PLC Connection Guide
PLC Connection Guide
1
PLC Connection Guide
Mitsubishi A2N/A3A/A3N/A1SH/A2SH ................. 248 OMRON FINS (Ethernet) ....................................... 408
Mitsubishi A2US....................................................... 251 OMRON Host Link .................................................. 410
Mitsubishi AJ71 ........................................................ 254 Panasonic FP............................................................. 414
Mitsubishi AJ71 (AnA/AnU CPU) .......................... 258 Panasonic FP (Ethernet) .......................................... 422
Mitsubishi AJ71 (Format 4) .................................... 262 Panasonic FP2 (Ethernet) ........................................ 425
Mitsubishi F930GOT Server ................................... 266 Panasonic MINAS A4 .............................................. 427
Mitsubishi FX0s/FX0n/FX1s/FX1n/FX2 ................ 269 Panasonic MINAS A5 .............................................. 433
Mitsubishi FX232/485BD ......................................... 273 Parker ACR9000 ...................................................... 437
Mitsubishi FX2n ....................................................... 278 Parker Compax3 ...................................................... 439
Mitsubishi FX3u (Ethernet) .................................... 281 Parker Compumotor 6K Series ............................... 444
Mitsubishi FX3u/FX3G............................................ 288 Parker SLVD Series ................................................. 446
Mitsubishi MELSEC-Q/L (Ethernet) ..................... 291 Rockwell CompactLogix - Free Tag Names ........... 449
Mitsubishi MR J3 A ................................................. 295 Rockwell CompactLogix/FlexLogix ........................ 451
Mitsubishi MR-MQ100 (Ethernet) ......................... 302 Rockwell DF1 ............................................................ 455
Mitsubishi Q00/Q00UJ/Q01/QJ71 .......................... 305 Rockwell DF1 (BCC) ................................................ 459
Mitsubishi Q00J ....................................................... 314 Rockwell DH485 ....................................................... 463
Mitsubishi Q00U/Q01U/Q02U/QnUD/QnUDH ..... 316 Rockwell EtherNet/IP (CompactLogix) .................. 468
Mitsubishi Q00UJ/QnU/QnUD/QnUDH/QnUDEH Rockwell EtherNet/IP (CompactLogix) – Free Tag
(mini USB) ................................................................ 319 Names ........................................................................ 471
Mitsubishi Q02/02H ................................................. 321 Rockwell EtherNet/IP (ControlLogix) – Free Tag
Mitsubishi Q06H ...................................................... 324 Names ........................................................................ 475
Mitsubishi QJ71E71 (Ethernet) .............................. 327 Rockwell EtherNet/IP (DF1) ................................... 480
MODBUS ASCII ...................................................... 334 Rockwell PLC5 ......................................................... 483
MODBUS ASCII Server .......................................... 339 RS Automation OEMAX Series .............................. 487
MODBUS RTU ......................................................... 343 SAIA PCD PGU Mode ............................................. 489
MODBUS RTU (0x/1x Range Adjustable) ............. 348 SAIA PCD S-BUS Mode .......................................... 491
MODBUS RTU (Adjustable)................................... 357 SAIA S-BUS (Ethernet) ........................................... 499
MODBUS RTU (zero-based addressing)................ 364 Samsung SPC-10 ...................................................... 502
MODBUS Server (COM/Ethernet) ........................ 369 SCENE6 Controller.................................................. 504
MODBUS TCP/IP .................................................... 377 Schleicher XCS 20C ................................................. 506
MODBUS TCP/IP (0x/1x Range Adjustable) ........ 379 Schleicher XCX 300 ................................................. 509
MODBUS TCP/IP (zero-based addressing) ........... 385 Schneider MODBUS RTU ....................................... 514
MODBUS TCP/IP 32Bit .......................................... 387 Schneider MODBUS TCP/IP .................................. 518
Moeller XC-CPU101 ................................................ 389 Schneider UniTelway ............................................... 520
OHJX ........................................................................ 391 SEW Movilink .......................................................... 522
OMRON C/CQM1 Series ........................................ 394 SEW MOVITRAC LTE .......................................... 524
OMRON CJ/CS/CP ................................................. 398 SHIMADEN MR13/FP93 ........................................ 528
OMRON CJ1/CS1 (Ethernet) ................................. 402 SHJ-A ........................................................................ 540
OMRON E5CN/E5EZ/E5ZN .................................. 404 SICK FLEXI SOFT ................................................. 542
2
PLC Connection Guide
Siemens LOGO (Ethernet) ...................................... 544 Trio MODBUS RTU, TCP/IP (Mode 7) ................. 659
Siemens S7-1200 (Ethernet)..................................... 549 VIGOR ...................................................................... 664
Siemens S7-200 ......................................................... 555 VIPA 200 ................................................................... 668
Siemens S7-200 (Ethernet)....................................... 558 VIPA 200 (VD any address) .................................... 671
Siemens S7-200 (VD any address) ........................... 565 VIPA 200, for ex. 214-2BT10 (Ethernet) ................ 674
Siemens S7-200 PPI .................................................. 568 VIPA 300 ................................................................... 676
Siemens S7-300 ......................................................... 573 VIPA 300 MPI .......................................................... 684
Siemens S7-300 MPI ................................................ 581 VIPA 300S (Ethernet) .............................................. 692
Siemens S7-300/ET200S (Ethernet) ........................ 589 VIPA 300S, for ex. 315-4NE12 (Ethernet) .............. 699
Siemens S7-400 (Ethernet)....................................... 595 XINJE XC Series ...................................................... 705
Siemens TI505 .......................................................... 603 YAMAHA ERCD ..................................................... 707
Siemens TI565/C400................................................. 609 YASKAWA CCMEP ............................................... 710
SSTC SSD Series ...................................................... 615 YASKAWA Memobus (MP Series Controllers) .... 712
TECHSOFT Intelligent Servo ................................. 627 YASKAWA MP Series Ethernet (Extension) ........ 719
TECO Inverter ......................................................... 629 YASKAWA MP2300Siec ......................................... 724
TECO TP02 Series ................................................... 632 YASKAWA SMC 3010 ............................................ 733
TECO TP03 Series ................................................... 635 YASKAWA SMC 3010 (Ethernet) .......................... 737
TINHAO ................................................................... 638 YOKOGAWA FA-M3 ............................................. 740
Toptek Topvert ......................................................... 641 YOKOGAWA FA-M3 (Ethernet) ........................... 746
TOSHIBA T Series ................................................... 644 YUDIAN AIBUS ....................................................... 748
TOSHIBA VF-S11 .................................................... 649 MT6050i/MT8050i Com Port Pin Assignment ...... 752
TOSHIBA MACHINE Provisor TC200 ................. 652
Trio MODBUS RTU, TCP/IP ................................. 654
3
PLC Connection Guide
Altus ALNET-I
Supported Series: Altus SeriesMode PO3042, PO3142, PO3242, PO3342, PL103 ,PL104,
PL105, QK800, QK801, QK2000.
HMI Setting:
Parameters Recommended Options Notes
PLC type Altus ALNET-I
PLC I/F RS232
Baud rate 9600
Data bits 8
Parity Even
Stop bits 1
PLC sta. no. 0
Device Address:
Bit/Word Device Type Format Range Memo
B M_Bit DDDDh 0 ~ 1023f Memories
B A DDDh 0 ~ 511f Auxiliary Relays
B E DDDh 0 ~ 511f Input Relays
B D_Bit DDDDdd 0 ~ 102331 Decimals
B F_Bit DDDDdd 0 ~ 102331 Reals
B I_Bit DDDDdd 0 ~ 102331 Integers
B S DDDh 0 ~ 511f Output Relays
W M DDDD 0 ~ 4096 Memories
DW D DDDD 0 ~ 4096 Decimals
DW F DDDD 0 ~ 1023 Reals
DW I DDDD 0 ~ 1023 Integers
W TM HHHH 0 ~ ffff* Memory Tables
DW TD HHHH 0 ~ ffff* Decimal Tables
DW TF HHHH 0 ~ ffff* Real Tables
DW TI HHHH 0 ~ ffff* Integer Tables
2
PLC Connection Guide
Note: The formats of TM, TD, TF and TI in PLC software are represented as TXA[B]. “X”
can be M, D, F, or I.
The address range of B is 0~FF, and A is 0~FF. The device type is AABB, and the range
depends on the PLC settings.
For example: Model PO3242, range of “A” is ”0” and range of “B” is 0 ~ 7.
Wiring Diagram:
The following represents the cable end connector.
9P D-Sub to 8P RJ45: PLC PO3042, PO3142, PO3242, PO3342
eMT3000 series
COM1 RS232 9P COM3 RS232 9P PLC RS232 8P RJ45
D-Sub Female D-Sub Female Male
2 RX 8 RX 2 TX
3 TX 7 TX 3 RX
5 GND 5 GND 5 GND
MT6050i/MT8050i
COM1 RS232 9P PLC RS232 8P RJ45
D-Sub Female Male
9 RX 2 TX
6 TX 3 RX
5 GND 5 GND
3
PLC Connection Guide
The following represents the cable end connector.
9P D-Sub to 9P D-Sub: PLC PL103, PL104, PL105
eMT3000 series
COM1 RS232 9P COM3 RS232 9P PLC RS232 9P D-Sub
D-Sub Female D-Sub Female Male
2 RX 8 RX 7 TX
3 TX 7 TX 1 RX
5 GND 5 GND 5 GND
MT6050i/MT8050i
COM1 RS232 9P PLC RS232 9P D-Sub
D-Sub Female Male
9 RX 7 TX
6 TX 1 RX
5 GND 5 GND
4
PLC Connection Guide
The following represents the cable end connector.
9P D-Sub to 9P D-Sub: PLC QK800, QK801, QK2000.
eMT3000 series
COM1 RS232 9P COM3 RS232 9P PLC RS232 9P D-Sub
D-Sub Female D-Sub Female Male
2 RX 8 RX 2 TX
3 TX 7 TX 3 RX
5 GND 5 GND 7 GND
MT6050i/MT8050i
COM1 RS232 9P PLC RS232 9P D-Sub
D-Sub Female Male
9 RX 2 TX
6 TX 3 RX
5 GND 7 GND
Driver Version:
Version Date Description
V1.10 Jul/24/2009
5
PLC Connection Guide
BACnet BACnet/IP
HMI Setting:
Parameters Recommended Options Notes
PLC type BACnet/IP
PLC I/F Ethernet
Port no. 47808
HMI port no. 47808 47808~47823
Device ID 342566 0~999999 According to device.
PLC sta. no. 1
2. As shown above, in BACnet/IP to MS/TP Adapter mode, [Network number] must follow
the factory setting, and enter the device station number in [Device ID].
3. [HMI port no]. default: 47808, can be filled in other effective value.
6
PLC Connection Guide
7
PLC Connection Guide
Step 3. Get tag address information
8
PLC Connection Guide
CSV file content is shown below; users can build the file and import:
a. Object format
b. OBJECT NAME (user defined tag name, EasyBuilder will start reading data from the
6th row of CSV file.), DEVICE ID, OBJECT TYPE(object ID) and INSTANCE(object
address)
Take (10,2)File as an example, 10 represents object ID, 2 represents object address, File
represents user defined name or default name.
9
PLC Connection Guide
10
PLC Connection Guide
Object ID Object Name Object Structure
Out Of Service
Units
Relinquish Default
Cov Increment
High Limit
Low Limit
Dead Band
Profile Name
3 Binary Input Object Name
Object Identifier
Object Type
Present Value
Event State
Out Of Service
Polarity
Profile Name
Notify Type
Alarm Value
4 Binary Output Object Name
Object Identifier
Object Type
Present Value
Event State
Out Of Service
Polarity
Profile Name
Notify Type
5 Binary Value Object Name
Object Identifier
Object Type
Present Value
Event State
Out Of Service
Profile Name
Notify Type
Alarm Value
6 Calendar Object Name
Object Identifier
11
PLC Connection Guide
Object ID Object Name Object Structure
Object Type
Present Value
7 Command Object Name
Object Identifier
Object Type
Present Value
In Process
All Writes Successful
8 Device Object Name
Object Identifier
Object Type
System Status
Vendor Name
Vendor Identifier
Model Name
Firmware Revision
Application Software Version
Protocol Version
Protocol Revision
Max APDU length Accepted
Segmentation Supported
Apdu Timeout
Number Of APDU retries
Data Base Revision
Max Segments Accepted
Day light Savings Status
Apdu Segment Timeout
Backup Failure Timeout
10 File Object Name
Object Identifier
Object Type
File Type
File Size
Archive
Read Only
11 Group Object Name
Object Identifier
Object Type
12
PLC Connection Guide
Object ID Object Name Object Structure
13 Multi State Object Name
Input Object Identifier
Object Type
Present Value
Event State
Out Of Service
Reliability
Number Of States
Time Delay
Notification Class
Notify Type
Profile Name
14 Multi State Object Name
Output Object Identifier
Object Type
Present Value
Event State
Out Of Service
Reliability
Number Of States
Time Delay
Notification Class
Notify Type
Profile Name
15 Notification Object Name
Class Object Identifier
Object Type
Notification Class
Priority
17 Schedule Object Name
Object Identifier
Object Type
Present Value
Priority For Writing
Reliability
Out Of Service
18 Averaging Object Name
Object Identifier
13
PLC Connection Guide
Object ID Object Name Object Structure
Object Type
Minimum Value
Average Value
Maximum Value
Attempted Samples
Valid Samples
Window Interval
Window Samples
19 Multi State Object Name
Value Object Identifier
Object Type
Present Value
Event State
Out Of Service
Reliability
Number Of States
Notification Class
Notify Type
Profile Name
Time Delay
20 Trend Log Object Name
Object Identifier
Object Type
Enable
Stop When Full
Buffer Size
Record Count
Total Record Count
21 Life Safety Object Name
Point Object Identifier
Object Type
Present Value
Tracking Value
Event State
Reliability
Out Of Service
Mode
Silenced
14
PLC Connection Guide
Object ID Object Name Object Structure
22 Life Safety Object Name
Zone Object Identifier
Object Type
Present Value
Tracking Value
Event State
Reliability
Out of Service
Mode
Silenced
23 Accumulator Object Name
Object Identifier
Object Type
Present Value
Event State
Out Of Service
Scale
Units
Reliability
24 Pulse Object Name
Converter Object Identifier
Object Type
Present Value
Event State
Out Of Service
Units
Scale Factor
Adjust Value
High Limit
Low Limit
Dead Band
Cov Increment
Count
Note 1. Object name can not include “#”.
15
PLC Connection Guide
Wiring Diagram:
Direct connect (crossover cable):
HMI RJ45 Male Wire Color PLC RJ45 Male
1 TX+ White/Orange 3 RX+
2 TX- Orange 6 RX-
3 RX+ White/Green 1 TX+
4 BD4+ Blue 4 BD4+
5 BD4- White/Blue 5 BD4-
6 RX- Green 2 TX-
7 BD3+ White/Brown 7 BD3+
8 BD3- Brown 8 BD3-
Through a hub:
HMI RJ45 Male Wire Color PLC RJ45 Male
1 TX+ White/Orange 1 TX+
2 TX- Orange 2 TX-
3 RX+ White/Green 3 RX+
4 BD4+ Blue 4 BD4+
5 BD4- White/Blue 5 BD4-
6 RX- Green 6 RX-
7 BD3+ White/Brown 7 BD3+
8 BD3- Brown 8 BD3-
Driver Version:
Version Date Description
V1.00 Jan/12/2012 Driver released
16
PLC Connection Guide
Barcode (USB/COM)
HMI Setting:
Parameters Recommended Options Notes
PLC type Barcode (USB/COM)
PLC I/F RS232 RS232/485,USB
Baud rate 9600 9600~115200
Data bits 8 7,8
Parity None None, Even, Odd
Stop bits 1 1,2
CR/LF, STX/ETX,
Terminator CR/LF
Other, None
Device Address:
Bit/Word Device type Format Range Memo
B FLAG DD 0 flag
W Barcode 0 DD 0 length
W Barcode 1 DD 1~255 string
Wiring Diagram:
The following represents the cable end connector.
eMT3000 series
COM1 RS232 9P COM3 RS232 9P RS232 9P D-Sub
D-Sub Female D-Sub Female FeMale
2 RX 8 RX TXD
3 TX 7 TX RXD
5 GND 5 GND GND
17
PLC Connection Guide
MT6000/8000 series except MT6050i/MT8050i
COM1 RS232 9P COM2 RS232 9P COM3 RS232 9P RS232 9P D-Sub
D-Sub Female D-Sub Female D-Sub Male FeMale
2 RX 6 RX 8 RX TXD
3 TX 4 TX 7 TX RXD
5 GND 5 GND 5 GND GND
MT6050i/MT8050i
COM1 RS232 9P RS232 9P D-Sub
D-Sub Female FeMale
9 RX TXD
6 TX RXD
5 GND GND
Driver Version:
Version Date Description
V1.30 Oct/1/2010
18
PLC Connection Guide
Baumuller
Website: http://www.baumuller.com/
HMI Setting:
Parameters Recommended Options Notes
PLC type Baumuller
PLC I/F RS485 4W
Baud rate 19200 9600, 19200
Data bits 8 7 or 8
Parity Even Even, Odd, None
Stop bits 1 1 or 2
HMI sta. no. 0
PLC sta. no. 0 Defaults
PLC Setting:
Communication mode RK 512 Protocol, 19200, 8, 1, Even
Device Address:
Bit/Word Device type Format Range Memo
DB0_bit ~
B DDDh 0 ~ 255f
DB29_bit
W DB0 ~ DB29 DDD 0 ~ 255
19
PLC Connection Guide
Wiring Diagram:
The following represents the cable end connector.
eMT3000 series
COM1 RS485 4W Baumuller servo RS422
9P D-Sub Male 9P D-Sub Male
1 RX- 1 TXD-
2 RX+ 9 TXD+
3 TX- 5 RXD-
4 TX+ 6 RXD+
5 GND 8 GND
MT6050i/MT8050i
COM1 RS485 4W Baumuller servo RS422
9P D-Sub Female 9P D-Sub Male
1 RX- 1 TXD-
2 RX+ 9 TXD+
3 TX- 5 RXD-
4 TX+ 6 RXD+
5 GND 8 GND
20
PLC Connection Guide
Driver Version:
Version Date Description
V1.10 Apr/17/2009
21
PLC Connection Guide
HMI Setting:
Parameters Recommended Options Notes
PLC type Beckhoff ADS/AMS (Ethernet)
PLC I/F Ethernet
Port no. 48898
ADS port 801 801, 811, 821, 831
PLC sta. no. 1
PLC Setting:
Step1.
Open TwinCat System Properties.
PLC Settings: Set HMI Name, AMS Net ID, and Address.
Ex:
HMI IP: 192.168.1.15
AMS Net ID: Must input 192.168.1.15.1.1
Address: 192.168.1.15
Name: Input “HMI” or any user–defined name.
22
PLC Connection Guide
Step2.
Simulate PLC on PC. 2 Twincat drivers must be installed as follows:
23
PLC Connection Guide
Step3.
The following commands can be utilized for Twincat PLC to output the parameters
observed.
24
PLC Connection Guide
PS. Twincat PLC
IX, QX, MX - Must output in BOOL type.
IW, QW, MW - Must output in UINT, WORD, and INT types.
ID, QD, MD - Must output in UDINT, DWORD, and DINT types.
25
PLC Connection Guide
Step5.
Click [Import Tag] button in EasyBuilder to open the TPY file compiled by Twincat PLC
Control.
Step6.
Download the project compiled in EasyBuilder to HMI.
26
PLC Connection Guide
Device address:
Bit/Word Device type Format Range Memo
B IX DDDDDo 0 ~ 655357 o : Bit no.(0 ~ 7)
B QX DDDDDo 0 ~ 655357 o : Bit no.(0 ~ 7)
B MX DDDDDo 0 ~ 655357 o : Bit no.(0 ~ 7)
W IW DDDDD 0 ~ 65535
W QW DDDDD 0 ~ 65535
W MW DDDDD 0 ~ 65535
DW ID DDDDD 0 ~ 65535
DW QD DDDDD 0 ~ 65535
DW MD DDDDD 0 ~ 65535
Wiring Diagram:
Direct connect (crossover cable):
HMI RJ45 Male Wire Color PLC RJ45 Male
1 TX+ White/Orange 3 RX+
2 TX- Orange 6 RX-
3 RX+ White/Green 1 TX+
4 BD4+ Blue 4 BD4+
5 BD4- White/Blue 5 BD4-
6 RX- Green 2 TX-
7 BD3+ White/Brown 7 BD3+
8 BD3- Brown 8 BD3-
27
PLC Connection Guide
Through a hub:
HMI RJ45 Male Wire Color PLC RJ45 Male
1 TX+ White/Orange 1 TX+
2 TX- Orange 2 TX-
3 RX+ White/Green 3 RX+
4 BD4+ Blue 4 BD4+
5 BD4- White/Blue 5 BD4-
6 RX- Green 6 RX-
7 BD3+ White/Brown 7 BD3+
8 BD3- Brown 8 BD3-
Driver Version:
Version Date Description
V1.00 Dec/08/2010 Driver released.
V1.10 Aug/24/2011 Extended address range up to 65535.
28
PLC Connection Guide
Beckhoff Embedded PC
HMI Setting:
Parameters Recommended Options Notes
PLC type Beckhoff Embedded PC
PLC I/F Ethernet
Port no. 48898
ADS port 801 801, 811, 821, 831
PLC sta. no. 1
PLC Setting:
For Twincat:
a. Confirm PC IP address
29
PLC Connection Guide
b. Open Twincat, Set IP address 169.254.56.12.1.1
c. Use Twincat to build a Route Table to make sure the system is connected, if PLC
power turns OFF and then ON, please redo this step.
Note: when connected, if “X” is displayed, the connection succeeded.
30
PLC Connection Guide
d. Open EasyBuilder, set IP address, ADS port and Port no.
For CERHOST:
a. Execute CERHOST.exe to connect with PLC on PC.
31
PLC Connection Guide
c. Succeeded to connect with PLC, click Start -> click Control Panel.
d. Click [Network and Dial-Up Connections] to display PLC device information; select
the PLC to check its IP.
e. Access PLC system settings, the default directory: \Hard Disk\System, execute
[TcAmsRemoteMgr].
32
PLC Connection Guide
f. AMS Net Id consists of 6 numbers, separated by “.”. The first 4 numbers stand for IP
and followed by “1.1”. The figure below shows the AMS Net Id of Local Computer,
please enter PLC IP plus “1.1”. Remote Computers shows the information of the HMI
to connect with. Click [Add] to add the HMI and click [OK] to finish setting.
33
PLC Connection Guide
h. Return to Control Panel; execute CX Configuration Tool to confirm PLC AMS Net
Id.
Device address:
Bit/Word Device type Format Range Memo
B IX DDDDDo 0 ~ 655357 o : Bit no.(0 ~ 7)
B QX DDDDDo 0 ~ 655357 o : Bit no.(0 ~ 7)
B MX DDDDDo 0 ~ 655357 o : Bit no.(0 ~ 7)
W IW DDDDD 0 ~ 65535
W QW DDDDD 0 ~ 65535
W MW DDDDD 0 ~ 65535
DW ID DDDDD 0 ~ 65535
DW QD DDDDD 0 ~ 65535
DW MD DDDDD 0 ~ 65535
34
PLC Connection Guide
Wiring Diagram:
Direct connect (crossover cable):
HMI RJ45 Male Wire Color PLC RJ45 Male
1 TX+ White/Orange 3 RX+
2 TX- Orange 6 RX-
3 RX+ White/Green 1 TX+
4 BD4+ Blue 4 BD4+
5 BD4- White/Blue 5 BD4-
6 RX- Green 2 TX-
7 BD3+ White/Brown 7 BD3+
8 BD3- Brown 8 BD3-
Through a hub:
HMI RJ45 Male Wire Color PLC RJ45 Male
1 TX+ White/Orange 1 TX+
2 TX- Orange 2 TX-
3 RX+ White/Green 3 RX+
4 BD4+ Blue 4 BD4+
5 BD4- White/Blue 5 BD4-
6 RX- Green 6 RX-
7 BD3+ White/Brown 7 BD3+
8 BD3- Brown 8 BD3-
Driver Version:
Version Date Description
V1.00 Apr/18/2011 Driver released.
V1.10 Aug/24/2011 Extended address range up to 65535.
35
PLC Connection Guide
HMI Setting:
Parameters Recommended Options Notes
PLC type CAN (Controller Area Network) Bus
Node ID 1 1~127
Baud rate 250K 10K~1M
Follow the steps to import EDS file.
36
PLC Connection Guide
Step 3. Select the EDS file to be imported.
Device Address:
Bit/Word Device type Format Range Memo
B TxPDOn_BIT DDDDo 100 ~ 99977
B RxPDOn_BIT DDDDo 100 ~ 99977
W TxPDOn DDDD 10 ~ 9997
W RxPDOn DDDD 10 ~ 9997
W SDO_8bit HHHHHH 0~FFFFFF
W SDO_16bit HHHHHH 0~FFFFFF
W SDO_32bit HHHHHH 0~FFFFFF
37
PLC Connection Guide
Wiring Diagram:
The following represents the cable end connector.
eMT3000 series
CAN Bus 9P CAN Device
D-Sub Female
7 D- D-
8 D+ D+
5 GND GND
Driver Version:
Version Date Description
V1.00 Jul/5/2011 Driver released.
38
PLC Connection Guide
Change
Supported Series: Compressor controller
Website: http://www.sh-changjia.com/
HMI Setting:
Parameters Recommended Options Notes
PLC type Change
PLC I/F RS485 2W
Baud rate 9600
Data bits 8
Parity None
Stop bits 1
PLC sta. no. 1 1~6
Device Address:
Bit/Word Device type Format Range Memo
B CTL DDD 0 ~ 5, 128, 150 Write only
DW SET DDD 0 ~ 57, 128
DW STATUS DD 1 ~ 20 Read only
Wiring Diagram:
The following represents the cable end connector.
eMT3000 series
COM1 RS485 2W COM3 RS485 2W Change RS485 terminal
9P D-Sub Male 9P D-Sub Male
1 RX- 6 Data- 15 D-
2 RX+ 9 Data+ 16 D+
5 GND 5 GND
39
PLC Connection Guide
MT6000/8000 series except MT6050i/MT8050i
COM1 RS485 2W COM3 RS485 2W Change RS485 terminal
9P D-Sub Male 9P D-Sub Male
1 RX- 6 Data- 15 D-
2 RX+ 9 Data+ 16 D+
5 GND 5 GND
MT6050i/MT8050i
COM1 RS485 2W COM3 RS485 2W Change RS485 terminal
9P D-Sub Female 9P D-Sub Female
1 RX- 7 Data- 15 D-
2 RX+ 8 Data+ 16 D+
5 GND 5 GND
Driver Version:
Version Date Description
V1.00 Jan/19/2011 Driver released.
40
PLC Connection Guide
Cimon CM1-CP4A/ECO1A
Supported Series: Cimon CM1 series, CP4A module
Website: http://www.kdtsys.com
HMI Setting:
Parameters Recommended Options Notes
PLC type Cimon CM1-CP4A/ECO1A
PLC I/F RS232
Baud rate 38400
Data bits 8
Parity None
Stop bits 1
PLC sta. no. 1
Device Address:
Bit/Word Device type Format Range Memo
B X DDh 0 ~ 23f 0-1F Read Only
B Y DDh 0 ~ 23f
B M DDDh 0 ~ 511f
B K DDDh 0 ~ 127f
B L DDDh 0 ~ 127f
B F DDDh 0 ~ 127f Read Only
B T DDDh 0 ~ 102f
B C DDDh 0 ~ 102f
W D DDDD 0 ~ 4999
W S DD 0 ~ 99 Max. Range: 99
W TS DDDD 0 ~ 1023
W TC DDDD 0 ~ 1023
W CS DDDD 0 ~ 1023
W CC DDDD 0 ~ 1023
41
PLC Connection Guide
Wiring Diagram:
The following represents the cable end connector.
eMT3000 series
COM1 RS232 9P COM3 RS232 9P CM1-CP4A RS232 6P
D-Sub Female D-Sub Female RJ11 Male
2 RX 8 RX 2 TXD
3 TX 7 TX 3 RXD
5 GND 5 GND 5 GND
MT6050i/MT8050i
COM1 RS232 9P CM1-CP4A RS232 6P
D-Sub Female RJ11 Male
9 RX 2 TXD
6 TX 3 RXD
5 GND 5 GND
Driver Version:
Version Date Description
V1.20 Nov/30/2009
42
PLC Connection Guide
Cimon CM1-SC02A
Supported Series: Cimon CM series, SC02A module
Website: http://www.kdtsys.com
HMI Setting:
Parameters Recommended Options Notes
PLC type Cimon CM1-SC02A
PLC I/F RS232
Baud rate 38400
Data bits 8
Parity None
Stop bits 1
PLC sta. no. 1
Device Address:
Bit/Word Device type Format Range Memo
B X DDh 0 ~ 23f 0-1F Read Only
B Y DDh 0 ~ 23f 0-F Read Only
B M DDDh 0 ~ 511f
B K DDDh 0 ~ 127f
B L DDDh 0 ~ 127f
B F DDDh 0 ~ 127f Read Only
B T DDDh 0 ~ 102f
B C DDDh 0 ~ 102f
W D DDDD 0 ~ 4999
W S DD 0 ~ 99 Max. Range: 99
W TS DDDD 0 ~ 1023
W TC DDDD 0 ~ 1023
W CS DDDD 0 ~ 1023
W CC DDDD 0 ~ 1023
43
PLC Connection Guide
Wiring Diagram:
The following represents the cable end connector.
eMT3000 series
COM1 RS232 9P COM3 RS232 9P CM1-SC02A RS232 9P
D-Sub Female D-Sub Female D-Sub Male
2 RX 8 RX 3 TD
3 TX 7 TX 2 RD
5 GND 5 GND 5 GND
MT6050i/MT8050i
COM1 RS232 9P CM1-SC02A RS232 9P
D-Sub Female D-Sub Male
9 RX 3 TD
6 TX 2 RD
5 GND 5 GND
Driver Version:
Version Date Description
V1.20 Nov/30/2009
44
PLC Connection Guide
Copley Controls
Supported Series: Digital Servo Driver & Controllers, Xenus, Xenus Micro, Accelnet,
Accelnet Micro, Stepnet series.
Website: http://www.copleycontrols.com/motion/
HMI Setting:
Parameters Recommended Options Notes
PLC type Copley Controls
PLC I/F RS232
Baud rate 9600 9600~115200
Data bits 8 8
Parity None Even, Odd, None
Stop bits 1 1
HMI sta. no. 0
PLC sta. no. 0 0-127
Device Address:
Bit/Word Device type Format Range Memo
W Flash INT 16 HHH 0 ~ 999 For Register is INT16 or U16
W RAM INT 16 HHH 0 ~ 999 For Register is INT16 or U16
W Flash INT 32 HHH 0 ~ 999 For Register is INT32 or U32
W RAM INT 32 HHH 0 ~ 999 For Register is INT32 or U32
W Register DDDD 0 ~ 2457
W T_command H 0
W Reset H 0
45
PLC Connection Guide
Wiring Diagram:
The following represents the cable end connector.
9P D-Sub to 6P RJ11: Xenus, Xenus Micro, Accelnet, Stepnet
eMT3000 series
COM1 RS232 9P COM3 RS232 9P RS232 6P RJ11 Male
D-Sub Female D-Sub Female
2 RX 8 RX 5 TXD
3 TX 7 TX 2 RXD
5 GND 5 GND 3, 4 GND
MT6050i/MT8050i
COM1 RS232 9P RS232 6P RJ11 Male
D-Sub Female
9 RX 5 TXD
6 TX 2 RXD
5 GND 3, 4 GND
46
PLC Connection Guide
The following represents the cable end connector.
Accelnet Micro:
eMT3000 series
COM1 RS232 9P COM3 RS232 9P Accelnet Micro Panel
D-Sub Female D-Sub Female RS232 J5 Cable
Connector
2 RX 8 RX 29 TXD
3 TX 7 TX 14 RXD
5 GND 5 GND 15 GND
47
PLC Connection Guide
MT6050i/MT8050i
COM1 RS232 9P Accelnet Micro Panel
D-Sub Female RS232 J5 Cable
Connector
9 RX 29 TXD
6 TX 14 RXD
5 GND 15 GND
Driver Version:
Version Date Description
V1.20 Dec/30/2008
48
PLC Connection Guide
CROUZET M3 (FBD)
HMI Setting:
Parameters Recommended Options Notes
PLC type CROUZET M3 (FBD)
PLC I/F RS232
Baud rate 115200
Data bits 7
Parity Even
Stop bits 1
PLC sta. no. 1
Device Address:
Bit/Word Device type Format Range Memo
B SLI_Bit DDh 10 ~ 24f Serial link input
B SLO_Bit DDh 250 ~ 48f Serial link output (read only)
B State D 1 State in PLC (read only)
W IA DD 1 ~ 99 Analogy input (default: 1 ~ 4)
W SL_IN DD 1 ~ 24 Serial link input
W SL_OUT DD 25 ~ 48 Serial link output (read only)
W Time D 1~6 Time & Day*
W Order D 1 Command** (write only)
* : address 1: second, address 2 : minute, address 3 : hour , address 4 : day, address 5 :
month, address 6 : year. The value range for “Year” is 0~99, entering “0” represents year
2000, entering “99” represents year 2099.
**: run mode write 2, stop mode write 1.
49
PLC Connection Guide
Wiring Diagram:
The following represents the cable end connector.
eMT3000 series
COM1 RS232 9P CROUZET M3 RS232
D-Sub Female 9P D-Sub Male
(Extension Cable)
2 RX 2 TD
3 TX 3 RD
5 GND 5 GND
7 RTS 4 DTR
50
PLC Connection Guide
Driver Version:
Version Date Description
V1.10 Oct/26/2010
V1.20 Mar/29/2012 Add device type : State, Time, Order
V1.30 May/14/2012 “Time” entering is now allowed.
51
PLC Connection Guide
CROUZET M3 (LAD)
HMI Setting:
Parameters Recommended Options Notes
PLC type CROUZET M3 (LAD)
PLC I/F RS232
Baud rate 115200
Data bits 7
Parity Even
Stop bits 1
PLC sta. no. 1
Device Address:
Bit/Word Device type Format Range Memo
B I DD 1 ~ 99 Input (default: 1 ~ 4)
B O DD 1 ~ 99 Output (default: 1 ~ 4)
B M DD 1 ~ 28 Relay
B SLI_Bit DDh 10 ~ 24f Serial link input
B SLO_Bit DDh 250 ~ 48f Serial link output (read only)
B State D 1 State in PLC (read only)
W T DD 1 ~ 12 Timer
W C DD 1 ~ 16 Counter
W IA DD 1 ~ 99 Analogy input (default: 1 ~ 4)
W SL_IN DD 1 ~ 24 Serial link input
W SL_OUT DD 25 ~ 48 Serial link output (read only)
W Time D 1~6 Time & Day *
W Order D 1 Command (write only) **
* : address 1: second, address 2 : minute, address 3 : hour , address 4 : day, address 5 :
month, address 6 : year .The value range for “Year” is 0~99, entering “0” represents year
2000, entering “99” represents year 2099.
**: run mode write 2, stop mode write 1.
52
PLC Connection Guide
Wiring Diagram:
The following represents the cable end connector.
eMT3000 series
COM1 RS232 9P CROUZET M3 RS232
D-Sub Female 9P D-Sub Male
(Extension Cable)
2 RX 2 TD
3 TX 3 RD
5 GND 5 GND
7 RTS 4 DTR
53
PLC Connection Guide
Driver Version:
Version Date Description
V1.20 Oct/26/2010
V1.30 Mar/30/2012 Add device type : State, Time, Order
V1.40 May/14/2012 “Time” entering is now allowed.
54
PLC Connection Guide
HMI Setting:
Parameters Recommended Options Notes
PLC type Danfoss ECL Apex20
PLC I/F RS232
Baud rate 9600
Data bits 8
Parity None
Stop bits 1
PLC sta. no. 1
Device Address:
Bit/Word Device type Format Range Memo
B Flag DDDD 0 ~ 8191
B Output DDDD 0 ~ 1023
B Input DDDD 0 ~ 1023
B Reg_Bit DDDDDdd 0 ~ 1638331 dd: Bit no. (00 ~ 31)
DW Register DDDDD 0 ~ 16383
DW Counter DDDD 0 ~ 1599
DW Timer DDDD 0 ~ 1599
DW Reg_Float DDDDD 0 ~ 16383 Support 32-bit float format
EasyBuilder device address range may differ from PLC extended mode, please refer to
EasyBuilder address range as above.
55
PLC Connection Guide
Wiring Diagram:
The following represents the cable end connector.
eMT3000 series
COM1 RS232 9P COM3 RS232 9P ECL Apex20 Controller
D-Sub Female D-Sub Female RS232 9P D-Sub Male
2 RX 8 RX 3 TXD
3 TX 7 TX 2 RXD
5 GND 5 GND 5 GND
7 RTS
circuit
8 CTS
MT6050i/MT8050i
COM1 RS232 9P ECL Apex20 Controller
D-Sub Female RS232 9P D-Sub Male
9 RX 3 TXD
6 TX 2 RXD
5 GND 5 GND
7 RTS
circuit
8 CTS
56
PLC Connection Guide
The following represents the cable end connector.
eMT3000 series
COM1 RS485 2W COM3 RS485 2W ECL Apex20 Controller
9P D-Sub Male 9P D-Sub Male Port#1 / Port#0
1 RX- 6 Data- 11 / 29
2 RX+ 9 Data+ 12 / 28
5 GND 5 GND
MT6050i/MT8050i
COM1 RS485 2W COM3 RS485 2W ECL Apex20 Controller
9P D-Sub Female 9P D-Sub Female Port#1 / Port#0
1 RX- 7 Data- 11 / 29
2 RX+ 8 Data+ 12 / 28
5 GND 5 GND
Driver Version:
Version Date Description
V1.40 OCT/06/2008
57
PLC Connection Guide
HMI Setting:
Parameters Recommended Options Notes
PLC type Danfoss ECL Apex20 (Ethernet)
PLC I/F Ethernet
Port no. 5050
PLC sta. no. 0
Device Address:
Bit/Word Device type Format Range Memo
B Flag DDDD 0 ~ 8191
B Output DDDD 0 ~ 1023
B Input DDDD 0 ~ 1023
B Reg_Bit DDDDDdd 0 ~ 1638331 dd: Bit no. (00 ~ 31)
W Register DDDDD 0 ~ 16383
W Counter DDDD 0 ~ 1599
W Timer DDDD 0 ~ 1599
W Reg_Float DDDDD 0 ~ 16383 Support 32-bit float format
EasyBuilder device address range may differ from PLC extended mode, please refer to
EasyBuilder address range as above.
58
PLC Connection Guide
Wiring Diagram:
Direct connect (crossover cable):
HMI RJ45 Male Wire Color PLC RJ45 Male
1 TX+ White/Orange 3 RX+
2 TX- Orange 6 RX-
3 RX+ White/Green 1 TX+
4 BD4+ Blue 4 BD4+
5 BD4- White/Blue 5 BD4-
6 RX- Green 2 TX-
7 BD3+ White/Brown 7 BD3+
8 BD3- Brown 8 BD3-
Through a hub:
HMI RJ45 Male Wire Color PLC RJ45 Male
1 TX+ White/Orange 1 TX+
2 TX- Orange 2 TX-
3 RX+ White/Green 3 RX+
4 BD4+ Blue 4 BD4+
5 BD4- White/Blue 5 BD4-
6 RX- Green 6 RX-
7 BD3+ White/Brown 7 BD3+
8 BD3- Brown 8 BD3-
Driver Version:
Version Date Description
V1.10 Jan/10/2011
59
PLC Connection Guide
Danfoss FC Series
Supported Series: FC051, FC100, FC200, FC300, VLT Micro Driver.
Website: http://www.danfoss.com/
HMI Setting:
Parameters Recommended Options Notes
PLC type Danfoss FC Series
PLC I/F RS485 2W
Baud rate 9600
Data bits 8
Parity Even
Stop bits 1
PLC sta. no. 1
Device Address:
Bit/Word Device type Format Range Memo
W Parameter 09 DDDD 0 ~ 9999 Set Parameter
DW Reference 10 D 0~1 Control Bus Reference
DW Para_Index 11 DDDDDD 0 ~ 999999 Set Parameter(Index)
Para_Index 310.1=31001, Para_Index310.0=31000
Wiring Diagram:
The following represents the cable end connector.
eMT3000 series
COM1 RS485 2W COM3 RS485 2W FC RS485 terminal
9P D-Sub Male 9P D-Sub Male
1 RX- 6 Data- 69 D-
2 RX+ 9 Data+ 68 D+
5 GND 5 GND
60
PLC Connection Guide
MT6000/8000 series except MT6050i/MT8050i
COM1 RS485 2W COM3 RS485 2W FC RS485 terminal
9P D-Sub Male 9P D-Sub Male
1 RX- 6 Data- 69 D-
2 RX+ 9 Data+ 68 D+
5 GND 5 GND
MT6050i/MT8050i
COM1 RS485 2W COM3 RS485 2W FC RS485 terminal
9P D-Sub Female 9P D-Sub Female
1 RX- 7 Data- 69 D-
2 RX+ 8 Data+ 68 D+
5 GND 5 GND
Driver Version:
Version Date Description
V1.10 Jan/14/2010
61
PLC Connection Guide
Website: http://www.danfoss.com/
HMI Setting:
Parameters Recommended Options Notes
PLC type Danfoss VLT2800 Series
PLC I/F RS485 2W
Baud rate 9600
Data bits 8
Parity Even
Stop bits 1
PLC sta. no. 1 0-126 According to PLC
PLC Setting:
Communication mode 9600, Even, 8, 1 (default)
Device Address:
Bit/Word Device type Format Range Memo
DW Parameter DDDD 0 ~ 2000 Set Parameter
W Reference D 0~1 Control Bus Reference
62
PLC Connection Guide
Wiring Diagram:
The following represents the cable end connector.
eMT3000 series
COM1 RS485 2W COM3 RS485 2W RS485 terminal
9P D-Sub Male 9P D-Sub Male
1 RX- 6 Data- 69 D-
2 RX+ 9 Data+ 68 D+
5 GND 5 GND
MT6050i/MT8050i
COM1 RS485 2W COM3 RS485 2W RS485 terminal
9P D-Sub Female 9P D-Sub Female
1 RX- 7 Data- 69 D-
2 RX+ 8 Data+ 68 D+
5 GND 5 GND
Driver Version:
Version Date Description
V1.10 Dec/30/2008
63
PLC Connection Guide
DELTA DVP
Supported Series: DELTA DVP series
Website: http://www.deltadriver.com
HMI Setting:
Parameters Recommended Options Notes
PLC type DELTA DVP
PLC I/F RS232 RS232, RS485
Baud rate 9600 9600, 19200
Data bits 7 7, 8
Parity Even Even, Odd, None
Stop bits 1 1
PLC sta. no. 1 0-255
Device Address:
Bit/Word Device type Format Range Memo
B X OOOOO 0 ~ 23417 (octal) Input
B Y OOOOO 0 ~ 23417 (octal) Output
B M DDDDD 0 ~ 65536 Auxiliary Relay
B S DDDD 0 ~ 9999 Step Relay
B T DDDD 0 ~ 9999 Timer
B C DDDD 0 ~ 9999 Counter
B TV_Bit DDDDdd 0 ~ 999915 Timer
W TV DDDD 0 ~ 9999 Timer
W CV DDD 0 ~ 127 Counter
W CV2 DDD 200 ~ 254 Double Word Counter
W D DDDD 0 ~ 9999 Data Register
64
PLC Connection Guide
Wiring Diagram:
The following represents the cable end connector.
eMT3000 series
COM1 RS232 9P COM3 RS232 9P RS232 8P Mini-DIN
D-Sub Female D-Sub Female Male
2 RX 8 RX 5 TXD
3 TX 7 TX 4 RXD
5 GND 5 GND 3/8 GND
MT6050i/MT8050i
COM1 RS232 9P RS232 8P Mini-DIN
D-Sub Female Male
9 RX 5 TXD
6 TX 4 RXD
5 GND 3/8 GND
Driver Version:
Version Date Description
V1.20 Dec/30/2008
65
PLC Connection Guide
Website: http://www.deltadriver.com
HMI Setting:
Parameters Recommended Options Notes
PLC type DELTA DVPEN01-SL (Ethernet)
PLC I/F Ethernet
Port no. 502
PLC sta. no. 0
Device Address:
Bit/Word Device type Format Range Memo
B C_Bit DDD 0 ~ 255
B M DDDD 0 ~ 4095
B S DDDD 0 ~ 1023
B T_Bit DDD 0 ~ 255
B X OOO 0 ~ 377
B Y OOO 0 ~ 377
W C DDD 0 ~ 255
W D DDDD 0 ~ 9999
W T DDD 0 ~ 255
66
PLC Connection Guide
Wiring Diagram:
Direct connect (crossover cable):
HMI RJ45 Male Wire Color PLC RJ45 Male
1 TX+ White/Orange 3 RX+
2 TX- Orange 6 RX-
3 RX+ White/Green 1 TX+
4 BD4+ Blue 4 BD4+
5 BD4- White/Blue 5 BD4-
6 RX- Green 2 TX-
7 BD3+ White/Brown 7 BD3+
8 BD3- Brown 8 BD3-
Through a hub:
HMI RJ45 Male Wire Color PLC RJ45 Male
1 TX+ White/Orange 1 TX+
2 TX- Orange 2 TX-
3 RX+ White/Green 3 RX+
4 BD4+ Blue 4 BD4+
5 BD4- White/Blue 5 BD4-
6 RX- Green 6 RX-
7 BD3+ White/Brown 7 BD3+
8 BD3- Brown 8 BD3-
Driver Version:
Version Date Description
V1.00 Jun/11/2012 Driver released.
67
PLC Connection Guide
Website: http://www.cw180.com
HMI Setting:
Parameters Recommended Options Notes
PLC type DL/T645 CHUANG HONG
PLC I/F RS485 2W
Baud rate 9600
Data bits 8
Parity Even
Stop bits 1
PLC sta. no. 1
Device Address:
Bit/Word Device type Format Range Memo
W B621 D 0~1
W B622 D 0~1
W B623 D 0~1
W zero phase D 0~1
W B611 D 0~1
W B612 D 0~1
W B613 D 0~1
W B631 D 0~1
W B632 D 0~1
W B633 D 0~1
W B630 D 0~1
W B641 D 0~1
W B642 D 0~1
W B643 D 0~1
W B640 D 0~1
W A-apparentT D 0~1
W B-apparentT D 0~1
W C-apparentT D 0~1
W T-apparentT D 0~1
W B650 D 0~1
68
PLC Connection Guide
Bit/Word Device type Format Range Memo
W B651 D 0~1
W B652 D 0~1
W B653 D 0~1
W 9010 D 0~1
W 9020 D 0~1
W 9110 D 0~1
W 9120 D 0~1
W 9130 D 0~1
W 9140 D 0~1
W 9150 D 0~1
W 9160 D 0~1
W 9410 D 0~1
W 9420 D 0~1
W 9510 D 0~1
W 9520 D 0~1
W 9530 D 0~1
W 9540 D 0~1
W 9550 D 0~1
W 9560 D 0~1
W 9810 D 0~1
W 9820 D 0~1
W 9910 D 0~1
W 9920 D 0~1
W 9930 D 0~1
W 9940 D 0~1
W 9950 D 0~1
W 9960 D 0~1
W A010 D 0~1
W A020 D 0~1
W A110 D 0~1
W A120 D 0~1
W A130 D 0~1
W A140 D 0~1
W A150 D 0~1
W A160 D 0~1
W A410 D 0~1
W A420 D 0~1
W A510 D 0~1
W A520 D 0~1
W A530 D 0~1
69
PLC Connection Guide
Bit/Word Device type Format Range Memo
W A540 D 0~1
W A550 D 0~1
W A560 D 0~1
W A810 D 0~1
W A820 D 0~1
W A910 D 0~1
W A920 D 0~1
W A930 D 0~1
W A940 D 0~1
W A950 D 0~1
W A960 D 0~1
W B010 D 0~1
W B020 D 0~1
W B110 D 0~1
W B120 D 0~1
W B130 D 0~1
W B140 D 0~1
W B150 D 0~1
W B160 D 0~1
W B410 D 0~1
W B420 D 0~1
W B510 D 0~1
W B520 D 0~1
W B530 D 0~1
W B540 D 0~1
W B550 D 0~1
W B560 D 0~1
W B810 D 0~1
W B820 D 0~1
W B910 D 0~1
W B920 D 0~1
W B930 D 0~1
W B940 D 0~1
W B950 D 0~1
W B960 D 0~1
W B210 D 0~1
W B211 D 0~1
W B212 D 0~1
W B213 D 0~1
W B214 D 0~1
70
PLC Connection Guide
Bit/Word Device type Format Range Memo
W B310 D 0~1
W B311 D 0~1
W B312 D 0~1
W B313 D 0~1
W B320 D 0~1
W B321 D 0~1
W B322 D 0~1
W B323 D 0~1
W B330 D 0~1
W B331 D 0~1
W B332 D 0~1
W B333 D 0~1
W B340 D 0~1
W B341 D 0~1
W B342 D 0~1
W B343 D 0~1
W C010 D 0~1
W C011 D 0~1
W C020 D 0~1
W C021 D 0~1
W C022 D 0~1
W C030 D 0~1
W C031 D 0~1
W C032 D 0~1
W C033 D 0~1
W C034 D 0~1
W C111 D 0~1
W C112 D 0~1
W C113 D 0~1
W C114 D 0~1
W C115 D 0~1
W C116 D 0~1
W C117 D 0~1
W C118 D 0~1
W C119 D 0~1
W C11A D 0~1
W C211 D 0~1
W C212 D 0~1
W C310 D 0~1
W C311 D 0~1
71
PLC Connection Guide
Bit/Word Device type Format Range Memo
W C312 D 0~1
W C313 D 0~1
W C314 D 0~1
W C320 D 0~1
W C321 D 0~1
W C322 D 0~1
W C330 D 0~1
W C331 D 0~1
W C332 D 0~1
W C340 D 0~1
W C341 D 0~1
W C342 D 0~1
W C3A0 D 0~1
W C3A1 D 0~1
W C3A2 D 0~1
W C410 D 0~1
W C411 D 0~1
W C41E D 0~1
W C510 D 0~1
W C511 D 0~1
W B634 D 0~1
W B635 D 0~1
72
PLC Connection Guide
Wiring Diagram:
The following represents the cable end connector.
eMT3000 series
COM1 RS485 2W COM3 RS485 2W RS485 terminal
9P D-Sub Male 9P D-Sub Male
1 RX- 6 Data- 13 RS485B1
2 RX+ 9 Data+ 12 RS485A1
5 GND 5 GND
MT6050i/MT8050i
COM1 RS485 2W COM3 RS485 2W RS485 terminal
9P D-Sub Female 9P D-Sub Female
1 RX- 7 Data- 13 RS485B1
2 RX+ 8 Data+ 12 RS485A1
5 GND 5 GND
Driver Version:
Version Date Description
V1.00 Apr/13/2011 Driver released.
73
PLC Connection Guide
DL/T645 Standard
Website: http://www.cw180.com
HMI Setting:
Parameters Recommended Options Notes
PLC type DL/T645 Standard
PLC I/F RS485 2W
Baud rate 9600
Data bits 8
Parity Even
Stop bits 1
PLC sta. no. 1
Device Address:
Bit/Word Device type Format Range Memo
W Data HHHHHHHH 0 ~ 6FFFFFF
Wiring Diagram:
The following represents the cable end connector.
eMT3000 series
COM1 RS485 2W COM3 RS485 2W RS485 terminal
9P D-Sub Male 9P D-Sub Male
1 RX- 6 Data- D-
2 RX+ 9 Data+ D+
5 GND 5 GND
74
PLC Connection Guide
MT6000/8000 series except MT6050i/MT8050i
COM1 RS485 2W COM3 RS485 2W RS485 terminal
9P D-Sub Male 9P D-Sub Male
1 RX- 6 Data- D-
2 RX+ 9 Data+ D+
5 GND 5 GND
MT6050i/MT8050i
COM1 RS485 2W COM3 RS485 2W RS485 terminal
9P D-Sub Female 9P D-Sub Female
1 RX- 7 Data- D-
2 RX+ 8 Data+ D+
5 GND 5 GND
Driver Version:
Version Date Description
V1.00 Apr/14/2011 Driver released.
75
PLC Connection Guide
DL-BCM Server
Website: http://www.hzdelin.com
HMI Setting:
Parameters Recommended Options Notes
PLC type DL-BCM Server
PLC I/F RS232 RS232, RS485
Baud rate 9600 9600~115200
Data bits 8 8
Parity None Even, Odd, None
Stop bits 1 1
PLC sta. no. 0 0-31
Device Address:
Bit/Word Device type Format Range Memo
B LB dddd 0 ~ 9998
W LW dddd 0 ~ 9998
W RW ddddd 0 ~ 55536
Wiring Diagram:
The following represents the cable end connector.
eMT3000 series
COM1 RS232 9P COM3 RS232 9P RS232 9P D-Sub
D-Sub Female D-Sub Female FeMale
2 RX 8 RX TXD
3 TX 7 TX RXD
5 GND 5 GND GND
RTS
circuit
CTS
76
PLC Connection Guide
MT6000/8000 series except MT6050i/MT8050i
COM1 RS232 9P COM2 RS232 9P COM3 RS232 9P RS232 9P D-Sub
D-Sub Female D-Sub Female D-Sub Male FeMale
2 RX 6 RX 8 RX TXD
3 TX 4 TX 7 TX RXD
5 GND 5 GND 5 GND GND
RTS
circuit
CTS
MT6050i/MT8050i
COM1 RS232 9P RS232 9P D-Sub
D-Sub Female FeMale
9 RX TXD
6 TX RXD
5 GND GND
RTS
circuit
CTS
77
PLC Connection Guide
MT6000/8000 series except MT6050i/MT8050i
COM1 RS485 2W COM3 RS485 2W RS485 2W 9P D-Sub
9P D-Sub Male 9P D-Sub Male Male
1 RX- 6 Data- 8 D-
2 RX+ 9 Data+ 3 D+
5 GND 5 GND 5 GND
MT6050i/MT8050i
COM1 RS485 2W COM3 RS485 2W RS485 2W 9P D-Sub
9P D-Sub Female 9P D-Sub Female Male
1 RX- 7 Data- 8 D-
2 RX+ 8 Data+ 3 D+
5 GND 5 GND 5 GND
Driver Version:
Version Date Description
V1.00 Dec/8/2008 Driver released
78
PLC Connection Guide
Website: http://www.emersonnetworkpower.com.cn/Pages/Default.aspx
HMI Setting:
Parameters Recommended Options Notes
PLC type EMERSON Charge Module
PLC I/F RS-232
Baud rate 9600
Data bits 8
Parity Odd
Stop bits 1
PLC sta. no. 1
Device Address:
Bit/Word Device type Format Range Memo
B Float_Point_Forced D 0~1
B Average_Point_Forced D 0~1
W Switch_Status D 0~1
W Manual_Status D 0~1
W Protect_Status D 0~1
W Failure_Status D 0~1
W Preset_Voltage D 0~1
W Preset_Percent D 0~1
W Output_Voltage D 0~1
W Output_Current D 0~1
W High_Limit D 0~1
W Low_Limit D 0~1
W Float_Point_Setting D 0~1
W Average_Point_Setting D 0~1
79
PLC Connection Guide
Wiring Diagram:
The following represents the cable end connector.
eMT3000 series
COM1 RS232 9P COM3 RS232 9P RS232 terminal
D-Sub Female D-Sub Female
2 RX 8 RX TXD
3 TX 7 TX RXD
5 GND 5 GND GND
MT6050i/MT8050i
COM1 RS232 9P RS232 terminal
D-Sub Female
9 RX TXD
6 TX RXD
5 GND GND
Driver Version:
Version Date Description
V1.00 Mar/3/2009
80
PLC Connection Guide
HMI Setting:
Parameters Recommended Options Notes
PLC type EMERSON PLC EC20
PLC I/F RS232
Baud rate 9600 9600, 19200, 115200
Data bits 8 7 or 8
Parity Even Even, Odd, None
Stop bits 1 1 or 2
PLC sta. no. 0 0-255
PLC Setting:
Communication mode Modbus RTU protocol
Device Address:
Bit/Word Device type Format Range Memo
B Y OOO 0 ~ 377 0000-02550
B X OOO 0 ~ 377 1200-01455 0000-0255
B M DDDD 0 ~ 1999 2000-3999
B SM DDD 0~ 255 4400-4655
B S DDD 0 ~ 991 6000-6991
B T DDD 0 ~ 255 8000-8255
B C DDD 0 ~ 255 9200-9455
W D DDDD 0 ~ 7999 0000-7999
W SD DDD 0 ~ 255 8000-8255
W Z DD 0 ~ 15 8500-8515
W T DDD 0 ~ 255 9000-9255
W C DDD 0 ~ 199 9500-9699
DW C_Double DDD 200 ~ 255 9700-9811
DW D_Double DDDD 0 ~ 7998 0000-7999
81
PLC Connection Guide
Wiring Diagram:
The following represents the cable end connector.
eMT3000 series
COM1 RS232 9P COM3 RS232 9P Emerson EC20 COM1
D-Sub Female D-Sub Female terminal
2 RX 8 RX TXD
3 TX 7 TX RXD
5 GND 5 GND GND
MT6050i/MT8050i
COM1 RS232 9P Emerson EC20 COM1
D-Sub Female terminal
9 RX TXD
6 TX RXD
5 GND GND
Driver Version:
Version Date Description
V1.10 Dec/30/2008
82
PLC Connection Guide
FATEK FB Series
Supported Series: FATEK FBs series, FB MC series, and FB MA series need FB-DTBR
converter.
Website: http://www.fatek.com/
HMI Setting:
Parameters Recommended Options Notes
PLC type FATEK FB Series
PLC I/F RS232 RS232/RS485
Baud rate 9600 /Ethernet
Data bits 7
Parity Even
Stop bits 1
PLC sta. no. 1 0-255 Must match PLC port setting.
TCP port no. 500 Ethernet only.
Device Address:
Bit/Word Device type Format Range Memo
B X DDDD 0 ~ 9999 Input
B Y DDDD 0 ~ 9999 Output
B M DDDD 0 ~ 9999 Internal Relay
B S DDDD 0 ~ 9999 Step Relay
B T DDDD 0 ~ 9999 Timer
B C DDDD 0 ~ 9999 Counter
B PLC_MODE D 0 PLC mode
B R_Bit DDDDdd 0 ~ 999915
B D_Bit DDDDdd 0 ~ 999915
W RT DDDD 0 ~ 9999 Timer Register
W RC DDDD 0 ~ 9999 Counter Register
W R DDDD 0 ~ 9999 Data Register
W D DDDD 0 ~ 9999 Data Register
W DRT DDDD 0 ~ 9999 Double Word Timer Register
W DRC DDD 200 ~ 255 Double Word Counter Register
W WX DDDD 0 ~ 9999 Input Word
W WY DDDD 0 ~ 9999 Output Word
83
PLC Connection Guide
Bit/Word Device type Format Range Memo
W WM DDDD 0 ~ 9999 Internal Relay Word
W WS DDDD 0 ~ 9999
W FR DDDD 0 ~ 9999
Wiring Diagram:
The following represents the cable end connector.
9P D-Sub to 4P Mini-DIN: FBs Port0
eMT3000 series
COM1 RS232 9P COM3 RS232 9P FBs RS232 4P Mini-DIN
D-Sub Female D-Sub Female Male
2 RX 8 RX 3 TX
3 TX 7 TX 4 RX
5 GND 5 GND 2 GND
84
PLC Connection Guide
MT6050i/MT8050i
COM1 RS232 9P FBs RS232 4P Mini-DIN
D-Sub Female Male
9 RX 3 TX
6 TX 4 RX
5 GND 2 GND
85
PLC Connection Guide
MT6050i/MT8050i
COM1 RS232 9P FBs communication
D-Sub Female module RS232 9P
D-Sub Male
9 RX 2 TX
6 TX 3 RX
5 GND 5 GND
86
PLC Connection Guide
MT6050i/MT8050i
COM1 RS485 2W COM3 RS485 2W FBs communication
9P D-Sub Female 9P D-Sub Female module 3P Terminal
1 RX- 7 Data- D-
2 RX+ 8 Data+ D+
5 GND 5 GND
87
PLC Connection Guide
MT6050i/MT8050i
COM1 RS232 9P FB CPU Port RS232
D-Sub Female 15P D-Sub Male
9 RX 2 TX
6 TX 1 RX
5 GND 6 GND
3 RTS
circuit
4 CTS
88
PLC Connection Guide
MT6050i/MT8050i
COM1 RS485 2W COM3 RS485 2W FB CPU Port RS485
9P D-Sub Female 9P D-Sub Female 2W 15P D-Sub Male
1 RX- 7 Data- 7 D-
2 RX+ 8 Data+ 5 D+
5 GND 5 GND
Driver Version:
Version Date Description
V1.60 Feb/17/2011 R_Bit, D_Bit and WS address types are added.
V1.70 Nov/29/2011 FR address types are added.
89
PLC Connection Guide
Fuji NB Series
Website: http://www.fujielectric.co.jp/fcs/eng/
HMI Setting:
Parameters Recommended Options Notes
PLC type Fuji NB Series
PLC I/F RS485 4W
Baud rate 19200
Data bits 8
Parity Odd
Stop bits 1
PLC sta. no. 0
PLC Setting:
Communication mode NITP Protocol / PLC Password (default is 0)
Device Address:
Bit/Word Device type Format Range Memo
B Y HHH 0 ~ 7ff Output Relay
B X HHH 0 ~ 3ff Input Relay
B M HHH 0 ~ fff Internal Relay
B L HHH 0 ~ fff Latch Relay
B C HH 0 - ff Counter
B M_Spe HHHH 0 ~ 81ff Special Relay
B T HHH 0 ~ 1ff Timer
W TV HHH 0 ~ 3ff Timer value
W CV HHH 0 ~ 3ff Counter value
W D HHHH 0 ~ 1fff Data Register
W D_Spe HHHH 0 ~ 81ff Special Register
90
PLC Connection Guide
Wiring Diagram:
The following represents the cable end connector.
eMT3000 series
COM1 RS485 4W Fuji NB Series RS422
9P D-Sub Male 8P RJ45 Male
1 RX- 4 TX-
2 RX+ 3 TX+
3 TX- 6 RX-
4 TX+ 5 RX+
5 GND
MT6050i/MT8050i
COM1 RS485 4W Fuji NB Series RS422
9P D-Sub Female 8P RJ45 Male
1 RX- 4 TX-
2 RX+ 3 TX+
3 TX- 6 RX-
4 TX+ 5 RX+
5 GND
91
PLC Connection Guide
Driver Version:
Version Date Description
V1.10 May/05/2009
92
PLC Connection Guide
GE FANUC 0i MD
Website: http://www.fanucfa.com/welcome_worldwide/
HMI Setting:
Parameters Recommended Options Notes
PLC type GE FANUC 0i MD
PLC I/F RS232
Baud rate 19200
Data bits 8
Parity Even
Stop bits 1
PLC sta. no. 0
PLC Setting:
Reader/Puncher interface (2ch.) is used for touch panel interface.
