operation counters: triggers, operation openings, energy
cut off by the switch and automatic reclosure
• Local interface with graphic display, LEDs and programmable
buttons
• Front panel with 4.9” programmable LEDs and 1 fixed two- • Selectable rear port connectivity
colour harware status LED, numerical keypad and menu –– Up to 6 serial communications
keys
–– Up to 2 Ethernet communications
• Digital inputs for control functions or automatic functions
• Serial ports in glass optic fibre, plastic optic fibre,
• Digital outputs for control and signalling RS232 or RS485
• Ethernet communication and USB on the front • Ethernet ports in glass fibre or RJ45
• Up to 6 serial and 2 rear Ethernet ports • PRP redundancy
• Automatic recloser, increasing the service’s availability • Different models for auxiliary voltages most commonly
without user intervention found in electrical installations
• Automatic reconnection after repositioning the network • IP54 Lid
frequency with user intervention
• Remote protection
• Protection functions for any earthing
• 9 programmable graphic pages in the local interface.
• IEC 61850 communication and serial protocols
• Web Server
• RIO module sensing (remote input/output) Applications
• Redundant networks applicable • Main control and protection of distribution lines
equipped with directional features, for networks with
Options earthing with or without impedance, compensated
neutral and isolated neutral.
• Two housing types 1/2 x 19” 5U rack and 19”, 4U rack,
which can contain the following modules in different • Transmission line backup protection with the option of
configurations: incorporating remote protection diagrams for units 67
and 46Q
–– 11 digital inputs and 9 digital outputs
• Busbar backup protection
–– 16 digital inputs and 16 digital outputs
• Subfrequency load shedding
–– 16 digital inputs and 8 digital outputs
• Backup protection for transformers, generators, motors
–– 32 digital inputs
• Network automation
BUSBAR
25
81 79
27 59 47 81R 78 79 (81m)
M/m
3
3x67 50/
67NS 67NA 67NC 59N 32 67Q 68FF 68LE 40
67N 51V
1
3
87N
2nd
Harmonic 49 50BF 37 46FA CLP HCL
Restraint
50/
51G
LINE OTRAS
APLICACIONES
BASIC FUNCTIONS OPTIONALS
MAIN FEATURES
LINE
ADVANTAGES
• Economy: A customized TCP/R solution can be and automation applications.
defined for each application, based on: • Multiple applications in one unique device: In
–– Number of logical features implemented addition to the bay control performance, the same
TCP/R can be applied to develop complex automation
–– Modular hardware, that allow multiple digital functions.
and analogue inputs, digital outputs and
communication ports combinations. TCP/R can also be used as gateway of two different
substation networks or interfacing local or
–– Number of communication networks connected remotely to an HMI terminal.
(hardware links, protocols)
–– Different CPU cards • Easy to set: SIPCON® and EFS® software tools
–– Auxiliary power supply levels provide an easy configuration environment fr the
–– Redundancy applications (in auxiliary supply, user to program logical application instructions to be
communication ports, wired commands, etc) performed by the TCP/R. There are multiple ways to
• Security charge these logical programming and settings:
–– Self and independent hardware, that allows –– Directly, via serial or Ethernet port
TCP/R to work full-performance individually, –– Through a local network administrator (a central
unaffected by the control system status unit in serial communication, or an administrator
–– Able to fit to several criteria of redundant client in IEC 61850)
schemes –– Remotely, through communication devices as
• Flexibility: TCP/R high programmability performance modems, routers, etc.
makes these devices able to suit to multiple control
HARDWARE CHARACTERISTICS –– 32 digital inputs extension module
–– ½ 19” rack mounting chassis. Height: 4 U –– 1 x 5 plastic or glass fibre optic hub extension
–– Up to 6 serial and 2 Ethernet communication ports module
CPU module with the possibility of redundancy
• Maximum TCP/R capability:
–– Demodulated IRIG-B input integrated in the CPU
module All TCP/R are equipped by one CPU module and one
power supply module.