External touch panel interface, S/N: A02B-0320-J685, for Power Mate Series.
Device Address:
Bit/Word Device type Format Range Memo
B X DDDDo 0 ~ 11277
B Y DDDDo 0 ~ 11277
B K DDDo 0 ~ 9997
B E DDDDo 0 ~ 99997
B D_Bit DDDDo 0 ~ 99997
B R_Bit DDDDo 0 ~ 94997
W T DDDD 0 ~ 9499 Must be a multiple of 2
W C DDDD 0 ~ 5199 Must be a multiple of 4
W D_Byte DDDD 0 ~ 9999
W R_Byte DDDD 0 ~ 9499
W D DDDD 0 ~ 9999 Must be a multiple of 2
W R DDDD 0 ~ 9499 Must be a multiple of 2
93
PLC Connection Guide
Wiring Diagram:
The following represents the cable end connector.
eMT3000 series
COM1 RS232 9P COM3 RS232 9P RS232 20P JD36B or
D-Sub Female D-Sub Female JD54 Female
2 RX 8 RX 11 TX
3 TX 7 TX 1 RX
5 GND 5 GND 8(JD36) 4(JD54) GND
15 RTS
circuit
05 CTS
03 DR
07 CD circuit
13 ER
94
PLC Connection Guide
MT6050i/MT8050i
COM1 RS232 9P RS232 20P JD36B or
D-Sub Female JD54 Female
9 RX 11 TX
6 TX 1 RX
5 GND 8(JD36) 4(JD54) GND
15 RTS
circuit
05 CTS
03 DR
07 CD circuit
13 ER
Driver Version:
Version Date Description
V1.00 May/16/2011 Driver released.
95
PLC Connection Guide
GE Fanuc CMM
Website: http://www.ge.com
HMI Setting:
Parameters Recommended Options Notes
PLC type GE Fanuc CMM
PLC I/F RS232 RS232/RS485
9600,19200,38400,5
Baud rate 19200
7600,115200
Must set to 8 for this
Data bits 8 7,8
protocol
Parity Odd Even, Odd, None
Stop bits 1 1, 2
Does not apply to this
PLC sta. no. 0 0-255
protocol
PLC Setting:
Refer to the related PLC manual.
Device Address:
Bit/Word Device type Format Range Memo
B I DDDDD 1 ~ 10000 Input relay
B Q DDDDD 1 ~ 10000 Output relay
B M DDDDD 1 ~ 10000 Auxiliary relay
B G DDDD 1 ~ 7680
B T DDD 1 ~ 256
B SA DDD 1 ~ 128
B SB DDD 1 ~ 128
B SC DDD 1 ~ 128
B S DDD 1 ~ 128
W AI DDDDD 1 ~ 10000 Analog input register
W AQ DDDDD 1 ~ 10000 Analog output register
W R DDDDD 1 ~ 32640 Data register
96
PLC Connection Guide
Wiring Diagram:
The following represents the cable end connector.
CPU Port 90-30/VersaMax
eMT3000 series
COM1 RS485 4W 90-30/VersaMax RS485
9P D-Sub Male 4W 15P D-Sub Male
1 RX- 12 SDA
2 RX+ 13 SDB
5 GND 7 GND
3 TX- 10 RDA
4 TX+ 11 RDB
circuit
9 RT
6 RTSA
circuit
15 CTSA
8 RTSB
circuit
14 CTSB
97
PLC Connection Guide
MT6050i/MT8050i
COM1 RS485 4W 90-30/VersaMax RS485
9P D-Sub Female 4W 15P D-Sub Male
1 RX- 12 SDA
2 RX+ 13 SDB
5 GND 7 GND
3 TX- 10 RDA
4 TX+ 11 RDB
circuit
9 RT
6 RTSA
circuit
15 CTSA
8 RTSB
circuit
14 CTSB
98
PLC Connection Guide
MT6050i/MT8050i
COM1 RS232 9P 90-30/90-70 series
D-Sub Female RS232 6P RJ11 Male
9 RX 2 TX
6 TX 5 RX
5 GND 3 GND
99
PLC Connection Guide
MT6050i/MT8050i
COM1 RS232 9P VersaMax series RS232
D-Sub Female 9P D-Sub Male
9 RX 2 TX
6 TX 3 RX
5 GND 5 GND
Driver Version:
Version Date Description
V1.00 Jul/09/2009 Driver released.
100
PLC Connection Guide
GE FANUC RX3i
Website: http://www.ge.com
HMI Setting:
Parameters Recommended Options Notes
PLC type GE FANUC RX3i
PLC I/F RS232 RS232, RS485
Baud rate 19200 1200~115200
Data bits 8
Parity Odd None, Even, Odd
Stop bits 1 1 or 2
PLC sta. no. 1 1~99
PLC Setting:
Refer to the related PLC manual.
Device Address:
Bit/Word Device type Format Range Memo
B I DDDDD 1 ~ 32768
B Q DDDDD 1 ~ 32768
B M DDDDD 1 ~ 32768
B G DDDDD 1 ~ 32768
B T DDDDD 1 ~ 32768
B SA DDDDD 1 ~ 32768
B SB DDDDD 1 ~ 32768
B SC DDDDD 1 ~ 32768
B S DDDDD 1 ~ 32768
W AI DDDDD 1 ~ 32768
W AQ DDDDD 1 ~ 32768
W R DDDDD 1 ~ 32768
101
PLC Connection Guide
Wiring Diagram:
The following represents the cable end connector.
eMT3000 series
COM1 RS232 9P COM3 RS232 9P GE Fanuc RX3i COM1
D-Sub Female D-Sub Female RS232 9P D-Sub Male
2 RX 8 RX 2 TXD
3 TX 7 TX 3 RXD
5 GND 5 GND 5 GND
MT6050i/MT8050i
COM1 RS232 9P GE Fanuc RX3i COM1
D-Sub Female RS232 9P D-Sub Male
9 RX 2 TXD
6 TX 3 RXD
5 GND 5 GND
102
PLC Connection Guide
103
PLC Connection Guide
MT6050i/MT8050i
COM1 RS485 4W GE Fanuc RX3i COM2
9P D-Sub Female RS232 15P D-Sub Male
1 RX- 12 SDA
2 RX+ 13 SDB
5 GND 7 GND
3 TX- 10 RDA
4 TX+ 11 RDB
circuit
9 RT
6 RTSA
circuit
15 CTSA
8 RTSB
circuit
14 CTSB
Driver Version:
Version Date Description
V1.10 Oct/01/2010 Driver released.
104
PLC Connection Guide
HMI Setting:
Parameters Recommended Options Notes
PLC type GE Fanuc Series 90-30 (Ethernet)
PLC I/F Ethernet
Port no. 18245
PLC sta. no. 1 1~99
Device Address:
Bit/Word Device type Format Range Memo
B I_bit DDDDD 1 ~ 32768
B Q_bit DDDDD 1 ~ 32768
B M_bit DDDDD 1 ~ 32768
B G_bit DDDDD 1 ~ 32768
B T_bit DDDDD 1 ~ 32768
B SA_bit DDDDD 1 ~ 32768 Read Only
B SB_bit DDDDD 1 ~ 32768 Read Only
B SC_bit DDDDD 1 ~ 32768 Read Only
B S_bit DDDDD 1 ~ 32768 Read Only
B R_bit DDDDD 1 ~ 32768
Address increment by 8 words, ex: I1,
W I DDDDD 1 ~ 32753
I9, I17, I25…..
The rule is same as above, ex:Q1, Q9,
W Q DDDDD 1 ~ 32753
Q17…
The rule is same as above, ex:M1,
W M DDDDD 1 ~ 32753
M9, M17..
The rule is same as above, ex:G1, G9,
W G DDDDD 1 ~ 32753
G17…
The rule is same as above, ex:T1, T9,
W T DDDD 1 ~ 1024
T17….
W SA DDDDD 1 ~ 32753 Read only, the rule is same as above
W SB DDDDD 1 ~ 32753 Read only, the rule is same as above
105
PLC Connection Guide
Wiring Diagram:
Direct connect (crossover cable):
HMI RJ45 Male Wire Color PLC RJ45 Male
1 TX+ White/Orange 3 RX+
2 TX- Orange 6 RX-
3 RX+ White/Green 1 TX+
4 BD4+ Blue 4 BD4+
5 BD4- White/Blue 5 BD4-
6 RX- Green 2 TX-
7 BD3+ White/Brown 7 BD3+
8 BD3- Brown 8 BD3-
Through a hub:
HMI RJ45 Male Wire Color PLC RJ45 Male
1 TX+ White/Orange 1 TX+
2 TX- Orange 2 TX-
3 RX+ White/Green 3 RX+
4 BD4+ Blue 4 BD4+
5 BD4- White/Blue 5 BD4-
6 RX- Green 6 RX-
7 BD3+ White/Brown 7 BD3+
8 BD3- Brown 8 BD3-
106
PLC Connection Guide
Driver Version:
Version Date Description
V1.70 Apr/09/2010
V1.80 Nov/09/2011 Add device type : R_bit
V1.90 Jan/17/2012 Add device type : W
107
PLC Connection Guide
GE Fanuc SNP-X
Supported Series: GE Fanuc 90 & VersaMax series PLC
Website: http://www.ge.com
HMI Setting:
Parameters Recommended Options Notes
PLC type GE Fanuc SNP-X
PLC I/F RS485 4w RS232/RS485
9600, 19200, 38400,
Baud rate 19200
57600, 115200
Data bits 8 7, 8 Must set to 8 for this protocol
Parity Odd Even, Odd, None
Stop bits 1 1, 2
PLC sta. no. 0 0-255 Does not apply to this protocol
PLC Setting:
Refer to the related PLC manual.
Device Address:
Bit/Word Device type Format Range Memo
B I DDDDD 1 ~ 10000 Input relay
B Q DDDDD 1 ~ 10000 Output relay
B M DDDDD 1 ~ 10000 Auxiliary relay
B G DDDD 1 ~ 7680
B T DDD 1 ~ 256
B SA DDD 1 ~ 128
B SB DDD 1 ~ 128
B SC DDD 1 ~ 128
B S DDD 1 ~ 128
W AI DDDDD 1 ~ 10000 Analog input register
W AQ DDDDD 1 ~ 10000 Analog output register
W R DDDDD 1 ~ 32640 Data register
108
PLC Connection Guide
Wiring Diagram:
The following represents the cable end connector.
CPU Port (90-30/VersaMax)
eMT3000 series
COM1 RS485 4W 90-30/VersaMax RS422
9P D-Sub Male 15P D-Sub Male
1 RX- 12 SDA
2 RX+ 13 SDB
5 GND 7 GND
3 TX- 10 RDA
4 TX+ 11 RDB
circuit
9 RT
6 RTSA
circuit
15 CTSA
8 RTSB
circuit
14 CTSB
109
PLC Connection Guide
MT6050i/MT8050i
COM1 RS485 4W 90-30/VersaMax RS422
9P D-Sub Female 15P D-Sub Male
1 RX- 12 SDA
2 RX+ 13 SDB
5 GND 7 GND
3 TX- 10 RDA
4 TX+ 11 RDB
circuit
9 RT
6 RTSA
circuit
15 CTSA
8 RTSB
circuit
14 CTSB
110
PLC Connection Guide
MT6050i/MT8050i
COM1 RS232 9P 90-30/90-70 series
D-Sub Female RS232 6P RJ11 Male
9 RX 2 TX
6 TX 5 RX
5 GND 3 GND
111
PLC Connection Guide
MT6050i/MT8050i
COM1 RS232 9P VersaMax series RS232
D-Sub Female 9P D-Sub Male
9 RX 2 TX
6 TX 3 RX
5 GND 5 GND
Driver Version:
Version Date Description
V1.20 Jan/09/2009
112
PLC Connection Guide
Haiwell PLC
Support Series: E series, S series and H series.
Web: http://www.haiwell.com/
HMI Setting:
Parameters Recommended Options Notes
PLC type Haiwell PLC
PLC I/F RS232 RS232,RS485 2W
Baud rate 19200 19200
Data bits 8 8
Parity None None
Stop bits 2 2
PLC sta. no. 1 1~247
Device Address:
Bit/Word Device type Format Range Memo
B X DDDD 0 ~ 1023 Input Switch
B Y DDDD 0 ~ 1023 Output Switch
B M DDDDD 0 ~ 12287 Internal Relay
B T DDDD 0 ~ 1023 Timer (Output Coil State)
B C DDD 0 ~ 255 Timer (Output Coil State)
B SM DDD 0 ~ 215 System Status Bit
B S DDDD 0 ~ 2047 Step Bit
Special Module Parameter
W CR DD 0 ~ 79
Register
W AI DDD 0 ~ 255 Analog Input Register
W AQ DDD 0 ~ 255 Analog Output Register
W V DDDDD 0 ~ 14847 Data Register
W TCV DDDD 0 ~ 1023 Timer (current value register)
W CCV DDD 0 ~ 255 Timer (current value register)
W SV DDD 0 ~ 154 System Register
113
PLC Connection Guide
Wiring Diagram:
The following represents the cable end connector.
eMT3000 series
COM1 RS232 9P COM3 RS232 9P RS232 4P Mini-DIN
D-Sub Female D-Sub Female Male
2 RX 8 RX 2 TX
3 TX 7 TX 1 RX
5 GND 5 GND 3 GND
MT6050i/MT8050i
COM1 RS232 9P RS232 4P Mini-DIN
D-Sub Female Male
9 RX 2 TX
6 TX 1 RX
5 GND 3 GND
114
PLC Connection Guide
eMT3000 series
COM1 RS485 2W COM3 RS485 2W RS485 2W Terminal
9P D-Sub Male 9P D-Sub Male
1 RX- 6 Data- B- Data+
2 RX+ 9 Data+ A+ Data-
5 GND 5 GND
MT6050i/MT8050i
COM1 RS485 2W COM3 RS485 2W RS485 2W Terminal
9P D-Sub Female 9P D-Sub Female
1 RX- 7 Data- B- Data+
2 RX+ 8 Data+ A+ Data-
5 GND 5 GND
Driver Version:
Version Date Description
V1.00 Mar/2/2012 Driver released.
115
PLC Connection Guide
Hanyoung Controller
Supported Series: Temperature Controller.
Website: http://hynux.com/kor/
HMI Setting:
Parameters Recommended Options Notes
PLC type Hanyoung Controller
PLC I/F RS485 4W
Baud rate 9600
Data bits 8 7 or 8
Parity None Even, Odd, None
Stop bits 1 1 or 2
PLC sta. no. 1 0-255
*In System Parameter Settings / Device Settings / COM Settings, set Parameter 1 to “1” to
support Check Sum Mode.
116
PLC Connection Guide
Device Address:
Bit/Word Device type Format Range Memo
B I DDDD 1 ~ 9999
W D DDDD 1 ~ 9999
Wiring Diagram:
The following represents the cable end connector.
eMT3000 series
COM1 RS485 4W Han Young RS422
9P D-Sub Male terminal
1 RX- 32 TX-
2 RX+ 31 TX+
3 TX- 34 RX-
4 TX+ 33 RX+
5 GND
117
PLC Connection Guide
MT6050i/MT8050i
COM1 RS485 4W Han Young RS422
9P D-Sub Female terminal
1 RX- 32 TX-
2 RX+ 31 TX+
3 TX- 34 RX-
4 TX+ 33 RX+
5 GND
Driver Version:
Version Date Description
V1.60 Jun/14/2010
118
PLC Connection Guide
HAWE PLVC
Supported Series: HAWE PLVC
Website: http://www.hawe.de/de/home/
HMI Setting:
Parameters Recommended Options Notes
PLC type HAWE PLVC
PLC I/F RS232
Baud rate 9600
Data bits 8
Parity None
Stop bits 1
PLC sta. no. 0
Device Address:
Bit/Word Device type Format Range Memo
B X HHHH 0 ~ ffff Input Bits
B Y HHHH 0 ~ ffff Output Bits
B M DDDDD 0 ~ 65535 Internal Relays
B T DDDDD 0 ~ 65535
B C DDDDD 0 ~ 65535
B B HHHH 0 ~ ffff
B F DDDDD 0 ~ 65535
W TV DDDDD 0 ~ 65535 Timer Preset Value
W CV DDDDD 0 ~ 65535 Counter Preset Value
W D DDDDD 0 ~ 65535 Data Registers
W W HHHH 0 ~ ffff
W R DDDDD 0 ~ 65535
119
PLC Connection Guide
Wiring Diagram:
The following represents the cable end connector.
eMT3000 series
COM1 RS232 9P COM3 RS232 9P RS232 terminal
D-Sub Female D-Sub Female
2 RX 8 RX TXD
3 TX 7 TX RXD
5 GND 5 GND GND
MT6050i/MT8050i
COM1 RS232 9P RS232 terminal
D-Sub Female
9 RX TXD
6 TX RXD
5 GND GND
Driver Version:
Version Date Description
V1.00 Sep/17/2009
120
PLC Connection Guide
Website: http://www.tjhysensor.cn/
HMI Setting:
Parameters Recommended Options Notes
PLC type Heng Yuan EU series
PLC I/F RS485 2W
Baud rate 9600
Data bits 8
Parity Even
Stop bits 1
PLC sta. no. 2 1-31
Device Address:
Bit/Word Device type Format Range Memo
W Parameter DDDD 0 ~ 2000
Wiring Diagram:
The following represents the cable end connector.
eMT3000 series
COM1 RS485 2W COM3 RS485 2W Heng Yuan Sensor
9P D-Sub Male 9P D-Sub Male RS485
1 RX- 6 Data- 7 RX- (Yellow)
2 RX+ 9 Data+ 6 RX+ (Green)
5 GND 5 GND 4 GND (Black)
121
PLC Connection Guide
MT6000/8000 series except MT6050i/MT8050i
COM1 RS485 2W COM3 RS485 2W Heng Yuan Sensor
9P D-Sub Male 9P D-Sub Male RS485
1 RX- 6 Data- 7 RX- (Yellow)
2 RX+ 9 Data+ 6 RX+ (Green)
5 GND 5 GND 4 GND (Black)
MT6050i/MT8050i
COM1 RS485 2W COM3 RS485 2W Heng Yuan Sensor
9P D-Sub Female 9P D-Sub Female RS485
1 RX- 7 Data- 7 RX- (Yellow)
2 RX+ 8 Data+ 6 RX+ (Green)
5 GND 5 GND 4 GND (Black)
Driver Version:
Version Date Description
V1.00 Dec/30/2008 Driver released.
122
PLC Connection Guide
Hitachi EH-SIO
HMI Setting:
Parameters Recommended Options Notes
PLC type Hitachi EH-SIO
PLC I/F RS232 RS232, RS485
Baud rate 19200 9600, 19200, 38400
Data bits 7 7
Parity Even Even
Stop bits 1 1
PLC sta. no. 0
PLC Setting:
Communication mode 19200, E, 7, 1 (default)
Device Address:
Bit/Word Device type Format Range Memo
B X HHHHh 0 ~ fffff External input-bit (X)
B Y HHHHh 0 ~ fffff External output-bit (Y)
B M HHHHh 0 ~ fffff Data area-bit (M)
B T HHHHh 0 ~ fffff Timer (T)
B R HHHHh 0 ~ fffff Internal output (R)
B L HHHHh 0 ~ fffff Link area-bit (L)
W TC HH 0 ~ ff Timer/Counter current value
W WM HHHH 0 ~ 270f Data area-word (M)
W WX HHHH 0 ~ 270f External input-word (X)
W WY HHHH 0 ~ 270f External output-word (Y)
W WR HHHH 0 ~ 270f Internal output-word (R)
W WL HHHH 0 ~ 270f Link area-word (L)
123
PLC Connection Guide
Wiring Diagram:
The following represents the cable end connector.
EH-SIO port1/port 2 RS232
eMT3000 series
COM1 RS232 9P COM3 RS232 9P RS232 8P RJ45 Male
D-Sub Female D-Sub Female
2 RX 8 RX 5 SD
3 TX 7 TX 6 RD
5 GND 5 GND 1 SG
8 CTS 8 RS
4 PHL
circuit
7 DR
124
PLC Connection Guide
MT6050i/MT8050i
COM1 RS232 9P RS232 8P RJ45 Male
D-Sub Female
9 RX 5 SD
6 TX 6 RD
5 GND 1 SG
8 RS
4 PHL
circuit
7 DR
125
PLC Connection Guide
MT6050i/MT8050i
COM1 RS485 4W Hitachi EH-SIO
9P D-Sub Female
1 RX- 2 TX-
2 RX+ 1 TX+
3 TX- 4 RX-
4 TX+ 3 RX+
5 GND 6 SG
126
PLC Connection Guide
MT6050i/MT8050i
COM1 RS485 2W COM3 RS485 2W Hitachi EH-SIO
9P D-Sub Female 9P D-Sub Female
1 RX- 7 Data- 2 TX-
circuit
4 RX-
2 RX+ 8 Data+ 1 TX+
circuit
3 RX+
5 GND 5 GND 6 SG
Driver Version:
Version Date Description
V1.00 May/25/2010 Driver released.
127
PLC Connection Guide
Website: http://www.hitachi-ies.co.jp/english/products/plc/index.htm
HMI Setting:
Parameters Recommended Options Notes
PLC type Hitachi EHV Series (Ethernet)
PLC I/F Ethernet
Port no. 3004 3004~3007
Device Address:
Bit/Word Device type Format Range Memo
B X HHHHh 0 ~ fffff External input-bit (X)
B Y HHHHh 0 ~ fffff External output-bit (Y)
B M HHHHh 0 ~ fffff Data area-bit (M)
B T DDDDD 0 ~ 65535 Timer (T)
B R HHHHh 0 ~ fffff Internal output (R)
B L HHHHh 0 ~ fffff Link area-bit (L)
W TC DDDD 0 ~ 2559 Timer/Counter current value
W WM HHHH 0 ~ 7fff Data area-word (M)
W WX HHHH 0 ~ ffff External Input-word (X)
W WY HHHH 0 ~ ffff External output-word (Y)
W WR HHHH 0 ~ ffff Internal output-word (R)
W WL HHHH 0 ~ 73ff Link area-word (L)
128
PLC Connection Guide
Wiring Diagram:
Direct connect (crossover cable):
HMI RJ45 Male Wire Color PLC RJ45 Male
1 TX+ White/Orange 3 RX+
2 TX- Orange 6 RX-
3 RX+ White/Green 1 TX+
4 BD4+ Blue 4 BD4+
5 BD4- White/Blue 5 BD4-
6 RX- Green 2 TX-
7 BD3+ White/Brown 7 BD3+
8 BD3- Brown 8 BD3-
Through a hub:
HMI RJ45 Male Wire Color PLC RJ45 Male
1 TX+ White/Orange 1 TX+
2 TX- Orange 2 TX-
3 RX+ White/Green 3 RX+
4 BD4+ Blue 4 BD4+
5 BD4- White/Blue 5 BD4-
6 RX- Green 6 RX-
7 BD3+ White/Brown 7 BD3+
8 BD3- Brown 8 BD3-
Driver Version:
Version Date Description
V1.00 Jan/12/2010 Driver released
129
PLC Connection Guide
Website: http://www.hitachi-ies.co.jp/english/products/plc/index.htm
HMI Setting:
Parameters Recommended Options Notes
PLC type Hitachi H/EH/EHV Series
PLC I/F RS232 RS232, RS485
Baud rate 19200 9600, 19200, 38400
Data bits 7 7
Parity Even Even
Stop bits 1 1
Does not apply to this
PLC sta. no. 0 0-255
protocol.
Device Address:
Bit/Word Device type Format Range Memo
B X HHHHh 0 ~ fffff External input-bit (X)
B Y HHHHh 0 ~ fffff External output-bit (Y)
B M HHHHh 0 ~ fffff Data area-bit (M)
B T HHHHh 0 ~ fffff Timer (T)
B R HHHHh 0 ~ fffff Internal output (R)
B L HHHHh 0 ~ fffff Link area-bit (L)
W TC HH 0 ~ ff Timer/Counter current value
W WM HHHH 0 ~ 270f Data area-word (M)
W WX HHHH 0 ~ 270f External input-word (X)
W WY HHHH 0 ~ 270f External output-word (Y)
W WR HHHH 0 ~ c3ff Internal output-word (R)
W WL HHHH 0 ~ 270f Link area-word (L)
130
PLC Connection Guide
Wiring Diagram:
WARNING: If your communication cable is not wired exactly as shown in our cable
assembly instructions, damage to the HMI or loss of communications can be caused.
Switch Number
1 OFF Normal mode
2 OFF TRNS0 operation
3, 4 3 4 Port1 transmission speed
ON ON 4,800 bps Doesn’t support
OFF ON 9,600 bps
ON OFF 19,200 bps Default
OFF OFF 38,400 bps
5 ON Dedicated port
6 6 PHL Port2 transmission speed
ON Low 9,600 bps Toggle-Switch
ON High 38,400 bps PHL
OFF Low 4,800 bps Doesn’t support Low
OFF High 19,200 bps Default
7 OFF (System mode) Do not turn on. PHL
8 OFF (System mode) Do not turn on. High
131
PLC Connection Guide
The following represents the cable end connector.
EH-150 port1/port 2 RS232 / MICRO-EH port1 RS232
eMT3000 series
COM1 RS232 9P COM3 RS232 9P RS232 8P RJ45 Male
D-Sub Female D-Sub Female
2 RX 8 RX 5 SD
3 TX 7 TX 6 RD
5 GND 5 GND 1 SG
8 CTS 8 RS
4 PHL
circuit
7 DR
MT6050i/MT8050i
COM1 RS232 9P RS232 8P RJ45 Male
D-Sub Female
9 RX 5 SD
6 TX 6 RD
5 GND 1 SG
8 RS
4 PHL
circuit
7 DR
132
PLC Connection Guide
The following represents the cable end connector.
EH-150 port1 RS485 4W
eMT3000 series
COM1 RS485 4W RS485 4W 8P RJ45
9P D-Sub Male Male
1 RX- 5 TX-
2 RX+ 4 TX+
3 TX- 6 RX-
4 TX+ 7 RX+
5 GND 1 SG
MT6050i/MT8050i
COM1 RS485 4W RS485 4W 8P RJ45
9P D-Sub Female Male
1 RX- 5 TX-
2 RX+ 4 TX+
3 TX- 6 RX-
4 TX+ 7 RX+
5 GND 1 SG
133
PLC Connection Guide
The following represents the cable end connector.
EH-150 port1 RS485 2W
eMT3000 series
COM1 RS485 2W COM3 RS485 2W RS485 2W 8P RJ45
9P D-Sub Male 9P D-Sub Male Male
1 RX- 6 Data- 4 TX+
circuit
7 RX+
2 RX+ 9 Data+ 5 TX-
circuit
6 RX-
5 GND 5 GND 1 SG
MT6050i/MT8050i
COM1 RS485 2W COM3 RS485 2W RS485 2W 8P RJ45
9P D-Sub Female 9P D-Sub Female Male
1 RX- 7 Data- 4 TX+
circuit
7 RX+
2 RX+ 8 Data+ 5 TX-
circuit
6 RX-
5 GND 5 GND 1 SG
134
PLC Connection Guide
The following represents the cable end connector.
H Series CPU Port RS232
eMT3000 series
COM1 RS232 9P COM3 RS232 9P RS232 15P D-Sub Male
D-Sub Female D-Sub Female
2 RX 8 RX 2 TXD
3 TX 7 TX 3 RXD
5 GND 5 GND 9 SG
circuit
10 SG
8 CTS 4 RTS
5 CTS
7 DSR
circuit
8 PHL
14 PV12
135
PLC Connection Guide
MT6050i/MT8050i
COM1 RS232 9P RS232 15P D-Sub Male
D-Sub Female
9 RX 5 SD
6 TX 6 RD
5 GND 1 SG
circuit
8 RS
5 CTS
7 DSR
circuit
8 PHL
14 PV12
Driver Version:
Version Date Description
V1.10 Oct/22/2009 Fixed HMI occupies the control right of CPU module.
V1.30 Mar/22/2010
136
PLC Connection Guide
HUST H4X
Supported Series: HUST CNC Controller H4 Series.
Website: http://www.hust.com.tw/
HMI Setting:
Parameters Recommended Options Notes
PLC type HUST H4X
PLC I/F RS-232 CPU port
Baud rate 38400 9600,19200,38400,57600
Data bits 7
Parity Even
Stop bits 2
Turn around delay 5
PLC sta. no. 1
Device Address:
Bit/Word Device type Format Range Memo
Mapping to VM 10800 ~ 10807 (read
B I DDD 0 ~ 255
only)
Mapping to VM 10808 ~ 10815 (read
B O DDD 0 ~ 255
only)
Mapping to VM 10816 ~ 10823 (read
B C DDD 0 ~ 255
only)
Mapping to VM 10824 ~ 10831 (read
B S DDD 0 ~ 255
only)
Mapping to VM 10832 ~ 10863 (read
B A DDD 0 ~ 255
only)
137
PLC Connection Guide
Wiring Diagram:
The following represents the cable end connector.
eMT3000 series
COM1 RS232 9P COM3 RS232 9P HUST CNC Controller
D-Sub Female D-Sub Female RS232 D-Sub Male
2 RX 8 RX 2 TXD
3 TX 7 TX 3 RXD
5 GND 5 GND 5 GND
MT6050i/MT8050i
COM1 RS232 9P HUST CNC Controller
D-Sub Female RS232 D-Sub Male
9 RX 2 TXD
6 TX 3 RXD
5 GND 5 GND
Driver Version:
Version Date Description
V2.01 Sep/29/2009
138
PLC Connection Guide
Website: http://www.iai-robot.co.jp/
HMI Setting:
Parameters Recommended Options Notes
PLC type IAI X-SEL CONTROLLER
PLC I/F RS232
Baud rate 9600 9600~19200
Data bits 7 7 or 8
Parity None Even, Odd, None
Stop bits 1 1 or 2
PLC sta. no. 0
Device Address:
Bit/Word Device type Format Range Memo
Address 1~8 represent the corresponding
W Servo_On_Off H 1~8 axis.
Write 1 means ON and 0 means OFF.
Address 1~8 represent the corresponding
W Servo_Origin H 1~8 axis.
Back to origin.
For reading current position. The state of
current axis is put in RW axis*100.
W CurrentAxisPos H 1~8
i.e., for the state of axis 2, 2*100=200, so it
is in RW200.
Data written indicates which program to
W RunProgram H 0
run.
Data written indicates which program to
W EndProgram H 0
stop.
Address 1~8 represent the corresponding
axis. The data written indicates which point
W PointMove H 0~8 to reach. Put parameters ACC, DEC,
SPEED in axis*100+1, axis*100+2 and
axis*100+3 respectively.
139
PLC Connection Guide
Bit/Word Device type Format Range Memo
Jogging. Address 1~8 represent the
corresponding axis. Put parameters ACC,
W JoggingMove H 0~8 DEC, SPEED and Position in axis*100+11,
axis*100+12, axis*100+13 and
axis*100+14 respectively.
Jog to the set absolute coordinate. Address
1~8 represent the corresponding axis. Put
W AbsoluteMove H 0~8 parameters ACC, DEC, SPEED and
Position in axis*100+21, axis*100+22,
axis*100+23 and axis*100+24 respectively.
To change the value of the point. Address
1~8 represent the corresponding axis. Put
W PointChange H 0~8 parameters ACC, DEC, SPEED and
Position in axis*100+31, axis*100+32,
axis*100+33 and axis*100+34 respectively.
W SoftWareReset H 0 Reset soft ware.
Note: ddd: Decimal, hhh: Hexadecimal, ooo: Octal.
Each model of CPU is different; it is recommended to refer to PLC Manual Device List.
Wiring Diagram:
The following represents the cable end connector.
eMT3000 series
COM1 RS232 9P COM3 RS232 9P Host RS232 D-Sub
D-Sub Female D-Sub Female Female
2 RX 8 RX 3 TX
3 TX 7 TX 2 RX
5 GND 5 GND 5 GND
140
PLC Connection Guide
MT6000/8000 series except MT6050i/MT8050i
COM1 RS232 9P COM2 RS232 9P COM3 RS232 9P Host RS232 D-Sub
D-Sub Female D-Sub Female D-Sub Male Female
2 RX 6 RX 8 RX 3 TX
3 TX 4 TX 7 TX 2 RX
5 GND 5 GND 5 GND 5 GND
MT6050i/MT8050i
COM1 RS232 9P Host RS232 D-Sub
D-Sub Female Female
9 RX 3 TX
6 TX 2 RX
5 GND 5 GND
Driver Version:
Version Date Description
V1.00 Jun/01/2010 Driver released.
141
PLC Connection Guide
IDEC Micro
Supported Series: IDEC Micro3, Micro3C, MicroSmart, OpenNet Controller series.
Website: http://www.idec.com
HMI Setting:
Parameters Recommended Options Notes
PLC type IDEC Micro
PLC I/F RS232 RS232, RS485
Baud rate 9600 9600, 19200
Data bits 7 7, 8
Parity Even Even, Odd, None
Stop bits 1 1
255 (for 1:1 255 or same as the PLC
PLC sta. no. 0-255
connect) setting
PLC Setting:
Communication mode 9600, E, 7, 1 (default), Use Computer Link Protocol
Device Address:
Bit/Word Device type Format Range Memo
B X DDDDo 0 ~ 20477 Input (I)
B Y DDDDo 0 ~ 20477 Output (Q)
B M DDDDo 0 ~ 20477 Internal Relay (M)
W RT DDDD 0 ~ 9999 Timer (T)
W RC DDDD 0 ~ 9999 Counter (C)
W D DDDD 0 ~ 9999 Data Register (D)
142
PLC Connection Guide
Wiring Diagram:
The following represents the cable end connector.
Micro3C, MicroSmart, OpenNet Controller CPU Ladder Port
eMT3000 series
COM1 RS232 9P COM3 RS232 9P Port1 or Port2 RS232
D-Sub Female D-Sub Female 8P Mini-DIN Male
2 RX 8 RX 3 TXD
3 TX 7 TX 4 RXD
5 GND 5 GND 7 GND
MT6050i/MT8050i
COM1 RS232 9P Port1 or Port2 RS232
D-Sub Female 8P Mini-DIN Male
9 RX 3 TXD
6 TX 4 RXD
5 GND 7 GND
143
PLC Connection Guide
The following represents the cable end connector.
Micro3 CPU Port, MicroSmart with FC4A-PC2 RS485 Communication Adapter
eMT3000 series
COM1 RS485 2W COM3 RS485 2W RS485 8P Mini-DIN
9P D-Sub Male 9P D-Sub Male Male
1 RX- 6 Data- 2 RXD-
2 RX+ 9 Data+ 1 RXD+
5 GND 5 GND 7 GND
MT6050i/MT8050i
COM1 RS485 2W COM3 RS485 2W RS485 8P Mini-DIN
9P D-Sub Female 9P D-Sub Female Male
1 RX- 7 Data- 2 RXD-
2 RX+ 8 Data+ 1 RXD+
5 GND 5 GND 7 GND
144
PLC Connection Guide
The following represents the cable end connector.
Micro3C, OpenNet Controller Data Link Terminals,MicroSmart with FC4A-PC3 RS485
Communication Adapter
eMT3000 series
COM1 RS485 2W COM3 RS485 2W Data Link Terminal
9P D-Sub Male 9P D-Sub Male
1 RX- 6 Data- A RXD-
2 RX+ 9 Data+ B RXD+
5 GND 5 GND SG GND
MT6050i/MT8050i
COM1 RS485 2W COM3 RS485 2W Data Link Terminal
9P D-Sub Female 9P D-Sub Female
1 RX- 7 Data- A RXD-
2 RX+ 8 Data+ B RXD+
5 GND 5 GND SG GND
Driver Version:
Version Date Description
V1.20 Jun/19/2009
145
PLC Connection Guide
Inovance H2U/H1U
Website: http://www.inovance.cn/
HMI Setting:
Parameters Recommended Options Notes
PLC type Inovance H2U/H1U
PLC I/F RS485 4W
Baud rate 9600 9600~19200
Data bits 7 7 or 8
Parity Even Even, Odd, None
Stop bits 1 1 or 2
PLC sta. no. 0
Device Address:
Bit/Word Device type Format Range Memo
B X OOO 0 ~ 377 Input Bits
B Y OOO 0 ~ 377 Output Bits
B M DDDD 0 ~ 7999 Auxiliary Relay
B T DDD 0 ~ 255 Timer Relay
B C DDD 0 ~ 255 Counter Relay
B SM DDDD 8000 ~ 9999 Special Auxiliary Relay
B D_Bit DDDDdd 0 ~ 799915
B S DDDD 0 ~ 4095
W TV DDD 0 ~ 255 Timer Memory
W CV DDD 0 ~ 199 Counter Memory
W D DDDD 0 ~ 7999 Data Registers
DW CV2 DDD 200 ~ 255 Counter Memory (32bit)
W SD DDDD 8000 ~ 9999 Special Data Register
Note: ddd: Decimal, hhh: Hexadecimal, ooo: Octal.
Each model of CPU is different, it is recommended to refer to PLC Manual Device List.
146
PLC Connection Guide
Wiring Diagram:
The following represents the cable end connector.
eMT3000 series
COM1 RS485 4W H2U/H1U RS422 8P
9P D-Sub Male Mini-DIN Male
1 RX- 4 TX-
2 RX+ 7 TX+
3 TX- 1 RX-
4 TX+ 2 RX+
5 GND 3 GND
MT6050i/MT8050i
COM1 RS485 4W H2U/H1U RS422 8P
9P D-Sub Female Mini-DIN Male
1 RX- 4 TX-
2 RX+ 7 TX+
3 TX- 1 RX-
4 TX+ 2 RX+
5 GND 3 GND
147
PLC Connection Guide
Driver Version:
Version Date Description
V1.00 May/19/2010 Driver released.
148
PLC Connection Guide
Justfi Controller
Supported Series: Justfi weighing instruments, Industrial Batching Controller supports
XK31CB4, XK31CB6.
Website: http://www.justfi.com
HMI Setting:
Parameters Recommended Options Notes
PLC type Justfi controller
PLC I/F RS232
Baud rate 9600 9600, 19200
Data bits 7 7 or 8
Parity Even Even, Odd, None
Stop bits 1 1 or 2
PLC sta. no. 1
Device Address:
Bit/Word Device type Format Range Memo
W Func DD 0 ~ 99 Read / Write
DW Func_DW DD 0 ~ 99 Read / Write
W RW H 0 Weight (read only)
W RF H 0 Read result (read only)
W RT H 0 Read total (read only)
W RG H 0 Read prescription group
W RC H 0 Circle
W RB H 0 Read status (read only)
W MZ H 0 Zero (write only)
W MT H 0 Tare (write only)
W CT H 0 Clear tare (write only)
W DT H 0 Clear total (write only)
W BB H 0 Start (write only)
W HB H 0 Stop (write only)
W BD H 0 Discharge (write only)
RP1t
W …. H 0 Read/Write recipe
RP6F
149
PLC Connection Guide
Wiring Diagram:
The following represents the cable end connector.
eMT3000 series
COM1 RS232 9P COM3 RS232 9P CB4 RS232
D-Sub Female D-Sub Female
2 RX 8 RX TD
3 TX 7 TX RD
5 GND 5 GND GND
MT6050i/MT8050i
COM1 RS232 9P CB4 RS232
D-Sub Female
9 RX TD
6 TX RD
5 GND GND
Driver Version:
Version Date Description
V1.40 Nov/04/2009
150
PLC Connection Guide
Website: http://www.kernel.modena.it/
HMI Setting:
Parameters Recommended Options Notes
PLC type Kernel sistemi DMX Series
PLC I/F RS232 RS485
Baud rate 19200 9600
Data bits 8
Parity None
Stop bits 1
Must match the PLC port
PLC sta. no. 1
setting
Device Address:
Bit/Word Device type Format Range Memo
W D HHHH 0 ~ ffff
Wiring Diagram:
The following represents the cable end connector.
eMT3000 series
COM1 RS232 9P COM3 RS232 9P DMX30 RS232 9P
D-Sub Female D-Sub Female D-Sub Male
2 RX 8 RX 3 TX
3 TX 7 TX 2 RX
5 GND 5 GND 5 GND
151
PLC Connection Guide
MT6000/8000 series except MT6050i/MT8050i
COM1 RS232 9P COM2 RS232 9P COM3 RS232 9P DMX30 RS232 9P
D-Sub Female D-Sub Female D-Sub Male D-Sub Male
2 RX 6 RX 8 RX 3 TX
3 TX 4 TX 7 TX 2 RX
5 GND 5 GND 5 GND 5 GND
MT6050i/MT8050i
COM1 RS232 9P DMX30 RS232 9P
D-Sub Female D-Sub Male
9 RX 3 TX
6 TX 2 RX
5 GND 5 GND
Driver Version:
Version Date Description
V1.00 Feb/06/2010 Driver releasesd.
152
PLC Connection Guide
Website: http://www.keyence.com/
HMI Setting:
Parameters Recommended Options Notes
PLC type KEYENCE KV-10/16/24/40/80/Visual KV Series
PLC I/F RS232 RS232
Baud rate 9600
Data bits 8
Parity Even
Stop bits 1
PLC sta. no. 0
Device Address:
Bit/Word Device type Format Range Memo
B RLY DDDdd0* 0 ~ 655150* dd:0 ~ 15
B DM_Bit DDDDDh 0 ~ 65535f
W DM DDDDD 0 ~ 65535
W TM DDDD 0 ~ 8999
W T DDDD 0 ~ 9999
W T_Curr DDDD 0 ~ 9999 Timer_Current
W T_Preset DDDD 0 ~ 9999
W C DDDD 0 ~ 9999
W C_Curr DDDD 0 ~ 9999 Counter_Current
W C_Preset DDDD 0 ~ 9999
Note:*
If Relay (bit) register is used, please place a zero at the end of the address.
For example, to read Relay (bit) 100, the address is written as “1000”.
153
PLC Connection Guide
Wiring Diagram:
The following represents the cable end connector.
RS232 CPU Port:
eMT3000 series
COM1 RS232 9P COM3 RS232 9P OP-26486 9P D-Sub
D-Sub Female D-Sub Female Male
2 RX 8 RX 3 TXD
3 TX 7 TX 2 RXD
5 GND 5 GND 5 GND
MT6050i/MT8050i
COM1 RS232 9P OP-26486 9P D-Sub
D-Sub Female Male
9 RX 3 TXD
6 TX 2 RXD
5 GND 5 GND
154
PLC Connection Guide
The following represents the cable end connector.
9P D-Sub to 6P RJ11:
eMT3000 series
COM1 RS232 9P COM3 RS232 9P RS232 6P RJ11 Male
D-Sub Female D-Sub Female
2 RX 8 RX 2 TXD
3 TX 7 TX 4 RXD
5 GND 5 GND 3 GND
MT6050i/MT8050i
COM1 RS232 9P RS232 6P RJ11 Male
D-Sub Female
9 RX 2 TXD
6 TX 4 RXD
5 GND 3 GND
Driver Version:
Version Date Description
V1.40 Apr/17/2009
155
PLC Connection Guide
HMI Setting:
Parameters Recommended Options Notes
PLC type KEYENCE KV-5000 (Ethernet)
PLC I/F Ethernet
Port no. 8501
PLC sta. no. 0
Device Address:
Bit/Word Device type Format Range Memo
B MR DDDdd 0 ~ 99915
B LR DDDdd 0 ~ 99915
B CR DDDdd 0 ~ 99915
B RLY DDDdd 0 ~ 99915
W DM DDDDD 0 ~ 65535
W TM DDDD 0 ~ 9999
W T DDDD 0 ~ 9999
W T_Curr DDDD 0 ~ 9999 Timer Current
W T_Preset DDDD 0 ~ 9999 Timer Preset
W C DDDD 0 ~ 9999
W C_Curr DDDD 0 ~ 9999
W C_Preset DDDD 0 ~ 9999
W CM DDDDD 0 ~ 65535
W EM DDDDD 0 ~ 65535
W FM DDDDD 0 ~ 65535
Note:
If RLY (bit) register is used, please place a zero at the end of the address.
For example, to read RLY 100, the address is written as “1000”.
156
PLC Connection Guide
Wiring Diagram:
Direct connect (crossover cable):
HMI RJ45 Male Wire Color PLC RJ45 Male
1 TX+ White/Orange 3 RX+
2 TX- Orange 6 RX-
3 RX+ White/Green 1 TX+
4 BD4+ Blue 4 BD4+
5 BD4- White/Blue 5 BD4-
6 RX- Green 2 TX-
7 BD3+ White/Brown 7 BD3+
8 BD3- Brown 8 BD3-
Through a hub:
HMI RJ45 Male Wire Color PLC RJ45 Male
1 TX+ White/Orange 1 TX+
2 TX- Orange 2 TX-
3 RX+ White/Green 3 RX+
4 BD4+ Blue 4 BD4+
5 BD4- White/Blue 5 BD4-
6 RX- Green 6 RX-
7 BD3+ White/Brown 7 BD3+
8 BD3- Brown 8 BD3-
Driver Version:
Version Date Description
V1.00 Dec/25/2009 Driver released.
157
PLC Connection Guide
HMI Setting:
Parameters Recommended Options Notes
PLC type KEYENCE KV-700/1000/3000/5000 Series
PLC I/F RS232 RS232
Baud rate 115200
Data bits 8
Parity Even
Stop bits 1
PLC sta. no. 0
Device Address:
Bit/Word Device type Format Range Memo
B MR DDDdd 0 ~ 99915
B LR DDDdd 0 ~ 99915
B CR DDDdd 0 ~ 99915
B RLY DDDdd 0 ~ 99915
W DM DDDDD 0 ~ 65535
W TM DDDD 0 ~ 9999
W T DDDD 0 ~ 9999
W T_Curr DDDD 0 ~ 9999 Timer_Current
W T_Preset DDDD 0 ~ 9999
W C DDDD 0 ~ 9999
W C_Curr DDDD 0 ~ 9999 Counter_Current
W C_Preset DDDD 0 ~ 9999
W CM DDDDD 0 ~ 65535
W EM DDDDD 0 ~ 65535
W FM DDDDD 0 ~ 65535
Note:
If Relay (bit) register is used, please place a zero at the end of the address.
For example, to read Relay (bit) 100, the address is written as “1000”.
158
PLC Connection Guide
Wiring Diagram:
The following represents the cable end connector.
eMT3000 series
COM1 RS232 9P COM3 RS232 9P OP-26486 9P D-Sub
D-Sub Female D-Sub Female Male
2 RX 8 RX 3 TXD
3 TX 7 TX 2 RXD
5 GND 5 GND 5 GND
MT6050i/MT8050i
COM1 RS232 9P OP-26486 9P D-Sub
D-Sub Female Male
9 RX 3 TXD
6 TX 2 RXD
5 GND 5 GND
Driver Version:
Version Date Description
V2.20 Jul/28/2009
159
PLC Connection Guide
Korenix 6550
Website: http://www.korenix.com/
HMI Setting:
Parameters Recommended Options Notes
PLC type Korenix 6550 Modbus protocol
PLC I/F Ethernet
Port no. 502
PLC sta. no. 0
Device Address:
Bit/Word Device type Format Range Memo
B 1x DDDDD 1 ~ 65535
B 0x DDDDD 1 ~ 65535
B 3x_Bit DDDDDdd 100 ~ 6553515
B 4x_Bit DDDDDdd 100 ~ 6553515
B 6x_Bit DDDDDdd 100 ~ 6553515
W 3x DDDDD 1 ~ 65535
W 4x DDDDD 1 ~ 65535
W 5x DDDDD 1 ~ 65535
W 6x DDDDD 1 ~ 65535
160
PLC Connection Guide
Wiring Diagram:
Direct connect (crossover cable):
HMI RJ45 Male Wire Color PLC RJ45 Male
1 TX+ White/Orange 3 RX+
2 TX- Orange 6 RX-
3 RX+ White/Green 1 TX+
4 BD4+ Blue 4 BD4+
5 BD4- White/Blue 5 BD4-
6 RX- Green 2 TX-
7 BD3+ White/Brown 7 BD3+
8 BD3- Brown 8 BD3-
Through a hub:
HMI RJ45 Male Wire Color PLC RJ45 Male
1 TX+ White/Orange 1 TX+
2 TX- Orange 2 TX-
3 RX+ White/Green 3 RX+
4 BD4+ Blue 4 BD4+
5 BD4- White/Blue 5 BD4-
6 RX- Green 6 RX-
7 BD3+ White/Brown 7 BD3+
8 BD3- Brown 8 BD3-
Driver Version:
Version Date Description
V1.61 Apr/17/2009
161
PLC Connection Guide
KOYO CLICK
Supported Series: KOYO CLICK PLC series
Website: http://www.automationdirect.com
HMI Setting:
Parameters Recommended Options Notes
PLC type KOYO CLICK
PLC I/F RS232
Baud rate 38400 Com Port1 (fixed) Reference PLC Specification
Data bits 8 Com Port1 (fixed) Reference PLC Specification
Parity Odd Com Port1 (fixed) Reference PLC Specification
Stop bits 1 Com Port1 (fixed) Reference PLC Specification
PLC sta. no. 1 Com Port1 (fixed) Reference PLC Specification
Device Address:
Bit/Word Device type Format Range Memo
B X Ddd 001 ~ 816 Input Status (Read Only)
B Y Ddd 001 ~ 816 Output Status
B C DDDD 1 ~ 2000 Control Bit
B T DDD 1 ~ 500 Timer Status (Read Only)
B CT DDD 1 ~ 250 Counter Status (Read Only)
B SC DDDD 1 ~ 1000 System Control Bit (Read Only)
W DS DDDD 1 ~ 4500 Data Registers
W DD DDDD 1 ~ 1000 Data Registers (Double Word)
W DH DDD 1 ~ 500 Data Registers
W DF DDD 1 ~ 500 Data Registers (Double Word)
W XD D 0~8 Input Status Registers (Read Only)
W YD D 0~8 Output Status Registers
W TD DDD 1 ~ 500 Timer Current Values (Read Only)
Counter Current Values
W CTD DDD 1 ~ 250
(Double Word/Read Only)
System Data Registers
W SD DDDD 1 ~ 1000
(Read Only)
W TXT DDDD 1 ~ 1000 Text Data Registers
162
PLC Connection Guide
Wiring Diagram:
KOYO CLICK PLC Com Port:
163
PLC Connection Guide
MT6050i/MT8050i
COM1 RS232 9P RS232 6P RJ12 Male
D-Sub Female
9 RX 4 TXD
6 TX 3 RXD
5 GND 1 GND
Version:
Version Date Description
V1.50 Jun/22/2010
164
PLC Connection Guide
KOYO DIRECT
Supported Series: KOYO DirectLogic series PLC DL05, DL06, DL105, DL205, DL305, and
DL405 series.
Website: http://www.automationdirect.com
HMI Setting:
Parameters Recommended Options Notes
PLC type KOYO DIRECT
PLC I/F RS232 RS232, RS485
Baud rate 9600 9600, 19200, 38400
Data bits 8 7, 8
Parity Odd Even, Odd, None
Stop bits 1 1
PLC sta. no. 1 1-90
PLC Setting:
1. The PLC must not have a password.
2. PLC must be set for Full Duplex operation.
3. PLC must be set for No Hardware Handshaking.
4. The PLC must be set to use the ‘K’ Sequence Protocol.
5. Set the mode switch to the TERM mode.
6. When using the D4-440 CPU, the station number must be set to 1.
165
PLC Connection Guide
Device Address:
Bit/Word Device type Format Range Memo
B X OOOO 0 ~ 4000 Input Bits
B Y OOOO 0 ~ 4000 Output Bits
B C OOOOO 0 ~ 10000 Control Relays
B T OOOO 0 ~ 1000 Timer Status Bits
B CT OOOO 0 ~ 1000 Counter Status Bits
B S OOOO 0 ~ 2000
B SP OOOO 0 ~ 2000
B GX OOOOO 0 ~ 10000
B GY OOOOO 0 ~ 10000
W V OOOOO 0 ~ 77777 V Memory
W Timer OOOO 0 ~ 1000
W Counter OOOO 0 ~ 1000
Wiring Diagram:
The following represents the cable end connector.
DL05/DL06/DL105/DL230/DL240/DL250/DL350/DL450 RS232 port
eMT3000 series
COM1 RS232 9P COM3 RS232 9P KOYO CLICK PLC
D-Sub Female D-Sub Female RS232 6P RJ12 Male
2 RX 8 RX 4 TX
3 TX 7 TX 3 RX
5 GND 5 GND 1 GND
166
PLC Connection Guide
MT6050i/MT8050i
COM1 RS232 9P KOYO CLICK PLC
D-Sub Female RS232 6P RJ12 Male
9 RX 4 TX
6 TX 3 RX
5 GND 1 GND
167
PLC Connection Guide
MT6050i/MT8050i
COM1 RS232 9P RS232 Port2 15P
D-Sub Female D-Sub Male
9 RX 2 TX
6 TX 3 RX
5 GND 7 GND
4 RTC
circuit
5 CTS
168
PLC Connection Guide
MT6000/8000 series except MT6050i/MT8050i
COM1 RS485 4W RS422 Port2 15P
9P D-Sub Male D-Sub Male
1 RX- 10 TX-
2 RX+ 9 TX+
3 TX- 6 RX-
4 TX+ 13 RX+
5 GND 7 GND
11 RTS+
Circuit
14 CTS+
12 RTS-
Circuit
15 CTS-
MT6050i/MT8050i
COM1 RS485 4W RS422 Port2 15P
9P D-Sub Female D-Sub Male
1 RX- 10 TX-
2 RX+ 9 TX+
3 TX- 6 RX-
4 TX+ 13 RX+
5 GND 7 GND
11 RTS+
Circuit
14 CTS+
12 RTS-
Circuit
15 CTS-
169
PLC Connection Guide
The following represents the cable end connector.
DL430/DL440/DL450 CPU unit Port0 RS232
eMT3000 series
COM1 RS232 9P COM3 RS232 9P RS232 Port0 15P
D-Sub Female D-Sub Female D-Sub Male
2 RX 8 RX 2 TX
3 TX 7 TX 3 RX
5 GND 5 GND 13 GND
1 YOP
7 CTS circuit
2 YOM
4 ONLINE
circuit
14 GND
170
PLC Connection Guide
MT6050i/MT8050i
COM1 RS232 9P RS232 Port0 15P
D-Sub Female D-Sub Male
9 RX 2 TX
6 TX 3 RX
5 GND 13 GND
1 YOP
7 CTS circuit
2 YOM
4 ONLINE
circuit
14 GND
171
PLC Connection Guide
MT6000/8000 series except MT6050i/MT8050i
COM1 RS232 9P COM2 RS232 9P COM3 RS232 9P RS232 Port1 25P
D-Sub Female D-Sub Female D-Sub Male D-Sub Male
2 RX 6 RX 8 RX 2 TX
3 TX 4 TX 7 TX 3 RX
5 GND 5 GND 5 GND 7 GND
4 RTC
Circuit
5 CTS
MT6050i/MT8050i
COM1 RS232 9P RS232 Port1 25P
D-Sub Female D-Sub Male
9 RX 2 TX
6 TX 3 RX
5 GND 7 GND
4 RTC
Circuit
5 CTS
172
PLC Connection Guide
The following represents the cable end connector.
CPU unit: DL430/DL440/DL450 CPU unit Port1 & DL350 CPU unit Port2 RS422
eMT3000 series
COM1 RS485 4W RS422 Port 25P D-Sub
9P D-Sub Male Male
1 RX- 16 TX-
2 RX+ 14 TX+
3 TX- 10 RX-
4 TX+ 9 RX+
5 GND 7 GND
19 RTS+
Circuit
11 CTS+
18 RTS-
Circuit
23 CTS-
173
PLC Connection Guide
MT6050i/MT8050i
COM1 RS485 4W RS422 Port 25P D-Sub
9P D-Sub Female Male
1 RX- 16 TX-
2 RX+ 14 TX+
3 TX- 10 RX-
4 TX+ 9 RX+
5 GND 7 GND
19 RTS+
Circuit
11 CTS+
18 RTS-
Circuit
23 CTS-
174
PLC Connection Guide
MT6000/8000 series except MT6050i/MT8050i
COM1 RS485 4W RS422 Port3 25P
9P D-Sub Male D-Sub Male
1 RX- 13 TX-
2 RX+ 12 TX+
3 TX- 25 RX-
4 TX+ 24 RX+
5 GND 7 GND
MT6050i/MT8050i
COM1 RS485 4W RS422 Port3 25P
9P D-Sub Female D-Sub Male
1 RX- 13 TX-
2 RX+ 12 TX+
3 TX- 25 RX-
4 TX+ 24 RX+
5 GND 7 GND
175
PLC Connection Guide
MT6000/8000 series except MT6050i/MT8050i
COM1 RS232 9P COM2 RS232 9P COM3 RS232 9P RS232 Port 25P D-Sub
D-Sub Female D-Sub Female D-Sub Male Male
2 RX 6 RX 8 RX 2 TX
3 TX 4 TX 7 TX 3 RX
5 GND 5 GND 5 GND 7 GND
4 RTC
circuit
5 CTS
MT6050i/MT8050i
COM1 RS232 9P RS232 Port 25P D-Sub
D-Sub Female Male
9 RX 2 TX
6 TX 3 RX
5 GND 7 GND
4 RTC
circuit
5 CTS
Driver Version:
Version Date Description
V1.30 Nov/08/2010
176
PLC Connection Guide
KOYO Ethernet
Supported Series: KOYO DirectLogic series, model H0-ECOM100, H2-ECOM100.
Website: http://www.automationdirect.com
HMI Setting:
Parameters Recommended Options Notes
PLC type KOYO Ethernet
PLC I/F Ethernet UDP/IP
Port no. 28784
PLC sta. no. No need to set station no. 0
Device Address:
Bit/Word Device type Format Range Memo
B GX OOOO 0 ~ 3777 Global I/O
B X OOOO 0 ~ 1777 Real Word Inputs
B SP OOOO 0 ~ 1777 Special Purpose Relays
B GY OOOO 0 ~ 3777 More Global I/O
B Y OOOO 0 ~ 1777 Real Word Outputs
B C OOOO 0 ~ 3777 Control Relays
B S OOOO 0 ~ 1777 Stage Status Bits
B T OOO 0 ~ 377 Timer Status Bits
B CT OOO 0 ~ 377 Counter Status Bits
W V OOOOO 0 ~ 41237 V-memory
W CCM_32 HHH 1 ~ 200 GX, X, SP
W CCM_33 HHH 1 ~ 340 GY,Y,C,S,Y,CT,V
W CCM_31 HHHH 1 ~ 42a0 V
EasyBuilder device address ranges may be different from PLC extended mode, please
refer to EasyBuilder address range as above.
ddd:Decimal, hhh:Hexadecimal, ooo:Octal
177
PLC Connection Guide
Wiring Diagram:
Direct connect (crossover cable):
HMI RJ45 Male Wire Color PLC RJ45 Male
1 TX+ White/Orange 3 RX+
2 TX- Orange 6 RX-
3 RX+ White/Green 1 TX+
4 BD4+ Blue 4 BD4+
5 BD4- White/Blue 5 BD4-
6 RX- Green 2 TX-
7 BD3+ White/Brown 7 BD3+
8 BD3- Brown 8 BD3-
Through a hub:
HMI RJ45 Male Wire Color PLC RJ45 Male
1 TX+ White/Orange 1 TX+
2 TX- Orange 2 TX-
3 RX+ White/Green 3 RX+
4 BD4+ Blue 4 BD4+
5 BD4- White/Blue 5 BD4-
6 RX- Green 6 RX-
7 BD3+ White/Brown 7 BD3+
8 BD3- Brown 8 BD3-
Driver Version:
Version Date Description
V1.10 Jul/03/2009
178
PLC Connection Guide
Lenze
Supported Series: PLC Model No.: 9300/8200 series, and EPL10200
Pass-through 2102IB fieldbus module: RS485 (LECOM B)
Website: http://www.lenze.de
HMI Setting:
Parameters Recommended Options Notes
PLC type Lenze
PLC I/F RS232
Baud rate 9600 9600, 19200
Data bits 7 7,8
Parity None Even, Odd, None
Stop bits 1 1, 2
PLC sta. no. 1 0-255
PLC Setting:
Communication mode Same as the MT500 setting
Device Address:
Bit/Word Device type Format Range Memo
Subcode not supported.
B CNB DDDDdd 0 ~ 999915 Can only read/write CNI
Word Type.
Subcode supported.
B CB DDDDddxx 0 ~ 81920015 Can only read/write CI
Word Type.
DDDDdd Subcode supported.
W CI 0 ~ 819200 Integer
DDDDdd 0 ~ 819200 Subcode supported.
W CD DWord
DDDDdd 0 ~ 819200 Subcode supported.
W CF DWord (float point)
Subcode not supported.
W CNI DDDD 0 ~ 9999 Integer
Subcode not supported.
W CND DDDD 0 ~ 9999 DWord
Subcode not supported.
W CNF DDDD 0 ~ 9999 DWord (float point)
179
PLC Connection Guide
Wiring Diagram:
The following represents the cable end connector.
Lenze 2102IB LECOM-B RS485 plug-in terminal 4-pole
eMT3000 series
COM1 RS485 2W COM3 RS485 2W RS485 terminal
9P D-Sub Male 9P D-Sub Male
1 RX- 6 Data- 72 T/R (A)
2 RX+ 9 Data+ 71 T/R (B)
5 GND 5 GND
MT6050i/MT8050i
COM1 RS485 2W COM3 RS485 2W RS485 terminal
9P D-Sub Female 9P D-Sub Female
1 RX- 7 Data- 72 T/R (A)
2 RX+ 8 Data+ 71 T/R (B)
5 GND 5 GND
Driver Version:
Version Date Description
V1.20 Sep/6/2011
180
PLC Connection Guide
LingYan BMS
Website: http://www.lyeda.com/Project_file/bms01.htm
HMI Setting:
Parameters Recommended Options Notes
PLC type LingYan BMS
PLC I/F RS232
Baud rate 9600
Data bits 8
Parity None
Stop bits 1
PLC sta. no. 0
Device Address:
Bit/Word Device type Format Range Memo
W Battery_Unit D 0
W Insulator_Unit D 0
W Switch_Unit D 0
Wiring Diagram:
The following represents the cable end connector.
eMT3000 series
COM1 RS232 9P COM3 RS232 9P RS232 4P Terminal
D-Sub Female D-Sub Female
2 RX 8 RX 1 TXD
3 TX 7 TX 3 RXD
5 GND 5 GND 4 GND
181
PLC Connection Guide
MT6000/8000 series except MT6050i/MT8050i
COM1 RS232 9P COM2 RS232 9P COM3 RS232 9P RS232 4P Terminal
D-Sub Female D-Sub Female D-Sub Male
2 RX 6 RX 8 RX 1 TXD
3 TX 4 TX 7 TX 3 RXD
5 GND 5 GND 5 GND 4 GND
MT6050i/MT8050i
COM1 RS232 9P RS232 4P Terminal
D-Sub Female
9 RX 1 TXD
6 TX 3 RXD
5 GND 4 GND
Driver Version:
Version Date Description
V1.10 Nov/12/2009
182
PLC Connection Guide
LIYAN EX series
Supported Series: LIYAN PLC Ex/Ex1s/Ex1n/Ex2n series
Website: http://www.liyanplc.com/
HMI Setting:
Parameters Recommended Options Notes
PLC type Mitsubishi FX0s/FX0n/FX1s/FX1n/FX2
PLC I/F RS232 RS232
Baud rate 9600 9600~115200
Data bits 7 7,8
Parity Even Even, Odd, None
Stop bits 1 1,2
Must match the PLC port
PLC sta. no. 0 0-255
setting.
Device Address:
Bit/Word Device type Format Range Memo
B X ooo 0 ~ 377 Input Relay
B Y ooo 0 ~ 377 Output Relay
B M ddd 0 ~ 9999 Internal Bit Memory
B T ddd 0 ~ 255 Timer Bit Memory
B C ddd 0 ~ 255 Counter Bit Memory
W TV ddd 0 ~ 255 Timer Register
W CV ddd 0 ~ 199 Counter Register
W D ddd 0 ~ 9999 Data Register
W CV2 ddd 200 ~ 255 Counter Register (Double Word)
W SD ddd 8000 ~ 9999 Special Data Register
183
PLC Connection Guide
Wiring Diagram:
The following represents the cable end connector.
9P D-Sub to 8P Mini-DIN: Ex, Ex1s, Ex1n, Ex2n series
eMT3000 series
COM1 RS232 9P COM3 RS232 9P RS232 8P Mini-DIN
D-Sub Female D-Sub Female Male
2 RX 8 RX 2 TXD
3 TX 7 TX 7 RXD
5 GND 5 GND 6 GND
MT6050i/MT8050i
COM1 RS232 9P RS232 8P Mini-DIN
D-Sub Female Male
9 RX 2 TXD
6 TX 7 RXD
5 GND 6 GND
Driver Version:
Version Date Description
V1.20 Oct/26/2011
184
PLC Connection Guide
LoXin
Website: http://www.loxin-china.com
HMI Setting:
Parameters Recommended Options Notes
PLC type LoXin
PLC I/F RS-485 2W
Baud rate 9600
Data bits 8
Parity Odd
Stop bits 1
PLC sta. no. 0
Device Address:
Bit/Word Device type Format Range Memo
W Battery_Unit D 0
W Insulator_Unit D 0
W Switch_Unit D 0
Wiring Diagram:
The following represents the cable end connector.
eMT3000 series
COM1 RS485 2W COM3 RS485 2W RS485 terminal
9P D-Sub Male 9P D-Sub Male
1 RX- 6 Data- D-
2 RX+ 9 Data+ D+
5 GND 5 GND
185
PLC Connection Guide
MT6000/8000 series except MT6050i/MT8050i
COM1 RS485 2W COM3 RS485 2W RS485 terminal
9P D-Sub Male 9P D-Sub Male
1 RX- 6 Data- D-
2 RX+ 9 Data+ D+
5 GND 5 GND
MT6050i/MT8050i
COM1 RS485 2W COM3 RS485 2W RS485 terminal
9P D-Sub Female 9P D-Sub Female
1 RX- 7 Data- D-
2 RX+ 8 Data+ D+
5 GND 5 GND
Driver Version:
Version Date Description
V1.00 Oct/16/2008
186
PLC Connection Guide
LS GLOFA Cnet
Supported Series: LS GLOFA GM6/GM7 CPU port. G7L-CUEB / G6L-CUEB / G4L-CUEA
/ G3L-CUEA Cnet module
Website: http://www.lgis.com/
HMI Setting:
Parameters Recommended Options Notes
PLC type LS GLOFA Cnet
PLC I/F RS232 RS232/RS485 2W/4W
Baud rate 9600 9600~115200
Data bits 8 7, 8
Parity None Even, Odd, None
Stop bits 1 1
PLC sta. no. 0 0~31
PLC Setting:
Communication mode 9600,N,8,1 (default), Cnet protocol
Communication module Applicable mode: 1 dedicated communication
Device Address:
Bit/Word Device type Format Range Memo
B MX DDDDD 0 ~ 32767 Internal Relay
B IX ddDdd 0 ~ 63763 Input
B QX ddDdd 0 ~ 63763 Output
W MW DDDDD 0 ~ 32767 Data Register
DW MD DDDDD 0 ~ 16383 Double Word
187
PLC Connection Guide
Wiring Diagram:
The following represents the cable end connector.
9P D-Sub to 9P D-Sub:
eMT3000 series
COM1 RS232 9P COM3 RS232 9P RS232 9P D-Sub Male
D-Sub Female D-Sub Female
2 RX 8 RX 7 TXD
3 TX 7 TX 4 RXD
5 GND 5 GND 5 GND
MT6050i/MT8050i
COM1 RS232 9P RS232 9P D-Sub Male
D-Sub Female
9 RX 7 TXD
6 TX 4 RXD
5 GND 5 GND
188
PLC Connection Guide
The following represents the cable end connector.
9P D-Sub to 9P D-Sub: Communication Module (G7L-CUEB / G6L-CUEB / G4L-CUEA /
G3L-CUEA Cnet RS232)
eMT3000 series
COM1 RS232 9P COM3 RS232 9P RS232 9P D-Sub Male
D-Sub Female D-Sub Female
2 RX 8 RX 3 TXD
3 TX 7 TX 2 RXD
5 GND 5 GND 5 GND
1 CD
7 RTS circuit
8 CTS
4 DTR
circuit
6 DSR
189
PLC Connection Guide
MT6050i/MT8050i
COM1 RS232 9P RS232 9P D-Sub Male
D-Sub Female
9 RX 3 TXD
6 TX 2 RXD
5 GND 5 GND
1 CD
7 RTS circuit
8 CTS
4 DTR
circuit
6 DSR
190
PLC Connection Guide
MT6000/8000 series except MT6050i/MT8050i
COM1 RS485 4W RS422 terminal
9P D-Sub Male
1 RX- SDB
2 RX+ SDA
3 TX- RDB
4 TX+ RDA
5 GND GND
MT6050i/MT8050i
COM1 RS485 4W RS422 terminal
9P D-Sub Female
1 RX- SDB
2 RX+ SDA
3 TX- RDB
4 TX+ RDA
5 GND GND
Driver Version:
Version Date Description
V1.80 Jun/08/2010
191
PLC Connection Guide
Website: http://www.lgis.com/
HMI Setting:
Parameters Recommended Options Notes
PLC type LS GLOFA FEnet (Ethernet)
PLC I/F Ethernet
Port no. 2004
PLC sta. no. 0 0~31
Device Address:
Bit/Word Device type Format Range Memo
B MX DDDDDD 0 ~ 131056 Internal Relay
B IX ddDdd 0 ~ 63763 Input
B QX ddDdd 0 ~ 63763 Output
W MW DDDD 0 ~ 8191 Data Register
DW MD DDDD 0 ~ 4095 Double Word
192
PLC Connection Guide
Wiring Diagram:
Direct connect (crossover cable):
HMI RJ45 Male Wire Color PLC RJ45 Male
1 TX+ White/Orange 3 RX+
2 TX- Orange 6 RX-
3 RX+ White/Green 1 TX+
4 BD4+ Blue 4 BD4+
5 BD4- White/Blue 5 BD4-
6 RX- Green 2 TX-
7 BD3+ White/Brown 7 BD3+
8 BD3- Brown 8 BD3-
Through a hub:
HMI RJ45 Male Wire Color PLC RJ45 Male
1 TX+ White/Orange 1 TX+
2 TX- Orange 2 TX-
3 RX+ White/Green 3 RX+
4 BD4+ Blue 4 BD4+
5 BD4- White/Blue 5 BD4-
6 RX- Green 6 RX-
7 BD3+ White/Brown 7 BD3+
8 BD3- Brown 8 BD3-
Driver Version:
Version Date Description
V1.00 Apr/02/2009 Driver released.
193
PLC Connection Guide
Website: http://www.lgis.com/
HMI Setting:
Parameters Recommended Options Notes
PLC type LS GLOFA GM3467 (LOADER)
PLC I/F RS232
Baud rate 38400
Data bits 8
Parity None
Stop bits 1
PLC sta. no. 1
Device Address:
Bit/Word Device type Format Range Memo
B MX DDDDDD 0 ~ 524272
00.0.0 ~ 63.7.63
B IX ddDdd 0 ~ 63763
(dd.D.dd)
00.0.0 ~ 63.7.63
B QX ddDdd 0 ~ 63763
(dd.D.dd)
W IW HHH 0 ~ 273
W QW HHH 0 ~ 273
W MW DDDDD 0 ~ 32767
W MD DDDDD 0 ~ 16383
194
PLC Connection Guide
Wiring Diagram:
The following represents the cable end connector.
eMT3000 series
COM1 RS232 9P COM3 RS232 9P LS GLOFA series
D-Sub Female D-Sub Female RS232 9P D-Sub Male
2 RX 8 RX 3 TD
3 TX 7 TX 2 RD
5 GND 5 GND 5 GND
MT6050i/MT8050i
COM1 RS232 9P LS GLOFA series
D-Sub Female RS232 9P D-Sub Male
9 RX 3 TD
6 TX 2 RD
5 GND 5 GND
Driver Version:
Version Date Description
V1.30 Mar/08/2010
195
PLC Connection Guide
LS MASTER-K Cnet
Supported Series: LS MASTER-K series: K80S, K200S, K300S, and K1000S
Website: http://www.lgis.com/
HMI Setting:
Parameters Recommended Options Notes
PLC type LS MASTER-K Cnet
PLC I/F RS232 RS232/RS485
Baud rate 38400 9600, 19200, 38400
Data bits 8 8
Parity None Even, Odd, None
Stop bits 1 1
Must match the PLC port
PLC sta. no. 0 0-31
setting.
Device Address:
Bit/Word Device type Format Range Memo
B P DDDh 0 ~ 255f I/O Relay (P)
B K DDDh 0 ~ 255f Keep Relay (K)
B M DDDh 0 ~ 255f Auxiliary Relay (M)
B L DDDh 0 ~ 255f Link Relay (L)
B F DDDh 0 ~ 255f Special Relay (F)
B D_bit DDDDh 0 ~ 9999f D_bit
W TV DDD 0 ~ 255 Timer Present Value
W CV DDD 0 ~ 255 Counter Present Value
W D DDDD 0 ~ 9999 Data Register (D)
W M_word DDD 0 ~ 255 Word type for M
W L_word DDD 0 ~ 255 Word type for L
W F_word DDD 0 ~ 255 Word type for F
196
PLC Connection Guide
Wiring Diagram:
The following represents the cable end connector.
eMT3000 series
COM1 RS232 9P COM3 RS232 9P CPU Port Cnet I/F
D-Sub Female D-Sub Female RS232 9P D-Sub Male
2 RX 8 RX 7 TX
3 TX 7 TX 4 RX
5 GND 5 GND 5 GND
MT6050i/MT8050i
COM1 RS232 9P CPU Port Cnet I/F
D-Sub Female RS232 9P D-Sub Male
9 RX 7 TX
6 TX 4 RX
5 GND 5 GND
Driver Version:
Version Date Description
V1.00 Apr/19/2010 Driver released.
V1.10 May/11/2011 Added registers: D_bit, M_word, F_word, L_word
197
PLC Connection Guide
Website: http://www.lgis.com/
HMI Setting:
Parameters Recommended Options Notes
PLC type LG MASTER-K CPU Direct
PLC I/F RS232 RS232/RS485
Baud rate 38400 9600, 19200, 38400
Data bits 8 8
Parity None Even, Odd, None
Stop bits 1 1
Must match the PLC port
PLC sta. no. 0 0-31
setting.
Device Address:
Bit/Word Device type Format Range Memo
B P DDDh 0 ~ 255f I/O Relay (P)
B K DDDh 0 ~ 255f Keep Relay (K)
B M DDDh 0 ~ 255f Auxiliary Relay (M)
B L DDDh 0 ~ 255f Link Relay (L)
B F DDDh 0 ~ 255f Special Relay (F)
B D_bit DDDDh 0 ~ 9999f D_bit
W TV DDD 0 ~ 255 Timer Present Value
W CV DDD 0 ~ 255 Counter Present Value
W D DDDD 0 ~ 9999 Data Register (D)
W M_word DDD 0 ~ 255 Word type for M
W L_word DDD 0 ~ 255 Word type for L
W F_word DDD 0 ~ 255 Word type for F
198
PLC Connection Guide
Wiring Diagram:
The following represents the cable end connector.
eMT3000 series
COM1 RS232 9P COM3 RS232 9P RS232 9P D-Sub Male
D-Sub Female D-Sub Female
2 RX 8 RX 3 TX
3 TX 7 TX 2 RX
5 GND 5 GND 5 GND
MT6050i/MT8050i
COM1 RS232 9P RS232 9P D-Sub Male
D-Sub Female
9 RX 3 TX
6 TX 2 RX
5 GND 5 GND
Driver Version:
Version Date Description
V1.20 May/11/2011 Added registers: D_bit, M_word, F_word, L_word
199
PLC Connection Guide
Website: http://www.lgis.com/
HMI Setting:
Parameters Recommended Options Notes
PLC type LS MASTER-K MODBUS RTU
PLC I/F RS485 2W
Baud rate 9600
Data bits 8 8
Parity Even Even
Stop bits 1 1
PLC sta. no. 1
Device Address:
Bit/Word Device type Format Range Memo
B P DDDDh 0 ~ 9999f I/O Relay (P)
B M DDDDh 0 ~ 9999f Auxiliary Relay (M)
B L DDDDh 0 ~ 9999f Link Relay (L)
B K DDDDh 0 ~ 9999f Keep Relay (K)
B F DDDDh 0 ~ 9999f Special Relay (F)
B D_bit DDDDh 0 ~ 9999f
W T DDDD 0 ~ 9999 Timer (T)
W C DDDD 0 ~ 9999 Counter (C)
W S DDDD 0 ~ 9999
W D DDDD 0 ~ 9999 Data Register (D)
W T_double DDDD 0 ~ 9999
W C_double DDDD 0 ~ 9999
W S_double DDDD 0 ~ 9999
W D_double DDDD 0 ~ 9999
W F_word DDDD 0 ~ 9999
W L_word DDDD 0 ~ 9999
W M_word DDDD 0 ~ 9999
200
PLC Connection Guide
Wiring Diagram:
The following represents the cable end connector.
eMT3000 series
COM1 RS232 9P COM3 RS232 9P RS232 9P D-Sub Male
D-Sub Female D-Sub Female
2 RX 8 RX 3 TX
3 TX 7 TX 2 RX
5 GND 5 GND 5 GND
MT6050i/MT8050i
COM1 RS232 9P RS232 9P D-Sub Male
D-Sub Female
9 RX 3 TX
6 TX 2 RX
5 GND 5 GND
Driver Version:
Version Date Description
V1.10 May/11/2011 Added registers: D_bit, M_word, F_word, L_word
201
PLC Connection Guide
LS MASTER-K10S1
Supported Series: LS MASTER-K10S1
Website: http://www.lgis.com/
HMI Setting:
Parameters Recommended Options Notes
PLC type LS MASTER-K10S1
PLC I/F RS232 RS232/RS485
Baud rate 9600
Data bits 8 8
Parity None None
Stop bits 1 1
PLC sta. no. 0
Device Address:
Bit/Word Device type Format Range Memo
B P DDDh 0 ~ 255f I/O Relay (P)
B K DDDh 0 ~ 255f Keep Relay (K)
B M DDDh 0 ~ 255f Auxiliary Relay (M)
B L DDDh 0 ~ 255f Link Relay (L)
B F DDDh 0 ~ 255f Special Relay (F)
B T DDD 0 ~ 255 Timer (T)
B C DDD 0 ~ 255 Counter (C)
W TV DDD 0 ~ 255 Timer Present Value
W CV DDD 0 ~ 255 Counter Present Value
W D DDDD 0 ~ 9999 Data Register (D)
202
PLC Connection Guide
Wiring Diagram:
The following represents the cable end connector.
Driver eMT3000 series
COM1 RS232 9P COM3 RS232 9P RS232 9P D-Sub Male
D-Sub Female D-Sub Female
2 RX 8 RX 3 TX
3 TX 7 TX 2 RX
5 GND 5 GND 5 GND
MT6050i/MT8050i
COM1 RS232 9P RS232 9P D-Sub Male
D-Sub Female
9 RX 3 TX
6 TX 2 RX
5 GND 5 GND
Version:
Version Date Description
V1.00 Sep/08/2009 Driver released.
203
PLC Connection Guide
LS XGB Cnet
Supported Series: LS XGB/XGT Series
Website: http://www.lgis.com/
HMI Setting:
Parameters Recommended Options Notes
PLC type LS XGB Cnet
PLC I/F RS232 RS232/RS485
Baud rate 115200 9600~115200
Data bits 8 7, 8
Parity None Even, Odd, None
Stop bits 1 1
PLC sta. no. 1 0-31
Device Address:
Bit/Word Device type Format Range Memo
B P_Bit DDDDh 0 ~ 2047f I/O device Bit
B M_Bit DDDDh 0 ~ 2047f Internal device Bit
B L_Bit DDDDDh 0 ~ 11263f Communication device Bit
B K_Bit DDDDh 0 ~ 2559f Preservation device Bit
Special device Bit( write
B F_Bit DDDDh 0 ~ 2047f
available from 1025)
B S_Bit DDDDD 0 ~ 12799 Relay for step control Bit
Data register_Bit expression
B D_Bit DDDDDh 0 ~ 32767f
(D0000.0)
B U_Bit DH.DDh 0.000 ~ 7f.31f XGK-CPUE : hh(0~1f)
B T_Bit DDDD 0 ~ 2047 Timer device Bit
B C_Bit DDDD 0 ~ 2047 Counter device Bit
W P DDDD 0 ~ 2047 I/O device_2,048 points
W M DDDD 0 ~ 2047 Internal device_4,096 points
Communication device_20,480
W L DDDDD 0 ~ 11263
points
Preservation device_4,096
W K DDDD 0 ~ 2559
points
W F DDDD 0 ~ 2047 Special device_4,096 point
204
PLC Connection Guide
Bit/Word Device type Format Range Memo
W S DDDDD 0 ~ 12799 Relay for step control
W D DDDDD 0 ~ 32767 Data register_5120 words
W U DH.DD 0.00 ~ 7f.31 Analog data register_256 words
Communication data
W N DDDDD 0 ~ 21503
register_3,936 words
W Z DDD 0 ~ 127 Index register_128 words
Timer current value
W T DDDD 0 ~ 2047
register_256 words
Counter current value
W C DDDD 0 ~ 2047
register_256 words
Wiring Diagram:
The following represents the cable end connector.
eMT3000 series
COM1 RS232 9P COM3 RS232 9P RS232 6P Mini-DIN
D-Sub Female D-Sub Female Male
2 RX 8 RX 6 TXD
3 TX 7 TX 2 RXD
5 GND 5 GND 3 GND
205
PLC Connection Guide
MT6050i/MT8050i
COM1 RS232 9P RS232 6P Mini-DIN
D-Sub Female Male
9 RX 6 TXD
6 TX 2 RXD
5 GND 3 GND
Driver Version:
Version Date Description
V1.50 Mar/07/2011 Added registers: P_Bit, M_Bit, L_Bit, K_Bit…etc
206
PLC Connection Guide
HMI Setting:
Parameters Recommended Options Notes
PLC type LS XGB FEnet (Ethernet)
PLC I/F Ethernet
Port no. 2004
PLC sta. no. 0 0~255
PLC Setting:
Communication mode FEnet Potocol
Device Address:
Bit/Word Device type Format Range Memo
B P_Bit DDDDh 0 ~ 2047f I/O device Bit
B M_Bit DDDDh 0 ~ 2047f Internal device Bit
B L_Bit DDDDDh 0 ~ 11263f Communication device Bit
B K_Bit DDDDh 0 ~ 2559f Preservation device Bit
Special device Bit( write available
B F_Bit DDDDh 0 ~ 2047f
from 1025)
B S_Bit DDDh 0 ~ 127f Relay for step control Bit
B D_Bit DDDDDh 0 ~ 32767f Data register_Bit expression
B U_Bit DH.DDh 0.000 ~ 7f.31f XGK-CPUE : hh(0~1f)
B T_Bit DDDD 0 ~ 2047 Timer device Bit
B C_Bit DDDD 0 ~ 2047 Counter device Bit
W P DDDD 0 ~ 2047 I/O device_2,048 points
W M DDDD 0 ~ 2047 Internal device_4,096 points
Communication device_20,480
W L DDDDD 0 ~ 11263
points
W K DDDD 0 ~ 2559 Preservation device_4,096 points
W F DDDD 0 ~ 2047 Special device_4,096 point
W S DDDDD 0 ~ 12799 Relay for step control
207
PLC Connection Guide
Bit/Word Device type Format Range Memo
W D DDDDD 0 ~ 32767 Data register_5120 words
W U DH.DD 0.00 ~ 7f.31 Analog data register_256 words
Communication data
W N DDDDD 0 ~ 21503
register_3,936 words
W Z DDD 0 ~ 127 Index register_128 words
Timer current value register_256
W T DDDD 0 ~ 2047
words
Counter current value
W C DDDD 0 ~ 2047
register_256 words
Wiring Diagram:
Direct connect (crossover cable):
HMI RJ45 Male Wire Color PLC RJ45 Male
1 TX+ White/Orange 3 RX+
2 TX- Orange 6 RX-
3 RX+ White/Green 1 TX+
4 BD4+ Blue 4 BD4+
5 BD4- White/Blue 5 BD4-
6 RX- Green 2 TX-
7 BD3+ White/Brown 7 BD3+
8 BD3- Brown 8 BD3-
208
PLC Connection Guide
Through a hub:
HMI RJ45 Male Wire Color PLC RJ45 Male
1 TX+ White/Orange 1 TX+
2 TX- Orange 2 TX-
3 RX+ White/Green 3 RX+
4 BD4+ Blue 4 BD4+
5 BD4- White/Blue 5 BD4-
6 RX- Green 6 RX-
7 BD3+ White/Brown 7 BD3+
8 BD3- Brown 8 BD3-
Driver Version:
Version Date Description
V1.50 Aug/16/2011 Added registers: P_Bit, M_Bit, L_Bit, K_Bit…etc
209
PLC Connection Guide
LS XGI Cnet
Supported Series: LS XGI series communication module XGL-CH2A
Website: http://www.lgis.com/
HMI Setting:
Parameters Recommended Options Notes
PLC type LS XGI Cnet
PLC I/F RS232 RS232/RS485 4W
Baud rate 115200 9600~115200
Data bits 8 7, 8
Parity None Even, Odd, None
Stop bits 1 1
PLC sta. no. 0 0~255
Device Address:
Bit/Word Device type Format Range Memo
B A_Bit DDDDDDh 0 ~ 262143f
B I_Bit DDD.DD.Dh 0 ~ 127.15.3f
B Q_Bit DDD.DD.Dh 0 ~ 127.15.3f
B M_Bit DDDDDDh 0 ~ 131071f
B R_Bit DDDDDh 0 ~ 32767f
B W_Bit DDDDDh 0 ~ 65535f
B F_Bit DDDDh 0 ~ 2047f
B K_Bit DDDDh 0 ~ 8399f
B L_Bit DDDDDh 0 ~ 11263f
B N_Bit DDDDDh 0 ~ 25087f
B U_Bit DD.DD.DDh 0 ~ 31.15.31f
W A DDDDDD 0 ~ 262143
W I DDD.DD.D 0 ~ 127.15.3
W Q DDD.DD.D 0 ~ 127.15.3
W M DDDDDD 0 ~ 131071
W R DDDDD 0 ~ 32767
W W DDDDD 0 ~ 65535
W F DDDD 0 ~ 2047
W K DDDD 0 ~ 8399
210
PLC Connection Guide
Bit/Word Device type Format Range Memo
W L DDDDD 0 ~ 11263
W N DDDDD 0 ~ 25087
W U DD.DD.DD 0 ~ 31.15.31
Wiring Diagram:
The following represents the cable end connector.
9P D-Sub to 9P D-Sub:
eMT3000 series
COM1 RS232 9P COM3 RS232 9P XGL-CH2A CH1 RS232
D-Sub Female D-Sub Female 9P D-Sub Male
2 RX 8 RX 3 TXD
3 TX 7 TX 2 RXD
5 GND 5 GND 5 GND
MT6050i/MT8050i
COM1 RS232 9P XGL-CH2A CH1 RS232
D-Sub Female 9P D-Sub Male
9 RX 3 TXD
6 TX 2 RXD
5 GND 5 GND
211
PLC Connection Guide
The following represents the cable end connector.
9P D-Sub to Terminals:
eMT3000 series
COM1 RS485 4W XGL-CH2A CH2 5P
9P D-Sub Male Terminal
1 RX- TXD-
2 RX+ TXD+
3 TX- RXD-
4 TX+ RXD+
5 GND GND
MT6050i/MT8050i
COM1 RS485 4W XGL-CH2A CH2 5P
9P D-Sub Female Terminal
1 RX- TXD-
2 RX+ TXD+
3 TX- RXD-
4 TX+ RXD+
5 GND GND
212
PLC Connection Guide
Driver Version:
Version Date Description
V1.00 May/23/2012 Driver released
213
PLC Connection Guide
HMI Setting:
Parameters Recommended Options Notes
PLC type LS XGI CPU DIRECT
PLC I/F RS232 RS232
Baud rate 115200 9600~115200
Data bits 8 7, 8
Parity None Even, Odd, None
Stop bits 1 1
PLC sta. no. 1 1
Device Address:
Bit/Word Device type Format Range Memo
B A_Bit DDDDDDh 0 ~ 262143f
B I_Bit DDD.DD.Dh 0 ~ 127.15.3f
B Q_Bit DDD.DD.Dh 0 ~ 127.15.3f
B M_Bit DDDDDDh 0 ~ 131071f
B R_Bit DDDDDh 0 ~ 32767f
B W_Bit DDDDDh 0 ~ 65535f
B F_Bit DDDDh 0 ~ 2047f
B K_Bit DDDDh 0 ~ 8399f
B L_Bit DDDDDh 0 ~ 11263f
B N_Bit DDDDDh 0 ~ 25087f
B U_Bit DD.DD.DDh 0 ~ 31.15.31f
W A DDDDDD 0 ~ 262143
W I DDD.DD.D 0 ~ 127.15.3
W Q DDD.DD.D 0 ~ 127.15.3
W M DDDDDD 0 ~ 131071
W R DDDDD 0 ~ 32767
W W DDDDD 0 ~ 65535
W F DDDD 0 ~ 2047
214
PLC Connection Guide
Bit/Word Device type Format Range Memo
W K DDDD 0 ~ 8399
W L DDDDD 0 ~ 11263
W N DDDDD 0 ~ 25087
W U DD.DD.DD 0 ~ 31.15.31
Wiring Diagram:
The following represents the cable end connector.
eMT3000 series
COM1 RS232 9P COM3 RS232 9P RS232 9P D-Sub Male
D-Sub Female D-Sub Female
2 RX 8 RX 3 TXD
3 TX 7 TX 2 RXD
5 GND 5 GND 5 GND
MT6050i/MT8050i
COM1 RS232 9P RS232 9P D-Sub Male
D-Sub Female
9 RX 3 TXD
6 TX 2 RXD
5 GND 5 GND
215
PLC Connection Guide
Driver Version:
Version Date Description
V1.00 May/17/2012 Driver released.
216
PLC Connection Guide
HMI Setting:
Parameters Recommended Options Notes
PLC type LS XGI FEnet (Ethernet)
PLC I/F Ethernet
Port no. 2004
PLC sta. no. 0
Device Address:
Bit/Word Device type Format Range Memo
B A_Bit DDDDDDh 0 ~ 262143f
B I_Bit DDD.DD.Dh 0 ~ 127.15.3f
B Q_Bit DDD.DD.Dh 0 ~ 127.15.3f
B M_Bit DDDDDDh 0 ~ 131071f
B R_Bit DDDDDh 0 ~ 32767f
B W_Bit DDDDDh 0 ~ 65535f
B F_Bit DDDDh 0 ~ 2047f
B K_Bit DDDDh 0 ~ 8399f
B L_Bit DDDDDh 0 ~ 11263f
B N_Bit DDDDDh 0 ~ 25087f
B U_Bit DD.DD.DDh 0 ~ 31.15.31f
W A DDDDDD 0 ~ 262143
W I DDD.DD.D 0 ~ 127.15.3
W Q DDD.DD.D 0 ~ 127.15.3
W M DDDDDD 0 ~ 131071
W R DDDDD 0 ~ 32767
W W DDDDD 0 ~ 65535
W F DDDD 0 ~ 2047
W K DDDD 0 ~ 8399
W L DDDDD 0 ~ 11263
W N DDDDD 0 ~ 25087
W U DD.DD.DD 0 ~ 31.15.31
217
PLC Connection Guide
Wiring Diagram:
Direct connect (crossover cable):
HMI RJ45 Male Wire Color PLC RJ45 Male
1 TX+ White/Orange 3 RX+
2 TX- Orange 6 RX-
3 RX+ White/Green 1 TX+
4 BD4+ Blue 4 BD4+
5 BD4- White/Blue 5 BD4-
6 RX- Green 2 TX-
7 BD3+ White/Brown 7 BD3+
8 BD3- Brown 8 BD3-
Through a hub:
HMI RJ45 Male Wire Color PLC RJ45 Male
1 TX+ White/Orange 1 TX+
2 TX- Orange 2 TX-
3 RX+ White/Green 3 RX+
4 BD4+ Blue 4 BD4+
5 BD4- White/Blue 5 BD4-
6 RX- Green 6 RX-
7 BD3+ White/Brown 7 BD3+
8 BD3- Brown 8 BD3-
Driver Version:
Version Date Description
V1.00 May/21/2012 Driver released.
218
PLC Connection Guide
LS XGK Cnet
Supported Series: LS XGT series communication module XGL-CH2A
Website: http://www.lgis.com/
HMI Setting:
Parameters Recommended Options Notes
PLC type LS XGK Cnet
PLC I/F RS232 RS232/RS485 4W
Baud rate 115200 9600~115200
Data bits 8 7, 8
Parity None Even, Odd, None
Stop bits 1 1
PLC sta. no. 1 0~32
Device Address:
Bit/Word Device type Format Range Memo
B P_Bit DDDDh 0 ~ 2047f I/O device Bit
B M_Bit DDDDh 0 ~ 2047f Internal device Bit
B L_Bit DDDDDh 0 ~ 11263f Communication device Bit
B K_Bit DDDDh 0 ~ 2559f Preservation device Bit
Special device Bit( write
B F_Bit DDDDh 0 ~ 2047f
available from 1025)
B S_Bit DDDDD 0 ~ 12799 Relay for step control Bit
Data register_Bit expression
B D_Bit DDDDDh 0 ~ 32767f
(D0000.0)
B U_Bit DH.DDh 0.000 ~ 3f.31f XGK-CPUE : hh(0~1f)
B T_Bit DDDD 0 ~ 2047 Timer device Bit
B C_Bit DDDD 0 ~ 2047 Counter device Bit
W P DDDD 0 ~ 2047 I/O device
W M DDDD 0 ~ 2047 Internal device
W L DDDDD 0 ~ 11263 Communication device
W K DDDD 0 ~ 2559 Preservation device
Special device( write
W F DDDD 0 ~ 2047
available from 1025)
219
PLC Connection Guide
Bit/Word Device type Format Range Memo
W S DDDDD 0 ~ 127 Relay for step control
W D DDDDD 0 ~ 32767 Data register
Analog data register
W U DH.DD 0.00 ~ 3f.31
XGK-CPUE : hh(0~1f)
W N DDDDD 0 ~ 21503 Communication data register
W Z DDD 0 ~ 127 Index register_128 words
W T DDDD 0 ~ 2047 Timer current value register
Counter current value
W C DDDD 0 ~ 2047
register
W R DDDDD 0 ~ 32767
W ZR DDDDD 0 ~ 32767
Wiring Diagram:
The following represents the cable end connector.
9P D-Sub to 9P D-Sub:
eMT3000 series
COM1 RS232 9P COM3 RS232 9P XGL-CH2A CH1 RS232
D-Sub Female D-Sub Female 9P D-Sub Male
2 RX 8 RX 3 TXD
3 TX 7 TX 2 RXD
5 GND 5 GND 5 GND
220
PLC Connection Guide
MT6050i/MT8050i
COM1 RS232 9P XGL-CH2A CH1 RS232
D-Sub Female 9P D-Sub Male
9 RX 3 TXD
6 TX 2 RXD
5 GND 5 GND
221
PLC Connection Guide
MT6050i/MT8050i
COM1 RS485 4W XGL-CH2A CH2 5P
9P D-Sub Female Terminal
1 RX- TXD-
2 RX+ TXD+
3 TX- RXD-
4 TX+ RXD+
5 GND GND
Driver Version:
Version Date Description
V1.30 Feb /25/2011 Added registers: P_Bit, M_Bit, L_Bit, K_Bit…etc
V1.40 Jun/20/2012 Change the way to read/write S_Bit.
222
PLC Connection Guide
Website: http://www.lgis.com/
HMI Setting:
Parameters Recommended Options Notes
PLC type LS XGK FEnet (Ethernet)
PLC I/F Ethernet
Port no. 2004
PLC sta. no. 0
Device Address:
Bit/Word Device type Format Range Memo
B P_Bit DDDDh 0 ~ 2047f I/O device Bit
B M_Bit DDDDh 0 ~ 2047f Internal device Bit
B L_Bit DDDDDh 0 ~ 11263f Communication device Bit
B K_Bit DDDDh 0 ~ 2559f Preservation device Bit
Special device Bit( write available
B F_Bit DDDDh 0 ~ 2047f
from 1025)
223
PLC Connection Guide
Bit/Word Device type Format Range Memo
Analog data register XGK-CPUE :
W U DH.DD 0.00 ~ 3f.31
hh(0~1f)
W N DDDDD 0 ~ 21503 Communication data register
W Z DDD 0 ~ 127 Index register_128 words
W T DDDD 0 ~ 2047 Timer current value register
W C DDDD 0 ~ 2047 Counter current value register
W R DDDDD 0 ~ 32767
W ZR DDDDD 0 ~ 32767
Wiring Diagram:
Direct connect (crossover cable):
HMI RJ45 Male Wire Color PLC RJ45 Male
1 TX+ White/Orange 3 RX+
2 TX- Orange 6 RX-
3 RX+ White/Green 1 TX+
4 BD4+ Blue 4 BD4+
5 BD4- White/Blue 5 BD4-
6 RX- Green 2 TX-
7 BD3+ White/Brown 7 BD3+
8 BD3- Brown 8 BD3-
Through a hub:
HMI RJ45 Male Wire Color PLC RJ45 Male
1 TX+ White/Orange 1 TX+
2 TX- Orange 2 TX-
3 RX+ White/Green 3 RX+
4 BD4+ Blue 4 BD4+
5 BD4- White/Blue 5 BD4-
6 RX- Green 6 RX-
7 BD3+ White/Brown 7 BD3+
8 BD3- Brown 8 BD3-
224
PLC Connection Guide
Driver Version:
Version Date Description
V1.30 Mar/10/2011 Added registers: P_Bit, M_Bit, L_Bit, K_Bit…etc
V1.40 Jun/19/2012 Change the way to read/write S_Bit.
225
PLC Connection Guide
HMI Setting:
Parameters Recommended Options Notes
PLC type LS XGT/XGK CPU DIRECT
PLC I/F RS232 RS232
Baud rate 115200 9600~115200
Data bits 8 7, 8
Parity None Even, Odd, None
Stop bits 1 1
PLC sta. no. 1 1
Device Address:
Bit/Word Device type Format Range Memo
B P_Bit DDDDh 0 ~ 2047f I/O device Bit
B M_Bit DDDDh 0 ~ 2047f Internal device Bit
B L_Bit DDDDDh 0 ~ 11263f Communication device Bit
B K_Bit DDDDh 0 ~ 2559f Preservation device Bit
Special device Bit( write
B F_Bit DDDDh 0 ~ 2047f
available from 1025)
B S_Bit DDDDD 0 ~ 12799 Relay for step control Bit
B D_Bit DDDDDh 0 ~ 32767f Data register_Bit expression
B U_Bit DH.DDh 0.000 ~ 3f.31f XGK-CPUE : hh(0~1f)
B T_Bit DDDD 0 ~ 2047 Timer device Bit
B C_Bit DDDD 0 ~ 2047 Counter device Bit
W P DDDD 0 ~ 2047 I/O device
W M DDDD 0 ~ 2047 Internal device
W L DDDDD 0 ~ 11263 Communication device
W K DDDD 0 ~ 2559 Preservation device
Special device( write
W F DDDD 0 ~ 2047
available from 1025)
226
PLC Connection Guide
Bit/Word Device type Format Range Memo
W S DDDDD 0 ~ 127 Relay for step control
W D DDDDD 0 ~ 32767 Data register
Analog data register
W U DH.DD 0.00 ~ 3f.31
XGK-CPUE : hh(0~1f)
W N DDDDD 0 ~ 21503 Communication data register
W Z DDD 0 ~ 127 Index register_128 words
W T DDDD 0 ~ 2047 Timer current value register
W C DDDD 0 ~ 2047 Counter current value
W R DDDDD 0 ~ 32767 register
W ZR DDDDD 0 ~ 32767
W TS DDDD 0 ~ 2047 Setup value
W CS DDDD 0 ~ 2047 Setup value
Wiring Diagram:
The following represents the cable end connector.
eMT3000 series
COM1 RS232 9P COM3 RS232 9P RS232 9P D-Sub Male
D-Sub Female D-Sub Female
2 RX 8 RX 3 TXD
3 TX 7 TX 2 RXD
5 GND 5 GND 5 GND
227
PLC Connection Guide
MT6050i/MT8050i
COM1 RS232 9P RS232 9P D-Sub Male
D-Sub Female
9 RX 3 TXD
6 TX 2 RXD
5 GND 5 GND
Driver Version:
Version Date Description
V1.40 Mar/10/2011 Added registers: P_Bit, M_Bit, L_Bit, K_Bit…etc
V1.60 Jun/18/2012 Change the way to read/write S_Bit.
228
PLC Connection Guide
HMI Setting:
Parameters Recommended Options Notes
PLC type LS Mecapion Metronix AnyPack
PLC I/F RS232
Baud rate 9600
Data bits 8
Parity None
Stop bits 1
PLC sta. no. 0
Device Address:
Bit/Word Device Type Format Range Memo
B MX_L16bit DDDDDdd 0 ~ 9999915 MD Low 16bit
B MX_H16bit DDDDDdd 0 ~ 9999915 MD High 16bit
DW MD DDDD 0 ~ 9999
Wiring Diagram:
The following represents the cable end connector.
eMT3000 series
COM1 RS232 9P COM3 RS232 9P PLC RS232 Terminal
D-Sub Female D-Sub Female
2 RX 8 RX 6 TX
3 TX 7 TX 5 RX
5 GND 5 GND 11 GND
circuit
12 GND
229
PLC Connection Guide
MT6000/8000 series except MT6050i/MT8050i
COM1 RS232 9P COM2 RS232 9P COM3 RS232 9P PLC RS232 Terminal
D-Sub Female D-Sub Female D-Sub Male
2 RX 6 RX 8 RX 6 TX
3 TX 4 TX 7 TX 5 RX
5 GND 5 GND 5 GND 11 GND
circuit
12 GND
MT6050i/MT8050i
COM1 RS232 9P PLC RS232 Terminal
D-Sub Female
9 RX 6 TX
6 TX 5 RX
5 GND 11 GND
circuit
12 GND
Driver Version:
Version Date Description
V1.00 Jul/1/2008
230
PLC Connection Guide
Master-Slave Server
HMI Setting:
Parameters Recommended Options Notes
PLC type Master-Slave Server
PLC I/F RS232 RS232/RS485
Baud rate 115200 9600~115200
Data bits 8 7,8
Parity Even None,Even,Odd,Mark,Space
Stop bits 1 1,2
HMI sta. no. 0
PLC sta. no. 0
231
PLC Connection Guide
To connect HMI with MT500, MT500 has to be set as [Slave].
PLC Setting:
Communication mode MT500 Multiple HMI set Slave.
232
PLC Connection Guide
Device Address:
Bit/Word MT500 MT8000 Range Memo
ddd: 0 ~ 4095
B Ms_RB RW_Bit
(h): 0 ~ f
B Ms_LB LB dddd:0 ~ 9999
W Ms_RW RW ddd:0 ~ 65535
W Ms_LW LW ddd:0 ~ 9999
Driver Version:
Version Date Description
V1.00 Dec/30/2008 Driver released.
233
PLC Connection Guide
Memory Map
Memory Map protocol is similar to IBM 3764R communication protocol. EasyBuilder
reserves 512 words of data memory to use with this protocol. EasyBuilder must update the
values in these words. EasyBuilder uses these words to display data and control parts
status on screen. When touch actions are taken, data is sent to the others once, and then
update the memory in it. The HMI should always update the data memory.
HMI Setting:
Parameters Recommended Options Notes
PLC type Memory Map
RS232, RS485
PLC I/F RS232 RS232 default
4W, 2W
Baud rate 115200 9600~115200
Data bits 8
Parity Even Even, Odd, None
Stop bits 1
Device Address:
Bit/Word Device type Format Range Memo
B MB DDDDh 0 ~ 4095f
W MW DDDD 0 ~ 9999
MB and MW share the same data storage.
MW 0 = MB 00000 ~ MB 0000f, MW 1 = MB 00010 ~ MB 0001f
234
PLC Connection Guide
Wiring Diagram:
The following represents the cable end connector.
eMT3000 series
COM1 RS232 9P COM3 RS232 9P HMI COM1 RS232 9P
D-Sub Female D-Sub Female D-Sub Female
2 RX 8 RX 3 TX
3 TX 7 TX 2 RX
5 GND 5 GND 5 GND
MT6050i/MT8050i
COM1 RS232 9P HMI COM1 RS232 9P
D-Sub Female D-Sub Female
9 RX 3 TX
6 TX 2 RX
5 GND 5 GND
235
PLC Connection Guide
The following represents the cable end connector.
eMT3000 series
COM1 RS485 2W COM3 RS485 2W HMI COM1 RS485 2W
9P D-Sub Male 9P D-Sub Male 9P D-Sub Male
1 RX- 6 Data- 1 RX-
2 RX+ 9 Data+ 2 RX+
5 GND 5 GND 5 GND
MT6050i/MT8050i
COM1 RS485 2W COM3 RS485 2W HMI COM1 RS485 2W
9P D-Sub Female 9P D-Sub Female 9P D-Sub Female
1 RX- 7 Data- 1 RX-
2 RX+ 8 Data+ 2 RX+
5 GND 5 GND 5 GND
236
PLC Connection Guide
The following represents the cable end connector.
eMT3000 series
COM1 RS485 4W HMI COM1 RS485 4W
9P D-Sub Male 9P D-Sub Male
1 RX- 3 TX-
2 RX+ 4 TX+
3 TX- 1 RX-
4 TX+ 2 RX+
5 GND 5 GND
237
PLC Connection Guide
MT6050i/MT8050i
COM1 RS485 4W HMI COM1 RS485 4W
9P D-Sub Female 9P D-Sub Female
1 RX- 3 TX-
2 RX+ 4 TX+
3 TX- 1 RX-
4 TX+ 2 RX+
5 GND 5 GND
Note:
For Memory map information, please refer to User’s Manual “Chapter 31 Memory Map
Communication”.
Driver Version:
Version Date Description
V1.00 Mar/19/2009 Driver released.
238
PLC Connection Guide
HMI Setting:
Parameters Recommended Options Notes
PLC type MIKOM MX Series PLC
PLC I/F RS232 RS232/485/Ethernet
Baud rate 19200 9600~115200
Data bits Even None,Even,Odd
Parity 8 8
Stop bits 1 1,2
PLC sta. no. 1 0~31
PLC Setting:
PORT 0(RS232 Setting)
239
PLC Connection Guide
PORT 1(RS485 Setting)
Device Address:
Bit/Word Device type Format Range Memo
B Y DDD 0~777 Output Relay
B X DDD 0~777 Input Relay
B M DDDD 0~4095 Auxiliary Relay
B SM DDD 0-511 Special Auxiliary Relay
B S DDDD 0~1535 Step Relay
B T DDD 0~511 Timer Relay
B C DDD 0~511 Counter Relay
W D DDDDD 0~32767 Data Register
W SD DDD 0~511 Special Data Register
W Z DDD 0~255 Indexed Addressing Register
W T DDD 0~511 Timer
W C DDD 0~199 Counter
W U0 DDD 0~199 Special Module Register
W U1 DDD 0~199 Special Module Register
W U2 DDD 0~199 Special Module Register
W U3 DDD 0~199 Special Module Register
W U4 DDD 0~199 Special Module Register
W U5 DDD 0~199 Special Module Register
W U6 DDD 0~199 Special Module Register
W U7 DDD 0~199 Special Module Register
DW C-32bit DDD 200~511 32 Bit Counter
240
PLC Connection Guide
Wiring Diagram:
The following represents the cable end connector.
eMT3000 series
COM1 RS232 9P COM3 RS232 9P RS232 8P Mini-DIN
D-Sub Female D-Sub Female Male
2 RX 8 RX 3 TX
3 TX 7 TX 2 RX
5 GND 5 GND 5 GND
MT6050i/MT8050i
COM1 RS232 9P RS232 8P Mini-DIN
D-Sub Female Male
9 RX 3 TX
6 TX 2 RX
5 GND 5 GND
Driver Version:
Version Date Description
V1.00 May/3/2012 Driver released.
241
PLC Connection Guide
Mitsubishi A1S
Supported Series: Mitsubishi A1S
Website: http://www.mitsubishi-automation.com/
HMI Setting:
Parameters Recommended Options Notes
PLC type Mitsubishi A1S
PLC I/F RS232
Baud rate 9600
Data bits 8
Parity Odd
Stop bits 1
PLC sta. no. 0
Device Address:
Bit/Word Device type Format Range Memo
B X HHHH 0 ~ ffff Input Relay
B Y HHHH 0 ~ ffff Output Relay
B M DDDDD 0 ~ 65535 Auxiliary Relay
B B HHHH 0 ~ ffff
B F DDDDD 0 ~ 65535
W TV DDDDD 0 ~ 65535 Timer Memory
W CV DDDDD 0 ~ 65535 Counter Memory
W D DDDDD 0 ~ 65535 Data Register
W W HHHH 0 ~ ffff
W R DDDDD 0 ~ 65535
242
PLC Connection Guide
Wiring Diagram:
Use the RS422 to RS232 PLC programming cable (shown as follows)
243
PLC Connection Guide
MT6000/8000 series except MT6050i/MT8050i
COM1 RS232 9P Mitsubishi RS422 25P
PLC Programming Converter
D-Sub Female D-Sub Male
2 RX TX TX+ 2 RX+
3 TX RX RX+ 3 TX+
5 GND GND DTR+ 4 DSR+
7 RTS CTS GND 7 GND
8 CTS RTS TX- 15 RX-
RX- 16 TX-
DTR- 17 DSR-
Driver Version:
Version Date Description
V1.00 Sep/18/2009 Driver released.
244
PLC Connection Guide
Mitsubishi A2A/A2U/A2AS/A2USH
Supported Series: Mitsubishi A2A,A2U,A2AS,A2USH
Website: http://www.mitsubishi-automation.com/
HMI Setting:
Parameters Recommended Options Notes
PLC type Mitsubishi A2A/A2U/A2AS/A2USH
PLC I/F RS232
Baud rate 9600
Data bits 8
Parity Odd
Stop bits 1
PLC sta. no. 0
Device Address:
Bit/Word Device type Format Range Memo
B X HHHH 0 ~ 270f Input Relay
B Y HHHH 0 ~ 270f Output Relay
B M DDDD 0 ~ 9999 Auxiliary Relay
B B HHHH 0 ~ ffff
B F DDDDD 0 ~ 65535
W TV DDD 0 ~ 255 Timer Memory
W CV DDD 0 ~ 255 Counter Memory
W D DDDD 0 ~ 9999 Data Register
W W HHHH 0 ~ ffff
W R DDDDD 0 ~ 65535
245
PLC Connection Guide
Wiring Diagram:
Use the RS422 to RS232 PLC programming cable (shown as follows)
246
PLC Connection Guide
MT6000/8000 series except MT6050i/MT8050i
COM1 RS232 9P Mitsubishi RS422 25P
PLC Programming Converter
D-Sub Female D-Sub Male
2 RX TX TX+ 2 RX+
3 TX RX RX+ 3 TX+
5 GND GND DTR+ 4 DSR+
7 RTS CTS GND 7 GND
8 CTS RTS TX- 15 RX-
RX- 16 TX-
DTR- 17 DSR-
Driver Version:
Version Date Description
V1.00 Aug/12/2009 Driver released.
247
PLC Connection Guide
Mitsubishi A2N/A3A/A3N/A1SH/A2SH
Supported Series: Mitsubishi A2N,A3A,A3N,A1SH,A2SH
Website: http://www.mitsubishi-automation.com/
HMI Setting:
Parameters Recommended Options Notes
PLC type Mitsubishi A2N/A3A/A3N/A1SH/A2SH
PLC I/F RS232
Baud rate 9600
Data bits 8
Parity Odd
Stop bits 1
PLC sta. no. 0
Device Address:
Bit/Word Device type Format Range Memo
B X HHHH 0 ~ ffff Input Relay
B Y HHHH 0 ~ ffff Output Relay
B M DDDDD 0 ~ 65535 Auxiliary Relay
B B HHHH 0 ~ ffff
B F DDDDD 0 ~ 65535
W TV DDDDD 0 ~ 65535 Timer Memory
W CV DDDDD 0 ~ 65535 Counter Memory
W D DDDDD 0 ~ 65535 Data Register
W W HHHH 0 ~ ffff
W R DDDDD 0 ~ 65535
248
PLC Connection Guide
Wiring Diagram:
Use the RS422 to RS232 PLC programming cable (shown as follows)
249
PLC Connection Guide
MT6000/8000 series except MT6050i/MT8050i
COM1 RS232 9P Mitsubishi RS422 25P
PLC Programming Converter
D-Sub Female D-Sub Male
2 RX TX TX+ 2 RX+
3 TX RX RX+ 3 TX+
5 GND GND DTR+ 4 DSR+
7 RTS CTS GND 7 GND
8 CTS RTS TX- 15 RX-
RX- 16 TX-
DTR- 17 DSR-
Driver Version:
Version Date Description
V1.00 Oct/20/2009 Driver released.
250
PLC Connection Guide
Mitsubishi A2US
Supported Series: Mitsubishi A2US
Website: http://www.mitsubishi-automation.com/
HMI Setting:
Parameters Recommended Options Notes
PLC type Mitsubishi A2US
PLC I/F RS232
Baud rate 9600
Data bits 8
Parity Odd
Stop bits 1
PLC sta. no. 0
Device Address:
Bit/Word Device type Format Range Memo
B X HHHH 0 ~ 270f Input Relay
B Y HHHH 0 ~ 270f Output Relay
B M DDDD 0 ~ 9999 Auxiliary Relay
W TV DDD 0 ~ 255 Timer Memory
W CV DDD 0 ~ 255 Counter Memory
W D DDDD 0 ~ 9999 Data Register
251
PLC Connection Guide
Wiring Diagram:
Use the RS422 to RS232 PLC programming cable (shown as follows)
252
PLC Connection Guide
MT6000/8000 series except MT6050i/MT8050i
COM1 RS232 9P Mitsubishi RS422 25P
PLC Programming Converter
D-Sub Female D-Sub Male
2 RX TX TX+ 2 RX+
3 TX RX RX+ 3 TX+
5 GND GND DTR+ 4 DSR+
7 RTS CTS GND 7 GND
8 CTS RTS TX- 15 RX-
RX- 16 TX-
DTR- 17 DSR-
Driver Version:
Version Date Description
V1.00 Mar/20/2009 Driver released.
253
PLC Connection Guide
Mitsubishi AJ71
Supported Series: Mitsubishi A series PLC with AJ71C24 communication module using
the Computer Link protocol.
Website: http://www.mitsubishi-automation.com
HMI Setting:
Parameters Recommended Options Notes
Mitsubishi AJ71
(AnA/AnU CPU),
PLC type Mitsubishi AJ71
Mitsubishi AJ71
(Format 4)
PLC I/F RS485 4W RS485 4W, RS232
Baud rate 19200 9600, 19200
Data bits 8 8
Parity Even Even, Odd, None
Stop bits 1 1
PLC sta. no. 0
PLC Setting:
Communication mode Computer Link protocol 9600, Even, 8, 1 (default)
Mode setting switch Format 1
Parity check Enable
Sum check Enable
Device Address:
Bit/Word Device type Format Range Memo
B X HHHH 0 ~ ffff Input Bits
B Y HHHH 0 ~ ffff Output Bits
B M DDDDD 0 ~ 65535 Internal Relays
B T DDDDD 0 ~ 65535
B C DDDDD 0 ~ 65535
B B HHHH 0 ~ ffff
254
PLC Connection Guide
Bit/Word Device type Format Range Memo
B F DDDDD 0 ~ 65535
W TV DDDDD 0 ~ 65535 Timer Preset Value
W CV DDDDD 0 ~ 65535 Counter Preset Value
W D DDDDD 0 ~ 65535 Data Registers
W W HHHH 0 ~ ffff
W R DDDDD 0 ~ 65535
Wiring Diagram:
The following represents the cable end connector.
AJ71C24 RS422
eMT3000 series
COM1 RS485 4W AJ71C24 RS422
9P D-Sub Male Terminal
1 RX- SDB
2 RX+ SDA
3 TX- RDB
4 TX+ RDA
5 GND GND
255
PLC Connection Guide
MT6050i/MT8050i
COM1 RS485 4W AJ71C24 RS422
9P D-Sub Female Terminal
1 RX- SDB
2 RX+ SDA
3 TX- RDB
4 TX+ RDA
5 GND GND
256
PLC Connection Guide
MT6000/8000 series except MT6050i/MT8050i
COM1 RS232 9P COM2 RS232 9P COM3 RS232 9P RS232 9P D-Sub Male
D-Sub Female D-Sub Female D-Sub Male
2 RX 6 RX 8 RX 3 TXD
3 TX 4 TX 7 TX 2 RXD
5 GND 5 GND 5 GND 5 GND
1 DCD
4 DTR circuit
6 DSR
7 RTS
circuit
8 CTS
MT6050i/MT8050i
COM1 RS232 9P RS232 9P D-Sub Male
D-Sub Female
9 RX 3 TXD
6 TX 2 RXD
5 GND 5 GND
1 DCD
4 DTR circuit
6 DSR
7 RTS
circuit
8 CTS
Driver Version:
Version Date Description
V1.50 Mar/11/2010
257
PLC Connection Guide
HMI Setting:
Parameters Recommended Options Notes
PLC type Mitsubishi AJ71 (AnA/AnU CPU)
PLC I/F RS485 4W RS485 4W, RS232
Baud rate 19200 9600, 19200
Data bits 8 8
Parity Even Even, Odd, None
Stop bits 1 1
PLC sta. no. 0
PLC Setting:
Communication mode Computer Link protocol 9600, Even, 8, 1 (default)
Mode setting switch Format 1
Parity check Enable
Sum check Enable
Device Address:
Bit/Word Device type Format Range Memo
B X HHHH 0 ~ ffff Input Bits
B Y HHHH 0 ~ ffff Output Bits
B M DDDDD 0 ~ 65535 Internal Relays
B T DDDDD 0 ~ 65535
B C DDDDD 0 ~ 65535
B B HHHH 0 ~ ffff
B F DDDDD 0 ~ 65535
W TV DDDDD 0 ~ 65535 Timer Preset Value
W CV DDDDD 0 ~ 65535 Counter Preset Value
W D DDDDD 0 ~ 65535 Data Registers
W W HHHH 0 ~ ffff
W R DDDDD 0 ~ 65535
258
PLC Connection Guide
Wiring Diagram:
The following represents the cable end connector.
eMT3000 series
COM1 RS485 4W RS422 Terminal
9P D-Sub Male
1 RX- SDB
2 RX+ SDA
3 TX- RDB
4 TX+ RDA
5 GND GND
MT6050i/MT8050i
COM1 RS485 4W RS422 Terminal
9P D-Sub Female
1 RX- SDB
2 RX+ SDA
3 TX- RDB
4 TX+ RDA
5 GND GND
259
PLC Connection Guide
The following represents the cable end connector.
eMT3000 series
COM1 RS232 9P COM3 RS232 9P RS232 9P D-Sub Male
D-Sub Female D-Sub Female
2 RX 8 RX 3 TXD
3 TX 7 TX 2 RXD
5 GND 5 GND 5 GND
1 DCD
4 DTR circuit
6 DSR
7 RTS
circuit
8 CTS
260
PLC Connection Guide
MT6050i/MT8050i
COM1 RS232 9P RS232 9P D-Sub Male
D-Sub Female
9 RX 3 TXD
6 TX 2 RXD
5 GND 5 GND
1 DCD
4 DTR circuit
6 DSR
7 RTS
circuit
8 CTS
Driver Version:
Version Date Description
V1.00 Oct/31/2011 Driver released.
261
PLC Connection Guide
HMI Setting:
Parameters Recommended Options Notes
PLC type Mitsubishi AJ71 (Format 4)
PLC I/F RS485 4W RS485 4W, RS232
Baud rate 19200 9600, 19200
Data bits 8 8
Parity Even Even, Odd, None
Stop bits 1 1
PLC sta. no. 0
PLC Setting:
Communication mode Computer Link protocol 9600, Even, 8, 1 (default)
Mode setting switch Format 4
Parity check Enable
Sum check Enable
Device Address:
Bit/Word Device type Format Range Memo
B X HHHH 0 ~ ffff Input Bits
B Y HHHH 0 ~ ffff Output Bits
B M DDDDD 0 ~ 65535 Internal Relays
B T DDDDD 0 ~ 65535
B C DDDDD 0 ~ 65535
B B HHHH 0 ~ ffff
B F DDDDD 0 ~ 65535
W TV DDDDD 0 ~ 65535 Timer Preset Value
W CV DDDDD 0 ~ 65535 Counter Preset Value
W D DDDDD 0 ~ 65535 Data Registers
W W HHHH 0 ~ ffff
W R DDDDD 0 ~ 65535
262
PLC Connection Guide
Wiring Diagram:
The following represents the cable end connector.
eMT3000 series
COM1 RS485 4W AJ71C24 RS422
9P D-Sub Male Terminal
1 RX- SDB
2 RX+ SDA
3 TX- RDB
4 TX+ RDA
5 GND GND
MT6050i/MT8050i
COM1 RS485 4W AJ71C24 RS422
9P D-Sub Female Terminal
1 RX- SDB
2 RX+ SDA
3 TX- RDB
4 TX+ RDA
5 GND GND
263
PLC Connection Guide
The following represents the cable end connector.
A1SJ71UC24-R2
eMT3000 series
COM1 RS232 9P COM3 RS232 9P RS232 9P D-Sub Male
D-Sub Female D-Sub Female
2 RX 8 RX 3 TXD
3 TX 7 TX 2 RXD
5 GND 5 GND 5 GND
1 DCD
4 DTR circuit
6 DSR
7 RTS
circuit
8 CTS
264
PLC Connection Guide
MT6050i/MT8050i
COM1 RS232 9P RS232 9P D-Sub Male
D-Sub Female
9 RX 3 TXD
6 TX 2 RXD
5 GND 5 GND
1 DCD
4 DTR circuit
6 DSR
7 RTS
circuit
8 CTS
Driver Version:
Version Date Description
V1.00 Mar/08/2010
265
PLC Connection Guide
HMI Setting:
Parameters Recommended Options Notes
PLC type F930GOT Server
PLC I/F RS232
Baud rate 38400 9600, 115200
Data bits 8 7 or 8
Parity None Even, Odd, None
Stop bits 1 1 or 2
PLC sta. no. 1
Device Address:
Bit/Word Device type Format Range Memo
B RB DDDD 0 ~ 2047
W RW DDDDD 0 ~ 65535
Note: In PLC name drop - down menu don’t select F930GOT Server.
Please select Local HMI, Device Type=RW.
Wiring Diagram:
The following represents the cable end connector.
eMT3000 series
COM1 RS232 9P COM3 RS232 9P Micro Computer Board
D-Sub Female D-Sub Female RS232 Female
2 RX 8 RX 3 TD
3 TX 7 TX 2 RD
5 GND 5 GND 5 GND
266
PLC Connection Guide
MT6000/8000 series except MT6050i/MT8050i
COM1 RS232 9P COM2 RS232 9P COM3 RS232 9P Micro Computer Board
D-Sub Female D-Sub Female D-Sub Male RS232 Female
2 RX 6 RX 8 RX 3 TD
3 TX 4 TX 7 TX 2 RD
5 GND 5 GND 5 GND 5 GND
MT6050i/MT8050i
COM1 RS232 9P Micro Computer Board
D-Sub Female RS232 Female
9 RX 3 TD
6 TX 2 RD
5 GND 5 GND
Protocol:
Read Command:
PC HMI
02 ‘0’ Read address Size CR
02 30 30 30 30 30 30 32 0D
Read RW0 1 word (2 bytes) STX = 0x02, ‘0’ = Read command, CR = 0x0D
Read address (hexadecimal)
0 ~ FFFF = RW0 ~ 65535
Size (hexadecimal)
2 ~ FE = 2 ~ 254 bytes = 1 ~ 127 word.
Size must be even.
HMI PC (response)
02 Data1 Data2 ……. CR
02 30 30 31 30 0D
RW0 = 0x0010 = 16
267
PLC Connection Guide
Write Command:
PC HMI
02 ‘1’ Read address Size Data1 Data2 ……. CR
02 31 30 30 30 30 30 32 12 34 0D
Write RW0 = 0x1234
Read address (hexadecimal)
0 ~ FFFF = RW0 ~ 65535
Size (hexadecimal)
2 ~ FE = 2 ~ 254 bytes = 1 ~ 127 word.
Size must be even.
HMI PC (response)
06
ACK = 0x06
Driver Version:
Version Date Description
V1.00 Aug/14/2009 Driver released.