–– Single or redundant power supply module
Additionally, up to 2 extension modules of the inputs
–– 16 digital inputs & 8 digital outputs extension
& outputs type are admitted.
module
• Communication ports connections:
–– 16 digital inputs & 16 digital outputs with
common polarity extension module –– Serial ports: RS232, RS485, GFO, PFO
–– 16 digital inputs & 7 converter analog inputs –– Ethernet ports: RJ45, GFO, double GFO redundant
extension module
TCP/Q
MAIN FEATURES
TCP/Q is suitable for integration of telecontrol and power quality
recording for load distribution centres in one device.
• Data acquisition: Several combinations of digital and
analogue values modules, allowing to build up a suitable
device for each RTU application.
• Measurements and Power Quality data: Obtained directly
from the instrument transformers wired to the protection,
provides all the measured and calculated values that the
integrated PQM300 device can perform. Depending on the
model, these values are:
–– Phase-neutral voltage, module and angle
–– Average phase-neutral voltage
–– Phase-phase voltage, module and angle The LCD graphic display shows:
–– Average phase-phase voltage –– Position one-line diagram, including measurements
–– Inverse sequence voltage and other user defined indicators
–– Frequency –– Digital inputs and digital outputs status
–– Phase current, module and angle –– Hardware status
–– Average phase current –– User defined alarm indications
–– Neutral current, module and angle –– Current date and hour
–– Inverse sequence current • Event recording: Event data stamp and non-volatile
–– Active power memory buffering.
–– Reactive power • Local automation: Programming features, in order to
manage automatically local and remote command locking,
–– Apparent power
logical signals generation, and automatic tasks to make
–– Harmonics (individual and THD percentage) Phase operator’s decisions easier.
power factor
• Communications: Multiple communication ports, that
–– Average power factor allow TCP/Q to be integrated into several serial or Ethernet
–– Active energy counter (bidirectional) communication networks simultaneously. Thanks to that,
–– Reactive energy counter (bidirectional) communications gateway features can be implemented in
TCP/Q, as part of its functions.
–– Class 0.2 accuracy of voltage and current
TCP/Q supports all the commonly substation applied
• Local monitoring and command: Front panel with 5 push-
standard communications protocols as IEC 60870-5-101,
buttons, LCD graphic display and 5 programmable LED
IEC 60870-5-103, IEC 60870-5-104, DNP3.0, Modbus RTU
indicators.
and PROCOME. Other protocols can be considered under
demand. Some TCP/Q models can comply also with IEC
61850 standard.
• Synchronization: TCP/Q can be synchronized via suitable information concerning to power quality
communications protocol or via demodulated IRIG-B input. and operation that the user requires.
In serial architectures it can also send synchronization • Easy to set: SIPCON and EFS software tools
messages-via protocol to those devices working as slave provide an easy configuration environment for the
of this unit. user to program logical programming application
• Modularity: TCP/Q has been developed as a modular instructions to be performed by the TCP/Q. There
design, in order to offer the most suitable capabilities and are multiple ways to charge these logical and
prices of these devices in each case. settings:
–– Directly, via serial or Ethernet port
–– Through a local network administrator (a
BUS central unit in serial communication, or an
3 administrator client in IEC 61850)
–– Remotely, through communication devices as
TCP-Q modems, routers, etc.
Signalling
52
Command
3 MEASUREMENTS &
Power Quality
(see PQM300 series)
MAIN FEATURES
One single TCP/M unit is suitable to perform all the control features
required for any Medium Voltage or High Voltage substation position
(lines, feeders, transformers, capacitor banks, busbars, etc.). These
functions are:
LINE
ADVANTAGES
• Economy: A customized TCP/M solution can be defined for • Multiple applications in one unique device: In addition
each application, based on: to the bay control performance, the same TCP/M can
be applied to develop complex automation functions
–– Number of logical features implemented
as reactive power control, voltage regulation, service
–– Modular hardware, that allow multiple digital and automatic restoring, loads control, etc.
analogue inputs, digital outputs and
TCP/M can also be used as gateway to different
–– Communication ports combinations. substation networks or interfacing local or remotely to
–– Number of communication networks connected an HMI terminal.