268
PLC Connection Guide
Mitsubishi FX0s/FX0n/FX1s/FX1n/FX2
Supported Series: Mitsubishi FX0s/FX0n/FX1s/FX1n/FX2 PLC
Website: http://www.mitsubishi-automation.com
HMI Setting:
Parameters Recommended Options Notes
PLC type Mitsubishi FX0s/FX0n/FX1s/FX1n/FX2
PLC I/F RS485 4W RS232/RS485
9600/19200/38400/
Baud rate 9600
57600/115200
Data bits 7 7,8
Parity Even Even, Odd, None
Stop bits 1 1,2
PLC sta. no. 0 0-255
Device Address:
Bit/Word Device type Format Range Memo
B X OOO 0 ~ 377 Input Relay
B Y OOO 0 ~ 377 Output Relay
B M DDDD 0 ~ 9999 Auxiliary Relay
B T DDD 0 ~ 255 Timer Relay
B C DDD 0 ~ 255 Counter Relay
B SM DDDD 8000 ~ 9999 Special Aux. Relays
B D_Bit DDDDdd 0 ~ 999915 Data Register Bit (D)
B S DDDD 0 ~ 4095 States
W TV DDD 0 ~ 255 Timer Memory
W CV DDD 0 ~ 199 Counter Memory
W D DDDD 0 ~ 9999 Data Register
DW CV2 DDD 200 ~ 255 Counter Memory(D Word)
W SD DDDD 8000 ~ 9999 Special Data Register
269
PLC Connection Guide
Wiring Diagram:
The following represents the cable end connector.
eMT3000 series
COM1 RS485 4W RS422 Port 8P
9P D-Sub Male Mini-DIN Male
1 RX- 4 TX-
2 RX+ 7 TX+
3 TX- 1 RX-
4 TX+ 2 RX+
5 GND 3 GND
MT6050i/MT8050i
COM1 RS485 4W RS422 Port 8P
9P D-Sub Female Mini-DIN Male
1 RX- 4 TX-
2 RX+ 7 TX+
3 TX- 1 RX-
4 TX+ 2 RX+
5 GND 3 GND
270
PLC Connection Guide
The following represents the cable end connector..
9P D-Sub to 25P D-Sub:
eMT3000 series
COM1 RS485 4W RS422 Port 8P
9P D-Sub Male Mini-DIN Male
1 RX- 16 TXD-
2 RX+ 3 TXD+
3 TX- 15 RXD-
4 TX+ 2 RXD+
5 GND 7 GND
4 DSR+ circuit
8 GND
13 +5V
circuit
17 DSR-
271
PLC Connection Guide
MT6050i/MT8050i
COM1 RS485 4W RS422 Port 8P
9P D-Sub Female Mini-DIN Male
1 RX- 16 TXD-
2 RX+ 3 TXD+
3 TX- 15 RXD-
4 TX+ 2 RXD+
5 GND 7 GND
4 DSR+ circuit
8 GND
13 +5V
circuit
17 DSR-
Driver Version:
Version Date Description
V1.20 Oct/26/2011
272
PLC Connection Guide
Mitsubishi FX232/485BD
Supported Series: Mitsubishi FX0n/FX2/FX2n COM for Communication Module BD
FX2N-485-BD, FX2N-232-BD, FX1N-485-BD, FX1N-232-BD & FX3U-485ADP.
Website: http://www.mitsubishi-automation.com
HMI Setting:
Parameters Recommended Options Notes
PLC type Mitsubishi FX232/485BD
in accordance with the BD
PLC I/F RS232/RS485 RS232/RS485 2w/4w
module
Baud rate 19200 9600/19200/38400
Data bits 7 7,8
Parity Even Even, Odd, None
Stop bits 1 1,2
PLC sta. no. 1 0-15
Note: It is recommended to set turn around delay to 8. (For RS485 2W)
PLC Setting:
Communication mode Must set PLC station when useing BD Module.
Register D8120 setting: set b9 and b8 of BFM#0 to 0.
273
PLC Connection Guide
Device Address:
Bit/Word Device type Format Range Memo
B X OOO 0 ~ 377 Input Relay
B Y OOO 0 ~ 377 Output Relay
B M DDDD 0 ~ 7999 Auxiliary Relay
B T DDD 0 ~ 511 Timer Relay
B C DDD 0 ~ 255 Counter Relay
B SM DDDD 8000 ~ 9999 Special Auxiliary Relay
B D_Bit DDDDh 0 ~ 7999f Data Register Bit
B S DDDD 0 ~ 4095 State Relay
W TV DDD 0 ~ 255 Timer Memory
W CV DDD 0 ~ 199 Counter Memory
W D DDDD 0 ~ 7999 Data Register
W CV2 DDD 200 ~ 255 Counter Memory(D Word)
W SD DDDD 8000 ~ 9999 Special Data Register
Wiring Diagram:
The following represents the cable end connector.
9P D-Sub to 9P D-Sub: Communication Module RS232BD
eMT3000 series
COM1 RS232 9P COM3 RS232 9P RS232 9P D-Sub Male
D-Sub Female D-Sub Female
2 RX 8 RX 3 TXD
3 TX 7 TX 2 RXD
5 GND 5 GND 5 GND
274
PLC Connection Guide
MT6000/8000 series except MT6050i/MT8050i
COM1 RS232 9P COM2 RS232 9P COM3 RS232 9P RS232 9P D-Sub Male
D-Sub Female D-Sub Female D-Sub Male
2 RX 6 RX 8 RX 3 TXD
3 TX 4 TX 7 TX 2 RXD
5 GND 5 GND 5 GND 5 GND
MT6050i/MT8050i
COM1 RS232 9P RS232 9P D-Sub Male
D-Sub Female
9 RX 3 TXD
6 TX 2 RXD
5 GND 5 GND
275
PLC Connection Guide
MT6000/8000 series except MT6050i/MT8050i
COM1 RS485 4W 485BD Module 5P
9P D-Sub Male Termanal
1 RX- SDB
2 RX+ SDA
3 TX- RDB
4 TX+ RDA
5 GND SG
MT6050i/MT8050i
COM1 RS485 4W 485BD Module 5P
9P D-Sub Female Termanal
1 RX- SDB
2 RX+ SDA
3 TX- RDB
4 TX+ RDA
5 GND SG
276
PLC Connection Guide
MT6000/8000 series except MT6050i/MT8050i
COM1 RS485 2W COM3 RS485 2W 485BD Module 5P
9P D-Sub Male 9P D-Sub Male Termanal
1 RX- 6 Data- SDB
circuit
RDB
2 RX+ 9 Data+ SDA
circuit
RDA
5 GND 5 GND SG
MT6050i/MT8050i
COM1 RS485 2W COM3 RS485 2W 485BD Module 5P
9P D-Sub Female 9P D-Sub Female Termanal
1 RX- 7 Data- SDB
circuit
RDB
2 RX+ 8 Data+ SDA
circuit
RDA
5 GND 5 GND SG
Driver Version:
Version Date Description
V1.40 Jul/26/2011 Added registers: D_Bit and S.
277
PLC Connection Guide
Mitsubishi FX2n
Supported Series: Mitsubishi FX1n/FX2n series PLC
Website http://www.mitsubishi-automation.com
HMI Setting:
Parameters Recommended Options Notes
PLC type Mitsubishi FX2n
PLC I/F RS485 4W RS232/RS485
Baud rate 19200 9600/19200/38400
Data bits 7 /57600/115200
Parity Even
Stop bits 1
PLC sta. no. 0
Device Address:
Bit/Word Device type Format Range Memo
B X OOO 0 ~ 377 Input Relay
B Y OOO 0 ~ 377 Output Relay
B M DDDD 0 ~ 7999 Auxiliary Relay
B T DDD 0 ~ 255 Timer Relay
B C DDD 0 ~ 255 Counter Relay
B SM DDDD 8000 ~ 9999 Special Auxiliary Relay
B D_Bit DDDDdd 0 ~ 799915 Data Register Bit (D)
B S DDDD 0 ~ 4095 State Relay (S)
W TV DDD 0 ~ 255 Timer Memory
W CV DDD 0 ~ 199 Counter Memory
W D DDDD 0 ~ 7999 Data Register
DW CV2 DDD 200 ~ 255 Counter Memory(D Word)
W SD DDDD 8000 ~ 9999 Special Data Register
278
PLC Connection Guide
Wiring Diagram:
The following represents the cable end connector.
Mitsubishi FX series
eMT3000 series
COM1 RS485 4W RS422 8P Mini-DIN
9P D-Sub Male Male
1 RX- 4 TX-
2 RX+ 7 TX+
3 TX- 1 RX-
4 TX+ 2 RX+
5 GND 3 GND
279
PLC Connection Guide
MT6050i/MT8050i
COM1 RS485 4W RS422 8P Mini-DIN
9P D-Sub Female Male
1 RX- 4 TX-
2 RX+ 7 TX+
3 TX- 1 RX-
4 TX+ 2 RX+
5 GND 3 GND
Driver Version:
Version Date Description
V1.60 Sep/10/2009
280
PLC Connection Guide
Website: http://www.mitsubishi-automation.com
HMI Setting:
Parameters Recommended Options Notes
PLC type Mitsubishi FX3u (Ethernet)
PLC I/F Ethernet
Port no. 5001(default) Refer to Module Setting
PLC sta. no. 0 (default) Refer to Module Setting
PLC Setting:
Fx3u-ENET module setting:
Before using Ethernet module, use GX Developer / FX Configurator-EN to set the Ethernet
module, the FX3u-ENET module setting steps are shown below.
281
PLC Connection Guide
Step2. Select “FXCPU” in PLC series.
Step3. Connect PLC via serial port for setting IP address first.
282
PLC Connection Guide
Step4. After finishing the PLC settings, select Tools/FX special function utility/FX
Configurator-EN.
283
PLC Connection Guide
Step6. In Ethernet operational settings, select the related parameters and IP address and
then press ”End” to finish setting.
Step7. In Ethernet open settings, press “End” after setting the parameters below.
(The first Protocol means using GX Developer to communicate with module, the max.
“Fixed buffer communication preocedure” is 4 units.)
284
PLC Connection Guide
Or
285
PLC Connection Guide
Step8. After setting the parameters of PLC, restart for Ethernet communication.
Device Address:
Bit/Word Device type Format Range Memo
B X OOO 0 ~ 571 Input
B Y OOO 0 ~ 571 Output Relay
B M DDDD 0 ~ 7999 Internal Relay
B T DDD 0 ~ 511 Timer Contacts
B C DDD 0 ~ 255 Counter Contacts
B SM DDDD 8000 ~ 8511 Special Int. Relays
B D_Bit DDDDDdd 0 ~ 1799915 Data Register Bit Access
B S DDDD 0 ~ 4095 Step Relays
W TV DDD 0 ~ 511 Timer Value
W CV DDD 0 ~ 199 Counter Value
W D DDDD 0 ~ 7999 Data Registers
W CV2 DDD 200 ~255 Counter Value
W SD DDDD 8000 ~ 8511 Special Data Registers
W R DDDDD 0 ~ 32767 File Register
286
PLC Connection Guide
Wiring Diagram:
Direct connect (crossover cable):
HMI RJ45 Male Wire Color PLC RJ45 Male
1 TX+ White/Orange 3 RX+
2 TX- Orange 6 RX-
3 RX+ White/Green 1 TX+
4 BD4+ Blue 4 BD4+
5 BD4- White/Blue 5 BD4-
6 RX- Green 2 TX-
7 BD3+ White/Brown 7 BD3+
8 BD3- Brown 8 BD3-
Through a hub:
HMI RJ45 Male Wire Color PLC RJ45 Male
1 TX+ White/Orange 1 TX+
2 TX- Orange 2 TX-
3 RX+ White/Green 3 RX+
4 BD4+ Blue 4 BD4+
5 BD4- White/Blue 5 BD4-
6 RX- Green 6 RX-
7 BD3+ White/Brown 7 BD3+
8 BD3- Brown 8 BD3-
Driver Version:
Version Date Description
V1.00 Feb/12/2009 Driver released.
287
PLC Connection Guide
Mitsubishi FX3u/FX3G
Supported Series: Mitsubishi FX3U/FX3UC/FX3G.
Website: http://www.mitsubishi-automation.com
HMI Setting:
Parameters Recommended Options Notes
PLC type Mitsubishi FX3u/FX3G
PLC I/F RS485 4w RS232/RS485
Baud rate 38400 2w/4w
9600/19200
Data bits 7
Parity Even
Stop bits 1
PLC sta. no. 0 Does not apply to this protocol
Online simulator YES (9600 baud rate only) Extend address mode NO
Device Address:
Bit/Word Device type Format Range Memo
B X OOO 0 ~ 764 Input Relay
B Y OOO 0 ~ 764 Output Relay
B M DDDD 0 ~ 7999 Auxiliary Relay
B T DDD 0 ~ 511 Timer Relay (T)
B C DDD 0 ~ 255 Counter Relay (C)
B SM DDDD 8000 ~ 9999 Special Relay (M)
B D_Bit DDDDdd 0 ~ 799915 Data Register Bit (D)
B S DDDD 0 ~ 4095 State Relay (S)
W TV DDD 0 ~ 511 Timer Memory (T)
W CV DDD 0 ~ 199 Counter Memory (C)
W D DDDD 0 ~ 7999 Data Register (D)
DW CV2 DDD 200 ~ 255 Counter Memory(D Word)
W SD DDDD 8000 ~ 9999 Special Data Register (D)
W R DDDDD 0 ~ 32767 Extended Register (R)
W Z D 0~7 Index register
288
PLC Connection Guide
Wiring Diagram:
The following represents the cable end connector.
eMT3000 series
COM1 RS485 4W RS422 8P Mini-DIN
9P D-Sub Male Male
1 RX- 4 TX-
2 RX+ 7 TX+
3 TX- 1 RX-
4 TX+ 2 RX+
5 GND 3 GND
MT6050i/MT8050i
COM1 RS485 4W RS422 8P Mini-DIN
9P D-Sub Female Male
1 RX- 4 TX-
2 RX+ 7 TX+
3 TX- 1 RX-
4 TX+ 2 RX+
5 GND 3 GND
289
PLC Connection Guide
Driver Version:
Version Date Description
V1.71 Nov/15/2010
290
PLC Connection Guide
HMI Setting:
Parameters Recommended Options Notes
PLC type Mitsubishi MELSEC-Q/L (Ethernet)
PLC I/F Ethernet
Set identically to the PLC
Port no. Adviced to set port no. to 4999
setting
Networking no. (Set
Parameter 1 0~255 Q13UDEH has to be set to 0
identically to PLC setting)
Set identically to the PLC Q13UDEH has to be set to
PLC sta. no. 255
setting 255
PLC Setting:
MITSUBISHI Q/L series Ethernet module setting:
Note: If using QJ71E71 module, please refer to MITSUBISHI QJ71E71 connection guide.
291
PLC Connection Guide
1. Click [PLC parameter].
2. [Built-in Ethernet port].
3. Click [Open settings] and then set the IP address and communication data code
4. Set the MC protocol-TCP Port No.1387 (Hex) and in EasyBuilder, TCP port is 4999
(Dec).
292
PLC Connection Guide
Device Address:
Bit/Word Device type Format Range Memo
B SM DDDD 0 ~ 2047 Special Relay
B X HHHH 0 ~ 1fff Input Relay
B Y HHHH 0 ~ 1fff Output Relay
B M DDDDD 0 ~ 61439 Internal Relay
B L DDDDD 0 ~ 32767 Latch Relay
B F DDDDD 0 ~ 32767 Annunciator
B V DDDDD 0 ~ 32767 Edge Relay
B B HHHH 0 ~ efff Link Relay
B TS DDDDD 0 ~ 25471 Timer Contact
B TC DDDDD 0 ~ 25471 Timer Coil
B SS DDDDD 0 ~ 25471 Retentive Timer Contact
B SC DDDDD 0 ~ 25471 Retentive Timer Coil
B CS DDDDD 0 ~ 25471 Counter Contact
B CC DDDDD 0 ~ 25471 Counter Coil
B SB HHHH 0 ~ 7fff Special Link Relay
B S DDDD 0 ~ 8191 Step relay
B DX HHHH 0 ~ 1fff Direct Input
B DY HHHH 0 ~ 1fff Direct Output
B D_Bit DDDDDDDh 0 ~ 4184063f Data Register bit
B SD_bit DDDDh 0 ~ 2047f Special register Bit
B ZR_bit HHHHHHh 0 ~ 3fd7fff File Register Bit
B R_bit DDDDDh 0 ~ 32767f File Register Bit
B SW_bit HHHh 0 ~ 7fff Special Link Register Bit
B W_bit HHHHHHh 0 ~ 3fd7fff Link Register Bit
W SD DDDD 0 ~ 2047 Special register
W D DDDDDDD 0 ~ 4184063 Data Register
W W HHHHHH 0 ~ 3fd7ff Link Register
W TN DDDDD 0 ~ 25471 Timer Current value
Retentive Timer Current
W SN DDDDD 0 ~ 25471
value
W CN DDDDD 0 ~ 25471 Counter Current value
W SW HHH 0 ~ 7ff Special Link Register
W Z DD 0 ~ 20 Index Register
W R DDDDD 0 ~ 32767 File Register
W ZR HHHHHH 0 ~ 3fd7ff File Register
293
PLC Connection Guide
Note: Each model of CPU is different, it is recommended to refer to MITSUBISHI
MELSEC-Q Manual Device List.
Wiring Diagram:
Direct connect (crossover cable):
HMI RJ45 Male Wire Color PLC RJ45 Male
1 TX+ White/Orange 3 RX+
2 TX- Orange 6 RX-
3 RX+ White/Green 1 TX+
4 BD4+ Blue 4 BD4+
5 BD4- White/Blue 5 BD4-
6 RX- Green 2 TX-
7 BD3+ White/Brown 7 BD3+
8 BD3- Brown 8 BD3-
Through a hub:
HMI RJ45 Male Wire Color PLC RJ45 Male
1 TX+ White/Orange 1 TX+
2 TX- Orange 2 TX-
3 RX+ White/Green 3 RX+
4 BD4+ Blue 4 BD4+
5 BD4- White/Blue 5 BD4-
6 RX- Green 6 RX-
7 BD3+ White/Brown 7 BD3+
8 BD3- Brown 8 BD3-
Driver Version:
Version Date Description
V1.30 Jan/14/2011
294
PLC Connection Guide
Mitsubishi MR J3 A
Website: http://www.mitsubishi-automation.com
HMI Setting:
Parameters Recommended Options Notes
PLC type Mitsubishi MR J3 A
PLC I/F RS485 4W RS232/RS485
Baud rate 9600 9600~115200
Parity Even
Data bits 8
Stop bits 1
PLC sta. no. 0 0~31
Device Address:
Bit/Word Device type Format Range Memo
B EIP DD 0 ~ 31 External input pin status read**
B EOP DD 0 ~ 31 External output pin status read**
W PA DD 1 ~ 19 Basic Setting
W PB DD 1 ~ 45 Gain / Filter Setting
W PC DD 1 ~ 50 Extension Setting
W PD DD 1 ~ 30 Input / Output Setting
W Status DD 0 ~ 17 Amplifier Status
W Alarm D 0~6 Alarm
W Alarm_T D 0~6 Alarm Time (Hour)
W Mode D 1~4 Write Only, Mode Setting*
W Speed D 0~1 Write Only, Set Current Speed *
W Acc D 0~1 Write Only, Set Acceleration*
W Rotation D 0~1 Write Only, Rotation Direction*
W End D 0~1 Write Only, End*
W M_dist D 0~1 Write Only, Moving Distance*
W Rot_P D 0~1 Write Only, Rotation Position*
W P_start D 0~1 Write Only, Start Positioning*
Note: 1.* represents the write-only registers. The usage of this kind of registers is to run
Jog Mode and Positioning Mode.
2.** represents the read-only registers.
295
PLC Connection Guide
EIP:
EOP:
296
PLC Connection Guide
How to use EasyBuilder8000/Easy BuilderPro to run Jog and Positioning Mode
*Jog Mode
To run Jog Mode, please follow the steps listed sequentially:
(1) Set Jog Mode
(2) Set rotation speed
(3) Set acceleration
(4) Set forward / reverse rotation direction
(5) End
The following shows how to run the steps above using Macro in
EasyBuilder8000/Easy BuilderPro.
Macro Demonstration:
a. Start Macro
macro_command main()
short speed
short acc
short mode
mode = 1 // This represents Jog Mode.
297
PLC Connection Guide
short motion
motion = 0x0801 // Special code, see Note 1.
end macro_command
b. End Macro
macro_command main()
short stop
stop = 1 // See Note 2.
end macro_command
298
PLC Connection Guide
*Positioning Mode
Macro Demonstration:
macro_command main()
short mode
mode = 0x2 // Positioning Mode
SetData(mode, "MITSUBISHI MR J3 A", Mode, 1, 1)
short speed
GetData(speed, "Local HMI", LW, 2, 1)
SetData(speed, "MITSUBISHI MR J3 A", Speed, 0, 1)
short acc
GetData(acc, "Local HMI", LW, 3, 1)
SetData(acc, "MITSUBISHI MR J3 A", Acc, 0, 1)
short dist
GetData(dist, "Local HMI", LW, 4, 1)
SetData(dist, "MITSUBISHI MR J3 A", M_dist, 0, 1)
short rot_P
rot_P = 1 // Set to 0: Forward Rotation 1: Reverse Rotation
SetData(rot_P, "MITSUBISHI MR J3 A", Rot_P, 0, 1)
short rotat
rotat = 1 // See Note 3.
299
PLC Connection Guide
SetData(rotat, "MITSUBISHI MR J3 A", Rotation, 0, 1)
end macro_command
Wiring Diagram:
The following represents the cable end connector.
eMT3000 series
COM1 RS485 4W CN3 RS485 4W RJ45
9P D-Sub Male Male
1 RX- 4 TX-
2 RX+ 5 TX+
3 TX- 6 RX-
4 TX+ 3 RX+
5 GND 7 GND
300
PLC Connection Guide
MT6050i/MT8050i
COM1 RS485 4W CN3 RS485 4W RJ45
9P D-Sub Female Male
1 RX- 4 TX-
2 RX+ 5 TX+
3 TX- 6 RX-
4 TX+ 3 RX+
5 GND 7 GND
Driver Version:
Version Date Description
V1.00 Sep/01/2011 Driver released.
V1.10 Jan/13/2012 Added register: EIP and EOP.
301
PLC Connection Guide
HMI Setting:
Parameters Recommended Options Notes
PLC type Mitsubishi MR-MQ100 (Ethernet)
PLC I/F Ethernet
Set identically to the PLC Adviced to set port no. to
Port no.
setting 4999
Parameter1 1 Network No.
PLC sta. no. 255
PLC Setting:
302
PLC Connection Guide
1. Click [Basic Setting].
2. [Built-in Ethernet Port Setting].
3. Click [Open Setting] and then set the IP address and communication data code.
4. Set the MC Protocol-TCP Port No. (Hex)
Device Address:
Bit/Word Device type Format Range Memo
B SM DDDD 0 ~ 2255 Special Relay
B X HHHH 0 ~ 1fff Input
B Y HHHH 0 ~ 1fff Output
B M DDDDD 0 ~ 61439 Internal Relay
B F DDDDD 0 ~ 32767 Annunciator
B B HHHH 0 ~ efff Link Relay
B D_Bit DDDDDDDh 0 ~ 4184063f
W SD DDDD 0 ~ 2255 Special Register
W D DDDDDDD 0 ~ 4184063 Data Register
W W HHHHHH 0 ~ 3fd7ff Link Register
W # DDDDD 0 ~ 12287 Motion Register
Note: ddd: Decimal, hhh: Hexadecimal, ooo: Octal.
Wiring Diagram:
Direct connect (crossover cable):
HMI RJ45 Male Wire Color PLC RJ45 Male
1 TX+ White/Orange 3 RX+
2 TX- Orange 6 RX-
3 RX+ White/Green 1 TX+
4 BD4+ Blue 4 BD4+
5 BD4- White/Blue 5 BD4-
6 RX- Green 2 TX-
7 BD3+ White/Brown 7 BD3+
8 BD3- Brown 8 BD3-
303
PLC Connection Guide
Through a hub:
HMI RJ45 Male Wire Color PLC RJ45 Male
1 TX+ White/Orange 1 TX+
2 TX- Orange 2 TX-
3 RX+ White/Green 3 RX+
4 BD4+ Blue 4 BD4+
5 BD4- White/Blue 5 BD4-
6 RX- Green 6 RX-
7 BD3+ White/Brown 7 BD3+
8 BD3- Brown 8 BD3-
Driver Version:
Version Date Description
V1.10 Jun/08/2011 Added register: D_Bit
304
PLC Connection Guide
Mitsubishi Q00/Q00UJ/Q01/QJ71
Supported Series: Mitsubishi Q series PLC with QJ71C24 communication module, Q00,
Q00J, Q00UJ, Q01, Q02H, Q06H, Q12H, Q25H, Q12PH, Q25PH CPU port.
Website: http://www.mitsubishi-automation.com
HMI Setting:
Parameters Recommended Options Notes
PLC type Mitsubishi Q00/Q00UJ/Q01/QJ71
PLC I/F RS232 RS485 4W, RS232
Baud rate 9600 9600~115200
Data bits 8
Parity Odd
Stop bits 1
PLC sta. no. 0
PLC Setting:
Q00, Q01 CPU port setting:
1. In GX Developer “PLC data list” click [PLC parameter].
2. In “PLC parameter” go to [Serial] page.
3. Select [Use serial communication].
4. Set [Transmission speed] to 9600~115200.
5. Select [Sum check].
6. Set [Transmission wait time] to 10ms.
7. Permit [RUN write setting].
8. Click [End] to close the dialog.
9. Write the PLC Parameter to PLC.
10. Reset PLC, the parameter will be actived.
305
PLC Connection Guide
QJ71 setting:
306
PLC Connection Guide
Device Address:
Bit/Word Device type Format Range Memo
B X HHHH 0 ~ 1fff Input Relay
B Y HHHH 0 ~ 1fff Output Relay
B M DDDD 0 ~ 8191 Internal Relay
B L DDDD 0 ~ 8191 Latch Relay
B F DDDD 0 ~ 2047 Annunciator
B V DDDD 0 ~ 2047 Edge Relay
B B HHHH 0 ~ 1fff Link Relay
B TC DDDD 0 ~ 2047 Timer Coil
B SS DDDD 0 ~ 2047 Retentive Timer Contact
B SC DDDD 0 ~ 2047 Retentive Timer Coil
B CS DDDD 0 ~ 1023 Counter Contact
B CC DDDD 0 ~ 1023 Counter Coil
B SB HHH 0 ~ 7ff Special Link Relay
B S DDDD 0 ~ 8191 Step Relay
B DX HHHH 0 ~ 1fff Direct Input
B DY HHHH 0 ~ 1fff Direct Output
B TS DDDD 0 ~ 2047 Timer Contact
B SM DDDD 0 ~ 2047
B D_Bit DDDDDh 0 ~ 12287f
W W HHHH 0 ~ 2fff Link Register
W TN DDDD 0 ~ 2047 Timer Current Value
W SN DDDD 0 ~ 2047 Retentive Timer Current Value
W CN DDDD 0 ~ 1023 Counter Current Value
W R DDDDD 0 ~ 32767 File Register
W SW HHH 0 ~ 7ff Special Link Register
W Z DD 0 ~ 15 Index Register
W ZR HHHH 0 ~ ffff File Register
W D DDDDD 0 ~ 12287 Data Register
W SD DDDD 0 ~ 2047
307
PLC Connection Guide
Wiring Diagram:
The following represents the cable end connector.
QJ71C24 CH.2 RS422 Terminal
eMT3000 series
COM1 RS485 4W QJ71C24 CH.2 RS422
9P D-Sub Male Terminal
1 RX- SDB
2 RX+ SDA
3 TX- RDB
4 TX+ RDA
5 GND GND
308
PLC Connection Guide
MT6050i/MT8050i
COM1 RS485 4W QJ71C24 CH.2 RS422
9P D-Sub Female Terminal
1 RX- SDB
2 RX+ SDA
3 TX- RDB
4 TX+ RDA
5 GND GND
309
PLC Connection Guide
MT6000/8000 series except MT6050i/MT8050i
COM1 RS232 9P COM2 RS232 9P COM3 RS232 9P QJ71C24 CH.1 RS232
D-Sub Female D-Sub Female D-Sub Male 9P D-Sub Male
2 RX 6 RX 8 RX 3 TXD
3 TX 4 TX 7 TX 2 RXD
5 GND 5 GND 5 GND 5 GND
1 DCD
4 DTR circuit
6 DSR
7 RTS
circuit
8 CTS
MT6050i/MT8050i
COM1 RS232 9P QJ71C24 CH.1 RS232
D-Sub Female 9P D-Sub Male
9 RX 3 TXD
6 TX 2 RXD
5 GND 5 GND
1 DCD
4 DTR circuit
6 DSR
7 RTS
circuit
8 CTS
310
PLC Connection Guide
The following represents the cable end connector.
9P D-Sub to 6P Mini-DIN: Q00, Q01 CPU port RS232
eMT3000 series
COM1 RS232 9P COM3 RS232 9P RS232 6P Mini-DIN
D-Sub Female D-Sub Female Male
2 RX 8 RX 3 TXD
3 TX 7 TX 4 RXD
5 GND 5 GND 5 GND
MT6050i/MT8050i
COM1 RS232 9P RS232 6P Mini-DIN
D-Sub Female Male
9 RX 3 TXD
6 TX 4 RXD
5 GND 5 GND
311
PLC Connection Guide
The following represents the cable end connector.
9P D-Sub to 6P Mini-DIN: Q00UJ CPU port RS232
eMT3000 series
COM1 RS232 9P COM3 RS232 9P RS232 6P Mini-DIN
D-Sub Female D-Sub Female Male
2 RX 8 RX 3 TXD
3 TX 7 TX 4 RXD
5 GND 5 GND 5 GND
1 RTS
circuit
6 CTS
MT6050i/MT8050i
COM1 RS232 9P RS232 6P Mini-DIN
D-Sub Female Male
9 RX 3 TXD
6 TX 4 RXD
5 GND 5 GND
1 RTS
circuit
6 CTS
312
PLC Connection Guide
Driver Version:
Version Date Description
V1.80 Jun/08/2011 Added register: D_Bit
V1.90 Sep/23/2011 Fixed bit communication incorrect.
313
PLC Connection Guide
Mitsubishi Q00J
Supported Series: Mitsubishi Q00J CPU
HMI Setting:
Parameters Recommended Options Notes
PLC type Mitsubishi Q00J
PLC I/F RS232 CPU port
9600,19200,38400,
Baud rate 115200
57600,115200
Data bits 8
Parity Odd
Stop bits 1
PLC sta. no.
Device Address:
Bit/Word Device type Format Range Memo
B SM DDDD 0 ~ 1023
B X HHH 0 ~ 7ff
B Y HHH 0 ~ 7ff
B M DDDD 0 ~ 8191
B L DDDD 0 ~ 2047
B F DDDD 0 ~ 1023
B V DDDD 0 ~ 1023
B B HHH 0 ~ 7ff
B SB HHH 0 ~ 3ff
B D_Bit DDDDDh 0 ~ 11135f
W SD DDDD 0 ~ 1023
W D DDDDD 0 ~ 11135
W W HHH 0 ~ 7ff
W SW HHH 0 ~ 3ff
W Z D 0~9
W C DDD 0 ~ 511
W T DDD 0 ~ 511
314
PLC Connection Guide
Wiring Diagram:
The following represents the cable end connector.
9P D-Sub to 6P Mini-DIN: Q00 CPU port RS232
eMT3000 series
COM1 RS232 9P COM3 RS232 9P RS232 6P Mini-DIN
D-Sub Female D-Sub Female Male
2 RX 8 RX 3 TXD
3 TX 7 TX 4 RXD
5 GND 5 GND 5 GND
MT6050i/MT8050i
COM1 RS232 9P RS232 6P Mini-DIN
D-Sub Female Male
9 RX 3 TXD
6 TX 4 RXD
5 GND 5 GND
Driver Version:
Version Date Description
V1.20 Jun/08/2011 Added register D_bit
315
PLC Connection Guide
Mitsubishi Q00U/Q01U/Q02U/QnUD/QnUDH
Supported Series: Mitsubishi Q00U, Q01U, Q02U, Q03UD, Q04UDH, Q06UDH, Q10UDH,
Q13UDH, Q20UDH, Q26UDH CPU.
HMI Setting:
Parameters Recommended Options Notes
PLC type Mitsubishi Q00U/Q01U/Q02U/QnUD/QnUDH
PLC I/F RS232 RS485 4W, RS232 CPU port direct connect
9600,19200,38400,57600,115200
Baud rate 115200 115200 only
For Q00UJ, only 9600 is available
Data bits 8
Parity Odd
Stop bits 1
PLC sta. no. No
Device Address:
Bit/Word Device type Format Range Memo
B SM DDDD 0 ~ 2047
B X HHHH 0 ~ 1fff Input Relay
B Y HHHH 0 ~ 1fff Output Relay
B M DDDD 0 ~ 8191 Internal Relay
B L DDDD 0 ~ 8191 Latch Relay
B F DDDD 0 ~ 2047 Annunciator
B V DDDD 0 ~ 2047 Edge Relay
B B HHHH 0 ~ 1fff Link Relay
B SB HHH 0 ~ 7ff Special Link Relay
B D_Bit DDDDDh 0 ~ 12287f
W SD DDDD 0 ~ 2047
W D DDDDD 0 ~ 12287 Data Register
W W HHHH 0 ~ 1fff Link Register
W SW HHH 0 ~ 7ff Special Link Register
W Z DD 0 ~ 19 Index Register
W R DDDDD 0 ~ 32767
W C DDDD 0 ~ 1023 Counter Current Value
W T DDDD 0 ~ 2047 Timer Current Value
316
PLC Connection Guide
Note:
EasyBuilder doesn’t support MITSUBISHI Q02U CPU to do on-line simulation on PC.
When using Q02U driver, HMI needs 10 seconds to initiate PLC Q02U driver. Before the
completion of initiation, it is recommended not to wrire data to PLC, this could cause “PLC
no response”; Incorrect wiring or data could cause PLC to be locked. If PLC is locked,
please restart PLC or reinstall PLC module.
Wiring Diagram:
The following represents the cable end connector.
9P D-Sub to 6P Mini-DIN: Q02 CPU port RS232
eMT3000 series
COM1 RS232 9P COM3 RS232 9P RS232 6P Mini-DIN
D-Sub Female D-Sub Female Male
2 RX 8 RX 3 TXD
3 TX 7 TX 4 RXD
5 GND 5 GND 5 GND
1 RTS
circuit
6 CTS
317
PLC Connection Guide
MT6050i/MT8050i
COM1 RS232 9P RS232 6P Mini-DIN
D-Sub Female Male
9 RX 3 TXD
6 TX 4 RXD
5 GND 5 GND
1 RTS
circuit
6 CTS
Driver Version:
Version Date Description
V1.60 Jun/08/2011 Added register D_bit
318
PLC Connection Guide
Mitsubishi Q00UJ/QnU/QnUD/QnUDH/QnUDEH
(mini USB)
Supported Series: Mitsubishi Q00UJ, Q00U, Q01U, Q02U, Q03UDE, Q03UD, Q04UDEH,
Q04UDH, Q06UDEH, Q06UDH, Q10UDEH, Q10UDH, Q13UDEH, Q13UDH, Q20UDEH,
Q20UDH, Q26UDEH, Q26UDH USB Port.
HMI Setting:
Parameters Recommended Options Notes
PLC type Mitsubishi Q00UJ/QnU/QnUD/QnUDH/QnUDEH (mini USB)
PLC I/F USB CPU port direct connect
Device Address:
Bit/Word Device type Format Range Memo
B SM DDDD 0 ~ 2047
B X HHHH 0 ~ 1fff Input Relay
B Y HHHH 0 ~ 1fff Output Relay
B M DDDD 0 ~ 8191 Internal Relay
B L DDDD 0 ~ 8191 Latch Relay
B F DDDD 0 ~ 2047 Annunciator
B V DDDD 0 ~ 2047 Edge Relay
B B HHHH 0 ~ 1fff Link Relay
B SB HHH 0 ~ 7ff Special Link Relay
B D_Bit DDDDDh 0 ~ 12287f
W SD DDDD 0 ~ 2047
W D DDDDD 0 ~ 12287 Data Register
W W HHHH 0 ~ 1fff Link Register
W SW HHH 0 ~ 7ff Special Link Register
W Z DD 0 ~ 19 Index Register
W R DDDDD 0 ~ 32767
W C DDDD 0 ~ 1023 Counter Current Value
W T DDDD 0 ~ 2047 Timer Current Value
319
PLC Connection Guide
Note:
EasyBuilder doesn’t support MITSUBISHI Q02U CPU to do on-line simulation on PC.
When using Q02U driver, HMI needs 10 seconds to initiate PLC Q02U driver. Before the
completion of initiation, it is recommended not to wrire data to PLC, this could cause “PLC
no response”; Incorrect wiring or data could cause PLC to be locked. If PLC is locked,
please restart PLC or reinstall PLC module.
Driver Version:
Version Date Description
V1.30 Jun/08/2011 Added register D_bit
320
PLC Connection Guide
Mitsubishi Q02/02H
Supported Series; Mitsubishi Q02/Q02H CPU port.
Website: http://www.mitsubishi-automation.com
HMI Setting:
Parameters Recommended Options Notes
PLC type Mitsubishi Q02/02H
PLC I/F RS232 RS485 4W, RS232
Baud rate 115200 115200 only
Data bits 8
Parity Odd
Stop bits 1
PLC sta. no. 0
Device Address:
Bit/Word Device type Format Range Memo
B X HHHH 0 ~ 1fff Input Relay
B Y HHHH 0 ~ 1fff Output Relay
B M DDDD 0 ~ 8191 Internal Relay
B L DDDD 0 ~ 8191 Latch Relay
B F DDDD 0 ~ 2047 Annunciator
B V DDDD 0 ~ 2047 Edge Relay
B B HHHH 0 ~ 1fff Link Relay
B TC DDDD 0 ~ 2047 Timer Coil
B SS DDDD 0 ~ 2047 Retentive Timer Contact
B SC DDDD 0 ~ 2047 Retentive Timer Coil
B CS DDDD 0 ~ 1023 Counter Contact
B CC DDDD 0 ~ 1023 Counter Coil
B SB HHH 0 ~ 7ff Special Link Relay
B S DDDD 0 ~ 8191 Step Relay
321
PLC Connection Guide
Bit/Word Device type Format Range Memo
B DX HHHH 0 ~ 1fff Direct Input
B DY HHHH 0 ~ 1fff Direct Output
B TS DDDD 0 ~ 2047 Timer Contact
B D_Bit DDDDDh 0 ~ 12287f
W W HHHH 0 ~ 1fff Link Register
W TN DDDD 0 ~ 2047 Timer Current Value
W SN DDDD 0 ~ 2047 Retentive Timer Current Value
W CN DDDD 0 ~ 1023 Counter Current Value
W R DDDDD 0 ~ 32767 File Register
W SW HHH 0 ~ 7ff Special Link Register
W Z DD 0 ~ 15 Index Register
W ZR HHHH 0 ~ ffff File Register
W D DDDDD 0 ~ 12287 Data Register
Wiring Diagram:
The following represents the cable end connector.
9P D-Sub to 6P Mini-DIN: Q02 CPU port RS232
eMT3000 series
COM1 RS232 9P COM3 RS232 9P RS232 6P Mini-DIN
D-Sub Female D-Sub Female Male
2 RX 8 RX 3 TXD
3 TX 7 TX 4 RXD
5 GND 5 GND 5 GND
1 RTS
circuit
6 CTS
322
PLC Connection Guide
MT6000/8000 series except MT6050i/MT8050i
COM1 RS232 9P COM2 RS232 9P COM3 RS232 9P RS232 6P Mini-DIN
D-Sub Female D-Sub Female D-Sub Male Male
2 RX 6 RX 8 RX 3 TXD
3 TX 4 TX 7 TX 4 RXD
5 GND 5 GND 5 GND 5 GND
1 RTS
circuit
6 CTS
MT6050i/MT8050i
COM1 RS232 9P RS232 6P Mini-DIN
D-Sub Female Male
9 RX 3 TXD
6 TX 4 RXD
5 GND 5 GND
1 RTS
circuit
6 CTS
Driver Version:
Version Date Description
V1.60 Jun/08/2011 Added register D_bit
323
PLC Connection Guide
Mitsubishi Q06H
Supported Series: Mitsubishi Q06H CPU port.
Website: http://www.mitsubishi-automation.com
HMI Setting:
Parameters Recommended Options Notes
PLC type Mitsubishi Q06H
PLC I/F RS232 RS485 4W, RS232
Baud rate 115200 115200 only
Data bits 8
Parity Odd
Stop bits 1
PLC sta. no. 0
Device Address:
Bit/Word Device type Format Range Memo
B X HHHH 0 ~ 1fff Input Relay
B Y HHHH 0 ~ 1fff Output Relay
B M DDDD 0 ~ 8191 Internal Relay
B L DDDD 0 ~ 8191 Latch Relay
B F DDDD 0 ~ 2047 Annunciator
B V DDDD 0 ~ 2047 Edge Relay
B B HHHH 0 ~ 1fff Link Relay
B TC DDDD 0 ~ 2047 Timer Coil
B SS DDDD 0 ~ 2047 Retentive Timer
B SC DDDD 0 ~ 2047 Contact Timer Coil
Retentive
B CS DDDD 0 ~ 1023 Counter Contact
B CC DDDD 0 ~ 1023 Counter Coil
B SB HHH 0 ~ 7ff Special Link Relay
B S DDDD 0 ~ 8191 Step Relay
324
PLC Connection Guide
Bit/Word Device type Format Range Memo
B DX HHHH 0 ~ 1fff Direct Input
B DY HHHH 0 ~ 1fff Direct Output
B TS DDDD 0 ~ 2047 Timer Contact
B D_Bit DDDDDh 0 ~ 12287f
W W HHHH 0 ~ 1fff Link Register
W TN DDDD 0 ~ 2047 Timer Current Value
W SN DDDD 0 ~ 2047 Retentive Timer
W CN DDDD 0 ~ 1023 Current Value
Counter Current Value
W R DDDDD 0 ~ 32767 File Register
W SW HHH 0 ~ 7ff Special Link Register
W Z DD 0 ~ 15 Index Register
W ZR HHHH 0 ~ ffff File Register
W D DDDDD 0 ~ 12287 Data Register
Wiring Diagram:
The following represents the cable end connector.
9P D-Sub to 6P Mini-DIN: Q02 CPU port RS232
eMT3000 series
COM1 RS232 9P COM3 RS232 9P RS232 6P Mini-DIN
D-Sub Female D-Sub Female Male
2 RX 8 RX 3 TXD
3 TX 7 TX 4 RXD
5 GND 5 GND 5 GND
1 RTS
circuit
6 CTS
325
PLC Connection Guide
MT6000/8000 series except MT6050i/MT8050i
COM1 RS232 9P COM2 RS232 9P COM3 RS232 9P RS232 6P Mini-DIN
D-Sub Female D-Sub Female D-Sub Male Male
2 RX 6 RX 8 RX 3 TXD
3 TX 4 TX 7 TX 4 RXD
5 GND 5 GND 5 GND 5 GND
1 RTS
circuit
6 CTS
MT6050i/MT8050i
COM1 RS232 9P RS232 6P Mini-DIN
D-Sub Female Male
9 RX 3 TXD
6 TX 4 RXD
5 GND 5 GND
1 RTS
circuit
6 CTS
Driver Version:
Version Date Description
V1.60 Jun/08/2011 Added register D_bit
326
PLC Connection Guide
Website: http://www.mitsubishi-automation.com
HMI Setting:
Parameters Recommended Options Notes
PLC type Mitsubishi QJ71E71 (Ethernet)
PLC I/F Ethernet
Port no. 5002
PLC sta. no. 2 1~99
PLC Setting:
QJ71E71-100 Ethernet module settings:
1. Use USB or RS232 of Q-CPU for setting PLC parameters.
327
PLC Connection Guide
2. Click [Operational settings] to set IP information.
328
PLC Connection Guide
3. Select Ethernet (2.0) for communicating with HMI.
329
PLC Connection Guide
5. Press [END] to finish settings.
6. Restart PLC software and select [READ FROM PLC], select [QCPU(Qmode)]
and press [OK].
7. In [PC side I/F Ethernet board setting] set Network No. and Station No.
(Station No.1 is PC Station No. not Ethernet module Station No., ranged
from 2~64, the Network No. can not be the same as that of PC)
330
PLC Connection Guide
8. Select “Ethernet module” in PLC Side I/F to set QJ71E71 IP address.(IP
address = Network Parameter IP address)
9. For “Other station”, click [Other station(Single network)”] for setting [Check
at communication time] and [Retry times].
10. After finishing the settings above, click [Connection test] for testing the
communication and sending the PLC program.
331
PLC Connection Guide
Device Address:
Bit/Word Device type Format Range Memo
B SM DDDD 0 ~ 2047
B X HHHH 0 ~ 1fff Input Relay
B Y HHHH 0 ~ 1fff Output Relay
B M DDDD 0 ~ 8191 Internal Relay
B L DDDD 0 ~ 8191 Latch Relay
B F DDDD 0 ~ 2047 Annunciator
B V DDDD 0 ~ 2047 Edge Relay
B B HHHH 0 ~ 1fff Link Relay
B TS DDDD 0 ~ 2047
B TC DDDD 0 ~ 2047
B SS DDDD 0 ~ 2047
B SC DDDD 0 ~ 2047
B CS DDDD 0 ~ 1023
B CC DDDD 0 ~ 1023
B SB HHH 0 ~ 7ff Special Link Relay
B S DDDD 0 ~ 8191
B DX HHHH 0 ~ 1fff Direct Input
B DY HHHH 0 ~ 1fff Direct Output
B D_Bit DDDDDh 0 ~ 12287f
W SD DDDD 0 ~ 2047
W D DDDDD 0 ~ 12287 Data Register
W W HHHH 0 ~ 1fff Link Register
W TN DDDD 0 ~ 2047
W SN DDDD 0 ~ 2047
W CN DDDD 0 ~ 1023
W SW HHH 0 ~ 7ff Special Link Register
W Z DD 0 ~ 15 Index Register
W R DDDDD 0 ~ 32767 File Register
W ZR HHHHH 0 ~ fe7ff File Register
332
PLC Connection Guide
Wiring Diagram:
Direct connect (crossover cable):
HMI RJ45 Male Wire Color PLC RJ45 Male
1 TX+ White/Orange 3 RX+
2 TX- Orange 6 RX-
3 RX+ White/Green 1 TX+
4 BD4+ Blue 4 BD4+
5 BD4- White/Blue 5 BD4-
6 RX- Green 2 TX-
7 BD3+ White/Brown 7 BD3+
8 BD3- Brown 8 BD3-
Through a hub:
HMI RJ45 Male Wire Color PLC RJ45 Male
1 TX+ White/Orange 1 TX+
2 TX- Orange 2 TX-
3 RX+ White/Green 3 RX+
4 BD4+ Blue 4 BD4+
5 BD4- White/Blue 5 BD4-
6 RX- Green 6 RX-
7 BD3+ White/Brown 7 BD3+
8 BD3- Brown 8 BD3-
Driver Version:
Version Date Description
V2.20 Jun/08/2011 Added register: D_bit
333
PLC Connection Guide
MODBUS ASCII
Supported Series: MODBUS ASCII CONTROLLER
Website: http://www.modbus.org
HMI Setting:
Parameters Recommended Options Notes
PLC type MODBUS ASCII
PLC I/F RS485 RS232/RS485
9600/19200/38400/
Baud rate 9600
57600/115200
Data bits 8 7,8
Parity Even Even, Odd, None
Stop bits 1 1,2
PLC sta. no. 1 0-255
PLC Setting:
Communication mode Modbus ASCII protocol
Device Address:
Bit/Word Device type Format Range Memo
B 1x DDDDD 1 ~ 65535 Input bit (read only)
B 0x DDDDD 1 ~ 65535 Output bit
B 3x_Bit DDDDDdd 100 ~ 6553515 Input Register bit (read only)
B 4x_Bit DDDDDdd 100 ~ 6553515 Output Register bit
W 3x DDDDD 1 ~ 65535 Input Register (read only)
W 4x DDDDD 1 ~ 65535 Output Register
W 6x DDDDD 1 ~ 65535
334
PLC Connection Guide
Modbus RTU function code:
0x 0x01 Read coil 0x05 write single coil
1x 0x02 Read discrete input N/A for write operation
3x 0x04 Read input register N/A for write operation
4x 0x03 Read holding register 0x10 write multiple registers
3xbit is equivalent to 3x
4xbit is equivalent to 4x
Wiring Diagram:
The following represents the cable end connector.
Modbus ASCII Controller : RS232
eMT3000 series
COM1 RS232 9P COM3 RS232 9P RS232 9P D-Sub
D-Sub Female D-Sub Female Female
2 RX 8 RX TXD
3 TX 7 TX RXD
5 GND 5 GND GND
RTS
circuit
CTS
335
PLC Connection Guide
MT6050i/MT8050i
COM1 RS232 9P RS232 9P D-Sub
D-Sub Female Female
9 RX TXD
6 TX RXD
5 GND GND
RTS
circuit
CTS
336
PLC Connection Guide
MT6050i/MT8050i
COM1 RS485 4W RS485 4W 9P D-Sub
9P D-Sub Female Female
1 RX- TX-
2 RX+ TX+
3 TX- RX-
4 TX+ RX+
5 GND GND
337
PLC Connection Guide
MT6050i/MT8050i
COM1 RS485 2W COM3 RS485 2W RS485 2W 9P D-Sub
9P D-Sub Female 9P D-Sub Female Female
1 RX- 7 Data- D-
2 RX+ 8 Data+ D+
5 GND 5 GND GND
Driver Version:
Version Date Description
V1.40 Apr/17/2009
338
PLC Connection Guide
HMI Setting:
Parameters Recommended Options Notes
PLC type MODBUS ASCII Server
PLC I/F RS232 RS232, RS485
Baud rate 9600 9600~115200
Data bits 8 7,8
Parity Even Even, Odd, None
Stop bits 1 1
PLC sta. no. 1 1-31 HMI Modbus Station No.
PLC Setting:
Communication mode Modbus ASCII protocol
Device Address:
Bit/Word Device type Format Range Memo
B LB dddd 0 ~ 9998 Mapping to 0x/1x 1 ~ 9999
W LW dddd 0 ~ 9998 Mapping to 3x/4x 1 ~ 9999
W RW ddddd 0 ~ 55536 Mapping to 3x/4x 10000 ~ 65536
339
PLC Connection Guide
Wiring Diagram:
The following represents the cable end connector.
RS232
eMT3000 series
COM1 RS232 9P COM3 RS232 9P RS232 9P D-Sub
D-Sub Female D-Sub Female Female
2 RX 8 RX TXD
3 TX 7 TX RXD
5 GND 5 GND GND
RTS
circuit
CTS
MT6050i/MT8050i
COM1 RS232 9P RS232 9P D-Sub
D-Sub Female Female
9 RX TXD
6 TX RXD
5 GND GND
RTS
circuit
CTS
340
PLC Connection Guide
The following represents the cable end connector.
RS485 4W
eMT3000 series
COM1 RS485 4W RS485 4W 9P D-Sub
9P D-Sub Male Male
1 RX- TX-
2 RX+ TX+
3 TX- RX-
4 TX+ RX+
5 GND GND
MT6050i/MT8050i
COM1 RS485 4W RS485 4W 9P D-Sub
9P D-Sub Female Female
1 RX- TX-
2 RX+ TX+
3 TX- RX-
4 TX+ RX+
5 GND GND
341
PLC Connection Guide
The following represents the cable end connector.
RS485 2W
eMT3000 series
COM1 RS485 2W COM3 RS485 2W RS485 2W 9P D-Sub
9P D-Sub Male 9P D-Sub Male Male
1 RX- 6 Data- D-
2 RX+ 9 Data+ D+
5 GND 5 GND GND
MT6050i/MT8050i
COM1 RS485 2W COM3 RS485 2W RS485 2W 9P D-Sub
9P D-Sub Female 9P D-Sub Female Male
1 RX- 7 Data- D-
2 RX+ 8 Data+ D+
5 GND 5 GND GND
Note: Setting more than one Modbus ASCII Server in HMI Device List is of no effect.
Driver Version:
Version Date Description
V1.00 Feb/19/2009 Driver released
342
PLC Connection Guide
MODBUS RTU
Supported Series : MODBUS RTU CONTROLLER
Website : http://www.modbus.org
HMI Setting:
Parameters Recommended Options Notes
PLC type MODBUS RTU
PLC I/F RS485 RS232/RS485
Baud rate 9600 9600~115200
Data bits 8 7, 8
Parity Even Even, Odd, None
Stop bits 1 1, 2
PLC sta. no. 1 0-255
PLC Setting:
Communication mode Modbus RTU protocol
Device Address:
Bit/Word Device type Format Range Memo
B 0x DDDDD 1 ~ 65535 Output bit
B 1x DDDDD 1 ~ 65535 Input bit (read only)
B 3x_Bit DDDDDdd 100 ~ 6553515 Input Register bit (read only)
B 4x_Bit DDDDDdd 100 ~ 6553515 Output Register bit
B 6x_Bit DDDDDdd 100 ~ 6553515 Output Register bit
B 0x_multi_coils DDDDD 1 ~ 65535 Write multiple coils
W 3x DDDDD 1 ~ 65535 Input Register (read only)
W 4x DDDDD 1 ~ 65535 Output Register
DW 5x DDDDD 1 ~ 65535 4x double word swap
W 6x DDDDD 1 ~ 65535 4x single word write
W 4x_32Bit* DDDDD 1 ~ 65535 Output Register
4x_32Bit will only read / write 2 words for each package, for continuous addresses, it will
be divided into several packages.
343
PLC Connection Guide
NOTE:
Address type “5x” is mapping to Hold Reg. The communication protocol of 5x is almost the
same as “4x” except that “5x” swaps double word.
If 4x contains the following information:
Address 1 2 3 4 5 6 ...
Data in word 0x1 0x2 0x3 0x4 0x5 0x6
Data 0x20001 0x40003 0x60005
344
PLC Connection Guide
Wiring Diagram:
The following represents the cable end connector.
MODBUS RTU CONTROLLER : RS232
eMT3000 series
COM1 RS232 9P COM3 RS232 9P RS232 9P D-Sub
D-Sub Female D-Sub Female FeMale
2 RX 8 RX TXD
3 TX 7 TX RXD
5 GND 5 GND GND
RTS
circuit
CTS
MT6050i/MT8050i
COM1 RS232 9P RS232 9P D-Sub
D-Sub Female FeMale
9 RX TXD
6 TX RXD
5 GND GND
RTS
circuit
CTS
345
PLC Connection Guide
MT6050i/MT8050i
COM1 RS485 4W RS485 4W 9P D-Sub
9P D-Sub Female Female
1 RX- TX-
2 RX+ TX+
3 TX- RX-
4 TX+ RX+
5 GND GND
346
PLC Connection Guide
The following represents the cable end connector.
MODBUS RTU CONTROLLER : RS485 2W
eMT3000 series
COM1 RS485 2W COM3 RS485 2W RS485 2W 9P D-Sub
9P D-Sub Male 9P D-Sub Male Male
1 RX- 6 Data- D-
2 RX+ 9 Data+ D+
5 GND 5 GND GND
MT6050i/MT8050i
COM1 RS485 2W COM3 RS485 2W RS485 2W 9P D-Sub
9P D-Sub Female 9P D-Sub Female Female
1 RX- 7 Data- D-
2 RX+ 8 Data+ D+
5 GND 5 GND GND
Driver Version:
Version Date Description
Fixed when receiving data over 8 bytes from MODBUS RTU,
V1.90 May/05/2010
LW-9570 fails to calculate correctly.
347
PLC Connection Guide
HMI Setting:
Parameters Recommended Options Notes
PLC type MODBUS RTU (0x/1x Range Adjustable)
PLC I/F RS485 RS232/RS485
Baud rate 9600 9600~115200
Data bits 8 7,8
Parity Even Even, Odd, None
Stop bits 1 1,2
PLC sta. no. 1 0-255
PLC Setting:
Communication mode Modbus RTU protocol
Device Address:
Bit/Word Device type Format Range Memo
B 0x DDDDD 1 ~ 65535 Output bit
B 1x DDDDD 1 ~ 65535 Input bit (read only)
B 3x_Bit DDDDDdd 100 ~ 6553515 Input Register bit (read only)
B 4x_Bit DDDDDdd 100 ~ 6553515 Output Register bit
B 6x_Bit DDDDDdd 100 ~ 6553515 Output Register bit
B 0x_multi_coils DDDDD 1 ~ 65535 Write multiple coils
W 3x DDDDD 1 ~ 65535 Input Register (read only)
W 4x DDDDD 1 ~ 65535 Output Register
DW 5x DDDDD 1 ~ 65535 4x double word swap
W 6x DDDDD 1 ~ 65535 4x single word write
W 4x_32Bit* DDDDD 1 ~ 65535 Output Register
4x_32Bit will only read / write 2 words for each package, for continuous addresses, it will
be divided into several packages.
348
PLC Connection Guide
NOTE:
Address type “5x” is mapping to Hold Reg. The communication protocol of “5x” is almost
the same as “4x” except that “5x” swaps double words.
If 4x contains the following information:
Address 1 2 3 4 5 6 ...
Data in 0x1 0x2 0x3 0x4 0x5 0x6
word
Data 0x20001 0x40003 0x60005
349
PLC Connection Guide
Setting Instructions:
2. After adding Modbus RTU (0x 1x Range Adjustable) driver, [Add Address Range Limit]
button will be enabled as below. Users can set maximum read/write command size
here.
Note: Setting [Add Address Range Limit] is enabled only when bit address is not a multiple
of 16bit.
350
PLC Connection Guide
3. Click [Add Address Range Limit] button, Users can define 0x and 1x address range in
[0x 1x Address Range] dialog box, referring to bit range of the device used.
351
PLC Connection Guide
Add:Set [Station No.], [Device Type], [Min. Address], [Max. Address] then click [OK] to
finish adding as below:
Example:
Take D2 and D8 of SCON as example, the settings depend on bit range of different PLC
types. Set [Station No.] and address first.
For D2, set [Station No.] to 20, [Device Type] 0x, [Max. Address] 36.
For D8, set [Station No.] to 2, [Device Type] 0x, [Max. Address] 51.
352
PLC Connection Guide
Note: If communicating with a RS-485 2W PLC, the [Turn around delay] setting may need
to be adjusted according to the reply speed of the device. Please click [Settings] in [Device
Properties], and set the [Turn around delay (ms)] parameter as shown:
353
PLC Connection Guide
Wiring Diagram:
The following represents the cable end connector.
MODBUS RTU CONTROLLER : RS232
eMT3000 series
COM1 RS232 9P COM3 RS232 9P RS232 9P D-Sub
D-Sub Female D-Sub Female Female
2 RX 8 RX TXD
3 TX 7 TX RXD
5 GND 5 GND GND
RTS
circuit
CTS
MT6050i/MT8050i
COM1 RS232 9P RS232 9P D-Sub
D-Sub Female Female
9 RX TXD
6 TX RXD
5 GND GND
RTS
circuit
CTS
354
PLC Connection Guide
The following represents the cable end connector.
MODBUS RTU CONTROLLER : RS485 4W
eMT3000 series
COM1 RS485 4W RS485 4W 9P D-Sub
9P D-Sub Male Male
1 RX- TX-
2 RX+ TX+
3 TX- RX-
4 TX+ RX+
5 GND GND
MT6050i/MT8050i
COM1 RS485 4W RS485 4W 9P D-Sub
9P D-Sub Female Female
1 RX- TX-
2 RX+ TX+
3 TX- RX-
4 TX+ RX+
5 GND GND
355
PLC Connection Guide
The following represents the cable end connector.
MODBUS RTU CONTROLLER : RS485 2W
eMT3000 series
COM1 RS485 2W COM3 RS485 2W RS485 2W 9P D-Sub
9P D-Sub Male 9P D-Sub Male Male
1 RX- 6 Data- D-
2 RX+ 9 Data+ D+
5 GND 5 GND GND
MT6050i/MT8050i
COM1 RS485 2W COM3 RS485 2W RS485 2W 9P D-Sub
9P D-Sub Female 9P D-Sub Female Female
1 RX- 7 Data- D-
2 RX+ 8 Data+ D+
5 GND 5 GND GND
Driver Version:
Version Date Description
V1.10 Aug/25/2010
V1.20 Mar/2/2012 Allow modifying the Minimum address of 0x、1x Address Range.
356
PLC Connection Guide
HMI Setting:
Parameters Recommended Options Notes
PLC type MODBUS RTU (Adjustable)
PLC I/F RS485 RS232/RS485
9600/19200/3840
Baud rate 9600
0/57600/115200
Data bits 8 7,8
Parity Even Even, Odd, None
Stop bits 1 1,2
PLC sta. no. 1 0-255
PLC Setting:
Communication mode Modbus RTU protocol
Device Address:
Bit/Word Device type Format Range Memo
B 0x DDDDD 1 ~ 65535 Output bit
B 1x DDDDD 1 ~ 65535 Input bit (read only)
B 3x_Bit DDDDDdd 100 ~ 6553515 Input Register bit (read only)
B 4x_Bit DDDDDdd 100 ~ 6553515 Output Register bit
B 0x_multi_coils DDDDD 1 ~ 65535 Write multiple coils
W 3x DDDDD 1 ~ 65535 Input Register (read only)
W 4x DDDDD 1 ~ 65535 Output Register
W 5x DDDDD 1 ~ 65535 4x double word swap
DW 5x (32-bit) DDDDD 1 ~ 65535 4x double word
W 6x DDDDD 1 ~ 65535 4x single word write
357
PLC Connection Guide
NOTE:
Address type “5x” is mapping to Hold Reg. The communication protocol of “5x” is almost
the same as “4x” except that “5x” swaps double words.
If 4x contains the following information:
Address 1 2 3 4 5 6 ...
Data in 0x1 0x2 0x3 0x4 0x5 0x6
word
Data 0x20001 0x40003 0x60005
358
PLC Connection Guide
Setting Instructions:
2. After adding MODBUS RTU (Adjustable) driver, [Add Address Range Limit] button will
be enabled as below. Users can set maximum read/write command size here.
359
PLC Connection Guide
Note:
MODBUS RTU (adjustable) usage
Users can decide the address range via setting value on Parameter 1. For example, when
users set 5 to Parameter 1, the address range will be 5 ~ 65535.
360
PLC Connection Guide
Wiring Diagram:
The following represents the cable end connector.
MODBUS RTU CONTROLLER : RS232
eMT3000 series
COM1 RS232 9P COM3 RS232 9P RS232 9P D-Sub
D-Sub Female D-Sub Female Female
2 RX 8 RX TXD
3 TX 7 TX RXD
5 GND 5 GND GND
RTS
circuit
CTS
MT6050i/MT8050i
COM1 RS232 9P RS232 9P D-Sub
D-Sub Female Female
9 RX TXD
6 TX RXD
5 GND GND
RTS
circuit
CTS
361
PLC Connection Guide
The following represents the cable end connector.
MODBUS RTU CONTROLLER : RS485 4W
eMT3000 series
COM1 RS485 4W RS485 4W 9P D-Sub
9P D-Sub Male Male
1 RX- TX-
2 RX+ TX+
3 TX- RX-
4 TX+ RX+
5 GND GND
MT6050i/MT8050i
COM1 RS485 4W RS485 4W 9P D-Sub
9P D-Sub Female Female
1 RX- TX-
2 RX+ TX+
3 TX- RX-
4 TX+ RX+
5 GND GND
362
PLC Connection Guide
The following represents the cable end connector.
MODBUS RTU CONTROLLER : RS485 2W
eMT3000 series
COM1 RS485 2W COM3 RS485 2W RS485 2W 9P D-Sub
9P D-Sub Male 9P D-Sub Male Male
1 RX- 6 Data- D-
2 RX+ 9 Data+ D+
5 GND 5 GND GND
MT6050i/MT8050i
COM1 RS485 2W COM3 RS485 2W RS485 2W 9P D-Sub
9P D-Sub Female 9P D-Sub Female Female
1 RX- 7 Data- D-
2 RX+ 8 Data+ D+
5 GND 5 GND GND
Driver Version:
Version Date Description
V1.40 Jun/14/2011
363
PLC Connection Guide
Website : http://www.modbus.org
HMI Setting:
Parameters Recommended Options Notes
PLC type MODBUS RTU (zero-based addressing)
PLC I/F RS485 RS232/RS485
Baud rate 9600 9600~115200
Data bits 8 7,8
Parity Even Even, Odd, None
Stop bits 1 1,2
PLC sta. no. 1 0-255
PLC Setting:
Communication mode Modbus RTU protocol
Device Address:
Bit/Word Device type Format Range Memo
B 0x DDDDD 0 ~ 65535 Output bit
B 1x DDDDD 0 ~ 65535 Input bit (read only)
B 3x_Bit DDDDDdd 0 ~ 6553515 Input Register bit (read only)
B 4x_Bit DDDDDdd 0 ~ 6553515 Output Register bit
B 0x_multi_coils DDDDD 0 ~ 65535 Write multiple coils
W 3x DDDDD 0 ~ 65535 Input Register (read only)
W 4x DDDDD 0 ~ 65535 Output Register
DW 5x DDDDD 0 ~ 65535 4x double word swap
W 6x DDDDD 0 ~ 65535 4x single word write
364
PLC Connection Guide
NOTE:
Address type “5x” is mapping to Hold Reg. The communication protocol of 5x is almost the
same as “4x” except that “5x” swaps double words.
If 4x contains the following information:
Address 1 2 3 4 5 6 ...
Data in word 0x1 0x2 0x3 0x4 0x5 0x6
Data 0x20001 0x40003 0x60005
365
PLC Connection Guide
Wiring Diagram:
The following represents the cable end connector.
MODBUS RTU CONTROLLER : RS232
eMT3000 series
COM1 RS232 9P COM3 RS232 9P RS232 9P D-Sub
D-Sub Female D-Sub Female Female
2 RX 8 RX TXD
3 TX 7 TX RXD
5 GND 5 GND GND
RTS
circuit
CTS
MT6050i/MT8050i
COM1 RS232 9P RS232 9P D-Sub
D-Sub Female Female
9 RX TXD
6 TX RXD
5 GND GND
RTS
circuit
CTS
366
PLC Connection Guide
The following represents the cable end connector.
MODBUS RTU CONTROLLER : RS485 4W
eMT3000 series
COM1 RS485 4W RS485 4W 9P D-Sub
9P D-Sub Male Male
1 RX- TX-
2 RX+ TX+
3 TX- RX-
4 TX+ RX+
5 GND GND
MT6050i/MT8050i
COM1 RS485 4W RS485 4W 9P D-Sub
9P D-Sub Female Female
1 RX- TX-
2 RX+ TX+
3 TX- RX-
4 TX+ RX+
5 GND GND
367
PLC Connection Guide
The following represents the cable end connector.
MODBUS RTU CONTROLLER : RS485 2W
eMT3000 series
COM1 RS485 2W COM3 RS485 2W RS485 2W 9P D-Sub
9P D-Sub Male 9P D-Sub Male Male
1 RX- 6 Data- D-
2 RX+ 9 Data+ D+
5 GND 5 GND GND
MT6050i/MT8050i
COM1 RS485 2W COM3 RS485 2W RS485 2W 9P D-Sub
9P D-Sub Female 9P D-Sub Female Female
1 RX- 7 Data- D-
2 RX+ 8 Data+ D+
5 GND 5 GND GND
Driver Version:
Version Date Description
V1.30 Aug/26/2009
368
PLC Connection Guide
HMI Setting:
Parameters Recommended Options Notes
PLC type MODBUS Server (COM/Ethernet)
PLC I/F RS232 RS232, RS485
9600~115200 Ethernet supports UDP or TCP/IP
Baud rate 9600
Ethernet protocol
Data bits 8 8
Parity Even Even, Odd,
Stop bits 1 None
1
PLC sta. no. 1 1-31 HMI Modbus Station No.
Port no. 502
PLC Setting:
Communication mode Modbus RTU protocol
369
PLC Connection Guide
Modbus Server Port No. can not be set identically to HMI Port No. When doing so, the
warning message below will be shown requesting users to change setting.
Note:
A maximum of 64 Clients can be connected simultaneously.
Modbus Server Port No. can’t be identical to HMI Port No.
370
PLC Connection Guide
For Modbus Server TCP/IP, HMI Port No. is the same as Modbus Server Port No. To
change Prot No. go to [System Parameter Settings] / [Model], the default Port No. is
“8000”, and it is allowed to change Modbus Server Port No. here.
371
PLC Connection Guide
Device Address:
Bit/Word Device type Format Range Memo
B LB dddd 0 ~ 9998 Mapping to 0x/1x 1 ~ 9999
W LW dddd 0 ~ 9998 Mapping to 3x/4x 1 ~ 9999
W RW ddddd 0 ~ 55536 Mapping to 3x/4x 10000 ~ 65536
Wiring Diagram:
The following represents the cable end connector.
MODBUS SERVER : RS232
eMT3000 series
COM1 RS232 9P COM3 RS232 9P RS232 9P D-Sub
D-Sub Female D-Sub Female Female
2 RX 8 RX TXD
3 TX 7 TX RXD
5 GND 5 GND GND
RTS
circuit
CTS
372
PLC Connection Guide
MT6000/8000 series except MT6050i/MT8050i
COM1 RS232 9P COM2 RS232 9P COM3 RS232 9P RS232 9P D-Sub
D-Sub Female D-Sub Female D-Sub Male Female
2 RX 6 RX 8 RX TXD
3 TX 4 TX 7 TX RXD
5 GND 5 GND 5 GND GND
RTS
circuit
CTS
MT6050i/MT8050i
COM1 RS232 9P RS232 9P D-Sub
D-Sub Female Female
9 RX TXD
6 TX RXD
5 GND GND
RTS
circuit
CTS
373
PLC Connection Guide
MT6000/8000 series except MT6050i/MT8050i
COM1 RS485 4W RS485 4W 9P D-Sub
9P D-Sub Male Male
1 RX- TX-
2 RX+ TX+
3 TX- RX-
4 TX+ RX+
5 GND GND
MT6050i/MT8050i
COM1 RS485 4W RS485 4W 9P D-Sub
9P D-Sub Female Female
1 RX- TX-
2 RX+ TX+
3 TX- RX-
4 TX+ RX+
5 GND GND
374
PLC Connection Guide
MT6000/8000 series except MT6050i/MT8050i
COM1 RS485 2W COM3 RS485 2W RS485 2W 9P D-Sub
9P D-Sub Male 9P D-Sub Male Male
1 RX- 6 Data- D-
2 RX+ 9 Data+ D+
5 GND 5 GND GND
MT6050i/MT8050i
COM1 RS485 2W COM3 RS485 2W RS485 2W 9P D-Sub
9P D-Sub Female 9P D-Sub Female Male
1 RX- 7 Data- D-
2 RX+ 8 Data+ D+
5 GND 5 GND GND
375
PLC Connection Guide
Through a hub:
HMI RJ45 Male Wire Color PLC RJ45 Male
1 TX+ White/Orange 1 TX+
2 TX- Orange 2 TX-
3 RX+ White/Green 3 RX+
4 BD4+ Blue 4 BD4+
5 BD4- White/Blue 5 BD4-
6 RX- Green 6 RX-
7 BD3+ White/Brown 7 BD3+
8 BD3- Brown 8 BD3-
Note: Setting more than one Modbus Server in HMI Device List is of no effect.
Driver Version:
Version Date Description
V1.00 Dec/30/2008 Driver released
376
PLC Connection Guide
MODBUS TCP/IP
Supported Series: Modbus RTU TCP/IP device.
Website: http://www.modbus.org
HMI Setting:
Parameters Recommended Options Notes
PLC type MODBUS TCP/IP
PLC I/F Ethernet
Port no. 502
PLC sta. no. 1 0~255
Device Address:
Bit/Word Device type Format Range Memo
B 0x DDDDD 1 ~ 65535 Input bit
B 1x DDDDD 1 ~ 65535 Output bit
B 3x_bit DDDDDdd 100 ~ 6553515 Input Register bit(read only)
B 4x_bit DDDDDdd 100 ~ 6553515 Output Register bit
B 6x_bit DDDDDdd 100 ~ 6553515 Output Register bit
B 0x_multi_coils DDDDD 1 ~ 65535 Write multiple coils
W 3x DDDDD 1 ~ 65535 Input Register
W 4x DDDDD 1 ~ 65535 Output Register
DW 5x DDDDD 1 ~ 65535 4x double word swap
W 6x DDDDD 1 ~ 65535 4x single word write
4x string
W central DDDDD 1 ~ 65535
europe rev
377
PLC Connection Guide
Wiring Diagram:
Direct connect (crossover cable):
HMI RJ45 Male Wire Color PLC RJ45 Male
1 TX+ White/Orange 3 RX+
2 TX- Orange 6 RX-
3 RX+ White/Green 1 TX+
4 BD4+ Blue 4 BD4+
5 BD4- White/Blue 5 BD4-
6 RX- Green 2 TX-
7 BD3+ White/Brown 7 BD3+
8 BD3- Brown 8 BD3-
Through a hub:
HMI RJ45 Male Wire Color PLC RJ45 Male
1 TX+ White/Orange 1 TX+
2 TX- Orange 2 TX-
3 RX+ White/Green 3 RX+
4 BD4+ Blue 4 BD4+
5 BD4- White/Blue 5 BD4-
6 RX- Green 6 RX-
7 BD3+ White/Brown 7 BD3+
8 BD3- Brown 8 BD3-
Driver Version:
Version Date Description
V1.50 Aug/26/2009
378
PLC Connection Guide
HMI Setting:
Parameters Recommended Options Notes
PLC type MODBUS TCP/IP (0x/1x Range Adjustable)
PLC I/F Ethernet
Port no. 502
PLC sta. no. 1 0~255
Device Address:
Bit/Word Device type Format Range Memo
B 0x DDDDD 1 ~ 65535 Output bit
B 1x DDDDD 1 ~ 65535 Input bit (read only)
B 3x_Bit DDDDDdd 100 ~ 6553515 Input Register bit (read only)
B 4x_Bit DDDDDdd 100 ~ 6553515 Output Register bit
B 6x_Bit DDDDDdd 100 ~ 6553515 Output Register bit
B 0x_multi_coils DDDDD 1 ~ 65535 Write multiple coils
W 3x DDDDD 1 ~ 65535 Input Register (read only)
W 4x DDDDD 1 ~ 65535 Output Register
DW 5x DDDDD 1 ~ 65535 4x double word swap
W 6x DDDDD 1 ~ 65535 4x single word write
4x string
W central DDDDD 1 ~ 65535
europe rev
379
PLC Connection Guide
NOTE:
Address type “5x” is mapping to Hold Reg. The communication protocol of “5x” is almost
the same as “4x” except that “5x” swaps double words.
If 4x contains the following information:
Address 1 2 3 4 5 6 ...
Data in 0x1 0x2 0x3 0x4 0x5 0x6
word
Data 0x20001 0x40003 0x60005
380
PLC Connection Guide
Setting Instructions:
2. Click [Add Address Range Limit] button, Users can define 0x and 1x address range in
[0x 1x Address Range] dialog box, referring to bit range of the device used.
381
PLC Connection Guide
Add:Set [Station No.], [Device Type], [Max. Address] then click [OK] to finish adding as
below:
382
PLC Connection Guide
Example:
Take 0x and 1x as example, the settings depend on bit range of different PLC types.
For 0x, [Device Type] 0x, [Min. Address]5,[Max. Address] 20.
For 1x, [Device Type] 0x, [Min. Address]1,[Max. Address] 10.
383
PLC Connection Guide
Wiring Diagram:
Direct connect (crossover cable):
HMI RJ45 Male Wire Color PLC RJ45 Male
1 TX+ White/Orange 3 RX+
2 TX- Orange 6 RX-
3 RX+ White/Green 1 TX+
4 BD4+ Blue 4 BD4+
5 BD4- White/Blue 5 BD4-
6 RX- Green 2 TX-
7 BD3+ White/Brown 7 BD3+
8 BD3- Brown 8 BD3-
Through a hub:
HMI RJ45 Male Wire Color PLC RJ45 Male
1 TX+ White/Orange 1 TX+
2 TX- Orange 2 TX-
3 RX+ White/Green 3 RX+
4 BD4+ Blue 4 BD4+
5 BD4- White/Blue 5 BD4-
6 RX- Green 6 RX-
7 BD3+ White/Brown 7 BD3+
8 BD3- Brown 8 BD3-
Driver Version:
Version Date Description
V1.00 NOV/2/2011 Driver released.
V1.10 MAR/14/2012 Allow modifying the Minimum address of 0x、1x Address Range.
384
PLC Connection Guide
Website: http://www.modbus.org
HMI Setting:
Parameters Recommended Options Notes
PLC type MODBUS TCP/IP (zero-based addressing)
PLC I/F Ethernet
Port no. 502
PLC sta. no. 1 0~255
Device Address:
Bit/Word Device type Format Range Memo
B 0x DDDDD 0 ~ 65535 Input bit
B 1x DDDDD 0 ~ 65535 Output bit
B 3x_Bit DDDDDdd 0 ~ 6553515 Input Register bit (read only)
B 4x_Bit DDDDDdd 0 ~ 6553515 Output Register bit
B 6x_Bit DDDDDdd 0 ~ 6553515 Output Register bit
B 0x_multi_coils DDDDD 0 ~ 65535 Write multiple coils
W 3x DDDDD 0 ~ 65535 Input Register
W 4x DDDDD 0 ~ 65535 Output Register
DW 5x DDDDD 0 ~ 65535 4x double word swap
W 6x DDDDD 0 ~ 65535 4x single word write
385
PLC Connection Guide
Wiring Diagram:
Direct connect (crossover cable):
HMI RJ45 Male Wire Color PLC RJ45 Male
1 TX+ White/Orange 3 RX+
2 TX- Orange 6 RX-
3 RX+ White/Green 1 TX+
4 BD4+ Blue 4 BD4+
5 BD4- White/Blue 5 BD4-
6 RX- Green 2 TX-
7 BD3+ White/Brown 7 BD3+
8 BD3- Brown 8 BD3-
Through a hub:
HMI RJ45 Male Wire Color PLC RJ45 Male
1 TX+ White/Orange 1 TX+
2 TX- Orange 2 TX-
3 RX+ White/Green 3 RX+
4 BD4+ Blue 4 BD4+
5 BD4- White/Blue 5 BD4-
6 RX- Green 6 RX-
7 BD3+ White/Brown 7 BD3+
8 BD3- Brown 8 BD3-
Driver Version:
Version Date Description
V1.40 Aug/27/2009
386
PLC Connection Guide
Website: http://www.modbus.org
HMI Setting:
Parameters Recommended Options Notes
PLC type MODBUS TCP/IP 32Bit
PLC I/F Ethernet
Port no. 502
PLC sta. no. 1 0~255
Device Address:
Bit/Word Device type Format Range Memo
B 0x DDDDD 1 ~ 65535 Input bit
B 1x DDDDD 1 ~ 65535 Output bit
B 3x_Bit DDDDDdd 100 ~ 6553515 Input Register bit (read only)
B 4x_Bit DDDDDdd 100 ~ 6553515 Output Register bit
B 6x_Bit DDDDDdd 100 ~ 6553515 Output Register bit
B 0x_multi_coils DDDDD 1 ~ 65535 Write multiple coils
W 3x DDDDD 1 ~ 65535 Input Register
W 4x DDDDD 1 ~ 65535 Output Register
DW 5x DDDDD 1 ~ 65535 4x double word swap
W 6x DDDDD 1 ~ 65535 4x single word write
W 4x_32Bit* DDDDD 1 ~ 65535
4x_32Bit will only read / write 2 words for each package, for continuous addresses, it will
be divided into several packages.
387
PLC Connection Guide
Wiring Diagram:
Direct connect (crossover cable):
HMI RJ45 Male Wire Color PLC RJ45 Male
1 TX+ White/Orange 3 RX+
2 TX- Orange 6 RX-
3 RX+ White/Green 1 TX+
4 BD4+ Blue 4 BD4+
5 BD4- White/Blue 5 BD4-
6 RX- Green 2 TX-
7 BD3+ White/Brown 7 BD3+
8 BD3- Brown 8 BD3-
Through a hub:
HMI RJ45 Male Wire Color PLC RJ45 Male
1 TX+ White/Orange 1 TX+
2 TX- Orange 2 TX-
3 RX+ White/Green 3 RX+
4 BD4+ Blue 4 BD4+
5 BD4- White/Blue 5 BD4-
6 RX- Green 6 RX-
7 BD3+ White/Brown 7 BD3+
8 BD3- Brown 8 BD3-
Driver Version:
Version Date Description
V1.10 Aug/27/2009 Driver released.
388
PLC Connection Guide
Moeller XC-CPU101
Supported Series: MOELLER XC100/200 series
Website: http://www.moeller.net
HMI Setting:
Parameters Recommended Options Notes
PLC type Moeller XC-CPU101
PLC I/F RS232
Baud rate 38400 4800 ~ 57600
Data bits 8
Parity None
Stop bits 1
PLC sta. no. 1
Device Address:
Bit/Word Device type Format Range Note
B QX DDo 0 ~ 157
B IX DDo 0 ~ 157
W MW DDDD 0 ~ 4095
W QW DD 0 ~ 15
W IW DD 0 ~ 15
Wiring Diagram:
The following represents the cable end connector.
eMT3000 series
COM1 RS232 9P COM3 RS232 9P RS232 8P RJ45 Male
D-Sub Female D-Sub Female
2 RX 8 RX 5 TD
3 TX 7 TX 8 RD
5 GND 5 GND 4 GND
389
PLC Connection Guide
MT6000/8000 series except MT6050i/MT8050i
COM1 RS232 9P COM2 RS232 9P COM3 RS232 9P RS232 8P RJ45 Male
D-Sub Female D-Sub Female D-Sub Male
2 RX 6 RX 8 RX 5 TD
3 TX 4 TX 7 TX 8 RD
5 GND 5 GND 5 GND 4 GND
MT6050i/MT8050i
COM1 RS232 9P RS232 8P RJ45 Male
D-Sub Female
9 RX 5 TD
6 TX 8 RD
5 GND 4 GND
Driver Version:
Version Date Description
1.00 Apr/01/2010 Driver released.
390
PLC Connection Guide
OHJX
Website: http://www.ohjx.com/
HMI Setting:
Parameters Recommended Options Notes
PLC type OHJX
PLC I/F RS-232
Baud rate 9600 9600,19200
Data bits 8
Parity Odd
Stop bits 1
PLC sta. no. 1
Device Address:
Bit/Word Device type Format Range Memo
B R100 Dh 0 ~ 1f
B R101 Dh 0 ~ 1f
B R102 Dh 0 ~ 1f
B R103 Dh 0 ~ 1f
B R104 Dh 0 ~ 1f
B R105 Dh 0 ~ 1f
B R106 Dh 0 ~ 1f
B R107 Dh 0 ~ 1f
B R108 Dh 0 ~ 1f
B R109 Dh 0 ~ 1f
B R110 Dh 0 ~ 1f
B R210 Dh 0 ~ 1f
B R310 Dh 0 ~ 1f
W SV DDDD 0 ~ 9999
W EV DDDDD 0 ~ 65535
W DT DDDDD 0 ~ 9999
W LD DDDD 0 ~ 8447
W WX DDDD 0 ~ 9999
391
PLC Connection Guide
Bit/Word Device type Format Range Memo
W WY DDDD 0 ~ 9999
W WR DDDD 0 ~ 9999
W WL DDDD 0 ~ 9999
W FL DDDDD 0 ~ 99999
Wiring Diagram:
The following represents the cable end connector.
eMT3000 series
COM1 RS232 9P COM3 RS232 9P 4P Mini-DIN Male
D-Sub Female D-Sub Female
2 RX 8 RX 3 TX
3 TX 7 TX 2 RX
5 GND 5 GND 1 GND
circuit
4 GND
392
PLC Connection Guide
MT6050i/MT8050i
COM1 RS232 9P 4P Mini-DIN Male
D-Sub Female
9 RX 3 TX
6 TX 2 RX
5 GND 1 GND
circuit
4 GND
Driver Version:
Version Date Description
V1.00 Nov/22/2011 Driver released.
393
PLC Connection Guide
HMI Setting:
Parameters Recommended Options Notes
PLC type OMRON C/CQM1 Series
PLC I/F RS232 RS232, RS422, RS485
Baud rate 9600 9600, 19200
Data bits 7 7 or 8
Parity Even Even, Odd, None
Stop bits 2 1 or 2
PLC sta. no. 0 0-31 Host Link Station No.
PLC Setting:
Communication mode Host Link Protocol
Device Address:
Bit/Word Device type Format Range Memo
B IR DDDDdd 0 ~ 409515 I/O and Internal Relay
B HR DDDDdd 0 ~ 409515 Hold Relay
B LR DDDDdd 0 ~ 409515 Link Relay
B IR (Force Set/Reset) DDDDdd 0 ~ 409515
B HR (Force Set/Reset) DDDDdd 0 ~ 409515
B LR (Force Set/Reset) DDDDdd 0 ~ 409515
B AR DDDDdd 0 ~ 409515 Auxiliary Relay
W AR_W DDDD 0 ~ 4095
W IR_W DDDD 0 ~ 4095
W HR_W DDDD 0 ~ 4095
W LR_W DDDD 0 ~ 4095
W TC DDD 0 ~ 255
W DM DDDD 0 ~ 9999 Data Register
394
PLC Connection Guide
Wiring Diagram:
The following represents the cable end connector.
CPU Port (CPM2A,CQM1/1H,C200H/HS/ALPHA series)
Communication Module:
CPM1-CIF01 adapter (for CPM1/CPM1A/CPM2A series, CQM1/CQM1H series)
CPM1H-SCB41 communication module (for CQM1H-CPU51/61)
eMT3000 series
COM1 RS232 9P COM3 RS232 9P RS232 9P D-Sub Male
D-Sub Female D-Sub Female
2 RX 8 RX 2 SD
3 TX 7 TX 3 RD
5 GND 5 GND 9 GND
4 RS
circuit
5 CS
395
PLC Connection Guide
MT6050i/MT8050i
COM1 RS232 9P RS232 9P D-Sub Male
D-Sub Female
9 RX 2 SD
6 TX 3 RD
5 GND 9 GND
4 RS
circuit
5 CS
396
PLC Connection Guide
MT6050i/MT8050i
COM1 RS232 9P RS232 9P D-Sub Male
D-Sub Female
9 RX 2 SD
6 TX 3 RD
5 GND 7 GND
4 RS
circuit
5 CS
Driver Version:
Version Date Description
V1.80 Apr/14/2010
397
PLC Connection Guide
OMRON CJ/CS/CP
Supported Series: OMRON CP1L, CP1H, CJ1M, CJ2M, CJ1H, CJM1G, CS1H and CS1G.
(Host Link Protocol FINS command), this driver supports Extend Addressing Mode.
Website: http://oeiweb.omron.com/oei/Products-PLC.htm
HMI Setting:
Parameters Recommended Options Notes
PLC type OMRON CJ/CS/CP
PLC I/F RS232 RS232, RS422, RS485
Baud rate 9600 9600~115200
Data bits 7 7 or 8
Parity Even Even, Odd, None
Stop bits 2 1 or 2
PLC sta. no. 0 0-31 Host Link Station No.
PLC Setting:
Communication mode Host Link Protocol
Device Address:
Bit/Word Device type Format Range Memo
B CIO_Bit DDDDDdd 0 ~ 3276715 Channel I/O (CIO)
B W_Bit DDDDDdd 0 ~ 3276715 Work Area (WR)
B H_Bit DDDDDdd 0 ~ 3276715 Holding Area (HR)
B D_Bit DDDDDdd 0 ~ 3276715 Data Memory (DM)
B A_Bit DDDDDdd 0 ~ 3276715 Auxiliary Relay (AR)
B T_Bit DDDDDdd 0 ~ 3276715 Timer (TIM)
B C_Bit DDDDDdd 0 ~ 3276715 Counter (CNT)
B C_flag DDDD 0 ~ 4095
B T_flag DDDD 0 ~ 4095
B LR_Bit DDDdd 0 ~ 19915
398
PLC Connection Guide
Bit/Word Device type Format Range Memo
W T DDDDD 0 ~ 32767 Timer (TIM)
W H DDDDD 0 ~ 32767 Holding Area (HR)
W D DDDDD 0 ~ 32767 Data Memory (DM)
W A DDDDD 0 ~ 32767 Auxiliary Relay (AR)
W W DDDDD 0 ~ 32767 Work Area (WR)
W C DDDDD 0 ~ 32767 Counter (CNT)
W CIO DDDDD 0 ~ 32767 Channel I/O (CIO)
W EM0 ~ EMC DDDDD 0 ~ 32767 Extend Memory
W LR DDD 0 ~ 199
Wiring Diagram:
The following represents the cable end connector.
9P D-Sub to 9P D-Sub:
eMT3000 series
COM1 RS232 9P COM3 RS232 9P RS232 9P D-Sub Male
D-Sub Female D-Sub Female
2 RX 8 RX 2 SD
3 TX 7 TX 3 RD
5 GND 5 GND 9 GND
4 RS
circuit
5 CS
399
PLC Connection Guide
MT6050i/MT8050i
COM1 RS232 9P RS232 9P D-Sub Male
D-Sub Female
9 RX 2 SD
6 TX 3 RD
5 GND 9 GND
4 RS
circuit
5 CS
400
PLC Connection Guide
MT6050i/MT8050i
COM1 RS485 4W CP1W-CIF11 RS485
9P D-Sub Female 4W Terminal
1 RX- SDA
2 RX+ SDB
3 TX- RDA
4 TX+ RDB
5 GND FG
Driver Version:
Version Date Description
V1.90 Feb/01/2011 Added registers: LR, LR_Bit
401
PLC Connection Guide
HMI Setting:
Parameters Recommended Options Notes
PLC type OMRON CJ1/CS1 (Ethernet)
PLC I/F Ethernet
Port no. 9600
PLC sta. no. 0
PLC Setting:
Communication mode FINS Ethernet protocol
Device Address:
Bit/Word Device type Format Range Memo
B CIO_Bit DDDDDdd 0 ~ 3276715 Channel I/O (CIO)
B W_Bit DDDDDdd 0 ~ 3276715 Work Area (WR)
B H_Bit DDDDDdd 0 ~ 3276715 Holding Area (HR)
B A_Bit DDDDDdd 0 ~ 3276715 Auxiliary Relay (AR) (Read only)
B D_Bit DDDDDdd 0 ~ 3276715 Data Memory (DM)
B T_Bit DDDDDdd 0 ~ 3276715 Timer (TIM)
B C_Bit DDDDDdd 0 ~ 3276715 Counter (CNT)
B C_Flag DDDD 0 ~ 4095
B T_Flag DDDD 0 ~ 4095
W CIO DDDDD 0 ~ 32767 Channel I/O (CIO)
W W DDDDD 0 ~ 32767 Work Area (WR)
W H DDDDD 0 ~ 32767 Holding Area (HR)
W A DDDDD 0 ~ 32767 Auxiliary Relay (AR) (Read only)
W C DDDDD 0 ~ 32767 Counter (CNT)
W T DDDDD 0 ~ 32767 Timer (TIM)
W D DDDDD 0 ~ 32767 Data Memory (DM)
W EM0 ~ EMC DDDDD 0 ~ 32767 Extend Memory
402
PLC Connection Guide
Wiring Diagram:
Direct connect (crossover cable):
HMI RJ45 Male Wire Color PLC RJ45 Male
1 TX+ White/Orange 3 RX+
2 TX- Orange 6 RX-
3 RX+ White/Green 1 TX+
4 BD4+ Blue 4 BD4+
5 BD4- White/Blue 5 BD4-
6 RX- Green 2 TX-
7 BD3+ White/Brown 7 BD3+
8 BD3- Brown 8 BD3-
Through a hub:
HMI RJ45 Male Wire Color PLC RJ45 Male
1 TX+ White/Orange 1 TX+
2 TX- Orange 2 TX-
3 RX+ White/Green 3 RX+
4 BD4+ Blue 4 BD4+
5 BD4- White/Blue 5 BD4-
6 RX- Green 6 RX-
7 BD3+ White/Brown 7 BD3+
8 BD3- Brown 8 BD3-
Driver Version:
Version Date Description
V1.50 Jun/30/2010
403
PLC Connection Guide
OMRON E5CN/E5EZ/E5ZN
Supported Series: OMRON E5CN series temperature controller with communication
options. E5EN/CN/GN/EZ/ZN series.
Website: http://oeiweb.omron.com
HMI Setting:
Parameters Recommended Options Notes
PLC type OMRON E5CN
PLC I/F RS485 2W
9600/19200/38400/
Baud rate 9600
57600/115200
Data bits 7 7,8
Parity Even Even, Odd, None
Stop bits 2 1,2
PLC sta. no. 0 0-99
Device Address:
Bit/Word Device type Format Range Memo
B Status_CH1 DD 0 ~ 31 Page40
B Status_CH2 DD 0 ~ 31
DW C0 HHHH 0 ~ 270f Read only (Hex) Page34
DW C1 HHHH 0 ~ 270f Read/Write (Hex) Page35
DW C2 HHHH 0 ~ 270f Read/Write (Hex) Page35
DW C3 HHHH 0 ~ 270f Read/Write (Hex) Page36
W Code00_00 H 0 Communications writing OFF (disabled)
W Code00_01 H 0 Communications writing ON(enabled)
W Code01_00 H 0 Run
W Code01_01 H 0 Stop
W Code02_00 H 0 Multi-SP Set point 0
W Code02_01 H 0 Multi-SP Set point 1
W Code02_02 H 0 Multi-SP Set point 2
404
PLC Connection Guide
405
PLC Connection Guide
Wiring Diagram:
The following represents the cable end connector.
eMT3000 series
COM1 RS485 2W COM3 RS485 2W OMRON E5CN
9P D-Sub Male 9P D-Sub Male Terminal
1 RX- 6 Data- 12 B
2 RX+ 9 Data+ 11 A
5 GND 5 GND GND
MT6050i/MT8050i
COM1 RS485 2W COM3 RS485 2W OMRON E5CN
9P D-Sub Female 9P D-Sub Female Terminal
1 RX- 7 Data- 12 B
2 RX+ 8 Data+ 11 A
5 GND 5 GND GND
Note:
For communication with OMRON E5EZ, please set communication settings to 9600, E, 7,
2, station no. 1.
406
PLC Connection Guide
Driver Version:
Version Date Description
V1.21 Dec/21/2010
407
PLC Connection Guide
HMI Setting:
Parameters Recommended Options Notes
PLC type OMRON FINS (Ethernet)
PLC I/F Ethernet
Port no. 9600
PLC sta. no. 0
PLC Setting:
Communication mode FINS Ethernet protocol
Device Address:
Bit/Word Device type Format Range Memo
B CIO_Bit DDDDDdd 0 ~ 3276715 Channel I/O (CIO)
B W_Bit DDDDDdd 0 ~ 3276715 Work Area (WR)
B H_Bit DDDDDdd 0 ~ 3276715 Holding Area (HR)
B A_Bit DDDDDdd 0 ~ 3276715 Auxiliary Relay (AR) (Read only)
B D_Bit DDDDDdd 0 ~ 3276715 Data Memory (DM)
B T_Bit DDDDDdd 0 ~ 3276715 Timer (TIM)
B C_Bit DDDDDdd 0 ~ 3276715 Counter (CNT)
B C_Flag DDDD 0 ~ 4095
B T_Flag DDDD 0 ~ 4095
W CIO DDDDD 0 ~ 32767 Channel I/O (CIO)
W W DDDDD 0 ~ 32767 Work Area (WR)
W H DDDDD 0 ~ 32767 Holding Area (HR)
W A DDDDD 0 ~ 32767 Auxiliary Relay (AR) (Read only)
W C DDDDD 0 ~ 32767 Counter (CNT)
W T DDDDD 0 ~ 32767 Timer (TIM)
W D DDDDD 0 ~ 32767 Data Memory (DM)
W EM0 ~ EMC DDDDD 0 ~ 32767 Extend Memory
408
PLC Connection Guide
Wiring Diagram:
Direct connect (crossover cable):
HMI RJ45 Male Wire Color PLC RJ45 Male
1 TX+ White/Orange 3 RX+
2 TX- Orange 6 RX-
3 RX+ White/Green 1 TX+
4 BD4+ Blue 4 BD4+
5 BD4- White/Blue 5 BD4-
6 RX- Green 2 TX-
7 BD3+ White/Brown 7 BD3+
8 BD3- Brown 8 BD3-
Through a hub:
HMI RJ45 Male Wire Color PLC RJ45 Male
1 TX+ White/Orange 1 TX+
2 TX- Orange 2 TX-
3 RX+ White/Green 3 RX+
4 BD4+ Blue 4 BD4+
5 BD4- White/Blue 5 BD4-
6 RX- Green 6 RX-
7 BD3+ White/Brown 7 BD3+
8 BD3- Brown 8 BD3-
Driver Version:
Version Date Description
V1.00 May/26/2011 Driver released.
409
PLC Connection Guide
HMI Setting:
Parameters Recommended Options Notes
PLC type OMRON Host Link
PLC I/F RS232 RS232, RS422, RS485
Baud rate 9600 9600, 19200
Data bits 7 7 or 8
Parity Even Even, Odd, None
Stop bits 2 1 or 2
PLC sta. no. 0 0-31 Host Link Station No.
PLC Setting:
Communication mode Host Link Protocol
Device Address:
Bit/Word Device type Format Range Memo
B IR DDDDdd 0 ~ 409515 I/O and Internal Relay
B HR DDDDdd 0 ~ 409515 Hold Relay
B LR DDDDdd 0 ~ 409515 Link Relay
B IR (Force Set/Reset) DDDDdd 0 ~ 409515
B HR (Force Set/Reset) DDDDdd 0 ~ 409515
B LR (Force Set/Reset) DDDDdd 0 ~ 409515
B AR DDDDdd 0 ~ 409515 Auxiliary Relay
W AR_W DDDD 0 ~ 4095
W IR_W DDDD 0 ~ 4095
W HR_W DDDD 0 ~ 4095
W LR_W DDDD 0 ~ 4095
W TC DDD 0 ~ 255
W DM DDDD 0 ~ 9999 Data Register
410
PLC Connection Guide
Wiring Diagram:
The following represents the cable end connector.
CPU Port (CPM2A,CQM1/1H,C200H/HS/ALPHA series)
Communication Module:
CPM1-CIF01 adapter (for CPM1/CPM1A/CPM2A series, CQM1/CQM1H series)
CPM1H-SCB41 communication module (for CQM1H-CPU51/61)
eMT3000 series
COM1 RS232 9P COM3 RS232 9P RS232 9P D-Sub Male
D-Sub Female D-Sub Female
2 RX 8 RX 2 SD
3 TX 7 TX 3 RD
5 GND 5 GND 9 GND
4 RS
circuit
5 CS
411
PLC Connection Guide
MT6050i/MT8050i
COM1 RS232 9P RS232 9P D-Sub Male
D-Sub Female
9 RX 2 SD
6 TX 3 RD
5 GND 9 GND
4 RS
circuit
5 CS
412
PLC Connection Guide
MT6050i/MT8050i
COM1 RS232 9P RS232 9P D-Sub Male
D-Sub Female
9 RX 2 SD
6 TX 3 RD
5 GND 7 GND
4 RS
circuit
5 CS
Driver Version:
Version Date Description
V1.30 OCT/21/2010
413
PLC Connection Guide
Panasonic FP
Supported Series: NAIS (Matsushita) FP series include FP-X, FP-Σ, FP0, FP1, FP2,
FP2SH, FP10SH and FP3 Ethernet support FP-X with AFPX-COM5.
Website:http://pewa.panasonic.com/
HMI Setting:
Parameters Recommended Options Notes
PLC type Panasonic FP
PLC I/F RS232 RS232/RS485
Baud rate 9600 9600, 19200, 38400,
Data bits 8 57600,
7 or 8 115200
Parity Odd Even, Odd, None
Stop bits 1 1 or 2
Must match the PLC port
PLC sta. no. 1 0-255 setting.
FP3 must set to 0.
Device Address:
Bit/Word Device type Format Range Memo
B X DDDDh 0 ~ 9999f Input (X)
B Y DDDDh 0 ~ 9999f Output (Y)
B R DDDDh 0 ~ 9999f Internal Relay (R)
B L DDDD 0 ~ 9999 Link Relay (L)
B L_Bit DDDDh 0 ~ 9999f
B T DDDD 0 ~ 9999 Timer (T)
B C DDDD 0 ~ 9999 Counter (C)
W SV DDDD 0 ~ 9999 Timer/Counter Set Value (SV)
W EV DDDDD 0 ~ 65535 Timer/Counter Elapse Value (EV)
W DT DDDDD 0 ~ 99999 Data Register (DT)
W LD DDDD 0 ~ 8447 Link Register (LD)
W WX DDDD 0 ~ 9999 Input (WX) (read only)
W WY DDDD 0 ~ 9999 Output (WY)
W WR DDDD 0 ~ 9999 Internal Relay (WR)
W WL DDDD 0 ~ 9999 Link Relay (WL)
W FL DDDDD 0 ~ 99999 File Register (FL)
414
PLC Connection Guide
Wiring Diagram:
The following represents the cable end connector.
FP0, FP2, FP2SH, FPM CPU : 9P D-Sub to 5P Mini-DIN
eMT3000 series
COM1 RS232 9P COM3 RS232 9P RS232 5P Mini-DIN
D-Sub Female D-Sub Female Male
2 RX 8 RX 2 TXD
3 TX 7 TX 3 RXD
5 GND 5 GND 1 GND
MT6050i/MT8050i
COM1 RS232 9P RS232 5P Mini-DIN
D-Sub Female Male
9 RX 2 TXD
6 TX 3 RXD
5 GND 1 GND
415
PLC Connection Guide
The following represents the cable end connector.
FP0 CPU : 9P D-Sub to 3P Terminal:
eMT3000 series
COM1 RS232 9P COM3 RS232 9P RS232 3P Terminal
D-Sub Female D-Sub Female
2 RX 8 RX S
3 TX 7 TX R
5 GND 5 GND G
MT6050i/MT8050i
COM1 RS232 9P RS232 3P Terminal
D-Sub Female
9 RX S
6 TX R
5 GND G
416
PLC Connection Guide
The following represents the cable end connector.
eMT3000 series
COM1 RS232 9P COM3 RS232 9P RS232 9P D-Sub Male
D-Sub Female D-Sub Female
2 RX 8 RX 2 TXD
3 TX 7 TX 3 RXD
5 GND 5 GND 7 GND
4 RTS
circuit
5 CTS
8 CD
circuit
9 ER
417
PLC Connection Guide
MT6050i/MT8050i
COM1 RS232 9P RS232 9P D-Sub Male
D-Sub Female
9 RX 2 TXD
6 TX 3 RXD
5 GND 7 GND
4 RTS
circuit
5 CTS
8 CD
circuit
9 ER
418
PLC Connection Guide
MT6000/8000 series except MT6050i/MT8050i
COM1 RS485 4W RS485 4W 8P Hirose
9P D-Sub Male Male
1 RX- 2 TXDA
2 RX+ 5 TXDB
3 TX- 3 RXDA
4 TX+ 6 RXDB
5 GND 1 GND
MT6050i/MT8050i
COM1 RS485 4W RS485 4W 8P Hirose
9P D-Sub Female Male
1 RX- 2 TXDA
2 RX+ 5 TXDB
3 TX- 3 RXDA
4 TX+ 6 RXDB
5 GND 1 GND
419
PLC Connection Guide
The following represents the cable end connector.
FP3 CPU : 9P D-Sub to 15P D-Sub
eMT3000 series
COM1 RS485 4W RS485 4W 15P D-Sub
9P D-Sub Male Male
1 RX- 9 TXDA
2 RX+ 2 TXDB
3 TX- 10 RXDA
4 TX+ 3 RXDB
5 GND 7 GND
4 RTS+
circuit
5 CTS+
11 RTS-
circuit
12 CTS-
420
PLC Connection Guide
MT6050i/MT8050i
COM1 RS485 4W RS485 4W 15P D-Sub
9P D-Sub Female Male
1 RX- 9 TXDA
2 RX+ 2 TXDB
3 TX- 10 RXDA
4 TX+ 3 RXDB
5 GND 7 GND
4 RTS+
circuit
5 CTS+
11 RTS-
circuit
12 CTS-
Driver Version:
Version Date Description
V1.80 Apr/09/2010 Added registers: FL
421
PLC Connection Guide
Panasonic FP (Ethernet)
Supported Series: NAIS (Matsushita) FP series include FP-X, FP-Σ, FP0, FP1, FP2,
FP2SH, FP10SH and FP3 Ethernet support FP-X with AFPX-COM5.
Website: http://pewa.panasonic.com/
HMI Setting:
Parameters Recommended Options Notes
PLC type Panasonic FP (Ethernet)
PLC I/F Ethernet
Port no. 9094
PLC sta. no. 1 0~255
Device Address:
Bit/Word Device type Format Range Memo
B X DDDDh 0 ~ 9999f Input (X)
B Y DDDDh 0 ~ 9999f Output (Y)
B R DDDDh 0 ~ 9999f Internal Relay (R)
B L DDDD 0 ~ 9999 Link Relay (L)
B L_Bit DDDDh 0 ~ 9999f
B T DDDD 0 ~ 9999 Timer (T)
B C DDDD 0 ~ 9999 Counter (C)
W SV DDDD 0 ~ 9999 Timer/Counter Set Value (SV)
W EV DDDDD 0 ~ 65535 Timer/Counter Elapse Value (EV)
W DT DDDDD 0 ~ 99999 Data Register (DT)
W LD DDDD 0 ~ 8447 Link Register (LD)
W WX DDDD 0 ~ 9999 Input (WX) (read only)
W WY DDDD 0 ~ 9999 Output (WY)
W WR DDDD 0 ~ 9999 Internal Relay (WR)
W WL DDDD 0 ~ 9999 Link Relay (WL)
W FL DDDDD 0 ~ 99999 File Register (FL)
422
PLC Connection Guide
Wiring Diagram:
Direct connect (crossover cable):
HMI RJ45 Male Wire Color PLC RJ45 Male
1 TX+ White/Orange 3 RX+
2 TX- Orange 6 RX-
3 RX+ White/Green 1 TX+
4 BD4+ Blue 4 BD4+
5 BD4- White/Blue 5 BD4-
6 RX- Green 2 TX-
7 BD3+ White/Brown 7 BD3+
8 BD3- Brown 8 BD3-
Through a hub:
HMI RJ45 Male Wire Color PLC RJ45 Male
1 TX+ White/Orange 1 TX+
2 TX- Orange 2 TX-
3 RX+ White/Green 3 RX+
4 BD4+ Blue 4 BD4+
5 BD4- White/Blue 5 BD4-
6 RX- Green 6 RX-
7 BD3+ White/Brown 7 BD3+
8 BD3- Brown 8 BD3-
Ethernet RS232
MT8000 AFPX-COM5
FP-X
423
PLC Connection Guide
Driver Version:
Version Date Description
V1.80 Apr/12/2010
424
PLC Connection Guide
Website: http://pewa.panasonic.com/
HMI Setting:
Parameters Recommended Options Notes
PLC type Panasonic FP2 (Ethernet)
PLC I/F Ethernet
Port no. 8500
PLC sta. no. 2 0~255
Device Address:
Bit/Word Device type Format Range Memo
B X DDDDh 0 ~ 9999f Input (X)
B Y DDDDh 0 ~ 9999f Output (Y)
B R DDDDh 0 ~ 9999f Internal Relay (R)
B L DDDD 0 ~ 9999 Link Relay (L)
B L_Bit DDDDh 0 ~ 9999f
B T DDDD 0 ~ 9999 Timer (T)
B C DDDD 0 ~ 9999 Counter (C)
W SV DDDD 0 ~ 9999 Timer/Counter Set Value (SV)
W EV DDDDD 0 ~ 65535 Timer/Counter Elapse Value (EV)
W DT DDDDD 0 ~ 99999 Data Register (DT)
W LD DDDD 0 ~ 8447 Link Register (LD)
W WX DDDD 0 ~ 9999 Input (WX) (read only)
W WY DDDD 0 ~ 9999 Output (WY)
W WR DDDD 0 ~ 9999 Internal Relay (WR)
W WL DDDD 0 ~ 9999 Link Relay (WL)
425
PLC Connection Guide
Wiring Diagram:
Direct connect (crossover cable):
HMI RJ45 Male Wire Color PLC RJ45 Male
1 TX+ White/Orange 3 RX+
2 TX- Orange 6 RX-
3 RX+ White/Green 1 TX+
4 BD4+ Blue 4 BD4+
5 BD4- White/Blue 5 BD4-
6 RX- Green 2 TX-
7 BD3+ White/Brown 7 BD3+
8 BD3- Brown 8 BD3-
Through a hub:
HMI RJ45 Male Wire Color PLC RJ45 Male
1 TX+ White/Orange 1 TX+
2 TX- Orange 2 TX-
3 RX+ White/Green 3 RX+
4 BD4+ Blue 4 BD4+
5 BD4- White/Blue 5 BD4-
6 RX- Green 6 RX-
7 BD3+ White/Brown 7 BD3+
8 BD3- Brown 8 BD3-
Driver Version:
Version Date Description
V1.00 Mar/11/2010 Driver released.
426
PLC Connection Guide
Panasonic MINAS A4
Supported Series: Panasonic MINAS A4 series Servo Drive.
HMI Setting:
Parameters Recommended Options Notes
PLC type Panasonic MINAS A4
PLC I/F RS232
Baud rate 9600
Data bits 8
Parity None
Stop bits 1
Axis no. 0 (master station only) 0 ~ F (slave)
Device Address:
Bit/Word Device type Format Range Memo
B Command 20 D 0~7 States (Note 3)
B Command 27 DD 0 ~ 31 Input Signal (Note 3)
B Command 28 DD 0 ~ 31 Output Signal (Note 3)
CPU Version (Numeric
W Command 01 D 0
format:16-bit Hex)
W Command 05 DD 0 ~ 11 Driver Version (ASCII / 12 words)
W Command 06 DD 0 ~ 11 Motor Version (ASCII / 12 words)
command pulse counter
W Command 21 D 0~1
(Numeric format: 32-bit Signed)
feedback pulse counter
W Command 22 D 0~1
(Numeric format: 32-bit Signed)
present speed
W Command 24 D 0
(Numeric format: 16-bit Unsigned)
present torque
W Command 25 D 0
(Numeric format: 16-bit Unsigned)
present deviation counter
W Command 26 D 0~1
(Numeric format: 32-bit Signed)
write parameter to EEPROM
W Command 84 D 0
(Note 1)
427
PLC Connection Guide
Bit/Word Device type Format Range Memo
present Alarm Data
W Command 90 D 0
(Numeric format: 16-bit Unsigned)
Alarm History (Note 4)
W Command 91 DD 1 ~ 14
(Numeric format: 16-bit Unsigned)
Batch Alarm (Note 4)
W Command 92 DD 1 ~ 14
(Numeric format: 16-bit Unsigned)
clear Alarm History (include
W Command 93 D 0
EEPROM) (Note 1)
W Command 94 D 0 Alarm Clear (Note 1)
W Command 9B D 0 Absolute Clear (Note 1)
Individual Parameter (range: 0x00
W Parameter HH 0 ~ 7f
~ 0x7F) (Note 2)
Note:
1. Command 84, Command 93, Command 94, and Command 9B are write only. (These
commands are able to use Set Bit Object and execute the write command after
triggering Set Bit Object.). Commands other than these four are read only.
2. Parameter read/write: Use device type to define address control from 00~7F.
For example: “address_00” is mapping to “Parameter_00”.
(Please refer to Panasonic MINAS A4 Series User Manual.)
3. Device address type can define MINAS A4 Driver’s command list.
Command 20, Command 27, and Command 28 are Bit type, use “Operating range” to
map communication order status.
For example: “Command 20_3” means “Read state_CCW”.
(Please refer to Panasonic MINAS A4 Series User Manual.)
4. Command 91 and Command 92 are word type, use “Operating range” to map the
record of 14 alarms.
For example: “Command 91_1” means “Read alarm data_First alarm”.
428
PLC Connection Guide
Wiring Diagram:
The following represents the cable end connector.
MINAS A4 Driver CNX4 Port
eMT3000 series
COM1 RS232 9P COM3 RS232 9P RS232 8P Mini-DIN
D-Sub Female D-Sub Female Male
2 RX 8 RX 3 TXD
3 TX 7 TX 5 RXD
5 GND 5 GND 4 GND
MT6050i/MT8050i
COM1 RS232 9P RS232 8P Mini-DIN
D-Sub Female Male
9 RX 3 TXD
6 TX 5 RXD
5 GND 4 GND
429
PLC Connection Guide
The following represents the cable end connector.
MINAS A4 Driver CNX3/CNX4 Port
eMT3000 series
COM1 RS485 2W COM3 RS485 2W RS485 2W 8P Mini-DIN
9P D-Sub Male 9P D-Sub Male Male
1 RX- 6 Data- 7 D-
2 RX+ 9 Data+ 8 D+
5 GND 5 GND
MT6050i/MT8050i
COM1 RS485 2W COM3 RS485 2W RS485 2W 8P Mini-DIN
9P D-Sub Female 9P D-Sub Female Male
1 RX- 7 Data- 7 D-
2 RX+ 8 Data+ 8 D+
5 GND 5 GND
430
PLC Connection Guide
5 GND ` 4 GND
Station No. 0
HMI connect with multi devices
431
PLC Connection Guide
Weintek HMI
Com RS232 Panasonic
MINAS A4 Driver X3
Driver X4 Driver X3 Driver X4
RS232
RS485 RS485
Driver Version:
Version Date Description
V1.10 Jan/11/2010
432
PLC Connection Guide
Panasonic MINAS A5
Supported Series: Panasonic MINAS A5 series Servo Drive.
HMI Setting:
Parameters Recommended Options Notes
PLC type Panasonic MINAS A5
PLC I/F RS232 RS232/RS485 2W
Baud rate 9600 2400~115200
Data bits 8
Parity None
Stop bits 1
Axis no. 0 (master station only) 0 ~ 127 (slave)
* When connecting with more than two devices, it is recommended to set timeout to more
than 4 seconds. Set a longer timeout when connecting with more devices to maintain good
communication.
Device Address:
Bit/Word Device type Format Range Memo
B Command 20 D 0~7 States (Note 3)
B Command 27 DD 0 ~ 31 Input Signal (Note 3)
B Command 28 DD 0 ~ 31 Output Signal (Note 3)
CPU Version (Numeric
W Command 01 D 0
format:16-bit Hex)
W Command 05 DD 0 ~ 11 Driver Version (ASCII / 12 words)
W Command 06 DD 0 ~ 11 Motor Version (ASCII / 12 words)
command pulse counter
W Command 21 D 0~1
(Numeric format: 32-bit Signed)
feedback pulse counter
W Command 22 D 0~1
(Numeric format: 32-bit Signed)
present speed
W Command 24 D 0
(Numeric format: 16-bit Unsigned)
present torque
W Command 25 D 0
(Numeric format: 16-bit Unsigned)
433
PLC Connection Guide
Bit/Word Device type Format Range Memo
present deviation counter
W Command 26 D 0~1
(Numeric format: 32-bit Signed)
write parameter to EEPROM
W Command 72 D 0
(Note 1)
present Alarm Data
W Command 90 D 0
(Numeric format: 16-bit Unsigned)
Batch Alarm (Note 4)
W Command 92 DD 1 ~ 14
(Numeric format: 16-bit Unsigned)
clear Alarm History (include
W Command 93 D 0
EEPROM) (Note 1)
W Command 94 D 0 Alarm Clear (Note 1)
W Command 9B D 0 Absolute Clear (Note 1)
Individual Parameter (range: 0x000
W Parameter HHH 0 ~ 639
~ 0x639) (Note 2)
Note:
1. Command 72, Command 93, Command 94, and Command 9B are write only. (These
commands are able to use Set Bit Object and execute the write command after
triggering Set Bit Object.). Commands other than these four are read only.
2. Parameter read/write: Use device type to define address control from 000~639.
For example: “address_000” is mapping to “Parameter_000”.
(Please refer to Panasonic MINAS A5 Series User Manual.)
3. Device address type can define MINAS A5 Driver’s command list.
Command 20, Command 27, and Command 28 are Bit type, use “Operating range” to
map communication order status.
For example: “Command 20_3” means “Read state_CCW”.
(Please refer to Panasonic MINAS A5 Series User Manual.)
4. Command 92 are word type, use “Operating range” to map the record of 14 alarms.
434
PLC Connection Guide
Wiring Diagram:
The following represents the cable end connector.
MINAS A5 Driver X2 Port RS232 Signal
eMT3000 series
COM1 RS232 9P COM3 RS232 9P RS232 8P Connector
D-Sub Female D-Sub Female
2 RX 8 RX 3 TXD
3 TX 7 TX 4 RXD
5 GND 5 GND 1 GND
MT6050i/MT8050i
COM1 RS232 9P RS232 8P Connector
D-Sub Female
9 RX 3 TXD
6 TX 4 RXD
5 GND 1 GND
435
PLC Connection Guide
The following represents the cable end connector.
MINAS A5 Driver X2 Port RS485 Signal
eMT3000 series
COM1 RS485 2W COM3 RS485 2W RS485 2W 8P
9P D-Sub Male 9P D-Sub Male Connector
1 RX- 6 Data- 5,7 485-
2 RX+ 9 Data+ 6,8 485+
5 GND 5 GND 1 GND
MT6050i/MT8050i
COM1 RS485 2W COM3 RS485 2W RS485 2W 8P
9P D-Sub Female 9P D-Sub Female Connector
1 RX- 7 Data- 5,7 485-
2 RX+ 8 Data+ 6,8 485+
5 GND 5 GND 1 GND
Driver Version:
Version Date Description
V1.00 May/23/2012 Driver released.
436
PLC Connection Guide
Parker ACR9000
Supported Series: Parker ACR9000.
Website: http://www.parkermotion.com
HMI Setting:
Parameters Recommended Options Notes
PLC type Parker ACR9000
PLC I/F RS232 RS485 4W / RS232
Baud rate 38400 1200 - 38400
Data bits 8 7,8
Parity None Even, Odd, None
Stop bits 1 1,2
PLC sta. no. 0
Device Address:
Bit/Word Device type Format Range Memo
B P_Low16bit DDDDDdd 0 ~ 9999915
B P_High16bit DDDDDdd 0 ~ 9999915
W P_Int32 DDDDD 0 ~ 99999
W P_Float DDDDD 0 ~ 99999
437
PLC Connection Guide
Wiring Diagram:
The following represents the cable end connector.
eMT3000 series
COM1 RS232 9P COM3 RS232 9P Parker AC9000 RS232
D-Sub Female D-Sub Female 9P D-Sub Male
2 RX 8 RX 3 TXD
3 TX 7 TX 2 RXD
5 GND 5 GND 5 GND
MT6050i/MT8050i
COM1 RS232 9P Parker AC9000 RS232
D-Sub Female 9P D-Sub Male
9 RX 3 TXD
6 TX 2 RXD
5 GND 5 GND
Driver Version:
Version Date Description
V1.00 Dec/30/2008 Driver released.
438
PLC Connection Guide
Parker Compax3
Supported Series: Parker Compax3 Servo Drive.
Website: http://www.parker.com
HMI Setting:
RS232
Parameters Recommended Options Notes
PLC type Parker Compax3
PLC I/F RS232
Baud rate 115200
Data bits 8 7 or 8
Parity None Even, Odd, None
Stop bits 1 1 or 2
PLC sta. no. 0 0 Must be 0 for RS232
RS485
Parameters Recommended Options Notes
PLC type Parker Compax3
PLC I/F RS485 2W
Baud rate 9600
Data bits 8 7 or 8
Parity None Even, Odd, None
Stop bits 1 1 or 2
Range from 1 to 99 for
PLC sta. no. 1 1-99 RS485, according to the
PLC setting.
439
PLC Connection Guide
PLC Setting:
How to set Compax 3 servo to RS485 mode?
1. Open C3 ServoManager2, select “Communication” => “RS-485 Settings”.
440
PLC Connection Guide
4. Download settings to Compax3 Servo.
5. Set EasyBuilder system parameter and connect with PLC for communication of HMI
and Servo.
Device Address:
Bit/Word Device type Format Range Memo
B R_Low16bit DDDDDDDDh 0 ~ 99999999f
B R_High16bit DDDDDDDDh 0 ~ 99999999f
DW Register_Int DDDDDD 0 ~ 999999 For Register INT32, U32
DW Register_float DDDDDD 0 ~ 999999 For Register INT32, U32
W Register_Short DDDDDD 0 ~ 999999 For Register INT16, U16
Wiring Diagram:
The following represents the cable end connector.
Parker Compax3 PLC X10 : RS232
eMT3000 series
COM1 RS232 9P COM3 RS232 9P RS232 9P D-Sub Male
D-Sub Female D-Sub Female
2 RX 8 RX 3 TXD
3 TX 7 TX 2 RXD
5 GND 5 GND 5 GND
441
PLC Connection Guide
MT6050i/MT8050i
COM1 RS232 9P RS232 9P D-Sub Male
D-Sub Female
9 RX 3 TXD
6 TX 2 RXD
5 GND 5 GND
442
PLC Connection Guide
MT6050i/MT8050i
COM1 RS485 2W COM3 RS485 2W RS485 2W 9P D-Sub
9P D-Sub Female 9P D-Sub Female Male
1 RX- 7 Data- 3 RXD
2 RX+ 8 Data+ 7 TXD
5 GND 5 GND 5 GND
1 nable RS485
circuit
9 +5V
Driver Version:
Version Date Description
V1.70 Mar/30/2009
443
PLC Connection Guide
HMI Setting:
Parameters Recommended Options Notes
PLC type Parker Compumotor 6K Series
PLC I/F RS232
Baud rate 9600
Data bits 8
Parity None
Stop bits 1
PLC sta. no. 0
Device Address:
Bit/Word Device type Format Range Memo
B VARB(L) DDDdd 1 ~ 125 The lower 16 bits data of VARB
B VARB(H) DDDdd 1 ~ 125 The higher 16 bits data of VARB
D RUN_PRG D 0
DW VARI DDD 1 ~ 125
Must select single float data
DW VAR DDD 1 ~ 125
mode.
Wiring Diagram:
The following represents the cable end connector.
eMT3000 series
COM1 RS232 9P COM3 RS232 9P PLC RS232 9P D-Sub
D-Sub Female D-Sub Female Male
2 RX 8 RX 3 TX
3 TX 7 TX 2 RX
5 GND 5 GND 5 GND
444
PLC Connection Guide
MT6000/8000 series except MT6050i/MT8050i
COM1 RS232 9P COM2 RS232 9P COM3 RS232 9P PLC RS232 9P D-Sub
D-Sub Female D-Sub Female D-Sub Male Male
2 RX 6 RX 8 RX 3 TX
3 TX 4 TX 7 TX 2 RX
5 GND 5 GND 5 GND 5 GND
MT6050i/MT8050i
COM1 RS232 9P PLC RS232 9P D-Sub
D-Sub Female Male
9 RX 3 TX
6 TX 2 RX
5 GND 5 GND
Driver Version:
Version Date Description
V1.00 Apr/7/2011 Driver released.
445
PLC Connection Guide
Website: http://www.parker.com/portal/site/PARKER/
HMI Setting:
Parameters Recommended Options Notes
PLC type Parker SLVD Series
PLC I/F RS485 4W
Baud rate 9600 9600/19200
Data bits 8 7,8
Parity Even Even, Odd, None
Stop bits 1 1,2
PLC sta. no. 0 0-31
Device Address:
Bit/Word Device type Format Range Memo
B Par_Binary DDDDdd 0 ~ 999915 Set bit parameter
W Par_One_Word DDDD 0 ~ 9999 Set 2 bytes parameter
DW Par_Two_Word DDDD 0 ~ 9999 Set 4 bytes parameter
W Par_One_Byte DDDD 0 ~ 9999 Set 1 byte prarmeter
W RESET D 0
W RUN D 0
446
PLC Connection Guide
Wiring Diagram:
The following represents the cable end connector.
Parker SLVD Servo Serial Link X1
eMT3000 series
COM1 RS485 4W RS485 4W 15P D-Sub
9P D-Sub Male Male
1 RX- 7 TX-
2 RX+ 12 TX+
3 TX- 2 RX-
4 TX+ 1 RX+
circuit
6 TER
5 GND 3 GND
447
PLC Connection Guide
MT6050i/MT8050i
COM1 RS485 4W RS485 4W 15P D-Sub
9P D-Sub Female Male
1 RX- 7 TX-
2 RX+ 12 TX+
3 TX- 2 RX-
4 TX+ 1 RX+
circuit
6 TER
5 GND 3 GND
Driver Version:
Version Date Description
V1.00 Jan/27/2010 Driver released.
448
PLC Connection Guide
Website: http://www.ab.com
HMI Setting:
Parameters Recommended Options Notes
PLC type Allen-Bradley CompactLogix – Free Tag Names
PLC I/F RS232
Baud rate 19200 9600, 19200, 38400
Data bits 8 8
Parity None Even, Odd, None
Stop bits 1 1
HMI sta. no. 0
PLC sta. no. 1 1-31
PLC Setting:
DF1 Full Duplex protocol 19200, None, 8, 1 (default)
Communication mode
Error Check: BCC, Station Address: 1
Device Address:
PLC Data EasyBuilder Data
Bit/Word Memo
Type Name Format
BitArray
SINT
16-bit signed,
INT Integer -32768 ~ 32767
ASCII
449
PLC Connection Guide
Wiring Diagram:
The following represents the cable end connector.
eMT3000 series
COM1 RS232 9P COM3 RS232 9P AB CPU CH0 RS232 9P
D-Sub Female D-Sub Female D-Sub Female
2 RX 8 RX 3 TD
3 TX 7 TX 2 RD
5 GND 5 GND 5 GND
MT6050i/MT8050i
COM1 RS232 9P AB CPU CH0 RS232 9P
D-Sub Female D-Sub Female
9 RX 3 TD
6 TX 2 RD
5 GND 5 GND
Driver Version:
Version Date Description
V1.00 June/2/2011 Driver released.