(hardware links, protocols)
• Easy to set: SIPCON and EFS software tools provide an
–– Different CPU cards easy configuration environment for the user to program
–– Auxiliary power supply levels logical application instruction to be performed by the
–– Redundancy applications (in auxiliary supply, TCP/M. There are multiple ways to charge these logical
communication ports, wired commands, etc) programming and settings:
• Security –– Directly, via serial or Ethernet port
–– Self and independent hardware, that allows TCP/M to –– Through a local network administrator (a central unit
work full-performance individually, unaffected by the in serial communication, or an administrator client in
control system status IEC 61850)
–– Able to fit to several criteria of redundant schemes –– Remotely, through communication devices as
• Flexibility: TCP/M high programmability performance modems, routers, etc.
makes these devices able to suit to multiple control and
automation applications.
APPLICATIONS
ADVANTAGES
• Economic: Multifunctional solution, that allows to lighten
operation tasks in case of unstability critical conditions,
thanks to load shedding functionality.
• Fully communicable: If connected to a local network, allows
to be consulted, monitored and set local and remotely.
• FREE software.
• Multiprotocol: One unique relay supports all the commonly 3
** optional
Pin type terminals without extension board Pin type terminals with extension board
Ring type terminals without extension board Ring type terminals with extension board
PL70/IT OPTIONS
• DIGITAL INPUTS AND OUTPUTS CONFIGURATION
–– 2 digital inputs + 6 digital outputs
APPLICATIONS
–– 8 digital inputs + 11 digital outputs
PL70/IT protection unit represents an economical option of
–– 7 digital inputs + 11 digital outputs + 1 demodulated
overcurrent protection working as:
IRIG-B input
• Primary and/or back up distribution feeder protection • REAR COMMUNICATIONS OPTIONS
• Back up protection for transformers –– None
• Back up protection for motors –– 1 serial
• Back up protection for generators –– 2 serial
• REAR SERIAL COMMUNICATION CONNECTIONS
–– RS232, RS485, GFO, PFO
ADVANTAGES • ANALOG INPUT CONNECTIONS
–– Pin Type terminals
• Economic feeder protection solution.
–– Ring type terminals
• Multiple applications as backup overcurrent protection.
• FRONT IP54 PROTECTION
• Fully communicable. If connected to a local network, allows to • OSCILLOGRAPH DATA RECORDER + 4 SETTING GROUPS
be consulted, monitored and set local and remotely.
• DC AUXILIARY VOLTAGE MEASUREMENT
• Multiprotocol: One unique relay supports all the commonly
substation applied standard communications protocols.
PROCOME, DNP, Modbus, IEC 870-5-103.
• Unified phase rated current 1A/5A.
• Easy to communicate with: With SIPCON software automatic
detection tool, no previous knowledge is necessary to
communicate directly with the relay.
• Easy to use: Very intuitive universal software for Ingeteam
T&D protection relays.
• User programmable logic signals.
• Flexibility: Its design makes it adaptable to the specific needs
of each user.
–– Selectable ports type
–– Selectable analog input connection type
–– Programmable logical signals
–– Programmable digital inputs
–– Programmable digital outputs
–– Programmable LED indicators
• Improves system reliability: PL70/IT is provided with
complementary functions that allow, not only to prevent
possible failures in operation (breaker failure protection,
optional trip and close circuit supervision functions, breaker
monitoring, etc.) but to give real time indication and keep
updated reports of all events occurred in the protected element
(line, machine, etc)., what facilitates system’s maintenance
and incidence analysis.
• Multiple setting groups. 52
74TC
74CC
APPLICATIONS
PD3003/3 is a complete protection unit for three winding transformers of any voltage level. It can be used as main protection as well as back up
unit. It can be also applied in two winding transformers with a double secondary output.