450
PLC Connection Guide
Rockwell CompactLogix/FlexLogix
Supported Series: Rockwell ControlLogix, CompactLogix, FlexLogix CH0 DF1.
Website: http://www.ab.com
HMI Setting:
Parameters Recommended Options Notes
PLC type Allen-Bradley CompactLogix/FlexLogix
PLC I/F RS232
Baud rate 19200 9600, 19200, 38400
Data bits 8 8
Parity None Even, Odd, None
Stop bits 1 1
HMI sta. no. 0
PLC sta. no. 1 1-31
PLC Setting:
DF1 Full Duplex protocol 19200, None, 8, 1 (default)
Communication mode
Error Check: BCC, Station Address: 1
451
PLC Connection Guide
ControlLogix, CompactLogix CPU CH0 setting:
Create a Tag:
The name format must be 4 chars. For example: B003, T004, C005, N007, and F008.
Two or three chars are not available. For example: B03 or B3.
452
PLC Connection Guide
Device Address:
Bit/Word Device type Format Range Memo
B B_BOOL FFFDDDdd 0 ~ 25525515 Bit data file
Integer data file bit level (N7, 10 ~
B N_BOOL FFFDDDdd 0 ~ 25525515
255)
Timer Accumulator Value (T4, T10
DW Tx.ACC FFFDDD 0 ~ 255255
~ 255)
Timer Preset Value
DW Tx.PRE FFFDDD 0 ~ 255255
(T4, T10 ~ 255)
Integer data file
DW Nx_INT FFFDDD 0 ~ 255255
(N7, 10 ~ 255)
W Bx_INT FFFDDD 0 ~ 255255 Bit data file word level
Counter Accumulator Value (C5,
DW Cx.ACC FFFDDD 0 ~ 255255
C10 ~ 255)
Counter Preset Value
DW Cx.PRE FFFDDD 0 ~ 255255
(C5, C10 ~ 255)
Floating point data file
W F8_REAL DDD 0 ~ 255
(F8)
Floating point data file (F008, F010
W Fx_REAL FFFDDD 0 ~ 255255
~ F255)
453
PLC Connection Guide
Wiring Diagram:
The following represents the cable end connector.
eMT3000 series
COM1 RS232 9P COM3 RS232 9P AB CPU CH0 RS232 9P
D-Sub Female D-Sub Female D-Sub Female
2 RX 8 RX 3 TD
3 TX 7 TX 2 RD
5 GND 5 GND 5 GND
MT6050i/MT8050i
COM1 RS232 9P AB CPU CH0 RS232 9P
D-Sub Female D-Sub Female
9 RX 3 TD
6 TX 2 RD
5 GND 5 GND
Driver Version:
Version Date Description
V1.50 Dec/30/2008
454
PLC Connection Guide
Rockwell DF1
Supported Series: Rockwell MicroLogix 1000, 1100, 1200, 1400, 1500, SLC 5/03, 5/04,
5/05.
Website: http://www.ab.com
Note: Allen-Bradley DF1 driver uses CRC checksum.
HMI Setting:
Parameters Recommended Options Notes
PLC type Allen-Bradley DF1
PLC I/F RS232
Baud rate 9600 9600, 19200, 38400
Data bits 8 8
Parity None Even, Odd, None
Stop bits 1 1
HMI sta. no. 0
PLC sta. no. 1 1-31
PLC Setting:
DF1 Full Duplex protocol 19200, None, 8, 1 (default)
Communication mode
Error Check: CRC
Device Address:
Bit/Word Device type Format Range Memo
B I1 DDDdd 0 ~ 25515 Input (I)
B O0 DDDdd 0 ~ 25515 Output (O)
B B3 DDDdd 0 ~ 25515 Bit data file (B3)
B B10 ~ 13 DDDdd 0 ~ 25515 Bit data file (B10 ~ 13)
B S_Bit DDDdd 0 ~ 25515 Status (S) bit level
B Bfn FFFDDDdd 0 ~ 25525515 Bit data file (B3, 10 ~ 254)
Integer data file bit level
B NfnBit FFFDDDdd 0 ~ 25525515
(N7, 10 ~ 254)
W T4SV DDD 0 ~ 255 Timer Preset Value (T4)
W T4PV DDD 0 ~ 255 Timer Accumulator Value (T4)
455
PLC Connection Guide
Bit/Word Device type Format Range Memo
W C5SV DDD 0 ~ 255 Counter Preset Value (C5)
W C5PV DDD 0 ~ 255 Counter Accumulator Value (C5)
W TfnSV FFFDDD 0 ~ 255255 Timer Preset Value
W TfnPV FFFDDD 0 ~ 255255 Timer Accumulator Value
W CfnSV FFFDDD 0 ~ 255255 Counter Preset Value
W CfnPV FFFDDD 0 ~ 255255 Counter Accumulator Value
W N7 DDD 0 ~ 255 Integer data file (N7)
W N10 ~ 15 DDD 0 ~ 255 Integer data file (N10 ~ 15)
Integer data file
W Nfn FFFDDD 0 ~ 255255
(N7, 10 ~ 254)
W S DDD 0 ~ 255 Status (S)
W F8 DDD 0 ~ 255 Floating point data file (F8)
W Ffn FFFDDD 0 ~ 255255
W Lfn FFFDDD 0 ~ 255255
Wiring Diagram:
The following represents the cable end connector.
9P D-Sub to 8P Mini-DIN: MicroLogix 1000, 1100, 1200, 1400, 1500
eMT3000 series
COM1 RS232 9P COM3 RS232 9P MicroLogix RS232 8P
D-Sub Female D-Sub Female Mini-DIN Male
2 RX 8 RX 7 TXD
3 TX 7 TX 4 RXD
5 GND 5 GND 2 GND
456
PLC Connection Guide
MT6000/8000 series except MT6050i/MT8050i
COM1 RS232 9P COM2 RS232 9P COM3 RS232 9P MicroLogix RS232 8P
D-Sub Female D-Sub Female D-Sub Male Mini-DIN Male
2 RX 6 RX 8 RX 7 TXD
3 TX 4 TX 7 TX 4 RXD
5 GND 5 GND 5 GND 2 GND
MT6050i/MT8050i
COM1 RS232 9P MicroLogix RS232 8P
D-Sub Female Mini-DIN Male
9 RX 7 TXD
6 TX 4 RXD
5 GND 2 GND
457
PLC Connection Guide
MT6000/8000 series except MT6050i/MT8050i
COM1 RS232 9P COM2 RS232 9P COM3 RS232 9P AB CPU CH0 RS232 9P
D-Sub Female D-Sub Female D-Sub Male D-Sub Female
2 RX 6 RX 8 RX 3 TD
3 TX 4 TX 7 TX 2 RD
5 GND 5 GND 5 GND 5 GND
MT6050i/MT8050i
COM1 RS232 9P AB CPU CH0 RS232 9P
D-Sub Female D-Sub Female
9 RX 3 TD
6 TX 2 RD
5 GND 5 GND
Driver Version:
Version Date Description
V2.20 Jan/05/2010
458
PLC Connection Guide
Website: http://www.ab.com
Note: Allen-Bradley DF1 (BCC) and Allen-Bradley DF1 are the same; the only difference is
the use of BCC checksum.
HMI Setting:
Parameters Recommended Options Notes
PLC type Allen-Bradley DF1 (BCC)
PLC I/F RS232
Baud rate 19200 9600, 19200, 38400
Data bits 8 8
Parity None Even, Odd, None
Stop bits 1 1
HMI sta. no. 0
PLC sta. no. 1 1-31
PLC Setting:
DF1 Full Duplex protocol 19200, None, 8, 1 (default)
Communication mode
Error Check: CRC
Device Address:
Bit/Word Device type Format Range Memo
B I1 DDDdd 0 ~ 25515 Input (I)
B O0 DDDdd 0 ~ 25515 Output (O)
B B3 DDDdd 0 ~ 25515 Bit data file (B3)
B B10 ~ 13 DDDdd 0 ~ 25515 Bit data file (B10 ~ 13)
B S_Bit DDDdd 0 ~ 25515 Status (S) bit level
B Bfn FFFDDDdd 0 ~ 25525515 Bit data file (B3, 10 ~ 254)
Integer data file bit level (N7, 10 ~
B NfnBit FFFDDDdd 0 ~ 25525515 254)
W T4SV DDD 0 ~ 255 Timer Preset Value (T4)
W T4PV DDD 0 ~ 255 Timer Accumulator Value (T4)
459
PLC Connection Guide
Bit/Word Device type Format Range Memo
W C5SV DDD 0 ~ 255 Counter Preset Value (C5)
W C5PV DDD 0 ~ 255 Counter Accumulator Value (C5)
W TfnSV FFFDDD 0 ~ 255255 Timer Preset Value
W TfnPV FFFDDD 0 ~ 255255 Timer Accumulator Value
W CfnSV FFFDDD 0 ~ 255255 Counter Preset Value
W CfnPV FFFDDD 0 ~ 255255 Counter Accumulator Value
W N7 DDD 0 ~ 255 Integer data file (N7)
W N10~15 DDD 0 ~ 255 Integer data file (N10 ~ 15)
Integer data file
W Nfn FFFDDD 0 ~ 255255 (N7, 10 ~ 254)
W S DDD 0 ~ 255 Status (S)
W F8 DDD 0 ~ 255 Floating point data file (F8)
W Ffn FFFDDD 0 ~ 255255
W Lfn FFFDDD 0 ~ 255255
Wiring Diagram:
The following represents the cable end connector.
9P D-Sub to 8P Mini-DIN: MicroLogix 1000, 1100, 1200, 1500
eMT3000 series
COM1 RS232 9P COM3 RS232 9P MicroLogix RS232 8P
D-Sub Female D-Sub Female Mini-DIN Male
2 RX 8 RX 7 TXD
3 TX 7 TX 4 RXD
5 GND 5 GND 2 GND
460
PLC Connection Guide
MT6000/8000 series except MT6050i/MT8050i
COM1 RS232 9P COM2 RS232 9P COM3 RS232 9P MicroLogix RS232 8P
D-Sub Female D-Sub Female D-Sub Male Mini-DIN Male
2 RX 6 RX 8 RX 7 TXD
3 TX 4 TX 7 TX 4 RXD
5 GND 5 GND 5 GND 2 GND
MT6050i/MT8050i
COM1 RS232 9P MicroLogix RS232 8P
D-Sub Female Mini-DIN Male
9 RX 7 TXD
6 TX 4 RXD
5 GND 2 GND
461
PLC Connection Guide
MT6000/8000 series except MT6050i/MT8050i
COM1 RS232 9P COM2 RS232 9P COM3 RS232 9P AB CPU CH0 RS232 9P
D-Sub Female D-Sub Female D-Sub Male D-Sub Female
2 RX 6 RX 8 RX 3 TD
3 TX 4 TX 7 TX 2 RD
5 GND 5 GND 5 GND 5 GND
MT6050i/MT8050i
COM1 RS232 9P AB CPU CH0 RS232 9P
D-Sub Female D-Sub Female
9 RX 3 TD
6 TX 2 RD
5 GND 5 GND
Driver Version:
Version Date Description
V2.30 Apr/26/2010
462
PLC Connection Guide
Rockwell DH485
Supported Series: Rockwell MicroLogix 1000, 1100, 1200, 1500, SLC 5/03, 5/04, 5/05.
Website: http://www.ab.com
HMI Setting:
Parameters Recommended Options Notes
PLC type Allen-Bradley DH485
PLC I/F RS485 2W RS232
Baud rate 19200 9600, 19200
Data bits 8
Parity Even
Stop bits 1
HMI sta. no. 0 2
PLC sta. no. 1 1-31
PLC Setting:
DH485 protocol 19200 (default)
Communication mode
Set the Max. Node Address to the number of PLCs in use.
463
PLC Connection Guide
Device Address:
Bit/Word Device type Format Range Memo
B I1 DDDdd 0 ~ 25515 Input (I)
B O0 DDDdd 0 ~ 25515 Output (O)
B B3 DDDdd 0 ~ 25515 Bit data file (B3)
B B10 ~ 13 DDDdd 0 ~ 25515 Bit data file (B10 ~ 13)
B Bfn FFFDDDdd 0 ~ 25525515 Bit data file (B3, 10 ~ 254)
Integer data file bit level (N7,10 ~
B NfnBit FFFDDDdd 0 ~ 25525515
254)
B S_Bit DDDdd 0 ~ 25515 Status file
W T4SV DDD 0 ~ 255 Timer Preset Value (T4)
W T4PV DDD 0 ~ 255 Timer Accumulator Value (T4)
W C5SV DDD 0 ~ 255 Counter Preset Value (C5)
W C5PV DDD 0 ~ 255 Counter Accumulator Value (C5)
W TfnSV FFFDDD 0 ~ 255255 Timer Preset Value
W TfnPV FFFDDD 0 ~ 255255 Timer Accumulator Value
W CfnSV FFFDDD 0 ~ 255255 Counter Preset Value
W CfnPV FFFDDD 0 ~ 255255 Counter Accumulator Value
W F8 DDD 0 ~ 255 Floating point data file (F8)
W N7 DDD 0 ~ 255 Integer data file (N7)
W N10 ~ 15 DDD 0 ~ 255 Integer data file (N10 ~ 15)
Integer data file
W Nfn FFFDDD 0 ~ 255255
(N7,10 ~ 254)
W S DDD 0 ~ 255 Status file
464
PLC Connection Guide
Wiring Diagram:
The following represents the cable end connector.
RS-485: SLC500 Fixed type, SLC5/01, 02, 03 CH1.
HMI can’t connect to 1747-AIC peripheral port.
eMT3000 series
COM1 RS485 2W COM3 RS485 2W AB SLC500 DH485
9P D-Sub Male 9P D-Sub Male RJ8 Male
1 RX- 6 Data- 2 SDB
2 RX+ 9 Data+ 1 SDA
5 GND 5 GND 7 GND
MT6050i/MT8050i
COM1 RS485 2W COM3 RS485 2W AB SLC500 DH485
9P D-Sub Female 9P D-Sub Female RJ8 Male
1 RX- 7 Data- 2 SDB
2 RX+ 8 Data+ 1 SDA
5 GND 5 GND 7 GND
465
PLC Connection Guide
9P D-Sub to 8P Mini-DIN: MicroLogix 1000, 1100, 1200, and 1500 must set DH485
protocol.
eMT3000 series
COM1 RS232 9P COM3 RS232 9P MicroLogix RS232 8P
D-Sub Female D-Sub Female Mini-DIN Male
2 RX 8 RX 7 TXD
3 TX 7 TX 4 RXD
5 GND 5 GND 2 GND
MT6050i/MT8050i
COM1 RS232 9P MicroLogix RS232 8P
D-Sub Female Mini-DIN Male
9 RX 7 TXD
6 TX 4 RXD
5 GND 2 GND
466
PLC Connection Guide
9P D-Sub to 9P D-Sub: SLC5/03, 04, 05 CH0 must set DH485 protocol.
eMT3000 series
COM1 RS232 9P COM3 RS232 9P AB CPU CH0 RS232 9P
D-Sub Female D-Sub Female D-Sub Female
2 RX 8 RX 3 TD
3 TX 7 TX 2 RD
5 GND 5 GND 5 GND
MT6050i/MT8050i
COM1 RS232 9P AB CPU CH0 RS232 9P
D-Sub Female D-Sub Female
9 RX 3 TD
6 TX 2 RD
5 GND 5 GND
Driver Version:
Version Date Description
V1.20 Apr/17/2009
467
PLC Connection Guide
Website: http://www.ab.com
HMI Setting:
Parameters Recommended Options Notes
PLC type Allen-Bradley EtherNet/IP (CompactLogix)
PLC I/F Ethernet
Port no. 44818
PLC sta. no. 1
PLC Setting:
RSLogix 5000 setting
Create a Tag:
The name format must be 4 chars. For example: B003, T004, C005, N007, and F008.
Two or three chars are not available. For example: B03 or B3.
468
PLC Connection Guide
Device Address:
Bit/Word Device type Format Range Memo
B Bx_BOOL FFFDDDdd 0 ~ 25525515 Bit data file
Integer data file bit level (N7, 10
B Nx_BOOL FFFDDDdd 0 ~ 25525515
~ 99)
W Bx_INT FFFDDD 0 ~ 255255 Bit data file word level
Integer data file
W Nx_INT FFFDDD 0 ~ 255255
(N7, 10 ~ 99)
DW (F) F8_REAL DDD 0 ~ 255 Floating point data file (F8)
DW (F) Fx_REAL FFFDDD 0 ~ 255255 Floating point data file (F8)
Counter Accumulator Value (C5,
DW Cx.ACC FFFDDD 0 ~ 255255
C10 ~ 255)
Counter Preset Value
DW Cx.PRE FFFDDD 0 ~ 255255
(C5, C10 ~ 255)
Timer Accumulator Value (T4,
DW Tx.ACC FFFDDD 0 ~ 255255
T10 ~ 255)
Timer Preset Value
DW Tx.PRE FFFDDD 0 ~ 255255
(T4, T10 ~ 255)
DW Lx.DINT FFFDDD 0 ~ 255255
469
PLC Connection Guide
Wiring Diagram:
Driv Direct connect (crossover cable):
HMI RJ45 Male Wire Color PLC RJ45 Male
1 TX+ White/Orange 3 RX+
2 TX- Orange 6 RX-
3 RX+ White/Green 1 TX+
4 BD4+ Blue 4 BD4+
5 BD4- White/Blue 5 BD4-
6 RX- Green 2 TX-
7 BD3+ White/Brown 7 BD3+
8 BD3- Brown 8 BD3-
Through a hub:
HMI RJ45 Male Wire Color PLC RJ45 Male
1 TX+ White/Orange 1 TX+
2 TX- Orange 2 TX-
3 RX+ White/Green 3 RX+
4 BD4+ Blue 4 BD4+
5 BD4- White/Blue 5 BD4-
6 RX- Green 6 RX-
7 BD3+ White/Brown 7 BD3+
8 BD3- Brown 8 BD3-
Driver Version:
Version Date Description
V1.30 Dec/30/2008
V1.50 Mar/6/2012 Added register: Lx.DINT
470
PLC Connection Guide
Website: http://www.ab.com
HMI Setting:
Parameters Recommended Options Notes
Allen-Bradley EtherNet/IP
PLC type
(CompactLogix) – Free Tag Names
PLC I/F Ethernet
Port no. 44818
PLC sta. no. 1
PLC Setting:
1. Set PLC IP address.
471
PLC Connection Guide
2. Create Tags.
Note: The List Separator of the exported CSV file must be “,” otherwise it may not work.
The directory of changing system settings: Control Panel / Date, Time, Language, and
Regional Options / Change the format of numbers, dates, and times / Customize /
List separator. Please select “,” and export CSV file after setting.
472
PLC Connection Guide
4. In EasyBuilder, add Allen-Bradley EtherNet/IP (CompactLogix)- Free Tag Names driver.
Input PLC IP address. On System Parameter Settings dialog click [Import Tag…] button.
5. On object dialog, select PLC, click Tag and select a Controller Tag.
Device Address:
PLC data type EasyBuilder data
Bit/Word Memo
name format
BOOL Boolean Bit object
BitArray
SINT
INT Integer 16-bit signed, ASCII -32768 ~ 32767
DINT Double Integer 32-bit signed -231 ~ (231-1)
REAL Single Precision Float 32-bit Float IEEE 754
473
PLC Connection Guide
Wiring Diagram:
Direct connect (crossover cable):
HMI RJ45 Male Wire Color PLC RJ45 Male
1 TX+ White/Orange 3 RX+
2 TX- Orange 6 RX-
3 RX+ White/Green 1 TX+
4 BD4+ Blue 4 BD4+
5 BD4- White/Blue 5 BD4-
6 RX- Green 2 TX-
7 BD3+ White/Brown 7 BD3+
8 BD3- Brown 8 BD3-
Through a hub:
HMI RJ45 Male Wire Color PLC RJ45 Male
1 TX+ White/Orange 1 TX+
2 TX- Orange 2 TX-
3 RX+ White/Green 3 RX+
4 BD4+ Blue 4 BD4+
5 BD4- White/Blue 5 BD4-
6 RX- Green 6 RX-
7 BD3+ White/Brown 7 BD3+
8 BD3- Brown 8 BD3-
Driver Version:
Version Date Description
V1.10 Aug/25/2010
474
PLC Connection Guide
Website: http://www.ab.com
HMI Setting:
Parameters Recommended Options Notes
Allen-Bradley EtherNet/IP
PLC type
(ControlLogix) – Free Tag Names
PLC I/F Ethernet
Port no. 44818
PLC sta. no. The same as CPU Slot No.
PLC Setting:
1. Set PLC IP address.
475
PLC Connection Guide
2. Create Tags.
476
PLC Connection Guide
4. In EasyBuilder , add Allen-Bradley EtherNet/IP (ControlLogix) – Free Tag Names driver.
Input PLC IP address. On System Parameter Settings dialog click [Import Tag…] button.
5. On object dialog, select PLC, click Tag and select a Controller Tag.
477
PLC Connection Guide
Device Address:
PLC data type EasyBuilder data
Bit/Word Memo
name format
BOOL Boolean Bit object
BitArray
SINT
INT Integer 16-bit signed, ASCII -32768 ~ 32767
DINT Double Integer 32-bit signed -231 ~ (231-1)
REAL Single Precision Float 32-bit Float IEEE 754
Wiring Diagram:
Direct connect (crossover cable):
HMI RJ45 Male Wire Color PLC RJ45 Male
1 TX+ White/Orange 3 RX+
2 TX- Orange 6 RX-
3 RX+ White/Green 1 TX+
4 BD4+ Blue 4 BD4+
5 BD4- White/Blue 5 BD4-
6 RX- Green 2 TX-
7 BD3+ White/Brown 7 BD3+
8 BD3- Brown 8 BD3-
Through a hub:
HMI RJ45 Male Wire Color PLC RJ45 Male
1 TX+ White/Orange 1 TX+
2 TX- Orange 2 TX-
3 RX+ White/Green 3 RX+
4 BD4+ Blue 4 BD4+
5 BD4- White/Blue 5 BD4-
6 RX- Green 6 RX-
7 BD3+ White/Brown 7 BD3+
8 BD3- Brown 8 BD3-
478
PLC Connection Guide
Driver Version:
Version Date Description
V1.10 Oct/05/2010
479
PLC Connection Guide
Website: http://www.ab.com
HMI Setting:
Parameters Recommended Options Notes
PLC type Allen-Bradley EtherNet/IP (DF1)
PLC I/F Ethernet
Port no. 44818
HMI sta. no. 0
PLC sta. no. 1
PLC Setting:
Communication mode Port Setting: 10/100 Mbps Full Duplex/Half Duplex
Device Address:
Bit/Word Device type Format Range Memo
B I1 DDDdd 0 ~ 25515 Input (I)
B O0 DDDdd 0 ~ 25515 Output (O)
B B3 DDDdd 0 ~ 25515 Bit data file (B3)
B S_Bit DDDDDDdd 0 ~ 25525515 Status file
B Bfn FFFDDDdd 0 ~ 25525515 Bit data file (B3, 10 ~ 254)
Integer data file bit level (N7, 10 ~
B NfnBit FFFDDDdd 0 ~ 25525515
254)
W T4SV DDD 0 ~ 255 Timer Preset Value (T4)
W T4PV DDD 0 ~ 255 Timer Accumulator Value (T4)
W C5SV DDD 0 ~ 255 Counter Preset Value (C5)
W C5PV DDD 0 ~ 255 Counter Accumulator Value (C5)
W TfnSV FFFDDD 0 ~ 255255
W TfnPV FFFDDD 0 ~ 255255
W CfnSV FFFDDD 0 ~ 255255
480
PLC Connection Guide
Bit/Word Device type Format Range Memo
W CfnPV FFFDDD 0 ~ 255255
W S DDD 0 ~ 255
W N7 DDD 0 ~ 255 Integer data file (N7)
Integer data file
W Nfn FFFDDD 0 ~ 255255
(N7, 10 ~ 254)
DW (F) F8 DDD 0 ~ 255 Floating point data file (F8)
Floating point data file
DW (F) Ffn FFFDDD 0 ~ 255255
(F8, 10 ~ 254)
Driver version 2.00 or later
DW Lfn FFFDDD 0 ~ 255255
supported
Wiring Diagram:
Direct connect (crossover cable):
RS232 DF1
Ethernet
Crossover cable
481
PLC Connection Guide
Through a hub:
Switch Hub
MT8000
Driver Version:
Version Date Description
V2.00 Dec/21/2009 Add Lfn register.
482
PLC Connection Guide
Rockwell PLC5
Website: http://www.ab.com
HMI Setting:
Parameters Recommended Options Notes
PLC type Allen-Bradley PLC5
PLC I/F RS232
Baud rate 19200 9600, 19200
Data bits 8 8
Parity Even Even, Odd, None
Stop bits 1 1
HMI sta. no. 0
PLC sta. no. 1 1-31
PLC Setting:
Communication mode DF1 Full Duplex protocol 19200, None, 8, 1 (default)
Device Address:
Bit/Word Device type Format Range Memo
B I1 DDDdd 0 ~ 25515 Input (I)
B O0 DDDdd 0 ~ 25515 Output (O)
B B3 DDDdd 0 ~ 99915 Bit data file (B3)
B B10 ~ 13 DDDdd 0 ~ 99915 Bit data file (B10 ~ 13)
B S_Bit DDDDDDdd 0 ~ 25599915
B Bfn FFFDDDdd 0 ~ 25599915
B NfnBit FFFDDDdd 0 ~ 25599915
W T4SV DDD 0 ~ 999 Timer Preset Value (T4)
483
PLC Connection Guide
Bit/Word Device type Format Range Memo
W T4PV DDD 0 ~ 999 Timer Accumulator Value (T4)
W C5SV DDD 0 ~ 999 Counter Preset Value (C5)
W C5PV DDD 0 ~ 999 Counter Accumulator Value (C5)
W TfnSV FFFDDD 0 ~ 255999
W TfnPV FFFDDD 0 ~ 255999
W CfnSV FFFDDD 0 ~ 255999
W CfnPV FFFDDD 0 ~ 255999
W N7 DDD 0 ~ 999 Integer data file (N7)
W N10 ~ 15 DDD 0 ~ 999 Integer data file (N10 ~ 15)
Integer data file
W Nfn FFFDDD 0 ~ 255999
(V2.5.0 or newer)
W S DDD 0 ~ 255
W F8 DDD 0 ~ 999 Floating point data file (F8)
Floating point data file
W Ffn FFFDDD 0 ~ 255999
(V2.5.0 or newer)
Wiring Diagram:
The following represents the cable end connector.
9P D-Sub to 25P D-Sub: PLC5 CPU CH0
eMT3000 series
COM1 RS232 9P COM3 RS232 9P AB CPU CH0 RS232
D-Sub Female D-Sub Female 25P D-Sub Male
2 RX 8 RX 3 TD
3 TX 7 TX 2 RD
5 GND 5 GND 7 GND
484
PLC Connection Guide
MT6000/8000 series except MT6050i/MT8050i
COM1 RS232 9P COM2 RS232 9P COM3 RS232 9P AB CPU CH0 RS232
D-Sub Female D-Sub Female D-Sub Male 25P D-Sub Male
2 RX 6 RX 8 RX 3 TD
3 TX 4 TX 7 TX 2 RD
5 GND 5 GND 5 GND 7 GND
MT6050i/MT8050i
COM1 RS232 9P AB CPU CH0 RS232
D-Sub Female 25P D-Sub Male
9 RX 3 TD
6 TX 2 RD
5 GND 7 GND
Note:
The default error checking of AB PLC5 is BCC, whereas our driver is CRC.
485
PLC Connection Guide
Access [Channel Configuration] from RSLogix5, under Channel 0 tab, please select “CRC”
for [Error Detect].
Driver Version:
Version Date Description
V1.20 Apr/17/2009
486
PLC Connection Guide
Website: http://www.oemax.co.kr
HMI Setting:
Parameters Recommended Options Notes
PLC type RS Automation OEMAX Series
PLC I/F RS232
Baud rate 9600 9600, 19200, 38400
Data bits 8 8
Parity None Even, Odd, None
Stop bits 1 1
PLC sta. no. 0
Device Address:
Bit/Word Device type Format Range Memo
B R DDDdd 0 ~ 25515
B L DDDdd 0 ~ 25515
B M DDDDdd 0 ~ 199915
B K DDDdd 0 ~ 25515 Keep Contact
B F DDDdd 0 ~ 99115 Special Contact
B TC DDD 0 ~ 255 Timer/Counter
W W DDDD 0 ~ 7999 Data Register
W SV DDD 0 ~ 255 Timer/Counter Set Value
W PV DDD 0 ~ 255 Timer/Counter Preset Value
W SR DDD 0 ~ 255 Special Register
W WR DDD 0 ~ 255
W WL DDD 0 ~ 255
W WM DDDD 0 ~ 1999
W WK DDD 0 ~ 255
W WF DDD 0 ~ 991
487
PLC Connection Guide
Wiring Diagram:
The following represents the cable end connector.
eMT3000 series
COM1 RS232 9P COM3 RS232 9P Port1 RS232 9P D-Sub
D-Sub Female D-Sub Female Male
2 RX 8 RX 2 TXD
3 TX 7 TX 3 RXD
5 GND 5 GND 5 GND
MT6050i/MT8050i
COM1 RS232 9P Port1 RS232 9P D-Sub
D-Sub Female Male
9 RX 2 TXD
6 TX 3 RXD
5 GND 5 GND
Driver Version:
Version Date Description
V1.00 Dec/30/2008 Driver released.
488
PLC Connection Guide
Website :http://www.saia-burgess.com/
HMI Setting:
Parameters Recommended Options Notes
PLC type SAIA PCD PGU Mode PDS driver
PLC I/F RS232 RS232, RS485
Baud rate 9600 9600, 19200
Data bits 7 7,8
Parity Even Even, Odd, None
Stop bits 1 1
PLC sta. no. 1 0-255
Device Address:
Bit/Word Device type Format Range Memo
B Flag DDDD 0 ~ 8191
B Output DDD 0 ~ 511
B Input DDD 0 ~ 511
W Register DDDD 0 ~ 4095
W Counter DDDD 0 ~ 1599
W Timer DDDD 0 ~ 1599
W Reg_Float DDDD 0 ~ 4095 support single float point
W Reg_Word DDDD 0 ~ 4095
489
PLC Connection Guide
Wiring Diagram:
The following represents the cable end connector.
eMT3000 series
COM1 RS232 9P RS232 9P D-Sub Male
D-Sub Female
2 RX 3 TXD
3 TX 2 RXD
5 GND 5 GND
7 RTS 6 DSR
7 RTS circuit
8 CTS
Driver Version:
Version Date Description
V1.02 Dec/30/2008
490
PLC Connection Guide
Website: http://www.saia-burgess.com/
HMI Setting:
Parameters Recommended Options Notes
PLC type SAIA PCD S-BUS Mode PDS driver
PLC I/F RS232 RS232, RS485
Baud rate 9600 9600, 19200, 38400
Data bits 8 7,8
Parity None Even, Odd, None
Stop bits 1 1
PLC sta. no. 0 0-255
PLC Setting:
Communication mode 9600,N,8,1 (default)
RS232 Port 0-Type: RS232
RS485 2W S-BUS Mode: Data(S2), Port 1-Type: RS485
491
PLC Connection Guide
2. Give a project name.
4. Go to “Online Setting”.
492
PLC Connection Guide
5. Select “PGU”.
6. Go to ”Device Configurator”.
493
PLC Connection Guide
7. Click ” Change Device Type” to select your PLC model.
8. Select RS232 (PGU) in Type and then right click mouse on Onboard
Communications and select ” Properties”.
494
PLC Connection Guide
9. Select “Yes” in Series S-Bus Port: Enabled.
10. Set parameters in S-Bus Mode and Timing then upload to PLC.
495
PLC Connection Guide
11. Go to Online Settings >> Open to select S-Bus for finishing the PLC settings.
Device Address:
Bit/Word Device type Format Range Memo
B Flag DDDD 0 ~ 8191
B Output DDDD 0 ~ 1023
B Input DDDD 0 ~ 1023
B Reg_Bit DDDDdd 0 ~ 1638331 dd: Bit no. (00~31)
DW Register DDDDD 0 ~ 16383
DW Counter DDDD 0 ~ 1599
DW Timer DDDD 0 ~ 1599
DW Reg_Float DDDDD 0 ~ 16383 support single float point
DW DBn DDDDDDDDD 0 ~ 536016383
496
PLC Connection Guide
Wiring Diagram:
The following represents the cable end connector.
SAIA PCD PGU Port
eMT3000 series
COM1 RS232 9P COM3 RS232 9P RS232 9P D-Sub Male
D-Sub Female D-Sub Female
2 RX 8 RX 3 TXD
3 TX 7 TX 2 RXD
5 GND 5 GND 5 GND
7 RTS
circuit
8 CTS
MT6050i/MT8050i
COM1 RS232 9P RS232 9P D-Sub Male
D-Sub Female
9 RX 3 TXD
6 TX 2 RXD
5 GND 5 GND
7 RTS
circuit
8 CTS
497
PLC Connection Guide
The following represents the cable end connector.
SAIA PCD1 Port #1 (Port #0) Terminal
eMT3000 series
COM1 RS485 2W COM3 RS485 2W SAIA PCD1 Port #1
9P D-Sub Male 9P D-Sub Male (Port #0) Terminal
1 RX- 6 Data- 11 (29)
2 RX+ 9 Data+ 12 (28)
5 GND 5 GND
MT6050i/MT8050i
COM1 RS485 2W COM3 RS485 2W SAIA PCD1 Port #1
9P D-Sub Female 9P D-Sub Female (Port #0) Terminal
1 RX- 7 Data- 11 (29)
2 RX+ 8 Data+ 12 (28)
5 GND 5 GND
Driver Version:
Version Date Description
V1.40 Jun/21/2012 DBn address types are added.
498
PLC Connection Guide
Website : http://www.saia-burgess.com/
HMI Setting:
Parameters Recommended Options Notes
PLC type SAIA S-BUS (Ethernet)
PLC I/F Ethernet
Port no. 5050
PLC sta. no. 0
PLC Setting:
499
PLC Connection Guide
Device Address:
Bit/Word Device type Format Range Memo
B Flag DDDD 0 ~ 8191
B Output DDDD 0 ~ 1023
B Input DDDD 0 ~ 1023
B Reg_Bit DDDDdd 0 ~ 1638331 dd: Bit no. (00 ~ 31)
DW Register DDDDD 0 ~ 16383
DW Counter DDDD 0 ~ 1599
DW Timer DDDD 0 ~ 1599
DW Reg_Float DDDDD 0 ~ 16383 support single float point
DW DBn DDDDDDDDD 0 ~ 536016383
500
PLC Connection Guide
Wiring Diagram:
Direct connect (crossover cable):
HMI RJ45 Male Wire Color PLC RJ45 Male
1 TX+ White/Orange 3 RX+
2 TX- Orange 6 RX-
3 RX+ White/Green 1 TX+
4 BD4+ Blue 4 BD4+
5 BD4- White/Blue 5 BD4-
6 RX- Green 2 TX-
7 BD3+ White/Brown 7 BD3+
8 BD3- Brown 8 BD3-
Through a hub:
HMI RJ45 Male Wire Color PLC RJ45 Male
1 TX+ White/Orange 1 TX+
2 TX- Orange 2 TX-
3 RX+ White/Green 3 RX+
4 BD4+ Blue 4 BD4+
5 BD4- White/Blue 5 BD4-
6 RX- Green 6 RX-
7 BD3+ White/Brown 7 BD3+
8 BD3- Brown 8 BD3-
Driver Version:
Version Date Description
V1.40 Jun/21/2012 DBn address types are added.
501
PLC Connection Guide
Samsung SPC-10
Supported Series: Samsung SPC-10
Website: http://www.samsungelectronics.com/factory_automation/controller/plc/
HMI Setting:
Parameters Recommended Options Notes
PLC type Samsung SPC-10
PLC I/F RS485 2W
Baud rate 9600
Data bits None
Parity 8
Stop bits 1
PLC sta. no. 192
Device Address:
Bit/Word Device type Format Range Memo
B R DDDDdd 0 ~ 999915
B K DDDDdd 0 ~ 999915
B M DDDDdd 0 ~ 999915
B F DDDDdd 0 ~ 999915
W W DDDD 0 ~ 9999
502
PLC Connection Guide
Wiring Diagram:
The following represents the cable end connector.
eMT3000 series
COM1 RS485 2W COM3 RS485 2W RS485 2W 8P Mini-DIN
9P D-Sub Male 9P D-Sub Male Male
1 RX- 6 Data- 6 TR-
2 RX+ 9 Data+ 7 TR+
5 GND 5 GND 5 GND
MT6050i/MT8050i
COM1 RS485 2W COM3 RS485 2W RS485 2W 8P Mini-DIN
9P D-Sub Female 9P D-Sub Female Male
1 RX- 7 Data- 6 TR-
2 RX+ 8 Data+ 7 TR+
5 GND 5 GND 5 GND
Driver Version:
Version Date Description
V1.00 May/19/2009
503
PLC Connection Guide
SCENE6 Controller
HMI Setting:
Parameters Recommended Options Notes
PLC type SCENE6 Controller
PLC I/F RS232
Baud rate 9600
Data bits 8
Parity None
Stop bits 2
PLC sta. no. 0
Device Address:
Bit/Word Device type Format Range Memo
W Word DD 0 ~ 99
Wiring Diagram:
The following represents the cable end connector.
eMT3000 series
COM1 RS232 9P COM3 RS232 9P RS232 Terminal
D-Sub Female D-Sub Female
2 RX 8 RX TD
3 TX 7 TX RD
5 GND 5 GND GND
504
PLC Connection Guide
MT6000/8000 series except MT6050i/MT8050i
COM1 RS232 9P COM2 RS232 9P COM3 RS232 9P RS232 Terminal
D-Sub Female D-Sub Female D-Sub Male
2 RX 6 RX 8 RX TD
3 TX 4 TX 7 TX RD
5 GND 5 GND 5 GND GND
MT6050i/MT8050i
COM1 RS232 9P RS232 Terminal
D-Sub Female
9 RX TD
6 TX RD
5 GND GND
Driver Version:
Version Date Description
V1.00 Aug/24/2009
505
PLC Connection Guide
Website: http://www.schleicher-electronic.com
HMI Setting:
Parameters Recommended Options Notes
PLC type Schleicher XCS 20C
PLC I/F RS232
Baud rate 38400
Data bits 8
Parity N
Stop bits 1
PLC sta. no. 0
Device Address:
Bit/Word Device type Format Range Memo
B IX DDDDDo 0 ~ 655357 Input %IX
B QX DDDDDo 0 ~ 655357 Output %QX
B MX DDDDDo 0 ~ 655357 %MX
W IW DDDDD 0 ~ 65535 %IW
W QW DDDDD 0 ~ 65535 %QW
W MW DDDDD 0 ~ 65535 %MW
DW ID DDDDD 0 ~ 65535 %ID
DW QD DDDDD 0 ~ 65535 %QD
DW MD DDDDD 0 ~ 65535 %WD
Word address must be even.
506
PLC Connection Guide
Wiring Diagram:
507
PLC Connection Guide
MT6050i/MT8050i
COM1 RS232 9P Schleicher XCS20
D-Sub Female RS232 9P D-Sub Male
9 RX 3 TD
6 TX 2 RD
5 GND 5 GND
Driver Version:
Version Date Description
V1.10 Feb/26/2010
508
PLC Connection Guide
HMI Setting:
Parameters Recommended Options Notes
PLC type Schleicher XCX 300
PLC I/F Ethernet RS232, RS422, Ethernet
Port no. 20547
PLC sta. no. 2
PLC Setting:
A variable must be created for HMI access.
Device Address:
Bit/Word Device type Format Range Memo
B IX DDDDDo 0 ~ 655357 Input %IX
B QX DDDDDo 0 ~ 655357 Output %QX
B MX DDDDDo 0 ~ 655357 %MX
W IW DDDDD 0 ~ 65535 %IW
W QW DDDDD 0 ~ 65535 %QW
W MW DDDDD 0 ~ 65535 %MW
DW ID DDDDD 0 ~ 65535 %ID
DW QD DDDDD 0 ~ 65535 %QD
DW MD DDDDD 0 ~ 65535 %WD
Word address must be even.
509
PLC Connection Guide
Wiring Diagram:
Direct connect (crossover cable):
HMI RJ45 Male Wire Color PLC RJ45 Male
1 TX+ White/Orange 3 RX+
2 TX- Orange 6 RX-
3 RX+ White/Green 1 TX+
4 BD4+ Blue 4 BD4+
5 BD4- White/Blue 5 BD4-
6 RX- Green 2 TX-
7 BD3+ White/Brown 7 BD3+
8 BD3- Brown 8 BD3-
Through a hub:
HMI RJ45 Male Wire Color PLC RJ45 Male
1 TX+ White/Orange 1 TX+
2 TX- Orange 2 TX-
3 RX+ White/Green 3 RX+
4 BD4+ Blue 4 BD4+
5 BD4- White/Blue 5 BD4-
6 RX- Green 6 RX-
7 BD3+ White/Brown 7 BD3+
8 BD3- Brown 8 BD3-
510
PLC Connection Guide
The following represents the cable end connector.
Schleicher XCX300 RS232 Port
eMT3000 series
COM1 RS232 9P COM3 RS232 9P RS232 9P D-Sub
D-Sub Female D-Sub Female Female
2 RX 8 RX 3 TXD
3 TX 7 TX 2 RXD
5 GND 5 GND 5 GND
MT6050i/MT8050i
COM1 RS232 9P RS232 9P D-Sub
D-Sub Female Female
9 RX 3 TXD
6 TX 2 RXD
5 GND 5 GND
511
PLC Connection Guide
The following represents the cable end connector.
Schleicher XCX300 RS485 4W Terminal
eMT3000 series
COM1 RS485 4W RS485 4W Terminal
9P D-Sub Male
1 RX- TX-
2 RX+ TX+
3 TX- RX-
4 TX+ RX+
5 GND GND
MT6050i/MT8050i
COM1 RS485 4W RS485 4W Terminal
9P D-Sub Female
1 RX- TX-
2 RX+ TX+
3 TX- RX-
4 TX+ RX+
5 GND GND
512
PLC Connection Guide
Driver Version:
Version Date Description
V1.00 Nov/30/2009 Driver released.
V1.10 Jun/28/2010 Support RS232, RS422 interface connection.
513
PLC Connection Guide
Website: http://www.schleicher-electronic.com
HMI Setting:
Parameters Recommended Options Notes
PLC type Schneider MODBUS RTU
PLC I/F RS485 RS232/RS485
Baud rate 9600 9600~115200
Data bits 8 7,8
Parity Even Even, Odd, None
Stop bits 1 1,2
PLC sta. no. 1 0-255
PLC Setting:
Communication mode Modbus RTU protocol
Device Address:
Bit/Word Device type Format Range Memo
B %M DDDDD 0 ~ 65535 Output bit
B 1x DDDDD 0 ~ 65535 Input bit (read only)
B 3x_Bit DDDDDdd 0 ~ 6553515 Input Register bit (read only)
B 4x_Bit DDDDDdd 0 ~ 6553515 Output Register bit
B 0x_multi_coils DDDDD 0 ~ 65535 Write multiple coils
W 3x DDDDD 0 ~ 65535 Input Register (read only)
W %MW DDDDD 0 ~ 65535 Output Register
DW 5x DDDDD 0 ~ 65535 4x double word swap
W 6x DDDDD 0 ~ 65535 4x single word write
514
PLC Connection Guide
Wiring Diagram:
The following represents the cable end connector.
RS232
eMT3000 series
COM1 RS232 9P COM3 RS232 9P RS232 9P D-Sub
D-Sub Female D-Sub Female Female
2 RX 8 RX 2 B-
3 TX 7 TX 1 A+
5 GND 5 GND 5 DTP
MT6050i/MT8050i
COM1 RS232 9P RS232 9P D-Sub
D-Sub Female Female
9 RX 3 TX
6 TX 2 RX
5 GND 5 GND
515
PLC Connection Guide
The following represents the cable end connector.
9P D-Sub to 8P Mini-DIN : RS485 2W
eMT3000 series
COM1 RS485 2W COM3 RS485 2W RS485 2W 8P Mini-DIN
9P D-Sub Male 9P D-Sub Male Male
1 RX- 6 Data- 2 B-
2 RX+ 9 Data+ 1 A+
5 GND 5 GND 5 DTP
circuit
7 GND
MT6050i/MT8050i
COM1 RS485 2W COM3 RS485 2W RS485 2W 8P Mini-DIN
9P D-Sub Female 9P D-Sub Female Male
1 RX- 7 Data- 2 B-
2 RX+ 8 Data+ 1 A+
5 GND 5 GND 5 DTP
circuit
7 GND
516
PLC Connection Guide
The following represents the cable end connector.
9P D-Sub to Terminal : RS485 2W
eMT3000 series
COM1 RS485 2W COM3 RS485 2W RS485 2W 3P Terminal
9P D-Sub Male 9P D-Sub Male
1 RX- 6 Data- B-
2 RX+ 9 Data+ A+
5 GND 5 GND GND
MT6050i/MT8050i
COM1 RS485 2W COM3 RS485 2W RS485 2W 3P Terminal
9P D-Sub Female 9P D-Sub Female
1 RX- 7 Data- B-
2 RX+ 8 Data+ A+
5 GND 5 GND GND
Driver Version:
Version Date Description
V1.30 Aug/26/2009
517
PLC Connection Guide
HMI Setting:
Parameters Recommended Options Notes
PLC type Schneider MODBUS TCP/IP
PLC I/F Ethernet
Port no. 502
PLC sta. no. 1 0~255
Device Address:
Bit/Word Device type Format Range Memo
B %M DDDDD 0 ~ 65535 Input bit
B 1x DDDDD 0 ~ 65535 Output bit
B 3x_Bit DDDDDdd 0 ~ 6553515 Input Register bit (read only)
B 4x_Bit DDDDDdd 0 ~ 6553515 Output Register bit
B 6x_Bit DDDDDdd 0 ~ 6553515 Output Register bit
B 0x_multi_coils DDDDD 0 ~ 65535 Write multiple coils
W 3x DDDDD 0 ~ 65535 Input Register
W %MW DDDDD 0 ~ 65535 Output Register
DW 5x DDDDD 0 ~ 65535 4x double word swap
W 6x DDDDD 0 ~ 65535 4x single word write
518
PLC Connection Guide
Wiring Diagram:
Direct connect (crossover cable):
HMI RJ45 Male Wire Color PLC RJ45 Male
1 TX+ White/Orange 3 RX+
2 TX- Orange 6 RX-
3 RX+ White/Green 1 TX+
4 BD4+ Blue 4 BD4+
5 BD4- White/Blue 5 BD4-
6 RX- Green 2 TX-
7 BD3+ White/Brown 7 BD3+
8 BD3- Brown 8 BD3-
Through a hub:
HMI RJ45 Male Wire Color PLC RJ45 Male
1 TX+ White/Orange 1 TX+
2 TX- Orange 2 TX-
3 RX+ White/Green 3 RX+
4 BD4+ Blue 4 BD4+
5 BD4- White/Blue 5 BD4-
6 RX- Green 6 RX-
7 BD3+ White/Brown 7 BD3+
8 BD3- Brown 8 BD3-
Driver Version:
Version Date Description
V1.40 Aug/27/2009
519
PLC Connection Guide
Schneider UniTelway
Supported Series: Modicon TSX Micro&Nano&Neza series PLC.
Website: http://www.modicon.com
HMI Setting:
Parameters Recommended Options Notes
PLC type Schneider UniTelway
PLC I/F RS485 2W RS232/RS485
Baud rate 19200 9600~115200
Data bits 8 7,8 Must set to 8 for this protocol
Parity Odd Even, Odd, None
Stop bits 1 1, 2
HMI sta. no. 5 1-8
PLC sta. no. 0 0-3
PLC Setting:
Communication mode UniTelWay protocol, set PLC as master
Device Address:
Bit/Word Device type Format Range Memo
B S DDDDD 0 ~ 32767 Internal relay
B M DDDDD 0 ~ 32767 Auxiliary relay
B MW.B DDDDDdd 0 ~ 3276715 Data register bit
W MW DDDDD 0 ~ 32767 Data register
520
PLC Connection Guide
Wiring Diagram:
The following represents the cable end connector.
TSX37-XX/TSX07-XX CPU : 9P D-Sub to 9P D-Sub
eMT3000 series
COM1 RS485 2W COM3 RS485 2W RS485 2W 8P Mini-DIN
9P D-Sub Male 9P D-Sub Male Male
1 RX- 6 Data- 2 D-
2 RX+ 9 Data+ 1 D+
5 GND 5 GND 7 GND
MT6050i/MT8050i
COM1 RS485 2W COM3 RS485 2W RS485 2W 8P Mini-DIN
9P D-Sub Female 9P D-Sub Female Male
1 RX- 7 Data- 2 D-
2 RX+ 8 Data+ 1 D+
5 GND 5 GND 7 GND
Driver Version:
Version Date Description
V1.30 Sep/24/2009
521
PLC Connection Guide
SEW Movilink
Supported Series: SEW Eurodrive series, model MOVITRAC-07 inverter, MovitracB.
Website: http://sg.sew-eurodrive.com/
HMI Setting:
Parameters Recommended Options Notes
PLC type SEW Movilink
PLC I/F RS485 2W
Baud rate 9600
Data bits 8
Parity Even
Stop bits 1
PLC sta. no. 0 0~255
Device Address:
Bit/Word Device type Format Range Memo
B INDEX_Bit DDDDDDDDdd 0 ~ 2552500031
W INDEX DDDDDDDD 0 ~ 25525000
● The MOVITRAC-07 doesn’t support Sub index(other series may support), please input
000.
● When input D and d, the correct format:Sub index 15, Index 8359, Format is
01508359.
Wiring Diagram:
The following represents the cable end connector.
eMT3000 series
COM1 RS485 2W COM3 RS485 2W Movitrac-07 RS485 2W
9P D-Sub Male 9P D-Sub Male
1 RX- 6 Data- D- (Green)
2 RX+ 9 Data+ D+ (Red)
5 GND 5 GND
522
PLC Connection Guide
MT6000/8000 series except MT6050i/MT8050i
COM1 RS485 2W COM3 RS485 2W Movitrac-07 RS485 2W
9P D-Sub Male 9P D-Sub Male
1 RX- 6 Data- D- (Green)
2 RX+ 9 Data+ D+ (Red)
5 GND 5 GND
MT6050i/MT8050i
COM1 RS485 2W COM3 RS485 2W Movitrac-07 RS485 2W
9P D-Sub Female 9P D-Sub Female
1 RX- 7 Data- D- (Green)
2 RX+ 8 Data+ D+ (Red)
5 GND 5 GND
Driver Version:
Version Date Description
V1.31 Jun/25/2010
523
PLC Connection Guide
HMI Setting:
Parameters Recommended Options Notes
PLC type SEW MOVITRAC LTE
PLC I/F RS-485 2W
Baud rate 115200
Data bits 8
Parity None
Stop bits 1
PLC sta. no. 1
Device Address:
Bit/Word Device type Format Range Memo
W P-1 D 0~1 Max. speed limit
W P-2 D 0~1 Min. speed limit
W P-3 D 0~1 Acceleration ramp time
W P-4 D 0~1 Deceleration ramp time
W P-5 D 0~1 Stop mode select
W P-6 D 0~1 Energy optimizer
W P-7 D 0~1 Motor rated voltage
W P-8 D 0~1 Motor rated current
W P-9 D 0~1 Motor rated frequency
W P-10 D 0~1 Motor rated speed
W P-11 D 0~1 Voltage boost
W P-12 D 0~1 Terminal / Keypad control
W P-13 D 0~1 Trip log
W P-14 D 0~1 Extended menu access code
W P-15 D 0~1 Digital input function set
W P-16 D 0~1 Analog input V / mA
W P-17 D 0~1 Output switching frequency
524
PLC Connection Guide
Bit/Word Device type Format Range Memo
W P-18 D 0~1 User relay output select
W P-19 D 0~1 User relay output limit
W P-20 D 0~1 Preset speed 1
W P-21 D 0~1 Preset speed 2
W P-22 D 0~1 Preset speed 3
W P-23 D 0~1 Preset speed 4
W P-24 D 0~1 Deceleration ramp time 2
W P-25 D 0~1 Analog output function select
W P-26 D 0~1 Skip frequency hysteris band
W P-27 D 0~1 Skip frequency
W P-28 D 0~1 V/F characteristic adjustment voltage
W P-29 D 0~1 V/F characteristic adjustment frequency
W P-30 D 0~1 Terminal mode restart function
W P-31 D 0~1 Keypad mode restart function
W P-32 D 0~1 DC injection enable / duration
W P-33 D 0~1 Spin start
W P-34 D 0~1 Brake chopper enable
W P-35 D 0~1 Analog input scaling factor
Comms address; SBus enable/baudrate
W P-36 D 0~1
select; Trip enable / delay
W P-37 D 0~1 Access code definition
W P-38 D 0~1 Parameter access lock
W P-39 D 0~1 Analog input off-set
W P-40 D 0~1 Display speed scaling factor
W P-00-01 D 0~1 Analog input 1 value
W P-00-02 D 0~1 Analog input 2 value
W P-00-03 D 0~1 Speed reference input
W P-00-04 D 0~1 Digital input status
W P-00-05 D 0~1 Reserved
W P-00-06 D 0~1 Reserved
W P-00-07 D 0~1 Applied motor voltage
W P-00-08 D 0~1 DC bus voltage log
W P-00-09 D 0~1 Heatsink temperature
W P-00-10 D 0~1 Hours run meter
W P-00-11 D 0~1 Run time since last trip (1)
W P-00-12 D 0~1 Run time since last trip (2)
W P-00-13 D 0~1 Run time since last disable
525
PLC Connection Guide
Bit/Word Device type Format Range Memo
W P-00-14 D 0~1 Reserved
W P-00-15 D 0~1 DC bus voltage log
W P-00-16 D 0~1 Thermistor temperature log
W P-00-17 D 0~1 Motor current
W P-00-18 D 0~1 Software ID,IO and motor control
W P-00-19 D 0~1 Drive serial number
W P-00-20 D 0~1 Drive identifier
P-00-01 ~ P-00-20 read only.
Wiring Diagram:
The following represents the cable end connector.
eMT3000 series
COM1 RS485 2W COM3 RS485 2W PLC RS485 2W 8P
9P D-Sub Male 9P D-Sub Male RJ45 Male
1 RX- 6 Data- 4-
2 RX+ 9 Data+ 5+
5 GND 5 GND
526
PLC Connection Guide
MT6050i/MT8050i
COM1 RS485 2W COM3 RS485 2W PLC RS485 2W 8P
9P D-Sub Female 9P D-Sub Female RJ45 Male
1 RX- 7 Data- 4-
2 RX+ 8 Data+ 5+
5 GND 5 GND
Driver Version:
Version Date Description
V1.00 May/19/2011 Driver released.
527
PLC Connection Guide
SHIMADEN MR13/FP93
Supported Series: MR13, FP93 devices
Website: http://www.shimaden.co.jp
HMI Setting:
Note:
Address 018C is a communication control register, only when it is set to 1 can this register
be allowed to write to other registers.
528
PLC Connection Guide
Device Address:
Bit/Word Device type Format Range Memo
W Channel 1 HHHH 0 ~ ffff Read/Write 1st Channel Register
W Channel 2 HHHH 0 ~ ffff Read/Write 2nd Channel Register
W Channel 3 HHHH 0 ~ ffff Read/Write 3rd Channel Register
Wiring Diagram:
The following represents the cable end connector.
eMT3000 series
COM1 RS485 2W COM3 RS485 2W MR13/FP93 RS485 2W
9P D-Sub Male 9P D-Sub Male Terminal
1 RX- 6 Data- 25 -
2 RX+ 9 Data+ 24 +
5 GND 5 GND 23 GND
MT6050i/MT8050i
COM1 RS485 2W COM3 RS485 2W MR13/FP93 RS485 2W
9P D-Sub Female 9P D-Sub Female Terminal
1 RX- 7 Data- 25 -
2 RX+ 8 Data+ 24 +
5 GND 5 GND 23 GND
529
PLC Connection Guide
MR13 Communication Parameter Settings
Data
Address Parameter Details of Parameter R /W
(hex)
0100 PV Value Within measuring range R
E_SV Execution SV
0101 Within setting range R
Value
OUT Control Output
0102 Within range 0.0~100.0% R
Value
0103 Reserved
0104 Action Flag (See detailed explanation below.) R
0105 Event Output Flag (See detailed explanation below.) R
0106 Reserved
0107 Reserved
0108 REM Value Within setting range R
0109 Reserved
010A Reserved
010B DI Input State Flag (See detailed explanation below.) R
Data
Address Parameter Details of Parameter R /W
(hex)
Refer to the measuring range code
0111 RANGE R
list.
0112 Reserved
DP Position of decimal point(0:Without
0113 R
Decimal Point decimal point 1:With decimal point)
PV Sc_L Lower
0114 For Linear Imput:-1999~9999 unit R
Limit
For Thermocouple, and RTD Input:
PV Sc_H Higher
0115 Measuring range to be displayed. R
Limit
Data
Address Parameter Details of Parameter R/W
(hex)
0120 E_PRG Program Action Flag R
0121 Reserved
530
PLC Connection Guide
0122 Reserved
The number of execution patterns
0123 E_PRT (When program is reset, R
value=7FFEH)
Execution step number
0124 E_STP (When program is reset, R
value=7FFEH)
Remaining time of execution step
0125 E_TIM (When program is reset, R
value=7FFEH)
Execution PID number
0126 E_PID (When program is reset, R
value=7FFEH)
Data
Address Parameter Details of Parameter R/W
(hex)
0184 AT Auto Tuning 0:No execution 1:Execution W
Data
Address Parameter Details of Parameter R/W
(hex)
SV Limt_L Lower
030A Within measuring range,
Limit
On condition that SV Limt_L<SV R/W
SV Limt_h Higher
030B Limt_H
Limit
531
PLC Connection Guide
0314 REM SC_L Within measuring range
R/W
On condition that REM SC_L≠REM
0315 REM SC_H
SC_H
0316 REM Bias Range: -1999~5000 unit R/W
0317 REM Filt Range: 0~100 seconds R/W
Data
Address Parameter Details of Parameter R/W
(hex)
CH2 & CH3 SV follow setting flag 1:
0320 SV Follow SW R/W
Follow 0:No
Follow type deviation SV set value:
0321 SV Follow R/W
1999~5000 unit
532
PLC Connection Guide
040B Prog MR1 PROG mode MR1 R/W
Range: -50.0~50.0%
PROG mode DF1
040C Prog DF1 R/W
Range: 1~999 unit
Prog O_Lmt_L1 PROG mode lower limit side output
040D R/W
limiter 1 Range: 0.0~99.9%
PROG mode higher limit side output
040E Prog O_Lmt_H1 limiter 1 R/W
Range: 0.1~100.0%
PROG mode target value function 1
040F Prog SF1 R/W
Range: OFF,0.01~1.00
PROG mode PB2
0410 Prog P2 R/W
Range: 0.0~999.9% (0.0:OFF)
PROG mode IT2
0411 Prog I2 R/W
Range: 0~6000 seconds (0.0:OFF)
PROG mode DT2
0412 Prog D2 R/W
Range: 0~3600 seconds (0.0:OFF)
PROG mode MR2
0413 Prog MR2 R/W
Range: -50.0~50.0%
PROG mode DF2
0414 Prog DF2 R/W
Range: 1~999 unit
PROG mode lower limit side output
0415 Prog O_Lmt_L2 R/W
limiter 2 Range: 0.0~99.9%
PROG mode higher limit side output
0416 Prog O_Lmt_H2 limiter 2 R/W
Range: 0.1~100.0%
PROG mode target value function 2
0417 Prog SF2 R/W
Range: OFF,0.01~1.00
PROG mode PB3
0418 Prog P3 R/W
Range: 0.0~999.9% (0.0:OFF)
Prog I3 PROG mode IT3
0419 R/W
Range: 0~6000 seconds (0.0:OFF)
PROG mode DT3
041A Prog D3 R/W
Range: 0~3600 seconds (0.0:OFF)
Prog MR3 PROG mode MR3
041B R/W
Range: -50.0~50.0%
PROG mode DF3
041C Prog DF3 R/W
Range: 1~999 unit
041D Prog O_Lmt_L3 PROG mode lower limit side output R/W
533
PLC Connection Guide
limiter 3 Range: 0.0~99.9%
PROG mode higher limit side output
Prog O_Lmt_H3
041E limiter 3 R/W
Range: 0.1~100.0%
PROG mode target value function 3
041F Prog SF3 R/W
Range: OFF,0.01~1.00
DI setting flag
0580 DI 0:NON 1:FLW 2:RUN 3:HLD R/W
4:ADV
● When Out_Cyc is written, writing data is adjusted to 0.5 sec as one unit.
● The write command lock by keylock is the same as the screen lock. (Refer to the
manual of the instrument.)
● If there is a change in EV1_CH,EV2_CH,EV3_CH, the related parameters are
initialized.
● For CH1, PFLW (window 1~30), CH_P (window1-29)display- - - -.The read value is:
7FFEH, To a write command, error(0BH)is returned.
Driver Version:
Version Date Description
V1.20 Apr/08/2011
539
PLC Connection Guide
SHJ-A
HMI Setting:
Parameters Recommended Options Notes
PLC type SHJ-A
PLC I/F RS485 2W
Baud rate 9600
Data bits 8
Parity None
Stop bits 1
PLC sta. no. 0
Device Address:
Bit/Word Device type Format Range Memo
W Word DD 0 ~ 89
Wiring Diagram:
The following represents the cable end connector.
eMT3000 series
COM1 RS485 2W COM3 RS485 2W RS485 terminal
9P D-Sub Male 9P D-Sub Male
1 RX- 6 Data- D-
2 RX+ 9 Data+ D+
5 GND 5 GND
540
PLC Connection Guide
MT6000/8000 series except MT6050i/MT8050i
COM1 RS485 2W COM3 RS485 2W RS485 terminal
9P D-Sub Male 9P D-Sub Male
1 RX- 6 Data- D-
2 RX+ 9 Data+ D+
5 GND 5 GND
MT6050i/MT8050i
COM1 RS485 2W COM3 RS485 2W RS485 terminal
9P D-Sub Female 9P D-Sub Female
1 RX- 7 Data- D-
2 RX+ 8 Data+ D+
5 GND 5 GND
Driver Version:
Version Date Description
V1.00 Oct/18/2011 Driver released.
541
PLC Connection Guide
Device Address:
Bit/Word Device type Format Range Memo
B I DDo 0 ~ 967 Input
B Q DDo 0 ~ 487 Output
B Logic result DDo 0 ~ 327 Logic Result
B RS-232 DDo 0 ~ 327 RS-232
Wiring Diagram:
The following represents the cable end connector.
eMT3000 series
COM1 RS232 9P COM3 RS232 9P FLEXI soft CPU0 Port0
D-Sub Female D-Sub Female 4P Mini-DIN Male
2 RX 8 RX 3 TX
3 TX 7 TX 2 RX
5 GND 5 GND 4 GND
542
PLC Connection Guide
MT6000/8000 series except MT6050i/MT8050i
COM1 RS232 9P COM2 RS232 9P COM3 RS232 9P FLEXI soft CPU0 Port0
D-Sub Female D-Sub Female D-Sub Male 4P Mini-DIN Male
2 RX 6 RX 8 RX 3 TX
3 TX 4 TX 7 TX 2 RX
5 GND 5 GND 5 GND 4 GND
MT6050i/MT8050i
COM1 RS232 9P FLEXI soft CPU0 Port0
D-Sub Female 4P Mini-DIN Male
9 RX 3 TX
6 TX 2 RX
5 GND 4 GND
Driver Version:
Version Date Description
V1.00 Apr/6/2011 Driver released.
543
PLC Connection Guide
Website: http://www.siemens.com/entry/cc/en/
HMI Setting:
Parameters Recommended Options Notes
PLC type Siemens S7/200 (Ethernet)
PLC I/F Ethernet
Port no. 102
PLC sta. no. 1 1~99
Local TSAP 1000 Must be greater than 1000
Remote TSAP 2100 Range:2000~2700
★ For TSAP settings please refer to PLC Setting below.
PLC Setting:
Siemens LOGO! multi connection setting requires LOGO! Soft Comfort software to set
PLC to identify the connected devices. The following introduces LOGO! Soft Comfort
settings.
544
PLC Connection Guide
Step 2. Right click on ”Ethernet Connections” and click ”Add connections” to add a
connection, up to eight connections are allowed.
Note: The value of Local TSAP and Remote TSAP must be set oppositely in EasyBuilder
for communication.
545
PLC Connection Guide
Device Address:
Bit/Word Device type Format Range Memo
B I DD 1~24 Read Only
B Q DD 1~16
B M DD 1~27
B V DDDDo 0~1023 VW_Bit
W AI D 1~8
W AQ D 1~2
W AM DD 1~16
W VW DDDD 0~1023 See Table 1 Address Mapping
546
PLC Connection Guide
Table 1 Address Mapping
I VW Q VW M VW AI VW AQ VW AM VW
I1 V923.0 Q1 V942.0 M1 V948.0 AI1 VW926 AQ1 VW944 AM1 VW952
I2 V923.1 Q2 V942.1 M2 V948.1 AI2 VW928 AQ2 VW946 AM2 VW954
I3 V923.2 Q3 V942.2 M3 V948.2 AI3 VW930 AM3 VW956
I4 V923.3 Q4 V942.3 M4 V948.3 AI4 VW932 AM4 VW958
I5 V923.4 Q5 V942.4 M5 V948.4 AI5 VW934 AM5 VW960
I6 V923.5 Q6 V942.5 M6 V948.5 AI6 VW936 AM6 VW962
I7 V923.6 Q7 V942.6 M7 V948.6 AI7 VW938 AM7 VW964
I8 V923.7 Q8 V942.7 M8 V948.7 AI8 VW940 AM8 VW966
M25 V951.0
M26 V951.1
M27 V951.2
547
PLC Connection Guide
Wiring Diagram:
Direct connect (crossover cable):
HMI RJ45 Male Wire Color PLC RJ45 Male
1 TX+ White/Orange 3 RX+
2 TX- Orange 6 RX-
3 RX+ White/Green 1 TX+
4 BD4+ Blue 4 BD4+
5 BD4- White/Blue 5 BD4-
6 RX- Green 2 TX-
7 BD3+ White/Brown 7 BD3+
8 BD3- Brown 8 BD3-
Through a hub:
HMI RJ45 Male Wire Color PLC RJ45 Male
1 TX+ White/Orange 1 TX+
2 TX- Orange 2 TX-
3 RX+ White/Green 3 RX+
4 BD4+ Blue 4 BD4+
5 BD4- White/Blue 5 BD4-
6 RX- Green 6 RX-
7 BD3+ White/Brown 7 BD3+
8 BD3- Brown 8 BD3-
Driver Version:
Version Date Description
V1.00 DEC/7/2011 Driver released.
548
PLC Connection Guide
HMI Setting:
Parameters Recommended Options Notes
SIEMENS S7-1200 Siemens S7-400
PLC type
(Ethernet) (Ethernet)
PLC I/F Ethernet Ethernet
Port no. 102 102
PLC sta. no. 2 2
Rack - 0
CPU slot - 1
PLC Setting:
1. In S7-1200 program software create PLC program and tag and then download to
PLC.
2. Select Go offline, EasyBuilder will connect to PLC and get tag data. In PLC type
select “SIEMENS S7-1200 (Ethernet)”.
549
PLC Connection Guide
3. Click “Settings…”, input PLC IP address.
4. Check the PLC that is not connected to any PC. Click “Get tag info…”.
550
PLC Connection Guide
5. If the software used is a version later than TIA Portal V11,SP2, a dialog of
FunctionBlock directory will be shown, users have to define the mapping from FB to
DB in this directory then click “Check OK”. The tag information will be gained and
a successful message is shown.
551
PLC Connection Guide
6. Create an object and click read address “Setting…”
552
PLC Connection Guide
Wiring Diagram:
Direct connect (crossover cable):
HMI RJ45 Male Wire Color PLC RJ45 Male
1 TX+ White/Orange 3 RX+
2 TX- Orange 6 RX-
3 RX+ White/Green 1 TX+
4 BD4+ Blue 4 BD4+
5 BD4- White/Blue 5 BD4-
6 RX- Green 2 TX-
7 BD3+ White/Brown 7 BD3+
8 BD3- Brown 8 BD3-
553
PLC Connection Guide
Through a hub:
HMI RJ45 Male Wire Color PLC RJ45 Male
1 TX+ White/Orange 1 TX+
2 TX- Orange 2 TX-
3 RX+ White/Green 3 RX+
4 BD4+ Blue 4 BD4+
5 BD4- White/Blue 5 BD4-
6 RX- Green 6 RX-
7 BD3+ White/Brown 7 BD3+
8 BD3- Brown 8 BD3-
Driver Version:
Version Date Description
V1.70 Oct/7/2011 Add data type: Byte,SInt,UInt,UDInt
V1.90 Apr/26/2012 Add data type: USInt
554
PLC Connection Guide
Siemens S7-200
Supported Series: Siemens S7-200 series PLC
(CPU212/214/215/216/221/222/224/226/226XM)
Website: http://www.siemens.com/entry/cc/en/
HMI Setting:
Parameters Recommended Options Notes
PLC type SIEMENS S7-200
PLC I/F RS485 2w RS485 2w
The HMI which has a sticker
Baud rate 9600 9600, 19200, 187.5K “MPI187.5” on the rear
cover supports 187.5K
Data bits 8 7,8
Parity Even Even, Odd, None
Stop bits 1 1, 2
PLC sta. no. 2 1 ~ 126
Turn around
5
delay (ms)
Reserved 1 30 ACK delay time
PLC Setting:
Communication mode Set station number to 2
Device Address:
Bit/Word Device type Format Range Memo
B I DDDDo 0 ~ 40957 Input (I)
B Q DDDDo 0 ~ 40957 Output (O)
B M DDDDo 0 ~ 40957 Bit Memory
B VW_Bit DDDDDo 0 ~ 102397 V Memory Bit Address
Byte VB DDDDD 0 ~ 10239
555
PLC Connection Guide
Bit/Word Device type Format Range Memo
W VW DDDDD 0 ~ 10239 V Memory
W VW_Odd DDDDD 0 ~ 10239 V Memory
DW VD DDDDD 0 ~ 10239 V Memory Double Word
DW VD_Odd DDDDD 0 ~ 10239 V Memory Double Word
W VW_String DDDDD 0 ~ 10239 String
W VW_String_Odd DDDDD 0 ~ 10239 String
DW VD_String DDDDD 0 ~ 10239 String
DW VD_String_Odd DDDDD 0 ~ 10239 String
Byte MB DDDDD 0 ~ 10239 Byte Memory
W MW DDDDD 0 ~ 10239 Word Memory
DW MD DDDDD 0 ~ 10239 Word Memory
W MW_Odd DDDDD 0 ~ 10239 Word Memory
W T DDD 0 ~ 127 Timer
W C DDD 0 ~ 127 Counter
Double word and floating point value must use VD device type.
Wiring Diagram:
The following represents the cable end connector.
eMT3000 series
COM1 RS485 2W COM3 RS485 2W RS485 2W 9P D-Sub
9P D-Sub Male 9P D-Sub Male Male
1 RX- 6 Data- 8 D-
2 RX+ 9 Data+ 3 D+
5 GND 5 GND 5 GND
556
PLC Connection Guide
MT6050i/MT8050i
COM1 RS485 2W COM3 RS485 2W RS485 2W 9P D-Sub
9P D-Sub Female 9P D-Sub Female Male
1 RX- 7 Data- 8 D-
2 RX+ 8 Data+ 3 D+
5 GND 5 GND 5 GND
Driver Version:
Version Date Description
V2.30 Aug/17/2009
V2.40 Nov/1/2011 Add device type : MD
557
PLC Connection Guide
Website: http://www.siemens.com/entry/cc/en/
HMI Setting:
Parameters Recommended Options Notes
PLC type SIEMENS S7-200 (Ethernet)
PLC I/F Ethernet
Port no. 102
PLC sta. no. 1 0-31
PLC Setting:
S7/200 Ethernet Multi-Connection Settings
Step 1: Launching the Ethernet Wizard
1. In the Micro/WIN main menu, click Tools / Ethernet Wizard.
558
PLC Connection Guide
2. Then, click Next.
559
PLC Connection Guide
2. To view the results of Read Modules, select the Ethernet module. Click Next.
560
PLC Connection Guide
2. Enter the number of desired available connections for this device. If 0 is entered,
the only connection available will be the PG mode. The image below shows there
are 4 connections for this module.
561
PLC Connection Guide
4. Connection1,Select This is a Server Connection....
Notice the Local TSAP automatically incremented to 11.00.
5. Upon completion of the settings above, set parameters in EasyBuilder. Set the
value of Local TSAP here to the value of Remote TSAP in Micro/WIN and vice
versa to realize multi-connection.
562
PLC Connection Guide
Device Address:
Bit/Word Device type Format Range Memo
B I DDDDo 0 ~ 40957 Input (I)
B Q DDDDo 0 ~ 40957 Output (O)
B M DDDDo 0 ~ 40957 Bit Memory
B VW_Bit DDDDDo 0 ~ 102397 V Memory Bit Address
W VW DDDDD 0 ~ 10239 V Memory
DW VD DDDDD 0 ~ 10239 V Memory Double Word
W VW_String DDDDD 0 ~ 10239 String
DW VD_String DDDDD 0 ~ 10239 String
DW MD DDDDD 0 ~ 10239 Word Memory
Double word and floating point value must use VD device type.
Wiring Diagram:
Direct connect (crossover cable):
HMI RJ45 Male Wire Color PLC RJ45 Male
1 TX+ White/Orange 3 RX+
2 TX- Orange 6 RX-
3 RX+ White/Green 1 TX+
4 BD4+ Blue 4 BD4+
5 BD4- White/Blue 5 BD4-
6 RX- Green 2 TX-
7 BD3+ White/Brown 7 BD3+
8 BD3- Brown 8 BD3-
563
PLC Connection Guide
Through a hub:
HMI RJ45 Male Wire Color PLC RJ45 Male
1 TX+ White/Orange 1 TX+
2 TX- Orange 2 TX-
3 RX+ White/Green 3 RX+
4 BD4+ Blue 4 BD4+
5 BD4- White/Blue 5 BD4-
6 RX- Green 6 RX-
7 BD3+ White/Brown 7 BD3+
8 BD3- Brown 8 BD3-
Driver Version:
Version Date Description
V1.20 Dec/30/2008
V1.40 Nov/15/2011 Add device type : MD
564
PLC Connection Guide
HMI Setting:
Parameters Recommended Options Notes
PLC type Siemens S7-200 (VD any address)
PLC I/F RS485 2w RS485 2w
The HMI which has a sticker
Baud rate 9600 9600, 19200, 187.5K “MPI187.5” on the rear
cover supports 187.5K
Data bits 8 7,8
Parity Even Even, Odd, None
Stop bits 1 1, 2
PLC sta. no. 2 1 ~ 126
Turn around
5
delay (ms)
Reserved 1 30 ACK delay time
PLC Setting:
Communication mode Set station number to 2
Device Address:
Bit/Word Device type Format Range Memo
B I DDDDo 0 ~ 40957 Input (I)
B Q DDDDo 0 ~ 40957 Output (O)
B M DDDDo 0 ~ 40957 Bit Memory
B VW_Bit DDDDDo 0 ~ 102397 V Memory Bit Address
W VW DDDDD 0 ~ 10239 V Memory
565
PLC Connection Guide
Wiring Diagram:
The following represents the cable end connector.
eMT3000 series
COM1 RS485 2W COM3 RS485 2W RS485 2W 9P D-Sub
9P D-Sub Male 9P D-Sub Male Male
1 RX- 6 Data- 8 D-
2 RX+ 9 Data+ 3 D+
5 GND 5 GND 5 GND
566
PLC Connection Guide
MT6050i/MT8050i
COM1 RS485 2W COM3 RS485 2W RS485 2W 9P D-Sub
9P D-Sub Female 9P D-Sub Female Male
1 RX- 7 Data- 8 D-
2 RX+ 8 Data+ 3 D+
5 GND 5 GND 5 GND
Driver Version:
Version Date Description
V1.20 Nov/16/2011 Add device type : MD
567
PLC Connection Guide
HMI Setting:
Parameters Recommended Options Notes
PLC type SIEMENS S7-200 PPI
PLC I/F RS485 2w RS485 2w
9600, 19200, Only MT6000/8000V2 support
Baud rate 9600
187.5K baud rate 187.5 K
Data bits 8 7,8
Parity Even Even, Odd, None
Stop bits 1 1, 2
Turn around
5
delay (ms)
ACK delay
30
time (ms)
PLC sta. no. 2 1 ~ 126
PLC Setting:
PLC setting PLC sta. no. can not be the same as HMI sta. no.
Device Address:
Bit/Word Device type Format Range Memo
B I DDDDo 0 ~ 40957 Input (I)
B Q DDDDo 0 ~ 40957 Output (O)
B M DDDDo 0 ~ 40957 Bit Memory
B VW_Bit DDDDDo 0 ~ 102397 V Memory Bit Address
Byte VB DDDDD 0 ~ 10239
W VW DDDDD 0 ~ 10239 V Memory
568
PLC Connection Guide
Bit/Word Device type Format Range Memo
W VW_Odd DDDDD 0 ~ 10239 V Memory
DW VD DDDDD 0 ~ 10239 V Memory Double Word
DW VD_Odd DDDDD 0 ~ 10239 V Memory Double Word
W VW_String DDDDD 0 ~ 10239 String
W VW_String_Odd DDDDD 0 ~ 10239 String
DW VD_String DDDDD 0 ~ 10239 String
DW VD_String_Odd DDDDD 0 ~ 10239 String
Byte MB DDDDD 0 ~ 10239 Byte Memory
W MW DDDDD 0 ~ 10239 Word Memory
W MW_Odd DDDDD 0 ~ 10239 Word Memory
W T DDD 0 ~ 127 Timer
W C DDD 0 ~ 127 Counter
DW MD DDDDD 0 ~ 10239 Word Memory
Double Word and floating point value must use VD device type.
569
PLC Connection Guide
IN EasyBuilder COM Port Settings, two important parameters must be set:
570
PLC Connection Guide
Note:
HMI sta. no. can not be the same as PLC sta. no.
Highly recommended that HMI sta. no. starts from 0 and go on sequentially for the
effectiveness of operation.
Available for EasyBuilder V4.50 and later.
Wiring Diagram:
The following represents the cable end connector.
eMT3000 series
COM1 RS485 2W COM3 RS485 2W RS485 2W 9P D-Sub
9P D-Sub Male 9P D-Sub Male Male
1 RX- 6 Data- 8 D-
2 RX+ 9 Data+ 3 D+
5 GND 5 GND 5 GND
MT6050i/MT8050i
COM1 RS485 2W COM3 RS485 2W RS485 2W 9P D-Sub
9P D-Sub Female 9P D-Sub Female Male
1 RX- 7 Data- 8 D-
2 RX+ 8 Data+ 3 D+
5 GND 5 GND 5 GND
571
PLC Connection Guide
Driver Version
Version Date Description
V1.00 Aug/15/2011 Driver released.
V1.10 Nov/17/2011 Add device type : MD
572
PLC Connection Guide
Siemens S7-300
Supported Series: Siemens S7-300 series PLC
Website: http://www.siemens.com/entry/cc/en/
HMI Setting:
Parameters Recommended Options Notes
PLC type SIEMENS S7-300
PLC I/F RS232
Must be same as the PLC setting.
The HMI which has a sticker
Baud rate 19200 9600~187.5K
MPI187.5 on the rear cover
supports 187.5K.
Data bits 8
Parity Odd
Stop bits 1
PLC sta. no. 2 Must be same as the PLC setting.
Device Address:
Bit/Word Device type Format Range Memo
B I DDDDo 0 ~ 40957 Input (I)
B Q DDDDo 0 ~ 40957 Output (O)
B M DDDDo 0 ~ 40957 Bit Memory
B DBnBit FFFFDDDDo 0 ~ 409681927 Data Register Bit
DB0Bit ~
B DDDDo 0 ~ 81927
DB99Bit
W IW DDDD 0 ~ 4095 Input (I)
W QW DDDD 0 ~ 4095 Output (O)
W MW DDDD 0 ~ 4095 Bit Memory
DW MD DDDD 0 ~ 4094
Byte MB DDDD 0 ~ 4095 Bit Memory Byte
Byte DBBn FFFFDDDD 0 ~ 40968192 Data Register Byte
Data Register
W DBn FFFFDDDD 0 ~ 40968192
(must be even)
573
PLC Connection Guide
Bit/Word Device type Format Range Memo
Data Register Double Word
DW DBDn FFFFDDDD 0 ~ 40968192
(must be multiple of 4)
Data Register Double Word
W DBn_String FFFFDDDD 0 ~ 40968192
(must be multiple of 4)
Data Register Double Word
DW DBDn_String FFFFDDDD 0 ~ 40968192
(must be multiple of 4)
Data Register
W DB0-DB99 DDDD 0 ~ 8192
(must be even)
* Double word and floating point value must use DBDn device type.
574
PLC Connection Guide
b、 Click Export to export the edited file and click Save.
575
PLC Connection Guide
c、 Select Sources as storage path, specify the file name then click OK.
576
PLC Connection Guide
e、 Under Sources there will be names of the saved files, select Export Source
to build *.AWL file.
577
PLC Connection Guide
Wiring Diagram:
The following represents the cable end connector.
Siemens S7-300 PC Adapter : 9P D-Sub to 9P D-Sub:
eMT3000 series
COM1 RS232 9P COM3 RS232 9P RS232 9P D-Sub Male
D-Sub Female D-Sub Female
2 RX 8 RX 3 TXD
3 TX 7 TX 2 RXD
5 GND 5 GND 5 GND
7 RTS
circuit
8 CTS
MT6050i/MT8050i
COM1 RS232 9P RS232 9P D-Sub Male
D-Sub Female
9 RX 3 TXD
6 TX 2 RXD
5 GND 5 GND
7 RTS
circuit
8 CTS
578
PLC Connection Guide
The following represents the cable end connector.
Systeme Helmholz SSW7-TS : 9P D-Sub to 9P D-Sub
eMT3000 series
COM1 RS232 9P COM3 RS232 9P RS232 9P D-Sub Male
D-Sub Female D-Sub Female
2 RX 8 RX 3 TXD
3 TX 7 TX 2 RXD
5 GND 5 GND 5 GND
7 RTS
circuit
8 CTS
4 DTR
circuit
6 DSR
579
PLC Connection Guide
MT6050i/MT8050i
COM1 RS232 9P RS232 9P D-Sub Male
D-Sub Female
9 RX 3 TXD
6 TX 2 RXD
5 GND 5 GND
7 RTS
circuit
8 CTS
4 DTR
circuit
6 DSR
Driver Version:
Version Date Description
V3.10 May/24/2011 Added registers: MB & DBBn.
580
PLC Connection Guide
HMI Setting:
Parameters Recommended Options Notes
PLC type SIEMENS S7-300 MPI
PLC I/F RS-485 2W
Only HMI with a sticker “MPI 187.5K”
Baud rate 187.5K on the rear cover supports MPI
communication.
Data bits 8
Parity Even
Stop bits 1
PLC sta. no. 2 2 ~ 31
Device Address:
Bit/Word Device type Format Range Memo
B I DDDDo 0 ~ 40957 Input (I)
B Q DDDDo 0 ~ 40957 Output (O)
B M DDDDo 0 ~ 40957 Bit Memory
B DBnBit FFFFDDDDo 0 ~ 409699997 Data Register Bit
B DB0Bit ~ DDDDDo 0 ~ 655327 Data Register Bit
W DB99Bit
IW DDDD 0 ~ 4095 Input (I)
W QW DDDD 0 ~ 4095 Output (O)
W MW DDDD 0 ~ 4095 Bit Memory
DW MD DDDD 0 ~ 4094
Byte MB DDDD 0 ~ 4095 Bit Memory Byte
Byte DBBn FFFFDDDD 0 ~ 40969999 Data Register
581
PLC Connection Guide
Bit/Word Device type Format Range Memo
582
PLC Connection Guide
For the effectiveness of communication, users may set PLC device in STEP 7 as shown
below. In Properties MPI / Network Settings, set Highest MPI address to the number
closest to the actual device station number.
Note:
■ HMI sta. no. can not be the same as PLC sta. no.
■ Highly recommended that the device station numbers start from 0 sequentially and
correctly set [Max. station no. (MPI network)].
■ Available for EasyBuilder V4.50 and later.
583
PLC Connection Guide
1. Building *.dif File
a、 In “Symbols” create user-defined tag.
584
PLC Connection Guide
2. Building *.AWF File
a、 In Blocks create items as shown below:
c、 Select Sources as storage path, specify the file name then click OK.
585
PLC Connection Guide
d、 Select the objects to be exported then click OK.
e、 Under Sources there will be names of the saved files, select Export
Source to build *.AWL file.
586
PLC Connection Guide
The generated *.dif and *.AWL files can be imported in EasyBuilder8000/EasyBuilderPro
System Parameter Settings, by clicking Import Tag.
587
PLC Connection Guide
Wiring Diagram:
The following represents the cable end connector.
S7-200 PPI , S7-300 MPI :RS485 2W
eMT3000 series
COM1 RS485 2W COM3 RS485 2W RS485 2W 9P D-Sub
9P D-Sub Male 9P D-Sub Male Male
1 RX- 6 Data- 8 D-
2 RX+ 9 Data+ 3 D+
5 GND 5 GND 5 GND
MT6050i/MT8050i
COM1 RS485 2W COM3 RS485 2W RS485 2W 9P D-Sub
9P D-Sub Female 9P D-Sub Female Male
1 RX- 7 Data- 8 D-
2 RX+ 8 Data+ 3 D+
5 GND 5 GND 5 GND
Driver Version:
Version Date Description
V1.90 May/26/2011 Added registers: MB & DBBn
i Series HMI support Multi HMIs-Multi PLCs
V2.00 Aug/19d/2011
communication.
588
PLC Connection Guide
Supported Series: Siemens S7-300 Ethernet Series PLC, Ethernet module CP-343-1,
CPU315-2 PN/DP, CPU317-2 PN/DP, CPU319-3 PN/DP, and ET200S.
Website: http://www.siemens.com/entry/cc/en/
HMI Setting:
Parameters Recommended Options Notes
PLC type SIEMENS S7-300/ET200S (Ethernet)
PLC I/F Ethernet
Port no. 102
PLC sta. no. 1 0-31
Device Address:
Bit/Word Device type Format Range Memo
B I DDDDo 0 ~ 40957 Input (I)
B Q DDDDo 0 ~ 40957 Output (O)
B M DDDDo 0 ~ 40957 Bit Memory
B DBnBit FFFFDDDDo 0 ~ 409699997
B DB0Bit-DB99Bit DDDDDo 0 ~ 655327 Data Register Bit
W IW DDDD 0 ~ 4095 Input (I)
W QW DDDD 0 ~ 4095 Output (O)
W MW DDDD 0 ~ 4095 Bit Memory
DW MD DDDD 0 ~ 4094 Bit Memory Double Word
Bit Memory Double Word
DW MD_Anyaddr DDDD 0 ~ 4094
(must be even)
Data Register
W DBn FFFFDDDD 0 ~ 40969999
(must be even)
Data Register Double Word
DW DBDn FFFFDDDD 0 ~ 40969999
(must be multiple of 4)
Data Register Double Word
DW DBDn_Anyaddr FFFFDDDD 0 ~ 40969999
(must be even)
W DBn_String FFFFDDDD 0 ~ 40969999
DW DBDn_String FFFFDDDD 0 ~ 40969999
W DB0 ~ DB99 DDDDD 0 ~ 65532 Data Register
589
PLC Connection Guide
Bit/Word Device type Format Range Memo
(must be even)
Byte MB DDDD 0 ~ 4095 Bit Memory Byte
Byte DBBn FFFFDDDD 0 ~ 40969999 Data Register Byte
Double word and floating point value must use DBDn device type.
590
PLC Connection Guide
b、 Click Export to export the edited file and click Save.
591
PLC Connection Guide
c、 Select Sources as storage path, specify the file name then click OK.
592
PLC Connection Guide
e、 Under Sources there will be names of the saved files, select Export Source
to build *.AWL file.
593
PLC Connection Guide
Wiring Diagram:
Direct connect (crossover cable):
HMI RJ45 Male Wire Color PLC RJ45 Male
1 TX+ White/Orange 3 RX+
2 TX- Orange 6 RX-
3 RX+ White/Green 1 TX+
4 BD4+ Blue 4 BD4+
5 BD4- White/Blue 5 BD4-
6 RX- Green 2 TX-
7 BD3+ White/Brown 7 BD3+
8 BD3- Brown 8 BD3-
Through a hub:
HMI RJ45 Male Wire Color PLC RJ45 Male
1 TX+ White/Orange 1 TX+
2 TX- Orange 2 TX-
3 RX+ White/Green 3 RX+
4 BD4+ Blue 4 BD4+
5 BD4- White/Blue 5 BD4-
6 RX- Green 6 RX-
7 BD3+ White/Brown 7 BD3+
8 BD3- Brown 8 BD3-
Driver Version:
Version Date Description
V2.10 May/21/2011 Added registers: MB & DBBn.
V2.20 Apr/25/2012 Added registers: MD_Anyaddr & DBDn_Anyaddr.
594
PLC Connection Guide
HMI Setting:
Parameters Recommended Options Notes
PLC type Siemens S7-400 (Ethernet)
PLC I/F Ethernet
Port no. 102
Link type PG PC, OP
Rack 0 0-7
To Connect with S7-1200,slot 1
CPU slot 3 1-31
must be selected.
PLC sta. no. 0 0-31
Device Address:
Bit/Word Device type Format Range Memo
B I DDDDo 0 ~ 40957 Input (I)
B Q DDDDo 0 ~ 40957 Output (O)
B M DDDDo 0 ~ 40957 Bit Memory
B DBnBit FFFFDDDDo 0 ~ 409699997
B DB0Bit-DB99Bit DDDDDo 0 ~ 655327 Data Register Bit
W IW DDDD 0 ~ 4095 Input (I)
W QW DDDD 0 ~ 4095 Output (O)
W MW DDDD 0 ~ 4095 Bit Memory
DW MD DDDD 0 ~ 4094
Data Register
W DBn FFFFDDDD 0 ~ 40969999
(must be even)
Data Register Double Word
DW DBDn FFFFDDDD 0 ~ 40969999
(must be multiple of 4)
W DBn_String FFFFDDDD 0 ~ 40969999
DW DBDn_String FFFFDDDD 0 ~ 40969999
Data Register
W DB0 ~ DB99 DDDDD 0 ~ 65532
(must be even)
Byte MB DDDD 0 ~ 4095 Bit Memory Byte
Byte DBBn FFFFDDDD 0 ~ 40969999 Data Register Byte
* Double word and floating point value must use DBDn device type.
595
PLC Connection Guide
Wiring Diagram:
Direct connect (crossover cable):
HMI RJ45 Male Wire Color PLC RJ45 Male
1 TX+ White/Orange 3 RX+
2 TX- Orange 6 RX-
3 RX+ White/Green 1 TX+
4 BD4+ Blue 4 BD4+
5 BD4- White/Blue 5 BD4-
6 RX- Green 2 TX-
7 BD3+ White/Brown 7 BD3+
8 BD3- Brown 8 BD3-
Through a hub:
HMI RJ45 Male Wire Color PLC RJ45 Male
1 TX+ White/Orange 1 TX+
2 TX- Orange 2 TX-
3 RX+ White/Green 3 RX+
4 BD4+ Blue 4 BD4+
5 BD4- White/Blue 5 BD4-
6 RX- Green 6 RX-
7 BD3+ White/Brown 7 BD3+
8 BD3- Brown 8 BD3-
596
PLC Connection Guide
4. Press [Settings].
597
PLC Connection Guide
5. Set S7-400 IP, Port no., Link type, Rack and CPU slot. (must match PLC settings)
598
PLC Connection Guide
599
PLC Connection Guide
2. Building *.AWF File
a、 In Blocks create items as shown below:
c、 Select Sources as storage path, specify the file name then click OK.
600
PLC Connection Guide
d、 Select the objects to be exported then click OK.
e、 Under Sources there will be names of the saved files, select Export Source
to build *.AWL file.
601
PLC Connection Guide
The generated *.dif and *.AWL files can be imported in EasyBuilder8000/EasyBuilderPro
System Parameter Settings, by clicking Import Tag.
Driver Version:
Version Date Description
V1.40 May/25/2011 Added registers: MB & DBBn
602
PLC Connection Guide
Siemens TI505
Supported Series: SIMATIC TI505 Series PLCs: TI520, TI525, TI530, TI535, TI545, TI555,
TI560, TI565, TI575. Use NITP protocol in a point-to-point, single master, single slave
format.
Website: http://www.siemens.com/entry/cc/en/
HMI Setting:
Parameters Recommended Options Notes
PLC type SIMATIC TI505 NITP protocol
PLC I/F RS232 RS232,
Baud rate 19200 RS485(4W)
19200
Data bits 7 7
Parity Odd Odd
Stop bits 1 1
PLC sta. no. 0 Does not apply
Device Address:
Bit/Word Device type Format Range Memo
B CR DDDDD 1 ~ 65535 Internal Relay
B X DDDDD 1 ~ 65535 Discrete Input Coils
B Y DDDDD 1 ~ 65535 Discrete Output Coils
W V DDDDD 1 ~ 65535 User Data Registers
W STW DDDDD 1 ~ 65535 Status Word Registers
W TCP DDDDD 1 ~ 65535 Timer/Counter Preset Values
W TCC DDDDD 1 ~ 65535 Timer/Counter Current Values
W WX DDDDD 1 ~ 65535 Word Discrete Inputs
W WY DDDDD 1 ~ 65535 Word Discrete Outputs
603
PLC Connection Guide
Wiring Diagram:
The following represents the cable end connector.
SIMATIC TI505 RS232 : 9P D-Sub to 25P D-Sub
eMT3000 series
COM1 RS232 9P COM3 RS232 9P RS232 25P D-Sub Male
D-Sub Female D-Sub Female
2 RX 8 RX 2 TXD
3 TX 7 TX 3 RXD
5 GND 5 GND 7 GND
4 RTS
circuit
5 CTS
6 DSR
8 DCD circuit
20 DTR
604
PLC Connection Guide
MT6050i/MT8050i
COM1 RS232 9P RS232 25P D-Sub Male
D-Sub Female
9 RX 2 TXD
6 TX 3 RXD
5 GND 7 GND
4 RTS
circuit
5 CTS
6 DSR
8 DCD circuit
20 DTR
605
PLC Connection Guide
MT6000/8000 series except MT6050i/MT8050i
COM1 RS232 9P COM2 RS232 9P COM3 RS232 9P RS232 9P D-Sub Male
D-Sub Female D-Sub Female D-Sub Male
2 RX 6 RX 8 RX 3 TXD
3 TX 4 TX 7 TX 2 RXD
5 GND 5 GND 5 GND 5 GND
7 RTS 7 RTS
8 CTS 8 CTS
1 DCD 1 DCD
4 DTR 4 DTR
6 DSR
MT6050i/MT8050i
COM1 RS232 9P RS232 9P D-Sub Male
D-Sub Female
9 RX 3 TXD
6 TX 2 RXD
5 GND 5 GND
7 RTS
circuit
8 CTS
1 DCD
4 DTR circuit
6 DSR
606
PLC Connection Guide
The following represents the cable end connector.
SIMATIC TI505 RS485 4W : 9P D-Sub to 9P D-Sub
eMT3000 series
COM1 RS485 4W RS485 4W 9P D-Sub
9P D-Sub Male Male
1 RX- 7 DO (-)
2 RX+ 1 DO (+)
3 TX- 8 DI (-)
4 TX+ 5 DI (+)
5 GND 6 GND
MT6050i/MT8050i
COM1 RS485 4W RS485 4W 9P D-Sub
9P D-Sub Female Male
1 RX- 7 DO (-)
2 RX+ 1 DO (+)
3 TX- 8 DI (-)
4 TX+ 5 DI (+)
5 GND 6 GND
607
PLC Connection Guide
Driver Version:
Version Date Description
V1.10 Apr/22/2009
608
PLC Connection Guide
Siemens TI565/C400
Website: http://www.siemens.com/entry/cc/en/
HMI Setting:
Parameters Recommended Options Notes
PLC type SIMATIC TI565/C400
PLC I/F RS232 RS232, RS485(4W)
Baud rate 19200 19200
Data bits 7 7
Parity Odd Odd
Stop bits 1 1
PLC sta. no. 0 Does not apply
Device Address:
Bit/Word Device type Format Range Memo
B CR DDDDD 1 ~ 65535 Internal Relay
B X DDDDD 1 ~ 65535 Discrete Input Coils
B Y DDDDD 1 ~ 65535 Discrete Output Coils
B V_Bit DDDDDdd 100 ~ 6553515 User Data Registers
W V DDDDD 1 ~ 65535 User Data Registers
W STW DDDDD 1 ~ 65535 Status Word Registers
W TCP DDDDD 1 ~ 65535 Timer/Counter Preset Values
W TCC DDDDD 1 ~ 65535 Timer/Counter Current Values
W WX DDDDD 1 ~ 65535 Word Discrete Inputs
W WY DDDDD 1 ~ 65535 Word Discrete Outputs
609
PLC Connection Guide
Wiring Diagram:
The following represents the cable end connector.
9P D-Sub to 25P D-Sub: RS232
eMT3000 series
COM1 RS232 9P COM3 RS232 9P RS232 25P D-Sub Male
D-Sub Female D-Sub Female
2 RX 8 RX 2 TXD
3 TX 7 TX 3 RXD
5 GND 5 GND 7 GND
4 RTS
circuit
5 CTS
6 DSR
8 DCD circuit
20 DTR
610
PLC Connection Guide
MT6050i/MT8050i
COM1 RS232 9P RS232 25P D-Sub Male
D-Sub Female
9 RX 2 TXD
6 TX 3 RXD
5 GND 7 GND
4 RTS
circuit
5 CTS
6 DSR
8 DCD circuit
20 DTR
611
PLC Connection Guide
MT6000/8000 series except MT6050i/MT8050i
COM1 RS232 9P COM2 RS232 9P COM3 RS232 9P RS232 9P D-Sub Male
D-Sub Female D-Sub Female D-Sub Male
2 RX 6 RX 8 RX 3 TXD
3 TX 4 TX 7 TX 2 RXD
5 GND 5 GND 5 GND 5 GND
7 RTS
circuit
8 CTS
1 DCD
4 DTR circuit
6 DSR
MT6050i/MT8050i
COM1 RS232 9P RS232 9P D-Sub Male
D-Sub Female
9 RX 3 TXD
6 TX 2 RXD
5 GND 5 GND
7 RTS
circuit
8 CTS
1 DCD
4 DTR circuit
6 DSR
612
PLC Connection Guide
The following represents the cable end connector.
9P D-Sub to 9P D-Sub: RS-485 4W
eMT3000 series
COM1 RS485 4W RS485 4W 9P D-Sub
9P D-Sub Male Male
1 RX- 7 DO (-)
2 RX+ 1 DO (+)
3 TX- 8 DI (-)
4 TX+ 5 DI (+)
5 GND 6 GND
MT6050i/MT8050i
COM1 RS485 4W RS485 4W 9P D-Sub
9P D-Sub Female Male
1 RX- 7 DO (-)
2 RX+ 1 DO (+)
3 TX- 8 DI (-)
4 TX+ 5 DI (+)
5 GND 6 GND
613
PLC Connection Guide
Driver Version:
Version Date Description
V1.00 Aug/31/2011 Driver released.
614
PLC Connection Guide
HMI Setting:
Parameters Recommended Options Notes
PLC type SSTC SSD Series
PLC I/F RS232 RS232/RS485 2W
Baud rate 19200 9600~115200
Data bits 8 8
Parity None None,Odd
Stop bits 1 1
PLC sta. no. 1 1~32
Device Address:
Bit/Word Device Type Format Range Memo
W ID DDDDD 0 ~ 99999
W ID_35000 DDDDD 35000 String
W ID_35001 DDDDD 35001 String
ID Address List:
ID No. Data Length Data Type Write / Read Decimal Place*
1 BYT2 UDEC Yes/Yes 1
30 BYT4 HEX No/Yes Hex
36 BYT4 SDEC Yes/Yes 0.0001
38 BYT4 UDEC Yes/Yes 0.0001
39 BYT4 SDEC Yes/Yes 0.0001
40 BYT4 SDEC No/Yes 0.0001
41 BYT4 SDEC No/Yes 0.0001
43 BYT2 UDEC Yes/Yes 1
47 BYT4 SDEC Yes/Yes 1
48 BYT4 SDEC Yes/Yes 1
49 BYT4 SDEC Yes/Yes 1
50 BYT4 SDEC Yes/Yes 1
615
PLC Connection Guide
ID No. Data Length Data Type Write / Read Decimal Place*
51 BYT4 SDEC Yes/Yes 1
53 BYT4 SDEC Yes/Yes 1
55 BYT2 UDEC Yes/Yes 1
57 BYT4 UDEC Yes/Yes 1
80 BYT2 SDEC Yes/Yes 0.1
82 BYT2 UDEC Yes/Yes 0.1
83 BYT2 SDEC Yes/Yes 0.1
84 BYT2 SDEC No/Yes 0.1
85 BYT2 UDEC Yes/Yes 1
100 BYT2 UDEC Yes/Yes 1
101 BYT2 UDEC Yes/Yes 0.1
102 BYT2 UDEC Yes/Yes 0.1
103 BYT4 SDEC Yes/Yes 1
104 BYT2 UDEC Yes/Yes 1
109 BYT4 UDEC Yes/Yes 0.001
110 BYT4 UDEC No/Yes 0.001
111 BYT4 UDEC Yes/Yes 0.001
112 BYT4 UDEC No/Yes 0.001
113 BYT4 UDEC Yes/Yes 0.0001
116 BYT4 UDEC Yes/Yes 1
124 BYT4 SDEC Yes/Yes 0.0001
125 BYT4 SDEC Yes/Yes 0.0001
126 BYT2 SDEC Yes/Yes 0.1
136 BYT4 SDEC Yes/Yes 1
137 BYT4 SDEC Yes/Yes 1
147 BYT2 HEX Yes/Yes Hex
150 BYT4 SDEC Yes/Yes 1
153 BYT4 SDEC Yes/Yes 1
154 BUT2 HEX Yes/Yes Hex
157 BYT4 SDEC Yes/Yes 0.0001
159 BYT4 UDEC Yes/Yes 1
173 BYT4 SDEC Yes/Yes 1
193 BYT2 UDEC Yes/Yes 1
209 BYT4 UDEC Yes/Yes 0.0001
616
PLC Connection Guide
ID No. Data Length Data Type Write / Read Decimal Place*
210 BYT4 UDEC Yes/Yes 0.0001
211 BYT2 UDEC Yes/Yes 0.1
212 BYT2 UDEC Yes/Yes 0.1
222 BYT4 SDEC Yes/Yes 1
225 BYT2 HEX Yes/Yes Hex
228 BYT4 UDEC Yes/Yes 1
230 BYT4 UDEC Yes/Yes 1
268 BYT4 UDEC Yes/Yes 1
278 BYT4 UDEC Yes/Yes 1
32768 BYT2 UDEC Yes/Yes 0.1
32769 BYT4 UDEC Yes/Yes 0.001
32770 BYT4 UDEC Yes/Yes 0.001
32771 BYT2 UDEC Yes/Yes 0.1
32772 BYT4 UDEC Yes/Yes 0.0001
32773 BYT4 HEX Yes/Yes Hex
32774 BYT2 UDEC Yes/Yes 0.1
32775 BYT2 UDEC Yes/Yes 1
32776 BYT2 UDEC Yes/Yes 1
32777 BYT2 SDEC Yes/Yes 0.1
32778 BYT4 SDEC Yes/Yes 0.0001
32779 BYT4 SDEC Yes/Yes 0.0001
32780 BYT4 UDEC Yes/Yes 0.1
32781 BYT4 UDEC Yes/Yes 0.1
32782 BYT4 UDEC Yes/Yes 0.1
32783 BYT2 UDEC Yes/Yes 1
32784 BYT4 SDEC Yes/Yes 1
32785 BYT2 UDEC Yes/Yes 1
32786 BYT4 SDEC Yes/Yes 1
32787 BYT4 UDEC Yes/Yes 1
32788 BYT4 SDEC Yes/Yes 1
32789 BYT4 UDEC Yes/Yes 1
32790 BYT4 SDEC Yes/Yes 1
32791 BYT4 UDEC Yes/Yes 1
32792 BYT4 SDEC Yes/Yes 1
617
PLC Connection Guide
ID No. Data Length Data Type Write / Read Decimal Place*
32793 BYT4 UDEC Yes/Yes 1
32794 BYT4 SDEC Yes/Yes 1
32797 BYT4 HEX No/Yes Hex
32798 BYT4 HEX No/No Hex
32799 BYT4 HEX No/No Hex
32800 BYT4 HEX Yes/Yes Hex
32801 BYT4 HEX Yes/Yes Hex
32802 BYT4 HEX Yes/Yes Hex
32803 BYT4 HEX Yes/Yes Hex
32804 BYT4 HEX Yes/Yes Hex
32805 BYT4 HEX Yes/Yes Hex
32806 BYT4 UDEC Yes/Yes 1
32807 BYT4 UDEC Yes/Yes 1
32808 BYT4 UDEC Yes/Yes 1
32809 BYT4 UDEC Yes/Yes 1
32836 BYT2 UDEC No/Yes 1
32845 BYT2 UDEC Yes/Yes 1
32846 BYT2 SDEC Yes/Yes 1
32847 BYT2 SDEC Yes/Yes 1
32848 BYT2 UDEC Yes/Yes 1
32849 BYT2 SDEC Yes/Yes 1
32850 BYT2 SDEC Yes/Yes 1
32851 BYT2 SDEC Yes/Yes 1
32852 BYT2 SDEC Yes/Yes 1
32853 BYT2 SDEC Yes/Yes 1
32854 BYT2 SDEC Yes/Yes 1
32865 BYT2 UDEC Yes/Yes 1
32866 BYT2 UDEC Yes/Yes 1
32867 BYT2 UDEC Yes/Yes 1
32868 BYT2 UDEC Yes/Yes 1
32874 BYT2 UDEC Yes/Yes 1
32875 BYT2 UDEC Yes/Yes 1
32876 BYT2 UDEC Yes/Yes 1
32877 BYT2 UDEC Yes/Yes 1
618
PLC Connection Guide
ID No. Data Length Data Type Write / Read Decimal Place*
32880 BYT2 UDEC Yes/Yes 1
32881 BYT2 UDEC Yes/Yes 1
32882 BYT2 UDEC Yes/Yes 1
32883 BYT2 UDEC Yes/Yes 1
32891 BYT2 UDEC Yes/Yes 1
32892 BYT4 UDEC Yes/Yes 1
32893 BYT4 UDEC Yes/Yes 1
32922 BYT2 UDEC Yes/Yes 1
32925 BYT2 HEX Yes/Yes Hex
32926 BYT2 HEX Yes/Yes Hex
32927 BYT2 HEX Yes/Yes Hex
32928 BYT2 UDEC Yes/Yes 0.1
32929 BYT2 UDEC Yes/Yes 0.1
32934 BYT2 UDEC Yes/Yes 1
32935 BYT2 UDEC Yes/Yes 0.1
32936 BYT4 HEX Yes/Yes Hex
32940 BYT4 SDEC Yes/Yes 1
32947 BYT4 UDEC Yes/Yes 1
32952 BYT4 UDEC Yes/Yes 1
32953 BYT2 HEX Yes/Yes Hex
32956 BYT2 UDEC Yes/Yes 1
32958 BYT2 UDEC Yes/Yes 1
32959 BYT2 UDEC Yes/Yes 1
32964 BYT2 UDEC Yes/Yes 1
32966 BYT2 SDEC Yes/Yes 1
32967 BYT2 UDEC Yes/Yes 1
32968 BYT2 UDEC Yes/Yes 0.1
32978 BYT2 UDEC Yes/Yes 1
32979 BYT2 UDEC Yes/Yes 1
32980 BYT2 UDEC Yes/Yes 1
32981 BYT2 UDEC Yes/Yes 1
32992 BYT2 UDEC Yes/Yes 0.1
32993 BYT2 UDEC Yes/Yes 0.1
33700 BYT2 UDEC Yes/Yes 1
619
PLC Connection Guide
ID No. Data Length Data Type Write / Read Decimal Place*
33701 BYT2 UDEC Yes/Yes 1
33702 BYT2 UDEC Yes/Yes 1
33703 BYT2 UDEC Yes/Yes 1
33704 BYT2 UDEC Yes/Yes 1
33705 BYT2 UDEC Yes/Yes 1
33706 BYT2 UDEC Yes/Yes 1
33707 BYT2 UDEC Yes/Yes 1
33708 BYT2 UDEC Yes/Yes 1
33709 BYT2 UDEC Yes/Yes 1
33710 BYT2 UDEC Yes/Yes 1
33711 BYT2 UDEC Yes/Yes 1
33712 BYT2 UDEC Yes/Yes 1
33713 BYT2 UDEC Yes/Yes 1
33714 BYT2 UDEC Yes/Yes 1
33721 BYT2 UDEC Yes/Yes 1
33722 BYT2 UDEC Yes/Yes 1
33724 BYT2 UDEC Yes/Yes 1
33725 BYT2 UDEC Yes/Yes 1
33729 BYT2 UDEC Yes/Yes 1
33730 BYT2 UDEC Yes/Yes 1
33731 BYT2 UDEC Yes/Yes 1
33732 BYT2 UDEC No/Yes 1
33800 BYT2 UDEC Yes/Yes 1
33801 BYT2 UDEC Yes/Yes 1
33802 BYT2 UDEC Yes/Yes 1
33803 BYT2 UDEC Yes/Yes 1
33804 BYT2 UDEC Yes/Yes 1
33805 BYT2 UDEC Yes/Yes 1
33806 BYT2 UDEC Yes/Yes 1
33807 BYT2 UDEC Yes/Yes 1
33808 BYT2 UDEC Yes/Yes 1
33809 BYT2 UDEC Yes/Yes 1
33810 BYT2 UDEC Yes/Yes 1
33811 BYT2 UDEC Yes/Yes 1
620
PLC Connection Guide
ID No. Data Length Data Type Write / Read Decimal Place*
33812 BYT2 UDEC Yes/Yes 1
33813 BYT2 UDEC Yes/Yes 1
33814 BYT2 UDEC Yes/Yes 1
33815 BYT2 UDEC Yes/Yes 1
33816 BYT2 UDEC Yes/Yes 1
33817 BYT2 UDEC Yes/Yes 1
33818 BYT2 UDEC Yes/Yes 1
33819 BYT2 UDEC Yes/Yes 1
33820 BYT2 UDEC Yes/Yes 1
33839 BYT2 UDEC Yes/Yes 1
33840 BYT2 UDEC Yes/Yes 1
33859 BYT2 UDEC Yes/Yes 1
33860 BYT2 UDEC Yes/Yes 1
33869 BYT2 UDEC Yes/Yes 1
33880 BYT2 UDEC Yes/Yes 1
33889 BYT2 UDEC Yes/Yes 1
33890 BYT2 UDEC Yes/Yes 1
33899 BYT2 UDEC Yes/Yes 1
34000 BYT2 UDEC Yes/Yes 1
34001 BYT2 UDEC Yes/Yes 1
34002 BYT2 UDEC Yes/Yes 1
34003 BYT2 UDEC Yes/Yes 1
34004 BYT2 UDEC Yes/Yes 1
34005 BYT2 UDEC Yes/Yes 1
34006 BYT2 UDEC Yes/Yes 1
34007 BYT2 UDEC Yes/Yes 1
34008 BYT2 UDEC Yes/Yes 1
34009 BYT2 UDEC Yes/Yes 1
34010 BYT2 UDEC Yes/Yes 1
34011 BYT2 UDEC Yes/Yes 1
34012 BYT2 UDEC Yes/Yes 1
34013 BYT2 UDEC Yes/Yes 1
34014 BYT2 UDEC Yes/Yes 1
34015 BYT2 UDEC Yes/Yes 1
621
PLC Connection Guide
ID No. Data Length Data Type Write / Read Decimal Place*
34016 BYT2 UDEC Yes/Yes 1
34017 BYT2 UDEC Yes/Yes 1
34018 BYT2 UDEC Yes/Yes 1
34019 BYT2 UDEC Yes/Yes 1
34023 BYT2 UDEC Yes/Yes 1
34025 BYT2 UDEC Yes/Yes 1
34042 BYT2 UDEC Yes/Yes 1
34043 BYT2 UDEC Yes/Yes 0.01
34044 BYT2 UDEC Yes/Yes 0.01
34045 BYT2 UDEC Yes/Yes 0.01
34046 BYT2 UDEC Yes/Yes 0.01
34047 BYT2 UDEC Yes/Yes 0.01
34048 BYT2 UDEC Yes/Yes 0.01
34049 BYT2 UDEC Yes/Yes 0.01
34050 BYT2 UDEC Yes/Yes 0.1
34051 BYT2 UDEC Yes/Yes 0.01
34052 BYT2 UDEC Yes/Yes 0.1
34053 BYT2 UDEC Yes/Yes 1
34054 BYT2 UDEC Yes/Yes 0.1
34055 BYT2 UDEC Yes/Yes 0.1
34056 BYT2 UDEC Yes/Yes 1
34070 BYT2 UDEC Yes/Yes 1
34148 BYT2 UDEC Yes/Yes 0.001
34149 BYT2 UDEC Yes/Yes 0.1
34164 BYT2 UDEC Yes/Yes 0.01
34167 BYT2 UDEC Yes/Yes 0.01
34177 BYT2 UDEC Yes/Yes 1
34178 BYT2 UDEC Yes/Yes 1
34179 BYT2 UDEC Yes/Yes 1
34180 BYT2 UDEC Yes/Yes 1
34182 BYT4 SDEC Yes/Yes 1
35000 /* Depends on Text */ 0 ASCI No/Yes ASCII
35001 /* Depends on Text */ 0 ASCI No/Yes ASCII
35002 BYT4 HEX No/Yes 1
622
PLC Connection Guide
ID No. Data Length Data Type Write / Read Decimal Place*
35003 BYT2 HEX No/Yes Hex
35004 BYT2 UDEC No/Yes 0.1
35005 BYT2 UDEC No/Yes 0.1
35006 BYT2 UDEC No/Yes 0.1
35007 BYT2 UDEC No/Yes 0.1
35008 BYT2 UDEC No/Yes 0.1
35009 BYT2 UDEC No/Yes 0.1
35010 BYT2 UDEC No/Yes 0.1
35011 BYT2 UDEC No/Yes 1
36000 BYT2 UDEC No/Yes 1
36001 BYT2 UDEC No/Yes 1
36002 BYT4 SDEC No/Yes 1
36003 BYT4 SDEC No/Yes 1
36004 BYT4 UDEC No/Yes 1
36005 BYT4 UDEC No/Yes 1
36006 BYT2 UDEC No/Yes 1
36007 BYT2 UDEC No/Yes 1
36008 BYT2 UDEC No/Yes 1
36009 BYT2 UDEC No/Yes 1
36010 BYT2 UDEC No/Yes 1
36011 BYT2 UDEC No/Yes 1
36012 BYT4 UDEC No/Yes 1
36013 BYT4 UDEC No/Yes 1
36019 BYT2 UDEC Yes/Yes 1
36020 BYT2 UDEC Yes/Yes 1
36021 BYT2 UDEC Yes/Yes 1
36022 BYT2 UDEC Yes/Yes 1
36023 BYT2 UDEC Yes/Yes 1
36100 BYT4 UDEC Yes/Yes 1
36101 BYT4 UDEC Yes/Yes 1
36102 BYT4 UDEC Yes/Yes 1
36103 BYT4 UDEC Yes/Yes 1
36104 BYT4 UDEC Yes/Yes 1
623
PLC Connection Guide
*Note: If the decimal place of ID is 0.0001, please set [Right of decimal Pt.] of the object to
“4”.
Wiring Diagram:
The following represents the cable end connector.
RS-232
eMT3000 series
COM1 RS232 9P COM3 RS232 9P X5 Port RS232 9P
D-Sub Female D-Sub Female D-Sub Male
2 RX 8 RX 2 TX
3 TX 7 TX 3 RX
5 GND 5 GND 5 GND
624
PLC Connection Guide
MT6050i/MT8050i
COM1 RS232 9P X5 Port RS232 9P
D-Sub Female D-Sub Male
9 RX 2 TX
6 TX 3 RX
5 GND 5 GND
MT6050i/MT8050i
COM1 RS485 2W COM3 RS485 2W X5 Port RS485 2W 9P
9P D-Sub Female 9P D-Sub Female D-Sub Male
1 RX- 7 Data- 4 RS485-
2 RX+ 8 Data+ 1 RS485+
5 GND 5 GND 5 GND
625
PLC Connection Guide
Driver Version:
Version Date Description
V1.00 Mar/27/2012 Driver released.
The newly supported software SSTS_PAS_V2.2 supports ID
V1.10 May/14/2012
address.
626
PLC Connection Guide
Website: http://www.techsoftmotion.com
HMI Setting:
Parameters Recommended Options Notes
PLC type Intelligent Servo
PLC I/F RS232
Baud rate 9600 9600~115200
Data bits 8 7 or 8
Parity None Even, Odd, None
Stop bits 1 1 or 2
PLC sta. no. 1
Device Address:
Bit/Word Device type Format Range Memo
W Register_32bit HHHH 0 ~ 270f 32bit signed
DW Register_H HHHH 0 ~ 270f 32bit Hex
W UPD HHHHH 0 ~ 1869f Send UDP command
W STOP HHHHH 0 ~ 1869f Send STOP command
Wiring Diagram:
The following represents the cable end connector.
eMT3000 series
COM1 RS232 9P COM3 RS232 9P Servo RS232 D-Sub
D-Sub Female D-Sub Female Male
2 RX 8 RX 2 TD
3 TX 7 TX 3 RD
5 GND 5 GND 5 GND
627
PLC Connection Guide
MT6050i/MT8050i
COM1 RS232 9P Servo RS232 D-Sub
D-Sub Female Male
9 RX 2 TD
6 TX 3 RD
5 GND 5 GND
Driver Version:
Version Date Description
V1.00 Nov/06/2009 Driver released.
628
PLC Connection Guide
TECO Inverter
Supported Series: TECO Inverter series, 7300CV model.
HMI Setting:
Parameters Recommended Options Notes
PLC type TECO Inverter
PLC I/F RS232 RS232/RS485
Baud rate 38400
Data bits 8
Parity None
Stop bits 1
PLC sta. no. 1
Device Address:
Bit/Word Device type Format Range Memo
B 0x DDDDD 1 ~ 65535 Output Bit
B 1x DDDDD 1 ~ 65535 Input Bit (read only)
B 3x_Bit DDDDDdd 100 ~ 6553515 Input Register Bit (read only)
B 4x_Bit DDDDDdd 100 ~ 6553515 Output Register Bit
B 6x_Bit DDDDDdd 100 ~ 6553515
B 0x (0x0f) DDDDD 1 ~ 65535 Write Multiple Coils
W 3x DDDDD 1 ~ 65535 Input Register (read only)
W 4x DDDDD 1 ~ 65535 Output Register
DW 5x DDDDD 1 ~ 65535 4x Double Word Swap
W 6x DDDDD 1 ~ 65535 4x Single Word Write
629
PLC Connection Guide
Wiring Diagram:
630
PLC Connection Guide
MT6000/8000 series except MT6050i/MT8050i
COM1 RS232 9P RS232 9P D-Sub Male
D-Sub Female
2 RX 2 TX
3 TX 3 RX
5 GND 5 GND
7 RTS 7 VCC
Driver Version:
Version Date Description
V1.00 Jul/27/2009 Driver released.
631
PLC Connection Guide
HMI Setting:
Parameters Recommended Options Notes
PLC type TECO TP02 Series
MMI 422 port: 4W; RS485
PLC I/F RS485 4W/2W RS485 4W/2W
terminals: 2W
Baud rate 19200 9600, 19200, 38400
Data bits 7 7, 8
Parity Even Even, Odd, None
Stop bits 2 1, 2
PLC sta. no. 1 0-255
PLC Setting:
RS422 port: WS041=120, WS042=1;
RS485 terminals: WS044=120, WS045=1.
Device Address:
Bit/Word Device type Format Range Memo
B X DDD 1 ~ 384 Input relay
B Y DDD 1 ~ 384 Output relay
B C DDDD 1 ~ 2048 Auxiliary relay
632
PLC Connection Guide
Wiring Diagram:
The following represents the cable end connector.
TP02 Series MMI RS422 port : 9P D-Sub to 9P D-Sub
eMT3000 series
COM1 RS485 4W RS485 4W 9P D-Sub
9P D-Sub Male Male
1 RX- 8 TX-
2 RX+ 3 TX+
3 TX- 7 RX-
4 TX+ 2 RX+
5 GND
MT6050i/MT8050i
COM1 RS485 4W RS485 4W 9P D-Sub
9P D-Sub Female Male
1 RX- 8 TX-
2 RX+ 3 TX+
3 TX- 7 RX-
4 TX+ 2 RX+
5 GND
633
PLC Connection Guide
The following represents the cable end connector.
TP02 Series RS485 Terminal : 9P D-Sub to 9P D-Sub
eMT3000 series
COM1 RS485 2W COM3 RS485 2W RS485 2W Terminal
9P D-Sub Male 9P D-Sub Male
1 RX- 6 Data- T/R-
2 RX+ 9 Data+ T/R+
5 GND 5 GND
MT6050i/MT8050i
COM1 RS485 2W COM3 RS485 2W RS485 2W Terminal
9P D-Sub Female 9P D-Sub Female
1 RX- 7 Data- T/R-
2 RX+ 8 Data+ T/R+
5 GND 5 GND
Driver Version:
Version Date Description
V1.10 Jan/25/2010
634
PLC Connection Guide
Website: http://www.teco.com.tw/sa/en/
HMI Setting:
Parameters Recommended Options Notes
PLC type TECO TP03 Series
PLC I/F RS485 4W
Baud rate 19200 9600, 19200
Data bits 8 8
Parity None Even, Odd, None
Stop bits 2 1
PLC sta. no. 1 1-31
Device Address:
Bit/Word Device type Format Range Memo
B C DDDD 0 ~ 9999
B M DDDD 0 ~ 9999
B S DDDD 0 ~ 9999
B T DDDD 0 ~ 9999
B X OOO 0 ~ 377
B Y OOO 0 ~ 377
W D DDDD 0 ~ 9999
W V DDDD 0 ~ 9999
W Z DDDD 0 ~ 9999
W T_Curent DDDD 0 ~ 9999
W C_Curent DDDD 0 ~ 9999
W T_Preset DDDD 0 ~ 9999
W C_Preset DDDD 0 ~ 9999
635
PLC Connection Guide
Wiring Diagram:
The following represents the cable end connector.
eMT3000 series
COM1 RS485 4W RS485 4W 8P Mini-DIN
9P D-Sub Male Male
1 RX- 4 TX-
2 RX+ 7 TX+
3 TX- 1 RX-
4 TX+ 2 RX+
5 GND 3 GND
MT6050i/MT8050i
COM1 RS485 4W RS485 4W 8P Mini-DIN
9P D-Sub Female Male
1 RX- 4 TX-
2 RX+ 7 TX+
3 TX- 1 RX-
4 TX+ 2 RX+
5 GND 3 GND
636
PLC Connection Guide
Driver Version:
Version Date Description
V1.10 Nov/13/2009
637
PLC Connection Guide
TINHAO
Website: www.chinastrand.com
HMI Setting:
Parameters Recommended Options Notes
PLC type TINHAO
PLC I/F RS485 2W
Baud rate 19200
Data bits 8
Parity None
Stop bits 1
PLC sta. no. 1
Device Address:
Bit/Word Device type Format Range Memo
W Commend1 DDD 0 ~ 255
W Commend2 DDD 0 ~ 255
W Commend3 DDD 0 ~ 255
W Commend4 DDD 0 ~ 255
W Commend5 DDD 0 ~ 255
W Commend6 DDD 0 ~ 255
W Commend7 DDD 0 ~ 255
W Commend8 DDD 0 ~ 255
W Commend9 DDD 0 ~ 255
W Commend10 DDD 0 ~ 255
W Commend11 DDD 0 ~ 255
W Commend12 DDD 0 ~ 255
W Commend13 DDD 0 ~ 255
W Commend14 DDD 0 ~ 255
W Commend15 DDD 0 ~ 255
W Commend16 DDD 0 ~ 255
W Commend17 DDD 0 ~ 255
W Commend18 DDD 0 ~ 255
638
PLC Connection Guide
Wiring Diagram:
The following represents the cable end connector.
eMT3000 series
COM1 RS485 2W COM3 RS485 2W RS485 terminal
9P D-Sub Male 9P D-Sub Male
1 RX- 6 Data- D-
2 RX+ 9 Data+ D+
5 GND 5 GND
639
PLC Connection Guide
MT6050i/MT8050i
COM1 RS485 2W COM3 RS485 2W RS485 terminal
9P D-Sub Female 9P D-Sub Female
1 RX- 7 Data- D-
2 RX+ 8 Data+ D+
5 GND 5 GND
Driver Version:
Version Date Description
V1.00 Oct/14/2011 Driver released.