• 86 Lockout
• 74TC/CC Each voltage level breaker trip and close circuit 74TC
74CC
50 50 50
74TC
74CC
74TC
74CC
supervision
51 51 51
• Programmable logics
51N 51N 51N
87
• Event recorder
• Fault recorder
• Measurements: High voltage side currents, Low voltage side OPTIONS
currents,
• Differential currents, ground currents, one phase voltage, • HOUSING AVAILABLE
frequency,
–– Vertical: 266 x 132.5x259 mm
• Current unbalance, demand maximeter
–– Horizontal: 132.5x266x259 mm
• Operation counters: Trips, operator openings, energy opened
by the breaker –– IEC 61850 models: 177x480x256 mm
• 6 setting groups –– 19” rack TCP enclosed: 177x480x256 mm
• Front panel with 16 keys alphanumeric keyboard, LCD (TCP dimensions)
alphanumeric display and 8 programmable LED indicators • ANALOG INPUTS CONNECTIONS
• 8 digital inputs and 7 digital outputs (basic configuration) –– Pin type terminals
• Extension board* (one per protection relay): –– Ring type terminal
• 9 digital inputs and 7 digital inputs • RATED PHASE CURRENT INPUTS
• Control features extension, as part of a TCP/Control unit- –– 1 A
• Front 9 pin RS232C port –– 5 A
• 1 or 2 rear communication ports (1 serial, 1 Ethernet, 2 serial • DIGITAL INPUTS AND OUTPUTS CONFIGURATIONS
or 1 serial + 1 Ethernet) –– 8 digital inputs + 7 digital outputs
• GFO or RJ45 Ethernet port + 2 serial ports in IEC 61850 –– 17 digital inputs + 14 digital outputs
models –– More combinations in TCP enclosed models
• IRIG-B input (demodulated) • REAR COMMUNICATION PORTS CONNECTIONS
• IP54 front lid* –– Serial ports: RS232, RS485, GFO, PFO
• 87 Three phase percentage differential unit –– Ethernet ports: RJ45, GFO
• 2nd, 2nd + 4th, and 5th harmonic differential protection • REAR COMMUNICATIONS OPTIONS
restraint
–– 1 serial
• 87 Unrestrained three phase differential unit
–– 2 serial
• 49 Thermal overload, on each voltage level
–– 2 serial + 1 Ethernet (IEC 61850 models)
• 50BF Breaker failure, on each voltage level
–– 2 serial + 2 Ethernet redundant (IEC 61850 models)
• 50 Instantaneous three phase overcurrent (two levels),on
–– For TCP enclosed models see TCP/C flyer
each voltage level
• DC AUXILIARY VOLTAGE MEASUREMENT
• 51 Time delayed three phase overcurrent, on each voltage
level • INNER TEMPERATURE MEASUREMENT
• 50N Instantaneous neutral overcurrent (two levels), on each • FRONT IP54 PROTECTION
voltage level (calculated)
• 51N Time delayed neutral overcurrent, on each voltage level
(calculated)
STANDARDS AND TESTS 1 MHz damped waves immunity test IEC 60255-22-1
Electromagnetic DC power supply variations and interruptions IEC 61000-4-29/
immunity test IEC 60255-11
Measurement of conducted radioelectric IEC60255-25/
emissions in DC power port EN55022 50 Hz magnetic fields immunity test IEC 61000-4-8
Measurement of radiated radioelectric emissions IEC 60255-5/ Climatic
EN55022/EN5511 Saline-oiled fog testt UNE 112-017-92
Insulation resistance test IEC60255-5 Cold test IEC 60068-2-1
Dielectric test IEC60255-5 Dry heat test IEC 60068-2-2
Impulse voltage test IEC60255-5 Damp heat test, steady state IEC 60068-2-78
Electrostatic discharges immunity test IEC61000-4-2 Change of temperature (thermal shock) IEC 60068-2-14
Radiated radio-frequency fields immunity test ENV 50204/IEC Mechanical
61000-4-3
Vibration test IEC 60255-21-1
Electrical fast transients immunity test IEC61000-4-4
Shock and bump test IEC 60255-21-2
Surge immunity test IEC 61000-4-5
Conducted disturbances induced by radio- IEC 6100-4-6
frequency fields immunity test
Damped oscillatory waves immunity test IEC 61000-4-12
Horizontal housing.
Pin type terminals with extension board, two serial Glass Fibre
Optic ports
Vertical case.
Ring type terminals with extension board
and two Glass Fibre Optic ports
SCAN ME
www.ppi.ph/dlfiles/INPC.pdf