640
PLC Connection Guide
Toptek Topvert
Supported Series: TOPVERT G1/H1/P1 series.
Website: http://www.toptek.biz/
HMI Setting:
Parameters Recommended Options Notes
PLC type Toptek Topvert
PLC I/F RS485 2W
Baud rate 9600
Data bits 7
Parity None
Stop bits 2
PLC sta. no. 1
PLC Setting:
Communication mode Pr 7-15 = 0 (7, N, 2 ASCII)
Device Address:
Bit/Word Device type Format Range Memo
G=Groups, F=Function no.
B PR_Bit DDDDDdd 0 ~ 6553515 dd=0~15 bit no.
641
PLC Connection Guide
Note:
Max.read-command size (words): 16
Max.write-command size (words): 1
For G1/H1/P1 Series Inverter, if standard parameter address is in decimal= 100*G+F:
G=Group (parameter group code0~9); F=Function no. (parameter number 0~99)
For example: Pr5-20 (decimal Dec.) parameter address is expressed as 100*5+20=520.
Wiring Diagram:
The following represents the cable end connector.
eMT3000 series
COM1 RS485 2W COM3 RS485 2W RS485 2W Terminal
9P D-Sub Male 9P D-Sub Male
1 RX- 6 Data- SG-
2 RX+ 9 Data+ SG+
5 GND 5 GND
642
PLC Connection Guide
MT6050i/MT8050i
COM1 RS485 2W COM3 RS485 2W RS485 2W Terminal
9P D-Sub Female 9P D-Sub Female
1 RX- 7 Data- SG-
2 RX+ 8 Data+ SG+
5 GND 5 GND
Driver Version:
Version Date Description
V1.00 Dec/08/2010 Driver released.
643
PLC Connection Guide
TOSHIBA T Series
Supported Series: Toshiba T series, S2E.
Website: http://www.tic.toshiba.com
HMI Setting:
Parameters Recommended Options Notes
PLC type TOSHIBA T Series
PLC I/F RS232 RS232/RS485 In accordance with PLC port
9600, 19200, 38400,
Baud rate 9600
57600, 115200
Data bits 8 7,8
Parity Odd Even, Odd, None
Stop bits 1 1, 2
Must be same as the PLC
PLC sta. no. 0 0-255
setting
PLC Setting:
Communication mode Must set PLC node ID
Device Address:
Bit/Word Device type Format Range Memo
B X DDDDh 0 ~ 4095f Input Bit
B Y DDDDh 0 ~ 4095f Output Bit
B R DDDDh 0 ~ 8191f Auxiliary Bit
B S DDDDh 0 ~ 4095f Special Bit
B L DDDDh 0 ~ 4095f
B Z DDDDh 0 ~ 8191f
W T DDD 0 ~ 999 Timer Register
W C DDD 0 ~ 511 Counter Register
W D DDDD 0 ~ 8191 Data Memory
644
PLC Connection Guide
Bit/Word Device type Format Range Memo
W SW DDD 0 ~ 255 Special Register
W XW DDD 0 ~ 255 Input Register
W YW DDD 0 ~ 255 Output Register
W RW DDD 0 ~ 999 Auxiliary Register
W LW DDD 0 ~ 255
W W DDDD 0 ~ 1023
W F DDDD 0 ~ 8191
Wiring Diagram:
The following represents the cable end connector.
Toshiba T1 PRG RS232 : 9P D-Sub to 8P Mini-DIN
eMT3000 series
COM1 RS232 9P COM3 RS232 9P RS232 8P Mini-DIN
D-Sub Female D-Sub Female Male
2 RX 8 RX 6 TXD
3 TX 7 TX 8 RXD
5 GND 5 GND 5 GND
4 RTS
circuit
7 CTS
645
PLC Connection Guide
MT6050i/MT8050i
COM1 RS232 9P RS232 8P Mini-DIN
D-Sub Female Male
9 RX 6 TXD
6 TX 8 RXD
5 GND 5 GND
4 RTS
circuit
7 CTS
646
PLC Connection Guide
MT6050i/MT8050i
COM1 RS232 9P RS232 9P D-Sub Male
D-Sub Female
9 RX 3 TXD
6 TX 2 RXD
5 GND 5 GND
7 RTS
circuit
8 CTS
647
PLC Connection Guide
MT6000/8000 series except MT6050i/MT8050i
COM1 RS485 4W RS485 4W 15P D-Sub
9P D-Sub Male Male
1 RX- 11 TXB
2 RX+ 3 TXA
3 TX- 10 RXB
4 TX+ 2 RXA
5 GND 7 SG
5 RTSA
circuit
4 CTSA
13 RTSB
circuit
12 CTSB
MT6050i/MT8050i
COM1 RS485 4W RS485 4W 15P D-Sub
9P D-Sub Female Male
1 RX- 11 TXB
2 RX+ 3 TXA
3 TX- 10 RXB
4 TX+ 2 RXA
5 GND 7 SG
5 RTSA
circuit
4 CTSA
13 RTSB
circuit
12 CTSB
Driver Version:
Version Date Description
TOSHIBA T Series driver can now correctly read and write
V1.20 May/13/2011
“L”, “LW”, “F” address types.
648
PLC Connection Guide
TOSHIBA VF-S11
Supported Series: Toshiba Invertor Protocol (ASCII code).
HMI Setting:
Parameters Recommended Options Notes
PLC type TOSHIBA VF-S11
PLC I/F RS485 2W RS422, RS485
Baud rate 9600 9600, 19200
Data bits 8 7 or 8
Parity Even Even, Odd, None
Stop bits 1 1 or 2
PLC sta. no. 0 0-99
Device Address:
Bit/Word Device type Format Range Memo
B Cmd. No B HHHHdd 0 ~ 270f15
W Cmd. No HHHH 0 ~ ffff Parameters and data memory
Wiring Diagram:
Note:
Before connecting with VF-S11, make sure the SW1 of both sides are in the correct
position. (SW1: wiring method selector switch)
649
PLC Connection Guide
RS-485
The following represents the cable end connector.
eMT3000 series
COM1 RS485 2W COM3 RS485 2W RS485 2W 8P RJ45
9P D-Sub Male 9P D-Sub Male Male
1 RX- 6 Data- 5 Data-
2 RX+ 9 Data+ 4 Data+
5 GND 5 GND 8 Gnd
650
PLC Connection Guide
MT6050i/MT8050i
COM1 RS485 2W COM3 RS485 2W RS485 2W 8P RJ45
9P D-Sub Female 9P D-Sub Female Male
1 RX- 7 Data- 5 Data-
2 RX+ 8 Data+ 4 Data+
5 GND 5 GND 8 Gnd
Driver Version:
Version Date Description
V1.20 Aug/31/2009
651
PLC Connection Guide
WebSite: http://www.toshiba-machine.co.jp
HMI Setting:
Parameters Recommended Options Notes
PLC type TOSHIBA MACHINE Provisor TC200
PLC I/F RS232 RS232 In accordance with PLC port
Baud rate 9600 9600, 19200
Data bits 8 7,8
Parity None Even, Odd, None
Stop bits 1 1, 2
Device Address:
Bit/Word Device type Format Range Memo
B R_bit HHHh 0 ~ ffff h : Bit no.(0~f)
B X_bit HHHh 0 ~ ffff h : Bit no.(0~f)
B Y_bit HHHh 0 ~ ffff h : Bit no.(0~f)
B L_bit HHHh 0 ~ ffff h : Bit no.(0~f)
W P HHH 0 ~ fff
W V HHH 0 ~ fff
W X HHH 0 ~ fff
W Y HHH 0 ~ fff
W D HHH 0 ~ fff
W R HHH 0 ~ fff
W L HHH 0 ~ fff
652
PLC Connection Guide
Wiring Diagram:
The following represents the cable end connector.
eMT3000 series
COM1 RS232 9P COM3 RS232 9P TC mini series RS232
D-Sub Female D-Sub Female 9P D-Sub Male
2 RX 8 RX 2 TXD
3 TX 7 TX 3 RXD
5 GND 5 GND 5 GND
7 RTS
circuit
9 CTS
MT6050i/MT8050i
COM1 RS232 9P TC mini series RS232
D-Sub Female 9P D-Sub Male
9 RX 2 TXD
6 TX 3 RXD
5 GND 5 GND
7 RTS
circuit
9 CTS
653
PLC Connection Guide
HMI Setting:
Parameters Recommended Options Notes
PLC type Trio MODBUS RTU, TCP/IP
PLC I/F RS485 RS232/RS485/Ethernet
Baud rate 9600 9600~115200
Data bits 8 7, 8
Parity Even Even, Odd, None
Stop bits 1 1, 2
Port no. 502
PLC sta. no. 1 0-255
PLC Setting:
Communication mode Modbus RTU protocol
PLC Mode 4 (16bit signed integer)
Device Address:
Bit/Word Device type Format Range Memo
B VR_Bit DDDDdd 0 ~ 102315
B Table_Bit DDDDDdd 0 ~ 3199915
W VR DDDD 0 ~ 1023
W Table DDDDD 0 ~ 31999
654
PLC Connection Guide
Wiring Diagram:
The following represents the cable end connector.3
Trio : RS232
eMT3000 series
COM1 RS232 9P COM3 RS232 9P RS232 9P D-Sub Male
D-Sub Female D-Sub Female
2 RX 8 RX TXD
3 TX 7 TX RXD
5 GND 5 GND GND
RTS
circuit
CTS
MT6050i/MT8050i
COM1 RS232 9P RS232 9P D-Sub Male
D-Sub Female
9 RX TXD
6 TX RXD
5 GND GND
RTS
circuit
CTS
655
PLC Connection Guide
The following represents the cable end connector.
Trio : RS485 4W
eMT3000 series
COM1 RS485 4W RS485 4W 9P D-Sub
9P D-Sub Male Male
1 RX- TX-
2 RX+ TX+
3 TX- RX-
4 TX+ RX+
5 GND GND
MT6050i/MT8050i
COM1 RS485 4W RS485 4W 9P D-Sub
9P D-Sub Female Male
1 RX- TX-
2 RX+ TX+
3 TX- RX-
4 TX+ RX+
5 GND GND
656
PLC Connection Guide
The following represents the cable end connector.
Trio : RS485 2W
eMT3000 series
COM1 RS485 2W COM3 RS485 2W RS485 2W 9P D-Sub
9P D-Sub Male 9P D-Sub Male Male
1 RX- 6 Data- D-
2 RX+ 9 Data+ D+
5 GND 5 GND GND
MT6050i/MT8050i
COM1 RS485 2W COM3 RS485 2W RS485 2W 9P D-Sub
9P D-Sub Female 9P D-Sub Female Male
1 RX- 7 Data- D-
2 RX+ 8 Data+ D+
5 GND 5 GND GND
657
PLC Connection Guide
Direct connect (crossover cable):
HMI RJ45 Male Wire Color PLC RJ45 Male
1 TX+ White/Orange 3 RX+
2 TX- Orange 6 RX-
3 RX+ White/Green 1 TX+
4 BD4+ Blue 4 BD4+
5 BD4- White/Blue 5 BD4-
6 RX- Green 2 TX-
7 BD3+ White/Brown 7 BD3+
8 BD3- Brown 8 BD3-
Through a hub:
HMI RJ45 Male Wire Color PLC RJ45 Male
1 TX+ White/Orange 1 TX+
2 TX- Orange 2 TX-
3 RX+ White/Green 3 RX+
4 BD4+ Blue 4 BD4+
5 BD4- White/Blue 5 BD4-
6 RX- Green 6 RX-
7 BD3+ White/Brown 7 BD3+
8 BD3- Brown 8 BD3-
Driver Version:
Version Date Description
V1.00 May/27/2011 Driver released.
658
PLC Connection Guide
HMI Setting:
Parameters Recommended Options Notes
PLC type Trio MODBUS RTU, TCP/IP (Mode 7)
PLC I/F RS485 RS232/RS485/Ethernet
Baud rate 9600 9600~115200
Data bits 8 7, 8
Parity Even Even, Odd, None
Stop bits 1 1, 2
Port no. 502
PLC sta. no. 1 0-255
PLC Setting:
Communication mode Modbus RTU protocol
PLC 模式 7 (IEEE floating point)
Device Address:
Bit/Word Device type Format Range Memo
B VR_Bit DDDDdd 0 ~ 102331
B Table_Bit DDDDDdd 0 ~ 3199931
W VR DDDD 0 ~ 1023
W Table DDDDD 0 ~ 31999
659
PLC Connection Guide
Wiring Diagram:
The following represents the cable end connector.3
Trio : RS232
eMT3000 series
COM1 RS232 9P COM3 RS232 9P RS232 9P D-Sub Male
D-Sub Female D-Sub Female
2 RX 8 RX TXD
3 TX 7 TX RXD
5 GND 5 GND GND
RTS
circuit
CTS
MT6050i/MT8050i
COM1 RS232 9P RS232 9P D-Sub Male
D-Sub Female
9 RX TXD
6 TX RXD
5 GND GND
RTS
circuit
CTS
660
PLC Connection Guide
The following represents the cable end connector.
Trio : RS485 4W
eMT3000 series
COM1 RS485 4W RS485 4W 9P D-Sub
9P D-Sub Male Male
1 RX- TX-
2 RX+ TX+
3 TX- RX-
4 TX+ RX+
5 GND GND
MT6050i/MT8050i
COM1 RS485 4W RS485 4W 9P D-Sub
9P D-Sub Female Male
1 RX- TX-
2 RX+ TX+
3 TX- RX-
4 TX+ RX+
5 GND GND
661
PLC Connection Guide
The following represents the cable end connector.
Trio : RS485 2W
eMT3000 series
COM1 RS485 2W COM3 RS485 2W RS485 2W 9P D-Sub
9P D-Sub Male 9P D-Sub Male Male
1 RX- 6 Data- D-
2 RX+ 9 Data+ D+
5 GND 5 GND GND
MT6050i/MT8050i
COM1 RS485 2W COM3 RS485 2W RS485 2W 9P D-Sub
9P D-Sub Female 9P D-Sub Female Male
1 RX- 7 Data- D-
2 RX+ 8 Data+ D+
5 GND 5 GND GND
662
PLC Connection Guide
Direct connect (crossover cable):
HMI RJ45 Male Wire Color PLC RJ45 Male
1 TX+ White/Orange 3 RX+
2 TX- Orange 6 RX-
3 RX+ White/Green 1 TX+
4 BD4+ Blue 4 BD4+
5 BD4- White/Blue 5 BD4-
6 RX- Green 2 TX-
7 BD3+ White/Brown 7 BD3+
8 BD3- Brown 8 BD3-
Through a hub:
HMI RJ45 Male Wire Color PLC RJ45 Male
1 TX+ White/Orange 1 TX+
2 TX- Orange 2 TX-
3 RX+ White/Green 3 RX+
4 BD4+ Blue 4 BD4+
5 BD4- White/Blue 5 BD4-
6 RX- Green 6 RX-
7 BD3+ White/Brown 7 BD3+
8 BD3- Brown 8 BD3-
Driver Version:
Version Date Description
V1.00 Apr/20/2012 Driver released.
663
PLC Connection Guide
VIGOR
Supported Series: VIGOR M Series and VB Series.
Website: http://www.vigorplc.com.tw/
HMI Setting:
Parameters Recommended Options Notes
PLC type VIGOR
PLC I/F RS232 RS232, RS485 4W
Baud rate 19200
Data bits 7
Parity Even
Stop bits 1
PLC sta. no. 1
Device Address:
Bit/Word Device type Format Range Memo
B X OOO 0 ~ 377
B Y OOO 0 ~ 377
B M DDDD 0 ~ 7999
B T DDD 0 ~ 255
B C DDD 0 ~ 255
B SM DDDD 9000 ~ 9255
W TV DDD 0 ~ 255
W CV DDD 0 ~ 199
W D DDDD 0 ~ 9255
W CV2 DDD 200 ~ 255
W SD DDDD 9000 ~ 9255
664
PLC Connection Guide
Wiring Diagram:
The following represents the cable end connector.
Vigor M series : RS485 4W Terminal
eMT3000 series
COM1 RS485 4W Vigor M series RS485
9P D-Sub Male 4W 6P Terminal
1 RX- TX-
2 RX+ TX+
3 TX- RX-
4 TX+ RX+
5 GND SG
665
PLC Connection Guide
MT6050i/MT8050i
COM1 RS485 4W Vigor M series RS485
9P D-Sub Female 4W 6P Terminal
1 RX- TX-
2 RX+ TX+
3 TX- RX-
4 TX+ RX+
5 GND SG
666
PLC Connection Guide
MT6050i/MT8050i
COM1 RS232 9P Vigor M series RS232
D-Sub Female 9P D-Sub Male
9 RX 3 TXD
6 TX 2 RXD
5 GND 5 GND
Driver Version:
Version Date Description
V1.10 Dec/30/2008
667
PLC Connection Guide
VIPA 200
HMI Setting:
Parameters Recommended Options Notes
PLC type VIPA 200
PLC I/F RS485 2w RS485 2w
The HMI which has a sticker
Baud rate 9600 9600, 19200, 187.5K “MPI187.5” on the rear
cover supports 187.5K
Data bits 8 7,8
Parity Even Even, Odd, None
Stop bits 1 1, 2
PLC sta. no. 2 1 ~ 126
Turn around
5
delay (ms)
Reserved 1 30 ACK delay time
PLC Setting:
Communication mode Set station number to 2
Device Address:
Bit/Word Device type Format Range Memo
B I DDDDo 0 ~ 40957 Input (I)
B Q DDDDo 0 ~ 40957 Output (O)
B M DDDDo 0 ~ 40957 Bit Memory
B VW_Bit DDDDDo 0 ~ 102397 V Memory Bit Address
Byte VB DDDDD 0 ~ 10239
W VW DDDDD 0 ~ 10239 V Memory
W VW_Odd DDDDD 0 ~ 10239 V Memory
DW VD DDDDD 0 ~ 10239 V Memory Double Word
DW VD_Odd DDDDD 0 ~ 10239 V Memory Double Word
668
PLC Connection Guide
Bit/Word Device type Format Range Memo
W VW_String DDDDD 0 ~ 10239 String
W VW_String_Odd DDDDD 0 ~ 10239 String
DW VD_String DDDDD 0 ~ 10239 String
DW VD_String_Odd DDDDD 0 ~ 10239 String
Byte MB DDDDD 0 ~ 10239 Byte Memory
W MW DDDDD 0 ~ 10239 Word Memory
DW MD DDDDD 0 ~ 10239 Word Memory
W MW_Odd DDDDD 0 ~ 10239 Word Memory
W T DDD 0 ~ 127 Timer
W C DDD 0 ~ 127 Counter
Double word and floating point value must use VD device type.
Wiring Diagram:
The following represents the cable end connector.
eMT3000 series
COM1 RS485 2W COM3 RS485 2W RS485 2W 9P D-Sub
9P D-Sub Male 9P D-Sub Male Male
1 RX- 6 Data- 8 D-
2 RX+ 9 Data+ 3 D+
5 GND 5 GND 5 GND
669
PLC Connection Guide
MT6050i/MT8050i
COM1 RS485 2W COM3 RS485 2W RS485 2W 9P D-Sub
9P D-Sub Female 9P D-Sub Female Male
1 RX- 7 Data- 8 D-
2 RX+ 8 Data+ 3 D+
5 GND 5 GND 5 GND
Driver Version:
Version Date Description
V2.30 Aug/17/2009
V2.40 Nov/1/2011 Add device type : MD
670
PLC Connection Guide
HMI Setting:
Parameters Recommended Options Notes
PLC type VIPA 200 (VD any address)
PLC I/F RS485 2w RS485 2w
The HMI which has a
9600, 19200, sticker “MPI187.5” on
Baud rate 9600
187.5K the rear cover supports
187.5K
Data bits 8 7,8
Parity Even Even, Odd, None
Stop bits 1 1, 2
PLC sta. no. 2 1 ~ 126
Turn around delay 5
Reserved 1 30 ACK delay time
PLC Setting:
Communication mode Set station number to 2
Device Address:
Bit/Word Device type Format Range Memo
B I DDDDo 0 ~ 40957 Input (I)
B Q DDDDo 0 ~ 40957 Output (O)
B M DDDDo 0 ~ 40957 Bit Memory
B VW_Bit DDDDDo 0 ~ 102397 V Memory Bit Address
W VW DDDDD 0 ~ 10239 V Memory
DW VD DDDDD 0 ~ 10239 V Memory Double Word
W VW_String DDDDD 0 ~ 10239 String
DW VD_String DDDDD 0 ~ 10239 String
671
PLC Connection Guide
Wiring Diagram:
The following represents the cable end connector.
eMT3000 series
COM1 RS485 2W COM3 RS485 2W RS485 2W 9P D-Sub
9P D-Sub Male 9P D-Sub Male Male
1 RX- 6 Data- 8 D-
2 RX+ 9 Data+ 3 D+
5 GND 5 GND 5 GND
MT6050i/MT8050i
COM1 RS485 2W COM3 RS485 2W RS485 2W 9P D-Sub
9P D-Sub Female 9P D-Sub Female Male
1 RX- 7 Data- 8 D-
2 RX+ 8 Data+ 3 D+
5 GND 5 GND 5 GND
672
PLC Connection Guide
Driver Version:
Version Date Description
V1.20 Nov/16/2011 Add device type : MD
673
PLC Connection Guide
HMI Setting:
Parameters Recommended Options Notes
PLC type VIPA 200, for ex. 214-2BT10 (Ethernet)
PLC I/F Ethernet
Port no. 102
PLC sta. no. 1 0-31
Device Address:
Bit/Word Device type Format Range Memo
B I DDDDo 0 ~ 40957 Input (I)
B Q DDDDo 0 ~ 40957 Output (O)
B M DDDDo 0 ~ 40957 Bit Memory
B VW_Bit DDDDDo 0 ~ 102397 V Memory Bit Address
W VW DDDDD 0 ~ 10239 V Memory
DW VD DDDDD 0 ~ 10239 V Memory Double Word
W VW_String DDDDD 0 ~ 10239 String
DW VD_String DDDDD 0 ~ 10239 String
DW MD DDDDD 0 ~ 10239 Word Memory
Double word and floating point value must use VD device type.
674
PLC Connection Guide
Wiring Diagram:
Direct connect (crossover cable):
HMI RJ45 Male Wire Color PLC RJ45 Male
1 TX+ White/Orange 3 RX+
2 TX- Orange 6 RX-
3 RX+ White/Green 1 TX+
4 BD4+ Blue 4 BD4+
5 BD4- White/Blue 5 BD4-
6 RX- Green 2 TX-
7 BD3+ White/Brown 7 BD3+
8 BD3- Brown 8 BD3-
Through a hub:
HMI RJ45 Male Wire Color PLC RJ45 Male
1 TX+ White/Orange 1 TX+
2 TX- Orange 2 TX-
3 RX+ White/Green 3 RX+
4 BD4+ Blue 4 BD4+
5 BD4- White/Blue 5 BD4-
6 RX- Green 6 RX-
7 BD3+ White/Brown 7 BD3+
8 BD3- Brown 8 BD3-
Driver Version:
Version Date Description
V1.20 Dec/30/2008
V1.40 Nov/15/2011 Add device type : MD
675
PLC Connection Guide
VIPA 300
HMI Setting:
Parameters Recommended Options Notes
PLC type VIPA 300
PLC I/F RS232
Must be same as the PLC setting.
19200, 38400, The HMI which has a sticker
Baud rate 9600~187.5K
187.5K MPI187.5 on the rear cover
supports 187.5K.
Data bits 8
Parity Odd
Stop bits 1
PLC sta. no. 2 Must be same as the PLC setting.
Device Address:
Bit/Word Device type Format Range Memo
B I DDDDo 0 ~ 40957 Input (I)
B Q DDDDo 0 ~ 40957 Output (O)
B M DDDDo 0 ~ 40957 Bit Memory
B DBnBit FFFFDDDDo 0 ~ 409681927 Data Register Bit
B DB0Bit ~ DDDDo 0 ~ 81927
W DB99Bit
IW DDDD 0 ~ 4095 Input (I)
W QW DDDD 0 ~ 4095 Output (O)
W MW DDDD 0 ~ 4095 Bit Memory
DW MD DDDD 0 ~ 4094
Byte MB DDDD 0 ~ 4095 Bit Memory Byte
Byte DBBn FFFFDDDD 0 ~ 40968192 Data Register Byte
Data Register
W DBn FFFFDDDD 0 ~ 40968192
(must be even)
Data Register Double Word
DW DBDn FFFFDDDD 0 ~ 40968192
(must be multiple of 4)
Data Register Double Word
W DBn_String FFFFDDDD 0 ~ 40968192
(must be multiple of 4)
676
PLC Connection Guide
677
PLC Connection Guide
b、 Click Export to export the edited file and click Save.
678
PLC Connection Guide
c、 Select Sources as storage path, specify the file name then click OK.
679
PLC Connection Guide
e、 Under Sources there will be names of the saved files, select Export Source
to build *.AWL file.
680
PLC Connection Guide
Wiring Diagram:
The following represents the cable end connector.
Siemens S7-300 PC Adapter : 9P D-Sub to 9P D-Sub:
eMT3000 series
COM1 RS232 9P COM3 RS232 9P RS232 9P D-Sub Male
D-Sub Female D-Sub Female
2 RX 8 RX 3 TXD
3 TX 7 TX 2 RXD
5 GND 5 GND 5 GND
7 RTS
circuit
8 CTS
MT6050i/MT8050i
COM1 RS232 9P RS232 9P D-Sub Male
D-Sub Female
9 RX 3 TXD
6 TX 2 RXD
5 GND 5 GND
7 RTS
circuit
8 CTS
681
PLC Connection Guide
The following represents the cable end connector.
Systeme Helmholz SSW7-TS : 9P D-Sub to 9P D-Sub
eMT3000 series
COM1 RS232 9P COM3 RS232 9P RS232 9P D-Sub Male
D-Sub Female D-Sub Female
2 RX 8 RX 3 TXD
3 TX 7 TX 2 RXD
5 GND 5 GND 5 GND
7 RTS
circuit
8 CTS
4 DTR
circuit
6 DSR
682
PLC Connection Guide
MT6050i/MT8050i
COM1 RS232 9P RS232 9P D-Sub Male
D-Sub Female
9 RX 3 TXD
6 TX 2 RXD
5 GND 5 GND
7 RTS
circuit
8 CTS
4 DTR
circuit
6 DSR
Driver Version:
Version Date Description
V3.10 May/24/2011 Added registers: MB & DBBn.
683
PLC Connection Guide
Device Address:
Bit/Word Device type Format Range Memo
B I DDDDo 0 ~ 40957 Input (I)
B Q DDDDo 0 ~ 40957 Output (O)
B M DDDDo 0 ~ 40957 Bit Memory
B DBnBit FFFFDDDDo 0 ~ 409699997 Data Register Bit
DB0Bit ~
B DDDDDo 0 ~ 655327 Data Register Bit
DB99Bit
W IW DDDD 0 ~ 4095 Input (I)
W QW DDDD 0 ~ 4095 Output (O)
W MW DDDD 0 ~ 4095 Bit Memory
DW MD DDDD 0 ~ 4094
Byte MB DDDD 0 ~ 4095 Bit Memory Byte
Byte DBBn FFFFDDDD 0 ~ 40969999 Data Register
W DBn FFFFDDDD 0 ~ 40969999 Data Register (must be even)
DW DBDn FFFFDDDD 0 ~ 40969999 Data Register Double Word
W DBn_String FFFFDDDD 0 ~ 40969999
DW DBDn_String FFFFDDDD 0 ~ 40969999
W DB0 ~ DB99 DDDDD 0 ~ 65532 Data Register (must be even)
* Double word and floating point value must use DBDn device type.
684
PLC Connection Guide
685
PLC Connection Guide
For the effectiveness of communication, users may set PLC device in STEP 7 as shown
below. In Properties MPI / Network Settings, set Highest MPI address to the number
closest to the actual device station number.
Note:
■ HMI sta. no. can not be the same as PLC sta. no.
■ Highly recommended that the device station numbers start from 0 sequentially and
correctly set [Max. station no. (MPI network)].
■ Available for EasyBuilder V4.50 and later.
686
PLC Connection Guide
687
PLC Connection Guide
b、 Click Export to export the edited file and click Save.
688
PLC Connection Guide
c、 Select Sources as storage path, specify the file name then click OK.
689
PLC Connection Guide
e、 Under Sources there will be names of the saved files, select Export Source
to build *.AWL file.
690
PLC Connection Guide
Wiring Diagram:
The following represents the cable end connector.
S7-200 PPI , S7-300 MPI :RS485 2W
eMT3000 series
COM1 RS485 2W COM3 RS485 2W RS485 2W 9P D-Sub
9P D-Sub Male 9P D-Sub Male Male
1 RX- 6 Data- 8 D-
2 RX+ 9 Data+ 3 D+
5 GND 5 GND 5 GND
MT6050i/MT8050i
COM1 RS485 2W COM3 RS485 2W RS485 2W 9P D-Sub
9P D-Sub Female 9P D-Sub Female Male
1 RX- 7 Data- 8 D-
2 RX+ 8 Data+ 3 D+
5 GND 5 GND 5 GND
Driver Version:
Version Date Description
V1.90 May/26/2011 Added registers: MB & DBBn
i Series HMI support Multi HMIs-Multi PLCs
V2.00 Aug/19d/2011
communication.
691
PLC Connection Guide
Device Address:
Bit/Word Device type Format Range Memo
B I DDDDo 0 ~ 40957 Input (I)
B Q DDDDo 0 ~ 40957 Output (O)
B M DDDDo 0 ~ 40957 Bit Memory
B DBnBit FFFFDDDDo 0 ~ 409699997
B DB0Bit-DB99Bit DDDDDo 0 ~ 655327 Data Register Bit
W IW DDDD 0 ~ 4095 Input (I)
W QW DDDD 0 ~ 4095 Output (O)
W MW DDDD 0 ~ 4095 Bit Memory
DW MD DDDD 0 ~ 4094
Data Register
W DBn FFFFDDDD 0 ~ 40969999
(must be even)
Data Register Double Word
DW DBDn FFFFDDDD 0 ~ 40969999
(must be multiple of 4)
W DBn_String FFFFDDDD 0 ~ 40969999
DW DBDn_String FFFFDDDD 0 ~ 40969999
W DB0 ~ DB99 DDDDD 0 ~ 65532 Data Register
Byte MB DDDD 0 ~ 4095 (must
Bit be even)
Memory Byte
Byte DBBn FFFFDDDD 0 ~ 40969999 Data Register Byte
* Double word and floating point value must use DBDn device type.
692
PLC Connection Guide
Wiring Diagram:
Direct connect (crossover cable):
HMI RJ45 Male Wire Color PLC RJ45 Male
1 TX+ White/Orange 3 RX+
2 TX- Orange 6 RX-
3 RX+ White/Green 1 TX+
4 BD4+ Blue 4 BD4+
5 BD4- White/Blue 5 BD4-
6 RX- Green 2 TX-
7 BD3+ White/Brown 7 BD3+
8 BD3- Brown 8 BD3-
Through a hub:
HMI RJ45 Male Wire Color PLC RJ45 Male
1 TX+ White/Orange 1 TX+
2 TX- Orange 2 TX-
3 RX+ White/Green 3 RX+
4 BD4+ Blue 4 BD4+
5 BD4- White/Blue 5 BD4-
6 RX- Green 6 RX-
7 BD3+ White/Brown 7 BD3+
8 BD3- Brown 8 BD3-
693
PLC Connection Guide
1.
2.
4. Press [Settings].
5. Set S7-400 IP, Port no., Link type, Rack and CPU slot. (must match PLC settings)
694
PLC Connection Guide
6. The setting will be finished as below.
695
PLC Connection Guide
b、 Click Export to export the edited file and click Save.
696
PLC Connection Guide
c、 Select Sources as storage path, specify the file name then click OK.
697
PLC Connection Guide
e、 Under Sources there will be names of the saved files, select Export Source
to build *.AWL file.
Driver Version:
Version Date Description
V1.40 May/25/2011 Added registers: MB & DBBn
698
PLC Connection Guide
HMI Setting:
Parameters Recommended Options Notes
PLC type VIPA 300S, for ex. 315-4NE12 (Ethernet)
PLC I/F Ethernet
Port no. 102
PLC sta. no. 1 0-31
Device Address:
Bit/Word Device type Format Range Memo
B I DDDDo 0 ~ 40957 Input (I)
B Q DDDDo 0 ~ 40957 Output (O)
B M DDDDo 0 ~ 40957 Bit Memory
B DBnBit FFFFDDDDo 0 ~ 409699997
B DB0Bit-DB99Bit DDDDDo 0 ~ 655327 Data Register Bit
W IW DDDD 0 ~ 4095 Input (I)
W QW DDDD 0 ~ 4095 Output (O)
W MW DDDD 0 ~ 4095 Bit Memory
DW MD DDDD 0 ~ 4094 Bit Memory Double Word
Data Register
W DBn FFFFDDDD 0 ~ 40969999
(must be even)
Data Register Double Word
DW DBDn FFFFDDDD 0 ~ 40969999
(must be multiple of 4)
W DBn_String FFFFDDDD 0 ~ 40969999
DW DBDn_String FFFFDDDD 0 ~ 40969999
Data Register
W DB0 ~ DB99 DDDDD 0 ~ 65532
(must be even)
Byte MB DDDD 0 ~ 4095 Bit Memory Byte
Byte DBBn FFFFDDDD 0 ~ 40969999 Data Register Byte
Double word and floating point value must use DBDn device type.
699
PLC Connection Guide
700
PLC Connection Guide
b、 Click Export to export the edited file and click Save.
701
PLC Connection Guide
c、 Select Sources as storage path, specify the file name then click OK.
702
PLC Connection Guide
e、 Under Sources there will be names of the saved files, select Export Source
to build *.AWL file.
703
PLC Connection Guide
Wiring Diagram:
Direct connect (crossover cable):
HMI RJ45 Male Wire Color PLC RJ45 Male
1 TX+ White/Orange 3 RX+
2 TX- Orange 6 RX-
3 RX+ White/Green 1 TX+
4 BD4+ Blue 4 BD4+
5 BD4- White/Blue 5 BD4-
6 RX- Green 2 TX-
7 BD3+ White/Brown 7 BD3+
8 BD3- Brown 8 BD3-
Through a hub:
HMI RJ45 Male Wire Color PLC RJ45 Male
1 TX+ White/Orange 1 TX+
2 TX- Orange 2 TX-
3 RX+ White/Green 3 RX+
4 BD4+ Blue 4 BD4+
5 BD4- White/Blue 5 BD4-
6 RX- Green 6 RX-
7 BD3+ White/Brown 7 BD3+
8 BD3- Brown 8 BD3-
Driver Version:
Version Date Description
V2.10 May/21/2011 Added registers: MB & DBBn.
704
PLC Connection Guide
XINJE XC Series
Supported Series: XINJE XC Series
Website: http://www.xinje.com/0/index.html
HMI Setting:
Parameters Recommended Options Notes
PLC type XINJE XC Series
PLC I/F RS232 RS232
Baud rate 19200
Data bits 8
Parity Even
Stop bits 1
PLC sta. no. 1 0-255
Device Address:
Bit/Word Device type Format Range Memo
B M DDDD 0 ~ 8511
B X OOOO 0 ~ 1037
B Y OOOO 0 ~ 1037
B S DDDD 0 ~ 1023
B T DDD 0 ~ 618
B C DDD 0 ~ 634
W D DDDD 0 ~ 8511
W TD DDD 0 ~ 618
W CD DDD 0 ~ 634
W FD_1 DDDD 0 ~ 5000
W FD_2 DDDD 8000 ~ 8511
705
PLC Connection Guide
Wiring Diagram:
The following represents the cable end connector.
Driver Version: eMT3000 series
COM1 RS232 9P COM3 RS232 9P RS232 8P Mini-Din
D-Sub Female D-Sub Female Male
2 RX 8 RX 5 TX
3 TX 7 TX 4 RX
5 GND 5 GND 8 GND
MT6050i/MT8050i
COM1 RS232 9P RS232 8P Mini-Din
D-Sub Female Male
9 RX 5 TX
6 TX 4 RX
5 GND 8 GND
706
PLC Connection Guide
YAMAHA ERCD
HMI Setting:
Device Address:
Bit/Word Device type Format Range Memo
Word P DDD 0 ~ 999 Read/Write, PNT point data
Write only,RW0=program
Word SWI D 0 number,Switches program number
to run
Word ORG D 0 Write only,returns to origin
Word RESET D 0 Write only,reset program
Write only,starts automatic
Word RUN D 0
operation
Word X_ADD D 0 Write only,X+ command
Word X_SUB D 0 Write only,X- command
Write only,directly moves to
specified position
Word MOVD D 0
RW1=X-axis position(mm),
RW2=speed
707
PLC Connection Guide
Wiring Diagram:
The following represents the cable end connector.
eMT3000 series
COM1 RS232 9P COM3 RS232 9P RS232 9P D-Sub Male
D-Sub Female D-Sub Female
2 RX 8 RX 3 TX
3 TX 7 TX 2 RX
5 GND 5 GND 5 GND
7 RTS
circuit
8 CTS
MT6050i/MT8050i
COM1 RS232 9P RS232 9P D-Sub Male
D-Sub Female
9 RX 3 TX
6 TX 2 RX
5 GND 5 GND
7 RTS
circuit
8 CTS
708
PLC Connection Guide
Driver Version:
Version Date Description
V1.30 Jan/04/2010
709
PLC Connection Guide
YASKAWA CCMEP
Supported Series: YASKAWA CCMEP-100/ CCMEP-200
Website http://www.yaskawa.co.jp
HMI Setting:
Parameters Recommended Options Notes
PLC type YASKAWA CCMEP
PLC I/F RS485 4W
Baud rate 38400
Data bits 8
Parity Even
Stop bits 1
PLC sta. no. 1
Device Address:
Bit/Word Device type Format Range Memo
B 4_Bit DDDDDdd 100 ~ 6553515
W 4 DDDDD 1 ~ 65535
Wiring Diagram:
The following represents the cable end connector.
eMT3000 series
COM1 RS485 4W RS485 4W 8P RJ45
9P D-Sub Male Male
1 RX- 4 TX-
2 RX+ 3 TX+
3 TX- 2 RX-
4 TX+ 1 RX+
5 GND 8 GND
710
PLC Connection Guide
MT6000/8000 series except MT6050i/MT8050i
COM1 RS485 4W RS485 4W 8P RJ45
9P D-Sub Male Male
1 RX- 4 TX-
2 RX+ 3 TX+
3 TX- 2 RX-
4 TX+ 1 RX+
5 GND 8 GND
MT6050i/MT8050i
COM1 RS485 4W RS485 4W 8P RJ45
9P D-Sub Female Male
1 RX- 4 TX-
2 RX+ 3 TX+
3 TX- 2 RX-
4 TX+ 1 RX+
5 GND 8 GND
Driver Version:
Version Date Description
V1.00 Jun/14/2012 Driver released.
711
PLC Connection Guide
HMI Setting:
Parameters Recommended Options Notes
PLC type YASKAWA Memobus (MP Series Controllers)
RS232/RS485 2w/4w,
PLC I/F RS485/Ethernet
Ethernet
Baud rate 19200 9600~57600
Data bits 8
Parity Even
Stop bits 1
Port no. 502 default Ethernet Module Only
PLC sta. no. 1 1-31
PLC Setting:
Communication mode MEMOBUS, Slave, RTU
712
PLC Connection Guide
2. In Transmision Parameters input MP2300S IP address, Subnet Mask, Gateway IP.
In Connection Parameter, CNO -1 input: Local Port=502, Node IP
address=000.000.000.000, Node Port=00000, Connect Type=TCP, Protocol
Type=MEMOBUS, Code=RTU.
713
PLC Connection Guide
Note:
1. Only CNO 01 can auto communicate with one HMI. Other CNO need a ladder program
created for communication.
2. DIP SW2-2 of MP2300S must be set to OFF position during normal communication,
otherwise, IP address will be erased after reset power, and it will be unable to
communicate with HMI when set to ON position.
Device Address:
Bit/Word Device type Format Range Memo
B MB_1 DDDDh 0 ~ 9999f MB 0 ~ 9999
B MB_2 DDDDDh 100000 ~ 65534f MB 10000 ~ 65535
B IB HHHHH 0 ~ a7ff0 Read only
B IW_Bit HHHHdd 0~ a7ff15
W IW HHHH 0 ~ a7ff Read only
DW IL HHHH 0 ~ a7ff Read only
DW (F) IF HHHH 0 ~ a7ff Read only
W MW DDDDD 0 ~ 65534 Holding register
DW ML DDDDD 0 ~ 65533 Double word
DW (F) MF DDDDD 0 ~ 65533 Floating point
*: When connect via Ethernet interface the max range of IW, IL and IF would be restricted.
Wiring Diagram:
The following represents the cable end connector.
9P D-Sub to 9P D-Sub: 217IF-01, 218IF-01
eMT3000 series
COM1 RS232 9P COM3 RS232 9P RS232 9P D-Sub Male
D-Sub Female D-Sub Female
2 RX 8 RX 2 TX
3 TX 7 TX 3 RX
5 GND 5 GND 7 GND
714
PLC Connection Guide
MT6000/8000 series except MT6050i/MT8050i
COM1 RS232 9P COM2 RS232 9P COM3 RS232 9P RS232 9P D-Sub Male
D-Sub Female D-Sub Female D-Sub Male
2 RX 6 RX 8 RX 2 TX
3 TX 4 TX 7 TX 3 RX
5 GND 5 GND 5 GND 7 GND
MT6050i/MT8050i
COM1 RS232 9P RS232 9P D-Sub Male
D-Sub Female
9 RX 2 TX
6 TX 3 RX
5 GND 7 GND
715
PLC Connection Guide
MT6000/8000 series except MT6050i/MT8050i
COM1 RS485 2W COM3 RS485 2W 217IF-01 RS485 14P
9P D-Sub Male 9P D-Sub Male Connector
1 RX- 6 Data- 2, 4 D-
2 RX+ 9 Data+ 1, 3 D+
5 GND 5 GND 14 GND
MT6050i/MT8050i
COM1 RS485 2W COM3 RS485 2W 217IF-01 RS485 14P
9P D-Sub Female 9P D-Sub Female Connector
1 RX- 7 Data- 2, 4 D-
2 RX+ 8 Data+ 1, 3 D+
5 GND 5 GND 14 GND
716
PLC Connection Guide
MT6000/8000 series except MT6050i/MT8050i
COM1 RS485 4W 217IF-01 RS422 14P
9P D-Sub Male Connector
1 RX- 2 TX-
2 RX+ 1 TX+
3 TX- 4 RX-
4 TX+ 3 RX+
5 GND 14 GND
MT6050i/MT8050i
COM1 RS485 4W 217IF-01 RS422 14P
9P D-Sub Female Connector
1 RX- 2 TX-
2 RX+ 1 TX+
3 TX- 4 RX-
4 TX+ 3 RX+
5 GND 14 GND
717
PLC Connection Guide
Through a hub:
HMI RJ45 Male Wire Color PLC RJ45 Male
1 TX+ White/Orange 1 TX+
2 TX- Orange 2 TX-
3 RX+ White/Green 3 RX+
4 BD4+ Blue 4 BD4+
5 BD4- White/Blue 5 BD4-
6 RX- Green 6 RX-
7 BD3+ White/Brown 7 BD3+
8 BD3- Brown 8 BD3-
Driver Version:
Version Date Description
V1.70 Dec/20/2010
718
PLC Connection Guide
HMI Setting:
Parameters Recommended Options Notes
PLC type YASKAWA MP Series Ethernet (Extension)
PLC I/F Ethernet (UDP)
Port no. 10000
PLC sta. no. 1
PLC Setting:
Yaskawa PLC Communication Parameter Settings
(1) PLC Factory Communication Parameter Settings:
Item Set
IP Address 192.168.1.1
Subnet Mask 255.255.255.0
Gateway IP Address 0.0.0.0
System Port No. 10000 (UDP)
TCP Zero Window Timer Value 3 (s)
TCP Retry Time 500 (ms)
TCP Close Time 60 (s)
IP Assemble Time 30 (s)
Max. Packet Length 1500 (bytes)
719
PLC Connection Guide
2. Communication parameter setting.
3. Go to Module Details and select [218IFA] for setting relevant parameters for Ethernet
transmission.
720
PLC Connection Guide
5. Download PLC communication parameters to PLC, and restart the controller.
721
PLC Connection Guide
Device Address:
Bit/Word Device type Format Range Memo
B SB DDDDh 0 ~ 8191f
B IB HHHHh 0 ~ fffff
B OB HHHHh 0 ~ fffff
B MB DDDDDh 0 ~ 65534f
W SW DDDD 0 ~ 8191
W IW HHHH 0 ~ ffff
W OW HHHH 0 ~ ffff
W MW DDDDD 0 ~ 65534
Wiring Diagram:
Direct connect (crossover cable):
HMI RJ45 Male Wire Color PLC RJ45 Male
1 TX+ White/Orange 3 RX+
2 TX- Orange 6 RX-
3 RX+ White/Green 1 TX+
4 BD4+ Blue 4 BD4+
5 BD4- White/Blue 5 BD4-
6 RX- Green 2 TX-
7 BD3+ White/Brown 7 BD3+
8 BD3- Brown 8 BD3-
722
PLC Connection Guide
Through a hub:
HMI RJ45 Male Wire Color PLC RJ45 Male
1 TX+ White/Orange 1 TX+
2 TX- Orange 2 TX-
3 RX+ White/Green 3 RX+
4 BD4+ Blue 4 BD4+
5 BD4- White/Blue 5 BD4-
6 RX- Green 6 RX-
7 BD3+ White/Brown 7 BD3+
8 BD3- Brown 8 BD3-
Driver Version:
Version Date Description
V1.10 Jul/21/2011 Driver released.
723
PLC Connection Guide
YASKAWA MP2300Siec
Website: http://www.yaskawa.com/site/home.nsf/home/home.html
HMI Setting:
Parameters Recommended Options Notes
PLC type YASKAWA MP2300Siec
PLC I/F Ethernet
Port no. 44818
Assembly Input::101 Input::101~106
instance Output:111 Output:111~116
PLC sta. no. 1
PLC Setting:
MP2300Siec-Motion Works IEC Express (YASKAWA) Settings:
Step 1. Before HMI communicates with MP2300Siec using Ethernet/IP, the Instance Input
and Instance Output of MP2300Siec device must be set correctly. Multiple Instances are
allowed to be built at one time, please click [Save] after setting.
724
PLC Connection Guide
Step 2.Global Variables will automatically add in E/IP Input and Output data, Input and
Output data name and address type can be user-defined.
725
PLC Connection Guide
726
PLC Connection Guide
Step 5. Download project to device- MP2300Siec, and execute Cold.
727
PLC Connection Guide
Step 1. In EasyBuilder8000/EasyBuilder Pro project, when using Allen Bradley EIP driver
to import CSV file (as in Fig. 10), please open AB Data Type Editor (Fig. 11), and right click
on Module Defined to add New Data Type.
728
PLC Connection Guide
Fig. 10 RSLogix 5000 (Allen Bradley Software) Export Free Tag CSV File
Step 2. As in Fig 12, in AB Data Type Editor add Name of the new data type. The Name
must be set identically to the Data Type in Free Tag CSV file. As in Fig 14, Data Member
Name must be set identically to the AB software (as Data in Fig. 13), then click [Save] (Fig.
15).
729
PLC Connection Guide
730
PLC Connection Guide
Step 3. Import CSV file, Tag Information can be viewed from object address.
Device Address:
Bit/Word Device type Format Range Memo
B Input_Bit DDDDDdd 0 ~ 6553515
B Output_Bit DDDDDdd 0 ~ 6553515
DW Input DDDDD 0 ~ 65535
DW Output DDDDD 0 ~ 65535
731
PLC Connection Guide
Wiring Diagram:
Direct connect (crossover cable):
HMI RJ45 Male Wire Color PLC RJ45 Male
1 TX+ White/Orange 3 RX+
2 TX- Orange 6 RX-
3 RX+ White/Green 1 TX+
4 BD4+ Blue 4 BD4+
5 BD4- White/Blue 5 BD4-
6 RX- Green 2 TX-
7 BD3+ White/Brown 7 BD3+
8 BD3- Brown 8 BD3-
Through a hub:
HMI RJ45 Male Wire Color PLC RJ45 Male
1 TX+ White/Orange 1 TX+
2 TX- Orange 2 TX-
3 RX+ White/Green 3 RX+
4 BD4+ Blue 4 BD4+
5 BD4- White/Blue 5 BD4-
6 RX- Green 6 RX-
7 BD3+ White/Brown 7 BD3+
8 BD3- Brown 8 BD3-
Note: The wiring diagrams above are drawn based on MT8100i structure, the actual
placement of pins may vary according to HMI module.
Driver Version:
Version Date Description
V1.00 Aug/24/2011 Driver released.
732
PLC Connection Guide
HMI Setting:
Parameters Recommended Options Notes
PLC type YASKAWA SMC 3010
PLC I/F RS232
Baud rate 19200 9600, 19200
Data bits 8
Parity None
Stop bits 1
Device Address:
Bit/Word Device type Format Range Memo
B AF D 0~1
B BN D 0~1 Write only
B BP D 0~1 Write only
B BV D 0~1 Write only
B CB DDDD 0 ~ 9999 Write only
B CM D 0~1 Read only
B DV D 0~1
B EB D 0~1
B OE D 0~1
B RS D 0~1 Write only
B ST D 0~1 Write only
B TB Do 0 ~ 17 Read only
B V_Bit DDDdd 0 ~ 99931 *2
B D_arr_Bit DDDdd 0 ~ 99931
DW AC D 0~4
DW DC D 0~4
DW BL D 0~4
W CD D 0~2 Write only
W CE D 0~2
733
PLC Connection Guide
Bit/Word Device type Format Range Memo
DW DE D 0~4
DW DP D 0~4
W DT D 0~2
W EC D 0~2
DW EM D 0~4
W ER D 0~2
W FA D 0~2
DW FL D 0~4
W FV D 0~2
DW GR D 0~4
DW JG D 0~4
DW MM D 0~4
W MT D 0~2
W NA D 0~2
W OP D 0~2
DW PA D 0~4 Write only
DW PR D 0~4
DW SP D 0~4
W TC D 0~2 Read only
W TM D 0~2
W TW D 0~2
DW VA D 0~4
DW VD D 0~4
DW VS D 0~4
DW IL D 0~4
DW IT D 0~4
DW KD D 0~4
DW KI D 0~4
DW KP D 0~4
DW OF D 0~4
DW TL D 0~4
DW VR D 0~4
DW VT D 0~4
DW PF D 0~4 *1
DW VF D 0~4
734
PLC Connection Guide
Bit/Word Device type Format Range Memo
DW V DDD 0 ~ 999 *2
F F DDD 0 ~ 999 *2
W D_array DDD 0 ~ 999
W R_array DDD 0 ~ 999
Note:
*1 PF is the communication parameter of SMC_3010, the default is 10.4, if the value is not 10.4, all values
will be displayed incorrectly.
*2 User defined integer variable V000~V999, floating point variable F000~F999.
Wiring Diagram:
The following represents the cable end connector.
eMT3000 series
COM1 RS232 9P COM3 RS232 9P SMC3010 CN6 RS232
D-Sub Female D-Sub Female 9P D-Sub Male
2 RX 8 RX 2 TXD
3 TX 7 TX 3 RXD
5 GND 5 GND 5 GND
7 RTS
circuit
8 CTS
735
PLC Connection Guide
MT6050i/MT8050i
COM1 RS232 9P SMC3010 CN6 RS232
D-Sub Female 9P D-Sub Male
9 RX 2 TXD
6 TX 3 RXD
5 GND 5 GND
7 RTS
circuit
8 CTS
Driver Version:
Version Date Description
V1.30 Mar/29/2010
736
PLC Connection Guide
HMI Setting:
Parameters Recommended Options Notes
PLC type YASKAWA SMC 3010 (Ethernet)
PLC I/F Ethernet
Port no. 23
Device Address:
Bit/Word Device type Format Range Memo
B AF D 0~1
B BN D 0~1 Write only
B BP D 0~1 Write only
B BV D 0~1 Write only
B CB DDDD 0 ~ 9999 Write only
B CM D 0~1 Read only
B DV D 0~1
B EB D 0~1
B OE D 0~1
B RS D 0~1 Write only
B ST D 0~1 Write only
B TB Do 0 ~ 17 Read only
B V_Bit DDDdd 0 ~ 99931 *2
B D_arr_Bit DDDdd 0 ~ 99931
DW AC D 0~4
DW DC D 0~4
DW BL D 0~4
W CD D 0~2 Write only
W CE D 0~2
DW DE D 0~4
DW DP D 0~4
W DT D 0~2
W EC D 0~2
737
PLC Connection Guide
Bit/Word Device type Format Range Memo
DW EM D 0~4
W ER D 0~2
W FA D 0~2
DW FL D 0~4
W FV D 0~2
DW GR D 0~4
DW JG D 0~4
DW MM D 0~4
W MT D 0~2
W NA D 0~2
W OP D 0~2
DW PA D 0~4 Write only
DW PR D 0~4
DW SP D 0~4
W TC D 0~2 Read only
W TM D 0~2
W TW D 0~2
DW VA D 0~4
DW VD D 0~4
DW VS D 0~4
DW IL D 0~4
DW IT D 0~4
DW KD D 0~4
DW KI D 0~4
DW KP D 0~4
DW OF D 0~4
DW TL D 0~4
DW VR D 0~4
DW VT D 0~4
DW PF D 0~4 *1
DW VF D 0~4
DW V DDD 0 ~ 999 *2
W F DDD 0 ~ 999 *2
W D_array DDD 0 ~ 999
W R_array DDD 0 ~ 999
738
PLC Connection Guide
Note:
*1 PF is the communication parameter of SMC_3010, the default is 10.4, if the value is not
10.4, all values will be displayed incorrectly.
*2 User defined integer variable V000~V999, floating point variable F000~F999.
Wiring Diagram:
Direct connect (crossover cable):
HMI RJ45 Male Wire Color PLC RJ45 Male
1 TX+ White/Orange 3 RX+
2 TX- Orange 6 RX-
3 RX+ White/Green 1 TX+
4 BD4+ Blue 4 BD4+
5 BD4- White/Blue 5 BD4-
6 RX- Green 2 TX-
7 BD3+ White/Brown 7 BD3+
8 BD3- Brown 8 BD3-
Through a hub:
HMI RJ45 Male Wire Color PLC RJ45 Male
1 TX+ White/Orange 1 TX+
2 TX- Orange 2 TX-
3 RX+ White/Green 3 RX+
4 BD4+ Blue 4 BD4+
5 BD4- White/Blue 5 BD4-
6 RX- Green 6 RX-
7 BD3+ White/Brown 7 BD3+
8 BD3- Brown 8 BD3-
Driver Version:
Version Date Description
V1.10 Mar/29/2010
739
PLC Connection Guide
YOKOGAWA FA-M3
Supported Series : FA-M3 CPU SP35-5N, SP55-5N CPU port, F3LC11 Computer Link
module.
Website : http://www.yokogawa.com/itc/itc-index-en.htm
HMI Setting:
Parameters Recommended Options Notes
PLC type YOKOGAWA FA-M3
PLC I/F RS232
Baud rate 19200 9600, 19200
Data bits 8 8
Parity Even Even, Odd, None
Stop bits 1 1
PLC sta. no. 1 1-31
PLC Setting:
Use Personal Communication Link
Communication mode Use checksum
Use End Character
740
PLC Connection Guide
P.S Since Personal Computer link is used, when connecting to PLC it will delay about
20sec for testing communication.
741
PLC Connection Guide
Click [Configuration] to set up communication.
Device Address:
Bit/Word Device type Format Range Memo
B X DDDDD 0 ~ 71664
B Y DDDDD 0 ~ 71664
B I DDDDD 1 ~ 16384
B M DDDD 1 ~ 9984
B L DDDDD 0 ~ 78192
W D DDDDD 1 ~ 16384
W B DDDDD 1 ~ 32768
W V DDD 1 ~ 256
W W DDDDD 1 ~ 71024
W Z DDDD 1 ~ 1024
742
PLC Connection Guide
Wiring Diagram:
The following represents the cable end connector.
9P D-Sub to 9P D-Sub: Cable KM11
eMT3000 series
COM1 RS232 9P COM3 RS232 9P RS232 9P D-Sub Male
D-Sub Female D-Sub Female
2 RX 8 RX 2 TXD
3 TX 7 TX 3 RXD
5 GND 5 GND 5 GND
MT6050i/MT8050i
COM1 RS232 9P RS232 9P D-Sub Male
D-Sub Female
9 RX 2 TXD
6 TX 3 RXD
5 GND 5 GND
743
PLC Connection Guide
The following represents the cable end connector.
9P D-Sub to 9P D-Sub: LC11
eMT3000 series
COM1 RS232 9P COM3 RS232 9P RS232 9P D-Sub Male
D-Sub Female D-Sub Female
2 RX 8 RX 3 TXD
3 TX 7 TX 2 RXD
5 GND 5 GND 5 GND
7 RTS
circuit
8 CTS
MT6050i/MT8050i
COM1 RS232 9P RS232 9P D-Sub Male
D-Sub Female
9 RX 3 TXD
6 TX 2 RXD
5 GND 5 GND
7 RTS
circuit
8 CTS
744
PLC Connection Guide
Driver Version:
Version Date Description
V1.20 Oct/23/2009
V1.30 May/31/2012 Extended address L range up to 78192.
745
PLC Connection Guide
HMI Setting:
Parameters Recommended Options Notes
PLC type YOKOGAWA FA-M3 (Ethernet)
PLC I/F Ethernet
Port no. 12289
PLC sta. no. 1
PLC Setting:
Communication mode Set IP Address, and set all condition setup switch to OFF.
Device Address:
Bit/Word Device type Format Range Memo
B X DDDDD 0 ~ 71664
B Y DDDDD 0 ~ 71664
B I DDDDD 1 ~ 16384
B M DDDD 1 ~ 9984
B L DDDDD 0 ~ 78192
W D DDDD 1 ~ 8192
W B DDDDD 1 ~ 32768
W V DD 1 ~ 64
W W DDDDD 1 ~ 71024
W Z DDD 1 ~ 512
746
PLC Connection Guide
Wiring Diagram:
Direct connect (crossover cable):
HMI RJ45 Male Wire Color PLC RJ45 Male
1 TX+ White/Orange 3 RX+
2 TX- Orange 6 RX-
3 RX+ White/Green 1 TX+
4 BD4+ Blue 4 BD4+
5 BD4- White/Blue 5 BD4-
6 RX- Green 2 TX-
7 BD3+ White/Brown 7 BD3+
8 BD3- Brown 8 BD3-
Through a hub:
HMI RJ45 Male Wire Color PLC RJ45 Male
1 TX+ White/Orange 1 TX+
2 TX- Orange 2 TX-
3 RX+ White/Green 3 RX+
4 BD4+ Blue 4 BD4+
5 BD4- White/Blue 5 BD4-
6 RX- Green 6 RX-
7 BD3+ White/Brown 7 BD3+
8 BD3- Brown 8 BD3-
Driver Version:
Version Date Description
V1.00 Dec/30/2008 Driver released.
V1.10 May/31/2012 Extended address L range up to 78192.
747
PLC Connection Guide
YUDIAN AIBUS
Supported Series: UDIAN Automation AI-501, AI-518, AI-519, AI-701, AI-702M, AI-704M,
AI-706M, AI-719.
Website: http://www.yudian.us
HMI Setting:
Parameters Recommended Options Notes
PLC type AIBUS
PLC I/F RS485 2W RS232
Baud rate 9600 9600, 19200
Data bits 8
Parity None
Stop bits 2
HMI sta. no. 0
PLC sta. no. 1 0-100
Device Address:
AI-518
748
PLC Connection Guide
AI-701
Bit/Word Device type Format Range Memo
W 1 01H DD -9990 ~ 30000 HIAL
W 2 02H DD -9990 ~ 30000 LoAL
W 3 03H DD -9990 ~ 30000 HdAL
W 4 04H DD -9990 ~ 30000 LdAL
W 5 05H DD 0 ~ 2000 AHYS
W 11 0BH DD 0 ~ 37 InP (read only)
W 12 0CH DD 0~3 dPt
W 13 0DH DD -9999 ~ 30000 SCL
W 14 0EH DD -9999 ~ 30000 SCH
W 15 0FH DD 0 ~ 4444 AOP
-1999 ~ 4000
W 16 10H DD Scb
0.1℃
749
PLC Connection Guide
Bit/Word Device type Format Range Memo
W 17 11H DD 0 ~ 48 Opt
Baud rate(bAud)
/808P status word
W 21 15H DD 0 ~ 19.2K
run: 0 suspend: 4 stop: 12
(read only)
W 22 16H DD 0 ~ 80 ADDR
W 23 17H DD 0 ~ 40 FILt
W 25 19H DD 0 ~ 255 Loc
Wiring Diagram:
The following represents the cable end connector.
eMT3000 series
COM1 RS485 2W COM3 RS485 2W RS485 2W terminal
9P D-Sub Male 9P D-Sub Male
1 RX- 6 Data- 4 COMM A
2 RX+ 9 Data+ 3 COMM B
5 GND 5 GND
750
PLC Connection Guide
MT6050i/MT8050i
COM1 RS485 2W COM3 RS485 2W RS485 2W terminal
9P D-Sub Female 9P D-Sub Female
1 RX- 7 Data- 4 COMM A
2 RX+ 8 Data+ 3 COMM B
5 GND 5 GND
Driver Version:
Version Date Description
V1.20 Dec/30/2008
751
PLC Connection Guide
C O M C P U P W R
Bottom View
Front View
MT6050i/MT8050i
Pin assignment of the 9 Pin, Male,
Pin assignment of the 9 Pin, Male, SUB-D, COM1 [RS-232]/ [RS-485], COM3 [RS-485] Port. Only
Com1[RS485 2W] support MPI 187.5K.
Pin# Symbol Com1[RS485] Com1[RS232] Com3[RS485]
4 wire R e s e t
D I P S W
2 wire
Cutout dimensions:
1 Rx- Rx- Data- MT-6050i:
119mm [4.685"] W x 93mm [3.661"] H
2 Rx+ Rx+ Data+
3 Tx-
+ --
--
Tx- C O M
4 Tx+ Tx+
Rear View
5 GND GND
6 TxD Transmit
7 Data- Data-
8 Data+ Data+
9 RxD Receive
752
PLC Connection Guide
Wiring Diagram:
MT6050i COM1 [RS-232] PLC RS-232
9P D-SUB Female Communication Com Port interface
9 RXD TXD
6 TXD RXD
5 GND GND
753